0% found this document useful (0 votes)
40 views8 pages

3m-Es53u Multimetering

This document provides ordering information for the Model 53U multi-power monitor. The monitor can measure current, voltage, power factors and other variables for heavy-current power systems. It stores measured values and settings in non-volatile memory. Options include input types, auxiliary power supplies, external interfaces like Modbus, and approvals. Specifications cover measurements, inputs, outputs, communication protocols and general device information.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
40 views8 pages

3m-Es53u Multimetering

This document provides ordering information for the Model 53U multi-power monitor. The monitor can measure current, voltage, power factors and other variables for heavy-current power systems. It stores measured values and settings in non-volatile memory. Options include input types, auxiliary power supplies, external interfaces like Modbus, and approvals. Specifications cover measurements, inputs, outputs, communication protocols and general device information.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

MODEL: 53U

Power Transducer Series [2] CONTACT INPUT


0: None
( ‘External Interface’ codes 1, 4 and 5 Not selectable.)
MULTI POWER MONITOR
1: 24 V DC
(4 digital displays)
(‘External Interface’ codes 2, 3, 6, 7, 8 and 9 Not selectable.)
Functions & Features
2: 110 V DC
• Measures simultaneously several variables of a heavy-
(‘External Interface’ codes 2, 3, 6, 7, 8 and 9 Not selectable.)
current power system: current, voltage, active, reactive and
apparent power, active and reactive energy, power factor,
frequency, etc. [3] EXTERNAL INTERFACE
• All measured values, counter values, display mode, 1: Modbus, Do × 1, Di × 1
setting data are stored in the non-volatile memory at the 2: 4 – 20 mA DC × 4
power off 3: 1 – 5 V DC × 4
• Conversion factors, system configuration, interval times 4: 4 – 20 mA DC × 2, Do × 1, Di × 1
are programmable using the front keys 5: 1 – 5 V DC × 2, Do × 1, Di × 1
• Open collector output for alarm or energy count 6: 4 – 20 mA DC × 2, Do × 2
7: 1 – 5 V DC × 2, Do × 2
Typical Applications 8: Modbus, Do × 3
• Multi-functional power monitor incorporated in an electric 9: Do × 4
device: saves space, wiring works, and cost

[4] AUXILIARY POWER SUPPLY


96 (3.78)
AD4: universal (Option /UL not selectable.)
100 – 240 V AC (Operational range 85 – 264 V, 47 – 66 Hz) /
110 – 240 V DC (Operational range 99 – 264 V,
AX

ripple 10 %p-p max)


IN

96
(3.78) M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,
47 – 66 Hz)
115
(4.53)
mm (inch) [5] OPTIONS (multiple selections)
Performance
blank: Standard
MODEL: 53U-1[1][2][3]-[4][5] /H: High accuracy (voltage/current: ±0.2 %, energy: ±0.5 %)
Standards & Approvals
ORDERING INFORMATION blank: CE marking
• Code number: 53U-1[1][2][3]-[4][5] /UL: UL approval, CE marking
Specify a code from below for each [1] through [5]. Other Options
(e.g. 53U-1211-M2/H/Q) blank: none
• Specify the specification for option code /Q /Q: Option other than the above (specify the specification)
(e.g. /SET) (UL not available)

CONFIGURATION SPECIFICATIONS OF OPTION: Q


1: Single-phase / 2-wire and 3-wire, EX-FACTORY SETTING
3-phase / 3-wire and 4-wire /SET: Preset according to the Ordering Information Sheet
(No. ESU-6485)

[1] INPUT
1: 480 V / 1 A AC RELATED PRODUCTS
2: 480 V / 5 A AC • PC configurator software (model: PMCFG)
• PC Recorder Light software for the 53U (model:
MSR128LUx) Software downloadable at M-System’s web.
Software downloadable at M-System’s web site.
A dedicated cable is required to connect the module to the

http://www.m-system.co.jp/ 53U SPECIFICATIONS ES-6485 Rev.19 Page 1/8


MODEL: 53U
PC. Please refer to the internet software download site or Line-to-line (delta voltage): 480 V
the users manual for the PC configurator for applicable Line-neutral (phase voltage): 277 V (single-phase / 2-wire
cable types. and 3-wire)
Consumption VA: ≤ ULN2 / 300 kΩ / phase
Overload capacity: 200 % of rating for 10 sec., 120%
GENERAL SPECIFICATIONS
continuous
Construction: 96-mm square (1/4 DIN size) panel flush
Selectable primary voltage range: 50 – 400 000 V
mounted
• Current Input
Degree of protection
Rated current: 1 A or 5 A
Front panel: IP 50
Consumption VA: ≤ I2 · 0.01 Ω / phase
Terminal block, housing: IP 30
Overload capacity: 4000 % of rating for 1 sec., 2000% for 4
Connection
sec., 120% continuous
Voltage input: Connector type terminal block
Selectable primary current range: 1 – 20 000 A
(applicable wire size ≤ 2.5 dia, 0.5 – 3.5 mm2)
Operational range
Current input: Screw terminal block
Voltage, current, apparent power: ≤ 120 % of the rating
(applicable wire size ≤ 2.4 dia, 0.5 – 3.5 mm2)
Active/reactive power: ≤ ±120 % of the rating
Output, power: Connector type terminal block
Frequency: 45 – 65 Hz
(applicable wire size ≤ 2.4 dia, 0.5 – 2.5 mm2)
Power factor: ≤ ±1
Configuration: Single phase/2-wire and 3-wire, 3-phase/3-
■ Contact Input: 24 V DC or 110 V DC
wire balanced/unbalanced load, 3-phase/4-wire
(input resistance 6 kΩ)
balanced/unbalanced load
Detecting voltage: External 24 V DC ±10 % or 110 V DC
Housing material: Flame-resistant resin (gray)
±10 %
Isolation: Voltage input to current input to contact input to
ON current: ≥ 1 mA (≤ 24 kΩ @ 24 V, ≤ 110 kΩ @110 V)
network interface or configurator jack or analog output to
OFF current: ≤ 0.1 mA (≥ 240 kΩ @ 24 V, ≥ 1.1 MΩ @ 110
contact output (between each contact output except for
V)
External Interface code 8) to power
Detecting time: 10 – 1000 msec.
• Measured variables
The status can be monitored on the Modbus; usable to reset
Voltage: 1 – N, 2 – N, 3 – N, 1 – 2, 2 – 3, 3 – 1
energy count or to update average (demand) value.
Current: 1, 2, 3, N
Average current: 1, 2, 3
Active / reactive / apparent power: 1, 2, 3, Σ OUTPUT SPECIFICATIONS
Power factor: 1, 2, 3, Σ ■ Network Interface
Frequency Communication: Half-duplex, asynchronous, no procedure
Phase angle between voltages: 1 - 2, 2 - 3, 3 - 1 Interface: Conforms to EIA RS-485
Active energy incoming / outgoing: Σ Max. transmission distance: 500 meters
Reactive energy inductive / capacitive: Σ Baud rate: 1.2 – 38.4 kbps
Apparent energy: Σ Max. number of nodes: 31 (except the master)
Active / reactive / apparent power intervals (demand) Protocol: Modbus RTU
Other demands Node address: 1 – 247 (factory default setting: 1)
Harmonic contents: 2nd to 31st Parity: none, even or odd (factory default setting: odd)
Max. and min. values Stop bit: 1 or 2 (factory default setting: 1)
Media: Shielded twisted-pair cable (CPEV-S 0.9 dia.)
■ DISPLAY: LCD with LED backlight ■ DC Current: 4 – 20 mA DC
(LED OFF timer available) Load resistance: ≤ 270 Ω
Signed: 4 digits, 3 lines Measurands converted into analog output: Voltage, Current,
Energy: 9 digits, 1 line Active / reactive / apparent power, Power factor, Frequency,
Bargraph: 3 points Harmonic contents
■ DC Voltage: 1 – 5 V DC
Load resistance: ≥ 5000 Ω
INPUT SPECIFICATIONS
Measurands converted into analog output: Voltage, Current,
Frequency: 50 / 60 Hz (45 – 65 Hz)
Active / reactive / apparent power, Power factor, Frequency,
• Voltage Input
Harmonic contents
Rated voltage
■ Open Collector

http://www.m-system.co.jp/ 53U SPECIFICATIONS ES-6485 Rev.19 Page 2/8


MODEL: 53U
Programmable for either alarm or energy count. output to power)
Max. rated load: 130 V DC @50 mA 2500 V AC @1 minute
Continuous rated load: 130 V DC @30 mA (voltage input to current input to contact input to contact
Saturation voltage: 1.5 V DC output to network interface or configurator jack or analog
Measurands applicable to alarm: Voltage, current, current output)
intervals, neutral current, frequency, energy, energy 2000 V AC @1 minute
intervals (between each contact output except for External Interface
(ON delay, deadband and other parameters are selectable) code 8)
Measurands applicable to count: Energy; 2000 V AC @1 minute (circuits to housing)
Pulse rate selectable within
0.1 – 10 000.0 kWh/p, kvarh/p, kVAh/p
STANDARDS & APPROVALS
CE conformity:
EMC Directive (2004/108/EC)
EMI EN 61000-6-4: 2007
EMS EN 61000-6-2: 2005
INSTALLATION Low Voltage Directive (2006/95/EC)
Power consumption
EN 61010-1: 2001
•AC: < 8 VA
Measurement Category III (input)
•DC: < 4 W
Installation Category II (power)
Operating temperature: -10 to +55°C (14 to 131°F)
Pollution Degree 2
Storage temperature: -20 to +80°C (-4 to +176°F)
Input to power: Reinforced insulation (550 V)
Operating humidity: 90 % RH max. (non-condensing)
Output to power: Reinforced insulation (300 V)
Mounting: Panel flush mounting
Input to output: Basic insulation (550 V)
Weight: 300 g (0.66 lb)
Approval:
UL/C-UL general safety requirements
PERFORMANCE (UL 61010-1:2005, CAN/CSA-C22.2 No.61010-1:2004)
Accuracy (at 23°C ±10°C or 73.4°F ±18°F, 45 – 65 Hz) IEC standard:
Voltage: ±0.3 % (±0.2 % for Option /H)* IEC 62053-22: 2003 class 0.5s
Current: ±0.3 % (±0.2 % for Option /H)* IEC 62053-23: 2003 class 2
Power: ±0.5 %* (IEC standards are applicable with Option /H only)
Power factor: ±0.5 %
Frequency: ±0.1 %*
MOUNTING REQUIREMENTS mm (inch)
Energy: ±1 % (±0.5 % for Option /H)
■ PANEL CUTOUT unit: mm (inch)
Harmonic contents: ±1 %* +0.8 (3.65)
92 0 (3.63)
Analog output: Accuracy of assigned measurand or ±0.2 %,
whichever is greater.
* In percentage of the spans: 480 V for voltage, 1 A or 5 A
for current, 4155 W (5 A) or 831 W (1 A) for active power.
The described accuracy levels are ensured at the input 1 %
+0.8 (3.65)
0 (3.63)

or more for phase 2 current with 3-phase/3-wire unbalanced


load, for neutral current with 3-phase/4-wire unbalanced
92

load, and neutral current with 1-phase/3-wire.


Response time: ≤ 2 sec. (0 – 99 %),
≤ 3 sec. for frequency and harmonic contents
Sampling time: Panel thickness : 2 to 15 mm (0.08 to 0.59 inch)
Harmonic contents and frequency: ≤ 1.1 sec.
Other: ≤ 600 msec.
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength:
4000 V AC @1 minute
(voltage input or current input or contact input or contact
output or network interface or configurator jack or analog

http://www.m-system.co.jp/ 53U SPECIFICATIONS ES-6485 Rev.19 Page 3/8


MODEL: 53U
EXTERNAL VIEW
■ FRONT VIEW ■ REAR VIEW

Voltage Input
Data Displays Terminals
Current Input
Terminals

Power Input
Terminals Configurator
Jack
Control Buttons ∑ IU PQS PF THD MAX E PRG
Ext. Interface
ENTER ESCAPE Terminals

TERMINAL CONNECTIONS
For UL approved model, L and N are marked, instead of U(+) and V(-).
Input

V1 V2 V3 N 1S 1L 2S 2L 3S 3L System /
Application
Terminal

V1 V2 V3 1S 1L 3S 3L V1 V2 V3 1S 1L 3S 3L

source load source k l load


L1 L1
K L k l
L2 L2
CONFIG Three phase /
U V + – + – T1 T2T3 T4 L3 L3
K L
(+) (–) 3-wire,
unbalanced load
Configurator Jack V1 V2 V3 1S 1L 3S 3L
DO/PO DI

u v v u

source k l load
U V V U
Power Input External Interface L1
K L k l
L2
System / L3
Application
Terminal K L

V1 N 1S 1L V1 N 1S 1L V1 N 1S 1L V1 N 1S 1L

source load source k l load source load source k l load


L1 L1 L1 L1
K L K L
N N L2 L2
Single phase / Three phase / L3 L3
2-wire 4-wire, N N

V1 N 1S 1L balanced load V1 N 1S 1L

u v u v

source U V k l load k l
source U V load
L1 L1
K L K L
N L2
L3
N

V1 V2 V3 1S 1L V1 V2 V3 1S 1L

V1 V2 V3 N 1S 1L 2S 2L 3S 3L
source load source k l load
L1 L1
K L
L2 L2
Three phase / L3 L3 source load
3-wire, L1
L2
balanced load V1 V2 V3 1S 1L L3
N
u v v u

source k l load
U V V U
L1 V1 V2 V3 N 1S 1L 2S 2L 3S 3L
K L
L2
L3
Three phase /
4-wire, source k l load
k l
V1 N V2 1S 1L 2S 2L V1 N V2 1S 1L 2S 2L unbalanced load L1
K L k l
L2
K L
L3
K L
N
source load source k l load
L1 L1
K L k l
N N
L2 L2 V1 V2 V3 N 1S 1L 2S 2L 3S 3L
Single phase / K L

3-wire u v u v u v
V1 N V2 1S 1L 2S 2L
source k l load
U V U V U V k l
L1
u v v u K L k l
L2
K L
source k l load L3
U V V U K L
L1 N
K L k l
N
L2
K L

http://www.m-system.co.jp/ 53U SPECIFICATIONS ES-6485 Rev.19 Page 4/8


MODEL: 53U
■ EXTERNAL INTERFACE CODE: 1 ■ EXTERNAL INTERFACE CODE: 2, 3

DI + AO1 +
CONTACT ANALOG
INPUT OUTPUT 1
DI – AO1 –

DO/PO+ AO2 +
CONTACT ANALOG
OUTPUT OUTPUT 2
DO/PO– AO2 –
Shielded Twisted-pair Cable
T1 + To other AO3 +
ANALOG
T2 – Modbus devices OUTPUT 3
AO3 –
T3
Term.
Jumper *1
Resist. T4 AO4 +
ANALOG
*3 OUTPUT 4
U(+) AO4 –
POWER 3
V(–) U(+) *
POWER
JACK CONFIGURATOR V(–)

JACK CONFIGURATOR *2

■ EXTERNAL INTERFACE CODE: 4, 5 ■ EXTERNAL INTERFACE CODE: 6, 7

DI + AO1 +
CONTACT ANALOG
INPUT OUTPUT 1
DI – AO1 –

DO/PO+ AO2 +
CONTACT ANALOG
OUTPUT OUTPUT 2
DO/PO– AO2 –

AO1 + DO/PO1+
ANALOG CONTACT
OUTPUT 1 OUTPUT 1
AO1 – DO/PO1–

AO2 + DO/PO2+
ANALOG CONTACT
OUTPUT 2 OUTPUT 2
AO2 – DO/PO2–
*3 3
U(+) U(+) *
POWER POWER
V(–) V(–)

JACK CONFIGURATOR *2 JACK CONFIGURATOR *2

■ EXTERNAL INTERFACE CODE: 8 ■ EXTERNAL INTERFACE CODE: 9

DO/PO1+ DO/PO1+
CONTACT OUTPUT 1 CONTACT
OUTPUT 1
DO/PO2+ DO/PO1–
CONTACT OUTPUT 2
DO/PO3+ DO/PO2+
CONTACT OUTPUT 3 CONTACT
OUTPUT 2
DO/PO COM DO/PO2–
Shielded Twisted-pair Cable
T1 + To other DO/PO3+
CONTACT
T2 – Modbus devices OUTPUT 3
DO/PO3–
T3
Term.
Jumper *1
Resist. T4 DO/PO4+
CONTACT
OUTPUT 4
U(+) *3 DO/PO4–
POWER
V(–) U(+) *3
POWER
JACK CONFIGURATOR V(–)

JACK CONFIGURATOR

• Contact Input Connection E.g. • Contact Output Connection E.g.


*1. When the device is located at the end of a transmission line via
twisted-pair cable, (when there is no cross-wiring), close across the
DI + + DO/PO+ +
terminal T2 – T3 with a leadwire.
When the device is not at the end, no shortcircuit wire is required.
DI – - DO/PO– - *2. Analog output may momentarily fluctuate while the configurator cable
is left connected.
*3. For UL approved model, L and N are marked, instead of U(+) and V(–).

http://www.m-system.co.jp/ 53U SPECIFICATIONS ES-6485 Rev.19 Page 5/8


MODEL: 53U
MODBUS WIRING CONNECTION
R2K-1 RS-485 RS-485
53U 53U

CONNECTOR
T1 T1 T1
RS-232C
T2 T2 T2
*1 *1
T3 T3 T3
T4 T4 T4

FG *
2

*1. Internal terminating resistor is used when the device is at the end of a transmission line.
*2. Install shield cables to all sections and ground them at single point.

DIMENSIONS unit: mm (inch)


3 (.12)

96 (3.78) 23 (.91) 80 (3.15) [12 (.47)] 92 (3.62)

10
0(
3.9
4)
dia
.

92 (3.62)
96 (3.78)

2 (.08)
3 (.12)

GASKET MOUNTING BRACKET

http://www.m-system.co.jp/ 53U SPECIFICATIONS ES-6485 Rev.19 Page 6/8


MODEL: 53U
SYSTEM CONFIGURATION EXAMPLES
■ RS-485 / RS-232C

RS-232C

RS-232C/RS-485
Converter
(model: R2K-1 or LK1)

Lightning Surge Protector


for RS-485/422
(model: MD74R or MDP-4R) *1

RS-485 (Modbus RTU)

Lightning Surge Protector


for RS-485/422
(model: MD74R or MDP-4R) *1

AX AX AX
IN IN IN

Multi Power Monitor


(model: 53U)

■ RS-485 / ETHERNET

Ethernet

Communication Adaptor
ETHERNET

RUN
SEND
FIELD
(model: 72EM-M4 or 72EM2-M4)
CNFG

Lightning Surge Protector


for RS-485/422
(model: MD74R or MDP-4R) *1

RS-485 (Modbus RTU)

Lightning Surge Protector


for RS-485/422
(model: MD74R or MDP-4R) *1

AX AX AX
IN IN IN

Multi Power Monitor


(model: 53U)

*1. Insert lightning surge protectors recommended in this example if necessary.

http://www.m-system.co.jp/ 53U SPECIFICATIONS ES-6485 Rev.19 Page 7/8


MODEL: 53U

Specifications are subject to change without notice.

http://www.m-system.co.jp/ 53U SPECIFICATIONS ES-6485 Rev.19 Page 8/8