Programmable Thermostat Guide

This programmable ambient thermostat allows you to control your heating and air conditioning systems with four temperature levels for comfort, a second comfort level, eco, and frost protection. It can be installed on an interior wall away from heat sources and sunlight. The thermostat connects to the boiler or heat pump thermostat input for temperature regulation and can also connect to circulators, remote controls, and external probes.

Uploaded by

r.muharem
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
28 views4 pages

Programmable Thermostat Guide

This programmable ambient thermostat allows you to control your heating and air conditioning systems with four temperature levels for comfort, a second comfort level, eco, and frost protection. It can be installed on an interior wall away from heat sources and sunlight. The thermostat connects to the boiler or heat pump thermostat input for temperature regulation and can also connect to circulators, remote controls, and external probes.

Uploaded by

r.muharem
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

§ Programmable ambient User instructions

thermostat, mains, weekly

This programmable ambient thermostat has been designed to bring you comfort and energy economy.
It allows you to program and regulate your heating system at 4 temperature levels :
6T 7786-02B


ok
+ - Comfort : this is the temperature you desire during the hours you are present.
- Comfort 2 : 2nd temperature level that you desire during the time you are present.
- Eco : this is the temperature you desire during short absences or at night.
- Frost protection : this is the guaranteed minimum temperature during your prolonged absences.
It protects your accommodation against the dangers of frost.
It also enables you to program and regulate your air conditioning at 2 temperature levels :
EK530 - Comfort : this is the temperature you desire during the hours you are present.
- Eco : this is the temperature you desire during short absences or at night.

Product description Electrical installation and connections 5. Reclose the flap.


To guarantee its ambient temperature-regulation 6. Clip the front face onto the wall-mounted base.
function, the thermostat should be installed around
1.3 m above the ground, on an interior wall and
Connection of the thermostat to a thermostat
away from direct sunlight or any heat source such
input on the boiler
as a television, lamp, radiator, draft, chimney, etc.
Fix the thermostat onto the flush-mounted casing or
in the slot without a casing intended for this purpose. L
N

external probe
123 4 - 5 6 7 8 9 (ref. 25190)
2A

telephonic
remote control
(ref. 61123, 61124)
– +
ok

input
from remote ambient thermostat

 Context key for menu access For optimum quality temperature regulation, seal
 Context key for mode access holidays the flush-mounted casing or the electrical duct. Connection of the thermostat to the thermostat
 Context key to access the temporary 1. Separate the product from the wall-mounted input of a reversible or irreversible heat pump (HP)
base, by pushing on the button located under
override
the base.
 Confirmation key OK L
 Adjustment keys + and - N

external probe
123 4 - 5 6 7 8 9 (ref. 25190)
TOP 2A

+

ok telephonic
remote control
(ref. 61123, 61124)

input
from remote ambient thermostat

2. Open the flap with the help of a screwdriver and


attach the wall-mounted base using the screws.
3. Next, pass the electrical cables into the holes Connection of a heating or air conditioning
 Indicator for days of the week intended for this purpose. circulator
 Automatic mode/manual mode
(thermostat without program)
Temperature set-points adjustment L
N
Standby
Heating/Air-con selector external
TOP TOP 123 4 - 5 6 7 8 9 probe
Programming/program selection (ref. 25190)
Time and date adjustment 6A 2A
 Adjustment of settings telephonic
 Ambient temperature remote control
 Heating or air conditioning indicator (ref. 61123, 61124)

 Current mode (heating or air conditioning)


 Current setting ( , , , )
 Temperature of current setting
 Telephonic remote control
 Profile of today’s program
2
This product must be installed according
Current time 4. Connect the product according to the wiring
diagram opposite. to the local installation standards in force.

1
Downloaded from www.Manualslib.com manuals search engine
Initial adjustment and updating Installer parameters
When the product is first used, the screen offers the To access all the parameters (from PA:1 to PA:12), press key  menu to place the cursor under
option to adjust the year, date and time, without and then give one long press (>5s) on OK.
going into the parameter settings. To only access parameters from (PA:1 to PA:4), press key  menu to place the cursor under
or and confirm using the OK key.
Press key  menu to place the cursor under .
• The year flashes. Press key  +, the navigation key,
to adjust the current year. PA:1 - Default duration of the temporary override
Confirm using the OK key. This parameter allows you to input a default, restart time delay. Possible delay times are the following:
• The month flashes. Now press key  + or -. 1 hour, 2 hours, 3 hours, 4 hours, 5 hours and 12 hours. The restart delay is set to 1 hour by default.
Confirm using the OK then proceed in the same • PA:1 and flash. Press key  + or - to modify the restart delay.
manner to select the day, hour and minutes. Confirm using the OK key to pass to the next parameter.
• AUTO flashes. Press key  + to set the installation
to switch automatically between summer and PA:2 - Backlighting
winter time (auto) or not (OFf). Confirm using the Backlighting is activated (ON) by default.
OK key. • Press key  + or - to deactivate it (OFf).
• 24:H flashes. Press key  + and select Confirm using the OK key key to pass to the next parameter.
the 12 hour or 24 hour time format.
Confirm using the OK key. PA:3 - Temperature calibration
This parameter lets you adjust the value displayed by the thermostat if you measure a different
Automatic mode (auto) ambient temperature to that which the thermostat measures.
In automatic mode, the thermostat adapts itself to • Press key  + or - to modify the temperature within a range of +/-3 °C.
the rhythm of your life by applying one or more pro- Confirm using the OK key to pass to the next parameter.
grams that you have selected. PA:4 - 2nd Comfort temperature level
• Press key  menu to place the cursor under
auto. This parameter allows you to select one or two Comfort temperature levels. It is only applicable
Key  menu allows you to return to auto mode during programming of the free program (P4).
when the (holiday) program is running or a timed • Press key  + or - to choose 1 or 2 .
restart is in progress. Confirm using the OK key to pass to the next parameter.
Parameter PA:4 is set to 1 single level of Comfort by default.
Manual mode (manu) PA:5 - Heating/Air-con mode
Manual mode transforms your equipment into a
simple thermostat. It allows you to maintain a This parameter allows you to put your installation into Heating mode (H), Air conditioning mode (C)
constant temperature in your accommodation or reversible Heating/Air-con mode (HC) (the icon is displayed).
(adjustable from +5 °C to +30 °C) and ignores the • Press key  + or - to select H, C or HC.
available program profiles. Confirm using the OK key to pass to the next parameter.
• Press key  menu to place the cursor under Parameter PA:5 is set to heating H) by default.
manu. In HC mode, care should be taken to switch the HP suitably for the chosen thermostat mode.
• Press key  + or - to adjust the desired tempera- PA:6 - Degumming the pump
ture.
Example : the desired temperature is at 22.5 °C and This parameter allows you to activate/deactivate the automatic start-up of the pump at midnight
the ambient temperature is 20 °C. everyday, in order to avoid its jamming during the summer.
The heating-activated indicator 15 is illuminated. • Press key  + or - to activate (ON) or desactivate (OFf).
Confirm using the OK key to pass to the next parameter.
Parameter PA:6 6 is set to OFf by default.
PA:7 - Type of heating regulation
This parameter lets you define the type of inertia of your heating installation.
• Press key  + or - to select :
- On/OFf = On or off (default setting). The differential is less than 0.3°C (factory setting).
- FAS = PID regulation for installations with rapid inertia (radiator).
Minimum run time 1 minute (10% of the cycle time).
- SLo = PID for installations with slow inertia (underfloor heating).
Minimum run time 2 minutes (10% of the cycle time).
• Confirm using the OK key to pass to the next parameter.
In On/Off regulation, only the anticipation function is available, see PA:9
In PID regulation, the optimisation and anticipation functions are available, see PA:9.
PA:8 - Type of regulation for air conditioning
As PA:7 but FAS used for convector fan and SLo for underfloor cooling.
Standby mode PA:9 - Optimisation and anticipation
The heating and/or air conditioning system can be
put on standby. The thermostat is live and protects This parameter allows you to activate an optimisation or anticipation function which is deactivated
your installation if the temperature drops below (OFf) by default.
5 °C (fixed non-modifiable instruction). It displays The optimisation function is only available with PID regulation, see PA:7 or PA:8
the time, current day, ambient temperature and The anticipation function is available with on/off and PID regulation.
Off information. Optimisation : he thermostat automatically estimates the time required
• Press key  menu to place the cursor to reach the Comfort temperature and adjusts the switch-on time of the
under . heating so that the desired temperature is attained at the desired time. 20 °C
OFf flashes. A period of around 10 days is necessary to train the installation because 18 °C
• Confirm using the OK key. it depends on the type of inertia of your heating. 16 °C
• Press key  menu to exit standby mode. Note : only P1o benefits from the optimisation function. 7h
From air conditioning mode, standby mode • Press key  + to activate (AUT) the optimisation function. x H (automatic calculation)
represents a stop command and the ambient Confirm using the OK key to pass to the next parameter.
temperature is no longer regulated.
In reversible heating/air-conditioning mode (select HC for parameter
PA:5); it is possible to select a different mode of regulation for each
system.
The heating may be configured as on/off and the air conditioning as PID
regulated. In this case, the optimisation function and program P1o can
only be applied during PID regulated air-conditioning.
Anticipation : this function allows the Comfort or Comfort 2
temperature from the personalised program (P4) to be applied, in
advance, for a configurable period of 1, 2 or 3 hours. 20 °C

Note : only P4a benefits from the anticipation function. 18 °C


• Press key  + to select the duration (1H, 2H ou 3H) of anticipation 16 °C
desired, (e.g. anticipation of 2 hours). 6h
Confirm using the OK key to pass to the next parameter. 2H

2
Downloaded from www.Manualslib.com manuals search engine
… cont. Modification of the Comfort 2 temperature
• The Comfort temperature flashes.
PA:10 - Return to factory settings • Press key  + or - to modify the temperature.
This parameter lets you return programs and parameters to the factory settings. Confirm using the OK key.
• Press key  + or - to choose Yes (reset) or no (pas de reset). This adjustment is only available if the 2nd Comfort
Confirm using the OK key to pass to the next parameter. temperature level has been selected in the parame-
ter menu PA:4.
PA:12 - Software version Modification of the Eco temperature
This parameter displays which version of the software is installed in the product. • The Eco temperature flashes.
Press OK to exit from parameter adjustments. • Press key  + or - to modify the temperature.
Confirm using the OK key.
Choice of the mode of regulation as a function of the heating/air-conditioning generator.
- ON/OFF regulation: suitable for all types of installation (gas boiler with or without flue, fuel oil boiler,
heat pump, heating/air-conditioning circulation).
- PID regulation: suitable for the following installations: heating or cooling circulation, gas boiler. Programming
The most accurate regulation. Four programs are available to program your
week : P1, P2, P3, , which are pre-recorded and not
modifiable, and P4 P4 which is free and allows
User parameters you to create a personalised program that can be
To access the user parameters, press key  menu to place the cursor under and confirm using different for each day of the week.
the OK key. P1o is only available when the optimisation parame-
ter is active (PA:9) and P4a is only available when
PA:1 - Default duration of the temporary override the anticipation parameter is active (PA:9). Your
installer will perform the required parameterisation.
This parameter allows you to input a default, restart time delay. Possible delay times are the following:
1 hour, 2 hours, 3 hours, 4 hours, 5 hours and 12 hours. The restart delay is set to 1 hour by default. P1 = Comfort temperature from 06:00 to 23:00.
• PA:1 and flash. Press key  + or - to modify the timed restart delay. Eco temperature from 23:00 to 06:00.
Confirm using the OK key to pass to the next parameter.
PA:2 - Backlighting
Backlighting is activated (on) by default.
• Press key  + or - to deactivate it (OFf). P1 is activated 7 days per week by
Confirm using the OK key to pass to the next parameter. default. If this fits the rhythm of your life
PA:3 - Temperature calibration then remain in automatic mode; if not,
continue.
This parameter lets you adjust the value displayed by the thermostat if you measure a different
ambient temperature to that which the thermostat measures.
• Press key  + or - to modify the temperature within a range of +/-3 °C.
Confirm using the OK key. P1o = Optimisation (only with P1).
Comfort temperature from 07:00 to 23:00.
PA:4 - 2nd Comfort temperature level Eco temperature from 23:00 to 07:00.
This parameter allows you to choose one or two Comfort temperature levels. It is only
applicable during programming of the free program (P4).
• Press key  + or - to choose 1 to 2 .
Confirm using the OK key to pass to the next parameter.
Parameter PA:4 is set to 1, single Comfort level, by default.
P2 = Comfort temperature from 06:00 to 08:30
Once adjustment of these 4 parameters is carried out, the thermostat switches to auto mode and and from 16:30 to 23:00.
registers these modifications. Eco temperature from 08:30 to 16:30
and from 23:00 to 06:00.
Holiday mode flashes and the thermostat regulates the air
This mode protects your accommodation conditioning.
against the dangers of frost and maintains a
minimum temperature during your absences, In HC mode, care should be taken to switch the HP
which can be adjusted between 5 °C and suitably for the chosen thermostat mode.
30 °C. P3 = Comfort temperature from 06:00 to 08:30,
You can program the duration of your absence from 11:30 to 13:30 and from 16:30 to 23:00.
to anticipate a rise in temperature for your Eco temperature from 08:30 to 11:30,
return. from 13:30 to 16:30 and from 23:00 to 06:00.
• Press key  , and then press key  +
to select the number of days absence
(from 1 to 99 days).
The current day counts as 1.
Confirm using the OK key.
• The icon appears and the temperature
to be adjusted flashes. P4 = a free program which allows you to create
• Press key  + or - to indicate the desired up to 5 Comfort temperature periods and
temperature level. Confirm using the OK key. 5 Eco temperature periods, for each of the
Leave the thermostat in this mode. To cancel days of the week.
and return to automatic mode,  menu.
• To modify the duration of your absence or Adjusting the temperature set-points
the temperature value, press key  and By default, the thermostat is in Heating mode (H) Assigning an existing program (P1, P2 or P3)
proceed to the changes. see installer parameters PA:5 - Heating/Air-con mode. to one or more days of the week
- If PA:5 5 is set to heating only (H). The tempera- You can assign any of the programs to all 7 days
If the thermostat is in air conditioning mode, of the week, to a group of five weekdays, to a
you can create 1 holiday programme and tures are preset:
Comfort = 19 °C, Comfort 2 = 20 °C, Eco = 16 °C. group of two days for the weekend or to an indivi-
define the number of days absence. dual day.
The adjustment range for the heating set-points
The air conditioning will stop.
is from 5 °C to 30 °C. • Press key  menu to place the cursor under
The ambient temperature will not be regulated. prog. The indicators for the seven days of the
- If PA:5 is set to air conditioning only (C).
The temperatures are preset: week flash.
Heating/Air-con reversibility Comfort = 24 °C, Eco = 29 °C. The range of • Press key  + to select which day, or group of
This function allows your installation to switch adjustment for the air conditioning set points days, to assign a program to.
from Heating to Air conditioning mode. is from 20 °C to 30 °C. Confirm using the OK key.
It requires that parameter PA:5 in HC in the - If PA:5 is set to reversible heating/air conditioning • P1 flashes. Press key  + to select the program
menu (Heating/Air-con mode) is set (HC), you can modify the pre-set temperatures for to apply.
beforehand. each mode and . Confirm using the OK key.
• Press key  menu to place the cursor As an example, to assign P2 to the group of five
under . Modification of the Comfort temperature
• flashes and the thermostat regulates the • Press key  menu to place the cursor under . weekdays and P1 to the group of two weekend days:
The Comfort temperature flashes. • Press key  menu to place the cursor under
heating.
• Press key  to change from Heating • Press key  + or - to modify the temperature. prog. The indicators for the seven days of the
Confirm using the OK key. week flash.
mode to Air conditioning mode.

3 www.hager.com
Downloaded from www.Manualslib.com manuals search engine
• Press key  + to select to affect the group of Temporary overrides The thermostat estimates that the ambient
five days (the group of five days flashes). By overriding until the next program step, temperature will be less than the setpoint
Confirm using the OK key. in auto mode, it is possible to modify the temperature temperature if it does not contribute additional
• P1 flashes. Press key  + to select P2 (P2 of the current set-point. energy. It requests ignition of the generator.
flashes). Confirm using the OK key. • Press key  + or - to increase or reduce Ask your installer for confirmation.
• Press key  + to select the group of 2 weekend the temperature of the displayed set-point.
days (the group of 2 weekend days flashes). The set-point temperature flashes and the override
Confirm using the OK key. is valid until the next step of the program. Technical characteristics
• P1 flashes. Confirm using the OK key. During the override period, the current set-point Power supply : 230V 쓒 +10/-15% 50 Hz
The thermostat returns to auto mode. temperature flashes. Power reserve : 4 hours
Temporary override Static differential (On/Off regulation) : < 0.3 °C
Creation of a personalised program P4 In auto mode, this function allows temporary Adjustment range
This program allows you to adjust the heating to modification of the ambient temperature, at any - Comfort temperature : +5 °C to +30 °C
suit your way of life. A 24-hour profile is composed time, whatever the instruction in progress. The - Comfort 2 temperature : +5 °C to +30 °C
of 48 points (representing the set-points). You can range of duration of this function is from 15 minutes - Eco temperature : +5 °C to +30 °C
visualise the composition of your program at the to 12 hours. Ambient temperature display range : 0 °C to +40 °C
bottom of the display. • Press key  , the duration adjusted in PA:1 Operating temperature : +5 °C to +45 °C
1 program step = 30 minutes. flashes. Storage temperature : -25 °C to +70 °C
• Press key  + or - to adjust the desired duration. Ball test temperature : 75°C and 125°C
Confirm using the OK key. Clock operating accuracy : drifts < 1sec/day
• Press key  + or - to adjust the desired Trip values : 250V max. 5A resistive/3A inductive
temperature. Confirm using the OK key. Minimum load excepted by the relay : 12V / 10mA
The end time of the temporary override flashes Relative humidity : 90 % at 20 °C
on the bar chart of the screen and the value of IP : 30
the duration of the temporary override is displayed IK : 04
30 min. 30 min. 30 min. in place of the current time, until the return to Insulation class : II
in Eco in Comfort in Comfort 2 automatic mode. Insulation type : 4 kV
If a temporary override is in progress, it is possible Rigid cable cross-sections : 0,5 to 2.5 mm²
Example : creating a program, P4 for a group of to modify the temperature in steps of 0.5 °C using Flexible cable cross-sections : 0,5 to 1.5 mm²
days (5 weekdays + 2 weekend days). key 0,5 °C  + or -. Minimum pulse voltage : 4 kV
For the 5 weekdays, we would like 3 Comfort One press on key  allows the delay time to be Pollution class : 3
periods from 06:00 to 08:00, from 12:00 to 14:00 modified; the last selected duration is displayed. Action type : 2B
and from 18:00 to 22:00. Insulation type : reinforced insulation
For the two weekend days, we would like a Software structure : class A
Accessories Dimensions (l x h x d) : 97 x 138 x 30
Comfort period from 08:00 to 19:00, then a Telephonic remote control
Comfort 2 period from 19:30 to 22:00. Standards : NF EN 60730-1, NF EN 60730-2-1,
The thermostat is equipped with an input for
• Press key  menu to place the cursor telephonic commands for your heating.
NF EN 60730-2-7, NF EN 60730-2-9,
under prog. The indicators for the seven days of NF EN 60730-2-11
The symbol is displayed if the Frost protection EN 12098-2, EN 12098-5
the week flash. mode is requested telephonically. Detection of
• Press key  + to select to affect the group of telephonic remote commands is taken into account
five days (the group of five days flashes). Confirm in less than 1 minute. You can modify the Frost
using the OK key. protection temperature using the Holiday menu.
• P1 flashes. Press key  + to select P4
(P4 flashes). Confirm using the OK key. The temperature applied will be the last value
• Press key  until 6:00 appears and then key confirmed in Holiday mode. In Air conditioning
 until 8:00 appears. Then press key  mode, during telephonic forcing the regulation is
until 12:00 and key  until 14:00. Then press stopped.
key  until 18:00 appears and finally key 
until 22:00.
If you make an error, press key  - to move back-
wards or key  + to advance and correct your
programming.
• Confirm using the OK key.
• The group of 2 weekend days flashes. Confirm
using the OK key.
• P1 flashes. Press key  + to select P4
(P4 flashes). Confirm using the OK key.
• Press key  until 8:00 appears and
key  until 19:30 appears. Then press key 
until 22:00 and press key  until 24:00.
Confirm using the OK key.
Correct Disposal
Note : Remote temperature probe
The latest P4 program is held in memory and auto- of This product
The thermostat is equipped with an input for
matically offered to be assigned to a new day or connection of a remote temperature probe (Waste Electrical
group of days (whose P4 is empty). (reference : 25190). Once this is connected, the & Electronic Equipment).
Setting anticipation to 1 sends program thermostat detects it automatically. The ambient
P4 => P4A. temperature display flashes for 10 seconds.
The thermostat then regulates the temperature (Applicable in the European Union and
in response to the remote probe. other European countries with separate
collection systems).
What to do if... ? This marking shown on the product or its
The symbol is displayed: literature indicates that it should not be dis-
the thermostat is locked in Frost protection mode posed with other household wasted at the
by telephonic remote control. end of its working life. To prevent possible
Unlock the function by a telephone call or using harm to the environment or human health
the remote control. from uncontrolled waste disposal, please
The heating does not start up, even though the separate this from other types of wastes
ambient temperature is less than the set point : and recycle it responsibly to promote the
function of the evolution of the ambient sustainable reuse of material resources.
OCOM 114409

temperature over the last few hours. Household users should contact either
The thermostat estimates that the temperature will the retailer where they purchased this pro-
be obtained without contributing additional energy. duct, or their local government office, for
If the anticipation function (1H, 2H or 3H) ) in the It does not request ignition of the generator.
Installer parameters PA:9 has been confirmed, P4A is details of where and how they can take this
Ask your installer for confirmation. item for environmentally safe recycling.
displayed in place of P4. The heating starts up even though the ambient
during programming, proceed in the same way as temperature is greater than the set point Business users should contact their sup-
for p4 knowing that the thermostat will automati-
Hager 06.2012

temperature: plier and check the terms and conditions of


cally apply the anticipation with the duration set in Your installer has selected a form of regulation the purchase contract. This product should
pa:9. it is not useful to foresee this anticipation time known as PID which anticipates a drop in the not be mixed with other commercial wastes
during your programming. ambient temperature as a function of its evolution of disposal.
over the last few hours.

4 6T 7786-02B