MiCOM P14x Feeder Relay Guide
MiCOM P14x Feeder Relay Guide
Feeder Management
                                 Relays
                           T&D
                           Protection & Control
MiCOM P14x Series
Feeder Management Relays
                                                            2
Models available
• P141 Feeder Management Relay
• P142 with autoreclose
• P143 with autoreclose and check
  synchronising
                                                                                                         P141
Application                                                                                              51P        64N
                                                                                                                                                     M
                                                                                                         51N        27
The MiCOM P14x series is suitable                                                                        67P        47
for all applications where                                                                               67N        50BF
overcurrent protection is required.
The integration of many functions                         Figure 2a: Typical parallel transformer application
                                                                 3
Standard earth fault                     Neutral admittance protection           Negative sequence
There are two standard earth fault       Neutral admittance protection is        overcurrent
elements, each with four                 provided for the Polish market for      Negative sequence overcurrent
independent stages.                      earth fault protection. Three single    protection can be set as either non-
                                         stage elements are provided for         directional or directional
• The first element operates from        non-directional overadmittance,         (forward/reverse), and can operate
  measured quantities:                   non-directional/directional             for remote phase-phase and phase-
  • earth fault current which is         overconductance and                     earth faults even with delta-star
    directly measured using a            non-directional/directional             transformers present.
    separate CT                          oversusceptance.
                                                                                 RMS thermal overload
  • residual connection of the           Restricted earth fault                  Thermal characteristics suitable for
    three line CTs
                                         The restricted earth fault protection   cables and transformers are
• The second standard earth fault        may be configured as either high        available providing both alarm and
  element operates from a residual       impedance or low impedance              trip stages. The thermal element may
  current that is derived internally     biased differential.                    be set with either a single time
  from the summation of the three                                                constant characteristic for the
  phase currents.                        Blocked overcurrent logic               protection of cables or dry
All earth fault elements have the        Each stage of overcurrent and earth     transformers, or a dual time constant
same directionality and IDMT             fault protection can be blocked by      characteristic to protect oil filled
characteristics as the phase             an optically isolated input.            transformers. In the event of loss of
overcurrent element.                     This enables overcurrent and earth      auxiliary supply, the thermal state is
                                         fault protection to integrate into a    stored in non-volatile memory.
Both earth fault elements may be
                                         blocked overcurrent busbar
enabled at the same time providing                                               Under/overvoltage
                                         protection scheme.
discriminative directional earth fault
                                                                                 Under/overvoltage protection may
protection and back-up standby
                                         Selective overcurrent logic             be configured to operate from
earth fault protection in the same
                                         Selective overcurrent logic assists     either phase-phase or phase-neutral
device. The directionality of the
                                         with relay co-ordination by allowing    quantities. Two independent stages
earth fault elements is provided by
                                         the time delay settings of the          with definite time elements are
either residual voltage or negative
                                         overcurrent elements to be              available, one of the stages can
sequence voltage.
                                         temporarily modified by                 also be configured to an inverse
Sensitive earth fault                    energisation of an optically isolated   characteristic.
                                         input. This is available using
A core balance CT should be used                                                 Neutral
                                         programmable scheme logic.
to drive the sensitive earth fault                                               displacement/residual
function. The directionality of the                                              overvoltage
                                         Cold load pick-up logic
sensitive earth fault elements is
                                         Cold load pick-up temporarily raises    Residual overvoltage protection is
provided by the residual voltage.
                                         the overcurrent settings following      available for detecting earth faults
Wattmetric                               closure of the circuit breaker,         in high impedance earthed or
                                         allowing the protection settings to     isolated systems. The neutral voltage
As an alternative to the directional
                                         be set closer to the load profile.      is derived from the three phase
wattmetric characteristic a
                                                                                 voltage inputs. Two independent
directional I cos (φ) characteristic
                                         Voltage controlled                      measuring elements with definite
can be used for Petersen coil earth
                                         overcurrent                             time characteristics are available,
fault protection using the sensitive
                                         Voltage controlled overcurrent          one of the elements can also be
earth fault input. This protection
                                         provides back-up protection for         configured to have an inverse
provides discrimination as faulted
                                         remote phase faults whilst              characteristic.
feeders will have a large
component of residual current whilst     remaining insensitive to load
                                         conditions.                             Negative sequence
healthy feeders will have a small                                                overvoltage
value.
                                                                                 Negative sequence overvoltage
A directional I sin (φ) characteristic
                                                                                 protection provides either a tripping
is also available for protection of
                                                                                 or an interlocking function, upon
insulated feeders.
                                                                                 detection of unbalanced supply
                                                                                 voltages
                                                             4
Under/overfrequency                     Autoreclose with check                           the scheme logic signals and thus
                                        synchronising                                    avoid unnecessary signal
Two independent stages of
                                        The P142 provides three pole multi-              processing.
overfrequency and four of
underfrequency are provided.            shot autoreclose. The user may                   The programmable scheme logic is
Each stage functions as a definite      select a single, two, three or four              configured using the graphical
time element.                           shot autoreclose cycle, with                     MiCOM S1 PC based support
                                        independently settable dead times                software, as illustrated in Figure 3.
Broken conductor                        and reclaim time. Autoreclose can
                                        be initiated from the internal                   The required logic is drawn as
The broken conductor protection                                                          shown and is then downloaded
detects unbalanced conditions           protection elements or from external
                                        protection via an opto input.                    directly into the relay. The logic
caused by broken conductors, mal-                                                        may also be uploaded from the
operation of single phase switchgear    More advanced features of the                    relay and then modified using
or by single phasing conditions.        P143 include check synchronising,                MiCOM S1 support software.
                                        live line working and sequence
Supervisory functions                   co-ordination (co-ordination with                Independent protection
                                        downstream reclosing equipment).                 settings groups
Circuit breaker failure
                                                                                         The settings are divided into two
protection                              Programmable scheme logic
                                                                                         categories; protection settings, and
Two stage circuit breaker failure       Programmable scheme logic allows                 control and support settings. Four
protection may be used for tripping     the user to customise the protection             setting groups are provided for the
upstream circuit breakers and           and control functions. It is also used           protection settings to allow for
retripping of the local circuit         to programme the functionality of                different operating conditions and
breaker if required. The circuit        the optically isolated inputs, relay             adaptive relaying. All settings are
breaker failure logic may also be       outputs and LED indications.                     stored in E2PROM.
initiated externally from other
                                        The programmable scheme logic
protection devices if required.                                                          Control inputs
                                        comprises gate logic and general
                                        purpose timers. The gate logic                   The control inputs allow the user to
Voltage transformer supervision
                                        includes OR, AND and majority                    manualy change the status of DDB
Voltage transformer supervision is      gate functions, with the ability to              signals 800 to 831. These signals
provided to detect loss of one, two     invert the inputs and outputs, and               can be assigned to provide user
or three VT signals, providing          provide feedback. The system is                  defined control functions.
indication and inhibition of voltage    optimised to evaluate changes to
dependent protection elements.
An optically isolated input may also
be configured to initiate the voltage
transformer supervision alarm and
blocking when used with MCBs or
other external forms of voltage
transformer supervision.
Current transformer
supervision
Current transformer supervision is
provided to detect loss of phase CT
signals and inhibit the operation of
current dependent protection
elements.
Control
Circuit breaker control
Circuit breaker control is available
from the front panel user interface,
optically isolated inputs and
remotely via the substation
communications.                            Figure 3: Programmable scheme logic editor (MiCOM S1)
                                                              5
Measurement and                           Integrated values                         Disturbance records
recording facilities                      Wh                 VArh                   The internal disturbance recorder
                                                                                    has 8 analogue channels, 32
The P14x series is capable of             Peak, average and rolling demand:
                                                                                    digital and 1 time channel. Data is
measuring and storing the values of                                                 sampled 12 times a cycle and
                                          •   Ia Ib Ic
a wide range of quantities.                                                         typically 20 disturbance records,
All events, fault and disturbance         • W VAr
                                                                                    each of up to 10.5 seconds
records are time tagged to a              The P143 provides an additional           duration are stored in battery
resolution of 1ms using an internal       voltage input for synchronisation         backed memory. All channels and
real time clock. An optional IRIG-B       and additional measurements:              the trigger source are user
port is also provided for accurate                                                  configurable. Disturbance records
time synchronisation.                     • Check synchronising voltage
                                                                                    can be extracted from the relay via
A lithium battery provides a back-        • Slip frequency                          the remote communications and
up for the real time clock and all                                                  saved in the COMTRADE format.
records in the event of supply            Post fault analysis                       These records may be examined
failure. This battery is supervised                                                 using MiCOM S1 or any suitable
and easily replaced from the front        Fault location                            software program.
of the relay.                             A fault location algorithm provides
                                          distance to fault in miles, kilometres,   Plant supervision
Measurements                              ohms or percentage of line length.
The measurements provided, which                                                    Trip circuit supervision
may be viewed in primary or               Event records                             Supervision of the trip circuit in both
secondary values, can be accessed         Up to 250 time-tagged event               circuit breaker open and closed
by the back-lit liquid crystal display,   records are stored in battery             states can be realised using the
or the communications ports. Phase        backed memory, and can be                 optically isolated inputs and
notation is user definable using the      extracted using the communication         programmable scheme logic.
MiCOM S1 text editor.                     ports or viewed on the front panel
                                          display.                                  Circuit breaker state
Instantaneous measurements                                                          monitoring
Phase voltages       Van Vbn Vcn          Fault records                             An alarm will be generated if there
Line voltages        Vab Vbc Vca          Records of the last 5 faults are          is a discrepancy between the open
                                          stored in battery backed memory.          and closed auxiliary contacts of the
Neutral voltage      Vn                   The information provided in the           circuit breaker.
Phase current        Ia Ib Ic             fault record includes:
                                                                                    Circuit breaker condition
Neutral currents     In ISEF              • Indication of faulted phase             monitoring
Sequence currents and voltages            • Protection operation                    The circuit breaker condition
Ratio of   I2/I1                          • Active setting group                    monitoring features include:
                                                              6
Local and remote                       Local communications                       Hardware description
communications                         The front serial communications port
                                                                                  All models within the MiCOM P14x
                                       has been designed for use with
Two communication ports are                                                       series include:
                                       MiCOM S1, which fully supports
available; a rear port providing
                                       functions within the relay by              • A back-lit liquid crystal display
remote communications and a front
                                       providing the ability to programme
port providing local                                                              • 12 LEDs
                                       the settings off-line, configure the
communications.                                                                   • An optional IRIG-B port
                                       programmable scheme logic,
                                       extract and view event, disturbance        • An RS232 port
Remote communications
                                       and fault records, view the
The remote communications are                                                     • An RS485 port
                                       measurement information
based on RS485 voltage levels.         dynamically and perform control            • A download/monitor port
Any of the protocols listed below      functions. PAS&T support software
can be chosen at the time of                                                      • A battery (supervised)
                                       can also be used with the local
ordering.                              communications port.                       • N/O and N/C watchdog
                                                                                    contacts
Courier/K-Bus
                                       Diagnostics                                • Supervised +48V field voltage
The Courier language is a protocol
which has been developed               Automatic tests performed including        • 1A/5A dual rated CTs
specifically for the purpose of        power-on diagnostics and                   The hardware variations between
developing generic PC programmes       continuous self-monitoring ensure a        the MiCOM P14x series models
that will, without modification,       high degree of reliability. The results    are:
communicate with any device using      of the self-test functions are stored in
the Courier language.                  battery backed memory.                                       P141 P142 P143
                                       Test features available on the user        100 - 120V or
Modbus                                                                                               3       3     4
                                       interface provide examination of           380 - 480V VTs
Modbus is a master/slave protocol,     input quantities, states of the digital    Optically
                                                                                                     8       8     16
whereby the master must have           inputs and relay outputs. A local          isolated inputs
knowledge of the slave’s databases     monitor port providing digital             Relay outputs     3N/O   3N/O 6N/O
and addresses. The Modbus              outputs, selected from a prescribed                          4C/O   4C/O 8C/O
implementation supported by the        list of signals, including the status of
MiCOM P14x series is RTU mode.         protection elements, may be used in        Expansion cards are available to
                                       conjunction with test equipment.           allow further inputs and outputs for
IEC 60870-5-103                        These test signals can also be             the P142 and P143 (see page 16).
The relay is compliant with the        viewed using the Courier and               N/O – normally open
transmission protocol defined by the   Modbus communications ports and            C/O – change over
specification IEC 60870-5-103.         the front panel user interface.
                                                                                  The allocation of the optically
The standarised messages based on
                                                                                  isolated inputs, relay outputs and 8
the VDEW communication protocol
                                                                                  of the LEDs are preconfigured as a
are supported.
                                                                                  default, but may be programmed by
DNP 3.0                                                                           the user.
                                                                                  The optically isolated inputs are
The DNP 3.0 protocol is defined
                                                                                  independent and may be powered
and administered by the DNP User
                                                                                  from the +48V field voltage.
Group. The relay operates as a
                                                                                  The relay outputs may be
DNP 3.0 slave and supports subset
                                                                                  configured as latching or self reset.
level 2 of the protocol plus some of
                                                                                  All CT connections have integral
the features from level 3.
                                                                                  shorting.
                                                                                  A system overview of the MiCOM
                                                                                  P143 is shown in Figure 4.
                                                            7
                                                                   C23                                                                                               J11
                                                                                                                                                                          Relay failed
                             N
                     C
                                         c
                                                         V synch                                                                                                     J12
                                                                                                                                               Watchdog
                                                                                                    P143
                                         b
                                                          check                                                                                                      J13
                                                                   C24                                                                                                    Relay healthy
                                         a
                                                                                                                                                                     J14
                                                                                                                                                                         + J7
                                                    C1              5A                                                                                                                48V field voltage
                                                                                                                                                                                J9
                                              IA    C2
                                                                                                                       kA, kV, Hz
                                                    C3                       50P   50N    51P        1   4    0 0      kW, kVA, kVArs                                      + J8
                                                                    1A                                                                                                                48V field voltage
                                                                                                                       kWh, kVArh                                               J10
                                                    C4              5A
                                                                                                                       Sequence components                           + J2
                                              IB    C5                       51N   64     37P       Measurements       Thermal state                                             Auxiliary voltage
                                                    C6
                                                                    1A                                                                                                    J1
                      See note 2                    C7              5A       37N   46     49                         IN > 1       Start   ON
                                              IC    C8                                             250                                            See note 4
                                                                                                                     00:12:00     01/01/99
                                                    C9
                                                                                                   Event
                                                                                                                     Trip A B C           ON           IRIG-B
                                                                    1A       79    50BF            records
                                                   C10              5A                                               00:12:01     01/01/99
                                             IN    C11                                                                                                 RS232                               MiCOM S1
                                                   C12
                                                                             BC    CTS
                                                                                                                                                                     J17
                                                                    1A
                                                                                                   20                                                  RS485                               Courier
                                                   C13              5A                                                                                               J18
                                        IN                                                         Disturbance                                                                             Modbus
                                      Sensitive C14                                                                                                                                        IEC60870-5-103
                                                   C15
                                                                                                   records                                                    LEDs
                                                                    1A
                                                                             59     67    67W
                                                                See note 1                                                                                                User programmable
                                                                See note 3                          5                  Fault A-B-C 15ms
                                                          C19                47     27    VTS       Fault              Ia = 1000 A
                                                                                                    reports            Ib = 1000 A
                                                   VA                              81U    81O                          Ic = 1000 A
                                                                             51V
                                                          C20                                                                                                        H1
                                                                                                                                                        RL1
                                                                                                                                                                     H2
                                                                                                                                                                               In>/ISEF> start
                                                   VB                                                                               1                   RL2
                                                                                                                                                                     H3
                                                                                                                                                                               I> start
                                                          C21                                                            &          1     &                          H4
                                                                                                                                                                     H5
                                                                                                                                                        RL3                    Protection trip
                                                                                                    Programmable scheme logic                                        H6
                            N
                     C
                                                   VC                                                                                                                H7
                     B
                                                          C22
                                                                                                                                                        RL4
                                                                                                                                                                     H8        General alarm
                                                                                                                                                                     H9                              User
                     A
          52
                                                                                                                                                                     H13
                                                                                                                                                        RL6
                                                                                                                                                                     H14       Control CB close
                                                                                                                                                                     H15
                                               D2                                                                                                                    H16
                            Setting group                                                                                                               RL7          H17       Control CB trip
                                               D1                                                                                                                    H18
                                               D4
                            Setting group
                                               D3
                                               D6
                           Block In1>3&4       D5
                                               D8
                             Block I>3&4
                                               D7
                                               D10
                                 Reset LEDs
                                               D9
                                               D12
                                                                                                                                                                     G1
                              External trip                                                                                                             RL8                    Any start
                                               D11                                                                                                                   G2
                                               D14                                                                                                                   G3
                                       52A                                                                                                              RL9                    A/R successful
                                               D13                                                                                                                   G4
                                               D16                                                                                                                   G5
                                       52B                                                                                                              RL10
                                                                                                                                                                     G6
                                                                                                                                                                               Non auto mode
                                               D15
                                                                                                                                                                     G7
                                               F2                                                                                                       RL11         G8        A/R in progress       User
                         Select auto mode                                                                                                                            G9
                                                                                                                                                                                                     programmable
                                               F1
                                                                                                                                                                     G10
                                               F4
                                                                                                                                                                     G11       A/R prot. lockout     See note 2
                  Select telecontrol mode                                                                                                               RL12
                                               F3                                                                                                                    G12
                                               F6                                                                                                                    G13
                    Select live line mode                                                                                                                            G14       A/R in service
                                               F5                                                                                                       RL13
                                                                                                                                                                     G15
                                               F8
                                CB healthy                                                                                                                           G16
                                               F7                                                                                                                    G17       Live line mode
                                               F10                                                                                                      RL14         G18
                                 Block A/R
                                               F9
                                               F12
                             Reset lockout     F11
                                               F14
           User                                F13
           programmable                        F16
           See note 2                          F15
ANSI Numbers
        Note 1:    All CT connectors have integral shorting. These contacts are made before the internal CT circuits are disconnected.
        Note 2:    Additional hardware for P143 only.
        Note 3:    5A CT connections shown, 1A CT connections available on the terminal blocks.
        Note 4:    The bridge rectifier is not present on the 24 – 48V dc version.
                                                                                                         8
                                                                               1
                                                                                              4
                             2
                                                                                          8
                          7
User interface
The front panel user interface      (6)      An upper cover identifying the        The user interface and menu text
comprises:                                   product name. The cover may           are available in English, French,
                                             be raised to provide access to        German and Spanish as standard.
(1)   A 2 x 16 character back-lit            the product model number,             Labels supplied with the device
      liquid crystal display.                serial number and ratings.            allow customised descriptions of the
(2)   Four fixed function LEDs.                                                    LEDs. A user selectable default
                                    (7)      A lower cover concealing the
                                                                                   display provides measurement
(3)   Eight user programmable                front RS232 port,
                                                                                   information, time/date, protection
      LEDs.                                  download/monitor port and
                                                                                   functions and plant reference
                                             battery compartment. The
(4)   Menu navigation and data                                                     information. The ability to customise
                                             front of the cover can display
      entry keys.                                                                  the menu text and alarm
                                             the name of the product, or
                                                                                   descriptions is also supported.
(5)   “READ”       and “CLEAR”               any user defined name.
      keys for viewing and          (8)      Facility for fitting a security
      acknowledging alarms.                  lead seal.
                                                                                    Password protection
                                                                                    Password protection may be
                                                                                    independently applied to the
                                                                                    front user interface, front
                                                                                    communications port and rear
                                                                                    communications port. Two levels
                                                                                    of password protection are
                                                                                    available providing access to
                                                                                    the controls and settings
                                                                                    respectively.
                                                                9
Protection setting ranges
                                                      IEC/UK curves                                                                  IEEE/US curves
                                      Operating
                                                                                                                             10
                                      time (s)
Standard earth fault
                                                                                                                        Operating
                                                                                                                        time (s)
IDMT/definite time                           10
                                                                                           120
  0 to 20W      (100 – 120V)             UK Long time inverse       t = TMS x                                        US CO8 Inverse
                                                                     I DIFF
                                                                                                Operate
                                                                                                                                                              K1 0% to 20%
                                                                                                                K2                                            K2 0% to 150%
                                                                                                                                                              I s1          0.08 to 1.0I n
                                                                                                                           Restrain                           I s2          0.10 to 1.5I n
                                                                                 K1
                                                                      I s1
                                                                                       I s2                                         I BIAS
                                                                    10
Undercurrent                                   Thermal trip current setting         Autoreclose and check
                                                          0.08 to 3.2In             synchronising (where
Phase and neutral
                                                                                    appropriate
  0.02 to 3.2In                              Undervoltage
                                                                                    Main shots          1 to 4
  ISEF 0.001 to 0.8In                        Voltage settings, Vs
                                                                                    Dead times (1, 2) 0.01 to 300s
Voltage controlled                             10 to 120V      (100 – 120V)
                                                                                    Dead times (3, 4) 0.01 to 9999s
overcurrent                                    40 to 480V      (380 – 480V)
                                                                                    Check
Voltage control threshold                    Time settings
                                                                                    synchronising       5° to 90°
  20 to 120V (100 – 120V)                      Definite time 0 to 100s              Slip frequency      0.02 to 1.00Hz
  80 to 480V (380 – 480V)
                                               IDMT            t = TMS/(1 – V/Vs)
Overcurrent sensitivity factor                                                      Neutral admittance
                                               TMS             0.5 to 100
  0.25 to 1.0                                                                       Voltage threshold Vn
                                             Overvoltage
Negative sequence                                                                     1 to 40V      (100 – 120V)
                                             Voltage settings, Vs
overcurrent                                                                           4 to 160V (380 – 480V)
Threshold                    0.08 to 4.0In     60 to 185V      (100 – 120V)         Correction angle
Definite time                0 to 100s         240 to 680V (380 – 480V)
                                                                                      –30° to +30°
                                             Time settings
Thermal overload                                                                    Overadmittance settings
Thermal alarm                50% to 100%       Definite time   0 to 100s            YN>/Overconductance settings
                                                                                    GN>/Oversusceptance settings
                                               IDMT            t = TMS/(V/Vs – 1)
Single time constant                                                                BN>
characteristic                                 TMS             0.5 to 100
                                                                                      25µs to 2.5ms (SEF input)
                         2            2      Residual overvoltage
                     (I – kI     FLC)                                                 250µs to 25ms (EF input)
    t = -τ loge I2 – I             2         Voltage settings, Vs
                      P                                                             Time settings (definite time)
                                               1 to 80V        (100 – 120V)
Where:                                                                                Operating time 0.05 to 100s
                                               4 to 320V       (380 – 480V)
  t=        time to trip, following                                                   Reset time 0 to 100s
                                             Time settings
            application of the
                                                                                    Accuracy/operating times
            overload current, I                Definite time   0 to 100s            (typically)
  τ=        plant heating and cooling          IDMT            t = TMS/(V/Vs – 1)   Phase and earth fault ±5% or 50ms
            time constant (1 to 200
            minutes)                           TMS             0.5 to 100           Wattmetric             ±5% or 40ms
  I=        largest phase current            Negative sequence                      Restricted earth fault ±5% or 45ms
                                             overvoltage
  IFLC = thermal trip setting                                                       Negative sequence
                                             Voltage settings, Vs                     overcurrent     ±2% or 60ms
  k=        1.05 constant
                                               1 to 110V       (100 – 120V)         Undervoltage           ±2% or 50ms
  IP =      Steady state pre-load
            current                            4 to 440V       (380 – 480V)         Overvoltage            ±2% or 50ms
                                             Time settings
Dual time constant                                                                  Measurements
characteristic                                 Definite time   0 to 100s            Voltage and amperes       <1%
                  –t            –t
         0.4    e τ1 +   0.6   eτ2           Under/overfrequency                      0.2 – 3.0In     ±0.5%
             I2 – (k.IFLC)2                  Frequency settings     45 to 65Hz        0.2 – 2.0In     ±0.5%
         =
               I2 – IP2                      Definite time          0 to 100s       Derived value     <2%
Where:
                                             Broken conductor
  τ1, τ2 = plant heating and
                                             I2/I1             0.2 to 1.0
           cooling time constants
           (1 to 200 minutes)                Definite time     0 to 100s
                                                                  11
Technical data                         Thermal withstand                     • Watchdog contact ratings
                                                            12
IRIG-B Port                             Three positive and three negative       • Radiated immunity
                                        impulses of 5kV peak, 1.2/50µs,           C37.90.2: 1995
• Carrier signal
                                        0.5J between all terminals and
  Amplitude modulated                                                             25MHz to 1000MHz, zero and
                                        all terminals and case earth.
                                                                                  100% square wave modulated.
• Cable type                          Electrical environment                      Field strength of 35V/m.
  50 ohm coaxial cable                • DC supply interruption                  • Electrostatic discharge
• Connection       BNC                  IEC 60255-11: 1979                        IEC 60255-22-2: 1996 Class 4
• Isolation        SELV                 The unit will withstand a 20ms            15kV discharge in air to user
                                        interruption in the auxiliary             interface, display and exposed
Internal battery
                                        supply, in its quiescent state,           metal work.
                   1/
Battery type:        2AA,   3.6V        without de-energising.                    IEC 60255-22-2: 1996 Class 3
Download/monitor port                 • AC ripple on dc supply                    8kV discharge in air to all
This is a 25 pin D-type female          IEC 60255-11: 1979                        communication ports. 6kV point
connector located on the front user                                               contact discharge to any part of
                                        The unit will withstand a 12% ac          the front of the product.
interface and is specifically
                                        ripple on the dc supply.
designed for test purposes and                                                  • Surge immunity
software download.                    • AC voltage dips and short
                                        interruptions                             IEC 61000-4-5: 1995 Level 4
• Isolation        ELV                                                            4kV peak, 1.2/50µs between all
                                        IEC 61000-4-11: 1994
• Local access                                                                    groups and case earth.
                                        20ms interruptions/dips.
High voltage withstand                                                            2kV peak, 1.2/50µs between
                                      • High frequency disturbance                terminals of each group.
This is not applicable to the RS232
                                        IEC 60255-22-1: 1988 Class III            This is not applicable to the
and download/monitor ports.
                                        At 1MHz, for 2s with 200                  RS232 and download/monitor
• Dielectric withstand                  source impedance:                         ports.
  IEC 60255-5: 1977                     2.5kV peak between                      • EMC compliance
  2kV rms for 1 minute between all      independent circuits and                          89/336/EEC
  case terminals connected              independent circuits and case
  together and the case earth.          earth.                                    Compliance to the European
                                                                                  Commission Directive on EMC is
  2kV rms for 1 minute between all      1.0kV peak across terminals of            claimed via the Technical
  terminals of independent circuits     the same circuit.                         Construction File route.
  with terminals on each              This is not applicable to the RS232 and
  independent circuit connected       download/monitor ports.
                                                                                  Generic Standards were used to
  together.                                                                       establish conformity:
                                      • Fast transient disturbance                EN50081-2: 1994
  ANSI/IEEE C37.90-1989
  (r1994)                               IEC 60255-22-4 : 1992 Class IV            EN50082-2: 1995
  1kV rms for 1 minute across the       4kV, 2.5kHz applied directly to         • Product safety
  open contacts of the watchdog         auxiliary supply
                                                                                          73/23/EEC
  relays.                               4kV, 2.5kHz applied to all
                                        inputs.                                   Compliance with European
  1kV rms for 1 minute across
                                                                                  Commission Low Voltage
  open contacts of changeover           This is not applicable to the
                                        RS232 and download/monitor                Directive.
  output relays.
                                        ports.                                    Compliance is demonstrated by
  1.5kV rms for 1 minute across
                                      • Surge withstand capability                reference to generic safety
  open contacts of normally open
                                        IEEE/ANSI C37.90.1 (1989)                 standards:
  output relays.
                                        4kV fast transient and 2.5kV              EN61010-1: 1993/A2: 1995
• High voltage impulse
                                        oscillatory applied directly across
                                                                                  EN60950: 1992/A11: 1997
  IEC 60255-5: 1977                     each output contact, optically
                                        isolated input and power supply
                                        circuit.
                                                          13
Atmospheric environment             Additional information
• Temperature                       MiCOM P14x Series
  IEC 60255-6:1988                  Technical Guide                        TG8612
  Operating –25°C to +55°C          Operation Guide                        OG8612
  Storage and transit –25°C to      Courier Communications                 R4113
  +70°C
                                    MiCOM S1 User Manual R8610
  IEC 60068-2-1: 1990/A2:1994
                                    Midos Parts Catalogue
  Cold
                                    and Assembly Instructions R7012
  IEC 60068-2-2: 1974/A2:1994
                                    PAS&T                                  R8514
  Dry heat
• Humidity
                                    Case
  IEC 60068-2-3: 1969
                                    The MiCOM P14x series relays are housed in a specially designed case
  56 days at 93% RH and +40°C
                                    providing a high density of functionality within the product, a customisable
• Enclosure protection              user interface, additional functions and information concealed by upper and
  IEC 60529: 1989                   lower covers. Physical protection of the front panel user interface and
                                    prevention of casual access is provided by an optional transparent front
  IP52 Protection (front panel)     cover, which can be fitted or omitted according to choice, since the front
  against dust and dripping water   panel has been designed to IP52 protection against dust and water. The
  at 15° to the vertical.
                                    case is suitable for either rack or panel mounting as shown in
Mechanical environment              Figures 7 and 8.
• Vibration
  IEC 60255-21-1: 1996
                                                                         8 off holes Dia. 3.4
  Response Class 2                     23.30           155.40
                                                 A B                BA
  Endurance Class 2                                                                                                 Sealing strip
                                                                                       177.0
                                       159.00                            168.00         (4U)
• Shock and bump
                                                 AB                 BA
  IEC 60255-21-2: 1995
                                       10.35            181.30                                            483 (19” rack)
  Shock response Class 2                                202.00
                                                                                   Flush mounting panel
  Shock withstand Class 1                      A = Clearance holes
                                                                                   Panel cut-out detail
                                               B = Mounting holes
  Bump Class 1
                                                       200.00                     Note: If mounting plate
• Seismic                                                                         is required use flush
                                                                                  mounting cut out dimensions
  IEC 60255-21-3: 1995 Class 2
                                                                                                           Side view
                                                       206.00                             30.00
                                                              14
                              116.55     142.45                                                                              Sealing
                23.25                                  12 off holes Dia. 3.4                                                 strip
                         AB            A B        BA
                                                       168.00
                                                                               177.0
                159.00                                                          (4U)
AB B A BA
All dimensions in mm
                                                                                           Side view
                                  309.60                                  30.00
                                                                               15
Information required with order
Version
Standard version                                                                       1
With integral autoreclose                                                              2
With integral autoreclose and check synchronising                                      3
Vx aux rating
24 – 48V dc                                                                                1
48 – 110V dc (30 – 100V ac)                                                                2
110 – 250V dc (100 – 240V ac)                                                              3
Vn rating
100 – 120V ac                                                                                  1
380 – 480V ac                                                                                  2
Hardware options
Standard version                                                                                   1
IRIG-B input                                                                                       2
Fibre optic converter (IEC 60870-5-103)                                                            3
IRIG-B input & fibre optic converter (IEC 60870-5-103)                                             4
Protocol options
K-Bus                                                                                                      1
Modbus                                                                                                     2
IEC 60870-5-103 (VDEW)                                                                                     3
DNP 3.0                                                                                                    4
Original hardware/software                                                                                            A
48V opto inputs only
Lower contact rating
No I/O expansion available
Technical guide reference TG8612C
                                                                  16
Accessories                                                                               Please quote on order
Push-on tab: 4.8 x 0.8mm converter for 18 way medium duty terminal block (20 per order) ZA0005 104
2 metre long, 3-wire serial communications cable kit for use with:
                             PC to KITZ or                                                     ZA0012 001
                             PC to MiCOM relay via front port
                                                                    17
ALSTOM T&D Protection & Control Business contact addresses
                                                                    18
Notes:
Your contact:
    19
                                                                                                                                                                                            © 2002 ALSTOM - 040201 Clément imprimeurs
                                                                                                                                                                                          Publication: P14x/EN BR/Fa
T R A N S M I S S I O N & D I S T R I B U T I O N Protection & Control, Le Sextant, 3 avenue André Malraux, 92300 Levallois-Perret. France
   Tel: +33 (0) 141 49 20 00 Fax: +33 (0) 1 41 49 24 85 Email: protection.control@tde.alstom.com Internet: www.tde.alstom.com
                                           Contact Centre on line 24 hours a day : +44 (0) 1785 25 00 70
                                 ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and service marks of ALSTOM.
                      MiCOM is a registered trademark of ALSTOM. Other names mentioned, registered or not, are the property of their respective companies.
   Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up to date literature, this
brochure should only be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advice on the application of any product
                           referred to in it. We cannot be held responsible for any reliance on any decisions taken on its contents without specific advice.