Schneider Electric C60N

C60N circuit breakers are used in tertiary and industrial sectors for circuit protection. They provide protection against short-circuits, overloads, and allow for control, isolation, and protection against indirect contact. They are available in 1P, 2P, 3P, 3P+N, and 4P configurations with B, C, and D tripping curves for various current ratings from 0.5A to 63A. Technical data includes voltage rating up to 440V AC, breaking capacity up to 10kA, fast closing, positive break indication, and 20000 operations.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
758 views5 pages

Schneider Electric C60N

C60N circuit breakers are used in tertiary and industrial sectors for circuit protection. They provide protection against short-circuits, overloads, and allow for control, isolation, and protection against indirect contact. They are available in 1P, 2P, 3P, 3P+N, and 4P configurations with B, C, and D tripping curves for various current ratings from 0.5A to 63A. Technical data includes voltage rating up to 440V AC, breaking capacity up to 10kA, fast closing, positive break indication, and 20000 operations.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

Protect C60N circuit breakers 0

Circuit protection B, C and D curves


IEC 60898: 6000 A , IEC 60947-2: 10 kA

Function
b The circuit-breakers combine the following functions:
v protection of circuits against short-circuit currents
v protection of circuits against overload currents
v control
v isolation
v protection of persons against indirect contact with TN and IT neutral systems.
C60N circuit breakers are used in the tertiary and industrial sectors.

Tripping curves
24409 B curve
When the short-circuit currents are weak (generators, long cables).
b Power circuit:
v ratings: 1 to 63 A set at 30 °C
v tripping curve: the magnetic trip units operate between 3 and 5 In.

C curve
Cables feeding conventional loads.
b Power circuit:
v ratings: 0.5 to 63 A set at 30 °C
v tripping curve: the magnetic trip units operate between 5 and 10 In.

D curve
24591 Loads with high inrush currents (motors, transformers).
b Power circuit:
v ratings: 0.5 to 63 A set at 40 °C
v tripping curve: the magnetic trip units operate between 10 and 14 In.

Technical data according to IEC 60898


b Power circuit:
v voltage rating (Ue): 440 V AC
v breaking capacity:
- according to IEC 60898, Icn ultimate breaking capacity (O-CO cycle):
Rating (A) Type Voltage (V) Breaking capacity Icn (A)
0.5...63 1P 230/400 6000
2P, 3P, 3P+N, 4P 400 6000
24094 v limitation class (IEC 60898): 3.

Technical data according to IEC 60947-2


b Power circuit:
v voltage rating (Ue): 440 V AC
v impulse voltage (Uimp): 6 kV
v insulation voltage (Ui): 500 V AC
v breaking capacity:
- according to IEC 60947-2, Icu ultimate breaking capacity (O-CO cycle):
Rating (A) Type Voltage (V) Breaking capacity Icu (kA)
0.5...63 1P 230...240 10
400...415 3 (1)
2P, 3P, 3P+N, 4P 230...240 20
24027
400...415 10
(1) Breaking capacity under 1 pole with IT isolated neutral system (case of double fault).

Generals technical data


b Fast closing: allows the high inrush currents of some loads to be better held.
b Isolation with positive break indication: opening is indicated by a green strip on the
device operating handle. This indicator shows opening contacts of all the poles.
b Number of cycles (O-C): 20000.
b Environment:
v tropicalisation: treatment 2 (relative humidity: 95 % at 55 °C) according to
IEC 60068-1
v weight (g):
24631 Type 1P 2P 3P 4P
120 240 360 480
b Connection: tunnel terminals for the following cables:
v 16 mm2 flexible or 25 mm2 rigid up to 25 A ratings
v 25 mm2 flexible or 35 mm2 rigid for 32 to 63 A ratings.

 version: 4.1 90078E.indd


Protect C60N circuit breakers 0

Circuit protection B, C and D curves


IEC 60898: 6000 A , IEC 60947-2: 10 kA

Catalogue numbers
Type Rating (A) Width Quantity Catalogue number
in mod. per batch
of 9 mm B curve C curve
1P
0.5 2 12 - 24067
1 2 12 24045 24395
2 2 12 24046 24396
3 2 12 24047 24397
4 2 12 24048 24398
6 2 12 24049 24399
10 2 12 24050 24401
16 2 12 24051 24403
20 2 12 24052 24404
25 2 12 24053 24405
32 2 12 24054 24406
40 2 12 24055 24407
50 2 12 24056 24408
63 2 12 24057 24409
2P
0.5 4 6 - 24068
1 4 6 24071 24331
2 4 6 24072 24332
3 4 6 24073 24333
4 4 6 24074 24334
6 4 6 24075 24335
10 4 6 24076 24336
16 4 6 24077 24337
20 4 6 24078 24338
25 4 6 24079 24339
32 4 6 24080 24340
40 4 6 24081 24341
50 4 6 24082 24342
63 4 6 24083 24343
3P
0.5 6 4 - 24069
1 6 4 24084 24344
2 6 4 24085 24345
3 6 4 24086 24346
4 6 4 24087 24347
6 6 4 24088 24348
10 6 4 24089 24349
16 6 4 24090 24350
20 6 4 24091 24351
25 6 4 24092 24352
32 6 4 24093 24353
40 6 4 24094 24354
50 6 4 24095 24355
63 6 4 24096 24356
3P + N
4 8 3 24383 -
6 8 3 24384 -
10 8 3 24386 -
13 8 3 24387 -
15 8 3 24415 -
16 8 3 24388 -
20 8 3 24389 -
25 8 3 24390 -
32 8 3 24391 -
40 8 3 24392 -
50 8 3 24393 -
63 8 3 24394 -
4P
0.5 8 3 - 24070
1 8 3 24097 24357
2 8 3 24098 24358
3 8 3 24099 24359
4 8 3 24100 24360
6 8 3 24101 24361
10 8 3 24102 24362
16 8 3 24103 24363
20 8 3 24104 24364
25 8 3 24105 24365
32 8 3 24106 24366
40 8 3 24107 24367
50 8 3 24108 24368
63 8 3 24109 24369

90078E.indd version: 4.1 


Protect C60N circuit breakers 0

Circuit protection B, C and D curves


IEC 60898: 6000 A , IEC 60947-2: 10 kA

Connection
1 1 3 1 3 5

2 2 4 2 4 6

1P 2P 3P

1 3 5 7

2 4 6 8

3P + N 4P

 version: 4.1 90078E.indd


Protect C60N circuit breakers 0

Circuit protection D curve


IEC 60947-2: 10 kA

Catalogue numbers
Type Rating (A) Width Quantity Catalogue
in mod. per batch number
of 9 mm D curve
1P
0.5 2 12 24493
1 2 12 24565
2 2 12 24566
3 2 12 24567
4 2 12 24568
6 2 12 24569
10 2 12 24571
16 2 12 24572
20 2 12 24573
25 2 12 24574
32 2 12 24575
40 2 12 24576
50 2 12 24578
63 2 12 24579
2P
0.5 4 6 24494
1 4 6 24580
2 4 6 24581
3 4 6 24582
4 4 6 24583
6 4 6 24584
10 4 6 24586
16 4 6 24587
20 4 6 24588
25 4 6 24589
32 4 6 24590
40 4 6 24591
50 4 6 24593
63 4 6 24594
3P
0.5 6 4 24495
1 6 4 24595
2 6 4 24596
3 6 4 24597
4 6 4 24598
6 6 4 24599
10 6 4 24601
16 6 4 24602
20 6 4 24603
25 6 4 24604
32 6 4 24605
40 6 4 24606
50 6 4 24608
63 6 4 24609
4P
0.5 8 3 24496
1 8 3 24610
2 8 3 24611
3 8 3 24612
4 8 3 24613
6 8 3 24614
10 8 3 24616
16 8 3 24617
20 8 3 24618
25 8 3 24619
32 8 3 24620
40 8 3 24621
50 8 3 24623
63 8 3 24624

90078E.indd version: 4.1 


Protect C60N circuit breakers 0

Circuit protection D curve


IEC 60947-2: 10 kA

Connection
1 1 3 1 3 5

2 2 4 2 4 6

1P 2P 3P

1 3 5 7

2 4 6 8

4P

Additional information
Vigi modules: page 90116
Electrical auxiliaries: page 90142
Accessories: page 91903
Dimensions: page 90148
Curves: page 90180

 version: 4.1 90078E.indd