Project No.
: Date : 24-Aug-23
Doc No. : Prepared by : NFL
Equipment tag : Checked by : Vegapunk
Project Name :
Tittle : Collecting Header Calculation Revision No. 0
1. Input Data
Flowrate Pipe Size *) Fluid velocity
No Header inlet
(L/h) NPS ID (mm) (m/s)
1 Header inlet 1 3.600 1" 27,86 1,64
2 Header inlet 2 8.000 1.5" 42,76 1,55
3 Header inlet 3 15.000 2" 54,76 1,77
4 Header inlet 4 1" 27,86
5 Header inlet 5 1" 27,86
6 Header inlet 6 1" 27,86
7 Header inlet 7 1" 27,86
8 Header inlet 8 1" 27,86
*) Nominal pipe size is according to ASME Sch40 pipe size
Total flowrate : 26.600 L/h
Average velocity : 1,65 m/s
2. Header Design
Designated header pipe size : 3" NPS
Designated header pipe ID : 82,8 mm
Designated header length : 20 meter
Header pipe roughness : Commercial steel Roughness : 0,046 mm
Fluid media : Water
Fluid density : 1000 kg/m3
Fluid viscosity : 0,001 Pa.s
3. Results
Header fluid velocity : 1,37 m/s
Header fluid Reynold number : 113621,1
Header fluid Reynold criteria : Turbulence
Friction factor : 0,012
Header friction head : 1,1 meter
Header pressure drop : 0,11 barg
Now with above results, the header size is based on this following criteria. The size
will satisfied if the results fullfill at least two criteria
Header size is > 1.33 times of maximum inlet Yes
Header velocity is not over 2 m/s Yes
Header pressure drop less than 1 barg Yes
Selected header pipe ID : 82,8 mm
Selected header pipe size : 3" Satisfied