Air System Sizing Summary for Default System
Project Name: HMT LAB                                                                                                    12/13/2022
Prepared by: KFUEIT                                                                                                        10:25PM
Air System Information
  Air System Name                  Default System           Number of zones                                   1
  Equipment Class                          UNDEF            Floor Area                                   1145.5 ft²
  Air System Type                          SZCAV            Location                   Rahim Yar Khan, Pakistan
Sizing Calculation Information
  Calculation Months                   Jan to Dec           Zone CFM Sizing           Sum of space airflow rates
  Sizing Data                          Calculated           Space CFM Sizing         Individual peak space loads
Central Cooling Coil Sizing Data
  Total coil load                             7.3   Tons    Load occurs at                             Jul 1600
  Total coil load                            87.0   MBH     OA DB / WB                               109.4 / 77.9   °F
  Sensible coil load                         74.3   MBH     Entering DB / WB                          82.8 / 67.7   °F
  Coil CFM at Jul 1600                       3054   CFM     Leaving DB / WB                           60.0 / 58.6   °F
  Max block CFM                              3054   CFM     Coil ADP                                         57.5   °F
  Sum of peak zone CFM                       3054   CFM     Bypass Factor                                  0.100
  Sensible heat ratio                       0.853           Resulting RH                                       54   %
  CFM/Ton                                   421.1           Design supply temp.                              58.0   °F
  ft²/Ton                                   157.9           Zone T-stat Check                              0 of 1   OK
  BTU/(hr·ft²)                               76.0           Max zone temperature deviation                    0.1   °F
  Water flow @ 10.0 °F rise                 17.42   gpm
Central Heating Coil Sizing Data
  Max coil load                             17.3    MBH     Load occurs at                              Des Htg
  Coil CFM at Des Htg                       3054    CFM     BTU/(hr·ft²)                                     15.1
  Max coil CFM                              3054    CFM     Ent. DB / Lvg DB                          65.9 / 71.2 °F
  Water flow @ 20.0 °F drop                 1.73    gpm
Supply Fan Sizing Data
  Actual max CFM                            3054 CFM        Fan motor BHP                                   0.09 BHP
  Standard CFM                              3023 CFM        Fan motor kW                                    0.07 kW
  Actual max CFM/ft²                        2.67 CFM/ft²
Outdoor Ventilation Air Data
  Design airflow CFM                          570 CFM       CFM/person                                     22.81 CFM/person
  CFM/ft²                                    0.50 CFM/ft²
Hourly Analysis Program 5.10                                                                                        Page 1 of 7
                                  Zone Sizing Summary for Default System
Project Name: HMT LAB                                                                                                               12/13/2022
Prepared by: KFUEIT                                                                                                                   10:25PM
Air System Information
  Air System Name                Default System                   Number of zones                                        1
  Equipment Class                        UNDEF                    Floor Area                                        1145.5 ft²
  Air System Type                        SZCAV                    Location                        Rahim Yar Khan, Pakistan
Sizing Calculation Information
  Calculation Months                 Jan to Dec                   Zone CFM Sizing                Sum of space airflow rates
  Sizing Data                        Calculated                   Space CFM Sizing              Individual peak space loads
Zone Terminal Sizing Data
                                                                                             Reheat       Zone           Zone
                                        Design    Minimum                      Reheat         Coil      Htg Unit        Htg Unit    Mixing
                                        Supply     Supply                       Coil         Water        Coil           Water     Box Fan
                                        Airflow    Airflow        Zone          Load          gpm         Load            gpm      Airflow
  Zone Name                             (CFM)      (CFM)         CFM/ft²       (MBH)        @ 20.0 °F    (MBH)          @ 20.0 °F   (CFM)
  Zone 1                                     3054       3054          2.67           0.0           0.00        0.0            0.00         0
Zone Peak Sensible Loads
                                          Zone                             Zone            Zone
                                        Cooling       Time of             Heating          Floor
                                        Sensible   Peak Sensible           Load            Area
  Zone Name                              (MBH)     Cooling Load           (MBH)             (ft²)
  Zone 1                                      55.5       Jul 1700                5.9          1145.5
Space Loads and Airflows
                                                               Time of
                                                  Cooling       Peak            Air          Heating         Floor
  Zone Name /                                     Sensible     Sensible        Flow           Load           Area         Space
    Space Name                         Mult.       (MBH)        Load          (CFM)          (MBH)            (ft²)       CFM/ft²
  Zone 1
    HMT Lab                                 1          55.5      Jul 1700          3054                5.9     1145.5          2.67
Hourly Analysis Program 5.10                                                                                                     Page 2 of 7
                               Air System Design Load Summary for Default System
Project Name: HMT LAB                                                                                                      12/13/2022
Prepared by: KFUEIT                                                                                                          10:25PM
                                                 DESIGN COOLING                                 DESIGN HEATING
                                    COOLING DATA AT Jul 1600                      HEATING DATA AT DES HTG
                                    COOLING OA DB / WB 109.4 °F / 77.9 °F         HEATING OA DB / WB 49.0 °F / 41.1 °F
                                                        Sensible           Latent                     Sensible           Latent
  ZONE LOADS                              Details       (BTU/hr)         (BTU/hr)       Details       (BTU/hr)         (BTU/hr)
  Window & Skylight Solar Loads             64 ft²          3851                -          64 ft²             -               -
  Wall Transmission                        858 ft²          5480                -        858 ft²          4177                -
  Roof Transmission                          0 ft²              0               -           0 ft²             0               -
  Window Transmission                       64 ft²          1990                -          64 ft²         1349                -
  Skylight Transmission                      0 ft²              0               -           0 ft²             0               -
  Door Loads                                38 ft²           492                -          38 ft²           333               -
  Floor Transmission                         0 ft²              0               -           0 ft²             0               -
  Partitions                                 0 ft²              0               -           0 ft²             0               -
  Ceiling                                    0 ft²              0               -           0 ft²             0               -
  Overhead Lighting                       120 W              409                -              0              0               -
  Task Lighting                             60 W             205                -              0              0               -
  Electric Equipment                    10750 W            36679                -              0              0               -
  People                                       25           6125            5125               0              0               0
  Infiltration                                   -              0               0               -             0               0
  Miscellaneous                                  -              0               0               -             0               0
  Safety Factor                          0% / 0%                0               0            0%               0               0
  >> Total Zone Loads                            -         55231            5125                -         5860                0
  Zone Conditioning                              -         54069            5125                -         4940                0
  Plenum Wall Load                            0%                0               -              0              0               -
  Plenum Roof Load                            0%                0               -              0              0               -
  Plenum Lighting Load                        0%                0               -              0              0               -
  Return Fan Load                      3054 CFM                 0               -    3054 CFM                 0               -
  Ventilation Load                      570 CFM            19957            7642       570 CFM           12593                0
  Supply Fan Load                      3054 CFM              239                -    3054 CFM              -239               -
  Space Fan Coil Fans                            -              0               -               -             0               -
  Duct Heat Gain / Loss                       0%                0               -            0%               0               -
  >> Total System Loads                          -         74265           12767                -        17294                0
  Central Cooling Coil                           -         74265           12774                -             0               0
  Central Heating Coil                           -              0               -               -        17294                -
  >> Total Conditioning                          -         74265           12774                -        17294                0
  Key:                                     Positive values are clg loads                 Positive values are htg loads
                                          Negative values are htg loads                  Negative values are clg loads
Hourly Analysis Program 5.10                                                                                             Page 3 of 7
                                        System Psychrometrics for Default System
Project Name: HMT LAB                                                                                                                 12/13/2022
Prepared by: KFUEIT                                                                                                                     10:25PM
                                                       July DESIGN COOLING DAY, 1600
TABLE 1:     SYSTEM DATA
                                                          Dry-Bulb         Specific                                       Sensible      Latent
                                                             Temp         Humidity              Airflow     CO2 Level        Heat        Heat
  Component                                Location            (°F)          (lb/lb)             (CFM)         (ppm)      (BTU/hr)    (BTU/hr)
  Ventilation Air                              Inlet         109.4         0.01350                  570           400       19957        7642
  Vent - Return Mixing                       Outlet           82.7         0.01118                3054            805            -           -
  Supply Fan                                 Outlet           82.8         0.01118                3054            805         239            -
  Central Cooling Coil                       Outlet           60.0         0.01029                3054            805       74265       12774
  Central Heating Coil                       Outlet           60.0         0.01029                3054            805            0           -
  Cold Supply Duct                           Outlet           60.0         0.01029                3054            805            -           -
  Zone Air                                         -          76.6         0.01065                3054            898       54069        5125
  Return Plenum                              Outlet           76.6         0.01065                3054            898            0           -
  Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.069 BTU/(hr-CFM-F)
  Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4697.2 BTU/(hr-CFM)
  Site Altitude = 289.0 ft
TABLE 2:     ZONE DATA
                                               Zone                                                                       Terminal      Zone
                                            Sensible                   Zone            Zone         Zone         CO2       Heating    Heating
                                               Load            T-stat  Cond            Temp       Airflow       Level         Coil       Unit
  Zone Name                                 (BTU/hr)           Mode (BTU/hr)             (°F)      (CFM)       (ppm)      (BTU/hr)   (BTU/hr)
  Zone 1                                      55231           Cooling 54069             76.6        3054          898            0          0
Hourly Analysis Program 5.10                                                                                                         Page 4 of 7
                                        System Psychrometrics for Default System
Project Name: HMT LAB                                                                                                                 12/13/2022
Prepared by: KFUEIT                                                                                                                     10:25PM
                                                           WINTER DESIGN HEATING
TABLE 1:     SYSTEM DATA
                                                          Dry-Bulb         Specific                                       Sensible      Latent
                                                             Temp         Humidity              Airflow     CO2 Level         Heat       Heat
  Component                                Location            (°F)          (lb/lb)             (CFM)         (ppm)      (BTU/hr)    (BTU/hr)
  Ventilation Air                              Inlet          49.0         0.00369                  570           400       -12593           0
  Vent - Return Mixing                       Outlet           65.8         0.00369                3054            441            -           -
  Supply Fan                                 Outlet           65.9         0.00369                3054            441          239           -
  Central Cooling Coil                       Outlet           65.9         0.00369                3054            441            0           0
  Central Heating Coil                       Outlet           71.2         0.00369                3054            441        17294           -
  Cold Supply Duct                           Outlet           71.2         0.00369                3054            441            -           -
  Zone Air                                         -          69.7         0.00369                3054            451        -4940           0
  Return Plenum                              Outlet           69.7         0.00369                3054            451            0           -
  Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.069 BTU/(hr-CFM-F)
  Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4697.2 BTU/(hr-CFM)
  Site Altitude = 289.0 ft
TABLE 2:     ZONE DATA
                                               Zone                                                                       Terminal      Zone
                                            Sensible                   Zone            Zone         Zone         CO2       Heating    Heating
                                               Load            T-stat  Cond            Temp       Airflow       Level         Coil       Unit
  Zone Name                                 (BTU/hr)           Mode (BTU/hr)             (°F)      (CFM)       (ppm)      (BTU/hr)   (BTU/hr)
  Zone 1                                       -5860          Heating  -4940            69.7        3054          451            0          0
Hourly Analysis Program 5.10                                                                                                         Page 5 of 7
                                                   System Psychrometrics for Default System
Project Name: HMT LAB                                                                                                          12/13/2022
Prepared by: KFUEIT                                                                                                              10:25PM
         Location: Rahim Yar Khan, Pakistan
         Altitude: 289.0 ft.
         Data for: July DESIGN COOLING DAY, 1600
                                                                                                          0.020
                  1. Outdoor Air
                  2. Mixed Air
                  3. Supply Fan Outlet
                  4. Central Cooling Coil Outlet                                                          0.018
                  5. Room Air
                                                                                                          0.016
                                                                                                                  Specific Humidity ( lb/lb )
                                                                                                    1     0.014
                                                                               23                         0.012
                                                                       5
                                                     4
                                                                                                          0.010
                                                                                                          0.008
                                                                                                          0.006
                                                                                                          0.004
                                                                                                          0.002
                                                                                                          0.000
            30                 40          50       60        70          80         90       100   110
                                                          Temperature ( °F )
Hourly Analysis Program 5.10                                                                                      Page 6 of 7
                                                        System Psychrometrics for Default System
Project Name: HMT LAB                                                                                                              12/13/2022
Prepared by: KFUEIT                                                                                                                  10:25PM
         Location: Rahim Yar Khan, Pakistan
         Altitude: 289.0 ft.
         Data for: WINTER DESIGN HEATING
                                                                                                              0.020
                  1. Outdoor Air
                  2. Mixed Air
                  3. Supply Fan Outlet
                  4. Central Heating Coil Outlet                                                              0.018
                  5. Room Air
                                                                                                              0.016
                                                                                                                      Specific Humidity ( lb/lb )
                                                                                                              0.014
                                                                                                              0.012
                                                                                                              0.010
                                                                                                              0.008
                                                                                                              0.006
                                                   1                     23   5 4
                                                                                                              0.004
                                                                                                              0.002
                                                                                                              0.000
            30                 40                  50           60           70            80      90   100
                                                               Temperature ( °F )
Hourly Analysis Program 5.10                                                                                          Page 7 of 7