Protect C60N circuit breakers 0
Circuit protection B, C and D curves
IEC 60898: 6000 A , IEC 60947-2: 10 kA
Function
b The circuit-breakers combine the following functions:
v protection of circuits against short-circuit currents
v protection of circuits against overload currents
v control
v isolation
v protection of persons against indirect contact with TN and IT neutral systems.
C60N circuit breakers are used in the tertiary and industrial sectors.
Tripping curves
24409 B curve
When the short-circuit currents are weak (generators, long cables).
b Power circuit:
v ratings: 1 to 63 A set at 30 °C
v tripping curve: the magnetic trip units operate between 3 and 5 In.
C curve
Cables feeding conventional loads.
b Power circuit:
v ratings: 0.5 to 63 A set at 30 °C
v tripping curve: the magnetic trip units operate between 5 and 10 In.
D curve
24591 Loads with high inrush currents (motors, transformers).
b Power circuit:
v ratings: 0.5 to 63 A set at 40 °C
v tripping curve: the magnetic trip units operate between 10 and 14 In.
Technical data according to IEC 60898
b Power circuit:
v voltage rating (Ue): 440 V AC
v breaking capacity:
- according to IEC 60898, Icn ultimate breaking capacity (O-CO cycle):
Rating (A) Type Voltage (V) Breaking capacity Icn (A)
0.5...63 1P 230/400 6000
2P, 3P, 3P+N, 4P 400 6000
24094 v limitation class (IEC 60898): 3.
Technical data according to IEC 60947-2
b Power circuit:
v voltage rating (Ue): 440 V AC
v impulse voltage (Uimp): 6 kV
v insulation voltage (Ui): 500 V AC
v breaking capacity:
- according to IEC 60947-2, Icu ultimate breaking capacity (O-CO cycle):
Rating (A) Type Voltage (V) Breaking capacity Icu (kA)
0.5...63 1P 230...240 10
400...415 3 (1)
2P, 3P, 3P+N, 4P 230...240 20
24027
400...415 10
(1) Breaking capacity under 1 pole with IT isolated neutral system (case of double fault).
Generals technical data
b Fast closing: allows the high inrush currents of some loads to be better held.
b Isolation with positive break indication: opening is indicated by a green strip on the
device operating handle. This indicator shows opening contacts of all the poles.
b Number of cycles (O-C): 20000.
b Environment:
v tropicalisation: treatment 2 (relative humidity: 95 % at 55 °C) according to
IEC 60068-1
v weight (g):
24631 Type 1P 2P 3P 4P
120 240 360 480
b Connection: tunnel terminals for the following cables:
v 16 mm2 flexible or 25 mm2 rigid up to 25 A ratings
v 25 mm2 flexible or 35 mm2 rigid for 32 to 63 A ratings.
version: 4.1 90078E.indd
Protect C60N circuit breakers 0
Circuit protection B, C and D curves
IEC 60898: 6000 A , IEC 60947-2: 10 kA
Catalogue numbers
Type Rating (A) Width Quantity Catalogue number
in mod. per batch
of 9 mm B curve C curve
1P
0.5 2 12 - 24067
1 2 12 24045 24395
2 2 12 24046 24396
3 2 12 24047 24397
4 2 12 24048 24398
6 2 12 24049 24399
10 2 12 24050 24401
16 2 12 24051 24403
20 2 12 24052 24404
25 2 12 24053 24405
32 2 12 24054 24406
40 2 12 24055 24407
50 2 12 24056 24408
63 2 12 24057 24409
2P
0.5 4 6 - 24068
1 4 6 24071 24331
2 4 6 24072 24332
3 4 6 24073 24333
4 4 6 24074 24334
6 4 6 24075 24335
10 4 6 24076 24336
16 4 6 24077 24337
20 4 6 24078 24338
25 4 6 24079 24339
32 4 6 24080 24340
40 4 6 24081 24341
50 4 6 24082 24342
63 4 6 24083 24343
3P
0.5 6 4 - 24069
1 6 4 24084 24344
2 6 4 24085 24345
3 6 4 24086 24346
4 6 4 24087 24347
6 6 4 24088 24348
10 6 4 24089 24349
16 6 4 24090 24350
20 6 4 24091 24351
25 6 4 24092 24352
32 6 4 24093 24353
40 6 4 24094 24354
50 6 4 24095 24355
63 6 4 24096 24356
3P + N
4 8 3 24383 -
6 8 3 24384 -
10 8 3 24386 -
13 8 3 24387 -
15 8 3 24415 -
16 8 3 24388 -
20 8 3 24389 -
25 8 3 24390 -
32 8 3 24391 -
40 8 3 24392 -
50 8 3 24393 -
63 8 3 24394 -
4P
0.5 8 3 - 24070
1 8 3 24097 24357
2 8 3 24098 24358
3 8 3 24099 24359
4 8 3 24100 24360
6 8 3 24101 24361
10 8 3 24102 24362
16 8 3 24103 24363
20 8 3 24104 24364
25 8 3 24105 24365
32 8 3 24106 24366
40 8 3 24107 24367
50 8 3 24108 24368
63 8 3 24109 24369
90078E.indd version: 4.1
Protect C60N circuit breakers 0
Circuit protection B, C and D curves
IEC 60898: 6000 A , IEC 60947-2: 10 kA
Connection
1 1 3 1 3 5
2 2 4 2 4 6
1P 2P 3P
1 3 5 7
2 4 6 8
3P + N 4P
version: 4.1 90078E.indd
Protect C60N circuit breakers 0
Circuit protection D curve
IEC 60947-2: 10 kA
Catalogue numbers
Type Rating (A) Width Quantity Catalogue
in mod. per batch number
of 9 mm D curve
1P
0.5 2 12 24493
1 2 12 24565
2 2 12 24566
3 2 12 24567
4 2 12 24568
6 2 12 24569
10 2 12 24571
16 2 12 24572
20 2 12 24573
25 2 12 24574
32 2 12 24575
40 2 12 24576
50 2 12 24578
63 2 12 24579
2P
0.5 4 6 24494
1 4 6 24580
2 4 6 24581
3 4 6 24582
4 4 6 24583
6 4 6 24584
10 4 6 24586
16 4 6 24587
20 4 6 24588
25 4 6 24589
32 4 6 24590
40 4 6 24591
50 4 6 24593
63 4 6 24594
3P
0.5 6 4 24495
1 6 4 24595
2 6 4 24596
3 6 4 24597
4 6 4 24598
6 6 4 24599
10 6 4 24601
16 6 4 24602
20 6 4 24603
25 6 4 24604
32 6 4 24605
40 6 4 24606
50 6 4 24608
63 6 4 24609
4P
0.5 8 3 24496
1 8 3 24610
2 8 3 24611
3 8 3 24612
4 8 3 24613
6 8 3 24614
10 8 3 24616
16 8 3 24617
20 8 3 24618
25 8 3 24619
32 8 3 24620
40 8 3 24621
50 8 3 24623
63 8 3 24624
90078E.indd version: 4.1
Protect C60N circuit breakers 0
Circuit protection D curve
IEC 60947-2: 10 kA
Connection
1 1 3 1 3 5
2 2 4 2 4 6
1P 2P 3P
1 3 5 7
2 4 6 8
4P
Additional information
Vigi modules: page 90116
Electrical auxiliaries: page 90142
Accessories: page 91903
Dimensions: page 90148
Curves: page 90180