DETECTOR SELECTION.. .................... .................... .................7 TECTOR SELECTION.. .................... ....................
.................... ......13 .................... .................... ....27 .................... ........40
...............41
ecognition techniques are now being combined with CCTV technology providing antion based on monochrome
and full colour technology is available from as. Manufacturers early results with full colour systems seem encouragingr, the
INTENDED USE AND REGULATOR Y CONSIDERA TIONS
definitions
Aided DesignFluid
Dynamic sControl SystemGas and Smoke detecto rSafety and Environmen tProtective Functio
nProtective Syste mEmitting Diodeof Sigh tExposure Limitof Failure on DemandRisk
Assessmen tFailure Robustnes sIntegrity LevelTerm Exposure LimitLimit ValuePower Supply
GAS AND SMOKE DETECTOR SELECTION own Fire & Gas Mapping software has been used widely by Shell and Contractors to
Shell,are may not be required for all designs. For example, where designs (point) monitoring e data transmission (typically 0 20 mA)
between the detector and the rest of themonitoring
GAS DETECTOR SELECTION
d detectors are now available as drop-in
replacements for catalytic (pellistor) detectors. of point gas detectors
absorption type;
gas turbines:on thresholds for
gas turbine protection should be set to 15 % LFL and 40 % LF Lngress/egress thresholds for gas turbine protection vary widely
throughout the Group. Gas
type detectors type detectors
gas detections detectors suffer from both short-
term and longterm drift. Short-term drift may resultetectors also suffer from both shortterm and longterm drift, but this is small whens.s
detectors are used, 20 % LFL and 60 % LFL should be set as respective Low/High
gas detection
of open path gas detectors
monitoring
path gas monitors : recommended) minimum alarm level setting of 0.5 LFLm (50 % LFL extended foring
distances from 4 m to 200 m. However, an optimum distance for offshore
LEAK DETECTION alves operating at
high flowrates and hightools operating off instrument air;valves and relief
valves;winds and flaring operations.
a detailed mapping review is undertaken to establish the level of background
ultrasound ,acoustic leak detection is employed, a high-pass frequency threshold in the 25KHz
MIST DETECTION
GAS DETECTOR SELECTION be fast and reliable and preference shall be given to speed of
responseof HSE shall be included in the design study. shall be reliable and precise;limit values for
an 8 hour working day) shall be monitored ;aspects shall be included in the design
study ;control system with capabilities such as statistical analysis and a data base to
electrochem ical celltype. semiconductor type.
toxic gas detectors
monoxide is sometimes measured with infrared type instruments. Point detectors are gas detection thresholds
Time Weighted Average (TWA) for an 8 hour day, 40 hour week as 5 mL/m
Short Term Exposure Limit ((4) x 10 minutes exposures per day) as 10 mL/m
American Conference of
Governmental Industrial Hygienists (ACGIH) is a recognised body and a
AND SMOKE DETECTOR SELECTION
type selection
by persons (with manual call points);(IR) flame detectors ;flame detectors ;detectors,
such as:type detectors ;detectors. bulbs;alloy links or plugs; by personstype fire
detectorsfire detectors
type fire detectors have an upper ambient temperature limit of 75 C. d flame detectors have
the advantage of improved false alarm rejection
type fire detectors
etectors are subject to interference from welding
activities, Xrays used in nondestructiv eupper ambient temperature limit of 150 C.
flame detector s
detector ssmoke detectors smoke detectors
application of this type of detector may be restricted
due to the fact that the detection principle
sensitivity smoke detectors detectors
heat and smoke detectorsC.
ENGINEERING, SPECIFICATIO N AND INSTALLATION PRACTICES
visual alarms/mess
ages in the control centre and/or in the plant. Additiona lemergency situations to local
community services, e.g. fire brigades, etc.;fire fighting equipment, e.g. fire water
pumps, water spray and fog systems,of safeguardin g and depressurisi ng (blowdown
systems) ;closure of air ventilation inlets ;evacuation systems (barriers, howlers,
etc.).shall be normally closed contacts unless otherwise specified by thedetection is provided
for specific plant equipment, such as a turbine which video display units; andif
the Fire & Gas IPF is SIL 1 or higher, and the confirmed fire or INTERFACE (HMI)
mimic panels
toxic gas : yellow ,flammable gas : bluefire : red,system fault : white,pump
running lights : green,other alarms : red . gas ,gas,pump
auto-start stand-by indication , fault ,fault,fault. a nonlatching
push button to test all indication lights on the mimic.nonlatching push button to change all alarm
lights (except for the plant non-latching push button to reset all visual and audible alarms,
provided that allnonlatching push button to initiate an all-clear signal in the buildings and innon-
latching push button to manually initiate a fire alarm with effect sAlarm: a non-latching push button
to manually initiate a toxic gas alarm in theAlarm: a non-latching push button to manually initiate a
flammable gasPumps: one or more non-latching push buttons to manually start the fire
Dampers: latching push buttons to manually close the dampers .valves: three-
position switches with the positions and related text: open,valve reset: nonlatching
push buttons to reset the water spray valves.
control system
- This shall show the relevant
plants as a simplified plot plan. If Displays One plant overview display shall be provided for each
plant.splays - A unit detailed display shall be available for each process unit,
of events recorder (SER) of communicatio n interfaces with other systems
STANDARDS
of construction and performance
Heat detectors EN 54and ionisationtype detectors
EN 5 4 (flammable) gas detectors EN 61779 Parts 1 through 5
of certification
purpose) detectors may be used only for fire, toxic gas and smokend gas
detectors for use in process areas shall be certified for use in zonefor use in all areas shall be
certified for use in zone 1 areas as MODULE Sloop detection (input and output)
;circuit (input and output) ; fault(s) ;supply failure, e.g. low battery
voltage (of UPS);unit failure; LEVEL SETTINGSas minimum for point detectors, see (2.2.2.1)
for recommend ed alarmpically for open path detectors, see (2.2.3.2) for
recommend ed LOS alarm
typical longterm random drift of flammable gas detectors is in the order of 3
% LFL. Setting the typical long term random drift of H
FOR CIRCUIT INTEGRIT Yuld be individually wired to the
control module or to the FGS IPS.initiators may be applied in buildings. Zoned circuitry
shall be achieved by SYSTEMS REQUIREME NTS
specification and testing facilities
requirements
and error message sMagnetic Compatibilit y (EMC )supplyof sensors
PRACTICES FOR DETECTORS AND ASSOCIATED EQUIPMENT
may be positioned at approximately the same
elevation as the potential source ofs are generally the preferred technology for detecting gas leaks in open areas.tioned so that they are easily
accessible for calibration andply and electronic measuring circuits shall be located in a non-hazardous area, e.g. the definitions
(fire detection) The probability that an assigned set of(gas detection) The
probability that an assigned set oftarget The minimum acceptable performance of atolerance
Ability of a fire or gas detection system todegree of fault tolerance If the minimum
degree of fault tolerance is T, of failure A failure of a set of fire or gas detectors is
requirements for F&G systems requirement for establishing the performance of a set of detectors
of flammable gas detectors
inlets for HVAC (heating, ventilation and air conditioning );outlets of
enclosed hazardous areas/modul es, etc.;inlets to analyser houses ;suction of instrument
air compressors ;to furnaces in gas plants;to air compressors in gas plants;to
breathing air systems.
the temperture and molecular weight of a gas have an impact on buoyancy. In particular, of acoustic leak detectors
of H and positioning of smoke and fire detectors
detectors ntilation patterns, i.e. draught due to air
conditioning ;diluting effects of air conditioning and ventilation systems .type detector
sfloors in computer rooms, auxiliary rooms, and inside electrical andcable trays in
buildings . detector sceiling and depth to which the detector projects
below the ceiling ;patterns in the building/roo m;blocking the heat flow to the detector,
e.g. system cabinets .detection tubing DEP 32.30.20.11Gen.Septem ber
2002Page 36resistant to ultraviolet light; for example, Polyflo 44PF. Such tubing is supplied
byImperial Eastman or by Samuel Moore; however, an equivalent may be used followingapp
roval by the Principal.Th e instrument air in the tubing shall be maintained at an appropriate
pressure, typically 1.5bar (ga), for the transmitter it is to operate, as this relates to rupture
temperature .
NOTE: The instrument air lines for interconnections and for connecting the tubing to the instrument
airheader shall be of plasticsheathed copper tubing.
For a typical application of fire detection tubing, refer to Standard
Drawings S 88.020 andS 88.021.Syst ems based on fire detection tubing are vulnerable and prone to
failures induced byexposure to chemicals or by mechanical damage. The Principal
shall be consulted on theuse of fire detection tubing.A sturdy alternative, although
possibly slower to respond to fire, is a point detection systemwith frangible bulb
detectors in AISI 316 tee fittings interconnect ed by AISI 316 tubing andmounted at twometre
intervals. Fusible plugs may be used instead of frangible bulbs.3) Optical type fire
detectorsOp tical type fire detectors are line-ofsight devices and shall therefore be
positioned so thatthey can see the entire section to be protected. They shall be mounted
so that they are freefrom the effects of vibration and shock, and spaced in accordance with the
detectionobj ectives, see (Appendix IV).Infrared (IR) lenses shall be protected against the effects of
water and the possibility offreezing.
NOTE: Certain hydrocarbons and other gases, e.g., carbon dioxide, may interfere
with the signal to the IRdetector.
Ultraviolet (UV) detectors shall be protected from
possible fouling of their windows / lensesbut such protection shall not impair their
operation.O ptical type fire detectors provide rapid response and good space
detection see (2.6.1.3).
3.9.8 Positioning of beacons
Beacons shall be positioned
so that they will be visible in the area for which they are toprovide a warning, but they should
be accessible for maintenanc e. Suggested locations arepipe racks, top
corners of buildings and the principal passages inside auxiliary buildings.
3.9.9 Positioning of manual call points
Manual call points shall be positioned (see DEP
80.47.10.30Gen) so that they stand outagainst the background, i.e. they shall be clearly
recognisable from a distance. If necessaryth ey shall be provided with signs to enhance their
visibility from access roads.Manu al call points should be positioned as follows:along roads in the plant
area at intervals not exceeding 100 m, preferably at or near tolamp posts;along roads
in storage / tank areas not exceeding intervals of 200 m; near or at locations having a
-
higher risk such as remote pump floors, oil catchers,ma nifolds, motor control
centres, jetty heads; on offshore locations, at escape routes (entrance to bridges and staircases);-
inside buildings, office entrance, canteens, warehouses, medical centres, gate
andguardho uses, etc.;inside the plant and positioned:outside power station(s);outside
analyser house(s);outside control room(s);outside utility buildings;outside
hazardous enclosed areas; DEP 32.30.20.11Gen.Septem ber 2002Page 37- along
logical escape routes. DEP 32.30.20.11Gen.Septem ber 2002Page 383.10
DETECTOR VOTINGDete ctor voting is one method of ensuring that fire or gas detector configuratio
ns are robustagain st failure and robust against spurious alarms. But detector voting may
not berequired; for example, where detectors or detector systems themselves are robust,
orwhere appropriate actions are taken by experienced operators.Cl early, combining detectors to
vote logically in any configuratio n requires additionalde tectors to provide the same
degree of coverage. Generally, the number of detectorsreq uired increases as the voting
architecture become more complex (Appendix IV) listspossible configuratio ns.An
architecture finding widespread use is that referred to as 1oo2D. This strategy requires2
detectors for confirmed Fire or Gas as with 2ooN, except that under detector faultconditio
ns, e.g. if a detector has failed, the logic reverts to 1ooN (i.e. the logic considersfail ed detectors as alarms,
which is the equivalent of voting High on detector fault). Thishas the major advantage
that detection coverage is not lost if a detector has failed, as with2ooN in fact coverage is
increased. The concept, however, is slightly less robust againstspuri ous trips when alarms
are produced from F&G zones that have failed detectors, butthis lower robustness
does not affect the entire facility. Furthermore , modern detectorsha ve a typical MTBF of 10
years or more, so this drawback is marginal and inconsequen tialwhen judged
against the improvemen t in safety performance . Nevertheles s, this highlightsth e need for
prompt action to repair faulty instruments. The main reason for adopting 1oo2D detector
voting is that the required performance (coverage) is delivered with the minimum number of
detectors. Other detector votingconfig urations may be required to achieve identified
safety or economic needs, but suchconfigu rations will require a greater number of detectors.