ITEM 124
115 Cable
CU/XLPE/CTS/PVC/SWA/PVC
D1 - rev:00 3.6/6 kV
Date : 25.03.2021
M.V. POWER CABLE Max core temperature: 90°C
Design
1 Conductor 6 Separation sheath
Stranded annealed round Polyvinyl Chloride (PVC)
plain copper (Class 2) coloured natural
2 Conductor screen 7 Metallic armour
Extruded semi-conductor Galvanized steel wires (GSWA)
3 Insulation 8 Protective sheath
Cross-linked polyethylene (XLPE) Polyvinyl Chloride (PVC)
coloured red
4 Insulation screen
Extruded semi-conductor (Strippable)
Copper tape
(coverage: 100%)
5 Assembling
Inner covering acting as a
filler with practically
zero thickness
Marking (embossed) Core identification Standards
(Two lines embossed marking) 3x: red-yellow-blue IEC 60228
(by tape under copper screen) IEC 60502
NEXANS IEC 60502 IEC 60332-3-22
CU/XLPE/CTS/PVC/SWA/PVC
<Nb of cores & x-section> 3.6/6
kV 2021
+ METER MARKING
Ambient Good Oil&Hydrocarbon Flame retardant U.V. resistant
Temperature Resistant IEC 60332-3-22 ISO 4892-2
-20°C / +60°C (CAT A)
1/8
D1 - rev:00
THEORETICAL SIZE CHARACTERISTICS THEORETICAL ELECTRICAL CHARACTERISTICS
Current ratings based on IEC 60502-2
Conditions for installation underground (Single cable) - Thermal resistivity of soil: 1.5 K.m/W - Burying depth: 0.8 m
Conditions for installation in air (Single cable) - Horizontal
CONDUCTOR INSULATION ARMOUR PROTECTIVE SHEATH BENDING RESISTANCE CURRENT RATING REACTANCE SHORT-CIRCUIT CURRENT VOLTAGE DROP IMPEDANCE
POS N° NEXANS N° DESIGNATION STANDARD VOLTAGE SECTION Class Diam. Thickness Thickness Diam. Thickness Outer Diameter RADIUS WEIGHT DC AC in free air underground 50Hz 0.3 s 1s AC 50Hz
RATE (approx) (nominal) (nominal) (approx.) (min.) (min.) (max.) (minimum) (approx.) at 20°C at Max°C at 30°C at 20°C approx. maximum maximum approx. approx.
mm² # mm mm mm mm mm mm mm mm kg/km /km /km A A /km kA kA V/A.km /km
1 60612658 CU/XLPE/CTS/PVC/SWA/PVC IEC 60502 3.6/6 kV 3x50 Class 2 8.1 2.5 2.5 * 1.80 46.6 51.5 588 4940 0.387 0.497 205 158 0.10 13.1 7.15 0.9 0.505
2/8