SINGLE MONITORED INPUT/OUTPUT UNIT – BN-304
Interactive fire detection systems
Product Datasheet
Features
•	 Interactive
•	 For interfacing and controlling external units to
   Autronica’s interactive fire detection systems
•	 Multi function unit: Function selected by switch
   setting.
•	 Input/Output signals
•	 1 non-isolated input: on/off function with end-of-
   line monitoring
•	 1 output: Potential free contact without end-of-
   line monitoring
•	 1A 30 VDC dry relay contact for the output port
•	 Includes the SelfVerify function for reduced
   maintenance/testing and increased reliability on
   the input for critical alarm functions
•	 Short-circuit isolator of detection loop in each
   unit
•	 Automatic addressing
•	 Proven technology
•	 Wall mounted
•	 Designed to meet the requirement of the major         on this datasheet (Descriptions of function options A-K).
   maritime classification societies                     The available functions include:
•	 Approved according to EN 54-17 and EN 54-18
                                                         •	 Function A
                                                            Alarm condition signalling input unit with relay feedback
Product overview                                         •	 Function B
                                                            Pre Alarm condition signalling input unit with relay
The Single Monitored Input/Output Unit BN-304 has           feedback
been designed for use with Autronica’s fire detection    •	 Function C
                                                            Fault condition signalling input unit with relay feedback
systems Autroprime (version 1.1.0 or newer) and          •	 Function D
AutroSafe (version 4.3.1 or newer), and includes the        Uncommitted input unit (Output follows input)
SelfVerify function. This function ensures the highest   •	 Function E
grade of reliability and reduces the need for manual        Pre Alarm and Alarm condition signalling input unit with
testing because the panel is able to continuously           configurable input delay and relay feedback
                                                         •	 Function F
and automatically check all units that include this         Fault, Pre Alarm and Alarm condition signalling input
function.                                                •	 Function G
                                                            Alarm condition signalling input unit with relay output used
Note: External devices attached to this interface unit      for reset
require a separate power source (they can not be         •	 Function H
                                                            Alarm condition signalling input and independent relay
powered by the detector loop).                              output function
SelfVerify: The unit’s ability to initiate alarm is      •	 Function I
regularly checked.                                          Uncommitted input unit and independent relay output
                                                            function
                                                         •	 Function J
Function options / Switch settings                          Relay output function (Input not in use)
The internal DIP switch S1 selects the function          •	 Function K
performed by the BN 304 unit. For location of the           Relay output function with activation feedback (input)
DIP switch, refer to circuit board drawing on the next
page. Refer to detailed descriptions of each function
116-P-BN304/CGB, Doc-1000372-1, 2021-02-16
Single Monitored Input/Output Unit – BN-304
Technical Specification
Dimensions (mm)                                                112 x 110 x 50
Weight (g)                                                     192
Housing material                                               Polyamide 6.6.
Colour                                                         Light grey
Mounting                                                       Wall mounting, 100 mm bolt space
Power                                                          Unit connects to AL_Com only
Voltage                                                        16-26 VDC
Peak current consumption (during communication)                359μA
Average current consumption                                    <60μA
Temperature range                                              -25 to +70 °C
Humidity                                                       10% - 95% RH (non-condensing)
Degree of protection
Membrane inlets:                                               IP54
PG inlets (PG-13,5):                                           IP67
Communication loop                                             Autronica loop communication protocol (AL_Com)
Cable terminals                                                Max 2.5 mm² single core wires
Cable requirements AL_Com                                      Refer to specification for Autroprime or AutroSafe
Maximum input cable length                                     10 m
Maximum cable capacitance                                      10nF
Response time                                                  <= 1 second
Output relay rating                                            1A 30 VDC resistive load
Output relay type                                              Dry contact, latching type; keep state on loss of power. No EOL
                                                               monitoring
Threshold                                                      Short circuit: 0-235 Ω
                                                               Activate: 260-1000 Ω
                                                               Normal: 1200-4800 Ω
                                                               Open circuit: 5400-∞ Ω
Approvals                                                      EN54, MED. For detailed info, see Autronica’s product web
                                                               http://product.autronicafire.com/products/
Product name                   Part number                     Description
BN-304                         116-BN-304                      Single monitored input/output unit
6571-011.6020                  116-6571-011.6020               Membrane gland TSS M20, grey
Optional
6571-011.1920                  116-6571-011.1920               Gland IP67
6531-006.1920                  116-6531-006.1920               Backnut for gland
                               Autronica Fire and Security AS | www.autronicafire.com | Page 2
Single Monitored Input/Output Unit – BN-304
Dimension (mm)
Connectors
Terminal              Description
1                     AL_Com In (+)
2                     AL_Com In (-)
3                     AL_Com Out (+)
4                     AL_Com Out (-)
5                     Input (+)
6                     Input (common)
7                     Relay contact
8                     Relay contact
Connectors and DIP switches on circuit board
                          Autronica Fire and Security AS | www.autronicafire.com | Page 3
Single Monitored Input/Output Unit – BN-304
Descriptions of connection options
Input configuration A
                        Class 1
                                  N.O.
                                                2KOhm
                                   910 Ohm
Input configuration B
                        Class 2
                                  N.C.
                                                  2KOhm
                                   910 Ohm
Input configuration C
                        Class 3
                                  N.O.
                                                  2KOhm
Input configuration D
                        Class 4
                                  N.C.
                                                 2KOhm
		Figure 1
                             Autronica Fire and Security AS | www.autronicafire.com | Page 4
Single Monitored Input/Output Unit – BN-304
The electrical connection options for the input to the unit are shown in Figure 1. The various electrical input
configurations allow a user to select under what condition the unit will be ‘triggered’ to provide a signal the fire
alarm system indicating the selected condition.
The four different behaviours can be configured by DIP switch 5 and 6 in order to be able to monitor different
setups of the input contact (s). (Switch 8 is not used).
(See location and dip switch no. on the circuit board drawing).
Input configuration A activates when the contacts are closed. This arrangement also allows the unit to monitor
for an electrical wiring fault in the form of an open or short-circuit, between the contacts and the unit, either
before or during activation.
 S1.5    S1.6
 OFF     OFF
Normally Open contact with ‘activate’ resistor, fault monitored for open and short-circuit.
Input configuration B activates when the contacts are opened. This arrangement allows the unit to monitor for
an electrical wiring fault in the form of an open or short-circuit, between the contacts and the unit, either before
or during
 S1.5    S1.6
 OFF     ON
Normally Closed contact with ‘activate’ resistor, fault monitored for open and short-circuit.
Input configuration C activates when the contacts are closed. This arrangement allows the unit to monitor for an
open circuit fault in the electrical wiring before activation. A short-circuit in the wiring will trigger the unit.
 S1.5    S1.6
 ON      OFF
Normally Open contact without ‘activate’ resistor, fault monitored for open circuit.
Input configuration D activates when the contacts are opened. This arrangement allows the unit to monitor for
an open circuit fault in the electrical wiring during activation.
 S1.5    S1.6
 ON      ON
Normally Closed contact without ‘activate’ resistor, fault monitored for open circuit.
Output configuration
The output relay can be set to Normal Open or Normal Closed operation by DIP switch 1.7:
•	 DIP 1.7 OFF = Normally Open
•	 DIP 1.7 ON = Normally Closed
DIP switch 1.8 determines the state of output if the unit loses its power.
•	 DIP 1.8 OFF = Relay remains in current state
•	 DIP 1.8 ON = Relay switches to initial state as chosen by DIP 1.7
                             Autronica Fire and Security AS | www.autronicafire.com | Page 5
Single Monitored Input/Output Unit – BN-304
Descriptions of function options
(See location of DIP switch S1 on the circuit board drawing)
Function A
 S1.1   S1.2    S1.3    S1.4
 OFF    OFF     OFF     OFF
Function: Alarm condition signalling input unit with feedback function.
The relay contact will follow the state of the input.
Number of addresses: 1
Application include:
•	 Fire alarm push buttons
•	 Flame, heat or beam detectors with relay contacts
Function B
 S1.1   S1.2    S1.3    S1.4
 ON     OFF     OFF     OFF
Function: Pre Alarm condition signalling input unit with feedback function.
The relay contact will follow the state of the input.
Number of addresses: 1
Application include:
•	 Manual input for Pre Alarm
•	 Pre Alarm input from a detector with relay output
•	 Sprinkler contacts, etc.
Function C
 S1.1   S1.2    S1.3    S1.4
 OFF    ON      OFF     OFF
Function: Fault condition signalling input unit with feedback function.
Relay contact closes when the fault state is entered, and opens when the unit is reset.
Number of addresses: 1
Application include:
•	 Monitoring of associated equipment for faults
•	 Monitoring of detectors with relay contacts
Function D
 S1.1   S1.2    S1.3    S1.4
 ON     ON      OFF     OFF
                               Autronica Fire and Security AS | www.autronicafire.com | Page 6
Single Monitored Input/Output Unit – BN-304
Function: Uncommitted input.
Number of addresses: 1
Applications:
A typical application is monitoring of the power fault contact in the power supply or a fire pump. This unit can be
used for:
•	 Monitoring of water level detection systems
•	 Monitoring of smoke control damper systems
•	 Monitoring of extinguishing systems
•	 General Alarm Push Button (GAPB)
The relay contact will follow the state of the input.
Function E
 S1.1    S1.2    S1.3    S1.4
 OFF     OFF     ON      OFF
Function: Delayed Alarm condition signalling input unit with feedback function. Input delay 2 seconds.
Configurable delays for entering Pre Alarm and Alarm condition. Default delays: Pre Alarm 10 seconds, Alarm 20
seconds (timers are configurable).
Relay contact closes when the alarm state is entered, and opens when the input goes to normal.
Number of addresses: 1
Application include:
•	 Sprinkler contacts, etc.
Function F
 S1.1    S1.2    S1.3    S1.4
 ON      OFF     ON      OFF
Function: Fault, Pre Alarm and Alarm condition.
Number of addresses: 1
Applications include:
•	 Fire detectors with two-level output (Pre Alarm and Alarm).
Relay contact activates for a configurable period when the unit is reset. This provides a 5 seconds (configurable)
pulse for resetting the external detector.
                                Autronica Fire and Security AS | www.autronicafire.com | Page 7
Single Monitored Input/Output Unit – BN-304
Function G
 S1.1   S1.2    S1.3    S1.4
 OFF    ON      ON      OFF
Function: Alarm condition signaling input unit with reset function for external detector.
Relay contact activates for a configurable period when the unit is reset. This provides a 5 seconds (configurable)
pulse for resetting the external detector.
Number of addresses: 1
Applications include:
•	 Flame, heat or beam detectors with relay contacts.
Function H
 S1.1   S1.2    S1.3    S1.4
 ON     ON      ON      OFF
Function: Alarm condition signalling input and independent relay output function.
Number of addresses: 2
Input application includes:
•	 Fire Alarm push buttons
•	 Flame, heat or beam detectors with relay contacts
•	 Sprinkler contacts, etc.
The output unit contains a potential free contact, which can be activated from a detector or a combination of
several detectors or other preconfigured cause and effect relationships. No end-of-line monitoring on output
function.
The output can be used for:
•	 Door release
•	 Sprinkler control/functions
•	 Control of fire dampers
•	 FPE/FAD without bell patterns
                               Autronica Fire and Security AS | www.autronicafire.com | Page 8
Single Monitored Input/Output Unit – BN-304
Function I
 S1.1    S1.2   S1.3    S1.4
 OFF     OFF    OFF     ON
Function: Uncommitted input and independent relay output function.
Number of addresses: 2
Applications:
A typical application is monitoring of the power fault contact in the power supply or a fire pump. This unit can be
used for:
•	 Monitoring of water level detection systems
•	 Monitoring of smoke control damper systems
•	 Monitoring of extinguishing systems
The output unit contains a potential free contact, which can be activated from a detector or a combination of
several detectors or other preconfigured cause and effect relationships. No end-of-line monitoring on output
function.
The output can be used for:
•	 Door release
•	 Sprinkler control/functions
•	 Control of fire dampers
•	 FPE/FAD without bell patterns
Function J
 S1.1    S1.2   S1.3    S1.4
 ON      OFF    OFF     ON
Function: Relay output function (input not in use)
Number of addresses: 1
Applications:
The output unit contains a potential free contact, which can be activated from a detector or a combination of
several detectors or other preconfigured cause and effect relationships. The output can be used for:
•	 Door release
•	 Sprinkler control/functions
•	 Control of fire dampers
•	 FPE/FAD without bell patterns
Function K
 S1.1    S1.2   S1.3    S1.4
 OFF     ON     OFF     ON
Function: Relay output function with activation feedback monitoring. Default delay for change of position is 15
seconds. At activation there is a 30 seconds delay before a technical alarm is initiated if the door is not closed
within that timer. When the door closes an indication of this status is given immediately. When the door is
closed, an indication of the new status is sent after 120 seconds. All delays are configurable.
Number of addresses: 1
Applications:
•	 Door control and monitoring
•	 Fire damper control and monitoring
•	 Low location lights control and monitoring
•	 Other equipment