MCS-CONNECT Manual
MCS-CONNECT Manual
2023-02-22
MCS-CONNECT
5580 Enterprise Pkwy.
Fort Myers, FL 33905
Manual and Installation Guide
Office: 239-694-0089
Includes Graphics
Fax: 239-694-0031
www.mcscontrols.com
Written in Java
MCS Total
Solution
for all your See Appendix section in back of Manual for
Control quick steps for some MCS-CONNECT functions
Needs
Energy Efficient and RoHS Compliant
MCS-CONNECT REVISION 2.4
All information contained within this document is considered to be proprietary information of Micro Control Systems, Inc.
No information or data from this document shall be published, used, reproduced, transmitted, or disclosed to others out-
side your organization without the prior expressed written consent of Micro Control Systems, Inc. This document and the
information contained herein shall be treated as proprietary. Reasonable provisions shall be provided to ensure that this
information remains proprietary by your employees, agents, and other personnel that may have access to this document.
Copyright ©2023
2
MCS-CONNECT REVISION 2.4
Table of Contents
Chapter - 1. Introduction ...............................................................................................................................7
1.1. About MCS Controllers..................................................................................................................................7
Chapter - 2. PC Requirements & Product Features ...............................................................................8
Chapter - 3. Setting up Communication with Controllers .................................................................... 9
3.1. REMOTE - DIALUP - USING MCS-WIRELESS MODEM.............................................................................9
3.2. LOCAL CONNECTION USING CROSSOVER ETHERNET CABLE..........................................................10
3.3. NETWORK RS-485 CONNECTION............................................................................................................11
Chapter - 4. Installing MCS-CONNECT ................................................................................................... 12
4.1. Downloading from our Website.................................................................................................................12
4.1.1 ► VIEW ONLY VERSION................................................................................................................12
4.1.2 ► AUTH CODE VERSION...............................................................................................................12
4.2. Competing Installation.................................................................................................................................13
4.2.1 MCS-CONNECT Icon - Window’s Start Menu...................................................................................13
Chapter - 5. Setup Options for MCS-CONNECT ................................................................................... 14
5.1. Finding your Communication Ports on your PC..........................................................................................14
5.2. MCS-PC-CONNECT Communication Setup...............................................................................................14
5.3. PC Communication Speed & Wait Timers...................................................................................................15
5.4. PC Communication Modem - Remote.........................................................................................................15
5.5. Initialization Dial String................................................................................................................................16
5.5.1 Local Communication Errors.............................................................................................................16
5.6. Remote Communications............................................................................................................................17
5.7. DIALUP - ....................................................................................................................................................17
5.7.1.1. Remote Communication Errors.............................................................................................17
5.7.1.2. IP (Internet) ..........................................................................................................................18
5.7.1.3. IP LANTRONIX .....................................................................................................................18
5.8. General Setup Options................................................................................................................................19
Authorization Keypad ........................................................................................................................................19
Exception Popups ............................................................................................................................................19
Inactivity Shutdown Timer .................................................................................................................................19
Turbo Download ................................................................................................................................................19
Default Workspace Selector .............................................................................................................................19
Authorization Reset Timer ................................................................................................................................20
5.9. Tables Options.............................................................................................................................................20
5.9.1 Alarm Table........................................................................................................................................20
5.9.2 Table Font Size .................................................................................................................................20
5.9.3 Spare Row Display............................................................................................................................21
5.9.4 Basic and Advanced Display of Tables..............................................................................................21
5.10. Network Options - Make any changes, click save.......................................................................................22
5.11. Extended History Option - Make any changes, click save...........................................................................22
5.12. Create Scheduled Print (prior to 17.03).......................................................................................................23
5.13. Alarm Alerts - VERSION 17.12....................................................................................................................24
5.13.1 Enter the information for your ‘OUTGOING SERVER’......................................................................24
5.13.2 Enter Recipient Contact Info..............................................................................................................24
5.13.3 Setup which alarms you want sent....................................................................................................25
5.13.4 Enable................................................................................................................................................25
5.13.5 Save new Alarm Alert Setup.............................................................................................................25
5.13.6 Alarm Alert Types...............................................................................................................................25
5.14. Diagnostic Save Setup................................................................................................................................26
5.15. OFFLINE MENU BAR.................................................................................................................................27
Chapter - 6. System Information Screen ................................................................................................ 29
6.1. SCAN FOR CONTROLLERS......................................................................................................................29
3
MCS-CONNECT REVISION 2.4
9.2.4 Clearing of a ‘Last On/ MAX TDY’ and ‘Last Off/ MIN TDY’ cell........................................................58
9.3. Analog Output Information...........................................................................................................................59
9.4. Status Information.......................................................................................................................................60
9.4.1 Capacity Information..........................................................................................................................61
9.4.2 Compressor Information....................................................................................................................61
9.4.3 Compressor/Superheat Info...............................................................................................................62
9.4.4 EXV Info.............................................................................................................................................62
9.5. Alarm Information........................................................................................................................................63
9.6. Alarm Alerts - Active/Inactive Button............................................................................................................64
9.6.1 Suspending ‘ALARM ALERTS’ after they occur................................................................................64
9.7. Set Point Information...................................................................................................................................66
9.7.1 Set Point Value Change.....................................................................................................................67
9.7.2 Set Point Time Change......................................................................................................................67
Chapter - 10. Schedule Window for MCS Controller ............................................................................. 68
Chapter - 11. Service Windows .................................................................................................................. 69
Chapter - 12. Graph Capabilities of MCS Controllers ........................................................................... 70
12.1. Graph Setup Tabs .......................................................................................................................................71
12.1.1 Graph Setup Button...........................................................................................................................71
12.1.1.1. Interval and Y AXIS SETUP...................................................................................................71
12.1.2 Refresh Data Button .........................................................................................................................72
12.1.3 Save History Button...........................................................................................................................72
12.1.4 Print Graph........................................................................................................................................72
Chapter - 13. Diagnostic Save ‘EASY BUTTON’ ..................................................................................... 73
13.1. Diagnostic Save...........................................................................................................................................73
Chapter - 14. Graphics and MCS-Connect .............................................................................................. 74
14.1. GRAPHICS .................................................................................................................................................74
Chapter - 15. MCS-CONNECT PC Requirements & Product Features .............................................. 75
Chapter - 16. About MCS-Graphical Interface ......................................................................................... 76
Chapter - 17. Building of the Graphic Screens ....................................................................................... 78
17.1. BACKGROUND...........................................................................................................................................78
17.2. IMAGES USED............................................................................................................................................78
17.3. BUTTONS...................................................................................................................................................78
17.4. SENSOR INPUTS AND ANALOG OUTPUTS ............................................................................................78
17.5. ANIMATION GRAPHICS.............................................................................................................................78
17.6. GAUGES.....................................................................................................................................................79
Chapter - 18. Sample Graphic Interface Screen ..................................................................................... 80
Chapter - 19. MCS-GRAPHICS with MCS-CONNECT ............................................................................ 81
19.1. MCS-Connect and MCS-Graphics - Installed on your PC hard drive..........................................................81
19.2. Installing MCS-Connect...............................................................................................................................81
19.2.1 Installing MCS-Graphics Files...........................................................................................................81
19.3. Whats inside your Graphics files?...............................................................................................................82
19.3.1 Starting MCS-Connect.......................................................................................................................83
19.3.2 Setting up where MCS-Connect finds the Graphic Interface file.......................................................84
19.3.3 Selecting the Graphic tab..................................................................................................................85
Chapter - 20. Samples of Graphics ........................................................................................................... 86
Chapter - 21. Trouble Shooting problems MCS-Graphics ................................................................... 88
21.1. Troubleshooting Information........................................................................................................................89
Chapter - 22. Appendix - Transmit Config, Receive Config ................................................................. 90
Chapter - 23. Appendix - Alarms - Print & Save ..................................................................................... 91
Chapter - 24. Appendix - Graph - Quick steps to setup ....................................................................... 92
Chapter - 25. Appendix - Loading New Firmware .................................................................................. 94
5
MCS-CONNECT REVISION 2.4
6
MCS-CONNECT REVISION 2.4
Chapter - 1. Introduction
MCS-CONNECT software is part of the MCS Support System. Its purpose is to provide both local
and remote communication for MCS micro controllers either by themselves or as part of a network.
MCS-CONNECT supports the following controllers:
• MCS-MAGNUM controller
• MicroMag controller
• MCS-8 controller with firmware version # (call MCS-SUPPORT)
• MCS-6 controller (limited with firmware)
MCS-CONNECT permits the user to monitor the status of the micro controller in real time and, with
proper authorization, changes can be made to the system. In as fast as 10 seconds configuration
files can be transmitted to or received from a MCS micro controller.
Another powerful feature of MCS-CONNECT is its ability to graph event history. Since MCS control-
lers automatically perform history logging, the user can select which inputs or outputs to graph and
view the results either in real time or over a user selectable period of time.
MCS-CONNECT supports the SAVE of history data in the GRAPH function as a *.txt file. This
allows the user to bring the data up in MCS-CONNECT offline or in a spreadsheet program such as
Microsoft Excel.
Updates for MCS-CONNECT can be downloaded directly from the MCS website under
“Support”, PC Software.
The program is available as Microsoft Windows based software or as Linux based software.
This manual was created using Adobe Indesign. An approved OEM of MCS may obtain a copy of
this manual in PDF format and make copies or change sections of this manual to develop
custom documentation for a site where an MCS controller is installed. In this way, MCS
supports the documentation requirements of individual customer sites.
Additional information on the setup and using MCS-CONNECT can be found on our web site.
A Powerpoint presentation can be found at:
http://www.mcscontrols.com/Documents/MCS/Presentations/MCS%20Connect.pps
7
MCS-CONNECT REVISION 2.4
8
MCS-CONNECT REVISION 2.4
Cable
rnet
Ethe
Crossover Ethern
9
MCS-CONNECT REVISION 2.4
10
MCS-CONNECT REVISION 2.4
RS-485
MCS-USB-RS485 CABLE
USB PORT
PC with
Windows & MCS-CONNECT
NNECT
11
MCS-CONNECT REVISION 2.4
Please Note:
The software contained on our website is the latest official release of MCS-CONNECT for Windows and
Linux versions.
We post ‘BETA’ versions of the software here also. This is software that is being tested in our plant and is
made available for testing in the field before its general release to OEM’s, Contractors and Installers.
These are full install versions and does not require previous versions to have been installed. To install the
software, first download (Save) the file to your computer or flash drive.
If installing on our Touchscreens, move the installer to the touchscreen via network or flash drive. Then run
it by clicking on the downloaded file and following the instructions given.
IMPORTANT!!
Prior to making any changes to your Touchscreen, read the application notes which are posted
to our website on upgrading.
12
MCS-CONNECT REVISION 2.4
13
MCS-CONNECT REVISION 2.4
14
MCS-CONNECT REVISION 2.4
Next screen shows com ports - make changes as per your computer’s communication ports
and save these changes.
15
MCS-CONNECT REVISION 2.4
COM PORT is in use – Can occur in either the local or remote modes.
COM PORT is not available, it is busy - This can occur if another MCS-CONNECT is running on
the network or another program is using the requested COM PORT. When this condition occurs the
above message will be displayed:
16
MCS-CONNECT REVISION 2.4
5.7. DIALUP -
If you are setting up communications with a
controller using a modem, click on the button
‘DIALUP’. Setup your ‘SITE NAME’, ‘PHONE
NUMBER’, and ‘SITE COMMENTS’, click
‘SAVE SITE’.
Up to 200 phone numbers are supported.
DIALUP USING
Each phone number is accessed via the Site MODEM
Name drop down list.
The phone number can be up to 30 characters,
thus enabling phone cards to be used.
Once the ‘Connect Remotely button’ is selected the following pop-up
appears: (only if ‘Dial up’.) There is an opportunity to hang-up the
modem’s phone line by clicking the ‘Cancel’ button at anytime
during this procedure.
A “Successful Connection!” message will be displayed if the PC
modem successfully connects to the MCS controller.
17
MCS-CONNECT REVISION 2.4
5.7.1.2. IP (Internet)
You can setup a remote Network connection using the IP address of the controller you are communicating
with. Click on ‘IP (Internet)’, enter the ‘IP Address’, ‘Port Range’, (if you know the range is within a
set of numbers, click on ‘Default Port Range’ to search that range of numbers only). Add any
comments about the site, click on ‘Save Site’.
5.7.1.3. IP LANTRONIX
If you are setting up communicating with a controller that has a RS-232 port, you can use a
MCS-ETHERNET (Lantronix) .
REMOTE USING
IP ADDRESS & PORT
RANGE
REMOTE, CONVERTING
ETHERNET TO RS-232
IP ADDRESS & PORT RANGE
18
MCS-CONNECT REVISION 2.4
19
MCS-CONNECT REVISION 2.4
‘LOCKOUT ALARMS’
ONLY
5.9.2 Table Font Size
Only affects Magnum V14 and
MicroMag SW versions.
Default ‘Small’ SHOWS ‘ALL ALARMS’
SCROLL DOWN
TO SEE MORE
20
MCS-CONNECT REVISION 2.4
‘SPARE ROWS’
ARE HIDDEN
21
MCS-CONNECT REVISION 2.4
22
MCS-CONNECT REVISION 2.4
YOU DO NOT NEED TO BE CONNECTED TO THE UNIT TO PRINT THESE REPORTS- BUT YOU MUST HAVE A
NETWORK CONNECTION TO PRINT/SAVE THESE FILES TO YOUR COMPUTER
23
MCS-CONNECT REVISION 2.4
24
MCS-CONNECT REVISION 2.4
5.13.4 Enable
Next Screen - Enable the completed setup.
Click ‘OK’
1. Click in “Schedule Name” - add the name you want for this diagnostic report.
2. Click on ‘Site Information- and choose the connection type to communicate with this controller.
3. Add the ‘Local IP Address if Local Ethernet.
4. Add the Auth Code if needed.
5. Click ‘Add Current Setup to List
6. Click on ‘Load a Schedule - setting the time of day you want to generate the report.
7. Save current schedule
8. Run the Schedule if you want a report right now, otherwise the report will print at the scheduled
time.
26
MCS-CONNECT REVISION 2.4
USED ONLY ON
TOUCHSCREEN
See APP#127 for information
at www.mcscontrols.com
• Load an Offline MODBUS.cfg File - You can setup a MODBUS communication port using
MCS-CONNECT and re-save the file once changes are made. Below is a sample of the screen.
• For more detail on setting up MODBUS control for a slave device, see MCS-MODBUS manual.
27
MCS-CONNECT REVISION 2.4
28
MCS-CONNECT REVISION 2.4
Serial Network Connection: If MCS-CONNECT does not find any MCS controllers, the Scan
Finished message will be displayed in the title bar and no units will be displayed in the grid.
In the info grid MCS-CONNECT version and scanning information is displayed in the title bar.
Once in the Status Screen MCS-CONNECT version, day, date and time, plus the company name
will be displayed.
If a MCS Controller has an invalid configuration, its entire row will have a RED background.
Installer needs to Transmit a new configuration file to this controller before continuing with setup.
The installer is authorized at ‘View’ level to ‘Transmit Cfg’ and ‘Receive Cfg’.
Authorization Level
‘Grayed out’ Invalid Config
29
MCS-CONNECT REVISION 2.4
Note: The color of the Authorization button indicates what level you are authorized,
and the current level of authorization. The system default is ‘View’ only.
YOU MUST HAVE AUTHORIZATION TO MAKE CHANGES TO THE SYSTEM
HIGHER THAN VIEW. CONSULT YOUR SUPERVISOR FOR WHAT AUTHORIZATION
LEVEL IS NEEDED FOR MAKING CHANGES TO THE SYSTEM.
Red = VIEW ONLY
Light Blue = USER LEVEL
Fuscia = SERVICE
Blue = SUPERVISOR
Green = FACTORY
When you select the Authorization button the following pop up will be displayed:
Enter the 4 digit authorization code in the space provided and press the ‘enter’ button.
The Cancel button will return the user to the previous screen with no changes made to the
authorization level. Note: That the code that is entered is not visually displayed. If an invalid
authorization code is entered, no message is displayed. The Authorization color and level will
remain unchanged.
30
MCS-CONNECT REVISION 2.4
On each screen at the top there is a button bar with the following menu of buttons that will
access all of the available screens and functions.
If a button is grayed out that function is disabled, and that screen cannot be viewed. See the
button explanations below for access availability of the various screens or functions. To access
some of the above buttons you must first select the MCS controller you wish to view from the
System Information Screen. Clicking on the associated address tab will select the controller.
Exiting MCS-CONNECT
To end the communications link with the MCS controllers click on the ‘DISCONNECT’ tab. If remote con-
nection is underway, the PC’s modem will receive a hang up
command to terminate the live session. Control will be returned to the main user interface.
7.2. To Re-scan the Network for MCS Controllers
To force MCS-CONNECT to re-scan the network press the ‘Scan’ button.
32
MCS-CONNECT REVISION 2.4
33
MCS-CONNECT REVISION 2.4
Below is a pull down list of functions for the Menu Bar Tabs. The tabs allows the user to make fast
screen changes, save custom workspaces, etc. See a description for each item below.
8.1. FILE BAR - Allows user to exit MCS-CONNECT and or print BMS points lists.
34
MCS-CONNECT REVISION 2.4
8.4. RESET/CLEAR BAR - The following screen will appear when the RESET button is selected.
To clear lockouts, click on the button ‘RESET LOCKOUTS’
To clear lockouts the user must be authorized at a level greater than view.
If not the ‘NOT AUTHORIZED MESSAGE WILL BE DISPLAYED’.
NOTE:
Prior to doing a lockout reset, YOU MUST review the alarm grid to verify what caused the
lockout. When the cause is corrected you can press ‘RESET LOCKOUTS’ and a message will
appear stating that the controller has received lockout reset and an alarm notification will be
logged.
This feature allows the user to reset all lockouts.
If you have a circuit or the entire package is in lockout, clicking the Reset Lockout button
through MCS-CONNECT will clear all lockouts. If the lockout condition still has not been cor-
rected, the system will lockout instantly and not run.
YOU ARE LIMITED TO 6 LOCKOUT RESETS PER DAY.
35
MCS-CONNECT REVISION 2.4
36
MCS-CONNECT REVISION 2.4
After creating and saving a workspace, continue to view other options under the
‘Workspace Menu Bar’
8.5.2 Switch Workspace
User can select different ‘SAVED WORKSPACES’
8.5.3 Save Current Workspace
Choose the items you wish to view and save the current workspace.
NOTE: At the ‘GENERAL SETUP SCREEN’ in MCS-CONNECT you can choose a workspace as your
default workspace so each time you connect to your controller, your custom workspace
will appear. You can change back to the default workspace or create a new workspace.
37
MCS-CONNECT REVISION 2.4
Screen 4
8.8. BUTTON BAR - Click to hide/show Button Bar, short cuts to ‘Scan’, ‘Graph’,‘Transmit’,
‘Receive Ctg’, ‘Authorization Level’, ‘Print’ and ‘Graphics’.
39
MCS-CONNECT REVISION 2.4
8.10. TIME -
You must be authorized to make changes to the time feature.
40
MCS-CONNECT REVISION 2.4
The User can select up to six (6) points to graph when ‘Analog Data’ is selected.
A drop down menu next to the point you are graphing will show all the available
sensor inputs and outputs configured to the controller you are connected to.
NOTE: Sensor inputs have digital and analog points that can be selected .
Refer to your controller to graph the correct sensor information.
41
MCS-CONNECT REVISION 2.4
Y-Max
Y-Min
42
MCS-CONNECT REVISION 2.4
43
MCS-CONNECT REVISION 2.4
When prompted, select your graph and click ok to save this SETUP to your computer.
NOTE:
REMEMBER YOU ARE SAVING JUST
THE SETUP FOR THE GRAPH
EACH TIME YOU OPEN THIS
GRAPH IT WILL BE A
‘LIVE VIEW OF YOUR CONTROLLER’
44
MCS-CONNECT REVISION 2.4
1. Click on the Live Graph Menu Tab and use your arrow keys to highlight ‘REMOVE A SAVED
GRAPH GROUP’.
2. Click on the ‘GROUP’ file you want to remove.
3. You will be prompted ‘Are you sure we want to delete this Live Graph Setup?
45
MCS-CONNECT REVISION 2.4
4. Click ‘OK’, the setup file for the group highlighted will be
permanently deleted.
2. Click on a ‘LIVE GRAPH’ file that was saved and place the ‘Live Graph’ setup file into your
saved workspace. The next time you open the saved workspace, the ‘Live Graph’ will be placed
in the exact location you specify in your workspace.
3. You can experiment with different workspace setups to allow room for two ‘Live Graph setups’.
46
Providing HVAC/R Control Solutions Worldwide
MCS-CONNECT REVISION 2.4
5580 Enterprise Pkwy., Fort Myers, FL 33905
Office: 239-694-0089 Fax: 239-694-0031
www.mcscontrols.com
8.15. UNITS
For Immediate Release Rev. 2022-07-29
Units - Temperature
Change the Fahrenheit,
TEMPERATURE Celsius
and or PRESSURE Un Kelvin or’
its Use config units
TEMPORARILY
Units - Pressure
PSI,
Bar,
Kilopascals or’
Use config units
Setup
Defaults
for viewing Units
and save
47
MCS-CONNECT REVISION 2.4
‘UNITS’ WILL DISPLAY RED when you are connected to MCS-MAGNUM controller showing that the original
configuration file is being overridden, TEMPORARILY or by Default Display Units set in General Options.
The following Firmware and Software tools are needed for these new features:
▪ MCS-CONFIG: VER 18.04.06 or higher
▪ MCS-CONNECT: VER 18.39.16 or higher
▪ MCS-MAGNUM FIRMWARE: XXXX V17.90 or higher (XXXX=HVAC, CENT, etc)
New Feature added in new Firmware (XXXX V17.90) and MCS-CONFIG V18.04.06 and higher:
• Added new option, DELTA_TMP in drop-down menu of setpoints tab and SI screens
Contact your OEM or MCS for existing MCS-MAGNUMS in the field that
will require a configuration update to use the new software and firmware.
For additional information on this new product or if you need information on any of our products, Email: sales@mcscontrols.com
48
MCS-CONNECT REVISION 2.4
Once you scan for all controllers in MCS-CONNECT you can click on the ‘DIAGNOSTIC SAVE’ button at the
top. The Diagnostic Save Popup will appear.
If you have multiple controllers connected to the network, you can choose a ‘Diagnostic Save’ for each controller,
again you have the option of what information you want saved.
A second popup will appear showing the file has been saved to
your hard drive.
You have the option to email the zip saved file to:
support@MCScontrols.com or to a custom email address (In-
ternet connection required).
Below shows file that was emailed as per the setup in the
‘Diagnostic Save’.
49
MCS-CONNECT REVISION 2.4
GRAPHS - LEFT TO RIGHT READING - Graphs now move from left to right as shown in
screen shot below: This makes it easier when viewing the graph to see changes aligned with
the legend on the left.
‘FIXED VAL’ - When adding a new Live Graph you now can set ‘Fixed Val’ for setting up
you zones for plotting a point. Each new Live Graph can contain 2 fixed values on the graph.
These fixed values or lines help in seeing the movement of the plotted point (see above
screen shot).
50
MCS-CONNECT REVISION 2.4
STATUS SCREEN
SHOWS
GRIDS IN
BASIC MODE
CLICK ON ADVANCED
TO SEE
ADDITIONAL
INFORMATION
STATUS SCREEN
ADVANCED MODE
51
MCS-CONNECT REVISION 2.4
Relay Outputs - This is the name of the Relay Output. Click on this cell to toggle highlight function
Double clicking on Controller’s RO brings up FLA popup. (for compressor relay outputs)
Value – This is the value of the Relay Output. A value of On or Off shows the value as a normal
digital RO. This field can be changed, see Relay Output Manual Status Change.
52
MCS-CONNECT REVISION 2.4
Manual Status – This is the status of the device, i.e. AUTO, MANON, MANOFF, LOCKOFF,
LOCKOFF AND MANCMP%. If the status is other than AUTO, the background for that cell will be
RED. This is to highlight a condition that is not normal operations.
53
MCS-CONNECT REVISION 2.4
54
MCS-CONNECT REVISION 2.4
55
MCS-CONNECT REVISION 2.4
SI # – This is the number of the Sensor Input. M-1 shows the data for SI #1 on the Master board
and a 1-1 would show data for SI #1 on I/O board #1 and so on.
Sensor Input Name – This is the descriptive name of the Sensor Input.
Value – This is the value of the Sensor Input. If the sensor is an analog, the value plus a character
will be displayed. If the sensor is a digital, the status will be displayed as per
this popup:
Manual Status – Auto or Manual, if manual and an analog, the value displayed
will be the manual value. If digital then it can be ‘MANON’ on or ‘MANOFF’.
This field can be changed, see Sensor Input Manual Status Change. If the sta-
tus is something other than AUTO, the background for that cell will be RED. This
is to highlight a condition that is not normal operations.
Filter/Offset – Is the amount of adjustment that has been made to the actual value of an analog
input. This field can be changed, see Sensor Input Offset Change.
Sensor Type – Displays the type of sensor. This field can be changed, see Sensor Input Type
Change.
Last On / Maximum Today –
IF DIGITAL INPUT – Time that it was last on
IF ANALOG INPUT – Maximum value today
56
MCS-CONNECT REVISION 2.4
Cycles Today - Digital only, total number of time the sensor cycled today
Total Cycles - - Digital only, total number of times the sensor cycled
Changing the status of an analog input to manual will cause the following screen to
appear. Enter the desired sensor and press ENTER. or click ‘OK’
57
MCS-CONNECT REVISION 2.4
If properly authorized
you may change the
type of sensor you
have on the input
sensor.
9.2.4 Clearing of a ‘Last On/ MAX TDY’ and ‘Last Off/ MIN TDY’ cell
Double click the column and row you wish to clear.
58
MCS-CONNECT REVISION 2.4
ANALOG OUTPUT
LINEAR CONTROL
SETTING SCREEN
make changes, apply and
click ok.
59
MCS-CONNECT REVISION 2.4
To assist in identifying an item, the background color can be toggled between WHITE, normal, and GREEN
or BLUE (color alternated by line), highlighted, by clicking on the items Name cell. The highlighting will remain
active until clicked off or MCS-CONNECT is exited. Individual MCS controllers’s can have different items
highlighted and this will not be lost when moving between units.
AO # – This is the number of the Analog Output. M-1 shows the data for the 1st AO on the Master board.
The MCS-8 has 1 AO on the master. The Magnum has 4 AO’s on the master. A 1-1 would show data
for AO #1 on I/O board #1 and so on.
Analog Output Name – This is the name of the Analog Output. Click on this cell to toggle highlight func-
tion.
Manual Status - This is the status of the device, i.e. auto, manual. If the device is in ‘Manual’. then the
information in the value field is for the manual setting. If the device is not in AUTO status, the back-
ground for this cell will be RED.
Maximum Today – This is the maximum value that has occurred in the value field today.
Minimum Today - This is the minimum value that has occurred in the value field today.
Average Today - This is the average value that has occurred in the value field today.
Maximum Yesterday - This is the maximum value that occurred in the value field yesterday.
Minimum Yesterday - This is the minimum value that occurred in the value yesterday.
Average Yesterday - This is the average value that occurred in the value field yesterday.
60
MCS-CONNECT REVISION 2.4
Capacity Control State – State of the chiller. (Startup, disabled, lockout, lost I/O, off, holding, step-,
and step+) See the MCS controller manual for your application for descriptions of each state.
Step Delay – Sensitivity of control temperature. The set point (step sensitivity) value assigned to
limit or dampen the rate of change between compressor steps. If sensitivity = 1, then 1 degree
of difference from target accumulators 1 second worth of delay. If sensitivity = 2, then 1 degree of
difference from target accumulators .5 seconds worth of delay.
Control On – Sensor input that is being used to determine the needed capacity of the system, back-
ground color based on if it is above or below the Control On value.
61
MCS-CONNECT REVISION 2.4
Suction Temp – Compressor number and current valve of the Suction Temperature, if available.
Saturated Suction – Calculated Suction Saturated Temperature, if available. The Suction
Pressure is converted into temperature based upon the type of refrigerant (R22, R134a, R407c, and
R410a are supported.)
Suction Superheat – Calculated Suction SUPERHEAT, only available if both the Suction
Temperature and the Suction Pressure are used. The calculation is Suction Temperature minus the
Suction Saturated Temperature.
Disc Temp – Discharge Temperature, if available
Saturated Discharge – Calculated Discharge Saturated Temperature, if available. The
Discharge pressure is converted into temperature based upon the type of refrigerant (R22, R134a,
R407c, and R410a are supported.)
Disc Superheat – Calculated Discharge SUPERHEAT, only available if both the Discharge
Temperature and the Discharge Pressure are used. The calculation is Discharge Temperature mi-
nus the Discharge Saturated Temperature.
Subcooling – the amount of heat removed below the refrigerants condensing temperature at
a particular pressure measured in deg. F
Liquid Temp – The temperature of the refrigerant.
Saturated Liquid Temp. – Temperature and pressure of refrigerant.
Evap EXV State – Compressor number and current valve of the EXV.
Time – The time the valve has been in this state.
Valve % – This is the current valve % opening. While 0 to 100 % is the range, there are set points
that limit the range to avoid unnecessary movement outside the required operating range.
Control on Suction Superheat – The current superheat for this circuit.
SuperHeat ROC – The rate of change of superheat based on the time defined in the superheat
target setpoint.
ADJ Delay – When this value reaches zero the controller will adjust the EXV based on the
current status.
EXV Target (Adjusted) – The adjusted value of the EXV based on setpoints.
62
MCS-CONNECT REVISION 2.4
Alarm Additional
Info Pop up screen
There are three types of alarms that are generated by the MCS controller control logic (See your
MCS controller manual for your application for more details regarding types of alarms generated):
Information only alarms
System generated alarms
Alarms as a result of individual action
Alarms generated by the control algorithm
MCS controller system alarms
Configuration problem alarms
MCS local network problem alarms
Key sensor problem alarms
Emergency stop alarm
Chiller set point safety alarms
Sensor inputs used in conjunction with MCS controller set point safeties
Set point safeties
Alarm Name – This is the name of the alarm generated by the MCS controller.
63
MCS-CONNECT REVISION 2.4
Clicking on the ‘ALARM ALERTS ACTIVE BUTTON’ will open the following screen:
You can choose to ‘SUSPEND’ the Alarm Alerts here on the status screen or Reactivate Alarm
Alerts if they were previously suspended without going back to the setup screen at the startup.
Clicking on ‘SUSPEND ALARM ALERTS’ brings up a sub menu screen allowing you to choose the
amount of time you wish to suspend the Alarm Alerts. The time period can be from 1 hour to 8 hours.
Once you ‘SUSPEND’ the ‘ALARM ALERTS’ and set the time you want them suspended for, the
button at the top will read ‘ALARM ALERTS-SUSPENDED’ and turn ‘RED’ as shown below.
After the time has expired, the ‘ALARM ALERTS’ button will show ‘ACTIVE’ and turn ‘GREEN’.
The Alarm Alerts are now active again and will save a Diagnostic Save once an alarm occurs.
64
MCS-CONNECT REVISION 2.4
1. COMPLETE THE SAVE - MCS-CONNECT will continue with the Diagnostic Save.
2. CANCEL - the Diagnostic Save will be canceled.
3. CANCEL AND SUSPEND - the Diagnostic Save will be canceled and can be suspended for a set
time (one to 8 hours).
65
MCS-CONNECT REVISION 2.4
SEC Ignore (Sec. to Ignore Safety)- Time delay that the safety will be ignored upon compressor
startup.
Window EXT (Window to Extend Safety Time) - The amount of time after compressor startup (or
“Sec to Ignore Safety” if used) in which the “Safety Time Extension” field is added to the ”Time
(sec)” field.
Safety EXT (Safety Time Extension)- The amount of time added to the “Time (sec)” field during the
“Window to Extend Safety Time”.
66
MCS-CONNECT REVISION 2.4
To change the value of a set point you must be authorized at a level that will accept a change to
the set point in question. If your authorization is not sufficient the system does not respond to the
request
If the authorization is sufficient then the following screen will appear:
Type in the desired value within the range allowed.Click ‘Send Change” when complete.
The request will be acknowledged in the information frame screen.
9.7.2 Set Point Time Change
To change the time of a set point click on the appropriate set point cell and the following screen will
appear. Type in the values wanted then press OK. The value will change in the setpoint screen.
67
MCS-CONNECT REVISION 2.4
To change a schedule, click on any cell tin the row to be changed and enter the new values. When
all changes have been made, click on the OK button to update the system.
The CANCEL button will keep the schedules as their original values.
Note different types of control software may product a different schedule format.
68
MCS-CONNECT REVISION 2.4
69
MCS-CONNECT REVISION 2.4
The MCS controller captures history of the status for all RO, AO and SI points based on the setup of your
configuration file. Through MCS-Config, the user is also able to setup additional “USER LOGIC’ statements to
capture additional internal information for plotting.
71
MCS-CONNECT REVISION 2.4
This Graph setup screen displays in tabbed pane at top of the screen: the RELAY OUTPUTS(RO),
ANALOG OUTPUT(AO), SENSOR INPUT(SI’s) or DIGITAL INPUT(DI’s) of all the points in this
configuration file.
To add a point to the list that will be graphed, move the cursor to the check box next to the point you
wish to graph, and click. The name will be added to the Points to Graph list in the right screen of the
popup and a check mark will appear in the box. To remove an item from the list, click on the box to
remove the check mark. The item will be removed from the Points to Graph list.
When you are finished adding the points, you can click ‘Save Selected’, which will save all points for
the controller you are viewing. If you view another MCS controller you can setup the graph points
so each time you view the MCS controller your points for the graph will be loaded for that MCS
controller.
Clicking ‘Graph Selected’ will plot the current selections in the graph.
The Y-Axis section contains the maximum and minimum setting for the Y-axis. The axis is divided
proportionally between these two points divided by the # of lines specified.
The Interval tab enables the interval to be changed. The time is recorded in seconds. Click on the
appropriate radio buttons in minutes or hours. The Seconds History Interval Box automatically
updates in seconds. (You may double click on the seconds box and put in a value as small as 2
seconds).
Save Selected- Clicking on this button will enable the current settings to be saved. If the settings
are saved, they will be active when the system is again accessed.
Cancel - Clicking on this button will return control to the GRAPH screen. None of the changes that
were made will be reflected on this screen. The original settings will be used.
72
MCS-CONNECT REVISION 2.4
73
MCS-Graphic and MCS-Connect REVISION 2.5
MCS-Connect can also communicate with other control boards sold by MCS.
MicroMag Controller
MCS-MAGNUM
15.4 TOUCHSCREEN
MCS-MAGNUM NEMA4-15.4
CONTROL CABINET
PC LAPTOP
RUNNING MCS-CONNECT
with the option to communicate using an MCS-485-USB
MCS-REMOTE 15.4 cable direct to your controller or you can communicate
CONTROL CABINET remotely using a MCS-WIRELESS-MODEM cabled to
your controller using the internet.
74
MCS-Graphic and MCS-Connect REVISION 2.5
75
MCS-Graphic and MCS-Connect REVISION 2.5
DEPENDING ON
AUTHORIZATION LEVEL,
THE USER IS ABLE TO HIDE, SHOW,
DISCONNECT, PRINT OR
SEE STATUS OF UNIT
76
MCS-Graphic and MCS-Connect REVISION 2.5
Remote monitoring using MCS-Connect and the ‘Graphical user interface’ will increase the value of
your installation. It enables the user to change system settings without the need to call the customer
or send out a technician. It enables the user to troubleshoot failures and have the appropriate
repair parts on site as a technician arrives.
MCS-Connect and the ‘Graphic Interface’ can reduce a lot of service trips which mean savings in
time and money, but more importantly you have better control of your compressors and can monitor
all parameters in real time through MCS-CONNECT.
Each ‘Graphic Package’ screen is different depending on how you wanted the setup to be and what
compressor(s) you are viewing.
77
MCS-Graphic and MCS-Connect REVISION 2.5
17.1. BACKGROUND
The background we use is kept to a simple design which
does not interfere with the buttons, images, animation and
widgets used to show the status of your compressor(s).
17.3. BUTTONS
Buttons are used to show a feature as ‘Stop, Start, and so forth. Examples of buttons are shown
below.
78
MCS-Graphic and MCS-Connect REVISION 2.5
17.6. GAUGES
A gauge used in our graphic package is “a device for measuring a physical quantity”, [1] pressure of
flow”, [2] or “a device that displays the measurement of a monitored system by the use of a needle
or pointer that moves along a calibrated scale”.
There are two types of gauges soon to be available in the Graphic Package:
Radial gauges
Linear gauges
79
MCS-Graphic and MCS-Connect REVISION 2.5
SENSOR INPUTS
ANIMATION GRAPHIC
BUTTONS USED
RELAY OUTPUTS TO MOVE BETWEEN
DIFFERENT SCREEN
VIEWS
BACKGROUND
On this grapic package, there are three different screens available, ‘System Overview’,
‘Comp Overview’, ‘Evap & Cond Overview’.
The screen above shows the ‘Compressor Overview’. Clicking on the left button would show
‘System overview’, clicking on the right button would display the ‘Evap and Cond overview’.
80
MCS-Graphic and MCS-Connect REVISION 2.5
1. Navigate to your ‘Desktop’ click on the window icon to view your program files loaded on your
hard drive.
2. The ‘Graphics folder’ should be located in the ‘root directory” of your computer under ‘MCS’
where the installer wanted to place the files. If you overrode this location, you will need to
change where you are going to place the new graphic package.
3. Open the ‘MCS’ folder and place the supplied ‘Graphic Files’ into the folder labeled
‘Graphics’.
4. If the file was supplied as a ‘zip’ file, unzip the file and than place the contents
into the ‘Graphics folder.
81
MCS-Graphic and MCS-Connect REVISION 2.5
5. Below is a sample of what Graphic Files you will have depending on the configuration of your
system.
CONTENTS OF
GRAPHIC FILE
1. CFG - this sub directory contains your configuration files which tells your compressor what to
do. These files are used by your installer.
2. images - sub directory of the images
used for your ‘graphics’.
3. XML - the next five files ending with .xml
are the actual ‘build’ files for presenting
your graphics while in MCS-Connect for
this compressor.
4. SystemOverview.xml - is the main
screen used by ‘Graphics’ to display the
status of your compressor. The remaining
.xml files are ‘graphic builds’ of additional screens which show diffenence information of
the compressor, its sensors, relays and settings.
5. The ‘SystemOverview.xml’ is the file you will use to start the ‘graphics’ for your compressor.
WE’LL SHOW YOU WHERE THAT FILE IS STORED IN MCS-CONNECT IN THE
NEXT PAGES OF THIS MANUAL.
82
MCS-Graphic and MCS-Connect REVISION 2.5
6. Navigate to the ‘Desktop’, locate the ‘Shortcut’ that was placed on your desktop when you
loaded MCS-Connect.
Screen 3.1
83
MCS-Graphic and MCS-Connect REVISION 2.5
Screen 3.2
Add the
Graphic File
name here
/CHL/SystemOverview.xml
84
MCS-Graphic and MCS-Connect REVISION 2.5
Figure 13.6
Now you can select the graphics button (Fig. 13.6) and wait for all the information to be displayed.
85
MCS-Graphic and MCS-Connect REVISION 2.5
86
MCS-Graphic and MCS-Connect REVISION 2.5
87
MCS-Graphic and MCS-Connect REVISION 2.5
If you are connected to multiple compressors - make sure the correct ‘Graphic
Multiple Compressors
file” is linked to the correct compressor.
88
REVISION 2.5
Check the Com Port setting in your PC and in the setup in MCS-CONNECT if you are trying to
Can’t communicate with controller
connect ‘LOCALLY’
Connecting with MCS-Connect to a MCS- Go to www.mcscontrols.com / Support / Literature / APP NOTES / APP079 for
MAGNUM over Ethernet instructions.
Failed to Launch Graphics Check to make sure File name and path is correct in Service/Graphics Link
MCS-CONNECT support can help you with any problems you are having connecting to a contoller,
setting and changing sensors, etc.
89
REVISION 2.5
90
REVISION 2.5
91
REVISION 2.5
YOU MUST BE LOCALLY CONNECTED TO THE CONTROLLER directly at the job site using a
MCS-USB-RS485 cable.
NOTE: Important: VERSION XX FIRMWARE MUST USE VERSION XX MCS-CONFIG FILES. (EX: HVAC
17.25 must be using a MCS-CONFIG version 17).
MIXED FIRMWARE AND CONFIG FILE WILL NOT WORK. MAKE SURE YOU HAVE THE LATEST FILES
PRIOR TO LOADING NEW FIRMWARE TO YOUR CONTROLLER.
7. Connect the MCS-USB-485 cable to your PC and to the 485 port on the MAGNUM-N.
8. Open MCS-CONNECT, click on ‘FIRMWARE’ and upload the new MAGSOFT to your controller.
Upload will take about 10-15 minutes.
93
REVISION 2.5
Standard Method
1. USING THE MCS-USB-485, connect the USB end to your PC port and connect the RS485 port to the MAGNUM-N
port.
2. Open MCS-Connect
3. Select Local Serial as method of connection (you must already be connected to the Magnum using an
MCS-USB-485 cable to the Magnum). This will bring up the Magnum
scanning screen.
4. Select the Magnum controller you would like to connect to and click
the respective tab. Wait for the tables to load.
5. Click the ‘VIEW’ button and enter the correct authorization code (must
be Service level or higher). This will enable the button.
6. Click the ‘LOAD FIRMWARE’ button and navigate to the software
you wish to insert in the menu that pops up. (will be a .hex file)
7. Once you have selected the firmware, click on ‘LOAD’ and wait until
firmware has finished transmitting.
94
REVISION 2.5
Backdoor Method
There may be certain situations where the standard method for transmitting software will not work (for example,
software corruption through incomplete transfer, power failure, etc.). The magnum may be in constant reset
and might not show up on the scanning screen of MCS-Connect. In such instances the following backdoor
method must be used to transmit software.
1. Open MCS-Connect
2. Select Local Serial as method of connection (make sure you are NOT connected to the Magnum yet,
keep the serial cable unplugged for this step so that the ‘LOAD FIRMWARE’ does not become
disabled). This will bring up the Magnum scanning screen. Click the button and navigate to the MAG-
SOFT version you wish to insert in the menu that pops up (will be a .hex file).
3. Reconnect the MCS-USB-485 cable to the MAGNUM.
4. Before actually transmitting software however, locate the RESET button on the MCS-Magnum board.
You will need to start transmitting the software within seconds of pressing the RESET button.
5. Press the RESET button and then immediately begin transmitting the software.
95
REVISION 2.5
Kit Includes
Kit Includes:
1. Compact Flash 2 Gigabyte Memory Card as shown
2. USB CABLE for connection from Compact Card
Reader to PC Computer.
3. Compact Flash Card Reader
USB Cable
Part # MCS-COMPACT for connection from
Compact Card Reader to
computer
96
REVISION 2.5
The MCS-Magnum can save onto a MCS-COMPACT, a 2G compact flash card, the same history
file as in the graphing screen “Save History” option.
The only difference is MCS-Magnum names the history file and automatically saves the history file
when the MCS-Magnum internal history data has filled up. You must remove the compact flash card
from the MCS-Magnum and using the USB top Compact flash adapter, read the compact flash card
on your laptop like you would read a USB memory stick.
Once you insert the USB Compact adapter (with Compact Flash card plugs into it) into your laptop
you will see all the history files saved on it. The MCS-Magnum names the file with ‘HISTORY-INFO’
plus the date and number. The Number is sequentially numbered starting from 1 every midnight.
Please see below an example of history files saved on compact file card. In this example there are
two files, both saved on June 6, 2015, one file was the 48 file saved that day and the other being
the 52 file saved that day.
97
REVISION 2.5
Now to view a graphing file that has been saved on the compact flash card or one you manually
saved in the graphing screen open MCS-Connect and click on the “Offline” text at the top of the
screen. Then in the popup menu click on ‘Load an Offline Graph File’.
Then you will get a popup file selection window(see below photo) . Move to the folder where the
history file has been saved and select the history file you want to view.
Then after you select the file you will see a screen like below.
Click on the offline graph tab and you will see the screen below:
98
REVISION 2.5
Now it will work just like the normal “Graph” button/screen in MCS-Connect, where you can select
which points you want to graph.
Prior to MCS-CONNECT 18.27.10 when plotting a point(s) in a graph MCS-CONFIG was
pre-programmed with user logic ‘fixed values’ so a technician could set a zone for the point plotted
when reading a pulled back history file.
With the release of the above version, you are now able to add the fixed points after receiving the
pulled back history file along with the points you are plotting.
Having user logic statements added to your config is no longer necessary.
You can set 4 different ‘fixed Vals’ for setting zones for different graphed points.
99
REVISION 2.5
3
POPUP FOR SETTING
MINUTES OF INACTIVITY FOR
STATUS UPDATES.
3. Set the number of minutes of inactivity for status updates to stop from the chiller,
which enables the ‘EXTENDED HISTORY SAVE’ to begin saving.
(The unit will wait the time specified, then ‘EXTENDED HISTORY pullback will begin.
100
REVISION 2.5
4. Choose the location for MCS-CONNECT to save the file to. The file location when
connected on a PC or laptop can be your ‘C’ drive and sub directory MCS where most
of the MCS-CONNECT files are stored.
IMPORTANT:
DO NOT CLICK ON THE COMPUTER OR TOUCHSCREEN AT THIS TIME
IT WILL DISABLE EXTENDED HISTORY PULLBACK.
101
REVISION 2.5
When you choose the points list you want to print, the next screen will open, choose where you will save the
points list. MCS-CONNECT will print a pdf file in this location.
102
MCS-CONNECT REVISION 2.3
REVISION 2.5
MCS-MAGNUM (BACnet IP & Modbus) MCS-BMS-GATEWAY (BACnet MSTP, JOHNSON N2, LONTALK
Points List Points List
NAME: OFFICE AHU COMPANY NAME: MicroCtrlSystem UNIT MODEL #: Cool/Heat/OA UNIT SERIAL #: NAME: OFFICE AHU COMPANY NAME: MicroCtrlSystem UNIT MODEL #: Cool/Heat/OA UNIT SERIAL #:
POINT MAPPING INFO BUILT IN MCS-MAGNUM POINT MAPPING INFO BUILT IN MCS-MAGNUM
BMS Points SI Grid Information BMS Points SI Grid Information
MCS MAGNUM BACNET ID MODBUS IP & RTU MCS MAGNUM BACNET ID MODBUS IP & RTU
PT # NAME ID NAME REGISTER # ASSUMED DEC PT # NAME ID NAME REGISTER # ASSUMED DEC
M-1 SUPPLY TMP AI:1 SUPPLY TMP 30001 1 M-1 SUPPLY TMP AI:1 SUPPLY TMP 30001 1
M-2 RETURN TMP AI:2 RETURN TMP 30002 1 M-2 RETURN TMP AI:2 RETURN TMP 30002 1
M-3 ReturnHumd AI:3 ReturnHumd 30003 1 M-3 ReturnHumd AI:3 ReturnHumd 30003 1
M-4 RETURN CO2 AI:4 RETURN CO2 30004 0 M-4 RETURN CO2 AI:4 RETURN CO2 30004 0
M-5 COIL TMP AI:5 COIL TMP 30005 1 M-5 COIL TMP AI:5 COIL TMP 30005 1
M-6 OA TMP AI:6 OA TMP 30006 1 M-6 OA TMP AI:6 OA TMP 30006 1
M-7 OA HUMD AI:7 OA HUMD 30007 1 M-7 OA HUMD AI:7 OA HUMD 30007 1
M-8 DuctStatic AI:8 DuctStatic 30008 2 M-8 DuctStatic AI:8 DuctStatic 30008 2
M-9 MFG CO2 AI:9 MFG CO2 30009 0 M-9 MFG CO2 AI:9 MFG CO2 30009 0
M10 TRANE SPLY AI:10 TRANE SPLY 30010 1 M10 TRANE SPLY AI:10 TRANE SPLY 30010 1
M11 SPAREM-11 AI:11 SPAREM-11 30011 0 M11 SPAREM-11 AI:11 SPAREM-11 30011 0
M12 DmprClosed AI:12 DmprClosed 30012 0 M12 DmprClosed AI:12 DmprClosed 30012 0
M13 SplyFanFlt AI:13 SplyFanFlt 30013 0 M13 SplyFanFlt AI:13 SplyFanFlt 30013 0
M14 SPAREM-14 AI:14 SPAREM-14 30014 0 M14 SPAREM-14 AI:14 SPAREM-14 30014 0
M15 SMOKE ALM AI:15 SMOKE ALM 30015 0 M15 SMOKE ALM AI:15 SMOKE ALM 30015 0
M16 RUN/STOP AI:16 RUN/STOP 30016 0 M16 RUN/STOP AI:16 RUN/STOP 30016 0
1-1 IonizerAlm AI:17 IonizerAlm 30017 0 1-1 IonizerAlm AI:17 IonizerAlm 30017 0
1-2 OA ENTHLPY AI:18 OA ENTHLPY 30018 1 1-2 OA ENTHLPY AI:18 OA ENTHLPY 30018 1
1-3 RUN ECNMZR AI:19 RUN ECNMZR 30019 0 1-3 RUN ECNMZR AI:19 RUN ECNMZR 30019 0
1-4 SPARE1-4 AI:20 SPARE1-4 30020 0 1-4 SPARE1-4 AI:20 SPARE1-4 30020 0
1-5 WtdOADmpr AI:21 WtdOADmpr 30021 1 1-5 WtdOADmpr AI:21 WtdOADmpr 30021 1
1-6 CoilContrl AI:22 CoilContrl 30022 1 1-6 CoilContrl AI:22 CoilContrl 30022 1
1-7 RtnDmpCtrl AI:23 RtnDmpCtrl 30023 1 1-7 RtnDmpCtrl AI:23 RtnDmpCtrl 30023 1
1-8 EntWtrTmp AI:24 EntWtrTmp 30024 1 1-8 EntWtrTmp AI:24 EntWtrTmp 30024 1
1-9 LevWtrTmp AI:25 LevWtrTmp 30025 1 1-9 LevWtrTmp AI:25 LevWtrTmp 30025 1
1-10 SPARE1-10 AI:26 SPARE1-10 30026 0 1-10 SPARE1-10 AI:26 SPARE1-10 30026 0
1-11 SPARE1-11 AI:27 SPARE1-11 30027 0 1-11 SPARE1-11 AI:27 SPARE1-11 30027 0
1-12 DmprMin% AI:28 DmprMin% 30028 1 1-12 DmprMin% AI:28 DmprMin% 30028 1
1-13 DmprCtrl% AI:29 DmprCtrl% 30029 1 1-13 DmprCtrl% AI:29 DmprCtrl% 30029 1
1-14 AllwEcnmzr AI:30 AllwEcnmzr 30030 0 1-14 AllwEcnmzr AI:30 AllwEcnmzr 30030 0
1-15 COOLING AI:31 COOLING 30031 0 1-15 COOLING AI:31 COOLING 30031 0
1-16 HEATING AI:32 HEATING 30032 0 1-16 HEATING AI:32 HEATING 30032 0
2-1 OCCUPIED AI:33 OCCUPIED 30033 0 2-1 OCCUPIED AI:33 OCCUPIED 30033 0
2-2 TMP RESET AI:34 TMP RESET 30034 1 2-2 TMP RESET AI:34 TMP RESET 30034 1
104
103
REVISION 2.5
Revision Page
Date Author Description of Changes
08-22-07 J. Walterick Created manual.
09-06-07 J. Walterick Alignment changes (Rev-1.1)
03-02-15 DEW Convert to Indesign, edits
03-10-15 DEW Edits
03-25-15 DEW Edits
04-01-15 DEW Edits - comments from Ray
04-07-15 DEW Edits
04-17/20-15 DEW Edits - comments from Ray
06-02-15 DEW Edits
06-05-15 DEW Edits
06-25-15 DEW Edits
07-17-15-20 DEW Edits
07-30-15 DEW Added Diagnostic Save to section 9
09-29-15 DEW Changed some network drawing, Graphic pages
12-09-15 DEW Updated Screen shots added Diagnostic Save
2-11-16 DEW Added graphic section at rear
3-04-16 DEW Add new Alarm Alert setup Ver 17.12
3-7-16 DEW Add lookup table, P/T Converter
6-13-16 DEW Add New Live Graph Section
10-10/14-16 DEW Edits from latest version
11-7-16 DEW Updates and edits
06-20-17 DEW Add BMS file print
06-22-17 DEW Add info for editing Autostart file on touchscreen and MODBUS config
10-24-18 DEW Add Diagnostic Save Pop up info
04-08-19 DEW Add Fixed Values to Live Graph and Graph Pullback using Fixed Values
11-19-2021 DEW Add Alarm Alerts setup for Gmail
11-29-2021 DEW Add Hide/Show info
08-02-2022 DEW Add ‘UNITS’ for F and C
02-21-2023 DEW Update Alarm section - remove GMail reference
104
Providing HVAC/R Control Solutions Worldwide