Cws Modul2015 Eng
Cws Modul2015 Eng
CWS MODUL
                                    VECO S.p.A.
                                    via Cantore 6, 20833 Giussano - (MI)ITALY
                                    ViaCantore,6/8-20034Giussano    Italy
                                    Tel. +39 0362 35321 | Fax. +39 0362 852995
                                    E-mail: info@veco.net | Web: www.veco.net
                    Table of contents
    Chapter                   Contents                            page
      1            Important warnings                              3
             2     Introduction                                       4
             3     Installation                                       6
             3-1   Sea water circuit                                6
             3-2   Fresh water circuit                              8
             3-3   Electrical circuit                               10
             4     Operation                                        12
             5     Maintenance                                      16
             6     Troubleshooting                                  17
             7     Electrical schematic                             22
                                           VECO S.p.A.
                                           via Cantore 6, 20833 Giussano - (MI)ITALY
                                           ViaCantore,6/8-20034Giussano    Italy
                                           Tel. +39 0362 35321 | Fax. +39 0362 852995
                                           E-mail: info@veco.net | Web: www.veco.net
1.1.2 – CORROSION
In order to prevent any problem of galvanic corrosion (electrolysys) the central unit is equipped
with a ground connection for every seawater condenser. It is compulsary that every condenser is
linked in the correct way to the sea water pump and sea water intake, in order to keep these
points equipotential.
Failing to follow this rule voids any warranty on the product and puts in great danger the integrity
and the life of the system and of all components in contact with the sea water.
The sea water condensers of our units are made in Cu.Ni special material perfectly resistent to the
marine environment. Nevertheless we specify a value for the maximum flow thru the condenser in
order not to enter in the danger of damaging the condenser due to high speed.
The measure must be made with the modules running and measuring the temperature difference
between the IN and OUT of each condenser.
The temperature difference SHOULD NOT BE LESS THAN 6 °C which guarantees that the water
flow doesn't exceed the safe speed value.
Ignoring or infringing this specification voids the warranty of the sea water condensers.
    Failure to follow all the instructions in this manual can cause property damage, injury or death.
    Improper installation, adjustment or alteration can cause property damage, injury or death.
    Electrical connections should be performed only by a certified professional.
    Electrical and grounding connections must comply with the National Electric Code and local
    electric codes. Failure to comply with this procedure can cause property damage, injury or
     death.
    Before connecting the unit to the electrical supply, verify that the electrical connection agrees
    with the specifications on the data plate, placed on the main electrical box of the unit. Failure to
    comply with this procedure can cause property damage, injury or death.
    This appliance must be connected to a grounded, metal, permanent wiring system. Failure to
    comply with this procedure can cause property damage, injury or death.
When loading or unloading the unit, use a fork lift equipped with forks at least 2/3 the length of the
shipping base.
Use an overhead lift if the unit is equipped with lifting eye-bolts.
Select lifting equipment suited to the weight and overall dimensions of the packaged unit or
components.
Take every precaution to prevent damage, when handling the unit or components keeping in
compliance with the information given on the packaging material.
Injuries or accidents caused by failure to comply with the recommendations of this manual are
solely to the responsibility of the unit operator.
Basic Rules for Safe Operation:
● do not touch the unit with moist or wet hands or feet;
● before installation and maintenance operations, disconnect the unit from the power supply failure
  and electrical components. Only a Climma certified service center should install and maintain the
  system;
● to minimize the hazard of electrical shock and personal injury, this component must be effectively
  grounded;
● during installation and maintenance follow safety codes, wear safety glasses and work gloves;
FWD
A- B
  3.1.3 – INSTALLATION
      The pump should be fastened with adequate screws using the holes in its base or the special fixing base (available
      for small models). For larger pumps, the original quiet and smooth running can be improved by using a silent block
      mounting.
    The sea water condensers of our units are made in Cu.Ni special
    material perfectly resistent to the marine environment. Nevertheless
    we specify a value for the maximum flow thru the condenser in order
    not to enter in the danger of damaging the condenser due to high
    speed.
    The measure must be made with the modules running and measuring
    the temperature difference between the IN and OUT of each
    condenser.
    The temperature difference SHOULD NOT BE LESS THAN 6 °C
    which guarantees that the water flow doesn't exceed the safe speed
    value.
    For this scope it is compulsary to install a calibrating valve on the
    pump outlet. The calibrating valve will then be set to supply the correct                    Calibrating valve
    cooling flow to the condenser(s).
See also point 3.1.3. The sea water circuit must always rise from the sea water intake to the heat exchanger. It is
important to avoid ups and downs which will create syphons and prevent the circuit to run properly.
                                                      IMPORTANT
The sea water outlet must be installed close to the sea level considering the the water out should not make noise for
the boat itself and for the neighbours.
The flow switch is an additional safety equipment that will stop the
system whenever the fresh water flow stops or if it is not enough.
The flow switch has to be installed on the fresh water circuit. It has
to be accessible for maintenance and for calibration.
The flow switch has to be electrically connected (two wires) to the
main electrical box of the unit as specified in the electrical
schematic ( terminals 1-3 opens on low flow).
  The fresh water circuit has 2 service ports. Each port has a manual valve with check valve to prevent the water in the
  circuit to go back to the sanitary water circuit.
  Use one of the 2 valves and the pressure gauge in order to pressurize the circuit with fresh water at 1,5 Bar; this valve
  must be connected to the water sanitary circuit in the boat.
  Check that the fresh water circuit keeps the pressure over the time, which means that it has no leaks. See also 3,2,6
  for the antifreeze mixture.
                                                Page 8 of 22                                              www.climma.it
April 2019
                          3 - INSTALLATION
  3.2.6 – ANTIFREEZE LIQUID
The fresh water circuit needs to be filled with water (80%) and antifreeze (20%). Antifreeze will prevent water from
freezing in case there is an anomaly in the circulation of the fresh water loop. Antifreeze also reduces the corrosion
inside the fresh water circuit.
Always check that the pressure gauge shows 1.5 Bar in the fresh water circuit.
We suggest two methods for filling the fresh water circuit with antifreeze:
1.Calculate approximately the circuit capacity; Fill the circuit with water and add to it 20% of antifreeze, using the
  second charging valve by gravity or using a pressure pump. Then connect the circuit to the sanitary water circuit of
  the vessel, pressurize up to 1.5 Bar and start purging the air. It is obvious that if purging will be difficult the
  percentage of antifreeze will decrease, as more water will be needed to fill the circuit, therefore more antifreeze must
  be added to the circuit.
2.Empty the circuit from the water used for leak test. Prepare an antifreeze solution of the quantity needed to fill the
  circuit, made with 20% of antifreeze liquid; fill the circuit using a pressure pump. Then proceed with purging air and
  topping up the pressure using the solution.
  We strongly recommend that a special “Automatic Air bleeding vessel” be installed in the fresh water circuit, just
  after the pump outlet. This device will dramatically reduce the bleeding procedure and will also keep the system free
  of air during its life. The “air-bleeding vessel” is available in several sizes. See 3.2.4.
  When the circuit is under pressure with the antifreeze solution, purge the air as follows:
  Bleed the entire circuit (manifold, fan coils, and all the other purging points) starting from the lowest level and
  keeping the circuit pressure at 1.5 Bars.
  This bleeding must be done without running the pump.
  Repeat all points, until no more air comes out from the bleeding valves, still keeping the pressure at 1.5 Bars.
  Then...
  Set to “off “ position each compressor switch.
  Check that seawater intake is open and start the unit in “Cool “ mode; both pumps will run (see also 5.4).
  Let the fresh water pump run for 30 seconds then stop the system and bleed again all points, keeping the pressure
  at 1.5 Bars.
  During this filling procedure it is normal that the red alarm light (flow switch alarm) sometimes comes on, indicating
  that there is no flow in the circuit.
  Bleeding can be considered over when no more air is coming off the purging points and the fresh water circulation
  pump runs even and quiet.
                                        Fresh water
                                     temperature probe
                                                                                                     X = back
      The system is controlled by the
      Danfoss step regulator.
      At power up it will prompt the main                                                            Arrow-up = scroll up
      screen like this.
      The highlighted row is the actual
                                                                                                     Arrow-down = scroll down
      choice as you press enter. Scroll
      the highlighted row using the
      arrows to reach the other actions                                                              Enter = confirm
                              Press enter
                               to modify             Press arrows to change the value and then press enter to confirm
                                    Press enter to
                                       modify
                                                                                           Press arrows to
                                                                                        change the value and
                                                                                         then press enter to
                                                                                               confirm
The display will show you that the 2 pumps (SWP : ON – FWP : ON) are
running and in a short time 10-30 seconds) the compressor(s) will start in
sequence. The highlighted row is automatiucally positioned on the “SHUT
DOWN” action.
                                                         This utility can run the sea water and fresh water
                                                                     pumps for test and during the
                                                            commissioning/maintenenace procedures
a) that every condenser is properly linked in the correct way to the sea water pump and sea water
intake, in order to keep these points equipotential.
b) that the temperature difference between the IN and OUT of each condenser SHOULD NOT
BE LESS THAN 6 °C, the value which guarantees that the water flow doesn't exceed the safe
speed value.
5.1.2 ROUTINE CHECKS
Every time the unit is operated check that:
1 – The Step Regulator doesn't show any alarm warning.
2 - The fresh water pressure in the circuit is between 1 and 2 bars as indicated by the gauge on
the unit. If the pressure drops frequently the circuit must be repaired and the leak(s) fixed as
continuous topping up the pressure will dilute the antifreeze reducing the unit safety. The
antifreeze solution of the fresh water (Fan Coil) circuit must be checked at least every year.
The solution to refill the circuit must be composed 80% water and 20% glycol or a good antifreeze
product. Clean monthly the strainer of the circuit.
3 - Check frequently the efficiency of the seawater circuit, inspecting daily the seawater strainer.
4 - Clean or better replace the air filters on each fan coil. A dirty air filter is dramatically
reducing the fan coil efficiency as it reduces the airflow.
5 - At the beginning of the summer season, check that the condensate drain from each fan
coil is clean and discharges freely.
6 - If the system is not operated for a while (over a week), we suggest turning both pumps
manually for few turns before running the system.
5.1.3 HOUR COUNTER
The running time of the compressors and pumps is recorded by the step regulator. Go to the
MENU and choose the “Hour counter”.
The Step regulator records in its memory in hours. The hour is made also by short running times
unless the power is cut before reaching the complete hour running.
Check at least weekly that ther are no leaks for the pump body and rotary seal. The rotary seals of
both sea water and fresh water pumps must be replaced avery 12 months. Failing to do this
maintenance could cause the pumps to be deteriorated and corroded, voiding any warranty.
It is a must that yearly the pump impellers are checked and replaced if they show any sign of
deterioration.
   The system has several safety protections. When a value goes beyond the prescribed limit the
    Danfoss stops the module which is involved and prompts an Alarm or Master Alarm warning.
                                             Press enter to open the detail of the alarm. There are two types of alarm:
                                                                            AUTORESET
                                                                          MASTER ALARM
                                             The autoreset will make 3 consecutive auto resets once the alarm contact
                                          closes. At the fourth attempt the module will be locked out until a manual rest is
                                                                                made.
  In case of lack of fresh water                                     The FLOW safety is installed on each module of the
  water flow (COOL MODE) the                                         system. This means that the lack of fresh water flow
  system is protected by a flow-                                                  might affect all the modules.
 meter device. Its intervention will                                     REMEDY: restore the correct fresh water flow
stop the module where the flow is                                     inspecting the circulation pump. Make sure that the
lower than the minimum value for                                     fresh water circuit is in pressure (1,5 Bar). Clean the
 that unit. The Danfoss will show                                                            strainer.
            this screen.                                            Do not insist in manual resetting aslow fresh water flow
                                                                                       is very dangerous.
 In case of lack of fresh water water                                        This alarm could also happen in particular
  flow (COOL MODE) the system is                                         circumstances like very cold sea water and also
also protected by a sensor which will                                          if the set point has been set very low.
     detect a risk of freezing of the                                    In any case, make the necessary checks before
 evaporator. Its intervention will stop                                                 doing the manual reset
the module where the temperature is                                        REMEDY: check the values of the fresh water
    lower than the minimum value.                                        flow; check the COOL mode set point and rise it
 The Danfoss will show this screen.                                         to 10°C. Do not insist in manual restting as
                                                                                     freezing is very dangerous.
                                            If the module has a leak and looses its refrigerant there is a low pressure switch
                                            which will stop the unit. This control is active also before starting the compressor,
                                           so in case the unit is very low in refrigerant it will not start. This safety is ONE OFF,
                                           so it needs a manual reset. We warn to be very careful before resetting this alarm
                                            as the module could be in risk of being flooded if the leak is in its internal circuit.
                                            REMEDY: the refrigerant pressure must be chacked by a specilized engineer. Do
                                                   not run the module until its pressure has been verified with gauges.
6.1.7 DEW RISK ALARM – CODE 44 MASTER ALARM MANUAL RESET ONLY
       The inverter is water cooled and its                                              The inverter power module temperature is
      temperature is monitored. In case of                                                 controlled with a water valve. This valve
subcooling there is the risk of condensation                                                could get jammed by debris and leak
  which is very dangerous. This alarm stops                                               causing subcooling of the inverter power
the entire system. Cut off the main power to                                                                 module.
    the system and then isolate the module                                              REMEDY: If the dew alarm has stopped the
 from its circuit breaker to prevent any short                                              system, first of all cut the power to the
                      circuit.                                                           module and then check if the inverter heat
   Do not reset until you have checked that                                             exchanger is cold. If it is cold, it means that
 the inverter back plate (heat exchanger) is                                             the water valve is not tight. The valve body
  warm or tepid which means that the alarm                                                       must be cleaned carefully.
   is due to weird circumstances (very high                                             Before powering up, wait until the inverters
           engine room temperature)                                                     have been warmed up and there is no more
                                                                                                     risk of condensation.
      In this table are listed the minimum voltage values accepted in order to start the
    compressor and also the minimum value to keep it running. If the voltage supply falls
   below these values, the compressor will not start or will stop when it is already running,
                           showing the STDBY or DIS-NOPWR state.
    Under a certain minimum the system will simply consider the compressor “disabled” .
    REMEDY: check the voltage supply at the inverter terminals. On case of three phase
   supply, check that all the phases are present. In this case we suggest to stop the chiller
                     and restart it only when the powerr supply is restored.
6.1.9 FRESH WATER PROBE FAULT – CODE 1 MASTER ALARM SYSTEM OFF
6.1.10 SLAVE INVERTER ANTIFREEZE PROBE FAULT- CODE 2 MASTER ALARM - MANUAL RESET ONLY
                                                                                       Code 2 on inverter
                                                                                          module #1
                                                                                       REMEDY: Check
                                                                                       and/or replace the
                                                                                     probe NTC. It needs a
                                                                                         manual reset.
                                                                                      The module remains
                                                                                     OFF until you reset it
                     Press enter to open the detail                                        manually
                             of the alarm.
6.1.11 SLAVE INVERTER SW-IN PROBE FAULT - CODE 46 MASTER ALARM - MANUAL RESET ONLY
                                                                              The probe installed on Sea
                                                                                water IN is monitored. In
                                                                              case of failure it triggers its
                                                                                      specific alarm.
                                                                                REMEDY: Check and/or
                                                                               replace the probe which is
                                                                                   causing the alarm.
                                                                               The module remains OFF
                                                                               until you reset it manually.
6.1.12 SLAVE INVERTER SW-OUT- CODE 47 MASTER ALARM - MANUAL RESET ONLY
                                                                             The probe installed on Sea
                                                                             water OUT is monitored. In
                                                                             case of failure it triggers its
                                                                                     specific alarm.
                                                                               REMEDY: Check and/or
                                                                              replace the probe which is
                                                                                  causing the alarm.
                                                                              The module remains OFF
                                                                              until you reset it manually.
6.1.13 SLAVE INVERTER TENVIR PROBE FAULT- CODE 48 MASTER ALARM - MANUAL RESET ONLY
Error                             Description – Description                          Individual Individual   Auto    Manual System general                          notes
code                                                                                module ALM module        Reset    reset goes off alarm
                                                                                                  STOP
 1         Fresh water temp error – master unit                                                               N        Y      Y       Y      Only for master unit
           Guasto sensore temperatura acqua dolce unità master
 2         Antifreeze sensor error – Guasto sensore antigelo                             Y          Y         N        Y                     Short or open circuit – Unit #
10 Fresh water pump thermal cut-out – Allarme klixon pompa acqua dolce N Y Y
 22        Missing CAN slave n.1 – Allarme comunicazione modulo#1                        Y          Y         Y*       N      N       N      Y* = Autoreset if communication is lost while
                                                                                                                                             running.
                                                                                                                                             If there is no communication at start the system
 23        Missing CAN slave n.2 – Allarme comunicazione modulo#2                        Y          Y         Y*       N      N       N
                                                                                                                                             must be re-powered once the communication is
                                                                                                                                             restored
 24        Missing CAN slave n.3 – Allarme comunicazione modulo#3                        Y          Y         Y*       N      N       N
 30        General inverter alarm-check subcode – Allarme generico inverter-             Y          Y         N                       Y      see detail exadecimal sub-code
           verificare sub-code
 33        Boiler #1 thermal cut-out – Allarme klixon boiler #1                         Y**         Y         N        Y              N       N.C. when boiler is ON- If the contact remains
                                                                                                                                               open it means that the boiler klixon is open.
                                                                                                                                                  Y** = it lights the boiler general alarm
 34        Boiler #2 thermal cut-out – Allarme klixon boiler #2                         Y**         Y         N        Y              N
 37        Boiler #1 power relay error – Errore teleruttore boiler #1                   Y**                   N        Y              Y      N.O. When boiler is OFF. If the contact is closed
                                                                                                                                             it means that the power relay is jammed closed.
                                                                                                                                                  Y** = it lights the boiler general alarm
 42        All boilers in alarm – Allarme di tutti i boiler                              Y                    N        N      Y      Y***    Y*** general alarm and then system goes OFF
                                                                                                                                             and ALM OFF
 44        Dew risk on inverter – Rischio condensa per l'inverter                        Y          Y                         Y       Y      system goes OFF and ALM ON
There is also a series of alarms monitored by the inverter. These alarms appear with the same
alarm code 30.
In order to have the correct information move the higlighted bar to the alarm message and press
enter.
The Danfoss will then show the details of that alarm
1 – 00000002h    Inverter over current The amperage draw of the compressor went beyond the maximum amperage accepted by the inverter. This
                                       could be caused by a problem with the compressor. Check the inverter model first. Then check the compressor
                                       windings.
2 – 00000004h    Under Voltage >30 The voltage has been below the minimum value for a very long time. For 30 minutes the inverter remains in
                       min.        stand-by and ready to run the compressor in case the voltage rises to the normal value.
                                   Complete missing of power supply is interpreted by the inverter as a condition of compressor disabled without
                                   further warnings. The compressor state becomes DIS-UV.
3 – 00000008h    Inverter Overheating The inverter power module temperature exceeds 70°. This means that its water cooling is not working properly.
                                      Check the water valve which supplies the cooling water to the inverter heat exchanger.
4 – 00000010h     Motor thermal cut- This alarm is generated by the inverter if the compressor connection is found “OPEN”
                         out
5 – 00000020h     Motor maximum       Current overload of the compressor. The compressor has been drawing in excess of its set maximum value for
                  current overload    more than the maximum set time (15 seconds).
6 – 00000040h     Sea Water Delta The 2 temperature probes installed on IN and OUT of the sea water condenser are measuring a difference
                 Temperature excess exceeding 20°C. This is caused by lack of cooling water, even before that the HP alarm trips. Check the sea
                                    water flow veryfing the sea water pump, intake and strainer.
7 – 00000080h     Inverter overload Inverter thermal cut-out. This is due to overheating of the inverter power module. Check that the inverter
                                    model corresponds to the compressor power draw.
8 – 00000100h       Motor average     The compressor has been drawing in excess of its maximum current for a time sufficient to saturate the
                   current overload   maximum average power value I2xT. The inverter has a maximum nominal compressor current. When this
                                      limit is exceeded, the inverter makes a calculation of the excess and the time. When the limit is reached the
                                      inverter gives this alarm. There is also a maximum compressor current which will cause the alarm 00000020h.
9 – 00000200h     Short on inverter In this case there is a real short circuit on the inverter output. This alarm is the attempt to protect the inverter
                       output       from a damage. Several attempts to reset this alarm might cause the complete failure of the inverter power
                                    module.
10 - 00000400h       Temporary        This is the case which happens if the mains supply is not sufficient to run the compressor(s). The inverter
                   undervoltage 3     starts the compressor because the voltage is correct but after the start, due to insufficient power, the voltage
                   times – DISUV      drops below the minimum. After three times the inverter stops the compressor and waits a manual reset. Make
                                      sure that the power supply is sufficient. If not you could disable temporary one or more compressors from the
                                      Danfoss user menu.