L O A D D I S T R I B U T I O N S C H E D U L E
PANEL REFERENCE: DB-CH.R INCOMING C.B: 63A MCCB, 3-P ENCLOSURE MOUNTING: FLUSH
LOCATION: GROUND FLOOR INCOMING CABLE: 4Cx16+16mm² CU/XLPE/PVC NUMBER OF WAYS: 36 WAYS
VOLTAGE & FREQ: 380/220V,3-Ph,5-W,50Hz FED FROM: MDB-02 ACCESSORIES: INDECATOR LAMPS
PROTECTION DEGREE: IP42 S.C. RATING: 25KA BUSBAR: 80A,3PH+N+PE,CU
WIRE OR WIRE OR
NO. OF DESCRIPTION MCB RATING(AMP) DESCRIPTION NO. OF
WAYS LOCATION QTY VA/UNIT CABLE SIZE PHASE LOAD IN VA PHASE LOAD IN VA CABLE SIZE QTY VA/UNIT LOCATION
OF LOAD (mm2)
R Y B
(mm2) OF LOAD WAYS
R Y B R Y B
1 GROUND FLOOR LIGHTING 13 100 3*2.5 1300 16 16 1000 3*2.5 10 100 LIGHTING GROUND FLOOR 4
2 GROUND FLOOR LIGHTING 13 100 3*2.5 1300 16 16 1200 3*2.5 12 100 LIGHTING GROUND FLOOR 5
3 GROUND FLOOR LIGHTING 5 100 3*2.5 500 16 16 1300 3*2.5 13 100 LIGHTING GROUND FLOOR 6
7 GROUND FLOOR LIGHTING 5 100 3*2.5 500 16 16 600 3*3 3 200 N.SOCKETS GROUND FLOOR 10
8 GROUND FLOOR LIGHTING 13 100 3*2.5 1300 16 16 600 3*3 3 200 N.SOCKETS GROUND FLOOR 11
9 GROUND FLOOR N. SOCKETS 3 200 3*3 600 16 16 600 3*3 3 200 N.SOCKETS GROUND FLOOR 12
13 GROUND FLOOR N. SOCKETS 3 200 3*3 600 16 20 2500 3*6 1 2500 SP.U2 GROUND FLOOR 16
14 GROUND FLOOR N. SOCKETS 3 200 3*3 600 16 20 2500 3*6 1 2500 SP.U3 GROUND FLOOR 17
15 GROUND FLOOR SP.U1 1 2500 3*6 2500 20 20 2500 3*6 1 2500 SP.U4 GROUND FLOOR 18
19 416.67 416.67 22
20 GROUND FLOOR EX.F1 1 1250 4*4+4 416.67 20 20 416.67 4*4+4 1 1250 EX.F2 GROUND FLOOR 23
21 416.67 416.67 24
25 416.67 416.67 28
26 GROUND FLOOR EX.F3 1 1250 4*4+5 416.67 20 20 416.67 4*4+4 1 1250 EX.F4 GROUND FLOOR 29
27 416.67 416.67 30
31 SPARE 16 20 SPARE 34
32 SPARE 16 20 SPARE 35
33 SPARE 16 20 SPARE 36
3233.3 4033.3 4433.3 4933.3 5133.3 5233.3
SUBTOTALS ( KVA )
4933.3 5133.3 5233.3 ▬ ▬
63A MCCB, 3-P
TOTAL ( KVA ) ( CONNECTED ) 8166.7 9166.7 9666.7
TOTAL CONNECTED LOAD = 27.00 KVA
TOTAL DEMAND LOAD = 26 KVA LOAD STATEMENT LIGHTING N.SOCKET P.SOCKET AC E.W.H TOTAL
CONNECTED ( KVA ) 8.40 3.60 0.00 15.00 0.00 27.00
DEMAND FACTOR 1.00 0.60 0.70 1.00 0.60 0.95
DEMAND ( KVA ) 8.40 2.16 0.00 15.00 0.00 25.56
NOTES:
* CB TO BE EQUIPPED WITH EARTH LEAKAGE PROTECTION 30 Ma
L O A D D I S T R I B U T I O N S C H E D U L E
PANEL REFERENCE: EDB-CH.R INCOMING C.B: 40A MCCB, 3-P ENCLOSURE MOUNTING: FLUSH
LOCATION: GROUND FLOOR INCOMING CABLE: 4Cx10+10 mm² CU/XLPE/PVC NUMBER OF WAYS: 12 WAYS
VOLTAGE & FREQ: 380/220V,3-Ph,5-W,50Hz FED FROM: EMDB-02 ACCESSORIES: INDECATOR LAMPS
PROTECTION DEGREE: IP42 S.C. RATING: 10KA BUSBAR: 40A,3PH+N+PE,CU
WIRE OR WIRE OR
NO. OF DESCRIPTION MCB RATING(AMP) DESCRIPTION NO. OF
WAYS LOCATION QTY VA/UNIT CABLE SIZE PHASE LOAD IN VA PHASE LOAD IN VA CABLE SIZE QTY VA/UNIT LOCATION
OF LOAD (mm2)
R Y B
(mm2) OF LOAD WAYS
R Y B R Y B
1 GROUND FLOOR LIGHTING 8 100 3*3 800 16 16 700 3*3 7 100 LIGHTING GROUND FLOOR 4
2 GROUND FLOOR LIGHTING 9 100 3*3 900 16 16 500 3*3 5 100 LIGHTING GROUND FLOOR 5
3 GROUND FLOOR LIGHTING 5 100 3*3 500 16 16 900 3*3 9 100 LIGHTING GROUND FLOOR 6
7 GROUND FLOOR LIGHTING 7 100 3*3 700 16 16 SPARE 10
8 GROUND FLOOR LIGHTING 7 100 3*3 16 16 SPACE 11
9 SPARE 16 SPARE 12
1500 900 500 700 500 900
SUBTOTALS ( KVA )
700 500 900 ▬ ▬
40A MCCB, 3-P
TOTAL ( KVA ) ( CONNECTED ) 2200 1400 1400
TOTAL CONNECTED LOAD = 5.00 KVA
TOTAL DEMAND LOAD = 5 KVA LOAD STATEMENT LIGHTING N.SOCKET P.SOCKET AC E.W.H TOTAL
CONNECTED ( KVA ) 5.00 0.00 0.00 0.00 0.00 5.00
DEMAND FACTOR 1.00 0.60 1.00 1.00 0.60 1.00
DEMAND ( KVA ) 5.00 0.00 0.00 0.00 0.00 5.00
NOTES:
* CB TO BE EQUIPPED WITH EARTH LEAKAGE PROTECTION 30 Ma