EPC99.

09E•General 11/10/00 16:25 Page 81

EPCE99-09E

General Catalogue 2000


Hydronic Commercial VRV
Guarantee VRV
Long Life Europe
Residential
Hydronic Long Life
Reliability Residential Quality
Quality
Commercial
Long Life
G eneral
Residential
Industrial Environment
Europe
Hydronic
Guarantee

Environment Guarantee Safety Long Life VRV


Daikin units comply with the European regulations
that guarantee the safety of the product.
Daikin Europe NV is approved by LRQA for its Quality
Management System in accordance with the ISO9001 standard.
ISO9001 pertains to quality assurance regarding design,
Commercial Residential
Accurate C
Quality
atalogue
Reliability
Residential
development, manufacturing as well as to services related to
the product.
Safety Quality
Environment Commercial
ISO14001 assures an effective environmental management Residential
Daikin Europe NV is participating in
the EUROVENT Certification Programme.
Products are as listed in the EUROVENT
system in order to help protect human health and the
environment from the potential impact of our activities, products Environment Long Life Hydronic Safety Residential
Directory of Certified Products.
and services and to assist in maintaining and improving the
quality of the environment.
Residentia Guarantee Commercial Long Life
Commercial
Quality Europe
Safety
Commercial Residential Environment
Reliability
1999 Commercia Hydronic
Residential
Daikin products are distributed by:
Commercial
Europe Reliability
VRV Quality Commercial
Daikin Air Conditioning Systems
Residential VRV Environment Reliability
Printed in Belgium on non-chlorinated paper
EPCE99-09E / 4,500 / 10/00 La Movida

VRV
Specifications are subject to change without prior notice
To consult the explanation of the pictogrammes,
please open the flap of this catalogue.
Zandvoordestraat 300
B-8400 Oostende, Belgium
Internet: http://www.daikin.be AIR CONDITIONING SYSTEMS
Infrared remote control
Infrared remote control with LCD to start, stop and regulate
the air conditioner from a distance.
Wired remote control
Wired remote control to start, stop and regulate the air conditioner from a
distance.
Centralised control
Centralised control to start, stop and regulate several air conditioners
from one central point.

Auto-swing
Possibility to select automatic moving of the air discharge louvre, for
uniform air flow and temperature distribution.

Draught prevention
When starting to warm up or when the thermostat is off, the air discharge direction is set horizontally and
the fan to low speed, to prevent draught. After warming up, air discharge and fan speed are set as desired.
Auto-restart
The unit restarts automatically at the original settings after power.

Auto cooling-heating changeover


Automatically selects cooling or heating mode to achieve the set temperature
(heat pump types only).
Dry programme
Allows humidity levels to be reduced without variations in room temperature.

Fan only
The air conditioner can be used as fan, blowing air without cooling
or heating.
Auto fan speed
Automatically selects the necessary fan speed to reach or maintain
the set temperature.
Fan speed steps
Allows to select up to the given number of fan speed.

Timer
Allows to preset the air conditioner to start/stop at a specified time.

24 Hour timer
Timer can be set to start cooling/heating anytime during a 24-hours period.

Night set mode


Saves energy, by preventing overcooling or overheating during night time.

Ceiling soiling prevention


A special function prevents air blowing out too long in horizontal position,
to prevent ceiling stains.
Self-diagnosis
Simplifies maintenance by indicating system faults or operating anomalies.

Scroll compressor
Silent, reliable Daikin compressor used in medium sized outdoor units.

Energy efficiency
Daikin air conditioners are energy efficient and economical.

Whisper quiet
Daikin indoor units are whisper quiet. Also the outdoor units are
guaranteed not to disturb the quiet of the neighbourhood.
Double thermostat function
Controls the temperature via a sensor on the air conditioner or via a sensor on
the remote control.
Air filter
Removes airborne dust particles to ensure a steady supply of clean air.

Air purification filter


Removes airborne dust particles and prevents the propagation of bacteria
and viruses to ensure a steady supply of clean air.
Drain pump kit
Facilitates condensation draining from the indoor unit.

Twin/triple/double twin application


2, 3 or 4 indoor units can be connected to only 1 outdoor unit even if they have different capacities.
All indoor units operate within the same mode (cooling or heating) from one remote control.
Multi model application
Up to 5 indoor units (even different capacities) can be connected to a single outdoor unit.
All indoor units can individually be operated within the same mode.
Powerful mode
If the temperature in the room is too high/low, it can be cooled down/heated quickly by selecting
the ‘powerful mode’. After the powerful mode is turned off, the unit returns to the preset mode.
Movement sensor
The sensor detects whether someone is in the room. When the room is empty, the unit switches to
economy mode after 20 minutes and restarts when a person enters the room.
Comfortable sleeping mode
Increased comfort function that follows a specific temperature fluctuation
rhythm.
EPC99.09E•General 11/10/00 16:25 Page 80

Power supply
T1 = 3~, 220V, 50Hz W1 = 3N~, 400V, 50Hz
V1 = 1~, 230V, 50Hz Y1 = 3~, 400V, 50Hz
VE = 1~, 230V, 50Hz

Measuring conditions
COOLING ONLY
1) nominal cooling capacities are based on:
indoor temperature 27°CDB/19°CWB (UAT: 19.5°CWB/FWHC: 19.4°CWB)
outdoor temperature 35°CDB
refrigerant piping length 7.5m - 8/5m VRV
level difference 0m

HEAT PUMP
1) nominal cooling capacities are based on:
F oreword
indoor temperature 27°CDB/19°CWB (UATY: 19.5°CWB)
outdoor temperature 35°CDB/24°CWB “ MIGHTY OAKS FROM LITTLE ACORNS GROW “
refrigerant piping length 7.5m - 8/5m VRV
level difference 0m In 1972, Daikin Industries Ltd, established its European headquarters
2) nominal heating capacities are based on:
in Ostend, Belgium in answer to the rapidly growing European demand
indoor temperature 20°CDB/12°CWB (UATY: 21°CDB)
outdoor temperature 7°CDB/6°CWB for high quality air conditioning. Perceived at first, simply as an
refrigerant piping length 7.5m - 8/5m VRV assembly centre for Japanese manufactured equipment, the nascent
level difference 0m
plant - occupying a mere 5,000 m2 - soon evolved into a supply base
for a Europe wide distribution network. Since those early years,
Daikin Europe has benefited from continuous investment on the part of
CHILLERS: its parent company and now enjoys a position of pre eminence among
EUWA-HD(Z) / EUWA*-KA(X) / EUWA*-LZ / EUWAC-FA: evaporator: 12°C/7°C; ambient: 35°C
the largest and best known names in European air conditioning.
EUWY-HD: evaporator: 12°C/7°C; ambient: 35°C
condenser: 40°C/45°C; ambient: 7°CDB/6°CWB The company’s record of spectacular growth in both turnover and
EUW-KX: evaporator: 12°C/7°C; condenser: 30°C/35°C (cooling); 40°C/45°C (heating) production capacity is to be envied among engineering manufacturers
EUW(H)-FA/FB: evaporator: 12.5°C/7°C; condenser: 29,5°C/35°C (cooling); 39.5°C/45°C (heating)
in general and the air conditioning sector in particular.
EUWL*-KX: evaporator: 12.5°C/7°C; condensing temperature: 40OC
Fan coils: cooling: ambient 27°CDB/19°CWB
entering water temperature 7°C Widely recognised as the most advanced air conditioning production
heating: ambient 20°CDB
entering water temperature 50°C
facility in Europe, the Ostend plant is responsible for well over 80% of
FWHC: cooling: ambient 26.7°CDB/19°CWB Daikin Europe products and occupies a site approaching 150,000 m2.
entering water temperature 7.2°C
heating: ambient 20°CDB
entering water temperature 60°C

The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value, depending on the distance and acoustic environment
(for measuring conditions: please refer to the technical databooks).
The sound power level is an absolute value indicating the “power” which a sound source generates.
For more detailed information please consult our technical databooks.
78 3
EPC99.09E•General 11/10/00 16:14 Page 6

FOREWORD 3 3. Hi-VRV

• The complete air conditioning system 44


TA B L E O F C O N T E N T S 4
• Variable Refrigerant Volume 46
• VRV Inverter heat pump series 46
DAIKIN EUROPE 7 • VRV Heat recover y series 47
• VRV Plus series using R-407C 48 New
1. A/C FOR RESIDENTIAL USE • VRV Plus series using R-22 49
• Wall mounted unit FT(Y)-G 10 • VRV Indoor units 50
• Wall mounted unit FT-GZ 11 • Heat Recovery Ventilation 57 New
• Wall mounted, Inverter controlled unit - FTX/FTK-JA 12 New • Daikin Air Conditioning Management System 58
• Wall mounted, Inverter controlled unit - FTX/FTK-H 13 • Hi-VRV Selection programme 59
• Wall mounted, Inverter controlled unit - FTX-JZ 14
• Concealed ceiling, Inverter controlled unit - CDX/CDK-HA 15 New
• Floor standing unit FV(Y)/FCVY-D 16
• Floor standing inverter FVXT-G 17
• Concealed ceiling unit FHE(Y)B-BA/GZ 18
• Flexi type FL(Y)-G 19
T able of contents
2. A/C FOR COMMERCIAL USE 4. HYDRONIC SYSTEMS

• Ceiling suspended unit FH(Y)-FJ 22 • Concealed ceiling CHILLERS


• Ceiling suspended FH(Y)B-GZ 29 Power & precision 61
FH(Y)-GZ 23 • Concealed ceiling
Air Cooled Water Cooled
• 4-way blow ceiling FHYB-F 30
• EUWA/Y 62 /Remote Condenser
suspended cassette FUY-FJ 24 • Wall mounted unit FAY-FJ 31
• EUWA-HZ 63 • EUW(H) 68
• Ceiling mounted corner • Concealed ceiling FDY-F 32
• EUWA* 64 • EUW(L)*-KX 69
cassette FH(Y)K-FJ 25 • Packaged units UAT(Y) 33
• EUWA*-KX 65 DICN
• 4-way blow ceiling mounted Daikin Integrated
• EUWA*-LZ 66
cassette FH(Y)C-BJ 26 Chiller Network 70
• EUWAC 67
• 4-way blow ceiling mounted
cassette FH(Y)C-BZ 27
HYDRAULIC MODULE
• Concealed ceiling
FH(Y)B-FK 28 • EHMC 71

FAN COIL UNITS


• FWV(M)/FWH(M)/FWHC 72
OUTDOOR UNITS
• Pair application - cooling only 35 DAIKIN CHILLER SELECTION SOFTWARE
• Pair application - heat pump 36
• Selection software 75
• Pair application - Inverter controlled 37
• Sky air application - Inverter controlled 38
• Condensing units ER/ERC 39 5. CONDENSING UNITS
• Multi model application - possible indoor units 40
• Multi model application 41 • ER 77
• Multi model application - Inverter controlled 42
• Twin/triple/double twin application 43 POWER SUPPLY & MEASURING CONDITIONS 78

4 5
EPC99.09E•General 11/10/00 16:14 Page 8

D aikin Europe
THE PRODUCTS
Daikin Europe designs and produces an extensive range of hi tech air
conditioning equipment, including air and water cooled chillers, packaged air
conditioners, splits and multi splits, VRV and Sky Air systems for commercial,
industrial and residential comfort cooling and process applications.
Around 95% of production is exported via the company’s distribution network
to countries stretching from Scandinavia to Africa.

DAIKIN QUALITY
Daikin’s much envied quality levels, stem quite simply from the close attention
paid to design, production and testing procedures as well as post sales
support. To this end, every bought in component is carefully selected and
rigorously tested to verify its contribution to product quality and reliability.

DAIKIN EUROPE NV - BELGIUM


DAIKIN AND THE ENVIRONMENT
Some years ago, Daikin launched the very first optimised HFC R-134a chiller
into Europe and has since built on this early success with a complete range of
air cooled units. The company has also introduced new VRV systems, chillers
and split systems, operating with HFC R-407C refrigerant, further indications
that Daikin’s unique position as the world’s only manufacturer of both air
conditioning equipment and refrigerant gases, will contribute to a successful
outcome in the near future.

TRAINING
The continual application of leading edge technology to air conditioning has
considerable bearing on the likely future shape and direction of the European
market and only a thorough understanding of new generation Daikin products
and systems will enable their full commercial potential to be realised. Training
has long been accepted as a cornerstone of the company’s sales development
and customer support programmes and is vital if a broader understanding of
the present and future impact of air conditioning is to be achieved.

7
A/C for residential use
1
Daikin residential air conditioning is the modern, economic
and efficient way to switch on to springtime - in the living room,
dining room, kitchen or bedroom, night and day, throughout the year.

Daikin air conditioning units are easy to install, easy to use, ultra
reliable, quiet running and come in an elegant and up to date range
of wall, floor and ceiling mounted indoor models.

Also, the incorporation of inverter control enables Daikin to bring


air conditioning technology of the future to the residential market
today. Inverter control cuts start up time and energy consumption

STYLISH AND ELEGANT


by almost a third, alters unit output to suit outdoor conditions,
improves performance relative to power input, ensures a more even
room temperature and eliminates power surges and stop/start cycles.

9
EPC99.09E•General 11/10/00 16:14 Page 12

optional FTY optional

FT(Y)18/25(22)/35G
FT25-35GZV1NB
FT 5 steps

p.40 5 steps p.40

FT(Y)40G

WA L L M O U N T E D U N I T
FT(Y)-G FT-GZ WA L L M O U N T E D U N I T
FT45GZV1NB

• lightweight and compact


• efficient and even horizontal and vertical
air distribution
• air purification and deodorizing filter
• easily washable front panel

• optimised for use with R-407C


• swing compressor
• lightweight and compact
Refrigerant: R-22 • Power supply: V1: 1~, 230V, 50 Hz
• automatic airflow director ensures
COOLING ONLY FT18GV1B FT25GV1B FT35GV1B FT40GV1B FT45GV1B FT60GV1B uniform airflow and temperature
Cooling capacity kW 1.8 2.45 3.30/3.35 4.15 5.25 6.35 distribution
Nominal input kW 0.55 0.86 1.27 1.58 2.05/2.16 2.35 • optimised unit in new and smaller
Dimensions HxWxD mm 250x750x180 298x790x189 298x1,050x190
Weight kg 7 7 7 9 12 12 casing
Air flow rate H/L m3/min 7.3/4.7 6.6/4.2 7.8/5.5 8.6/6.0 11.8/9.1 13.3/10.3 • powerful mode can be selected for
Sound pressure level H/L dB(A) 36/26 36/26 39/31 41/32 43/36 46/38
rapid cooling
Sound power level H dB(A) 51 51 54 55 58 61
Outdoor unit see page 35 RE-GA7V1 RE-GA7V1/R-DC7V11 RE-GA7V1/R-DC7V11 RE-GA7V1 R-DC7V11/W11 R-FA7V1/W1 • washable front panel
• energy efficient
Refrigerant: R-22 • Power supply: V1: 1~, 230V, 50 Hz

HEAT PUMP FTY18GV1B FTY22GV1B FTY35GV1B FTY40GV1B FTY45GV1B FTY60GV1B


Cooling capacity kW 1.85 2.55/2.40 3.50/3.25 3.9 4.9 6.0
Refrigerant: R-407C • Power supply: V1: 1~, 230V, 50 Hz
Heating capacity kW 1.85 3.20/2.65 4.10/3.60 4.7 5.55 7.15
Nominal input cooling kW 0.59 1.10/0.86 1.44/1.19 1.63 2.06 2.43
heating kW 0.52 1.14/0.78 1.50/1.22 1.62 1.90 2.4 COOLING ONLY FT25GZV1NB FT35GZV1NB FT45GZV1NB
Dimensions HxWxD mm 250x750x180 298x790x189 298x1,050x190 Cooling capacity kW 2.4 3.45 5.1
Weight kg 7 7 7 9 12 12 Nominal input kW 0.84 1.24 2.10 (V11)/2.0(W11)
Air flow rate (H/L) cooling m3/min 7.1/4.5 6.6/4.2 7.8/5.5 8.6/6.0 11.8/9.5 13.3/9.8 Dimensions HxWxD mm 250x750x180 298x1,050x190
heating m3/min 6.6/4.8 7.3/4.8 8.0/5.9 9.7/7.6 14.9/10.0 15.5/11.1 Weight kg 7 7 12
Sound pressure cooling dB(A) 36/26 36/26 39/31 40/33 43/36 46/38 Air flow rate H/L m3/min 6.6/4.2 7.8/5.5 11.8/9.1
level (H/L) heating dB(A) 35/26 35/26 38/30 41/33 44/34 45/34 Sound pressure level H/L dB(A) 36/26 39/31 43/36
Sound power level (H) dB(A) 51 51 54 55 58 61 Sound power level H dB(A) 51 55 58
Outdoor unit see page 36 REY-GA7V1 RY-DB7V1/REY-GA7V1 RY-DA7V1/REY-GA7V1 REY-GA7V1 RY-DB7V1 RY-FA7V1 Outdoor unit see page 35 R-GZ7V11 R-GZ7V11 R-GZ7V11/W11

10 11
EPC99.09E•General 11/10/00 16:15 Page 14

optional FTX only optional FTX only

New p. 43 FTK only 5 steps p. 43 FTK only 5 steps

WA L L M O U N T E D
INVERTER
CONTROLLED UNIT
FTX/FTK-JA FTX/FTK-H WA L L M O U N T E D
INVERTER
CONTROLLED UNIT

• consumes 30% less power than non-


inverter models
• achieves set temperature more quickly
• diffuser and flexible louvre improves air
distribution
• easily washable front panel
• air purification and deodorizing filter
• supersilent operation
• movement sensor: • consumes 30% less power than non-
An infrared sensor on the unit automatically detects inverter models
the presence of any occupant in the room within 5m.
• achieves set temperature more quickly
As long as the room remains occupied, the unit functions
normally but will switch to economy mode 20 minutes after • the indoor units are equipped with an
the occupant leaves. This important new feature prevents automatic vertical airflow director
energy wastage in empty rooms and cuts power consumption by 30% in heating mode and 20% in cooling mode.
• diffuser and flexible louvre improves air
Air conditioning will start up again as soon as anybody enters an empty room, establishing all round comfort in virtually
no time at all. distribution
The sensor can be positioned vertically or horizontally, on either the left or right of the unit. • easily washable front panel
• comfortable sleeping mode • air purification and deodorizing filter
This innovative mode is an increased comfort function that follows a specific temperature fluctuation rhythm.
• supersilent operation
Uninterrupted comfort and peaceful sleep can thus be enjoyed throughout the night.
The “Comfortable sleeping mode” is the result of a three-year joint study of the Human Engineering Laboratory of
University of Occupational and Environmental Health in Japan.

Refrigerant: R-22 • Power supply: V1: 1~, 230V, 50 Hz


Pair/Multi Pair/Multi Refrigerant: R-22 • Power supply: V1: 1~, 230V, 50 Hz
CO/HP FTK25JAV1NB FTK35JAV1NB FTX25JAV1NB FTX35JAV1NB Multi Multi
Cooling capacity (1) min.-nom.-max kW 1.3 ~ 2.5 ~ 3.0 1.4 ~ 3.5 ~ 3.8 1.3 ~ 2.5 ~ 3.0 1.4 ~ 3.43 ~ 3.8 CO/HP FTK50HV1NB FTK60HV1NB FTX50HV1NB FTX60HV1NB
Heating capacity (1) min.-nom.-max kW - - 1.3 ~ 3.4 ~ 4.0 1.4 ~ 4.1 ~ 5.1 Cooling capacity (1) min.-nom.-max kW * * * *
Nominal input (1) cooling kW 0.43 ~ 0.94 ~ 1.25 0.47 ~ 1.35 ~ 1.72 0.35 ~ 0.98 ~ 1.35 0.5 ~ 1.43 ~ 1.72 Heating capacity (1) min.-nom.-max kW - - * *
heating kW - - 0.35 ~ 1.13 ~ 1.35 0.4 ~ 1.38 ~ 1.9 Nominal input cooling kW * * * *
Dimensions HxWxD mm 273x784x185 273x784x185 heating kW - - * *
Weight kg 7.5 7.5 7.5 7.5 Dimensions HxWxD mm 298x1,050x190 298x1,050x190
Air flow rate (H/L) cooling m3/min 7.1/4.9 7.4/4.7 7.1/4.6 7.4/4.7 Weight kg 12 12 12 12
heating m3/min - - 8.4/5.7 8.4/5.9 Air flow rate (H/L) cooling m3/min 12.9/9.4 14.0/10.3 12.9/9.4 14.0/10.3
Sound pressure level cooling dBA 38/26 39/27 38/26 39/27 heating m3/min - - 15.2/11.0 16.3/11.7
(H/L) heating dBA - - 38/26 39/27 Sound pressure level cooling dBA 44/35 46/38 44/35 46/38
Sound power level cooling dBA 54 55 54 55 (H/L) heating dBA - - 44/33 46/34
(H) heating dBA - - 54 55 Sound power level H dBA 60 62 60 62
Outdoor unit see page 37 RK-JV1NB RK-JV1NB RX-JV1NB RX-JV1NB Outdoor unit see page 37 only for multi model application only for multi model application

(1) Units should be selected on nominal capacity. Maximum capacity is limited to peak periods. *Capacity and nominal input depend on the combinations between outdoor unit and indoor units.
12 13
(1) Units should be selected on nominal capacity. Maximum capacity is limited to peak periods.
EPC99.09E•General 11/10/00 16:15 Page 16

optional optional 5 steps

CDK optional p.43

WALL MOUNTED INVERTER


CONTROLLED UNIT
FTX-JZ CDK/CDX-HA CONCEALED CEILING
INVERTER CONTROLLED
UNIT

• highly energy efficient -


consumes 30% less energy
• lightweight and compact
• optimised for use with R-407C • only suction and discharge grilles
• swing compressor are visible
• highly energy efficient - consumes • blends unobtrusively into any
30% less energy interior decor
• super silent operation • extremely quiet in operation both
• compact indoors and outdoors
• washable and easily removable
front panel

Refrigerant: R-22 • Power supply: V1: 1~, 230V, 50 Hz

MULTI COOLING ONLY CDK25HAV1NB CDK35HAV1NB CDK50HAV1NB CDK60HAV1NB


Cooling capacity kW * * * *
Nominal input kW * * * *
Dimensions HxWxD mm 260x900x580
Weight kg 23 23 24 24
Air flow rate H/L m3/min 13.0/11.0 13.0/11.0 13.0/11.0 14.5/11.5
Sound pressure level H/L dBA 39/36 39/36 42/39 44/41
Refrigerant: R-407C • Power supply: V1: 1~, 230V, 50 Hz Sound power level H dBA 55 55 58 60
Outdoor unit see page 42 4MK90HV1NB
HEAT PUMP FTX25JZV1NB FTX35JZV1NB
Cooling capacity (1) min.-nom.-max kW 1.5 ~ 2.6 ~ 3.1 1.5 ~ 3.45 ~ 3.6 Refrigerant: R-22 • Power supply: V1: 1~, 230V, 50 Hz
Heating capacity (1) min.-nom.-max kW 1.5 ~ 3.6 ~ 4.6 1.5 ~ 4.2 ~ 4.8
Nominal input (1) cooling kW 0.5 ~ 1.0 ~ 1.3 0.5 ~ 1.5 ~ 1.55
MULTI HEAT PUMP CDX25HAV1NB CDX35HAV1NB CDX50HAV1NB CDX60HAV1NB
heating kW 0.46~ 1.21 ~ 1.53 0.46 ~ 1.52 ~ 1.76
Cooling capacity kW * * * *
Dimensions HxWxD mm 273x784x185
Heating capacity kW * * * *
Weight kg 7.5 7.5
Nominal input kW * * * *
Air flow rate (H/L) cooling m3/min 7.1/5.2 7.4/5.2
Dimensions HxWxD mm 260x900x580
heating m3/min 8.4/5.9 8.7/5.9
Weight kg 23 23 24 24
Sound pressure cooling dB(A) 38/30 39/31
Air flow rate H/L m3/min 13.0/11.0 13.0/11.0 13.0/11.0 14.5/11.5
level (H/L) heating dB(A) 38/30 39/31
Sound press. level cooling dBA 39/36 39/36 42/39 44/41
Sound power level (H) cooling/heating dB(A) 55 55
(H/L) heating dBA 40/36 40/36 42/38 44/40
Outdoor unit see page 37 RXT25JZV1NB RXT35JZV1NB
Sound power level (H) cooling/heating dBA 55/56 55/56 58/58 60/60
(1) Units should be selected on nominal capacity. Outdoor unit see page 42 2MX52HV1NB/3MX68HV1NB/4MX80HV1NB
Maximum capacity is limited to peak periods.
* Capacity and nominal input depend on the combinations between outdoor unit and indoor units. 15
14
EPC99.09E•General 11/10/00 16:15 Page 18

FVY/FCVY FV only optional FVY optional 5 steps

FVY only p.40

FV only FV : 3 steps
F(C)VY : 5 steps

F L O O R S TA N D I N G U N I T
FV(Y)/FCVY-D FVXT-G F L O O R S TA N D I N G
INVERTER

• can be installed against a


wall or recessed
• compact design
• horizontal and/or vertical • consumes 30% less power than
air distribution non-inverter models
• remote control (FVY/FCVY) or • PAM (Pulse Amplitude Modulation)
wired remote control (FV) inverter technology
• lightweight and compact
• can be installed against a wall or
recessed
• dual air discharge blow for better
air distribution
• washable air suction grille
Refrigerant: R-22 • Power supply: V1: 1~, 230V, 50 Hz
• air purification filter
COOLING ONLY FV25D7V1 FV35D7V1 FV45D7V1 FV60D7V1
Cooling capacity kW 2.38 3.48 5.13 6.35
Nominal input kW 0.91 1.37 2.23 2.35
Dimensions HxWxD mm 600x750x205 600x870x205
Weight kg 19 19 19 22
Air flow rate H/L m3/min 9.3/6.5 9.3/6.5 11.0/8.7 12.5/11.2
Sound pressure level H/L dB(A) 39/31 40/32 43/37 46/40
Sound power level H dB(A) 47 48 51 54
Outdoor unit see page 35 R-DC7V11 R-DC7V11 R-DC7V11/W11 R-FA7V1/W1
Refrigerant: R-22 • Power supply: V1: 1~, 230V, 50 Hz

Refrigerant: R-22 • Power supply: V1: 1~, 230V, 50 Hz


HEAT PUMP FVXT40GV1NB FVXT50GV1NB
Cooling capacity (1) min.-nom.-max kW 0.9 - 4.0 - 4.5 0.9 - 5.0 - 5.2
HEAT PUMP FVY223D7V1 FVY353D7V1 FVY453D7V1 FCVY223D7V1** FCVY353D7V1** FCVY453D7V1** Heating capacity (1) min.-nom.-max kW 0.9 - 6.0 - 7.5 0.9 - 6.6 - 7.7
Cooling capacity kW 2.4 3.6 4.9 * * *
Nominal input (1) cooling kW 0.19 - 1.26 - 1.46 0.19 - 2.08 - 2.11
Heating capacity kW 3.2 4.1 5.55 * * *
heating kW 0.19 - 1.86 - 2.81 0.19 - 2.35 - 3.05
Nominal input cooling kW 1.09 1.48 2.02 * * *
Dimensions HxWxD mm 600x650x195
heating kW 1.17 1.50 1.84 * * *
Weight kg 13 13
Dimensions HxWxD mm 600x750x205 600x870x205 600x750x205 600x870x205
Air flow rate (H/L) cooling m3/min 9.6 - 7.1 10.8 - 7.7
Weight kg 19 19 22 19 19 22
heating m3/min 12.5 - 8.7 13.2 - 9.4
Air flow rate (H/L) cooling m3/min 9.0/6.3 9.3/6.5 11/8.7 9.0/6.5 9.3/6.5 11/8.7
Sound pressure cooling dB(A) 41/34 44/36
heating m3/min 10/7.4 10.3/7.4 13.2/9.7 10/7.4 10.3/7.4 13.2/9.7
level (H/L) heating dB(A) 43/34 45/36
Sound pressure cooling dB(A) 38/30 40/31 42/37 40/32 41/32 44/37
Sound power level (H) cooling/heating dB(A) 53 56
level (H/L) heating dB(A) 39/30 41/30 44/38 40/32 41/32 44/37
Outdoor unit see page 37 RXT40GV1NB RXT50GV1NB
Sound power level (H) cooling/heating dB(A) 46/47 48/49 50/52 48/48 49/49 52/52
Outdoor unit see page 36/41 RY-DB7V1 RY-DA7V1 RY-DB7V1 MY-DA7V1/CJ7V1/W1 MY-DA7V1/CJ7V1/W1 MY-DA7V1/CJ7V1/W1 (1) Units should be selected on nominal capacity.
Maximum capacity is limited to peak periods.
16 * Capacity and nominal input depend on the combinations between outdoor unit and indoor units. 17
** FCVY-D is not within the scope of the Eurovent certification programme.
EPC99.09E•General 11/10/00 16:16 Page 20

FHEYB FHEB optional FLY only

p.40 2 steps

p.40 FL only 5 steps

CONCEALED CEILING UNIT


FHE(Y)B-BA/GZ FL(Y)-G FLEXI TYPE UNIT

• compact • lightweight
• suction and discharge grilles only are visible • can be fitted on either ceiling
• rear or bottom air suction or lower part of wall (e.g.
• drain pan on left or right beneath a window)
• ideal for use in hotel bedrooms • powerful mode ensures a
• the air duct between the indoor unit and quick adaptation to
discharge grille can be up to 0.5m long temperature variations
• forced ON/OFF function: energy saving and • automatic airflow director
comfort increasing feature ensures uniform airflow and
temperature distribution

Refrigerant: R-22/R-407C • Power supply: V1: 1~, 230V, 50 Hz Refrigerant: R-22 • Power supply: V1: 1~, 230V, 50 Hz

COOLING ONLY FHEB18BA7V1 FHEB25GZ7V1* COOLING ONLY FL25GV1NB FL35GV1NB FL40GV1NB FL45GV1NB
Cooling capacity kW 1.7 2.4/2.4 Cooling capacity kW 2.45 3.35/3.30 4.15 5.25
Nominal input kW 0.54 0.88/0.88 Nominal input kW 0.86 1.27 1.63 2.13(V11)/2.02(W11)
Dimensions HxWxD mm 230x652x502 Dimensions HxWxD mm 490x1,050x200
Weight kg 17 17 Weight kg 16 16 17 17
Air flow rate H/L m3/min 6.5/5.2 6.5/5.2 Air flow rate H/L m3/min 7.5/6.0 8.0/6.4 6.5/5.1 10.7/6.1
Sound pressure level H/L dB(A) 34/28 35/28 Sound pressure level H/L dB(A) 37/31 38/32 39/33 47/36
Sound power level H/L dB(A) 53/49 55/49 Sound power level H dB(A) 50 51 52 59
Outdoor unit see page 35 RE-GA7V1 RE-GA7V1 (R-22) / R-GZ7V1 (R-407C) Outdoor unit see page 35 R-DC7V11/RE-GA7V1 R-DC7V11/RE-GA7V1 R-DC7V11/RE-GA7V1 R-DC7V11/W11

*FHEB25GZ7V1 can be used in combination with an R-22 or R-407C outdoor unit.


Refrigerant: R-22 • Power supply: V1: 1~, 230V, 50 Hz Refrigerant: R-22 • Power supply: V1: 1~, 230V, 50 Hz

HEAT PUMP FHEYB18BA7V1 FHEYB22BA7V1 HEAT PUMP FLY22GV1NB FLY35GV1NB FLY40GV1NB FLY45GV1NB
Cooling capacity kW 1.8 2.2 Cooling capacity kW 2.55/2.4 3.5/3.25 3.9 4.9
Heating capacity kW 1.85 2.5 Heating capacity kW 3.2/2.65 4.1/3.6 4.7 5.55
Nominal input cooling kW 0.62 0.88 Nominal input cooling kW 1.16/0.87 1.47/1.23 1.63 2.06
heating kW 0.58 0.82 heating kW 1.14/0.79 1.5/1.23 1.62 1.90
Dimensions HxWxD mm 230x652x502 Dimensions HxWXD mm 490x1,050x200
Weight kg 17 17 Weight kg 17 17 18 18
Air flow rate (H/L) cooling m3/min 6.5/5.2 6.5/5.2 Air flow rate (H/L) cooling m3/min 7.6/6.0 8.7/6.6 7.0/5.2 10.7/6.3
heating m3/min 6.95/5.2 6.95/5.2 heating m3/min 9.2/7.4 10.0/8.0 7.8/5.7 11.5/6.9
Sound pressure cooling dB(A) 34/28 35/28 Sound pressure cooling dB(A) 37/31 38/32 40/34 47/37
level (H/L) heating dB(A) 34/29 35/29 level (H/L) heating dB(A) 37/31 39/33 40/34 47/36
Sound power level (H) cooling/heating dB(A) 53/53 55/55 Sound power level H dB(A) 50 51 52 59
Outdoor unit see page 36 REY-GA7V1 REY-GA7V1 Outdoor unit see page 36 RY-DB7V1/REY-GA7V1 RY-DA7V1/REY-GA7V1 REY-GA7V1 RY-DB7V1

18 19
EPC99.09E•General 11/10/00 16:16 Page 22

2 A/C for commercial use

In offices, hotels, shops, restaurants and many other commercial


premises, high levels of personal comfort and satisfaction achieved by
the application of Daikin air conditioning, enhance the environment
and help set the scene for increased business prosperity - economically,
efficiently and discreetly.

User friendly, quiet running, ultra reliable and easy to control, Daikin
air conditioning adds that cool, fresh, relaxing “extra something” to
the indoor climate, providing the perfect platform for commercial success.

COMFORT AND FLEXIBILITY


Available in a wide range of modern, stylish wall, floor and ceiling
mounted models, Daikin air conditioning is designed to harmonise with
any interior decor and fits rooms of any shape or size.

21
EPC99.09E•General 11/10/00 16:17 Page 24

optional optional FHY only heat pump optional optional FHY only heat pump

FH(Y) 35 ~125
p.43

2 steps FH 35 ~60 2 steps twin/triple FH only


p.40 FH(Y)35-71 p.40
p.43

CEILING SUSPENDED UNIT


FH(Y)-FJ FH(Y)-GZ CEILING SUSPENDED UNIT

• the ideal solution for shops, restaurants or • leaves maximum floor and wall
offices without false ceilings space for furniture, decoration
• leaves maximum floor and wall space for and fittings
furniture, decoration and fittings. • extremely quiet in operation both
• air flow distribution pattern can be adapted indoors and outdoors
to suit ceiling heights up to 3.8m without loss • automatic airflow director ensures
of capacity. uniform airflow and temperature
distribution (FHY only)
• air flow distribution for ceiling
heights up to 3.8m without loss of
capacity

Refrigerant: R-22 • Power supply: V1: 1~, 230V, 50 Hz Refrigerant: R-407C • Power supply: V1: 1~, 230V, 50 Hz

COOLING ONLY FH35FJ7V1 FH45FJ7V1 FH60FJ7V1 FH71FJ7V1 FH100FJ7V1 FH125FJ7V1 COOLING ONLY FH35GZ7V1 FH45GZ7V1 FH71GZ7V1 FH100GZ7V1 FH125GZ7V1
Cooling capacity kW 4.05 5.35 6.5 7.4 10.3 12.4 Cooling capacity kW 3.75 5.18 7.1 9.7 12.3
Nominal input kW 1.3 2.11 2.42 3.0(V1)/2.8(W1) 3.7(V1)/3.4(W1) 4.50 Nominal input kW 1.32 2.16/2.06 2.90/2.86/2.86 3.69/3.47/3.47 4.76
Dimensions HxWxD mm 188x1,100x600 188x1,300x600 238x1,300x695 238x1,590x695 Dimensions HxWxD mm 188x1,100x600 188x1,300x600 238x1,300x695 238x1,590x695
Weight kg 26 27 30 30 37 45 Weight kg 26 27 30 37 45
Air flow rate H/L m3/min 13/10 13/10 18/14 18/14 26/20 33/25 Air flow rate H/L m3/min 13/10 13/10 18/14 26/20 33/25
Sound pressure level H/L dB(A) 38/33 39/34 40/35 40/35 43/38 44/39 Sound pressure level H/L dB(A) 38/33 39/34 40/35 43/38 44/39
Sound power level H dB(A) 54 55 56 56 59 61 Sound power level H dB(A) 54 55 56 59 61
Outdoor unit see page 35 R-DC7V11 R-DC7V11/W11 R-FA7V1/W1 R-FJ7V1/W1 R-FJ7V1/W1 R-FJ7W1 Outdoor unit see page 35 R-GZ7V11 R-GZ7V11/W11 R-GZ7V1/W1/T1 R-GZ7V1/W1/T1 R-GZ7W1/T1

Refrigerant: R-22 • Power supply: V1: 1~, 230V, 50 Hz Refrigerant: R-407C • Power supply: V1: 1~, 230V, 50 Hz

HEAT PUMP FHY35FJ7V1 FHY45FJ7V1 FHY60FJ7V1 FHY71FJ7V1 FHY100FJ7V1 FHY125FJ7V1 HEAT PUMP FHY35GZ7V1 FHY45GZ7V1 FHY71GZ7V1 FHY100GZ7V1 FHY125GZ7V1
Cooling capacity kW 4.1 4.8 6.15 7.3 10.0 12.4 Cooling capacity kW 3.6 4.9 7.1 10 12.2
Heating capacity kW 4.35 5.8 7.15 8.7 11.6 15.2 Heating capacity kW 4.1 5.5 8.2 11.2 14.7
Nominal input cooling kW 1.59 2.05 2.51 3.1(V1)/3(W1) 3.9(V1)/3.7(W1) 4.6 Nominal input cooling kW 1.51 2.04 2.97(V1)/2.93(W1) 4.04(V1)/3.84(W1) 4.85
heating kW 1.42 1.94 2.4 3.1(V1)/3(W1) 3.9(V1)/3.7(W1) 4.7 heating kW 1.46 1.91 3.02(V1)/2.98(W1) 4.02(V1)/3.85(W1) 4.92
Dimensions HxWxD mm 188x1,100x600 188x1,300x600 238x1,300x695 238x1,590x695 Dimensions HxWxD mm 188x1,100x600 188x1,300x600 238x1,300x695 238x1,590x695
Weight kg 26 27 30 30 37 45 Weight kg 26 27 30 37 45
Air flow rate H/L m3/min 13/10 13/10 18/14 18/14 26/20 33/25 Air flow rate H/L m3/min 13/10 13/10 18/14 26/20 33/25
Sound pressure level H/L dB(A) 38/33 39/34 40/35 40/35 43/38 44/39 Sound pressure level H/L dB(A) 38/33 39/34 40/35 43/38 44/39
Sound power level H dB(A) 54 55 56 56 59 60 Sound power level H dB(A) 54 55 56 59 60
Outdoor unit see page 36 RY-DA7V1 RY-DB7V1/W1 RY-FA7V1 RY-FJ7V1/W1 RY-FJ7V1/W1 RY-FJ7W1 Outdoor unit see page 36 RY-EAZ7V1 RY-EAZ7V1 RY-GAZ7V1/W1 RY-GAZ7V1/W1 RY-GAZ7W1

22 23
EPC99.09E•General 11/10/00 16:17 Page 26

optional optional optional heat pump optional optional heat pump

2 steps

2 steps twin/triple only FHYK FHK 35 ~ 60


p.43 35 ~ 71 p.40
p.43

4 - W AY B L O W C E I L I N G
SUSPENDED CASSETTE
FUY-FJ FH(Y)K-FJ CEILING MOUNTED
CORNER CASSETTE

• ideal for refurbishment • perfect for applications in shops,


• leaves maximum floor and wall restaurants or offices with false
space for furniture, decoration ceilings
• air can be discharged in any of • leaves maximum floor and wall
four directions space for furniture, decoration and
• air flow distribution for ceiling fittings
heights up to 3.5m • air flow distribution pattern can be
• no ceiling staining adapted to suit ceiling heights up to
• possibility to shut off one or two 3.8 m without loss of capacity
flaps for easy installation in
corners
• extremely quiet in operation both Refrigerant: R-22 • Power supply: V1: 1~, 230V, 50 Hz
indoor and outdoors
• air purification filter, drain pan COOLING ONLY FHK35FJV1 FHK45FJV1 FHK60FJV1 FHYK71FJV1
Cooling capacity kW 4.05 5.35 6.5 7.4
and heat exchanger fin are Nominal input kW 1.28 2.11 2.42 3.0(V1)/2.8(W1)
mildew proof and have Dimensions (HxWxD) unit mm 215x1,110x710 215x1,310x710
anti-bacterial treatment decor. panel mm 70x1,240x800 70x1,440x800
Weight unit kg 30 31 33 33
decor. panel kg 8.5 8.5 9.5 9.5
Air flow rate H/L m3/min 12/9 12/10 17/14 17/14
Sound pressure level H/L dB(A) 39/33 39/34 41/36 41/36
Sound power level H dB(A) 50 50 52 52
Outdoor unit see page 35 R-DC7V11 R-DC7V11/W11 R-FA7V1/W1 R-FJ7V1/W1

Refrigerant: R-22 • Power supply: V1: 1~, 230V, 50 Hz


Refrigerant: R-22 • Power supply: V1: 1~, 230V, 50 Hz
HEAT PUMP FHYK35FJV1 FHYK45FJV1 FHYK60FJV1 FHYK71FJV1
C/O & H/P FUY71FJV1 FUY100FJV1 FUY125FJV1 FUY71FJV1 FUY100FJV1 FUY125FJV1 Cooling capacity kW 4.1 4.8 6.15 7.3
Cooling capacity kW 7.3 9.9 12.3 7.3 10.0 12.8 Heating capacity kW 4.35 5.8 7.15 8.7
Heating capacity kW - - - 8.7 12.2 15.3 Nominal input cooling kW 1.5 2.05 2.51 3.1(V1)/3.0(W1)
Nominal input (V1/W1) cooling kW 3.1/2.9 3.7/3.4 4.5 3.2/3.1 4.0/3.8 4.6 heating kW 1.39 1.90 2.4 3.1(V1)/3.0(W1)
heating kW - - - 3.1/3.0 3.8/3.6 4.7 Dimensions (HxWxD) unit mm 215x1,110x710 215x1,310x710
Dimensions HxWxD mm 165x895x895 230x895x895 165x895x895 230x895x895 decor. panel mm 70x1,240x800 70x1,440x800
Weight kg 25 31 31 25 31 31 Weight unit kg 30 31 33 33
Air flow rate (H/L) cooling/heating m3/min 19/14 29/21 32/23 19/14 29/21 32/23 decor. panel kg 8.5 8.5 9.5 9.5
Sound pressure level cooling dBA 40/35 43/38 44/39 40/35 43/38 44/39 Air flow rate H/L m3/min 12/9 12/10 17/14 17/14
H/L heating dBA - - - 40/35 43/38 44/39 Sound pressure level H/L dB(A) 39/33 39/34 41/36 41/36
Sound power level H dBA 56 59 60 56 59 60 Sound power level H dB(A) 50 50 52 52
Outdoor unit see page 35/36 R-FJ7V1/W1 R-FJ7V1/W1 R-FJ7W1 RY-FJ7V1/W1 RY-FJ7V1/W1 RY-FJ7W1 Outdoor unit see page 36 RY-DA7V1 RY-DB7V1 RY-FA7V1 RY-FJ7V1/W1

24 25
EPC99.09E•General 11/10/00 16:17 Page 28

optional optional optional heat pump optional optional optional

FHYC heat pump 2 steps


35 ~ 125

FHC35~60 2 steps Twin/triple FHC35~60


p.40 FHYC35~71 p.40
p.43

4 - W AY B L O W C E I L I N G
MOUNTED CASSETTE
FH(Y)C-BJ FH(Y)C-BZ 4 - W AY B L O W C E I L I N G
MOUNTED CASSETTE

• fits flush into each ceiling • compact and lightweight unit with
• air can be discharged in any of mimimum operating sound levels
four directions • choice of 8 air flow distribution
• possibility to shut off one or two patterns
flaps for easy installation in • air flow distribution for ceiling heights
corners up to 4.2m without loss of capacity
• air flow distribution for ceiling
heights up to 4.2m without loss of
capacity

Refrigerant: R-22 • Power supply: V1: 1~, 230V, 50 Hz Refrigerant: R-407C • Power supply: V1:1~, 230V, 50 Hz

COOLING ONLY FHC35BJV1 FHC45BJV1 FHC60BJV1 FHYC71BJV1 FHYC100BJV1 FHYC125BJV1 COOLING ONLY FHC35BZV1 FHC45BZV1 FHYC71BZV1 FHYC100BZV1 FHYC125BZV1
Cooling capacity kW 3.9 5.2 6.5 7.3 10.2 12.3 Cooling capacity kW 3.80 5.2 7.1 10.0 12.3
Nominal input kW 1.36 2.15 2.42 3.0(V1)/2.8(W1) 3.7(V1)/3.4(W1) 4.5 Nominal input kW 1.36 2.20/2.10 2.99/2.96/2.96 3.77/3.56/3.56 4.76
Dimensions (HxWxD) unit mm 230x840x840 288x840x840 Dimensions HxWxD unit mm 230x840x840 288x840x840
decor. panel mm 40x950x950 decor. panel mm 40x950x950
Weight unit kg 23 23 23 23 27 27 Weight unit kg 23 23 23 27 27
decor. panel kg 5 5 5 5 5 5 decor. panel kg 5 5 5 5 5
Air flow rate H/L m3/min 14/10 15/11 18/14 18/14 28/21 31/24 Air flow rate H/L m3/min 14/10 15/11 18/14 28/21 31/24
Sound pressure level H/L dB(A) 31/27 31/27 33/28 33/28 37/32 40/35 Sound press. level H/L dBA 31/27 31/27 33/28 37/32 40/35
Sound power level H/L dB(A) 47/43 47/43 49/44 49/44 52/47 55/50 Sound power level H/L dBA 47/43 47/43 49/44 52/47 55/50
Outdoor unit see page 35 R-DC7V11 R-DC7V11/W11 R-FA7V1/W1 R-FJ7V1/W1 R-FJ7V1/W1 R-FJ7W1 Outdoor unit see page 35 R-GZ7V11/W11 R-GZ7V11/W11 R-GZ7V1/W1/T1 R-GZ7V1/W1/T1 R-GZ7W1/T1

Refrigerant: R-22 • Power supply: V1: 1~, 230V, 50 Hz Refrigerant: R-407C • Power supply: V1:1~, 230V, 50 Hz

HEAT PUMP FHYC35BJV1 FHYC45BJV1 FHYC60BJV1 FHYC71BJV1 FHYC71BJV1 FHYC100BJV1FHYC125BJV1 HEAT PUMP FHYC35BZV1 FHYC45BZV1 FHYC71BZV1 FHYC100BZV1 FHYC125BZV1
Cooling capacity kW 3.6 4.8 6.15 7.3 8.0 10.3 12.8 Cooling capacity kW 3.60 4.9 7.1 10.0 12.2
Heating capacity kW 4.65 5.8 7.15 8.7 9.0 12.2 15.3 Heating capacity kW 4.10 5.5 8.2 11.6 14.6
Nominal input cooling kW 1.63 2.07 2.51 3.1(V1)/3(W1) 3.5 4(V1)/3.8(W1) 4.6 Nominal input cooling kW 1.51 2.04 3.0/2.96 4.11/3.89 4.89
heating kW 1.52 1.93 2.4 3.1(V1)/3(W1) 3.3 3.8(V1)/3.6(W1) 4.7 heating kW 1.46 1.91 2.97/2.93 4.03/3.86 4.99
Dimensions (HxWxD) unit mm 230x840x840 288x840x840 Dimensions (HxWxD) unit mm 230x840x840 288x840x840
decor. panel mm 40x950x950 decor. panel mm 40x950x950
Weight unit kg 23 23 23 23 23 27 27 Weight unit kg 23 23 23 27 27
decor. panel kg 5 5 5 5 5 5 5 decor. panel kg 5 5 5 5 5
Air flow rate H/L m3/min 14/10 15/11 18/14 18/14 18/14 28/21 31/24 Air flow rate H/L m3/min 14/10 15/11 18/14 28/21 31/24
Sound pressure level H/L dB(A) 31/27 31/27 33/28 33/28 33/28 37/32 40/35 Sound press. level H/L dBA 31/27 31/27 33/28 37/32 40/35
Sound power level H/L dB(A) 47/43 47/43 49/44 49/44 49/44 52/47 55/50 Sound power level H/L dBA 47/43 47/43 49/44 52/47 55/50
Outdoor unit see page 36 RY-DA7V1 RY-DB7V1/W1 RY-FA7V1 RY-FJ7V1/W1 RZY71LV1 RY-FJ7V1/W1 RY-FJ7W1 Outdoor unit see page 36 RY-EAZ7V1 RY-EAZ7V1 RY-GZ7V1/W1 RY-GZ7V1/W1 RY-GZ7W1

26 27
EPC99.09E•General 11/10/00 16:18 Page 30

optional optional heat pump optional optional heat pump

FHYB FHB 35 ~ 60
35 ~125 p.40
p.43

2 steps Twin FHB only 2 steps


FHYB35-71 p.40
p.43

CONCEALED CEILING UNIT


FH(Y)B-FK FH(Y)B-GZ CONCEALED CEILING UNIT

• particularly suitable for restaurants, • lightweight and compact


open-plan offices, apartments, entrance • blends unobtrusively with any
halls and irregularly shaped rooms interior decor
• movable air discharge grilles ensure • extremely quiet in operation both
uniform room temperatures indoors and outdoors
• the maximum external static pressure (ESP) • the position of the individual air
is 9mmH2O discharge grilles can be altered,
enabling a uniform temperature,
even in irregularly shaped rooms

Refrigerant: R-22 • Power supply: V1: 1~, 230V, 50 Hz Refrigerant: R-407C • Power supply: V1: 1~, 230V, 50 Hz

COOLING ONLY FHB35FK7V1 FHB45FK7V1 FHB60FK7V1 FHYB71FK7V1 FHYB100FK7V1 FHYB125FK7V1 COOLING ONLY FHB35GZ7V1 FHB45GZ7V1 FHYB71GZ7V1 FHYB100GZ7V1 FHYB125GZ7V1
Cooling capacity kW 3.95 5.3 6.5 7.2 10.5 12.4 Cooling capacity kW 3.70 4.90 7.1 10.0 12.3
Nominal input kW 1.36 2.17 3.10 3.1(V1)/2.9(W1) 3.8(V1)/3.5(W1) 4.6 Nominal input kW 1.40 2.23/2.13 2.96/2.93/2.93 3.70/3.54/3.54 4.79
Dimensions (HxWxD) unit mm 300x700x800 300x1,000x800 300x1,400x800 Dimensions (HxWxD) unit mm 300x700x800 300x1,000x800 300x1,400x800
decor. panel mm 55x880x500 55x1,100x500 55x1,500x500 decor. panel mm 55x880x500 55x1,100x500 55x1,500x500
Weight unit kg 30 31 41 41 51 52 Weight unit kg 30 31 41 51 52
decor. panel kg 3.5 3.5 4.5 4.5 6.5 6.5 decor. panel kg 3.5 3.5 4.5 6.5 6.5
Air flow rate H/L m3/min 11.5/9 14/10 17/13 19/14 27/20 35/24 Air flow rate H/L m3/min 11.5/9.0 14.0/10.0 19/14 27/20 35/24
Sound pressure level H/L dB(A) 33/29 33/29 34/30 34/30 36/31 38/32 Sound pressure level H/L dB(A) 33/29 33/29 34/30 36/31 38/32
Sound power level H dB(A) 52 53 60 60 62 63 Sound power level H dB(A) 52 53 60 62 63
Outdoor unit see page 35 R-DC7V11 R-DC7V11/W11 R-FA7V1/W1 R-FJ7V1/W1 R-FJ7V1/W1 R-FJ7W1 Outdoor unit see page 35 R-GZ7V11 R-GZ7V11/W11 R-GZ7V1/W1/T1 R-GZ7V1/W1/T1 R-GZ7W1/T1

Refrigerant: R-22 • Power supply: V1: 1~, 230V, 50 Hz Refrigerant: R-407C • Power supply: V1: 1~, 230V, 50 Hz

HEAT PUMP FHYB35FK7V1 FHYB45FK7V1 FHYB60FK7V1 FHYB71FK7V1 FHYB100FK7V1 FHYB125FK7V1 HEAT PUMP FHYB35GZ7V1 FHYB45GZ7V1 FHYB71GZ7V1 FHYB100GZ7V1 FHYB125GZ7V1
Cooling capacity kW 3.8 4.45 6.25 7.2 10.0 12.4 Cooling capacity kW 3.60 4.9 7.1 10.0 12.2
Heating capacity kW 4.2 5.60 7.40 8.6 11.6 15.2 Heating capacity kW 4.10 5.5 8.2 11.2 14.7
Nominal input cooling kW 1.64 2.15 3.09 3.2(V1)/3.1(W1) 4.1(V1)/3.9(W1) 4.7 Nominal input cooling kW 1.64 2.09 2.97/2.93 4.04/3.87 4.92
heating kW 1.45 1.96 2.74 3.2(V1)/3.1(W1) 4.1(V1)/4.1(W1) 4.8 heating kW 1.46 1.97 3.03/2.96 4.02/3.93 4.97
Dimensions (HxWxD) unit mm 300x700x800 300x1,000x800 300x1,400x800 Dimensions (HxWxD) unit mm 300x700x800 300x1,000x800 300x1,400x800
decor. panel mm 55x880x500 55x1,100x500 55x1,500x500 decor. panel mm 55x880x500 55x1,100x500 55x1,500x500
Weight unit kg 30 31 41 41 51 52 Weight unit kg 30 31 41 51 52
decor. panel kg 3.5 3.5 4.5 4.5 6.5 6.5 decor. panel kg 3.5 3.5 4.5 6.5 6.5
Air flow rate H/L m3/min 11.5/9 14/10 17/13 19/14 27/20 35/24 Air flow rate H/L m3/min 11.5/9.0 14.0/10.0 19/14 27/20 35/24
Sound pressure level H/L dB(A) 33/29 33/29 34/30 34/30 36/31 38/32 Sound pressure level H/L dB(A) 33/29 33/29 34/30 36/31 38/32
Sound power level H dB(A) 52 53 60 60 62 63 Sound power level H dB(A) 52 53 60 62 63
Outdoor unit see page 36 RY-DA7V1 RY-DB7V1 RY-FA7V1 RY-FJ7V1/W1 RY-FJ7V1/W1 RY-FJ7W1 Outdoor unit see page 36 RY-EAZ7V1 RY-EAZ7V1 RY-GZ7V1/W1 RY-GZ7V1/W1 RY-GZ7W1

28 29
EPC99.09E•General 11/10/00 16:18 Page 32

optional optional
optional optional optional heat pump

2 steps
2 steps

CONCEALED CEILING
UNIT
FHYB-F FAY-FJ WA L L M O U N T E D U N I T

• designed to allow maximum use of


floor space
• modern, space saving configuration
• even air distribution via automatic
• incorporates “SUPER INVERTER” movable louvre that can also be fixed
technology at any desired angle
• achieves set temperature more quickly
• consumes up to 40% less energy than
non-inverter models on an annual basis
• blends unobtrusively into any interior décor
• particularly suitable for restaurants,
open-plan offices, apartments, entrance
halls and irregularly shaped rooms
• movable air discharge grilles ensure
uniform room temperatures Refrigerant: R-22 • Power supply: V1: 1~, 230V, 50 Hz
• the maximum external static pressure (ESP)
is 9mmH2O COOLING ONLY FAY71FJV1 FAY100FJV1
Cooling capacity kW 7.4 9.9
• leaves maximum floor and wall space for furniture, decoration and fittings Nominal input kW 3.1(V1)/2.9(W1) 3.7(V1)/3.4(W1)
Dimensions HxWxD mm 360x1,570x200 360x1,690x200
Weight kg 26 27
Air flow rate H/L m3/min 19/16 24/20
Sound pressure level H/L dB(A) 41/37 45/41
Sound power level H dB(A) 57 61
Refrigerant: R-22 • Power supply: V1: 1~, 230V, 50 Hz Outdoor unit see page 35 R-FJ7V1/W1 R-FJ7V1/W1

HEAT PUMP FHYB71FV1 Refrigerant: R-22 • Power supply: V1: 1~, 230V, 50 Hz
Cooling capacity (1) kW 5.7-7.1-8.0
Heating capacity (1) kW 5.4-8.0-9.0 HEAT PUMP FAY71FJV1 FAY100FJV1
Nominal input (1) cooling kW 3.5 Cooling capacity kW 7.3 10.3
heating kW 3.3 Heating capacity kW 8.3 12.0
Dimensions (HxWxD) unit mm 300x1,000x800 Nominal input cooling kW 3(V1)/2.9(W1) 3.8(V1)/3.6(W1)
decor. panel mm 55x1,100x500 heating kW 3(V1)/2.9(W1) 4.1(V1)/3.9(W1)
Weight unit kg 41 Dimensions HxWxD mm 360x1,570x200 360x1,690x200
decor. panel kg 4.5 Weight kg 26 27
Air flow rate H/L m3/min 19/14 Air flow rate H/L m3/min 19/16 24/20
Sound pressure level H/L dB(A) 42/36 Sound pressure level H/L dB(A) 42/38 45/41
Sound power level H dB(A) * Sound power level H dB(A) 57 61
Outdoor unit see page 38 RZY71LV1 Outdoor unit see page 36 RY-FJ7V1/W1 RY-FJ7V1/W1

30 * Sound power levels were not available at the time of publication. 31


(1) Units should be selected on nominal capacity. Maximum capacity is limited to peak periods.
EPC99.09E•General 11/10/00 16:18 Page 34

optional
option

optional

CONCEALED CEILING UNIT


FDY-F UAT(Y) PA C K A G E D U N I T S

• extremely compact • provides comfort conditions for


• the maximum external static large areas such as department
pressure (ESP) ranges from 15 till stores or warehouses
25 mmH2O • distributes supply and return air
• only air suction & discharge grilles via ducts, ensuring optimum air
are visible distribution
• optimum air distribution • only inlet and discharge grilles are
visible

Refrigerant: R-22 • Power supply: V1: 1~, 230V, 50 Hz Refrigerant: R-22 • Power supply: Y1: 3~, 400V, 50 Hz

COOLING ONLY FDY125F7V1 FDY200F7V1 FDY250F7V1 COOLING ONLY UAT12JY1 UAT22JAY1 UAT30HY1
Cooling capacity kW 12.4 20 24.2 Cooling capacity kW 30.9 59.3 97.1
Nominal input kW 5.1 8.1 9.4 Nominal input kW 9.9 21.2 31.4
Dimensions HxWxD mm 350x1,400x662 450x1,400x900 Dimensions HxWxD mm 1,000x1,175x1,450 1,300x1,965x1,760 1,755x2,860x1,340
Weight kg 57 84 86 Weight kg 340 660 1080
Air flow rate M m3/min 45 72 90 Nominal air flow m3/min 95 200 295
Sound pressure level M dB(A) 44 45 47 Sound pressure level H/L dB(A) 72 80 79
Sound power level M dB(A) 78 83 83 Sound power level H dB(A) * * *
Outdoor unit see page 35 R-FJ7W1 R-F7W1 R-F7W1
Refrigerant: R-22 • Power supply: Y1: 3~, 400V, 50 Hz
Refrigerant: R-22 • Power supply: V1: 1~, 230V, 50 Hz
HEAT PUMP UATY06KY1 UATY08KY1 UATY09KY1 UATY10KY1 UATY15KY1 UATY18KY1 UATY21KY1
HEAT PUMP FDY125F7V1 FDY200F7V1 FDY250F7V1 Cooling capacity kW 17.7 22.0 26.4 31.4 43.9 52.7 61.6
Cooling capacity kW 12.4 19.5 25 Heating capacity kW 18.1 23.0 26.9 32.1 46.1 54.2 62.8
Heating capacity kW 13.4 23.4 27 Nominal input cooling kW 5.8 6.3 8.2 9.9 13.0 17.1 19.8
Nominal input cooling kW 5.1 7.9 9.4 heating kW 5.3 5.7 7.7 9.4 11.8 15.8 18.5
heating kW 4.5 6.8 8.1 Dimensions HxWxD mm 1,490x690x1,750 1,270x1,600x1,280 1,270x1,600x1,280 1,490x1,600x1,280 1,270x1,980x1,980 1,270x1,980x1,980 1,490x1,980x1,980
Dimensions HxWxD mm 350x1,400x662 450x1,400x900 Weight kg 230 326 329 344 650 656 686
Weight kg 57 84 86 Nominal air flow (indoor fan) m3/min 52 68 68 83 136 136 166
Air flow rate M m3/min 45 72 90 Sound pressure level H/L dB(A) 62 63 63 64 66 66 67
Sound pressure level M dB(A) 44 45 47 Sound power level H dB(A) * * * * * * *
Sound power level M dB(A) 78 83 83
* Sound power levels were not available at the time of publication.
Outdoor unit see page 36 RY-FJ7W1 RY-F7W1 RY-F7W1

32 33
EPC99.09E•General 11/10/00 16:19 Page 36

Daikin outdoor units are neat and sturdy and can be mounted easily
on a roof or terrace or simply placed against an outside wall. They are RE18-25-35-40
fitted with either rotary or scroll compressor, renowned for low noise and R25-35-45
R100/125 R200/250
high energy efficiency. R60

A special acryl precoated fin for anti-corrosion treatment on the heat R(E) PA I R A P P L I C AT I O N -
C O O L I N G O N LY
exchanger ensures greater resistance against severe weather conditions.

O utdoor units

Refrigerant: R-22 • Power supply: V1: 1~, 230V, 50 Hz / W1: 3N~, 400V, 50 Hz

COOLING ONLY R-22 RE18GA7V1 RE25GA7V1R25DC7V11 RE35GA7V1 R35DC7V11 RE40GA7V1R45DC7V11/W11 R60FA7V1/W1


Dimensions HxWxD mm 540x750x270 660x880x350
Weight kg 28 30 31 34 39 43 45 64
Sound pressure level dBA 45 45 43 49 48 50 50 54
Sound power level dBA 56 58 56 62 61 63 63 67
Operation range °CDB 20~43 20~43 -15~46 20~43 -15~46 20~43 -15~46 -15~46

Refrigerant: R-22 • Power supply: V1: 1~, 230V, 50 Hz / W1: 3N~, 400V, 50 Hz

COOLING ONLY R-22 R71FJ7V1/W1 R100FJ7V1/W1 R125FJ7W1 R200F7W1 R250F7W1


Dimensions HxWxD mm 860x830x320 1,215x830x320 1,215x880x320 1,220x1,290x700 1,440x1,290x700
Weight kg 77(V1)/74(W1) 100(V1)/95(W1) 97 169 191
Sound pressure level dBA 48 51 51 56 57
Sound power level dBA 62 64 65 77 78
Operation range °CDB -15~46 -15~46 -15~46 -5~46 -5~46

Refrigerant: R-407C • Power supply: V1: 1~, 230V, 50 Hz / W1: 3N~, 400V, 50 Hz

COOLING ONLY R-407C R25GZ7V11 R35GZ7V11 R45GZ7V11/W11 R71GZ7V1/W1/T1 R100GZ7V1/W1/T1 R125GZ7W1/T1


Dimensions HxWxD mm 540x750x270 860x830x320 1,215x830x320 1,215x880x320
Weight kg 32 39 46 77/74/74 100/95/95 97
Sound pressure level dBA 44 48 51 50 53 53
Sound power level dBA 58 61 64 62 65 65
Operation range °CDB -15~46 -15~46 -15~46 -15~46 -15~46 -15~46

35
EPC99.09E•General 11/10/00 16:19 Page 38

REY18-22-35
RY22

RY200/250 RY100/125 RY60FA7

PA I R A P P L I C AT I O N -
H E AT P U M P
R(E)Y RK-J/RX-J/RXT-JZ PAIR APPLICATION -
INVERTER CONTROLLED
Inverter Control:
The use of integrated inverter control ensures S TA R T- U P T I M E
REDUCED BY 1/3
maximum comfort and efficiency
• Short start up cycle
Inverter control enables the required room temperature
to be achieved quicker than with non inverter units,
standard
in fact, start up time is reduced by one third. heat pump
• 30 % less power consumption system

The inverter controlled air conditioning detects changes small temperature difference
in room or outdoor conditions and adjusts the indoor
inverter heat pump system
temperature to compensate within seconds.
Rapid response reduces power consumption to 30% lower
than that of non inverter systems.
Refrigerant: R-22 • Power supply: V1: 1~, 230V, 50Hz / W1: 3N~, 400V, 50Hz • Whisper quiet
Inverter controlled air conditioners, like all Daikin systems, are extremely quiet in
HEAT PUMP R-22 REY18GA7V1 REY22GA7V1 RY22DB7V1 REY35GA7V1 RY35DA7V1 REY40GA7V1 RY45DB7V1 RY60FA7V1
Dimensions HxWxD mm 540x750x270 660x880x350 operation. Only the extraordinary pleasure of the indoor environment betrays their existence.
Weight kg 29 31 37 39 50 50 57 72 • In case of RXT40-50G the use of the PAM (Pulse Amplitude Modulation) inverter technology
Sound pressure level (H) cool./heat. dBA 44/45 44/45 44/45 48/50 46/47 46/49 47/48 54/55
results in better cooling and heating performances and lower energy consumption.
Sound power level (H) cool./heat. dBA 57/58 57/58 57/58 61/63 59/60 59/62 60/61 67/68
Operation range cooling °CDB 20~43 20~43 -5~46 20~43 -5~46 20~43 -5~46 -15~46
heating CWB -10~15.5 -10~15.5 -10~15.5 -10~15.5 -10~15.5 -10~15.5 -10~15.5 -10~15.5

Refrigerant: R-22 • Power supply: V1: 1~, 230V, 50Hz / W1: 3N~, 400V, 50Hz Refrigerant: R-22 • Power supply: V1: 1~, 230V, 50 Hz

HEAT PUMP R-22 RY71FJ7V1/W1 RY100FJ7V1/W1 RY125FJ7W1 RY200F7W1 RY250F7W1 CO/HP RK25JV1NB RK35JV1NB RX25JV1NB RX35JV1NB RXT40GV1NB RXT50GV1NB
Dimensions HxWxD mm 860x830x320 1,215x830x320 1,215x880x320 1,220x1,290x700 1,440x1,290x700 Dimensions HxWxD mm 550x695x265 550x695x265 640x685x285
Weight kg 81/78 101/96 102 170 195 Weight kg 33 35 33 35 37 37
Sound pressure level (H) cool./heat. dBA 48/50 51/53 51/53 58/59 58/59 Sound pressure level (H) cool/heat dBA 46/- 47/- 46/47 47/48 46/50 49/51
Sound power level (H) cool./heat. dBA 61 64 64 79/80 79/80 Sound power level (H) cool/heat dBA 59 60 59/60 60/61 59 62
Operation range cooling °CDB -5~46 -5~46 -5~46 0~46 0~46 Standard oper. range cooling °CDB 10~46 10~46 10~46 10~46
heating °CWB -10~15 -10~15 -10~15 -10~15 -10~15 heating °CWB - - -10~15 -15~15

Refrigerant: R-407C • Power supply: V1: 1~, 230V, 50Hz / W1: 3N~, 400V, 50Hz Refrigerant: R-407C • Power supply: V1: 1~, 230V, 50 Hz

HEAT PUMP R-407C RY35EAZ7V1 RY45EAZ7V1 RY71GZ7V1/W1 RY100GZ7V1/W1 RY125GZ7W1 HEAT PUMP RXT25JZV1NB RXT35JZV1NB
Dimensions HxWxD mm 660x880x350 660x880x350 860x830x320 1,215x830x320 1,215x880x320 Dimensions HxWxD mm 550x695x245
Weight kg 50 57 81/78 101/96 102 Weight kg 36
Sound pressure level (H) cool./heat. dBA 46/48 47/48 50/52 53/56 53/56 Sound pressure level (H) cool/heat dBA 46/48 47/49
Sound power level cool./heat. dBA 59/60 60/61 62/- 65/- 65/- Sound power level (H) cool/heat dBA 61/63 62/64
Operation range cooling °CDB -5~46 -5~46 -5~46 -5~46 -5~46 Standard oper. range cooling °CDB 10~43
heating °CWB -10~15.5 -10~15.5 -10~15 -10~15 -10~15 heating °CWB -10~15

36 37
EPC99.09E•General 11/10/00 16:19 Page 40

SKY AIR APPLICATION RZY ER/ERC ER

CONDENSING UNITS
ERC

INVERTER CONTROLLED

• increased comfort thanks to the air


flow adjustment grille. The grille can
be altered in 4 directions according
to how it is installed
• the outdoor unit operates very quietly
• the outdoor unit can easily be
mounted on a roof or terrace or
placed against an outside wall
• possible indoor units are FHYB71FV1
(see p.30) and FHYC71BJV1 (see p.26)

Room temperatures fluctuate constantly, depending on the number of people present in an


office or shop, or on the amount of office equipment in use at any one time. Besides these
indoor fluctuations there are variations in day and night outdoor temperatures as well.
The Super Inverter controlled unit closely monitors these variations and maintains the room
temperature at the most comfortable level. In this way the Super Inverter drastically saves on
power consumption creating an ideal climate in shops and offices.
Refrigerant: R-22 • Power supply: V1: 1~, 230V, 50 Hz / W1: 3N~, 400V, 50 Hz / T1=3~,220V, 50Hz
The longer it operates, the greater the savings!
ER ER3DAW1/T1/V1 ER5DAW1/T1 ER8DAW1/T1 ER10DAW1/T1
Dimensions HxWxD mm 796x922x373 1,179x922x373 1,254x1,390x373 1,560x1,390x373
Longer business hours mean longer operating periods for the air conditioning and in contrast Weight kg 85 130 185 210
with Super Inverter controlled equipment, this results in increased power consumption on non Sound pressure level dBA 54 58 59 60
Sound power level dBA 67 71 72 73
inverter units. The application of inverter technology reduces unit power consumption by
Standard oper. range °CDB 0~43 0~43 0~43 0~43
keeping temperatures constant, thus additional business hours do not necessarily lead to Optional oper. range °CDB -15~43 -15~43 -15~43 -15~43
higher costs.
Refrigerant: R-22 • Power supply: T1: 3~, 220V, 50 Hz / W1: 3N~, 400V, 50 Hz
Refrigerant: R-22 • Power supply: V1: 1~, 230V, 50 Hz

ERC ERC3CBW1/T1 ERC5CBW1/T1 ERC8CBW1/T1 ERC10CBW1/T1


HEAT PUMP RZY71LV1 Dimensions HxWxD mm 1,100x675x605 1,345x795x605 1,290x1,125x605 1,395x1,275x605
Dimensions HxWxD mm 860x830x320 Weight kg 105 160 215 250
Weight kg 91 Sound pressure level dBA 54 58 59 60
Sound pressure level(H) cooling/heating dB(A) 51/53 Sound power level dBA * * * *
Sound power level H dB(A) * Standard oper. range °CDB 0~43 0~43 0~43 0~43
Operation range cooling °CDB -5 ~ 50 Optional oper. range °CDB -10~43 -10~43 -10~43 -10~43
heating °CWB -15 ~ 15.5
* Sound power levels were not available at the time of publication
38 39
EPC99.09E•General 11/10/00 16:20 Page 42

M U LT I M O D E L A P P L I C AT I O N - P O S S I B L E I N D O O R U N I T S

Outdoor units for multi model application

With Multi outdoor units, it is possible to connect up to 5 indoor units of different capacities MA90 MEY32
to a single outdoor unit, thereby reducing installation space and costs.
It is possible to combine different types of indoor units as well (e.g. wall mounted, ceiling mounted corner
cassette). All indoor units remain individually controllable and do not need to be installed at the same time or in
the same room. Further units can always be added at a later stage. Moreover, the energy consumption of a
MA(E)/M(E)Y M U LT I M O D E L A P P L I C AT I O N
Daikin Multi model system can be up to 20% lower than that of a separate indoor and outdoor unit combination.
Multi outdoor units are equipped with a rotary compressor, renowned for its low sound level and high energy
efficiency (multi inverter units are equipped with a horizontal scroll compressor).

Notes: Multi units are certified by Eurovent for combinations up to two indoor units.

MULTI MODEL APPLICATION - COOLING ONLY - R-22 18 25 35 40 45 60


Wall mounted unit FT X X X X X X
Concealed ceiling unit FHEB X X
Floor standing unit FV X X X X
Flexi type unit FL X X X
Ceilling suspended unit FH X X X
4-way blow ceiling mounted cassette FHC X X X
Ceiling mounted corner cassette FHK X X X
Concealed ceiling unit FHB X X X

Refrigerant: R-22/R-407C • Power supply: V1: 1~, 230V, 50 Hz / W1: 3N~, 400V, 50 Hz

MULTI MODEL APPLICATION - COOLING ONLY - R-407C 25 35 45 COOLING ONLY MAE25GA7V1 MAE32GA7V1 MA45DA7V1 MA56DB7V1/W1 MA90CK7V1/W1 MA90GZ7V11/W11
Max. nr. of indoor units 2 2 3 4 5 5
Wall mounted unit FT-GZ X X X
Maximum capacity kW 2.9 3.6 4.8 6.02 8.78 8.34
Concealed ceiling unit FHEB-GZ X
Maximum nominal input kW 0.9 1.34 1.42 1.83 3.07 2.86
Ceilling suspended unit FH-GZ X X
Dimensions HxWxD mm 540x750x270 540x750x270 660x880x350 660x880x350 865x880x350 865x880x350
4-way blow ceiling mounted cassette FHC-GZ X X
Weight kg 31 36 50 62 82 87
Concealed ceiling unit FHB-GZ X X
Sound pressure level H dBA 45 49 48 52 56 56
Sound power level dBA 58 62 61 65 67/68 67/68
Operation range standard °CDB 20~43 20~43 19.4~46 19.4~46 19.4~46 19.4~46
(ambient temperature) optional °CWB / / -15~46 -15~46 -5~46 -5~46
MULTI MODEL APPLICATION - HEAT PUMP - R-22 18 22 35 40 45 60
Wall mounted unit FTY X X X X X X
Refrigerant: R-22 • Power supply: V1: 1~, 230V, 50 Hz / W1: 3N~, 400V, 50 Hz
Concealed ceiling unit FHEYB X X
Floor standing unit FCVY X X X
Flexi type unit FLY X X X
HEAT PUMP MEY32GA7V1 MY56DA7V1 MY90CJ7V1/W1
Max. nr. of indoor units 2 3 5
Maximum capacity cooling kW 3.95 5.8 8.45
heating kW 3.8 5.95 9.43
Maximum nominal input cooling kW 1.38 2.19 3.12
MULTI MODEL APPLIC., INV. CONTROLLED - COOLING ONLY - R-22 25 35 50 60 heating kW 1.06 2.25 2.49
Wall mounted unit FTK X X X X Dimensions HxWxD mm 660x880x350 660x880x350 865x880x350
Concealed ceiling unit CDK X X X X Weight kg 50 72 96/95
Sound pressure level cooling dBA 46 46 56
H/L heating dBA 47 49 57
Sound power level cooling dBA 58 59 68
MULTI MODEL APPLIC., INV. CONTROLLED - HEAT PUMP - R-22 25 35 50 60 heating dBA 60 62 69/70
Wall mounted unit FTX X X X X Operation range cooling °CDB 20~43 -5~46 -5~46
Concealed ceiling unit CDX X X X X (ambient temperature) heating °CWB -10~15.5 -10~15.5 -7~15.5

Note: The power consumption mentioned in the table above is the TOTAL power consumption, i.e. based on the combination with FT(Y)...GV1B indoor unit(s).
40 41
EPC99.09E•General 11/10/00 16:20 Page 44

M U LT I M O D E L
A P P L I C AT I O N
INVERTER CONTROLLED
2MX/3MX/4MX/4MK
OUTDOOR UNITS FOR TWIN, TRIPLE AND
Multi model application, inverter controlled D O U B L E T W I N A P P L I C AT I O N

Wall mounted and concealed ceiling, inverter controlled units can be installed in multi model
application. Combination with non-inverter indoor units is not possible. It is possible to connect 2,3 or 4 indoor units to a single outdoor unit. The indoor units may
be of different types (e.g. ceiling mounted 4-way blow cassette, wall mounted, ...) and even
Multi inverter controlled outdoor units can be placed on top of each other*, thereby saving different capacities (e.g. 45 and 60 class).
installation space. An optional fixing plate between the 2 outdoor units is necessary.
All indoor units are operated together within the same mode (cooling or heating) from one
* 3MX68HV1NB/2MX52HV1NB units only remote control. This allows equal air distribution, even in larger, irregularly shaped rooms.

For specifications of outdoor units, see pages 35 (cooling only) and 36 (heat pump).

The total capacities (outdoor base) for simultaneous operation are the same as for the pair
applications.
example: R200 + FHY71 + FAY71 + FHYB71
= R200 + FDY200
= 20.0 kW

POSSIBLE INDOOR APPLICATIONS


SIMULTANEOUS OPERATION
SYSTEM TWIN TRIPLE DOUBLE TWIN
SYSTEM out out out
Refrigerant: R-22 • Power supply: V1: 1~, 230V, 50 Hz LAY-OUT
in in in in in in in in in
*
HP/CO 2MX52HV1NB 3MX68HV1NB 4MX80HV1NB 4MK90HV1NB 71

71 35 35
Max. nr. of indoor units 2 3 4 4 (KHR79BA7)

Maximum capacity cooling kW 3.60 ~ 5.20 ~ 5.34 3.90 ~ 6.80 ~ 7.24 4.37 ~ 8 ~ 9.13 4.33 ~ 9 ~ 9.40 100 * 100 100 * 100 *

OUTDOOR UNIT
(min.-nom.-max.) heating kW 4.56 ~ 6.10 ~ 7.80 1.20 ~ 2.47 ~ 2.81 5.83 ~ 9.6 ~ 10.63 / 100 45 45 45 60 35 71 35 35 35

(KHR79BA7) (KHR79BA7) (KHR79BA7) (KHR86HA7)


Maximum nominal input cooling kW 1.09 ~ 2.10 ~ 2.30 4.60 ~ 8.60 ~ 9.45 1.29 ~ 2.59 ~ 3.76 1.16 ~ 3.24 ~ 3.53
125 125 * 125 *
(min.-nom.-max.) heating kW 1.20 ~ 1.74 ~ 2.57 1.11 ~ 2.61 ~ 3.07 1.35 ~ 2.58 ~ 3.07 /
125 60 60 45 71 45 45 45

Dimensions HxWxD mm 660x790x330 750x790x300 860x790x300 (KHR79BA7) (KHR79BA7) (KHR86HA7)

Weight kg 61 69 80 75 200 200 200 200 200 200 200

Sound pressure level cooling dBA 45 47 49 49 200 100 100 71 125 71 71 71 60 60 60 45 71 71 45 45 100 45 45 45 45
(KHR102BA7) (KHR102BA7) (KHR127HA7) (KHR127HA7) (KHR127HA7) (KHR127HA7) (2xKHR79BA7+KHR102BA7)
H heating dBA 46 48 49 / 250 250 250 250

Sound power level H dBA * * * * 250 125 125 45 100 100 60 60 125 60 60 60 60

Standard oper. range cooling °CDB 21~43 21~43 10~43 10~43 (KHR102BA7) (KHR127HA7) (KHR127HA7) (2xKHR79BA7+KHR102BA7)

(ambient temperature) heating °CWB -10~15 -10~15 -10~15 / Note 1 : Possible indoor types R-22: FHYC35-125 - FUY71-125 - FHYK35-71 - FAY71/100 - FHY35-60 - FHY71-125 - FH71-125 - FHYB35-125 - FDY125
Note 2 : Combinations marked with * are also available with the ozone-friendly refrigerant R-407C. Possible indoor types are FHYC - FHY - FHYB 35-71.
42 * Sound power levels were not available at the time of publication. Replace refnet kits with KHRP79BA7 and KHRP86HA7. 43
Note 3 : Between brackets the required refnet kits are mentioned necessary to install the combination.
EPC99.09E•General 11/10/00 16:20 Page 46

Hi-VRV
3
Rising energy and general building services running costs have led end users
to expect far more than just cooling and heating from their air conditioning.
A truly complete and acceptable system therefore, must be energy efficient,
economic to run, easy to install, flexible, reliable and user friendly.
Fresh air must also be supplied without increasing energy consumption
and central management and control facilities have gained in importance,

THE COMPLETE AIR CONDITIONING SYSTEM


particularly for medium to large sized buildings.

The Daikin Hi-VRV system meets all these requirements:

Air Conditioning
VRV

HRV DACMS

Ventilation Management

VRV air conditioning can be found in offices, restaurants, theatres,


hospitals, universities, museums, shops - in short, in any location where
the provision of a balanced, pleasant working environment can improve
the lifestyle and comfort of the individual.

45
EPC99.09E•General 11/10/00 16:21 Page 48

VA R I A B L E R E F R I G E R A N T V O L U M E
VRV
The VRV system is available in inverter driven cooling only, heat pump and heat recovery format, each Modular design enables Daikin VRV outdoor units
designed to provide efficient and flexible comfort cooling and/or heating in a wide range of public and to be joined together in rows with an outstanding
private commercial premises. degree of uniformity. The design of the outdoor
units is sufficiently compact to allow them to be
An electronic expansion valve continually adjusts the flow of refrigerant to respond to the load requirements taken up to the top of a building in a commercial
of the indoor units, enabling the system to maintain temperatures at a virtually constant and comfortable elevator, overcoming site transportation problems.
level without the fluctuations typical of ON/OFF control systems.

The ability to control each conditioned zone keeps VRV system running costs to an absolute minimum.
Furthermore, only those areas calling for air conditioning need to be cooled or
heated and the system can be shut down
completely in unoccupied rooms.

VRV Inverter series


for either cooling or heating
The system links up to 16 smart, stylish
Inverter controlled
indoor units with a single outdoor unit,
enabling cooling or heating to be
supplied from the same refrigeration
circuit. VRV heat recovery series
for simultaneous cooling
Refrigerant: R-22 • Power supply: W1: 3N~, 400V, 50 Hz and heating
The system combines 16 indoor units
INVERTER HP/CO R-22 RSXY5KA7W1 RSXY8KA7W1 RSXY10KA7W1 RSX5KA7W1 RSX8KA7W1 RSX10KA7W1 and one outdoor unit, with remarkable
Cooling capacity kW 14.0 22.4 28.0 14.0 22.4 28.0 savings in energy consumption.
Heating capacity kW 16.0 25.0 31.5 - - - Heat recovery is achieved by diverting
Nominal input cooling kW 6.10 9.43 11.8 6.10 9.43 11.8
exhaust heat from indoor units in cooling
heating kW 5.40 8.48 10.5 - - -
Dimensions HxWxD mm 1,440x635x690 1,220x1,280x690 1,440x1,280x690 1,440x635x690 1,220x1,280x690 1,440x1,280x690
mode to those areas requiring heating.
Weight kg 140 230 250 140 230 250
Air flow rate m3/min 80 150 170 80 150 170
Sound pressure level (380V) dBA 54 57 57 54 57 57
Operation range cooling °CDB -5 ~ 43 -5 ~ 43 Inverter controlled
heating °CWB -15 ~ 15.5 -

Refrigerant: R-407C • Power supply: W1: 3N~, 400V, 50 Hz Refrigerant: R-22/R-407C • Power supply: Y1:3~, 400V, 50 Hz

INVERTER HP/CO R-407C RSXYP5K7W1 RSXYP8K7W1 RSXYP10K7W1 RSXP5K7W1 RSXP8K7W1 RSXP10K7W1 HEAT RECOVERY R-22/R-407C RSEY8KLY1 RSEY10KLY1 RSEYP8KJY1 RSEYP10KJY1
Cooling capacity kW 14.0 22.4 28.0 14.0 22.4 28.0 Cooling capacity kW 22.4 28.0 22.4 28.0
Heating capacity kW 16.0 25.0 31.5 - - - Heating capacity kW 25.0 31.5 25.0 31.5
Nominal input cooling kW 6.10 9.43 11.8 6.10 9.43 11.8 Nominal input cooling kW 9.43 11.8 9.43 11.8
heating kW 5.67 8.66 11.0 - - - heating kW 8.48 10.5 8.66 11.0
Dimensions HxWxD mm 1,440x635x690 1,220x1,280x690 1,440x1,280x690 1,440x635x690 1,220x1,280x690 1,440x1,280x690 Dimensions HxWxD mm 1,220x1,280x690 1,440x1,280x690 1,220x1,280x690 1,440x1,280x690
Weight kg 137 227 248 137 227 248 Weight kg 250 275 247 273
Air flow rate m3/min 80 150 170 80 150 170 Air flow rate m3/min 150 170 150 170
Sound pressure level (380V) dBA 54 57 58 54 57 58 Sound pressure level (380V) dBA 57 57 57 57
Operation range cooling °CDB -5 ~ 43 -5 ~ 43 Operation range cooling °CDB -5 ~ 43 -5 ~ 43 -5 ~ 43 -5 ~ 43
heating °CWB -15 ~ 15.5 - heating °CWB -15 ~ 15.5 -15 ~ 15.5 -15 ~ 15.5 -15 ~ 15.5
46 47
EPC99.09E•General 11/10/00 16:21 Page 50

VRV Plus using R-407C VRV Plus using R-22


Available in heat pump format Available in heat pump and
New The latest addition to the VRV Plus series heat recovery format.
is the heat pump version using R-407C Daikin VRV PLUS is a high capacity system for
refrigerant. This new line-up from 16HP installations between 16 and 30hp (3 times the
up to 30HP consists of 2 outdoor standard VRV capacity) and is the first available
components, main & sub unit. refrigerant flow system able to operate
main unit
Up to 32 indoor units can be as many as 30 indoor units on a
sub unit RSXYP20KJY1 connected to 1 single refrigerant single refrigerant circuit.
circuit. function
unit constant
The use of Daikin 'super wiring' reduces installation speed type inverter type RXY20K
costs by integrating the control and communication
wiring into a single circuit.

Refrigerant: R-22 • Power supply: W1: 3N~,400V, 50 Hz Power supply: V1: 1~, 230V, 50 Hz
Inverter type Constant speed type Function unit
VRV PLUS USING R-22 RXY8K7W1 RXY10K7W1 RNY8K7W1 RNY10K7W1 BR2KV1/BL2KV1 BR3KV1/BL3KV1
Cooling capacity kW 21.9 27.4 21.9 27.4 - -
main unit
Heating capacity kW 21.9 27.4 21.9 27.4 - -
Dimensions HxWxD mm 1,220x1,280x690 1,440x1,280x690 1,220x1,280x690 1,440x1,280x690 1,280x400x690 1,280x500x690
sub unit RSXYP28KJY1
Weight kg 220 240 220 240 80/64 96/76
Sound pressure level dBA 58 58 58 58 - -
Operation range cooling °CDB -5 ~ 43 -5 ~ 43 -5 ~ 43 -5 ~ 43 -5 ~ 43 -5 ~ 43
heating °CWB -15 ~ 15.5 -15 ~ 15.5 -15 ~ 15.5 -15 ~ 15.5 -15 ~ 15.5 -15 ~ 15.5
Refrigerant: R-407C • Power supply: Y1:3~, 400V, 50 Hz

RSXYP16KJY1 RSXYP18KJY1 RSXYP20KJY1


main unit sub unit main unit sub unit main unit sub unit
INVERTER HEAT PUMP RXYP8KJY1 RXEP8KJY1 RXYP10KJY1 RXEP8KJY1 RXYP10KJY1 RXEP10KJY1
INVERTER HEAT PUMP RXY16K RXY18K RXY20K RXY24K RXY26K RXY28K RXY30K
Equivalent HP HP 16 18 20 24 26 28 30
Cooling capacity kW 43.8 49.3 54.7
Cooling Capacity kW 43.8 49.3 54.7 65.7 71.2 76.1 82.1
Heating capacity kW 43.8 49.3 54.7
Heating Capacity kW 43.8 49.3 54.7 65.7 71.2 76.1 82.1
Nominal input (1) cooling W 15.7 18.1 20.2
Nominal input cooling kW 16.5 19.1 21.3 26.3 28.3 30.2 32.8
heating W 14.2 15.5 16.9
heating kW 13.5 14.8 16.1 20.4 20.9 22.8 25.8
Dimensions H mm 1,440 1,220 1,440 1,220 1,440 1,440
Indoor Unit Connectable Capacity 200-520 225-585 250-650 300-780 325-845 350-910 375-975
W mm 1,280 1,280 1,280 1,280 1,280 1,280
Function unit heat pump (L Unit) BL2KJV1 1 1 1
D mm 690 690 690 690 690 690
Function unit heat pump (L Unit) BL3KJV1 1 1 1 1
Weight kg 360 95 365 95 365 105
Inverter outdoor unit RXY8K7W1 1 1
Air flow rate m3/min 320 320 340
Inverter outdoor unit RXY10K7W1 1 1 1 1 1
Sound pressure level dBA 60 60 60
Constant speed type outdoor unit RNY8K7W1 1 1 2 2 1
Operation range cooling °CDB -5 ~ 43 -5 ~ 43 -5 ~ 43
Constant speed type outdoor unit RNY10K7W1 1 1 2
heating °CWB -15 ~ 15.5 -15 ~ 15.5 -15 ~ 15.5
(1) preliminary info

RSXYP24KJY1 RSXYP26KJY1 RSXYP28KJY1 RSXYP30KJY1


main unit sub unit main unit sub unit main unit sub unit main unit sub unit HEAT RECOVERY REY16K REY18K REY20K REY24K REY26K REY28K REY30K
INVERTER HEAT PUMP RXYP16KJY1 RXEP8KJY1 RXYP16KJY1 RXEP10KJY1 RXYP20KJY1 RXEP8KJY1 RXYP20KJY1 RXEP10KJY1 Equivalent HP HP 16 18 20 24 26 28 30
Cooling capacity kW 65.7 71.2 76.1 82.1 Cooling Capacity kW 43.8 49.3 54.7 65.7 71.2 76.1 82.1
Heating capacity kW 65.7 71.2 76.1 82.1 Heating Capacity kW 43.8 49.3 54.7 65.7 71.2 76.1 82.1
Nominal input (1) cooling W 25.0 26.9 28.7 31.2 Nominal input cooling kW 16.5 19.1 21.3 26.3 28.3 30.2 32.8
heating W 21.4 21.9 23.9 27.1 heating kW 13.5 14.8 16.1 20.4 20.9 22.8 25.8
Dimensions H mm 1,450 1,220 1,450 1,440 1,450 1,220 1,450 1,440 Indoor Unit Connectable Capacity 200-520 225-585 250-650 300-780 325-845 350-910 375-975
W mm 2,580 1,280 2,580 1,280 2,580 1,280 2,580 1,280 Function unit heat rec. (R Unit) BR2KJV1 1 1 1
D mm 690 690 690 690 690 690 690 690 Function unit heat rec. (R Unit) BR3KJV1 1 1 1 1
Weight kg 620 95 620 105 630 95 630 105 Inverter outdoor unit RXY8K7W1 1 1
Air flow rate m3/min 490 510 490 510 Inverter outdoor unit RXY10K7W1 1 1 1 1 1
Sound pressure level dBA 62 62 62 62 Constant speed type outdoor unit RNY8K7W1 1 1 2 2 1
Operation range cooling °CDB -5 ~ 43 -5 ~ 43 -5 ~ 43 -5 ~ 43 Constant speed type outdoor unit RNY10K7W1 1 1 2
heating °CWB -15 ~ 15.5 -15 ~ 15.5 -15 ~ 15.5 -15 ~ 15.5
48 (1) preliminary info 49
EPC99.09E•General 11/10/00 16:22 Page 52

VRV indoor units, available


in 10 different models and optional optional FXYC, FXYF, FXYS, FXYH,
(FXYB optional)
except VRV Inverter
Cooling only

60 different size combinations


(58 combinations with ozone- only FXYS, FXYH, FXYL(M), FXYC, FXYF, FXYC

friendly refrigerant R-407C), FXYM, FXYB FXYK, FXYS

can meet virtually any site


installation requirement. optional

Indoor units

FXYF(P) 4-way blow ceiling mounted cassette


FXYC(P) 2-way blow ceiling mounted cassette

Refrigerant: R-22 • Power supply: V1: 1~, 50Hz, 230V


Refrigerant: R-22 • Power supply: V1: 1~, 50Hz, 230V
FXYC-K7V1 20 25 32 40 50 63 80 125
FXYF-K7V1 20 25 32 40 50 63 80 100 125 Inverter CO/HP cooling capacity kW 2.2 2.8 3.6 4.5 5.6 7.1 9.0 14.0
Inverter CO/HP cooling capacity kW 2.2 2.8 3.6 4.5 5.6 7.1 9.0 11.2 14.0 Heat recovery heating capacity kW 2.5 3.2 4.0 5.0 6.3 8.0 10.0 16.0
Heat recovery heating capacity kW 2.5 3.2 4.0 5.0 6.3 8.0 10.0 12.5 16.0 VRV Plus cooling capacity kW 2.2 2.7 3.4 4.4 5.5 6.8 8.8 13.7
VRV Plus cooling capacity kW 2.2 2.7 3.4 4.4 5.5 6.8 8.8 10.9 13.7 heating capacity kW 2.2 2.7 3.4 4.4 5.5 6.8 8.8 13.7
heating capacity kW 2.2 2.7 3.4 4.4 5.5 6.8 8.8 10.9 13.7 Nominal input cooling W 77 92 92 130 130 153 209 256
Nominal input cooling W 140 140 140 140 140 161 204 204 238 heating W 44 59 59 97 97 120 176 223
heating W 107 107 107 107 107 128 171 171 205 Dimensions (HxWxD) unit mm 305x780x600 305x995x600 305x1,180x600 305x1,670x600
Dimensions (HxWxD) unit mm 240x840x840 280x1,230x840 decor. panel mm 53x1,030x680 53x1,245x680 53x1,430x680 53x1,920x680
decor. panel mm 50x950x950 50x1,340x950 Weight unit kg 26 26 26 31 32 35 47 48
Weight unit kg 25 25 25 25 25 25 34 34 35 decor. panel kg 8 8 8 8.5 8.5 9.5 12 12
decor. panel kg 6.5 6.5 6.5 6.5 6.5 6.5 9.5 9.5 9.5 Air flow rate H/L m3/min 7/5 9/6.5 9/6.5 12/9 12/9 15/12 26/20 32/24
Air flow rate H/L m3/min 10/7.8 10/7.8 13/10 14/10 16/11 19/14 28/19 28/19 33/22 Sound pressure level H/L dBA 33/25 35/30 35/30 36/30 36/30 36/31 43/36 45/39
Sound pressure level H/L dBA 31/29 31/29 35/30 35/30 36/31 37/32 40/34 40/34 44/37
Refrigerant: R-407C • Power supply: V1: 1~, 50Hz, 230V
Refrigerant: R-407C • Power supply: VE: 1~, 50Hz, 230V
FXYCP-K7V1 20 25 32 40 50 63 80 125
FXYFP-KVE 32 40 50 63 80 100 125 Inverter CO/HP cooling capacity kW 2.2 2.8 3.6 4.5 5.6 7.1 9.0 14.0
Inverter CO/HP cooling capacity kW 3.6 4.5 5.6 7.1 9.0 11.2 14.0 Heat recovery heating capacity kW 2.5 3.2 4.0 5.0 6.3 8.0 10.0 16.0
Heat recovery heating capacity kW 4.0 5.0 6.3 8.0 10.0 12.5 16.0 VRV Plus (1) cooling capacity kW 2.2 2.8 3.6 4.5 5.6 7.1 9.0 14.0
VRV Plus (1) cooling capacity kW 3.6 4.5 5.6 7.1 9.0 11.2 14.0 heating capacity kW 2.5 3.2 4.0 5.0 6.3 8.0 10.0 16.0
heating capacity kW 4.0 5.0 6.3 8.0 10.0 12.5 16.0 Nominal input (1) cooling W 77 92 92 130 130 161 209 256
Nominal input (1) cooling W 158 158 158 178 178 238 278 heating W 44 59 59 97 97 126 176 223
heating W 120 120 120 140 140 200 240 Dimensions (HxWxD) unit mm 305x780x600 305x995x600 305x1,180x600 305x1,670x600
Dimensions (HxWxD) unit mm 230x840x840 288x840x840 decor. panel mm 53x1,030x680 53x1,245x680 53x1,430x680 53x1,920x680
decor. panel mm 40x950x950 Weight unit kg 26 26 26 31 32 35 47 48
Weight unit kg 24 24 24 24 28 28 28 decor. panel kg 8 8 8 8.5 8.5 9.5 12 12
decor. panel kg 5 5 5 5 5 5 5 Air flow rate H/L m3/min 7/5 9/6.5 9/6.5 12/9 12/9 16.5/13 26/21 33/25
Air flow rate H/L m3/min 13/10 14/10 16/11 18/14 28/20 28/21 33/24 Sound pressure level H/L dBA 33/28 35/29 35/29 35.5/30.5 35.5/30.5 38/33 40/35 45/39
Sound pressure level H/L (220V) dBA 30/27 31/27 32/27 33/28 37/31 39/32 44/35 Sound power level dBA 45 50 50 50 50 52 54 60

50
(1) preliminary info for VRV Plus applications using R-407C (1) preliminary info for VRV Plus applications using R-407C
51
EPC99.09E•General 11/10/00 16:22 Page 54

FXYK(P) ceiling mounted corner cassette

Refrigerant: R-22/R-407C • Power supply: V1: 1~, 50Hz, 230V

FXYK-KJV1/FXYKP-KV1 25 32 40 63 25 32 40 63
Inverter CO/HP cooling capacity kW 2.8 3.6 4.5 7.1 2.8 3.6 4.5 7.1
Heat recovery heating capacity kW 3.2 4.0 5.0 8.0 3.2 4.0 5.0 8.0
VRV Plus (1) cooling capacity kW 2.7 3.4 4.4 6.8 2.8 3.6 4.5 7.1
heating capacity kW 2.7 3.4 4.4 6.8 3.2 4.0 5.0 8.0
Nominal input (1) cooling W 66 66 80 105 66 66 80 105
heating W 46 46 56 85 46 46 56 85
Dimensions (HxWxD) unit mm 215x1,110x710 215x1,310x710 215x1,110x710 215x1,310x710
decor. panel mm 70x1,240x800 70x1,440x800 70x1,240x800 70x1,440x800
Weight unit kg 31 31 31 34 31 31 31 34
decor. panel kg 8.5 8.5 8.5 9.5 8.5 8.5 8.5 9.5
Air flow rate H/L m3/min 11/9 11/9 12/9 17/14 11/9 11/9 13/10 18/15
Sound pressure level H/L dBA 39/34 39/34 40/34 42/37 38/33 38/33 42/35 42/37
(1) preliminary info for VRV Plus applications using R-407C

FXYM(P) concealed ceiling unit (large)

Refrigerant: R-22 • Power supply: V1: 1~, 50Hz, 230V/VE: 1~, 50Hz, 230V

FXYM-KJV1/VE* 40 50 63 80 100 125 200* 250*


Inverter CO/HP cooling capacity kW 4.5 5.6 7.1 9.0 11.2 14.0 22.4 28.0
Heat recovery heating capacity kW 5.0 6.3 8.0 10.0 12.5 16.0 25.0 31.5
VRV Plus cooling capacity kW 4.4 5.5 6.8 8.8 10.9 13.7 22.4 28.0
heating capacity kW 4.4 5.5 6.8 8.8 10.9 13.7 25.0 31.5
Nominal input cooling W 211 211 284 411 411 619 1,294 1,465
heating W 211 211 284 411 411 619 1,294 1,465
Dimensions HxWxD mm 390x720x690 390x1,110x690 470x1,380x1,100
Weight kg 44 44 45 62 63 65 137 137 FXYB(P) concealed ceiling unit (small)
Air flow rate H/L m3/min 14/11.5 14/11.5 18/15 29/23 29/23 36/29 58/50 72/62
Sound pressure level H/L (220V) dBA 39/35 39/35 41/37 43/39 43/39 45/42 48/45 48/45
Refrigerant: R-22 / R407-C •Power supply: V1: 1~, 50Hz, 230V
Refrigerant: R-407C • Power supply: V1: 1~, 50Hz, 230V
FXYB-K7V1/FXYBP-K7V1 20 25 20 25
FXYMP-KV1 40 50 63 80 100 125 200 250 Inverter CO/HP cooling capacity kW 2.2 2.8 2.2 2.8
Inverter CO/HP cooling capacity kW 4.5 5.6 7.1 9.0 11.2 14.0 22.4 28.0 Heat recovery heating capacity kW 2.5 3.2 2.5 3.2
Heat recovery heating capacity kW 5.0 6.3 8.0 10.0 12.5 16.0 25.0 31.5 VRV Plus (1) cooling capacity kW 2.2 2.7 2.2 2.8
VRV Plus (1) cooling capacity kW 4.5 5.6 7.1 9.0 11.2 14.0 22.4 28.0 heating capacity kW 2.2 2.7 2.5 3.2
heating capacity kW 5.0 6.3 8.0 10.0 12.5 16.0 25.0 31.5 Nominal input (1) cooling W 50 50 50 50
Nominal input (1) cooling W 211 211 281 411 411 619 1,294 1,465 heating W 50 50 50 50
heating W 211 211 281 411 411 619 1,294 1,465 Dimensions HxWxD mm 230x652x502 230x652x502
Dimensions HxWxD mm 390x720x690 390x1,110x690 470x1,380x1,100 Weight kg 17 17 17 17
Weight kg 44 44 45 62 63 65 137 137 Air flow rate H/L m3/min 6.7/5.2 7.4/5.8 6.7/5.2 7.4/5.8
Air flow rate H/L m3/min 14/11.5 14/11.5 19.5/16 29/23 29/23 36/29 58/50 72/62 Sound pressure level H/L dBA 37/32 37/32 37/32 37/32
Sound pressure level H/L (220V) dBA 39/35 39/35 42/38 43/39 43/39 45/42 48/45 48/45 Sound power level dBA - - 50 50

(1) preliminary info for VRV Plus applications using R-407C (1) preliminary info for VRV Plus applications using R-407C
52 53
EPC99.09E•General 11/10/00 16:22 Page 56

FXYA(P) wall mounted unit

Refrigerant: R-22/R-407C • Power supply: V1: 1~, 50Hz, 230V

FXYA-KJV1/FXYAP-KV1 25 32 40 50 63 25 32 40 50 63
Inverter CO/HP cooling capacity kW 2.8 3.6 4.5 5.6 7.1 2.8 3.6 4.5 5.6 7.1
Heat recovery heating capacity kW 3.2 4.0 5.0 6.3 8.0 3.2 4.0 5.0 6.3 8.0
VRV Plus (1) cooling capacity kW 2.7 3.4 4.4 5.5 6.8 2.8 3.6 4.5 5.6 7.1
heating capacity kW 2.7 3.4 4.4 5.5 6.8 3.2 4.0 5.0 6.3 8.0
Nominal input (1) cooling W 26 28 36 35 44 26 28 36 35 44
heating W 26 28 36 35 44 26 28 36 35 44
Dimensions HxWxD mm 360x1,050x200 360x1,250x200 360x1,050x200 360x1,250x200
Weight kg 21 24 21 24
Air flow rate H/L m3/min 7/6 8/6.5 10/8 12/10 15/12 8/6.5 9/7 11/9 13/11 15/12
Sound pressure level H/L dBA 34/31 35/32 40/33 41/36 45/41 35/32 37/33 41/34 43/37 45/41

(1) preliminary info for VRV Plus applications using R-407C

FXYS(P) concealed ceiling unit

Refrigerant: R-22 • Power supply: V1: 1~, 50Hz, 230V

FXYS-KA7V1 20 25 32 40 50 63 80 100 125


Inverter CO/HP cooling capacity kW 2.2 2.8 3.6 4.5 5.6 7.1 9.0 11.2 14.0
Heat recovery heating capacity kW 2.5 3.2 4.0 5.0 6.3 8.0 10.0 12.5 16.0
VRV Plus cooling capacity kW 2.2 2.7 3.4 4.4 5.5 6.8 8.8 10.9 13.7
heating capacity kW 2.2 2.7 3.4 4.4 5.5 6.8 8.8 10.9 13.7
Nominal input cooling W 110 110 110 127 140 184 216 216 290
heating W 90 90 90 107 120 164 196 196 270
Dimensions (HxWxD) unit mm 300x550x800 300x700x800 300x1,000x800 300x1,400x800
decor. panel mm 55x650x500 55x800x500 55x1,100x500 55x1,500x500
Weight unit kg 30 30 30 30 31 41 51 51 52
decor. panel kg 3 3 3 3.5 3.5 4.5 6.5 6.5 6.5
Air flow rate H/L m3/min 9/6.5 9/6.5 9/6.5 11.5/9 14/10 19/14 27/20 27/20 35/24
Sound pressure level H/L dBA 32/28 32/28 32/28 33/29 33/29 34/30 36/31 36/31 38/32

Refrigerant: R-407C • Power supply: V1: 1~, 50Hz, 230V FXYH(P) ceiling suspended unit

FXYSP-KA7V1 20 25 32 40 50 63 80 100 125 Refrigerant: R-22/R-407C •Power supply: V1: 1~, 50Hz, 230V
Inverter CO/HP cooling capacity kW 2.2 2.8 3.6 4.5 5.6 7.1 9.0 11.2 14.0
Heat recovery heating capacity kW 2.5 3.2 4.0 5.0 6.3 8.0 10.0 12.5 16.0 FXYH-K7V1/FXYHP-K7V1 32 63 100 32 63 100
VRV Plus (1) cooling capacity kW 2.2 2.8 3.6 4.5 5.6 7.1 9.0 11.2 14.0 Inverter CO/HP cooling capacity kW 3.6 7.1 11.2 3.6 7.1 11.2
heating capacity kW 2.5 3.2 4.0 5.0 6.3 8.0 10.0 12.5 16.0 Heat recovery heating capacity kW 4.0 8.0 12.5 4.0 8.0 12.5
Nominal input (1) cooling W 110 110 114 127 143 189 216 246 321 VRV Plus (1) cooling capacity kW 3.4 6.8 10.9 3.6 7.1 11.2
heating W 90 90 94 107 123 169 196 226 301 heating capacity kW 3.4 6.8 10.9 4.0 8.0 12.5
Dimensions (HxWxD) unit mm 300x550x800 300x700x800 300x1,000x800 300x1,400x800 Nominal input (1) cooling W 101 114 190 101 114 190
decor. panel mm 55x650x500 55x800x500 55x1,100x500 55x1,500x500 heating W 101 114 190 101 114 190
Weight unit kg 30 30 30 30 31 41 51 51 52 Dimensions HxWxD mm 188x1,100x600 188x1,300x600 238x1,300x695 188x1,100x600 188x1,300x600 238x1,300x695
decor. panel kg 3 3 3 3.5 3.5 4.5 6.5 6.5 6.5 Weight kg 27 31 38 27 31 38
Air flow rate H/L m3/min 9/6.5 9/6.5 9.5/7 11.5/9 15/11 21/15.5 27/20 28/20.5 38/28 Air flow rate H/L m3/min 13/10 18/14 26/20 13/10 19/15 27/21
Sound pressure level H/L dBA 32/28 32/28 33/28 33/29 35/31 35/30 37/31 38/33 40/35 Sound pressure level H/L dBA 38/33 40/35 43/38 38/33 42/37 45/40
Sound power level dBA 50 50 51 56 58 56 55 56 65 Sound power level dBA - - - 56 61 63
(1) preliminary info for VRV Plus applications using R-407C (1) preliminary info for VRV Plus applications using R-407C
54 55
EPC99.09E•General 11/10/00 16:22 Page 58

Refrigerant: R-22/R-407C • Power supply: VE: 1~, 50Hz, 230V/V1: 1~, 50Hz, 230V

FXYLM-KJVE/FXYLMP-KV1 20 25 32 40 50 63
Inverter CO/HP cooling capacity kW 2.2 2.8 3.6 4.5 5.6 7.1
New
Heat recovery heating capacity kW 2.5 3.2 4.0 5.0 6.3 8.0
VRV Plus (1) cooling capacity kW 2.2/2.2 2.7/2.8 3.4/3.6 4.4/4.5 5.5/5.6 6.8/7.1
R-22/R-407C heating capacity kW 2.2/2.5 2.7/3.2 3.4/4.0 4.4/5.0 5.5/6.3 6.8/8.0
Nominal input (1) cooling W 49 49 90 90 110 110
heating W 49 49 90 90 110 110
Dimensions HxWxD mm 610x930x220 610x1,070x220 610x1,350x220
Weight kg 19 19 23 23 27 27
Air flow rate
Sound pressure level
H/L
H/L (220V)
m3/min
dBA
7/6
35/32
7/6
35/32
8/6
35/32
11/8.5
38/33
14/11
39/34
16/12
40/35 HRV H E AT R E C O V E RY
V E N T I L AT I O N
(1) preliminary info for VRV Plus applications using R-407C

Clean outdoor air

Total heat exchanged foul air

FXYLM(P) concealed floor standing unit

Total heat exchanged


clean air

Foul indoor air

FXYL(P) floor standing unit The Daikin heat recovery ventilation system modulates the temperature and humidity of
Refrigerant: R-22 • Power supply: VE: 1~, 50Hz, 230V incoming fresh air to match indoor conditions.
A balance is thus achieved between indoor and outdoor ambients, enabling the cooling or
FXYL-KJVE 20 25 32 40 50 63 heating load placed on the air conditioning system to be reduced significantly.
Inverter CO/HP cooling capacity kW 2.2 2.8 3.6 4.5 5.6 7.1
Heat recovery heating capacity kW 2.5 3.2 4.0 5.0 6.3 8.0 HRV units can be controlled individually or integral with the air conditioning system
VRV Plus cooling capacity kW 2.2 2.7 3.4 4.4 5.5 6.8 (Daikin VRV or Sky Air series).
heating capacity kW 2.2 2.7 3.4 4.4 5.5 6.8
Nominal input cooling W 49 49 90 90 110 110
heating W 49 49 90 90 110 110
Dimensions HxWxD mm 600x1,000x222 600x1,140x222 600x1,420x222
Weight kg 25 25 30 30 36 36
Air flow rate H/L m3/min 7/6 7/6 8/6 11/8.5 14/11 16/12
Sound pressure level H/L (220V) dBA 35/32 35/32 35/32 38/33 39/34 40/35
Power supply: VE: 1~, 50Hz, 230V
Refrigerant: R-407C • Power supply: V1: 1~, 50Hz, 230V

VAM-FJVE 150 250 350 500 650 800 1000 1500 2000
FXYLP-KV1 20 25 32 40 50 63 Air flow rate m3/h 150 250 350 500 650 800 1,000 1,500 2,000
Inverter CO/HP cooling capacity kW 2.2 2.8 3.6 4.5 5.6 7.1 Sound pressure level (max.) (1) dBA 27/28.5 28/29 32/34 33/34.5 34.5/35.5 36/37 36/37 39.5/41.5 40/42.5
Heat recovery heating capacity kW 2.5 3.2 4.0 5.0 6.3 8.0 External static pressure (max.) Pa 69 64 98 98 93 137 157 137 137
VRV Plus (1) cooling capacity kW 2.2 2.8 3.6 4.5 5.6 7.1 Temperature exchange efficiency % 74 72 75 74 74 74 75 75 75
heating capacity kW 2.5 3.2 4.0 5.0 6.3 8.0 Enthalpy exchange efficiency (%) cooling 58 58 61 58 58 60 61 61 61
Nominal input (1) cooling W 49 49 90 90 110 110 heating 64 64 65 62 63 65 66 66 66
heating W 49 49 90 90 110 110 Dimensions H mm 269 269 285 285 348 348 348 710 710
Dimensions HxWxD mm 600x1,000x222 600x1,140x222 600x1,420x222 W mm 760 760 812 812 988 988 988 1,498 1,498
Weight kg 25 25 30 30 36 36 D mm 509 509 800 800 852 852 1,140 852 1,140
Air flow rate H/L m3/min 7/6 7/6 8/6 11/8.5 14/11 16/12 Weight kg 24 24 33 33 48 48 61 132 158
Sound pressure level H/L (220V) dBA 35/32 35/32 35/32 38/33 39/34 40/35 Duct diameter mm Ø 100 Ø 150 Ø 150 Ø 200 Ø 200 Ø 250 Ø 250 Ø 350 Ø 350
(1) preliminary info for VRV Plus applications using R-407C (1) Sound pressure level is measured in heat exchange mode.
56 57
EPC99.09E•General 11/10/00 16:23 Page 60

DACMS is a centralized control and management system for medium and large sized
buildings. Designed for use with Windows95®, Windows98® and WindowsNT® it offers New
precise control of VRV systems and associated heat recovery ventilation units, fans and even
lighting, from a personal computer and can monitor up to 1,024 indoor units from a single PC.

DAIKIN AIR CONDITIONING


MANAGEMENT SYSTEM
DACMS Hi-VRV SELECTION
PROGRAMME

DACMS can be integrated into a general building management system, both to control A simple to use, Daikin Hi-VRV air conditioning computerised selection programme,
the air conditioning (monitoring energy consumption, indoor temperatures etc) and also to designed for use with Windows95®, Windows98® and WindowsNT® systems, enables
provide a wide range of custom designed management and service functions. consulting engineers, design and build contractors, property developers and architects etc.
It can, for example, be used to limit energy consumption, indicate filter replacement needs to plan a Daikin air conditioning project on a step by step basis, complete with detailed
or calculate optimum start up periods. drawings, bills of quantities and costs.
The programme thus enables VRV air conditioning systems to be engineered precisely
Windows95®, Windows98® and WindowsNT® are registered trademarks of Microsoft corporation. and economically (without oversizing units), thereby ensuring optimum operating cycles
and maximum energy efficiency.

Windows95®, Windows98® and WindowsNT® are registered trademarks of Microsoft corporation.

58 59
EPC99.09E•General 11/10/00 16:23 Page 62

H ydronic systems
4
Precise environmental control is vital in many industrial and
commercial applications. Daikin offers an outstanding range of
powerful air cooled, water cooled and condenserless chiller systems
that will maintain ideal conditions in even the largest premises.
Daikin water chillers are of advanced design, compact and easy to
install and maintain.

They prove flexible and effective in multiple process cooling applications


in for example, fish farms, wine cellars, maritime transport,
agricultural, pharmaceutical or industrial processes. When combined
with air handling units or Daikin fan coil units of course, they are ideal

POWER & PRECISION


for air conditioning offices, hotels, restaurants and even domestic premises.

Matched and flexible equipment/refrigerant combinations enable


Daikin to offer a complete range of chillers, genuinely optimised for
use with R-134a and R-407C and possessing the same quality and
performance levels as comparable R-22 models. All chiller components
-evaporator, condenser, dryer, oil etc - have been specially selected for use
with either R-407C or R-134a refrigerants. The end result is a range of
hi tech, high performance units, indicated by published EUROVENT
data to be among the most energy efficient of their type on the market.

Advanced technology allied unsurpassed product reliability and quality,


make Daikin chillers the first choice for professionals.

61
EPC99.09E•General 11/10/00 16:23 Page 64

CHILLERS
EUWA/Y EUWA-HZ CHILLERS
air cooled air cooled
• low operating sound level
• low energy consumption
• extremely compact
• Daikin scroll compressor
• electronic controller
• wide operating range • optimised for use with R-407C
• easy to install and maintain • special Daikin R-407C scroll
• anti-corrosion treated plate type heat exchangers compressors
• available in cooling only (EUWA) and heat pump • high energy efficiency ratio
format (EUWY) • low pressure drops
• low sound level
• low direct on line start up current
• small footprint
• standard operating range from
-5°C to 43°C ambient temperature

Refrigerant : R-22 • Power supply: W1 = 3N~, 50Hz, 400V; T1 = 3~, 50Hz, 230V.

Refrigerant : R-407C • Power supply: W1 = 3N~, 50Hz, 400V; T1 = 3~, 50Hz, 230V. (except for 12HP)
COOLING ONLY EUWA5HD EUWA8HD EUWA10HD EUWA15HD EUWA20HD EUWA25HD EUWA30HD
Cooling capacity kW 10.3 18.3 21.6 30.7 43.6 52.9 65.2
Nominal input kW 4.3 6.4 8.5 13.2 17.3 21.5 26 COOLING ONLY EUWA5HDZ EUWA8HDZ EUWA10HDZ EUWA12HDZ
Dimensions HxWxD mm 1,444x645x700 1,220x1,290x700 1,444x1,290x700 1,535x1,930x700 1,535x2,575x700 1,535x3,220x700 1,535x3,865x700 Cooling capacity kW 10.1 17.7 22.7 26.5
Weight kg 135 200 230 375 510 655 780 Nominal input kW 4.2 7.2 8.5 10.6
Sound power/pressure level dB(A) 69/- 78/- 78/- 78/- 81/- 81/- 83/- Dimensions HxWxD mm 1,444x645x700 1,220x1,290x700 1,444x1,290x700 1,444x1,290x700
Weight kg 135 200 230 233
Sound power/pressure level dB(A) 69/56 78/61 78/61 78/61
Refrigerant : R-22 • Power supply: W1 = 3N~, 50Hz, 400V

Refrigerant : R-407C • Power supply: W1 = 3N~, 50Hz, 400V; T1 = 3~, 50Hz, 230V. (except for 25,35HP)
HEAT PUMP EUWY5HD EUWY8HD EUWY10HD EUWY15HD EUWY20HD EUWY25HD EUWY30HD
Cooling capacity kW 9.1 17.7 21.0 30.0 42.4 51.5 63.4
Heating capacity kW 11.9 20 25.4 36.4 50.3 62.3 75.2 COOLING ONLY EUWA15HDZ EUWA20HDZ EUWA25HDZ EUWA30HDZ EUWA35HDZ
Nominal input cooling kW 4.2 6.4 8.4 13.0 17.0 21.2 25.6 Cooling capacity kW 32.8 45.4 53.0 68.1 79.5
heating kW 4.2 7 8.5 12.6 17.3 21.5 25.9 Nominal input kW 12.7 17.0 21.2 25.5 31.8
Dimensions HxWxD mm 1,444x645x700 1,220x1,290x700 1,444x1,290x700 1,535x1,930x700 1,535x2,575x700 1,535x3,220x700 1,535x3,865x700 Dimensions HxWxD mm 1,535x1,930x700 1,535x2,575x700 1,535x2,575x700 1,535x3,865x700 1,535x3,865x700
Weight kg 140 208 240 390 530 675 800 Weight kg 375 510 510 780 780
Sound power/pressure level dB(A) 69/- 78/- 78/- 78/- 81/- 81/- 83/- Sound power/pressure level dB(A) 78/62 81/64 81/64 83/67 83/67

62 63
EPC99.09E•General 11/10/00 16:23 Page 66

low noise
option

CHILLERS
EUWA* EUWA*-KX CHILLERS
air cooled air cooled
• low operating sound level • optimised for use with R-134a
• single screw compressor • special Daikin single screw compressor
• high energy efficiency ratio • high EER
• operating range from • low noise option available
-15°C to 43°C • BMS connection possible
• available in 6 models with • evaporators located in the middle
nominal cooling capacities of the unit
EUWA* 40 - 60 KAX
from 101 to 300 kW • 2 switchboxes (high and low voltage)
• units with special pressure vessel • new compressor housing
approval are available on request • victaulic joints for plate heat exchangers
• pre mounted 5 inch piping for easier
field piping operations (from 160hp on)
EUWA* 40 - 60 KA

EUWA* 160 - 200 KX

Refrigerant : R-134a • Power supply: Y1 = 3~, 50Hz, 400V; T1 = 3~, 50Hz, 230V (only EUWA*40-120K(A)X)

COOLING ONLY EUWA*40KAX EUWA*50KAX EUWA*60KAX EUWA*80KAX EUWA*100KAX


Cooling capacity kW 111 140 166 211 276
Nominal input kW 39.1 53.7 64 79 110
EUWA* 80 - 120 KA Dimensions HxWxD mm 2,135x3,980x1,110 2,156x3,980x2,210
Weight kg 1,391 1,600 1,705 2,710 3,210
Sound power/pressure level dB(A) 91/- 97/- 95/- 94/- 100/-

Refrigerant : R-22 • Power supply: Y1: 3~, 50 Hz, 400V / T1: 3~, 50Hz, 230V Refrigerant : R-134a • Power supply: Y1 = 3~, 50Hz, 400V; T1 = 3~, 50Hz, 230V (only EUWA*40-120K(A)X)

COOLING ONLY EUWA*40KA EUWA*50KA EUWA*60KA EUWA*80KA EUWA*100KA EUWA*120KA COOLING ONLY EUWA*120KAX EUWA*160KX EUWA*180KX EUWA*200KX
Cooling capacity kW 101 129 161 202 258 300 Cooling capacity kW 316 400 438 475
Nominal input kW 38.5 52.7 59.0 78.5 106 115 Nominal input kW 130 164 178 191
Dimensions HxWxD mm 2,135x3,980x1,110 2,156x3,980x2,210 Dimensions HxWxD mm 2,156x3,980x2,210 2,156x5,906x2,265
Weight kg 1,205 1,345 1,530 2,500 2,750 2,950 Weight kg 3,260 5,400 5,450 5,500
Sound power/pressure level dB(A) 88/- 92/- 94/- 97/- 96/- 95/- Sound power/pressure level dB(A) 98/- 99/- 100/- 100/-

* =T(Germany - TüV), K(Finland - TTK), M(France - SdM), B(Italy - ISPESL), Q(Poland-UDT), D(The Netherlands - RLK law), S(Sweden - AB-Staten) according * =T(Germany - TüV), K(Finland - TTK), M(France - SdM), B(Italy - ISPESL), Q(Poland-UDT), D(The Netherlands - RLK law), S(Sweden - AB-Staten) according
64 65
to corresponding pressure vessel approval. to corresponding pressure vessel approval.
EPC99.09E•General 11/10/00 16:24 Page 68

CHILLERS
EUWA*-LZ EUWAC CHILLERS
air cooled air cooled
• Daikin single screw compressor
• all components optimised for use with R-407C refrigerant
• electronic DDC control
• modular format
• standard operating range down to -15°C ambient
• high quality, standard anti-corrosion treated components
• moisture indicator as standard
• victaulic joints as standard
EUWA*40 - 60LZ
• chilled water temperatures down to 4°C
(down to -10°C with ZL option and glycol)
• optional BMS and DICN
connection available
• double refrigeration circuits
(from 160hp on)
• pre-mounted, 5 inch piping
for easier field connection • centrifugal fan
• cooling only application
• nom. cooling capacities ranging
from 11.5 to 23.0 kW
EUWA*80 - 120LZ • available in 3 standard sizes
Refrigerant : R-407C • Power supply: Y1 = 3~, 50Hz, 400V
• specially designed for inside
installation
COOLING ONLY EUWA*40LZ (1) EUWA*50LZ (1) EUWA*60LZ EUWA*80LZ (1) EUWA*100LZ (1)
Cooling capacity kW 99 131 155 205 269
Nominal input kW 43 55 66 87 112
Dimensions HxWxD mm 2,160x2,340x2,238 2,165x4,280x2,238
Weight kg 1,346 1,610 1,637 2,833 3,152
Sound power/pressure level dB(A) 88/- 92/- 96/- 95/- 96/-

Refrigerant : R-22 • Power supply: W1 = 3N~, 50Hz, 380/415V; T1 = 3~, 50Hz, 220V.
Refrigerant : R-407C • Power supply: Y1 = 3~, 50Hz, 400V
COOLING ONLY EUWAC5FA EUWAC8FA EUWAC10FA
COOLING ONLY EUWA*120LZ (1) EUWA*160LZ EUWA*180LZ EUWA*200LZ Cooling capacity kW 11.5 18.8 23.0
Cooling capacity kW 310 419 479 539 Nominal input kW 5.2 9.0 11.1
Nominal input kW 135 171 202 232 Maximum external static pressure mmH2O 10 15 15
Dimensions HxWxD mm 2,165x4,280x2,238 2,165x5,906x2,238 Dimensions HxWxD mm 1,345x795x605 1,290x1,125x605 1,395x1,175x605
Weight kg 3,404 5,002 5,044 5,086 Weight kg 175 230 270
Sound power/pressure level dB(A) 97/- 100/- 101/- 102/- Sound power/pressure level dB(A) -/53 -/59 -/60

66
* =T (Germany - TüV), K(Finland - TTK), M(France - SdM), B(Italy - ISPESL), Q(Poland - UDT), D(The Netherlands - RLK law), S(Sweden - AB-Staten) 67
according to corresponding pressure vessel approval. / (1) Preliminary info
EPC99.09E•General 11/10/00 16:25 Page 70

EUWL*40-100KX

CHILLERS

CHILLERS
EUW(H) EUW(L)*-KX water cooled /
water cooled • the most compact unit in the market
remote condenser
• optimised design for use with R-134a
• special Daikin screw compressor
• high EER
• electronic controller
• control on cold and hot side
• voltage free contacts (for alarms etc)
• LWE control
• lead lag switch
• victaulic joints as standard
• totally independent twin circuits
(from 120hp on) EUW*120-200KX
• condenserless units available throughout
the range
Refrigerant : R-134a • Power supply: T1 = 3~, 50Hz, 230V/ Y1 = 3~, 50Hz, 4000V

EUW(L)*40KX EUW(L)*60KX EUW(L)*80KX EUW(L)*100KX


Cooling capacity (EUW) kW 120 190 249 290
• for indoor (or outdoor) installation Cooling capacity (EUWL) kW 119 188 246 287
Heating capacity (EUW) kW 149 237 313 362
• available in cooling only (EUW) Power input (EUW) Cooling kW 30.0 48.6 66.1 74.0
and heating only (EUWH) models Power input (EUWL) Cooling kW 30.5 49.4 67.2 75.3
Power input (EUW) Heating kW 35.1 57.2 75.5 87.3
• units with special pressure vessel
Dimensions HxWxD mm 1,014x2,672x898
approval are available on request Weight (EUW) kg 990 1,320 1,640 1,680
• hermetic reciprocating compressor Weight (EUWL) kg 882 1,100 1,370 1,410
Sound power/pressure level dB(A) 90/- 96/- 96/- 98/-

Refrigerant : R-134a • Power supply: T1= 3~,50Hz, 230V / Y1 = 3~, 50Hz, 400V

EUW(L)*120KX EUW(L)*140KX EUW(L)*160KX EUW(L)*180KX EUW(L)*200KX


Refrigerant : R-22 • Power supply: T1=3~, 50Hz, 230V ; Y1 = 3~, 50Hz, 400V Cooling capacity (EUW) kW 380 439 498 539 580
Cooling capacity (EUWL) kW 376 434 493 533 574
C/O & H/O EUW(H)5FB EUW(H)8FA EUW(H)10FA EUW(H)15F EUW(H)20F Heating capacity (EUW) kW 474 551 626 675 724
Cooling capacity kW 13.2 20.4 26.8 49.4 59.6 Power input (EUW) Cooling kW 97.2 115 132 140 148
Heating capacity kW 16.1 24.2 32.0 56.6 68.9 Power input (EUWL) Cooling kW 98.9 117 134 143 151
Nominal input cooling kW 3.9 5.8 7.6 12.3 15.3 Power input (EUW) Heating kW 114 133 151 163 175
heating kW 4.4 6.5 8.5 13.6 16.9 Dimensions HxWxD mm 2,000x2,672x898
Dimensions HxWxD mm 700x904x604 800x1,104x754 800x1,104x754 1,155x1,092x448 1,155x1,092x448 Weight (EUW) kg 2,640 2,960 3,280 3,320 3,360
Weight kg 150 200 215 285 306 Weight (EUWL) kg 2,200 2,470 2,740 2,780 2,820
Sound power/pressure level dB(A) -/50 -/51 -/51 -/56 -/59 Sound power/pressure level dB(A) 99/- 99/- 99/- 100/- 101/-

* =T(Germany - TüV), K(Finland - TTK), M(France - SdM), B(Italy - ISPESL), Q(Poland-UDT), D(The Netherlands - RLK law), S(Sweden - AB-Staten)
68 69
according to corresponding pressure vessel approval.
EPC99.09E•General 11/10/00 16:25 Page 72

DAIKIN INTEGRATED
CHILLER NETWORK
D.I.C.N EHMC HYDRAULIC MODULE

• 3 models available
• 100 l tank for all sizes (even for 35 H.P. chiller)
models R-22 models R-407C models R-134a
• freeze up protection
EUWAT(B,M,D)40,50,60KAY1/T1 EUWAT(B,D,K,Q,M,S)40,50,60,80,100,120,160,180,200LZY1 EUWAT(B,D,K,Q,M,S)40,50,60,80,100,120KAXY1/T1 • low and high static pump (option)
EUWAT(B,M,D)80,100,120KAY1/T1 EUWAT(B,D,K,Q,M,S)160,180,200KXY1 • specially designed for Daikin EUWA5-30HD,
EUWT(B,D,K,Q,M,S)40,60,80,100,120KXY1/T1
EUWT(B,D,K,Q,M,S)160,180,200KXY1/T1
EUWA5-35HDZ and EUWY5-30HD water chillers
• standard drain kit (for indoor use)
• standard dual pressure ports
(before & behind the pump)

Daikin chillers with DDC control can be equipped with DICN which allows the simultaneous
operation of up to 4 chillers as if they were a single unit, in order to deliver the required
EHMC10-15-30 AV1010
cooling capacity. This results in precise and efficient capacity control and is also useful for
back up purposes, ensuring that the necessary amount of cooling is available and
guaranteeing reliable operation of the chiller plant.
This function enables a Daikin 2MW chiller plant to be operated via a single controller.

(1) for high static option Power supply: V1 = 1~, 50Hz, 230V.

EHMC EHMC10AV1010 EHMC15AV1010 EHMC30AV1010


Nominal flow l/min 62 88 187
Nominal static height mH2O 17/34 (1) 15/27 (1) 10/27 (1)
Nominal input W 630/1,050 (1) 650/1,070 (1) 1,070/2,090 (1)
Dimensions HxWxD mm 1,284x635x688
Weight kg 99 102 105
Sound power/pressure level dB(A) 63/52 63/52 63/52
Operation range (airside/waterside) -10°C to +43°C /-10°C to +55°C

70 71
EPC99.09E•General 11/10/00 16:25 Page 74

Low wall unit

Power supply: V1 = 1~, 50Hz, 230V.

FWV-BA6V1 / FWV-BAF6V1 1 2 3 4 6 8 10
Cooling capacity (2-/4-pipe) kW 1.31 / 1.29 1.98 / 1.95 2.90 / 2.86 3.89 / 3.83 4.60 / 4.54 6.29 / 6.20 7.84 / 7.73
Heating capacity (2-/4-pipe) kW 1.77 / 1.90 2.55 / 2.49 3.64 / 3.68 4.88 / 4.74 6.35 / 6.05 8.03 / 8.07 10.1 / 10.2
Nominal input H/L W 38/20 66/27 60/29 84/36 111/54 180/87 242/111
Dimensions HxWxD mm 560x775x228 560x985x228 560x1195x228 560x1405x253
Weight (2-/4-pipe) kg 20.1 / 21.2 20.6 / 21.7 26.1 / 27.4 31.8 / 33.5 31.8 / 33.5 40.8 / 43.1 40.8 / 43.1
Air flow rate (2-/4-pipe) M l/s 52.9 / 51.9 68.7 / 67.4 95.9 / 93.9 133.1 / 130.4 171.7 / 168.3 224.6 / 220.1 278.9 / 273.4

FA N C O I L U N I T S
FWV(M)/FWH(M)/FWHC Sound pressure level
Sound power level
H/L
H/L
dB(A)
dB(A)
33/20
47/34
40/23
54/37
34/19
48/33
38/23
52/37
46/32
60/46
48/35
62/49
53/40
67/54

5 different models, several capacity versions Concealed low wall unit


• low sound level
• fashionable design Power supply: V1 = 1~, 50Hz, 230V.

• wide range of options


FWVM-BA6V1 / FWVM-BAF6V1 1 2 3 4 6 8 10
• to be combined with water chiller or boiler Cooling capacity (2-/4-pipe) kW 1.31 / 1.29 1.98 / 1.95 2.90 / 2.86 3.89 / 3.83 4.60 / 4.54 6.29 / 6.20 7.84 / 7.73
• washable air filter Heating capacity (2-/4-pipe) kW 1.77 / 1.90 2.55 / 2.49 3.64 / 3.68 4.88 / 4.74 6.35 / 6.05 8.03 / 8.07 10.1 / 10.2
Nominal input H/L W 38/20 66/27 60/29 84/36 111/54 180/87 242/111
Dimensions HxWxD mm 535x498x223 535x708x223 535x918x223 535x1,128x248
Weight (2-/4-pipe) kg 14.6 / 15.7 15.1 / 16.2 19.5 / 20.8 23.8 / 25.5 24.6 / 26.3 31.8 / 34.1 31.8 / 34.1
Air flow rate (2-/4-pipe) M l/s 52.9 / 51.9 68.7 / 67.4 95.9 / 93.9 133.1 / 130.4 171.7 / 168.3 224.6 / 220.1 278.9 / 273.4
Sound pressure level H/L dB(A) 36/23 43/26 37/22 42/26 49/35 51/38 56/43
Sound power level H/L dB(A) 47/34 54/37 48/33 52/37 60/46 62/49 67/54

Ceiling suspended unit

Power supply: V1 = 1~, 50Hz, 230V.

FWH-BA6V1 / FWH-BAF6V1 1 2 3 4 6 8 10
Cooling capacity (2-/4-pipe) kW 1.31 / 1.29 1.98 / 1.95 2.90 / 2.86 3.89 / 3.83 4.60 / 4.54 6.29 / 6.20 7.84 / 7.73
Heating capacity (2-/4-pipe) kW 1.77 / 1.90 2.55 / 2.49 3.64 / 3.68 4.88 / 4.74 6.35 / 6.05 8.03 / 8.07 10.1 / 10.2
Nominal input H/L W 38/20 66/27 60/29 84/36 111/54 180/87 242/111
Dimensions HxWxD mm 228x775x560 228x985x560 228x1,195x560 253x1,405x560
Weight (2-/4-pipe) kg 20.9 / 22 22.1 / 23.2 27.7 / 29 33.3 / 35 33.3 / 35 42.3 / 44.6 43.1 / 45.4
Air flow rate (2-/4-pipe) M l/s 52.9 / 51.9 68.7 / 67.4 95.9 / 93.9 133.1 / 130.4 171.7 / 168.3 224.6 / 220.1 278.9 / 273.4
Sound pressure level H/L dB(A) 33/20 40/23 34/19 38/23 46/32 48/35 53/40
Sound power level H/L dB(A) 47/34 54/37 48/33 52/37 60/46 62/49 67/54

Concealed ceiling unit

Power supply: V1 = 1~, 50Hz, 230V.

FWHM-BA6V1 / FWHM-BAF6V1 1 2 3 4 6 8 10
Cooling capacity (2-/4-pipe) kW 1.31 / 1.29 1.98 / 1.95 2.90 / 2.86 3.89 / 3.83 4.60 / 4.54 6.29 / 6.20 7.84 / 7.73
Heating capacity (2-/4-pipe) kW 1.77 / 1.90 2.55 / 2.49 3.64 / 3.68 4.88 / 4.74 6.35 / 6.05 8.03 / 8.07 10.1 / 10.2
Nominal input H/L W 38/20 66/27 60/29 84/36 111/54 180/87 242/111
Dimensions HxWxD mm 223x706x535 223x916x535 223x1,126x535 248x1,336x535
Weight (2-/4-pipe) kg 15.3 / 16.4 16.1 / 17.2 20.4 / 21.7 24.8 / 26.5 25.1 / 26.7 33.3 / 35.6 33.3 / 35.6
Air flow rate (2-/4-pipe) M l/s 52.9 / 51.9 68.7 / 67.4 95.9 / 93.9 133.1 / 130.4 171.7 / 168.3 224.6 / 220.1 278.9 / 273.4
Sound pressure level H/L dB(A) 33/20 40/23 34/19 38/23 46/32 48/35 53/40
Sound power level H/L dB(A) 47/34 54/37 48/33 52/37 60/46 62/49 67/54

72 73
EPC99.09E•General 11/10/00 16:25 Page 76

Daikin Chiller S E L E C T I O N S O F T WA R E

Purpose designed, user friendly and powerful, this facility simplifies and speeds up
the selection of Daikin chillers. The built-in programme enables the most suitable selection
to be made according to cooling/heating capacity and specified design conditions.
Extensive print outs are available.
The Daikin chiller selection programme runs under Windows95®, Windows98® and
WindowsNT®, without specific computer requirements.

Daikin chillers are equipped with a user friendly electronic controller, complete with
electronic sensors to monitor and provide information on water inlet and outlet temperatures
and air/coil temperatures. The controller also incorporates a number of safety devices, timer
functions, an adjustable thermostat function etc.

The selection software covers a complete database of all chiller units, which includes
specifications, wiring diagrams, piping diagrams, technical data, options and
installation space.

Windows95®, Windows98® and WindowsNT® are registered trademarks of Microsoft corporation.

2-way blow cassette

Power supply: V1=1~, 230V, 50Hz

2-PIPE SYSTEM FWHC2B FWHC3B FWHC4B FWHC6B FWHC8B FWHC12B


Cooling capacity kW 1.96 2.58 3.71 5.36 7.22 9.32
Heating capacity kW 3.58 4.79 6.80 9.79 13.52 17.6
Nominal input W 48 71 85 112 172 207
Dimensions (HxWxD) unit mm 449x591x550 449x721x550 449x871x550 449x1,181x550 449x1,491x550 449x1,951x550
decor. panel mm 48x855x550 48x985x550 48x1,135x550 48x1,445x550 48x1,755x550 48x2,215x550
Weight unit kg 16 19 23 32 39 50
decor. panel kg 4 5 7 8 11 13
Air flow rate H l/s 101.7 141.7 188.3 283.3 376.7 566.7
Sound pressure level H/L dBA 30/19 32/21 32/21 33/22 36/26 38.5/27

Power supply: V1=1~, 230V, 50Hz

4-PIPE SYSTEM FWHC2BF FWHC3BF FWHC4BF FWHC6BF FWHC8BF FWHC12BF


Cooling capacity kW 2.26 2.85 3.63 4.47 6.38 7.85
Heating capacity kW 2.50 3.22 4.14 5.31 8.02 10.86
Nominal input W 44 64 68 99 129 219
Dimensions (HxWxD) unit mm 449x591x550 449x721x550 449x871x550 449x1,181x550 449x1,491x550 449x1,951x550
decor. panel mm 48x855x550 48x985x550 48x1,135x550 48x1,445x550 48x1,755x550 48x2,215x550
Weight unit kg 18 21 26 36 44 57
decor. panel kg 4 5 7 8 11 13
Air flow rate H l/s 101.7 141.7 183.3 271.7 350 511.7
Sound pressure level H/L dBA 30/19 32/21 32/21 33/22 36/26 38.5/27

74 75
EPC99.09D•Eng•OK 31/03/00 12:21 Page 78

ER

5
CONDENSING UNIT

• split type condensing unit


• slim and compact
• easy to install and maintain
• indoor or outdoor installation

CONDENSING UNITS
Refrigerant : R-22 • Power supply: T1 = 3~, 50Hz, 230V

COOLING ONLY ER3DA ER5DA ER8DA ER10DA


Cooling capacity kW 8.3 13.0 22.2 26.6
Nominal input kW 3.0 4.5 7.1 9.5
Dimensions HxWxD mm 796 x 922 x 373 1,179 x 922 x 373 1,254 x 1,390 x 373 1,560 x 1,390 x 373
Weight kg 85 130 185 210
Sound power/pressure level dB(A) 67/54 71/58 72/59 73/60

77