HMOP
HMOP
TMN 01/119E
Date 2001. .
General Manager of
Hardware Laboratory
Your information
FANUC Robotics
MILACRON
Sales agency
○ End user
3. Notice
New Feature Release Statement was issued at the end of May in 2001.
The interface unit for Handy machine operator’s panel is necessary for connecting to CNC.
Specification and Connection materials were modified. And, Maintenance and PMC Programming
materials were added newly.
4. Attached Document
Drawing
A-80050E ( 59 pages)
No.
Table of Contents
Specification
1. Outline ..................................................................................................................4
2. Specification ........................................................................................................4
4. Environmental requirements..............................................................................5
5. External figure......................................................................................................6
5.1 Handy machine operator’s panel.............................................................. 6
5.2 Interface unit ............................................................................................. 7
6. System diagram ...................................................................................................8
6.1 In the case of keeping unit always ........................................................... 8
6.2 In the case of detachable connecting........................................................ 8
7. Emergency stop circuit .......................................................................................9
8. Connection panel...............................................................................................10
Maintenance
1. Fuse. ...................................................................................................................26
3. Error message....................................................................................................27
PMC Programming
1. Preface................................................................................................................28
TITLE
TITLE
2. Specification
Manual pulse Including
generator
Display LCD 16 characters × 2 lines
Input key 20 (with LED)
LED User programmable LED × 2, system LED × 2
Key sheet FANUC standard key sheet is provided.
Customization of key sheet is possible with user’s order.
And it can be customized simply with putting their seals.
Operation ON/OFF Including
switch
Rotary switch 16 positions (for override)
Emergency stop button 2 contacts
Enabling switch 2 contacts , 3 positions
Interface FANUC I/O Link via interface unit
Additional circuit is provided to emergency stop system.
Cable length Between handy machine operator’s panel and interface unit is up
to 50m.
Input power 24VDC±10% 0.4A (include a moment and ripple)
<Sum of Handy machine operator’s panel and interface unit>
Note
1. Connecting cables are not included in the handy machine operator’s panel.
2. Power supply unit and cables must be prepared by user.
3. When detachable connection, connector panel must be prepared by user.
4. In view of CE standard, there is a possibility that detachable connection by installing the
connection panel in the cabinet is not permitted. (This is because the emergency stop
circuit is bypassed). Please confirm it to CE competent body. When detachable connection
is not permitted, please use handy machine operator’s panel by keeping always.
TITLE
4. Environmental requirements
Note
Please use in away place from noise and magnetism.
TITLE
2 lines×16
characters
LCD
Single
LED
Operation
ON/OFF
switch
Override
Input key
switch
with LED
×20 3 positions
enabling
switch
Manual
Pulse
Connector
CA74
Installation method
Cabinet
Installation metal fitting
A300-0001-0060
3 11 10
11.25
Φ6.5
M4
Unit: mm Φ13
Installation metal fitting is equivalent of A300-0001-0060. The strength is necessary to support the
weight of handy machine operator’s panel.
Notice
1. Please install the handy machine operator’s panel seen head-on it.
2. Don’t install the handy machine operator’s panel by belt.
3. Please hold the handy machine operator’s panel through belt. This unit has an enabling
switch. When operator is surprised unexpected motion, he will release the enabling switch.
When operator holds the handy machine operator’s panel without using belt, the handy
machine operator’s panel may be dropped.
TITLE
Fuse FU1
LED
LI
LD
PO
MS
E0
E1
E2 Installation
side
Connector to
handy machine
operator’s panel
JD47
70mm space at front and under of this unit are necessary for cable connection.
There is connector terminal TNB in the upper side. This connector terminal is possible to
connect/disconnect with connecting wire. The space for minus driver (100mm or over) is necessary.
In the case of the connector terminal is installed while the interface unit is not installed on the
cabinet, 50mm space is necessary at upper side of this unit.
This interface unit can be installed to the cabinet with DIN rail or screw. Please refer to the item
of “connection of connector panel I/O module” of connection manual.
Notice
Terminal block of connector TNB can be disconnected without disconnecting wire. When it is
difficult to disconnect the terminal block, please remove the unit from DIN rail etc. The
terminal block should not be disconnected with screwdriver while the unit is mounted to DIN
rail, the case may be broken.
TITLE
Cabinet
Emergency input DI
CNC
Handy machine
operator’s panel
Cabinet
Emergency input DI
CNC
Connection panel
Handy machine
operator’s panel
TITLE
Enabling switch
ON/OFF circuit Enabling
switch
Emergency stop
circuit lower step
Safety relay for input DI of CNC and Maximum electric current of
emergency stop of servo amplifier emergency stop line -> 200mA
Note
The state of the emergency stop button and the enabling switch on the handy machine
operator’s panel can be read by PMC ladder diagram. But emergency stop of CNC is not
occurred with this signal on I/O Link. Emergency stop of CNC is occurred by DI of CNC.
Notice
1. When an operator controls machine tool with handy machine operator’s panel, the operation
must be done under the condition that CNC and servo amplifier can be stopped with the
emergency stop button on the handy machine operator’s panel.
2. When an operator controls machine tool with handy machine operator’s panel and there is
a possibility that the operator meet a dangerous situation, the operation must be done
under the condition that CNC and servo amplifier can be stopped with the enabling switch
on the handy machine operator’s panel.
3. The contact and the additional contact of the emergency stop button and the enabling
switch must be always used.
4. In the case of detachable connection, handy machine operator’s panel must be removed from
the connection panel and be put away, when machine tool is not operated with it.
TITLE
Emergency
stop circuit
Serial Serial
signal signal
Notice
Please keep the following notice, when detachable connection.
1. While operation, detachable connection switch must be ON, not OFF.
2. Detachable connection switch with key must be used. Operator must hold the key while
operation. The other person must not hold the key or the copy key.
3. When emergency stop is occurred with switches on handy machine operator’s panel,
emergency stop state must not be released with turning off the detachable connection switch.
TITLE
Notice
1. In the case of existing of same purpose switches on the handy machine operator’s panel and
main operator’s panel, and the switch is an alternate switch, there are possibility of damage to
the machine when this sequence is not kept. Example, override is set to 120% with override
switch on the handy machine operator’s panel, but the override switch on the main operator’s
panel is 50%, override is changed from 120% to 50% by turning off the operation ON/OFF
switch.
2. In the case of detachable connection, detachable connection switch must not be turned on with
the state of turning on the operation switch. The override switch and the input key, which is
pushed by accident, are valid after turning on the operation ON/OFF switch.
3. In the case of detachable connection, the Handy machine operator’s panel should not be
connected and disconnected while handle mode. The position of axes may be changed.
4. In the case of detachable connection, the Handy machine operator’s panel should not be
connected when the detachable connection switch on the connection panel is turned on.
Because system alarm may be occurred.
TITLE
Notice
1. The enabling switch has a possibility of fusing and attaching. Operator must check the
occurrence of fusing and attaching of this switch before operating with handy machine
operator’s panel with this switch. Please check that the red LED ALM is not turned on while
enabling switch is released. And check that the red LED ALM is not turned on while enabling
switch is gripped tightly.
2. When fusing and attaching is occurred in the enabling switch, do not use the handy machine
operator’s panel with the enabling switch.
3. Do not cancel the state of emergency stop with the method except for keeping the enabling
switch in the middle of three positions, when the enabling switch is available.
Notice
When there are same purpose switches on the handy machine operator’s panel and the main
operator’s panel
1) Please decide which switches are available by the state of the operation ON/OFF switch.
When the both switches are available, the state can be changed from main operator’s panel,
though the operation with handy machine operator’s panel is done. It is dangerous.
2) Please don’t turn off the operation ON/OFF switch in the situation that operator expose
himself to danger. When the operation ON/OFF switch is turned off, the operation from main
operator’s panel is possible. It is dangerous.
10.4 LCD
The display is 2 lines and 16 characters LCD.
The position and the messages with figures/alphabet/kana are displayed by PMC ladder program.
TITLE
There are two LEDs, which is turned on/off by PMC ladder program for the following purpose
mainly
1) Red LED (right side); The notation of FANUC standard key sheet is “CNC ALM”.
This LED shows the occurrence of Alarm of CNC.
Please assign Alarm signal (AL) for this LED.
2) Green LED (second LED from right); The notation of FANUC standard key sheet is “SRDY”.
This LED shows possibility of axis motion.
Please assign servo ready signal (SA) for this LED.
TITLE
XYZ
456 SPINDL SPINDL
REF RESET
START STOP
SPINDL SPINDL
HANDLE JOG
INC DEC
×n F1
FUNC
MEM MESSAG RAPID
TION
When using this key sheet, memory operation “MEM”, manual handle feed “HANDLE”, manual
continuous feed “JOG” and manual reference position return “REF” are possible. We suppose that the
following operation and display is done by PMC ladder program.
1) Memory operation
XYZ SPINDL SPINDL
REF RESET
456 START STOP
SPINDL SPINDL
HANDLE JOG +
INC DEC
FUNC
×n MEM MESSAG RAPID
TION
SINGLE DRY CYCLE FEED
BLOCK RUN START HOLD
・When the “MEM” key is pushed, mode is changed to MEM operation mode.
・When the “CYCLE START” key is pushed, automatic operation is started.
・When the “FEED HOLD” key is pushed, automatic operation is stopped.
・When the “RESET” key is pushed, CNC is reset.
Reset and rewind signal should be on for rewinding part program.
・Override can be applied to feedrate speed by the override switch on handy machine operator’s
panel. Set feedrate override signal from 0% to 120% according to the override switch position.
・When the “×n” key is pushed, rapid traverse override is applied. Please rotate the setting value
100%→50%→25%→F0→100% by each pushing this key.
・For test operation, Dry run “DRY RUN” and single block “SINGLE BLOCK” are available.
・One axis position is displayed normally. When the “XYZ 456” key is pushed, next axis position is
displayed.
<Display example>
Program number Block number Present rapid override
O 1 0 0 0 N 0 0 1 0 1 0 0 %
X - 9 9 9 9 9 . 9 9 9 1 2 0 %
Position display Present feedrate override
TITLE
・ When the “REF ” key is pushed, mode is changed to manual continuous feed mode and manual
reference position return selection signal “ZRN” is asserted.
・ The axis, which is moved for manual reference position return, is selected by pushing the “XYZ
456” key several times. And the selected axis is decided for pushing the “FUNCTION” key.
・ When the “+ ” key or the “-” key is pushed, the axis moves to the direction of reference position.
<Display example>
X - 9 9 9 9 9 . 9 9 9
Position display
5) Spindle control
TITLE
10mm
8mm
10mm
Note
When a handy machine operator’s panel, which is customized by seal, is changed, the
customization must be done by MTB. Please prepare the seal. Transparent key sheet,
which is stripped off, can not be used again. Please use other transparent key sheet.
13. Supplement
1) The following edition number or later of control software of CNC is necessary for Handy machine
operator’s panel.
16i-TA 18i-TA 21i-TA 16i-MA 18i-MA 21i-MA
B1F4 01 BEF4 01 DEF4 01 B0F4 02 BDF4 02 DDF4 02
16i-TB 18i-TB 21i-TB 16i-MB 18i-MB 21i-MB
B1H1 03 BEH1 03 DEH1 03 B0H1 02 BDH1 02 DDH1 02
15i-MA 15i-MA PM i-D PM i-H
②
F008 01版 F608 01版 88E0 15版 88F1 07版
2) The following edition number or later of control software of PMC is necessary for Handy machine
operator’s panel.
PMC-SB5/SB6 PMC-SA1 PMC-SB7 PMC-NB6
406A 09 406A 18、406H 01 406G 01 404A 01
3) When the time of one period of PMC ladder program is very long, key input is not accepted. The
time of one period of PMC ladder program must be the time that key input is accepted certainly.
The standard time is about 50ms.
4) The display routine of LCD should be run periodically. The standard time is about 200ms.
Especially for position display, the changing of position is not smooth when the periodic time is
exceeding the standard time.
5) When two input keys are pushed at the same time, PMC ladder program can read these input keys.
But when three or more input keys are pushed at the same time, PMC ladder program can not read
these input keys.
② 6) In the case of 16i/18i/21i –A/B which are correspond to FANUC I/O Link 2 channels, the schedule of
the connecting to channel No. 2 of FANUC I/O Link with HMOP is about December of this year.
There are not channel No. 2 of FANUC I/O Link with 15i and Power Mate i.
② 7) In the case of connecting a HMOP to FANUC I/O Link, that MPGs have been connected already, the
schedule of the function is about December of this year.(16i/18i/21i –A/B and Power Mate i)
TITLE
SHEET
EDIT. DATE DESIG. DESCRIPTION FANUC LTD 17
Connection of Handy machine operator’s panel
Cabinet
1) The total length of the cable J186 must not exceed 50m.
Please keep the following about 24VDC at connector CA74.
DC24V±10% (including instantaneous changes and ripple)
(The 24VDC power is subject to a voltage drop corresponding to the total resistance of the 0V and
24V lines of cable J186 and J187.)
TITLE
24V
CA74(10) 24V 24V JD47(10) To CNC and
TNB(24V)
servo amplifier
CA74(19,20) 0V 0V JD47(12,14)② TNB(0V)
0V 24VDC
0V ②
CA74(3) SOUT SIN JD47(1) Power
Shield
Note 1) This switch must be opened in automatically, when the operator exposes himself to danger,
example the observation working in the protection cover of cutting part, and the working in the
fence for danger area. So, the enable switch must be hold at the middle position avoiding the
emergency stop. When the operator does not expose himself to danger, this switch is closed. So he
does not have to hold the enable switch at the middle position.
And this switch may be the switch for the detection of fusing and attaching on the main operator’s
panel. When there is the switch, the protection cover and the fence does not have to open for the
testing of fusing and attaching of enable switch.
Note 2) The details connection of JD1A, JD1B (I/O Link) of interface unit is eliminated.
TITLE
CA74 JD47
1 3
SIN SOUT
2 4
*SIN *SOUT
Shielded
3 1
SOUT SIN #24AWG
4 2 pair
*SOUT *SIN
11 5
ESPI1 ESPI1
ESPI2 12 6 ESPI2
EN1 13 17 EN1
EN2 14 19 EN2
24V 10 10 24V
0V 19,20 12,14 0V
Shield
TITLE
2) Open pins and pins with “() “must not be connected with wire.
3) Don’t change pair of wires.
Interface unit
TNB
Emergency
24V 24V
stop circuit
0V 0V
1 ESPO2
2 ESPO2 J187
3 EN2
4 ESPI2
5 ESPO1 PHOENIX contact
DC24V
6 ESPO1 Co., Ltd.
power supply
7 EN1 MSTB2.5/10-STF
8 ESPI1
24V
TNB(8)
Upper step
emergency
TNB(4)
stop circuit
TNB(5)
Lower step
TNB(2) emergency To CNC and
stop circuit servo amplifier
TNB(1)
TNB(24V)
24V
TNB(0V) 24VDC power supply
0V
②
TNB is a connector terminal, it is attached to unit.
24V 0V 1 2 …… 8 10
TITLE
Cabinet
J188 J189
JD47 JD1B (JD1)
I/O Link lower unit
(Optical I/O link adapter)
1) The total length of the cable J188 and J189 must not exceed 50m.
Please keep the following about 24VDC at connector CA74.
DC24V±10% (including instantaneous changes and ripple)
(The 24VDC power is subject to a voltage drop corresponding to the total resistance of the 0V and
24V lines of cable J187, J188 and J189.)
3) Please refer to the section 1.3 for emergency stop line and power line cable J187.
4) Please refer to the chapter 8 of the specification about the connection panel. And keep notice of
the chapter 8.
Warning
In the case of detachable connection, the emergency stop button and the
enabling switch is not available under the condition of the detachable
connection switch is OFF on the connection panel.
TITLE
Interface unit
Emergency stop button 24V
24V Lower
CA74(10) 24V 24V JD47(10) TNB(24V) step
emergency
CA74(19,20) 0V 0V JD47(12,14) ② TNB(0V) ② stop
0V circuit
0V
Note4
CA74(3) SOUT SIN JD47(1)
CA74(4) 0V 24V
*SOUT *SIN JD47(2)
TITLE
1 12
SIN SOUT
2 13
*SIN *SOUT
Shielded
3 10
SOUT SIN #24AWG
4 11 pair
*SOUT *SIN
11 2
ESPI1 ESPI1
ESPI2 12 3 ESPI2
EN1 13 4 EN1
EN2 14 5 EN2
24V 10 9 24V
19,20 ② 1,8
0V 0V
15 FG
Shield #24AWG
Shell
TITLE
12 3
SOUT SOUT
13 4
*SOUT *SOUT
Shielded
10 1
SIN SIN #24AWG
11 2 pair
*SIN *SIN
2 5
ESPI1 ESPI1
ESPI2 3 6 ESPI2
EN1 4 17 EN1
EN2 5 19 EN2
24V 9 10 24V
0V 1,8 ② 12,14 0V
②
FG 15
#24AWG Shield
Shell
TITLE
1. Fuse
Interface unit has a fuse FU1 for the input of DC24V power supply. This fuse is for the protection of
the input of DC24V power supply of Handy machine operator’s panel (HMOP) and Interface unit. It
has the possibility that the fuse of FU1 blows when the Single LED "EN" of HMOP isn't turned on
and the LED "PO" of Interface unit isn't turned on after a DC24V power supply is supplied. In this
case, pull out the fuse from the socket, and examine continuity with a tester (or visual observation).
When the fuse blows, investigate the cause, and do proper treatment, and exchange it. The capacity
and the specification of the fuse are as the next. Refer to the section 5.2 of the specification material
for the mounting position of the fuse.
2. Indication of LED
Refer to the section 10.7 of the specification material for the Single LED "EN" and "ALM" of HMOP.
The following seven LEDs are mounted on Interface unit, and the condition of the unit is indicated.
As for the mounting position, refer to the section 5.2 of the specification material.
The details of LEDs turned on by the error occurrence (○: lighting, ×: un-lighting)
MS E0 E1 E2 Error’s name Description Countermeasure
○ ○ × × Peripheral error Interface unit is wrong. Replace Interface unit.
of Interface unit
○ × ○ × RAM parity error Interface unit is wrong. Replace Interface unit.
of Interface unit
○ × × ○ Receiving error of The other equipment Confirm the other
I/O Link connected with I/O equipment connected
Link is wrong. with I/O Link.
○ ○ × ○ Framing error of The communication
I/O Link end signal of I/O Link
is incorrect.
○ × ○ ○ CRC error of I/O The communication
Link data of I/O Link is
incorrect.
TITLE
3. Error message
Following error message is displayed on LCD of HMOP when error occurs.
Message Description Countermeasure
SYSTEM ERROR:001 The firmware of HMOP Replace HMOP.
(CPU WATCHDOG) terminated by the
malfunction
SYSTEM ERROR:002 The firmware of HMOP is Replace HMOP.
(ROM ERROR ) broken.
SYSTEM ERROR:003 The combination of the PCB Replace HMOP.
(PCB VER. ERROR) and the firmware is not
correct.
COMM. ERROR: 001 HMOP is wrong. Replace HMOP.
(PERIPH. ERROR )
COMM. ERROR: 011 The communication with the
(WATCHDOG ERROR) interface unit got the
suspension.
COMM. ERROR: 100 The communication data is
(CRC ERROR ) incorrect.
COMM. ERROR: 101 The communication ripple
(DMI ERROR ) has fallen into disorder.
COMM. ERROR: 110 The communication end
(FRAMING ERROR ) signal is incorrect.
COMM. ERROR: 111 The number of
(DATA NUM. ERR.) communication bytes exceeds
four bytes.
The above errors have the possibility that it occurs by the contact defect of the cable, the breakage or
the manufacture defect, too. And, the errors have the possibility that they occur by the noise, too. In
this case, confirm the connection of the cable, the treatment of shielding and grounding according to
the connection material. And, refer to the "Countermeasures against noise" of the manual of NC, too.
TITLE
1. Preface
Handy machine operator's panel (HMOP) is controlled with PMC sequence program. The status of
the input key and the switches mounted on HMOP is read by PMC sequence program. The position
and the message are displayed on the LCD mounted on HMOP by PMC sequence program. This
document describes the information that is necessary to program PMC sequence.
2. Applied Software
The information contained in this document is applicable to the following software.
TITLE
Note) The occupied input/output point for Handy machine operator’s panel is 32 bytes/32 bytes.
TITLE
X Bit0 to 7 Y Bit0 to 7
+0 +0
+1 +1
Power-on/off information LED bit image
+2 +2
+3 +3
+4 +4 LCD line control
Status of Handy Machine
+5 +5 1st (left) character of selected line
Operator's Panel
+6 +6 2nd character of selected line
+7 +7 3rd character of selected line
+8 +8 4th character of selected line
Input key bit image
+9 +9 5th character of selected line
+10 +10 6th character of selected line
+11 Reserved +11 7th character of selected line
+12 Manual pulse generator +12 8th character of selected line
+13 +13 9th character of selected line
+14 Reserved +14 10th character of selected line
+15 +15 11th character of selected line
+16 12th character of selected line
+17 13th character of selected line
+18 14th character of selected line
+19 15th character of selected line
+20 16th(right) character of selected line
+21
+22 Numeric variable data information
+23
+24
+25
+26
+27
Numeric variable data
+28
+29
+30
+31
TITLE
1) Communication error
When HMOP is not communicating correctly, "ERINF" becomes "1". So, the message on the display
unit of CNC can be displayed.
2) Power-on/off information
After HMOP and CNC once communicated, Power-on/off information PWR01 becomes "1". When the
HMOP is disconnected or the power supply is OFF, the signal becomes "0". By using this input
signal, PMC LADDER can detect whether the HMOP is connected or disconnected (The power is
turned on or off.) So, the message on the display unit of CNC can be displayed. There are 22 Power-
on/off information (PWR01 to PWR22), but please use PWR01.
Turning off the power supply could be detected by only PWR01 signal though there are 22 signals.
When "ERINF" is "1", Power-on/off information is not valid. Please judge the Power-on/off
information under the condition of ERINF is “0”.
TITLE
Note 1) Please check OVREN (Valid override switch signal) is "1" before referring
to OVR0 -OVR3.
When the HMOP is disconnected or the power is off or communication
alarm is occurred, the above signals will be “0”. It can be distinguished the
situation that the override switch is set to position 0 (0%), so the machine
can be avoid the shock.
Note 2) When the Handy machine operator’s panel is used with detachable
connection and is disconnected, the override value is hold by the ladder
program with the turning off the operation ON/OFF switch. But if the
Handy machine operator’s panel is disconnected without turning off the
operation ON/OFF switch, the machine can be avoid the shock with the
judging of the OVREN bit.
TITLE
4.2.2 Emergency stop button, 3 position enabling switch, Operation on/off switch
ON/OFF state of Operation on/off switch can be read. So, it can be decided that the signals from the
HMOP can be used. And the states of Emergency stop button, 3 position enabling switch and
Operation on/off switch can be confirmed by CNC diagnoses screen.
Address bit7 bit6 Bit5 bit4 bit3 bit2 bit1 Bit0
X+5 (Reserved) (Reserved) (Reserved) OPSW EQDSW DSW2 DSW1 ESP
Bit0 Description
ESP
0 Emergency stop button is not pushed.
1 Emergency stop button is pushed. Or 24VDC is not supplied to emergency
stop circuit.
Bit2 Description
DSW2
0 Contacts of pass2 of enabling switch or emergency stop button are opened.
Or 24VDC is not supplied to emergency stop circuit.
1 Contacts of pass2 of enabling switch and emergency stop button are closed.
TITLE
TITLE
TITLE
1
3. Requesting to display
new data(REQDSP)
(PMC --> HMOP) 0
(d) (e) (f) (d) (e) (f)
1
4. Acknowledgement
(ACKLCD)
(HMOP --> PMC) 0
TITLE
TITLE
-Please refer to “4.4.8 LCD character-code table" for the character-code which can be set.
-The location where numeric variable code (16) was specified is substituted for the character
strings which displays numeric variable (X+21 to X+31). When the numeric variable is shown
by two or more digits, the characters following the numeric variable code are also substituted.
When a numeric variable is illegal, the location where numeric variable code was specified
becomes blank.
TITLE
LCD column 1 2 3 4 5 6 7 8 -- 16
LCD displays X = - 1 2 . 3 (Space) (Space)
(Note) In this case, the number of digits to display numeric variable data is 5, and the
number of decimal digits is 1.
-The location where the transparent character-code (31) was specified leaves the last character
(Example)
LCD column 1 2 3 4 5 6 - 16
Current LCD Y = 6 A B C P
displays
+
Address Y+5 Y+6 Y+7 Y+8 Y+9 Y+10 - Y+20
Char.-code 31 31 31 90 61 52 - 32
Displayed char. (trans.) (trans.) (trans.) Z = 4 (space)
LCD column 1 2 3 4 5 6 - 16
Next LCD displays Y = 6 Z = 4 (space)
-Only one numeric variable can be specified by one display request. When two or more numeric
variables are specified for one line, it is necessary to overwrite selected line two or more times
by using the transparent character-code (31).
TITLE
TITLE
TITLE
-This specification is invalid when “Custom macro variable data” is specified to numeric
type (VTYPE0 to 1)
TITLE
-When the value of this setting is smaller than the effective decimal position of numeric
variable, the digit is rounded by the method of specification with DSPPRC.
(Example) "Value of the numeric variable=13.45, Number of display columns = 6,
DSPPOS =Left justify, DSPPRC=Half-adjust" Situation
Number of display Display of six characters
columns below decimal
point
0 1 3
1 1 3 . 5
2 1 3 . 4 5
3 1 3 . 4 5 0
TITLE
-When numeric type (VTYPE0-1) is "Custom macro variable", Mantissa is stored in VDATA0-
3(four bytes), exponent is stored in VDATA4-5(two bytes).
TITLE
TITLE
TITLE
TITLE
TITLE
TITLE
TITLE
Address R98 R100 R102 R104 R106 R108 R110 R112 R114
Contents (decimal) 16 -1 -501 -1001 -2001 -3001 -4001 -5001 -6001
TITLE
TITLE
Set 1 to
HANDLEAXIS_TMP when
it is 0. It is the procedure
when power turned on.
Shift HANDLEAXIS_TMP
to left when XYZ456 key is
pushed.
TITLE
Copy HANDLEAXIS_TMP
to HS1A-HS1D when
FUNCTION key is pushed.
TITLE
TITLE
TITLE
If ACKLCD=0 (display
demand is not accepted),
REQDSP=1.
TITLE
TITLE
Getting the selected axis name to display is done in the procedure of axis selection which is
executed when XYZ456 key is pushed. That is, reading CNC parameter 1020 by PMC window
function and move the result of it to R316.
TITLE