Section 11
                                                                        Switchboards and Switchgear
                                                  Low Voltage Switchboards                                                 11-2
                                                                                                                                   11
                                                         Masterclad™ Medium Voltage Metalclad Switchgear (UL Listed) 11-37
                                                         Passive, Arc-Resistant Masterclad™ Medium Voltage Switchgear 11-38
                            Unit Substation       Unit Substations                                                        11-39
                                                                          whole new level, making the best switchboards in the market even better.
                                                                          Designed to be assembled anywhere without the need of heavy machinery or complex
                                                                          tools, FlexSeT is structured to be simple and intuitive, not only for assembly but also for
SWITCHBOARDS AND SWITCHGEAR
                              Bussing System
                              The bussing designs deliver
                              reliable connections with
                              quick and easy installation!
                              Visi-tite™ bolts ensure proper
                              torquing while the bus bridge
                              connects all phases simultaneously
                              in one simple operation. The bussing
                              has an enclosed design which greatly
                              reduces the points of exposed bus bars.
                                                                                                 Plug-on Neutral
                                                                                                 From Panelboards to
                                                                                                 Switchboards! Land the
                                                                                                 neutral closer to the load,
                                                                                                 reducing complexity and
                                                                                                 making wiring cleaner and
                                                                                                 more efficient.
                                                                                                                                                        11
                                                          •   2000 A I-Line™ feeder section with neutral bar within the stack—feeders from 15 A up
                                                              to 1200 A
                                                          •   Splice bridge with extending bussing
                                                          •   Visi-Tite™ bolts on all torque-required bussing connections
                                                          •   Swingable instrument compartment—separated and modularized
                                                          •   Available devices:
                                                              – PowerLogic™ power meter PM5563
                                                              – Surge protective device—rated up to 240 kA
                                                              – Maintenance mode setting (MMS) switch—compliant with NEC 240.87 Arc Energy
                                                                 Reduction requirements
                                                              – SmartCell™ compatible!
                                                          •   Digital Asset Lifecycle Management—all drawings, test reports, and instruction/
                                                              installation manuals are cyber-secured and available online
                                                                                                         Many applications are retrofittable. New functionality can be added by purchasing the
                                                                                                         kits below and installing on existing installed equipment. Certain spare parts are provided
                                                                                                         for replacement as needed by the customer.
SWITCHBOARDS AND SWITCHGEAR
                              [1]     Required for MMS/Trip unit, PM5563, or SPD installation only. An instrument compartment for field installation needs to be ordered with an instrument compartment cover (catalog number
                                      80210-181-50) in theTable 11.4 FlexSeT Spare Parts, page 11-6 table. Not required for ENCT or shunt trip kits.
                              [2]     Shunt trip kits to be shipped from partner to field job site for contractor installation only.
                              [3]     Plug-on neutrals have limited amounts of devices that can be provided. Please consult the FlexSeT PON instruction bulletin (NNZ9919501) to determine the right allocation per circuit
                                      breakers and other devices.
                               11-4                                                                                                                                                                   © 2022 Schneider Electric
                                                                                                                                                                                                           All Rights Reserved
                                                                                                                                                                                                                     12/7/2022
                                   FlexSeT (cULus Listed)                                                                     Low Voltage Switchboards
www.se.com/us                      Class 2700 / Refer to Instruction Bulletin JYT1078000
                                                                                                                                                                    11
                                  Main or feeder; MMS and
 600 V, 1200 A circuit breaker       ground fault capable      I-Line Group Mounted   6.0 A (LISG)   MMS, Trip Unit Power, and ENCT     RKA36120CU44AFLEX
 600 V, 1000 A circuit breaker   Main or feeder; MMS capable        Unit Mount        5.0 A (LSI)       MMS and Trip Unit Power         RKF36100CU43AFLEX
                                  Main or feeder; MMS and
 600 V, 1000 A circuit breaker       ground fault capable           Unit Mount        6.0 A (LISG)   MMS, Trip Unit Power, and ENCT     RKF36100CU44AFLEX
 600 V, 1200 A circuit breaker   Main or feeder; MMS capable        Unit Mount        5.0 A (LSI)       MMS and Trip Unit Power         RKF36120CU43AFLEX
                                  Main or feeder; MMS and                             6.0 A (LISG)   MMS, Trip Unit Power, and ENCT
 600 V, 1200 A circuit breaker       ground fault capable           Unit Mount                                                          RKF36120CU44AFLEX
 600 V, 1200 A circuit breaker   Main or feeder; MMS capable        Unit Mount        5.0 A (LSI)       MMS and Trip Unit Power          RKF36120U43AFLEX
                                  Main or feeder; MMS and                             6.0 A (LISG)   MMS, Trip Unit Power, and ENCT
 600 V, 1200 A circuit breaker       ground fault capable           Unit Mount                                                           RKF36120U44AFLEX
 600 V, 1600 A circuit breaker   Main or feeder; MMS capable        Unit Mount        5.0 A (LSI)       MMS and Trip Unit Power         RKF36160CU43AFLEX
                                  Main or feeder; MMS and                             6.0 A (LISG)   MMS, Trip Unit Power, and ENCT
 600 V, 1600 A circuit breaker       ground fault capable           Unit Mount                                                          RKF36160CU44AFLEX
 600 V, 1600 A circuit breaker   Main or feeder; MMS capable        Unit Mount        5.0 A (LSI)       MMS and Trip Unit Power          RKF36160U43AFLEX
                                  Main or feeder; MMS and
 600 V, 1600 A circuit breaker                                      Unit Mount        6.0 A (LISG)   MMS, Trip Unit Power, and ENCT      RKF36160U44AFLEX
                                     ground fault capable
 600 V, 2000 A circuit breaker   Main or feeder; MMS capable        Unit Mount        5.0 A (LSI)       MMS and Trip Unit Power         RKF36200CU43AFLEX
                                  Main or feeder; MMS and
 600 V, 2000 A circuit breaker                                      Unit Mount        6.0 A (LISG)   MMS, Trip Unit Power, and ENCT     RKF36200CU44AFLEX
                                     ground fault capable
 600 V, 2000 A circuit breaker   Main or feeder; MMS capable        Unit Mount        5.0 A (LSI)       MMS and Trip Unit Power          RKF36200U43AFLEX
                                  Main or feeder; MMS and
 600 V, 2000 A circuit breaker                                      Unit Mount        6.0 A (LISG)   MMS, Trip Unit Power, and ENCT      RKF36200U44AFLEX
                                     ground fault capable
 600 V, 2500 A circuit breaker   Main or feeder; MMS capable        Unit Mount        5.0 A (LSI)       MMS and Trip Unit Power          RKF36250U43AFLEX
                                  Main or feeder; MMS and
 600 V, 2500 A circuit breaker       ground fault capable           Unit Mount        6.0 A (LISG)   MMS, Trip Unit Power, and ENCT      RKF36250U44AFLEX
                                                         Spare Parts
                                                         These kits can be ordered for replacing parts, as necessary. The following table lists
                                                         commercial kits for parts sold in individual or paired quantities. These kits can be ordered
                                                         for replacing parts, as necessary. If a needed part or hardware is not listed, please
                                                         contact Customer Service or the Partner Support Program Team.
                                                                                                                          Features
                                                                                                                                 •   QED-2 Switchboards are designed, listed, and built to UL 891
NOTE: A single-row, I-Line distribution section is
shown on the right side of the switchboard photo                                                                                 •   Several tiered EcoStruxure communication offers available
above, while a double-row, I-Line distribution                                                                                   •   Switchboard ratings through 6000 A, 200 kA; higher amperages available
section is shown in the drawing below.                                                                                           •   Front accessible load connections
.                                                                                                                                •   Front and rear alignment standard
                                                                                                                                 •   Cable, busway, transformer, or remote QED switchboard incoming fed
                                                                                                                                 •   Hot or cold sequence utility metering
            800 A = 9 " & 1200 A = 15 "
                                                                                                                                                                                                                                          11
                                                                                                                                     Thermal-magnetic, PowerPact™ electronic, or MasterPact™ NW stored
                                                 63 " mounting height; 250 A max.
                     W = 48 "
                                                                                           • Flexible  branch circuit breaker locations: MasterPact and PowerPact circuit breakers
                                                                                              can be mixed in a single 30-inch wide section (15–2000 A)
                                                                                           • Compartmentalization:       separate compartments for circuit breakers, bussing, and load
SWITCHBOARDS AND SWITCHGEAR
                                                                                              cabling
                                                                                           • Available in 54-, 60-, 72-, and 80-inch deep construction
                                                                                           • Available in NEMA 3R outdoor walk-in enclosures
                                                                                           • Mixing   of MTZ and NW/NT circuit breakers are not offered in factory configured
                                                                                              sections but can be field retrofitted as such
                                                                                           • MasterPact and PowerPact circuit breakers are field maintainable
                                                                                           QED-6 switchboards are reliable power protection equipment when working with
                                                                                           telecommunication facilities, e-business servers, or mainframes that perform critical
                                                                                           business transactions. These types of facilities cannot afford downtime.
                                                                                           QED-6 rear-connected switchboards are designed as standalone switchboards or as an
                                                                                           integral part of the low voltage equipment lineup in a user’s power unit substation.
                                                        System Coordination
                                                        Short-time ratings are high, giving users excellent system coordination and selectivity
                                                        with downstream breakers.
                                                        High Short-Circuit Current Ratings (SCCR)
                                                        Up to 200 k AIR at 240 V, 150 k AIR at 480 V, and 100 k AIR at 600 V, which allows
                                                        customers to design systems with high fault current and paralleling schemes.
                                                        Arc Flash Limiting (LF) Feeder Breakers
                                                        High speed operation of MasterPact MTZ, NW and NT circuit breakers (150 k AIR at 480
                                                        V) helps reduce arc flash incident energy (cal/cm2) on downstream equipment.
                                                        Ease of Installation and Maintenance
                                                        Thru-the-door construction, an easy to operate drawout mechanism, and front access to
                                                        all control wiring make this equipment easy to install, maintain, and upgrade. Load
                                                        connections in the cable compartment are easily accessible in the rear of the
                                                        switchboard. Remote racking of the MasterPact circuit breaker is also available with the
                                                        optional remote racking tool, which, if required, is field installable.
                                                        Ability to Upgrade
                                                        UL Listed, field-installable accessories include: motor operators, shunt trips, under
                                                        voltage devices, trip units, and communication modules for trip units. Manually operated
                                                        circuit breakers are field convertible to electrical operation.
                                                        Open Communication System
                                                        The MicroLogic trip units in MasterPact circuit breakers use the Ethernet TCP/IP or
                                                        Modbus™ serial protocol. These are widely accepted protocols which allow QED-6 to be
                                                        integrated into new or many existing communication systems.
                                                        Adaptable
                                                        Drawout circuit breakers, front access control wiring, and expandable lineups are quickly
                                                        adaptable to changing load and control requirements.
11
                                                                                                                                                                  11
                                                                 metering requirements.
                                                                 Branches
                                                                 NQ distribution bus is rated 400 A and provides mounting space for QO™/QOB Type
                                                                 (150 A maximum) circuit breakers. Panel provides space for mounting 42 single pole
                                                                 circuit breakers. One or two individually mounted 225 A maximum circuit breakers can
                                                                 be added with bus connectors. (Order subfeed circuit breakers from Table 11.12 Subfeed
                                                                 Circuit Breakers (Series E4) , page 11-14.)
                                                                 I-Line™ distribution bus is rated 400, 600, or 800 A and will accept 27 inches of I-Line
                                                                 circuit breakers on the left side with a maximum frame size of “J” . The right side will
                                                                 accept either a QO plug-on distribution panel (240 V only) or LA or LH I-Line circuit
                                                                 breaker, which allows for a back-fed solar power source.
                                                                 Enclosure
                                                                 Totally enclosed front accessible with ANSI 49 gray baked enamel finish. Dimensions are
                                                                 90 in. (H) x 36 in. (W) x 14 in. (D) for indoor and 90 in. (H) x 36 in. (W) x 24.5 in. (D) for
                                                                 outdoor enclosures.
                                                                                   800
                                                                                                   Electronic                                    None          SB348WSJS               SB348WRJS
                                                                                                                        100           65
                                                                                                   LSI Power                                     I-Line         SB348ISJP               SB348IRJP
                                                                                                   Electronic                                    None          SB348WSJP               SB348WRJP
SWITCHBOARDS AND SWITCHGEAR
                              [1]    Can be used on 3Ø3W Delta voltage systems (for example, 240 V Delta or 480 V Delta).
                               11-12                                                                                                                                             © 2022 Schneider Electric
                                                                                                                                                                                      All Rights Reserved
                                                                                                                                                                                                12/7/2022
                                     Merchandised, Service Selection                                                                                 Speed-D™ Switchboards
 www.se.com/us
                                     Class 2710 / Refer to Catalog 2700CT1101
Table 11.7: Single Main Fusible Disconnect with Distribution (Series E4)
                                                               Mains                                         SCCR            SCCR                 Fusible Disconnect Catalog No.
         System                     Service                   Ratings               Distribution
                                    Voltage                                                                  240 V           480 V
                                                                (A)                   Interior               Max.            Max.               Indoor                         Outdoor
                                                                                          NQ                   65             —               SF124QS                          SF124QR
                                                                400                     I-Line                100             —                SF124IS                          SF124IR
         1Ø3W                       120/240                                             None                  200             —               SF124WS                          SF124WR
                                                                                        I-Line                100             —               SF126IS                          SF126IR
                                                                600
                                                                                        None                  200             —               SF126WS                          SF126WR
                                  208Y/120
        3Ø4W [2]                                                400                      NQ                    65              —              SF324QS                          SF324QR
                                   240/120
                                  208Y/120
        3Ø4W [2]                                                400                     None                  200              —              SF324WS                          SF324WR
                                   240/120
                                  208Y/120
        3Ø4W [2]                   240/120                      400                     I-Line                100              65              SF344IS                         SF344IR
                                  480Y/277
                                  208Y/120
        3Ø4W [2]                   240/120                      400                     None                  200             200             SF344WS                          SF344WR
                                  480Y/277
                                  208Y/120
        3Ø4W [2]                   240/120                      600                     I-Line                100              65              SF346IS                         SF346IR
                                  480Y/277
                                  208Y/120
        3Ø4W [2]                   240/120                      600                     None                  200             200             SF346WS                          SF346WR
                                  480Y/277
                                  208Y/120
        3Ø4W [2]                   240/120                      800                     I-Line                100              65              SF348IS                         SF348IR
                                  480Y/277
                                  208Y/120
        3Ø4W [2]                   240/120                      800                     None                  200             200             SF348WS                          SF348WR
                                  480Y/277
                                                                                Selection
Table 11.9: I-Line Distribution Section (Series E4)
                              Mains                         SCCR        SCCR                                                                                                Catalog No.
  System       Service       Ratings      Distribution                                                              Distribution Type
               Voltage                                      240 V       480 V
                               (A)          Interior        Max.        Max.                                                                                          Indoor        Outdoor
              208Y/120                                                           Add-on distribution section, must be connected to an SB UCT and main
                                                                                                                                                                                                  11
      3Ø4W     240/120        800             I-Line          65 k       65 k    section without distribution panel, such as SB348WS. An I-Line plug-on              SBAD800       SBAD800R
              480Y/277                                                           subfeed lug kit must be ordered to terminate the distribution section.
              208Y/120                                                           Stand-alone distribution section not connected to an SB section. A back-fed
      3Ø4W     240/120        800             I-Line         125 k      100 k    main circuit breaker or I-Line plug-on subfeed lug kit must be ordered to          SBSAD800       SBSAD800R
              480Y/277                                                           terminate the distribution section. (Non-ULSE)
[2]     Can be used on 3Ø3W Delta voltage systems (for example, 240 V Delta or 480 V Delta).
[3]     QMB/QMJ fusible switches, maximum 400 A, SCCR based on Class J, R, or T fuses. QMB plug-in circuit breaker rating is equal to the lowest rating of the circuit breaker.
[4]     Multiple mains—provisions for mounting 30 inches of fusible devices. No more than six main devices permitted per NEC.
[5]     6-jaw meter socket can also be used on 4- and 5-jaw applications.
[6]     Door with provisions for mounting meter socket.
[7]     All EUSERC Utilities (except Arizona Public Service and Salt River Project) require a lug landing kit SA8LL.
                                                                                                         Ordering Information
                                                                                                         1. Service section: Order service section from Table 11.6 Single Main Circuit Breaker
                                                                                                            with Distribution (Series E4), page 11-12 , Table 11.7 Single Main Fusible Disconnect
                                                                                                            with Distribution (Series E4), page 11-13 , or Table 11.8 Multiple Mains—Fusible
                                                                                                            (Series E4) , page 11-13, as determined by mains rating, voltage, and system.
                                                                                                         2. Meter doors: Order meter door from Table 11.10 Meter Door Selection, page 11-13
                                                                                                            as determined by the height and utility metering requirements.
                                                                                                         3. Accessories and subfeeds: Order as required from Table 11.11 Accessories, page
11
                                                                                                            11-13 and/or Table 11.12 Subfeed Circuit Breakers (Series E4) , page 11-14.
                                                                                                         4. Circuit breakers and switches: Order devices from pages listed below as
                                                                                                            determined by voltage, trip rating, AIR, and mounting space.
SWITCHBOARDS AND SWITCHGEAR
                                                                                                                                                                           11
                                                                               1Ø3W, 3Ø3W, 3Ø4W                         (Main circuit breaker or main lugs only)
                                                                                      50/60 Hz
                          Power-Zone 4
             Front Accessible Low Voltage Switchgear
                          (Class 6037)
  NOTE: Shown with MasterPact MTZ circuit
 breakers. MasterPact NW circuit breakers are
                also available.
                                NOTE: Shown with MasterPact NW ArcBlok        • Section barriers (rear, cable, and side)
                                circuit breakers. MasterPact MTZ2,3 ArcBlok   • Circuit breaker remote racking
                                      circuit breakers are also available.    • ANSI Type 2B rated arc plenum exhaust
SWITCHBOARDS AND SWITCHGEAR
                                                                                                                                                                                                        11
                                                                                         25E                                                                                 5GS025
                                                                                         30E                                                                                 5GS030
                                                                                         40E                                                                                 5GS040
                                                                                         50E                                                                                 5GS050
                                                                                                                    D                          12”
                                                                                         65E                                                                                 5GS065
                                                                                         80E                                                                                 5GS080
                                                                                        100E                                                                                 5GS100
                                                                                        125E                                                                                 5GS125
                                                                                        150E                                                                                 5GS150
                                                                                                                    D                          12”
                                                                                        175E                                                                                 5GS175
                                                                                        200E                                                                                 5GS200
[1]   Contact your Schneider Electric representative for current stock quantities.
[2]   Includes one set of three fuses, packed in a single box.
[3]   Arresters are line side connected.
                                                                                                                                            25.15                                           25.20
                                                                                                                             2.20           639                                              640
                                                                                                                              56
                                                                                                                            66.00
                                                                                                                            1677
                                                                                                                                                                                                             47.52
                                                                                                                                                                                                             1207
                                                                                                                                                                                                         29.00
                                                                                                                                                                                                          737
                                                                                                                                    25.20
                                                                                                                                    640
SWITCHBOARDS AND SWITCHGEAR
                                                                                                                                                                                                25.15
                                                                                                                                                                                                 639
                                                                                                                                                                                  2.20         20.75
                                                                                                                                                                                   56           527
                                                                                                                                                                                                                 23.78
                                                                                                                                                                                                                   604
                                                                                                                                                                                                            18.38
                                                                                                                                                                                                             467
                                                                                                                                                    47.52
                                                                                                                                                    1207
                                                                                                                                                                                                                 2.70
                                                                                                                                                                                                                   69
                                                                                                                                               15.35
                                                                                                                                                  390
                              [4]   For fuses produced by other manufacturers, contact your nearest Schneider Electric sales office or your local Schneider Electric distributor.
                              [5]   Current-limiting fuses will increase the integrated short-circuit ratings beyond the non-fusible units. Contact your nearest Schneider Electric sales office or your local Schneider Electric
                                    distributor.
                               11-18                                                                                                                                                                    © 2022 Schneider Electric
                                                                                                                                                                                                             All Rights Reserved
                                                                                                                                                                                                                       12/7/2022
                            Premset™                                                                  Medium Voltage Metal-Enclosed
www.se.com/us
                                                                                                                         Switchgear
                            Class 6045 / Refer to Catalog 6045CT1601
11
                                                                                              Front
                                                                         Optional
                                                                         low voltage
                                                                         compartment
                                                                         Main bus
                                                                         compartment
                                                                         Switch with                                                                                   90.00
                                                                         enclosure                                                                                      2286
                                                                         Mechanism
                                                                         compartment
11
                                                                         Fuse cable
                                                                                                                                       37.25
                                                                         compartment                                                    946
SWITCHBOARDS AND SWITCHGEAR
                                                                         Fuse/cable
                                                                         access
                                                                         panel                   37.25
                                                                                                  946
                                                                                                                                                  W           14.75
                                                                                                                                                               375
                                                                                             Right Side
                                                                                               View                                            Plan           Front
                                                                                                                                               View           View
                                                                        Table 11.19: HVL/cc Load Interrupter Switches— Full Range 600/1200 A Ratings
                                                                         Switch (kV)—maximum design              5.5        17.5        17.5           25.8            38
                                                                         BIL (kV)                                60          95          110            125            150
                                                                         Frequency (Hz)                         50/60       50/60       50/60          50/60          50/60
                                                                         Withstand (kV)                          19          36          36             50             80
                                                                         Continuous current (A)               600/1200    600/1200    600/1200          600            600
                                                                         Interrupting current (A)             600/1200    600/1200    600/1200          600            600
                                                                         Fault close
                                                                         (kA asymmetrical)                       40          40          40             32             32
                                                                         Momentary current
                                                                         (kA asymmetrical)                       40          40          40             32             32
                                                                         Short time current
                                                                         (kA symmetrical)                        25          25          25             25             25
                                                                         Electrical endurance                 100/600 A   100/600 A   100/600 A
                                                                         (number of operations at 80% P.F.)                                             100           100
                                                                                                              26/1200 A   26/1200 A   26/1200 A
                                                                         Mechanical endurance
                                                                         (number of operations)                 1000        1000        1000           1000           1000
                                                                               To                         To                          To
                                                                             Ground                     Ground                      Ground
                                                                              Bus                        Bus                         Bus
                                                            Options
                                                            •   Internal ground switch: Has full fault making capability
                                                            •   Fuselogic™ system
                                                            •   Infrared viewing windows
                                                            •   Class I, Division 2
                                                            •   Fast auto transfers
                                                            •
                                                                                                                                                                           11
                                                                Fuse/cable access panel interlocked with switch
                      Listed Metal-Enclosed
                      Interrupter Switchgear                •   Front access only options available at system voltages below 17.5 kV
                                                            •   Animated mechanism mimic bus
                                                            •   Padlocking provision—open or closed (OTM); open-only (SEM)
                                                            •   Top or bottom cable entry
                                                            •   UL/CUL Listed, IEEE C37.20.3
                                                            •   Live line indicators on all incoming switch bays and outgoing feeder circuits
                                                            •   Cable lugs included for one cable per phase
                                                            •   Tin plated copper bus for lineups
                                                            Table 11.20: Surge Arresters
                                                                       System L-L Voltage kV                                        Arrester MCOV-kV
                                                                                                                   Effectively                Impedance Grounded
                                                                   Nominal                Maximum                  Grounded                     and Ungrounded
                                                                                                                 Neutral Circuits                   Circuits
                                                                     2.4                     2.54                      —                              2.55
                                                                    4.16                      4.4                     2.55                            5.1
                                                                     4.8                     5.08                      —                              5.1
                                                                     6.9                     7.26                      —                              7.65
                                                                    12.0                     12.7                     7.65                           12.70
                                                                    12.47                    13.2                     7.65                           12.70
                                                                    13.2                     13.97                     8.4                             —
                                                                    13.8                     14.52                     8.4                             —
                                                                                              M
                                                                                                                                                    M
                                                                         90.00   450E
                                                                         2286                 M                            90.00
                                                                                                                            2286       450E
11
                                                                                                                                                    M
SWITCHBOARDS AND SWITCHGEAR
                                                                                                  37.25
                                                                                    14.75          946                                                   37.25
                                                                                        375                                               14.75           946
                                                                                                                                              375
                                                                               5 kV Indoor N1                                    5 kV Indoor N1
                                                                          Top Cable In/Bottom Cable                       Top Cable In/Bottom Cable Out
                                                                           Out Switch in Position A                            Switch in Position B
                                                                                                                                                                                      11
                                                                   HVLCCMBA20A20                     A         20.00           508               A        20.00             508
                                                                   HVLCCMBB14B14                     B         14.75           375               B        14.75             375
                                                                   HVLCCMBB14B20                     B         14.75           375               B        20.00             508
                                                                   HVLCCMBB20B14                     B         20.00           508               B        14.75             375
                                                                   HVLCCMBB20B20                     B         20.00           508               B        20.00             508
                                                           Ratings
                                                           HVL/cc Switch with manually operated type OTM mechanism in cubicle enclosure (does
                                                           not include internal ground switch). Ratings are based on an X/R ratio of 1.6.
                                                                                     600 A “Single” HVL/cc Switch with PROVISIONS ONLY for Square D™ brand
                                                           600 A,                    Current-Limiting, Non-Disconnect Type Fuses for Cable Connection to Power-
                                                           tin-plated,               Dry™, Power-Cast™, and Uni-Cast™ Transformers
                                                           copper bus                (FLC = 300 A MAXIMUM)
                                                                                     RH—Transformer on right, LH—Transformer on Left
                                                                                     Application A = Top Entry (Incoming Cables)
                                                                                     Application B = Bottom Entry (Incoming Cables)
                                                                         M
                                        90.00               200E
                                        2286                                         Table 11.29: 600 A “Single” HVL/cc Switch Selection
11
                                                                              946
                                                    375            375
                                                                                            HVLCCA20405DGR                 4.76           10–450E         A          20.00           508       RH
                                                                                            HVLCCA14405DGL                 4.76           10–450E         A          14.75           375       LH
                                                                                            HVLCCA20405DGL                 4.76           10–450E         A          20.00           508       LH
                                                                                            HVLCCA14415DGR                  15            10–200E         A          14.75           375       RH
                                                                                            HVLCCA20415DGR                  15            10–200E         A          20.00           508       RH
                                                Listed Metal-Enclosed                       HVLCCA14415DGL                  15            10–200E         A          14.75           375       LH
                                                Interrupter Switchgear
                                                                                            HVLCCA20415DGL                  15            10–200E         A          20.00           508       LH
                                                                                            HVLCCB14405DGR                 4.76           10–450E         B          14.75           375       RH
                                                                                            HVLCCB20405DGR                 4.76           10–450E         B          20.00           508       RH
                                                                                            HVLCCB14405DGL                 4.76           10–450E         B          14.75           375       LH
                                                                                            HVLCCB20405DGL                 4.76           10–450E         B          20.00           508       LH
                                                                                            HVLCCB14415DGR                  15            10–200E         B          14.75           375       RH
                                                                                            HVLCCB20415DGR                  15            10–200E         B          20.00           508       RH
                                                                                            HVLCCB14415DGL                  15            10–200E         B          14.75           375       LH
                                                                                            HVLCCB20415DGL                  15            10–200E         B          20.00           508       LH
                                                                                     NOTE: Switches with transformer connections are painted ANSI 49. Standalone
                                                                                     switches are painted ANSI 61. Transformer connections in HVL/cc switches are
                                                                                     based on standard Square D™ brand transformer connections. If these switches are
                                                                                     used to connect to other manufacturers' transformers, then connections must match
                                                                                     standard Square D™ brand transformer connections. (Cable connections are
                                                                                     furnished with the transformer.)
                                                                               600 A “Duplex” HVL/cc Switch with PROVISIONS ONLY for Square D™ brand
                                                                               Current-Limiting, Non-Disconnect Type Fuses for Cable Connection to Power-Dry,
                                                                               Power-Cast, and Uni-Cast Transformers
                                                                               • FLC = 300 A maximum
                                                                               • RH—Transformer on right
                                                                               • LH—Transformer    on left includes mechanical interlock to prevent paralleling of
                                                                                                                                                                                          11
                                                                                 sources
                                                                               • Application A = top entry (incoming cables)
                                                                               • Application B = bottom entry (incoming cables)
                                                                               Table 11.31: 600 A “Duplex” HVL/cc Switch Selection
                                                                                                                                                                 Width
                                                                                                Catalog                kV                     Appli-
                                                                                                                      Rating   Fuse Range                                      RH / LH
                                                                                                  No.                                          cati-      in             mm
                                                                                                                                                on
                                                                                         HVLCCA14505DGR                4.76     10–450E         A        14.75           375     RH
                                                                                         HVLCCA20505DGR                4.76     10–450E         A        20.00           508     RH
                                                                                         HVLCCA14505DGL                4.76     10–450E         A        14.75           375     LH
                                                                                         HVLCCA20505DGL                4.76     10–450E         A        20.00           508     LH
                                                                                         HVLCCA14515DGR                 15      10–200E         A        14.75           375     RH
                                                                                         HVLCCA20515DGR                 15      10–200E         A        20.00           508     RH
                                                                                         HVLCCA14515DGL                 15      10–200E         A        14.75           375     LH
                                                                                         HVLCCA20515DGL                 15      10–200E         A        20.00           508     LH
                                                                                         HVLCCB14505DGR                4.76     10–450E         B        14.75           375     RH
                                                                                         HVLCCB20505DGR                4.76     10–450E         B        20.00           508     RH
                                                                                         HVLCCB14505DGL                4.76     10–450E         B        14.75           375     LH
                                                                                         HVLCCB20505DGL                4.76     10–450E         B        20.00           508     LH
                                                                                         HVLCCB14515DGR                 15      10–200E         B        14.75           375     RH
                                                                                         HVLCCB20515DGR                 15      10–200E         B        20.00           508     RH
                                                                                         HVLCCB14515DGL                 15      10–200E         B        14.75           375     LH
                                                                                         HVLCCB20515DGL                 15      10–200E         B        20.00           508     LH
[7] Each set of fuses contains three fuses, so, for example, two sets of fuses yield a total of six fuses.
                                                                   Standard Features
                          Listed Metal-Enclosed
                          Interrupter Switchgear                   • 11 gauge steel enclosure
                                                                   • Direct drive mechanism
                                                                   • Permanently attached operating handle
                                                                   • Visible isolation viewing window
                                          H
                                                                   • Mechanical interlocked fuse access door
                                                                   • Provision for padlock and key interlock
                                                                   • Highly flexible design
                                                                   • ANSI 61 paint
                                                                   Options
                               D                     W
                                                                   • Outdoor construction
                                                                                                                                                                    11
                    Side view              Front view
                                                                   • Square D™ brand DIN-style current-limiting fuses
                     Recommended power                             • Boric acid fuses
                      cable conduit area                           • Silver or tin plated copper bus
                       2.00           38.00              2.00      • 600, 1200, or 2000 A main bus
                          51            965               51
                                                                   • Heat shrink insulated bus
                                       34 x 6
                                     864 x 152
                                                                   • Motor operator
                          4.00
                           102
                                       34 x 6
                                     864 x 152                     • Shunt trip
                      D
                          Conduit
                                       Control
                                    Conduit Area
                                                          D1       • Fuselogic™ tripping system
                                        2x4
                                      51 x 102                     • Roof bushings
                                                         6.36
                                                                   • Key interlocks
                                      35.74
                                                         162
                                                                   • Surge arresters
                      1.13
                         29             908                        • Utility metering bays
                         .875 Mounting Hole
                   (4 Places for .75 Anchor Bolts)                 • Duplex switch
                                                                   • Transformer connections
                                                                   • Infrared windows for thermal scanning of connections
                                                                   Fuselogic™
                                                                   Fuselogic is a protection system that provides the ultimate in medium voltage fuse
                                                                   protection. This patented system utilizes the Square D™ brand current-limiting fuses
                                                                   with mechanical sensors that function without any auxiliary power requirements. Several
                                                                   combinations of Fuselogic functions can be combined to provide simple blown fuse
                                                                   indication contacts with mechanical lockout to anti-single phasing protection. Anti-single
                                                                   phasing requires the optional stored energy mechanism (SEM). Fuselogic is available on
                                                                   both HVL/cc™ and HVL switches.
                                                                                                               Table 11.34: 600 A “Single” Switch with PROVISIONS ONLY for Square D™ brand
                                                                                                               Current-Limiting, Non-Disconnect Type Fuses
                                                                                                                          Catalog No.                kV Rating                   Fuse Range                 Enclosure Type
                                                                                                                         HVL305DEG                     4.76                       10–450E              NEMA 1
11
                                                                                                               Table 11.35: 600 A “Single” Switch with PROVISIONS ONLY for S&C Boric Acid
                                                                                                               Non-Disconnect Type Fuses [8]
                                                                                                                          Catalog No.                kV Rating                   Fuse Range                 Enclosure Type
                                                                                                                          HVL305BG                     4.76                       10E–400E             NEMA 1
                                                                                                                          HVL305BW                     4.76                       10E–400E             NEMA 3R
                                                                                                                          HVL315BG                      15                        10E–400E             NEMA 1
                                                                                                                          HVL315BW                      15                        10E–400E             NEMA 3R
                                                                                                                          HVL317BG                      17                        10E–400E             NEMA 1
                                                                                                                          HVL317BW                      17                        10E–400E             NEMA 3R
                              [8]      Boric acid fuses may increase lead times. Contact the factory for availability.
                               11-28                                                                                                                                                                        © 2022 Schneider Electric
                                                                                                                                                                                                                 All Rights Reserved
                                                                                                                                                                                                                           12/7/2022
                                   HVL                                                                                                      Medium Voltage Metal-Enclosed
 www.se.com/us
                                                                                                                                                               Switchgear
                                   Class 6040 / Refer to Catalog 6040CT9201 or Brochure 6040BR9401
                                                                              Provisions for Future Expansion
                                                                              All “single” Digest switches have provisions for future expansion on either side. Order
                                                                              kits HVMB for top crossover copper 600 A bus and HVLC for line connections to the top
                                                                              bus. (See Table 11.43 Factory Modifications, page 11-30.)
                                                                              HVL Switches for Power-Dry II™, Power-Cast II™, and Uni-Cast
                                                                              II™ Transformer Connections
                                                                              HVL switches can be configured for close coupling cable connections to listed dry type
                                                                              transformers for primary main switches of unit substations. These are listed in the tables
                                                                              below with current-limiting or boric acid fuses. Both single and duplex switch mains are
                                                                              included in this selection. Transformers are listed on Digest Section 14: “Medium Voltage
                                                                              Distribution Transformers” and may not be suitable for close coupling. For transformer
                                                                              availability and specific configurations, contact your local Schneider Electric sales office.
                                                                              All connections in this digest are based on standard Square D™ brand transformer
                                                                              connections. If these switches are used to connect to other manufacturers’ transformers,
                                                                              then connections must coordinate with
                                                                              standard Square D™ brand transformer connections. (Cable connections are furnished
                                                                              with the transformer.)
                                                                              Table 11.39: 600 A “Single” Switch with PROVISIONS ONLY for Square D™ brand
                                                                              Current-Limiting, Non-Disconnect Type Fuses for Cable Connection to Power-Dry
                                                                              II, Power-Cast II, and Uni-Cast II Transformers
                                                                              (FLC = 300 A max.) RH—Transformer on Right, LH—Transformer on Left
                                                                                           Catalog                        kV
                                                                                                                                          Fuse Range             Enclosure Type    RH / LH
                                                                                             No.                        Rating
                                                                                         HVL405DEGR                      4.76               10–450E           NEMA 1                 RH
                                                                                         HVL405DEGL                      4.76               10–450E           NEMA 1                 LH
                                                                                       HVL405DEWRH                       4.76               10–450E           NEMA 3R                RH
                                                                                        HVL405DEWLH                      4.76               10–450E           NEMA 3R                LH
                                                                                        HVL415DEGR1                       15                10–100E           NEMA 1                 RH
                                                                                        HVL415DEGR2                       15               125–200E           NEMA 1                 RH
                                                                                        HVL415DEGL1                       15                10–100E           NEMA 1                 LH
                                                                              Table 11.40: 600 A “Duplex” Switch with PROVISIONS ONLY for Square D™ brand
                                                                              Current-Limiting, Non-Disconnect Type Fuses for Cable Connection to Power-Dry
                                                                              II, Power-Cast II, and Uni-Cast II Transformers
                                                                              (FLC = 300 A max.) RH—Transformer on Right, LH—Transformer on Left
                                                                                           Catalog                        kV              Fuse Range             Enclosure Type
                                                                                             No.                        Rating                                                     RH / LH
                                                                                         HVL505DEGR                      4.76               10–450E           NEMA 1                 RH
                                                                                         HVL505DEGL                      4.76               10–450E           NEMA 1                 LH
                                                                                       HVL505DEWRH                       4.76               10–450E           NEMA 3R                RH
                                                                                        HVL505DEWLH                      4.76               10–450E           NEMA 3R                LH
                                                                                        HVL515DEGR1                       15                10–100E           NEMA 1                 RH
                                                                                        HVL515DEGR2                       15               125–200E           NEMA 1                 RH
                                                                                                                                                                                                  11
                                                                                        HVL515DEGL1                       15                10–100E           NEMA 1                 LH
                                                                                        HVL515DEGL2                       15               125–200E           NEMA 1                 LH
                                                                                       HVL515DEWR1H                       15                10–100E           NEMA 3R                RH
                                                                                       HVL515DEWR2H                       15               125–200E           NEMA 3R                RH
                                                                                       HVL515DEWL1H                       15                10–100E           NEMA 3R                LH
                                                                                       HVL515DEWL2H                       15               125-200E           NEMA 3R                LH
                                                                              Table 11.41: 600 A “Single” Switch with PROVISIONS ONLY for S&C Boric Acid
                                                                              Non-Disconnect Type Fuses for Cable Connection to Power-Dry II, Power-Cast II,
                                                                              and Uni-Cast II Transformers [9]
                                                                              (FLC = 300 A max.) RH—Transformer on Right, LH—Transformer on Left
                                                                                           Catalog                        kV
                                                                                                                        Rating            Fuse Range             Enclosure Type    RH / LH
                                                                                             No.
                                                                                          HVL405BGR                      4.76              10E–400E           NEMA 1                 RH
                                                                                          HVL405BGL                      4.76              10E–400E           NEMA 1                 LH
                                                                                         HVL405BWRH                      4.76              10E–400E           NEMA 3R                RH
                                                                                         HVL405BWLH                      4.76              10E–400E           NEMA 3R                LH
                                                                                          HVL415BGR                       15               10E–400E           NEMA 1                 RH
                                                                                          HVL415BGL                       15               10E–400E           NEMA 1                 LH
                                                                                         HVL415BWRH                       15               10E–400E           NEMA 3R                RH
                                                                                         HVL415BWLH                       15               10E–400E           NEMA 3R                LH
[9] Includes fuse holder only. See Table 11.45 Boric Acid Fuses , page 11-32 for fuse refills. Boric acid fuses may increase lead times. Contact the factory for availability.
                                                                                                                       Catalog                                                     Description
                                                                                                                         No.
                                                                                                                        HVMB              Main Bus Kit, 600 A copper
                                                                                                                                          Line side connector kit (main bus) 600 A
SWITCHBOARDS AND SWITCHGEAR
                                                                                                             Standard Features
                                                                                                             •   Switches for transformer primaries are cable connected only.
                                                                                                             •   Key interlocks must be ordered and coordinated by customer.
                                                                                                             •   Standard color is ANSI 61 for standalone units; ANSI 49 for switches connecting to
                                                                                                                 transformers.
                                                                                                             •   If switches are purchased to coordinate with Square D™ brand transformers,
                                                                                                                 composite drawings and shipment coordination will not be available.
                                                                                                             •   Switches are not designed for any special dimensions for retrofit purposes. For
                                                                                                                 dimensions other than shown, contact your nearest Schneider Electric sales office or
                                                                                                                 your local Schneider Electric distributor.
                                                                                                             Ordering Information
                                                                                                             1. Select switch catalog number based on fused or unfused and enclosure type.
                                                                                                             2. Select catalog numbers for factory modifications from the table above.
                                                                                                             3. If fused, select fuse from Table 11.44 DIN/E Current-Limiting Fuses, Non-
                                                                                                                Disconnecting Type (Extended Travel Blown Fuse Indicator), page 11-31 or Table
                                                                                                                11.45 Boric Acid Fuses, page 11-32.
                                                                                                             4. Price switch and fuses separately. Switches are furnished with provisions only for
                                                                                                                current-limiting fuse or boric acid fuse.
                              [10]   Includes fuse holder only. See Table 11.45 Boric Acid Fuses , page 11-32 for fuse refills. Boric acid fuses may increase lead times. Contact the factory for availability.
                              [11]   Load side connected
                               11-30                                                                                                                                                                        © 2022 Schneider Electric
                                                                                                                                                                                                                 All Rights Reserved
                                                                                                                                                                                                                           12/7/2022
                                    HVL                                                                                                      Medium Voltage Metal-Enclosed
 www.se.com/us
                                                                                                                                                                Switchgear
                                    Class 6040 / Refer to Catalog 6040CT9201 or Brochure 6040BR9401
                                                                               Square D™ Brand DIN/E Fuse Selection Tables—HVL
                                                                               Table 11.44: DIN/E Current-Limiting Fuses, Non-Disconnecting Type [12][13][14]
                                                                               (Extended Travel Blown Fuse Indicator)
                                                                                                                              Fuse Mounting Clip [15]
                                                                                       Continuous                                                                                    Catalog
                                                                                        Current                        Centers                   Diameter                           No. [16][17]
                                                                                                                         (in)                      (mm)
                                                                                5 kV Fuse
                                                                                           10E                           17.4                           51                           55DE010
                                                                                           15E                           17.4                           51                           55DE015
                                                                                           20E                           17.4                           51                           55DE020
                                                                                           25E                           17.4                           51                           55DE025
                                                                                           30E                           17.4                           51                           55DE030
                                                                                           40E                           17.4                           51                           55DE040
                                                                                           50E                           17.4                           51                           55DE050
                                                                                           65E                           17.4                           51                           55DE065
                                                                                           80E                           17.4                           51                           55DE080
                                                                                         100E                            17.4                           51                           55DE100
                                                                                         125E                            17.4                           76                           55DE125
                                                                                         150E                            17.4                           76                           55DE150
                                                                                         175E                            17.4                           76                           55DE175
                                                                                         200E                            17.4                           76                           55DE200
                                                                                         250E                            17.4                           76                           55DE250
                                                                                         300E                            17.4                           76                           55DE300
                                                                                         350E                            17.4                           76                           55DE350
                                                                                         400E                            17.4                           76                           55DE400
                                                                                         450E                            17.4                           76                           55DE450
                                                                                15 kV Fuse
                                                                                           10E                           17.4                           51                          175DE010
                                                                                           15E                           17.4                           51                          175DE015
                                                                                           20E                           17.4                           51                          175DE020
                                                                                           25E                           17.4                           51                          175DE025
                                                                                           30E                           17.4                           51                          175DE030
                                                                                           40E                           17.4                           76                          175DE040
                                                                                           50E                           17.4                           76                          175DE050
11
[12]   Square D™ brand DIN/E fuses are shown in this table. For fuses produced by other manufacturers, contact your nearest Schneider Electric sales office or your local Schneider Electric
       distributor.
[13]   Current-limiting fuses will increase the integrated short-circuit ratings beyond the non-fusible units. Contact your nearest Schneider Electric sales office or your local Schneider Electric
       distributor.
[14]   Caution—These fuses will not work for the MiniBreak. See Table 11.16 Current-Limiting Fuses, page 11-17 for the appropriate MiniBreak fuses.
[15]   All fuses are single barrel arrangement with ferrule diameters per the chart.
[16]   Contact your Schneider Electric representative for current stock quantities.
[17]   Includes one set of three fuses, packed in a single box.
11
                                                                        Nominal voltage
                                                                        (kV)                   15 27 38            15 27 38        15 27 38        15 27 38          15 27 38
                                                                        Busbar system
                                                                                              1200/2000           1200/2000        1200/2000      1200/2000          1200/2000
SWITCHBOARDS AND SWITCHGEAR
                                                                                                                                        O
                                                                                                                      I      D
VIP
                                                                                                                                                        11
                                                              – disconnector operating mechanism
                                                              – operating mechanism of the circuit breaker
                                                              – protection relay VIP, Sepam, or Micom
                                                              – zero sequence current transformer CSH 30
                    YO 1      Mitop   VIP
                                                           •   MV cable compartment
                                                               – bushings for cable connection
                            CSH 30
                                                               – Three CRc current sensors per phase
                                                           •   Stainless steel, gas-tight tank
                                                               – busbar system
                                                               – three position disconnector
                                                               – circuit breaker
Module D
                                                                                                                                     D+O
                                                                                                                      DO
                                                                                                                                     Transformer protection + Outgoing line
                                                                                                                                     (I + D + O)
                                                                                                                     I DO            Incoming line + Transformer protection +
                                                                                                                                     Outgoing line
                                                                                                                                     (I + I + D + O)
                                                                                                                    I I DO           Two Incoming lines + Transformer
                                                                                                                                     protection + Outgoing line
Recommended Configurations
                                                                                                                                                                      11
                                                               •   Automatic shutters driven by breaker racking mechanism
                                                               •   Closed door breaker position indication
                                                               •    Closed door breaker racking mechanism
                                                               •   Insulated main bus—aluminum or copper
                                                               •   Standard glass polyester insulators or optional epoxy and porcelain insulators
                                                               •   Mechanical interlocks
                                                               •   Disconnect type CPT and VT trucks
                                                               •   Grounded breaker truck in and between test/disconnected and connected positions
                   Masterclad 27 kV, Outdoor                   •   Low voltage instrument/control compartment isolated from primary voltage areas
                Non Walk-in, Metalclad Switchgear              •   Compliance to ANSI/IEEE standards C37.20.2 and C37.55 (designed and tested to
                                                                   comply with or exceed ANSI and IEEE standards)
                                                               •   ISO 9001 Certification (Designed and manufactured in a facility that is Quality
                                                                   Systems Certified by Underwriters Laboratories, Inc.® to ISO 9001)
                                                               •   Indoor NEMA 1 enclosure
                                                               •   Outdoor NEMA 3R enclosure
                                                                   – Walk-in enclosure
                                                                   – Non walk-in enclosure
                                                                            Ratings
                                                                            • Up to 63 kA arc containment for 0.5 seconds
                                                                            • Voltage ratings from 2.4 kV to 15 kV up to 4,000 A
11
                                                                                                                                                                      11
                                                              , P-, and R-frame molded case circuit breakers are available with electronic trip units.
                                                              Additional options include PowerLogic™ and ION™ series metering, surge arresters, and
                                                              I-Line™ plug-on units with a Surgelogic™ Surge Protective Device (SPD).
                 Model III Package Unit Substation
            with HVL/cc Load Interrupter Switch (on left)
                                                 Transformer Section
                                                 Special barrel wound dry-type transformers employing resin encapsulated VPI (Vacuum
                                                 Pressure Impregnation) techniques are used to achieve the low-loss, compact design
                                                 necessary for the space-saving package substation concept. Class H, 220 °C insulation
                                                 is used throughout. Temperature rise is 150 °C as standard, although 80°C or 115 °C low
                                                 temperature premium transformers are available through 750 kVA. Aluminum windings
                                                 are standard with copper as an option. Four full capacity 2-1/2 percent taps are provided-
                                                 two above nominal voltage and two below.
                                                 Fan cooling is optional. When selected, it increases the capacity rating of the transformer
                                                 an additional 33 percent. The Model 98 digital controller is employed. This system
                                                 provides precision control through the use of three high accuracy thermocouple type
                                                 sensors—one in each phase of the windings.
                                                 The controller has a membrane front panel for displaying the temperature of all three
                                                 phases with individual readings. The hottest phase is automatically displayed. The
                                                 Model 98 digital controller features simple three-button operation with fan, alarm and trip
                                                 function settings and is Powerlogic™ compatible.
                                                                                          HVL/cc™ switch,              I-Line panelboard
                                                                                          top feed
                                                                                                                            Nameplate
                                                                                                   Removable
                                                                                                   cover                            5.45
                                                                                                                                    (138)
                                                                                                                                     85.0
                                                                                                                                    (2159)
11
                                                                                                                               80.00
                                                                                                                               (2032)
SWITCHBOARDS AND SWITCHGEAR
                                                                   Distribution Section
                                                                   I-Line™ Mounted Molded Case Circuit Breakers
                                                                   Molded case circuit breakers are group mounted in an I-Line panelboard section offering
                                                                   the inherent ease of installation for which the plug-on I-Line circuit breaker has become
                                                                   known. All circuit breakers are quick-make, quick-break, thermal magnetic, permanent
                                                                   trip type and are factory-calibrated and sealed for accurate overcurrent response and
                                                                   maximum short-circuit strength. PowerPact™ P and R circuit breakers are available with
                                                                   solid-state MicroLogic™ trip units. Current limiting high interrupting capacity FI, KI, and
                                                                   LI circuit breakers are also available. Circuit breakers may be safely back-fed for use as
                                                                   main circuit breakers. All circuit breakers are UL listed and carry integrated equipment
                                                                   rating when used exclusively with other Square D™ brand circuit breakers in intended
                                                                   assemblies.
                                                                   I-Line panel is available in 1200 A. Maximum mounting space is 108 inches.
                                                                   Tin-plated copper bus is standard.
                                                                                                                                                  Dimensions shown
                                                                                                                                                 in Inches (mm). See
                                                                                                                                                 table below for A, B,
                                                                                                                         A                       C, D, E dimensions.                8.6
                                                                                                         1.0                                                                        (218)                             8.0
                                                                                                         (25)                                                                   D    Typ.          E                  (203)              4.0
                                                                                                                                                                                                                                       (102)
                                                                                           5.0                                                            13.9
                                                                                17.5                               Medium voltage                         (353)
                                                                                (445)      (127)
                                                                                                                    conduit area
                                                                                                                     (top entry)
                                                                                                                                                                                                                                40.0
                                                                                22.0                                                                                                                                            (1016)
                                                                                                                                                          29.3
                                                                                (559)                                                                     (744)
                                                                                                                                                                                                              7.5
                                                                                                                                                7.0                                                           (191)
                                                                                                                                                (178)
                                                                              4.0
                                                                              (102)
                                                                                                                                                       1.2                                                    3.3                        4.0
                                                                                                                                                        (30)                         9.3                              9.3
                                                                   Low voltage conduit     1.6                                   C                                                                            (84)                     (102)
                                                                                           (41)                                                 1.5            0.50 (13) dia.       (236)                             (236)
                                                                   provision; 2 places;                     B                                                                                0.63 (16) dia.
                                                                                                                          Low voltage           (38)            bolt-down                     bolt-down         Low voltage
                                                                   1.125 (29) dia.                        1.5
                                                                   Contact your nearest Schneider Electric sales office for ordering assistance.
      1200 A Max. Main Lugs or
                                   SN
      1200 A Max. Main Breaker
11
                                                                Full front and or front and rear accessibility are provided. A full height cable pulling area
                                                                is standard.
SWITCHBOARDS AND SWITCHGEAR
                                           Listed Controllers
                                                                Controller voltage ratings range from 2.3–7.2 kV vacuum contactors feature a drawout
                                                                design and have ratings of 200, 400, 450, and 720 A.
                                                                Options include live line indicators, blown fuse tripping, solid state protective relays,
                                                                power factor correction capacitors, surge arresters, surge capacitors and a cable
                                                                grounding switch.