                            Analogue threshold display
                                              DP2200
11470257 / 00   09 / 2022
DP2200                                                                                                          Analogue threshold display
Contents
1    Preliminary note . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .         4
     1.1 Symbols used . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .               4
     1.2 Warnings used . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                4
2    Safety instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .         5
3    Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .       6
     3.1 Block diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .              6
4    Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .     7
     4.1 Use as a stand-alone device without IO-Link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                                7
     4.2 Application as an IO-Link device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                       7
        4.2.1 General information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                    7
        4.2.2 Application example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                     8
        4.2.3 Functionality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .               8
        4.2.4 IO Device Description (IODD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                          8
5    Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .    9
6    Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
     6.1 Removing the connector with vibration protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
     6.2 Cable length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
7    Operating and display elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                  12
     7.1 Push rings (pushbuttons) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                    12
     7.2 LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .        12
     7.3 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .         12
        7.3.1 Representation of the measured current value . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                                   13
8    Menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   14
     8.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .         14
     8.2 Menu structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .              15
     8.3 Parameters of the main menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                       15
        8.3.1 SP1/rP1 ─ set point/reset point OUT1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                              15
        8.3.2 FH1/FL1 ─ min/max switching limits for window function . . . . . . . . . . . . . . . . . . . . .                                         16
        8.3.3 EF ─ extended functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                      16
     8.4 Parameters of the extended functions (EF) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                             16
        8.4.1 rES ─ restore factory setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                      16
        8.4.2 A.Trm ─ analogue termination for OUT2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                                16
        8.4.3 ou1 ─ output function for OUT1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                          16
        8.4.4 dS1/dr1 ─ switching delay/switch-off delay for OUT1 . . . . . . . . . . . . . . . . . . . . . . . .                                      17
        8.4.5 ScAL ─ scaling of the displayed value. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                             17
        8.4.6 C.ASP/C.AEP - customer-specific analogue start/end point . . . . . . . . . . . . . . . . . . .                                           17
        8.4.7 coLr ─ display colours and colour changes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                                18
        8.4.8 cFH/cFL ─ upper/lower value for colour change . . . . . . . . . . . . . . . . . . . . . . . . . . . .                                    18
        8.4.9 diS ─ refresh rate of the displayed measured value . . . . . . . . . . . . . . . . . . . . . . . . .                                     19
        8.4.10 Lo/Hi ─ min/max measured input values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                               19
        8.4.11 dAP ─ damping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                 19
        8.4.12 Reset [Hi] and [Lo] memory. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                       19
     8.5 Parameters adjustable via IO-Link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                         19
        8.5.1 C.uni – customer-specific unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                       19
        8.5.2 S.Loc – software locking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                     20
        8.5.3 Application-specific tag . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                   20
9    Parameter setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .         21
     9.1 Parameter setting in general . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                    21
     9.2 Example [ou1] ─ output function for OUT1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                              21
     9.3 Notes on programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                    22
        9.3.1 Locking / unlocking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                  22
        9.3.2 Timeout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .             22
        9.3.3 Numerical entries with [▼] or [▲] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                          22
10 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
   10.1 Functions output 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
2
Analogue threshold display                                                                                                           DP2200
                                                                                                                                               3
DP2200                                                                      Analogue threshold display
1 Preliminary note
You will find instructions, technical data, approvals and further information using the QR code on the
unit / packaging or at www.ifm.com.
1.1 Symbols used
            Requirement
            Instructions
            Reaction, result
    [...]   Designation of keys, buttons or indications
            Cross-reference
            Important note
            Non-compliance may result in malfunction or interference.
            Information
            Supplementary note
1.2 Warnings used
            CAUTION
            Warning of personal injury
            w Slight reversible injuries may result.
4
Analogue threshold display                                                                         DP2200
2 Safety instructions
•   The unit described is a subcomponent for integration into a system.
    – The system architect is responsible for the safety of the system.
    – The system architect undertakes to perform a risk assessment and to create documentation in
      accordance with legal and normative requirements to be provided to the operator and user of
      the system. This documentation must contain all necessary information and safety instructions
      for the operator, the user and, if applicable, for any service personnel authorised by the
      architect of the system.
•   Read this document before setting up the product and keep it during the entire service life.
•   The product must be suitable for the corresponding applications and environmental conditions
    without any restrictions.
•   Only use the product for its intended purpose (Ò Intended use).
•   If the operating instructions or the technical data are not adhered to, personal injury and/or damage
    to property may occur.
•   The manufacturer assumes no liability or warranty for any consequences caused by tampering with
    the product or incorrect use by the operator.
•   Installation, electrical connection, set-up, programming, configuration, operation and maintenance
    of the product must be carried out by personnel qualified and authorised for the respective activity.
•   Protect units and cables against damage.
•   Replace damaged units, otherwise the technical data and safety will be impaired.
•   Observe applicable documents.
                                                                                                        5
DP2200                                                                                  Analogue threshold display
3 Intended use
The device is used for the evaluation of an analogue signal (4...20 mA) from a connected sensor or
another device with analogue output (4...20 mA). The device has one analogue current input and two
outputs: output 1 (digital) and optionally output 2 (analogue current output).
        The unit is not suited for environments with particular requirements on mechanical stability (e.g.
        shock/vibration).
        The unit is intended for indoor use only.
        u Observe the operating conditions (Ò Technical data at www.ifm.com).
3.1 Block diagram
                                                      DP2200
                                                                     OUT1 (SIO / IO-Link)
                                                                                               2
                               Input (analogue) IIN                  OUT2 (analogue)
                        1                                                                      3
                                                          A.Trm
                                                           *)       **)
        The current loop of the analogue input must be terminated. Only one load may be connected,
        either an internal or an external load.
        See:
        A.Trm ─ analogue termination for OUT2 (Ò / 16)
        Troubleshooting (Ò / 24)
6
Analogue threshold display                                                                                    DP2200
4 Function
There are basically two modes in which the device can be operated:
•    As stand-alone device
     The device compares the measured current value with the set parameters and switches its output
     according to the selected parameters. This mode is without IO-Link functionality. The parameters
     can, however, also be set with an IO-Link tool.
•    As IO-Link device
     The device operates as an “analogue/IO-Link converter”. The evaluation of the measured current
     value depends on the parameters which are set with IO-Link tools or a PLC via IO-Link
     communication or directly on the device.
        In some points parameter setting via IO-Link tools or PLC is different from parameter setting via
        the menu (Ò Parameter setting).
                                                                   24 V DC            4...20 mA 4
                                                          OUT1 3
                                         4...20 mA
                                         24 V DC
bar M
                                                                                            6
                                                            2
                                     1                                       5
4.2.1 General information
The unit has an IO-Link communication interface which requires an IO-Link capable module (IO-Link
master).
The IO-Link interface allows direct access to the process and diagnostic data and enables setting of
the parameters of the unit during operation.
You will find further information about IO-Link and all the necessary information about the required IO-
Link hardware and software at:
www.io-link.ifm
                                                                                                                   7
DP2200                                                                                             Analogue threshold display
4.2.2 Application example
4...20 mA 4
                                                             3
                                         4...20 mA                                  Fieldbus
                                         24 V DC                                       6
bar
                                                            2
                                     1                                     5                   7
4.2.3 Functionality
In the IO-Link SIO mode, the device has the same functionality as a stand-alone device. The
measured value is also displayed.
Additionally, the device converts the measured current and transmits the value via IO-Link connection
to the PLC.
8
Analogue threshold display                                                                         DP2200
5 Installation
u Install the device so that the M12 connection parts and the device are protected from mechanical
  stress such as shock and vibration.
u If necessary, fix the device with a mounting clip. Use M4 screw or cable tie for this purpose.
u During installation, ensure that the pollution degree is 2 or better.
        The mounting clip is not supplied with the device. More information about available accessories
        at www.ifm.com.
                                                                                                        9
DP2200                                                                                Analogue threshold display
6 Electrical connection
        The unit must be connected by a qualified electrician.
        Observe the national and international regulations for the installation of electrical equipment.
        Voltage supply according to SELV, PELV.
The circuit is insulated from device surfaces that could be touched with basic insulation according to
IEC 61010-1 (secondary circuit with max. 32 V DC, supplied from the mains circuit up to 300 V of
overvoltage category II).
The external wiring has to be carried out in a way that ensures the required separation from other
circuits.
            CAUTION
            Input current is not limited.
            w No fire protection.
            u Protect circuits.
The threaded connections in the device correspond to the M12 standard. To ensure compliance with
the specified protection rating, only cables that comply with this standard may be used. In the case of
self-assembled cables, the system manufacturer is responsible for the protection rating.
u Use connectors with gold-plated contacts.
u During installation, place the connectors vertically so that the coupling nut will not damage the
  thread.
u Observe the coding of the connectors during installation.
u Tighten the cable sockets according to the torque specifications indicated by the cable
  manufacturer. Maximum permissible tightening torque: 1.3 ± 0.1 Nm
10
Analogue threshold display                                                                   DP2200
6.2 Cable length
•   Without IO-Link communication: 30 m on each side
•   With IO-Link communication: 20 m on the master side
                                                                                                   11
DP2200                                                                                       Analogue threshold display
      1
                                                    2
Button                             Function
[esc]            Escape            Return to the previous menu. Exit parameter setting without saving the new value.
[●]              Enter             Open menu mode.
                                   Selection of the parameter and acknowledgement of a parameter value.
[▼]              Down              Selection of a parameter. Setting a parameter value (scrolling by holding down, incremen-
                                   tally by pressing repeatedly).
[▲]              Up
          To ensure correct operation of the push rings (buttons), do not install or place the unit directly
          on a metal surface.
          For the installation use the mounting clip Ò Installation.
7.2 LEDs
LED                       Colour           Status             Designation
I            OUT1         yellow           on                 Output 1 switched.
Power                     green            on                 Voltage supply OK.
                                                              Device in operating mode.
                                           off                No voltage supply.
                                                              Device switched off.
II           OUT2         yellow           on                 Output 2 switched.
7.3 Display
Colour                                                          Designation
Red/green                                                       7-segment LED display, 4 digits, with colour change
12
Analogue threshold display                                                                                                          DP2200
Input current 1 2 3
                     Process
                                   32764                     -32760                    3600-21000 μA                 32760
                     data
           IO-Link
                     Silent
                     events         nPrb                      UL                                                      OL
                                                                                                                                        13
DP2200                                                                         Analogue threshold display
8 Menu
8.1 General
Irrespective of the operating mode (standard IO mode or IO-Link device) there are two options to set
the parameters of the unit:
•    directly on the device via the menu (Ò Parameter setting)
•    or via an IO-Link tool
Access via an IO-Link tool has a higher priority than parameter setting via the menu.
Parameter cloning and parameter setting backup is possible with an IO-Link tool.
        If the device was locked via IO-Link, it can also only be unlocked via the IO-Link interface:
        Locking / unlocking (Ò / 22).
The scaling parameter [ScAL] only influences the display and not the transferred process data or the
actual switching threshold values.
Via IO-Link, the current value is always transmitted in μA → Representation of the measured current
value (Ò / 13). The switching thresholds can be set in steps of 0.01 mA.
        If a scaling is set, the menu settings of the switching thresholds (SP, rP etc.) are also scaled.
        Via IO-Link, however, the settings continue to be displayed and executed in steps of 0.01 mA
        (resolution 10 bits).
14
Analogue threshold display                                                                                           DP2200
8.2 Menu structure
                               mA                                                                          3
                                              EF         rES        ---
A.trm On OFF
dS1 0.0...50.0
dr1 0.0...50.0
C.ASP -746...9745
C.AEP -366...9366
cFH 4.10...20.00
cFL 4.00...19.90
diS d1 d2 d3 OFF
Lo ---
Hi ---
dAP 0.000...4.000
                                        t
                     1
                     0                      Hno
              OUT1
                     1
                     0                      Hnc
u Select [SP1] and set the value at which output OUT1 switches.
u Select [rP1] and set the value at which output OUT1 switches off.
        [rP1] is always smaller than [SP1]. The device only accepts values which are lower than the
        value for [SP1].
                                                                                                                         15
DP2200                                                                           Analogue threshold display
[rP1] follows the changes of [SP1] and keeps the set hysteresis.
                                   t
                    1
                    0                  Fno
             OUT1
                    1
                    0                  Fnc
        [FL1] is always smaller than [FH1]. The device only accepts values which are lower than the
        value for [FH1].
[FL1] follows the changes of [FH1] and keeps the set hysteresis.
16
Analogue threshold display                                                                                       DP2200
       If a scaling is set via [ScAL], the C.AEP value also has to be adapted accordingly:
       With [ScAL] = [ccc.c] → C.AEP value x 10
       With [ScAL] = [cc.cc] → C.AEP value x 100
       With [ScAL] = [c.ccc] → C.AEP value x 1000
       All displayed current values are interpolated based on a 2-point approximation ([SP1]+[rP1],
       [FH1]+[FL1], [cFH]+[cFL], [Lo]+[Hi]).
       IO-Link process data and parameters are not affected by the scaling.
             ~ 9999                                                   ~ 9999
            C.AEP                      9366                          C.ASP               9745
                            4                 20 [mA]                                4                 20 [mA]
                      3.6                      21                              3.6                      21
            C.ASP               -746                                 C.AEP                      -366
              ~ 999                                                    ~ 999
                                                                                                                     17
DP2200                                                                              Analogue threshold display
rd gn
            OUT1                                                    OUT1
                          gn                                                   rd
4 mA 20 mA 4 mA 20 mA
Fig. 10: Hysteresis function with [r1ou] Fig. 11: Hysteresis function with [G1ou]
rd FH1 gn FH1
              FL1                                                    FL1
                          gn           gn                                      rd              rd
4 mA 20 mA 4 mA 20 mA
Fig. 12: Window function with [r1ou] Fig. 13: Window function with [G1ou]
[r-cF] = red when the measured value is between the values [cFL] and [cFH].
[G-cF] = green when the measured value is between the values [cFL] and [cFH].
18
Analogue threshold display                                                                                  DP2200
rd gn
                           gn        gn                                             rd        rd
                cFL                          cFH                         cFL                          cFH
                      4 mA           20 mA                                     4 mA           20 mA
8.4.11 dAP ─ damping
Damping of the measured analogue value.
Setting also influences the set point, the IO-Link process data and the display.
Value: 0.000...4.000 s (T value: 63 %).
At 0.000 damping is not active.
                                                                                                                19
DP2200                                                                Analogue threshold display
8.5.3 Application-specific tag
Customer-specific application description, max. 32 characters long.
Default value: “ *** ” / can be freely defined by the customer
20
Analogue threshold display                                                                        DP2200
9 Parameter setting
       During parameter setting the unit remains in the operating mode. It continues its monitoring
       functions with the existing parameters until the parameter setting has been completed.
Step                                                                                Button
1      Change from operating mode to parameter setting mode.                        [●]
2      Select the required parameter: [SP1], [dr1], …                               [▲] or [▼]
3      Change to the programming mode of the parameter.                             [●]
4      Select or change the parameter value.                                        [▲] or [▼] > 2 s
5      Acknowledge the set parameter value.                                         [●]
6      Return to the operating mode.                                                [esc]
                                                                                                       21
DP2200                                                                                     Analogue threshold display
Step                                                                                              Display
6      u Press [esc].
       u Press - [▼] or [▲] several times until the current measured value is displayed.
         - or wait for the timeout function (approx. 30 s).
       w The unit has returned to the operating mode.
       w The current value is displayed.
9.3 Notes on programming
9.3.1 Locking / unlocking
The unit can be locked electronically to prevent unauthorised setting. Set parameter values and
settings can be displayed but not changed.
To lock the unit:
u Make sure that the unit is in normal operating mode.
u Press [esc] + [▲] simultaneously for 10 s.
w [Loc] is displayed.
w The unit is locked.
w [Loc] is briefly displayed if you try to change parameter values.
To unlock the unit:
u Press [esc] + [▲] simultaneously for 10 s.
w [uLoc] is displayed.
On delivery the unit is not locked.
       Customer locking
       If [C.Loc] is displayed when an attempt is made to modify a parameter value, an IO-Link
       communication is active (temporary locking).
       Software locking
       If [S.Loc] is displayed, the sensor is permanently locked via software. This locking can only be
       removed using an IO-Link parameter setting software.
9.3.2 Timeout
If no button is pressed for 30 s during parameter setting, the unit returns to the operating mode with
the unchanged value.
22
Analogue threshold display                                                                        DP2200
10 Operation
After power on, the device is in the operating mode (SIO). It carries out its measurement and
evaluation functions and provides output signals according to the set parameters (Ò Menu).
10.1 Functions output 1
OUT1 (connector, pin 4):
•   Digital output (SIO)
•   IO-Link interface
Selectable switching functions:
•   Hysteresis functions, normally open / normally closed: SP1/rP1 ─ set point/reset point OUT1
    (Ò / 15)
•   Window functions, normally open / normally closed: FH1/FL1 ─ min/max switching limits for
    window function (Ò / 16)
OUT1 changes its status if the input signal is above or below the set switching limits. First the switch
point SP1 is set, then the reset point rP1: SP1/rP1 ─ set point/reset point OUT1 (Ò / 15).
       The hysteresis defined remains even if [SP1] is changed again. Changing the parameter [rP1]
       also changes the hysteresis.
The width of the window can be set by means of the difference between FH1 and FL1.
FH1 = upper value
FL1 = lower value
10.2 Functions output 2
OUT2 (connector, pin 2):
•   Analogue output (looping through the analogue input signal)
                                                                                                           23
DP2200                                                                            Analogue threshold display
11 Troubleshooting
                          LED
Display                                    Error                                 Troubleshooting
                I    Power            II
OFF       off       off         off        Supply voltage too low.               Check/correct the supply voltage:
                                                                                 Electrical connection (Ò / 10)
SC1       flashes   any         any        Excessive current at switching out-   Check switching output OUT1 for
                                           put OUT1.                             short circuit or excessive current.
                                                                                 Remove the fault.
C.Loc     any       any         any        Parameter setting via pushbuttons     Wait until parameter setting via
                                           locked due to active IO-Link trans-   IO-Link is finished.
                                           mission.
S.Loc     any       any         any        Parameter setting via pushbuttons     Unlocking only possible via IO-
                                           disabled by software.                 Link interface/IO-Link parameter
                                                                                 setting software.
Loc       any       any         any        Parameter setting via pushbuttons     Unlock pushbuttons:
                                           disabled.                             Locking / unlocking (Ò / 22)
OL        any       on          any        Process value too high (measured      Check connected sensor and cur-
                                           current > 21 mA).                     rent range:
                                                                                 Representation of the measured
UL        any       on          any        Process value too low (measured       current value (Ò / 13)
                                           current < 3.6 mA).
                                                                                 Check the setting for internal or
nPrb      any       on          any        No sensor connected to the ana-       external analogue termination for
                                           logue input.                          OUT2:
                                                                                 A.Trm ─ analogue termination for
                                                                                 OUT2 (Ò / 16)
24
Analogue threshold display                                                                    DP2200
                                                                                                  25
DP2200                                                                     Analogue threshold display
13 Factory settings
Parameter                                               Factory settings     User settings
SP1/FH1                   Set point OUT1                6.00
rP1/FL1                   Reset point OUT1              5.00
A.Trm                     Analogue termination OUT2     On                   • OFF
                                                                             • On
ou1                       Output function OUT1          Hno                  • Hno
                                                                             • Hnc
                                                                             • Fno
                                                                             • Fnc
dS1                       Switching delay OUT1          0.0 s
dr1                       Switch-off delay OUT1         0.0 s
ScAL                      Scaling value                 OFF                  • OFF
                                                                             • cccc
                                                                             • ccc.c
                                                                             • cc.cc
                                                                             • c.ccc
C.ASP                     Customised analogue start     ----
                          point
C.AEP                     Customised analogue end       ----
                          point
C.uni *                   Customer-specific unit        mA
coLr                      Display: colour setting       rEd                  • rEd
                                                                             • grEn
                                                                             • r1ou
                                                                             • G1ou
                                                                             • r-cF
                                                                             • G-cF
cFH                       Colour change: upper limit    20.0
                          value
cFL                       Colour change: lower limit    4.0
                          value
diS                       Display refresh rate          d2 (200 ms)          • OFF
                                                                             • d1 (50 ms)
                                                                             • d2 (200 ms)
                                                                             • d3 (600 ms)
Lo                        Lowest measured input value   ----
Hi                        Highest measured input value ----
dAP                       Damping of the measured an- 0.060 s
                          alogue value                (= 60 ms)
26