Ventilation Calculation

This document provides a calculation of ventilation requirements for various rooms on the ground floor and mezzanine floor of a building based on ASHRAE 62.1-2007 standards. It lists the room name, maximum population, floor area, outdoor air flow requirements, and whether the planned fresh air being provided meets the minimum standard for each room.

Uploaded by

ARUL SANKARAN
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
132 views1 page

Ventilation Calculation

This document provides a calculation of ventilation requirements for various rooms on the ground floor and mezzanine floor of a building based on ASHRAE 62.1-2007 standards. It lists the room name, maximum population, floor area, outdoor air flow requirements, and whether the planned fresh air being provided meets the minimum standard for each room.

Uploaded by

ARUL SANKARAN
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 1

Single Zone Ventilation Calculation

For EQ. Pr -1 : Minimum IAQ Performance


Minimum ASHRAE 62.1-2007 Requirements

Fresh air Meeting


Breathing Zone PROVIDED to Minimum
Zone air
Max. Zone Zone Floor Zone Outdoor Outdoor the zone (must Standard
People Outdoor Area Outdoor distribution REQUIRED
LEVEL Served By ROOM NAME Population Area (sq.m) Air flow Air Flow meet values in Requireme
Air Rate,Rp Air Rate, Ra effectiveness AIRFLOW
Pz Az (Vbz= (Voz = drawing) nt
Ez (Vot) (l/s)
RpPz+RaAz) Vbz/Ez) (l/s)

Ground Floor
GF GAC-01 MD OFFICE 2 2.5 16 0.30 10 1 10 10 19 YES
GF GAC-02 RECEPTION 5 2.5 44 0.30 26 1 26 26 28 YES
GF GAC-03 OPEN OFFICE/CORR 6 2.5 65 0.30 35 1 35 35 35 YES
GF GAC-04 MEETING ROOM 4 2.5 15 0.30 15 1 15 15 26 YES
GF GAC-06 CABIN / FILE ROOM 8 2.5 31 0.30 29 1 29 29 29 NO
GF GAC-07 SUPERVISOR 6 2.5 6 0.30 17 1 17 17 19 YES

MF MAC-01 PRAYER ROOM/DIN 7 2.5 71 0.30 39 1 39 39 40 YES