CATEGORY-2
LII/11041/PLL/465/5275
                                                                Dated: 15th Nov 2013
                                                                Lahmeyer International India (Pvt.) Ltd.
                                    Technical Data of ABB motor
Customer                                          : Haldia Power Project
Application                                       :
Frame Size                                       : HX+280SMC4
Method of Starting                               : DOL
Type of coupling                                 : Direct
Output                                            : 90 KW
Quantity                                         :3
Duty type                                        : S1
Supply                                           : 415 V ±10% 50 Hz ±5%
Full load Speed                                  : 1475 r/min
Full load Current                                 : 157 A
Full load current at
75% load                                         : 122
50% load                                         : 92
Locked rotor current (Is/In)                      : 6.0
Full load torque                                 : 583 Nm
Locked rotor torque (Ts/Tn)                      : 240%
Breakdown torque (Tmax/Tn)                       : 270%
Efficiency -full load                            : 94%
Efficiency -3/4 load                              : 94%
Efficiency -1/2 load                              : 93%
Power factor - Full load                         : 0.85
Power factor - 1/2 load                           : 0.82
Power factor -1/2 load                            : 0.73
Insulation Class                                  :F
Ambient temperature                               : 50 Deg C
Temperature rise                                  : 70 Deg C
Type of enclosure and cooling                    : TEFC/IC411
Degree of protection                             : IP55
Motor Gd2                                        : 5.32 kgm2
Fan moment of inertia referred
at motor shaft                                   : load details needed
Weight                                           : 680 kg
Applicable standards                             : IS:325-1996
Bearing DS                                       : 6316C3
Bearing NDS                                      : 6315C3
Motor Thermal time constant
Thermal withstand time Hot (Sec)                 : 20
Thermal withstand time cold (Sec)                : 46
Accessories                                      : Space heater (1 no 240V;50W),
Paint shade                                      : Epoxy paint 631
Rotation                                         : Bi directional
Noise levels                                     : as per IS12065
Vibration levels                                 : as per IS12075
Terminal box                                        : Rotatable 360 deg in steps of 90 deg
Terminal box IP class                                : IP 55
Terminal box fault level                            : 50 kA for 0.25 sec
Safe stall time at hot and cold condition (Sec)
for 80%                                             : 31 / 72
for 100%                                            : 20 / 46
for 110%                                            : 17 / 38
Bearing
Make                                               : SKF/FAG
Type                                               : Ball Bearings
Recommended Lubricant                              : Lithium based grease
Details of motor terminal box                      : Stud type arrangement
Temperature Indicator details                      : NA
Details of accessory terminal box                  : Stud type
Details of grounding                               : 2 earthing terminals on opposite sides on the
                                                     motor body and 1 inside the main terminal box
Value of Stator Resistance/phase at 20 deg C
(R1) approx. and stator Reactance(X1) appox.        : 0.065 ohm & 0.1309 ohm
Service factor                                      : 1.0
Starting time (sec)
     a) Without load
     at 80% V                                       : 0.28
    at 100% V                                       : 0.165
    at 110% V                                       : 0.132
     b) With load
     at 80% V                                       : Load details needed
     at 90% V                                       :
     at 110% V                                      :
Number of starts per hour                           : 2 hot 3 cold and 3 successive starts per hour
Pull out torque                                     : 1574 Nm
Overspeed and overloading capability
Overspeed                                           : 120% for 2 min
Overloading                                         : 160% for 15 sec
Number of grounding terminals                       : 2 at motor body and 1 in main terminal box
Efficiency at ¼ load                                : 88.3%
Connection                                          : Delta
Max. Cable size can be terminated                   : 2 x 3C x 185 Sqmm
Note: All performance figures are subject to IS tolerances
                                 TORQUE & CURRENT / SPEED CURVES
                    6.00                                                                                      3.00
                    5.00                                                                                      2.50
                    4.00                                                                                      2.00
                                                                                                                     Torque [T/Tn]
   Current [I/In]
                    3.00                                                                                      1.50
                    2.00                                                                                      1.00
                    1.00                                                                                      0.50
                    0.00                                                                                      0.00
                           0     200          400    600        800        1000    1200         1400    1600
                                                           Speed [r/min]
                                 I/In at Un         T/Tn at Un             Load T/Tn              T/Tn at 80%UnD
calculated catalog values, binding data on request
Date                                      16/9/13                                                      HX+280SMC4
GD2 motor [kgm2]                          5.32      Full load torque(Nm)     583   FLC in Ampère       157.0                D
                    Rating[kW]            90.00     Full load               1500   Voltage (volts)      415                 D
                                                    speed[r/min]
                                                                                   Current at          942.0                D
                                                                                   start[A]
                                                    GD2 Load[kgm2] at              starttime[s]         0.17         (0.28)
                                                    Motorspeed                     (80%D)
                                                                                   Stall time hot[s]   20.00         (31.3)
                     Project                                                 Ref
                                 TORQUE & CURRENT / SPEED CURVES
                    6.00                                                                                          3.50
                                                                                                                  3.00
                    5.00
                                                                                                                  2.50
                    4.00
                                                                                                                         Torque [T/Tn]
   Current [I/In]
                                                                                                                  2.00
                    3.00
                                                                                                                  1.50
                    2.00
                                                                                                                  1.00
                    1.00
                                                                                                                  0.50
                    0.00                                                                                          0.00
                           0      200         400        600        800        1000    1200         1400    1600
                                                               Speed [r/min]
                                 I/In at Un             T/Tn at Un             Load T/Tn            T/Tn at 110%UnD
calculated catalog values, binding data on request
Date                                          16/9/13                                                      HX+280SMC4
GD2 motor [kgm2]                              5.32      Full load torque(Nm)     583   FLC in Ampère       157.0                D
                    Rating[kW]                90.00     Full load               1500   Voltage (volts)      415                 D
                                                        speed[r/min]
                                                                                       Current at          942.0                D
                                                                                       start[A]
                                                        GD2 Load[kgm2] at              starttime[s]         0.17         (0.13)
                                                        Motorspeed                     (110%D)
                                                                                       Stall time hot[s]   20.00         (16.5)
                     Project                                                     Ref
                                        Load Current & Speed v/s Time
                  1600                                                                                            1000
                                                                                                                  900
                  1400
                                                                                                                  800
                  1200
                                                                                                                  700
                  1000
                                                                                                                  600
  Speed [r/min]
                                                                                                                         Current [A]
                  800                                                                                             500
                                                                                                                  400
                  600
                                                                                                                  300
                  400
                                                                                                                  200
                  200
                                                                                                                  100
                    0                                                                                            0
                         0       0.02   0.04      0.06    0.08     0.1       0.12       0.14       0.16      0.18
                                                            time [s]
                                                         Speed          Current
calculated catalog values, binding data on request
Date                                      16/9/13                        Motor Type                    HX+280SMC4
GD2 motor [kgm2]                           5.32     Full load              583      FLC in Ampère         157.0          D
                                                    torque(Nm)
                    Rating[kW]            90.00     Full load              1500     Voltage (volts)       415            D
                                                    speed[r/min]
                                                                                    Current at            942.0          D
                                                                                    start[A]
                                                    GD2 Load[kgm2] at               starttime[s]          0.17       (0.28)
                                                    Motorspeed                      (80%D)
                                                                                    Stall timehot[s]      20.00      (31.3)
                     Project                                               Ref
                                    LOAD PERFORMANCE CURVES
                  1.000                                                                    2.50
                  0.900
                  0.800                                                                    2.00
   / Efficiency
                  0.700
                                                                                                   I/In
                  0.600                                                                    1.50
                                                                                                   Slip % /
                  0.500
   Power Factor
                  0.400                                                                    1.00
                  0.300
                  0.200                                                                    0.50
                  0.100
                  0.000                                             0.00
                      0.000 0.200 0.400 0.600 0.800 1.000 1.200 1.400
                                                        P/Pn
                                  Cosphi           Effcy.           Slip          I/In
  Date                    16/9/13                                                        HX+280SMC4
Rating [kW]                90        Full load speed        1475     Voltage [volts]     415                  D
                                          [min-1]
FLC [amps]                157.0      Full load torque       582.7    Frequency [Hz]      50
                                           [Nm]
  CUSTOMER                                          0                      REF                 0
                                        Thermal withstand curve
                10000
                                                                  HOT
                                                                  COLD
                1000
    Time, sec
                 100
                  10
                   1
                        0         200               400             600         800
                                                 % Current
Voltage,%                   100                                           HX+280SMC4
CUSTOMER                                                  REF
                                       Thermal withstand curve
                10000
                                                                 HOT
                                                                 COLD
                1000
    Time, sec
                 100
                  10
                   1
                        0        200               400             600         800
                                                % Current
Voltage,%                   80                                           HX+280SMC4
CUSTOMER                                                 REF
                                       Thermal withstand curve
                1000
                                                                 HOT
                                                                 COLD
                100
    Time, sec
                 10
                  1
                       0         200               400             600         800
                                                % Current
Voltage,%                  110                                           HX+280SMC4
CUSTOMER                                                 REF