Condenser Simulation

This document summarizes the key parameters of a cooling water and compressed freon gas stream passing through a condenser heat exchanger. It provides the name, pressure, temperature, mass flow rate, enthalpy and other relevant details of the inlet and outlet streams. The condenser has a duty of 1,382,667 kJ/h and an overall heat transfer coefficient of 1,962 kJ/h-m2-C, cooling the freon gas from 85°C to 41.9°C.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
40 views3 pages

Condenser Simulation

This document summarizes the key parameters of a cooling water and compressed freon gas stream passing through a condenser heat exchanger. It provides the name, pressure, temperature, mass flow rate, enthalpy and other relevant details of the inlet and outlet streams. The condenser has a duty of 1,382,667 kJ/h and an overall heat transfer coefficient of 1,962 kJ/h-m2-C, cooling the freon gas from 85°C to 41.9°C.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 3

Case - Material Stream

Name cooling water IN cooling water OUT


Pressure [kPa] 200 176.524207700096
Temperature [C] 30 33.2763332257869
Mass Flow [kg/h] 100000 100000
Std Ideal Liq Vol Flow [m3/h] 100.285764695425 100.285764695425
Vapor / Phase Fraction 0 0
Molar Enthalpy [kJ/kgmole] -284519.984568979 -284270.981028943
Utility Type
Stream Price
Stream Price Basis Molar Flow Molar Flow
Cost Rate [Cost/s]

Feed Stream
Name cooling water IN compressed freon gas
Pressure [kPa] 200 1600
Temperature [C] 30 85
Mass Flow [kg/h] 100000 8000
Std Ideal Liq Vol Flow [m3/h] 100.285764695425 6.51441613434732
Vapor / Phase Fraction 0 1
Molar Enthalpy [kJ/kgmole] -284519.984568979 -498449.119830837
Utility Type
Stream Price
Stream Price Basis Molar Flow Molar Flow
Cost Rate [Cost/s]

Product Stream
Name cooling water OUT condensed freon liquid
Pressure [kPa] 176.524207700096 1594.98568633706
Temperature [C] 33.2763332257869 41.8691256629663
Mass Flow [kg/h] 100000 8000
Std Ideal Liq Vol Flow [m3/h] 100.285764695425 6.51441613434732
Vapor / Phase Fraction 0 0.233507096221517
Molar Enthalpy [kJ/kgmole] -284270.981028943 -513387.875992896
Utility Type
Stream Price
Stream Price Basis Molar Flow Molar Flow
Cost Rate [Cost/s]

Heat Exchanger
Name Condenser
Duty [kJ/h] 1382667.97469912
UA [kJ/C-h] 118376.361048371
Control UA [kJ/C-h] 118376.361048371
Tube Side Pressure Drop [kPa] 23.4757922999045
Shell Side Pressure Drop [kPa] 5.01431366293735
Tube Side Delta T [C] 3.27633322578691
Shell Side Delta T [C] -43.1308743370337
Uncorrected LMTD [C]
LMTD [C] 11.6802709802351
Ft Factor 1
Wall Time Constant [seconds]
Tube Side Zones 1
Shell Side Zones 1
Tube Side Volume [m3] 0.1
Shell Side Volume [m3] 0.1
Heat Trans. Area [m2] 60.318578948924
Shell UA Reference Flow [kg/h]
Tube UA Reference Flow [kg/h]
Minimum Flow Scale Factor 0
Shell side U [kJ/h-m2-C]
Tube side U [kJ/h-m2-C]
Overall U [kJ/h-m2-C] 1962.51906313325
Stream
compressed freon gas condensed freon liquid
1600 1594.98568633706
85 41.8691256629663
8000 8000
6.51441613434732 6.51441613434732
1 0.233507096221517
-498449.119830837 -513387.875992896

Molar Flow Molar Flow