CP Calculation
CP Calculation
                                                                                               MC :
         DOCUMENT TITLE                                DOCUMENT NUMBER
                                                                                                                      Page | 1
CLIENT:                                  PROJECT:                                        CONTRACTOR:
                                                                                         MC :
         DOCUMENT TITLE                                 DOCUMENT NUMBER
                                                         REVISION INDEX
PAG
                                                                 PAGE
          OWNER / MC                    CONTRACTOR                      OWNER / MC              CONTRACTOR
  E
           0     1     2    0      1    2    3      4    5   6          0    1   2   7     8       9   10      11      12   13
  1                         *
  2                         *
  3                         *
  4                         *
  5                         *
  6                         *
  7                         *
  8                         *
  9                         *
 10                         *
 11                         *
 12                         *
 13                         *
 14                         *
 15                         *
 16                         *
 17                         *
 18                         *
 19                         *
 20                         *
CLIENT:                              PROJECT:                          CONTRACTOR:
                                                                       MC :
      DOCUMENT TITLE                            DOCUMENT NUMBER
REV. 00 Page 3 of 20
CONTENTS
1. PURPOSE
2. REFERENCE DOCUMENTS
3. STRUCTURE TO BE PROTECTED
4. DESIGN BASIS
   5. DESIGN CALCULATION
CLIENT:                                PROJECT:                           CONTRACTOR:
                                                                          MC :
        DOCUMENT TITLE                            DOCUMENT NUMBER
REV. 00 Page 4 of 20
1. PURPOSE
       This document is prepared for Cathodic Protection calculation and analysis review in
       accordance with actually utilized equipment in the process area of the END Hydro
       treatment unit project in BouAli, Iran.
2. REFERENCE DOCUMENTS
               GN-ESS-EL-520,
                Specification for Cathodic Protection.
3. STRUCTURE TO BE PROTECTED
       Cathodic protection current shall be applied to the whole underground metallic pipelines
       listed in table 1. Total surface area of the structures to be protected is also calculated and
       mentioned in the below tables as following procedure:
                                                                                           MC :
      DOCUMENT TITLE                               DOCUMENT NUMBER
                                                       REVIEW OF
                                                          THE
   Cathodic Protection Calculation                    CALCULATION
REV. 00 Page 5 of 20
                                                                                                  Total Surface
       Item         Diameter(inch)              Diameter(m)            Length(m)
                                                                                                   Area(sqm)
          1                   1                      0.0254                 28.63                       2.28
          2                   2                      0.0508               1234.38                      196.90
          3                   3                      0.0762                 293.8                      70.30
          4                   4                      0.1016                829.68                      264.69
          5                   8                      0.2032                192.53                      122.84
          6                  10                      0.254                   72.6                      57.90
          7                  12                      0.3048                162.09                      155.13
          8                  20                      0.508                   83.4                      133.03
                                                                                                        Total
                                                    Average                 Total                      area(sq
                 Average diameter (inch)          diameter (m)            length(m)                      m)
                            4.34                     0.1103                2897.11                      1003
      NOTE 1: Coefficient factor of 20% has been applied to U/G piping surface area for other
      structures in close vicinity.
      NOTE 2: overall coating damage for pipelines will be considered as 30% for 25 years design
      life. 5% initial damage and 1% annual damage will be considered for pipelines coating.
CLIENT:                                PROJECT:                                         CONTRACTOR:
                                                                                        MC :
          DOCUMENT TITLE                            DOCUMENT NUMBER
4. DESIGN BASIS
 The generally accepted design guideline for anodes buried in coke breeze is 0.1 Kg/per amp-
year. The maximum output current density and consumption rate of C TYPE , HSCCI(high silica
chrome cast iron ) anodes in different environmental conditions are as follows:
                                                                                  MC :
      DOCUMENT TITLE                                 DOCUMENT NUMBER
REV. 00 Page 7 of 20
 ii. Extend the anode surface area, thus increasing the amount of current the anode can discharge.
iii. Reduce consumption of the anode since the carbon becomes the part of the anode consumed
before the anode itself.
These anodes are produced in of 2 × 60 inches. It should be noted that output current of anode with
2 × 60 inches dimension in carbon backfill environment (coke breeze) is about 2 ampers for 25
years life time.
Dimensional specifications and weight of the bare and canister anodes are as follows:
22.5 1525 76 51
The anodes shall be installed in shallow vertical beds in order to maintain a uniform protective
current distribution.
4.3 Coating System
       The conjoint use of coating and cathodic protection takes advantages to the most attractive
       features of each method of corrosion control. Although coating and cathodic protection are
       mutually supportive, it is important to recognize in their joint use.
4.4 Protection level
       The system is so designed that the potential at any point of the protected pipelines shall be
       in the range of -0.85 volts to -1.2 volts, when current ON with respect to a Cu/CuSo4
       reference electrode. in the case of sulfate reducing bacteria (SRB) existence the minimum
       negative potential shall be considered as -0.95 volts with reference electrode Cu/CuSo4.
4.5 Soil Condition
       The soil resistivity measurements have been conducted along the main right ways of the
       structures. According to attached report the average soil resistivity is equal to 70.7 Ώ.cm for
       underground pipelines which is in the range of very corrosive.
CLIENT:                                    PROJECT:                                             CONTRACTOR:
                                                                                                MC :
         DOCUMENT TITLE                                 DOCUMENT NUMBER
REV. 00 Page 8 of 20
                                        Soil resistivity
                                          (ohm-cm)               Degree of Corrosiveness
                                          500–1,000                          Corrosive
                                         1,000–2,000                  Moderately corrosive
                                                                                                                                                        MC :
            DOCUMENT TITLE                                                                   DOCUMENT NUMBER
REV. 00 Page 9 of 20
5. DESIGN CALCULATION
               According to the total surface area of the pipelines, with considering the protective current
               density for bare pipe (= 30 mA/ m2 refer to clause 4.6) and coated surface area (=0.35
               mA /m2 refer to clause 4.6) as mentioned in clause 3, the protection current shall be
               calculated as table 5.
                                                             Table 5 : Cathodic Protection Calculation Notes
                                                                          (Pipe for Process area)
A=D*L*Ω At=A*1.2 Icb=At*5%*CDb Icc=At*95%*CDc Icb+Icc Fcb=At*30%*CDb FCc=At*70%*CDc Fcb+Fcc (Icb+Icc+Fcb+Fcc)/2 Icb+Icc+Fcb+Fcc
 1         1      0/0254      28/63     2/28341428    2/740097136       0/004110146     0/000780928      0/004891073       0/024660874        0/000739826         0/0254007      0/015145887         0/030291774
 2         2      0/0508    1234/38    196/8984226    236/2781071       0/354417161     0/067339261      0/421756421       2/126502964        0/063795089        2/190298053     1/306027237         2/612054474
 3         3      0/0762      293/8     70/2969384    84/35632608       0/126534489     0/024041553      0/150576042       0/759206935        0/022776208        0/781983143     0/466279592         0/932559185
 4         4      0/1016     829/68    264/6878323    317/6253988       0/476438098     0/090523239      0/566961337       2/858628589        0/085758858        2/944387447     1/755674392         3/511348784
 5         8      0/2032     192/53    122/8433814    147/4120577       0/221118087     0/042012436      0/263130523        1/32670852        0/039801256        1/366509775     0/814820149         1/629640298
 6        10      0/254        72/6     57/902856      69/4834272       0/104225141     0/019802777      0/124027918       0/625350845        0/018760525         0/64411137     0/384069644         0/768139288
 7        12      0/3048     162/09    155/1318005    186/1581606       0/279237241     0/053055076      0/332292317       1/675423445        0/050262703        1/725686149     1/028989233         2/057978465
 8        20      0/508        83/4     133/033008    159/6396096       0/239459414     0/045497289      0/284956703       1/436756486        0/043102695        1/479859181     0/882407942         1/764815884
CDb(current density for bare pipe )= 30 mA/m2
CDc(current density for caoted pipe )= 0.3 mA/ m2
Desigen life= 25 Years                                                                 Total current demand                                                                    13/31                      A
Anode mass consumption rate = 0/1kg/A× Year , but                           Total current demand with 150% coefficient                                                         19/96024223                A
      assumed 0.25 kg/A× Year in base of soil
                    corrosiveness
                                                                                          (current demand*design life*consumption rate)
                                 Total Required Mass of Anode(kg) in base of                        (utilization factor*efficiency)                                      19/96*25*0.25
                                                                                                                                                                                                     499/0060557
                                              consumption(Kg)                                                                                                                0.5*0.5
                                                                                      19.96 (A) x 25 (Years) x .52(kg/A Year )/ (0.5 x 0.5)
                                                                       MC :
      DOCUMENT TITLE                            DOCUMENT NUMBER
REV. 00 Page 10 of 20
As above calculation 24 anode required to cover the 25 years anode consumption with 20 amperes
current demand.
Where:
ρ: resistivity of soil (ohm.cm); ρ=70.7 ohm.cm
L: Length of active column canister (m); L=2m
d: Diameter of canister (m); d=0.0.2m
Rb= 0.00159*70.7/2 (Ln (8×2/0.2)-1)=0.074(Ln80-1)=0.074×3.38= 0.324ohm
Where:
ρ: resistivity of backfill material; ρ= 50 ohm.cm
L: Length of anode (m); L=1.525m
d: Diameter of anode (m); d=0.051m
Ra= 0.00159*50/1.525 (Ln (8×1.525/0.051)-1)=0.052(Ln239.2 -1)=0.052×4.48=
0.234 ohm
Rg = 0.234+0.324=0.5648
Maximum acceptable ground bed resistance is 0.6 ohm so one anode covers the ground bed
resistance requisition.
                                                                          MC :
      DOCUMENT TITLE                      DOCUMENT NUMBER
REV. 00 Page 11 of 20
Considering coating quality is suppressed by the time, higher current demand is required in order
to grant sufficient structure protection during the expected life of (25 years) which has been
considered in the design.
NOTE 3: Details Calculation for Underground Pipelines is given in the clause 5.1.1.
According to the calculation 24 numbers of anodes is required to apply cathodic protection
to the external surface of the underground pipelines, but because of obtaining the
satisfactory ground bed resistance and also current distribution to pipes, the number of
anodes has been increased to 30
     Anode Distribution
Attenuation
                                                                             MC :
      DOCUMENT TITLE                             DOCUMENT NUMBER
REV. 00 Page 12 of 20
Attenuation coefficient:
       Where:
       RI : Pipeline lineal resistance
       Rt : Coating leakage resistivity
       α =√(0.0052/5.3)= √0.00038 =0.019
following table includes Attenuation Coefficient Calculation Results:
CLIENT:                                PROJECT:                                  CONTRACTOR:
                                                                               MC :
      DOCUMENT TITLE                               DOCUMENT NUMBER
REV. 00 Page 13 of 27
- Protective Length:
          Where:
          α : Attenuation coefficient of pipeline
          ΔUs : Change in pipeline potential at drain point due to application of impressed current
          ΔU0 : Change in pipeline potential at a point at distance Lmax due to application of
          impressed current.
          U0 : Pipeline native potential (-0.5V for steel).
          ΔUs = −1.2 − (−0.5) = −0.7V (refer to clause 4.4)
          ΔU0 = −0.85 − (−0.5) = − 0.35V (refer to clause 4.4)
          Lmax=1/0.0309 Ln( -0.7/-0.35- √( -0.7/-0.35)²-1)=32.36Ln2-√4-1=32.36Ln2-√3
          =32.36×o.27= 8.74 km
                                                                                          MC :
        DOCUMENT TITLE                               DOCUMENT NUMBER
REV. 00 Page 14 of 20
               Above calculation has been done for average equal pipeline with 4.34 inch diameter
               and 2897.11 m length, the calculation indicated that the CP system is adequate for
               8.74 km pipeline cathodic protection .So for protective pipes with average length of
               2897.11 m, is workable.
          Impressed current ground beds are designed to have a resistance that will permit current
          output with an impressed voltage within rating of D.C power supply to be used. Anodes are
          installed in distributed a shallow vertical ground beds to avoid risk of damage to the coating
          and poor distributed of protective current. Alternatively anodes may be installed in shallow
          vertical ground bed with different spacing. Where feasible, anode placement shall be
          designed to shallow discharge of nearly equal currents from all anodes in the ground bed.
          For (4) ground beds have been designed for protecting the pipelines, with same numbers of
          anodes : Five ground bed with 6 Nos anode with 1.5˷3 m spacing. ( In view of more safety
          and longevity of serviceable life of anodes , totally 30 Nos of Canister type High
          Silicon , Chrome Cast Iron anodes will be installed in the site).
          The most important parameter for ground bed design is the calculation of the total ground
          beds resistance.
          The resistance for each ground bed is:
Rbg = 0.00159ρ/NL[Ln8L/d-1+Ln0.656N]
          Rbg: anode canister to electrolyte resistance for a group of vertical anodes (ohms)
       L: Length (m) of backfill column length=2m
       N: Number of Anodes = 6
       ρ: Average backfill Resistivity=70.7 ohm.cm
       S: Anode Spacing= AVERAGE 1.5-3m
       d: Backfill Column Diameter (canister type)=0.2m
Rbg = 0.00159ρ/NL[Ln8L/d-1+Ln0.656N]
Rbg = 0.00159ρ/NL[Ln8L/d-1+Ln0.656N]=0.00159×70.7/6×2[Ln8× 2/ 0.2-1+Ln0.656 ×6]= 0.0322
CLIENT:                                PROJECT:                                                   CONTRACTOR:
                                                                                                  MC :
        DOCUMENT TITLE                                DOCUMENT NUMBER
REV. 00 Page 15 of 20
Rab = 0.00159ρ/NL[Ln8L/d-1+Ln0.656N]
             Rab: anode to backfill resistance for a group of vertical anodes (ohms)
     L:Anode Length (m) =1.525m
     N:Number of Anodes = 6
     ρ: Average backfill Resistivity=50 ohm.cm
     S:Anode Spacing= AVERAGE 1.5-3
     d:Anode Diameter (canister type)=0.051m
       Anode Weigth~22.5 Kg
Rbg = 0.00159ρ/NL[Ln8L/d-1+Ln0.656N]
Rab = 0.00159ρ/NL[Ln8L/d-1+Ln0.656N]=0.00159×50/6×1.525[Ln8× 1.525/ .051-1+Ln0.656 ×6] = 0.0508
Rmv = Rtg = Rbg + Rab = 0.0508+0.0322=0.083 Ω
       THEREFORE:
       Rmv2 = (according to the layout drawing with 6 Nos. Anodes) = 0.083 ohms
       Rmv3 = (according to the layout drawing with 6 Nos. Anodes) = 0.083 ohms
       Rmv5 = (according to the layout drawing with 6 Nos. Anodes) = 0.083 ohms
       Rmv6 = (according to the layout drawing with 6 Nos. Anodes) = 0.083 ohms
       Rmv9 = (according to the layout drawing with 6 Nos. Anodes) = 0.083 ohms
         CP Circuit Resistance
           The total electrical resistance of the cathodic protection circuit is included of three main
           resistances as follows:
                                                                                             MC :
      DOCUMENT TITLE                                       DOCUMENT NUMBER
                                                     2               2
              The resistance of 1x95mm and 1x35mm XLPE/PVC cable, which are used as circuit
              cable at 50˚C, are determined by the following formulas: Cable Length x 0.216 x
              0.001= Cable Resistance (1*95)
              Cable Length x 0.586 x 0.001= Cable Resistance (1*35)
                                                 Cable
                                     Item                      Cable Size   Positive Cable
                                               Length (m)
                                     2               31          1*35        AJB2-CCB1
                                     3               30          1*35        AJB3-CCB1
                                     4               15          1*35         CCB1-PBB
                                     6               33          1*35        AJB5-CCB2
                                     7               44          1*35        AJB6-CCB2
                                     8               40          1*35         CCB2-PBB
                                     11              58          1*35         AJB9-CCB
                                     12              72          1*35         CCB3-PBB
                                     13              110         1*95          PBB-TR
                                                 Cable
                                     Item                      Cable Size   Negative Cable
                                               Length (m)
                                      1              20          1*35        NBB-NCB1
                                      2              9           1*35        NCB1-NCB2
                                      3              8           1*35        NCB2-NCB3
                                      4              7           1*35        NCB3-NCB4
                                      5              17          1*35        NCB4-NCB5
                                      6              23          1*35        NCB5-NCB6
                                      7              9           1*35        NCB6-NCB7
                                      8              20          1*35        NCB7-NCB8
                                      9              13          1*35        NCB8-NCB9
                                     10              7           1*35       NCB9-NCB10
                                     11              24          1*35       NCB10-NCB11
                                     12              7           1*35       NCB11-NCB12
                                     13              11          1*35       NCB12-NCB13
                                     14              11          1*35       NCB13-NCB14
                                     15              62          1*35       NCB14-NCB15
CLIENT:                                   PROJECT:                                                  CONTRACTOR:
                                                                                                    MC :
      DOCUMENT TITLE                                      DOCUMENT NUMBER
                                                             REVIEW OF
                                                                THE
   Cathodic Protection Calculation                          CALCULATION
REV. 00 Page 17 of 20
                                                   Cable
                                     Item                      Cable Size           Negative Cable
                                                 Length (m)
                                     16              5             1*35             NCB15-NCB16
                                     17              5             1*35             NCB16-NCB17
                                     18              10            1*35             NCB17-NCB18
                                     19              17            1*35             NCB18-NCB19
                                     20              25            1*35              NCB19-NBB
                               21                  110             1*95                NBB-TR
      AJB: Anode Junction Box
      CCB: Current Control Box
      PBB: Positive Bond Box
      NCB: Negative Connection Box
      NBB: Negative Bond Box
      1/R=1/R1+1/R2=1/R3=1/R4+…………………+1/R19+1/R20=1/R21
      1/R*= 1/R2*+1/R3*+1/R4*+1/R6*+1/R7*+1/R8*+1/R11*+1/12*+1/R13*
      R1 ~ R21=Negative Cable Resistance
        *      *
      R1 ~ R13 =Positive Cable Resistance
      RN=Total Negative Cable Resistance
      RP=Total Positive Cable Resistance
                   2
      1*35 mm Cable resistance per unit length= 0.586Ω/km
       Cable resistance =cable length (m) x cable resistance per unit length (Ω/km) x 0.001
                                                                                   MC :
         DOCUMENT TITLE                            DOCUMENT NUMBER
REV. 00 Page 18 of 20
RN=1/R= 0.0029Ω
              RP=1/R*=0.0016Ω
                                                          Ω
R             R        R     R
    Total =    GBT +    N+     P
          Power supply requirements, namely current and voltage, are determined from the required
          current for protection of the structures and the calculated total circuit resistance. It must be
          considered that the actual power supply requirement should allow for future lodes, rectifier
          aging film formation and seasonal changes in the soil resistivity. Factor of 1.5 is considered
          for the capacitance of the selected Transformer / Rectifier.
                     T/R :
                     I=Current requirement=I =19.96Amps
                     R=Actual total circuit resistance =0.0211 Ω
              According to the client request we consider T/R with 100 volt, 125 Amperes capacity
              for considering load factor and worst weather conditions.
CLIENT:                              PROJECT:                                  CONTRACTOR:
                                                                               MC :
      DOCUMENT TITLE                            DOCUMENT NUMBER
REV. 00 Page 19 of 20
                                                                            MC :
      DOCUMENT TITLE                            DOCUMENT NUMBER
REV. 00 Page 20 of 20
Ia=It/Nmax.
Rc= (Ep-Ea) / Ia