www.ck-electrical.
com
MSQ Current Transformer
Technical characteristics of current transformers:
Bar:30 10mm
WINDOWSTYPE conductor:ø20mm
Rated Rated power(VA) Weight
Type
current(A) Class:0.5 Class:1 (kg)
30/5 - 1 0,4
40/5 - 1 0,4
50/5 - 1 0,4
MSQ-30 60/5 - 1 0,4
75/5 1 1.5 0,4
MSQ-30 80/5 1.5 2.5 0,4
100/5 2.5 5 0,4
150/5 5-10 5-10 0,4
200/5 5-10 5-10 0,4
250/5 5-10 5-10 0,4
300/5 5-10 5-10 0,4
Bar:40 10mm
WINDOWSTYPE conductor:ø30mm
Rated Rated power(VA) Weight
Type
current(A) Class:0.5 Class:1 (kg)
100/5 2.5 2.5 0,38
MSQ-40 150/5 3 5 0,38
200/5 5 5-10 0,38
MSQ-40 250/5 5-10 5-10 0,38
300/5 5-10 5-10 0,38
400/5 5-10 5-10 0,38
500/5 5-10 5-10 0,38
Bar:40 10mm
WINDOWSTYPE conductor:ø30mm
Rated Rated power(VA) Weight
Type
current(A) Class:0.5 Class:1 (kg)
250/5 5 5 0,60
300/5 5 5 0,60
400/5 5-10 5-10 0,60
MSQ-60 MSQ-60 500/5 5-10 5-15 0,60
600/5 10-15 10-1 0,60
750/5 10-15 10-15 0,60
800/5 10-15 10-15 0,60
1000/5 15 15 0,60
Bar:40 10mm
WINDOWSTYPE conductor:ø30mm
Rated Rated power(VA) Weight
Type
current(A) Class:0.5 Class:1 (kg)
1500/5 15 15 0,80
1600/5 15 15 0,80
2000/5 15 15 0,94
MSQ-100 2250/5 15 15 0,98
MSQ-100 2500/5 15 15 1,10
3000/5 15 15 1,16
Tel:0086-577-88999052 Fax:0086-577-88999161 E-mail:info@ck-electrical.com
135
www.ck-electrical.com
NSQ Current Transformer
NSQ Series:
Primary current: 30A-3000A
Secondary current: 5A,1A
Standard approval: BS7626,IEC44-1
Maximum voltage: 0.66KV
Frequency: 50-60Hz
Rated load: 2.5VA,15VA
NSQ-30 Class: 0.5,1.0,3.0
Short-time thermal current: Ith=60 Ih
Rated security coefficient: FS 5
Techical data:
Primary Bushbar Hole Rated Rated Rated
Model class
secondary Dimension Load(VA) Voltage Frequency
NSQ-35 NSQ-30 30/5A-300/5A 30 10mm 2.5~5 0.5/1.0 0.72 50/60Hz
NSQ-35 50/5A-400/5A 35 10mm 5 0.5/1.0 0.72 50/60Hz
NSQ-40 100/5A-600/5A 40 10mm 10 0.5/1.0 0.72 50/60Hz
NSQ-60 600/5A-1600/5A 60 10mm 15 0.5/1.0 0.72 50/60Hz
NSQ-100 800/5A-3000/5A 100 10mm 15 0.5/1.0 0.72 50/60Hz
Dimensions of case(mm)
Model A B C D E F
NSQ-40
NSQ-30 30 78 46 95 112 70
NSQ-35 40 70 46 84 100 70
NSQ-40 45 80 46 87 104 70
NSQ-60 60 110 53 130 148 80
NSQ-100 100 155 53 174 191 80
Dimensions
NSQ-60
NSQ-100
Tel:0086-577-88999052 Fax:0086-577-88999161 E-mail:info@ck-electrical.com
136
www.ck-electrical.com
RCT Current Transformers
RCT Series:
Primary current: 30A-3000A
Secondary current: 5A,1A
Standard approval: IEC44-1
Maximum voltage: 0.66KV
Frequency: 50-60Hz
Rated load: 15VA
Class: 1.0
RCT-25
Short-time thermal current: Ith=60 Ih
Rated security coefficient: FS 5
Specificaton:
Model Primary/secondary(A)
RCT-25 15/5,20/5,30/5,40/5,50/5,60/5,75/5,100/5A
RCT-35 30/5,50/5,60/5,80/5,100/5,120/5,150/5,200/5A,250/5,300/5
RCT-60 300/5,400/5,500/5,600/5,800/5,1000/5,1200/5
RCT-35 RCT-90 800/5,1000/5,1200/5,1500/5,1600/5
RCT-110 1000/5,1200/5,1500/5,1600/5,2000/5,2500/5,3000/5
Specificaton:
Model RCT-25 RCT-35 RCT-60 RTC-90 RCT-110
A 93 93 93 93 102
B 78 78 78 78 86
RCT-60 C 25 32 60 90 111
D 78 78 104 136 157
E 2 2 2 2 2
F 55 55 41 41 52
G 9 9 9 9 9
Outline drawing:
RCT-90
RCT-110
Tel:0086-577-88999052 Fax:0086-577-88999161 E-mail:info@ck-electrical.com
137