Wood Connections
Wood Connections
Connections
7.1 General
The objectives of connection design are
Toenail 3 8d
Header and stringer (band) joists to sill
Toenail 8d 16 inches on center
Board sheathing
Face-nail 2 or 3 8d To each joist
Toenail 4 8d
Sole plate to joist or blocking
Face-nail 16d 16 inches on center
Face-nail,
Doubled studs
10d 16 inches on center
stagger
End stud of interior wall to exterior wall
Face-nail
structural panel wall sheathing on center at intermediate framing
Minimum 1/2-inch-thick (or greater) wood 8d at 6 inches on center at panel edges; 12 inches
Face-nail
structural panel wall/roof/floor sheathing on center at intermediate framing
Source: Based on current industry practice and other sources (ICC,1998, NAHB, 1994; NAHB, 1982).
Note:
1
In practice, types of nails include common, sinker, box, or pneumatic; refer to Section 7.2 for descriptions of these fasteners. Some recent
codes have specified that common nails are to be used in all cases. However, certain connections may not necessarily require su ch a nail or
may actually be weakened by use of a nail that has too large a diameter (i.e., causing splitting of wood members). Other codes allow box
nails to be used in most or all cases. NER-272 guidelines for pneumatic fasteners should be consulted (NES, Inc., 1997). However, the NER-
272 guidelines are based on simple, conservative conversions of various code nail schedules, such as above, using the assumption that the
required performance is defined by a common nail in all applications. In short, there is a general state of confusion regarding appropriate
nailing requirements for the multitude of connections and related purposes in conventional residential construction.
7.2.1 Nails
Several characteristics distinguish one nail from another. Figure 7.1
depicts key nail features for a few types of nails that are essential to wood-framed
design and construction. This section discusses some of a nail’s characteristics
relative to structural design; the reader is referred to Standard Terminology of
Nails for Use with Wood and Wood-Base Materials (ASTM F547) and Standard
Specification for Driven Fasteners: Nails, Spikes, and Staples (ASTM F 1667) for
additional information (ASTM, 1990; ASTM, 1995).
The most common nail types used in residential wood construction follow:
• Common nails are bright, plain-shank nails with a flat head and
diamond point. The diameter of a common nail is larger than that of
sinkers and box nails of the same length. Common nails are used
primarily for rough framing.
• Sinker nails are bright or coated slender nails with a sinker head and
diamond point. The diameter of the head is smaller than that of a
common nail with the same designation. Sinker nails are used
primarily for rough framing and applications where lumber splitting
may be a concern.
• Box nails are bright, coated, or galvanized nails with a flat head and
diamond point. They are made of lighter-gauge wire than common
nails and sinkers and are commonly used for toenailing and many
other light framing connections where splitting of lumber is a concern.
• Cooler nails are generally similar to the nails above, but with slightly
thinner shanks. They are commonly supplied with ring shanks (i.e.,
annular threads) as a drywall nail.
• Power-driven nails (and staples) are produced by a variety of
manufacturers for several types of power-driven fasteners. Pneumatic-
driven nails and staples are the most popular power-driven fasteners in
residential construction. Nails are available in a variety of diameters,
lengths, and head styles. The shanks are generally cement-coated and
are available with deformed shanks for added capacity. Staples are
also available in a variety of wire diameters, crown widths, and leg
lengths. Refer to NER-272 for additional information and design data
(NES, Inc., 1997).
Nail lengths and weights are denoted by the penny weight, which is
indicated by d. Given the standardization of common nails, sinkers, and cooler
nails, the penny weight also denotes a nail’s head and shank diameter. For other
nail types, sizes are based on the nail’s length and diameter. Table 7.2 arrays
dimensions for the nails discussed above. The nail length and diameter are key
factors in determining the strength of nailed connections in wood framing. The
steel yield strength of the nail may also be important for certain shear
connections, yet such information is rarely available for a “standard” lot of nails.
Notes
1
Based on ASTM F 1667 (ASTM, 1995).
2
Based on a survey of pneumatic fastener manufacturer data and NER-272 (NES, Inc., 1997).
There are many types of nail heads, although three types are most
commonly used in residential wood framing.
• The flat nail head is the most common head. It is flat and circular, and
its top and bearing surfaces are parallel but with slightly rounded
edges.
• The sinker nail head is slightly smaller in diameter than the flat nail
head. It also has a flat top surface; however, the bearing surface of the
nail head is angled, allowing the head to be slightly countersunk.
• Pneumatic nail heads are available in the above types; however, other
head types such as a half-round or D-shaped heads are also common.
(i.e., ring shank), helical, or longitudinal deformations rolled onto the shank,
creating ridges and depressions. Flutes are helical or vertical deformations rolled
onto the shank. Threaded nails are most often used to connect wood to wood
while fluted nails are used to connect wood to concrete (i.e., sill plate to concrete
slab or furring strip to concrete or masonry). Shank diameter and surface
condition both affect a nail’s capacity.
The nail tip, as illustrated in Figure 7.1, is the end of the shank–usually
tapered–that is formed during manufacturing to expedite nail driving into a given
material. Among the many types of nail points, the diamond point is most
commonly used in residential wood construction. The diamond point is a
symmetrical point with four approximately equal beveled sides that form a
pyramid shape. A cut point used for concrete cut nails describes a blunt point. The
point type can affect nail drivability, lumber splitting, and strength characteristics.
The material used to manufacture nails may be steel, stainless steel, heat-
treated steel, aluminum, or copper, although the most commonly used materials
are steel, stainless steel, and heat-treated steel. Steel nails are typically formed
from basic steel wire. Stainless steel nails are often recommended in exposed
construction near the coast or for certain applications such as cedar siding to
prevent staining. Stainless steel nails are also recommended for permanent wood
foundations. Heat-treated steel includes annealed, case-hardened, or hardened
nails that can be driven into particularly hard materials such as extremely dense
wood or concrete.
Various nail coatings provide corrosion resistance, increased pullout
resistance, or ease of driving. Some of the more common coatings in residential
wood construction are described below.
7.2.2 Bolts
Bolts are often used for “heavy” connections and to secure wood to other
materials such as steel or concrete. In many construction applications, however,
special power-driven fasteners are used in place of bolts. Refer to Figure 7.2 for
an illustration of some typical bolt types and connections for residential use.
• Epoxy-set anchors are anchor bolts that are drilled and installed
with epoxy adhesives into concrete after the concrete has cured and
sometimes after the framing is complete so that the required anchor
location is obvious.
While wood connections are generally responsible for the complex, non-
linear behavior of wood structural systems, the design procedures outlined in the
NDS are straightforward. The NDS connection values are generally conservative
from a structural safety standpoint. Further, the NDS’s basic or tabulated design
values are associated with tests of single fasteners in standardized conditions. As
a result, the NDS provides several adjustments to account for various factors that
alter the performance of a connection; in particular, the performance of wood
connections is highly dependent on the species (i.e., density or specific gravity) of
wood. Table 7.3 provides the specific gravity values of various wood species
typically used in house construction.
The NDS provides tabulated connection design values that use the
following symbols for the three basic types of loading:
In addition to the already tabulated design values for the above structural
resistance properties of connections, the NDS provides calculation methods to
address conditions that may not be covered by the tables and that give more
Residential Structural Design Guide 7-13
Chapter 7 - Connections
flexibility to the design of connections. The methods are appropriate for use in
hand calculations or with computer spreadsheets.
For withdrawal, the design equations are relatively simple empirical
relationships (based on test data) that explain the effect of fastener size
(diameter), penetration into the wood, and density of the wood. For shear, the
equations are somewhat more complex because of the multiple failure modes that
may result from fastener characteristics, wood density, and size of the wood
members. Six shear-yielding modes (and a design equation for each) address
various yielding conditions in either the wood members or the fasteners that join
the members. The critical yield mode is used to determine the design shear value
for the connection. Refer to NDS•Appendix I for a description of the yield modes.
The yield equations in the NDS are based on general dowel equations that
use principles of engineering mechanics to predict the shear capacity of a doweled
joint. The general dowel equations can be used with joints that have a gap
between the members and they can also be used to predict ultimate capacity of a
joint made of wood, wood and metal, or wood and concrete. However, the
equations do not account for friction between members or the anchoring/cinching
effect of the fastener head as the joint deforms and the fastener rotates or develops
tensile forces. These effects are important to the ultimate capacity of wood
connections in shear and, therefore, the general dowel equations may be
considered to be conservative; refer to Section 7.3.6. For additional guidance and
background on the use of the general dowel equations, refer to the NDS
Commentary and other useful design resources available through the American
Forest & Paper Association (AF&PA, 1999; Showalter, Line, and Douglas, 1999).
[NDS•12.2&7.3]
W ′ = WC D C M C t C tn for nails and spikes
W ′ = WC D C M C t C eg for lag screws
The total allowable design value for a connection (as adjusted by the
appropriate factors above) must meet or exceed the design load determined for the
connection (refer to Chapter 3 for design loads). The values for W and Z are
based on single fastener connections. In instances of connections involving
multiple fasteners, the values for the individual or single fastener can be summed
to determine the total connection design value only when Cg is applied (to bolts
and lag screws only) and fasteners are the same type and similar size. However,
this approach may overlook certain system effects that can improve the actual
[NDS•12.2.1]
5
W = 1380(G) 2 DL p unadjusted withdrawal design value (lb) for a smooth shank
nail
where,
G = specific gravity of the lumber member receiving the nail tip
D = the diameter of the nail shank (in)
Lp = the depth of penetration (in) of the nail into the member receiving the nail tip
The design strength of nails is greater when a nail is driven into the side
rather than the end grain of a member. Withdrawal information is available for
nails driven into the side grain; however, the withdrawal capacity of a nail driven
into the end grain is assumed to be zero because of its unreliability. Furthermore,
the NDS does not provide a method for determining withdrawal values for
deformed shank nails. These nails significantly enhance withdrawal capacity and
are frequently used to attach roof sheathing in high-wind areas. They are also used
to attach floor sheathing and some siding materials to prevent nail “back-out.”
The use of deformed shank nails is usually based on experience or preference.
The design shear value, Z, for a nail is typically determined by using the
following tables from NDS•12:
[NDS•9.2.1]
3 3
W = 1800(G) 2 D 4 L p unadjusted withdrawal design value (lb) for a lag screw
where,
G = specific gravity of the lumber receiving the lag screw tip
Lp = the depth of penetration (in) of the lag screw into the member receiving the
Several recent studies have focused on roof sheathing attachment and nail
withdrawal, primarily as a result of Hurricane Andrew (HUD, 1999a; McClain,
1997; Cunningham, 1993; Mizzell and Schiff, 1994; and Murphy, Pye, and
Rosowsky, 1995); refer to Chapter 1. The studies identify problems related to
predicting the pull-off capacity of sheathing based on single nail withdrawal
values and determining the tributary withdrawal load (i.e., wind suction pressure)
on a particular sheathing fastener. One clear finding, however, is that the nails on
the interior of the roof sheathing panels are the critical fasteners (i.e., initiate
panel withdrawal failure) because of the generally larger tributary area served by
these fasteners. The studies also identified benefits to the use of screws and
deformed shank nails. However, use of a standard geometric tributary area of the
sheathing fastener and the wind loads in Chapter 3, along with the NDS
withdrawal values (Section 7.3.3), will generally result in a reasonable design
using nails. The wind load duration factor should also be applied to adjust the
withdrawal values since a commensurate reduction is implicit in the design
withdrawal values relative to the short-term, tested, ultimate withdrawal
capacities (see Section 7.3).
It is interesting, however, that one study found that the lower-bound (i.e.,
5th percentile) sheathing pull-off resistance was considerably higher than that
predicted by use of single-nail test values (Murphy, Pye, and Rosowsky, 1995).
The difference was as large as a factor of 1.39 greater than the single nail values.
While this would suggest a withdrawal system factor of at least 1.3 for sheathing
nails, it should be subject to additional considerations. For example, sheathing
nails are placed by people using tools in somewhat adverse conditions (i.e., on a
roof), not in a laboratory. Therefore, this system effect may be best considered as
a reasonable “construction tolerance” on actual nail spacing variation relative to
that intended by design. Thus, an 8- to 9-inch nail spacing on roof sheathing nails
in the panel’s field could be “tolerated” when a 6-inch spacing is “targeted” by
design.
Roof-to-Wall Connections
to-grain at the end of a member (i.e., a wall stud toenail connection to the top or
bottom plate that may be used instead of end nailing). Slant nailing occurs when a
nail is driven at an angle, but in a direction perpendicular-to-grain through the
side of the member and into the face grain of the other (i.e., from a roof rafter or
floor band joist to a wall top plate). Though a generally reliable connection in
most homes and similar structures built in the United States, even a well-designed
slant-nail connection used to attach roofs to walls will become impractical in
hurricane-prone regions or similar high-wind areas. In these conditions, a metal
strap or bracket is preferrable.
Based on the studies of roof-to-wall connections, five key findings are
summarized as follows (Reed et al., 1996; Conner et al., 1987):
The heel joint connection at the intersection of rafters and ceiling joists
have long been considered one of the weaker connections in conventional wood
roof framing. In fact, this highly stressed joint is one of the accolades of using a
wood truss rather than conventional rafter framing (particularly in high-wind or
snow-load conditions). However, the performance of conventional rafter-ceiling
joist heel joint connections should be understood by the designer since they are
frequently encountered in residential construction.
First, conventional rafter and ceiling joist (cross-tie) framing is simply a
“site-built” truss. Therefore, the joint loads can be analyzed by using methods
that are applicable to trusses (i.e., pinned joint analysis). However, the
performance of the system should be considered. As mentioned earlier for roof
trusses (Section 5.6.1 in Chapter 5), a system factor of 1.1 is applicable to tension
members and connections. Therefore, the calculated shear capacity of the nails in
the heel joint (and in ceiling joist splices) may be multiplied by a system factor of
1.1, which is considered conservative. Second, it must be remembered that the
nail shear values are based on a deformation limit and generally have a
conservative safety factor of three to five relative to the ultimate capacity.
Finally, the nail values should be adjusted for duration of load (i.e., snow load
duration factor of 1.15 to 1.25); refer to Section 5.2.4 of Chapter 5. With these
considerations and with the use of rafter support braces at or near mid-span (as is
common), reasonable heel joint designs should be possible for most typical design
conditions in residential construction.
Wall-to-Floor Connections
When wood sole plates are connected to wood floors, many nails are often
used, particularly along the total length of the sole plate or wall bottom plate.
When connected to a concrete slab or foundation wall, there are usually several
bolts along the length of the bottom plate. This points toward the question of
possible system effects in estimating the shear capacity (and uplift capacity) of
these connections for design purposes.
In recent shear wall tests, walls connected with pneumatic nails (0.131-
inch diameter by 3 inches long) spaced in pairs at 16 inches on center along the
bottom plate were found to resist over 600 pounds in shear per nail (HUD,
1999b). The bottom plate was Spruce-Pine-Fir lumber and the base beam was
Southern Yellow Pine. This value is about 4.5 times the adjusted allowable design
shear capacity predicted by use of the NDS equations. Similarly, connections
using 5/8-inch-diameter anchor bolts at 6 feet on center (all other conditions
equal) were tested in full shear wall assemblies; the ultimate shear capacity per
bolt was found to be 4,400 pounds. This value is about 3.5 times the adjusted
allowable design shear capacity per the NDS equations. These safety margins
appear excessive and should be considered by the designer when evaluating
similar connections from a practical “system” standpoint.
[ACI-318•22.5]
Vu ≤ φVn
4
Vn = f c′ bh
3
Shear forces at the base of exterior foundation walls may require a dowel to
transfer the forces from the wall to the footing. The equations below described by
ACI-318 as the Shear-Friction Method are used to develop shear resistance with
vertical reinforcement (dowels) across the wall-footing interface.
[ACI-318•11.7]
Masonry Walls Concrete Walls
l be ≥ 12d b Vu ≤ φVn
350
4 f m′ A v
0.2f
c′ A c
Vn = A vf f y µ ≤
B v =
minimumof
800
A c
0
.12A v f y
Vu
A vf =
φf y µ
φ = 0.85
If dowels are used to transfer shear forces from the base of the wall to the
footing, use the equations below to determine the minimum development length
required (refer to Figure 7.7 for typical dowel placement). If development length
exceeds the footing thickness, the dowel must be in the form of a hook, which is
rarely required in residential construction.
The equations below determine whether the concrete or masonry shear area
of each bolt is sufficient to resist pull-out from the wall as a result of uplift forces
and shear friction in the concrete.
[ACI-318•11.3, ACI-530•2.1.2]
Concrete Foundation Wall Masonry Foundation Wall
Vu ≤ φVc b a ≤ Ba
Vc = 4A v f c′ 0.5A p f m′
B a = minimumof
0.2A b f y
πl b 2 πl b 2
A p = minimum of
A v = minimumof
πl be
2
πh
2
Bearing Strength
When the foundation wall’s supporting surface is wider on all sides than the
loaded area, the designer is permitted to determine the design bearing strength on the
loaded area by using the equations below.
Given
• Design wind speed is 130 mph gust with an open (coastal) exposure
• Two-story home with a gable roof
• Roof framing lumber is Southern Yellow Pine (G=0.55)
• Roof framing is spaced at 24 inches on center
• Roof sheathing is 7/16-inch-thick structural wood panel
Solution
1. Determine the wind load on roof sheathing (Chapter 3, Section 3.6.2)
Step 3: Skip
2. Select a trial nail type and size, determine withdrawal capacity, and calculated
required spacing
Use an 8d pneumatic nail (0.113 inch diameter) with a length of 2 3/8 inches. The
unadjusted design withdrawal capacity is determined using the equation in Section
7.3.3.
W = 1380(G)2.5DLp
G = 0.55
D = 0.113 in
Determine the required nail spacing in the roof sheathing panel interior.
Notes:
1. If Spruce-Pine-Fir (G=0.42) roof framing lumber is substituted, W’ would be
54 lb and the required nail spacing would reduce to 4 inches on center in the
roof sheathing panel interior. Thus, it is extremely important to carefully
consider and verify the species of framing lumber when determining
fastening requirements for roof sheathing.
2. The above analysis is based on a smooth shank nail. A ring shank nail may
be used to provide greater withdrawal capacity that is also less susceptible to
lumber moisture conditions at installation and related long-term effects on
withdrawal capacity.
3. With the smaller tributary area, the roof sheathing edges that are supported
on framing members may be fastened at the standard 6 inch on center
fastener spacing. For simplicity, it may be easier to specify a 6 inch on
center spacing for all roof sheathing fasteners, but give an allowance of 2 to 3
inches for a reasonable construction tolerance; refer to Section 7.3.6.
4. As an added measure given the extreme wind environment, the sheathing nail
spacing along the gable end truss/framing should be specified at a closer
spacing, say 4 inches on center. These fasteners are critical to the
performance of light-frame gable roofs in extreme wind events; refer to the
discussion on hurricanes in Chapter 1. NDS•12.3.8 provides an equation to
determine nail lateral strength when subjected to a combined lateral and
withdrawal load. This equation may be used to verify the 4 inch nail spacing
recommendation at the gable end.
Conclusion
Given
• Design wind speed is 120 mph gust with an open coastal exposure
• One-story home with a hip roof (28 ft clear span trusses with 2 ft overhangs)
• Roof slope is 6:12
• Trusses are spaced at 24 in on center
Solution
1. Determine the design loads on the connection (Chapter 3)
Step 3: Skip
Determine the transverse shear (lateral) load on the roof-to-wall connection. The
transverse load is associated with the role of the roof diaphragm in supporting and
transferring lateral loads from direct wind pressure on the walls.
*The 1.1 coefficient is used since the maximum uplift on the roof and roof
pressure).
= 232 lb
468 lb (uplift)
*The lateral load parallel to a wall is not considered to be significant in this example
problem, although it may be checked to verify the transfer of lateral wind loads on the
roof to shear walls; refer to Chapter 6.
Generally, manufacturers publish loading data for metal connectors for multiple loading
directions. The designer should verify that these values are for simultaneous multi-
directional loading or make reasonable adjustments as needed. In this example problem,
the NDS will be used to design a simple roof tie-down strap and slant nail connection.
A tie down strap will be used to resist the uplift load and typical slant nailing will be
used to resist the lateral load. The slant nailing, however, does not contribute
appreciably to the uplift capacity when a strap or metal connector is used; refer to
Section 7.3.6.
Assuming an 18g (minimum 0.043 inches thick) metal strap is used, determine the
number of 6d common nails required to connect the strap to the truss and to the wall top
plate to resist the design uplift load.
The above Z value for metal side-plates implicitly addresses failure modes that may be
associated with strap/nail head tear-through. However, the width of the strap must be
calculated. Assuming a minimum 33 ksi steel yield strength and a standard 0.6 safety
factor, the width of the strap is determined as follows:
w = 0.55 in
Therefore, use a minimum 1-inch wide strap to allow for the width of nail holes and an
a staggered nail pattern. Alternatively, a thinner strap may be used (i.e., 20g or 0.033
inches thick) which may create less problem with installing finishes over the
connection.
Assuming that a 16d pneumatic nail will be used (0.131 in diameter by 3.5 inches long),
determine the number of slant-driven nails required to transfer the lateral load from the
wall to the roof sheathing diaphragm through the roof trusses. Assume that the wall
framing is Spruce-Pine-Fir (G = 0.42).
Therefore, the number of nails required to transfer the transverse shear load is
determined as follows:
Conclusion
The beginning of the uplift load path is on the roof sheathing which is transferred to the
roof framing through the sheathing nails; refer to Example 7.1. The uplift load is then
passed through the roof-to-wall connections as demonstrated in this example problem.
It should be noted that the load path for wind uplift cannot overlook any joint in the
framing.
One common error is to attach small roof tie-straps or clips to only the top member of
the wall top plate. Thus, the uplift load must be transferred between the two members
of the double top plate which are usually only face nailed together for the purpose of
assembly, not to transfer large uplift loads. This would not normally be a problem if
the wall sheathing were attached to the top member of the double top plate, but walls
are usually built to an 8 ft – 1 in height to allow for assembly of interior finishes and to
result in a full 8 ft ceiling height after floor and ceiling finishes. Since sheathing is a
nominal 8 ft in length, it cannot span the full wall height and may not be attached to the
top member of the top plate. Also, the strap should be placed on the structural
sheathing side of the wall unless framing joints within the wall (i.e., stud-to-plates) are
adequately reinforced.
Longer sheathing can be special ordered and is often used to transfer uplift and shear
loads across floor levels by lapping the sheathing over the floor framing to the wall
below. The sheathing may also be laced at the floor band joist to transfer uplift load,
but the cross grain tension of the band joist should not exceed a suitably low stress
value (i.e., 1/3Fv); refer to Chapter 5, Section 5.3.1.
Given
• Rafter and ceiling joist roof construction (without intermediate rafter
braces)
• Roof horizontal span is 28 ft and rafter slope is 6:12 (26 degrees)
• Roof framing is Hem-Fir (G=0.43) with a spacing of 16 inches on-center
• Roof snow load is 25 psf
• Rafter & roofing dead load is 10 psf
• Ceiling dead load is 5 psf
Solution
1. Determine the tensile load on the heel joint connection
Using basic principles of mechanics and pinned-joint analysis of the rafter and
ceiling joist “truss” system, the forces on the heel joint can be determined. First,
the rafter bearing reaction is determined as follows:
Summing forces in the y-direction (vertical) for equilibrium of the heel joint
connection, the compression (axial) force in the rafter is determined as follows:
Now, summing the forces in the x-direction (horizontal) for equilibrium of the
heel joint connection, the tension (axial) force in the ceiling joist is determined as
follows:
Try a 12d box nail. Using NDS Table 12.3A, the following Z value is obtained:
Z = 80 lb
Z’ = (80 lb)(1.25)(0.98) = 98 lb
In Section 5.6.1, a system factor of 1.1 for tension members and connections in
trussed, light-frame roofing systems was discussed for repetitive member
applications (i.e., framing spaced no greater than 24 inches on center). Therefore,
the Z’ value may be adjusted as follows:
If a 16d common nail is substituted, the number of nails may be reduced to about
8. If, in addition, the species of framing lumber was changed to Southern Yellow
Pine (G = 0.55), the number of nails could be reduced to 6.
Conclusion
This example problem demonstrates the design of one of the most critical roof
framing connections for site-built rafter and ceiling joist framing. In some cases,
the ceiling joist or cross-tie may be located at a higher point on the rafter than the
wall bearing location which will increase the load on the joint. In most designs, a
simple pinned-joint analysis of the roof framing is used to determine the
connection forces for various roof framing configurations.
The snow load duration factor of 1.25 was used in lieu of the 1.15 factor
recommended by the NDS; refer to Table 5.3. In addition, a system factor for
repetitive member, light-frame roof systems was used. The 1.1 factor is
considered to be conservative which may explain the difference between the
design solution in this example and the nailing required in Table 7.1 by
conventional practice (i.e., four 16d common nails). If the slant nailing of the
rafter to the wall top plate and wall top plate to the ceiling joist are considered in
transferring the tension load, then the number of nails may be reduced relative to
that calculated above. If a larger system factor than 1.1 is considered (say 1.3),
then the analysis will become more closely aligned with conventional practice;
refer to the roof framing system effects discussion in Section 5.6.1. It should also
be remembered that the NDS safety factor on nail lateral capacity is generally in
the range of 3 to 5. However, in more heavily loaded conditions (i.e., lower roof
slope, higher snow load, etc.) the connection design should be expected to depart
somewhat from conventional practice that is intended for “typical” conditions of
use.
In any event, 12 nails per rafter-ceiling joist joint may be considered unacceptable
by some builders and designers since the connection is marginally “over-crowed”
with fasteners. Therefore, alternative analysis methods and fastener solutions
should be considered with some regard to extensive experience in conventional
practice; refer to NDS•7.1.1.4 and the discussion above.
Given
• A 2x4 wall bottom (sole) plate of Spruce-Pine-Fir is fastened to a wood floor
deck
• Floor framing lumber is Hem-Fir
• A 3/4-inch-thick wood structural panel subfloor is used
• The bottom plate is subject to the following design loads due to wind and/or
earthquake lateral loads:
250 plf shear parallel-to-grain (shear wall slip resistance)
120 plf shear perpendicular-to-grain (transverse load on wall)
• The uplift load on the wall, if any, is assumed to be resisted by other
connections (i.e., uplift straps, shear wall hold-downs, etc.)
Find A suitable nailing schedule for the wall sole plate connection using 16d pneumatic
nails (0.131inch diameter by 3.5 inches long).
Solution
It is assumed that the nails will penetrate the sub-flooring and the floor framing
members. It will also be conservatively assumed that the density of the sub-floor
sheathing and the floor framing is the same as the wall bottom plate (lowest
density of the connected materials). These assumptions allow for the use of NDS
Table 12.3A. Alternatively, a more accurate nail design lateral capacity may be
calculated using the yield equations of NDS•12.3.1.
Using NDS Table 12.3A, it is noted that the closest nail diameters in the table are
0.135 and 0.128 inches. Interpolating between these values, using a side member
thickness of 1.5 inches, and assuming Spruce-Pine-Fir for all members, the
following Z value is obtained:
Assuming that both of the lateral loads act simultaneously at their full design
value (conservative assumption), the resultant design load is determined as
follows:
Using the conservative assumptions above, the number of nails per linear foot of
wall plate is determined as follows:
Rounding this number, the design recommendation is 2 nails per foot or 3 nails
per 16 inches of wall plate.
Conclusion
The number of 16d pneumatic nails (0.131 inch diameter) required is 2 nails per foot of
wall bottom plate for the moderate loading condition evaluated. The number of nails
may be reduced by using a larger diameter nail or by evaluating the nail lateral capacity
using the yield equations of NDS•12.3.1.
As noted in Chapter 6, the ultimate capacity of base connections for shear walls should
at least exceed the ultimate capacity of the shear wall for seismic design and, for wind
design, the connection should at least provide a safety factor of 2 relative to the wind
load. For seismic design, the safety factor for shear walls recommended in this guide is
2.5; refer to Chapter 6, Section 6.5.2.3. Therefore, the fastening schedule of 2-16d
pneumatic nails at 16 inches on center is not quite adequate for seismic design loads of
the magnitude assumed in this problem (i.e., the connection does not provide a safety
factor of at least 2.5). The reader is referred to Chapter 3, Section 3.8.4 for additional
discussion on seismic design considerations and the concept of “balanced” design.
Given
• A 2x10 Douglas-Fir joist is side-bearing (shear connection) on a built-up wood
girder
• The design shear load on the side-bearing joint is 400 lb due to floor live and
dead loads
Find 1. The number of 16d box toenails required to transfer the side-bearing (shear)
load.
2. A suitable joist hanger
Solution
1. Determine the number of 16d box toenails required
Z’ = ZCDCdCtn
Z’ = (103 lb)(0.83) = 85 lb
Use 6 toenails with 3 on each side of the joist to allow for reasonable construction
tolerance in assembling the connection in the field.
Data on metal joist hangers and various other connectors are available from a number
of manufacturers of these products. The design process simply involves the selection of
a properly rated connector of the appropriate size and configuration for the application.
Rated capacities of specialty connectors are generally associated with a particular
fastener and species of framing lumber. Adjustments may be necessary for use with
various lumber species and fastener types.
Conclusion
The example problem details the design approach for two simple methods of
transferring shear loads through a side-bearing connection. One approach uses a
conventional practice of toe-nailing the joist to a wood girder. This approach is
commonly used for short-span floor joists (i.e., tail joist to header joist connections at a
floor stairwell framing). For more heavily loaded applications, a metal joist hanger is
the preferred solution.
Given
• A 3x8 wood ledger board (Douglas-Fir) is used to support a side-bearing floor
system.
• The ledger is attached to 3x4 wall studs (Douglas-Fir) spaced at 16 inches on
center in a balloon-framed portion of a home; as a second condition, the ledger
is attached to a concrete wall.
• The design shear load on the ledger is 300 plf due to floor live and dead loads.
Find 1. The spacing of 5/8-inch-diameter lag screws required to fasten the ledger to
the wood wall framing
2. The spacing of 5/8-inch-diameter anchor bolts required to fasten the ledger to
a concrete wall
Solution
1. Determine connection requirements for use of a 5/8-inch-diameter lag screw
CΔ = 1.0**
*The Zs⊥ value is used for joints when the shear load is perpendicular to the grain
of the side member (or ledger in this case).
**A CΔ value of 1.0 is predicated on meeting the minimum edge and end
distances required for lag screws and bolts; refer to NDS•8.5.3 and NDS•9.4.
The required edge distance in the side member is 4D from the top of the ledger
(loaded edge) and 1.5D from the bottom of the ledger (unloaded edge), where D is
the diameter of the bolt or lag screw. The edge distance of 1.5D is barely met for
the nominal 3-inch-wide (2.5 inch actual) stud provided the lag screws are
installed along the center line of the stud.
***A 6-inch-long lag screw will extend through the side member (2.5 inches
thick) and penetrate into the main member 3.5 inches. The design penetration into
the main member must be reduced by the length of the tapered tip on the lag
screw (see Appendix L of NDS for lag screw dimensions).
Therefore, one lag screw per stud-ledger intersection may be used (i.e., 1.33 ft
spacing). The lag screws should be staggered about 2 inches from the top and
bottom of the 3x8 ledger board. Since the bolts are staggered (i.e., not two bolts
in a row), the value of Cg may be revised to 1.0 in the above calculations.
Cg = 1.0**
CΔ = 1.0***
***Edge and end distance requirements of NDS•8.5.3 and NDS•8.5.4 will be met
Therefore, the anchor bolts should be spaced at about 2 ft on center and staggered
from the top and bottom edge of the ledger by a distance of about 2 inches.
Note: In conditions where this connection is also required to support the wall
laterally (i.e., an outward tension load due to seismic loading on a heavy concrete
wall), the tension forces may dictate additional connectors to transfer the load into
the floor diaphragm. In lower wind or seismic load conditions, the ledger
connection to the wall and the floor sheathing connection to the ledger are usually
sufficient to transfer the design tension loading, even though it may induce some
cross grain tension forces in the ledger. The cross-grain tension stress may be
minimized by locating every other bolt as close to the top of the ledger as
practical or by using a larger plate washer on the bolts.
Conclusion
Given
• The foundation wall is connected to a wood sill plate and laterally supported as
shown in the figure below.
• Assume that the soil has a 30 pcf equivalent fluid density and that the
unbalanced backfill height is 7.5 ft.
• The foundation wall unsupported height (from basement slab to top of wall) is
8 ft.
• The wood sill is preservative-treated Southern Yellow Pine.
Find 1. The lateral load on the foundation wall to sill plate connection due to the
backfill lateral pressure
2. The required spacing of ½-inch-diameter anchor bolts in the sill plate
Solution
1. Determine the lateral load on the sill plate connection
Using the procedure in Section 3.5 of Chapter 3 and the associated beam
equations in Appendix A, the reaction at the top of the foundation wall is
determined as follows:
2. Determine the design lateral capacity of the anchor bolt and the required spacing
Conclusion
Given
• A 2x8 preservative-treated header is attached to each side of a deck post in a
bolted, double shear connection to support load from deck joists bearing on the
headers.
• The deck post is a preservative treated 4x4.
• The deck framing lumber is preservative-treated Southern Yellow Pine.
• The design double shear load on the connection is 2,560 lb (1,280 lb per header).
Find Determine if two 5/8-inch-diameter bolts are sufficient to resist the design load.
Solution
Calculate the design shear capacity of the bolted joint assuming that the bolts are
located approximately 2 inches from the top and bottom edge of the 2x8 headers
along the centerline of the 4x4 post.
**A normal duration of load is assumed for the deck live load. However, load duration studies for
deck live loads have not been conducted. Some recent research has indicated that a load duration
factor of 1.25 is appropriate for floor live loads; refer to Table 5.3 of Chapter 5.
***The top bolt is placed 2 inches from the top (loaded) edge of the 2x8 header and does not meet
the 4D (2.5 inch) edge distance requirement of NDS•8.5.3. However, neglecting the bolt entirely
If the top bolt is considered to be 80 percent effective based on its edge distance
relative to the required edge distance (i.e., 2 inches / 2.5 inches = 0.8), then the
design shear capacity for the two bolts in double shear may be estimated as
follows:
Conclusion
The calculation of the design shear capacity of a double shear bolted connection is
demonstrated in this example. As shown in the calculations, the connection
doesn’t meet the required load in the manner analyzed. A larger bolt diameter or
3 bolts may be used to meet the required design load. However, as in previous
examples, this connection is typical in residential deck construction (i.e.,
supporting deck spans of about 8 ft each way) and may be approved by the
“extensive experience” clause of NDS•7.1.1.4. As additional rationale, the
capacity of shear connections in the NDS is related to a yield (or deformation) limit
state and not capacity. On the basis of capacity, the safety margins are fairly
conservative for such applications; refer to Section 7.3.1. The use of a 1.25 load
duration factor for the deck live load will also increase the joint capacity to a value
nearly equivalent to the design load assumed in this example.
EXAMPLE 7.9 Wood King and Jamb Stud to Floor or Foundation Connection
Given
• From Example 7.2, the net design uplift load at the roof-to-wall connection
was determined to be 234 plf for a 120 mph gust, open exposure wind
condition.
• Assume that the uplift loads at the top of the wall are adequately transferred
through interconnection of wall framing members (i.e. top plates, sheathing,
studs, headers to king and jamb studs, etc.) to the base of the upper story wall.
• The framing lumber is Hem-Fir
Find 1. The net uplift load at the base of the king and jamb studs adjacent to a 6 ft
wide wall opening
2. An adequate connection detail to transfer the uplift load
Solution
1. Determine the net design uplift load at the base of the king and jamb studs
supporting the 6 ft header using the ASD load combinations in Chapter 3.
Tributary load
= (1/2 header span + 1/2 stud spacing)[uplift load – 0.6(wall dead load)]
= [0.5(6 ft) + 0.5(1.33 ft)][234 plf – 0.6(64 plf)]
= 717 lb (uplift)
2. Determine the number of 8d common nails in each end of an 18g (0.043 inch
minimum thickness) steel strap
The number of nails required in each end of the strap is determined as follows:
Note: As an option to the above solution, the same strap used on the layout studs
may be used on the jamb and king stud connection by using multiple straps. The
uplift strap on the layout studs would be required to resist 234 plf (1.33 ft) = 311
lb. Therefore, two or three of these straps could be used at wall opening location
and attached to the jamb and king studs. If the single strap is used as calculated in
the example problem, the jamb and king studs should be adequately
interconnected (i.e., face nailed) to transfer shear load from one to the other. For
example, if the header is strapped down to the top of the jamb stud and the king
stud is strapped at its base, then the two members must be adequately fastened
together. To some degree, the sheathing connections and other conventional
connections will assist in strengthening the overall load path and their
contribution should be considered or enhanced as appropriate.
As another alternative design, the king/jamb stud uplift connection may serve a
dual role as a wind uplift strap and a shear wall hold-down restraint if the wall
segment adjacent to the opening is designed to be a part of the building’s lateral
force resisting system (i.e., shear wall segment). The method to calculate hold-
down restraint forces for a shear wall is detailed in Chapter 6, Section 6.5.2.4.
The uplift force due to wind would be simply added to the uplift force due to
shear wall restraint to properly size a hold-down bracket or larger strap than
required for wind uplift alone.
Conclusion
In this example, the transfer of wind uplift loads through wall framing adjacent to
a wall opening is addressed. In addition, several alternate design approaches are
noted that may optimize the design and improve construction efficiency – even in
severe wind or seismic design conditions.
Given
Maximum transverse shear load on bottom of wall = 1,050 plf (due to soil)
Assume µ = 0.6 for concrete placed against hardened concrete not intentionally
roughened.
Find • Whether a dowel or key is required to provide increased shear transfer capacity
• If a dowel or key is required, size accordingly
Solution
1. Determine factored shear load on wall due to soil load (i.e., 1.6H per Chapter 3,
Table 3.1)
V = 1,050 plf
Therefore, a dowel or key is needed to secure the foundation wall to the footing.
3. Determine a required dowel size and spacing (Section 7..2 and ACI-318•5.14)
Avf = Vu / (φfyµ)
Try a No. 4 bar (Av = 0.20 in2) and determine the required dowel spacing as
follows:
Avf = Av/S
0.05 in2/lf = (0.2 in2)/S
S = 48 inches
Conclusion
This example problem demonstrates that for the given conditions a minimum of
one No. 4 rebar at 48 inches on center is required to adequately restrict the wall
from slipping. Alternatively, a key may be used or the base of the foundation wall
may be laterally supported by the basement slab.
It should be noted that the factored shear load due to the soil lateral pressure is
compared to the estimated friction resistance in Step 1 without factoring the
friction resistance. There is no clear guideline in this matter of designer
judgment.
Given
• 1/2-inch diameter anchor bolt at 4 feet on center with a 6 inch embedment
depth in an 8-inch thick concrete wall
• The bolt is an ASTM A36 bolt with fy = 36 ksi and the following design
properties for ASD; refer to AISC Manual of Steel Construction
(AISC,1989):
Ft = 19,100 psi (allowable tensile stress)
Fu = 58,000 psi (ultimate tensile stress)
Fv = 10,000 psi (allowable shear stress)
• The specified concrete has f’c = 3,000 psi
• The nominal design (unfactored) loading conditions are as follows:
Shear load = 116 plf
Uplift load = 285 plf
Dead load = 180 plf
Find Determine if the bolt and concrete are adequate for the given conditions.
Solution
1. Check shear in bolt using appropriate ASD steel design specifications (AISC,
1989) and the ASD load combinations in Chapter 3.
2. Check tension in bolt due to uplift using appropriate ASD steel design
specifications (AISC, 1989) and the appropriate ASD load combination in
Chapter 3.
Vu ≤ φVc
1,062 lb ≤ 21,044 lb OK
Conclusion
A 1/2-inch diameter anchor bolt with a 6 inch concrete embedment and spaced 4
feet on center is adequate for the given loading conditions. In lieu of using an
anchor bolt, there are many strap anchors that are also available. The strap anchor
manufacturer typically lists the embedment length and concrete compressive
strength required corresponding to strap gauge and shear and tension ratings. In
this instance, a design is not typically required−the designer simply ensures that
the design loads do not exceed the strap anchor’s rated capacity.
7.6 References
ACI, Building Code Requirements for Structural Concrete and Commentary, ACI
Standard 318-99, American Concrete Institute, Farmington Hills, MI,
1999a.
ACI, Building Code Requirements for Masonry Structures, ACI Standard 530,
American Concrete Institute, Farmington Hills, MI, 1999b.
ASTM, Standard Specification for Driven Fasteners: Nails, Spikes, and Staples
(ASTM F 1667), American Society of Testing and Materials, West
Conshohocken, PA, 1995.
ASTM, Standard Terminology of Nails for Use with Wood and Wood-Base
Materials (ASTM F 547), American Society of Testing and Materials,
West Conshohocken, PA, 1990.
Conner, H., Gromala, D., and Burgess, D., “Roof Connections in Houses: Key to
Wind Resistance,” Journal of Structural Engineering, Vol. 113, No. 12,
American Society of Civil Engineers, Reston, VA, 1987.
Cunningham, T.P., Roof Sheathing Fastening Schedules For Wind Uplift, APA
Report T92-28, American Plywood Association, Tacoma, WA, 1993.
Hoyle, R.J. and Woeste, F.R., Wood Technology in the Design of Structures, fifth
edition, Iowa State University Press, Ames, IA, 1989.
HUD, Perforated Shear Walls with Conventional and Innovative Base Restraint
Connections, prepared by the NAHB Research Center, Inc., for the U.S.
Department of Housing and Urban Development, Washington, DC, 1999b.
McClain, T.E., “Design Axial Withdrawal Strength from Wood: II. Plain-Shank
Common Wire Nails,” Forest Products Journal, Volume 47, No. 6,
Madison, WI, 1997.
Mizzell, D.P. and Schiff, S.D., Wind Resistance of Sheathing for Residential
Roofs, Clemson University, Clemson, SC, 1994.
Murphy, S., Pye, S., and Rosowsky, D., System Effects and Uplift Capacity of
Roof Sheathing Fasteners, Structures Congress, American Society of Civil
Engineers, New York, NY, 1995.
NES, Power-Driven Staples and Nails for Use in All Types of Building
Construction, NER-272, National Evaluation Service, Inc., Falls Church,
VA, 1997.
Reed, T.D., Rosowsky, D.V., and Schiff, S.D., Uplift Capacity of Rafter-to-Wall
Connections in Light-Frame Construction, Clemson University, Clemson,
SC, 1996.
Showalter, J., Line, P., and Douglas, P., Calculation of Lateral Connection Values
Using General Gowel Equations, Paper No. 994176, American Society of
Agricultural Engineers, St. Joseph, MI, 1999.
Diagrams and
Beam Equations
V 2
q = equivalent fluid density of soil (pcf)
L -h R 2
qh = soil presure (psf) at x = 0
− qh 3
V2 = − R 2 =
6L
1 2 h
V1 = R1 = qh (l − )
L 2 3L
h 1
Vx = V 1 − xq (2h − x) (where x < h)
2
x Vx = V2 (where x ≥ h)
R 1 1 1
Mx = V1x − qhx 2 + qx 3 (where x < h)
q h V 1
M m a x 2 6
S H E A R M O M E N T Mx = −V2 (L - x) (where x ≥ h)
2V1
x @ M max = h − h 2 −
q
qL3 hL L2 h 2 h3
Δ max (at x ≅ L ) ≅ − − +
2 EI 128 960 48 144L
Figure A.1 - Simple Beam (Foundation Wall) - Partial Triangular Load
M max
P 1
P 2 V M M M
Vmax = R 2 =
m a x 1 2 m a x L
e 1 e R M 1 = P1e1
2
1
M 2 = P2 e 2
S H E A R M O M E N T
L R = Vmax =
wL
x 2
w L
Vx = w − x
2
R R M max =
wL2 L
(at x = )
L /2 L /2 8 2
Mx =
wx
(L − x )
2
V Δ max =
5wL4 L
(at x = )
384EI 2
S H E A R V Δx =
wx 3
24EI
(
L − 2Lx 2 + x 3 )
M m a x
M O M E N T
Figure A.3 - Simple Beam - Uniformly Distributed Load
L R 1 = V1 =
w max
x 3
w m a x R 2 = V2 =
2w max
3
w max w 2
Vx = − max
R 1 R 2
3 L2
0 .5 8 L 0 .4 2 L L 2w max L
M max (at x = )=
3 9 3
V 1 w max x
Mx = (L2 − x 2 )
S H E A R V 3L2
2
8 w L3
Δ max (at x = L 1 − ) = max
M m a x
15 77 EI
w max x
Δx = (3x 4 − 10L2 x 2 + 7L4 )
180EIL2
M O M E N T
L
x P
Pb
R1 = V1 (max when a<b) =
L
Pa
R 1 R 2
R2 = V2 (max when a>b) =
L
a b Pab
Mmax (at point of load) =
L
V 1 S H E A R Mx (when x<a) =
Pbx
L
V 2 a (a + 2b) Fab (a + 2b) 3a (a + 2b)
Δmax [at x = when a<b] =
3 27EIL
Pa 2 b 2
M Δa (at point of load) =
m a x 3EIL
Pbx 2 2 2
Δx (when x<a) = (L - b - x )
M O M E N T 6EIL
L R1 = V1 =
P1 (L − a) + P2 b
L
x
P1a + P2 (L − b)
P 1
P 2
R2 = V2 =
L
M M 2
1
M O M E N T
Figure A.6 - Simple Beam - Two Unequal Concentrated Loads Unsymmetrically Placed
L
R = Vmax = wL
w
Vx = wx
wL2
Mmax (at fixed end) =
x R 2
wx 2
Mx =
V m a x
2
S H E A R Δmax (at free end) =
wL4
8EI
M Δx =
w
M O M E N T m a x
24EI
(x4 – 4L3x + 3L4)
L
R=V=P
x P
Mmax (at fixed end) = Pb
R Mx (when x>a) = P(x-a)
a b
Pb 2
Δmax (at free end) = (3L-b)
6EI
V Pb 3
Δa (at point of load) =
S H E A R 3EI
Pb 2
Δx (when x<a) = (3L-3x-b)
M O M E N M m a x
6EI
P(L − x) 2
Δx (when x>a) = (3b-L+x)
6EI
L
3wL
w R1 = V1 =
8
5wL
R2 = V2 = Vmax =
8
R x R 2
Vx = R1 - wx
1 wL2
Mmax =
V 1
8
3 9
M1 (at x = ) = L= wL2
3 /8 L V 2
8 128
S H E A R wx 2
1 /4 L Mx = R1x
2
M 1 L wL4
Δmax (at x = (1 + 33 ) = 0.42L) =
M O M E N T M m a x
16 185EI
wx
Δx = (L3 – 3Lx2 + 2x3)
48EI
Figure A.9 - Beam Fixed at One End, Supported at Other - Uniformly Distributed Load
L R1 = V1 =
Pb 2
(a + 2L)
2L3
x P Pa
R2 = V2 = (3L2 - a2)
2L3
R 2 M1 (at point of load) = R1a
R 1 a b Pab
M2 (at fixed end) = (a + L)
2L2
V 1
Mx (when x<a) = R1x
Mx (when x>a) = R1x - P(x-a)
V 2 L2 + a 2 Pa (L2 − a 2 ) 3
S H E A R Δmax (when a<0.4L at x = L 2 ) =
3L − a 2 3EI (3L2 − a 2 ) 2
Pab 2
M 1
Δmax (when a>0.4L at x = L
a
)=
a
2L + a 6EI 2L + a
M O M E N T M Pa 2 b 3
2 Δa (at point of load) = (3L + a)
P a /R 2 12EIL3
Pa 2 x
Δx (when x<a) = 3
(3aL2 – 2Lx2 - ax2)
12EIL
Pa
Δx (when x>a) = 3
(L-x)2(3L2x - a2x - 2a2L)
12EIL
Figure A.10 - Beam Fixed at One End, Supported at Other - Concentrated Load at Any Point
L R=V=
wL
x w
2
L
Vx = w − x
2
R R Mmax (at ends) =
wL2
L /2 L /2 12
wL2
M1 (at center) =
24
V w
Mx = (6Lx - L - 6x2)
2
12
S H E A R V wL4
Δmax (at center) =
0 .2 L 384EI
wx 2
M 1 Δx = (L - x)2
24EI
M m a x M O M E N T M m a x
Figure A.12 - Beam Fixed at Both Ends - Concentrated Load at Any Point
L R1 = V1 =
w 2 2
(L - a )
2L
x x 1 w
R2 = V2 + V3 = (L + a)2
w V2 = wa
2L
w 2 2
R 1
R 2
V3 =
2L
(L + a )
Vx (between supports) = R1 - wx
V 1 V
Vx1 (for overhang) = w(a - x1)
2 L a2 w
M1 (at x = 1 − 2 ) = (L + a) 2 (L − a) 2
S H E A R V 2 L 8L2
3
wa 2
M2 (at R2) =
M 1
2
wx 2 2
M 2
Mx (between supports) =
2L
(L - a - xL)
L R1 = V1 =
Pa
P L
x x 1 P
R2 = V1 + V2 = (L + a)
L
V2 = P
R 1
R 2 Mmax (at R2) = Pa
Pax
Mx (between supports) =
L
V 2 Mx1 (for overhang) = P(a - x1)
V 1 L PaL2
Δmax (between supports at x = )=
S H E A R 3 9 3EI
2
Pa
Δmax (for overhang at x1 = a) = (L + a)
M m a x
3EI
Pax 2 3
M O M E N T Δx (between supports) =
6EIL
(L - x )
Px 1
Δx (for overhang) = (2aL + 3ax1 - x12)
6EI
Figure A.14 - Beam Overhanging One Support - Concentrated Load at End of Overhang
2 L R1 = V1 = R3 = V3 =
3wL
8
x 10wL
R2 =
w 8
5wL
L L V2 = Vm =
8
R R wL2
1 R 2 3 Mmax = −
8
3L 9wL2
V V 2
M1 [at x = ]=
1 8 128
V V 3 3wLx wx 2
2 Mx [at x < L] = −
8 2
3 /8 L S H E A R 3 /8 L wL4
Δmax [at x ≅ 0.46L] =
185EI
M x
x M m a x
M O M E N T
Figure A.15 - Continuous Beam - Two Equal Spans and Uniformly Distributed Load
2 L R1 = V1 =
7
wL
16
x 5
w R2 = V2 + V3 = wL
8
1
L L R3 = V3 = − wL
16
R 1 R 2
R 3
9
V2 = wL
16
7 49
Mmax [at x = L ] = wL2
V 1 V 16 512
3 1
V M1 [at R2] = − wL2
2 16
7 /1 6 L S H E A R Mx [at x < L] =
wx
(7L - 8x)
16
wL4
Δmax [at x ≅ 0.47L] =
M m a x 109EI
M 1
M O M E N T
Figure A.16 - Continuous Beam - Two Equal Spans with Uniform Load on One Span
x x 1 R1 = V1 =
M1
+
wL1
L1 2
w R2 = wL1 + wL2 - R1 - R3
M wL 2
L 1 L 2
R3 = V4 = 1 +
L1 2
R 1 R 2 R V2 = wL1 - R1
3
V3 = wL2 - R3
V 1 3 M1 [at x < L1 , max. at x =
R1
] = R1x =
wx 2
V w 2
V 2
4
wL 2 3 + wL1 3
M2 = −
S H E A R 8 (L 1 + L 2 )
R3 wx 1 2
M3 [at x1 < L2 , max. at x1 = ] = R3x1 -
w 2
M 1 M 3
M 2
M O M E N T
Figure A.17 - Continuous Beam - Two Unequal Spans and Uniformly Distributed Load
Unit Conversions
The following list provides the conversion relationship between U.S. customary units and the International System
(SI) units. A complete guide to the SI system and its use can be found in ASTM E 380, Metric Practice.
To convert from to multiply by
Length
inch (in.) meter(µ) 25,400
inch (in.) centimeter 2.54
inch (in.) meter(m) 0.0254
foot (ft) meter(m) 0.3048
yard (yd) meter(m) 0.9144
mile (mi) kilometer(km) 1.6
Area
square foot (sq ft) square meter(sq m) 0.09290304
square inch (sq in) square centimeter(sq cm) 6.452
square inch (sq in.) square meter(sq m) 0.00064516
square yard (sq yd) square meter(sq m) 0.8391274
square mile (sq mi) square kilometer(sq km) 2.6
Volume
cubic inch (cu in.) cubic centimeter(cu cm) 16.387064
cubic inch (cu in.) cubic meter(cu m) 0.00001639
cubic foot (cu ft) cubic meter(cu m) 0.02831685
cubic yard (cu yd) cubic meter(cu m) 0.7645549
gallon (gal) Can. liquid liter 4.546
gallon (gal) Can. liquid cubic meter(cu m) 0.004546
gallon (gal) U.S. liquid* liter 3.7854118
gallon (gal) U.S. liquid cubic meter(cu m) 0.00378541
fluid ounce (fl oz) milliliters(ml) 29.57353
fluid ounce (fl oz) cubic meter(cu m) 0.00002957
Force
kip (1000 lb) kilogram (kg) 453.6
kip (1000 lb) Newton (N) 4,448.222
pound (lb) kilogram (kg) 0.4535924
pound (lb) Newton (N) 4.448222
Stress or pressure
kip/sq inch (ksi) megapascal (Mpa) 6.894757
kip/sq inch (ksi) kilogram/square 70.31
centimeter (kg/sq cm)
Mass (weight)
pound (lb) avoirdupois kilogram (kg) 0.4535924
ton, 2000 lb kilogram (kg) 907.1848
grain kilogram (kg) 0.0000648
Moment
1 foot-pound (ft-lb) Newton-meter 1.356
(N-m)
Velocity
mile per hour (mph) kilometer per hour 1.60934
(km/hr)
mile per hour (mph) kilometer per second 0.44704
(km/sec)
Temperature
degree Fahrenheit (°F) degree Celsius (°C) tC = (tF-32)/1.8
degree Fahrenheit (°F) degree Kelvin (°K) tK= (tF+ 459.7)/1.8
degree Kelvin (°F) degree Celsius (°C) tC = (tK -32)/1.8
The prefixes and symbols below are commonly used to form names and symbols of the decimal multiples and
submultiples of the SI units.
A zone, 4-52
Dead load, 3-4, 3-24, 3-31, 3-32, 4-58, 4-61, 4-64,
Adhesive, 6-75
4-70, 4-72, 4-77, 4-80, 4-84, 5-49, 5-52, 5-72, 7-30,
Blocking, 6-24
Drainage, 4-34, 4-47
7-51
Flexure, 4-14, 4-15, 4-17
Checks, 5-16
Flood load, 2-4
3-38, 4-2, 4-4, 4-5, 4-6, 4-7, 4-10, 4-11, 4-13, 4-14,
Header, 5-14, 5-37, 5-67, 5-82, 7-2, 7-43
Cyclic, 3-38
Impact, 3-18, 3-40, 5-12, 5-83
Dampening, 3-25
Joist hanger, 7-9
7-25, 7-50
Live load, 3-6, 3-31, 3-32, 4-58, 4-61, 4-64, 4-70, 4-72,
Seismic (see Earthquake also), 1-25, 2-2, 2-3, 3-23,
Moisture, 5-6
Sinker nail, 7-5
Nail, 5-31, 5-45, 6-22, 6-30, 6-38, 6-74, 7-2, 7-4, 7-5,
Slump, 4-5, 4-88
7-6, 7-28
Snow load, 2-17, 4-64
Partition, 5-44
6-48, 6-52
7-50
System, 2-2, 3-4, 3-26, 5-13, 5-14, 5-22, 5-25, 5-33,
7-9, 7-33
Topographic effect, 3-15
Rankine, 3-8
Tributary area, 6-11
REACH, 1-15
Tributary load, 7-45
Rebar, 4-6
Truss, 1-5, 1-7, 2-25, 2-9, 2-10, 3-17, 3-33, 3-35, 3-19,
5-84, 7-50
V zone, 4-51
Weight, 3-10, 4-4, 4-7, 4-80, 6-23, 6-74 Wood truss, 1-5
Wind load, 3-14, 3-15, 3-33, 5-63, 5-72, 7-28, 7-30 Yield,7-47