H07RN-F
450/750 Volts
❙ Application
This cable is dedicated for
installations with moving equipment,
electric appliances and for building
sites.
The cable may be rated 0.6 / 1 kV
where the installations has built-in
protection and for motors in lifting Max continuous operating
appliances - machine tolls - etc conductor Temperature :
in normal use : 60°C
85° C if protected
(200° C in short circuit)
❙ Design ❙ Installation
1. Conductor This cable can be installed in
Flexible, bare copper class 5 open air or be buried but with 1
2. Insulation extra mechanical protection.
Special reticulated elastomer Bending radius 2
3. Conductors laid up Dynamic in use :
Assembled conductors 6 to 8 times outer diameter
Static in use : 3
4. Outer sheath
3 to 4 times outer diameter
High mechanical performance
Reticulated elastomer
4
construction
❙ Marking ❙ Core identification ❙ Standards
USE < HAR > H07RN-F 1 core : Black FRANCE
Nb X (or G) S LINEAX 2 cores : Brown - Blue NF C 32-102-4
X = without G/Y 3 cores : Brown - Blue - CEI 245-4 (modifiée) - HD22-4
G = with G/Y Green/Yellow EUROPE CENELEC
S = section in mm² 4 cores : Black - Brown - Blue - HD 22-4
Black or Green/Yellow INTERNATIONAL
5 cores : Black - Brown - Blue - IEC 60245-4 type 66
Black -Black or Green/Yellow
> 5 cores Black printed with white
numbers with Green/Yellow
-25 + 85° C Very good Good Accidental Flame Flexible AD6
AG 2 AF 3 retardant AD8 on request
❙ Technical Data H07RN-F
Nbre of cores Permissible Voltage drop Outer diameter
Cross section current rating (mm) Weigth
∆u(cos ϕ 0,8)
(mm2) (A) V/A.km Conductor Mini Maxi (kg/km)
1 x 1.5 23 23.3 1.5 5.7 7.1 50
1 x 2.5 32 14.0 1.9 6.3 7.9 66
1x4 43 8.7 2.5 7.2 9.0 94
1x6 56 5.9 3.0 7.9 9.8 109
1 x 10 77 3.4 3.8 9.5 11.9 182
1 x 16 102 2.2 5.0 10.8 13.4 256
1 x 25 136 1.4 6.3 12.7 15.8 369
1 x 35 168 1.04 7.6 14.3 17.9 482
1 x 50 203 0.75 9.0 16.5 20.6 662
1 x 70 254 0.56 10.8 18.6 23.3 895
1 x 95 315 0.44 12.7 20.8 26.0 1160
1 x 120 363 0.36 13.9 22.8 28.6 1430
1 x 150 416 0.31 15.9 25.2 31.4 1740
1 x 185 475 0.28 17.7 27.6 34.4 2160
1 x 240 559 0.23 19.4 30.6 38.3 2730
1 x 300 637 0.20 23.0 33.5 41.9 3480
1 x 400 746 0.18 26.0 37.4 46.8 4510
1 x 500 833 0.16 30.0 41.3 52.0 5700
2x1 18 39.4 1.3 7.7 10.0 99
2 x 1.5 23 27.0 1.5 8.5 11.0 111
2 x 2.5 32 16.2 1.9 10.2 13.1 161
2x4 43 10.1 2.5 11.8 15.1 238
2x6 56 6.7 3.0 13.1 16.8 279
2 x 10 77 3.8 3.8 17.7 22.6 538
2 x 16 102 2.5 5.0 20.2 25.7 744
2 x 25 136 1.68 6.3 24.3 30.7 1074
Permissible current ratings are shown for an ambient temperature of 30°C where the cable is installed in
fixed installations for a maximum operating and a conductor temperature of 85°C.
For other temperatures refer to NFC 15.100 for correction factors.
❙ Technical Data H07RN-F
Nbre of core Permissible Voltage drop Outer diameter
Cross section current rating (mm) Weigth
∆u(cos ϕ 0,8)
(mm2) (A) V/A.km Conductor Mini Maxi (kg/km)
3G1 18 39.4 1.3 8.3 10.7 117
3 G 1.5 23 27.0 1.5 9.2 11.9 134
3 G 2.5 32 16.2 1.9 10.9 14.0 195
3G4 43 10.1 2.5 12.7 16.2 290
3G6 56 7.0 3.0 14.1 18.0 346
3 G 10 77 4.0 3.8 19.1 24.2 663
3 G 16 102 2.5 5.0 21.8 27.6 924
3 G 25 136 1.7 6.3 26.1 33.0 1345
3 G 35 168 1.21 7.6 29.3 37.1 1760
3 G 50 203 0.87 9.0 34.1 42.9 2390
3 G 70 262 0.64 10.8 38.4 48.3 3110
3 G 95 320 0.50 12.7 43.3 54.0 4170
3 G 120 373 0.40 13.9 47.4 60.0 5080
3 G 150 432 0.35 15.9 52.0 66.0 6220
3 G 185 495 0.30 17.7 57.0 72.0 7730
3 G 240 587 0.26 19.4 65.0 82.0 9780
3 G 300 680 0.22 23.0 72.0 90.0 12620
4G1 16 34.08 1.3 9.6 12.0 144
4 G 1.5 21 23.30 1.5 10.2 13.1 165
4 G 2.5 29 14.0 1.9 12.5 15.5 245
4G4 38 8.71 2.5 14.0 18.0 357
4G6 50 5.84 3.0 15.7 20.0 443
4 G 10 68 3.42 3.8 20.8 26.5 818
4 G 16 92 2.20 5.0 23.8 30.1 1150
4 G 25 122 1.44 6.3 28.9 36.6 1700
4 G 35 150 1.04 7.6 32.5 41.1 2180
4 G 50 182 0.75 9.0 37.7 47.5 3030
4 G 70 232 0.56 10.8 42.7 54.0 3990
4 G 95 281 0.44 12.7 48.4 61.0 5360
4 G 120 325 0.36 13.9 53.0 66.0 6500
4 G 150 373 0.31 15.9 58.0 73.0 7990
4 G 185 425 0.28 17.7 64.0 80.0 9910
4 G 240 500 0.23 19.4 72.0 91.0 13120
Permissible current ratings are shown for an ambient temperature of 30°C where the cable is installed in
fixed installations for a maximum operating and a conductor temperature of 85°C.
For other temperatures refer to NFC 15.100 for correction factors.
❙ Technical Data H07RN-F
Nbre of cores Permissible Voltage drop Outer diameter
Cross section current rating (mm) Weigth
∆u(cos ϕ 0,8)
(mm2) (A) V/A.km Conductor Mini Maxi (kg/km)
5 G 1.5 21 23.6 1.5 11.2 14.4 238
5 G 2.5 29 14.00 1.9 13.3 17.0 297
5G4 38 8.72 2.5 15.6 19.9 453
5G6 50 5.84 3.0 17.5 22.2 557
5 G 10 68 3.43 3.8 22.9 29.1 1001
5 G 16 92 2.20 5.0 26.4 33.3 1430
5 G 25 122 1.44 6.3 32.0 40.4 2096
7G1 11.5 — 1.30 13.7 17.5 310
9G1 10.2 — 1.30 16.0 20.4 430
12G1 8.8 — 1.30 17.6 20.9 450
24G1 7.2 34.10 1.30 20.3 24.3 640
27G1 6.2 — 1.30 22.6 28.7 870
30G1 5.9 — 1.30 24.3 29.2 885
36G1 5.6 — 1.30 27.8 30.3 960
6G1.5 16.0 — 1.50 13.4 17.2 300<
12G1.5 11.0 23.30 1.50 17.6 22.14 510
18G1.5 9.0 — 1.50 20.7 26.3 730
24G1.5 7.8 — 1.50 24.3 30.7 1000
36G1.5 6.3 — 1.50 27.8 35.2 1325
juin 2002 - Copyright 2002 - Data is only given as indication without obligation for Nexans
Permissible current ratings are shown for an ambient temperature of 30°C where the cable is installed in
fixed installations for a maximum operating and a conductor temperature of 85°C.
For other temperatures refer to NFC 15.100 for correction factors.