Chiller
Chiller
CO2
• 	Hyperchill water chillers, ideal for water or antifreeze fluid cooling in a closed circuit by means of a
	 refrigeration cycle, featuring superior reliability, high energy efficiency and accurate temperature control of the
   chilled fluid;
	 The chiller cools the water in a closed circuit, making use of one or more refrigeration compressors.
	 The system consists of a cooling circuit and a water circuit: the refrigerant flows in the former and the process
   water circulates in the latter. The two fluids never come into direct contact, however they exchange heat in
   the evaporator, where the refrigerant absorbs the heat contained in the water and evaporates. The water then
   exits the chiller at the temperature required by the application.
• 	Hyperfree drycoolers, heat exchangers where water is cooled down thanks to forced circulating ambient air,
	 with an extremely low energy consumption.
	 The water in the coolers circulates inside a heat exchanger coil, whereas an external air flow is forced through by
   one or more fans, thereby cooling the water to the required temperature.
Applications
Water chilling and cooling is needed in almost all areas of industry. Hyperchill and Hyperfree are particularly
suitable for the textile, food processing, plastics, pharmaceutical, beverages, engineering, glass, laser and
electronics industries in the following applications:
To prevent overheating, wear and loss of production and increase operator safety:
Machine cooling: direct or indirect (cooling oil temperature control).
Ambient cooling: cold rooms, air conditioning, electrical panels, cooling tunnels.
Drying (in combination with aftercoolers) of: compressed air, technical and biogases, control air,
chemical/pharmaceutical products, paints.
Other applications: temperature control of baths, ovens, chemical reactors, special applications.
Water and refrigerant gauges allow complete         Circulation pump (std 3 bar): various pressures
control of the working conditions.                  available to meet specific application
                                                    requirements. Dual pump that can be configured
Microprocessors: guarantee full control of the      for 100% back-up.
machine parameters. The proprietary software
enable flexible selection, configuration of         Metal filters on the condensers: protection
working parameters and remote                       against dirt and knocks, thereby reducing
control operation.                                  downtime risks and maintenance costs.
Air-cooled version with axial fans: for outdoor     Water tank: oversized to guarantee enhanced
installation, with no protection required.          reliability and improve temperature control.
ICE003-ICE010                                        Reference applications:
The chillers of the Hyperchill range,                cooling of small dies, individual extruders,
from ICE003 to ICE010, are compact units             printing systems, thermoforming, welding and
designed for industrial use.                         spindle machines and machine tools in general.
They are machines suitable for cooling fluids
such as water or water and glycol mixtures or low
viscosity fluids. Temperature range of the cooling
fluid: from +5 °C to +30 °C.
All models are suitable for ambient temperatures
of up to +45 °C and can be installed internally
                                                     Options:
or externally, with suitable protection              Available kits for ICE003-ICE010:
against the weather.                                 • Remote control
The integrated storage tank is closed and made       • Wheels
of carbon steel, (ICE 003 and ICE 005 have an        • Water filters
open plastic top loading tank or a relief valve      • Water filling
when installed in pressurised circuits).
The evaporator immersed in the tank is coaxial,      ICE007 and ICE010 are available
tube-in-tube and of counter flow design              with the following options:
for excellent heat exchange.                         •	 Low ambient temperature: with fan speed
The circulation pump is peripheral,                     control in order to guarantee operation even in
with an available pressure of 3 bar and an              very cold environments and reduce the noise
integrated water by-pass.                               of the machine.
The pump draws the water from the tank               • 	Low water temperature: water and glycol
at the set temperature and delivers it to               mixtures up to -10 °C can be used (the low
the application. A gauge always indicates               ambient temperature option is recommended
the pressure available for use.                         as a supplement).
                                                     • 	Antifreeze: prevents ice formation in cold
                                                        environments if water is used with no
                                                        antifreeze aditive, or the heating of the process
                                                        fluid to the value is not provided by the user.
Technical data Hyperchill ICE003-ICE010
 Model ICE                                          003                    005                 007             010
 Cooling capacity     1
                                       kW           2,5                    5,1                 7               9,5
 Compressor abs. power           1
                                       kW           0,7                    1,4                 2,0             2,3
 Cooling capacity     2
                                       kW           1,7                    3,7                 5,0             6,7
 Compressor abs. power           2
                                       kW           0,67                   1,3                 1,9             2,1
 Power supply                        V/ph/Hz               230/1/50                        400/3/50 no neutral
 Protection index                                              33                                       44
 Refrigerant                                                                      R407C
 Compressors
 Type                                                                       ermetic pistons
 Compressors/circuits                                                               1/1
                                                                                                                                      ICE003-005
 Max abs. power - 1 comp.              kW           0,7                    1,5                 1,8                3
 Axial fans
 Quantity                              n°                                           1
 Max abs. Power - 1 fan               kW            0,12                  0,12                 0,1             0,1
 Air flow                             m /h
                                        3
                                                    2300                  2300             4400                4100
 Pump P30
 Max abs.power                        kW            0,4                    0,4                 0,5             0,5
 Water flow (nom/max)        1
                                      m /h
                                        3
                                                0,43/2,4                 0,88/2,4          1,2/3               1,6/3
 Head pressure (nom/min)         1
                                     m H2O          36/5                  29/5             36/8                30/8
 Water flow (nom/max)        2
                                      m /h
                                        3
                                                0,29/2,4                 0,64/2,4          0,86/3              1,2/3
 Head pressure (nom/min)         2
                                     m H2O          38/5                  33/5             42/8                36/8                    ICE007-010
 Dimensions and weight
 Width                                mm            530                    530                 980             980
 Depth                                mm            750                    750                 534             534
 Height                               mm            800                    800             1228                1228
 Connections in/out                    in            1”                    1”                  1”                 1”
 Tank capacity                          l           25                     25                  45                 45
 Weight (axial)                        kg           105                    110                 170             180
 Noise level
 Sound pressure (axial)3             dB(A)          52                     52                  53                 53
1) 	at water in/out temperature = 20/15°C, glycol 0%, either 25°C ambient temperature (air-cooled models) or 25°C condenser water inlet
	 temperature with 35°C condensing temperature (water-cooled models).
2) 	at water in/out temperature = 12/7°C, glycol 0%, 32°C ambient temperature (air-cooled models)
3) 	referred to axial fan version in free field conditions at a distance of 10m from unit, measured on condenser side, 1m from ground.
Correction factors
 A) Ambient temp. (air-cooled models)          °C          5                 10                15            20        25        30       35        40           45
    correction factor (f1)                                1,05              1,05           1,05              1,05      1      0,95     0,89         0,83        0,77
 C) Glycol                                     %                 0                        10                      20        30                 40           50
    correction factor (f3)                                       1                      0,99                   0,98         0,97           0,96            0,94
To obtain the required cooling capacity multiply the value at nominal conditions by the above correction factors (i.e. cooling capacity =
Pxf1xf2xf3xf4, where P is the cooling capacity at conditions (1)). Hyperchill, in its standard configuration, can operate up to ambient
temperatures of max 45°C and min. 5°C and water temperatures of max 30°C inlet and min. 0°C outlet. The above correction factors are
approximative: for a precise selection always refer to the software selection program.
ICE015-ICE230
The chillers of the Hyperchill range, from ICE015      High reliability and back-up eliminates
to ICE230, are a complete solution, easy to install    downtime risks
and operate.                                           • 	 The oversized storage tanks eleviate the work of
• 	 The water circuit consists of: a storage tank,         the compressors. Minimising the number
    an immersed finned evaporator and a pump           	 of times the machine is switched on-off,
    with a standard by-pass and does not require           improving temperature control and prolonging
    expensive water connections during start-up.       	 the life of the machine.
• 	 As from ICE076, the tanks are equipped             • 	 Separate, double cooling circuits
	 with a manual valve on the pump connection,          	 (as per ICE076) guarantee total back-up,
    in order to facilitate its replacement, in case        preventing system downtime in case of faults
	 of a fault.                                              or maintenance.
• 	 Electronic controllers with proprietary software   • 	 2 compressors as per ICE076 and 4
    guarantee full access to the machines operating        compressors as per ICE150, with automatic
    parameters. This enables reliable operation to         rotation, improve temperature control and
    meet all industrial requirements, even where           reduce the wear of the individual components.
    these demand customisation.                        • 	 Dual pumps in “stand-by” are available
• 	 Remote control and monitoring is available.        	 as optional to prevent any downtime risks.
• 	 The machines are fully configurable                • 	 Water tank minimum level alarm, pump
	 with various options and kits to meet all                and compressor absorption, high and low
    industrial process requirements.                       refrigerant pressure, ice formation and high
• 	 The protection filters on the condensers reduce        and low water temperature indication.
    dirt, thereby preventing system downtime           • 	 Maximum ambient temperature up to +45 °C.
	 and also guarantee protection against knocks
    and enhanced user safety.
• 	 The separate condenser compartment enables
    routine and special maintenance
	 to be performed without stopping the system.
• 	 The structure and design guarantees full
    internal access for easy maintenance.
                                                       Reference applications:
The lowest energy consumption on the market            precision cooling of injection moulding machines
• 	 Oversized condensers and evaporators               and printing machines, medical scanners,
    optimise the work of the cooling cycle.            compressed air or technical gas.
• 	 The compliant scroll compressors guarantee         Heat dissipation from production processes,
    low power consumption and minimum peak             fermentation of beverages such as beer or wine
    start-up current.                                  and galvanising systems.
• 	 The evaporator immersed in the cold                Temperature control of pumps, motors
	 and insulated tank optimises heat exchange           and machinery in general.
    and minimises heat loss to the external
    environment.
Options:
• 	 Water fill kit: pressurised
	 automatic, manual or automatic under
	 atmospheric pressure, to fill or easily top
	 up the coolant.
                                                                                         Tank kit
• 	 Remote control kit: basic version for start-up/
    shutdown and general alarms. Advanced model
    for full control of the machine.                                   Remote control
	 Monitoring is available.
ICE015-046 ICE057-230
Correction factors
 A) Ambient temp. (air-cooled models)                   °C    5             10          15       20         25         30        35        40            45
    correction factor (f1)                                   1,05           1,05     1,05        1,05       1       0,95     0,89          0,83          0,77
 C) Glycol                                              %           0              10                 20          30                  40            50
    correction factor (f3)                                          1              0,99            0,98           0,97            0,96             0,94
To obtain the required cooling capacity multiply the value at nominal conditions by the above correction factors (i.e. cooling capacity =
Pxf1xf2xf3xf4, where P is the cooling capacity at conditions (1)). Hyperchill, in its standard configuration, can operate up to ambient
temperatures of max 45°C and min. 5°C and water temperatures of max 30°C inlet and min. 0°C outlet. The above correction factors are
approximative: for a precise selection always refer to the software selection program.
Technical data Hyperchill ICE015-ICE230
 Model ICE                                  015         022    029          039         046        057        076         090     116     150         183      230
 Cooling capacity   1
                                  kW        14,3        21,8   28,1         38,2        45,2       56,4       76,0        90,2    115,5   149,2       182,3    228
 Compressor abs. power      1
                                  kW        3,4         5,2     5,7          7,7        10,1       12,3       15,4        20,3    24,9    30,8        40,1    51,4
 Cooling capacity   2
                                  kW        10          15,4   21,2         27,7        33,0       40,8       55,2        65,8    84,2    108         133      166
 Compressor abs. power      2
                                  kW        3,2         5,5     6,0          8,2        10,3       13,1       16,4        26,2    25,8    32,5        41,3    54,6
 Power supply                   V/ph/Hz                                                        400/3/50 no neutral
 Protection index                                                                                        54
 Refrigerant                                                                                         R407C
 Compressors
 Type                                     hermetic                                                   hermetic scroll
                                           piston
 Compressors/circuits                                                 1/1                                                  2/2                         4/2
 Max abs. power - 1 comp.         kW        5,8         6,9     7,8         11,1        13,7       16,8       11,1        13,7    16,8    11,1        13,7    16,8
 Axial fans
 Quantity                         n°                    1                           2                                 3                           2             3
 Max abs. Power - 1 fan           kW        0,61        0 61   0,78         0,61        0,61       0,61       0,78        0,78    0,78     2           2        2
 Air flow                        m /h
                                   3
                                           7100        6800    9200         12400 12000 17400 25500 25000 26400 47000 46000 66000
 Centrifugal fans
 Quantity                         N°               1                         2                                        3                                3
 Max abs. Power - 1 fan           kW        1,1         1,1     1,1          1,1         1,1       1,1         1,5         1,5     1,5     3           3        3
 Air flow                        m /h
                                   3
                                           7100        6800    9200         12400 12000 17400 25500 25000 26400 47000 46000 66000
 Head pressure                    Pa        140         130    200          180         160        200        100         100     100     180         180      130
 Water cooled version
 Condenser water flow            m3/h       1,3         1,9     2,4          4           5,6        8         11,1        11,5    16,6    19,2         31      33
 Condensers connections           in        1”          1”     1 ¼”         1 ¼”        1 ¼”      1 ¼”        1 ¼”        1 ¼”    1 ¼”    1 ¼”        1 ¼”    1 1/2”
 Pump P30
 Max abs.power                    kW        1,1         1,3     1,3          1,3         2,3       2,3         2,5         2,7     2,7     4,5         4,5     4,5
 Water flow (nom/max)1           m3/h      2,3/6       3,7/9,6 4,8/9,6 6,6/9,6 7,8/18 9,7/18 13/31                        15/27   20/27   25/50       30/50   39/50
 Head pressure (nom/min)1       m H2O      29/21       28/17   27/17        24/17       28/22     27/22       23/13       28/16   25/16   34/20       32/20   26/20
 Water flow (nom/max)   2
                                 m /h
                                   3
                                           1,6/6       2,7/9,6 3,6/9,6 4,8/9,6 5,7/18 7,0/18 9,5/31 11/27                         14/27   18/50       23/50   29/50
 Head pressure (nom/min)    2
                                m H2O      30/21       29/17   28/17        27/17       28/22     28/22       23/13       32/16   30/16   36/20       35/20   32/20
 Dimensions and weight
 Width                           mm        1090        1090    1650         1650        1650      2200        2200        2200    2200    3000        3000    3260
 Depth                           mm         744         744    744          744         744        744        898         898     898     1287        1287    1287
 Height                          mm        1358        1358    1358         1358        1358      1358        1984        1984    1984    2298        2298    2298
 Connections in/out               in       1 ¼”        1 ¼”    1 ½”         1 ½”        1 ½”      1 ½”         2”          2”      2”     2 ½”        2 ½”    2 ½”
 Tank capacity                     l        120         120    180          180         250        300        500         500     500     1000        1000    1000
 Weight (axial)                   kg        250         270    380          410         430        520        800         900     1000    1500        1800    2100
 Weight (centrif.)                kg        280         300    410          450         480        610        950         1050    1150    1700        2000    2300
 Weight (water cooled)            kg        250         260    380          410         430        520        800         900     1000    1500        1800    2100
 Noise level
 Sound pressure (axial)3         dB(A)      50          50      53           52          52        56          58          58      58      62          62      64
1) 	at water in/out temperature = 20/15°C, glycol 0%, either 25°C ambient temperature (air-cooled models) or 25°C condenser water inlet
    temperature with 35°C condensing temperature (water-cooled models).
2) 	at water in/out temperature = 12/7°C, glycol 0%, 32°C ambient temperature (air-cooled models)
3) 	referred to axial fan version in free field conditions at a distance of 10m from unit, measured on condenser side, 1m from ground.
ICE310-ICE360                                                                  Reference applications:
The ICE310 and ICE360 chillers of the Hyperchill                               cooling the high-capacity extruders, multiple
range are designed and built to meet the                                       printing and processing systems of plastic
requirements of centralised industrial cooling                                 material and production of glass, aluminium
systems. They can also be easily installed on                                  and other materials. Wine, beer, oil and general
existing systems and integrated in parallel                                    beverage industries.
for complete and modular solutions.
Two completely independent cooling circuits,
four compliant scroll compressors, a shell and
tube evaporator and an optional hydronic
(internal tank and pump) kit provide maximum                                   Options:
flexibility and allow the product to be adapted to                             •	 Remote control kit
the specific requirements of each application.                                 • 	 Connectivity kit
The controller with proprietary software can be                                • 	 Control panel protection kit
programmed with various customised solutions.
The optional pump draws the water from the                                     • 	 Water tank: inside the machine,
application and delivers it towards the                                        	 guarantees a minimum volume to control
evaporator, where it cools to the set temperature.                             	 the outlet water temperature.
In this configuration, the pump can work directly
with external open tanks.                                                      • 	 Bioenergy: protection with epoxy coating on all
                                                                                   exposed parts made of copper, for operation in
                                                                                   harsh environments (landfills, fermentation of
                                                                                   biomass, marine environments).
ICE310-360
Correction factors
 A) Ambient temp. (air-cooled models)   °C    5             10            15        20        25        30       35        40           45
    correction factor (f1)                   1,05           1,05      1,05         1,05       1      0,95     0,89         0,83        0,77
 C) Glycol                              %           0                10                  20        30                 40           50
    correction factor (f3)                          1               0,99              0,98         0,97           0,96            0,94
To obtain the required cooling capacity multiply the value at nominal conditions by the above correction factors (i.e. cooling capacity =
Pxf1xf2xf3xf4, where P is the cooling capacity at conditions (1)). Hyperchill, in its standard configuration, can operate up to ambient
temperatures of max 45°C and min. 5°C and water temperatures of max 30°C inlet and min. 0°C outlet. The above correction factors are
approximative: for a precise selection always refer to the software selection program.
Technical data Hyperchill ICE310-ICE360
 Model ICE                                           310        360
 Cooling capacity1           kW                      309        360
 Compressor abs. power1      kW                       65         82
 Cooling capacity 2
                             kW                      231        262
 Compressor abs. power   2
                             kW                       65         85
 Power supply              V/ph/Hz                 400/3/50 no neutral
 Protection index                                          54
 Refrigerant                                             R407C
 Compressors
 Type                                                 hermetic scroll
 Compressors/circuits                                     4/2
 Max abs. power - 1 comp.    kW                      23,3       28,7
 Axial fans
 Quantity                     n°                             4
 Max abs. Power - 1 fan      kW                       2            2
 Air flow                   m3/h                    88000        88000
 Pump P30
 Max abs.power               kW                      8,4          8,4
 Water flow (nom/max)1      m3/h                    53/90        62/90
 Head pressure (nom/min)1   m H2O                   26/19        23/19
 Water flow (nom/max) 2
                            m3/h                    40/90        45/90
 Head pressure (nom/min) 2
                            m H2O                   37/19        35/19
 Dimensions and weight
 Width                       mm                     4200          4200
 Depth                       mm                     1500          1500
 Height                      mm                     2240          2240
 Connections in/out           in                      4”           4”
 Tank capacity                 l                     400          400
 Weight (axial)               kg                    2900          3100
 Noise level
 Sound pressure (axial)3    dB(A)                     65           65
1) 	at water in/out temperature = 20/15°C, glycol 0%, either 25°C ambient temperature (air-cooled models) or 25°C condenser water
	 inlet temperature with 35°C condensing temperature (water-cooled models).
2) 	at water in/out temperature = 12/7°C, glycol 0%, 32°C ambient temperature (air-cooled models)
3) 	referred to axial fan version in free field conditions at a distance of 10m from unit, measured on condenser side, 1m from ground.
Hyperchill MAXI (ICE460-ICE880)
Hyperchill MAXI are process chillers designed to work in large industrial systems,
outdoor installation and centralised cooling systems. They guarantee reliability
and efficiency in all industrial environments, with compact system dimensions
and low noise levels.
Quality components, meticolous construction and strict testing procedures
guarantee maximum safety and reliability and prevent industrial users from
experiencing production downtime.
Correction factors
 A) Ambient temp. (air-cooled models)         °C        5                10          15             20        25              30           35        40             45
    correction factor (f1)                             1,05             1,05      1,05             1,05       1            0,95         0,89         0,83          0,77
 C) Glycol                                    %               0                 10                       20              30                     40             50
    correction factor (f3)                                    1                 0,99                 0,98                0,97               0,96              0,94
To obtain the required cooling capacity multiply the value at nominal conditions by the above correction factors (i.e. cooling capacity = Pxf1xf2xf3xf4, where P is the
cooling capacity at conditions (1)). Hyperchill, in its standard configuration, can operate up to ambient temperatures of max 45°C and min. 5°C and water temperatures
of max 30°C inlet and min. 0°C outlet. The above correction factors are approximative: for a precise selection always refer to the software selection program.
Hyperchill Laser (HLS005-HLS116)
Industrial process chillers for Precision Cooling with a Non-Ferrous water circuit.
Hyperchill Laser is designed to satisfy many applications that require stable
working conditions with maximum quality and clean process fluid.
Compact and reliable machines designed for industrial applications and built
to the highest standards of quality and safety.
Laser marking, cutting and welding are typical industrial processes in which
the Hyperchill Laser features are necessary to achieve quality products
and optimise the production processes.
Maximum stability
•	 Non-ferrous water circuit. All the parts that come
    into contact with the cooling water are
	 made of stainless steel or plastic to guarantee
	 the quality of the process fluid.
• 	 The water temperature control is very precise in
    all working conditions thanks to a double hot gas
    valve that controls the flow of the refrigerant via
    the evaporator (± 0.5°C). (Optional for HLS005-
    HLS029; std for HLS039-HLS116)
Cooled water
Hot water
Correction factors
 A) Ambient temperature                   °C       5                10         15          20        25           30             35        40               45
    Correction factor (f1)                        1,05              1,05      1,05        1,05        1          0,95            0,89     0,83              0,77
To obtain the required cooling capacity multiply the value at nominal conditions by the above correction factors (i.e. cooling capacity = Pxf1xf2xf3, where P
is the cooling capacity at conditions (1). Hyperchill Laser, in its standard configuration, can operate up to ambient temperatures of max 45°C and min. 5°C
and water temperatures of max 30°C inlet and min. 0°C outlet. The above correction factors are approximative: for a precise selection always refer to the
software selection program.
Technical data Hyperchill Laser (HLS005-HLS116)
Model HLS                              005           007       010          015      022       029        039            046         057       076          090     116
Cooling capacity   1
                             kW         5            6,8       9,5          14,2     21,8      27,8       38,2          45,2         56,4     76,2          90,2    115,5
Compressor abs. Power1       kW        1,4           1,9       2,3           3,4      5,2       5,6       7,7           10,1         12,3     15,4          20,3    24,9
Cooling capacity2            kW        4,7           6,2       8,7           13      20,6      26,2       36,4          42,9         53,7     67,1          79,9    101,3
Compressor abs. Power2       kW        1,6           2,2       2,6           3,9      6,5       7,1       9,6            13          15,3     18,7          24,2    29,9
Power supply               V/ph/Hz       230/1/50                                                         400/3/50 no neutral
Protection index                               33                      44                                                       54
Refrigerant                                                                                             R407c
Compressors
Type                                                hermetic pistons                                                      hermetic scroll
Compressors/circuits                                                                    1/1                                                                 2/2
Max abs. power - 1 comp.     kW        1,5           1,8        3            2,9      6,9       7,8       11,1          13,7         16,8     11,1          13,7    16,8
Axial fans
Quantity                      n°                                       1                                           2                                  3
Max abs. Power - 1 fan       kW       0,12           0,1       0,1          0,61     0 61      0,78       0,61          0,61         0,61     0,78          0,78    0,78
Air flow                    m /h
                              3
                                      2300          4400      4100          7100     6800      9200      12400         12000      17400       25500        25000   26400
Pump P30
Max abs. power               kW        0,4           0,4       0,5           0,5     1,34      1,34       1,34          2,35         2,35     1,85          2,24    2,24
Water flow (nom/max)1       m3/h     0,8/2,4        1,3/3     1,5/6         2,3/6   3,5/9,6   4,5/9,6    6,3/9,6       7,6/18     9,3/18      13/18        15/26    19/27
Head pressure (nom/min)1   m H2O      30/6          28/6     31/20          29/20   28/17     27/17     24/17          28/22     27/22       26/22        28/16    25/16
Pump P50
Max abs. power               kW       0,75           0,75     0,75          0,75      2,3       2,3       2,3            2,3          2,3       4            4        4
Water flow (nom/max)   1
                            m /h
                              3
                                     0,8/2,4        1,3/3     1,5/6         2,3/6   3,5/9,6   4,5/9,6    6,3/9,6       7,6/18     9,3/18      13/18        15/26    19/27
Head pressure (nom/min)1   m H2O      58/22         52/22     52/35         50/35    58/38    55/38      48/37          47/37        46/37    47/28        45/28    41/28
Dimensions and weight
Width                        mm        530           530       980          980      1650      1650      1650           1650         2200     2200          2200    2200
Depth                        mm        760           760       540          540      750       750        750            750         750       890          890     890
Height                       mm        800           800      1260          1390     1390      1390      1390           1390         1390     1970          1970    1970
Connections in/out            in      3/4”           3/4”      3/4”         3/4”      1”        1”        1 ¼”          1 ¼”         1 ½”      2”            2”      2”
Tank capacity                 l        30             30       50            50      120       120        120            120         200       300          300     300
Weight (axial)               kg        95            110       150          160      270       340        380            390         470       750          870     960
Noise level
Sound pressure (axial)      dB(A)      52             53       53            50       50        53         52            52           56       58            58      58
(1) at water inlet/outlet temperature = 20/15°C, glycol 0%, ambient temperature 25°C. Net cooling capacity, without pump heat load.
(2) at water inlet/outlet temperature = 25/20°C, glycol 0%, ambient temperature 35°C. Net cooling capacity, without pump heat load.
(3) referred to free field conditions at a distance of 10m from unit, measured on condenser side, 1 m from ground.
Hyperfree (HDC040-HDC710)
Hyperfree is the ideal solution when the cooling water temperature is required to
be above room temperature. All models are easy to install, have low operating
and maintenance costs, are built for outdoor installation, with IP54
and galvanised aluminium panels that are epoxy coated. The new generation
of Parker Hiross drycoolers is a range of competitive products, which are robust
and reliable and offer excellent performance and a unique solution that can be
integrated with other components, dedicated to cooling industrial systems.
High efficiency fans combine low noise levels with reduced consumption.
                                                        Accessories:
                                                        •	 Support legs for horizontal installation
                                                        • 	 Fan wiring in an electrical box
                                                        • 	 Electrical panel with wiring and control
Versions:                                               • 	 Control panel with temperature step
                                                        	 (number of steps equal to number of fans)
•	 horizontally mounted coil configuration              • 	 Control panel with continuous temperature
• 	vertically mounted coil configuration                    control (0-100 %)
• 	 compact “V” configuration                           • 	 Nebulisation cooling
• 	 different levels of noise available upon request    • 	 Anti-corrosion treatment
Technical data Hyperfree
                Cooling         Water        Water pressure          Fans                    Max abs. power                       Conn.
                                                                              Air flow                            Noise level                  Dimensions            Weight
   Model       Capacity*        Flow             drops               n° x D                      (1 fan)                         IN/OUT
                   kW            m3/h             kPa              n° x mm     m3/h               kW                db (A)          in          (AXBxCxD)             kg
  HDC040          39,5            6,8             39,3               2x500    15729               0,8                  47         1"1/4      830x950x2042x530         97
  HDC060          59,1           10,2             37,3               3x500    23593               0,8                  49         1"1/2      830x950x2942x530         134
  HDC080          80,7           13,9             80,8               3x500    20638               0,8                  49           2"       830x950x2942x530         165
  HDC110         107,9           18,6             74,8               4x500    27517               0,8                  50           2"       830x950x3842x530         223
  HDC 140        137,7           23,7             17,3               2x630    33848               2,6                  59           2"      1255x1220x3235x850        380
  HDC 165        164,1           28,2             44,5               3x630    53118               2,6                  61           2"      1255x1220x4635x850        480
  HDC 190        192,2           33,0             39,7               3x630    51951               2,6                  61           2"      1255x1220x4635x850        525
  HDC 210        207,0           35,6             30,4               3x630    50709               2,6                  61         2"1/2     1255x1220x4635x850        570
  HDC 250        247,4           42,5             44,4               2x910    60529               3,6                  58         2"1/2     1494x1290x4635x850        580
  HDC 345        344,5           59,3              8,3               3x910    93167               3,6                  60           3"      1494x1290x6735x850        795
  HDC 440        438,1           75,3             48,7               4x910    112224              3,6                  60          2x3"     2290x1290x4650x790        940
  HDC 510        506,6           87,1             72,8               6x910    183482              3,6                  62          2x4"     2290x1290x6750x790        980
  HDC 580        579,7           99,7              9,7               6x910    175746              3,6                  62          2x4"     2290x1290x6750x790       1073
  HDC 660        655,1          112,7             71,2               6x910    168088              3,6                  62          2x4"     2290x1290x6750x790       1159
  HDC 710        714,4          122,9             18,6               8x910    244541              3,6                  63          2x4"     2290x1290x8850x790       1318
 HDCV 490        486,2           83,6             30,5               6x800    123000              2,0                  58        2 x DN80    2230x2208x4251          1323
 HDCV 540        535,5           92,1             34,2               6x910    185200              3,6                  64        2 x DN80    2230x2208x4251          1167
 HDCV 620        622,7          107,1             34,0               6x910    178100              3,6                  64        2 x DN80    2230x2208x5560          1347
 HDCV 720        717,2          123,3             42,0               8x910    247000              3,6                  65        2 x DN80    2230x2208x5560          1628
 HDCV 820        823,2          141,6             32,0               8x910    237700              3,6                  65        2 x DN80    2230x2208x6870          1826
& $
,1
287
                                                                                                                   %
& $
Hyperfree
CATICE-01-EN