0% found this document useful (0 votes)
64 views192 pages

PCL1/PCM1 G/PCM1 M

This document provides information about connection, functions, and operation of automatic control systems for emergency power and isolated operations parallel with the mains. Section 1 discusses safety, connections for power supply, inputs/outputs, and diagrams. Section 2 describes functional aspects like control inputs/outputs, startup/stopping processes, circuit breaker operation, monitoring, logic, emergency power functions, and load sharing. The document contains detailed information about configuration and use of the control systems.

Uploaded by

Hari Haran
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
64 views192 pages

PCL1/PCM1 G/PCM1 M

This document provides information about connection, functions, and operation of automatic control systems for emergency power and isolated operations parallel with the mains. Section 1 discusses safety, connections for power supply, inputs/outputs, and diagrams. Section 2 describes functional aspects like control inputs/outputs, startup/stopping processes, circuit breaker operation, monitoring, logic, emergency power functions, and load sharing. The document contains detailed information about configuration and use of the control systems.

Uploaded by

Hari Haran
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 192

PCL1/PCM1-G/PCM1-M

Automatic control/Gen-set control for emergency power


and isolated operations/operations parallel with the mains
Version 4.3
Contents Page

1 Introduction .................................................................................................................................... 6
1.1 Safety technical note for the user..................................................................................................................... 6
1.2 Connection of the item.................................................................................................................................. 7
1.2.1 Power supply ....................................................................................................................................... 7
1.2.2 Measuring inputs .................................................................................................................................. 8
1.2.3 Auxiliary and control inputs................................................................................................................... 10
1.2.4 Auxiliary and control outputs ................................................................................................................. 14
1.2.5 Controller outputs (standard/option ..-A) .............................................................................................. 15
1.2.6 Interface [PCL1/H & PCM1x] ............................................................................................................ 18
1.2.7 Loop The CAN Bus ............................................................................................................................. 19
1.3 Connection diagram .................................................................................................................................. 20
1.3.1 Version PCL1/L .................................................................................................................................. 20
1.3.2 Version PCL1/H................................................................................................................................. 21
1.3.3 Version PCM1-G/L ............................................................................................................................. 22
1.3.4 Version PCM1-G/H-I .......................................................................................................................... 23
1.3.5 Version PCM1-G/H-E ......................................................................................................................... 24
1.3.6 Version PCM1-M/L............................................................................................................................. 25
1.3.7 Version PCM1-M/H ........................................................................................................................... 26
2 Functional description.................................................................................................................... 27
2.1 What must one pay attention to in the event of ... ............................................................................................ 27
2.1.1 ... different options.............................................................................................................................. 27
2.1.2 ... systems with one power circuit breaker ............................................................................................... 27
2.2 Table of setpoint values............................................................................................................................... 27
2.3 Control inputs............................................................................................................................................ 28
2.4 Control outputs .......................................................................................................................................... 31
2.5 Text in the display ...................................................................................................................................... 33
2.5.1 Item messages in the display................................................................................................................. 33
2.5.2 Alarm messages in the display .............................................................................................................. 35
2.6 Description starting/stopping process ............................................................................................................ 37
2.6.1 Diesel engine..................................................................................................................................... 37
2.6.2 Gas engine ....................................................................................................................................... 39
2.7 Operation of the power circuit breaker .......................................................................................................... 41
2.7.1 Synchronization of the GCB ................................................................................................................. 41
2.7.2 Closing the GCB without synchronization (GCB black start) ....................................................................... 42
2.7.3 Synchronization of the MCB [PCL1/PCM1-M] ...................................................................................... 43
2.7.4 Closing the MCB without synchronization (MCB black start) [PCL1 / PCM1-M] ............................................ 44
2.7.5 Open GCB ....................................................................................................................................... 45
2.7.6 Open MCB [PCL1/PCM1-M] ............................................................................................................ 45
2.7.7 GCB Pulse/Continuous Pulse ................................................................................................................ 46
2.8 Monitoring power circuit breakers ................................................................................................................. 47
2.8.1 Breaker connect time monitoring ............................................................................................................ 47
2.8.2 Circuit breaker monitoring .................................................................................................................... 47
2.9 Power circuit breaker logic .......................................................................................................................... 48
2.9.1 CB logic "PARALLEL" [PCM1x] .............................................................................................................. 48
2.9.2 CB logic "INTERCHANGE" [PCM1-M] ................................................................................................. 49
2.9.3 CB logic "CLOSED TRANSIT." [PCL1/PCM1-M] .................................................................................... 49
2.9.4 CB logic "OPEN TRANSIT." [PCL1/PCM1-M] ....................................................................................... 49
2.9.5 CB logic "EXTERNAL" .......................................................................................................................... 50
2.10 Emergency power [PCL1/PCM1-M] ....................................................................................................... 50
2.10.1 Emergency power with "PARALLEL" CB logic [PCM1-M] ............................................................................ 51
2.10.2 Emergency power with "OPEN TRANSIT." CB logic .................................................................................. 51
2.10.3 Emergency power with "CLOSED TRANSIT." CB logic ............................................................................... 51
2.10.4 Emergency power with "INTERCHANGE" CB logic [PCM1-M] .................................................................. 52
2.10.5 Emergency power with "EXTERNAL" CB logic ........................................................................................... 52
2.10.6 Emergency power with MCB malfunction ................................................................................................ 52
2.11 Sprinkler operation ................................................................................................................................. 53
2.12 Direction of power ................................................................................................................................. 54
2.13 Analog controller outputs (option ..-A) ....................................................................................................... 55
2.13.1 Controller setting ................................................................................................................................ 56

2 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
2.14 Load and/or var sharing [PCM1x] ........................................................................................................... 58
2.14.1 Load/var sharing via the CAN bus ........................................................................................................ 59
2.15 Language manager ................................................................................................................................ 60
2.16 Connection to external components ........................................................................................................... 61
2.16.1 Pickup input....................................................................................................................................... 61
2.16.2 Speed governor ................................................................................................................................. 61
2.16.3 Digital I/O expansion board EM1-D [PCM1x] ....................................................................................... 61
2.17 Alarms ................................................................................................................................................. 62
2.17.1 Alarm classes..................................................................................................................................... 62
2.17.2 Internally detected alarms ..................................................................................................................... 63
2.17.3 Alarm acknowledgement...................................................................................................................... 64
3 Display elements and push-buttons ............................................................................................... 66
3.1 Pressure-sensitive front membrane .................................................................................................................. 66
3.1.1 PCL1 & PCM1-M ............................................................................................................................... 66
3.1.2 PCM1-G........................................................................................................................................... 66
3.1.3 Short description of LEDs and push-buttons ............................................................................................... 67
3.1.4 Overview of key functions .................................................................................................................... 68
3.2 LEDs ........................................................................................................................................................ 69
3.3 Push-buttons .............................................................................................................................................. 70
3.3.1 Display touch..................................................................................................................................... 70
3.3.2 Operation of the power circuit breakers .................................................................................................. 72
3.3.3 Operating mode selector switch ............................................................................................................ 72
3.4 Display .................................................................................................................................................... 74
4 Configuration screens (input of the parameters) ........................................................................ 75
4.1 Load basic values ...................................................................................................................................... 76
4.2 Version number ......................................................................................................................................... 76
4.3 Password protection ................................................................................................................................... 76
4.4 Direct configuration .................................................................................................................................... 77
4.5 Generator number ..................................................................................................................................... 77
4.6 Load language.......................................................................................................................................... 78
4.7 Service display.......................................................................................................................................... 78
4.8 Event logging [PCM1x..-H-..] ..................................................................................................................... 79
4.8.1 Internal events and discrete inputs .......................................................................................................... 80
4.8.2 Analog inputs .................................................................................................................................... 81
4.9 Basic settings configuration .......................................................................................................................... 82
4.9.1 Generator and mains environment ......................................................................................................... 82
4.9.2 Transformer and measuring variables...................................................................................................... 84
4.9.3 Mains Current/Mains Power Measurement ............................................................................................. 85
4.9.4 Changing passwords .......................................................................................................................... 87
4.10 Controller configuration ........................................................................................................................... 87
4.10.1 Constant and interchange (import/export) power controller [PCM1x] .......................................................... 88
4.10.2 Frequency controller ............................................................................................................................ 89
4.10.3 Voltage controller ............................................................................................................................... 92
4.10.4 Power-factor controller [PCM1x] ........................................................................................................... 95
4.10.5 Real power controller [PCM1x] ............................................................................................................ 96
4.10.6 Load/var sharing [PCM1x] ................................................................................................................. 99
4.11 Load management configuration [PCM1x] ............................................................................................... 100
4.11.1 Load-dependent start/stop in operation in parallel .................................................................................. 100
4.11.2 Temperature dependent start/stop [PCM1x/H] .................................................................................... 107
4.11.3 Stop of the engine at mains failure [PCM1-G] ........................................................................................ 108
4.11.4 Remote control via interface - Guidance bus [PCx/H] ............................................................................ 109
4.11.5 Power circuit breaker configuration ...................................................................................................... 110
4.11.6 Power circuit breaker logic ................................................................................................................. 110
4.11.7 GCB pulse/continuous pulse .............................................................................................................. 113
4.11.8 Synchronization................................................................................................................................ 113
4.11.9 Synchronization time monitoring .......................................................................................................... 114
4.11.10 Dead start ................................................................................................................................... 115
4.11.11 Circuit breaker monitoring (switch pulses)......................................................................................... 116
4.11.12 Mains decoupling ......................................................................................................................... 117
4.12 Emergency power configuration [PCL1 & PCM1-M] ................................................................................. 118

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 3
4.13 Watchdog configuration ....................................................................................................................... 119
4.13.1 Generator power monitoring............................................................................................................... 120
4.13.2 Mains power monitoring [PCM1x] ..................................................................................................... 121
4.13.3 Generator overload monitoring ........................................................................................................... 122
4.13.4 Generator reverse/reduced power monitoring ....................................................................................... 123
4.13.5 Load imbalance monitoring ................................................................................................................ 123
4.13.6 Generator overcurrent monitoring......................................................................................................... 124
4.13.7 Generator frequency monitoring .......................................................................................................... 125
4.13.8 Generator voltage monitoring ............................................................................................................. 126
4.13.9 AMF (emergency power) limits [PCL1] ................................................................................................. 127
4.13.10 Mains frequency monitoring [PCM1x] ............................................................................................. 128
4.13.11 Mains voltage monitoring [PCM1x]................................................................................................. 129
4.13.12 Phase/vector shift monitoring [PCM1x] ............................................................................................ 130
4.14 Mains settling time................................................................................................................................ 131
4.14.1 Battery voltage monitoring .................................................................................................................. 131
4.14.2 Time of active horn ........................................................................................................................... 131
4.15 Discrete input configuration .................................................................................................................... 132
4.15.1 Setting the alarm inputs...................................................................................................................... 132
4.15.2 Setting of the texts of the alarm inputs ................................................................................................... 134
4.15.3 Setting the control inputs .................................................................................................................... 135
4.15.4 Adjust function of terminal 6................................................................................................................ 136
4.16 Analog inputs configuration.................................................................................................................... 137
4.16.1 Setting the analog inputs .................................................................................................................... 138
4.16.2 Measuring range monitoring ............................................................................................................... 140
4.16.3 Analog input delay using the delayed engine speed ............................................................................... 141
4.16.4 Analog inputs selectable as control inputs.............................................................................................. 141
4.17 Configure outputs ................................................................................................................................. 142
4.17.1 Analog outputs................................................................................................................................. 142
4.17.2 Relay manager................................................................................................................................. 143
4.17.3 Relay outputs programming in the PCx .................................................................................................. 143
4.17.4 Relay outputs programming in the EM1-D .............................................................................................. 144
4.18 Engine configuration ............................................................................................................................. 144
4.18.1 Auxiliaries ....................................................................................................................................... 144
4.18.2 Engine type definition ........................................................................................................................ 145
4.18.3 Coasting, delayed engine monitoring and firing speed ............................................................................ 147
4.18.4 Pickup ............................................................................................................................................ 148
4.19 Counter configuration............................................................................................................................ 148
4.19.1 Maintenance call.............................................................................................................................. 149
4.19.2 Operating hour counter...................................................................................................................... 149
4.19.3 Set start counter................................................................................................................................ 150
4.19.4 kWh counter.................................................................................................................................... 150
4.19.5 Real time clock [PCM1x/H] ............................................................................................................. 151
4.19.6 Current slave pointer ......................................................................................................................... 152
4.20 Engine bus [PCMx] ............................................................................................................................. 153
4.20.1 EM1-D – Digital Expansion Board........................................................................................................ 153
4.20.2 Lambda controller 'PCR3' ................................................................................................................... 153
4.20.3 Engine control 'General' .................................................................................................................... 154
5 Commissioning............................................................................................................................ 158
6 Appendix.................................................................................................................................... 160
6.1 Analog output manager ............................................................................................................................ 160
6.2 Relay manager (list of parameters with explanations) ................................................................................. 162
6.3 Interface [PCL1/H & PCM1x] ................................................................................................................. 165
6.3.2 Transmission telegram........................................................................................................................ 165
6.3.3 Receiving telegram ........................................................................................................................... 176
6.3.4 Notes (on interface)......................................................................................................................... 176
6.4 Measured quantities and technical data ....................................................................................................... 177
6.4.1 Measured quantities.......................................................................................................................... 177
6.4.2 Technical data ................................................................................................................................. 178
6.5 Dimensions ............................................................................................................................................. 180
7 Parameter list ............................................................................................................................. 181
8 Index .......................................................................................................................................... 190

4 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
NOTE

With the exception of the following differences, the versions described in this manual are completely
identical:
Described products
PCL1 Genset control with two circuit breakers without operation in mains parallel.
PCM1-G Genset control with one circuit breaker for operation in mains parallel.
PCM1-M Genset control with two circuit breakers for operation in mains parallel.
Code of types:

PCx-Ia-Ub-y1-y2-z
[x = L1/M1-G/M1-M] Item type PCL1, PCM1-G and PCM1-M
[y1 = L/H] Variations Low-/High-Variation
[y2 = I/E] Variations {PCM1-G} internal/external voltage tracing
[z = A] Analog controller output selectable
[a = 1/5] Current measuring, prim. 1 = ../1 A; 5 = ../5 A
[b = ¼] Voltage measuring, prim. 1 = 100 Vac; 4 = 400 Vac
xxx/L Low variation of one type ([xxx = PCL/PCM]; e.g. PCL1/L, PCM1-G/L or PCM1-M/L)
xxx/H High variation of one type ([xxx = PCL/PCM]; e.g. PCL1/H, PCM1-G/H or PCM1-M/H).

NOTE

These manual have been developed for an item fitted with all available options. Inputs/outputs, functions,
configuration screens and other details described, which do not exist on your item may be ignored.

CAUTION !

The present manual has been prepared to enable the installation and commissioning of the item. On
account of the large variety of parameter settings, it is not possible to cover every possible combination.
The manual are therefore only a guide. In case of incorrect entries or a total loss of functions, the default
settings can be taken from the enclosed list of parameters.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 5
1 Introduction

1.1 Safety technical note for the user

This documentation contains the relevant information for the normal use of the product de-
scribed herein. It is intended to be read by qualified staff.

Danger notice The following instructions are useful for both personal safety and safety from damage to the
described product or items connected to it. Safety notes and warnings to avoid any danger
to the life and health of users or maintenance staff and to avoid any damage to property
will be identified in this documentation by means of the symbols and terms defined in the
following. Within the framework of this documentation, the signals and terms which are
used have the following meaning:

DANGER!!!

The DANGER symbol draws your attention to dangers while the description indicates how to handle
and/or avoid such hazards. Any non-observance may cause fatal or serious injuries as well as
considerable damage to property.

WARNING!

To avoid the destruction of electric components due to improper handling, please read and adhere to the
relevant notes.

CAUTION!

This symbol points to important notes concerning the mounting, installation, and connection of the item.
These notes should absolutely be observed when connecting the item.

NOTE

References to other notes and supplements as well as tables and lists are identified by means of the "I"
symbol. Most of the referenced sections are included in the Annex.

Normal use The item must only be operated for the uses described in this manual. The prerequisite for a
proper and safe operation of the product is correct transportation, storage, and installation
as well as careful operation and maintenance.

6 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
1.2 Connection of the item

WARNING

A circuit breaker must be provided near to the item and in a position easily accessible to the operator. This
must also bear a sign identifying it as an isolating switch for the item.

NOTE

Connected inductances (e. g. Coils of operating current or undervoltage tripping devices, auxiliary
contactors and power contactors) must be wired with an appropriate interference protection.

1.2.1 Power supply

9.5..32 V DC
D1 = P600M
for 12 V DC systems C1 = 47.000 uF / 40 V
0V

2
C1 Power supply
9.5..32 V DC

1
9.5..32 V DC (in normal operation)
D1 (min. 12 V DC to start)
N

0
Terminal Description Amax
0 Neutral point of the three-phase system or neutral terminal of the voltage Solder
transformer (Measuring reference point) lug
1 9,5..32 V DC, 15 W 2.5 mm²
2 0 V reference point 2.5 mm²

Note: On use in a 12 Vdc system, please wire the power supply as described above.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 7
1.2.2 Measuring inputs

a.) Voltage measuring inputs


• Generator
MCB GCB
L1
L2
L3
G
N

0 20 21 22
L3
L2
Generator voltage
L1
N

Terminal Measurement Description Amax


20 400 V direct or Generator voltage L1 2.5 mm²
21 via ../100 V Generator voltage L2 2.5 mm²
22 measurement Generator voltage L3 2.5 mm²
0 transducer Neutral point of the 3-phase system/transformer Sold. lug

• Bus bar
MCB GCB
L1
L2
L3
G
N

23 24
L2
Busbar voltage
L1

Terminal Measurement Description Amax


23 400 V direct or Busbar voltage L1 2.5 mm²
24 ../100 V Busbar voltage L2 2.5 mm²

• Mains
MCB GCB
L1
L2
L3
G
N
50 51 52

L3
L2 Mains voltage
L1

Terminal Measurement Description Amax


50 400 V direct or Mains voltage L1 2.5 mm²
51 via ../100 V Mains voltage L2 2.5 mm²
52 measurement Mains voltage L3 2.5 mm²
0 transducer Neutral point of the 3-phase system / transformer Sold.lug

8 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
b.) Current measuring inputs

WARNING !

Before disconnecting the secondary terminals of the transformer or the connections of the transformer at the
item, make sure that the transformer is short-circuited.

• Generator
MCB GCB
L1
L2
L3
G
N

Detail:
Connection of the transducers
S2 S1
L.. G
s2 s1

s1 (k)

25 26 29 30 31 32
L3
s2 (l)
Generator
s1 (k) s1 (k) current

..
L.. L2
s2 (l) s2 (l)
.. s1 (k) ../1 A or ../5 A
L1
s2 (l)

Terminal Measurement Description Amax


25 Generator current L1, transformer terminal s2 (l) 2.5 mm²
26 Transformer Generator current L1, transformer terminal s1 (k) 2.5 mm²
29 ../1 A Generator current L2, transformer terminal s2 (l) 2.5 mm²
30 or Generator current L2, transformer terminal s1 (k) 2.5 mm²
31 ../5 A Generator current L3, transformer terminal s2 (l) 2.5 mm²
32 Generator current L3, transformer terminal s1 (k) 2.5 mm²

• Mains [PCM1x]

S2 S1
MCB GCB
L1

G
s2 s1
L2
L3
N

27 28
s1 (k) Mains current
L1
s2 (l) ../1A or ../5 A

Terminal Measurement Description Amax


27 Transformer Mains current L1, transformer terminal s2 (l) 2.5 mm²
28 ../1 A ../5 A Mains current L1, transformer terminal s1 (k) 2.5 mm²

• Mains [PCM1x] 20 mA configured as mains real power actual value measuring

MCB GCB
L1
L2
L3
G
N

Measuring transducer

-
27 28

Mains active power


+ 0/4..20 mA

Terminal Measurement Description Amax


Mains real power actual value measurement via 1.5 mm²
Analog signal 0/4..20 mA signal of an external measuring trans-
configurable
0/4..20 mA ducer

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 9
1.2.3 Auxiliary and control inputs

a.) Discrete inputs

WARNING !

Please note that the maximum voltages which may be applied at the discrete inputs are defined as follows.
Voltages higher than those specified destroy the hardware!
4..40 Vdc.

• Control inputs
+/-4..40 Vdc

Signal device

B A
Discrete input
Reply CB 3

D C
Discrete input

Terminal Associated Description Amax


Common (according to DIN 40 719 Part 3, 5.8.3)
A B NO contact
3 Automatic 1 2.5 mm²
5 Automatic 2 2.5 mm²
Multi function: Sprinkler operation / Engine enable
6 external acknowledgement / Engine stop / 2.5 mm²
7
STOP mode / start without CB
53 [PCM1-G] Enable externally 2.5 mm²
[PCM1-M & PCL1] Enable MCB (mains power circuit
breaker)
C D NC contact
4 Reply: Generator power circuit breaker is open 2.5 mm²
7 [PCM1-G] Status: Isolated operation
54 2.5 mm²
[PCM1-M & PCL1] Reply: MCB is open

10 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
The discrete inputs can be connected in positive or negative logic:

Positive logic The discrete input is wired to +/-24 Vdc.


Negative logic The discrete input is wired to GND.

• Alarm inputs (positive logic)


+/-4..40 Vdc
Signal device

B A
Discrete input

Terminal Associated Description Amax


Common (according to DIN 40 719 Part 3, 5.8.3)
A B Normally open contact
61 Discrete input 1 2.5 mm²
(if sprinkler = EMERGENCY STOP)
62 Discrete input 2 or 2.5 mm²
Control input "Dynamo”
63 Discrete input 3 or 2.5 mm²
Control input "Operation mode selector blocked”
64 Alarm input 4 or 2.5 mm²
Control input "CB logic”
65 Alarm input 5 2.5 mm²
66 60 Alarm input 6 or 2.5 mm²
Control input “Manual synchronization”
67 Alarm input 7 or Control input “Close GCB without 2.5 mm²
delayed engine monitoring”
68 Alarm input 8 2.5 mm²
69 Alarm input 9 2.5 mm²
70 Alarm input A 2.5 mm²
71 Alarm input B 2.5 mm²
72 Alarm input C 2.5 mm²
73 Alarm input D 2.5 mm²
125 Alarm input E 2,5 mm²
126 124 Alarm input F only PCM1x 2,5 mm²
127 Alarm input G only PCM1x 2,5 mm²

Example for negative logic


+/-4..40 Vdc
B A

Discrete input
Signal device

Associated Terminal Description Amax


Common (according to DIN 40 719 Part 3, 5.8.3)
A B Normally open contact
61 Alarm input 1 (sprinkler = EMERGENCY STOP) 2.5 mm²
60 62 Alarm input 2 2.5 mm²
63 Alarm input 3 2.5 mm²

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 11
b.) Analog inputs

C B A
Analog input
Pt100
only at Pt100

Ia

C B A
Analog input
GND
0/4..20 mA

Terminal Description Amax


A B C
93 94 95 Analog input 1 - Pt100 1.5 mm²
96 97 98 Analog input 2 - Pt100 1.5 mm²
99 100 101 Analog input 3 - 20 mA; 1.5 mm²
configurable function:
- Alarm input,
- Set value generator power,
- Actual value mains interchange power
102 103 104 Analog input 4 - Pt100 1.5 mm²
105 106 107 Analog input 5 - Pt100 only PCM1x/H 1.5 mm²
108 109 110 Analog input 6 - Pt100 only PCM1x/H 1.5 mm²
111 112 113 Analog input 7 - 20 mA; only PCM1x/H 1.5 mm²
configurable function:
- Alarm input,
- Set value generator power,
- Actual value mains interchange power

12 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
c.) Pickup input

92 91 90
sw./ind.
24 V Pickup
< 1.0 V GND
swiching/inductive

Terminal Description Amax


90 switching/inductive 2.5 mm²
91 Pickup 2.5 mm²
92 GND 2.5 mm²

Specification of the input circuit for inductive speed sensors

Ambient temperature: 25 °C

Signal shape Sinusoidal


Minimum input voltage of 200 ..10,000 Hz < 0.5 V eff

Minimum input voltage of 300 .. 5,000 Hz < 0.3 V eff

Note
As the ambient temperature increases, the minimum input temperature increases at a rate of
approximately 0.3 V/°C an.

Input Voltage in Dependence of the Frequency [Ueff]

2,5

2
Effective Input Voltage [V]

1,5

0,5

0
100 1000 10000 100000
Frequency [Hz]

Figure 1: Typical behavior of the input voltage sensitivity at an ambient temperature of 25°C.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 13
1.2.4 Auxiliary and control outputs

a.) Relay outputs


• Power circuit breaker
max. 250 V AC

15 14
Command: close GCB
GCB

17 16
Command: close MCB
MCB

40 39
Command: open MCB
MCB

42 41
Command: open GCB
GCB

Root Switched Description Amax


14 15 Generator power circuit breaker ! close 2.5 mm²
16 17 PCM1-M and PCL1: 2.5 mm²
Mains power circuit breaker ! close
PCM1-G-..-I:
Power circuit breaker ! close
39 40 PCM1-M and PCL1: 2.5 mm²
Mains power circuit breaker ! open
PCM1-G-..-I:
Power circuit breaker ! open
41 42 Generator power circuit breaker ! open 2.5 mm²

• Relay (general)
max. 250 V AC
B A

Relay output
external device

Root Switched Description Amax


A B
18 19 Readiness for operation 2.5 mm²
43 44 Fuel relay/gas valve 2.5 mm²
45 46 Starter 2.5 mm²
PCL1
33 34 Relay 1 (RM) 2.5 mm²
35 36 Relay 2 (RM) 2.5 mm²
37 38 Relay 3 (RM; pre-assigned: Preheat / Ignition ON) 2.5 mm²
47 48 Relay 4 (RM; pre-ass.: Centralized alarm) 2.5 mm²
PCM1x
74 75 Relay 1 (RM) 2.5 mm²
76 77 Relay 2 (RM) 2.5 mm²
78 79 Relay 3 (RM) 2.5 mm²
80 81 Relay 4 (RM) 2.5 mm²
82 83 Relay 5 (RM) 2.5 mm²
37 38 Relay 6 (RM; pre-assigned: Preheat / Ignition ON) 2.5 mm²
47 48 Relay 7 (RM; pre-ass.: Centralized alarm) 2.5 mm²
33 34 Relay 8 (RM) 2.5 mm²
35 36 Relay 9 (RM) 2.5 mm²
(RM)..configurable via the relay manager

14 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
b.) Analog outputs
IA

A
Analog output
0V

B
I
0V Description Amax
A B
120 121 Analog output 0/4..20 mA 1.5 mm²
122 123 Analog output 0/4..20 mA 1.5 mm²

1.2.5 Controller outputs (standard/option ..-A)

The controllers are configured in the standard version as three-position controllers (made up
of a changeover contact and a normally open contact). In option A these are optionally
available in different versions dependent on external bridges/jumpers as well as parame-
ters.

a.) Three-position controller (standard)


The three-position controller is only in standard version included.
max. 250 V AC

9 10
Speed / power Lower

controller Higher
Speed / power
controller
Common

8
11 12 13
Voltage / power factor Lower

controller Higher
Voltage / power
factor controller
Common

Terminal Assignment Description Amax


8 common 2.5 mm²
9 higher Speed/power controller 2.5 mm²
10 lower 2.5 mm²
11 common 2.5 mm²
12 higher Voltage-/power factor ϕ controller 2.5 mm²
13 lower 2.5 mm²

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 15
b.) Multi Functional Controller Outputs (Option A)
The multi functional controller outputs can be changed by configuration and external jump-
ers. These are only included in option A.
Versions
- Three-position controller via relay manager
- Control of n/f/P: Parameter "F/P contr.type" = THREESTEP
n+/f+/P+ = relay manger parameter 114
n-/f-/P- = relay manager parameter 115
- Control of V/Q: Parameter "V/Q contr.output" = THREESTEP
V+/Q+ = relay manager parameter 116
V-/Q- = relay manager parameter 117

- Analog controller output


- Control of n/f/P: Parameter "F/P contr.type" = ANALOG
Current output (mA) = no jumpers necessary
Voltage output (V) = jumpers between 8/9
Connect governor to terminals 9/10
- Control of V/Q: Parameter "V/Q contr.output" = ANALOG
Current output (mA) = no jumpers necessary
Voltage output (V) = jumpers between 11/12
Connect governor to terminals 12/13

- PWM controller output


- Control of n/f/P: Parameter "F/P contr.type" = PWM
PWM output = jumpers between 8/9
Connect governor to terminals 9/10

Wiring Of Controller
- Setting: THREE-POSITION (Three-position controller)
max. 250 Vac
B A

Relay output

RC wiring (external)
Values of R and C depend on used external
relay. Please contact manufacturer of used
relay for correct design.

Terminal Description Amax


A Speed / Frequency / Real power 2.5 mm²
higher
B (RM: "+" = 114, "-" = 115) 2.5 mm²
C or 2.5 mm²
lower
D Voltage/Reactive power (RM: "+" = 116, "-" = 117) 2.5 mm²
The selection and programming occurs via the relay manager (RM).

16 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
- Setting: ANALOG or PWM (Analog controller) - Frequency-/Power controller

GND

9 10
GND

Governor

Current
Speed
Speed / power
N/C
controller
IA IA

8
GND

9 10
GND

Governor

Voltage
Speed
UA Speed / power
UA
controller

8
GND

9 10
GND

Governor
Speed
Speed / power

PWM
PWM PWM
controller

8
Type Terminal Description Amax
8 IA 2.5 mm²
I 9 2.5 mm²
Current
10 GND 2.5 mm²
8 Speed controller / 2.5 mm²
V 9 VA Frequency controller / 2.5 mm²
Voltage
10 GND Real power controller 2.5 mm²
8 2.5 mm²
PWM 9 PWM 2.5 mm²
10 GND 2.5 mm²

- Setting: ANALOG (Analog controller) - Voltage-/Reactive power controller

GND
11 12 13 GND
Current

Voltage / re-active
AVR

N/C
power controller
IA IA

GND
11 12 13

GND
Voltage

Voltage / re-active
AVR

UA UA
power controller

Type Terminal Description Amax


11 IA 2.5 mm²
I 12 2.5 mm²
Current
13 GND 2.5 mm²
Voltage controller / Reactive power controller
11 2.5 mm²
V 12 VA 2.5 mm²
Voltage
13 GND 2.5 mm²

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 17
1.2.6 Interface [PCL1/H & PCM1x]

a.) Interface wiring

A B C D E

CAN-L
GND

CAN-H
Termination
CAN bus
Interface
Terminal Description
Whether the terminals are designated X or Y depends on the configuration of the system. Please
refer to the wiring diagram (A = X/Y, B = X/Y, etc.)
A (X1/Y1) B (X2/Y2) C (X3/Y3) D (X4/Y4) E (X5/Y5)
CAN-H [1]
CAN-L [1]
GND CAN-H CAN-L CAN bus
[1]..can be used to loop the CAN bus or/and to connect the termination resistance.

NOTE

Please note that the CAN bus must be terminated with an impedance which corresponds to the wave
impedance of the cable (e.g. 120 Ohm).

b.) CAN bus screen


Shield
CAN-H
CAN-L
Interface
CAN bus
GND

0.01 uF
1 MOhm
400 Vac

18 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
1.2.7 Loop The CAN Bus

NOTE

Please note that the CAN bus must be terminated with an impedance which corresponds to the wave
impedance of the cable (e.g. 120 Ohm). The Engine CAN bus is terminated between CAN-H and
CAN-L.

X1 X2 X3 X4 X5 X1 X2 X3 X4 X5 X1 X2 X3 X4 X5
Abschluß- Abschluß-
CAN-H

GND

GND
CAN-L

CAN-H

CAN-L

CAN-H

CAN-L

CAN-H

GND
CAN-L
Abschluß

Abschluß
widerstand widerstand

Hinweis:
Der Abschluß muß mit
einem Widerstand erfolgen,
der dem Wellenwiderstand
des verwendeten Kabels
entspricht (z.B. 120 Ω )

CAN-Bus CAN-Bus CAN-Bus

a.) DPC - Configuration interface

NOTE

For configuration via the configuration plug (direct configuration) you need the configuration cable, the PC
program (is delivered with the cable) and the corresponding configuration files. Please consult the online
help installed when the program is installed for a description of the PC program and its setup.
If the parameter "Direct config." is switched to ON a communication via the interface on terminals X1-X5 is
switched off.
If the device detects that the engine is running (ignition speed exceeded), the direct configuration is
disabled.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 19
1.3 Connection diagram

1.3.1 Version PCL1/L

The socket for the PC configuration is located

FL-CABLE-RS232 configuration cable has to be plugged in.


on the side of the device. This is where the
93 94 95 96 97 98 99 100 101 102 103 104
Analog input 4 [T4]
Pt100

120 121 122 123


GND

Analog output
manager
IA
Analog output
0/4..20 mA Analog input 3 [T3]
GND
0/4..20 mA
IA

Analog input 2 [T2]


Pt100

Analog input 1 [T1]


Pt100

37 38 47 48
Standard =
Relay 4 Centralized alarm
Option A: quasi-
continuous controller
with analog outputs
Standard =
Relay 3 Ignition / preglow
voltage

current
PWM

DC

DC
PWM GND

GND

GND

11 12 13 8 9 10
N/C
UA

IA
GND

GND
N/C

39 40 16 17 53 54 23 24 41 42 14 15 4 25 26 29 30 31 32 20 21 22 11 12 13 8 9 10 90 91 92
UA

GND

18 19 43 44 45 46 33 34 35 36
Pickup
IA

Relay 2
switching/inductive

lower SPEED / POWER


Drive

(three-position controller) Relay 1


higher
alternatively opt. A:
Analog controller output
Starter
lower VOLTAGE / POW. FAC.
(three-position controller)
G

higher
alternatively opt. A: Start relay / Gas valve
Analog controller output

Generator voltage L3
3

Readiness for operation


Generator voltage L2

Generator voltage L1

s1 (k)
Generator current L3
6 7 60 61 62 63 64 65 66 67 68 69 70 71 72 73 124 125

s2 (l) Alarm input 14 E

s1 (k) Common
Generator current L2
s2 (l) Alarm input 13 D

s1 (k) Alarm input 12 C


Generator current L1
s2 (l) Alarm input 11 B

Reply: GCB is open Alarm input 10 A

Alarm input 9 9
Command: close GCB
GCB

Alarm input 8 8
Alarm input 7 or
7
'GCB close' without 'eng.mon.'
Command: open GCB
Alarm input 6 or
6
Manual synchronization
PCL1-..-L (Genset Control)

L2 Alarm input 5 5
Busbar voltage
Alarm input 4 or
L1 4
Switch logic
Alarm input 3 or
3

Reply: MCB is open 3


Mode selection locked
Alarm input 2 or
Release MCB 2
Dynamo
Input 1 (EMERGENCY OFF) 1
MCB

Command: close MCB


Common

Common (term. 3/4/5/6/53/54)


Command: open MCB
Multifunction
3

Automatic 2
5

Automatic 1
2 3
50 51 52

Mains voltage L3 0 Vdc

Mains voltage L2 12/24 Vdc


0 1

Mains voltage L1 N
Subject to technical mocifications. 2004-09-23 | PCx Wiring Diagram SEG pcxseg-3904-ap.skf

20 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
1.3.2 Version PCL1/H

The socket for the PC configuration is located

FL-CABLE-RS232 configuration cable has to be plugged in.


on the side of the device. This is where the
93 94 95 96 97 98 99 100 101 102 103 104
Analog input 4 [T4]
Pt100

120 121 122 123


GND

Analog output
manager
IA
Analog output
0/4..20 mA Analog input 3 [T3]
GND
Control room
0/4..20 mA
IA
PLC
PC

Analog input 2 [T2]


Pt100

Analog input 1 [T1]


(modem)

Pt100
PCK

X1 X2 X3 X4 X5
CAN-L

CAN-H
CAN bus interface
GND
Guidance level

Termination

37 38 47 48
Standard =
Relay 4 Centralized alarm
Option A: quasi-
continuous controller
with analog outputs
Standard =
Relay 3 Ignition / preglow
voltage

current
PWM

DC

DC
PWM GND

GND

GND

11 12 13 8 9 10
N/C
UA

IA
GND

GND
N/C

39 40 16 17 53 54 23 24 41 42 14 15 4 25 26 29 30 31 32 20 21 22 11 12 13 8 9 10 90 91 92
UA

GND

18 19 43 44 45 46 33 34 35 36
Pickup
IA

Relay 2
switching/inductive

lower SPEED / POWER


Drive

(three-position controller) Relay 1


higher
alternatively opt. A:
Analog controller output
Starter
lower VOLTAGE / POW. FAC.
(three-position controller)
G

higher
alternatively opt. A: Start relay / Gas valve
Analog controller output

Generator voltage L3
3

Readiness for operation


Generator voltage L2

Generator voltage L1

s1 (k)
Generator current L3
6 7 60 61 62 63 64 65 66 67 68 69 70 71 72 73 124 125

s2 (l) Alarm input 14 E

s1 (k) Common
Generator current L2
s2 (l) Alarm input 13 D

s1 (k) Alarm input 12 C


Generator current L1
s2 (l) Alarm input 11 B

Reply: GCB is open Alarm input 10 A

Alarm input 9 9
Command: close GCB
GCB

Alarm input 8 8
Alarm input 7 or
7
'GCB close' without 'eng.mon.'
Command: open GCB
Alarm input 6 or
6
Manual synchronization
PCL1-..-H (Genset Control)

L2 Alarm input 5 5
Busbar voltage
Alarm input 4 or
L1 4
Switch logic
Alarm input 3 or
3

Reply: MCB is open 3


Mode selection locked
Alarm input 2 or
Release MCB 2
Dynamo
Input 1 (EMERGENCY OFF) 1
MCB

Command: close MCB


Common

Common (term. 3/4/5/6/53/54)


Command: open MCB
Multifunction
3

Automatic 2
5

Automatic 1
2 3
50 51 52

Mains voltage L3 0 Vdc

Mains voltage L2 12/24 Vdc


0 1

Mains voltage L1 N
Subject to technical mocifications. 2004-09-23 | PCx Wiring Diagram SEG pcxseg-3904-ap.skf

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 21
1.3.3 Version PCM1-G/L

The socket for the PC configuration is located

FL-CABLE-RS232 configuration cable has to be plugged in.


on the side of the device. This is where the
6 7 60 61 62 63 64 65 66 67 68 69 70 71 72 73 124 125 126 127 18 19 43 44 45 46 74 75 76 77 78 79 80 81 82 83 37 38 47 48 33 34 35 36 93 94 95 96 97 98 99 100 101 102 103 104
Analog input 4 [T4]
Pt100

X1 X2 X3 X4 X5 Y1 Y2 Y3 Y4 Y5 120 121 122 123


GND

Analog output
manager
IA
Analog output
0/4..20 mA Analog input 3 [T3]
GND
Control room
0/4..20 mA

partizipant
CAN bus
IA
PLC
PC

CAN-L
Analog input 2 [T2]
CAN-H
Pt100
CAN bus interface
GND
Engine level

Termination
Analog input 1 [T1]
(modem)
PCK4

Pt100
CAN-L

CAN-H
Relay 9
CAN bus interface
GND
Guidance level

Termination Relay 8

Standard =
Relay 7 Centralized alarm
Option A: quasi-
continuous controller
with analog outputs
up to 13 additional gensets
(each via one PCMx)

Standard =
Relay 6 Ignition / preglow
voltage

current
PWM

DC

DC

Relay 5
PWM GND

GND

GND

11 12 13 8 9 10
N/C
UA

Relay 4
IA
GND

GND

Relay 3
N/C

53 54 23 24 41 42 14 15 4 25 26 29 30 31 32 20 21 22 11 12 13 8 9 10 90 91 92
UA

GND

Pickup
IA

Relay 2
switching/inductive

lower SPEED / POWER


Drive

(three-position controller) Relay 1


higher
alternatively opt. A:
Analog controller output
Starter
lower VOLTAGE / POW. FAC.
(three-position controller)
G

higher
alternatively opt. A: Start relay / Gas valve
Analog controller output

Generator voltage L3
3

Readiness for operation


Generator voltage L2

Generator voltage L1 Alarm input 16 G

s1 (k) Alarm input 15 F


Generator current L3
s2 (l) Alarm input 14 E

s1 (k) Common
Generator current L2
s2 (l) Alarm input 13 D

s1 (k) Alarm input 12 C


Generator current L1
s2 (l) Alarm input 11 B

Reply: GCB is open Alarm input 10 A

Alarm input 9 9
Command: close GCB
GCB

Alarm input 8 8
Alarm input 7 or
7
'GCB close' without 'eng.mon.'
PCM1-G-..-L (Genset Control)

Command: open GCB


Alarm input 6 or
6
Manual synchronization
L2 Alarm input 5 5
Busbar voltage
Alarm input 4 or
L1 4
Switch logic
Alarm input 3 or
3

Isolated operation 3
Mode selection locked
Alarm input 2 or
see table below 2
Dynamo
Meaning Terminal 54 Terminal 53
Input 1 (EMERGENCY OFF) 1
Isolated YES NO
operation e.g. 24 V DC e.g. 0 V DC
Common
Mains parallel NO YES
operation e.g. 0 V DC e.g. 24 V DC
Mains parallel MCB reply - MCB to be closed: Common (term. 3/4/5/6/53/54)
operation with (closed YES (i.e. 24 Vdc)
MCB "EXTERNAL" = NO, i.e. 0Vdc) - MCB is not to be closed:
NO (i.e. 0 Vdc)
Multifunction
50 51 52 27 28

s1 (k) Automatic 2
5

Mains current L1
s2 (l) Automatic 1
2 3

Mains voltage L3 0 Vdc

Mains voltage L2 12/24 Vdc


0 1

Mains voltage L1 N
Subject to technical mocifications. 2004-09-23 | PCx Wiring Diagram SEG pcxseg-3904-ap.skf

22 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
1.3.4 Version PCM1-G/H-I

The socket for the PC configuration is located

FL-CABLE-RS232 configuration cable has to be plugged in.


on the side of the device. This is where the
6 7 60 61 62 63 64 65 66 67 68 69 70 71 72 73 124 125 126 127 18 19 43 44 45 46 74 75 76 77 78 79 80 81 82 83 37 38 47 48 33 34 35 36 93 94 95 96 97 98 99 100 101 102 103 104
Analog input 4 [T4]
Pt100

50 51 52 27 28 39 40 16 17 53 54 23 24 41 42 14 15 4 25 26 29 30 31 32 20 21 22 11 12 13 8 9 10 90 91 92 105 106 107 108 109 110 111 112 113 X1 X2 X3 X4 X5 Y1 Y2 Y3 Y4 Y5 120 121 122 123
GND

Analog output
manager
IA
Analog output
0/4..20 mA Analog input 3 [T3]
GND
Control room
0/4..20 mA

partizipant
CAN bus
IA
PLC
PC

CAN-L
Analog input 2 [T2]
Pt100
CAN-H
Temperature dept. start/stop
CAN bus interface Temperature dep. power red.
GND
Engine level

Termination
Analog input 1 [T1]
(modem)
PCK4

Pt100
CAN-L

CAN-H
Relay 9
CAN bus interface
GND
Guidance level

Termination Relay 8

Standard =
Relay 7 Centralized alarm
Option A: quasi- Analog input 7 [T7]
continuous controller 0/4..20 mA
with analog outputs
up to 13 additional gensets
(each via one PCMx)

Standard =
Relay 6 Ignition / preglow
voltage

current
PWM

Analog input 6 [T6]


DC

DC

Pt100
Relay 5
PWM GND

GND

GND

11 12 13 8 9 10
N/C
UA

Relay 4
Analog input 5 [T5]
IA

Pt100
GND

GND

Relay 3
N/C
UA

GND

Pickup
IA

Relay 2
switching/inductive

lower SPEED / POWER


Drive

(three-position controller) Relay 1


higher
alternatively opt. A:
Analog controller output
Starter
lower VOLTAGE / POW. FAC.
(three-position controller)
G

higher
alternatively opt. A: Start relay / Gas valve
Analog controller output

Generator voltage L3
3

Readiness for operation


Generator voltage L2

Generator voltage L1 Alarm input 16 G

s1 (k) Alarm input 15 F


Generator current L3
s2 (l) Alarm input 14 E

s1 (k) Common
Generator current L2
s2 (l) Alarm input 13 D

s1 (k) Alarm input 12 C


Generator current L1
s2 (l) Alarm input 11 B

Reply: GCB is open Alarm input 10 A

Alarm input 9 9
Command: close GCB
GCB

Alarm input 8 8
PCM1-G-..-H-I (Genset Control)

Alarm input 7 or
7
'GCB close' without 'eng.mon.'
Command: open GCB
Alarm input 6 or
6
Manual synchronization
L2 Alarm input 5 5
Busbar voltage
Alarm input 4 or
L1 4
Switch logic
Alarm input 3 or
3

Reply: CB open 3
Mode selection locked
Alarm input 2 or
Release CB 2
Dynamo
Input 1 (EMERGENCY OFF) 1
Command: close CB
Common

Common (term. 3/4/5/6/53/54)


Command: open CB
Multifunction

s1 (k) Automatic 2
5

Mains current L1
s2 (l) Automatic 1
2 3

Mains voltage L3 0 Vdc

Mains voltage L2 12/24 Vdc


0 1

Mains voltage L1 N
Subject to technical mocifications. 2004-11-18 | PCx Wiring Diagram SEG pcxseg-4704-ap.skf

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 23
1.3.5 Version PCM1-G/H-E

The socket for the PC configuration is located

FL-CABLE-RS232 configuration cable has to be plugged in.


on the side of the device. This is where the
6 7 60 61 62 63 64 65 66 67 68 69 70 71 72 73 124 125 126 127 18 19 43 44 45 46 74 75 76 77 78 79 80 81 82 83 37 38 47 48 33 34 35 36 93 94 95 96 97 98 99 100 101 102 103 104
Analog input 4 [T4]
Pt100

53 54 23 24 41 42 14 15 4 25 26 29 30 31 32 20 21 22 11 12 13 8 9 10 90 91 92 105 106 107 108 109 110 111 112 113 X1 X2 X3 X4 X5 Y1 Y2 Y3 Y4 Y5 120 121 122 123
GND

Analog output
manager
IA
Analog output
0/4..20 mA Analog input 3 [T3]
GND
Control room
0/4..20 mA

partizipant
CAN bus
IA
PLC
PC

CAN-L
Analog input 2 [T2]
CAN-H
Pt100
Temperature dep. start/stop
CAN bus interface Temperature dep. power red.
GND
Engine level

Termination
Analog input 1 [T1]
(modem)
PCK4

Pt100
CAN-L

CAN-H
Relay 9
CAN bus interface
GND
Guidance level

Termination Relay 8

Standard =
Relay 7 Centralized alarm
Option A: quasi- Analog input 7 [T7]
continuous controller 0/4..20 mA
with analog outputs
up to 13 additional gensets
(each via one PCMx)

Standard =
Relay 6 Ignition / preglow
voltage

current
PWM

Analog input 6 [T6]


DC

DC

Pt100
Relay 5
PWM GND

GND

GND

11 12 13 8 9 10
N/C
UA

Relay 4
Analog input 5 [T5]
IA

Pt100
GND

GND

Relay 3
N/C
UA

GND

Pickup
IA

Relay 2
switching/inductive

lower SPEED / POWER


Drive

(three-position controller) Relay 1


higher
alternatively opt. A:
Analog controller output
Starter
lower VOLTAGE / POW. FAC.
(three-position controller)
G

higher
alternatively opt. A: Start relay / Gas valve
Analog controller output

Generator voltage L3
3

Readiness for operation


Generator voltage L2

Generator voltage L1 Alarm input 16 G

s1 (k) Alarm input 15 F


Generator current L3
s2 (l) Alarm input 14 E

s1 (k) Common
Generator current L2
s2 (l) Alarm input 13 D

s1 (k) Alarm input 12 C


Generator current L1
s2 (l) Alarm input 11 B

Reply: GCB is open Alarm input 10 A

Alarm input 9 9
Command: close GCB
GCB

Alarm input 8 8
PCM1-G-..-H-E (Genset Control)

Alarm input 7 or
7
'GCB close' without 'eng.mon.'
Command: open GCB
Alarm input 6 or
6
Manual synchronization
L2 Alarm input 5 5
Busbar voltage
Alarm input 4 or
L1 4
Switch logic
Alarm input 3 or
3

isolated operation 3
Mode selection locked
Alarm input 2 or
see table below 2
Dynamo
Meaning Terminal 54 Terminal 53
Input 1 (EMERGENCY OFF) 1
Isolated YES NO
operation e.g. 24 V DC e.g. 0 V DC
Common
Mains parallel NO YES
operation e.g. 0 V DC e.g. 24 V DC
Mains parallel MCB reply - MCB to be closed: Common (term. 3/4/5/6/53/54)
operation with (closed YES (i.e. 24 Vdc)
MCB "EXTERNAL" = NO, i.e. 0Vdc) - MCB is not to be closed:
NO (i.e. 0 Vdc)
Multifunction
50 51 52 27 28

s1 (k) Automatic 2
5

Mains current L1
s2 (l) Automatic 1
2 3

Mains voltage L3 0 Vdc

Mains voltage L2 12/24 Vdc


0 1

Mains voltage L1 N
Subject to technical mocifications. 2004-11-18 | PCx Wiring Diagram SEG pcxseg-4704-ap.skf

24 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
1.3.6 Version PCM1-M/L

The socket for the PC configuration is located

FL-CABLE-RS232 configuration cable has to be plugged in.


on the side of the device. This is where the
6 7 60 61 62 63 64 65 66 67 68 69 70 71 72 73 124 125 126 127 18 19 43 44 45 46 74 75 76 77 78 79 80 81 82 83 37 38 47 48 33 34 35 36 93 94 95 96 97 98 99 100 101 102 103 104
Analog input 4 [T4]
Pt100

X1 X2 X3 X4 X5 Y1 Y2 Y3 Y4 Y5 120 121 122 123


GND

Analog output
manager
IA
Analog output
0/4..20 mA Analog input 3 [T3]
GND
Control room
0/4..20 mA

partizipant
CAN bus
IA
PLC
PC

CAN-L
Analog input 2 [T2]
CAN-H
Pt100
CAN bus interface
GND
Engine level

Termination
Analog input 1 [T1]
(modem)
PCK4

Pt100
CAN-L

CAN-H
Relay 9
CAN bus interface
GND
Guidance level

Termination Relay 8

Standard =
Relay 7 Centralized alarm
Option A: quasi-
continuous controller
with analog outputs
up to 13 additional gensets
(each via one PCMx)

Standard =
Relay 6 Ignition / preglow
voltage

current
PWM

DC

DC

Relay 5
PWM GND

GND

GND

11 12 13 8 9 10
N/C
UA

Relay 4
IA
GND

GND

Relay 3
N/C

50 51 52 27 28 39 40 16 17 53 54 23 24 41 42 14 15 4 25 26 29 30 31 32 20 21 22 11 12 13 8 9 10 90 91 92
UA

GND

Pickup
IA

Relay 2
switching/inductive

lower SPEED / POWER


Drive

(three-position controller) Relay 1


higher
alternatively opt. A:
Analog controller output
Starter
lower VOLTAGE / POW. FAC.
(three-position controller)
G

higher
alternatively opt. A: Start relay / Gas valve
Analog controller output

Generator voltage L3
3

Readiness for operation


Generator voltage L2

Generator voltage L1 Alarm input 16 G

s1 (k) Alarm input 15 F


Generator current L3
s2 (l) Alarm input 14 E

s1 (k) Common
Generator current L2
s2 (l) Alarm input 13 D

s1 (k) Alarm input 12 C


Generator current L1
s2 (l) Alarm input 11 B

Reply: GCB is open Alarm input 10 A

Alarm input 9 9
Command: close GCB
GCB

Alarm input 8 8
Alarm input 7 or
7
'GCB close' without 'eng.mon.'
PCM1-M-..-L (Genset Control)

Command: open GCB


Alarm input 6 or
6
Manual synchronization
L2 Alarm input 5 5
Busbar voltage
Alarm input 4 or
L1 4
Switch logic
Alarm input 3 or
3

Reply: MCB is open 3


Mode selection locked
Alarm input 2 or
Enable MCB 2
Dynamo
Input 1 (EMERGENCY OFF) 1
MCB

Command: close MCB


Common

Common (term. 3/4/5/6/53/54)


Command: open MCB
Multifunction
3

s1 (k) Automatic 2
5

Mains current L1
s2 (l) Automatic 1
2 3

Mains voltage L3 0 Vdc

Mains voltage L2 12/24 Vdc


0 1

Mains voltage L1 N
Subject to technical mocifications. 2004-09-23 | PCx Wiring Diagram SEG pcxseg-3904-ap.skf

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 25
1.3.7 Version PCM1-M/H

The socket for the PC configuration is located

FL-CABLE-RS232 configuration cable has to be plugged in.


on the side of the device. This is where the
6 7 60 61 62 63 64 65 66 67 68 69 70 71 72 73 124 125 126 127 18 19 43 44 45 46 74 75 76 77 78 79 80 81 82 83 37 38 47 48 33 34 35 36 93 94 95 96 97 98 99 100 101 102 103 104
Analog input 4 [T4]
Pt100

50 51 52 27 28 39 40 16 17 53 54 23 24 41 42 14 15 4 25 26 29 30 31 32 20 21 22 11 12 13 8 9 10 90 91 92 105 106 107 108 109 110 111 112 113 X1 X2 X3 X4 X5 Y1 Y2 Y3 Y4 Y5 120 121 122 123
GND

Analog output
manager
IA
Analog output
0/4..20 mA Analog input 3 [T3]
GND
Control room
0/4..20 mA

partizipant
CAN bus
IA
PLC
PC

CAN-L
Analog input 2 [T2]
Pt100
CAN-H
Temperature dep. start/stop
CAN bus interface Temperature dep. power red.
GND
Engine level

Termination
Analog input 1 [T1]
(modem)
PCK4

Pt100
CAN-L

CAN-H
Relay 9
CAN bus interface
GND
Guidance level

Termination Relay 8

Standard =
Relay 7 Centralized alarm
Option A: quasi- Analog input 7 [T7]
continuous controller 0/4..20 mA
with analog outputs
up to 13 additional gensets
(each via one PCMx)

Standard =
Relay 6 Ignition / preglow
voltage

current
PWM

Analog input 6 [T6]


DC

DC

Pt100
Relay 5
PWM GND

GND

GND

11 12 13 8 9 10
N/C
UA

Relay 4
Analog input 5 [T5]
IA

Pt100
GND

GND

Relay 3
N/C
UA

GND

Pickup
IA

Relay 2
switching/inductive

lower SPEED / POWER


Drive

(three-position controller) Relay 1


higher
alternatively opt. A:
Analog controller output
Starter
lower VOLTAGE / POW. FAC.
(three-position controller)
G

higher
alternatively opt. A: Start relay / Gas valve
Analog controller output

Generator voltage L3
3

Readiness for operation


Generator voltage L2

Generator voltage L1 Alarm input 16 G

s1 (k) Alarm input 15 F


Generator current L3
s2 (l) Alarm input 14 E

s1 (k) Common
Generator current L2
s2 (l) Alarm input 13 D

s1 (k) Alarm input 12 C


Generator current L1
s2 (l) Alarm input 11 B

Reply: GCB is open Alarm input 10 A

Alarm input 9 9
Command: close GCB
GCB

Alarm input 8 8
Alarm input 7 or
7
PCM1-M-..-H (Genset Control)

'GCB close' without 'eng.mon.'


Command: open GCB
Alarm input 6 or
6
Manual synchronization
L2 Alarm input 5 5
Busbar voltage
Alarm input 4 or
L1 4
Switch logic
Alarm input 3 or
3

Reply: MCB is open 3


Mode selection locked
Alarm input 2 or
Enable MCB 2
Dynamo
Input 1 (EMERGENCY OFF) 1
MCB

Command: close MCB


Common

Common (term. 3/4/5/6/53/54)


Command: open MCB
Multifunction
3

s1 (k) Automatic 2
5

Mains current L1
s2 (l) Automatic 1
2 3

Mains voltage L3 0 Vdc

Mains voltage L2 12/24 Vdc


0 1

Mains voltage L1 N
Subject to technical mocifications. 2004-11-18 | PCx Wiring Diagram SEG pcxseg-4704-ap.skf

26 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
2 Functional description

2.1 What must one pay attention to in the event of ...

2.1.1 ... different options

In accordance with its configuration, the item may differ from the maximum expansion via the following characteristics:
• The inputs and outputs are present or not present, corresponding to the item configuration (depending on your order). Please refer
to the wiring diagram and the notes on the options contained in these. Refer to the type plate to see whether or not the correspond-
ing option is contained in the item. If the type plate has been removed, all configuration screens can be called up in succession
and the options can be compiled with the assistance of this manual.
• There are different screens for the various types of interfaces.

2.1.2 ... systems with one power circuit breaker

If an item with a 2-power-circuit-breaker logic [PCM1-M] or a 1-power-circuit-breaker logic [PCM1-G] is installed for use with one
power circuit breaker, the following shall apply:

• If the stationary permanent operation application is to be operated in isolated or isolated parallel operation (the MCB is opened),
the following signals have to be applied:
- "Reply: MCB is open" / "Isolated operation" (term. 54): HIGH signal (log. "1") and
- "Enable MCB" (terminal 53): LOW signal (logical "0").
- Condition: The "Emergency power" must be set to "OFF".
• If the stationary permanent operation application is to be operated in mains parallel operation (the generator operates always in
mains parallel if the GCB is closed), the following signals have to be applied:
- "Reply: MCB is open" / "Isolated operation" (term. 54): LOW-Signal (log. "0") and
- "Enable MCB" (terminal 53): HIGH signal (logical "1").
• If the application is to be operated in isolated(parallel) as well as in mains parallel operation (the MCB can be opened or closed),
the following signals have to be applied:
- Reply, that the GCB is closed (terminal 4) and
- Reply, that the MCB is closed (terminal 54) and
- "Enable MCB" (terminal 53)

Case A - The MCB has to remain closed (except at an emergency power operation): The "Enable MCB" (terminal 53) always has to
be logical "1".

Case B - The MCB can be opened (also outside an emergency power operation): The "Enable MCB" (terminal 53) has to be logical
"1" if a mains parallel operation has to be established (a synchronization of the MCB has to be performed). During the synchroniza-
tion of the MCB (PCM1-G: External) the generator frequency is controlled with a slightly higher value than the mains frequency (df
max/2). Additionally a message is issued at the display. The "Enable MCB" (terminal 53) has to be logically "0", if the system has to
be operated in isolated operation (control of setpoint frequency and setpoint voltage).

2.2 Table of setpoint values


External ON
Interface ON

Setpoint value
Automatic 1

Automatic 2

Control via

Specification of Setpoint value through


1 X X X Setpoint 1
0 1 OFF OFF Setpoint 2
0 1 X ON Externally via 0/4..20 mA input
0 1 EIN AUS Externally via serial interface
0 0 AUS AUS Standby only emergency power
x..optionally

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 27
2.3 Control inputs

NOTE

Any possible emergency power ("Emergency power" configuration screen must be set to ON) or sprinkler
operation (terminal 6 must be configured accordingly) will be carried out in the "TEST" and "AUTOMATIC"
operating modes regardless of the discrete inputs "Automatic 1" and "Automatic 2". If terminals 3 and 5
are set simultaneously, preference is given to terminal 3.

Automatic 1 Selection of the operating mode "AUTOMATIC" with "Active power setpoint value 1" as
Terminal 3 well as starting/stopping of the engine.
Set.................If the item is in "AUTOMATIC" mode (selected using the mode selection
switch on the front side) the "active power setpoint value 1" is adjusted in
mains parallel mode. In the case of a fixed power (F), the engine is
started immediately and operation in parallel with the mains is com-
menced following the synchronization of the generator power circuit
breaker. In the case of incoming/import (B) or outgoing/export power (L),
starting is determined by automatic start/stop (start/stop) operation. If no
automatic start/stop operation is enabled, the engine is started immedi-
ately. The setpoint value can be modified via both the configuration mode
and via the "up/down" push-buttons in "AUTOMATIC" mode.
AUTOSTART
Reset ..............If the engine does not run either in sprinkler mode or emergency power
mode, it is stepped. Then a coasting is carried out and the engine is
stopped.

Automatic 2 Selection of the "AUTOMATIC" mode with "Active power setpoint value 2" as well as
Terminal 5 starting/stopping of the engine.
Set.................If the item is in "AUTOMATIC" mode (selected using the mode selection
switch on the front side) the "Active power setpoint value 2" is adjusted in
mains parallel mode. In the case of a fixed power (F), the engine is
started immediately and operation in parallel with the mains is com-
menced following the synchronization of the generator power circuit
breaker. In the case of incoming/import (B) or outgoing/export power (L),
starting is determined by automatic start/stop operation. If no automatic
start/stop operation is enabled, the engine is started immediately. The
setpoint value can be modified via both the configuration mode and via
the "up/down" push-buttons in "AUTOMATIC" mode. AUTOSTART
Reset ..............If the engine does not run either in sprinkler mode or emergency power
mode, it is stopped. Then a coasting is carried out and the engine is
stopped.

If a setpoint value is specified externally (e. g. via an analog input 0/4..20 mA or a bi-directional
interface), the external setpoint value is adjusted with the discrete input (see Table of setpoint values).

28 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
Multifunction Discrete input terminal 6 may reveal different functions according to the following description. Please
Terminal 6 note that, when used as a sprinkler input, the discrete input reveals negative functional logic. The
selection of the logic circuit is made using a configuration screen (Chapter 4.15.3 "Setting the control
inputs ", Page 135).

• Sprinkler By resetting terminal 6 (setting a low level) sprinkler operation is activated in accordance with the
functional description. This is terminated by setting terminal 6 (application of a High signal). Attention:
Negative functional logic! (for the function of the sprinkler operation, please also observe Chap-
ter 2.11 "Sprinkler operation" on page 53.)

• Engine enable Terminal 6 in this case has the same function as the STOP push-button: Resetting terminal 6 (applica-
tion of a LOW signal) prevents the engine's starting, and stops the engine if this is already running; the
application of a HIGH signal enables the starting of the engine; the application of a high signal en-
ables the engine for startup. Caution: Via this function, emergency power operation is also prevented
or aborted. Emergency power is not possible without this enable signal! The engine enable function is
only possible in "AUTOMATIC" operating mode.

• Ext. acknowledge In "STOP" and "AUTOMATIC" modes alarms can be acknowledged externally by setting terminal 6
(Change of slope from a LOW to a HIGH signal). In order to achieve further acknowledgement, ter-
minal 6 must accordingly first be reset and then set again. If a continuous HIGH signal is present at
terminal 6, this has no effect on the acknowledgement and suppression of alarm messages.

••STOP mode By setting terminal 6 (application of a HIGH signal) the STOP mode is chosen. If you remove this
signal the mode will change into the mode which was activated before terminal 6 was set.

• Engine stop By setting terminal 6 (application of a HIGH signal) a start of the engine can be prevented. If the
engine is running because emergency current is present, it is stopped by setting this discrete input. The
discrete input is not inverted. The engine block function is only possible in "AUTOMATIC" operating
mode.

• No CB by start If the terminal 6 is set, the engine starts; no synchronization is carried out and the generator power
circuit breaker is not engaged (no switching to black busbar). The GCB is then inserted only if emer-
gency current is present. After return of the mains, there is a switchover to the mains according to the
set CB logic. The start of terminal 6 is of a higher value than the start via terminals 3/5. If terminal 6
was selected, terminals 3/5 are ignored. If the genset is in mains parallel mode with power circuit
breaker logic "Parallel" and if terminal 6 is activated, the GCB is opened after a reduction in power.
The genset continues to operate without load with the GCB open.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 29
Reply: GCB is open With this input (logical "1") the item is signaled that the generator power circuit breaker is open
Terminal 4 (the "GCB ON" LED is off).

[PCL1 / PCM1-M] With this input (logical "1") the item is signaled that the mains power circuit breaker is open (the LED
Reply: MCB is open "MCB ON" is off).
Terminal 54

[PCM1-G] With this input (logical "1") the item is signaled that the power circuit breaker is open.
Reply: CB is open
Terminal 54

[PCM1-G] With this input (logical "1") the item is signaled that the genset is operating in isolated operation (the
Isolated operation LED "Mains parallel" is off). This discrete input is used to decide whether, after closing the GCB,
Terminal 54 frequency control (terminal 54 = logical "1") or power control (terminal 54 = logical "0") is to be
carried out.

[PCL1/PCM1-M] Set.................A mains parallel operation becomes possible and the MCB is operated.
Enable MCB Reset ..............The MCB is not operated. Depending on the reply of the MCB, an iso-
Terminal 53 lated operation or an operation in parallel with the mains is performed.

[PCM1-G] Set.................A mains parallel operation becomes possible and the CB is operated.
Enable CB Reset ..............The CB is not operated. Depending on the reply of the CB, an isolated
Terminal 53 operation or an operation in parallel with the mains is performed.

Discrete inputs Freely programmable alarm inputs with message text, alarm class, time delay, engine start delay and
[PCL1] Terminal 61-73/125 NO/NC shunt enable (description starting on page 132).
[PCM1] Terminal 61-73/125-127

30 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
2.4 Control outputs

Readiness for operation Setting the relay signals the readiness for operation of the item. If this relay drops out, the perfect
Terminals 18/19 function of the item can no longer be guaranteed. Appropriate measure must be introduced if this
relay has dropped out (e.g. open GCB, shut down engine).

Preheating (Diesel engine) When this relay is set the diesel engine is preheated (see functional description of diesel engine start
[PCL1] pre-ass. to relay 3, term. 37/38 cycle, pages 37/145).
[PCM1x] pre-ass. to relay 6, term. 37/38

Ignition "ON" (Gas engine) When this relay is set, the ignition of the gas engine is switched on (see functional description of gas
[PCL1] pre-ass. to relay 3, term. 37/38 engine start cycle, pages 39/145).
[PCM1x] pre-ass. to relay 6, term. 37/38

Fuel relay/gas valve Terminals 43/44


a) Diesel engine: fuel relay
a.1) Operating magnet
Setting this relay will initiate the starting sequence of the diesel engine. If the engine is to be shut-down the relay will
immediately drop out. If the speed of the engine drops below the adjustable ignition speed, the relay also drops out
(note chapter "Diesel engine").
a.2) Stopping magnet
Setting this relay will stop the engine.

b) Gas engine: Gas valve


Setting this relay will open the gas valve for the gas engine. If the engine shall be shut down, the relay drops out di-
rectly. If the engine speed falls below the adjustable firing speed, the relay drops out as well (please note the descrip-
tion in chapter „Gas engine“).

Starter By setting this relay the starter will be engaged. When the firing speed is reached or when there is a
Terminals 45/46 stoppage or after the flow of the engagement time the starter is disengaged (see chapter 2.6
"Description starting/stopping process" starting at page 37).

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 31
Centralized alarm By setting this relay, a centralized alarm is output. In this case e. g. a horn or buzzer is triggered. The
[PCL1] pre-ass. to relay 4, term. 47/48 operator can reset the relay by pressing the push-button "RESET/CLEAR" for a short period. The relay
[PCM1x] pre-ass. to relay 7, term. 47/48 will be set again in the event of another alarm. The centralized alarm is set for alarms of alarm
class F1 through F3 (see page 62).

Command: close GCB By setting this relay the generator power circuit breaker (GCB) will be closed. If the GCB connection
Terminals 14/15 is configured to continuous pulse, in response to a missing discrete input "Reply: GCB is open" the
relay is maintained in its closed state; this is also the case if the voltages of the generator and the
generator busbar are identical. In the event of an alarm of the alarm class 2 or 3, or the GCB is to
be opened, this relay drops out. In the event of an alarm of alarm class 2 the relay does not drop out
immediately, but only if the power is less than 3.125 % of the generator power rating (see page 84).
If the switching of the GCB is not configured to continuous pulse, the relay drops back out after a
pulse is output. Then, the self-holding of the GCB must be carried out externally.

Command: open GCB By setting this relay the GCB will be opened. Following "Reply: GCB is open", the relay output is
Terminals 41/42 removed.

[PCL1 / PCM1-M] By setting this relay the MCB will be closed. This output is always a connect pulse, i. e., the self-
Command: close MCB holding of the mains power circuit breaker must be externally carried out.
Terminals 16/17

[PCM1-G] By setting this relay the CB will be closed. This output is always a connect pulse, i. e., the self-holding
Command: close CB of the power circuit breaker must be externally carried out.
Terminals 16/17

[PCL1 / PCM1-M] By setting this relay the MCB will be opened. Following "Reply: MCB is open", the relay output is
Command: open MCB removed.
Terminals 39/40

[PCM1-G] By setting this relay the CB will be opened. Following "Reply: CB is open", the relay output is re-
Command: open CB moved.
Klemmen 39/40

Additional relays R1 through R9 These relays are managed by the "relay manager" (see page 143).
[PCL1] Terminal 33..38/47..48
[PCM1x] Terminal 33..38/47..48/74..83 Pre-settings:
• Relay 1-5 = Relay number (e. g. Relay 1 = Alarm class 1, Relay 2 = Alarm class 2, etc.)
• Relay 6 = Ignition / preheating (e.g. Relay 3 in the PCL1)
• Relay 7 = Centralized alarm (e.g. Relay 4 in the PCL1)

32 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
2.5 Text in the display

Operating and alarm messages are displayed in the bottom row in the display. Using the
"message" push-button, one can switch to the following screens: "Gen. power", "current
slave pointer", etc.

2.5.1 Item messages in the display

Relay messages The following relay outputs for the engine and generator control system are additionally shown in the
display:
• Synchronization GCB or MCB,
• Switching to black busbar GCB or MCB,
• Start,
• Preheat (Diesel engine),
• Purging operation (Gas engine),
• Ignition (gas engine),
• Initial state (Diesel engine): f- continuous speed governor signal is set prior to starting the engine,
• Auxiliary operations run/coasting.

"Start - Pause" An interrupted starting process is displayed with the message "Start pause".

"Testmode" If "TEST" operating mode is selected, this message is output.

"Load Test" If, in "TEST" mode, a load test is selected following the actuation of the "GCB ON" push-button, this
message is output.

"Emergency run" This message displays a current case of emergency power.

"Mains sett. 000s " This message in the display shows the mains settling time following a mains fault.
There is also shown the remaining mains settling time.

"Sprinklermode" This message is shown in the display during sprinkler operation.

"Sprinkler shutd." Following sprinkler operation, the engine operates without load for 10 minutes. This message is
shown in the display during this period.

"Cool down 000s " No-load operation (engine cooling) prior to engine shutdown is displayed with this message. There is
also shown the remaining coasting time.

"Stop engine !" When stopping the engine, a starting block is set for 10 seconds on negative deviation from the
firing speed. This message displays the operating condition.

"Power reduction" A stopping of the engine is desired: The power must be reduced.

"Sprinkler+Emerg." Both the sprinkler operation and the emergency power functions are active.

"Start without CB" Using terminal 6 the function "Start without GCB" was selected.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 33
NOTE
The following message is no allarm message in the true sense, but an informative message, which doesn
not have to be acknowledged and results no engine shutdown. The message disappears after correcting
the phase rotation.

Phase sequence! Alarm message: Rotating field generator/mains different Alarm class: 3

The rotating fields of generator and mains are different. Closing GCB/MCB is blocked.

NOTE
The texts "Sprinkler operation", "Emergency power", "Test", "Load test" and "Sprinkler+Emergency power"
are alternately displayed with the basic display screen. If one of these texts is active, the actuation of the
"Select" push-button switches to the continuous display of the basic display screen. This can be undone
again by actuating the "Acknowledge" push-button.

34 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
2.5.2 Alarm messages in the display

Alarm messages The following messages are output by the protection functions:
• Generator or mains undervoltage
• Generator or mains overvoltage
• Generator or mains underfrequency
• Generator or mains overfrequency
• Phase/vector shift
• Overspeed (Pickup triggering)
• Generator overload
• Reverse/reduced power
• Load imbalance
• Generator overcurrent 1
• Generator overcurrent 2
• Battery undervoltage

Alarm input messages The text assigned in the relevant screen is output as an alarm message. At the same time, alarm
output for the alarm class which has been set occurs.

Analog input messages The text assigned in the relevant screen is output as an alarm message. A "!" (for GW 1 "Warning"
and GW 2 "Shutoff") appears in front of the configured text. In the case of a wire break, the measur-
ing value is overwritten with "- -". At the same time, alarm output for the alarm class which has been
set occurs.

"Pickup/Gen.Freq" This alarm message is shown in the display if the Pickup speed deviates excessively (≈10 Hz) from
the generator frequency.

"Interf.err.Y1Y5" Interface Y1..Y5 malfunction. External control signals cannot be received.

"Interf.err.X1X5" Interface X1..X5 malfunction. External control signals cannot be received.

"GCB syn. failure" If the synchronization time for the generator power circuit breaker has been exceeded, this message
is shown in the display. At the same time, an alarm class F1 alarm is output.

"MCB syn. failure" If the synchronization time for the mains power circuit breaker has been exceeded, this message is
shown in the display. At the same time, an alarm class F1 alarm is output.

"GCB open failure" If closing of the GCB was not successful following 5 switching attempts, the message "GCB close
"GCB close failure " failure" is shown in the display. If it is present 2 seconds following the "Command: GCB open" pulse,
"Reply: GCB is open" is still present, the message "GCB open failure" is displayed. At the same time,
an alarm class F1 alarm is output.

"MCB open failure" If closing of the MCB was not successful following 5 switching attempts, the message "MCB close
"MCB close failure" failure" is shown in the display. If it is present 2 seconds following the "Command: MCB open" pulse,
"Reply: MCB is open" is still present, the message "MCB open failure" is displayed. At the same time,
an alarm class F1 alarm is output.

"Power not zero" The power circuit breaker logic "CLOSED TRANSIT." (softloading/interchange synchronization) has
been selected and the MCB is to be opened. If the incoming power zero cannot be adjusted within
the time set in the "Max. start/stop ramp time" screen, this message is displayed.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 35
"Fault df/dVmax." If, following starting and the expiration of the set time "GCB black start max. time" the generator does
not reach the voltage and frequency window allocated to it, this message is displayed.

"Start fail" This message is output following three unsuccessful starting attempts. No further attempt at starting is
made. In sprinkler operation, starting is attempted six times before this message is displayed.

"Stop failure" If speed is still detected 30 seconds following the stop signal, (acquired by the generator frequency,
the Pickup or the discrete input "Dynamo") the message "Stop failure" is output with an F3 alarm
shutoff.

"Service" Following the expiry of the maintenance interval, the imminence of the next maintenance is displayed
with this message.

"Not wanted stop" The engine's starting process was completed and the engine should run. This message is displayed if
the generator frequency suddenly drops to 0 Hz, e.g. due to mechanical damage. (Background note:
Since the delayed engine monitoring is deactivated when the firing speed is not reached, no under-
frequency can be detected. This message is not suppressed due to the delayed engine monitoring.)

"P-Ramp: GCB open" If the GCB can not be opened after stopping the engine in the time range of "add/stop ramp max.
time" this alarm message will be displayed (this message shows that the P control potentially has a
fault).

EXT open failure Alarm message: Malfunction when opening an external breakerAlarm class

With a changeover of the mains decoupling in the GCP-31: Malfunction on mains decoup-
ling via relay terminals 39/40.

36 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
2.6 Description starting/stopping process

2.6.1 Diesel engine

1500 1/min

Start frequency
f-contr. + time
ZD

Speed governor

Approach idle
gas position

Engine monitoring
activated

Start request

Start relay

Pre-glow

Starter 0,5 s 0,5 s

t/s
tSta tVG tEin tSPZ tVG tEin tMV tN
Delayed engine
monitoring 00s

Ignition speed reached

Start attempt Start attempt


unsuccessful successful
Start Stop

The formula signs and indices mean:


tSta .......................... Approach idle gas position [s]
tVG .......................... Preheating time [s]
tEin ........................... Engagement time [s]
tSPZ .......................... Time between two start attempts [s]
tMV .......................... Delayed engine monitoring [s]
tN ........................... Coasting time [s]

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 37
a.) Starting process
Explanation with reference to entered data (see page 144, "

Engine configuration")

Approach idle gas position (ON/OFF) ON


Preheating time (0..99 s) tVG = 3 s
Engagement time (0..99 s) tEin = 5 s
Time between two start attempts (0..99 s) tSPZ = 10 s

Function If the item is equipped with a three-position frequency controller, the relay "Frequency
lower" is output prior to the starting process for the "Frequency controller initial state" time.
Then the relay "Preheating" will be set for the period of the preheating time. Following pre-
heating, the operating magnet is first set, and then the starter. When the adjustable firing
speed is exceeded, the starter is disengaged again, and the operating magnet is held via
the firing speed. After reaching "start frequency f-controller" of the speed controller and after
expiration of the delay time, the speed controller is activated.

b.) Stopping process


Coasting time (0..999 s) tN = 3 s

Function Upon resetting the operating bit, power reduction (if the active load controller is switched
on) is carried out. After opening the generator power circuit breaker, the coasting time is
started, and the engine rotates without load. On termination of the coasting time, the oper-
ating magnet is reset. The engine is stopped. If the firing speed is not reached, engine
starting is prevented for a firmly pre-specified time of 10 seconds. If the engine cannot be
stopped via the operating magnet, after 30 s, the "Shutoff malfunction" alarm message ap-
pears; a class 3 alarm is output.

38 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
2.6.2 Gas engine

Time jump without Pickup active: < 15 Hz


1500 1/min
min. speed starter is not reached
Start frequency
f-contr. + time
ZD (1)
min. speed starter
(Pickup ON)
[1/min] (2) [1/min]

Speed governor

Approach idle
gas position

Engine monitoring
activated

Start request

Gas valve

Ignition

Starter

t/s
tSt tZV tSPZ tZV tGV tEZ tMV tN tZN
Delayed engine
monitoring 00s

Ignition speed reached

Start attempt Start attempt


unsuccessful successful

Start Stop

The formula signs and indices mean:


tSta .......................... Approach idle gas position [s]
tZV ........................... Firing delay [s]
tGV .......................... Gas delay [s]
tEZ ........................... Engagement time [s]
tSPZ .......................... Time between two start attempts [s]
tMV .......................... Delayed engine monitoring [s]
tZN .......................... Ignition coasting [s]; pre-specified: 5 s
tN ........................... Coasting time [s]
(1).......................... Disengagement of the starter; Ignition and gas also ON
(2).......................... Switching ON the ignition

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 39
a.) Starting process
Explanation using entered data (see page 144, "Engine configuration")

Approach idle gas position (ON/OFF) ON


Firing delay (0..99 s) tZV = 3 s
Gas delay (0..99 s) tGV = 8 s
Engagement time (0..99 s) tEZ = 15 s
Time between two start attempts (0..99 s) tSPZ = 10 s

Function If the item is equipped with a three-position frequency controller, a continuous signal (time
adjustable) is output prior to starting the engine at the "Frequency down" relay output. The
starter is then set. Following the expiration of the firing delay time and if the engine is rotat-
ing with at least the set "minimum speed start", the ignition is switched on. Following the
expiry of the gas delay, the gas valve is then switched on. If the starting attempt is success-
ful, i.e., the firing speed was exceeded, the starter is disengaged again. The gas valve
and the ignition are held via the firing speed. After reaching the "starting frequency f-
controller" and after expiration of the delay time, the speed controller is activated.

b.) Stopping process


Coasting time (0..999 s) TZN = 3 s

Function On resetting the starting request, power reduction (if the active load controller is switched
on) is carried out. After opening the generator power circuit breaker, the coasting time is
started, and the engine rotates without load. On termination of the coasting time, the gas
valve is closed. The engine is stopped. If the firing speed is not reached, engine starting is
prevented for a firmly pre-specified time of 10 seconds. If the engine cannot be stopped,
the "Shutoff malfunction" alarm message appears after 30 s, a class 3 alarm is output.

Following negative deviation from the firing speed, the ignition remains set for a further
5 seconds so that the remaining gas is able to combust.

40 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
2.7 Operation of the power circuit breaker

Permissible preset limits Generator:


• Voltage UGen 75..115 % Unominal
• Frequency fGen 80..110 % fnominal

Busbar:
• Voltage UGen 85..112.5 % Unominal
• Frequency fGen 90..110 % fnominal

NOTE

For the description of the CB logic, please refer to Chapter 4.11.6 "Power circuit breaker logic" starting at
page 110.

2.7.1 Synchronization of the GCB

The generator power circuit breaker (GCB) will be synchronized with frequency and volt-
age correction if the following conditions are met simultaneously.

Automatic mode:
• the operating mode "AUTOMATIC" is selected;
• one of the circuit breaker logics "PARALLEL" (operation in parallel with the mains), "IN-
TERCHANGE" (interchange synchronization) or "CLOSED TRANSIT." (no-break-
transfer/overlap synchronization) has been switched ON in configuration mode;
• no alarm class 2 or 3 alarm is present;
• an "Automatic 1" (terminal 3) or "Automatic 2" (terminal 5) input has been applied, or a
remote starting signal has be activated via the interface or one more engine will be
applied in the emergency mode (and will be synchronized on the busbar).
• the busbar has been energized;
• the engine is running, and the generator voltage and frequency are within the pre-
specified limits (see page 41);
• the delayed engine monitoring has expired (this does not apply in the case of emer-
gency power);
• the rotating field of the generator and the mains voltages are identical (and no alarms
are displayed).

Manual mode:
• The operating mode "MANUAL" has been selected;
• one of the circuit breaker logics "PARALLEL" (operation in parallel with the mains), "IN-
TERCHANGE" (interchange synchronization) or "CLOSED TRANSIT." (no-break-
transfer/overlap synchronization) has been switched ON in configuration mode;
• no alarm class 2 or 3 alarm is present;
• the busbar has been energized;
• the engine is running, and the generator voltage and frequency are within the pre-
specified limits (see page 41);
• the push-button "GCB ON" was pressed.
• the rotating field of the generator and the mains voltages are identical (and no alarms
are displayed).

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 41
Load test mode:
• the operating mode "TEST" has been selected;
• one of the circuit breaker logics "PARALLEL" (operation in parallel with the mains), "IN-
TERCHANGE" (interchange synchronization) or "CLOSED TRANSIT." (no-break-
transfer/overlap synchronization) has been switched ON in configuration mode;
• no alarm class 2 or 3 alarm is present;
• the busbar has been energized;
• the engine is running, and the generator voltage and frequency are within the pre-
specified limits (see page 41);
• the "GCB ON" push-button has been pressed
• the rotating field of the generator and the mains voltages are identical (and no alarms
are displayed).

2.7.2 Closing the GCB without synchronization (GCB black start)

The generator power circuit breaker (GCB) is closed without synchronization if the follow-
ing conditions are met simultaneously:

Automatic mode:
• the operating mode "AUTOMATIC" has been selected;
• no alarm class 2 or 3 alarm is present;
• the option "GCB black start" has been set to "ON" in configuration mode;
• the busbar has not been energized;
• the engine is running, and the generator voltage and frequency are within the pre-
specified limits (see page 41);
• the "Reply: MCB is open" exists (the MCB is open);
• if the load is distributed via the CAN bus
- no GCB may be closed in the event of possible isolated operation in parallel with
other gensets,
- the genset with the lowest item number will be the first to close its GCB (see chap-
ter 4.9 "Basic settings configuration" on page 82).

Manual mode:
• the operating mode "MANUAL" has been selected;
• no alarm class 2 or 3 alarm is present;
• the busbar has not been energized;
• the engine is running, and the generator voltage and frequency are within the pre-
specified limits (see page 41);
• the "Reply: MCB is open" exists (the MCB is open);
• if the load is distributed via the CAN bus
- no GCB may be closed in the event of possible isolated operation in parallel with
other gensets,
- the genset with the lowest item number will be the first to close its GCB (see chap-
ter 4.9 "Basic settings configuration" on page 82).
• the push-button "GCB ON was pressed.

Switched-off generator monitors:


If the generator monitors are switched off, the CB logic and the control system are con-
trolled by internally defined limit values.

Generator monitors Voltage Frequency


ON Monitor values Monitor values
OFF UGen. < 75 % URated fGen. < 80 % frated
UGen. > 115 % URated fGen. > 110 % frated

42 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
2.7.3 Synchronization of the MCB [PCL1/PCM1-M]

The mains power circuit breaker (MCB) will be synchronized with frequency and voltage
correction if the following conditions are met simultaneously:

Automatic mode:
• the operating mode "AUTOMATIC" has been selected;
• one of the circuit breaker logics "PARALLEL" (operation in parallel with the mains), "IN-
TERCHANGE" (interchange synchronization) or "CLOSED TRANSIT." (no-break-
transfer/overlap synchronization) has been switched ON in configuration mode;
• no alarm class 2 or 3 alarm is present;
• the busbar has been energized;
• the mains voltage is present and within the permissible limits;
• the engine is running, and the generator busbar voltage and frequency are within the
pre-specified limits (see page 41);
• the "Reply: GCB is open" is not present (the GCB is closed);
• the input "Enable MCB" has been set;
• the rotating field of the generator and the mains voltages are identical (and no alarms
are displayed).

Manual operation:
• the operating mode "MANUAL" has been selected;
• one of the circuit breaker logics "PARALLEL" (operation in parallel with the mains), "IN-
TERCHANGE" (interchange synchronization) or "CLOSED TRANSIT." (no-break-
transfer/overlap synchronization) has been switched ON in configuration mode;
• no alarm class 2 or 3 alarm is present;
• the busbar has been energized;
• the mains voltage is available;
• the engine is running, and the generator busbar voltage and frequency are within the
pre-specified limits (see page 41);
• the" Reply: GCB is open" is not present (the GCB is closed);
• the input "Enable MCB" has been set;
• the "MCB ON" has been pressed;
• Load test: On termination of the load test (circuit breaker logics "INTERCHANGE" (in-
terchange synchronization) or "CLOSED TRANSIT. (no-break-transfer/overlap synchroni-
zation), the GCB is opened;
• the rotating field of the generator and the mains voltages are identical (and no alarms
are displayed).

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 43
2.7.4 Closing the MCB without synchronization (MCB black start) [PCL1 / PCM1-M]

The mains power circuit breaker (MCB) is closed without synchronization if the following
conditions are met simultaneously:

Automatic mode:
• the operating mode "AUTOMATIC" has been selected;
• the option "MCB black start" has been set to "ON" in configuration mode;
• the busbar has not been energized;
• the mains voltage is available;
• the "Reply: GCB is open" is present (the GCB is open);
• the input "Enable MCB" has been set.
• if the load is distributed via the CAN bus
- no MCB must be closed in the event of possible isolated operation in parallel with
other gensets,
- the item with the lowest item number will be the first to close its MCB (see chap-
ter 4.9 "Basic settings configuration" on page 82).

Manual mode:
• the operating mode "MANUAL" has been selected;
• the busbar has not been energized;
• the mains voltage is available;
• the "Reply: GCB is open" is present (the GCB is open);
• the input "Enable MCB" has been set;
• the "MCB ON" push-button has been pressed.
• if the load is distributed via the CAN bus
- no MCB must be closed in the event of possible isolated operation in parallel with
other gensets,
- the item with the lowest item number will be the first to close its MCB (see chap-
ter 4.9 "Basic settings configuration" on page 82).

Operation mode STOP


• The MCB will be closed when the "Enable MCB" (terminal 53) is set if this has been
enabled via the configuration.

44 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
2.7.5 Open GCB

The generator power circuit breaker (GCB) is opened both when the relay "Command:
GCB close" drops out (only if "continuous pulse" has been selected in configuration mode),
and via the closure of the relay "Command: GCB open". The GCB will be opened under
the following circumstances:

• if a mains watchdog is triggered and the GCB is uncoupled;


• in the operating mode "STOP";
• in the case of alarm class 2 or 3;
• upon pressing the "GCB OFF" or "MCB ON" push-button (depending on the CB logic
which has been set) in manual operating mode;
• upon pressing the "STOP" push-button in manual operating mode;
• upon pressing the "GCB OFF" or "MCB ON" push-button (depending on the CB logic
which has been set) in load test mode;
• in the event of automatic stopping in "AUTOMATIC" operating mode;
• following the "CLOSED TRANSIT." (no-break-transfer/overlap synchronization) of the
MCB;
• before the MCB is switched to the black busbar in the case of "OPEN TRANSIT."
(ATS/break-before-make/changeover) logic;
• in sprinkler operation, provided that no case of emergency power is present;
• following the "INTERCHANGE" (interchange synchronization) of the MCB.

2.7.6 Open MCB [PCL1/PCM1-M]

The mains power circuit breaker (MCB) is opened via the closure of the relay "Command:
MCB open" (the "continuous pulse" setting is not possible in the case of the MCB). The
MCB will be opened under the following circumstances:

• when the mains watchdog is triggered, if mains decoupling is set to MCB;


• if emergency power is triggered (mains failure);
• following the "CLOSED TRANSIT." (no-break-transfer/overlap synchronization) of the
GCB;
• prior to the closure of the GCB in the case of "OPEN TRANSIT." (ATS/break-before-
make/changeover) logic;
• upon pressing the "MCB OFF" or "GCB ON" push-button (depending on the CB logic
which has been set) in manual operating mode;
• upon pressing the "MCB OFF" or "GCB ON" push-button (depending on the CB logic
which has been set) in load test mode;
• following the "INTERCHANGE" (interchange synchronization) of the MCB.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 45
2.7.7 GCB Pulse/Continuous Pulse

Closing and opening of the GCB and the MCB are described in the following figures. Changing of the breaker control logic is
configured via the parameter "GCB close relay" and has the described effect on the signal sequence (the operation of the MCB
cannot be carried out by means of the continuous pulse). If the "Automatic breaker deblocking" is configured to "ON", an open pulse
is issued prior to each close pulse. The discrete input "Enable MCB" disables the closure of the MCB. A closed MCB is not opened.

• Breaker logic: 'Impulse'


Connection time
1 2 3 8
'Enable
MCB'

Time/s

4 7
'Command: close
MCB' (16/17)

Time/s

'Command: open .. 9 13
.. GCB' (41/42)
.. MCB' (39/40) 2/0,8 s
12

Time/s

'Reply: .. 5 6 11
.. GCB is open' (4/7)
.. MCB is open' (54/7)
10

Time/s

'Impulse' logic (GCB and MCB): 1 Enable MCB; 2 Synchronization; 3 Connect time reached:
• close GCB/MCB: 4 Closing pulse for GCB/MCB set; 5 Inherent delay; 6 Reply GCB/MCB; 7 Closing pulse deleted;
• open GCB/MCB: 9 Opening pulse GCB/MCB set; 10 Inherent delay; 11 Reply GCB/MCB; 12 Time delay (GCB: 2 s;
MCB: 0.8 s); 13 Opening pulse deleted.

• Beaker logic: 'Continuous'


4 9
'Command: close
GCB' (14/15)

Time/s

4 7
'Command: close
GCB' (14/15)

Time/s

'Continuous' logic (GCB only): 1 Enable; 2 Synchronization; 3 Connect time reached:


• close GCB: 4 Continuous pulse GCB set; 5 Inherent delay; 6 Reply GCB;
• open GCB: 9 Continuous pulse deleted and switch off pulse GCB set; 10 Switcher time element; 11 Reply GCB; 12 Open-
ing pulse deleted.

46 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
2.8 Monitoring power circuit breakers

2.8.1 Breaker connect time monitoring

If, in the case of synchronous generators, the "synchronization time monitoring" mask or, in
the case of asynchronous generators, the "breaker connection monitoring" mask is set to
"ON", synchronization time monitoring (connection monitoring in the case of asynchronous
generators) is carried out: If the synchronization of the GCB or MCB is started, the time
counter is started following the expiry of delayed engine monitoring. If, following the expiry
of the set time, the power circuit breaker has not been activated, a warning message
"GCB synchronization time exceeded" ("GCB connect time exceeded" in the case of asyn-
chronous generators) or "MCB synchronization time exceeded" is output as an F1 alarm.

2.8.2 Circuit breaker monitoring

NOTE

If during active "MCB monitoring", circuit breaker monitoring, an alarm is detected on closing the MCB,
this is carried out during activated emergency power.

Upon CLOSING If the " GCB monitoring" or "MCB monitoring" is set to "ON", generator and mains power
circuit breaker monitoring is carried out (exception: the power circuit breaker logic is set to
"EXTERNAL"). If the circuit breaker cannot be activated by the fifth attempt, an alarm
class F1 "GCB malfunction" or "MCB malfunction" alarm message is output. If the relay
manager is available (see chapter 4.17.2 "Relay manager" starting at page 132) a relay
is set with the parameter 74 or 75.

Upon OPENING If the reply is still detected 2 seconds after a CLOSE pulse (opening of GCB or MCB) that
the GCB or MCB is closed, an alarm message of alarm class F1 "GCB malfunction" or
"MCB malfunction" is also output. If a relay manager is available, a relay is set with pa-
rameter 76 or 77.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 47
2.9 Power circuit breaker logic

NOTE

For a description of CB logics, please refer to chapter 4.11.6 "Power circuit breaker logic" starting at
page 110. The synchronization conditions as described in chapter 0 "
Synchronization of the " starting on page 41 and chapter 2.7.3 "Synchronization of the MCB" starting on
page 43 are applicable.

2.9.1 CB logic "PARALLEL" [PCM1x]

NOTE

This CB logic must be selected for the following operating modes: isolated operation, isolated operation in
parallel with other gensets and operation in parallel with the mains.

In the event of an engine request,


• the GCB is synchronized and closed, and
• the necessary generator real power or re-active power is adjusted.

Following the withdrawal of the engine request,


• the generator power is reduced, the generator power factor ϕ is adjusted to "1",
• the GCB is opened and
• the engine is shut off following coasting.

The mains power circuit breaker is synchronized and closed if


• terminal 53 "Enable MCB" is set and
• the GCB is closed.

The mains power circuit breaker is switched to the black busbar if


• the GCB and
• the MCB are open and
• the busbar is de-energized and
• terminal 53 "Enable MCB" is available.

NOTE

On stopping the engine (no F3 alarm), power reduction is carried out before opening the GCB.

48 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
2.9.2 CB logic "INTERCHANGE" [PCM1-M]

Interchange synchronization is activated via the "INTERCHANGE" (interchange synchroni-


zation screen input.
NOTE

In order to perform this function correctly, you have to obey that the mains power measurement is
connected properly. The sign of the power measurement has to be determined correctly as well.

In the event of a engine request, a switch is made from mains to generator supply. In order
to achieve this,
• the GCB is synchronized and closed,
• the mains interchange is adjusted to "zero" and
• the MCB is opened.

After the engine request has been reset, a switch is made from generator to mains supply.
In order to achieve this,
• the MCB is synchronized and closed,
• the generator power is adjusted to "zero" and
• the GCB is opened.

2.9.3 CB logic "CLOSED TRANSIT." [PCL1/PCM1-M]

Closed transition (no-break-transfer/overlap synchronization) is activated via the "CLOSED


TRANSIT." screen input.

In the event of a engine request, a switch is made from mains to generator supply. In order
to achieve this,
• the GCB is synchronized and closed and
• the MCB is opened.

After the engine request has been reset, a switch is made from generator to mains supply.
In order to achieve this,
• the MCB is synchronized and closed and
• the GCB is opened.
NOTE

The power circuit breakers are opened regardless of the power.

2.9.4 CB logic "OPEN TRANSIT." [PCL1/PCM1-M]

The open transition/break-before-make/changeover logic is activated via the "OPEN


TRANSIT." screen input.

In the event of a engine request, a switch is made from mains to generator supply. In order
to achieve this,
• the MCB is opened and
• the GCB is closed.

After the engine request has been reset, a switch is made from generator to mains supply.
In order to achieve this,
• the GCB is opened and
• the MCB is closed.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 49
2.9.5 CB logic "EXTERNAL"

The external CB logic is activated via the "EXTERNAL" screen input. All switch control must
be carried out via a superordinate controller (e. g. PLC). Closing and opening pulses to the
MCB and the GCB are only output by this control system (PCx) in the "MANUAL" operating
mode. In the event of an alarm, the switches are opened by this control system (PCx) under
all circumstances.

2.10 Emergency power [PCL1/PCM1-M]

Prerequisite The emergency power function can only be activated in the case of synchronous genera-
tors via the "Emergency power ON" screen. Emergency power is carried out in "AUTO-
MATIC" or "TEST" operating mode regardless of the status of the discrete inputs "Auto-
matic 1" and "Automatic 2".

NOTE

If the "Engine enable" or "Engine block" function is assigned to terminal 6, emergency power can be
discretely prevented or interrupted from an external source. Please refer also to the description in
chapter 4.15.3 "Setting the control inputs " on page 135on this.

Activation of emergency power If the mains power reveals an alarm on at least one of terminals 50, 51 or 52 for the
duration of the time set in the "Emergency power delay time ON" input screen, emergency
power is activated. A mains voltage fault is defined as follows: If the mains watchdogs are
switched ON, the limit values set there are used; otherwise, the limits are internally defined
as follows:

Mains watchdogs Voltage Frequency


ON Monitor values Monitor values
OFF UMains < 85 % Urated fMains < 90 % frated
UMains > 112 % Urated fMains > 110 % frated

Emergency power is also triggered via the detection of a switch fault when the MCB is
switched on. In order to achieve this, the "Emergency power" (page 117) and "MCB moni-
toring" screens must be set to "ON" .

The following principles are observed in the case of emergency power:

• If emergency power is triggered, the engine is started under all circumstances, unless the
procedure is interrupted via an alarm or a change in operating mode.
• If the mains returns during starting, the MCB is not opened. The engine starts under all
circumstances, and waits without load until the mains settling time has expired. If a further
mains fault occurs during this time, the MCB is opened, and the GCB is switched to the
black busbar. The engine otherwise shuts off following the double expiry of the mains set-
tling time.
• The GCB is closed regardless of the engine delay time after the black starting limits have
been reached.
• If the mains returns during emergency power (GCB is closed), the mains settling time must
pass before reverse synchronization of the MCB occurs.

Emergency power In the event of active emergency power, the message "Emergency power" is displayed.

50 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
2.10.1 Emergency power with "PARALLEL" CB logic [PCM1-M]

Emergency power Following the recognition of the emergency power case, the emergency power delay time
expires before the engine is started. Once reaching the voltage and frequency limit values,
the MCB is opened, and the GCB is then switched to the black busbar. The genset takes
over the supply of the isolated network.

Return of the mains Following the return of the mains voltage, the item waits until the mains settling time has
expired (0.0..999.9 s, framework: 0.1 seconds, shown in the display), before carrying
out reverse synchronization of the mains power circuit breaker. After closing the mains
power circuit breaker, the genset assumes its original operating mode. If the generator is
shut off, power reduction is carried out provided that the real power controller is activated.

If the mains returns during starting, the mains power circuit breaker is not opened. During
the mains settling time, the genset operates without load, in order to enable the immediate
connection of the GCB in the event of further mains faults.

2.10.2 Emergency power with "OPEN TRANSIT." CB logic

Emergency power Following the recognition of the emergency power case, the emergency power delay time
expires before the engine is started. On reaching the voltage and frequency limit values,
the MCB is opened, and the GCB is then switched to the black busbar. The genset takes
over the supply of the isolated network.

Return of the mains Following the return of the mains voltage, the genset waits until the mains settling time has
expired (0..999 s, framework: 1 seconds, shown in the display), before it switches the
mains power circuit breaker back via a voltage-free ("black") busbar. If, following the expiry
of the mains settling time, an operating request is present, the genset remains in isolated
operation.

If the mains returns during starting, the mains power circuit breaker is not opened. During
the mains settling time, the genset operates without load, in order to enable the immediate
connection of the GCB in the event of further mains faults.

2.10.3 Emergency power with "CLOSED TRANSIT." CB logic

Emergency power Following the recognition of the emergency power case, the emergency power delay time
expires before the engine is started. On reaching the voltage and frequency limit values,
the MCB is opened, and the GCB is then switched to the black busbar. The genset takes
over the supply of the isolated network.

Return of the mains Following the return of the mains voltage, the genset waits until the mains settling time has
expired (0..999 s, framework: 1 seconds, shown in display). If no operating request is
present, reverse synchronization of the MCB is carried out following the expiry of this time.
Following the closure of the mains power circuit breaker, the generator power circuit
breaker is opened immediately and without any reduction in power.

If the mains returns during starting, the mains power circuit breaker is not opened. During
the mains settling time, the genset operates without load, in order to enable the immediate
connection of the GCB in the event of further mains faults.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 51
2.10.4 Emergency power with "INTERCHANGE" CB logic [PCM1-M]

Emergency power Following the recognition of the emergency power case, the emergency power delay time
expires before the engine is started. On reaching the voltage and frequency limit values,
the MCB is opened, and the GCB is then switched to the black busbar. The genset takes
over the supply of the isolated network.

Return of the mains Following the return of the mains voltage, the genset waits until the mains settling time has
expired (0..999 s, framework: 1 seconds, shown in the display). If no operating request is
present, reverse synchronization of the MCB is carried out following the expiry of this time.
Following the closure of the mains power circuit breaker, the generator power circuit
breaker is opened following the reduction in power.

If the mains returns whilst the engine is starting, the mains power circuit breaker is not
opened. During the mains settling time, the genset operates without load, in order to en-
able the immediate connection of the GCB in the event of further mains faults.

2.10.5 Emergency power with "EXTERNAL" CB logic

ATTENTION

Emergency power in accordance with DIN VDE 0108 is not possible in this CB logic!

Emergency power Following the recognition of the emergency power case, the emergency power delay time
expires before the engine is started. On reaching the voltage and frequency limit values,
the MCB is opened, the GCB is not activated. The GCB and the MCB are not otherwise
operated. Not even following the return of the mains.

2.10.6 Emergency power with MCB malfunction

MCB malfunction In the "AUTOMATIC" operating mode without a starting request, the control system is set to
emergency power standby. If the MCB is tripped, the control system attempts to reactivate
this. If this is not possible (due to an MCB alarm), the engine is started following the "MCB
malfunction", if the parameter "Emergency power” is set “ON”. Emergency power subse-
quently supplies the busbar. Only following the successful acknowledgement of the "MCB
malfunction" alarm, is the MCB synchronized and the engine shut off again on expiry of the
mains settling time.

52 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
2.11 Sprinkler operation

NOTE

The function "Sprinkler operation" must be assigned to terminal 6. Please refer also to the description in
Chapter 4.15.3 "Setting the control inputs " on page 135 on this issue.

ATTENTION!

Please note that a High signal must be applied at terminal 6 so that no sprinkler operation is carried out.
A Low signal informs the control system that the conditions for sprinkler operation have been met.

! Negative functional logic

Sprinkler "ON" If the signal at terminal 6 drops off, the sprinkler ON command is triggered. The message
"Sprinkler operation" is shown on the display. Up to 6 attempts are made to start the engine
(otherwise 3) if it is not yet in operation. All malfunctions which cause shutoff become mes-
sages. Exception: Terminal 34 or 61 and overspeed. Terminal 34 (alarm input) retains its
set alarm class (if terminal 34 is not present, this is terminal 61). It is advisable to assign the
EMERGENCY OFF here.

NOTE

Via the activation of "Sprinkler operation" (terminal 6), alarm classes F2 and F3 are converted to alarm
class F1 (exception: terminal 34 or 61 and overspeed).

Alarm class F2 and alarm class F3 → alarm class F1

"Sprinkler shutd. F1 active" In the mask "Sprinkler shutd. F1 active" you can choose whether the sprinkler alarm classes
Mains are still active during the sprinkler coasting or if the primary alarm class will be active after
reset of the sprinkler request (terminal 6).
MCB
A distinction is made between three operating conditions:
Busbar

1.) MCB is closed


GCB Sprinkler
pump (mains voltage available):
a)••The engine is stopped:
The engine will be started and the GCB will not be closed.

G M b) The engine runs: The GCB will be opened.

2.) MCB is open


(mains voltage available) and the parameter "Emergency mode” is ON.
a) The GCB will be closed or remains closed.
b) In the event of a generator overload, the GCB will be opened; following the alarm
acknowledgement the GCB will be closed again.

3.) MCB is open


(mains voltage available):
a) The MCB will be synchronized,
b) Following the synchronization of the MCB, the GCB will be opened.

Sprinkler "OFF" Via the completion of the sprinkler input circuit, the sprinkler ON command is withdrawn;
however, sprinkler operation is retained. The message "Sprinkler coasting" appears. Sprin-
kler operation is automatically terminated 10 minutes later. Earlier termination can be
achieved via the "STOP" operating mode. On termination of sprinkler operation, malfunc-
tions which cause shutoffs become active again.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 53
2.12 Direction of power

If the item's current transformers are wired according to the pin diagram shown, the follow-
ing values are displayed:

• Positive generator real power The generator supplies real power.

• Inductive gen. power factor ϕ The generator is overexcited and supplies


inductive re-active power.

• Positive mains real power Real power is supplied to the mains.

• Inductive mains power factor ϕ The mains receives inductive re-active power.

MAINS

MCB
mains circuit breaker

s2 (l) S2 (L)
P Active power
27 pos Display positive
PCMx
Reactive power
28 Q
s1 (k) S1 (K) ind Display capazitive

BUSBAR

PCx

GCB
generator circuit breaker

s2 (l) S2 (L)
P Active power
25 pos Dispaly positive
PCL1
PCMx
Reactive power
26 Q
s1 (k) S1 (K) ind Display inductive

GENERATOR

54 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
2.13 Analog controller outputs (option ..-A)

As an alternative to a three-position controller output, the item may also be equipped with
an analog controller output. Other configuration masks then appear in configuration mode.
The analog PID controller forms a closed-loop control loop together with the controlled sys-
tem (usually a first-order lag element). The parameters of the PID controller (proportional-
action coefficient KPR, derivative-action time TV and reset time Tn) can be modified individu-
ally. The configuration screens are used for this purpose.

Influenciny
Control loop Kpr Tn Tv
quantity
Tt Kp T1

PID controller Lag element (Tt) Controlled system (PT1)

If an abrupt disturbance variable is applied to the control loop, the reaction of the con-
trolled system can be recorded at the output as a function of time (step response).

Step response x
(Example) xm
Tolerance band

xd
1

T rise Rise time


T sett Settling time
xm Overshoot
xd System deviation

0
0 Trise Tsett t/s

Various values can be obtained from the step response; these are required for adjusting the
controller to its optimum setting:

Rise time Trise Period starting when the value of the control variable leaves a predefined tolerance range
for the control variable following a step in the disturbance variable or reference input vari-
able and ending the first time the value re-enters this range.

Setting time Tsettling Period starting when the value of the control variable leaves a predefined tolerance range
for the control variable following a step in the disturbance variable or reference input vari-
able and ending when the value re-enters this range permanently.

Overshoot xm Highest transient setpoint value deviation during the transition from one steady-state condi-
tion to a new steady-state condition following modification of the disturbance variable or
reference input variable (xm Optimal ≤ 10 %).

System deviation xd Permanent deviation from the final value (PID controller: xd = 0).

By different conversions from these values, the values KPR, Tn and TV can be determined.
Moreover, it is possible, by performing various calculations, to determine the optimal con-
troller settings, e. g. by calculating compensation or adjustment of the time constants, T-sum
rule, symmetric optimum, Bode-diagram. Other setting procedures and information may be
obtained from current literature.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 55
2.13.1 Controller setting

CAUTION!

The following must be observed regarding the controller setting:


• Ensure that the emergency shutdown system is ready for use.
• While determining the critical frequency, pay attention to the amplitude and frequency.
• If the two values change uncontrollably:

! EMERGENCY SHUTDOWN

a.) Initial state


Initial state The start position of the controller is determined using the initial state of the controller. If the
controller is switched off, the basic setting can be used to output a fixed controller position.
If "MANUAL" operating mode has been selected, the initial state signal is output only with
the "START" push-button. Even when the analog controller is switched off, the initial state
can be freely adjusted (e. g. the speed controller can be controlled in a linear manner). On
setting the "STOP" push-button, the analog controller is switched off again.

Initial state Initial state frequency controller 0..100 %


Frequency = 000%
Analog controller output setting with controller switched off. This value is also used as the
initial value.

b.) General settings


The setting rule described below only serves as an example. Whether this method is suit-
able for setting your particular controlled system has not been and cannot be taken into ac-
count as each controlled system behaves uniquely.

There are various methods of setting a controller. The setting rules of Ziegler and Nichols
are explained below (determination for abrupt disturbances on the system input); this setting
method assumes a pure lag element connected in series with a first-order lag system.

1. Controller operated as a P-only controller


(where Tn = ∞ [screen setting: Tn =0], TV = 0).
2. Increase gain KPR (P-gain) until the control loop oscillates continuously at KP = KPkrit.

Attention If the engine starts to oscillate uncontrollably, carry out an emer-


gency shutdown and alter the screen setting accordingly.

3. At the same time: measure the critical cycle duration Tcrit


4. Set the parameters:

PID-controller PI-controller
KPR = 0.6 × KPcrit KPR = 0.45 × KPcrit
Tn = 0.5 × Tcrit Tn = 0.83 × Tcrit
TV = 0.125 × Tcrit

56 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
Step response

Controller setting Conroller setting Controller setting


Optimal (xm ≤ 10 %) Tcrit Incorrect

x x x

1 1 1

0 0 0
0 t/s 0 t/s 0 t/s

P-gain P-gain (KPR) Proportional-action coefficient 1..240


Kpr=000
The proportional-action coefficient KPR indicates the closed-loop control system gain. The
variable to be controlled is achieved more rapidly by increasing the P-gain.

Reset time Reset time (Tn) 0.2..60.0 s


Tn=00.0s
The reset time Tn represents the I-component of the PID controller. The I-component results in
permanent control deviation being eliminated in the controlled state.

Derivative time Derivative-action time (TV) 0.00..6.00 s


Tv=0.00s
The derivative-action time TV represents the D-component of the PID controller. An increase
in the phase reserve (stability) and the attenuation results from increasing this parameter.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 57
2.14 Load and/or var sharing [PCM1x]

Control guarantees that, in every operating condition (operation in parallel with the mains,
isolated operation in parallel with other gensets or reverse synchronization of the busbar to
the mains), the real power (in reference to the relevant nominal load) is evenly shared over
the gensets operating in parallel to the busbar. Those items that are found in the "Test" or
"Automatic" operating mode are involved in the load or var sharing. Moreover, a start
command has been issued and there are no alarms present that would shut down the sys-
tem.

Operation in parallel with the mains Each controller involved in load/var sharing influences the genset to which it is assigned
with mains interchange control in such a manner that the real power set at the mains interchange point (main control
variable) remains constant. All items are interlinked via a CAN bus, via which any devia-
tion in real power (generator power) can be determined for each genset. This control
variable is taken into consideration on controlling the interchange load. The weighting,
with which the secondary and the main control variable (= "reference variable") are
processed, can be set via a factor. In controlled state, the set real power flows at the
mains interchange point, whereby the total real power is subdivided equally amongst
those gensets involved in distribution control. If a constant power (F..fixed value) has
been entered as the setpoint value for a genset, this genset is no longer involved in
distribution control.

Isolated operation in parallel with Each controller involved in load/var sharing influences the genset to which it is assigned
other gensets in such a manner that the rated frequency (main control variable) which has been set
remains constant. All items are interlinked via a CAN bus, via which any deviation in
real power (generator power) can be determined for each genset. This control variable is
taken into consideration on controlling the frequency. The weighting, with which the
secondary and the main control variable (= "reference variable") are processed, can be
set via a factor. In controlled state, the isolated system has the set rated frequency,
whereby the total real power (in reference to the relevant nominal power) is subdivided
equally amongst those gensets involved in distribution control.

Reverse synchronization of the busbar Distribution is carried out according to the type of isolated operation. However, the set-
to the mains point value for the frequency is formed from the mains frequency (+/-0.1 Hz). The relay
outputs "Command: close GCB" for all items can be switched in parallel.

Prerequisites It is imperative that the rated system frequencies (page 82), the start/stop parameters
(page 100) and the circuit breaker logics (page 110) are set to the same values for all
items involved in distribution control.

58 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
Description of the interface for distribution Distribution control is based on a multi-master-capable bus between the items. This structure enables
control the parallel operation of up to 8 gensets.

The following must be noted to ensure 1. The maximum bus length must not exceed 250 meters.
trouble-free operation: 2. The bus must be terminated at each end with terminating resistors which correspond to the wave
impedance of the bus cable (approx. 80..120 Ω).
3. The bus must be of a linear structure. Dead-end feeders are not permissible.
4. Screened "Twister-Pairs" are preferable for use as the bus cable (Ex.: Lappkabel Unitronic LIYCY
(TP) 2×2×0.25, UNITRONIC-Bus LD 2×2×0.22).
5. The bus cable must not be routed in the vicinity of heavy current power lines.

Wiring diagram

X1 X2 X3 X4 X5 X1 X2 X3 X4 X5 X1 X2 X3 X4 X5
Terminal Terminal
CAN-H

CAN-L

CAN-H

CAN-L

CAN-H

CAN-L

CAN-H

CAN-L
GND

GND

GND
Termination

Termination
resistance resistance

Note:
The termination must be
effected with a resistor
which corresponds to the
wave impedance of the
used cable (e. g. 100 Ω )

CAN bus CAN bus CAN bus

2.14.1 Load/var sharing via the CAN bus

Whether, and the manner in which, a genset carries out real power or frequency control in
isolated operation in parallel with other gensets, is defined by the "real power distribution
reference variable." parameter in % in chapter 4.10.6 "Load/var sharing" on page 99 of
this manual. In this case, 10 % means increased real power control, and 99 % increased
frequency control. This parameter must be set individually for each genset.

In the case of the following control system, it must be noted that each item calculates the
mean utilization factor of all items from the data transmitted via the CAN bus, and then
compares this with its own utilization factor. The utilization factor is compared with the ref-
erence variable, and results in the new reference variable. Frequency and real power con-
trol are simultaneously carried out in these items (corresponding to the reference variable).

Frequency control is carried out via the measured voltage/frequency of the voltage system.
The pickup is used merely for monitoring functions, or is available as an actual control
value to the secondary controller.

f actual [Hz]

P actual [kW]
f set

n actual [min-1]
Leading value 10..99 [%]

10 % = only P control
99 % = only f control
Σ P nominal (via CAN)

P diff [%]
Calculation

P actual [kW]
P Utilization factor of this engine [%]
Σ P actual (via CAN)
Calculation
P nominal [kW] 2001-08-06 Leistungsverteilung Blockschaltbild.skf

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 59
2.15 Language manager

In order to load a different language into the control, please proceed as follows:

1.) Establish a connection between your PC and the control via the direct configuration
cable (FL-CABLE-RS232) or via a PCK4. To do this insert one end into the COM port of
your PC and the other end into the respective socket of the control.

2.) Enter the password for code level 2 into the control.

3.) If you use the FL-CABLE-RS232, the parameter „Direct. Para” has to be set “YES”.
If you use the PCK 4, the parameter „Direct. Para” has to be set “NO”.

4.) Please enter the number (1..14) into the mask "Generator number", with which you ad-
dress the PCx via FL-SOFT3.

5.) Now, scroll to the configuration mask "Language" and select the basic language by se-
lecting "first".

6.) Start the program FL-SOFT3 and enter the password.

7.) Open the respective .cfg file via menu "File", "open".

8.) Start the communication via the menu "Communication", "Connect".

9.) Select "Parameterize" in the menu item "Devices".

10.) Enter the password for the code level 2.

11.) Close the Parameterization window.

12.) Select the menu item "Devices" and "Load language".

13.) Load the respective language file using the button "Load language file ..."

14.) Check "All texts" and afterwards select "Transfer language".

15.) If an additional language is to be loaded after transmission of the first language, the
second language has to be selected in the configuration mask "Language" by select-
ing "second". Repeat steps 12.) through 14.).

Language Language first/second


--------------------
first All texts are displayed in the first language.
second All texts are displayed in the second language.

60 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
2.16 Connection to external components

2.16.1 Pickup input

See also chapter 4.18.4 "Pickup" on page 148.

In order to configure the Pickup input, the following values must be configured:

• Rated speed (min-1)


• Number of teeth of the Pickup speed sensor per revolution of the engine or number of
Pickup impulses per revolution of the engine.

2.16.2 Speed governor

NOTE

Please note the wiring diagram of the speed governor. For configuration of the speed governor you need
the PC program.

Three-position controller +24 V DC 0 V DC SG 2 / SG 2D


Common 8 12 Common
Higher 9 10 Higher
Lower 10 9 Lower

Analog output 20 mA SG 2 / SG 2D
Ia 8 7 + (IN)
GND 9 8 - (OUT)
10

2.16.3 Digital I/O expansion board EM1-D [PCM1x]

NOTE

Please note the wiring diagram of the EM1-D. For configuration of the digital expansion board you need
the PC program. To the CAN bus there can be max. two EM1-D simultaneously be connected and be
activated by the PCM1x Please note the description of the configuration masks of the EM1-D linking at
page 134/143.

Control Device (e.g. PCMx) External component (e.g. EM1)


A A
Termination Termination
B B
CAN bus

CAN bus

GND C C GND
CAN-H D D CAN-H
CAN-L E E CAN-L

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 61
2.17 Alarms

2.17.1 Alarm classes

The monitoring functions are divided into four alarm classes:

F0 Warning alarm This alarm does not lead to an interruption of the operation. An alarm message is dis-
played without a centralized alarm.
! Alarm text.
F1 Warning alarm This alarm does not lead to an interruption of the operation. A centralized alarm will be
output.
! Alarm text + flashing "alarm" LED + group alarm relay (horn).
F2 Triggering alarms This alarm leads to the shutdown of the engine. First the real power is reduced before the
GCB is opened. A coasting is carried out.
! Alarm text + flashing "alarm" LED + group alarm relay (horn) + coasting.
F3 Triggering alarm This alarm leads to the immediate opening of the GCB and to the shutdown of the engine.
! Alarm text + flashing "alarm" LED + group alarm relay (horn) + shutdown.

NOTE

Via the activation of "Sprinkler operation" (terminal 6), alarm classes F2 and F3 are converted to alarm
class F1. Exception: terminal 34 (or terminal 61, if terminal 34 is not available) and overspeed.

Alarm class F2 and alarm class F3 → alarm class F1

62 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
2.17.2 Internally detected alarms

List of alarms determined internally depending on the variables which are monitored:

Type of alarm see chapter Alarm Alarm text Relay output


class (terminal)
Engine overspeed (Pickup) 4.13.7 F3 Over speed
Generator overfrequency 4.13.7 F3 Over frequency
Generator underfrequency 4.13.7 F3 Low frequency
Generator overvoltage 4.13.8 F3 Gen.overvolt.
Generator undervoltage 4.13.8 F3 Gen.undervolt.
Generator overcurrent level 1 4.13.6 F3 Gen.overcurr. 1
Generator overcurrent level 2 4.13.6 F3 Gen.overcurr. 2
Reverse/reduced load 4.13.4 F3 Revers/min.power
Overload 4.13.4 F2 Gen.overload
Load imbalance 0 F3 Asymmetric load
Mains overvoltage 4.13.11 F0 Mains-overvolt.
Mains undervoltage 4.13.11 F0 Mains-undervolt. F1, F2, F3
Mains overfrequency 4.13.9 F0 Mains-overfreq. Group alarm
Mains underfrequency 4.13.9 F0 Mains-underfreq. via the
Mains phase/vector shift 4.13.12 F0 Vectorjump Relay manager
Battery undervoltage 0 F1 Batt.undervolt. with the
GCB synchronization time monitoring 4.11.9 F1 GCB syn.failure parameter 85
MCB synchronization time monitoring 4.11.9 F1 MCB syn.failure
Switching to black busbar time monitoring 4.11.10 F1 Failure df/dVmax.
fault P control, GCB will be opened after time F0:
--- F1 P ramp: GCB opened No output
"Boost/Settle ramp openedt
of a group alarm
Mechanical GCB malfunction on closing 4.11.11 F1 GCB close failure
Mechanical MCB malfunction on closing 4.11.11 F1 MCB close failure
Mechanical GCB malfunction on opening 4.11.11 F1 GCB open failure
Mechanical MCB malfunction on opening 4.11.11 F1 MCB open failure
Faulty ref. power zero control with interch. syn. GCB 4.11.8 F1 Power not zero
Maintenance call 4.19.1 F1 Service
Interface monitoring X1..X5 4.11.3 F1 Interf.err.X1X5
Interface monitoring Y1..Y5 4.11.3 F1 Interf.err.Y1Y5
Plausibility control Pickup/generator frequency 4.13.7a.) F3 Pickup/Gen.freq.
Shutoff malfunction --- F3 Stop failure
Start failure --- F3 Startfail
Unintended stop --- F3 Not wanted stop

Note: In the event of mains faults, the GCB or the MCB is opened according to the setting, and is
closed again following the mains settling time.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 63
2.17.3 Alarm acknowledgement

DANGER!!!

The engine may start unintentionally if an alarm, which caused the engine to shut down, is acknowledged
and an enabling is still present. Before acknowledging the alarm, check the cause of the alarm, in order to
protect operating personnel located in the vicinity of the system against injuries, and to protect the engine
against unintentional destruction.
⇒ If the cause of the alarm is not known or is unclear, NEVER press the acknowledge push-button! The
destruction of the engine cannot otherwise be ruled out !

By pressing the "QUIT" push-button, the output of the centralized alarm and the alarm mes-
sages on the LC display are acknowledged according to the following logic:

NOTE

In order to acknowledge alarm messages via terminal 6, the "acknowledgement" function must be
assigned to this terminal. Please see also the description in chapter "Adjust function of terminal 6" on
page 136.

Horn After 2 minutes the horn is reset regardless of the acknowledgement of an alarm.

Interface All internal errors are conveyed via the interface.

NOTE

By acknowledging the alarms via the interface there is no difference of "short acknowledge" and "long
acknowledge". After 0.1 s it will be "long acknowledged".

a.) Short acknowledgement (< 2.5 s)


Meaning The "QUIT" push-button is pressed for 0.5 s < t < 2.5 s or
the terminal 6 is set for 0.5 s < t < 2.5 s.

Result - The LED "alarm" is continually illuminated.

Acknowledgement via Operating mode


RESET button Terminal 6 Interface STOP AUTO TEST MANUAL
1 x x 1 1 1 1
0 1 x 1 1 0 0
0 0 1 0 1 0 0
x..no meaning

64 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
b.) Long acknowledgement (> 2.5 s)
Meaning The "QUIT" push-button is pressed for t > 2.5 s or
terminal 6 is set for t > 2.5 s or
the acknowledgement bit via the interface is set.

Result - The LED "alarm" switches off,


- the group alarm relays F1, F2 and F3 are reset and
- the display messages are acknowledged.

Tables for Warning alarms Acknowledgement via Operating mode


(alarm classes 0 and 1), RESET button Terminal 6 Interface STOP AUTO TEST MANUAL
if there are no alarms of alarm class 2 or 3 1 x x 1 1 1 1
present 0 1 x 1 1 0 0
0 0 1 0 1 0 0
x..no meaning

Tables for alarms causing a shutdown Acknowledgement via Operating mode


(alarm classes 2 and 3) RESET button Terminal 6 Interface STOP AUTO TEST MANUAL
1 x x 1 0 0 1
0 1 x 1 1 0 0
0 0 1 *) 0 1 0 0
x..no meaning
*) only if parameter "Quit F2, F3 via interface" is enabled

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 65
3 Display elements and push-buttons

3.1 Pressure-sensitive front membrane

The pressure-sensitive membrane of the front panel consists of a plastic coating. All keys
have been designed as touch-sensitive membrane switch elements. The display is an LC
display, comprising 2 ×16 characters, which are indirectly illuminated in red. The contrast
of the display can be infinitely adjusted via a rotary potentiometer positioned on the left.
The configuration bushing is located on the left side of the item. Please connect the direct
configuration cable there (FL-CABLE-RS232).

3.1.1 PCL1 & PCM1-M

PCM1-M
V /kV AL1 AL2 AL3

28

STATUS / ALARM / PARAMETER


1 2 3
11
U L1 L2 L3
+10%
12 U 14
4

15 13 16
17

18 fN
5
6 19
22
7
20 21 23
29 8 9 10
30 24 25 26 27
-10%

3.1.2 PCM1-G

PCM1-G
V /kV AL1 AL2 AL3

28

STATUS / ALARM / PARAMETER


1 2 3
11
U L1 L2 L3
+10%
12 U 14
4

15 13 16
17

Parallel fN
5
6
22
7
20 21 23
29 8 9 10
30 24 25 26 27
-10%

66 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
3.1.3 Short description of LEDs and push-buttons

____________________________ Light-emitting diodes ________________________________________ Buttons

1 "UL1" ................................................... Voltage L1 12 "U SELECT".................................... Switch display


2 "UL2" ................................................... Voltage L2 12 "U SELECT"...................................... Increase digit
3 "UL3" ................................................... Voltage L3 13 "STATUS / ALARM" ........................Route message
4 "Alarm" ............................... Alarm message present 13 "STATUS / ALARM " ....................Confirm selection
5 "NLS closed" ...........................Reply: MCB is closed 14 "PARAMETER" ...................... Activate setpoint value
5"Parallel" ................... Status message "Mains parallel" 14 "PARAMETER " ...........Move one position to the right
6 "Monitoring"...................... Monitoring function active 15 "RESET".................... Acknowledge alarm messages
7 "GLS closed" ...........................Reply: GCB is closed 16 " - " .....................................Reduce setpoint value
8 " 0 " .................................... Mode "STOP" selected 17 " + "...................................Increase setpoint value
9 "AUTOMATIC" ............Mode "AUTOMATIC" selected 18 " I " (MCB ON) ............... Close mains CB manually
10 "MANUAL" ....................Mode "MANUAL" selected 19 " O " (MCB OFF)............. Open mains CB manually
11 "-10%..fn..+10%".............................Synchroscope 20 "STOP" ................................Stop engine manually
21 "START" ............................... Start engine manually
22 " I " (GCB ON) .......... Close generator CB manually
________________________________________Display 23 " O " (GCB OFF) ........ Open generator CB manually
24 " 0 " (STOP)..........................Stop engine manually
28 "LC display" LC display 25 "AUTOMATIC" ........... Activate "AUTOMATIC" mode
29 "Connector" ........................... Configuration socket 26 "MANUAL" .....................Activate "MANUAL" mode
30 "Potentiometer" ............................... adjust contrast 27 "TEST" ................................. Activate "TEST" mode

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 67
3.1.4 Overview of key functions

Automatic operating mode


Engine GCB MCB Setpoint

U
annuncia- voltage Setpoint QUIT STOP MAN AUTO TEST Start STOP ON OFF ON OFF raise lower
tion display value
MANUAL
start engine 1st 2nd
stop engine 1st 2nd
close GCB 1st 2nd
open GCB 1st 2nd
close MCB 1st 2nd
open MCB 1st 2nd
nd
raise setpoint value 2 1st 3rd
lower setpoint value 2nd 1st 3rd
AUTOMATIC
start engine and DI or operating mode 1st
stop engine and DI or operating mode Yes 1st
close GCB and DI or operating mode 1st
open GCB and DI or operating mode 1st
close MCB and DI or operating mode 1st
open MCB and DI or operating mode 1st
raise setpoint value 2nd 1st 3rd
lower setpoint value 2nd 1st 3rd
TEST 1st
start engine 1st
start load test 1st 2nd
end load test 1st
end load test (depends on 1st
the type of switch)
raise setpoint value 2nd 1st 3rd
lower setpoint value 2nd 1st 3rd
STOP 1st
LED test 1st 1st
Operating mode "configuration"
U

Select Digit Cursor


st
start configuration 1 1st
Confirm and next screen 1st
previous screen 1st 1st
next pos./change text 1st
raise position 1st
end configuration 1st 1st

68 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
3.2 LEDs

Lamp test The LED's can be checked via a lamp test. In order to achieve this, the "Setpoint↑" and
"Setpoint↓" push-buttons must be pressed simultaneously.

1 2 3 ........................... LED Voltage control Color "GREEN"


"U L1 .. U L2 .. U L3"
The LED's "UL1", "UL2" and "UL3" show which voltage (UL1N, UL2N, UL3N, UL12, UL23 or UL31) is
currently being displayed. This applies both to the generator and the rated voltage dis-
play.

4 ................................... LED Alarm Color "RED"


"RESET" (Alarm)
If the "RESET" LED illuminates, an alarm is present in the item; this is processed according
to its alarm class. The message and the type of alarm are shown on the LC display. If this
LED flashes, a new alarm has occurred within the last two minutes. Via brief acknowledg-
ment, this switches to continuous illumination, and the centralized alarm (horn) is ceased.

5 ................................... LED Reply: MCB is closed / Mains parallel Color "GREEN"


[PCL1 or PCM1-M] "MCB ON"
[PCM1-G] "Mains parallel" [PCL1 or PCM1-M] Items with two power circuit breakers: The "MCB ON" LED indi-
cates that the mains power circuit breaker is closed.
[PCM1-G].. Items with one power circuit breaker or items which have been made into 1-
CB items via external wiring [see chapter 2.1.2 "... systems with one power
circuit breaker" on page 27): The "Mains parallel" LED indicates that the gen-
set is operating in parallel with the mains.

6 ................................... LED Engine monitoring Color "GREEN"


"Monitoring"
If the "Monitoring" LED is lit, engine monitoring is activated, i. e., in addition to the perma-
nently monitored alarm inputs, the delayed programmed alarm inputs are also monitored.
Generator underspeed, underfrequency, undervoltage and reverse power are also moni-
tored.

7 ................................... LED Reply: GCB is closed Color "GREEN"


"GCB ON"
The "GCB ON" LED signals that the generator power circuit breaker is closed.

8 ................................... LED Operating mode "STOP" Color "RED"


" 0 " (STOP)"
If the LED " 0 " (STOP) is illuminated, the "STOP" mode has been selected. If this LED
flashes, a firing speed is detected in "STOP" mode.

9 ................................... LED Operating mode "AUTOMATIC" Color "YELLOW"


"AUTOMATIC"
If the "AUTOMATIC" LED is lit, the "AUTOMATIC" operating mode is active. The push-
buttons for direct activation of the power circuit breaker and the start / stop push-buttons
are de-activated.

10 ................................. LED Operating mode "MANUAL" Color "YELLOW"


"MANUAL"
If the "MANUAL" LED is lit, the "MANUAL" operating mode is active. The push-buttons for
direct activation of the power circuit breaker and the start / stop push-buttons are de-
activated.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 69
11 ................................. LED Phase position/synchroscope Colors "RED/YELLOW/GREEN"
"-10%..fN..+10%"
Normal operation ......The LED's between -10 % and +10 % serve to visualize the gen-
erator frequency. The rated frequency (fN) is entered in the "gen-
erator rated frequency" screen. If the frequency is greater than
+10 % or less than -10 %, the corresponding outer LED flashes
LED.
Configuration ............If, in configuration mode, the service display is "ON" and the
double voltage/double frequency display is active, the LED's
show the current phase angle between the two displayed volt-
ages. The green LED in the center of the 15 LED's indicates that
the measured phase angle between the voltage systems dis-
played is less than 12 ° electrical. The phase angle is only dis-
played if the frequencies of the two voltages are within the fol-
lowing permissible ranges:

Generator............................. 88..112 % fN
Mains .................................. 96..104 % fN

A distinction is made between two directions of rotation:


-10 % → +10 %
On running the LED's from left to right, the genera-
tor frequency is too high, i. e., the generator is
turning too fast;
+10 % → -10 %
On running the LED's from right to left, the genera-
tor frequency is too low, i. e., the generator is
turning too slowly.

3.3 Push-buttons

3.3.1 Display touch

In order to facilitate the setting of the parameters, the push-buttons have an AUTOROLL func-
tion. It allows to switch to the next setting and configuration screens, the digits, or the cursor
position. The AUTOROLL function will only be activated when the user depresses the corre-
sponding keys for a certain period of time.

12 .................PUSH-BUTTON U SELECT Color "BLUE"


"U SELECT"
Normal operation..."U SELECT - By pressing this push-button, the generator and mains
voltage display is moved forwards. Note: If this push-button is
pressed for at least 5 seconds, the counter that can currently be seen
in the display is (re)set.
Configuration ........"U SELECT" - With this push-button, the number at which the cursor is
currently located is increased by one digit. The increase is restricted
by the admissible limits (see list of parameters included in the appen-
dix). In case the maximum number is reached which can be set, the
number automatically returns to the lowest admissible number.

70 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
13 ..................PUSH-BUTTON STATUS/ALARM Color "BLUE"
"STATUS / ALARM"
Normal operation..."STATUS / ALARM" - By pressing this push-button, the display of the
operating and alarm messages can be advanced.
Configuration ........"STATUS / ALARM" - A jump is made to the next input screen. If the
value originally displayed has been changed via the "U SELECT" or
"PARAMETER" push-buttons the newly set value is saved by pressing
the "STATUS / ALARM" push-button once. By pressing this push-button
again, the user causes the system to display the next entry screen.

14 .................PUSH-BUTTON PARAMETER Color "BLUE"


" PARAMETER"
Normal operation..."PARAMETER" - By pressing this push-button, the individual setpoint
values are displayed. The displayed setpoint values can be adjusted
with the "Setpoint +" or "Setpoint −" push-buttons. Certain setpoint val-
ues, which are entered into the item from external sources, can only
be viewed.
Configuration ........"PARAMETER" - This push-button is used to move the cursor one posi-
tion to the right. When the last right-hand position is reached, the
cursor automatically moves to the first position left-hand of the value to
be entered.

DANGER!!!

The engine may start unintentionally if an alarm, which caused the engine to shut down, is acknowledged
and an enabling is still present. Before acknowledging the alarm, check the cause of the alarm, in order to
protect operating personnel located in the vicinity of the system against injuries, and to protect the engine
against unintentional destruction.
⇒ If the cause of the alarm is not known or is unclear, NEVER press the acknowledge push-button! The
destruction of the engine cannot otherwise be ruled out !

15 .................PUSH-BUTTON Acknowledgement Color "NONE"/"BLUE"


"RESET"
The alarm messages are acknowledged using the "RESET" push-button, i. e., the alarm in-
dications on the LC display disappear and the "Alarm" LED goes out. The operating vari-
able display is set on the basic screen. Alarm class F2 and F3 alarms can only be ac-
knowledged in the "STOP" and "MANUAL" operating modes.

16 17 ...........PUSH-BUTTON Setpoint +..Setpoint


+ − Color "BLUE"
"Setpoint •..•"
By pressing the "Setpoint +" or "Setpoint - push-buttons, the setpoint selected via the "Set-
point" push-button is changed accordingly. Only those values which are available in the
relevant operating mode and which were switched on during configuration can be
changed. If the two push-buttons are depressed simultaneously, the lamp test is activated.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 71
3.3.2 Operation of the power circuit breakers

18 19 ...........PUSH-BUTTON MCB "ON/OFF" Color "RED"/"GREEN"


"I/O"
(MCB ON/OFF) (only enabled if manual operating mode ("MANUAL" push-button) or test mode ("TEST"
push-button) has been selected).
Push-button " I " (MCB ON) Depending on which power circuit breaker logic has been
set, the MCB can be closed by pressing the " I " (MCB ON) push-
button. This process can be aborted if the " O " (MCB OFF) CB OFF"
or " I " (MCB ON) push-button is actuated or the operating mode is
changed.
Push-button " O " (MCB OFF) By pressing the " O " (MCB OFF) push-button, the genera-
tor power circuit breaker can (depending on the power circuit
breaker logic) be opened, or synchronization of the MCB can be
aborted if started.

20..21 ......... PUSH-BUTTONS Engine "Start/Stop" Color "GREEN"/"RED"


"START / STOP"
START...................Using this push-button the engine is started in "Manual" operating
mode. The starter and the operating magnet are activated by press-
ing the push-button, whereby the starter is de-activated after the firing
speed has been reached, and the operating magnet remains picked
up. The push-button can now be enabled.
STOP ....................This push-button is used to stop the engine by de-activating the oper-
ating magnet.

22 23 ...........PUSH-BUTTON GCB "ON/OFF" Color "RED"/"GREEN"


[PCL1/PCM1-M] "I/O"
(GCB ON/OFF) (only enabled if manual operating mode ("MANUAL" push-button) or test mode ("TEST"
push-button) has been selected).
Push-button " I " (GCB ON) Depending on which power circuit breaker logic has been
set, the GCB can be closed by pressing the " I " (GCB ON) push-
button. This process can be aborted if the " O " (GCB OFF) or " I "
(GCB ON) push-button is actuated or the operating mode is
changed.
Push-button " O " (GCB OFF) By pressing the " O " (GCB OFF) push-button, the mains
power circuit breaker can (depending on the power circuit breaker
logic) be opened, or synchronization of the GCB can be aborted if
started.

3.3.3 Operating mode selector switch

24 .................PUSH-BUTTON "STOP" mode Color "RED"


STOP
" O " (STOP) ......... By selecting the "STOP" mode, the genset is always shut down. The
shutdown procedure is as follows:
Stopping process
• the "STOP" mode is selected,
• the real power is reduced,
• the GCB is opened at 5 % of the rated generator real power,
• coasting is carried out according to the parameters in order to
cool the engine.

72 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
25 .................PUSH-BUTTON Operating mode "AUTOMATIC" Color "GREY"
"AUTOMATIC"
AUTOMATIC .........The engine is automatically started and stopped, and the power cir-
cuit breakers are automatically actuated. The two control inputs
"Automatic 1" and "Automatic 2" are used to specify various modes in
"AUTOMATIC" operating mode (also see description of control in-
puts). Emergency power and sprinkler operation is carried out regard-
less of the status of the discrete inputs "Automatic 1"
and "Automatic 2".

• Discrete input "Automatic 1" set


Active (real) power setpoint 1 is adjusted.

• Discrete input "Automatic 2" set


Active (real) power setpoint 2 or an external setpoint (0/4..20 mA or inter-
face) is adjusted (can be selected in configuration mode).

26 .................PUSH-BUTTON Operating mode "MANUAL" Color "GREY"


"MANUAL"
MANUAL ..............Using "MANUAL" operating mode, the push-buttons can be activated
to control the equipment manually. The automatic control of the
power circuit breakers and the genset are blocked. Important auto-
matic processes continue to remain in operation (e. g. engine moni-
toring and the mains watchdog function for operation in parallel with
the mains). Sprinkler and emergency power operation are not active.
Activating emergency or Sprinkler operation before changing into
operation mode MANUAL remains unchanged.

27 .................PUSH-BUTTON Operating mode "TEST" Color "GREY"


"TEST"
TEST .....................By actuating the "TEST" push-button, the engine is started, and engine
monitoring is activated. No power circuit breakers are operated. This
is carried out in the event of mains failure and when emergency
power is switched on.
Start of a "LOAD TEST" A load test is enabled via the actuation of the " I " (GCB ON)
push-button. In addition to the functions of "TEST" mode, the GCB is
synchronized or the MCB is opened according to the CB logic and
the GCB is then switched to the black busbar. The power can be
changed by actuating the setpoint value push-buttons.
End of a "LOAD TEST" The "LOAD TEST" can be terminated by actuating the " O " (GCB
OFF) or " I " (MCB ON) push-button (depending on power circuit
breaker logic). In "STOP" or "AUTOMATIC" mode without request
signal, the genset is stopped with a reduction of power.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 73
3.4 Display

28 .......................... DISPLAY LC display


"LC display"
The LC display shows messages and values, depending on the respective mode applied.
In configuration mode, the individual parameters are displayed and changed. In Auto-
matic mode the operating variables (e. g. voltages and currents) can be called up.

Top line • In the "V/kV" field, the generator voltage is displayed depending on the LED's UL1, UL2
and UL3.
• In the fields "A(L1)", "A(L2)" and "A(L3)" the generator line currents are displayed sepa-
rately for each phase.

Bottom line The following screens appear in the "operating and alarm messages" field:

Basic screen
• Display of the generator power factor ϕ and the generator actual real power
or
• the action of the genset that is currently being carried out (synchronization, starting,
etc.)

Subordinate screens: Depending on the item's equipment,


• the engine speed,
• the mains voltage,
• [PCM1x] the mains current/the mains power, mains power factor ϕ,
• the analog input variables,
• the generator's active energy,
• the generator re-active power (is determined via the current of phase L1; also if "three-
phase" power measurement was selected),
• the operating hours,
• the time remaining until the next maintenance call,
• the engine start counter,
• the battery voltage (supply voltage),
• [PCM1x] the number of subscribers participating in load sharing,
• the maximum generator current (slave pointer),
• the four alarm messages which occurred first and
• [PCM1x] the time/the date
are displayed.

These display screens are displayed in succession by pressing the "STATUS / ALARM"
push-button. When the last display screen has been reached, the basic screen is dis-
played. If alarms have occurred, their message texts are displayed in the sequence of their
occurrence in the display screens before the basic screen. If item functions are active (e. g.
synchronization of the GCB), the basic screen is superimposed with the corresponding
message (e. g. "synchronization"). Following the termination of the item function, the basic
screen is displayed again.

74 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
4 Configuration screens (input of the parameters)
Configuration can be performed using a PC and the PC program FL-SOFT3 via the serial interface or via the front panel push-buttons
and the front panel LC display. Additionally it is possible to configure the unit via CAN bus. The following Baudrate are therefore
usable:

• Configuration via direct configuration plug = 9,600 Baud (8 Bit, no parity, 1 Stoppbit) and
• CAN bus (CiA) = 125, 250 or 500 kBaud configurable via the serial interface.

CAUTION

For configuration of this control (firmware software version starting with 4.1xxx) a PC software with the
following version number:

FL-SOFT3 ab 3.0.015
Because of functional enhancements within the controls of the PCx Series it is necessary (beginning with firmware version 4.1.xxx of
the PCx) to use a newer version of the configuration software FL-SOFT3. This version at least has to be 3.0.015 or higher.

Once you successfully finished the installation older project files still can be used.

WARNING

Please note that configuration only should be performed in a standstill of the system.

NOTE

Please take into account the list of parameters at the end of this manual.

The configuration screens, if they are in input mode (simultaneously pressing of "U SELECT"
and "PARAMETER"), can be scrolled via "STATUS / ALARM". If the "STATUS / ALARM"
push-button is pressed for a longer period of time, the scroll function will be activated, and
the screens will be browsed rapidly. Simultaneously pressing the "STATUS / ALARM" and
"PARAMETER" push-buttons allows you to scroll through the last four configuration screens.
(exception: change from the first to the last parameter as well as backwards in the service
screen is not possible). If no entry, modification or any other action is carried out for
60 seconds, the item automatically returns to the automatic mode.

NOTE

There are two different types of hardware, which are described in this manual: A 100 Vac version [1]
and a 400 Vac version [4]. The configuration screens and parameters differ in both versions, and the
setting limits also differ. The two types are identified by the preceding voltage values ([1] ... or [4] ...).

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 75
4.1 Load basic values

WARNING!

By loading the standard values all parameters are overwritten. Thereby the customer settings get lost and
shall be saved necessarily by FL-SOFT3.

Procedure:

• Enter code level 2.


• Select "operation mode STOP"
• Press the 3 buttons "U SELECT", "PARAMETER" and "STATUS / ALARM" for at least
5 seconds at the same time.
• Message "Default Values loading 000%" is displayed.
• Wait until value reaches 100%.
• Standard values are successfully loaded.

NOTE

If the device is equipped with a language manager, the first language is selected by loading the standard
values. Therefore the language has to be changed by hand.

4.2 Version number

Software version Software version


Vx.xxxx
Software version display.

4.3 Password protection

The item is equipped with a three-level code and configuration hierarchy, which enables it
to visualize various configuration screens for different users. A distinction is made between:

Code level 0 User: Third party


(CS0) This code level enables no access whatsoever to the parameters. The configuration is
blocked.

Code level 1 User: Customer


(CS1) This code level entitles the user to change a few selected parameters (e. g. rated real
power, etc.). Changing a password is not possible in this case.

Code level 2 User: Commissioner


(CS2) With code level 2 the user acquires all access rights, and therefore has direct access to all
parameters (displaying and changing). In addition, the user may also set the password for
levels 1 and 2 in this level.

NOTE

Once the code level is set, this is not changed, even if the configuration mode is accessed steady. When
an incorrect code number is entered, the code level is set to CS0 and the item is therefore locked for
external users (set of password on page 86). Two hours after the final operation of the item, code level
CS0 is automatically set. By inputting the corresponding code number, the corresponding level is
accessed again.

76 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
Enter code Enter code number 0..9999
0000
On accessing the configuration mode, a code number, which identifies the various users,
is first requested. The displayed number XXXX is a random number (RN) and is confirmed
with the "Select" push-button. If the random number has been confirmed with "Select" with-
out being changed, the item's code level remains as it was. Two four-digit code numbers
(0000..9999) exist for changing the code level and setting up new code words for the
users. No assignment is required for the "third party" user level, as the user does not usually
receive access to the configuration level (protected via the code).

4.4 Direct configuration

NOTE

To carry out direct configuration, you require a direct configuration cable, the PC program (supplied with
the cable) and the corresponding configuration files. Please consult the online help installed when the
program is installed for a description of the PC program and its setup.

Remote configuration For remote configuration, the password of level 2 must be entered via the parameter
"password level 2", otherwise, the values can only be read but not written. Inputting via the
bus has no influence on the displayed screen; this means, if the item itself is in code
level 0, it also behaves as described in the previous section; only configuration via the bus
is permissible. The isolation for the configuration via the bus is valid for 10 minutes from the
point in time at which configuration or readout has not occurred; afterwards, the password
must be configured again. The password must also be entered in advance to load the lan-
guage. If the code for level 2 is entered on the item itself, the configuration is automatically
isolated via the bus.

WARNING !

If the following parameter "direct para." is set to "YES", communication via the interface with terminals
X1..X5 is locked. If communication is to be re-established via interface X1..X5 after configurating the item
(e. g. CAN bus connection via a Gateway), the following parameter must be set to "NO"!
Direct configuration is switched off for safety reasons once the firing speed has been reached. That means
that further setting of the item parameters is only possible using the display and push-buttons, directly or via
the CAN bus interface. The screen is switched from YES to NO (this is done using the software). The de-
activation of the direct configuration is for safety reasons, so that in the case of multiple systems starting
simultaneously (e. g. emergency power situation) a simultaneous switching of the generator switches to the
black busbar is prevented.

Direct para. Direct configuration YES/NO


YES
YES .......... A configuration via the lateral plug is possible, and any CAN bus connection
that may be available via terminals X1..X5 is de-activated. The following con-
ditions must be met in order to carry out configuration via the lateral plug:
- A connection must be established via the direct configuration cable between
the item and the PC,
- the baud rate of the FL-Soft3 program must be set to 9,600 Baud and
- the corresponding configuration file must be used (file name: "xxxx-xxxx-yyy-
zz.asm", initiated by xxxx-xxxx-yyy-zz.cfg).
NO .......... Configuration via the lateral plug cannot be carried out, and any available
CAN bus connection via the terminals X1..X5 is activated.

4.5 Generator number

Generator number Generator/item number 1..8


0
If several generators are available and these are coupled via a can bus, a different num-
ber must be assigned to each generator for differentiation purposes. The generator num-
ber 1 should be assigned even in the case of individual items. The generator number en-
tered here corresponds to the genset number in the program.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 77
4.6 Load language

Language Language first/second


first
First .......... All texts are displayed in the base language.
Second ..... All texts are displayed in the second language that is available in the item.

4.7 Service display

Service display Service display ON/OFF


ON
ON .......... The following three screens are displayed (the voltages and frequencies of the
mains, the busbar and the mains are displayed). In addition, the controller
outputs and the switching statuses of the power circuit breakers during syn-
chronization are displayed. According to the used hardware (with or without
voltage transducer) different screens are displayed.
OFF.......... The service screens are not displayed.

B 00.0kV 00.00Hz Double voltage and double frequency display


G 00.0kV 00.00Hz
The generator and busbar voltage and frequency are displayed. The phase angle be-
tween the generator and busbar is displayed by the synchroscope (LED strip):
B.............. Busbar voltage and frequency.
G ............. Generator voltage and frequency.

M 00,0kV 00,00Hz Double voltage and double frequency display


B 00,0kV 00,00Hz
The mains and busbar voltage and frequency are displayed. The phase angle between
the mains and busbar is displayed by the synchroscope (LED strip):
M............. Mains voltage and frequency.
B.............. Busbar voltage and frequency.

Rel.: MCB Status of power circuit breakers and relays


F/U GCB
The display shows the actual relay state of the three-position controller output respectively
the direction of the analog controller and the signals of the power circuit breakers during
synchronization:
f............... + Frequency controller RAISE Terminal 8/9
- Frequency controller LOWER Terminal 8/10
U ............. + Voltage controller RAISE Terminal 11/12
- Voltage controller LOWER Terminal 11/13
MCB......... ON Connect pulse of the MCB Terminal 16/17
OFF Disconnect pulse of the MCB Terminal 39/40
GCB......... ON Connect pulse of the GCB Terminal 14/15
OFF Disconnect pulse of the Terminal 41/42

78 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
4.8 Event logging [PCM1x..-H-..]

NOTE

The viewing and acknowledgement of alarms depends on access authorization:


Viewing of alarms................ Access authorization CL1 0, CS1 1 and CL1 2
Acknowledgment of alarms.... Access authorization CL1 2
1 ....................... CL = Code level (see chapter 2.17.1 "Alarm classes" on page 62

If an event that is stored in the item occurs in the item, there is an entry into the event log.
The following functions are supported:

• Event
• Date of occurrence
• Time of occurrence

Stored in the alarm log are the last 50 alarms, beginning with the most current window
(FIFO). By pressing the "RESET" push-button, the window that is displayed can be canceled.
The alarms are displayed on two lines. The top line indicates the date and time of the
alarm that has occurred; the lower line shows the type of alarm.

check event list Event logging YES/NO


YES
YES .......... The events can be viewed and acknowledged.
NO .......... The events cannot be viewed and acknowledged.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 79
4.8.1 Internal events and discrete inputs

YY-MM-DD ss:mm 50 × alarm log


xxxxxxxxxxxxxxxx
YY-MM-DD ss:mm .... Display of day and time of the event.
xxxxxxxxxxxxx..... See bottom table.

xxxxxxxxxxxxxxxx
German English
Internal alarm
Engine overspeed (Pickup) Überdrehzahl Over speed
Generator overfrequency Überfrequenz Over frequency
Generator underfrequency Unterfrequenz Low frequency
Generator overvoltage Gen.-Überspg. Gen.overvolt.
Generator undervoltage Gen.-Unterspg. Gen.undervolt.
Generator overcurrent, level 1 Gen.-Überstrom 1 Gen.overcurr. 1
Generator overcurrent, level 2 Gen.-Überstrom 2 Gen.overcurr. 2
Reverse/reduced load Rück/Minderleist Revers/min.power
Overload Gen.-Überlast Gen.overload
Load imbalance Schieflast Asymmetric load
Mains overvoltage Netz-Überspg. Mains-overvolt.
Mains undervoltage Netz-Unterspg. Mains-undervolt.
Mains overfrequency Netz-Überfreq. Mains-overfreq.
Mains underfrequency Netz-Unterfreq. Mains-underfreq.
Mains vector jump Phasensprung Phase shift
Battery undervoltage Batt.-Unterspg. Batt.undervolt.
GCB synchronization time monitoring Synch.Zeit GLS GCB syn.failure
MCB synchronization time monitoring Synch.Zeit NLS MCB syn.failure
Switching to black busbar time monitoring Stör. df/dt-max. Failure df/dVmax
Fault P-control: GCB will be opened after time R-Ramope:GLS auf P-ramp:open GCB
boost/settle
Mechanical GCB malfunction on closing Störung GLS ZU GCB close fail.
Mechanical MCB malfunction on closing Störung NLS ZU MCB close fail.
Mechanical GCB malfunction on opening Störung GLS AUF GCB open fail.
Mechanical MCB malfunction on opening Störung NLS AUF MCB open fail.
Faulty reference power zero control with inter- Bezugsleist. <>0 Import power<>0
change synchronization on GCB
Maintenance call Wartung Service
Interface monitoring X1..X5 Fehl.Schnit.X1X5 Interf.err.X1X5
Plausibility control Pickup/generator frequency Freq.Gen/Pickup Pickup/Gen.freq.
Plausibility control power (optionally) L.-Plausibilität P.-Plausibility
Shutoff malfunction Abstellstörung Stop failure
Start failure Fehlstart Start failure
Unintentional stop ungewollter Stop Not wanted stop
Discrete Inputs
Discrete input 1
Discrete input 2
Discrete input 3
Discrete input 4
Discrete input 5
Discrete input 6
Discrete input 7
Discrete input 8
freely configurable freely configurable
Discrete input 9
Discrete input [A]
Discrete input [B]
Discrete input [C]
Discrete input [D]
Discrete input [E]
Discrete input [F]
Discrete input [G]

80 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
xxxxxxxxxxxxxxxx
German English
EM1-D.1 – Discrete inputs
Discrete input [1]
Discrete input [2]
Discrete input [3]
Discrete input [4]
freely configurable freely configurable
Discrete input [5]
Discrete input [6]
Discrete input [7]
Discrete input [8]
EM1-D.2 – Discrete inputs
Discrete input [1]
Discrete input [2]
Discrete input [3]
Discrete input [4]
freely configurable freely configurable
Discrete input [5]
Discrete input [6]
Discrete input [7]
Discrete input [8]
Other
Switch into "Load-TEST" mode BAW Lastprobe Load-test mode
Switch into "STOP" mode BAW Stop Stop mode
Switch into "TEST" mode BAW Probe Test mode
Switch into "MANUAL" mode BAW Hand Manual mode
Switch into "AUTOMATIC" mode BAW Automatik Automatic mode
"MCB OFF" button pressed (in MANUAL MODE) Taste NLS AUS Button MCB OFF
"GCB OFF" button pressed (in MANUAL MODE) Taste GLS AUS Button GCB OFF
"GCB ON" button pressed (in MANUAL MODE) Taste GLS EIN Button GCB ON
"MCB ON" button pressed (in MANUAL MODE) Taste NLS EIN Button MCB ON
"START" button pressed (in MANUAL MODE) Taste Hand START Button START
"STOP" button pressed (in MANUAL MODE) Taste Hand STOP Button STOP
Remote start Fernstart Remote start
Remote stop Fernstop Remote stop
Remote acknowledgment via interface Fernquittierung Remote acknowl.
Remote acknowledgment via Terminal 6 Quittierung Kl.6 Acknowledge-ter6
Acknowledgment via "RESET" button Quittierg. Taste Ackn.button QUIT
Mains failure Netzausfall Mains faildown
Return of the mains Netzwiederkehr Mains o.k.
Emergency power start Notstrom Anfang Emerg. run start
Emergency power end Notstrom Ende Emerg. run stop
Engine successfully started (engine enabled, Aggr. gestartet Start of engine
firing speed exceeded)
Engine stopped (engine not enabled, firing Aggregatestop Stop of engine
speed was undershot)

4.8.2 Analog inputs

The name of the analog inputs is moved to the right. The alarm type is written in the space
that has become open.

WIRE_ ..... Wire break


ALARM_ ... Limit value 1
STOP_ ..... Limit value 2

JJ-MM-TT SS:MM Example


STOP Analog input
Limit value 2 (STOP) of the analog input 1 was exceeded. The text of the analog alarm
input will be moved to the right for the numbers of letters of the alarm class (here alarm
class "STOP"). In this case the measured value disappears. Please note this text displacing
already during the configuration of the analog input!

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 81
4.9 Basic settings configuration

Configure Configuration of the basic settings YES/NO


measuring YES
Various groups of parameters are placed together in blocks to allow you to navigate
through the large number of configuration screens more rapidly. Selecting "YES" or "NO"
has no effect on whether or not control or monitoring etc., is carried out. The input merely
has the following effects:
YES .......... The configuration screens in the next block are displayed and can either be
viewed ("STATUS / ALARM" push-button) or modifications can be made to the
parameters ("PARAMETER", "U SELECT" or "STATUS / ALARM" push-buttons). A
decision is not made on whether the parameters are processed or not.
NO .......... The parameters in the next block are not displayed, cannot be modified and
are therefore skipped.

WARNING !

Incorrect entries may lead to wrong measured results and cause the destruction of the generator!

4.9.1 Generator and mains environment

Generator freq. Generator setpoint frequency 40.0..70.0 Hz


f set 00.0Hz
The generator setpoint frequency is entered in this screen. This is required for the frequency
controller in isolated and no-load operation. In most cases, the values entered into this
screen will be 50 Hz or 60 Hz. Of course different values are possible.

Rated system Rated system frequency 50.0..60.0 Hz


frequency 00.0Hz
The rated frequency of the system is transferred to the genset. This parameter depends on
the three-phase system in the relevant country.

WARNING !

If the value of the following parameter is changed, the values of the following masks have to be proved:
• Generator nominal voltage (see on page 82),
• Voltage controller insensitivity (see on page 92),
• Synchronizing dUmax (see on page 113),
• Black start GCB dUmax (see on page 115),
• Threshold generator overvoltage (see on page 126), as well as
• Threshold generator undervoltage (see on page 126).

Gen.volt.transf. Secondary gen. voltage transformer [1] 50..125 V; [4] 50..480 V


secondary 000V
The secondary voltage is set here in V. This entry serves to indicate the secondary voltages
in the display.

Gen.volt.transf. Primary gen. voltage transformer 0.050..65.000 kV


primary 00.000kV
The primary voltage is set her in kV. The entry is used to output the primary voltages on the
display. In the case of measured voltages of 100 V without a measurement transducer,
0.1 kV must be set here; for 400 V = 0.4 kV.

Bus.volt.transf. Secondary busbar voltage transformer [1] 50..125 V; [4] 50..480 V


secondary 000V
The secondary voltage is set here in V. This entry serves to indicate the secondary voltages
in the display.

82 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
Bus.volt.transf. Primary busbar voltage transformer 0.050..65.000 kV
primary 00.000kV
The primary voltage is set here in kV. The entry is used to output the primary voltages on
the display. In the case of measured voltages of 100 V without a measurement transducer,
0.1 kV must be set here; for 400 V = 0.4 kV.

WARNING !

If the value of the following parameter is changed, the values of the following masks have to be proved:
• Threshold mains overvoltage (chapter 4.13.11 at page 129) as well as
• Threshold mains undervoltage (chapter 4.13.11 at page 129).

mains volt.trans Secondary mains voltage transformer [1] 50..125 V; [4] 50..480 V
secondary 000V
The secondary voltage is set here in V. This entry serves to indicate the secondary voltages
in the display.

mains volt.trans Primary mains voltage transformer 0.050..65.000 kV


primary 00.000kV
The primary voltage is set here in kV. The entry is used to output the primary voltages on
the display. In the case of measured voltages of 100 V without a measurement transducer,
0.1 kV must be set here; for 400 V = 0.4 kV.

Gen.voltage Generator setpoint voltage [1] 50..125 V; [4] 50..530 V


U set 000V
This value of the voltage specifies the setpoint of the generator voltage for no-load and iso-
lated operation.

Rated voltage in Rated voltage in system [1] 50..125 V; [4] 50..480 V


system 000V The rated voltage (UL-L) is preset with this value.
The proportional entries of the following parameters refer to this value:
- Generator voltage monitoring
- Mains voltage monitoring
- Insensitivity voltage controller
- Synchronization dU max
- Black start GCB dU max

NOTE

Terminal 0 has to be isolated for the setting 'Ph-Ph/Ph-Ph' (voltage measuring Ph-Ph, voltage monitoring
Ph-Ph), since a contact voltage in inadmissible range may occur at terminal 0.

Volt.meas./mon. Voltage measuring/voltage monitoring 4/4; 4/3; 3/3


-----------------------------
Ph-neut/Ph-neut (4/4) - The electrical system(generator, busbar and main) consists of the
three outer conductors and a neutral conductor. Thus, the N lug (terminator 0)
has to be connected. The outer conductor voltages and the phase-neutral volt-
ages are displayed in the display. The voltage monitoring entries are referred
to the phase-neutral voltages (VL-N).
Ph-neut/Ph-Ph (4/3) - The electrical system(generator, busbar and main) consists of the
three outer conductors and a neutral conductor. Thus, the N lug (terminator 0)
has to be connected. The outer conductor voltages and the phase-neutral volt-
ages are displayed in the display. The voltage monitoring entries are referred
to the phase-phase voltages (VL-L).
Ph-Ph/Ph-Ph (3-/3) - The electrical system(generator, busbar and main) consists only of the
three outer conductors (without neutral conductor). Thus, the N lug (termina-
tor 0) can not be connected. Only the outer conductor voltages are displayed
in the display. The voltage monitoring entries are referred to the phase-phase
voltages (VL-L).

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 83
Voltage systems Voltage system Threewire/Fourwire
Threewire
Threewire . The star voltages of the generator and the mains will not be shown.
Fourwire ... The star voltages of the generator and the mains will be shown.

4.9.2 Transformer and measuring variables

Current transf. Generator current transformer 10..7,000/x A


generator 0000/x
The input of the current conversion ratio is necessary in order to display and control the ac-
tual values. The ratio must be selected in such a manner that, at maximum power, at least
60 % of the converter's nominal current flows. A lower percentage may lead to malfunc-
tions. Additional inaccuracies in the control and monitoring functions also occur.

{X} / 1 A... Secondary current = 1 A at primary rated current = {X} A;


{X} / 5 A... Secondary rated current = 5 A at primary rated current = {X} A;
{X}............ e.g. from the main series 10, 15, 20, 30, 50 or 75 A and the decimal frac-
tions and multiples of these or the corresponding secondary series with 25,
40 or 60 A.

Power measuring Generator power measurement singlephase/threephase


gen.
With regard to the measurement of generator power, single-phase or three-phase meas-
urement may be selected. If "single-phase power measurement" is set, the current and the
voltage in phase L1 are used for power measurement. If "three-phase power measurement"
is set, all three currents and the relevant voltages are used for power measurement.
• single phase power measurement: P = 3 ⋅ UL12 ⋅ IL1 ⋅ cos ϕ .
• three phase power measurement:
P = UL1N × IL1 × cosϕ + UL2N × IL2 × cosϕ + UL3N × IL3 × cosϕ.

Rated power Generator rated power 5..9,999 kW


generator 0000kW
On inputting the value into this screen, the generator rated power is pre-specified. The ex-
act input of the generator rated power is absolutely vital, as very many measurement, con-
trol and monitoring functions refer to this value.

Rated current Generator rated current 10...7,000 A


generator 0000A
On inputting the value into this screen, the generator rated current is pre-specified. The ex-
act input of the generator rated current is absolutely vital, as very many measurement func-
tions refer to this value.

84 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
4.9.3 Mains Current/Mains Power Measurement

a.) Mains power actual value measurement via analog input (only PCM1-..H-..)
Measurement of the mains power actual value measurement via an analog input T{x} [x = 1-7] is possible if at least one of the ana-
log inputs T{x} [x = 1-7] is a 0/4-20 input. Selection of the analog input occurs via the following parameters.

Analog in Pmains Analog input P-mains: Selection OFF/T{x}


OFF
OFF ........................... The mains interchange (import/export) real power actual value is
only PCM1-..H-.. calculated out of the measured mains current and the measured
mains voltage. The analog inputs can either be used as real
power setpoint value or as free configurable alarm inputs. The
following masks of this function are not displayed.
T{x}............................ The mains interchange (import/export) real power actual value
can be fed to the control by a measuring transducer and can be
measured via the configured free scalable 0/4-20 mA input T{x}
({x} = 1-7) (other types of analog inputs cannot be used).The fol-
lowing masks of this function are displayed.

Note
Please note that the selected analog input T{x}
• has to be configured to OFF in chapter "Analog inputs" and that this analog input
• must not be configured as generator real power setpoint value in chapter
"Controller".
• T{x}: Dependent on the control model these analog inputs are included and possibly
built as 0/4-20 mA type. For this function only 0/4-20 mA inputs can be used
(only these inputs are displayed for selection at this parameter).
• A change of the function of the analog inputs is updated in the visualization of
FL-CABLE-RS232 once the PC program has been restarted after the dynamic
configuration has been started.

Priority of the functions of the analog inputs


The following priority is valid if more than one function has been assigned to a analog in-
put:
• Highest priority: Mains interchange (import/export) real power actual value
• Middle priority: Generator real power setpoint value
• Lowest priority: Measuring input as common analog value

Analog in Pmains Analog input P mains: Range 0-20 mA/4-20 mA


0-00mA
The measuring range 0-20 mA or 4-20 mA is selected with this parameter. If the range
only PCM1-..H-.. was selected 4-20 mA and the current is lower than 2 mA, a wire break alarm is issued.

Note
It is possible to adjust the display range of the mains interchange (import/export) real
power actual value. Thereto the wanted value must be entered and saved using the pa-
rameter "name and unit" of the selected analog input (see chapter "Analog inputs").

NOTE

In case of an import/export real power control you have to take care that the setpoint value is set in the
middle of the measuring range. By this setting the controller dynamic can be used to full capacity.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 85
Analog in Pmains Mains real power 0/4 mA[1] –9,990..0..+9,990 kW; [4] –6,900..0..+6,90
0% 0000kW
To the scaleable analog input a numerical value is assigned which corresponds to the
only PCM1-..H-.. smallest input value ! Definition of the lower value with minimum analog input value (0 %
corresponds to, e. g. -500 kW; 0 or 4 mA).

Analog in Pmains Mains real power 20 mA[1] –9,990..0..+9,990 kW; [4] –6,900..0..+6,900
100% 0000kW
To the scaleable analog input a numerical value is assigned which corresponds to the
only PCM1-..H-.. greatest input value ! Definition of the higher value with maximum analog input value
(100 % corresponds to e. g. 500 kW; 20 mA).

b.) Mains current measurement via mains CT (only PCMx)

Current transf. Mains current transformer (terminals 27/28) 5..7,000/x A


mains 0000/1
The input of the current conversion ratio is necessary in order to display and control the ac-
[PCM1x] tual values. The ratio must be selected in such a manner that, at maximum power, at least
60 % of the converter's nominal current flow. A lower percentage may lead to malfunc-
tions. Additional inaccuracies in the control and monitoring functions also occur.

{X} / 1 A....................Secondary rated current = 1 A at primary rated current = {X} A;


{X} / 5 A....................Secondary rated current = 5 A at primary rated current = {X} A;
{X} .............................e. g. from the main series 10, 15, 20, 30, 50 or 75 A and the
decimal fractions and multiples of these or the corresponding
secondary series with 12.5, 25, 40 or 60 A.

PCN4 modus PCN4 modus ON/OFF


ON
ON ........................... The PCM is operating in PCN4mode. The control PCM expects
only PCM1-G-..-E-.. CAN bus messages from the PCN4 and reacts accordingly. Ad-
ditionally the control PCM transmits messages to the PCN4.
OFF ........................... The control PCM operates without PCN4 functionality as a nor-
mal genset control.

Rated power in Rated power in the system 0..16,000 kW


system
The PCN4 transmits the current mains interchange real power in percent related to the
only PCM1-G-..-E-.. rated power in the system to the controller PCM.

Note
This configuration is valid only if parameter " PCN4 modus" is configured to ON.

ATTENTION
Since the PCN4is only able to transmit a percentage value related to the rated value it is
absolutely necessary to configure the rated power in all units (PCN4 and PCM; in the
PCM) to the same value.

86 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
4.9.4 Changing passwords

NOTE

Once the code level is set, this is not changed, even if the configuration mode is accessed steady. If an
incorrect code number is input, the code level is set to CL0, and the item is thereby blocked for third
parties. If the supply voltage is present, uninterrupted, at the item for 2 hours, code level 0 is automatically
set.

Define level 1 Code level 1 (Customer) 0..9999


code 0000
This screen first appears in code level 2. Following the input of digits in this screen, the
code level for level 1 (Customer) is set. After inputting his code, the customer possesses
only the access rights with which he has been assigned.
The default setting for this code level (CL) is CS1 = 0 0 0 1

Define level 2 Code level 2 (Commissioner) 0..9999


code 0000
This screen first appears in code level 2. Following the input of digits in this screen, the
code level for level 2 (mechanic) is set. After inputting his code, the mechanic possesses
the access rights with which he has been assigned.
The default setting for this code level (CL) is CS2 = 0 0 0 2

4.10 Controller configuration

WARNING !

An incorrect input can lead to uncontrolled controller actions and destroy the generator!

Configure Configuration of the controller YES/NO


controller YES
Various groups of parameters are placed together in blocks to allow you to navigate
through the large number of configuration screens more rapidly. Selecting "YES" or "NO"
as no effect on whether or not control or monitoring etc., is carried out:
YES .......... The configuration screens in the next block are displayed and can either be
viewed ("STATUS / ALARM" push-button) or modifications can be made to the
parameters ("PARAMETER", "U SELECT" or "STATUS /ALARM"). A decision is
not made on whether the parameters are processed or not.
NO .......... The parameters in the next block are not displayed, cannot be modified and
are therefore skipped.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 87
4.10.1 Constant and interchange (import/export) power controller [PCM1x]

These screens appear only if the real power controller (see “Real power controller
[PCM1x]" on page 96) is set to "ON".

NOTE

The fixed-value power control does not take into account the mains interchange point, i. e., the mains will
be supplied in the event of excessive power (power export); in the event of a power deficit, differential
power coverage will be provided by the mains (power import).

Power controller Setpoint 1 real power controller C/I/E 0..6,900 kW


Pset1 I0000kW
Setpoint 1 is active when Automatic 1 (voltage applied to terminal 3) is enabled. The
mains interchange power is then regulated to the set value.
The real power is regulated to the input value.
F .............. The letter F stands for fixed setpoint control (= constant power). I. e., the gen-
erator always supplies a constant real power value. The genset is always
started on activation of fixed setpoint power.
The mains interchange power is regulated to the set value.
I ............... The letter I stands for import power (power supplied by the mains). I. e., the
power set here is always supplied by the mains, whereby the minimum and
maximum generator real power are adhered to.
E .............. The letter E stands for export power (power supplied to the mains). I. e.,
power set here is always supplied to the mains, whereby the minimum and
maximum generator real power are adhered to.

Power controller Setpoint 2 real power controller C/I/E 0..6,900 kW


Pset2 L0000kW
Setpoint 2 is active if Automatic 2 (voltage applied to terminal 5) is enabled and no ex-
ternal setpoint parameter (0/4..20 mA or interface) has been selected. The mains inter-
change power is then regulated to the set value.
The real power is regulated to the input value.
F .............. The letter F stands for fixed setpoint control (= constant power). I. e., the gen-
erator always supplies a constant real power value. The genset is always
started on activation of fixed setpoint power.
The mains interchange power is regulated to the set value.
I ............... The letter I stands for import power (power supplied by the mains). I. e., the
power set here is always supplied by the mains, whereby the minimum and
maximum generator real power are adhered to.
E .............. The letter E stands for export power (power supplied to the mains). I. e.,
power set here is always supplied to the mains, whereby the minimum and
maximum generator real power are adhered to.

NOTE

Engine starting depends on whether an automatic start/stop operation has been selected. If not, the
engine is always started (description starting on page 100).

88 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
4.10.2 Frequency controller

Alternatively, the following screens become visible.

a.) Three-position controller (standard)

Freq.controller Frequency controller ON/OFF


ON
ON .......... The generator frequency is controlled. The generator frequency is controlled in
various manners depending on the task (isolated operation / synchronization)
The subsequent screens of this option are displayed.
OFF .......... Control is not carried out, and the subsequent screens of this option are not
displayed.

f-contr. active Frequency controller starting frequency 0.0..70.0 Hz


at: 00.0Hz
The frequency controller is only activated when the generator frequency has exceeded the
value set here. The undesired adjustment of the setpoint value of a lower-level controller
can therefore be prevented when starting the engine.

Delay time for Delayed start of the frequency controller 0..999 s


f-contr. 000s
The starting frequency of the frequency controller must well exceed the time set here, be-
fore the frequency controller is active.

Freq.controller Frequency controller setpoint ramp 1..50 Hz/s


ramp 00Hz/s
The change in setpoint is supplied to the controller via a ramp. The slope of the ramp is
used to alter the rate at which the controller modifies the setpoint value. The more rapidly
the change in the setpoint is to be carried out, the greater the value input here must be.

NOTE

The parameters for the speed/frequency controller influence the generator real power controller.

F-/P contr.type f controller: type THREESTEP/ANALOG/PWM


-----------------------------
THREESTEP The signal to control the speed/frequency/real power is output via the relay
only Option A manager to any configured relay. You can use the following functions of the
relay manager:
• function 114 = n+ / f+ / P+
• function 115 = n- / f- / P-
Please note to wire an external RC protection.
ANALOG .. A control is done via the analog controller outputs to terminals 8/9/10. Se-
lection of the type of the signal (mA or V) is carried out by the parameter and
an external jumper that has to be added
PWM........ A control of speed/frequency/real power is carried out via a PWM signal.
The settings in the parameter "Level PWM" are to be used. An additional
jumper is to be added

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 89
b.) Three-position controller (Standard; Option A, Setting 'THREE POSITION')

Freq.controller Frequency controller insensitivity 0.02..1.00 Hz


deadband 0.00Hz
Isolated operation .... The generator setpoint frequency is controlled in such a manner
that, in its adjusted state, the actual value deviates from the genera-
tor setpoint frequency setting (setpoint from mask setting) by the set
sensitivity value at most.
Synchronization ....... The generator frequency is controlled in such a manner that, in its
adjusted state, the differential frequency reaches the set sensitivity
value at most. The mains or busbar frequency is used as the set-
point value.

Freq.controller Minimum frequency controller ON period 10..250 ms


time pulse >000ms
The minimum ON period of the relay should be selected in such a manner that the down-
stream adjustment facility responds reliably to the pulse which has been set according to
the set time. The smallest possible time must be set in order to ensure optimum control be-
havior.

Freq.controller Frequency controller gain 0.1..99.9


gain Kp 00.0
The gain factor Kp influences the operating time of the relays. By increasing the factor, the
operating time can be increased in the event of a certain control deviation.

Analog controller output (only Option A, Setting 'ANALOG' und 'PWM')

F/P contr.output f controller: output range see below


-----------------------------
If the parameter has been configured to "ANALOG" this parameter is to be taken into ac-
count. Here you configure the range of the analog output. To switch between current and
voltage analog controller output please add/do not add an external jumper between ter-
minals 8/9. Please note that this setting also affects the PWM signal. Following ranges
apply.

Type Setting in above Jumper Range


configuration between Lower Upper
screen term. 8/9 level level
Current +/-20mA (+/-10V) no +/-20mA -20 mA +20 mA
+/-10mA (+/-5V) +/-10mA -10 mA +20 mA
0-10mA (0-5V) 0-10mA 0 mA 10 mA
0-20mA (0-10V) 0-20mA 0 mA 20 mA
4-20mA 4-20mA 4 mA 20 mA
10-0mA (5-0V) 10-0mA 10 mA 0 mA
20-0mA (10-0V) 20-0mA 20 mA 0 mA
20-4mA 20-4mA 20 mA 4 mA
Voltage +/-20mA (+/-10V) yes +/-10V -10 Vdc +10 Vdc
+/-10mA (+/-5V) +/-5V -5 Vdc +5 Vdc
+/-3V +/-3V -3 Vdc +3 Vdc
+/-2.5V +/-2.5V -2.5Vdc +2.5 Vdc
+/-1V +/-1V -1 Vdc +1 Vdc
0-10mA (0-5V) 0-5V 0 Vdc 5 Vdc
0.5V-4.5V 0.5-4.5V 0.5 Vdc 4.5 Vdc
0-20mA (0-10V) 0-10V 0 Vdc 10 Vdc
10-0mA (5-0V) 5-0V 5 Vdc 0 Vdc
4.5V-0.5V 4.5-0.5V 4.5 Vdc 0.5 Vdc
20-0mA (10-0V) 10-0V 10 Vdc 0 Vdc

90 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
NOTE

The control logic of the PWM signal can be inverted by following steps:
- Select "F/P contr.type" = ANALOG.
- Select with "F/P contr.output" any of above inverted control outputs
(e.g. "10-0mA (5-0V)", "4.5V-0.5V", "20-0mA (10-0V)" or "20-4mA").
- Step one mask back; by pressing "Select" and "Cursor→" simultaneously).
- Select "F/P contr.type" = PWM.
Now the PWM signal is inverted.

Level PWM f controller: PWM level 3.0..10.0 V


-----------------------------
If PWM has been selected via the above the level of the PWM signal can be adjusted
here.

Stepper sign.frq f controller: minimum value 0..100%


(min.) 000%
Lower limit of the analog controller output.

Stepper sign.frq f controller: maximum value 0..100%


(max.) 000%
Upper limit of the analog controller output.

Freq.controller P gain of the frequency controller 1..240


gain Kpr 000
The proportional coefficient specifies the gain (see analog controller).

Freq.controller Reset time load frequency controller 0.0..60.0 s


reset Tn 00.0s
The reset time Tn identifies the I part of the PID controller (see analog controller).

Freq.controller Derivative-action time load frequency controller 0.00..6.00 s


derivat. Tv 0.00s
The derivative-action time TV identifies the D part of the PID controller
(see analog controller).

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 91
4.10.3 Voltage controller

Starting point Voltage controller initial state 0..100 %


voltage 000%
Analog controller output setting with controller switched off. This value is also used as a
only Option A. starting value, e. g. for a switch from a power factor ϕ- to a voltage controller.

Volt.controller Voltage controller ON/OFF


ON
ON .......... Generator voltage control is carried out. The subsequent screens of this option
are displayed.
OFF .......... Control is not carried out, and the subsequent screens of this option are not
displayed.

Start voltage Start voltage of voltage controller 12.0..100.0 %


U control. 000.0%
The voltage controller will be active, if the generator voltage has exceeded the set value.
This prevents an unintentional change of the setpoint of an under classified controller while
starting the engine.

Delayed. Start Delayed start of the voltage controller 0..999 s


U contr. 000s
The start voltage of the voltage controller has to exceed the here set value of time.

NOTE

The following parameters for the voltage controller influence the power factor cos ϕ controller.

V/Q contr.type V controller: type THREESTEP/ANALOG


-----------------------------
THREESTEP The signal to control the voltage/power factor is output via the relay manager
only Option A to any configured relay. You can use the following functions of the relay man-
ager:
• function 116 = U+/Q+
• function 117 = U-/Q-
Please note to wire an external RC protection..
ANALOG ..A control is done via the analog controller outputs to terminals 11/12/13.
Selection of the type of the signal (mA or V) is carried out by the parameter
and an external jumper that has to be added.

92 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
a.) Three-position controller (Standard, Option A: Setting 'THREE POSITION')

Volt.controller Voltage controller insensitivity 0.1..15.0 %


dead band 00.0%
This value refers to the parameter „Rated voltage in system“.
Isolated operation ..The voltage is controlled in such a manner that, in its adjusted state,
the actual value deviates from the setpoint voltage setting (setpoint
from mask setting) by the set sensitivity value at most.
Synchronization .....The generator voltage is controlled in such a manner that, in its ad-
justed state, the differential voltage reaches the set sensitivity value at
most. The mains or busbar voltage is used as the setpoint value.

Volt.controller Minimum voltage controller ON period 20..250 ms


time pulse >000ms
The minimum ON period of the relay should be selected in such a manner that the down-
stream adjustment facility responds reliably to the pulse which has been set according to
the set time. The smallest possible time must be set in order to ensure optimum control be-
havior.

Volt.controller Voltage controller gain factor 0.1..99.9


gain Kp 00.0
The gain factor Kp influences the operating time of the relays. By increasing the factor, the
operating time can be increased in the event of a certain control deviation.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 93
b.) Analog controller (Option A: Setting 'ANALOG')

V/Q contr.output V controller: range see below


-----------------------------
If the parameter “V/Q controller type” has been configured to "ANALOG" this
parameter is to be taken into account. Here you configure the range of the analog
output. To switch between current and voltage analog controller output please
add/do not add an external jumper between terminals 11/12. Following ranges
apply.

Type Setting in above Jumper Range


configuration between Lower Upper
screen term. 11/12 level level
Current +/-20mA (+/-10V) nein +/-20mA -20 mA +20 mA
+/-10mA (+/-5V) +/-10mA -10 mA +20 mA
0-10mA (0-5V) 0-10mA 0 mA 10 mA
0-20mA (0-10V) 0-20mA 0 mA 20 mA
4-20mA 4-20mA 4 mA 20 mA
10-0mA (5-0V) 10-0mA 10 mA 0 mA
20-0mA (10-0V) 20-0mA 20 mA 0 mA
20-4mA 20-4mA 20 mA 4 mA
Voltage +/-20mA (+/-10V) ja +/-10V -10 Vdc +10 Vdc
+/-10mA (+/-5V) +/-5V -5 Vdc +5 Vdc
+/-3V +/-3V -3 Vdc +3 Vdc
+/-2.5V +/-2.5V -2.5Vdc +2.5 Vdc
+/-1V +/-1V -1 Vdc +1 Vdc
0-10mA (0-5V) 0-5V 0 Vdc 5 Vdc
0.5V-4.5V 0.5-4.5V 0.5 Vdc 4.5 Vdc
0-20mA (0-10V) 0-10V 0 Vdc 10 Vdc
10-0mA (5-0V) 5-0V 5 Vdc 0 Vdc
4.5V-0.5V 4.5-0.5V 4.5 Vdc 0.5 Vdc
20-0mA (10-0V) 10-0V 10 Vdc 0 Vdc

Stepper sign.vol V controller: minimum value 0..100%


(min.) 000%
Lower limit of the analog controller output.

Stepper sign.vol V controller: maximum value 0..100%


(max.) 000%
Upper limit of the analog controller output.

Volt.controller P-gain voltage controller 1..240


gain Kpr 000
The proportional coefficient specifies the gain (see analog controller).

Volt.controller Voltage controller reset time 0.0..60.0 s


reset Tn 00.0s
The reset time Tn identifies the I part of the PID controller (see analog controller).

Volt.controller Derivative-action time voltage controller 0.00..6.00 s


derivat. Tv 0.00s
The derivative-action time TV identifies the D part of the PID controller (see analog control-
ler).

94 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
4.10.4 Power-factor controller [PCM1x]

Pow.fact.contr. Power-factor controller ON/OFF


ON
ON .......... In operation in parallel with the mains a load independent automatic control
of the power factor ϕ is carried out. In the case of excessively low currents
(secondary current less than 5 % IN) the power factor can only be measured
very inaccurately. In order to avoid power swings, the controller is automati-
cally locked in such cases. The subsequent screens of this option are dis-
played.
OFF .......... Control is not carried out, and the subsequent screens of this option are not
displayed.

Pow.fact.contr. Power-factor controller setpoint i0.70..1.00..c0.70


setpoint 0.00
The amount of the re-active power is controlled in such a manner that, when regulated, this
results in the pre-specified power factor ϕ. The designations "i" and "c" stand for inductive
(generator overexcited) and capacitive (generator underexcited) re-active power. This set-
point is active in operation in parallel with the mains.

NOTE

Please note the settings for the voltage controller in chapter "Voltage controller". The settings there for the
voltage controller also influence the cos ϕ controller.

a.) Three-position controller (Standard; Option A: Setting 'THREE POSITION')


Pow.fact.contr. Power factor controller insensitivity 0.5..25.0 %
dead band 00.0%
The item automatically calculates the amount of re-active power which belongs to the
power factor ϕsetpoint. In operation in parallel with the mains, the re-active power is con-
trolled in such a manner that, in its regulated state, the actual value deviates from the inter-
nally calculated setpoint (setpoint 1) percentage value of the insensitivity setting at most. In
this case, the percentage value refers to the generator rated power.

Pow.fact.contr. Power-factor controller gain 0.1..99.9


gain Kp 00,0
The gain factor Kp influences the operating time of the relays. By increasing the factor, the
operating time can be increased in the event of a certain control deviation.

b.) Analog controller (Option A: Setting 'ANALOG')

Pow.fact.contr. Power-factor controller P-gain 1..240


gain Kpr 000
The proportional coefficient specifies the gain (see analog controller).

Pow.fact.contr. Power-factor controller reset time 0.0..60.0 s


reset Tn 00.0s
The reset time Tn identifies the I part of the PID controller (see analog controller).

Pow.fact.contr. Power-factor controller derivative-action time 0.0..6.0 s


derivat. Tv 0.00s
The derivative-action time TV identifies the D part of the PID controller (see analog control-
ler).

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 95
4.10.5 Real power controller [PCM1x]

Power controller Real power controller ON/OFF


ON
ON .......... In operation in parallel with the mains, the real power is automatically ad-
justed to the pre-selected setpoint (page 88/96) when the real power control-
ler is switched on. The subsequent screens of this option are displayed.
OFF .......... Control is not carried out, and the subsequent screens of this option are not
displayed.

Power controller Real power controller setpoint ramp 0..100 %/s


ramp 000%/s
The setpoint change is supplied to the controller via a ramp in percent per second in ref-
erence to the generator rated power (see page 84). The slope of the ramp is used to alter
the rate at which the controller modifies the setpoint value. The more rapidly the change in
the setpoint is to be carried out, the greater this value has to be.

a.) Power limitation

Power limit Real power controller maximum power limitation 10..120 %


P max. 000%
If the maximum real generator load is to be limited, a percentage, based on the rated
generator power (see page 84), will be entered into this screen, in accordance with the
specified setting limits. The controller adjusts the genset in such a manner that this value is
not exceeded. The value "Pmax" only limits the setpoint of the real power controller, and is
without significance in isolated operation.

Power limit Real power controller minimum power limitation 0..50 %


P min. 00%
If the maximum real generator load is to be limited, a percentage, based on the rated
generator power (see page 84), will be entered into this screen, in accordance with the
specified setting limits. The controller adjusts the genset in such a manner that no negative
deviation from this value occurs. This parameter is ignored in the case of fixed-setpoint
control or in isolated operation.

96 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
b.) External setpoint value
The generator real power setpoint value via an analog input T{x} [x = 1-7] is possible at the time when minimum one of the analog
inputs T{x} [x = 1-7] is carried out as 0/4-20 mA input. The selection of the analog input is done using the following parameters.

Power setpoint P setpoint value: external setpoint value OFF/T{x}


external OFF
OFF .......... If this parameter is configured to "OFF" a generator real power setpoint value
can not be fed via the 0/4-20 mA input to the control. The analog inputs can
be used either as mains interchange (import/export) real power actual value
or as free configurable alarm inputs. In case of selection of terminal 5 the in-
ternal setpoint value 2 "Pset2" is used as setpoint value. The subsequent screens
of this function are not displayed.
T{x}........... The generator real power setpoint value can be fed to the control via an ex-
ternal signal using the 0/4-20 mA inputs (T{x}, {x) = 1-7; other types of ana-
log inputs cannot be used). This setpoint value is used when automatic 2 (ter-
minal 5) is set. The subsequent screens of this function are displayed.

Note
Please note that the selected analog input T{x}
• has to be configured to OFF in chapter "Analog inputs" and
• must not be configured as mains interchange real power actual value in chapter
"Measuring".
• T{x}: Dependent on the configuration of the control these analog inputs are included
and possibly a 0/4-20 mA type. For this function only 0/4-20 mA analog inputs can be
used.
• A change of the function of the analog inputs is updated in the visualization of FL-
CABLE-RS232 once the PC program has been restarted after the dynamic configuration
has been started.

Priority of the functions of the analog inputs


The following priority is valid if more than one function has been assigned to a analog in-
put:
• Highest priority: Mains interchange real power actual value measurement
• Middle priority: Real power setpoint value
• Lowest priority: Measuring input as common analog value

Analog input Real power setpoint value specification analog input 0-20 / 4-20 mA
0-00mA
The analog input of the real power controller (terminals 93, 94 and 95 - see wiring dia-
gram; in exceptional cases, the setpoint is applied to terminals 91 and 92) can be
switched here between 0-20 mA and 4-20 mA depending on the setpoint source.
0-20 mA ... Minimum value of the setpoint at 0 mA; maximum value at 20 mA.
4-20 mA ... Minimum value of the setpoint at 4 mA; maximum value at 20 mA.

CAUTION!

The interchange power setpoint (import/export power)can also be scaled. When controlling interchange
power, it is vital to ensure that no F power is entered simultaneously with I or E power when scaling the
external analog input.
External setpoint 0/4 mA F I E I E
External setpoint 20 mA F I E E I

Ext.setpoint Scaling the minimum value (fixed power) C/I/E 0..9,999 kW


0% F0000kW
The minimum value of the real power is defined here (e. g. 0 kW).

Ext.setpoint Scaling the maximum value (fixed power) C/I/E 0..9,999 kW


100% F0000kW
The maximum value of the real power is defined here (e. g. 100 kW).

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 97
c.) Three-position controller (Standard; Option A: Setting 'THREE POSITION')

Power controller Real power controller insensitivity 0.1..25.0 %


dead band 00.0%
In operation in parallel with the mains, the real power is controlled in such a manner that,
in its regulated state, the actual value deviates from the real power setpoint by the per-
centage value of the sensitivity setting at the most. In this case, the percentage value refers
to the generator rated power (see page 84).

Power controller Real power controller gain factor 0.1..99.9


gain Kp 00.0
The gain factor Kp influences the operating time of the relays. By increasing the factor, the
operating time can be increased in the event of a certain control deviation.

Powercontr. dead Real power controller insensitivity reduction 1.0..9.9


band ratio *0.0
If, following the adjustment of the controller, no further adjusting pulse has been output for
at least 5 s, the insensitivity is reduced by the input factor.
For example: In the case of an insensitivity of 2.5 % and a factor of 2.0 the insensitivity is increased
after 5 s to 5.0 %. If the control deviation subsequently exceeds 5.0 %, again, the controller's original
sensitivity is automatically reset (2.5 %). This input can be used, in the event of small control devia-
tions, to avoid unnecessarily frequent actuation processes, thereby protecting the adjustment facility.

d.) Analog controller (Option A: Setting 'ANALOG')

Power controller Real power controller P gain 1..240


gain Kpr 000
The proportional coefficient specifies the gain (see analog controller).

Power controller Real power controller reset time 0.0..60.0 s


reset Tn 00.0s
The reset time Tn identifies the I part of the PID controller (see analog controller).

Power controller Real power controller derivative-action time 0.0..6.0 s


derivat. Tv 0.00s
The derivative action time TV identifies the D part of the PID controller
(see analog controller).

e.) Part-load lead

Warm up load Part-load lead limit value 5..110 %


limit value 000%
If the engine needs a warm-up run, a lower fixed value power can be entered so that the
engine can first warm up. The setting for the generator real power that is to be adjusted
during this warm-up run phase is made in this screen. A fixed value power in terms of the
rated power input (see page 84) will be adjusted.

Warm up load Period of part-load lead 0..600 s


time 000s
Input of the holding time with part-load following the initial closure of the generator power
circuit breaker in operation in parallel with the mains. If engine warming-up is not desired,
this parameter must be set to zero.

98 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
4.10.6 Load/var sharing [PCM1x]

Active power Load sharing ON/OFF


load-share ON
ON .......... Real power is distributed to several generators operating in parallel. The gen-
erator outputs are distributed depending on the set value. The subsequent
screens of this option are displayed.
OFF .......... No distribution is carried out, and the subsequent screens of this option are
not displayed.

Act. load share Load sharing reference variable 10..99 %


factor 00%
This factor refers to the primary control variable.

Definition "Primary control variable"


• Isolated operation = frequency
• Mains parallel operation = real power (at the mains interchange point)

Definition "Secondary control variable"


• Isolated operation = real power related to the other generators
• Mains parallel operation = real power related to the other generators

The smaller this factor the higher the priority to equally share the load to all generators.

Reactive power var sharing ON/OFF


load share ON
ON .......... Re-active power is distributed to several generators operating in parallel. The
generator outputs are distributed depending on the set value. The subsequent
screens of this option are displayed.
OFF .......... No distribution is carried out, and the subsequent screens of this option are
not displayed.

React.load share var sharing reference variable 10..99 %


factor 00%
Increasing the weighting factor increases the influence of the primary control variable (the
voltage) to the control. The smaller the factor which is configured, the greater the influence
of the secondary control variable (generator reactive power). Var sharing is activated dur-
ing isolated parallel operating only.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 99
4.11 Load management configuration [PCM1x]

Configure Configuration of load management YES/NO


automatic YES
Various groups of parameters are placed together in blocks to allow you to navigate
through the large number of configuration screens more rapidly. Selecting "YES" or "NO"
has no effect on whether or not control or monitoring etc., is carried out. The input merely
has the following effects:
YES .......... The configuration screens in the next block are displayed and can either be
viewed ("STATUS / ALARM" push-button) or modifications can be made to the
parameters ("PARAMETER", "U SELECT" or "STATUS / ALARM" push-button). A
decision is not made on whether the parameters are processed or not.
NO .......... The parameters in the next block are not displayed, cannot be modified and
are therefore skipped.
4.11.1 Load-dependent start/stop in operation in parallel

NOTE

Please be aware that load sharing must remain configured to "ON", regardless of whether an additional
generator is available for a load sharing, in order to enable a automatic start/stop to be carried out .

NOTE

To carry out an automatic start/stop of the engine, all participating controls have to be configured with
the identical rated power.

Loadd.start/stop Load-dependent start/stop on terminal 3 ON/OFF


at ter.3 ON
ON .......... If this mask is active, and the control input "Automatic 1" is connected to termi-
nal 3, an automatic start/stop operation is carried out on the basis of the
generator setpoint power 1 (see page 88). If terminal 5 is simultaneously
connected 3 has priority.
OFF .......... No automatic start/stop operation is carried out; the adjustment of the pre-
specified setpoint value is carried out under all circumstances.

Loadd.start/stop Load-dependent start/stop on terminal 5 ON/OFF


at ter.5 ON
ON .......... If this mask is active, and the control input "Automatic 2" is connected to termi-
nal 5, an automatic start/stop operation is carried out on the basis of the
generator setpoint power 2 (see page 88). If terminal 3 is simultaneously
connected, terminal 3 has priority.
OFF .......... No automatic start/stop operation is carried out; the adjustment of the pre-
specified setpoint value is carried out under all circumstances.

100 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
a.) Single genset in operation in parallel with the mains
The load-dependent start/stop function is activated when
• the "AUTOMATIC" mode has been selected and
• interchange power control (import/export power) has been activated by one of the two
discrete inputs ("Automatic 1" or "Automatic 2") (" I " or " E " power) and
• one or both input screens "Load-dependent stop/start on terminal 3/5" has been set to
"ON".
Minimum load Generator minimum setpoint power 0..6,900 kW
generator 0000kW
Interchange real power control (import/export power) requires a generator setpoint power
value. In many cases, starting the engine is only sensible after reaching a certain genera-
tor setpoint power value, in order therefore to operate the genset with a reasonable de-
gree of efficiency. For example, at least 40 kW of real power must be supplied by the
genset in order for it to start.

Add-on delay Start delay for load-dependent start/stop 0..999 s


mains oper. 000s
Starting may be delayed even if the generator start power has been reached. In order to
avoid starting the engine in the event of short-term load switch-ons, a start delay time may
be input here in seconds. The start power must therefore be present without interruption
during this period of time, in order to ensure that the engine is started.

Shed-off delay Stop delay for load-dependent start/stop 0..999 s


mains oper. 000s
Stopping can be delayed even if the generator stop power has been reached. In order to
avoid switching the engine off in the event of short-term load interruptions, a stop delay
time may be input here in seconds. The stop power must therefore be present without inter-
ruption during this period of time, in order to ensure that the engine is stopped.

b.) Stopping hysteresis

NOTE

The following screen is used to determine stopping hysteresis for single gensets in operation in parallel with
the mains, for gensets connected to other gensets in operation in parallel with the mains and in isolated
operation in parallel with other gensets. However, the screen appears only once at this point.

Hysteresis add-. Hysteresis of load-dependent start/stop 0..9,999 kW


on/off op.0000kW
The stop power of the genset is determined via hysteresis. Hysteresis is used to prevent the
engine continuously starting and shutting down again.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 101
c.) Operation in parallel with the mains (interchange power control with one genset)
The following generally applies:

Case 1: Engine start If [PNT.setpoint - PNT.actual > Pstart] the engine starts. (a)

Case 2: Engine stop If [PNT.setpoint - PNT.actual + PGN.actual.tot < Pstart - PHyst] the engine stops. (b)

Example The power supplied by the mains, which is to be adjusted, is 50 kW. This value is entered
into the setpoint value screen (see chapter "Controller") as "I0050kW". The generator
should be operated with at least 30 kW.

PNT.setpoint= -50 kW....... Incoming/import power must be entered as a negative number,


output/export power as a positive number.
Pstart= 30 kW ............ The minimum power requested by the genset.
PHyst = 10 kW ........... The power hysteresis for stopping.

When inserted into the above mentioned formulae, this means:

Example for case 1 The engine starts with the following incoming mains power: If formula (a) is inverted, this
results in

[PNT.actual < PNT.setpoint - Pstart] ⇒ PNT.actual< - 50 kW - 30 kW = -80 kW ⇒ "B0080 kW".

The power supplied by the mains must be at least 80 kW in order for the engine to start.
This is then operated with a minimum power of 30 kW.

Example for case 2 The engine stops if it has to output less than the minimum power minus hysteresis. This is the
case with the following generator power: If formula (b) is inverted, this results in

[PGN.actual = stop power genset < - PNT.setpoint+ PNT.actual + Pstart - Physt].


[PGN.actual < - 50 kW + 50 kW + 30 kW - 10 kW = 20 kW.

If the generator falls below its minimum power minus hysteresis, it is stopped. The power
incoming from the mains therefore remains at the value which is to be controlled until just
prior to stopping. Following stopping, the power supplied by the mains increases to
70 kW.

102 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
d.) Interconnection with other gensets in operation in parallel with the mains
The load-dependent start/stop function is activated when, for every genset,
• the "AUTOMATIC" mode has been selected and
• interchange power control (import/export power) has been activated by one of the two
discrete inputs ("Automatic 1" or "Automatic 2") (" E "- or " I " power) and
• all inputs, such as start/stop power, start/stop delays, selected setpoint values are
identical for all gensets involved and
• one or both input screens "Load-dependent stop/start on terminal 3/5" has been set to
"ON" and
• the input screens "Load sharing" or. "var sharing" have been set to "ON" and
• the same rated power is available to all gensets.

NOTE

The following parameter only becomes effective if another engine is to be started in operation in parallel
with the mains. The first engine is started as described under individual operation on the basis of minimum
generator power.

Reserve power Reserve power for load-dependent start/stop (mains) 0..9,999 kW


mains op. 0000kW
The starting of an additional engine is determined via the reserve power. The reserve
power results from the currently available total generator rated real power (generator
rated real power × number of closed generator power circuit breakers) and the current to-
tal generator actual real power. If the current total generator real power is deducted from
the currently available total generator rated real power, this results in the system's reserve
power. If negative deviation from this reserve power occurs, the next engine is started.

Total generator rated real power


- Total currently available generator actual real power

= Reserve power

Priority of Priority of gensets 0..14


generators 00
This priority specifies the sequence in which the individual engines are started. The item for
which the smallest number was set has the highest priority. This engine is the first to be
started and the last to be stopped. In the event of identical priorities, the starting sequence
is determined by the operating hours. In this case, the engine with fewer operating hours
takes priority. In the event of the same number of operating hours, the engine with the
smaller item number is permitted to start.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 103
e.) Operation in parallel with the mains (interchange power control with several gensets)
The following generally applies:

Case 3: Start first genset. There is still no GCB connected in the group.

If [PNT.setpoint - PNT.actual > Pstart] the first engine starts. (c)

Case 4: Starting additional gensets. At least one GCB in the group is closed.

If [PGN.actual.tot + Preserve.parallel > Prated.tot] the next engine starts. (d)

Case 5: Stoping At least two GCBs in the group are closed.

If [PGN.act.tot + Preserve.parallel + Physt + Prated < Prated.tot] a engine stops. (e)

Case 6: Stoping last genset Only one more GCBs in the group are closed.

If PNT.setpoint - PNT.actual + PGN.actual.tot < Pstart - Physt] the last engine stops.

Example The real power supplied by the mains, which is to be adjusted, is 0 kW. This value is
entered into the setpoint value screen (see chapter "Controllers") as "B0000kW" (corre-
sponds to "L0000kW"). The reserve power in the system should be 40 kW. The power hys-
teresis should be 20 kW. Three gensets are to be operated within the group. he rated
power of a genset is 200 kW. The minimum power of a genset should be 30 kW.

PRated= 200 kW ......... Rated power of a genset.


PRated.tot ...................... Total of the rated power values of the gensets with closed GCB's.
PStart.tot = 30 kW ........ Minimum power of a genset.
PNT.actual ..................... Current mains power.
PNT.setpoint = B0000 kW . setpoint mains power
PReserve.Parallel = 40 kW.... reserve power in operation in parallel with the mains
PHyst = 20 kW ........... power hysteresis
No. GCB ................ number of closed power circuit breakers

Example for Case 3 Power supplied by the mains, with which the first engine is started:

PNT.actual < PNT.setpoint - Pstart.gen.


PNT.actual < 0 kW - 30 kW = -30 kW ⇒ B0030 kW.

The power supplied by the mains must be at least 30 kW in order for the first engine to
start. This is then operated with a minimum power of 30 kW.

Example for Case 4 Generator real power, at which the second engine is started:

PGN.actual > Prated.tot - (PReserve.Parallel / No. GCB).


PGN.actual > 200 kW – (40 kW / 1) = 160 kW.

If the generator real power exceeds 160 kW, negative deviation from the pre-specified re-
serve power has occurred. As a result of this, the next engine is started.

104 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
Example for Case 4 Generator real power of each individual genset, at which the third engine is started:

PGN.actual > Prated.tot - (Preserve.parallel / No. GCB) - Prated.


PGN.actual. > 400 kW – (40 kW / 2) - 200 kW = 180 kW.

If the generator real power of both gensets exceeds 360 kW (each genset supplies more
than 180 kW), negative deviation from the pre-specified reserve power has occurred. As a
result of this, the next engine is started.

Example for Case 5 Generator real power of each individual genset, at which one genset is stopped:

PGN.actual.tot < Prated.tot - Preserve.parallel - Prated - Physt.


PGN.actual.tot < 600 kW - 40 kW - 200 kW - 20 kW = 340 kW.
(PGN.actual < PGN.actual.tot ) / No. GCB = 340 kW / 3 = 113.3 kW.

If the generator real power of the three gensets falls below 340 kW (each individual gen-
set below 113.3 kW), one engine is stopped. After one engine has been stopped, the in-
put reserve power is still available.

Example for Case 5 Generator real power of each individual genset, at which one of the two engines is
stopped:

PGN.actual.tot < Prated.tot - Preserve.parallel - Prated - Physt.


PGN.actual.tot < 400 kW - 40 kW - 200 kW - 20 kW = 140 kW.
(PGN.actual < PGN.actual.tot) / No. GCB = 140 kW / 2 = 70 kW.

If the generator real power of the two gensets falls below 140 kW (each individual genset
below 70 kW), one engine is stopped. After the engine has been stopped, the input re-
serve power is still available.

Example for Case 6 Generator real power, at which the last engine is stopped:

PGN.actual < - PNT.setpoint + PNT.actual + Pstart.gen - Physt.


PGN.actual. < - 0 kW + 0 kW + 30 kW - 20 kW = 10 kW.

If the generator falls below its minimum real power minus hysteresis, the engine is stopped.
The power incoming from the mains therefore remains at the value which is to be controlled
until just prior to stopping. Following stopping, the power supplied by the mains increases
to 10 kW.

f.) Isolated operation


The load-dependent start/stop function is activated when, for every genset
• the "AUTOMATIC" mode has been selected and
• all inputs, such as start/stop power, start/stop delays, frequency setpoint values are
identical for all gensets involved and
• one or both input screens "Load-dependent stop/start on terminal 3/5" has been set to
"ON" and
• the input screens "Load sharing" or "var sharing" have been set to "ON" and
• the same rated power is available to all gensets.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 105
Reserve power Reserve power for load-dependent start/stop (isol. op.) 0..9,999 kW
isol.op. 0000kW
Starting of an additional engine is determined via the reserve power. The reserve power
results from the currently available total generator rated real power (generator rated real
power × number of closed generator power circuit breakers) and the current total genera-
tor actual real power. If the current total generator real power is deducted from the cur-
rently available total generator rated real power, this results in the system's reserve power.
If negative deviation from this reserve power occurs, the next engine is started.

Total generator rated real power


- Total currently available generator actual real power

= Reserve power

NOTE

The reserve power should be selected in such a manner that the expected load surges can be covered by
the genset.

Add-on delay Start delay for load-dependent start/stop 0..999 s


isol.op. 000s
Starting may be delayed even if the engine's start power has been reached. In order to
avoid starting the engine in the event of short-term load switch-ons, a start delay time may
be input in seconds. The start power must therefore be present without interruption during
this period of time, in order to ensure that the engine is started.

Shed-off delay Stop delay for load-dependent start/stop 0..999 s


isol.op. 000s
Stopping can be delayed even if the engine's stop power has been reached. In order to
avoid switching the engine off in the event of short-term load interruptions, a stop delay
time may be input in seconds. The stop power must therefore be present without interrup-
tion during this period of time, in order to ensure that the engine is stopped.

The following generally applies:

Case 7: Engine start If [PGN.actual.tot + Preserve.isolated + > Prated.tot] the engine starts. (f)

Case 8: Engine stop If [PGN.actual.tot + Preserve.isolated + Physt + Prated + < Prated.tot] the engine stops.

Example Two gensets are used in isolated operation in parallel with other gensets. One genset
should always be in operation.

Prated = 200 kW ........ Rated real power of a genset.


PReserve.isolated= 60 kW
Physt = 30 kW

Example for Case 8 Generator real power, at which the second engine is started:

PGN.actual > Prated.tot - Preserve.isolated.


PGN.actual > 200 kW - 60 kW = 140 kW.

If the generator real power exceeds 140 kW negative deviation from the pre-specified
minimum reserve power occurs. As a result of this, the next engine is started.

106 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
Example for Case 9 Generator real power, at which the second engine is stopped:

PGN.actual.tot < Prated.tot - Preserve.isolated - Prated - Physt.


PGN.actual.tot < 400 kW - 60 kW - 200 kW - 30 kW = 110 kW.
PGN.actual < PGN.actual.tot / No. GCB = 110 kW / 2 = 55 kW.

If, in the case of outgoing isolated load, the total actual generator real power is reduced to
such an extent that one genset is sufficient to ensure the reserve power, the second engine
is stopped.

4.11.2 Temperature dependent start/stop [PCM1x/H]

a.) Automatic start/stop

CHP temp.depend. CHP temperature dependent start/stop on terminal 3 ON/OFF


at ter.3 ON
ON .......... If this mask is active and the control input "Automatic 1" is connected to termi-
nal 3 a temperature dependent start/stop operation is carried out. If termi-
nal 5 is simultaneously connected, terminal 3 has priority. The start/stop is
performed via analog input 2.
OFF .......... No automatic start/stop operation is carried out via terminal 3 depending on
the temperature.

CHP temp.depend. CHP temperature dependent start/stop on terminal 5 ON/OFF


at ter.5 ON
ON .......... If this mask is active and the control input "Automatic 2" is connected to termi-
nal 5 a temperature dependent start/stop operation is carried out. If termi-
nal 3 is simultaneously connected, terminal 3 has priority. The start/stop is
performed via analog input 2.
OFF .......... No automatic start/stop operation is carried out via terminal 5 depending on
the temperature.

Even if temperature dependent start/stop is switched off on both terminals, the subsequent
screens of this option are displayed.

CHP start-up CHP switch-on temperature 0..255 °C


temperat. 000°C
The temperature at which the engine is to be started is set in this mask. If this value is not
reached, the engine starts automatically and runs until the switch-off temperature is
reached.

CHP shut-down CHP switch-off temperature 0..255 °C


temperat. 000°C
The temperature at which the engine is to be stopped is set in this mask. If the value is
reached or exceeded, the engine stops automatically.

CHP start-up CHP switch-on delay 0..255 s


delay 000s
In order for the engine to be started, uninterrupted, negative deviation from the switch-on
temperature must occur for at least the period of time set in this mask. If the actual value
exceeds the threshold value within this period of time, calculation of the time is re-started
(this delay time applies both to switching on and switching off).

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 107
b.) Temperature dependent power reduction

reduce of load Temperature level 1 for the power reduction 0..255 °C


step 1 at 000°C
If the value set here is reached, the first level of the temperature dependent power reduc-
tion takes effect. The power reduction is performed via analog input 2.

reduce of load Temperature level 2 for the power reduction 0..255 °C


step 2 at 000°C
If the value set here is reached, the second level of temperature dependent power reduc-
tion takes effect. The power reduction is performed via analog input 2.

reduce of load Magnitude of the power reduction, level 1 and level 2 0..100 %
per step 000%
If the set value for temperature dependent power reduction is reached (level 1 and
level 2), the generator power is reduced each by the value set here as a percentage of
the generator rated power. The power reduction is performed via analog input 2.

4.11.3 Stop of the engine at mains failure [PCM1-G]

Mains error - Engine stop at mains failure ON/OFF


stop eng. ON
ON .......... If the mains fails for at least the time of the emergency power start delay and
the discrete input "Enable MCB" (terminal 53) is set (the mains parallel opera-
tion is enabled), the engine is stopped. Once the mains returns and the mains
settling time has expired, the engine is started and the GCB is synchronized.
OFF .......... If the mains fails for at least the time of the emergency power start delay and
the discrete input "Enable MCB" (terminal 53) is set (the mains parallel opera-
tion is enabled), the GCB is opened. The engine is running in idle mode.
Once the mains returns and the mains settling time has expired, the GCB is
synchronized.

108 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
4.11.4 Remote control via interface - Guidance bus [PCx/H]

NOTE

For remote acknowledgement of alarms you have to carry out first a remote stop in idle mode. If this
control is in isolated operation, an acknowledgement combined with a remote start must be sent..

Control via Control via interface COM X1..X5 ON/OFF


COM X1X5 ON
ON .......... Control via the interface is activated if the item contains this option, direct con-
figuration is set to "OFF", the control system is set to "ON" the operating mode
is set to "AUTOMATIC" and the discrete input "Automatic 2" (terminal 5) has
been selected. The engine can be started and stopped via "Remote start" de-
scription of the serial interface in the appendix). The generator setpoint real
power and the generator setpoint power factor ϕ may also be transmitted. If
unsuccessful data exchange is determined, an alarm class 1 alarm is trig-
gered.
OFF .......... The acceptance of control data is rejected. The internally set power "Psetpoint2" is
activated with the discrete input "Automatic 2". At the same time, the internally
set power factor ϕ setpoint is accessed. Interface monitoring is deactivated.

Supervision Remote monitoring of the interface ON/OFF


COMX1X5 EIN
ON .......... Remote monitoring of the interface is enabled. If no control signal is received
only if COMX1X5 = ON within 90 seconds (ID 503), a warning alarm of alarm class 1 will be issued.
OFF .......... Remote monitoring of the interface is disabled.

Ackn. F2,F3 via Acknowledgment of F2/F3 alarms via the interface ON/OFF
COM interf ON
ON .......... Alarm acknowledgement of alarms of the alarm classes F2/F3 via the inter-
only if COMX1X5 = ON face is enabled
OFF .......... Alarm acknowledgement of alarms of the alarm classes F2/F3 via the inter-
face is disabled. Acknowledgment can be performed via the discrete input
"Acknowledgment" (terminal 6) or via the push button "RESET".

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 109
4.11.5 Power circuit breaker configuration

Configurebreaker Configuration of the power circuit breakers ON/OFF


YES
Various groups of parameters are placed together in blocks to allow you to navigate
through the large number of configuration screens more rapidly. Selecting "YES" or "NO"
has no effect on whether or not control or monitoring etc., is carried out. The input merely
has the following effects:
YES .......... The configuration screens in the next block are displayed and can either be
viewed ("STATUS / ALARM" push-button) or modifications can be made to the
parameters ("PARAMETER", "U SELECT" or "STATUS / ALARM" push-button). A
decision is not made on whether the parameters are processed or not.
NO .......... The parameters in the next block are not displayed, cannot be modified and
are therefore skipped.

4.11.6 Power circuit breaker logic

NOTE

You can change between two breaker logics via the discrete input "Breaker logic via discrete input"
(description on page 132). The desired standard breaker logic is configured via the following mask. If the
discrete input terminal 62 is configured to "Control input" (parameter is ON) and if is there is a signal to
the terminal the described breaker logic is used (see chapter 4.15.3 “Setting the control inputs” at
page 135). If the signal is reset, the breaker logic of the following mask is valid again. Therefore it is
possible during the operation i.e. to change between the breaker logic "PARALLEL" (automatic
synchronizing) and "EXTERNAL" (manual synchronizing).

The item automatically controls the two power circuit breakers (MCB and GCB). In this
Breaker logic:
case, up to five control functions (modes) may be selected. These are: EXTERNAL, PARAL-
PARALLEL
LEL, OPEN TRANSIT, CLOSED TRANSIT and INTERCHANGE.

110 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
a.) Version PCL1 & PCM1-M
STOP TEST MANUAL AUTOMATIC
EXTERNAL CB logic "External"
In this operating mode, the MCB and the GCB are operated in "MANUAL" mode only. In operation in parallel with the mains,
uncoupling from the mains is carried out via the MCB or the GCB in the event of mains faults. The power circuit breakers are
not automatically closed in emergency power operation. Emergency power operation in accordance with DIN VDE 0108 is
not therefore possible in this power circuit breaker logic.
The GCB is The GCB and the MCB are not oper- The MCB and the GCB can be manu- The GCB is opened for stopping or for de-
opened. ated. Exception: The circuit breakers ally switched on and off without syn- coupling from the mains, but is not closed for
are opened for decoupling from the chronization. The circuit breakers are starting. The MCB is only opened for decoup-
mains. opened for decoupling from the mains. ling from the mains, and is never closed.
PARALLEL CB logic "Mains parallel"
[PCM1-M] This operating mode represents continuous operation in parallel with the mains.
The GCB is The GCB and the MCB are not oper- Operation in parallel with the mains Via a engine request, the GCB is synchronized
opened, the ated. Exception: Load test by actuating can be assumed via the "GCB ON" or and operation in parallel with the mains is
MCB is not the "GCB ON" push-button. Termina- "MCB ON" push-button. assumed. On enabling of the engine request,
operated. tion of the load test with the "GCB the generator power is reduced, the GCB is
OFF" push-button. Emergency power: opened and the engine is shut off with coast-
Automatic setting of the GCB. Black ing. Emergency power operation is terminated
busbar and current release MCB will following the expiry of a mains settling time
be closed. with the reverse synchronization of the MCB.
OPEN TRANSIT. CB logic "Open transition / ATS / change-over / brake-before-make"
In this operating mode, the MCB and GCB are never synchronized.
The GCB is The GCB and the MCB are not oper- Via the "GCB ON" and "MCB ON" A switch is made to generator operation via
opened, the ated. Exception: Load test by actuating push-button, a switch can be made to an engine request. On enabling of the engine
MCB is not the "GCB ON" push-button. Termina- either generator or mains operation. request a switch is made back to mains opera-
operated. tion of the load test via the "GCB OFF" The "STOP" push-button opens the GCB tion. Even if no engine request is present, the
or "MCB ON" push-button. Emergency and simultaneously stops the engine. MCB is closed when the busbar is voltage-
power: Automatic setting of the GCB. free. Emergency power operation is terminated
following the expiry of a mains settling time
with the reverse synchronization of the MCB.
CLOSED TRANSIT. CB logic "Closed transition / make-before-brake / no-break-transfer / overlap synchronization"
In this operating mode, the MCB and the GCB are synchronized, in order to avoid a voltage-free busbar. Immediately after the
synchronization of one power circuit breaker, the other is opened. Continuous operation in parallel with the mains is not possi-
ble.
The GCB is The GCB and the MCB are not oper- Via the "GCB ON" and "MCB ON" The GCB is synchronized via a engine re-
opened, the ated. Exception: Load test by actuating push-button, synchronization to either quest. The MCB is then opened. Following the
MCB is not the "GCB ON" push-button. Termina- generator or mains operation can be enabling of the engine request, the MCB is
operated. tion of the load test via the "GCB OFF" carried out. reverse synchronized and the GCB is then
or "MCB ON" push-button. Emergency opened. Emergency power operation is termi-
power: Automatic setting of the GCB. nated following the expiry of a mains settling
time with the reverse synchronization of the
MCB.
INTERCHANGE CB logic "Softloading / interchange synchronization"
[PCM1-M] In this operating mode, the MCB and the GCB are synchronized, in order to avoid a voltage-free busbar. The actuation of a
power circuit breaker under load is avoided. Otherwise, the other power circuit breaker is opened immediately following the
synchronization of the one power circuit breaker. Continuous operation in parallel with the mains is not possible. Following the
reset of the engine request, the MCB is synchronized, the engine is stopped with a reduction in power.
The GCB is The GCB and the MCB are not oper- Via the "GCB ON" and "MCB ON" Via a engine request, the GCB is synchronized
opened, the ated. Exception: Load test by actuating push-button, synchronization to either and the generator power is reduced. The
MCB is not the "GCB ON" push-button. Termina- generator operation or operation with MCB is then opened. Following the enabling
operated. tion of the load test via the "GCB OFF" the mains can be carried out. of the engine request, the MCB is reverse
or "MCB ON" push-button. Emergency synchronized and the GCB is then opened.
power: Automatic setting of the GCB. Emergency power operation is terminated
Black busbar and current release MCB following the expiry of a mains settling time
will be closed. with the reverse synchronization of the MCB.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 111
b.) Version PCM1-G
STOP TEST MANUAL AUTOMATIC
EXTERNAL CB logic "External"
In this operating mode, the GCB is never synchronized. In operation in parallel with the mains, decoupling from the mains is
carried out via the GCB in the event of mains faults. The power circuit breaker is not automatically closed in emergency power
operation.
The GCB is The GCB is not operated. Exception: The GCB can be manually switched on The GCB is opened for stopping or for de-
opened. The circuit breaker is opened for de- and off without synchronization. The coupling from the mains, but is not closed in
coupling from the mains. circuit breaker is opened for decoup- the event of a engine request.
ling from the mains.
PARALLEL CB logic "Mains parallel"
This operating mode may be used both in the case of an isolated system, an isolated parallel system and a system which is
operated in parallel with the mains.
The GCB is The GCB is not operated. Exception: Operation in parallel with the mains Via a engine request, the GCB is synchronized
opened. Load test by actuating the "GCB ON" can be assumed via the "GCB ON" and operation in parallel with the mains is
push-button. Termination of the load test push-button. assumed. On enabling of the engine request,
with the "GCB OFF" push-button. the generator power is reduced, the GCB is
Emergency power: The GCB is opened and the engine is shut off with coast-
opened for decoupling from the mains. ing.

Add-on/off ramp Start/stop ramp 0..999 s


max.time 000s
This time can be used to influence two functions:

Stop
The power of the genset is reduced, at most, for the time set here. If, within this time, nega-
tive deviation from 3 % of the generator rated power (see page 84) does not occur, the
GCB is still opened.

Start with interchange synchronization


If, in interchange synchronization, the reference power level to be supplied by the mains
of "zero" is not reached within the time set here, a "Reference power.<>0" message and
an alarm class 1 alarm is issued. At the same time, the relay manager relay, which is pro-
grammed with parameter 78 is set.

Open GCB with F2 Max. perm. time with F2 alarms for starting a further engine 0..999 s
max.time 000s
Prerequisite: Load sharing and automatic start/stop are set to "ON". The generator is
in isolated operation and at least one additional generator is connected to a busbar.

If an alarm class 2 alarm occurs, switching the engine off may be delayed by this time.
Another engine is therefore given the opportunity to start in order to assume the load.
Shutdown is activated following the expiry of this time.

112 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
4.11.7 GCB pulse/continuous pulse

GCB close.relay Signal logic for the GCB Impulse/Constant


-----------------------------
Constant ... The relay "Command: close GCB" can be looped directly into the self-holding
circuit of the power circuit breaker. After the connect pulse has been output
and the reply of the power circuit breaker has been received, the relay
"Command: close GCB" remains picked up. As long as the following condi-
tions are fulfilled:
”Reply: GCB is closed” is active.
The angle between generator voltage and busbar voltage is within ±14°.
If the power circuit breaker has to be opened, the relay drops out.
Impulse ..... The relay "Command: close GCB" outputs a connect pulse. Generator power
circuit breaker self-holding must be carried out via an external self-holding cir-
cuit. The reply of the generator power circuit breaker is used to detect the
closed contacts.
In both cases, the relay "Command: open GCB" remains picked up.

GCB open relay Opening the GCB (terminal 41/42) NO-contact/NC-contact


------------------------------
NC-cont. ... If the generator power circuit breaker is to be opened, the relay "Command:
open GCB" (terminal 41/42) remains picked up. Following "Reply: GCB is
open" the relay drops off again.
NO-cont. ... If the generator power circuit breaker is to be opened, the relay "Command:
open GCB" (terminal 41/42) drops off. Following "Reply: GCB is open" the
relay picks up again.

4.11.8 Synchronization

Synchronize Max. perm. differential frequency for synchron. (pos. slip)0.02..0.49 Hz


df max 0.00Hz
The prerequisite of a connect command's being output is negative deviation from this set
differential frequency. This value specifies the upper frequency (positive value corresponds
to positive slip ! generator frequency is greater than the busbar frequency on connection
of the GCB; busbar frequency is greater than the mains frequency in the case of MCB
synchronization).

Synchronize Max. perm. differential frequency for syn. (neg. slip) 0.00..-0.49 Hz
df min -0.00Hz
The prerequisite of a connect command's being output is negative deviation from this set
differential frequency. This value specifies the lower frequency (negative value corresponds
to negative slip ! generator frequency is less than the busbar frequency in the case of
GCB synchronization; busbar frequency of smaller mains frequency for MCB synchroniza-
tion).

Synchronize Max. perm. differential voltage for synchronization 0.1..20.0 %


dV max 00,0%
This value refers to the parameter “Rated voltage in System”. To ensure that a connect
command will be issued, the actual value must fall below the entered differential voltage.

Synchronize Min. pulse duration of connect relay for synchronization 0.02..0.26 s


time pulse >0.00s
The duration of the connect pulse can be adjusted to the downstream switching item (valid
for synchronization and black start).

Closing time Inherent delay of GCB for synchronization 40..300 ms


GCB 000ms
The inherent switching time of the generator power circuit breaker corresponds to the lead-
time of the connect command. The connect command will be issued independently of the
differential frequency at the entered time (before the synchronous point).

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 113
Closing time Inherent delay of MCB for synchronization 40..300 ms
MCB 000ms
The inherent switching time of the mains power circuit breaker corresponds to the lead-time
[PCL1 & PCM1-M] of the connect command. The connect command will be issued independently of the dif-
ferential frequency at the entered time (before the synchronous point).

Automat.breaker Automatic circuit breaker enabling ON/OFF


deblocking ON
ON .......... Prior to each connect pulse, a "Command: open GCB", or "Command: open
MCB" is output for 1 second. A connect signal is then set until the circuit
breaker is closed.
OFF .......... Circuit breaker initialization on closing is carried out only via the connect
pulse. No open pulse is output prior to the close pulse.

4.11.9 Synchronization time monitoring

Sync.time contr. Monitoringw of synchronization time ON/OFF


ON
ON .......... This setting ensures that the synchronization time will be monitored. The sub-
sequent screens of this option are displayed.
OFF .......... The synchronization will not be monitored. A synchronization will be tried
again and again until it can be carried out. The subsequent screens of this op-
tion are not displayed.

Sync.time contr. Final value for synchronization time monitoring 10..999 s


delay 000s
If the synchronization of the GCB or MCB is started, the time counter is started following
the expiry of delayed engine monitoring. If the power circuit breaker is not inserted once
the set time has elapsed, the warning messages "GCB sync. time" or "MCB sync. time" are
displayed. A further attempt is made to close the power circuit breaker. The relay with
function 16 (GCB) and/or 70 (MCB) is set.

Tripping of alarm class 1

114 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
4.11.10 Dead start

If the busbar is in its voltage-free state, the direct connection (black start) of the generator
power circuit breaker (GCB) or the mains power circuit breaker (MCB) may be carried out.
If both connect commands are issued simultaneously, priority is given to the MCB if the in-
put "Enable MCB" is set.

NOTE

The mains power circuit breaker is never opened except in the mains protection function or in the event of
emergency power operation.

GCB dead bus op. Black start of GCB ON/OFF


ON
ON .......... A black start is carried out in the event of a voltage-free busbar and an open
mains power circuit breaker. The prerequisite of this is the detection of an op-
erating condition which corresponds to the specifications. The subsequent
screens of this option are displayed.
OFF .......... No black start is carried out (not even in operation mode MANUAL), and the
subsequent screens of this option are not displayed.

GCB dead bus op. Maximum differential frequency for GCB black start 0.05..5.00 Hz
df max 0,00Hz
The prerequisite of the output of the connect command is that the generator frequency
may, at most, deviate from the setpoint by the set value.

GCB dead bus op. Maximum differential voltage for GCB black start 0.1..15.0 %
dV max. 00.0%
This value refers to the parameter “Rated voltage in system”. The prerequisite of the output
of the connect command is that the generator voltage may, at most, deviate from the set-
point by the set value.

GCB dead bus op Maximum time for closing the GCB 0..999 s
max.time 000s
If the generator power circuit breaker (GCB) is to be closed, this time counter is started af-
ter the procedure of switching to the black busbar has been started. If, following the expiry
of this time counter, connection has not yet been carried out, an alarm message is output.

Tripping of alarm class 1

MCB dead bus op. Black start of MCB ON/OFF


ON
ON .......... A black start is carried out in the event of a voltage-free busbar and an open
[PCL1 & PCM1-M] generator power circuit breaker. The prerequisite of this is the detection of an
operating condition which corresponds to the specifications. The subsequent
screens of this option are displayed.
OFF .......... No black start is carried out, and the subsequent screens of this option are not
displayed.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 115
4.11.11 Circuit breaker monitoring (switch pulses)

Supervision GCB GCB monitoring ON/OFF


ON
ON .......... Monitoring of the generator power circuit breaker is carried out (except in the
"EXTERNAL") CB logic. If the circuit breakers cannot be closed by the fifth at-
tempt, the alarm class alarm message "GCB CLOSED malfunction" is output.
The relay is set with the parameter 75. Following an alarm message, further
attempts are made to connect the GCB. If load sharing has been enabled the
closing command to the breaker is deleted in the case of an alarm to enable
another control to close its breaker. If, 2 seconds following a "Command:
open GCB" pulse, the "Reply: GCB is open" is not detected, an alarm with the
message "GCB OFF malfunction" is output. the relay is set with parameter 77.

Tripping of alarm class 1

OFF .......... No GCB monitoring is carried out.

Supervision MCB MCB monitoring ON/OFF


ON
ON .......... Monitoring of the mains power circuit breaker is carried out (except in the "EX-
[PCL1 & PCM1-M] TERNAL" CB logic). If the circuit breakers cannot be closed by the fifth at-
tempt, an alarm message "MCB CLOSED malfunction" is output. The relay is
set with parameter 74. If load sharing has been enabled the closing com-
mand to the breaker is deleted in the case of an alarm to enable another con-
trol to close its breaker. Following an alarm message, further attempts are
made to connect the MCB. If 2 seconds following a "Command: open MCB"
pulse the "Reply: MCB is open" is not detected, an alarm with the message
"MCB OPEN malfunction" is output. the relay is set with parameter 76.

Tripping of alarm class 1

OFF .......... No MCB monitoring is carried out.

116 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
4.11.12 Mains decoupling

Mains decoupling Decoupling from the mains via ... GCB; GCB->EXT; EXT; EXT->GCB
via --------------------
GCB ......... In case of a mains failure the GCB will be opened. (The mains failure is de-
only on PCM1-G tected via the mains voltage [terminals 50/51/52]).

GCB->EXT . In case of a mains failure the GCB will be opened. (The mains failure is de-
tected via the mains voltage [terminals 50/51/52]). If there is no reply de-
tected via terminal 4 that the GCB has been opened, an alarm message will
be issued with the expire of the delay time. The relay 76 of the relay manager
will be set, too. The "Command: open GCB" relay will be reset (termi-
nal 41/42) and therefore the relay with terminals 39/40 is set.
Tripping of alarm class 1
EXT........... In case of a mains failure the relay with the terminals 39/40 will be set. (The
mains failure is detected via the mains voltage [terminals 50/51/52]).

EXT->GCB . In case of a mains failure the relay with the terminals 39/40 will be set. (The
mains failure is detected via the mains voltage [terminals 50/51/52]). If
there is no reply detected via terminal 54 that the breaker has been opened,
an alarm message will be issued with the expire of the delay time. The func-
tion 77 of the relay manager will be set, too. The relay with the termi-
nals 39/40 will be reset and therefore the relay "Command: open GCB"
(terminals 41/42) is set.
Tripping of alarm class 1

Paramet
Decoupling from the mains via ... GCB; GCB->MCB; MCB; MCB->GCB
Mains decoupling
via ------------------- GCB ......... In case of a mains failure the GCB will be opened. (The mains failure is de-
tected via the mains voltage [terminals 50/51/52]).
only on PCM1-M

GCB -> MCB In case of a mains failure the GCB will be opened. (The mains failure is
detected via the mains voltage [terminals 50/51/52]). If there is no reply de-
tected via terminal 4 that the GCB has been opened, an alarm message will
be issued with the expire of the delay time. The function 76 of the relay man-
ager will be set, too. The "Command: open GCB" relay will be reset (termi-
nal 41/42) and therefore the relay "Command: open MCB" (termi-
nals 39/40) is set.
Tripping of alarm class 1
MCB......... In case of a mains failure (Fehler!
Fehler! Verweisquelle konnte nicht gefunden
werden. to Fehler! Verweisquelle konnte nicht gefunden werden.)
werden. the MCB
will be opened. (The mains failure is detected via the mains voltage [terminals
50/51/52]).

MCB->GCB In case of a mains failure the MCB will be opened. (The mains failure is
detected via the mains voltage [terminals 50/51/52]). If there is no reply de-
tected via terminal 54 that the MCB has been opened, an alarm message
will be issued with the expire of the delay time. The function 77 of the relay
manager will be set, too. The "Command: open MCB" relay will be reset
(terminals 39/40) and therefore the relay "Command: open GCB" (termi-
nals 41/42) is set.
Tripping of alarm class 1

Parameter 1
Mains decoupling after 0.10..5.00 s
Mains decoupling
-> after 0,00s Time after which the change of the type of the mains decoupling should be performed.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 117
WARNING

During maintenance at the busbar take into account that an open MCB will be closed by the GCP
with the expire of the mains settling time when the following parameter is configured to "YES".
Configure the parameter to "NO" or prevent the busbar to be energized.

Switch MCB in Operate MCB in operation mode STOP YES/NO


STOP mode NO
YES ..........The MCB will be operated by the GCP in operation mode STOP, i.e. the
busbar will be supplied also in case of changing into this operation mode.
Thereto it is necessary that the "Enable MCB" is set.
NO ..........The MCB will not be operated by the GCP in operation mode STOP, i.e. the
busbar will not be supplied or remains unsupplied in case of changing into
this operation mode.

4.12 Emergency power configuration [PCL1 & PCM1-M]

NOTE

Emergency power is only possible with synchronous generators with 2 power circuit breakers.

Configure Configuration of the emergency power YES/NO


emergency YES
Various groups of parameters are placed together in blocks to allow you to navigate
through the large number of configuration screens more rapidly. Selecting "YES" or "NO"
has no effect on whether or not control or monitoring etc., is carried out. The input merely
has the following effects:
YES .......... The configuration screens in the next block are displayed and can either be
viewed ("Select" push-button) or modifications can be made to the parameters
("Cursor→", "Digit↑" or "Select" push-button). A decision is not made on
whether the parameters are processed or not.
NO .......... The parameters in the next block are not displayed, cannot be modified and
are therefore skipped.

HINWEIS

Emergency power is possible only with synchronous generators with 2 breakers, i.e. PCM1-M and the
PCM1-G with PCN4 coupling.

Emergency power Emergency power ON/OFF


ON
ON .......... If the item is set to "AUTOMATIC" or "TEST" mode and a mains failure occurs,
the engine is started and automatic emergency power operation is carried
out. The subsequent screens of this option are displayed. Emergency power is
also triggered via the detection of a switch fault when the MCB is switched
on. In order to achieve this, the "MCB monitoring" screen must additionally be
set to "ON".
OFF .......... Emergency power operation is not carried out and the subsequent screens of
this option are not displayed.

118 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
CAUTION !

Emergency power in accordance with DIN VDE 0108 s not possible in "EXTERNAL" CB logic!

Emergency power Starting delay for emergency power 0.5..99.9 s


start del. 00.0s
In order to start the engine and to carry out emergency power operation, the mains must
have failed for a minimum period of time.

4.13 Watchdog configuration

Configure Configuration of the watchdog YES/NO


monitoring YES
Various groups of parameters are placed together in blocks to allow you to navigate
through the large number of configuration screens more rapidly. Selecting "YES" or "NO"
has no effect on whether or not control or monitoring etc., is carried out. The input merely
has the following effects:
YES .......... The configuration screens in the next block are displayed and can either be
viewed ("STATUS / ALARM" push-button) or modifications can be made to the
parameters ("PARAMETER", "U SELECT" or "STATUS / ALARM" push-button). A
decision is not made on whether the parameters are processed or not.
NO .......... The parameters in the next block are not displayed, cannot be modified and
are therefore skipped.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 119
4.13.1 Generator power monitoring

Monitoring the generator power's exceeding two values, which can be configured, is pos-
sible. Via the relay manager (parameter 56 and 80) tripping can be set to each one of the
relays, which can be freely configured. The execution of load shutoff is therefore possible
with an external circuit.

Note With this function no centralized alarm is output and no message is output on the display.
Only a relay output, which has to be externally evaluated, is carried out.

CAUTION !

This function does not represent generator protection.


If generator protection is necessary, either the generator protection of this control or an external protection
device can be used.

Gen.power monit. Generator power monitoring ON/OFF


ON
ON .......... The generator power is monitored with regard to its exceeding two values,
which can be freely configured. In order to enable output, the following val-
ues must be set in the relay manager: level 1 = 56; level 2 = 80. The subse-
quent screens of this option are displayed.
OFF .......... Monitoring is not carried out, and the subsequent screens of this option are
not displayed.

Gen.power monit. Power monitoring threshold value, level 1 0..9,999 kW


resp.val1 0000kW
The value as of which the watchdog is triggered is specified here. If the value has been
exceeded, the relay assigned via the relay manager (parameter 56).

Gen.power monit. Power monitoring hysteresis, level 1 0..999 kW


hyst.lv1 000kW
If negative deviation from the threshold value by the hysteresis value occurs, the relay
drops off again.

Gen.power monit. Power monitoring delay, level 1 0..999 s


delay lv1 000s
In order to trip monitoring, the threshold value must be exceeded without interruption for at
least the period of time specified in this screen.

Gen.power monit. Power monitoring threshold value, level 2 0..9,999 kW


resp.val2 0000kW
The value as of which the watchdog is triggered is specified here. If the value has been
exceeded, the relay assigned via the relay manager (parameter 80).

Gen.power monit. Power monitoring hysteresis, level 2 0..999 kW


hyst.lv2 000kW
If negative deviation from the threshold value by the hysteresis value occurs, the relay
drops off again.

Gen.power monit. Power monitoring delay, level 2 0..999 s


delay lv2 000s
In order to trip monitoring, the threshold value must be exceeded without interruption for at
least the period of time specified in this screen.

120 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
4.13.2 Mains power monitoring [PCM1x]

Monitoring the mains power's exceeding a value, which can be configured, is possible.
Via the relay manager (parameter 67) tripping can be set to one of the relays, which can
be freely configured. The execution of load shutoff is therefore possible with an external
circuit.

Note With this function no centralized alarm is output and no message is output on the display.
Only a relay output, which has to be externally evaluated, is carried out.

CAUTION!

This function does not represent generator protection.


If generator protection is necessary, either the generator protection of this control or an external protection
device can be used.

Mains power mon. Mains power monitoring ON/OFF


ON
ON .......... Switching mains power monitoring on. One relay must be occupied with pa-
rameter 56 of the relay manager. The subsequent screens of this option are
displayed.
OFF .......... Monitoring is not carried out, and the subsequent screens of this option are
not displayed.

Mains power mon. Power monitoring threshold value I/E 0..9,999 kW


res.val. I0000kW
The value as of which the watchdog is triggered is input here. If the value is exceeded,
the relevant relay picks up. Incoming power is input with a "-", before the value, outgoing
power is input with a "+" before the value. If this value is saved, the "-" becomes " I " and
the "+" becomes " E ".

Mains power mon. Power monitoring hysteresis 0..999 kW


hysteresis 000kW
If negative deviation from the threshold value by the hysteresis value occurs, the relay
drops off again.

Mains power mon. Power monitoring delay 0..650 s


delay 000s
In order to trip monitoring, the threshold value must be exceeded without interruption for at
least the period of time specified in this screen.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 121
4.13.3 Generator overload monitoring

Overload monit. Generator overload monitoring ON/OFF


ON
ON .......... Switching generator overload monitoring on. The subsequent screens of this
option are displayed.
OFF .......... Monitoring is not carried out, and the subsequent screens of this option are
not displayed.

Gen.overload MOP Generator overload monitoring threshold value 80..150 %


resp.value 000%
The threshold value refers to the input rated power of the generator (see page 84). Trip-
ping is carried out without delay (MOP..operation in parallel with the mains).
Generator overload.................... Tripping if the generator real power exceeds the limit
value.

Tripping of alarm class 2


without power reduction

Gen.overload MOP Generator overload monitoring delay (mains parallel operation) 0..99 s
delay 00s
For a tripping the threshold must be exceeded continuously minimum for the time shown in
this mask.. A coasting is made. (MOP..mains parallel operation).

Gen.overload IOP Generator overload monitoring threshold value 80..150 %


resp.value 000%
The threshold value refers to the generator rated power input (see page 84) (IOP..isolated
operation in parallel with other gensets, also for single plants in isolated operation).
Generator overload.................... Tripping, if the generator real power exceeds the limit
value.

Tripping of alarm class 2


without power reduction

Gen.overload IOP Generator overload monitoring delay (isolated operation) 0..99 s


delay 00s
In order for tripping to occur, the threshold value must be exceeded without interruption for
at least the period of time specified in this screen (IOP..isolated operation in parallel with other
gensets).

122 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
4.13.4 Generator reverse/reduced power monitoring

Rev./red.power Reverse/reduced power monitoring ON/OFF


monitoring ON
ON .......... Switching reverse/reduced power monitoring on. The subsequent screens of
this option are displayed.
OFF .......... Monitoring is not carried out, and the subsequent screens of this option are
not displayed.

Rev./red.power Reverse/reduced power monitoring threshold value -99..0..+99 %


resp.value -00%
The threshold value refers to the rated power of the generator (see page 84).
Reduced power monitoring .......... Tripping when the real power falls below the (positive)
limit value.
Reverse power monitoring ........... Tripping when the real power falls below the (nega-
tive) limit value.

Tripping of alarm class 3

Rev./red.power Reverse power monitoring delay 0.0..9.9 s


delay 0.0s
In order for tripping to occur, negative deviation from the threshold value must occur with-
out interruption for at least the period of time specified in this screen.

4.13.5 Load imbalance monitoring

The percentage threshold value specifies the permissible deviation of a conductor current
from the arithmetic mean value of all three conductor currents. If generator load imbalance
occurs, the engine is immediately shut down with alarm class 3 and the alarm message
"Load imbalance" is displayed.

Load unbalanced Load imbalance monitoring ON/OFF


monitoring ON
ON .......... Generator load imbalance monitoring is carried out. The subsequent screens
of this option are displayed.
OFF .......... Monitoring is not carried out, and the subsequent screens of this option are
not displayed.

Load unbalanced Maximum permissible load imbalance 0..100 %


max. 000%
Monitoring of the set maximum load imbalance is carried out in reference to the generator
rated current which has been set (see page 84). If the load imbalance value exceeds the
set percentage value due, for example, to asymmetrical generator load, shutoff occurs.

Tripping of alarm class 3

Load unbalanced Load imbalance monitoring delay 0.02..99.98 s


delay 00.00s
In order to trip monitoring, the threshold value must be exceeded without interruption for at
least the period of time specified in this screen.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 123
4.13.6 Generator overcurrent monitoring

If generator overcurrent occurs, the engine is immediately shut down (alarm class 3, and
the alarm message "Overcurrent" is displayed.

I [%]

I >>
(I2)

I>
(I1)

t2 t1 t [s]

Gen.overcurrent Independent time overcurrent monitoring ON/OFF


monitoring ON
ON .......... Generator current monitoring is carried out, and the following screens of this
option are displayed.
OFF .......... Monitoring is not carried out, and the subsequent screens of this option are
not displayed.

Gen.overcurrent Independent time overcurrent, threshold value, limit 1 0..300 %


limit 1 000%
If the value of the generator current exceeds the set percentage value, with reference to the
generator rated current (see page 84), shut-off occurs.

Tripping of alarm class 3

Gen.overcurrent Independent time overcurrent, delay, limit 1 0.02..99.98 s


delay 1 00.00s
In order to trip monitoring, the threshold value must be exceeded without interruption for at
least the period of time specified in this screen.

Gen.overcurrent Independent time overcurrent, threshold value, limit 2 0..300 %


limit 2 000%
If the value of the generator current exceeds the set percentage value, with reference to the
generator rated current (see page 84), shut-off occurs.

Tripping of alarm class 3

Gen.overcurrent Independent time overcurrent, delay, limit 2 0.02..99.98 s


delay 2 00.00s
In order to trip monitoring, the threshold value must be exceeded without interruption for at
least the period of time specified in this screen.

124 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
4.13.7 Generator frequency monitoring

Function "Generator frequency not within the permissible range"


The generator frequency lies outside of the limit values set for overfrequency and underfre-
quency. The engine is immediately shut down (alarm class 3), and the malfunction message
"Gen.overfreq" or "Gen.underfreq" appears. The activation of generator underfrequency
monitoring is delayed via "Delayed engine monitoring" in order to enable correct generator
start-up.

Gen.frequency- Generator frequency monitoring ON/OFF


monitoring ON
ON .......... Generator frequency monitoring is carried out. The subsequent screens of this
option are displayed.
OFF .......... Monitoring is not carried out, and the subsequent screens of this option are
not displayed.

Gen.overfreq. Generator overfrequency threshold value 50.0..140.0 %


f> 000.0Hz
This value refers to the parameter “Rated frequency in system”. The overfrequency value
which is to be monitored is set in this screen. The overfrequency value which is to be moni-
tored is set in this screen.

Tripping of alarm class 3

Gen.overfreq. Generator overfrequency delay 0.02..9.98 s


delay 0.00s
In order to trip monitoring, the threshold value must be exceeded without interruption for at
least the period of time specified in this screen.

Gen.underfreq. Generator underfrequency threshold value 50.0..140.0 %


f< 000.0Hz
This value refers to the parameter “Rated frequency in system”. The underfrequency value
which is to be monitored is set in this screen. If the value is reached or fallen below, the
item outputs a message and opens the generator power circuit breaker.

Tripping of alarm class 3

Gen.underfreq. Generator underfrequency delay 0.02..9.98 s


delay 0.00s
In order for tripping to occur, negative deviation from the threshold value must occur with-
out interruption for at least the period of time specified in this screen.

a.) Engine overspeed monitoring

Engine overspeed Engine overspeed monitoring 0..9,999 rpm


> 0000 rpm
Overspeed monitoring is independently carried out by the Pickup in addition to generator
frequency monitoring. If the Pickup input is switched off, this monitoring is also de-
activated. The alarm message "overspeed" is output.

Tripping of alarm class 3

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 125
4.13.8 Generator voltage monitoring

The line-to-line voltage is monitored in each case.

Function "Generator voltage not within the permissible range"


At least one phase of the generator voltage lies outside of the limit values set for overvolt-
age or undervoltage. The engine is immediately shut down (alarm class 3), the malfunction
message "Gen.overvolt." or "Gen.undervolt." appears. The activation of generator under-
voltage monitoring is delayed via "Delayed engine monitoring" in order to enable correct
generator start-up.

Gen.voltage Generator voltage monitoring ON/OFF


monitoring ON
ON .......... Generator voltage monitoring is carried out. The subsequent screens of this
option are displayed.
OFF .......... Monitoring is not carried out, and the subsequent screens of this option are
not displayed.

Gen.overvoltage Generator overvoltage threshold value 20.0..150.0 %


U> 000.0%
This value refers to the parameter “Rated voltage in system”. The overvoltage value which
is to be monitored is set in this screen. If the value is reached or exceeded, the item out-
puts a message and opens the generator power circuit breaker.

Tripping of alarm class 3

Gen.overvoltage Generator overvoltage delay 0.02..9.98 s


delay 0.00s
In order to trip monitoring, the threshold value must be exceeded without interruption for at
least the period of time specified in this screen.

Gen.undervoltage Generator undervoltage threshold value 20.0..150.0 %


U< 000,0%
This value refers to the parameter “Rated voltage in system”. The undervoltage value which
is to be monitored is set in this screen. If the value is reached or fallen below, the item
outputs a message and opens the generator power circuit breaker.

Tripping of alarm class 3

Gen.undervoltage Generator undervoltage delay 0.02..9.98 s


delay 0.00s
In order for tripping to occur, negative deviation from the threshold value must occur with-
out interruption for at least the period of time specified in this screen.

126 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
4.13.9 AMF (emergency power) limits [PCL1]

The following limits are used to determine a AMF (automatic mains failure/emergency
power case). Following this limits it is calculated if the mains is available or not. If one level
for f or U is reached (higher or lower) a message is displayed. Relay manager parameter
number 5 is calculated out of this values, too.

Mains overfreq. Limit for mains overfrequency 80.0..140.0 %


f> 000.0%
This value refers to the parameter “Rated voltage in system”. The limit value to be moni-
tored for overfrequency is entered here.

Mains underfreq. Limit for mains underfrequency 80.0..140.0 %


f< 000.0%
This value refers to the parameter “Rated voltage in system”. The limit value to be moni-
tored for underfrequency is entered here.

Mains overvolt. Limit for mains overvoltage 20.0..150.0 %


U> 000.0%
This value refers to the parameter “Rated voltage in system”. The limit value to be moni-
tored for overvoltage is entered here.

Mains undervolt. Limit for mains undervoltage 20.0..150.0 %


U< 000.0%
This value refers to the parameter “Rated voltage in system”. The limit value to be moni-
tored for undervoltage is entered here.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 127
4.13.10 Mains frequency monitoring [PCM1x]

Monitoring the mains frequency is absolutely vital if a generator is operated within a public
network. In the event of mains failure (e. g. short interruption) the generator which is operat-
ing in parallel with the mains must be automatically disconnected from the mains. Decoup-
ling from the mains is only activated when both power circuit breakers (mains and genera-
tor power circuit breaker) are closed.

The here fixed limit values are used for assessment of the emergency power operation in
case that the following protective items are switched to "ON". On the basis of the here
fixed limit values it is defined whether mains is present or not. The tripping times will not be
noticed.

Function "Mains frequency not within the permissible range"


The mains frequency lies outside of the limit values set for overfrequency or underfrequency.
The power circuit breaker, which is to carry out decoupling from the mains, is immediately
opened. The prerequisite of mains frequency monitoring is operation in parallel with the
mains (both power circuit breakers closed). The malfunction message "Mains overfreq." or
"Mains underfreq" appears. Output via an alarm relay is always possible.

Mains frequency Mains frequency monitoring ON/OFF


monitoring ON
ON .......... Mains frequency monitoring is carried out. The subsequent screens of this op-
tion are displayed.
OFF .......... Monitoring is not carried out, and the subsequent screens of this option are
not displayed.

Mains overfreq. Mains overfrequency threshold value 80.0..140.0 %


f> 000.0%
This value refers to the parameter “Rated voltage in system”. The overfrequency value
which is to be monitored is set in this screen. If the value is reached or exceeded, the item
outputs a message and opens the generator or the mains power circuit breaker regardless
of the nature of decoupling from the mains.

Tripping of alarm class 0

Mains overfreq. Mains overfrequency delay 0.02..9.98 s


delay 0.00s
In order to trip monitoring, the threshold value must be exceeded without interruption for at
least the period of time specified in this screen.

Mains underfreq. Mains underfrequency threshold value 80.0..140.0 %


f< 000.0%
This value refers to the parameter “Rated voltage in system”. The underfrequency value
which is to be monitored is set in this screen. If the value is reached or fallen below, the
item outputs a message and opens the generator or the mains power circuit breaker re-
gardless of the nature of decoupling from the mains.

Tripping of alarm class 0

Mains underfreq. Mains underfrequency delay 0.02..9.98 s


delay 0.00s
In order for tripping to occur, negative deviation from the threshold value must occur with-
out interruption for at least the period of time specified in this screen.

128 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
4.13.11 Mains voltage monitoring [PCM1x]

Monitoring the mains voltage is absolutely vital if a generator is operated within a public
network. In the event of mains failure (e. g. short interruption) the generator which is operat-
ing in parallel with the mains must be automatically disconnected from the mains.

The line-to-line voltage is monitored in each case.

The here fixed limit values are used for assessment of the emergency power operation in
case that the following protective items are switched to "ON". On the basis of the here
fixed limit values it is defined whether mains is present or not. The tripping times will not be
noticed.

Function "Mains voltage not within the permissible range"


At least one phase of the mains voltage lies outside of the limit values set for overvoltage or
undervoltage. The power circuit breaker, which is to carry out decoupling from the mains,
is immediately opened. The prerequisite of mains voltage monitoring is operation in parallel
with the mains (both power circuit breakers closed). The malfunction message "Mains over-
freq." or. "Mains underfreq. appears" Output via an alarm relay is always possible.

Mains voltage Mains voltage monitoring ON/OFF


monitoring ON
ON .......... Mains voltage monitoring is carried out. The subsequent screens of this option
are displayed.
OFF .......... Monitoring is not carried out, and the subsequent screens of this option are
not displayed.

Mains overvolt. Mains overvoltage threshold value 20.0..150.0 %


U> 000.0%
This value refers to the parameter “Rated voltage in system”. The overvoltage value which
is to be monitored is set in this screen. If the value is reached or exceeded, the item out-
puts a message and opens the generator or the mains power circuit breaker regardless of
the nature of decoupling from the mains.

Tripping of alarm class 0

Mains overvolt. Mains overvoltage delay 0.02..9.98 s


delay 0.00s
In order to trip monitoring, the threshold value must be exceeded without interruption for at
least the period of time specified in this screen.

Mains undervolt. Mains undervoltage threshold value 20.0..150.0 %


U< 000.0%
This value refers to the parameter “Rated voltage in system”. The undervoltage value which
is to be monitored is set in this screen. If the value is reached or fallen below, the item
outputs a message and opens the generator or the mains power circuit breaker regardless
of the nature of decoupling from the mains.

Tripping of alarm class 0

Mains undervolt. Mains undervoltage delay 0.02..9.98 s


delay 0.00s
In order for tripping to occur, negative deviation from the threshold value must occur with-
out interruption for at least the period of time specified in this screen.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 129
4.13.12 Phase/vector shift monitoring [PCM1x]

Function A phase/vector shift is a sudden change in the voltage curve, and may be caused by a
major generator load change. In this case, the measuring circuit detects a change in the
cycle duration once. This change in the cycle duration is compared with a calculated mean
value from previous measurements. Monitoring encompasses all three phases. The threshold
value in degrees specifies the difference in time between the mean and the current value in
reference to a full cycle. Monitoring can be set in various manners. The phase/vector shift
watchdog may be used as an additional facility for decoupling from the mains.

Phase shift Phase/vector shift monitoring ON/OFF


monitoring ON
ON .......... Mains frequency monitoring is carried out, and any phase/vector shift within
the defined range is registered. The subsequent screens of this option are dis-
played.
OFF .......... Monitoring is not carried out, and the subsequent screens of this option are
not displayed.

Monitoring Phase/vector shift monitoring one-/threephase..threephase


------------------------------
one-/threephase .....During single-phase voltage phase/vector shift monitoring, tripping
occurs if the phase/vector shift exceeds the specified threshold value
in at least one of the three phases. Note: If a phase/vector shift oc-
curs in one or two phases, the single-phase threshold value is taken
into consideration; if a phase/vector shift occurs in all three phases,
the three-phase threshold value is taken into consideration. His type
of monitoring is very sensitive, and may lead to false tripping if the
selected phase angle settings are too small.
threephase ............During three-phase voltage phase/vector shift monitoring, tripping
occurs only if the phase/vector shift exceeds the specified threshold
value in all three phases within 2 cycles.

Tripping of alarm class 0

NOTE

If monitoring is set to "threephase", only the bottom of the two following screens is visible; if monitoring is
set to "one-/threephase", both configuration screens are visible.

Phase shift Maximum phase difference 3..30 °


one-phase 00°
Tripping occurs if the electrical angle of the voltage curve shifts by more than the specified
This mask is only visible if angle. In this case, tripping depends on the type of monitoring which has been set:
monitoring is set to
"one-/threephase".

Phase shift Maximum phase difference 3..30 °


three-phase 00°
Tripping occurs if the electrical angle of the voltage curve shifts by more than the specified
angle. In this case, tripping depends on the type of monitoring which has been set

130 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
4.14 Mains settling time

Mains settling Mains settling time 0..999 s


time 000s
In order to disable the reverse synchronization of the generator to the mains for a certain
time, the delay time for which the generator is to remain in idle or isolated (parallel) opera-
tion can be configured with this parameter. The following applies in the case of generators
with 1-power circuit breaker, which are to be operated in parallel with the mains: If the
mains fails for the duration of the mains settling time, the engine is stopped. If the mains is
available for at least 5 seconds without any interruption, the engine is started.

Note
If both circuit breakers (PCM1-M und PCL1) are open, the mains settling time is reduced to
2 seconds when the mains return, for the case that this is configured longer.

4.14.1 Battery voltage monitoring

Batt.undervolt. Threshold value 9.5..30.0 V


U< 00,0V
Battery undervoltage threshold value. Continuous negative deviation from the set limit value
for at least x seconds (see next screen) leads to the output of the alarm message "Batt. un-
dervolt." in the LC display and to the output of the centralized alarm.

Tripping of alarm class 1

Batt.undervolt. Battery undervoltage delay 0..99 s


delay 00s
In order for tripping to occur, negative deviation from the threshold value must occur with-
out interruption for at least the period of time specified in this screen.

Note: Regardless of the set battery voltage watchdog, readiness for operation is with-
drawn and the message "Battery undervolt." is output if
• the supply voltage falls below 17.7 V or if
• the supply voltage falls below 11 V during the start procedure.

4.14.2 Time of active horn

Horn self reset Horn acknowledgment after 1..9,999 s


0000s
If the horn (centralized alarm) has been active for this time it will be deactivated (acknowl-
edged) automatically.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 131
4.15 Discrete input configuration

Configure Configuration of discrete inputs YES/NO


dig.inputs YES
Various groups of parameters are placed together in blocks to allow you to navigate
through the large number of configuration screens more rapidly. Selecting "YES" or "NO"
has no effect on whether or not control or monitoring etc., is carried out. The input merely
has the following effects:
YES .......... The configuration screens in the next block are displayed and can either be
viewed ("STATUS / ALARM" push-button) or modifications can be made to the
parameters ("PARAMETER", "U SELECT" or "STATUS / ALARM" or "Select" push-
button). A decision is not made on whether the parameters are processed or
not.
NO .......... The parameters in the next block are not displayed, cannot be modified and
are therefore skipped.

NOTE

The discrete inputs can be used as alarm inputs and alternatively as control inputs. If they were configured
as alarm inputs (parameter is "OFF") the masks in chapter 4.15.1 Setting the alarm inputs

Setting the alarm inputs" at page 132 are valid. If they were configured as control inputs the masks in
chapter "Setting the control inputs " at page 135 are valid. The choice whether a discrete input is an
alarm or a control input occurs directly after the input of the alarm text of the according discrete input.

4.15.1 Setting the alarm inputs

Discrete input 1 2 3 4 5 6 7 8 9 1 1 1 1 14 15 16
0 1 2 3
Name 1 2 3 4 5 6 7 8 9 A B C D E F G
Terminal 61 62 63 64 65 66 67 68 69 70 71 72 73 12 12 12
5 6 7
PCL1 " " " " " " " " " " " " " " - -
PCM1 " " " " " " " " " " " " " " " "
Function Alarm or control input (depends on configuration)

NOTE

NO (operation current) The relay picks up after tripping, i. e., in the operative state, current flows through the
coil.
! There will be no change in the state of the relay in the event of a power outage and
the relay will not trip. In this case, the relay's readiness for operation should be moni-
tored.

NC (idle current) ...... The relay drops out after tripping, i. e., in the idle state, current flows through the coil.
The relay is pulled in the idle state (= no tripping).
! There will be no change in the state of the relay in the event of a power outage and
the relay will trip.

24 V 24 V
Operating current Idle-current
contact contact
RELEASE RELEASE
Idle-current Operating current
contact contact
no current flow
current flow

RELEASE RELEASE
Relay operates Relay releases

0V 0V

132 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
Example Discrete inputs 1 through 4 (same procedure for inputs 5-16)

Dig.input 1234 Discrete alarm input, function E/D


function EEEE
The alarm inputs can be triggered via whether an operating current (NO) or an idle cur-
rent (NC) contact. The idle current input enables an open circuit to be monitored. Either a
positive or a negative voltage difference may be applied. Terminals 34 (input 1), 35 (in-
put 2), 36 (input 3) and 61 (input 4) are assigned.
E ............. Enable to operate (NO) The discrete alarm input is triggered via the applica-
tion of a voltage difference.
D ............ Disable to operate (NC) The discrete alarm input is triggered by the drop-off
of a voltage difference.

Dig.input 1234 Discrete alarm input, delay 0..9 s


delay 0000
A delay can be assigned to each alarm input. The delay is input in the form of delay
stages. The individual stages are listed below. The input must be present, without interrup-
tion, throughout the delay time in order for tripping to occur.

Delay stage Delay stage


0 100 ms
1 200 ms
2 500 ms
3 1s
4 2s
5 5s
6 10 s
7 20 s
8 50 s
9 100 s

Delayed by 1234 Discrete alarm input, delayed by firing speed Y/N


eng.speed YYYY
For the alarm inputs the question of whether the input is only to be monitored when the en-
gine is rotating ("firing speed reached") is specified here.
Y .............. After engine monitoring has been activated (the green "Monitoring" LED illumi-
nates), the discrete input is evaluated.
N ............. The discrete input is always evaluated.
Dig.input 1234 Discrete alarm input, alarm class 0..3
error class 3000
Different alarm classes are assigned to discrete alarm inputs 1 to 4. The alarm classes are
listed following.

The monitoring functions are divided into four alarm classes:

F0 Warning alarm This alarm does not lead to an interruption of the operation. An alarm message is dis-
played without a centralized alarm.
! Alarm text.
F1 Warning alarm This alarm does not lead to an interruption of the operation. A centralized alarm will be
output.
! Alarm text + flashing "alarm" LED + group alarm relay (horn).
F2 Triggering alarms This alarm leads to the shutdown of the engine. First the real power is reduced before the
GCB is opened. A coasting is carried out.
! Alarm text + flashing "alarm" LED + group alarm relay (horn) + coasting.
F3 Triggering alarm This alarm leads to the immediate opening of the GCB and to the shutdown of the engine.
! Alarm text + flashing "alarm" LED + group alarm relay (horn) + shutdown.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 133
4.15.2 Setting of the texts of the alarm inputs

a.) Texts of the discrete inputs in the PCx

NOTE

If terminal 6 is allocated as "Sprinkler operation" function (see chapter 4.15.4 on page 136) or if a gas
engine is selected (see chapter 4.18.2 Engine type definition on page 145

Engine configuration" on page 144), the EMERGENCY OFF function must always be assigned to
terminal 61.

NOTE

If the device is equipped with a 2. interface (via Y1-Y5), the alarm texts can only be configured using the
PC program.

Example Alarm text terminal 61

Errortxt.term.61 Setting the alarm texts


EMERGENCY OFF
These screens are used to input the alarm texts (in this example for terminal 61 the alarm
text "EMERGENCY OFF"). The EMERGENCY OFF function should generally be assigned
to terminal 61.

NOTE

Certain special characters, numbers, high case and low case letters may be set.

b.) Texts of the discrete inputs of the EM1-D


The discrete inputs of the EM1-D can be configured only by using the PC program. The pa-
rameter of the EM1-D are listed at the end in the configuration file of the PCx. Please note
that you have to put on additional adjustments directly at the EM1-D. Please use the sepa-
rate configuration file for the EM1-D.

Alarm text DIx EM1-Dy Settings of the alarm texts of EM1-D.y


(terminal z)
The discrete input x (terminal y) on the EM1-D.z displays the here adjusted text on the LCD
[x = 1..8] / [y = 1/2] / [z = 5..12]
of the PCx.

Example Discrete input 5 on the EM1-D.1

Alarm text DI5 EM1-D Settings of the alarm texts of EM1-D.1


(terminal 9)
The discrete input 5 (terminal 9) on the EM1-D.1 displays the here adjusted text on the
LCD of the PCx.

134 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
4.15.3 Setting the control inputs

Firing speed by Firing speed reached via terminal 62 ON/OFF


Term. 62 ON
OFF .......... The discrete input terminal 62 is used as a normal alarm input.
ON .......... The logic to be set applies to the starting procedure:
If the input is set to operating current (NO), the starter is dis-engaged when a
signal is applied. After the termination of the delayed engine monitoring, the
"operating current" is still programmed, however, internally, the device
switches over to the "closed-circuit current" logic (NO), in order to enable the
generation of an alarm tripping in the event of a voltage loss (including set
time lag). The same principle, inverted, also applies to the closed-circuit cur-
rent (NC) tripping. The discrete input is programmed for closed-circuit current
(NC), to dis-engage the starter in the event of a voltage loss. After the delayed
engine monitoring, the discrete input is internally set to operating current (NO)
and is therefore tripped as soon as voltage is applied. The here adjusted
logic applies for the start operation.

Op.mode blocked Disabling the change of the mode using the front folio ON/OFF
by Ter.63 ON
ON .......... Terminal 63 is used as control input. If terminal 63 applies to a high level, the
operation mode can no longer be changed using the front folio push-buttons.
OFF .......... This terminal is evaluated as alarm input.

Breaker logic CB logic via terminal 64 ON/OFF


by Term64 ON
ON .......... This terminal is used as control input.
• High level If this terminal applies to a high level, the power circuit
breaker logic configured using the next mask will be acti-
vated.
• Low level If this terminal applies to a low level, the power circuit
breaker logic configured in this item will be activated (see
chapter 4.11.6 "Power circuit breaker logic" at page 110).
OFF .......... Terminal 64 is evaluated as alarm input.

Breaker logic: CB logic via discrete input see page 110


EXTERNAL
In this mask the CB logic is selected which is activated using terminal 64. This parameter
Only visuable if CB logic via ter- is only visible if parameter „Breaker logic“ has been configured to ON (for the description
minal 64 is set to "ON". of the breaker logic note chapter "Breaker logic").

Manual synchr. Manual synchronization via terminal 66 ON/OFF


by Ter.66 ON
ON .......... Terminal 66 would be used as control input:
- breaker and synchronization time monitoring is disabled
- no control output or control to base position is disabled
OFF .......... Terminal 66 would be used as alarm input.

Close GLS asap Close GCB prior to delayed engine protection via term. 67 ON/OFF
by Ter.67 ON
ON .......... Terminal 67 would be used as control input: Closing of the GCB would be
enabled prior to completion of the delayed engine monitoring and after reach-
ing the window of the possible range for generator voltage and frequency.
AUS ......... Terminal 67 would be used as alarm input.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 135
4.15.4 Adjust function of terminal 6

ATTENTION!

The various functions of terminal 6 are active at different signal levels!

Function term.6 Function of terminal 6


Sprinklermode
This screen is used to assign a function to the discrete control input terminal 6. A selection
may be made from among the following functions:
• Sprinkler operation,
• Engine enabling,
• External acknowledgment,
• STOP mode,
• Engine blocked or
• Start without CB.

• Sprinkler By resetting terminal 6 (setting a low level) sprinkler operation is activated in accordance with the
functional description. This is terminated by setting terminal 6 (application of a High signal). Attention:
Negative functional logic! (for the function of the sprinkler operation, please also observe Chap-
ter 2.11 "Sprinkler operation" on page 53.)

• Engine enable Terminal 6 in this case has the same function as the STOP push-button: Resetting terminal 6 (applica-
tion of a LOW signal) prevents the engine's starting, and stops the engine if this is already running; the
application of a HIGH signal enables the starting of the engine; the application of a high signal en-
ables the engine for startup. Caution: Via this function, emergency power operation is also prevented
or aborted. Emergency power is not possible without this enable signal! The engine enable function is
only possible in "AUTOMATIC" operating mode.

• Ext. acknowledge In "STOP" and "AUTOMATIC" modes alarms can be acknowledged externally by setting terminal 6
(Change of slope from a LOW to a HIGH signal). In order to achieve further acknowledgement, ter-
minal 6 must accordingly first be reset and then set again. If a continuous HIGH signal is present at
terminal 6, this has no effect on the acknowledgement and suppression of alarm messages.

• ΣΤΟΠ mode By setting terminal 6 (application of a HIGH signal) the STOP mode is chosen. If you remove this
signal the mode will change into the mode which was activated before terminal 6 was set.

• Engine stop By setting terminal 6 (application of a HIGH signal) a start of the engine can be prevented. If the
engine is running because emergency current is present, it is stopped by setting this discrete input. The
discrete input is not inverted. The engine block function is only possible in "AUTOMATIC" operating
mode.

• No CB by start If the terminal 6 is set, the engine starts; no synchronization is carried out and the generator power
circuit breaker is not engaged (no switching to black busbar). The GCB is then inserted only if emer-
gency current is present. After return of the mains, there is a switchover to the mains according to the
set CB logic. The start of terminal 6 is of a higher value than the start via terminals 3/5. If terminal 6
was selected, terminals 3/5 are ignored. If the genset is in mains parallel mode with power circuit
breaker logic "Parallel" and if terminal 6 is activated, the GCB is opened after a reduction in power.
The genset continues to operate without load with the GCB open.

136 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
Start withno GCB Costing if starting without CB ON/OFF
cool down ON
ON .......... After removing the start request, a coasting is carried out for the time period
Only if terminal 6 was configured set in the "coasting" screen.
to "start without CB". OFF .......... After removing the start request, no coasting is carried out and the engine is
stopped immediately.

Sprinkler shutd. Sprinkler alarm classes only active if terminal 6 is active ON/OFF
F1 aktive ON
ON .......... If terminal 6 "sprinkler operation" is configured, the primary alarm classes will
be active after sprinkler demand has been finished (setting terminal 6).
OFF .......... If terminal 6 is configured as "sprinkler operation", the primary alarm classes
will be again active after sprinkler coasting has been finished (setting termi-
nal 6 and sprinkler coasting 10 minutes).

4.16 Analog inputs configuration

Analog input 1 2 3 4 5 6 7
Type Pt100 Pt100 0/4..20m Pt100 Pt100 Pt100 0/4..20m
A A
Terminals 93-95 96-98 99-101 102-104 105-107 108-110 111-113
PCL1 " " " " - - -
PCM1/L " " " " - - -
PCM1/H " "* " " " " "

*This analog input is also used for the temperature dependent start/stop and the temeperature dependent power
reduction.

Configure Configuration of analog inputs YES/NO


analg.inp. YES
Various groups of parameters are placed together in blocks to allow you to navigate
through the large number of configuration screens more rapidly. Selecting "YES" or "NO"
has no effect on whether or not control or monitoring etc., is carried out. The input merely
has the following effects:
YES .......... The configuration screens in the next block are displayed and can either be
viewed ("STATUS / ALARM" push-button) or modifications can be made to the
parameters ("PARAMETER", "U SELECT" or "STATUS /ALARM" or "Select" push-
button). A decision is not made on whether the parameters are processed or
not.
NO .......... The parameters in the next block are not displayed, cannot be modified and
are therefore skipped.

NOTE

If you want to visualize the analog inputs via the PC programm FL-SOFT3 starting with Firmware 3.1.xxx of PCx
please note the following:
1. Establish a connection between FL-SOFT3 and PCx.
2. Select in the menu "Devices" the topic "Refresh Configuration".
3. Restart FL-SOFT3 according to the requests.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 137
4.16.1 Setting the analog inputs

a.) Pt100 input


The temperature input Pt100 is designed for temperatures up to 240 °C. A name may be
assigned to each Pt100 input. Each input is displayed with its name, and can be moni-
tored in two stages. The first stage triggers alarm class 1, the second stage triggers alarm
class 3.

Example Temperature 4:

Temperature 4 Activation/de-activation of Pt100 input ON/OFF


Pt1OO ON
ON .......... The temperature value of this input is displayed, temperature monitoring is ac-
tivated. The subsequent screens of this option are displayed.
OFF .......... No display or monitoring are carried out, and the subsequent screens of this
option are not displayed.

***name**** Assignment of a name to the analog input Characters [any]


000°C
An arbitrary name with a maximum of 11 characters is assigned to temperature 4. In the
event of an alarm, the name and the trigger temperature are faded in, whereby an excla-
mation mark is blended in before the temperature.

Limit Warning limit value 0..200 °C


warning 000°C
The limit value at which a warning occurs is configured here.

Tripping of alarm class 1

Limit Shutdown limit value 0..200 °C


shutdown 000°C
The limit value at which shutdown occurs is configured here.

Tripping of alarm class 3

Delay Delay time for warning and shutdown 0..650 s


limit 1/2 000s
In order for tripping to occur, the limit value must be exceeded or fallen below without in-
terruption for at least the period of time specified in this screen. If the actual value falls be-
low or exceeds the threshold value within this period of time, the delay time is restarted
(this delay time applies to both limit values).

Monitoring for Monitoring for ... high limit mon./low limit mon.
high limit mon.
Temperature input 4 is monitored in different manners:
high limit mon. ............The set value must be exceeded;
low limit mon. .............The set value must fall below.

NOTE

If temperature limit value monitoring is not required, a limit value which is higher than the expected
temperature must be set in the corresponding screen (e. g. for the ambient temperature: 100 °C).

138 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
b.) Scaleable analog input 0/4..20 mA

NOTE

The scalable analog inputs 0/4-20 mA can be configured alternatively for the following functions:
• Mains interchange (import/export) real power actual value, or
• real power setpoint value.
If one of the both functions is assigned to an available 0/4-20 mA input T{x}, the corresponding analog
input T{x} has to be configured to OFF. The analog input can no longer be used as an alarm input.

Priority of the functions of the analog inputs


The following priority is valid if more than one function has been assigned to a analog input:
• Highest priority: Mains interchange (import/export) real power actual value measurement
• Middle priority: Real power setpoint value
• Lowest priority: Measuring input as common analog value

Example Scaleable analog input 7:

Analog input 7 Scaleable analog input ON/OFF


scalable ON
ON .......... The display of this input appears, monitoring is activated. The subsequent
screens of this option are displayed.
OFF .......... No display or monitoring are carried out, and the subsequent screens of this
option are not displayed.

Name and unit Assignment of a name to the analog input any


°°°°°°°°°°°°°°°°°°°°°°°°°°°°
The input may be assigned with an arbitrary name in this screen. A maximum of four zeros
may be used to reserve places for the numerical measuring values. In this case, the place-
holders may be divided by any characters, e. g. comma. The measuring values subse-
quently appear wherever the zeros are placed.

Analog input 7 Measuring range of the analog input 0-20 mA/4-20mA


0-00mA
The measuring range 0..20 mA or 4..20 mA is selected in this screen. If, in the case of
the 4..20 mA setting, a current of less than 2 mA is measured, this is evaluated as a wire
break (see below).

Value at Smallest input value of the analog input -9,999..0..9,999


O% -0000
The scaleable analog input is assigned a numerical value which corresponds to the small-
est input value ! Definition of the lower value (0 %, e. g. 0 kW, 0 V) with minimum ana-
log input value (0 mA or 4 mA).

Value at Largest input value of the analog input -9,999..0..9,999


100% -0000
The scaleable analog input is assigned a numerical value which corresponds to the largest
input value ! Definition of the upper value (100 %, e. g. 500 kW, 400 V) with maximum
analog input value (20 mA).

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 139
Limit warning Warning limit value -9,999..0..9,999
value -0000
The limit value at which a warning occurs is configured here.

Tripping of alarm class 1

Limit shutdown Shutdown limit value -9,999..0..9,999


value -0000
The limit value at which shutdown occurs is configured here.

Tripping of alarm class 3

Delay Delay time for warning and shutdown limit values 0..650 s
limit 1/2 000s
In order for tripping to occur, the limit value must be exceeded or fallen below without in-
terruption for at least the period of time specified in this screen. If the actual value falls be-
low or exceeds the threshold value within this period of time, the delay time is restarted
(this delay time applies to both limit values).

Monitoring for Monitoring for ... high limit mon./low limit mon.
high limit mon.
Temperature input 7 is monitored in different manners:
high limit mon. ............The set value must be exceeded;
low limit mon. .............The set value must fall below.

NOTE

If a temperature limit monitoring is not required, a threshold value which is higher than the expected
temperature has to be configured to the corresponding parameter (e. g. for the ambient temperature: 100 °C).

4.16.2 Measuring range monitoring

Measuring range monitoring


Ana.input !----
This message appears when positive or negative deviation from the measuring range oc-
curs. Tripping occurs depending on the values specified below.

NOTE

If positive measuring range deviation (wire break) has been determined and tripping has occurred, limit
value monitoring for this analog input is deactivated.
Measuring range monitoring, tripping at:
4..20 mA 2 mA (negative deviation)
Pt100 216 °C (positive deviation)

140 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
4.16.3 Analog input delay using the delayed engine speed

Ana.in 12345678 Analog inputs, engine delayed monitoring Y/N


Sv.del. NNNNNNNN
The analog inputs may be disabled until the engine has reached rated speed (“firing
[PCMx/H] speed reached”). This parameter specifies which analog inputs are to be constantly en-
abled and temporarily disabled by configuring a “Y” or an “N” below the input number.
Ana.in 1234
Y .............. Once the firing speed has been reached monitoring of the analog input is en-
Sv.del. NNNN
abled (the green LED “Protection” illuminates).
[PCLx/PCMx/L] N ............. The analog input is monitored always.

NOTE

Above screen (8 inputs) appears if at least 5 analog inputs are equipped. If less than 5 inputs are equipped, a
screen with 4 inputs appears. If less inputs are equipped than inputs appear in the screen, only the entries for
the equipped inputs are valid.

4.16.4 Analog inputs selectable as control inputs

Ana.in 12345678 Analog input as control input Y/N


control NNNNNNNN
This parameter defines for each analog whether it operates as control input or not.
[PCMx/H] Y .............. The analog input operates as control input. The analog value is displayed and
the configured relays are energized when reaching the configured limits.
Ana.in 1234
However, no alarm is issued. No guidance bus output is performed as well.
control NNNN
(The setting has no effect on the behavior in case a wire breaks).
[PCLx/PCMx/L] N ............. The analog input operates as described for the above settings.

NOTE

Above screen (8 inputs) appears if at least 5 analog inputs are equipped. If less than 5 inputs are equipped, a
screen with 4 inputs appears. If less inputs are equipped than inputs appear in the screen, only the entries for
the equipped inputs are valid.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 141
4.17 Configure outputs

Configure Configuration of the outputs YES/NO


outputs YES
Various groups of parameters are placed together in blocks to allow you to navigate
through the large number of configuration screens more rapidly. Selecting "YES" or "NO"
has no effect on whether or not control or monitoring etc., is carried out. The input merely
has the following effects:
YES .......... The configuration screens in the next block are displayed and can either be
viewed ("Select" push-button) or modifications can be made to the parameters
("Cursor→","Digit↑" or "Select" push-button). A decision is not made on
whether the parameters are processed or not.
NO .......... The parameters in the next block are not displayed, cannot be modified and
are therefore skipped.

4.17.1 Analog outputs

The analog output manager can be used to apply a very specific measurement variable to
the available analog outputs. Output may be carried out as a 0-20 mA or as a 4-20 mA
value. A list of the possible parameters is contained in the appendix. A separate number is
assigned to each variable. The variable may be scaled via an upper and a lower input
value. The inputs may also be assigned with prefixes (for further details, see "Analog output
manager" in the appendix).

NOTE

The list of values and setting limits for the analog output manager is contained in chapter 6.1 "Analog
output manager" starting on page 160.

Example Analog output 120/121:

Analg.out.12O121 Parameter for analog output 0..22


parameter 00
The number of the desired measurement variable output is entered here. A list of all select-
able parameters, together with output and limit value ranges, is contained in the appen-
dix.

Analg.out.12O121 Analog output range 0-20/4-20 mA


0-00mA
The outputs 0-20 mA or 4-20 mA may be selected.

Analg.out.12O121 Scaling the lower output value 0..9,990


O% 0000
The setting range for inputting the 0 % value is contained in the appendix. If the generator
actual real power is to be displayed with an decimal point the input has to occur as fol-
lows: for example "10.0 kW" # "100".

Analg.out.12O121 Scaling the upper output value 0..9,990


1OO% 0000
The setting range for inputting the 100 % value is contained in the appendix. If the genera-
tor actual real power is to be displayed with an decimal point the input has to occur as fol-
lows: for example "10.0 kW" # "100".

142 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
4.17.2 Relay manager

The relay manager enables the assignment of an arbitrary combination of functions to each
relay of the relay manager (PCL1: terminals 33-38 and 47..48; PCM1: 33..38, 47..48,
74..83). In order to achieve this, each function which is possible in the item has its own
number. A text, which describes a logical condition for this relay's picking up, must now be
entered in the configuration menu for each relay. Up to three numbers may be involved in
this link. The length of the text must not exceed 16 characters. The item detects incorrect
function numbers or incorrect formula constructions, and does not accept these.

NOTE

The list of functions and numbers for the relay manager is contained in chapter 6.2 "Relay manager (list of
parameters with explanations)" starting on page 162.

Permissible letters for such texts and their meaning include:


+ ................. OR operator (logical function)
$ ................ and-Operator (logical function)
-................... EMERGENCY operator (logical function)
1, 2, 3, ... .... Function numbers
+/$............. the following applies "$" before "+"

Example Relay picks up if function 22 is applied. ⇒ 22


of logical conditions and Relay picks up if function 22 is not applied. ⇒ - 22
relevant texts Relay picks up if both function 2 and function 27 are applied. ⇒ 2 $ 27
Relay picks up if function 2 or function 27 is applied. ⇒ 2 + 27
Relay picks up if function 5 or function 3 or function 13 is not applied. ⇒ 3 + -5 + 13
Relay picks up if function 4 or 7 or 11 is applied. ⇒ 4 + 7 + 11
Relay picks up if function 4 and function 7 and function 11 are not applied. ⇒ - 4 $ -7 $ -11
Relay picks up if function 4 and 7 and 11 are applied. ⇒ 4 $ 7 $ 11
Relay picks up if function 7 and 11 are simultaneously applied or function 4 is ⇒ 4 + 7 $ 11
applied.
Relay picks up if function 4 or function 7 or function 11 is not applied. ⇒ -4 + -7 + -11

NOTE

The input line is deleted via the input of an illogical parameter.

4.17.3 Relay outputs programming in the PCx

Example Relay 2

Assignm.relay 2 Programming relay outputs see parameter list


3+-8+13
Relay 2 picks up if the logical condition in the second line is met.
Example: 3 + -8 + 13 (OR link)
3 ..... Alarm class 3 has occurred
-8..... "MANUAL" operating mode has not been selected
13 ... "Generator underspeed" alarm is present

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 143
4.17.4 Relay outputs programming in the EM1-D

The relay outputs of the EM1-D can be programmed only by using the PC program FL-
SOFT3. The parameter of the EM1-D are listed at the end in the configuration file of the
PCx. Please note, that you have to make additional adjustments directly at the EM1-D.
Please use the separate configuration file for the EM1-D.

Assignm. x. Relais Programming the relay outputs on the EM1-D.y see parameter list
on EM1-Dy
The relay x on EM1-D.y picks up if the programmed logic condition is fulfilled.
[x = 1..8] / [y = 1/2]

Example Relay 2 on the EM1-D.2

Assignm. 2. Relay Programming the relay outputs on the EM1-D.2 see parameter list
on EM1-D.2
The relay 2 on the EM1-D.2 picks up, if the programmed logic condition is fulfilled.
Example: 3 + -8 + 13 (OR link)
3...... alarm class 3 has occurred
-8 ..... "MANUAL" operating mode has not been selected
13.... "Generator underspeed" alarm is present

4.18 Engine configuration

Configure Configuration of the engine YES/NO


engine YES
Various groups of parameters are placed together in blocks to allow you to navigate
through the large number of configuration screens more rapidly. Selecting "YES" or "NO"
has no effect on whether control or monitoring etc., is performed. The input merely has the
following effects:
YES .......... The configuration screens in the next block are displayed and can either be
viewed ("STATUS / ALARM" push-button) or modifications can be made to the
parameters ("PARAMETER", "U SELECT" or "STATUS / ALARM" push-button).
EA decision is not made on whether the parameters are processed or not.
NO .......... The parameters in the next block are not displayed, cannot be modified and
are therefore skipped.

4.18.1 Auxiliaries

Aux.services Auxiliary advance (start preparation) 0..999 s


prerun 000s
Prior to each starting process, a relay output (relay manager parameter 52) can be output
for an adjustable time (e. g. opening of a shutter). By setting the relay output, the message
"Aux. advance." is displayed. This relay output is immediately set in "MANUAL" operating
mode. The signal remains present until the operating mode is changed. Caution: In the
event of emergency power operation, this delay is not taken into consideration. The en-
gine is started immediately.

Aux.services Auxiliary coasting 0..999 s


postrun 000s
The relay output (relay manager parameter 52) can be output for an adjustable time after
each engine coasting (e. g. in order to operate a cooling water pump). If the operating
mode is switched from "MANUAL" to "STOP" or to "AUTOMATIC" without a start request,
the relay remains set for this coasting time. The message "Aux. coasting." is shown in the
display.

144 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
4.18.2 Engine type definition

Start-stop-logic Start/stop logic for ... DIESEL/GAS/EXTERNAL


for DIESELENGINE
DIESEL Start-stop-procedure for a diesel engine.
GAS Start-stop-procedure for a gas engine.
EXTERNAL External start-stop-procedure (start-stop-procedure disabled).

The start procedure is described in "Description starting/stopping process" starting on


page 37.

a.) Start/stop logic for gas engines

NOTE

The starting process for the gas engine is described in chapter "Gas engine" starting on page 39. The
configured attempts at starting are made.

Min.speed for Minimum speed at start 0..999 rpm


ignit. 000 rpm
The minimum starter speed can only be detected using an enabled pick-up. After expira-
This mask is only visible if the pa- tion of the firing delay, at least the speed entered here must be reached in order to set the
rameter "Pickup" is set ON. relay "ignition" (parameter 84) (see also the following parameters).

Ignition delay Ignition delay 0..99 s


00s
In the case of gas engines, a so-called purging operation is frequently desired prior to
starting. Firing delay is started when the starter is engaged. If, following the expiration of
this period of time, the "Starter minimum speed" has been reached, ignition is set.

Gasvalve delay Gas valve activation delay 0..99 s


00s
The gas delay time is started when the firing relay is set. Following the expiry of the period
of time set here, the gas valve is set as long as the speed still exceeds 150 rpm. On
reaching the firing speed, this relay holds itself until the engine comes to a stop.

Max. attempts to Gas engine; maximum number of start attempts 1..6


start 0
The control initiates this maximum of start sequences. If the engine could not started within
this maximum of start attempts, an alarm message is issued.

Starter time Engagement time: the gas valve is opened 2..99 s


00s
Maximum time, during which the starter starts the engine.

Start pause time Time between two start attempts 1..99 s


00s
Time between the individual attempts at starting.

f lower before Approach idle gas position ON/OFF


start ON
If this function is activated via "ON" and the item is equipped with a three-position fre-
[only with three- quency controller, "Speed down" is output for the period of time specified below before
position controllers] the starter is engaged. The idle gas position must either be protected via a limit switch, or
the engine potentiometer must be equipped with a slipping clutch. The message "Initial
state" is shown in the display. Caution: In the event of emergency power operation, en-
gine starting is delayed via the idle gas position.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 145
time f lower Approach idle gas position (time) 0..999 s
bef.start 000s
The duration of the "Speed down" output is entered here.
[only with three-
position controllers]

b.) Start/stop logic for diesel engines

NOTE

The starting process for the diesel engine is described in chapter "Diesel engine" starting on page 37. The
configured number of start attempts will be performed.

Preglow time Preheating time 0..99 s


00s
Prior to each starting procedure, the diesel engine is preheated for this period of time.

Max. attempts to Maximum number of start attempts 1..6


Start 0
The control initiates this maximum of start sequences. If the engine could not started within
this maximum of start attempts, an alarm message is issued.

Starter time Engagement time of the starter 2..99 s


00s
Maximum time, during which the starter tries to start the engine.

Start pause time Time between two start attempts 1..99 s


00s
Time between the individual attempts at starting.

f lower before Approach idle gas position ON/OFF


start OFF
If this function is activated via "ON" and the item is equipped with a three-position fre-
[only with three- quency controller, a continuous "Speed down" signal is output before the starter is en-
position controllers] gaged. The idle gas position must either be protected via a limit switch, or the engine po-
tentiometer must be equipped with a slipping clutch. The message "Initial state" is shown in
the display. Caution: In the event of emergency power operation, engine starting is de-
layed via this idle gas position.

time f lower Approach idle gas position (time) 0..999 s


bef.start 000s
The duration of the "Speed down" output is input here.
[only with three-
position controllers]

Fuel relay Start/stop logic operating magnet/stop magnet


-----------------------------
Operating magnet............ The operating magnet is set prior to each start procedure. In
order to switch the engine off, the operating magnet is with-
drawn.
Stop magnet .................... In order to switch the engine off, the stop magnet is set. The
stop magnet remains set for an additional 30 seconds after
negative deviation from the firing speed has occurred and the
generator voltage is less than 20 V.

146 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
4.18.3 Coasting, delayed engine monitoring and firing speed

a.) Coasting

Cool down time Coasting time 0..999 s


000s
In the event of normal engine shutdown (change to "STOP" mode) or stoppage via an
alarm class 2, coasting with frequency control is carried out with an open GCB for this
time. This time can be set. If coasting has been terminated (coasting time is exceeded) and
if a firing speed is nevertheless detected, the message "Shutoff malfunction is output after
30 s. Note: Coasting will be carried out only if there is the reply, GCB was closed (termi-
nal 4) for at least 5 seconds.

b.) Delayed engine monitoring

Delayed engine Delayed engine monitoring 1..99 s


monitoring 00s
The delay between reaching the firing speed and monitoring associated alarms (e. g. oil
pressure, generator underfrequency, etc.).

c.) Ignition speed

Firing speed Firing speed reached 5..70 Hz


reached f >00Hz
Setting the firing speed: After firing speed has been reached, the starter is switched off
and the frequency controller takes over the speed control.
Note: Measurement is only possible up to 15 Hz, even if 5 Hz are displayed. If the
Pickup measurement is set to "ON", values up to 5 Hz are measured.

Nominal frequency
Generator
frequency [Hz]

Minimum
frequency

Parameterization mask A

Monitoring on
at f gen > 00Hz

Time [s]

Delay 2
'ON' (parameterization
mask B)
1
Time [s]

1
Monitoring: generator undervoltage, generator underfrequency,
(generator underspeed; only option N), (reverse/reduced power; only option R1)

2
In addition the "Monitoring" LED is illuminated

Parameterization mask B Monitoring ON


after 00s

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 147
4.18.4 Pickup

Pickup input Pickup measurement ON/OFF


ON
ON .......... Engine speed monitoring is carried out via the Pickup. The disengagement of
the starter after the firing speed has been reached is additionally carried out
via Pickup measurement.
OFF .......... Frequency monitoring/control is carried out via the generator frequency
measurement. The disengagement of the starter after the firing speed has been
reached is carried out via the generator frequency.

Gen.rated speed Rated speed at rated frequency 0..3,000 rpm


0000 rpm
The number of revolutions carried out by the generator at rated frequency is specified here.

Number of pickup Number of Pickup teeth 30..280


teeth 000
The number of pulses per revolution.

Plausibility control
Plausibility control is carried out continuously; this compares the measured electrical fre-
quency (determined from the generator voltage) with the measured "mechanical" speed (de-
termined from the Pickup signal). If the two frequencies are not identical, an alarm is output
(alarm class 1). This is only activated following the expiry of the engine delay time.

4.19 Counter configuration

Configure Configuration of the counters YES/NO


counters YES
Various groups of parameters are placed together in blocks to allow you to navigate
through the large number of configuration screens more rapidly. Selecting "YES" or "NO"
has no effect on whether or not control or monitoring etc., is carried out. The input merely
has the following effects:
YES .......... The configuration screens in the next block are displayed and can either be
viewed ("STATUS / ALARM" push-button) or modifications can be made to the
parameters ("PARAMETER", "U SELECT" or "STATUS / ALARM" push-button). A
decision is not made on whether the parameters are processed or not.
NO .......... The parameters in the next block are not displayed, cannot be modified and
are therefore skipped.

148 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
4.19.1 Maintenance call

Service interval Maintenance call 0..9,999 h


in 0000h
A maintenance interval can be specified via this screen. After the engine has been in op-
eration for the number of hours set here, a maintenance message (alarm class 1, "Mainte-
nance") is displayed. Following the acknowledgement of the message, the counter is reset
to this value.

Note: The maintenance call can be disabled by setting it to "0".

NOTE

In order to acknowledge the maintenance call prematurely (no maintenance call is present yet), please proceed as
follows:
- Navigate to the display "Maintenance in 000h" using "Select".
- Press the button "Digit" für 10 seconds.
- The new maintenance interval is displayed.

4.19.2 Operating hour counter

NOTE

The number of operating hours can be set to a maximum of 65,000 hours.

Set oper.hours Operating hour counter 0..65,000 h


counter 00000h
This screen can be used to specify data regarding hours during which operation has al-
ready been carried out. This may be necessary, e. g. if an old engine is used or if this
control item is to be replace by a newer one.

NOTE

If a certain number of operating hours is to be pre-specified, the item must be in code level 2. For safety
reasons, the counter is set in a 2-step procedure. The following procedure applies:
1. Step: Setting and storage of the desired operating hours.
2. Step: Integration of the value which has been saved by ...
• terminating the configuration mode and switching to automatic mode,
• display of the operating hours and by
• pressing the "Digit" push-button for at least 5 seconds.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 149
4.19.3 Set start counter

NOTE

After 32,000 starts, the counter is automatically reset.

Set start Number of engine starts 0..32,000


counter 00000
The start counter can only be adjusted by the system maintenance personnel! The start
counter is used to display how often the engine has already been started. Following each
attempt at starting, the start counter is increased by one.

NOTE

If a certain value of operating hours is to be pre-specified, this control must be in code level 2.
For safety reasons, the counter is set in a 2-step sequence.
The following sequence applies:
1. Step: Setting and storage of the desired operating hours.
2. Step: Integration of the value which has been saved by ...
• terminating the configuration mode and switching to automatic mode,
• display of the operating hours and by
• pressing the "Digit" push-button for at least 5 seconds.

4.19.4 kWh counter

NOTE

The real energy can be set to a maximum of 65,500 MWh. After this, the kWh counter is automatically
reset to "0".

kWh counter kWh counter kWh/MWh


set in kWh
This screen is used to select whether the kWh counter is to be pre-loaded with kWh or
MWh. This may be the case, e.. g. if an old control item is to be replaced.

kWh counter kWh counter 0..65,500 kWh/MWh


set 00000MWh
The value with which the kWh counter is to be pre-loaded is specified here. In this case,
the input is dependent on the setting in the top screen. Positioning may be necessary,
e. g., if an old genset is used or if this control item is to replace a newer one.

NOTE

If a particular kWh counter value is to be predetermined, the device has to be in code level 2. The
counter is set in a two-step procedure due to safety reasons.
1. Step: Setting and storing of the desired counter value
2. Step: Taking over the stored value by ......
• ending the configuration mode and changing to automatic mode,,
• displaying the kWh counter and
• pressing the button "U SELECT" for at least 5 seconds.

150 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
4.19.5 Real time clock [PCM1x/H]

NOTE

If there are several PCM working in parallel on one common CAN bus all clocks are synchronized every
day at 12:00 o'clock (noon) to the time of the control with the lowest control/generator number. Therefore
it is necessary that the controls have different control numbers.

Time Clock display


00:00
The hours and minutes in the internal clock are set.
Setting
Hours
00 Nth hour of the day
01 1st hour of the day
... ...
23 23rd hour of the day
Minute
00 0st minute of the hour
01 1st minute of the hour
..
59 59th minute of the hour

Year,month Date display


00.00
Setting the year and month of the internal clock.
Setting
Year
98 Year 1998
99 Year 1999
00 Year 2000
... ...
Month
01 January
02 February
..
12 December

Day/weekday Date display


00/0
The day and weekday in the internal clock are set here.
Setting
Day
01 1st of the month
02 2nd of the month
... ...
31 31st of the month, if available
Weekday
1 Monday
2 Tuesday
... ...
7 Sunday

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 151
4.19.6 Current slave pointer

A current slave pointer, which records and stores the maximum generator current, is imple-
mented in the item. The display of the maximum generator current can be selected in
Automatic mode via the "Message" push-button. The following screen appears in the dis-
play:

000 000 000 000 Display of the maximum generator current


max. Gen.current
The maximum generator current in the three conductors is displayed and stored in this
screen.

Reset The current slave pointer is reset by pressing the "QUIT" push-button for 2.5 s. In order to
achieve this, the screen described in the above must be visible in the display.

152 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
4.20 Engine bus [PCMx]

Configure Configuration of the engine bus YES/NO


engine bus JA
Various groups of parameters are grouped together in blocks to allow to navigate through
the large number of configuration screens more rapidly. Selecting "YES" or "NO" has no
effect on whether or not control or monitoring etc., is carried out. The input merely has the
following effects:
YES ..........The configuration screens in the next block are displayed and can either be
viewed ("Select" push-button) or modifications can be made to the parameters
("Cursor→", "U SELECT" or "SELECT" push-buttons). A decision is not made on
whether the parameters are processed or not.
NO ..........The parameters in the next block are not displayed, cannot be modified and
are therefore skipped.

CAN-Baudrate Baudrate of the engine bus 100/125/250/500 kBaud


000kBd
Baudrate of the engine CAN bus. Please note, that all participants on the engine CAN
bus must use the same Baud rate.

4.20.1 EM1-D – Digital Expansion Board

NOTE

For the function as well as for the configuration of the EM1-D please see in the separate manual. This
parameter can only be configured using FL-SOFT3.

EM1-D on bus EM1-D on bus YES/NO


JA
YES .......... The functions of the EM1-D are active. And there is a monitoring whether the
[x = 1/2] EM1-D {x} is on engine bus. If this parameter is set to YES but the EM1-D is
not connected to the CAN bus the PCx releases an interface fault.
NO .......... The functions of the EM1-D are blocked and there is no communication moni-
toring to the EM1-D.

Notes to EM1-D-Interface fault – The "Interface fault Y1Y5" of the alarm class 1 will be released when the PCx receives no mes-
sages from the EM1-D for about 5 s. Furthermore the relais drops-out (or picks up according to the configuration). The relay picks up
again, when the PCx receives data from the EM1-D.

4.20.2 Lambda controller 'PCR3'

NOTE

This parameter can only be configured using FL-SOFT3.

PCR3 on bus PCR3 on bus YES/NO


NO
YES ..........The functions of the PCR3 are active. And there is a monitoring whether the
PCR3 is on engine bus. If this parameter is set to YES but the PCR3is not con-
nected to the CAN bus the PCx releases an interface fault.
NO ..........The functions of the PCR3 are blocked and there is no communication monitor-
ing to the PCR3.

Notes to the PCR3 interface faults – The "Interface fault Y1Y5" of the alarm class 1 will be released when the PCx receives no
messages from hte PCR3 for about 5 s. The measuring values of PCR3 are overwritten with "0". Furthermore the relais drops-out (or
picks up according to the configuration). When the PCx receives again data from the PCR3, the relay picks up and the measuring
values from the PCR3 were displayed again. (If an interface fault Y1Y5 will be released for example by a faulty EM1-D communica-
tion, the data of the PCR3 will be furthermore displayed correct.)

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 153
4.20.3 Engine control 'General'

NOTE

Simultaneous CAN bus interconnection of MDEC and J1939 components is not possible.

Description Display/Messages J1939 MDEC


German English Std. EMR2 S6
Display: Engine speed Mot.Drehz.0000,0 Eng.speed 0000.0 " " " "
/#4
Display: Oil pressure Öldruck 00,00b Oil pres. 00.00b " " " "
Display: Fail codes Fehlercodes 0000 Fail.codes 0000 "
Display: ECU Operating hours ECUBetrstd00000h ECU OpHrs 00000h "
/#4
Display: Coolant temperature Kühlmit. 000,0C Coolant 000.0C " /#1 " " "
/#4
Display: Oil temperature Öl 000,0C Oil 000.0C " " "
/#4
Display: Fuel temperature Kraftst. 000,0C Fuel ü000.0C " /#1 " " "
Display: Feedback speed Feedb.Drz.0000,0 Feedb.spd.0000.0 "
Display: Coolant level Kühlm.Stand 000% Cool. level 000% " " "
Alarm: ECU defect AL ECU defekt AL ECU defect "
Alarm: Coolant temperature Kühlmitteltemp. Coolant temp. " "
Alarm: ST Coolant temperature ST Kühlmitt.temp ST Coolant temp. " "
Alarm: Oil temperature too high Öltemp. zu hoch HI Oil temp. "
Alarm: SD Coolant level SD Kühlm.stand SD Coolant level " " " "
Alarm: SD Coolant charging air SDKühlm.Ladeluft SD Cool.chrg.air "
Alarm: ST Oil level ST Ölstand ST oil level " " /#2
Alarm: ST Engine protection ST Motorschutz ST Eng. protect. "
Alarm: ST Overspeed ST Überdrehzahl ST overspeed "
Alarm: ECU Red Alarm ECU Rot-Alarm ECU red alarm "
Alarm: Oil pressure to low Öldruck niedrig Low oil pressure " "
Alarm: ST Oil pressure ST Öldruck ST oil pressure " "
Alarm: ECU Yellow Alarm ECU Gelb-Alarm ECU yell. alarm "
Alarm: Coolant level Kühlmittelstand Coolant level " /#3 " /#3
Alarm: Coolant temperature Kühlmittelvorh. Preheat Temp low "
Alarm: ST Coolant charging air STKühlm.Ladeluft ST Cool.chrg.air " "
Alarm: SD Speed demand SD Solldrehzahl SD Speed demand "
Alarm: SD Engine speed SD Agg.Drehzahl SD Engine speed " " " "
Alarm: SD Oil pressure SD Öldruck SD Oil pressure " " " "
Alarm: SD Failure codes SD Fehler Codes SD failure codes "
Alarm: SD Operating hours SD Betr.Std. SD oper. hours "
Alarm: SD Coolant temperature SD Kühlmitteltmp SD Coolant temp. " " " "
Alarm: SD Oil temperature SD Öltemperatur SD Oil temp. " "
Alarm: SD Fuel temperature SD Kraftst.Tmp. SD Fuel temp. " " " "
SD..Sensor defect, ST..Stop/Shut down, AL..Alarm; #1 the unit amount is 1 °C; #2 may be as well as "Oil pressure to high" as also "Oil pressure to low";
#3 On EMR2 this display means Shutdown because of too low coolant level, on MDEC it means Warning because of too low coolant level,
#4 changeable bar ↔ psi, bzw. °C ↔ °F.

Notes to J1939 protocol – In the above table (J1939 'Standard') the messages are listed which can be displayed of the PCx. If a
value cannot be send from the used ECU, a FFxx'h is sent according to the SAE J1939 standard. The PCx identifies this and the
according value will not be displayed. According to the SAE J1939 standard a priority is defined in the CAN-ID of a SAE J1939
message. This will not be regarded from the PCx. The PCx receives messages of all priorities.

Notes to "Interface fault engine bus" – Basically the "Interface fault Y1Y5" is released in alarm class 1 and is shown in the display if
the PCx does not receive CAN data of an active subunit for a certain time. As perhaps several devices are connected to the bus the
relay manager can be configured additionally for every subunit which signals the missing/existing connection to the subunit.

154 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
NOTE

Please refer to the manufacturer's manual for information about the functionality of the MDEC.

ECU interface monitoring YES/NO

YES .......... If the connection MDEC – PCM or J1939-PCM is interrupted for a certain
time, the message “interf,err. Y1Y5” is displayed with alarm class 1.
NO .......... If the connection MDEC-PCM or J1939-PCM is interrupted, this message is
not displayed. (This setting makes sense, if an engine shutdown is only possi-
ble by disconnecting the power supply of the engine control. Otherwise, an
interface error would be triggered with shutdown).

NOTE

This setting has no effect on the interface error triggering for EM1-D and PCR3. It has also no influence on the
relays with the parameters 134 to 138.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 155
a.) Engine control 'MDEC'

NOTE

Please refer to the manufacturer's manual for information about the functionality of the MDEC.

MDEC MDEC OFF/Visual/Control/Visualization/Control


-----------------------------
OFF .......... The coupling to the mtu MDEC is disabled and no MDEC data is processed.
Note The MDEC cannot trigger an interface error Y1Y5.
MDEC and J1939 cannot be operated
Visual/Control - The coupling to the mtu MDEC is enabled, MDEC values and the follow-
simultaneous!
ing parameters are displayed, and values are sent to the MDEC. The MDEC
can trigger an interface error Y1Y5.
Visualization - The coupling to the mtu MDEC is enabled and MDEC values and the fol-
lowing parameters are displayed. The MDEC can trigger an interface error
Y1Y5.
Control...... The coupling to the mtu MDEC is enabled, the following parameters are dis-
played, and values are sent to the MDEC. The MDEC can trigger an interface
error Y1Y5.

(The display values are overwritten with question marks in case of an interface error, trig-
gered by the CCM.)

Note
The MDEC cannot be used together with J1939.

MDEC protocol MDEC protocol V302/V303/V304


---------------------
Firmware software version of the MDEC.

max.speed loop MDEC speed loop 0..999 rpm


000 rpm
The setting of this mask will be attended, if the setpoint value to the MDEC controller oc-
curs via the CAN bus. For a power control the rated real power will be regulated by the
nominal speed value. The entered speed loop depends on the droop characteristics of the
engine. As an adjustment help, you can determine the speed loop as follows:

Without setpoint value at the MDEC speed governor the engine will be loaded half or full.
The occurred speed break-in can be entered on full load directly as speed loop. If you
measure under half load you have to enter the double value. For more information please
not the manual of the MDEC:

A speed control is only possible if the frequency controller is set to ANALOG. If the control
is not active yet, the set rated speed is calculated as follows:

nAusgabe = nNenn +
((GS − 50% )x nmax Hub )x 2
100%

nAusgabe output value [min-1]


nNenn rated speed [min-1]
GS initial setting [%]
nmaxHub maximum speed loop [min-1] (this parameter)

Note to the MDEC interface error – The "interface error Y1Y5" with alarm class 1 is triggered, if the PCx does not receive an "Alive"
message for about 0,5 s from the MDEC. The measurement values of the MDEC are overwritten with question marks and the MDEC
alarm messages are suppressed. Moreover, the relay with the parameter 137 de-energizes (or energizes depending on program-
ming). If the PCx receives the "Alive" message again, the relay energizes again and the measurement values as well as the alarm
messages of the MDEC are displayed again. (If an interface error Y1Y5 is triggered, which was caused by e.g. a faulty EM1-D
communication, the data of the MDEC is still displayed correctly.)

156 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
b.) Engine control 'SAE J1939'

NOTE

The J1939 data coupling, parameter setting 'Standard', is performed according to the standard SAE
J1939.

NOTE

Please take the description of the functonality of the units, which can be connected to the SAE J1939
engine CAN bus, from the manufacturer's manual.

J1939 J1939 Off/Standard/EMR2/S6


-----------------------------
Off ........... The coupling to J1939 is disabled and no J1939 data is processed. The
Notes J1939 cannot trigger an interface error Y1Y5.
J1939 and MDEC cannot be operated
Standard ... The coupling to J1939 is enabled, the J1939 values are displayed according
simultaneous!
to the SAE J1939 standard and the following parameters are displayed. The
J1939 can trigger an interface error Y1Y5. (The display values are overwritten
with question marks in case of an interface error, triggered by the J1939.)
EMR2 ....... The coupling to Deutz EMR2 is enabled and EMR2 values and the following
parameters are displayed. The EMR2 can trigger an interface error Y1Y5.
S6 ............ The coupling to Scania EMS/S6 is enabled and EMS/S6 values and the fol-
lowing parameters are displayed. The EMS/S6 can trigger an interface error
Y1Y5.

Note
The J1939 coupling cannot be used together with the MDEC.

J1939 unit numb. J1939 device number 0..255


000
The PCx processes only data of a J1939 device, which sends using this CAN device
number.

Note to the J1939 interface error – The "interface error Y1Y5" with alarm class 1 is triggered, if the PCx does not receive an "Alive"
message for about 0,5 s via the J1939 CAN bus. The measurement values of the J1939 participant are overwritten with question
marks and the J1939 alarm messages are suppressed. Moreover, the relay with the parameter 138 de-energizes (or energizes
depending on programming). If the PCx receives the "Alive" message again, the relay energizes again and the measurement values
as well as the alarm messages of the J1939 participant are displayed again. (If an interface error Y1Y5 is triggered, which was
caused by e.g. a faulty EM1-D communication, the data of the J1939 participant is still displayed correctly.)

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 157
5 Commissioning

DANGER !!!WI

When commissioning the item, please observe the five safety rules that apply to the handling of live
equipment. Make sure that you know how to provide first aid in current-related accidents and that you
know where the first aid kit and the nearest telephone are. Never touch any live components of the system
or on the back of the system:

LIFE THREATENING

WARNING !

The item may only be commissioned by a qualified technician. The "EMERGENCY OFF function must
function safely before the commissioning and must not depend on the particular engine.

CAUTION !

1. Prior to commissioning, check that all measuring voltages are correctly connected with regard
to phases. The connect commands for the power circuit breakers must be disconnected at
the power circuit breakers. The rotating field must be measured. Any lack or incorrect
connection of measuring voltages or other signals may lead to incorrect functions and
damage the item as well as engines and components connected to the item.

Procedure 2. After checking to ensure that all measuring voltages have been connected to the correct phases,
the supply voltage (12/24 Vdc) has to be connected.

3. By simultaneously pressing the two push-buttons " U SELECT" and "PARAMETER", the configuration
and test mode is accessed. After entering the code number, all parameters are first set (see the
chapter regarding the parameters).

4. Following the application of the supply voltage, please check that all measuring values (voltages,
currents, wattages, power circuit breakers replies) are correctly displayed. The engine must only
be started if the power circuit breaker replies are correct.

5. First start the engine via the "MANUAL" operating mode (press the "MANUAL" push-button)
("START") and then stop it ("STOP"). All generator measuring values must be checked. Please also
check any messages caused by alarms.

6. Check the automatic start procedure via the "TEST" operating mode (press the "TEST" push-
button). Test protection caused by alarms with shutdown.

7. Operating mode "AUTO" (press the push-button "AUTOMATIC"): Automatic starting with subse-
quent synchronization can now be carried out by applying the automatic control inputs and the
engine request.
Check synchronization: Check the generator and the generator busbar rotating field. Check the
connect command with a zero voltmeter (determination of the phase angle) at the generator
power circuit breaker. If several correct synchronizing pulses have been output, switch the oper-
ating mode to "STOP" and reconnect the connect pulse "Command: close GCB" with the engine
at a standstill.

158 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
8. If Points 1 to 7 have been carried out successfully, you may now initially commence operation in
parallel with the mains with a constant power (approx. 25 % of the generator rated power).
Whilst this is being carried out, the displayed measuring values must be checked. Check GCB
shutdown. Check the real power controller and, if necessary, the power factor ϕ controller. Pre-
specify various setpoint values and check control.

9. If operation in parallel with the mains is carried out in a satisfactory manner, the synchronization
of the mains power circuit breaker must be checked:

At this point, at the latest, it must be ensured that a power failure in the system has been clarified
or registered. During operation in parallel with the mains, the item must be switched to "MAN-
UAL" operating mode; the mains power circuit breaker is then de-activated ("MCB ON" LED is
extinguished). The item must then be switched back to "AUTOMATIC" operating mode.

Check the generator busbar and the mains rotating field. Check the connect command with a
zero voltmeter (determination of the phase angle) at the mains power circuit breaker. If several
correct synchronizing pulses have been output, switch the operating mode to "STOP" and re-
connect the connect pulse "Command: close MCB" with the engine at a standstill.

10.Test emergency power operation functions.

NOTE

The function in automatic mode is influenced via the available input signals "Automatic 1" and
"Automatic 2". Make sure that the reply messages of the power circuit breakers are processed inverted,
i. e., when the power circuit breaker is closed there must be a "reply message applied on the inputs: CB is
open" 0 V (auxiliary contact of the power circuit breaker as a break contact (NC)! - note the description of
the auxiliary and control inputs at the beginning of this manual). It is vital that these replies be connected!

Electrical isolation between voltage supply and discrete control and feedback inputs
Via corresponding external wiring, the common reference point of the discrete inputs can be
electrically isolated from the supply voltage (0 V, terminal 2). This is necessary, for example, if
the discrete inputs are not to be triggered with 24 Vdc and an electrically isolation of the control
voltage (e. g. 220 Vdc, 220 Vac) from the supply voltage must be insured.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 159
6 Appendix

6.1 Analog output manager

NOTE

The parameters listed below can only be output correctly if the existing version of the item permits this.

Parameter Output Input of the two limit values


0 The analog output is inactive. Input irrelevant
1 Generator real power 0% Lower power (can also be
negative) e.g. –0050 kW
100% Upper power (can also be
[kW] negative) e.g. 0200 kW
2 Actual generator power factor ϕ 0% Lower interval to power factor ϕ=1
[e. g. (-070.....+080) /100] e. g. -0030 corresponds to c0.70
(Definition at end of Table) 100% Upper interval to power factor ϕ=1
[dimensionless] e. g. 0030 corresponds to i0.70
3 Actual generator frequency 0% Lower frequency e. g. 0000
corresponds to 00.00 Hz.
100% Upper frequency e. g. 7000
[Hz∗100] corresponds to 70.00 Hz.
4 Actual generator re-active power 0% capacitive re-active power
(negative) e. g. -0100 kvar
100% inductive re-active power
[kvar] (positive) e. g. +0100 kvar
5 Rated power of all generators con- 0% Lower power (can also be
nected to generator busbar minus negative) e. g. –0050 kW
nominal actual power 100% Upper power (can also be
[kW] negative) e. g. 0200 kW
6 Total actual power of all generators 0% Lower power (can also be
connected to generator busbar negative) e. g. –0050 kW
[kW] 100% Upper power (can also be
negative) e. g. 0200 kW
7 Generator apparent current in L1 0% Lower current output
e. g. 0000 A
100% Upper current output
[A] e. g. 500 A
8 Generator apparent current in L2 0% Lower current output
e. g. 0000 A
100% Upper current output
[A] e. g. 500 A
9 Generator apparent current in L3 0% Lower current output
e. g. 0000 A
100% Upper current output
[A] e. g. 500 A
10 Speed via Pickup 0% Lower speed
(terminals 91, 92, 93) e. g. 0,000 rpm
100% Upper speed
[min-1] e. g. 3,000 rpm
11 Analog input [T1]
temperature [°C] or [°F] or
freely scaleable analog input
0% Lower measured value
e. g. 0000 corresponds to 000 °C
12 Analog input [T2]
at temperature input
temperature [°C] or [°F]
100% Upper measuring value
freely scaleable analog input
e. g. 0255 corresponds to 255 °C
at temperature input
13 Analog input [T3]
temperature [°C] or [°F]
0% Lower measured value e. g. 0000
freely scaleable analog input
corresponds to 00.0 bar oil pressure
100% Upper measured value e. g. 0100
14 Analog input [T4]
corresponds to 10.0 bar oil pressure
temperature [°C] or [°F]
freely scaleable analog input

160 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
Parameter Output Input of the two limit values
15 Analog input [T5]
temperature [°C] or [°F]
freely scaleable analog input
0% Lower measured value
e. g. 0000 corresponds to 000 °C
16 Analog input [T6]
at temperature input
temperature [°C] or [°F]
100% Upper measuring value
freely scaleable analog input
e. g. 0255 corresponds to 255 °C
at temperature input
17 Analog input [T7]
temperature [°C] or [°F] 0% Lower measured value e. g. 0000
freely scaleable analog input corresponds to 00.0 bar oil pressure
100% Upper measuring value e. g. 0100
18 Additional freely scaleable analog corresponds to 10.0 bar oil pressure
input (terminals 91, 92)

19 Actual mains real power 0% lower power


e. g. -0800 kW
100% upper power
[kW] e. g. 0800 kW
20 Mains apparent current in L1 0% Lower current output
e. g. 0000 A
100% Upper current output
[A] e. g. 500 A
21 Mains power factor ϕ 0% Lower interval to power factor ϕ=1
[e. g. (-070.....+080) /100] e. g. -0030 corresponds to k0.70
(Definition at end of Table) 100% Upper interval to power factor ϕ=1
[dimensionless] e. g. 0030 corresponds to i0.70
22 Actual mains re-active power 0% capacitive re-active power (negative)
e. g. -0100 kvar
100% inductive re-active power (positive)
[kvar] e. g. +0100 kvar

The designation 0 % stands for either 4 mA or 0 mA; the designation 100 % stands for 20 mA. The values may also
be assigned with prefixes (see parameter 1).

Definition of power factor ϕ-scaling According to the scaling of the analog output, the power factor ϕ can be output within the
range from capacitive values ranging from c0.00 via power factor ϕ = 1 to inductive val-
ues up to i0.00.

Power factor = 1,00

Capacitive Inductive
Lower distance Higher distance
eg. 0030 eg. 0030
Scalable range (0..20 mA)
k 0.00 eg. k0.70..1.00..i0.70 i 0.00

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 161
6.2 Relay manager (list of parameters with explanations)

Parameter Output Explanation


1 Alarm class 1
2 Alarm class 2
3 Alarm class 3
4 Firing speed reached / engine runs
5 Mains failure; undelayed The function is evaluated depending
on the status of the breakers. The
conditions described in chapter
"Emergency power" apply.
6 Battery undervoltage
7 Operating mode AUTOMATIC
8 Operating mode MANUAL
9 Operating mode TEST
10 Operating mode STOP
11 Generator undervoltage
12 Generator overvoltage
13 Generator underfrequency
14 Generator overfrequency
15 Generator overcurrent level 1
16 "Synchronization GCB" or "Connect GCB" time monitoring alarm.
17 Engine false start
18 Generator load imbalance
19 Generator overload
20 Generator reverse/reduced power
21 Readiness for operation Output via relay manager
22 Analog input [T1], level 1
23 Analog input [T1], level 2
24 Analog input [T2], level 1
25 Analog input [T2], level 2
26 Analog input [T3], level 1
27 Analog input [T3], level 2
28 Analog input [T4], level 1
29 Analog input [T4], level 2
30 Analog input [T5], level 1
33 Analog input [T5], level 2
32 Analog input [T6], level 1
33 Analog input [T6], level 2
34 Analog input [T7], level 1
35 Analog input [T7], level 2
36 Discrete input [1]
37 Discrete input [2]
38 Discrete input [3]
39 Discrete input [4]
40 Discrete input [5]
41 Discrete input [6]
42 Discrete input [7]
43 Discrete input [8]
44 Discrete input [9]
45 Discrete input [A]
46 Discrete input [B]
47 Discrete input [C]
48 Discrete input [D]
49 Discrete input [E]
50 Discrete input [F]
51 Discrete input [G]
52 Auxiliaries e. g. pump advance/coasting
53 Internal
54 Group alarm class 1, class 2 or class 3 (remanent up until acknowledgement)
55 Operating mode TEST or AUTOMATIC selected
56 Generator power watchdog, level 1
57 MCB is closed
58 GCB is closed
59# Interface alarm Y1Y5

162 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
Parameter Output Explanation
60 Operation in parallel with the mains is desired: blockage of GCB ↔ enable of MCB
61 Overcurrent I/t or generator overcurrent, level 2
62 Introduce load-shedding: Connection / synchronization of GCB is carried out or circuit Signal is set prior to connection /
breaker is closed synchronization and remains present
when circuit breaker is closed.
63 Connection / synchronization MCB carried out or circuit breaker is closed Signal is set prior to connection /
synchronization and remains present
when circuit breaker is closed.
64 Overspeed via Pickup
65 Emergency power is active
66 Shutdown malfunction
67 Power watchdog for power supplied by the mains
68 Maintenance call
69 Pickup/gen. differential frequency The electrically determined speed
and the speed determined via Pickup
are different
70 "Synchronization MCB" or. "Connect MCB" time monitoring alarm.
71 GCB synchronization carried out
72 MCB synchronization carried out
73 Lamp test active
74 Malfunction "Reply: GCB is open" - fault on closing The GCB cannot be closed after 5
attempts.
75 Malfunction "Reply: MCB is open" - fault on closing The MCB cannot be closed after 5
attempts.
76 Malfunction "Reply: GCB is open" - fault on opening 2 s following the "Command: open
GCB" a reply continues to be de-
tected.
77 Malfunction "Reply: MCB is open" - fault on opening 2 s following the "Command: open
MCB" a reply continues to be de-
tected.
78 Power supplied by the mains <> 0 In the event of interchange synchro-
nization, the incoming power zero
cannot be adjusted. As a result of
this, the MCB is prevented from
opening. Reset via acknowledgment.
79 Connect time on black start exceeded
80 Generator power watchdog, level 2
81 Left mains rotating field
82 Engine enable Set engine enable
As long as there is a start request for
the engine and during coasting (as
long as the operation of the engine is
enabled, e. g. operating mode
AUTOMATIC and discrete input
3/5, emergency power, start via
interface, manual start, etc.).
Reset engine enable
If the start request is no longer pre-
sent, in the event of manual stop-
page, with alarm class F3, during
the engine stop time (prior to a further
attempt at starting) and on detection
of "zero" speed if, at the same time,
no start request is present and coast-
ing is not taking place.
83 "QUIT" push-button pressed
84 Preheating/firing ON (pre-assigned to relay [7]) pre-assigned default value
85 Group alarm of alarm class 1, 2 or 3 (pre-assigned to relay [8]) pre-assigned default value
Horn: after 2 min independent shutoff
86# Power reduction level 1 reached Option Tz, temperature-dependent
87# Magnitude of the power reduction level 2 reached power reduction
88 Generator voltage and frequency are not available (undelayed)
89 Busbar voltage and frequency are not available (undelayed)

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 163
Parameter Output Explanation
90 Internal
91 Pickup has nominal speed (+/-6 %)
92 Mains voltage fault via protection device
93 Mains frequency fault via protection device
94 Phase/vector shift fault via protection device
95 Internal
96 Delayed engine monitoring time exceeded
97 Sprinkler mode is active (included Sprinkler coasting)
98 EM1-D.[1] – Discrete input [1]
99 EM1-D.[1] – Discrete input [2]
100 EM1-D.[1] – Discrete input [3]
101 EM1-D.[1] – Discrete input [4]
102 EM1-D.[1] – Discrete input [5]
103 EM1-D.[1] – Discrete input [6]
104 EM1-D.[1] – Discrete input [7]
105 EM1-D.[1] – Discrete input [8]
106 EM1-D.[2] – Discrete input [1]
107 EM1-D.[2] – Discrete input [2]
108 EM1-D.[2] – Discrete input [3]
109 EM1-D [2] – Discrete input [4]
110 EM1-D.[2] – Discrete input [5]
111 EM1-D.[2] – Discrete input [6]
112 EM1-D.[2] – Discrete input [7]
113 EM1-D.[2] – Discrete input [8]
114 Three-position controller: n+ / f+ / P+
115 Three-position controller: n- / f- / P-
(use an external RC protection circuit)
116 Three-position controller: V+ / Q+
117 Three-position controller: V- / Q-
118 Internal
119 Wire break Analog input [T1]
120 Wire break Analog input [T2]
121 Wire break Analog input [T3]
122 Wire break Analog input [T4]
123 Wire break Analog input [T5]
124 Wire break Analog input [T6]
125 Wire break Analog input [T7]
126 Internal
127 Internal
128 Internal
129 Fault Lambda sensor (via CAN bus)
130 Lambda control active
131 Fuel relay is ON / stop relay is ON / gas valve is ON
132 Internal
133 Internal
134 Communication with EM1-D [1] okay
135 Communication with EM1-D [2] okay
Direct configuration via
136 Communication with PCR3 okay
FL-SOFT3 possible.
137 Communication with MDEC okay
138 Communication with J1939 okay
139 Phase rotation generator/busbar or busbar/mains different
140 Direction of rotation, mains voltage: CW
141 Direction of rotation, generator voltage: CCW
142 Direction of rotation, generator voltage: CW
143 Starter engaged (cranking)
144 GCB is to be opened
145 Internal
146 Parallel operation CB from V4.3161
147 Time internal
148 Unintended stop from V4.3161
149 Interface error X1/X5 from V4.3161

164 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
6.3 Interface [PCL1/H & PCM1x]

6.3.2 Transmission telegram

The data of the following table can be handled by a Gateway or a PLC and can be trans-
ferred to other busses. An PCx is sending the data via circular CAN messages.

The transmitting rate of this communication is 125 kBaud.

The CAN ID, on which the PCx is sending is calculated as follows:

CAN-ID = d‘800 + Item number (or H‘320 + item number)

(The item number is a parameter adjustable on the PCx which influences directly the CAN
ID on which the item sends the visualization message).

A visualization message which is send out of an PCx has got 8 Byte and is built as follows:

Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7


data word 1 data word 1 data word 2 data word 2 data word 3 data word 3
H‘DD MUX number
High-Byte Low Byte High-Byte Low Byte High-Byte Low Byte

In a visualization message the byte 0 is always used to show the hexadecimal value DD.
This one defines the message as a visualization message. As the complete transmission
telegram of the PCx includes more than three words byte 1 sends additionally a MUX
number starting with 0. Therefore it is theoretically possible to send (256 × 3 = 768)
words via the CAN ID. The whole telegram is built up as follows:

line 1: MUX number 0, word 1


line 2: MUX number 0, word 2
line 3: MUX number 0, word 3
line 4: MUX number 1, word 1
line 5: MUX number 1, word 2
line 6: MUX number 1, word 3
.
.
line (n): MUX number (n-1/3), word 1
line (n+1): MUX number (n-1/2), word 2
line (n+2): MUX number (n-1/1), word 3

n depends on the total length of the item special telegram and can not be larger than H’FF.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 165
Contents (words) Unit Note

MUX

0/1 Nr.
1 Generator voltage U12 V × 10UGNEXPO
0/2 2 Generator frequency f Hz × 100
0/3 3 Generator real power P W × 10PGNEXPO
1/1 4 H.B. Generator power exponent PGNEXPO
L.B. Generator voltage exponent UGNEXPO
1/2 5 Current generator real power setpoint (steps) For display in kW: (Value/2800) × PGNWD
1/3 6 Step conversion factor ! kW PGNWD
2/1 7 Busbar voltage chain-linked U12 V × 10UGNEXPO
2/2 8 Mains voltage chain-linked U12 V × 10UNTEXPO
2/3 9 Currently present alarm class Bit 15 =1 Internal
Bit 14 =1 Internal
Bit 13 =1 \
Alarm class 2 or 3
Bit 12 =1 /
Bit 11 =1 \
"Alarm" LED flashes
Bit 10 =1 /
Bit 9 =1 Internal
Bit 8 =1 Internal
Bit 7 =1 \
Alarm class 3
Bit 6 =1 /
Bit 5 =1 \
Alarm class 2
Bit 4 =1 /
Bit 3 =1 \
Alarm class 1
Bit 2 =1 /
Bit 1 =1 \
Alarm class 0
Bit 0 =1 /
3/1 10 Control register 2 Bit 15 =1 \
Terminal 3 is set
Bit 14 =1 /
Bit 13 =1 \
Terminal 5 is set
Bit 12 =1 /
Bit 11 =1 Internal
Bit 10 =1 Internal
Bit 9 =1 \
Enable MCB
Bit 8 =1 /
Bit 7 =1 \
Reply: GCB is closed
Bit 6 =1 /
Bit 5 =1 \
Reply: MCB is closed
Bit 4 =1 /
Bit 3 =1 \
Terminal 6 has been set (High signal)
Bit 2 =1 /
Bit 1 =1 \
Shutoff power reached
Bit 0 =0 /
Bit 1 =0 \
Shutoff power not reached
Bit 0 =1 /
3/2 11 Actual mains real power W × 10PNTEXPO
3/3 12 Control register 1 Bit 15 = 1 \ Starting enabled (in isolated operation or
Bit 14 = 1 / operation in parallel with the mains)
Bit 13 = 1 Internal
Bit 12 = 1 Internal
Bit 11 = 1 \ Execution of acknowledgment
Bit 10 = 1 / of a F2/F3 alarm
Bit 9 = 1 \ Execution of acknowledgment
Bit 8 = 1 / of a F1 alarm
Bit 7 = 1 \
PMS internal
Bit 6 = 1 /
Bit 5 = 1 \
PMS internal
Bit 4 = 1 /
Bit 3 = 1 \
PMS internal
Bit 2 = 1 /
Bit 1 = 1 Internal
Bit 0 = 1 Internal

166 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
Contents (words) Unit Note
MUX

Nr.
4/1 13 EM1-D.[1] alarms Bit 15 =1 EM1-D.[1] - discrete input [8]
Bit 14 =1 EM1-D.[1] - discrete input [7]
Bit 13 =1 EM1-D.[1] - discrete input [6]
Bit 12 =1 EM1-D.[1] - discrete input [5]
Bit 11 =1 EM1-D.[1] - discrete input [4]
Bit 10 =1 EM1-D.[1] - discrete input [3]
Bit 9 =1 EM1-D.[1] - discrete input [2]
Bit 8 =1 EM1-D.[1] - discrete input [1]
Bit 7 =1 Internal
Bit 6 =1 Internal
Bit 5 =1 Internal
Bit 4 =1 Internal
Bit 3 =1 Internal
Bit 2 =1 Internal
Bit 1 =1 Internal
Bit 0 =1 Internal
4/2 14 Internal alarm 6 Bit 15 =1 Pickup plausibility fault
Bit 14 =1 Engine shut-off malfunction
Bit 13 =1 GCB time overrun when switching
to the black busbar
Bit 12 = 1 Internal
Bit 11 = 1 MCB open switch malfunction
Bit 10 = 1 GCB open switch malfunction
Bit 9 = 1 MCB synchronization time monitoring
Bit 8 = 1 GCB synchronization time monitoring
Bit 7 = 1 Range alarm analog input [T8]
Bit 6 = 1 Range alarm analog input [T7]
Bit 5 = 1 Range alarm analog input [T6]
Bit 4 = 1 Range alarm analog input [T5]
Bit 3 = 1 Range alarm analog input [T4]
Bit 2 = 1 Range alarm analog input [T3]
Bit 1 = 1 Range alarm analog input [T2]
Bit 0 = 1 Range alarm analog input [T1]
4/3 15 Generator voltage chain-linked U23 V × 10UGNEXPO
5/1 16 Generator voltage chain-linked U31 V × 10UGNEXPO
5/2 17 Generator voltage star U1N V × 10UGNEXPO
5/3 18 Generator voltage star U2N V × 10UGNEXPO
6/1 19 Generator voltage star U3N V × 10UGNEXPO
#1# °C bar/10 % keine
6/2 20 Configuration [T1]-[T4] Display in
Einh.
Analog input [T4]
Bit 15 = 0 0 1 1 0
Bit 14 = 0 1 0 1 0
Bit 13 = 0 0 0 0 1
Bit 12 = 0 1 1 0 1
Analog input [T3]
Bit 11 0 0 1 1 0
Bit 10 0 1 0 1 0
Bit 9 0 0 0 0 1
Bit 8 0 1 1 0 1
Analog input [T2]
Bit 7 0 0 1 1 0
Bit 6 0 1 0 1 0
Bit 5 0 0 0 0 1
Bit 4 0 1 1 0 1
Analog input [T1]
Bit 3 0 0 1 1 0
#1#: The analog input is not available or Bit 2 0 1 0 1 0
configured as real power set value or as mains Bit 1 0 0 0 0 1
real power actual value. Bit 0 0 1 1 0 1

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 167
Contents (words) Unit Note
MUX

Nr.
6/3 21 Engine speed determined via Pickup min-1
7/1 22 Generator current in L1 A × 10IGNEXPO
7/2 23 Generator current in L2 A × 10IGNEXPO
7/3 24 Generator current in L3 A × 10IGNEXPO
8/1 25 Actual generator re-active power var × 10PNTEXPO positive = inductive
8/2 26 Generator power factor ϕ Example: 0064H power factor ϕ = 1.00
0063H power factor ϕ = i0.99 (inductive)
FF9EH power factor ϕ = c0.98 (capacitive)
8/3 27 Current reserve power in the system kW
9/1 28 Current actual real power in the system kW
9/2 29 Number of subscribers in the CAN bus
9/3 30 H.B. Mains status FFH Voltage and frequency available
L.B. Generator status 00H Voltage and frequency not available
10/1 31 H.B. Exponent generator current
IGNEXPO
L.B. Reserve
10/2 32 Busbar frequency Hz × 100
10/3 33 #1# °C bar/10 % keine
Konfiguration [T5]-[T8] Display in
Einh.
Analog input [T8]
Bit 15 = 0 0 1 1 0
Bit 14 = 0 1 0 1 0
Bit 13 = 0 0 0 0 1
Bit 12 = 0 1 1 0 1
Analog input [T7]
Bit 11 = 0 0 1 1 0
Bit 10 = 0 1 0 1 0
Bit 9 = 0 0 0 0 1
Bit 8 = 0 1 1 0 1
Analogeingang [T6]
Bit 7 = 0 0 1 1 0
Bit 6 = 0 1 0 1 0
Bit 5 = 0 0 0 0 1
Bit 4 = 0 1 1 0 1
Analogeingang [T5]
Bit 3 = 0 0 1 1 0
#1#:
#1# The analog input is not available or Bit 2 = 0 1 0 1 0
configured as real power set value or as mains Bit 1 = 0 0 0 0 1
real power actual value. Bit 0 = 0 1 1 0 1

168 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
Contents (words) Unit Note
MUX

Nr.
11/1 34 Mains voltage chain-linked U23 V × 10UNTEXPO
11/2 35 Mains voltage chain-linked U31 V × 10UNTEXPO
11/3 36 Mains voltage star U1N V × 10UNTEXPO
12/1 37 Mains voltage star U2N V × 10UNTEXPO
12/2 38 Mains voltage star U3N V × 10UNTEXPO
12/3 39 Mains frequency out off UN12/UN23/UN31 Hz × 100
13/1 40 Mains current in L1 A × 10INTEXPO
13/2 41 Mains re-active power var × 10PNTEXPO
13/3 42 Mains power factor ϕ Example: 0064H power factor cos ϕ = 1.00
0063H power factor cos ϕ = i0.99 (inductive)
FF9EH power factor cos ϕ = c0.98 (capacitive)
14/1 43 H.B. Mains power exponent PNTEXPO
L.B. Mains voltage exponent UNTEXPO
14/2 44 H.B. Mains current exponent INTEXPO
L.B. Busbar voltage exponent USSEXPO
14/3 45 Engine operating hours ( H.W.) h Double word
15/1 46 Engine operating hours ( L.W.)
15/2 47 Hours until next maintenance h
15/3 48 Engine start number
16/1 49 Operating mode( H.B.) Bit 15 = 1 Operating mode LOAD TEST
Bit 14 = 1 Operating mode STOP
Bit 13 = 1 Operating mode TEST
Bit 12 = 1 Operating mode MANUAL
Bit 11 = 1 Operating mode AUTOMATIC
Bit 10 = 1 Internal
Bit 9 = 1 Internal
Bit 8 = 1 Internal
Bit 7 =1 \
Emergency power is ON
Bit 6 =0 /
Operating mode ( L.B.)
Bit 7 =0 \
Emergency power is OFF
Bit 6 =1 /
Bit 5 =1 \
Delayed engine monitoring is ON
Bit 4 =1 /
Bit 3 =1 \
Coasting END
Bit 2 =1 /
Bit 1 =1 \
Internal
Bit 0 =1 /
16/2 50 Generator active energy ( H.W.) kWh Double word
16/3 51 Generator active energy (L.W.)
17/1 52 Battery voltage V × 10
17/2 53 Internal alarm 1 Bit 15 = 1 \
Generator overfrequency
Bit 14 = 1 /
Bit 13 = 1 \
Generator underfrequency
Bit 12 = 1 /
Bit 11 = 1 \
Generator overvoltage
Bit 10 = 1 /
Bit 9 = 1 \
Generator undervoltage
Bit 8 = 1 /
Bit 7 = 1 \
Internal
Bit 6 = 1 /
Bit 5 = 1 \
Battery undervoltage
Bit 4 = 1 /
Bit 3 = 1 \
Generator overload
Bit 2 = 1 /
Bit 1 = 1 \
Generator reverse power
Bit 0 = 1 /

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 169
Contents (words) Unit Note
MUX

Nr.
17/3 54 Internal alarm 2 Bit 15 = 1 \
Mains overfrequency
Bit 14 = 1 /
Bit 13 = 1 \
Mains underfrequency
Bit 12 = 1 /
Bit 11 = 1 \
Mains overvoltage
Bit 10 = 1 /
Bit 9 = 1 \
Mains undervoltage
Bit 8 = 1 /
Bit 7 = 1 \
Interface fault X1..X5
Bit 6 = 1 /
Bit 5 = 1 \
Internal
Bit 4 = 1 /
Bit 3 = 1 \
Internal
Bit 2 = 1 /
Bit 1 = 1 \
Mains phase/vector jump
Bit 0 = 1 /
18/1 55 Internal alarm 3 Bit 15 = 1 \
Generator overcurrent, level 2
Bit 14 = 1 /
Bit 13 = 1 \
Generator overspeed (Pickup)
Bit 12 = 1 /
Bit 11 = 1 \
Incoming power 0 kW not reached
Bit 10 = 1 /
Bit 9 = 1 \
Generator load imbalance
Bit 8 = 1 /
Bit 7 = 1 \
Generator overcurrent, level 1
Bit 6 = 1 /
Bit 5 = 1 \
Interface fault Y1..Y5
Bit 4 = 1 /
Bit 3 = 1 \
Maintenance call
Bit 2 = 1 /
Bit 1 = 1 \
Start failure
Bit 0 = 1 /
18/2 56 Internal alarm 4 Bit 15 = 1 \
Analog input [T1] - level 1
Bit 14 = 1 /
Bit 13 = 1 \
Analog input [T1] - level 2
Bit 12 = 1 /
Bit 11 = 1 \
Analog input [T2] - level 1
Bit 10 = 1 /
Bit 9 = 1 \
Analog input [T2] - level 2
Bit 8 = 1 /
Bit 7 = 1 \
Analog input [T3] - level 1
Bit 6 = 1 /
Bit 5 = 1 \
Analog input [T3] - level 2
Bit 4 = 1 /
Bit 3 = 1 \
Analog input [T4] - level 1
Bit 2 = 1 /
Bit 1 = 1 \
Analog input [T4] - level 2
Bit 0 = 1 /
18/3 57 Internal alarm 5 Bit 15 = 1 \
Analog input [T5] - level 1
Bit 14 = 1 /
Bit 13 = 1 \
Analog input [T5] - level 2
Bit 12 = 1 /
Bit 11 = 1 \
Analog input [T6] - level 1
Bit 10 = 1 /
Bit 9 = 1 \
Analog input [T6] - level 2
Bit 8 = 1 /
Bit 7 = 1 \
Analog input [T7] - level 1
Bit 6 = 1 /
Bit 5 = 1 \
Analog input [T7] - level 2
Bit 4 = 1 /
Bit 3 = 1 \
Analog input [T8] - level 1
Bit 2 = 1 /
Bit 1 = 1 \
Analog input [T8] - level 2
Bit 0 = 1 /

170 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
Contents (words) Unit Note
MUX

Nr.
19/1 58 External alarm 1 Bit 15 = 1 \
Discrete input [1]
Bit 14 = 1 /
Bit 13 = 1 \
Discrete input [2]
Bit 12 = 1 /
Bit 11 = 1 \
Discrete input [3]
Bit 10 = 1 /
Bit 9 = 1 \
Discrete input [4]
Bit 8 = 1 /
Bit 7 = 1 \
Discrete input [5]
Bit 6 = 1 /
Bit 5 = 1 \
Discrete input [6]
Bit 4 = 1 /
Bit 3 = 1 \
Discrete input [7]
Bit 2 = 1 /
Bit 1 = 1 \
Discrete input [8]
If both bits are set the input is active. Bit 0 = 1 /
19/2 59 External alarm 2 Bit 15 = 1 \
Discrete input [9]
Bit 14 = 1 /
Bit 13 = 1 \
Discrete input [A]
Bit 12 = 1 /
Bit 11 = 1 \
Discrete input [B]
Bit 10 = 1 /
Bit 9 = 1 \
Discrete input [C]
Bit 8 = 1 /
Bit 7 = 1 \
Discrete input [D]
Bit 6 = 1 /
Bit 5 = 1 \
Discrete input [E]
Bit 4 = 1 /
Bit 3 = 1 \
Discrete input [F]
Bit 2 = 1 /
Bit 1 = 1 \
Discrete input [G]
If both bits are set the input is active. Bit 0 = 1 /
19/3 60 Internal alarm 7 Bit 15 = 1 Internal
Bit 14 = 1 Internal
Bit 13 = 1 Alarm PCR3: Lambda sensor
Bit 12 = 1 Internal
Bit 11 = 1 Internal
Bit 10 = 1 Internal
Bit 9 = 1 Internal
Bit 8 = 1 Internal
Bit 7 = 1 MCB close mech. malfunction
Bit 6 = 1 GCB close mech. malfunction
Bit 5 = 1 Internal
Bit 4 = 1 Internal
Bit 3 = 1 Internal
Bit 2 = 1 Internal
Bit 1 = 1 Internal
Bit 0 = 1 Immediate stop

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 171
Contents (words) Unit Note
MUX

Nr.
20/1 61 Analog input [T1] The measured value is transmitted.
20/2 62 Analog input [T2] The measured value is transmitted.
20/3 63 Analog input [T3] The measured value is transmitted.
21/1 64 Analog input [T4] The measured value is transmitted.
21/2 65 Analog input [T5] The measured value is transmitted.
21/3 66 Analog input [T6] The measured value is transmitted.
22/1 67 Analog input [T7] The measured value is transmitted.
22/2 68 EM1-D.[2]-Alarms Bit 15 =1 EM1-D.[2] – Discrete input [8]
Bit 14 =1 EM1-D.[2] – Discrete input [7]
Bit 13 =1 EM1-D.[2] – Discrete input [6]
Bit 12 =1 EM1-D.[2] – Discrete input [5]
Bit 11 =1 EM1-D.[2] – Discrete input [4]
Bit 10 =1 EM1-D.[2] – Discrete input [3]
Bit 9 =1 EM1-D.[2] – Discrete input [2]
Bit 8 =1 EM1-D.[2] – Discrete input [1]
Bit 7 =1 Internal
Bit 6 =1 Internal
Bit 5 =1 Internal
Bit 4 =1 Internal
Bit 3 =1 Internal
Bit 2 =1 Internal
Bit 1 =1 Internal
Bit 0 =1 Internal
22/3 69 LCD-display / Pickup Currently active display message
Bit 15 =x
Bit 14 =x
Bit 13 =x A number is transmitted, please consult
Bit 12 =x the table for the "meaning of the num-
Bit 11 =x ber 69 of the telegram "Monitoring of
Bit 10 =x the active display".
Bit 9 =x
Bit 8 =x
Pick up
Bit 7 = 1
Bit 6 = 1 Firing speed reached
Bit 5 = 1 f > parameter
Bit 4 = 1
Bit 3 = 1 Speed existing
Bit 2 = 1 without pickup (pickup = OFF): f > 15
Bit 1 = 1 Hz
Bit 0 = 1 with pickup (pickup = ON): f > 5 Hz
23/1 70 Lambda set value x 100
23/2 71 Lambda actual value x 100
23/3 72 Actuator position x 0.01 %

UGNEXPO Generator voltage exponent


IGNEXPO Generator current exponent
PGNEXPO Generator power exponent
UNTEXPO Mains voltage exponent
PNTEXPO Mains power exponent
PGNWD Step conversion factor ! kW

172 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
Meaning of the number 69 of the telegram "Currently active display":

Number Meaning
0 GCB synchronization
1 MCB synchronization
2 GCB black start
3 MCB black start
4 Start
5 Start pause
6 Coasting 000s (000s:the remaining time is displayed.)
7 Engine stop!
8 Preheating
9 Purging operation
10 Initial state
11 Auxiliary coasting
12 Auxiliary advance
13 Mains settling 000s (000s:the remaining time is displayed.)
14 Lambda initial state
15 Sprinkler coasting
16 Firing
17 Internal
18 Internal
19 Internal
20 Internal
21 Internal
22 Internal
23 Internal
24 Phase rotation incorrect!
25 Start without setting GCB and simultaneous emergency power
26 Start without setting GCB
27 Sprinkler operation and simultaneous emergency power
28 Sprinkler operation
29 Emergency power
30 TEST
31 Load test
32 Internal
33 Internal
34 Internal
35 Internal
36 Internal
37 Internal
38 Internal
39 Internal
40 Internal
41 Internal
42 Internal
43 Internal
44 Internal
45 Internal
46 Internal
47 Power reduction
...
255 No display on the display (basic screen)

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 173
a.) MDEC

NOTE

The following data is transferred in the 'extended blocks' of the PCx. The data volume, which is added by
the ' extended blocks ', results that a Gateway PCK4 can only transfer the data of the first four PCx
anymore. If it is necessary that all data of all PCx is transferred, a second Gateway PCK4 has to be used.

Contents (words) Unit Note


MUX

Nr.

24/1 73 Engine speed min-1 × 0.1


24/2 74 Oil pressure bar × 0.01
24/3 75 Fail codes
25/1 76 Operating hours of the ECU h
25/2 77 Coolant temperature °C × 0.1 (+/-)
25/3 78 Oil temperature °C × 0.1 (+/-)
26/1 79 Fuel temperature °C × 0.1 (+/-)
26/2 80 Feedback speed min-1 × 0.1
26/3 81 ECU-Alarme 1 Bit 15 = 1 ST Coolant charge air
Bit 14 = 1 Coolant available
Bit 13 = 1 Coolant level
Bit 12 = 1 ECU Yellow Alarm
Bit 11 = 1 ST Oil pressure
Bit 10 = 1 Oil pressure too low
Bit 9 = 1 ECU Red Alarm
Bit 8 = 1 ST Overspeed
Bit 7 = 1 Internal
Bit 6 = 1 Internal
Bit 5 = 1 SD Coolant charge air
Bit 4 = 1 SD Coolant level
Bit 3 = 1 Oil temperature too high
Bit 2 = 1 ST Coolant temperature
Bit 1 = 1 Coolant temperature
Bit 0 = 1 AL ECU defect
27/1 82 ECU-Alarm 2 Bit 15 = 1 SD Fuel temperature
Bit 14 = 1 SD Oil temperature
Bit 13 = 1 SD Cooling water temperature
Bit 12 = 1 SD Operating hours
Bit 11 = 1 SD Fail codes
Bit 10 = 1 SD Oil pressure
Bit 9 = 1 SD Engine speed
Bit 8 = 1 Reserve (MDEC Bit 8)
Bit 7 = 1 Reserve (MDEC Bit 7)
Bit 6 = 1 Reserve (MDEC Bit 6)
Bit 5 = 1 Reserve (MDEC Bit 5)
Bit 4 = 1 Reserve (MDEC Bit 4)
Bit 3 = 1 Reserve (MDEC Bit 3)
Bit 2 = 1 Reserve (MDEC Bit 2)
Bit 1 = 1 Reserve (MDEC Bit 1)
Bit 0 = 1 SD Speed demand
27/2 83 Reserve (MDEC Bit 11)
27/3 84 Reserve (MDEC Bit 12)
28/1 85 Reserve (MDEC Bit 13)
28/2 86 Reserve (MDEC Bit 14)
28/3 87 Reserve (MDEC Bit 15) Bit 15 = 1 Internal
... ...
Bit 9 = 1 Internal
Bit 8 = 1 Interface fault Y1Y5 by MDEC
Bit 7 = 1 Internal
... ...
Bit 0 = 1 Internal
29/1 88 Reserve (MDEC Bit 16)
29/2 89 Reserve (MDEC Bit 17)
29/3 90 Reserve (MDEC Bit 18)

174 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
b.) J1939

NOTE

The following data is transferred in the 'extended blocks' of the PCx. The data volume, which is added by
the ' extended blocks ', results that a Gateway PCK4 can only transfer the data of the first four PCx
anymore. If it is necessary that all data of all PCx is transferred, a second Gateway PCK4 has to be
used.

Contents (words) Unit Note


MUX

Nr.

24/1 73 Engine speed min-1 × 0.1


24/2 74 Oil pressure bar × 0.01
24/3 75 Reserve
25/1 76 Reserve h
25/2 77 Coolant temperature °C × 0.1 (+/-)
25/3 78 Oil temperature °C × 0.1 (+/-)
26/1 79 Fuel temperature °C × 0.1 (+/-)
26/2 80 Reserve min-1 × 0,1
26/3 81 ECU-Alarm 1 Bit 15 = 1 ST Coolant charge air /#1
Bit 14 = 1 Internal
Bit 13 = 1 Coolant level /#1
Bit 12 = 1 Internal
Bit 11 = 1 ST Oil pressure /#1
Bit 10 = 1 Low oil pressure /#2
Bit 9 = 1 Internal
Bit 8 = 1 Internal
Bit 7 = 1 ST Engine protection /#1
Bit 6 = 1 ST Oil level /#1 /#2
Bit 5 = 1 Internal
Bit 4 = 1 SD Coolant level
Bit 3 = 1 Internal
Bit 2 = 1 ST Coolant temperature /#1
Bit 1 = 1 Coolant temperature /#2
Bit 0 = 1 Internal
27/1 82 ECU Alarm 2 Bit 15 = 1 SD Fuel temperature
Bit 14 = 1 SD Oil temperature
Bit 13 = 1 SD Coolant temperature
Bit 12 = 1 Internal
Bit 11 = 1 Internal
Bit 10 = 1 SD Oil pressure
Bit 9 = 1 SD Engine speed
Bit 8 = 1 Internal
Bit 7 = 1 Internal
Bit 6 = 1 Internal
Bit 5 = 1 Internal
Bit 4 = 1 Internal
Bit 3 = 1 Internal
Bit 2 = 1 Internal
Bit 1 = 1 Internal
Bit 0 = 1 Internal
27/2 83 Reserve
27/3 84 Reserve
FFxx'h = no value of ECU available
28/1 85 Coolant level %
FExx'h = Sensor fault
28/2 86 Reserve
28/3 87 Reserve Bit 15 = 1 Internal
... ...
Bit 9 = 1 Intern
Bit 8 = 1 Interface fault Y1Y5 by J1939
Bit 7 = 1 Internal
... ...
Bit 0 = 1 Internal
#1 #2
only Deutz EMR 2, only Scania EMS/S6

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 175
6.3.3 Receiving telegram

The CAN protocol for remote control of the PCx is available on request. We however
recommend to use a Gateway. The following three data words can be received by the
PCx. Please see in the manual of the GW 4 how you can control several PCx.

No. Contents (words) Unit Note

1 Generator real power set value kW see below


2 Setpoint for the generator power factor ϕ Example: 0064H power factorϕ = 1.00
0063H power factorϕ = i0.99 (inductive)
FF9EH power factorϕ = c0.98 (capacitive)
3 Control word Bit 15 Internal
Bit 14 Internal
Bit 13 Internal
Bit 12 Internal
Bit 11 Internal
Bit 10 Internal
Bit 91 Internal
Bit 8 Internal
Bit 7 Internal
Bit 6 Internal
Bit 5 Internal
Bit 4 =1 Remote acknowledgement
Bit 3 =0 Always 0
Bit 2 =0 Always 0
Bit 1 =1 Remote stop (high priority)
Bit 0 =1 Remote start

6.3.4 Notes (on interface)

a.) Coding of the current direction


The current direction can be recognized via the code word prefix. A positive transmitted
value indicates supply (power output), a negative transmitted value indicates power con-
sumption (incoming supply).

b.) Coding of the power default


The following power values may be pre-specified: fixed power (F power), outgoing/export
power (E power) and incoming/import power (I power). The real power setpoint is trans-
mitted in binary form using bits 0..13. The control argument must be transmitted in the basis
of bits 14 and 15. In this case, the following coding applies:

Control argument Bit 15 Bit 14


F power 0 1
E power 0 0
I power 1 1

Examples:
F power of 150 kW is to be compensated. The value transmitted is then:
01/00 0000 1001 0110 B # 4096 H

L power of 300 kW is to be compensated. The value transmitted is then:


00/00 0001 0010 1100 B # 012C H

I power of 600 kW is to be compensated. Negative power is transmitted. The value


transmitted is then:
11/11 1101 1010 1000 B # FDA8 H

176 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
6.4 Measured quantities and technical data

6.4.1 Measured quantities

Measuring variable Display and range Note

Frequency
Generator, busbar fL1Gen/SS, fL2Gen/SS, fL3Gen 15.0..85.0 Hz
Mains fL1Mains, fL2Mains, fL3Mains 40.0..85.0 Hz
Voltage
UL1, UL2, UL3, UL12, UL23, UL31 0..520 V Adjustable transformer ratio
current
Generator, mains IL1Gen/Mains, IL2Gen, IL3Gen 0..9,999 A -
Maximum value IL1Gen, IL2Gen, IL3Gen 0..9,999 A Slave pointer
Real power
Total actual real power value -32.0..32.0 MW -
Re-active power
Actual value in L1, L2, L3 -32.0..32.0 Mvar -
cos
Actual value of power factor L1 generatorϕ/mains i0.00..1.00..c0.00 -
Miscellaneous
Active energy 0..4,200 GWh Not calibrated by PTB
Operating hours 0..65,000 h -
Maintenance call 0..9,999 h -
Start counter 0..32,750 → 1 -
Battery voltage 10..30 V -
Pickup speed fN ± 40 % -
Analog inputs
Pt100 0..250 °C Not calibrated by PTB
Pt1000 0..150 °C Not calibrated by PTB
0..180 Ω Freely scaleable For VDO pulsar
0..360 Ω Freely scaleable For VDO pulsar
PTC Freely scaleable -
0 /4.. 20 mA Freely scaleable -
0 ..10 V Freely scaleable -
0.. 150 mV Freely scaleable -

a.) Reference conditions for the recorded quantities


*
The data apply to the following reference conditions:

- Input voltage = sinusoidal rated voltage


- Input current = sinusoidal rated current
- Frequency = rated frequency ± 2 %
- Supply voltage = rated voltage ± 2 %
- Power factor ϕ = 1
- Ambient temperature 23 °C ± 2 K
- Warm-up period = 20 minutes.

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 177
6.4.2 Technical data

Measuring values - Measuring voltages ......................................[1] 100..115 VAC, [4] 380..440 VAC
- Measuring voltages .................................. [1] max. 150 Vac, [4] max. 300 Vac
- Measuring currents.................................................................... ../1 A, ../5 A
- Measuring frequency................................................ 50/60 Hz (40.0..70.0 Hz)
- Accuracy ........................................................................................... Class 1

Ambient variables - Power supply ................12/24 Vdc (9.5..32 VDC), Intrinsic consumption max. 20 W
- Ambient temperature ....................................................................... -20..70 °C
- Ambient humidity..............................................................95 %, non-condensing

Measuring inputs • Voltage ...............................................................................Resistances 0.1 %


- Continuous input voltage..................................................................... 2.0 × UN
- Linear measuring range up to............................................................... 1.3 × UN
- Input resistance ......................................................... [1] 0.21 MΩ, [4] 0.7 MΩ
- Maximum power consumption per path .................................................. 0.15 W

• Current .......................................................................... metalically separated


- Maximum continuous current .................................... IGen = 3.0 × IN, IMains = 1.5 × IN
- Power consumption..........................................................................< 0.15 VA
- Rated short time current (1 s) ........................ [..1/ A] 50.0 × IN, [../5 A] 10.0 × IN

Discrete inputs - Electrically isolated


- Input range.......................................................................................6..32 VDC
- Input resistance .............................................................................. ca. 6.8 kΩ

Potential-free outputs - Electrically isolated


- Contact material..................................................................................AgCdO
- Load (GP) (UCont, relay output) AC.......................2.00 Aac@250 Vac
DC.........................2.00 Adc@24 Vdc
0.36 Adc@125 Vdc
0.18 Adc@250 Vdc
- Inductive load (PD) (UCont, relay output) AC...........................................B300
DC.........................1.00 Adc@24 Vdc
0.22 Adc@125 Vdc
........................................................................................0.10 Adc@250 Vdc

Analog inputs - Freely scaleable ....................................................................... resolution 10 Bit


- Pt100/Pt1000 Input .......................for measuring resistances according to IEC 751
2/3-conductor measurement, 0..200 °C,
- 0/4..20 mA input....................................... Difference measurement, load 150 Ω

Analog outputs - at rated output .......................................................................... freely scalable,


electrically isolated, insulation voltage 3,000 VDC
0..5 V, ±5 V, 0..10 V, 0..20 mA
- Resolution PWM .................................................8/12 bit (depending on model)
- 0/4..20 mA output ..........................................................maximum load 500 Ω

Pickup - Input ..............................................................................capacitively separated


- Input impedance .................................................................min. approx. 17 kΩ
- Input voltage.................................................................................. 875 mV eff

178 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
Interface Service interface
- Version ............................................................................................... RS232
- Signal level .............................................................................................. 5 V
level conversion and separation by FL-CABLE-RS232

CAN bus interface ........................................................... galvanically separated


- Insulation voltage.............................................................................1,500 Vdc
- Version ............................................................................................ CAN bus
- Internal line termination .............................................................................. n/a
Battery - Type .................................................................................................... NiCd
- Life (for operation without power supply) ....................................... approx. 5 years
- Battery change in place ...................................................................not possible

Housing - type ......................................................................... APRANORM DIN 43 700


- Dimensions (B×H×T)........................................................ 144 × 144 × 118 mm
- Front cutout (B×H) ................................................. 138 [+1,0] × 138 [+1,0] mm
- Connection ... 1.5 mm² or 2.5 mm² screw terminals depending on the plug connector
- Weight......................................................... depending on model, ca. 1,000 g

Protection - disturbance test (CE)........................ Tested according to valid EN codes of practice


- Degree of protection .................................... IP42 from front with proper installation
IP54 from front with gasket
............................................................................................ IP21 from behind
- Front foil ................................................................................ insulating surface
- Listings............................................. CE approved; UL listing for ordinary locations
- Type approval ................................................. UL-/cUL-Listed, Ordinary Locations

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 179
6.5 Dimensions

Housing Type APRANORM DIN 43 700


Dimensions (B×H×T) 144 × 144 × 118 mm
Front cutout (B×H) 138 × 136 mm
Connection screw terminals depending on the plug connector 1.5 mm² or 2.5 mm²
Degree of protection IP 21
Weight depending on model, ca. 1,000 g

144,0 mm
32,0 mm
12,0 mm

Parameterizing plug

42,0 mm
8,0 mm

48 25

Y1 Y5 X1 X5 120 127

90 93 99 105 111 113

144,0 mm
136,0 mm

83 60

50 54

01 24

136,0 mm 111,0 mm

PCMx 2002-08-06 PCx Abmessungen SEG pcmxseg-3202-ab.skf

180 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
7 Parameter list

PCL1 & PCM1-G & PCM1-M - Genset Control


Version ________________________________________________________________________________________________
Project ________________________________________________________________________________________________
Item number ______________________________________________________________________ Date ______________

Parameter Code
Option Adjustment range Standard settings Customer settings
1. line text 2. line level

GENERAL
Software version - V x.xxxx - - 0
Entercode 0..9.999 XXXX 0
PCMx/H Direct para YES/NO YES %Y %N %Y %N 2
.. Generator-Nummer 1..14 1 2
PCMx/H Language first/second first %f %s %f %s 0
Service display ON/OFF ON % ON % OFF % ON % OFF 0
PCMx/H check event list YES/NO YES %Y %N %Y %N 2

GENERATOR AND MAINS ENVIRONMENT CONFIGURATION


Configure measuring YES/NO Yes %Y %N %Y %N 2
Generator number 1..8 1 2
Generator freq. f set 40.0..70.0 Hz 50.0 Hz 2
Rated system frequency 50.0..60.0 Hz 50.0 Hz 2
Gen.volt.transf. secondary 50..125/50..480 V 400 V 2
Gen.volt.transf. primary 0.05..65.0 kV 0.40 kV 2
Bus.volt.transf. secondary 50..125/50..480 V 400 V 2
Bus.volt.transf. primary 0.05..65.0 kV 0.40 kV 2
mains volt.trans secondary 50..125/50..480 V 400 V 2
mains volt.trans primary 0.05..65.0 kV 0.40 kV 2
Gen.voltage U set 50..125/50..480 V 100/400 V 2
Rated voltage in system 50..125/50..480 V 100/400 V 2
Volt.meas./mon. Threewire 4/4 4/4 % 4/4 % 4/4 2
4/3 % 4/3 % 4/3
3/3 % 3/3 % 3/3
Current transf. generator 10..7,000/x A 500/x A 2
Power measuring gen. singlephase/threephase threepase 2
Rated power generator 5..9,999 kW 200 kW 2
Rated current generator 10..7,000 A 300 A 2
Analog in Pmains OFF / T{x} OFF
Analog in Pmains 0-20 mA / 4-20 mA 0-20 mA
Analog in Pmains 0% -9,990..0..+9,990kW/ -200 kW
6,900..0..+6,900 kW
Analog in Pmains 100% -9,990..0..+9,990kW/ 200 kW
6,900..0..+6,900 kW
Current transf. mains 5..7,000/x A 500/x A 2
PCN4 mode ON/OFF OFF % ON % OFF % ON % OFF 2
Rated power in system 0..16,000kW 1,600 kW 2
Define level 1 code 0..9999 0001 2
Define level 2 code 0..9999 0002 2

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 181
CONTROLLER CONFIGURATION
Configure controller YES/NO YES %Y %N %Y %N 2
PCMx Power controller Pset1 C/I/E 0..6,900 kW F 50 kW 1
PCMx Power controller Pset2 C/I/E 0..6,900 kW F 80 kW 1
A Initial state Frequency 0..100 % 0% 2
Freq.controller ON/OFF ON % ON % OFF % ON % OFF 2
f-contr. active at 0.0..70.0 Hz 40.0Hz 2
Delay time for f-contr. 0...999 s 5s 2
Freq.controller ramp 1..50 Hz/s 10 Hz/s 2
F/P contr.type Three- Analog 2
step/Analog/PWM
Freq.controller deadband 0.02..1.00 Hz 0.03 Hz 2
Freq.controller time pulse> 10.. 250 ms 80 ms 2
Freq.controller gain Kp 0.1..99.9 20.0 2
F/P contr.output see table +/-10 V 2
Level PWM 3.0..10.0V 3,0 V
Stepper sign.frq (min.) 0..100% 0%
Stepper sign.frq (max.) 0..100% 100%
A Freq.controller gain Kpr 1..240 20 2
.. Freq.controller reset Tn 0.0..60.0 s 1.0 s 2
A Freq.controller derivat.Tv 0.00..6.00 s 0.00 s 2

182 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
Parameter Code
Option Adjustment range Standard settings Customers settings
1. line text 2. line level

CONTROLLER CONFIGURATION
A Starting point voltage 0..100 % 0% 2
Volt.controller ON/OFF ON % ON % OFF % ON % OFF 2
Start voltage U control. 50..400 V 2
Delayed. Start U contr. 0..999 s 2
V/Q contr.type Three-step/Analog Analog 2
Volt.controller dead band 0.1..15.0/0.5..60.0 3.5 V 2
V
Volt.controller time pulse> 20.. 250 ms 80 ms 2
Volt.controller gain Kp 0.1..99.9 20.0 2
V/Q contr.output see table +/-10 V 2
Stepper sign.vol. (min.) 0..100% 0%
Stepper sign.vol. (max.) 0..100% 100%
A Volt.controller gain Kpr 1..240 20.0 2
.. Volt.controller reset Tn 0.0..60.0 s 1.0 s 2
A Volt controller derivat.Tv 0.00..6.00 s 0.0 s 2
PCMx Pow.fact.contr. ON/OFF OFF % ON % OFF % ON % OFF 2
.. Pow.fact.contr. setpoint i0.70..1.00..c0.70 1.00 1
.. Pow.fact.contr. dead band 0.5..25.0 % 0.5 % 2
.. Pow.fact.contr. gain Kp 0.1..99.9 20.0 2
PCMx/A Pow.fact.contr. gain Kpr 1..240 20 2
.. Pow.fact.contr. reset Tn 0.0..60.0 s 1.0 s 2
PCMx/A Pow.fact.contr. derivat.Tv 0.0..6.0 s 0.0 s 2
PCMx Power controller ON/OFF ON % ON % OFF % ON % OFF 2
.. power controller ramp 0..100 %/s 10 %/s 2
.. Power limit P max. 10..120 % 100 % 2
.. Power limit P min. 0..50 % 0% 2
.. Power setpoint external OFF / T{x} % ON % OFF % ON % OFF 2
.. Analog input 0-20/4-20 mA 4-20 mA 2
.. Ext.setpoint 0% C/I/E 0..9,999 kW F0 kW 2
.. Ext.setpoint 100% C/I/E 0..9,999 kW F200 kW 2
.. Power controller dead band 0.1..25.0 % 0.5 % 2
.. Power controller gain Kp 0.1..99.9 20.0 2
.. Powercontr. dead band ratio 1.0..9.9 2.0 2
PCMx/A Power controller gain Kpr 1..240 20 2
.. Power controller reset Tn 0.0..60.0 s 1.0 s 2
PCMx/A Power controller derivat. Tv 0.0..6.0 s 0.0 s 2
PCMx Warm up load limit value 5..110 % 15 % 2
.. Warm up load time 0..600 s 0s 2
.. Active power load-share ON/OFF OFF % ON % OFF % ON % OFF 2
.. Act. load share factor 10..99 % 50 % 2
.. Reactive power load share ON/OFF OFF % ON % OFF % ON % OFF 2
PCMx React.load share factor 10..99% 50 % 2

LOAD MANAGEMENT CONFIGURATION


PCMx Configure automatic YES/NO NO %Y %N %Y %N 2
.. Loadd.start/stop at ter.3 ON/OFF OFF % ON % OFF % ON % OFF 2
.. Loadd.start/stop at ter.5 ON/OFF OFF % ON % OFF % ON % OFF 2
.. Minimum load generator 0..6,900 kW 15 kW 2
.. Add-on delay mains oper. 0..999 s 1s 2
.. Shed-off delay mains oper. 0..999 s 3s 2
.. Hysteresis add- on/off op. 0..9,999 kW 5 kW 2
.. Reserve power mains op. 0..9,999 kW 10 kW 2
.. Priority of generators 0..14 0 2
.. Reserve power isol.op. 0..9,999 kW 20 kW 2

.. Add-on delay isol.op. 0..999 s 1s 2


PCMx Shed-off delay isol.op. 0..999 s 4s 2

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 183
Parameter Code
Option Adjustment range Standard setting Customer settings
1. line text 2. line level

LOAD MANAGEMENT CONFIGURATION


PCMx/H CHP temp.depend. at ter.3 ON/OFF OFF % ON % OFF % ON % OFF 2
.. CHP temp.depend. at ter.5 ON/OFF OFF % ON % OFF % ON % OFF 2
.. CHP start-up temperat. 0..255 °C 30 °C 2
.. CHP shut-down temperat. 0..255 °C 60 °C 2
.. CHP start-up delay 0..255 s 1s 2
.. reduce of load step 1 at 0..255 °C 60 °C 2
.. reduce of load step 2 at 0..255 °C 70 °C 2
PCMx/H reduce of load per step 0..100 % 10 % 2
Mains error stop eng. ON/OFF OFF % ON % OFF % ON % OFF 2
PCx/H Control via COM X1X5 ON/OFF OFF % ON % OFF % ON % OFF 2
Supervision COM X1X5 ON/OFF OFF % ON % OFF % ON % OFF 2
Ackn. F2,F3 via COM interf ON/OFF OFF % ON % OFF % ON % OFF

CIRCUIT BREAKER CONFIGURATION


Configure breaker YES/NO NO %Y %N %Y %N 2
Breaker logic EXTERNAL PARALLEL % external % external 2
PARALLEL % parallel % parallel
OPEN TRANSIT. % open tran. % open tran.
CLOSED TRANSIT. % closed tran. % closed tran.
INTERCHANGE % interchange % interchange
Add-on/off ramp max.time 0..999 s 20 s 2
Open GCB with F2 max.time 0..999 s 10 s 2
GCB close.relay Impulse Impulse/Constant Impulse %i %c %i %c 2
GCB open relay NO-/NC-contact NC-contact 2
Synchronize df max .0.02...0.49 Hz 0.20 Hz 2
Synchronize df min 0.0..-0.49 Hz -0.10 Hz 2
Synchronize dV max 1..20/2..60 V 10 V 2
Synchronize time pulse> 0.02..0.26 s 0.24.s 2
Closing time GCB 40.. 300 ms 80 ms 2
Closing time MCB 40.. 300 ms 80 ms 2
Automat.breaker deblocking ON/OFF ON % ON % OFF % ON % OFF 2
Sync.time contr. ON/OFF ON % ON % OFF % ON % OFF 1
Sync.time contr. delay 10..999 s 180 s 1
GCB dead bus op. ON/OFF ON % ON % OFF % ON % OFF 2
GCB dead bus op. df max 0.05..5.00 Hz 0.45 Hz 2
GCB dead bus op. dV max 1..15/2..60 V 40 V 2
GCB dead bus op. max.time 0..999 s 10 s 2
MCB dead bus op. ON/OFF ON % ON % OFF % ON % OFF 2
Supervision GCB ON/OFF ON % ON % OFF % ON % OFF 2
Supervision MCB ON/OFF ON % ON % OFF % ON % OFF 2
Mains decoupling via GCB/MCB GCB 2
Mains settling time 0..999 s 10 s 2
Switch MCB in STOP mode YES/NO %Y %N %Y %N

EMERGENCY POWER CONFIGURATION


Configure emergency YES/NO NO %Y %N %Y %N 2
Emergency power ON/OFF ON % ON % OFF % ON % OFF 2
Emergency power start del. 0.5..99.9 s 3.0.s 2
Mains settling time 0..999 s 10 s 2

184 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
Parameter Code
Option Adjustment range Standard setting Customer settings
1. line Text 2. line level

WATCHDOG CONFIGURATION
Configure monitoring YES/NO Yes %Y %N %Y %N 2
Gen.power monit. ON/OFF OFF % ON % OFF % ON % OFF 2
Gen.power monit. resp.val1 0..9,999 kW 100 kW 2
Gen.power monit. hyst.lv1 0..999 kW 10 kW 2
Gen.power monit. delay lv1 0..999 s 1s 2
Gen.power monit. resp.val2 0..9,999 kW 100 kW 2
Gen.power monit. hyst.lv2 0..999 kW 10 kW 2
Gen.power monit. delay lv2 0..999 s 1s 2
Mains power mon. ON/OFF OFF % ON % OFF % ON % OFF 2
Mains power mon. res.val. I/E 0..9,999 kW 100 kW 2
Mains power mon. hysteresis 0..999 kW 10 kW 2
Mains power mon. delay 0..650 s 1s 2
Overload monit. ON/OFF OFF % ON % OFF % ON % OFF 2
Gen.overload MOP resp.value 80..150 % 120 % 2
Gen.overload MOP delay 0..99 s 1s 2
Gen.overload IOP resp.value 80..150 % 120 % 2
Gen.overload IOP delay 0..99 s 1s 2
Rev./red.power monitoring ON/OFF OFF % ON % OFF % ON % OFF 2
Rev./red.power resp.value -99..0..+99 % -10 % 2
Rev./red.power delay 0.0..9.9. s 1.0 s 2
Load unbalanced monitoring ON/OFF OFF % ON % OFF % ON % OFF 2
Load unbalanced max. 0..100 % 30 % 2
Load unbalanced delay 0.02..99.98 s 1.00 s 2
Gen.overcurrent monitoring ON/OFF OFF % ON % OFF % ON % OFF 2
Gen.overcurrent limit 1 0..300 % 110 % 2
Gen.overcurrent delay 1 0.02..99.98 s 1.00 s 2
Gen.overcurrent limit 2 0..300 % 120 % 2
Gen.overcurrent delay 2 0.02..99.98 s 0.04.s 2
Gen.frequency- monitoring ON/OFF ON % ON % OFF % ON % OFF 2
Gen.overfreq. f> xxx xxx 2
Gen.overfreq. delay 0.02..9.98 s 0.30 s 2
Gen.underfreq. f< xxx xxx 2
Gen.underfreq. delay 0.02..9.98 s 0.30 s 2
Engine overspeed > 0..9,999 rpm 1,900 rpm 2
Gen.voltage monitoring ON/OFF ON % ON % OFF % ON % OFF 2
Gen.overvoltage U> xxx xxx 2
Gen.overvoltage delay 0.02..9.98 s 0.30 s 2
Gen.undervoltage U< xxx xxx 2
Gen.undevoltage delay 0.2..9.98 s 0.30 s 2
Mains frequency monitoring ON/OFF ON % ON % OFF % ON % OFF 2
Mains overfreq. f> xxx xxx 2
Mains overfreq. delay 0.02..9.98 s 0.06 s 2
Mains underfreq. f< xxx xxx 2
Mains underfreq. delay 0.02..9.98 s 0.06 s 2
Mains voltage monitoring ON/OFF ON % ON % OFF % ON % OFF 2
Mains overvolt. U> xxx xxx 2
Mains overvolt. delay 0.02..9.98 s 0.06 s 2
Mains undervolt. U< xxx xxx 2
Mains undervolt. delay 0.02..9.98 s 0.06 s 2
Phase shift monitoring ON/OFF ON % ON % OFF % ON % OFF 2
Monitoring one-/threephase three-..one-/threephase threephase 2
Phase shift one-phase 3..30 ° 9° 2
Phase shift three-phase 3..30 ° 9° 2
Mains settling time 0..999 s
Batt.undervolt. U< 9.5..30.0 V 10.0 V 2
Batt.undervolt. delay 0..99 s 10 s 2

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 185
Parameter Code
Option Adjustment range Standard setting Customer settings
1. line Text 2. line level

DISCRETE INPUTS CONFIGURATION


Configure dig.inputs YES/NO NO %Y %N %Y %N 2
Dig.input 1234 function E/D EEEE 2
Dig.input 1234 delay 0..9 s 0000 2
Delayed by 1234 eng.speed Y/N NNNN 2
Dig.input 1234 error class 0..3 3210 2
Dig.input 5678 function E/D EEEE 2
Dig.input 5678 delay 0..9 0000 2
Delayed by 5678 eng.speed Y/N NNNN 2
Dig.input 5678 error class 0..3 3210 2
Dig.input 9ABC function E/D EEEE 2
Dig.input 9ABC delay 0..9 0000 2
Delayed by 9ABC eng.speed Y/N NNNN 2
Dig.input 9ABC error class 0..3 3210 2
Dig.input DEFG function E/D EEEE 2
Dig.input DEFG delay 0..9 0000 2
Delayed by DEFG eng.speed Y/N NNNN 2
Dig.input DEFG error class 0..3 3210 2
Errortxt.term.61 Any EMERGENCY OFF 2
Errortxt.term.62 Any Terminal 62 2
Errortxt.term.63 Any Terminal 63 2
Errortxt.term.64 Any Terminal 64 2
Errortxt.term.65 Any Terminal 65 2
Errortxt.term.66 Any Terminal 66 2
Errortxt.term.67 Any Terminal 67 2
Errortxt.term.68 Any Terminal 68 2
Errortxt.term.69 Any Terminal 69 2
Errortxt.term.70 Any Terminal 70 2
Errortxt.term.71 Any Terminal 71 2
Errortxt.term.72 Any Terminal 72 2
Errortxt.term.73 Any Terminal 73 2
Errortxt.term.125 Any Terminal 125 2
PCMx Errortxt.term.126 Any Terminal 126 2
PCMx Errortxt.term.127 Any Terminal 127 2
Firing speed by by Term.62 ON/OFF OFF % ON % OFF % ON % OFF 2
Op.mode blocked by Term.63 ON/OFF OFF % ON % OFF % ON % OFF 2
Breaker logic by Term.64 ON/OFF OFF % ON % OFF % ON % OFF 2
Breaker logic EXTERNAL EXTERNAL % external % external 2
PARALLEL % parallel % parallel
OPEN TRANSIT. % open tran. % open tran.
CLOSED TRANSIT. % closed tran. % closed tran.
INTERCHANGE % interchange % interchange
Manual synchr. by Ter.66 ON/OFF OFF % ON % OFF % ON % OFF 2
Close GLS asap by Ter.67 ON/OFF OFF % ON % OFF % ON % OFF 2
Function term.6 Sprinkler Ext. acknowledge % Sprinkler % Sprinkler 2
Engine enable % Engine rel. % Engine rel.
ext. acknowledge % ext. ackn. % ext. ackn.
Engine block % Engine blk. % Engine blk.
No CB by start % No CB start % No CB start
Start withno GCB cool down ON/OFF 2
Sprinkler shutd. F1 aktive ON/OFF 2

186 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
Parameter Code
Option Adjustment range Standard setting Customer settings
1. line Text 2. line level

ANALOG INPUTS CONFIGURATION


Configure analg.inp. YES/NO NO %Y %N %Y %N 2
Temperature 1 Pt100 ON/OFF ON % ON % OFF % ON % OFF 2
***name**** OOO°C Any 2
Limit warning 0..200 °C 80 °C 2

Limit shutdown 0..200 °C 90 °C 2


Delay limit 1/2 0..650 s 1s 2
Monitoring for high/low limit mon. high limit mon. %h %l %h %l 2
Temperature 2 Pt100 ON/OFF ON % ON % OFF % ON % OFF 2
***name**** OOO°C Any 2
Limit warning 0..200 °C 80 °C 2

Limit shutdown 0..200 °C 90 °C 2


Delay limit 1/2 0..650 s 1s 2
Monitoring for high/low limit mon. high limit mon. %h %l %h %l 2
Analog input 3 scalable ON/OFF ON % ON % OFF % ON % OFF 2
Name and unit Any 2
Analog input 3 0-20mA/4-20mA 4-20 mA 2
Value at 0% -9,999..0..9,999 0 2
Value at 100% -9,999..0..9,999 100 2
Limit warning value -9,999..0..9,999 80 2
Limit shutdown value -9,999..0..9,999 90 2
Delay limit 1/2 0..650 s 1s 2
Monitoring for high/low limit mon. high limit mon. %h %l %h %l 2
Temperature 4 Pt100 ON/OFF ON % ON % OFF % ON % OFF 2
***name**** OOO°C Any 2
Limit warning 0..200 °C 80 °C 2

Limit shutdown 0..200 °C 90 °C 2


Delay limit 1/2 0..650 s 1s 2
Monitoring for high/low limit mon. high limit mon. %h %l %h %l 2
PCMx/H Temperature 5 Pt100 ON/OFF ON % ON % OFF % ON % OFF 2
.. ***name**** OOO°C Any 2
.. Limit warning 0..200 °C 80 °C 2

.. Limit shutdown 0..200 °C 90 °C 2


.. Delay limit 1/2 0..650 s 1s 2
.. Monitoring for high/low limit mon. high limit mon. %h %l %h %l 2
.. Temperature 6 Pt100 ON/OFF ON % ON % OFF % ON % OFF 2
.. ***name**** OOO°C Any 2
.. Limit warning 0..200 °C 80 °C 2

.. Limit shutdown 0..200 °C 90 °C 2


.. Delay limit 1/2 0..650 s 1s 2
.. Monitoring for high/low limit mon. high limit mon. %h %l %h %l 2
Analog input 7
.. scalable ON/OFF ON % ON % OFF % ON % OFF 2
Name and unit
.. Any 2
Analog input 7
.. 0-20mA/4-20mA 4-20 mA 2
Value at
.. 0% -9,999..0..9,999 0 2
Value at
.. 100% -9,999..0..9,999 100 2
Limit warning
.. value -9,999..0..9,999 80 2
Limit shutdown
.. value -9,999..0..9,999 90 2
Delay
.. limit 1/2 0..650 s 1s 2
PCMx/H Monitoring for high/low limit mon. high limit mon. %h %l %h %l 2
PCLx Ana.in 1234 Sv.del. Y/N NNNN 2
PCMx/LAna.in 1234 control Y/N NNNN 2
PCMx/H Ana.in 12345678 Sv.del. Y/N NNNNNNNN 2
PCMx/H Ana.in 12345678 control Y/N NNNNNNNN 2

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 187
Parameter Code
Option Adjustment range Standard setting Customer settings
1. line Text 2. line level

ANALOG OUTPUTS CONFIGURATION


Configure outputs YES/NO NO %Y %N %Y %N 2
Analg.out.120121 parameter 0..22 1 2
Analg.out.120121 0-00mA 0-20mA/4-20mA 0-20 mA 2
Analg.out.120121 0% 0..9,990 0 2
Analg.out.120121 100% 0..9,990 200 2
Analg.out.122123 Parameter 0..22 1 2
Analg.out.122123 0-00 mA 0-20mA/4-20mA 0-20 mA 2
Analg.out.122123 0% 0..9,990 0 2
Analg.out.122123 100% 0..9,990 200 2
Assignm.relay 1 According to list 1 2
Assignm.relay 2 According to list 2 2
Assignm.relay 3 According to list 3 2
Assignm.relay 4 According to list 4 2
PCMx Assignm.relay 5 According to list 5 2
.. Assignm.relay 6 According to list 84 2
PCMx Assignm.relay 7 According to list 85 2

ENGINE CONFIGURATION
Configure engine YES/NO Yes %Y %N %Y %N 2
Aux.services prerun 0..999 s 0s 2
Aux.services postrun 0..999 s 0s 2
Start-stop-logic for DIESEL DIESEL % DIESEL % DIESEL 2
GAS % GAS % GAS
EXTERNAL % EXTERNAL % EXTERNAL
Min.speed for ignit. 0..999 rpm 100 2
Gas Ignition delay 0..99 s 3s 2
.. Gasvalve delay 0..99 s 5s 2
Max. attempts to start 1..6
Max. numbers unint.Stops 0..25
.. Starter time 2..99 s 5s 2
.. Start pause time 1..99 s 8s 2
.. f lower before start ON/OFF OFF % ON % OFF % ON % OFF 2
Gas time f lower bef.start 0..999 s 5s 2
Diesel Preglow time 0..99 s 3s 2
Max. attempts Start 1..6
Max. numbers unint.Stops 0..25
.. Starter time 2..99 s 5s 2
.. Start pause time 1..99 s 8s 2
.. f lower before start ON/OFF OFF % ON % OFF % ON % OFF 2
.. time f lower bef.start 0..999 s 5s 2
Diesel Start-stop-logic operating/stop magn. operating magnet % op % st % op % st 2
Cool down time 0..999 s 30 s 2
Delayed engine monitoring 1..99 s 8s 2
Firing speed reached f > 5..70 Hz 15 Hz 2
Pickup input ON/OFF OFF % ON % OFF % ON % OFF 2
Gen.rated speed 0..3,000 rpm 1,500 rpm 2
Number of pickup teeth 30..280 96 2

COUNTER CONFIGURATION
Configure counters YES/NO Yes %Y %N %Y %N 2
Service interval in 0..9,999 h 300 h 1
Set oper.hours counter 0..65,000 h 0h 2
Set start counter 0..32,000 0 2
kWh counter set in kWh/MWh kWh 2
kWh counter set 0..65,500 kWh/MWh 0 kWh 2
PCMx/H Time 00:00..23:59 00:00 2
.. Year,month 00..99.01..12 00.00 2
PCMx/H Day/weekday 01..31/1..7 00.0 2
000 000 000 000 max. Gen.strom -

188 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
INTERFACE ENGINE BUS CONFIGURATION
s Configure engine bus YES/NO NO %Y %N %Y %N 2
CAN-Baudrate 100/125/250/500 250 1
EM1-D on bus YES/NO NO %Y %N %Y %N 2
PCR3 on bus YES/NO NO %Y %N %Y %N 2
ECU interface monitoring YES/NO NO %Y %N %Y %N 2
MDEC Off / Vis./Ct. / Vis. / OFF 2
Ct.
MDEC protocol V302 / V303 / V304 V302 2
max. speed loop 0..999 min-1 100 2
J1939 AUS/Stand./EMR2/S6 OFF 2
J1939 unit numb. 0..255 0 2

HB_PCL1/PCM1-M/PCM1-G_09.04_GB 189
8 Index
Accuracy ............................................................... 175 Brief explanation.....................................................67 ATS ..................................................................... 49
Alarms .................................................................... 62 Display .................................................................74 Emergency power .................................................. 50
Acknowledgement .................................................. 64 Display touch .........................................................70 GCB black start ..................................................... 42
Alarm classes ......................................................... 62 LEDs .....................................................................69 GCB open ............................................................ 45
Alarm names.......................................................... 63 Operation of the Power Circuit Breakers ......................72 GCB synchronization .............................................. 41
Analog controller Pressure-Sensitive Front Membrane..............................66 Interchange synchronization...................................... 49
Configuration......................................................... 55 Push-buttons ...........................................................70 MCB black start ..................................................... 44
Real power............................................................ 96 Display messages ......................................................33 MCB open............................................................ 45
Settings................................................................. 56 Alarm messages......................................................35 MCB synchronization .............................................. 43
Analog input .................................................... 12, 139 Analog inputs .........................................................35 Operation in parallel with the mains........................... 48
Configuration....................................................... 137 Coasting ...............................................................33 Overlap synchronization .......................................... 49
Analog output manager .................................... 141, 158 Connection fault GCB..............................................35 Sprinkler operation ................................................. 53
Analog outputs.......................................................... 15 Connection fault MCB .............................................35 Operating hour counter ............................................ 148
Appendix .............................................................. 158 Digital Inputs ..........................................................35 Operating magnet .................................................. 145
ATS 49 Function messages ..................................................33 Operating mode
Automatic 1 ............................................................. 28 GCB malfunction ....................................................35 Automatic ............................................................. 73
Automatic 2 ............................................................. 28 Interface fault X1..X5 ...............................................35 Manual ................................................................ 73
Battery voltage monitoring......................................... 131 Interface fault Y1..Y5 ...............................................35 STOP ................................................................... 72
Black start .............................................................. 115 Load test mode: ......................................................33 Test ..................................................................... 73
Breaker connect time monitoring................................... 47 Mains settling .........................................................33 Operating mode selector switch................................... 73
Breaker Pickup time monitoring..................................... 47 Maintenance..........................................................36 Operation in parallel with the mains ............................. 48
CB logic................................................................ 110 MCB malfunction ....................................................35 Options
ATS...................................................................... 49 Monitor messages ...................................................35 A2 - Analog outputs .................................15, 141, 158
CLOSED TRANSITION .................................... 49, 111 Motor stop !...........................................................33 Qf - Analog controller.............................................. 55
EXTERNAL ............................................. 50, 111, 112 Pickup/Frequency ...................................................35 Qu - Analog controller ............................................. 55
INTERCHANGE ............................................. 49, 111 Power reduction......................................................33 Sb - Interface ....................................................... 163
OPEN TRANSITION ....................................... 49, 111 Reference power<>0...............................................35 Sf - CAN bus................................................163, 174
PARALLEL ............................................... 48, 111, 112 Relay messages ......................................................33 T7 - Analog inputs ...........................................12, 137
Centralized alarm...................................................... 32 Shutoff malfunction ..................................................36 Tz - Temperature dependent start/stop...................... 107
Change setpoint ....................................................... 71 Sprinkler coasting....................................................33 Overcurrent monitoring............................................. 124
Circuit breaker monitoring ........................................... 47 Sprinkler operation ..................................................33 Overlap synchronization............................................. 49
Coasting time ......................................................... 146 Sprinkler+Emergency power......................................33 Overload monitoring ............................................... 122
Code levels.............................................................. 76 Start failure ............................................................36 Overshoot ............................................................... 55
Command Start pause ............................................................33 Parameter list ......................................................... 179
close CB ............................................................... 32 Start without GCB ...................................................33 Part-load lead........................................................... 98
close GCB ............................................................ 32 Synchronizatin fault MCB .........................................35 Password protection .................................................. 76
close MCB ............................................................ 32 Synchronization fault GCB ........................................35 Phase position .......................................................... 70
open CB ............................................................... 32 Test mode..............................................................33 Phase/vector shift monitoring .................................... 130
open GCB ............................................................ 32 ungewollter Stop .....................................................36 Pickup .......................................................13, 61, 147
open MCB ............................................................ 32 Unintended stop......................................................36 Plausibility control.................................................... 147
Commissioning ....................................................... 156 DPC........................................................................77 Power circuit breaker configuration ............................. 110
Configuration EM1-D Expansion Board.............................................61 Power circuit breaker logic........................................ 110
Basic settings ......................................................... 82 Emergency power..............................................50, 118 Power factor controller ............................................... 95
Controller .............................................................. 87 Mains failure ..........................................................50 Power monitoring.....................................120, 121, 123
External setpoint value ............................................. 96 Engine start ............................................................149 Power protection..................................................... 121
Frequency controller ................................................ 89 Engine type ............................................................144 Preheating ..........................................................31, 33
Load/var sharing.................................................... 99 Event log .................................................................79 Pt100 input ........................................................... 138
Measuring variables ................................................ 84 EXTERNAL ................................................................50 Rated system frequency .............................................. 82
Part-load lead ........................................................ 98 External reset ............................................................29 Readiness for operation.............................................. 31
Real power controller............................................... 96 External setpoint value ................................................96 Real power controller................................................. 96
Transformer variables............................................... 84 Frequency controller ...................................................89 Part-load lead ........................................................ 98
Configuration screens................................................. 75 Function of terminal 6 .......................................135, 136 Three-position controller ........................................... 98
Configure basic settings.............................................. 82 Functional description .................................................27 Reduced power protection ........................................ 123
Configure outputs .................................................... 141 Starting/stopping process.........................................37 Relay...................................................................... 14
Connection Table of Setpoint Values ...........................................27 Relay manager ................................................142, 160
Current Measuring Inputs............................................ 9 Gas engine ......................................................39, 144 Release CB.............................................................. 30
Power Supply........................................................... 7 Generator frequency monitoring .................................125 Release MCB........................................................... 30
Voltage measuring inputs............................................ 8 Generator number .....................................................78 Reply
Connection diagram Generator overload IOP ...........................................122 GCB is open ......................................................... 30
PCL1/H................................................................ 21 Generator overload MOP .........................................122 MCB is open......................................................... 30
PCL1/L................................................................. 20 Generator power monitoring......................................120 Reply
PCM1-G/H .......................................................... 23 Generator rated current...............................................84 CB is open ........................................................... 30
PCM1-G/H-E ........................................................ 24 Generator rated power...............................................84 Reverse power protection ......................................... 123
PCM1-G/L............................................................ 22 Generator rated speed .............................................147 Rise time ................................................................. 55
PCM1-M/H .......................................................... 26 Generator setpoint frequency .......................................82 Safety technical note ................................................... 6
PCM1-M/L ........................................................... 25 Generator setpoint voltage ..........................................83 Selection of the engine type ...................................... 144
Connection of the device .............................................. 7 Generator voltage monitoring ....................................126 Service display ......................................................... 78
Conroller Ignition ON..............................................................31 Set kWh ............................................................... 149
External setpoint value ............................................. 96 Ignition speed .........................................................146 Setting process according to Ziegler and Nichols............ 56
Constant and interchange power controller..................... 88 Interchange synchronization.........................................49 Settling time ............................................................. 55
Contents .................................................................... 2 Interface ..........................................................18, 163 SG 2D Speed governor ............................................. 61
Control inputs ........................................................... 28 Current direction ...................................................174 Sprinkler operation ...............................................29, 53
Control Outputs......................................................... 31 Gateway GW 4 ..........................................163, 174 Start counter........................................................... 149
Controller Power default .......................................................174 Start without power circuit breaker................................ 29
Constant and interchange power controller .................. 88 Introduction ................................................................6 Start/stop...............................................100, 101, 107
Frequency ............................................................. 89 Isolated operation......................................................30 Isolated operation in parallel with other gensets.......... 105
Load/var sharing.................................................... 99 kWh counter...........................................................149 Isolated operation in parallel with several gensets ....... 105
Power factor controller ............................................. 95 Lamp test .................................................................69 Load dependent ................................................... 101
Real power controller............................................... 96 Load distribution Mains parallel operation.................................100, 101
Voltage controller.................................................... 92 Wiring diagram......................................................59 Power-level dependent .......................................... 103
Controller configuration .............................................. 87 Load management configuration .................................100 Temperature dependent ......................................... 107
Controller output........................................................ 15 Load sharing.............................................................58 Start/stop ramp...................................................... 100
Counter configuration............................................... 147 Load shutoff ....................................................120, 121 Starter..................................................................... 31
Current slave pointer ................................................ 151 Load/var sharing ................................................58, 99 Starting/stopping process .......................................... 37
Current transformer Mains frequency monitoring.......................................128 Diesel engine ........................................................ 37
Generator ............................................................. 84 Mains power monitoring ...........................................121 Gas engine........................................................... 39
Mains................................................................... 86 Mains voltage monitoring..........................................129 Stopping magnet .................................................... 145
Decoupling from mains............................................. 117 Maintenance call.....................................................148 Stopping process ...................................................... 72
Delayed engine monitoring ....................................... 146 Measured quantities .................................................175 Synchroscope .......................................................... 70
Diesel engine ................................................... 37, 145 Measuring range monitoring ......................................140 System deviation....................................................... 55
Digital input configuration ......................................... 132 Monitoring of load imbalance....................................123 Table of Setpoint Values ............................................. 27
Digital inputs ............................................................ 10 Monitoring power circuit breakers.................................47 Technical data ....................................................... 176
Alarm text............................................................ 134 Motor block..............................................................29 Terminal 6 ......................................................135, 136
Dimensions ............................................................ 178 Motor configuration .................................................143 var sharing .............................................................. 58
Direct configuration.................................................... 77 Motor release ...........................................................29 Voltage controller...................................................... 92
Direction of power..................................................... 54 Normal use ................................................................6 Three-position controller ........................................... 93
Display elements and push-buttons ................................ 66 Operating conditions..................................................41 Watchdog configuration .......................................... 119

190 HB_PCL1/PCM1-M/PCM1-G_09.04_GB
HB_PCL1/PCM1-M/PCM1-G_09.04_GB 191
Woodward SEG GmbH & Co. KG
Krefelder Weg 47 ⋅ D – 47906 Kempen (Germany)
Postfach 10 07 55 (P.O.Box) ⋅ D – 47884 Kempen (Germany)
Phone: +49 (0) 21 52 145 1

Internet
Homepage http://www.woodward-seg.com
Documentation http://doc.seg-pp.com

Sales
Phone: +49 (0) 21 52 145 635 ⋅ Telefax: +49 (0) 21 52 145 354
e-mail: kemp.electronics@woodward.com

Service
Phone: +49 (0) 21 52 145 614 ⋅ Telefax: +49 (0) 21 52 145 455
e-mail: kemp.pd@woodward.com

You might also like