Catalogue Fww-E
Catalogue Fww-E
Contents
Nomenclature……………………………………………………………………………………… 2
Valve Nomenclature……………………………………………………………………………… 3
Features…………………………………………………………………………………………… 4
Specifications……………………………………………………………………………………… 6
Sound Data………………………………………………………………………………………… 7
Operating Limits…………………………………………………………………………………… 8
Electrical Data……………………………………………………………………………………… 10
Wiring Diagrams…………………………………………………………………………………… 10
Installation………………………………………………………………………………………… 11
Operation…………………………………………………………………………………………… 16
Valve Kit…………………………………………………………………………………………… 17
Wired Controller…………………………………………………………………………………… 20
Maintenance……………………………………………………………………………………… 24
Precautions………………………………………………………………………………………… 25
Troubleshooting…………………………………………………………………………………… 25
   NOTE:	 Installation and maintenance are to be performed only by qualified personnel who are
       	 familiar with local codes and regulations, and experienced with this type of equipment.
Caution: Sharp edges and coil surfaces are a potential injury hazard. Avoid contact with them.
   Warning:	Moving machinery and electrical power hazard. May cause severe personal
            injury or death. Disconnect and lock off power before servicing equipment.
                                                  1
Nomenclature
FWW 1000 EC 5 L C X - A 0 A C
                                                      2
Valve Nomenclature
FWW - 2V 4 Y B R A E
                       E-Export
                       U-Stick "Made In China"
                       Power Supply:
                       A-220-240V/1Ph/50Hz
                       K-208-230V/1Ph/60Hz
                       Pipe Connection
                       R-for Right hand unit
                       L-for Left hand unit
                       Valve Type
                       B-with Ball Valve
                       X-without Ball Valve
                       Strainer Type
                       Y-with Y-Strainer
                       X-without Y-Strainer
                       Union Size
                       Omitted-R3/4
                       4-R1
                       Valve model
                       2V:2-Way Valve Kit
                       3V:3-Way Valve Kit
                       FWW-DAIKIN FCU
                       (Only 2-pipe system is applicable)
                                               3
Features
More Energy Saving
■ FWW-EC series fan coil unit significantly reduces power consumption for its outstanding energy saving feature.
   Compared to traditional fan coil, FWW-EC series fan coil unit can save:
                                                                                                            sav
                                                                                                        ele       e4
                                                                                                           ctr       7
                                                                                                               ic e %
                                                                                                                   ne
                                                                                                                      rgy
More Comfortable
■ Room temperature fluctuation is usually ±2°C if use traditional AC motor fan coil unit, and the fan has only three
   speed, which could easily cause the supply air too hot or too cold.
■ Room temperature fluctuation can be limited to ±0.5 when use FWW-EC series fan coil unit, and air flow can
   adjust at one rpm per step, so comfortable environment is widely available.
                                                         4
Lower Sound Level
■ No electromagnetic noise: units using brushless DC motor adopt electronic commutation to replace the
   mechanical commutation, so as to avoid the electromagnetic interference and carbon brush noise in mechanical
   commutation.
■ Lower running speed: the higher fan speed, the bigger sound level. Traditional fan coil units can only run under
   three speed while fan coil units with stepless speed regulation can run at lower speed.
■ Fan silence technology
   • Large diameter, wide impeller
   • Dynamic and static balance test
   • Even supply air
■ Use rubber bush between the fan and motor to achieve flexible connection, which effectively reduce the noise
   and vibration of unit when on/off, loading/unloading.
More Healthy
■ Isolation of carbon dust pollution Use brushless DC motor without Hall element, with carbon brush commutation
   removed to prevent indoor air pollution caused by toner dust.
                                                      5
Specifications
General Data
                                                                                  FWW-EC
                MODEL                   FWW200EC      FWW300EC      FWW400EC      FWW500EC        FWW600EC        FWW800EC      FWW1000EC      FWW1200EC      FWW1400EC
                              m3/h         340           510           680           850             1020             1360         1700           2040           2380
                   HIGH
                              CFM          200           300           400           500              600             800          1000           1200           1400
                              m3/h         279           418           558           697              836             1115         1394           1673           1952
AIR FLOW        MEDIUM
                              CFM          164           246           328           410              492             656           820            984            1148
                              m3/h         170           255           340           425              510             680           850           1020            1190
                   LOW
                              CFM          100           150           200           250              300             400           500            600            700
EXTERNAL STATIC
                             Pa/in.wg                                                           12,30,50/0.05,0.12,0.20
PRESSURE
TOTAL COOLING                   W          2550          3550          4330          5200            6100             8200         9500           11500          13500
CAPACITY                      Btu/h        8701          12113        14775         17743            20814           27980         32415          39240          46064
SENSIBLE COOLING                W          1515          2120          2850          3450            4050             5650         6750           8250           9250
CAPACITY                      Btu/h        5169          7234          9725          11772           13819           19279         23032          28150          31562
TOTAL HEATING                   W          3800          5800          6800          8650            10450           14000         16500          20250          23000
CAPACITY                      Btu/h       12966         19790         23203         29515            35657           47770         56300          69096          78479
                              m3/h         0.44          0.61          0.74          0.89             1.05            1.41          1.63           1.97           2.31
WATER FLOW RATE
                             USGPM          1.9           2.7           3.3           3.9             4.6                 6.2       7.2            8.7            10.2
                               kPa         14.0          31.0          16.0          25.0             33.0            37.0          27.0           42.0           41.0
HEAD LOSS (Cooling)
                              in.wg.        0.1           0.1           0.1           0.1             0.1                 0.1       0.1            0.2            0.2
UNIT WEIGHT                    Kg          14.5          16.8          19.3          20.3             21.4            30.6          33.6           36.3           42.0
(Without plenum)                lb         32.0          37.0          42.5          44.8             47.2            67.5          74.1           80.0           92.6
UNIT GROSS WEIGHT              Kg          17.0          20.1          22.9          24.0             25.3            35.8          39.5           42.7           49.4
(Without plenum)                lb         37.5          44.3          50.5          52.9             55.8            78.9          87.1           94.1          108.9
UNIT WEIGHT                    Kg          17.2          20.1          23.0          24.3             25.7            36.3          39.7           43.2           49.9
(With plenum)                   lb         37.9          44.3          50.7          53.6             56.7            80.0          87.5           95.2          110.0
UNIT GROSS WEIGHT              Kg          19.7          23.4          26.6          28.0             29.6            41.5          45.6           49.6           57.3
(With plenum)                   lb         43.4          51.6          58.6          61.7             65.3            91.5         100.5          109.3          126.3
                Without
                Return Air     mm       675x478x235   815x478x235   915x478x235   995x478x235    1095x478x235    1425x478x235   1525x478x235   1725x478x235   1985x478x235
                Plenum
                With Back
                Return Air     mm       675x516x235   815x516x235   915x516x235   995x516x235    1095x516x235    1425x516x235   1525x516x235   1725x516x235   1985x516x235
DIMENSIONS Plenum
                With
                Bottom
                Return Air
                               mm       675x497x235   815x497x235   915x497x235   995x497x235    1095x497x235    1425x497x235   1525x497x235   1725x497x235   1985x497x235
                Plenum
CONDENSATE
                                                                                                         R3/4
DRAIN SIZE
NOTES:
1)	 ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2)	 ALL THE UNITS ARE BEING TESTED UNDER FOLLOWING CONTITION:
	   • COOLING-27°C DB/19.5°C WB INDOOR AND WATER INLET 7°C OUTLET 12°C
	   • HEATING-21°C DB INDOOR AND WATER 60°C INLET.WATER FLOW:WAME WITH COOLING CONDITION.
3)	 SOUND PRESSURE LEVEL ARE ACCORDING TO MICROPHONE POSITION OF THE MEASUREMENT POINT
    IS 1m IN FRONT AND
                                                                                      6
Components Data
                                                                                  FWW-EC
                                          FWW200EC    FWW300EC      FWW400EC         FWW500EC       FWW600EC      FWW800EC      FWW1000EC   FWW1200EC   FWW1400EC
          TYPE                                                  GALVANIZED STEEL DOUBLE STAGE IMPELLER CENTRIFUGAL (BLADE: FORWARD)
FAN
          QUANTITY                           1           2             2                 2             2             3              4           4           4
          TYPE                                                                    SINGLE PHAZE BALL BEARING CAPACITOR RUNNING
MOTOR     QUANTITY                           1           1             1                 1             1             2              2           2           2
          IP/INSULATION GRADE                                                                          IP44/B
                     MATERIAL                                                                         COPPER
                                    mm                                                                  9.52
                     DIAMETER
          TUBE                      in                                                                  0.37
                                    mm                                                                  0.33
COIL                 THICKNESS
                                    in                                                                  0.01
                     MATERIAL                                                                   HYDROPHILIC ALUMINUM
          FIN        ROW                                                                                    3
                     FIN PER INCH                                                                          12
NOTES:
ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
Sound Data
                                                                                  FWW-EC
Model                                      FWW200EC    FWW300EC      FWW400EC           FWW500EC     FWW600EC      FWW800EC      FWW1000EC FWW1200EC FWW1400EC
                       High         dBA       34.0           35.5          37.0              40.0          44.5          43.0       47.0       47.5        50.5
Sound Pressure
                       Middle       dBA       27.2           29.1          29.7              32.6          37.1          36.9       39.0       41.9        41.9
Level (ESP:12 Pa)
                       Low          dBA       20.9           18.9          22.5              24.0          30.1          29.6       29.2       32.0        30.8
                       High         dBA       37.5           39.0          41.0              42.5          46.5          44.5       48.0       50.0        50.5
Sound Pressure
                       Middle       dBA       31.0           33.5          33.0              35.1          39.8          37.8       40.0       42.7        42.0
Level (ESP: 30 Pa)
                       Low          dBA       23.0           20.0          25.0              25.8          32.5          30.3       30.6       35.6        33.5
                       High         dBA       39.0           42.0          44.0              45.0          48.0          46.0       49.5       52.5        52.0
Sound Pressure
                       Middle       dBA       35.5           35.7          36.6              38.1          41.9          38.6       42.2       45.1        44.2
Level (ESP: 50 Pa)
                       Low          dBA       23.8           27.2          27.4              28.5          34.0          30.5       33.5       36.4        35.8
NOTES:
1)	 ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2)	 SOUND PRESSURE LEVEL ARE ACCORDING TO MICROPHONE POSITION OF THE MEASUREMENT POINT IS 1m
    IN FRONT AND 1m BELOW THE UNIT.
                                                                                    7
Operating Limits
                    Operating Limits                                               FWW-EC
Water Circuit
Max. Water side pressure                                1.6MPa
Min. Entering water temperature                         3ºC (cooling)
Power supply
Operating voltage limits                                ±10% Volt
Operating frequency limits                              ±2Hz
FWW500EC
FWW200EC
FWW600EC
FWW1400EC
FWW1000EC
                                                          8
Outlines and Dimensions
                                                               FWW500EC
                                                              MCW600A      1095           1095+a
                                                                                        995            995+a
                                                                                                        872          772
                                                                                                                   907          807
                                                                                                                                910               810 2            2
                                                              MCW800A
                                                               FWW600EC    1425           1425+a
                                                                                       1095           1095+a
                                                                                                        1202         872
                                                                                                                   1237         907
                                                                                                                                1240              910 3            2
                                                              MCW1000A     1525           1525+a
                                        WATER SUPPLY           FWW800EC                1425           1425+a
                                                                                                        1302        1202 1237
                                                                                                                   1337         1340             1240 4            3
                                        Rc3/4″                MCW1200A     1725           1725+a
                                                              FWW1000EC                1525             1502
                                                                                                      1525+a       1537
                                                                                                                    1302 1337   1540             1340 4            4
                                                              MCW1400A     1985           1985+a
                                        WATER RETURN
                                        Rc3/4″                FWW1200EC                1725             1762
                                                                                                      1725+a       1797
                                                                                                                    1502 1537   1800             1540 4            4
                                                              FWW1400EC
                                                              Note:                    1985drain pan 1985+a
                                                                    The length of extended                          1762
                                                                                                      has 100,200,300  optional1797              1800              4
                                                              Note:The length of extended drai n pan has 100,200,300 optional
 WITH BACK RETURN AIR PLENUM
                                                                                                                                                                                   Unit: mm
                                                                                                                                                                             Unit: mm
                                                                                                              A
                                                                                           A                                                                                       Number Of
                                                                  Molde
                                                               MODEL                  Standard                    LongB Drain   C   B    DC       D E          E       F     F    Number of
                                                                       Standard Drain                                                                                                Fans
                                                                                                                                                                                  Fans
                                       TERMINAL BOX                       Pan              Drain  Pan
                                                                                             Long Drain Pan
                                                                                                                      Pan
                                                               MCW200A 675                      675+a                452        487      470                                           1
                              MOUNTING HOLE         ×16         FWW200EC                      675                   675+a         452    487      470522 522           552
                                                                                                                                                                           552             1
                                                               MCW300A 815                      815+a                592        627      610                                           2
                               CONDENSATE DRAIN R3/4″           FWW300EC                      815                   815+a         592    627      610662 662           692
                                                                                                                                                                          692              2
                                                               MCW400A 915                      915+a                692        727      710         762               792             2
                                        AIR VENT                FWW400EC                      915                   915+a         692    727      710      762            792              2
                                                               MCW500A 995                      995+a                772        807      790                                           2
                                                                FWW500EC                      995                   995+a         772    807      790842 842           872
                                                                                                                                                                          872              2
                                                               MCW600A  1095                   1095+a                872        907      890         942               972             2
                                                                FWW600EC                     1095                  1095+a         872    907      890      942            972              2
                                                               MCW800A  1425                   1425+a                1202       1237     1220                                          3
                                      WATER SUPPLY              FWW800EC                     1425                  1425+a        1202   1237     12201272 1272         1302
                                                                                                                                                                         1302              3
                                      Rc3/4″                   MCW1000A 1525                   1525+a                1302       1337     1320        1372              1402            4
                                                               FWW1000EC                     1525                  1525+a        1302   1337     1320 1372               1402              4
                                                               MCW1200A 1725                   1725+a                1502       1537     1520        1572              1602            4
                                      WATER RETURN
                                      Rc3/4″
                                                               FWW1200EC                     1725                  1725+a        1502   1537     1520 1572               1602              4
                                                               MCW1400A 1985                   1985+a                1762       1797     1780                                          4
                                                               FWW1400EC                     1985                  1985+a        1762   1797     17801832 1832         1862
                                                                                                                                                                         1862              4
                                                              Note: The length of extended drain pan has 100,200,300 optional
                                                              Note:The length of extended drain pan has 100,200,300 optional
FILTER ELIMINATOR
                                                          9
Electrical Data
FWW-EC
MODEL                             FWW200EC FWW300EC FWW400EC FWW500EC FWW600EC FWW800EC FWW1000EC      FWW1200EC   FWW1400EC
        INSULATION GRADE                                                          B
        POWER SOURCE    V/Ph/Hz                                          220V/1Ph/50Hz
        RATED POWER
12Pa                       W         17       28       31         43       62            81     106       136         152
        INPUT
MOTOR
        RATED RUNNING
                           A        0.10     0.18     0.19        0.21     0.32          0.38   0.50      0.63        0.76
        CURRENT
        POLES                                                                   8P
        INSULATION GRADE                                                          B
        POWER SOURCE    V/Ph/Hz                                          220V/1Ph/50Hz
        RATED POWER
30Pa                       W         22       34       42         55       73            97     126       160         180
        INPUT
MOTOR
        RATED RUNNING
                           A        0.13     0.20     0.20        0.27     0.40          0.45   0.59      0.78        0.90
        CURRENT
        POLES                                                                   8P
        INSULATION GRADE             B
        POWER SOURCE    V/Ph/Hz                                          220V/1Ph/50Hz
        RATED POWER
50Pa                       W         28       41       53         68       85            117    148       188         213
        INPUT
MOTOR
        RATED RUNNING
                           A        0.16     0.23     0.26        0.35     0.47          0.54   0.69      0.93        1.05
        CURRENT
        POLES                                                                   8P
NOTES:
1)	 ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2)	 ALL ELECTRIC DATA ARE BEING TESTED UNDER HIGH SPEED.
Wiring Diagrams
                                                             10
Installation
1.	 The unit can be installed only by professionals that are familiar with the series of air conditioners and
    local laws and regulations.
2.	 Make the following preparations before the unit is ready and installed:
    I	 Ensure that there is sufficient space for unit installation and maintenance (see the unit hoisting
         diagram).
    II	 Confirm the space for pipeline placement and cable layout.
    III	 Check the hoisting structure. The hoisting point of unit must be secure and hard enough to bear the
         weight of the unit and the vibration during unit operating.
3.	 Do not carry the unit by holding the fan volute or impeller during unit installation.
4.	 Hoist the unit horizontally; otherwise, the condensate water may overflow. It is recommended to fix the
    unit during hoisting by using full-thread screws (diameter: 6 mm to 8 mm), flat gaskets, spring washers,
    and nuts.
5.	 The following figure shows the structure and dimensions of a unit without return air plenum. For the
    structure and dimensions of a unit with return air plenum, see the other technical materials.
                                                                                                                                             
                                                                                                                                                                               Unit: mm
                                                                      
                                         
                           A
                                                                                                                                          Long
                                                                                                                           Standard                       C               Number
                                                                                                              
      Molde                     Drain     B             D                    
                                                                           
                                                                                                                                                                                    Of Fans
                                                                                                                                      
                                                                      
                                                   Drain Pan
                                                                                                                                              Pan
                                                                                                                                                   
                                                                                                                                                                 
                                                                                                                                                                                          
                                                                           
                                   
                                                                                                    
                                                                                                             
                                                                                                                       FWW200EC
                                                                                                                            675
                                                                                                                                    675+a
                                                                                                                                                   
                                                                                                                                                      
                                                                                                                                                             452 
                                                                                                                                                                 487    490
                                                                                                                                                                           
                                                                                                                                                                                       1        
                                                             
                                                                                
                                                                                                                       FWW300EC
                                                                                                                            815
                                                                                                                                    815+a
                                                                                                                                                         592 627   630         2           
                                                                           
                                                                                                  
                                                                                                                       FWW400EC       915  915+a      692 727   730         2
                                                                                                    
                                                                                                                        
                                                                                                                                                   
                                                                                                                                                                                        
                                                                                                                                                                                                 
         
                                                                                                                                                                                 
                                                                                                                                                                             
                                                                                                                   FWW600EC
                                                                                                                          1095 1095+a         
                                                                                                                                                              872 907    910
                                                                                                                                                                                    2    
                                                                          
                                                                                                                 FWW800EC
                                                                                                                          1425 1425+a            
                                                                                                                                                             1202 
                                                                                                                                                                    1237   1240    3    
                                                                    
                 
                                                                                                                                                                       
                                                                                  
                                                                                                                         
                                                                                                                       FWW1000EC
                                                                                                                                
                                                                                                                                 1525         
                                                                                                                                          1525+a            
                                                                                                                                                             1302 
                                                                                                                                                                    1337   1340    4       
                                                      
                                                                                                                                                                       
                                                                           
                                                                                                 
                                            
                                           
                                                                          
                                                                      
                                                                                                                           
                                                                                                                       FWW1200EC
                                                                                                                                
                                                                                                                                 1725         
                                                                                                                                          1725+a   1502 
                                                                                                                                                                    1537
                                                                                                                                                                       1540
                                                                                                                                                                               4       
                                                                           
                                                                     
                                                       
                                                      
                                                                          
                                                                                                                        
                                                                                                                       FWW1400EC 1985 1985+a   1762 
                                                                                                                                                                    1797   1800
                                                                                                                                                                                   4   
                                                                                            
                                                                                            
                                                                                      
                                                                                                            
                                                                                               11
7.	 Length of the duct connecting to the unit must match the rated static pressure over outlet of the unit; otherwise,
     the unit may break down. It is commended that the duct and unit be connected by a flexible connector tube.
     The duct must also be installed in accordance with local laws and regulations.
8.	 Use a reducer when the unit duct does not fit the supply outlet.
9.	 For the unit without the air filter, install the air filter near the return air inlet to avoid dust particle blockage and
     to ensure the heat exchanging performance.
10.	 Use flexible connector tubes to connect the water entering and leaving pipes of the unit. Seal the joint with tape
     after connection. Keep the wrench near the water entering and leaving pipe during pipeline connection. Fasten
     the joints slowly at a constant speed. The torque is 110 N m (11.2 kgf m) at most. When tools with long arm of
     force are used, properly set the torque. An excessive torque can deform or even damage the copper pipe and
     cause leakage. The pipeline connection is shown in the following figure.
11.	 Install the water filter near the inlet of the chilled water pump and the water inlet of unit to prevent the unit from
     being blocked by dirt.
12.	 Implement strict thermal insulation measures on the valves, water entering pipe, water leaving pipe, and
     condensate water pipe to avoid condensation.
13.	 Clean the unit after installation. Ensure that no sundries left on the drain pan; otherwise, the discharge of
     condensate water can be blocked. Cover the unit to protect it if other constructions are still in progress,
     because unit damage and tiny foreign substances inside the unit can cause malfunctions.
14.	 Ensure that the power supply is the same as that specified on the unit nameplate. Power off the unit before
     installation. Electric connections must be conducted in accordance with the provided diagram, as shown in the
     following figure. Proper grounding should be provided for the unit. (The grounding resistance is smaller than or
     equal to 4 ohms.)
                                                              12
                                   Model: FWW200~1400EC
                                                             RXWSXWRSWLRQDO
                                                             (OHFWULFKHDWLQJVLJQDO
                                                                                        5HVHUYHG
)DXOWDODUPRXWSXW
                                                                                                                         2QRIILQGLFDWRU
    KHDWLQJYDOYH
    &RQQHFWHGWRWKH
                        FRROLQJKHDWLQJYDOYH
                        &RQQHFWHGWRWKH
FWW
	    DIP settings and electrical wiring diagrams for other functions are as follows:
(1)	 Condition of ON/OFF indicator and dial-up setting
                                                          Temperature control
                                                                                                                                                                     Function
                                                          DIP
                                                                                                                                                  The on/off indicator is connected or disconnected based
                                                                                                                                            ON
                                                                                                                                                        on the status of the cooling or heating valve.
                                                         SWP2.3
                                                                                                                                                  The on/off indicator is connected or disconnected based
                                                                                                                                            OFF
                                                                                                                                                            on the on/off status of the master unit.
	   The default setting is OFF.
	   The following figure shows the electrical wiring for fault alarm output and on/off indicator.
                                                
	   When the unit or valve operates, the on/off status contactor is closed and the on/off external device turns on. In
    the case of a fault in the unit, the fault status contactor is closed and the fault external device turns on.
                                                                                                                                                  13
(2)	 Electric heater
                                               Electric Heater
                                                                                            Function
                              DIP
                                                                         ON         The electric heater function is enabled.
                       SWP2.4
                                                                         OFF        The electric heater function is disabled.
	   The default setting is OFF. (Note: In a four-pipe heat pump system, do not set the auxiliary heating function.)
The following figure shows the electric wiring for electric heater output signals.
                                                 
                                                 
                                                   
                                                   
	 The following figures show the electric wiring of a two-wire valve and three-wire valve.
		 Wiring of two-pipe cooling-only or 		                Wiring of four-pipe heat pump system
		 heat pump system
                            
                            
                                                                                            
                                                                                            
                                                                                                           
                                                                                                           
                       
                       
                                                                                             
                                                                                             
                                                                                                          
                                                                                                          
                                                                               14
(4)	 Room card
     A.	 If J1 port is connected, the unit disables the room card function.
     B.	 If J1 port is disconnected, the unit enables the room card function.
         a.	 If J1 port is disconnected when the unit is off, the unit is disabled.
         b.	 If J1 port is disconnected when the unit is on, the unit works intermittently based on the room
             temperature and working mode before the disconnection. If J1 port is disconnected in heating mode, the
             room temperature will be kept between 18°C and 21°C. If J1 port is disconnected in cooling mode, the
             room temperature will be kept between 25°C and 28°C. If J1 port is disconnected in air supply mode, the
             unit is under standby mode.
15.	 The voltage, frequency, and phases of power must be the same as those specified on the unit nameplate. The
     voltage range is ±10% of the rated value. The power frequency range is ±1% of the rated value.
16. Customers must install a circuit-break device with sufficient capacity near the inlet power cable. The circuit-
     break device must support short-circuit protection and earthing-fault protection, and the clearance between
     open contacts must be at least 3 mm.
17. All cables must be protected properly for safety. For example, cables cannot contact fans or motors, and
     necessary measures must be taken to prevent the cables from water, dust, corrosion, vibration, and animal
     bites.
18.	 Electrical data
                  Model                 FWW200EC         FWW300EC        FWW400EC         FWW500EC   FWW600EC
              Power supply                                               220 V–/50 Hz
           Max power input (W)                32              42              56             73            92
           Max input current(A)              0.19             0.23           0.28           0.35          0.44
                        Section area
                                              1                1               1             1             1
      Power wires          (mm2)
                          Quantity            3                3               3             3             3
                  Model                 FWW800EC        FWW1000EC FWW1200EC FWW1400EC                      *
              Power supply                                               220 V–/50 Hz
           Max power input (W)               118              150             181           217            *
         Max running current (A)             0.56             0.70           0.84           1.00           *
                        Section area
                                              1                1               1             1             *
      Power wires          (mm2)
                          Quantity            3                3               3             3             *
    NOTE:
    THE MAX POWER INPUT IS TESTED UNDER 50Pa EXTERNAL STATIC PRESSURE.
19. After the installation, debug the unit and ensure that the unit operates properly.
                                                         15
Operation
1.	 Remove the sundries from the drain pan, fan volute, and places around the unit. Check pipeline connection
    and cabling.
2.	 Wear protective devices before starting the unit. Do not touch any switch when your hands are wet.
3.	 Turn around the fan impeller with hands before unit operation. Ensure that the fan impeller turns smoothly
    without colliding with the volute. Then, power on the unit and ensure that the rotation direction of impeller is
    consistent with that specified on the unit nameplate.
4.	 Before the unit test run, close the water entering and leaving valves and clean the pipelines, then open the
    water entering and leaving valves again.
5.	 During the unit test run, open the air vent on the unit water leaving pipe to discharge the air inside the
    pipelines. Close the air vent until stream of water flowing out of the air vent.
6.	 Remove any obstacles from the places near the air outlet of unit and duct to ensure smooth ventilation.
7.	 Use clean and soft water to prevent scale formation. Scale formation on the heat exchanger can reduces
    the heat exchanging performance, and hinders the water flow and pump efficiency with an increased water
    resistance.
	   Requirements of water quality are listed in the following table:
                                                                                           Tendency
                              Item                              Base Value
                                                                                  Corrosion       Scale Formation
                         pH value (25°C)                        7.5 to 9.0            О                  О
                           Conductivity
                                                μS/cm             < 800               О                  О
                             (25°C)
                                Cl-            mg(Cl-)/L          < 200               О
       Standard item                2-               2-
                               SO             mg(SO )/L           < 200               О
                        Acid consumption
                                             mg(CaCO3)/L         < 100 K                                 О
                            (pH=4.8)
                          Full hardness      mg(CaCO3)/L         < 200 K                                 О
                                Fe             mg(Fe)/L           < 1.0               О                  О
                                 2-                 2-
                                S              mg(S )/L             0                 О
      Reference item                +                +
                               NH             mg(NH )/L          < 1.0 K              О
                               SiO2           mg(SiO2)/L          < 50 K                                 О
    NOTE:
    K INDICATES RELEVANT FACTORS THAT ARE INCLINED TO CORROSION OR SCALE FORMATION.
                                                           16
Valve Kit
The valve kit is applied for 2-pipe system.
The kit consists of (refer structure figure 0):
•	 2/3 way valve body is made of brass, maximum working pressure 1.6MPa.
•	 Electric actuator has the following specifications:
	   -Power supply: 220V±10%/50/60Hz (±2Hz)
	   -Activation: ON/OFF
•	 Hydraulic kit for the installation of the valve on the heat exchanger, complete with 2 ball valves for
   adjusting the water flow and for closing the water circuit when perform maintenance to the unit.
•	 Y-strainer protects unit from impurity, increases the service life and isolating valves.
Figure 0
All parts of 2-way valve kit are indicated in the figure 1. ( For right pipe connection unit.)
                               F
           E                                                A Ball valve
                                                            B Brass connector
                                                            C Y-strainer
                                                            D Water inlet pipe
                                                            E Water outlet pipe
                                                   A
                                                            F 2-way valve
                                   B
                       C
                                           Figure 1
               D
All parts of 3-way valve kit are indicated in the figure 2. ( For right pipe connection unit.)
                                                            A Ball valve
                                                            B Brass connector
                                   G                        C Y-strainer
                                                            D Connector pipe
                           F
                                                       A
                                                            E Water inlet pipe
                                               B            F 3-way valve
                                       C                    G Water outlet pipe
                   E       D
Figure 2
                                                            17
Installation
1.	 Install the 2-way valve kit as indicated in the pictures of figure 3. (For right pipe connection unit.) As
    shown as detail A, firstly take apart connector, then install ① to unit with necessary sealing material . Fix
    ② between ① and ③. At last tighten ③, make sure all of connectors are sealed.
2.	 Install the 3-way valve kit as indicated in the pictures of figure 4. (For right pipe connection unit.) Detail is
    as same as 2-way valve unit.
                                                         209
                                                               65
                                                                                    220
                                                                              203
                                                                                                              ķ
                                                                                                                   ĸ
                                                     A
                                                                                                                   Detail A
                                                                                                                                      146
                                                    Figure 3              2-Way Valve
                                             218
                                            153
                                                                                                                   Ĺ
                                                                    300
                                                                                                    ķ
                                                                                                        ĸ
                                                                                                        Detail A
                                                A
                                                                                                                                210
                                                                                                                              120
                                                                     18
Insulation
1.	 The insulation design and materials should be complying with local and national codes and regulations.
2.	 Chilled water pipes and all parts on the pipes should be insulated.
The flow resistance of the connecting valve/hydraulic kit assembly is obtained from the following formula:
△PW = (QW/100Kv)2
Pipe Connection
1.	 Using suitable fittings as water pipe connections with reference to the outline and dimensions.
2.	 The water inlet is on the bottom while outlet on top.
3.	 The connection must be concealed with rubberized fabric to avoid leakage.
4.	 Tightening torque should not be too high when connecting water pipes, in order to avoid brass deformation
    or water-leakage by torsion split.
Wiring
1.	 Refer to the wiring diagram of the appropriate controller.
2.	 For connection with the DAIKIN controller, position the water temperature probe into the appropriate
    position. Refer to the dedicated controller installation and operation manual.
                                                       19
Wired Controller
1.	 The unit uses MC316 wired controller, which is applicable to fan coils in FWW-EC series.
	   Dimensions:
LCD interface
3.	   Wired controller
	     (1)	Status screen: displays set temperature, mode, air speed, clock, and timer.
	     (2)	Infrared receiving window: receives infrared.
	     (3)	On/off button: starts up and shuts down the unit.
	     (4)	Mode button: switches the mode in cycle, that is, cooling > air supply >      
           heating > automatic (only available to a four-pipe unit) > cooling.                          
           speed > medium speed > low speed > automatic speed (there is no
           automatic speed in fan mode).
	     (8)	Temperature setting button ( △ ): raise the set temperature.
	     (9)	Temperature setting button ( ▽ ): decrease the set temperature.
                                                          20
4.	 Operation guide
	   (1)	 Set room temperature
		Press the setting button once to display room temperature on the LCD
                                                                                                    
		     A.	As shown in the right figure, press △ and ▽ at the same time to switch
			 Fahrenheit temperature and centigrade temperature.
		     B. 	Centigrade temperature ranges from 16°C to 30°C. Fahrenheit
            temperature ranges from 61°F to 86°F.                                              
                                                       21
5.	 The energy saving mode and power failure memory function can be set at the back of the wired controller.
	   (1)	 Power failure memory
		This function avoids wired controller has power failure memory function. After the power is resumed, the
         wired controller displays the status and parameters that are set before a power failure if the power failure
         memory function is enabled.
		       You can set the function by using SW1.4 DIP, as shown in the following table.
                   SW1.4 Status                                     Function
                        ON                              Power failure memory is enabled.
                       OFF                              Power failure memory is disabled.
         The default setting is OFF.
6.	 An infrared remote controller can be equipped on the wired controller. The receiving diameter is 8 meters within
    an angle of 30°. An infrared remote controller can be used to set only basic functions and cannot be used to
    set time or the timing function. (Optional)
	   Operation panel of an infrared remote controller:
	   (1)	 Fan button
	   (2)	 ON/OFF button
	   (3)	 Temperature raise button
	   (4)	 Temperature decrease button
	   (5)	 Mode button
                                                          22
	 (2)	 Fix the button shell and install wired controller connection
		     A.	Fasten the bottom shell of the wired controller to a flat surface of a hidden box with two accessory
           screws. Do not tighten the screws too much; otherwise, the bottom shell may be damaged.
		     B.	 Recommended wired controller connection
                        Cable Type                2-core polyvinyl chloride jacketed and insulated flexible
                                                      cable (cable with shield layer is recommended)
                    Cable Specification                                 0.5–1.0 mm2
			Strip only 7 mm to 8 mm jacket at the end of the cable connecting to the wired controller. At the other
       end of the cable, prevent the core from being exposed when stripping the jacket and connecting the
       cable to the module SLM terminal.
			 Note: The cable should be shorter than 20 m. Otherwise, signals may be interfered.
		 C.	 The following figure shows the installation and connection of the wired controller.
(3) Fix the top shell and bottom shell of the wired controller, as shown in the following figure.
		       Note: Do not clamp cables while fixing the shells. Do not touch the printed circuit board directly with your
              hand.
8.	 Precautions
	   (1)	Power off the wired controller before installing or maintaining it. The wired controller should be installed or
         maintained by authorized personnel.
	   (2)	Do not remove or insert the connection when the wired controller is powered on. Otherwise, electric shock
         or other damage may be caused. Do not place the wired controller under direct sunlight or in an extremely
         humid environment.
	   (3)	When installing the wired controller, do not hole it at random. Install the wired controller on a flat surface.
         Do not hit the display screen against any hard object or press the display screen with force.
	   (4)	Use accessory screws to fasten the wired controller. Screws in other specifications are not allowed.
	   (5)	If the wired controller operates abnormally in a long time, contact the supplier.
                                                         23
Remote Control Indicator Panel
The unit uses MC313 remote control indicator panel, which is applicable to fan coils in FWW-EC series.
Dimensions:
This remote control indicator panel matches with G4 remote controller, which can be used to set the energy saving
mode and power failure memory function.
Set the temperature to 16°C and press the power button to enable energy saving. Set the temperature to 17°C and
press the power button to disable energy saving.
Set the temperature to 18°C and press the power button to enable power failure memory. Set the temperature to
19°C and press the power button to disable power failure memory.
For details, refer to user guide to G4 remote controller.
Maintenance
1.	 The unit must be maintained routinely by professionals.
2.	Before maintenance or repairing, cut off the power and place a warning sign (for example, "Unit Is Under
    Repair, Do Not Turn on the Power") near the power.
3.	Clean the air filter at least every two months (the cleaning frequency varies with the operation performance and
    environment) to ensure smooth air returning.
4.	 Clean the heat exchanger at least every six months. (The cleaning frequency varies with the operation
    performance and environment.) Do not push down or damage the fins, and repair pushed-down fins. Alkaline
    cleaning solution cannot be used to clean heat exchanger fins.
5.	 Check the unit routinely: remove the sundries from the drain pan; clean the unit; ensure that the motor and fan
    are fixed securely.
6.	 Cut off the unit power if the unit is not used for a long time. Ensure well insulation before the unit is started up
    in the next time.
7.	 When the unit is not operating, ensure that the coil is full of water to minimize corrosion if the ambient
    temperature is above 0°C; if the ambient temperature is 0°C or below 0°C, adopt either of the following freeze-
    proofing measures: (1) ensure continuous operation of the circulating pump; (2) add antifreeze agent with
    proper concentration; (3) drain the water in the coil.
                                                           24
Precautions
1.	Do not stop the running of unit when cold water is being provided continuously; otherwise, the unit and
     adjacent object surface may have condensation.
2.	High-temperature and humid air may cause unit condensation. Therefore, install the unit in a place where
     doors are not opened and closed frequently, and away from the vent and places where vapor may generate.
3. 	 Condensation may occur when the unit is operating in a moist environment. Increase the water entering
     temperature or reduce the water flow to avoid condensation.
4.	 Long-time operation may cause unit condensation. Please install the electric control valve and temperature
     controller.
5.	 The noise at sound pressure level specified on the unit nameplate is obtained based on the test in National
     Standard (GB) in a hemi-anechoic chamber with the background noise set to 11.5 dB(A). In practice, the unit
     installation and onsite pipe connection can affect the unit noise.
6.	 For unit performance parameters, see the unit nameplate.
7.	 Do not reconstruct the unit; otherwise, the unit performance may degrade, and disasters such as operation
     failure, electric shock, and fire may occur.
Troubleshooting
in the case of abnormal status during unit operation, check the unit according to the following table. If the
problem still cannot be resolved, contact the seller.
   Problem
                                          Possible Causes                                            Recommended Solution
  Description
                    Power failure or the unit power is not on.                   Wait until the power is on or turn on the unit power.
  The unit does
                    The power plug is loose.                                     Plug in the power plug properly.
   not operate.
                    The motor is damaged.                                        Replace the motor.
                    The motor bearing is damaged.                                Replace the motor.
                  Screws for fixing the fan and motor are loose.                 Fix the screws securely.
Abnormal noise
  and vibration   The fan volute is deformed and collides with the fan
                                                                                 Replace the fan.
occur during unit impeller, or the impeller is deformed.
   operation.     Sundries exist in the ventilation outlet or the duct.          Remove the sundries.
                    The air filter is blocked.                                   Clean the filter.
  The air supply The return air inlet or air outlet of unit is blocked.          Remove the obstacle.
  is not smooth
  or the air flow The air filter is blocked.                                     Clean the filter.
 volume is small.
                    The electric control valve of unit is not started.           Start the electric control valve of unit.
                    The circulating pump is not started. As a result, the cold
                                                                                 Start the circulating pump.
                    or hot water does not flow.
  The cooling or The heat exchanger fins are blocked or pushed down.             Clean and repair the heat exchanger.
 heating function Temperature of the cold water during cooling is too high,
       fails.                                                                    Adjust the configured temperature of the unit.
                  or temperature of the hot water during heating is too low.
                    The set temperature of temperature controller is             Adjusted the set temperature of the temperature
                    inappropriate.                                               controller.
                    The air filter is blocked.                                   Clean the filter.
                    The condensate drain pan is blocked.                         Clean the condensate drain pan.
                    The unit is not installed horizontally.                      Adjust the place of the unit until it is placed horizontally.
                    Cold water is being provided continuously when the fan       Stop the electric control valve of unit or operate the unit
                    has already stopped.                                         at a low gear.
  Water leaks.
                                                                                 Perform dehumidification and avoid the entering of high-
                    Ambient temperature too high.
                                                                                 temperature and high-humidity air into indoor places.
                    The discharge valve is loose.                                Tighten the discharge valve.
                    The unit piping leaks.                                       Contact the seller.
                                                                     25
If a fault occurs when the unit is running, the fault code will be displayed on the wired controller and
indicated by the remote control panel for easy troubleshooting.
                     Statuses of Indicators on the Remote Control
 Code on the
                                    Indicator Panel                                   Fault Description
Wired Controller
                    COOL      DRY/TIMER        FAN            HEAT
                                                                        Communication failure between the main
      LC           Flashing       Off        Flashing          Off
                                                                        control board and driving board
                                                                        Undervoltage or overvoltage on the DC
      U2           Flashing       Off           Off            Off
                                                                        bus
       L9            Off        Flashing        Off            Off      Motor stall
      A6             Off          Off           Off          Flashing   Motor overcurrent
      P1             Off          Off        Flashing          Off      Motor open-phase or disconnection
      LA           Flashing     Flashing        Off            Off      IPM module fault
       L3          Flashing       Off           Off          Flashing   MCU overheat
      CJ             Off        Flashing        Off          Flashing   Indoor temperature sensor fault
                                                                        DIP setting error (resetting is required
      UA           Flashing     Flashing        Off          Flashing
                                                                        according to the circuit diagram)
      A1             Off        Flashing     Flashing        Flashing   Storage fault
                                                                        Communication failure between the
      U5                                                                master board and wired controller
                                                                        (reconnection is required)
                                                        26
Warning     ●	 Daikin Industries, Ltd.’s products are manufactured for export to numerous countries throughout the
               world. Daikin Industries, Ltd. does not have control over which products are exported to and used in
               a particular country. Prior to purchase, please therefore confirm with your local authorized importer,
               distributor and/or retailer whether this product conforms to the applicable standards, and is suitable
               for use, in the region where the product will be used. This statement does not purport to exclude,
               restrict or modify the application of any local legislation.
            ●	 Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
               Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
            ●	 Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
               contractor to install those parts and accessories. Use of unauthorized parts and accessories or
               improper installation of parts and accessories can result in water or refrigerant leakage, electrical
               shock, fire or explosion.
            ●	 Read the User’s Manual carefully before using this product. The User’s Manual provides important
               safety instructions and warnings. Be sure to follow these instructions and warnings.