This document summarizes the header calculation for a project. It provides input data on flow rates and pipe sizes for 8 header inlets totaling 26,600 L/h. The designated header pipe size is 3" with an ID of 82.8 mm and length of 20 meters. The results show the header fluid velocity is 1.37 m/s, Reynolds number is 113621.1, and friction head is 1.1 meters with a pressure drop of 0.11 barg. The selected header pipe ID of 82.8 mm and size of 3" satisfies the criteria of being greater than the maximum inlet, having a velocity under 2 m/s, and a pressure drop less than 1 barg.

Uploaded by

Naufal Hadi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
460 views1 page

Header Size

This document summarizes the header calculation for a project. It provides input data on flow rates and pipe sizes for 8 header inlets totaling 26,600 L/h. The designated header pipe size is 3" with an ID of 82.8 mm and length of 20 meters. The results show the header fluid velocity is 1.37 m/s, Reynolds number is 113621.1, and friction head is 1.1 meters with a pressure drop of 0.11 barg. The selected header pipe ID of 82.8 mm and size of 3" satisfies the criteria of being greater than the maximum inlet, having a velocity under 2 m/s, and a pressure drop less than 1 barg.

Uploaded by

Naufal Hadi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Project No.

: Date : 24-Aug-23
Doc No. : Prepared by : NFL
Equipment tag : Checked by : Vegapunk
Project Name :

Tittle : Collecting Header Calculation Revision No. 0

1. Input Data

Flowrate Pipe Size *) Fluid velocity


No Header inlet
(L/h) NPS ID (mm) (m/s)
1 Header inlet 1 3.600 1" 27,86 1,64
2 Header inlet 2 8.000 1.5" 42,76 1,55
3 Header inlet 3 15.000 2" 54,76 1,77
4 Header inlet 4 1" 27,86
5 Header inlet 5 1" 27,86
6 Header inlet 6 1" 27,86
7 Header inlet 7 1" 27,86
8 Header inlet 8 1" 27,86
*) Nominal pipe size is according to ASME Sch40 pipe size

Total flowrate : 26.600 L/h


Average velocity : 1,65 m/s

2. Header Design

Designated header pipe size : 3" NPS


Designated header pipe ID : 82,8 mm
Designated header length : 20 meter
Header pipe roughness : Commercial steel Roughness : 0,046 mm

Fluid media : Water


Fluid density : 1000 kg/m3
Fluid viscosity : 0,001 Pa.s

3. Results

Header fluid velocity : 1,37 m/s


Header fluid Reynold number : 113621,1
Header fluid Reynold criteria : Turbulence
Friction factor : 0,012
Header friction head : 1,1 meter
Header pressure drop : 0,11 barg

Now with above results, the header size is based on this following criteria. The size
will satisfied if the results fullfill at least two criteria

Header size is > 1.33 times of maximum inlet Yes


Header velocity is not over 2 m/s Yes
Header pressure drop less than 1 barg Yes

Selected header pipe ID : 82,8 mm


Selected header pipe size : 3" Satisfied