Industrial Controls Catalog
Industrial Controls Catalog
Catalog Edition
,&ϷϮ ϶Ϯ϶ϵ
SIRIUS
Industrial Controls
siemens.com/sirius
© Siemens 2023
Verwandte Kataloge
Related catalogs Miscellaneous
SIMATIC ST 70 Contact
Products for Your personal contact can be found in our
Totally Integrated Automation Contacts Database at:
SITOP KT 10.1
SITOP Expert technical support
Power Supply for Industrial controls:
PDF (E86060-D4001-A510-E0)
Support Request:
SITRAIN www.siemens.com/support-request
Digital Industry Academy
www.siemens.com/sitrain
© Siemens 2023
Industrial Controls
SIRIUS 1 Introduction
2 Industrial communication
3 Switching devices –
Contactors and contactor assemblies –
for switching motors
4 Switching devices –
Contactors and contactor assemblies –
Special applications
5 Switching devices –
Contactors and contactor assemblies –
Contactor relays and relays
Catalog IC 10 · 2023 6 Switching devices –
Soft starters and solid-state switching
Supersedes: devices
Catalog IC 10 · 01/2022
7 Protection equipment
11 Safety technology
The catalog PDF contains click-on article numbers, graphics 12 Position and safety switches
and videos.
Ordering notes
Catalog IC 10 contains all selection
and order-relevant data.
2 Siemens IC 10 · 2023
© Siemens 2023
SIRIUS in the
World Wide Web
The most important online services
at a glance.
Siemens IC 10 · 2023 3
© Siemens 2023
SIRIUS 3RW
soft starters
As diverse as your tasks
The strong, harmonized portfolio of soft starters is suited
to a wide range of standard – and also Failsafe and
ATEX – applications thanks to comprehensive and specific
functions.
Benefit from intelligent functions such as condition monitoring,
automatic parameterization, pump cleaning and integrated
braking functions, regardless of the industry you are in.
Strong portfolio
Comprehensive, coordinated soft starter portfolio for simple to
demanding starting: Basic, General, High Performance
Efficient switching
Energy-efficient switching and mechanical protection of the
drive train thanks to soft starter with hybrid switching technology
Intelligent use
Concentrated, application-specific functionality thanks to
intelligent features such as automatic parameterization,
pump cleaning and condition monitoring
4 Siemens IC 10 · 2023
© Siemens 2023
SIRIUS 3RW
Strong, comprehensive
portfolio with a wide
range of possibilities
thanks to a flexible
design.
Digitalization
The 3RW soft starters
help you to realize the
full potential of
digitalization. This is
particularly beneficial
when it comes to
economic efficiency.
IC01_00559
IC01_00555
IC01_00557
IC01_00558
IC01_00556
Siemens IC 10 · 2023 5
© Siemens 2023
SIRIUS
modular system
Efficiently combined.
More information,
see
www.siemens.com/
sirius-modular-
system
Optimally matched Highest performance Ready-made and Comprehensive Configuration data Fulfills all relevant
and dimensioned on the market based tested combinations portfolio for spring- and macros for standards worldwide
products expandable on installation size with short-circuit loaded terminals, integration into your and requirements of
with uniform strength up to function blocks for CAE systems many applications
accessories 150 kA/400 V contactor assemblies even under extreme
for reversing operating conditions
and star-delta (safety applications,
(wye-delta) starting rail and shipbuilding,
as well as connectors etc.)
6 Siemens IC 10 · 2023
© Siemens 2023
For you to get the most out of our portfolio quickly and easily.
For more
information,
The TIA Selection Tool is a scan the QR code
completely paperless solution.
Download it now:
www.siemens.com/tst
Siemens IC 10 · 2023 7
© Siemens 2023
At the push of a button you receive the appropriate switching and protection devices
for your motor, including standard-compliant cable cross-sections and short-circuit
values for fuseless and fused load feeders.
Never before has the dimensioning of your load feeders been so quick and reliable!
1. 2.
Digital expertise on standards Easy dimensioning
IC01_00718
3. 4.
Consistent workflow Supported portfolio
Electrical engineering Intelligent devices for
with unlimited creativity versatile solutions
Highlights
• Automatic short-circuit calculation and cable dimensioning
• Automatic dimensioning of fuseless and fused load feeders up to 250 hp
according to UL 508A or up to 250 kW according to IEC 60204-1
• Selection of the appropriate switching and protection devices for the motor
• Visual planning of the main circuit in the single-line diagram
• Simple accessory selection
• Complete PDF documentation of technical specifications and calculation results
(e.g. for the short-circuit verification)
• Simple main switch dimensioning for IEC and UL infeeds
8 Siemens IC 10 · 2023
© Siemens 2023
For more
information,
tool download
and videos, see
www.siemens.com/
cpd
Are you looking for a clear and easy way to dimension your circuits?
The main circuit view with single-line display and the automatic display of accessories
are two of the many new functions in the TIA Selection Tool.
Siemens IC 10 · 2023 9
© Siemens 2023
Integrated
Control Panels
The easy way to build the
optimum control panel.
We offer practical support in mastering the typical challenges
of control panel engineering through a harmonized product
portfolio, tools and data for digitalization in engineering,
and expert know-how.
10 Siemens IC 10 · 2023
© Siemens 2023
For more
information, see
www.siemens.com/
panelbuilding
With a range of tools and data-based services, we support you with Harmonized product and system portfolio saves construction time.
the digitalization of your business and enable the leverage of all the With our coordinated, integrated portfolio of products
advantages this offers for control panel design: greater efficiency, that includes automation technology, drive train components,
flexibility and quality – in every process phase! industrial controls and matching control panel enclosures, we can
• Intelligent selection, dimensioning and design reduce your engineering overhead and ensure the harmonious
www.siemens.com/controlpanel/cpd interaction of all devices. These are extensively tested, and are all
www.siemens.com/controlpanel/tools certified and available for use worldwide – enabling you to remain
• Control panel engineering flexible within the global business environment.
www.siemens.com/controlpanel/engineering Benefit also from our expert tips concerning control panels.
www.siemens.com/controlpanel/tips
Siemens IC 10 · 2023 11
© Siemens 2023
Product
highlights
SIRIUS 3RW5 soft starters 3RW55 system redundancy S2 SIRIUS 3RQ1 force-guided coupling
can be flexibly deployed in many for PROFINET High-Feature relays, fail-safe up to SIL 3/PL e
applications communications module
Type: 3RW5 Type: 3RW5950-0CH00 Type: 3RQ1
Pages 6/15, 6/39, 6/55 and 6/73 onwards Page 6/10 onwards Page 5/21 onwards
For more
information, see
www.siemens.com/
sirius
12 Siemens IC 10 · 2023
© Siemens 2023
Sustainability@SI
An intelligent infrastructure is
a sustainable infrastructure.
For more
information, see
www.siemens.com/
sustainability-
figures
As a company, Siemens considers environmental, social and governance (ESG) criteria from all angles with its DEGREE
framework (decarbonization, ethics, governance, resource efficiency, equity and employability). We are not only
committed to reducing the carbon footprint in our own operations to net zero by 2030, but also helping our customers
achieve their decarbonization and sustainability goals. The main areas where Smart Infrastructure contributes to the
DEGREE framework are decarbonization, resource efficiency and employability.
Mission & strategy Technology with aim Our contribution Sustainability facts
and purpose
As a focused technology We develop technologies that Siemens makes an impact every For almost 175 years, Siemens
company, Siemens is committed connect the real and digital day by providing innovative has been driven by the desire
to addressing the world's most worlds and enable our solutions in response to to improve the lives of people
profound challenges by customers to positively challenges relating to around the world with our
leveraging the synergies between transform the industries that environmental protection, technologies.
digitalization and sustainability. form the backbone of our decarbonization, health and
economy: industry, safety. Innovative solutions that
infrastructure, transportation have a clear goal: to make the
and healthcare. world more sustainable,
more integrative and a better
place to live.
Siemens IC 10 · 2023 13
© Siemens 2023
Technical Support
One click – and you have all
the information you need.
Support Request –
the fast track to the experts
www.siemens.com/support-request
Using the Support Request form in Online Support you can
send your query directly to Technical Support.
Conversion tool –
the easy and efficient way to find successor
products
www.siemens.com/conversion-tool
ng
in
nn
technical advice.
Technical ● Competitor conversion
is si o nin g
● Special versions
Infor m
● Commissioning
ati
_00
Co
on
● Maintenance
01
IC
Se
r vi Further input channel for other topics:
ce ion
O p e r at
Support Request: ● Returned goods
14 Siemens IC 10 · 2023
1
© Siemens 2023
Introduction
1
Energy-efficient controls
1/2 SIRIUS brings down energy costs
IE3/IE4 ready
1/8 SIRIUS controls for reliable switching
and protection of highly efficient IE3 and
IE4 motors
Siemens IC 10 · 2023
© Siemens 2023
Introduction
Energy-efficient controls
SIRIUS brings down energy costs
1
■ Overview
Energy management in industry
Whether you are a plant
operator, planner or machine
Third party applications manufacturer: Energy-
Cloud-based, open IoT operating system: efficient production is
MindSphere a challenge and an
Product opportunity in equal
manufacturer's measure.
perspective
1 Product
design
Machine
2 Production
planning
Machine
3 Production
engineering
Machine
4 Production
execution
Machine
5 Service
Machine
Machine concept engineering commis- operation service
IC01_00550
manufacturer's sioning
perspective
Collaboration platform: Teamcenter
Energy-efficient production as a success factor Energy data acquisition represents an important component of
the overall energy data management process here. Through
In order to harness energy potential, with our vast portfolio, transparency right down to the loads, it is possible to identify and
we always maintain a clear view of the overall product utilize potential energy savings.
development and production process. Because maximum
energy efficiency in production can only be achieved through With communication-capable SIRIUS switching devices you can
perfect interaction of all components. acquire energy data from the drive train without any additional
effort.
That is why it is important to first create an awareness for existing
energy-saving potential, recognize (identify) and assess SIRIUS controls help you make energy flows visible.
(evaluate) opportunities for optimization through precise Best drive solutions in terms of energy
analysis. Finally, appropriate measures must be implemented
(realized). In order to design processes for optimal energy efficiency,
it is not enough to simply measure the energy flow and deploy
With our full-range portfolio of energy-efficient drive solutions, energy-efficient products. The greatest lever for saving energy
automation and services, you too will reach maximum energy can be derived from closely examining the application.
efficiency, higher productivity and lasting competitiveness in
your company. SinaSave energy efficiency tool
SIRIUS
up to
60%
energy saving
Introduction
Energy management with SIRIUS
Integration into energy management software
1
■ Overview
SIMATIC Energy Suite SENTRON powermanager
High energy consumption and automated production processes
are typical for many industries.
If you want to keep your energy costs under control in the
long term and you are already focusing on the digital future,
it's a good idea to equip your plant with integrated energy
measuring technology, thus anchoring energy management into
the automation of your production processes – which is where
most energy is consumed.
SIMATIC Energy Suite as an integrated option for the TIA Portal
efficiently links energy management with automation, thus
creating energy transparency in the production system.
The considerably simplified configuration of energy measuring
components from the product families SIMATIC, SENTRON,
SINAMICS, SIRIUS and SIMOCODE significantly reduces the
configuration costs. For details on the currently supported
devices, see www.siemens.com/energysuite-hardware.
SENTRON powermanager
Thanks to the end-to-end connection to SIMATIC Energy The SENTRON powermanager energy monitoring software
Manager PRO (innovative successor to SIMATIC B.Data) or displays important characteristic quantities for individual
cloud-based Service Energy Analytics, you can seamlessly devices and the entire system on a clearly organized dashboard
expand the recorded energy data to create a cross-site energy and thus analyzes the energy consumption.
management system.
The advantages at a glance:
This also enables companies to fulfill all economic and energy
management requirements – from purchasing of energy through • Analyzing energy flows: Cost-saving measures can be
planning to energy management. derived directly and faults can be localized rapidly – for
greater awareness regarding energy consumption and
The advantages at a glance: lower costs.
• Simple and intuitive configuration instead of programming • Easy to get started: Can be added to existing hardware and
• Automatic generation of the PLC energy program available infrastructure.
• Convenient integration of measuring components from • Fast savings: Analyzes power curve and detects load peaks.
the Siemens portfolio and from the portfolios of other • High plant availability: Continuous monitoring of power
manufacturers distribution ensures that critical system states are detected
• Integrated in the TIA Portal and automation at an early stage.
• Archiving on WinCC Professional or PLC The SIRIUS 3RW55 soft starter is integrated into SENTRON
• Seamless connection to Energy Manager PRO and powermanager by simple installation of an XML file, see
Energy Analytics https://support.industry.siemens.com/cs/ww/en/view/109798105
For more information on SIMATIC Energy Suite, see For more information on SENTRON powermanager, see
www.siemens.com/energysuite. www.siemens.com/powermanager.
Introduction
Systematic industrial safety technology
SIRIUS Safety Integrated
1
■ Overview
3RK1 3SE29
ASIsafe compact safety
module foot switch
Electronically
configurable 8WD46
signaling column
3RK1
ASIsafe
SlimLine
IC01_00695b
Compact
module
Introduction
Systematic industrial safety technology
SIRIUS Safety Integrated
1
The quick and easy way to safe machinery Your partner for machine and plant safety
In addition to the statutory regulations governing the protection With Safety Integrated, Siemens has provided the smart answer
of people there are also economic reasons for avoiding personal to constantly increasing requirements for the functional safety of
injury and the resulting downtimes, and for protecting both a machine and for its cost-effectiveness and flexibility. Our
machinery and equipment from damage. comprehensive portfolio of safe controls, control technology
and drive technology provides scalable solutions for precisely
Safety Integrated benefits machine manufacturers and plant tailored safety concepts for protecting people, machines
operators in many ways: and the environment. Our products meet the current safety
• Lower costs for hardware, assembly and engineering standards in the industry, including IEC, ISO, NFPA and UL.
• Higher availability thanks to faster diagnostics and fewer As a partner for machine and plant safety, Siemens also
downtimes supports users with examples of functions and up-to-date
At the same time, using modular safety concepts allows them to know-how concerning international standards and directives.
modernize their plants more easily and at lower cost. The Safety Selector (www.siemens.com/safety-selector) thus
guides the user to the appropriate application example based
Smart controls ensure the functional safety of machinery on selection criteria to be assigned.
Our SIRIUS Safety Integrated controls are a central element of The free safety evaluation for evaluating safety functions in
the Siemens Safety Integrated concept, based on Totally accordance with IEC 62061 and ISO 13849-1 is integrated in the
Integrated Automation. TIA Selection Tool, see www.siemens.com/safety-evaluation.
SIRIUS Safety Integrated, see Thus, the selection of components and their safety-related
www.siemens.com/safety-integrated. assessment are implemented in a coherent workflow.
Whether for reliable detecting, evaluating and reacting, our Requirements-based training on CE marking, functional safety,
SIRIUS Safety Integrated controls (page 1/6 onwards) provide risk assessment, and on our Safety Integrated products rounds
cost-effective solutions for the safety of your machine or plant. off our portfolio, see www.siemens.com/sitrain.
Take the SIRIUS 3SK safety relays for example: They are
modularly expandable, and can integrate compact motor
starters such as the fail-safe SIRIUS 3RM1 very simply via the
device connector (parameterization is performed easily with
a screwdriver on the DIP switches or by drag and drop in the
engineering software).
The SIMOCODE pro modular motor management system
combines all required protection, monitoring, safety and control
functions for motor feeders. It can be connected to fail-safe
controllers via PROFIBUS or PROFINET and shut down motors
in emergency situations.
SIRIUS Safety Integrated uses fail-safe communication via
standard fieldbus systems, such as ASIsafe via AS-Interface
and PROFIsafe via PROFIBUS and PROFINET, to solve even
networked safety tasks of greater complexity. This opens the
door to flexible safety solutions for compact machines or large-
scale plants – naturally compliant with current standards up to
SIL 3/PL e.
The first integrated ASIsafe connection to the distributed
I/O system ensures even more consistency. With the
SIMATIC AS-i F-Links, AS-i networks can be connected
quite simply to safety controls via PROFIsafe via the
SIMATIC ET 200SP.
Particular highlights are the 3RT contactors
of sizes S2 to S12 with fail-safe control input, the
SIRIUS ACT 3SU1 EMERGENCY STOP with PROFINET or
PROFIsafe interface, and the fail-safe motor starters for
ET 200SP (page 8/94 onwards) and the 3RW55 fail-safe soft
starters (page 6/39 onwards). With these products, seamless
integration into fail-safe control systems is possible.
The Application Manual SIRIUS Safety Integrated
(SIAM Safety Integrated Application Manual) provides
users with comprehensive application examples for
SIRIUS Safety Integrated products, see
https://support.industry.siemens.com/cs/ww/en/view/81366718.
Introduction
Systematic industrial safety technology
SIRIUS Safety Integrated
1
Flexible thanks to modular design, Fail-safe expansion modules SIRIUS 3RQ1 force-guided coupling
suitable for offshore applications DM-F Local and DM-F PROFIsafe, safe relays, fail-safe up to SIL 3/PL e
shutdown of motors up to SIL 3/PL e
3SE6 non-contact safety switches 12/4 3SK safety relays 11/13 3RW55 Failsafe soft starters 6/39
Magnetically operated switches (IP67) Key modules of a consistent and cost- 3RW55 Failsafe High Performance soft
and RFID safety switches (IP69) effective safety chain. Flexible thanks to starters with STO
input and output expansion units
3SU11 EMERGENCY STOP mushroom 13/26, 3TK2810 safety relays 11/33 SIRIUS 3RM1 motor starters 8/83
pushbuttons, 3SU18 two-hand 13/50,
operation console 13/106
• SIRIUS ACT two-hand operation console Further modules of a consistent and cost- Compact, narrow and fail-safe hybrid
with user-friendly capacitive sensor keys effective safety chain for fail-safe detection motor starters in IP20
• High level of flexibility due of standstill or speed Easy configuration and low outlay for
to direct integration of the storage thanks to wide setting range of
SIRIUS ACT EMERGENCY STOP via the overload release
standardized, fail-safe communication
protocols (PROFIsafe, ASIsafe)
3SE7 cable-operated switches, 13/156, ET 200SP fail-safe motor starters 8/94
3SE29 safety foot switches 13/161
• Foot switches with cover, metal Compact, fail-safe hybrid motor starters
enclosure with degree of protection IP65 for the ET 200SP system
• Cable-operated switches with latching
and positive-opening NC contacts,
in degree of protection IP65 or IP67
Introduction
Systematic industrial safety technology
SIRIUS Safety Integrated
1
Devices with safety functions for AS-Interface
Detecting Evaluating Reacting
Product Page Product Page Product Page
Safety modules/EMERGENCY STOP CM AS-i Master ST, 2/29, ET 200pro Safety motor starters 9/3
mushroom pushbuttons F-CM AS-i Safety ST 2/34 Solution PROFIsafe
for SIMATIC ET 200SP
• K45F and K20F compact safety 2/26
modules for use in the field
• SC17.5F SlimLine Compact safety 2/26 Evaluation and processing of signals via Communication-capable motor starters
modules for use in the control cabinet a fail-safe SIMATIC or SINUMERIK with high degree of protection IP65
control. Special safety modules enable the
Simple combination of the highest safety levels
CM AS-i Master ST and
F-CM AS-i Safety ST modules in one
ET 200SP station results in a powerful, 3RT contactors from 18.5 kW
safety-oriented network transition (F-PLC input)
between PROFINET (or PROFIBUS)
and AS-Interface.
Introduction
IE3/IE4 ready
SIRIUS controls for reliable switching and protection of highly efficient IE3 and IE4 motors
1
■ Overview
SIRIUS controls
P E
IC01_00482d
No false tripping Reliable switching capacity
but are characterized by
higher currents during startup process for use with IE3 and IE4 motors Are you IE3/IE4 ready?
during starting
Introduction
Innovative technology for saving energy
Electronic starting with hybrid switching technology
1
■ Overview
SIRIUS 3RV29 infeed system with 3RA2 load feeder and 3RM1 motor starter
Compact
Simple
Only 22.5 mm wide,
Minimum wiring in the main and regardless of whether
control circuits thanks to direct-on-line or reversing
assembly option starter function
IC01_00526
Economical
Thanks to low device variance due
to wide setting range
Long service life
Hybrid switching technology
uses benefits of relay and
semiconductor technology
Safety
Safe switching possible with F-CPU
or SIRIUS 3SK safety relays
The hybrid switching technology uses low-wear semiconductor Further energy savings are provided by the integrated electronic
technology for switching the motor on and off, and in the overload protection.
operating phase it relies on energy-saving relay technology.
This causes a lower intrinsic power loss than comparable motor
This ensures durability, especially with high switching frequency, feeders with thermal overload protection.
and thus significantly reduces maintenance costs and extends
the life of the motor starters. In this way, you benefit from reduced heat generation and
therefore lower cooling power. And that saves energy.
In addition, due to the hybrid switching technology, motor
starters have lower electromagnetic interference emissions,
enabling you to increase your plant availability.
SIRIUS soft starters 3RW30, 3RW40, 3RW50,3RW52, 3RW55 and 3RW55 Failsafe
Safe
SIL 1/STO without additional
safety relay or contactor
Long service life
Reduced mechanical and
electrical load
IC01_00528d
Energy saving
Reduced temperature rise in the
control cabinet thanks to
bypass contacts
Simple
Fast and easy commissioning
Introduction
Innovative technology for saving energy
Electronic starting with hybrid switching technology
1
Highlights
Use of hybrid switching technology for:
• SIRIUS 3RM1 motor starters
• ET 200SP motor starters
• SIRIUS soft starters
Failsafe functionality for SIRIUS 3RW55 soft starters,
SIRIUS 3RM1 motor starters and ET 200SP:
• Maximum safety:
Safety function up to SIL 3/PL e
Additional benefits for SIRIUS 3RM1 motor starters:
Easy to wire • Using device connectors safety-related group shutdown
Thanks to push-in technology with reduced wiring is possible
Option handling • Direct connection to the 3SK safety relay, without
additional wiring
IC01_00527
Increased flexibility and
efficient savings through
single configuration of complex
automation projects
IC01_00529
Power bus
Supply with power only once, then automatic setup with side-by-side
mounting of multiple modules
Quick stop and end position disconnection
Load switch off even at high Switch on Operation Switch off
speed – independent of central controller
Quick installation Service life
Hook in, slide into place and engage
Plant availability
Once it is installed and wired, you simply connect the Energy saving
ET200SP motor starter to the controller in the
TIA Portal ready for parameterization.
Industrial communication
2
Introduction 2/45 - Digital I/O modules, IP67 - K60
2/3 AS-Interface 2/47 - Digital I/O modules, IP68/IP69 - K60R
2/13 IO-Link 2/50 - Digital I/O modules, IP67 - K45
2/52 - Digital I/O modules, IP67 - K20
AS-Interface
2/54 - Analog I/O modules, IP67 - K60
Introduction
I/O modules for use in the control
2/19 Communications overview cabinet
2/21 System components 2/57 - Introduction
AS-Interface specification 2/58 - SlimLine Compact
2/22 - Specification V3.0 2/62 - F90 module
2/23 - AS-i Power24V 2/63 - Flat module
ASIsafe Modules with special functions
2/24 Introduction 2/64 - Counter modules
2/25 AS-i safety solution with F-CPU and 2/65 - Ground-fault detection modules
AS-i in ET 200SP 2/66 - Overvoltage protection modules
2/34 F-CM AS-i Safety ST for Contactors and contactor assemblies
SIMATIC ET 200SP 3/18 - SIRIUS 3RT contactors, 3-pole up to
2/26 AS-Interface safety modules 250 kW
12/93 SIRIUS 3SF1 mechanical safety 3/142 - SIRIUS 3RA23 reversing contactor
switches for AS-Interface assemblies, up to 55 kW
SIRIUS ACT pushbuttons and indicator 3/158 - SIRIUS 3RA24 contactor assemblies
lights for star-delta (wye-delta) starting, up to
90 kW
13/88 - Modules: AS-Interface modules for
mounting on the front plate or in the 3/101 - SIRIUS 3RA27 function modules
enclosure Motor starters for use in the control
13/100 - Pushbuttons and indicator lights in the cabinet
enclosure for AS-Interface 8/57 - SIRIUS 3RA6 compact starters:
Masters 3RA61 direct-on-line starters,
3RA62 reversing starters
Masters for SIMATIC ET 200
9/21 Motor starters for use in the field,
2/29 - CM AS-i Master ST for
high degree of protection
SIMATIC ET 200SP
- SIRIUS M200D motor starters for
2/34 - F-CM AS-i Safety ST for
AS-Interface
SIMATIC ET 200SP
D 31.21) SINAMICS G115D distributed converters
Masters for SIMATIC S7
2/37 - CM 1243-2 SIRIUS ACT pushbuttons and indicator
2/39 - CP 343-2P/CP 343-2 lights
13/88 - Modules: AS-Interface modules for
Routers
mounting on the front plate or in the
2/41 DP/AS-Interface Link 20E enclosure
13/100 - Pushbuttons and indicator lights in the
enclosure for AS-Interface
13/170 SIRIUS 8WD42 and 8WD44 signaling
columns
1) See Catalog D 31.2.
Siemens IC 10 · 2023
2
© Siemens 2023
Industrial communication
Siemens IC 10 · 2023
© Siemens 2023
Industrial communication
Introduction
AS-Interface
■ Overview
More information
Homepage, see www.siemens.com/as-interface TIA Selection Tool Cloud (TST Cloud), see
2
Industry Mall, see www.siemens.com/product?as-interface www.siemens.com/tstcloud/?node=AsInterface
System Manual for AS-Interface, see
https://support.industry.siemens.com/cs/ww/en/view/26250840
Industrial communication
Introduction
AS-Interface
SC17.5F
SIRIUS 3SF1 mechanical safety switches for AS-Interface 3SF1 From 12/93
• Plastic with degree of protection IP65 and metal with degree of protection IP66/IP67
• ASIsafe electronics integrated into the enclosure
• Available with separate actuator, with or without tumbler
Your advantage: Conventional wiring of safety functions no longer required.
Safety switch
SIRIUS ACT EMERGENCY STOP mushroom pushbuttons for AS-Interface 3SU14 modules 13/88
• Degree of protection IP66/IP67/IP69 (IP69K) 3SU18 enclosure From 13/100
• Metal or plastic version
• Connection of an EMERGENCY STOP command device according to ISO 13850 to
AS-Interface
EMERGENCY STOP • Safety-related AS-Interface module is snapped onto the command device from behind
mushroom pushbutton • Can be used up to SIL 3/PL e
in enclosure
Your advantage: Easy direct connection of control elements to ASIsafe.
Industrial communication
Introduction
AS-Interface
2
but also parameter setting, monitoring and diagnostics functions.
Masters for SIMATIC ET 200
CM AS-i Master ST for SIMATIC ET 200SP 3RK7 From 2/29
• Connection of up to 62 AS-Interface slaves per master
• Connection of up to 496 inputs and 496 outputs per AS-Interface network
• Integrated analog value transmission
• Simple configuration by adopting the ACTUAL configuration on the AS-Interface network
• Easy operation in the input/output address range of the SIMATIC (or other controller)
comparable to standard I/O modules
• Monitoring of the control supply voltage on the AS-Interface shaped cable
CM AS-i Master ST for • Integrated ground-fault monitoring
SIMATIC ET 200SP Your advantage: Easy connection of AS-i networks to distributed I/Os.
Industrial communication
Introduction
AS-Interface
The slaves then exchange their data in cyclic mode with a control module (master).
I/O modules for use in the field, high degree of protection
Digital I/O modules, IP67 - K60, K60R, K45 and K20 3RK1, 3RK2 From 2/44
• Degree of protection IP65/IP67 or IP68/IP69 (IP69K)
• Modules available with up to degree of protection IP68/IP69 (IP69K)
• Connection sockets in M8/M12
• Up to eight inputs and four outputs
• A/B technology available
K20 digital module • Contacting protected against polarity reversal
• DIN-rail mounting and wall mounting possible
• Mounting of the module on the base plate using just one screw
• Diagnostics LEDs
Your advantage: Reduction of mounting and startup times by up to 40%.
K45 digital module
Industrial communication
Introduction
AS-Interface
2
• No M12 plugs required for connection
• Especially narrow design for SlimLine Compact modules with widths of 17.5 mm
and 22.5 mm
• Analog modules are also available
• Removable, finger-safe terminal blocks that cannot be inadvertently interchanged when
using the SlimLine Compact modules
• Flat design of the flat modules for small control cabinets and confined conditions
SlimLine SlimLine
Compact Compact • Connection with screw terminals or spring-loaded terminals
SC17.5 SC22.5 • DIN-rail mounting and wall mounting possible
• Diagnostics LEDs
Your advantage: Modules enable space-saving use in control cabinets and small local
control boxes.
F90 module
Flat module
Modules with special functions
Counter modules 3RK1 2/64
• Degree of protection IP20
• For evaluation of pulses
• Connection with screw terminals or spring-loaded terminals
Your advantage: Evaluation of pulses which exceed even the clock frequency of AS-Interface.
Counter module
Ground-fault detection modules 3RK1 2/65
• Degree of protection IP20
• Display using LEDs
• Two signaling outputs
Your advantage: Automatic diagnostics of ground faults on AS-Interface.
Ground-fault detection
module
Overvoltage protection modules 3RK1 2/66
• Degree of protection IP67
• Discharge through ground cable with oil-proof outer sheath
• Protection at transition of lightning protection zones
Your advantage: The AS-Interface overvoltage protection module protects downstream
AS-Interface devices or individual sections in AS-Interface networks from conducted
overvoltages.
Overvoltage protection
module
Industrial communication
Introduction
AS-Interface
SIRIUS contactor
3RT203.-1NB30-0CC0
SIRIUS 3RA27 function modules 3RA2712 From 3/101
• Connection of 3RT20 power contactors with communication capability, 3RA23 reversing
contactor assemblies, and 3RA24 contactor assemblies for star-delta (wye-delta) starting
to AS-Interface
• Reduction of control current wiring through plug-in design and integrated monitoring of
circuit breaker/motor starter protector and contactor
SIRIUS 3RA2712
• Reduced space requirement in the control cabinet through fewer digital inputs and outputs
function module
in the control system
• Easy configuration through operation of feeders instead of individual contactors
• Enhanced operational reliability and quick wiring thanks to spring-loaded terminals
• Small number of variants through use of identical modules for size S00 to S3 contactors
Your advantage: Shortening of mounting and startup times.
Motor starters for use in the control cabinet
SIRIUS 3RA6 compact starters 3RA6 From 8/57
3RA61 direct-on-line starters, 3RA62 reversing starters 3RA61, 3RA62 From 8/65
• Degree of protection IP20
• Very compact load feeders with the integrated functionality of an electronic overload relay
• As direct-on line or reversing starters for motors up to 15 kW/400 V
• Easy expansion into a communication-capable load feeder using AS-i add-on modules
• On-site safe disconnection also possible using AS-i add-on modules
3RA61 compact starter • Standardized integration of the loads in higher-level control systems using AS-i
Your advantage: Compact solution with minimum wiring outlay for actuating direct-on-line
and reversing starters in the control cabinet.
Motor starters for use in the field, high degree of protection
SIRIUS M200D motor starters for AS-Interface 3RK1 From 9/21
• High degree of protection IP65 for cabinet-free design
• As direct-on line or reversing starters for motors up to 5.5 kW/400 V
• Mechanical or electronic switching for high switching frequencies
• Optional with manual operation and brake actuation
SIRIUS • Expanded diagnostics and parameterization possible through AS-Interface
M200D
motor starter • Easy and consistent integration in STEP 7 through AS-Interface
Your advantage: The correct solution for all simple applications in conveyor systems with
spatially distributed drives.
Industrial communication
Introduction
AS-Interface
2
wall-mounted:
• Wide power range from 0.37 to 7.5 kW (SINAMICS G115D motor-mounted up to 4 kW) 6SL352;
• Preconfigured with SIMOGEAR 2KJ8 SINAMICS
• Local commissioning via DIP switch, USB interface and potentiometer or G115D
SINAMICS G120 Smart Access motor-mounted:
SINAMICS G115D 2KJ8
frequency converters, • Integrated safety functions (STO via F-DI or via PROFIsafe)
wall-mounted • Integrated applications for conveyor systems, e.g. for roller conveyor, rotary table,
transfer carriage
• Expanded diagnostics and parameterization through AS-Interface
• Flexible connection method for cables, choice of screw connection or push-in,
compatible with SINAMICS G110D/G110M/G120D
• Optional maintenance switch (SINAMICS G115D wall-mounted)
• Optional manual local operation (SINAMICS G115D wall-mounted)
Your advantage: The simple solution for consistent implementation of distributed plant
concepts with requirements for wall-mounted and motor-mounted variable-speed drives
SINAMICS G115D with Safety functionality.
frequency converters,
motor-mounted
Commanding and signaling devices
SIRIUS ACT pushbuttons and indicator lights for AS-Interface 3SU14 modules 13/88
• AS-Interface modules for snap-on mounting on front plate 3SU18 enclosure From 13/101
• AS-Interface modules for base mounting for mounting in enclosure
• Modular enclosure configuration based on individual specifications
• Enclosures with standard fittings
• Up to six command points for standard signals or EMERGENCY STOP
• Degree of protection IP66/IP67/IP69 (IP69K)
AS-Interface module
• Metal or plastic version
• Indicator lights with integrated LED
• Any change of equipment possible even after installation
Your advantage: Complete operating system with simple AS-Interface integration for
your plant.
AS-i enclosure
SIRIUS 8WD42 and 8WD44 signaling columns 8WD42, 8WD44 From 13/170
• Many optical and acoustic elements can be combined
• Up to four signaling elements can be connected using an AS-Interface adapter element
• With integrated LEDs or with BA15d base for LEDs/incandescent lamps
• For fastening to connection elements (screw or spring-loaded terminals)
• 24 V DC, diameters 50 mm (8WD42) and 70 mm (8WD44)
• Connection with bayonet mechanism
8WD42, AS-Interface Your advantage: Signaling columns for monitoring production sequences and for visual or
8WD44 adapter acoustic warnings in emergency situations, with easy AS-Interface integration.
signaling element
columns
Industrial communication
Introduction
AS-Interface
component of the AS-Interface network and enable the simultaneous transmission of data
and energy on one cable.
In conjunction with data decoupling modules, AS-Interface can also be operated with
standard power supply units.
AS-Interface power supply units 3RX9 2/67
• With wide performance spectrum from 2.6 to 8 A
• Degree of protection IP20
• Separation of data and energy by means of the integrated data decoupling
• UL/CSA approval for global use,
2.6 A version with output power restricted to max. 100 W
(for Class 2 circuits in accordance with NEC)
• Certified for global use
IP20, 3 A
• Integrated ground-fault and overload detection save the need for additional components
and make applications reliable
• Diagnostics memory, remote signaling and Remote RESET allow fast detection of faults
in the system
• Ultra-wide input range permits 1-phase and 2-phase use (8 A version).
Your advantage: Optimum performance for each application.
IP20, 8 A
30 V power supply units
Standard 30 V power supply units without data decoupling 3RX9 From 2/69
• Power spectrum 3 A, 4 A and 8 A
• Overload and short-circuit-proof in every performance class
• Diagnostics: With output voltage > 26.5 V DC
LED and signaling contact for output voltage 30 V O.K.
• Primary-side connection to 120/230 V AC (1-phase) with automatic range selection
PSN130S Your advantage: Economical alternatives in conjunction with data decoupling modules while
30 V DC, 8 A making full use of the maximum AS-Interface cable length.
24 V power supply units
Standard 24 V power supply units (SITOP), without data decoupling 6EP 15/1 or
• Power spectrum 2.5 to 40 A Catalog KT 10.1
• Overload and short-circuit-proof in every performance class
• Add-on modules for signaling, redundancy, buffering and UPS
• 1-, 2- and 3-phase versions
Your advantage: Economical alternatives in conjunction with data decoupling modules.
SITOP PSU100M,
24 V DC, 20 A
S22.5 data decoupling modules 3RK1 From 2/71
• Degree of protection IP20, narrow design 22.5 mm
• Supply of several AS-i networks with a single power supply unit
• Single and double data decoupling
• Operation with 24 V DC or 30 V DC
Your advantage: Cost-effective installation of AS-i networks in conjunction with standard
power supply units.
S22.5 data decoupling
module
DCM 1271 data decoupling module for SIMATIC S7-1200 3RK7 From 2/73
• Simple data decoupling in IP20 design
• Supply of several AS-i networks with a single power supply unit
• Operation with 24 V DC or 30 V DC
Your advantage: Cost-effective installation of AS-i networks in conjunction with standard
power supply units in the design of a SIMATIC S7-1200 module.
Industrial communication
Introduction
AS-Interface
2
Repeaters and extension plugs 6GK1 repeater 2/77
• Repeaters for extending the AS-Interface cable by 100 m per repeater 3RK1 extension
• Extension plug for extending the AS-Interface segment to max. 200 m plug 2/79
• Parallel connection of several repeaters possible (star configuration option)
• Maximum size increases (when combined) to more than 600 m
• Easy mounting
Repeater
• IP67 module enclosure
Your advantage: Lower infrastructure costs, more possibilities of use and greater freedom
for plant planning.
Industrial communication
Introduction
AS-Interface
Diagnostics blocks
• For CM AS-i Master ST and F-CM AS-i Safety ST in ET 200SP, see
https://support.industry.siemens.com/cs/ww/en/view/109479103
• For other Siemens AS-i master and links, see
Diagnostics for https://support.industry.siemens.com/cs/ww/en/view/50897766
AS-Interface via
HMI panels Your advantage: Detailed diagnostics display for fast fault analysis and short downtimes –
for easy integration into STEP 7 projects.
Software
AS-Interface block library for SIMATIC PCS 7 3ZS1635 From 14/19
• Engineering and runtime software
• Easy connection of AS-Interface to PCS 7
• Engineering work reduced to positioning and connecting the blocks in the CFC
• No additional configuring steps required for connection to the PCS 7 Maintenance Station,
diagnostics for the AS-i system optimally guaranteed
AS-Interface block library
for PCS 7 Your advantage: Easy connection of AS-Interface to PCS 7, little engineering and
configuration.
Industrial communication
Introduction
IO-Link
■ Overview
More information
Homepage, see www.siemens.com/io-link For brochure, see
2
TIA Selection Tool Cloud (TST Cloud), see https://assets.new.siemens.com/siemens/assets/api/uuid:ad500ab0-de89-
www.siemens.com/tstcloud/?node=IoLink 4933-8d76-78728f45720d/dffa-b10447-01broschuereiolinkde-144.pdf
For important topics at a glance, see
https://support.industry.siemens.com/cs/ww/en/view/109737170
IO-Link
engineering: Visualization:
SIMATIC SIMATIC HMI
S7-PCT WinCC
S7-300/ S7-1200/
S7-400 S7-1500
controller controller
PROFINET
ET 200SP SIMATIC
with IO-Link master ET 200eco PN
IO-Link
with IO-Link
master
3SU1 ID key-
operated switch
IK10_30141h
RF200 RF200 Standard
8WD44/8WD46 RFID system RFID system sensors
signaling column Actuators
Industrial communication
Introduction
IO-Link
CM 8xIO-Link
for SIMATIC S7-1500
IO-Link master module for SIMATIC S7-1200
SM 1278 4xIO-Link master 6ES7 2/98
• IO-Link master as serial communications module with four ports (channels) according to
IO-Link specification V1.1
• Easy device exchange with automatic data recovery without engineering for IO-Link device
• Up to four IO-Link devices (three-wire connections) can be connected to each IO-Link
master module
• Data transmission rates COM1 (4.8 kBd), COM2 (38.4 kBd), COM3 (230.4 kBd),
automatic adjustment to the data transmission rate supported by the device
Your advantage: Easy connection of IO-Link connections to the SIMATIC S7-1200.
SM 1278 4xIO-Link
for SIMATIC S7-1200
IO-Link master modules for ET 200SP
CM 4xIO-Link V1.1 Standard 6ES7 2/99
• IO-Link master as serial communications module with four ports (channels) according to
IO-Link specification V1.1
• Module replacement with automatic data recovery without engineering for IO-Link master
and device
• Up to four IO-Link devices (three-wire connections) can be connected to each IO-Link
master module.
• Data transmission rates COM1 (4.8 kBd), COM2 (38.4 kBd), COM3 (230.4 kBd),
automatic adjustment to the data transmission rate supported by the device
CM 4xIO-Link Your advantage: Easy connection of IO-Link connections to distributed I/Os.
for ET 200SP
IO-Link master module for ET 200pro
4 IO-LINK HF 6ES7 2/100
• IO-Link master as serial communications module with four ports (channels) according to
IO-Link specification V1.1
• Easy device exchange with automatic data recovery without engineering for IO-Link device
• Up to four IO-Link devices can be connected to each IO-Link master module
• Support of IO-Link Port Class B
• Data transmission rates COM1 (4.8 kBd), COM2 (38.4 kBd), COM3 (230.4 kBd),
automatic adjustment to the data transmission rate supported by the device
Your advantage: Easy connection of sensors and actuators to the I/Os directly in the
IO-Link master module machine's field area.
for ET 200pro
IO-Link master module for ET 200eco PN
IO-Link master 6ES7 2/101
• 4 IO-L + 8 DI + 4 DO 24 V DC/1.3 A
- Up to four IO-Link devices (IO-Link Port Class A) can be connected
- Up to eight standard sensors and up to four standard actuators can be additionally
connected
- Enclosure width 60 mm
• 4 IO-L
- Up to four IO-Link devices (IO-Link Port Class B) can be connected
- Enclosure width 30 mm
6ES7148-6J.00-0.B0 • 8 IO-L + 4 DI 24 V DC
- Up to eight IO-Link devices (4 x Port Class A + 4 x Port Class B) can be connected
- Additionally four digital inputs
- Enclosure width 45 mm
Your advantage: Easy connection of sensors and actuators to the I/Os directly in the
machine's field area.
IO-Link master module for ET 200AL
CM IO-Link 6ES7 2/102
• IO-Link master as serial communications module with four ports (channels) according to
IO-Link specification V1.1
• Easy device exchange with automatic data recovery without engineering for IO-Link device
• Up to four IO-Link devices can be connected to each IO-Link master module
• Support of IO-Link Port Class B
• Data transmission rates COM1 (4.8 kBd), COM2 (38.4 kBd), COM3 (230.4 kBd),
automatic adjustment to the data transmission rate supported by the device
Your advantage: Easy connection of sensors and actuators to the I/Os directly in the
CM IO-Link machine's field area.
for ET 200AL
Industrial communication
Introduction
IO-Link
2
- DI 8 x 24 V DC, 8 x M8
- DI 16 x 24 V DC, 8 x M12
• IO-Link, digital output modules
- DQ 8 x 24 V DC/2 A, 8 x M12
• IO-Link, digital input/output modules
- DIQ 4+DQ 4 x 24 V DC/0.5 A, 8 x M8
- DIQ 16 x 24 V DC/0.5 A, 8 x M12
SIRIUS contactor
3RT201.-1B...-0CC0
SIRIUS 3RA27 function modules 3RA2711 From 3/101
• Connection of 3RT20 power contactors with communication capability, 3RA23 reversing
contactor assemblies, and 3RA24 contactor assemblies for star-delta (wye-delta) starting
to IO-Link
• Reduction of control current wiring through plug-in technology, feeder groups and
integrated monitoring of circuit breaker/motor starter protector and contactor
SIRIUS 3RA2711
• Reduced space requirement in the control cabinet through fewer digital inputs and outputs
function module for
in the control system
IO-Link
• Simple user program through operation of feeders instead of individual contactors
• Enhanced operational reliability and quick wiring thanks to spring-loaded terminals
• Can be flexibly combined with many automation solutions using the open, standardized
IO-Link wiring system
• Small number of variants through use of identical modules for size S00 to S3 contactors
Your advantage: Shortening of mounting and startup times
Overload relays
SIRIUS 3RB24 electronic overload relays for IO-Link for high-feature applications 3RB24 From 7/127
• Diagnostics and current value transmission via IO-Link
• Current measuring modules (3RB29) for current values from 0.3 to 630 A
• In connection with contactors: Controlling direct-on-line, reversing and star-delta
(wye-delta) starters via IO-Link
• Full motor protection through PTC connection
Your advantage: Communication-capable overload relay enables remote diagnostics and
preventive maintenance.
SIRIUS 3RB24
overload relay
Motor starters for use in the control cabinet 3RA6 From 8/57
SIRIUS 3RA64, 3RA65 compact starters for IO-Link 3RA64, 3RA65 From 8/67
• Integrated functionality of a circuit breaker, contactor and electronic overload relay and
various functions of optional mountable accessories
• Can be used for direct starting of standard three-phase motors up to 32 A
(approx. 15 kW/400 V)
• Compact design offers enormous savings in space and wiring in the control cabinet
• Low variance of devices thanks to wide setting ranges for the rated current and wide
voltage ranges
SIRIUS 3RA64 Your advantage: The diagnostics data of the process collected by the 3RA6 compact
compact starter starter, e.g. short circuit, end of service life, limit position, etc., are not only indicated on the
compact starter itself but also transmitted to the higher-level control system through IO-Link.
Industrial communication
Introduction
IO-Link
Industrial communication
Introduction
IO-Link
2
Signaling columns for IO-Link, with or without audible signal
• Configuration of signaling column via IO-Link interface (IODD)
• Fast connection of signaling columns to application using 4-pole M12 plugs
• Via the IO-Link interface, the pattern, color and brightness of the individual segments
(9 to 15 segments) can be set.
• The audible signal can also be set (volume, type of sound up to 105 dB).
Your advantage: Signaling columns for monitoring production sequences and for visual or
acoustic warnings in emergency situations, with easy IO-Link connection.
Industrial communication
Introduction
IO-Link
RECORD_IOL_
DATA
Function block
IO-Link device
Industrial communication
AS-Interface
Introduction
Communications overview
■ Overview
AS-Interface is an open, international standard according to
IEC 62026-2 for process and field communication. Leading
manufacturers of actuators and sensors all over the world
2
support the AS-Interface. Interested companies are provided
with the electrical and mechanical specifications by the
AS-Interface Association. Video: AS-Interface – Powerful integration in SIMATIC ET 200SP
AS-Interface is a single master system. For automation systems
from Siemens, there are communications processors (CPs),
communications modules (CMs) and routers (links) that control
the process or field communication as masters, and actuators
and sensors that are activated as AS-Interface slaves.
More information
Homepage, see www.siemens.com/as-interface TIA Selection Tool Cloud (TST Cloud), see
Industry Mall, see www.siemens.com/product?as-interface www.siemens.com/tstcloud/?node=AsInterface
OpenVPN
RTU3030C
Firewall
PROFINET
Industrial Ethernet
Access Access
Controller point point
Controller PC/PG IWLAN
Notebook RCoax cable Industrial Ethernet
switches
Controller
Control and PC/PG/IPC
Field device for monitoring system Wireless
intrinsically safe area Remote devices
maintenance
access SCALANCE
Numeric SC646-2C
Coupler control
Link
PROFIBUS PA PROFIBUS
ASM456 Field devices
Mobile Optical
Field devices reading
Mobile HMI
SIMOCODE RF185C systems
HMI
pro IO-Link RFID system Access
RFID Optical master
reading IO-Link point
system DP slave Motion control
IO-Link systems systems
IO-Link
AS-i master I/O module AS-i master
IO-Link DP/AS-i Link 20E in ET 200SP in ET 200SP
I/O module AS-Interface
power supply Protection and
Slave monitoring Client
devices module
SINAMICS
drives RFID Compact
Compact Signaling column Protection and RFID system feeder
feeder monitoring system
G_IK10_XX_20002e
devices
AS-Interface
Compact
feeder Field device
Slave Slave
Slave Slave
AS-Interface
Compact Signaling column power supply
feeder
Industrial communication
AS-Interface
Introduction
Communications overview
■ Benefits
An important characteristic of the AS-Interface technology Elaborately wired control cables in the control cabinet and
is the use of a shared twisted pair for data transmission and marshaling racks can be replaced by AS-Interface.
distribution of auxiliary power to the sensors and actuators.
2
An AS-i power supply unit or alternatively a standard power The AS-Interface cable can be connected to any points thanks
supply unit that meets the requirements of the AS-Interface to a specially developed cable and connection by the insulation
transmission method and has an external AS-i data piercing method.
decoupling module is used for the distribution of auxiliary power. With this concept you become extremely flexible and achieve
The AS-Interface cable used for the wiring is mechanically high savings.
coded and hence protected against polarity reversal and can
be easily contacted by the insulation piercing method.
■ Application
I/O data exchange Command interface
The AS-i master automatically transfers the inputs and outputs In addition to I/O data exchange with binary and analog
between the controller and the digital and analog AS-Interface AS-Interface slaves, the AS-Interface masters can provide
slaves. Slave diagnostics information is forwarded to the control a number of other functions through the command interface.
system when required.
Hence it is possible, for example, for slave addresses to
The latest AS-Interface masters according to the AS-Interface be issued, parameter values transferred or configuration
specification V3.0 support integrated analog value processing. information read out from user programs.
This means that data exchange with analog AS-Interface slaves
is just as easy as with digital slaves. For more information, see
https://support.industry.siemens.com/cs/ww/en/view/51678777.
Industrial communication
AS-Interface
Introduction
System components
■ Overview
To implement communication, the following components of • Network components such as repeaters and extension plugs
a system installation are available: (cannot be used for AS-i Power24V)
2
• AS-i master modules for central control units such as • I/O modules (AS-i slaves) for connection of standard
SIMATIC S7, ET 200M/ET 200SP distributed I/Os, or network sensors/actuators
transitions from PROFIBUS to AS-Interface • Actuators and sensors with integrated AS-i slave
• AS-i power supply unit or alternatively a standard power • Safe I/O modules (ASIsafe slaves) for transmitting
supply unit in combination with an AS-i data decoupling safety-related data through AS-Interface
module for the power supply to the slaves and sensors
• Addressing device for setting slave addresses during
• AS-Interface shaped cables commissioning
SIMATIC/
SIMOTION SINUMERIK
IK10_20027q
PROFINET
Industrial Ethernet
CM AS-i Master ST and CM AS-i Master ST and PROFIBUS DP
F-CM AS-i Safety ST F-CM AS-i Safety ST
for SIMATIC ET 200SP for SIMATIC ET 200SP
S7-300 CP 343-2(P)
AS-Interface S7-300 CP 343-2(P)
power supply
AS-Interface
DP/AS-i Link 20E power supply
S7-1200 with CM 1243-2
S7-1200 with CM 1243-2
AS-Interface AS-Interface
24 V DC 24 V DC
power supply power supply
Industrial communication
AS-Interface
Introduction
AS-Interface specification > Specification V3.0
■ Overview
Scope of AS-Interface specification V3.0
More information
Maximum number Number of digital Number of digital
2
Industrial communication
AS-Interface
Introduction
AS-Interface specification > AS-i Power24V
2
available from Siemens, see • The power supply units must comply with the ES1
https://support.industry.siemens.com/cs/ww/en/view/42806066 (IEC 62368-1) or PELV (Protective Extra Low Voltage)/
For details of AS-i Power24V, see System Manual for AS-Interface, SELV (Safety Extra Low Voltage) standards, have a residual
https://support.industry.siemens.com/cs/ww/en/view/26250840 ripple of < 250 mVpp, and must limit the output voltage to
a maximum of 40 V in the event of a fault. We recommend
SITOP power supplies, see page 15/1 or Catalog KT 10.1,
https://support.industry.siemens.com/cs/ww/en/view/109745655.
• When used in conjunction with standard 24 V power supply
units, each AS-Interface network requires AS-i Power24V-
capable data decoupling, see page 2/71 onwards.
• For reliable operation of an AS-i network with 24 V voltage,
it is important that the masters, slaves and other components
are approved for AS-i Power24V. AS-i Power24V-capable
AS-i components can also be used without restriction in
standard 30 V AS-i networks.
• Use of repeaters or extension plugs in AS-i Power24V
networks is not permitted.
■ Benefits
In small control cabinets the AS-i power supply unit can be
replaced by an AS-i data decoupling module that is connected
to an existing 24 V power supply unit.
AS-Interface data decoupling modules for AS-i Power24V • The advantages of the AS-i communications system in terms
Left: S22.5 data decoupling module,
Right: DCM 1271 data decoupling module for SIMATIC S7-1200 of commissioning, maintenance and diagnostics can be fully
exploited.
Parallel wiring frequently dominates, above all, in applications • If a double data decoupling module is used, two AS-i networks
with very few I/Os. AS-Interface can, however, also replace can be supplied.
extensive parallel wiring in small applications at a favorable price.
AS-i Power24V enables an already existing standard 24 V DC ■ Application
power supply unit to be used for the AS-i network.
Configuration of an AS-i Power24V network
Data and power in the standard AS-Interface network
One of the great advantages of AS-Interface is the ability
to convey not only data, but also the power needed for the PROFINET
connected slaves and sensors over the same unshielded
twisted pair. This is owed to the service-proven AS-Interface S7-1200 with DCM 1271, CM 1243-2
power supply units which provide integrated data decoupling and 24 V standard power supply unit
as well as overload and short-circuit protection and integrated
ground-fault monitoring.
AS-i Power24V
Up to 50 m
Instead of the AS-Interface power supply unit (with 30 V output
voltage and integrated data decoupling) the AS-i cable is
supplied via a data decoupling module from a 24 V standard AS-Interface
power supply unit. The communication technology of
AS-Interface works at the same high level of quality with
NSB0_02245a
Industrial communication
AS-Interface
ASIsafe
Introduction
■ Overview
Higher-level control
More information
As usual, nodes on the AS-Interface bus are controlled in
For more information and typical circuit diagrams on safety engineering, see operation by the standard program of the higher-level
2
https://support.industry.siemens.com/cs/ww/en/view/83150405
SIMATIC (F) CPU or by a SINUMERIK control.
ASIsafe – Safety is included Configuring safety functions
ASIsafe enables the integration of safety-related components In order to implement safe functions, the information from the
such as EMERGENCY STOP pushbuttons, protective door safe and standard nodes must be combined logically and
switches, cable-operated switches or other AS-i safety sensors further parameters set.
in an AS-Interface network. These are fully compatible with the
familiar AS-Interface components (masters, slaves, power In conjunction with the modular safety AS-i master,
supply units, repeaters, etc.) in accordance with IEC 62026-2 which is formed by combining the CM AS-i Master ST and
and are operated in conjunction with them on the yellow F-CM AS-i Safety ST modules in an ET 200SP station, all safety
AS-Interface cable. functions and combinations are configured via STEP 7 and
processed in the controller (F-CPU) by the Failsafe program.
Tested safety
• Protective door switches
• Cable-operated switches
• Other AS-i safety sensors
The transmission method for safety-related signals is released
for applications up to SIL 3 (IEC 62061)/PL e (ISO 13849-1).
■ Benefits
• Simple system structure thanks to standardized AS-Interface • Inclusion of the safety signals in the plant diagnostics,
technology also on existing HMI Panels
• Safety-related and standard data on the same bus • Approved up to SIL 3 (IEC 62061)/PL e (ISO 13849-1)
• Existing systems can be expanded quickly and easily • ASIsafe is certified by TÜV (Germany), NRTL (USA)
• Optimum integration in TIA (Safety Diagnostics) and INRS (France)
and Safety Integrated
■ Application
Integrated safety technology in the AS-Interface system can be
used wherever EMERGENCY STOP buttons, protective door
interlocks, safety switches, light arrays and two-hand operation
are installed.
Industrial communication
AS-Interface
ASIsafe
AS-i safety solution with F-CPU and AS-i in ET 200SP
■ Overview
Operational Safety-oriented
2
control processing
Safe control
e.g. SIMATIC S7-1500F
or SIMATIC S7-300F/S7-400F
PROFINET/PROFIsafe or SINUMERIK 840D sl
IC01_00288f
1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6
Industrial communication
AS-Interface
ASIsafe
AS-Interface safety modules
■ Overview
AS-Interface safety modules
The following modules are available for selection:
2
Industrial communication
AS-Interface
ASIsafe
AS-Interface safety modules
2
K20F compact safety modules
Slave addressing type: Standard address
I/O type Uaux 24 V
2 F-DI -- 3RK1205-0BQ30-0AA3 1 1 unit 42C
3RK1205-0BQ30-0AA3
K45F compact safety modules
Slave addressing type: Standard address
(modules supplied without mounting plate)
I/O type Uaux 24 V
2 F-DI -- 3RK1205-0BQ00-0AA3 1 1 unit 42C
4 F-DI1) -- 3RK1205-0CQ00-0AA3 1 1 unit 42C
3RK1205-0BQ00-0AA3 2 F-DI/2 DQ -- 3RK1405-0BQ20-0AA3 1 1 unit 42C
2 F-DI/2 DQ 3RK1405-1BQ20-0AA3 1 1 unit 42C
SC17.5F SlimLine Compact safety modules
Slave addressing type: Standard address
I/O type Outputs
Screw terminals
Industrial communication
AS-Interface
ASIsafe
AS-Interface safety modules
■ Accessories
More information
For the Equipment Manual for SlimLine Compact modules, see
2
https://support.industry.siemens.com/cs/ww/en/view/109481489
3RK1901-2EA00
Input bridges for K45F
• Black version 3RK1901-1AA00 1 1 unit 42C
3RK1901-1AA00 • Red version 3RK1901-1AA01 1 1 unit 42C
AS-Interface sealing caps M12 3RK1901-1KA00 100 10 units 42C
For free M12 sockets
• Tamper proof 3RK1901-1KA01 100 10 units 42C
3RK1901- 3RK1901-
1KA00 1KA01
Accessories for SlimLine Compact safety modules
Device connectors
For the electrical connection of SlimLine Compact modules
(connects AS-i bus cable and 24 V DC auxiliary power supply
Uaux when using several SlimLine Compact modules)
• Width 17.5 mm 3RK1901-1YA00 1 1 unit 42C
• Width 22.5 mm 3RK1901-1YA10 1 1 unit 42C
Device termination connectors
3RK1901- 3RK1901- Required for the last module in the network
1YA00 1YA01 • Width 17.5 mm 3RK1901-1YA01 1 1 unit 42C
• Width 22.5 mm 3RK1901-1YA11 1 1 unit 42C
Removable terminals Screw terminals
3ZY1450-1BA00
Blank labels
Unit labeling plates1)
• 10 mm x 7 mm, titanium gray 3RT2900-1SB10 100 816 units 41B
IC01_00181
3RT2900-1SB20
Tools for opening spring-loaded terminals Spring-loaded terminals
(push-in)
Screwdriver for SIRIUS devices with spring-loaded terminals 3RA2908-1A 1 1 unit 41B
3.0 mm x 0.5 mm, length approx. 200 mm,
3RA2908-1A titanium gray/black, partially insulated
1)
PC labeling system for individual inscription of unit labeling
plates available from:
murrplastik Systemtechnik GmbH
(see page 16/18).
Industrial communication
AS-Interface
Masters
Masters for SIMATIC ET 200 > CM AS-i Master ST for SIMATIC ET 200SP
■ Overview
AS-i gateways with ET 200SP
An AS-i gateway or AS-i link enables access to the AS-Interface
2
data via PROFINET or PROFIBUS.
With the CM AS-i Master ST module, flexible and powerful
PROFINET/AS-i links or PROFIBUS/AS-i link solutions are set up.
Depending on the requirements, even several AS-i masters can
be plugged into one ET 200SP station, so that the setup can
easily be extended from a single master to double masters or
multiple masters.
The maximum number of modules is determined by the
ET 200SP interface module (IM): Up to 8 AS-i masters with
PROFINET IM 155-6PN Standard, up to 43 AS-i masters with
IM 155-6PN High Feature, or a single AS-i master with
IM 155-6PN Basic. For the connection to PROFIBUS,
the IM 155-6DP HF interface module with up to 7 AS-i master
modules is used.
Since in many plants an ET 200SP station with I/O, motor starter
CM AS-i Master ST for SIMATIC ET 200SP or other peripheral modules is provided, the AS-i master
modules are simply plugged in without any additional effort.
There are countless possible combinations.
An AS-i Safety gateway can also be implemented without
any problems by adding the safety-related module
F-CM AS-i Safety ST in the ET 200SP station. This greatly
simplifies the cabling and connection of distributed
Video: AS-Interface – Powerful integration in SIMATIC ET 200SP
EMERGENCY STOP pushbuttons and protective door
monitoring systems to a Failsafe CPU. The AS-i Safety
More information application is completely configured in TIA Portal/STEP 7.
SIMATIC ET 200SP Manual Collection, see
https://support.industry.siemens.com/cs/ww/en/view/84133942
The ET 200SP modules CM AS-i Master ST and
F-CM AS-i Safety ST (see page 2/34 onwards) can of course
Diagnostics blocks with visualization, see
https://support.industry.siemens.com/cs/ww/en/view/109479103
also be used directly on an ET 200SP CPU or F-CPU, so that an
extremely compact SIMATIC control system with AS-i bus
AS-Interface block library for SIMATIC PCS 7 for easy connection of
AS-Interface to PCS 7, see page 14/19 onwards
connection can be set up.
Released combinations of the AS-i modules for ET 200SP, see For further application possibilities, see the brochure
https://support.industry.siemens.com/cs/ww/en/view/103624653 "The modular AS-i master" at www.siemens.com/as-interface.
The CM AS-i Master ST communications module is designed for More information, see the
use in the SIMATIC ET 200SP distributed I/O system and has the SIMATIC ET 200SP Manual Collection.
following features:
Design
• Connection of up to 62 AS-Interface slaves
The CM AS-i Master ST module has an ET 200SP module
• Supports all AS-Interface master functions according to the
enclosure with a width of 20 mm. A type C0 BaseUnit (BU)
AS-Interface specification V3.0
is required for use in the ET 200SP.
• User-friendly configuration with graphic or tabular display of
the AS-i line in TIA Portal or STEP 7 (Classic) or via GSD in The communications module has LED displays for diagnostics,
other systems operation, AS-i voltage and AS-i slave status and offers
informative front-side module inscription for
• Supply via AS-Interface cable
• Plain-text marking of the module type and function class
• Suitable for AS-i Power24V and for AS-Interface with
30 V voltage • 2D matrix code (article and serial number)
• Integrated ground-fault monitoring for the AS-Interface cable • Circuit diagram
• Through connection to AS-Interface, the number of digital • Color coding module type communications module, light gray
inputs and outputs available for the control system is greatly • Hardware and firmware version
increased (max. 496 DI/496 DQ on the AS-Interface per • Supported BaseUnit type BU: C0
CM AS-i Master ST).
• Integrated analog value processing
Industrial communication
AS-Interface
Masters
Masters for SIMATIC ET 200 > CM AS-i Master ST for SIMATIC ET 200SP
Function Configuration
The CM AS-i Master ST communications module supports all The following software is required for configuration of the
specified functions of the AS-Interface specification V3.0. CM AS-i Master ST module:
The input/output values of the digital AS-i slaves can be • STEP 7 (TIA Portal) or
2
activated via the cyclic process image. The values of the analog • STEP 7 (Classic) or
AS-i slaves are accessible via the cyclic process image or via • the GSD file of the ET 200SP with STEP 7 or another
data record transfer. engineering tool
If required, master calls can be performed with the command STEP 7 enables user-friendly configuration and diagnostics of
interface, e.g. read/write parameters, read/write configuration. the AS-i master and any connected slave modules.
Changeover of the operating mode, automatic application of Alternatively, you can also apply the AS-Interface ACTUAL
the slave configuration and the re-addressing of a connected configuration as the TARGET configuration at the "touch of
AS-i slave can be implemented via the control panel of the a button" via the control panel integrated in the TIA Portal or
CM AS-i Master ST in STEP 7. an optional expansion button. Configuration with the GSD file
For the implementation of modular machine concepts, is possible only with the button.
the AS-i slaves can be activated or deactivated via the PLC The CM AS-i Master ST module occupies up to 288 input
program (option handling). The configuration of AS-i slaves bytes and up to 288 output bytes in the I/O data of the
can be modified while being executed, thus enabling variable ET 200SP station. The I/O assignment depends on the
machine setups and tool changing with integrated input/output configuration in STEP 7.
modules during ongoing operation. AS-i input/output modules
can be added to the system without deactivating the controller. Together with an ET 200SP CPU 1510SP, 1512SP or 1515SP PC,
preprocessing of safe AS-i signals directly in the ET 200SP station
An existing AS-i installation can be read into the STEP 7 and setting up of an independent AS-i station without
hardware configuration and adapted and documented in the a higher-level CPU are possible.
project. Analog values are transmitted via the cyclic process
image, the length of which is adjustable and extendable up to
288 bytes (depending on the interface module (IM) used).
Diagnostics information is accessed via automatic alarm
indications, via the status information in the process image or
via the graphical status display in the online diagnostics of the
TIA Portal. The transmission quality of the AS-i network can also
be read out. To avoid configuration errors, duplicate addresses
can be detected on the AS-i network.
Configuration is possible with SIMATIC CPUs S7-300 up to
S7-1500 and with a SINUMERIK 840D sl or other controller.
The online diagnostic status of the AS-i slaves can be
displayed directly on the slaves in the network view in TIA Portal
(for S7-1500 CPUs with firmware version V 2.0 or higher).
Notes on security:
In order to protect plants, systems, machines and networks
against cyber threats, it is necessary to implement – and
continuously maintain – a holistic, state-of-the-art industrial
security concept. Siemens products and solutions represent Configuration of an AS-Interface network with CM AS-i Master ST via the
TIA Portal
only one component of such a concept.
For more information about the subject of Industrial Security,
see www.siemens.com/industrialsecurity.
Industrial communication
AS-Interface
Masters
Masters for SIMATIC ET 200 > CM AS-i Master ST for SIMATIC ET 200SP
■ Benefits
The CM AS-i Master ST for ET 200SP communications module For diagnostics during ongoing operation, diagnostics blocks
enables modular, simple and high-performance expansion of with clearly arranged visualization on the SIMATIC HMI panel are
AS-interface networks via engineering in the TIA Portal. available or can be downloaded free of charge via a web
2
browser, see
Up to eight CM AS-i Master ST units can be plugged into one https://support.industry.siemens.com/cs/ww/en/view/109479103.
ET 200SP station with IM 155-6PN Standard. When using the
IM 155-6 PN High Feature, the number of CM AS-i Master ST in
the ET 200SP station can be further increased. The maximum
configuration depends on the interface module used. Multiple
masters as well as single masters can thus be implemented in
the ET 200SP depending on the number of modules.
Together with the interface module, a scalable
PROFINET/AS-i link or PROFIBUS/AS-i link can be assembled.
Using STEP 7, the AS-i network is consistently configured and
programmed with only one configuration tool.
The PRONETA PC program (for ET 200SP with PROFINET
interface module) is available for convenient input/output testing
during the commissioning of an AS-i network without a CPU; see
www.siemens.com/proneta.
For the connection of an AS-i network to systems with Ethernet/IP
and Modbus TCP, the ET 200SP MultiFieldbus interface module
IM155-6MF in combination with the CM AS-i Master ST module CM AS-i Master ST diagnostics block
is available.
Industrial communication
AS-Interface
Masters
Masters for SIMATIC ET 200 > CM AS-i Master ST for SIMATIC ET 200SP
■ Application
Configuration examples of AS-Interface networks with CM AS-i Master ST for SIMATIC ET 200SP
2
Controller
e.g. SIMATIC S7-1500
or SIMATIC S7-300
or SINUMERIK 840D sl
PROFINET PROFIBUS
SIMATIC ET 200SP SIMATIC ET 200SP
with 2 x CM AS-i Masters ST with CM AS-i Master ST
AS-Interface AS-Interface AS-Interface
power supply power supply power supply
IC01_00237e
1 2 3 4 5 1 2 3 4 5
3RK7137-6SA00-0BC1
Industrial communication
AS-Interface
Masters
Masters for SIMATIC ET 200 > CM AS-i Master ST for SIMATIC ET 200SP
■ Accessories
Version Spring-loaded PU PS* PG
terminals (UNIT,
SET, M)
2
Article No. Price
per PU
BaseUnit BU20-P6+A2+4D 6ES7193-6BP20-0DC0 1 1 unit 255
• BaseUnit (light), BU type C0
• Suitable for the CM AS-i Master ST module
• For connection of the AS-Interface cable to
the CM AS-i Master ST
• Start of an AS-i network, isolation of the
AS-i voltage from the left-hand module
6ES7193-6BP20-0DC0
6ES7193- 6ES7193-
6AR00-0AA0 6AF00-0AA0
Industrial communication
AS-Interface
Masters
Masters for SIMATIC ET 200 > F-CM AS-i Safety ST for SIMATIC ET 200SP
■ Overview
• Simple module replacement thanks to automatic importing of
the safety parameters from the coding element
2
Industrial communication
AS-Interface
Masters
Masters for SIMATIC ET 200 > F-CM AS-i Safety ST for SIMATIC ET 200SP
Supported BaseUnits The input and output channels are assigned to the process
image automatically and manual linking via configuration blocks
With the combination of the CM AS-i Master ST and is not necessary.
F-CM AS-i Safety ST modules, the CM module is plugged onto
a light type C0 BaseUnit and, immediately to the right of it, If the F-CM AS-i Safety ST module is replaced, all necessary
2
the F-CM module is plugged onto a dark type C1 BaseUnit. settings are automatically imported into the new module.
The AS-i cable is connected only on the light BaseUnit of the
CM module. The F-CM AS-i Safety ST module occupies 16 input bytes and
8 output bytes in the I/O data of the ET 200SP station.
Notes on security:
For diagnostics during ongoing operation, diagnostics blocks
In order to protect plants, systems, machines and networks with clearly arranged visualization on the SIMATIC HMI panel are
against cyber threats, it is necessary to implement – and available or can be downloaded free of charge via a web
continuously maintain – a holistic, state-of-the-art industrial browser, see
security concept. Siemens products and solutions represent https://support.industry.siemens.com/cs/ww/en/view/109479103.
only one component of such a concept.
For more information about the subject of Industrial Security,
see www.siemens.com/industrialsecurity.
Configuration
The following software is required for configuration of the
F-CM AS-i Safety ST module:
• STEP 7 (TIA Portal) and Safety Advanced or
• STEP 7 (Classic) and Distributed Safety or F-Configuration
Pack SP11 or SIMATIC S7 F/FH systems
Configuration and programming are done entirely in the
STEP 7 user interface. No additional configuration software
is needed for commissioning.
Data management – together with all other configuration data of
the SIMATIC – is realized completely in the S7 project.
Diagnostics block for F-CM AS-i Safety ST
■ Application
Thanks to use of the fail-safe module in the ET 200SP, it is The fail-safe output signals can be output via safe
possible to fulfill the safety-related application requirements in SIMATIC output modules or also directly via AS-i output
a manner that is integrated in the overall automation solution. modules. No special functions are required for this in
the program.
The safety functions required for fail-safe operation are
integrated in the modules. Communication with the fail-safe Operation with SINUMERIK 840D sl is possible with
SIMATIC S7 CPUs is realized via PROFIsafe. SINUMERIK software version V4.7 SP2 HF1 or higher.
The safety application is programmed in the SIMATIC S7 F-CPU Together with an ET 200SP station with ET 200SP F-CPU
with Distributed Safety, S7 F/FH Systems or Safety Advanced. 1510SP F, 1512SP F or 1515SP PC F, pre-processing of safe
The fail-safe input signals of the ASIsafe slave modules are read AS-i signals directly in the ET 200SP station is possible, as well
via the AS-i bus line and are combined with any chosen further as the configuration of an autonomous AS-i Safety station
signals in the fail-safe program. without a higher-level CPU.
Industrial communication
AS-Interface
Masters
Masters for SIMATIC ET 200 > F-CM AS-i Safety ST for SIMATIC ET 200SP
Configuration examples of AS-Interface networks with CM AS-i Master ST and F-CM AS-i Safety ST for SIMATIC ET 200SP
Operational Safety-oriented
control processing
2
Safe control
e.g. SIMATIC S7-1500F
or SIMATIC S7-300F/S7-400F
PROFINET/PROFIsafe or SINUMERIK 840D sl
IC01_00288f
1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6
AS-Interface configuration comprising an ET 200SP station with CM AS-i Master ST and F-CM AS-i Safety ST modules
3RK7136-6SC00-0BC1
■ Accessories
Version Spring-loaded PU PS* PG
terminals (UNIT,
SET, M)
Article No. Price
per PU
BaseUnit BU20-P6+A2+4B 6ES7193-6BP20-0BC1 1 1 unit 255
• BaseUnit (dark), BU type C1
• Suitable for the F-CM AS-i Safety ST fail-safe
communications module
• Continuation of an AS-i network, connection with
the AS-i voltage of the left-hand module
6ES7193-6BP20-0BC1
Coding element type H (spare part) 6ES7193-6EH00-1AA0 1 5 units 256
• For the ET 200SP modules F-CM AS-i Safety ST and
CM 4xIO-Link
• Packing unit 5 items
Industrial communication
AS-Interface
Masters
Masters for SIMATIC S7 > CM 1243-2
■ Overview Function
The CM 1243-2 supports all specified functions of the
AS-Interface specification V3.0.
The values of the digital AS-i slaves can be activated via the
2
process image of the S7-1200. During configuration of the
slaves in the TIA Portal, the values of the analog AS-i slaves can
also be accessed directly in the process image.
If required, master calls can be performed with the data record
interface, e.g. read/write parameters, read/write configuration.
Changeover of the operating mode, automatic application of
the slave configuration and the re-addressing of a connected
AS-i slave can be implemented via the control panel of the
CM 1243-2 in the TIA Portal.
The optional DCM 1271 data decoupling module (see
"Accessories", page 2/38) has an integrated detection unit
for detecting ground faults on the AS-Interface cable.
The integrated overload protection also disconnects the
AS-Interface cable if the drive current required exceeds 4 A.
For more information on DCM 1271, see page 2/73.
CM 1243-2 communications module for S7-1200
Notes on security:
More information
In order to protect plants, systems, machines and networks
Equipment Manual for AS-i master CM 1234-2 and AS-i DCM 1271 against cyber threats, it is necessary to implement – and
decoupling module, see continuously maintain – a holistic, state-of-the-art industrial
https://support.industry.siemens.com/cs/ww/en/view/57358958
security concept. Siemens products and solutions represent
The CM 1243-2 communications module is the AS-Interface only one component of such a concept.
master for the SIMATIC S7-1200 and has the following features: For more information about the subject of Industrial Security,
• Connection of up to 62 AS-Interface slaves see www.siemens.com/industrialsecurity.
• Integrated analog value transmission Configuration
• Supports all AS-Interface master functions in accordance with The TIA Portal enables user-friendly configuration and
the AS-Interface specification V3.0 diagnostics of the AS-Interface master and any connected
• Indication of the operating state on the front of the device slave modules.
displayed via LED
When operated on an S7-1200 CPU with firmware version V4.0
• Display of operating mode, AS-Interface voltage faults, or higher, the firmware version V1.1 (or higher) is required for the
configuration faults and peripheral faults via LED behind CM 1243-2.
the front panel
• Compact enclosure in the design of the SIMATIC S7-1200 ■ Benefits
• Suitable for AS-i Power24V and for AS-Interface with 30 V
• More flexibility and versatility in the use of SIMATIC S7-1200
voltage: A standard 24 V power supply unit can be used in
as the result of a significant increase in the number of digital
combination with the optional DCM 1271 data decoupling
and analog inputs/outputs available
module.
• Very easy configuration and diagnostics of the AS-Interface
• Configuration and diagnostics via the TIA Portal
via the TIA Portal
Design • Simple operation with AS-Interface power supply unit
The CM 1243-2 communications module is positioned to the left (see page 2/67) possible without restrictions.
of the S7-1200 CPU and linked to the S7-1200 via lateral contacts. • Alternatively: No need for the AS-i power supply unit with
AS-i Power24V. The AS-Interface cable is supplied through
It has: an existing 24 V DC PELV power supply unit. For decoupling,
• Terminals for two AS-i cables (internally jumpered) via two the AS-i DCM 1271 data decoupling module is required,
screw terminals see "Accessories" and page 2/73.
• One terminal for connection to the functional ground • LEDs for indication of fault statuses for fast diagnostics
• LEDs for indication of the operating state and fault statuses of • Monitoring of AS-Interface voltage facilitates diagnostics
the connected slaves
The screw terminals (included in scope of supply) can be
removed to facilitate installation.
Industrial communication
AS-Interface
Masters
Masters for SIMATIC S7 > CM 1243-2
■ Application
The CM 1243-2 is the AS-Interface master connection for Operating conditions
the 12xx CPUs of the SIMATIC S7-1200. Through connection to • The CM 1243-2 communications module exchanges data with
AS-Interface, the number of digital inputs and outputs available
2
3RK7243-2AA30-0XB0
Note:
The CM 1243-2 communications module is available as
a SIPLUS version under article number 6AG1243-2AA30-7XB0
in the extended temperature range (from -25 to +70 °C) and for
use in harsh environmental conditions (coated according to
environment standard IEC 60721).
For more information, see www.siemens.com/siplus-extreme.
■ Accessories
Version Screw terminals PU PS* PG
(UNIT,
SET, M)
Article No. Price
per PU
DCM 1271 data decoupling module 3RK7271-1AA30-0AA0 1 1 unit 42C
• Max. 1 x 4 A
• Removable terminals (included in the scope of supply)
• Dimensions W x H x D (mm): 30 x 100 x 75
Screw terminals (spare part)
• 5-pole, 3RK1901-3MA00 1 1 unit 42C
For AS-i master CM 1243-2 and AS-i DCM 1271 data
decoupling module
• 3-pole, 3RK1901-3MB00 1 1 unit 42C
3RK7271-1AA30-0AA0 For AS-i DCM 1271 data decoupling module for
connecting the power supply unit
Industrial communication
AS-Interface
Masters
Masters for SIMATIC S7 > CP 343-2P/CP 343-2
■ Overview
Design
The CP 343-2P/CP 343-2 is connected like an I/O module to
2
the S7-300. It has:
• Two terminal connections for connecting the AS-Interface
cable directly.
• LEDs in the front panel for indicating the operating state and
the readiness for operation of all connected and activated
slaves
• Pushbuttons for switching over the master operating state
and for adopting the existing ACTUAL configuration of
the AS-i slave as the TARGET configuration
Function
The CP 343-2P/CP 343-2 supports all specified functions of
the AS-Interface specification V3.0.
Each CP 343-2P/CP 343-2 occupies 16 bytes in the I/O address
area of the SIMATIC S7-300. The digital I/O data of the standard
CP 343-2P/CP 343-2 slaves and A slaves are saved in this area. The digital I/O data
of the B slaves and the analog I/O data can be accessed with
More information the S7 system functions for read/write data records.
Manuals, see https://support.industry.siemens.com/cs/ww/en/ps/15754/man If required, master calls can be performed with the command
For diagnostics during ongoing operation, diagnostics blocks with clearly interface, e.g. read/write parameters, read/write configuration.
arranged visualization on the SIMATIC HMI panel are available or can be
downloaded free of charge via a web browser, see For more information, see
https://support.industry.siemens.com/cs/ww/en/view/61892138 https://support.industry.siemens.com/cs/ww/en/view/51678777.
AS-Interface block library for SIMATIC PCS 7 for easy connection of
AS-Interface to PCS 7, see page 14/19 onwards Notes on security:
The CP 343-2P communications processor is the AS-Interface In order to protect plants, systems, machines and networks
master for the SIMATIC S7-300 and the ET 200M distributed against cyber threats, it is necessary to implement – and
I/O station, with user-friendly parameterizing options. continuously maintain – a holistic, state-of-the-art industrial
security concept. Siemens products and solutions represent
The CP 343-2 is the basic version of the module. only one component of such a concept.
The CP 343-2P/CP 343-2 has the following characteristics: For more information about the subject of Industrial Security,
• Connection of up to 62 AS-Interface slaves see www.siemens.com/industrialsecurity.
• Integrated analog value transmission Configuration
• Support of all AS-Interface master functions in accordance All connected AS-Interface slaves are configured at the press
with the AS-Interface specification V3.0 of a button. No further configuration of the CP is required.
• Status displays of operating states and indication of the
Additionally for CP 343-2P
readiness for operation of connected slaves by means of
LEDs in the front panel The CP 343-2P also supports configuring of the AS-Interface
• Fault indications (including AS-Interface voltage errors, network with STEP 7. Specifying the AS-i configuration in
configuration errors) by means of LEDs on the front plate. HW Config facilitates the setting of slave parameters and
documentation of the plant. Uploading the ACTUAL
• Compact enclosure in the design of the SIMATIC S7-300 configuration of an already configured AS-Interface network is
• Suitable for AS-Interface with 30 V voltage and AS-i Power24V also supported. The saved configuration cannot be overwritten
• Additionally for CP 343-2P: Supports the configuration of the at the press of a button and is therefore tamper-proof.
AS-Interface network with STEP 7
■ Benefits
• Shorter startup times through simple configuration at the press • Lower costs for stock keeping and spare parts inventory
of a button because the CP can be used for the SIMATIC S7-300 and also
• Design of flexible machine-related structures using the for the ET 200M
ET 200M distributed I/O system • Additionally for CP 343-2P: Improved plant documentation
• Provides diagnostics of the AS-Interface network and support for service assignments thanks to a description
of the AS-Interface configuration in the STEP 7 project
• Well suited also for complex applications thanks to connection
options for 62 slaves and integral analog value processing • Simple operation with AS-Interface power supply unit
(see page 2/67) possible without restrictions.
• Reduction of standstill and servicing times in the event of
a fault thanks to the LED displays: • Alternatively: No need for the AS-i power supply unit with
- Status of the AS-Interface network AS-i Power24V. The AS-Interface cable is supplied through an
- Slaves connected and their readiness for operation existing 24 V DC PELV power supply unit. An S22.5 AS-i data
- Monitoring of the AS-Interface voltage decoupling module (e.g. 3RK1901-1DE12-1AA0) is required
for the decoupling, see page 2/71.
Industrial communication
AS-Interface
Masters
Masters for SIMATIC S7 > CP 343-2P/CP 343-2
■ Application
The CP 343-2P/CP 343-2 is the AS-Interface master connection The CP 343-2P is the further development of the CP 343-2 and
for SIMATIC S7-300 and ET 200M. contains its entire functionality. An existing STEP 7 user program
for a CP 343-2 can thus be used without restrictions with
2
Through connection to AS-Interface it is possible to access max. a CP 343-2P. It is only in STEP 7 HW Config that the two modules
248 DI/248 DQ per CP, using 62 A/B slaves with 4 DI/4 DQ each. are configured differently, with the CP 343-2P offering additional
With the integrated analog value processing, it is easy to options. This is why the CP 343-2P is recommended.
transmit analog signals. Up to 62 analog slaves with an
A/B address (each with up to two channels) or up to 31 analog
slaves with a standard address (each with up to four channels)
are possible per CP.
6GK7343-2AH01-0XA0
■ Accessories
Version Article No. Price PU PS* PG
per PU (UNIT,
SET, M)
Industrial communication
AS-Interface
Routers
DP/AS-Interface Link 20E
■ Overview
Routers
High-performance routers between PROFINET and AS-Interface
2
and between PROFIBUS and AS-Interface can be set up by
combining the CM AS-i Master ST and F-CM AS-i Safety ST
modules in an ET 200SP station (for safety-related applications),
see pages 2/29 and 2/34.
Design
• Compact plastic enclosure in degree of protection IP20 for
DIN-rail mounting
• LEDs in the front panel for indicating the operating state and
functional readiness of all connected slaves
• Setting of PROFIBUS DP address is possible by pressing
a button
• LED display of the PROFIBUS DP slave address,
PROFIBUS DP bus faults and diagnostics
• Two pushbuttons for switching over the operating state
and for adopting the existing ACTUAL configuration as
DP/AS-Interface Link 20E manual
the TARGET configuration
More information
Functionality
Manual for DP/AS-Interface Link 20E, see
https://support.industry.siemens.com/cs/ww/en/view/5281638 Communication
The DP/AS-Interface Link 20E enables a DP master to access all
PN DP-M DP-S AS-i M the slaves of an AS-Interface network.
The DP/AS-Interface Link 20E occupies a standard 32 bytes
IK10_10195a
■ Benefits
• Reduction of installation costs because the power is supplied • Quick and easy commissioning by reading the AS-Interface
entirely via the AS-Interface cable, which means that no configuration
additional power supply is required • For diagnostics during ongoing operation, diagnostics blocks
• Short startup times thanks to easy configuration at the touch with clearly arranged visualization on the SIMATIC HMI panel
of a button are available or can be downloaded free of charge via a web
• The LED displays help reduce downtime and service times if browser; see
a slave fails https://support.industry.siemens.com/cs/ww/en/view/61892138.
Industrial communication
AS-Interface
Routers
DP/AS-Interface Link 20E
■ Application
The DP/AS-Interface Link 20E is a PROFIBUS DP slave PROFIBUS DP masters (DP-V0) can exchange digital I/O data
(according to IEC 61158/IEC 61784) and an AS-Interface cyclically with the AS-Interface.
master (according to IEC 62026-2). It enables the AS-Interface
2
S7-400
e.g. with
CP 443-5 Extended
S7-1500 with DP-Master S7-300 with DP-Master
PROFIBUS
DP/AS-Interface
Link 20E
AS-Interface
IK10_40008c
AS-Interface Digital and analog input/output modules 3RA2 load feeder Pushbuttons Signal column
power supply with 3RA27 function Indicator lights
unit module
6GK1415-2AA10
Industrial communication
AS-Interface
Routers
DP/AS-Interface Link 20E
■ Accessories
Version Article No. Price PU PS* PG
per PU (UNIT,
SET, M)
2
PROFIBUS FC standard cable GP 6XV1830-0EH10 1 1M 5K1
FastConnect standard type with special design
for fast installation, 2-core, shielded
PROFIBUS FastConnect bus connector
With insulation displacement connection, max. transmission rate
12 Mbps, activatable terminating resistor integrated
• RS 485 bus connector with 90° cable outlet
- Without PG connection socket 6ES7972-0BA52-0XA0 1 1 unit 250
- With PG connection socket 6ES7972-0BB52-0XA0 1 1 unit 250
• RS 485 bus connector with diagonal cable outlet (35°)
- Without PG connection socket 6ES7972-0BA61-0XA0 1 1 unit 250
- With PG connection socket 6ES7972-0BB61-0XA0 1 1 unit 250
PROFIBUS FastConnect stripping tool 6GK1905-6AA00 1 1 unit 5K2
Preset stripping tool for speedy stripping of
PROFIBUS FastConnect bus cables
Industrial communication
AS-Interface
Slaves
I/O modules for use in the field, high degree of protection > Digital I/O modules, IP67 - Introduction
■ Overview
Connection types
For flexible connection of different sensors and actuators,
2
Industrial communication
AS-Interface
Slaves
I/O modules for use in the field, high degree of protection > Digital I/O modules, IP67 - K60
■ Overview
Addressing and connection of the sensors/actuators
Addressing of the K60 modules is performed using an
2
addressing socket integrated in the compact module.
The addresses can also be assigned after installation.
K60 modules with a maximum of four digital inputs and outputs
These compact modules contain the M12 standard connections
for inputs and outputs. Using M12 standard plugs, a maximum
of four sensors and four actuators can be connected to the
compact module.
K60 compact modules with a maximum of eight digital inputs
These modules have eight digital inputs for connection through
M12 plugs.
The module requires two AS-Interface addresses for processing
all eight inputs. The addressing can thus be performed through
a double addressing socket integrated in the module.
K60
The K60 digital AS-Interface compact modules are K60 data couplers
characterized by optimized handling characteristics and An AS-Interface data coupler has been added to the K60
user-friendliness. They permit the mounting times and startup compact module range. Integrated in this module are two
times of AS-Interface to be reduced by up to 40%. AS-i slaves which are connected to two different AS-i networks.
Each of the two integrated slaves has four virtual inputs and four
Mounting and connection of the AS-Interface shaped cables virtual outputs. The bidirectional data transmission of four data
Assembly of the K60 modules is performed with a mounting bits between two AS-i networks is thus possible in a simple and
plate which accommodates the AS-Interface shaped cables. cost-effective manner. The data coupler needs its own address
Two different mounting plates are offered for in each AS-i network. The data coupler is supplied with power
• Wall mounting directly from the AS-i cable.
• DIN-rail mounting Each AS-i network works with a different cycle time depending
on the number of stations. Hence two AS-i networks are not
The mounting plate and the compact module are joined together necessarily synchronous. For this reason, the AS-i data coupler
by means of a screw, with simultaneous contacting of the can be used to transmit only standard data and no safety data.
AS-Interface cable by the service-proven insulation piercing
method.
Industrial communication
AS-Interface
Slaves
I/O modules for use in the field, high degree of protection > Digital I/O modules, IP67 - K60
■ Accessories
Version Article No. Price PU PS* PG
per PU (UNIT,
SET, M)
3RK1901-0CA00
AS-Interface sealing caps M12 3RK1901-1KA00 100 10 units 42C
For free M12 sockets
3RK1901-1KA00
Sealing sets 3RK1902-0AR00 100 5 units 42D
• For K60 mounting plate
• Cannot be used for K45 mounting plate
• One set contains one straight and one shaped seal
3RK1902-0AR00
Industrial communication
AS-Interface
Slaves
I/O modules for use in the field, high degree of protection > Digital I/O modules, IP68/IP69 - K60R
■ Overview
Operation in particularly harsh environments Connection
2
NSA0_00339f
K60R K60R K60R
IP68 IP68 IP68
Distributor
The K60R modules are connected instead of the AS-Interface In the IP67 environment, the service-proven standard
flat cable using a round cable with M12 cable box. The components are connected using flat cables. Spur lines are laid
AS-Interface bus cable and the 24 V DC auxiliary power into the IP68 environment by means of an AS-Interface M12
supply are routed in this case in a shared round cable. feeder (3RK1901-2NR..). The module is connected with a round
cable to an M12 cable box. For this purpose, the module has an
Degree of protection IP68 permits many new applications that M12 bus connection instead of the former addressing socket.
were impossible with the former field modules with degree of The AS-Interface bus cable and the 24 V DC auxiliary voltage
protection IP67. In applications such as filling plants or machine are routed together in a 4-pole round cable. There must be no
tools, the K60R with degree of protection IP68 enables the ground conductor in this round cable. Connection to ground is
module to be used directly in zones exposed to permanent made through the mounting plate.
loading by humidity. It is thus possible to make even more
rigorous savings in wiring with AS-Interface. For more In the IP68 environment, only cables with extruded M12 plugs
information on IP68 test conditions, see "IP68/IP69 (IP69K) may be used.
tests", page 2/48. Please note the following conditions:
Cleaning with high-pressure cleaners, such as is regularly • The configuration guidelines for AS-Interface apply.
required in the food and beverages industry for instance, For all M12 connecting cables, the maximum permissible
is possible without difficulty (IP69). current is limited to 4 A. The cross-section of these cables
is just 0.34 mm². For connection of the K60R modules,
In applications with cable carriers, many users rely on placing the aforementioned M12 connecting cables can be used
the AS-Interface bus cable in a round cable. With the K60R for the spur lines. The voltage drop caused by the ohmic
module, a round cable connection enables direct connection resistance (approx. 0.11 /m) must be taken into account.
to a round cable. No adapter is required.
• For round cable connections with shared AS-i and Uaux in
Mounting a single cable, the following maximum lengths apply:
- Per spur line from feeder to module: max. 5 m
The same mounting plates are used as for the K60 modules. - Total of all round cable segments in an AS-Interface network:
Instead of using flat cables, the K60R is connected using max. 20 m
a 4-pole round cable with an M12 connection. With the K60R the
mounting plate thus serves only as a fixture and ground terminal.
Addressing
Addressing is performed using the same socket as for the bus
connection. Connecting the module to the addressing unit takes
place over a 3-pole standard M12 cable.
When the mounting is finished, the module is connected with
the addressing cable to the addressing unit and addressed.
The addressing cable is then removed and the module
connected to the bus cable.
Industrial communication
AS-Interface
Slaves
I/O modules for use in the field, high degree of protection > Digital I/O modules, IP68/IP69 - K60R
IP68/IP69 (IP69K) tests To simulate requirements as realistically as possible,
the modules were artificially aged prior to the tests by
K60R modules were tested with the following tests: 15 temperature cycles of -25/+85 °C. During the test,
• Stricter test than IP67: 90 min at 1.8 m depth of water the modules were connected to 3RX1 connecting cables.
(IP67: 30 min at 1 m depth of water) Unassigned connections were closed with 3RK1901-1KA00
2
• Salt water test: Five months in salt water, 20 cm deep, at room sealing caps.
temperature Note:
• Test with particularly creepable oil: Five months completely
under oil at room temperature Sealing caps and M12 connections must be tightened with
the correct torque.
• Test with drilling emulsion: Five months at room temperature
(components of the drilling emulsion: Anionic and non-ionic
emulsifiers, paraffinic low-aromatic mineral oil, boric acid
alkanolamines, corrosion inhibitors, oil content 40%)
• Test in oil bath (Excellence 416 oil) with alternating oil bath
temperature: 130 cycles of 15 to 55 °C, two months
• Cleaning with a high-pressure cleaner according to IP69
(IP69K): 80 to 100 bar, 10 to 15 cm distance, time per side
> 30 s, water temperature 80 °C
Industrial communication
AS-Interface
Slaves
I/O modules for use in the field, high degree of protection > Digital I/O modules, IP68/IP69 - K60R
■ Accessories
Version Article No. Price PU PS* PG
per PU (UNIT,
SET, M)
2
K60 mounting plates
Suitable for all K60 and K60R compact modules
• Wall mounting 3RK1901-0CA00 1 1 unit 42C
• DIN-rail mounting 3RK1901-0CB01 1 1 unit 42C
3RK1901-0CA00
AS-Interface sealing caps M12 3RK1901-1KA00 100 10 units 42C
For free M12 sockets
3RK1901-1KA00
AS-Interface M12 feeders, current-carrying capacity up
to 4 A
For flat For Cable Cable end in
cable length feeder
AS-i/Uaux M12 socket -- Not available 3RK1901-2NR20 1 1 unit 42C
AS-i/Uaux M12 cable box 1m Not available 3RK1901-2NR21 1 1 unit 42C
AS-i/Uaux M12 cable box 2m Not available 3RK1901-2NR22 1 1 unit 42C
3RK1901-2NR21
AS-Interface M12 feeders, 4-fold, current-carrying
capacity up to 4 A
For flat For Cable Cable end in
cable length feeder
AS-i/Uaux 4-fold M12 socket, -- Not available 3RK1901-1NR04 1 1 unit 42C
delivery includes
mounting plate (for
wall and DIN-rail
mounting)
3RK1901-1NR04
M12 connecting cables 3RK1902-4PB15-3AA0 1 1 unit 42D
• 3-pole
3RK1902-4PB15-3AA0
• For addressing AS-i slaves with M12 bus connection
• Cable length 1.5 m
Industrial communication
AS-Interface
Slaves
I/O modules for use in the field, high degree of protection > Digital I/O modules, IP67 - K45
■ Overview
Connection of the AS-Interface shaped cables
The mounting plate and the compact module are joined together
2
Industrial communication
AS-Interface
Slaves
I/O modules for use in the field, high degree of protection > Digital I/O modules, IP67 - K45
2
Digital I/O modules, IP67 - K45
• PNP transistor
• Width 45 mm
• Current-carrying capacity of the inputs: 200 mA
• Modules supplied without mounting plate
Type Current- Slave Pin Uaux Connection
carrying addressing assign- 24 V methods
capacity type ment
of outputs
8 inputs1) -- A/B Y -- M12 3RK2200-0DQ20-0AA3 1 1 unit 42C
3RK1400- 4 inputs -- Standard Standard -- M12 3RK1200-0CQ20-0AA3 1 1 unit 42C
0GQ20-0AA3
-- Standard Standard -- M8 3RK1200-0CT20-0AA3 1 1 unit 42C
-- A/B Standard -- M12 3RK2200-0CQ20-0AA3 1 1 unit 42C
-- A/B Standard -- M8 3RK2200-0CT20-0AA3 1 1 unit 42C
2 x 2 inputs -- A/B Y -- M12 3RK2200-0CQ22-0AA3 1 1 unit 42C
2 inputs/ 2 A2) Standard Standard ✓ M12 3RK1400-1BQ20-0AA3 1 1 unit 42C
2 outputs
2 x (1 input/ 0.2 A Standard Y -- M12 3RK1400-0GQ20-0AA3 1 1 unit 42C
1 output)
4 x (1 input/ 0.2 A A/B Y -- M12 3RK2400-0GQ20-0AA3 1 1 unit 42C
1 output) (spec. V3.0)
0.5 A A/B Y ✓ M12 3RK2400-1GQ20-1AA3 1 1 unit 42C
(spec. V3.0)
4 outputs 1A A/B Standard ✓ M12 3RK2100-1CQ20-0AA3 1 1 unit 42C
(spec. V3.0)
3 outputs 1A A/B Standard ✓ M12 3RK2100-1EQ20-0AA3 1 1 unit 42C
4 outputs 1A Standard Standard ✓ M12 3RK1100-1CQ20-0AA3 1 1 unit 42C
2 outputs/ 2A A/B Standard ✓ M12 3RK2400-1BQ20-0AA3 1 1 unit 42C
2 inputs
✓ Available 1) Module occupies two AS-Interface addresses
2)
-- Not available The typical current-carrying capacity per output increases with version
"E12" from 1.5 to 2 A (available since approx. 07/2003).
For safety modules for AS-Interface, see page 2/27 onwards.
■ Accessories
Version Article No. Price PU PS* PG
per PU (UNIT,
SET, M)
3RK1901-2EA00
Cable end terminator 3RK1901-1MN00 1 10 units 42C
For sealing open cable ends of the
AS-Interface shaped cable with IP67
3RK1901-1MN00
AS-Interface sealing caps
• For free M12 sockets 3RK1901-1KA00 100 10 units 42C
• For free M8 sockets 3RK1901-1PN00 100 10 units 42C
3RK1901-1KA00
3RK1901-1PN00
Industrial communication
AS-Interface
Slaves
I/O modules for use in the field, high degree of protection > Digital I/O modules, IP67 - K20
■ Overview
Robotics is yet another application area. The K20 modules are
connected to the AS-Interface with a round cable with M12 cable
box instead of with the AS-Interface flat cable. The AS-Interface
2
Industrial communication
AS-Interface
Slaves
I/O modules for use in the field, high degree of protection > Digital I/O modules, IP67 - K20
■ Accessories
Version Article No. Price PU PS* PG
per PU (UNIT,
SET, M)
2
AS-Interface sealing caps
• For free M12 sockets 3RK1901-1KA00 100 10 units 42C
• For free M8 sockets 3RK1901-1PN00 100 10 units 42C
3RK1901-1KA00
3RK1901-1PN00
AS-Interface compact distributors, 1 1 unit 42C
for AS-Interface flat cable AS-i or Uaux
• Current-carrying capacity up to 8 A
3RK1901-2NN10 • Degree of protection IP67/IP68/IP69 (IP69K)
For flat For Cable Cable end in
cable length feeder
AS-i or Uaux Flat ribbon cable -- Not available 3RK1901-2NN10 1 1 unit 42C
AS-i or Uaux
AS-Interface M12 feeders
• Current-carrying capacity up to 2 A
• Degree of protection IP67
3RX9801-0AA00 For flat For Cable Cable end in
cable length feeder
AS-i M12 socket -- Available 3RX9801-0AA00 1 1 unit 42C
AS-Interface M12 feeders
• Current-carrying capacity up to 4 A
• Degree of protection IP67/IP68/IP69 (IP69K)
For flat For Cable Cable end in
3RK1901-2NR10 cable length feeder
AS-i M12 socket -- Not available 3RK1901-2NR10 1 1 unit 42C
AS-i M12 cable box 1m Not available 3RK1901-2NR11 1 1 unit 42C
AS-i M12 cable box 2m Not available 3RK1901-2NR12 1 1 unit 42C
AS-i/Uaux M12 socket -- Not available 3RK1901-2NR20 1 1 unit 42C
AS-i/Uaux M12 cable box 1m Not available 3RK1901-2NR21 1 1 unit 42C
AS-i/Uaux M12 cable box 2m Not available 3RK1901-2NR22 1 1 unit 42C
3RK1901-2NR21
AS-Interface M12 feeders, 4-fold
• Current-carrying capacity up to 4 A
• Degree of protection IP67
For flat For Cable Cable end in
cable length feeder
AS-i/Uaux 4-fold M12 socket, -- Not available 3RK1901-1NR04 1 1 unit 42C
delivery includes
mounting plate
3RK1901-1NR04 (for wall and DIN-rail
mounting)
M12 Y-shaped coupler plugs 6ES7194-1KA01-0XA0 1 1 unit 250
For connection of two sensors to one M12 socket with
Y-assignment
6ES7194-1KA01-0XA0
M12 connecting cables 3RK1902-4PB15-3AA0 1 1 unit 42D
• 3-pole
3RK1902-4PB15-3AA0
• For addressing AS-i slaves with M12 bus connection
• Cable length 1.5 m
Industrial communication
AS-Interface
Slaves
I/O modules for use in the field, high degree of protection > Analog I/O modules, IP67 - K60
■ Overview ■ Benefits
• Analog modules are just as easy to integrate in AS-Interface
as digital modules
2
More information
Manual for AS-Interface analog modules, see
https://support.industry.siemens.com/cs/ww/en/view/7643815
Industrial communication
AS-Interface
Slaves
I/O modules for use in the field, high degree of protection > Analog I/O modules, IP67 - K60
2
SET, M)
Industrial communication
AS-Interface
Slaves
I/O modules for use in the field, high degree of protection > Analog I/O modules, IP67 - K60
■ Accessories
Version Article No. Price PU PS* PG
per PU (UNIT,
SET, M)
2
3RK1901-0CA00
M12 sealing caps 3RK1901-1KA00 100 10 units 42C
3RK1901-1KA00
Sealing sets 3RK1902-0AR00 100 5 units 42D
• For K60 mounting plate
• Cannot be used for K45 mounting plate
• One set contains one straight and one shaped seal
3RK1902-0AR00
Jumper plugs 3RK1901-1AA00 1 1 unit 42C
For changing over the 2-channel input modules
3RK1901-1AA00
Industrial communication
AS-Interface
Slaves
I/O modules for use in the control cabinet > Introduction
■ Overview
For AS-Interface applications inside control cabinets, there are
various module series for the most diverse requirements:
2
• SlimLine Compact – particularly slim design ideal for space-
saving use in the control cabinet
• F90 module – particularly flat design for flat control boxes
• Flat module – special design for integration into customer-
specific solutions
The existing SlimLine series of modules S22.5 and S45 are being
replaced by the innovative new devices in the SlimLine Compact
SC17.5, SC17.5F and SC22.5 series. The previous SlimLine
modules are still available as replacements for existing systems.
Available versions
The following table provides an overview of the key features of
the different series of control cabinet modules.
Feature SlimLine Compact F90 Flat module
SlimLine Compact modules SC17.5F, SC17.5 and SC22.5 module
Digital I/O ✓ ✓ ✓
Analog I/O ✓ -- --
Safe inputs ✓ -- --
Relay outputs ✓ -- --
Addressing type ✓ -- --
A/B address
Mounting on TH 35 DIN ✓ ✓ --
rail according to
IEC 60715
Wall mounting using ✓ -- --
push-in lugs
Integrated lugs for screw -- -- ✓
fixing
Width in mm 17.5 or 22.5 90 80
✓ Available
-- Not available
F90 module
Flat module
Industrial communication
AS-Interface
Slaves
I/O modules for use in the control cabinet > SlimLine Compact
■ Overview
SlimLine Compact modules
2
SC17.5 and SC22.5 SlimLine Compact modules with screw terminals SC22.5 SlimLine Compact module with connector with screw terminals
The AS-Interface module series for the control cabinet SlimLine All devices for the connection of three-wire sensors offer the
Compact with degree of protection IP20 creates space in the option of supplying the sensors either from the AS-Interface bus
cabinet and in distributed local control boxes. A width of just cable or alternatively from the 24 V DC voltage supply Uaux
17.5 mm or 22.5 mm ensures considerable space savings in the depending on the requirements of the particular application.
control cabinet. A slide switch is used to make the selection. If supply via Uaux is
selected, the wiring of the sensor terminals remains unchanged.
The SlimLine Compact module series comprises not only digital This means that no external supply is required for the sensors.
and analog I/O modules but also ASIsafe modules with safe
inputs. Digital outputs are available as solid-state and relay All modules have LEDs on the front that provide diagnostics
outputs. information and indicate the status of the module inputs and
outputs. Devices with semiconductor outputs indicate the status
Sensors and actuators, as well as the AS-Interface bus cable, of each output by means of a dual LED. Thus the status
are connected by means of removable screw or push-in spring- (on/off/overload) is displayed for each output. An addressing
loaded terminals. Device connectors available as accessories socket integrated at the front enables the module to be
offer the possibility of looping through the AS-Interface bus addressed also when it is installed. Integrated adapters permit
cable and the 24 V DC power supply Uaux from one module to mounting on a DIN rail either directly for the module or for the
additional modules. This significantly simplifies the wiring, as the device connector. Alternatively, the modules can also be screw-
AS-Interface bus cable and Uaux only have to be connected to mounted using push-in lugs (accessories). These lugs for screw
one device. fastening must be ordered separately.
Industrial communication
AS-Interface
Slaves
I/O modules for use in the control cabinet > SlimLine Compact
2
Equipment Manual, see
https://support.industry.siemens.com/cs/ww/en/view/109481489
Industrial communication
AS-Interface
Slaves
I/O modules for use in the control cabinet > SlimLine Compact
■ Accessories
Version Article No. Price PU PS* PG
per PU (UNIT,
SET, M)
2
Device connectors
For electrical connection of SlimLine Compact modules
(connects AS-i bus cable and 24 V DC auxiliary power supply
Uaux when using several SlimLine Compact modules)
• Width 17.5 mm 3RK1901-1YA00 1 1 unit 42C
• Width 22.5 mm 3RK1901-1YA10 1 1 unit 42C
3RK1901- 3RK1901-
1YA00 1YA10
Device termination connectors
Required for the last module in the network
• Width 17.5 mm 3RK1901-1YA01 1 1 unit 42C
• Width 22.5 mm 3RK1901-1YA11 1 1 unit 42C
3RK1901- 3RK1901-
1YA01 1YA11
Removable terminals Screw terminals
3ZY1450- 3ZY1450-
1BA00 1AB00
Push-in lugs for wall mounting 3ZY1311-0AA00 1 10 units 41L
Two lugs are required per device
3ZY1311-0AA00
Coding pins for removable terminals 3ZY1440-1AA00 1 12 units 41L
For mechanical coding of the terminals
3ZY1440-1AA00
Blank labels
Unit labeling plates1)
• 10 mm x 7 mm, titanium gray 3RT2900-1SB10 100 816 41B
units
IC01_00181
Industrial communication
AS-Interface
Slaves
I/O modules for use in the control cabinet > SlimLine Compact
■ More information
The existing SlimLine series of I/O modules for use in the control
cabinet is being replaced by the new, innovative SlimLine
Compact series. We recommend that these new devices are
2
used in future.
The code conversion table indicates the best options for replacing
the existing SlimLine devices with SlimLine Compact devices.
Note:
The previous SlimLine devices are still available for use as
replacements in existing systems. As a result of the innovation,
the new SlimLine Compact devices are not fully compatible in
terms of either mechanical dimensions or electrical properties.
The code conversion table below links the existing S22.5,
S22.5F and S45 SlimLine modules with the new SC17.5,
SC17.5F and SC22.5 SlimLine Compact devices.
Industrial communication
AS-Interface
Slaves
I/O modules for use in the control cabinet > F90 module
F90 module
• Slave addressing type: Standard address
• Width 90 mm
• With COMBICON version:
Delivery without COMBICON plug
Type Connection Inputs Outputs
4 Screw Two and PNP transistor 3RG9002-0DB00 1 1 unit 42C
3RG9002-0DB00 inputs/ three-wire 1A
4 PNP transistor
outputs Two and PNP transistor 3RG9002-0DA00 1 1 unit 42C
three-wire 2A
PNP transistor
Two and PNP transistor 3RG9002-0DC00 1 1 unit 42C
three-wire 2A
PNP transistor
floating
COMBICON1) Two and PNP transistor 3RG9004-0DB00 1 1 unit 42C
three-wire 1A
PNP transistor
Two and PNP transistor 3RG9004-0DA00 1 1 unit 42C
three-wire 2A
PNP transistor
Two and PNP transistor 3RG9004-0DC00 1 1 unit 42C
three-wire 2A
PNP transistor
floating
1)
Scope of supply does not include COMBICON connector set
3RX9810-0AA00, this must be ordered separately, see "Accessories".
■ Accessories
Version Article No. Price PU PS* PG
per PU (UNIT,
SET, M)
Industrial communication
AS-Interface
Slaves
I/O modules for use in the control cabinet > Flat module
■ Overview
The flat module for the control cabinet in degree of protection
IP20 has four inputs and four outputs.
2
The module is fitted at the front with an LED which indicates the
module's status.
With the integrated lugs, the modules can be screwed on.
An integrated addressing socket enables the module to be
addressed when it is installed.
Standard sensors/actuators and the AS-Interface cable can be
connected using screw terminals.
3RK1400-0CE00-0AA3
Industrial communication
AS-Interface
Slaves
Modules with special functions > Counter modules
■ Overview
This results in a maximum frequency of fZmax = 1/1.3 ms = 769 Hz
independently of the control system (see figure below).
2
U IN1
NSA0_00084
≥ 1 ms ≥ 300 s t
A further condition for the maximum frequency is the required Terminal 7: Sensor supply +
pulse shape. For the counter to accept a pulse as valid, a Low Terminal 8: Counter input
must have been applied at the input for at least 300 µs and Terminal 9: Sensor supply -
NSA0_00085
Counter modules
Slave addressing type: Standard address
Width 22.5 mm
• With screw terminals 3RK1200-0CE03-0AA2 1 1 unit 42C
3RK1200-0CG03-0AA2
Industrial communication
AS-Interface
Slaves
Modules with special functions > Ground-fault detection modules
■ Overview
"Ground faults in any control circuit must not lead to unintentional
starting or potentially hazardous movements or prevent the
machine from stopping." (IEC 60204-1/VDE 0113-1).
2
The AS-Interface ground-fault detection module is used to meet
these requirements. Using this module from the SlimLine series,
ground faults in AS-Interface systems can be reliably detected
and reported.
The following ground faults are detected:
• Ground fault from AS-i "+" to ground
• Ground fault from AS-i "-" to ground
• Ground fault on sensors and actuators that are supplied from
the AS-Interface voltage.
Note:
Not suitable for AS-i Power24V.
Check whether the AS-i power supply unit or the AS-i master
module, etc. features integrated ground-fault detection, and
Ground-fault detection module with spring-loaded terminals therefore whether a separate ground fault detection module can
be omitted.
It should be noted that an AS-i cable segment behind an
AS-i repeater requires its own ground-fault monitoring.
3RK1408-8KG00-0AA2
Industrial communication
AS-Interface
Slaves
Modules with special functions > Overvoltage protection modules
■ Overview
With the AS-Interface overvoltage protection module, it is now
also possible to integrate AS-Interface in the overall overvoltage
protection concept of a plant or machine.
2
The module has the same design and degree of protection (IP67)
as the AS-Interface K45 compact modules. It is a passive module
and as such does not need its own address on the AS-Interface
network. The module can be used to protect the AS-Interface cable
and the cable for the auxiliary voltage from overvoltage.
Overvoltages are discharged through a ground cable with a green/
yellow oil-proof outer sheath. This cable is fixed in the module and
must be connected with low resistance to the system's ground.
Rated discharge current Isn
The rated discharge current is the peak value of a surge current
of the form 8/20 s (microseconds), for which the protection
AS-Interface overvoltage protection module module is designed in accordance with a specified test
program. With an 8/20 waveform, 100% of the value is achieved
The AS-Interface overvoltage protection module (protection after 8s and 50% after 20 s.
module) protects downstream AS-Interface devices or individual
sections in AS-i networks from conducted overvoltages which can Protection level Up
be caused by switching operations and remote lightning strikes.
The protection level of a protection module is the highest
The location of the protection module forms the transition from
momentary value of the voltage at the terminals, established in
zone 1 to 2/3 within the lightning protection zone concept. Direct
individual tests and characterizes the capability of a protection
lightning strikes must be coped with using additional protective
module to limit overvoltages to a residual level.
measures at the transitions from lightning protection zone 0A to 1.
Configuration guidelines
The grounding of protection modules and the units to be If insulated devices are protected, their mounts must be
protected must be effected through a shared grounding point. included in the grounding points.
Sample application
Protected range
NSA0_00092b
Equipotential bonding
(system earth)
Protection approx. 0.5 m to the left
Protection approx. 5 m to the right OVP = Overvoltage protection
Industrial communication
AS-Interface
Power supply units and data decoupling modules
AS-Interface power supply units
■ Overview
Dimensions
AS-Interface power supply units have compact dimensions in
2
widths of 50/70/120 mm. No distances from other devices need
to be observed when mounting the power supply units.
Features
• Higher rating: The power supply units deliver currents
of 2.6 to 8 A.
• Integrated data decoupling: As the result, AS-Interface is able
to convey both data and power along a single line.
• Integrated ground-fault detection: The power supply units
perform the reliable detection and signaling of ground faults
according to IEC 60204-1. The AS-Interface voltage can be
disconnected automatically in the event of a ground fault.
• Integrated overload detection: An output overload is detected
and reported over a diagnostics LED.
• Diagnostics memory: Any ground faults or overloads on the
output side are stored in a diagnostics memory and signaled
AS-Interface power supply unit for 3 A
until the device is RESET.
More information • Remote RESET and remote signaling: Using relay contacts,
Operating Instructions for AS-i power supply units, see a ground fault can be signaled and evaluated by a central
https://support.industry.siemens.com/cs/ww/en/view/21489904 and controller and/or indicator light.
https://support.industry.siemens.com/cs/ww/en/view/22317836 • Diagnostics LEDs: Three different LEDs indicate the status
AS-Interface power supply units feed 30 V DC into the of the AS-Interface power supply unit locally at the power
AS-Interface cable and supply the AS-Interface components. supply unit.
They include power-optimized data decoupling for the • Ultra-wide input range/2-phase connection: The ultra-wide
separation of communication signals and supply voltage. As the input range of 120 to 500 V of the 8 A version means that the
result, AS-Interface is able to convey both data and power along supply units can be used in virtually any network worldwide.
a single line. The power supply units are resistant to overload In addition, this version dispenses with the need for an
and short circuits. N conductor as the device can be connected directly
between 2 phases of a network.
• Operation with 24 V DC: The 3 A power supply unit is also
available as a version with a 24 V DC input. This power supply
unit is suitable for use in battery-powered systems or in
systems with UPS (uninterruptible power supply).
• Removable terminal blocks with spring-loaded terminals:
For easy exchanging of devices, each power supply unit has
three removable terminal blocks: for the input side, for the
output side and for Signal/RESET connections.
■ Benefits
• Complete solution for supplying AS-Interface networks while • Fast fault detection and reduced downtimes thanks to
making full use of the maximum possible cable length per diagnostics memory, remote signaling and Remote RESET
AS-i segment • Reduced downtimes as the result of removable terminal
• Only AS-i masters and AS-i slaves need to be connected to blocks which enable the fast exchanging of devices
the AS-Interface cable in order to operate AS-Interface • Ultra-wide input range of the 8 A version permits 1-phase and
• Compact, space-saving dimensions 2-phase operation and removes the need for an N conductor
• Reliable power supply even for large numbers of AS-Interface • Can be used world-wide thanks to, for example, UL/CSA
modules with a high power requirement approval (UL 508)
• Integrated ground-fault and overload detection saves the • With the 2.6 A version, the output power is restricted to
need for additional components and enhances safety max. 100 W for use in Class 2 circuits in accordance with NEC
(National Electrical Code)
Industrial communication
AS-Interface
Power supply units and data decoupling modules
AS-Interface power supply units
Industrial communication
AS-Interface
Power supply units and data decoupling modules
30 V power supply units
■ Overview
The PSN130S 30 V power supply units feed 30 V DC into the
AS-Interface cable and supply the AS-Interface components,
but do not include data decoupling. Data decoupling modules
2
are needed in addition therefore to separate communication
signals and control supply voltage, see page 2/71 or 2/73.
The power supply units are resistant to overload and short
circuits.
Dimensions
The 30 V power supply units have compact dimensions with
widths of 50 and 70 mm. No distances from other devices need
to be observed when mounting the power supply units.
Features
• Primary switched-mode power supplies for connection to
a 1-phase AC system
• Power for currents of 3 A, 4 A and 8 A
• The output voltage is floating, and resistant to short-circuits
PSN130S 30 V power supply units for 3 A, 4 A and 8 A and no-load operation. If there is an overload, the output
voltage is reduced or cut-off. After a short circuit or overload,
More information the devices start up again automatically.
For operating instructions and other technical information, see • In the event of a device fault, the output voltage will be limited
https://support.industry.siemens.com/cs/ww/en/view/64364000 and
https://support.industry.siemens.com/cs/ww/en/view/44030789
to max. 37 V.
• Modular installation devices in degree of protection IP20 and
protection class I
• Diagnostics: With an output voltage > 26.5 V DC, the green
LED (30 V O.K.) is lit and the signaling contact 13-14 is closed.
■ Benefits
• Low-cost alternative solution for supplying AS-Interface • Reliable power supply even for large numbers of AS-Interface
networks while making full use of the maximum possible cable modules with a high power requirement
length per AS-i segment • Can be used world-wide thanks to, for example, UL/CSA
• Cost advantage particularly for multiple networks approval (UL 508)
• Compact, space-saving dimensions
■ Application
Configuration examples of AS-Interface networks with a 30 V power supply unit
SIMATIC ET 200SP
IC01_00222a
AS-Interface
PSN130S
PSN130S 30 V power supply unit
30 V power
supply unit AS-Interface AS-Interface
AS-Interface AS-Interface
Configuration of AS-Interface multiple networks with one PSN130S 30 V power supply unit (examples with schematic representation):
Left: Double network based on the S22.5 double data decoupling module and a SIMATIC ET 200SP with two CM AS-i Master ST modules
Right: Triple network based on the SIMATIC S7-1200 with DCM 1271 data decoupling modules and CM 1243-2 communications processors
Industrial communication
AS-Interface
Power supply units and data decoupling modules
30 V power supply units
■ Technical specifications
PSN130S 30 V DC power supply unit 3A 4A 8A PSN130S 30 V DC power supply unit 3A 4A 8A
Input data Protection and monitoring
2
• Input voltage, rated value Ue V AC 120/230 V, 1-phase, • Output overvoltage protection V < 37
automatic selection • Current limiting, typ. A 4 5.5 11
• Range of input voltage V AC 85 ... 132/174 ... 264 Operating data
• Mains frequency Hz 50/60 Ambient temperature
• Power consumption at full load, typ. W 103 139 270 • Operation °C -20 ... +70
Output data • Transportation/storage °C -40 ... +85
• Output voltage, rated value Ua V DC 30 Pollution degree 2
• Residual ripple mVpp < 150 Humidity class Climate class according
• Output current, rated value A 3 4 8 to DIN 50010, relative air
at -20 ... +60 °C humidity max. 100%,
• Max. output current A 3 3 4 without condensation
at +60 ... +70 °C Dimensions and weight
Degree of efficiency under rated conditions • Width mm 50 50 70
• Degree of efficiency % 87 88 90 • Height x depth mm 125 x 126.5
• Power loss, typ. W 12 17 25 • Weight kg 0.4 0.4 0.7
3RX9512-0AA00
3RX9513-0AA00
Industrial communication
AS-Interface
Power supply units and data decoupling modules
S22.5 data decoupling modules
■ Overview ■ Benefits
• Compatible expansion of the AS-Interface system
• An existing standard power supply unit with 24 V DC or
2
30 V DC can be used for supplying AS-i networks
• The AS-Interface system can also be used in tightly budgeted
applications because no AS-Interface power supply unit
needs to be purchased
• Applications benefit in addition from the advantages of
a modern bus system:
- High level of standardization
- Additional diagnostics and maintenance information
- Faster commissioning
• Easy and cost-efficient design of single and multiple networks
is possible
■ Application
The AS-Interface data decoupling module is designed for
AS-Interface networks with 30 V or 24 V supply (AS-i Power24V).
AS-Interface S22.5 double data decoupling module: Operation of an AS-i network with the data decoupling module
Screw terminal version (picture on left),
Spring-loaded terminal version (picture on right)
and a 30 V standard power supply unit is technically equivalent
to the use of an AS-Interface power supply unit and offers the
More information service-proven features of AS-Interface for all applications.
Operating Instructions, see AS-Interface Power24V uses a 24 V power supply unit in
https://support.industry.siemens.com/cs/ww/en/view/44030789 conjunction with a data decoupling module and is particularly
More information on AS-i Power24V, see suitable for:
System Manual for AS-Interface,
https://support.industry.siemens.com/cs/ww/en/view/26250840 • Compact machines using AS-Interface input/output modules
• Applications in the control cabinet for AS-Interface integration
With the aid of the S22.5 data decoupling module, the of SIRIUS 3RT2 contactors using 3RA27 function modules
AS-Interface network can also be supplied with 24 V DC or
30 V DC from a standard power supply unit and the transmission When using the double data decoupling module or other
of data and power can be realized along one cable. data decoupling units, several AS-Interface networks can be
operated with a single power supply unit. This results in an
The combination of data decoupling modules and standard additional cost advantage.
power supply units is therefore a cost-efficient alternative to
the service-proven AS-Interface power supply units. Note:
The quality of the data signals and the reliable operation of The power supply units must comply with the ES1 (IEC 62368-1)
the AS-i network are not negatively affected as the result. or PELV (Protective Extra Low Voltage)/SELV (Safety Extra Low
Voltage) standards, have a residual ripple of < 250 mVpp, and
Features of the S22.5 data decoupling module must limit the output voltage to a maximum of 40 V in the event
• Degree of protection IP20 of a fault.
• Narrow design: 22.5 mm wide We recommend
• Version with screw or spring-loaded terminals • SITOP power supplies, see page 15/1 or Catalog KT 10.1,
• Versions for single and double data decoupling https://support.industry.siemens.com/cs/ww/en/view/109745655.
• Supply of several AS-i networks with a single power supply unit • PSN130S 30 V power supply units, see page 2/69
• Operation with 24 V DC or 30 V DC, grounded or non-grounded Note on AS-i Power24V:
• Adjustable current limiting up to 2 x 4 A The length of an AS-i Power24V network is restricted to 50 m in
• Integrated ground-fault detection with fault storage, display order to limit the voltage drop along the cable.
can optionally be switched off AS-i masters, AS-i slaves and the sensors and actuators
• Diagnostics LEDs and signaling contacts supplied through the AS-i cable must be designed for the
• RESET by button or Remote RESET reduced voltage. Sensors and actuators for the standard voltage
range of 10 to 30 V can be supplied with sufficient voltage.
Ground-fault detection
Please also observe the requirements specified in
The integrated ground-fault detection works with a grounded "AS-i Power24V" for the operation of an AS-i Power24V network,
and non-grounded supply: The connection of negative pole and see page 2/23.
ground (upstream from the data decoupling module) customary
with 24 V DC power supplies is permitted. A ground fault to For more information on AS-i Power24V, see System Manual for
the negative or positive pole on the AS-Interface network AS-Interface,
(downstream from the data decoupling module) is detected https://support.industry.siemens.com/cs/ww/en/view/26250840.
and stored as a fault and will be signaled using LEDs and
a relay contact.
Using the ground-fault detection in the AS-i master is
recommended for non-grounded supply. In this case,
the ground-fault indicator can be deactivated in the data
decoupling module to avoid any unwanted LED messages.
Industrial communication
AS-Interface
Power supply units and data decoupling modules
S22.5 data decoupling modules
Configuration of an AS-i Power24V network with AS-Interface S22.5 data decoupling module
PROFINET PROFINET
2
Single Up to 50 m Double Up to 50 m
data data
decoupling decoupling
module AS-Interface module AS-Interface
NSB0_02191b
AS-Interface
NSB0_02192b
I/O modules
3RK1901-1DE12-1AA0
S22.5 data decoupling modules Spring-loaded
With spring-loaded terminals, removable terminals, terminals
width 22.5 mm, height 105 mm, depth 115 mm
• Single data decoupling module, 1 x 4 A 3RK1901-1DG12-1AA0 1 1 unit 42C
• Double data decoupling module, 2 x 4 A 3RK1901-1DG22-1AA0 1 1 unit 42C
3RK1901-1DG12-1AA0
Industrial communication
AS-Interface
Power supply units and data decoupling modules
Data decoupling modules for S7-1200 > DCM 1271 data decoupling module
■ Overview
The DCM 1271 data decoupling module has the same enclosure
design as the S7-1200 module and is therefore ideal for
combining with the CM 1243-2 AS-i master.
2
The DCM 1271 data decoupling module has no connection to
the backplane bus of the SIMATIC S7-1200 and is not counted
as a communications module when calculating the maximum
configuration.
Features of the DCM 1271 data decoupling module
• Design: S7-1200, width 30 mm, degree of protection IP20
• Detachable terminals (included in the scope of supply)
• Single data decoupling
• Supply of several AS-i networks with a single power supply unit
• Operation with 24 V DC or 30 V DC, grounded or non-grounded
• Current limiting at 4 A
• Integrated ground-fault detection
• Diagnostics LEDs for ground faults and overloads
DCM 1271 data decoupling module for SIMATIC S7-1200
• Signaling contacts for ground-fault detection
More information
Ground-fault detection
Manual for AS-i master CM 1234-2 and AS-i DCM 1271 data decoupling
module, see https://support.industry.siemens.com/cs/ww/en/view/57358958 The integrated ground-fault detection works with a grounded
For more information on AS-i Power24V, see and non-grounded supply: The connection of negative pole and
System Manual for AS-Interface, ground (upstream from the data decoupling module) customary
https://support.industry.siemens.com/cs/ww/en/view/26250840 with 24 V DC power supplies is permitted. A ground fault to
the negative or positive pole on the AS-Interface network
With the aid of the DCM 1271 data decoupling module,
(downstream of the data decoupling module) is identified
the AS-Interface network can also be supplied with 24 V DC or
and signaled via LED and a transistor output.
30 V DC from a standard power supply unit and the transmission
of data and power can be realized along one cable.
■ Benefits
• An existing standard power supply unit with 24 V DC or
30 V DC can be used for supplying AS-i networks
• The AS-Interface system can also be used in tightly budgeted
applications because no AS-Interface power supply unit
needs to be purchased
• Applications benefit in addition from the advantages of
a modern bus system:
- High level of standardization
- Additional diagnostics and maintenance information
- Faster commissioning
Industrial communication
AS-Interface
Power supply units and data decoupling modules
Data decoupling modules for S7-1200 > DCM 1271 data decoupling module
■ Application
The AS-Interface data decoupling module is designed for Note on AS-i Power24V:
AS-Interface networks with 30 V or 24 V supply (AS-i Power24V).
The length of an AS-i Power24V network is restricted to 50 m in
2
Operation of an AS-i network with the data decoupling module order to limit the voltage drop along the cable.
and a 30 V standard power supply unit is technically equivalent
to the use of an AS-Interface power supply unit and offers the AS-i masters, AS-i slaves and the sensors and actuators
service-proven features of AS-Interface for all applications. supplied through the AS-i cable must be designed for the
reduced voltage. Sensors and actuators for the standard voltage
AS-i Power24V uses a 24 V power supply unit in conjunction with range of 10 to 30 V can be supplied with sufficient voltage.
a data decoupling module and is particularly suitable for
Please also observe the requirements specified in
• Compact machines using AS-Interface input/output modules "AS-i Power24V" for the operation of an AS-i Power24V network,
• Applications in the control cabinet for AS-Interface integration see page 2/23.
of SIRIUS 3RT2 contactors using 3RA27 function modules For more information on AS-i Power24V, see System Manual for
Note: AS-Interface,
https://support.industry.siemens.com/cs/ww/en/view/26250840.
The power supply units must comply with the ES1 (IEC 62368-1)
or PELV (Protective Extra Low Voltage)/SELV (Safety Extra Low
Voltage) standards, have a residual ripple of < 250 mVpp, and PROFINET
must limit the output voltage to a maximum of 40 V in the event
of a fault. S7-1200 with DCM 1271, CM 1243-2
We recommend and 24 V standard power supply unit
AS-Interface
NSB0_02245a
I/O modules
Industrial communication
AS-Interface
Power supply units and data decoupling modules
Data decoupling modules for S7-1200 > DCM 1271 data decoupling module
2
SET, M)
Article No. Price
per PU
DCM 1271 data decoupling module 3RK7271-1AA30-0AA0 1 1 unit 42C
• Max. current: 1 x 4 A
• Removable terminals (included in the scope of supply)
• Dimensions W x H x D (mm): 30 x 100 x 75
3RK7271-1AA30-0AA0
■ Accessories
Version Screw terminals PU PS* PG
(UNIT,
SET, M)
Article No. Price
per PU
Screw terminals (spare part)
• 5-pole, 3RK1901-3MA00 1 1 unit 42C
For AS-i master CM 1243-2 and AS-i DCM 1271 data
decoupling module
• 3-pole, 3RK1901-3MB00 1 1 unit 42C
For AS-i DCM 1271 data decoupling module for
connecting the power supply unit
CM 1243-2 communications module 3RK7243-2AA30-0XB0 1 1 unit 42C
• AS-Interface master for SIMATIC S7-1200
• Corresponds to AS-Interface specification V3.0
• Removable terminals (included in the scope of supply)
• Dimensions W x H x D (mm): 30 x 100 x 75
See also from page 2/37 onwards
3RK7243-2AA30-0XB0
Industrial communication
AS-Interface
Transmission media
AS-Interface shaped cable
■ Overview
To enable use in the most varied ambient conditions (e.g. in an
oily environment), the AS-Interface cable is available in different
materials (rubber, TPE, PUR).
2
Industrial communication
AS-Interface
System components and accessories
Repeaters
■ Overview
• A repeater adds an extra segment to an existing segment.
The extra segment can have a cable length of up to 100 m
2
(without extension plug) or up to 200 m (with an extension
plug in the extra segment)
• Each segment requires a separate AS-i power supply unit
The repeater is automatically supplied with power by the
AS-i power supply units.
• Electrical separation of the two AS-Interface shaped cable
lines, e.g. interfering signals or ground faults are blocked at
the repeater. The wanted signals are prepared by the repeater
and passed on after amplification.
• Slaves can be used on both sides of the repeater because the
repeater has a symmetrical internal structure. The AS-i master
can be positioned before or after the repeater.
AS-Interface repeater • The additional power supply can increase the current infeed for
slaves/sensors and lower the voltage drop on the AS-i cable
The AS-Interface repeater is used to extend the AS-Interface
• Separate display of the correct AS-Interface voltage by means
cable.
of LED for each segment
• In its basic version, an AS-i network comprises one segment
• Installed in K45 module enclosure IP67 with mounting plate
with a maximum cable length of 100 m. An extension plug
(see page 2/79) can be used to increase the cable length for • Easy mounting
a segment to a maximum of 200 m.
• If this is insufficient, however, you can use one or more
repeaters
■ Benefits
• More possibilities of use and greater freedom for plant In safety-related applications the following also applies:
planning through extension of the AS-Interface network • When used without an extension plug, no more than two
• Reduced downtime and servicing times in the event of a fault repeaters are permitted between evaluation unit (e.g.
thanks to separate display of the correct AS-Interface voltage F-CM AS-i Safety ST for ET 200SP) and ASIsafe input slave
for each side or safe output module.
• Increased operational reliability in extensive networks due to • When used with an extension plug, no more than
conditioning and amplification of the wanted signals. one repeater is permitted between the evaluation unit
(e.g. F-CM AS-i Safety ST for ET 200SP) and ASIsafe input
Design of an AS-Interface network with repeaters slave or safe output module.
• Parallel connection of several repeaters possible
(star configuration) Note:
• Combination of series and parallel connection possible The open end of an AS-i bus cable must not be in the
AS-Interface repeater. The AS-Interface shaped cable can
The following conditions apply to enable the signal propagation be terminated by means of a cable end terminator to provide
times to be maintained: degree of protection IP67 where required, see "Miscellaneous
• When used without an extension plug no more than two accessories" on page 2/86.
repeaters are permitted between AS-i master and slave The AS-Interface repeater is not suitable for AS-i Power24V
(repeaters connected in series) networks. It is recommended for use in AS-Interface networks
• When used with an extension plug no more than one repeater with AS-Interface power supply units (e.g. 3RX9501-0BA00).
is permitted between AS-i master and slave
ET 200SP with
CM AS-i Master ST
and optional
F-CM AS-i Safety ST
Industrial communication
AS-Interface
System components and accessories
Repeaters
■ Application
The repeater is used to extend the AS-Interface network. In this In an example configuration with two repeaters and three
case there are AS-Interface slaves and one AS-Interface power extension plugs, the maximum possible size of the AS-Interface
supply unit on each side of the repeater. network is 600 m, see example configuration with extension plug
2
on page 2/79.
As with all AS-Interface networks, any network structure (line,
tree, star) is possible.
■ Accessories
Version Article No. Price PU PS* PG
per PU (UNIT,
SET, M)
3RK1901-1MN00
Industrial communication
AS-Interface
System components and accessories
Extension plugs
■ Overview
Design of an AS-Interface segment with an extension plug
To construct an AS-Interface segment with a cable length of more
2
than 100 m and up to a maximum of 200 m, the extension plug is
installed in a radius of around 10 m at the point of the network
that is furthest from the AS-i power supply unit (tolerance up to
10 m from the end point). The extension plug is not allowed to be
used in AS-Interface networks smaller than 100 m. Generally,
any network structure (line, tree, star) is possible when using the
extension plug. Only one extension plug is required per 200 m
segment even with a tree or star structure.
The extension plug can be combined with the AS-Interface
AS-Interface Extension Plug Compact repeater, see page 2/78.
With the Extension Plug Compact, it is possible to double the cable Note:
length possible in an AS-Interface segment from 100 to 200 m. The open end of an AS-i bus cable must not be in the extension
Only one AS-i power supply unit is needed to supply power to plug. The AS-Interface shaped cable can be terminated by
the slaves on the up to 200 m long segment. means of a cable end terminator to provide degree of protection
IP67 where required, see "Miscellaneous accessories" on
The extension plug suppresses interfering signals that can arise page 2/86.
due to reflection at the end of a long cable. The extension plug
contains no amplification of the wanted signals. The AS-Interface extension plug is not suitable for
AS-i Power24V networks. It is recommended for use in
The extension plug is mounted directly on the AS-Interface AS-Interface networks with AS-Interface power supply units
shaped cable by means of the insulation displacement method (e.g. 3RX9501-0BA00).
and does not require its own power supply.
ET 200SP with
CM AS-i Master ST
and optional
F-CM AS-i Safety ST
Extension
Extension Repeater I/O modules plug Repeater Extension
plug I/O modules I/O modules plug
AS-Interface
■ Accessories
Version Article No. Price PU PS* PG
per PU (UNIT,
SET, M)
3RK1901-1MN00
* You can order this quantity or a multiple thereof.
Illustrations are approximate Siemens IC 10 · 2023 2/79
© Siemens 2023
Industrial communication
AS-Interface
System components and accessories
Addressing units
■ Overview Note:
For operation of the addressing unit on an AS-Interface cable
with connected power supply unit, the following applies:
The AS-Interface addressing unit is suitable for standard
2
■ Benefits
• Increased power supply to the slaves to 150 mA
• Better utilization of the battery capacity thanks to improved
circuitry
• Support for the current AS-i specification V3.0
• Expanded display for simultaneously displaying input and
output states
• Clearly recognizable display of status of digital inputs/outputs
in binary format (0/1), optionally also available as hexadecimal
values
• Intuitive display of analog data either as decimal, hexadecimal
or as a percentage (e.g. 100% corresponds to input/output
The innovated addressing unit for AS-Interface of the AS-i specification value 20 mA)
V3.0
• I/O data of complex slaves (CTT2 profile) can be displayed
The addressing unit is used to assign an address during
commissioning to each AS-Interface slave. The device detects • Decoded display of the input data of safe input slaves,
a connected slave module or a complete AS-i network and including code table
displays the found module in the LCD display. Each address can • Simplification of the operating steps when setting the slave
be individually set using the Up/Down keys. By turning the rotary address with automatic read back of the set address
switch, further commissioning functions are selected intuitively. • Addressing cable, ready for operation even without screwing
The innovative device has been adapted to the current in tight into the M12 socket, thus faster availability of the
AS-i specification V3.0 and can now also handle the I/O data addressing unit
of the latest slaves.
• Proven compact housing with smooth keys and rotary switch
Functionality • Connection of standard AS-i networks possible with 30 V as
• Reading out and adjusting the slave address 0 to 31 or 1A to well as Power24V networks
31A, 1B to 31B, with automatic addressing aid and prevention • Complex slaves with high operating currents can be
of double addresses addressed without external supply
• Reading out the slave profile (IO, ID, ID2) • Longer operating time by automatic shutdown after approx.
• Reading out and adjusting the ID1 code 5 minutes (or approx. 1 minute when data exchange is active)
• Input/output test when commissioning the slaves: Read input after last operation
signals and write outputs with all digital and analog slaves • Can be used with all types of digital and analog slaves
according to AS-Interface specification V3.0, including safe • Comprehensive and fast input/output test of plants, even for
input slaves and complex CTT2 slaves A/B slaves with 4 DI/4 DQ and current analog modules with an
• Measuring the voltage on the AS-Interface cable (measuring A/B address
range from 2 to 35 V) • Faster and more reliable commissioning of the AS-Interface
• Display of the operational current in case of direct connection modules
of an AS-i slave (measuring range from 0 to 150 mA) • One-hand operation possible, with unique selection of
• Storage of complete network configurations (profiles of all the functions
slaves) to simplify the addressing • Connection via M12 socket (pin 1: ASI+; pin 3: ASI-;
• Adjusting the slave parameters for commissioning pins 2, 4, 5: not used)
• Reading out the identification and diagnostics of CTT2 slaves • Universal applicability for all AS-i networks
• Reading out the code table of safe input slaves (ASIsafe)
Industrial communication
AS-Interface
System components and accessories
Addressing units
■ Accessories
Version Article No. Price PU PS* PG
per PU (UNIT,
SET, M)
2
Addressing cable, with M12 plug to M12 socket1) 3RK1902-4PB15-3AA0 1 1 unit 42D
• For addressing slaves with M12 connection,
e.g. K20 or K60R modules or light curtains
• Length 1.5 m, 3-pole, 3 x 0.34 mm2
3RK1902-4PB15-3AA0
AS-Interface M12 3RX feeder 3RX9801-0AA00 1 1 unit 42C
• Transition of AS-Interface cable to a standard round cable
• Insulation piercing method for connection of AS-Interface
cable
3RX9801-0AA00 • M12 socket for connection of standard round cable
• Current-carrying capacity up to 2 A
AS-Interface M12 3RK feeder 3RK1901-2NR10 1 1 unit 42C
• AS-Interface cable transition without Uaux,
with M12 socket
• Insulation piercing method for connection of AS-Interface
cable
3RK1901-2NR10 • M12 socket for connection of standard round cable
M12 cable plug2) 3RK1902-4HB50-5AA0 1 1 unit 42D
• Extruded M12 plug (angled cable outlet 90°),
other cable end open
• Length: 5 m, 5-pole, color: Black
3RK1902-4HB50-5AA0
M12 plug, straight2) 3RK1902-4BA00-5AA0 1 1 unit 42D
• For screw fixing, 5-pole screw terminal, max. 0.75 mm2
• A-coded, max. 4 A
3RK1902-4BA00-5AA0
Addressing cable, with M12 plug to addressing plug Z236A
(hollow plug)3)
• Included in the scope of supply of the addressing unit
• Length 1.5 m
1)
Not included in scope of supply of the 3RK1904-2AB02 addressing unit.
2) For connecting the addressing unit to an AS-i network via AS-Interface
M12 feeder it is necessary to establish a connection by means of
a connecting cable (M12 plug to M12 connector) which must be wired
as follows:
- M12 cable plug: pin 1/core brown M12 plug: pin 1
- M12 cable plug: pin 3/core blue M12 plug: pin 3
- Pin 2, 4, 5 not connected.
3)
Addressing cable available from:
GMC-I Messtechnik GmbH
(see page 16/18).
Industrial communication
AS-Interface
System components and accessories
Analyzer
■ Overview
Connection
2
ET 200SP with
CM AS-i Master ST and
optionally
F-CM AS-i Safety ST
M12 feeder
AS-Interface
NSA0_00359d
AS-Interface analyzer
AS-Interface analyzer PC
The AS-Interface analyzer is used to test AS-Interface networks.
Installation errors, e.g. loose contacts or EMC interference under Connection of AS-Interface analyzer to PC and AS-Interface network
extreme loads, can be revealed by this device. The AS-Interface analyzer follows the communication on the
Thanks to the easy-to-use software the user can assess the AS-Interface network as a passive station. The unit is supplied
quality of complete networks even if he lacks detailed specialist simultaneously from the AS-Interface cable.
knowledge of AS-Interface. In addition it is an easy matter with This analyzer interprets the physical signals on the AS-Interface
the AS-Interface analyzer to create test logs from the records network and records the communication.
produced, thus providing documentation for startups and
service assignments. The data thus obtained are transferred through an RS 232
interface to a PC such as a notebook, for evaluation with the
For advanced AS-Interface users there are trigger functions for supplied diagnostics software.
detailed diagnostics.
■ Benefits
• Simple and user-friendly operation enables diagnostics of
AS-Interface networks without help from specialists
• Speedy troubleshooting thanks to intuitive display in statistics
mode
• Test logs provide verification of the state and quality of the
installation for service and approval
• Recorded logs facilitate remote diagnostics by
Technical Support
• Comprehensive trigger functions enable exact analysis
• Process data can be monitored online
Industrial communication
AS-Interface
System components and accessories
Analyzer
■ Application
Online statistics Data mode
2
Online statistics, overview Presentation of the I/O data: Safety data
Online statistics, details, e.g. here a fault on slave 5 Presentation of the I/O data: Analog values
This mode provides a quick overview of the existing AS-Interface In this mode, the analyzer shows not only the digital input/output
system. The error rates are displayed per slave in a traffic-light values but also the current analog values and the input status of
function (green, yellow, red). the safety slaves.
The bus configuration and the currently transmitted data of
the slaves are shown in a well arranged presentation.
With the expanded statistics function, it is possible to determine
the error rates as the number of transmitted or faulty bus
message frames.
The bundle error overview shows in steps how many multiple
repetitions of message frames occurred in order to enable
a selective and look-ahead assessment of the transmission
quality.
Industrial communication
AS-Interface
System components and accessories
Analyzer
Trace mode Test log
2
Presentation of message frames in trace mode The recorded data of the online statistics are easy to output and
document using a test log. Verification of the state of the plant
The presentation of message frames in the style of a classic can thus be provided for approvals or service assignments.
fieldbus analyzer is indispensable for complex troubleshooting.
Extensive trigger functions and recording and viewing filters are The integrated measurement assistant records the bus signals
available for this purpose. An external trigger input and trigger for a variable duration, thereby triggering creation of an
output round off the scope of functions in order to find even the automatic test log. A standardized quality test of AS-i plants
most difficult errors. is thus possible.
For troubleshooting in connection with ASIsafe applications, Note:
changes of status in the code tables of safety slaves are The AS-Interface analyzer is suitable for standard AS-i networks
identified and assessed. and AS-i Power24V networks (min. operational voltage 20 V).
The AS-i analyzer can be used with an AS-i master in
accordance with AS-Interface specification V3.0 or
a predecessor version.
The analyzer does not automatically decode the process values
for type CTT2 - CTT5 AS-i slaves. As for other slave types, the
message frames are recorded and evaluated in the statistics.
If required, decoding can also be performed by the user manually.
For more information, see
https://support.industry.siemens.com/cs/ww/en/view/109746763.
Note:
Download the current version of the diagnostics software for PC
with Windows operating system, see
https://support.industry.siemens.com/cs/ww/en/view/109750259.
Industrial communication
AS-Interface
System components and accessories
Analyzer
■ Accessories
Version Article No. Price PU PS* PG
per PU (UNIT,
SET, M)
2
AS-Interface M12 3RX feeder 3RX9801-0AA00 1 1 unit 42C
• Transition of AS-Interface shaped cable to a standard
round cable
• Insulation piercing method for connection of AS-Interface
3RX9801-0AA00 cable
• M12 socket for connection of standard round cable
• Current-carrying capacity up to 2 A
• Degree of protection IP67
AS-Interface M12 3RK feeder 3RK1901-2NR10 1 1 unit 42C
• AS-Interface cable transition without Uaux,
with M12 socket
• Insulation piercing method for connection of AS-Interface
cable
3RK1901-2NR10
• M12 socket for connection of standard round cable
• Max. 4 A
• Degree of protection IP67/IP68/IP69 (IP69K)
M12 cable plugs 3RK1902-4HB50-5AA0 1 1 unit 42D
• PUR cable, 5-pole
• Length 5 m
3RK1902-4HB50-5AA0 • Color black
• Extruded M12 plug (angled cable outlet 90°), other cable
end open
Industrial communication
AS-Interface
System components and accessories
Miscellaneous accessories
https://support.industry.siemens.com/cs/ww/en/view/26250840
6ES7194-1KA01-0XA0
AS-Interface sealing caps
For free M12 sockets
• M12
3RK1901- 3RK1901- - Standard version 3RK1901-1KA00 100 10 units 42C
1KA00 1KA01
- Tamper proof 3RK1901-1KA01 100 10 units 42C
• M8 standard version 3RK1901-1PN00 100 10 units 42C
3RK1901-1PN00
AS-Interface M20 seals 3RK1901-1MD00 100 10 units 42C
• For AS-Interface shaped cable
• For insertion in M20 glands
3RK1901-1MD00
Industrial communication
AS-Interface
System components and accessories
Miscellaneous accessories
2
Cable adapters for flat cables
Connection of AS-Interface cable to metric gland with
insulation piercing method
• Continuation using standard cable
- For M16 gland 3RK1901-3QM00 1 1 unit 42C
- For M20 gland 3RK1901-3QM10 1 1 unit 42C
• Continuation using pins
3RK1901-3QM00 - For M16 gland 3RK1901-3QM01 1 1 unit 42C
- For M20 gland 3RK1901-3QM11 1 1 unit 42C
Cable clip for cable adapters 3RK1901-3QA00 100 10 units 42C
3RK1901-3QA00
Cable end terminator 3RK1901-1MN00 1 10 units 42C
For sealing open cable ends of the AS-Interface shaped
cable with IP67
3RK1901-1MN00
Mounting plates
• K45
- For wall mounting 3RK1901-2EA00 1 1 unit 42C
- For DIN-rail mounting 3RK1901-2DA00 1 1 unit 42C
• K60, suitable for all K60 compact modules
- For wall mounting 3RK1901-0CA00 1 1 unit 42C
- For DIN-rail mounting 3RK1901-0CB01 1 1 unit 42C
3RK1901- 3RK1901-
2EA00 0CA00
Sealing set 3RK1902-0AR00 100 5 units 42D
• For K60 mounting plate
• Cannot be used for K45 mounting plate
3RK1902-0AR00 • One set contains one straight and one shaped seal
Control cable, assembled at one end
Angled M12 socket for screw fixing, 4-pole, 4 x 0.34 mm2,
A-coded, black PUR sheath, max. 4 A
3RK1902-4GB50-4AA0
• Cable length 5 m 3RK1902-4GB50-4AA0 1 1 unit 42D
M12 socket, angled 3RK1902-4CA00-4AA0 1 1 unit 42D
For screw fixing, 4-pole screw terminals, max. 0.75 mm2,
A-coded, max. 4 A
3RK1902-4CA00-4AA0
M12 plugs
For screw fixing, 5-pole screw terminals, max. 0.75 mm2,
A-coded, max. 4 A
3RK1902-4BA00-5AA0 • Straight 3RK1902-4BA00-5AA0 1 1 unit 42D
• Angled 3RK1902-4DA00-5AA0 1 1 unit 42D
3RK1902-4DA00-5AA0
Control cable, assembled at one end
Angled M12 plug for screw fixing, 5-pole, 5 x 0.34 mm2,
A-coded, black PUR sheath, max. 4 A
3RK1902-4H...-5AA0 • Cable length 1.5 m 3RK1902-4HB15-5AA0 1 1 unit 42D
• Cable length 5 m 3RK1902-4HB50-5AA0 1 1 unit 42D
• Cable length 10 m 3RK1902-4HC01-5AA0 1 1 unit 42D
Control cable, assembled at both ends 3RK1902-4PB15-3AA0 1 1 unit 42D
3RK1902-4PB15-3AA0 Straight M12 plug, straight M12 socket, for screw fixing,
3-pole, 3 x 0.34 mm2,
A-coded, black PUR sheath, max. 4 A
• Cable length 1.5 m
• Also for addressing AS-i slaves with
M12 bus connection (e.g. K20, K60R compact modules,
M200D motor starters)
Industrial communication
IO-Link
Introduction
Communications overview
■ Overview
More information
Homepage, see www.siemens.com/io-link For brochure, see
2
OpenVPN
RTU3030C
Firewall
PROFINET
Industrial Ethernet
Access Access
Controller point point
Controller PC/PG IWLAN
Notebook RCoax cable Industrial Ethernet
switches
Controller
Control and PC/PG/IPC
Field device for monitoring system Wireless
intrinsically safe area Remote devices
maintenance
access SCALANCE
Numeric SC646-2C
Coupler control
Link
PROFIBUS PA PROFIBUS
ASM456 Field devices
Mobile Optical
Field devices reading
Mobile HMI
SIMOCODE RF185C systems
HMI
pro IO-Link RFID system Access
RFID Optical master
reading IO-Link point
system DP slave Motion control
IO-Link systems systems
IO-Link
AS-i master I/O module AS-i master
IO-Link DP/AS-i Link 20E in ET 200SP in ET 200SP
I/O module AS-Interface
power supply Protection and
Slave monitoring Client
devices module
SINAMICS
drives RFID Compact
Compact Signaling column Protection and RFID system feeder
feeder monitoring system
G_IK10_XX_30049e
devices
AS-Interface
Compact
feeder Field device
Slave Slave
Slave Slave
AS-Interface
Compact Signaling column power supply
feeder
Industrial communication
IO-Link
Introduction
Communications overview
■ Benefits
Engineering Installation and commissioning
• Standardized, open system for greater flexibility • Faster assembly with minimized error rate as a result of
2
(non-Siemens IO-Link devices can be integrated in reduced control current wiring
engineering) • Less space required in the control cabinet
• Uniform, transparent configuring and programming through • Low-cost circuitry where there are several feeders by making
integrated engineering (SIMATIC STEP 7) full use of existing components
• Unassigned SIMATIC function blocks for easy parameter-
ization, diagnostics and read-out of measured values Operation and maintenance
• Efficient engineering thanks to pre-integration into • High transparency in the system right down to field level and
SIMATIC HMI integration into power management systems
• Low error rate in CAD circuit diagram design as a result of • Reduction in downtimes and maintenance times thanks to
reduced control current wiring system-wide diagnostics and faster fault correction
• Support of predictive maintenance
• Shorter changeover times, even for field devices, by means of
parameter and recipe management
■ Application
IO-Link can be used in the following main applications: Integration in STEP 7
• Easy connection of complex IO-Link sensors/actuators with Integration of the device configuration in the STEP 7
a large number of parameters and diagnostics data to the environment guarantees:
control system
• Quick and easy engineering
• Replacement of sensor boxes for connecting binary sensors
with the IO-Link input modules optimized in terms of cabling • Consistent data storage
• Optimized cable connection of switching devices to the • Quick localization and rectification of faults
control system
• Simple transmission of energy values from the device to the
control system for integration into a user program or power
management
In these cases, all the diagnostics data are transmitted to the
higher-level control system through IO-Link. The parameter
settings can be changed during operation.
Industrial communication
IO-Link
Introduction
System components
■ Overview
2
IO-Link master
IC01_00787
IO-Link devices
IO-Link
engineering: Visualization:
SIMATIC SIMATIC HMI
S7-PCT WinCC
S7-300/ S7-1200/
S7-400 S7-1500
controller controller
PROFINET
ET 200SP SIMATIC
with IO-Link master ET 200eco PN
IO-Link
with IO-Link
master
3SU1 ID key-
operated switch
IK10_30141h
Industrial communication
IO-Link
Introduction
System components
IO-Link compatibility Overload relays
IO-Link ensures compatibility between IO-Link-capable A starter combination, for example, consists of one or more
modules and standard modules as follows: SIRIUS 3RT contactors and one 3RB24 electronic overload relay
• IO-Link sensors can generally be operated both on for IO-Link plus its 3RB29 current measuring module.
2
IO-Link modules (masters) and standard input modules. 3RB24 overload relays with IO-Link are basically designed
• IO-Link sensors/actuators as well as today's standard to provide current-dependent protection for loads against
sensors/actuators can be used on IO-Link masters. inadmissibly high temperature rises due to overload, phase
• If conventional components are used in the IO-Link system, asymmetry or phase failure.
then of course only the standard functions are available at Direct-on-line starters can, therefore, as shown in the image,
this point. be connected to the control system via IO-Link without much
wiring. Remote control of connected contactors, current value
Analog signals transmission and immediate remote fault diagnosis are just
Another advantage of IO-Link technology is that analog signals some examples of the large number of functions that can be
are already digitized in the IO-Link sensor itself and are digitally implemented with this device.
transmitted via IO-Link communication. As the result, faults are It is also possible to directly address a drive on-site via IO-Link
prevented and there is no extra cost for cable shielding. using the optional handheld device.
Enhancement with IO-Link input modules
IO-Link compatibility also permits connection of standard Programmable logic
sensors/actuators, i.e. conventional sensors/actuators can also controller (PLC)
CPU S7-1200 SM 1278 4 x IO-Link master
be connected to IO-Link. This is particularly cost-effective with
the IO-Link input modules, which allow several sensors to be Feeder
connected at one time via a cable to the controller.
3RB29
current
SIRIUS 3RB24 measuring
electronic overload relay module
and 3RA69 handheld device
IC01_00295
Motor
Point-to-point Classic
connection wiring
through IO-Link
IO-Link
IO-Link Sensor
I/O module box
NSA0_00489f
Industrial communication
IO-Link
Introduction
System components
Monitoring relays
By using monitoring relays with IO-Link it is now possible to
send data that has already been recorded and evaluated in
the devices directly to the controller. This avoids the use of
2
duplicated sensors.
3 1
3UG46
monitoring 3UG48
relay monitoring
Feeder relay Feeder
ET 200SP
with IO-Link
master ET 200SP
with IO-Link master
1 Analog 2 IO-Link
signal 3UG46 3UG46
converter monitoring monitoring
relay relay 1 2
3UG48 3UG48
monitoring monitoring
relay relay
Current
trans-
former
IC01_00003a IC01_00004a
Motor Motor
1 Signaling of limit value violation plus measurement data 1 Signaling of limit value violation plus measurement data
transmission to PLC transmission to PLC
2 Autonomous operation without PLC 2 Autonomous operation without PLC
3 Signaling of limit value violation to PLC
Possibilities for interfacing conventional 3UG46 monitoring relays Possibilities of interfacing 3UG48 monitoring relays for IO-Link
(in comparison with 3UG48)
Industrial communication
IO-Link
Introduction
System components
Wireless communication
Using an upstream IWLAN client module, such as The individual diagnostics options offered by the various IO-Link
SCALANCE W722-1 RJ45, allows IO-Link to be integrated into devices provide greater transparency for the production
the PROFINET world via a distributed I/O. Possible uses include process. Just like the parameter data for a device, these
2
acting as an alternative to fault-prone cable carrier or collector diagnostics data can be evaluated remotely using the
wire technology. possibilities offered by SIMATIC. This supports remote
maintenance down to the lowest level in the field.
SCALANCE
W722-1 RJ45
ET 200SP
with IO-Link master
Industrial Ethernet
SIRIUS
3RA2 load feeders
with 3RA27 Control room
function modules
SIMATIC HMI
KTP 1500 Basic
SIMATIC
S7-300
IO-Link
Industrial Ethernet
SCALANCE
IC01_00198c
W786-1 RJ45
access point
Industrial communication
IO-Link
Introduction
System components
IO-Link components
IO-Link masters IO-Link devices (continued)
Masters Monitoring with IO-Link
IO-Link master module for S7-1500 SIRIUS 3RR24 monitoring relays for mounting on
2
Industrial communication
IO-Link
Introduction
System components
IO-Link RFID systems IO-Link software
SIMATIC RF200 RFID system in the HF range S7-PCT (Port Configuration Tool)
SIMATIC RF210R, SIMATIC RF220R, SIMATIC RF240R, Engineering software for configuring the IO-Link master
SIMATIC RF250R, SIMATIC RF260R products modules for SIMATIC S7-1200, ET 200SP, ET 200MP,
2
• Simple identification tasks such as reading an ET 200pro, ET 200eco PN and ET 200AL
ID number (UID) • Available as a stand-alone version or integrated into
• Reading of user data S7-PCT STEP 7 (V5.5 SP1 and higher) and TIA (V12 and higher)
RFID system • Writing of user data • Engineering of the IO-Link devices connected to the
for IO-Link • No RFID-specific programming, ideal for those new master
to RFID • Monitoring of the process image of the IO-Link devices
• Simple connection via master modules for IO-Link, • Open interface for importing further IODDs
such as SIMATIC S7-1200, ET 200SP, ET 200pro, • Freely available for download from
ET 200eco PN and ET 200AL Industry Online Support, see
• Use with the tried and tested ISO 15693 transponders https://support.industry.siemens.com/cs/ww/en/view/32469496
(MDS xxx) Library for IO-Link (LIOLink)
See Catalog ID 10
This library provides blocks and PLC data types to
IO-Link Device Description (IODD) enable communication between the SIMATIC controller
IODD files and the IO-Link master or IO-Link device.
These files provide the device description for IO-Link • Freely available for download from
devices. Industry Online Support, see
https://support.industry.siemens.com/cs/ww/en/view/82981502
• Comprehensive IODD catalog of SIEMENS IO-Link
devices Library for
• Freely available for download from IO-Link (LIOLink)
Industry Online Support, see WFB50001 Application of the device-specific blocks for IO-Link
IODD files for https://support.industry.siemens.com/cs/ww/en/ps/15851 "IO_LINK_DEVICE"
IO-Link EN END This application shows on a specific example how
REQ DONE_VALID
IODDfinder ID BUSY easy it is to connect Siemens IO-Link devices to
CAP ERROR
RD_WR STATUS a SIMATIC S7 CPU using the library for
The entire world of IO-Link under one roof PORT IOL_STATUS
IO-Link (LIOLink).
IOL_INDEX RD_LEN
The IODDfinder is a service provided by the IO-Link IOL_SUBINDEX
• Freely available for download from
IODDfinder for LEN
IC01_00467
community. It is a central cross-vendor database for RECORD_IOL_
Industry Online Support, see
IO-Link descriptive files (IODDs). In addition, the platform DATA
https://support.industry.siemens.com/cs/ww/en/view/90529409
provides an overview of the available IO-Link devices. IO-Link device
function block
For more information, see
https://ioddfinder.io-link.com/#/.
Industrial communication
IO-Link
Introduction
IO-Link specification
■ Overview
Principles of the IO-Link specification Device data
According to the IO-Link specification, communication functions Device data can be parameters, identification data and
2
Industrial communication
IO-Link
Masters
IO-Link master module for S7-1500 > CM 8xIO-Link
■ Overview ■ Design
• Fastening to the S7-1500 DIN rail with a single screw
• 40-pole front connector, optionally with screw terminals or
2
push-in terminals
• Front connector with expandable cable compartment
• Included in the scope of supply:
- One U connector
- Front door
■ Function
Overview of functions
• Suitable for connecting up to 8 IO-Link devices (three-wire
connection) or 8 standard sensors
• IO-Link master according to IO-Link specification V1.1
• Data transmission rates COM1 (4.8 kBd), COM2 (38.4 kBd),
COM3 (230.4 kBd)
• Parameterizable diagnostics can be set for each channel
CM 8xIO-Link master • Master backup with "IO_Link_MASTER_8" function block
• Communications module for connecting up to 8 IO-Link • Replacement of the IO-Link device (for V1.1 devices only)
devices (three-wire connection) or 8 standard sensors
• Support for firmware updating of IO-Link devices
• Can be used directly downstream of an S7-1500 CPU or
distributed in ET 200MP via PROFINET or PROFIBUS • Variable address range for I/O data with up to 240 byte inputs
and 240 byte outputs;
• Powerful diagnostics functions facilitate preventive expansion limits:
maintenance to avoid plant standstills - Max. 32 bytes of input data and 32 bytes of output data
• Simple replacement of sensors/actuators without time- per port
consuming parameterization - Max. 240 bytes of input data and 240 bytes of output data
per module
■ Application • Port Qualifier Information (PQI)
IO-Link makes it easy to change the parameters for manu- • IO-Link port configuration with S7-PCT
facturing and processing different product versions and • IO-Link port configuration with STEP 7 or GSD (without S7-PCT)
batches, even during CPU runtime, down to the sensor/actuator • Standard system functions of SIMATIC ET 200MP:
level. Easy, much more detailed diagnostics are also possible - Identification and maintenance data IM0
down to the sensor or actuator, including remote diagnostics. - Firmware update
The CM 8xIO-Link enables direct connection of up to 8 IO-Link - Unequivocal, front-side module inscription
devices directly to SIMATIC S7-1500 and ET 200MP. This makes
external stations unnecessary.
■ Configuration
This results in savings on wiring, engineering and commissioning,
because everything can be configured centrally with the CPU. The SIMATIC S7-1500 IO-Link master of the S7-1500 can be
conveniently configured using the graphical user interface in the
free S7 Port Configuration Tool (S7-PCT, V3.5 and higher, SP1).
In addition to this configuration, commissioning without S7-PCT
is also possible. In this case, the port is configured by means of
either the TIA Portal or GSD file. The following port modes are
supported:
• Operation in "IO-Link autostart" mode (default)
• Operation in "IO-Link manual" mode
• Operation as DI
• Deactivated
6ES7547-1JF00-0AB0
For more information, see https://mall.industry.siemens.com/mall/en/ww/Catalog/Products/10355273.
Industrial communication
IO-Link
Masters
IO-Link master module for S7-1200 > SM 1278 4xIO-Link master
■ Overview ■ Design
• Expansion limits
- Cable length: Max. 20 m
- Max. 32 bytes of input data and 32 bytes of output data
2
per port
- Max. 32 bytes of input data and 32 bytes of output data
per module
LED displays
• DIAG: Operating state display (green/red) of the module
• C1..C4: Port status display (green) for ports 1, 2, 3 and 4
• Q1..Q4: Channel status display (green) for ports 1, 2, 3 and 4
• F1..F4: Port error display (red) for ports 1, 2, 3 and 4
Depending on the CPU type used, up to 8 SM 1278 units can be
used on one S7-1200 CPU.
■ Function
Supported functions
SM 1278 4xIO-Link master • I&M identification data
Module for connecting up to four IO-Link devices in accordance • Firmware update
with the IO-Link specification V1.1. The IO-Link parameters are • SIO Mode (standard IO mode)
configured by means of the Port Configuration Tool (PCT) with
• IO-Link parameter assignment with the S7-PCT interface
version V3.2 and higher.
configuration tool, TIA Portal from V13 and an
S7-1200 CPU V4.0 or higher
■ Application Supported data transmission rates
The SM 1278 module enables an exchange of data with up to • COM1 (4.8 kBd)
four external IO-Link devices through one three-wire cable each
or four standard actuators or standard encoders. Control can • COM2 (38.4 kBd)
be flexibly adapted to the communication partners using the • COM3 (230.4 kBd)
comprehensive parameter assignment options. Since IO-Link
is compatible with standard sensors, commercially available
sensors compliant with IEC 61131 Type 1 can also be operated
on the IO-Link master.
6ES7278-4BD32-0XB0
■ Accessories
Version Article No. Price PU PS* PG
per PU (UNIT,
SET, M)
6ES7292-1AG30-0XA0
For more information, see https://mall.industry.siemens.com/mall/en/ww/Catalog/Products/10231178.
Industrial communication
IO-Link
Masters
IO-Link master module for ET 200SP > CM 4xIO-Link V1.1 Standard
■ Overview
• ET 200SP system functions supported
- Exchange of IO-Link device parameters (V1.1 devices only)
and of IO-Link master parameters without a PG including
2
automatic backup recovery without an engineering tool by
means of redundant parameter storage on the e-coding
element
- Reparameterization during ongoing operation
- I&M identification data
- Firmware update
- PROFIenergy
• Can be plugged onto type A0 BaseUnits (BU) with automatic
e-coding
• LED displays
- DIAG: Operating state display (green/red) of the module
- C1..C4: Port status display (green) for ports 1, 2, 3 and 4
- Q1..Q4: Channel status display (green) for ports 1, 2, 3 and 4
- F1..F4: Port error display (red) for ports 1, 2, 3 and 4
CM 4xIO-Link - PWR: Supply voltage display (green)
• CM 4xIO-Link communications module • Informative front-side module inscription
Serial communications module for connecting up to - Plain-text marking of the module type and function class
four IO-Link devices in accordance with the IO-Link - 2D matrix code (article and serial number)
specification V1.0 and V1.1. The IO-Link parameters are - Circuit diagram
configured by means of the Port Configuration Tool (PCT) - CM module class color coding: Silver
with version V3.0 and higher. - Hardware and firmware version
• Time-based IO - Complete article number
Time-based IO ensures that signals are output with a precisely • Optional accessories
defined response time. By combination of inputs and outputs, - Labeling strips
products passing by, for example, can be measured exactly - Reference identification label
or liquids can be perfectly dosed. - Color-coded label with color code CC04
• Supported data transmission rates • Optional system-integrated shield connection
- COM1 (4.8 kBd)
- COM2 (38.4 kBd)
- COM3 (230.4 kBd)
• Expansion limits
- Cable length: Max. 20 m
- Max. 32 bytes of input data and 32 bytes of output data
per port
- Max. 144 bytes of input data and 128 bytes of output data
per module
■ Application
• The CM 4xIO-Link communications module enables an • Since IO-Link is compatible with standard sensors,
exchange of data with up to 4 external IO-Link devices commercially available sensors compliant with IEC 61131
through one three-wire cable each. Type 1 can also be operated on the IO-Link master.
• Control can be flexibly adapted to the communication
partners using the comprehensive parameter assignment
options.
6ES7137-6BD00-0BA0
For more information, see https://mall.industry.siemens.com/mall/en/ww/Catalog/Products/10205200.
Industrial communication
IO-Link
Masters
IO-Link master module for ET 200pro > 4 IO-Link HF
■ Overview
• 45-mm-wide 4 IO-Link HF solid-state module
• 4 IO-Link ports according to IO-Link specification V1.1
2
• Port class B
• The IO-Link parameters are configured using the Port
Configuration Tool (S7-PCT), version V3.4 and higher
4 IO-LINK HF
■ Application
The 4 IO-Link HF solid-state module enables the exchange of Since IO-Link is compatible with standard sensors, commercially
data with up to 4 IO-Link devices. available sensors compliant with IEC 61131 Type 1 can also be
operated on the IO-Link master.
■ Design
The 4 IO-Link HF solid-state module is used together with the IO-Link devices (e.g. sensors) with a class A port are
CM IO-LINK 4 X M12 P connection module. Sensors and interconnected by means of a three-wire cable. IO-Link devices
actuators are integrated using commercially available 3- or that require an additional supply voltage and have a class B port
5-pole M12 plugs on the CM IO-Link 4 X M12 P. (e.g. actuators) are interconnected by means of a five-wire cable.
6ES7147-4JD00-0AB0
■ Accessories
Version Article No. Price PU PS* PG
per PU (UNIT,
SET, M)
Industrial communication
IO-Link
Masters
IO-Link master module for ET 200eco PN > IO-Link master modules
■ Overview
IO-Link master with 2 x M12-L coded power connector and
45-mm width
2
• IO-Link communications modules for connecting up to
8 IO-Link devices
• IO-Link master with 4 x port class A and 4 x port class B and
additional 4 digital inputs
• The IO-Link specifications V1.0 and V1.1 are supported.
IO-Link master with 2 x M12-A coded power connector and
30-mm width
• IO-Link communications modules for connecting up to
4 IO-Link devices
• IO-Link master with 4 x port class B
• The IO-Link specifications V1.0 and V1.1 are supported.
IO-Link master with 2 x M12-A coded power connector
and 60-mm width
• IO-Link communications modules for connecting up to
4 IO-Link devices
ET 200eco PN IO-Link master modules • IO-Link master with 4 x port class A and additional 8 digital
inputs and 4 digital outputs
• The IO-Link specification V1.0 is supported.
■ Application
IO-Link enables easy integration of sensors and actuators Since IO-Link is compatible with standard sensors,
from different manufacturers. ET200eco PN IO-Link master commercially available sensors compliant with IEC 61131
I/O devices enable an exchange of data with up to 4 or 8 IO-Link Type 1 can also be operated on the IO-Link master.
devices. With a high degree of protection, ruggedness and small
IO-Link devices (e.g. sensors) with a class A port are inter- dimensions, the IO-Link master I/O devices are especially well-
connected by means of a three-wire cable. IO-Link devices that suited for use at the machine level in confined spaces. They
require an additional supply voltage and have a class B port have adjustable parameters and diagnostics functions and can
(e.g. actuators) are interconnected by means of a five-wire cable. therefore be flexibly adapted to individual process requirements.
■ Function
In addition to the general functions of the ET 200eco PN • Expansion limits
I/O system, the IO-Link masters according to the IO-Link - Cable length to the IO-Link device: Max. 20 m
specification V1.1 have some further functions: - Max. 32 bytes of input data and 32 bytes of output data
• Supported data transmission rates of the IO-Link per IO-Link port
communication • Automatic backup of device parameters when the
- COM1 (4.8 kBd) IO-Link device is replaced (V1.1 devices only)
- COM2 (38.4 kBd) • Reparameterization of the device during operation using
- COM3 (230.4 kBd) a PLC function block
• Master backup using a PLC function block
• Support for firmware updates of IO-Link devices
• Configuration using a GSD file or S7-PCT
Industrial communication
IO-Link
Masters
IO-Link master module for ET 200AL > CM IO-Link
6ES7147-5JD00-0BA0
For more information, see https://mall.industry.siemens.com/mall/en/ww/Catalog/Products/10233997.
* You can order this quantity or a multiple thereof.
2/102 Siemens IC 10 · 2023 Illustrations are approximate
© Siemens 2023
Industrial communication
IO-Link
IO-Link digital modules
IO-Link I/O modules
■ Overview
The IO-Link communication standard enables and standardizes
communication between machine and plant control systems on
one hand and sensors, actuators and other field devices on
2
the other.
The IO-Link I/O modules permit simple connection of binary
standard sensors and actuators and the signals and power
supply are transmitted via IO-Link (IO-Link master).
The IO-Link IO modules can be connected to any IO-Link master
and distributed I/O units that are independent of the fieldbus can
be built. The universal deployability of the IO-Link DIQ I/O
modules provides additional versatility.
With the ET 200AL IO-Link I/O modules, a rounded portfolio of
digital input, digital output and digital input/output modules is
available in the design and with the ET 200AL system features.
■ Application
IO-Link can provide advantages as a communications system, I/O station, with which distributed signals can be detected and
e.g. when complex sensors and actuators are to be used. These output in the plant or machine.
IO-Link devices can be connected via an IO-Link master and be
integrated into the automation system with reduced effort, The following IO-Link I/O modules are available:
e.g. for cabling. • IO-Link, digital input module DI 8 x 24 V DC, 8 x M8
• IO-Link, digital input module DI 16 x 24 V DC, 8 x M12
If such an IO-Link master is available, further binary
sensor/actuator signals can be integrated in the field via the • IO-Link, digital output module DQ 8 x 24 V DC/2 A, 8 x M12
IO-Link I/O modules without great effort. IO-Link masters can • IO-Link, digital input/output module
be expanded with the IO-Link I/O modules to form a modular DIQ 4+DQ 4 x 24 V DC/0.5 A
• IO-Link, digital input/output module DIQ 16 x 24 V DC/0.5 A
■ Function
• Standardized display and diagnostics concept: Engineering
- Channel status display for signal status log. "0" and log. "1"
(green LED) The engineering of the IO-Link I/O modules is performed
- Module status display (DIAG, red/green LED) via IO-Link engineering of the relevant IO-Link master.
- Display for monitoring the load voltage 2L+ (PWR, green LED, For this purpose, one device description file (IODD)
only modules with outputs) per IO-Link I/O module is provided.
• Supported functions:
- Channel-specific parameterization
- Detailed module-level diagnostics and diagnostic interrupt
- Safety-related tripping of digital outputs according to
IEC 62061 (SILCL2) and ISO 13849-1 (Cat 3/PL d)
- IO-Link V1.1
- Support for the "general profile" of IO-Link
- Firmware update
Industrial communication
IO-Link
IO-Link digital modules
IO-Link I/O modules
■ Accessories
Version Article No. Price PU PS* PG
per PU (UNIT,
SET, M)
2
3RK1902-4DA00-5AA0
Control cable
Assembled at one end with 1 x M12 angled plug, 5-pole,
5 x 0.34 mm², A-coded, max. 4 A, PUR sheath, black
3RK1902-4H...-5AA0 • Cable length 5 m 3RK1902-4HB50-5AA0 1 1 unit 42D
• Cable length 10 m 3RK1902-4HC01-5AA0 1 1 unit 42D
AS-Interface sealing caps
• For free M12 sockets 3RK1901-1KA00 100 10 units 42C
• For free M8 sockets 3RK1901-1PN00 100 10 units 42C
3RK1901-1KA00
3RK1901-1PN00
For more information, see https://mall.industry.siemens.com/mall/en/ww/Catalog/Products/10383153.
Price groups
PG 41B, 41E, 41H, 42F
3/2 Introduction
3
3/18 SIRIUS 3RT contactors, 3-pole
up to 250 kW
Accessories for SIRIUS 3RT contactors
and SIRIUS 3RH2 contactor relays
3/69 - General data
3/81 - Auxiliary switches, instantaneous
NEW NEU
Siemens IC 10 · 2023
© Siemens 2023
Introduction
■ Overview
AC-3/AC-3e
AC-3e
le
3
po
3-
3RT12 3TF6
500 A/250 kW 820 A/450 kW
AC-3/AC-3e
AC-3e
le
po
3-
3RT20 3RT10
110 A/55 kW 500 A/250 kW
AC-1
le
po
3-
3RT24 3RT14
160 A 690 A 2 650 A
AC-1
le
po
4-
3RT23 3RT13
160 A 525 A
AC- 6b
le
po
3-
3RT26
151 A/100 kvar
AC-3
IC01_00563b
le
po
4-
3RT25
80 A/37 kW
Introduction
More information
Homepage, see www.siemens.com/sirius Conversion tool, see www.siemens.com/conversion-tool
Industry Mall, see www.siemens.com/product?3RT_3TK_3TC TIA Selection Tool Cloud (TST Cloud), see
www.siemens.com/tstcloud/?node=Contactor
3
Size S00 S0
Type 3RT201 3RT202
3RT20 contactors
Type 3RT2015 3RT2016 3RT2017 3RT2018 3RT2023 3RT2024 3RT2025 3RT2026 3RT2027 3RT2028
AC, DC operation (p. 3/47, 3/52 ... 3/55) (p. 3/48, 3/49, 3/56 ... 3/58, 3/60)
AC-3 and AC-3e
Ie/AC-3/AC-3e/400 V A 7 9 12 16 9 12 17 25 32 38
400 V kW 3 4 5.5 7.5 4 5.5 7.5 11 15 18.5
230 V kW 1.5 2.2 3 4 2.2 3 4 5.5 7.5 11
500 V kW 6 7.7 9.2 12.4 9 12 17 18 32 32
690 V kW 4 5.5 5.5 7.5 7.5 7.5 11 11 18.5 18.5
1 000 V kW -- -- -- -- -- -- -- -- -- --
AC-4 (at Ia = 6 x Ie)
400 V kW 3 4 4 5.5 4 5.5 7.5 7.5 11 11
400 V (200 000 operating cycles) kW 1.15 2 2 2.5 2 2.6 3.5 4.4 6 6
AC-1 (40 °C, 690 V)
Ie A 18 22 22 22 40 40 40 40 50 50
Note:
Safety characteristics for contactors, see "Standards and
approvals", page 16/9.
Introduction
3
Size S2 S3
Type 3RT203 3RT204
3RT20 contactors
Type 3RT2035 3RT2036 3RT2037 3RT2038 3RT2045 3RT2046 3RT2047
AC, DC operation (p. 3/50, 3/59, 3/61) (p. 3/51, 3/59, 3/63)
AC-3 and AC-3e
Ie/AC-3/AC-3e/400 V A 41 50 65 80 80 95 110
400 V kW 18.5 22 30 37 37 45 55
230 V kW 11 15 18.5 22 22 22 30
500 V kW 41 51 65 80 80 95 110
690 V kW 22 22 37 45 55 75 90
1 000 V kW -- -- -- -- 37 37 37
AC-4 (at Ia = 6 x Ie)
400 V kW 18.5 22 30 37 37 45 55
400 V (200 000 operating cycles) kW 11.6 12.6 14.7 15.8 17.9 22 24.3
AC-1 (40 °C, 690 V)
Ie A 60 70 80 90 125 130 130
Accessories for contactors
Auxiliary • On the front 3RH29, 3RA28 (p. 3/87 ... 3/95) 3RH29, 3RA28 (p. 3/87 ... 3/95)
switches • Lateral 3RH29 (p. 3/91 ... 3/94) 3RH29 (p. 3/91 ... 3/94)
Function • Direct-on-line starting 3RA283. (p. 3/100) 3RA283. (p. 3/100)
modules • IO-Link, AS-Interface 3RA271.-.AA00 (p. 3/101, 3/102) 3RA271.-.AA00 (p. 3/101, 3/102)
Surge suppressors 3RT2936 (p. 3/97, 3/98) 3RT2936, 3RT2946 (p. 3/97, 3/98)
Terminal covers 3RT2936-4EA2 (p. 3/112) 3RT2946-4EA2 (p. 3/112)
3RU2 and 3RB overload relays
3RU thermal overload relays 3RU2136 11 ... 80 A (p. 7/90) 3RU2146 28 ... 100 A (p. 7/90)
3RB electronic overload relays
• For standard applications 3RB3036, 12.5 ... 80 A (p. 7/102 ... 7/104) 3RB3046, 12.5 ... 115 A (p. 7/102 ... 7/104)
3RB3133 3RB3143
• For High-Feature applications 3RB22, 3RB23 and 3RB24 (p. 7/125, 7/133) 3RB22, 3RB23 and 3RB24 (p. 7/125, 7/133)
with current measuring with current measuring
module 3RB2906-2JG1 (p. 7/137) module 3RB2906-2JG1 (p. 7/137)
10 ... 100 A 10 ... 100 A
3RV20 motor starter protectors
Motor starter protectors 3RV2031, 3RV2032 9.5 ... 80 A (p. 7/30) 3RV2041, 3RV2042 28 ... 100 A (p. 7/30)
Link modules 3RA2931 (p. 7/61) 3RA1941 (p. 7/61)
3RA23 reversing contactor assemblies
Complete units Type 3RA2335 3RA2336 3RA2337 3RA2338 3RA2345 3RA2346 3RA2347
(p. 3/151) (p. 3/152)
400 V kW 18.5 22 30 37 37 45 55
Assembly kits/wiring modules 3RA2933-2AA. (p. 3/104) 3RA2943-2AA. (p. 3/104)
Function modules 3RA271.-.BA00 (p. 3/101) 3RA271.-.BA00 (p. 3/101)
Mechanical interlocks 3RA2934-2B (p. 3/108) 3RA2934-2B (p. 3/108)
3RA24 contactor assemblies for star-delta (wye-delta) starting
Complete units Type 3RA2434 3RA2435 3RA2436 3RA2437 3RA2444 3RA2445 3RA2446
(p. 3/169) (p. 3/170)
400 V kW 22/30 37 45 55 55 75 90
Assembly kits/wiring modules 3RA2933-2BB./-2C (p. 3/105) 3RA2943-2BB./-2C (p. 3/105)
Function modules 3RA271.-.CA00 (p. 3/101) 3RA271.-.CA00 (p. 3/101)
Note:
Safety characteristics for contactors, see "Standards and
approvals", page 16/9.
Introduction
3
Size S6 S10 S12
Type 3RT105 3RT1.6 3RT1.7
3RT10 contactors · 3RT12 vacuum contactors
Type 3RT1054 3RT1055 3RT1056 3RT1064 3RT1065 3RT1066 3RT1075 3RT1076
AC, DC operation (p. 3/64 ... 3/66) (p. 3/64 ... 3/66) (p. 3/64 ... 3/66)
Type -- -- -- 3RT1264 3RT1265 3RT1266 3RT1275 3RT1276
(p. 3/130) (p. 3/130)
AC-3 and AC-3e
Ie/AC-3/AC-3e/400 V A 115 150 185 225 265 300 400 500
400 V kW 55 75 90 110 132 160 200 250
230 V kW 37 45 55 55 75 90 132 160
500 V kW 75 90 132 160 160 200 250 315 (355)1)
690 V kW 110 132 160 On request On request On request 400 400 (500)1)
1 000 V kW 75 90 90 90 (315)1) 132 (355)1) 132 (400)1) 250 (560)1) 250 (710)1)
AC-4 (at Ia = 6 x Ie)
400 V kW 55 75 90 110 132 160 200 250
400 V (200 000 operating kW 29 38 45 54 (78)1) 66 (93)1) 71 (112)1) 84 (140)1) 98 (161)1)
cycles)
AC-1 (40 °C, 690 V)
Ie A 160 185 215 275 (330)1) 330 330 430 (610)1) 610
3RT14 AC-1 contactors
Type 3RT1456 (p. 4/17, 4/18) 3RT1466 3RT1467 (p. 4/17, 4/18) 3RT1476
Ie/AC-1/40 °C/ 690 V A 275 400 500 690
Accessories for contactors
Auxiliary • On the front 3RH19, 3RT1926 (p. 3/90, 3/96)
switches • Lateral 3RH19 (p. 3/92 ... 3/94)
Surge suppressors 3RT1956-1C (RC element) (p. 3/98)
Terminal covers 3RT1956-4EA. (p. 3/112) 3RT1966-4EA. (p. 3/112)
Box terminal blocks 3RT1955-4G, 3RT1956-4G (p. 3/110) 3RT1966-4G (p. 3/110)
3RB2 overload relays
3RB electronic overload relays
• For standard applications 3RB2056 50 ... 200 A (p. 7/114, 7/115) 3RB2066 55 ... 250 A or 160 ... 630 A
3RB2153 50 ... 200 A (p. 7/116) 3RB2163 55 ... 250 A or 160 ... 630 A
• For High-Feature applications 3RB22, 3RB23 and 3RB24 (p. 7/125, 7/133) 3RB22, 3RB23 and 3RB24 (p. 7/125, 7/133)
with current measuring with current measuring module
module 3RB2956-2TH2 (p. 7/137) 3RB2966-2WH2 (p. 7/137)
20 ... 200 A 63 ... 630 A
3VA2 molded case motor starter protectors
Molded case motor starter (See Catalog LV 10)
protectors
• for 3RT10 3VA21 3VA22 3VA22 3VA23 3VA23 3VA24 3VA24 3VA25
• for 3RT12 3VA21 3VA22 3VA22 3VA23 3VA23 3VA24 3VA24 3VA25
Reversing contactor assemblies2)
Complete units Type --
400 V kW 55 75 90 110 132 160 200 250
Assembly kits/wiring modules 3RA1953-2A (p. 3/104) 3RA1963-2A (p. 3/104) 3RA1973-2A (p. 3/104)
Mechanical interlocks 3RA1954-2A (p. 3/108)
Contactor assemblies for star-delta (wye-delta) starting2)
Complete units Type --
400 V kW --
Assembly kits/wiring modules 3RA1953-2B (p. 3/106) 3RA1963-2B (p. 3/106) 3RA1973-2B (p. 3/106)
1) Value applies for 3RT12 contactors. Note:
2)
Contactor assemblies for customer assembly:
- Reversing contactor assemblies, see pages 3/154 to 3/156, Safety characteristics for contactors, see "Standards and
- Contactor assemblies for star-delta (wye-delta) starting, approvals", page 16/9.
see pages 3/172 to 3/177.
Introduction
3
Size 14 14
Type 3TF68 3TF69
3TF68/3TF69 vacuum contactors
Type 3TF68 3TF69
(p. 3/131, 3/132) (p. 3/131, 3/132)
AC-3 and AC-3e
Ie/AC-3/AC-3e/690 V A 630 820 (630)1)
400 V kW 335 450 (335)1)
230 V kW 200 260 (200)1)
690 V kW 600 800 (600)1)
1 000 V kW 600 800
AC-4 (at Ia = 6 x Ie)
400 V kW 355 400
400 V (200 000 operating kW 168 191
cycles)
AC-1 (40 °C, 690 V)
Ie A 700 910
Accessories for contactors
Auxiliary switches
• Lateral 3TY7561 (p. 3/133)
Surge suppressors 3TX7572 (p. 3/134)
Terminal covers 3TX7686, 3TX7696 (p. 3/134)
3RB2 overload relays
3RB electronic overload relays
• For standard applications 3RB2066, 55 ... 250 A (p. 7/114, 7/115) 3RB22, 3RB23 and 3RB24 (p. 7/125, 7/133)
3RB2163 or (p. 7/116) with current measuring module
160 ... 630 A 3RB2906-2.G1 (p. 7/137)
• For High-Feature applications 3RB22, 3RB23 and 3RB24 (p. 7/125, 7/133) with 3UF series transformer
with current measuring up to 820 A
module 3RB2966-2WH2 (p. 7/137)
63 ... 630 A 63 ... 820 A
3VA2 molded case motor starter protectors
Molded case motor starter 3VA25 (See Catalog LV 10)
protectors
Reversing contactor assemblies2)
Complete units Type --
400 V kW 335
Assembly kits/wiring modules 3TX7680-1A (p. 3/135)
Mechanical interlocks 3TX7686-1A (p. 3/135)
Contactor assemblies for star-delta (wye-delta) starting2)
Complete units Type --
400 V kW 710
Assembly kits/wiring modules 3TX7680-1B (p. 3/135)
1)
Value applies for utilization category AC-3e. Note:
2)
Contactor assemblies for customer assembly:
- Reversing contactor assemblies, see page 3/157, Safety characteristics for contactors, see "Standards and
- Contactor assemblies for star-delta (wye-delta) starting, see page 3/178. approvals", page 16/9.
Introduction
Connection methods
The 3RT contactors are available with screw terminals (box
terminals or flat connectors) or with spring-loaded terminals.
The 3TG10 power relays/miniature contactors are available with
screw terminals or flat connectors.
Screw terminals
3
Type 3TG10 Spring-loaded terminals
3TG10 power relays/miniature contactors
Number of main contacts 4 Flat connectors
AC, DC operation (p. 3/138)
AC-1 The terminals are indicated in the corresponding
Ie at 400 V 55 °C A 20 tables by the symbols shown on orange backgrounds.
P at 400 V kW 13
Voltage data
At 230 V kW 7.5
AC-3 The data for 3-phase power systems according to IEC 60947-4-1
Ie up to 400 V A 8.4 are valid for the following line system configurations:
.
IC01_00703
IC01_00709
V V V
230 -- 230
400 230/400 400
440 260/440 440
500 -- 500
690 400/690 690 (only from size S3)
1 000 -- 1 000
-- Not specified
■ Overview
The SIRIUS family of controls
The SIRIUS modular system with its components for the
switching, starting, protection and monitoring of motors and
industrial systems stands for the fast, flexible and space-saving
construction of control cabinets.
11 13
12
14
17
2 1 16
19
1
6 2
7
8 18
IC01_00614d
3 4
5
9
17
14
15
10
2 2-pole auxiliary switch, laterally mountable 12 Star jumper, 3-pole, without connecting terminal
3 1-pole auxiliary switch, for snapping onto the front, 13 Link for paralleling, 3-pole, with connecting terminal
cable entry from the top
14 Solder pin adapter
4 2-pole auxiliary switch, for snapping onto the front, 15 Connection module (adapter and connector) for contactors
cable entry from the bottom with screw terminals
5 4-pole auxiliary switch, for snapping onto the front 16 Safety main current connector for two contactors
6 3RA27 function module for AS-Interface Assembly kit 3RA2913-2AA1
7 3RA27 function module for IO-Link Consisting of:
8 3RA28 function module 17 Wiring modules on the top and bottom for connecting the main,
auxiliary and control current paths, electrical interlock 1)
9 Surge suppressor with/without LED
included, interruptible (NC contact interlock)
10 Cover, sealable
18 Mechanical interlocks 2)
11 3-phase infeed terminal
19 Two connecting clips for two contactors 2)
For contactors
For contactors and coupling contactors
1) 3RT201. contactors with one NC contact in the basic unit
are required for the electrical interlock. An additional NO contact
is required for momentary-contact operation.
2) The parts
18 and 19 can only be ordered together as 3RA2912-2H
mechanical connectors.
16
17
15
19
3
2 1
18 1
21 2
4
3 5
IC01_00615e
6
20
7
8
9
10
19
11 15
14
13
12
1 Contactor, size S0
2 2-pole auxiliary switch, laterally mountable 13 Link for paralleling, 3-pole, with connecting terminal
3 1-pole auxiliary switch, for snapping onto the front 14 Connection module (adapter and plug) for contactors
cable entry from the top with screw terminals
4 2-pole auxiliary switch, for snapping onto the front 15 Coil connection module, on the top or bottom
cable entry from the bottom 16 3-phase infeed terminal
5 4-pole auxiliary switch, for snapping onto the front 17 Link for paralleling (star jumper), 3-pole,
6 Pneumatically delayed auxiliary switch without connecting terminal
18 Safety main current connector for two contactors
7 3RA27 function module for AS-Interface
8 3RA27 function module for IO-Link Assembly kit 3RA2923-2AA1
Consisting of:
9 3RA28 function module
19 Wiring modules on the top and bottom for connecting the
10 Surge suppressor with/without LED main current paths, electrical interlock included
11 Mechanical latching block (NC contact interlock)
12 Cover, sealable 20 Mechanical interlocks 1)
21 Two connecting clips for two contactors 1)
For contactors
For contactors and coupling contactors
1)
The parts 20 and 21 can only be ordered together as 3RA2922-2H
mechanical connectors.
12
13
14
3
16
1
17
15
2 1
18
2
3 4
5
IC01_00616d
6
7
14 16
8
11
10
1 Contactor, size S2
2 2-pole auxiliary switch, laterally mountable 14 Coil connection module, top or bottom
3 1-pole auxiliary switch, for snapping onto the front, 15 Safety main current connector for two contactors
cable entry from the top
Assembly kit 3RA2933-2AA1
4 2-pole auxiliary switch, for snapping onto the front, Consisting of:
cable entry from the bottom
16 Wiring modules on the top and bottom for connecting the
5 4-pole auxiliary switch, for snapping onto the front main current paths, electrical interlock included
6 3RA27 function module for AS-Interface (NC contact interlock)
7 3RA27 function module for IO-Link 17 Two connecting clips for two contactors
8 3RA28 function module
To be ordered separately:
9 Surge suppressor with/without LED
18 Mechanical interlocks
10 Cover, sealable
11 Link for paralleling, 3-pole, with connecting terminal
12 3-phase infeed terminal For contactors
13 Link for paralleling (star jumper), 3-pole, For contactors and coupling contactors
without connecting terminal
16
15
14
3
13
17
18 1
19
2
10 2
IC01_00617d
3 4
5
6
7
9
17
8 13
12
11
1 Contactor, size S3
2 2-pole auxiliary switch, laterally mountable 12 Links for paralleling, 3-pole, with connecting terminal
3 1-pole auxiliary switch, for snapping onto the front, 13 Coil connection module, top or bottom
cable entry from the top
14 Links for paralleling (star jumper), 3-pole,
4 2-pole auxiliary switch, for snapping onto the front, without connecting terminal
cable entry from the bottom
15 Auxiliary conductor terminal, 3-pole
5 4-pole auxiliary switch, for snapping onto the front
16 Single-phase infeed terminals (3 units)
6 3RA27 function module for AS-Interface
7 3RA27 function module for IO-Link Assembly kit 3RA2943-2AA1
Consisting of:
8 3RA28 function module
17 Wiring modules on the top and bottom for connecting the main,
9 Surge suppressor with/without LED auxiliary and control current paths, electrical interlock1)
(Varistor, diode assembly), can be plugged in on the front included, interruptible (NC contact interlock)
10 Surge suppressor without LED (RC element), can be 18 Two connectors for two contactors
plugged in on the front in the recesses on the left next to
the connection block To be ordered separately:
11 Cover, sealable 19 Mechanical interlock
1) For contactors
3RT201. contactors with one NC contact in the basic unit
are required for the electrical interlock. An additional NO contact For contactors and coupling contactors
is required for momentary-contact operation.
15
15
17
3
16
13
12
18
11
15
8
9
10
16
14
1
Accessories 33 to 77 and
12 to 17 can be mounted onto
12
7 2
contactors 11 and 2 respectively.
7
7
3
IC01_00651a
6
5
Can be mounted onto the front of contactors 1 and 2 Can be plugged onto the top of contactor operating
3 3RT1926: Auxiliary switch, electronically delayed (ON-delay or OFF-delay mechanisms 88 and 99
or star-delta (wye-delta) starting) 11 3RT1956-1C: Surge suppressor (RC element)
4 3RH192: 4-pole auxiliary switch
Can be mounted onto the top or bottom on busbars or box
5 3RH192: 1-pole auxiliary switch (max. four can be snapped on) terminals of contactors 11 and 2
6 3RT1926-4MA10: Cover, sealable 12 3RT1956-4G: Box terminal block
Can be mounted onto the side of contactors 1 and 2 13 3TX7500-0A: Auxiliary conductor terminal, 1-pole
7 3RH192: 2-pole auxiliary switch 14 3TX6526-3B: Terminal cover (can be screwed on), covers one
busbar connection
Can be inserted in top of contactors
15 3RT1956-4EA1: Terminal cover for busbar connection and on box
8 3RT1955-5A.3.: Withdrawable coil, standard operating mechanism terminal
9 3RT1955-5N.3.: Withdrawable coil, solid-state operating mechanism 16 3RT1956-4EA3: Terminal cover for busbar connection
10 3RT1955-5P.3.: Withdrawable coil, solid-state operating mechanism and 17 3RT1956-4EA2: Terminal cover on box terminal
remaining lifetime indicator
18 3RT1956-4EA4: Terminal cover for busbar connection,
covers 15 , 16 to 18
18 can be mounted
14
16
3
12
11
14
8
9
10
15
13
Accessories 33 to 7 and 2
12 to 16
17 can be mounted onto 7
contactors 1 and 2 respectively.
7
7
3
IC01_00652b
5 6
1 3RT106 and 3RT146 air-break contactors, size S10 Can be inserted in the top of contactors
(version without withdrawable coil) 8 3RT1965-5A.3.: Withdrawable coil, standard operating mech.
2 3RT106.-.P and 3RT146.-.P air-break contactors with solid-state operating 9 3RT1965-5N.3.: Withdrawable coil, solid-state operating mech.
mechanism and remaining lifetime indicator, size S10 10 3RT1965-5P.3.: Withdrawable coil, solid-state operating mech.
(version with withdrawable coil and laterally mountable add-on module) and remaining lifetime indicator
Can be mounted onto the front of contactors 11 and 2 Can be plugged onto the top of contactor operating
mechanisms 88 and 99
3 3RT1926: Auxiliary switch, electronically delayed (ON-delay or OFF-delay
or star-delta (wye-delta) starting) 11 3RT1956-1C: Surge suppressor (RC element)
4 3RH192: 4-pole auxiliary switch Can be mounted at the top or bottom on busbars or box
5 3RH192: 1-pole auxiliary switch (max. four can be snapped on) terminals of contactors 11 and 22
6 3RT1926-4MA10: Cover, sealable 12 3RT1966-4G: Box terminal block
Can be mounted onto the side of contactors 1 and 2 13 3TX6546-3B: Terminal cover (can be screwed on), covers one
busbar connection
7 3RH192: 2-pole auxiliary switch
14 3RT1966-4EA1: Terminal cover for busbar connection and on box
terminal
15 3RT1966-4EA3: Terminal cover for busbar connection
16 3RT1966-4EA2: Terminal cover on box terminal
9 11
3
10
7
3
4
1
IC01_00653b
14
16
3
12
11
14
8
9
10
15
13
Accessories 33 to 7 and 2
12 to 16
12 17 can be mounted onto
7
contactors 1 and 2 respectively.
7
7
3
IC01_00654b
5 6
1 3RT107 and 3RT147 air-break contactors, size S12 Can be inserted in top of contactors
(version without withdrawable coil) 8 3RT1975-5A.3.: Withdrawable coil, standard operating mech.
2 3RT107.-.P and 3RT147.-.P air-break contactors with solid-state operating 9 3RT1975-5N.3.: Withdrawable coil, solid-state operating mech.
mechanism and remaining lifetime indicator, size S12 10 3RT1975-5P.3.: Withdrawable coil, solid-state operating mech.
(version with withdrawable coil and laterally mountable add-on module) and remaining lifetime indicator
Can be mounted onto the front of contactors 1 and 2 Can be plugged onto top of contactor operating
mechanisms 88 and 99
3 3RT1926: Auxiliary switch, electronically delayed (ON-delay or OFF-delay
or star-delta (wye-delta) starting) 11 3RT1956-1C: Surge suppressor (RC element)
4 3RH192: 4-pole auxiliary switch Can be mounted at the top or bottom on busbars or box
5 3RH192: 1-pole auxiliary switch (max. four can be snapped on) terminals of contactors 11 and 2
6 3RT1926-4MA10: Cover, sealable 12 3RT1966-4G: Box terminal block
13 3TX6546-3B: Terminal cover (can be screwed on), covers one
Can be mounted onto the side of contactors 1 and 2
busbar connection
7 3RH192: 2-pole auxiliary switch
14 3RT1966-4EA1: Terminal cover for busbar connection and on box
terminal
15 3RT1966-4EA3: Terminal cover for busbar connection
16 3RT1966-4EA2: Terminal cover on box terminal
9 11
3
10
7
3
4
8
1
IC01_00573b
3
4
IC01_00721a
3
Can be inserted or mounted on the front of the contactor (with the Can be mounted on the front from above or below on busbars
cover removed) 4 Box terminal (1 set = 3 units)
2 Solenoid coils for AC operation, with switch-on electronics for contactor 3TF68: 3TX7570-1E
3TF6844-.C: 3TY7683-0C.7 3TF69: 3TX7690-1F
3TF6944-.C: 3TY7693-0C.7 5 Terminal cover for busbar connection (1 set = 2 units),
3 Solenoid coils for AC control supply voltage subject to attached to the right and left busbar connection in each case
strong interference 3TF68: 3TX7686-0A
3TF6833-.Q: 3TY7683-0Q.7 3TF69: 3TX7696-0A
3TF6933-.Q: 3TY7693-0Q.7 Can be mounted on the front of 3TF68 contactors from below on
Solenoid coils for DC operation busbars
3TF6833-.D: 3TY7683-0D.4 6 Terminal cover for busbar connection
(on outgoing side in combination with overload relay)
3TF68: 3TX7686-0B
Can be snapped onto the left-hand side of the auxiliary switches
7 Surge suppressor (only with DC operation)
3TF6.33-.D: 3TX7572-3.
■ Overview
Version Size Ratings of three- Connection methods Type Page
phase motors at Screw Spring-
50 Hz and 400 V terminals loaded
terminals
kW
Power contactors for switching motors
AC operation
3
3
Contactors with screw terminals: 3RT20 (sizes S00 to S3) and 3RT10 (sizes S6 to S12)
Our power range of contactors for switching IE2 motors and Standards
highly efficient IE3 and IE4 motors:
IEC 60947-1, IEC 60947-4-1, IEC 60947-5-1 (auxiliary switches)
• Contactors,
see pages 3/47 to 3/66: Contactors with increased tamper protection
- Size S00: 3RT201 up to 7.5 kW Increased tamper protection is ensured either by using our
- Size S0: 3RT202 up to 18.5 kW contactor versions with factory-installed, permanently mounted
- Size S2: 3RT203 up to 37 kW auxiliary switches protected against mechanical external
- Size S3: 3RT204 up to 55 kW actuation (e.g. 3RT20...-.....-3MA0 or 3RT10...-.....-3PA0
- Sizes S6 to S12: 3RT10 up to 250 kW contactors), or by using the 3RT2916-4MA10 or
• Vacuum contactors, 3RT1926-4MA10 sealable cover as an accessory
see page 3/120 onwards: (see page 3/112).
- Sizes S10 and S12: 3RT12 up to 250 kW
- Size 14: 3TF6 up to 450 kW
IC01_00747a
3
auxiliary NO contacts
Switching state of 21/22 closed OD open CD closed
auxiliary NC contacts
t (ms)
20 ms
CD = closing delay
OD = opening delay
AT = arcing time
Operation Closing delay Opening delay Total break time =
Opening delay +
Arcing time 10 … 15 ms
AC 20 ... 95 ms 40 ... 60 ms 50 ... 75 ms
DC 20 ... 95 ms 40 ... 60 ms 50 ... 75 ms
3
direct connection to the connecting bar is possible with cable
lugs for 3RT204 when the box terminal is removed. onwards).
• 3RT10 contactors: Without a function module, these contactors can be used like the
Screw terminals with connecting bars that the cables can be standard versions.
connected to using either cable lugs or flexible or rigid For more information on IO-Link and AS-Interface, see
busbars. Alternatively, box terminals are available as "Industrial communication", page 2/1 onwards.
accessories.
Operating mechanism types
Auxiliary and control circuits
3RT20 contactors
The 3RT contactors are available with screw terminals or spring-
loaded terminals. The standard versions are available with AC or DC operating
mechanisms or as versions with a wide-range solid-state
Electromagnetic compatibility operating mechanism and a universal actuating voltage
The contactors fulfill the requirements for environment category A. (AC or DC operation possible).
Note: Versions with solid-state operating mechanisms for AC or DC
operation with a fail-safe PLC input are also available for the
When the contactors are used in an environment with 3RT203 and 3RT204 contactors.
frequency converters, the configuration notes must be
observed, see Equipment Manual. Control takes place via the control supply voltage connection
A1 - A2 with varying operating ranges (see the technical product
Contact reliability of the auxiliary contacts data sheet for further details).
If voltages 110 V and currents 100 mA are to be switched, DC coupling contactors with reduced power consumption are
the auxiliary contacts of the 3RT contactors or 3RH contactor also ideally suited for connection to the controller.
relays should be used as they guarantee a high level of contact
reliability. 3RT10 contactors
These auxiliary contacts are particularly suitable for solid-state The operating mechanisms are powered via a supply voltage
circuits with currents 1 mA at a voltage 17 V. with an operating range from 0.8 to 1.1 x Us, optionally also
controlled depending on the chosen mode of operation. Various
Motor protection rated voltage ranges are available for AC/DC control.
3RT20 contactors The following control and/or operating mechanism versions can
be selected for contactors 3RT105 to 3RT107:
For protection against overload, 3RU2 thermal overload relays
(see page 7/89 onwards) or 3RB3 electronic overload relays • 3RT10..-.A contactors:
(see page 7/102 onwards) can be mounted on the 3RT20 Standard operating mechanism for AC and DC operation
contactors. (reduced power consumption when closing and in the closed
state)
3RT10 contactors
• Solid-state operating mechanisms:
For protection against overload, 3RB2 electronic overload relays Overvoltage damping of the operating mechanism coil is
(see page 7/114 onwards) can be mounted on the 3RT10 already integrated in the electronics for contactors with
contactors. solid-state operating mechanisms.
The following versions are available:
- 3RT10..-.N contactors:
With two operating modes: Direct control or via PLC input
(24 V DC)
- 3RT10..-.P contactors:
Control via PLC input (24 V DC) only, but with additional
remaining lifetime indicator (RLT)
- 3RT10..-.S contactors:
Control via fail-safe PLC input (24 V DC) only, for
simplification of safety applications (without mode of
operation selection)
3
Example for SIL 2 and SIL 3/PL e application – previously:
3RT1 contactor
A1
PLC-IN
A2
IC01_00704
N/-
Application with safety-related disconnection with standard contactors using the example of a 3RT105 contactor
Example for SIL 3/PL e (left-hand side) or SIL 2/PL c (right-hand side) application – new:
N/- N/-
Application with safety-related disconnection with contactors with fail-safe control using the example of a 3RT105 contactor
■ Technical specifications
More information
Technical specifications, see System Manual for modular system, see
https://support.industry.siemens.com/cs/ww/en/ps/16134/td https://support.industry.siemens.com/cs/ww/en/view/60311318
FAQs, see Equipment Manual, see
https://support.industry.siemens.com/cs/ww/en/ps/16134/faq https://support.industry.siemens.com/cs/ww/en/view/60306557
Application Manual - Switching devices with IE3 and IE4 motors, see
https://support.industry.siemens.com/cs/ww/en/view/94770820
3
Configuration Manual for load feeders, see
https://support.industry.siemens.com/cs/ww/en/view/39714188
Configuration Manual for UL, see
https://support.industry.siemens.com/cs/ww/en/view/53433538
Guide of use for contactors in safety applications, see
https://support.industry.siemens.com/cs/ww/en/view/109807687
Type Contactors
3RT2 3RT1
Size S00 to S2 S3 S6 to S12
Rated data of the auxiliary contacts
According to IEC 60947-5-1
Data apply to integrated auxiliary contacts and conventional contacts
in the auxiliary switches
Rated insulation voltage Ui (pollution degree 3) V 690 1 000 --
(3RT20..-0CC0: 690)
• For laterally mountable auxiliary switches V 690 690 500
• For front auxiliary switches V 690 690 690
Conventional thermal current Ith = A 10
rated operational current Ie/AC-12
AC load
Rated operational current Ie/AC-15/AC-14
• At rated operational voltage Ue Up to 230 V A 101) 6 6
400 V A 3 3
500 V A 2 2
690 V A 1 12)
DC load
Rated operational current Ie/DC-12
• At rated operational voltage Ue 24 V A 10 10
60 V A 6 6
110 V A 3 3
125 V A 2 2
220 V A 1 1
440 V A 0.3 0.3
600 V A 0.15 0.152)
Rated operational current Ie/DC-13
• At rated operational voltage Ue 24 V A 101) 103)
60 V A 2 2
110 V A 1 1
125 V A 0.9 0.9
220 V A 0.3 0.3
440 V A 0.14 0.14
600 V A 0.1 0.152)
Contact reliability at 17 V, 1 mA Frequency of contact faults < 10-8 i.e. < 1 fault per 100 million operating cycles
According to IEC 60947-5-4
1)
3RH22, 3RH29, 3RT2...-....4, 3RT2...-....6: Ie = 6 A at AC-15/AC-14 and
DC-13.
2)
With laterally mountable auxiliary switches, only the currents for rated
operational voltages up to 500 V apply.
3) For laterally mountable auxiliary switches, DC-13/at 24 V: max. 6 A.
DC-13
24 V
0,1
1)
0,05
0,01
0,01 0,03 0,05 0,1 0,3 0,5 1 2 3 4 5 6 7 10 a (A)
e -DC-13 e -DC-13 e -DC-13 e -AC-15
220 V 110 V 24 V < 230 V
Diagram legend:
a = Breaking current
e = Rated operational current
10
5 Basic unit
4 with attach.
3 contact block
2
DC-13
1 220 V DC-13 AC-15/AC-14
0,5 110 V
DC-13
24 V
0,1
0,05
2)
0,01
0,01 0,03 0,05 0,1 0,3 0,5 1 2 3 5 6 7 10 (A)
a
230 V
500 V
690 V
400 V
AC-3e) depending on the breaking current
and rated operational voltage. It is assumed Contactor 3RT2015, 3RT2016 3RT2017, 3RT2018
3
that the operating mechanisms are switched 7 type (3 kW, 4 kW) (5,5 kW, 7,5 kW)
arbitrarily and not synchronously with the 7 10
10 8 6 8
NSB0_02059a
phase angle of the supply system switching 6
8 4 6
operating mechanism. 6 4 4
The rated operational current Ie complies with 4 2
utilization category AC-4 (breaking 6 times 2
the rated operational current) and is intended 6 2
2 6 10
for a contact endurance of approximately 10 8 10
6
6 8
200 000 operating cycles. 10 6 8
8 6 4 6
If a shorter contact endurance is sufficient,
the rated operational current Ie/AC-4 can be 6 4 4
increased. 4 2
If the contacts are used for mixed operation, 2 2
2 5
i.e. normal switching (breaking the rated 5 10
operational current according to utilization 10 8 105
5
category AC-3 and AC-3e) in combination 10 8 6 8
with intermittent inching (breaking several 8 6 4 6
times the rated operational current according 6 4 4
to utilization category AC-4), the contact 4 2
endurance can be calculated approximately 2
from the following equation: 4
2
2 10
4
A 10 8 10
4
X = ---------------------------------------------------------- 2 3 4 5 6 8 10 15 20 30 40 50 60 80 100
1 + ---------- ---- – 1
C A
100 B Breaking current a (A)
500 V
690 V
400 V
230 V
500 V
690 V
400 V
Contactor 3RT2035 3RT2036 3RT2037 3RT2038
3
Size S3
Operating cycles at
230 V
500 V
690 V
400 V
Sizes S6 to S12
Operating cycles at
230 V
500 V
690 V
400 V
Contactor type
3RT1054 3RT1055 3RT1056 3RT1064 3RT1065 3RT1066 3RT1075 3RT1076
7 (55 kW) (75 kW) (90 kW) (110 kW) (132 kW) (160 kW) (200 kW) (250 kW)
7 10
10 8 6 8 NSB0_01141a
8 6 4 6
6 4 4
4 2
2 6 2
2 6 6 10
10
6 10 8
10 8 8 6
8 6 6 4
6 4 4
4 2
2 5 2
2 5 10 5
5 10 8 10
10 8 6 8
8 6 4 6
6 4 4
4 2
2 4 2
2 4 10 4
10 8 10
10 20 30 40 50 60 80 100 150 200 300 400 600 800 1 000 2 0003 000
Breaking current a (A)
Contactors
Type 3RT2015, 3RT2016 3RT2017, 3RT2018
Size S00
General data
Dimensions (W x H x D)
• Basic unit
- Screw terminals mm 45 x 58 x 73
H
- Spring-loaded terminals mm 45 x 70 x 73
3
D
• Basic unit with mounted auxiliary switch W
- Screw terminals mm 45 x 58 x 117
- Spring-loaded terminals mm 45 x 70 x 121
• Basic unit with mounted function module or
solid-state time-delayed auxiliary switch
- Screw terminals mm 45 x 58 x 147
- Spring-loaded terminals mm 45 x 70 x 147
Permissible mounting position
The contactors are designed for operation on
NSB0_00478c
360° 22,5° 22,5°
a vertical mounting surface.
NSB0_00477a
Contactors
Type 3RT2015, 3RT2016 3RT2017, 3RT2018
Size S00
Short-circuit protection
Main circuit
• Fuse links, operational class gG:
LV HRC, type 3NA; DIAZED, type 5SB; NEOZED, type 5SE
according to IEC 60947-4-1
3
Coupling contactors
Type 3RT201.-.HB4. 3RT201.-.JB4. 3RT201.-.KB4. 3RT201.-.MB4.-0KT0 3RT201.-.VB4. 3RT201.-.SB4.
Size S00
Control
Solenoid coil 0.7 ... 1.25 x Us 0.85 ... 1.85 x Us
operating range
Power consumption of at Us 24 V DC W 2.8 1.6
the solenoid coils
(for cold coil)
Closing = Closed
Permissible residual current < 6 mA x (24 V/Us) On request
of the electronics (with 0 signal)
Upright mounting position On request
Overvoltage No overvoltage Integrated Integrated No overvoltage Integrated Integrated
configuration of the damping diode suppressor damping diode suppressor
solenoid coil diode diode
Contactors
Type 3RT2015 3RT2016 3RT2017 3RT2018
Size S00
Rated data of the main contacts
Load rating with AC
Utilization category AC-3 and AC-3e
• Rated operational currents Ie Up to 400 V A 7 9 12 16
440 V A 7 9 11 14
3
500 V A 6 7.7 9.2 12.4
690 V A 4.9 6.7 8.9
• Rated power for slip-ring or squirrel-cage at 230 V kW 1.5 2.2 3 4
motors at 50 and 60 Hz 400 V kW 3 4 5.5 7.5
690 V kW 4 5.5 7.5
Thermal load capacity 10 s current A 56 72 96 128
Power loss per main conducting path at Ie/AC-3/ W 0.2 0.3 0.5 1
AC-3e/400 V
Utilization category AC-4 (at Ia = 6 x Ie)1)
• Maximum values
- Rated operational current Ie Up to 400 V A 6.5 8.5 11.5
- Rated power for squirrel-cage motors at Up to 400 V kW 3 4 5.5
50 Hz and 60 Hz
• The following applies to a contact endurance
of about 200 000 operating cycles:
- Rated operational currents Ie Up to 400 V A 2.6 4.1 5.5
690 V A 1.8 3.3 4.4
- Rated power for squirrel-cage motors at at 230 V kW 0.67 1.1 1.5
50 Hz and 60 Hz 400 V kW 1.15 2 2.5
690 V kW 1.15 2.5 3.5
1)
The data only apply to 3RT2516 and 3RT2517 contactors (2 NO + 2 NC)
up to a rated operational voltage of 400 V.
Contactors
Type 3RT2015 to 3RT2018
Size S00
Conductor cross-sections
Main conductors, auxiliary conductors and coil terminals Screw terminals
(1 or 2 conductors can be connected)
• Solid or stranded mm2 2 x (0.5 ... 1.5)1); 2 x (0.75 ... 2.5)1); max. 2 x 4
• Finely stranded with end sleeve (DIN 46228) mm2 2 x (0.5 ... 1.5)1); 2 x (0.75 ... 2.5)1)
• AWG cables, solid or stranded AWG 2 x (20 ... 16)1); 2 x (18 ... 14)1); 2 x 12
• Terminal screw M3 (for Pozidriv size 2; 5 ... 6 mm)
• Tightening torque Nm 0.8 ... 1.2 (7 ... 10.3 lb.in)
Main conductors, auxiliary conductors and coil terminals2) Spring-loaded terminals
(1 or 2 conductors can be connected)
• Operating devices mm 3.0 x 0.5
• Solid or stranded mm2 2 x (0.5 ... 4)
• Finely stranded with end sleeve (DIN 46228) mm2 2 x (0.5 ... 2.5)
• Finely stranded without end sleeve mm2 2 x (0.5 ... 2.5)
• AWG cables, solid or stranded AWG 2 x (20 ... 12)
Auxiliary conductors for front and laterally mounted auxiliary
switches2)
(1 or 2 conductors can be connected)
• Operating devices mm 3.0 x 0.5
• Solid or stranded mm2 2 x (0.5 ... 2.5)
• Finely stranded with end sleeve (DIN 46228) mm2 2 x (0.5 ... 1.5)
• Finely stranded without end sleeve mm2 2 x (0.5 ... 2.5)
• AWG cables, solid or stranded AWG 2 x (20 ... 14)
1) 2)
If two different conductor cross-sections are connected to one clamping Max. outer diameter of the conductor insulation: 3.6 mm.
point, both cross-sections must lie in one of the ranges specified. On spring-loaded terminals with conductor cross-sections 1 mm2, an
insulation stop is recommended, see page 3/115.
Contactors
Type 3RT2023 to 3RT2025 3RT2026 to 3RT2028
Size S0
General data
Dimensions (W x H x D)
AC operation
H
• Basic unit
- Screw terminals mm 45 x 85 x 97
3
D
- Spring-loaded terminals W mm 45 x 102 x 97
• Basic unit with mounted auxiliary switch
- Screw terminals mm 45 x 85 x 141
- Spring-loaded terminals mm 45 x 102 x 145
• Basic unit with mounted function module or
solid-state time-delayed auxiliary switch
- Screw terminals mm 45 x 85 x 171
- Spring-loaded terminals mm 45 x 102 x 171
DC operation
• Basic unit
- Screw terminals mm 45 x 85 x 107
- Spring-loaded terminals mm 45 x 102 x 107
• Basic unit with mounted auxiliary switch
- Screw terminals mm 45 x 85 x 151
- Spring-loaded terminals mm 45 x 102 x 155
• Basic unit with mounted function module or
solid-state time-delayed auxiliary switch
- Screw terminals mm 45 x 85 x 181
- Spring-loaded terminals mm 45 x 102 x 181
Permissible mounting position
The contactors are designed for operation on
NSB0_00478c
360° 22,5° 22,5°
a vertical mounting surface.
NSB0_00477a
Contactors
Type 3RT2023 to 3RT2025 3RT2026 3RT2027, 3RT2028
Size S0
Short-circuit protection
Main circuit
• Fuse links, operational class gG:
LV HRC, type 3NA; DIAZED, type 5SB; NEOZED, type 5SE
according to IEC 60947-4-1
3
- Type of coordination "1" A 63 100 125
- Type of coordination "2" A 25 35 50
- Weld-free (test conditions according to IEC 60947-4-1) A 10 16
• Miniature circuit breaker with C characteristic A 25 32 40
(short-circuit current 3 kA, type of coordination "1")
Auxiliary circuit
• Fuse links, operational class gG: A 10
DIAZED, type 5SB; NEOZED, type 5SE
(weld-free protection at Ik 1 kA)
• 230 V miniature circuit breaker, C characteristic A 10
(short-circuit current Ik < 400 A)
Short-circuit protection for contactors with overload relays See Configuration Manual for load feeders
Short-circuit protection for fuseless load feeders See 3RA2 load feeders, page 8/5 onwards
Contactors
Type 3RT2023 to 3RT2026 to 3RT202.-.NB3 3RT202.-.NF3. 3RT202.-.NP3
3RT2025 3RT2028
Size S0
Control
Type of operating mechanism AC or DC AC/DC
Solenoid coil operating range AC/DC 0.8 ... 1.1 x Us1) 0.7 ... 1.3 x Us2)
Power consumption of the solenoid coils
(for cold coil and 1.0 x Us)
• AC operation, 50 Hz, standard version
- Closing VA 65 77 6.6 11.9 12.7
- P.f. 0.82 0.98
- Closed VA 7.6 9.8 1.9 1.6 3.9
- P.f. 0.25 0.86 0.79 0.51
• AC operation, 50/60 Hz, standard version
- Closing VA 68/67 81/79 6.6/6.7 11.9/12.0 12.7/14.7
- P.f. 0.72/0.74 0.98/0.98
- Closed VA 7.9/6.5 10.5/8.5 1.9/2.0 1.6/1.8 3.9/4.3
- P.f. 0.25/0.28 0.86/0.82 0.79/0.74 0.51/0.56
• AC operation, 50 Hz, for USA/Canada
- Closing VA 65 77 --
- P.f. 0.82 0.82 --
- Closed VA 73)/7.6 9.8 --
- P.f. 0.25 0.28 --
• AC operation, 60 Hz, for USA/Canada
- Closing VA 73 87 --
- P.f. 0.76 --
- Closed VA 7.2 9.4 --
- P.f. 0.28 --
• DC operation (closing = closed) W 5.9/5.9 5.9/1.4 10.2/1.3 14.3/1.9
Permissible residual current of the electronics
(with 0 signal)
• AC operation mA < 6 mA x (230 V/Us) < 7 mA x (230 V/Us)
• DC operation mA < 16 mA x (24 V/Us)
1) 2)
Coil operating range The following applies to Us max = 280 V: Upper limit = 1.1 x Us max
- At 50 Hz: 0.8 to 1.1 x Us 3)
Value applies to 3RT2023 contactor at 50 Hz AC.
- At 60 Hz: 0.85 to 1.1 x Us.
Coupling contactors
Type 3RT202.-.KB4.
Size S0
Control
Solenoid coil operating range 0.7 ... 1.25 x Us
Power consumption of the solenoid coils at Us 24 V DC W 4.5
(for cold coil)
Closing = Closed
Permissible residual current < 10 mA x (24 V/Us)
of the electronics (with 0 signal)
Overvoltage configuration of the solenoid coil Integrated varistor
Contactors
Type 3RT2023 3RT2024 3RT2025 3RT2026 3RT2027 3RT2028
Size S0
Rated data of the main contacts
Load rating with AC
Utilization category AC-3 and AC-3e
• Rated operational currents Ie Up to 400 V A 9 12 17 25 32 38
440 V A 9 12 17 22 32 35
3
500 V A 9 12 17 18 32
690 V A 9 13 21
• Rated power for slip-ring or squirrel-cage motors at 230 V kW 2.2 3 4 5.5 7.5 11
at 50 and 60 Hz 400 V kW 4 5.5 7.5 11 15 18.5
690 V kW 7.5 11 18.5
Thermal load capacity 10 s current A 80 110 150 200 260 304
Power loss per main conducting path at Ie/AC-3/ W 0.2 0.3 0.6 1.9 2.3 3.2
AC-3e/400 V
Utilization category AC-4 (at Ia = 6 x Ie)
• Maximum values:
- Rated operational current Ie Up to 400 V A 8.5 12.5 15.5 22
- Rated power for squirrel-cage motors at 50 Hz at 400 V kW 4 5.5 7.5 11
and 60 Hz
• The following applies to a contact endurance
of about 200 000 operating cycles:
- Rated operational currents Ie Up to 400 V A 4.1 5.5 7.7 9 12
690 V A 3.3 5.5 7.7 9 12
- Rated power for squirrel-cage motors at 50 Hz at 110 V kW 0.5 0.73 1 1.2 1.6
and 60 Hz 230 V kW 1.1 1.5 2 2.5 3.4
400 V kW 2 2.6 3.5 4.4 6
690 V kW 2.5 4.6 6 7.7 10.3
Contactors
Type 3RT2023 to 3RT2028
Size S0
Conductor cross-sections
Main conductors Screw terminals
(1 or 2 conductors can be connected)
2
• Solid or stranded mm 2 x (1 ... 2.5)1); 2 x (2.5 ... 10)1)
2
• Finely stranded with end sleeve (DIN 46228) mm 2 x (1 ... 2.5)1); 2 x (2.5 ... 6)1); 1 x 10
• AWG cables, solid or stranded AWG 2 x (16 ... 12)1); 2 x (14 ... 8)1)
• Terminal screws M4 (for Pozidriv size 2; 5 ... 6 mm)
- Tightening torque Nm 2 ... 2.5 (18 ... 22 lb.in)
Auxiliary conductors
(1 or 2 conductors can be connected)
• Solid or stranded mm2 2 x (0.5 ... 1.5)1); 2 x (0.75 ... 2.5)1
2
• Finely stranded with end sleeve (DIN 46228) mm 2 x (0.5 ... 1.5)1); 2 x (0.75 ... 2.5)1)
• AWG cables, solid or stranded AWG 2 x (20 ... 16)1); 2 x (18 ... 14)1)
• Terminal screws M3 (for Pozidriv size 2; 5 ... 6 mm)
- Tightening torque Nm 0.8 ... 1.2 (7 ... 10.3 lb.in)
Main conductors2) Spring-loaded terminals
(1 or 2 conductors can be connected)
• Operating devices mm 3.0 x 0.5
• Solid or stranded mm2 2 x (1 ... 10)
• Finely stranded with end sleeve (DIN 46228) mm2 2 x (1 ... 6)
• Finely stranded without end sleeve mm2 2 x (1 ... 6)
• AWG cables, solid or stranded AWG 2 x (18 ... 8)
Auxiliary conductors2)
(1 or 2 conductors can be connected)
• Operating devices 3.0 x 0.5
• Solid or stranded mm2 2 x (0.5 ... 2.5)
• Finely stranded with end sleeve (DIN 46228) mm2 2 x (0.5 ... 1.5)
• Finely stranded without end sleeve mm2 2 x (0.5 ... 2.5)
• AWG cables, solid or stranded AWG 2 x (20 ... 14)
1) 2)
If two different conductor cross-sections are connected to one clamping Max. outer diameter of the conductor insulation: 6.4 mm.
point, both cross-sections must lie in one of the ranges specified. On spring-loaded terminals with conductor cross-sections 1 mm2, an
insulation stop is recommended, see page 3/115.
Contactors
Type 3RT2035 3RT2036 3RT2037 3RT2038
Size S2
General data
Dimensions (W x H x D)
• Basic unit
- Screw/spring-loaded terminals mm 55 x 114 x 130
H
• Basic unit with mounted auxiliary switch
3
D
- Screw terminals W mm 55 x 114 x 174
- Spring-loaded terminals mm 55 x 114 x 178
• Basic unit with mounted function module or
solid-state time-delayed auxiliary switch
- Screw/spring-loaded terminals mm 55 x 114 x 204
Permissible mounting position
The contactors are designed for operation on
NSB0_00478c
360° 22,5° 22,5°
a vertical mounting surface.
NSB0_00477a
Special version required
Mechanical endurance
• Basic units and Operat- 10 million (3RT203.-.S.30: 5 million)
basic units with mounted auxiliary switch ing
cycles
• Basic units with solid-state compatible auxiliary switch Operat- 5 million
ing
cycles
Electrical endurance For contact endurance of the main contacts, see page 3/28.
Rated insulation voltage Ui (pollution degree 3) V 690
Rated impulse withstand voltage Uimp
• Auxiliary circuit kV 6
• Main circuit kV 6
Protective separation between the coil and the main contacts V 400
(according to IEC 60947-1, Annex N)
Mirror contacts
A mirror contact is an auxiliary NC contact that cannot be closed
simultaneously with an NO main contact.
• Integrated auxiliary switches Yes, according to IEC 60947-4-1, Annex F
• 3RT2.3. (removable auxiliary switch) Yes, according to IEC 60947-4-1, Annex F
Permissible ambient temperature
• During operation °C -25 ... +60
• During storage °C -55 ... +80
Short-circuit protection
Main circuit
• Fuse links, operational class gG:
LV HRC, type 3NA; DIAZED, type 5SB; NEOZED, type 5SE
according to IEC 60947-4-1
- Type of coordination "1" A 160 250
- Type of coordination "2" A 80 125 160
- Weld-free (test conditions according to IEC 60947-4-1) A 16 25 50
Auxiliary circuit
• Fuse links, operational class gG: A 10
DIAZED, type 5SB; NEOZED, type 5SE
(weld-free protection at Ik 1 kA)
• 230 V miniature circuit breaker, C characteristic A 10
(short-circuit current Ik < 400 A)
Short-circuit protection for contactors with overload relays See Configuration Manual for load feeders
Short-circuit protection for fuseless load feeders See 3RA2 load feeders, page 8/5 onwards
Contactors Coupling
contactors
Type 3RT203.-.A..., 3RT203.-.N.3. 3RT203.-.S.3. 3RT203.-.KB4.
3RT203.-.C...
Size S2
Control
Type of operating mechanism AC AC/DC DC
Solenoid coil operating range
3
U
PLC control input according to IEC 60947-1
• Solid-state operating mechanism -- Type 1 --
• Rated voltage V DC -- 24 --
• Operating range V DC -- 17 ... 30 --
• Power consumption mA -- 30 --
• Recovery time after mains failure, typical s -- 2 --
1) Coil operating range
- At 50 Hz: 0.8 to 1.1 x Us,
- At 60 Hz: 0.85 to 1.1 x Us.
2)
In the case of AC/DC coils, increased pickup currents (2.6 A on average)
arise during the first 230 ms. For direct control by PLC, we therefore
recommend special coupling contactors with reduced power
consumption. The connection of one 3RT203.-.KB4. coupling contactor is
possible per PLC output port with an output current of 2 A, see page 3/59.
3) In the case of DC coils, increased pickup currents (2.1 A on average) arise
during the first 230 ms.
Contactors
Type 3RT2035 3RT2036 3RT2037 3RT2038
Size S2
Rated data of the main contacts
Load rating with AC
Utilization category AC-3 and AC-3e
• Rated operational currents Ie Up to 400 V A 41 51 65 80
440 V A 41 51 65 80
3
500 V A 41 51 65 80
690 V A 24 47 58
• Rated power for slip-ring or at 230 V kW 11 15 18.5 22
squirrel-cage motors at 50 and 60 Hz 400 V kW 18.5 22 30 37
690 V kW 22 37 45
Thermal load capacity 10 s current A 400 420 520 640
Power loss per main conducting path at Ie/AC-3/ W 2.2 4 3.8 5.7
AC-3e/400 V
Utilization category AC-4 (at Ia = 6 x Ie)
• Maximum values
- Rated operational current Ie Up to 400 V A 35 41 55
- Rated power for squirrel-cage motors at 400 V kW 18.5 22 30
at 50 Hz and 60 Hz
• The following applies to a contact
endurance of about 200 000 operating
cycles:
- Rated operational currents Ie Up to 400 V A 22 24 28 30
690 V A 18.5 20 22 24
- Rated power for squirrel-cage motors at 110 V kW 3.2 3.5 4.1 4.3
at 50 Hz and 60 Hz 230 V kW 6.7 7.3 8.5 9.1
400 V kW 11.6 12.6 14.7 15.8
690 V kW 16.8 18.2 20 21.8
Contactors
Type 3RT2035 to 3RT2038
Size S2
Conductor cross-sections
Main conductors Screw terminals
(1 or 2 conductors can be connected)
• Solid or stranded mm2 2 x (1 ... 35)1); 1 x (1 ... 50)1)
2
• Finely stranded with end sleeve (DIN 46228) mm 2 x (1 ... 25)1); 1 x (1 ... 35)1)
• AWG cables, solid or stranded AWG 2 x (18 ... 2)1); 1 x (18 ... 1)1)
• Terminal screws Pozidriv size 2; 5 ... 6 mm
- Tightening torque Nm 3 ... 4.5 (27 ... 40 lb.in)
Auxiliary conductors and control conductors
(1 or 2 conductors can be connected)
• Solid or stranded mm2 2 x (0.5 ... 1.5)1); 2 x (0.75 ... 2.5)1)
2
• Finely stranded with end sleeve (DIN 46228) mm 2 x (0.5 ... 1.5)1); 2 x (0.75 ... 2.5)1)
• AWG cables, solid or stranded AWG 2 x (20 ... 16)1); 2 x (18 ... 14)1)
• Terminal screws M3 (for Pozidriv size 2; 5 ... 6 mm)
- Tightening torque Nm 0.8 ... 1.2 (7 ... 10.3 lb.in)
Auxiliary and control conductors2) Spring-loaded terminals
(1 or 2 conductors can be connected)
• Operating devices mm 3.0 x 0.5
• Solid or stranded mm2 2 x (0.5 ... 2.5)
• Finely stranded with end sleeve (DIN 46228) mm2 2 x (0.5 ... 1.5)
• Finely stranded without end sleeve mm2 2 x (0.5 ... 2.5)
• AWG cables, solid or stranded AWG 2 x (20 ... 14)
1) 2)
If two different conductor cross-sections are connected to one clamping Max. outer diameter of the conductor insulation: 3.6 mm.
point, both cross-sections must lie in one of the ranges specified. On spring-loaded terminals with conductor cross-sections 1 mm2, an
insulation stop is recommended, see page 3/115.
Contactors
Type 3RT2045 3RT2046 3RT2047
Size S3
General data
Dimensions (W x H x D)
• Basic unit
- Screw/spring-loaded terminals mm 70 x 140 x 152
H
• Basic unit with mounted auxiliary switch
3
D
- Screw terminals W mm 70 x 140 x 196
- Spring-loaded terminals mm 70 x 140 x 200
• Basic unit with mounted function module or
solid-state time-delayed auxiliary switch
- Screw/spring-loaded terminals mm 70 x 140 x 226
Permissible mounting position
The contactors are designed for operation on
NSB0_00478c
360° 22,5° 22,5°
a vertical mounting surface.
NSB0_00477a
Special version required
Mechanical endurance
• Basic units and Operat- 10 million
basic units with mounted auxiliary switch ing
cycles
• Basic units with solid-state compatible auxiliary switch Operat- 5 million
ing
cycles
Electrical endurance For contact endurance of the main contacts, see page 3/28.
Rated insulation voltage Ui (pollution degree 3) V 1 000 (3RT20..-.....-0CC0: 690)
Rated impulse withstand voltage Uimp
• Auxiliary circuit kV 6
• Main circuit kV 8
Protective separation between the coil and the main contacts V 690
(according to IEC 60947-1, Annex N)
Mirror contacts
A mirror contact is an auxiliary NC contact that cannot be closed
simultaneously with an NO main contact.
• Integrated auxiliary switches Yes, according to IEC 60947-4-1, Annex F
• 3RT2.4. (removable auxiliary switch) Yes, according to IEC 60947-4-1, Annex F
Permissible ambient temperature
• During operation °C -25 ... +60
• During storage °C -55 ... +80
Short-circuit protection
Main circuit
• Fuse links, operational class gG:
LV HRC, type 3NA; DIAZED, type 5SB; NEOZED, type 5SE
according to IEC 60947-4-1
- Type of coordination "1" A 250
- Type of coordination "2" A 160 160 200
- Weld-free (test conditions according to IEC 60947-4-1) A On request
Auxiliary circuit
• Fuse links, operational class gG: A 10
DIAZED, type 5SB; NEOZED, type 5SE
(weld-free protection at Ik 1 kA)
• 230 V miniature circuit breaker, C characteristic A 10
(short-circuit current Ik < 400 A)
Short-circuit protection for contactors with overload relays See Configuration Manual for load feeders
Short-circuit protection for fuseless load feeders See 3RA2 load feeders, page 8/5 onwards
Contactors Coupling
contactors
Type 3RT204.-.A..., 3RT204.-.N.3. 3RT204.-.S.3. 3RT204.-.KB4.
3RT204.-.C...
Size S3
Control
Type of operating mechanism AC AC/DC DC
Solenoid coil operating range
3
• AC operation1) 0.8 ... 1.1 x Us --
• AC/DC operation1) -- 0.8 ... 1.1 x Us --
• DC operation -- 0.8 ... 1.2 x Us
Power consumption of the solenoid coils
(for cold coil and 1.0 x Us)
• AC operation, 50 Hz, standard version
- Closing VA 296 --
- P.f. 0.61 --
- Closed VA 19 --
- P.f. 0.38 --
• AC operation, 50/60 Hz, standard version
- Closing VA 348/296 --
- P.f. 0.62/0.55 --
- Closed VA 25/18 --
- P.f. 0.35/0.41 --
• AC operation, 60 Hz, for USA/Canada
- Closing VA 326 --
- P.f. 0.62 --
- Closed VA 22 --
- P.f. 0.38 --
• AC/DC operation
- Closing for AC operation VA -- 163 130 --
- P.f. -- 0.95 --
- Closed for AC operation VA -- 3.1 2.4 --
- P.f. -- 0.95 0.7 --
- Closing for DC operation VA -- 762) 130 --
- Closed for DC operation VA -- 1.8 --
• DC operation
- Closing for DC operation W -- 253)
- Closed for DC operation W -- 0.9
Permissible residual current of the electronics
(with 0 signal)
• AC/DC operation mA -- < 20 --
• DC operation mA -- < 20
Overvoltage configuration of the solenoid coil -- Integrated varistor
Contactors
Type 3RT2045 3RT2046 3RT2047
Size S3
Rated data of the main contacts
Load rating with AC
Utilization category AC-3 and AC-3e
• Rated operational currents Ie Up to 400 V A 80 95 110
500 V A 80 95 110
3
690 V A 58 78 98
1 000 V A 30
• Rated power for slip-ring at 230 V kW 22 22 30
or squirrel-cage motors 400 V kW 37 45 55
at 50 and 60 Hz 690 V kW 55 75 90
1 000 V kW 37
Thermal load capacity 10 s current A 760 880
Power loss per main conducting path at Ie/AC-3/ W 5.3 6.6 7.9
AC-3e/400 V
Utilization category AC-4 (at Ia = 6 x Ie)
• Maximum values
- Rated operational current Ie Up to 400 V A 66 80 97
- Rated power for squirrel-cage at 400 V kW 37 45 55
motors at 50 Hz and 60 Hz
• The following applies to a contact endurance
of about 200 000 operating cycles:
- Rated operational currents Ie Up to 400 V A 34 42 46
690 V A 24 30 36
- Rated power for squirrel-cage at 110 V kW 4.9 6.1 6.7
motors at 50 Hz and 60 Hz 230 V kW 10.4 12 14
400 V kW 17.9 22 24.3
690 V kW 21.8 27.4 32.9
Contactors
Type 3RT2045 to 3RT2047
Size S3
Conductor cross-sections
Main conductors Screw terminals
(1 or 2 conductors can be connected)
• Solid mm2 2 x (2.5 ... 16)1)
• Stranded mm2 2 x (6 ... 16)1); 2 x (10 ... 50)1); 1 x (10 ... 70)1)
• Finely stranded with end sleeve (DIN 46228) mm2 2 x (2.5 ...35)1); 1 x (2.5 ... 50)1)
• AWG cables, solid or stranded AWG 2 x (10 ... 1/0)1); 1 x (10 ... 2/0)1)
• Terminal screws Hexagon socket, size 4
- Tightening torque Nm 4.5 ... 6 (40 ... 53 lb.in)
Auxiliary conductors and control conductors
(1 or 2 conductors can be connected)
• Solid or stranded mm2 2 x (0.5 ... 1.5)1); 2 x (0.75 ... 2.5)1)
• Finely stranded with end sleeve (DIN 46228) mm2 2 x (0.5 ... 1.5)1); 2 x (0.75 ... 2.5)1)
• AWG cables, solid or stranded AWG 2 x (20 ... 16)1); 2 x (18 ... 14)1)
• Terminal screws M3 (for Pozidriv size 2; 5 ... 6 mm)
- Tightening torque Nm 0.8 ... 1.2 (7 ... 10.3 lb.in)
2)
Auxiliary and control conductors Spring-loaded terminals
(1 or 2 conductors can be connected)
• Operating devices mm 3.0 x 0.5
• Solid or stranded mm2 2 x (0.5 ... 2.5)
• Finely stranded with end sleeve (DIN 46228) mm2 2 x (0.5 ... 1.5)
• Finely stranded without end sleeve mm2 2 x (0.5 ... 2.5)
• AWG cables, solid or stranded AWG 2 x (20 ... 16)
1) 2)
If two different conductor cross-sections are connected to one clamping Max. outer diameter of the conductor insulation: 3.6 mm.
point, both cross-sections must lie in one of the ranges specified. On spring-loaded terminals with conductor cross-sections 1 mm2, an
insulation stop is recommended, see page 3/115.
Contactors
Type 3RT1054 3RT1055, 3RT1064 to 3RT1075 3RT1076
3RT1056 3RT1066
Size S6 S10 S12
General data
Dimensions (W x H x D) :
• Basic unit mm 120 x 172 x 170 145 x 210 x 202 160 x 214 x 225
• Basic unit with mounted auxiliary switch mm 120 x 172 x 217 145 x 210 x 251 160 x 214 x 271
3
+
'
Permissible mounting position
NSB0_00649a
22,5° 22,5°
The contactors are designed for operation on a vertical 90° 90°
mounting surface.
Contactors
Type 3RT105. 3RT106. 3RT107.
Size S6 S10 S12
Control
Operating range of the solenoid AC/DC 0.8 x Us min ... 1.1 x Us max
operating mechanism
Power consumption of the solenoid operating mechanism
(with cold coil and rated range Us min ... Us max)
3
Contactors
Type 3RT1054 3RT1055 3RT1056 3RT1064 3RT1065 3RT1066 3RT1075 3RT1076
Size S6 S10 S12
Rated data of the main contacts
Load rating with AC
Utilization category AC-3 and AC-3e
• Rated operational currents Ie
3
- Up to 500 V A 115 150 185 225 265 300 400 500
- At 690 V A 115 150 170 225 265 280 400 450
- At 1 000 V A 53 65 65 68 95 95 180 180
• Rated power for slip-ring or squirrel-cage motors
at 50 and 60 Hz
- At 230 V kW 37 45 55 55 75 90 132 160
- At 400 V kW 55 75 90 110 132 160 200 250
- At 500 V kW 75 90 132 160 160 200 250 315
- At 690 V kW 110 132 160 On request On request On request 400 400
- At 1 000 V kW 75 90 160 200 132 132 250 250
Thermal load capacity, 10 s current A 1 100 1 300 1 480 1 800 2 400 3 200 4 000
Power loss per main conducting path W 7 9 13 17 18 22 35 55
at Ie/AC-3/AC-3e/400 V
Utilization category AC-4 (at Ia = 6 x Ie)
Maximum values:
• Rated operational current Ie
- Up to 400 V A 97 132 160 195 230 280 350 430
• Rated power for squirrel-cage motors at
50 Hz and 60 Hz
- At 400 V kW 55 75 90 110 132 160 200 250
The following applies to a contact endurance
of about 200 000 operating cycles:
• Rated operational currents Ie
- Up to 500 V A 54 68 81 96 117 125 150 175
- Up to 690 V A 48 57 65 85 105 115 135 150
• Rated power for squirrel-cage motors at
50 Hz and 60 Hz
- At 230 V kW 16 20 25 30 37 40 48 56
- At 400 V kW 29 38 45 54 66 71 85 98
- At 500 V kW 37 47 57 67 82 87 105 123
- At 690 V kW 48 55 65 82 102 112 133 148
Contactors
Type 3RT105. 3RT106. 3RT107.
Size S6 S10 S12
Conductor cross-sections
Main conductors (1 or 2 conductors can be connected) Screw terminals
With mounted box terminals Type 3RT1955-4G (55 kW) 3RT1956-4G 3RT1966-4G
• Terminal screws M10 (hexagon socket, A/F 4) M12 (hexagon socket, A/F 5)
3
• Finely stranded without end sleeve 16 ... 70 16 ... 120 70 ... 240
• Stranded mm2 16 ... 70 16 ... 120 95 ... 300
• AWG cables, solid or stranded AWG 6 ... 2/0 6 ... 250 kcmil 3/0 ... 600 kcmil
• Ribbon cable conductors mm Min. 3 x 9 x 0.8, Min. 3 x 9 x 0.8, Min. 6 x 9 x 0.8,
(number x width x thickness) max. 6 x 15.5 x 0.8 max. 10 x 15.5 x 0.8 max. 20 x 24 x 0.5
Rear clamping point connected
• Finely stranded with end sleeve (DIN 46228) mm2 16 ... 70 16 ... 120 120 ... 185
NSB0_00480
• Finely stranded without end sleeve mm2 16 ... 70 16 ... 120 120 ... 185
• Stranded mm2 16 ... 70 16 ... 120 120 ... 240
• AWG cables, solid or stranded AWG 6 ... 2/0 6 ... 250 kcmil 250 ... 500 kcmil
• Ribbon cable conductors mm Min. 3 x 9 x 0.8, Min. 3 x 9 x 0.8, Min. 6 x 9 x 0.8,
(number x width x thickness) max. 6 x 15.5 x 0.8 max. 10 x 15.5 x 0.8 max. 20 x 24 x 0.5
Both clamping points connected
(minimum cross-section 16 mm²)
• Finely stranded with end sleeve (DIN 46228) mm2 Max. 1 x 50, 1 x 70 Max. 1 x 95, 1 x 120 Min. 2 x 50, max. 2 x 185
• Finely stranded without end sleeve mm2 Max. 1 x 50, 1 x 70 Max. 1 x 95, 1 x 120 Min. 2 x 50, max. 2 x 185
NSB0_00481
• Stranded mm2 Max. 1 x 50, 1 x 70 Max. 1 x 95, 1 x 120 Min. 2 x 70, max. 2 x 240
• AWG cables, solid or stranded AWG Max. 2 x 1/0 Max. 2 x 3/0 Min. 2 x 2/0,
max. 2 x 500 kcmil
• Ribbon cable conductors mm Max. 2 x (6 x 15.5 x 0.8) Max. 2 x (10 x 15.5 x 0.8) Max. 2 x (20 x 24 x 0.5)
(number x width x thickness)
Busbar connections
Connecting bar (max. width) mm 17 25
Cable lug connection
• Finely stranded with cable lug1)2) mm2 16 ... 95 50 ... 240
• Stranded with cable lug1)2) mm2 25 ... 120 70 ... 240
• AWG cables, solid or stranded AWG 4 ... 250 kcmil 2/0 ... 500 kcmil
• Terminal screws M8 x 25 (A/F 13) M10 x 30 (A/F 17)
- Tightening torque Nm 10 ... 14 14 ... 24
lb.in 90 ... 124 124 ... 210
Auxiliary conductors (1 or 2 conductors can be connected)
• Solid mm2 2 x (0.5 ... 1.5)3); 2 x (0.75 ... 2.5)3); max. 2 x (0.75 ... 4)3)
• Finely stranded with end sleeve (DIN 46228) mm2 2 x (0.5 ... 1.5)3); 2 x (0.75 ... 2.5)3)
• AWG cables, solid or stranded AWG 2 x (18 ... 14)
• Terminal screws M3 (Pozidriv size 2)
- Tightening torque Nm 0.8 ... 1.2
lb.in 7 ... 10.3
Auxiliary conductors4) (1 or 2 conductors can be connected) Spring-loaded terminals
3
(from s and u approved values)
• Rated power for three-phase motors at 200 V hp 1.5 2 3
at 60 Hz 230 V hp 2 3 5
460 V hp 3 5 7.5 10
575 V hp 5 7.5 10
Short-circuit protection at 600 V kA 5
(contactor)
• Class J fuse A 60
(values for RK5 fuses available on request)
• Circuit breakers in accordance with UL 489 A 50
("Inverse Time Breakers")
• Combination Motor Controllers (Type E) 3RV2.1 or 3RV2.2
according to UL 508 and UL 60947-4-1
Contactors
Type 3RT2023 3RT2024 3RT2025 3RT2026 3RT2326-.....-4AA0 3RT2027 3RT2028
Size S0
s and u rated data
Rated operational voltage V AC 600
Uninterrupted current, at 40 °C, open and enclosed A 30 42
Maximum horsepower ratings
(from s and u approved values)
• Rated power for three-phase motors at 200 V hp 2 3 5 3 10
at 60 Hz 230 V hp 3 5 7.5 5 10
460 V hp 5 7.5 10 15 10 20 25
575 V hp 7.5 10 15 20 15 25
Short-circuit protection at 600 V kA 5
(contactor)
• Class J fuse A 125 150
(values for RK5 fuses available on request)
• Circuit breakers in accordance with UL 489 A 70 100
("Inverse Time Breakers")
• Combination Motor Controllers (Type E) at 480 V Type 3RV202
according to UL 508 and UL 60947-4-1 at 600 V Type 3RV202
Contactors
Type 3RT2035 3RT2036, 3RT2037 3RT2038 3RT2045 3RT2046 3RT2047
3RT2336-.....-4AA0
Size S2 S3
s and u rated data
Rated operational voltage V AC 600
Uninterrupted current, at 40 °C, open and enclosed A 55 60 80 90 62 77 99
Maximum horsepower ratings
(from s and u approved values)
• Rated power for three-phase motors at 200/208 V hp 10 15 20 25 30
at 60 Hz 230/240 V hp 15 20 25 30 40
460/480 V hp 30 40 50 60 75
575/600 V hp 40 50 60 60 75 100
Short-circuit protection at 600 V kA 5 10 10
(contactor)
• RK5 fuse A 150 200 250 300 350
• Combination Motor Controllers (Type E) Type 3RV203 3RV204
according to UL 508 and UL 60947-4-1
Contactors
Type 3RT1054 3RT1055 3RT1056 3RT1064 3RT1065 3RT1066 3RT1075 3RT1076
Size S6 S10 S12
s and u rated data
Rated operational voltage V AC 600
Uninterrupted current, at 40 °C, open and A 140 195 250 330 400 540
enclosed
Maximum horsepower ratings
3
Contactors
Type 3RT201 3RT202 to 3RT204 3RT105 to 3RT107
Size S00 S0 to S3 S6 to S12
Integrated or Integrated Mountable auxiliary Mountable auxiliary
mountable auxiliary switch switch
switch
s and u rated data of the auxiliary contacts
Rated voltage V AC 600
Switching capacity A 600, Q 600 A 600, P 600 A 600, Q 600 A 600, Q 600
• Uninterrupted current at 240 V AC A 10
3
3RT201.-1A... 3RT201.-2A... 3RT201.-1AP04-3MA0 3RT201.-2AP04-3MA0
Rated data Auxiliary contacts Rated control Screw terminals Spring-loaded
AC-3 and AC-3e, AC-1, supply terminals
tu: 60 °C tu: 40 °C voltage Us
Opera- Ratings of Opera- Ident. Version 50/60 Hz AC
tional three-phase tional No.
current Ie motors at current Ie Article No. Price Article No. Price
up to 50 Hz and up to per PU per PU
400 V 400 V 690 V
A kW A NO NC V
For screw fixing and snap-on mounting on TH 35 DIN rail
Size S00
7 3 18 10 1 -- 24 3RT2015-1AB01 3RT2015-2AB01
110 3RT2015-1AF01 3RT2015-2AF01
230 3RT2015-1AP01 3RT2015-2AP01
01 -- 1 24 3RT2015-1AB02 3RT2015-2AB02
110 3RT2015-1AF02 3RT2015-2AF02
230 3RT2015-1AP02 3RT2015-2AP02
9 4 22 10 1 -- 24 3RT2016-1AB01 3RT2016-2AB01
110 3RT2016-1AF01 3RT2016-2AF01
230 3RT2016-1AP01 3RT2016-2AP01
01 -- 1 24 3RT2016-1AB02 3RT2016-2AB02
110 3RT2016-1AF02 3RT2016-2AF02
230 3RT2016-1AP02 3RT2016-2AP02
12 5.5 22 10 1 -- 24 3RT2017-1AB01 3RT2017-2AB01
110 3RT2017-1AF01 3RT2017-2AF01
230 3RT2017-1AP01 3RT2017-2AP01
01 -- 1 24 3RT2017-1AB02 3RT2017-2AB02
110 3RT2017-1AF02 3RT2017-2AF02
230 3RT2017-1AP02 3RT2017-2AP02
16 7.5 22 10 1 -- 24 3RT2018-1AB01 3RT2018-2AB01
110 3RT2018-1AF01 3RT2018-2AF01
230 3RT2018-1AP01 3RT2018-2AP01
01 -- 1 24 3RT2018-1AB02 3RT2018-2AB02
110 3RT2018-1AF02 3RT2018-2AF02
230 3RT2018-1AP02 3RT2018-2AP02
With permanently mounted auxiliary switch
7 3 18 22 2 2 230 3RT2015-1AP04-3MA0 3RT2015-2AP04-3MA0
9 4 22 22 2 2 230 3RT2016-1AP04-3MA0 3RT2016-2AP04-3MA0
12 5.5 22 22 2 2 230 3RT2017-1AP04-3MA0 3RT2017-2AP04-3MA0
16 7.5 22 22 2 2 230 3RT2018-1AP04-3MA0 3RT2018-2AP04-3MA0
With permanently mounted auxiliary switch and varistor plugged
into the front
7 3 18 22 2 2 230 3RT2015-1CP04-3MA0 3RT2015-2CP04-3MA0
9 4 22 22 2 2 230 3RT2016-1CP04-3MA0 3RT2016-2CP04-3MA0
12 5.5 22 22 2 2 230 3RT2017-1CP04-3MA0 3RT2017-2CP04-3MA0
16 7.5 22 22 2 2 230 3RT2018-1CP04-3MA0 3RT2018-2CP04-3MA0
3RT202.-1A.00 3RT202.-2A.00
Rated data Auxiliary contacts Rated control Screw terminals Spring-loaded terminals
AC-3 and AC-3e, AC-1, supply voltage
tu: 60 °C tu: 40 °C Us
Opera- Ratings of three- Opera- Ident. Version 50 Hz AC
tional phase motors at tional No.
current Ie 50 Hz and current Ie Article No. Price Article No. Price
up to up to per PU per PU
400 V 400 V 690 V
A kW A NO NC V
For screw fixing and snap-on mounting on TH 35 DIN rail
Size S0
9 4 40 11 1 1 24 3RT2023-1AB00 3RT2023-2AB00
110 3RT2023-1AF00 3RT2023-2AF00
230 3RT2023-1AP00 3RT2023-2AP00
12 5.5 40 11 1 1 24 3RT2024-1AB00 3RT2024-2AB00
110 3RT2024-1AF00 3RT2024-2AF00
230 3RT2024-1AP00 3RT2024-2AP00
17 7.5 40 11 1 1 24 3RT2025-1AB00 3RT2025-2AB00
110 3RT2025-1AF00 3RT2025-2AF00
230 3RT2025-1AP00 3RT2025-2AP00
25 11 40 11 1 1 24 3RT2026-1AB00 3RT2026-2AB00
110 3RT2026-1AF00 3RT2026-2AF00
230 3RT2026-1AP00 3RT2026-2AP00
32 15 50 11 1 1 24 3RT2027-1AB00 3RT2027-2AB00
110 3RT2027-1AF00 3RT2027-2AF00
230 3RT2027-1AP00 3RT2027-2AP00
38 18.5 50 11 1 1 24 3RT2028-1AB00 3RT2028-2AB00
110 3RT2028-1AF00 3RT2028-2AF00
230 3RT2028-1AP00 3RT2028-2AP00
3
3RT202.-1A.04 3RT202.-2A.04 3RT202.-1CL24-3MA0 3RT202.-2CL24-3MA0
Rated data Auxiliary contacts Rated control Screw terminals Spring-loaded
AC-3 and AC-3e, AC-1, supply voltage terminals
tu: 60 °C tu: 40 °C Us
Opera- Ratings of Opera- Ident. Version 50 Hz AC
tional three-phase tional No.
current Ie motors at current Ie Article No. Price Article No. Price
up to 50 Hz and up to per PU per PU
400 V 400 V 690 V
A kW A NO NC V
For screw fixing and snap-on mounting on TH 35 DIN rail
Size S0
With removable auxiliary switch
9 4 40 22 2 2 24 3RT2023-1AB04 3RT2023-2AB04
230 3RT2023-1AP04 3RT2023-2AP04
12 5.5 40 22 2 2 24 3RT2024-1AB04 3RT2024-2AB04
110 3RT2024-1AF04 3RT2024-2AF04
230 3RT2024-1AP04 3RT2024-2AP04
17 7.5 40 22 2 2 24 3RT2025-1AB04 3RT2025-2AB04
110 3RT2025-1AF04 3RT2025-2AF04
230 3RT2025-1AP04 3RT2025-2AP04
25 11 40 22 2 2 24 3RT2026-1AB04 3RT2026-2AB04
110 3RT2026-1AF04 3RT2026-2AF04
230 3RT2026-1AP04 3RT2026-2AP04
32 15 50 22 2 2 24 3RT2027-1AB04 3RT2027-2AB04
110 3RT2027-1AF04 3RT2027-2AF04
230 3RT2027-1AP04 3RT2027-2AP04
38 18.5 50 22 2 2 24 3RT2028-1AB04 3RT2028-2AB04
110 3RT2028-1AF04 3RT2028-2AF04
230 3RT2028-1AP04 3RT2028-2AP04
With permanently mounted auxiliary switch and varistor plugged in
9 4 40 22 2 2 230 3RT2023-1CL24-3MA0 3RT2023-2CL24-3MA0
12 5.5 40 22 2 2 230 3RT2024-1CL24-3MA0 3RT2024-2CL24-3MA0
17 7.5 40 22 2 2 230 3RT2025-1CL24-3MA0 3RT2025-2CL24-3MA0
25 11 40 22 2 2 230 3RT2026-1CL24-3MA0 3RT2026-2CL24-3MA0
32 15 50 22 2 2 230 3RT2027-1CL24-3MA0 3RT2027-2CL24-3MA0
38 18.5 50 22 2 2 230 3RT2028-1CL24-3MA0 3RT2028-2CL24-3MA0
3
3RT204.-1A.00 3RT204.-1A.04 3RT204.-1CL24-3MA0 3RT204.-3A.00
Rated data Auxiliary contacts Rated control Screw terminals Spring-loaded
AC-3 and AC-3e, AC-1, supply voltage terminals
tu: 60 °C tu: 40 °C Us
Opera- Ratings of Opera- Ident. Version 50 Hz AC
tional three-phase tional No.
current Ie motors at current Ie Article No. Price Article No. Price
up to 50 Hz and up to per PU per PU
400 V 400 V 690 V
A kW A NO NC V
For screw fixing and snap-on mounting on TH 35-15 and
TH 75-15 DIN rails
Size S3
80 37 125 11 1 1 24 3RT2045-1AB00 3RT2045-3AB00
110 3RT2045-1AF00 3RT2045-3AF00
230 3RT2045-1AP00 3RT2045-3AP00
95 45 130 11 1 1 24 3RT2046-1AB00 3RT2046-3AB00
110 3RT2046-1AF00 3RT2046-3AF00
230 3RT2046-1AP00 3RT2046-3AP00
110 55 130 11 1 1 24 3RT2047-1AB00 3RT2047-3AB00
110 3RT2047-1AF00 3RT2047-3AF00
230 3RT2047-1AP00 3RT2047-3AP00
With removable auxiliary switch
80 37 125 22 2 2 24 3RT2045-1AB04 --
110 3RT2045-1AF04 --
230 3RT2045-1AP04 --
95 45 130 22 2 2 24 3RT2046-1AB04 --
110 3RT2046-1AF04 --
230 3RT2046-1AP04 --
110 55 130 22 2 2 24 3RT2047-1AB04 --
110 3RT2047-1AF04 --
230 3RT2047-1AP04 --
With permanently mounted auxiliary switch and integrated coil circuit
(varistor plugged in at the factory)
80 37 125 22 2 2 230 3RT2045-1CL24-3MA0 --
95 45 130 22 2 2 230 3RT2046-1CL24-3MA0 --
110 55 130 22 2 2 230 3RT2047-1CL24-3MA0 --
3RT201.-1B... 3RT201.-2B...
Rated data Auxiliary contacts Rated control Screw terminals Spring-loaded terminals
AC-3 and AC-3e, AC-1, supply voltage
tu: 60 °C tu: 40 °C Us
Opera- Ratings of Opera- Ident. Version DC
tional three-phase tional No.
current Ie motors at current Ie Article No. Price Article No. Price
up to 50 Hz and up to per PU per PU
400 V 400 V 690 V
A kW A NO NC V
For screw fixing and snap-on mounting on TH 35 DIN rail
Size S00
7 3 18 10 1 -- 24 3RT2015-1BB41 3RT2015-2BB41
220 3RT2015-1BM41 3RT2015-2BM41
01 -- 1 24 3RT2015-1BB42 3RT2015-2BB42
220 3RT2015-1BM42 3RT2015-2BM42
9 4 22 10 1 -- 24 3RT2016-1BB41 3RT2016-2BB41
220 3RT2016-1BM41 3RT2016-2BM41
01 -- 1 24 3RT2016-1BB42 3RT2016-2BB42
220 3RT2016-1BM42 3RT2016-2BM42
12 5.5 22 10 1 -- 24 3RT2017-1BB41 3RT2017-2BB41
220 3RT2017-1BM41 3RT2017-2BM41
01 -- 1 24 3RT2017-1BB42 3RT2017-2BB42
220 3RT2017-1BM42 3RT2017-2BM42
16 7.5 22 10 1 -- 24 3RT2018-1BB41 3RT2018-2BB41
220 3RT2018-1BM41 3RT2018-2BM41
01 -- 1 24 3RT2018-1BB42 3RT2018-2BB42
220 3RT2018-1BM42 3RT2018-2BM42
With integrated coil circuit (varistor integrated at the factory)
7 3 18 10 1 -- 24 3RT2015-1UB41 3RT2015-2UB41
01 -- 1 24 3RT2015-1UB42 3RT2015-2UB42
9 4 22 10 1 -- 24 3RT2016-1UB41 3RT2016-2UB41
01 -- 1 24 3RT2016-1UB42 3RT2016-2UB42
12 5.5 22 10 1 -- 24 3RT2017-1UB41 3RT2017-2UB41
01 -- 1 24 3RT2017-1UB42 3RT2017-2UB42
16 7.5 22 10 1 -- 24 3RT2018-1UB41 3RT2018-2UB41
01 -- 1 24 3RT2018-1UB42 3RT2018-2UB42
With integrated coil circuit (diode integrated at factory)
7 3 18 10 1 -- 24 3RT2015-1FB41 3RT2015-2FB41
01 -- 1 24 3RT2015-1FB42 3RT2015-2FB42
9 4 22 10 1 -- 24 3RT2016-1FB41 3RT2016-2FB41
01 -- 1 24 3RT2016-1FB42 3RT2016-2FB42
12 5.5 22 10 1 -- 24 3RT2017-1FB41 3RT2017-2FB41
01 -- 1 24 3RT2017-1FB42 3RT2017-2FB42
16 7.5 22 10 1 -- 24 3RT2018-1FB41 3RT2018-2FB41
01 -- 1 24 3RT2018-1FB42 3RT2018-2FB42
3
3RT201.-1BB44-3MA0 3RT201.-2BB44-3MA0 3RT201.-1BB4.-0CC0 3RT201.-2BB4.-0CC0
Rated data Auxiliary contacts Rated control Screw terminals Spring-loaded terminals
AC-3 and AC-3e, AC-1, supply
tu: 60 °C tu: 40 °C voltage Us
Opera- Ratings of Opera- Ident. Version DC
tional three-phase tional No.
current Ie motors at current Ie Article No. Price Article No. Price
up to 50 Hz and up to per PU per PU
400 V 400 V 690 V
A kW A NO NC V
For screw fixing and snap-on mounting on TH 35 DIN rail
Size S00
With permanently mounted auxiliary switch
7 3 18 22 2 2 24 3RT2015-1BB44-3MA0 3RT2015-2BB44-3MA0
9 4 22 22 2 2 24 3RT2016-1BB44-3MA0 3RT2016-2BB44-3MA0
12 5.5 22 22 2 2 24 3RT2017-1BB44-3MA0 3RT2017-2BB44-3MA0
16 7.5 22 22 2 2 24 3RT2018-1BB44-3MA0 3RT2018-2BB44-3MA0
With permanently mounted auxiliary switch and integrated coil circuit
(diode integrated at the factory)
7 3 18 22 2 2 24 3RT2015-1FB44-3MA0 3RT2015-2FB44-3MA0
9 4 22 22 2 2 24 3RT2016-1FB44-3MA0 3RT2016-2FB44-3MA0
12 5.5 22 22 2 2 24 3RT2017-1FB44-3MA0 3RT2017-2FB44-3MA0
16 7.5 22 22 2 2 24 3RT2018-1FB44-3MA0 3RT2018-2FB44-3MA0
With voltage tap-off (only available with 24 V DC coils)
7 3 18 10 1 -- 24 3RT2015-1BB41-0CC0 3RT2015-2BB41-0CC0
01 -- 1 24 3RT2015-1BB42-0CC0 3RT2015-2BB42-0CC0
9 4 22 10 1 -- 24 3RT2016-1BB41-0CC0 3RT2016-2BB41-0CC0
01 -- 1 24 3RT2016-1BB42-0CC0 3RT2016-2BB42-0CC0
12 5.5 22 10 1 -- 24 3RT2017-1BB41-0CC0 3RT2017-2BB41-0CC0
01 -- 1 24 3RT2017-1BB42-0CC0 3RT2017-2BB42-0CC0
16 7.5 22 10 1 -- 24 3RT2018-1BB41-0CC0 3RT2018-2BB41-0CC0
01 -- 1 24 3RT2018-1BB42-0CC0 3RT2018-2BB42-0CC0
3RT201.-1.B4. 3RT201.-2.B4.
Rated data Auxiliary contacts Rated control Screw terminals Spring-loaded
AC-3 and AC-3e, AC-1, supply terminals
tu: 60 °C tu: 40 °C voltage Us
Opera- Ratings of Opera- Ident. Version DC
tional three-phase tional No.
current Ie motors current Ie Article No. Price Article No. Price
up to at 50 Hz and up to per PU per PU
400 V 400 V 690 V
A kW A NO NC V
For screw fixing and snap-on mounting on TH 35 DIN rail
Size S00
(cannot be expanded with auxiliary switches)
Operating range 0.7 ... 1.25 x Us,
power consumption of the solenoid coils 2.8 W at 24 V
7 3 18 10 1 -- 24 3RT2015-1HB41 3RT2015-2HB41
01 -- 1 24 3RT2015-1HB42 3RT2015-2HB42
9 4 22 10 1 -- 24 3RT2016-1HB41 3RT2016-2HB41
01 -- 1 24 3RT2016-1HB42 3RT2016-2HB42
12 5.5 22 10 1 -- 24 3RT2017-1HB41 3RT2017-2HB41
01 -- 1 24 3RT2017-1HB42 3RT2017-2HB42
Operating range 0.85 ... 1.85 x Us,
power consumption of the solenoid coils 1.6 W at 24 V
7 3 18 10 1 -- 24 3RT2015-1MB41-0KT0 3RT2015-2MB41-0KT0
01 -- 1 24 3RT2015-1MB42-0KT0 3RT2015-2MB42-0KT0
9 4 22 10 1 -- 24 3RT2016-1MB41-0KT0 3RT2016-2MB41-0KT0
01 -- 1 24 3RT2016-1MB42-0KT0 3RT2016-2MB42-0KT0
12 5.5 22 10 1 -- 24 3RT2017-1MB41-0KT0 3RT2017-2MB41-0KT0
01 -- 1 24 3RT2017-1MB42-0KT0 3RT2017-2MB42-0KT0
With integrated coil circuit (diode integrated at factory)
(cannot be expanded with auxiliary switches)
Operating range 0.7 ... 1.25 x Us,
power consumption of the solenoid coils 2.8 W at 24 V
7 3 18 10 1 -- 24 3RT2015-1JB41 3RT2015-2JB41
01 -- 1 24 3RT2015-1JB42 3RT2015-2JB42
9 4 22 10 1 -- 24 3RT2016-1JB41 3RT2016-2JB41
01 -- 1 24 3RT2016-1JB42 3RT2016-2JB42
12 5.5 22 10 1 -- 24 3RT2017-1JB41 3RT2017-2JB41
01 -- 1 24 3RT2017-1JB42 3RT2017-2JB42
Operating range 0.85 ... 1.85 x Us,
power consumption of the solenoid coils 1.6 W at 24 V
7 3 18 10 1 -- 24 3RT2015-1VB41 3RT2015-2VB41
01 -- 1 24 3RT2015-1VB42 3RT2015-2VB42
9 4 22 10 1 -- 24 3RT2016-1VB41 3RT2016-2VB41
01 -- 1 24 3RT2016-1VB42 3RT2016-2VB42
12 5.5 22 10 1 -- 24 3RT2017-1VB41 3RT2017-2VB41
01 -- 1 24 3RT2017-1VB42 3RT2017-2VB42
3
3RT201.-1.B4. 3RT201.-2.B4.
Rated data Auxiliary contacts Rated control Screw terminals Spring-loaded terminals
AC-3 and AC-3e, AC-1, supply voltage
tu: 60 °C tu: 40 °C Us
Opera- Ratings of Opera- Ident. Version DC
tional three-phase tional No.
current Ie motors current Ie Article No. Price Article No. Price
up to at 50 Hz and up to per PU per PU
400 V 400 V 690 V
A kW A NO NC V
For screw fixing and snap-on mounting on TH 35 DIN rail
Size S00
With integrated coil circuit (suppressor diode integrated at factory)
(cannot be expanded with auxiliary switches)
Operating range 0.7 ... 1.25 x Us,
power consumption of the solenoid coils 2.8 W at 24 V
7 3 18 10 1 -- 24 3RT2015-1KB41 3RT2015-2KB41
01 -- 1 24 3RT2015-1KB42 3RT2015-2KB42
9 4 22 10 1 -- 24 3RT2016-1KB41 3RT2016-2KB41
01 -- 1 24 3RT2016-1KB42 3RT2016-2KB42
12 5.5 22 10 1 -- 24 3RT2017-1KB41 3RT2017-2KB41
01 -- 1 24 3RT2017-1KB42 3RT2017-2KB42
Operating range 0.85 ... 1.85 x Us,
power consumption of the solenoid coils 1.6 W at 24 V
7 3 18 10 1 -- 24 3RT2015-1SB41 3RT2015-2SB41
01 -- 1 24 3RT2015-1SB42 3RT2015-2SB42
9 4 22 10 1 -- 24 3RT2016-1SB41 3RT2016-2SB41
01 -- 1 24 3RT2016-1SB42 3RT2016-2SB42
12 5.5 22 10 1 -- 24 3RT2017-1SB41 3RT2017-2SB41
01 -- 1 24 3RT2017-1SB42 3RT2017-2SB42
3
3RT202.-1.B44-3MA0 3RT202.-2.B44-3MA0 3RT202.-1BB40-0CC0 3RT202.-2BB40-0CC0
Rated data Auxiliary contacts Rated control Screw terminals Spring-loaded
AC-3 and AC-3e, AC-1, supply voltage terminals
tu: 60 °C tu: 40 °C Us
Opera- Ratings of Opera- Ident. Version DC
tional three-phase tional No.
current Ie motors at current Ie Article No. Price Article No. Price
up to 50 Hz and up to per PU per PU
400 V 400 V 690 V
A kW A NO NC V
For screw fixing and snap-on mounting on TH 35 DIN rail
Size S0
With permanently mounted auxiliary switch and integrated coil circuit
(varistor integrated at the factory)
12 5.5 40 22 2 2 24 3RT2024-1DB44-3MA0 3RT2024-2DB44-3MA0
17 7.5 40 22 2 2 24 3RT2025-1DB44-3MA0 3RT2025-2DB44-3MA0
25 11 40 22 2 2 24 3RT2026-1DB44-3MA0 3RT2026-2DB44-3MA0
32 15 50 22 2 2 24 3RT2027-1DB44-3MA0 3RT2027-2DB44-3MA0
With permanently mounted auxiliary switch and integrated coil circuit
(diode assembly plugged in at the factory)
9 4 40 22 2 2 24 3RT2023-1FB44-3MA0 3RT2023-2FB44-3MA0
12 5.5 40 22 2 2 24 3RT2024-1FB44-3MA0 3RT2024-2FB44-3MA0
17 7.5 40 22 2 2 24 3RT2025-1FB44-3MA0 3RT2025-2FB44-3MA0
25 11 40 22 2 2 24 3RT2026-1FB44-3MA0 3RT2026-2FB44-3MA0
32 15 50 22 2 2 24 3RT2027-1FB44-3MA0 3RT2027-2FB44-3MA0
38 18.5 50 22 2 2 24 3RT2028-1FB44-3MA0 3RT2028-2FB44-3MA0
With voltage tap-off
9 4 40 11 1 1 24 3RT2023-1BB40-0CC0 3RT2023-2BB40-0CC0
12 5.5 40 11 1 1 24 3RT2024-1BB40-0CC0 3RT2024-2BB40-0CC0
17 7.5 40 11 1 1 24 3RT2025-1BB40-0CC0 3RT2025-2BB40-0CC0
25 11 40 11 1 1 24 3RT2026-1BB40-0CC0 3RT2026-2BB40-0CC0
32 15 50 11 1 1 24 3RT2027-1BB40-0CC0 3RT2027-2BB40-0CC0
38 18.5 50 11 1 1 24 3RT2028-1BB40-0CC0 3RT2028-2BB40-0CC0
3RT202.-1KB40 3RT202.-2KB40
Rated data Auxiliary contacts Rated control Screw terminals Spring-loaded terminals
AC-3 and AC-3e, AC-1, supply voltage
tu: 60 °C tu: 40 °C Us
Opera- Ratings of three- Opera- Ident. Version DC
tional phase motors at tional No.
current Ie 50 Hz and current Ie Article No. Price Article No. Price
up to up to per PU per PU
400 V 400 V 690 V
A kW A NO NC V
For screw fixing and snap-on mounting on TH 35 DIN rail
Size S0
With integrated coil circuit (varistor integrated in electronics at the factory)
(cannot be expanded with auxiliary switches)
Operating range 0.7 ... 1.25 x Us,
power consumption of the solenoid coils 4.5 W at 24 V
9 4 40 11 1 1 24 3RT2023-1KB40 3RT2023-2KB40
12 5.5 40 11 1 1 24 3RT2024-1KB40 3RT2024-2KB40
17 7.5 40 11 1 1 24 3RT2025-1KB40 3RT2025-2KB40
25 11 40 11 1 1 24 3RT2026-1KB40 3RT2026-2KB40
32 15 50 11 1 1 24 3RT2027-1KB40 3RT2027-2KB40
3
3RT203.-1KB40 3RT203.-3KB40 3RT204.-1KB40 3RT204.-3KB40
Rated data Auxiliary contacts Rated control Screw terminals Spring-loaded terminals
AC-3 and AC-3e, AC-1, supply voltage
tu: 60 °C tu: 40 °C Us
Opera- Ratings of three- Opera- Ident. Version DC
tional phase motors at tional No.
current Ie 50 Hz and current Ie Article No. Price Article No. Price
up to up to per PU per PU
400 V 400 V 690 V
A kW A NO NC V
For screw fixing and snap-on mounting on TH 35 DIN rail
Size S2
With integrated coil circuit (varistor integrated in electronics at the factory)
Operating range 0.8 ... 1.2 x Us,
closing power of the solenoid coils 21.5 W at 24 V
41 18.5 60 11 1 1 24 3RT2035-1KB40 3RT2035-3KB40
51 22 70 11 1 1 24 3RT2036-1KB40 3RT2036-3KB40
65 30 80 11 1 1 24 3RT2037-1KB40 3RT2037-3KB40
80 37 90 11 1 1 24 3RT2038-1KB40 3RT2038-3KB40
For screw fixing and snap-on mounting on TH 35-15 and TH 75-15
DIN rails
Size S3
With integrated coil circuit (varistor integrated in electronics at the factory)
Operating range 0.8 ... 1.2 x Us,
closing power of the solenoid coils 25 W at 24 V
80 37 125 11 1 1 24 3RT2045-1KB40 3RT2045-3KB40
95 45 130 11 1 1 24 3RT2046-1KB40 3RT2046-3KB40
3RT202.-1N.30 3RT202.-2N.30
Rated data Auxiliary contacts Rated control Screw terminals Spring-loaded terminals
AC-3 and AC-3e, AC-1, supply voltage
tu: 60 °C tu: 40 °C Us
Opera- Ratings of three- Opera- Ident. Version 50/60 Hz AC
tional phase motors at tional No. or DC
current Ie 50 Hz and current Ie Article No. Price Article No. Price
up to up to per PU per PU
400 V 400 V 690 V
A kW A NO NC V
For screw fixing and snap-on mounting on TH 35 DIN rail
Size S0
With integrated coil circuit (varistor integrated in electronics at the factory)
12 5.5 40 11 1 1 21 ... 28 3RT2024-1NB30 3RT2024-2NB30
95 ... 130 3RT2024-1NF30 3RT2024-2NF30
200 ... 280 3RT2024-1NP30 3RT2024-2NP30
17 7.5 40 11 1 1 21 ... 28 3RT2025-1NB30 3RT2025-2NB30
95 ... 130 3RT2025-1NF30 3RT2025-2NF30
200 ... 280 3RT2025-1NP30 3RT2025-2NP30
25 11 40 11 1 1 21 ... 28 3RT2026-1NB30 3RT2026-2NB30
95 ... 130 3RT2026-1NF30 3RT2026-2NF30
200 ... 280 3RT2026-1NP30 3RT2026-2NP30
32 15 50 11 1 1 21 ... 28 3RT2027-1NB30 3RT2027-2NB30
95 ... 130 3RT2027-1NF30 3RT2027-2NF30
200 ... 280 3RT2027-1NP30 3RT2027-2NP30
38 18.5 50 11 1 1 21 ... 28 3RT2028-1NB30 3RT2028-2NB30
95 ... 130 3RT2028-1NF30 3RT2028-2NF30
200 ... 280 3RT2028-1NP30 3RT2028-2NP30
3
3RT203.-1N.30 3RT203.-3N.30 3RT203.-1N.34 3RT203.-1NB34-3MA0 3RT203.-3NB34-3MA0
Rated data Auxiliary contacts Rated control Screw terminals Spring-loaded terminals
AC-3 and AC-3e, AC-1, supply voltage
tu: 60 °C tu: 40 °C Us
Opera- Ratings of Opera- Ident. Version 50/60 Hz AC
tional three-phase tional No. or DC
current Ie motors at 50 Hz current Ie Article No. Price Article No. Price
up to and up to per PU per PU
400 V 400 V 690 V
A kW A NO NC V
For screw fixing and snap-on mounting on TH 35 DIN rail
Size S2
With integrated coil circuit (varistor integrated in electronics at
the factory)
41 18.5 60 11 1 1 20 ... 33 3RT2035-1NB30 3RT2035-3NB30
83 ... 155 3RT2035-1NF30 3RT2035-3NF30
175 ... 280 3RT2035-1NP30 3RT2035-3NP30
51 22 70 11 1 1 20 ... 33 3RT2036-1NB30 3RT2036-3NB30
83 ... 155 3RT2036-1NF30 3RT2036-3NF30
175 ... 280 3RT2036-1NP30 3RT2036-3NP30
65 30 80 11 1 1 20 ... 33 3RT2037-1NB30 3RT2037-3NB30
83 ... 155 3RT2037-1NF30 3RT2037-3NF30
175 ... 280 3RT2037-1NP30 3RT2037-3NP30
80 37 90 11 1 1 20 ... 33 3RT2038-1NB30 3RT2038-3NB30
83 ... 155 3RT2038-1NF30 3RT2038-3NF30
175 ... 280 3RT2038-1NP30 3RT2038-3NP30
With removable auxiliary switch and integrated coil circuit
(varistor integrated in electronics at the factory)
41 18.5 60 22 2 2 20 ... 33 3RT2035-1NB34 --
83 ... 155 3RT2035-1NF34 --
175 ... 280 3RT2035-1NP34 --
51 22 70 22 2 2 20 ... 33 3RT2036-1NB34 --
83 ... 155 3RT2036-1NF34 --
175 ... 280 3RT2036-1NP34 --
65 30 80 22 2 2 20 ... 33 3RT2037-1NB34 --
83 ... 155 3RT2037-1NF34 --
175 ... 280 3RT2037-1NP34 --
80 37 90 22 2 2 20 ... 33 3RT2038-1NB34 --
83 ... 155 3RT2038-1NF34 --
175 ... 280 3RT2038-1NP34 --
With permanently mounted auxiliary switch and integrated coil circuit
(varistor integrated in electronics at the factory)
41 18.5 60 22 2 2 20 ... 33 3RT2035-1NB34-3MA0 3RT2035-3NB34-3MA0
51 22 70 22 2 2 20 ... 33 3RT2036-1NB34-3MA0 3RT2036-3NB34-3MA0
65 30 80 22 2 2 20 ... 33 3RT2037-1NB34-3MA0 3RT2037-3NB34-3MA0
80 37 90 22 2 2 20 ... 33 3RT2038-1NB34-3MA0 3RT2038-3NB34-3MA0
With voltage tap-off and integrated coil circuit (varistor integrated in
electronics at the factory)
41 18.5 60 11 1 1 20 ... 33 3RT2035-1NB30-0CC0 3RT2035-3NB30-0CC0
51 22 70 11 1 1 20 ... 33 3RT2036-1NB30-0CC0 3RT2036-3NB30-0CC0
65 30 80 11 1 1 20 ... 33 3RT2037-1NB30-0CC0 3RT2037-3NB30-0CC0
80 37 90 11 1 1 20 ... 33 3RT2038-1NB30-0CC0 3RT2038-3NB30-0CC0
3
3RT204.-1N.30 3RT204.-3N.30 3RT204.-1N.34 3RT204.-1NB34-3MA0 3RT204.-3NB34-3MA0
Rated data Auxiliary contacts Rated control Screw terminals Spring-loaded
AC-3 and AC-3e, AC-1, supply voltage terminals
tu: 60 °C tu: 40 °C Us
Opera- Ratings of Opera- Ident. Version 50/60 Hz AC
tional three-phase tional No. or DC
current Ie motors at current Ie Article No. Price Article No. Price
up to 50 Hz and up to per PU per PU
400 V 400 V 690 V
A kW A NO NC V
For screw fixing and snap-on mounting on TH 35-15 and
TH 75-15 DIN rails
Size S3
With integrated coil circuit (varistor integrated in electronics at
the factory)
80 37 125 11 1 1 20 ... 33 3RT2045-1NB30 3RT2045-3NB30
83 ... 155 3RT2045-1NF30 3RT2045-3NF30
175 ... 280 3RT2045-1NP30 3RT2045-3NP30
95 45 130 11 1 1 20 ... 33 3RT2046-1NB30 3RT2046-3NB30
83 ... 155 3RT2046-1NF30 3RT2046-3NF30
175 ... 280 3RT2046-1NP30 3RT2046-3NP30
110 55 130 11 1 1 20 ... 33 3RT2047-1NB30 3RT2047-3NB30
83 ... 155 3RT2047-1NF30 3RT2047-3NF30
175 ... 280 3RT2047-1NP30 3RT2047-3NP30
With removable auxiliary switch and integrated coil circuit
(varistor integrated in electronics at the factory)
80 37 125 22 2 2 20 ... 33 3RT2045-1NB34 --
83 ... 155 3RT2045-1NF34 --
175 ... 280 3RT2045-1NP34 --
95 45 130 22 2 2 20 ... 33 3RT2046-1NB34 --
83 ... 155 3RT2046-1NF34 --
175 ... 280 3RT2046-1NP34 --
110 55 130 22 2 2 20 ... 33 3RT2047-1NB34 --
83 ... 155 3RT2047-1NF34 --
175 ... 280 3RT2047-1NP34 --
With permanently mounted auxiliary switch and integrated coil circuit
(varistor integrated in electronics at the factory)
80 37 125 22 2 2 20 ... 33 3RT2045-1NB34-3MA0 3RT2045-3NB34-3MA0
95 45 130 22 2 2 20 ... 33 3RT2046-1NB34-3MA0 3RT2046-3NB34-3MA0
110 55 130 22 2 2 20 ... 33 3RT2047-1NB34-3MA0 3RT2047-3NB34-3MA0
With voltage tap-off and integrated coil circuit (varistor integrated in
electronics at the factory)
80 37 125 11 1 1 20 ... 33 3RT2045-1NB30-0CC0 3RT2045-3NB30-0CC0
95 45 130 11 1 1 20 ... 33 3RT2046-1NB30-0CC0 3RT2046-3NB30-0CC0
110 55 130 11 1 1 20 ... 33 3RT2047-1NB30-0CC0 3RT2047-3NB30-0CC0
PS* = 1 unit
PG = 41B
3
- Fail-safe applications can be implemented using • Guide of use for contactors in safety applications
this contactor.
• Version with removable lateral auxiliary switches or
permanently mounted auxiliary switches
Size Rated data according to IEC 60947-4-1 Auxiliary Rated control Screw terminals PU PS* PG
AC-3 and AC-3e, contacts, supply voltage (UNIT,
tu: 60 °C lateral Us SET, M)
Operational Rating of three-phase Version 50/60 Hz AC
current Ie motors at 50 Hz and or DC
up to Article No. Price
per PU
500 V 400 V
A kW NO NC V
Solid-state operating mechanism
With two removable laterally mounted auxiliary switches
With integrated coil circuit (varistor integrated in electronics at the factory)
S6 115 55 2 2 96 ... 127 3RT1054-6SF36 1 1 unit 41B
200 ... 277 3RT1054-6SP36 1 1 unit 41B
150 75 2 2 96 ... 127 3RT1055-6SF36 1 1 unit 41B
200 ... 277 3RT1055-6SP36 1 1 unit 41B
185 90 2 2 96 ... 127 3RT1056-6SF36 1 1 unit 41B
200 ... 277 3RT1056-6SP36 1 1 unit 41B
S10 225 110 2 2 96 ... 127 3RT1064-6SF36 1 1 unit 41B
200 ... 277 3RT1064-6SP36 1 1 unit 41B
265 132 2 2 96 ... 127 3RT1065-6SF36 1 1 unit 41B
200 ... 277 3RT1065-6SP36 1 1 unit 41B
300 160 2 2 96 ... 127 3RT1066-6SF36 1 1 unit 41B
200 ... 277 3RT1066-6SP36 1 1 unit 41B
S12 400 200 2 2 96 ... 127 3RT1075-6SF36 1 1 unit 41B
200 ... 277 3RT1075-6SP36 1 1 unit 41B
500 250 2 2 96 ... 127 3RT1076-6SF36 1 1 unit 41B
200 ... 277 3RT1076-6SP36 1 1 unit 41B
With two permanently laterally mounted auxiliary switches
With integrated coil circuit (varistor integrated in electronics at the factory)
S6 115 55 2 2 96 ... 127 3RT1054-6SF36-3PA0 1 1 unit 41B
200 ... 277 3RT1054-6SP36-3PA0 1 1 unit 41B
150 75 2 2 96 ... 127 3RT1055-6SF36-3PA0 1 1 unit 41B
200 ... 277 3RT1055-6SP36-3PA0 1 1 unit 41B
185 90 2 2 96 ... 127 3RT1056-6SF36-3PA0 1 1 unit 41B
200 ... 277 3RT1056-6SP36-3PA0 1 1 unit 41B
S10 225 110 2 2 96 ... 127 3RT1064-6SF36-3PA0 1 1 unit 41B
200 ... 277 3RT1064-6SP36-3PA0 1 1 unit 41B
265 132 2 2 96 ... 127 3RT1065-6SF36-3PA0 1 1 unit 41B
200 ... 277 3RT1065-6SP36-3PA0 1 1 unit 41B
300 160 2 2 96 ... 127 3RT1066-6SF36-3PA0 1 1 unit 41B
200 ... 277 3RT1066-6SP36-3PA0 1 1 unit 41B
S12 400 200 2 2 96 ... 127 3RT1075-6SF36-3PA0 1 1 unit 41B
200 ... 277 3RT1075-6SP36-3PA0 1 1 unit 41B
500 250 2 2 96 ... 127 3RT1076-6SF36-3PA0 1 1 unit 41B
200 ... 277 3RT1076-6SP36-3PA0 1 1 unit 41B
PG = 41B
Other voltages according to page 3/68 on request. Accessories and spare parts, see pages 3/69 to 3/119.
■ Options
Rated control supply voltages for 3RT20 contactors,
possible on request (change of the 10th and 11th digits of the article number)
Delivery time on request
Rated control supply Contactor type 3RT201, 3RH2 3RT202 3RT203 3RT204
voltage Us Size S00 S0 S2 S3
Sizes S00 to S3
3
AC operation1)
Solenoid coils for 50 Hz
(exception: Size S00: 50 and 60 Hz2))
24 V AC B0 B0 B0 B0
42 V AC D0 D0 D0 D0
48 V AC H0 H0 H0 H0
110 V AC F0 F0 F0 F0
230 V AC P0 P0 P0 P0
240 V AC U0 U0 U0 U0
400 V AC V0 V0 V0 V0
Solenoid coils for 50 and 60 Hz2)
24 V AC B0 C2 C2 C2
42 V AC D0 D2 D2 D2
48 V AC H0 H2 H2 H2
110 V AC F0 G2 G2 G2
220 V AC N2 N2 N2 N2
230 V AC P0 L2 L2 L2
Solenoid coils (for USA and Canada3))
50 Hz 60 Hz
110 V AC 120 V AC K6 K6 K6 K6
220 V AC 240 V AC P6 P6 P6 P6
Solenoid coils (for Japan)
50/60 Hz4) 60 Hz5)
100 V AC 110 V AC G6 G6 G6 G6
200 V AC 220 V AC N6 N6 N6 N6
400 V AC 440 V AC R6 R6 R6 R6
DC operation1)
12 V DC A4 A4 -- --
24 V DC B4 B4 -- --
42 V DC D4 D4 -- --
48 V DC W4 W4 -- --
60 V DC E4 E4 -- --
110 V DC F4 F4 -- --
125 V DC G4 G4 -- --
220 V DC M4 M4 -- --
230 V DC P4 P4 -- --
Examples
AC operation 3RT2023-1AP00 Contactor with screw terminals; with solenoid coil for 50 Hz for rated control supply voltage 230 V AC.
3RT2023-1AG20 Contactor with screw terminals; with solenoid coil for 50/60 Hz for rated control supply voltage 110 V AC.
DC operation 3RT2025-2BB40 Contactor with spring-loaded terminals; for rated control supply voltage 24 V DC.
3RT2025-2BG40 Contactor with spring-loaded terminals; for rated control supply voltage 125 V DC.
1) 4)
For deviating coil voltages and operating ranges of sizes S00 and S0, Coil operating range
a SITOP 24 V DC power supply with wide-range input can be used for - Size S00:
the coil control, see page 15/1 and Catalog KT 10.1. at 50/60 Hz: 0.85 to 1.1 x Us,
2)
Coil operating range - Size S0:
- at 50 Hz: 0.8 to 1.1 x Us, at 50 Hz: 0.8 to 1.1 x Us,
- at 60 Hz: 0.85 to 1.1 x Us. at 60 Hz: 0.85 to 1.1 x Us.
3) 5) Coil operating range at 60 Hz: 0.8 to 1.1 x U .
Coil operating range s
- Size S00:
at 50 Hz: 0.85 to 1.1 x Us,
at 60 Hz: 0.8 to 1.1 x Us,
- Sizes S0 to S3: at 50 Hz and 60 Hz: 0.8 to 1.1 x Us.
Rated control supply voltage Contactor type 3RT202.-.N Rated control supply voltage Contactor type 3RT203.-.N 3RT204.-.N
Us min to Us max1) Size S0 Us min to Us max1) Size S2 S3
Sizes S00 to S3
AC/DC operation (50/60 Hz AC or DC)
21 ... 28 V AC/DC B3 20 ... 33 V AC/DC B3 B3
95 ... 130 V AC/DC F3 48 ... 80 V AC/DC E3 E3
200 ... 280 V AC/DC2) P3 83 ... 155 V AC/DC F3 F3
175 ... 280 V AC/DC P3 P3
1) 2)
Coil operating range The following applies to S0 and Us max = 280 V: Upper limit = 1.1 x Us max
- Size S0: 0.7 x Us min to 1.3 x Us max,
- Sizes S2 and S3: 0.8 x Us min to 1.1 x Us max.
■ Overview
Extensive accessories and spare parts are available for
SIRIUS 3RT power contactors and SIRIUS 3RH2 contactor relays. More information
These components are easily fitted to the contactors without TIA Selection Tool Cloud (TST Cloud), see
www.siemens.com/tstcloud/?node=Contactor
the use of any tools according to requirements.
Overview graphics with mountable accessories:
• 3RT2 contactors, see pages 3/8 to 3/11
3
• 3RT10, 3RT12 and 3RT14 contactors, see pages 3/12 to 3/16
• 3RH2 contactor relays, see page 5/5
3
(combination of interference suppression diode and Zener
3RT2 contactors and 3RH2 contactor relays diode for short break times) can also be used.
See pages 3/76 and 3/95 The surge suppressors are plugged onto the front of size S00
The 3RA28 solid-state time-delayed auxiliary switches which contactors. Space is provided for them next to a snap-on
can be mounted on the contactor are designed for applications auxiliary switch.
in the range from 24 to 240 V AC/DC (wide voltage range). Both Varistors, RC elements or diode assemblies can be plugged
the electrical and mechanical connection are made by simple onto the front of size S0 to S3 contactors. Exception: For size S3,
snapping on and locking. the RC element is inserted on the front into the recesses to the
The time-delay auxiliary switch is supplied with power directly by left of the connection block.
two plug-in contacts through the coil terminals of the contactor, Coupling contactors are supplied either without overvoltage
in parallel with A./A2. damping or with a suppressor diode, varistor or diode
A protection circuit (varistor) is integrated in each module. connected as standard, according to the version.
A sealable cover is available to protect against careless Note:
adjustment of the set times. The break times of the contactor, the opening delay times of the
Note: NO contacts and the closing delay times of the NC contacts
increase with damping.
Mounting more auxiliary switches on the contactor is not
permitted. For more detailed information about how damping affects the
time response, see Equipment Manual.
Coupling links for control by PLC
See pages 3/78 and 3/99
• Operation with 24 V DC
• Operating range 17 to 30 V
• Low power consumption of 0.5 W
• An LED indicates the switching state.
The 3RH2924-1GP11 coupling link has an integrated surge
suppressor (varistor) for the contactor coil being switched and
is mounted on the size S0 contactor coil via a coil connection
module.
Protection of the device connections modules for the main circuit, these starters can be assembled
easily and with absolutely no errors.
The specifications for short-circuit protection (fuses, circuit
breakers, or miniature circuit breakers) are available for the The entire sequence in the control circuit is integrated in the
device connections of the main circuit and the auxiliary circuit. snap-on modules. This covers:
In order to ensure a holistic view for the protection of the device • An adjustable star time t from 0.5 to 60 s
connections, the manufacturer is obliged to provide all relevant • A non-adjustable dead interval of 50 ms
information for short-circuit protection and overcurrent • Electrical contacting of the contactors by means of coil
protection. pick-off (contact legs)
• Feedback of the switching state at the contactor using
For more information, for example if device connections for a mechanical switch position indicator (plunger)
the control supply voltage, the supply voltage, or digital • Electrical interlocking between the contactors
inputs/digital outputs are not connected to self-limiting current
sources or energy sources, see Equipment Manual or the These modules do not require their own terminals and can
technical product data sheet. therefore be used for contactors with both screw and spring-
loaded terminals in all the sizes S00 to S3. To start the star-delta
SIRIUS function modules for direct-on-line starting (wye-delta) starter, only the first of the three contactors (line
The electronic timing relays which can be mounted on the contactor) is actuated, like in the case of a direct-on-line starter.
contactor are available in these versions: All other functions then take place inside the individual modules.
• Sizes S00 and S0 for applications in the range from 24 to This also offers advantages if the timing function was previously
240 V AC/DC (wide voltage range) implemented in a controller, as it again results in a significant
• Sizes S2 and S3 for applications in either the range from reduction in the number of PLC outputs, the programming work
24 to 90 V AC/DC or 90 to 240 V AC/DC and the wiring outlay.
Both the electrical and mechanical connection are made The kits for the main circuit include the mechanical interlock,
by simple snapping on and locking. the star jumper, the wiring modules at the top and at the bottom,
and the required connectors or connecting clips.
A protection circuit (varistor) is integrated in each module.
A protection circuit (varistor) is integrated in the basic module.
The electronic timing relay with semiconductor output uses two
contact legs to actuate the contactor underneath by means of The function modules for star-delta (wye-delta) starting are
a semiconductor after the set time t has elapsed. mostly used where current-limiting measures for starting a drive
are required and a high level of availability is essential at the
The switching state feedback is performed by a mechanical same time. This technology has been used with success for
switching state indicator (plunger). In addition, the auxiliary several decades and has the additional advantage of requiring
switches in the contactors are freely accessible and can be used relatively little know-how. Through the use of function modules,
for feedbacks to the control system or for signal lamps. the assembly work with simple standard components is even
A sealable cover is available to protect against careless easier and absolutely error-free.
adjustment of the set times. The use of function modules for star-delta (wye-delta) starting
The snap-on function modules for direct-on-line starting are results in the following advantages:
used above all for realizing timing functions independently of • Operation solely through the line contactor A1/A2 – no further
the control system. control current wiring needed
With the OFF-delay variant of the timing relay it is possible for • Prevention of wiring errors
example for the fan motor for cooling a main drive to be switched • Reduction of testing costs
off with a delay so that sufficient cooling after operation is • Integrated electrical interlocking saves costs and prevents
guaranteed; the programmer of the control system does not errors
need to worry about such technical details of the plant. • Less space needed in the control cabinet compared to using
a separate timing relay
The ON-delay timing relays enable for example the time-delayed • Adjustable starting in star mode from 0.5 to 60 s
starting of several drives so that the summation starting current • Independent of the contactor's control supply voltage
does not rise too high, which could result in voltage failure. (24 to 240 V AC/DC)
• Varistor integrated – no additive protection circuit required
The use of snap-on function modules for direct-on-line starting • Mechanically coded assembly enables easy configuration
results in the following advantages: and reliable wiring
• Reduction of control current wiring • Fewer versions – one module kit for screw and spring-loaded
• Prevention of wiring errors connection and for all the contactor sizes S00 to S3
• Reduction of testing costs • Mechanical interlocking (with wiring kit for the main circuit)
• Implementation of timing functions independently of the
control system
• Less space required in the control cabinet compared to
a separate timing relay
• No additive protection circuit required (varistor integrated)
3
system via either IO-Link or AS-Interface. amounts to the control supply voltage and the two individual
wires for AS-Interface.
The electrical and mechanical connection to the contactor
is established by snapping on and locking the respective The following essential signals are thus transmitted:
modules. An additive protection circuit for the individual • Availability of the feeder in response to an indirect inquiry from
contactors can be dispensed with completely because a varistor the motor starter protector/circuit breaker
is integrated in the modules. Feedback from the contactor
contacts is performed with Hall sensors which provide reliable • Starter control
feedback on the switching state even under extremely dusty • Feedback concerning the switching state of the starter
conditions.
Availability
Control
NSB0_02084a
Availability
Control
NSB0_02085a
Contactor
NSB0_02086
Availability signal through voltage tap-off
The following benefits result from the use of SIRIUS 3RA27 Protection of the device connections
function modules:
The specifications for short-circuit protection (fuses, circuit
• Reduction of control current wiring. In the case of IO-Link to no breakers, or miniature circuit breakers) are available for the
more than three cables for four feeders. device connections of the main circuit and the auxiliary circuit.
• Elimination of testing costs and wiring errors In order to ensure a holistic view for the protection of the device
• Reduction of configuration work connections, the manufacturer is obliged to provide all relevant
• Parameter server functionality information for short-circuit protection and overcurrent protection.
• Integration in TIA means unambiguous IO-Link diagnostics For more information, for example if device connections for the
if a fault occurs control supply voltage, the supply voltage, or digital inputs/digital
• Dispensing with IO modules saves space in the control outputs are not connected to self-limiting current sources or
cabinet energy sources, see Equipment Manual or the technical product
data sheet.
• All essential timing and interlocking functions for reversing
duty and star-delta (wye-delta) starting are integrated
• No additive protection circuit required
For more information on IO-Link and AS-Interface, see
"Industrial communication", page 2/1 onwards.
SIRIUS 3RA2711 function modules for IO-Link for mounting on 3RT2 contactors
By grouping up to four starters, it is possible to connect up to at the ET 200SP or S7-1200 master and at the switching devices,
16 starters to one master of the ET 200SP or S7-1200. In this the wiring can be further reduced by connecting the supply
case all the signals of the individual controls are made available voltage of the contactor coils to the communication wires via
directly in the process image of the input through only three jumpers.
individual wires per starter group. If the same potential is present
Port 1
NSB0_02087b
...
Port 2
3
And with IO modules no longer needed, the width of the PLC
• Manual mode is far smaller.
• Process image fault
This easy integration of the starters in the TIA world does not limit
the flexibility in the field in the least. For example, all function
modules have special terminals in order to enable direct local
disconnection. These terminals can be connected for example
to a position switch. The input interrupts the voltage supply to
the contactor coil directly, i.e. without going through the PLC.
These terminals are jumpered in the delivery state.
SIRIUS 3RA2712 function modules for AS-Interface for mounting on 3RT2 contactors
NSB0_02088b
Addr. 1a Addr. 1b Addr. 2a
AS-Interface
■ Technical specifications
More information
TIA Selection Tool Cloud (TST Cloud), see FAQs
www.siemens.com/tstcloud/?node=Contactor • SIRIUS 3RT2 contactors and SIRIUS 3RH2 contactor relays, see
Technical specifications https://support.industry.siemens.com/cs/ww/en/ps/16208/faq
• SIRIUS 3RT2 contactors and SIRIUS 3RH2 contactor relays, see • SIRIUS 3RT1 contactors, see
https://support.industry.siemens.com/cs/ww/en/ps/16208/td https://support.industry.siemens.com/cs/ww/en/ps/16209/faq
• SIRIUS 3RT1 contactors, see System Manual for modular system, see
3
https://support.industry.siemens.com/cs/ww/en/ps/16209/td https://support.industry.siemens.com/cs/ww/en/view/60311318
Equipment Manual, see
https://support.industry.siemens.com/cs/ww/en/view/60306557
3
• Terminal screws M3 (for standard screwdriver size 2 or Pozidriv 2)
• Tightening torque Nm 0.8 ... 1.2
Connection type Spring-loaded terminals
(1 or 2 conductors can be connected)
• Solid mm2 2 x (0.25 ... 1.5)
• Finely stranded with end sleeve (DIN 46228) mm2 2 x (0.25 ... 1.5)
• Finely stranded without end sleeve mm2 2 x (0.25 ... 1.5)
• AWG cables, solid or stranded AWG 2 x (24 ... 16)
• Operating devices mm 3.0 x 0.5
3
Dimensions (basic unit with mounted function module) See 3RT2 contactors (pages 3/29, 3/32, 3/35, 3/38) and
3RH2 contactor relays (page 5/8)
Rated insulation voltage Ui V AC 300
Pollution degree 3,
overvoltage category III
Rated impulse withstand voltage Uimp kV AC 4
Overvoltage protection Varistor integrated
Recovery time ms 50 150
Minimum ON duration ms -- 35 --
Setting accuracy, typ., 15%
with reference to upper limit of scale
Repeat accuracy, max. 1%
Permissible ambient temperature
• During operation °C -25 ... +60
• During storage °C -40 ... +80
Electromagnetic compatibility (EMC) IEC 61000-6-2, IEC 61000-6-4, IEC 61812-1, IEC 60947-4-1
Control side
Operating range of excitation 0.85 ... 1.1 x Us,
0.95 ... 1.05 times the rated frequency
Rated power W 1
• Power consumption at 230 V AC, 50 Hz VA 1 2
Load side
Mechanical endurance Operating 100 x 106 10 x 106
cycles
Electrical endurance
• With 3RT2028 contactor Operating 100 000 --
cycles
• At AC-15, 250 V, 3 A Operating -- 100 000
cycles
Residual current, max. mA 5 -- --
Voltage drop, max., with conducting output VA 3.5 -- --
Short-circuit protection
Version of the fuse link required for short-circuit protection of A -- Fuse gL/gG: 4
the auxiliary switch
Conductor cross-sections
Connection type Screw terminals
(1 or 2 conductors can be connected)
• Solid mm2 1 x (0.5 ... 4), 2 x (0.5 ... 2.5) --
• Finely stranded with end sleeve (DIN 46228) mm2 1 x (0.5 ... 2.5), 2 x (0.5 ... 1.5) --
• AWG cables, solid or stranded AWG 2 x (20 ... 14) --
• Terminal screws M3 (for standard screwdriver size 2 or Pozidriv 2) --
• Tightening torque Nm 0.8 ... 1.2 --
Connection type Spring-loaded terminals
(1 or 2 conductors can be connected)
• Operating devices mm 3.0 x 0.5 --
• Solid mm2 2 x (0.25 ... 1.5) --
• Finely stranded with end sleeve (DIN 46228) mm2 2 x (0.25 ... 1.5) --
• Finely stranded without end sleeve mm2 2 x (0.25 ... 1.5) --
• AWG cables, solid or stranded AWG 2 x (24 ... 16) --
■ Overview
Auxiliary switch: Terminal designations and identification numbers for auxiliary contacts
Terminal designations Identification numbers
The terminal designations are 2-digit, e.g. 13, 14, 21, 22: The identification number indicates the number and type of the
• Tens digit: Sequence digit auxiliary contacts, e.g. 40, 31, 22, 13:
- Related terminals have the same sequence digit • 1st digit: number of normally open contacts (NO)
• 2nd digit: number of normally closed contacts (NC)
3
• Units digit: Function digit
- 1-2 for normally closed contacts (NC) Examples:
- 3-4 for normally open contacts (NO) • 31 = 3 NO + 1 NC
• 40 = 4 NO
Selection aid for mountable auxiliary switches for power contactors and contactor relays
The auxiliary switches of the 3RH29 series for mounting on the
front and side can be used for 3RT2 power contactors as well as Example 1 Example 2
for 3RH2 contactor relays. Type 3RT20 motor contactor, 3RT20 motor contactor,
S00 with 1 NO S0 with 1 NO + 1 NC
The possible combinations of basic unit and mounted auxiliary
switch can be found in the tables, see the following pages.
1 3 5
Where the columns and lines intersect (blue and green in the
SIRIUS
example) you will find the identification number for the 3. 4. 5. 6.
combination of basic unit (column) and auxiliary switch (line). 13 21 A1
1 3 5 13
SIRIUS
A1
2. 3. 4. 5.
Additional auxiliary switch 3-pole contactors
Article number Auxiliary contacts 3RT201 3RT201 3RT202
to
3RT204 3. 4. 5. 6.
Version S00 S00 S0 to S3 14 22 A2
NO NC 10 01 11 2. 3. 4. 5.
2 4 6
13 21 13 21 2 4 6 14 A2
Sequence
digit 2. 3. 4. 5. 3. 4. 5. 6.
14 22 14 22
Type Auxiliary switch with 4 NC, Auxiliary switch with 3 NC,
2. 3. 4. 5. 5. 6. 7. 8. 3. 4. 5. 6.
3RH2911-.FA04 3RH2911-.HA03
According to EN 500121)
.1 .1 .1 .1 .1 .1 .1
Auxiliary switches without NO contact
3RH2911- HA01 -- 1 .1 11 02 12
.2
.2 .2 .2 .2 .2 .2 .2
3RH2911- HA02 -- 2 .1 .1 12 03 13
Function 1. 1. 1. 1. 1. 1. 1.
digit 2. 2. 2. 2. 2. 2. 2.
.2 .2 Combi- 3RT20 motor contactor, 3RT20 motor contactor,
3RH2911- HA03 -- 3 .1 .1 .1 13 04 14 nation S00 with aux. switch S0 with aux. switch
.2 .2 .2
3RH2911- FA04 -- 4 .1 .1 .1 .1 14 -- --
IC01_00716
SIRIUS
3. 4. 5. 6.
.2 .2 .2 .2 13 21 A1
Auxiliary switch with 1 NO contact SIRIUS
13 A1 .1 .1
.1
2. 3. 4. 5.
3RH2911- HA10 1 -- .3 20 11 21
.1 .1 .1 .1
.4
.2 .2 .2
1 For screw terminals
14 22 A2
2 For spring-loaded terminals
.2 .2 .2 .2
1)
Combinations according to EN 50012, EN 50011 and IEC 60947-5-1 are in 14 A2
IC01_00717a
14 22 14 22 14 22 14 22 14 24 34 44 14 22 34 44 14 22 32 44
2. 3. 4. 5. 5. 6. 7. 8. 3. 4. 5. 6. 1. 2. 3. 4. 1. 2. 3. 4. 3. 4. 5. 6. 3. 4. 5. 6. 5. 6. 7. 8. 5. 6. 7. 8. 5. 6. 7. 8.
According to EN 500121) According to EN 500121) According to EN 500111)
Auxiliary switches, front
Without NO contact
3RH2911-@HA01 -- 1 .1 11 02 12 01 01 12 12 41X 32X 23X
.2
3RH2911-@HA02 -- 2 .1 .1 12 03 13 02 02 13 -- 42E 33X 24
.2 .2
3RH2911-@HA03 -- 3 .1 .1 .1 13 04 14 03 -- -- -- 43 34 --
.2 .2 .2
3RH2911-@FA04 -- 4 .1 .1 .1 .1 14 -- -- -- -- -- -- 44E -- --
.2 .2 .2 .2
With 1 NO contact
3RH2911-@HA10 1 -- .3 20 11 21 10 10 21 21 50E 41E 32E
.4
3RH2911-@HA11 1 1 .1 .3 21 12 22 11 11 22 22 51X 42X 33X
.2 .4
3RH2911-@HA12 1 2 .1 .1 .3 22 13 23 12 12 23 -- 52 43 34
.2 .2 .4
3RH2911-@HA13 1 3 .1 .1 .1 .3 23 14 24 13 -- -- -- 53X 44X --
.2 .2 .2 .4
With 2 NO contacts
3RH2911-@HA20 2 -- .3 .3 30 21 31 20 20 31 31 60E 51X 42X
.4 .4
3RH2911-@HA21 2 1 .1 .3 .3 31 22 32 21 21 32 32 61 52 43
.2 .4 .4
3RH2911-@HA22 2 2 .1 .1 .3 .3 32 23 33 22 22 33 -- 62X 53 44X
.2 .2 .4 .4
3RH2911-@FA22 2 2 .3 .1 .1 .3 32 23 33 22 22 33 -- 62X 53 44X
.4 .2 .2 .4
With 3 NO contacts
3RH2911-@HA30 3 -- .3 .3 .3 40 31 41 30 30 41 41 70 61 52
.4 .4 .4
3RH2911-@HA31 3 1 .1 .3 .3 .3 41 32 42 31 31 42 42 71X 62X 53X
.2 .4 .4 .4
With 4 NO contacts
3RH2911-@FA40 4 -- .3 .3 .3 .3 50 41 51 40 40 51 51 80E 71X 62X
.4 .4 .4 .4
1) Combinations according to EN 50012, EN 50011 and IEC 60947-5-1 are in bold print. All combinations comply with EN 50005.
3
14 22 14 22 14 22 14 22 14 24 34 44 14 22 34 44 14 22 32 44
2. 3. 4. 5. 5. 6. 7. 8. 3. 4. 5. 6. 1. 2. 3. 4. 1. 2. 3. 4. 3. 4. 5. 6. 3. 4. 5. 6. 5. 6. 7. 8. 5. 6. 7. 8. 5. 6. 7. 8.
According to EN 50005 According to EN 50005 According to EN 50005
Auxiliary switches, front
(continued)
With make-before-break1)
3RH2911-@FB11 1 1 .7 .5 21 12 22 11 11 22 22 51 42 33
.8 .6
3RH2911-@FB22 2 2 .3 .1 .5 .7 32 23 33 22 22 33 -- 62 53 44
.4 .2 .6 .8
3RH2911-@FC22 2 2 .7 .7 .5 .5 32 23 33 22 22 33 -- 62 53 44
.8 .8 .6 .6
74
3RH2911-1BA10 1 -- 73 20 11 21 10 10 21 21 50 41 32
74
3RH2911-1AA01 -- 1 71 11 02 12 01 01 12 12 41 32 23
72
3RH2911-1BA01 -- 1 71 11 02 12 01 01 12 12 41 32 23
72
3RH2911-1LA11 1 1 73 81 21 12 22 11 11 22 22 51 42 33
74 82
3RH2911-1MA11 1 1 73 81 21 12 22 11 11 22 22 51 42 33
74 82
3RH2911-1LA20 2 -- 73 83 30 21 31 20 20 31 31 60 51 42
74 84
3RH2911-1MA20 2 -- 73 83 30 21 31 20 20 31 31 60 51 42
74 84
1) Contacts with make-before-break have no mirror contact function.
14 22 14 22 14 22 14 22 14 24 34 44 14 22 34 44 14 22 32 44
2. 3. 4. 5. 5. 6. 7. 8. 3. 4. 5. 6. 1. 2. 3. 4. 1. 2. 3. 4. 3. 4. 5. 6. 3. 4. 5. 6. 5. 6. 7. 8. 5. 6. 7. 8. 5. 6. 7. 8.
According to EN 50005 According to EN 50005 According to EN 500111)
Auxiliary switches, front
(continued)
With complete inscription (for contactor relays)2)
3RH2911-@GA40 4 -- 53 63 73 83 -- -- -- -- -- -- -- 80E -- --
54 64 74 84
3RH2911-@GA31 3 1 53 61 73 83 -- -- -- -- -- -- -- 71E -- --
54 62 74 84
3RH2911-@GA22 2 2 53 61 71 83 -- -- -- -- -- -- -- 62E -- --
54 62 72 84
3RH2911-@GA13 1 3 53 61 71 81 -- -- -- -- -- -- -- 53E -- --
54 62 72 82
3RH2911-@GA04 -- 4 51 61 71 81 -- -- -- -- -- -- -- 44E -- --
52 62 72 82
Complete inscription
3RH2911-@XA40 4 -- 53 63 73 83 50 41 51 40 40 51 51 80E 71X 62X
-0MA0
54 64 74 84
3RH2911-@XA31 3 1 53 61 73 83 41 32 42 31 31 42 42 71E 62X 53
-0MA0
54 62 74 84
3RH2911-@XA22 2 2 53 61 71 83 32 23 33 22 22 33 -- 62E 53 44X
-0MA0
54 62 72 84
3RH2911-@XA04 -- 4 51 61 71 81 14 -- -- -- -- -- -- 44E -- --
-0MA0
52 62 72 82
Solid-state compatible3)
3RH2911-2NE21 24) 1 .3 .3 .1 31 22 32 21 21 32 32 61 52 43
.4 .4 .2
3RH2911-1NE22 24) 24) .3 .3 .1 .1 32 23 33 22 22 33 -- 62 53 44
.4 .4 .2 .2
3RH2911-@NF02 -- 2 .1 .1 12 03 13 02 02 13 -- 42 33 24
.2 .2
3RH2911-@NF11 1 1 .3 .1 21 12 22 11 11 22 22 51 42 33
.4 .2
3RH2911-@NF20 2 -- .3 .3 30 21 31 20 20 31 31 60 51 42
.4 .4
1) 3)
Combinations according to EN 50011 and IEC 60947-5-1 are in bold print. The internal circuit diagrams shown apply to sizes S00 to S3 (including
All combinations comply with EN 50005. mirror contacts). If size S00 is used for the contactor relays, the function of
2) For selection and ordering data, see page 3/89. the mirror contact is not needed.
4) Of which one auxiliary contact is not solid-state compatible.
3
13
14 22 14 22 14 22 14 22 14 24 34 44 14 22 34 44 14 22 32 44
2. 3. 4. 5. 5. 6. 7. 8. 3. 4. 5. 6. 1. 2. 3. 4. 1. 2. 3. 4. 3. 4. 5. 6. 3. 4. 5. 6. 5. 6. 7. 8. 5. 6. 7. 8. 5. 6. 7. 8.
According to EN 500121) According to EN 500121) According to EN 500111)
Lateral auxiliary switches
For size S00 Left Right
3RH2911-@DA02 -- 2 -- 21 31 12 -- -- 02 02 -- -- -- -- --
22 32
3RH2911-@DA02 -- 2 41 51 21 31 14 -- -- -- -- -- -- -- -- --
+
3RH2911-@DA02 -- 2
42 52 22 32
3RH2911-@DA11 1 1 -- 21 33 21 -- -- 11 11 -- -- -- -- --
22 34
3RH2911-@DA11 1 1 41 53 21 33 32 -- -- 22 22 -- -- -- -- --
+
3RH2911-@DA11 1 1
42 54 22 34
3RH2911-@DA20 2 -- -- 23 33 30 -- -- 20 20 -- -- -- -- --
24 34
3RH2911-@DA20 2 -- 43 53 23 33 50 -- -- 40 40 -- -- -- -- --
+
3RH2911-@DA20 2 --
44 54 24 34
3RH2911-@DA20 2 -- 43 53 21 33 41 -- -- 31 31 -- -- -- -- --
+
3RH2911-@DA11 1 1
44 54 22 34
3RH2911-@DA20 2 -- 43 53 21 31 32 -- -- 22 22 -- -- -- -- --
+
3RH2911-@DA02 -- 2
44 54 22 32
3RH2911-@DA11 1 1 41 53 21 31 23 -- -- 13 -- -- -- -- -- --
+
3RH2911-@DA02 -- 2
42 54 22 32
32 42
3RH2921-@DA02 -- 2 51 61 31 41 14 -- -- -- -- -- -- -- -- --
+
3RH2921-@DA02 -- 2
52 62 32 42
3RH2921-@DA11 1 1 -- 31 43 21 12 22 11 11 22 22 -- -- --
32 44
3RH2921-@DA11 1 1 51 63 31 43 32 23 33 22 22 -- -- -- -- --
+
3RH2921-@DA11 1 1
52 64 32 44
3RH2921-@DA20 2 -- -- 33 43 30 21 31 20 20 31 31 -- -- --
34 44
3RH2921-@DA20 2 -- 53 63 33 43 50 41 51 40 40 -- -- -- -- --
+
3RH2921-@DA20 2 --
54 64 34 44
1) Combinations according to EN 50012, EN 50011 and IEC 60947-5-1 are in bold print. All combinations comply with EN 50005.
14 22 14 22 14 22 14 22 14 24 34 44 14 22 34 44 14 22 32 44
2. 3. 4. 5. 5. 6. 7. 8. 3. 4. 5. 6. 1. 2. 3. 4. 1. 2. 3. 4. 3. 4. 5. 6. 3. 4. 5. 6. 5. 6. 7. 8. 5. 6. 7. 8. 5. 6. 7. 8.
According to EN 500121) According to EN 500121) According to EN 500111)
Lateral auxiliary switches
(continued)
For sizes S00 to S3 Left Right
3RH2921-@DA20 2 -- 53 63 31 43 41 32 42 31 31 -- -- -- -- --
+
3RH2921-@DA11 1 1
54 64 32 44
3RH2921-@DA20 2 -- 53 63 31 41 32 23 33 22 22 -- -- -- -- --
+
3RH2921-@DA02 -- 2
54 64 32 42
3RH2921-@DA11 1 1 51 63 31 41 23 14 24 13 -- -- -- -- -- --
+
3RH2921-@DA02 -- 2
52 64 32 42
52 62
52 64
54 64
Solid-state compatible
For size S00 Left Right
3RH2911-2DE11 1 1 -- 23 31 21 -- -- 11 11 -- -- -- -- --
24 32
3RH2911-2DE11 1 1 41 53 23 31 32 -- -- 22 22 -- -- -- -- --
+
3RH2911-2DE11 1 1
42 54 24 32
34 42
3RH2921-@DE11 1 1 51 63 33 41 32 23 33 22 22 -- -- -- -- --
+
3RH2921-@DE11 1 1
52 64 34 42
52 64
1)
Combinations according to EN 50012, EN 50011 and IEC 60947-5-1 are in
bold print. All combinations comply with EN 50005.
2) Without force-guided operation.
3
3RH2911-1HA22 3RH2911-2HA22
For contactors/ Auxiliary contacts Screw terminals Spring-loaded terminals
contactor relays1) Version
Article No. Price Article No. Price
per PU per PU
Type NO NC
Auxiliary switches for snapping onto the front
Sizes S00 to S3
3RT2.1, -- 1 .1 3RH2911-1HA01 3RH2911-2HA01
3RT2.2,
3RT2.3,
3RT2.4, .2
3RH21, -- 2 .1 .1 3RH2911-1HA02 3RH2911-2HA02
3RH24
.2 .2
-- 3 .1 .1 .1 3RH2911-1HA03 3RH2911-2HA03
.2 .2 .2
1 -- .3 3RH2911-1HA10 3RH2911-2HA10
.4
1 1 .1 .3 3RH2911-1HA11 3RH2911-2HA11
.2 .4
1 2 .1 .1 .3 3RH2911-1HA12 3RH2911-2HA12
.2 .2 .4
1 3 .1 .1 .1 .3 3RH2911-1HA13 3RH2911-2HA13
.2 .2 .2 .4
2 -- .3 .3 3RH2911-1HA20 3RH2911-2HA20
.4 .4
2 1 .1 .3 .3 3RH2911-1HA21 3RH2911-2HA21
.2 .4 .4
2 2 .1 .1 .3 .3 3RH2911-1HA22 3RH2911-2HA22
.2 .2 .4 .4
3 -- .3 .3 .3 3RH2911-1HA30 3RH2911-2HA30
.4 .4 .4
3 1 .1 .3 .3 .3 3RH2911-1HA31 3RH2911-2HA31
.2 .4 .4 .4
1) For detailed information on use, see page 3/82.
Type NO NC NO NC
Auxiliary switches for snapping onto the front
Sizes S00 to S3
3RT2.1, -- 4 -- -- -- .3 .3 .3 .3 3RH2911-1FA40 3RH2911-2FA40
3RT2.2,
3RT2.3,
3RT2.4, .4 .4 .4 .4
3RH21, -- 2 2 -- -- .3 .1 .1 .3 3RH2911-1FA22 3RH2911-2FA22
3RH24
.4 .2 .2 .4
-- -- 4 -- -- .1 .1 .1 .1 3RH2911-1FA04 3RH2911-2FA04
.2 .2 .2 .2
-- -- -- 1 1 .7 .5 3RH2911-1FB11 3RH2911-2FB11
.8 .6
-- 1 1 1 1 .3 .1 .5 .7 3RH2911-1FB22 3RH2911-2FB22
.4 .2 .6 .8
-- -- -- 2 2 .7 .7 .5 .5 3RH2911-1FC22 3RH2911-2FC22
.8 .8 .6 .6
1-pole and 2-pole auxiliary switches, cable entry from top or bottom
3RT2.1, Top 1 -- -- -- 73 3RH2911-1AA10 --
3RT2.2, Bottom 1 -- -- -- 3RH2911-1BA10 --
3RT2.3,
3RT2.4, 74
3RH21, Top -- 1 -- -- 71 3RH2911-1AA01 --
3RH24
Bottom -- 1 -- -- 3RH2911-1BA01 --
72
Top 1 1 -- -- 73 81 3RH2911-1LA11 --
Bottom 1 1 -- -- 3RH2911-1MA11 --
74 82
Top 2 -- -- -- 73 83 3RH2911-1LA20 --
Bottom 2 -- -- -- 3RH2911-1MA20 --
74 84
1)
For detailed information on use, see pages 3/82 and 3/83.
PU (UNIT, SET, M) = 1
PS* = 1 unit
PG = 41B
3RH2911-1GA22 3RH2911-2GA22
3
For contactor Contactor relay with Auxiliary contacts Screw terminals Spring-loaded terminals
relays1) auxiliary switch
Ident. No. Version
Article No. Price Article No. Price
per PU per PU
Type NO NC
Auxiliary switches for snapping onto the front
Size S00
Blocks for the assembly of contactor relays with 8 contacts
3RH2140, 80E 4 -- 53 63 73 83 3RH2911-1GA40 3RH2911-2GA40
3RH2440,
Ident. No. 40E
54 64 74 84
71E 3 1 53 61 73 83 3RH2911-1GA31 3RH2911-2GA31
54 62 74 84
62E 2 2 53 61 71 83 3RH2911-1GA22 3RH2911-2GA22
54 62 72 84
53E 1 3 53 61 71 81 3RH2911-1GA13 3RH2911-2GA13
54 62 72 82
44E -- 4 51 61 71 81 3RH2911-1GA04 3RH2911-2GA04
52 62 72 82
1)
For detailed information on use, see page 3/84.
PU (UNIT, SET, M) = 1
PS* = 1 unit
PG = 41B
3RH2911-1XA22-0MA0 3RH2911-2XA22-0MA0
For contactors/ Auxiliary Screw terminals Spring-loaded terminals
contactor relays1) contacts
Version
Article No. Price Article No. Price
per PU per PU
Type NO NC
Auxiliary switches for snapping onto the front
Sizes S00 to S3 S00 S0 ... S3
3RT2.1, 4 -- 53 63 73 83 53 63 73 83 3RH2911-1XA40-0MA0 3RH2911-2XA40-0MA0
3RT2.2,
3RT2.3,
3RT2.4, 54 64 74 84 54 64 74 84
3RH212), 3 1 53 61 73 83 53 61 73 83 3RH2911-1XA31-0MA0 3RH2911-2XA31-0MA0
3RH242)
54 62 74 84 54 62 74 84
2 2 53 61 71 83 53 61 71 83 3RH2911-1XA22-0MA0 3RH2911-2XA22-0MA0
54 62 72 84 54 62 72 84
-- 4 51 61 71 81 51 61 71 81 3RH2911-1XA04-0MA0 3RH2911-2XA04-0MA0
52 62 72 82 52 62 72 82
1) 2)
For detailed information on use, see page 3/84. For size S00, positively driven operation only applies for the 3RH contactor
relay, and there is no positively driven operation for 3RT2 power contactors.
* You can order this quantity or a multiple thereof.
Illustrations are approximate Siemens IC 10 · 2023 3/89
© Siemens 2023
Type NO NC NO NC
Auxiliary switches for snapping onto the front
Sizes S6 to S12
4-pole auxiliary switches
• According to EN 50012
3RT1.5 ... 22 2 2 -- -- 53 61 71 83 3RH1921-1XA22-0MA0 3RH1921-2XA22-0MA0
3RT1.7
54 62 72 84
.4
01 -- 1 -- -- .1 3RH1921-1CA01 3RH1921-2CA01
.2
10 -- -- 1 -- .7 3RH1921-1CD10 --
(lead-
ing)
.8
01 -- -- -- 1 .5 3RH1921-1CD01 --
(lag-
ging)
.6
3
3RH2911-1DA02 3RH2911-2DA02
For Auxiliary contacts Screw terminals Spring-loaded terminals
contactors/ Version
contactor
relays1)
Article No. Price Article No. Price
per PU per PU
Type NO NC
Laterally mountable auxiliary switches,
mounting on the right and/or the left,
2-pole
Size S00 Left Right
3RT2.1 -- 2 41 51 21 31 3RH2911-1DA02 3RH2911-2DA02
42 52 22 32
1 1 41 53 21 33 3RH2911-1DA11 3RH2911-2DA11
42 54 22 34
2 -- 43 53 23 33 3RH2911-1DA20 3RH2911-2DA20
44 54 24 34
52 62
1 1 51 63 -- 3RH2921-1DA11 3RH2921-2DA11
52 64
2 -- 53 63 -- 3RH2921-1DA20 3RH2921-2DA20
54 64
1 1 51 63 31 43 3RH2921-1DA11 3RH2921-2DA11
52 64 32 44
2 -- 53 63 33 43 3RH2921-1DA20 3RH2921-2DA20
54 64 34 44
1) 2)
For detailed information on use, see pages 3/85 and 3/86. With 3RT232. and 3RT252. contactors, mountable only on the right.
3) 3RH2921-1DA.. lateral auxiliary switches can only be mounted on 3RT26
capacitor contactors of sizes S2 and S3.
Type NO NC
Lateral auxiliary switches,
mounting on the right or left,
2-pole
Sizes S6 to S12 Left Right
First auxiliary switch
• According to EN 50012
3RT1.5 ... 1 1 21 13 31 43 3RH1921-1DA11 3RH1921-2DA11
3RT1.7
22 14 32 44
• According to EN 50005
3RT1.5 ... 2 -- 53 63 73 83 3RH1921-1EA20 3RH1921-2EA20
3RT1.7
54 64 74 84
1 1 51 63 71 83 3RH1921-1EA11 --
52 64 72 84
-- 2 51 61 71 81 3RH1921-1EA02 3RH1921-2EA02
52 62 72 82
62 54 72 84
• According to EN 50005
3RT1.5 ... 2 -- 153 163 173 183 3RH1921-1KA20 3RH1921-2KA20
3RT1.7
3
3RH2911-1NF.. 3RH2911-2NF..
For Size Contacts Screw terminals Spring-loaded terminals
contactors/ Version
contactor
relays1)
Article No. Price Article No. Price
per PU per PU
Type NO NC
Auxiliary switches for snapping onto the front
Solid-state compatible auxiliary switches, 2-pole
• For operation in dusty atmospheres
• For solid-state circuits with rated operational currents Ie/AC-14 and DC-13 from
1 to 300 mA at 3 to 60 V
• Hard gold-plated contacts
• Auxiliary switches for snapping onto the front for 3RT2.2 to 3RT2.4 contactors are
designed as mirror contacts according to IEC 60947-4-1, Annex F.
Sizes S00 to S3 S00 S0 ... S3
3RT2.1, S00 ... S3 22) 1 .3 .3 .1 .3 .3 .1 NEW NEU -- 3RH2911-2NE21
3RT2.2,
3RT2.3,
3RT2.4 .4 .4 .2 .4 .4 .2
2) 2)
2 2 .3 .3 .1 .1 .3 .3 .1 .1 NEW NEU 3RH2911-1NE22 --
.4 .4 .2 .2 .4 .4 .2 .2
-- 2 .1 .1 .1 .1 3RH2911-1NF02 3RH2911-2NF02
.2 .2 .2 .2
1 1 .3 .1 .3 .1 3RH2911-1NF11 3RH2911-2NF11
.4 .2 .4 .2
2 -- .3 .3 .3 .3 3RH2911-1NF20 3RH2911-2NF20
.4 .4 .4 .4
2)
3RH21, S00 2 1 .3 .3 .1 -- NEW NEU -- 3RH2911-2NE21
3RH24
.4 .4 .2
.4 .4 .2 .2
-- 2 .1 .1 -- 3RH2911-1NF02 3RH2911-2NF02
.2 .2
1 1 .3 .1 -- 3RH2911-1NF11 3RH2911-2NF11
.4 .2
2 -- .3 .3 -- 3RH2911-1NF20 3RH2911-2NF20
.4 .4
1)
For detailed information on use, see page 3/84.
2)
Of which one auxiliary contact is not solid-state compatible.
3RH2911-2DE11 3RH1921-2JE11
For Size Contacts Screw terminals Spring-loaded terminals
contactors/ Version
contactor
relays1)
Article No. Price Article No. Price
per PU per PU
Type NO NC
Lateral auxiliary switches, mounting on the right and/or the left,
according to EN 50012
Solid-state compatible auxiliary switches, 2-pole
• For operation in dusty atmospheres
• For solid-state circuits with rated operational currents Ie/AC-14 and DC-13
from 1 to 300 mA at 3 to 60 V
• Hard gold-plated contacts
• Laterally mountable auxiliary switches for 3RT2.1 to 3RT2.4 and 3RT1.5 to 3RT1.7
contactors are designed as mirror contacts according to IEC 60947-4-1, Annex F.
Sizes S00 to S3 Left Right
Auxiliary switches
3RT2.1 S00 1 1 41 53 23 31 -- 3RH2911-2DE11
42 54 24 32
52 64
3
Size S0
Auxiliary contacts 1 NO and 1 NC1)
ON-delay
3RT2022) 1 ... 30 3RT2927-2PA01 1 1 unit 41B
10 ... 180 3RT2927-2PA11 1 1 unit 41B
OFF-delay
3RT2022) 1 ... 30 3RT2927-2PR01 1 1 unit 41B
3RT2927-2P..1
10 ... 180 3RT2927-2PR11 1 1 unit 41B
1)
In addition to these, no other auxiliary contacts are permitted.
2)
Cannot be fitted onto coupling contactors and coupling contactor relays.
PU (UNIT, SET, M) = 1
PS* = 1 unit
PG = 41B
3RA2813-1FW10 3RA2813-2AW10
For Rated control supply Time setting Output/ Screw terminals Spring-loaded terminals
contactors voltage Us1) range t auxiliary contacts
Article No. Price Article No. Price
Type V s per PU per PU
Solid-state time-delay auxiliary switches2)
for mounting on 3RT2 contactors and 3RH2 contactor relays
Sizes S00 to S3
The electrical connection between the solid-state time-delay auxiliary
switch and the contactor or contactor relay underneath is established
automatically when it is snapped on and locked.
ON-delay
(varistor integrated)
3RT23)4), 24 ... 240 AC/DC 0.05 ... 100 1 CO 3RA2813-1AW10 3RA2813-2AW10
3RH213), (1, 10, 100; 1 NO + 1 NC 3RA2813-1FW10 3RA2813-2FW10
3RH24 selectable)
OFF-delay with control signal
(varistor integrated)
3RT23)4), 24 ... 240 AC/DC 0.05 ... 100 1 CO 3RA2814-1AW10 3RA2814-2AW10
3RH213), (1, 10, 100; 1 NO + 1 NC 3RA2814-1FW10 3RA2814-2FW10
3RH24 selectable)
5)
OFF-delay without control signal
(varistor integrated)
3RT23)4), 24 ... 240 AC/DC 0.05 ... 100 1 CO 3RA2815-1AW10 3RA2815-2AW10
3RH213), (1, 10, 100; 1 NO + 1 NC 3RA2815-1FW10 3RA2815-2FW10
3RH24 selectable)
1) AC voltage values apply for 50 Hz and 60 Hz. Technical specifications, see page 3/76.
2)
The solid-state time-delay auxiliary switches are also available as 3RA28
function modules for mounting on 3RT2 contactors and 3RH2 contactor
relays, see page 3/100.
3)
Cannot be fitted onto coupling contactors and coupling contactor relays.
4) From product version E04 onwards, 3RA281. solid-state time-delay
auxiliary switches can be used for 3RT2.4 contactors.
5)
Setting of output contacts in as-supplied state not defined (bistable relay).
Application of the control supply voltage once results in contact
changeover to the correct setting.
For contactors Auxiliary contacts Rated control Time setting Screw terminals PU PS* PG
supply voltage Us1) range t (UNIT,
SET, M)
Article No. Price
Type V s per PU
Solid-state time-delay auxiliary switches
for mounting on 3RT1 contactors
Sizes S6 to S12
ON-delay2)
3
3RT1926-2G.51
1)
AC voltage values apply for 50 and 60 Hz.
2)
Connecting terminals A1 and A2 for the control supply voltage of the solid-
state time-delay auxiliary switch must be connected to the associated
contactor by means of cables.
3) Setting of output contacts in as-supplied state not defined (bistable relay).
Application of the control supply voltage once results in contact
changeover to the correct setting.
3
(with or without auxiliary switches)
3RT2.1, Varistors 24 ... 48 24 ... 70 3RT2916-1BB00 1 1 unit 41B
3RH2 48 ... 127 70 ... 150 3RT2916-1BC00 1 1 unit 41B
127 ... 240 150 ... 250 3RT2916-1BD00 1 1 unit 41B
240 ... 400 -- 3RT2916-1BE00 1 1 unit 41B
3RT2916-1B.00 400 ... 600 -- 3RT2916-1BF00 1 1 unit 41B
3RT2.1, RC elements 24 ... 48 24 ... 70 3RT2916-1CB00 1 1 unit 41B
3RH2 48 ... 127 70 ... 150 3RT2916-1CC00 1 1 unit 41B
127 ... 240 150 ... 250 3RT2916-1CD00 1 1 unit 41B
240 ... 400 -- 3RT2916-1CE00 1 1 unit 41B
400 ... 600 -- 3RT2916-1CF00 1 1 unit 41B
3RT2.1, Interference -- 12 ... 250 3RT2916-1DG00 1 1 unit 41B
3RH2 suppression
diode
3RT2.1, Diode assemblies -- 12 ... 250 3RT2916-1EH00 1 1 unit 41B
3RH2 (diode and Zener
diode) for DC
operation
Size S0
For plugging into the front of the contactors
(before mounting the auxiliary switch)
3RT2.2 Varistors2) 24 ... 48 24 ... 70 3RT2926-1BB00 1 1 unit 41B
48 ... 127 70 ... 150 3RT2926-1BC00 1 1 unit 41B
127 ... 240 150 ... 250 3RT2926-1BD00 1 1 unit 41B
240 ... 400 -- 3RT2926-1BE00 1 1 unit 41B
3RT2926-1E.00 400 ... 600 -- 3RT2926-1BF00 1 1 unit 41B
3RT2.2 RC elements 24 ... 48 24 ... 70 3RT2926-1CB00 1 1 unit 41B
48 ... 127 70 ... 150 3RT2926-1CC00 1 1 unit 41B
127 ... 240 150 ... 250 3RT2926-1CD00 1 1 unit 41B
240 ... 400 -- 3RT2926-1CE00 1 1 unit 41B
400 ... 600 -- 3RT2926-1CF00 1 1 unit 41B
3RT2.2 Diode assemblies -- 24 3RT2926-1ER00 1 1 unit 41B
for DC operation -- 30 ... 250 3RT2926-1ES00 1 1 unit 41B
Size S2
For plugging into the front of the contactors
(before mounting the auxiliary switch)
3RT2.3 Varistors2) 24 ... 48 -- 3RT2936-1BB00 1 1 unit 41B
48 ... 127 -- 3RT2936-1BC00 1 1 unit 41B
127 ... 240 -- 3RT2936-1BD00 1 1 unit 41B
240 ... 400 -- 3RT2936-1BE00 1 1 unit 41B
3RT2936-1BF00 400 ... 600 -- 3RT2936-1BF00 1 1 unit 41B
3RT2.3 RC elements 24 ... 48 24 ... 70 3RT2936-1CB00 1 1 unit 41B
48 ... 127 70 ... 150 3RT2936-1CC00 1 1 unit 41B
127 ... 240 150 ... 250 3RT2936-1CD00 1 1 unit 41B
240 ... 400 -- 3RT2936-1CE00 1 1 unit 41B
400 ... 600 -- 3RT2936-1CF00 1 1 unit 41B
3RT2.3 Diode assemblies -- 24 3RT2936-1ER00 1 1 unit 41B
for DC operation -- 30 ... 250 3RT2936-1ES00 1 1 unit 41B
Size S3
For plugging into the front of the contactors
(before mounting the auxiliary switch)
3RT2.4 Varistors2) 24 ... 48 -- 3RT2936-1BB00 1 1 unit 41B
48 ... 127 -- 3RT2936-1BC00 1 1 unit 41B
127 ... 240 -- 3RT2936-1BD00 1 1 unit 41B
240 ... 400 -- 3RT2936-1BE00 1 1 unit 41B
3RT2936-1ER00 400 ... 600 -- 3RT2936-1BF00 1 1 unit 41B
3RT2.4 Diode assemblies -- 24 3RT2936-1ER00 1 1 unit 41B
for DC operation -- 30 ... 250 3RT2936-1ES00 1 1 unit 41B
For plugging into the two recesses on the left next to
the connection block for auxiliary switches and coils A1
and A2, the connecting cables are wired to A1 and A2
(see also overview graphic on page 3/11)
3RT2.4 RC elements 24 ... 48 24 ... 70 3RT2946-1CB00 1 1 unit 41B
48 ... 127 70 ... 150 3RT2946-1CC00 1 1 unit 41B
127 ... 240 150 ... 250 3RT2946-1CD00 1 1 unit 41B
240 ... 400 -- 3RT2946-1CE00 1 1 unit 41B
400 ... 600 -- 3RT2946-1CF00 1 1 unit 41B
3RT2946-1C.00
1) Can be used for AC operation for 50/60 Hz. Other voltages on request. 2) The varistor is already integrated on the AC/DC contactors.
For con- Version Rated control supply voltage Us1) Article No. Price PU PS* PG
tactors AC operation DC operation per PU (UNIT,
SET, M)
Type V AC V DC
Surge suppressors without LED
Sizes S6 to S12
For connecting to withdrawable coil for contactors Screw terminals
with
• Standard operating mechanisms 3RT1...-.A...
3
For con- Version Rated control supply Power con- Article No. Price PU PS* PG
tactors voltage Us1) sumption P per PU (UNIT,
AC DC of LED SET, M)
operation operation at Us
Type V AC V DC mW
Surge suppressors with LED (also for spring-loaded terminals)
Size S00
For plugging onto the front of the contactors
(with or without auxiliary switches)
3RT2.1, Varistors 24 ... 48 12 ... 24 10 ... 120 3RT2916-1JJ00 1 1 unit 41B
3RH2 48 ... 127 24 ... 70 20 ... 470 3RT2916-1JK00 1 1 unit 41B
127 ... 240 70 ... 150 50 ... 700 3RT2916-1JL00 1 1 unit 41B
-- 150 ... 250 160 ... 950 3RT2916-1JP00 1 1 unit 41B
3RT2916-1J.00 3RT2.1, Interference -- 24 ... 70 20 ... 470 3RT2916-1LM00 1 1 unit 41B
3RH2 suppression -- 50 ... 150 50 ... 700 3RT2916-1LN00 1 1 unit 41B
diodes -- 150 ... 250 160 ... 950 3RT2916-1LP00 1 1 unit 41B
Size S0
For plugging into the front of the contactors
(before mounting the auxiliary switch)
3RT2.2 Varistors 24 ... 48 12 ... 24 10 ... 120 3RT2926-1JJ00 1 1 unit 41B
48 ... 127 24 ... 70 20 ... 470 3RT2926-1JK00 1 1 unit 41B
127 ... 240 70 ... 150 50 ... 700 3RT2926-1JL00 1 1 unit 41B
3RT2.2 Diode -- 24 20 ... 470 3RT2926-1MR00 1 1 unit 41B
3RT2926-1MR00 assemblies
Sizes S2 and S3
For plugging into the front of the contactors
(before mounting the auxiliary switch)
3RT2.3, Varistors 24 ... 48 12 ... 24 10 ... 120 3RT2936-1JJ00 1 1 unit 41B
3RT2.4 48 ... 127 24 ... 70 20 ... 470 3RT2936-1JK00 1 1 unit 41B
127 ... 240 70 ... 150 50 ... 700 3RT2936-1JL00 1 1 unit 41B
3RT2936-1JJ00
1)
Can be used for AC operation for 50/60 Hz. Other voltages on request.
3
Size S0
For mounting on the coil terminals of the
contactors
(for contactors with screw terminals only)
With LED for the switching state and
with integrated varistor for damping switching
overvoltages
3RT2.2 • 24 V DC control, 3RH2924-1GP11 1 1 unit 41B
3RH2924-1GP11 17 ... 30 V DC operating range
Sizes S00 to S3
For mounting on the front of contactors
with AC, DC or AC/DC operation
3RT2.1, • 24 V DC control, 3RH2914-1GP11 1 1 unit 41B
3RT2.2, 17 ... 30 V DC operating range
3RT2.3,
3RT2.4
3RH2
3RH2914-1GP11 Spring-loaded terminals
3RH2914-2GP11
Technical specifications, see page 3/78.
For Size Version Rated control Time Screw terminals Spring-loaded terminals
contactors supply setting
voltage Us1) range t
Article No. Price Article No. Price
Type V AC/DC s per PU per PU
3RA28 function modules for mounting on 3RT2 contactors and
3RH2 contactor relays
For direct-on-line starting
3RT2.12), S00, S0 ON-delay 24 ... 240 0.05 ... 100 3RA2811-1CW10 3RA2811-2CW10
3RT2.22), two-wire design, (1, 10, 100;
3RH212), varistor integrated selectable)
3RH24 The electrical connection
3RT2.32), S2, S3 between the function 24 ... 90 0.05 ... 100 3RA2831-1DG10 3RA2831-2DG10
3RT2.42)3) module and the contactor 90 ... 240 (1, 10, 100; 3RA2831-1DH10 3RA2831-2DH10
underneath is established selectable)
automatically when it is
snapped on and locked.
3RT2.12), S00, S0 OFF-delay 24 ... 240 0.05 ... 100 3RA2812-1DW10 3RA2812-2DW10
3RT2.22), with control signal, (1, 10, 100;
3RH212), varistor integrated selectable)
3RH24 The electrical connection
3RT2.32), S2, S3 between the function 24 ... 90 0.05 ... 100 3RA2832-1DG10 3RA2832-2DG10
3RT2.42)3) module and the contactor 90 ... 240 (1, 10, 100; 3RA2832-1DH10 3RA2832-2DH10
underneath is established selectable)
automatically when it is
snapped on and locked.
For star-delta (wye-delta) starting
3RT2.1, S00 ... S3 Varistor integrated 24 ... 240 0.5 ... 60 3RA2816-0EW20 3RA2816-0EW20
3RT2.2, Comprising one basic (10, 30, 60;
3RT2.32), module and two coupling selectable)
3RT2.42)4) modules
The electrical connection
between the function
module and the contactor
assembly is established
automatically by snapping
on and plugging in the
connecting cables.
Accessories
3RA28 S00 ... S3 Cover, sealable 3RA2910-0 3RA2910-0
1)
AC voltage values apply for 50 and 60 Hz. Assembly of reversing starters
2)
Cannot be fitted onto coupling relays and coupling contactor relays.
3) From product version E03 onwards, 3RA283. function modules can be We offer ready-made wiring kits for the assembly of reversing
used for 3RT2.4 contactors.
starters. Use of these wiring kits offers further advantages,
4) see page 3/148.
From product version E04 onwards, 3RA2816 function modules can be
used for 3RT2.4 contactors.
Technical specifications, see page 3/79.
3
3RA2711-1AA00 3RA2711-2AA00 3RA2711-1BA00 3RA2712-1CA00 3RA2711-2BA00 3RA2711-2CA00
Type
Accessories for 3RA27 function modules
3RA271.-..A00 Module connector set 3RA2711-0EE10 1 1 unit 41B
Comprising:
• Two module connectors (14-pole, short)
• Two interface covers
3RA271.-..A00 Module connectors
• 14-pole
- 6 cm 3RA2711-0EE17 1 1 unit 41B
- 9 cm 3RA2711-0EE06 1 1 unit 41B
- 13 cm 3RA2711-0EE18 1 1 unit 41B
- 26 cm 3RA2711-0EE07 1 1 unit 41B
- 33.5 cm 3RA2711-0EE08 1 1 unit 41B
• 10-pole, 9 cm 3RA2711-0EE16 1 1 unit 41B
for the additional auxiliary voltage infeed
Note:
Selection of module connectors, see Equipment Manual for 3RA2711
function modules for IO-Link.
3RA271.-..A00 Interface covers 3RA2711-0EE15 1 1 unit 41B
(set of 5)
3RA271.-..A00 Cover, sealable 3RA2910-0 1 5 units 41B
Operator panel for communication via IO-Link
3RA2711-..A00 Operator panel (set) 3RA6935-0A 1 1 unit 42F
Comprising:
• 1 x operator panel
• 1 x enabling module
• 1 x interface cover
• 1 x fixing terminal
3RA2711-..A00 Connecting cable 3RA2711-0EE11 1 1 unit 41B
For connecting the operator panel to the coupling module
Length 2 m, 10- to 14-pole
3RA2711-..A00 Enabling modules (replacement) 3RA6936-0A 1 1 unit 42F
3RA2711-..A00 Interface covers (replacement) 3RA6936-0B 1 5 units 42F
For contactors Rated control supply Time setting Screw terminals PU PS* PG
voltage Us range t (UNIT,
SET, M)
Article No. Price
Type V s per PU
Mechanical latching blocks
(no switching state change in the event of voltage drop)
Size S0
For snapping onto the front of contactors
3
The contactor remains in the energized state in the event of voltage
drop.
3RT202, 24 AC/DC -- 3RT2926-3AB31 1 1 unit 41B
3RT232, 110 AC/DC -- 3RT2926-3AF31 1 1 unit 41B
3RT252
230 AC/DC -- 3RT2926-3AP31 1 1 unit 41B
3RT2926-3A.31
OFF-delay devices for contactors with AC/DC and DC operation
Sizes S00 to S3
Non-adjustable delay time
3RT201.-1BF4., 110 AC/DC S00: > 0.1 3RT2916-2BK01 1 1 unit 41B
3RT202.-1BF4., S0: > 0.08
3RT203.-1NF3., S2: > 0.25
3RH2...-1BF40
3RT201.-1BM4./-1BP4., 220/230 AC/DC S00: > 0.5 3RT2916-2BL01 1 1 unit 41B
3RT202.-1BM4./-1BP4., S0: > 0.3
3RT203.-1NP3., S2: > 0.8
3RH2...-1BM40/-1BP40
3RT2916-2B.01 3RT201.-1BB4., 24 DC S00: > 0.2 3RT2916-2BE01 1 1 unit 41B
3RT202.-1BB4., S0: > 0.1
3RT203.-1NB3., S2: > 0.1
3RT204.-1NB3.,
3RT244.-1NB3., S3: > 0.05
3RH2...-1BB40
3RA2926-1A
PU (UNIT, SET, M) = 1
PS* = 1 unit (unless otherwise specified)
PG = 41B
For con- Size Version Article No. Price Article No. Price
tactors per PU per PU
Type
Assembly kits for reversing contactor assemblies
for making 3-pole contactor assemblies
Screw terminals Spring-loaded terminals
3RA1953-2A
3RA1963-2A
1) 2)
Use of the 3RA2923-2AA1 assembly kit in conjunction with the Version in size S0 with spring-loaded terminals:
3RT202.-.....-3MA0 contactors is limited because the auxiliary switches Only the wiring modules for the main circuit are included.
in the basic unit are not allowed to be used on account of the permanently No connecting clips are included for the auxiliary and control circuit.
mounted auxiliary switch. 3)
Version in sizes S2 and S3 with spring-loaded terminals in the auxiliary and
control circuits: Only the wiring modules for the main circuit are included.
A cable set is included for the auxiliary circuit.
3
3RA2913-2BB1 3RA2923-2BB1 3RA2923-2BB2 3RA2933-2BB1 3RA2943-2C 3RA2943-2BB2
3RA1953-2B
3RT1.5 S6-S6-S6 -- 3RA1953-2N 1 1 unit 41B
For
connection
without box
terminal
3RA1953-2N
3RT1.6, S10-S10-S6 The S6 star jumper must be 3RA1963-3E 1 1 unit 41B
3RT1.5 For ordered separately,
connection see page 3/107.
with box
3RA1963-3E terminal only
3RT1.6 S10-S10-S10 -- 3RA1963-2B 1 1 unit 41B
For
connection
without box
terminal
3RA1963-2B
3RT1.7, S12-S12-S10 The S10 star jumper must 3RA1973-3E 1 1 unit 41B
3RT1.6 For be ordered separately,
connection see page 3/107.
with box
terminal only
3RA1973-3E
3RT1.7 S12-S12-S12 -- 3RA1973-2B 1 1 unit 41B
For
connection
without box
terminal
3RA1973-2B
3
Screw terminals Spring-loaded terminals
3RT2926-4BA32
3RT203 S2 3RT1936-4BA31 3RT1936-4BA31
3RT1936-4BA31
3RT204 S3 3RT1946-4BA31 3RT1946-4BA31
3RT1946-4BA31
3RT1.5 S6 3RT1956-4BA31 3RT1956-4BA31
3RT1956-4BA31
3RT1.6, S10, 3RT1966-4BA31 3RT1966-4BA31
3RT1.7 S12
3RT1966-4BA31
3RT202, S0-S0 One assembly kit consists of a mechanical 3RA2922-2H 1 10 units 41B
3RT232 interlock and two connecting clips.
3RA2922-2H
3RA2934-2B
3RT1.5 S6 (3RT1)- Adapter in addition to the mechanical 3RA1954-2G 1 1 unit 41B
with S6 (3RT1)- interlock
1)
3RT204 S3 (3RT2)1) The mechanical interlock is only possible
together with this 3RA1954-2G adapter
and the 3RA1954-2A mechanical
interlock.
Two connectors are included with the
adapter, the interlock must be ordered
3RA1954-2G separately.
3RT1.5 S6 Mechanical interlocks 3RA1954-2A 1 1 unit 41B
3RT1.6 S10 Without auxiliary contacts;
3RT1.7 S12 contactors in sizes S6, S10 and S12 can
be interlocked with each other as
required. No adaption of mounting depth
3RA1954-2A is necessary.
Mechanical connectors for contactor assemblies
Two connectors are required for each
assembly. The contactor clearance must
be considered when selecting the
connectors.
3-pole version
3RT203, S2-S2, • Without contactor clearance 3RA2932-2C 1 10 units 41B
3RT204 S3-S3 • With 10 mm contactor clearance 3RA2932-2D 1 10 units 41B
3RA1932-2D
3RT105 S6-S6 • With 10 mm contactor clearance 3RA1932-2D 1 10 units 41B
(1 unit corresponds to 2 parts for
1 assembly)
4-pole version
3RT233 S2-S2 • With 20 mm contactor clearance 3RA2932-2G 1 10 units 41B
3RT234. S3-S3 • With 10 mm contactor clearance 3RA2942-2G 1 10 units 41B
3RA2942-2G
1) The 3RA1954-2G adapter cannot be used in conjunction with
3RT204..-.KB coupling contactors, size S3.
3
one pole. With connecting terminal
3-pole
3RT201 S00 • Max. conductor cross-section: 25 mm2, stranded 3RT1916-4BB31 1 1 unit 41B
3RT1916-4BB31
3RT202 S0 • Max. conductor cross-section: 50 mm2, stranded 3RT2926-4BB31 1 1 unit 41B
3RT2926-4BB31
3RT203 S2 • Max. conductor cross-section: 120 mm2, stranded 3RT1936-4BB31 1 1 unit 41B
3RT1936-4BB31
3RT204, S3 • Max. conductor cross-section: 185 mm2, stranded 3RT1946-4BB31 1 1 unit 41B
3RT244 A cover plate is included for touch protection
(can only be used when box terminal is removed).
3RT1946-4BB31
4-pole
3RT231, S00 • Max. conductor cross-section: 25 mm2, stranded 3RT1916-4BB41 1 1 unit 41B
3RT251
3RT1916-4BB41
3RA2943-3L
3-phase infeed terminals
3RT201 S00 Max. conductor cross-section: 3RA2913-3K 1 10 units 41B
Up to 10 mm2, AWG 12 ... 8
3RA2913-3K
3RT202, S0 Max. conductor cross-section: 3RV2925-5AB 1 1 unit 41E
3RT262 Up to 25 mm2, AWG 10 ... 2/0
3RV2925-5AB
3RT203, S2 Max. conductor cross-section: 3RV2935-5A 1 1 unit 41E
3RT263 Up to 70 mm2, AWG 10 ... 2/0
3RV2935-5A
3-phase infeed terminals with increased clearance and creepage
distances
3RT203 S2 Max. conductor cross-section: 3RV2935-5E 1 1 unit 41E
Up to 70 mm2, AWG 10 ... 2/0
3RV2935-5E
3-phase busbars
3RT202 S0 Bridging phase-by-phase of all input 3RV1915-1AB 1 1 unit 41E
terminals of the line contactor (Q11)
and delta contactor (Q13)
3RV1915-1AB
Terminal blocks for connecting auxiliary conductors to main terminals
Box terminal blocks
For round and ribbon cables
(Connectable cross-sections of the
contactors for size S3, see page 3/40 and
for sizes 6 to S12, see page 3/44)
3RT204 S3 • 3-pole, for connection of main contacts, 3RT2946-4G 1 1 unit 41B
2.5 to 70 mm2
3RT2946-4G
3RT1.5 S6 • Up to 70 mm2, as standard on 3RT1955-4G 1 1 unit 41B
3RT1054-1 contactor (55 kW)
• Up to 120 mm2 3RT1956-4G 1 1 unit 41B
3RT1956-4G
3RT1.6, S10, • Up to 240 mm2, 3RT1966-4G 1 1 unit 41B
3RT1.7 S12 with auxiliary conductor connection up to
2.5 mm2
3RT1966-4G
3RT1.5 S6 Box terminal for auxiliary conductor 3TX7500-0A 1 1 unit 41B
connection, 1-pole
For connection of auxiliary and control
3TX7500-0A cables (0.5 ... 2.5 mm2) to the main
conductor terminals
3RT204 S3 Auxiliary conductor terminals, 3-pole 3RT2946-4F 1 1 unit 41B
For connection of auxiliary and control
cables (0.5 ... 2.5 mm2) to the main
3RT2946-4F conductor terminals
3RT2.1, S00 Assembly kit for soldering contactors 3RT1916-4KA1 1 4 units 41B
3
3RH21 with an integrated auxiliary contact onto
a printed circuit board
Note:
One kit is required for one contactor.
3RT1916-4KA1
3RT2.1, S00 Assembly kit for soldering contactors 3RT1916-4KA2 1 4 units 41B
3RH21 with 4-pole mounted auxiliary switch
onto a printed circuit board
Note:
One kit is required for one contactor.
3RT1916-4KA2
Coil connection modules for connections from top or from below
3RT2.2, S0 to S3 • Connection from top 3RT2926-4RA11 1 1 unit 41B
3RT2.3, • Connection from below 3RT2926-4RB11 1 1 unit 41B
3RT2.4
• Connection diagonally 3RT2926-4RC11 1 1 unit 41B
Spring-loaded terminals
3RT2926-4RA11
3RT2.2 S0 • Connection from top 3RT2926-4RA12 1 1 unit 41B
• Connection from below 3RT2926-4RB12 1 1 unit 41B
3RT2926-4RA12
3RT1900-4RE01
3RT2936-4EA4 3RT2946-4EA4
Covers for contactors with
cable lugs and busbar
connections
• For complying with the phase
clearances and as touch
protection if box terminal is
removed (2 units required per
contactor)
3RT1946-4EA1 3RT2.4 S3 - Length: 100 mm 3RT1946-4EA1 1 1 unit 41B
3RT1.5 S61) - Length: 100 mm 3RT1956-4EA1 1 1 unit 41B
3RT1.6, S101), - Length: 120 mm 3RT1966-4EA1 1 1 unit 41B
3RT1.7 S121)
• For the assembly kits for
3RA1953-.. contactor assemblies
3RT1956-4EA1 3RT1966-4EA1 for star-delta (wye-delta) starting
(see page 3/106) or for the
3RA1953-3 single wiring
modules. (see page 3/107)
3RT1956-4EA4 3RT1.5 S6 - Length: 38 mm 3RT1956-4EA4 1 1 unit 41B
• For the assembly kits for
reversing contactor assemblies
and contactor assemblies for
3RT1966-4EA3 star-delta (wye-delta) starting
3RT1.6, S10, - Length: 42 mm 3RT1966-4EA3 1 1 unit 41B
3RT1.7 S12
Terminal covers for busbar
connections
• Cover the three busbar
connections, between the
contactor and 3RB2 overload
3RT1956-4EA3 3RT1966-4EA3 relay
3RT1.5 S6 - Length: 27 mm 3RT1956-4EA3 1 1 unit 41B
3RT1.6, S10, - Length: 42 mm 3RT1966-4EA3 1 1 unit 41B
3RT1.7 S12
• Can be screwed on free screw
end; covers one busbar
connection (1 set = 6 units)
3RT1.5 S6 - M8 3TX6526-3B 1 1 unit 41B
3RT1.6, S10, - M10 3TX6546-3B 1 1 unit 41B
3RT1.7 S12
3TX6526-3B 3TX6546-3B
Sealable covers
3RT2.1, S00 ... For preventing manual 3RT2916-4MA10 1 5 units 41B
3RT2.2, S3 operation
3RT2.3, (Not suitable for coupling
3RT2.4, contactors)
3RH22)
3RT2916-4MA10 3RT1926-4MA10
3RT1.5 S6 ... 3RT1926-4MA10 1 5 units 41B
... S12
3RT1.72)
1) 2)
Also fits on contactors of sizes S6 to S12 with box terminals. Exception: Contactors and contactor relays with auxiliary switch mounted
on the front.
* You can order this quantity or a multiple thereof.
3/112 Siemens IC 10 · 2023 Illustrations are approximate
© Siemens 2023
3
3RT1.6 S10 contactor assemblies 3RA1962-2A 1 1 unit 41B
3RT1.7 S12 3RA1972-2A 1 1 unit 41B
3RA1952-2A
For contactor assemblies for star-delta (wye-delta) starting
3RT2/ S2-S2-S0, For configuring contactor assemblies 3RA2932-2F 1 1 unit 41B
3RT2/ S2-S2-S2 for star-delta (wye-delta) starting
3RT2 S3-S3-S2, 3RA2942-2F 1 1 unit 41B
S3-S3-S3
3RA2932-2F
3RA2942-2F
3RT1/ S6-S6-S3 For customer assembly of contactor 3RA1952-2E 1 1 unit 41B
3RT1/ assemblies for star-delta (wye-delta)
3RT2 starting with a laterally mounted
3RT1/ S6-S6-S6 timing relay 3RA1952-2F 1 1 unit 41B
3RT1/ S10-S10-S6 10 mm clearance between the 3RA1962-2E 1 1 unit 41B
3RT1 contactors
S10-S10-S10 3RA1962-2F 1 1 unit 41B
3RA1952-2E S12-S12-S10 3RA1972-2E 1 1 unit 41B
S12-S12-S12 3RA1972-2F 1 1 unit 41B
3RA1952-2F
Adapters for screw fixing
3RT2.2 S0 Screw adapters for securing the 3RT1926-4P 1 10 units 41B
contactors, two units required per
contactor
3RT1926-4P (1 pack = 10 sets for 10 contactors)
3RT1955-4PA00
EMC suppression modules; 3-phase, up to 7.5 kW
For contactors with AC or DC operation
Screw terminals
3
Can be inserted in cable entry of the
spring-loaded terminal (two strips per
3RT2916-4JA02 contactor required)
3RT2.1, S00 • For basic units, removable individually 3RT2916-4JA02 1 20 units 41B
3RH2
3RT2.2 S0 ... S12 • For auxiliary and control current on 3RT1916-4JA02 1 20 units 41B
3RT1916-4JA02 ... basic units and for mountable 3RH29
3RT2.4, auxiliary switches, removable in pairs
3RT1,
3RH29
Tools for opening spring-loaded terminals
3RT, S00 ... S12 Screwdrivers 3RA2908-1A 1 1 unit 41B
3RH For all SIRIUS devices with
spring-loaded terminals
Length: approx. 200 mm,
3.0 mm x 0.5 mm,
titanium gray/black,
3RA2908-1A
partially insulated
Blank labels
Unit labeling plates1)
For SIRIUS devices
3RT S00 ... S12 • 10 mm x 7 mm, titanium gray 3RT2900-1SB10 100 816 units 41B
• 20 mm x 7 mm, titanium gray 3RT2900-1SB20 100 340 units 41B
IC01_00181
Adhesive labels
For SIRIUS devices
3RT S00 ... S12 • 19 mm x 6 mm, titanium gray 3RT2900-1SB60 100 3060 units 41B
3RT2900-1SB20
1)
PC labeling system for individual inscription
of unit labeling plates available from:
murrplastik Systemtechnik GmbH
(see page 16/18).
3RT2924-5A.01
For contactors Rated control supply voltage Us Article No. Price PU PS* PG
50 Hz 50/60 Hz 60 Hz per PU (UNIT,
SET, M)
Type V V V
Solenoid coils AC operation
Size S0
3RT2023-.A, 24 -- -- 3RT2924-5AB01 1 1 unit 41B
3RT2024-.A, 42 -- -- 3RT2924-5AD01 1 1 unit 41B
3RT2025-.A 48 -- -- 3RT2924-5AH01 1 1 unit 41B
110 -- -- 3RT2924-5AF01 1 1 unit 41B
230 -- -- 3RT2924-5AP01 1 1 unit 41B
400 -- -- 3RT2924-5AV01 1 1 unit 41B
-- 24 -- 3RT2924-5AC21 1 1 unit 41B
-- 42 -- 3RT2924-5AD21 1 1 unit 41B
-- 48 -- 3RT2924-5AH21 1 1 unit 41B
-- 110 -- 3RT2924-5AG21 1 1 unit 41B
-- 220 -- 3RT2924-5AN21 1 1 unit 41B
-- 230 -- 3RT2924-5AL21 1 1 unit 41B
-- -- 24 3RT2924-5AC11 1 1 unit 41B
110 -- 120 3RT2924-5AK61 1 1 unit 41B
220 -- 240 3RT2924-5AP61 1 1 unit 41B
-- 100 110 3RT2924-5AG61 1 1 unit 41B
-- 200 220 3RT2924-5AN61 1 1 unit 41B
-- 400 440 3RT2924-5AR61 1 1 unit 41B
3RT2026-.A, 24 -- -- 3RT2926-5AB01 1 1 unit 41B
3RT2027-.A, 42 -- -- 3RT2926-5AD01 1 1 unit 41B
3RT2028-.A 48 -- -- 3RT2926-5AH01 1 1 unit 41B
3RT2325-.A, 110 -- -- 3RT2926-5AF01 1 1 unit 41B
3RT2326-.A, 230 -- -- 3RT2926-5AP01 1 1 unit 41B
3RT2327-.A 400 -- -- 3RT2926-5AV01 1 1 unit 41B
3RT2526-.A
-- 24 -- 3RT2926-5AC21 1 1 unit 41B
-- 42 -- 3RT2926-5AD21 1 1 unit 41B
-- 48 -- 3RT2926-5AH21 1 1 unit 41B
-- 110 -- 3RT2926-5AG21 1 1 unit 41B
-- 220 -- 3RT2926-5AN21 1 1 unit 41B
-- 230 -- 3RT2926-5AL21 1 1 unit 41B
-- -- 24 3RT2926-5AC11 1 1 unit 41B
110 -- 120 3RT2926-5AK61 1 1 unit 41B
220 -- 240 3RT2926-5AP61 1 1 unit 41B
-- 100 110 3RT2926-5AG61 1 1 unit 41B
-- 200 220 3RT2926-5AN61 1 1 unit 41B
-- 400 440 3RT2926-5AR61 1 1 unit 41B
Note:
Contactors with AC and AC/DC coils have different depths. It is
only possible to replace the coils on AC contactors with AC coils.
It is not possible to replace the coils on DC contactors.
3
3RT2934-5A.01 3RT2934-5N.31 3RT2944-5A..1 3RT2944-5N.31
For contactors Rated control supply voltage Us Article No. Price PU PS* PG
50 Hz 50/60 Hz 60 Hz DC per PU (UNIT,
SET, M)
Type V V V
Solenoid coils AC operation
Size S2
3RT203.-.A, 24 -- -- -- 3RT2934-5AB01 1 1 unit 41B
3RT233.-.A, 42 -- -- -- 3RT2934-5AD01 1 1 unit 41B
3RT243.-.A, 48 -- -- -- 3RT2934-5AH01 1 1 unit 41B
3RT253.-.A 110 -- -- -- 3RT2934-5AF01 1 1 unit 41B
230 -- -- -- 3RT2934-5AP01 1 1 unit 41B
400 -- -- -- 3RT2934-5AV01 1 1 unit 41B
-- 24 -- -- 3RT2934-5AC21 1 1 unit 41B
-- 42 -- -- 3RT2934-5AD21 1 1 unit 41B
-- 48 -- -- 3RT2934-5AH21 1 1 unit 41B
-- 110 -- -- 3RT2934-5AG21 1 1 unit 41B
-- 208 -- -- 3RT2934-5AM21 1 1 unit 41B
-- 220 -- -- 3RT2934-5AN21 1 1 unit 41B
-- 230 -- -- 3RT2934-5AL21 1 1 unit 41B
110 -- 120 -- 3RT2934-5AK61 1 1 unit 41B
220 -- 240 -- 3RT2934-5AP61 1 1 unit 41B
-- -- 480 -- 3RT2934-5AV61 1 1 unit 41B
-- -- 600 -- 3RT2934-5AT61 1 1 unit 41B
-- 100 110 -- 3RT2934-5AG61 1 1 unit 41B
-- 200 220 -- 3RT2934-5AN61 1 1 unit 41B
-- -- 277 -- 3RT2934-5AU61 1 1 unit 41B
-- 400 440 -- 3RT2934-5AR61 1 1 unit 41B
Size S3
3RT204.-.A, 24 -- -- -- 3RT2944-5AB01 1 1 unit 41B
3RT234.-.A, 42 -- -- -- 3RT2944-5AD01 1 1 unit 41B
3RT244.-.A, 48 -- -- -- 3RT2944-5AH01 1 1 unit 41B
3RT254.-.A 110 -- -- -- 3RT2944-5AF01 1 1 unit 41B
230 -- -- -- 3RT2944-5AP01 1 1 unit 41B
400 -- -- -- 3RT2944-5AV01 1 1 unit 41B
-- 24 -- -- 3RT2944-5AC21 1 1 unit 41B
-- 42 -- -- 3RT2944-5AD21 1 1 unit 41B
-- 48 -- -- 3RT2944-5AH21 1 1 unit 41B
-- 110 -- -- 3RT2944-5AG21 1 1 unit 41B
-- 220 -- -- 3RT2944-5AN21 1 1 unit 41B
-- 230 -- -- 3RT2944-5AL21 1 1 unit 41B
110 -- 120 -- 3RT2944-5AK61 1 1 unit 41B
220 -- 240 -- 3RT2944-5AP61 1 1 unit 41B
-- -- 480 -- 3RT2944-5AV61 1 1 unit 41B
-- -- 600 -- 3RT2944-5AT61 1 1 unit 41B
-- 100 110 -- 3RT2944-5AG61 1 1 unit 41B
-- 200 220 -- 3RT2944-5AN61 1 1 unit 41B
-- 400 440 -- 3RT2944-5AR61 1 1 unit 41B
Solenoid coils AC/DC operation, with varistor
Size S2
3RT203.-.N, -- 20 ... 33 -- 20 ... 33 3RT2934-5NB31 1 1 unit 41B
3RT233.-.N -- 30 ... 42 -- 30 ... 42 3RT2934-5ND31 1 1 unit 41B
-- 48 ... 80 -- 48 ... 80 3RT2934-5NE31 1 1 unit 41B
-- 83 ... 155 -- 83 ... 155 3RT2934-5NF31 1 1 unit 41B
-- 175 ... 280 -- 175 ... 280 3RT2934-5NP31 1 1 unit 41B
Size S3
3RT204.-.N, -- 20 ... 33 -- 20 ... 33 3RT2944-5NB31 1 1 unit 41B
3RT234.-.N, -- 30 ... 42 -- 30 ... 42 3RT2944-5ND31 1 1 unit 41B
3RT244.-.N, -- 48 ... 80 -- 48 ... 80 3RT2944-5NE31 1 1 unit 41B
3RT254.-.N -- 83 ... 155 -- 83 ... 155 3RT2944-5NF31 1 1 unit 41B
-- 175 ... 280 -- 175 ... 280 3RT2944-5NP31 1 1 unit 41B
Notes:
It is only possible to replace the coils on AC contactors with Coil replacement is not permitted for 3RT20..-.S contactors with
AC coils, and on AC/DC contactors with AC/DC coils. fail-safe control.
Solid-state operating mechanism for DC with 24 ... 110 V DC control signal input
e.g. for control by PLC with extended application range
(see also contactors for railway applications, page 4/61 onwards)
S6 3RT105..-.X...-0LA2 24 DC -- 3RT1955-5XB42
72 DC -- 3RT1955-5XJ42
110 DC -- 3RT1955-5XF42
S10 3RT106..-.X...-0LA2 24 DC -- 3RT1965-5XB42
72 DC -- 3RT1965-5XJ42
110 DC -- 3RT1965-5XF42
3RT1955-5X.42 S12 3RT107..-.X...-0LA2 24 DC -- 3RT1975-5XB42
72 DC -- 3RT1975-5XJ42
110 DC -- 3RT1975-5XF42
Note:
In the case of 3RT10..-.S contactors with fail-safe control inputs,
removing and replacing the operating mechanism are not permitted.
* You can order this quantity or a multiple thereof.
3/118 Siemens IC 10 · 2023 Illustrations are approximate
© Siemens 2023
3
3RT2036 utilization category AC-3 and AC-3e 3RT2936-6A 1 1 unit 41B
3RT2037 (1 set = 3 movable and 6 fixed 3RT2937-6A 1 1 unit 41B
3RT2038 contacts with fixing parts) 3RT2938-6A 1 1 unit 41B
1)
S3 3RT2045 3RT2945-6A 1 1 unit 41B
3RT2046 3RT2946-6A 1 1 unit 41B
3RT2047 3RT2947-6A 1 1 unit 41B
3RT294.-6A S6 3RT1054 3RT1954-6A 1 1 unit 41B
3RT1055 3RT1955-6A 1 1 unit 41B
3RT1056 3RT1956-6A 1 1 unit 41B
S10 3RT1064 3RT1964-6A 1 1 unit 41B
3RT1065 3RT1965-6A 1 1 unit 41B
3RT1066 3RT1966-6A 1 1 unit 41B
S12 3RT1075 3RT1975-6A 1 1 unit 41B
3RT1076 3RT1976-6A 1 1 unit 41B
3RT1954-6A S3 3RT2446 Main contacts (3 NO contacts) for 3RT2946-6D 1 1 unit 41B
3RT2448 utilization category AC-1 3RT2948-6D 1 1 unit 41B
S6 3RT1456 (1 set = 3 movable and 6 fixed 3RT1956-6D 1 1 unit 41B
S10 3RT1466 contacts with fixing parts) 3RT1966-6D 1 1 unit 41B
3RT1467 3RT1967-6D 1 1 unit 41B
S12 3RT1476 3RT1976-6D 1 1 unit 41B
3RT197.-6A,
3RT1976-6D
For contactors with 4 main contacts
S2 3RT2336 Main contacts (4 NO contacts) for 3RT2936-6E 1 1 unit 41B
3RT2337 utilization category AC-1 3RT2937-6E 1 1 unit 41B
(1 set = 3 movable and 6 fixed
contacts and spare pole with fixing
parts)
3RT2936-6E
Arc chutes
For contactors with 3 main contacts
S6 3RT1054 Only for contactors with AC/DC coil 3RT1954-7A 1 1 unit 41B
3RT1055 3RT1955-7A 1 1 unit 41B
3RT1056 3RT1956-7A 1 1 unit 41B
3RT1456 3RT1956-7B 1 1 unit 41B
3RT195.-7.
S10 3RT1064 3RT1964-7A 1 1 unit 41B
3RT1065 3RT1965-7A 1 1 unit 41B
3RT1066 3RT1966-7A 1 1 unit 41B
3RT1466 3RT1966-7B 1 1 unit 41B
3RT196.-7.
S12 3RT1075 3RT1975-7A 1 1 unit 41B
3RT1076 3RT1976-7A 1 1 unit 41B
3RT1476 3RT1976-7B 1 1 unit 41B
3RT197.-7.
1)
Switching of the spare contact is not permitted for
3RT20..-.S contactors with fail-safe control.
■ Overview
If there are further switching elements in the circuit, such as the
auxiliary contact system of an overload relay that operates the
contactor, the short-circuit protection necessary for this must
also be considered.
For further recommendations, e.g. the use of miniature circuit
breakers or circuit breakers for equipment in control circuits, see
Control panel tip – Fast, reliable selection and dimensioning of
3
3
contactor.
These auxiliary contacts are particularly suitable for solid-state
circuits with currents 1 mA at a voltage 17 V. Fitting auxiliary contacts and mounting additional auxiliary
switches
Vacuum interrupters Features in the delivery state
3RT12 vacuum contactors • 3RT12 vacuum contactors:
The contact gaps of the vacuum contactors are contained These contactors are supplied with two laterally mounted
in hermetically enclosed vacuum interrupters unlike the auxiliary switches with two contacts each (2 NO + 2 NC)
3RT10 contactors – the main contacts operate in air under • 3TF6 vacuum contactors:
atmospheric conditions. The particular benefit of vacuum These contactors are supplied with four laterally mounted
contactors, however, is that their electrical endurance is auxiliary switches with two contacts each (4 NO + 4 NC).
significantly higher. For operating mechanism versions with 3TC (3 NO + 3 NC)
series contactor, two auxiliary contacts are already defined.
They are especially suited to frequent switching in inching/mixed
operation, e.g. in crane control systems. Expansion possibilities
3TF6 vacuum contactors • 3RT12 vacuum contactors:
All basic devices can be expanded via auxiliary switches.
The switching contacts of the vacuum contactors are contained The permitted configuration must be taken into account.
in hermetically enclosed vacuum interrupters.
• Vacuum contactor 3TF6:
With these contactors, the contact erosion of the vacuum These devices are already fully equipped and no expansion
interrupters can be checked in the energized state with the help is possible.
of three white double slides below the connecting bars on the
outgoing side.
Operating mechanism types
3RT12 vacuum contactors
The contactors can be operated with AC (50 to 60 Hz) as well as
with DC.
Two types of solenoid operation are available:
• Standard operating mechanism for AC and DC operation
(power consumption reduced from closing to closed),
version 3RT12..-.A
• Solid-state operating mechanism, version 3RT12..-.N
3TF6 vacuum contactors
• Standard version 3TF6.44-.C.7 with AC operation
• Version 3TF6.33-.Q.7 for AC control supply voltage subject to
strong interference:
Contactors in this version are more robust against
EMC interference and are therefore designed for operation in
systems with AC control supply voltage that is subject to
strong interference. A 3TC44 (3TY7684-0Q..) reversing
contactor with a series resistor fitted is used to switch over
to holding control. The reversing contactor can be mounted
separately. It is connected to the 3TF6 main contactor by
means of a pre-assembled connecting cable (approx. 1 m
long) with plug-in connectors.
This version is recommended in the environment of frequency
converters and in the case of unshielded control cables.
• 3TF6.33-.D.4 contactors with DC control are supplied with
a 3TC4417-4A.. reversing contactor and a series resistor.
■ Technical specifications
Unless otherwise listed on subsequent pages, the technical
specifications of the SIRIUS 3RT12 vacuum contactors More information
correspond to those of the 3RT10 basic units; see pages 3/25, Technical specifications, see
and 3/41 to 3/46. https://support.industry.siemens.com/cs/ww/en/ps/16137/td
FAQs, see
https://support.industry.siemens.com/cs/ww/en/ps/16137/faq
System Manual for modular system, see
3
https://support.industry.siemens.com/cs/ww/en/view/60311318
Equipment Manual, see
https://support.industry.siemens.com/cs/ww/en/view/60306557
Application Manual - Switching devices with IE3 and IE4 motors, see
https://support.industry.siemens.com/cs/ww/en/view/94770820
Configuration Manual for load feeders, see
https://support.industry.siemens.com/cs/ww/en/view/39714188
Configuration Manual for UL, see
https://support.industry.siemens.com/cs/ww/en/view/53433538
Guide of use for contactors in safety applications, see
https://support.industry.siemens.com/cs/ww/en/view/109807687
690 V
400 V
breaking current and rated operational voltage. It is assumed that Contactor 3RT1264 3RT1265 3RT1266 3RT1275 3RT1276
the operating mechanisms are switched arbitrarily and not type (110 kW) (132 kW) (160 kW) (200 kW) (250 kW)
synchronously with the phase angle of the supply system switching 7
10
operating mechanism. 107 8 6 8 NSB0_01142a
8 6 4 6
The rated operational current Ie complies with utilization 6 4 4
category AC-4 (breaking 6 times the rated operational current) 4 2
and is intended for a contact endurance of approximately 2 6 2
200 000 operating cycles. 2 6 10
10 6
6 8 10
If a shorter contact endurance is sufficient, the rated operational 10 8 6 8
current Ie/AC-4 can be increased. 8 6 4 6
6 4 4
If the contacts are used for mixed operation, i.e. normal switching 4 2
(breaking the rated operational current according to utilization 2 5 2
category AC-3 and AC-3e) in combination with intermittent inching 2 5 10
10 5
(breaking several times the rated operational current according to 5 8 10
10 8 6 8
utilization category AC-4), the contact endurance can be 8 6 4 6
calculated approximately from the following equation: 6 4 4
4 2
A 2 2
X = ---------------------------------------------------------- 2 4
4 10
1 + ---------- ---- – 1
C A 4
10
100 B 8 10
40 50 60 80 100 200 300 400 600 8001 000 2 000 3 000
Characters in the equation: Breaking current a(A)
X Contact endurance for mixed operation in operating cycles
A Contact endurance for normal operation
(Ia = Ie) in operating cycles
B Contact endurance for inching
(Ia = multiple of Ie) in operating cycles
C Inching operations as a percentage of
total switching operations
Vacuum contactors
Type 3TF6
Size 14
Rated data of the auxiliary contacts According to IEC 60947-5-1
Rated insulation voltage Ui V 690
(pollution degree 3)
Conventional thermal current Ith = A 10
rated operational current Ie/AC-12
3
AC load
Rated operational current Ie/AC-15/AC-14
• At rated operational voltage Ue - At 24 V A 10
- At 110 V A 10
- At 125 V A 10
- At 220 V A 6
- At 230 V A 5.6
- At 380 V A 4
- At 400 V A 3.6
- At 500 V A 2.5
- At 660 V A 2.5
- At 690 V A 2.3
DC load
Rated operational current Ie/DC-12
• At rated operational voltage Ue - At 24 V A 10 10 10
- At 60 V A 10 10 10
- At 110 V A 3.2 3.2 3.2
- At 125 V A 2.5 2.5 2.5
- At 220 V A 0.9 0.9 0.9
- At 440 V A 0.33 0.33 0.33
- At 600 V A 0.22 0.22 0.22
Rated operational current Ie/DC-13 Auxiliary contacts with
delayed NC contact: N S = No specification
• At rated operational voltage Ue - At 24 V A 10 6
- At 60 V A 5 NS
- At 110 V A 1.14 0.98
- At 125 V A 0.98 NS
- At 220 V A 0.48 NS
- At 440 V A 0.13 NS
- At 600 V A 0.07 0.07
s and u rated data of the auxiliary contacts
Rated voltage, max. V AC 600
Switching capacity A 600, P 600
Vacuum contactors
Type 3TF6
Size 14
Electrical endurance of auxiliary contacts
The electrical endurance for utilization category
AC-12 or AC-15/AC-14 depends mainly on 4 NSB0_00651b
the breaking current. It is assumed that the 3
operating mechanisms are switched arbitrarily 2
Operating cycles
and not synchronously with the phase angle of
3
500 V
690 V
400 V
X Contact endurance for mixed operation 100 200 400 600 1 000 2 000 4 000 6 000
in operating cycles Breaking current a (A)
A Contact endurance for normal operation
(Ia = Ie) in operating cycles
B Contact endurance for inching
(Ia = multiple of Ie) in operating cycles
C Inching operations as a percentage of total
switching operations
3
'
Permissible mounting position
NSB0_00649a
NSB0_00650c
22,5° 22,5° 22,5° 22,5° 22,5° 22,5°
The contactors are designed for operation on a vertical 90° 90°
mounting surface.
mechanism
(3RT10..-.A)
- AC operation Closing at Us min/Us max VA 530/630 700/830 --
P.f. 0.9 --
Closed at Us min/Us max VA 6.1/7.4 7.6/9.2 --
P.f. 0.9 --
- DC operation Closing at Us min/Us max W 580/780 770/920 --
Closed at Us min/Us max W 6.8/8.2 8.5/10 --
• Solid-state operating
mechanism
(3RT10..-.N/-.P)
- AC operation Closing at Us min/Us max VA 420/570 560/750 --
P.f. 0.8 --
Closed at Us min/Us max VA 5.5/8.5 5.6/9 --
P.f. 0.5/0.4 --
- DC operation Closing at Us min/Us max W 460/630 600/800 --
Closed at Us min/Us max W 2.8/3.4 3/3.6 --
• Solid-state operating
mechanism
- AC operation Closing at Us min/Us max VA -- 1 200/1 850 600/950
(3TF6...-.C) P.f. -- 1 0.98
Closed at Us min/Us max VA -- 13.5/49 12.9/30.6
P.f. -- 0.15 0.31
- AC operation Closing at Us min VA -- 1 000 1 150
(3TF6...-.Q) P.f. -- 0.99
Closed at Us min VA -- 11
P.f. -- 1
- DC operation1) Closing at Us min W -- 1 010 960
(3TF6...-.D) Closed at Us min W -- 28 20.6
PLC control input according to IEC 61131-2 Type 2 --
• Rated voltage V DC 24 --
• Operating range V DC 17 ... 30 --
• Power consumption mA 30 --
Minimum command Standard ms -- 120
duration Reduced make-time ms -- 90 --
For closing
Minimum interval time between two ON commands ms -- 100 300
1)
At 24 V DC; for further voltages, deviations of up to 10% are possible.
3
• Rated power for slip-ring or - At 230 V kW 55 75 90 132 160 200 260 (200)1)
squirrel-cage motors - At 400 V kW 110 132 160 200 250 335 450 (335)1)
at 50 and 60 Hz - At 500 V kW 160 160 200 250 335 -- --
- At 690 V kW 200 250 250 400 500 600 800 (600)1)
- At 1 000 V kW 315 355 400 560 710 600 800
Thermal load capacity, 10 s current A 1 800 2 120 2 400 3 200 4 000 5 040 7 000
Power loss per main conducting path at Ie/AC-3/AC-3e/400 V W 9 12 14 21 32 45 70
Utilization category AC-4 (at Ia = 6 x Ie)
Maximum values:
• Rated operational current Ie - Up to 690 V A 195 230 280 350 430 610 690
• Rated power - At 400 V kW 110 132 160 200 250 355 400
for squirrel-cage motors
at 50 Hz and 60 Hz
The following applies to a contact endurance of about
200 000 operating cycles:
• Rated operational currents Ie - Up to 690 V A 97 115 140 175 215 300 360
- Up to 1 000 V A 68 81 98 123 151 210 250
• Rated power - At 230 V kW 30 37 45 56 70 97 110
for squirrel-cage motors - At 400 V kW 55 65 79 98 122 168 191
at 50 Hz and 60 Hz - At 500 V kW 68 81 98 124 153 2102) 2502)
- At 690 V kW 94 112 138 172 212 2782) 3352)
- At 1 000 V kW 95 114 140 183 217 2902) 3502)
1)
Value applies for utilization category AC-3e.
2) Max. permissible rated operational current Ie/AC-4 = Ie/AC-3/AC-3e up to
500 V, for reduced contact endurance and reduced switching frequency.
3
• Rated power for three-phase motors at 60 Hz
- At 200 V hp 60 75 100 125 150 231 290
- At 230 V hp 75 100 125 150 200 266 350
- At 460 V hp 150 200 250 300 400 530 700
- At 575 V hp 200 250 300 400 500 664 860
NEMA/EEMAC ratings
SIZE hp -- 6 7
• Uninterrupted current
- Open A -- 600 820
- Enclosed A -- 540 810
• Rated power for three-phase motors at 60 Hz
- At 200 V hp -- 150 --
- At 230 V hp -- 200 300
- At 460 V hp -- 400 600
- At 575 V hp -- 400 600
Short-circuit protection1) kA 10 18 30 100
• CLASS L fuse A 600 700 800 1 000 1 200 1 600
• Circuit breakers according to UL 489 A 500 700 800 1 000 1 200 On request1)
1) For more information about short-circuit values, e.g. for protection against
high short-circuit currents, see Certificate of Compliance for the individual
devices.
For the selection and dimensioning of load feeders, see
Configuration Manual for UL and the
UL guide "Competitive control panels for the North American market".
3RT1264-6AF36 3RT127.-6N.36
Size Rated data Auxiliary Rated control Screw terminals PU PS* PG
AC-3 and AC-3e, AC-1, contacts, supply (UNIT,
tu: up to 60 °C tu: 40 °C lateral voltage Us SET, M)
50/60 Hz AC
or DC
Opera- Rating of Opera- Article No. Price
tional three-phase motors tional per PU
current Ie at 50 Hz and current Ie
up to up to
1 000 V 230 V 400 V 500 V 690 V 1 000 V
A kW kW kW kW A NO NC V
Standard operating mechanism for AC and DC operation
(power consumption reduced from closing to closed)
With integrated coil circuit (varistor integrated at the factory)
S10 225 55 110 160 200 330 2 2 110 ... 127 3RT1264-6AF36 1 1 unit 41B
220 ... 240 3RT1264-6AP36 1 1 unit 41B
265 75 132 160 250 330 2 2 110 ... 127 3RT1265-6AF36 1 1 unit 41B
220 ... 240 3RT1265-6AP36 1 1 unit 41B
300 90 160 200 250 330 2 2 110 ... 127 3RT1266-6AF36 1 1 unit 41B
220 ... 240 3RT1266-6AP36 1 1 unit 41B
S12 400 132 200 250 400 610 2 2 110 ... 127 3RT1275-6AF36 1 1 unit 41B
220 ... 240 3RT1275-6AP36 1 1 unit 41B
500 160 250 355 500 610 2 2 110 ... 127 3RT1276-6AF36 1 1 unit 41B
220 ... 240 3RT1276-6AP36 1 1 unit 41B
Solid-state operating mechanism
With 24 V DC control signal input
e.g. for control by PLC
With integrated coil circuit (varistor integrated in electronics at the factory)
S10 225 55 110 160 200 330 2 2 96 ... 127 3RT1264-6NF36 1 1 unit 41B
200 ... 277 3RT1264-6NP36 1 1 unit 41B
265 75 132 160 250 330 2 2 96 ... 127 3RT1265-6NF36 1 1 unit 41B
200 ... 277 3RT1265-6NP36 1 1 unit 41B
300 90 160 200 250 330 2 2 96 ... 127 3RT1266-6NF36 1 1 unit 41B
200 ... 277 3RT1266-6NP36 1 1 unit 41B
S12 400 132 200 250 400 610 2 2 96 ... 127 3RT1275-6NF36 1 1 unit 41B
200 ... 277 3RT1275-6NP36 1 1 unit 41B
500 160 250 355 500 610 2 2 96 ... 127 3RT1276-6NF36 1 1 unit 41B
200 ... 277 3RT1276-6NP36 1 1 unit 41B
3
3TF68 3TF69
Size Rated data Auxiliary Rated control Screw terminals PU PS* PG
AC-3 and AC-3e, AC-1, contacts, supply (UNIT,
tu: up to 55 °C tu: 40 °C lateral voltage Us SET, M)
50/60 Hz AC
Opera- Rating of Opera- Article No. Price
tional three-phase motors tional per PU
current Ie at 50 Hz and current
up to Ie up to
690 V 230 V 400 V 690 V 1 000 V 690 V
A kW kW kW kW A NO NC V
AC operation 50/60 Hz1)
14 630 200 335 600 -- 700 4 4 110 ... 132 3TF6844-0CF7 1 1 unit 41B
200 ... 240 3TF6844-0CM7 1 1 unit 41B
600 700 4 4 110 ... 132 3TF6844-8CF7 1 1 unit 41B
200 ... 240 3TF6844-8CM7 1 1 unit 41B
14 820 260 450 800 -- 910 4 4 110 ... 132 3TF6944-0CF7 1 1 unit 41B
(630)2) (200)2) (335)2) (600)2) 200 ... 240 3TF6944-0CM7 1 1 unit 41B
800 910 4 4 110 ... 132 3TF6944-8CF7 1 1 unit 41B
200 ... 240 3TF6944-8CM7 1 1 unit 41B
1)
Please observe the information regarding the use of 3TF6 vacuum Rated control supply voltages, possible on request
contactors in the environment of frequency converters, see page 3/120. (change of the 10th and 11th digits of the article number)
2)
Value applies for utilization category AC-3e.
Delivery time on request
For an overview of the 3TF6 vacuum contactors with mountable
accessories, see page 3/17. Rated control supply Contactor type 3TF6844-.C..,
voltage Us 3TF6944-.C..
Accessories and spare parts, see pages 3/133 to 3/137.
Size 14
AC operation
Solenoid coils for 50/60 Hz
110 ... 132 V AC F7
200 ... 240 V AC M7
230 ... 277 V AC P7
380 ... 460 V AC Q7
500 ... 600 V AC S7
A1 3TF68,
A2 Main
3TF69
3
V contactor
V
6 Connecting
cable, 1 m
NSB0_01374a
3TC44 Reversing
contactor
3
Article No. Price
per PU
14 22 32 44
3TY7561-1AA00
3TF68, First auxiliary switch 3TY7561-1EA00 1 1 unit 41B
3TF69 1 -- 1 13 25 35 43
14 26 36 44
3TY7561-1EA00
3TF68, Second auxiliary switch 3TY7561-1KA00 1 1 unit 41B
3TF69 1 1 -- 53 61 71 83
54 62 72 84
3TY7561-1KA00
For switchover of the coil with DC circuit
14 3TF68, -- -- 1 B1 25 -- 3TY7681-1G 1 1 unit 41B
3TF69
B2 26
3TY7681-1G
Solid-state compatible auxiliary switches
For lateral mounting
14 3TF68, Second auxiliary switch, left or right 3TY7561-1UA00 1 1 unit 41B
3TF69 1 CO contact
51 61
52 54 62 64
5TY7561-1UA00
3RT1966-4G
Surge suppressors
14 3TF68, Varistors
3TF69 AC operation
The surge suppressor (varistor) is included in
the scope of supply of the 3TF68 and 3TF69
contactors with AC operation.
DC operation
3TX7572-3.
Varistor for snapping onto the side of the auxiliary
switch (includes the peak value of the alternating
voltage on the DC side),
connection to A1 and A2
Rated control supply voltage Us
• 24 ... 48 V DC 3TX7572-3G 1 1 unit 41B
• 127 ... 240 V DC 3TX7572-3J 1 1 unit 41B
Terminal covers
14 3TF68 For protection against inadvertent contact, 3TX7686-0A 1 1 unit 41B
3TF69 two units required per contactor 3TX7696-0A 1 1 unit 41B
(1 set = 2 units)
3TX76.6-0A
3TF68 On the outgoing side combined with overload 3TX7686-0B 1 1 unit 41B
relay, for protection against inadvertent contact
with exposed busbar connections
3TX7686-0B
Links for paralleling (star jumpers), 3-pole
14 3TF68, without connecting terminal 3TX7680-0D 1 1 unit 41B
3TF69 (the link for paralleling can be reduced
by one pole)
3TX7680-0D
Box terminals for laminated copper bars
14 3TF68 Without auxiliary conductor connection 3TX7570-1E 1 1 unit 41B
(1 set = 3 units)
With single covers for protection against
3TX7570-1E inadvertent contact (IEC 60529)
3TF69 With auxiliary conductor connection 3TX7690-1F 1 1 unit 41B
(1 set = 3 units)
Conductor cross-sections for auxiliary conductors:
3TX7690-1F • Solid 2 x (0.75 ... 2.5) mm2
• Finely stranded with end sleeve
2 x (0.5 ... 2.5) mm2
• AWG, solid or stranded 2 x (18 ... 12)
• Tightening torque 0.8 ... 1.4 Nm (7 ... 12 lb.in)
3
3TX7686-1A
Base plates
For reversing contactor assemblies
14 3TF68- For customer assembly of reversing contactor 3TX7681-1A 1 1 unit 41B
3TF68 assemblies
3TX7681-1A
For contactor assemblies for star-delta
(wye-delta) starting
14 3TF68- For configuring contactor assemblies for 3TX7681-1B 1 1 unit 41B
3TF68- star-delta (wye-delta) starting
3RT1.7
3TX7681-1B
Assembly kits for contactor assemblies
For reversing contactor assemblies
14 3TF68- The assembly kit contains: 3TX7680-1A 1 1 unit 41B
3TF68 wiring modules on the top and bottom
3TX7680-1A
For contactor assemblies for star-delta
(wye-delta) starting
14 3TF68- The assembly kit contains: 3TX7680-1B 1 1 unit 41B
3TF68- Wiring modules on the top and bottom,
3RT1.7 Star jumper S12
3TX7680-1B
Withdrawable coils
Standard operating mechanism for AC/DC
S10 3RT126 23 ... 26 3RT1966-5AB31 --
42 ... 48 3RT1966-5AD31 --
110 ... 127 3RT1966-5AF31 --
200 ... 220 3RT1966-5AM31 --
220 ... 240 3RT1966-5AP31 --
240 ... 277 3RT1966-5AU31 --
380 ... 420 3RT1966-5AV31 --
440 ... 480 3RT1966-5AR31 --
500 ... 550 3RT1966-5AS31 --
3RT1975-5A.31 575 ... 600 3RT1966-5AT31 --
S12 3RT127 23 ... 26 3RT1975-5AB31 3RT1975-5AB32
42 ... 48 3RT1975-5AD31 3RT1975-5AD32
110 ... 127 3RT1975-5AF31 3RT1975-5AF32
200 ... 220 3RT1975-5AM31 3RT1975-5AM32
220 ... 240 3RT1975-5AP31 3RT1975-5AP32
240 ... 277 3RT1975-5AU31 3RT1975-5AU32
380 ... 420 3RT1975-5AV31 3RT1975-5AV32
440 ... 480 3RT1975-5AR31 3RT1975-5AR32
500 ... 550 3RT1975-5AS31 3RT1975-5AS32
3RT1975-5A.32 575 ... 600 3RT1975-5AT31 3RT1975-5AT32
3
is supplied with switch-on 200 ... 240 3TY7683-0CQ7 1 1 unit 41B
electronics. 380 ... 460 3TY7683-0CS7 1 1 unit 41B
3TF69 110 ... 132 3TY7693-0CF7 1 1 unit 41B
200 ... 240 3TY7693-0CM7 1 1 unit 41B
3TY76.3-0C.. 230 ... 277 3TY7693-0CP7 1 1 unit 41B
200 ... 240 3TY7693-0CQ7 1 1 unit 41B
380 ... 460 3TY7693-0CS7 1 1 unit 41B
DC operation
14 3TF68 The solenoid coils are 24 DC 3TY7683-0DB4 1 1 unit 41B
supplied without reversing 110 DC 3TY7683-0DF4 1 1 unit 41B
3TY7683-0D.. contactor. 125 DC 3TY7683-0DG4 1 1 unit 41B
220 DC 3TY7683-0DM4 1 1 unit 41B
230 DC 3TY7683-0DP4 1 1 unit 41B
Vacuum interrupters
S10 3RT1264 Set with three vacuum -- 3RT1964-6V 1 1 unit 41B
3RT1265 interrupters with fixing parts -- 3RT1965-6V 1 1 unit 41B
3RT1266 -- 3RT1966-6V 1 1 unit 41B
S12 3RT1275 -- 3RT1975-6V 1 1 unit 41B
3RT1276 -- 3RT1976-6V 1 1 unit 41B
3RT197.-6V
14 3TF68 Set with three vacuum -- 3TY7680-0B 1 1 unit 41B
3TF69 interrupters with components -- 3TY7690-0B 1 1 unit 41B
Note:
In order to ensure reliable
operation of the contactors,
only original replacement
interrupters should be used.
3TY7690-0B
3TY7684-0Q.7
AC solenoid operating mechanism with coil
14 3TF6844-.C Solenoid operating 200 ... 240 3TY7685-0CM7 1 1 unit 41B
mechanism with coil 230 ... 276 3TY7685-0CP7 1 1 unit 41B
380 ... 420 3TY7685-0CS7 1 1 unit 41B
3TY7685-0C.7
■ Overview ■ Application
Standards Because they are hum-free they are suitable for use in
household appliances and distribution boards in office and
IEC 60947-1, IEC 60947-4-1, IEC 60947-5-1 residential areas.
Version They can also be used for applications where there is little
The 3TG10 power relays/miniature contactors are available with space, such as air conditioners, heating systems, pumps
screw terminals or 6.3 mm × 0.8 mm flat connectors. and fans, i.e. for simple electrical controls.
3
■ Technical specifications
More information
Technical specifications, see Reference Manual for switching devices, see
https://support.industry.siemens.com/cs/ww/en/ps/16186/td https://support.industry.siemens.com/cs/ww/en/view/35554359
FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/16186/faq
Type 3TG10
General data
Dimensions (W x H x D) mm 36 x 56 x 56
H
Endurance
• Mechanical Operating cycles 3 million
• Electrical
- AC-1 at Ie Operating cycles 0.1 million
- AC-3/AC-3e at Ie Operating cycles 0.4 million
Rated insulation voltage Ui (pollution degree 3) V 400
Rated impulse withstand voltage Uimp kV 4
Protective separation
Between the coil and the contacts according to IEC 60947-1, Annex N V Up to 300
Permissible ambient temperature
• During operation1) °C -25 ... + 55
• During storage °C -50 ... + 80
Short-circuit protection
Fuse links, operational class gG:
LV HRC, type 3NA; DIAZED, type 5SB; NEOZED, type 5SE
according to IEC 60947-4-1
• Type of coordination "1" A 25
• Type of coordination "2" A 10
Miniature circuit breakers, C characteristic A 10
Control
Solenoid coil operating range 0.85 ... 1.1 x Us
Power consumption of the solenoid coils (for cold coil and 1.0 x Us)
• AC operation, 45 ... 450 Hz VA 4.4
- P.f. 0.9 (hum-free)
• DC operation W 4
Rated data of the main contacts
Load rating with AC
Utilization category AC-1
• Rated operational current Ie up to 400 V at 55 °C1) A 20 for screw terminals, 16 for flat connectors
• Rated power Ue for AC loads with p.f. = 1, 230/220 V
- For screw terminals kW 7.5 (13 at 400 V)
- For flat connectors kW 6 (10 at 400 V)
• Minimum conductor cross-section for loads with Ie mm2 2.5
1) If the three main conducting paths carry a load of 20 A, the following
applies if I > 10 A in the fourth conducting path: Permissible ambient
temperature 40 °C.
Type 3TG10
Rated data of the main contacts (continued)
Load rating with AC
Utilization category AC-3 and AC-3e
• Operational current for AC-3/AC-3e at Ue 400 V rated value A 8.4/6.4
• Rated power for slip-ring or squirrel-cage motors for kW 4/3
AC-3/AC-3e, at 50 and 60 Hz and at Ue 400 V
Utilization category AC-5a (permissible nominal impedance: 0.5 )
3
Switching of gas discharge lamps
Per main conducting path at 230 V, 50 Hz
Rated power Rated
per lamp operational
current per
lamp
• Uncompensated 18 W 0.37 A Unit(s) 43
36 W 0.43 A Unit(s) 37
58 W 0.67 A Unit(s) 24
• DUO switching 18 W 2 x 0.11 A Unit(s) 2 x 81
36 W 2 x 0.21 A Unit(s) 2 x 42
58 W 2 x 0.32 A Unit(s) 2 x 28
Switching of gas discharge lamps with compensation or ECG
Per main conducting path 230 V, 50 Hz
Connection Rated power Capacitor Rated
per lamp capacitance operational
current
per lamp
• Shunt compensation L18 W 4.5 µF 0.11 A Unit(s) 15
L36 W 4.5 µF 0.21 A Unit(s) 15
L58 W 7 µF 0.32 A Unit(s) 10
• With ECG (single lamp) L18 W 6.8 µF 0.10 A Unit(s) 39
L36 W 6.8 µF 0.18 A Unit(s) 39
L58 W 10 µF 0.27 A Unit(s) 26
• With ECG (two lamps) L18 W 10 µF 0.18 A Unit(s) 2 x 26
L36 W 10 µF 0.35 A Unit(s) 2 x 26
L58 W 22 µF 0.52 A Unit(s) 2 x 12
Utilization category AC-5b, switching incandescent lamps kW 1.6
Per main conducting path at 230 V, 50 Hz
Load rating with DC
Utilization category DC-1, (L/R 15 ms)
• Rated operational currents Ie
- 1 conducting path Up to 24 V A 16
60 V A 6
110 V A 2
220 V/240 V A 0.8
- 2 conducting paths in series Up to 24 V A 16
60 V A 16
110 V A 6
220 V/240 V A 1.6
- 3 conducting paths in series Up to 24 V A 18
60 V A 18
110 V A 16
220 V/240 V A 6
Utilization category DC-3 and DC-5
Shunt-wound and series-wound motors (L/R 15 ms)
• Rated operational currents Ie
- 1 conducting path Up to 24 V A 10
60 V A 0.5
110 V A 0.15
220 V/240 V A 0
- 2 conducting paths in series Up to 24 V A 16
60 V A 5
110 V A 0.35
220 V/240 V A 0
- 3 conducting paths in series Up to 24 V A 16
60 V A 16
110 V A 10
220 V/240 V A 1.75
Type 3TG10
Conductor cross-sections
Screw terminals
• Terminal screws M3
• Finely stranded with end sleeve (DIN 46228 Form A/D/C) mm2 2 x (0.75 ... 2.5)
• Solid mm2 2 x (1 ... 2.5), 1 x 4
• Permissible opening tool (screwdriver) 3.0 mm x 0.5 mm (3RA2908-1A) or Pozidriv 2
3
Flat connectors
3
Opera- Power of Opera- Power of Version
tional AC loads at tional AC loads at
current Ie 50 Hz and current Ie 50 Hz and
up to 400 V up to 400 V
400 V 400 V1)
A kW A kW NO NC V
Hum-free with screw terminals
Screw terminals
■ Accessories
Version Max. rated operational Max. Screw terminals PU PS* PG
currents Ie/AC-1 conductor (UNIT,
(at 55 °C) of the cross-sections SET, M)
contactors
Article No. Price
A mm2 per PU
Links for paralleling (insulated star jumpers)1)
3-pole
• Without connecting 16 -- 3RT1916-4BA31 1 1 unit 41B
terminal
• With connecting terminal 40 25 3RT1916-4BB31 1 1 unit 41B
4-pole
3RT1916-4BB31 • With connecting terminal 40 25 3RT1916-4BB41 1 1 unit 41B
1)
The links for paralleling can be reduced by one pole.
The rated operational currents apply to each pole.
■ Overview
More information
Homepage, see www.siemens.com/sirius TIA Selection Tool Cloud (TST Cloud), see
Industry Mall, see www.siemens.com/product?3RA23_3RT1 www.siemens.com/tstcloud/?node=LoadFeeder
Conversion tool, see www.siemens.com/conversion-tool Guide of use for contactors in safety applications, see
https://support.industry.siemens.com/cs/ww/en/view/109807687
The 3RA23 reversing contactor assemblies in sizes S00 to S3 Complete 3RA23 reversing contactor assemblies
3
3
3 7 S00-S00 3RT2015-1...2 3RA2913-2AA1 3RA2315-8XB30-1...
4 9 3RT2016-1...2 3RA2913-2AA1 3RA2316-8XB30-1...
5.5 12 3RT2017-1...2 3RA2913-2AA1 3RA2317-8XB30-1...
7.5 16 3RT2018-1...2 3RA2913-2AA1 3RA2318-8XB30-1...
5.5 12 S0-S0 3RT2024-1...0 3RA2923-2AA1 3RA2324-8XB30-1...
7.5 17 3RT2025-1...0 3RA2923-2AA1 3RA2325-8XB30-1...
11 25 3RT2026-1...0 3RA2923-2AA1 3RA2326-8XB30-1...
15 32 3RT2027-1...0 3RA2923-2AA1 3RA2327-8XB30-1...
18.5 38 3RT2028-1...0 3RA2923-2AA1 3RA2328-8XB30-1...
18.5 41 S2-S2 3RT2035-1...0 3RA2933-2AA1 3RA2335-8XB30-1...
22 51 3RT2036-1...0 3RA2933-2AA1 3RA2336-8XB30-1...
30 65 3RT2037-1...0 3RA2933-2AA1 3RA2337-8XB30-1...
37 80 3RT2038-1...0 3RA2933-2AA1 3RA2338-8XB30-1...
37 80 S3-S3 3RT2045-1...0 3RA2943-2AA1 3RA2345-8XB30-1...
45 95 3RT2046-1...0 3RA2943-2AA1 3RA2346-8XB30-1...
55 110 3RT2047-1...0 3RA2943-2AA1 3RA2347-8XB30-1...
Spring-loaded terminals
9
3
5
7
1 4
2
IC01_00621c
10
10
3
8
9
6
6
6
6
6
1) Auxiliary switch according to EN 50005 must be used. For complete reversing contactor assemblies, see page 3/149.
2)
The parts 3 and 4 can only be ordered together as 3RA2912-2H
mechanical connectors.
3)
3RT201. contactors with one NC contact in the basic unit are required for
the electrical interlock. An additional NO contact is required for
momentary-contact operation.
3
1
7
4 2
IC01_00622b
9
9 3
8 5
6
6 6
6
6
1)
The parts 3 and 4 can only be ordered together as 3RA2922-2H For complete reversing contactor assemblies, see page 3/150.
mechanical connectors.
3
1
5 2
7
IC01_00623b
9
8 4
6
6
6
6
6
3
1
3 2
5
7
9
IC01_00624d
10
10
8 4
6
6
6
6
6
■ Benefits
Using wiring kits for reversing contactor assemblies has the Connecting combs for screw terminals also result in:
following advantages: • Prevention of wiring errors in the control circuit
• Notable reduction of wiring in the control circuit • Reduction of testing costs
• Integrated mechanical interlock for sizes S00 to S3 • Ready-jumpered actuation of the auxiliary switches and
• Prevention of wiring errors in the main circuit the frame (A2)
• Integrated electrical interlocking
3
■ Accessories
Selecting the auxiliary switches Surge suppression
The following points should be noted: Sizes S00 to S3
Size S00 All reversing contactor assemblies can be fitted with
• For maintained-contact operation: RC elements or varistors for damping switching overvoltages
Use contactors with an NC contact in the basic unit for in the coil.
the electrical interlock. As with the individual contactors, the surge suppressors can
• For momentary-contact operation: either be plugged onto the top of the contactors (S00) or be
Use contactors with an NC contact in the basic unit for the plugged into the front of the contactors (S0 to S3).
electrical interlock; in addition, an auxiliary switch with at least
one NO contact for self-locking is required per contactor.
Sizes S0 to S3
• For maintained-contact operation:
The contactors have two integrated auxiliary contacts
(1 NO contact + 1 NC contact); the NC contact can be
used for electrical interlocking.
• For momentary-contact operation:
Electrical interlock as for maintained-contact operation;
the NO contact in the basic unit can be used for the latching.
■ Technical specifications
More information
Technical specifications, see System Manual for modular system, see
https://support.industry.siemens.com/cs/ww/en/ps/16146/td https://support.industry.siemens.com/cs/ww/en/view/60311318
FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/16146/faq Equipment Manual, see
https://support.industry.siemens.com/cs/ww/en/view/60306557
Application Manual - Switching devices with IE3 and IE4 motors, see
https://support.industry.siemens.com/cs/ww/en/view/94770820
Guide of use for contactors in safety applications, see
https://support.industry.siemens.com/cs/ww/en/view/109807687
3
3RA231.-8XB30-1A.0 3RA231.-8XE30-1BB4 3RA231.-8XB30-2A.0
Rated data AC-3 and AC-3e Rated control Screw terminals Spring-loaded
Operational Ratings of three-phase motors supply voltage terminals
current Ie up to at 50 Hz and 60 Hz Us Article No. Price Article No. Price
400 V 230 V 400 V 690 V per PU per PU
A kW kW kW V
AC operation, 50/60 Hz
7 2.2 3 4 24 AC 3RA2315-8XB30-1AB0 3RA2315-8XB30-2AB0
110 AC 3RA2315-8XB30-1AF0 3RA2315-8XB30-2AF0
230 AC 3RA2315-8XB30-1AP0 3RA2315-8XB30-2AP0
9 3 4 5.5 24 AC 3RA2316-8XB30-1AB0 3RA2316-8XB30-2AB0
110 AC 3RA2316-8XB30-1AF0 3RA2316-8XB30-2AF0
230 AC 3RA2316-8XB30-1AP0 3RA2316-8XB30-2AP0
12 3 5.5 5.5 24 AC 3RA2317-8XB30-1AB0 3RA2317-8XB30-2AB0
110 AC 3RA2317-8XB30-1AF0 3RA2317-8XB30-2AF0
230 AC 3RA2317-8XB30-1AP0 3RA2317-8XB30-2AP0
16 4 7.5 7.5 24 AC 3RA2318-8XB30-1AB0 3RA2318-8XB30-2AB0
110 AC 3RA2318-8XB30-1AF0 3RA2318-8XB30-2AF0
230 AC 3RA2318-8XB30-1AP0 3RA2318-8XB30-2AP0
DC operation
7 2.2 3 4 24 DC 3RA2315-8XB30-1BB4 3RA2315-8XB30-2BB4
9 3 4 5.5 24 DC 3RA2316-8XB30-1BB4 3RA2316-8XB30-2BB4
12 3 5.5 5.5 24 DC 3RA2317-8XB30-1BB4 3RA2317-8XB30-2BB4
16 4 7.5 7.5 24 DC 3RA2318-8XB30-1BB4 3RA2318-8XB30-2BB4
With voltage tap-off
7 2.2 3 4 24 DC 3RA2315-8XE30-1BB4 3RA2315-8XE30-2BB4
9 3 4 5.5 24 DC 3RA2316-8XE30-1BB4 3RA2316-8XE30-2BB4
12 3 5.5 5.5 24 DC 3RA2317-8XE30-1BB4 3RA2317-8XE30-2BB4
16 4 7.5 7.5 24 DC 3RA2318-8XE30-1BB4 3RA2318-8XE30-2BB4
1)
The contactors integrated in the reversing contactor assemblies have no Representation of the complete reversing contactor assemblies
unassigned auxiliary contacts. When used with a voltage tap-off and with optionally mountable accessories, see page 3/144.
function module, the auxiliary contacts are unassigned.
3
3RA233.-8XB30-1A.2 3RA233.-8XE30-1NB3
Rated data AC-3 and AC-3e Rated control Screw terminals Spring-loaded
Operational Ratings of three-phase motors supply voltage terminals
current Ie up to at 50 Hz and 60 Hz Us
Article No. Price Article No. Price
400 V 230 V 400 V 690 V per PU per PU
A kW kW kW V
AC operation, 50/60 Hz
41 11 18.5 22 110 AC 3RA2335-8XB30-1AG2 --
230 AC 3RA2335-8XB30-1AL2 --
51 15 22 22 110 AC 3RA2336-8XB30-1AG2 --
230 AC 3RA2336-8XB30-1AL2 --
65 18.5 30 37 110 AC 3RA2337-8XB30-1AG2 --
230 AC 3RA2337-8XB30-1AL2 --
80 22 37 45 110 AC 3RA2338-8XB30-1AG2 --
230 AC 3RA2338-8XB30-1AL2 --
AC/DC operation
With integrated coil circuit
(varistor integrated in electronics at the factory)
41 11 18.5 22 20 ... 33 AC/DC 3RA2335-8XB30-1NB3 --
51 15 22 22 20 ... 33 AC/DC 3RA2336-8XB30-1NB3 --
65 18.5 30 37 20 ... 33 AC/DC 3RA2337-8XB30-1NB3 --
80 22 37 45 20 ... 33 AC/DC 3RA2338-8XB30-1NB3 --
With voltage tap-off
41 11 18.5 22 20 ... 33 AC/DC 3RA2335-8XE30-1NB3 --
51 15 22 22 20 ... 33 AC/DC 3RA2336-8XE30-1NB3 --
65 18.5 30 37 20 ... 33 AC/DC 3RA2337-8XE30-1NB3 --
80 22 37 45 20 ... 33 AC/DC 3RA2338-8XE30-1NB3 --
3RA234.-8XB30-1A.2 3RA234.-8XE30-1NB3
Rated data AC-3 and AC-3e Rated control Screw terminals Spring-loaded
Operational Ratings of three-phase motors supply voltage terminals
current Ie up to at 50 Hz and 60 Hz Us1) Article No. Price Article No. Price
400 V 230 V 400 V 690 V per PU per PU
A kW kW kW V
AC operation, 50/60 Hz
80 22 37 55 110 AC 3RA2345-8XB30-1AG2 --
230 AC 3RA2345-8XB30-1AL2 --
95 22 45 75 110 AC 3RA2346-8XB30-1AG2 --
230 AC 3RA2346-8XB30-1AL2 --
110 30 55 75 110 AC 3RA2347-8XB30-1AG2 --
230 AC 3RA2347-8XB30-1AL2 --
AC/DC operation
With integrated coil circuit
(varistor integrated in electronics at the factory)
80 22 37 55 20 ... 33 AC/DC 3RA2345-8XB30-1NB3 --
95 22 45 75 20 ... 33 AC/DC 3RA2346-8XB30-1NB3 --
110 30 55 75 20 ... 33 AC/DC 3RA2347-8XB30-1NB3 --
With voltage tap-off 1)
80 22 37 55 20 ... 33 AC/DC 3RA2345-8XE30-1NB3 --
95 22 45 75 20 ... 33 AC/DC 3RA2346-8XE30-1NB3 --
110 30 55 75 20 ... 33 AC/DC 3RA2347-8XE30-1NB3 --
1)
The associated module connectors 3RA2711-0EE17 for the 3RA271. Representation of the complete reversing contactor assemblies
function modules must be ordered separately, see page 3/102. with optionally mountable accessories, see page 3/147.
■ Overview
The individual parts for the reversing contactor assemblies for
customer assembly must be ordered separately. More information
• 3RT1 contactors (see page 3/64 onwards) and Homepage, see www.siemens.com/sirius
3RT12 and 3TF6 vacuum contactors (see page 3/130 Industry Mall, see www.siemens.com/product?3RA23_3RT1
onwards): Guide of use for contactors in safety applications, see
The operating times of the individual contactors are rated in https://support.industry.siemens.com/cs/ww/en/view/109807687
such a way that no overlapping of the contact connection and
3
the arcing time between two contactors can occur on
reversing, provided they are interlocked by way of their
auxiliary switches (NC contact interlock) and the mechanical
interlock.
For assemblies with AC operation and 50/60 Hz, a dead
interval of 50 ms must be provided when used with voltages
over 500 V; a dead interval of 30 ms is recommended for use
with voltages up to and including 400 V. These dead times do
not apply to assemblies with DC operation.
The operating times of the individual contactors are not
affected by the mechanical interlock.
• Mechanical interlocks
- 3RT1 contactors: see page 3/108
- 3TF68 vacuum contactors: Locking device for mechanical
interlock, see page 3/135.
• Wiring kits consisting of wiring modules on the top and bottom
- 3RT1 contactors: see page 3/104
- 3TF68 vacuum contactors: see page 3/135
• Base plates
- 3RT1 contactors: see page 3/113
- 3TF68 vacuum contactors: see page 3/135
Additional components
• For momentary-contact operation: auxiliary switch
(NO contact) for self-locking
• 3RB2 overload relays (see page 7/114 onwards),
SIMOCODE pro 3UF7 motor management and control
devices (see page 10/12 onwards) or 3RN2 thermistor motor
protection relays (see page 10/136 onwards) can be used for
overload protection.
6
3
2
8
4
8
5
IC01_00583c
7
7
3
3
1
2
7
IC01_00584c
6
6
5
3
3
1
IC01_00585c
6
6
3
2
IC01_00779
2
■ Overview
More information
Homepage, see www.siemens.com/sirius TIA Selection Tool Cloud (TST Cloud), see
Industry Mall, see www.siemens.com/product?3RA24_3RT www.siemens.com/tstcloud/?node=LoadFeeder
Conversion tool, see www.siemens.com/conversion-tool Guide of use for contactors in safety applications, see
https://support.industry.siemens.com/cs/ww/en/view/109807687
3
Screw terminals
9
3
2
1 5 3
IC01_00625c
4
Mountable accessories (optional) Complete contactor assembly for star-delta (wye-delta) starting
To be ordered separately Type Page Individual parts Type Page
Q112) Q13 Q12
9 3-phase infeed terminal1) 3RA2913-3K 3/110 1 2 3 Contactors, 5.5 kW 3RT2015 3RT2015 3RT2015 3/47, 3/52
1 2 3 Contactors, 7.5 kW 3RT2017 3RT2017 3RT2015 3/47, 3/52
1 2 3 Contactors, 11 kW 3RT2018 3RT2018 3RT2016 3/47, 3/52
4 ... 7 Assembly kit S00-S00-S00 3RA2913-2BB1 3/105
comprising:
4 Mechanical interlock
5 Four connecting clips for three contactors
6 Wiring modules on top and bottom for
connecting the main and auxiliary circuits
7 Star jumper
8 Function modules for star-delta 3RA2816-0EW20 3/100
(wye-delta) starting
1)
Part 9 can only be mounted for contactors with screw terminals. Complete contactor assemblies for star-delta (wye-delta)
2)
The version with 1 NO is required for momentary-contact operation. starting, see page 3/167.
10
9 6
3
7
2
3
1
IC01_00626c
4
Mountable accessories (optional) Complete contactor assembly for star-delta (wye-delta) starting
To be ordered separately Type Page Individual parts Type Page
Q11 Q13 Q12
9 3-phase infeed terminal1) 3RV2925-5AB 3/110 1 2 3 Contactors, 11 kW 3RT2024 3RT2024 3RT2024 3/48, 3/56
10 3-phase busbar1) 3RV1915-1AB 3/110 1 2 3 Contactors, 15/18.5 kW 3RT2026 3RT2026 3RT2024 3/48, 3/56
1 2 3 Contactors, 22 kW 3RT2027 3RT2027 3RT2026 3/48, 3/56
4 ... 7 Assembly kit S0-S0-S0 3RA2923-2BB1 3/105
comprising:
4 Mechanical interlock
5 Four connecting clips for three contactors
6 Wiring modules on top and bottom for
connecting the main and auxiliary circuits
7 Star jumper
8 Function modules for star- 3RA2816-0EW20 3/100
delta (wye-delta) starting
1)
The parts 9 and 10 can only be mounted for contactors with screw Complete contactor assemblies for star-delta (wye-delta)
terminals, the wiring modules 6 must be removed beforehand. starting, see page 3/168.
10
5
3
11
2
4
3
1
8
IC01_00627c
9
5
Mountable accessories (optional) Complete contactor assembly for star-delta (wye-delta) starting
To be ordered separately Type Page Individual parts Type Page
Q11 Q13 Q12
11 3-phase infeed terminal 3RV2935-5A 3/110 1 2 3 Contactors, 22/30 kW 3RT2035 3RT2035 3RT2026 3/50, 3/61
1 2 3 Contactors, 37 kW 3RT2035 3RT2035 3RT2027 3/50, 3/61
1 2 3 Contactors, 45 kW 3RT2036 3RT2036 3RT2028 3/50, 3/61
1 2 3 Contactors, 55 kW 3RT2037 3RT2037 3RT2035 3/50, 3/61
4 ... 7 Assembly kit S2-S2-S2 3RA2933-2BB1 3/105
comprising:
4 Four connectors for three contactors (not required for fully
pre-wired contactor assemblies for star-delta (wye-delta) starting)
5 Wiring modules on top and bottom for
connecting the main and auxiliary circuits
6 Star jumper S2
7 Cable for connecting the A2 coil contact of the line contactor
with the A2 coil contact of the delta contactor
(not shown in the drawing)
8 Mechanical interlock 3RA2934-2B 3/108
9 Function modules for star-delta 3RA2816-0EW20 3/100
(wye-delta) starting
10 Base plate star-delta 3RA2932-2F 3/113
(wye-delta)
1) Complete contactor assembly for star-delta (wye-delta) starting in size Complete contactor assemblies for star-delta (wye-delta)
S2-S2-S0 (not shown): The 3RA2933-2C assembly kit is to be used here, starting, see page 3/169.
see page 3/105.
10
5
11
3
1
2
6
4
3
IC01_00628c
9 5
9
Mountable accessories (optional) Complete contactor assembly for star-delta (wye-delta) starting
To be ordered separately Type Page Individual parts Type Page
Q11 Q13 Q12
11 1-phase infeed terminal 3RA2943-3L 3/110 1 2 3 Contactors, 55 kW 3RT2045 3RT2045 3RT2035 3/51, 3/63
(three units are required) Contactors, 75 kW 3RT2045 3RT2045 3RT2036 3/51, 3/63
1 2 3
1 2 3 Contactors, 90 kW 3RT2046 3RT2046 3RT2037 3/51, 3/63
4 ... 7 Assembly kit S3-S3-S2 3RA2943-2C 3/105
comprising:
4 Two connectors for three contactors (not required for fully
pre-wired contactor assemblies for star-delta (wye-delta) starting)
5 Wiring modules on top and bottom (S3-S2) for connecting the
main and auxiliary circuits and a cable set for the auxiliary circuit
6 Star jumper S2
7 Cable for connecting the A2 coil contact of the line contactor
with the A2 coil contact of the delta contactor
(not shown in the drawing)
8 Mechanical interlock 3RA2934-2B 3/108
9 Function modules for star-delta 3RA2816-0EW20 3/100
(wye-delta) starting
10 Base plate star-delta 3RA2942-2F 3/113
(wye-delta)
1)
Contactor assembly for star-delta (wye-delta) starting for customer Complete contactor assemblies for star-delta (wye-delta)
assembly in size S3-S3-S3 (not shown): The 3RA2943-2BB. assembly kit is starting, see page 3/170.
to be used here, see page 3/105.
■ Technical specifications
More information
Technical specifications, see Equipment Manual, see
https://support.industry.siemens.com/cs/ww/en/ps/16150/td https://support.industry.siemens.com/cs/ww/en/view/60306557
FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/16150/faq Application Manual - Switching devices with IE3 and IE4 motors, see
System Manual for modular system, see https://support.industry.siemens.com/cs/ww/en/view/94770820
https://support.industry.siemens.com/cs/ww/en/view/60311318 Guide of use for contactors in safety applications, see
https://support.industry.siemens.com/cs/ww/en/view/109807687
3
W
- Screw terminals mm 135 x 68 x 145 135 x 101 x 181
- Spring-loaded terminals mm 135 x 84 x 145 135 x 114 x 181
Individual contactors
• Q11 line contactor Type 3RT2015 3RT2017 3RT2018 3RT2024 3RT2026 3RT2027
• Q13 delta contactor Type 3RT2015 3RT2017 3RT2018 3RT2024 3RT2026 3RT2027
• Q12 star contactor Type 3RT2015 3RT2015 3RT2016 3RT2024 3RT2024 3RT2026
Mechanical endurance Operating 3 million
cycles
Unassigned auxiliary contacts of the individual For circuit diagrams of the control circuit, see
contactors Equipment Manual for contactors/contactor assemblies
Short-circuit protection
Main circuit without overload relays
Fuse links, operational class gG:
LV HRC, type 3NA; DIAZED, type 5SB; NEOZED,
type 5SE with single or double infeed
• Highest rated current of the fuse
according to IEC 60947-4-1
- Type of coordination "1" A 35 63 100 125
- Type of coordination "2" A 20 25 35 63
Auxiliary circuit
Short-circuit test
• With fuse links, operational class gG: A 10
DIAZED, type 5SB; NEOZED, type 5SE A 6 (up to Ik < 0.5 kA; 260 V),
with short-circuit current Ik = 1 kA according to if the auxiliary contact of the overload relay is connected in the contactor coil circuit
IEC 60947-5-1
• With miniature circuit breaker, C characteristic A 10
with short-circuit current Ik = 400 A A 6 (up to Ik < 0.5 kA; 260 V),
if the auxiliary contact of the overload relay is connected in the contactor coil circuit
Short-circuit protection with overload relay See Configuration Manual for load feeders
3
motors at 50 Hz and 60 Hz 400 V kW 5.8 8.2 12.5 21 30.1
690 V kW 5.8 7.5 18 20.4 33
• Switching frequency with overload relay 1/h 15
Current-carrying capacity with reversing time
up to 15 s
• Rated operational current Ie at 400 V A 12 17 25 31 44
690 V A 6.9 9 20.8 22.5 35
• Rated power for three-phase at 230 V kW 3.3 4.7 7.2 9.4 13.8
motors at 50 Hz and 60 Hz 400 V kW 5.8 8.2 12.5 16.3 24
690 V kW 5.8 7.5 18 20.4 33
• Switching frequency with overload relay 1/h 15
Current-carrying capacity with reversing time
up to 20 s
• Rated operational current Ie at 400 V A 12 17 25 28 39
690 V A 6.9 9 20.8 22.5 35
• Rated power for three-phase at 230 V kW 3.3 4.7 7.2 8.5 12.2
motors at 50 Hz and 60 Hz 400 V kW 5.8 8.2 12.5 14.7 21.3
690 V kW 5.8 7.5 18 20.4 33
• Switching frequency with overload relay 1/h 15
D
W
3
Individual contactors
• Q11 line contactor Type 3RT2035 3RT2035 3RT2036 3RT2037 3RT2045 3RT2045 3RT2046
• Q13 delta contactor Type 3RT2035 3RT2035 3RT2036 3RT2037 3RT2045 3RT2045 3RT2046
• Q12 star contactor Type 3RT2026 3RT2027 3RT2028 3RT2035 3RT2035 3RT2036 3RT2037
Mechanical endurance Operat- 1 million
ing
cycles
Unassigned auxiliary contacts of the individual For circuit diagrams of the control circuit, see Equipment Manual.
contactors
Short-circuit protection
Main circuit without overload relays
Fuse links, operational class gG:
LV HRC, type 3NA; DIAZED, type 5SB; NEOZED,
type 5SE with single or double infeed
• Highest rated current of the fuse
according to IEC 60947-4-1
- Type of coordination "1" A 160 250
- Type of coordination "2" A 80 125 160
Auxiliary circuit
Short-circuit test
• With fuse links, operational class gG: A 10
DIAZED, type 5SB; NEOZED, type 5SE A 6 (up to Ik < 0.5 kA; 260 V),
with short-circuit current Ik = 1 kA if the auxiliary contact of the overload relay is connected in the contactor coil circuit
according to IEC 60947-5-1
• With miniature circuit breaker, C characteristic A 10
with short-circuit current Ik = 400 A A 6 (up to Ik < 0.5 kA; 260 V),
if the auxiliary contact of the overload relay is connected in the contactor coil circuit
Short-circuit protection with overload relay See Configuration Manual for load feeders On request
Rated data of the main contacts
Current-carrying capacity with reversing time
up to 10 s
• Rated operational current Ie at 400 V A On request
690 V A On request
• Rated power for three-phase at 230 V kW On request
motors at 50 Hz and 60 Hz 400 V kW On request
690 V kW On request
• Switching frequency with overload relay 1/h 15
Current-carrying capacity with reversing time
up to 15 s
• Rated operational current Ie at 400 V A On request
690 V A On request
• Rated power for three-phase at 230 V kW On request
motors at 50 Hz and 60 Hz 400 V kW On request
690 V kW On request
• Switching frequency with overload relay 1/h 15
Current-carrying capacity with reversing time
up to 20 s
• Rated operational current Ie at 400 V A On request
690 V A On request
• Rated power for three-phase at 230 V kW On request
motors at 50 Hz and 60 Hz 400 V kW On request
690 V kW On request
• Switching frequency with overload relay 1/h 15
3
3RA241.-8XF31-1A.0 3RA241.-8XF31-2A.0 3RA241.-8XE31-2BB4
Rated data AC-3 Rated control Screw terminals Spring-loaded
Operational Ratings of three-phase motors supply terminals
current Ie at 50 Hz and 60 Hz voltage Us Article No. Price Article No. Price
up to at per PU per PU
400 V 230 V 400 V 690 V
A kW kW kW V
AC operation, 50/60 Hz
12 3.3 5.5 9.2 24 AC 3RA2415-8XF31-1AB0 3RA2415-8XF31-2AB0
110 AC 3RA2415-8XF31-1AF0 3RA2415-8XF31-2AF0
230 AC 3RA2415-8XF31-1AP0 3RA2415-8XF31-2AP0
16 4.7 7.5 9.2 24 AC 3RA2416-8XF31-1AB0 3RA2416-8XF31-2AB0
110 AC 3RA2416-8XF31-1AF0 3RA2416-8XF31-2AF0
230 AC 3RA2416-8XF31-1AP0 3RA2416-8XF31-2AP0
25 5.5 11 11 24 AC 3RA2417-8XF31-1AB0 3RA2417-8XF31-2AB0
110 AC 3RA2417-8XF31-1AF0 3RA2417-8XF31-2AF0
230 AC 3RA2417-8XF31-1AP0 3RA2417-8XF31-2AP0
DC operation
12 3.3 5.5 9.2 24 DC 3RA2415-8XF31-1BB4 3RA2415-8XF31-2BB4
16 4.7 7.5 9.2 24 DC 3RA2416-8XF31-1BB4 3RA2416-8XF31-2BB4
25 5.5 11 11 24 DC 3RA2417-8XF31-1BB4 3RA2417-8XF31-2BB4
For IO-Link connection
12 3.3 5.5 9.2 24 DC 3RA2415-8XE31-1BB4 3RA2415-8XE31-2BB4
16 4.7 7.5 9.2 24 DC 3RA2416-8XE31-1BB4 3RA2416-8XE31-2BB4
25 5.5 11 11 24 DC 3RA2417-8XE31-1BB4 3RA2417-8XE31-2BB4
For AS-Interface integration
12 3.3 5.5 9.2 24 DC 3RA2415-8XH31-1BB4 3RA2415-8XH31-2BB4
16 4.7 7.5 9.2 24 DC 3RA2416-8XH31-1BB4 3RA2416-8XH31-2BB4
25 5.5 11 11 24 DC 3RA2417-8XH31-1BB4 3RA2417-8XH31-2BB4
Fully wired and tested contactor assemblies for star-delta (wye-delta) starting · Size S0-S0-S0 · Up to 22 kW
AC operation or DC operation
PU (UNIT, SET, M) = 1
PS* = 1 unit
PG = 41B
3
3
3RA2437-8XF32-1A.2 3RA2434-8XE32-1NB3
Rated data AC-3 Rated control Screw terminals Spring-loaded
Operational Ratings of three-phase motors supply terminals
current Ie at 50 Hz and 60 Hz voltage Us Article No. Price Article No. Price
up to at per PU per PU
400 V 230 V 400 V 690 V
A kW kW kW V
AC operation, 50/60 Hz
50/65 19.6 22/30 34 24 AC 3RA2434-8XF32-1AC2 --
110 AC 3RA2434-8XF32-1AG2 --
230 AC 3RA2434-8XF32-1AL2 --
80 25 37 63 24 AC 3RA2435-8XF32-1AC2 --
110 AC 3RA2435-8XF32-1AG2 --
230 AC 3RA2435-8XF32-1AL2 --
86 27 45 63 24 AC 3RA2436-8XF32-1AC2 --
110 AC 3RA2436-8XF32-1AG2 --
230 AC 3RA2436-8XF32-1AL2 --
115 37 55 93 24 AC 3RA2437-8XF32-1AC2 --
110 AC 3RA2437-8XF32-1AG2 --
230 AC 3RA2437-8XF32-1AL2 --
AC/DC operation, 50/60 Hz AC or DC
With integrated coil circuit
(varistor integrated in electronics at the factory)
50/65 19.6 22/30 34 20 ... 33 AC/DC 3RA2434-8XF32-1NB3 --
80 25 37 63 20 ... 33 AC/DC 3RA2435-8XF32-1NB3 --
86 27 45 63 20 ... 33 AC/DC 3RA2436-8XF32-1NB3 --
115 37 55 93 20 ... 33 AC/DC 3RA2437-8XF32-1NB3 --
For IO-Link connection
50/65 19.6 22/30 34 20 ... 33 AC/DC 3RA2434-8XE32-1NB3 --
80 25 37 63 20 ... 33 AC/DC 3RA2435-8XE32-1NB3 --
86 27 45 63 20 ... 33 AC/DC 3RA2436-8XE32-1NB3 --
115 37 55 93 20 ... 33 AC/DC 3RA2437-8XE32-1NB3 --
For AS-Interface integration
50/65 19.6 22/30 34 20 ... 33 AC/DC 3RA2434-8XH32-1NB3 --
80 25 37 63 20 ... 33 AC/DC 3RA2435-8XH32-1NB3 --
86 27 45 63 20 ... 33 AC/DC 3RA2436-8XH32-1NB3 --
115 37 55 93 20 ... 33 AC/DC 3RA2437-8XH32-1NB3 --
Fully wired and tested contactor assemblies for star-delta (wye-delta) starting · Size S3-S3-S2 · Up to 90 kW
AC operation or AC/DC operation
PU (UNIT, SET, M) = 1
PS* = 1 unit
PG = 41B
3
■ Overview
The individual parts for the contactor assemblies for star-delta
(wye-delta) starting for customer assembly must be ordered
separately.
• 3RT contactors (see page 3/64 onwards) and
3RT12 and 3TF6 vacuum contactors (see page 3/135
onwards): Video: SIRIUS contactor assembly for star-delta (wye-delta) starting –
The operating times of the individual contactors are rated in configuration example with 75 kW contactors
3
such a way that no overlapping of the contact connection and
the arcing time between two contactors can occur on More information
reversing, provided they are interlocked by way of their
Homepage, see www.siemens.com/sirius
auxiliary switches (NC contact interlock) and the mechanical
interlock. Industry Mall, see www.siemens.com/product?3RA24_3RT
For assemblies with AC operation and 50/60 Hz, a dead Guide of use for contactors in safety applications, see
interval of 50 ms must be provided when used with voltages https://support.industry.siemens.com/cs/ww/en/view/109807687
over 500 V; a dead interval of 30 ms is recommended for use
with voltages up to and including 400 V. These dead times do
not apply to assemblies with DC operation.
The operating times of the individual contactors are not
affected by the mechanical interlock.
• Mechanical interlocks
- 3RT contactors and 3RT12 vacuum contactors: Adapter and
mechanical interlock to interlock S6 and S3, see page 3/108.
- 3TF68 vacuum contactors: Locking device for mechanical
interlock, see page 3/135.
• Wiring kits consisting of wiring modules or link rails and star
jumpers
- 3RT contactors and 3RT12 vacuum contactors:
see page 3/106 onwards
- 3TF68 vacuum contactors: see page 3/135
• Base plates
- 3RT contactors and 3RT12 vacuum contactors:
see page 3/113
- 3TF68 vacuum contactors: see page 3/135
Additional components
• For momentary-contact operation: auxiliary switch
(NO contact) for self-locking
• 3RB2 overload relays (see page 7/114 onwards),
SIMOCODE pro 3UF7 motor management and control
devices (see page 10/12 onwards) or 3RN2 thermistor motor
protection relays (see page 10/136 onwards) can be used for
overload protection.
The overload relay can either be mounted on the line
contactor or separately fitted. It must be set to 0.58 times
the rated motor current.
• Optional surge suppression for the S3 contactors; the
contactors in sizes S6 to S12 are wired as standard with
varistors.
The contactor assemblies for star-delta (wye-delta) starting
for customer assembly are designed for standard applications.
Note:
Contactor assemblies for star-delta (wye-delta) starting in
special applications such as very heavy starting1) or star-delta
(wye-delta) starting of special motors must be customized.
Help with designing such special applications is available from
our Technical Support,
www.siemens.com/support-request.
1)
For effective assistance from Technical Support, you must provide the
following details:
- Rated motor voltage,
- Rated motor current,
- Service factor, operating values
- Motor starting current factor
- Starting time
- Ambient temperature
10
3
11
11
1
2
5
3 9
IC01_00630b
6
11
8
11
9
4 Additional connecting
cables are not shown.
Mountable accessories (optional) Contactor assemblies for star-delta (wye-delta) starting for customer assembly
To be ordered separately Type Page Individual parts Type Page
Q11 Q13 Q12
11 Box terminal blocks 3RT1955-4G 3/110 1 2 3 Contactors, 110 kW 3RT1054 3RT1054 3RT2045 3/51, 3/59,
3/63 ... 3/66
1 2 3 Contactors, 132 kW 3RT1055 3RT1055 3RT2046 3/51, 3/59,
3/63 ... 3/66
1 2 3 Contactors, 160 kW 3RT1056 3RT1056 3RT2047 3/51, 3/59,
3/63 ... 3/66
4 Assembly kit S6-S6-S3 3RA1953-3G 3/106
for contactors with box terminals
consisting of:
Wiring modules, bottom
5 Star jumper S3 3RT1946-4BA31 3/107
6 Adapter for the mechanical interlock 3RA1954-2G1) 3/108
between S6 and S3 (including two
connectors)
7 Mechanical interlock between S6 3RA1954-2A 3/108
and S3
8 Timing relay with star-delta 3RP257. 10/34
(wye-delta) function
9 Push-in lugs for star-delta 3ZY1311-0AA00 10/35
(wye-delta) timing relays
10 Base plate star-delta (wye-delta) 3RA1952-2E 3/113
11 Box terminal block 3RT1955-4G 3/110
1)
The 3RA1954-2G adapter cannot be used in conjunction
with 3RT204..-.KB coupling contactors, size S3.
11
5 5
3
12
12
12
1
2
8 3 10
IC01_00629b
8
10
6
12
12
12
Mountable accessories (optional) Contactor assemblies for star-delta (wye-delta) starting for customer assembly
To be ordered separately Type Page Individual parts Type Page
Q11 Q13 Q12
12 Box terminal blocks 3RT1955-4G 3/110 1 2 3 Contactors, 110 kW 3RT1054 3RT1054 3RT1054 3/64 ... 3/66
1 2 3 Contactors, 132 kW 3RT1055 3RT1055 3RT1055 3/64 ... 3/66
1 2 3 Contactors, 160 kW 3RT1056 3RT1056 3RT1056 3/64 ... 3/66
4 5 Assembly kit S6-S6-S6 3RA1953-2B 3/106
for contactors with box terminals
consisting of:
4 Link rails, bottom
5 Star jumper S6
5 6 Assembly kit S6-S6-S6 3RA1953-2N 3/106
for contactors without box terminals
consisting of:
6 Link rails, bottom
5 Star jumper S6
7 Mechanical interlock 3RA1954-2A 3/108
8 Four connectors 3RA1932-2D 3/108
9 Timing relay with star-delta (wye-delta) function 3RP257. 10/34
10 Push-in lugs for star-delta (wye-delta) timing relays 3ZY1311-0AA00 10/35
11 Base plate star-delta (wye-delta) 3RA1952-2F 3/113
12 Box terminal block 3RT1955-4G 3/110
Video: SIRIUS contactor assembly for star-delta (wye-delta) starting – configuration example with 75 kW contactors
9
3
10
10
2
5
8
3
6 7
IC01_00589b
10
10
8
Mountable accessories (optional) Contactor assemblies for star-delta (wye-delta) starting for customer assembly
To be ordered separately Type Page Individual parts Type Page
Q11 Q13 Q12
10 Box terminal blocks 3RT1966-4G 3/110 1 2 3 Contactors, 200 kW 3RT1.64 3RT1.64 3RT1054 3/64 ... 3/66, 3/130
1 2 3 Contactors, 250 kW 3RT1.65 3RT1.65 3RT1055 3/64 ... 3/66, 3/130
4 Assembly kit S10-S10-S6 3RA1963-3E 3/106
for contactors with box terminals
consisting of:
Wiring modules, bottom
5 Star jumper S6 3RT1956-4BA31 3/107
6 Mechanical interlock between 3RA1954-2A 3/108
S10 and S6
7 Timing relay with star-delta 3RP257. 10/34
(wye-delta) function
8 Push-in lugs for star-delta 3ZY1311-0AA00 10/35
(wye-delta) timing relays
9 Base plate star-delta (wye-delta) 3RA1962-2E 3/113
10 Box terminal block 3RT1966-4G 3/110
Video: SIRIUS contactor assembly for star-delta (wye-delta) starting – configuration example with 75 kW contactors
3
5
10
10
10
3 8
IC01_00588b
10 7
8
4
Mountable accessories (optional) Contactor assemblies for star-delta (wye-delta) starting for customer assembly
To be ordered separately Type Page Individual parts Type Page
Q11 Q13 Q12
10 Box terminal blocks 3RT1966-4G 3/110 1 2 3 Contactors, 200 kW 3RT1.64 3RT1.64 3RT1.64 3/64 ... 3/66, 3/130
1 2 3 Contactors, 250 kW 3RT1.65 3RT1.65 3RT1.65 3/64 ... 3/66, 3/130
4 5 Assembly kit S10-S10-S10 3RA1963-2B 3/106
for contactors without box terminals
consisting of:
4 Link rails, bottom
5 Star jumper S10
6 Mechanical interlock 3RA1954-2A 3/108
7 Timing relay with star-delta 3RP257. 10/34
(wye-delta) function
8 Push-in lugs for star-delta 3ZY1311-0AA00 10/35
(wye-delta) timing relays
9 Base plate star-delta (wye-delta) 3RA1962-2F 3/113
Video: SIRIUS contactor assembly for star-delta (wye-delta) starting – configuration example with 75 kW contactors
9
3
10
10
10
1
2
3 8
IC01_00587b
10
10
10 8
Mountable accessories (optional) Contactor assemblies for star-delta (wye-delta) starting for customer assembly
To be ordered separately Type Page Individual parts Type Page
Q11 Q13 Q12
10 Box terminal blocks 3RT1966-4G 3/110 1 2 3 Contactors, 355 kW 3RT1.75 3RT1.75 3RT1.64 3/64 ... 3/66, 3/130
1 2 3 Contactors, 400 kW 3RT1.75 3RT1.75 3RT1.65 3/64 ... 3/66, 3/130
1 2 3 Contactors, 500 kW 3RT1.76 3RT1.76 3RT1.66 3/64 ... 3/66, 3/130
4 Assembly kit S12-S12-S10 3RA1973-3E 3/106
for contactors with box terminals
consisting of:
Wiring modules, bottom
5 Star jumper S10 3RT1966-4BA31 3/107
6 Mechanical interlock between S12 and S10 3RA1954-2A 3/108
7 Timing relay with star-delta (wye-delta) function 3RP257. 10/34
8 Push-in lugs for star-delta 3ZY1311-0AA00 10/35
(wye-delta) timing relays
9 Base plate star-delta (wye-delta) 3RA1972-2E 3/113
10 Box terminal blocks 3RT1966-4G 3/110
Video: SIRIUS contactor assembly for star-delta (wye-delta) starting – configuration example with 75 kW contactors
3
5
10
10
10
3 8
IC01_00586b
10 7
Mountable accessories (optional) Contactor assemblies for star-delta (wye-delta) starting for customer assembly
To be ordered separately Type Page Individual parts Type Page
Q11 Q13 Q12
10 Box terminal blocks 3RT1966-4G 3/110 1 2 3 Contactors, 400 kW 3RT1.75 3RT1.75 3RT1.75 3/64 ... 3/66, 3/130
1 2 3 Contactors, 500 kW 3RT1.76 3RT1.76 3RT1.76 3/64 ... 3/66, 3/130
4 5 Assembly kit S12-S12-S12 3RA1973-2B 3/106
for contactors without box
terminals
consisting of:
4 Link rails, bottom
5 Star jumper S12
6 Mechanical interlock 3RA1954-2A 3/108
7 Timing relay with star-delta 3RP257. 10/34
(wye-delta) function
8 Push-in lugs for star-delta 3ZY1311-0AA00 10/35
(wye-delta) timing relays
9 Base plate star-delta (wye-delta) 3RA1972-2F 3/113
Video: SIRIUS contactor assembly for star-delta (wye-delta) starting – configuration example with 75 kW contactors
7
3
1
4
2 6
IC01_00778
6
Price groups
PG 41A, 41B
4/2 Introduction
4
4/36 SIRIUS 3RT25 contactors, 4-pole,
2 NO + 2 NC
4/42 SIRIUS 3RT26 contactors for capacitive
loads (AC-6b), 3-pole
4/52 SIRIUS 3RT23 to 3RT26, 3RT14
contactors
Contactors for railway applications
4/54 - SIRIUS 3RT contactors with extended
operating range, 3-pole
4/63 - SIRIUS 3RH2 contactor relays with
extended operating range
4/66 - 3TH4 contactor relays, 8-pole
4/68 - 3TC contactors for switching DC
voltage, 2-pole
4/70 3TC contactors for switching DC
voltage, 1- and 2-pole
Siemens IC 10 · 2023
© Siemens 2023
Introduction
■ Overview
AC-3/AC-3e
AC-3e
le
po
3-
3RT12 3TF6
500 A/250 kW 820 A/450 kW
4
AC-3/AC-3e
AC-3e
le
po
3-
3RT20 3RT10
110 A/55 kW 500 A/250 kW
AC-1
le
po
3-
3RT24 3RT14
160 A 690 A 2 650 A
AC-1
le
po
4-
3RT23 3RT13
160 A 525 A
AC- 6b
le
po
3-
3RT26
151 A/100 kvar
AC-3
IC01_00563b
le
po
4-
3RT25
80 A/37 kW
Introduction
More information
Homepage, see www.siemens.com/sirius Conversion tool, see www.siemens.com/conversion-tool
Industry Mall, see www.siemens.com/product?3RT_3TK_3TC TIA Selection Tool Cloud (TST Cloud), see
www.siemens.com/tstcloud/?node=Contactor
4
Size S3 S6 S10 S12
Type 3RT244. 3RT1456 3RT146. 3RT1476
3-pole 3RT244 and 3RT145 to 3RT147 contactors
Type 3RT2446 3RT2448 3RT1456 3RT1466 3RT1467 3RT1476
Number of main contacts 3 NO 3 NO 3 NO 3 NO
AC, AC/DC operation (p. 4/16) (p. 4/17, 4/18) (p. 4/17, 4/18) (p. 4/17, 4/18)
AC-1
Ui V 1 000
Ue V 690
Ie up to 690 V 40 °C A 140 160 275 400 500 690
60 °C A 130 140 250 380 450 Standard operating
mechanism: 650,
solid-state operating
mechanism: 600
Introduction
Size S00 S0 S2 S3
Type 3RT231. 3RT232. 3RT233. 3RT234.
4-pole 3RT23 contactors
Type 3RT2316 3RT2317 3RT2325 3RT2326 3RT2327 3RT2336 3RT2337 3RT2344 3RT2346 3RT2348
4
Introduction
Size S00 S0 S2 S3
Type 3RT251. 3RT252. 3RT253. 3RT254.
4-pole 3RT25 contactors
Type 3RT2516 3RT2517 3RT2518 3RT2526 3RT2535 3RT2536 3RT2544 3RT2545
4
Number of main contacts 2 NO + 2 NC 2 NO + 2 NC 2 NO + 2 NC 2 NO + 2 NC
AC, DC and AC/DC operation (p. 4/39, 4/40) (p. 4/39, 4/40) (p. 4/39, 4/41) (p. 4/39, 4/41)
AC-1
Ui V 690
Ue V 690
Ie up to 690 V 40 °C A 18 22 22 40 60 70 100 125
60 °C A 16 20 20 35 55 60 90 105
AC-3
Ie up to 400 V NO A 9 12 16 25 35 41 65 80
NC A 9 9 9 25 (20)1) 35 41 65 80
P
At 400 V NO kW 4 5.5 7.5 11 18.5 22 30 37
NC kW 4 4 4 11 (7.5)1) 18.5 22 30 37
At 230 V NO kW 2.2 3/2.2 4/2.2 5.5 11 11 18.5 22
NC kW 2.2 3/2.2 4/2.2 5.5 11 11 18.5 22
Further contactors
• SIRIUS 3RT26 contactors for capacitive loads (AC-6b), 3-pole,
see page 4/42 onwards
• 3TC contactors for switching DC voltage, 1-pole and 2-pole,
see page 4/70 onwards
• Contactors for railway applications
- SIRIUS 3RT contactors with extended operating range, 3-pole,
see page 4/54 onwards
- SIRIUS 3RH2 contactor relays with extended operating
range, see page 4/65
- 3TH4 contactor relays, 8-pole, see page 4/66 onwards
Introduction
Connection methods Voltage data
The following connection options are available for The data for 3-phase power systems according to
3RT contactors depending on the size and version: IEC 60947-4-1 are valid for the following forms of power supply:
.
IC01_00703
• 3RT13 contactors, sizes S6 to S12: Busbar connections
IC01_00709
(partly with bus connectors offset), auxiliary and control
circuits with screw terminals
4
■ Overview
4
3-pole AC-1 contactors
top row: 3RT148 contactors
bottom row: 3RT244, 3RT145 to 3RT147 contactors
Standards If there are further switching elements in the circuit, such as the
auxiliary contact system of an overload relay that operates the
IEC 60947-1, IEC 60947-4-1, IEC 60947-5-1 (auxiliary switches) contactor, the short-circuit protection necessary for this must
Contactors with increased tamper protection also be considered.
Increased tamper protection is ensured either by using our For further recommendations, e.g. the use of miniature circuit
contactor versions with factory-installed, permanently mounted breakers or circuit breakers for equipment in control circuits, see
auxiliary switches which are protected against mechanical Control panel tip – Selecting and dimensioning suitable power
external actuation (e.g. 3RT14..-.....-3PA0 contactors), or by supplies quickly and reliably.
using the 3RT1926-4MA10 sealable cover as an accessory, Short-circuit and overload protection of contactors with
(see page 3/112). a digital input
Protecting connections against short circuit, overload and A typical rated current of 20 mA applies to these inputs
overvoltage according to the PLC input types according to IEC 60947-4-1.
All connections must generally be protected against overload The inputs can be protected accordingly.
and short circuits using suitable measures. Different constraints • Contactors with PLC and F-PLC inputs:
must be considered depending on the type of connection: - For 3RT14..-.S and 3RT14..-.N, marked with +/-
Short-circuit and overload protection of main connections • Supply voltage connections A1 - A2:
- For 3RT14..-.N, protection based on the load characteristics
For information on the protection of a free-standing contactor, must be employed.
see the technical product data sheet. For information on power consumption, see the technical
For more information on complete units such as contactors with product data sheet.
overload relays or contactors with motor starter protectors as the - For 3RT14..-.S, protection is already integrated.
motor feeder, see Configuration Manual for load feeders. Short-circuit and overload protection of other connections
Short-circuit and overload protection of auxiliary connections The 3RT14..-.P contactor version with remaining lifetime
For information on the protection of auxiliary contacts, see the indicator (RLT) also has additional connections H1 - H2 and
technical product data sheet R1 - R2.
Short-circuit and overload protection of control supply voltage If A1 - A2 is already protected, further protection of H1 - H2 is not
connections or supply voltage connections required.
First of all, the relevant standards and regulations for configuring For protection specifications for protecting R1 - R2, see the
control panels and the parts and components installed in them technical product data sheet.
must be taken into account, for example for cable dimensioning.
One possible protection for these circuits could be the selection
of a suitable power supply, i.e. one with a current-limiting
function. In the selection of the source and the connecting cable,
the load characteristics of the contactor must be considered
(short-time inrush current peaks for solid-state operating
mechanisms, switch-on power, holding power).
4
3RH2 contactor relay
• Standard operating mechanism:
operational switching via coupling links and
3RT2 contactor F-DQ
• Solid-state operating mechanism:
Feedback operational switching with PLC-IN and DQ
EMERGENCY SIMATIC S7-1500 DQ 3RT1
STOP F-DQ
contactor
A1
PLC-IN
A2
3RT1 contactor
A1
PLC-IN
A2
IC01_00540
N/-
Application with safety-related disconnection with standard contactors using the example of a 3RT145 contactor
Example for SIL 3/PL e (left-hand side) or SIL 2/PL c (right-hand side) application – new:
N/- N/-
Application with safety-related disconnection with contactors with fail-safe control using the example of a 3RT145 contactor
IC01_00694
■ Application
The 3RT.4 contactors can be used for the following applications:
• For switching weak or non-inductive loads (AC-1)
• Disconnecting loads or power generation plants from the grid
(e.g. wind turbines or photovoltaic systems)
• Disconnecting frequency converters from the grid
■ Technical specifications
More information
Technical specifications, see Manuals, see
https://support.industry.siemens.com/cs/ww/en/ps/24229/td https://support.industry.siemens.com/cs/ww/en/ps/24229/man
For FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/24229/faq Guide of use for contactors in safety applications, see
https://support.industry.siemens.com/cs/ww/en/view/109807687
4
• Basic units
- Screw/spring-loaded terminals mm 70 x 140 x 152 120 x 172 x 170 145 x 210 x 202 160 x 214 x 225
H
switch W
- Screw terminals mm 70 x 140 x 196 120 x 172 x 217 145 x 210 x 251 160 x 214 x 271
- Spring-loaded terminals mm 70 x 140 x 200 --
• Basic unit with mounted function
module or solid-state time-delayed
auxiliary switch
- Screw/spring-loaded terminals mm 70 x 140 x 226 --
Permissible mounting position
NSB0_00649a
NSB0_00478c
360° 22,5° 22,5° 22,5° 22,5°
The contactors are designed for operation on a vertical 90° 90°
mounting surface.
NSB0_00477a
Closed VA 25/18 --
P.f. 0.35/0.41 --
• AC operation, 50/60 Hz, Closing VA 326/326 --
for USA/Canada P.f. 0.62/0.55 --
Closed VA 22/22 --
P.f. 0.38/0.4 --
• AC/DC operation Closing for VA -- 163 300 280 590 530 830 750
AC operation
P.f. -- 0.9 0.8 0.9 0.8 0.9 0.8
Closed for VA -- 3.1 5.8 4.8 6.7 8.5 9.2 9
AC operation
P.f. -- 0.8 0.6 0.9 0.4 0.9 0.4
Closing for W -- 76 360 320 650 580 920 800
DC operation
Closed for W -- 1.8 5.2 2.8 7.4 3.4 10 3.6
DC operation
Type of PLC control input according to IEC 60947-1
• Solid-state operating mechanism 3RT14..-.N/-.P -- Type 2
3RT14..-.S -- Type 1
• Rated voltage V DC -- 24
• Operating range V DC -- 17 ... 30
• Power consumption mA -- 30
• Recovery time after mains failure, typical s -- 2
(applicable only for fail-safe version 3RT14..-.S)
• Finely stranded without end sleeve 16 ... 70 16 ... 120 70 ... 240
4
• Stranded mm2 16 ... 70 16 ... 120 95 ... 300
• AWG cables, solid or stranded AWG 6 ... 2/0 6 ... 250 kcmil 3/0 ... 600 kcmil
• Ribbon cable conductors mm Min. 3 x 9 x 0.8, Min. 3 x 9 x 0.8, Min. 6 x 9 x 0.8,
(Number x Width x Thickness) max. 6 x 15.5 x 0.8 max. 10 x 15.5 x 0.8 max. 20 x 24 x 0.5
Rear clamping point connected
• Finely stranded with end sleeve (DIN 46228) mm2 16 ... 70 16 ... 120 120 ... 185
NSB0_00480
• Finely stranded without end sleeve mm2 16 ... 70 16 ... 120 120 ... 185
• Stranded mm2 16 ... 70 16 ... 120 120 ... 240
• AWG cables, solid or stranded AWG 6 ... 2/0 6 ... 250 kcmil 250 ... 500 kcmil
• Ribbon cable conductors mm Min. 3 x 9 x 0.8, Min. 3 x 9 x 0.8, Min. 6 x 9 x 0.8,
(Number x Width x Thickness) max. 6 x 15.5 x 0.8 max. 10 x 15.5 x 0.8 max. 20 x 24 x 0.5
Both clamping points connected
(minimum cross-section 16 mm²)
• Finely stranded with end sleeve (DIN 46228) mm2 Max. 1 x 50, 1 x 70 Max. 1 x 95, 1 x 120 Min. 2 x 50, max. 2 x 185
• Finely stranded without end sleeve mm2 Max. 1 x 50, 1 x 70 Max. 1 x 95, 1 x 120 Min. 2 x 50, max. 2 x 185
NSB0_00481
• Stranded mm2 Max. 1 x 50, 1 x 70 Max. 1 x 95, 1 x 120 Min. 2 x 70, max. 2 x 240
• AWG cables, solid or stranded AWG Max. 2 x 1/0 Max. 2 x 3/0 Min. 2 x 2/0,
max. 2 x 500 kcmil
• Ribbon cable conductors mm Max. 2 x (6 x 15.5 x 0.8) Max. 2 x (10 x 15.5 x 0.8) Max. 2 x (20 x 24 x 0.5)
(Number x Width x Thickness)
Busbar connections
• Connecting bar (max. width) mm 17 25
- Bore diameter mm 9 11
1) 2)
Cable lug connection
• Finely stranded with cable lug mm2 16 ... 95 50 ... 240
• Stranded with cable lug mm2 25 ... 120 70 ... 240
• AWG cables, solid or stranded AWG 4 ... 250 kcmil 2/0 ... 500 kcmil
• Terminal screws M8 x 25 (A/F 13) M10 x 30 (A/F 17)
- Tightening torque Nm 10 ... 14 14 ... 24
lb.in 90 ... 124 124 ... 210
Auxiliary conductors
(1 or 2 conductors can be connected)
• Solid mm2 2 x (0.5 ... 1.5)3), 2 x (0.75 ... 2.5)3) according to IEC 60947;
max. 2 x (0.75 ... 4)3)
• Finely stranded with end sleeve (DIN 46228) mm2 2 x (0.5 ... 1.5)3); 2 x (0.75 ... 2.5)3)
• AWG cables, solid or stranded AWG 2 x (18 ... 14)
• Terminal screws M3 (Pozidriv size 2)
- Tightening torque Nm 0.8 ... 1.2
lb.in 7 ... 10.3
Auxiliary conductors4) Spring-loaded terminals
(1 or 2 conductors can be connected)
• Operating devices 3.0 x 0.5; 3.5 x 0.5
• Solid mm2 2 x (0.25 ... 2.5)
• Finely stranded with end sleeve (DIN 46228) mm2 2 x (0.25 ... 1.5)
• Finely stranded without end sleeve mm2 2 x (0.25 ... 2.5)
• AWG cables, solid or stranded AWG 2 x (24 ... 14)
1) 3RT1456: When connecting cable lugs according to DIN 46235, use the 3) If two different conductor cross-sections are connected to one clamping
3RT1956-4EA1 terminal cover for conductor cross-sections from 95 mm2 point, both cross-sections must lie in one of the ranges specified.
to maintain the phase clearance, see page 3/112. 4)
Max. external diameter of the conductor insulation: 3.6 mm.
2)
3RT1466, 3RT1467 and 3RT1476: When connecting cable lugs according On spring-loaded terminals with conductor cross-sections 1 mm2
to DIN 46234 for conductor cross-sections larger than 240 mm2 and an insulation stop is recommended, see page 3/115.
according to DIN 46235 for conductor cross-sections larger than 185 mm2,
the 3RT1966-4EA1 terminal cover is required to maintain the phase
clearance, see page 3/112.
D
W
4
Closed apparent power of the solenoid coil for AC
• At 50 Hz VA 18 23 18 23 20 33
• At 60 Hz VA 18 23 18 23 20 33
Main circuit
Operational current at AC-1
• Up to 690 V
- At an ambient temperature of 40 °C A 900 1 050 1 260 1 700 2 100 2 650
- At an ambient temperature of 55 °C A 900 1 050 1 260 1 700 2 100 2 650
• Up to 1000 V
- At an ambient temperature of 40 °C A 900 1 050 1 260 1 700 2 100 2 650
- At an ambient temperature of 55 °C A 900 1 050 1 260 1 700 2 100 2 650
Type of electrical connection for the main circuit Busbar connections
Minimum cross-section in the main circuit for mm2 600 800 1 000 1 500 2 000 3 000
max. AC-1 rated value
3RT244.-1...0
Size Rated data Auxiliary contacts Rated control supply voltage Us Screw terminals PU PS* PG
AC-1, tu: (UNIT,
SET, M)
40 °C 60 °C
Operational Ident. No. Version 50 Hz AC 50 Hz AC or DC
current Ie Article No. Price
up to per PU
690 V 690 V
A A NO NC V V
For screw fixing and snap-on mounting on TH 35-15 and TH 75-15 DIN rails
AC operation
S3 140 130 11 1 1 24 -- 3RT2446-1AB00 1 1 unit 41B
110 -- 3RT2446-1AF00 1 1 unit 41B
230 -- 3RT2446-1AP00 1 1 unit 41B
160 140 11 1 1 24 -- 3RT2448-1AB00 1 1 unit 41B
110 -- 3RT2448-1AF00 1 1 unit 41B
230 -- 3RT2448-1AP00 1 1 unit 41B
AC/DC operation
With integrated coil circuit (varistor integrated in electronics at the factory)
S3 140 130 11 1 1 -- 20 ... 33 3RT2446-1NB30 1 1 unit 41B
-- 83 ... 155 3RT2446-1NF30 1 1 unit 41B
-- 175 ... 280 3RT2446-1NP30 1 1 unit 41B
160 140 11 1 1 -- 20 ... 33 3RT2448-1NB30 1 1 unit 41B
-- 83 ... 155 3RT2448-1NF30 1 1 unit 41B
-- 175 ... 280 3RT2448-1NP30 1 1 unit 41B
4
3RT1456-6A.36 3RT1466-6A.36 3RT1476-6A.36 3RT1476-6N.36 3RT1476-6P.35
4
3RT1481-6A.36, 3RT1482-6A.36 3RT1483-6AP36 3RT1485-6AP36, 3RT1486-6AP36 3RT1487-6AP36
Rated data according to Auxiliary Rated control supply voltage Us Busbar PU PS* PG
IEC 60947-4-1 contacts, lateral connections (UNIT,
AC-1, tu: 40 °C Version 50/60 Hz AC DC SET, M)
Operational current Ie Article No. Price
up to per PU
1 000 V
A NO NC V V
Solid-state operating mechanism
With integrated coil circuit
900 2 2 100 ... 127 100 ... 110 3RT1481-6AF36 1 1 unit 41B
200 ... 240 200 ... 220 3RT1481-6AP36 1 1 unit 41B
1 050 2 2 100 ... 127 100 ... 110 3RT1482-6AF36 1 1 unit 41B
200 ... 240 200 ... 220 3RT1482-6AP36 1 1 unit 41B
1 260 2 2 100 ... 240 100 ... 220 3RT1483-6AP36 1 1 unit 41B
1 700 2 2 100 ... 240 100 ... 220 3RT1485-6AP36 1 1 unit 41B
2 100 2 2 100 ... 240 100 ... 220 3RT1486-6AP36 1 1 unit 41B
2 650 2 2 100 ... 240 100 ... 220 3RT1487-6AP36 1 1 unit 41B
Accessories, see next table; spare parts, see page 4/19.
■ Accessories
Overview graphics for 3RT148 contactors with mountable
accessories, see page 4/10. More information
Manuals, see
https://support.industry.siemens.com/cs/ww/en/ps/24229/man
62 54 72 84
3RH1981-1JA11
■ Spare parts
For Auxiliary contacts Rated control supply Article No. Price PU PS* PG
contactors voltage Us per PU (UNIT,
Version 50/60 Hz AC DC SET, M)
22 14 32 44
3RH1981-1DA11
Phase barriers
(1 set = 4 units)
3RT1481 -- -- -- -- -- -- 3RT1983-4AA1 1 1 unit 41B
...
3RT1483
3RT1983-4AA1
3RT1485 -- -- -- -- -- -- 3RT1987-4AA1 1 1 unit 41B
...
3RT1487
3RT1987-4AA1
Withdrawable coils ·AC/DC operation
3RT1481, -- -- -- -- 100 ... 127 100 ... 110 3RT1982-5AF31 1 1 unit 41B
3RT1482 -- -- -- -- 200 ... 240 200 ... 220 3RT1982-5AP31 1 1 unit 41B
3RT1483 -- -- -- -- 100 ... 240 100 ... 220 3RT1983-5AP31 1 1 unit 41B
3RT1982-5A.31,
3RT1983-5AP31
3RT1485 -- -- -- -- 100 ... 240 100 ... 220 3RT1987-5AP31 1 1 unit 41B
...
3RT1487
3RT1987-5AP31
■ Overview
Protection against overvoltage at the control supply voltage
connection
3RT23 contactors supplied without a coil circuit can be
retrofitted with RC elements, varistors, diodes or diode
assemblies (combination of diode and Zener diode for short
break times) for damping switching overvoltages in the coil and
can be ordered separately as accessories, see page 3/97
onwards.
3RT13 contactors are already equipped with coil damping
(varistor).
Note:
4
The break times of the contactor, the opening delay times of the
NO contacts and the closing delay times of the NC contacts
increase with damping.
For more information about influencing the time response using
damping, see Equipment Manual.
3RT231 to 3RT234 and 3RT135 to 3RT137 contactors, Connection methods
with screw terminals
Main circuit
Standards • 3RT231 and 3RT232 contactors:
IEC 60947-1, IEC 60947-4-1, IEC60947-5-1 (auxiliary switches) Screw terminals or spring-loaded terminals;
spring-loaded terminals with convenient plug-in design for
Protecting connections against short circuit, overload and device connectors
overvoltage
• 3RT233 and 3RT234 contactors:
All connections must generally be protected against overload Screw terminals with box terminal;
and short circuits using suitable measures. Different constraints direct connection to the connecting bar possible with cable
must be considered depending on the type of connection: lugs for 3RT234 when the box terminal is removed.
Short-circuit and overload protection of main connections • 3RT135 to 3RT137 contactors:
Screw terminals with connecting bars that the cables can be
For information on the protection of a free-standing contactor, connected to using either cable lugs or flexible or rigid
see the technical product data sheet. busbars.
For more information on complete units such as contactors with • 3RT136 and 3RT137 contactors:
overload relays or contactors with motor starter protectors as the These can be fitted with bus connectors offset, see page 4/35.
motor feeder, see Configuration Manual for load feeders.
Auxiliary and control circuits
Short-circuit and overload protection of auxiliary connections
Screw terminals
For information on the protection of auxiliary contacts, see the
technical product data sheet. Electromagnetic compatibility
Short-circuit and overload protection of control supply voltage The contactors fulfill the requirements for environment category A.
connections or supply voltage connections Note:
First of all, the relevant standards and regulations for configuring When the contactors are used in an environment with frequency
control panels and the parts and components installed in them converters, the configuration notes must be observed, see
must be taken into account, for example for cable dimensioning. Equipment Manual.
One possible protection for these circuits could be the selection
of a suitable power supply, i.e. one with a current-limiting
function. In the selection of the source and the connecting cable,
the load characteristics of the contactor must be considered
(short-time inrush current peaks for solid-state operating
mechanisms, switch-on power, holding power).
If there are further switching elements in the circuit, such as the
auxiliary contact system of an overload relay that operates the
contactor, the short-circuit protection necessary for this must
also be considered.
For further recommendations, e.g. the use of miniature circuit
breakers or circuit breakers for equipment in control circuits, see
Control panel tip – Selecting and dimensioning suitable power
supplies quickly and reliably.
4 5
4
1
1
2
IC01_00577a
5
4
5
1 4-pole 3RT13 contactors, sizes S6 to S12 4 3RT19.6-4D bus connectors offsets, can be mounted on the top or
(scope of supply: The contactors are supplied with two laterally bottom (providing no terminal cover 55 is mounted)
mounted auxiliary switch blocks)
5 3RT19.6-4EB10 terminal covers, can be mounted on the top or bottom
2 3RH1951-1SA11 second auxiliary switch block, can be laterally (providing no bus connectors offset 44 is mounted)
mounted on the left or right
3 3RA1954-3A mechanical interlock for configuring contactor
assemblies:
Two 3RT13 contactors of the same size (S6, S10 and S12) can be
interlocked with each other. The laterally mounted auxiliary switches
of the contactors must be removed beforehand.
The mechanical interlock cannot be used in conjunction with the bus Same accessories for sizes S6 to S12
connectors offset (4)
4 . Different accessories depending on size
■ Application
The 3RT.3 contactors can be used for the following applications: We additionally offer special versions of the 3RT23 contactors for
• 4-pole switching of weak or non-inductive loads (AC-1) switching motor-driven loads (AC-3).
• Disconnecting loads or power generation plants from the grid
• For system transfers
■ Technical specifications
More information
Technical specifications, see Manuals, see
4
https://support.industry.siemens.com/cs/ww/en/ps/16165/td https://support.industry.siemens.com/cs/ww/en/ps/16165/man
FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/16165/faq
Type 3RT2316, 3RT2317 3RT2325 to 3RT2327 3RT2336, 3RT2337 3RT2344, 3RT2346, 3RT2348
Size S00 S0 S2 S3
General data
Dimensions (W x H x D) (The values in brackets
AC or DC operation apply for DC
operation)
H
• Basic units
- Screw terminals mm 45 x 58 x 73 60 x 85 x 97 (107) 75 x 114 x 130 96 x 140 x 152
D
NSB0_00477a
Special version required
Mechanical endurance Oper- 30 million 10 million
ating
cycles
Electrical endurance at Ie/AC-1 Oper- Approx. 0.5 million
ating
cycles
Rated insulation voltage Ui V 690
(pollution degree 3)
Protective separation V 400 690
between the coil and the main contacts
according to IEC 60947-1, Annex N
Permissible ambient temperature
• During operation °C -25 ... +60
• During storage °C -55 ... +80
4
• Version of the fuse link required for short-circuit Fuse gG: 10 A (690 V, 1 kA)
protection of the auxiliary switch
• Miniature circuit breaker version required for 6 A (230 V, 400 A, C characteristic)
short-circuit protection of the auxiliary switch
Type 3RT2316 3RT2317 3RT2325 3RT2326, 3RT2327 3RT2336, 3RT2337 3RT2344, 3RT2346, 3RT2348
Size S00 S0 S2 S3
Control
Solenoid coil operating range
• AC operation At 50 Hz 0.8 ... 1.1 x Us
At 60 Hz 0.85 ... 1.1 x Us 0.8 ... 1.1 x Us
• DC operation At 50 °C 0.8 ... 1.1 x Us --
At 60 °C 0.85 ... 1.1 x Us --
• AC/DC operation -- 0.8 ... 1.1 x Us
Power consumption of the solenoid coils
(for cold coil and 1.0 x Us)
• AC operation, 50 Hz, standard version
4
Type 3RT2316 3RT2317 3RT2325 3RT2326 3RT2327 3RT2336 3RT2337 3RT2344 3RT2346 3RT2348
Size S00 S0 S2 S3
Rated data of the main contacts
Load rating with AC
Utilization category AC-1
• Rated operational At 40 °C, up to 690 V A 18 22 35 40 50 60 110 110 140 160
currents Ie (110)1)
At 60 °C, up to 690 V A 16 20 30 35 42 55 95 100 130 140
(100)1)
• Rated power for AC At 230 V kW 6 7.5 11 13 16 21 36 38 49 53
loads 400 V kW 10.5 13 20 23 28 36 63 72 92 105
P.f. = 0.95
(at 60 °C)
• Minimum cross- mm2 2.5 4 10 16 35 50 (35)1) 70
section in the main
circuit at maximum
AC-1 rated value
Power loss per main conducting path
• At Ie/AC-1 At 40 °C W 1.1 1.6 1.8 2.4 3 3.2 9.7 7.3 11.8 15.4
• At Ie/AC-3 At 400 V W -- -- -- (2.6)1) -- (4.3)1) -- -- (6.8)1) --
1) The values in brackets apply for 3RT23.6-1...0-4AA0 versions.
4
maximum
Insulation voltage at pollution degree 3
• Of the main circuit V 1 000
• Of the auxiliary circuit V 690
Impulse withstand voltage
• Of the main circuit kV 8
• Of the auxiliary circuit kV 6
Product function, mirror contact according to Yes
IEC 60947-4-1
Ambient temperature
• During operation °C -40 ... +60
• During storage °C -40 ... +70
Short-circuit protection
Version of the fuse link required
• For short-circuit protection of the main circuit for gG: 250 A gG: 355 A gG: 400 A gG: 630 A
type of coordination 2 (500 V, 100 kA) (500 V, 100 kA) (500 V, 100 kA) (500 V, 100 kA)
• For short-circuit protection of the auxiliary switch gG: 10 A (690 V, 1 kA)
• At 60 Hz VA 475 340 385 420 475 340 385 420 475 340 385 420
Solenoid coil closed for DC W 3.5 2.5 4.5 4.7 3.5 2.5 4.5 4.7 3.5 2.5 4.5 4.7
Closed apparent power of the solenoid coil
for AC
• At 50 Hz VA 8.5 17 17.5 21 8.5 17 17.5 21 8.5 17 17.5 21
• At 60 Hz VA 8.5 17 17.5 21 8.5 17 17.5 21 8.5 17 17.5 21
Main circuit
Operational current at AC-1
• Up to 690 V
- At an ambient temperature of 40 °C A 400 500 525
- At an ambient temperature of 60 °C A 350 400 425
• Up to 1000 V
- At an ambient temperature of 40 °C A 350 375 400
- At an ambient temperature of 60 °C A 300 325 350
4
3RT231.-1A.00 3RT231.-2A.00 3RT232.-1A.00 3RT232.-2A.00 3RT233.-1A.00 3RT234.-1A.00
Rated data AC-1, Auxiliary contacts Rated control supply Screw terminals Spring-loaded terminals
tu: 40/60 °C voltage Us
Operational current Ie Ident. No. Version 50/60 Hz AC 50 Hz AC
up to Article No. Price Article No. Price
690 V per PU per PU
A NO NC V V
For screw fixing and snap-on mounting on TH 35 DIN rail
Size S00
18/16 -- -- -- 24 -- 3RT2316-1AB00 3RT2316-2AB00
110 -- 3RT2316-1AF00 3RT2316-2AF00
230 3RT2316-1AP00 3RT2316-2AP00
22/20 -- -- -- 24 -- 3RT2317-1AB00 3RT2317-2AB00
110 -- 3RT2317-1AF00 3RT2317-2AF00
230 -- 3RT2317-1AP00 3RT2317-2AP00
Size S0
35/301) 11 1 1 -- 24 3RT2325-1AB00 3RT2325-2AB00
-- 110 3RT2325-1AF00 3RT2325-2AF00
-- 230 3RT2325-1AP00 3RT2325-2AP00
40/351) 11 1 1 -- 24 3RT2326-1AB00 3RT2326-2AB00
-- 110 3RT2326-1AF00 3RT2326-2AF00
-- 230 3RT2326-1AP00 3RT2326-2AP00
50/421) 11 1 1 -- 24 3RT2327-1AB00 3RT2327-2AB00
-- 110 3RT2327-1AF00 3RT2327-2AF00
-- 230 3RT2327-1AP00 3RT2327-2AP00
Size S2
60/55 11 1 1 -- 24 3RT2336-1AB00 --
-- 110 3RT2336-1AF00 --
-- 230 3RT2336-1AP00 --
110/95 11 1 1 -- 24 3RT2337-1AB00 --
-- 110 3RT2337-1AF00 --
-- 230 3RT2337-1AP00 --
For screw fixing and snap-on mounting on TH 35-15 and TH 75-15
DIN rails
Size S3
110/100 11 1 1 -- 24 3RT2344-1AB00 --
-- 110 3RT2344-1AF00 --
-- 230 3RT2344-1AP00 --
140/130 11 1 1 -- 24 3RT2346-1AB00 --
-- 110 3RT2346-1AF00 --
-- 230 3RT2346-1AP00 --
160/140 11 1 1 -- 24 3RT2348-1AB00 --
-- 110 3RT2348-1AF00 --
-- 230 3RT2348-1AP00 --
1) Required conductor cross-section 10 mm2. Other voltages according to page 4/52 on request.
Accessories and spare parts, see page 3/69 onwards.
Rated data Auxiliary contacts Rated control Screw terminals Spring-loaded terminals
AC-3/AC-3e, AC-1, supply
tu: up to 60 °C tu: 40/60 °C voltage Us
Operational Operational Ident. No. Version 50 Hz AC
current Ie current Ie Article No. Price Article No. Price
up to up to per PU per PU
400 V 690 V
A A NO NC V
For screw fixing and snap-on mounting on TH 35 DIN rail
Size S0
32 40/35 11 1 1 230 3RT2326-1AP00-4AA0 --
Size S2
50 60/55 11 1 1 230 3RT2336-1AP00-4AA0 --
4
3RT231.-1B.40 3RT231.-2B.40 3RT232.-1B.40 3RT232.-2B.40
Rated data Auxiliary contacts Rated control supply Screw terminals Spring-loaded terminals
AC-1, tu: 40/60 °C voltage Us
Operational current Ie Ident. No. Version DC
up to Article No. Price Article No. Price
690 V per PU per PU
A NO NC V
For screw fixing and snap-on mounting on TH 35 DIN rail
Size S00
18/16 -- -- -- 24 3RT2316-1BB40 3RT2316-2BB40
220 3RT2316-1BM40 3RT2316-2BM40
22/20 -- -- -- 24 3RT2317-1BB40 3RT2317-2BB40
220 3RT2317-1BM40 3RT2317-2BM40
Size S0
35/301) 11 1 1 24 3RT2325-1BB40 3RT2325-2BB40
220 3RT2325-1BM40 3RT2325-2BM40
40/351) 11 1 1 24 3RT2326-1BB40 3RT2326-2BB40
220 3RT2326-1BM40 3RT2326-2BM40
50/421) 11 1 1 24 3RT2327-1BB40 3RT2327-2BB40
220 3RT2327-1BM40 3RT2327-2BM40
1)
Required conductor cross-section 10 mm2. Other voltages according to page 4/52 on request.
Accessories and spare parts, see page 3/69 onwards.
3RT233.-1N.30 3RT234.-1N.30
Rated data Auxiliary contacts Rated control supply Screw terminals Spring-loaded terminals
AC-1, tu: 40/60 °C voltage Us
Operational current Ie Ident. No. Version 50/60 Hz AC or DC
up to Article No. Price Article No. Price
690 V per PU per PU
A NO NC V
For screw fixing and snap-on mounting on TH 35 DIN rail
Size S2
With integrated coil circuit
(varistor integrated in electronics at the factory)
60/55 11 1 1 20 ... 33 3RT2336-1NB30 --
175 ... 280 3RT2336-1NP30 --
110/95 11 1 1 20 ... 33 3RT2337-1NB30 --
175 ... 280 3RT2337-1NP30 --
For screw fixing and snap-on mounting on TH 35-15 and
TH 75-15 DIN rails
Size S3
With integrated coil circuit
(varistor integrated in electronics at the factory)
110/100 11 1 1 20 ... 33 3RT2344-1NB30 --
175 ... 280 3RT2344-1NP30 --
140/130 11 1 1 20 ... 33 3RT2346-1NB30 --
175 ... 280 3RT2346-1NP30 --
160/140 11 1 1 20 ... 33 3RT2348-1NB30 --
175 ... 280 3RT2348-1NP30 --
4
3RT2336-1NB30-4AA0 3RT2346-1NB30-4AA0
Rated data Auxiliary contacts Rated control supply Screw terminals Spring-loaded terminals
AC-3/AC-3e, AC-1, Ident. No. Version voltage Us
tu: up to tu: 40/60 °C 50/60 Hz AC or DC
60 °C
Operational Operational Article No. Price Article No. Price
current Ie current Ie per PU per PU
up to up to
400 V 690 V
A A NO NC V
For screw fixing and snap-on mounting on TH 35 DIN rail
Size S2
With integrated coil circuit
(varistor integrated in electronics at the factory)
50 60/55 11 1 1 20 ... 33 3RT2336-1NB30-4AA0 --
A NO NC V V
Solid-state operating mechanism
With integrated coil circuit (varistor integrated in electronics at the factory)
S6 200 2 2 24 ... 60 20 ... 60 3RT1355-6AE36 1 1 unit 41B
48 ... 130 48 ... 130 3RT1355-6AF36 1 1 unit 41B
100 ... 250 100 ... 250 3RT1355-6AP36 1 1 unit 41B
250 ... 500 250 ... 500 3RT1355-6AR36 1 1 unit 41B
S10 275 2 2 24 ... 60 20 ... 60 3RT1363-6AE36 1 1 unit 41B
48 ... 130 48 ... 130 3RT1363-6AF36 1 1 unit 41B
100 ... 250 100 ... 250 3RT1363-6AP36 1 1 unit 41B
250 ... 500 250 ... 500 3RT1363-6AR36 1 1 unit 41B
350 2 2 24 ... 60 20 ... 60 3RT1364-6AE36 1 1 unit 41B
48 ... 130 48 ... 130 3RT1364-6AF36 1 1 unit 41B
100 ... 250 100 ... 250 3RT1364-6AP36 1 1 unit 41B
250 ... 500 250 ... 500 3RT1364-6AR36 1 1 unit 41B
S12 400 2 2 24 ... 60 20 ... 60 3RT1373-6AE36 1 1 unit 41B
48 ... 130 48 ... 130 3RT1373-6AF36 1 1 unit 41B
100 ... 250 100 ... 250 3RT1373-6AP36 1 1 unit 41B
250 ... 500 250 ... 500 3RT1373-6AR36 1 1 unit 41B
500 2 2 24 ... 60 20 ... 60 3RT1374-6AE36 1 1 unit 41B
48 ... 130 48 ... 130 3RT1374-6AF36 1 1 unit 41B
100 ... 250 100 ... 250 3RT1374-6AP36 1 1 unit 41B
250 ... 500 250 ... 500 3RT1374-6AR36 1 1 unit 41B
525 2 2 24 ... 60 20 ... 60 3RT1375-6AE36 1 1 unit 41B
48 ... 130 48 ... 130 3RT1375-6AF36 1 1 unit 41B
100 ... 250 100 ... 250 3RT1375-6AP36 1 1 unit 41B
250 ... 500 250 ... 500 3RT1375-6AR36 1 1 unit 41B
Depending on the operational current, bus connectors offset Accessories and spare parts, see page 4/35 onwards.
must be used for sizes S10 and S12, see page 4/35:
• 3RT136: For more than 275 A, the 3RT1966-4D bus
connectors offset must be used.
• 3RT137: For more than 450 A, the 3RT1976-4D bus
connectors offset must be used.
■ Accessories
Overview graphic for 3RT135 to 3RT137 contactors with
mountable accessories, see page 4/23. More information
Equipment Manual, see
https://support.industry.siemens.com/cs/ww/en/view/60306557
4
Second auxiliary switch (1 NO + 1 NC)
Lateral mounting on the right and/or the left, 2-pole Screw terminals
54 62 72 84
3RH1951-1SA11
Terminal covers
Two units required per contactor (1 set = 2 units)
Either bus connectors offset or terminal covers can be used.
3RT135 -- -- -- -- 3RT1956-4EB10 1 1 unit 41B
3RT136 -- -- -- -- 3RT1966-4EB10 1 1 unit 41B
3RT1956-4EB10
3RT137 -- -- -- -- 3RT1976-4EB10 1 1 unit 41B
3RT1966-4EB10
3RT1976-4EB10
Bus connectors offset
(Two units required per contactor)
Either terminal covers or bus connectors offset can be used.
3RT136 -- -- -- -- 3RT1966-4D 1 1 unit 41B
3RT1966-4D 3RT137 -- -- -- -- 3RT1976-4D 1 1 unit 41B
3RT1976-4D
Mechanical interlocks for contactor assemblies
Enables two 3RT13 contactors of the same size (S6, S10 and S12)
to be interlocked with each other. The laterally mounted auxiliary
switches of the contactor must be removed beforehand.
The mechanical interlock cannot be used in conjunction with the
bus connectors offset.
3RA1954-3A 3RT135 ... -- -- -- -- 3RA1954-3A 1 1 unit 41B
3RT137
■ Spare parts
For contactors Auxiliary contacts Screw terminals PU PS* PG
Version (UNIT,
SET, M)
Article No. Price
per PU
14 22 32 44
3RH1951-1TA11
■ Overview
Standards Protection against overvoltage at the control supply voltage
connection
IEC 60947-1, IEC 60947-4-1, IEC 60947-5-1 (auxiliary switches)
3RT25 contactors supplied without a coil circuit can be
Protecting connections against short circuit, overload and retrofitted with RC elements, varistors, diodes or diode
overvoltage assemblies (combination of diode and Zener diode for short
All connections must generally be protected against overload break times) for damping switching overvoltages in the coil and
and short circuits using suitable measures. Different constraints can be ordered separately as accessories, see page 3/97
must be considered depending on the type of connection: onwards.
Short-circuit and overload protection of main connections Note:
For information on the protection of a free-standing contactor, The break times of the contactor, the opening delay times of the
4
see the technical product data sheet. NO contacts and the closing delay times of the NC contacts
increase with damping.
For more information on complete units such as contactors with
overload relays or contactors with motor starter protectors as the For more information about influencing the time response using
motor feeder, see Configuration Manual for load feeders. damping, see Equipment Manual.
Short-circuit and overload protection of auxiliary connections Replacing solenoid coils or spare contacts
For information on the protection of auxiliary contacts, see the Solenoid coil or contact replacement is possible.
technical product data sheet.
Fitting auxiliary contacts and mounting additional auxiliary
Short-circuit and overload protection of control supply voltage switches
connections or supply voltage connections
Features in the delivery state
First of all, the relevant standards and regulations for configuring
control panels and the parts and components installed in them The 3RT252 to 3RT254 basic units contain two integrated
must be taken into account, for example for cable dimensioning. auxiliary contacts (1 NO + 1 NC).
One possible protection for these circuits could be the selection Expansion possibilities
of a suitable power supply, i.e. one with a current-limiting All basic units can be expanded using auxiliary switches;
function. In the selection of the source and the connecting cable, the permissible configuration must be observed.
the load characteristics of the contactor must be considered
(short-time inrush current peaks for solid-state operating For detailed information about the fitting of auxiliary switches for
mechanisms, switch-on power, holding power). 3RT25 contactors, see pages 3/81 to 3/86.
If there are further switching elements in the circuit, such as the Accessories
auxiliary contact system of an overload relay that operates the The accessories for the 3-pole SIRIUS 3RT2 contactors can also
contactor, the short-circuit protection necessary for this must be used for the 4-pole versions, see page 3/69 onwards.
also be considered.
Use of 3RT contactors with IE3 and IE4 motors
For further recommendations, e.g. the use of miniature circuit
breakers or circuit breakers for equipment in control circuits, see Note:
Control panel tip – Selecting and dimensioning suitable power
supplies quickly and reliably. For the use of 3RT25 contactors in conjunction with highly
efficient IE3 and IE4 motors, please observe the information on
dimensioning and configuring, see Application Manual.
More information, see page 1/8.
■ Application
The contactors are suitable: Note:
• For changing the polarity of hoisting gear motors Single device for pole reversal; not suitable for reversing operation.
• For switching two separate loads 3RT25 contactors are not suitable for switching a load between two
current sources.
■ Technical specifications
More information
Technical specifications, see Manuals, see
https://support.industry.siemens.com/cs/ww/en/ps/16169/td https://support.industry.siemens.com/cs/ww/en/ps/16169/man
FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/16169/faq
4
Permissible mounting position
The contactors are designed for operation
NSB0_00478c
360° 22,5° 22,5°
on a vertical mounting surface.
NSB0_00477a
Type 3RT2516- 3RT2517-1A, 3RT2516-1B, 3RT2526- 3RT2526- 3RT253.- 3RT253.- 3RT254.- 3RT254.-
1A 3RT2518-1A 3RT2517-1B, 1A 1B 1A 1N 1A 1N
3RT2518-1B
Size S00 S0 S2 S3
Control
Type of operating mechanism AC DC AC DC AC AC/DC AC AC/DC
Solenoid coil operating range
• AC operation At 50 Hz 0.8 ... -- 0.8 ... -- 0.8 ... -- 0.8 ... --
1.1 x Us 1.1 x Us 1.1 x Us 1.1 x Us
At 60 Hz 0.85 ... -- 0.8 ... -- 0.8 ... -- 0.8 ... --
1.1 x Us 1.1 x Us 1.1 x Us 1.1 x Us
• DC operation Up to 50 °C -- 0.8 ... -- 0.8 ... --
1.1 x Us 1.1 x Us
4
4
3RT251.-1A.00 3RT251.-2A.00 3RT252.-1A.00 3RT252.-2A.00 3RT253.-1A.00 3RT254.-1A.00
Rated data Auxiliary Rated control supply Screw terminals Spring-loaded terminals
contacts voltage Us
AC-3, AC-1, Ident. Version 50/60 Hz AC 50 Hz AC
tu: up to 60 °C tu: 40/60 °C No.
Opera- Ratings of Operational Article No. Price Article No. Price
tional three-phase current Ie per PU per PU
current Ie motors up to
up to at 50 Hz and
400 V 400 V 690 V
A kW A NO NC V V
For screw fixing and snap-on mounting on TH 35 DIN rail
Size S00
9 4 18/16 -- -- -- 24 -- 3RT2516-1AB00 3RT2516-2AB00
110 -- 3RT2516-1AF00 3RT2516-2AF00
230 -- 3RT2516-1AP00 3RT2516-2AP00
12/91) 5.5/41) 22/20 -- -- -- 24 -- 3RT2517-1AB00 3RT2517-2AB00
110 -- 3RT2517-1AF00 3RT2517-2AF00
230 -- 3RT2517-1AP00 3RT2517-2AP00
16/91) 7.5/41) 22/20 -- -- -- 24 -- 3RT2518-1AB00 3RT2518-2AB00
110 -- 3RT2518-1AF00 3RT2518-2AF00
230 -- 3RT2518-1AP00 3RT2518-2AP00
Size S0
25 11 40/35 11 1 1 -- 24 3RT2526-1AB00 3RT2526-2AB00
-- 110 3RT2526-1AF00 3RT2526-2AF00
-- 230 3RT2526-1AP00 3RT2526-2AP00
Size S2
35 18.5 60/55 11 1 1 -- 24 3RT2535-1AB00 --
-- 110 3RT2535-1AF00 --
-- 230 3RT2535-1AP00 --
41 22 70/60 11 1 1 -- 24 3RT2536-1AB00 --
-- 110 3RT2536-1AF00 --
-- 230 3RT2536-1AP00 --
For screw fixing and snap-on mounting on TH 35-15 and
TH 75-15 DIN rails
Size S3
65 30 100/90 11 1 1 -- 24 3RT2544-1AB00 --
-- 110 3RT2544-1AF00 --
-- 230 3RT2544-1AP00 --
80 37 125/105 11 1 1 -- 24 3RT2545-1AB00 --
-- 110 3RT2545-1AF00 --
-- 230 3RT2545-1AP00 --
1)
Values for NO contact/NC contact. The NC contact can switch no more Other voltages according to page 4/52 on request.
than 4 kW.
Accessories and spare parts, see page 3/69 onwards.
4
3RT253.-1N.30 3RT254.-1N.30
Rated data Auxiliary Rated control Screw terminals Spring-loaded terminals
contacts supply voltage Us
AC-3, AC-1, Ident. Version 50/60 Hz AC
tu: up to 60 °C tu: 40/60 °C No. or DC
Opera- Ratings of Operational Article No. Price Article No. Price
tional three-phase current Ie per PU per PU
current motors up to
Ie up to at 50 Hz and
400 V 400 V 690 V
A kW A NO NC V
For screw fixing and snap-on mounting on TH 35 DIN rail
Size S2
With integrated coil circuit (varistor integrated in electronics at the factory)
35 18.5 60/55 11 1 1 20 ... 33 3RT2535-1NB30 --
83 ... 155 3RT2535-1NF30 --
175 ... 280 3RT2535-1NP30 --
41 22 70/60 11 1 1 20 ... 33 3RT2536-1NB30 --
83 ... 155 3RT2536-1NF30 --
175 ... 280 3RT2536-1NP30 --
For screw fixing and snap-on mounting on TH 35-15 and
TH 75-15 DIN rails
Size S3
With integrated coil circuit (varistor integrated in electronics at the factory)
65 30 100/90 11 1 1 20 ... 33 3RT2544-1NB30 --
175 ... 280 3RT2544-1NP30 --
80 37 125/105 11 1 1 20 ... 33 3RT2545-1NB30 --
175 ... 280 3RT2545-1NP30 --
■ Overview
Standards Protection against overvoltage at the control supply voltage
connection
IEC 60947-1, IEC 60947-4-1, IEC 60947-5-1, IEC 60831-1,
IEC 61921 3RT26 contactors supplied without a coil circuit can be
retrofitted with RC elements, varistors, diodes or diode
Function assemblies (combination of diode and Zener diode for short
The 3RT26 contactors are special versions of the 3RT2, break times) for damping switching overvoltages in the coil and
designed for switching capacitive loads (AC-6b) up to 100 kvar can be ordered separately as accessories, see page 3/97
at 400 V. onwards.
Characteristic components of the 3RT26 contactors are the Note:
precharging resistors switched on via leading auxiliary contacts, The break times of the contactor, the opening delay times of the
which are closed before the main contacts. This limits the peak
4
■ Technical specifications
More information
Technical specifications, see Manuals, see
https://support.industry.siemens.com/cs/ww/en/ps/16171/td https://support.industry.siemens.com/cs/ww/en/ps/16171/man
Type 3RT26
Size S00 to S3
Contact endurance of the main contacts
The characteristic curves show the contact endurance of the contactors
when switching capacitive loads (AC-6b) depending on the reactive 10+6 IC01_00386d
power QN and the rated operational voltage. 8
4
(breaking of 1.35 times the rated operational current) and is intended for 4 3RT2617
a contact endurance of approximately 150 000 to 200 000 operating cycles.
3RT2625
2 3RT2626
3RT2627
10+5 3RT2628
3RT2636
3RT2637
3RT2645
3RT2646
10+4
100 2 4 6 8 101 2 4 6 8 102 2
Reactive power N
[kvar] at 400 V
W
• DC operation, mm 45 x 125 x 45 x 135 x 165 45 x 150 x 65 x 114 x 130 80 x 140 x 152
AC/DC operation 120 165
Permissible mounting position
NSB0_00478c
360° 22,5° 22,5°
The contactors are designed for operation on
a vertical mounting surface.
Mechanical endurance
Basic units with mounted auxiliary switch Operat- 3 million
ing
cycles
Electrical endurance kvar 12.5 16.7 20 25 33 50 75 100
For apparent power at 400 V Operat- 300 000 200 000 150 000 200 000 150 000 200 000 150 000
ing
cycles
Rated insulation voltage Ui V 690 1 0002)
(pollution degree 3)
Rated impulse withstand voltage Uimp kV 6 82)
Protective separation V 400 690
between the coil and the main contacts
according to IEC 60947-1, Annex N
Permissible ambient temperature
• During operation1) °C -25 ... +60
• During storage °C -55 ... +80
Short-circuit protection
Main circuit
Fuse links, operational class gG:
LV HRC, type 3NA; DIAZED, type 5SB;
NEOZED, type 5SE
according to IEC 60947-4-1
• Type of coordination "1" A 25 ... 40 32 ... 80 40 ... 80 50 ... 100 63 ... 100 100 ... 160 160 ... 200 200 ...
250
Auxiliary circuit
• With fuse links of operational class gG: A 10
DIAZED, type 5SB; NEOZED, type 5SE
With short-circuit current Ik = 1 kA
according to IEC 60947-5-1
• With miniature circuit breakers with A 10
C characteristic with short-circuit
current Ik = 400 A
1) A clearance of 10 mm is required for side-by-side mounting. 2) Only applies for main conducting paths, otherwise Ui = 690 V; Uimp = 6 kV.
4
• AC operation, 50 Hz, standard version
- Closing VA -- 77 190 296
- P.f. -- 0.82 0.72 0.61
- Closed VA -- 9.8 16 19
- P.f. -- 0.25 0.37 0.38
• AC operation, 50/60 Hz, standard version
- Closing VA 49 81/79 210/188 348/296
- P.f. 0.8 0.72/0.74 0.69/0.65 0.62/0.55
- Closed VA 7.8 10.5/8.5 17.2/16.5 25/18
- P.f. 0.25 0.25/0.28 0.36/0.39 0.35/0.41
• DC operation
- Closing W 4 5.9 --
- Closed W 4 5.9 --
Type 3RT2617 3RT2625 3RT2626 3RT2627 3RT2628 3RT2636 3RT2637 3RT2645 3RT2646
Size S00 S0 S2 S3
Auxiliary circuit
Auxiliary contacts (unassigned) 1 NO + 1 NO + 2 NC 1 NO + 1 NC, 2 NC
1 NC,
2 NC
Further auxiliary switches, -- No more than one lateral auxiliary switch can
laterally mountable be mounted.
Technical specifications including CSA and UL
rated data of the auxiliary contacts, see
"3RT20 contactors", page 3/25 onwards.
Rated data of the main contacts
Load rating with AC
4
4
• AWG cables, AWG 2 x (20 ... 16)1); 2 x (16 ... 12)1); 1 x (10 ... 4) 2 x (18 ... 2); 2 x (8 ... 3/0);
solid or stranded 2 x (18 ... 14)1); 2 x (14 ... 8)1) 1 x (18 ... 0) 1 x (8 ... 3/0)
2 x 12
• Terminal screw M3 M4 M8 M6 M8
(for Pozidriv size 2; (for Pozidriv size 2; (for Pozidriv size 2; (hexagon socket,
5 ... 6 mm) 5 ... 6 mm) 5 ... 6 mm) A/F 4)
• Tightening torque Nm 0.8 ... 1.2 2 ... 2.5 3 ... 4 3 ... 4.5 4.5 ... 6
lb.in 7 ... 10.3 18 ... 22 27 ... 36 27 ... 40 40 ... 53
Auxiliary conductors
(1 or 2 conductors can be
connected)
• Solid or stranded mm2 2 x (0.5 ... 1.5)1);
2 x (0.75 ... 2.5)1); max. 2 x 4
• Finely stranded with end sleeve mm2 2 x (0.5 ... 1.5)1);
(DIN 46228) 2 x (0.75 ... 2.5)1)
• AWG cables, AWG 2 x (20 ... 16)1);
solid or stranded 2 x (18 ... 14)1);
2 x 12
• Terminal screw M3
(for Pozidriv size 2;
5 ... 6 mm)
• Tightening torque Nm 0.8 ... 1.2
lb.in 7 ... 10.3
1)
If two different conductor cross-sections are connected to one clamping
point, both cross-sections must lie in one of the ranges specified.
4
3RT263.-1A.05 3RT264.-1A.05
Utilization category AC-6b Auxiliary Rated control supply Screw terminals PU PS* PG
Switching AC capacitors contacts, voltage Us (UNIT,
at an ambient temperature of 60 °C unassigned SET, M)
Version 50 Hz AC
Capacitor rating at Article No. Price
operational voltage 50/60 Hz per PU
at 230 V at 400 V at 500 V at 690 V
kvar kvar kvar kvar NO NC V
For screw fixing and snap-on mounting on TH 35 DIN rail
Size S2
29 50 63 86 1 1 24 3RT2636-1AB03 1 1 unit 41B
110 3RT2636-1AF03 1 1 unit 41B
230 3RT2636-1AP03 1 1 unit 41B
29 50 63 86 0 2 24 3RT2636-1AB05 1 1 unit 41B
110 3RT2636-1AF05 1 1 unit 41B
230 3RT2636-1AP05 1 1 unit 41B
43 75 94 129 1 1 24 3RT2637-1AB03 1 1 unit 41B
110 3RT2637-1AF03 1 1 unit 41B
230 3RT2637-1AP03 1 1 unit 41B
43 75 94 129 0 2 24 3RT2637-1AB05 1 1 unit 41B
110 3RT2637-1AF05 1 1 unit 41B
230 3RT2637-1AP05 1 1 unit 41B
For screw fixing and snap-on mounting on TH 35-15 and TH 75-15 DIN rails
Size S3
43 75 94 129 1 1 24 3RT2645-1AB03 1 1 unit 41B
110 3RT2645-1AF03 1 1 unit 41B
230 3RT2645-1AP03 1 1 unit 41B
43 75 94 129 0 2 24 3RT2645-1AB05 1 1 unit 41B
110 3RT2645-1AF05 1 1 unit 41B
230 3RT2645-1AP05 1 1 unit 41B
57 100 125 172 1 1 24 3RT2646-1AB03 1 1 unit 41B
110 3RT2646-1AF03 1 1 unit 41B
230 3RT2646-1AP03 1 1 unit 41B
57 100 125 172 0 2 24 3RT2646-1AB05 1 1 unit 41B
110 3RT2646-1AF05 1 1 unit 41B
230 3RT2646-1AP05 1 1 unit 41B
4
3RT262.-1N.35 3RT2628-1N.35 3RT263.-1N.35 3RT264.-1N.35
with infeed terminal
Utilization category AC-6b Auxiliary Rated control supply Screw terminals PU PS* PG
Switching AC capacitors contacts, voltage Us (UNIT,
at an ambient temperature of 60 °C unassigned SET, M)
Version 50/60 Hz AC or DC
Capacitor rating at Article No. Price
operational voltage 50/60 Hz per PU
at 230 V at 400 V at 500 V at 690 V
kvar kvar kvar kvar NO NC V
For screw fixing and snap-on mounting on TH 35 DIN rail
Size S0
9.6 16.7 21 29 1 2 21 ... 28 3RT2625-1NB35 1 1 unit 41B
95 ... 130 3RT2625-1NF35 1 1 unit 41B
200 ... 280 3RT2625-1NP35 1 1 unit 41B
11.5 20 25 34 1 2 21 ... 28 3RT2626-1NB35 1 1 unit 41B
95 ... 130 3RT2626-1NF35 1 1 unit 41B
200 ... 280 3RT2626-1NP35 1 1 unit 41B
14 25 31 43 1 2 21 ... 28 3RT2627-1NB35 1 1 unit 41B
95 ... 130 3RT2627-1NF35 1 1 unit 41B
200 ... 280 3RT2627-1NP35 1 1 unit 41B
19 33 41 57 1 2 21 ... 28 3RT2628-1NB35 1 1 unit 41B
95 ... 130 3RT2628-1NF35 1 1 unit 41B
200 ... 280 3RT2628-1NP35 1 1 unit 41B
Size S2
29 50 63 86 0 2 20 ... 33 3RT2636-1NB35 1 1 unit 41B
83 ... 155 3RT2636-1NF35 1 1 unit 41B
175 ... 280 3RT2636-1NP35 1 1 unit 41B
43 75 94 129 0 2 20 ... 33 3RT2637-1NB35 1 1 unit 41B
83 ... 155 3RT2637-1NF35 1 1 unit 41B
175 ... 280 3RT2637-1NP35 1 1 unit 41B
For screw fixing and snap-on mounting on TH 35-15 and TH 75-15 DIN rails
Size S3
43 75 94 129 0 2 20 ... 33 3RT2645-1NB35 1 1 unit 41B
83 ... 155 3RT2645-1NF35 1 1 unit 41B
175 ... 280 3RT2645-1NP35 1 1 unit 41B
57 100 125 172 0 2 20 ... 33 3RT2646-1NB35 1 1 unit 41B
83 ... 155 3RT2646-1NF35 1 1 unit 41B
175 ... 280 3RT2646-1NP35 1 1 unit 41B
■ Options
Rated control supply voltages for 3RT2 contactors, possible on request
(change of the 10th and 11th digits of the article number)
Delivery time on request
Rated control supply Contactor type 3RT231, 3RT232, 3RT233, 3RT234, 3RT2617,
voltage Us 3RT251 3RT252 3RT253 3RT244, 3RT262, 3RT263,
3RT254 3RT264
Size S00 S0 S2 S3 S00 to S3
Sizes S00 to S3
AC operation1)
Solenoid coils for 50 Hz
(exception: Size S00: 50 and 60 Hz2))
4
24 V AC B0 B0 B0 B0 B0
42 V AC D0 D0 D0 D0 --
48 V AC H0 -- -- H0 --
110 V AC F0 F0 F0 F0 F0
230 V AC P0 P0 P0 P0 P0
240 V AC -- -- U0 U0 --
400 V AC V0 V0 V0 V0 --
Solenoid coils for 50 and 60 Hz2)
24 V AC B0 C2 C2 C2 C2
42 V AC D0 D2 D2 D2 --
48 V AC H0 H2 H2 H2 --
110 V AC F0 G2 G2 G2 --
220 V AC N2 N2 N2 N2 N2
230 V AC P0 L2 L2 L2 L2
Solenoid coils (for USA and Canada3))
50 Hz 60 Hz
110 V AC 120 V AC K6 K6 K6 K6 --
220 V AC 240 V AC P6 P6 P6 P6 --
Solenoid coils (for Japan)
50/60 Hz4) 60 Hz5)
100 V AC 110 V AC G6 G6 G6 G6 G6
200 V AC 220 V AC N6 N6 N6 N6 N6
400 V AC 440 V AC R6 R6 R6 R6 R6
DC operation1)
12 V DC A4 A4 -- -- --
24 V DC B4 B4 -- -- B4
42 V DC D4 D4 -- -- --
48 V DC W4 W4 -- -- --
60 V DC -- -- -- -- --
110 V DC F4 F4 -- -- F4
125 V DC G4 G4 -- -- --
220 V DC M4 M4 -- -- --
230 V DC P4 -- -- -- --
Examples
AC operation 3RT2325-1AP00 Contactor with screw terminals; with solenoid coil for 50 Hz for rated control supply voltage 230 V AC
3RT2325-1AG20 Contactor with screw terminals; with solenoid coil for 50/60 Hz for rated control supply voltage 110 V AC
DC operation 3RT2526-2BB40 Contactor with spring-loaded terminals; for rated control supply voltage of 24 V DC
3RT2526-2BG40 Contactor with spring-loaded terminals; for rated control supply voltage 125 V DC
1) 4)
For deviating coil voltages and operating ranges of sizes S00 and S0, Coil operating range
a SITOP 24 V DC power supply with wide-range input can be used for the - Size S00:
coil control, see page 15/1 and Catalog KT 10.1. at 50/60 Hz: 0.85 to 1.1 x Us,
2) Coil operating range - Sizes S0 to S3:
- at 50 Hz: 0.8 to 1.1 x Us, at 50 Hz: 08 to 1.1 x Us,
- at 60 Hz: 0.85 to 1.1 x Us. at 60 Hz: 0.85 to 1.1 x Us.
5)
3)
Coil operating range Coil operating range at 60 Hz: 0.8 to 1.1 x Us.
- Size S00:
at 50 Hz: 0.85 to 1.1 x Us,
at 60 Hz: 0.8 to 1.1 x Us,
- Sizes S0 to S3: at 50 Hz and 60 Hz: 0.8 to 1.1 x Us.
Rated control supply Contactor 3RT2.2.-.N Rated control supply Contactor 3RT2.3.-.N 3RT2.4.-.N
voltage type voltage type
Us min to Us max1) Size S0 Us min to Us max1) Size S2 S3
Sizes S0 to S3
AC/DC operation (50/60 Hz AC or DC)
21 ... 28 V AC/DC B3 20 ... 33 V AC/DC B3 B3
95 ... 130 V AC/DC F3 48 ... 80 V AC/DC E3 E3
200 ... 280 V AC/DC P3 83 ... 155 V AC/DC F3 F3
175 ... 280 V AC/DC P3 P3
1)
Coil operating range: 0.8 x Us min to 1.1 x Us max.
4
23 ... 26 V AC/DC B3 21 ... 27.3 V AC/DC B3 --
42 ... 48 V AC/DC D3 96 ... 127 V AC/DC F3 F3
110 ... 127 V AC/DC F3 200 ... 277 V AC/DC P3 P3
200 ... 220 V AC/DC M3
220 ... 240 V AC/DC P3
240 ... 277 V AC/DC U3
380 ... 420 V AC/DC V3
440 ... 480 V AC/DC R3
500 ... 550 V AC/DC S3
575 ... 600 V AC/DC T3
■ Overview
Standards Performance range
IEC 60947-4-1, IEC 60077-2, EN 50155 Sizes S00 to S3
• 3RT20 contactors for motor loads (AC-3 and AC-3e)
up to 110 A/55 kW
Sizes S6 to S12
• 3RT10 contactors for motor loads (AC-3 and AC-3e)
from 55 kW to 500 A/250 kW
• 3RT14 contactors for weak or non-inductive loads (AC-1)
up to 690 A
■ Application
4
Besides standard approval in compliance with IEC 60947-4-1, Short-circuit and overload protection of auxiliary connections
the contactors with an extended operating range are also
approved in compliance with the relevant parts of IEC 60077-2, For information on the protection of auxiliary contacts, see the
thus fulfilling the requirement for use in railway applications. technical product data sheet.
Thus, their suitability for increased requirements such as an Short-circuit and overload protection of control supply voltage
connections or supply voltage connections
• extended temperature range compared to the IEC 60947-4-1
product standard or First of all, the relevant standards and regulations for configuring
control panels and the parts and components installed in them
• extended operating range of the contactor operating must be taken into account, for example for cable dimensioning.
mechanisms or also
• increased resistance to mechanical oscillations and vibrations One possible protection for these circuits could be the selection
is warranted. The design of the terminals in the spring-loaded of a suitable power supply, i.e. one with a current-limiting
connection system also contributes toward vibration function. In the selection of the source and the connecting cable,
resistance. the load characteristics of the contactor must be considered
(short-time inrush current peaks for solid-state operating
Operating range of contactor operating mechanisms mechanisms, switch-on power, holding power).
The contactors with extended operating range and railway If there are further switching elements in the circuit, such as the
approval are available with a solid-state DC operating auxiliary contact system of an overload relay that operates the
mechanism in all sizes from S00 to S12. contactor, the short-circuit protection necessary for this must
also be considered.
This operating mechanism version has an operating range from
0.7 to 1.25 x Us in the temperature range -40 to 70 °C. For further recommendations, e.g. the use of miniature circuit
breakers or circuit breakers for equipment in control circuits, see
As from size S6, the operating mechanisms are equipped with Control panel tip – Selecting and dimensioning suitable power
an additional control input that can be operated between 24 DC supplies quickly and reliably.
and 110 V. This function can optionally be switched on or off via
a selector switch. Short-circuit and overload protection of contactors with
a digital input
Protecting connections against short circuit, overload and
overvoltage A typical rated current of 20 mA applies to these inputs based
on the PLC input types according to IEC 60947-4-1.
All connections must generally be protected against overload
and short circuits using suitable measures. Different constraints The inputs can be protected accordingly (for 3RT1...-.X contactors,
must be considered depending on the type of connection: marked with IN+/IN-). The supply voltage connections A1 - A2 must
be protected based on the load characteristics.
Short-circuit and overload protection of main connections
For information on power consumption, see the technical
For information on the protection of a free-standing contactor, product data sheet.
see the technical product data sheet.
Protection against overvoltage at the control supply voltage
For more information on complete units such as contactors with connection
overload relays or contactors with motor starter protectors as the
motor feeder, see Configuration Manual for load feeders. 3RT contactors are already equipped with coil damping
(varistor).
Note:
The break times of the contactor, the opening delay times of the
NO contacts and the closing delay times of the NC contacts
increase with damping.
For more information about influencing the time response using
damping, see Equipment Manual.
4
Expansion possibilities • Sizes S00 to S3:
Side-by-side mounting is permissible at ambient
All basic units (with the exception of coupling contactors in size temperatures up to 70 °C.
S00) can be expanded using auxiliary switches; the permissible
configuration must be observed. • Sizes S6 to S12:
Side-by-side mounting is permissible at ambient
Detailed information about the fitting of auxiliary switches for temperatures up to 60 °C. At > 60 to 70 °C, a clearance
3RT20 contactors, see pages 3/81 to 3/86. of at least 10 mm shall be provided.
Ambient temperature
The permissible ambient temperature for operation of the
contactors (across the full operating range of the operating
mechanisms) is -40 to +70 °C.
■ Technical specifications
More information
Technical specifications, see Manuals, see
https://support.industry.siemens.com/cs/ww/en/ps/16177/td https://support.industry.siemens.com/cs/ww/en/ps/16177/man
FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/16177/faq Guide of use for contactors in safety applications, see
https://support.industry.siemens.com/cs/ww/en/view/109807687
4
Actuated via A1/A2
• Rated control supply voltage V DC 24, 72 or 110
• Operating range 0.7 ... 1.25
Actuated via PLC input
• Rated voltage V DC 24 ... 110
• Operating range 0.7 ... 1.25
• Consumed current at PLC control input according to mA 2
IEC 60947-1, maximum
Rated data of the main contacts
Load rating with AC
Minimum cross-section in the main circuit
• At maximum AC-1 rated value mm2 70 95 150 185 300 370
• At maximum Ith rated value mm2 70 95 150 185 300 370
3RT201.-2K.4. 3RT201.-2K.42-0LA0
Rated data according to IEC 60947-4-1 Auxiliary contacts Rated control Spring-loaded PU PS* PG
AC-3 and AC-3e, supply terminals (UNIT,
tu: 70 °C voltage Us SET, M)
Operational Rating of Ident. No. Version
current Ie three-phase motors Article No. Price
up to at per PU
400 V 230 V 400 V 500 V 690 V
A kW kW kW kW NO NC V DC
For screw fixing and snap-on mounting on TH 35 DIN rail
Size S00
Coupling contactors with integrated coil circuit
• Suppressor diode integrated at the factory
12 3 5.5 5.5 5.5 101) 1 -- 24 3RT2017-2KB41 1 1 unit 41B
110 3RT2017-2KF41 1 1 unit 41B
12 3 5.5 5.5 5.5 011) -- 1 24 3RT2017-2KB42 1 1 unit 41B
110 3RT2017-2KF42 1 1 unit 41B
• Varistor integrated at the factory
12 3 5.5 5.5 5.5 101) 1 -- 24 3RT2017-2LB41 1 1 unit 41B
110 3RT2017-2LF41 1 1 unit 41B
12 3 5.5 5.5 5.5 011) -- 1 24 3RT2017-2LB42 1 1 unit 41B
110 3RT2017-2LF42 1 1 unit 41B
With plug-on series resistor and integrated coil circuit
• Suppressor diode integrated at the factory
12 3 5.5 5.5 5.5 --2) -- 13) 24 3RT2017-2KB42-0LA0 1 1 unit 41B
110 3RT2017-2KF42-0LA0 1 1 unit 41B
16 4 7.5 10 11 --2) -- 13) 24 3RT2018-2KB42-0LA0 1 1 unit 41B
110 3RT2018-2KF42-0LA0 1 1 unit 41B
• Varistor integrated at the factory
12 3 5.5 5.5 5.5 --2) -- 13) 24 3RT2017-2LB42-0LA0 1 1 unit 41B
110 3RT2017-2LF42-0LA0 1 1 unit 41B
16 4 7.5 10 11 --2) -- 13) 24 3RT2018-2LB42-0LA0 1 1 unit 41B
110 3RT2018-2LF42-0LA0 1 1 unit 41B
1) It is not possible to mount an auxiliary switch. A clearance of 10 mm is Accessories and spare parts, see page 3/69 onwards.
required for side-by-side mounting at ambient temperatures > 60 °C.
2)
One 4-pole auxiliary switch according to EN 50005 can be mounted
from -40 to 70 °C; no clearance required.
3)
NC contact cannot be used because it is used for switching of the series
resistor.
4
Rated data according to Auxiliary contacts Rated Spring-loaded PU PS* PG
IEC 60077-2 IEC 60947-4-1 control terminals (UNIT,
supply SET, M)
AC-3 and AC-3e voltage Us
tu: 70 °C tu: 60 °C
Conventional Opera- Rating of three-phase Ident. Version
thermal tional motors No.
current Ith current Ie at Article No. Price
up to up to per PU
3RT203.-3X.40-0LA2 3RT204.-3X.40-0LA2
Rated data according to Auxiliary contacts Rated Spring-loaded PU PS* PG
IEC 60077-2 IEC 60947-4-1 control terminals (UNIT,
supply for auxiliary and control SET, M)
AC-3 and AC-3e voltage circuits
tu: 70 °C tu: 60 °C Us
Conventional Opera- Rating of three-phase Ident. Version
thermal tional motors No.
current Ith current Ie at Article No. Price
up to up to per PU
4
3RT105.-2X.46-0LA2 3RT106.-2X.46-0LA2 3RT107.-2X.46-0LA2
Size Rated data according to Auxiliary Rated control Spring-loaded PU PS* PG
IEC 60077-2 IEC 60947-4-1 contacts, supply voltage terminals (UNIT,
lateral Us SET, M)
AC-3 and AC-3e
tu: 70 °C tu: 60 °C
Conventional thermal Operational Version
current Ith current Ie Article No. Price
up to up to per PU
690 V 400 V
A A NO NC V DC
Solid-state operating mechanism
With control signal input 24 ... 110 V DC
e. g. for control by PLC
With integrated coil circuit (varistor integrated in electronics at the factory)
S6 120 115 2 2 24 3RT1054-2XB46-0LA2 1 1 unit 41B
72 3RT1054-2XJ46-0LA2 1 1 unit 41B
110 3RT1054-2XF46-0LA2 1 1 unit 41B
140 150 2 2 24 3RT1055-2XB46-0LA2 1 1 unit 41B
72 3RT1055-2XJ46-0LA2 1 1 unit 41B
110 3RT1055-2XF46-0LA2 1 1 unit 41B
145 185 2 2 24 3RT1056-2XB46-0LA2 1 1 unit 41B
72 3RT1056-2XJ46-0LA2 1 1 unit 41B
110 3RT1056-2XF46-0LA2 1 1 unit 41B
S10 215 225 2 2 24 3RT1064-2XB46-0LA2 1 1 unit 41B
72 3RT1064-2XJ46-0LA2 1 1 unit 41B
110 3RT1064-2XF46-0LA2 1 1 unit 41B
265 265 2 2 24 3RT1065-2XB46-0LA2 1 1 unit 41B
72 3RT1065-2XJ46-0LA2 1 1 unit 41B
110 3RT1065-2XF46-0LA2 1 1 unit 41B
265 300 2 2 24 3RT1066-2XB46-0LA2 1 1 unit 41B
72 3RT1066-2XJ46-0LA2 1 1 unit 41B
110 3RT1066-2XF46-0LA2 1 1 unit 41B
S12 350 400 2 2 24 3RT1075-2XB46-0LA2 1 1 unit 41B
72 3RT1075-2XJ46-0LA2 1 1 unit 41B
110 3RT1075-2XF46-0LA2 1 1 unit 41B
475 500 2 2 24 3RT1076-2XB46-0LA2 1 1 unit 41B
72 3RT1076-2XJ46-0LA2 1 1 unit 41B
110 3RT1076-2XF46-0LA2 1 1 unit 41B
A A NO NC V DC
Solid-state operating mechanism
With control signal input 24 ... 110 V DC
e. g. for control by PLC
With integrated coil circuit (varistor integrated in electronics at the factory)
S6 190 275 2 2 24 3RT1456-2XB46-0LA2 1 1 unit 41B
72 3RT1456-2XJ46-0LA2 1 1 unit 41B
110 3RT1456-2XF46-0LA2 1 1 unit 41B
S10 330 400 2 2 24 3RT1466-2XB46-0LA2 1 1 unit 41B
72 3RT1466-2XJ46-0LA2 1 1 unit 41B
110 3RT1466-2XF46-0LA2 1 1 unit 41B
330 500 2 2 24 3RT1467-2XB46-0LA2 1 1 unit 41B
72 3RT1467-2XJ46-0LA2 1 1 unit 41B
110 3RT1467-2XF46-0LA2 1 1 unit 41B
S12 520 690 2 2 24 3RT1476-2XB46-0LA2 1 1 unit 41B
72 3RT1476-2XJ46-0LA2 1 1 unit 41B
110 3RT1476-2XF46-0LA2 1 1 unit 41B
■ Overview
Standards Control and auxiliary circuits
IEC 60947-5-1 The solenoid coils of the contactor relays have an extended coil
operating range from 0.7 to 1.25 x Us and are fitted as standard
Ambient temperature with surge suppressors. The opening delay time is consequently
The permissible ambient temperature for operation of the 2 to 5 ms longer than for standard contactors.
contactor relays (across the full operating range of the operating
mechanisms) is -40 to +70 °C.
Uninterrupted duty at temperatures > +60 °C reduces the
mechanical endurance, the current carrying capacity of the
conducting paths and the switching frequency.
4
■ Application
For operation in installations that are subject both to If there are further switching elements in the circuit, such as the
considerable variations in the control voltage and to high auxiliary contact system of an overload relay that operates the
ambient temperatures, e. g. railway applications under extreme auxiliary contactor, the short-circuit protection necessary for this
climatic conditions, rolling mills, etc. must also be considered.
Also for control supply voltages with battery buffering to extend For further recommendations, e.g. the use of miniature circuit
the operating time in the event of battery charge failure. breakers or circuit breakers for equipment in control circuits, see
Control panel tip – Selecting and dimensioning suitable power
Operating mechanism types supplies quickly and reliably.
Contactor relays with conventional coil Protection against overvoltage at the control supply voltage
These auxiliary contactors have an extended operating range of connection
0.7 to 1.25 x Us. An additional auxiliary switch is not required. • Contactor relays with conventional coil:
Contactor relays with series resistor A surge suppressor (suppressor diode) is integrated.
• Contactor relays with series resistor:
These auxiliary contactors have an extended operating range of A surge suppressor (a suppressor diode or varistor as
0.7 to 1.25 x Us. preferred) is integrated.
The DC solenoid system is modified to holding operation by • Contactor relays with solid-state operating mechanism:
means of a series resistor. This is plugged on in a prewired A surge suppressor (varistor) is integrated.
module.
Connection methods
A 4-pole auxiliary switch can be fitted additionally.
The 3RH2 contactor relays are available with screw terminals.
Contactor relays with solid-state operating mechanism
Side-by-side mounting
Thanks to the integrated electronics, these auxiliary contactors
have an extended operating range of 0.7 to 1.25 x Us. Contactor relays with conventional coil
Protecting connections against short circuit, overload and A clearance of 10 mm is required for side-by-side mounting at
overvoltage ambient temperatures > 60 °C 70 °C.
All connections must generally be protected against overload Contactor relays with series resistor
and short circuits using suitable measures. Different constraints Side-by-side mounting is permissible at ambient temperatures
must be considered depending on the type of connection: up to 70 °C.
Short-circuit and overload protection of auxiliary connections Contactor relays with solid-state operating mechanism
For information on the protection of auxiliary contacts, see the Side-by-side mounting is permissible at ambient temperatures
technical product data sheet. up to 70 °C.
Short-circuit and overload protection of control supply voltage
connections or supply voltage connections
First of all, the relevant standards and regulations for configuring
control panels and the parts and components installed in them
must be taken into account, for example for cable dimensioning.
One possible protection for these circuits could be the selection
of a suitable power supply, i.e. one with a current-limiting
function. In the selection of the source and the connecting cable,
the load characteristics of the contactor relay must be
considered (short-time inrush current peaks for solid-state
operating mechanisms, switch-on power, holding power).
■ Technical specifications
More information
Technical specifications, see Manuals, see
https://support.industry.siemens.com/cs/ww/en/ps/16174/td https://support.industry.siemens.com/cs/ww/en/ps/16174/man
FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/16174/faq
Ambient temperature
• During operation °C -40 ... +701)
• During storage °C -55 ... +80
Control
Solenoid coil operating range DC operation 0.7 ... 1.25 x Us
Power consumption of the solenoid coils For cold coil and 1.0 x Us
• Contactors with series resistor Closing W 13 -- --
Closed W 4 -- --
• Contactors with conventional coil Closing W 2.8 -- --
Closed W 2.8 -- --
• Contactors with solid-state operating Closing W -- 4 4.5
mechanism Closed W -- 0.95 0.75
1) 3RH21..-.K contactor relays without article number suffix "-0LA." are
coupling contactor relays that are certified for the temperature range -25 to
+60 °C. For railway applications, an additional certification approves these
contactors with a minimum clearance of 10 mm for the extended
temperature range from -40 to +70 °C.
All details and technical specifications not mentioned here are
identical to those of the 3RH2 basic units, see page 5/5 onwards.
3RH2122-2K.40 3RH2122-2K.40-0LA0
4
Rated operational current Contacts Rated control Spring-loaded PU PS* PG
Ie/AC-15/AC-14 Ident. No. Version supply voltage terminals (UNIT,
tu: 70 °C at according Us SET, M)
to
230 V 400 V 500 V 690 V EN 50011
Article No. Price
per PU
A A A A NO NC V DC
For screw fixing and snap-on mounting on TH 35 DIN rail
Size S00
With integrated coil circuit
• Suppressor diode integrated at the factory
10 3 2 1 22E 2 21) 24 3RH2122-2KB40 1 1 unit 41A
110 3RH2122-2KF40 1 1 unit 41A
31E 3 11) 24 3RH2131-2KB40 1 1 unit 41A
40E 4 01) 24 3RH2140-2KB40 1 1 unit 41A
• Varistor integrated at the factory
10 3 2 1 22E 2 21) 24 3RH2122-2LB40 1 1 unit 41A
110 3RH2122-2LF40 1 1 unit 41A
With plug-on series resistor and integrated coil circuit
• Suppressor diode integrated at the factory
10 3 2 1 21X 2 12) 24 3RH2122-2KB40-0LA0 1 1 unit 41A
110 3RH2122-2KF40-0LA0 1 1 unit 41A
• Varistor integrated at the factory
10 3 2 1 21X 2 12) 24 3RH2122-2LB40-0LA0 1 1 unit 41A
110 3RH2122-2LF40-0LA0 1 1 unit 41A
With integrated coil circuit (varistor integrated in electronics at the factory)
10 3 2 1 22E 2 22) 24 ... 34 3RH2122-2XB40-0LA2 1 1 unit 41A
72 ... 125 3RH2122-2XF40-0LA2 1 1 unit 41A
1) It is not possible to mount an auxiliary switch. Accessories, see page 3/69 onwards.
2)
4-pole auxiliary switch according to EN 50005 can be mounted.
Other voltages according to page 3/67 on request.
■ Overview
Standards Ambient temperature
IEC 60947-5-1 The permissible ambient temperature for operation of the
contactors (across the full solenoid coil operating range)
Terminal covers may have to be fitted onto the connecting bars, is -50 to +70 °C. Uninterrupted duty at temperatures < -25 °C
depending on the configuration with other devices. and > +55 °C reduces the mechanical endurance, the current
carrying capacity of the conducting paths and the switching
frequency.
A clearance of 10 mm is required for side-by-side mounting at
ambient temperatures > 55 °C. There is no need to reduce the
technical specifications.
4
■ Application
For operation in installations which are subject both to Control and auxiliary circuits
considerable variations in the control voltage and to high
ambient temperatures, e.g. in railway applications. The solenoid coils of the contactor relays have an extended coil
operating range from 0.7 to 1.25 x Us and are fitted as standard
with varistors to provide protection against overvoltage. The
opening delay time is consequently 2 to 5 ms longer than for
standard contactors.
■ Technical specifications
More information
Technical specifications, see Manuals, see
https://support.industry.siemens.com/cs/ww/en/ps/16176/td https://support.industry.siemens.com/cs/ww/en/ps/16176/man
FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/16176/faq
3TH4244-0L..
4
Contacts Rated operational current Contacts1) Rated control Screw terminals PU PS* PG
Ie/AC-15/AC-14 Ident. No. Version supply voltage (UNIT,
according Us SET, M)
to
230 V 400 V 500 V 690 V EN 50011
Article No. Price
per PU
Number A A A A NO NC V DC
For screw fixing and snap-on mounting on TH 35 DIN rail
With integrated coil circuit (varistor integrated at the factory)
8 10 6 4 2 44E 4 4 24 3TH4244-0LB4 1 1 unit 41A
110 3TH4244-0LF4 1 1 unit 41A
8 10 6 4 2 53E 5 3 24 3TH4253-0LB4 1 1 unit 41A
110 3TH4253-0LF4 1 1 unit 41A
8 10 6 4 2 62E 6 2 24 3TH4262-0LB4 1 1 unit 41A
110 3TH4262-0LF4 1 1 unit 41A
1)
No expansion contacts can be fitted. Other voltages according to page 5/19 on request.
Accessories, see page 5/20.
■ Overview
Standards Protection against overvoltage at the control supply voltage
connection
IEC 60947-4-1
The 3TC contactors for railway applications are fitted as
Protecting connections against short circuit, overload and standard with varistors against overvoltage.
overvoltage
Ambient temperature
All connections must generally be protected against overload
and short circuits using suitable measures. Different constraints The permissible ambient temperature for operation of the
must be considered depending on the type of connection: contactors (across the full solenoid coil operating range)
is -50 to +70 °C. Uninterrupted duty at temperatures < -25 °C and
Short-circuit and overload protection of main connections > +55 °C reduces the mechanical endurance, the current
For information on the protection of a free-standing contactor, carrying capacity of the conducting paths and the switching
4
For further recommendations, e.g. the use of miniature circuit Contactors with AC operation can be expanded using auxiliary
breakers or circuit breakers for equipment in control circuits, see switches; the permissible configuration must be observed.
Control panel tip – Selecting and dimensioning suitable power Reversing contactors
supplies quickly and reliably.
With the 3TC52 and 3TC56 contactors, the series resistor must
be connected using an additional K2 reversing contactor.
This contactor is automatically included in the scope of supply.
■ Application
For operation in installations which are subject both to Control and auxiliary circuits
considerable variations in the control voltage and to high
ambient temperatures, e.g. in railway applications. The solenoid coils of the contactors have an extended coil
operating range from 0.7 to 1.25 x Us.
■ Technical specifications
More information
Technical specifications, see Manuals, see
https://support.industry.siemens.com/cs/ww/en/ps/16180/td https://support.industry.siemens.com/cs/ww/en/ps/16180/man
All details and technical specifications not mentioned here see page 4/71.
are identical to those of the basic units of the 3TC contactors,
4
3TC48 3TC56 with reversing contactor
Size Utilization Rated Rated power Auxiliary Rated control Screw terminals PU PS* PG
category operational of loads contacts1) supply (UNIT,
current Ie at voltage Us SET, M)
at Version
Article No. Price
per PU
750 V 220 V 440 V 600 V 750 V
A kW kW kW kW NO NC V DC
Contactors for switching DC voltage
With integrated coil circuit (varistor integrated at the factory)
2 DC-1 32 7 14 19.2 24 2 12) 24 3TC4417-0LB4 1 1 unit 41B
DC-3/DC-5 7.5 5 9 9 4 110 3TC4417-0LF4 1 1 unit 41B
With laterally mounted coil circuit (varistor mounted externally in
additional auxiliary switch enclosure on the contactor)
4 DC-1 75 16.5 33 45 56 2 12) 24 3TC4817-0LB4 1 1 unit 41B
DC-3/DC-5 75 13 27 38 45 110 3TC4817-0LF4 1 1 unit 41B
8 DC-1 170 48 97 132 165 2 12) 24 3TC5217-0LB4 1 1 unit 41B
DC-3/DC-5 170 41 82 110 110 110 3TC5217-0LF4 1 1 unit 41B
12 DC-1 400 88 176 240 300 2 12) 24 3TC5617-0LB4 1 1 unit 41B
DC-3/DC-5 400 70 140 200 250 110 3TC5617-0LF4 1 1 unit 41B
1) No expansion auxiliary contacts can be fitted. Other rated control supply voltages according to page 4/78
2)
One NC contact used for series resistor. on request.
■ Accessories
Accessories, see basic units of the 3TC contactors, page 4/78
onwards.
Spare parts for contactors with extended operating range
For contactors Remarks Rated control Article No. Price PU PS* PG
supply voltage per PU (UNIT,
Us SET, M)
Size Type V DC
Arc chutes
2 3TC4417-0L.. With recess for resistor -- 3TY2442-0B 1 1 unit 41B
mounting
Solenoid coils
2 3TC44 With series resistor, 24 3TY6443-0LB4 1 1 unit 41B
without varistor 110 3TY6443-0LF4 1 1 unit 41B
4 3TC48 24 3TY6483-0LB4 1 1 unit 41B
110 3TY6483-0LF4 1 1 unit 41B
■ Overview
3TC4 and 3TC5 3TC7
IEC 60947-1, IEC 60947-4-1, IEC 60947-5-1 (auxiliary switches) IEC 60947-4-1
The DC motor ratings given in the tables are applicable to the The contactors are suitable for switching and controlling
DC-3 and DC-5 utilization categories with 2-pole switching of the DC motors as well as all other DC loads.
load or with the two conducting paths of the contactor
connected in series. The solenoid excitation is configured for a particularly large
operating range. It is between 0.7 or 0.8 and 1.2 Us.
One contactor conducting path can switch full power up to
220 V. For voltages over 220 V, the two conducting paths are to 3TC74 contactors can be used at up to 750 V/400 A and 50 Hz
be switched in series, see Rated data of the main contacts, in AC-1 operation. For voltages over 750 V, the two conducting
page 4/73. paths (3TC74: two contactors) are to be switched in series,
see Rated data of the main contacts, page 4/75.
4
Surge suppression
Contactors (not for railway applications) supplied without a coil
circuit can be retrofitted with RC elements, varistors, diodes or
diode assemblies (combination of diode and Zener diode for
short break times) for damping switching overvoltages in the
coil, see page 4/79 onwards.
Fitting auxiliary contacts and mounting additional auxiliary
switches
• Features in the delivery state:
The 3TC contactors are equipped with two lateral auxiliary
switches with four auxiliary contacts. Of those contacts,
one NC contact is required if a series resistor is used
(2 NO + 1 NC).
• Expansion possibilities:
Contactors with AC operation can be expanded using
auxiliary switches; the permissible configuration must be
observed.
■ Application
The contactors are suitable for switching and controlling A version with a particularly large solenoid coil operating range
DC motors as well as all other DC circuits. is available for operation in electrically driven vehicles and in
switchgear subject to large fluctuations in actuating voltage
(see page 4/69).
■ Technical specifications
More information
Technical specifications, see Manuals, see
https://support.industry.siemens.com/cs/ww/en/ps/16181/td https://support.industry.siemens.com/cs/ww/en/ps/16181/man
FAQs, see
https://support.industry.siemens.com/cs/ww/en/ps/16181/faq
4
AC load
Rated operational current Ie/AC-15/AC-14
• At rated operational voltage Ue 24 V A 10 10
110 V A 10 10
125 V A 10 10
220 V A 6 6
230 V A 5.6 5.6
380 V A 4 4
400 V A 3.6 3.6
500 V A 2.5 2.5
660 V A 2.5 2.5
690 V A -- --
DC load
Rated operational current Ie/DC-12
• At rated operational voltage Ue 24 V A 10 10
60 V A 10 10
110 V A 3.2 8
125 V A 2.5 6
220 V A 0.9 2
440 V A 0.33 0.6
600 V A 0.22 0.4
Rated operational current Ie/DC-13
• At rated operational voltage Ue 24 V A 10 10
48 V A 5 5
110 V A 1.14 2.4
125 V A 0.98 2.1
220 V A 0.48 1.1
440 V A 0.13 0.32
600 V A 0.07 0.21
18
3TC44 3TC48 3TC52 3TC56
2
16
10 6
8
6 14
4
2 12
5
10 10
4
8
6
4 8
2
6
10 4
8
6 4
4
2
2
0,5
10 3
200 400 50 100 150 200 250 300 a (A) 400
10 20 40 100 600 1 000 a (A)
• AC operation mm 70 x 85 x 100 100 x 183 x 154 135 x 238 x 200 160 x 279 x 251
D
4
• AC operation, 60 Hz coil Closing 95/0.79 365/0.45 730/0.38 2 140/0.3
Closed VA/p.f. 12/0.3 35/0.26 56/0.24 140/0.29
• AC operation, 50/60 Hz coil Closing VA/p.f. 79/73/0.83/0.78 --
at 50/60 Hz
Closed VA/p.f. 11/9/0.28/0.27 --
at 50/60 Hz
Rated data of the main contacts
Load rating with DC
Utilization category DC-1 (L/R 1 ms)
• Rated operational currents Ie Up to Ue 750 V A 32 75 220 400
(at 55 °C)
• Minimum conductor cross-section mm2 6 25 95 240
• Rated power at Ue At 220 V kW 7 16.5 48 88
( 220 V DC: one conducting path, 440 V kW 14 33 97 176
> 220 V DC: two conducting paths in series) 600 V kW 19.2 45 132 240
750 V kW 24 56 165 300
Utilization category DC-3 and DC-5,
shunt-wound and series-wound motors (L/R 15 ms)
• Rated operational currents Ie Up to 220 V A 32 75 220 400
(at 55 °C) 440 V A 29 75 220 400
600 V A 21 75 220 400
750 V A 7.5 75 170 400
• Rated power at Ue At 110 V kW 2.5 6.5 20 35
( 220 V DC: one conducting path, 220 V kW 5 13 41 70
> 220 V DC: two conducting paths in series) 440 V kW 9 27 82 140
600 V kW 9 38 110 200
750 V kW 4 45 110 250
Conductor cross-sections
Main conductors Screw terminals
(1 or 2 conductors can be connected)
• Solid mm2 2 x (2.5 ... 10) 2 x (6 ... 16) --
• Finely stranded with end sleeve mm2 2 x (1.5 ... 4) --
• Stranded with cable lug mm2 2 x 16 2 x 35 2 x 120 2 x 150
• Pin cable lug according to DIN 46231 mm2 2 x (1 ... 6) --
• Busbars mm -- 15 x 2.5 25 x 4 2 x (25 x 3)
• Terminal screw M5 M6 M10
Auxiliary conductors
(1 or 2 conductors can be connected)
• Solid mm2 2 x (1 ... 2.5)
• Finely stranded with end sleeve mm2 2 x (0.75 ... 1.5)
D
W
NSB0_00650c
22,5° 22,5° 22,5° 22,5°
The contactors are designed for operation on a vertical
mounting surface.
4
4
• Critical currents, without arc extinction At 440 V A 7 --
600 V A 13 --
750 V A 15 --
800 V A -- 7
1 200 V A -- 13
1 500 V A -- 15
Utilization category DC-3 and DC-5,
shunt-wound and series-wound motors (L/R 15 ms)
• Rated operational current Ie (at 55 °C) A 400
• Rated power at Ue At 110 V kW 35
( 750 V DC: one conducting path, 220 V kW 70
> 750 V DC: two conducting paths in series) 440 V kW 140
600 V kW 200
750 V kW 250
1 200 V kW -- 400
1 500 V kW -- 500
Permissible rated current for regenerative braking A 400
At 110 ... 600 V
Conductor cross-sections
Main conductors Screw terminals
(1 or 2 conductors can be connected)
• Stranded with cable lug mm2 2 x ... 150
• Busbars mm 2 x (30 x 4)
Auxiliary conductors
(1 or 2 conductors can be connected)
• Solid mm2 1 ... 2.5
• Finely stranded with end sleeve mm2 0.75 ... 1.5
3TC44 3TC48
4
Size Utilization Opera- Ratings of Auxiliary Rated control Screw terminals PU PS* PG
category1) tional DC motors contacts3) supply voltage (UNIT,
current at Version Us SET, M)
Ie2)
110 V 220 V 440 V 600 V 750 V Article No. Price
per PU
A kW kW kW kW kW NO NC V
3TC44 to 3TC56 2-pole contactors · Operational voltage up to 750 V
DC operation
For screw fixing and snap-on mounting on TH 35 DIN rail
2 DC-3, 32 2.5 5 9 9 4 2 2 24 DC 3TC4417-0AB4 1 1 unit 41B
DC-5 110 DC 3TC4417-0AF4 1 1 unit 41B
220 DC 3TC4417-0AM4 1 1 unit 41B
For screw fixing
4 DC-3, 75 6.5 13 27 38 45 2 2 24 DC 3TC4817-0AB4 1 1 unit 41B
DC-5 110 DC 3TC4817-0AF4 1 1 unit 41B
220 DC 3TC4817-0AM4 1 1 unit 41B
8 DC-3, 2204) 20 41 82 110 110 2 2 24 DC 3TC5217-0AB4 1 1 unit 41B
DC-5 110 DC 3TC5217-0AF4 1 1 unit 41B
220 DC 3TC5217-0AM4 1 1 unit 41B
12 DC-3, 400 35 70 140 200 250 2 2 24 DC 3TC5617-0AB4 1 1 unit 41B
DC-5 110 DC 3TC5617-0AF4 1 1 unit 41B
220 DC 3TC5617-0AM4 1 1 unit 41B
AC operation, 50 Hz
For screw fixing and snap-on mounting on TH 35 DIN rail
2 DC-3, 32 2.5 5 9 9 4 2 2 220/230 AC5) 3TC4417-0BP0 1 1 unit 41B
DC-5 110/110 AC 3TC4417-0BF0 1 1 unit 41B
For screw fixing
4 DC-3, 75 6.5 13 27 38 45 2 2 220/230 AC5) 3TC4817-0BP0 1 1 unit 41B
DC-5 110 AC 3TC4817-0BF0 1 1 unit 41B
8 DC-3, 2204) 20 41 82 110 110 2 2 220/230 AC5) 3TC5217-0BP0 1 1 unit 41B
DC-5 110 AC 3TC5217-0BF0 1 1 unit 41B
12 DC-3, 400 35 70 140 200 250 2 2 220/230 AC5) 3TC5617-0BP0 1 1 unit 41B
DC-5 110 AC 3TC5617-0BF0 1 1 unit 41B
1)
Permissible load for DC-1 utilization category, see detailed technical Other rated control supply voltages according to page 4/78
specifications in the Reference Manual. on request.
2)
The following rated operational currents are permitted for reversing duty
with 3TC44 to 3TC56 contactors: Accessories, see page 4/78 onwards.
Contactor Rated operational voltage Spare parts, see page 4/80.
Type 110 V, 220 V 440 V
3TC44 32 A 7A
3TC48 75 A 75 A
3TC52 170 A 170 A
3TC56 400 A 400 A
3) The fitting of auxiliary switches cannot be altered on DC-operated
contactors.
4)
At > 600 V: Ie = 170 A.
5)
Operating range at 220 V AC: 0.85 to 1.15 × Us;
lower operating range limit according to IEC 60947.
3TC74 3TC78
4
Size Utiliza- Oper- Ratings of Auxil- Rated Screw terminals PU PS* PG
tion cat- ational DC motors iary control (UNIT,
egory1) cur- at con- supply SET, M)
rent Ie tacts2) voltage
Ver- Us
sion
110 V 220 V 440 V 600 V 750 V 1 200 V 1 500 V Article No. Price
per PU
A kW kW kW kW kW kW kW NO NC V
3TC74 1-pole contactors · Operational voltage up to 750 V
DC operation
12 DC-3, 400 35 70 140 200 250 -- -- 4 4 24 DC 3TC7414-0EB 1 1 unit 41B
DC-5 110 DC 3TC7414-0EF 1 1 unit 41B
AC operation, 50 Hz
12 DC-3, 400 35 70 140 200 250 -- -- 4 4 230/220 3TC7414-1CM 1 1 unit 41B
DC-5 AC3)
3TC78 2-pole contactors · Operational voltage up to 1 500 V
DC operation
12 DC-3, 400 35 70 140 200 250 400 500 4 4 24 DC 3TC7814-0EB 1 1 unit 41B
DC-5 110 DC 3TC7814-0EF 1 1 unit 41B
AC operation, 50 Hz
12 DC-3, 400 35 70 140 200 250 400 500 4 4 230/220 3TC7814-1CM 1 1 unit 41B
DC-5 AC3)
1) Permissible load for DC-1 utilization category, see detailed technical Other rated control supply voltages according to page 4/78
specifications in the Reference Manual. on request.
2)
The fitting of auxiliary switches cannot be altered on DC-operated
contactors. Spare parts, see page 4/80.
3)
Upper operating range limit at 230 V AC: 1.14 x Us.
■ Options
Rated control supply voltages,
possible on request (change of the 10th and 11th digits of the article number)
Delivery time on request
Rated control supply Contactor type 3TC44 3TC48 3TC52/3TC56 3TC74/3TC78
voltage Us
DC operation
24 V DC B4 B4 B4 B
48 V DC W4 W4 -- --
60 V DC E4 E4 -- --
110 V DC F4 F4 F4 F
4
125 V DC G4 G4 -- --
220 V DC M4 M4 M4 M
230 V DC P4 P4 -- --
AC operation
Solenoid coils for 50 Hz
24 V AC B0 B0 -- --
110 V AC F0 F0 F0 --
230/220 V AC P01) P01) P01) M2)
240 V AC U0 U0 -- --
Solenoid coils for 50/60 Hz
24 V AC C2 -- -- --
110 V AC G2 -- -- --
120 V AC K2 -- -- --
220 V AC N2 -- -- --
230 V AC L2 -- -- --
1) 2)
Operating range at 220 V AC: 0.85 to 1.15 × Us; Upper operating range limit at 230 V AC: 1.14 x Us.
lower operating range limit according to IEC 60947.
■ Accessories
For contactors Version Auxiliary switches Screw terminals PU PS* PG
Auxiliary Left Right (UNIT,
contacts SET, M)
Article No. Price
per PU
Size Type NO NC
Second auxiliary switch (for AC operation only)
4 3TC48 2nd auxiliary switch, left 3TY6501-1K 1 1 unit 41B
1 1 53 61 --
54 62
2nd auxiliary switch, right 3TY6501-1L 1 1 unit 41B
1 1 -- 71 83
72 84
8 and 12 3TC52, 2nd auxiliary switch, left 3TY6561-1K 1 1 unit 41B
3TC56 1 1 53 61 --
54 62
2nd auxiliary switch, right 3TY6561-1L 1 1 unit 41B
1 1 -- 71 83
72 84
52 54 62 64
5TY7561-1.
For contactors Version Rated control supply Article No. Price PU PS* PG
voltage Us per PU (UNIT,
SET, M)
Size Type V AC V DC
Surge suppressors · Varistors
2 3TC441) Varistors2) 24 ... 48 24 ... 70 3TX7402-3G 1 1 unit 41B
With line spacer, 48 ... 127 70 ... 150 3TX7402-3H 1 1 unit 41B
for mounting on 127 ... 240 150 ... 250 3TX7402-3J 1 1 unit 41B
the coil terminal 240 ... 400 -- 3TX7402-3K 1 1 unit 41B
400 ... 600 -- 3TX7402-3L 1 1 unit 41B
4 3TC48 Varistors2) 24 ... 48 24 ... 70 3TX7462-3G 1 1 unit 41B
For sticking onto 48 ... 127 70 ... 150 3TX7462-3H 1 1 unit 41B
3TX7402-3. the contactor base 127 ... 240 150 ... 250 3TX7462-3J 1 1 unit 41B
or for mounting 240 ... 400 -- 3TX7462-3K 1 1 unit 41B
separately
4
400 ... 600 -- 3TX7462-3L 1 1 unit 41B
8 and 12 3TC52, Varistors 24 ... 48 -- 3TX7462-3G 1 1 unit 41B
3TC56 For sticking onto 48 ... 127 -- 3TX7462-3H 1 1 unit 41B
the contactor base 127 ... 240 -- 3TX7462-3J 1 1 unit 41B
or for mounting 240 ... 400 -- 3TX7462-3K 1 1 unit 41B
separately 400 ... 600 -- 3TX7462-3L 1 1 unit 41B
3TX7462-3. 8 and 12 3TC52, Varistors2) -- 24 ... 70 3TX7522-3G 1 1 unit 41B
3TC56 For separate screw -- 70 ... 150 3TX7522-3H 1 1 unit 41B
fixing or snapping -- 150 ... 250 3TX7522-3J 1 1 unit 41B
onto TH 35 DIN rail
3TX7522-3.
Surge suppressors · RC elements
4 3TC48 RC elements 24 ... 48 -- 3TX7462-3R 1 1 unit 41B
For lateral -- 24 ... 70 3TX7522-3R 1 1 unit 41B
snapping onto 48 ... 127 -- 3TX7462-3S 1 1 unit 41B
auxiliary switch or -- 70 ... 150 3TX7522-3S 1 1 unit 41B
TH 35 DIN rail
127 ... 240 -- 3TX7462-3T 1 1 unit 41B
-- 150 ... 250 3TX7522-3T 1 1 unit 41B
240 ... 400 -- 3TX7462-3U 1 1 unit 41B
400 ... 600 -- 3TX7462-3V 1 1 unit 41B
3TX7462-3., 8 and 12 3TC52, RC elements 24 ... 48 -- 3TX7522-3R 1 1 unit 41B
3TX7522-3. 3TC56 For lateral 48 ... 127 -- 3TX7522-3S 1 1 unit 41B
snapping onto 127 ... 240 -- 3TX7522-3T 1 1 unit 41B
auxiliary switch or 240 ... 400 -- 3TX7522-3U 1 1 unit 41B
TH 35 DIN rail 400 ... 600 -- 3TX7522-3V 1 1 unit 41B
Surge suppressors · Diodes
4 to 12 3TC48, Diode -- 24 ... 250 3TX7462-3D 1 1 unit 41B
3TC52, assemblies3)
3TC56 (Diode and Zener
diode) for DC
solenoid system,
for sticking onto the
contactor base or
for mounting
3TX7462-3. separately
1) 2)
The connection piece for mounting the surge suppressor must be bent Includes the peak value of the alternating voltage on the DC side.
slightly. 3) Not for DC operation.
■ Spare parts
For contactors Version Auxiliary Auxiliary switches Screw terminals PU (UNIT, PS* PG
contacts Left Right SET, M)
Article No. Price
per PU
Size Type NO NC
Auxiliary switches
For lateral mounting
2 and 4 3TC44, Auxiliary switch 1 1 13 21 31 43 3TY6501-1AA00 1 1 unit 41B
3TC48 (replacement for
3TY6501-1A,
3TY6501-1B) 14 22 32 44
4
14 22
3TY6561-1A Auxiliary switch, 1 1 -- 31 43 3TY6561-1B 1 1 unit 41B
right
32 44
12 3TC74 Auxiliary 4 4 13 21 31 43 53 61 71 83 3TY2741-2J 1 1 unit 41B
switches
14 22 32 44 54 62 72 84
54 62 72 84
For contactors Version Rated control supply Article No. Price PU (UNIT, PS* PG
voltage Us per PU SET, M)
Size Type V AC/DC
Surge suppressors Varistors
12 3TC7 For sticking onto the 24 3TX2746-2F 1 1 unit 41B
contactor base 110 3TX2746-2G 1 1 unit 41B
3TY2482-0A
1)
Rated control supply voltages, see page 4/78. The 10th and 11th digits of
the article number must be supplemented accordingly.
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Price groups
PG 41A, 41B, 41H, 41L
5/2 Introduction
Contactor relays
5/5 SIRIUS 3RH2 contactor relays,
4- and 8-pole
5/14 3TH4 contactor relays,
8- and 10-pole
5/20 - Accessories for 3TH4 contactor relays
Contactors for railway applications
4/63 - SIRIUS 3RH2 contactor relays with
extended operating range
4/66 - 3TH4 contactor relays, 8-pole
5
Coupling relays
5/21 SIRIUS 3RQ1 force-guided coupling
relays, fail-safe up to SIL 3/PL e
NEW NEU
Siemens IC 10 · 2023
© Siemens 2023
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Introduction
■ Overview
More information
Homepage, see www.siemens.com/sirius Conversion tool, see www.siemens.com/conversion-tool
Industry Mall, see www.siemens.com/product?3RH_3TH
Note:
Safety characteristics for contactors, see "Standards and
approvals", page 16/9.
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Introduction
More information
Homepage, see www.siemens.com/sirius-coupling-relays
Industry Mall, see www.siemens.com/product?3RQ_3RS_LZ
TIA Selection Tool Cloud (TST Cloud), see
www.siemens.com/tstcloud/?node=SIRIUSRelais
Video: Overview of SIRIUS coupling relays
Conversion tool, see www.siemens.com/conversion-tool
5
Article No. Page
SIRIUS 3RQ1 force-guided coupling relays, fail-safe up to SIL 3/PL e
Coupling relays with • Widths 17.5 and 22.5 mm 3RQ1 5/21
force-guided contacts • Safety certification according to functional safety SIL 3/PL e
• Can be used as output extension for SIRIUS 3SK safety relays via
device connectors
SIRIUS 3RQ2 coupling relays with industrial enclosure
Coupling relays with relay output • 1, 2 or 3 changeover contacts with wide voltage range 3RQ2 5/29
• Also available with hard gold-plated contacts
SIRIUS 3RQ3 coupling relays, narrow design
Coupling relays with relay output • Width 6.2 mm, 1 CO,
(not plug-in) versions with hard gold-plated contacts optionally available
- Output coupling links 3RQ301 5/33
- Input coupling links 3RQ303 5/33
Coupling relays with plug-in • Width 6.2 mm, 1 CO,
relays versions with hard gold-plated contacts optionally available
- Output coupling links 3RQ311 5/33
Coupling relays • Width 6.2 mm, output 1 semiconductor, triac or transistor
with semiconductor output - Output coupling links 3RQ305, 3RQ306 5/33
(not plug-in) - Input coupling links 3RQ307 5/33
LZS coupling relays with plug-in relays
Coupling relays with plug-in • Switching capacity 12 A/10 A/6 A LZS:PT, LZX:PT 5/48 ... 5/50
relays with 2, 3 and 4 changeover • Width 27 mm
contacts • Base with or without logical separation
Coupling relays with plug-in • Switching capacity 10 A LZS:MT, LZX:MT 5/48
relays with 3 changeover • 11-pole circular base
contacts and circular base • Width 38 mm
Coupling relays with plug-in • Switching capacity 16 A/8 A LZS:RT, LZX:RT 5/49
relays with 1 or 2 changeover • Width 15.5 mm
contacts • Base with or without logical separation
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Introduction
Connection methods Ordering notes for multi-unit packaging
The contactor relays and the relays are available with screw On request, 3RQ1 and 3RQ2 coupling relays can also be
terminals (box terminals) or with spring-loaded terminals. ordered in practical and environmentally friendly multi-unit
packaging.
The 3RQ coupling relays are supplied with screw terminals or
spring-loaded (push-in) terminals. The plug-in sockets for Multi-unit packaging with order code X90
LZS/LZX coupling relays are also available with plug-in (push-in)
terminals. When ordering products in multi-unit packaging, the article number
of the product concerned must be supplemented with "-Z" and,
in addition, the order code "X90" must be specified.
Screw terminals
Ordering examples:
Spring-loaded terminals, • 3RQ10 coupling relays with a width of 17.5 mm
spring-loaded terminals (push-in) 3RQ1000-1EB00-Z X90;
Order quantity 16 units Delivered in one package
Flat connectors containing 16 units
• 3RQ20 coupling relays with a width of 22.5 mm
3RQ2000-1AW00-Z X90;
Plug-in terminals (push-in) Order quantity 12 units Delivered in one package
containing 12 units
5
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Contactor relays
SIRIUS 3RH2 contactor relays, 4- and 8-pole
■ Overview
Contactor relays,
size S00, with accessories
10
11
11
1
5
IC01_00632c
8
9
3
12
13 14
11
6
4
5 11
7
10
1 Contactor relay
2 Coupling contactor relay for auxiliary circuits
3 3RA28 function module 10 Solder pin adapter for contactor relays with 4-pole auxiliary switch
4 1-pole auxiliary switch, cable entry from the top 11 Solder pin adapter
5 2-pole auxiliary switch, cable entry from the top 12 Additional load module for increasing the permissible residual current
6 1-pole auxiliary switch, cable entry from the bottom 13 Surge suppressor with LED
7 2-pole auxiliary switch, cable entry from the bottom 14 Surge suppressor without LED
8 4-pole auxiliary switch
(terminal designations according to EN 50011 or EN 50005)
For contactor relays
9 2-pole auxiliary switch, solid-state compatible version
(terminal designations according to EN 50005) For contactor relays and coupling contactor relays
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Contactor relays
SIRIUS 3RH2 contactor relays, 4- and 8-pole
Standards Accessories
IEC 60947-1, IEC 60947-4-1, IEC 60947-5-1 The accessories for the 3RT2 contactors in size S00 can also be
used for the 3RH2 contactor relays (see page 3/69 onwards).
The 3RH2 contactor relays are available with screw or spring-
loaded terminals. The basic unit contains four contacts with Mounting of additional auxiliary switches
terminal designations according to EN 50011.
Expansion possibilities
The 3RH21 coupling contactor relays for switching auxiliary
circuits are tailored to the special requirements of working with All 3RH21 contactor relays (except for coupling contactor
electronic controls. relays) can be expanded using auxiliary switches;
the permissible configuration must be observed.
Contact reliability of auxiliary contacts
For detailed information about fitting of auxiliary switches, see
High contact stability at low voltages and currents, suitable for pages 3/81 to 3/86.
solid-state circuits with currents 1 mA at a voltage of 17 V.
The auxiliary switch can easily be snapped onto the front of the
Protection of the device connections against overvoltage contactor relays. The auxiliary switch has a centrally positioned
release lever for disassembly.
Protection against overvoltage at the control supply voltage
connection The conventional front auxiliary contacts fulfill the characteristics
of force-guided operation and are therefore suitable for safety
RC elements, varistors, diodes or diode assemblies
5
applications.
(combination of a diode and a Zener diode) can be plugged
onto all 3RH2 contactor relays from the front for damping Contactor relays in safety-related applications
opening surges in the coil. The plug-in direction is determined
by a coding device. Contactor relays are a significant part of safety-related
applications. They are generally the actuators that perform
Coupling contactor relays have a low power consumption and the switching operation leading to the safe disconnection
an extended solenoid coil operating range. of the corresponding application or system.
Depending on the version, the solenoid coils of the coupling Contactor relays with force-guided operation according to
contactor relays are supplied either without overvoltage IEC 60947-5-1 are generally required for use in safety-related
damping (versions 3RH21..-.HB40 or 3RH21..-.MB40-0KT0) applications. Most of our contactors meet this requirement;
or with a diode or suppressor diode connected as standard. a corresponding note can be found in the technical product
data sheet.
Note:
The break times of the contactor, the opening delay times of the Contactor relays with increased tamper protection
NO contacts and the closing delay times of the NC contacts Increased tamper protection is ensured either by using our
increase with damping. contactor relay versions with permanently mounted auxiliary
For more information on how damping influences the time switches installed in the factory (e.g. 3RH22 contactor relays),
response, see the Equipment Manual. or by using the 3RT2916-4MA10 sealable cover as an accessory
(see page 3/112).
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Contactor relays
SIRIUS 3RH2 contactor relays, 4- and 8-pole
■ Technical specifications
More information
Technical specifications, see Manuals, see
https://support.industry.siemens.com/cs/ww/en/ps/16188/td https://support.industry.siemens.com/cs/ww/en/ps/16188/man
FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/16188/faq
Contactor relays
Type 3RH2
Size S00
Permissible mounting position
The contactor relays are designed for operation
NSB0_00478c
360° 22,5° 22,5°
on a vertical mounting surface.
5
NSB0_00477a
Special version required
(in the case of coupling contactor relays and contactor relays with extended
operating range 3RH2122-2K.40 on request)
Force-guided operation of contacts in contactor relays
3RH2: Explanations:
Yes, in the basic unit and the auxiliary switch as well as between the There is force-guided operation if it is ensured that the NC and NO contacts
basic unit and the mounted auxiliary switch (removable) according to: cannot be closed at the same time.
• ZH1/457
• IEC 60947-5-1, Annex L ZH1/457
3RH22: Safety Rules for Controls on Power-Operated Metalworking Presses.
Yes, in the basic unit and the auxiliary switch as well as between the
basic unit and the mounted auxiliary switch (permanently mounted) IEC 60947-5-1, Annex L
according to: Standard for low-voltage switchgear and controlgear; "Special requirements
• ZH1/457 for mechanically linked contact elements"
• IEC 60947-5-1, Annex L
Note:
3RH2911-.NF. solid-state-compatible auxiliary switches have
no force-guided contacts.
Contact reliability
Contact reliability at 17 V, 1 mA according to IEC 60947-5-4 Frequency of contact faults <10-8, i.e. < 1 fault per 100 million operating cycles
Contact endurance for AC-15/AC-14 and
DC-13 utilization categories
The contact endurance is mainly dependent on the breaking current.
It is assumed that the operating mechanisms are switched arbitrarily and 30 NSB0_02061d
not synchronously with the phase angle of the supply system switching Basic unit
operating mechanism.
Million operating cycles (106)
10
If magnetic circuits other than the contactor operating mechanisms or
5 Basic unit with
solenoid valves are present, e.g. magnetic brakes, protective measures 4
for the load circuits are necessary, e.g. in the form of RC elements and 3 attachable
contact block AC-15/AC-14
freewheeling diodes. 2
DC-13 DC-13 Basic unit with
The characteristic curves apply to 1 220 V 110 V attachable
• 3RH21/3RH22 contactor relays1) 0,5 contact block
• 3RH24 latched contactor relays
• 3RH2911 auxiliary switches1) DC-13
• Auxiliary switches for snapping onto the front, 24 V
max. 4-pole and for mounting on the side in size S00 0,1
1)
0,05
0,01
0,01 0,03 0,05 0,1 0,3 0,5 1 2 3 4 5 6 7 10 a (A)
e -DC-13 e -DC-13 e -DC-13 e -AC-15
220 V 110 V 24 V < 230 V
Diagram legend:
a = Breaking current
e = Rated operational current
1)
3RH22, 3RH2911: Ie = 6 A for AC-15/AC-14 and DC-13.
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Contactor relays
SIRIUS 3RH2 contactor relays, 4- and 8-pole
Contactor relays
Type 3RH21 3RH22 3RH24
Size S00
General data
Dimensions (W x H x D)
• Basic units
H
- Screw terminals mm 45 x 58 x 73 -- 90 x 58 x 73
- Spring-loaded terminals mm 45 x 70 x 73 --
D
W
• Basic unit with mounted auxiliary switch
- Screw terminals mm 45 x 58 x 117 --
- Spring-loaded terminals mm 45 x 70 x 121 --
• Basic unit with mounted function module
or solid-state time-delay auxiliary switch
- Screw terminals mm 45 x 58 x 147 --
- Spring-loaded terminals mm 45 x 70 x 147 --
Mechanical endurance
5
Contactor relays
Type 3RH21 3RH22 3RH24
Size S00
Conductor cross-sections
Auxiliary conductors and coil terminals Screw terminals
(1 or 2 conductors can be connected)
• Solid or stranded mm2 2 x (0.5 ... 1.5)1); 2 x (0.75 ... 2.5)1), max. 2 x 4
• Finely stranded with end sleeve mm2 2 x (0.5 ... 1.5)1); 2 x (0.75 ... 2.5)1)
• AWG cables, solid or stranded AWG 2 x (20 ... 16)1); 2 x (18 ... 14)1)
• Terminal screw M3 (for Pozidriv size 2, 5 ... 6 mm)
- Tightening torque Nm 0.8 ... 1.2 (7 ... 10.3 lb.in)
Auxiliary conductors and coil terminals2) Spring-loaded terminals
(1 or 2 conductors can be connected)
• Operating devices mm 3.0 x 0.5; 3.5 x 0.5
• Solid or stranded mm2 2 x (0.5 ... 4)
• Finely stranded with end sleeve mm2 2 x (0.5 ... 2.5)
• Finely stranded without end sleeve mm2 2 x (0.5 ... 2.5)
• AWG cables, solid or stranded AWG 2 x (20 ... 12)
Auxiliary conductors for front and laterally mounted auxiliary switches2)
• Operating devices mm 3.0 x 0.5; 3.5 x 0.5
• Solid or stranded mm2 2 x (0.5 ... 2.5)
• Finely stranded with end sleeve mm2 2 x (0.5 ... 1.5)
• Finely stranded without end sleeve mm2 2 x (0.5 ... 2.5)
• AWG cables, solid or stranded AWG 2 x (20 ... 14)
1)
If two different conductor cross-sections are connected to one clamping
point, both cross-sections must lie in one of the ranges specified.
2)
Max. external diameter of the conductor insulation: 3.6 mm.
On spring-loaded terminals with conductor cross-sections 1 mm2
an insulation stop is recommended, see page 3/115.
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Contactor relays
SIRIUS 3RH2 contactor relays, 4- and 8-pole
Contactor relays
Type 3RH2
Size S00
Control
Solenoid coil operating range
• AC operation at 50 Hz 0.8 ... 1.1 x Us
at 60 Hz 0.85 ... 1.1 x Us
• DC operation at +50 °C 0.8 ... 1.1 x Us
at +60 °C 0.85 ... 1.1 x Us
Power consumption of the solenoid coil
(for cold coil and 1.0 x Us)
• AC operation, 50 Hz
- Closing VA/p.f. 37/0.8
- Closed VA/p.f. 5.7/0.25
• AC operation, 60 Hz
- Closing VA/p.f. 33/0.75
- Closed VA/p.f. 4.4/0.25
5
• DC operation W 4.0
Closing = Closed
Permissible residual current of the electronics
(with 0 signal)
• For AC operation1) < 4 mA x (230 V/Us)
• For DC operation < 10 mA x (24 V/Us)
1)
The 3RT2916-1GA00 additional load module is recommended for higher
residual currents, see page 3/114.
Contactor relays
Type 3RH2
Size S00
Rated data of the auxiliary contacts
Load rating with AC
Rated operational currents Ie
AC-12 A 10
AC-15/AC-14, at rated operational voltage Ue
Up to 230 V A 101)
400 V A 3
500 V A 2
690 V A 1
s and u rated data
Basic units and auxiliary switches
• Rated control supply voltage V AC max. 600
• Rated voltage V AC 600
• Switching capacity A 600, Q 600
• Uninterrupted current at 240 V AC A 10
1)
3RH22, 3RH29: Ie = 6 A for AC-15/AC-14 and DC-13.
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Contactor relays
SIRIUS 3RH2 contactor relays, 4- and 8-pole
Rated operational current Contacts Rated control supply Screw terminals Spring-loaded
Ie/AC-15/AC-14 voltage Us terminals
at 230 V Ident. No. Version at 50/60 Hz1)
Article No. Price Article No. Price
per PU per PU
A NO NC V AC
For screw and snap-on mounting on TH 35 DIN rail
Size S00
10 40E 4 -- 24 3RH2140-1AB00 3RH2140-2AB00
110 3RH2140-1AF00 3RH2140-2AF00
230 3RH2140-1AP00 3RH2140-2AP00
31E 3 1 24 3RH2131-1AB00 3RH2131-2AB00
110 3RH2131-1AF00 3RH2131-2AF00
230 3RH2131-1AP00 3RH2131-2AP00
22E 2 2 24 3RH2122-1AB00 3RH2122-2AB00
110 3RH2122-1AF00 3RH2122-2AF00
230 3RH2122-1AP00 3RH2122-2AP00
With permanently mounted auxiliary switch
6 44E 4 4 230 3RH2244-1AP00 3RH2244-2AP00
62E 6 2 230 3RH2262-1AP00 3RH2262-2AP00
Latched
No lateral auxiliary switches can be mounted
10 40 E 4 -- 24 3RH2440-1AB00 --
110 3RH2440-1AF00 --
230 3RH2440-1AP00 --
31 E 3 1 24 3RH2431-1AB00 --
110 3RH2431-1AF00 --
230 3RH2431-1AP00 --
22 E 2 2 24 3RH2422-1AB00 --
110 3RH2422-1AF00 --
230 3RH2422-1AP00 --
1) Coil operating range Other voltages according to page 3/67 on request.
- at 50 Hz: 0.8 to 1.1 x Us
- at 60 Hz: 0.85 to 1.1 x Us. Accessories, see page 3/69 onwards.
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Contactor relays
SIRIUS 3RH2 contactor relays, 4- and 8-pole
DC operation
PU (UNIT, SET, M) = 1
PS* = 1 unit
PG = 41A
Rated operational current Contacts Rated control supply Screw terminals Spring-loaded
Ie/AC-15/AC-14 Ident. No. Version voltage Us terminals
at 230 V
5
Article No. Price Article No. Price
per PU per PU
A NO NC V DC
For screw and snap-on mounting on TH 35 DIN rail
Size S00
10 40E 4 -- 24 3RH2140-1BB40 3RH2140-2BB40
220 3RH2140-1BM40 3RH2140-2BM40
31E 3 1 24 3RH2131-1BB40 3RH2131-2BB40
220 3RH2131-1BM40 3RH2131-2BM40
22E 2 2 24 3RH2122-1BB40 3RH2122-2BB40
220 3RH2122-1BM40 3RH2122-2BM40
With integrated coil circuit (diode integrated at the factory)
10 40E 4 -- 24 3RH2140-1FB40 3RH2140-2FB40
31E 3 1 24 3RH2131-1FB40 3RH2131-2FB40
22E 2 2 24 3RH2122-1FB40 3RH2122-2FB40
With permanently mounted auxiliary switch
6 44E 4 4 24 3RH2244-1BB40 3RH2244-2BB40
62E 6 2 24 3RH2262-1BB40 3RH2262-2BB40
Latched
No lateral auxiliary switches can be mounted
10 40E 4 -- 24 3RH2440-1BB40 --
110 3RH2440-1BF40 --
220 3RH2440-1BM40 --
31E 3 1 24 3RH2431-1BB40 --
110 3RH2431-1BF40 --
220 3RH2431-1BM40 --
22E 2 2 24 3RH2422-1BB40 --
110 3RH2422-1BF40 --
220 3RH2422-1BM40 --
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Contactor relays
SIRIUS 3RH2 contactor relays, 4- and 8-pole
DC operation for direct control by PLC
• Coupling contactor relays with adapted power consumption
• Suitable for solid-state PLC outputs
• Cannot be expanded with auxiliary switches
PU (UNIT, SET, M) = 1
PS* = 1 unit
PG = 41A
3RH21..-1.B40 3RH21..-2.B40
5
Rated operational current Auxiliary contacts Rated control Screw terminals Spring-loaded
Ie/AC-15/ AC-14 Ident. No. Version supply voltage Us terminals
at 230 V according
to
EN 50011
Article No. Price Article No. Price
per PU per PU
A NO NC V DC
For screw and snap-on mounting on TH 35 DIN rail
Size S00
Cannot be expanded with auxiliary switches
Operating range 0.7 to 1.25 x Us,
power consumption of the solenoid coils 2.8 W at 24 V
10 40E 4 -- 24 3RH2140-1HB40 3RH2140-2HB40
31E 3 1 24 3RH2131-1HB40 3RH2131-2HB40
22E 2 2 24 3RH2122-1HB40 3RH2122-2HB40
Operating range 0.85 to 1.85 x Us,
power consumption of the solenoid coils 1.6 W at 24 V
10 40E 4 -- 24 3RH2140-1MB40-0KT0 3RH2140-2MB40-0KT0
31E 3 1 24 3RH2131-1MB40-0KT0 3RH2131-2MB40-0KT0
22E 2 2 24 3RH2122-1MB40-0KT0 3RH2122-2MB40-0KT0
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Contactor relays
SIRIUS 3RH2 contactor relays, 4- and 8-pole
DC operation for direct control by PLC
• Coupling contactor relays with adapted power consumption
• Suitable for solid-state PLC outputs
• Cannot be expanded with auxiliary switches
PU (UNIT, SET, M) = 1
PS* = 1 unit
PG = 41A
5
3RH21..-1.B40 3RH21..-2.B40
Rated operational current Auxiliary contacts Rated control Screw terminals Spring-loaded
Ie/AC-15/ AC-14 Ident. No. Version supply voltage Us terminals
at 230 V according
to
EN 50011
Article No. Price Article No. Price
per PU per PU
A NO NC V DC
For screw and snap-on mounting on TH 35 DIN rail
Size S00
With integrated coil circuit (diode integrated at factory)
Cannot be expanded with auxiliary switches
Operating range 0.7 to 1.25 x Us
Power consumption of the solenoid coils 2.8 W at 24 V
10 40E 4 -- 24 3RH2140-1JB40 3RH2140-2JB40
31E 3 1 24 3RH2131-1JB40 3RH2131-2JB40
22E 2 2 24 3RH2122-1JB40 3RH2122-2JB40
Operating range 0.85 to 1.85 x Us
Power consumption of the solenoid coils 1.6 W at 24 V
10 40E 4 -- 24 3RH2140-1VB40 3RH2140-2VB40
31E 3 1 24 3RH2131-1VB40 3RH2131-2VB40
22E 2 2 24 3RH2122-1VB40 3RH2122-2VB40
With integrated coil circuit (suppressor diode integrated at factory)
Cannot be expanded with auxiliary switches
Operating range 0.7 to 1.25 x Us
Power consumption of the solenoid coils 2.8 W at 24 V
10 40E 4 -- 24 3RH2140-1KB40 3RH2140-2KB40
31E 3 1 24 3RH2131-1KB40 3RH2131-2KB40
22E 2 2 24 3RH2122-1KB40 3RH2122-2KB40
Operating range 0.85 to 1.85 x Us
Power consumption of the solenoid coils 1.6 W at 24 V
10 40E 4 -- 24 3RH2140-1SB40 3RH2140-2SB40
31E 3 1 24 3RH2131-1SB40 3RH2131-2SB40
22E 2 2 24 3RH2122-1SB40 3RH2122-2SB40
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Contactor relays
3TH4 contactor relays, 8- and 10-pole
■ Overview
Standards Protection of the device connections against overvoltage
IEC 60947-1, IEC 60947-5-1 Protection against overvoltage at the control supply voltage
connection
Note:
The 3TH42 and 3TH43 contactor relays can be equipped with
The 3TH42 and 3TH43 contactor relays feature force-guided RC elements, varistors, diodes or diode assemblies
operation in accordance with IEC 60947-5-1, Ed. 3.1. (combination of a diode and a Zener diode) for damping
Terminal designations according to EN 50011 opening surges. The surge suppressors can be mounted
directly on the coil, see page 5/20.
In terms of their terminal designations, identification numbers
and identification letters, the 3TH42 and 3TH43 contactor Note:
relays conform to the standard EN 50011 for "Particular The break times of the contactor, the opening delay times of the
Contactor Relays". NO contacts and the closing delay times of the NC contacts
Contact reliability of auxiliary contacts increase with damping.
High contact stability at low voltages and currents as a result of For more information on how damping influences the time
double-break contacts, suitable for solid-state circuits with response, see the Equipment Manual.
5
■ Technical specifications
More information
Technical specifications, see Manuals, see
https://support.industry.siemens.com/cs/ww/en/ps/16176/td https://support.industry.siemens.com/cs/ww/en/ps/16176/man
FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/16176/faq
operating mechanism.
10
If magnetic circuits other than the contactor operating mechanisms or
solenoid valves are present, e.g. magnetic brakes, protective measures DC-13 AC-15/AC-14
for the load circuits are necessary. 5
4
110 V
RC elements or freewheeling diodes are suitable as protective measures 3
for the circuits.
2
DC-13 DC-13
220 V 24 V
1
0,5
0,1
0,01 0,03 0,05 0,1 0,3 0,5 1 2 3 4 5 7 10 a (A)
-DC-13 e -DC-13
e -DC-13
e
220 V 110 V 24 V
Diagram legend:
e-AC-15/AC-14
a = Breaking current ≤ 230 V
e = Rated operational current
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Contactor relays
3TH4 contactor relays, 8- and 10-pole
H
• DC operation mm 45 x 78 x 130 55 x 78 x 130
D
W
NSB0_00478c
360° 22,5° 22,5°
• DC operation
NSB0_00649a
22,5° 22,5°
90° 90°
5
Upright mounting position
AC and DC operation
NSB0_00477a
Special version required
Mechanical endurance Basic units Operat- 30 million
ing
cycles
Rated insulation voltage Ui V 690
(pollution degree 3)
Rated impulse withstand voltage Uimp kV 8
Protective separation between the coil and the main contacts V Up to 500
according to IEC 60947-1, Annex N
Permissible ambient temperature
• During operation °C -25 ... +55
• During storage °C -55 ... +80
Short-circuit protection
Short-circuit test
• With fuse links of operational class gG
With short-circuit current Ik = 1 kA according to IEC 60947-5-1
- LV HRC, type 3NA A 16
- DIAZED, type 5SB A 16
- NEOZED, type 5SE, quick A 20
• With miniature circuit breakers
With short-circuit current Ik = 400 A according to IEC 60947-5-1
- C characteristic A 16
- B characteristic A 16
s and u rated data
Basic units
Rated control supply voltage Us Max. 600 V AC, 230 V DC (according to UL 240 V DC)
Rated voltage 600 V AC, 600 V DC
Switching capacity A 600, P 600
Conductor cross-sections
Auxiliary conductors and coil terminals Screw terminals
(1 or 2 conductors can be connected)
• Solid or stranded mm2 2 x (0.5 ... 1)1); 2 x (1 ... 2.5)1); 1 x 4
• Finely stranded with end sleeve mm2 2 x (0.75 ... 2.5)
• Terminal screw M3.5
1) If two different conductor cross-sections are connected to one clamping
point, both cross-sections must lie in one of the ranges specified.
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Contactor relays
3TH4 contactor relays, 8- and 10-pole
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Contactor relays
3TH4 contactor relays, 8- and 10-pole
3TH4280-0AP0 3TH4244-0BB4
Contacts Rated operational current Contacts Screw terminals PU PS* PG
Ie/AC-15/AC-14 (UNIT,
at SET, M)
230/ 400/ 500 V 690/ Ident. No. Version
5
220 V 380 V 660 V according to
EN 50011
Article No. Price
per PU
Number A A A A NO NC NO NC
For screw and snap-on mounting on TH 35 DIN rail
AC operation, rated control supply voltage Us = 50 Hz 230/220 V AC1)
8 10 6 4 2 80E 8 -- -- -- 3TH4280-0AP0 1 1 unit 41A
71E 7 1 -- -- 3TH4271-0AP0 1 1 unit 41A
62E 6 2 -- -- 3TH4262-0AP0 1 1 unit 41A
53E 5 3 -- -- 3TH4253-0AP0 1 1 unit 41A
44E 4 4 -- -- 3TH4244-0AP0 1 1 unit 41A
44E, U 3 3 1 1 3TH4293-0AP0 1 1 unit 41A
DC operation, rated control supply voltage Us = 24 V DC
8 10 6 4 2 80E 8 -- -- -- 3TH4280-0BB4 1 1 unit 41A
71E 7 1 -- -- 3TH4271-0BB4 1 1 unit 41A
62E 6 2 -- -- 3TH4262-0BB4 1 1 unit 41A
53E 5 3 -- -- 3TH4253-0BB4 1 1 unit 41A
44E 4 4 -- -- 3TH4244-0BB4 1 1 unit 41A
44E, U 3 3 1 1 3TH4293-0BB4 1 1 unit 41A
1)
Operating range at 220 V: 0.85 to 1.1 × Us; Other voltages according to page 5/19 on request.
lower operating range limit according to IEC 60947.
Accessories, see page 5/20.
Note:
The solenoid coils of the 3TH42 contactor relays are available in
various voltages as spare parts (on request).
- AC operation: 3TY7403-0A..
- DC operation: 3TY4803-0B..
The contacts cannot be replaced on 3TH42 contactor relays.
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Contactor relays
3TH4 contactor relays, 8- and 10-pole
10-pole contactor relays
AC operation or DC operation
3TH4355-0AP0 3TH4355-0BB4
Contacts Rated operational current Contacts Screw terminals PU PS* PG
Ie/AC-15/AC-14 (UNIT,
at SET, M)
230 V 400 V 500 V 690 V Ident. No. Version
according to
EN 50011
Article No. Price
5
per PU
Number A A A A NO NC NO NC
For screw and snap-on mounting on TH 35 DIN rail
AC operation, rated control supply voltage Us = 50 Hz 230/220 V AC1)
10 10 6 4 2 100E 10 -- -- -- 3TH4310-0AP0 1 1 unit 41A
91E 9 1 -- -- 3TH4391-0AP0 1 1 unit 41A
82E 8 2 -- -- 3TH4382-0AP0 1 1 unit 41A
73E 7 3 -- -- 3TH4373-0AP0 1 1 unit 41A
73E, U 6 2 1 1 3TH4346-0AP0 1 1 unit 41A
64E 6 4 -- -- 3TH4364-0AP0 1 1 unit 41A
55E 5 5 -- -- 3TH4355-0AP0 1 1 unit 41A
55E, U 4 4 1 1 3TH4394-0AP0 1 1 unit 41A
DC operation, rated control supply voltage Us = 24 V DC
10 10 6 4 2 100E 10 -- -- -- 3TH4310-0BB4 1 1 unit 41A
91E 9 1 -- -- 3TH4391-0BB4 1 1 unit 41A
82E 8 2 -- -- 3TH4382-0BB4 1 1 unit 41A
73E 7 3 -- -- 3TH4373-0BB4 1 1 unit 41A
73E, U 6 2 1 1 3TH4346-0BB4 1 1 unit 41A
64E 6 4 -- -- 3TH4364-0BB4 1 1 unit 41A
55E 5 5 -- -- 3TH4355-0BB4 1 1 unit 41A
55E, U 4 4 1 1 3TH4394-0BB4 1 1 unit 41A
1)
Operating range at 220 V: 0.85 to 1.1 × Us; Other voltages according to page 5/19 on request.
lower operating range limit according to IEC 60947.
Accessories, see page 5/20.
Note:
The solenoid coils of the 3TH43 contactor relays are available in
various voltages as spare parts (on request).
- AC operation: 3TY7403-0A..
- DC operation: 3TY4803-0B..
The contacts cannot be replaced on 3TH43 contactor relays.
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Contactor relays
3TH4 contactor relays, 8- and 10-pole
■ Options
Rated control supply voltages, possible on request (change of the 10th and 11th digits of the article number)
Delivery time on request
Contactor type 3TH42/3TH43 Contactor type 3TH42/3TH43
Rated control supply Control supply voltage Rated control supply
voltage Us at voltage Us
AC operation DC operation
Solenoid coils for 50 and 60 Hz AC 12 V DC A4
24 V DC B4
50 Hz 60 Hz
30 V DC C4
24 V AC 29 V AC B0
36 V DC V4
36 V AC 42 V AC G0
42 V DC D4
42 V AC 50 V AC D0
48 V DC W4
48 V AC 58 V AC H0
60 V DC E4
60 V AC 72 V AC E0
110 V DC F4
110 V AC 132 V AC F0
125 V DC G4
125/127 V AC 150/152 V AC L0
5
220 V DC M4
230/220 V AC 276 V AC P01)
230 V DC P4
240 V AC 288 V AC U0
240 V DC Q4
400/380 V AC 480/460 V AC V01)
415 V AC 500 V AC R0
500 V AC 600 V AC S0
50/60 Hz
24 V AC C2
42 V AC D2
110 V AC G2
115 V AC J2
120 V AC K2
220 V AC N2
230 V AC L2
240 V AC P2
440 V AC R2
For Japan
50 Hz 60 Hz
100 V AC 100 ... 110 V AC G62)
200 V AC 200 ... 220 V AC N62)
For USA and Canada
50 Hz 60 Hz
110 V AC 120 V AC K62)
220 V AC 240 V AC P62)
1)
Operating range at 220 V or 380 V: 0.85 to 1.1 x Us.
2)
Operating range at 60 Hz: 0.85 to 1.1 x Us.
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Contactor relays
3TH4 contactor relays, 8- and 10-pole > Accessories for 3TH4 contactor relays
3TX4180-0A
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Coupling relays
NEW NEU
SIRIUS 3RQ1 force-guided coupling relays, fail-safe up to SIL 3/PL e
■ Overview
More information
Homepage, see www.siemens.com/sirius-coupling-relays
Industry Mall, see www.siemens.com/product?3RQ1
Technical specifications, see
https://support.industry.siemens.com/cs/ww/en/ps/26008/td
Manuals, see
https://support.industry.siemens.com/cs/ww/en/ps/26008/man
TIA Selection Tool Cloud (TST Cloud), see
www.siemens.com/tstcloud/?node=SIRIUSRelais
SIRIUS 3SK safety relays, see
https://mall.industry.siemens.com/mall/en/ww/Catalog/Products/
10143262?tree=CatalogTree
5
Video: SIRIUS 3RQ1 coupling relays
Picture on left: 3RQ1000-1EW00 coupling relay,
1 NO contact + 1 NC contact, screw terminal The force-guided SIRIUS 3RQ1 coupling relays in a modern
Picture on right: 3RQ1000-2LW00 coupling relay, titanium gray industrial enclosure are available in widths of
4 NO contacts + 1 NC contact, spring-loaded terminal (push-in)
17.5 mm and 22.5 mm, and each with a supply voltage
of 24 V DC (120 mm mounting depth) and 24 to 240 V AC/DC
(90 mm mounting depth).
They are used for safe coupling up to SIL 3/PL e of control
signals to and from a control system or as an output expansion
for the SIRIUS 3SK safety relays (see page 11/13 onwards).
Further fields of application are based on the force-guided
operation of relays according to IEC 60947-5-1 and EN 61810-3
for reading back relay states, for reliable diagnostics or signaling,
or for the use of antivalent signals. Typical fields of application
here are railways, signaling technology and elevators.
The series consists of devices with up to five outputs and can be
supplied with screw or spring-loaded (push-in) terminals.
International standards and certifications including CE, UL/CSA,
EAC and railway approvals ensure international usability and
exportability.
An extensive range of accessories is also available, such as
device connectors for easy and safe connection of the 3RQ1
3RQ1 coupling relay in the 3SK system devices, replacement terminals, push-in lugs for wall mounting
and coding pins, see page 5/27 onwards.
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Coupling relays
SIRIUS 3RQ1 force-guided coupling relays, fail-safe up to SIL 3/PL e NEW NEU
The article number scheme shows an overview of product versions For your orders, please use the article numbers quoted in the
for better understanding of the logic behind the article numbers. selection and ordering data.
■ Benefits
• Wide-range voltage versions from 24 to 240 V AC/DC
available with a mounting depth of 90 mm for all variants
• Permanent wiring thanks to removable terminals in screw
or spring-loaded technology (push-in)
• Replacement of individual terminals minimizes wiring effort
• Can be used as output extension for SIRIUS 3SK safety relays
via device connectors
• All versions with real load contacts, also in the NC circuit
• Safety certification according to functional safety SIL 3/PL e
• International standards and certifications including CE,
UL/CSA, EAC, railway approvals, and more
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Coupling relays
NEW NEU
SIRIUS 3RQ1 force-guided coupling relays, fail-safe up to SIL 3/PL e
■ Application
• Safe coupling up to SIL 3/PL e of control signals from and
to a control system
• Output expansion for 3SK safety relays
• Use of force-guided contacts for reading back relay states
• For reliable diagnostics or signaling or for antivalent switching
1 of loads
IC 01_0 06
92a • Safe coupling:
- Electrical separation between the input and output circuit
- Adjustment of different signal levels
2 - Signal amplification
2 2 2 3 - Contact multiplication
3RQ1 output expansion (up to SIL 3/PL e) for the 3SK system
The force-guided 3RQ1 coupling relays with a mounting depth
of 120 mm can be used as an output expansion up to SIL 3/PL e
and can be connected by wiring to all 3SK basic units and by
5
using the 3ZY12 device connector to all 3SK1 and 3SK2
Advanced basic units.
They have a switching capacity of AC-15 5/3 A (like 3SK1211)
at a switching voltage of 230 V and are available in widths of
17.5 mm and 22.5 mm. Furthermore, they have NC contacts with
8 a switching capacity of AC-15 2/1.5 A for direct switching of
7 loads (anti-parallel switching, signaling, etc.).
6
5
1 DIN rail 4
2 Device connector
3 Device termination connector
4 SIRIUS 3RM1 motor starter
5 Force-guided 3RQ1 coupling relay as output
expansion up to SIL 3/PL e
6 SIRIUS 3SK1211 output expansion
7 SIRIUS 3SK1121 Advanced basic unit
8 SIRIUS 3SK1220 sensor expansion
Electronic
I/O control
devices 110 V AC 110 V AC Actuators
Output
230 V AC
Input
24 V DC 24 V DC 230 V AC
M
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Coupling relays
SIRIUS 3RQ1 force-guided coupling relays, fail-safe up to SIL 3/PL e NEW NEU
Applications
IC01_00741
IC01_00740
F-PLC
3RQ1
coupling
relay
5
3RT2
contactor
Sensor Actuator
(e.g. SIDOOR) Motor Valve
Application based on force-guided operation 3RQ1 as coupling link for signals, e.g. for a fail-safe control system
3SK1 safety
relays 3RQ1 coupling
relays
IC01_00742
3RT2
contactors
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Coupling relays
NEW NEU
SIRIUS 3RQ1 force-guided coupling relays, fail-safe up to SIL 3/PL e
■ Technical specifications
More information
Technical specifications, see Manuals, see
https://support.industry.siemens.com/cs/ww/en/ps/26008/td https://support.industry.siemens.com/cs/ww/en/ps/26008/man
Equipment Manual 3SK1/3RQ1, see
https://support.industry.siemens.com/cs/ww/en/view/67585885
5
Safety Integrity Level (SIL) 2 3 2 3 2
according to IEC 62061
Performance Level (PL) c e c e c
according to ISO 13849-1
Certificate of suitability
• UL approval Yes
• TÜV approval Yes
Insulation voltage for overvoltage V 300
category III according to IEC 60664 for
pollution degree 3
Ambient temperature
• During operation °C -25 ... +60
• During storage °C -40 ... +80
Degree of protection IP IP20
Control circuit
Control supply voltage
• At AC
- At 50 Hz V -- 24 ... 240 -- 24 ... 240
- At 60 Hz V -- 24 ... 240 -- 24 ... 240
• At DC V 24 24 ... 240 24 24 ... 240
Operating range factor of the control
supply voltage, rated value
• At DC 0.8 ... 1.2 0.7 ... 1.1 0.8 ... 1.2 0.7 ... 1.1
Load circuit
Thermal current of the non-solid-state A 5
contact blocks, maximum
Mechanical endurance (operating 10 000 000
cycles) typical
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Coupling relays
SIRIUS 3RQ1 force-guided coupling relays, fail-safe up to SIL 3/PL e NEW NEU
3RQ1000- 3RQ1000-
1LW00 2LW00
✓ Yes Note:
-- No
1)
All force-guided 3RQ1 coupling relays have safety certification up
NC contact designed to act as feedback contact. to SIL 2/PL c or SIL 3/PL e according to IEC 62061/ISO 13849.
To achieve SIL 3/PL e, two 3RQ10 devices can also be wired in
series, see Equipment Manual.
In addition, the 3SK1211 devices (output expansions for 3SK)
provide force-guided coupling relays with 4 NO contacts and
1 NC contact up to SIL 3/PL e with 24 V AC, 24 V DC, and 110 to
240 V AC/DC.
For applications with high currents up to a switching capacity of
10 A AC-15, the 3SK1213 output expansions are also available
with 24 V AC, 24 V DC and 110 to 240 V AC/DC.
These devices can be used in the same way as the 3RQ1
coupling relays for coupling to and from safe control systems,
they feature 4 NO contacts and 1 NC contact, and are available
as variants with 24 V AC, 24 V DC and 110 to 240 V AC/DC (see
page 11/27).
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Coupling relays
NEW NEU
SIRIUS 3RQ1 force-guided coupling relays, fail-safe up to SIL 3/PL e
■ Accessories
More information
Manuals, see
https://support.industry.siemens.com/cs/ww/en/ps/26008/man
5
3ZY1212- 3ZY1212-
1BA00 2BA00
Device termination connectors
• Width 17.5 mm (for 3RQ1000-.EB00/-.GB00, 3ZY1212-1DA00 1 1 unit 41L
3RQ1200-.EB00)
• Width 22.5 mm (for 3RQ1000-.HB00/-.LB00) 3ZY1212-2DA00 1 1 unit 41L
Note:
Observe positions of the slide switch for width
22.5 mm, see Equipment Manual.
3ZY1212-
2DA00
Device daisy chain connectors 3ZY1212-2AB00 1 1 unit 41L
24 V DC, 22.5 mm, for implementation of distances
between devices according to the installation
guidelines
Device connectors 3ZY1210-2AA00 1 1 unit 41L
For height adjustment for device arrangements
without electrical connection via device connector,
with a width of 22.5 mm or greater
Terminals for SIRIUS devices in the industrial DIN-rail enclosure
Removable terminals Screw terminals
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Coupling relays
SIRIUS 3RQ1 force-guided coupling relays, fail-safe up to SIL 3/PL e NEW NEU
3ZY1321-2AA00
Push-in lugs 3ZY1311-0AA00 1 10 units 41L
For wall mounting
5
3ZY1311-0AA00
Coding pins 3ZY1440-1AA00 1 12 units 41L
For removable terminals of SIRIUS devices
in the industrial DIN-rail enclosure;
they enable the mechanical coding of terminals,
3ZY1440-1AA00 see Equipment Manual.
Hinged cover
Replacement cover, without terminal labeling, yellow
• 17.5 mm wide 3ZY1450-1BA00 1 5 units 41L
• 22.5 mm wide 3ZY1450-1BB00 1 5 units 41L
3ZY1450- 3ZY1450-
1BA00 1BB00
Blank labels
Unit labeling plates1)
For SIRIUS devices
• 17.5 mm: 10 mm x 7 mm, titanium gray 3RT2900-1SB10 100 816 units 41B
• 22.5 mm: 20 mm x 7 mm, titanium gray 3RT2900-1SB20 100 340 units 41B
IC01_00181
3RT2900-1SB20
Tools for opening spring-loaded terminals
Screwdriver Spring-loaded terminals
For all SIRIUS devices with spring-loaded terminals (push-in)
3.0 mm x 0.5 mm, 3RA2908-1A 1 1 unit 41B
length approx. 200 mm,
titanium gray/black,
3RA2908-1A partially insulated
1)
PC labeling system for individual inscription of
unit labeling plates available from:
murrplastik Systemtechnik GmbH
(see page 16/18).
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Coupling relays
SIRIUS 3RQ2 coupling relays with industrial enclosure
■ Overview
More information
Homepage, see www.siemens.com/sirius-coupling-relays
Industry Mall, see www.siemens.com/product?3RQ2
TIA Selection Tool Cloud (TST Cloud), see
www.siemens.com/tstcloud/?node=SIRIUSRelais
Conversion tool, see www.siemens.com/conversion-tool
3RQ2 coupling relays in their 22.5 mm industrial enclosure serve
to couple control signals to and from a controller and replace
the 3RS18 coupling relays. The 3RQ2 has an impressively
high-quality industrial enclosure finished in modern titanium
gray so that it fits in visually with the SIRIUS series of relays.
The series consists of devices with up to three changeover
contacts with screw or spring-loaded terminals (push-in) and,
with its wide voltage range from 24 to 240 V AC/DC, is a genuine
highlight in the coupling relay market.
5
Thanks to terminal assignment that is identical to the previous
version, existing products can easily be converted.
SIRIUS 3RQ2 coupling relay, screw terminals, 3 changeover contacts
The reduced variety of components simplifies product selection
and standardization.
Numerous accessories are available for the 3RQ2 coupling
relays, for example replacement terminals, push-in lugs for wall
mounting and coding pins.
Article number scheme
Product versions Article number
Coupling relays, standard 3RQ2000 – @ @ @ 0 @
Connection methods Screw terminals 1
Spring-loaded terminals (push-in) 2
Outputs 1 CO contact A
2 CO contacts B
3 CO contacts C
Rated control supply voltage 24 ... 240 V AC/DC W
Material of switching contacts 0 = AgSnO2 0
1 = AgNi + Au 1
Example 3RQ2000 – 1 C W 0 1
Note:
The article number scheme shows an overview of product versions For your orders, please use the article numbers quoted
for better understanding of the logic behind the article numbers. in the selection and ordering data.
■ Benefits
• Permanent wiring thanks to removable terminals in screw • Reduced costs thanks to fewer versions
or spring-loaded technology (push-in) • Especially high contact reliability even at low currents thanks
• Replacement of individual terminals minimizes wiring effort to versions with hard gold-plated contacts
• A product for all voltages from 24 to 240 V AC/DC • International standards and certifications including CE,
UL/CSA, EAC, railway approvals, and more
■ Application
• Electrical separation between the input and output circuit • Signal amplification
• Adjustment of different signal levels • Contact multiplication
Electronic
I/O control
devices 110 V AC 110 V AC Actuators
Output
230 V AC
Input
24 V DC 24 V DC 230 V AC
M
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Coupling relays
SIRIUS 3RQ2 coupling relays with industrial enclosure
■ Technical specifications
More information
Technical specifications, see Operating Instructions, see
https://support.industry.siemens.com/cs/ww/en/ps/25158/td https://support.industry.siemens.com/cs/ww/en/ps/25158/man
D
W
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Coupling relays
SIRIUS 3RQ2 coupling relays with industrial enclosure
5
3RQ2000- 3RQ2000-
1CW00 2CW00
■ Accessories
More information
Operating Instructions, see Conversion tool, see www.siemens.com/conversion-tool
https://support.industry.siemens.com/cs/ww/en/ps/25158/man
3ZY1450-1AB00
Push-in lugs 3ZY1311-0AA00 1 10 units 41L
For wall mounting
3ZY1311-0AA00
Coding pins 3ZY1440-1AA00 1 12 units 41L
For removable terminals of SIRIUS devices
in the industrial DIN-rail enclosure;
3ZY1440-1AA00 they enable the mechanical coding of terminals
Blank labels
Unit labeling plates 3RT2900-1SB20 100 340 units 41B
For SIRIUS devices
20 mm x 7 mm, titanium gray1)
IC01_00181
3RT2900-1SB20
Tools for opening spring-loaded terminals
Screwdriver Spring-loaded terminals
For all SIRIUS devices with spring-loaded terminals (push-in)
3.0 mm x 0.5 mm, length approx. 200 mm, 3RA2908-1A 1 1 unit 41B
titanium gray/black, partially insulated
3RA2908-1A
1) PC labeling system for individual inscription of murrplastik Systemtechnik GmbH
unit labeling plates available from: (see page 16/18).
* You can order this quantity or a multiple thereof.
Illustrations are approximate Siemens IC 10 · 2023 5/31
© Siemens 2023
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Coupling relays
SIRIUS 3RQ2 coupling relays with industrial enclosure
■ More information
Code conversion table
SIRIUS 3RS18 coupling relays Comparison type SIRIUS 3RQ2 coupling relays
Screw terminals Spring-loaded Version Contacts Screw terminals Spring-loaded Version Contacts
terminals terminals
(push-in)
3RS1800-1AQ00 3RS1800-2AQ00 24 V AC/DC; 110 ... 120 V AC 1 CO 3RQ2000-1AW00 3RQ2000-2AW00 24 ... 240 V AC/DC 1 CO
3RS1800-1AP00 3RS1800-2AP00 24 V AC/DC; 220 ... 240 V AC contact contact
3RS1800-1BW00 3RS1800-2BW00 24 ... 240 V AC/DC 2 CO 3RQ2000-1BW00 3RQ2000-2BW00 24 ... 240 V AC/DC 2 CO
3RS1800-1BQ00 3RS1800-2BQ00 24 V AC/DC; 110 ... 120 V AC contacts contacts
3RS1800-1BP00 3RS1800-2BP00 24 V AC/DC; 220 ... 240 V AC
3RS1800-1HW00 3RS1800-2HW00 24 ... 240 V AC/DC 3 CO 3RQ2000-1CW00 3RQ2000-2CW00 24 ... 240 V AC/DC 3 CO
3RS1800-1HQ00 3RS1800-2HQ00 24 V AC/DC; 110 ... 120 V AC contacts contacts
3RS1800-1HP00 3RS1800-2HP00 24 V AC/DC; 220 ... 240 V AC
3RS1800-1HW01 3RS1800-2HW01 24 ... 240 V AC/DC 3 CO 3RQ2000-1CW01 3RQ2000-2CW01 24 ... 240 V AC/DC 3 CO
24 V AC/DC; 110 ... 120 V AC contacts, contacts,
5
3RS1800-1HQ01 3RS1800-2HQ01
hard gold- hard gold-
3RS1800-1HP01 3RS1800-2HP01 24 V AC/DC; 220 ... 240 V AC plated plated
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Coupling relays
SIRIUS 3RQ3 coupling relays, narrow design
■ Overview
Coupling relays with relay output (not plug-in)
AC and DC operation
IEC 60947-5-1
The input and output coupling relays differ with regard to the
positioning of the terminals and the LEDs.
Coupling relays with plug-in relays
AC and DC operation
IEC 60947-1
The coupling relays are plug-in, so the relay can be replaced
quickly at the end of its service life without detaching the wiring.
Coupling relays with semiconductor output (not plug-in)
AC and DC operation
5
IEC 60947-1, EN 60664-1 and EN 50005;
coupling relays with semiconductor output: EN 60747-5;
SIRIUS 3RQ3 coupling relays programmable logic controllers: IEC 61131-2
More information The input and output coupling relays differ with regard to the
Homepage, see www.siemens.com/sirius-coupling-relays positioning of the terminals and the LEDs.
Industry Mall, see www.siemens.com/product?3RQ3 The coupling relays with semiconductor output have extremely
TIA Selection Tool Cloud (TST Cloud), see high contact reliability, so they are especially suitable for
www.siemens.com/tstcloud/?node=SIRIUSRelais solid-state systems.
Conversion tool, see www.siemens.com/conversion-tool
For test purposes, versions are available with manual-off-
SIRIUS 3RQ3 coupling relays in narrow design are used for automatic switches.
coupling control signals from and to a controller, and they are
available in different versions:
• Coupling relays with relay output (not plug-in)
• Coupling relays with plug-in relays
• Coupling relays with semiconductor output (not plug-in)
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Coupling relays
SIRIUS 3RQ3 coupling relays, narrow design
Article number schemes
Product versions Article number
Coupling relays with relay output (not plug-in) 3RQ30 @ 8 – @ A @ 0 @
Design and type of output Output coupler, without manual-off-automatic 1
switch
Input coupler 3
Type of electrical connection Screw terminals 1
Spring-loaded terminals (push-in) 2
Control supply voltage 24 V AC/DC B
115 V AC/DC E
230 V AC/DC F
Material of switching e.g.
contacts 0 = AgSnO2 @
1 = AgSnO2 hard gold-plated @
Example 3RQ30 1 8 – 1 A B 0 1
5
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Coupling relays
SIRIUS 3RQ3 coupling relays, narrow design
■ Benefits
General Coupling relays with relay output (not plug-in)
• All versions with screw terminals or spring-loaded terminals • Relays fixed in enclosure for increased contact reliability
(push-in technology) • Device variants with hard gold-plated contacts, hence high
• TOP wiring with spring-loaded terminals (push-in) for quick contact reliability at low currents
and reliable wiring
Coupling relays with plug-in relays
• Low space requirements in the control cabinet thanks to a
consistent width of 6.2 mm • Fast replacement of the relays with existing wiring
• Reduced stock-keeping due to fewer variants • Shorter installation times thanks to certified complete units
• Clearly visible functional state of the coupling relay by green • Individual relays available as spare parts
LED • Device variants with hard gold-plated contacts, hence high
• Integrated reverse polarity protection and EMC suppressor contact reliability at low currents
diode Coupling relays with semiconductor output (not plug-in)
• Standardized accessories across the entire 3RQ3 series • Long service life since there is no mechanical wear
• Universal bridging option using connecting combs for all • High switching frequency thanks to short make-break times
5
terminals
• Vibration-resistant
• Galvanic isolation plate for isolating different voltages for
neighboring units • No contact bounce
• Clip-on labels available as set for individual labeling • Extremely high contact reliability
• Noise-free switching
• Low control power required
• Switching of DC and capacitive loads
Note:
With semiconductors, the switching current is not dependent
on the inductance of the load, i.e. the switching current for an
inductive DC-13 load is the same as that for a DC-12 load.
This means that coupling links with a semiconductor output are
particularly suitable for inductive loads such as solenoid valves.
It is not relevant to specify the number of operating cycles,
because this does not affect the endurance of the semiconductor,
provided it is not overheated.
■ Application
• Electrical separation between the input and output circuit
• Adjustment of different signal levels
• Signal amplification
Electronic
I/O control
devices 110 V AC 110 V AC Actuators
Output
230 V AC
Input
24 V DC 24 V DC 230 V AC
M
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Coupling relays
SIRIUS 3RQ3 coupling relays, narrow design
■ Technical specifications
More information
Technical specifications, see Operating Instructions, see
https://support.industry.siemens.com/cs/ww/en/ps/16198/td https://support.industry.siemens.com/cs/ww/en/ps/16198/man
FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/16198/faq
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Coupling relays
SIRIUS 3RQ3 coupling relays, narrow design
Coupling relays with plug-in relays
Article number 3RQ3118- 3RQ3118- 3RQ3118- 3RQ3118- 3RQ3118- 3RQ3118- 3RQ3118- 3RQ3118-
.AB00 .AB01 .AE00 .AE01 .AF00 .AF01 .AM00 .AM01
General technical specifications
Width x height x depth mm 6.2 x 93 x 76
D
W
5
Version of the fuse link required for short-circuit Fuse gG: 4 A
protection of the auxiliary switch
Operational current of the auxiliary contacts
• At AC-15
- At 24 V A 3
- At 250 V A 3
• At DC-13
- At 24 V A 1
- At 125 V A 0.2
- At 250 V A 0.1
Contact reliability of the auxiliary contacts 17 V, 5 V, 17 V, 5 V, 17 V, 5 V, 17 V, 5 V,
(one contact failure per 100 million) 5 mA 1 mA 5 mA 1 mA 5 mA 1 mA 5 mA 1 mA
Mechanical endurance (operating cycles) typical 10 000 000
Electrical endurance (operating cycles) for AC-15 100 000
at 250 V typical
Operating range factor of the control supply
voltage, rated value
• At AC
- At 50 Hz 0.8 ... 1.25 0.8 ... 1.1 --
- At 60 Hz 0.8 ... 1.25 0.8 ... 1.1 --
• At DC 0.8 ... 1.25 0.8 ... 1.1 0.8 ... 1.25
Active power input W 0.3 0.5 1 0.3
Thermal current A 6
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Coupling relays
SIRIUS 3RQ3 coupling relays, narrow design
Coupling relays with semiconductor output (not plug-in)
Article number 3RQ3050- 3RQ3052- 3RQ3052- 3RQ3052- 3RQ3053- 3RQ3055- 3RQ3065- 3RQ3070- 3RQ3070-
.SM50 .SM30 .SM40 .SM50 .SG30 .SM30 .SM30 .SB30 .SG30
General technical specifications
Width x height x mm 6.2 x 93 x 72.5 6.2 x 93 x 6.2 x 93 x 72.5
depth 75
H
semiconductor output
• At AC V -- 20 ... 264 --
• At DC V 10 ... 60 10 ... 30 10 ... 60 -- 10 ... 30
Current-carrying capacity of the
semiconductor output
• At AC -- 5 mA ... 2 A --
• At DC 1 mA ... 0.5 A 5 mA ... 2 A 1 mA ... 2 A -- 1 mA ... 3 A 5 mA ... 5 A 10 mA ... 0.5 A
Operating range factor of the
control supply voltage, rated value
• At AC
- At 50 Hz -- 0.7 ... 1.1 -- 1 ... 1 0.7 ... 1.1
- At 60 Hz -- 0.7 ... 1.1 -- 1 ... 1 0.7 ... 1.1
• At DC 1 ... 1 0.7 ... 1.1 1 ... 1 0.7 ... 1.1
Active power input W 0.3 0.25 0.3 0.5
Thermal current A 0.5 2 3 5 0.5
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Coupling relays
SIRIUS 3RQ3 coupling relays, narrow design
5
2.... 110 1 AgSnO2 -- 3RQ3018-2AN08-0AA0 1 5 units 41H
AgSnO2 Yes NEW NEU
3RQ3018-2AN08-0AX0
Input coupling links
AC/DC 24 24 24 1 AgSnO2 -- 3RQ3038-@AB00 1 5 units 41H
AgSnO2 -- 3RQ3038-@AB01 1 5 units 41H
Hard gold-
plated
115 115 115 1 AgSnO2 -- 3RQ3038-@AE00 1 5 units 41H
AgSnO2 -- 3RQ3038-@AE01 1 5 units 41H
Hard gold-
plated
230 230 230 1 AgSnO2 -- 3RQ3038-@AF00 1 5 units 41H
AgSnO2 -- 3RQ3038-@AF01 1 5 units 41H
Hard gold-
plated
Coupling relays with plug-in relays
Output coupling links
AC/DC 24 24 24 1 AgSnO2 -- 3RQ3118-@AB00 1 5 units 41H
AgSnO2 -- 3RQ3118-@AB01 1 5 units 41H
Hard gold-
plated
115 115 115 1 AgSnO2 -- 3RQ3118-@AE00 1 5 units 41H
AgSnO2 -- 3RQ3118-@AE01 1 5 units 41H
Hard gold-
plated
3RQ3118- 230 230 230 1 AgSnO2 -- 3RQ3118-@AF00 1 5 units 41H
2....
AgSnO2 -- 3RQ3118-@AF01 1 5 units 41H
Hard gold-
plated
DC -- -- 24 1 AgSnO2 -- 3RQ3118-@AM00 1 5 units 41H
AgSnO2 -- 3RQ3118-@AM01 1 5 units 41H
Hard gold-
plated
Type of electrical connection
• Screw terminals 1
• Spring-loaded terminals (push-in) 2
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Coupling relays
SIRIUS 3RQ3 coupling relays, narrow design
Type of Control supply voltage Current-carrying capacity Operating Article No. Price PU PS* PG
voltage of the semiconductor mode per PU (UNIT,
output selectable SET, M)
at AC at DC at AC at DC via switch
position
at at
50 Hz 60 Hz
2SM50 AC/DC 110 ... 110 ... 110 ... -- 1 mA ... 3 A -- 3RQ3053-@SG30 1 5 units 41H
230 V 230 V 230 V
Input coupling links
AC/DC 11 ... 11 ... 11 ... -- 10 mA ... -- 3RQ3070-@SB30 1 5 units 41H
30 V 30 V 30 V 0.5 A
110 ... 110 ... 110 ... -- 10 mA ... -- 3RQ3070-@SG30 1 5 units 41H
230 V 230 V 230 V 0.5 A
Type of electrical connection
• Screw terminals 1
• Spring-loaded terminals (push-in) 2
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Coupling relays
SIRIUS 3RQ3 coupling relays, narrow design
■ Accessories
Version Article No. Price PU PS* PG
per PU (UNIT,
SET, M)
3RQ3900-0A
Connecting combs
For linking the same potentials,
current carrying capacity for infeed max. 6 A
5
• 2-pole 3RQ3901-0A 1 10 units 41H
3RQ3901-0B
• 4-pole 3RQ3901-0B 1 10 units 41H
• 8-pole 3RQ3901-0C 1 10 units 41H
• 16-pole 3RQ3901-0D 1 10 units 41H
Clip-on labels1)
For terminal and equipment labeling, white
• 5 x 5 mm 3RQ3902-0A 100 2000 units 41H
• 6 x 12 mm (for 3RQ31 only) 3RQ3902-0B 100 1200 units 41H
3RQ3902-0A
Tools for opening spring-loaded terminals
Screwdriver Spring-loaded terminals
For all SIRIUS devices with spring-loaded terminals (push-in)
3.0 mm x 0.5 mm, 3RA2908-1A 1 1 unit 41B
length approx. 200 mm,
titanium gray/black,
3RA2908-1A partially insulated
1) PC labeling system for individual inscription of unit labeling
plates available from:
Conta-Clip Verbindungstechnik GmbH
(see page 16/18).
Coupling relays Control Material of switching Number Article No. Price PU PS* PG
with plug-in supply contacts of CO per PU (UNIT,
relays voltage contacts SET, M)
for
auxiliary
contacts
Type V
Replacement modules for 3RQ3118 coupling relays with plug-in relays
3RQ3118-.AM00 24 DC AgSnO2 1 3TX7014-7BM00 1 15 units 41H
3RQ3118-.AM01 AgSnO2 3TX7014-7BM02 1 15 units 41H
Hard gold-plated
3RQ3118-.AB00 24 AC/DC AgSnO2 1 3TX7014-7BM00 1 15 units 41H
3RQ3118-.AB01 AgSnO2 3TX7014-7BM02 1 15 units 41H
Hard gold-plated
3RQ3118-.AE00 115 AC/DC AgSnO2 1 3TX7014-7BP00 1 20 units 41H
3RQ3118-.AF00 230 AC/DC AgSnO2
3RQ3118-.AE01 115 AC/DC AgSnO2 1 3TX7014-7BP02 1 20 units 41H
Hard gold-plated
3RQ3118-.AF01 230 AC/DC AgSnO2
Hard gold-plated
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Coupling relays
LZS coupling relays with plug-in relays
■ Overview
Logical separation
More information
Homepage, see www.siemens.com/sirius-coupling-relays The terminals for the contacts and the terminals for the coil are
arranged on separate levels, e.g. above for contacts and below
Industry Mall, see www.siemens.com/product?3RQ_3RS_LZ
for coil. Logical separation is not necessarily protective
TIA Selection Tool Cloud (TST Cloud), see separation.
www.siemens.com/tstcloud/?node=SIRIUSRelais
LZS coupling relays with plug-in relays can be ordered as Protective separation
complete units or as individual modules for customer assembly. For protective separation, transfer of the voltage of one circuit to
another circuit is prevented to a suitable degree of safety
Function
(requirements and tests are described in IEC 60947-1 in Annex N).
The coupling relays with semiconductor output have low power
consumption and are therefore particularly well-suited to solid- Notes on the previous LZX series
state systems. In the versions equipped with LEDs, these The lower-cost complete units of the LZS series are fully
indicate the switching state. The LZS:PT/MT coupling relays compatible with the corresponding complete units of the
have a test button. This can be used to force the relays into the previous LZX series.
switching state and to lock it without electrical control. This is
indicated by a raised petrol-colored lever. The LZX plug-in relays are available unchanged and are used
5
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Coupling relays
LZS coupling relays with plug-in relays
■ Technical specifications
More information
Technical specifications, see Manuals, see
https://support.industry.siemens.com/cs/ww/en/ps/16204/td https://support.industry.siemens.com/cs/ww/en/ps/16204/man
Relay type LZX:RT print relay, 8-pole, LZX:PT industrial relay, 8-, 11- and 14-pole,
(12.7 mm) 1 CO/2 CO (22.5 mm) 2 CO/3 CO/4 CO
General data
Dimensions (W x H x D)
• LZS:RT.A4/LZS:PT.A5 mm 15.5 x 78 x 71 28 x 74 x 72
H
• LZS:RT.B4/LZS:PT.B5 mm 15.5 x 77 x 71 28 x 77 x 79
• LZS:RT.D4/LZS:PT.D5 mm 15.5 x 98 x 71 28 x 98 x 79
D
5
(Pollution degree 3)
Overvoltage category III
According to IEC 60664-1
Protective separation Up to 250 V (with plug-in socket LZS:RT78726) No
Between coil and contacts No (for complete units with standard socket)
According to IEC 60947-1, Annex N
Degree of protection
• Relays IP67 IP50
• Bases IP20
Permissible ambient temperature
• During operation °C -40 ... +70
• During storage °C -40 ... +80
Conductor cross-sections
Connection type Screw terminals
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Coupling relays
LZS coupling relays with plug-in relays
Relay type LZX:RT print relay, 8-pole, LZX:PT industrial relay, 8-, 11- and 14-pole,
(12.7 mm) 1 CO/2 CO (22.5 mm) 2 CO/3 CO/4 CO
Rated control supply voltage Us1) V 24 DC 24 AC 115 AC 230 AC 24 DC 24 AC 115 AC 230 AC
Control side
Operating range factor 0.9 ... 1.4 0.9 ... 1.1 0.9 ... 1.4 0.9 ... 1.1
Power consumption at Us
• AC VA -- 0.75 -- 1
• DC W 0.4 -- 0.75 --
Release voltage V 2.4 3.6 17.3 34.5 2.4 7.2 34.5 69
Protection circuit Freewheel- -- Freewheel- --
ing diode ing diode
for com- in LED
plete unit module
Load side
Switching voltage
AC/DC V 24 ... 250
Rated currents2)
5
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Coupling relays
LZS coupling relays with plug-in relays
D
W
5
• Bases IP20
Permissible ambient temperature
• During operation °C -40 ... +60 -45 ... +50
• During storage °C -45 ... +80
Conductor cross-sections
Connection type Screw terminals
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Coupling relays
LZS coupling relays with plug-in relays
Note:
Logical separation: The terminals for the contacts and the
terminals for the coil are arranged on separate levels, e.g. above
for contacts and below for the coil. Logical separation is not
necessarily protective separation.
Protective separation: Protective separation prevents voltage
of one circuit affecting another circuit with sufficient protection
(IEC 61140).
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Coupling relays
LZS coupling relays with plug-in relays
Version Rated control supply Contacts, Width Article No. Price PU PS* PG
voltage Us number of per PU (UNIT,
at 50/60 Hz AC CO SET, M)
contacts
V mm
Individual modules for customer assembly, PT series
Industrial relays, 8-, 11-, and 14-pole
Mini industrial relays
• With test bracket and mechanical
switch position indicator, without LED1)
24 DC 2 22.5 LZX:PT270024 1 1 unit 41H
3 LZX:PT370024 1 1 unit 41H
4 LZX:PT570024 1 1 unit 41H
LZX:PT370024 24 AC 2 22.5 LZX:PT270524 1 1 unit 41H
3 LZX:PT370524 1 1 unit 41H
4 LZX:PT570524 1 1 unit 41H
115 AC 2 22.5 LZX:PT270615 1 1 unit 41H
3 LZX:PT370615 1 1 unit 41H
5
4 LZX:PT570615 1 1 unit 41H
230 AC 2 22.5 LZX:PT270730 1 1 unit 41H
3 LZX:PT370730 1 1 unit 41H
4 LZX:PT570730 1 1 unit 41H
• With hard gold-plating
24 DC 4 22.5 LZX:PT580024 1 1 unit 41H
230 AC LZX:PT580730 1 1 unit 41H
• Without test bracket
24 DC 4 22.5 LZX:PT520024 1 1 unit 41H
230 AC LZX:PT520730 1 1 unit 41H
Plug-in sockets for PT relays
Standard plug-in sockets Screw terminals
For mounting on TH 35 DIN rail
-- 2 28 LZS:PT78720 1 1 unit 41H
3 LZS:PT78730 1 1 unit 41H
4 LZS:PT78740 1 1 unit 41H
LZS:PT78740
Plug-in sockets with logical separation
For mounting on TH 35 DIN rail
-- 2 28 LZS:PT78722 1 1 unit 41H
4 LZS:PT78742 1 1 unit 41H
LZS:PT78722
Plug-in sockets with logical separation Plug-in terminals
For mounting on TH 35 DIN rail (push-in)
-- 2 28 LZS:PT7872P 1 1 unit 41H
4 LZS:PT7874P 1 1 unit 41H
LZS:PT7874P
1)
The test bracket is designed to be non-latching. If the test bracket is
pressed further until 90° has been reached, two small lugs break off and
the test bracket can be latched in position.
Note:
Logical separation: The terminals for the contacts and the
terminals for the coil are arranged on separate levels, e.g. above
for contacts and below for the coil. Logical separation is not
necessarily protective separation.
Protective separation: Protective separation prevents voltage
of one circuit affecting another circuit with sufficient protection
(IEC 61140).
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Coupling relays
LZS coupling relays with plug-in relays
Version Rated control supply Contacts, Width Article No. Price PU PS* PG
voltage Us number of per PU (UNIT,
at 50/60 Hz AC CO SET, M)
contacts
V mm
Individual modules for customer assembly, PT series
More individual modules
LED modules
• Red
- With freewheeling 24 DC -- 12.5 LZS:PTML0024 1 1 unit 41H
diode
LZS:PTML0024 - Without 24 AC/DC LZS:PTML0524 1 1 unit 41H
freewheeling diode 110 … 230 AC LZS:PTML0730 1 1 unit 41H
• Green
- With freewheeling 24 DC -- 12.5 LZS:PTMG0024 1 1 unit 41H
diode
- Without 24 AC/DC LZS:PTMG0524 1 1 unit 41H
freewheeling diode 110 … 230 AC LZS:PTMG0730 1 1 unit 41H
LZS:PT17021
5
LZS:MT78750
Note:
Logical separation: The terminals for the contacts and the
terminals for the coil are arranged on separate levels, e.g. above
for contacts and below for the coil. Logical separation is not
necessarily protective separation.
Protective separation: Protective separation prevents voltage of
one circuit affecting another circuit with sufficient protection
(IEC 61140).
SITOP DC power supplies such as 6EP1331-5BA00 or
6EP1331-5BA10 can be used for unavailable coil voltages,
see page 15/1 or Catalog KT 10.1.
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Coupling relays
LZS coupling relays with plug-in relays
Version Rated control supply Contacts, Width Article No. Price PU PS* PG
voltage Us number of per PU (UNIT,
at 50/60 Hz AC CO SET, M)
contacts
V mm
Complete units, 8-pole, 5 mm pinning, RT series
Complete units with standard plug-in socket Screw terminals
For snap-on mounting on TH 35 DIN rail
Comprising:
• Coupling relays with plug-in relays
• Standard plug-in socket with screw terminals
• LED module (24 V DC version: LED module with freewheeling diode)
• Fixing/ejection brackets
• Labels
1 CO contact 24 DC 1 15.5 LZS:RT3A4L24 1 5 units 41H
24 AC LZS:RT3A4R24 1 5 units 41H
LZS:RT4A4T30 115 AC LZS:RT3A4S15 1 5 units 41H
230 AC LZS:RT3A4T30 1 5 units 41H
2 CO contacts 24 DC 2 15.5 LZS:RT4A4L24 1 5 units 41H
24 AC LZS:RT4A4R24 1 5 units 41H
5
115 AC LZS:RT4A4S15 1 5 units 41H
230 AC LZS:RT4A4T30 1 5 units 41H
Complete units with plug-in socket
With logical separation
For snap-on mounting on TH 35 DIN rail
Comprising:
• Coupling relays with plug-in relays
• Plug-in socket with logical separation and screw terminals
• LED module (24 V DC version: LED module with freewheeling diode)
• Fixing/ejection brackets
• Labels
1 CO contact 24 DC 1 15.5 LZS:RT3B4L24 1 5 units 41H
24 AC LZS:RT3B4R24 1 5 units 41H
LZS:RT4B4T30 115 AC LZS:RT3B4S15 1 5 units 41H
230 AC LZS:RT3B4T30 1 5 units 41H
2 CO contacts 24 DC 2 15.5 LZS:RT4B4L24 1 5 units 41H
24 AC LZS:RT4B4R24 1 5 units 41H
115 AC LZS:RT4B4S15 1 5 units 41H
230 AC LZS:RT4B4T30 1 5 units 41H
Complete units with plug-in socket Plug-in terminals
With logical separation (push-in)
For snap-on mounting on TH 35 DIN rail
Comprising:
• Coupling relays with plug-in relays
• Plug-in socket with logical separation and plug-in terminals (push-in)
• LED module (24 V DC version: LED module with freewheeling diode)
• Fixing/ejection brackets
• Labels
1 CO contact 24 DC 1 15.5 LZS:RT3D4L24 1 5 units 41H
24 AC LZS:RT3D4R24 1 5 units 41H
LZS:RT3D4L24 115 AC LZS:RT3D4S15 1 5 units 41H
230 AC LZS:RT3D4T30 1 5 units 41H
2 CO contacts 24 DC 2 15.5 LZS:RT4D4L24 1 5 units 41H
24 AC LZS:RT4D4R24 1 5 units 41H
115 AC LZS:RT4D4S15 1 5 units 41H
230 AC LZS:RT4D4T30 1 5 units 41H
Note:
Logical separation: The terminals for the contacts and the
terminals for the coil are arranged on separate levels, e.g. above
for contacts and below for the coil. Logical separation is not
necessarily protective separation.
Protective separation: Protective separation prevents voltage
of one circuit affecting another circuit with sufficient protection
(IEC 61140).
Switching devices – Contactors and contactor assemblies – Contactor relays and relays
Coupling relays
LZS coupling relays with plug-in relays
LZS:PTML0024
Fixing/ejection brackets
For RT base
-- -- 15.5 LZS:RT17016 100 10 units 41H
Labels
-- -- 15.5 LZS:RT17040 100 10 units 41H
LZS:RT17016
RC elements
6 ... 60 AC -- 15.5 LZS:PTMU0524 1 1 unit 41H
110 ... 230 AC LZS:PTMU0730 1 1 unit 41H
Freewheeling diodes with connection to A1
LZS:RT17040
6 … 230 DC -- 15.5 LZS:PTMT00A0 1 1 unit 41H
Connecting combs for RT screw base
8-pole, -- -- -- LZS:RT170R8 1 10 units 41H
10 A current-carrying
capacity, natural-colored
LZS:PTMU0730 Connecting brackets for push-in base
2-pole, -- -- -- LZS:RT170P1 100 10 units 41H
10 A current-carrying
capacity, natural-colored
Note:
SITOP DC power supplies such as 6EP1331-5BA00 or
6EP1331-5BA10 can be used for unavailable coil voltages,
see page 15/1 or Catalog KT 10.1.
6
3RW52 soft starters SIRIUS 3RF29 function modules
6/55 - General data 6/150 General data
6/67 - Standard (inline) circuit 6/152 SIRIUS converters for 3RF2
6/69 - Inside-delta circuit
6/71 - Accessories 6/153 SIRIUS load monitoring for 3RF2
Basic Performance soft starters 6/154 SIRIUS heating current monitoring
for 3RF2
3RW50 soft starters
6/73 - General data 6/155 SIRIUS power controllers for 3RF2
6/81 - Standard (inline) circuit 6/157 SIRIUS power regulators for 3RF2
6/82 - Accessories
SIRIUS 3RF34 solid-state switching
3RW40 soft starters
devices for switching motors
6/84 - General data
6/92 - Standard (inline) circuit Solid-state contactors
6/94 - Accessories 6/159 General data
3RW30 soft starters 6/162 SIRIUS 3RF34 solid-state contactors,
6/96 - General data 3-phase
6/103 - Standard (inline) circuit 6/165 SIRIUS 3RF34 solid-state reversing
6/104 - Accessories contactors, 3-phase
Spare parts
6/106 For 3RW55
6/110 For 3RW55 Failsafe
6/112 For 3RW52
6/115 For 3RW50
Software
14/4 Simulation Tool for Soft Starters (STS)
14/5 SIRIUS Soft Starter ES (TIA Portal)
14/8 SIRIUS 3RW soft starter block library for
SIMATIC PCS 7
14/25 SIRIUS Sim
Siemens IC 10 · 2023
© Siemens 2023
Introduction
■ Overview
More information
Homepage, see www.siemens.com/sirius-soft-starter Industry Online Support (SIOS) topic page, see
Industry Mall, see www.siemens.com/product?3RW https://support.industry.siemens.com/cs/ww/en/view/109747404
TIA Selection Tool Cloud (TST Cloud), see Simulation Tool for Soft Starters (STS), see page 6/9 or
www.siemens.com/tstcloud/?node=Sirius3rwFolder https://support.industry.siemens.com/cs/ww/en/view/101494917
Conversion tool, see www.siemens.com/conversion-tool
Introduction
6
• Up to 315 kW at 400 V (can be used in supply systems up to 600 V)
• Hybrid switching technology for minimum power loss and 2-phase motor control
• Soft Torque for reduced mechanical loading and optimum pump stop
• Parameterization using potentiometers
• ATEX/IECEx certification
3RW40 soft starters • Soft starting and stopping 3RW40 6/84
• Current limiting
• Motor overload protection (optionally with thermistor motor protection)
• Up to 55 kW at 400 V (can be used in supply systems up to 600 V)
• Hybrid switching technology for minimum power loss and 2-phase motor control
• ATEX certification
3RW30 soft starters • Soft starting with voltage ramp 3RW30 6/96
• Up to 55 kW at 400 V (can be used in supply systems up to 480 V)
Use of SIRIUS 3RW soft starters in conjunction with IE3 and Decision-making support for motor starting – Starting and
IE4 motors running three-phase asynchronous motors efficiently
Note:
For the use of SIRIUS 3RW soft starters in conjunction with highly
efficient IE3 and IE4 motors, please observe the information on
dimensioning and configuring, see Application Manual.
More information, see page 1/8.
Introduction
More information
Industry Mall, see www.siemens.com/product?3RF Online configurator, see www.siemens.com/sirius/configurators
Conversion tool, see www.siemens.com/conversion-tool
■ Overview
More information
Homepage, see www.siemens.com/sirius-soft-starter Simulation Tool for Soft Starters (STS), see page 6/9 or
Industry Mall, see www.siemens.com/product?3RW https://support.industry.siemens.com/cs/ww/en/view/101494917
TIA Selection Tool Cloud (TST Cloud), see SIRIUS Soft Starter ES (TIA Portal), see page 6/9 or
www.siemens.com/tstcloud/?node=Sirius3rwFolder https://support.industry.siemens.com/cs/ww/en/ps/24230/dl
Industry Online Support (SIOS) topic page, see Decision-making support for motor starting – Starting and running three-phase
https://support.industry.siemens.com/cs/ww/en/view/109747404 asynchronous motors efficiently see www.siemens.com/motorstart-guide
Conversion tool, see www.siemens.com/conversion-tool
High 3RW55 ( 3)
5.5 ... 710/1 200 kW ( 3)
Performance
6
3-phase controlled
3RW55 Failsafe
5.5 ... 315/560 kW ( 3) ( 3)
TIA Integration
General 3RW52
5.5 ... 315/560 kW ( 3)
Performance
( 3)
2-phase controlled
3RW50
Basic 75 ... 315 kW
Performance
3RW40
5.5 ... 55 kW
3RW30
1.5 ... 55 kW
IC01_00698a
Typical
Pumping Ventilating Compressing Conveying Processing
applications
Escalators ● ● ● ●
Piston compressors ● ● ● ●
Screw compressors ● ● ● ●
Small fans1) ● ● ● ●
Centrifugal blowers ● ● ● ●
Bow thrusters ● ● ● ●
6
Voltage ramp ✓ ✓ ✓ ✓ ✓ ✓
Starting voltage % 20 ... 100 20 ... 100 30 ... 100 30 ... 100 40 ... 100 40 ... 100
Ramp-up and ramp-down time s 0 ... 360 0 ... 360 0 ... 20 0 ... 20 0 ... 20 0 ... 203)
Pump stop (torque control)4) ✓ ✓ -- -- -- --
• Starting torque % 10 ... 100 10 ... 100 -- -- -- --
• Torque limit % 20 ... 200 20 ... 200 -- -- -- --
Soft Torque (torque limit) -- -- ✓ ✓ -- --
Integral bypass contact system ✓ ✓ ✓ ✓ ✓ ✓
Intrinsic device protection ✓ ✓ ✓ ✓ ✓ --
Motor overload protection ✓5) ✓5) ✓ ✓5) ✓5) --
Thermistor motor protection evaluation ✓ ✓ ✓6) ✓6) ✓6) --
Analog output ✓ ✓ ✓6) ✓6) -- --
Remote RESET ✓ ✓ ✓ ✓ ✓ --
Adjustable current limiting ✓ ✓ ✓ ✓ ✓ --
Inside-delta circuit1) ✓ ✓ ✓ -- -- --
Breakaway pulse ✓ ✓ -- -- -- --
Automatic parameterization ✓ ✓ -- -- -- --
Pump cleaning ✓ ✓ -- -- -- --
Condition monitoring ✓ ✓ -- -- -- --
User account administration7) ✓ ✓ -- -- -- --
Creep speed in both directions of rotation ✓ -- -- -- -- --
Reversing operation ✓ ✓ -- -- -- --
Reversing DC braking4)8) ✓ -- -- -- -- --
DC braking4)8) ✓ -- -- -- -- --
Dynamic DC braking4)8) ✓ -- -- -- -- --
Motor heating ✓ -- -- -- -- --
Communication function9) ✓ ✓ ✓ ✓ -- --
HMI module installable in the control ✓ ✓ ✓9) ✓9) -- --
cabinet door
Operating measured value display ✓ ✓ ✓9) ✓9) -- --
Logbooks ✓ ✓ ✓9) ✓9) -- --
Statistical data and slave pointer function ✓ ✓ ✓9) ✓9) -- --
Trace function7) ✓ ✓ -- -- -- --
Programmable control inputs and outputs ✓ ✓ -- -- -- --
Number of parameter sets 3 3 1 1 1 1
Parameterizable via software7) ✓ ✓ -- -- -- --
Number of controlled phases 3 3 3 2 2 2
Heavy starting CLASS 304) ✓ ✓ -- -- -- --
5)
✓ Function available When using the motor overload protection according to ATEX/IECEx,
-- Function not available an upstream contactor may be required, see page 6/13.
6) Special device versions only.
1)
Inside-delta circuit only up to operational voltage 600 V. 7)
2) With software Soft Starter ES (TIA Portal).
Note derating above 40 °C. 8)
3) Not possible in inside-delta circuit.
Only soft starting available for 3RW30. 9)
4) Only in conjunction with special accessories.
Calculate soft starter and motor with overdimension where required.
NSB0_01704
The 3RW soft starters should always be designed on the basis
of the required rated operational current of the motor. 100
The selection and ordering data were determined for the following constraints (stand-alone installation without auxiliary fan)
6
Easy and clearly arranged parameter setting of the SIRIUS 3RW44 and
3RW55 soft starters with SIRIUS Soft Starter ES (TIA Portal)
The SIRIUS Soft Starter ES (TIA Portal) software permits quick
Easy input of motor and load data and easy parameterization, monitoring and diagnostics of
The Simulation Tool for Soft Starters (STS) provides a convenient SIRIUS 3RW44 and 3RW5 soft starters for service purposes.
means of designing soft starters using a simple, quick and easy-
6
• Transparent setting of the device functions and their
to-use interface. Entering the motor and load data will simulate parameters – online and offline
the application and prompt suggestions for suitable soft starters.
• Effective diagnostics functions on the soft starter and display
• Simple, quick and user-friendly interface of the most important measured values
• Detailed and up-to-date Siemens motor database, • Trace function (oscilloscope function) for recording measured
including IE3 and IE4 motors. values and events (only in the Professional software version)
• Simulation of heavy starting up to CLASS 30 • Time savings through shorter startup times
• Update-capable (e.g. motors, load types, functions) • Fast, low-cost licensing using a simple licensing procedure
• Fast simulations with minimum input data (also available online)
• Immediate, graphical curve charts of start operations with
limit values
• Table view of suitable soft starters for the application
The Simulation Tool for Soft Starters (STS) is available as a free
download for Windows and as an app (for Android and iOS).
The PCS 7 block library for SIRIUS 3RW soft starter contains The PROFINET High-Feature communications module for
the diagnostics and driver blocks that correspond to the the SIRIUS 3RW55 and SIRIUS 3RW55 Failsafe soft starters
supports the S2 system redundancy mechanisms of
6
6
following the local short-circuit conditions. Fuses and switching
devices must be ordered separately. The harmonic component
load of the starting current must be taken into consideration for
the selection of motor starter protectors/circuit breakers
(selection of release). Please observe the maximum switching
frequencies specified in the technical specifications.
Notes:
When three-phase motors are switched on, voltage drops occur
as a rule on starters of all types (direct-on-line starters, star-delta
Standard (inline) circuit: Rated current Ie corresponds to the rated motor (wye-delta) starters, soft starters). The infeed transformer must
current In, three cables to the motor always be dimensioned such that the voltage dip when starting
the motor remains within the permissible tolerance. If the infeed
transformer is dimensioned with only a small margin, it is best for
L1 NSB0_00425
L2
the control voltage to be supplied from a separate circuit
L3
(independently of the main voltage) in order to avoid the
N potential switching off of the soft starter.
PE
For dimensioning soft starters, we recommend our Simulation Tool
for Soft Starters (STS), see page 6/9 or our Technical Support,
www.siemens.com/support-request.
U2 L2 Recommended parameters for the initial commissioning of
U1 our SIRIUS 3RW soft starters are listed in every report of
T1 T2 our Simulation Tool for Soft Starters (STS). In addition,
V1 our High Performance soft starters provide support by means
L1 V2 of their commissioning wizards.
W2 W1 T3 L3
The types of coordination are indicated in the and in case of a short circuit. The circuit breaker must have an
corresponding tables by the symbols shown on overload release. That is the case for motor starter protectors
orange backgrounds. (e.g. SIRIUS 3RV20).
Feeder tests and results Circuit breakers without an overload release (e.g. SIRIUS 3RV23
motor starter protectors) must not be used because they do not
To keep the scope of feeder tests with SIRIUS 3RW soft starters provide overload protection. The feeder tests for these were
within economically reasonable limits, tests were conducted with therefore not performed. If the motor feeder with SIRIUS 3RW
feeder components (motor starter protectors/circuit breakers, soft starters is configured without a fuse, motor starter protectors
fuses) that cover the greatest number of use cases (different soft must be used that ensure tripping on an overload in all cases.
starter versions depending on, for example, line voltage, type of
circuit, or necessary overdimensioning). For the combined tests Motor protection
that were conducted, the values for the short-circuit breaking If fuses are used to provide protection against overload
capacity Iq in kA were determined and documented. and short circuit of the cables, the motor is protected by
If the short-circuit breaking capacity is the same, of course, the SIRIUS 3RW soft starter. If the constraints (simple starting
smaller motor starter protectors/circuit breakers or fuses can conditions CLASS 10, listed maximum values for starting
also be used for the selected soft starter provided the current, starting time and number of starts per hour) of page 6/8
dimensioning of the short-circuit components is suitable for the are observed, the motor feeders can be configured according to
connected three-phase motor and the line protection for the IEC as described in the section about soft starters (an optional
cables used. For type of coordination "2" (with semiconductor line contactor is not required). If these preconditions are met,
protection), it is also necessary to compare the characteristics the SIRIUS 3RW soft starters are able to trip on overloads to
because the protection function would no longer be completely protect the motor in any case.
ensured if too small a fuse were selected. If the soft starter does In other starting conditions and on heavy starting, the following
not have a motor protection function, the motor protection must must be considered:
also be dimensioned appropriately.
Trip classes
Setting the motor current
Tested fuseless switchgear assemblies comprising SIRIUS 3RW
If circuit breakers with an overload release are used soft starters and motor starter protectors only comply with
(e.g. SIRIUS 3RV20 motor starter protector), we recommend CLASS 10.
activating the motor protection function of the SIRIUS 3RW soft To configure tested motor feeders, for example, for CLASS 20
starter to protect the motor and setting the soft starter to the or CLASS 30, fuses must be used together with SIRIUS 3RW
rated operational current Ie of the motor. We recommend setting soft starters.
the motor starter protector/circuit breaker in such a way that it
provides line protection but does not usually trip before the soft Line contactor
starter when a motor overload occurs. In applications with high starting frequencies or heavy starting
Line protection and motor protection as of CLASS 20, we recommend combining fuses with the use of
a line contactor on the line side so that a motor overload is
Line protection and motor protection are not ensured in all disconnected by the fault signaling contact of the soft starter in
operating cases, depending on: any case (that is, even in rare cases in which disconnection by
• How the motor feeder is constructed (e.g. with fuses or motor the SIRIUS 3RW soft starter is no longer possible due to the
starter protectors/circuit breakers) operating state of the thyristors).
• Whether the SIRIUS 3RW soft starters are operated within
the specification relevant for the tests (IEC 60947-4-2)
• Or whether the documented constraints (see page 6/8)
have been observed
6
ATEX/IECEx chapters of the Equipment Manual for the selected
Avoid impermissibly high cable surface temperatures by soft starter.
correctly dimensioning the cross-sections.
The cable cross-section must be adequately dimensioned.
■ Benefits
Can be flexibly deployed in many applications
Strong portfolio: Intelligent operation:
wide range of matching products concentrated, application-specific functionality
• The right hardware for all requirements, • Can be used in a wide variety of applications:
soft starters for tasks ranging from simple to demanding starting in Basic, Pumping, ventilating, compressing, conveying and processing
General and High Performance versions
• Integrated, self-learning automatic parameterization depending on
• Extensive portfolio for individual expansion: motor starting conditions
Optional HMIs for installation in the device or mounting on the control
cabinet door • Application-specific functionality such as pump cleaning and pump stop
• Energy-efficient switching and mechanical protection of the drive train • Support from tools and data during engineering
thanks to soft starters with hybrid switching technology
• Simulation Tool for Soft Starters for support during product selection
• Low-wear switching extends the service life of the devices
• Very simple, standardized commissioning and configuration via
• Soft starting prevents current peaks, thereby increasing the network Soft Starter ES in TIA Portal
stability
• Integration in the automation system via communication links
• Protection against disturbances in the application:
Mechanical protection for the drive train • Data availability and analysis:
large volumes of data at any time and anywhere, even into MindSphere
■ Overview
More information
Homepage, see www.siemens.com/sirius-soft-starter SIRIUS Soft Starter ES (TIA Portal), see page 6/9 or
Industry Mall, see www.siemens.com/product?3RW55 https://support.industry.siemens.com/cs/ww/en/ps/24230/dl
TIA Selection Tool Cloud (TST Cloud), see SIRIUS 3RW soft starter block library for SIMATIC PCS 7, see page 6/10 or
www.siemens.com/tstcloud/?node=3rw55 https://support.industry.siemens.com/cs/ww/en/view/109770336
Industry Online Support (SIOS) topic page, see Decision-making support for motor starting – Starting and running three-phase
https://support.industry.siemens.com/cs/ww/en/view/109747404 asynchronous motors efficiently, see www.siemens.com/motorstart-guide
Simulation Tool for Soft Starters (STS), see page 6/9 or SIRIUS Sim, see page 6/10 or
https://support.industry.siemens.com/cs/ww/en/view/101494917 https://support.industry.siemens.com/cs/ww/en/view/109763750
Conversion tool, see www.siemens.com/conversion-tool
6
With their modern hybrid switching technology,
the SIRIUS 3RW55 soft starters offer efficient switching
for long-term, energy-saving use.
2 Communications modules
3 Hinged cover
4 Fan covers
5 Terminal covers (size 2 to size 4)
1 6 Push-in lugs for wall mounting
7
IC01_00582d
2 4
SIRIUS 3RW55 High Performance soft starter with accessories (see page 6/37)
■ Benefits
6
Automatic parameterization Extremely easy commissioning and reliability even under changing
load conditions
Hybrid switching technology and 3-phase motor control Minimum power loss and optimum/symmetrical motor control
TIA integration – communications modules optional Efficient configuration and maximum flexibility in automation engineering
Removable HMI with color display, local interface, slot for Maximum flexibility with regard to user interface and intuitive menu guidance
micro SD memory card
Pump stop and torque control Reduced mechanical loading and optimum pump stop control
Certified according to ATEX/IECEx directive Suitable for the starting of explosion-proof motors
System redundancy S2 Simple and straight-forward integration into fault-tolerant automation systems
Direct integration into MindSphere via the OPC UA server Worldwide data availability for optimal plant operation
■ Technical specifications
More information
Technical specifications, see FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/25099/faq
https://support.industry.siemens.com/cs/ww/en/ps/25099/td Simulation Tool for Soft Starters (STS), see page 6/9 or
Equipment Manual, see https://support.industry.siemens.com/cs/ww/en/view/101494917
https://support.industry.siemens.com/cs/ww/en/view/109753752
6
• Above mm 100
• At the side mm 5
• Below mm 75
Installation altitude at height above sea level, m 5 000 2 000 5 000 2 000 5 000 2 000
maximum1)
Degree of protection IP on the front IP20 IP00 (IP20 with cover) IP00
according to IEC 60529
Touch protection on the front Finger-safe for vertical Finger-safe for vertical touching from the front --
according to IEC 60529 touching from the front with cover
Ambient conditions
Ambient temperature
• During operation2) °C -25 ... +60
• During storage and transport °C -40 ... +80 -25 ... +80 -40 ... +80
Environmental category according to IEC 60721
• During operation 3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist),
3S2 (sand must not get into the devices), 3M6
• During storage 1K6 (only occasional condensation), 1C2 (no salt mist),
1S2 (sand must not get into the devices), 1M4
• During transport 2K2, 2C1, 2S1, 2M2 (max. height of fall 0.3 m)
1)
Derating from 1 000 m, see characteristic curve on page 6/8.
2)
Note derating above 40 °C.
6
• 350% IM
- Start-up time 10 s 1/h 13 13 13 13 13
- Start-up time 20 s 1/h 4 4 4 4 4
Heavy starting (CLASS 20E)
Rated motor current IM, Tu = 40/50/60 °C A 13/11.5/10.5 18/15.9/13.8 25/22.3/19.6 29.6/27.2/23.6 33.5/30.5/27.5
ON period = 70%; motor protection activated
• 300% IM
- Start-up time 20 s 1/h 10 10 10 10 10
- Start-up time 40 s 1/h 4 4 4 4 4
• 350% IM
- Start-up time 20 s 1/h 7 7 7 7 7
- Start-up time 40 s 1/h 2.5 2.5 2.5 2.5 2.5
Heavy starting (CLASS 30E)
Rated motor current IM, Tu = 40/50/60 °C A 13/11.5/10.5 18/15.9/13.8 25/22.3/19.6 26/23.6/21.2 29/26/23
ON period = 70%; motor protection activated
• 300% IM
- Start-up time 30 s 1/h 7 7 7 7 7
- Start-up time 60 s 1/h 3 3 3 3 3
• 350% IM
- Start-up time 30 s 1/h 4 4 4 4 4
- Start-up time 60 s 1/h 1.8 1.8 1.8 1.8 1.8
Adjustable rated motor current IM
• Minimum/maximum A 2.5/13 3.5/18 5/25 6.5/32 7.5/38
• Minimum/maximum in inside-delta circuits A 4.3/22.5 6.1/31.1 8.7/43.3 11.3/55.4 13/65.8
• 350% IM
- Start-up time 10 s 1/h 13 13 13 13 13
- Start-up time 20 s 1/h 4 4 4 4 4
Heavy starting (CLASS 20E)
Rated motor current IM, Tu = 40/50/60 °C A 25/22.3/19.6 47/41.6/36.2 63/55.5/50.5 77/68/62 93/82.5/75.5
ON period = 70%; motor protection activated
• 300% IM
- Start-up time 20 s 1/h 10 10 10 10 10
- Start-up time 40 s 1/h 4 4 4 4 4
• 350% IM
- Start-up time 20 s 1/h 7 7 7 7 7
- Start-up time 40 s 1/h 2.5 2.5 2.5 2.5 2.5
Heavy starting (CLASS 30E)
Rated motor current IM, Tu = 40/50/60 °C A 25/22.3/19.6 43.4/38/34.4 53/48/43 68/62/56 82.5/75.5/65
ON period = 70%; motor protection activated
• 300% IM
- Start-up time 30 s 1/h 7 7 7 7 7
- Start-up time 60 s 1/h 3 3 3 3 3
• 350% IM
- Start-up time 30 s 1/h 4 4 4 4 4
- Start-up time 60 s 1/h 1.8 1.8 1.8 1.8 1.8
Adjustable rated motor current IM
• Minimum/maximum A 5/25 10/47 13/63 16/77 19/93
• Minimum/maximum in inside-delta circuits A 8.7/43.3 17.3/81.4 22.5/109 27.7/133 32.9/161
Type 10
3RW5534 3RW5535 3RW5536
Rated operational current Ie A 113 143 171
Power electronics
Load rating with rated operational current Ie
IEC + UL/CSA, individual mounting at 40/50/60 °C, A 113/101/89 143/128/118 171/153/141
AC-53a
Permissible rated motor current and starts/h
Normal starting (CLASS 10A)
Rated motor current IM, Tu = 40/50/60 °C A 113/101/89 143/128/118 171/153/141
ON period = 70%; motor protection activated
• 300% IM
- Start-up time 5 s 1/h 43 43 43
- Start-up time 10 s 1/h 18 18 18
• 350% IM
- Start-up time 5 s 1/h 28 28 28
- Start-up time 10 s 1/h 10 10 10
Normal starting (CLASS 10E)
Rated motor current IM, Tu = 40/50/60 °C A 113/101/89 143/128/118 171/153/141
ON period = 70%; motor protection activated
• 300% IM
- Start-up time 10 s 1/h 21 21 21
- Start-up time 20 s 1/h 8 8 8
6
• 350% IM
- Start-up time 10 s 1/h 13 13 13
- Start-up time 20 s 1/h 4 4 4
Heavy starting (CLASS 20E)
Rated motor current IM, Tu = 40/50/60 °C A 109/97/85 128/113/103 141/129/117
ON period = 70%; motor protection activated
• 300% IM
- Start-up time 20 s 1/h 10 10 10
- Start-up time 40 s 1/h 4 4 4
• 350% IM
- Start-up time 20 s 1/h 7 7 7
- Start-up time 40 s 1/h 2.5 2.5 2.5
Heavy starting (CLASS 30E)
Rated motor current IM, Tu = 40/50/60 °C A 89/81/74 108/98/88 117/105/93
ON period = 70%; motor protection activated
• 300% IM
- Start-up time 30 s 1/h 7 7 7
- Start-up time 60 s 1/h 3 3 3
• 350% IM
- Start-up time 30 s 1/h 4 4 4
- Start-up time 60 s 1/h 1.8 1.8 1.8
Adjustable rated motor current IM
• Minimum/maximum A 23/113 29/143 34/171
• Minimum/maximum in inside-delta circuits A 39.8/195 50.2/247 58.9/296
• 350% IM
- Start-up time 10 s 1/h 13 13 13 13 10 2
- Start-up time 20 s 1/h 4 4 4 4 2 --
Heavy starting (CLASS 20E)
Rated motor current IM, Tu = 40/50/60 °C A 162/146/130 200/180/160 231/207/183 258/230/202 272/254/236 284/262/240
ON period = 70%; motor protection activated
• 300% IM
- Start-up time 20 s 1/h 10 10 10 10 10 10
- Start-up time 40 s 1/h 4 4 4 4 4 4
• 350% IM
- Start-up time 20 s 1/h 7 7 7 7 7 7
- Start-up time 40 s 1/h 2.5 2.5 2.5 2.5 2.5 2.5
Heavy starting (CLASS 30E)
Rated motor current IM, Tu = 40/50/60 °C A 138/122/106 160/140/120 183/159/135 202/174/160 210/190/170 220/200/180
ON period = 70%; motor protection activated
• 300% IM
- Start-up time 30 s 1/h 7 7 7 7 7 7
- Start-up time 60 s 1/h 3 3 3 3 3 3
• 350% IM
- Start-up time 30 s 1/h 4 4 4 4 4 4
- Start-up time 60 s 1/h 1.8 1.8 1.8 1.8 1.8 1.8
Adjustable rated motor current IM
• Minimum/maximum A 42/210 50/250 63/315 74/370 94/470 114/570
• Minimum/maximum in inside-delta circuits A 72.7/363 86.6/433 109.1/545 128.2/640 162.8/814 197.5/987
6
• 350% IM
- Start-up time 10 s 1/h 13 13 10 9 1
- Start-up time 20 s 1/h 4 4 2 2 1
Heavy starting (CLASS 20E)
Rated motor current IM, Tu = 40/50/60 °C A 500/450/400 520/470/420 570/520/470 920/840/760 980/900/810
ON period = 70%; motor protection activated
• 300% IM
- Start-up time 20 s 1/h 10 10 10 10 10
- Start-up time 40 s 1/h 4 4 4 4 4
• 350% IM
- Start-up time 20 s 1/h 7 7 7 7 7
- Start-up time 40 s 1/h 2.5 2.5 2.5 2.5 2.5
Heavy starting (CLASS 30E)
Rated motor current IM, Tu = 40/50/60 °C A 380/340/300 400/360/320 420/380/340 740/670/600 790/720/650
ON period = 70%; motor protection activated
• 300% IM
- Start-up time 30 s 1/h 7 7 7 7 7
- Start-up time 60 s 1/h 3 3 3 3 3
• 350% IM
- Start-up time 30 s 1/h 4 4 4 4 4
- Start-up time 60 s 1/h 1.8 1.8 1.8 1.8 1.8
Adjustable rated motor current IM
• Minimum/maximum A 114/630 144/720 168/840 220/1 100 258/1 280
• Minimum/maximum in inside-delta circuits A 197.5/987 249.4/1 247 291/1 454 381.1/1 905 446.9/2 217
Q1 Q1
Q11 Q11
NSB0_01902
IC01_00544
M M
3~ 3~
Soft starters Motor starter protectors/circuit breakers Motor starter protectors/circuit breakers
for 400 V systems for 500 V systems for 400 V systems for 500 V systems
Q11 Q1 Iq Q1 Iq Q1 Iq Q1 Iq
Type Type kA Type kA Type kA Type kA
Type of Standard (inline) circuit Inside-delta circuit
6
ToC
coordination 1
"1"
3RW5513 3RV2032-4TA10 65 3RV2032-4TA10 18 3RV2032-4DA10 65 3RV2032-4DA10 18
3RW5514 3RV2032-4DA10 65 3RV2032-4DA10 15 3RV2032-4EA10 65 3RV2032-4EA10 15
3RW5515 3RV2032-4EA10 65 3RV2032-4EA10 15 3RV2032-4VA10 65 3RV2032-4VA10 15
3RW5516 3RV2032-4VA10 65 3RV2032-4VA10 10 3RV2032-4JA10 65 3RV2032-4JA10 10
3RW5517 3RV2032-4WA10 65 3RV2032-4WA10 10 3RV2032-4RA10 65 3RV2032-4RA10 10
3RW5521 -- -- -- -- -- -- -- --
3RW5524 3RV2032-4JA10 65 3RV2032-4JA10 10 3RV2032-4RA10 65 3RV2032-4RA10 10
3RW5525 3VA2163-7MN32-0AA0 65 3VA2163-7MN32-0AA0 20 3VA2110-7MN32-0AA0 65 3VA2110-7MN32-0AA0 20
3RW5526 3VA2110-7MN32-0AA0 65 3VA2110-7MN32-0AA0 20 3VA2216-7MN32-0AA0 65 3VA2216-7MN32-0AA0 20
3RW5527 3VA2216-7MN32-0AA0 15 3VA2216-7MN32-0AA0 10 3VA2220-7MN32-0AA0 15 3VA2220-7MN32-0AA0 10
3RW5534 3VA2216-7MN32-0AA0 65 -- -- 3VA2220-7MN32-0AA0 65 -- --
3RW5535 3VA2220-7MN32-0AA0 65 -- -- 3VA2325-7MN32-0AA0 65 -- --
3RW5536 3VA2325-7MN32-0AA0 30 3VA2325-7MN32-0AA0 10 3VA2440-7MN32-0AA0 30 3VA2440-7MN32-0AA0 10
3RW5543 3VA2325-7MN32-0AA0 65 3VA2325-7MN32-0AA0 65 3VA2440-7MN32-0AA0 65 3VA2440-7MN32-0AA0 65
3RW5544 3VA2440-7MN32-0AA0 65 3VA2440-7MN32-0AA0 65 3VA2450-7MN32-0AA0 65 3VA2450-7MN32-0AA0 65
3RW5545 3VA2440-7MN32-0AA0 65 3VA2440-7MN32-0AA0 65 3VA2580-6HN32-0AA0 65 3VA2580-6HN32-0AA0 65
3RW5546 3VA2440-7MN32-0AA0 65 3VA2440-7MN32-0AA0 65 3VA2580-6HN32-0AA0 65 3VA2580-6HN32-0AA0 65
3RW5547 3VA2450-7MN32-0AA0 65 3VA2450-7MN32-0AA0 65 3VA2510-6HN32-0AA0 65 3VA2510-6HN32-0AA0 65
3RW5548 3VA2580-6HN32-0AA0 65 3VA2580-6HN32-0AA0 65 3VA2510-6HN32-0AA0 65 3VA2510-6HN32-0AA0 65
3RW5552 3VA2580-6HN32-0AA0 65 3VA2580-6HN32-0AA0 65 3VA2716-7AB05-0AA0 65 3VA2716-7AB05-0AA0 65
3RW5553 3VA2510-6HN32-0AA0 65 3VA2510-6HN32-0AA0 65 3VA2716-7AB05-0AA0 65 3VA2716-7AB05-0AA0 65
3RW5554 3VA2510-6HN32-0AA0 65 3VA2510-6HN32-0AA0 65 3VA2716-7AB05-0AA0 65 3VA2716-7AB05-0AA0 65
3RW5556 3VA2716-7AB05-0AA0 65 3VA2716-7AB05-0AA0 65 -- -- -- --
3RW5558 3VA2716-7AB05-0AA0 65 3VA2716-7AB05-0AA0 65 -- -- -- --
Note:
The service factor and measurement inaccuracies, for example,
have been taken into account for the selection of the specified
motor starter protectors/circuit breakers; the specified short-
circuit breaking capacities Iq in kA are covered by combination
tests. Smaller motor starter protectors/circuit breakers from the
same series can be used at any time as smaller ones trip more
quickly in the event of a short circuit (unchanged short-circuit
breaking capacity) and thus protect the soft starter in any case.
The dimensioning of the short-circuit components must match
the connected three-phase motor, the short-circuit and overload
requirements of the application, and the line protection for the
cables used.
When using braking functions, the use of fuses is recommended
to avoid the risk of false tripping of 3VA circuit breakers with
electronic motor protection function during braking.
In motor feeder tests with soft starters conducted in 690 V
systems, demonstrable short-circuit breaking capacities could
only be achieved using fuses (Iq > 5 to 10 kA).
F1 F1 F1
IC01_00545a
NSB0_01904
IC01_00565
M M M
3~ 3~ 3~
Soft starters gG class fuse Line contactor (optional) gG class fuse Line contactor (optional)
for systems for systems for systems for systems for systems for systems for systems for systems
6
up to 690 V up to 480 V up to 690 V up to 600 V up to 480 V up to 600 V up to 480 V up to 600 V
in the supply in the supply in the delta in the delta
cable cable
Q11 F1 Q21 Q21 F1 Q21 Q21 Q21 Q21
Type Type Type Type Type Type Type Type Type
Type of ToC Standard (inline) circuit Inside-delta circuit
coordination 1
"1"
3RW5513 3NA3820-6 3RT2025 3RT2025 3NA3820-6 3RT2027 3RT2035 3RT2025 3RT2025
3RW5514 3NA3820-6 3RT2026 3RT2027 3NA3820-6 3RT2027 3RT2037 3RT2026 3RT2027
3RW5515 3NA3822-6 3RT2027 3RT2037 3NA3822-6 3RT2036 3RT2037 3RT2027 3RT2037
3RW5516 3NA3824-6 3RT2035 3RT2037 3NA3824-6 3RT2037 3RT2038 3RT2035 3RT2037
3RW5517 3NA3824-6 3RT2035 3RT2037 3NA3824-6 3RT2038 3RT2046 3RT2035 3RT2037
3RW5521 3NA3824-6 3RT2027 3RT2037 3NA3824-6 3RT2036 3RT2037 3RT2027 3RT2037
3RW5524 3NA3824-6 3RT2036 3RT2037 3NA3824-6 3RT2046 3RT2047 3RT2036 3RT2037
3RW5525 3NA3830-6 3RT2037 3RT2046 3NA3830-6 3RT2047 3RT1054 3RT2037 3RT2046
3RW5526 3NA3132-6 3RT2038 3RT2046 3NA3132-6 3RT1055 3RT1055 3RT2038 3RT2046
3RW5527 3NA3136-6 3RT2046 3RT2047 3NA3136-6 3RT1056 3RT1056 3RT2046 3RT2047
3RW5534 3NA3244-6 3RT1054 3RT1054 3NA3244-6 3RT1064 3RT1064 3RT1054 3RT1054
3RW5535 3NA3244-6 3RT1055 3RT1055 3NA3244-6 3RT1065 3RT1065 3RT1055 3RT1055
3RW5536 3NA3365-6 3RT1056 3RT1064 3NA3365-6 3RT1066 3RT1075 3RT1056 3RT1064
3RW5543 2 x 3NA3354-6 3RT1064 3RT1064 2 x 3NA3354-6 3RT1075 3RT1075 3RT1064 3RT1064
3RW5544 2 x 3NA3354-6 3RT1065 3RT1065 2 x 3NA3354-6 3RT1076 3RT1076 3RT1065 3RT1065
3RW5545 2 x 3NA3365-6 3RT1075 3RT1075 2 x 3NA3365-6 3TF68 3TF68 3RT1075 3RT1075
3RW5546 2 x 3NA3365-6 3RT1075 3RT1075 2 x 3NA3365-6 3TF69 3TF69 3RT1075 3RT1075
3RW5547 2 x 3NA3365-6 3RT1076 3RT1276 2 x 3NA3365-6 3TF69 3TF69 3RT1076 3RT1276
3RW5548 2 x 3NA3365-6 3TF68 3TF68 2 x 3NA3365-6 -- -- 3TF68 3TF68
3RW5552 2 x 3NA3365-6 3TF68 3TF69 -- -- -- 3TF68 3TF69
3RW5553 2 x 3NA3365-6 3TF69 3TF69 -- -- -- 3TF69 3TF69
3RW5554 2 x 3NA3365-6 -- -- -- -- -- -- --
3RW5556 3 x 3NA3365-6 -- -- -- -- -- -- --
3RW5558 3 x 3NA3365-6 -- -- -- -- -- -- --
Note:
The specified short-circuit breaking capacities Iq in kA are
covered by combination tests. Smaller fuses than those
specified can be used at any time as smaller ones trip more
quickly in the event of a short circuit (unchanged short-circuit
breaking capacity) and thus protect the soft starter in any case.
The dimensioning of the short-circuit components must,
however, be suitable for the connected three-phase motor
and the line protection for the cables used.
In inside-delta circuits, motor feeders with soft starters can only
be operated in systems with up to 600 V.
F’1
Q21
Q11
NSB0_01905
M
3~
F1 F1 F1
F3 F3 F3
IC01_00546a
IC01_00566
M M M
3~ 3~ 3~
Soft starters gG class fuse aR class fuse Line contactor gG class fuse aR class fuse Line contactor (optional)
(optional)
6
for systems for systems for systems for systems for systems for systems for for for for
up to 690 V up to 690 V up to 480 V up to 690 V up to 600 V up to 600 V systems systems systems systems
up to up to up to up to
480 V 600 V 480 V 600 V
in the in the in the delta in the delta
supply supply
cable cable
Q11 F1 F3 Q21 Q21 F1 F3 Q21 Q21 Q21 Q21
Type Type Type Type Type Type Type Type Type Type Type
Type of ToC Standard (inline) circuit Inside-delta circuit
coordination 2
"2"
3RW5513 3NA3820-6 3NE8017-1 3RT2025 3RT2025 3NA3820-6 3NE8017-1 3RT2027 3RT2035 3RT2025 3RT2025
3RW5514 3NA3820-6 3NE8020-1 3RT2026 3RT2027 3NA3820-6 3NE8020-1 3RT2027 3RT2037 3RT2026 3RT2027
3RW5515 3NA3822-6 3NE8021-1 3RT2027 3RT2037 3NA3822-6 3NE8021-1 3RT2036 3RT2037 3RT2027 3RT2037
3RW5516 3NA3824-6 3NE8022-1 3RT2035 3RT2037 3NA3824-6 3NE8022-1 3RT2037 3RT2038 3RT2035 3RT2037
3RW5517 3NA3824-6 3NE8024-1 3RT2035 3RT2037 3NA3824-6 3NE8024-1 3RT2038 3RT2046 3RT2035 3RT2037
3RW5521 3NA3824-6 3NE8021-1 3RT2027 3RT2037 3NA3824-6 3NE8021-1 3RT2036 3RT2037 3RT2027 3RT2037
3RW5524 3NA3824-6 3NE8024-1 3RT2036 3RT2037 3NA3824-6 3NE8024-1 3RT2046 3RT2047 3RT2036 3RT2037
3RW5525 3NA3830-6 3NE3227 3RT2037 3RT2046 3NA3830-6 3NE3227 3RT2047 3RT1054 3RT2037 3RT2046
3RW5526 3NA3132-6 3NE3227 3RT2038 3RT2046 3NA3132-6 3NE3227 3RT1055 3RT1055 3RT2038 3RT2046
3RW5527 3NA3136-6 3NE3227 3RT2046 3RT2047 3NA3136-6 3NE3227 3RT1056 3RT1056 3RT2046 3RT2047
3RW5534 3NA3244-6 3NE3231 3RT1054 3RT1054 3NA3244-6 3NE3231 3RT1064 3RT1064 3RT1054 3RT1054
3RW5535 3NA3244-6 3NE3233 3RT1055 3RT1055 3NA3244-6 3NE3233 3RT1065 3RT1065 3RT1055 3RT1055
3RW5536 3NA3365-6 3NE3334-0B 3RT1056 3RT1064 3NA3365-6 3NE3334-0B 3RT1066 3RT1075 3RT1056 3RT1064
3RW5543 2 x 3NA3354-6 3NE3333 3RT1064 3RT1064 2 x 3NA3354-6 3NE3333 3RT1075 3RT1075 3RT1064 3RT1064
3RW5544 2 x 3NA3354-6 3NE3335 3RT1065 3RT1065 2 x 3NA3354-6 3NE3335 3RT1076 3RT1076 3RT1065 3RT1065
3RW5545 2 x 3NA3365-6 -- 3RT1075 3RT1075 2 x 3NA3365-6 -- 3TF68 3TF68 3RT1075 3RT1075
3RW5546 2 x 3NA3365-6 -- 3RT1075 3RT1075 2 x 3NA3365-6 -- 3TF69 3TF69 3RT1075 3RT1075
3RW5547 2 x 3NA3365-6 3NE3340-8 3RT1076 3RT1276 2 x 3NA3365-6 3NE3340-8 3TF69 3TF69 3RT1076 3RT1276
3RW5548 2 x 3NA3365-6 3NC3342-1U 3TF68 3TF68 2 x 3NA3365-6 3NC3342-1U -- -- 3TF68 3TF68
3RW5552 2 x 3NA3365-6 3NC3343-1U 3TF68 3TF69 -- 3NC3343-1U -- -- 3TF68 3TF69
3RW5553 2 x 3NA3365-6 3NC3343-1U 3TF69 3TF69 -- 3NC3343-1U -- -- 3TF69 3TF69
3RW5554 2 x 3NA3365-6 3NC3343-1U -- -- -- 3NC3343-1U -- -- -- --
3RW5556 3 x 3NA3365-6 3 x 3NE3340-8 -- -- -- 3 x 3NE3340-8 -- -- -- --
3RW5558 3 x 3NA3365-6 3 x 3NE3340-8 -- -- -- 3 x 3NE3340-8 -- -- -- --
Note: In inside-delta circuits, motor feeders with soft starters can only
be operated in systems with up to 600 V.
The specified short-circuit breaking capacities Iq in kA are
covered by combination tests. Smaller fuses than those
specified can be used at any time as smaller ones trip more
quickly in the event of a short circuit (unchanged short-circuit
breaking capacity) and thus protect the soft starter in any case.
The dimensioning of the short-circuit components must,
however, be suitable for the connected three-phase motor
and the line protection for the cables used.
For CLASS 10 applications, as an alternative to the 3NA3
gG class full-range fuses for cable and line protection (F1),
3RV2 motor starter protectors/3VA circuit breakers can also be
used, possibly with reduced short-circuit breaking capacity (see
page 6/24). In these cases, optional line contactors can be
dispensed with.
3RW551 3RW552.
At 40 °C At 50 °C Article No. Price PU PS* PG
Opera- Operating power for Opera- Rating [hp] for three-phase motors per PU (UNIT,
tional three-phase motors tional SET, M)
current at at at at current at at at at
230 V 400 V 500 V 690 V 200/208 V 220/230 V 460/480 V 575/600 V
A kW kW kW kW A hp hp hp hp
6
Operational voltage 200 ... 480 V
13 3 5.5 -- -- 11.5 2 3 7.5 -- 3RW5513-@HA@4 1 1 unit 42S
18 4 7.5 -- -- 15.9 3 5 10 -- 3RW5514-@HA@4 1 1 unit 42S
25 5.5 11 -- -- 22.3 5 7.5 15 -- 3RW5515-@HA@4 1 1 unit 42S
32 7.5 15 -- -- 28.4 7.5 10 20 -- 3RW5516-@HA@4 1 1 unit 42S
38 11 18.5 -- -- 33.5 10 10 20 -- 3RW5517-@HA@4 1 1 unit 42S
47 11 22 -- -- 41.6 10 10 30 -- 3RW5524-@HA@4 1 1 unit 42S
63 18.5 30 -- -- 55.5 15 20 40 -- 3RW5525-@HA@4 1 1 unit 42S
77 22 37 -- -- 68 20 25 50 -- 3RW5526-@HA@4 1 1 unit 42S
93 22 45 -- -- 82.5 25 30 60 -- 3RW5527-@HA@4 1 1 unit 42S
Note:
For the constraints for the motor outputs specified here,
see page 6/8.
Note:
For the constraints for the motor outputs specified here,
see page 6/8.
3RW551. 3RW552.
At 40 °C At 50 °C Article No. Price PU PS* PG
Opera- Operating power for Opera- Rating [hp] for three-phase motors per PU (UNIT,
tional three-phase motors tional SET, M)
current at at at at current at at at at
230 V 400 V 500 V 690 V 200/208 V 220/230 V 460/480 V 575/600 V
A kW kW kW kW A hp hp hp hp
Operational voltage 200 ... 600 V
13 3 5.5 7.5 -- 11.5 2 3 7.5 10 3RW5513-@HA@5 1 1 unit 42S
18 4 7.5 11 -- 15.9 3 5 10 10 3RW5514-@HA@5 1 1 unit 42S
6
25 5.5 11 15 -- 22.3 5 7.5 15 20 3RW5515-@HA@5 1 1 unit 42S
32 7.5 15 18.5 -- 28.4 7.5 10 20 25 3RW5516-@HA@5 1 1 unit 42S
38 11 18.5 22 -- 33.5 10 10 20 30 3RW5517-@HA@5 1 1 unit 42S
Operational voltage 200 ... 690 V
25 5.5 11 15 22 22.3 5 7.5 15 20 3RW5521-@HA@6 1 1 unit 42S
47 11 22 30 45 41.6 10 10 30 40 3RW5524-@HA@6 1 1 unit 42S
63 18.5 30 37 55 55.5 15 20 40 50 3RW5525-@HA@6 1 1 unit 42S
77 22 37 45 75 68 20 25 50 60 3RW5526-@HA@6 1 1 unit 42S
93 22 45 55 90 82.5 25 30 60 75 3RW5527-@HA@6 1 1 unit 42S
Note:
For the constraints for the motor outputs specified here,
see page 6/8.
Note:
For the constraints for the motor outputs specified here,
see page 6/8.
3RW551. 3RW552.
At 40 °C for inside-delta circuit At 50 °C for inside-delta circuit Article No. Price PU PS* PG
Opera- Operating power for Opera- Rating [hp] for three-phase motors per PU (UNIT,
tional three-phase motors tional SET, M)
current at at at current at at at at
230 V 400 V 500 V 200/208 V 220/230 V 460/480 V 575/600 V
A kW kW kW A hp hp hp hp
6
Operational voltage 200 ... 480 V
22.5 5.5 11 -- 19.9 5 5 10 -- 3RW5513-@HA@4 1 1 unit 42S
31.5 7.5 15 -- 28 7.5 7.5 20 -- 3RW5514-@HA@4 1 1 unit 42S
43.3 11 18.5 -- 39 10 10 25 -- 3RW5515-@HA@4 1 1 unit 42S
55.4 15 22 -- 49 15 15 30 -- 3RW5516-@HA@4 1 1 unit 42S
65.8 18.5 30 -- 58 15 20 40 -- 3RW5517-@HA@4 1 1 unit 42S
81.4 22 45 -- 72 20 25 50 -- 3RW5524-@HA@4 1 1 unit 42S
109 30 55 -- 96 30 30 75 -- 3RW5525-@HA@4 1 1 unit 42S
133 37 75 -- 118 30 40 75 -- 3RW5526-@HA@4 1 1 unit 42S
161 45 90 -- 143 40 50 100 -- 3RW5527-@HA@4 1 1 unit 42S
Note:
For the constraints for the motor outputs specified here,
see page 6/8.
Note:
For the constraints for the motor outputs specified here,
see page 6/8.
3RW551. 3RW552.
At 40 °C for inside-delta circuit At 50 °C for inside-delta circuit Article No. Price PU PS* PG
Opera- Operating power for Opera- Rating [hp] for three-phase motors per PU (UNIT,
tional three-phase motors tional SET, M)
current at at at current at at at at
230 V 400 V 500 V 200/208 V 220/230 V 460/480 V 575/600 V
A kW kW kW A hp hp hp hp
Operational voltage 200 ... 600 V
22.5 5.5 11 15 19.9 5 5 10 15 3RW5513-@HA@5 1 1 unit 42S
31.5 7.5 15 18.5 28 7.5 7.5 20 25 3RW5514-@HA@5 1 1 unit 42S
6
43.3 11 18.5 22 39 10 10 25 30 3RW5515-@HA@5 1 1 unit 42S
55.4 15 22 30 49 15 15 30 40 3RW5516-@HA@5 1 1 unit 42S
65.8 18.5 30 37 58 15 20 40 50 3RW5517-@HA@5 1 1 unit 42S
43.3 11 18.5 22 39 10 10 25 30 3RW5521-@HA@6 1 1 unit 42S
81.4 22 45 45 72 20 25 50 60 3RW5524-@HA@6 1 1 unit 42S
109 30 55 55 96 30 30 75 75 3RW5525-@HA@6 1 1 unit 42S
133 37 75 90 118 30 40 75 100 3RW5526-@HA@6 1 1 unit 42S
161 45 90 110 143 40 50 100 125 3RW5527-@HA@6 1 1 unit 42S
Note:
For the constraints for the motor outputs specified here,
see page 6/8.
Note:
For the constraints for the motor outputs specified here,
see page 6/8.
Fan covers
Fan cover 3RW551 (1x), -- -- 3RW5983-0FC00 1 1 unit 42S
3RW552 (2x),
3RW553 (2x)
3RW554 (1x) -- -- 3RW5984-0FC00 1 1 unit 42S
3RW5983-0FC00 3RW555 (3x) -- -- 3RW5985-0FC00 1 1 unit 42S
Terminal covers
Terminal 3RW552 (2x), -- -- 3RW5983-0TC20 1 1 unit 42S
cover 3RW553 (2x)
3RW5983-0TC20
3RW554 (2x) -- -- 3RW5984-0TC20 1 1 unit 42S
6
3RW5984-0TC20
Enclosure components
Hinged cover 3RW55 Without -- 3RW5950-0GL20 1 1 unit 42S
cutout
3RW5950-0GL20
Communications modules
Communica- 3RW55 PROFINET -- 3RW5950-0CH00 1 1 unit 42S
tions High-Feature
module1) with integral
switch
PROFINET -- 3RW5980-0CS00 1 1 unit 42S
Standard
PROFIBUS -- 3RW5980-0CP00 1 1 unit 42S
3RW5980-0CS00
EtherNet/IP -- 3RW5980-0CE00 1 1 unit 42S
3RW5980-0CE00
Modbus RTU -- 3RW5980-0CR00 1 1 unit 42S
Modbus TCP -- 3RW5980-0CT00 1 1 unit 42S
3RW5980-0CR00
1) Use the recommended connection plugs for attaching the bus connecting
cable (e.g. angled or suitable for industrial use), see Equipment Manual for
the relevant communications module.
HMI modules
IP65 door 3RW55 IP65 For 3RW5980-0HD00 1 1 unit 42S
mounting kit HMI modules
for HMI
modules
3RW5980-0HD00
Connecting cables
HMI 3RW55 5 m, round For 3RW5980-0HC60 1 1 unit 42S
connecting 2.5 m, round door 3UF7933-0BA00-0 1 1 unit 42J
cable mounting
3UF793.-0BA00-0 1.0 m, round 3UF7937-0BA00-0 1 1 unit 42J
0.5 m, round 3UF7932-0BA00-0 1 1 unit 42J
Further accessories
Push-in lugs -- Two lugs are For 3ZY1311-0AA00 1 10 units 41L
6
3RT2900-1SB20
1) PC labeling system for individual inscription
of unit labeling plates available from:
murrplastik Systemtechnik GmbH
(see page 16/18).
■ Overview
More information
Homepage, see www.siemens.com/sirius-soft-starter SIRIUS Soft Starter ES (TIA Portal), see page 6/9 or
Industry Mall, see www.siemens.com/product?3RW55Failsafe https://support.industry.siemens.com/cs/ww/en/ps/24230/dl
TIA Selection Tool Cloud (TST Cloud), see Decision-making support for motor starting – Starting and running three-phase
www.siemens.com/tstcloud/?node=3rw55 asynchronous motors efficiently, see www.siemens.com/motorstart-guide
Industry Online Support (SIOS) topic page, see SIRIUS Sim, see page 6/10 or
https://support.industry.siemens.com/cs/ww/en/view/109747404 https://support.industry.siemens.com/cs/ww/en/view/109763750
Simulation Tool for Soft Starters (STS), see page 6/9 or Conversion tool, see www.siemens.com/conversion-tool
https://support.industry.siemens.com/cs/ww/en/view/101494917
6
maximum flexibility.
With their modern hybrid switching technology, the 3RW55
Failsafe soft starters offer efficient switching for long-term,
energy-saving use.
2 Communications modules
3 Hinged cover
4 Fan covers
5 Terminal covers (size 2 to size 4)
7
IC01_00690c
2 4
SIRIUS 3RW55 Failsafe High Performance soft starter with accessories (see page 6/53)
■ Benefits
6
Automatic parameterization Extremely easy commissioning and reliability even under changing
load conditions
Hybrid switching technology and 3-phase motor control Minimum power loss and optimum/symmetrical motor control
TIA integration – communications modules optional Efficient configuration and maximum flexibility in automation engineering
Removable HMI with color display, local interface, slot for Maximum flexibility with regard to user interface and intuitive menu guidance
micro SD memory card
Pump stop and torque control Reduced mechanical loading and optimum pump stop control
Certified according to ATEX/IECEx directive Suitable for the starting of explosion-proof motors
Fail-safe disconnection up to SIL 3/PL e/STO Reduced costs and space requirements thanks to direct wiring of the
EMERGENCY STOP mushroom pushbutton to the soft starter for SIL 1/PL c
System redundancy S2 Simple and straight-forward integration into fault-tolerant automation systems
Direct integration into MindSphere via the OPC UA server Worldwide data availability for optimal plant operation
■ Technical specifications
More information
Technical specifications, see FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/25776/faq
https://support.industry.siemens.com/cs/ww/en/ps/25776/td Simulation Tool for Soft Starters (STS), see page 6/9 or
Equipment Manual, see https://support.industry.siemens.com/cs/ww/en/view/101494917
https://support.industry.siemens.com/cs/ww/en/view/109753752
D
W
6
• Below mm 75
Installation altitude at height above sea level, maximum1) m 2 000
Degree of protection IP on the front according to IEC 60529 IP20 IP00 (IP20 with cover)
Touch protection on the front according to IEC 60529 Finger-safe for vertical Finger-safe for vertical touching from the front
touching from the front with cover
Ambient conditions
Ambient temperature
• During operation2) °C -25 ... +60
• During storage and transport °C -40 ... +80
Environmental category according to IEC 60721
• During operation 3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist),
3S2 (sand must not get into the devices), 3M6
• During storage 1K6 (only occasional condensation), 1C2 (no salt mist),
1S2 (sand must not get into the devices), 1M4
• During transport 2K2, 2C1, 2S1, 2M2 (max. height of fall 0.3 m)
1) Derating from 1 000 m, see characteristic curve on page 6/8. 2) Note derating above 40 °C.
Type 3RW55..-.HF.4
Power electronics
Operational voltage V 200 ... 480
• Relative negative tolerance/relative positive tolerance % -15/10
Operational voltage for inside-delta circuit V 200 ... 480
• Relative negative tolerance/relative positive tolerance % -15/10
Operating frequency Hz 50 ... 60
• Relative negative tolerance/relative positive tolerance % -10/10
Minimum load [% of IM]1) % 10
Maximum cable length between soft starter and motor m 800
1)
Relative to set Ie.
• 350% IM
- Start-up time 10 s 1/h 13 13 13 13 13
- Start-up time 20 s 1/h 4 4 4 4 4
Heavy starting (CLASS 20E)
Rated motor current IM, Tu = 40/50/60 °C A 13/11.5/10.5 18/15.9/13.8 25/22.3/19.6 29.6/27.2/23.6 33.5/30.5/27.5
ON period = 70%; motor protection activated
• 300% IM
- Start-up time 20 s 1/h 10 10 10 10 10
- Start-up time 40 s 1/h 4 4 4 4 4
• 350% IM
- Start-up time 20 s 1/h 7 7 7 7 7
- Start-up time 40 s 1/h 2.5 2.5 2.5 2.5 2.5
Heavy starting (CLASS 30E)
Rated motor current IM, Tu = 40/50/60 °C A 13/11.5/10.5 18/15.9/13.8 25/22.3/19.6 26/23.6/21.2 29/26/23
ON period = 70%; motor protection activated
• 300% IM
- Start-up time 30 s 1/h 7 7 7 7 7
- Start-up time 60 s 1/h 3 3 3 3 3
• 350% IM
- Start-up time 30 s 1/h 4 4 4 4 4
- Start-up time 60 s 1/h 1.8 1.8 1.8 1.8 1.8
Adjustable rated motor current IM
• Minimum/maximum A 2.5/13 3.5/18 5/25 6.5/32 7.5/38
• Minimum/maximum in inside-delta circuits A 4.3/22.5 6.1/31.1 8.7/43.3 11.3/55.4 13/65.8
6
• 350% IM
- Start-up time 10 s 1/h 13 13 13 13
- Start-up time 20 s 1/h 4 4 4 4
Heavy starting (CLASS 20E)
Rated motor current IM, Tu = 40/50/60 °C A 47/41.6/36.2 63/55.5/50.5 77/68/62 93/82.5/75.5
ON period = 70%; motor protection activated
• 300% IM
- Start-up time 20 s 1/h 10 10 10 10
- Start-up time 40 s 1/h 4 4 4 4
• 350% IM
- Start-up time 20 s 1/h 7 7 7 7
- Start-up time 40 s 1/h 2.5 0 0 0
Heavy starting (CLASS 30E)
Rated motor current IM, Tu = 40/50/60 °C A 43.4/38/34.4 53/48/43 68/62/56 82.5/75.5/65
ON period = 70%; motor protection activated
• 300% IM
- Start-up time 30 s 1/h 7 7 7 7
- Start-up time 60 s 1/h 3 3 3 3
• 350% IM
- Start-up time 30 s 1/h 4 4 4 4
- Start-up time 60 s 1/h 1.8 1.8 1.8 1.8
Adjustable rated motor current IM
• Minimum/maximum A 10/47 13/63 16/77 19/93
• Minimum/maximum in inside-delta circuits A 17.3/81.4 22.5/109 27.7/133 32.9/161
• 350% IM
- Start-up time 10 s 1/h 13 4 0
- Start-up time 20 s 1/h 4 0 0
Heavy starting (CLASS 20E)
Rated motor current IM, Tu = 40/50/60 °C A 109/97/85 128/113/103 141/129/117
ON period = 70%; motor protection activated
• 300% IM
- Start-up time 20 s 1/h 10 10 10
- Start-up time 40 s 1/h 4 4 4
• 350% IM
- Start-up time 20 s 1/h 7 6 6
- Start-up time 40 s 1/h 0 0 0
Heavy starting (CLASS 30E)
Rated motor current IM, Tu = 40/50/60 °C A 89/81/74 108/98/88 117/105/93
ON period = 70%; motor protection activated
• 300% IM
- Start-up time 30 s 1/h 7 7 7
- Start-up time 60 s 1/h 3 3 3
• 350% IM
- Start-up time 30 s 1/h 4 4 4
- Start-up time 60 s 1/h 1.8 1.8 1.8
Adjustable rated motor current IM
• Minimum/maximum A 23/113 29/143 34/171
• Minimum/maximum in inside-delta circuits A 39.8/195 50.2/247 58.9/296
6
• 350% IM
- Start-up time 10 s 1/h 0 13 5 12 6 1
- Start-up time 20 s 1/h 0 4 0 3 0.4 --
Heavy starting (CLASS 20E)
Rated motor current IM, Tu = 40/50/60 °C A 162/146/130 200/180/160 231/207/183 258/230/202 272/254/236 284/262/240
ON period = 70%; motor protection activated
• 300% IM
- Start-up time 20 s 1/h 10 10 10 10 10 10
- Start-up time 40 s 1/h 4 4 4 4 4 4
• 350% IM
- Start-up time 20 s 1/h 7 7 7 7 7 7
- Start-up time 40 s 1/h 2 2.5 2.5 2.5 2.5 2.5
Heavy starting (CLASS 30E)
Rated motor current IM, Tu = 40/50/60 °C A 138/122/106 160/140/120 183/159/135 202/174/160 210/190/170 220/200/180
ON period = 70%; motor protection activated
• 300% IM
- Start-up time 30 s 1/h 7 7 7 7 7 7
- Start-up time 60 s 1/h 3 3 3 3 3 3
• 350% IM
- Start-up time 30 s 1/h 4 4 4 4 4 4
- Start-up time 60 s 1/h 1.8 1.8 1.8 1.8 1.8 1.8
Adjustable rated motor current IM
• Minimum/maximum A 42/210 50/250 63/315 74/370 94/470 114/570
• Minimum/maximum in inside-delta circuits A 72.7/363 86.6/433 109.1/545 128.2/640 162.8/814 197.5/987
Q1 Q1
Q11 Q11
NSB0_01902
IC01_00544
M M
3~ 3~
Soft starters Motor starter protectors/circuit breakers Motor starter protectors/circuit breakers
for 400 V systems for 480 V systems for 400 V systems for 480 V systems
Q11 Q1 Iq Q1 Iq Q1 Iq Q1 Iq
Type Type kA Type kA Type kA Type kA
Type of Standard (inline) circuit Inside-delta circuit
6
ToC
coordination 1
"1"
3RW5513 3RV2032-4TA10 65 3RV2032-4TA10 18 3RV2032-4DA10 65 3RV2032-4DA10 18
3RW5514 3RV2032-4DA10 65 3RV2032-4DA10 15 3RV2032-4EA10 65 3RV2032-4EA10 15
3RW5515 3RV2032-4EA10 65 3RV2032-4EA10 15 3RV2032-4VA10 65 3RV2032-4VA10 15
3RW5516 3RV2032-4VA10 65 3RV2032-4VA10 10 3RV2032-4JA10 65 3RV2032-4JA10 10
3RW5517 3RV2032-4WA10 65 3RV2032-4WA10 10 3RV2032-4RA10 65 3RV2032-4RA10 10
3RW5524 3RV2032-4JA10 65 3RV2032-4JA10 10 3RV2032-4RA10 65 3RV2032-4RA10 10
3RW5525 3VA2163-7MN32-0AA0 65 3VA2163-7MN32-0AA0 20 3VA2110-7MN32-0AA0 65 3VA2110-7MN32-0AA0 20
3RW5526 3VA2110-7MN32-0AA0 65 3VA2110-7MN32-0AA0 20 3VA2216-7MN32-0AA0 65 3VA2216-7MN32-0AA0 20
3RW5527 3VA2216-7MN32-0AA0 15 3VA2216-7MN32-0AA0 10 3VA2220-7MN32-0AA0 15 3VA2220-7MN32-0AA0 10
3RW5534 3VA2216-7MN32-0AA0 65 -- -- 3VA2220-7MN32-0AA0 65 -- --
3RW5535 3VA2220-7MN32-0AA0 65 -- -- 3VA2325-7MN32-0AA0 65 -- --
3RW5536 3VA2325-7MN32-0AA0 30 3VA2325-7MN32-0AA0 10 3VA2440-7MN32-0AA0 30 3VA2440-7MN32-0AA0 10
3RW5543 3VA2325-7MN32-0AA0 65 3VA2325-7MN32-0AA0 65 3VA2440-7MN32-0AA0 65 3VA2440-7MN32-0AA0 65
3RW5544 3VA2440-7MN32-0AA0 65 3VA2440-7MN32-0AA0 65 3VA2450-7MN32-0AA0 65 3VA2450-7MN32-0AA0 65
3RW5545 3VA2440-7MN32-0AA0 65 3VA2440-7MN32-0AA0 65 3VA2580-6HN32-0AA0 65 3VA2580-6HN32-0AA0 65
3RW5546 3VA2440-7MN32-0AA0 65 3VA2440-7MN32-0AA0 65 3VA2580-6HN32-0AA0 65 3VA2580-6HN32-0AA0 65
3RW5547 3VA2450-7MN32-0AA0 65 3VA2450-7MN32-0AA0 65 3VA2510-6HN32-0AA0 65 3VA2510-6HN32-0AA0 65
3RW5548 3VA2580-6HN32-0AA0 65 3VA2580-6HN32-0AA0 65 3VA2510-6HN32-0AA0 65 3VA2510-6HN32-0AA0 65
Note:
The service factor and measurement inaccuracies, for example,
have been taken into account for the selection of the specified
motor starter protectors/circuit breakers; the specified short-
circuit breaking capacities Iq in kA are covered by combination
tests. Smaller motor starter protectors/circuit breakers from the
same series can be used at any time as smaller ones trip more
quickly in the event of a short circuit (unchanged short-circuit
breaking capacity) and thus protect the soft starter in any case.
The dimensioning of the short-circuit components must match
the connected three-phase motor, the short-circuit and overload
requirements of the application, and the line protection for the
cables used.
F1 F1 F1
IC01_00545a
NSB0_01904
IC01_00565
M M M
3~ 3~ 3~
Soft starters gG class fuse Line contactor (optional) gG class fuse Line contactor (optional)
for systems for systems for systems for systems for systems
6
up to 480 V up to 480 V up to 480 V up to 480 V up to 480 V
in the supply cable in the delta
Q11 F1 Q21 F1 Q21 Q21
Type Type Type Type Type Type
Type of ToC Standard (inline) circuit Inside-delta circuit
coordination 1
"1"
3RW5513 3NA3820-6 3RT2025 3NA3820-6 3RT2027 3RT2025
3RW5514 3NA3820-6 3RT2026 3NA3820-6 3RT2027 3RT2026
3RW5515 3NA3822-6 3RT2027 3NA3822-6 3RT2036 3RT2027
3RW5516 3NA3824-6 3RT2035 3NA3824-6 3RT2037 3RT2035
3RW5517 3NA3824-6 3RT2035 3NA3824-6 3RT2038 3RT2035
3RW5524 3NA3824-6 3RT2036 3NA3824-6 3RT2046 3RT2036
3RW5525 3NA3830-6 3RT2037 3NA3830-6 3RT2047 3RT2037
3RW5526 3NA3132-6 3RT2038 3NA3132-6 3RT1055 3RT2038
3RW5527 3NA3136-6 3RT2046 3NA3136-6 3RT1056 3RT2046
3RW5534 3NA3244-6 3RT1054 3NA3244-6 3RT1064 3RT1054
3RW5535 3NA3244-6 3RT1055 3NA3244-6 3RT1065 3RT1055
3RW5536 3NA3365-6 3RT1056 3NA3365-6 3RT1066 3RT1056
3RW5543 2 x 3NA3354-6 3RT1064 2 x 3NA3354-6 3RT1075 3RT1064
3RW5544 2 x 3NA3354-6 3RT1065 2 x 3NA3354-6 3RT1076 3RT1065
3RW5545 2 x 3NA3365-6 3RT1075 2 x 3NA3365-6 3TF68 3RT1075
3RW5546 2 x 3NA3365-6 3RT1075 2 x 3NA3365-6 3TF69 3RT1075
3RW5547 2 x 3NA3365-6 3RT1076 2 x 3NA3365-6 3TF69 3RT1076
3RW5548 2 x 3NA3365-6 3TF68 2 x 3NA3365-6 -- 3TF68
Note:
The specified short-circuit breaking capacities Iq in kA are
covered by combination tests. Smaller fuses than those
specified can be used at any time as smaller ones trip more
quickly in the event of a short circuit (unchanged short-circuit
breaking capacity) and thus protect the soft starter in any case.
The dimensioning of the short-circuit components must,
however, be suitable for the connected three-phase motor
and the line protection for the cables used.
F’1
Q21
Q11
NSB0_01905
M
3~
up to 480 V up to 480 V
Q11 F’1 Q21
Type Type Type
Type of ToC Standard (inline) circuit
coordination 2
"2"
3RW5513 3NE1815-0 3RT2025
3RW5514 3NE1802-0 3RT2026
3RW5515 3NE1817-0 3RT2027
3RW5516 3NE1818-0 3RT2035
3RW5517 3NE1820-0 3RT2035
3RW5524 3NE1021-2 3RT2036
3RW5525 3NE1022-0 3RT2037
3RW5526 3NE1224-0 3RT2038
3RW5527 3NE1224-0 3RT2046
3RW5534 3NE1225-0 3RT1054
3RW5535 3NE1227-0 3RT1055
3RW5536 3NE1230-0 3RT1056
3RW5543 3NE1230-2 3RT1064
3RW5544 3NE1331-0 3RT1065
3RW5545 3NE1334-2 3RT1075
3RW5546 3NE1334-2 3RT1075
3RW5547 3NE1436-2 3RT1076
3RW5548 3NE1437-2 3TF68
Note:
The specified short-circuit breaking capacities Iq in kA are
covered by combination tests. Smaller fuses than those
specified can be used at any time as smaller ones trip more
quickly in the event of a short circuit (unchanged short-circuit
breaking capacity) and thus protect the soft starter in any case.
The dimensioning of the short-circuit components must,
however, be suitable for the connected three-phase motor
and the line protection for the cables used.
In inside-delta circuits, a gR/gS class full-range fuse could not
provide the semiconductor protection of the delta-connected
soft starter with a short-circuit breaking capacity that is
adequate for practical use. In this case, we recommend using
aR class partial-range fuses for semiconductor protection for
type of coordination "2" (see page 6/49).
F1 F1 F1
F3 F3 F3
IC01_00546a
NSB0_01906
IC01_00566
M M M
3~ 3~ 3~
Soft starters gG class fuse aR class fuse Line contactor (optional) gG class fuse aR class fuse Line contactor (optional)
for systems for systems for systems for systems for systems for systems for systems
6
up to 480 V up to 480 V up to 480 V up to 480 V up to 480 V up to 480 V up to 480 V
in the supply in the delta
cable
Q11 F1 F3 Q21 F1 F3 Q21 Q21
Type Type Type Type Type Type Type Type
Type of ToC Standard (inline) circuit Inside-delta circuit
coordination 2
"2"
3RW5513 3NA3820-6 3NE8017-1 3RT2025 3NA3820-6 3NE8017-1 3RT2027 3RT2025
3RW5514 3NA3820-6 3NE8020-1 3RT2026 3NA3820-6 3NE8020-1 3RT2027 3RT2026
3RW5515 3NA3822-6 3NE8021-1 3RT2027 3NA3822-6 3NE8021-1 3RT2036 3RT2027
3RW5516 3NA3824-6 3NE8022-1 3RT2035 3NA3824-6 3NE8022-1 3RT2037 3RT2035
3RW5517 3NA3824-6 3NE8024-1 3RT2035 3NA3824-6 3NE8024-1 3RT2038 3RT2035
3RW5524 3NA3824-6 3NE8024-1 3RT2036 3NA3824-6 3NE8024-1 3RT2046 3RT2036
3RW5525 3NA3830-6 3NE3227 3RT2037 3NA3830-6 3NE3227 3RT2047 3RT2037
3RW5526 3NA3132-6 3NE3227 3RT2038 3NA3132-6 3NE3227 3RT1055 3RT2038
3RW5527 3NA3136-6 3NE3227 3RT2046 3NA3136-6 3NE3227 3RT1056 3RT2046
3RW5534 3NA3244-6 3NE3231 3RT1054 3NA3244-6 3NE3231 3RT1064 3RT1054
3RW5535 3NA3244-6 3NE3233 3RT1055 3NA3244-6 3NE3233 3RT1065 3RT1055
3RW5536 3NA3365-6 3NE3334-0B 3RT1056 3NA3365-6 3NE3334-0B 3RT1066 3RT1056
3RW5543 2 x 3NA3354-6 3NE3333 3RT1064 2 x 3NA3354-6 3NE3333 3RT1075 3RT1064
3RW5544 2 x 3NA3354-6 3NE3335 3RT1065 2 x 3NA3354-6 3NE3335 3RT1076 3RT1065
3RW5545 2 x 3NA3365-6 -- 3RT1075 2 x 3NA3365-6 -- 3TF68 3RT1075
3RW5546 2 x 3NA3365-6 -- 3RT1075 2 x 3NA3365-6 -- 3TF69 3RT1075
3RW5547 2 x 3NA3365-6 3NE3340-8 3RT1076 2 x 3NA3365-6 3NE3340-8 3TF69 3RT1076
3RW5548 2 x 3NA3365-6 3NC3342-1U 3TF68 2 x 3NA3365-6 3NC3342-1U -- 3TF68
Note:
The specified short-circuit breaking capacities Iq in kA are
covered by combination tests. Smaller fuses than those
specified can be used at any time as smaller ones trip more
quickly in the event of a short circuit (unchanged short-circuit
breaking capacity) and thus protect the soft starter in any case.
The dimensioning of the short-circuit components must,
however, be suitable for the connected three-phase motor
and the line protection for the cables used.
For CLASS 10 applications, as an alternative to the gG class
full-range fuses for cable and line protection 3NA3 (F1), 3RV2
motor starter protectors/3VA circuit breakers can also be used,
possibly with reduced short-circuit breaking capacity
(see page 6/46). In these cases, optional line contactors
can be dispensed with.
3RW5543 -- 3RT1064
3RW5544 -- 3RT1065
3RW5545 -- 3RT1075
3RW5546 -- 3RT1075
3RW5547 -- 3RT1076
3RW5548 -- 3TF68
F1 F1
Q11 Q11
Q21 Q21
IC01_00790
IC01_00791
M M
3~ 3~
6
13 3 5.5 11.5 2 3 7.5 3RW5513-@HF@4 1 1 unit 42S
18 4 7.5 15.9 3 5 10 3RW5514-@HF@4 1 1 unit 42S
25 5.5 11 22.3 5 7.5 15 3RW5515-@HF@4 1 1 unit 42S
32 7.5 15 28.4 7.5 10 20 3RW5516-@HF@4 1 1 unit 42S
38 11 18.5 33.5 10 10 20 3RW5517-@HF@4 1 1 unit 42S
47 11 22 41.6 10 10 30 3RW5524-@HF@4 1 1 unit 42S
63 18.5 30 55.5 15 20 40 3RW5525-@HF@4 1 1 unit 42S
77 22 37 68 20 25 50 3RW5526-@HF@4 1 1 unit 42S
93 22 45 82.5 25 30 60 3RW5527-@HF@4 1 1 unit 42S
Note:
For the constraints for the motor outputs specified here,
see page 6/8.
Note:
For the constraints for the motor outputs specified here,
see page 6/8.
Note:
For the constraints for the motor outputs specified here,
see page 6/8.
At 40 °C for inside-delta circuit At 50 °C for inside-delta circuit Article No. Price PU PS* PG
Opera- Operating power for Opera- Rating [hp] for three-phase motors per PU (UNIT,
tional three-phase motors tional SET, M)
current at at current at at at
230 V 400 V 200/208 V 220/230 V 460/480 V
A kW kW A hp hp hp
Operational voltage 200 ... 480 V
196 55 110 175 50 60 125 3RW5534-@HF@4 1 1 unit 42S
248 75 132 222 75 75 150 3RW5535-@HF@4 1 1 unit 42S
296 90 160 265 75 100 200 3RW5536-@HF@4 1 1 unit 42S
364 110 200 322 100 125 250 3RW5543-@HF@4 1 1 unit 42S
433 132 250 381 125 150 300 3RW5544-@HF@4 1 1 unit 42S
546 160 315 483 150 200 400 3RW5545-@HF@4 1 1 unit 42S
641 200 355 568 200 200 450 3RW5546-@HF@4 1 1 unit 42S
814 250 400 721 250 250 600 3RW5547-@HF@4 1 1 unit 42S
987 315 560 873 300 350 750 3RW5548-@HF@4 1 1 unit 42S
Note:
For the constraints for the motor outputs specified here,
see page 6/8.
Fan covers
Fan cover 3RW551 (1x), -- -- 3RW5983-0FC00 1 1 unit 42S
3RW552 (2x),
3RW553 (2x)
3RW554 (1x) -- -- 3RW5984-0FC00 1 1 unit 42S
3RW5983-0FC00
Terminal covers
Terminal 3RW552 (2x), -- -- 3RW5983-0TC20 1 1 unit 42S
cover 3RW553 (2x)
3RW5983-0TC20
3RW554 (2x) -- -- 3RW5984-0TC20 1 1 unit 42S
6
3RW5984-0TC20
Enclosure components
Hinged cover 3RW55 Without -- 3RW5950-0GL20 1 1 unit 42S
cutout
3RW5950-0GL20
Communications modules
Communica- 3RW55 PROFINET -- 3RW5950-0CH00 1 1 unit 42S
tions module1) High-Feature
with integral
switch
PROFINET -- 3RW5980-0CS00 1 1 unit 42S
Standard
PROFIBUS -- 3RW5980-0CP00 1 1 unit 42S
3RW5980-0CS00
EtherNet/IP -- 3RW5980-0CE00 1 1 unit 42S
3RW5980-0CE00
Modbus RTU -- 3RW5980-0CR00 1 1 unit 42S
Modbus TCP -- 3RW5980-0CT00 1 1 unit 42S
3RW5980-0CR00
1) Use the recommended connection plugs for attaching the bus connecting
cable (e.g. angled or suitable for industrial use), see Equipment Manual for
the relevant communications module.
* You can order this quantity or a multiple thereof.
Illustrations are approximate Siemens IC 10 · 2023 6/53
© Siemens 2023
HMI modules
IP65 door 3RW55 IP65 For 3RW5980-0HD00 1 1 unit 42S
mounting kit HMI modules
for HMI
modules
3RW5980-0HD00
Connecting cables
HMI 3RW55 5 m, round For 3RW5980-0HC60 1 1 unit 42S
connecting 2.5 m, round door 3UF7933-0BA00-0 1 1 unit 42J
cable mounting
3UF793.-0BA00-0 1.0 m, round 3UF7937-0BA00-0 1 1 unit 42J
0.5 m, round 3UF7932-0BA00-0 1 1 unit 42J
Further accessories
Push-in lugs -- Two lugs are For 3ZY1311-0AA00 1 10 units 41L
6
3RT2900-1SB20
1) PC labeling system for individual inscription
of unit labeling plates available from:
murrplastik Systemtechnik GmbH
(see page 16/18).
■ Overview
More information
Homepage, see www.siemens.com/sirius-soft-starter SIRIUS Soft Starter ES (TIA Portal) for diagnostics, see page 6/9 or
Industry Mall, see www.siemens.com/product?3RW52 https://support.industry.siemens.com/cs/ww/en/ps/24230/dl
TIA Selection Tool Cloud (TST Cloud), see SIRIUS 3RW soft starter block library for SIMATIC PCS 7, see page 6/10 or
www.siemens.com/tstcloud/?node=3rw52 https://support.industry.siemens.com/cs/ww/en/view/109770336
Industry Online Support (SIOS) topic page, see Decision-making support for motor starting – Starting and running three-phase
https://support.industry.siemens.com/cs/ww/en/view/109747404 asynchronous motors efficiently, see www.siemens.com/motorstart-guide
Simulation Tool for Soft Starters (STS), see page 6/9 or Conversion tool, see www.siemens.com/conversion-tool
https://support.industry.siemens.com/cs/ww/en/view/101494917
6
long-term, energy-saving use.
7
4
2
IC01_00581b
3 5
SIRIUS 3RW52 General Performance soft starter with accessories (see page 6/71), for expansion with HMI module or communications module
■ Benefits
6
Hybrid switching technology and 3-phase motor control Minimum power loss and optimum/symmetrical motor control
TIA integration – communications modules and HMI modules optional Efficient configuration and maximum flexibility in automation engineering
Wide range for control supply and main voltage Low variance, high system availability even with weak supply networks
■ Technical specifications
More information
Technical specifications, see FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/25100/faq
https://support.industry.siemens.com/cs/ww/en/ps/25100/td Simulation Tool for Soft Starters (STS), see page 6/9 or
Equipment Manual, see https://support.industry.siemens.com/cs/ww/en/view/101494917
https://support.industry.siemens.com/cs/ww/en/view/109753751
6
can be rotated can be rotated can be rotated for vertical mounting surface
+/- 10° and tilted +/- 90°, +/- 10° and tilted can be tilted +/- 22.5°
forward or for vertical forward or forward or backward
backward mounting surface backward
can be tilted
+/- 22.5° forward
or backward
Distance to be maintained with side-by-side mounting
• Above mm 100
• At the side mm 5
• Below mm 75
Installation altitude at height above sea level, m 5 000
maximum1)
Degree of protection IP on the front according to IP20 IP00 (IP20 with cover)
IEC 60529
Touch protection on the front according to IEC 60529 Finger-safe for vertical touching Finger-safe for vertical touching from the front
from the front with cover
Ambient conditions
Ambient temperature
• During operation2) °C -25 ... +60
• During storage and transport °C -40 ... +80
Environmental category according to IEC 60721
• During operation 3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist),
3S2 (sand must not get into the devices), 3M6
• During storage 1K6 (only occasional condensation), 1C2 (no salt mist),
1S2 (sand must not get into the devices), 1M4
• During transport 2K2, 2C1, 2S1, 2M2 (max. height of fall 0.3 m)
1) Derating from 1 000 m, see characteristic curve on page 6/8.
2)
Note derating above 40 °C.
6
• 350% IM
- Start-up time 10 s 1/h 13 13 13 13 13
- Start-up time 20 s 1/h 4 4 4 4 4
Heavy starting (CLASS 20E)
Rated motor current IM, Tu = 40/50/60 °C A 13/11.5/10.5 18/15.9/13.8 25/22.3/19.6 29.6/27.2/23.6 33.5/30.5/27.5
ON period = 70%; motor protection activated
• 300% IM
- Start-up time 20 s 1/h 10 10 10 10 10
- Start-up time 40 s 1/h 4 4 4 4 4
• 350% IM
- Start-up time 20 s 1/h 7 7 7 7 7
- Start-up time 40 s 1/h 2.5 2.5 2.5 2.5 2.5
Adjustable rated motor current IM
• Minimum/maximum A 5.5/13 7.5/18 11.5/25 14/32 15.5/38
• Minimum/maximum in inside-delta circuits A 9.5/22.5 13/31.2 19.9/43.3 24.2/55.4 26.8/65.8
• 350% IM
- Start-up time 10 s 1/h 13 13 13 13
- Start-up time 20 s 1/h 4 4 4 4
Heavy starting (CLASS 20E)
Rated motor current IM, Tu = 40/50/60 °C A 47/41.6/36.2 63/55.5/50.5 65/59/53 93/82.5/75.5
ON period = 70%; motor protection activated
• 300% IM
- Start-up time 20 s 1/h 10 10 10 10
- Start-up time 40 s 1/h 4 3 4 4
• 350% IM
- Start-up time 20 s 1/h 7 4 7 7
- Start-up time 40 s 1/h 2 0 2.5 2.5
Adjustable rated motor current IM
• Minimum/maximum A 20/47 25.5/63 32/77 40.5/93
• Minimum/maximum in inside-delta circuits A 34.6/81.4 44.2/109 55.4/133 70.1/161
Type 10
3RW5234 3RW5235 3RW5236
Rated operational current Ie A 113 143 171
Power electronics
Load rating with rated operational current Ie
IEC + UL/CSA, individual mounting A 113/101/89 143/128/118 171/153/141
at 40/50/60 °C, AC-53a
Permissible rated motor current and starts/h
Normal starting (CLASS 10A)
Rated motor current IM, Tu = 40/50/60 °C A 113/101/89 143/128/118 171/153/141
ON period = 70%; motor protection activated
• 300% IM
- Start-up time 5 s 1/h 43 43 43
- Start-up time 10 s 1/h 18 18 18
• 350% IM
- Start-up time 5 s 1/h 28 27 20
- Start-up time 10 s 1/h 10 8 4
Normal starting (CLASS 10E)
Rated motor current IM, Tu = 40/50/60 °C A 113/101/89 139/127/116 158/146/129
ON period = 70%; motor protection activated
• 300% IM
- Start-up time 10 s 1/h 21 21 21
- Start-up time 20 s 1/h 8 8 8
6
• 350% IM
- Start-up time 10 s 1/h 13 12 12
- Start-up time 20 s 1/h 4 1 1
Heavy starting (CLASS 20E)
Rated motor current IM, Tu = 40/50/60 °C A 109/97/85 113/103/93 129/117/105
ON period = 70%; motor protection activated
• 300% IM
- Start-up time 20 s 1/h 10 10 10
- Start-up time 40 s 1/h 4 4 4
• 350% IM
- Start-up time 20 s 1/h 7 7 7
- Start-up time 40 s 1/h 2.5 2.5 2.5
Adjustable rated motor current IM
• Minimum/maximum A 53/113 68/143 81/171
• Minimum/maximum in inside-delta circuits A 91.8/196 118/248 140/296
• 350% IM
- Start-up time 10 s 1/h 12 13 12 13 13 11
- Start-up time 20 s 1/h 1 4 3 4 4 2
Heavy starting (CLASS 20E)
Rated motor current IM, Tu = 40/50/60 °C A 162/146/130 200/180/160 195/171/147 258/230/202 272/236/218 284/262/240
ON period = 70%; motor protection activated
• 300% IM
- Start-up time 20 s 1/h 10 10 10 10 10 10
- Start-up time 40 s 1/h 4 4 4 4 4 4
• 350% IM
- Start-up time 20 s 1/h 7 7 7 7 7 7
- Start-up time 40 s 1/h 2.5 2.5 2.5 2.5 2.5 2.5
Adjustable rated motor current IM
• Minimum/maximum A 90/210 100/250 135/315 160/370 200/470 240/570
• Minimum/maximum in inside-delta circuits A 156/364 173/433 234/546 277/641 346/814 416/987
Q1 Q1
Q11 Q11
NSB0_01902
IC01_00544
M M
3~ 3~
Soft starters Motor starter protectors/circuit breakers Motor starter protectors/circuit breakers
for 400 V systems for 500 V systems for 400 V systems for 500 V systems
Q11 Q1 Iq Q1 Iq Q1 Iq Q1 Iq
Type Type kA Type kA Type kA Type kA
Type of Standard (inline) circuit Inside-delta circuit
6
ToC
coordination 1
"1"
3RW5213 3RV2032-4TA10 65 3RV2032-4TA10 18 3RV2032-4DA10 65 3RV2032-4DA10 18
3RW5214 3RV2032-4DA10 65 3RV2032-4DA10 15 3RV2032-4EA10 65 3RV2032-4EA10 15
3RW5215 3RV2032-4EA10 65 3RV2032-4EA10 15 3RV2032-4VA10 65 3RV2032-4VA10 15
3RW5216 3RV2032-4VA10 65 3RV2032-4VA10 10 3RV2032-4JA10 65 3RV2032-4JA10 10
3RW5217 3RV2032-4WA10 65 3RV2032-4WA10 10 3RV2032-4RA10 65 3RV2032-4RA10 10
3RW5224 3RV2032-4JA10 65 3RV2032-4JA10 10 3RV2032-4RA10 65 3RV2032-4RA10 10
3RW5225 3VA2163-7MN32-0AA0 65 3VA2163-7MN32-0AA0 20 3VA2110-7MN32-0AA0 65 3VA2110-7MN32-0AA0 20
3RW5226 3VA2110-7MN32-0AA0 65 3VA2110-7MN32-0AA0 20 3VA2216-7MN32-0AA0 65 3VA2216-7MN32-0AA0 20
3RW5227 3VA2216-7MN32-0AA0 15 3VA2216-7MN32-0AA0 10 3VA2220-7MN32-0AA0 15 3VA2220-7MN32-0AA0 10
3RW5234 3VA2216-7MN32-0AA0 65 -- -- 3VA2220-7MN32-0AA0 65 -- --
3RW5235 3VA2220-7MN32-0AA0 65 -- -- 3VA2325-7MN32-0AA0 65 -- --
3RW5236 3VA2325-7MN32-0AA0 30 3VA2325-7MN32-0AA0 10 3VA2440-7MN32-0AA0 30 3VA2440-7MN32-0AA0 10
3RW5243 3VA2325-7MN32-0AA0 65 3VA2325-7MN32-0AA0 65 3VA2440-7MN32-0AA0 65 3VA2440-7MN32-0AA0 65
3RW5244 3VA2440-7MN32-0AA0 65 3VA2440-7MN32-0AA0 65 3VA2450-7MN32-0AA0 65 3VA2450-7MN32-0AA0 65
3RW5245 3VA2440-7MN32-0AA0 65 3VA2440-7MN32-0AA0 65 3VA2580-6HN32-0AA0 65 3VA2580-6HN32-0AA0 65
3RW5246 3VA2440-7MN32-0AA0 65 3VA2440-7MN32-0AA0 65 3VA2580-6HN32-0AA0 65 3VA2580-6HN32-0AA0 65
3RW5247 3VA2450-7MN32-0AA0 65 3VA2450-7MN32-0AA0 65 3VA2510-6HN32-0AA0 65 3VA2510-6HN32-0AA0 65
3RW5248 3VA2580-6HN32-0AA0 65 3VA2580-6HN32-0AA0 65 3VA2510-6HN32-0AA0 65 3VA2510-6HN32-0AA0 65
Note:
The service factor and measurement inaccuracies, for example,
have been taken into account for the selection of the specified
motor starter protectors/circuit breakers; the specified short-
circuit breaking capacities Iq in kA are covered by combination
tests. Smaller motor starter protectors/circuit breakers from the
same series can be used at any time as smaller ones trip more
quickly in the event of a short circuit (unchanged short-circuit
breaking capacity) and thus protect the soft starter in any case.
The dimensioning of the short-circuit components must match
the connected three-phase motor, the short-circuit and overload
requirements of the application, and the line protection for the
cables used.
F1 F1 F1
IC01_00545a
NSB0_01904
IC01_00565
M M M
3~ 3~ 3~
Soft starters gG class fuse Line contactor (optional) gG class fuse Line contactor (optional)
for systems for systems for systems for systems for systems for systems for systems for systems
6
Note:
The specified short-circuit breaking capacities Iq in kA are
covered by combination tests. Smaller fuses than those
specified can be used at any time as smaller ones trip more
quickly in the event of a short circuit (unchanged short-circuit
breaking capacity) and thus protect the soft starter in any case.
The dimensioning of the short-circuit components must,
however, be suitable for the connected three-phase motor
and the line protection for the cables used.
F’1
Q21
Q11
NSB0_01905
M
3~
6
up to 600 V up to 480 V up to 600 V
Q11 F’1 Q21 Q21
Type Type Type Type
Type of ToC Standard (inline) circuit
coordination 2
"2"
3RW5213 3NE1815-0 3RT2025 3RT2025
3RW5214 3NE1802-0 3RT2026 3RT2027
3RW5215 3NE1817-0 3RT2027 3RT2037
3RW5216 3NE1818-0 3RT2035 3RT2037
3RW5217 3NE1820-0 3RT2035 3RT2037
3RW5224 3NE1021-2 3RT2036 3RT2037
3RW5225 3NE1022-0 3RT2037 3RT2046
3RW5226 3NE1224-0 3RT2038 3RT2046
3RW5227 3NE1224-0 3RT2046 3RT2047
3RW5234 3NE1225-0 3RT1054 3RT1054
3RW5235 3NE1227-0 3RT1055 3RT1055
3RW5236 3NE1230-0 3RT1056 3RT1064
3RW5243 3NE1230-21) 3RT1064 3RT1064
3RW5244 3NE1331-0 3RT1065 3RT1065
3RW5245 3NE1334-2 3RT1075 3RT1075
3RW5246 3NE1334-2 3RT1075 3RT1075
3RW5247 3NE1436-2 3RT1076 3RT1276
3RW5248 3NE1437-2 3TF68 3TF68
1)
For systems up to 500 V.
Note:
The specified short-circuit breaking capacities Iq in kA are
covered by combination tests. Smaller fuses than those
specified can be used at any time as smaller ones trip more
quickly in the event of a short circuit (unchanged short-circuit
breaking capacity) and thus protect the soft starter in any case.
The dimensioning of the short-circuit components must,
however, be suitable for the connected three-phase motor
and the line protection for the cables used.
In inside-delta circuits, a gR/gS class full-range fuse could not
provide the semiconductor protection of the delta-connected
soft starter with a short-circuit breaking capacity that is
adequate for practical use. In this case, we recommend using
aR class partial-range fuses for semiconductor protection for
type of coordination "2" (see page 6/66).
F1 F1 F1
F3 F3 F3
IC01_00546a
IC01_00566
M M M
3~ 3~ 3~
Soft starters gG class fuse aR class fuse Line contactor gG class fuse aR class fuse Line contactor (optional)
(optional)
6
for systems for systems for for for systems for systems for systems for systems for for
up to 600 V up to 500 V systems systems up to 600 V up to 600 V up to 480 V up to 600 V systems systems
up to up to in the supply in the supply up to 480 V up to 600 V
480 V 600 V cable cable in the delta in the delta
Q11 F1 F3 Q21 Q21 F1 F3 Q21 Q21 Q21 Q21
Type Type Type Type Type Type Type Type Type Type Type
Type of ToC Standard (inline) circuit Inside-delta circuit
coordination 2
"2"
3RW5213 3NA3820-6 3NE8017-1 3RT2025 3RT2025 3NA3820-6 3NE8017-1 3RT2027 3RT2035 3RT2025 3RT2025
3RW5214 3NA3820-6 3NE8020-1 3RT2026 3RT2027 3NA3820-6 3NE8020-1 3RT2027 3RT2037 3RT2026 3RT2027
3RW5215 3NA3822-6 3NE8021-1 3RT2027 3RT2037 3NA3822-6 3NE8021-1 3RT2036 3RT2037 3RT2027 3RT2037
3RW5216 3NA3824-6 3NE8022-1 3RT2035 3RT2037 3NA3824-6 3NE8022-1 3RT2037 3RT2038 3RT2035 3RT2037
3RW5217 3NA3824-6 3NE8024-1 3RT2035 3RT2037 3NA3824-6 3NE8024-1 3RT2038 3RT2046 3RT2035 3RT2037
3RW5224 3NA3824-6 3NE8024-1 3RT2036 3RT2037 3NA3824-6 3NE8024-1 3RT2046 3RT2047 3RT2036 3RT2037
3RW5225 3NA3830-6 3NE8024-1 3RT2037 3RT2046 3NA3830-6 3NE8024-1 3RT2047 3RT1054 3RT2037 3RT2046
3RW5226 3NA3132-6 3NE8024-1 3RT2038 3RT2046 3NA3132-6 3NE8024-1 3RT1055 3RT1055 3RT2038 3RT2046
3RW5227 3NA3136-6 3NE4124 3RT2046 3RT2047 3NA3136-6 3NE4124 3RT1056 3RT1056 3RT2046 3RT2047
3RW5234 3NA3244-6 3NE3332-0B 3RT1054 3RT1054 3NA3244-6 3NE3332-0B 3RT1064 3RT1064 3RT1054 3RT1054
3RW5235 3NA3244-6 3NE3334-0B 3RT1055 3RT1055 3NA3244-6 3NE3334-0B 3RT1065 3RT1065 3RT1055 3RT1055
3RW5236 3NA3365-6 3NE3335 3RT1056 3RT1064 3NA3365-6 3NE3335 3RT1066 3RT1075 3RT1056 3RT1064
3RW5243 2 x 3NA3354-6 3NE3333 3RT1064 3RT1064 2 x 3NA3354-6 3NE3333 3RT1075 3RT1075 3RT1064 3RT1064
3RW5244 2 x 3NA3354-6 3NE3336 3RT1065 3RT1065 2 x 3NA3354-6 3NE3336 3RT1076 3RT1076 3RT1065 3RT1065
3RW5245 2 x 3NA3365-6 3NE3336 3RT1075 3RT1075 2 x 3NA3365-6 3NE3336 3TF68 3TF68 3RT1075 3RT1075
3RW5246 2 x 3NA3365-6 3NE3336 3RT1075 3RT1075 2 x 3NA3365-6 3NE3336 3TF69 3TF69 3RT1075 3RT1075
3RW5247 2 x 3NA3365-6 3NE3340-8 3RT1076 3RT1276 2 x 3NA3365-6 3NE3340-8 3TF69 3TF69 3RT1076 3RT1276
3RW5248 2 x 3NA3365-6 3NE3340-8 3TF68 3TF68 2 x 3NA3365-6 3NE3340-8 -- -- 3TF68 3TF68
Note:
The specified short-circuit breaking capacities Iq in kA are
covered by combination tests. Smaller fuses than those
specified can be used at any time as smaller ones trip more
quickly in the event of a short circuit (unchanged short-circuit
breaking capacity) and thus protect the soft starter in any case.
The dimensioning of the short-circuit components must,
however, be suitable for the connected three-phase motor
and the line protection for the cables used.
For CLASS 10 applications, as an alternative to the gG class
full-range fuses for cable and line protection 3NA3 (F1), 3RV2
motor starter protectors/3VA circuit breakers can also be used,
possibly with reduced short-circuit breaking capacity
(see page 6/63). In these cases, optional line contactors
can be dispensed with.
6
18 4 7.5 -- 15.9 3 5 10 -- 3RW5214-@@C@4 1 1 unit 42S
25 5.5 11 -- 22.3 5 7.5 15 -- 3RW5215-@@C@4 1 1 unit 42S
32 7.5 15 -- 28.4 7.5 10 20 -- 3RW5216-@@C@4 1 1 unit 42S
38 11 18.5 -- 33.5 10 10 20 -- 3RW5217-@@C@4 1 1 unit 42S
47 11 22 -- 41.6 10 10 30 -- 3RW5224-@@C@4 1 1 unit 42S
63 18.5 30 -- 55.5 15 20 40 -- 3RW5225-@@C@4 1 1 unit 42S
77 22 37 -- 68 20 25 50 -- 3RW5226-@@C@4 1 1 unit 42S
93 22 45 -- 82.5 25 30 60 -- 3RW5227-@@C@4 1 1 unit 42S
6
31.5 7.5 15 -- 28 7.5 7.5 20 -- 3RW5214-@@C@4 1 1 unit 42S
43.3 11 18.5 -- 39 10 10 25 -- 3RW5215-@@C@4 1 1 unit 42S
55.4 15 22 -- 49 15 15 30 -- 3RW5216-@@C@4 1 1 unit 42S
65.8 18.5 30 -- 58 15 20 40 -- 3RW5217-@@C@4 1 1 unit 42S
81.4 22 45 -- 72 20 25 50 -- 3RW5224-@@C@4 1 1 unit 42S
109 30 55 -- 96 30 30 75 -- 3RW5225-@@C@4 1 1 unit 42S
133 37 75 -- 118 30 40 75 -- 3RW5226-@@C@4 1 1 unit 42S
161 45 90 -- 143 40 50 100 -- 3RW5227-@@C@4 1 1 unit 42S
Fan covers
Fan cover 3RW5216/17 (1x), -- -- 3RW5983-0FC00 1 1 unit 42S
3RW5226/27 (2x),
3RW523 (2x)
3RW524 (1x) -- -- 3RW5984-0FC00 1 1 unit 42S
3RW5983-0FC00
Terminal covers
Terminal 3RW522 (2x), -- -- 3RW5983-0TC20 1 1 unit 42S
cover 3RW523 (2x)
3RW5983-0TC20
3RW524 (2x) -- -- 3RW5984-0TC20 1 1 unit 42S
6
3RW5984-0TC20
Enclosure components
Hinged 3RW52 With cutout -- 3RW5950-0GL30 1 1 unit 42S
cover for High-
Feature
HMI module
3RW5950-0GL30
With cutout -- 3RW5950-0GL40 1 1 unit 42S
for Standard
HMI module
3RW5950-0GL40
Communications modules
Communica- 3RW52 PROFINET -- 3RW5980-0CS00 1 1 unit 42S
tions Standard
module1) PROFIBUS -- 3RW5980-0CP00 1 1 unit 42S
EtherNet/IP -- 3RW5980-0CE00 1 1 unit 42S
3RW5980-0CS00
Modbus RTU -- 3RW5980-0CR00 1 1 unit 42S
Modbus TCP -- 3RW5980-0CT00 1 1 unit 42S
3RW5980-0CR00
1)
Use the recommended connection plugs for attaching the bus connecting
cable (e.g. angled or suitable for industrial use), see Equipment Manual for
the relevant communications module.
HMI modules
HMI module 3RW52 High-Feature -- 3RW5980-0HF00 1 1 unit 42S
3RW5980-0HF00
Standard -- 3RW5980-0HS00 1 1 unit 42S
3RW5980-0HS00
IP65 door 3RW52 IP65 For 3RW5980-0HD00 1 1 unit 42S
mounting kit HMI modules
for HMI
modules
6
3RW5980-0HD00
Connecting cables
HMI 3RW52 5 m, round For door 3RW5980-0HC60 1 1 unit 42S
connecting 2.5 m, round mounting 3UF7933-0BA00-0 1 1 unit 42J
cable
3UF793.-0BA00-0 1.0 m, round 3UF7937-0BA00-0 1 1 unit 42J
0.5 m, round 3UF7932-0BA00-0 1 1 unit 42J
0.1 m, flat For mounting 3UF7931-0AA00-0 1 1 unit 42J
in the device
3UF7931-0AA00-0
Further accessories
Push-in lugs -- Two lugs are For 3ZY1311-0AA00 1 10 units 41L
for wall required per HMI modules
mounting device and commu-
nications
modules
3ZY1311-0AA00
Blank labels
Unit labeling -- 20 mm x For 3RT2900-1SB20 100 340 41B
plates1) 7 mm, SIRIUS units
titanium gray devices
IC01_00181
3RT2900-1SB20
1) PC labeling system for individual inscription
of unit labeling plates available from:
murrplastik Systemtechnik GmbH
(see page 16/18).
■ Overview
More information
Homepage, see www.siemens.com/sirius-soft-starter Simulation Tool for Soft Starters (STS), see page 6/9 or
Industry Mall, see www.siemens.com/product?3RW50 https://support.industry.siemens.com/cs/ww/en/view/101494917
TIA Selection Tool Cloud (TST Cloud), see SIRIUS Soft Starter ES (TIA Portal) for diagnostics, see page 6/9 or
www.siemens.com/tstcloud/?node=3rw50 https://support.industry.siemens.com/cs/ww/en/ps/24230/dl
Industry Online Support (SIOS) topic page, see Decision-making support for motor starting – Starting and running three-phase
https://support.industry.siemens.com/cs/ww/en/view/109747404 asynchronous motors efficiently, see www.siemens.com/motorstart-guide
Conversion tool, see www.siemens.com/conversion-tool
6
SIRIUS 3RW50 soft starters device family
7 8
11
2
9
4
5 6
10
SIRIUS 3RW50 Basic Performance soft starter with accessories (see page 6/82), for expansion with HMI module or communications module
■ Benefits
6
Hybrid switching technology and 2-phase motor control Minimum power loss and optimized motor control by avoiding DC components
Small and compact design Space-saving, clearly arranged control panel layout
TIA integration – communications modules and HMI modules optional Efficient configuration and maximum flexibility in automation engineering
Motor overload and intrinsic device protection without additional wiring Adjustable trip classes, integrated diagnostics functions
Wide range for control supply and main voltage Low variance, high system availability even with weak supply networks
Certified according to ATEX/IECEx directive Suitable for the starting of explosion-proof motors with "increased safety" type
of protection
■ Technical specifications
More information
Technical specifications, see FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/25252/faq
https://support.industry.siemens.com/cs/ww/en/ps/25252/td Simulation Tool for Soft Starters (STS), see page 6/9 or
Equipment Manual, see https://support.industry.siemens.com/cs/ww/en/view/101494917
https://support.industry.siemens.com/cs/ww/en/view/109753750
6
Distance to be maintained with side-by-side mounting
• Above mm 100
• At the side mm 5
• Below mm 75
Installation altitude at height above sea level, maximum1) m 5 000
Degree of protection IP on the front according to IEC 60529 IP00 (IP20 with cover)
Touch protection on the front according to IEC 60529 Finger-safe for vertical touching from the front with cover
Ambient conditions
Ambient temperature
• During operation2) °C -25 ... +60
• During storage and transport °C -40 ... +80
Environmental category according to IEC 60721
• During operation 3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist),
3S2 (sand must not get into the devices), 3M6
• During storage 1K6 (only occasional condensation), 1C2 (no salt mist),
1S2 (sand must not get into the devices), 1M4
• During transport 2K2, 2C1, 2S1, 2M2 (max. height of fall 0.3 m)
1) Derating from 1 000 m, see characteristic curve on page 6/8. 2) Note derating above 40 °C.
• 350% IM
- Start-up time 10 s 1/h 12 9
- Start-up time 20 s 1/h 4 --
Heavy starting (CLASS 20E)
Rated motor current IM, Tu = 40/50/60 °C A 108/98/88 135/123/111
ON period = 70%; motor protection activated
• 300% IM
- Start-up time 20 s 1/h 10 10
- Start-up time 40 s 1/h 4 4
• 350% IM
- Start-up time 20 s 1/h 7 7
- Start-up time 40 s 1/h 2.5 2.5
Adjustable rated motor current IM
• Minimum/maximum A 68/143 81/117
Type 10
3RW5072 3RW5073 3RW5074 3RW5075 3RW5076 3RW5077
Rated operational current Ie A 210 250 315 370 470 570
Power electronics
Load rating with rated operational current Ie
IEC + UL/CSA, individual mounting at 40/50/60 °C, A 210/186/170 250/220/200 315/279/255 370/328/300 470/416/380 570/504/460
AC-53a
Permissible rated motor current and starts/h
Normal starting (CLASS 10A)
Rated motor current IM, Tu = 40/50/60 °C A 210/186/170 250/220/200 315/279/255 370/328/300 470/416/380 570/504/460
ON period = 70%; motor protection activated
• 300% IM
- Start-up time 5 s 1/h 43 43 43 43 43 28
- Start-up time 10 s 1/h 18 18 18 18 18 11
• 350% IM
- Start-up time 5 s 1/h 28 28 28 28 28 16
- Start-up time 10 s 1/h 8 10 10 10 10 4
Normal starting (CLASS 10E)
Rated motor current IM, Tu = 40/50/60 °C A 210/186/170 250/220/200 315/279/255 370/328/300 470/416/380 570/504/460
ON period = 70%; motor protection activated
• 300% IM
- Start-up time 10 s 1/h 21 21 21 21 20 21
- Start-up time 20 s 1/h 8 8 8 8 7 8
• 350% IM
- Start-up time 10 s 1/h 8 13 12 13 12 13
- Start-up time 20 s 1/h -- 4 4 4 2 4
Heavy starting (CLASS 20E)
Rated motor current IM, Tu = 40/50/60 °C A 162/146/130 200/180/160 219/195/171 258/230/202 272/254/218 284/262/240
ON period = 70%; motor protection activated
• 300% IM
- Start-up time 20 s 1/h 10 10 10 10 10 10
- Start-up time 40 s 1/h 4 4 4 4 4 4
• 350% IM
- Start-up time 20 s 1/h 7 7 7 7 7 7
- Start-up time 40 s 1/h 2.5 2.5 2.5 2.5 2.5 2.5
Adjustable rated motor current IM
• Minimum/maximum A 90/210 100/250 135/315 160/370 200/470 240/570
Q1
Q11
NSB0_01902
M
3~
6
ToC
coordination 1
"1"
3RW5055 3VA2220-7MN32-0AA0 20 3VA2220-7MN32-0AA0 20
3RW5056 3VA2220-7MN32-0AA0 20 3VA2220-7MN32-0AA0 20
3RW5072 3VA2440-7MN32-0AA0 65 3VA2440-7MN32-0AA0 65
3RW5073 3VA2440-7MN32-0AA0 65 3VA2440-7MN32-0AA0 65
3RW5074 3VA2440-7MN32-0AA0 65 3VA2440-7MN32-0AA0 65
3RW5075 3VA2580-6HN32-0AA0 65 3VA2580-6HN32-0AA0 65
3RW5076 3VA2580-6HN32-0AA0 65 3VA2580-6HN32-0AA0 65
3RW5077 3VA2580-6HN32-0AA0 65 3VA2580-6HN32-0AA0 65
Note:
The service factor and measurement inaccuracies, for example,
have been taken into account for the selection of the specified
motor starter protectors/circuit breakers; the specified short-
circuit breaking capacities Iq in kA are covered by combination
tests. Smaller motor starter protectors/circuit breakers from the
same series can be used at any time as smaller ones trip more
quickly in the event of a short circuit (unchanged short-circuit
breaking capacity) and thus protect the soft starter in any case.
The dimensioning of the short-circuit components must match
the connected three-phase motor, the short-circuit and overload
requirements of the application, and the line protection for the
cables used.
F1
Q21
Q11
NSB0_01904
M
3~
Note:
The specified short-circuit breaking capacities Iq in kA are
covered by combination tests. Smaller fuses than those
specified can be used at any time as smaller ones trip more
quickly in the event of a short circuit (unchanged short-circuit
breaking capacity) and thus protect the soft starter in any case.
The dimensioning of the short-circuit components must,
however, be suitable for the connected three-phase motor
and the line protection for the cables used.
F’1
Q21
Q11
NSB0_01905
M
3~
6
up to 600 V up to 480 V up to 600 V
Q11 F’1 Q21 Q21
Type Type Type Type
Type of ToC Standard (inline) circuit
coordination 2
"2"
3RW5055 3NE1227-0 3RT1055 3RT1055
3RW5056 3NE1230-0 3RT1056 3RT1064
3RW5072 3NE1230-2 3RT1064 3RT1064
3RW5073 3NE1331-0 3RT1065 3RT1065
3RW5074 3NE1333-2 3RT1075 3RT1075
3RW5075 3NE1334-2 3RT1075 3RT1075
3RW5076 3NE1436-2 3RT1076 3RT1076
3RW5077 3NE1437-2 3TF68 3TF68
Note:
The specified short-circuit breaking capacities Iq in kA are
covered by combination tests. Smaller fuses than those
specified can be used at any time as smaller ones trip more
quickly in the event of a short circuit (unchanged short-circuit
breaking capacity) and thus protect the soft starter in any case.
The dimensioning of the short-circuit components must,
however, be suitable for the connected three-phase motor
and the line protection for the cables used.
F1
Q21
F3
Q11
NSB0_01906
M
3~
Note:
The specified short-circuit breaking capacities Iq in kA are
covered by combination tests. Smaller fuses than those
specified can be used at any time as smaller ones trip more
quickly in the event of a short circuit (unchanged short-circuit
breaking capacity) and thus protect the soft starter in any case.
The dimensioning of the short-circuit components must,
however, be suitable for the connected three-phase motor
and the line protection for the cables used.
For CLASS 10 applications, as an alternative to the gG class full-
range fuses for cable and line protection 3NA3 (F1), 3VA circuit
breakers can also be used, possibly with reduced short-circuit
breaking capacity (see page 6/77). In these cases, optional line
contactors can be dispensed with.
3RW5055 3RW5075
At 40 °C At 50 °C Size Article No. Price PU PS* PG
Opera- Operating power Opera- Rating [hp] for three-phase motors per PU (UNIT,
tional for three-phase tional SET, M)
current motors current
at at at at at at at
230 V 400 V 500 V 200/208 V 220/230 V 460/480 V 575/600 V
A kW kW kW A hp hp hp hp
Operational voltage 200 ... 480 V
143 37 75 -- 128 40 40 100 -- S6 3RW5055-@@B@4 1 1 unit 42S
171 45 -- 153 50 50 -- S6 1 1 unit 42S
6
90 100 3RW5056-@@B@4
210 55 110 -- 186 60 60 150 -- S12 3RW5072-@@B@4 1 1 unit 42S
250 75 132 -- 220 60 75 150 -- S12 3RW5073-@@B@4 1 1 unit 42S
315 90 160 -- 279 75 100 200 -- S12 3RW5074-@@B@4 1 1 unit 42S
370 110 200 -- 328 100 125 250 -- S12 3RW5075-@@B@4 1 1 unit 42S
470 132 250 -- 416 150 150 350 -- S12 3RW5076-@@B@4 1 1 unit 42S
570 160 315 -- 504 150 200 400 -- S12 3RW5077-@@B@4 1 1 unit 42S
Fan covers
Fan cover 3RW50 (1x) -- -- 3RW5985-0FC00 1 1 unit 42S
3RW5985-0FC00
Box terminal block
Box terminal 3RW505 (2x) Up to 70 mm2 -- 3RT1955-4G 1 1 unit 41B
block for round Up to 120 mm2 -- 3RT1956-4G 1 1 unit 41B
and ribbon
cables 3RW507 (2x) Up to -- 3RT1966-4G 1 1 unit 41B
240 mm2
(with auxiliary
3RT1956-4G conductor
connection)
Terminal covers
Covers for 3RW505 (2x) -- -- 3RT1956-4EA2 1 1 unit 41B
box terminals 3RW507 (2x) -- -- 3RT1966-4EA2 1 1 unit 41B
6
3RT1956-4EA2
Covers for 3RW505 (2x) -- -- 3RT1956-4EA1 1 1 unit 41B
cable lugs 3RW507 (2x) -- -- 3RT1966-4EA1 1 1 unit 41B
and busbar
connections
3RT1966-4EA1
Communications modules
Communica- 3RW50 PROFINET -- 3RW5980-0CS00 1 1 unit 42S
tions module1) Standard
PROFIBUS 3RW5980-0CP00 1 1 unit 42S
EtherNet/IP 3RW5980-0CE00 1 1 unit 42S
Modbus RTU 3RW5980-0CR00 1 1 unit 42S
Modbus TCP 3RW5980-0CT00 1 1 unit 42S
3RW5980-0CS00
COM 3RW50 0.3 m, round -- 3RW5900-0CC00 1 1 unit 42S
connecting
cable
3RW5900-0CC00 For mounting
laterally on the
device
1)
Use the recommended connection plugs for attaching the bus connecting
cable (e.g. angled or suitable for industrial use), see Equipment Manual for
the relevant communications module.
HMI modules
HMI module 3RW50 High-Feature -- 3RW5980-0HF00 1 1 unit 42S
3RW5980-0HF00
Standard -- 3RW5980-0HS00 1 1 unit 42S
3RW5980-0HS00
IP65 door 3RW50 IP65 For HMI 3RW5980-0HD00 1 1 unit 42S
mounting kit modules
for HMI
modules
6
3RW5980-0HD00
Connecting cables
HMI 3RW50 5 m, round For door 3RW5980-0HC60 1 1 unit 42S
connecting 2.5 m, round mounting 3UF7933-0BA00-0 1 1 unit 42J
cable
3UF793.-0BA00-0 1.0 m, round 3UF7937-0BA00-0 1 1 unit 42J
0.5 m, round 3UF7932-0BA00-0 1 1 unit 42J
Further accessories
Push-in lugs -- Two lugs are For HMI 3ZY1311-0AA00 1 10 units 41L
for wall required per modules
mounting device and com-
munica-
tions
modules
3ZY1311-0AA00
Blank labels
Unit labeling -- 20 mm x For SIRIUS 3RT2900-1SB20 100 340 41B
plates1) 7 mm, devices units
titanium gray
IC01_00181
3RT2900-1SB20
1)
PC labeling system for individual inscription
of unit labeling plates available from:
murrplastik Systemtechnik GmbH
(see page 16/18).
■ Overview
More information
Homepage, see www.siemens.com/sirius-soft-starter TIA Selection Tool Cloud (TST Cloud), see
Industry Mall, see www.siemens.com/product?3RW40 www.siemens.com/tstcloud/?node=3rw40
Simulation Tool for Soft Starters (STS), see page 6/9 or
https://support.industry.siemens.com/cs/ww/en/view/101494917
Conversion tool, see www.siemens.com/conversion-tool
8
IC01_00539a
SIRIUS 3RW40 Basic Performance soft starter with accessories (see page 6/94)
■ Benefits
Small and compact design Space-saving, clearly arranged control panel layout
Motor overload and intrinsic device protection without additional wiring Adjustable trip classes, integrated diagnostics functions
Integrated in the SIRIUS modular system Link modules to motor starter protectors
Hybrid switching technology and 2-phase motor control Minimum power loss and optimized motor control by avoiding DC components
6
Certified according to ATEX Directive 94/9/EC Suitable for starting explosion-proof motors with "increased safety" type of
protection EEx e.
■ Technical specifications
More information
Technical specifications, see FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/25251/faq
https://support.industry.siemens.com/cs/ww/en/ps/25251/td Simulation Tool for Soft Starters (STS), see page 6/9 or
Equipment Manual, see https://support.industry.siemens.com/cs/ww/en/view/101494917
https://support.industry.siemens.com/cs/ww/en/view/38752095
D
W
NSB0_00649a
22,5° 22,5°
(for 3RW402. to 3RW404.) 90° 90°
6
NSB0_01897
Installation type1) Stand-alone
installation
16%B
16%B
ุPP ุLQ ุPP ุLQ
ุPP ุLQ ุPP ุLQ
ุPP ุLQ ุPP ุLQ
6
2) Current limiting on soft starter set to 300% IM, Tu = 40/50 °C. installation vertical. The quoted switching frequencies do not apply for
Maximum adjustable rated motor current IM dependent on CLASS setting. automatic mode. Factors for permissible switching frequency in other
mounting position, direct mounting, side-by-side mounting, and
implementation of optional auxiliary fan, see Equipment Manual
in the chapter "Configuration".
Q1
Q11
NSB0_01902
M
3~
ToC
coordination 1
"1"
3RW4024 3RV2021-4AA10 55 3RV2021-4AA10 10
3RW4026 3RV2021-4DA10 55 3RV2021-4DA10 10
3RW4027 3RV2021-4EA10 55 3RV2021-4EA10 10
3RW4028 3RV2021-4FA10 55 3RV2021-4FA10 10
3RW4036 3RV2031-4WA10 10 3RV2031-4WA10 10
3RW4037 3RV2031-4JA10 10 3RV2031-4JA10 5
3RW4038 3RV2031-4KA10 10 3RV2031-4KA10 5
3RW4046 3RV2041-4RA10 11 3RV2041-4YA10 5
3RW4047 3RV2041-4MA10 11 3RV2041-4MA10 5
Note:
The specified short-circuit breaking capacities Iq in kA
are covered by combination tests. Smaller motor starter
protectors/circuit breakers from the same series can be used at
any time as smaller ones trip more quickly in the event of a short
circuit (unchanged short-circuit breaking capacity) and thus
protect the soft starter in any case. The dimensioning of the
short-circuit components must match the connected three-
phase motor, the short-circuit and overload requirements of
the application, and the line protection for the cables used.
F1
Q21
Q11
NSB0_01904
M
3~
6
up to 600 V up to 400 V up to 480 V up to 600 V
Q11 F1 Q21 Q21 Q21
Type Type Type Type Type
Type of ToC Standard (inline) circuit
coordination 1
"1"
3RW4024 3NA3820-6 3RT2025 3RT2025/ 3RT2025
3RT2018
(in size S00)
3RW4026 3NA3822-6 3RT2026 3RT2027 3RT2037
3RW4027 3NA3824-6 3RT2027 3RT2028 3RT2037
3RW4028 3NA3824-6 3RT2028 3RT2035 3RT2037
3RW4036 3NA3130-6 3RT2036 3RT2036 3RT2038
3RW4037 3NA3132-6 3RT2037 3RT2037 3RT2046
3RW4038 3NA3132-6 3RT2038 3RT2038 3RT2046
3RW4046 3NA3136-6 3RT2045 3RT2045 3RT2047
3RW4047 3NA3136-6 3RT2047 3RT2047 3RT1054
Note:
The specified short-circuit breaking capacities Iq in kA are
covered by combination tests. Smaller fuses than those
specified can be used at any time as smaller ones trip more
quickly in the event of a short circuit (unchanged short-circuit
breaking capacity) and thus protect the soft starter in any case.
The dimensioning of the short-circuit components must,
however, be suitable for the connected three-phase motor
and the line protection for the cables used.
F’1
Q21
Q11
NSB0_01905
M
3~
Note:
The specified short-circuit breaking capacities Iq in kA are
covered by combination tests. Smaller fuses than those
specified can be used at any time as smaller ones trip more
quickly in the event of a short circuit (unchanged short-circuit
breaking capacity) and thus protect the soft starter in any case.
The dimensioning of the short-circuit components must,
however, be suitable for the connected three-phase motor
and the line protection for the cables used.
F1
Q21
F3
Q11
NSB0_01906
M
3~
Soft starters gG class fuse aR class fuse Cylindrical Line contactor (optional)
fuse
6
for systems for systems for systems for systems for systems for systems for systems for systems
up to 600 V up to 600 V up to 600 V up to 600 V up to 480 V up to 400 V up to 480 V up to 600 V
Q11 F1 F3 F3 F3 F3 Q21 Q21 Q21
Type Type Type Type Type Type Type Type Type
Type of ToC Standard (inline) circuit
coordination 2
"2"
3RW4024 3NA3820-6 -- 3NE4101 3NE8015-1 3NC2240 3RT2025 3RT2025/ 3RT2025
3RT2018
(in size S00)
3RW4026 3NA3822-6 -- 3NE4102 3NE8017-1 3NC2263 3RT2026 3RT2027 3RT2037
3RW4027 3NA3824-6 -- 3NE4118 3NE8018-1 3NC2280 3RT2027 3RT2028 3RT2037
3RW4028 3NA3824-6 -- 3NE4118 3NE8020-1 3NC2280 3RT2028 3RT2035 3RT2037
3RW4036 3NA3130-6 -- 3NE4120 3NE8020-1 3NC2280 3RT2036 3RT2036 3RT2038
3RW4037 3NA3132-6 -- 3NE4121 3NE8021-1 -- 3RT2037 3RT2037 3RT2046
3RW4038 3NA3132-6 3NE3221 -- 3NE8022-1 -- 3RT2038 3RT2038 3RT2046
3RW4046 3NA3136-6 3NE3222 -- 3NE8022-1 -- 3RT2045 3RT2045 3RT2047
3RW4047 3NA3136-6 3NE3224 -- 3NE8024-1 -- 3RT2047 3RT2047 3RT1054
Note:
The specified short-circuit breaking capacities Iq in kA are
covered by combination tests. Smaller fuses than those
specified can be used at any time as smaller ones trip more
quickly in the event of a short circuit (unchanged short-circuit
breaking capacity) and thus protect the soft starter in any case.
The dimensioning of the short-circuit components must,
however, be suitable for the connected three-phase motor
and the line protection for the cables used.
For CLASS 10 applications, as an alternative to the gG class
full-range fuses for cable and line protection 3NA3 (F1), 3RV2
motor starter protectors can also be used, possibly with reduced
short-circuit breaking capacity (see page 6/88). In these cases,
optional line contactors can be dispensed with.
6
25 5.5 11 -- 23 5 5 15 -- S0 3RW4026-@TB04 1 1 unit 42G
32 7.5 15 -- 29 7.5 7.5 20 -- S0 3RW4027-@TB04 1 1 unit 42G
38 11 18.5 -- 34 10 10 25 -- S0 3RW4028-@TB04 1 1 unit 42G
45 11 22 -- 42 10 15 30 -- S2 3RW4036-@TB04 1 1 unit 42G
63 18.5 30 -- 58 15 20 40 -- S2 3RW4037-@TB04 1 1 unit 42G
72 22 37 -- 62 20 20 40 -- S2 3RW4038-@TB04 1 1 unit 42G
80 22 45 -- 73 20 25 50 -- S3 3RW4046-@TB04 1 1 unit 42G
106 30 55 -- 98 30 30 75 -- S3 3RW4047-@TB04 1 1 unit 42G
Rated operational voltage Ue 400 ... 600 V,
with thermistor motor protection,
rated control supply voltage Us 24 V AC/DC
12.5 -- 5.5 7.5 11 -- -- 7.5 10 S0 3RW4024-@TB05 1 1 unit 42G
25 -- 11 15 23 -- -- 15 20 S0 3RW4026-@TB05 1 1 unit 42G
32 -- 15 18.5 29 -- -- 20 25 S0 3RW4027-@TB05 1 1 unit 42G
38 -- 18.5 22 34 -- -- 25 30 S0 3RW4028-@TB05 1 1 unit 42G
45 -- 22 30 42 -- -- 30 40 S2 3RW4036-@TB05 1 1 unit 42G
63 -- 30 37 58 -- -- 40 50 S2 3RW4037-@TB05 1 1 unit 42G
72 -- 37 45 62 -- -- 40 60 S2 3RW4038-@TB05 1 1 unit 42G
80 -- 45 55 73 -- -- 50 60 S3 3RW4046-@TB05 1 1 unit 42G
106 -- 55 75 98 -- -- 75 75 S3 3RW4047-@TB05 1 1 unit 42G
3RV2925-5AB
3RT2946-4F
Covers for soft starters
Terminal covers for box terminals
3RW403. S2 Additional touch protection 3RT2936-4EA2 1 1 unit 41B
3RW404. S3 to be fitted at the box terminals 3RT2946-4EA2 1 1 unit 41B
(two units required per device)
3RT2936-4EA2
Terminal covers for cable lugs and busbar connections
3RW404. S3 For complying with the voltage 3RT1946-4EA1 1 1 unit 41B
clearances and as touch protection
if box terminal is removed
(two units required per device)
3RT1946-4EA1
Sealing covers
3RW402. to S0, S2, -- 3RW4900-0PB10 1 1 unit 42G
3RW404. S3
3RW4900-0PB10
For motor For soft Version Article No. Price PU (UNIT, PS* PG
starter starters per PU SET, M)
protectors
Size Size
DIN-rail adapters
For mechanical fixing of motor
starter protector and soft
starter; for snapping onto
DIN rail or for screw fixing
S2 S2 Single-unit packaging 3RA2932-1CA00 1 1 unit 41B
3RA2932-1CA00
6
3RW404.
3RW49..-8VB00
For soft starters Motor starter protectors Article No. Price PU (UNIT, PS* PG
per PU SET, M)
Type Size Size
Link modules to motor starter protectors1)
• Screw terminals Screw terminals
3RA2921-2GA00
1)
Can be used in size S0 up to maximum 32 A.
Can be used in size S2 up to maximum 65 A in combination with
3RA2932-1CA00 DIN-rail adapter (specially for soft starters).
Can be used in size S3 up to maximum 64 A and only with mounting plate.
3RT2900-1SB20
1)
PC labeling system for individual inscription
of unit labeling plates available from:
murrplastik Systemtechnik GmbH
(see page 16/18).
* You can order this quantity or a multiple thereof.
Illustrations are approximate Siemens IC 10 · 2023 6/95
© Siemens 2023
■ Overview
More information
Homepage, see www.siemens.com/sirius-soft-starter TIA Selection Tool Cloud (TST Cloud), see
Industry Mall, see www.siemens.com/product?3RW30 www.siemens.com/tstcloud/?node=3rw30
Simulation Tool for Soft Starters (STS), see page 6/9 or
https://support.industry.siemens.com/cs/ww/en/view/101494917
Conversion tool, see www.siemens.com/conversion-tool
1
IC01_00538a
SIRIUS 3RW30 Basic Performance soft starter with accessories (see page 6/104)
■ Benefits
Small and compact design Space-saving, clearly arranged control panel layout
Integrated in the SIRIUS modular system Link modules to motor starter protectors
6
Hybrid switching technology and 2-phase motor control Minimum power loss and optimized motor control by avoiding DC components
■ Technical specifications
More information
Equipment Manual, see Catalog LV 10, see www.siemens.com/lowvoltage/lv10
https://support.industry.siemens.com/cs/ww/en/view/38752095
FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/16213/faq
16%B
ุPP ุLQ ุPP ุLQ
ุPP ุLQ ุPP ุLQ
ุPP ุLQ ุPP ุLQ
Power loss
• In operation after completed starting with uninterrupted rated W 0.25 0.5 1 2 4
operational current (40 °C) approx.
• During starting with 300% IM (40 °C) W 24 52 80 80 116
Permissible rated motor current and starts per hour
• For normal starting (CLASS 10) at 40/50 °C
- Rated motor current IM2), start-up time 3 s A 3.6/3.3 6.5/6.0 9/8 12.5/12.0 17.6/17.0
- Starts per hour3) 1/h 200/150 87/60 50/50 85/70 62/46
2)
- Rated motor current IM , start-up time 4 s A 3.6/3.3 6.5/6.0 9/8 12.5/12.0 17.6/17.0
- Starts per hour3) 1/h 150/100 64/46 35/35 62/47 45/32
1) 3)
Measurement at 60 °C according to UL/CSA not required. For intermittent duty S4 with ON period = 30%, Tu = 40/50 °C, stand-alone
2)
At 300% IM, Tu = 40/50 °C. installation vertical. The quoted switching frequencies do not apply for
automatic mode.
Q1
Q11
NSB0_01902
M
3~
6
ToC
coordination 1
"1"
3RW3013 3RV2011-1FA10 5
3RW3014 3RV2011-1HA10 5
3RW3016 3RV2011-1JA10 5
3RW3017 3RV2011-1KA10 5
3RW3018 3RV2021-4BA10 5
3RW3026 3RV2021-4DA10 55
3RW3027 3RV2021-4EA10 55
3RW3028 3RV2021-4FA10 55
3RW3036 3RV2031-4WA10 10
3RW3037 3RV2031-4JA10 10
3RW3038 3RV2031-4KA10 10
3RW3046 3RV2041-4RA10 11
3RW3047 3RV2041-4MA10 11
Note:
The specified short-circuit breaking capacities Iq in kA
are covered by combination tests. Smaller motor starter
protectors/circuit breakers from the same series can be used at
any time as smaller ones trip more quickly in the event of a short
circuit (unchanged short-circuit breaking capacity) and thus
protect the soft starter in any case. The dimensioning of the
short-circuit components must match the connected three-
phase motor, the short-circuit and overload requirements of
the application, and the line protection for the cables used.
F1
Q21
Q11
NSB0_01904
M
3~
Note:
The specified short-circuit breaking capacities Iq in kA are
covered by combination tests. Smaller fuses than those
specified can be used at any time as smaller ones trip more
quickly in the event of a short circuit (unchanged short-circuit
breaking capacity) and thus protect the soft starter in any case.
The dimensioning of the short-circuit components must,
however, be suitable for the connected three-phase motor
and the line protection for the cables used.
F’1
Q21
Q11
NSB0_01905
M
3~
6
up to 480 V up to 400 V up to 480 V
Q11 F’1 Q21 Q21
Type Type Type Type
Type of ToC Standard (inline) circuit
coordination 2
"2"
3RW3013 3NE1813-0 3RT2015 3RT2015
3RW3014 3NE1813-0 3RT2015 3RT2016
3RW3016 3NE1813-0 3RT2016 3RT2017
3RW3017 3NE1813-0 3RT2018 3RT2025
3RW3018 3NE1814-0 3RT2026 3RT2026
3RW3026 3NE1803-0 3RT2026 3RT2027
3RW3027 3NE1020-2 3RT2027 3RT2028
3RW3028 3NE1020-2 3RT2028 3RT2035
3RW3036 3NE1020-2 3RT2036 3RT2036
3RW3037 3NE1820-0 3RT2037 3RT2037
3RW3038 3NE1820-0 3RT2038 3RT2038
3RW3046 3NE1021-0 3RT2045 3RT2045
3RW3047 3NE1022-0 3RT2047 3RT2047
Note:
The specified short-circuit breaking capacities Iq in kA are
covered by combination tests. Smaller fuses than those
specified can be used at any time as smaller ones trip more
quickly in the event of a short circuit (unchanged short-circuit
breaking capacity) and thus protect the soft starter in any case.
The dimensioning of the short-circuit components must,
however, be suitable for the connected three-phase motor
and the line protection for the cables used.
F1
Q21
F3
Q11
NSB0_01906
M
3~
Soft starters gG class fuse aR class fuse Cylindrical fuse Line contactor (optional)
for systems for systems for systems for systems for systems for systems for systems
6
Note:
The specified short-circuit breaking capacities Iq in kA are
covered by combination tests. Smaller fuses than those
specified can be used at any time as smaller ones trip more
quickly in the event of a short circuit (unchanged short-circuit
breaking capacity) and thus protect the soft starter in any case.
The dimensioning of the short-circuit components must,
however, be suitable for the connected three-phase motor
and the line protection for the cables used.
For CLASS 10 applications, as an alternative to the gG class
full-range fuses for cable and line protection 3NA3 (F1), 3RV2
motor starter protectors can also be used, possibly with reduced
short-circuit breaking capacity (see page 6/99). In these cases,
optional line contactors can be dispensed with.
6
3.6 0.75 1.5 -- 3 0.5 0.5 1.5 -- S00 3RW3013-@BB@4 1 1 unit 42G
6.5 1.5 3 -- 6 1 1 3 -- S00 3RW3014-@BB@4 1 1 unit 42G
9 2.2 4 -- 8 2 2 5 -- S00 3RW3016-@BB@4 1 1 unit 42G
12.5 3 5.5 -- 12 3 3 7.5 -- S00 3RW3017-@BB@4 1 1 unit 42G
17.6 4 7.5 -- 17 3 3 10 -- S00 3RW3018-@BB@4 1 1 unit 42G
25 5.5 11 -- 23 5 5 15 -- S0 3RW3026-@BB@4 1 1 unit 42G
32 7.5 15 -- 29 7.5 7.5 20 -- S0 3RW3027-@BB@4 1 1 unit 42G
38 11 18.5 -- 34 10 10 25 -- S0 3RW3028-@BB@4 1 1 unit 42G
45 11 22 -- 42 10 15 30 -- S2 3RW3036-@BB@4 1 1 unit 42G
63 18.5 30 -- 58 15 20 40 -- S2 3RW3037-@BB@4 1 1 unit 42G
72 22 37 -- 62 20 20 40 -- S2 3RW3038-@BB@4 1 1 unit 42G
80 22 45 -- 73 20 25 50 -- S3 3RW3046-@BB@4 1 1 unit 42G
106 30 55 -- 98 30 30 75 -- S3 3RW3047-@BB@4 1 1 unit 42G
3RV2925-5AB
Type Size
Auxiliary conductor terminals
Auxiliary conductor terminals, 3-pole
3RW304. S3 3RT2946-4F 1 1 unit 41B
3RT2946-4F
Covers for soft starters
Terminal covers for box terminals
Additional touch protection to be fitted at the box terminals
(two units required per device)
3RW303. S2 3RT2936-4EA2 1 1 unit 41B
3RW304. S3 3RT2946-4EA2 1 1 unit 41B
3RT2936-4EA2
Terminal covers for cable lugs and busbar connections
For complying with the voltage clearances and as touch
protection if box terminal is removed
(two units required per device)
3RW304. S3 3RT1946-4EA1 1 1 unit 41B
3RT1946-4EA1
3RA2932-1CA00
For soft starters Motor starter protectors Article No. Price PU PS* PG
per PU (UNIT,
SET, M)
Type Size Size
Link modules to motor starter protectors1)
• Screw terminals Screw terminals
3RA2921-2GA00
1)
Can be used in size S0 up to maximum 32 A.
Can be used in size S2 up to maximum 65 A in combination with
6
3RA2932-1CA00 DIN-rail adapter (specially for soft starters).
Can be used in size S3 up to maximum 64 A and only on a mounting plate.
3RT2900-1SB20
1) PC labeling system for individual inscription
of unit labeling plates available from:
murrplastik Systemtechnik GmbH
(see page 16/18).
■ Overview
More information
Homepage, see www.siemens.com/sirius-soft-starter Industry Online Support (SIOS) topic page, see
Industry Mall, see www.siemens.com/product?3RW https://support.industry.siemens.com/cs/ww/en/view/109747404
Control units
Control unit 3RW551..-.HA0., 24 V 3RW5950-1UY00 1 1 unit 42S
3RW552..-.HA0.,
3RW553..-.HA0.,
3RW554..-.HA0.
3RW555..-.HA0. 3RW5955-1UY00 1 1 unit 42S
3RW551..-.HA1., 110 ... 250 V 3RW5950-1UY10 1 1 unit 42S
3RW552..-.HA1.,
3RW553..-.HA1.,
3RW554..-.HA1.
3RW5950-1UY00 3RW555..-.HA1. 3RW5955-1UY10 1 1 unit 42S
Printed circuit boards
Printed circuit 3RW5513-.HA.4 480 V, 13 A 3RW5951-0PA04 1 1 unit 42S
boards 3RW5514-.HA.4 480 V, 18 A 3RW5951-0PB04 1 1 unit 42S
3RW5515-.HA.4 480 V, 25 A 3RW5951-0PC04 1 1 unit 42S
3RW5516-.HA.4 480 V, 32 A 3RW5951-0PD04 1 1 unit 42S
3RW5517-.HA.4 480 V, 38 A 3RW5951-0PE04 1 1 unit 42S
3RW552.-.HA.4, 480 V 3RW5953-0PY04 1 1 unit 42S
6
3RW553.-.HA.4
3RW554.-.HA.4 480 V 3RW5954-0PY04 1 1 unit 42S
3RW5951-0PA04 3RW5513-.HA.5 600 V, 13 A 3RW5951-0PA05 1 1 unit 42S
3RW5514-.HA.5 600 V, 18 A 3RW5951-0PB05 1 1 unit 42S
3RW5515-.HA.5 600 V, 25 A 3RW5951-0PC05 1 1 unit 42S
3RW5516-.HA.5 600 V, 32 A 3RW5951-0PD05 1 1 unit 42S
3RW5517-.HA.5 600 V, 38 A 3RW5951-0PE05 1 1 unit 42S
3RW552.-.HA.6, 690 V 3RW5953-0PY06 1 1 unit 42S
3RW553.-.HA.6
3RW554.-.HA.6 690 V 3RW5954-0PY06 1 1 unit 42S
3RW5954-0PY06 Firing printed 3RW555.-.HA.4 480 V 3RW5955-0PY14 1 1 unit 42S
circuit boards 3RW555.-.HA.6 690 V 3RW5955-0PY16 1 1 unit 42S
TSE printed 3RW555.-.HA.4 480 V 3RW5955-0PY24 1 1 unit 42S
circuit boards 3RW555.-.HA.6 690 V 3RW5955-0PY26 1 1 unit 42S
Fans
Fan 3RW551 (1x), -- 3RW5983-0FF00 1 1 unit 42S
3RW552 (2x),
3RW553 (2x)
3RW554 (1x) -- 3RW5984-0FF00 1 1 unit 42S
3RW555 (3x) -- 3RW5985-0FF00 1 1 unit 42S
3RW5983-0FF00
Terminals and terminal covers
Box terminal 3RW552 (2x) -- 3RW5982-0TB00 1 1 unit 42S
block
3RW5982-0TB00
Removable • Screw terminals Screw terminals
control
terminals 3RW551.-1H... (2x), Contains 2 blocks 3RW5980-1TR00 1 1 unit 42S
3RW552.-1H... (2x), each with 6 terminals
3RW553.-6H... (2x),
3RW554.-6H... (2x),
3RW555.-6H... (2x)
• Spring-loaded terminals Spring-loaded terminals
3RW5955-0TC20
Enclosure components
Lower part of 3RW552.-.HA.., -- 3RW5953-0GB00 1 1 unit 42S
enclosure 3RW553.-.HA..
3RW554.-.HA.. -- 3RW5954-0GB00 1 1 unit 42S
3RW5953-0GB00
Ventilation 3RW555 (3x) -- 3RW5955-0GC00 1 1 unit 42S
cover
3RW5955-0GC00
Cover for 3RW55..-.HA.. Titanium gray 3RW5950-0GD20 1 1 unit 42S
control cable
duct
6
3RW5950-0GD20
Front cover 3RW554.-.HA.. -- 3RW5954-0GF00 1 1 unit 42S
3RW555 -- 3RW5955-0GF00 1 1 unit 42S
3RW5954-0GF00
Hinged cover 3RW55 With cutout for 3RW5950-0GL30 1 1 unit 42S
High-Feature
HMI module
3RW5950-0GL30
HMI modules
HMI module 3RW55 High-Feature 3RW5980-0HF00 1 1 unit 42S
3RW5980-0HF00
Interface cover 3RW55 -- 3RW5980-0HL00 1 1 unit 42S
3RW5980-0HL00
6
Connecting cable for installing the HMI module in the soft starter
Connecting -- Length 0.1 m, flat 3UF7931-0AA00-0 1 1 unit 42J
cable
3UF7931-0AA00-0
Transport packaging
Transport 3RW551 -- 3RW5951-0VY00 1 1 unit 42S
packaging 3RW552, 3RW553 -- 3RW5953-0VY00 1 1 unit 42S
3RW554 -- 3RW5954-0VY00 1 1 unit 42S
3RW555 -- 3RW5955-0VY00 1 1 unit 42S
3RW5953-0VY00
■ Overview
More information
Homepage, see www.siemens.com/sirius-soft-starter Industry Online Support (SIOS) topic page, see
Industry Mall, see www.siemens.com/product?3RW https://support.industry.siemens.com/cs/ww/en/view/109747404
Fans
Fan 3RW551 (1x), -- 3RW5983-0FF00 1 1 unit 42S
3RW552 (2x),
3RW553 (2x)
3RW554 (1x) -- 3RW5984-0FF00 1 1 unit 42S
3RW5983-0FF00
Terminals and terminal covers
Box terminal 3RW552 (2x) -- 3RW5982-0TB00 1 1 unit 42S
6
block
3RW5982-0TB00
Removable • Screw terminals Screw terminals
control
terminals 3RW551.-1H... (2x), Contains 2 blocks 3RW5980-1TR00 1 1 unit 42S
3RW552.-1H... (2x), each with 6 terminals
3RW553.-6H... (2x),
3RW554.-6H... (2x)
• Spring-loaded terminals Spring-loaded terminals
3RW5950-0GD30
Hinged cover 3RW55 With cutout for 3RW5950-0GL30 1 1 unit 42S
High-Feature
HMI module
3RW5950-0GL30
HMI modules
HMI module 3RW55 High-Feature 3RW5980-0HF00 1 1 unit 42S
3RW5980-0HF00
Interface cover 3RW55 -- 3RW5980-0HL00 1 1 unit 42S
3RW5980-0HL00
6
Connecting cable for installing the HMI module in the soft starter
Connecting -- Length 0.1 m, flat 3UF7931-0AA00-0 1 1 unit 42J
cable
3UF7931-0AA00-0
Transport packaging
Transport 3RW551 -- 3RW5951-0VY00 1 1 unit 42S
packaging 3RW552, 3RW553 -- 3RW5953-0VY00 1 1 unit 42S
3RW554 -- 3RW5954-0VY00 1 1 unit 42S
3RW5953-0VY00
■ Overview
More information
Homepage, see www.siemens.com/sirius-soft-starter Industry Online Support (SIOS) topic page, see
Industry Mall, see www.siemens.com/product?3RW https://support.industry.siemens.com/cs/ww/en/view/109747404
3RW5924-0ST05
Bypass units
Bypass unit 3RW522, 3RW523 -- 3RW5953-0BY00 1 1 unit 42S
3RW5243, 3RW5244, 210 ... 315 A 3RW5954-0BP00 1 1 unit 42S
3RW5245
3RW5246, 3RW5247, 370 ... 570 A 3RW5954-0BT00 1 1 unit 42S
3RW5248
3RW5953-0BY00
Control units
Control unit 3RW52..-.AC0. 24 V 3RW5920-1UA00 1 1 unit 42S
analog output
3RW52..-.AC1. 110 ... 250 V 3RW5920-1UA10 1 1 unit 42S
analog output
3RW52..-.TC0. 24 V 3RW5920-1UT00 1 1 unit 42S
thermistor
input
3RW52..-.TC1. 110 ... 250 V 3RW5920-1UT10 1 1 unit 42S
thermistor
input
3RW5920-1UA00
6
Fans
Fan 3RW5216/17 (1x), -- 3RW5983-0FF00 1 1 unit 42S
3RW5226/27 (2x),
3RW523 (2x)
3RW524 (1x) -- 3RW5984-0FF00 1 1 unit 42S
3RW5983-0FF00
Terminals
Box terminal block 3RW522 (2x) -- 3RW5982-0TB00 1 1 unit 42S
3RW5982-0TB00
Removable control • Screw terminals Screw terminals
terminals
3RW521.-1.C.., Contains 3RW5980-1TR00 1 1 unit 42S
3RW522.-1.C.., 2 blocks
3RW523.-6.C.., each with
3RW524.-6.C.. 6 terminals
• Spring-loaded terminals Spring-loaded terminals
3RW5953-0GB00
Cover for control 3RW52 Titanium gray 3RW5950-0GD20 1 1 unit 42S
cable duct
3RW5950-0GD20
Enclosure components
Front cover 3RW524 -- 3RW5954-0GF00 1 1 unit 42S
3RW5954-0GF00
Hinged cover 3RW52 Without 3RW5950-0GL20 1 1 unit 42S
cutout
6
3RW5950-0GL20
Transport packaging
Transport 3RW521 -- 3RW5951-0VY00 1 1 unit 42S
packaging 3RW522, 3RW523 -- 3RW5953-0VY00 1 1 unit 42S
3RW524 -- 3RW5954-0VY00 1 1 unit 42S
3RW5953-0VY00
■ Overview
More information
Homepage, see www.siemens.com/sirius-soft-starter Industry Online Support (SIOS) topic page, see
Industry Mall, see www.siemens.com/product?3RW https://support.industry.siemens.com/cs/ww/en/view/109747404
6
3RW5953-0SL0.
3RW5072 (2x) 600 V, 210 A 3RW5924-0SN05 1 1 unit 42S
3RW5073 (2x), 600 V, 315 A 3RW5924-0SQ05 1 1 unit 42S
3RW5074 (2x)
3RW5075 (2x), 600 V, 470 A 3RW5924-0SS05 1 1 unit 42S
3RW5076 (2x)
3RW5077 (2x) 600 V, 570 A 3RW5924-0ST05 1 1 unit 42S
3RW5924-0S.05
Bypass units
Bypass unit 3RW505 -- 3RW5905-0BY00 1 1 unit 42S
3RW5072, 3RW5073, 210 ... 315 A 3RW5907-0BQ00 1 1 unit 42S
3RW5074
3RW5075, 3RW5076, 370 ... 570 A 3RW5907-0BY00 1 1 unit 42S
3RW5077
3RW5905-0BY00
Control units
Control unit
Analog output 3RW505.-.AB0. 24 V 3RW5905-1UA00 1 1 unit 42S
3RW505.-.AB1. 110 ... 250 V 3RW5905-1UA10 1 1 unit 42S
3RW507.-.AB0. 24 V 3RW5907-1UA00 1 1 unit 42S
3RW507.-.AB1. 110 ... 250 V 3RW5907-1UA10 1 1 unit 42S
Thermistor input 3RW505.-.TB0. 24 V 3RW5905-1UT00 1 1 unit 42S
3RW505.-.TB1. 110 ... 250 V 3RW5905-1UT10 1 1 unit 42S
3RW507.-.TB0. 24 V 3RW5907-1UT00 1 1 unit 42S
3RW5905-1UA00 3RW507.-.TB1. 110 ... 250 V 3RW5907-1UT10 1 1 unit 42S
3RW5905-0PY04
Fans
Fan 3RW505 (1x) -- 3RW5905-0FF00 1 1 unit 42S
3RW507 (1x) -- 3RW5907-0FF00 1 1 unit 42S
3RW5905-0FF00
Terminals
6
3RW5905-0GB00
Hinged cover 3RW50 -- 3RW5900-0GL00 1 1 unit 42S
3RW5900-0GL00
Transport packaging
Transport 3RW505 -- 3RW5905-0VY00 1 1 unit 42S
packaging 3RW507 -- 3RW5907-0VY00 1 1 unit 42S
3RW5905-0VY00
■ Overview
More information
Industry Mall, see www.siemens.com/product?3RF Online configurator, see www.siemens.com/sirius/configurators
Conversion tool, see www.siemens.com/conversion-tool
6
ensures reliable operation up to an ambient temperature
of +60 °C.
• Thanks to fast configuration and the ease of mounting and
1-phase solid-state relay and 3-phase solid-state contactor startup, not only time but also expenses are saved.
The SIRIUS 3RF2 solid-state switching devices reliably switch Also for switching motors (see page 6/159)
a wide range of different loads with alternating voltages in
In order to achieve higher productivity, the switching frequency
50 and 60 Hz systems.
is continuously increased in drive technology. It is no problem for
SIRIUS 3RF2 solid-state switching devices for resistive/inductive our SIRIUS solid-state contactors for switching motors. With
loads: three-phase motors up to 7.5 kW, they can reliably withstand
• Solid-state relays even the highest switching frequencies. Even a continuous
change in the direction of rotation is possible with the solid-state
• Solid-state contactors reversing contactors. Both versions can be perfectly combined
• Function modules with components from the SIRIUS modular system. Connecting
with SIRIUS motor starter protectors or SIRIUS overload relays
SIRIUS 3RF2 – for almost unending activity can be implemented without any further steps.
Conventional electromechanical switchgear is often overtaxed SIRIUS 3RF3 solid-state switching devices for switching motors:
by the rise in the number of switching operations. A high
switching frequency results in frequent failure and short • Solid-state contactors
replacement cycles. However, this does not have to be the case, • Solid-state reversing contactors
because with the latest generation of our SIRIUS 3RF2 solid-
state switching devices we provide you with solid-state relays Connection methods
and contactors with a particularly long endurance – for almost The solid-state switching devices are available with screw
unending activity even under the toughest conditions and under terminals (box terminals), spring-loaded terminals or ring cable
high mechanical loading, but also in noise-sensitive areas. lug connections.
Proven time and again in service
Screw terminals
SIRIUS 3RF2 solid-state switching devices have firmly
established themselves in industrial applications. They are used
above all in applications where loads are switched frequently – Spring-loaded terminals
mainly with resistive load controllers, with the control of electrical
heat or the control of valves and motors in conveyor systems.
In addition to its use in areas with high switching frequencies, Ring cable lug connection
their silent switching means that SIRIUS is also ideally suited
for use in noise-sensitive areas, such as offices or hospitals.
The terminals are indicated in the corresponding
tables by the symbols shown on orange backgrounds.
6
Control of the -- -- -- -- -- ✓ -- -- -- ✓ ✓
heating power
through an
analog input
Power control -- -- -- -- -- -- -- -- -- -- ✓
Startup
Easy setting of -- -- -- -- -- -- ✓ ✓ -- ✓ ✓
setpoint values with
"Teach" button
"Remote Teach" -- -- -- -- -- -- -- -- ✓ -- --
input for setting
setpoints
Mounting
Mounting on -- -- -- ✓ ✓ -- -- -- -- -- --
mounting rails or
mounting plates
Can be snapped -- -- -- -- -- ✓ ✓ ✓ ✓ ✓ ✓
directly onto
a solid-state relay
or contactor
For use with ✓ ✓ ✓ -- -- -- -- -- -- -- --
"Coolplate" heat sink
Cable routing
Connection of load ✓ -- ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
circuit as for
switchgear
Connection of load -- ✓ -- -- -- -- -- -- -- -- --
circuit from above
✓ Function available
❑ Function possible
-- Function not possible
1)
The converter can also be used with 3-phase devices.
■ Benefits
Main features Benefits
• LED display • Saves time and costs with fast mounting and commissioning,
• Variety of connection methods, also with high degree short startup times and easy wiring
of protection • Extremely long life, low maintenance, rugged and reliable
• Plug-in control connection • Space-saving and safe thanks to side-by-side mounting up
• Zero-point switching, 2-phase or 3-phase controlled to an ambient temperature of +60 °C
• Modular design: Standardized function modules and heat
Features sinks can be used in conjunction with solid-state relays to
• Considerable space savings thanks to a width of only 22.5 mm satisfy individual requirements.
• Variety of connection methods: Screw terminal, spring-loaded • Safety due to lifelong, vibration-resistant and shock-resistant
terminal or ring cable lug, there is no problem – they are all spring-loaded terminals even under tough conditions
finger-safe • Optimum heat transfer allows small, space-saving heat sinks
• Flexible for all applications with function modules for retrofitting to be used
• Possibility of fuseless short-circuit-proof design
■ Application
Applications The powerful SIRIUS 3RF2 solid-state relays and contactors can
be used for the simultaneous control of several heating loads.
Example: Plastics processing industry
6
■ More information
Notes on integration in the load feeders Electromagnetic compatibility (EMC)
The SIRIUS solid-state switching devices are very easy The solid-state switching devices are suitable for interference-
to integrate into the load feeders thanks to their industrial free operation in industrial networks without further measures.
connection method and design. If they are used in public networks, it may be necessary for
conducted interference to be reduced by means of filters.
Particular attention must however be paid to the circumstances
of the installation and ambient conditions, as the performance of This does not include the solid-state contactors for resistive
the solid-state switching devices is largely dependent on these. loads of the special type 3RF23..-.CA.. "low noise". These
Depending on the version, certain restrictions must be comply with the class B limit values up to a rated current of 16 A.
observed. For detailed information, for example in relation to If other versions are used, and at currents of over 16 A, standard
solid-state contactors about the minimum spacing and to filters can be used in order to comply with the limit values.
solid-state relays about the choice of heat sink, see technical The decisive factors when it comes to selecting the filters
specifications and product data sheets, are essentially the current loading and the other parameters
https://support.industry.siemens.com/cs/ww/en/ps/16222. (operational voltage, design type, etc.) in the load feeder.
Short-circuit and overload protection Suitable filters can be ordered from EPCOS AG, see page 16/18.
Despite the rugged power semiconductors that are used, Product information and technical specifications
solid-state switching devices respond more sensitively to short
circuits in the load feeder. Consequently, special precautions For product data sheets with detailed technical specifications,
have to be taken against destruction, depending on the type dimensional drawings and characteristic curves, see
of design. https://support.industry.siemens.com/cs/ww/en/ps/16222.
Siemens generally recommends using SITOR semiconductor For more information, please enter the article number of
protection fuses. These fuses also provide protection against the required device under the tab "Product List".
destruction in the event of a short circuit even when the
solid-state contactors and solid-state relays are fully utilized.
Alternatively, if there is lower loading, protection can also
be provided by standard fuses or miniature circuit breakers.
This protection is achieved by overdimensioning the solid-state
switching devices accordingly. The technical specifications
and the product data sheets contain details both about the
solid-state fuse protection itself and about use of the devices
with conventional protection equipment.
■ Overview
Solid-state relays (without heat sink) 3RF22 3-phase solid-state relays (without heat sink)
with a width of 45 mm
SIRIUS solid-state relays are suitable for surface mounting
on existing cooling surfaces. Mounting is quick and easy, With its compact design, which stays the same even at currents
involving just two screws. The special technology of the power of up to 55 A, the 3RF22 solid-state relay with a width of just
semiconductor ensures that there is excellent thermal contact 45 mm offers an ultra small footprint. The logical connection
with the heat sink. Depending on the nature of the heat sink, method, with the power infeed from above and load connection
the capacity reaches up to 88 A on resistive loads. from below, ensures tidy installation in the control cabinet.
The solid-state relays are available in three different versions: The 3-phase solid-state relays are available with
• 3RF21 1-phase solid-state relay with a width of 22.5 mm • 2-phase control (suitable in particular for circuits without
• 3RF20 1-phase solid-state relay with a width of 45 mm connection to the neutral conductor) and
• 3RF22 3-phase solid-state relay with a width of 45 mm • 3-phase control (suitable for star circuits with connection to
the neutral conductor or for applications in which the system
Version for resistive loads "zero-point switching" requires all phases to be switched)
This standard version is often used for 3RF20 to 3RF22 Selection notes
solid-state relays for switching heaters on and off.
When selecting solid-state relays, in addition to information
Version for inductive loads "instantaneous switching" about the network, the load and the ambient conditions, it is also
In this version, the 3RF20 and 3RF21 solid-state relays are necessary to know details of the planned design. The solid-state
specifically matched to inductive loads. Whether it is a matter of relays can only conform to their specific technical specifications
frequent actuation of the valves in a filling plant or starting and if they are mounted with appropriate care on an adequately
6
stopping small operating mechanisms in packet distribution dimensioned heat sink.
systems, operation is carried out safely and noiselessly. Mounting solid-state relays directly on a mounting plate made of
Special "low noise" version sheet steel is inadequate in terms of heat dissipation.
Thanks to a special control circuit of the 3RF21 solid-state The following procedure is recommended:
contactors, this special version can be used in public networks • Determine the rated current of the load and the mains voltage
up to 16 A without any additional measures such as interference • Select the relay design and choose a solid-state relay with
suppressor filters. As a result, in terms of emitted interference, higher rated current than the load
it conforms to limit value curve class B according to IEC 60947-4-3.
• Determine the thermal resistance of the proposed heat sink
Function modules • Check the correct relay size with the aid of the diagrams
The 3RF21 and 3RF22 solid-state relays can be expanded • In systems that have high voltage peaks or at voltages of
with various function modules for individual adaptation to 575 V and higher, use of versions with a blocking voltage
applications, see page 6/150 onwards. of 1 600 V is recommended.
3RF21 1-phase solid-state relays (without heat sink)
with a width of 22.5 mm
With its compact design and a width of just 22.5 mm, which is
not exceeded even for currents of up to 88 A, the 3RF21 solid-
state relay offers an ultra-small footprint. The logical connection
method, with the power infeed from above and load connection
from below, ensures tidy installation in the control cabinet.
3RF20 1-phase solid-state relays (without heat sink)
with a width of 45 mm
The solid-state relays with a width of 45 mm provide for
connection of the power supply lead and the load from above.
This makes it easy to replace existing solid-state relays in
existing arrangements. The connection of the control cable is as
space-saving as the 22.5 mm design, as it is simply plugged on.
■ Technical specifications
More information
System Manual for modular system, see FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/16223/faq
https://support.industry.siemens.com/cs/ww/en/view/60311318
D
W
General data
Ambient temperature
• During operation, derating from 40 °C °C -25 ... +60
• During storage °C -55 ... +80
Installation altitude m 0 ... 1 000; derating from 1 000
Shock resistance according to IEC 60068-2-27 g/ms 15/11
Vibration resistance according to IEC 60068-2-6 g 2
Degree of protection IP on the front IP20 IP00 (IP20 when using the
according to IEC 60529 3RF2900-3PA88 terminal cover)
Touch protection on the front according to Finger-safe for vertical touching from the front --
6
IEC 60529
Electromagnetic compatibility (EMC)
• Emitted interference
- Conducted interference voltage Class A for industrial applications
according to IEC 60947-4-3
- Emitted, high-frequency interference voltage Class B for residential, business and commercial applications
according to IEC 60947-4-3
• Interference immunity
- Electrostatic discharge kV Contact discharge 4; air discharge 8; behavior criterion 2
according to IEC 61000-4-2
(corresponds to degree of severity 3)
- Induced RF fields MHz 0.15 ... 80; 140 dBµV; behavior criterion 1
according to IEC 61000-4-6
- Burst according to IEC 61000-4-4 kV 2/5.0 kHz; behavior criterion 2
- Surge according to IEC 61000-4-5 kV Conductor - ground 2; conductor - conductor 1; behavior criterion 2
Mounting
• Screws (not included in the scope of supply) 2 x M4
• Tightening torque Nm 1.5
Connection type Screw terminals Spring-loaded terminals Ring cable lug
connection
Connection, main contacts
• Conductor cross-sections
- Solid mm2 2 x (1.5 ... 2.5)1), 2 x (2.5 ... 6)1) 2 x (0.5 ... 2.5) --
- Finely stranded with end sleeve mm2 2 x (1 ... 2.5)1), 2 x (2.5 ... 6)1), 2 x (0.5 ... 1.5) --
1 x 10
- Finely stranded without end sleeve mm2 -- 2 x (0.5 ... 2.5) --
- Solid or stranded, AWG cables AWG 2 x (14 ... 10) 2 x (18 ... 14) --
• Terminal screws M4 -- M5
• Tightening torque Nm 2 ... 2.5 -- 2 ... 2.5
lb.in 7 ... 10.3 -- 7 ... 10.3
• Cable lugs
- According to DIN 46234 -- -- 5-2.5, 5-6, 5-10, 5-16, 5-25
- According to JIS C 2805 -- -- R 2-5, R 5.5-5, R 8-5, R 14-5
- Width, maximum mm -- -- 12
Connection, auxiliary/control contacts
• Conductor cross-sections mm 1 x (0.5 ... 2.5), 2 x (0.5 ... 1.0) 0.5 ... 2.5 1 x (0.5 ... 2.5), 2 x (0.5 ... 1.0)
AWG 20 ... 12 20 ... 12 20 ... 12
• Stripped length mm 7 10 7
• Terminal screw M3 -- M3
• Tightening torque Nm 0.5 ... 0.6 -- 0.5 ... 0.6
lb.in 4.5 ... 5.3 -- 4.5 ... 5.3
1) If two different conductor cross-sections are connected to one clamping
point, both cross-sections must lie in one of the ranges specified.
Type Imax1) Ie according to Ie according to UL/CSA Power loss Minimum load Off-state current
IEC 60947-4-3 current
at Rthha/Tu = 40 °C at Rthha/Tu = 40 °C at Rthha/Tu = 50 °C at Imax
A K/W A K/W A K/W W A mA
Main circuit
3RF2120-..... 20 2.00 20 1.70 20 1.30 28.6 0.1 10
3RF2130-1.... 30 1.45 30 1.45 30 1.25 44.2 0.5 10
3RF2150-1.... 50 0.85 50 0.85 50 0.70 66 0.5 10
3RF2150-2.... 50 0.85 20 2.90 20 2.60 66 0.5 10
3RF2150-3.... 50 0.85 50 0.85 50 0.70 66 0.5 10
3RF2170-1.... 70 0.50 50 1.15 50 1.00 94 0.5 10
3RF2190-1.... 88 0.55 50 1.40 50 0.85 118 0.5 10
3RF2190-2.... 88 0.55 20 3.50 20 2.80 118 0.5 10
3RF2190-3.... 88 0.55 80 0.55 80 0.45 118 0.5 10
1)
The current Imax provides information about the performance of the Note:
solid-state relay. The actual permitted rated operational current Ie can be
smaller depending on the connection method and cooling conditions. The required heat sinks for the corresponding load currents can
be determined from the characteristic curves (see page 6/120,
"More Information"). The minimum thickness values for the
mounting surface must be observed.
Type Rated peak withstand current Itsm I2t value
A A 2s
6
Main circuit
3RF2120-..... 200 200
3RF2130-..A.2 300 450
3RF2130-..A.4 300 450
3RF2130-..A.5 300 450
3RF2130-..A.6 400 800
3RF2150-..... 600 1 800
3RF2170-..A.2 1 200 7 200
3RF2170-..A.4 1 200 7 200
3RF2170-..A.5 1 200 7 200
3RF2170-..A.6 1 150 6 600
3RF2190-..... 1 150 6 600
Instantaneous switching,
rated operational voltage Ue 48 ... 460 V AC
20 24 DC 3RF2120-1BA04 1 1 unit 41C
30 3RF2130-1BA04 1 1 unit 41C
50 3RF2150-1BA04 1 1 unit 41C
702) 3RF2170-1BA04 1 1 unit 41C
902) 3RF2190-1BA04 1 1 unit 41C
Instantaneous switching · Blocking voltage 1 600 V,
rated operational voltage Ue 48 ... 600 V AC
50 24 DC 3RF2150-1BA06 1 1 unit 41C
6
solid-state relay. The actual permitted rated operational current Ie can be
smaller depending on the connection method and cooling conditions. Other rated control supply voltages on request.
2) Please note that this version with an M4 screw connection can only
Accessories, see page 6/127.
be used for a rated current of up to approx. 50 A and a conductor
cross-section of 10 mm2.
Please use the 3RF21 solid-state relays with ring cable lug connections
for these currents, see page 6/126.
3RF2120-2AA02
Zero-point switching,
rated operational voltage Ue 48 ... 460 V AC
20 24 DC 3RF2120-2AA04 1 1 unit 41C
502) 3RF2150-2AA04 1 1 unit 41C
902) 3RF2190-2AA04 1 1 unit 41C
502) 24 AC/DC 3RF2150-2AA14 1 1 unit 41C
20 110 ... 230 AC 3RF2120-2AA24 1 1 unit 41C
502) 3RF2150-2AA24 1 1 unit 41C
902) 3RF2190-2AA24 1 1 unit 41C
Zero-point switching,
rated operational voltage Ue 48 ... 600 V AC
20 4 ... 30 DC 3RF2120-2AA45 1 1 unit 41C
3RF2120-3AA02
Zero-point switching,
rated operational voltage Ue 48 ... 460 V AC
20 24 DC 3RF2120-3AA04 1 1 unit 41C
50 3RF2150-3AA04 1 1 unit 41C
90 3RF2190-3AA04 1 1 unit 41C
20 110 ... 230 AC 3RF2120-3AA24 1 1 unit 41C
6
■ Accessories
Version Article No. Price PU PS* PG
per PU (UNIT,
SET, M)
Terminal covers
Ring cable lug
connection
Terminal covers 3RF2900-3PA88 1 10 units 41C
For 3RF21 solid-state relays with ring cable lug
connection
With this terminal cover, degree of protection IP20
can be achieved on the front with a ring cable lug
connection. It can also be used for screw terminals
after simple adaptation.
3RF2900-3PA88
Control connectors
Screw terminals
6
3RF2900-1TA88
Spring-loaded
terminals
Replacement control connectors 3RF2900-2TA88 1 50 units 41C
For 3RF20 to 3RF22 solid-state relays
With spring-loaded terminals
3RF2900-2TA88
Control connectors 3RF2900-2TB88 1 10 units 41C
For 3RF20 to 3RF22 solid-state relays
With spring-loaded terminals
With two clamping points per contact
3RF2900-2TB88
Tools for opening spring-loaded terminals
Screwdrivers 3RA2908-1A 1 1 unit 41B
For all SIRIUS devices
With spring-loaded terminals
Length approx. 200 mm,
size 3.0 mm x 0.5 mm,
3RA2908-1A titanium gray/black,
partially insulated
Blank labels
Unit labeling plates
For SIRIUS devices1)
10 mm × 7 mm, titanium gray 3RT2900-1SB10 100 816 41B
units
20 mm × 7 mm, titanium gray 3RT2900-1SB20 100 340 41B
IC01_00181
units
Adhesive labels
3RT2900-1SB20 For SIRIUS devices
19 mm × 6 mm, titanium gray 3RT2900-1SB60 100 3060 41B
units
1) PC labeling system for individual inscription
of unit labeling plates available from:
murrplastik Systemtechnik GmbH
(see page 16/18).
■ Technical specifications
More information
System Manual for modular system, see FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/16223/faq
https://support.industry.siemens.com/cs/ww/en/view/60311318
D
W
General data
Ambient temperature
• During operation, derating from 40 °C °C -25 ... +60
• During storage °C -55 ... +80
Installation altitude m 0 ... 1 000; derating from 1 000
Shock resistance according to IEC 60068-2-27 g/ms 15/11
Vibration resistance according to IEC 60068-2-6 g 2
Degree of protection IP on the front IP20
according to IEC 60529
Touch protection on the front according to IEC 60529 Finger-safe for vertical touching from the front
6
Type Imax1) Ie according to Ie according to Power loss Minimum load Off-state current
IEC 60947-4-3 UL/CSA current
at Rthha/Tu = 40 °C at Rthha/Tu = 40 °C at Rthha/Tu = 50 °C at Imax
A K/W A K/W A K/W W A mA
Main circuit
3RF2020-1.A.. 20 2.00 20 1.70 20 1.30 28.6 0.1 10
3RF2030-1.A.. 30 1.45 30 1.45 30 1.25 44.2 0.5 10
3RF2050-1.A.. 50 0.85 50 0.85 50 0.70 66 0.5 10
3RF2070-1.A.. 70 0.50 50 1.15 50 1.00 94 0.5 10
3RF2090-1.A.. 88 0.55 50 1.40 50 1.00 118 0.5 10
1) The current Imax provides information about the performance of the Note:
solid-state relay. The actual permitted rated operational current Ie can be
smaller depending on the connection method and cooling conditions. The required heat sinks for the corresponding load currents can
be determined from the characteristic curves (see page 6/120,
"More Information"). The minimum thickness values for the
mounting surface must be observed.
6
3RF2030-1.A.2 300 450
3RF2030-1.A.4 300 450
3RF2030-1.A.6 400 800
3RF2050-1.A.. 600 1 800
3RF2070-1.A.2 1 200 7 200
3RF2070-1.A.4 1 200 7 200
3RF2070-1.A.5 1 200 7 200
3RF2070-1.A.6 1 150 6 600
3RF2090-1.A.. 1 150 6 600
1)
The type current provides information about the performance capacity of Accessories, see page 6/127.
the solid-state relay. The actual permitted rated operational current Ie can
be smaller depending on the connection method and cooling conditions.
2)
Please note that this version with an M4 screw connection can only
be used for a rated current of up to approx. 50 A and a conductor
cross-section of 10 mm2.
3RF2050-4AA02
1)
The type current provides information about the performance capacity of Accessories, see page 6/127.
the solid-state relay. The actual permitted rated operational current Ie can
be smaller depending on the connection method and cooling conditions.
■ Technical specifications
More information
System Manual for modular system, see FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/16223/faq
https://support.industry.siemens.com/cs/ww/en/view/60311318
D
W
General data
Ambient temperature
• During operation, derating from 40 °C °C -25 ... +60
• During storage °C -55 ... +80
Installation altitude m 0 ... 1 000; > 1 000 ask Technical Support
Shock resistance according to IEC 60068-2-27 g/ms 15/11
Vibration resistance according to IEC 60068-2-6 g 2
Degree of protection IP on the front IP20 IP00
according to IEC 60529
Touch protection on the front Finger-safe for vertical touching from the front --
according to IEC 60529
6
Type Imax1) Ie according to Ie according to UL/CSA Power loss Minimum load Max. off-state
IEC 60947-4-3 current current
at Rthha/Tu = 40 °C at Rthha/Tu = 40 °C at Rthha/Tu = 50 °C at Imax
A K/W A K/W A K/W W A mA
Main circuit
3RF2230-1AB.. 30 0.80 30 0.80 30 0.65 81 0.5 10
3RF2230-2AB.. 20 1.36 20 1.15
3RF2230-3AB.. 30 0.80 30 0.65
3RF2255-1AB.. 55 0.25 50 0.35 50 0.15 151 0.5 10
3RF2255-2AB.. 20 1.83 20 1.58
3RF2255-3AB.. 55 0.25 55 0.15
3RF2230-1AC.. 30 0.45 30 0.45 30 0.35 122 0.5 10
3RF2230-2AC.. 20 0.86 20 0.72
3RF2230-3AC.. 30 0.45 30 0.35
3RF2255-1AC.. 55 0.14 50 0.20 50 0.12 226 0.5 10
3RF2255-2AC.. 20 1.19 20 1.02
3RF2255-3AC.. 55 0.14 55 0.12
1)
The current Imax provides information about the performance of the Note:
solid-state relay. The actual permitted rated operational current Ie can
be smaller depending on the connection method and cooling conditions. The required heat sinks for the corresponding load currents can
be determined from the characteristic curves (see page 6/120,
"More Information"). The minimum thickness values for the
mounting surface must be observed.
6
Type Rated peak withstand current Itsm I2t value
A A 2s
Main circuit
3RF2230-....5 300 450
3RF2255-....5 600 1 800
2)
Please note that the version with an M4 screw connection can only be used
for a rated current of up to approx. 50 A and a conductor cross-section
of 10 mm2.
Please use the 3RF22 solid-state relays with ring cable lug connections for
these currents.
3RF2230-2AB45
1) The type current provides information about the performance capacity of Accessories, see page 6/127.
the solid-state relay. The actual permitted rated operational current Ie can
be smaller depending on the connection method and cooling conditions.
2) Please note that the version with spring-loaded terminals can only be used
for a rated current of up to approx. 20 A and a conductor cross-section of
2.5 mm2. Higher currents can be achieved by connecting two conductors
per terminal.
3RF2230-3AB45
1)
The type current provides information about the performance capacity of the Accessories, see page 6/127.
solid-state relay. The actual permitted rated operational current Ie can be
smaller depending on the connection method and cooling conditions.
■ Overview
Solid-state contactors (with integrated heat sink) In systems that have high voltage peaks or at voltages of 575 V
and higher, use of versions with a blocking voltage of 1 600 V is
The solid-state contactors are available in two different versions: recommended.
• 3RF23 1-phase solid-state contactors: Their compact design
with optimized heat sink enables small complete units with The following miniature circuit breakers with a B characteristic
currents up to 70 A. and 10 kA or 6 kA breaking capacity protect the 3RF23..-.DA..
solid-state contactors in the event of short circuits on the load
• 3RF24 3-phase solid-state contactors: Their compact design and the specified conductor cross-sections and lengths:
with optimized heat sink enables the provision of small
complete units with currents up to 50 A. Rated current of the Example of Max. Minimum
miniature circuit type1) conductor cable length from
The complete units consist of a solid-state relay plus optimized breaker cross- contactor to load
heat sink, and are therefore ready to use. They offer defined section
rated currents to make selection as easy as possible. Like all 6A 5SY4106-6 1 mm2 5m
of our solid-state switching devices, one of their particular 10 A 5SY4110-6 1.5 mm2 8m
advantages is their compact and space-saving design.
16 A 5SY4116-6 1.5 mm2 12 m
Thanks to optimized power electronics, versions of 3RF2310 to 2.5 mm2 20 m
3RF2330 solid-state contactors can be mounted side-by-side 20 A 5SY4120-6 2.5 mm2 20 m
without derating, see product information or product data sheets
25 A 5SY4125-6 2.5 mm2 26 m
for the individual products.
1)
The miniature circuit breakers can be used up to a maximum rated voltage
Note: of 480 V!
6
Due to a special mounting foot for versions 3RF2310 to 3RF2330
and 3RF2410, snapping onto grounded DIN rails or mounting 3/N/PE 50 Hz 230/400 V 3/N/PE 50 Hz 230/400 V
on a grounded mounting plate simultaneously provides safe L1 L1
grounding of the heat sink. Additional grounding is no longer L2 L2
necessary in this case.
With other types of mounting, an additional ground connection L3 L3
to the heat sink can be established by means of a screw terminal N N
connection.
3RF23 1-phase solid-state contactors with heat sink F1 F1 F2
This standard version is often used for switching heaters on and off. 1 L 1 L
line
line
of the valves in a filling plant or starting and stopping small I,A I,A
operating mechanisms in packet distribution systems, operation
NSB0_01473b
In order to achieve problem-free short-circuit protection by The 3-phase solid-state contactors for resistive loads up to 50 A
means of miniature circuit breakers, however, certain constraints are available with
must be observed. As the magnitude and duration of the short- • 2-phase control (suitable in particular for circuits without
circuit current are determined not only by the short-circuit connection to the neutral conductor) and
breaking response of the miniature circuit breaker but also the • 3-phase control (suitable for star circuits with connection to
properties of the wiring system, such as the internal resistance the neutral conductor or for applications in which the system
of the input to the network and damping by switching devices requires all phases to be switched)
and cables, particular attention must also be paid to these
parameters. The necessary cable lengths are therefore shown The converter function module can be snapped onto both
for the main factor, the line resistance, in the following table. versions for the simple power control of loads in a three-phase
network by means of analog signals.
Note:
Checking the correct solid-state contactor size with the aid of
the rated current diagram, taking account of the installation
conditions, is recommended.
■ Technical specifications
More information
System Manual for modular system, see FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/16223/faq
https://support.industry.siemens.com/cs/ww/en/view/60311318
• Screw terminals and spring-loaded terminals Finger-safe for vertical touching from the front
• Ring cable lug connection Finger-safe for vertical touching from the front when using the 3RF2900-3PA88 terminal cover
Electromagnetic compatibility (EMC)
• Emitted interference according to IEC 60947-4-3
- Conducted interference voltage Class A for industrial applications Class A for industrial Class A for industrial
applications; applications
Class B for residential,
business and
commercial applica-
tions up to 16 A,
AC-51 low noise
- Emitted, high-frequency interference voltage Class B for residential, business and commercial applications
• Interference immunity
- Electrostatic discharge kV Contact discharge 4; air discharge 8; behavior criterion 2
according to IEC 61000-4-2
(corresponds to degree of severity 3)
- Induced RF fields according to IEC 61000-4-6 MHz 0.15 ... 80; 140 dBµV; behavior criterion 1
- Burst according to IEC 61000-4-4 kV 2/5.0 kHz; behavior criterion 2
- Surge according to IEC 61000-4-5 kV Conductor - ground 2; conductor - conductor 1; behavior criterion 2
NSB0_01701
6
Blocking voltage V 800 1 200 1 600
Rate of voltage rise V/µs 1 000
A mm
Main circuit
3RF2310-.AA.. 10.5 22.5 x 95 x 84
3RF2320-.AA.. 20 22.5 x 95 x 116
3RF2320-.CA..
3RF2320-.DA..
3RF2330-.AA.. 30 45 x 95 x 131.5
3RF2330-.CA..
3RF2330-.DA.. 22.5 x 95 x 116
3RF2340-.AA.. 40 67 x 100 x 136
3RF2340-.DA..
3RF2350-.AA.. 50 67 x 100 x 136
3RF2370-.AA.. 70 80 x 100 x 157
1)
The type current provides information about the performance of the
solid-state contactor. The actual permitted rated operational current Ie
can be smaller depending on the installation conditions.
Type Type current AC-51/performance capacity1) Power loss Minimum load Off-state Rated peak I2t value
at Imax according to according to at Imax current current withstand
IEC 60947-4-3 UL/CSA current Itsm
at 40 °C at 40 °C at 50 °C
A A A W A mA A A²s
Main circuit
3RF2310-.AA.2 10.5 7.5 9.6 11 0.1 10 200 200
3RF2310-.AA.4
3RF2310-.AA.5
3RF2310-.AA.6 400 800
3RF2320-.AA.2 20 13.2 17.6 20 0.5 10 600 1 800
3RF2320-.AA.4
3RF2320-.AA.5
3RF2320-.AA.6
3RF2320-.CA.2 25 600 1 800
3RF2320-.CA.4
3RF2320-.DA.2 10 1 150 6 600
3RF2320-.DA.4
3RF2330-.AA.2 30 22 27 33 0.5 10 600 1 800
3RF2330-.AA.4
3RF2330-.AA.5
3RF2330-.AA.6
3RF2330-.CA.2 25 600 1 800
6
Type Type current AC-51/performance Type current AC-15/ Power loss Minimum Off-state Rated peak I2t value
capacity1) performance at Imax load current current withstand
capacity1) current
at Imax according to according 10 x Ie Parameters Itsm
IEC 60947-4-3 to UL/CSA for
at 40 °C at 40 °C at 50 °C 60 ms
A A A A W A mA A A²s
Main circuit
3RF2310-.BA.2 10.5 7.5 9.6 6 1 200 1/h 11 0.1 10 200 200
3RF2310-.BA.4 50%
3RF2310-.BA.6 ON period 400 800
3RF2320-.BA.2 20 13.2 17.6 12 1 200 1/h 20 0.5 10 600 1 800
3RF2320-.BA.4 50%
3RF2320-.BA.6 ON period
3RF2330-.BA.2 30 22 27 15 1 200 1/h 33 0.5 10 600 1 800
3RF2330-.BA.4 50%
3RF2330-.BA.6 ON period
3RF2340-.BA.2 40 33 36 20 1 200 1/h 44 0.5 10 1 200 7 200
3RF2340-.BA.4 50%
3RF2340-.BA.6 ON period 1 150 6 600
3RF2350-.BA.2 50 36 45 25 1 200 1/h 54 0.5 10 1 150 6 600
3RF2350-.BA.4 50%
3RF2350-.BA.6 ON period
3RF2370-.BA.2 70 70 62 27.5 1 200 1/h 83 0.5 10 1 150 6 600
3RF2370-.BA.4 50%
3RF2370-.BA.6 ON period
1) The type current provides information about the performance of the
solid-state contactor. The actual permitted rated operational current Ie
can be smaller depending on the installation conditions.
6
10.5 110 ... 230 AC 3RF2310-1AA22 1 1 unit 41C
20 3RF2320-1AA22 1 1 unit 41C
30 3RF2330-1AA22 1 1 unit 41C
3RF2310-1 40 -- 3RF2340-1AA22 1 1 unit 41C
50 -- 3RF2350-1AA22 1 1 unit 41C
Zero-point switching · Integrated heat sink,
rated operational voltage Ue 48 ... 460 V AC
10.5 24 DC 3RF2310-1AA04 1 1 unit 41C
20 3RF2320-1AA04 1 1 unit 41C
30 3RF2330-1AA04 1 1 unit 41C
40 -- 3RF2340-1AA04 1 1 unit 41C
50 -- 3RF2350-1AA04 1 1 unit 41C
10.5 24 DC low power 3RF2310-1AA04-0KN0 1 1 unit 41C
10.5 24 AC/DC 3RF2310-1AA14 1 1 unit 41C
20 3RF2320-1AA14 1 1 unit 41C
30 3RF2330-1AA14 1 1 unit 41C
40 -- 3RF2340-1AA14 1 1 unit 41C
3RF2320-1 50 -- 3RF2350-1AA14 1 1 unit 41C
10.5 110 ... 230 AC 3RF2310-1AA24 1 1 unit 41C
20 3RF2320-1AA24 1 1 unit 41C
30 3RF2330-1AA24 1 1 unit 41C
40 -- 3RF2340-1AA24 1 1 unit 41C
50 -- 3RF2350-1AA24 1 1 unit 41C
10.5 4 ... 30 DC 3RF2310-1AA44 1 1 unit 41C
20 3RF2320-1AA44 1 1 unit 41C
30 3RF2330-1AA44 1 1 unit 41C
These versions are equipped with a special mounting foot. Snapping them Other rated control supply voltages on request.
onto grounded DIN rails or mounting them on a grounded mounting plate
simultaneously provides safe grounding of the heat sink. Additional Accessories, see page 6/145.
grounding is no longer necessary in this case.
-- With these versions, the ground connection to the heat sink can be
established by means of a screw terminal connection.
1)
The type current provides information about the performance of the
solid-state contactor. The actual permitted rated operational current Ie
can be smaller depending on the installation conditions.
For derating characteristic curves, see page 6/120, "More information".
3RF2320-1
Low noise2),
zero-point switching · Integrated heat sink,
rated operational voltage Ue 48 ... 460 V AC
20 24 DC 3RF2320-1CA04 1 1 unit 41C
20 110 ... 230 AC 3RF2320-1CA24 1 1 unit 41C
20 4 ... 30 DC 3RF2320-1CA44 1 1 unit 41C
Short-circuit-proof with B MCB ·
Zero-point switching · Integrated heat sink,
rated operational voltage Ue 24 ... 230 V AC
20 24 DC 3RF2320-1DA02 1 1 unit 41C
20 110 ... 230 AC 3RF2320-1DA22 1 1 unit 41C
Short-circuit-proof with B MCB ·
Zero-point switching · Integrated heat sink,
rated operational voltage Ue 48 ... 460 V AC
20 24 DC 3RF2320-1DA04 1 1 unit 41C
40 24 DC low power -- 3RF2340-1DA04-0KN0 1 1 unit 41C
20 110 ... 230 AC 3RF2320-1DA24 1 1 unit 41C
20 4 ... 30 DC 3RF2320-1DA44 1 1 unit 41C
30 3RF2330-1DA44 1 1 unit 41C
303) 24 DC 3RF2330-1DA06 1 1 unit 41C
3RF2330-1
These versions are equipped with a special mounting foot. Snapping them 1) The type current provides information about the performance of the
onto grounded DIN rails or mounting them on a grounded mounting plate solid-state contactor. The actual permitted rated operational current Ie
simultaneously provides safe grounding of the heat sink. Additional can be smaller depending on the installation conditions.
grounding is no longer necessary in this case. For derating characteristic curves, see page 6/120, "More information".
-- With these versions, the ground connection to the heat sink can be 2) See page 6/135.
established by means of a screw terminal connection. 3) Blocking voltage 1 600 V, rated operational voltage Ue 48 ... 600 V AC
Other rated control supply voltages on request.
Accessories, see page 6/145.
6
40 20 -- 3RF2340-1BA04 1 1 unit 41C
50 25 -- 3RF2350-1BA04 1 1 unit 41C
50 27.5 -- 3RF2370-1BA04 1 1 unit 41C
10.5 6 110 ... 230 AC 3RF2310-1BA24 1 1 unit 41C
20 12 3RF2320-1BA24 1 1 unit 41C
30 15 3RF2330-1BA24 1 1 unit 41C
40 20 -- 3RF2340-1BA24 1 1 unit 41C
50 25 -- 3RF2350-1BA24 1 1 unit 41C
3RF2320-1 50 27.5 -- 3RF2370-1BA24 1 1 unit 41C
20 12 4 ... 30 DC 3RF2320-1BA44 1 1 unit 41C
30 15 3RF2330-1BA44 1 1 unit 41C
50 25 -- 3RF2350-1BA44 1 1 unit 41C
Instantaneous switching · Integrated heat sink,
blocking voltage 1 600 V,
rated operational voltage Ue 48 ... 600 V AC
10.5 6 24 DC 3RF2310-1BA06 1 1 unit 41C
20 12 3RF2320-1BA06 1 1 unit 41C
30 15 3RF2330-1BA06 1 1 unit 41C
40 20 -- 3RF2340-1BA06 1 1 unit 41C
50 25 -- 3RF2350-1BA06 1 1 unit 41C
50 27.5 -- 3RF2370-1BA06 1 1 unit 41C
10.5 6 110 ... 230 AC 3RF2310-1BA26 1 1 unit 41C
20 12 3RF2320-1BA26 1 1 unit 41C
30 15 3RF2330-1BA26 1 1 unit 41C
40 20 -- 3RF2340-1BA26 1 1 unit 41C
50 25 -- 3RF2350-1BA26 1 1 unit 41C
3RF2330-1 50 27.5 -- 3RF2370-1BA26 1 1 unit 41C
These versions are equipped with a special mounting foot. Snapping them Other rated control supply voltages on request.
onto grounded DIN rails or mounting them on a grounded mounting plate
simultaneously provides safe grounding of the heat sink. Additional Accessories, see page 6/145.
grounding is no longer necessary in this case.
-- With these versions, the ground connection to the heat sink can be
established by means of a screw terminal connection.
1) The type current provides information about the performance of the
solid-state contactor. The actual permitted rated operational current Ie
can be smaller depending on the installation conditions.
For derating characteristic curves, see page 6/120, "More information".
2) Utilization category AC-15:
Electromagnetic loads, e.g. valves according to IEC 60947-5-1.
Parameters: max. 1 200 1/h, 50% ON period, 10-times inrush current
for 60 ms.
3RF2320-2
Zero-point switching · Integrated heat sink,
rated operational voltage Ue 48 ... 460 V AC
10.5 24 DC 3RF2310-2AA04 1 1 unit 41C
20 3RF2320-2AA04 1 1 unit 41C
10.5 110 ... 230 AC 3RF2310-2AA24 1 1 unit 41C
6
Type current/ Rated control supply Grounding Ring cable lug PU PS* PG
performance voltage Us connection (UNIT,
capacity1) SET, M)
Imax
Article No. Price
A V per PU
Zero-point switching · Integrated heat sink,
rated operational voltage Ue 24 ... 230 V AC
10.5 24 DC 3RF2310-3AA02 1 1 unit 41C
20 3RF2320-3AA02 1 1 unit 41C
30 3RF2330-3AA02 1 1 unit 41C
40 -- 3RF2340-3AA02 1 1 unit 41C
50 -- 3RF2350-3AA02 1 1 unit 41C
70 -- 3RF2370-3AA02 1 1 unit 41C
10.5 110 ... 230 AC 3RF2310-3AA22 1 1 unit 41C
20 3RF2320-3AA22 1 1 unit 41C
30 3RF2330-3AA22 1 1 unit 41C
40 -- 3RF2340-3AA22 1 1 unit 41C
50 -- 3RF2350-3AA22 1 1 unit 41C
3RF2310-3 70 -- 3RF2370-3AA22 1 1 unit 41C
Zero-point switching · Integrated heat sink,
rated operational voltage Ue 48 ... 460 V AC
10.5 24 DC 3RF2310-3AA04 1 1 unit 41C
20 3RF2320-3AA04 1 1 unit 41C
30 3RF2330-3AA04 1 1 unit 41C
6
40 -- 3RF2340-3AA04 1 1 unit 41C
50 -- 3RF2350-3AA04 1 1 unit 41C
70 -- 3RF2370-3AA04 1 1 unit 41C
10.5 110 ... 230 AC 3RF2310-3AA24 1 1 unit 41C
20 3RF2320-3AA24 1 1 unit 41C
30 3RF2330-3AA24 1 1 unit 41C
40 -- 3RF2340-3AA24 1 1 unit 41C
50 -- 3RF2350-3AA24 1 1 unit 41C
3RF2330-3 70 -- 3RF2370-3AA24 1 1 unit 41C
20 4 ... 30 DC 3RF2320-3AA44 1 1 unit 41C
30 3RF2330-3AA44 1 1 unit 41C
50 -- 3RF2350-3AA44 1 1 unit 41C
Zero-point switching · Integrated heat sink,
rated operational voltage Ue 48 ... 600 V AC
40 4 ... 30 DC -- 3RF2340-3AA45 1 1 unit 41C
70 -- 3RF2370-3AA45 1 1 unit 41C
Zero-point switching · Integrated heat sink,
blocking voltage 1 600 V,
rated operational voltage Ue 48 ... 600 V AC
10.5 24 DC 3RF2310-3AA06 1 1 unit 41C
20 3RF2320-3AA06 1 1 unit 41C
30 3RF2330-3AA06 1 1 unit 41C
40 -- 3RF2340-3AA06 1 1 unit 41C
50 -- 3RF2350-3AA06 1 1 unit 41C
70 -- 3RF2370-3AA06 1 1 unit 41C
10.5 110 ... 230 AC 3RF2310-3AA26 1 1 unit 41C
20 3RF2320-3AA26 1 1 unit 41C
30 3RF2330-3AA26 1 1 unit 41C
40 -- 3RF2340-3AA26 1 1 unit 41C
50 -- 3RF2350-3AA26 1 1 unit 41C
70 -- 3RF2370-3AA26 1 1 unit 41C
These versions are equipped with a special mounting foot. Snapping them Other rated control supply voltages on request.
onto grounded DIN rails or mounting them on a grounded mounting plate
simultaneously provides safe grounding of the heat sink. Additional Accessories, see page 6/145.
grounding is no longer necessary in this case.
-- With these versions, the ground connection to the heat sink can be
established by means of a screw terminal connection.
1)
The type current provides information about the performance of the
solid-state contactor. The actual permitted rated operational current Ie
can be smaller depending on the installation conditions.
For derating characteristic curves, see page 6/120, "More information".
Type current/ Operational Rated control supply Ground- Ring cable lug PU PS* PG
performance current voltage Us ing connection (UNIT,
capacity1) Ie/AC-152) SET, M)
Imax
Article No. Price
A A V per PU
Instantaneous switching · Integrated heat sink,
rated operational voltage Ue 24 ... 230 V AC
70 27.5 24 DC -- 3RF2370-3BA02 1 1 unit 41C
70 27.5 110 ... 230 AC -- 3RF2370-3BA22 1 1 unit 41C
Instantaneous switching · Integrated heat sink,
rated operational voltage Ue 48 ... 460 V AC
70 27.5 24 DC -- 3RF2370-3BA04 1 1 unit 41C
70 27.5 110 ... 230 AC -- 3RF2370-3BA24 1 1 unit 41C
Instantaneous switching · Integrated heat sink,
blocking voltage 1 600 V,
rated operational voltage Ue 48 ... 600 V AC
70 27.5 24 DC -- 3RF2370-3BA06 1 1 unit 41C
70 27.5 110 ... 230 AC -- 3RF2370-3BA26 1 1 unit 41C
Short-circuit-proof with B MCB,
zero-point switching · Integrated heat sink,
rated operational voltage Ue 24 ... 230 V AC
6
3RF2320-3DA02
Short-circuit-proof with B MCB,
zero-point switching · Integrated heat sink,
rated operational voltage Ue 48 ... 460 V AC
20 -- 24 DC 3RF2320-3DA04 1 1 unit 41C
20 -- 110 ... 230 AC 3RF2320-3DA24 1 1 unit 41C
These versions are equipped with a special mounting foot. Snapping them Other rated control supply voltages on request.
onto grounded DIN rails or mounting them on a grounded mounting plate
simultaneously provides safe grounding of the heat sink. Additional Accessories, see page 6/145.
grounding is no longer necessary in this case.
-- With these versions, the ground connection to the heat sink can be
established by means of a screw terminal connection.
1)
The type current provides information about the performance of the
solid-state contactor. The actual permitted rated operational current Ie
can be smaller depending on the installation conditions.
For derating characteristic curves, see page 6/120, "More information".
2)
Utilization category AC-15:
Electromagnetic loads, e.g. valves according to IEC 60947-5-1.
Parameters: max. 1 200 1/h, 50% ON period, 10-times inrush current
for 60 ms.
■ Accessories
Version Article No. Price PU PS* PG
per PU (UNIT,
SET, M)
Terminal covers
Ring cable lug
connection
Terminal covers 3RF2900-3PA88 1 10 units 41C
For 3RF23 solid-state contactors with ring cable lug
connection
With this terminal cover, degree of protection IP20
can be achieved on the front with a ring cable lug
connection. It can also be used for screw terminals
after simple adaptation.
3RF2900-3PA88
Control connectors
Screw terminals
6
3RF2900-1TA88
Spring-loaded
terminals
Replacement control connectors 3RF2900-2TA88 1 50 units 41C
For 3RF23 and 3RF24 solid-state contactors
With spring-loaded terminals
3RF2900-2TA88
Control connectors 3RF2900-2TB88 1 10 units 41C
For 3RF23 and 3RF24 solid-state contactors
With spring-loaded terminals
With two clamping points per contact
3RF2900-2TB88
Tools for opening spring-loaded terminals
Screwdrivers 3RA2908-1A 1 1 unit 41B
For all SIRIUS devices
With spring-loaded terminals
Length approx. 200 mm,
size 3.0 mm x 0.5 mm,
3RA2908-1A titanium gray/black,
partially insulated
Blank labels
Unit labeling plates
For SIRIUS devices1)
10 mm × 7 mm, titanium gray 3RT2900-1SB10 100 816 41B
units
20 mm × 7 mm, titanium gray 3RT2900-1SB20 100 340 41B
IC01_00181
units
Adhesive labels
3RT2900-1SB20 For SIRIUS devices
19 mm × 6 mm, titanium gray 3RT2900-1SB60 100 3060 41B
units
1) PC labeling system for individual inscription
of unit labeling plates available from:
murrplastik Systemtechnik GmbH
(see page 16/18).
■ Technical specifications
More information
System Manual for modular system, see FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/16223/faq
https://support.industry.siemens.com/cs/ww/en/view/60311318
NSB0_01703
1) These products were built as Class A devices. The use of these devices
in residential areas could result in radio interference. In this case it may
be required to introduce additional interference suppression measures.
The versions 3RF24..-1AC55 comply with Class B for residential, business
and commercial applications.
2)
If two different conductor cross-sections are connected to one clamping
point, both cross-sections must lie in one of the ranges specified.
Type Type current/ Rated operational current Ie Power loss Minimum load Max. off-state Rated peak I2t value
performance at IAC-51 current current withstand
capacity1) current Itsm
IAC-51 according to according to
IEC 60947-4-3 UL/CSA
at 40 °C at 40 °C at 50 °C
A A A W A mA A A²s
Main circuit
3RF2410-.AB.5 10.5 7 7 23 0.1 10 200 200
3RF2420-.AB.5 22 15 15 44 0.5 10 600 1 800
3RF2430-.AB.5 30 22 22 61 0.5 10 1 200 7 200
3RF2440-.AB.5 40 30 30 80 0.5 10 1 150 6 600
3RF2450-.AB.5 50 38 38 107 0.5 10 1 150 6 600
3RF2410-.AC.5 10.5 7 7 31 0.5 10 300 450
3RF2420-.AC.5 22 15 15 66 0.5 10 600 1 800
3RF2430-.AC.5 30 22 22 91 0.5 10 1 200 7 200
3RF2440-.AC.5 40 30 30 121 0.5 10 1 150 6 600
3RF2450-.AC.5 50 38 38 160 0.5 10 1 150 6 600
1)
The type current provides information about the performance of the
solid-state contactor. The actual permitted rated operational current Ie
can be smaller depending on the connection method and installation
conditions.
6
H
H
D
D
W W
A mm A mm
Main circuit Main circuit
3RF2410-.AB.. 10.5 45 x 95 x 92.5 3RF2430-.AC.. 30 89.5 x 100 x 123
3RF2410-.AC.. 3RF2440-.AB.. 40
3RF2420-.AB.. 22 45 x 100 x 112 3RF2440-.AC.. 40 120 x 95 x 130
3RF2420-.AC.. 22 74.5 x 100 x 114.5 3RF2450-.AB.. 50
3RF2430-.AB.. 30 3RF2450-.AC.. 50 120 x 150 x 130
6
established by means of a screw terminal connection.
Type current/ Rated control supply Grounding Ring cable lug PU PS* PG
performance voltage Us connection (UNIT,
capacity1) SET, M)
Imax
Article No. Price
A V per PU
Zero-point switching · Integrated heat sink,
rated operational voltage Ue 48 ... 600 V AC
2-phase controlled
50 4 ... 30 DC -- 3RF2450-3AB45 1 1 unit 41C
50 230 AC -- 3RF2450-3AB55 1 1 unit 41C
3-phase controlled
50 4 ... 30 DC -- 3RF2450-3AC45 1 1 unit 41C
50 230 AC -- 3RF2450-3AC55 1 1 unit 41C
-- With these versions, the ground connection to the heat sink can be Accessories, see page 6/145.
established by means of a screw terminal connection.
1)
The type current provides information about the performance of the
solid-state contactor. The actual permitted rated operational current Ie
can be smaller depending on the connection method and installation
conditions.
For derating characteristic curves, see page 6/120, "More information".
■ Overview
Function modules for SIRIUS 3RF2 solid-state switching devices
A great variety of applications demand an expanded range The following function modules are available:
of functionality. With our function modules, these requirements • Converters (without current measurement)
can be met really easily. The modules are mounted simply • Load monitoring
by clicking them into place; straight away the necessary • Heating current monitoring
connections are made with the solid-state relay or contactor. • Power controllers
The plug-in connection to control the solid-state switching • Power regulators
devices can simply remain in use. The external connections Note:
have screw terminals.
With the exception of the converter, the function modules can
For function modules with current measurement, the load cable be used only with 1-phase solid-state switching devices.
must be inserted through the straight-through transformer and
reconnected to the solid-state switching device. For recommended assignment of the function modules to
3RF2 solid-state switching devices, see Industry Mall.
■ Technical specifications
More information
Online configurator, see www.siemens.com/sirius/configurators FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/16231/faq
System Manual for modular system, see Conversion tool, see www.siemens.com/conversion-tool
6
https://support.industry.siemens.com/cs/ww/en/view/60311318
6
Type 3RF29..-...0. 3RF29..-...1.
Control circuit
Method of operation DC operation AC/DC operation
Rated control supply voltage Us V 24
Rated actuating current mA 25 40
Rated frequency Hz -- 50/60
of the control supply voltage
Actuating voltage, max. V 30
Rated actuating current mA 30 50
At maximum voltage
Response voltage V 15
• For operating current mA 2
Drop-out voltage V 5
■ Overview ■ Application
Converters for 3RF2 solid-state switching devices The function module is used for converting an analog input
signal to an input/output ratio with the time base 1 s. The module
These modules are used to convert analog control signals, such can only be used in conjunction with 3RF21 and 3RF23 1-phase
as those output from many temperature controllers for example, solid-state switching devices or 3RF22 and 3RF24 3-phase
into a pulse-width-modulated digital signal. The connected devices. It can be used on versions with 24 V DC and
solid-state contactors and relays can therefore regulate the 24 V AC/DC control supply voltage.
output of a load as a percentage.
Note:
The use of 1-pole solid-state switching devices with converters,
power controllers or power regulators of loads in a three-phase
network in full-wave control mode is not recommended.
As mutual synchronization of the function modules is not
possible, fluctuations in the heating power are possible; there is
no optimum settling in particular with setpoint values < 50%.
Converters
Rated control supply voltage 24 V AC/DC
-- -- 3RF2900-0EA18 1 1 unit 41C
3RF2900-0EA18
■ Accessories
Version Article No. Price PU PS* PG
per PU (UNIT,
SET, M)
Blank labels
Unit labeling plates
For SIRIUS devices1)
10 mm × 7 mm, titanium gray 3RT2900-1SB10 100 816 41B
units
20 mm × 7 mm, titanium gray 3RT2900-1SB20 100 340 41B
IC01_00181
units
Adhesive labels
3RT2900-1SB20 For SIRIUS devices
19 mm × 6 mm, titanium gray 3RT2900-1SB60 100 3060 41B
units
1) PC labeling system for individual inscription
of unit labeling plates available from:
murrplastik Systemtechnik GmbH
(see page 16/18).
■ Overview In order to detect the failure of one of several loads, the current
difference must be 1/6 (in the basic version) or 1/12 (in the
Load monitoring for 3RF2 1-phase solid-state switching extended version) of the reference value. In the event of a fault,
devices an output is actuated and one or more LEDs indicate the fault.
6
A V per PU
Basic load monitoring
Rated control supply voltage 24 V DC
6 -- 3RF2906-0FA08 1 1 unit 41C
20 -- 3RF2920-0FA08 1 1 unit 41C
• With mounted 3RF2900-0RA88 cover
6 -- 3RF2906-0FA08-0KH0 1 1 unit 41C
20 -- 3RF2920-0FA08-0KH0 1 1 unit 41C
3RF2920-0FA08
Extended load monitoring
Rated control supply voltage 24 V AC/DC
20 110 ... 230 3RF2920-0GA13 1 1 unit 41C
20 400 … 600 3RF2920-0GA16 1 1 unit 41C
50 110 ... 230 3RF2950-0GA13 1 1 unit 41C
50 400 … 600 3RF2950-0GA16 1 1 unit 41C
90 110 ... 230 3RF2990-0GA13 1 1 unit 41C
90 400 … 600 3RF2990-0GA16 1 1 unit 41C
3RF2920-0GA13
■ Accessories
Version Article No. Price PU PS* PG
per PU (UNIT,
SET, M)
Covers
Sealable covers for function modules 3RF2900-0RA88 1 10 units 41C
(not for converters)
For securing against unauthorized adjustment of setting knobs
3RF2900-0RA88
Blank labels
Unit labeling plates
For SIRIUS devices1)
10 mm × 7 mm, titanium gray 3RT2900-1SB10 100 816 41B
units
IC01_00181
3RF2916-0JA13
1)
Supplied without control connector. The control connector can be
purchased from Wieland by quoting article number 8213 B/6VR
(PCB connector), see page 16/18.
■ Accessories
Version Article No. Price PU PS* PG
per PU (UNIT,
SET, M)
Covers
Sealable covers for function modules 3RF2900-0RA88 1 10 units 41C
(not for converters)
For securing against unauthorized adjustment of setting knobs
3RF2900-0RA88
Blank labels
Unit labeling plates
For SIRIUS devices1)
10 mm × 7 mm, titanium gray 3RT2900-1SB10 100 816 41B
units
20 mm × 7 mm, titanium gray 3RT2900-1SB20 100 340 41B
IC01_00181
units
Adhesive labels
3RT2900-1SB20 For SIRIUS devices
19 mm × 6 mm, titanium gray 3RT2900-1SB60 100 3060 41B
units
1)
PC labeling system for individual inscription
of unit labeling plates available from:
murrplastik Systemtechnik GmbH
(see page 16/18).
■ Overview ■ Application
Power controllers for 3RF2 1-phase solid-state switching The power controller can be used for:
devices • Complex heating systems
The power controller is a function module for the autonomous • Inductive loads
power control of complex heating systems and inductive loads. • Loads with temperature-dependent resistor
The following functions have been integrated: • Loads with ageing after long-time service
• Power controller • Simple indirect control of temperature
For adjusting the power of the connected load. The setpoint
value is selected via a rotary knob on the module as Notes:
a percentage of the 100% power value stored. This function module can only be used in conjunction with
• Inrush current limiting a 3RF21 solid-state relay or a 3RF23 solid-state contactor.
With the aid of an adjustable voltage ramp, the inrush current The solid-state switching devices with spring-loaded terminals
is limited by means of phase control. This is useful above all in the load circuit are not suitable!
with loads such as lamps or infrared lamps which have an
inrush transient current. Power control
• Load circuit monitoring The power controller adjusts the power in the connected load
For detecting load failure, partial load faults, alloyed power by means of a solid-state switching device depending on the
semiconductors, lack of voltage or a break in the load circuit. setpoint selection. It does not compensate for changes in the
Note: mains voltage or load resistance. The setpoint value can be
predefined externally as a 0 to 10 V signal or internally by
With the phase control operating mode, a partial load fault is
6
means of a potentiometer. Depending on the setting of the
detected by cyclic "scanning" of the load; the exact mode of potentiometer (tR), the control is carried out according to the
operation is described in the data sheets! principle of full-wave control or generalized phase control.
Special versions: Note:
Deviations from the standard version
In the case of ohmic loads, the power is set linear to the setpoint
3RF2904-0KA13-0KC0 (no teach current) value. During operation of inductive loads, the power control is
During the teach routine, the connected solid-state relay or no longer proportional and linear due to the phase shift between
contactor is not activated; i.e. no current will flow. No current current and voltage.
reference value is stored. No partial load monitoring! Full-wave control
3RF29..-0KA1.-0KT0 (without partial load faults) In this operating mode the output is adjusted to the required
No partial load monitoring! setpoint value by changing the on-to-off period. The period
duration is predefined at 1 s.
Notes:
The use of 1-pole solid-state switching devices with converters,
power controllers or power regulators of loads in a three-phase
network in full-wave control mode is not recommended.
As mutual synchronization of the function modules is not
possible, fluctuations in the heating power are possible; there is
no optimum settling in particular with setpoint values < 50%.
Generalized phase control
In this operating mode the output is adjusted to the required
setpoint value by changing the current flow angle. In order to
observe the limit values of the conducted interference voltage
for industrial networks, at loads up to 20 kVA, the load circuit
must include an additional filter, and for loads above 20 kVA,
a reactor with a rating of at least 200 H must be used. You will
find details about the filters in the FAQ "Filters for 3RF29 power
regulators and power controllers to comply with the limits for
electromagnetic emitted interference", see
https://support.industry.siemens.com/cs/ww/en/view/109751887.
■ Accessories
Version Article No. Price PU PS* PG
per PU (UNIT,
6
SET, M)
Covers
Sealable covers for function modules 3RF2900-0RA88 1 10 units 41C
(not for converters)
For securing against unauthorized adjustment of setting knobs
3RF2900-0RA88
Blank labels
Unit labeling plates
For SIRIUS devices1)
10 mm × 7 mm, titanium gray 3RT2900-1SB10 100 816 41B
units
20 mm × 7 mm, titanium gray 3RT2900-1SB20 100 340 41B
IC01_00181
units
Adhesive labels
3RT2900-1SB20 For SIRIUS devices
19 mm × 6 mm, titanium gray 3RT2900-1SB60 100 3060 41B
units
1)
PC labeling system for individual inscription
of unit labeling plates available from:
murrplastik Systemtechnik GmbH
(see page 16/18).
■ Overview ■ Application
Power regulators for 3RF2 1-phase solid-state switching The power regulator can be used for:
devices • Complex heating systems
The power regulator is a function module for the autonomous • Heating elements with temperature-dependent resistor
power control of complex heating systems. • Heating elements with ageing after long-time service
The following functions have been integrated: • Simple indirect control of temperature
• Power controller with proportional-action control Notes:
For adjusting the power of the connected load. The setpoint
value is selected via a rotary knob on the module as This function module can only be used in conjunction with
a percentage of the 100% power value stored. Changes in the a 3RF21 solid-state relay or a 3RF23 solid-state contactor.
mains voltage or in the load resistance are compensated in The solid-state switching devices with spring-loaded terminals
this case. in the load circuit are not suitable!
• Inrush current limiting
With the aid of an adjustable voltage ramp, the inrush current Power control
is limited by means of phase control. This is useful above all The power regulator adjusts the power in the connected load by
with loads such as lamps which have an inrush transient means of a solid-state switching device depending on the taught
current. power and the selected setpoint. Changes in the mains voltage
• Load circuit monitoring or in the load resistance are thus compensated by the power
For detecting load failure, alloyed power semiconductors, regulator. The setpoint value can be predefined externally as
lack of voltage or a break in the load circuit. Partial load a 0 to 10 V signal or internally by means of a potentiometer.
monitoring is not possible. Load fluctuations are compensated. Depending on the setting of the potentiometer (tR),
6
the adjustment is carried out according to the principle
of full-wave control or generalized phase control.
Note:
In the case of ohmic loads, the power is set linear to the setpoint
value. During operation of inductive loads, the power control is
no longer proportional and linear due to the phase shift between
current and voltage.
Full-wave control
In this operating mode the output is adjusted to the required
setpoint value by changing the on-to-off period. The period
duration is predefined at 1 s.
Notes:
The use of 1-pole solid-state switching devices with converters,
power controllers or power regulators of loads in a three-phase
network in full-wave control mode is not recommended.
As mutual synchronization of the function modules is not
possible, fluctuations in the heating power are possible; there is
no optimum settling in particular with setpoint values < 50%.
Generalized phase control
In this operating mode the output is adjusted to the required
setpoint value by changing the current flow angle. In order to
observe the limit values of the conducted interference voltage
for industrial networks, at loads up to 20 kVA, the load circuit
must include an additional filter, and for loads above 20 kVA,
a reactor with a rating of at least 200 H must be used. You will
find details about the filters in the FAQ "Filters for 3RF29 power
regulators and power controllers to comply with the limits for
electromagnetic emitted interference", see
https://support.industry.siemens.com/cs/ww/en/view/109751887.
3RF2920-0HA13
■ Accessories
Version Article No. Price PU PS* PG
per PU (UNIT,
6
SET, M)
Covers
Sealable covers for function modules 3RF2900-0RA88 1 10 units 41C
(not for converters)
For securing against unauthorized adjustment of setting knobs
3RF2900-0RA88
Blank labels
Unit labeling plates
For SIRIUS devices1)
10 mm × 7 mm, titanium gray 3RT2900-1SB10 100 816 41B
units
20 mm × 7 mm, titanium gray 3RT2900-1SB20 100 340 41B
IC01_00181
units
Adhesive labels
3RT2900-1SB20 For SIRIUS devices
19 mm × 6 mm, titanium gray 3RT2900-1SB60 100 3060 41B
units
1)
PC labeling system for individual inscription
of unit labeling plates available from:
murrplastik Systemtechnik GmbH
(see page 16/18).
■ Overview
More information
Industry Mall, see www.siemens.com/product?3RF Online configurator, see www.siemens.com/sirius/configurators
Conversion tool, see www.siemens.com/conversion-tool
6
Spring-loaded terminals
This innovative technology manages without any screw
connection. This means that very high vibration resistance is
Solid-state contactor for direct-on-line starting achieved. Two conductors of up to 2.5 mm² can be connected
to each terminal.
The solid-state contactors for switching motors are intended
for frequently switching on and off three-phase current operating Motor feeders
mechanisms up to 7.5 kW and reversing up to 3.0 kW.
The devices are constructed with complete insulation and The devices can use a link module to directly connect to
can be mounted directly on SIRIUS motor starter protectors, a motor starter protector. Also possible is the mounting of
overload relays and current monitoring relays, resulting in a very a 3RB30/3RB31 electronic overload relay (see page 7/95)
simple integration into motor feeders. or a 3RR2 current monitoring relay (see pages 10/47 and 10/55)
using a link adapter. The simultaneous mounting of a motor
These 3-phase solid-state contactors are equipped with starter protector and an overload or current monitoring relay is
a 2-phase control which is particularly suitable for typical motor not recommended for space and heat development reasons.
current circuits without connecting to the neutral conductor.
Rapid-switching fuseless and fused motor feeders can thereby
Solid-state contactors for switching motors are available in two be implemented in a time-saving manner.
versions:
Selecting solid-state contactors
• SIRIUS 3RF34 solid-state contactors, 3-phase:
These 2-phase controlled, instantaneous switching solid-state The solid-state contactors are selected on the basis of details of
contactors in the insulating enclosure are offered with a width the network, the load and the ambient conditions.
of 45 mm up to 5.2 A – and with a width of 90 mm up to 16 A.
They allow the operation of motors up to 7.5 kW. The following procedure is recommended:
• SIRIUS 3RF34 solid-state reversing contactors, 3-phase: • Determine the rated current of the load and the mains voltage
The integration of four conducting paths to a reverse switch, • Select a solid-state contactor with the same or higher rated
combined in one enclosure, makes this device a particularly current than the load
compact solution. Compared to conventional systems, • Testing of the maximum permissible switching frequency
for which two contactors are required, it is possible to save up based on the characteristic curves (see "More information" ➞
to 50% width with the 3-phase reversing contactors. Devices "Product information", page 6/161). To do this, the starting
with a width of 45 mm cover motors up to 2.2 kW – and those current, the starting time and the motor load in the operating
with a width of 90 mm cover motors up to 3 kW. phase must be known.
Note: • If the permissible switching frequency is under the desired
frequency, it is possible to achieve an increase only by
In accordance with the product standard IEC 60947-4-2,
overdimensioning the motor and the solid-state contactor!
the motor contactors are designed for motors with maximum
starting current conditions of I/Ie 8. For configuring motors with The correct device size can be determined by entering the
higher starting current conditions (typically I/Ie 8), the data in network and motor data along with the application and ambient
the Equipment Manual for 3RF34 solid-state switching devices conditions.
must be taken into account, see
https://support.industry.siemens.com/cs/ww/en/view/60298187.
■ Benefits
• Insulated enclosure with integrated heat sink, "ready to use" • Variety of connection methods
• Compact and space-saving design • Plug-in control connection
• Reversing contactors with integrated interlocking • Display via LEDs
• High degree of protection • Wide voltage range for AC control supply voltage
• Integrated mounting foot for snapping onto a DIN rail or for
mounting on a support plate
■ Application
Use in load feeders Standards and approvals
There is no typical design of a load feeder with solid-state relays • IEC 60947-4-2
or solid-state contactors; instead, the great variety of connection • UL 508, CSA for North America1)
methods and control voltages offers universal application • CE marking for Europe
opportunities.
• C-Tick approval for Australia
SIRIUS solid-state relays and solid-state contactors can be
installed in fuseless or fused feeders, as required. • CCC approval for China
1) Please note: Use overvoltage protection device;
See Configuration Manual for load feeders, max. cut-off-voltage 6 000 V;
https://support.industry.siemens.com/cs/ww/en/view/39714188. min. energy handling capability 100 J.
■ Technical specifications
Type 3RF3405-1BB.. 3RF3410-1BB.., 3RF3405-2BB.. 3RF3410-2BB..,
3RF3403-1BD.., 3RF3412-1BB.., 3RF3412-2BB..,
3RF3405-1BD.. 3RF3416-1BB.. 3RF3416-2BB..
3RF3410-1BD..
H
Dimensions (W x H x D)
• 3RF34..-1BB.. mm 45 x 95 x 96.5 90 x 95 x 96.5 45 x 95 x 96.5 90 x 95 x 96.5
D
W
• 3RF34..-1BD.. mm 45 x 95 x 108.5 90 x 95 x 108.5 -- --
General technical specifications
Ambient temperature
• During operation, derating from 40 °C °C -25 ... +60
• During storage °C -55 ... +80
Installation altitude m 0 ... 1 000; derating over 1 000 m on request
Shock resistance according to IEC 60068-2-27 g/ms 15/11
Vibration resistance according to IEC 60068-2-6 g 2
Degree of protection IP on the front IP20
according to IEC 60529
Touch protection on the front according to IEC 60529 Finger-safe for vertical touching from the front
Insulation strength at 50/60 Hz V rms 4 000
(main/control circuit to floor)
Electromagnetic compatibility (EMC)
6
• Emitted interference according to IEC 60947-4-2
- Conducted interference voltage Class A for industrial applications1)
- Emitted, high-frequency interference voltage Class A for industrial applications
• Interference immunity
- Electrostatic discharge kV Contact discharge: 4; air discharge: 8;
according to IEC 61000-4-2 Behavior criterion 2
(corresponds to degree of severity 3)
- Induced RF fields MHz 0.15 ... 80;
according to IEC 61000-4-6 140 dBµV; behavior criterion 1
- Burst according to IEC 61000-4-4 kV 2; at 5 kHz; behavior criterion 2
- Surge according to IEC 61000-4-52) kV Conductor - ground 2; conductor - conductor 1; behavior criterion 2
Connection type Screw terminals Spring-loaded terminals
Operating devices Standard screwdriver size 2 and Pozidriv 2 3.0 x 0.5 and 3.5 x 0.5
Conductor cross-sections, main contacts
• Solid mm2 2 x (1.5 ... 2.5)3), 2 x (2.5 ... 6)3) 2 x (0.5 ... 2.5)
• Finely stranded with end sleeve mm2 2 x (1 ... 2.5)3), 2 x (2.5 ... 6)3), 1 x 10 2 x (0.5 ... 1.5)
• Finely stranded without end sleeve mm2 -- 2 x (0.5 ... 2.5)
• AWG cables, solid or stranded AWG 2 x (14 ... 10) 2 x (18 ... 14)
Conductor cross-sections, auxiliary/control contacts
• With/without end sleeve mm2 1 x (0.5 ... 2.5), 2 x (0.5 ... 1.0) 0.5 ... 2.5
• AWG cables, solid or stranded AWG 20 ... 12 20 ... 12
Permissible mounting position ±10° ±10°
NSB0_01703
1) These products were built as Class A devices. The use of these devices in 2) The following applies for reversing contactors: To maintain the values,
residential areas could result in radio interference. In this case it may be a 3TX7462-3L surge suppressor should be used between phases L1 and
required to introduce additional interference suppression measures. L3 as close as possible to the reversing contactor.
3) If two different conductor cross-sections are connected to one clamping
point, both cross-sections must lie in one of the ranges specified.
■ More information
For more information, see Product information and technical specifications
• System Manual for modular system, For product data sheets with detailed technical specifications
https://support.industry.siemens.com/cs/ww/en/view/60311318 and dimensional drawings, see
• Equipment Manual for 3RF34 solid-state switching devices, https://support.industry.siemens.com/cs/ww/en/ps/16237/td.
https://support.industry.siemens.com/cs/ww/en/view/60298187 For more information, please enter the article number of the
required device under the tab "Product List".
■ Technical specifications
More information
System Manual for modular system, see FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/16237/faq
https://support.industry.siemens.com/cs/ww/en/view/60311318
Equipment Manual for 3RF34 solid-state switching devices, see
https://support.industry.siemens.com/cs/ww/en/view/60298187
1)
The reduced values in brackets apply to a directly mounted motor starter
protector and simultaneous side-by-side mounting.
6
12.5 5.5 3RF3412-1BB06 1 1 unit 41C
16 7.5 3RF3416-1BB06 1 1 unit 41C
5.2 2.2 110 ... 230 AC 3RF3405-1BB26 1 1 unit 41C
9.2 4.0 3RF3410-1BB26 1 1 unit 41C
12.5 5.5 3RF3412-1BB26 1 1 unit 41C
16 7.5 3RF3416-1BB26 1 1 unit 41C
3RF3410-1BB
3RF3410-2BB
■ Accessories
Version Article No. Price PU PS* PG
per PU (UNIT,
SET, M)
3RA2921-1BA00
Link adapters between solid-state contactor and overload relay
Link adapters
For direct mounting of 3RB3 overload relays or
3RR2 current monitoring relays to the solid-state
contactor with screw terminals
3RF3900-0QA88
The adapter is snapped onto the enclosure of the 3RF3900-0QA88 1 1 unit 41C
3RF34 contactor and accommodates the fixing hooks
of the 3RB3 overload relays or the 3RR2 current monitoring
relays for direct mounting.
6
3RA2908-1A
Control connectors
Control connectors
For solid-state contactors with spring-loaded terminals
With two clamping points per contact 3RF2900-2TB88 1 10 units 41C
3RF2900-2TB88
Blank labels
Unit labeling plates
For SIRIUS devices1)
10 mm x 7 mm, titanium gray 3RT2900-1SB10 100 816 41B
units
20 mm x 7 mm, titanium gray 3RT2900-1SB20 100 340 41B
IC01_00181
units
Adhesive labels
3RT2900-1SB20 For SIRIUS devices
19 mm x 6 mm, titanium gray 3RT2900-1SB60 100 3060 41B
units
1)
PC labeling system for individual inscription
of unit labeling plates available from:
murrplastik Systemtechnik GmbH
(see page 16/18).
■ Technical specifications
More information
System Manual for modular system, see Equipment Manual for 3RF34 solid-state switching devices, see
https://support.industry.siemens.com/cs/ww/en/view/60311318 https://support.industry.siemens.com/cs/ww/en/view/60298187
FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/16237/faq
6
The reduced values in brackets apply to a directly mounted motor starter
protector and simultaneous side-by-side mounting.
Type 3RF34..-.BD.4
Main circuit
Controlled phases 2-phase
Rated operational voltage Ue1) V AC 48 ... 480
• Operating range V AC 40 ... 506
• Rated frequency Hz 50/60 10%
Rated insulation voltage Ui V 600
Rated impulse withstand voltage Uimp kV 6
Blocking voltage V 1 200
Rate of voltage rise V/µs 1 000
1)
To reduce the risk of a phase short circuit due to overvoltage, We recommend a design with semiconductor protection as short-circuit
we recommend using a varistor type 3TX7462-3L between the phases L1 protection.
and L3 as close as possible to the switchgear.
3RF3403-1BD
3.8 1.5 110 ... 230 AC 3RF3403-1BD24 1 1 unit 41C
5.4 2.2 3RF3405-1BD24 1 1 unit 41C
7.4 3.0 3RF3410-1BD24 1 1 unit 41C
6
3RF3410-1BD
■ Accessories
Version Article No. Price PU PS* PG
per PU (UNIT,
SET, M)
3RA2921-1BA00
Link adapters between solid-state contactor and overload relay
Link adapters
For direct mounting of 3RB3 overload relays or 3RR2 current
monitoring relays to the solid-state contactor with screw
terminals
3RF3900-0QA88
The adapter is snapped onto the enclosure of the 3RF3900-0QA88 1 1 unit 41C
3RF34 contactor and accommodates the fixing hooks
of the 3RB3 overload relays or the 3RR2 current monitoring
relays for direct mounting.
Blank labels
Unit labeling plates
For SIRIUS devices1)
10 mm x 7 mm, titanium gray 3RT2900-1SB10 100 816 41B
units
20 mm x 7 mm, titanium gray 3RT2900-1SB20 100 340 41B
IC01_00181
units
Adhesive labels
3RT2900-1SB20 For SIRIUS devices
19 mm x 6 mm, titanium gray 3RT2900-1SB60 100 3060 41B
units
1)
PC labeling system for individual inscription
of unit labeling plates available from:
murrplastik Systemtechnik GmbH
(see page 16/18).
Protection equipment
Price groups
PG 12P, 14O, 41B, 41E, 41F, 41G, 41H,
41J, 42F, 42J
7/2 Introduction
7
7/50 - Busbar accessories
7/54 - Rotary operating mechanisms
7/57 - Mounting accessories
7/64 - Enclosures and front plates
7/67 3RV29 infeed system
SIRIUS 3RV1 motor starter
protectors/circuit breakers
7/73 For fuse monitoring
7/74 For distance protection
7/75 For motor protection
Overload relays
7/76 General data
SIRIUS 3RU2 thermal overload relays
7/83 3RU2 for standard applications
7/93 Accessories
SIRIUS 3RB3 electronic overload relays
7/95 3RB30, 3RB31 for standard
applications
7/105 Accessories
SIRIUS 3RB2 electronic overload relays
7/107 3RB20, 3RB21 for standard
applications
7/117 Accessories for 3RB20, 3RB21
7/119 3RB22, 3RB23
for high-feature applications
7/127 3RB24 for IO-Link for high-feature
applications
7/134 Current measuring modules for 3RB22,
3RB23 and 3RB24
7/138 Accessories for 3RB22, 3RB23, 3RB24
Siemens IC 10 · 2023
© Siemens 2023
Protection equipment
Introduction
■ Overview
• Size S0 A Up to 40 Up to 32 Up to 40 Up to 25 Up to 22 Up to 22
• Size S2 A Up to 80 Up to 80 Up to 80 Up to 65 -- --
• Size S3 A Up to 100 Up to 100 Up to 100 -- Up to 70 --
Rated operational voltage Ue V 690 AC3) 690 AC3) 690 AC3) 690 AC3) 690 AC 690 AC
according to IEC
Rated frequency Hz 50/60 50/60 50/60 50/60 50/60 50/60
Trip class CLASS 10 (S00 ... S3), CLASS 10 -- CLASS 10 -- --
CLASS 20 (S2, S3)
Thermal overload release A 0.11 ... 0.16 to 0.11 ... 0.16 to None4) 0.11 ... 0.16 to 0.16 ... 70 0.16 ... 22
A 80 ... 100 80 ... 100 54 ... 65 Non-adjustable Non-adjustable
Electronic release
A multiple of the rated current 13 times 13 times 13 times 20 times 13 times 20 times
Short-circuit breaking kA 20/55/65/100 55/65/100 20/55/65/100 55/65/100 5) 5)
capacity Icu at 400 V AC
Pages 7/27 ... 7/34 7/35, 7/36 7/37 ... 7/39 7/40, 7/41 7/45 7/46
Accessories
For sizes S00 S0 S2 S3 S00 S0 S2 S3 S00 S0 S2 S3 S00 S0 S2 S00 S0 S3 S00 S0
Auxiliary switches ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓6) ✓ ✓
Signaling switches ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- -- -- -- --
Undervoltage releases ✓ ✓ ✓ ✓ -- -- -- -- ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
Shunt releases ✓ ✓ ✓ ✓ -- -- -- -- ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
Isolator modules ✓ ✓ ✓ -- ✓ ✓ ✓ -- ✓ ✓ ✓ -- ✓ ✓ ✓ -- -- -- -- --
Insulated 3-phase busbar ✓ ✓ ✓ -- -- -- ✓ -- ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓ -- ✓ ✓
system
Busbar adapters ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- --
Door-coupling rotary operating ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
mechanisms
Link modules ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- -- -- -- --
Enclosures for surface mounting ✓ ✓ ✓ -- ✓ ✓ ✓ -- ✓ ✓ ✓ -- ✓ ✓ ✓ -- -- -- -- --
Enclosures for flush mounting ✓ ✓ -- -- ✓ ✓ -- -- ✓ ✓ -- -- ✓ ✓ -- -- -- -- -- --
Front plates ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- -- -- -- --
Infeed system ✓ ✓ -- -- -- -- -- -- ✓ ✓ -- -- ✓ ✓ -- ✓ ✓ -- ✓ ✓
Sealable scale covers for setting ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- -- -- -- ✓ ✓ ✓ -- -- -- -- --
knobs
Pages 7/47 ... 7/66
✓ Has this function or can use this accessory 5) According to UL 489 at 480 Y/277 V AC: 65 kA or 50 kA.
6)
-- Does not have this function or cannot use this accessory Only lateral auxiliary switches can be used
1) For symmetrical loading of the three phases.
2)
For 1-phase, 2-phase and 3-phase asymmetrical loading of the three phases.
3)
With molded-plastic enclosure 500 V AC.
4) For overload protection of the motors, appropriate overload relays must
be used.
Protection equipment
Introduction
7
Accessories
For sizes S00 S00 S00
Auxiliary switches ✓ ✓ ✓
Further accessories -- -- ✓
Pages 7/73 7/74 7/47 ... 7/72
1)
✓ Has this function or can use this accessory With molded-plastic enclosure 500 V AC.
-- Does not have this function or cannot use this accessory
Protection equipment
Introduction
Accessories
For sizes S00 S0 S2 S3 S00 S0 S2 S3 S00 S0 S2 S3
Terminal supports for stand-alone ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
installation
Mechanical RESET ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
Cable releases for RESET ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
Electrical Remote RESET ✓ ✓ ✓ ✓ -- -- -- -- Integrated in the unit
Terminal covers for box terminal -- -- ✓ ✓ -- -- ✓ ✓ -- -- ✓ ✓
Sealable covers for setting knobs ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
Pages 7/93, 7/94 7/105, 7/106 7/105, 7/106
1)
✓ Has this function or can use this accessory The units are responsible in the main circuit for overload protection of the
-- Does not have this function or cannot use this accessory assigned electrical loads (e.g. motors), feeder cable, and other switching
and protection devices in the respective load feeder.
Protection equipment
Introduction
7
with current measuring modules
3RB2906-2BG1/3RB2906-2DG1
• Size S2 A -- -- Up to 100 and 55 mm width
• Size S3 A -- -- with current measuring module
3RB2906-2JG1
• Size S6 A Up to 200 Up to 200 Up to 200 and 120 mm width
with current measuring modules
3RB2956-2TH2/3RB2956-2TG2
• Size S10/S12 A Up to 630 Up to 630 Up to 630 and 145 mm width
with current measuring module
3RB2966-2WH2
• Size 14 (3TF68/3TF69) A Up to 630 Up to 630 Up to 820
with current measuring module
3RB2906-2BG1 and
transformer 3UF1868-3GA00
Rated operational voltage Ue V 690/1 000 AC 690/1 000 AC 690/1 000 AC2)
Rated frequency Hz 50/60 50/60 50/60
Trip class CLASS 10, 20 CLASS 5, 10, 20, 30 CLASS 5, 10, 20, 30
adjustable adjustable
Thermal overload release A -- -- --
Electronic overload releases A 50 ... 200 to 50 ... 200 to 0.3 ... 3 to
A 160 ... 630 160 ... 630 63 ... 630
Pages 7/114, 7/115 7/116 7/125, 7/126, 7/137 7/133, 7/137
Accessories
For sizes S6 S10/S12 S6 S10/S12 S00 S0 S2 S3 S6 S10/S12
3) 3) 3) 3) 3) 3) 3) 3) 3) 3)
Terminal supports for stand-alone
installation
Mechanical RESET ✓ ✓ ✓ ✓ -- -- -- -- -- --
Cable releases for RESET ✓ ✓ ✓ ✓ -- -- -- -- -- --
Electrical Remote RESET -- -- Integrated in the unit Integrated in the unit
Terminal covers ✓ ✓ ✓ ✓ -- -- -- ✓ ✓ ✓
Sealable covers for setting knobs ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
Operator panel for 3RB24 evaluation -- -- -- -- ✓ ✓ ✓ ✓ ✓ ✓
module
Pages 7/117, 7/118 7/117, 7/118 7/137 ... 7/139
1)
✓ Has this function or can use this accessory The units are responsible in the main circuit for overload protection of the
-- Does not have this function or cannot use this accessory assigned electrical loads (e.g. motors), feeder cable, and other switching
and protection devices in the respective load feeder.
2)
With reference to the 3RB29.6 current measuring modules.
3) Stand-alone installation without accessories is possible.
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
General data
■ Overview
More information
Homepage, see www.siemens.com/sirius-circuit-breakers Application Manual for switching devices with IE3 and IE4 motors, see
Industry Mall, see www.siemens.com/product?3RV2 https://support.industry.siemens.com/cs/ww/en/view/94770820
TIA Selection Tool Cloud (TST Cloud), see System Manual for modular system, see
www.siemens.com/tstcloud/?node=MotorStarterProtector https://support.industry.siemens.com/cs/ww/en/view/60311318
Conversion tool, see www.siemens.com/conversion-tool Equipment Manual, see
https://support.industry.siemens.com/cs/ww/en/view/60279172
Certificates, see https://support.industry.siemens.com/cs/ww/en/ps/16245/cert
The following illustration shows 3RV2 motor starter protectors/ Accessories, see page 7/47 onwards.
circuit breakers with the accessories which can be mounted for the
sizes S00 to S3, see also "Introduction" ➞ "Overview", page 7/2.
7
Mountable accessories
1 Transverse auxiliary switch
2 Lateral auxiliary switch with 2 contacts
3 Lateral auxiliary switch with 4 contacts
8 4 Shunt release (can not be used with
8 3RV21 motor starter protectors)
5 Undervoltage release without/with
leading contacts (can not be used with
3RV21 motor starter protectors)
6 Signaling switch (can not be used with
3RV27 and 3RV28 circuit breakers)
7
5
1
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
General data
The 3RV2...-.....-0BA0 motor starter protectors/circuit breakers Connection methods
can be used at low ambient temperatures down to -50 °C.
The 3RV2 motor starter protectors/circuit breakers can be
3RV20..-.....-0DA0 motor starter protectors for system protection supplied with screw terminals and spring-loaded terminals.
according to IEC, 3RV24..-.....-0DA0 for transformer protection
according to IEC and 3RV27 and 3RV28 circuit breakers Screw terminals
according to UL 489 can be used for 1-phase, 2-phase and
3-phase loads, as these motor starter protectors/circuit breakers Spring-loaded terminals
do not have asymmetry detection.
The 3RV27 and 3RV28 are approved as circuit breakers The terminals are indicated in the corresponding
according to UL 489; they are a special version of the 3RV2 tables by the symbols shown on orange backgrounds.
motor starter protectors.
Voltage data
Thanks to their dimensions, the 3RV1011 motor starter
The data for 3-phase power systems according to
protectors are suitable for installation in enclosures or under
IEC 60947-4-1 are valid for the following line system
cramped installation conditions.
configurations:
.
Type of construction
Voltage Ue Line system configurations
The 3RV2 motor starter protectors are available in four sizes: Three-phase Three-phase
• Size S00 – width 45 mm, four-wire networks three-wire networks
max. rated current 16 A,
at 400 V AC suitable for three-phase motors up to 7.5 kW
• Size S0 – width 45 mm,
IC01_00703
max. rated current 40 A,
IC01_00709
at 400 V AC suitable for three-phase motors up to 18.5 kW
• Size S2 – width 55 mm,
max. rated current 80 A,
V V V
at 400 V AC suitable for three-phase motors up to 37 kW
7
230 -- 230
• Size S3 – width 70 mm,
max. rated current 100 A, 400 230/400 400
at 400 V AC suitable for three-phase motors up to 45/55 kW 440 260/440 440
500 -- 500
Circuit breakers according to UL 489
690 400/690 690 (only as from size S3)
The 3RV27 and 3RV28 circuit breakers are available in two or 1 000 -- 1 000
three sizes:
-- Not specified
• Size S00 – width 45 mm,
max. rated current 15 A, for 480 Y/277 V AC Use in hazardous areas
• Size S0 – width 45 mm, The 3RV20 motor starter protectors for motor protection (without
max. rated current 22 A, for 480 Y/277 V AC 3RV20..-.....-0BA0 and -0DA0) have certification in accordance
• Size S3 – width 70 mm, with both the European Explosion Protection Directive (ATEX)
max. rated current 70 A, for 480 Y/277 V AC and the International Explosion Protection Standard (IECEx).
In accordance with the European Directive (ATEX), the 3RV20
(without 3RV20..-.....-0BA0 and -0DA0) are able to switch and
protect explosion-proof motors of type of protection "Increased
Safety EEx e".
In accordance with the international guideline (IECEx), the
3RV20 (without 3RV20..-.....-0BA0 and -0DA0) are able to switch
and protect motors of the types "Increased Safety Ex e" or
"Flameproof enclosure Ex d".
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
General data
■ Application
Operating conditions Possible uses
3RV2 motor starter protectors/circuit breakers are suitable for The 3RV motor starter protectors/circuit breakers can be used:
use in any climate. They are intended for use in enclosed rooms • For short-circuit protection
in which no severe operating conditions (such as dust, caustic
vapors, hazardous gases) prevail. When installed in dusty and • For motor protection (also with overload relay function)
damp areas, suitable enclosures must be provided. • For system protection
3RV2 motor starter protectors/circuit breakers can optionally be • For short-circuit protection for starter combinations
fed from the top or from below. • For transformer protection
The permissible ambient temperatures, the maximum switching • As main and EMERGENCY OFF switches
capacities, the tripping currents and other boundary conditions • For operation in IT systems (IT networks)
can be found in the technical specifications and tripping
characteristics. • In hazardous areas (ATEX, IECEx)
• As circuit breakers according to UL 489 (3RV27 and 3RV28)
3RV2 motor starter protectors/circuit breakers are suitable for
operation in IT systems (IT networks). In this case, the different • For fuse monitoring
short-circuit breaking capacity in the IT system must be taken • For distance protection
into account, see page 7/11.
Use of SIRIUS protection devices in conjunction with
Since operational currents, starting currents and current peaks IE3 and IE4 motors
are different even for motors with identical power ratings due to
the inrush current, the motor ratings in the selection tables are Note:
only guide values. The specific rated and startup data of the For the use of 3RV2 motor starter protectors/circuit breakers
motor to be protected are always paramount to the choice of the in conjunction with highly efficient IE3 and IE4 motors, please
most suitable motor starter protector/circuit breaker. This also observe the information on dimensioning and configuring,
applies to motor starter protectors for transformer protection. see Application Manual.
7
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
General data
■ Technical specifications
More information
System Manual for modular system, see Equipment Manual, see
https://support.industry.siemens.com/cs/ww/en/view/60311318 https://support.industry.siemens.com/cs/ww/en/view/60279172
Configuration Manual for load feeders, see Technical specifications, see
https://support.industry.siemens.com/cs/ww/en/view/39714188 https://support.industry.siemens.com/cs/ww/en/ps/16245/td
For UL reports for the individual devices, see
https://support.industry.siemens.com/cs/ww/en/ps/16245/cert
7
Type A kA kA A kA kA A kA kA A kA kA A kA kA A
Size S00
3RV1011 0.16 ... 1 100 100 -- 100 100 -- 100 100 -- 100 100 -- 100 100 --
1.25, 1.6 100 100 -- 100 100 -- 100 100 -- 100 100 -- 2 2 20
2; 2.5 100 100 -- 100 100 -- 100 100 -- 10 10 35 2 2 35
3.2; 4 100 100 -- 100 100 -- 50 12.5 40 3 3 40 2 2 40
5; 6.3 100 100 -- 100 100 -- 50 12.5 50 3 3 50 2 2 40
8 100 100 -- 50 12.5 80 50 12.5 63 3 3 63 2 2 50
10 100 100 -- 50 12.5 80 10 10 63 3 3 63 2 2 50
12 100 100 -- 50 12.5 80 10 10 80 3 3 80 2 2 50
3RV2.11 0.16 ... 1.6 100 100 -- 100 100 -- 100 100 -- 100 100 -- 100 100 --
2; 2.5 100 100 -- 100 100 -- 100 100 -- 100 100 -- 10 10 25
3.2 100 100 -- 100 100 -- 100 100 -- 100 100 -- 10 10 32
4; 5 100 100 -- 100 100 -- 100 100 -- 100 100 -- 6 4 32
6.3 100 100 -- 100 100 -- 100 100 -- 100 100 -- 6 4 50
8 100 100 -- 100 100 -- 50 50 63 42 42 63 6 4 50
10 100 100 -- 100 100 -- 50 50 80 42 42 63 6 4 50
12.5 100 100 -- 100 100 -- 50 50 80 42 42 80 6 4 63
16 100 100 -- 55 30 100 50 12.5 80 10 5 80 4 4 63
3RV1611-0BD10 0.2 100 100 -- 100 100 -- 100 100 -- 100 100 -- 100 100 --
Size S0
3RV2.21 0.16 ... 1.6 100 100 -- 100 100 -- 100 100 -- 100 100 -- 100 100 --
2; 2.5 100 100 -- 100 100 -- 100 100 -- 100 100 -- 10 10 25
3.2 100 100 -- 100 100 -- 100 100 -- 100 100 -- 10 10 32
4; 5 100 100 -- 100 100 -- 100 100 -- 100 100 -- 6 4 32
6.3 100 100 -- 100 100 -- 100 100 -- 100 100 -- 6 4 50
8 100 100 -- 100 100 -- 50 50 63 42 42 63 6 4 50
10 100 100 -- 100 100 -- 50 50 80 42 42 63 6 4 50
12.5 100 100 -- 100 100 -- 50 50 80 42 42 80 6 4 63
16 100 100 -- 55 25 100 50 12.5 80 10 5 80 4 2 63
20 100 100 -- 55 25 125 50 10 80 10 5 80 4 2 63
22; 25 100 100 -- 55 25 125 50 10 100 10 5 80 4 2 63
28; 32 100 100 -- 55 25 125 30 10 125 10 5 100 4 2 100
36; 40 100 100 -- 20 10 125 12 8 125 6 3 100 3 2 100
3)
-- No back-up fuse required, since short-circuit-proof up to 100 kA Back-up fuse only required if short-circuit current at the installation location
1)
10% overvoltage. is > Icu.
4) Alternatively, fuseless limiter combinations for 690 V AC can also be used.
2) 5% overvoltage.
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
General data
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
General data
Short-circuit breaking capacity IcuIT in the IT system (IT network) according to IEC 60947-2
3RV motor starter protectors/circuit breakers are suitable for use If the short-circuit current at the installation location exceeds the
in IT systems. The values of Icu and Ics apply for the 3-pole short motor starter protector/circuit breaker's specified rated short-
circuit. In the case of a double ground fault in different phases circuit breaking capacity, you will need to use a back-up fuse.
at the input and output side of a motor starter protector/ The maximum rated current of this back-up fuse is indicated in
circuit breaker, the special short-circuit breaking capacity the tables. The rated short-circuit breaking capacity then applies
IcuIT applies. The specifications in the table below apply as specified on the fuse.
to 3RV motor starter protectors/circuit breakers.
Type A kA A kA A kA A kA A kA A
Size S00
3RV1011 0.16 ... 0.4 100 -- 100 -- 100 -- 100 -- 100 --
0.5 100 -- 100 -- 100 -- 100 -- 0.5 4
0.63 100 -- 100 -- 6 6 6 6 0.5 6
0.8 100 -- 100 -- 5 6 5 6 0.5 6
1 100 -- 4 10 2 10 2 10 0.5 10
1.25 100 -- 2 20 2 16 2 16 0.5 16
1.6 100 -- 2 20 2 20 2 20 1 16
2 100 -- 2 35 2 25 2 25 1 20
2.5 100 -- 2 35 2 25 2 25 1 25
3.2 100 -- 2 40 2 35 2 35 1 25
4 100 -- 2 40 2 35 2 35 1 35
5 100 -- 2 50 2 35 2 35 1 35
6.3 100 -- 2 50 2 40 2 40 1 40
8 50 80 2 63 2 40 2 40 1 40
7
10 50 80 2 63 2 50 2 50 1 50
12 50 80 2 80 2 50 2 50 1 50
3RV2.11 0.16 ... 0.4 100 -- 100 -- 100 -- 100 -- 100 --
0.5 100 -- 100 -- 100 -- 100 -- 0.5 4
0.63; 0.8 100 -- 100 -- 100 -- 100 -- 0.5 6
1 100 -- 100 -- 2 10 2 10 1.5 10
1.25 100 -- 100 -- 2 16 2 16 1.5 16
1.6 100 -- 100 -- 2 20 2 20 1.5 16
2; 2.5 100 -- 8 25 2 25 2 25 1.5 20
3.2 100 -- 8 32 2 32 2 32 1.5 25
4; 5 100 -- 4 32 1.5 32 1.5 32 1.5 25
6.3; 8 100 -- 4 50 1 40 1 40 1 35
10 100 -- 4 50 1 40 1 40 1 40
12.5 100 -- 4 63 1 50 1 50 1 40
16 55 80 4 63 1 50 1 50 1 40
Size S0
3RV2.21 0.16 ... 0.4 100 -- 100 -- 100 -- 100 -- 100 --
0.5 100 -- 100 -- 100 -- 100 -- 0.5 4
0.63; 0.8 100 -- 100 -- 100 -- 100 -- 0.5 6
1 100 -- 100 -- 2 10 2 10 1.5 10
1.25 100 -- 100 -- 2 16 2 16 1.5 16
1.6 100 -- 100 -- 2 20 2 20 1.5 16
2; 2.5 100 -- 8 25 2 25 2 25 1.5 20
3.2 100 -- 8 32 2 32 2 32 1.5 25
4; 5 100 -- 4 32 1.5 32 1.5 32 1.5 25
6.3; 8 100 -- 4 50 1 40 1 40 1 35
10 100 -- 4 50 1 40 1 40 1 40
12.5 100 -- 4 63 1 50 1 50 1 40
16 55 80 4 63 1 50 1 50 1 40
20 ... 25 55 80 4 63 1 50 1 50 1 50
28; 32 55 80 2 63 1 63 1 63 1 63
36; 40 20 80 2 63 1 63 1 63 1 63
-- No back-up fuse required, since short-circuit-proof up to 100 kA 3) Overvoltage category II applies for applications in IT systems > 600 V.
1) 5% overvoltage. 4) Back-up fuse only required if short-circuit current at installation location is
2)
Without overvoltage. > IcuIT.
5)
Alternatively, fuseless limiter combinations for 690 V AC can also be used.
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
General data
3)
-- No back-up fuse required, since short-circuit-proof up to 100 kA Overvoltage category II applies for applications in IT systems > 600 V.
1) 4)
10% overvoltage. Back-up fuse only required if short-circuit current at installation location is
2)
5% overvoltage. > IcuIT.
5)
Alternatively, fuseless limiter combinations for 690 V AC can also be used.
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
General data
Limiter function with standard devices for 500 V AC and 690 V AC according to IEC 60947-2
The table shows the rated ultimate short-circuit breaking With motor starter protector/circuit breaker assemblies, note the
capacity Icu and the rated service short-circuit breaking clearance to grounded parts and between the motor starter
capacity Ics with an upstream standard motor starter protectors/circuit breakers. Short-circuit-proof wiring between
protector/circuit breaker that fulfills the limiter function the motor starter protectors/circuit breakers must be ensured.
at voltages 500 V AC and 690 V AC. The motor starter protectors/circuit breakers can be mounted
side by side in a modular arrangement.
The short-circuit breaking capacity can be increased
significantly with an upstream standard motor starter
protector/circuit breaker with limiter function. The motor
starter protector/circuit breaker which is connected downstream
must be set to the rated current of the load.
Standard motor starter protectors/circuit breakers Rated current In Up to 500 V AC1)/525 V AC2) Up to 690 V AC1)3)
With limiter
Rated current In Icu Ics Icu Ics
Type Type A kA kA kA kA
Size S00
Size S0: 3RV2011 2 ... 6.3 -- -- 50 25
3RV2321-4EC10 8 100 50 50 25
In = 32 A 10 ... 16 100 50 204) 104)
Size S2: 3RV2011 10 ... 16 -- -- 50 25
3RV2331-4WC10
In = 52 A
Size S0
Size S0: 3RV2021 12 ... 32 100 50 204) 104)
3RV2321-4EC10
7
In = 32 A
Size S2: 3RV2021 16 ... 32 -- -- 50 20
3RV2331-4WC10
In = 52 A
Size S2, with increased switching capacity
Size S2: 3RV2032 14 ... 80 100 50 70 35
3RV2332-4RC10
In = 80 A
Size S3, with increased switching capacity
Size S35): 3RV2042 40 ... 100 100 50 50 25
3RV2342-4MC10
In = 100 A
-- No limiter required 3) Use 3RV29.8-1K phase barriers on the infeed side
1) 10% overvoltage. 4) Infeed to the limiter is always on the side 1L1/3L2/5L3.
2) 5)
5% overvoltage. Infeed to the limiter only on the side 2T1/4T2/6T3. Use 3RV2948-1K phase
barriers on the infeed side.
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
General data
Permissible rated data of devices approved for North America (UL/CSA)
Motor starter protectors of the 3RV2 series are approved These motor starter protectors/circuit breakers can be used as
for UL/CSA, and according to UL 508/UL 60947-4-1 and "Manual Motor Controllers" for "Group Installations", as "Manual
CSA C22.2 No. 14/CSA C22.2 No. 60947-4-1 they can be used Motor Controllers Suitable for Tap Conductor Protection in Group
on their own or as load feeders in combination with a contactor. Installations" and as "Self-Protected Combination Motor
Controllers (Type E)".
10 65 65 65 65 10 10
12 65 65 65 65 10 10
3RV2011, 3RV2111, 3RV2311, 3RV2411 0.16 ... 12.5 65 65 65 65 30 30
16 65 65 65 65 -- --
FLA2) max. 115/120 1 2
16 A, 480 V 200/208 2 3
12.5 A, 600 V 230/240 2 5
460/480 -- 10
575/600 -- 10
3RV1611-0BD10 0.2 65 65 65 65 10 10
Size S0
3RV2021, 3RV2121, 3RV2321, 3RV2421 0.16 ... 12.5 65 65 65 65 30 30
16 ... 25 65 65 65 65 --/(30)4) --/(30)4)
FLA2) max. 115/120 3 5 28, 32 65 65 50 50 -- --
40 A, 480 V 200/208 5 10 36, 40 65 65 12 12 -- --
12.5 A, 600 V 230/240 7 1/2 10
460/480 -- 30
575/600 -- --
Size S2
3RV2031, 3RV2131, 3RV2331, 3RV2431 14 ... 36 65 65 65 65 25 25
40 ... 52 65 65 65 65 22 22
FLA2) max. 115/120 7 1/2 10 59 ... 65 65 65 655) 655) 205) 205)
80 A, 600 V 200/208 15 25 73 ... 80 65 65 655) 655) 205) 205)
230/240 15 30
460/480 -- 60
575/600 -- 75
Size S2, with increased switching capacity
3RV2032, 3RV2332 14 ... 36 100 100 100 100 25 25
40 ... 52 100 100 100 100 22 22
FLA2) max. 115/120 7 1/2 10 59 ... 65 100 100 1005) 1005) 255) 255)
80 A, 600 V 200/208 15 25 73 ... 80 100 100 1005) 1005) 255) 255)
230/240 15 30
460/480 -- 60
575/600 -- 75
Size S3
3RV2041, 3RV2142, 3RV2341, 3RV2042, 3RV2342 40 ... 75 65 65 65 65 30 30
84 ... 100 65 65 65 65 10/306) 10/306)
2)
FLA max. 115/120 7 1/2 15
100 A, 600 V 200/208 15 30
230/240 20 40
460/480 -- 75
575/600 -- 100
4)
-- No approval Values in brackets only apply to 3RV2.23 motor starter protectors.
1) 5)
hp rating = Power rating in horse power (maximum motor rating). With Class J fuse.
2) 6) With Class J fuse 300 A.
FLA = Full Load Amps (motor full load current).
3) Corresponds to "short-circuit breaking capacity" according to UL/CSA.
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
General data
3RV20 motor starter protectors (up to 100 A) as "Manual Motor Controllers Suitable for Tap Conductor Protection in Group Installations"
The application as "Manual Motor Controllers Suitable for The 3RV20 motor starter protectors are approved as "Manual
Tap Conductor Protection in Group Installations" is only Motor Controllers Suitable for Tap Conductor Protection in Group
available for UL. CSA does not recognize this approval! When Installations" under the following file number:
the motor starter protector is used as a "Manual Motor Controller • UL File No. 47705, CCN: NLRV
Suitable for Tap Conductor Protection in Group Installations",
it must always be combined with upstream short-circuit
protection. Approved fuses or circuit breakers according to
UL 489 may be used for this purpose.
These devices must be dimensioned according to the
National Electrical Code.
Motor starter hp rating1) for FLA2) Rated current 240 V AC 480 Y/277 V AC 600 Y/347 V AC
protectors/ max. In UL UL UL
circuit breakers
3)
Ibc Ibc3) Ibc3)
Type V 1-phase 3-phase A kA kA kA
Size S00
3RV1011 0.16 ... 0.8 65 65 10
1 65 65 10
FLA2) max. 8 A, 115 1/3 -- 1.25 65 65 10
480 V 200 3/4 2 2 65 65 10
230 1 2 2.5 65 65 10
460 -- 5 3.2 65 65 10
575/600 -- --
4 65 65 10
5 65 65 10
6.3 65 65 10
8 65 65 10
3RV2011 0.16 ... 12.5 65 65 30
7
16 65 65 --
2)
FLA max. 115/120 1 2
16 A, 480 V 200/208 2 3
12.5 A, 600 V 230/240 2 5
460/480 -- 10
575/600 -- 10
Size S0
3RV2021 0.16 ... 12.5 65 65 30
16 ... 25 65 65 --
FLA2) max. 115/120 2 5 28; 32 50 50 --
32 A, 480 V 200/208 3 10
12.5 A, 600 V 230/240 5 10
460/480 -- 20
575/600 -- --
Size S2
3RV2031 14 ... 36 65 65 25
40 ... 52 65 65 22
FLA2) max. 115/120 7 1/2 10 59 ... 65 65 30 --
80 A, 480 V 200/208 15 25 73 65 20 --
52 A, 600 V 230/240 15 30 80 65 10 --
460/480 -- 60
575/600 -- 75
Size S2, with increased switching capacity
3RV2032 14 ... 36 100 100 25
40 ... 52 100 100 22
FLA2) max. 115/120 7 1/2 10 59 ... 65 100 42 --
80 A, 480 V 200/208 15 25 73 100 30 --
52 A, 600 V 230/240 15 30 80 100 10 --
460/480 -- 60
575/600 -- 75
Size S3
3RV2041, 3RV2042 40 ... 75 65 65 30
84 ... 100 65 65 --
2)
FLA max. 115/120 7 1/2 15
100 A, 480 V 200/208 15 30
75 A, 600 V 230/240 20 40
460/480 -- 75
575/600 -- 75
2)
-- No approval FLA = Full Load Amps (motor full load current).
1) 3)
hp rating = Power rating in horse power (maximum motor rating). Corresponds to "short-circuit breaking capacity" according to UL.
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
General data
3RV20 motor starter protectors (up to 100 A) as "Self-Protected Combination Motor Controllers (Type E)"
UL 508/UL 60947-4-1 approval demands 1-inch clearance omitted when the device is used as a "Self-Protected
and 2-inch creepage distance at line side for "Self-Protected Combination Motor Controller".
Combination Motor Controllers".
The 3RV20 motor starter protectors are approved as
Therefore, 3RV20 motor starter protectors of sizes S00 to S3 are "Self-Protected Combination Motor Controllers" under the
approved according to UL 508/UL 60947-4-1 in combination following file numbers:
with the terminal blocks listed below. • UL File No. E156943, CCN: NKJH
CSA does not require these extended clearance and creepage • CSA Master Contract 165071, Product Class: 3211 08
distances. According to CSA, these terminal blocks can be
Motor starter hp rating1) for FLA2) Rated current Up to 240 V AC Up to 480 Y/277 V AC Up to 600 Y/347 V AC
protectors/ max. In UL CSA UL CSA UL CSA
circuit breakers
3)
Ibc Ibc3) Ibc 3)
Ibc3) Ibc 3)
Ibc3)
Type V 1-phase 3-phase A kA kA kA kA kA kA
Size S00
3RV2011 + 3RV2928-1H4)5) 0.16 ... 12.5 65 65 65 65 30 30
16 65 65 65 65 -- --
FLA2) max. 115/120 1 2
16 A, 480 V; 200/208 2 3
12.5 A, 600 V 230/240 2 5
460/480 -- 10
575/600 -- 10
Size S0
3RV2021 + 3RV2928-1H4)5) 0.16 ... 12.5 65 65 65 65 30 30
16 ... 25 65 65 65 65 -- --
FLA2) max. 115/120 2 5 28; 32 50 50 50 50 -- --
32 A, 480 V 200/208 3 10
7
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
General data
3RV27 and 3RV28 motor starter protectors as "circuit breakers"
These motor starter protectors are approved as circuit breakers 3RV27 and 3RV28 motor starter protectors are approved as
according to UL 489 and CSA 22.2 No. 5. They can be used "circuit breakers" under the following file numbers:
therefore as upstream short-circuit protective devices for • UL File No. E235044, CCN: DIVQ
"Manual Motor Controllers" and "Manual Motor Controllers
Suitable for Tap Conductor Protection in Group Installations". • CSA Master Contract 165071, Product Class: 1432 01
Motor starter Rated current In 240 V AC 480 Y/277 V AC 480 V AC 600 Y/347 V AC 600 V AC
protectors/ UL CSA UL CSA UL CSA UL CSA UL CSA
circuit breakers
Ibc1) Ibc1) Ibc1) Ibc1) Ibc1) Ibc1) Ibc1) Ibc1) Ibc1) Ibc1)
Type A kA kA kA kA kA kA kA kA kA kA
Size S00
3RV2711 0.16 ... 12.5 65 65 65 65 -- -- 10 10 -- --
15 65 65 65 65 -- -- -- -- -- --
3RV2811 0.16 ... 12.5 65 65 65 65 -- -- 10 10 -- --
15 65 65 65 65 -- -- -- -- -- --
Size S0
3RV2721 20; 22 50 50 50 50 -- -- -- -- -- --
3RV2821 20; 22 50 50 50 50 -- -- -- -- -- --
Size S3
3RV2742 10; 15 65 65 65 65 65 65 20 20 20 20
20 ... 30 65 65 65 65 65 65 20 20 -- --
35 ... 60 65 65 65 65 -- -- 20 20 -- --
70 65 65 65 65 -- -- 10 10 -- --
-- No approval 1) Corresponds to "short-circuit breaking capacity" according to UL.
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
General data
General data
Type 3RV2.1. 3RV2.2. 3RV2.3. 3RV2.4. 3RV27, 3RV28
Size S00 S0 S2 S3 S00, S0
H
Dimensions (W x H x D)
• Screw terminals mm 45 x 97 x 92 45 x 97 x 92 55 x 140 x 149 70 x 165 x 169 45 x 144 x 92
D
W
• Spring-loaded terminals mm 45 x 106 x 92 45 x 119 x 92 -- -- --
Standards
• IEC 60947-1 (VDE 0660 Part 100) Yes
• IEC 60947-2 (VDE 0660 Part 101) Yes
• IEC 60947-4-1 (VDE 0660 Part 102) Yes
• UL 508/UL 60947-4-1, Yes (not for 3RV2...-.....-0BA0 and -0DA0 motor starter protectors) --
CSA C22.2 No. 14/CSA C22.2 No. 60947-4-1
• UL 489, CSA C22.2 No. 5 -- Yes
Number of poles 3
Max. rated current In max A 16 40 80 100 22
(= max. rated operational current Ie)
Permissible ambient temperature
• Storage/transport °C -50 ... +80
• Operation In: 0.16 ... 32 A °C -20 (-50)1) ... +70 --
(current reduction above +60 °C)
In: 36 ... 40 A °C -- -20 ... +40 --
(the devices must
not be mounted
side-by-side and
they must not be
assembled with
link modules with
contactors.
A lateral clearance
of 9 mm is
required.)
7
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
General data
H
Dimensions (W x H x D)
• Screw terminals mm 45 x 97 x 92 45 x 97 x 92 55 x 140 x 149 70 x 165 x 169 45 x 144 x 92
D
W
• Spring-loaded terminals mm 45 x 106 x 92 45 x 119 x 92 -- -- --
Degree of protection IP on the front according to IEC 60529 IP20 (screw terminals and spring-loaded terminals)
Touch protection on the front according to IEC 60529 Finger-safe for vertical touching from the front (screw and spring-loaded terminals)
Temperature compensation According to IEC 60947-4-1 °C -20 ... +60
Phase failure sensitivity According to IEC 60947-4-1 Yes (not for 3RV23, 3RV2...-.....-0DA0 motor starter protectors) No
Protection of motors in hazardous environments Yes (only for 3RV20 motor starter protectors, No
not for 3RV20..-.....-0BA0 and -0DA0)
• EC type-examination certificate number according to DMT 02 ATEX F 001 II (2) GD No
European Directive 2014/34/EU (ATEX)
• According to international standard IECEx IECEx BVS14.0102 [Ex] No
Isolating function According to IEC 60947-2 Yes
Main and EMERGENCY STOP According to IEC 60204-1 Yes
switch characteristics (VDE 0113)
(with corresponding accessories)
Protective separation between According to IEC 60947-1
main and auxiliary circuits
required for PELV applications
• Up to 400 V + 10% Yes
• Up to 415 V + 5% (higher voltages on request) Yes
• Up to 690 V (depends on mounted accessories) Yes, see certificate
Permissible mounting position Any, according to IEC 60447 start command "I" right-hand side or top
Mechanical endurance (operating cycles)
• 3RV2 100 000 Up to 52 A: 25 000 100 000
7
50 000, up to
80 A: 20 000
• 3RV2...-.....-0BA0 500 250 --
Electrical endurance (operating cycles)
• 3RV2 100 000 Up to 52 A: 25 000 100 000
50 000, up to
80 A: 20 000
• 3RV2...-.....-0BA0 500 250 --
Max. switching frequency per hour (motor starts) 1/h 15
General data
Type 3RV2742 3RV1611-0BD101) 3RV1011
Size S3 S00 S00
H
Standards
• IEC 60947-1 (VDE 0660 Part 100) Yes
• IEC 60947-2 (VDE 0660 Part 101) Yes
• UL 508/UL 60947-4-1, CSA C22.2 No.14/CSA 60947-4-1 No Yes
• UL 489, CSA C22.2 No. 5 Yes No
Number of poles 3
Max. rated current In max A 70 0.2 12
(= max. rated operational current Ie)
Permissible ambient temperature
• Storage/transport °C -50 ... +80
• Operation °C -20 ... +70 (current reduction above +60 °C)
Permissible rated current at inside temperature of control cabinet
• +60 °C % 100
• +70 °C % 87
Permissible rated current at ambient temperature
of enclosure (applies to motor starter protector/
circuit breaker inside enclosure)
• +35 °C % -- 100
• +60 °C % --
Rated operational voltage Ue
• According to IEC V AC 690 (with molded-plastic enclosure 500 V)
• According to UL/CSA V AC 600
Rated frequency Hz 50/60
Rated insulation voltage Ui V 1 000 690
Rated impulse withstand voltage Uimp kV 8 6
Utilization category
• IEC 60947-2 (motor starter protector/circuit breaker) A
• IEC 60947-4-1 (motor starter) AC-3 AC-3 and AC-3e
1)
"Technical specifications" for 3RV1611 voltage transformer circuit breakers,
see page 7/24.
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
General data
H
Dimensions (W x H x D) mm 70 x 168 x 169 45 x 90 x 70 45 x 90 x 70
D
W
IEC 60947-2
Main and EMERGENCY STOP According to Yes
switch characteristics IEC 60204-1
(with corresponding accessories) (VDE 0113)
Protective separation between According to
main and auxiliary circuits, IEC 60947-1
required for PELV applications
• Up to 400 V + 10% Yes
• Up to 415 V + 5% (higher voltages on request) Yes
Permissible mounting position Any, according to IEC 60447 start command "I" right-hand side or top
Mechanical endurance Operat- 25 000 100 000
ing cy-
cles
Electrical endurance Operat- 25 000 100 000
ing cy-
cles
Max. switching frequency per hour (motor starts) 1/h 15
1)
"Technical specifications" for 3RV1611 voltage transformer circuit breakers,
see page 7/24.
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
General data
7
Minimum load capacity V 5
mA 1
Auxiliary releases
Undervoltage releases Shunt releases
Power consumption
• During pick-up
- AC voltages VA/W 20.2/13
- DC voltages W 20 13 ... 80
• During uninterrupted duty
- AC voltages VA/W 7.2/2.4 --
- DC voltages W 2.1 --
Response voltage
• Tripping V 0.35 ... 0.7 x Us 0.7 ... 1.1 x Us
• Pick-up V 0.85 ... 1.1 x Us --
Opening time maximum ms 20
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
General data
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
General data
7
I201_12740
1) 4)
"Technical specifications" for 3RV16 voltage transformer circuit breakers, If bars larger than 12 mm x 10 mm are connected, a 3RT2946-4EA2 cover
see page 7/24. is needed to maintain the required phase clearance, see page 7/59.
2) If two different conductor cross-sections are connected to one clamping 5) If conductors larger than 25 mm2 are connected, the 3RT2946-4EA2 cover
point, both cross-sections must be in the range specified. is needed to maintain the required phase clearance, see page 7/59.
3)
Cable lug and busbar connection possible after removing the box
terminals. This does not apply for 3RV2742.
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
General data
Voltage transformer circuit breakers
General data
Type 3RV1611-1AG14 3RV1611-1CG14 3RV1611-1DG14
Size S00 S00 S00
H
Dimensions (W x H x D) mm 45 x 90 x 70 45 x 90 x 70 45 x 90 x 70
D
W
Endurance
• Mechanical Oper- 10 000
ating
cycles
• Electrical Oper- 10 000
ating
cycles
Permissible mounting position Any
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
General data
Finely stranded with end sleeve mm2 1 ... 101), 1 ... 61)
Stranded mm2 2.5 ... 10
AWG cables, solid or stranded AWG 14 ... 6
Terminal screw M4
- Rear clamping point:
Solid mm2 1 ... 10
Finely stranded with end sleeve mm2 1 ... 101), 1 ... 161)
Stranded mm2 2.5 ... 10
AWG cables, solid or stranded AWG 16 ... 3
Terminal screw M4
7
1)
The following connections are possible when both clamping points are
connected:
- front 1 to 10 mm2 and rear 1 to 10 mm2,
- front 1 to 6 mm2 and rear 1 to 16 mm2.
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
General data
2
• Solid mm 1 x (0.5 ... 6)
• Finely stranded without/with end sleeve mm2 1 x (0.5 ... 6)
• Stranded mm2 1 x (0.5 ... 6)
• AWG cables, solid or stranded AWG 1 x (20 ... 10)
• Tightening torque Nm 0.6 ... 0.8
• Corresponding opening tool Cross-tip screwdriver PZ2
s and u rated data
Rated operational voltage Ue V 480
Rated insulation voltage Ui V 600
Uninterrupted current, at 40 °C A 25
Short-circuit protection1)
• At 600 V kA 5
• CLASS RK5 fuse A 100
• Circuit breakers A 100
with overload protection according to UL 489
Combination motor controllers type E according to UL 508
at 480 V Type 3RV202
A 22
kA 65
at 600 V Type 3RV202
A 22
kA 10
1)
For more information about short-circuit values, e.g. for protection against
high short-circuit currents, see the UL reports.
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
AC-3e E3 ready IE4 ready IE3/IE4 ready For motor protection
3RV2011-..A10, 3RV2011-..A20,
3RV2011-..A10-0BA0 3RV2011-.AA20-0BA0
Rated Suitable for Setting range Instanta- Short-circuit Screw terminals Spring-loaded
current three-phase for thermal neous breaking capacity terminals
motors1) overload electronic at 400 V AC
with P release release
In Icu Article No. Price Article No. Price
per PU per PU
A kW A A kA
Size S00
0.16 0.04 0.11 ... 0.16 2.1 100 3RV2011-0AA10 3RV2011-0AA20
0.2 0.06 0.14 ... 0.2 2.6 100 3RV2011-0BA10 3RV2011-0BA20
0.25 0.06 0.18 ... 0.25 3.3 100 3RV2011-0CA10 3RV2011-0CA20
7
0.32 0.09 0.22 ... 0.32 4.2 100 3RV2011-0DA10 3RV2011-0DA20
0.4 0.09 0.28 ... 0.4 5.2 100 3RV2011-0EA10 3RV2011-0EA20
0.5 0.12 0.35 ... 0.5 6.5 100 3RV2011-0FA10 3RV2011-0FA20
0.63 0.18 0.45 ... 0.63 8.2 100 3RV2011-0GA10 3RV2011-0GA20
0.8 0.18 0.55 ... 0.8 10 100 3RV2011-0HA10 3RV2011-0HA20
1 0.25 0.7 ... 1 13 100 3RV2011-0JA10 3RV2011-0JA20
1.25 0.37 0.9 ... 1.25 16 100 3RV2011-0KA10 3RV2011-0KA20
1.6 0.55 1.1 ... 1.6 21 100 3RV2011-1AA10 3RV2011-1AA20
2 0.75 1.4 ... 2 26 100 3RV2011-1BA10 3RV2011-1BA20
2.5 0.75 1.8 ... 2.5 33 100 3RV2011-1CA10 3RV2011-1CA20
3.2 1.1 2.2 ... 3.2 42 100 3RV2011-1DA10 3RV2011-1DA20
4 1.5 2.8 ... 4 52 100 3RV2011-1EA10 3RV2011-1EA20
5 1.5 3.5 ... 5 65 100 3RV2011-1FA10 3RV2011-1FA20
6.3 2.2 4.5 ... 6.3 82 100 3RV2011-1GA10 3RV2011-1GA20
8 3 5.5 ... 8 104 100 3RV2011-1HA10 3RV2011-1HA20
10 4 7 ... 10 130 100 3RV2011-1JA10 3RV2011-1JA20
12.5 5.5 9 ... 12.5 163 100 3RV2011-1KA10 3RV2011-1KA20
16 7.5 10 ... 16 208 55 3RV2011-4AA10 3RV2011-4AA20
For special operating conditions down to -50 °C2)3)
1.25 0.37 0.9 ... 1.25 16 100 3RV2011-0KA10-0BA0 --
1.6 0.55 1.1 ... 1.6 21 100 3RV2011-1AA10-0BA0 3RV2011-1AA20-0BA0
2.5 0.75 1.8 ... 2.5 33 100 3RV2011-1CA10-0BA0 --
3.2 1.1 2.2 ... 3.2 42 100 3RV2011-1DA10-0BA0 --
4 1.5 2.8 ... 4 52 100 3RV2011-1EA10-0BA0 --
5 1.5 3.5 ... 5 65 100 3RV2011-1FA10-0BA0 --
6.3 2.2 4.5 ... 6.3 82 100 3RV2011-1GA10-0BA0 --
8 3 5.5 ... 8 104 100 3RV2011-1HA10-0BA0 --
10 4 7 ... 10 130 100 3RV2011-1JA10-0BA0 --
12.5 5.5 9 ... 12.5 163 100 3RV2011-1KA10-0BA0 --
16 7.5 10 ... 16 208 55 3RV2011-4AA10-0BA0 3RV2011-4AA20-0BA0
1)
Guide value for 4-pole standard motors at 50 Hz 400 V AC. The actual Auxiliary switches and other accessories can be ordered
starting and rated data of the motor to be protected must be considered separately (see page 7/48 onwards).
when selecting the units.
2)
The 3RV2011-.....-0BA0 motor starter protectors have a mechanical
endurance of 500 operating cycles.
3) The motor starter protectors do not have UL/CSA approval and are not certified
either according to the European Explosion Protection Directive (ATEX) or
according to the International Explosion Protection Standard (IECEx).
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
For motor protection IE3 ready IE4 ready IE3/IE4 ready
AC-3e
CLASS 10, without auxiliary switches
PU (UNIT, SET, M) = 1
PS* = 1 unit
PG = 41E
Rated Suitable for Setting range Instanta- Short-circuit Screw terminals Spring-loaded
current three-phase for thermal neous breaking capacity terminals
motors1) overload electronic at 400 V AC
with } release release
In Icu Article No. Price Article No. Price
per PU per PU
A kW A A kA
Size S0
0.16 0.04 0.11 ... 0.16 2.1 100 3RV2021-0AA10 --
0.2 0.06 0.14 ... 0.2 2.6 100 3RV2021-0BA10 --
0.25 0.06 0.18 ... 0.25 3.3 100 3RV2021-0CA10 --
0.32 0.09 0.22 ... 0.32 4.2 100 3RV2021-0DA10 --
0.4 0.09 0.28 ... 0.4 5.2 100 3RV2021-0EA10 --
0.5 0.12 0.35 ... 0.5 6.5 100 3RV2021-0FA10 --
7
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
AC-3e E3 ready IE4 ready IE3/IE4 ready For motor protection
CLASS 10, without auxiliary switches
3RV2031-4.A10, 3RV2032-4.A10
3RV2031-4.A10-0BA0
Rated Suitable for Setting range for Instantaneous Short-circuit Screw terminals PU PS* PG
current three-phase thermal overload electronic release breaking (UNIT,
motors1) release capacity at SET, M)
with P 400 V AC
In Icu Article No. Price
per PU
A kW A A kA
Size S2
14 5.5 9.5 ... 14 208 65 3RV2031-4SA10 1 1 unit 41E
17 7.5 12 ... 17 260 65 3RV2031-4TA10 1 1 unit 41E
20 7.5 14 ... 20 260 65 3RV2031-4BA10 1 1 unit 41E
25 11 18 ... 25 325 65 3RV2031-4DA10 1 1 unit 41E
32 15 22 ... 32 416 65 3RV2031-4EA10 1 1 unit 41E
36 18.5 28 ... 36 520 65 3RV2031-4PA10 1 1 unit 41E
7
40 18.5 32 ... 40 585 65 3RV2031-4UA10 1 1 unit 41E
45 22 35 ... 45 650 65 3RV2031-4VA10 1 1 unit 41E
52 22 42 ... 52 741 65 3RV2031-4WA10 1 1 unit 41E
59 30 49 ... 59 845 65 3RV2031-4XA10 1 1 unit 41E
65 30 54 ... 65 845 65 3RV2031-4JA10 1 1 unit 41E
73 37 62 ... 73 949 65 3RV2031-4KA10 1 1 unit 41E
802) 37 70 ... 80 1 040 65 3RV2031-4RA10 1 1 unit 41E
For special operating conditions down to -50 °C3)4)
25 11 18 ... 25 325 65 3RV2031-4DA10-0BA0 1 1 unit 41E
32 15 22 ... 32 416 65 3RV2031-4EA10-0BA0 1 1 unit 41E
65 30 54 ... 65 845 65 3RV2031-4JA10-0BA0 1 1 unit 41E
Size S2, with increased switching capacity
14 5.5 9.5 ... 14 208 100 3RV2032-4SA10 1 1 unit 41E
17 7.5 12 ... 17 260 100 3RV2032-4TA10 1 1 unit 41E
20 7.5 14 ... 20 260 100 3RV2032-4BA10 1 1 unit 41E
25 11 18 ... 25 325 100 3RV2032-4DA10 1 1 unit 41E
32 15 22 ... 32 416 100 3RV2032-4EA10 1 1 unit 41E
36 18.5 28 ... 36 520 100 3RV2032-4PA10 1 1 unit 41E
40 18.5 32 ... 40 585 100 3RV2032-4UA10 1 1 unit 41E
45 22 35 ... 45 650 100 3RV2032-4VA10 1 1 unit 41E
52 22 42 ... 52 741 100 3RV2032-4WA10 1 1 unit 41E
59 30 49 ... 59 845 100 3RV2032-4XA10 1 1 unit 41E
65 30 54 ... 65 845 100 3RV2032-4JA10 1 1 unit 41E
73 37 62 ... 73 949 100 3RV2032-4KA10 1 1 unit 41E
802) 37 70 ... 80 1 040 100 3RV2032-4RA10 1 1 unit 41E
1) Guide value for 4-pole standard motors at 50 Hz 400 V AC. The actual Auxiliary switches and other accessories can be ordered
starting and rated data of the motor to be protected must be considered separately (see page 7/48 onwards).
when selecting the units.
2)
Suitable for use with IE3 and IE4 motors up to a starting current of 720 A.
For higher starting currents we recommend using 3RV2 motor starter
protectors size S3.
3)
The 3RV2031-.....-0BA0 motor starter protectors have a mechanical
endurance of 250 operating cycles.
4) The motor starter protectors do not have UL/CSA approval and are not certified
either according to the European Explosion Protection Directive (ATEX) or
according to the International Explosion Protection Standard (IECEx).
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
For motor protection IE3 ready IE4 ready IE3/IE4 ready
AC-3e
CLASS 10, without auxiliary switches
3RV204.-4.A10
Rated Suitable for Setting range for Instantaneous Short-circuit Screw terminals PU PS* PG
current three-phase thermal overload electronic release breaking (UNIT,
motors1) release capacity at SET, M)
with P 400 V AC
In Icu Article No. Price
per PU
A kW A A kA
Size S3
40 18.5 28 ... 40 520 65 3RV2041-4FA10 1 1 unit 41E
50 22 36 ... 50 650 65 3RV2041-4HA10 1 1 unit 41E
63 30 45 ... 63 819 65 3RV2041-4JA10 1 1 unit 41E
75 37 57 ... 75 975 65 3RV2041-4KA10 1 1 unit 41E
84 45 65 ... 84 1 170 65 3RV2041-4RA10 1 1 unit 41E
7
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
AC-3e E3 ready IE4 ready IE3/IE4 ready For motor protection
CLASS 10, with transverse auxiliary switch (1 NO + 1 NC)
PU (UNIT, SET, M) = 1
PS* = 1 unit
PG = 41E
Rated Suitable for Setting range for Instantaneous Short-circuit Screw terminals Spring-loaded
current three-phase thermal overload electronic breaking terminals
motors1) release release capacity at
with P 400 V AC
In Icu Article No. Price Article No. Price
per PU per PU
A kW A A kA
Size S00
0.16 0.04 0.11 ... 0.16 2.1 100 3RV2011-0AA15 3RV2011-0AA25
0.2 0.06 0.14 ... 0.2 2.6 100 3RV2011-0BA15 3RV2011-0BA25
0.25 0.06 0.18 ... 0.25 3.3 100 3RV2011-0CA15 3RV2011-0CA25
0.32 0.09 0.22 ... 0.32 4.2 100 3RV2011-0DA15 3RV2011-0DA25
0.4 0.09 0.28 ... 0.4 5.2 100 3RV2011-0EA15 3RV2011-0EA25
7
0.5 0.12 0.35 ... 0.5 6.5 100 3RV2011-0FA15 3RV2011-0FA25
0.63 0.18 0.45 ... 0.63 8.2 100 3RV2011-0GA15 3RV2011-0GA25
0.8 0.18 0.55 ... 0.8 10 100 3RV2011-0HA15 3RV2011-0HA25
1 0.25 0.7 ... 1 13 100 3RV2011-0JA15 3RV2011-0JA25
1.25 0.37 0.9 ... 1.25 16 100 3RV2011-0KA15 3RV2011-0KA25
1.6 0.55 1.1 ... 1.6 21 100 3RV2011-1AA15 3RV2011-1AA25
2 0.75 1.4 ... 2 26 100 3RV2011-1BA15 3RV2011-1BA25
2.5 0.75 1.8 ... 2.5 33 100 3RV2011-1CA15 3RV2011-1CA25
3.2 1.1 2.2 ... 3.2 42 100 3RV2011-1DA15 3RV2011-1DA25
4 1.5 2.8 ... 4 52 100 3RV2011-1EA15 3RV2011-1EA25
5 1.5 3.5 ... 5 65 100 3RV2011-1FA15 3RV2011-1FA25
6.3 2.2 4.5 ... 6.3 82 100 3RV2011-1GA15 3RV2011-1GA25
8 3 5.5 ... 8 104 100 3RV2011-1HA15 3RV2011-1HA25
10 4 7 ... 10 130 100 3RV2011-1JA15 3RV2011-1JA25
12.5 5.5 9 ... 12.5 163 100 3RV2011-1KA15 3RV2011-1KA25
16 7.5 10 ... 16 208 55 3RV2011-4AA15 3RV2011-4AA25
For special operating conditions down to -50 °C2)3)
2 0.06 1.4 ... 2 2.6 100 3RV2011-1BA15-0BA0 --
2.5 0.75 1.8 ... 2.5 33 100 3RV2011-1CA15-0BA0 --
4 1.5 2.8 ... 4 52 100 3RV2011-1EA15-0BA0 3RV2011-1EA25-0BA0
5 1.5 3.5 ... 5 65 100 3RV2011-1FA15-0BA0 --
6.3 2.2 4.5 ... 6.3 82 100 3RV2011-1GA15-0BA0 --
8 3 5.5 ... 8 104 100 3RV2011-1HA15-0BA0 --
12.5 5.5 9 ... 12.5 163 100 3RV2011-1KA15-0BA0 --
16 7.5 10 ... 16 208 55 3RV2011-4AA15-0BA0 --
Size S0
16 7.5 10 ... 16 208 55 3RV2021-4AA15 3RV2021-4AA25
20 7.5 13 ... 20 260 55 3RV2021-4BA15 3RV2021-4BA25
22 11 16 ... 22 286 55 3RV2021-4CA15 3RV2021-4CA25
25 11 18 ... 25 325 55 3RV2021-4DA15 3RV2021-4DA25
28 15 23 ... 28 364 55 3RV2021-4NA15 3RV2021-4NA25
324) 15 27 ... 32 400 55 3RV2021-4EA15 3RV2021-4EA25
365) 18.5 30 ... 36 432 20 3RV2021-4PA15 --
405) 18.5 34 ... 40 480 20 3RV2021-4FA15 --
For special operating conditions down to -50 °C2)3)
20 7.5 13 ... 20 260 55 3RV2021-4BA15-0BA0 --
324) 15 27 ... 32 400 55 3RV2021-4EA15-0BA0 --
1) Guide value for 4-pole standard motors at 50 Hz 400 V AC. The actual 5) The devices must not be mounted side-by-side and they must not be
starting and rated data of the motor to be protected must be considered assembled with link modules with contactors. A lateral clearance of 9 mm
when selecting the units. is required. For use with IE3 and IE4 motors we recommend using 3RV2
2)
The 3RV20.1-.....-0BA0 motor starter protectors in sizes S00 and S0 have motor starter protectors size S2.
a mechanical endurance of 500 operating cycles. Auxiliary switches and other accessories can be ordered
3)
The motor starter protectors do not have UL/CSA approval and are not certified separately (see page 7/48 onwards).
either according to the European Explosion Protection Directive (ATEX) or
according to the International Explosion Protection Standard (IECEx).
4) Suitable for use with IE3 and IE4 motors up to a starting current of 256 A.
For higher starting currents we recommend using 3RV2 motor starter
protectors size S2.
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
For motor protection IE3 ready IE4 ready IE3/IE4 ready
AC-3e
CLASS 10, with transverse auxiliary switch (1 NO + 1 NC)
Rated Suitable for Setting range for Instantaneous Short-circuit Screw terminals PU PS* PG
current three-phase thermal overload electronic release breaking (UNIT,
motors1) release capacity at SET, M)
with P 400 V AC
In Icu Article No. Price
per PU
A kW A A kA
Size S2
14 5.5 9.5 ... 14 208 65 3RV2031-4SA15 1 1 unit 41E
17 7.5 12 ... 17 260 65 3RV2031-4TA15 1 1 unit 41E
20 7.5 14 ... 20 260 65 3RV2031-4BA15 1 1 unit 41E
25 11 18 ... 25 325 65 3RV2031-4DA15 1 1 unit 41E
7
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
AC-3e E3 ready IE4 ready IE3/IE4 ready For motor protection
CLASS 20, without auxiliary switches
Rated Suitable for Setting range for Instantaneous Short-circuit Screw terminals PU PS* PG
current three-phase thermal overload electronic release breaking (UNIT,
motors1) release capacity at SET, M)
with P 400 V AC
In Icu Article No. Price
per PU
A kW A A kA
Size S2
14 5.5 9.5 ... 14 208 65 3RV2031-4SB10 1 1 unit 41E
17 7.5 12 ... 17 260 65 3RV2031-4TB10 1 1 unit 41E
20 7.5 14 ... 20 260 65 3RV2031-4BB10 1 1 unit 41E
25 11 18 ... 25 325 65 3RV2031-4DB10 1 1 unit 41E
7
32 15 22 ... 32 416 65 3RV2031-4EB10 1 1 unit 41E
36 18.5 28 ... 36 520 65 3RV2031-4PB10 1 1 unit 41E
40 18.5 32 ... 40 585 65 3RV2031-4UB10 1 1 unit 41E
45 22 35 ... 45 650 65 3RV2031-4VB10 1 1 unit 41E
52 22 42 ... 52 741 65 3RV2031-4WB10 1 1 unit 41E
59 30 49 ... 59 845 65 3RV2031-4XB10 1 1 unit 41E
65 30 54 ... 65 845 65 3RV2031-4JB10 1 1 unit 41E
For special operating conditions down to -50 °C2)3)
32 15 22 ... 32 416 65 3RV2031-4EB10-0BA0 1 1 unit 41E
36 18.5 28 ... 36 520 65 3RV2031-4PB10-0BA0 1 1 unit 41E
40 18.5 32 ... 40 585 65 3RV2031-4UB10-0BA0 1 1 unit 41E
Size S3, with increased switching capacity
40 18.5 28 ... 40 520 100 3RV2042-4FB10 1 1 unit 41E
50 22 36 ... 50 650 100 3RV2042-4HB10 1 1 unit 41E
63 30 45 ... 63 819 100 3RV2042-4JB10 1 1 unit 41E
75 37 57 ... 75 975 100 3RV2042-4KB10 1 1 unit 41E
84 45 65 ... 84 1 170 100 3RV2042-4RB10 1 1 unit 41E
93 45 75 ... 93 1 300 100 3RV2042-4YB10 1 1 unit 41E
1004) 45, 55 80 ... 100 1 300 100 3RV2042-4MB10 1 1 unit 41E
1) Guide value for 4-pole standard motors at 50 Hz 400 V AC. The actual Auxiliary switches and other accessories can be ordered
starting and rated data of the motor to be protected must be considered separately (see page 7/48 onwards).
when selecting the units.
2)
The 3RV2031-.....-0BA0 motor starter protectors have a mechanical
endurance of 250 operating cycles.
3)
The motor starter protectors do not have UL/CSA approval and are not certified
either according to the European Explosion Protection Directive (ATEX) or
according to the International Explosion Protection Standard (IECEx).
4) Suitable for use with IE3 and IE4 motors up to a starting current of 780 A.
For higher starting currents we recommend using 3VA circuit breakers
(see Catalog LV 10).
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
For motor protection IE3 ready IE4 ready IE3/IE4 ready
AC-3e
CLASS 20, with transverse auxiliary switch (1 NO + 1 NC)
3RV2031-4.B15, 3RV2031-4.B15,
14 to 45 A 52 to 65 A
Rated Suitable for Setting range for Instantaneous Short-circuit Screw terminals PU PS* PG
current three-phase thermal overload electronic release breaking capacity (UNIT,
motors1) release at 400 V AC SET, M)
with P
In Icu Article No. Price
per PU
A kW A A kA
Size S2
14 5.5 9.5 ... 14 208 65 3RV2031-4SB15 1 1 unit 41E
17 7.5 12 ... 17 260 65 3RV2031-4TB15 1 1 unit 41E
20 7.5 14 ... 20 260 65 3RV2031-4BB15 1 1 unit 41E
25 11 18 ... 25 325 65 3RV2031-4DB15 1 1 unit 41E
32 15 22 ... 32 416 65 3RV2031-4EB15 1 1 unit 41E
36 18.5 28 ... 36 520 65 3RV2031-4PB15 1 1 unit 41E
7
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
AC-3e E3 ready IE4 ready IE3/IE4 ready For motor protection with overload relay function
3RV2111-..A10 3RV2121-4.A10
Rated Suitable for Setting range for Instantaneous Short-circuit Screw terminals PU PS* PG
current three-phase thermal overload electronic release breaking capacity (UNIT,
motors1) release at 400 V AC SET, M)
with P
In Icu Article No. Price
per PU
A kW A A kA
Size S002)
0.16 0.04 0.11 ... 0.16 2.1 100 3RV2111-0AA10 1 1 unit 41E
0.2 0.06 0.14 ... 0.2 2.6 100 3RV2111-0BA10 1 1 unit 41E
0.25 0.06 0.18 ... 0.25 3.3 100 3RV2111-0CA10 1 1 unit 41E
0.32 0.09 0.22 ... 0.32 4.2 100 3RV2111-0DA10 1 1 unit 41E
0.4 0.09 0.28 ... 0.4 5.2 100 3RV2111-0EA10 1 1 unit 41E
0.5 0.12 0.35 ... 0.5 6.5 100 3RV2111-0FA10 1 1 unit 41E
0.63 0.18 0.45 ... 0.63 8.2 100 3RV2111-0GA10 1 1 unit 41E
0.8 0.18 0.55 ... 0.8 10 100 3RV2111-0HA10 1 1 unit 41E
7
1 0.25 0.7 ... 1 13 100 3RV2111-0JA10 1 1 unit 41E
1.25 0.37 0.9 ... 1.25 16 100 3RV2111-0KA10 1 1 unit 41E
1.6 0.55 1.1 ... 1.6 21 100 3RV2111-1AA10 1 1 unit 41E
2 0.75 1.4 ... 2 26 100 3RV2111-1BA10 1 1 unit 41E
2.5 0.75 1.8 ... 2.5 33 100 3RV2111-1CA10 1 1 unit 41E
3.2 1.1 2.2 ... 3.2 42 100 3RV2111-1DA10 1 1 unit 41E
4 1.5 2.8 ... 4 52 100 3RV2111-1EA10 1 1 unit 41E
5 1.5 3.5 ... 5 65 100 3RV2111-1FA10 1 1 unit 41E
6.3 2.2 4.5 ... 6.3 82 100 3RV2111-1GA10 1 1 unit 41E
8 3 5.5 ... 8 104 100 3RV2111-1HA10 1 1 unit 41E
10 4 7 ... 10 130 100 3RV2111-1JA10 1 1 unit 41E
12.5 5.5 9 ... 12.5 163 100 3RV2111-1KA10 1 1 unit 41E
16 7.5 10 ... 16 208 55 3RV2111-4AA10 1 1 unit 41E
Size S02)
16 7.5 10 ... 16 208 55 3RV2121-4AA10 1 1 unit 41E
20 7.5 13 ... 20 260 55 3RV2121-4BA10 1 1 unit 41E
22 11 16 ... 22 286 55 3RV2121-4CA10 1 1 unit 41E
25 11 18 ... 25 325 55 3RV2121-4DA10 1 1 unit 41E
28 15 23 ... 28 364 55 3RV2121-4NA10 1 1 unit 41E
323) 15 27 ... 32 400 55 3RV2121-4EA10 1 1 unit 41E
1)
Guide value for 4-pole standard motors at 50 Hz 400 V AC. The actual Auxiliary switches and other accessories can be ordered
starting and rated data of the motor to be protected must be considered separately (see page 7/48 onwards).
when selecting the units.
2) Accessories for mounting on the right and 3RV1915 3-phase busbars
cannot be used.
3)
Suitable for use with IE3 and IE4 motors up to a starting current of 256 A.
For higher starting currents we recommend using 3RV2 motor starter
protectors size S2.
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
For motor protection with overload relay function IE3 ready IE4 ready IE3/IE4 ready
AC-3e
CLASS 10, with overload relay function (Automatic RESET), without auxiliary switches
3RV2131-4.A10 3RV2142-4.A10
Rated Suitable for Setting range for Instantaneous Short-circuit Screw terminals PU PS* PG
current three-phase thermal overload electronic release breaking capacity (UNIT,
motors1) release at 400 V AC SET, M)
with P
In Icu Article No. Price
per PU
A kW A A kA
Size S22)
14 5.5 9.5 ... 14 208 65 3RV2131-4SA10 1 1 unit 41E
17 7.5 12 ... 17 260 65 3RV2131-4TA10 1 1 unit 41E
20 7.5 14 ... 20 260 65 3RV2131-4BA10 1 1 unit 41E
25 11 18 ... 25 325 65 3RV2131-4DA10 1 1 unit 41E
32 15 22 ... 32 416 65 3RV2131-4EA10 1 1 unit 41E
7
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
AC-3e E3 ready IE4 ready IE3/IE4 ready For starter combinations
3RV2311-..C10 3RV2311-..C20,
3RV2311-4AC20-0BA0
Rated Suitable for Thermal overload Instantaneous Short-circuit Screw terminals Spring-loaded
current three-phase release2) electronic breaking terminals
motors1) release capacity at
with P 400 V AC
In Icu Article No. Price Article No. Price
per PU per PU
A kW A A kA
Size S00
0.16 0.04 Without 2.1 100 3RV2311-0AC10 3RV2311-0AC20
0.2 0.06 Without 2.6 100 3RV2311-0BC10 3RV2311-0BC20
7
0.25 0.06 Without 3.3 100 3RV2311-0CC10 3RV2311-0CC20
0.32 0.09 Without 4.2 100 3RV2311-0DC10 3RV2311-0DC20
0.4 0.09 Without 5.2 100 3RV2311-0EC10 3RV2311-0EC20
0.5 0.12 Without 6.5 100 3RV2311-0FC10 3RV2311-0FC20
0.63 0.18 Without 8.2 100 3RV2311-0GC10 3RV2311-0GC20
0.8 0.18 Without 10 100 3RV2311-0HC10 3RV2311-0HC20
1 0.25 Without 13 100 3RV2311-0JC10 3RV2311-0JC20
1.25 0.37 Without 16 100 3RV2311-0KC10 3RV2311-0KC20
1.6 0.55 Without 21 100 3RV2311-1AC10 3RV2311-1AC20
2 0.75 Without 26 100 3RV2311-1BC10 3RV2311-1BC20
2.5 0.75 Without 33 100 3RV2311-1CC10 3RV2311-1CC20
3.2 1.1 Without 42 100 3RV2311-1DC10 3RV2311-1DC20
4 1.5 Without 52 100 3RV2311-1EC10 3RV2311-1EC20
5 1.5 Without 65 100 3RV2311-1FC10 3RV2311-1FC20
6.3 2.2 Without 82 100 3RV2311-1GC10 3RV2311-1GC20
8 3 Without 104 100 3RV2311-1HC10 3RV2311-1HC20
10 4 Without 130 100 3RV2311-1JC10 3RV2311-1JC20
12.5 5.5 Without 163 100 3RV2311-1KC10 3RV2311-1KC20
16 7.5 Without 208 55 3RV2311-4AC10 3RV2311-4AC20
For special operating conditions down to -50 °C3)4)
16 7.5 Without 208 55 -- 3RV2311-4AC20-0BA0
1)
Guide value for 4-pole standard motors at 50 Hz 400 V AC. The actual Auxiliary switches and other accessories can be ordered
starting and rated data of the motor to be protected must be considered separately (see page 7/48 onwards).
when selecting the units.
2)
For overload protection of the motors, appropriate overload relays must
be used.
3) The 3RV2311-.....-0BA0 motor starter protectors have a mechanical
endurance of 500 operating cycles.
4)
The motor starter protectors do not have UL/CSA approval and are not certified
either according to the European Explosion Protection Directive (ATEX) or
according to the International Explosion Protection Standard (IECEx).
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
For starter combinations IE3 ready IE4 ready IE3/IE4 ready
AC-3e
Without auxiliary switches
PU (UNIT, SET, M) = 1
PS* = 1 unit
PG = 41E
3RV2321-..C10 3RV2321-..C20,
3RV2321-4AC20-0BA0
Rated Suitable for Thermal overload Instantaneous Short-circuit Screw terminals Spring-loaded
current three-phase release2) electronic breaking terminals
motors1) release capacity at
with P 400 V AC
In Icu Article No. Price Article No. Price
per PU per PU
A kW A A kA
Size S0
1.6 0.55 Without 21 100 3RV2321-1AC10 3RV2321-1AC20
2 0.75 Without 26 100 3RV2321-1BC10 3RV2321-1BC20
2.5 0.75 Without 33 100 3RV2321-1CC10 3RV2321-1CC20
3.2 1.1 Without 42 100 3RV2321-1DC10 3RV2321-1DC20
4 1.5 Without 52 100 3RV2321-1EC10 3RV2321-1EC20
7
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
AC-3e E3 ready IE4 ready IE3/IE4 ready For starter combinations
Without auxiliary switches
Rated Suitable for three- Thermal overload Instantaneous Short-circuit Screw terminals PU PS* PG
current phase motors1) release2) electronic release breaking capacity (UNIT,
with P at 400 V AC SET, M)
In Icu Article No. Price
per PU
A kW A A kA
Size S2
14 5.5 Without 208 65 3RV2331-4SC10 1 1 unit 41E
17 7.5 Without 260 65 3RV2331-4TC10 1 1 unit 41E
20 7.5 Without 260 65 3RV2331-4BC10 1 1 unit 41E
25 11 Without 325 65 3RV2331-4DC10 1 1 unit 41E
7
32 15 Without 416 65 3RV2331-4EC10 1 1 unit 41E
36 18.5 Without 520 65 3RV2331-4PC10 1 1 unit 41E
40 18.5 Without 585 65 3RV2331-4UC10 1 1 unit 41E
45 22 Without 650 65 3RV2331-4VC10 1 1 unit 41E
52 22 Without 741 65 3RV2331-4WC10 1 1 unit 41E
59 30 Without 845 65 3RV2331-4XC10 1 1 unit 41E
65 30 Without 845 65 3RV2331-4JC10 1 1 unit 41E
73 37 Without 949 65 3RV2331-4KC10 1 1 unit 41E
803) 37 Without 1040 65 3RV2331-4RC10 1 1 unit 41E
Size S2, with increased switching capacity
14 5.5 Without 208 100 3RV2332-4SC10 1 1 unit 41E
17 7.5 Without 260 100 3RV2332-4TC10 1 1 unit 41E
20 7.5 Without 260 100 3RV2332-4BC10 1 1 unit 41E
25 11 Without 325 100 3RV2332-4DC10 1 1 unit 41E
32 15 Without 416 100 3RV2332-4EC10 1 1 unit 41E
36 18.5 Without 520 100 3RV2332-4PC10 1 1 unit 41E
40 18.5 Without 585 100 3RV2332-4UC10 1 1 unit 41E
45 22 Without 650 100 3RV2332-4VC10 1 1 unit 41E
52 22 Without 741 100 3RV2332-4WC10 1 1 unit 41E
59 30 Without 845 100 3RV2332-4XC10 1 1 unit 41E
65 30 Without 845 100 3RV2332-4JC10 1 1 unit 41E
73 37 Without 949 100 3RV2332-4KC10 1 1 unit 41E
803) 37 Without 1 040 100 3RV2332-4RC10 1 1 unit 41E
Size S3
40 18.5 Without 520 65 3RV2341-4FC10 1 1 unit 41E
50 22 Without 650 65 3RV2341-4HC10 1 1 unit 41E
63 30 Without 819 65 3RV2341-4JC10 1 1 unit 41E
75 37 Without 975 65 3RV2341-4KC10 1 1 unit 41E
84 45 Without 1 170 65 3RV2341-4RC10 1 1 unit 41E
93 45 Without 1 300 65 3RV2341-4YC10 1 1 unit 41E
1004) 45, 55 Without 1 300 65 3RV2341-4MC10 1 1 unit 41E
Size S3, with increased switching capacity
40 18.5 Without 520 100 3RV2342-4FC10 1 1 unit 41E
50 22 Without 650 100 3RV2342-4HC10 1 1 unit 41E
63 30 Without 819 100 3RV2342-4JC10 1 1 unit 41E
75 37 Without 975 100 3RV2342-4KC10 1 1 unit 41E
84 45 Without 1 170 100 3RV2342-4RC10 1 1 unit 41E
93 45 Without 1 300 100 3RV2342-4YC10 1 1 unit 41E
1004) 45, 55 Without 1 300 100 3RV2342-4MC10 1 1 unit 41E
1) Guide value for 4-pole standard motors at 50 Hz 400 V AC. The actual 4) Suitable for use with IE3 and IE4 motors up to a starting current of 780 A.
starting and rated data of the motor to be protected must be considered For higher starting currents we recommend using 3VA circuit breakers
when selecting the units. (see Catalog LV 10).
2)
For overload protection of the motors, appropriate overload relays must
be used.
Auxiliary switches and other accessories can be ordered
3)
Suitable for use with IE3 and IE4 motors up to a starting current of 720 A.
separately (see page 7/48 onwards).
For higher starting currents we recommend using 3RV2 motor starter
protectors size S3.
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
For transformer protection
3RV2411-..A10, 3RV2411-..A20
3RV2411-..A10-0BA0
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
For transformer protection
CLASS 10, without auxiliary switches
Motor starter protectors for the protection of transformers with high inrush current
PU (UNIT, SET, M) = 1
PS* = 1 unit
PG = 41E
3RV2421-..A10, 3RV2421-4.A20;
3RV2421-4BA10-0BA0, 3RV2421-4.A20-0DA0,
32 A 16 and 20 A
7
0.32 0.22 ... 0.32 6.5 100 3RV2421-0DA10 --
0.4 0.28 ... 0.4 8.2 100 3RV2421-0EA10 --
0.5 0.35 ... 0.5 10 100 3RV2421-0FA10 --
0.63 0.45 ... 0.63 13 100 3RV2421-0GA10 --
0.8 0.55 ... 0.8 16 100 3RV2421-0HA10 --
1 0.7 ... 1 21 100 3RV2421-0JA10 --
1.25 0.9 ... 1.25 26 100 3RV2421-0KA10 --
1.6 1.1 ... 1.6 33 100 3RV2421-1AA10 --
2 1.4 ... 2 42 100 3RV2421-1BA10 --
2.5 1.8 ... 2.5 52 100 3RV2421-1CA10 --
3.2 2.2 ... 3.2 65 100 3RV2421-1DA10 --
4 2.8 ... 4 82 100 3RV2421-1EA10 --
5 3.5 ... 5 104 100 3RV2421-1FA10 --
6.3 4.5 ... 6.3 130 100 3RV2421-1GA10 --
8 5.5 ... 8 163 100 3RV2421-1HA10 --
10 7 ... 10 208 100 3RV2421-1JA10 --
12.5 9 ... 12.5 260 100 3RV2421-1KA10 --
16 10 ... 16 286 55 3RV2421-4AA10 3RV2421-4AA20
20 13 ... 20 325 55 3RV2421-4BA10 3RV2421-4BA20
22 16 ... 22 364 55 3RV2421-4CA10 3RV2421-4CA20
25 18 ... 25 400 55 3RV2421-4DA10 3RV2421-4DA20
Without phase asymmetry/failure detection for 1-, 2- and
3-phase loads1)
16 10 ... 16 286 55 -- 3RV2421-4AA20-0DA0
20 13 ... 20 325 55 -- 3RV2421-4BA20-0DA0
For special operating conditions down to -50 °C2)3)
20 13 ... 20 325 55 3RV2421-4BA10-0BA0 --
1) The motor starter protectors do not have UL/CSA approval and are not certified Auxiliary switches and other accessories can be ordered
either according to the European Explosion Protection Directive (ATEX) or separately (see page 7/48 onwards).
according to the International Explosion Protection Standard (IECEx).
2)
The motor starter protectors have IEC approval, but not UL/CSA approval.
3)
The 3RV2431-.....-0BA0 motor starter protectors have a mechanical
endurance of 250 operating cycles.
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
For transformer protection
CLASS 10, without auxiliary switches
Motor starter protectors for the protection of transformers with high inrush current
PU (UNIT, SET, M) = 1
PS* = 1 unit
PG = 41E
3RV2431-4.A10, 3RV2431-4.A10,
14 to 40 A; 45 to 65 A
3RV2431-4EA10-0BA0,
32 A
Size S2
14 9.5 ... 14 328 65 3RV2431-4SA10 --
17 12 ... 17 410 65 3RV2431-4TA10 --
20 14 ... 20 410 65 3RV2431-4BA10 --
25 18 ... 25 512 65 3RV2431-4DA10 --
32 22 ... 32 656 65 3RV2431-4EA10 --
36 28 ... 36 820 65 3RV2431-4PA10 --
40 32 ... 40 820 65 3RV2431-4UA10 --
45 35 ... 45 922 65 3RV2431-4VA10 --
52 42 ... 52 1 025 65 3RV2431-4WA10 --
59 49 ... 59 1 040 65 3RV2431-4XA10 --
65 54 ... 65 1 040 65 3RV2431-4JA10 --
For special operating conditions down to -50 °C1)2)
32 22 ... 32 656 65 3RV2431-4EA10-0BA0 --
1) The motor starter protectors do not have UL/CSA approval and are not certified
either according to the European Explosion Protection Directive (ATEX) or
according to the International Explosion Protection Standard (IECEx).
2)
The 3RV2431-.....-0BA0 motor starter protectors have a mechanical
endurance of 250 operating cycles.
Auxiliary switches and other accessories can be ordered
separately (see page 7/48 onwards).
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
For transformer protection
CLASS 10, with transverse auxiliary switch (1 NO + 1 NC)
Motor starter protectors for the protection of transformers with high inrush current
3RV2411-..A15 3RV2421-4.A15
7
1.25 0.9 ... 1.25 26 100 3RV2411-0KA15 1 1 unit 41E
1.6 1.1 ... 1.6 33 100 3RV2411-1AA15 1 1 unit 41E
2 1.4 ... 2 42 100 3RV2411-1BA15 1 1 unit 41E
2.5 1.8 ... 2.5 52 100 3RV2411-1CA15 1 1 unit 41E
3.2 2.2 ... 3.2 65 100 3RV2411-1DA15 1 1 unit 41E
4 2.8 ... 4 82 100 3RV2411-1EA15 1 1 unit 41E
5 3.5 ... 5 104 100 3RV2411-1FA15 1 1 unit 41E
6.3 4.5 ... 6.3 130 100 3RV2411-1GA15 1 1 unit 41E
8 5.5 ... 8 163 100 3RV2411-1HA15 1 1 unit 41E
10 7 ... 10 208 100 3RV2411-1JA15 1 1 unit 41E
12.5 9 ... 12.5 260 100 3RV2411-1KA15 1 1 unit 41E
16 10 ... 16 286 55 3RV2411-4AA15 1 1 unit 41E
Size S0
16 10 ... 16 286 55 3RV2421-4AA15 1 1 unit 41E
20 13 ... 20 325 55 3RV2421-4BA15 1 1 unit 41E
22 16 ... 22 364 55 3RV2421-4CA15 1 1 unit 41E
25 18 ... 25 400 55 3RV2421-4DA15 1 1 unit 41E
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
For system protection
Rated Suitable for Setting range Instanta- Short-circuit Screw terminals Spring-loaded
current three-phase for thermal neous breaking capacity terminals
motors1) overload electronic at 400 V AC
with } release release
7
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
For system protection according to UL 489/CSA C22.2 No. 5
7
0.4 0.4 5.2 65 -- 3RV2711-0ED10 1 1 unit 41E
0.5 0.5 6.5 65 -- 3RV2711-0FD10 1 1 unit 41E
0.63 0.63 8.2 65 -- 3RV2711-0GD10 1 1 unit 41E
0.8 0.8 10 65 -- 3RV2711-0HD10 1 1 unit 41E
1 1 13 65 -- 3RV2711-0JD10 1 1 unit 41E
1.25 1.25 16 65 -- 3RV2711-0KD10 1 1 unit 41E
1.6 1.6 21 65 -- 3RV2711-1AD10 1 1 unit 41E
2 2 26 65 -- 3RV2711-1BD10 1 1 unit 41E
2.5 2.5 33 65 -- 3RV2711-1CD10 1 1 unit 41E
3.2 3.2 42 65 -- 3RV2711-1DD10 1 1 unit 41E
4 4 52 65 -- 3RV2711-1ED10 1 1 unit 41E
5 5 65 65 -- 3RV2711-1FD10 1 1 unit 41E
6.3 6.3 82 65 -- 3RV2711-1GD10 1 1 unit 41E
8 8 104 65 -- 3RV2711-1HD10 1 1 unit 41E
10 10 130 65 -- 3RV2711-1JD10 1 1 unit 41E
12.5 12.5 163 65 -- 3RV2711-1KD10 1 1 unit 41E
15 15 208 65 -- 3RV2711-4AD10 1 1 unit 41E
Size S0
20 20 260 50 -- 3RV2721-4BD10 1 1 unit 41E
22 22 286 50 -- 3RV2721-4CD10 1 1 unit 41E
Size S33)
10 10 150 65 65 3RV2742-5AD10 1 1 unit 41E
15 15 225 65 65 3RV2742-5BD10 1 1 unit 41E
20 20 260 65 65 3RV2742-5CD10 1 1 unit 41E
25 25 325 65 65 3RV2742-5DD10 1 1 unit 41E
30 30 390 65 65 3RV2742-5ED10 1 1 unit 41E
35 35 455 65 -- 3RV2742-5FD10 1 1 unit 41E
40 40 520 65 -- 3RV2742-5GD10 1 1 unit 41E
45 45 585 65 -- 3RV2742-5HD10 1 1 unit 41E
50 50 650 65 -- 3RV2742-5JD10 1 1 unit 41E
60 60 780 65 -- 3RV2742-5LD10 1 1 unit 41E
70 70 910 65 -- 3RV2742-5QD10 1 1 unit 41E
1)
Rated value 100% according to UL 489 and IEC 60947-2 Lateral and transverse auxiliary switches can be ordered
("100% rated breaker"). separately (see from page 7/48 onwards).
2) Values for 600 Y/347 V AC, see page 7/17.
3)
Transverse auxiliary switches cannot be used for 3RV2742.
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
For transformer protection according to UL 489/CSA C22.2 No. 5
3RV2811-..D10 3RV2821-4.D10
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
Accessories > Mountable accessories
■ Overview
Mounting location and function
The 3RV2 motor starter protectors/circuit breakers have three These components are easily fitted to the switches without the
main contact elements. In order to achieve maximum flexibility, use of any tools according to requirements.
auxiliary switches, signaling switches, auxiliary releases and
isolator modules can be supplied separately. Overview graphic, see page 7/6.
Front side Transverse auxiliary An auxiliary switch can be inserted transversely on the front. The overall
Notes: switches, solid-state width of the motor starter protectors/circuit breakers remains unchanged.
compatible transverse
• A maximum of four auxiliary contacts with auxiliary switches
auxiliary switches can be mounted on each
motor starter protector/circuit breaker. 1 NO + 1 NC
or
• Transverse auxiliary switches cannot be used 2 NO
for circuit breaker 3RV2742 (size S3). or
1 CO
Left-hand side Lateral auxiliary switches One of the three lateral auxiliary switches can be mounted on the left side
Notes: (two contacts) per motor starter protector/circuit breaker. The contacts of the auxiliary
1 NO + 1 NC switch close and open together with the main contacts of the motor starter
• A maximum of four auxiliary contacts with protector/circuit breaker.
auxiliary switches can be mounted on each or
motor starter protector/circuit breaker. 2 NO The width of the lateral auxiliary switch with two contacts is 9 mm.
or
• Lateral auxiliary switches (two contacts) and 2 NC
signaling switches can be mounted separately
or together. Lateral auxiliary switches One lateral auxiliary switch with four contacts can be mounted on the left
(four contacts) side per motor starter protector/circuit breaker. The contacts of the auxiliary
• Signaling switches cannot be used for
2 NO + 2 NC switch close and open together with the main contacts of the motor starter
3RV1011, 3RV27 and 3RV28 motor starter
protector/circuit breaker.
protectors/circuit breakers.
The width of the lateral auxiliary switch with four contacts is 18 mm.
• Only lateral auxiliary switches can be used for
7
3RV2742 (size S3). Signaling switches One signaling switch can be mounted on the left side of each motor starter
Tripping 1 NO + 1 NC protector.
Short circuit 1 NO + 1 NC The signaling switch has two contact systems.
One contact system always signals tripping irrespective of whether this was
caused by a short circuit, an overload or an auxiliary release. The other
contact system only switches in the event of a short circuit. There is no
signaling as a result of switching off with the actuator.
In order to be able to switch on the motor starter protector again after a short
circuit, the signaling switch must be reset manually after the error cause has
been eliminated.
The width of the signaling switch is 18 mm.
Right-hand side Auxiliary releases
Notes: Shunt releases For remote-controlled tripping of the motor starter protector/circuit breaker.
• One auxiliary release can be mounted per The release coil should only be energized for short periods (see circuit
motor starter protector/circuit breaker. diagrams).
• Accessories cannot be mounted on the right- or
hand side of the 3RV21 motor starter protectors
for motor protection with overload relay Undervoltage releases Trips the motor starter protector/circuit breaker when the voltage is
function. interrupted and prevents the motor from being restarted accidentally when
the voltage is restored. Used for remote-controlled tripping of the motor
starter protector/circuit breaker.
Particularly suitable for EMERGENCY OFF disconnection by way of
corresponding EMERGENCY OFF pushbuttons according to IEC 60204-1.
or
Undervoltage releases with Function and use as for the undervoltage release without leading auxiliary
leading auxiliary contacts 2 NO contacts, but with the following additional function: the auxiliary contacts will
Own version for 3RV1011 open in switch position OFF to deenergize the coil of the undervoltage
release, thus interrupting energy consumption. In the "tripped" position,
these auxiliary contacts are not guaranteed to open. The leading contacts
permit the motor starter protector/circuit breaker to reclose.
The width of the auxiliary release is 18 mm.
Top Isolator modules Isolator modules can be mounted to the upper connection side of the motor
Notes: starter protectors.
• Isolator modules cannot be used for 3RV1011, The supply cable is connected to the motor starter protector through the
3RV27 and 3RV28 motor starter protectors/ isolator module.
circuit breakers. The plug can only be unplugged when the motor starter protector is open
• The isolator module for size S2 can be used and isolates all 3 poles of the motor starter protector from the network.
only with 3RV2 motor starter protectors/ The shock-protected isolation point is clearly visible and secured with
circuit breakers up to max. 65 A. a padlock to prevent reinsertion of the plug.
• The isolator module cannot be used with the
transverse auxiliary switch.
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
Accessories > Mountable accessories
Auxiliary switches1)
Transverse auxiliary switches2)
For front mounting
1 CO S00 ... S3 3RV2901-1D --
1 NO + 1 NC 3RV2901-1E 3RV2901-2E
3RV2901-1E 2 NO 3RV2901-1F 3RV2901-2F
Solid-state compatible
transverse auxiliary
switches2)
3RV2901-2E For mounting on the front,
for operation in dusty
atmosphere and in solid-
state circuits with low
operating currents
3RV2901-1G 1 CO S00 ... S3 3RV2901-1G --
Covers for transverse S00 ... S3 3RV2901-0H --
auxiliary switches
7
(PS* = 10 units)
3RV2901-0H
Lateral auxiliary switches
For mounting on the left
1 NO + 1 NC S00 ... S3 3RV2901-1A 3RV2901-2A
2 NO 3RV2901-1B 3RV2901-2B
2 NC 3RV2901-1C 3RV2901-2C
2 NO + 2 NC 3RV2901-1J --
3RV2901-1A 3RV2901-2A
Signaling switches3)
Signaling switches S005) ... S3 3RV2921-1M 3RV2921-2M
One signaling switch can be
mounted on the left per motor
starter protector.
Separate tripped and
short-circuit alarms,
1 NO + 1 NC each
3RV2921-1M 3RV2921-2M
Isolator modules3)4)
Isolator modules S005), S0 3RV2928-1A --
Visible isolating distance for S2 3RV2938-1A --
isolating individual motor
starter protectors from the
network, lockable in
disconnected position
3RV2928-1A 3RV2938-1A
1) 3)
Each motor starter protector/circuit breaker can be fitted with one This accessory cannot be used for the 3RV27 and 3RV28 circuit breakers
transverse and one lateral auxiliary switch. The lateral auxiliary switch (sizes S00, S0, S3).
with 2 NO + 2 NC is used without a transverse auxiliary switch. 4)
The isolator module for size S2 can be used only with 3RV2 motor starter
2)
Not for 3RV2742 circuit breakers. protectors/circuit breakers up to max. 65 A. Similarly, it cannot be used
with the transverse auxiliary switch
5) Not for 3RV1011 motor starter protectors.
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
Accessories > Mountable accessories
PU (UNIT, SET, M) = 1
PS* = 1 unit
PG = 41E
Auxiliary releases3)
Undervoltage releases
-- -- -- -- 24 S00 ... S3 3RV2902-1AB4 --
24 24 -- -- -- S00 ... S3 3RV2902-1AB0 --
110 120 -- -- -- S00 ... S3 3RV2902-1AF0 --
-- 208 -- -- -- S00 ... S3 3RV2902-1AM1 --
230 240 -- -- -- S00 ... S3 3RV2902-1AP0 3RV2902-2AP0
7
400 440 -- -- -- S00 ... S3 3RV2902-1AV0 3RV2902-2AV0
415 480 -- -- -- S00 ... S3 3RV2902-1AV1 --
500 600 -- -- -- S00 ... S3 3RV2902-1AS0 --
Undervoltage releases with leading auxiliary contacts 2 NO
24 24 -- -- -- S004) ... S3 3RV2922-1CB0 --
230 240 -- -- -- S004) ... S3 3RV2922-1CP0 3RV2922-2CP0
400 440 -- -- -- S004) ... S3 3RV2922-1CV0 3RV2922-2CV0
415 480 -- -- -- S004) ... S3 3RV2922-1CV1 3RV2922-2CV1
Shunt releases
-- -- 20 ... 24 20 ... 70 -- S00 ... S3 3RV2902-1DB0 3RV2902-2DB0
-- -- 90 ... 110 70 ... 190 -- S00 ... S3 3RV2902-1DF0 3RV2902-2DF0
-- -- 210 ... 240 190 ... 330 -- S00 ... S3 3RV2902-1DP0 3RV2902-2DP0
-- -- 350 ... 415 330 ... 500 -- S00 ... S3 3RV2902-1DV0 --
-- -- 500 500 -- S00 ... S3 3RV2902-1DS0 --
1) 3)
The voltage range is valid for 100% (infinite) ON period. The response One auxiliary release can be mounted on the right per motor starter
voltage lies at 0.9 of the lower limit of the voltage range. protector/circuit breaker (does not apply to 3RV21 motor starter
2) The voltage range is valid for 5 s ON period at 50/60 Hz AC and DC. protectors/circuit breakers with overload relay function).
The response voltage lies at 0.85 of the lower limit of the voltage range. 4)
Not for 3RV1011 motor starter protectors.
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
Accessories > Busbar accessories
■ Overview
Insulated 3-phase busbar system The 3-phase busbar systems can also be used to construct
"Starters (Type E)" according to UL/CSA and for 3RV27 and
3-phase busbar systems provide an easy, time-saving 3RV28 circuit breakers according to UL 489. However,
and clearly arranged means of feeding 3RV2 motor starter special infeed terminals, 3RV2925-5EB for sizes S00/S0
protectors/circuit breakers with screw terminals. Different and 3RV2935-5E for size S2, must be used for this purpose,
versions are available for sizes S00 to S2 and can be used for see page 7/52.
the different types of motor starter protectors/circuit breakers
(size S0 up to 32 A). 8US busbar adapters for 60 mm systems
The 3RV1915 3-phase busbar systems are generally unsuitable The motor starter protectors/circuit breakers are mounted
for the 3RV21 motor starter protectors with sizes S00 and S0 for directly with the aid of busbar adapters on busbar systems with
motor protection with overload relay function. 60 mm center-to-center clearance in order to save space and to
The busbars are suitable for between two and five motor starter reduce infeed times and costs.
protectors/circuit breakers. However, any kind of extension is Busbar adapters for busbar systems with 60 mm center-to-
possible by clamping the connection tags of an additional center clearance are suitable for copper busbars with a width of
busbar (rotated by 180°) underneath the terminals of the 12 mm to 30 mm. The busbars can be 5 mm or 10 mm thick.
respective last motor starter protector/circuit breaker.
The motor starter protectors/circuit breakers are snapped onto
A combination of motor starter protectors/circuit breakers of the adapter and connected on the line side. This prepared unit
size S00 and S0 is possible. The motor starter protectors/ is then plugged directly onto the busbar system, and is thus
circuit breakers are supplied by appropriate infeed terminals. connected both mechanically and electrically at the same time.
For the setup of UL feeders (Type E and F), Type E terminal
3RV2925-5AB blocks or phase barriers must be fitted to the infeed module on
the motor starter protector (see from page 7/57).
3RV1915-1CB
For further busbar adapters for snap-mounting direct-on-line
starters and reversing starters as well as additional accessories
7
3RV2915-5B
NSB0_02079c
3RV1915-6AB
3RV2935-5A 3RV1935-1C
3RV1935-1A
NSB0_02080a
NSB0_01074e
3RV1935-6A
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
Accessories > Busbar accessories
7
1) 4)
Not suitable for 3RV21 motor starter protectors of sizes S00 and S0 with For 3RV2 motor starter protectors with auxiliary switches with 1 NO + 1 NC,
overload relay function. 2 NO and 2 NC mounted on the left (9 mm wide).
2) 5)
For 3RV2 motor starter protectors without accessories mounted on the side. For 3RV20, 3RV21, 3RV23 and 3RV24 motor starter protectors with
3) Approved for motor starter protectors size S0 with I 32 A. mounted accessories (18 mm wide). Auxiliary switches with 2 NO + 2 NC
n
or signaling switch (mounted on the left) or with auxiliary release (mounted
on the right).
3RV2935-5A
Connection from below
Terminal is connected in place of a switch, take space
requirement into account
2.5 … 25 2.5 … 16 10 ... 4 Input: S00, S0 3RV2915-5B 1 1 unit 41E
4,
output:
3RV2915-5B 2 ... 2.5
1)
If two different conductor cross-sections are connected to one clamping
point, both cross-sections must be in the range specified.
2) Especially suitable for 3RV1011 motor starter protectors. If the 3RV2 motor
starter protector is used, the terminal block extends beyond the device
width.
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
Accessories > Busbar accessories
3RV2935-5E
1)
If two different conductor cross-sections are connected to one clamping
point, both cross-sections must be in the range specified.
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
Accessories > Busbar accessories
Busbar adapters
For motor starter Rated current Connecting Adapter Adapter Rated voltage Article No. Price PU PS* PG
protectors/ cable length width per PU (UNIT,
circuit breakers SET, M)
Size A AWG mm mm V
Busbar adapters for 60 mm systems
For copper busbars according to DIN 46433
Width: 12 mm and 30 mm
Thickness: 5 mm and 10 mm
and for T and double-T special profiles
• For motor starter protectors/circuit breakers with screw terminals1) Screw terminals
7
S2 80 4 260 55 690 8US1261-6MT10 1 1 unit 14O
S24) 80 4 260 118 690 8US1211-6MT10 1 1 unit 14O
S3 100/705) 4 215 72 690/6005) 8US1211-4TR00 1 1 unit 14O
• For motor starter protectors/circuit breakers with spring-loaded terminals6) Spring-loaded
terminals
S002), S03) 25 12 200 45 690 8US1251-5DS11 1 1 unit 14O
S002), S03) 25 12 260 45 690 8US1251-5DT11 1 1 unit 14O
S0 32 10 200 45 690 8US1251-5NS11 1 1 unit 14O
S03) 32 10 260 45 690 8US1251-5NT11 1 1 unit 14O
Accessories
Device holders -- -- 200 45 -- 8US1250-5AS10 1 1 unit 14O
For lateral attachment -- -- 260 45 -- 8US1250-5AT10 1 1 unit 14O
to busbar adapters
Side modules -- -- 200 9 -- 8US1998-2BJ10 1 10 units 14O
For widening busbar
adapters
Vibration and
shock kits
For high vibration
and shock loads
S2 -- -- -- -- -- 8US1998-1DA10 1 1 unit 14O
1) For the setup of UL feeders (Type E and F), Type E terminal blocks or For additional busbar adapters and accessories, see
phase barriers (for sizes S00 to S2) must be fitted to the infeed module Catalog LV 10.
on the motor starter protector (see from page 7/57).
2)
Not for 3RV1011 motor starter protectors.
3)
Also approved for 3RV27, 3RV28 circuit breakers according to UL.
4) For the assembly of feeders for reversing starters consisting of a motor
starter protector and two contactors.
5)
Values according to UL/CSA:
- Rated current: 70 A at 600 V AC
- Short-circuit breaking capacity:
480 V AC: 65 kA, up to In = 30 A,
480 Y/277 V AC: 65 kA,
600 Y/347 V AC: 20 kA.
6) It is not possible to set up UL feeders (Type E and F).
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
Accessories > Rotary operating mechanisms
■ Overview
Door-coupling rotary operating mechanisms
3RV2926-1B door-coupling rotary operating
Motor starter protectors/circuit breakers with a rotary operating
mechanism for sizes S00 to S3
mechanism can be mounted in a control cabinet and operated
externally by means of a door-coupling rotary operating Consisting of:
mechanism. When the cabinet door with motor starter 1 Actuator
protector/circuit breaker is closed, the operating mechanism 2 Plastic cover
is coupled. When the motor starter protector/circuit breaker
3 Coupling driver
IC01_00711
closes, the coupling is locked which prevents the door from
being opened unintentionally. This interlock can be defeated 4 Extension shaft (6 mm x 6 mm),
130 mm long
by the maintenance personnel. In the OFF position, the rotary
operating mechanism can be secured against reclosing with 5 Coupling enclosure
up to three padlocks. Inadvertent opening of the door is not
possible in this case either. 6 Control cabinet door 5
1
Video: SIRIUS door-coupling rotary mechanism
7
IC01_00712
mechanism for sizes S00 and S0
Consisting of:
1 Actuator
2 Plastic cover
3 Coupling driver 6
4 Extension shaft (8 mm x 8 mm),
300 mm long
5 Spacer
5
6 Metal brackets for inserting
motor starter protector/circuit
breaker
4
7 Control cabinet door
7
1
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
Accessories > Rotary operating mechanisms
Door-coupling rotary operating mechanism for mounting
one main switch in size S3 according to UL 508A and 3RV2946-3C EMERGENCY OFF door-coupling rotary operating
NFPA 79 mechanism for size S3
For the installation of a door-coupling rotary operating Consisting of:
mechanism for harsh conditions for a main switch (only possible 1 Actuator
in size S3) in a UL control cabinet (according to UL 508A and 2 Plastic cover
NFPA 79), the standard stipulates a second handle in the control 3 Coupling driver
cabinet. With the cabinet door open, it shall only be possible to
4 Extension shaft (8 mm x 8 mm), 300 mm long
switch on this supplementary handle by means of a "deliberate
action". 5 Spacer
IC01_00713
6 Metal brackets for inserting
The figure below shows the setup required for this purpose, motor starter protector/circuit breaker
with the 3RV2946-3C door-coupling rotary operating
mechanism for harsh conditions, the 3RV2926-0P shaft 7 Control cabinet door
support, and the 3VA9137-0GC05 supplementary handle 6
(EMERGENCY OFF version). Required for assembly of main control
switch in accordance with UL 508A
To switch on the supplementary handle, the handle must be
and NFPA 79
pressed against a spring in the direction of the mounting plane. (can be optionally ordered):
This is the required "deliberate action" so that the supplementary 8
8 3RV2926-0P shaft support
handle does not turn empty and the circuit breaker can
be closed. 9 3VA9137-0GC05 9
supplementary handle 5
(EMERGENCY OFF
version)
4
7
2
3RV2926-1C
Optional accessories
Tolerance -- -- -- 3RV2926-0Q 1 1 unit 41E
compensation
3RV2926-0Q
1)
Not for 3RV1011 motor starter protectors.
* You can order this quantity or a multiple thereof.
Illustrations are approximate Siemens IC 10 · 2023 7/55
© Siemens 2023
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
Accessories > Rotary operating mechanisms
Version Color of Version of For motor starter Article No. Price PU PS* PG
actuator extension shaft protectors/ per PU (UNIT,
circuit breakers SET, M)
mm Size
Door-coupling rotary operating mechanisms for harsh conditions
The door-coupling rotary operating mechanisms consist of an actuator, a coupling driver, an extension shaft of 300 mm in length
(8 mm x 8 mm), a spacer and two metal brackets, into which the motor starter protector/circuit breaker is inserted.
The door-coupling rotary operating mechanisms are designed to degree of protection IP65. For UL/CSA applications, they are
tested for enclosure types 1, 3R and 12. The door interlocking reliably prevents opening of the control cabinet door in the
ON position of the motor starter protector/circuit breaker. The OFF position can be locked with up to three padlocks.
Laterally mountable auxiliary releases and 2-pole auxiliary switches can be used.
The door-coupling rotary operating mechanisms thus meet the requirements for isolating functions according to IEC 60947-2.
With the optional 3RV2926-2Q tolerance compensation, an offset can be compensated when installing the door-coupling rotary
operating mechanism for harsh conditions.
Door-coupling Gray 300 S001), S0 3RV2926-3B 1 1 unit 41E
3RV2946-3B
rotary S2 3RV2936-3B 1 1 unit 41E
operating
mechanisms S3 3RV2946-3B 1 1 unit 41E
EMERGENCY Red/ 300 S001), S0 3RV2926-3C 1 1 unit 41E
OFF door- yellow S2 3RV2936-3C 1 1 unit 41E
coupling
rotary S3 3RV2946-3C 1 1 unit 41E
operating
mechanism
3RV2946-3C
Optional accessories
Tolerance -- -- S00 ... S3 3RV2926-2Q 1 1 unit 41E
7
compensation
3RV2926-2Q
Necessary accessories for mounting one main switch in size S3 according to UL 508A and NFPA 79
(see also page 7/55)
Shaft supports -- -- S00 ... S3 3RV2926-0P 1 1 unit 41E
3RV2926-0P
Supplementary handles
• Standard Gray -- S3 3VA9137-0GC01 1 1 unit 12P
3VA9137-0GC01
• EMERGENCY Red/ -- S3 3VA9137-0GC05 1 1 unit 12P
OFF yellow
3VA9137-0GC05
1) Not for 3RV1011 motor starter protectors.
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
Accessories > Mounting accessories
■ Overview
More information
System Manual for modular system, see Equipment Manual, see
https://support.industry.siemens.com/cs/ww/en/view/60311318 https://support.industry.siemens.com/cs/ww/en/view/60279172
7
"Starters (Type E)" with an insulated 3-phase busbar system
(see "Busbar accessories", page 7/52).
NSB0_01380c
For the setup of "Starters (Type E)" with 8US busbar adapters,
Type E terminal blocks or phase barriers (for sizes S00 to S2)
must be fitted to the infeed module on the motor starter
protector/circuit breaker, see page 7/60.
The 3RV29 infeed system also enables the assembly of
"Starters (Type E)", see page 7/67 onwards.
SIRIUS 3RT2946-4GA07 terminal block (Type E)
Note:
According to CSA, these terminal blocks and the phase barriers
can be omitted when the device is used as a "Self-Protected
Combination Motor Controller (Type E)".
8
40
00
1_
IC0
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
Accessories > Mounting accessories
Link modules
Feeders can be easily assembled from single devices with the
help of the link modules. The following table shows the different
combination options for devices with screw or spring-loaded
terminals.
Combination 3RV2 motor starter 3RT2 contactors; Link modules
devices protectors/ 3RW30, 3RW40 soft starters; Screw terminals Spring-loaded terminals
circuit breakers 3RF34 solid-state contactors
Size Size
Link modules
for connecting switching devices to 3RV2 motor starter protectors/circuit breakers1)
3RT2 contactors with AC or DC coil S00 S00 3RA1921-1DA00 3RA2911-2AA00
S0 S00 --
S2 S2 3RA2931-1AA00 --
S32) S32) 3RA1941-1AA00 --
3RT2 contactors with AC coil S00 S0 3RA2921-1AA00 --
S0 S0 3RA2921-2AA003)
3RT2 contactors with DC or AC/DC coil S00 S0 3RA2921-1BA00 --
S0 S0 3RA2921-2AA00
3RW30 soft starters S00 S00 3RA2921-1BA00 3RA2911-2GA00
S0 S00 --
3RW30/3RW40 soft starters S00 S0 3RA2921-1BA00 --
S0 S0 3RA2921-2GA00
S24) S24) 3RA2931-1AA00 --
S35) S35) 3RA1941-1AA00 --
7
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
Accessories > Mounting accessories
7
S3 3RT2946-4EA2 1 1 unit 41B
Terminal covers for box terminals on 3RV2742 and
Type E terminal block 3RT2946-4GA07
Additional touch protection to be fitted at the
3RV2742 box terminals (two units required
per device) and at 3RT2946-4GA07 terminal
block (Type E)
Main current level S3 3RV2948-1LA00 1 1 unit 41E
3RV2948-1LA00
Phase barrier for constructing limiter combinations of size S31)
Infeed to the limiter is always on the side
2T1/4T2/6T3. Use 3RV2948-1K phase
barriers on the infeed side.
Main current level S3 3RV2948-1K 1 1 unit 41E
3RV2948-1K
Fixing accessories
Push-in lugs S00, S0 3RV2928-0B 100 10 units 41E
For screw fixing of the motor starter protector/
circuit breaker onto mounting plates
Two units are required for each motor starter
3RV2928-0B protector.
Tools for opening spring-loaded terminals
Screwdrivers Spring-loaded
For all SIRIUS devices with spring-loaded terminals terminals
Length approx. 200 mm, 3.0 mm x 0.5 mm, S00 ... S3 3RA2908-1A 1 1 unit 41B
titanium gray/black, partially insulated
3RA2908-1A
Blank labels
Unit labeling plates1) S00 ... S3 3RT2900-1SB20 100 340 41B
For SIRIUS devices, units
20 mm x 7 mm, titanium gray
Adhesive labels S00 ... S3 3RT2900-1SB60 100 3 060 41B
IC01_00181
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
Accessories > Mounting accessories
3RV2928-1K
7
3RV2938-1K
Auxiliary conductor terminals, 3-pole
For connection of auxiliary and control S3 3RT2946-4F 1 1 unit 41B
cables to the main conductor connections
(for one side)
3RT2946-4F
1)
Not for 3RV1011 motor starter protectors.
2) Cannot be used on 3RV2.4. motor starter protectors in combination with
transverse auxiliary switches.
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
Accessories > Mounting accessories
Link modules
For For Actuating voltage of Article No. Price PU PS* PG
3RV2 motor starter 3RT2 contactor per PU (UNIT,
protectors/ contactors SET, M)
circuit breakers
Size Size
Link modules for motor starter protector to contactor1)
For connection between Screw terminals
motor starter protector and contactor with screw terminals
Single-unit packaging
S00/S0 S00 AC, DC 3RA1921-1DA00 1 1 unit 41B
S00/S0 S0 AC 3RA2921-1AA00 1 1 unit 41B
S00/S0 S0 DC, AC/DC 3RA2921-1BA00 1 1 unit 41B
3RA2921-1AA00 S2 S2 AC, DC, AC/DC 3RA2931-1AA00 1 1 unit 41B
S3 S3 AC, DC, AC/DC 3RA1941-1AA00 1 1 unit 41B
Multi-unit packaging
S00/S0 S00 AC, DC 3RA1921-1D 1 10 units 41B
S00/S0 S0 AC 3RA2921-1A 1 10 units 41B
S00/S0 S0 DC, AC/DC 3RA2921-1B 1 10 units 41B
S2 S2 AC, DC, AC/DC 3RA2931-1A 1 5 units 41B
S3 S3 AC, DC, AC/DC 3RA1941-1A 1 5 units 41B
3RA2931-1AA00
7
3RA1941-1AA00
For connection between Spring-loaded
motor starter protector and contactor with spring-loaded terminals
terminals
Single-unit packaging
S00 S00 AC, DC 3RA2911-2AA00 1 1 unit 41B
S0 S0 AC2), DC, AC/DC 3RA2921-2AA00 1 1 unit 41B
3RA2911-1CA00
1)
The link modules for motor starter protector to contactor cannot be used Note:
for 3RV1011, 3RV2.21-4PA1., 3RV2.21-4FA1., 3RV2.31-4K.1.,
3RV2.31-4R.1., 3RV2.32-4K.1., 3RV2.32-4R.1., 3RV27 and 3RV28 Link modules can be used in
motor starter protectors/circuit breakers.
2) A spacer for height compensation on AC contactors size S0 is optionally • Size S00: up to max. 16 A
available. • Size S0: up to max. 32 A
• Size S2: up to max. 65 A
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
Accessories > Mounting accessories
3RA1941-1A
7
3RA2911-2GA00
1)
The link modules from motor starter protector to soft starter and motor Note:
starter protector to solid-state contactor cannot be used for the 3RV1011,
3RV2.21-4PA1., 3RV2.21-4FA1., 3RV2.31-4K.1., 3RV2.31-4R.1., Link modules can be used in
3RV2.32-4K.1., 3RV2.32-4R.1., 3RV27 and 3RV28 motor starter
protectors/circuit breakers. • Size S00: up to max. 16 A
2) • Size S0: up to max. 32 A
To assemble the feeder between a motor starter protector and a soft starter
in size S2, the 3RA2932-1CA00 DIN-rail adapter must be used.
3) • Size S2: up to max. 65 A
It is only permissible to assemble the feeder between the motor starter
protector and the soft starter in size S3 on a mounting plate.
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
Accessories > Mounting accessories
3RA2921-2FA00
Spacers2)
For height compensation on AC contactors size S0 with spring-
loaded terminals
S0 S0 Single-unit packaging 3RA2911-1CA00 1 1 unit 41B
S0 S0 Multi-unit packaging 3RA2911-1C 1 5 units 41B
7
3RA2911-1CA00
1)
The hybrid link modules for motor starter protector to contactor cannot be Note:
used for 3RV1011, 3RV2.21-4PA1., 3RV2.21-4FA1., 3RV27 and 3RV28
motor starter protectors/circuit breakers. They are suitable only for Link modules can be used in
constructing direct-on-line starters.
2) • Size S00: up to max. 16 A
A spacer for height compensation on AC contactors size S0 is optionally
available. • Size S0: up to max. 32 A
3RT1926-4RD01
3RV2.2 Motor feeder connector 3RT1900-4RE01 1 1 unit 41B
Size S0
3RT1900-4RE01
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
Accessories > Enclosures and front plates
■ Overview
Enclosures There are two knock-out cable entries for cable glands at the top
and two at the bottom; also on the rear corresponding cable
For the stand-alone installation of 3RV20 to 3RV24 motor starter entries are scored. There is a knockout on the top of the
protectors size S00 (In max = 16 A), S0 (In max = 32 A), S2 enclosure for indicator lights that are available as accessories.
(In max = 65 A), and for 3RV1011 motor starter protectors,
molded-plastic and cast aluminum enclosures for surface The narrow enclosure can accommodate a motor starter
mounting and molded-plastic enclosures for flush mounting are protector without accessories, with transverse auxiliary switch
available in various dimensions. and with lateral auxiliary switch. There is no provision for
installing a motor starter protector with a signaling switch.
When installed in a molded-plastic enclosure, the motor starter
protectors have a rated operational voltage Ue of 500 V. With size S00 to S2 3RV2 circuit breakers, the molded-plastic
enclosures are equipped with a rotary operating mechanism.
The enclosures for surface mounting have the degree of
protection IP55; the enclosures for flush mounting also comply The enclosures can be supplied with either a black rotary
with the degree of protection IP55 at the front. The cast operating mechanism or with an EMERGENCY OFF rotary
aluminum enclosures for surface mounting achieve degree of operating mechanism with a red/yellow knob.
protection IP65.
In the OFF position, all rotary operating mechanisms can be
locked with up to three padlocks. These enclosures are not
suitable for 3RV1011 motor starter protectors.
Front plates
Motor starter protectors are frequently required to be actuated in
any enclosure. Front plates equipped with a rotary operating
mechanism for 3RV20 to 3RV24 motor starter protectors sizes
S00 to S3 are available for this purpose.
A holder for the motor starter protectors sizes S00 and S0, into
which the motor starter protectors can be snapped, is available
7
NSB0_02081a
NSB0_02083a
Enclosures for flush mounting (only for sizes S00 and S0)
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
Accessories > Enclosures and front plates
7
+ auxiliary release)
Cast aluminum enclosures for surface mounting1)
With rotary IP65 PE4) 72 S003), S0 3RV1923-1DA01 1 1 unit 41E
operating (for motor starter protector
mechanism, + lateral auxiliary switch2)
lockable in + auxiliary release)
0 position
With IP65 PE4) 72 S003), S0 3RV1923-1GA01 1 1 unit 41E
3RV1923-1DA01 EMERGENCY (for motor starter protector
OFF rotary + lateral auxiliary switch2)
operating + auxiliary release)
mechanism,
lockable in
0 position
Molded-plastic enclosures for flush mounting5)
With rotary IP55 N and 72 S003), S0 3RV1923-2DA00 1 1 unit 41E
operating (front PE (for motor starter protector
mechanism, side) + lateral auxiliary switch2)
lockable in + auxiliary release)
0 position
3RV1923-2DA00
With IP55 N and 72 S003), S0 3RV1923-2GA00 1 1 unit 41E
EMERGENCY (front PE (for motor starter protector
OFF rotary side) + lateral auxiliary switch2)
operating + auxiliary release)
mechanism,
lockable in
0 position
With actuator IP55 N and 72 S006) 3RV1913-2DA00 1 1 unit 41E
diaphragm (front PE (for motor starter protector
side) + lateral auxiliary switch2)
+ auxiliary release)
3RV1913-2DA00
Molded-plastic enclosures for surface mounting
With actuator IP55 N and 85 S006) 3RV1913-1CA00 1 1 unit 41E
diaphragm PE 105 S006) 3RV1913-1DA00 1 1 unit 41E
3RV1913-1CA00
1) The rear cable bushings cannot be used on 3RV2.11-...2. and 5) Not suitable for 3RV2.11-...2. and 3RV2.21-...2. devices with spring-loaded
3RV2.21-...2. devices with spring-loaded terminals. terminals.
2) 6)
Only valid for lateral auxiliary switches with two auxiliary contacts. Only for 3RV1011 motor starter protectors.
3)
Not for 3RV1011 motor starter protectors.
4) If required, an additional N terminal can be mounted (e.g. 8WA1011-1BG11).
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
Accessories > Enclosures and front plates
motor SET, M)
starter
protectors
V Size
Indicator lights
Indicator lights 110 ... 120 S00 to S3 3RV1903-5B 1 1 unit 41E
For all enclosures and front plates 220 ... 240 3RV1903-5C 1 1 unit 41E
• With LED lamp for versions 380 ... 415 3RV1903-5E 1 1 unit 41E
110 ... 120 V, 480 ... 500 3RV1903-5G 1 1 unit 41E
with glow lamp for versions
220 ... 500 V
3RV1903-5B • With colored lenses red, green,
yellow-orange and clear
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
3RV29 infeed system
■ Overview
The 3RV29 infeed system is a convenient means of energy degree of flexibility for configuring the control cabinet: Infeed on
supply and distribution for a group of several motor starter left-hand or right-hand side as well as infeed on one side and
protectors or complete load feeders with screw or spring-loaded outfeed on the other side to supply further loads are all possible.
terminals in sizes S00 and S0. Motor starter protectors or load A terminal block with spring-loaded terminals in combination
feeders with a rated current of maximum 32 A each can be used. with a DIN rail enables the integration of not only SIRIUS motor
3RV21 motor starter protectors cannot be used in this system. starter protectors but also 1-phase, 2-phase and 3-phase
components such as 5SY miniature circuit breakers or
The system is based on a basic module complete with a lateral SIRIUS relay components.
incoming unit (3-phase busbar with infeed). This infeed with
spring-loaded terminals is mounted on the right or left, The 3RV29 infeed system is approved in accordance with IEC to
depending on the version, and can be supplied with a maximum 500 V. It is also UL-approved and authorized for "Self-Protected
conductor cross-section of 25 mm2 (with end sleeve). A basic Combination Motor Controllers" starters (Type E), for starters
module has two sockets onto each of which a motor starter (Type F) (starters (Type E) + contactors) and for circuit breakers
protector can be snapped. according to UL 489 (3RV27/3RV28).
Expansion modules (3-phase busbars for system expansion) Assembly kits for constructing the infeed system with
are available for extending the system. The individual modules spring-loaded terminals
are connected through an expansion plug.
The following versions can be ordered:
The electrical connection between the 3-phase busbars and • Basic set for two feeders
the motor starter protectors is implemented through plug-in
connectors. The complete system can be mounted on • Expansion sets for two or three feeders
a TH 35 DIN rail to IEC 60715, and can be expanded as required The assembly kits contain 3-phase busbars, plug-in connectors
up to a maximum current carrying capacity of 63 A. and contactor bases (see page 7/72).
The system is mounted extremely quickly and easily thanks to Note:
the simple plug-in terminals. Thanks to the lateral infeed, the
system also saves space in the control cabinet. Each set contains plug-in connectors for sizes S00 and S0.
7
The additional height required for the infeed unit is only 30 mm. Example: The basic set contains four plug-in connectors
The alternative infeed possibilities on each side offer a high (two each for S00 and S0).
2
4
7
IC01_00634a
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
3RV29 infeed system
$ 3-phase busbars with infeed + Contactor base
A 3-phase busbar with infeed unit is required for connecting the Load feeders can be assembled in the system using the S00
incoming supply. These modules comprise one infeed module and S0 contactor base. The contactor bases are suitable for
and two sockets which each accept one motor starter protector. contactors of sizes S00 and S0 with screw and spring-loaded
A choice of two versions with infeed on the left or right is terminals and are simply snapped onto the 3-phase busbars.
available. The infeed is connected to spring-loaded terminals. Direct-on-line starters and reversing starters are possible. One
They permit an infeed with conductor cross-sections of up to contactor base is required for direct-on-line starters and two are
25 mm2 with end sleeve. An end cover is supplied with required for reversing starters.
each module.
To assemble load feeders for reversing starters, the contactor
% 3-phase busbars for system expansion bases can be arranged alongside each other (90 mm overall
width). In this case the mechanical interlocking of the contactors
The 3-phase busbars for system expansion support expansion is possible. The S0 contactor bases are also suitable for soft
of the system. There is a choice of modules with two or three starters size S00 and S0 with screw terminal.
sockets. The system can be expanded as required up to
a maximum current carrying capacity of 63 A. An expansion The infeed system is designed for mounting on a TH 35 DIN rail
plug is supplied with each module. with 7.5 mm overall depth. This DIN rail gives the contactor base
a stable mounting surface to sit on. If DIN rails with a depth of
&a Expansion plug 15 mm are used, the spacer connected to the bottom of the
contactor base must be knocked out and plugged into the
The expansion plug is used for electrical connection of adjacent DIN rail mating piece, which is also located on the underside.
3-phase busbars. The current carrying capacity of this plug Then the contactor base also has a stable mounting surface.
equals 63 A. One expansion plug is supplied with each 3-phase When DIN rails with a depth of 7.5 mm are used, the spacer has
busbar for system expansion. Additional expansion plugs are no function and can be removed.
therefore only required as spare parts.
The link modules are used for direct on-line starters, in which
&b Extra-wide expansion plug case the use of a contactor base is not absolutely necessary.
The wide expansion plug makes the electrical connection Motor starter protector and contactor assemblies can then be
between two 3-phase busbars, thus performing the same directly snapped onto the sockets of the 3-phase busbars.
For feeders of sizes S00 and S0, the corresponding
7
* Plug-in connector
The plug-in connector is used for the electrical connection
between the 3-phase busbar and the 3RV2 or 3RV1011 motor
starter protector. These plug-in connectors are available for
screw or spring-loaded terminals.
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
3RV29 infeed system
■ Technical specifications
More information
Equipment Manual, see
https://support.industry.siemens.com/cs/ww/en/view/60279172
General data
Type 3RV29.7
Size S00, S0
Standards
• IEC 60947-2 Yes
• IEC 60947-4-1 Yes
• UL 508/UL 60947-4-1 Yes
Rated current In A 63
Permissible rated current at inside temperature of control cabinet
Motor starter Size Rated current Inside
protectors temperature of
control cabinet
• 3RV2.11/3RV1011 S00 ... 14 A 60 °C % 100
> 14 ... 16 A 40 °C % 100
60 °C % 87
• 3RV2.21 S0 ... 16 A 60 °C % 100
> 16 ... 25 A 40 °C % 100
60 °C % 87
> 25 ... 32 A 40 °C % 87
Permissible ambient temperature
7
• Storage/transport °C -50 ... +80
• Operation °C -20 ... +60
Rated operational voltage Ue
• According to IEC 10% overvoltage V AC 500
5% overvoltage V AC 525
• According to UL/CSA V AC 600
Rated frequency Hz 50/60
Rated impulse withstand voltage Uimp kV 6
Short-circuit strength corresponds to the mounted motor starter protector or load feeder.
The assembly instructions must be followed, see Operating Instructions
Degree of protection IP on the front according to IEC 60529 IP20 with cover and 25 mm2 conductor cross-section at the infeed terminal
Touch protection on the front according to IEC 60529 Finger-safe for vertical touching from the front with cover and 25 mm2
conductor cross-section at the infeed terminal
Conductor cross-sections
Type 3-phase busbar Terminal block Terminal block for
with infeed device infeed
3RV2917-1A,
3RV2917-1E 3RV2917-5D 3RV2917-5FA00
Conductor cross-sections (min./max.)
• Solid or stranded mm2 4 ... 25 1.5 ... 6 1 ... 10
• Finely stranded with end sleeve mm2 4 ... 25 1.5 ... 4 1 ... 6
• Finely stranded without end sleeve mm2 6 … 25 1.5 ... 6 --
• AWG cables AWG 10 ... 3 15 ... 10 18 ... 8
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
3RV29 infeed system
3RV2917-1A
3-phase busbars for system expansion
3-phase busbars For motor starter
Incl. 3RV2917-5BA00 protectors with screw or
expansion plug spring-loaded terminals
• For 2 motor starter S00, S0 3RV2917-4A 1 1 unit 41E
protectors
7
3RV2917-4A
Plug-in connectors
Plug-in connectors • For spring-loaded Spring-loaded
To make contact with terminals terminals
the 3RV2 motor starter
protectors - Single-unit packaging S001) 3RV2917-5AA00 1 1 unit 41E
S02) 3RV2927-5AA00 1 1 unit 41E
- Multi-unit packaging S001) 3RV2917-5A 1 10 units 41E
S02) 3RV2927-5A 1 10 units 41E
3RV2917-5AA00
• For screw terminals Screw terminals
3RV2917-5CA00
Plug-in connectors • For screw terminals
To make contact with
the 3RV1011 motor - Single-unit packaging S00 3RV1917-5CA00 1 1 unit 41E
starter protectors
- Multi-unit packaging S00 3RV1917-5C 1 10 units 41E
1) 4)
I > 14 A, please note derating. The plug-in connector can be used for the 3RV2711, 3RV2811 (size S00)
2) I > 16 A, please note derating. and 3RV2721, 3RV2821 (size S0) circuit breakers.
3)
The plug-in connector cannot be used for the 3RV2711 and 3RV2811
circuit breakers with size S00.
3RV2927-7AA00
1)
Not for 3RV1011 motor starter protectors.
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
3RV29 infeed system
Terminal blocks
Terminal blocks Single-unit packaging 3RV2917-5D 1 1 unit 41E
For integration of 1-phase,
2-phase and 3-phase
components
3RV2917-5D
TH 35 DIN rails, width 45 mm
TH 35 DIN rails Single-unit packaging 3RV1917-7B 1 1 unit 41E
According to IEC 60715,
width 45 mm
For mounting on 3-phase
busbars
3RV1917-7B
Extra-wide expansion plugs
Extra-wide expansion plugs Single-unit packaging 3RV2917-5E 1 1 unit 41E
As accessory
7
3RV2917-5E
Expansion plugs
Expansion plugs1) Single-unit packaging 3RV2917-5BA00 1 1 unit 41E
As spare part
3RV2917-5BA00
End covers
End covers2) Multi-unit packaging 3RV2917-6A 100 10 units 41E
As spare part
3RV2917-6A
Terminal blocks for device infeed
Terminal blocks for Single-unit packaging 3RV2917-5FA00 1 1 unit 41E
device infeed
3RV2917-5FA00
1)
The expansion plug is included in the scope of supply of the 3RV2917-4.
3-phase busbars for system expansion.
2) The end cover is included in the scope of supply of the 3RV2917-1.
3-phase busbars with infeed system.
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV2 motor starter protectors/circuit breakers
3RV29 infeed system
terminals
• 2 x plug-in connectors for spring-loaded terminals S00
3RV2917-5AA00
• 2 x plug-in connectors for spring-loaded terminals S0
3RV2927-5AA00
• 2 x 3RV2927-7AA00 contactor bases S00, S0
Expansion set for three feeders 3RV2907-4BB00 1 1 unit 41E
contains:
• 1 x 3-phase busbars 3RV2917-4B S00, S0
(incl. expansion plug 3RV2917-5BA00),
for three motor starter protectors with spring-loaded
terminals
• 3 x plug-in connectors for spring-loaded terminals S00
3RV2917-5AA00
• 3 x plug-in connectors for spring-loaded terminals S0
3RV2927-5AA00
• 3 x 3RV2927-7AA00 contactor bases S00, S0
1) Not for 3RV1011 motor starter protectors.
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV1 motor starter protectors/circuit breakers
AC-3e E3 ready IE4 ready IE3/IE4 ready For fuse monitoring
■ Technical specifications
See pages 7/9, 7/11, 7/14, 7/19, 7/20 and 7/23
A A A kA
Size S00
0.2 0.2 1.2 100 3RV1611-0BD10 1 1 unit 41E
3RV1611-0BD10
7
Note:
The auxiliary switch required for signaling must be ordered
separately.
■ Accessories
Version Contacts Screw terminals PU PS* PG
(UNIT,
SET, M)
Article No. Price
per PU
3RV2901-1E
Lateral auxiliary switches 1 NO + 1 NC 3RV2901-1A 1 1 unit 41E
With screw terminals, mountable on the left
3RV2901-1A
Additional auxiliary switches and other accessories, see from page 7/47 onwards.
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV1 motor starter protectors/circuit breakers
For distance protection
■ Technical specifications
See page 7/24
3RV1611-1.G14
7
■ Accessories
Version Contacts Screw terminals PU PS* PG
(UNIT,
SET, M)
Article No. Price
per PU
3RV2901-1A
Additional auxiliary switches and other accessories, see from page 7/47 onwards.
Protection equipment
Motor starter protectors/circuit breakers
SIRIUS 3RV1 motor starter protectors/circuit breakers
AC-3e E3 ready IE4 ready IE3/IE4 ready For motor protection
A kW A A kA
Size S00
0.16 0.04 0.11 ... 0.16 2.1 100 3RV1011-0AA10 1 1 unit 41E
0.2 0.06 0.14 ... 0.2 2.6 100 3RV1011-0BA10 1 1 unit 41E
0.25 0.06 0.18 ... 0.25 3.3 100 3RV1011-0CA10 1 1 unit 41E
0.32 0.09 0.22 ... 0.32 4.2 100 3RV1011-0DA10 1 1 unit 41E
0.4 0.09 0.28 ... 0.4 5.2 100 3RV1011-0EA10 1 1 unit 41E
0.5 0.12 0.35 ... 0.5 6.5 100 3RV1011-0FA10 1 1 unit 41E
0.63 0.18 0.45 ... 0.63 8.2 100 3RV1011-0GA10 1 1 unit 41E
0.8 0.18 0.55 ... 0.8 10 100 3RV1011-0HA10 1 1 unit 41E
1 0.25 0.7 ... 1 13 100 3RV1011-0JA10 1 1 unit 41E
1.25 0.37 0.9 ... 1.25 16 100 3RV1011-0KA10 1 1 unit 41E
3RV1011-..A10 1.6 0.55 1.1 ... 1.6 21 100 3RV1011-1AA10 1 1 unit 41E
2 0.75 1.4 ... 2 26 100 3RV1011-1BA10 1 1 unit 41E
2.5 0.75 1.8 ... 2.5 33 100 3RV1011-1CA10 1 1 unit 41E
3.2 1.1 2.2 ... 3.2 42 100 3RV1011-1DA10 1 1 unit 41E
4 1.5 2.8 ... 4 52 100 3RV1011-1EA10 1 1 unit 41E
5 1.5 3.5 ... 5 65 100 3RV1011-1FA10 1 1 unit 41E
7
6.3 2.2 4.5 ... 6.3 82 100 3RV1011-1GA10 1 1 unit 41E
8 3 5.5 ... 8 104 50 3RV1011-1HA10 1 1 unit 41E
10 4 7 ... 10 130 50 3RV1011-1JA10 1 1 unit 41E
12 5.5 9 ... 12 156 50 3RV1011-1KA10 1 1 unit 41E
1) Guide value for 4-pole standard motors at 50 Hz 400 V AC. The actual The accessories of 3RV2 motor starter protectors/circuit breakers
starting and rated data of the motor to be protected must be considered can be used with exceptions, see page 7/47 onwards.
when selecting the units.
A kW A A kA
Size S00
0.16 0.04 0.11 ... 0.16 2.1 100 3RV1011-0AA15 1 1 unit 41E
0.2 0.06 0.14 ... 0.2 2.6 100 3RV1011-0BA15 1 1 unit 41E
0.25 0.06 0.18 ... 0.25 3.3 100 3RV1011-0CA15 1 1 unit 41E
0.32 0.09 0.22 ... 0.32 4.2 100 3RV1011-0DA15 1 1 unit 41E
0.4 0.09 0.28 ... 0.4 5.2 100 3RV1011-0EA15 1 1 unit 41E
0.5 0.12 0.35 ... 0.5 6.5 100 3RV1011-0FA15 1 1 unit 41E
0.63 0.18 0.45 ... 0.63 8.2 100 3RV1011-0GA15 1 1 unit 41E
0.8 0.18 0.55 ... 0.8 10 100 3RV1011-0HA15 1 1 unit 41E
1 0.25 0.7 ... 1 13 100 3RV1011-0JA15 1 1 unit 41E
1.25 0.37 0.9 ... 1.25 16 100 3RV1011-0KA15 1 1 unit 41E
3RV1011-..A15 1.6 0.55 1.1 ... 1.6 21 100 3RV1011-1AA15 1 1 unit 41E
with integrated 2 0.75 1.4 ... 2 26 100 3RV1011-1BA15 1 1 unit 41E
transverse 2.5 0.75 1.8 ... 2.5 33 100 3RV1011-1CA15 1 1 unit 41E
auxiliary switch 3.2 1.1 2.2 ... 3.2 42 100 3RV1011-1DA15 1 1 unit 41E
4 1.5 2.8 ... 4 52 100 3RV1011-1EA15 1 1 unit 41E
5 1.5 3.5 ... 5 65 100 3RV1011-1FA15 1 1 unit 41E
6.3 2.2 4.5 ... 6.3 82 100 3RV1011-1GA15 1 1 unit 41E
8 3 5.5 ... 8 104 50 3RV1011-1HA15 1 1 unit 41E
10 4 7 ... 10 130 50 3RV1011-1JA15 1 1 unit 41E
12 5.5 9 ... 12 156 50 3RV1011-1KA15 1 1 unit 41E
1)
Guide value for 4-pole standard motors at 50 Hz 400 V AC. The actual The accessories of 3RV2 motor starter protectors/circuit breakers
starting and rated data of the motor to be protected must be considered can be used with exceptions, see page 7/47 onwards.
when selecting the units.
Protection equipment
Overload relays
General data
■ Overview
More information
Homepage, see www.siemens.com/sirius-control TIA Selection Tool Cloud (TST Cloud), see
Industry Mall, see www.siemens.com/tstcloud/?node=ElectronicOverloadRelay
• www.siemens.com/product?3RU2 Configuration Manual for load feeders, see
https://support.industry.siemens.com/cs/ww/en/view/39714188
• www.siemens.com/product?3RB3
Conversion tool, see www.siemens.com/conversion-tool
• www.siemens.com/product?3RB2
Protection equipment
Overload relays
General data
7
Integrated auxiliary -- -- -- -- ✓ • Enable the controlling of contactors directly
contacts from the higher-level control system through
(1 CO and 1 NO in IO-Link
series)
IO-Link connection -- -- -- -- ✓ • Reduction of wiring in the control cabinet
• Enables communication
Connection of -- -- -- -- ✓ • Enables local operation
optional handheld
device
Communication capability through IO-Link
Full starter -- -- -- -- ✓ • Enables in combination with the SIRIUS 3RT
functionality contactors the assembly of communication-
through IO-Link capable motor starters (direct-on-line,
reversing and star-delta (wye-delta) starting)
Readout of -- -- -- -- ✓ • Enables the readout of diagnostics
diagnostics information such as overload, open circuit,
functions ground fault, etc.
Readout of current -- -- -- -- ✓ • Enables the readout of current values and
values their direct processing in the higher-level
control system
Readout of all set -- -- -- -- ✓ • Enables the readout of all set parameters,
parameters e.g. for plant documentation
✓ Available
-- Not available
Protection equipment
Overload relays
General data
Protection equipment
Overload relays
General data
7
CLASS 20E CLASS 20E
CLASS 5E, 10E, 20E, -- ✓ ✓ ✓ ✓ • Enable solutions for very fast starting motors
30E trip classes (only 3RB31) (only 3RB21) requiring special protection (e.g. Ex motors)
adjustable on the • Enable heavy starting solutions
device
• Reduce the number of variants
• Minimize the configuring outlay and costs
• Minimize storage overhead, storage costs,
and tied-up capital
Low power loss -- ✓ ✓ ✓ ✓ • Reduces power consumption and energy
costs (up to 98% less power is used than for
thermal overload relays)
• Minimizes temperature rises of the
contactor and control cabinet – in some
cases this may eliminate the need for
control cabinet cooling
• Direct mounting to contactor saves space,
even for high motor currents (i.e. no heat
decoupling is required)
Internal power --1) ✓ ✓ -- -- • Eliminates the need for configuration and
supply connecting an additional control circuit
Supplied from an -- -- -- -- ✓ • Eliminates the need for configuration and
external source via connecting an additional control circuit
IO-Link
✓ Available 1) SIRIUS 3RU21 thermal overload relays use a bimetal contactor and
-- Not available therefore do not require a control supply voltage.
Protection equipment
Overload relays
General data
Protection equipment
Overload relays
General data
Overview of overload relays – matching contactors
Overload Current Current Contactors (type, size, rating in kW)
relays measure- range 3RT201. 3RT202. 3RT203. 3RT204. 3RT105. 3RT106. 3RT107. 3TF68/3TF69
ment
S00 S0 S2 S3 S6 S10 S12 14
Type A 3/4/5.5/7.5 5.5/7.5/11/15/18.5 15/18.5/22/30/37 37/45/55 55/75/90 110/132/160 200/250 375/450
SIRIUS 3RU21 thermal overload relays
3RU211 Integrated 0.11 … 16 ✓ -- -- -- -- -- -- --
3RU212 Integrated 1.8 … 40 -- ✓ -- -- -- -- -- --
3RU213 Integrated 11 … 80 -- -- ✓ -- -- -- -- --
3RU214 Integrated 28 ... 100 -- -- -- ✓ -- -- -- --
3RU21
SIRIUS 3RB30 electronic overload relays1)
3RB301 Integrated 0.1 … 16 ✓ -- -- -- -- -- -- --
3RB302 Integrated 0.1 … 40 -- ✓ -- -- -- -- -- --
3RB303 Integrated 12.5 … 80 -- -- ✓ -- -- -- -- --
3RB304 Integrated 32 ... 115 -- -- -- ✓ -- -- -- --
3RB30
SIRIUS 3RB31 electronic overload relays1)
3RB311 Integrated 0.1 … 16 ✓ -- -- -- -- -- -- --
3RB312 Integrated 0.1 … 40 -- ✓ -- -- -- -- -- --
3RB313 Integrated 12.5 … 80 -- -- ✓ -- -- -- -- --
✓
7
3RB314 Integrated 32 ... 115 -- -- -- -- -- -- --
3RB31
SIRIUS 3RB20 electronic overload relays1)
3RB205 Integrated 50 … 200 -- -- -- -- ✓ -- -- --
3RB206 Integrated 55 … 630 -- -- -- -- -- ✓ ✓ ✓
3RB201 + Integrated 630 … 820 -- -- -- -- -- -- -- ✓
3UF18
3RB20
SIRIUS 3RB21 electronic overload relays1)
3RB215 Integrated 50 … 200 -- -- -- -- ✓ -- -- --
3RB216 Integrated 55 … 630 -- -- -- -- -- ✓ ✓ ✓
3RB211 + Integrated 630 … 820 -- -- -- -- -- -- -- ✓
3UF18
3RB21
SIRIUS 3RB22 to 3RB24 electronic overload relays1)
3RB2906 0.3 … 25 ✓ ✓ -- -- -- -- -- --
3RB2283/ 3RB2906 10 … 100 ✓ ✓ ✓ ✓ -- -- -- --
3RB2383/
3RB2483 3RB2956 20 … 200 -- ✓ ✓ ✓ ✓ -- -- --
+ 3RB2966 63 … 630 -- -- -- -- -- ✓ ✓ ✓
3RB2906 630 … 820 -- -- -- -- -- -- -- ✓
+ 3UF18
3RB22, 3RB23,
3RB24
✓ Can be used 1) "Technical specifications" for the use of overload relays with trip class
-- Cannot be used CLASS 20E, see "Short-circuit protection with fuses for motor feeders"
in theConfiguration Manual.
Protection equipment
Overload relays
General data
Connection methods Voltage data
3RU2 thermal overload relays The data for 3-phase power systems according to IEC 60947-4-1
• Sizes S00 and S0: are valid for the following line system configurations:
.
- Main and auxiliary circuit: Either screw or spring-loaded Voltage Ue Line system configurations
terminals
Three-phase Three-phase
• Sizes S2 and S3: four-wire networks three-wire networks
- Main circuit: Screw terminals with box terminal
- Auxiliary circuit: Either screw or spring-loaded terminals
3RB3 electronic overload relays
IC01_00703
• Sizes S00 and S0:
IC01_00709
- Main and auxiliary circuit: Either screw or spring-loaded
terminals
• Sizes S2 and S3: V V V
- Main circuit: Screw terminals with box terminal or as straight-
through transformer 230 -- 230
- Auxiliary circuit: Either screw or spring-loaded terminals 400 230/400 400
440 260/440 440
3RB2 electronic overload relays
500 -- 500
3RB20 and 3RB21 overload relays: 690 400/690 690 (only as from size S3)
• Size S6: 1 000 -- 1 000
- Main circuit: With busbar connection or as straight-through
-- Not specified
transformer
- Auxiliary circuit: Either screw or spring-loaded terminals
• Sizes S10/S12:
- Main circuit: With busbar connection
- Auxiliary circuit: Either screw or spring-loaded terminals
7
Screw terminals
Spring-loaded terminals
Busbar connections
Straight-through transformers
Protection equipment
Overload relays
SIRIUS 3RU2 thermal overload relays
3RU2 for standard applications
■ Overview
More information
Homepage, see www.siemens.com/sirius-control Application Manual for switching devices with IE3 and IE4 motors, see
Industry Mall, see www.siemens.com/product?3RU2 https://support.industry.siemens.com/cs/ww/en/view/94770820
TIA Selection Tool Cloud (TST Cloud), see Equipment Manual, see
www.siemens.com/tstcloud/?node=ThermalOverloadRelay https://support.industry.siemens.com/cs/ww/en/view/60298164
Conversion tool, see www.siemens.com/conversion-tool Characteristics and certificates, see
https://support.industry.siemens.com/cs/ww/en/ps/16271
IC01_00659
4 Cable release with holder for RESET
5 Sealable cover
2 6 Mechanical RESET
7 Pushbutton
7
3
5
4
Protection equipment
Overload relays
SIRIUS 3RU2 thermal overload relays
3RU2 for standard applications
3RU21 thermal overload relays up to 100 A have been designed
to provide inverse-time delayed protection for loads with normal
starting against impermissibly high temperature rises due to
6 overload or phase failure.
An overload or phase failure results in an increase of the
motor current beyond the set rated motor current. Via heating
IC01_00403a
elements, this current rise heats up the bimetal strips inside
the device which then bend and as a result trigger the auxiliary
contacts by means of a tripping mechanism. The auxiliary
contacts then switch off the load by means of a contactor.
5 The break time depends on the ratio between the tripping
1
current and the current setting Ie and is stored in the form of
4 a long-term stable tripping characteristic curve, see
2
Characteristic curves.
3 The "tripped" status is signaled by means of a switch position
indicator. The relay is reset manually or automatically after
a recovery time has elapsed.
The 3RU2 thermal overload relays are suitable for operation with
1 Switch position indicator and TEST function of the wiring: frequency converters.
Indicates a trip and enables the wiring test.
The devices are manufactured in accordance with
2 Motor current setting: environmental guidelines and contain environmentally friendly
Setting the device to the rated motor current is easy with the large
rotary knob. and reusable materials. They comply with all important
worldwide standards and approvals.
3 Connecting terminals:
Depending on the device version, the connecting terminals are Use in hazardous areas
screw terminals or spring-loaded terminals for the main and
auxiliary circuits. The 3RU2 overload relays are certified in accordance with both
4 STOP button: the European Explosion Protection Directive (ATEX) and the
7
If the STOP button is pressed, the NC contact is opened. This International Explosion Protection Standard (IECEx), see
switches off the contactor downstream. The NC contact is closed
again when the button is released. Certificates.
5 Selector switch for Manual/Automatic RESET and RESET button:
With this switch you can choose between Manual and Automatic
RESET. A device set to Manual RESET can be reset locally by
pressing the RESET button. A Remote RESET is possible using the
RESET modules (accessories), which are independent of size.
6 Connection for mounting onto contactors:
Optimally adapted in electrical, mechanical and design terms to the
contactors. The overload relay can be connected directly to the
contactor using these pins. Stand-alone installation is possible as
an alternative (in conjunction with a terminal support for stand-alone
installation).
A sealable transparent cover can be optionally mounted (accessory).
It secures the motor current setting against adjustment.
Protection equipment
Overload relays
SIRIUS 3RU2 thermal overload relays
3RU2 for standard applications
■ Benefits
The most important features and benefits of the 3RU21 thermal
overload relays are listed in the overview table (see "General
data", page 7/76 onwards).
■ Application
Industries Ambient conditions
The 3RU21 thermal overload relays are suitable for customers 3RU21 thermal overload relays compensate temperature
from all industries who want to guarantee optimum inverse-time in the temperature range from -40 to +60 °C according to
delayed protection of their electrical loads (e.g. motors) under IEC 60947-4-1. At temperatures from +60 to +70 °C, the upper
normal starting conditions (CLASS 10, 10A). set value of the setting range has to be reduced by a specific
factor.
Application
Use of SIRIUS protection devices in conjunction with
The 3RU21 thermal overload relays have been designed for the IE3 and IE4 motors
protection of three-phase and single-phase AC and DC motors.
Note:
If single-phase AC or DC loads are to be protected by the 3RU21
thermal overload relays, all three bimetal strips must be heated. For the use of 3RU21 thermal overload relays in conjunction with
For this purpose, all main conducting paths of the relay must be highly efficient IE3 and IE4 motors, please observe the
connected in series. information on dimensioning and configuring,
see Application Manual.
For more information, see page 1/8.
■ Technical specifications
7
More information
System Manual for modular system, see Equipment Manual, see
https://support.industry.siemens.com/cs/ww/en/view/60311318 https://support.industry.siemens.com/cs/ww/en/view/60298164
Configuration Manual for load feeders, see Technical specifications, see
https://support.industry.siemens.com/cs/ww/en/view/39714188 https://support.industry.siemens.com/cs/ww/en/ps/16270/td
Dimensions (W x H x D)
(overload relay with stand-alone installation
D
W
support)
• Screw terminals mm 45 x 89 x 80 45 x 97 x 95 55 x 105 x 117 70 x 106 x 124
• Spring-loaded terminals mm 45 x 102 x 79 45 x 114 x 95 55 x 105 x 117 70 x 106 x 124
General data
Tripping in the event of Overload and phase failure
Trip class according to IEC 60947-4-1 CLASS 10 10, 10A
Phase failure sensitivity Yes
Overload warning No
Reset and recovery
• Reset options after tripping Manual, Auto and Remote RESET
(Remote RESET in conjunction with the appropriate accessories)
• Recovery time
- For Automatic RESET min. Depends on the strength of the tripping current and characteristic
- For Manual RESET min. Depends on the strength of the tripping current and characteristic
- For Remote RESET min. Depends on the strength of the tripping current and characteristic
Features
• Display of operating state on device Yes, by means of TEST function/switch position indicator slide
• TEST function Yes
• RESET button Yes
• STOP button Yes
Protection of motors in hazardous environments
• Certificate of suitability/explosion protection type according to DMT 98 ATEX G 001 II (2) GD
ATEX Directive 2014/34/EU IECEx BVS 15.0046
• According to international standard IECEx see https://support.industry.siemens.com/cs/ww/en/ps/16270/cert
Protection equipment
Overload relays
SIRIUS 3RU2 thermal overload relays
3RU2 for standard applications
H
Dimensions (W x H x D)
(overload relay with stand-alone installation
D
W
support)
• Screw terminals mm 45 x 89 x 80 45 x 97 x 95 55 x 105 x 117 70 x 106 x 124
• Spring-loaded terminals mm 45 x 102 x 79 45 x 114 x 95 55 x 105 x 117 70 x 106 x 124
General data (continued)
Ambient temperature
• Storage/transport °C -55 ... +80
• Operation °C -40 ... +70
• Temperature compensation °C Up to +60
• Permissible rated current at
- Temperature inside control cabinet 60 °C % 100 (current reduction is required above +60 °C)
- Temperature inside control cabinet 70 °C % 87
Repeat terminals
• Coil repeat terminals Yes Not required
• Auxiliary contact repeat terminals Yes Not required
Degree of protection IP on the front according to IEC 60529 IP20 (screw terminals and spring-loaded terminals)
Touch protection on the front according to IEC 60529 Finger-safe for vertical touching from the front (screw and spring-loaded terminals)
Shock resistance with sine according to IEC 60068-2-27 g/ms 15/11 (auxiliary contacts 95/96 and 97/98: 8 g/11 ms)
Electromagnetic compatibility (EMC)
• Interference immunity Not relevant
• Emitted interference Not relevant
Installation altitude above sea level m Up to 2 000
Mounting position The diagrams show the permissible mounting positions for mounting on contactors
7
and stand-alone installation. For mounting position in the hatched area, a setting
correction of 10% must be implemented.
Stand-alone installation:
0°
45° 0° 45°
e x 1,1 e x 1,1
90° 90°
135° 135° NSB0_01364
e x 1,1
e x 1,1
Type of mounting For mounting on contactor or stand-alone installation with terminal support,
screw and snap-on mounting on DIN rail.
Protection equipment
Overload relays
SIRIUS 3RU2 thermal overload relays
3RU2 for standard applications
7
Connection type Screw terminals Screw terminals
with box terminal
Terminal screw M3, Pozidriv size 2 M4, Pozidriv size 2 M6, Pozidriv size 2 4 mm Allen screw
Operating devices mm 5 ... 6 5 ... 6 5 ... 6 4 mm Allen screw
Prescribed tightening torque Nm 0.8 ... 1.2 2 ... 2.5 3 ... 4.5 4.5 ... 6
Conductor cross-sections (min./max.),
one or two conductors can be connected
• Solid or stranded mm2 2 x (0.5 ... 1.5)1); 2 x (1 ... 2.5)1), 2 x (2.5 ... 35)1), 2 x (2.5 ... 16)1),
2 x (0.75 ... 2.5)1), 2 x (2.5 ... 10)1) 1 x (2.5 ... 50)1) 2 x (10 ... 50)1),
max. 2 x 4 1 x (10 ... 70)1)
• Finely stranded with end sleeve (DIN 46228) mm2 2 x (0.5 ... 1.5)1), 2 x (1 ... 2.5)1); 2 x (1 ... 25)1), 2 x (2.5 ... 35)1),
2 x (0.75 ... 2.5)1) 2 x (2.5 ... 6)1), 1 x (1 ... 35)1) 1 x (2.5 ... 50)1)
max. 1 x 10
• AWG cables, solid or stranded AWG 2 x (20 ... 16)1), 2 x (16 ... 12)1), 2 x (18 ... 2)1), 2 x (10 ... 1/0)1),
2 x (18 ... 14)1), 2 x (14 ... 8)1) 1 x (18 ... 1)1) 1 x (10 ... 2/0)1)
2 x 12
Removable box terminals2)
• With copper bars3) mm -- -- -- 2 x 12 x 4
• With cable lugs4)
- Terminal screw -- -- -- M6
- Prescribed tightening torque Nm -- -- -- 4.5 ... 6
- Usable ring cable lugs d3 mm -- -- -- d2 = min. 6.3
d2 d3 = max. 19
I201_12740
Protection equipment
Overload relays
SIRIUS 3RU2 thermal overload relays
3RU2 for standard applications
• With fuse
- Operational class gG A 6
- Quick A 10
• With miniature circuit breaker (C characteristic) A 6 (up to Ik 0.5 kA; U 260 V)
Reliable operational voltage for protective separation between V 440
auxiliary conducting paths
According to IEC 60947-1
CSA, UL and UR rated data
Auxiliary circuit – Switching capacity B600, R300
Conductor cross-sections for auxiliary circuit
Connection type Screw terminals
Protection equipment
Overload relays
SIRIUS 3RU2 thermal overload relays
IE3 ready IE4 ready IE3/IE4 ready 3RU2 for standard applications
Size Trip class Rated power for Current setting Short-circuit Screw terminals Spring-loaded
contac- three-phase value of the protection with fuse, terminals
tor motors, rated inverse-time type of
value2) delayed overload coordination "2",
7
release operational
class gG3)
Article No. Price Article No. Price
CLASS kW A A per PU per PU
Size S00
S00 10 0.04 0.11 ... 0.16 0.5 3RU2116-0AB0 3RU2116-0AC0
10 0.06 0.14 ... 0.2 1 3RU2116-0BB0 3RU2116-0BC0
10 0.06 0.18 ... 0.25 1 3RU2116-0CB0 3RU2116-0CC0
10 0.09 0.22 ... 0.32 1.6 3RU2116-0DB0 3RU2116-0DC0
10 0.09 0.28 ... 0.4 2 3RU2116-0EB0 3RU2116-0EC0
10 0.12 0.35 ... 0.5 2 3RU2116-0FB0 3RU2116-0FC0
10 0.18 0.45 ... 0.63 2 3RU2116-0GB0 3RU2116-0GC0
10 0.18 0.55 ... 0.8 4 3RU2116-0HB0 3RU2116-0HC0
10 0.25 0.7 ... 1 4 3RU2116-0JB0 3RU2116-0JC0
10 0.37 0.9 ... 1.25 4 3RU2116-0KB0 3RU2116-0KC0
10 0.55 1.1 ... 1.6 6 3RU2116-1AB0 3RU2116-1AC0
10 0.75 1.4 ... 2 6 3RU2116-1BB0 3RU2116-1BC0
10 0.75 1.8 ... 2.5 10 3RU2116-1CB0 3RU2116-1CC0
10 1.1 2.2 ... 3.2 10 3RU2116-1DB0 3RU2116-1DC0
10 1.5 2.8 ... 4 16 3RU2116-1EB0 3RU2116-1EC0
10 1.5 3.5 ... 5 20 3RU2116-1FB0 3RU2116-1FC0
10 2.2 4.5 ... 6.3 20 3RU2116-1GB0 3RU2116-1GC0
10 3 5.5 ... 8 25 3RU2116-1HB0 3RU2116-1HC0
10 4 7 ... 10 35 3RU2116-1JB0 3RU2116-1JC0
10 5.5 9 ... 12.5 35 3RU2116-1KB0 3RU2116-1KC0
10 7.5 11 ... 16 40 3RU2116-4AB0 3RU2116-4AC0
Size S0
S0 10 0.75 1.8 ... 2.5 10 3RU2126-1CB0 3RU2126-1CC0
10 1.1 2.2 ... 3.2 10 3RU2126-1DB0 3RU2126-1DC0
10 1.5 2.8 ... 4 16 3RU2126-1EB0 3RU2126-1EC0
10 1.5 3.5 ... 5 20 3RU2126-1FB0 3RU2126-1FC0
10 2.2 4.5 ... 6.3 20 3RU2126-1GB0 3RU2126-1GC0
10 3 5.5 ... 8 25 3RU2126-1HB0 3RU2126-1HC0
10 4 7 ... 10 35 3RU2126-1JB0 3RU2126-1JC0
10 5.5 9 ... 12.5 35 3RU2126-1KB0 3RU2126-1KC0
10 7.5 11 ... 16 40 3RU2126-4AB0 3RU2126-4AC0
10 7.5 14 ... 20 50 3RU2126-4BB0 3RU2126-4BC0
10 11 17 ... 22 63 3RU2126-4CB0 3RU2126-4CC0
10 11 20 ... 25 63 3RU2126-4DB0 3RU2126-4DC0
10 15 23 ... 28 63 3RU2126-4NB0 3RU2126-4NC0
10 15 27 ... 32 80 3RU2126-4EB0 3RU2126-4EC0
10 18.5 30 ... 36 80 3RU2126-4PB0 3RU2126-4PC0
10 18.5 34 ... 40 80 3RU2126-4FB0 3RU2126-4FC0
1) 3)
With the appropriate terminal supports (see page 7/93), the 3RU2 overload Maximum protection by fuse only for overload relays, type of
relays for mounting on contactors can also be installed as stand-alone units. coordination "2". For fuse values in connection with contactors,
2)
Guide value for 4-pole standard motors at 50 Hz 400 V AC. The actual see Configuration Manual.
starting and rated data of the motor to be protected must be considered
when selecting the units.
Protection equipment
Overload relays
SIRIUS 3RU2 thermal overload relays
3RU2 for standard applications IE3 ready IE4 ready IE3/IE4 ready
3RU21 thermal overload relays for mounting on contactor1), sizes S2 and S3, CLASS 10 or 10A
Features and technical specifications: • TEST function
• Connection methods • STOP button
- Main circuit: Screw terminals with box terminal • Sealable covers (optional accessory)
- Auxiliary circuit: Either screw or spring-loaded terminals
• Overload and phase failure protection PU (UNIT, SET, M) = 1
• Auxiliary contacts 1 NO + 1 NC PS* = 1 unit
PG = 41F
• Manual and Automatic RESET
• Switch position indicator
Size Trip class Rated power for Current setting Short-circuit Screw terminals Spring-loaded
contac- three-phase value of the protection with fuse, terminals
tor motors, rated inverse-time type of (on auxiliary current
value2) delayed overload coordination "2", side)
7
release operational
class gG3)
Article No. Price Article No. Price
CLASS kW A A per PU per PU
Size S2
S2 10 3 5.5 ... 8 25 3RU2136-1HB0 3RU2136-1HD0
10 4 7 ... 10 35 3RU2136-1JB0 3RU2136-1JD0
10 5.5 9 ... 12.5 35 3RU2136-1KB0 3RU2136-1KD0
10 7.5 11 ... 16 40 3RU2136-4AB0 3RU2136-4AD0
10 7.5 14 ... 20 50 3RU2136-4BB0 3RU2136-4BD0
10 11 18 ... 25 63 3RU2136-4DB0 3RU2136-4DD0
10 15 22 ... 32 80 3RU2136-4EB0 3RU2136-4ED0
10 18.5 28 ... 40 80 3RU2136-4FB0 3RU2136-4FD0
10 22 36 ... 45 100 3RU2136-4GB0 3RU2136-4GD0
10 22 40 ... 50 100 3RU2136-4HB0 3RU2136-4HD0
10 30 47 ... 57 100 3RU2136-4QB0 3RU2136-4QD0
10 30 54 ... 65 125 3RU2136-4JB0 3RU2136-4JD0
10A 37 62 ... 73 160 3RU2136-4KB0 3RU2136-4KD0
10A 37 70 ... 80 160 3RU2136-4RB0 3RU2136-4RD0
Size S3
S3 10 18.5 28 ... 40 80 3RU2146-4FB0 3RU2146-4FD0
10 22 36 ... 50 125 3RU2146-4HB0 3RU2146-4HD0
10 30 45 ... 63 125 3RU2146-4JB0 3RU2146-4JD0
10 37 57 ... 75 160 3RU2146-4KB0 3RU2146-4KD0
10 45 70 ... 90 160 3RU2146-4LB0 3RU2146-4LD0
10 45 80 ... 1004) 200 3RU2146-4MB0 3RU2146-4MD0
1) 3)
With the appropriate terminal supports (see page 7/93), the 3RU2 overload Maximum protection by fuse only for overload relays, type of
relays for mounting on contactors can also be installed as stand-alone units. coordination "2". For fuse values in connection with contactors,
2) Guide value for 4-pole standard motors at 50 Hz 400 V AC. The actual see Configuration Manual.
starting and rated data of the motor to be protected must be considered 4) For overload relays > 100 A, see 3RB2 electronic overload relays,
when selecting the units. page 7/107 onwards.
Protection equipment
Overload relays
SIRIUS 3RU2 thermal overload relays
IE3 ready IE4 ready IE3/IE4 ready 3RU2 for standard applications
3RU21 thermal overload relays for stand-alone installation, sizes S00 and S0, CLASS 10
Features and technical specifications: • TEST function
• Connection methods • STOP button
Main and auxiliary circuit: Either screw or spring-loaded • Sealable covers (optional accessory)
terminals
• Overload and phase failure protection PU (UNIT, SET, M) = 1
• Auxiliary contacts 1 NO + 1 NC PS* = 1 unit
PG = 41F
• Manual and Automatic RESET
• Switch position indicator
Size Trip class Rated power for Current setting Short-circuit Screw terminals Spring-loaded
contac- three-phase value of the protection with fuse, terminals
tor motors, rated inverse-time type of
value1) delayed overload coordination "2",
release operational
class gG2)
7
Article No. Price Article No. Price
CLASS kW A A per PU per PU
Size S00
S00 10 0.04 0.11 ... 0.16 0.5 3RU2116-0AB1 3RU2116-0AC1
10 0.06 0.14 ... 0.2 1 3RU2116-0BB1 3RU2116-0BC1
10 0.06 0.18 ... 0.25 1 3RU2116-0CB1 3RU2116-0CC1
10 0.09 0.22 ... 0.32 1.6 3RU2116-0DB1 3RU2116-0DC1
10 0.09 0.28 ... 0.4 2 3RU2116-0EB1 3RU2116-0EC1
10 0.12 0.35 ... 0.5 2 3RU2116-0FB1 3RU2116-0FC1
10 0.18 0.45 ... 0.63 2 3RU2116-0GB1 3RU2116-0GC1
10 0.18 0.55 ... 0.8 4 3RU2116-0HB1 3RU2116-0HC1
10 0.25 0.7 ... 1 4 3RU2116-0JB1 3RU2116-0JC1
10 0.37 0.9 ... 1.25 4 3RU2116-0KB1 3RU2116-0KC1
10 0.55 1.1 ... 1.6 6 3RU2116-1AB1 3RU2116-1AC1
10 0.75 1.4 ... 2 6 3RU2116-1BB1 3RU2116-1BC1
10 0.75 1.8 ... 2.5 10 3RU2116-1CB1 3RU2116-1CC1
10 1.1 2.2 ... 3.2 10 3RU2116-1DB1 3RU2116-1DC1
10 1.5 2.8 ... 4 16 3RU2116-1EB1 3RU2116-1EC1
10 1.5 3.5 ... 5 20 3RU2116-1FB1 3RU2116-1FC1
10 2.2 4.5 ... 6.3 20 3RU2116-1GB1 3RU2116-1GC1
10 3 5.5 ... 8 25 3RU2116-1HB1 3RU2116-1HC1
10 4 7 ... 10 35 3RU2116-1JB1 3RU2116-1JC1
10 5.5 9 ... 12.5 35 3RU2116-1KB1 3RU2116-1KC1
10 7.5 11 ... 16 40 3RU2116-4AB1 3RU2116-4AC1
Size S0
S0 10 7.5 14 ... 20 50 3RU2126-4BB1 3RU2126-4BC1
10 11 17 ... 22 63 3RU2126-4CB1 3RU2126-4CC1
10 11 20 ... 25 63 3RU2126-4DB1 3RU2126-4DC1
10 15 23 ... 28 63 3RU2126-4NB1 3RU2126-4NC1
10 15 27 ... 32 80 3RU2126-4EB1 3RU2126-4EC1
10 18.5 30 ... 36 80 3RU2126-4PB1 3RU2126-4PC1
10 18.5 34 ... 40 80 3RU2126-4FB1 3RU2126-4FC1
1) 2)
Guide value for 4-pole standard motors at 50 Hz 400 V AC. The actual Maximum protection by fuse only for overload relays, type of
starting and rated data of the motor to be protected must be considered coordination "2". For fuse values in connection with contactors,
when selecting the units. see Configuration Manual.
Protection equipment
Overload relays
SIRIUS 3RU2 thermal overload relays
3RU2 for standard applications IE3 ready IE4 ready IE3/IE4 ready
3RU21 thermal overload relays for stand-alone installation, sizes S2 and S3, CLASS 10 or 10A
Features and technical specifications: • TEST function
• Connection methods • STOP button
- Main circuit: Screw terminals with box terminal • Sealable covers (optional accessory)
- Auxiliary circuit: Either screw or spring-loaded terminals
• Auxiliary contacts 1 NO + 1 NC PU (UNIT, SET, M) = 1
• Manual and Automatic RESET PS* = 1 unit
• Switch position indicator PG = 41F
Size Trip class Rated power for Current setting Short-circuit Screw terminals Spring-loaded
contac- three-phase value of the protection with fuse, terminals
tor motors, rated inverse-time type of
value1) delayed overload coordination "2",
release operational
class gG2)
7
Protection equipment
Overload relays
SIRIUS 3RU2 thermal overload relays
Accessories
■ Overview
The following optional accessories are available for the • Electrical Remote RESET module in three voltage variants
3RU21 thermal overload relays: (for all sizes)
• Size-specific terminal support for stand-alone installation, • Sealable cover (for all sizes)
in sizes S00 and S0 also with spring-loaded terminals • Size-specific terminal covers for devices with screw terminals
• Mechanical RESET (for all sizes) (box terminals)
• Cable release for resetting devices which are difficult to
access (for all sizes)
7
S0 3RU2926-3AC01 1 1 unit 41F
3RU2926- 3RU2926-
3AA01 3AC01
3RU2936-3AA01
3RU2946-3AA01
Mechanical RESET
Resetting plungers, holders and formers S00 ... S3 3RU2900-1A 1 1 unit 41F
3RU2900-1A
Pushbuttons with extended stroke S00 ... S3 3SU1200-0FB10-0AA0 1 1 unit 41J
(12 mm), IP65, 22 mm
3SU1200-0FB10-0AA0
Extension plungers S00 ... S3 3SU1900-0KG10-0AA0 1 1 unit 41J
For compensation of the distance between
the pushbutton and the resetting plunger of
the relay
3SU1900-0KG10-0AA0
Protection equipment
Overload relays
SIRIUS 3RU2 thermal overload relays
Accessories
3RU2900-1B
Modules for Remote RESET, electrical
Operating range 0.85 ... 1.1 x Us,
Power consumption 80 VA AC, 70 W DC,
ON period 0.2 ... 4 s,
Switching frequency 60/h
• 24 ... 30 V AC/DC S00 ... S3 3RU1900-2AB71 1 1 unit 41F
• 110 ... 127 V AC/DC S00 ... S3 3RU1900-2AF71 1 1 unit 41F
• 220 ... 250 V AC/DC S00 ... S3 3RU1900-2AM71 1 1 unit 41F
3RU1900-2AM71
Sealable covers
For covering the setting knobs S00 ... S3 3RV2908-0P 100 10 units 41E
7
3RV2908-0P
Terminal covers
Covers for contactors with cable lug and S3 3RT1946-4EA1 1 1 unit 41B
busbar connections
For complying with the phase clearances
and as touch protection if box terminal is
removed
3RT1946-4EA1
Covers for devices with screw terminals Screw terminals
(box terminals)
Additional touch protection for fastening to the
box terminals
• Main current level S2 3RT2936-4EA2 1 1 unit 41B
3RT2936-4EA2
S3 3RT2946-4EA2 1 1 unit 41B
General accessories
Version Size Color For Article No. Price PU PS* PG
overload per PU (UNIT,
relays SET, M)
Protection equipment
Overload relays
SIRIUS 3RB3 electronic overload relays
3RB30, 3RB31 for standard applications
■ Overview
More information
Homepage, see www.siemens.com/sirius-control Application Manual for switching devices with IE3 and IE4 motors, see
Industry Mall, see www.siemens.com/product?3RB3 https://support.industry.siemens.com/cs/ww/en/view/94770820
TIA Selection Tool Cloud (TST Cloud), see Equipment Manual, see
www.siemens.com/tstcloud/?node=ElectronicOverloadRelay https://support.industry.siemens.com/cs/ww/en/view/60298164
Conversion tool, see www.siemens.com/conversion-tool Characteristics and certificates, see
https://support.industry.siemens.com/cs/ww/en/ps/16276
IC01_00649
4 Sealable cover
5 Mechanical RESET
2 6 Pushbutton
7
4
3
Protection equipment
Overload relays
SIRIUS 3RB3 electronic overload relays
3RB30, 3RB31 for standard applications
The 3RB30/3RB31 electronic overload relays up to 115 A with
internal power supply have been designed for current-
dependent protection of loads with normal and heavy starting,
8 and to protect against excessive temperature rises due to
overload, phase asymmetry or phase failure. An overload, phase
IC01_00406
asymmetry or phase failure result in an increase of the motor
current beyond the set rated motor current. This current rise is
detected by the current transformers integrated into the devices
and evaluated by corresponding solid-state circuits which then
output a pulse to the auxiliary contacts. The auxiliary contacts
7
1 then switch off the load by means of a contactor. The break time
6 depends on the ratio between the tripping current and the
2 current setting Ie and is stored in the form of a long-term stable
5 tripping characteristic curve, see Characteristics.
3
In addition to inverse-time delayed protection of loads against
4
excessive temperature rises due to overload, phase asymmetry
and phase failure, the 3RB31 electronic overload relays also
allow internal ground-fault detection (not possible in conjunction
with contactor assemblies for star-delta (wye-delta) starting).
1 Switch position indicator and TEST function of the wiring: This provides protection of loads against incomplete ground
Indicates a trip and enables the wiring test. faults due to damage to the insulation material, moisture,
2 Trip class setting/internal ground-fault detection (only 3RB31): condensed water, etc.
Using the rotary switch you can set the required trip class and
activate the internal ground-fault detection dependent on the
The "tripped" status is signaled by means of a switch position
starting conditions. indicator. The relay is reset manually or automatically after the
recovery time has elapsed.
3 Solid-state test (device test):
Enables a test of all important device components and functions. The 3RB3 electronic overload relays are suitable for operation
4 Connecting terminals (removable terminal block for auxiliary with frequency converters.
circuits):
7
Depending on the device version, the connecting terminals are The devices are manufactured in accordance with environ-
screw terminals or spring-loaded terminals for the main and mental guidelines and contain environmentally friendly and
auxiliary circuits. reusable materials. They comply with all important worldwide
5 Selector switch for Manual/Automatic RESET: standards and approvals.
With the slide switch you can choose between Manual and Automatic
RESET. For 3RB20 and 3RB21 overload relays in sizes S6 to S10/S12,
6 Motor current setting: see page 7/114 onwards.
Setting the device to the rated motor current is easy with the large
rotary knob. Use in hazardous areas
7 A device set to Manual RESET can be reset locally by pressing the The 3RB30/3RB31 electronic overload relays are suitable for the
RESET button. On 3RB31 overload relays an electrical Remote
RESET is integrated. overload protection of motors with the following types of
protection:
8 Connection for mounting onto contactors:
Optimally adapted in electrical, mechanical and design terms to the • II (2) G[Ex e] [Ex d] [Ex px]
3RT2 contactors. The overload relay can be connected directly
using these connection pins. Stand-alone installation is possible as • II (2) D[Ex t] [Ex p]
an alternative (in conjunction with a terminal support for EC type-examination certificate for Group II, Category (2) G/D
stand-alone installation).
exists. It has the number PTB 09 ATEX 3001.
A sealable transparent cover can be optionally mounted
(accessory). It secures the motor current setting against adjustment.
Protection equipment
Overload relays
SIRIUS 3RB3 electronic overload relays
3RB30, 3RB31 for standard applications
Article number scheme
Product versions Article number
Electronic overload relays 3RB3 @ @ @ – @ @ @ @
Device type e.g. 0 = standard device, with internal supply, @
for three-phase loads
Size, rated operational current e.g. 1 = 16 A (7.5 kW) for size S00 @
and power
Version of the Automatic RESET, e.g. 6 = switchable between Manual/Automatic RESET @
electrical Remote RESET
Trip class (CLASS) e.g. 1 = CLASS 10E @
Setting range of the overload release e.g. R = 0.1 ... 0.4 A @
Connection methods e.g. B = screw terminals for main and auxiliary circuits @
Installation type e.g. 0 = for mounting onto contactors @
Example 3RB3 0 1 6 – 1 R B 0
Note:
The article number scheme shows an overview of product For your orders, please use the article numbers quoted in the
versions for better understanding of the logic behind the article selection and ordering data.
numbers.
■ Benefits
The most important features and benefits of the 3RB30/3RB31
electronic overload relays are listed in the overview table
(see "General Data" page 7/76 onwards.)
■ Application
7
Industries The 3RU21 thermal overload relay or the 3RB22/3RB23/3RB24
electronic overload relay can be used for single-phase AC
The 3RB30/3RB31 electronic overload relays are suitable for loads. For DC loads we recommend the 3RU21 thermal
customers from all industries who want to guarantee optimum overload relay.
inverse-time delayed protection of their electrical loads
(e.g. motors) under normal and heavy starting conditions Ambient conditions
(CLASS 5E to 30E), minimize project completion times,
inventories and energy consumption, and optimize plant The devices are insensitive to external influences such as
availability and maintenance management. shocks, corrosive ambient conditions, aging and temperature
fluctuations.
Application
For the temperature range from -25 to +60 °C, the 3RB30/3RB31
The 3RB30/3RB31 electronic overload relays have been electronic overload relays compensate the temperature in
designed for the protection of three-phase motors in sinusoidal accordance with IEC 60947-4-1.
50/60 Hz voltage networks. The relays are not suitable for the
protection of single-phase AC or DC loads. Use of SIRIUS protection devices in conjunction with
IE3 and IE4 motors
Note:
For the use of 3RB30/3RB31 electronic overload relays in
conjunction with highly efficient IE3 and IE4 motors, please
observe the information on dimensioning and configuring, see
Application Manual.
For more information, see page 1/8.
Protection equipment
Overload relays
SIRIUS 3RB3 electronic overload relays
3RB30, 3RB31 for standard applications
■ Technical specifications
More information
System Manual for modular system, see Equipment Manual, see
https://support.industry.siemens.com/cs/ww/en/view/60311318 https://support.industry.siemens.com/cs/ww/en/view/60298164
Configuration Manual for load feeders, see Technical specifications, see
https://support.industry.siemens.com/cs/ww/en/view/39714188 https://support.industry.siemens.com/cs/ww/en/ps/16276/td
Dimensions (W x H x D)
(overload relay with stand-alone installation
D
W
support)
• Screw terminals mm 45 x 89 x 80 45 x 97 x 94 55 x 105 x 117 70 x 106 x 124
• Spring-loaded terminals mm 45 x 102 x 80 45 x 116 x 95 55 x 105 x 117 70 x 106 x 124
General data
Tripping in the event of Overload, phase failure, and phase asymmetry
+ ground fault (for 3RB31 only)
Trip class according to IEC 60947-4-1 CLASS 3RB30: 10E, 20E;
3RB31: 5E, 10E, 20E or 30E adjustable
Phase failure sensitivity Yes
Reset and recovery
• Reset options after tripping Manual and Automatic RESET, 3RB31 has an integrated connection for electrical
Remote RESET (24 V DC)
7
• Recovery time
- For Automatic RESET Approx. 3 min
- For Manual RESET Immediately
- For Remote RESET Immediately
Features
• Display of operating state on device Yes, by means of switch position indicator slide
• TEST function Yes, test of electronics by pressing the TEST button/
test of auxiliary contacts and wiring of control circuit by actuating the switch position
indicator slide/self-monitoring
• RESET button Yes
• STOP button No
Protection and operation of explosion-proof motors
Certificate of suitability/explosion protection type according to PTB 09 ATEX 3001
ATEX Directive 2014/34/EU II (2) G[Ex e] [Ex d] [Ex px]
II (2) G[Ex t] [Ex p]
see https://support.industry.siemens.com/cs/ww/en/view/40591327
Ambient temperatures
• Storage/transport °C -40 ... +80
• Operation °C -25 ... +60
• Temperature compensation °C +60
• Permissible rated current at
- Temperature inside control cabinet 60 °C % 100
- Temperature inside control cabinet 70 °C % On request
Repeat terminals
• Coil repeat terminals Yes Not required
• Auxiliary contact repeat terminals Yes Not required
Degree of protection IP on the front according to IEC 60529
• Screw terminals/spring-loaded terminals IP20
• Straight-through transformers -- IP20
Touch protection on the front according to IEC 60529
• Screw terminals/spring-loaded terminals Finger-safe for vertical touching from the front
• Straight-through transformers -- Finger-safe for vertical touching from
the front
Shock resistance with sine according to IEC 60068-2-27 g/ms 15/11 15/11
(signaling contact 97/98 in position (signaling contact 97/98 in position
"tripped": 9 g/11 ms) "tripped": 8 g/11 ms)
Protection equipment
Overload relays
SIRIUS 3RB3 electronic overload relays
3RB30, 3RB31 for standard applications
H
Dimensions (W x H x D)
(overload relay with stand-alone installation
D
W
support)
• Screw terminals mm 45 x 89 x 80 45 x 97 x 94 55 x 105 x 117 70 x 106 x 124
• Spring-loaded terminals mm 45 x 102 x 80 45 x 116 x 95 55 x 105 x 117 70 x 106 x 124
General data (continued)
Electromagnetic compatibility (EMC) – Interference immunity
• Conductor-related interference
- Burst according to IEC 61000-4-4 kV 2 (power ports), 1 (signal port)
(corresponds to degree of severity 3)
- Surge according to IEC 61000-4-5 kV 2 (line to earth), 1 (line to line)
(corresponds to degree of severity 3)
• Electrostatic discharge according to IEC 61000-4-2 kV 8 (air discharge), 6 (contact discharge)
(corresponds to degree of severity 3)
• Field-related interference according to IEC 61000-4-3 V/m 10
(corresponds to degree of severity 3)
Electromagnetic compatibility (EMC) – Emitted interference Degree of severity B according to EN 55011 (CISPR 11)
and EN 55022 (CISPR 22)
Installation altitude above sea level m Up to 2 000
Mounting position Any
Type of mounting Direct mounting/stand-alone installation with terminal support
7
Size S00 S0 S2 S3
Main circuit
Rated insulation voltage Ui V 690 690 1 000
(pollution degree 3) 1 000 with straight-
through transformer
Rated impulse withstand voltage Uimp kV 6 6 8
8 with straight-
through transformer
Rated operational voltage Ue V 690 690 1 000
1 000 with straight-
through transformer
Type of current
• Direct current No
• Alternating current Yes, 50/60 Hz 5%
Current setting A 0.1 ... 0.4 0.1 ... 0.4 12.5 ... 50 12.5 ... 50
to to and and
A 4 ... 16 10 ... 40 20 ... 80 32 ... 115
Heavy starting See Equipment Manual
Power loss per unit (max.) W 0.1 ... 1.1 0.1 ... 4.5 0.5 ... 4.6 0.9 ... 4.6
Short-circuit protection
• With fuse without contactor See "Selection and ordering data", pages 7/102 ... 7/104
• With fuse and contactor "Short-Circuit Protection with Fuses/Motor Starter Protectors for Motor Feeders",
see Configuration Manual.
Protective separation between main and auxiliary
conducting paths
According to IEC 60947-1 (pollution degree 2)
• For systems with grounded neutral point V 690
• For systems with ungrounded neutral point V 600
Protection equipment
Overload relays
SIRIUS 3RB3 electronic overload relays
3RB30, 3RB31 for standard applications
d2 d3 = max. 19
I201_12740
Diameter of opening mm -- 15 18
1) If two different conductor cross-sections are connected to one clamping 3) If bars larger than 12 mm x 10 mm are connected, a 3RT2946-4EA2 cover
point, both cross-sections must be in the range specified. is needed to maintain the required phase clearance, see page 7/106.
2) 4)
Cable lug and busbar connection possible after removing the box terminals. If conductors larger than 25 mm2 are connected, the 3RT2946-4EA2 cover
is needed to maintain the required phase clearance, see page 7/106.
Protection equipment
Overload relays
SIRIUS 3RB3 electronic overload relays
3RB30, 3RB31 for standard applications
7
• With fuse, operational class gG A 6
Ground-fault protection (only 3RB31) The information refers to sinusoidal residual currents at 50/60 Hz.
• Tripping value I > 0.75 x Imotor
• Operating range I Lower current setting < Imotor < 3.5 x upper current setting
• Response time ttrip (in steady-state condition) s <1
Integrated electrical Remote RESET (only 3RB31)
Connecting terminals A3, A4 24 V DC, max. 200 mA for approx. 20 ms, then < 10 mA
Protective separation between auxiliary conducting paths V 300
according to IEC 60947-1
Protection equipment
Overload relays
SIRIUS 3RB3 electronic overload relays
3RB30, 3RB31 for standard applications IE3 ready IE4 ready IE3/IE4 ready
Size Rated power for Current setting value Short-circuit protection Screw terminals Spring-loaded
contactor three-phase of the inverse-time with fuse, type of terminals
7
Protection equipment
Overload relays
SIRIUS 3RB3 electronic overload relays
IE3 ready IE4 ready IE3/IE4 ready 3RB30, 3RB31 for standard applications
3RB30 electronic overload relays, CLASS 20E
Features and technical specifications: • Auxiliary contacts 1 NO + 1 NC
• Connection methods • Manual and Automatic RESET
- Sizes S00 and S0 • Switch position indicator
Main and auxiliary circuit: Either screw or spring-loaded
terminals • TEST function and self-monitoring
- Sizes S2 and S3 • Sealable covers (optional accessory)
Main circuit: Screw terminals with box terminal or as straight-
through transformer PU (UNIT, SET, M) = 1
Auxiliary circuit: Either screw or spring-loaded terminals PS* = 1 unit
PG = 41G
• Overload protection, phase failure protection and asymmetry
protection
• Internal power supply
Size Rated power for Current setting value Short-circuit protection Screw terminals Spring-loaded
contactor three-phase of the inverse-time with fuse, type of terminals
motors, rated delayed overload coordination "2",
7
value1) release operational class gG2)
Article No. Price Article No. Price
kW A A per PU per PU
Size S00
S00 Devices for mounting on contactor3)
0.04 ... 0.09 0.1 ... 0.4 4 3RB3016-2RB0 3RB3016-2RE0
0.12 ... 0.37 0.32 ... 1.25 6 3RB3016-2NB0 3RB3016-2NE0
0.37 ... 1.5 1…4 20 3RB3016-2PB0 3RB3016-2PE0
1.5 ... 5.5 3 … 12 50 3RB3016-2SB0 3RB3016-2SE0
2.2 ... 7.5 4 ... 16 50 3RB3016-2TB0 3RB3016-2TE0
Size S0
S0 Devices for mounting on contactor3)
0.04 ... 0.09 0.1 ... 0.4 4 3RB3026-2RB0 3RB3026-2RE0
0.12 ... 0.37 0.32 ... 1.25 6 3RB3026-2NB0 3RB3026-2NE0
0.37 ... 1.5 1…4 20 3RB3026-2PB0 3RB3026-2PE0
1.5 ... 5.5 3 … 12 50 3RB3026-2SB0 3RB3026-2SE0
3 ... 11 6 … 25 63 3RB3026-2QB0 3RB3026-2QE0
5.5 ... 18.5 10 ... 40 80 3RB3026-2VB0 3RB3026-2VE0
Size S2
S2 Devices with screw terminals (main current side)
and for mounting on contactor3)
7.5 ... 22 12.5 ... 50 200 3RB3036-2UB0 3RB3036-2UD0
11 ... 37 20 ... 80 250 3RB3036-2WB0 3RB3036-2WD0
Devices with straight-through transformer for stand-alone
installation
7.5 ... 22 12.5 ... 50 200 3RB3036-2UW1 3RB3036-2UX1
11 ... 37 20 ... 80 250 3RB3036-2WW1 3RB3036-2WX1
Size S3
S3 Devices with screw terminals (main current side)
and for mounting on contactor3)
7.5 ... 22 12.5 ... 50 200 3RB3046-2UB0 3RB3046-2UD0
18.5 ... 55 32 ... 115 315 3RB3046-2XB0 3RB3046-2XD0
Devices with straight-through transformer for stand-alone
installation
7.5 ... 22 12.5 ... 50 200 3RB3046-2UW1 3RB3046-2UX1
18.5 ... 55 32 ... 115 315 3RB3046-2XW1 3RB3046-2XX1
1) 3)
Guide value for 4-pole standard motors at 50 Hz 400 V AC. The actual With the appropriate terminal supports (see page 7/105), these overload
starting and rated data of the motor to be protected must be considered relays can also be installed as stand-alone units.
when selecting the units.
2) Maximum protection by fuse only for overload relays, type of coordination "2".
For fuse values in connection with contactors, see Configuration Manual.
Protection equipment
Overload relays
SIRIUS 3RB3 electronic overload relays
3RB30, 3RB31 for standard applications IE3 ready IE4 ready IE3/IE4 ready
3RB31 electronic overload relays, CLASS 5E, 10E, 20E or 30E (adjustable)
Features and technical specifications: • Internal power supply
• Connection methods • Auxiliary contacts 1 NO + 1 NC
- Sizes S00 and S0 • Manual and Automatic RESET
Main and auxiliary circuit: Either screw or spring-loaded
terminals • Electrical Remote RESET integrated
- Sizes S2 and S3 • Switch position indicator
Main circuit: Screw terminals with box terminal or as straight- • TEST function and self-monitoring
through transformer
Auxiliary circuit: Either screw or spring-loaded terminals • Sealable covers (optional accessory)
• Overload protection, phase failure protection and asymmetry PU (UNIT, SET, M) = 1
protection PS* = 1 unit
• Internal ground-fault detection (activatable) PG = 41G
Size Rated power for Current setting value Short-circuit protection Screw terminals Spring-loaded
contactor three-phase motors, of the inverse-time with fuse, type of terminals
rated value1) delayed overload coordination "2",
operational class gG2)
7
release
Article No. Price Article No. Price
kW A A per PU per PU
Size S00
S00 Devices for mounting on contactor3)
0.04 ... 0.09 0.1 ... 0.4 4 3RB3113-4RB0 3RB3113-4RE0
0.12 ... 0.37 0.32 ... 1.25 6 3RB3113-4NB0 3RB3113-4NE0
0.37 ... 1.5 1…4 20 3RB3113-4PB0 3RB3113-4PE0
1.5 ... 5.5 3 … 12 50 3RB3113-4SB0 3RB3113-4SE0
2.2 ... 7.5 4 ... 16 50 3RB3113-4TB0 3RB3113-4TE0
Size S0
S0 Devices for mounting on contactor3)
0.04 ... 0.09 0.1 ... 0.4 4 3RB3123-4RB0 3RB3123-4RE0
0.12 ... 0.37 0.32 ... 1.25 6 3RB3123-4NB0 3RB3123-4NE0
0.37 ... 1.5 1…4 20 3RB3123-4PB0 3RB3123-4PE0
1.5 ... 5.5 3 … 12 50 3RB3123-4SB0 3RB3123-4SE0
3 ... 11 6 … 25 63 3RB3123-4QB0 3RB3123-4QE0
5.5 ... 18.5 10 ... 40 80 3RB3123-4VB0 3RB3123-4VE0
Size S2
S2 Devices with screw terminals (main current side)
and for mounting on contactor3)
7.5 ... 22 12.5 ... 50 200 3RB3133-4UB0 3RB3133-4UD0
11 ... 37 20 ... 80 250 3RB3133-4WB0 3RB3133-4WD0
Devices with straight-through transformer for stand-
alone installation
7.5 ... 22 12.5 ... 50 200 3RB3133-4UW1 3RB3133-4UX1
11 ... 37 20 ... 80 250 3RB3133-4WW1 3RB3133-4WX1
Size S3
S3 Devices with screw terminals (main current side)
and for mounting on contactor3)
7.5 ... 22 12.5 ... 50 200 3RB3143-4UB0 3RB3143-4UD0
18.5 ... 55 32 ... 115 315 3RB3143-4XB0 3RB3143-4XD0
Devices with straight-through transformer for stand-
alone installation
7.5 ... 22 12.5 ... 50 200 3RB3143-4UW1 3RB3143-4UX1
18.5 ... 55 32 ... 115 315 3RB3143-4XW1 3RB3143-4XX1
1) Guide value for 4-pole standard motors at 50 Hz 400 V AC. The actual
starting and rated data of the motor to be protected must be considered
when selecting the units.
2)
Maximum protection by fuse only for overload relays, type of coordination "2".
For fuse values in connection with contactors, see Configuration Manual.
3)
With the appropriate terminal supports (see page 7/105), these overload
relays can also be installed as stand-alone units.
Protection equipment
Overload relays
SIRIUS 3RB3 electronic overload relays
Accessories
■ Overview
The following optional accessories are available for the • Cable release for resetting devices which are difficult to
3RB30/3RB31 electronic overload relays: access (for all sizes)
• Size-specific terminal support for stand-alone installation, • Sealable cover (for all sizes)
in sizes S00 and S0 also with spring-loaded terminals • Size-specific terminal covers for devices with screw terminals
• Mechanical RESET (for all sizes) (box terminals)
7
3RU2926- 3RU2926-
3AA01 3AC01
3RU2936-3AA01
3RU2946-3AA01
Mechanical RESET
Resetting plungers, holders and formers S00 ... S3 3RB3980-0A 1 1 unit 41F
3RB3980-0A
Pushbuttons with extended stroke S00 ... S3 3SU1200-0FB10-0AA0 1 1 unit 41J
(12 mm), IP65, 22 mm
3SU1200-0FB10-0AA0
Extension plungers S00 ... S3 3SU1900-0KG10-0AA0 1 1 unit 41J
For compensation of the distance between
the pushbutton and the resetting plunger of
the relay
3SU1900-0KG10-0AA0
Protection equipment
Overload relays
SIRIUS 3RB3 electronic overload relays
Accessories
3RB3980-0B
Sealable covers
For covering the setting knobs S00 ... S3 3RB3984-0 1 1 unit 41F
3RB3984-0
Terminal covers
Covers for contactors with cable lug and S3 3RT1946-4EA1 1 1 unit 41B
busbar connections
For complying with the phase clearances
and as touch protection if box terminal is
removed
7
3RT1946-4EA1
Covers for devices with screw terminals Screw terminals
(box terminals)
Additional touch protection for fastening to the
box terminals
• Main current level S2 3RT2936-4EA2 1 1 unit 41B
3RT2936-4EA2
S3 3RT2946-4EA2 1 1 unit 41B
General accessories
Version Size Color For Article No. Price PU PS* PG
overload per PU (UNIT,
relays SET, M)
Protection equipment
Overload relays
SIRIUS 3RB2 electronic overload relays
3RB20, 3RB21 for standard applications
■ Overview
More information
Homepage, see www.siemens.com/sirius-control Application Manual for switching devices with IE3 and IE4 motors, see
Industry Mall, see www.siemens.com/product?3RB2 https://support.industry.siemens.com/cs/ww/en/view/94770820
Conversion tool, see www.siemens.com/conversion-tool Equipment Manual, see
https://support.industry.siemens.com/cs/ww/en/view/60298164
Characteristics and certificates, see
https://support.industry.siemens.com/cs/ww/en/ps/16278
IC01_00650a
7 Pushbutton
7
4 5
Protection equipment
Overload relays
SIRIUS 3RB2 electronic overload relays
3RB20, 3RB21 for standard applications
The 3RB20 and 3RB21 electronic overload relays up to 630 A
with internal power supply have been designed for inverse-time
delayed protection of loads with normal and heavy starting
8 (see Equipment Manual) against excessive temperature rises
IC01_00335b
due to overload, phase asymmetry or phase failure.
7 An overload, phase asymmetry or phase failure result in an
1 increase of the motor current beyond the set rated motor current.
6 This current rise is detected by the current transformers
2 integrated into the devices and evaluated by corresponding
solid-state circuits which then output a pulse to the auxiliary
5
3 contacts. The auxiliary contacts then switch off the load by
means of a contactor. The break time depends on the ratio
4
between the tripping current and the current setting Ie and is
stored in the form of a long-term stable tripping characteristic
curve, see Characteristics.
In addition to inverse-time delayed protection of loads against
1 Switch position indicator and TEST function of the wiring: excessive temperature rises due to overload, phase asymmetry
Indicates a trip and enables the wiring test. and phase failure, the 3RB21 electronic overload relays also
2 Trip class setting/internal ground-fault detection (only 3RB21): allow internal ground-fault detection (not possible in conjunction
Using the rotary switch you can set the required trip class and with contactor assemblies for star-delta (wye-delta) starting).
activate the internal ground-fault detection dependent on the
starting conditions. This provides protection of loads against incomplete ground
faults due to damage to the insulation material, moisture,
3 Solid-state test (device test):
Enables a test of all important device components and functions. condensed water, etc.
4 Connecting terminals (removable terminal block for auxiliary circuits): The "tripped" status is signaled by means of a switch position
The generously sized terminals permit connection of two indicator. The relay is reset manually or automatically after the
conductors with different cross-sections for the main and auxiliary
circuits. The auxiliary circuit can be connected with screw terminals recovery time has elapsed.
and alternatively with spring-loaded terminals.
The 3RB2 electronic overload relays are suitable for operation
7
5 Selector switch for Manual/Automatic RESET: with frequency converters, see Equipment Manual.
With the slide switch you can choose between Manual and
Automatic RESET. The devices are manufactured in accordance with environ-
6 Motor current setting: mental guidelines and contain environmentally friendly and
Setting the device to the rated motor current is easy with the large reusable materials. They comply with all important worldwide
rotary knob.
standards and approvals.
7 A device set to Manual RESET can be reset locally by pressing the
RESET button. On the 3RB21 overload relay a solid-state Remote For 3RB30 and 3RB31 overload relays sizes S00 to S3,
RESET is integrated. see page 7/102 onwards.
_ Connection for mounting onto contactors:
Optimally adapted in electrical, mechanical and design terms to the Use in hazardous areas
3RT1 contactors. These connecting pins can be used for direct
mounting of the overload relay to the contactor. Stand-alone The 3RB20/3RB21 electronic overload relays are suitable for
installation is possible as an alternative (partly in conjunction with a the overload protection of motors with the following types of
terminal support for stand-alone installation). protection:
• II (2) G[Ex e] [Ex d] [Ex px]
SIRIUS 3RB2153-4FW2 electronic overload relays
• II (2) D[Ex t] [Ex p]
EC type-examination certificate for Group II, Category (2)
G/D exists. It has the number PTB 06 ATEX 3001.
Protection equipment
Overload relays
SIRIUS 3RB2 electronic overload relays
3RB20, 3RB21 for standard applications
Article number scheme
Product versions Article number
Electronic overload relays 3RB2 @ @ @ – @ @ @ @
Device type e.g. 0 = standard device, with internal supply, @
for three-phase loads
Size, rated operational current e.g. 5 = 200 A (90 kW) for size S6 @
and power
Version of the Automatic RESET, e.g. 6 = switchable between Manual/Automatic @
electrical Remote RESET RESET
Trip class (CLASS) e.g. 1 = CLASS 10E @
Setting range of the overload release e.g. F = 5 ... 200 A @
Connection methods e.g. C = busbar connections main circuit; screw @
terminals auxiliary circuit
Installation type e.g. 2 = mounting on contactor and stand-alone @
installation
Example 3RB2 0 5 6 – 1 F C 2
Note:
The article number scheme shows an overview of product For your orders, please use the article numbers quoted in the
versions for better understanding of the logic behind the article selection and ordering data.
numbers.
■ Benefits
The most important features and benefits of the 3RB20/3RB21
electronic overload relays are listed in the overview table
(see "General data", page 7/76 onwards).
7
■ Application
Industries Ambient conditions
The 3RB20 and 3RB21 electronic overload relays are suitable for The devices are insensitive to external influences such as
customers from all industries who want to guarantee optimum shocks, corrosive ambient conditions, aging and temperature
inverse-time delayed protection of their electrical loads fluctuations.
(e.g. motors) under normal and heavy starting conditions
(CLASS 5E to 30E), minimize project completion times, For the temperature range from -25 to +60 °C, the 3RB20 and
inventories and energy consumption, and optimize plant 3RB21 electronic overload relays compensate the temperature
availability and maintenance management. in accordance with IEC 60947-4-1.
For the 3RB20 and 3RB21 electronic overload relays with the
Application sizes S6, S10 and S12, the upper set value of the setting range
The 3RB20 and 3RB21 electronic overload relays have been must be reduced for ambient temperatures > 50 °C by a certain
designed for the protection of three-phase motors in sinusoidal factor.
50/60 Hz voltage networks. The relays are not suitable for the
protection of single-phase AC or DC loads. Use of SIRIUS protection devices in conjunction with
IE3 and IE4 motors
The 3RU21 thermal overload relays or the 3RB22 to 3RB24
electronic overload relays can be used for single-phase Note:
AC loads. For DC loads we recommend the 3RU21 thermal For the use of 3RB20 and 3RB21 electronic overload relays in
overload relay. conjunction with highly efficient IE3 and IE4 motors, please
observe the information on dimensioning and configuring, see
Application Manual.
For more information, see page 1/8.
Protection equipment
Overload relays
SIRIUS 3RB2 electronic overload relays
3RB20, 3RB21 for standard applications
■ Technical specifications
More information
Configuration Manual for load feeders, see Technical specifications, see
https://support.industry.siemens.com/cs/ww/en/view/39714188 https://support.industry.siemens.com/cs/ww/en/ps/16278/td
Equipment Manual, see
https://support.industry.siemens.com/cs/ww/en/view/60298164
Protection equipment
Overload relays
SIRIUS 3RB2 electronic overload relays
3RB20, 3RB21 for standard applications
H
Dimensions (W x H x D) mm 120 x 119 x 155 145 x 147 x 156
(overload relay with stand-alone installation
D
W
support)
General data (continued)
Shock resistance with sine according to IEC 60068-2-27 g/ms 15/11 (signaling contact 97/98 in position "tripped": 4 g/11 ms
Electromagnetic compatibility (EMC) – Interference immunity
• Conductor-related interference
- Burst according to IEC 61000-4-4 kV 2 (power ports), 1 (signal port)
(corresponds to degree of severity 3)
- Surge according to IEC 61000-4-5 kV 2 (line to earth), 1 (line to line)
(corresponds to degree of severity 3)
• Electrostatic discharge according to IEC 61000-4-2 kV 8 (air discharge), 6 (contact discharge)
(corresponds to degree of severity 3)
• Field-related interference according to IEC 61000-4-3 V/m 10
(corresponds to degree of severity 3)
Electromagnetic compatibility (EMC) – Emitted interference Degree of severity B according to EN 55011 (CISPR 11) and EN 55022
(CISPR 22)
Installation altitude above sea level m Up to 2 000
Mounting position Any
Type of mounting Direct mounting/stand-alone installation
Protection equipment
Overload relays
SIRIUS 3RB2 electronic overload relays
3RB20, 3RB21 for standard applications
Protection equipment
Overload relays
SIRIUS 3RB2 electronic overload relays
3RB20, 3RB21 for standard applications
7
- 250 V A 0.11
• Conventional thermal current Ith A 5
• Contact reliability (suitability for PLC control; 17 V, 5 mA) Yes
Short-circuit protection
• With fuse, operational class gG A 6
Ground-fault protection (only 3RB21) The information refers to sinusoidal residual currents at 50/60 Hz.
• Tripping value I > 0.75 × Imotor
• Operating range I Lower current setting < Imotor < 3.5 × upper current setting
• Response time ttrip (in steady-state condition) s <1
Integrated electrical Remote RESET (only 3RB21)
Connecting terminals A3, A4 24 V DC, 100 mA, 2.4 W short-term
Protective separation between auxiliary conducting paths V 300
According to IEC 60947-1
CSA, UL and UR rated data
Auxiliary circuit – Switching capacity B300, R300
Conductor cross-sections of the auxiliary circuit
Connection type Screw terminals
Protection equipment
Overload relays
SIRIUS 3RB2 electronic overload relays
3RB20, 3RB21 for standard applications IE3 ready IE4 ready IE3/IE4 ready
3RB2056-1FW2 3RB2066-1MF2
7
Size contactor Rated power for Current setting value Short-circuit Screw terminals Spring-loaded
three-phase motors, of the inverse-time protection with fuse, (on auxiliary current terminals
1)
rated value delayed overload type of side) (on auxiliary current
release coordination "2", side)
operational
class gG2)
Article No. Price Article No. Price
kW A A per PU per PU
Size S6
Devices with busbar connection,
for mounting onto contactor and stand-alone installation
S6 30 ... 90 50 … 200 315 3RB2056-1FC2 3RB2056-1FF2
Devices with straight-through transformer,
for mounting on contactor and stand-alone installation
For mounting 30 ... 90 50 … 200 315 3RB2056-1FW2 3RB2056-1FX2
on S6 contac-
tors with box
terminals
Size S10/S12
Devices with busbar connection,
for mounting onto contactor and stand-alone installation
S10/S12 30 ... 132 55 … 250 400 3RB2066-1GC2 3RB2066-1GF2
and size 14 90 ... 355 160 … 630 800 3RB2066-1MC2 3RB2066-1MF2
(3TF68/
3TF69)3)
1)
Guide value for 4-pole standard motors at 50 Hz 400 V AC. The actual
starting and rated data of the motor to be protected must be considered
when selecting the units.
2)
Maximum protection by fuse only for overload relays, type of
coordination "2". For fuse values in connection with contactors,
see Configuration Manual.
3) For 3TF68/3TF69 contactors, direct mounting is not possible.
Protection equipment
Overload relays
SIRIUS 3RB2 electronic overload relays
IE3 ready IE4 ready IE3/IE4 ready 3RB20, 3RB21 for standard applications
3RB20 electronic overload relays for mounting on contactors and stand-alone installation, CLASS 20E
Features and technical specifications:
• Connection methods • Overload protection, phase failure protection and asymmetry
- Size S6 protection
Main circuit: With busbar connection or as straight-through • Internal power supply
transformer (an appropriate connection kit with screws,
spring washers and nuts is enclosed with the devices with • Auxiliary contacts 1 NO + 1 NC
busbar connection) • Manual and Automatic RESET
Auxiliary circuit: Either screw or spring-loaded terminals • Switch position indicator
- Sizes S10/S12
Main circuit: With busbar connection (an appropriate • TEST function and self-monitoring
connection kit with screws, spring washers and nuts PU (UNIT, SET, M) = 1
is enclosed) PS* = 1 unit
Auxiliary circuit: Either screw or spring-loaded terminals PG = 41G
3RB2056-2FW2 3RB2066-2MF2
Size contactor Rated power for Current setting value Short-circuit Screw terminals Spring-loaded
three-phase motors, of the inverse-time protection with fuse, (on auxiliary current terminals
rated value1) delayed overload type of side) (on auxiliary current
7
release coordination "2", side)
operational
class gG2)
Article No. Price Article No. Price
kW A A per PU per PU
Size S6
Devices with busbar connection,
for mounting onto contactor and stand-alone installation
S6 30 ... 90 50 … 200 315 3RB2056-2FC2 3RB2056-2FF2
Devices with straight-through transformer,
for mounting on contactor and stand-alone installation
For mounting 30 ... 90 50 … 200 315 3RB2056-2FW2 3RB2056-2FX2
on S6 contac-
tors with box
terminals
Size S10/S122)
Devices with busbar connection,
for mounting onto contactor and stand-alone installation
S10/S12 30 ... 132 55 … 250 400 3RB2066-2GC2 3RB2066-2GF2
and size 14 90 ... 355 160 … 630 800 3RB2066-2MC2 3RB2066-2MF2
(3TF68/
3TF69)3)
1)
Guide value for 4-pole standard motors at 50 Hz 400 V AC. The actual
starting and rated data of the motor to be protected must be considered
when selecting the units.
2)
Maximum protection by fuse only for overload relays, type of
coordination "2". For fuse values in connection with contactors,
see Configuration Manual.
3) For 3TF68/3TF69 contactors, direct mounting is not possible.
Protection equipment
Overload relays
SIRIUS 3RB2 electronic overload relays
3RB20, 3RB21 for standard applications IE3 ready IE4 ready IE3/IE4 ready
3RB21 electronic overload relays for mounting on contactors and stand-alone installation, CLASS 5E, 10E, 20E and 30E
adjustable
Features and technical specifications:
• Connection methods • Overload protection, phase failure protection and asymmetry
- Size S6 protection
Main circuit: With busbar connection or as straight-through • Internal ground-fault detection (activatable)
transformer (an appropriate connection kit with screws,
spring washers and nuts is enclosed with the devices with • Internal power supply
busbar connection) • Auxiliary contacts 1 NO + 1 NC
Auxiliary circuit: Either screw or spring-loaded terminals • Manual and Automatic RESET
- Sizes S10/S12
Main circuit: With busbar connection (an appropriate • Electrical Remote RESET integrated
connection kit with screws, spring washers and nuts is • Switch position indicator
enclosed) • TEST function and self-monitoring
Auxiliary circuit: Either screw or spring-loaded terminals
PU (UNIT, SET, M) = 1
PS* = 1 unit
PG = 41G
7
3RB2153-4FW2 3RB2163-4MF2
Size contactor Rated power for Current setting value Short-circuit Screw terminals Spring-loaded
three-phase motors, of the inverse-time protection with fuse, (on auxiliary current terminals
rated value1) delayed overload type of side) (on auxiliary current
release coordination "2", side)
operational
class gG2)
Article No. Price Article No. Price
kW A A per PU per PU
Size S6
Devices with busbar connection,
for mounting onto contactor and stand-alone installation
S6 30 ... 90 50 … 200 315 3RB2153-4FC2 3RB2153-4FF2
Devices with straight-through transformer,
for mounting on contactor and stand-alone installation
For mounting 30 ... 90 50 … 200 315 3RB2153-4FW2 3RB2153-4FX2
on S6
contactors with
box terminals
Size S10/S122)
Devices with busbar connection,
for mounting onto contactor and stand-alone installation
S10/S12 30 ... 132 55 … 250 400 3RB2163-4GC2 3RB2163-4GF2
and size 14 90 ... 355 160 … 630 800 3RB2163-4MC2 3RB2163-4MF2
(3TF68/
3TF69)3)
1)
Guide value for 4-pole standard motors at 50 Hz 400 V AC. The actual
starting and rated data of the motor to be protected must be considered
when selecting the units.
2)
Maximum protection by fuse only for overload relays, type of
coordination "2". For fuse values in connection with contactors,
see Configuration Manual.
3) For 3TF68/3TF69 contactors, direct mounting is not possible.
Protection equipment
Overload relays
SIRIUS 3RB2 electronic overload relays
Accessories for 3RB20, 3RB21
■ Overview
Overload relays for standard applications • Cable release for resetting devices which are difficult to
access (for all sizes)
The following optional accessories are available for the
3RB20 and 3RB21 electronic overload relays: • Sealable cover (for all sizes)
• Mechanical RESET (for all sizes) • Terminal covers for sizes S6 and S10/S12
• Box terminal blocks for sizes S6 and S10/S12
Mechanical RESET
Resetting plungers, holders and formers S6 ... S12 3RB3980-0A 1 1 unit 41F
3RB3980-0A
Pushbuttons with extended stroke S6 ... S12 3SU1200-0FB10-0AA0 1 1 unit 41J
(12 mm), IP65, 22 mm
7
3SU1200-0FB10-0AA0
Extension plungers S6 ... S12 3SU1900-0KG10-0AA0 1 1 unit 41J
For compensation of the distance between
the pushbutton and the resetting plunger of
the relay
3SU1900-0KG10-0AA0
Cable releases with holder for RESET
For 6.5 mm holes in the control panel;
max. control panel thickness 8 mm
• Length 400 mm S6 ... S12 3RB3980-0B 1 1 unit 41F
• Length 600 mm S6 ... S12 3RB3980-0C 1 1 unit 41F
3RU3980-0B
Sealable covers
For covering the setting knobs S6 ... S12 3RB3984-0 1 1 unit 41F
3RB3984-0
Terminal covers
Covers for cable lugs and busbar connections
• Length 100 mm S6 3RT1956-4EA1 1 1 unit 41B
• Length 120 mm S10/S12 3RT1966-4EA1 1 1 unit 41B
Covers for box terminals
• Length 25 mm S6 3RT1956-4EA2 1 1 unit 41B
• Length 30 mm S10/S12 3RT1966-4EA2 1 1 unit 41B
3RT1956-4EA1 Covers for screw terminals S6 3RT1956-4EA3 1 1 unit 41B
Between contactor and overload relay, without S10/S12 3RT1966-4EA3 1 1 unit 41B
box terminals (1 unit required per combination)
3RT1956-4EA2
Box terminal blocks
For round and ribbon cables
• Up to 70 mm2 S61) 3RT1955-4G 1 1 unit 41B
• Up to 120 mm2 S6 3RT1956-4G 1 1 unit 41B
• Up to 240 mm2 S10/S12 3RT1966-4G 1 1 unit 41B
3RT1955-4G
1)
In the scope of supply for 3RT1054-1 contactors (55 kW).
Protection equipment
Overload relays
SIRIUS 3RB2 electronic overload relays
Accessories for 3RB20, 3RB21
General accessories
Version Size Color For Article No. Price PU PS* PG
overload per PU (UNIT,
relays SET, M)
3RT2900-1SB20
1) PC labeling system for individual inscription
of unit labeling plates available from:
murrplastik Systemtechnik GmbH
(see page 16/18).
7
Protection equipment
Overload relays
SIRIUS 3RB2 electronic overload relays
3RB22, 3RB23 for high-feature applications
■ Overview
More information
Homepage, see www.siemens.com/sirius-control Application Manual for switching devices with IE3 and IE4 motors, see
Industry Mall, see www.siemens.com/product?3RB2 https://support.industry.siemens.com/cs/ww/en/view/94770820
Operating Instructions, see
https://support.industry.siemens.com/cs/ww/en/view/21833251
Characteristics and certificates, see
https://support.industry.siemens.com/cs/ww/en/ps/16280
7
2 Motor current and trip class setting: 3RB23 electronic overload relays also allow direct temperature
Setting the device to the motor current and to the required trip class monitoring of the motor windings (full motor protection!) by
dependent on the starting conditions is easy with the two rotary
switches. connection with broken-wire interlock of a PTC sensor circuit.
With this temperature-dependent protection, the loads can be
3 Connecting terminals (removable terminal block): protected against overheating caused, for example, indirectly
The generously sized terminals permit connection of two conductors by reduced coolant flow and which cannot be detected by
with different cross-sections for the auxiliary, control and sensor
circuits. Connection is possible with screw terminals and alterna- means of the current alone. In the event of overheating, the
tively with spring-loaded terminals. devices switch off the contactor, and thus the load, by means of
4 Test/RESET button: the auxiliary contacts. The "tripped" status is signaled by means
Enables testing of all important device components and functions, of a continuously illuminated "THERMISTOR" LED.
plus resetting of the device after a trip when Manual RESET is
selected. To protect the loads against incomplete ground faults due to
5 Selector switch for Manual/Automatic RESET: damage to the insulation, humidity, condensed water, etc., the
With this switch you can choose between Manual and Automatic 3RB22 and 3RB23 electronic overload relays offer the possibility
RESET. of internal ground fault monitoring in conjunction with a function
expansion module (for details, see Operating Instructions, not
6 Red LED "OVERLOAD":
A continuous red light signals an active overload trip; a flickering red possible in conjunction with contactor assemblies for star-delta
light signals an imminent trip (overload warning). (wye-delta) starting). In the event of a ground fault, the 3RB22
7 Red LED "THERMISTOR": and 3RB23 relays trip instantaneously.
A continuous red light signals an active thermistor trip.
The "tripped" status is signaled by means of a continuous red
8 Red LED "GND FAULT": "Ground Fault" LED. Signaling through auxiliary contacts is also
A continuous red light signals a ground-fault tripping. possible.
9 Green LED "READY": After tripping due to overload, phase asymmetry, phase failure,
A continuous green light signals that the device is working correctly.
thermistor or ground-fault tripping, the relay is reset manually or
automatically after the recovery time has elapsed.
SIRIUS 3RB22 and 3RB23 evaluation modules
In conjunction with a corresponding function expansion module,
The 3RB22 and 3RB23 electronic overload relays up to 630 A the motor current measured by the microprocessor can be
(up to 820 A possible in combination with a series transformer) output in the form of a DC 4 to 20 mA analog signal for operating
are from a modular system and comprise an evaluation unit, a rotary coil instruments or for feeding into analog inputs of
current measuring module and a connecting cable. The 3RB22 programmable logic controllers.
overload relays (with monostable auxiliary contacts) and the
3RB23 overload relays (with bistable auxiliary contacts) are
supplied from an external voltage.
They have been designed for inverse-time delayed protection
of loads with normal and heavy starting against excessive
temperature rises due to overload, phase asymmetry or phase
failure. An overload, phase asymmetry or phase failure result in
an increase of the motor current beyond the set rated motor
current.
Protection equipment
Overload relays
SIRIUS 3RB2 electronic overload relays
3RB22, 3RB23 for high-feature applications
With an additional AS-Interface analog module the current Use in hazardous areas
values can also be transferred via the AS-i bus system.
The 3RB22 electronic overload relays (monostable) with the
The 3RB2 electronic overload relays are suitable for operation 3RB29 current measuring module are suitable for the overload
with frequency converters. protection of explosion-proof motors.
The devices are manufactured in accordance with environ- EC type-examination certificate for Category (2) G/D exists.
mental guidelines and contain environmentally friendly and It has the number PTB 05 ATEX 3022.
reusable materials. They comply with all important worldwide
standards and approvals.
Article number scheme
Product versions Article number
Electronic overload relays 3RB2 @ @ @ – @ @ @ @
Device type e.g. 2 = monostable device for high-feature applications, @
supplied from external source, for three-phase loads
Size, rated operational current e.g. 8 = irrespective of size and current @
and power
Version of the Automatic RESET, e.g. 3 = switchable between Manual/Automatic RESET, @
electrical Remote RESET with integral electrical Remote RESET
Trip class (CLASS) e.g. 4 = CLASS 5E, 10E, 20E, 30E (adjustable) @
Setting range of the overload release e.g. A = none specified @
Connection methods e.g. A = screw terminals for auxiliary, control and main circuits @
Installation type e.g. 1 = stand-alone installation @
Example 3RB2 2 8 3 – 4 A A 1
Note:
The article number scheme shows an overview of product For your orders, please use the article numbers quoted in the
7
versions for better understanding of the logic behind the article selection and ordering data.
numbers.
■ Benefits
The most important features and benefits of the 3RB22 and
3RB23 electronic overload relays are listed in the overview table,
see "General data", page 7/76 onwards.
■ Application
Industries Ambient conditions
The 3RB22 and 3RB23 electronic overload relays are suitable for The devices are insensitive to external influences such as
customers from all industries who want to guarantee optimum shocks, corrosive ambient conditions, aging and temperature
inverse-time delayed and temperature-dependent protection of fluctuations.
their electrical loads (e.g. motors) under normal and heavy
starting conditions (CLASS 5 to CLASS 30), minimize project For the temperature range from -25 to +60 °C, the 3RB22 and
completion times, inventories and power consumption, and 3RB23 electronic overload relays compensate the temperature
optimize plant availability and maintenance management. in accordance with IEC 60947-4-1.
Configuration notes for use of the devices below -25 °C or above
Application +60 °C on request.
The 3RB22 and 3RB23 devices have been designed for the
protection of three-phase asynchronous and single-phase Use of SIRIUS protection devices in conjunction with
AC motors. IE3 and IE4 motors
Protection equipment
Overload relays
SIRIUS 3RB2 electronic overload relays
3RB22, 3RB23 for high-feature applications
■ Technical specifications
More information
Application Manual for switching devices with IE3 and IE4 motors, see Operating Instructions, see
https://support.industry.siemens.com/cs/ww/en/view/94770820 https://support.industry.siemens.com/cs/ww/en/view/21833251
Configuration Manual for load feeders, see Technical specifications, see
https://support.industry.siemens.com/cs/ww/en/view/39714188 https://support.industry.siemens.com/cs/ww/en/ps/16280/td
D
W
General data
Tripping in the event of Overload, phase failure and phase asymmetry (> 40% according to NEMA),
+ ground fault (with corresponding function expansion module) and activation of the
thermistor motor protection (with closed PTC sensor circuit)
Trip class according to IEC 60947-4-1 CLASS 5E, 10E, 20E and 30E adjustable
Phase failure sensitivity Yes
Overload warning Yes, from 1.125 × Ie for symmetrical loads
and from 0.85 × Ie for asymmetrical loads
Reset and recovery
• Reset options after tripping Manual, Automatic and Remote RESET
• Recovery time
- For Automatic RESET min. - For tripping due to overcurrent: 3 (stored permanently)
7
- For tripping by thermistor: time until the motor temperature has fallen 5 K
below the response temperature
- For tripping due to a ground fault: no Automatic RESET
- For Manual RESET min. - For tripping due to overcurrent: 3 (stored permanently)
- For tripping by thermistor: time until the motor temperature has fallen 5 K
below the response temperature
- For tripping due to a ground fault: immediately
- For Remote RESET min. - For tripping due to overcurrent: 3 (stored permanently)
- For tripping by thermistor: time until the motor temperature has fallen 5 K
below the response temperature
- For tripping due to a ground fault: immediately
Features
• Display of operating state on device Yes, with four LEDs:
- Green LED "Ready"
- Red LED "Ground Fault"
- Red LED "Thermistor"
- Red LED "Overload"
• TEST function Yes, test of LEDs, electronics, auxiliary contacts and wiring of control circuit by
pressing the button TEST/RESET/self-monitoring
• RESET button Yes, with the TEST/RESET button
• STOP button No
Protection and operation of explosion-proof motors
Certificate of suitability/explosion protection type according to PTB 05 ATEX 3022 II (2) GD --
ATEX Directive 2014/34/EU see
https://support.automation.siemens.com/WW/view/en/23115758
Ambient temperatures
• Storage/transport °C -40 ... +80
• Operation °C -25 ... +60
• Temperature compensation °C +60
• Permissible rated current
- Temperature inside control cabinet 60 °C % 100
- Temperature inside control cabinet 70 °C % On request
Degree of protection IP on the front according to IEC 60529 IP20
Touch protection on the front according to IEC 60529 Finger-safe for vertical touching from the front
Shock resistance with sine according to IEC 60068-2-27 g/ms 15/11
Protection equipment
Overload relays
SIRIUS 3RB2 electronic overload relays
3RB22, 3RB23 for high-feature applications
H
Dimensions of evaluation modules mm 45 x 111 x 95
(W x H x D)
D
W
Auxiliary circuit
Number of NO contacts 2
Number of NC contacts 2
Number of CO contacts --
Auxiliary contacts – Assignment • Alternative 1
- 1 NO for the signal "tripped by overload and/or thermistor",
- 1 NC for disconnecting the contactor,
- 1 NO for the signal "tripped by ground fault",
- 1 NC for disconnecting the contactor
or1)
• Alternative 2
- 1 NO for the signal "tripped by overload and/or thermistor and/or ground fault",
- 1 NC for disconnecting the contactor,
- 1 NO for overload warning,
- 1 NC for disconnecting the contactor
Rated insulation voltage Ui (pollution degree 3) V 300
Rated impulse withstand voltage Uimp kV 4
Auxiliary contacts – Contact rating
• NC, NO contact with alternating current AC-14/AC-15,
rated operational current Ie at Ue
- 24 V A 6
- 120 V A 6
- 125 V A 6
- 250 V A 3
• NC, NO contacts with direct current DC-13,
rated operational current Ie at Ue
- 24 V A 2
- 60 V A 0.55
- 110 V A 0.3
- 125 V A 0.3
- 250 V A 0.2
• Conventional thermal current Ith A 5
• Contact reliability Yes
(suitability for PLC control; 17 V, 5 mA)
Short-circuit protection
• With fuse, operational class gG A 6
• With miniature circuit breaker, C characteristic A 1.6
Protective separation between auxiliary conducting paths V 300
According to IEC 60947-1
CSA, UL and UR rated data
Auxiliary circuit – Switching capacity B300, R300
1) The assignment of auxiliary contacts may be influenced by function
expansion modules.
Protection equipment
Overload relays
SIRIUS 3RB2 electronic overload relays
3RB22, 3RB23 for high-feature applications
7
- For 2.0 × Ie < Imotor < 8.0 × Ie > 0.15 x Imotor
• Response time ttrip ms 500 ... 1 000
Analog output1)2)
Rated values
• Output signal mA 4 ... 20
• Measuring range 0 ... 1.25 x Ie
4 mA corresponds to 0 x Ie
16.8 mA corresponds to 1.0 x Ie
20 mA corresponds to 1.25 x Ie
• Load, max. 100
Conductor cross-sections for the auxiliary, control and
sensor circuits as well as the analog output
Connection type Screw terminals
Protection equipment
Overload relays
SIRIUS 3RB2 electronic overload relays
3RB22, 3RB23 for high-feature applications
Functions of the 3RB22 and 3RB23 evaluation modules in combination with the 3RB2985 function expansion modules
Evaluation modules With function Basic functions Inputs
expansion module
A1/A2 T1/T2 Y1/Y2
3RB2283-4AA1 -- Inverse-time delayed protection, Power supply Connection for Electrical
3RB2283-4AC1 temperature-dependent protection, 24 ... 240 V AC/DC PTC sensor Remote RESET
electrical Remote RESET,
3RB2383-4AA1 overload warning
3RB2383-4AC1 3RB2985-2CA1 Inverse-time delayed protection, Power supply Connection for Electrical
temperature-dependent protection, 24 ... 240 V AC/DC PTC sensor Remote RESET
internal ground-fault detection,
electrical Remote RESET,
overload warning
3RB2985-2CB1 Inverse-time delayed protection, Power supply Connection for Electrical
temperature-dependent protection, 24 ... 240 V AC/DC PTC sensor Remote RESET
internal ground-fault detection,
electrical Remote RESET,
ground-fault signal
3RB2985-2AA0 Inverse-time delayed protection, Power supply Connection for Electrical
temperature-dependent protection, 24 ... 240 V AC/DC PTC sensor Remote RESET
electrical Remote RESET,
overload warning, analog output
3RB2985-2AA1 Inverse-time delayed protection, Power supply Connection for Electrical
temperature-dependent protection, 24 ... 240 V AC/DC PTC sensor Remote RESET
internal ground-fault detection,
electrical Remote RESET,
overload warning, analog output
3RB2985-2AB1 Inverse-time delayed protection, Power supply Connection for Electrical
temperature-dependent protection, 24 ... 240 V AC/DC PTC sensor Remote RESET
internal ground-fault detection,
electrical Remote RESET,
7
Protection equipment
Overload relays
SIRIUS 3RB2 electronic overload relays
IE3 ready IE4 ready IE3/IE4 ready 3RB22, 3RB23 for high-feature applications
3RB22 and 3RB23 electronic overload relays (evaluation modules) for full motor protection for stand-alone installation,
CLASS 5E, 10E, 20E and 30E (adjustable)
Type 3RB2283-4A.1, 3RB2383-4A.1
Features and technical specifications
Overload protection, phase failure protection and asymmetry protection ✓
Supplied from an external source ✓
24 ... 240 V AC/DC
Auxiliary contacts ✓
2 NO + 2 NC
Electrical Remote RESET integrated ✓
Four LEDs for operating and status displays ✓
TEST function and self-monitoring ✓
Internal ground-fault detection ✓
(with function expansion module)
Screw or spring-loaded terminals for auxiliary, control and sensor circuits ✓
Input for PTC sensor circuit ✓
Analog output ✓
(with function expansion module)
✓ Available
7
3RB2283-4AA1 3RB2283-4AC1
Size Version Screw terminals Spring-loaded
contactor terminals
Article No. Price Article No. Price
per PU per PU
Evaluation modules
S00 ... S12 Monostable 3RB2283-4AA1 3RB2283-4AC1
Bistable 3RB2383-4AA1 3RB2383-4AC1
Protection equipment
Overload relays
SIRIUS 3RB2 electronic overload relays
3RB22, 3RB23 for high-feature applications IE3 ready IE4 ready IE3/IE4 ready
Function expansion modules for 3RB22 and 3RB23 overload relays (evaluation modules)
Size Version For Article No. Price PU PS* PG
contactor overload per PU (UNIT,
relays SET, M)
residual currents at 50/60 Hz: module must not supply current to the analog output of the
- With a motor current of between 0.3 and 2 times the current setting Ie, the 3RB22/3RB23 relay.
unit will trip at a ground-fault current equal to 30% of the current setting.
- With a motor current of between 2 and 8 times the current setting Ie, the
unit will trip at a ground-fault current equal to 15% of the motor current.
- The response delay amounts to between 0.5 s and 1 s.
Protection equipment
Overload relays
SIRIUS 3RB2 electronic overload relays
3RB24 for IO-Link for high-feature applications
■ Overview
More information
Homepage, see www.siemens.com/sirius-control Application Manual for switching devices with IE3 and IE4 motors, see
Industry Mall, see www.siemens.com/product?3RB2 https://support.industry.siemens.com/cs/ww/en/view/94770820
Equipment Manual, see
https://support.industry.siemens.com/cs/ww/en/view/46165627
Certificates, see https://support.industry.siemens.com/cs/ww/en/ps/16281/cert
NSB0_02180c
This current rise is detected by means of the current measuring
module (see page 7/137) and electronically evaluated by the
evaluation module which is connected to it. The evaluation
electronics sends a signal to the auxiliary contacts. The auxiliary
contacts then switch off the load by means of a contactor.
The break time depends on the ratio between the tripping
current and the current setting Ie and is stored in the form of
a long-term stable tripping characteristic curve, see Equipment
Manual. The "tripped" status is signaled by means of
a continuously illuminated red "OVERLOAD" LED and also
reported as a group fault via IO-Link.
The LED indicates imminent tripping of the relay due to overload,
Plug-in point for operator panel: phase asymmetry or phase failure by flickering when the limit
enables connection of the 3RA6935-0A operator panel. current has been violated. This warning can also be reported to
Motor current and trip class setting: the higher-level PLC via IO-Link at the 3RB24 overload relays.
Setting the device to the motor current and to the required trip
7
class dependent on the starting conditions is easy with the two In addition to the described inverse-time delayed protection of
rotary switches. loads against excessive temperature rises, the 3RB24 electronic
overload relays also allow direct temperature monitoring of the
Connecting terminals (removable terminal block):
The generously sized terminals permit connection of two motor windings (full motor protection!) by connection with
conductors with different cross-sections for the auxiliary, control broken-wire interlock of a PTC sensor circuit. With this
and sensor circuits. Connection is possible with screw terminals temperature-dependent protection, the loads can be protected
and alternatively with spring-loaded terminals.
against overheating caused, for example, indirectly by reduced
Test/RESET button: coolant flow and which cannot be detected by means of the
Enables testing of all important device components and functions,
plus resetting of the device after a trip when Manual RESET is current alone. In the event of overheating, the devices switch off
selected. the contactor, and thus the load, by means of the auxiliary
contacts. The "tripped" status is signaled by means of
Selector switch for Manual/Automatic RESET:
With this switch you can choose between Manual and Automatic a continuously illuminated "THERMISTOR" LED and also reported
RESET. as a group fault via IO-Link.
Red LED "OVERLOAD": To protect the loads against incomplete ground faults due to
A continuous red light signals an active overload trip; a flickering
led light signals an imminent trip (overload warning). damage to the insulation, humidity, condensation, etc., the
3RB24 electronic overload relays offer the possibility of internal
Red LED "THERMISTOR": ground-fault detection (for details, see Equipment Manual,
A continuous red light signals an active thermistor trip.
not possible in conjunction with contactor assemblies for
Red LED "GND FAULT": star-delta (wye-delta) starting). In the event of a ground fault,
A continuous red light signals an active ground-fault trip.
the 3RB24 relays trip instantaneously.
Green LED "DEVICE/IO-Link:
A continuous green light signals that the device is working The "tripped" status is signaled by means of a flashing red
correctly, a green flickering light signals the communication "Ground Fault" LED and reported at the 3RB24 overload relay as
through IO-Link. a group fault via IO-Link.
Protection equipment
Overload relays
SIRIUS 3RB2 electronic overload relays
3RB24 for IO-Link for high-feature applications
The current values can be transmitted to the higher-level Use in hazardous areas
controller via IO-Link.
The 3RB24 electronic overload relays for IO-Link with the 3RB29
The 3RB24 electronic overload relay for IO-Link is suitable for current measuring module are suitable for the overload
operation with frequency converters. protection of motors with the following types of protection:
The devices are manufactured in accordance with environ- • II (2) G[Ex e] [Ex d] [Ex px]
mental guidelines and contain environmentally friendly and • II (2) D[Ex t] [Ex p]
reusable materials. They comply with all important worldwide
standards and approvals. EC type-examination certificate for Group II, Category (2)
G/D exists. It has the number PTB 11 ATEX 3014.
The article number scheme shows an overview of product For your orders, please use the article numbers quoted in the
versions for better understanding of the logic behind the article selection and ordering data.
numbers.
Protection equipment
Overload relays
SIRIUS 3RB2 electronic overload relays
3RB24 for IO-Link for high-feature applications
■ Application
Industries Ambient conditions
The 3RB24 electronic overload relays are suitable for customers The devices are insensitive to external influences such as
from all industries who want to guarantee optimum current and shocks, corrosive ambient conditions, aging and temperature
temperature-dependent protection of their electrical loads (e.g. fluctuations.
motors) under normal and heavy starting conditions (CLASS 5E
to 30E), minimize project completion times, inventories and In the temperature range from -25 to +60 °C, the 3RB24
energy consumption, and optimize plant availability and electronic overload relays compensate the temperature in
maintenance management. accordance with IEC 60947-4-1.
Configuration notes for use of the devices below -25 °C or above
Application +60 °C on request.
The 3RB24 electronic overload relays have been designed for
the protection of three-phase asynchronous and single-phase Use of SIRIUS protection devices in conjunction with
AC motors. IE3 and IE4 motors
7
■ Technical specifications
More information
Application Manual for switching devices with IE3 and IE4 motors, see Equipment Manual, see
https://support.industry.siemens.com/cs/ww/en/view/94770820 https://support.industry.siemens.com/cs/ww/en/view/46165627
Configuration Manual for load feeders, see Technical specifications, see
https://support.industry.siemens.com/cs/ww/en/view/39714188 https://support.industry.siemens.com/cs/ww/en/ps/16281/td
General data
Tripping in the event of Overload, phase failure and phase asymmetry (> 40% according to NEMA),
+ ground fault (connectable and disconnectable) and activation of the thermistor
motor protection (with closed PTC sensor circuit)
Trip class according to IEC 60947-4-1 CLASS 5E, 10E, 20E and 30E adjustable
Phase failure sensitivity Yes
Overload warning Yes, from 1.125 × Ie for symmetrical loads
and from 0.85 × Ie for asymmetrical loads
Reset and recovery
• Reset options after tripping Manual and Automatic RESET, electrical Remote RESET or via IO-Link
• Recovery time
- For Automatic RESET min. - For tripping due to overcurrent: 3 (stored permanently)
- For tripping by thermistor: time until the motor temperature has fallen 5 K
below the response temperature
- For tripping due to a ground fault: no Automatic RESET
- For Manual RESET min. - For tripping due to overcurrent: 3 (stored permanently)
- For tripping by thermistor: time until the motor temperature has fallen 5 K
below the response temperature
- For tripping due to a ground fault: immediately
- For Remote RESET min. - For tripping due to overcurrent: 3 (stored permanently)
- For tripping by thermistor: time until the motor temperature has fallen 5 K
below the response temperature
- For tripping due to a ground fault: immediately
Protection equipment
Overload relays
SIRIUS 3RB2 electronic overload relays
3RB24 for IO-Link for high-feature applications
H
Dimensions of evaluation modules mm 45 x 111 x 95
(W x H x D)
D
W
Protection equipment
Overload relays
SIRIUS 3RB2 electronic overload relays
3RB24 for IO-Link for high-feature applications
7
• With fuse, operational class gG A 6
• With miniature circuit breaker, C characteristic A 1.6
Protective separation between auxiliary conducting paths V 300
according to IEC 60947-1
CSA, UL and UR rated data
Auxiliary circuit – Switching capacity B300, R300
Conductor cross-sections of the auxiliary circuit
Connection type Screw terminals
Protection equipment
Overload relays
SIRIUS 3RB2 electronic overload relays
3RB24 for IO-Link for high-feature applications
Rated values
• Output signal mA 4 ... 20
• Measuring range 0 ... 1.25 x Ie
4 mA corresponds to 0 x Ie
16.8 mA corresponds to 1.0 x Ie
20 mA corresponds to 1.25 x Ie
• Load, max. 100
Conductor cross-sections for the control and sensor circuit
as well as the analog output
Connection type Screw terminals
Protection equipment
Overload relays
SIRIUS 3RB2 electronic overload relays
IE3 ready IE4 ready IE3/IE4 ready 3RB24 for IO-Link for high-feature applications
3RB24 electronic overload relays (evaluation modules) for full motor protection for stand-alone installation,
CLASS 5E, 10E, 20E and 30E (adjustable)
Type 3RB2483-4A.1
Features and technical specifications
Overload protection, phase failure protection and asymmetry protection ✓
Supplied from an external source ✓
24 V DC via IO-Link
Direct-on-line or reversing starters (star-delta (wye-delta) starting also possible) ✓
controllable via IO-Link
Auxiliary contacts ✓
1 CO and 1 NO in series
Manual and Automatic RESET ✓
Remote RESET ✓
(electrically or via IO-Link)
Four LEDs for operating and status displays ✓
TEST function and self-monitoring ✓
Internal ground-fault detection ✓
Screw or spring-loaded terminals for auxiliary, control and sensor circuits ✓
Input for thermistor (PTC) sensor circuit ✓
Analog output ✓
IO-Link-specific functions
• Connection of direct-on-line, reversing and star-delta (wye-delta) starters to the controller via IO-Link ✓
• On-site controlling of the starter using the handheld device ✓
• Accessing process data (e.g. current values in all three phases) via IO-Link ✓
• Accessing parameterization and diagnostics data (e.g. tripped signals) via IO-Link ✓
7
✓ Available
3RB2483-4AA1 3RB2483-4AC1
Size Version Screw terminals Spring-loaded
contactor terminals
Article No. Price Article No. Price
per PU per PU
Evaluation modules
S00 ... S12 Monostable 3RB2483-4AA1 3RB2483-4AC1
Protection equipment
Overload relays
SIRIUS 3RB2 electronic overload relays
Current measuring modules for 3RB22, 3RB23 and 3RB24
■ Overview
More information
Homepage, see www.siemens.com/sirius-control Application Manual for switching devices with IE3 and IE4 motors, see
Industry Mall, see www.siemens.com/product?3RB2 https://support.industry.siemens.com/cs/ww/en/view/94770820
Other manuals, see
https://support.industry.siemens.com/cs/ww/en/ps/16282/man
■ Application
Use of SIRIUS protection devices in conjunction with
IE3 and IE4 motors
Note:
For the use of current measuring modules for 3RB22, 3RB23,
3RB24 in conjunction with highly efficient IE3 and IE4 motors,
please observe the information on dimensioning and
configuration, see Application Manual.
For more information, see page 1/8.
Protection equipment
Overload relays
SIRIUS 3RB2 electronic overload relays
Current measuring modules for 3RB22, 3RB23 and 3RB24
■ Technical specifications
More information
Manuals, see Technical specifications, see
https://support.industry.siemens.com/cs/ww/en/ps/16282/man https://support.industry.siemens.com/cs/ww/en/ps/16282/td
H
Size contactor S00/S0 S2/S3 S6 S10/S12
Dimensions of current measuring modules mm 45 x 84 x 45 55 x 94 x 72 120 x 119 x 145 145 x 147 x 148
D
W
(W x H x D)
Main circuit
Rated insulation voltage Ui V 690 1 000
(pollution degree 3)
Rated impulse withstand voltage Uimp kV 6 8
Rated operational voltage Ue V 690 1 000
Type of current
• Direct current No
• Alternating current Yes, 50/60 Hz 5%
Current setting A 0.3 ... 3; 10 ... 100 20 ... 200 63 ... 630
2.4 ... 25
Power loss per unit (max.) W 0.5
Short-circuit protection
• With fuse without contactor See "Selection and ordering data", page 7/137
7
• With fuse and contactor See Configuration Manual
Degree of protection IP on the front according to IEC 60529
• Screw terminals/busbar connections IP20 IP00 (IP20 with box terminal/cover)
• Straight-through transformers IP20 IP20 --
Touch protection on the front according to IEC 60529
• Screw terminals/busbar connections Finger-safe for vertical Finger-safe for vertical touching from the front
touching from the front (with box terminals/cover)
• Straight-through transformers Finger-safe for vertical Finger-safe for vertical --
touching from the front touching from the front
Protective separation between main and auxiliary conducting paths
According to IEC 60947-1 (pollution degree 2)
• For systems with grounded neutral point V 690
• For systems with ungrounded neutral point V 600
Protection equipment
Overload relays
SIRIUS 3RB2 electronic overload relays
Current measuring modules for 3RB22, 3RB23 and 3RB24
H
Size contactor S00/S0 S2/S3 S6 S10/S12
Dimensions of current measuring modules mm 45 x 84 x 45 55 x 94 x 72 120 x 119 x 145 145 x 147 x 148
D
W
(W x H x D)
Conductor cross-sections of main circuit
Connection type Screw terminals with box terminal
1 x max. 120),
1 x (10 ... 120)
• Finely stranded with end sleeve (DIN 46228) mm2 -- With 3RT1955-4G 2 x (50 ... 185),
box terminal: Front clamping
2 x (1 x max. 50, point only:
1 x max. 70), 1 x (70 ... 240)
1 x (10 ... 70)
With 3RT1956-4G Rear clamping
box terminal: point only:
2 x (1 x max. 95, 1 x (120 ... 185)
1 x max. 120),
1 x (10 ... 120)
• AWG cables AWG -- With 3RT1955-4G 2 x (2/0 ... 500 kcmil),
box terminal: Front clamping
2 x (max. 1/0), point only:
1 x (6 ... 2/0) 1 x (3/0 ... 600 kcmil)
With 3RT1956-4G Rear clamping
box terminal: point only:
2 x (max. 3/0), 1x
1 x (6 ... 250 kcmil) (250 kcmil ... 500 kcmil)
• Ribbon cables (number x width x thickness) mm -- With 3RT1955-4G 2 x (20 x 24 x 0.5),
box terminal: 1 x (6 x 9 x 0.8 ...
2 x (6 x 15.5 x 0.8), 20 x 24 x 0.5)
1 x (3 x 9 x 0.8 ...
6 x 15.5 x 0.8)
With 3RT1956-4G
box terminal:
2 x (10 x 15.5 x 0.8),
1 x (3 x 9 x 0.8 ...
10 x 15.5 x 0.8)
Connection type Busbar connections
Protection equipment
Overload relays
SIRIUS 3RB2 electronic overload relays
IE3 ready IE4 ready IE3/IE4 ready Current measuring modules for 3RB22, 3RB23 and 3RB24
7
S2/S3 10 … 100 315 3RB22 to 3RB2906-2JG1 1 1 unit 41G
3RB24
Size S6
Devices with busbar connection,
for mounting on contactor and stand-alone installation
(an appropriate connection kit with screws,
spring washers and nuts is enclosed)
S6 20 … 200 315 3RB22 to 3RB2956-2TH2 1 1 unit 41G
3RB24
Devices with straight-through transformer,
for mounting on contactor and stand-alone installation
For mounting on 20 … 200 315 3RB22 to 3RB2956-2TG2 1 1 unit 41G
S6 contactors with 3RB24
box terminals
Sizes S10/S122)
Devices with busbar connection,
for mounting on contactor and stand-alone installation
(an appropriate connection kit with screws,
spring washers and nuts is enclosed)
S10/S12 63 … 630 800 3RB22 to 3RB2966-2WH2 1 1 unit 41G
and 3RB24
size 14 (3TF68/3TF69)2)
1) Maximum protection by fuse only for overload relays, type of Note:
coordination "2". For fuse values in connection with contactors,
see Configuration Manual. The connecting cable between the current measuring module
2) and the evaluation module is not included in the scope of
For 3TF68/3TF69 contactors, direct mounting is not possible.
supply; please order separately (see "Accessories").
■ Accessories
Size Version For Article No. Price PU PS* PG
contactor overload per PU (UNIT,
relays SET, M)
Protection equipment
Overload relays
SIRIUS 3RB2 electronic overload relays
Accessories for 3RB22, 3RB23, 3RB24
■ Overview
More information
Homepage, see www.siemens.com/sirius-control Manuals, see
Industry Mall, see www.siemens.com/product?3RB2 https://support.industry.siemens.com/cs/ww/en/ps/16283/man
The following optional accessories are available for the 3RB22 to • Terminal covers for the 3RB29 current measuring modules
3RB24 electronic overload relays: size S6 and S10/S12
• Operator panel for the 3RB24 evaluation modules • Box terminal blocks for the 3RB29 current measuring modules
• Sealable cover for the 3RB22 to 3RB24 evaluation modules size S6 and S10/S12
• Push-in lugs for screw fixing for 3RB22 to 3RB24 evaluation
modules and 3RB2906 current measuring modules
3RA6935-0A
Note:
The connecting cable between the evaluation
module and the operator panel is not included
in the scope of supply; please order
separately.
Connecting cable 3RB24 3UF7933-0BA00-0 1 1 unit 42J
Length 2.5 m (round),
for connecting the evaluation module to the
operator panel
Enabling modules (spare part) 3RB24 3RA6936-0A 1 1 unit 42F
Interface covers 3RB24 3RA6936-0B 1 5 units 42F
General accessories
Version Size For Article No. Price PU PS* PG
overload per PU (UNIT,
relays SET, M)
3RB2984-2
Terminal covers for current measuring modules
Covers for cable lugs and
busbar connections
• Length 100 mm S6 3RB2956 3RT1956-4EA1 1 1 unit 41B
• Length 120 mm S10/S12 3RB2966 3RT1966-4EA1 1 1 unit 41B
Covers for box terminals
• Length 25 mm S6 3RB2956 3RT1956-4EA2 1 1 unit 41B
3RT1956-4EA1 • Length 30 mm S10/S12 3RB2966 3RT1966-4EA2 1 1 unit 41B
Covers for screw terminals S6 3RB2956 3RT1956-4EA3 1 1 unit 41B
Between contactor and overload S10/S12 3RB2966 3RT1966-4EA3 1 1 unit 41B
relay, without box terminals
3RT1956-4EA2 (1 unit required per combination)
Protection equipment
Overload relays
SIRIUS 3RB2 electronic overload relays
Accessories for 3RB22, 3RB23, 3RB24
3RB1900-0B
7
spring-loaded partially connection:
terminals insulated 3RB2
Blank labels
Unit labeling 20 mm x 7 mm Titanium 3RB2 3RT2900-1SB20 100 340 41B
plates1) gray units
For SIRIUS devices
Adhesive labels 19 mm x 6 mm Titanium 3RB2 3RT2900-1SB60 100 3 060 41B
For SIRIUS devices gray units
IC01_00181
3RT2900-1SB20
1)
PC labeling system for individual inscription
of unit labeling plates available from:
murrplastik Systemtechnik GmbH
(see page 16/18).
Protection equipment
Notes
7
Load feeders and motor starters for use in the control cabinet
Price groups
PG 14O, 255, 41B, 41D, 41E, 41L,
42C, 42D, 42F, 42G
8/2 Introduction
8
8/74 Add-on modules for AS-Interface
8/76 Infeed system for 3RA6
Siemens IC 10 · 2023
© Siemens 2023
Load feeders and motor starters for use in the control cabinet
Introduction
■ Overview
Central and compact starter solutions
Our range offers you many different possibilities for simple with each other, have a very compact design and are particularly
and practical starter solutions in the control cabinet. Features easy and quick to install and wire up.
common to all our load feeders, compact starters and motor
starters: Like all SIRIUS devices they are optimally coordinated In addition there is a seamless range of SIRIUS 3RW soft starters
available for soft starting in the control cabinet (see page 6/2).
Performance (kW/400 V)
SIRIUS tested combinations
SINAMICS G120
frequency converter
SINAMICS V20
frequency converter
625
Functionality
IC01_00738a
G120C
(wye-delta) starter
G120X
direct-on-line
25
G120
SIRIUS 3RM1 and reversing
motor starter starter
5
Requirement Fixed Speed Variable Speed
Load feeders and motor starters for use in the control cabinet
Introduction
8
for 60 mm busbars
Accessories for 3RA2 direct-on-line and 8/45
reversing starters
Infeed system • The infeed system is a convenient means of energy supply and distribution 3RV29 7/67,
for a group of several motor starter protectors or complete load feeders with 8/56
screw or spring-loaded terminals up to size S0.
SIRIUS 3RA6 compact starters
• Integrated functionality of a motor starter protector, contactor and electronic
overload relay and various functions of optional mountable accessories
• Can be used for direct starting of standard three-phase motors up to 32 A
3RA61 direct-on-line starters • Up to 15 kW/400 V, weld-free, wide setting range, removable terminals 3RA61 8/65
3RA62 reversing starters • Up to 15 kW/400 V, weld-free, wide setting range, removable terminals 3RA62 8/66
3RA64 direct-on-line starters for IO-Link • Up to 15 kW/400 V, weld-free, wide setting range, removable terminals 3RA64 8/67
3RA65 reversing starters for IO-Link • Up to 15 kW/400 V, weld-free, wide setting range, removable terminals 3RA65 8/68
Accessories for 3RA6 direct-on-line and 3RA69 8/69
reversing starters
Add-on modules for AS-Interface 3RA69 8/74
Infeed system for 3RA6 • Modular expandability, up to 100 A, terminals up to 70 mm2 3RA68 8/76
• 3-phase infeeds and expansion modules 8/79
• Expansion modules 8/80
• Accessories for infeed systems for 3RA6 8/81
Load feeders and motor starters for use in the control cabinet
Introduction
• Push-in lugs for wall mounting, integrated sealable cover, coding pins 3ZY1 8/93
ET 200SP motor starters
• In hybrid technology in the SIMATIC ET 200SP I/O system
• For the switching and protection of three-phase asynchronous motors,
1-phase AC motors and 1-phase asynchronous motors up to 5.5 kW
(at 400 V)
3RK1308 direct-on-line starters • Direct-on-line starting with electronic overload protection 3RK1308-0A.0 8/100
3RK1308 reversing starters • Reversing functionality with electronic overload protection 3RK1308-0B.0 8/100
3RK1308 fail-safe direct-on-line starters • Direct-on-line starting with electronic overload protection 3RK1308-0C.0 8/100
3RK1308 fail-safe reversing starters • Reversing functionality with electronic overload protection 3RK1308-0D.0 8/100
BaseUnits • Mounting components for infeed and for integration into the 3RK1908-0AP00 8/101
ET 200SP I/O system
3DI/LC control module • Module with three digital inputs for the use of additional functions such 3RK1908-1AA00 8/101
as "Quick stop", and for manual-local operation
Accessories • Cover for BaseUnit and infeed bus, additional mechanical mounting unit, fan 3RK19, 3RW49 8/102
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
General data
■ Overview
3RA2 load feeders
More information
Operating conditions
3RA2 load feeders are climate-proof. They are intended for
use in enclosed rooms in which no severe operating conditions
(such as dust, caustic vapors, hazardous gases) prevail.
Suitable covers must be provided for installation in dusty
and damp locations.
Behavior in the event of short circuit
3RA22 reversing starters for DIN-rail mounting or screw fixing with screw EN 60947-4-1 (VDE 0660 Part 102) and IEC 60947-4-1 make
terminals a distinction between two different types of coordination,
which are referred to as type of coordination "1" and type of
The 3RA2 fuseless load feeders consist of the 3RV2 motor coordination "2". Any short circuits that occur are cleared safely
starter protector and the 3RT2 electromechanical contactor. by both types of coordination. The only differences concern the
The devices are electrically and mechanically connected using extent of the damage caused to the device by a short circuit.
prefabricated assembly kits (link modules, wiring kits and
DIN-rail or busbar adapters). ToC Type of coordination "1"
1
Around 500 preassembled 3RA2 combinations can be ordered The load feeder may be non-operational after a short
for direct-on-line and reversing starting of standard three-phase circuit has been cleared. Damage to the contactor or
to the overload release is permissible.
8
motors up to 65 A (approx. 37 kW/400 V). Prefabricated
assembly kits are available as accessories for the power
spectrum up to 45 kW. The desired fuseless load feeder can ToC Type of coordination "2"
2
thus be assembled quickly and economically by the customer. There must be no damage to the overload release
A time saving is also achieved in connection with switchgear or to any other components after a short circuit has
acceptances, as – unlike with conventional wiring systems – been cleared. The load feeder can resume operation
there is no need to rectify possible wiring errors. without needing to be renewed. At most, welding of
the contactor contacts is permissible if they can
In the 3RA2 load feeder, the 3RV2 motor starter protector be disconnected easily without any significant
is responsible for overload and short-circuit protection. deformation.
Back-up protective devices, such as melting fuses or limiters,
are superfluous here, as the motor starter protector is The types of coordination are indicated in
short-circuit proof up to 150 kA at 400 V. the corresponding tables by the symbols
The 3RT2 contactor is particularly suitable for extremely shown on orange backgrounds.
complex switching tasks requiring the greatest endurance.
Voltage specifications
The 3RA2 load feeders are available with setting ranges from
0.14 to 65 A in sizes S00, S0 and S2. Load feeders in size S3 up The specifications for 3-phase systems according to
to 100 A are available for customer assembly. IEC 60947-4-1 apply for the following line system configurations:
.
Size Width Max. rated current For three- Voltage Ue Line system configurations
Direct-on-line starters/ In max phase motors Three-phase Three-phase
reversing starters up to four-wire systems three-wire systems
mm A kW
S00 45/90 16 7.5
S0 45/90 32 15
IC01_00703
IC01_00709
S2 55/120 65 37
S3 70/150 100 45
The size of the 3RA2 load feeders is based on the size of the V V V
contactor: 230 -- 230
400 230/400 400
Size 3RA2 S00 S0 S2 S3
440 260/440 440
Size of 3RV2 motor starter S00 S001), S2 S3 500 -- 500
protector S0
690 400/690 690 (only from size S3)
Size of 3RT2 contactor S00 S0 S2 S3
-- Not specified
1)
The combination of an S00 motor starter protector with an S0 contactor is
possible only for screw terminal versions.
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
General data
Tripping times In particular, certain accessories have been optimized for
the fuseless load feeders. These include the top-connected,
All 3RA2 load feeders described here are designed for normal transverse auxiliary switch on the motor starter protector, which
starting, in other words for overload tripping times of less is available in a range of different versions. Special auxiliary
than 10 s (CLASS 10). At rated-load operating temperature switches that can be snapped on from below are available for
the tripping times are shorter, depending on the particular the contactor. These two accessories enable the fuseless load
equipment and the setting range. The exact values can be feeders to be wired simply without having to route cables
derived from the tripping characteristics of the motor starter through the device.
protectors.
Connection methods Incoming power supply
For all 3RA2 feeders up to 32 A, spring-loaded terminals are In total, four different energy supply options are available
available as well as screw terminals. To connect two devices (see "3RV29 infeed system for load feeders" on page 8/56).
with spring-loaded terminals, there are plug-in link module for Customer assembly of fuseless load feeders
sizes S00 and S0 which enable very quick mounting of the
feeders and a vibration-resistant assembly. Whereas preassembled 3RA2s can be ordered up to 65 A,
combinations in size S3 up to 100 A (approx. 45 kW/400 V)
To connect a motor starter protector with screw terminals to are also possible for customer assembly.
a contactor with spring-loaded terminals there are special
hybrid link modules for the sizes S00 and S0. The standard devices can be combined optimally – in terms
of both technical specifications and dimensions, thanks to the
Screw terminals modular system of the SIRIUS series.
The fuseless load feeders can thus be assembled easily by
the customer. It is simply necessary to assemble the standard
Spring-loaded terminals 3RV2 motor starter protector, the 3RT2 contactor and the
appropriate assembly kit.
The terminals are indicated in the corresponding tables For single devices and assembly kits, see the "Selection
by the symbols shown on orange backgrounds. and ordering data" for 3RA21 direct-on-line starters and
3RA22 reversing starters, page 8/22 or 8/34 onwards.
Use of load feeders in conjunction with IE3 and IE4 motors
For assembly kits for direct-on-line starting or reversing
Note: operation for mounting onto DIN rails or busbars, see page 8/50.
For the use of SIRIUS 3RA2 load feeders in conjunction For size S3 direct-on-line starters and sizes S0, S2 and S3
with highly efficient IE3 and IE4 motors, please observe the reversing starters, it is imperative that a DIN-rail adapter is used
8
information on dimensioning and configuring, see Application to ensure the necessary mechanical strength. If a busbar
Manual. adapter is used (not possible for size S3) then a DIN-rail adapter
For more information, see page 1/8. is not necessary.
3RA2 complete units SENTRON 3VA circuit breakers and SIRIUS 3RT contactors are
available for rated currents >100 A.
The 3RA2 fuseless load feeders can be ordered as preassem-
bled complete units for direct-on-line starting (3RA21) or for Single devices for customer assembly can be ordered if other
reversing operation (3RA22) with screw or spring-loaded termi- rated control supply voltages are required. Assembly kits can be
nals. From size S2, complete units for direct-on-line starting used to facilitate assembly.
(3RA21) are only available with screw terminals. Customers can also assemble tested combinations of motor
There are control supply voltages available of 50 Hz 230 V AC starter protectors with electronic controls (soft starters, solid-
and 24 V DC. state contactors) and load feeders with additional monitoring
and control devices (3RR monitoring relays, SIMOCODE 3UF).
A distinction is also drawn between whether the feeder is
mounted on a 35 mm DIN rail, on a flat surface using screws, For the electrical and mechanical connection of protection
or on a 60 mm busbar system. equipment and controls, there are prefabricated assembly kits
(link modules, wiring kits and DIN-rail or busbar adapters).
3RA21 load feeders in the S0 size must be configured on
DIN-rail adapters if high vibration and shock loads (railways, The following types of configuration are possible:
Kraftwerk Union, etc.) are involved. • Direct-on-line/reversing starting
• Star-delta (wye-delta) starting
A vibration and shock kit is available for mounting on busbar
• Solid-state/soft starting
adapters.
For more information and assignment tables for combinations of
Accessories the 3RA2 generation for self-assembly, see
As the 3RA2 fuseless load feeders are constructed from • Configuration Manual for load feeders,
3RV2 motor starter protectors and 3RT2 contactors, the same https://support.industry.siemens.com/cs/ww/en/view/39714188
accessories – such as auxiliary switches, undervoltage releases
• Equipment Manual,
or door-coupling rotary operating mechanisms – can be used for
https://support.industry.siemens.com/cs/ww/en/view/60284351
the 3RA2 fuseless load feeders as for these motor starter
protectors and contactors.
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
General data
Customer assembly of fused load feeders The function modules perform not only the communication
(contactor operation and feedback, ready signal) but also the
The flexible, modular system of SIRIUS also enables the electrical interlocking (for reversing and star-delta (wye-delta)
configuration of fused load feeders up to 100 A (approx. starters) and the timing relay function (star-delta (wye-delta)
45 kW/400 V). Up to 32 A is also available for 45 mm installation reversing time).
widths.
Communication information and control supply voltages are
Compact 3NW7...-1 cylindrical fuse holders for IEC fuses size passed on through ribbon cables so that the complete control
10 x 38 mm, or 3NW7...-1HG holders for Class CC UL fuses, current wiring on the starter is no longer needed.
can be used for this purpose.
More information:
For more information about fuse systems, see Catalog LV 10.
• AS-Interface see page 2/19 onwards
Communication link through IO-Link • 3RA27 function modules, see pages 3/73, 3/80 and 3/101
Load feeders can also be assembled with IO-Link for connection
to the higher-level control system. For each feeder, this requires Contactors with voltage tap
a contactor with a voltage tap onto which a 3RA2711 function For configuring load feeders with communication links
module is plugged (various versions for direct-on-line, reversing (AS-i/IO-Link), contactors with voltage taps are required. These
and star-delta (wye-delta) starters). The design of the SIRIUS contactors are not included as standard in the preassembled
load feeders permits a group of up to four SIRIUS controls to be 3RA2 load feeders. A load feeder with communication link must
conveniently connected through the standardized open system be assembled therefore from single devices.
IO-Link to a control system, thus reducing wiring considerably
compared to the conventional parallel wiring method. The electrical Complete integration in the automation landscape
connection is made using only three standard cables. As the result of the communication link through IO-Link or AS-i,
The function modules perform not only the communication the SIRIUS load feeders are fully integrated in the automation
(contactor operation and feedback, ready signal) but also the landscape and can draw on all the advantages of TIA
electrical interlocking (for reversing and star-delta (wye-delta) (e.g. integration in the TIA Maintenance Station).
starters) and the timing relay function (star-delta (wye-delta) Mounting
reversing time).
3RA2 fuseless load feeders can be supplied:
Communication information and control supply voltages are
passed on through ribbon cables so that the complete control • For mounting onto TH 35 DIN rails according to IEC 60715
current wiring on the feeder is no longer needed. (depth 15 mm)
The monitoring and maintenance of a plant is made • For mounting onto busbar adapters (busbar center-to-center
clearance 60 mm, busbar thickness 5 to 10 mm with beveled
8
considerably easier by transmitting diverse diagnostics data
from the function modules (e.g. missing main and auxiliary edges)
voltage, local disconnection…) through IO-Link to the higher- The fuseless load feeders are also suitable for screw fixing using
level control system. Also, feeders equipped for IO-Link can be two 3RV2928-0B push-in lugs.
conveniently controlled from the control cabinet door using the
optional operator panel. 3RA2 fuseless load feeders can also be installed using the
3RV29 infeed system (S0 and S00 only, see page 7/67).
More information:
• IO-Link, see page 2/88 onwards
• 3RA27 function modules, see pages 3/73, 3/80 and 3/101
Communication link through AS-Interface
Connection of the load feeders to the higher-level control
system is possible not only through IO-Link but also through
AS-Interface. The AS-Interface connection is recommended
wherever load feeders are used in distributed applications.
In this case, too, a contactor with a voltage tap is required with
a corresponding 3RA2712 function module (various versions
for direct-on-line, reversing and star-delta (wye-delta) starters).
The devices are implemented in A/B technology, making it easy
to connect up to 62 feeders to an AS-i master (regardless of
whether they are direct-on-line, reversing or star-delta (wye-
delta) starters). This results in a significant reduction of wiring
compared to the conventional parallel wiring method.
The electrical connection is made using standard cables.
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
General data
Direct-on-line starting • For DIN-rail mounting or screw fixing • Sizes S00 and S0
1 1 1 1 2 push-in lugs
3RV2928-0B
(only for screw fixing)
2 Motor starter protector
Size S00/S0
3 Screw terminals
2 2
3 Motor starter protector
Size S00/S0
Spring-loaded terminals
4 Link module
(Screw terminals)
3RA1921-1DA00 (for S00)
3RA2921-1AA00 (for S0, AC contactor)
3RA2921-1BA00 (for S0, DC contactor)
5 Link module
(Spring-loaded terminals)
4 5 3RA2911-2AA00 for S00
6 3RA2921-2AA00 for S0
6 Link module
(Hybrid)
3RA2911-2FA00 for S00
3RA2921-2FA00 for S0
7 Contactor
8 8 Size S00/S0
7 Screw terminals
IC01_00636
8 Contactor
Size S00/S0
Spring-loaded terminals
8
1 1 1 2 push-in lugs
3RV2928-0B
(only for screw fixing)
7
IC01_00637
Left: Combination of motor starter protector and solid-state switching device with screw terminals
Right: Combination of motor starter protector and soft starter with spring-loaded terminals
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
General data
Direct-on-line starting • For DIN-rail mounting • Size S2
IC01_00638
6 Soft starter
Size S2
Screw terminals
4 4
5 6
8
Left: 3RA21 load feeder with screw terminals
Right: Combination of motor starter protector and soft starter with screw terminals
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
General data
Direct-on-line starting • For DIN-rail mounting • Size S3
5 6
IC01_00655b
8
3RA21 load feeder for direct-on-line starting and DIN-rail mounting in size S3
(the version with screw terminals is shown in the picture)
1 2 1 60 mm busbar adapter
for screw terminals
8US1251-5DS10 for S00
8US1251-5NT10 for S0
2 60 mm busbar adapter
for spring-loaded terminals
8US1251-5DT11 for S00
8US1251-5NT11 for S0
3 4
3 Motor starter protector
Size S00/S0
Screw terminals
4 Motor starter protector
Size S00/S0
Spring-loaded terminals
5 Link module
Screw terminals
3RA1921-1DA00 for S00
3RA2921-1AA00 for S0, AC contactor
IC01_00639
8 7 Contactor
7 Size S00/S0
Screw terminals
8 Contactor
Size S00/S0
Spring-loaded terminals
Left: 3RA21 load feeder for direct-on-line starting with busbar adapter with screw terminals
Right: 3RA21 load feeder for direct-on-line starting with busbar adapter with spring-loaded terminals
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
General data
Direct-on-line starting • For 60 mm busbar systems • Size S2
8
3RA21 load feeder for direct-on-line starting with busbar adapter with screw terminals
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
General data
Reversing operation • For DIN-rail mounting or screw fixing • Size S00
1 1 1 Push-in lug
3RV2928-0B
(only for screw fixing)
2 Motor starter protector
3 Size S00/S0
2
Screw terminals
3 Motor starter protector
Size S00/S0
Spring-loaded terminals
4 Link module
Screw terminals
3RA1921-1DA00 for S00
3RA2921-1AA00 for S0, AC contactor
3RA2921-1BA00 for S0, DC contactor
5 Link module
Spring-loaded terminals
4 5 3RA2911-2AA00 for S00
3RA2921-2AA00 for S0
6 Contactor
Size S00/S0
Screw terminals
7 Contactor
Size S00/S0
e Spring-loaded terminals
6 a
6 7
c
7
g
8
IC01_00641
b f
Left: 3RA22 load feeder with screw terminals with push-in lugs with two contactors for reversing operation and
wiring kit 3RA2913-2AA1 for connecting the contactors (including mechanical interlocking and connecting clips)
Right: 3RA22 load feeder with spring-loaded terminals with push-in lugs with two contactors for reversing operation and
wiring kit 3RA2913-2AA2 (including mechanical interlocking and connecting clips)
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
General data
Reversing operation • For DIN-rail mounting • Size S0
2
2 RH assembly kit for reversing operation and
DIN-rail mounting in size S0
Screw terminals
3RA2923-1BB1
Spring-loaded terminals
1)
3RA2923-1BB2
1 Consisting of:
• Wiring kit for the
main and auxiliary circuits
• Two DIN-rail adapters
• Two connecting wedges
• Mechanical interlock
• Two connecting clips
• Fixing accessories
4 Contactor
IC01_00642
Size S0
8
d Screw terminals/spring-loaded terminals
Wiring kit
Screw terminals
3RA2923-2AA1
Spring-loaded terminals
3RA2923-2AA2
a Upper wiring module
b
b Lower wiring module
c Two connecting clips for two contactors
d Mechanical interlock
(can be removed if necessary)
3RA22 load feeder for reversing operation and DIN-rail mounting in size S0
(the version with screw terminals is shown in the picture)
RH mounting kits for reversing operation and DIN-rail mounting
in size S0, see page 8/52.
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
General data
Reversing operation • For DIN-rail mounting • Size S2
3RA2933-1BB1
Consisting of:
• Wiring kit for the
main and auxiliary circuits
• Two DIN-rail adapters
1
• Two side modules
• Four connecting wedges
• Mechanical interlock
• Two connectors for two contactors
• Fixing accessories
3RA2932-1AA00
with two side modules
3 3RA2902-1B
and four connecting wedges
8US1998-1AA00
3 Link module
3RA2931-1AA00
Screw terminals
4 Contactor
a
Size S2
4 Screw terminals
4 c
Wiring kit
d
8
Screw terminals
3RA2933-2AA1
a Upper wiring module
b Lower wiring module
c Two connectors for two contactors
d Mechanical interlock
3RA2934-2B (not part of the wiring
kit, must be ordered separately)
3RA22 load feeder for reversing operation and DIN-rail mounting in size S2
(the version with screw terminals is shown in the picture)
RH mounting kits for reversing operation and DIN-rail mounting
in size S2, see page 8/52.
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
General data
Reversing operation • For DIN-rail mounting • Size S3
8
c Two connectors for two contactors
d Mechanical interlock
3RA2934-2B (not part of the wiring kit,
must be ordered separately)
b
3RA22 load feeder for reversing operation and DIN-rail mounting in size S3
(the version with screw terminals is shown in the picture)
RH mounting kits for reversing operation and DIN-rail mounting
in size S3, see page 8/52.
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
General data
Reversing operation • For 60 mm busbar systems • Sizes S00 and S0
Screw terminals
3RA2913-1DB1 for S00
3RA2923-1DB1 for S0
Spring-loaded terminals
3RA2913-1DB2 for S00
1 3RA2923-1DB2 for S0 1)
Consisting of:
• Wiring kit for the
main and auxiliary circuits
• Busbar adapter
• Device holder
• Two connecting wedges
• Mechanical interlock
• Two connecting clips for two contactors
• Fixing accessories
Screw terminals
IC01_00644a
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
General data
Reversing operation • For 60 mm busbar systems • Size S2
8
d Mechanical interlock
4 c 4 3RA2934-2B (not part of the wiring kit,
must be ordered separately)
d
IC01_00645
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
General data
Article number scheme
Note:
The article number scheme shows an overview of product
8
■ Benefits
• Minimum planning and assembly work and far less wiring • Uniform accessories for sizes S00, S0, S2 and S3
with the preassembled complete units (only one article • Spring-loaded terminals possible throughout: Enhanced
number 3RA2) operational reliability (vibration-resistant wiring) and less
• Plug-in connectors from the motor starter protector to all types wiring work thanks to plug-in connections (S00 and S0 only)
of SIRIUS controls, for quicker and error-free assembly of • Power loss 5 to 10% smaller than for comparable devices,
feeders with screw and spring-loaded terminals hence lower energy consumption
• High planning reliability through consistent combination • Connection of feeders to the control system through
tests for fuseless and fused configuration in accordance standardized system connection (IO-Link and AS-i),
with IEC and UL/CSA for fast integration in TIA and less wiring work
• Comprehensive approvals for use world-wide on request,
see page 16/9 onwards.
• High operational reliability through short-circuit breaking
capacity of 150 kA with type of coordination "1" and "2"
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
General data
■ Technical specifications
More information
Industry Mall, see www.siemens.com/product?3RA2 FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/16289/faq
Equipment Manual, see
https://support.industry.siemens.com/cs/ww/en/view/60284351
Configuration Manual, see
https://support.industry.siemens.com/cs/ww/en/view/39714188
Direct-on-line starters/ Size Connection method Mounting Control voltage Width W Height H Depth D
reversing starters
mm mm mm
Mounting dimensions
Direct-on-line starters S00 Screw terminals DIN rails AC/DC 45 167 97
3RA21. 3RA211. Busbar adapters AC/DC 45 200 155
(Size S3 or larger is only Spring-loaded terminals DIN rails AC/DC 45 198 97
available for self-assembly) Busbar adapters AC/DC 45 260 155
S0 Screw terminals DIN rails AC 45 193 97
3RA212. DC 45 193 107
H
W
Spring-loaded terminals DIN rails AC/DC 45 243 107
Busbar adapters AC/DC 45 260 165
S2 Screw terminals DIN rails AC/DC 55 274 150
3RA213./3RA215. Busbar adapters AC/DC 55 350 208
S3 Screw terminals DIN-rail adapters AC/DC 70 333 198
(self-assembly only)
Reversing starters S00 Screw terminals DIN rails AC/DC 90 170 97
3RA22. 3RA221. Busbar adapters AC/DC 90 200 155
8
(Size S2 or larger is only Spring-loaded terminals DIN rails AC/DC 90 204 97
available for self-assembly) Busbar adapters AC/DC 90 260 155
S0 Screw terminals DIN-rail adapters AC 90 265 120.3
3RA222. DC 90 265 130
Busbar adapters AC 90 260 155
DC 90 260 165
Spring-loaded terminals DIN-rail adapters AC/DC 90 270 131
Busbar adapters AC/DC 90 260 165
S2 Screw terminals DIN rails AC/DC 120 295 175
(self-assembly only) Busbar adapters AC/DC 120 361 208
S3 Screw terminals DIN-rail adapters AC/DC 150 333 198
(self-assembly only)
90° 90°
Important: According to DIN 43602 start command "I" at the right or top
Shock resistance IEC 60068-2-27 g/ms 6/11 (sine pulse) On request
Degree of protection IP on the front According to IP20
IEC 60529
Touch protection on the front According to Finger-safe for vertical touching from the front
IEC 60529
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
General data
Power consumption of the solenoid coils with contactors See technical specifications of the contactor, page 3/26 onwards
Solenoid coil operating range with contactors
Endurance of the motor starter protector
• Mechanical endurance Oper- 100 000 Up to 52 A: 50 000 25 000
ating
cycles
• Electrical endurance Oper- 100 000 From 59 A: 20 000 25 000
ating
cycles
• Max. switching frequency per hour (motor starts) 1/h 15
Endurance of contactor
• Mechanical endurance Oper- 30 million 10 million
ating
cycles
• Electrical endurance Oper- See endurance characteristic curves of the contactors, page 3/26 onwards
ating
cycles
Phase failure sensitivity According to ✓
of the motor starter protector IEC 60947-1,
EN 60947-1
(VDE 0660 Part 102)
Isolating features of the According to ✓
motor starter protector IEC 60947-2,
EN 60947-2
(VDE 0660 Part 101)
Main and EMERGENCY STOP switch According to ✓
characteristics of the motor starter IEC 60204-1, (With overvoltage releases of category "1"
protector and accessories EN 60204-1 under conditions of proper use)
(VDE 0113 Part 1)
Protective separation between main and According to V Up to 400
auxiliary circuits EN 60947-1, Annex N
Mirror contacts for contactors ✓
Integrated auxiliary switches According to IEC 60947-4-1, Annex F
✓ Function available
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
General data
8
• Solid or stranded mm2 2 x (0.5 ... 4) 2 x (1 ... 10) --
• Finely stranded without end sleeve mm2 2 x (0.5 ... 2.5) 2 x (1 ... 6) --
• Finely stranded with end sleeve (DIN 46228) mm2 2 x (0.5 ... 2.5) 2 x (1 ... 6) --
• AWG cables, solid or stranded AWG 2 x (20 ... 12) 2 x (18 ... 8) --
Max. external diameter of the conductor insulation mm 3.6 3.6 --
1)
If two different conductor cross-sections are connected to one clamping
point, both cross-sections must be in the range specified.
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
3RA21 direct-on-line starters > for DIN-rail mounting or screw fixing IE3 ready IE4 ready IE3/IE4 ready
AC-3e
1)
Push-in lugs, see "Accessories", page 8/52.
2) Auxiliary switches, see "Accessories", page 8/45.
3)
The actual starting and rated data of the motor to be protected must be
considered when selecting the units.
4) Suitable for use with IE3 and IE4 motors up to a starting current of 256 A.
For higher starting currents we recommend using size S2.
5)
Maximum permissible current setting at motor starter protector 65 A, as the
maximum permissible current of the 3RA2931-1AA00 link module is 65 A.
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
AC-3e E3 ready IE4 ready IE3/IE4 ready 3RA21 direct-on-line starters > for DIN-rail mounting or screw fixing
8
4 8.5 7 ... 10 11-1JA10 16-1AP01 3RA2110-1JA16-1AP0 1 1 unit 41D
5.5 11.5 9 ... 12.5 11-1KA10 17-1AP01 3RA2110-1KA17-1AP0 1 1 unit 41D
7.5 15.5 10 ... 16 11-4AA10 18-1AP01 3RA2110-4AA18-1AP0 1 1 unit 41D
1)
Push-in lugs, see "Accessories", page 8/52.
2)
Auxiliary switches, see "Accessories", page 8/45.
3) The actual starting and rated data of the motor to be protected must be
considered when selecting the units.
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
3RA21 direct-on-line starters > for DIN-rail mounting or screw fixing IE3 ready IE4 ready IE3/IE4 ready
AC-3e
Direct-on-line starting Rated control supply voltage
50 Hz 230 V AC for S2 and S3
With screw terminals
• Screw fixing with two push-in lugs per load feeder
possible1)
• The motor starter protector and contactor are
mechanically and electrically connected by means
of the link module.
• Auxiliary switches2) on the motor starter protector
and the contactor can be easily fitted thanks to the
modular system.
• Integrated auxiliary switches:
3RA2130 Contactor sizes S2 and S3: 1 NO + 1 NC
Size Standard Adjustable Comprising the following Fuseless PU PS* PG
three-phase current single devices load feeder (UNIT,
motor 4-pole at response value SET, M)
400 V AC3) of the inverse-
time delayed
Standard Motor overload Motor + Contactor + Link Screw terminals
output current I release starter module
P (guide protector
value)
Article No. Basic
price
kW A A per PU
Type of coordination "2" at Iq = 100 kA at 400 V
(the motor starter protector is compatible with type of coordination "2")
3RV20 3RT20 3RA ToC
2
S2 15 29 22 ... 32 31-4EA10 35-1AP00 2931-1AA00 3RA2130-4EA35-0AP0 1 1 unit 41D
18.5 35 28 ... 36 31-4PA10 3RA2130-4PA35-0AP0 1 1 unit 41D
18.5 35 32 ... 40 31-4UA10 3RA2130-4UA35-0AP0 1 1 unit 41D
22 41 35 ... 45 31-4VA10 36-1AP00 3RA2130-4VA36-0AP0 1 1 unit 41D
22 41 42 ... 50 31-4WA10 3RA2130-4WA36-0AP0 1 1 unit 41D
8
1)
Push-in lugs, see "Accessories", page 8/52.
2)
Auxiliary switches, see "Accessories", page 8/45.
3) The actual starting and rated data of the motor to be protected must be
considered when selecting the units.
4)
Maximum permissible current setting at motor starter protector 65 A, as the
maximum permissible current of the 3RA2931-1AA00 link module is 65 A.
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
AC-3e E3 ready IE4 ready IE3/IE4 ready 3RA21 direct-on-line starters > for DIN-rail mounting or screw fixing
8
0.12 0.4 0.35 ... 0.5 11-0FA20 3RA2110-0FE15-1AP0 1 1 unit 41D
0.18 0.6 0.45 ... 0.63 11-0GA20 3RA2110-0GE15-1AP0 1 1 unit 41D
0.18 0.6 0.55 ... 0.8 11-0HA20 3RA2110-0HE15-1AP0 1 1 unit 41D
0.25 0.85 0.7 ... 1 11-0JA20 3RA2110-0JE15-1AP0 1 1 unit 41D
0.37 1.1 0.9 ... 1.25 11-0KA20 3RA2110-0KE15-1AP0 1 1 unit 41D
0.55 1.5 1.1 ... 1.6 11-1AA20 3RA2110-1AE15-1AP0 1 1 unit 41D
0.75 1.9 1.4 ... 2 11-1BA20 3RA2110-1BE15-1AP0 1 1 unit 41D
0.75 1.9 1.8 ... 2.5 11-1CA20 3RA2110-1CE15-1AP0 1 1 unit 41D
1.1 2.7 2.2 ... 3.2 11-1DA20 3RA2110-1DE15-1AP0 1 1 unit 41D
1.5 3.6 2.8 ... 4 11-1EA20 3RA2110-1EE15-1AP0 1 1 unit 41D
S0 1.5 3.6 3.5 ... 5 21-1FA20 24-2AP00 21-2AA00 3RA2120-1FE24-0AP0 1 1 unit 41D
2.2 4.9 4.5 ... 6.3 21-1GA20 3RA2120-1GE24-0AP0 1 1 unit 41D
3 6.5 5.5 ... 8 21-1HA20 3RA2120-1HE24-0AP0 1 1 unit 41D
4 8.5 7 ... 10 21-1JA20 3RA2120-1JE24-0AP0 1 1 unit 41D
5.5 11.5 9 ... 12.5 21-1KA20 3RA2120-1KE24-0AP0 1 1 unit 41D
7.5 15.5 10 ... 16 21-4AA20 26-2AP00 3RA2120-4AE26-0AP0 1 1 unit 41D
7.5 15.5 13 ... 20 21-4BA20 27-2AP00 3RA2120-4BE27-0AP0 1 1 unit 41D
11 22 16 ... 22 21-4CA20 3RA2120-4CE27-0AP0 1 1 unit 41D
11 22 18 ... 25 21-4DA20 3RA2120-4DE27-0AP0 1 1 unit 41D
15 28 23 ... 28 21-4NA20 3RA2120-4NE27-0AP0 1 1 unit 41D
15 294) 27 ... 32 21-4EA20 3RA2120-4EE27-0AP0 1 1 unit 41D
Type of coordination "1" at Iq = 150 kA at 400 V
(the motor starter protector is compatible with type of coordination "2")
S00 For load feeders for lower outputs, see this table at ToC
type of coordination "2". 1
1.5 3.6 3.5 ... 5 11-1FA20 15-2AP01 11-2AA00 3RA2110-1FE15-1AP0 1 1 unit 41D
2.2 4.9 4.5 ... 6.3 11-1GA20 3RA2110-1GE15-1AP0 1 1 unit 41D
3 6.5 5.5 ... 8 11-1HA20 3RA2110-1HE15-1AP0 1 1 unit 41D
4 8.5 7 ... 10 11-1JA20 16-2AP01 3RA2110-1JE16-1AP0 1 1 unit 41D
5.5 11.5 9 ... 12.5 11-1KA20 17-2AP01 3RA2110-1KE17-1AP0 1 1 unit 41D
7.5 15.5 10 ... 16 11-4AA20 18-2AP01 3RA2110-4AE18-1AP0 1 1 unit 41D
1)
Push-in lugs, see "Accessories", page 8/52.
2) Auxiliary switches, see "Accessories", page 8/45.
3)
The actual starting and rated data of the motor to be protected must be
considered when selecting the units.
4)
Suitable for use with IE3 and IE4 motors up to a starting current of 256 A.
For higher starting currents we recommend using size S2.
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
3RA21 direct-on-line starters > for DIN-rail mounting or screw fixing IE3 ready IE4 ready IE3/IE4 ready
AC-3e
Direct-on-line starting Rated control supply voltage 24 V DC
With screw terminals
• Screw fixing with two push-in lugs per load feeder
possible1)
• The motor starter protector and contactor are
mechanically and electrically connected by means
of the link module.
• Auxiliary switches2) on the motor starter protector
and the contactor can be easily fitted thanks to the
modular system.
• Integrated auxiliary switches:
Contactor size S00: 1 NO,
3RA2110 3RA2120 3RA2150 Contactor sizes S0, S2 and S3: 1 NO + 1 NC
Size Standard Adjustable Comprising the following Fuseless PU PS* PG
three-phase current single devices load feeder (UNIT,
motor 4-pole at response value SET, M)
400 V AC3) of the inverse-
time delayed
Standard Motor overload Motor + Contactor + Link Screw terminals
output current I release starter module
P (guide protector
value)
Article No. Basic
price
kW A A per PU
Type of coordination "2" at Iq = 150 kA at 400 V
(also compatible with type of coordination "1")
3RV20 3RT20 3RA ToC
2
S00 0.06 0.2 0.14 ... 0.2 11-0BA10 15-1BB41 1921-1DA00 3RA2110-0BA15-1BB4 1 1 unit 41D
0.06 0.2 0.18 ... 0.25 11-0CA10 3RA2110-0CA15-1BB4 1 1 unit 41D
0.09 0.3 0.22 ... 0.32 11-0DA10 3RA2110-0DA15-1BB4 1 1 unit 41D
0.09 0.3 0.28 ... 0.4 11-0EA10 3RA2110-0EA15-1BB4 1 1 unit 41D
0.12 0.4 0.35 ... 0.5 11-0FA10 3RA2110-0FA15-1BB4 1 1 unit 41D
8
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
AC-3e E3 ready IE4 ready IE3/IE4 ready 3RA21 direct-on-line starters > for DIN-rail mounting or screw fixing
8
5.5 11.5 9 ... 12.5 11-1KA10 17-1BB41 3RA2110-1KA17-1BB4 1 1 unit 41D
7.5 15.5 10 ... 16 11-4AA10 18-1BB41 3RA2110-4AA18-1BB4 1 1 unit 41D
1) Push-in lugs, see "Accessories", page 8/52.
2)
Auxiliary switches, see "Accessories", page 8/45.
3)
The actual starting and rated data of the motor to be protected must be
considered when selecting the units.
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
3RA21 direct-on-line starters > for DIN-rail mounting or screw fixing IE3 ready IE4 ready IE3/IE4 ready
AC-3e
Direct-on-line starting Rated control supply voltage 24 V DC
With screw terminals
• Screw fixing with two push-in lugs per load feeder
possible1)
• The motor starter protector and contactor are
mechanically and electrically connected by means
of the link module.
• Auxiliary switches2) on the motor starter protector
and the contactor can be easily fitted thanks to the
modular system.
• Integrated auxiliary switches:
3RA2130 Contactor sizes S2 and S3: 1 NO + 1 NC
Size Standard Adjustable Comprising the following Fuseless PU PS* PG
three-phase current single devices load feeder (UNIT,
motor 4-pole at response value SET, M)
400 V AC3) of the inverse-
time delayed
Standard Motor overload Motor + Contactor + Link Screw terminals
output current I release starter module
P (guide protector
value)
Article No. Basic
price
kW A A per PU
Type of coordination "2" at Iq = 100 kA at 400 V
(the motor starter protector is compatible with type of coordination "2")
3RV20 3RT20 3RA ToC
2
S2 15 29 22 ... 32 31-4EA10 35-1NB30 2931-1AA00 3RA2130-4EA35-0NB3 1 1 unit 41D
18.5 35 28 ... 36 31-4PA10 3RA2130-4PA35-0NB3 1 1 unit 41D
18.5 35 32 ... 40 31-4UA10 3RA2130-4UA35-0NB3 1 1 unit 41D
22 41 35 ... 45 31-4VA10 36-1NB30 3RA2130-4VA36-0NB3 1 1 unit 41D
22 41 42 ... 50 31-4WA10 3RA2130-4WA36-0NB3 1 1 unit 41D
30 55 49 ... 59 31-4XA10 37-1NB30 3RA2130-4XA37-0NB3 1 1 unit 41D
8
1)
Push-in lugs, see "Accessories", page 8/52.
2)
Auxiliary switches, see "Accessories", page 8/45.
3) The actual starting and rated data of the motor to be protected must be
considered when selecting the units.
4)
Maximum permissible current setting at motor starter protector 65 A, as the
maximum permissible current of the 3RA2931-1AA00 link module is 65 A.
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
AC-3e E3 ready IE4 ready IE3/IE4 ready 3RA21 direct-on-line starters > for DIN-rail mounting or screw fixing
8
0.18 0.6 0.45 ... 0.63 11-0GA20 3RA2110-0GE15-1BB4 1 1 unit 41D
0.18 0.6 0.55 ... 0.8 11-0HA20 3RA2110-0HE15-1BB4 1 1 unit 41D
0.25 0.85 0.7 ... 1 11-0JA20 3RA2110-0JE15-1BB4 1 1 unit 41D
0.37 1.1 0.9 ... 1.25 11-0KA20 3RA2110-0KE15-1BB4 1 1 unit 41D
0.55 1.5 1.1 ... 1.6 11-1AA20 3RA2110-1AE15-1BB4 1 1 unit 41D
0.75 1.9 1.4 ... 2 11-1BA20 3RA2110-1BE15-1BB4 1 1 unit 41D
0.75 1.9 1.8 ... 2.5 11-1CA20 3RA2110-1CE15-1BB4 1 1 unit 41D
1.1 2.7 2.2 ... 3.2 11-1DA20 3RA2110-1DE15-1BB4 1 1 unit 41D
1.5 3.6 2.8 ... 4 11-1EA20 3RA2110-1EE15-1BB4 1 1 unit 41D
S0 1.5 3.6 3.5 ... 5 21-1FA20 24-2BB40 21-2AA00 3RA2120-1FE24-0BB4 1 1 unit 41D
2.2 4.9 4.5 ... 6.3 21-1GA20 3RA2120-1GE24-0BB4 1 1 unit 41D
3 6.5 5.5 ... 8 21-1HA20 3RA2120-1HE24-0BB4 1 1 unit 41D
4 8.5 7 ... 10 21-1JA20 3RA2120-1JE24-0BB4 1 1 unit 41D
5.5 11.5 9 ... 12.5 21-1KA20 3RA2120-1KE24-0BB4 1 1 unit 41D
7.5 15.5 10 ... 16 21-4AA20 26-2BB40 3RA2120-4AE26-0BB4 1 1 unit 41D
7.5 15.5 13 ... 20 21-4BA20 27-2BB40 3RA2120-4BE27-0BB4 1 1 unit 41D
11 22 16 ... 22 21-4CA20 3RA2120-4CE27-0BB4 1 1 unit 41D
11 22 18 ... 25 21-4DA20 3RA2120-4DE27-0BB4 1 1 unit 41D
15 28 23 ... 28 21-4NA20 3RA2120-4NE27-0BB4 1 1 unit 41D
15 294) 27 ... 32 21-4EA20 3RA2120-4EE27-0BB4 1 1 unit 41D
Type of coordination "1" at Iq = 150 kA at 400 V
(the motor starter protector is compatible with type of coordination "2")
S00 For load feeders for lower outputs, see this table at ToC
type of coordination "2". 1
1.5 3.6 3.5 ... 5 11-1FA20 15-2BB41 11-2AA00 3RA2110-1FE15-1BB4 1 1 unit 41D
2.2 4.9 4.5 ... 6.3 11-1GA20 3RA2110-1GE15-1BB4 1 1 unit 41D
3 6.5 5.5 ... 8 11-1HA20 3RA2110-1HE15-1BB4 1 1 unit 41D
4 8.5 7 ... 10 11-1JA20 16-2BB41 3RA2110-1JE16-1BB4 1 1 unit 41D
5.5 11.5 9 ... 12.5 11-1KA20 17-2BB41 3RA2110-1KE17-1BB4 1 1 unit 41D
7.5 15.5 10 ... 16 11-4AA20 18-2BB40 3RA2110-4AE18-1BB4 1 1 unit 41D
1)
Push-in lugs, see "Accessories", page 8/52.
2)
Auxiliary switches, see "Accessories", page 8/45.
3) The actual starting and rated data of the motor to be protected must be
considered when selecting the units.
4)
Suitable for use with IE3 and IE4 motors up to a starting current of 256 A.
For higher starting currents we recommend using size S2.
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
3RA21 direct-on-line starters > for 60 mm busbars IE3 ready IE4 ready IE3/IE4 ready
AC-3e
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
AC-3e E3 ready IE4 ready IE3/IE4 ready 3RA21 direct-on-line starters > for 60 mm busbars
8
0.18 0.6 0.45 ... 0.63 11-0GA20 3RA2110-0GH15-1AP0 1 1 unit 41D
0.18 0.6 0.55 ... 0.8 11-0HA20 3RA2110-0HH15-1AP0 1 1 unit 41D
0.25 0.85 0.7 ... 1 11-0JA20 3RA2110-0JH15-1AP0 1 1 unit 41D
0.37 1.1 0.9 ... 1.25 11-0KA20 3RA2110-0KH15-1AP0 1 1 unit 41D
0.55 1.5 1.1 ... 1.6 11-1AA20 3RA2110-1AH15-1AP0 1 1 unit 41D
0.75 1.9 1.4 ... 2 11-1BA20 3RA2110-1BH15-1AP0 1 1 unit 41D
0.75 1.9 1.8 ... 2.5 11-1CA20 3RA2110-1CH15-1AP0 1 1 unit 41D
1.1 2.7 2.2 ... 3.2 11-1DA20 3RA2110-1DH15-1AP0 1 1 unit 41D
1.5 3.6 2.8 ... 4 11-1EA20 3RA2110-1EH15-1AP0 1 1 unit 41D
S0 1.5 3.6 3.5 ... 5 21-1FA20 24-2AP00 21-2AA00 3RA2120-1FH24-0AP0 1 1 unit 41D
2.2 4.9 4.5 ... 6.3 21-1GA20 + 8US1251- 3RA2120-1GH24-0AP0 1 1 unit 41D
3 6.5 5.5 ... 8 21-1HA20 5NT113) 3RA2120-1HH24-0AP0 1 1 unit 41D
4 8.5 7 ... 10 21-1JA20 3RA2120-1JH24-0AP0 1 1 unit 41D
5.5 11.5 9 ... 12.5 21-1KA20 3RA2120-1KH24-0AP0 1 1 unit 41D
7.5 15.5 10 ... 16 21-4AA20 26-2AP00 3RA2120-4AH26-0AP0 1 1 unit 41D
7.5 15.5 13 ... 20 21-4BA20 27-2AP00 3RA2120-4BH27-0AP0 1 1 unit 41D
11 22 16 ... 22 21-4CA20 3RA2120-4CH27-0AP0 1 1 unit 41D
11 22 18 ... 25 21-4DA20 3RA2120-4DH27-0AP0 1 1 unit 41D
15 28 23 ... 28 21-4NA20 3RA2120-4NH27-0AP0 1 1 unit 41D
15 294) 27 ... 32 21-4EA20 3RA2120-4EH27-0AP0 1 1 unit 41D
Type of coordination "1" at Iq = 150 kA at 400 V
(the motor starter protector is compatible with type of coordination "2")
S00 For load feeders for lower outputs, see this table at ToC
type of coordination "2". 1
1.5 3.6 3.5 ... 5 11-1FA20 15-2AP01 11-2AA00 3RA2110-1FH15-1AP0 1 1 unit 41D
2.2 4.9 4.5 ... 6.3 11-1GA20 + 8US1251- 3RA2110-1GH15-1AP0 1 1 unit 41D
3 6.5 5.5 ... 8 11-1HA20 5DT11 3RA2110-1HH15-1AP0 1 1 unit 41D
4 8.5 7 ... 10 11-1JA20 16-2AP01 3RA2110-1JH16-1AP0 1 1 unit 41D
5.5 11.5 9 ... 12.5 11-1KA20 17-2AP01 3RA2110-1KH17-1AP0 1 1 unit 41D
7.5 15.5 10 ... 16 11-4AA20 18-2AP01 3RA2110-4AH18-1AP0 1 1 unit 41D
1)
Auxiliary switches, see "Accessories", page 8/45.
2) The actual starting and rated data of the motor to be protected must be
considered when selecting the units.
3)
A 3RA2911-1CA00 spacer for height compensation on AC contactors size
S0 with spring-loaded terminals is included in the scope of supply.
4)
Suitable for use with IE3 and IE4 motors up to a starting current of 256 A.
For higher starting currents we recommend using size S2.
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
3RA21 direct-on-line starters > for 60 mm busbars IE3 ready IE4 ready IE3/IE4 ready
AC-3e
Direct-on-line starting Rated control supply voltage 24 V DC
With screw terminals
• With busbar adapter
• The motor starter protector and contactor are
mechanically and electrically connected by means
of the link module.
• Auxiliary switches1) on the motor starter protector
and the contactor can be easily fitted thanks to the
modular system.
• Integrated auxiliary switches:
Contactor size S00: 1 NO,
3RA2110 3RA2120 Contactor sizes S0 and S2: 1 NO + 1 NC
Size Standard Adjustable Comprising the following Fuseless PU PS* PG
three-phase current single devices load feeder (UNIT,
motor 4-pole at response value SET, M)
400 V AC2) of the inverse-
time delayed
Standard Motor overload Motor + Contactor + Link Screw terminals
output current I release starter module
P (guide protector + Busbar
value) adapter
Article No. Basic
price
kW A A per PU
Type of coordination "2" at Iq = 150 kA at 400 V
(also compatible with type of coordination "1")
3RV20 3RT20 3RA ToC
2
S00 0.06 0.2 0.14 ... 0.2 11-0BA10 15-1BB41 1921-1DA00 3RA2110-0BD15-1BB4 1 1 unit 41D
0.06 0.2 0.18 ... 0.25 11-0CA10 + 8US1251- 3RA2110-0CD15-1BB4 1 1 unit 41D
0.09 0.3 0.22 ... 0.32 11-0DA10 5DS10 3RA2110-0DD15-1BB4 1 1 unit 41D
0.09 0.3 0.28 ... 0.4 11-0EA10 3RA2110-0ED15-1BB4 1 1 unit 41D
0.12 0.4 0.35 ... 0.5 11-0FA10 3RA2110-0FD15-1BB4 1 1 unit 41D
0.18 0.6 0.45 ... 0.63 11-0GA10 3RA2110-0GD15-1BB4 1 1 unit 41D
8
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
AC-3e E3 ready IE4 ready IE3/IE4 ready 3RA21 direct-on-line starters > for 60 mm busbars
8
0.18 0.6 0.55 ... 0.8 11-0HA20 3RA2110-0HH15-1BB4 1 1 unit 41D
0.25 0.85 0.7 ... 1 11-0JA20 3RA2110-0JH15-1BB4 1 1 unit 41D
0.37 1.1 0.9 ... 1.25 11-0KA20 3RA2110-0KH15-1BB4 1 1 unit 41D
0.55 1.5 1.1 ... 1.6 11-1AA20 3RA2110-1AH15-1BB4 1 1 unit 41D
0.75 1.9 1.4 ... 2 11-1BA20 3RA2110-1BH15-1BB4 1 1 unit 41D
0.75 1.9 1.8 ... 2.5 11-1CA20 3RA2110-1CH15-1BB4 1 1 unit 41D
1.1 2.7 2.2 ... 3.2 11-1DA20 3RA2110-1DH15-1BB4 1 1 unit 41D
1.5 3.6 2.8 ... 4 11-1EA20 3RA2110-1EH15-1BB4 1 1 unit 41D
S0 1.5 3.6 3.5 ... 5 21-1FA20 24-2BB40 21-2AA00 3RA2120-1FH24-0BB4 1 1 unit 41D
2.2 4.9 4.5 ... 6.3 21-1GA20 + 8US1251- 3RA2120-1GH24-0BB4 1 1 unit 41D
3 6.5 5.5 ... 8 21-1HA20 5NT11 3RA2120-1HH24-0BB4 1 1 unit 41D
4 8.5 7 ... 10 21-1JA20 3RA2120-1JH24-0BB4 1 1 unit 41D
5.5 11.5 9 ... 12.5 21-1KA20 3RA2120-1KH24-0BB4 1 1 unit 41D
7.5 15.5 10 ... 16 21-4AA20 26-2BB40 3RA2120-4AH26-0BB4 1 1 unit 41D
7.5 15.5 13 ... 20 21-4BA20 27-2BB40 3RA2120-4BH27-0BB4 1 1 unit 41D
11 22 16 ... 22 21-4CA20 3RA2120-4CH27-0BB4 1 1 unit 41D
11 22 18 ... 25 21-4DA20 3RA2120-4DH27-0BB4 1 1 unit 41D
15 28 23 ... 28 21-4NA20 3RA2120-4NH27-0BB4 1 1 unit 41D
15 293) 27 ... 32 21-4EA20 3RA2120-4EH27-0BB4 1 1 unit 41D
Type of coordination "1" at Iq = 150 kA at 400 V
(the motor starter protector is compatible with type of coordination "2")
S00 For load feeders for lower outputs, see this table at ToC
type of coordination "2". 1
1.5 3.6 3.5 ... 5 11-1FA20 15-2BB41 11-2AA00 3RA2110-1FH15-1BB4 1 1 unit 41D
2.2 4.9 4.5 ... 6.3 11-1GA20 + 8US1251- 3RA2110-1GH15-1BB4 1 1 unit 41D
3 6.5 5.5 ... 8 11-1HA20 5DT11 3RA2110-1HH15-1BB4 1 1 unit 41D
4 8.5 7 ... 10 11-1JA20 16-2BB41 3RA2110-1JH16-1BB4 1 1 unit 41D
5.5 11.5 9 ... 12.5 11-1KA20 17-2BB41 3RA2110-1KH17-1BB4 1 1 unit 41D
7.5 15.5 10 ... 16 11-4AA20 18-2BB40 3RA2110-4AH18-1BB4 1 1 unit 41D
1)
Auxiliary switches, see "Accessories", page 8/45.
2)
The actual starting and rated data of the motor to be protected must be
considered when selecting the units.
3) Suitable for use with IE3 and IE4 motors up to a starting current of 256 A.
For higher starting currents we recommend using size S2.
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
3RA22 reversing starters > for DIN-rail mounting or screw fixing IE3 ready IE4 ready IE3/IE4 ready
AC-3e
2
S00 0.06 0.2 0.14 ... 0.2 11-0BA10 15-1AP02 1921-1DA00 3RA2210-0BA15-2AP0 1 1 unit 41D
0.06 0.2 0.18 ... 0.25 11-0CA10 + 2913-2AA1 3RA2210-0CA15-2AP0 1 1 unit 41D
0.09 0.3 0.22 ... 0.32 11-0DA10 3RA2210-0DA15-2AP0 1 1 unit 41D
0.09 0.3 0.28 ... 0.4 11-0EA10 3RA2210-0EA15-2AP0 1 1 unit 41D
0.12 0.4 0.35 ... 0.5 11-0FA10 3RA2210-0FA15-2AP0 1 1 unit 41D
0.18 0.6 0.45 ... 0.63 11-0GA10 3RA2210-0GA15-2AP0 1 1 unit 41D
0.18 0.6 0.55 ... 0.8 11-0HA10 3RA2210-0HA15-2AP0 1 1 unit 41D
0.25 0.85 0.7 ... 1 11-0JA10 3RA2210-0JA15-2AP0 1 1 unit 41D
0.37 1.1 0.9 ... 1.25 11-0KA10 3RA2210-0KA15-2AP0 1 1 unit 41D
0.55 1.5 1.1 ... 1.6 11-1AA10 3RA2210-1AA15-2AP0 1 1 unit 41D
0.75 1.9 1.4 ... 2 11-1BA10 3RA2210-1BA15-2AP0 1 1 unit 41D
0.75 1.9 1.8 ... 2.5 11-1CA10 3RA2210-1CA15-2AP0 1 1 unit 41D
1.1 2.7 2.2 ... 3.2 11-1DA10 3RA2210-1DA15-2AP0 1 1 unit 41D
1.5 3.6 2.8 ... 4 11-1EA10 3RA2210-1EA15-2AP0 1 1 unit 41D
S0 1.5 3.6 3.5 ... 5 11-1FA10 24-1AP00 2921-1AA00 3RA2220-1FB24-0AP0 1 1 unit 41D
2.2 4.9 4.5 ... 6.3 11-1GA10 + 2923-1BB1 3RA2220-1GB24-0AP0 1 1 unit 41D
3 6.5 5.5 ... 8 11-1HA10 3RA2220-1HB24-0AP0 1 1 unit 41D
4 8.5 7 ... 10 11-1JA10 3RA2220-1JB24-0AP0 1 1 unit 41D
5.5 11.5 9 ... 12.5 11-1KA10 3RA2220-1KB24-0AP0 1 1 unit 41D
7.5 15.5 10 ... 16 21-4AA10 26-1AP00 3RA2220-4AB26-0AP0 1 1 unit 41D
7.5 15.5 13 ... 20 21-4BA10 27-1AP00 3RA2220-4BB27-0AP0 1 1 unit 41D
11 22 16 ... 22 21-4CA10 3RA2220-4CB27-0AP0 1 1 unit 41D
11 22 18 ... 25 21-4DA10 3RA2220-4DB27-0AP0 1 1 unit 41D
15 28 23 ... 28 21-4NA10 3RA2220-4NB27-0AP0 1 1 unit 41D
15 295) 27 ... 32 21-4EA10 3RA2220-4EB27-0AP0 1 1 unit 41D
S2 15 29 22 ... 32 32-4EA10 35-1AP00 2931-1AA00 Size S2 is only available for self-assembly.
18.5 35 28 ... 36 32-4PA10 + 2933-1BB1
18.5 35 32 ... 40 32-4UA10
22 41 35 ... 45 32-4VA10 36-1AP00
22 41 42 ... 50 32-4WA10
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
AC-3e E3 ready IE4 ready IE3/IE4 ready 3RA22 reversing starters > for DIN-rail mounting or screw fixing
8
5.5 11.5 9 ... 12.5 11-1KA10 17-1AP02 3RA2210-1KA17-2AP0 1 1 unit 41D
7.5 15.5 10 ... 16 11-4AA10 18-1AP02 3RA2210-4AA18-2AP0 1 1 unit 41D
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
3RA22 reversing starters > for DIN-rail mounting or screw fixing IE3 ready IE4 ready IE3/IE4 ready
AC-3e
Reversing operation Rated control supply voltage
50/60 Hz 230 V AC for S00, 50 Hz 230 V AC for S0
With spring-loaded terminals
• Screw fixing with two push-in lugs per load feeder
possible1)
• Without DIN-rail adapter for size S00
• With two DIN-rail adapters for size S0 for mechanical
reinforcement (included in the scope of supply)
• The motor starter protector and contactor are
mechanically and electrically connected by means
of the link module.
• Auxiliary switches2) on the motor starter protector
and the contactor can be easily fitted thanks to the
modular system.
• With the contactor S0, an integrated NO contact is still
3RA2210 3RA2220 available for free use.
Size Standard Adjustable Comprising the following Fuseless PU PS* PG
three-phase current single devices load feeder (UNIT,
motor 4-pole at response value SET, M)
400 V AC3) of the inverse-
Stan- Motor time delayed Motor +2 + Link module Spring-loaded
dard current I overload starter contactors + RH mounting terminals
output (guide release protector kit4)/wiring kit
P value)
Article No. Basic
price
kW A A per PU
Type of coordination "2" at Iq = 150 kA at 400 V
(also compatible with type of coordination "1")
3RV20 3RT20 3RA29 ToC
2
S00 0.06 0.2 0.14 ... 0.2 11-0BA20 15-2AP02 11-2AA00 3RA2210-0BE15-2AP0 1 1 unit 41D
0.06 0.2 0.18 ... 0.25 11-0CA20 + 2913-2AA2 3RA2210-0CE15-2AP0 1 1 unit 41D
0.09 0.3 0.22 ... 0.32 11-0DA20 3RA2210-0DE15-2AP0 1 1 unit 41D
8
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
AC-3e E3 ready IE4 ready IE3/IE4 ready 3RA22 reversing starters > for DIN-rail mounting or screw fixing
8
0.09 0.3 0.28 ... 0.4 11-0EA10 3RA2210-0EA15-2BB4 1 1 unit 41D
0.12 0.4 0.35 ... 0.5 11-0FA10 3RA2210-0FA15-2BB4 1 1 unit 41D
0.18 0.6 0.45 ... 0.63 11-0GA10 3RA2210-0GA15-2BB4 1 1 unit 41D
0.18 0.6 0.55 ... 0.8 11-0HA10 3RA2210-0HA15-2BB4 1 1 unit 41D
0.25 0.85 0.7 ... 1 11-0JA10 3RA2210-0JA15-2BB4 1 1 unit 41D
0.37 1.1 0.9 ... 1.25 11-0KA10 3RA2210-0KA15-2BB4 1 1 unit 41D
0.55 1.5 1.1 ... 1.6 11-1AA10 3RA2210-1AA15-2BB4 1 1 unit 41D
0.75 1.9 1.4 ... 2 11-1BA10 3RA2210-1BA15-2BB4 1 1 unit 41D
0.75 1.9 1.8 ... 2.5 11-1CA10 3RA2210-1CA15-2BB4 1 1 unit 41D
1.1 2.7 2.2 ... 3.2 11-1DA10 3RA2210-1DA15-2BB4 1 1 unit 41D
1.5 3.6 2.8 ... 4 11-1EA10 3RA2210-1EA15-2BB4 1 1 unit 41D
S0 1.5 3.6 3.5 ... 5 11-1FA10 24-1BB40 2921-1BA00 3RA2220-1FB24-0BB4 1 1 unit 41D
2.2 4.9 4.5 ... 6.3 11-1GA10 + 2923-1BB1 3RA2220-1GB24-0BB4 1 1 unit 41D
3 6.5 5.5 ... 8 11-1HA10 3RA2220-1HB24-0BB4 1 1 unit 41D
4 8.5 7 ... 10 11-1JA10 3RA2220-1JB24-0BB4 1 1 unit 41D
5.5 11.5 9 ... 12.5 11-1KA10 3RA2220-1KB24-0BB4 1 1 unit 41D
7.5 15.5 10 ... 16 21-4AA10 26-1BB40 3RA2220-4AB26-0BB4 1 1 unit 41D
7.5 15.5 13 ... 20 21-4BA10 27-1BB40 3RA2220-4BB27-0BB4 1 1 unit 41D
11 22 16 ... 22 21-4CA10 3RA2220-4CB27-0BB4 1 1 unit 41D
11 22 18 ... 25 21-4DA10 3RA2220-4DB27-0BB4 1 1 unit 41D
15 28 23 ... 28 21-4NA10 3RA2220-4NB27-0BB4 1 1 unit 41D
15 295) 27 ... 32 21-4EA10 3RA2220-4EB27-0BB4 1 1 unit 41D
S2 15 29 22 ... 32 32-4EA10 35-1NB30 2931-1AA00 Size S2 is only available for self-assembly.
18.5 35 28 ... 36 32-4PA10 + 2933-1BB1
18.5 35 32 ... 40 32-4UA10
22 41 35 ... 45 32-4VA10 36-1NB30
22 41 42 ... 50 32-4WA10
30 55 49 ... 59 32-4XA10 37-1NB30
30 55 54 ... 65 32-4JA10
376) 66 62 ... 73 32-4KA10 38-1NB30
S3 Size S3 available on request Size S3 is only available for self-assembly.
1)
Push-in lugs, see "Accessories", page 8/52.
2)
Auxiliary switches, see "Accessories", page 8/45.
3) The actual starting and rated data of the motor to be protected must be
considered when selecting the units.
4)
RH = Mounting kit for reversing operation and DIN-rail mounting in
sizes S0 and S2.
5)
Suitable for use with IE3 and IE4 motors up to a starting current of 256 A.
For higher starting currents we recommend using size S2.
6) Maximum permissible current setting at motor starter protector 65 A, as the
maximum permissible current of the 3RA2931-1AA00 link module is 65 A.
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
3RA22 reversing starters > for DIN-rail mounting or screw fixing IE3 ready IE4 ready IE3/IE4 ready
AC-3e
Reversing operation Rated control supply voltage 24 V DC
With screw terminals
• Screw fixing with two push-in lugs per load feeder
possible1)
• Without DIN-rail adapter for size S00
• The motor starter protector and contactor are
mechanically and electrically connected by means
of the link module.
• Auxiliary switches2) on the motor starter protector
and the contactor can be easily fitted thanks to the
modular system.
3RA2210
Size Standard Adjustable Comprising the following Fuseless PU PS* PG
three-phase current single devices load feeder (UNIT,
motor 4-pole at response SET, M)
400 V AC3) value of the Motor +2 + Link module
inverse-time starter contactors + Wiring kit
Standard Motor delayed Screw terminals
output current I overload protector
P (guide release
value)
Article No. Basic
price
kW A A per PU
Type of coordination "1" at Iq = 150 kA at 400 V
(the motor starter protector is compatible with type of coordination "2")
3RV20 3RT20 3RA ToC
1
S00 Load feeders for lower outputs, see table for type of
coordination "2" on the previous page.
1.5 3.6 3.5 ... 5 11-1FA10 15-1BB42 1921-1DA00 3RA2210-1FA15-2BB4 1 1 unit 41D
2.2 4.9 4.5 ... 6.3 11-1GA10 + 2913-2AA1 3RA2210-1GA15-2BB4 1 1 unit 41D
3 6.5 5.5 ... 8 11-1HA10 3RA2210-1HA15-2BB4 1 1 unit 41D
8
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
AC-3e E3 ready IE4 ready IE3/IE4 ready 3RA22 reversing starters > for DIN-rail mounting or screw fixing
8
0.09 0.3 0.28 ... 0.4 11-0EA20 3RA2210-0EE15-2BB4 1 1 unit 41D
0.12 0.4 0.35 ... 0.5 11-0FA20 3RA2210-0FE15-2BB4 1 1 unit 41D
0.18 0.6 0.45 ... 0.63 11-0GA20 3RA2210-0GE15-2BB4 1 1 unit 41D
0.18 0.6 0.55 ... 0.8 11-0HA20 3RA2210-0HE15-2BB4 1 1 unit 41D
0.25 0.85 0.7 ... 1 11-0JA20 3RA2210-0JE15-2BB4 1 1 unit 41D
0.37 1.1 0.9 ... 1.25 11-0KA20 3RA2210-0KE15-2BB4 1 1 unit 41D
0.55 1.5 1.1 ... 1.6 11-1AA20 3RA2210-1AE15-2BB4 1 1 unit 41D
0.75 1.9 1.4 ... 2 11-1BA20 3RA2210-1BE15-2BB4 1 1 unit 41D
0.75 1.9 1.8 ... 2.5 11-1CA20 3RA2210-1CE15-2BB4 1 1 unit 41D
1.1 2.7 2.2 ... 3.2 11-1DA20 3RA2210-1DE15-2BB4 1 1 unit 41D
1.5 3.6 2.8 ... 4 11-1EA20 3RA2210-1EE15-2BB4 1 1 unit 41D
S0 1.5 3.6 3.5 ... 5 21-1FA20 24-2BB40 21-2AA00 3RA2220-1FF24-0BB4 1 1 unit 41D
2.2 4.9 4.5 ... 6.3 21-1GA20 + 2923-1BB2 3RA2220-1GF24-0BB4 1 1 unit 41D
3 6.5 5.5 ... 8 21-1HA20 3RA2220-1HF24-0BB4 1 1 unit 41D
4 8.5 7 ... 10 21-1JA20 3RA2220-1JF24-0BB4 1 1 unit 41D
5.5 11.5 9 ... 12.5 21-1KA20 3RA2220-1KF24-0BB4 1 1 unit 41D
7.5 15.5 10 ... 16 21-4AA20 26-2BB40 3RA2220-4AF26-0BB4 1 1 unit 41D
7.5 15.5 13 ... 20 21-4BA20 27-2BB40 3RA2220-4BF27-0BB4 1 1 unit 41D
11 22 16 ... 22 21-4CA20 3RA2220-4CF27-0BB4 1 1 unit 41D
11 22 18 ... 25 21-4DA20 3RA2220-4DF27-0BB4 1 1 unit 41D
15 28 23 ... 28 21-4NA20 3RA2220-4NF27-0BB4 1 1 unit 41D
15 295) 27 ... 32 21-4EA20 3RA2220-4EF27-0BB4 1 1 unit 41D
Type of coordination "1" at Iq = 150 kA at 400 V
(the motor starter protector is compatible with type of coordination "2")
S00 For load feeders for lower outputs, see this table at ToC
type of coordination "2". 1
1.5 3.6 3.5 ... 5 11-1FA20 15-2BB42 11-2AA00 3RA2210-1FE15-2BB4 1 1 unit 41D
2.2 4.9 4.5 ... 6.3 11-1GA20 + 2913-2AA2 3RA2210-1GE15-2BB4 1 1 unit 41D
3 6.5 5.5 ... 8 11-1HA20 3RA2210-1HE15-2BB4 1 1 unit 41D
4 8.5 7 ... 10 11-1JA20 16-2BB42 3RA2210-1JE16-2BB4 1 1 unit 41D
5.5 11.5 9 ... 12.5 11-1KA20 17-2BB42 3RA2210-1KE17-2BB4 1 1 unit 41D
7.5 15.5 10 ... 16 11-4AA20 18-2BB42 3RA2210-4AE18-2BB4 1 1 unit 41D
1)
Push-in lugs, see "Accessories", page 8/52.
2) Auxiliary switches, see "Accessories", page 8/45.
3)
The actual starting and rated data of the motor to be protected must be
considered when selecting the units.
4) RH = Mounting kit for reversing operation and DIN-rail mounting in size S0.
5)
Suitable for use with IE3 and IE4 motors up to a starting current of 256 A.
For higher starting currents we recommend using size S2.
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
3RA22 reversing starters > for 60 mm busbars IE3 ready IE4 ready IE3/IE4 ready
AC-3e
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
AC-3e E3 ready IE4 ready IE3/IE4 ready 3RA22 reversing starters > for 60 mm busbars
.
8
4 8.5 7 ... 10 11-1JA10 16-1AP02 3RA2210-1JD16-2AP0 1 1 unit 41D
5.5 11.5 9 ... 12.5 11-1KA10 17-1AP02 3RA2210-1KD17-2AP0 1 1 unit 41D
7.5 15.5 10 ... 16 11-4AA10 18-1AP02 3RA2210-4AD18-2AP0 1 1 unit 41D
1)
Auxiliary switches, see "Accessories", page 8/45.
2) The actual starting and rated data of the motor to be protected must be
considered when selecting the units.
3)
RS = Mounting kit for reversing operation and busbar mounting.
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
3RA22 reversing starters > for 60 mm busbars IE3 ready IE4 ready IE3/IE4 ready
AC-3e
Reversing operation Rated control supply voltage
50/60 Hz 230 V AC for S00, 50 Hz 230 V AC for S0
With spring-loaded terminals
• With busbar adapter and device holder (included in
the scope of supply)
• The motor starter protector and contactor are
mechanically and electrically connected by means
of the link module.
• Auxiliary switches1) on the motor starter protector
and the contactor can be easily fitted thanks to the
modular system.
• With the contactor S0, an integrated NO contact is still
3RA2210 3RA2220 available for free use.
Size Standard Adjustable Comprising the following Fuseless PU PS* PG
three-phase current single devices load feeder (UNIT,
motor 4-pole at response value SET, M)
400 V AC2) of the inverse-
Stan- Motor time delayed Motor +2 + Link module Spring-loaded
dard current I overload starter contactors + RS mounting terminals
output (guide release protector kit3)/wiring kit
P value)
Article No. Basic
price
kW A A per PU
Type of coordination "2" at Iq = 150 kA at 400 V
(also compatible with type of coordination "1")
3RV20 3RT20 3RA29 ToC
2
S00 0.06 0.2 0.14 ... 0.2 11-0BA20 15-2AP02 11-2AA00 3RA2210-0BH15-2AP0 1 1 unit 41D
0.06 0.2 0.18 ... 0.25 11-0CA20 + 13-1DB2 3RA2210-0CH15-2AP0 1 1 unit 41D
0.09 0.3 0.22 ... 0.32 11-0DA20 3RA2210-0DH15-2AP0 1 1 unit 41D
0.09 0.3 0.28 ... 0.4 11-0EA20 3RA2210-0EH15-2AP0 1 1 unit 41D
0.12 0.4 0.35 ... 0.5 11-0FA20 3RA2210-0FH15-2AP0 1 1 unit 41D
0.18 0.6 0.45 ... 0.63 11-0GA20 3RA2210-0GH15-2AP0 1 1 unit 41D
8
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
AC-3e E3 ready IE4 ready IE3/IE4 ready 3RA22 reversing starters > for 60 mm busbars
8
0.18 0.6 0.55 ... 0.8 11-0HA10 3RA2210-0HD15-2BB4 1 1 unit 41D
0.25 0.85 0.7 ... 1 11-0JA10 3RA2210-0JD15-2BB4 1 1 unit 41D
0.37 1.1 0.9 ... 1.25 11-0KA10 3RA2210-0KD15-2BB4 1 1 unit 41D
0.55 1.5 1.1 ... 1.6 11-1AA10 3RA2210-1AD15-2BB4 1 1 unit 41D
0.75 1.9 1.4 ... 2 11-1BA10 3RA2210-1BD15-2BB4 1 1 unit 41D
0.75 1.9 1.8 ... 2.5 11-1CA10 3RA2210-1CD15-2BB4 1 1 unit 41D
1.1 2.7 2.2 ... 3.2 11-1DA10 3RA2210-1DD15-2BB4 1 1 unit 41D
1.5 3.6 2.8 ... 4 11-1EA10 3RA2210-1ED15-2BB4 1 1 unit 41D
S0 1.5 3.6 3.5 ... 5 11-1FA10 24-1BB40 2921-1BA00 3RA2220-1FD24-0BB4 1 1 unit 41D
2.2 4.9 4.5 ... 6.3 11-1GA10 + 2923-1DB1 3RA2220-1GD24-0BB4 1 1 unit 41D
3 6.5 5.5 ... 8 11-1HA10 3RA2220-1HD24-0BB4 1 1 unit 41D
4 8.5 7 ... 10 11-1JA10 3RA2220-1JD24-0BB4 1 1 unit 41D
5.5 11.5 9 ... 12.5 11-1KA10 3RA2220-1KD24-0BB4 1 1 unit 41D
7.5 15.5 10 ... 16 21-4AA10 26-1BB40 3RA2220-4AD26-0BB4 1 1 unit 41D
7.5 15.5 13 ... 20 21-4BA10 27-1BB40 3RA2220-4BD27-0BB4 1 1 unit 41D
11 22 16 ... 22 21-4CA10 3RA2220-4CD27-0BB4 1 1 unit 41D
11 22 18 ... 25 21-4DA10 3RA2220-4DD27-0BB4 1 1 unit 41D
15 28 23 ... 28 21-4NA10 3RA2220-4ND27-0BB4 1 1 unit 41D
15 294) 27 ... 32 21-4EA10 3RA2220-4ED27-0BB4 1 1 unit 41D
S2 15 29 22 ... 32 32-4EA10 35-1NB30 2931-1AA00 Size S2 is only available for self-assembly.
18.5 35 28 ... 36 32-4PA10 + 2933-1DB1
18.5 35 32 ... 40 32-4UA10
22 41 35 ... 45 32-4VA10 36-1NB30
22 41 42 ... 50 32-4WA10
30 55 49 ... 59 32-4XA10 37-1NB30
30 55 54 ... 65 32-4JA10
375) 66 62 ... 73 32-4KA10 38-1NB30
Type of coordination "1" at Iq = 150 kA at 400 V
(the motor starter protector is compatible with type of coordination "2")
S00 For load feeders for lower outputs, see this table at ToC
type of coordination "2". 1
1.5 3.6 3.5 ... 5 11-1FA10 15-1BB42 1921-1DA00 3RA2210-1FD15-2BB4 1 1 unit 41D
2.2 4.9 4.5 ... 6.3 11-1GA10 + 2913-1DB1 3RA2210-1GD15-2BB4 1 1 unit 41D
3 6.5 5.5 ... 8 11-1HA10 3RA2210-1HD15-2BB4 1 1 unit 41D
4 8.5 7 ... 10 11-1JA10 16-1BB42 3RA2210-1JD16-2BB4 1 1 unit 41D
5.5 11.5 9 ... 12.5 11-1KA10 17-1BB42 3RA2210-1KD17-2BB4 1 1 unit 41D
7.5 15.5 10 ... 16 11-4AA10 18-1BB42 3RA2210-4AD18-2BB4 1 1 unit 41D
1) Auxiliary switches, see "Accessories", page 8/45. 4) Suitable for use with IE3 and IE4 motors up to a starting current of 256 A.
2)
The actual starting and rated data of the motor to be protected must be For higher starting currents we recommend using size S2.
5)
considered when selecting the units. Maximum permissible current setting at motor starter protector 65 A, as the
3)
RS = Mounting kit for reversing operation and busbar mounting. maximum permissible current of the 3RA2931-1AA00 link module is 65 A.
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
3RA22 reversing starters > for 60 mm busbars IE3 ready IE4 ready IE3/IE4 ready
AC-3e
Reversing operation Rated control supply voltage 24 V DC
With spring-loaded terminals
• With busbar adapter and device holder (included in
the scope of supply)
• The motor starter protector and contactor are
mechanically and electrically connected by means
of the link module.
• Auxiliary switches1) on the motor starter protector
and the contactor can be easily fitted thanks to the
modular system.
• With the contactor S0, an integrated NO contact is still
available for free use.
3RA2210 3RA2220
Size Standard Adjustable Comprising the following Fuseless PU PS* PG
three-phase current single devices load feeder (UNIT,
motor 4-pole at response value SET, M)
400 V AC2) of the inverse-
Stan- Motor time delayed Motor +2 + Link module Spring-loaded
dard current I overload starter contactors + RS mounting terminals
output (guide release protector kit3)/wiring kit
P value)
Article No. Basic
price
kW A A per PU
Type of coordination "2" at Iq = 150 kA at 400 V
(also compatible with type of coordination "1")
3RV20 3RT20 3RA29 ToC
2
S00 0.06 0.2 0.14 ... 0.2 11-0BA20 15-2BB42 11-2AA00 3RA2210-0BH15-2BB4 1 1 unit 41D
0.06 0.2 0.18 ... 0.25 11-0CA20 + 13-1DB2 3RA2210-0CH15-2BB4 1 1 unit 41D
0.09 0.3 0.22 ... 0.32 11-0DA20 3RA2210-0DH15-2BB4 1 1 unit 41D
0.09 0.3 0.28 ... 0.4 11-0EA20 3RA2210-0EH15-2BB4 1 1 unit 41D
0.12 0.4 0.35 ... 0.5 11-0FA20 3RA2210-0FH15-2BB4 1 1 unit 41D
0.18 0.6 0.45 ... 0.63 11-0GA20 3RA2210-0GH15-2BB4 1 1 unit 41D
8
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
Accessories
■ Overview
The accessories listed here are parts and add-ons for components for the customer assembly of fuseless load feeders.
the 3RA2 direct-on-line and reversing starters as well as
8
For mounting on the left
1 NO + 1 NC S00 ... S3 3RV2901-1A 3RV2901-2A
1)
Each motor starter protector can be fitted with one transverse and one
lateral auxiliary switch. The lateral auxiliary switch with 2 NO + 2 NC is
used without a transverse auxiliary switch.
PU (UNIT, SET, M) = 1
PS* = 1 unit
PG = 41E
3RV2902-1A.. 3RV2902-2A..
Rated control supply voltage Us For motor starter protectors Screw terminals Spring-loaded
terminals
AC AC AC AC/DC
50 Hz 60 Hz 50/60 Hz 50/60 Hz, Article No. Price Article No. Price
100% ON DC per PU per PU
period1) 5 s ON
period2)
V V V V Size
Auxiliary releases for motor starter protectors3)
Undervoltage releases
230 240 -- -- S00 ... S3 3RV2902-1AP0 3RV2902-2AP0
Shunt releases
-- -- 210 ... 240 190 ... 330 S00 ... S3 3RV2902-1DP0 3RV2902-2DP0
1)
The voltage range is valid for 100% (infinite) ON period. For the complete range of accessories for the motor starter
The response voltage lies at 0.9 of the lower limit of the voltage range. protectors, see page 7/47 onwards.
2) The voltage range is valid for 5 s ON period at 50/60 Hz AC and DC.
The response voltage lies at 0.85 of the lower limit of the voltage range.
3)
One auxiliary release can be mounted on the right per motor starter
protector (does not apply to 3RV21 motor starter protectors with overload
relay function).
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
Accessories
Accessories for contactors
For contactors Version Article No. Price PU PS* PG
per PU (UNIT,
SET, M)
Size
Auxiliary switches for snapping onto the front of contactors
Screw terminals
3RH2911-1MA..
Auxiliary switches for contactors, for lateral mounting
Screw terminals
3RT1900-4RE01
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
Accessories
8
(before installing the auxiliary switch)
3RT2.3 Varistors2) 24 ... 48 -- 3RT2936-1BB00 1 1 unit 41B
127 ... 240 -- 3RT2936-1BD00 1 1 unit 41B
3RT2.3 RC element 24 ... 48 24 ... 70 3RT2936-1CB00 1 1 unit 41B
127 ... 240 150 ... 250 3RT2936-1CD00 1 1 unit 41B
3RT2.3 Diode assemblies -- 24 3RT2936-1ER00 1 1 unit 41B
For DC operation -- 30 ... 250 3RT2936-1ES00 1 1 unit 41B
3RT2936-1B.00
Size S3
For plugging onto the front side of the contactors
(before installing the auxiliary switch)
3RT2.4 Varistors2) 24 ... 48 -- 3RT2936-1BB00 1 1 unit 41B
127 ... 240 -- 3RT2936-1BD00 1 1 unit 41B
3RT2.4 Diode assemblies -- 24 3RT2936-1ER00 1 1 unit 41B
For DC operation -- 30 ... 250 3RT2936-1ES00 1 1 unit 41B
3RT2936-1B.00
For plugging into the two recesses on the left of the connection
block for auxiliary switches and coils A1 and A2.
The connecting cables are wired to A1 and A2,
see also page 3/11.
3RT2.4 RC element 24 ... 48 24 ... 70 3RT2946-1CB00 1 1 unit 41B
127 ... 240 150 ... 250 3RT2946-1CD00 1 1 unit 41B
3RT2946-1C.00
1)
Can be used for AC operation for 50/60 Hz.
Please inquire about further voltages.
2)
The varistor is already integrated on the AC/DC contactors.
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
Accessories
Accessories for the customer assembly of fuseless load feeders
For For Control circuit voltage Article No. Price PU PS* PG
motor starter contactors contactors per PU (UNIT,
protectors SET, M)
Size Size
Link modules from motor starter protector to contactor1)
Connection between motor starter protector and Screw terminals
contactor with screw terminals
Single-unit packaging
S00/S0 S00 AC/DC 3RA1921-1DA00 1 1 unit 41B
S00/S0 S0 AC 3RA2921-1AA00 1 1 unit 41B
S00/S0 S0 DC, AC/DC 3RA2921-1BA00 1 1 unit 41B
S2 S2 AC, DC, AC/DC 3RA2931-1AA00 1 1 unit 41B
S3 S3 AC, DC, AC/DC 3RA1941-1AA00 1 1 unit 41B
3RA2921-1AA00
3RA2931-1AA00
Multi-unit packaging
S00/S0 S00 AC/DC 3RA1921-1D 1 10 units 41B
S00/S0 S0 AC 3RA2921-1A 1 10 units 41B
S00/S0 S0 DC, AC/DC 3RA2921-1B 1 10 units 41B
S2 S2 AC, DC, AC/DC 3RA2931-1A 1 5 units 41B
S3 S3 AC, DC, AC/DC 3RA1941-1A 1 5 units 41B
3RA1941-1AA00
Connection between motor starter protector and Spring-loaded
contactor with spring-loaded terminals terminals
8
Single-unit packaging
S00 S00 AC/DC 3RA2911-2AA00 1 1 unit 41B
S0 S0 AC2), DC, AC/DC 3RA2921-2AA00 1 1 unit 41B
Multi-unit packaging
S00 S00 AC/DC 3RA2911-2A 1 10 units 41B
3RA2911-2AA00 S0 S0 AC2), DC, AC/DC 3RA2921-2A 1 10 units 41B
Hybrid link modules from motor starter protector to contactor3)
Connection between motor starter protector with screw
terminals and contactor with spring-loaded terminals
Single-unit packaging
S00 S00 AC/DC 3RA2911-2FA00 1 1 unit 41B
S0 S0 AC2), DC, AC/DC 3RA2921-2FA00 1 1 unit 41B
3RA2911-2FA00
Multi-unit packaging
S00 S00 AC/DC 3RA2911-2F 1 10 units 41B
S0 S0 AC2), DC, AC/DC 3RA2921-2F 1 10 units 41B
3RA2921-2FA00
1)
The link modules from motor starter protector to contactor cannot be used Note:
for the 3RV1011, 3RV2.21-4PA1., 3RV2.21-4FA1., 3RV2.31-4K.1.,
3RV2.31-4R.1., 3RV2.32-4K.1., 3RV2.32-4R.1., 3RV27 and 3RV28 motor Link modules can be used in
starter protectors/circuit breakers.
2) A spacer for height compensation on AC contactors, size S0, is optionally • Size S00 up to max. 16 A
available, see page 8/54. • Size S0 up to max. 32 A
3)
The hybrid link modules for motor starter protector to contactor cannot be • Size S2 up to max. 65 A
used for the 3RV1011, 3RV2.21-4PA1., 3RV2.21-4FA1., 3RV27 and 3RV28
motor starter protectors/circuit breakers. They are only suitable for Hybrid link modules can be used in
assembling direct-on-line starters.
• Size S00 up to max. 16 A
• Size S0 up to max. 32 A
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
Accessories
Single-unit packaging
3RA2931-1AA00 S00 S00 3RA2911-2GA00 1 1 unit 41B
S0 S0 3RA2921-2GA00 1 1 unit 41B
3RA1941-1AA00
8
3RA2921-2GA00
1)
The link modules from motor starter protector to soft starter and motor Note:
starter protector to solid-state contactor cannot be used for the 3RV1011,
3RV2.21-4PA1., 3RV2.21-4FA1., 3RV2.31-4K.1., 3RV2.31-4R.1., Link modules can be used in
3RV2.32-4K.1., 3RV2.32-4R.1., 3RV27 and 3RV28 motor starter
protectors/circuit breakers. • Size S00 up to max. 16 A
2) • Size S0 up to max. 32 A
To assemble the feeder between a motor starter protector and a soft starter
in size S2, the 3RA2932-1CA00 DIN-rail adapter must be used.
3) It is only permitted to assemble the feeder between the motor starter • Size S2 up to max. 65 A
protector and the soft starter in size S3 on a mounting plate.
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
Accessories
PU (UNIT, SET, M) = 1
PS* = 1 unit (unless otherwise specified)
PG = 41B
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
Accessories
3RA2916-1A
8US1998-7CB45
DIN-rail adapters
For mechanical fixing of motor starter
protector and contactor; for snapping
onto DIN rail or for screw fixing
8
S00, S00 S00, S00 Short, single-unit packaging 3RA2922-1BA00 1 1 unit 41B
S00, S00 S00, S00 Short, multi-unit packaging 3RA2922-1B 1 5 units 41B
S00, S0 S00, S0 Single-unit packaging 3RA2922-1AA00 1 1 unit 41B
S00, S0 S00, S0 Multi-unit packaging 3RA2922-1A 1 5 units 41B
S2 S2 Single-unit packaging 3RA2932-1AA00 1 1 unit 41B
S2 S2 Multi-unit packaging 3RA2932-1A 1 5 units 41B
3RA2922-1AA00
S3 S3 Single-unit packaging 3RA2942-1AA00 1 1 unit 41B
S3 S3 Multi-unit packaging 3RA2942-1A 1 5 units 41B
For mechanical fixing of motor starter
protector and soft starter; for snapping
onto DIN rail or for screw fixing
S2 S2 Single-unit packaging 3RA2932-1CA00 1 1 unit 41B
3RA2932-1CA00
Side modules for DIN-rail adapters
S00 ... S3 S00 ... S3 For DIN-rail adapters 3RA2902-1B 1 10 units 41B
10 mm wide, 96 mm long:
for widening DIN-rail adapters when
using lateral auxiliary switches,
2 units required
3RA2902-1B
Connecting wedges
For mechanical linking of DIN-rail adapters 8US1998-1AA00 100 100 units 14O
(2 units required for mounting)
8US1998-1AA00
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
Accessories
3RA2923-1BB1
S2 S2 Comprising: 3RA2933-1BB1 1 1 unit 41B
• Wiring kit for main and auxiliary circuit
• Two DIN-rail adapters
• Two side modules
• Four connecting wedges
• Mechanical interlocks
• Two connectors for two contactors
• Fixing accessories
Link modules must be ordered
separately.
3RA2933-1BB1
S3 S3 Comprising: 3RA2943-1BB1 1 1 unit 41B
• Wiring kit for main and auxiliary circuit
• Two DIN-rail adapters
• Three side modules
• Six connecting wedges
• Mechanical interlocks
• Two connectors for two contactors
• Fixing accessories
8
3RV2928-0B
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
Accessories
Busbar adapters
8
S00 25 12 200 45 690 8US1251-5DS11 1 1 unit 14O
S00/S0 25 12 260 45 690 8US1251-5DT11 1 1 unit 14O
S0 32 10 200 45 690 8US1251-5NS11 1 1 unit 14O
S0 32 10 260 45 690 8US1251-5NT11 1 1 unit 14O
Accessories2)
Device holders -- -- 200 45 -- 8US1250-5AS10 1 1 unit 14O
For lateral attachment -- -- 260 45 -- 8US1250-5AT10 1 1 unit 14O
to busbar adapters
Side modules -- -- 200 9 -- 8US1998-2BJ10 1 10 units 14O
For widening
busbar adapters
Vibration and shock kits
For high vibration and
shock loads
S2 -- -- -- -- -- 8US1998-1DA10 1 1 unit 14O
1) For the assembly of load feeders for reversing starters comprising a motor
starter protector and two contactors.
2)
Additional mounting rails for busbar adapters, see page 8/51.
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
Accessories
3RA2933-1DB1
RS mounting kits for spring-loaded terminals Spring-loaded
terminals
S00 S00 Comprising: 3RA2913-1DB2 1 1 unit 41B
S0 S0 • Wiring kit for main and auxiliary 3RA2923-1DB2 1 1 unit 41B
8
circuit
• Busbar adapters
• Device holders
• Two connecting wedges
• Mechanical interlocks
• Two connectors for two contactors
• Two spacers
(for size S0 only)
• Fixing accessories
3RA2913-1DB2 Link modules must be ordered
separately.
8US1998-1AA10
Spacers
For height compensation on AC contactors size S0 with Spring-loaded
spring-loaded terminals terminals
S0 S0 Single-unit packaging 3RA2911-1CA00 1 1 unit 41B
S0 S0 Multi-unit packaging 3RA2911-1C 1 5 units 41B
3RA2911-1CA00
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
Accessories
3RT2900-1SB20
Manuals
Configuration Manual for load feeders
see
https://support.industry.siemens.com/cs/ww/en/view/39714188.
1)
PC labeling system for individual inscription
of unit labeling plates available from:
murrplastik Systemtechnik GmbH
(see page 16/18).
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA2 load feeders
3RV29 infeed system for load feeders
■ Overview
Types of infeed for 3RA2 fuseless load feeders 8US busbar adapters for 60 mm systems
On the whole four different power infeed possibilities The load feeders are mounted directly with the aid of busbar
are available: adapters on busbar systems with 60 mm center-to-center
• Parallel wiring clearance in order to save space and to reduce infeed times
and costs.
• Use of 3-phase busbars (combination with SIRIUS motor
starter protectors and contactors possible) The busbar adapters for busbar systems with 60 mm center-to-
• 8US busbar adapters center clearance are suitable for copper busbars with a width of
12 to 30 mm. The busbars can be 4 to 5 mm or 10 mm thick.
• SIRIUS 3RV29 infeed systems
The feeders are snapped onto the adapter and connected on
Insulated 3-phase busbar system the line side. This prepared unit is then plugged directly onto the
3-phase busbar systems provide an easy, time-saving and busbar system, and is thus connected both mechanically and
clearly arranged means of feeding 3RA2 load feeders with electrically at the same time.
screw terminals. Different versions are available for sizes S00 "Selection and ordering data", see page 8/53.
and S0 and can also be used for the various different types of
motor starter protectors.
The busbars are suitable for between two and five feeders.
However, any kind of extension is possible by clamping
the connection tags of an additional busbar (rotated 180°)
underneath the terminals of the respective last motor starter
protector.
A combination of feeders of different sizes is possible with sizes
S00 and S0. Connecting pieces are available for this purpose.
The motor starter protectors are supplied by appropriate infeed
terminals.
3RV2925-5AB
3RV1915-1CB
8
NSB0_02080a
3RV2915-5B SIRIUS load feeders with busbar adapters snapped onto busbars
NSB0_02079c
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA6 compact starters
General data
■ Overview
3RA6 fuseless compact starters and infeed system for 3RA6
More information
Homepage, see www.siemens.com/sirius-compact-starters
Industry Mall, see www.siemens.com/product?3RA6
Online configurator, see www.siemens.com/sirius/configurators
8
compared to the parallel wiring method.
Communication link through IO-Link
Up to four compact starters in IO-Link version (reversing
and direct-on-line starters) can be connected together and
conveniently linked to the IO-Link master through a standardized
IO-Link connection.
The IO-Link connection enables a high density of information
in the local range.
For details regarding the communication link using IO-Link,
see page 2/88 onwards.
The diagnostics data of the process collected by the 3RA6
compact starter, e.g. short circuit, end of service life, limit
position, etc., are not only indicated on the compact starter itself
but also transmitted to the higher-level control system through
IO-Link.
Thanks to the optionally available operator panel, which can be
installed in the control cabinet door, it is easy to control the 3RA6
compact starters with IO-Link from the control cabinet door.
Permanent wiring/easy replacement
3RA6 compact starters with the integrated functionality of a motor starter Using the SIRIUS infeed system for 3RA6 (see page 8/76),
protector, contactor and electronic overload relay it is possible to carry out the wiring in advance without
Applications a compact starter having to be connected.
SIRIUS compact starters can be used wherever standard A compact starter is very easily replaced simply by pulling it out
three-phase motors or resistive loads up to 32 A of the device without disconnecting the wiring.
(approx. 15 kW/400 V) are directly started or switched. Even with screw fixing or mounting on a DIN rail there is no need
The compact starters are not suitable for the protection of to disconnect any wiring (on account of the removable main and
DC loads. control circuit terminals) in order to replace a compact starter.
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA6 compact starters
General data
Consistent solution from the infeed to the motor feeder SIRIUS 3RA6 compact starters
The SIRIUS feeder system for 3RA6 with integral PE bar is SIRIUS 3RA6 compact starters are universal motor feeders
available as a user-friendly system for supplying summation according to IEC 60947-6-2. As control and protective switching
current up to 100 A with a maximum conductor cross-section of devices (CPS) they can connect, convey and disconnect the
70 mm² and for direct connection of the motor cable without thermal, dynamic and electrical loads from short-circuit
additional intermediate terminals. currents up to Iq = 53 kA, i.e. they are practically weld-free.
They combine the functions of a motor starter protector,
Screw and spring-loaded terminals a contactor and an electronic overload relay in one enclosure.
The SIRIUS compact starters and the infeed system for 3RA6 are The versions available are the 45-mm-wide direct-on-line
available with screw and spring-loaded terminals. starters and the 90-mm-wide reversing starters.
The reversing starter version comes with not only an internal
Screw terminals electrical interlock but also with a mechanical interlock to
prevent simultaneous actuation of both directions of rotation.
Spring-loaded terminals The compact starters have isolating features in accordance
with IEC 60947-2 and can be used as disconnector units (main
The terminals are indicated in the corresponding control switch according to EN 60204 or VDE 0113). Isolation
tables by the symbols shown on orange backgrounds. is effected by moving the handle into the "OFF" position;
disconnection by means of the control contacts is not enough.
System configurator for engineering 3RA6 fuseless compact starters are available in five current
A free system configurator is available to reduce further the setting ranges. The 3RA61 and 3RA62 have two control voltage
amount of engineering work for selecting the required compact ranges (AC/DC), and the 3RA64 and 3RA65 have one control
starters and matching infeed. voltage range (DC):
Use of load feeders in conjunction with IE3 and IE4 motors Current At 400 V AC for Rated control supply voltage for
setting three-phase
range motors 3RA61, 3RA62 3RA64, 3RA65
Note: compact starters compact starters
Standard for IO-Link
For the use of SIRIUS 3RA6 compact starters in conjunction output P
with highly efficient IE3 and IE4 motors, please observe the
information on dimensioning and configuring, see A kW V AC/DC V DC
Application Manual. 0.1 ... 0.4 0.09 24 24
For more information, see page 1/8. 0.32 ... 1.25 0.37 110 ... 240
8
Types of infeed for the 3RA6 fuseless compact starters 1 ... 4 1.5
3 ... 12 5.5
On the whole four different infeed possibilities are available:
• Parallel wiring 8 ... 32 15
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA6 compact starters
General data
Overload tripping times More components of the 3RA6
The tripping time in the event of overload can be set on the Apart from the control supply voltage, "Overload" (1 CO)
device to normal starting conditions (CLASS 10) and to heavy and "Short circuit/Function fault" (1 NO) signaling contacts are
starting conditions (CLASS 20). As the breaker mechanism still already integrated into the 3RA61/3RA62 – and lockable via two
remains closed after an overload, resetting is possible by either 6-pole removable control circuit terminals. The 3RA61 has two
local Manual RESET or Auto RESET1) after three minutes auxiliary contacts (1 NO + 1 NC) for displaying the position
cooling time. of the main contacts. Unlike the 3RA61 direct-on-line starter,
the 3RA62 reversing starter has one auxiliary contact (1 NO)
With Auto RESET, there is no need to open the control cabinet. per direction of rotation per main contact.
Diagnostics options A slot for an optional auxiliary switch (either 2 NO, 2 NC or
The compact starter provides the following diagnostics options: 1 NO + 1 NC) is available for the 3RA61 and 3RA64 direct-on-
• With LEDs line starters. For the 3RA62 and 3RA65 reversing starters,
- Connection to the control voltage two slots are available (auxiliary switches, see "Accessories",
- Position of the main contacts page 8/70).
• With mechanical display Force-guided operation of the auxiliary contacts
- Tripping due to overload Force-guided operation between individual auxiliary circuits
- Tripping due to short circuit exists for the compact starter in the version as a direct-on-line
- Tripping due to malfunction (end of service life reached starter for parallel wiring (3RA61) between the auxiliary circuits
because of worn switching contacts or a worn switching of the NC contacts (NC 21-22) and the NO contacts (NO 13-14)
mechanism or faults in the control electronics) in the basic unit.
These states can also be evaluated in the higher-level control In addition, the optional auxiliary switch offers force-guided
system: contacts in the 3RA6913-1A version, each with one normally
closed contact and one normally open contact.
• With parallel wiring using the integrated auxiliary and
signaling switches of the compact starter Configurator
• With AS-Interface or IO-Link in even greater detail using
the respective communications interface
Four complement versions for 3RA61 and 3RA62 compact
starters
• For DIN-rail mounting or screw fixing:
basic version including one pair of main circuit terminals
8
and one pair of control circuit terminals
• For DIN-rail mounting or screw fixing when using the
AS-i add-on module:
without control circuit terminals because the AS-i add-on
module is plugged on instead
• For use in the infeed system for 3RA6:
without main circuit terminals because they are supplied with
the infeed system and the expansion modules
• For use in the infeed system for 3RA6 and AS-i add-on Configurator
module: without terminal complement (also for reordering
when replacing the compact starter) Advantages:
• Simple usage – from individual compact starters or also with
The control circuit terminals are always required by the compact corresponding infeed system and AS-i connection
starters for IO-Link; the main circuit terminals depend on the use
of the infeed system. • In the final configuration, you will be presented with additional
1) technical information such as CAD data and product data
The Auto RESET function is not available for versions 3RA6120-.B/.C with
a rated current of 1.25 A and 3RA6250-.B/-.C with a rated current of 4 A. sheets as well as characteristic curves, operating instructions,
The reset can be alternatively carried out by disconnecting the supply manuals, etc.
voltage A1/A2 via the NC contacts 95/96 (overload signaling contact).
The Auto RESET function is provided with this circuitry. See www.siemens.com/sirius/configurators
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA6 compact starters
General data
Article number scheme
1/0 4 With 1 pair of main circuit terminals, without control circuit terminals
Special versions
Example 3RA6 1 2 0 – 0 A B 3 0
1) Standard three-phase motor, basis 4-pole at 400 V AC; the actual starting
and rated data of the motor to be protected must be considered when
selecting the units.
Note:
The article number scheme shows an overview of product For your orders, please use the article numbers quoted in the
versions for better understanding of the logic behind the article selection and ordering data.
numbers.
■ Benefits
Product advantages
The SIRIUS 3RA6 compact starters offer a number of benefits: • Quick replacement of devices thanks to removable terminals
• Compact design saves space in the control cabinet with spring-loaded and screw terminals in the main and
control circuit
• Little planning and assembly work and far less wiring thanks
to a single complete unit with one article number • Efficient power distribution through the related SIRIUS infeed
system for 3RA6
• Low variance and therefore low stock levels, with two wide
voltage ranges and five wide setting ranges for the rated • Direct connection of the motor feeder cable to the
current SIRIUS infeed system for 3RA6 thanks to integrated PE bar
• High plant availability through integrated functionalities such • Connecting and looping through of incoming feeders up to
as prevention of main contact welding and disconnection at a cross-section of 70 mm²
end of service life • When using the infeed system for 3RA6, possibility of directly
• Enhanced productivity through automatic device RESET1) connecting the motor cable without intermediate terminals
in case of overload and differentiated detection of overload • Integration in Totally Integrated Automation thanks to
and short circuit the optional connection to AS-Interface or IO-Link
• Easy checking of the wiring and testing of the motor direction The SIRIUS 3RA6 compact starters create the basis for
prior to startup thanks to optional control kits high-availability and future-proof machine concepts.
1) The Auto RESET function is not available for versions 3RA6120-.B/.C with
a rated current of 1.25 A and 3RA6250-.B/-.C with a rated current of 4 A.
The reset can be alternatively carried out by disconnecting the supply
voltage A1/A2 via the NC contacts 95/96 (overload signaling contact).
The Auto RESET function is provided with this circuitry.
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA6 compact starters
General data
■ Technical specifications
More information
Industry Mall, see www.siemens.com/product?3RA6 Notes on security:
System Manual, see In order to protect plants, systems, machines and networks against cyber
http://support.industry.siemens.com/cs/ww/en/view/27865747. threats, it is necessary to implement – and continuously maintain – a holistic,
state-of-the-art industrial security concept. Siemens products and solutions
FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/16301/faq represent only one component of such a concept.
For more information about the subject of Industrial Security, see
www.siemens.com/industrialsecurity.
W D
NSB0_00649a
22,5° 22,5°
90° 90°
Shock resistance (sine-wave pulse) a = 60 m/s² = 6 g with 10 ms; for every 3 shocks in all axes
Vibratory load f = 4 ... 5.8 Hz; d = 15 mm; f = 5.8 ... 500 Hz; a = 20 m/s2; 10 cycles
Degree of protection IP on the front According to IEC 60529 IP20
8
Touch protection on the front According to IEC 60529 Finger-safe for vertical touching from the front
Installation altitude m Up to 2 000 above sea level without restriction
Relative air humidity % 10 ... 90
Pollution degree 3
Electrical specifications
Device standard IEC 60947-6-2
Maximum rated operational voltage Ue V 690
V 400 at 3RA6250-.E... and 3RA6500-.E...
(Reversing starter 32 A versions)
Rated frequency Hz 50/60
Rated insulation voltage Ui V 690
(pollution degree 3)
Rated impulse withstand voltage Uimp kV 6
Rated current Ie1) 0.1 ... 0.4 A A 0.4
and setting range for overload release 0.32 ... 1.25 A A 1.25
1 ... 4 A A 4
3 ... 12 A A 12
8 ... 32 A A 32
Permissible operational current of the compact starter2)
When several compact starters are mounted side-by-side in the infeed system
for 3RA6 (for more details on the various design versions,
see System Manual)
• For a control cabinet inside temperature of +40 °C % 100
• For a control cabinet inside temperature of +60 °C % 80
• For a control cabinet inside temperature of +70 °C % 60
Trip class (CLASS) According to IEC 60947-4-1, 10/20
EN 60947-4-1
(VDE 0660 Part 102)
Overload function 1:4
Ratio of lower to upper current mark
Rated service short-circuit breaking kA 53
capacity ICS at 50/60 Hz, 400 V AC
Rated service short-circuit breaking kA 1.5
capacity ICSIT at 50/60 Hz 400/690 V AC
in IT systems
1) 2)
For the use of 3RA6 compact starters in conjunction with highly efficient Details about installation conditions and the use of the compact starters,
IE3 and IE4 motors, please observe the information on dimensioning and and particularly about the derating of the rated current, can be found in the
configuring, see Application Manual. System Manual.
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA6 compact starters
General data
- Conductor - Ground kV 4 2
- Conductor - Conductor kV 2 1
• In the auxiliary circuit
- Conductor - Ground kV 2 0.51)
- Conductor - Conductor kV 1 0.51)
Auxiliary switches
• Integrated
- Position of the main contacts 1 NO + 1 NC 2 NO 1 NO + 1 NC 2 NO
- Overload/short circuit and malfunction signal 1 CO/1 NO
• Expandable
- Position of the main contacts 2 NO, 2 NC, 1 NO, 1 NC
Surge suppressors Integrated (varistor)
Electromagnetic operating mechanisms
Control voltage V 24 AC/DC 24 DC
V 110 ... 240 AC/DC --
Frequency At AC Hz 50/60 ( 5%)
Operating range 0.7 ... 1.25 Us 0.85 ... 1.2 Us
No-load switching frequency 1/h 3 600
Line protection At 10 kA mm² 2.5
At 50 kA mm² 4
Shock resistance
• Breaker mechanism OFF g 25
• Breaker mechanism ON g 15
Normal switching duty
Making capacity 12 x In
Breaking capacity 10 x In
Switching capacity dependent on Up to 12 A kW 5.5
rated current Up to 32 A kW 15
Endurance in operating cycles
• Electrical endurance At Ie = 0.9 x In and 400 V 3 ... 2x 3 000 000 2 x 1 500 000
10 000 000 3 ... 10 000 000
✓ Function available
1)
To maintain maximum interference immunity in a harsh electromagnetic
environment, additional overvoltage protection should be provided in the
control circuit. The 5SD7432-4 plug-in surge arrester with remote signaling,
for instance, is suitable, see Catalog LV 10.
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA6 compact starters
General data
8
• Off ms < 35 < 30
1)
Plus IO-Link communication.
Type 3RA6
Control circuit
Rated operational voltage
• External auxiliary switch V 400/690
• Internal auxiliary switch V 400/690
• Short-circuit signaling switch V 400
• Overload signaling switch V 400
Switching capacity
• External auxiliary switch AC-15
• Up to Ue = 230 V A 6
• Up to Ue = 400 V A 3
• Up to Ue = 289/500 V A 2
• Up to Ue = 400/690 V A 1
DC-13
• Up to Ue = 24 V A 6
• Up to Ue = 60 V A 0.9
• Up to Ue = 125 V A 0.55
• Up to Ue = 250 V A 0.27
• Internal auxiliary switch AC-15
• Up to Ue = 230 V A 6
• Up to Ue = 400 V A 3
• Up to Ue = 289/500 V A 2
• Up to Ue = 400/690 V A 1
DC-13
• Up to Ue = 24 V A 10
• Up to Ue = 60 V A 2
• Up to Ue = 125 V A 1
• Up to Ue = 250 V A 0.27
• Up to Ue = 480 V A 0.1
• Signaling switch AC-15
• Up to Ue = 230 V A 3
• Up to Ue = 400 V A 1
DC-13
• Up to Ue = 24 V A 2
• Up to Ue = 250 V A 0.11
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA6 compact starters
General data
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA6 compact starters
IE3 ready IE4 ready IE3/IE4 ready 3RA61, 3RA62 compact starters > 3RA61 direct-on-line starters
PU (UNIT, SET, M) = 1
PS* = 1 unit
NSB0_01946 PG = 42F
3RA6120-1CB32 3RA6120-2EB32
Standard three-phase Setting range Instantaneous Article No. Price Article No. Price
motor 4-pole at 400 V AC1) for electronic electronic release per PU per PU
Standard output P overload release
kW A A
For use in the infeed system for 3RA6 and
with AS-i add-on module or as a replacement device,
without main and control circuit terminals
0.09 0.1 ... 0.4 56 3RA6120-0A@30 --
0.37 0.32 ... 1.25 56 3RA6120-0B@30 --
1.5 1 ... 4 56 3RA6120-0C@30 --
5.5 3 ... 12 168 3RA6120-0D@30 --
15 8 ... 32 448 3RA6120-0E@30 --
8
Screw terminals Spring-loaded
terminals
For DIN-rail mounting or screw fixing,
with 1 pair of main circuit terminals and 1 pair of control circuit terminals
0.09 0.1 ... 0.4 56 3RA6120-1A@32 3RA6120-2A@32
0.37 0.32 ... 1.25 56 3RA6120-1B@32 3RA6120-2B@32
1.5 1 ... 4 56 3RA6120-1C@32 3RA6120-2C@32
5.5 3 ... 12 168 3RA6120-1D@32 3RA6120-2D@32
15 8 ... 32 448 3RA6120-1E@32 3RA6120-2E@32
For use in the infeed system for 3RA6,
without main circuit terminals, with 1 pair of control circuit terminals
0.09 0.1 ... 0.4 56 3RA6120-1A@33 3RA6120-2A@33
0.37 0.32 ... 1.25 56 3RA6120-1B@33 3RA6120-2B@33
1.5 1 ... 4 56 3RA6120-1C@33 3RA6120-2C@33
5.5 3 ... 12 168 3RA6120-1D@33 3RA6120-2D@33
15 8 ... 32 448 3RA6120-1E@33 3RA6120-2E@33
Article No. supplements for rated control supply voltage
• 24 V AC/DC B B
• 110 ... 240 V AC/DC P P
For DIN-rail mounting or screw fixing,
for use with AS-i add-on module
with 1 pair of main circuit terminals, without control circuit terminals
Rated control supply voltage 24 V AC/DC
0.09 0.1 ... 0.4 56 3RA6120-1AB34 3RA6120-2AB34
0.37 0.32 ... 1.25 56 3RA6120-1BB34 3RA6120-2BB34
1.5 1 ... 4 56 3RA6120-1CB34 3RA6120-2CB34
5.5 3 ... 12 168 3RA6120-1DB34 3RA6120-2DB34
15 8 ... 32 448 3RA6120-1EB34 3RA6120-2EB34
1) The actual starting and rated data of the motor to be protected must be
considered when selecting the units.
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA6 compact starters
3RA61, 3RA62 compact starters > 3RA62 reversing starters IE3 ready IE4 ready IE3/IE4 ready
NSB0_01947
PU (UNIT, SET, M) = 1
PS* = 1 unit
PG = 42F
3RA6250-1CP32 3RA6250-2DP32
Standard three-phase Setting range for electronic Instantaneous Article No. Price Article No. Price
motor 4-pole at 400 V AC1) overload release electronic release per PU per PU
Standard output P
kW A A
For use in the infeed system for 3RA6,
and with AS-i add-on module or as a replacement device,
without main and control circuit terminals
0.09 0.1 ... 0.4 56 3RA6250-0A@30 --
0.37 0.32 ... 1.25 56 3RA6250-0B@30 --
1.5 1 ... 4 56 3RA6250-0C@30 --
5.5 3 ... 12 168 3RA6250-0D@30 --
15 8 ... 32 448 3RA6250-0E@30 --
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA6 compact starters
IE3 ready IE4 ready IE3/IE4 ready 3RA64, 3RA65 compact starters for IO-Link > 3RA64 direct-on-line starters
Width 45 mm
8
1.5 1 ... 4 56 3RA6400-1CB43 3RA6400-2CB43
5.5 3 ... 12 168 3RA6400-1DB43 3RA6400-2DB43
15 8 ... 32 448 3RA6400-1EB43 3RA6400-2EB43
1)
The actual starting and rated data of the motor to be protected must be
considered when selecting the units.
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA6 compact starters
3RA64, 3RA65 compact starters for IO-Link > 3RA65 reversing starters IE3 ready IE4 ready IE3/IE4 ready
Width 90 mm
PU (UNIT, SET, M) = 1
PS* = 1 unit
3RA65 with 3RA6911-1A PG = 42F
auxiliary switch
Standard three-phase Setting range for Instantaneous electronic Article No. Price Article No. Price
motor 4-pole at 400 V AC1) electronic overload release per PU per PU
Standard output P release
Screw terminals Spring-loaded
terminals
kW A A
For DIN-rail mounting or screw fixing,
with 1 pair of main circuit terminals and 1 pair of control circuit terminals
0.09 0.1 ... 0.4 56 3RA6500-1AB42 3RA6500-2AB42
0.37 0.32 ... 1.25 56 3RA6500-1BB42 3RA6500-2BB42
1.5 1 ... 4 56 3RA6500-1CB42 3RA6500-2CB42
5.5 3 ... 12 168 3RA6500-1DB42 3RA6500-2DB42
15 8 ... 32 448 3RA6500-1EB42 3RA6500-2EB42
For use in the infeed system for 3RA6,
without main circuit terminals, with 1 pair of control circuit terminals
0.09 0.1 ... 0.4 56 3RA6500-1AB43 3RA6500-2AB43
8
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA6 compact starters
Accessories
■ Overview
Accessories for SIRIUS 3RA6 compact starters Busbar adapters for 60 mm systems
The following accessories are available specially for the 3RA6 The compact starters are mounted directly with the aid of busbar
compact starters: adapters on busbar systems with 60 mm center-to-center
• Infeed system for 3RA6, see page 8/76 onwards clearance in order to save space and to reduce infeed times
and costs. These feeders are suitable for copper busbars with
• For AS-i add-on modules, see "Add-on modules for a width from 12 to 30 mm. The busbars can be 4 to 5 mm
AS-Interface", page 8/74 onwards or 10 mm thick.
• External auxiliary switches: Snap-on auxiliary switch as
versions 2 NO, 2 NC and 1 NO + 1 NC with screw or spring- The 8US busbar system can be loaded with a maximum
loaded terminals; the contacts of the auxiliary switch open and summation current of 630 A.
close jointly with the main contacts of the compact starter. The "reversing starter" version requires a device holder
The NC contacts are designed as mirror contacts. alongside the busbar adapter for lateral mounting.
• Control kit: Aid for manually closing the main contacts in order The compact starters are snapped onto the adapter and
to check the wiring and motor direction under conditions of connected on the line side. This prepared unit is then plugged
short-circuit protection directly onto the busbar system, and is thus connected both
• Adapter for screw fixing the compact starter, including mechanically and electrically at the same time.
push-in lugs
For further accessories, such as incoming and outgoing
• Main circuit terminal: Available with screw and spring-loaded terminals, flat copper profiles etc., see Catalog LV 10.
terminals
• Main circuit terminal mixed connection method: Accessories for SIRIUS 3RA6 compact starters in
With the main circuit terminal mixed connection method, IO-Link version
it is also possible to switch from screw connection on the The following accessories are available specially for the 3RA64,
line side to spring-loaded terminals on the outgoing side in 3RA65 compact starters:
the main circuit. • Additional connecting cables for side-by-side mounting of up
This means for example that several compact starters can be to four compact starters
mounted side by side and be cost-efficiently connected using
the 3-phase busbars on the infeed side. The motors are then • Operator panel for on-site control and diagnostics of up to four
connected directly by the quick and reliably contacting compact starters coupled to each other
spring-loaded terminals.
8
Accessories for UL applications
The terminal block for "Self-Protected Combination Motor
Controller (Type E)" is available for complying with the clearance
and creepage distances required according
to UL 508.
Accessories for infeed using 3-phase busbar systems
The 3RV1915-1.B 3-phase busbars can be used as an easy,
time-saving and clearly arranged means of feeding
SIRIUS 3RA6 compact starters with screw terminals.
Motor starter protector sizes S00 and S0 can also be integrated.
The busbars are suitable for between two and five devices.
However, any kind of extension up to a maximum summation
current of 63 A is possible by clamping the tags of an additional
busbar (rotated by 180°) underneath the terminals of the
respective last circuit breaker.
Motor starter protectors S00 and S0 of the 3RV2 series can be
combined in any way. The motor starter protectors are supplied
by appropriate infeed terminals. Special infeed terminals are
required for constructing "Starters (Type E)" according to
UL/CSA.
The 3-phase busbar systems have touch protection but empty
connection tags must be fitted with covers. They are designed
for any short-circuit stress which can occur at the output side of
connected SIRIUS 3RA6 compact starters or motor starter
protectors.
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA6 compact starters
Accessories
3RA6950-0A
Adapters for screw fixing the 3RA6940-0A 1 1 unit 42F
compact starter
(set including push-in lugs)
Direct-on-line starters require one set,
reversing starters two sets.
3RA6940-0A
Screw terminals
3RA6920-1A
Control circuit terminals
(1 set comprising 2 terminals)
• For 3RA61 3RA6920-1B 1 1 unit 42F
• For 3RA62 3RA6920-1C 1 1 unit 42F
3RA6920-1B
Spring-loaded
terminals
Auxiliary switches for compact starters
• 2 NO 3RA6911-2A 1 1 unit 42F
• 2 NC 3RA6912-2A 1 1 unit 42F
• 1 NO + 1 NC (these auxiliary contacts are force-guided) 3RA6913-2A 1 1 unit 42F
3RA6911-2A
Main circuit terminals 3RA6920-2A 1 1 unit 42F
(line side and outgoing side)
3RA6920-2A
Control circuit terminals
(1 set comprising 2 terminals)
• For 3RA61 3RA6920-2B 1 1 unit 42F
• For 3RA62 3RA6920-2C 1 1 unit 42F
3RA6920-2B
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA6 compact starters
Accessories
3RA6920-3A
8
• 1 fixing terminal
3RA6935-0A
Enabling modules (replacement) 3RA6936-0A 1 1 unit 42F
Interface covers (replacement) 3RA6936-0B 1 5 units 42F
Connecting cables (round) 3RA6933-0A 1 1 unit 42F
For connecting the operator panel
10-pole, 2 000 mm
1)
10-pole connecting cables are required for EMERGENCY OFF group
concepts.
2)
Is included in the scope of supply of the SIRIUS 3RA6 compact starter
in IO-Link version.
Matching IO-Link masters, see page 2/98 onwards.
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA6 compact starters
Accessories
3RV1915-1CB
3RV1915-1DB
1)
Not suitable for 3RV21 motor starter protectors for motor protection
with overload relay function and for 3RV27 and 3RV28 circuit breakers
according to UL 489/CSA C22.2 No. 5.
3RV1915-6AB
3RV2925-5EB
3-phase infeed terminals for 3-phase busbars
Connection from below1)
2.5 … 25 2.5 … 16 10 ... 4 Input: 4; S00, S0 3RV2915-5B 1 1 unit 41E
Output:
2 ... 2.5
3RV2915-5B
1)
This terminal is connected in place of a compact starter, please take the
space requirement (45 mm) into account.
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA6 compact starters
Accessories
8US1211-1NS10
Device holders for lateral mounting alongside the busbar adapter
for 60 mm systems
Required in addition to the busbar adapter for mounting 8US1250-1AA10 1 1 unit 14O
a reversing starter
8US1250-1AA10
Tools for opening spring-loaded terminals
Screwdriver Spring-loaded
For all SIRIUS devices with spring-loaded terminals terminals
Length, approx. 200 mm, 3RA2908-1A 1 1 unit 41B
3.0 mm x 0.5 mm,
8
titanium gray/black,
3RA2908-1A partially insulated
Blank labels
Unit labeling plates1) 3RT2900-1SB20 100 340 units 41B
For SIRIUS devices
20 mm x 7 mm,
titanium gray
IC01_00181
3RT2900-1SB20
Manuals
System Manual for 3RA6 compact starter and infeed system for
the 3RA6, see
https://support.industry.siemens.com/cs/ww/en/view/27865747
1)
PC labeling system for individual inscription
of unit labeling plates available from:
murrplastik Systemtechnik GmbH
(see page 16/18).
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA6 compact starters
Add-on modules for AS-Interface
■ Overview
Various AS-i add-on modules are available for communication
of the 3RA6 compact starter with the control system using AS-i D0
AS-Interface: 3RA6120-..B3.
• Standard version
• With two local inputs
• With two free external inputs D1
AS-i
• With one free external input and one free external output
• With two free external outputs
• For local control
Y4
The AS-i add-on modules can be combined only in connection S0
with compact starters with a rated control supply voltage of AUX PWR + +
Y2
24 V AC/DC.
S1
AUX PWR - +
AS-i add-on module for local control S2
With this new module it is also possible for the connected 3RA6970-3F Automatic- 0 - Manual
compact starter to be operated directly using simple switches, Switch with 3 switch positions
i.e. without recourse to AS-i communication, if required. Shown in "0" position
NSB0_02096a
connections are connected simultaneously to both local inputs,
the AS-i add-on module will be in "Automatic" mode, i.e. it will S1 Closed Open Open
communicate with the control system through AS-Interface. S2 Open Open Closed
Local control
Opening the two inputs Y2 and Y4 will result in the direct Circuit diagram example for controlling a 3RA6120 direct-on-line starter
disconnection of the compact starter. Operation through using an AS-i add-on module for local control
AS-i communication is finished and the compact starter can
8
LEFT - RIGHT
If AS-i communication is reset, the motor is first switched off and Y4 S4
then on again when requested by the control system. AUX PWR + + S0
Y2
S1 S3
AUX PWR - +
S2
S3 Open Closed
S4 Closed Open
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA6 compact starters
Add-on modules for AS-Interface
8
• Flat, black, extender 3RK1901-0PA00 1 5 units 42C
3RK1901-0NA00,
3RK1901-0PA00
Accessories for AS-i add-on modules
AS-Interface addressing unit V3.0 3RK1904-2AB02 1 1 unit 42C
• For AS-Interface modules and sensors and
actuators with integrated AS-Interface according
to AS-i specification V3.0
• For setting the AS-i address of standard slaves, and
slaves with extended addressing mode (A/B slaves)
• With input/output test function and many other
commissioning functions
• Battery operation with four type AA batteries
(IEC LR6, NEDA 15)
• Scope of supply:
- Addressing unit with four batteries
- Addressing cable, with M12 plug to addressing plug
(hollow plug), length 1.5 m
3RK1904-2AB02
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA6 compact starters
Infeed system for 3RA6
■ Overview
More information
Homepage, see www.siemens.com/sirius-infeed-system Online configurator, see www.siemens.com/sirius/configurators
Industry Mall, see www.siemens.com/product?3RA68
The infeed system for 3RA6 compact starters enables far less the main circuit without a compact starter needing to be
wiring in the main circuit and, thanks to the easy exchangeability connected at the same time. As the result of the removable
of the compact starters, reduces the usual downtimes for terminals in the main circuit, compact starters can be integrated
maintenance work during the plant's operating phase. The in an infeed system in easy manner (without the use of tools).
infeed system provides the possibility of completely prewiring
3
4
1
9
IC01_00648
5
8
11
12
10
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA6 compact starters
Infeed system for 3RA6
In addition, the integrated PE bar means it is optionally possible + PE pick-off
to connect the motor cable directly to the infeed system without
additional intermediate terminals. The infeed system for The PE pick-off is available with screw terminals and spring-
3RA6 compact starters is designed for summation currents loaded terminals (6/10 mm2). It is snapped into the infeed
up to 100 A with a maximum conductor cross-section of system from below.
up to 70 mm² on the infeed terminal block.
, Connecting wedges
The infeed system can be mounted on a DIN rail or flat surfaces.
Two connecting wedges are used to hold together two
$ Infeed expansion modules.
The 3-phase infeed is available as an infeed with screw terminal - End covers
(25/35 mm2 up to 63 A or 50/70 mm2 up to 100 A) and as an
infeed with spring-loaded terminal (25/35 mm2 up to 63 A). On the last expansion module of a row, the socket provided for
the expansion plug can be covered by inserting the end cover.
The infeed with spring-loaded terminal can be fitted on the left
as well as on the right of an expansion module. . 45 mm adapter for SIRIUS motor starter protectors
size S0
The infeed with screw terminal is supplied only with a 3-socket
expansion module and permanently fitted on the left side. SIRIUS 3RV2 motor starter protectors size S0 with screw
terminals can be fitted to the adapter, enabling them to be
The infeeds with screw terminal enable connection of the main plugged into the infeed system.
conductors (L1, L2, L3) either from above or from below.
Terminal covers for increasing finger protection on
The infeed with screw terminal is supplied complete with one the front
end cover, the infeed with spring-loaded terminal complete with
two end covers. Universally configured terminal covers are available for the
25/35 mm2 and 50/70 mm2 3-phase infeeds with screw terminal:
% 3-socket expansion module • 3RA6880-2AB terminal covers for infeeds with screw terminal
The expansion module with three sockets for compact starters is 25/35 mm2 (3RA6812-8AB/AC)
available with screw terminals and with spring-loaded terminals. • 3RA6880-3AB terminal covers for infeeds with screw terminal
Expansion modules enable the infeed system to be expanded 50/70 mm2 (3RA6813-8AB/AC)
and can be fitted to each other in any number. The terminal covers can be used in two ways on the infeed
Two expansion modules are held together with the help of two terminals of the infeeds with screw terminal 25/35 mm² and
connecting wedges and one expansion plug. These assembly 50/70 mm² (see illustration):
8
parts are included in the scope of supply of the respective • If the terminals are connected, the cables are also covered:
expansion module. - by approx. 14 mm with the 3RA6880-2AB
- by approx. 18 mm with the 3RA6880-3AB
When the infeed system for 3RA6 compact starters is used,
the compact starters (plug-in modules) are easily assembled • On clamping points without connected cables, the covers can
and disassembled even when live. be turned once and then pushed over the clamping points for
finger-safe covering of the metal parts.
Optional possibilities:
• PE connection on motor outgoing side
• Outfeed for external auxiliary devices
• Connection to 3RV29 infeed system
• Integration of SIRIUS 3RV2 motor starter protectors size S0
up to 25 A (using 3RA6890-0BA adapter)
) PE infeed
This module enables a PE cable to be connected.
Use of the 3RA6880-2AB terminal cover on the infeed with screw terminal
The PE infeed can be ordered with screw terminals and spring- 25/35 mm² (3RA6812-8AB/AC). The upper cover increases the finger-
loaded terminals (35 mm2) and can be fitted on the left or right safety for the connected conductors. The identical lower cover is turned
of the expansion block. for use and prevents touching of the voltage-carrying metal parts of
the infeed terminal. For better recognition, the covers are shown as
* PE expansion plug transparent in this illustration and not in their original color.
The PE expansion plug is inserted from below and enables two
PE bars to be connected.
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA6 compact starters
Infeed system for 3RA6
Terminal blocks Proposal for upstream short-circuit protection devices
Using the terminal block the three phases can be fed out of The following short-circuit data apply for the components of
the system; this means that 1-phase, 2-phase and 3-phase the infeed system for 3RA6 compact starters:
components can also be integrated in the system.
Conduc- Maximum let-through Proposal for Maxi-
After the end cover is pulled out, the terminal block can be tor current Id,max and upstream mum
plugged onto an expansion module. cross- current integral I2t short-circuit prospec-
section protection device tive
Expansion plug for SIRIUS 3RV29 infeed systems Ishort-
circuit
After the end cover is pulled out, the expansion plug for the mm² kA
SIRIUS 3RV29 infeed system can be plugged onto an expansion
Short-circuit protection for
module. It connects the infeed system for 3RA6 compact 3RA681.-8A. infeed with screw terminal
starters with the SIRIUS 3RV29 infeed system. (25/35 mm2 and 50/70 mm2)
Maximum rated operational current 2.5 … 35 Id, max < 21 kA, I²t = 530 kA²s 3RV2041-4MA10 50
2.5 ... 70 (NH gG 3NA3; 315 A)
The following maximum rated operational currents apply for
the components of the infeed system for 3RA6: Short-circuit protection for infeed
with spring-loaded terminal 25/35 mm2,
3RA6830-5AC
Component Maximum rated
operational current 4 Id, max < 9.5 kA, I²t = 85 kA²s 3RV2021-4DA10 40
A 6 Id, max < 12.5 kA, I²t = 140 kA²s 3RV2031-4EA10 30
Infeed with screw terminal 50/70 mm² 100 10 Id, max < 15 kA, I²t = 180 kA²s 3RV2031-4WA10 25
Infeed with screw terminal 25/35 mm² 63 16/25 Id, max < 19 kA, I²t = 440 kA²s 3RV2031-4JA10 65
Infeed with spring-loaded terminal 25/35 mm² 63 3RV2041-4JA10 65
Expansion plug 63 35 Id, max < 21 kA, I²t = 530 kA²s 3RV2041-4MA10 50
(NH gG 3NA3; 315 A)
With side-by-side mounting of several expansion modules, Short-circuit protection for terminal
the maximum rated operational current from the second block, 3RV2917-5D
expansion module to the end of the row is 63 A. 1.5 Id, max < 7.5 kA 5SY...
1)
2.5 Id, max < 9.5 kA
4 Id, max < 9.5 kA
6 Id,max < 12.5 kA
8
1)
To prevent the possibility of short circuits, the cables on the terminal block
must be installed so that they are short-circuit-proof.
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA6 compact starters
Infeed system for 3RA6
Spring-loaded
terminals
• Spring-loaded terminals on the outgoing side 3RA6812-8AC 1 1 unit 42F
3RA6812-8AC
Infeeds with screw terminal 50/70 mm2 left
Infeed with screw terminal at line side with
a permanently fitted 3-socket expansion module
with screw or spring-loaded terminals on the
outgoing side and integrated PE bar
Expansion module with 3 sockets for
8
3 direct-on-line starters or 1 direct-on-line starter
and 1 reversing starter,
suitable for UL operation according to UL 508
3RA6813-8AB Type E
Screw terminals
3RA6813-8AC
Infeeds with spring-loaded terminals
25/35 mm2 left or right
Spring-loaded
terminals
Up to 63 A 3RA6830-5AC 1 1 unit 42F
3RA6830-5AC
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA6 compact starters
Infeed system for 3RA6
Expansion modules
2-socket expansion modules
With screw or spring-loaded terminals
and integrated PE bar
With 2 sockets for 2 direct-on-line starters or
1 reversing starter
Expansion plug and 2 connecting wedges
are included in the scope of supply.
Screw terminals
3RA6822-0AC
3-socket expansion modules
With screw or spring-loaded terminals
and integrated PE bar
With 3 sockets for 3 direct-on-line starters or
1 direct-on-line starter and 1 reversing starter
Expansion plug and 2 connecting wedges
are included in the scope of supply.
Screw terminals
8
3RA6823-0AC
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA6 compact starters
Infeed system for 3RA6
3RA6860-6AB
Spring-loaded
terminals
• Version with spring-loaded terminals 3RA6860-5AC 1 1 unit 42F
3RA6860-5AC
PE pick-offs 6/10 mm2
Screw terminals
8
3RA6870-4AB
Spring-loaded
terminals
• Version with spring-loaded terminals 3RA6870-3AC 1 1 unit 42F
3RA6870-3AC
Expansion plugs
PE expansion plugs 3RA6890-0EA 1 1 unit 42F
3RA6890-0EA
Expansion plugs 3RA6890-1AB 1 1 unit 42F
Between 2 expansion modules
Included in the scope of supply of the expansion
modules
3RA6890-1AB
Expansion plugs for SIRIUS 3RV29 infeed system 3RA6890-1AA 1 1 unit 42F
Connect infeed system for 3RA6 to
3RV29 infeed system
3RA6890-1AA
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RA6 compact starters
Infeed system for 3RA6
3RA6890-0BA
Terminal covers for infeeds with screw terminals
IP20 terminal covers for infeeds with screw terminal 3RA6880-2AB 1 1 unit 42F
25/35 mm² (3RA6812-8AB/AC)
(2 units per pack)
3RA6880-2AB
IP20 terminal covers for infeeds with screw terminal 3RA6880-3AB 1 1 unit 42F
50/70 mm² (3RA6813-8AB/AC)
(2 units per pack)
3RA6880-3AB
8
Terminal blocks
For integration of 1-phase, 2-phase and 3-phase external Spring-loaded
components terminals
• Spring-loaded terminals 3RV2917-5D 1 1 unit 41E
3RV2917-5D
Tools for opening spring-loaded terminals
Screwdriver
For all SIRIUS devices with spring-loaded terminals Spring-loaded
terminals
Length, approx. 200 mm, 3RA2908-1A 1 1 unit 41B
3.0 mm x 0.5 mm,
titanium gray/black,
3RA2908-1A partially insulated
Manuals
System Manual for 3RA6 compact starter and
infeed system for 3RA6, see
https://support.industry.siemens.com/cs/ww/en/view/27865747
Load feeders and motor starters for use in the control cabinet
■ Overview
1 3RM1 motor starters
2 Fuse modules
3 Adapters for busbar
systems/DIN rails
4
4 Device connectors
5 3-phase infeed system
6 Covers for infeed busbars
7 Sealable covers
8 Push-in lugs for wall mounting
8 3
2
1
7
6
IC01_00751
8
5
Load feeders and motor starters for use in the control cabinet
Online configurator
An online configurator with a wide range of functions is available
for the SIRIUS 3RM1 motor starters.
(see www.siemens.com/sirius/configurators):
• Create individual motor starters or a complex motor
starter group
• Individual selection options, such as direct or reversing
starting, spring-loaded or screw terminals, as well as motor
3SK + 3RM1 current and control voltage
IC01_00533
the simple combination of 3RM1 and 3SK devices Multi-unit packaging with order code X90
Functional safety in the main circuit needs to be both simple and When ordering products in multi-unit packaging, the article
flexible. number of the product concerned must be supplemented with
The unique compatibility of hybrid 3RM1 fail-safe motor starters "-Z" and, in addition, the order code "X90" must be specified.
and 3SK safety relays means that integrated functional safety Ordering example:
right through to the main circuit is no longer a problem.
3RM1201-2AA04-Z X90;
Their compact design allows the motor starters to be installed to purchase order quantity 12 units Delivery of one package
the right of the safety relay in a simple manner, just like an output containing 12 units
expansion. The wiring of the safety-related signals to the relay
can be performed simply, quickly and in an error-free manner For more information, see page 16/7.
using the device connector.
The ergonomically designed enclosure with removable
terminals and terminal labeling in the hinged cover allows for the
cables to be conveniently diagonally mounted from the front.
Either screw or spring-loaded terminals with push-in technology
are available.
Highlights
• Fail-safe disconnection of motors up to 3 kW
• Problem-free combination of fail-safe motor starters and
safety relays
• End-to-end system, simple setup using device connectors
• Ergonomic enclosure
Note:
For SIRIUS 3SK safety relays, see page 11/13.
Load feeders and motor starters for use in the control cabinet
■ Benefits
• Less space required in the control cabinet (20 to 80%) thanks • Virtually error-free wiring on the mains connection side and
to high functional density, which also means reduced wiring reduction in short-circuit protective devices by means of
and testing 3RM19 infeed system
8
• Greater endurance and reduced heat losses thanks to hybrid • ATEX certification of the overload protection of the
technology 3RM1 Failsafe motor starters: "Increased safety" type of
• Lower costs for stock keeping and configuration as a result protection EEx e according to ATEX directive 2014/34/EU
of the wide setting range of the electronic overload release • The 3RM1 motor starters can be used with highly efficient
(up to 1:5) IE3 and IE4 motors. In this regard, please observe the
• Fast wiring without tools for rigid conductors or conductors information on dimensioning and configuring, see
equipped with end sleeves thanks to spring-loaded terminals Application Manual.
(push-in) For more information, see page 1/8.
• Safety-related shutdown in accordance with SIL 3 and PL e by Standards and approvals
shutting down the control supply voltage without additional • IEC/EN 60947-4-2
devices in the main circuit • UL 60947-4-2
• The motor starters can be ideally combined with 3SK safety • CSA1)
relays for safety-related shutdown (see page 11/13) • ATEX
• Motor status feedback to the higher-level control system in • IEC 61508: SIL 3
the case of 3RM10 and 3RM12 motor starters in the 24 V DC • IEC 62061: SIL 3
version • ISO 13849-1: PL e
• CCC approval for China
1)
The CSA approval is valid for a maximum operational voltage of 400 V,
see https://support.industry.siemens.com/cs/ww/en/view/109481789.
Load feeders and motor starters for use in the control cabinet
■ Technical specifications
More information
Industry Mall, see www.siemens.com/product?3RM1 FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/16311/faq
Equipment Manual, see
https://support.industry.siemens.com/cs/ww/en/view/66295730
IC01_00469
Load feeders and motor starters for use in the control cabinet
■ Accessories
More information
Equipment Manual, see 1
https://support.industry.siemens.com/cs/ww/en/view/66295730
IC01_00169c
The busbars are available in three lengths, for two, three or five
motor starters. More than five devices can be connected by
clamping the connection tags of a second busbar underneath,
rotated 180°.
The 3-phase busbars have touch protection but empty 4
connection tags must be fitted with covers.
1 Four 3RM1 motor starters on DIN rail with one free slot
8
2 3RM1920-1AA 3-phase infeed terminal
3 Two 3RM1910-1DA 3-phase busbars rotated through 180°
for the connection of up to nine motor starters
4 Covers for three 3RM1910-6AA connection tags respectively
for unused slots
Load feeders and motor starters for use in the control cabinet
5 1 Busbar system
2 3 5
1 4 2 Cover profiles for busbars
3 Busbar adapter
4 Compact busbar adapter
IC01_00611a
8
6
7
By means of the fuse module, 3RM1 motor starters can be used in busbar systems and 8US compact busbar systems as well as on
mounting rails
Load feeders and motor starters for use in the control cabinet
IC01_00178a
IC01_00218b
Motor
8
A1 and A2 terminals of only one motor starter.
Device daisy chain connectors can be used for gaps between • For motor suppression modules that are fitted in the main
two motor starters. Device termination connectors terminate circuit, see page 8/93
a group. Note:
Using the device connectors for safe group shutdown For more information, see
In combination with the 3RM11 and 3RM13 fail-safe motor https://support.industry.siemens.com/cs/ww/en/view/109758696.
starters, the device connector can also be used for safety-
related shutdown. For this application, groups of no more than
five fail-safe motor starters can be connected using a device
connector, and the group must be terminated with a termination
connector. Removing the control voltage supply from the first
motor starter will safely shut down the whole group.
Load feeders and motor starters for use in the control cabinet
SIRIUS 3RM1 motor starters IE3 ready IE4 ready IE3/IE4 ready
Multi-unit packaging Ratings Adjustable Control supply Article No. Price PU PS* PG
see page 16/7. of three-phase current response voltage per PU (UNIT,
motors value of the inverse- SET, M)
at 400 V1) time delayed at DC at AC at
overload release 50 Hz
kW A V V
Direct-on-line starters
0 … 0.12 0.1 … 0.5 24 -- 3RM1001-@AA04 1 1 unit 41D
0.09 … 0.75 0.4 … 2 24 -- 3RM1002-@AA04 1 1 unit 41D
0.55 … 3 1.6 … 7 24 -- 3RM1007-@AA04 1 1 unit 41D
0 … 0.12 0.1 … 0.5 110 110 ... 230 3RM1001-@AA14 1 1 unit 41D
0.09 … 0.75 0.4 … 2 110 110 ... 230 3RM1002-@AA14 1 1 unit 41D
0.55 … 3 1.6 … 7 110 110 ... 230 3RM1007-@AA14 1 1 unit 41D
3RM1001-1AA04
Reversing starters
0 … 0.12 0.1 … 0.5 24 -- 3RM1201-@AA04 1 1 unit 41D
0.09 … 0.75 0.4 … 2 24 -- 3RM1202-@AA04 1 1 unit 41D
0.55 … 3 1.6 … 7 24 -- 3RM1207-@AA04 1 1 unit 41D
0 … 0.12 0.1 … 0.5 110 110 ... 230 3RM1201-@AA14 1 1 unit 41D
0.09 … 0.75 0.4 … 2 110 110 ... 230 3RM1202-@AA14 1 1 unit 41D
0.55 … 3 1.6 … 7 110 110 ... 230 3RM1207-@AA14 1 1 unit 41D
8
3RM1201-1AA04
Failsafe direct-on-line starters
0 … 0.12 0.1 … 0.5 24 -- 3RM1101-@AA04 1 1 unit 41D
0.09 … 0.75 0.4 … 2 24 -- 3RM1102-@AA04 1 1 unit 41D
0.55 … 3 1.6 … 7 24 -- 3RM1107-@AA04 1 1 unit 41D
0 … 0.12 0.1 … 0.5 110 110 ... 230 3RM1101-@AA14 1 1 unit 41D
0.09 … 0.75 0.4 … 2 110 110 ... 230 3RM1102-@AA14 1 1 unit 41D
0.55 … 3 1.6 … 7 110 110 ... 230 3RM1107-@AA14 1 1 unit 41D
3RM1101-1AA04
Failsafe reversing starters
0 … 0.12 0.1 … 0.5 24 -- 3RM1301-@AA04 1 1 unit 41D
0.09 … 0.75 0.4 … 2 24 -- 3RM1302-@AA04 1 1 unit 41D
0.55 … 3 1.6 … 7 24 -- 3RM1307-@AA04 1 1 unit 41D
0 … 0.12 0.1 … 0.5 110 110 ... 230 3RM1301-@AA14 1 1 unit 41D
0.09 … 0.75 0.4 … 2 110 110 ... 230 3RM1302-@AA14 1 1 unit 41D
0.55 … 3 1.6 … 7 110 110 ... 230 3RM1307-@AA14 1 1 unit 41D
3RM1301-1AA04
Type of electrical connection
• Screw terminals for main circuit, screw terminals for control circuit 1
• Spring-loaded terminals (push-in) for main circuit, spring-loaded terminals (push-in) 2
for control circuit
• Screw terminals for main circuit, spring-loaded terminals (push-in) for control circuit 3
1) The actual starting and rated data of the motor to be protected must be
considered when selecting the units.
Load feeders and motor starters for use in the control cabinet
3RM1920-1AA
3-phase busbars
• For 2 motor starters 3RM1910-1AA 1 1 unit 41D
3RM1910-1AA
• For 3 motor starters 3RM1910-1BA 1 1 unit 41D
3RM1910-1BA
• For 5 motor starters 3RM1910-1DA 1 1 unit 41D
3RM1910-1DA
Covers 3RM1910-6AA 1 10 units 41D
For 3 connection tags of the
8
3-phase busbars
3RM1910-6AA
Fuse modules for 3RM1 for use on busbars or mounting rails
Fuse module with 3NW6007-1 fuse 3RM1932-1AB 1 1 unit 41D
Fuse module without fuse1) 3RM1930-1AA 1 1 unit 41D
3RM1932-1AB
Adapters
Adapters for 60 mm busbar systems 8US1216-0AS00 1 1 unit 14O
22.5 mm x 200 mm x 41.5 mm
Note: The adapter can be used on busbars with
a width of 12 mm, 15 mm, 20 mm, 25 mm or 30 mm
and a thickness of 5 mm or 10 mm.
8US1216-0AS00
Adapters for 60 mm compact busbar systems 8US1616-0AK02 1 1 unit 14O
22.5 mm x 160 mm x 41.5 mm
Note: The adapter can be used on busbars with
a width of 12 mm and a thickness of 5 mm or 10 mm.
8US1616-0AK02
1) For details of alternative fuses, see Equipment Manual.
Load feeders and motor starters for use in the control cabinet
Adapters
Adapter for 35 mm DIN mounting rails 8US1716-0RK00 1 1 unit 14O
22.5 mm x 185 mm x 23.5 mm
8US1716-0RK00
Cover profiles1)2)
Cover profiles for busbars
12 mm x 5 mm x 1 000 mm 8US1922-2CA00 1 10 units 14O
40 mm or 60 mm center-to-center busbar clearance
depending on busbar system
8US1922-2CA00
15 mm x 5 mm x 1 000 mm 8US1922-2AA00 1 10 units 14O
20 mm x 5 mm x 1 000 mm
25 mm x 5 mm x 1 000 mm
30 mm x 5 mm x 1 000 mm
40 mm or 60 mm center-to-center busbar clearance
depending on busbar system
8US1922-2AA00
12 mm x 10 mm x 1 000 mm 8US1922-2BA00 1 10 units 14O
15 mm x 10 mm x 1 000 mm
20 mm x 10 mm x 1 000 mm
25 mm x 10 mm x 1 000 mm
30 mm x 10 mm x 1 000 mm
8
3ZY1212-2EA00
Device daisy chain connectors 3ZY1212-2AB00 1 1 unit 41L
For 3RM1 motor starters, 24 V DC, 22.5 mm
For gaps without motor starters in assemblies
3ZY1212-2AB00
Device termination connectors 3ZY1212-2FA00 1 1 unit 41L
For 3RM1 motor starters, 24 V DC, 22.5 mm
3ZY1212-2FA00
1) The cover profiles for busbars can be used for maintaining minimum
spacing between the load feeders.
2)
For further accessories for the configuration of a busbar system,
see Catalog LV 10.
Load feeders and motor starters for use in the control cabinet
Removable terminals
Terminals for main circuit, 2-pole
Screw terminals
3ZY1311-0AA00
Sealable covers, 22.5 mm 3ZY1321-2AA00 1 5 units 41L
8
For simple protection against unauthorized access
3ZY1321-2AA00
Coding pins for removable terminals 3ZY1440-1AA00 1 12 units 41L
For mechanical coding of the terminals
3ZY1440-1AA00
Hinged cover
Replacement cover, without terminal labeling,
22.5 mm wide
• Titanium gray 3ZY1450-1AB00 1 5 units 41L
• Yellow 3ZY1450-1BB00 1 5 units 41L
3ZY1450-1AB00
Motor suppression module
• Square 3RK1911-6EA00 1 1 unit 42D
• Round 3RK1911-6EB00 1 1 unit 42D
3RK1911-6EA00
Screwdriver Spring-loaded
For all SIRIUS devices with spring-loaded terminals terminals
Length, approx. 200 mm, 3RA2908-1A 1 1 unit 41B
3.0 mm x 0.5 mm,
titanium gray/black,
3RA2908-1A partially insulated
Load feeders and motor starters for use in the control cabinet
■ Overview
1 2 3 4 5 6 6 7
2
1
IC01_00662a
5 9
1 ET 200SP interface module
IC01_00613a
2 ET 200SP digital input
3 1 ET 200SP fail-safe motor starter 3 ET 200SP digital output
2 BaseUnit for ET 200SP motor starter 4 ET 200SP analog input
7 Dummy module consisting of
3 Fan 5 Dummy module consisting of BaseUnit + BU cover, 30 mm
BaseUnit + BU cover, 15 mm
4 3DI/LC module 8 3DI/LC module
4
6 ET 200SP motor starter F-DI and 9 Infeed bus cover
5 Infeed bus cover ET 200SP motor starter
Motor starter, BaseUnit, fan and 3DI/LC control module 3RK1308 motor starter in the ET 200SP I/O system
8
More information
Homepage, see www.siemens.com/sirius-motor-starter-et200sp Industry Online Support (SIOS) topic page with information on
Industry Mall, see www.siemens.com/product?3RK1308 the planning and operating phases, see
https://support.industry.siemens.com/cs/ww/en/view/109792664
TIA Selection Tool, see www.siemens.com/TST
Further components in the ET 200SP I/O system:
Decision support for motor start – Starting and operating three-phase • Catalog ST 70
asynchronous motors efficiently, see www.siemens.com/motorstart-guide • Homepage, see www.siemens.com/et200sp
Load feeders and motor starters for use in the control cabinet
IC01_00535b
before the first motor starter. The dummy module consists of the 7 500 V AC
6ES7193-6BP00-0BA0 or 6ES7193-6BP00-0DA0 BaseUnit and with F-DI infeed
the 6ES7133-6CV15-1AM0 BU cover 15 mm. 8 500 V AC
1 2 3 4 7 8 9 10
with F-DI loop-through
The 15 mm BU cover protects the plug contacts of the BaseUnit
against dirt. 9 without infeed
with F-DI loop-through
Electromechanical switching devices in series with hybrid motor
starters 10 without infeed
with F-DI infeed
Switching an inductive load - in particular of motors <1 kW with
high inductance - with an electromechanical switching device View of the BaseUnit infeeds for the motor starters
(e.g. contactor) can cause high and steep voltage edges.
BaseUnits are components used for mounting the
The resulting faults/damage can be prevented by first ET 200SP I/O modules.
disconnecting with the hybrid motor starter or by using
EMC suppression modules: The self-assembling voltage buses integrated into the BaseUnits
reduce wiring outlay to the single infeed (both of auxiliary and
• For 3RT2916-1P.. EMC suppression modules for direct load voltage).
mounting on the contactor, see page 3/113
• For motor suppression modules that are fitted in the main All modules following on the right are automatically supplied
circuit, see page 8/102 upon plugging the BaseUnits together, if BaseUnits are inserted
with a loop-through.
8
Note:
The rugged design and keyed connection technology enables
For more information, see use in harsh industrial conditions.
https://support.industry.siemens.com/cs/ww/en/view/109758696.
The BaseUnits are available with various infeeds for the motor
3DI/LC control module starters.
Load feeders and motor starters for use in the control cabinet
Example 3RK1908 – 0 A P 0 0 – 0 A P 0
Note:
The article number schemes show an overview of product For your orders, please use the article numbers quoted in
versions for better understanding of the logic behind the the selection and ordering data.
article numbers.
■ Benefits
The ET 200SP motor starters offer a number of advantages: • The ET 200SP motor starters can be used with highly efficient
• Fully integrated into the ET 200SP I/O system (including IE3 and IE4 motors, see Application Manual.
TIA Selection Tool and TIA Portal) Take the current characteristics of the connected motor
and motor starter into account when dimensioning.
• High degree of flexibility when it comes to safety applications In addition to the rated current, the maximum permissible
via SIMATIC F-CPU or 3SK safety relays up to SIL 3 and current range of the motor starter and the ratio of the rated
PL e Cat. 4. current to the starting current of the motor are relevant.
• Simple, integrated current value transmission For more information, see page 1/8.
• Extensive parameterization by means of TIA Portal Standards and approvals
• Increase of plant availability through fast replacement of units • IEC/EN 60947-4-2
(easy mounting and plug-in technology)
• UL 60947-4-2
• Greater endurance and reduced heat losses thanks to hybrid
technology • CSA
• Less space required in the control cabinet (20 to 80%) • ATEX
as a result of greater functional density (direct-on-line and • IEC 62061: SIL 3
reversing starters in same width) • ISO 13849-1: PL e
• Extensive diagnostics and information for preventive • CCC approval for China
maintenance
• Parameterizable inputs via 3DI/LC control module
• Less wiring and testing required as a result of integrating
several functions into a single device
• Lower overheads for stock keeping and configuration as
a result of the wide setting range of the electronic overload
release (up to 1:3)
• Technology has lower inherent power losses than speed-
controlled drive systems, so that less cooling (and smaller
footprint) are possible
Load feeders and motor starters for use in the control cabinet
■ Application
The ET 200SP motor starters are suitable for the following • Track switching and lifting table control in conveyor systems:
applications: Track switches can be implemented by means of the quick
• Switching and monitoring of stop function and lifting table controls by means of the
- 3-phase motors with overload and short-circuit protection "immediate end position disconnection" function without
(e.g. 400 V asynchronous motors for secondary drives in any laborious programming.
conveyor systems) • Safe isolation of drive from main power supply:
- 1-phase motors with overload and short-circuit protection The isolating functions in accordance with IEC 60947-1
(e.g. 230 V motors for pump applications) offer protection against inadvertent activation during plant
- Resistive loads by means of current value and diagnostics maintenance.
via the maintenance function (e.g. for heaters)
Motor starters in the process industry
• Plant monitoring and energy management in conveyor
systems: For the ET 200SP motor starters, special 3RK1908-0AP00-0.H0
By means of the phase asymmetry and zero current detection BaseUnits are available that enable the devices to also be used
during current measurement, drive belt monitoring and in the ET 200SP HA I/O system. This is typically used in process
blocking monitoring are possible, for example. engineering applications.
For more information, see https://mall.industry.siemens.com/
mall/ww/en/Catalog/Products/10398144?tree=CatalogTree.
■ Technical specifications
More information
Industry Mall, see www.siemens.com/product?3RK1308 FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/21800/faq
Equipment Manual, see
https://support.industry.siemens.com/cs/ww/en/view/109479973
8
General technical specifications
Width x height x depth mm 30 x 142 x 150
H
Load feeders and motor starters for use in the control cabinet
Ambient temperature
• During operation °C -25 ... +60
• During transport °C -40 ... +70
• During storage °C -40 ... +70
Degree of protection IP IP20
on the front
according to IEC 60529
Touch protection on Finger-safe
the front
according to IEC 60529
Connections/terminals
Type of connectable
conductor cross-sections
• At the inputs for supply
voltage
- Solid 1 x 0.5 ... 2.5 mm2 --
- Finely stranded with end 1 x 0.5 ... 2.5 mm2 --
sleeve
- Finely stranded without 1 x 0.5 ... 2.5 mm2 --
end sleeve
- Solid for AWG cables 1 x 20 ... 12 --
8
• For infeed
- Solid 1 x 1 ... 6 mm2 -- 1 x 1 ... 6 mm2 --
- Finely stranded with end 1 x 1 ... 6 mm2 -- 1 x 1 ... 6 mm2 --
sleeve
- Finely stranded without 1 x 1 ... 6 mm2 -- 1 x 1 ... 6 mm2 --
end sleeve
- For AWG cables 1 x 18 ... 10 -- 1 x 18 ... 10 --
• For load-side outgoing
feeder
- Solid 1 x 0.5 ... 2.5 mm2
- Finely stranded with end 1 x 0.5 ... 2.5 mm2
sleeve
- Finely stranded without 1 x 0.5 ... 2.5 mm2
end sleeve
- For AWG cables 1 x 20 ... 12
Type of electrical Spring-loaded terminals (push-in)
connection for auxiliary
and control circuits
Miscellaneous
Type of screwdriver tip Slotted
Size of screwdriver tip Standard screwdriver 0.6 mm x 3.5 mm
Load feeders and motor starters for use in the control cabinet
8
Control supply voltage at DC rated value V 20.4 ... 28.8
Miscellaneous
Type of screwdriver tip Slotted
Size of screwdriver tip Standard screwdriver 0.6 mm x 3.5 mm
Load feeders and motor starters for use in the control cabinet
3RK1308-0AB00-0CP0
Reversing starters
0.1 ... 0.4 4 3RK1308-0BA00-0CP0 1 1 unit 42D
0.3 ... 1 10 3RK1308-0BB00-0CP0 1 1 unit 42D
0.9 ... 3 30 3RK1308-0BC00-0CP0 1 1 unit 42D
2.8 ... 9 90 3RK1308-0BD00-0CP0 1 1 unit 42D
4 ... 12 100 3RK1308-0BE00-0CP0 1 1 unit 42D
3RK1308-0BB00-0CP0
Fail-safe direct-on-line starters
0.1 ... 0.4 4 3RK1308-0CA00-0CP0 1 1 unit 42D
8
3RK1308-0CE00-0CP0
Fail-safe reversing starters
0.1 ... 0.4 4 3RK1308-0DA00-0CP0 1 1 unit 42D
0.3 ... 1 10 3RK1308-0DB00-0CP0 1 1 unit 42D
0.9 ... 3 30 3RK1308-0DC00-0CP0 1 1 unit 42D
2.8 ... 9 90 3RK1308-0DD00-0CP0 1 1 unit 42D
4 ... 12 100 3RK1308-0DE00-0CP0 1 1 unit 42D
3RK1308-0DE00-0CP0
Load feeders and motor starters for use in the control cabinet
Product
Product version
version Operational Supply Push-in terminals PU PS* PG
voltage voltage (UNIT,
of AC of DC Article No. Price SET, M)
infeed infeed per PU
V V
BaseUnits1)
For motor starters
• With AC/DC infeed 500 24 3RK1908-0AP00-0AP0 1 1 unit 42D
• With DC infeed -- 24 3RK1908-0AP00-0BP0 1 1 unit 42D
• With AC infeed 500 -- 3RK1908-0AP00-0CP0 1 1 unit 42D
• Without infeed -- -- 3RK1908-0AP00-0DP0 1 1 unit 42D
For fail-safe motor starters
• With AC infeed, 500 -- 3RK1908-0AP00-0GP0 1 1 unit 42D
with F-DI infeed
3RK1908-0AP00-0AP0 • With AC infeed, 500 -- 3RK1908-0AP00-0HP0 1 1 unit 42D
with F-DI loop-through
• Without AC/DC infeed, -- -- 3RK1908-0AP00-0JP0 1 1 unit 42D
with F-DI loop-through
• Without AC/DC infeed, -- -- 3RK1908-0AP00-0KP0 1 1 unit 42D
with F-DI infeed
1)
The voltage is looped-through from BaseUnits with infeed to subsequent
BaseUnits without infeed.
Product
Product version
version Supply voltage Loop through Push-in terminals PU PS* PG
at DC rated the potential (UNIT,
value group from Article No. Price SET, M)
the left per PU
V
BaseUnits
For dummy modules
8
• Dark, looping through 24 Yes 6ES7193-6BP00-0BA0 1 1 unit 255
the potential group
• Light, opening a new 24 No 6ES7193-6BP00-0DA0 1 1 unit 255
potential group
6ES7193-6BP00-0BA0
3RK1908-1AA00-0BP0
Load feeders and motor starters for use in the control cabinet
6ES7133-6CV15-1AM0
BU cover 30 mm For protection of 3RK1908-1CA00-0BP0 1 1 unit 42D
empty slots, 30 mm
3RK1908-1CA00-0BP0
Covers For ET 200SP 3RK1908-1DA00-2BP0 1 1 unit 42D
Infeed bus
(1 bag containing
10 covers)
3RK1908-1DA00-2BP0
Additional mounting Mechanical, 3RK1908-1EA00-1BP0 1 1 unit 42D
8
3RW4928-8VB00
Motor suppression module
• Square 3RK1911-6EA00 1 1 unit 42D
3RK1911-6EA00
• Round 3RK1911-6EB00 1 1 unit 42D
3RK1911-6EB00
Starter kit Consists of 3RK1908-1SK00 1 1 unit 42D
3RK1308-0BC00-0CP0
reversing starter
(0.9 ... 3 A),
3RK1908-0AP00-0AP0
BaseUnit with 500 V and
24 V AC/DC infeed, and
EMC distance module
(consisting of
6ES7193-6BP00-0BA0
BaseUnit plus
6ES7133-6CV15-1AM0
BU cover 15 mm)
3RK1908-1SK00
Price groups
PG 241, 250, 368, 41J, 42C, 42D, 5K1,
5K2
9/2 Introduction
9
Software
9/34 Motor Starter ES
Accessories
9/35 For all M200D motor starters
9/40 For M200D motor starters for
AS-Interface
9/42 For M200D motor starters for PROFIBUS
9/43 For M200D motor starters for PROFINET
Siemens IC 10 · 2023
© Siemens 2023
Introduction
■ Overview
Flexible and cost-efficient distributed starter solutions Decision support for motor start – Starting and operating
three-phase asynchronous motors efficiently
Be it their high degree of protection, compact design or
integrated multifunctionality – our motor starters and soft starters
for use in the field are ideal for realizing distributed drive
solutions. The modular concepts, distributed power supply
and integrated safety technology of our portfolio for a high
degree of protection consistently supports current trends in
drive technology.
3RK1304 3RK1315
Type Page
ET 200pro motor starters
Motor starters in the SIMATIC ET 200pro I/O system up to 5.5 kW
Standard motor starters 3RK1304 9/8
High Feature motor starters 3RK1304 9/9
ET 200pro isolator modules • With switch disconnector function for safe disconnection 3RK1304 9/10
Safety modules PROFIsafe • F-Switch PROFIsafe 6ES7148 9/11
• 400 V disconnecting module 3RK1304 9/11
Accessories for ET 200pro motor starters • Incoming power supply, power loop-through connection on the field device, 3RK19 9/13
motor cable, power bus with power terminal connectors
ET 200pro – interface modules • For communication with PROFIBUS, PROFINET and IWLAN 6ES71 ST 70
ET 200pro – CPUs • Standard CPUs, fail-safe CPUs 6ES71 ST 70
ET 200pro – I/O modules • Digital/analog expansion modules, fail-safe expansion modules, 6ES71 ST 70
power modules, ET 200pro pneumatic interfaces
ET 200pro PS • Stabilized power supplies 6ES7148 ST 70
ET 200pro FC-2 frequency converters 6SL35 D 31.2
ET 200pro add-on products • Modules for EtherNet/IP ZNX:EIP ST 70
SIRIUS M200D motor starters
Distributed motor starters up to 5.5 kW
M200D AS-i Basic motor starters 3RK1315 9/25
M200D AS-i Standard motor starters 3RK1325 9/26
M200D communications modules for PROFIBUS 3RK1305 9/33
M200D communications modules for PROFINET 3RK1335 9/33
M200D motor starter modules 3RK1395 9/33
Accessories • Incoming power supply, motor cable, power bus with power terminal connectors 3RK1911 9/37
• Motor control with I/O communication 3RK1902 9/39
• Motor control with AS-i communication 3RK1902 9/40
• Motor control with PROFIBUS 3RK1902 9/42
• Motor control with PROFINET 3RK1902 9/43
■ Overview
ET 200pro motor starters in ET 200pro I/O system
More information
SIMATIC ET 200pro is the modular I/O system with high
degree of protection IP65/66/67 for local, cabinet-free use. Homepage, see www.siemens.com/sirius-motor-starter-et200pro
The ET 200pro motor starters with the high degree of protection Industry Mall, see www.siemens.com/product?ET200pro
IP65 are an integral part of ET 200pro. Decision support for motor start – Starting and operating three-phase
asynchronous motors efficiently, see www.siemens.com/motorstart-guide
Further components in the ET 200pro distributed I/O system:
• Interface modules, central processing units, I/O modules, ET 200pro PS,
see Catalog ST 70
• ET 200pro FC-2 frequency converters, see Catalog D 31.2
9
• Current asymmetry monitoring
• Stall protection The ET 200pro electromechanical starters are offered as direct-
on-line starters (DSe) and reversing starters (RSe) as Standard
• EMERGENCY START function on overload and High Feature versions. There are device versions with or
• Current value transmission by bus without control for externally supplied brakes with 400 V AC.
• Current limit monitoring Compared with the Standard motor starters, the High Feature,
• Full support of acyclic services mechanical motor starter also has:
• Direct-on-line or reversing starters • Four digital inputs
• Power bus connection can be plugged in using Han Q4/2 • Advanced parameterization options
plug-in connectors
The ET 200pro electronic starters are offered as direct-on-line
• Motor feeder with Han Q8/0 connector starters (sDSSte/sDSte) and reversing starters (sRSSte/sRSte)
• Conductor cross-sections up to 6 x 4 mm² in the High Feature version.
• 25 A per segment (power looped through using jumper plug) Compared with the High Feature mechanical motor starters,
• In the Standard and High Feature versions (with 4 DI on-board) the High Feature electronic motor starter also has:
• Electromechanical switching and electronic switching • Soft starting and smooth ramp-down function
• Electronic starter for direct activation or with integrated soft • Deactivated soft start function as an electronic starter for
starter function applications with a high switching frequency
• Supplied with 400 V AC brake contact as an option • Advanced parameterization options
• Temperature sensor can be connected
(Thermoclick or PTC type A)
• Provision of the motor current in PROFIenergy format to
higher-level systems, motor current shutdown in dead times
using PROFIenergy
positively felt particularly in manufacturing processes with high Voltage Ue Line system configurations
plant stoppage costs:
Three-phase Three-phase
• Configuration is made easier by the fine modular structure four-wire systems three-wire systems
with ET 200pro. When using the ET 200pro motor starters,
the parts list per load feeder is reduced to two main items:
the bus module and the motor starter. This makes the
ET 200pro ideal for modular machine concepts or solutions
IC01_00703
for conveyor systems and in machine-tool construction.
IC01_00709
• Expansions are easily possible through the subsequent
adding of modules. The innovative plug-in technology also
does away with the wiring needed up to now. Through the hot V V V
swapping function (disconnection and connection during 230 -- 230
operation) a motor starter can be replaced within seconds if
400 230/400 400
necessary, without having to shut down the ET 200pro station
and with it the process in the plant. The motor starters are 440 260/440 440
therefore recommendable in particular for applications with 500 -- 500
special demands on availability. Storage costs are also -- Not specified
optimized by the low level of variance (two units up to 5.5 kW).
• With four locally acting inputs available on the High Feature
motor starter it is possible to realize autonomous special
functions which work independently of the bus and the higher-
level control system, e.g. as a quick stop on gate valve
controls or limit position disconnectors. In parallel with this,
the states of these inputs are signaled to the control system.
Note:
The article number schemes show an overview of product
versions for better understanding of the logic behind the article
numbers.
For your orders, please use the article numbers quoted in the
selection and ordering data.
9
Local device interface ✓
Firmware update ✓ By specialists
Thermal motor model ✓
Parameterizable trip class -- CLASS 10 fixed ✓ CLASS 5, 10, 15, 20
Parameterizable response in case of overload of thermal -- ✓ 3 possible states
motor model
Advance warning limit for motor heating % -- ✓ Parameterizable 0 ... 95
Advance warning limit time-related trip reserve s -- ✓ Parameterizable 0 ... 500
Parameterizable recovery time min -- ✓ 1 ... 30
Parameterizable protection against voltage failure -- Permanently ✓
integrated
Reversing start function ✓ Order option
Parameterizable interlock time for reversing starters -- 150 ms fixed ✓ 0 ... 60 s
Integrated logbook functions ✓ 3 device logbooks
Integrated statistics data memory ✓
Parameterizable response in case of CPU/master stop ✓
PROFIenergy profile support
• Disconnection of the motor current during dead times ✓
• Measured motor current values ✓
Device indications
• Group fault SF LED (red)
• Switching state STATE LED (red, yellow, green)
• Device status DEVICE LED (red, yellow, green)
• Digital inputs -- IN 1 ... IN 4, LED
✓ Function available
-- Function not available
1)
DS .... Direct-on-line starters
RS .... Reversing starters
DSS .. Direct-on-line soft starters
RSS .. Reversing soft starters
e ....... Electronic motor protection
te ...... Full motor protection (thermal + electronic)
s ....... Electronic switching with semiconductor.
■ Benefits
ET 200pro motor starters provide the following advantages: • Extensive diagnostics and information for preventive
• High flexibility thanks to a modular and compact design maintenance
• Little variance among all motor starter versions (two units up • Parameterizable inputs for local control functions
to 5.5 kW) (High Feature)
• Extensive parameterization using STEP 7 HW Config • Cabinet-free design thanks to high degree of protection IP65
• Increase of plant availability through fast replacement of units
(easy mounting and plug-in technology)
■ Application
The SIMATIC ET 200pro motor starters are ideal for the use Use of ET 200pro motor starters in conjunction with
of several spatially concentrated distributed drive solutions in IE3 and IE4 motors
which several motors, or digital or analog sensors and actuators
are addressed from a distributed station. They are perfectly Note:
suited for protecting and switching any AC loads. For the use of ET 200pro motor starters in conjunction with highly
efficient IE3 and IE4 motors, please observe the information on
Application areas dimensioning and configuring, see Application Manual.
The SIMATIC ET 200pro motor starters are suitable for numerous For more information, see page 1/8.
sectors of industry, e.g. machinery and plant engineering or
conveying applications.
9
■ Technical specifications
More information
Equipment Manual, see Notes on security:
https://support.industry.siemens.com/cs/ww/en/view/22332388 System networking requires suitable protective measures (including
network segmentation for IT security) in order to ensure safe plant operation.
For more information on the subject of Industrial Security, see
www.siemens.com/industrialsecurity.
9
• DIN VDE 0106, Part 101 V Up to 400 Up to 480
• CSA and UL approval V Up to 600 Up to 480
Conductor cross-sections
• Incoming power supply mm2 Max. 6 x 4
Touch protection Finger-safe
Rated impulse withstand voltage Uimp kV 6
Rated insulation voltage Ui V 400
Rated operational current Ie for starters
• AC-1/2/3 at 40 °C
- At 400 V A 0.15 ... 2.0/1.5 ... 12.0 0.15 ... 2.0/1.5 ... 12.02)
- At 500 V A 0.15 ... 2.0/1.5 ... 9.0
• AC-4 at 40 °C
- At 400 V A 0.15 ... 2.0/1.5 ... 4.0
Rated short-circuit breaking capacity kA 100 at 400 V
Type of coordination according to IEC 60947-4-1 1
Power of three-phase motors at 400 V kW Max. 5.5 Max. 5.5/43)
Utilization categories AC-1, AC-3, AC-4 AC-53a4) (max. 9 A with
deactivated soft start
function up to CLASS 10)
Protective separation between main and auxiliary circuits V 400, according to EN 60947-1, Annex N
Endurance of contactor
• Mechanical Operating 30 million --
cycles
• Electrical Operating Up to 10 million; depending on the current loading --
cycles (see manual)
Permissible switching frequency Depending on the current loading, motor starting time, and relative ON period
(see manual)
Operating times for 0.85 ... 1.1 x Ue
• Closing delay ms 11 ... 50 --
• Opening delay ms 5 ... 45 --
1) 2)
DS .... Direct-on-line starters If the soft starter control function is deactivated, the permissible rated
RS .... Reversing starters operational current is reduced to 9 A up to CLASS 10.
DSS .. Direct-on-line soft starters 3) With parameterization as electronic starter max. 4 kW.
RSS .. Reversing soft starters 4)
8-hour operation.
e ....... Electronic motor protection
te ...... Full motor protection (thermal + electronic)
s ....... Electronic switching with semiconductor.
■ Overview
The functionality, device functions, and technical specifications
of the Standard motor starter are described in "ET 200pro motor
starters, General data" (see page 9/3 onwards).
✓ = Additional price
1)
Only functions when used together with the backplane bus module and the
wide module rack. The backplane bus module and the wide module rack
must be ordered separately (see "Accessories for ET 200pro motor
starters", page 9/17).
9
■ Overview
The functionality, device functions, and technical specifications The High Feature motor starter differs from the Standard
of the High Feature motor starter are described in motor starter in having more parameters and four integrated,
"ET 200pro motor starters, General data" (see page 9/3 onwards). freely-parameterizable digital inputs.
9
Rated operational current
sRSSte High Feature • 0.15 ... 2.0 A None
K
• 1.5 ... 12.0 A L ✓
✓ = Additional price
1)
Only functions when used together with the backplane bus module and the
wide module rack. The backplane bus module and the wide module rack
must be ordered separately (see "Accessories for ET 200pro motor
starters", page 9/17).
2)
The electronic motor starters can be used not only as electronic motor
starters with a high level of switching frequency but also as fully fledged
soft starters for soft starting and stopping. The changeover from motor
starter to soft starter takes place through reparameterization in HW Config.
Depending on the setting, this results in the following current ranges:
- Parameterization as electronic motor starter: 0.15 to 2 A and
1.5 to 9 A (4 kW)
- Parameterization as soft starter: 0.15 to 2 A and 1.5 to 12 A (5.5 kW).
■ Overview
The isolator module with integrated group fusing function The following properties apply to the isolator module:
(i.e. additional group short-circuit protection for all subsequently • Increase of plant availability through fast replacement of units
supplied motor starters) and switch disconnector function is (easy mounting and plug-in technology)
used for safe disconnection of the 400 V operational voltage
during repair work in the plant. • Cabinet-free design thanks to high degree of protection IP65
■ Technical specifications
Type Isolator modules Type Isolator modules
General data Degree of protection IP65
Mounting dimensions (W x H x D) Touch protection Finger-safe
• Direct-on-line starters and reversing mm 110 x 230 x 170 Pollution degree 3, IEC 60664 (IEC 61131)
starters
Rated impulse withstand voltage kV 6
Permissible ambient temperature Uimp
• During operation °C -25 ... +55
• During storage °C -40 ... +70 Rated insulation voltage Ui V 400
Permissible mounting position Any Rated operational current Ie
for starters
Vibration resistance according to g 2
IEC 60068, Part 2-6 • AC-1/2/3 at 40 °C
- At 400 V A 25
Shock resistance according to g/ms Half-sine 15/11 - At 500 V A 25
IEC 60068, Part 2-27
Rated short-circuit breaking kA 50 at 400 V
Power consumption capacity
• From auxiliary circuit L+/M (U1) mA Approx. 20
• From auxiliary circuit A1/A2 (U2) -- Type of coordination according to 2
IEC 60947-4-1
Rated operational current Ie for A 25
power bus Protective separation between V 400,
main and auxiliary circuits according to DIN VDE 0106,
Rated operational voltage Ue V 400 Part 101
Approvals according to Device functions
• DIN VDE 0106, Part 101 V Up to 500 • Group diagnostics Yes, parameterizable
• CSA and UL V Up to 600
Device indications
Conductor cross-sections • Group fault SF LED (red)
• Incoming power supply mm2 Max. 6 x 4
9
3RK1304-0HS00-6AA0
1)
Only functions when used together with the related 110 mm backplane bus
module and the wide module rack. The backplane bus module and the
wide module rack must be ordered separately (see page 9/17).
■ Overview
Safety Solution PROFIsafe Functionality
With the Safety modules PROFIsafe The F-Switch PROFIsafe is a fail-safe solid-state module for
• F-Switch and PROFIsafe safety applications. It has two fail-safe inputs and
• 400 V disconnecting module outputs for safe switching of the 24 V supply over backplane
with an appropriate connection, safety levels SIL 3 (according to busbars. In combination with the 400 V disconnecting module,
IEC 62061) or PL e (according to ISO 13849-1) can be reached. fail-safe disconnection of ET 200pro motor starters is possible in
PROFIsafe applications up to SIL 3/PL e.
F-Switch PROFIsafe
400 V disconnecting module
Fail-safe digital inputs/outputs in degrees of protection IP65 to
IP67 for near-machine, cabinet-free use. The 400 V disconnecting module enables the safe
disconnection of an operational voltage of 400 V up to
Fail-safe digital inputs SIL 3/PL e. For operation in a Safety PROFIsafe application
• For the fail-safe reading in of sensor information it functions only in combination with the F-Switch.
(1-/2-channel)
• Including integrated discrepancy evaluation Functionality
for 2v2 signals The 400 V disconnecting module can be used together with
• Internal sensor supplies (incl. testing) available the F-Switch for PROFIsafe safety applications. It contains two
Fail-safe digital outputs contactors connected in series for safety-related disconnection
of the main circuit. The auxiliary circuit supply of the device is
• Three fail-safe PP-switching outputs for safe switching of the provided via a safety power rail in the backplane bus module.
backplane busbars The 400 V disconnecting module can be used in conjunction
The F-Switch is certified up to SIL 3/PL e and has detailed with the
diagnostics. It supports PROFIsafe in PROFIBUS configurations F-Switch for safety applications up to SIL 3/PL e.
as well as in PROFINET configurations.
Note:
Safety characteristics, see page 16/9.
■ Technical specifications
Type 400 V disconnecting module
General data
Mounting dimensions (W x H x D)
• Direct-on-line starters and reversing starters mm 110 x 230 x 150
9
Permissible ambient temperature
• During operation °C -25 ... +55
• During storage °C -40 ... +70
Permissible mounting position Any
Vibration resistance according to IEC 60068, Part 2-6 2g
Shock resistance according to IEC 60068, Part 2-27 Half-sine 15 g/11 ms
Power consumption
• From auxiliary circuit L+/M (U1) mA Approx. 20
• From auxiliary circuit A1/A2 (U2) --
Rated operational current Ie for power bus A 25
Rated operational voltage Ue V 400 (50/60 Hz)
Approval DIN VDE 0106, Part 101 V Up to 500
CSA and UL approval V Up to 600
Conductor cross-sections
Incoming power supply mm2 Max. 6 x 4
Degree of protection IP65
Touch protection Finger-safe
Pollution degree 3, IEC 60664 (IEC 61131)
Rated impulse withstand voltage Uimp kV 6
Rated insulation voltage Ui V 400
Rated operational current Ie for starters
• AC-1/2/3 at 40 °C
- At 400 V A 25
- At 500 V A 25
Rated short-circuit breaking capacity kA 50 at 400 V
Type of coordination according to IEC 60947-4-1 2
Protective separation between main and auxiliary circuits V 400,
according to DIN VDE 0106, Part 101
Operating times for 0.85 ... 1.1 x Ue
• Closing delay ms 25 ... 100
• Opening delay ms 7 ... 10
Device functions
• Group diagnostics Yes, parameterizable
Device indications
• Group fault SF LED (red)
3RK1304-0HS00-8AA0
F-Switch PROFIsafe
24 V DC, including bus module 6ES7148-4FS00-0AB0 1 1 unit 241
Note:
Connection module must be ordered separately
6ES7148-1FS00-0AB0
Connection module for F-Switch
24 V DC 6ES7194-4DA00-0AA0 1 1 unit 241
1)
The 400 V disconnecting module functions only when used together with
the F-Switch PROFIsafe.
2)
The 400 V disconnecting module functions only when used together with
the backplane bus module and the wide module rack. The backplane bus
module and the wide module rack must be ordered separately (see
"Accessories for ET 200pro motor starters", page 9/17).
9
■ Overview
RSM RSM
MS MS MS MS
NSA0_00465a
NSA0_00467a
3 4 7
2 9
5 / 6
M M
Basic design of an ET 200pro version with (from the left) connection Infeed on the RSM isolator module
module for IM, interface module for communication (IM), RSM isolator
module, two ET 200pro motor starters (MS), and connections for energy
Legend:
Infeed on the ET 200pro motor starter $ Power feeder plug (see page 9/15)
% Power connection plug (see page 9/15)
& Power jumper plug (see page 9/15)
9
( Motor connection plug (see page 9/15)
) Motor plug (see page 9/15)
MS MS * Motor plug with EMC suppressor circuit (see page 9/15)
+ Power loop-through plug (see page 9/15)
, Power connecting cable (see page 9/15)
- Power connecting cable for isolator module (see page 9/15)
. Motor cable (see page 9/16)
NSA0_00466a
10
8
11
12 13 13
ET 200pro
M200D M200D
IC01_00230a
9
Motors
Power supply to the motors via the power bus with power T and double-T terminal connectors linked by power bus cables, spur lines to the field devices
(motor starters), and power loop-through connections to the motors via motor connecting cables
Motor control via PROFIBUS Motor control via PROFINET
The interface modules (IM) for PROFIBUS can be combined For connection modules with the relevant accessories, see
with two different connection modules for connecting "Accessories for ET 200pro interface modules" in Catalog ST 70
PROFIBUS DP and the power supply: or the Industry Mall.
• Direct connection with cable gland
• M12, 7/8" connection
- with M12 connecting cable and M12 plugs for data
transmission with PROFIBUS DP
- with 7/8" connecting cable and 7/8" plugs for the power
supply
For connection modules with the relevant accessories, see
"Accessories for ET 200pro interface modules" in Catalog ST 70
or the Industry Mall.
9
comprising a cable-end connector hood, angled
outgoing feeder, pin insert for HAN Q4/2, incl. gland
• 4 male contacts, 2.5 mm2 3RK1911-2BF50 1 1 unit 42D
• 4 male contacts, 4 mm2 3RK1911-2BF10 1 1 unit 42D
Motor cables
( Motor connection plugs
Connector set for motor cable for connection to
ET 200pro motor starters, comprising a cable-end
connector hood, angled outgoing feeder, pin insert
for HAN Q8/0, incl. gland
• 8 male contacts, 1.5 mm2 3RK1902-0CE00 1 1 unit 42D
• 6 male contacts, 2.5 mm2 3RK1902-0CC00 1 1 unit 42D
) Motor plugs
Connector set for motor cable for connection to motors,
comprising a cable-end connector hood, straight
outgoing feeder, female insert for HAN 10e, incl. star
jumper, incl. gland
• 7 female contacts, 1.5 mm2 3RK1911-2BM21 1 1 set 42D
• 7 female contacts, 2.5 mm2 3RK1911-2BM22 1 1 set 42D
* Motor plugs with EMC suppressor circuit
Connector set for motor cable for connection to motors,
comprising a cable-end connector hood, straight
outgoing feeder, female insert for HAN 10e with
EMC suppressor circuit, incl. star jumper, incl. gland
• 7 female contacts, 1.5 mm2 3RK1911-2BL21 1 1 set 42D
• 7 female contacts, 2.5 mm2 3RK1911-2BL22 1 1 set 42D
3RK1902-0CW00
Dismantling tools
• For male and female contacts for 9-pole HAN Q4/2 inserts 3RK1902-0AB00 1 1 unit 42D
• For male and female contacts for 9-pole HAN Q8 inserts 3RK1902-0AJ00 1 1 unit 42D
Sealing caps
For 9-pole power sockets
• 1 unit per pack 3RK1902-0CK00 1 1 unit 42D
• 10 units per pack 3RK1902-0CJ00 1 10 units 42D
3RK1902-0CK00
Further accessories
Module racks, wide1)
• Length 500 mm 6ES7194-4GB00-0AA0 1 1 unit 250
• Length 1 000 mm 6ES7194-4GB60-0AA0 1 1 unit 250
• Length 2 000 mm 6ES7194-4GB20-0AA0 1 1 unit 250
Module racks, wide, compact1)
• Length 500 mm 6ES7194-4GD00-0AA0 1 1 unit 250
• Length 1 000 mm 6ES7194-4GD10-0AA0 1 1 unit 250
• Length 2 000 mm 6ES7194-4GD20-0AA0 1 1 unit 250
Backplane bus modules 110 mm2) 3RK1922-2BA00 1 1 unit 42D
Handheld devices 3RK1922-3BA00 1 1 unit 42D
For ET 200pro motor starters (or for
ET 200S High Feature and M200D motor starters)
for local operation.
Notes:
• The motor-starter-specific serial interface cables must
be ordered separately.
• The RS 232 interface cable 3RK1922-2BP00 is used for
the MS ET 200pro.
RS 232 interface cable 3RK1922-2BP00 1 1 unit 42D
3RK1922-3BA00
Serial data connection between ET 200pro (or M200D)
motor starters and the RS 232 interface of a PC/PG/laptop
(with the Motor Starter ES software) or the handheld device
3RK1922-3BA00.
USB interface cable, 2.5 m 6SL3555-0PA00-2AA0 1 1 unit 368
Serial data connection between ET 200pro (or M200D)
motor starters and the USB interface of a PC/PG/laptop
(with the Motor Starter ES software).
M12 sealing caps 3RK1901-1KA00 100 10 units 42C
For sealing unused M12 input or output sockets
(one set contains ten sealing caps)
3RK1901-1KA00
Motor suppression module
RC element for installation in motor terminal box
9
• Angled design 3RK1911-6EA00 1 1 unit 42D
3RK1911-6EA00
• Round design 3RK1911-6EB00 1 1 unit 42D
3RK1911-6EB00
1)
The wide module rack can accommodate all ET 200pro motor starters and
any optional modules (isolator module, 400 V disconnecting module).
2)
The backplane bus module is a prerequisite for operation of the
ET 200pro motor starter and the optional module.
For more connection technology products, see
https://support.industry.siemens.com/cs/ww/en/view/65355810.
■ Overview
More information
Industry Mall, see www.siemens.com/product?3ZS1
Technical specifications and system requirements, see
https://support.industry.siemens.com/cs/ww/en/ps/16713/td
■ Overview
More information
Homepage, see www.siemens.com/sirius-motor-starter-m200d
Industry Mall, see www.siemens.com/product?M200D
Decision support for motor start – Starting and operating three-phase
asynchronous motors efficiently, see www.siemens.com/motorstart-guide
TIA Selection Tool Cloud (TST Cloud), see
www.siemens.com/tstcloud/?node=MS_M200D
Basic functionality
The versions of the M200D motor starter are equipped with the
following properties and functions:
• Available as direct-on-line and reversing starters in a rugged
design
• Electromechanical or electronic switching version
• Low variance – only two device versions up to 5.5kW thanks
to wide range setting
• All versions have the same enclosure size.
SIRIUS M200D AS-i Basic motor starter with manual local operation
• Degree of protection IP65
The intelligent and highly flexible SIRIUS M200D motor starters
for distributed installation start, monitor and protect motors and • Quick and fail-safe wiring of system and motor cables using
loads up to 5.5 kW. ISO 23570 plug-in connector technology (Q4/2 and Q8/0)
• Robust and widely used M12 connection method for digital
The M200D motor starters are available in four versions: inputs and outputs
M200D M200D M200D M200D • Integrated feeder connector monitoring
AS-i Basic AS-i Standard PROFIBUS PROFINET • Full motor protection through overload protection and
Motor control with a temperature sensor (PTC, TC)
AS-i communication PROFIBUS PROFINET • Short-circuit and overload protection integrated
Mechanical or electronic switching • Integrated repair switch lockable with three locks
✓ ✓ ✓ ✓ (multi-level service)
Electronic switching with soft starter functionality • Uniform wiring to the SINAMICS G115D and
-- ✓ ✓ ✓ SINAMICS G120D frequency converters and to the
ET 200pro distributed I/O system
9
✓ Function available • Extensive diagnostics concept using LEDs
-- Function not available
• Optionally available integrated manual local control with key-
Voltage data operated switch (ordering option)
The specifications for 3-phase systems according to • Optionally available brake actuation with voltages from
IEC 60947-4-1 apply for the following line system configurations: 180 V DC (no rectifier needed in motor) or 230/400 V AC
.
(order versions)
Voltage Ue Line system configurations
Three-phase Three-phase
four-wire systems three-wire systems
IC01_00703
IC01_00709
V V V
230 -- 230
400 230/400 400
440 260/440 440
500 -- 500
-- Not specified
Note:
The article number scheme shows an overview of product For your orders, please use the article numbers quoted in the
versions for better understanding of the logic behind the article selection and ordering data.
numbers.
■ Benefits
M200D motor starters provide the following advantages for • Comprehensive offering of accessories, including
customers: ready-assembled cables
• High plant availability through plug-in capability of the main • The M200D motor starters can be installed with a few manual
circuit, communication and I/Os – relevant for installing and steps. The integrated plug-in technology enables far lower
replacing devices wiring outlay:
• Cabinet-free construction and near-motor installation thanks Preassembled cables can be plugged directly onto the motor
9
■ Application
The high degree of protection IP65 makes the M200D motor Use of SIRIUS M200D motor starters in conjunction with
starters suitable in particular for use on extensive conveying IE3 and IE4 motors
systems such as are found in mail sorting centers, airports,
automotive factories and the packing industry. Note:
For simple drive tasks, particularly in conveyor applications, For the use of SIRIUS M200D motor starters in conjunction
the new SINAMICS G115D frequency converter series with with highly efficient IE3 and IE4 motors, please observe the
a performance range from 0.37 kW to 7.5 kW and degree of information on dimensioning and configuring, see Application
protection IP65 is the ideal partner for the M200D motor starters. Manual.
SINAMICS G115D converters allow for continuous speed control For more information, see page 1/8.
of three-phase asynchronous motors and comply with the
requirements of conveyor technology applications with
frequency control (for more information, see Catalog D 31.2).
■ Overview
For motor control using AS-Interface there are the following Mounting and installation
M200D motor starter versions: SIRIUS M200D AS-i Basic and
SIRIUS M200D AS-i Standard (basic functionality, see page 9/19 The M200D motor starters can be installed with a few manual
"SIRIUS M200D motor starters" ➞ "General data" ➞ "Overview"). steps. The integrated plug-in technology enables far lower
wiring outlay. Connecting cables can be plugged directly onto
SIRIUS M200D AS-i Basic the motor starter module. Swapping of the connecting wires and
malfunctions within the plant are prevented by preassembled
Functionality cables. The AS-i bus is connected cost-effectively using an
• Easy and fast on-site startup through parameterization of local M12 connection on the device. All versions have identical
setting knobs (DIP switches) and rotary coding switches for enclosure dimensions for easier system design and conversion.
adjusting the rated operational current. The rotary coding
switch has an OFF position for deactivating the overload Parameterization and configuration
protection with the help of the thermal motor model when The particularly robust M200D AS-i Standard motor starter is
using a temperature sensor. characterized by numerous functions which can be flexibly
Communications parameterized. It enables highly flexible parameterization
through the AS-i bus using data records from the user program
• AS-i communication with A/B addressing according to as well as user-friendly local parameterization using the
Spec V2.1 Motor Starter ES startup software through the local point-to-point
• The AS-i bus is connected cost-effectively using an interface.
M12 connection on the device. Of the four digital inputs, Functions can be flexibly assigned to the digital inputs and
two are contained in the process image and can therefore outputs, adapting them to all possible conveyor applications.
be used in the PLC program. The other two inputs are locally All motor protection functions, limit values and reactions can be
effective and permanently assigned with functions. defined by parameterization. The AS-i Standard is unique. In its
• The LEDs can provide comprehensive diagnostics of the 6E/4A process image the motor starter sends all four digital
device on the spot. In addition to diagnostics using the inputs and the digital output via the process image to the PLC in
PAE process image, the device can create up to 15 different cyclic mode. System configuration and system documentation
diagnostic messages per slave. The message with the highest are facilitated not least by a number of CAX data.
priority can be read out through the AS-i communication.
This is yet another new development which distinguishes Operation
the M200D AS-i Basic motor starter from the rest of the market The new generation of motor starters is characterized by its
and adds innovative technology, maximum availability and advanced functionality, maximum flexibility and extremely high
transparency to the system. degree of automation.
SIRIUS M200D AS-i Standard All digital inputs and outputs exist in the cyclic process image.
The intelligent and highly flexible M200D AS-i Standard motor All limit values for monitoring functions and their reactions are
starter in A/B technology starts and protects motors and loads parameterizable and therefore adaptable to the application.
The motor starters record the actual current flow. Evaluating the
9
up to 5.5 kW. It is available in direct-on-line or reversing starter
versions, in a mechanical version and also a solid-state version current of the parameterizable electronic overload protection
(the latter with soft start function). increases the availability of the drives, as do reliable messages
concerning the overshooting or undershooting of setpoint values.
The M200D AS-i Standard motor starter is the most functional
member of the SIRIUS motor starter family in the high degree of Diagnostics and preventive maintenance
protection IP65 for AS-i communication. Consistency with other The M200D sets new standards for diagnostics. In addition to
products of the SIRIUS M200D motor starter range and with the diagnostics using the PAE process image and diagnostics by
frequency converter and ET 200pro I/O system is assured. "parameter echo" (up to 15 different diagnostic messages per
Functionality slave can be read out via AS-i communication), the possibility of
reading out diagnostic data records is unique on the market.
• AS-i communication with A/B addressing according
to Spec 3.0 The AS-i Standard is recommended in particular for expansive
and highly automated system components because the
• Solid-state version also with soft start function possibility of monitoring devices and systems with data records
• AS-i slave profile 7AE/7A5 with process image 6E/4A (statistical data, measured values and device diagnostics)
• Full TIA integration: All digital inputs and outputs exist in the provides an in-depth view of the plant from the control room,
cyclic process image and are visible through AS-i, providing guaranteeing the monitoring process and increasing plant
maximum flexibility and best adaptability to the application. availability.
• Additionally expanded diagnostics using data record through Preventive maintenance can be carried out with the integrated
AS-i bus maintenance timer and plant downtimes prevented as a result in
• Complete plant monitoring using statistics data record and advance.
current value monitoring by means of data records Local control of a drive is possible using the ordering option
• Parameterization through AS-i bus with the help of data with integrated manual local operation. This is yet another new
records or an expanded process image from the user program development which distinguishes the M200D AS-i Standard
• Control of the motor starter using a command data record from motor starter from the rest of the market and adds innovative
the user program technology, maximum availability and transparency to the plant.
• Flexible assignment of the digital inputs and outputs with all
available assignable input actions
• Parameterization using Motor Starter ES at the local interface
(ordering option for startup software)
• Diagnostics with the help of Motor Starter ES (ordering option
for startup software)
✓ Function available
-- Function not available
1) The data records are a reduced selection compared with
PROFIBUS/PROFINET.
✓ Function available
9
-- Function not available
■ Application
The M200D AS-i Standard is particularly suitable for highly Use of M200D motor starters in conjunction with
automated applications in conveyor systems requiring devices IE3 and IE4 motors
and systems to be monitored to prevent or limit plant downtime.
The option of parameterizing the functions of the motor starter or Note:
its interfaces also creates the prerequisite for fine-adjustment to For the use of SIRIUS M200D motor starters in conjunction
the function of the motor starter in the application and hence with highly efficient IE3 and IE4 motors, please observe the
provides for extreme flexibility. information on dimensioning and configuring, see Application
Manual.
For more information, see page 1/8.
■ Technical specifications
More information
Manuals for SIRIUS M200D: Notes on security:
• AS-i Basic, see In order to protect plants, systems, machines and networks against cyber
https://support.industry.siemens.com/cs/ww/en/view/35016496 threats, it is necessary to implement – and continuously maintain – a holistic,
• AS-i Standard, see state-of-the-art industrial security concept. Siemens products and solutions
https://support.industry.siemens.com/cs/ww/en/view/38722160 represent only one component of such a concept.
FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/16324/faq For more information on the subject of Industrial Security, see
www.siemens.com/industrialsecurity.
M200D AS-i Basic without manual local operation M200D AS-i Basic with manual local operation
9
• 0.15 ... 2 K None
• 1.5 ... 9 N ✓
Direct-on-line starters/reversing starters
• Direct-on-line starters 0 None
• Reversing starters 1 ✓
• Direct-on-line starters with manual local operation 2 ✓
• Reversing starters with manual local operation 3 ✓
Brake actuation
• Without brake actuation 0 None
• Brake actuation (230/400 V AC) 3 ✓
• Brake actuation (180 V DC) 5 ✓
✓ = Additional price
M200D AS-i Standard without manual local operation M200D AS-i Standard with manual local operation
■ Overview
The intelligent, highly flexible M200D PROFIBUS/PROFINET
motor starters are the most functional motor starters of the
SIRIUS motor starter family in the high degree of protection IP65
for PROFIBUS/PROFINET communication.
They start and protect motors and loads up to 5.5 kW.
Direct-on-line and reversing starter versions are available
in a mechanical version and also a solid-state version
(the latter with soft start function).
The particularly robust M200D PROFIBUS/PROFINET motor
starters are characterized by numerous functions which can be
flexibly parameterized. Their modular design comprises a motor
starter module and a communications module.
The M200D PROFINET motor starters enable TIA-integrated
parameterization through PROFINET from STEP 7 – in familiar,
user-friendly manner with the look and feel of PROFIBUS.
Functionality
• For basic functionality, see page 9/19 "SIRIUS M200D motor
starters" ➞ "General data" ➞ "Overview" M200D motor starter module for PROFIBUS/PROFINET
• Solid-state version also with soft start function (without communications module)
9
the bus with the TIA-compatible mechanisms
• Expanded diagnostics using data records
• Complete plant monitoring using statistics data record and
current value monitoring by means of data records
• Parameterization through PROFIBUS/PROFINET bus with M200D communications module for PROFIBUS
the help of data records from the user program
• Control of the motor starter using a command data record from
the user program
• Removable modular control unit – quicker device replacement
and therefore lower costs when device outages occur – since
existing wiring is on the control unit and only one device needs
to be replaced
• Parameterization in STEP 7 HW Config via Motor Starter ES
(ordering option for startup software)
• Startup and diagnostics with the help of Motor Starter ES
(ordering option for startup software)
• Trace function through Motor Starter ES for optimized startup
and tracking of process and device values
Only with PROFINET:
• Just one bus system from the MES level to the devices –
no routers
• More stations on the bus and possible configuration of flexible M200D communications module for PROFINET
bus structures
• Automatic re-parameterization in case of device replacement
thanks to proximity detection
• Wireless integration of plant segments in difficult environ-
ments using WLAN
• Easier expansion of the system thanks to a higher number of
stations on the bus and elimination of terminating resistors
9
Motor Starter ES ✓ Through bus, optical interface
PROFIBUS/PROFINET data records ✓
From STEP 7/HW Config ✓
Diagnostics
Acyclic through data records ✓
Diagnostics alarm ✓
Process image
Process image ✓ 2 bytes PAE/2 bytes PAA
Data channels
Local optical interface (manual local) ✓
Using Motor Starter ES through local interface ✓
Using Motor Starter ES through bus ✓
Data records (acyclic)
Parameter assignment ✓ Using DS 131 (DS = data record)
Diagnostics ✓ Device-specific DS 92
Measured values ✓ Measured values DS 94
Statistics ✓ Statistical data DS 95
Commands ✓ Using DS 93
Slave pointer ✓ Slave pointer DS 96
Logbook ✓ Using Motor Starter ES and data records: device faults DS 72, tripping operation DS 73, events DS 75
Device identification ✓ Using DS 100
I&M data ✓ Using DS 231 ... 234 ✓ Using data records 0xAFF0 ... 0xAFF3
Inputs
Number ✓ 4
• Of these in the process image ✓ 4
Input action ✓ Parameterizable: For flexibly assignable action, see manual
Quick stop ✓ Parameterizable: latching, non-latching
✓ Function available
-- Function not available
Brake output
180 V DC/230/400 V AC/without ✓
Motor protection
Overload protection ✓ Electronic, wide range 1:10
Short-circuit protection ✓
Full motor protection ✓
Temperature sensor ✓ Parameterizable via Motor Starter ES, data record: PTC or Thermoclick or deactivated
Device function
Repair switch ✓
Current limit monitoring bottom ✓ Parameterizable
Current limit monitoring top ✓ Parameterizable
Residual current detection ✓ Parameterizable: tripping, warning
Blocking current ✓ Parameterizable
Asymmetry ✓ Parameterizable
Load type ✓ Parameterizable: 1-phase and 3-phase
Shutdown class ✓ Parameterizable via Motor Starter ES, data record: CLASS 5, 10, 15, 20
9
✓ Function available
-- Function not available
■ Benefits
M200D PROFINET motor starters with PROFIenergy
Both standards and laws are making environmental protection It is thus an objective within the industry to save energy and
and energy management increasingly important, as is the desire actively reduce CO2 emissions. By the careful use of valuable
to cut energy costs in production facilities and thus ensure resources, the manufacturer-independent PROFIenergy profile
a sustainable competitive advantage. on PROFINET can make an active contribution to environmental
protection.
■ Application
M200D PROFIBUS/PROFINET motor starters are particularly Adaptability of the motor starter functions and maximum
suitable for fully TIA-integrated, highly automated conveyor flexibility of the device enable a broad range of application
applications that meet all needs with regard to the monitoring without any limits. The PROFINET-specific expansions are
of devices and systems and preventive maintenance. the best assurance of a future-proof investment.
■ Technical specifications
More information
Equipment Manual for M200D PROFIBUS/PROFINET, see Notes on security:
https://support.industry.siemens.com/cs/ww/en/view/38823402 In order to protect plants, systems, machines and networks against cyber
FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/16325/faq threats, it is necessary to implement – and continuously maintain – a holistic,
state-of-the-art industrial security concept. Siemens products and solutions
represent only one component of such a concept.
For more information on the subject of Industrial Security, see
www.siemens.com/industrialsecurity.
9
Rated operational voltage Ue
• Approval according to EN 60947-1 V AC 400 (50/60 Hz)
• Approval according to UL and CSA V AC 600 (50/60 Hz) 480 (50/60 Hz)
• Rated operational current range A 0.15 ... 2/1.5 ... 12 --
• Rated operational current range for soft starting A -- 0.15 ... 2/1.5 ... 12
• Rated operational current range for direct-on-line starting A -- 0.15 ... 2/1.5 ... 9
Rated operational current Ie for starters at 400 V AC
• 400 V at AC-1, AC-3 and AC-3e A 12 --
• 500 V at AC-1, AC-3 and AC-3e A 9 --
• 400 V at AC-4 A 4 --
• 400 V at AC-53a A -- 12 for soft starting, 9 for direct-on-line starting
Mechanical endurance of contactor Oper- 30 million --
ating
cycles
Trip class CLASS 5, 10, 15, 20
Permissible switching frequency see manual
Rated ultimate short-circuit breaking capacity Iq
• At 400 V AC kA 50
• At 500 V AC kA 50 202)
Short-circuit protection
• At Iemax = 2 A Integrated, 2 x 13 Ie = 26 A
• At Iemax = 9/12 A Integrated, 2 x 13 Ie = 208 A
1)
DS .... Direct-on-line starters
RS .... Reversing starters
DSS .. Direct-on-line soft starters
RSS .. Reversing soft starters
te ...... Full motor protection (thermal + electronic)
s ....... Electronic switching with semiconductor.
2) Only systems with grounded neutral point permitted.
Line voltage
380 V AC 400 V AC 440 V AC 480 V AC 500 V AC
Brake voltage with brake actuation 180 V DC1)
Operational voltage V 230/400 AC or 180 DC
Uninterrupted current A < 0.5 at 230/400 V AC, < 0.8 at 180 V DC
Short-circuit protection Yes, 1 A melting fuse
Rectified brake voltage V DC 171 180 198 216 225
Recommended brake coil voltage for Siemens motors V DC 170 ... 200 170 ... 200 184 ... 218 184 ... 218 --
1)
Integrated brake actuation supplies DC power supply for the brake.
M200D motor starter module M200D motor starter M200D motor starter
PROFIBUS/PROFINET PROFIBUS PROFINET
(without communications module)
9
• Direct-on-line starters with manual local operation 2 ✓
• Reversing starters with manual local operation 3 ✓
Brake actuation
• Without brake actuation 0 None
• Brake actuation (230/400 V AC) 3 ✓
• Brake actuation (180 V DC) 5 ✓
Electronic starters (with thyristors)
3RK1395-6@S71-@AD@ 1 1 unit 42D
Rated operational current setting range/A Add. price
• 0.15 ... 2 K None
• 1.5 ... 12 L ✓
Direct-on-line starters/reversing starters
• Direct-on-line starters 0 None
• Reversing starters 1 ✓
• Direct-on-line starters with manual local operation 2 ✓
• Reversing starters with manual local operation 3 ✓
Brake actuation
• Without brake actuation 0 None
• Brake actuation (230/400 V AC) 3 ✓
• Brake actuation (180 V DC) 5 ✓
✓ = Additional price
■ Overview
More information
Industry Mall, see www.siemens.com/product?3ZS1
Technical specifications and system requirements, see
https://support.industry.siemens.com/cs/ww/en/ps/16713/td
■ Overview
7
1
NSA0_00485a
NSA0_00484
2 4 9 10
5
M 8
3 6
1 Power feeder plug 7 Connection for motor control with AS-i communication
2 Power connection plug 8 AS-Interface M12 feeder
3 Power connecting cable 9 Connection for digital input
(IO communication, 5-pole)
4 Motor connection plug
10 Connection for digital output
5 Motor plug (IO communication, 4- or 5-pole)
6 Motor cable
Power and motor connection on the M200D motor starter Communication link using AS-Interface and digital inputs and outputs
(in this example: M200D for AS-i)
9
13 14 13 14
11 12 15 15
NSA0_00488a
NSA0_00487a
9 10 9 10
Communication link using PROFIBUS and digital inputs and outputs Communication link using PROFINET and digital inputs and outputs
16
17 18 18
ET 200pro
M200D M200D
IC01_00231a
Motors
Power supply to the motors via the power bus with power T and double-T terminal connectors linked by power bus cables, spur lines to the field devices
(motor starters), and power loop-through connections to the motors via motor connecting cables
Power bus Interruption-free thanks to power terminal connectors
The power supply to the field devices (ET 200pro motor starters, In finger-safe connection technology the power T terminal
9
M200D motor starters) is provided via the power bus, in which connectors and power double-T terminal connectors connect
the power T terminal connectors or power double-T terminal the components of a feeder to the power bus. They ensure
connectors are connected by power bus cables. interruption-free operation, i.e. when the components are
plugged in, the power bus is not interrupted.
Feeders
From the terminal connectors, spur lines with Han Q4/2 plugs
lead to the field devices, from which the motors are supplied with
power via motor connecting cables.
Mountable accessories
M200D protective brackets 3RK1911-3BA00 1 1 unit 42D
Incoming power supply
$ Power feeder plugs
Connector set for power supply, e.g. for connecting to
T terminal connectors, comprising a coupling enclosure,
straight outgoing feeder (with bracket), pin insert for
HAN Q4/2, incl. gland
• 5 male contacts, 2.5 mm2 3RK1911-2BS60 1 1 unit 42D
• 5 male contacts, 4 mm2 3RK1911-2BS20 1 1 unit 42D
• 5 male contacts, 6 mm2 3RK1911-2BS40 1 1 unit 42D
% Power connection plugs
Connector set for energy supply for connection to
M200D motor starters, comprising a cable-end
connector hood, angled outgoing feeder, female insert
for HAN Q4/2, incl. gland
• 5 female contacts, 2.5 mm2, 3RK1911-2BE50 1 1 unit 42D
2 female contacts, 0.5 mm2
• 5 female contacts, 4 mm2, 3RK1911-2BE10 1 1 unit 42D
2 female contacts, 0.5 mm2
• 5 female contacts, 6 mm2, 3RK1911-2BE30 1 1 unit 42D
2 female contacts, 0.5 mm2
% + & Power connecting cables
Assembled at one end with "N" and jumper pin 11 and 12
for plug monitoring, with HAN Q4/2, angled;
open at one end; 5 x 4 mm2
9
• Length 1.5 m 3RK1911-0DC13 1 1 unit 42D
• Length 5.0 m 3RK1911-0DC33 1 1 unit 42D
Motor cables
( Motor connection plugs
Connector set for motor cable for connection to
M200D motor starters, comprising a cable-end connector
hood, angled outgoing feeder, pin insert for HAN Q8/0,
incl. gland
• 8 male contacts, 1.5 mm2 3RK1902-0CE00 1 1 unit 42D
• 6 male contacts, 2.5 mm2 3RK1902-0CC00 1 1 unit 42D
) Motor plugs
Connector set for motor cable for connection to motors,
comprising a cable-end connector hood, straight
outgoing feeder, female insert for HAN 10e,
incl. star jumper, incl. gland
• 7 female contacts, 1.5 mm2 3RK1911-2BM21 1 1 set 42D
• 7 female contacts, 2.5 mm2 3RK1911-2BM22 1 1 set 42D
( + * Motor cables, assembled at one end
For connection to M200D motor starter, HAN Q8/0,
angled, length 5 m
• Motor cables for motor without brake, 4 x 1.5 mm2 3RK1911-0EB31 1 1 unit 42D
• Motor cables for motor without brake with thermistor, 3RK1911-0EF31 1 1 unit 42D
6 x 1.5 mm2
• Motor cables for motor with brake actuation, 3RK1911-0ED31 1 1 unit 42D
brake voltage 400 V AC or 180 V DC, 6 x 1.5 mm2
• Motor cables for motor with brake actuation, 3RK1911-0EG31 1 1 unit 42D
brake voltage 400 V AC or 180 V DC
and thermistor, 8 x 1.5 mm2
• Motor cables for motor with brake actuation, 3RK1911-0EH31 1 1 unit 42D
brake voltage 230 V AC, 6 x 1.5 mm2
• Motor cables for motor with brake actuation, brake 3RK1911-0EE31 1 1 unit 42D
voltage 230 V AC and thermistor, 8 x 1.5 mm2
Power bus
5 Power T terminal connectors
For 400 V AC, for connection of feeders (e.g. motor
starters) by means of standard round cable at any point
of the power bus, by insulation displacement connection,
used with preassembled bus segments
• 2.5 mm²/4 mm² 3RK1911-2BF01 1 1 unit 42D
• 4 mm²/6 mm² 3RK1911-2BF02 1 1 unit 42D
6 Power double-T terminal connectors
For 400 V AC, for connection of feeders (e.g. motor
starters) by means of standard round cable at any point
of the power bus, by insulation displacement connection,
used with preassembled bus segments, connection of
two motor starters possible
• 4 mm²/6 mm² 3RK1911-2BG02 1 1 unit 42D
Sealing set (comprising 2 seals)
For power T/power double-T terminal connectors
• For power cables with
- Ø 10 ... 13 mm 3RK1911-5BA00 1 1 unit 42D
- Ø 13 ... 16 mm 3RK1911-5BA10 1 1 unit 42D
- Ø 16 ... 19 mm 3RK1911-5BA20 1 1 unit 42D
- Ø 19 ... 22 mm 3RK1911-5BA30 1 1 unit 42D
• Blanking plugs 3RK1911-5BA50 1 1 unit 42D
Further accessories for power connections
Crimping tools for pins/sockets 4 mm2 and 6 mm2 3RK1902-0CW00 1 1 unit 42D
3RK1902-0CW00
Dismantling tools
• For male and female contacts for 9-pole HAN Q4/2 inserts 3RK1902-0AB00 1 1 unit 42D
• For male and female contacts for 9-pole HAN Q8 inserts 3RK1902-0AJ00 1 1 unit 42D
Sealing caps
9
3RK1902-0CK00
3RK1902-4BA00-5AA0
. M12 plugs, angled 3RK1902-4DA00-5AA0 1 1 unit 42D
Screw fixing, 5-pole screw terminals,
max. 0.75 mm2,
A-coded, max. 4 A
3RK1902-4DA00-5AA0
-, . Control cables, assembled at one end
M12 plug, angled, screw fixing, 5-pole, 5 x 0.34 mm2,
A-coded, black PUR sheath, max. 4 A
• Cable length 1.5 m 3RK1902-4HB15-5AA0 1 1 unit 42D
3RK1902-4H...-5AA0 • Cable length 5 m 3RK1902-4HB50-5AA0 1 1 unit 42D
• Cable length 10 m 3RK1902-4HC01-5AA0 1 1 unit 42D
Control cables, assembled at both ends
Straight M12 plug, straight M12 socket, screw fixing,
3RK1902-4PB15-3AA0 3-pole, 3 x 0.34 mm2,
A-coded, black PUR sheath, max. 4 A
• Cable length 1.5 m 3RK1902-4PB15-3AA0 1 1 unit 42D
Further accessories
Handheld devices 3RK1922-3BA00 1 1 unit 42D
For M200D motor starters (or for ET 200pro and ET 200S
High Feature motor starters) for local operation.
The motor starter-specific serial interface cables must be
ordered separately.
The RS 232 interface cable 3RK1922-2BP00 is used for
the MS M200D.
RS 232 interface cable 3RK1922-2BP00 1 1 unit 42D
Serial data connection between M200D (or ET 200pro)
motor starters and the RS 232 interface of a PC/PG/laptop
9
(with the Motor Starter ES software) or the handheld device
3RK1922-3BA00 3RK1922-3BA00
USB interface cable, 2.5 m 6SL3555-0PA00-2AA0 1 1 unit 368
Serial data connection between M200D (or ET 200pro)
motor starters and the USB interface of a PC/PG/laptop
(with the Motor Starter ES software).
M12 sealing caps 3RK1901-1KA00 100 10 units 42C
For sealing unused M12 input or output sockets
and M12 sockets for PROFIBUS and
PROFINET communications modules
3RK1901-1KA00 (one set contains ten sealing caps)
RONIS SB30 keys 3SU1950-0FB80-0AA0 1 1 unit 41J
Spare key for M200D
for "manual local control" ordering option
3SU1950-0FB80-0AA0
3RK1902-4CA00-4AA0
, AS-Interface M12 feeders
For For Cable length Cable end
flat cable in feeder
AS-i/Uaux M12 socket -- Not 3RK1901-2NR20 1 1 unit 42C
available
M12 1m Not 3RK1901-2NR21 1 1 unit 42C
cable box available
2m Not 3RK1901-2NR22 1 1 unit 42C
available
3RK1901-2NR21
Cable end terminators 3RK1901-1MN00 1 10 units 42C
For sealing of open cable ends (AS-Interface shaped
cable) in IP67
3RK1901-1MN00
AS-Interface shaped cables, see also page 2/76
Material Color Quantity
9
Further accessories
AS-Interface addressing unit V3.0 3RK1904-2AB02 1 1 unit 42C
• For AS-Interface modules and sensors and
actuators with integrated AS-Interface according
to AS-i specification V3.0
• For setting the AS-i address of standard slaves,
and slaves with extended addressing mode
(A/B slaves)
• With input/output test function and many other
commissioning functions
• Battery operation with four type AA batteries
(IEC LR6, NEDA 15)
• Scope of supply:
- Addressing unit with four batteries
- Addressing cable, with M12 plug to addressing plug
(hollow plug), length 1.5 m
3RK1904-2AB02
M12 addressing cables to M12 3RK1902-4PB15-3AA0 1 1 unit 42D
• Standard M12 cable for addressing slaves with
M12 connection,e.g. K60R modules
3RK1902-4PB15-3AA0 • When using the current version of the 3RK1904-2AB01
addressing unit
• 1.5 m
Equipment manuals
M200D AS-Interface Basic motor starters, see
https://support.industry.siemens.com/cs/ww/en/view/35016496
M200D AS-Interface Standard motor starters, see
https://support.industry.siemens.com/cs/ww/en/view/38722160
3RK1902-1DA00
• 0 5 male contacts 3RK1902-1BA00 1 1 unit 42D
3RK1902-1BA00
Control cables, assembled at one end
M12, screw fixing, angled, B-coded,
no terminating resistor
3RK1902-1G. • / 5 female contacts, 3 m 3RK1902-1GB30 1 1 unit 42D
• / 5 female contacts, 5 m 3RK1902-1GB50 1 1 unit 42D
• / 5 female contacts, 10 m 3RK1902-1GC10 1 1 unit 42D
/ 0 Control cables, assembled at both ends
M12, screw fixing, angled, 5-pole
plug/socket connectors, B-coded,
no terminating resistor
3RK1902-1N.
• 3.0 m 3RK1902-1NB30 1 1 unit 42D
• 5.0 m 3RK1902-1NB50 1 1 unit 42D
• 10.0 m 3RK1902-1NC10 1 1 unit 42D
Further accessories
PROFIBUS trailing cables 6XV1830-3EH10 1 1M 5K2
Max. acceleration 4 m/s2, at least 3 000 000 bending
cycles, bending radius at least 60 mm, 2-core, shielded,
sold by the meter, minimum order quantity 20 m,
9
9
Connection for 24 V power supply of the M200D PROFIBUS/PROFINET
Plugs
On M200D, 7/8" for screw fixing, angled,
screw terminal, 1.5 mm2
• 1 5 female contacts 3RK1902-3DA00 1 1 unit 42D
3RK1902-3DA00
• 2 5 male contacts 3RK1902-3BA00 1 1 unit 42D
3RK1902-3BA00
1 Supply lines, assembled at one end
7/8" for screw fixing, angled, 1.5 mm2
• 5 female contacts, 3 m 3RK1902-3GB30 1 1 unit 42D
• 5 female contacts, 5 m 3RK1902-3GB50 1 1 unit 42D
• 5 female contacts, 10 m 3RK1902-3GC10 1 1 unit 42D
3RK1902-3G.
1 2 Supply lines, assembled at
both ends
7/8", for screw fixing, angled at both ends,
5-pole plug/socket connectors, 1.5 mm2
3RK1902-3N. •3m 3RK1902-3NB30 1 1 unit 42D
•5m 3RK1902-3NB50 1 1 unit 42D
• 10 m 3RK1902-3NC10 1 1 unit 42D
7/8" sealing caps 6ES7194-3JA00-0AA0 1 10 units 250
1 pack = 10 units
6ES7194-3JA00-0AA0
Equipment manual
M200D PROFIBUS/PROFINET motor starters, see
https://support.industry.siemens.com/cs/ww/en/view/38823402
Notes
9
10
SIRIUS 3RN2 thermistor motor
3RT1 contactors protection
SIRIUS 3RR21, 3RR22 monitoring
relays for mounting on 3RT2 contactors 10/129 General data
10/47 Current and active current monitoring 10/136 Basic units
SIRIUS 3RR24 monitoring relays 10/137 Accessories
for mounting on 3RT2 contactors Coupling relays and signal converters
for IO-Link 5/1 Coupling relays
10/55 Current and active current monitoring 3/138 3TG10 power relays/miniature
SIRIUS 3UG5 monitoring relays contactors
for stand-alone installation 10/138 SIRIUS 3RS70 signal converters
10/62 DC load monitoring
Siemens IC 10 · 2023
© Siemens 2023
Introduction
■ Overview
Type SIMOCODE pro C SIMOCODE pro V SIMOCODE pro S SIMOCODE pro V Page
PROFINET General Performance High Performance
General Performance PROFIBUS/PROFINET
Modbus RTU/EtherNet/IP
SIMOCODE pro 3UF7 motor management and control devices
Basic units ✓ ✓ ✓ ✓ 10/12
Current measuring modules ✓ ✓ ✓ ✓ 10/13
Current/voltage measuring modules -- -- -- ✓ 10/13
Operator panels ✓ ✓ ✓ ✓ 10/14
Operator panels with display -- -- -- ✓ 10/14
Expansion modules -- ✓ ✓ ✓ 10/15
Fail-safe expansion modules -- -- -- ✓ 10/17
Current transformers ✓ ✓ ✓ ✓ 10/21
SIMOCODE ES (TIA Portal) ✓ ✓ ✓ ✓ 14/12
SIMOCODE pro block library ✓ ✓ ✓ ✓ 14/15
for SIMATIC PCS 7
✓ Available
-- Not available
Introduction
Type 3UG546 3UG451., 3UG463. 3RR21, 3UG4641 3UG4625 3UG458. 3UG4501 3UG4651 Page
3UG461. 3RR22, with
3UG4621, 3UL23
3UG4622
Monitoring relays
DC load monitoring ✓ -- -- -- -- -- -- -- -- 10/62
Line monitoring -- ✓ -- -- -- -- -- -- -- 10/69
Voltage monitoring -- -- ✓ -- -- -- -- -- -- 10/74
Current monitoring -- -- -- ✓ -- -- -- -- -- 10/47, 10/77
Active current monitoring -- -- -- 3RR22 ✓ ✓ -- -- -- -- 10/47, 10/79
Power factor monitoring -- -- -- -- ✓ -- -- -- -- 10/79
Residual-current monitoring -- -- -- -- -- ✓ -- -- -- 10/82
Insulation monitoring -- -- -- -- -- -- ✓ -- -- 10/85
Level monitoring -- -- -- -- -- -- -- ✓ -- 10/89
Speed monitoring -- -- -- -- -- -- -- -- ✓ 10/92
✓ Available
-- Not available
10
monitoring
Residual-current monitoring -- -- -- -- -- ✓ -- 10/112
Speed monitoring -- -- -- -- -- -- ✓ 10/115
✓ Available
-- Not available
Introduction
Connection methods Ordering notes for multi-unit packaging
The monitoring and control devices are available with screw SIMOCODE pro S, SIRIUS 3RP25 timing relays, SIRIUS 3RS2
or spring-loaded terminals. temperature monitoring relays, and SIRIUS 3RN2 thermistor
motor protection can be ordered in practical and environ-
SIRIUS 3RP25 timing relays, 3UG458 insulation monitoring mentally multi-unit packaging on request.
relays, SIRIUS 3RS2 temperature monitoring relays,
SIRIUS 3RN2 thermistor motor protection and SIRIUS 3RS70 Multi-unit packaging with order code X90
signal converters are available with screw terminals or spring-
loaded terminals (push-in). When ordering products in multi-unit packaging, the article
number of the product concerned must be supplemented with
"-Z" and, in addition, the order code "X90" must be specified.
Screw terminals
Ordering examples:
Spring-loaded terminals, spring-loaded terminals • 3RP2505-1AB30-Z X90;
(push-in) Order quantity 16 items Delivery of one pack containing
16 items
The connection method is indicated in the
corresponding tables by the respective symbol shown • 3RP2505-1BB30-Z X90;
on orange backgrounds. Order quantity 12 items Delivery of one pack containing
12 items
"Increased safety" type of protection EEx e/d according to For more information, see page 16/7.
ATEX Directive 2014/34/EU
The communication-capable, modularly designed SIMOCODE pro
motor management system (SIRIUS Motor Management and
Control Devices) protects motors of types of protection EEx e and
EEx d in hazardous areas.
The SIRIUS 3RN2 thermistor motor protection relay protects
motors with types of protection EEx e and EEx d in hazardous
areas.
ATEX approval for operation in hazardous areas
The SIRIUS SIMOCODE pro 3UF7 motor management system is
certified for the protection of motors in hazardous areas
according to
• ATEX Ex I (M2); equipment group I, category M2 (mining)
• ATEX Ex II (2) GD; equipment group II, category 2 in area GD
The SIRIUS 3RN2011, 3RN2012-...30, 3RN2013 and 3RN2023
thermistor motor protection relays for PTC sensors are certified
according to ATEX Ex II (2) G and D for environments with
explosive gas or dust loads.
10
■ Overview
SIMOCODE pro offers, for example:
• Multifunctional, electronic full motor protection that is
independent of the automation system
• Integrated control functions instead of hardware for the motor
control
• Detailed operating, service and diagnostics data
• Open communication via PROFIBUS DP, PROFINET/OPC UA,
Modbus RTU or EtherNet/IP
• Safety relay function for the fail-safe disconnection of motors
up to SIL 3 according to IEC 61508, IEC 62061 or PL e
according to ISO 13849-1
• SIMOCODE ES is the software package for SIMOCODE pro
parameterization, startup and diagnostics, see page 14/12.
Device series
Basic Performance with SIMOCODE pro C
10
Current/voltage measuring module
Performance
Max. 5/7 expansion modules High
Safety
SIMOCODE pro V PN SIMOCODE pro V EIP SIMOCODE pro V PB SIMOCODE pro V MR
Operator panel
General
1 expansion module
IC01_00548b
Device series
PROFIBUS
Functions
Optional expansions
One option can be selected
1 2 3
Basic system
Current Basic unit Operator Ground-fault Temperature Digital module
measuring module panel module module Standard
SIMOCODE pro V PN GP
PROFINET/
OPC UA
Functions
IC01_00532b
10
Communication
Functions
System structure
Expansion possibilities SIMOCODE pro C SIMOCODE pro S SIMOCODE pro V SIMOCODE pro V
Basic Performance General Performance General Performance High Performance
PROFIBUS PROFIBUS PROFINET GP PROFIBUS/ PROFINET/
Modbus RTU EtherNet/IP
Operator panels ✓ ✓ ✓ ✓ ✓
Operator panels -- -- -- ✓ ✓
with display
Current measuring modules ✓ ✓ ✓ ✓ ✓
Current/voltage measuring modules -- -- -- ✓ ✓
Expansion modules:
• Digital modules -- -- 12) 2 2
1)
• Fail-safe digital modules -- -- -- 1 1
• Analog modules -- -- -- 1 2
• Ground-fault modules -- -- 1 1 1
• Temperature modules -- -- 1 1 2
• Multifunction modules -- 1 -- -- --
✓ Available 1) The fail-safe digital module can be used instead of one of the two
-- Not available digital modules.
2) Only monostable version can be used.
Per feeder each system always comprises one basic unit and added to the SIMOCODE pro V and SIMOCODE pro S by
one separate current measuring module. The two modules are means of optional expansion modules, thus supplementing the
connected together electrically through the system interface inputs and outputs already existing on the basic unit. With the
with a connecting cable and can be mounted mechanically DM-F Local and DM-F PROFIsafe fail-safe digital modules it is
connected as a unit (one behind the other) or separately also possible to integrate the fail-safe disconnection of motors in
(side by side). The motor current to be monitored is decisive the SIMOCODE pro V motor management system.
only for the choice of the current measuring module.
All modules are connected by connecting cables.
An operator panel for mounting in the control cabinet door is The connecting cables are available in various lengths.
optionally connectable through a second system interface on The maximum distance between the modules (e.g. between
the basic unit. Both the current measuring module and the the basic unit and the current measuring module) must not
operator panel are electrically supplied by the basic unit through exceed 2.5 m. The total length of all the connecting cables per
the connecting cable. More inputs, outputs and functions can be system interface of the basic unit may be up to 3 m.
10
Product versions Article number
SIMOCODE pro motor management system 3UF7 @@@– 1 @@0 @– 0
Type of unit/module e.g. 0 = basic unit @
Functional version of the module e.g. 20 = SIMOCODE pro S @@
Connection type of the current transformer e.g. A = through-hole technology @
Voltage version e.g. B = 24 V DC @
Enclosure color e.g. 1 = titanium gray @
Example 3UF7 0 2 0 – 1 A B 0 1 – 0
Note:
The article number scheme shows an overview of product For your orders, please use the article numbers quoted in the
versions for better understanding of the logic behind the article selection and ordering data.
numbers.
■ Benefits
General customer benefits Recording of measuring curves
• Integrating the whole motor feeder into the process control by SIMOCODE pro can record measuring curves and therefore is
means of PROFIBUS DP, PROFINET/OPC UA, Modbus RTU or able, for example, to present the progression of motor current
EtherNet/IP significantly reduces the wiring between the motor during motor startup.
feeder and the PLC
• Decentralization of the automated processes by means of Flexible motor control implemented with integrated control
configurable control and monitoring functions in the feeder functions (instead of comprehensive hardware interlocks)
saves resources in the automation system and ensures full Many predefined motor control functions have already been
functionality and protection of the feeder even if the I&C or bus integrated into SIMOCODE pro, including all necessary logic
system fails operations and interlocks:
• The acquisition and monitoring of operating, service and • Overload relays
diagnostics data in the feeder and process control system • Direct-on-line and reversing starters
increases plant availability as well as preventive maintenance
and service-friendliness • Star-delta (wye-delta) starters (also with direction reversal)
• The high degree of modularity allows users to perfectly • Two speeds, motors with separate windings (pole-changing
implement their plant-specific requirements for each motor starter); also with direction reversal
feeder • Two speeds, motors with separate Dahlander windings
• The SIMOCODE pro system offers functionally graded and (also with direction reversal)
space-saving solutions for each customer application • Positioner actuation
• The replacement of the control circuit hardware with • Solenoid valve actuation
integrated control functions decreases the number of • Actuation of a motor starter protector
hardware components and wiring required and in this way
limits stock keeping costs and potential wiring errors • Soft starter actuation (also with direction reversal)
• The use of electronic full motor protection permits better These control functions are predefined in SIMOCODE pro and
utilization of the motors and ensures long-term stability of the can be freely assigned to the inputs and outputs of the device
tripping characteristic and reliable tripping even after years of (including the PROFIBUS/PROFINET process image).
service
These predefined control functions can also be flexibly adapted
• Thanks to the precision of the current, voltage, power and to each customized configuration of a motor feeder by means of
energy measurements (especially those acquired by the freely configurable logic modules (truth tables, counters, timers,
2nd-generation current/voltage measuring modules), costs edge evaluation, etc.) and with the help of standard functions
can be internally allocated with a high degree of accuracy (power failure monitoring, emergency start, external faults, etc.),
Multifunctional, electronic full motor protection without additional auxiliary relays being necessary in the control
for rated motor currents up to 820 A circuit.
SIMOCODE pro offers comprehensive protection of the motor SIMOCODE pro makes a lot of additional hardware and wiring in
feeder by means of a combination of different, multi-step and the control circuit unnecessary, which results in a high level of
delayable protection and monitoring functions: standardization of the motor feeder in terms of its design and
circuit diagrams.
10
10
The operator panel is used to control the motor feeder and can SIMATIC S7-400 H. As such, SIMOCODE pro can provide
replace all conventional pushbuttons and indicator lights to save decisive added value also for the field level of plants in which
space. It makes SIMOCODE pro or the feeder directly operable plant availability and control system redundancy are priorities.
in the control cabinet. It features all the status LEDs available on SIMOCODE pro Modbus RTU
the basic unit and externalizes the system interface for simple
parameterization or diagnostics on a PC/PG. SIMOCODE pro Modbus RTU supports, for example:
Operator panel with display • Communication at 1 200/2 400/4 800/9 600/19 200 or
57 600 baud
As an alternative to the 3UF720 standard operator panel for • Access to freely parameterizable process image via
SIMOCODE pro V, a 3UF721 operator panel with display is also Modbus RTU
available. This can additionally indicate current measured
values, operating and diagnostics data or status information of • Access to all operating, service and diagnostics data via
the motor feeder at the control cabinet. The pushbuttons of the Modbus RTU
operator panel can be used to control the motor. Furthermore, SIMOCODE pro EtherNet/IP
it is possible to set parameters such as rated motor current,
limit values, etc. directly via the operator panel with display SIMOCODE pro EtherNet/IP supports, for example:
(with SIMOCODE pro V PROFIBUS as of E15, SIMOCODE pro V • Line and ring bus topology thanks to an integrated switch
Modbus RTU as of E03 and with all SIMOCODE pro V PROFINET
and EtherNet/IP). • Ring structures via Device Level Ring (DLR) protocol
• Operating, service and diagnostics data via standard
web browser
• NTP-synchronized time
• Parameter assignment via SIMOCODE ES V14 or higher –
via local device interface and Ethernet
Autonomous operation As an integrated option for the TIA Portal, the SIMATIC Energy
An essential feature of SIMOCODE pro is the autonomous Suite couples energy management with automation efficiently,
execution of all protection and control functions, even when making energy consumption at your production facility
communication to the I&C system is interrupted. This means that transparent.
even in the event of bus system or automation system failure, full Thanks to the simplified configuration of energy-measuring
functionality of the feeder is ensured or a specific behavior can components, e.g. SIMOCODE pro V, configuration effort is also
be parameterized in case of such a fault, e.g. targeted shutdown clearly reduced.
of the feeder or execution of particular parameterized control
mechanisms (such as reversal of the direction of rotation). Thanks to end-to-end connection with higher-level energy
management systems or cloud-based services, you can
seamlessly expand the recorded energy data to create a
cross-site energy management system.
The advantages at a glance:
• Automatic generation of energy management data
• Integration into TIA Portal and into automation
• Simple configuration
For more information, see page 1/3 or
www.siemens.com/energysuite.
■ Application
SIMOCODE pro is often used for automated processes where Safety technology for SIMOCODE pro
plant downtimes are very expensive (e.g. chemical, oil/gas,
water/wastewater, steel or cement industries) and where The safe disconnection of motors in the process industry is
it is important to prevent plant downtimes through detailed becoming increasingly important as the result of new and
operational, service and diagnostics data or to localize faults revised standards and requirements in the safety technology
very quickly when they occur. field.
With the DM-F Local and DM-F PROFIsafe fail-safe expansion
SIMOCODE pro is modular and space-saving and suited modules it is easy to integrate functions for fail-safe
especially for operation in motor control centers (MCCs) disconnection into the SIMOCODE pro V motor management
in the process industry and for power plant technology. system while retaining service-proven concepts. The strict
10
• Protection and control of motors in hazardous areas for types separation of safety functions and operational functions proves
of protection EEx e/d according to ATEX Directive 2014/34/EU particularly advantageous for planning, configuring and
- With heavy starting (paper, cement, metal and water construction. Seamless integration into the motor management
industries) system leads to greater transparency for diagnostics and during
- In high-availability plants (chemical, oil, raw material operation of the system.
processing industries, power plants)
Suitable components for this purpose are the DM-F Local and
• Dry-running protection of centrifugal pumps based on active DM-F PROFIsafe fail-safe expansion modules, depending on the
power monitoring for type of protection Ex b requirements:
Use of SIMOCODE pro 3UF7 with IE3 and IE4 motors • The DM-F Local fail-safe digital module for when direct
assignment between a fail-safe hardware shutdown signal
Note: and a motor feeder is required, or
When using the SIMOCODE pro 3UF7 in conjunction with highly • The DM-F PROFIsafe fail-safe digital module for when
efficient IE3 and IE4 motors, please observe the information on a fail-safe controller (F-CPU) creates the signal for
dimensioning and configuring, see Application Manual. disconnection and transmits it in a fail-safe manner
For more information, see page 1/8. through PROFIBUS/PROFIsafe or PROFINET/PROFIsafe to
the motor management system
■ Technical specifications
More information
Technical specifications, see Application Manual for controls with IE3 and IE4 motors, see
https://support.industry.siemens.com/cs/ww/en/ps/16337/td https://support.industry.siemens.com/cs/ww/en/view/94770820
Manual Collection "SIMOCODE pro", see Configuration Manual for load feeders, see
https://support.industry.siemens.com/cs/ww/en/view/109743951 https://support.industry.siemens.com/cs/ww/en/view/39714188
Manual for SIMOCODE pro fail-safe digital modules, see
https://support.industry.siemens.com/cs/ww/en/view/50564852
■ More information
Configuration instructions Types of protection EEx e and EEx d
When using an operator panel with display, please note that the The overload protection and the thermistor motor protection of
type and number of expansion modules that can be connected the SIMOCODE pro system comply with the requirements for
are limited for the use of a SIMOCODE pro V PROFIBUS basic overload protection of explosion-proof motors to the type of
unit (with product version lower than E15) or SIMOCODE pro V protection:
Modbus RTU (with product version lower than E03), see • EEx d "Flameproof enclosure" e.g. according to IEC 60079-1
• TIA Selection Tool • EEx e "Increased safety" e.g. according to IEC 60079-7
• SIMOCODE pro Manual Collection
When using SIMOCODE pro devices with a 24 V DC control
Protective separation voltage, electrical separation must be ensured using a battery or
a safety transformer according to IEC 61558-2-6.
All circuits in SIMOCODE pro are safely isolated from each other EC type-examination certificate: BVS 06 ATEX F 001
according to IEC 60947-1. That is, they are designed with Test report: BVS PP 05.2029 EC.
doubled clearance and creepage distances. In the event
10
of a fault, therefore, no parasitic voltages can be formed in Type of protection Ex b
neighboring circuits. The notes of the test report No. A0258 must
be complied with. The function for dry-running protection of centrifugal pumps in
hazardous areas complies with the requirements of the following
type of protection:
• Ex b "Control of ignition source", ignition protection system b1,
e.g. according to EN 80079-37
SIMOCODE pro is registered for the dry-running protection of
centrifugal pumps by means of active power monitoring
according to both ATEX and IEC Ex.
3UF7000-1AB00-0
SIMOCODE pro S
PROFIBUS DP interface, 1.5 Mbps, RS 485
4 I/2 O freely configurable, input for thermistor connection,
monostable relay outputs, can be expanded
by a multifunction module
Note: The connecting cable to the current measuring
module must be at least 15 cm.
Rated control supply voltage Us:
3UF7020-1AU01-0 • 24 V DC 3UF7020-1AB01-0 1 1 unit 42J
• 110 ... 240 V AC/DC 3UF7020-1AU01-0 1 1 unit 42J
SIMOCODE pro V
PROFIBUS DP interface, 12 Mbps, RS 485
4 I/3 O freely configurable, input for thermistor connection,
monostable relay outputs, can be expanded by
expansion modules
Rated control supply voltage Us:
• 24 V DC 3UF7010-1AB00-0 1 1 unit 42J
• 110 ... 240 V AC/DC 3UF7010-1AU00-0 1 1 unit 42J
3UF7010-1AB00-0
SIMOCODE pro PROFINET
SIMOCODE pro V PROFINET GP
ETHERNET/PROFINET IO,
OPC UA server and web server, 100 Mbps,
PROFINET system redundancy,
4 I/3 O freely configurable, input for
10
3UF7103-1AA00-0
2nd-generation current/voltage measuring modules
for SIMOCODE pro V2)
10
Voltage measuring up to 690 V,
measured values with increased accuracy,
power, power factor and frequency monitoring
• Straight-through transformers 0.3 ... 4 45 3UF7110-1AA01-0 1 1 unit 42J
3 ... 40 45 3UF7111-1AA01-0 1 1 unit 42J
10 ... 115 55 3UF7112-1AA01-0 1 1 unit 42J
20 ... 200 120 3UF7113-1AA01-0 1 1 unit 42J
1)
3UF7110-1AA01-0 • Busbar connection 20 ... 200 120 3UF7113-1BA01-0 1 1 unit 42J
63 ... 630 145 3UF7114-1BA01-0 1 1 unit 42J
Current/voltage measuring modules for dry-running
protection of centrifugal pumps in hazardous areas2)3)4)
• Straight-through transformers 0.3 ... 4 45 3UF7120-1AA01-0 1 1 unit 42J
3 ... 40 45 3UF7121-1AA01-0 1 1 unit 42J
10 ... 115 55 3UF7122-1AA01-0 1 1 unit 42J
20 ... 200 120 3UF7123-1AA01-0 1 1 unit 42J
• Busbar connection1) 20 ... 200 120 3UF7123-1BA01-0 1 1 unit 42J
63 ... 630 145 3UF7124-1BA01-0 1 1 unit 42J
3UF7123-1AA01-0
1)
One terminal parts kit 3RT1955-4PA00 or 3RT1966-4PA00 (see Note:
page 10/20) is included in the scope of supply for connection
to a contactor. SIMOCODE pro V basic unit in a hardened version via
2)
When installing the basic unit on a current/voltage measuring module, SIPLUS extreme upon request.
the connecting cable must be at least 15 cm long.
3)
The current/voltage measuring modules for dry-running protection require
SIMOCODE pro V PROFIBUS basic units as of product version E16,
SIMOCODE pro V PROFINET as of product version E13 or
SIMOCODE pro V EtherNet/IP as of product version E04.
4)
When using an operator panel with display with the current/voltage
measuring modules for dry-running protection, an operator panel
with display as of product version E03 is required.
3UF7200-1AA01-0
Analog modules
By means of the analog module, the basic unit can be 3UF7400-1AA00-0 1 1 unit 42J
optionally expanded by analog inputs and outputs
(0/4 ... 20 mA).
Two inputs (passive) for input and one output for output of
0/4 ... 20 mA signals, max. one analog module can be
connected per pro V PB/MB RTU basic unit and max. two
analog modules per pro V PN/EIP basic unit
10
3UF7400-1AA00-0
Ground-fault modules
Ground-fault monitoring using 3UL23 residual-current 3UF7510-1AA00-0 1 1 unit 42J
transformers and ground-fault modules is used in cases
where precise detection of the ground-fault current is
required or power systems with high impedance are
grounded.
With the ground-fault module, it is possible to determine
the precise fault current as a measured value, and to
define freely selectable warning and trip limits in a wide
range from 30 mA ... 40 A.
3UF7510-1AA00-0 One input for connecting a 3UL23 residual-current
transformer, up to one ground-fault module can be
connected
Note:
For corresponding residual-current transformers,
see page 10/84.
Temperature modules
Irrespective of the thermistor motor protection of the basic 3UF7700-1AA00-0 1 1 unit 42J
units, up to an additional three analog temperature sensors
can be evaluated using a temperature module.
Sensor types: Pt100/Pt1000, KTY83/KTY84 or NTC
Three inputs for connecting up to three analog temperature
sensors, up to one temperature module can be connected
per pro V PB/MB RTU basic unit and up to two temperature
modules per pro V PN/EIP basic unit
3UF7700-1AA00-0
Multifunction modules
The multifunction module is the expansion module of
the SIMOCODE pro S device series with the following
functions:
• Digital module function with four digital inputs and two
monostable relay outputs
• Ground-fault module function with an input for the
connection of a 3UL23 residual-current transformer with
freely selectable warning and trip limits in a wide zone of
30 mA ... 40 A
3UF7600-1AU01-0 • Temperature module function with an input for connecting
an analog temperature sensor Pt100, Pt1000, KTY83,
KTY84, or NTC
Max. one multifunction module can be connected per pro S
basic unit
Input voltage of the digital inputs:
• 24 V DC 3UF7600-1AB01-0 1 1 unit 42J
• 110 ... 240 V AC/DC 3UF7600-1AU01-0 1 1 unit 42J
10
10
3RA6936-0B
Addressing plugs
For assigning the PROFIBUS or Modbus RTU address 3UF7910-0AA00-0 1 1 unit 42J
without using a PC/PG to SIMOCODE pro through the
system interface
3UF7910-0AA00-0
3UF7960-0AA00-0
Door adapters
For external connection of the system interface from 3UF7920-0AA00-0 1 1 unit 42J
a control cabinet, for example
3UF7920-0AA00-0
Adapters for operator panel
The adapter enables the smaller 3UF7200 operator panel 3UF7922-0AA00-0 1 1 unit 42J
10
from SIMOCODE pro to be used in a front panel cutout in
which previously, e.g. after a change of system, a larger
3UF52 operator panel from SIMOCODE-DP had been
used, degree of protection IP54
3UF7922-0AA00-0
Labeling strips
• For pushbuttons of the 3UF720 operator panel 3UF7925-0AA00-0 100 400 units 42J
• For pushbuttons of the 3UF721 operator panel 3UF7925-0AA01-0 100 600 units 42J
with display
• For LEDs of the 3UF720 operator panel 3UF7925-0AA02-0 100 1200 units 42J
3UF7925-0AA02-0
Push-in lugs
For screw fixing, e.g. on mounting plate,
two units required per device
• Can be used for 3UF71.0, 3UF71.1 and 3UF71.2 3RV2928-0B 100 10 units 41E
• Can be used for 3UF700, 3UF701, 3UF73, 3UF74, 3UF75 3RP1903 1 10 units 41H
and 3UF77
• Can be used for 3UF7020, 3UF7600 3ZY1311-0AA00 1 10 units 41L
3RV2928-0B
Terminal covers
Covers for cable lug and busbar connections
• Length 100 mm, can be used for 3UF71.3-1BA0.-0 3RT1956-4EA1 1 1 unit 41B
• Length 120 mm, can be used for 3UF71.4-1BA0.-0 3RT1966-4EA1 1 1 unit 41B
Covers for box terminals
• Length 25 mm, can be used for 3UF71.3-1BA0.-0 3RT1956-4EA2 1 1 unit 41B
• Length 30 mm, can be used for 3UF71.4-1BA0.-0 3RT1966-4EA2 1 1 unit 41B
3RT1956-4EA1 Covers for screw terminals
Between contactor and current measuring module or
current/voltage measuring module for direct mounting
• Can be used for 3UF71.3-1BA0.-0 3RT1956-4EA3 1 1 unit 41B
3RT1956-4EA2 • Can be used for 3UF71.4-1BA0.-0 3RT1966-4EA3 1 1 unit 41B
Terminal parts kit
Can be used for current and/or current/voltage measuring
modules with DIN-rail connection, complete for one contactor
• M 8 x 25 3RT1955-4PA00 1 1 unit 41B
• M 10 x 30 3RT1966-4PA00 1 1 unit 41B
Box terminal blocks
For round and ribbon cables
• Up to 70 mm2, can be used for 3UF71.3-1BA0.-0 3RT1955-4G 1 1 unit 41B
• Up to 120 mm2, can be used for 3UF71.3-1BA0.-0 3RT1956-4G 1 1 unit 41B
• Up to 240 mm2, can be used for 3UF71.4-1BA0.-0 3RT1966-4G 1 1 unit 41B
3RT1956-4G
Bus termination modules
With separate control supply voltage for bus termination
following the last unit on the bus line
Supply voltage:
• 115/230 V AC 3UF1900-1KA00 1 1 unit 42J
• 24 V DC 3UF1900-1KB00 1 1 unit 42J
3UF1900-1KA00
Software
10
3ZS1322...
SIMOCODE pro block library for SIMATIC PCS 7
The PCS 7 block library can be used for simple and easy
integration of SIMOCODE pro into the SIMATIC PCS 7
process control system, see page 14/15.
3ZS1632-1XE04-0YA0
■ Overview
The 3UF18 current transformers are protection transformers and
More information are used for actuating overload relays. Protection transformers
Homepage, see www.siemens.com/sirius are designed to ensure proportional current transfer up to
Industry Mall, see www.siemens.com/product?3UF18 a multiple of the primary rated current. The 3UF18 current
transformers convert the maximum current of the corresponding
operating range into the standard value of 1 A secondary.
3UF1868
■ Accessories
For contactor type Article No. Price PU PS* PG
per PU (UNIT,
SET, M)
Terminal covers
For transformer/contactor combinations and 3TX7696-0A 1 1 unit 41B
stand-alone installation for 3UF1868-3GA00 transformer
Note: One cover required per connection side.
10
■ Overview
More information
Homepage, see www.siemens.com/LOGO
Industry Mall, see www.siemens.com/product?logo
LOGO!, see Catalog ST 70
The space-saving basic versions The cost-optimized basic versions Digital and analog inputs/outputs for
connection to LOGO!
LOGO! CMK2000 communications modules LOGO! CSM unmanaged LOGO! CMR (wireless communication)
10
For integration of LOGO! 8 in KNX For connecting to Industrial Ethernet in For configuring a low-cost remote
installations line, tree or star topologies signaling system
The flat power supply for distribution For switching resistive loads and motors The user-friendly software for switching
boards directly program generation
■ Application
The LOGO! logic module is the user-friendly, low-cost solution • Special controls for conservatories and greenhouses
for simple control tasks. • Signal preprocessing for other controllers
LOGO! is universally applicable, e.g.: LOGO! Modular logic modules can be expanded easily for each
• Building installation and wiring (lighting, shutters, awnings, application.
doors, access control, barriers, ventilation systems, etc.)
Marine approvals:
• Control cabinet installation American Bureau of Shipping, Bureau Veritas, Det Norske
• Machine and device construction (pumps, small presses, Veritas, Germanischer Lloyd, Lloyd's Register of Shipping,
compressors, hydraulic lifts, conveyors, etc.) Polski Rejestr Statków, etc.
■ Overview
The SIRIUS 3RA28 function modules enable the assembly
of starters and contactor assemblies for direct-on-line and
star-delta (wye-delta) starting. They include the key control
functions required for the particular feeder, e.g. timing and
electrical interlocking. The function modules that function as
timing relays are mounted quickly and simply on SIRIUS
contactors – without any great wiring effort.
The SIRIUS 3RA28 solid-state time-delay auxiliary switches
which can be mounted on contactors are designed for contactor
coil voltages in the range from 24 to 240 V AC/DC (wide voltage
range). Auxiliary switches for control and alarm signals are used
specially for switching the smallest signals for electronics
applications. They are used, for example, for allowing a pump
or fan to run on, or for the delayed activation of a gate drive.
Simply by being plugged in place, the SIRIUS 3RT19 timing
relays enable different functionalities required for the assembly
of starters to be realized in the feeder. At the same time the
timing relays for mounting on contactors reduce the wiring work
7PV15, SIRIUS 3RP25 and SIRIUS 3RP20 timing relays required within the feeder and save space in the control cabinet.
More information
Device series
Homepage, see www.siemens.com/sirius-timing-relays SIRIUS timing relays for DIN-rail mounting
Industry Mall, see www.siemens.com/product?3RP • SIRIUS 3RP25 timing relays, 17.5 mm and 22.5 mm,
see page 10/24
Electronic timing relays are used in control, starting, and protective • SIRIUS 3RP20 timing relays, 45 mm, see page 10/36
circuits for all switching operations involving time delays.
• 7PV15 timing relays, 17.5 mm, see page 10/42
Their fully developed concept and space-saving, compact
design make the SIRIUS 3RP timing relays ideal timer modules SIRIUS timing relays for mounting on contactors
for control cabinet, switchgear and control manufacturers in • SIRIUS 3RA28 solid-state time-delay auxiliary switches for
the industry. mounting on 3RT2 contactors and 3RH2 contactor relays,
see page 3/95
With their narrow design, the 7PV15 timing relays are ideal in
particular for use in heating, ventilation and air-conditioning • SIRIUS 3RA28 function modules for mounting on 3RT2
systems and in compressors. All 7PV15 timing relays in this contactors and 3RH2 contactor relays, see page 3/100
enclosure version are suitable for snap-on mounting on • SIRIUS 3RT19 solid-state time-delay auxiliary switches for
TH 35 DIN rails according to IEC 60175. The enclosure complies mounting on 3RT1 contactors, see page 3/96
with DIN 43880.
■ Benefits
10
• The right design for every application • Versions with logical separation
• Clear-cut basic range with five basic units in the case of the • Low variance: One design for distribution boards and for
7PV15 timing relays, and up to seven basic units in the case control cabinets
of the 3RP timing relays • Compliance with EMC requirements for buildings
• Considerable logistical advantages thanks to versions with • Environmentally friendly laser inscription instead of printing
wide voltage and wide time setting range containing solvents
• No tools required for assembly or disassembly on DIN rails • Versions as snap-on modules for reducing wiring and saving
• Cadmium-free relay contacts space in the control cabinet
• Recyclable, halogen-free enclosure • Versions with coated printed circuit board
• Optimum price/performance ratio • Versions with screw terminals or alternatively with spring-
loaded terminals
■ Application
Timing relays with ON-delay Star-delta (wye-delta) timing relays
• Interference pulse suppression (gating of interference pulses) • Switching over motors from wye to delta with a dead interval
• Gradual startup of motors so as not to overload the power of 50 ms to prevent phase-to-phase short circuits
supply Multifunctional timing relays
Timing relays with OFF-delay • Maximum flexibility, with a device for every application
• Generation of overtravel functions following removal of voltage • Available with relay and semiconductor output
• Gradual, delayed shutdown, e.g. of motors or fans, to allow • Versions for railway applications for more exacting
a plant to be shut down selectively requirements (e.g. temperature range, vibration/shock
resistance and EMC)
Clock-pulse relay
• Flashing, asymmetrical Watchdog function
• Monitoring of cyclic events
■ Overview
More information
Homepage, see www.siemens.com/sirius-timing-relays
Industry Mall, see www.siemens.com/product?3RP25
LED for indicating TIA Selection Tool Cloud (TST Cloud), see
"Timing relay
connected to voltage" Cover caps inscribed www.siemens.com/tstcloud/?node=SIRIUSRelais
on inside Conversion tool, see www.siemens.com/conversion-tool
LED for indicating Simulator, see
"Relay switched"
IC01_00291a
https://support.industry.siemens.com/cs/ww/en/view/103556391
Operating time
adjustment switch
Time setting range
selector switch Data matrix code
Function selector
switch
2 S1
1
A1 B1
K2 K1
A2
Setting the functions on the device N
IC01_00297
The functions of the 3RP2505 multifunctional timing relays can
be set by means of the function selector switch. Whether both
Diagram
CO contacts are switched in parallel or one CO contact with
a delay and one instantaneously and the choice of time setting
range are set by means of the time setting range selector switch.
The exact operating time can be adjusted with the operating
time switch.
Overview of functions
Identifica- 13 functions 27 functions
tion letter
1 CO contact (1 CO), 1 NO contact (1 NO) semiconductor, 13 functions (A - M) 2 CO contacts switched in parallel (2 CO) +
2 CO contacts switched in parallel (2 CO) or 13 functions (A - M) 1 delayed CO contact + 1 instantaneous CO contact
2 CO contacts force-guided and switched in parallel with delay (1 CO + 1 CO) and star-delta (wye-delta) function
(2 CO)
A ON-delay ON-delay and instantaneous contact
B OFF-delay with control signal OFF-delay with control signal and instantaneous contact
C ON-delay/OFF-delay with control signal ON-delay/OFF-delay with control signal and instantaneous contact
10
D Flashing, symmetrical, starting with interval Flashing, symmetrical, starting with interval and instantaneous contact
E Passing make contact, interval relay Passing make contact, interval relay and instantaneous contact
F Retriggerable interval relay with deactivated control signal Retriggerable interval relay with deactivated control signal
(passing break contact with control signal) (passing break contact with control signal) and instantaneous contact
G Passing make contact, with control signal, not retriggerable Passing make contact, with control signal, not retriggerable,
(pulse-forming with control signal) (pulse-forming with control signal) and instantaneous contact
H Additive ON-delay, instantaneous OFF Additive ON-delay, instantaneous OFF with control signal
with control signal and instantaneous contact
I Additive ON-delay with control signal Additive ON-delay with control signal and instantaneous contact
J Flashing, symmetrical, starting with pulse Flashing, symmetrical, starting with pulse and instantaneous contact
3RP25 simulator
■ Benefits
• Easy stock keeping and logistics thanks to low variance of Standards and approvals
devices • IEC 60721-3-3 "Classification of environmental conditions"
• Reduced space requirement in the control cabinet thanks to • IEC 61812-1/DIN VDE 0435 Part 2021 "Specified time relays
variants in width 17.5 mm and 22 mm for industrial use"
• Consistent for all functions thanks to wide voltage range from • IEC 61000-6-2, IEC 61000-6-3 and IEC 61000-6-4
12 to 240 V AC/DC "Electromagnetic compatibility"
• Up to 27 functions according to IEC 61812 in the • IEC 60947-5-1 "Low-voltage switchgear and controlgear –
multifunctional timing relay with wide voltage range Electromechanical control circuit devices"
• Multifunctional timing relay with semiconductor output for high
switching frequencies, bounce-free and wear-free switching
■ Application
Timing relays are used in control, starting, and protective circuits to IPC-610. Suitable for applications in rail, agriculture, mining,
for all switching operations involving time delays. They woodworking, etc.
10
Use in environments exposed to dust, condensation, rapid All timing relays are suitable for snap-on mounting on TH 35 DIN
temperature changes and corrosion is possible thanks to rails according to IEC 60715 or for screw fixing.
the standard coating of the printed circuit board according
■ Technical specifications
More information
Technical specifications, see Internal circuit diagrams, see CAx Download Manager
https://support.industry.siemens.com/cs/ww/en/ps/16354/td https://support.industry.siemens.com/my/ww/en/CAxOnline#CAxOnline
Equipment Manual, see FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/16354/faq
https://support.industry.siemens.com/cs/ww/en/view/103532830
10
3RP2525-.BW30,
3RP2505-.BW30-0AX0,
3RP2505-.CW30,
3RP2527-.EW30,
3RP257.-.NW30,
3RP2560-.SW30
General technical specifications
Operating range factor of the
control supply voltage, rated value
• At AC
- At 50 Hz 0.85 ... 1.1 0.85 ... 1.1 0.8 ... 1.1 0.7 ... 1.1
- At 60 Hz 0.85 ... 1.1 0.85 ... 1.1 0.8 ... 1.1 0.7 ... 1.1
• At DC 0.85 ... 1.1 -- 0.8 ... 1.1 0.7 ... 1.1
A1/A2 A1/A2
> 35 ms A1/A2
IC01_00344
IC01_00341d
A1/A2
IC01_00343
B1/A2
IC01_00342
B1/A2
15/18 15/18
15/18 15/16
15/16 15/18 15/16
t 15/16 t t
t t t
A B C D
ON-delay OFF-delay with control signal ON-delay/OFF-delay with Flashing, symmetrical, starting with
control signal interval
A1/A2
B1/A2 IC01_00346
IC01_00412
B1/A2
IC01_00347
B1/A2
15/18
15/16 15/18 15/18 15/18
t 15/16 15/16 15/16
t t t
E F G H
Passing make contact, interval relay Retriggerable interval relay with Passing make contact with Additive ON-delay, instantaneous OFF
deactivated control signal (passing control signal, not retriggerable with control signal
break contact with control signal) (pulse-forming with control signal)
A1/A2
1s B1/A2
IC01_00350c
IC01_00348a
B1/A2
15/18 15/18 1s
15/18 15/16 15/16 15/18
15/16 t t t 15/16
t t
I J K L
10
Additive ON-delay with control signal Flashing, symmetrical, starting with Pulse-delayed (fixed pulse (at 1 s) Pulse-delayed with control signal (fixed
pulse and settable pulse delay) pulse (at 1 s) and settable pulse delay)
A1/A2
IC01_00351
B1/A2
15/18
15/16
t <t t
M
Retriggerable interval relay with
activated control signal (watchdog)
Legend
A ... M Identification letters
Timing relay energized
Contact closed
Contact open
A1/A2 A1/A2
> 35 ms A1/A2
A1/A2
B1/A2
B1/A2 15/18
15/18 15/16
NSB0_00871d
15/18
IC01_00313
NSB0_00876
15/16 15/18
15/16
15/16 t t
IC01_00310
25/28
25/28 t 25/28 25/26
25/26 25/28 25/26
t t
t 25/26 t t
t
A B C D
ON-delay OFF-delay with control signal ON-delay/OFF-delay with Flashing, symmetrical, starting with
control signal interval
NSB0_00884
IC01_00411
15/16 15/16 15/16
25/28
25/26 25/28 25/28 25/28
t 25/26 25/26 25/26
t t t
E F G H
Passing make contact, interval relay Retriggerable interval relay with Passing make contact with Additive ON-delay, instantaneous OFF
deactivated control signal (passing control signal, not retriggerable with control signal
break contact with control signal) (pulse-forming with control signal)
A1/A2
A1/A2 A1/A2
t1 t2 t3 A1/A2 1s B1/A2
B1/A2 15/18 1s
15/18
15/16 IC01_00562 15/18
IC01_00476
15/16
15/18 15/16
IC01_00321c
1s
IC01_00307b
I J K L
Additive ON-delay with control signal Flashing, symmetrical, starting with Pulse-delayed (fixed pulse at 1 s and Pulse-delayed with control signal (fixed
10
pulse settable pulse delay) pulse at 1 s and settable pulse delay)
A1/A2
B1/A2
15/18
15/16
IC01_00323
t <t t
25/28
25/26
t <t t
M
Retriggerable interval relay with
activated control signal (watchdog)
Legend
A ... M Identification letters
Timing relay energized
Contact closed
Contact open
A1/A2
> 35 ms A1/A2
A1/A2 A1/A2 > 35ms
B1/A2
15/18 B1/A2
15/18
NSB0_00871d
IC01_00309
IC01_00310
25/28 t t 15/16
IC01_00311
25/26 21/24 25/28 t
t 21/22 25/26 21/24
t 21/22
ON-delay ON-delay and instantaneous contact OFF-delay with control signal OFF-delay with control signal and
instantaneous contact
C D
2 CO switched in parallel 1 delayed CO contact + 2 CO switched in parallel 1 delayed CO contact +
1 instantaneous CO contact 1 instantaneous CO contact
IC01_00313
15/18 15/16
NSB0_00876
IC01_00314
15/16 15/16 t t
t t
IC01_00312
25/28
25/28 t t 25/26 21/24
25/26 21/24 21/22
21/22 t t
t t
ON-delay/OFF-delay with ON-delay/OFF-delay with control Flashing, symmetrical, starting with Flashing, symmetrical, starting with
control signal signal and instantaneous contact interval interval and instantaneous contact
E F
2 CO switched in parallel 1 delayed CO contact + 2 CO switched in parallel 1 delayed CO contact +
1 instantaneous CO contact 1 instantaneous CO contact
A1/A2
> 35ms A1/A2
A1/A2 A1/A2 >35ms
B1/A2
15/18 B1/A2
15/18
NSB0_00880
15/18
IC01_00315
15/16
25/28 t 15/16
IC01_00316
10
Passing make contact, interval relay Passing make contact, interval relay Retriggerable interval relay with Retriggerable interval relay with
and instantaneous contact deactivated control signal (passing deactivated control signal (passing
break contact with control signal) break contact with control signal) and
instantaneous contact
G H
2 CO switched in parallel 1 delayed CO contact + 2 CO switched in parallel 1 delayed CO contact +
1 instantaneous CO contact 1 instantaneous CO contact
A1/A2 A1/A2
A1/A2 t1 t3 A1/A2
> 35ms >35ms t2 t1 t3
t2
B1/A2 B1/A2
B1/A2 B1/A2
15/18 15/18
15/18 15/18
NSB0_00884
IC01_00411
15/16 15/16
15/16 15/16
IC01_00317
IC01_00318
25/28 t 25/28 t
25/26 21/24 25/26 21/24
t 21/22 t 21/22
Passing make contact with Passing make contact with Additive ON-delay, instantaneous Additive ON-delay, instantaneous OFF
control signal, not retriggerable control signal, not retriggerable OFF with control signal with control signal and instantaneous
(pulse-forming with control signal) (pulse-forming with control signal) contact
and instantaneous contact
Legend
A ... H Identification letters
Timing relay energized
Contact closed
Contact open
A1/A2 A1/A2
t1 t2 t3 t1 t3 A1/A2
t2 A1/A2
B1/A2 B1/A2 15/18
15/18
IC01_00476
15/16
15/18 15/18 15/16
IC01_00307b
IC01_00319
15/16 15/16 25/28 t t
IC01_00306
25/28 t 25/26 21/24
25/26 21/24 t t 21/22
t 21/22
Additive ON-delay with control signal Additive ON-delay with control signal Flashing, symmetrical, starting with Flashing, symmetrical, starting with
and instantaneous contact pulse pulse and instantaneous contact
K L
2 CO switched in parallel 1 delayed CO contact + 2 CO switched in parallel 1 delayed CO contact +
1 instantaneous CO contact 1 instantaneous CO contact
A1/A2
A1/A2
A1/A2 A1/A2
B1/A2
1s B1/A2
1s
15/18 15/18 1s
NSB0_00871d
15/16
IC01_00321c
t 15/16
IC01_00322b
25/28 t 1s
25/26 21/24 25/28 t
21/22 25/26 21/24
t 21/22
t
Pulse-delayed (fixed pulse at 1 s and Pulse-delayed (fixed pulse at 1 s and Pulse-delayed with control signal Pulse-delayed with control signal (fixed
settable pulse delay) settable pulse delay) and (fixed pulse at 1 s and settable pulse pulse at 1 s and settable pulse delay)
instantaneous contact delay) and instantaneous contact
M *
2 CO switched in parallel 1 delayed CO contact + 2 CO contacts switched in parallel or
1 instantaneous CO contact 1 delayed CO contact +
1 instantaneous CO contact
A1/A2
A1/A2
B1/A2 A1/A2
B1/A2
IC01_00325
15/18 15/18
10
15/16 15/18
IC01_00323
15/16 25/28
IC01_00324
t <t t
25/28 t <t t t 50ms
25/26 21/24
21/22
t <t t
Retriggerable interval relay with Retriggerable interval relay with Star-delta (wye-delta) function
activated control signal (watchdog) activated control signal and
instantaneous contact (watchdog)
Legend
I ... M Identification letters
Timing relay energized
Contact closed
Contact open
A1/A2 A1/A2
NSB0_00869a
NSB0_00858
A1/A2 >35 ms
15/18
NSB0_00871d
NSB0_00859
15/16 A1/A2 B1/A2
15/18
15/16 t 15/18
25/28
t 25/26 15/16
t t
3RP251.-.AW30, 1 CO, ON-delay 3RP2525-..W30, 2 CO, ON-delay 3RP2527-.EW30, 1 NO 3RP2535-.AW30, 1 CO, OFF-delay with
(semiconductor), ON-delay control signal
250 ms 250 ms
> 250ms 250 ms A1/A2 A1/A2
IC01_00327
A1/A2 A1/A2
IC01_00354
15/18 15/18
15/16 15/16
IC01_00355
IC01_00326
15/18 15/18
15/16 15/16 t t
25/28 25/28
t t 25/26 25/26
t t
3RP2540-.A.30, 1 CO, OFF-delay 3RP2540-.A.30, 1 CO, positive 3RP2540-.B.30, 2 CO, OFF-delay 3RP2540-.B.30, 2 CO, positive passing
(N)1) passing make contact (O)1) (N)1) make contact (O)1)
A1/A2
A./A2 A1/A2
NSB0_00863
A1/A2
IC01_00330a
B1/A2
IC01_00407b
15/18 17/18 17/18
17/18
15/16
IC01_00328a
50 ms 17/28 17/28
17/28 t
t 50 ms 50 ms
Dead time Pulse time t t Idling
17/38
3RP2555-.AW30, 1 CO, flashing, 3RP2560-.SW30, 3 NO, star-delta 3RP257.-.NM20, 2 NO, star-delta 3RP257.-.NW30, 2 NO, star-delta
asymmetrical, starting with interval (wye-delta) function with overtravel (wye-delta) function (wye-delta) function
(clock-pulse relay) function (idling)
Legend
Timing relay energized
10
Contact closed
Contact open
1) 3RP2540 has a double function:
Function N = OFF-delay
Function O = Positive passing make contact.
Note: B./A2
Observe response time (dead time) of 400 ms on energizing
17/18
control supply voltage until contacts 17/18 and 17/38 close. Y
NSB0_00894f
17/28
A./A2
17/38
B./A2
tY 50 ms tIdling tIdling tIdling
17/18
Y Operation 4
NSB0_00891d
17/28 Legend
17/38 Timing relay energized
Contact closed
tY 50 ms tIdling tIdling50 ms tIdling 300 ms
Contact open
tY = Star time 1 to 20 s
Operation 1
tIdling = Idling time (coasting time) 30 to 600 s
Operation 2: Start contact B./A2 is closed when control supply
voltage A./A2 is applied.
Note:
If the control signal B./A2 is already present when the control
supply voltage A./A2 is applied, no timing is started. The timing The following applies to all operations: The pressure switch
is only started when the control signal B./A2 is switched off. controls the timing via B./A2.
10
Y
high demand for compressed air. A special control circuit
NSB0_00892d
17/28
prevents the compressor from being switched off immediately
17/38
when the required air pressure in the tank has been reached.
Instead, the valve in the intake tube is closed and the
compressor runs in "Idling" mode, i.e. in no-load operation for
tY tIdling
50 ms a specific time which can be set from 30 to 600 s.
Operation 2 If the pressure falls within this time, the motor does not have to
be restarted again, but can return to rated load operation from
Operation 3: Start contact B./A2 closes while star time is running
no-load operation.
If the control signal B./A2 is applied again during the star time,
If the pressure does not fall within this idling time, the motor is
the idling time starts and the timing is terminated normally.
switched off.
The pressure switch controls the timing via B./A2.
A./A2
The control supply voltage is applied to A./A2 and the start
B./A2 contact B./A2 is open, i.e. there is no control signal on B./A2
when the control supply voltage is applied. The pressure switch
17/18 signals "too little pressure in system" and starts the timing by way
Y of terminal B./A2. The compressor is started, enters * operation,
and fills the pressure tank.
NSB0_00893d
17/28
When the pressure switch signals "sufficient pressure", the
17/38
control signal B./A2 is applied, the idling time (coasting time)
is started, and the compressor enters no-load operation for the
tY 50 ms
set period of time from 30 to 600 s. The compressor is then
tIdling switched off. The compressor is only restarted if the pressure
switch responds again (low pressure).
Operation 3
Number of Number of CO Semi- Adjustable Control supply voltage Stan- Article No. Price PU PS* PG
NO contacts contacts con- time dard per PU (UNIT,
ductor coating SET, M)
Instan- De- Instan- De- output at at DC IPC-610
tane- layed tane- layed 50/60
ous switch- ous switch- Hz AC
switch- ing switch- ing
ing ing
V V
13 functions
0 0 0 1 No 0.05 s ... 100 h 24 24 No 3RP2505-@AB30 1 1 unit 41H
12 ... 240 12 ... 240 No 3RP2505-@AW30 1 1 unit 41H
Yes 3RP2505-2AW30-0AX0 1 1 unit 41H
0 1 0 0 Yes 0.05 s ... 100 h 12 ... 240 12 ... 240 No 3RP2505-@CW30 1 1 unit 41H
13 functions, suitable for railway applications
0 0 0 21) No 0.05 s ... 100 h 24 ... 240 24 ... 240 No 3RP2505-@RW30 1 1 unit 41H
Yes 3RP2505-2RW30-0AX0 1 1 unit 41H
27 functions
0 0 0 22) No 0.05 s ... 100 h 24 24 No 3RP2505-@BB30 1 1 unit 41H
400 ... 440 -- No 3RP2505-@BT20 1 1 unit 41H
12 ... 240 12 ... 240 No 3RP2505-@BW30 1 1 unit 41H
Yes 3RP2505-2BW30-0AX0 1 1 unit 41H
ON-delay
0 0 0 1 No 0.5 ... 10 s 12 ... 240 12 ... 240 No 3RP2511-@AW30 1 1 unit 41H
1 ... 30 s 12 ... 240 12 ... 240 No 3RP2512-@AW30 1 1 unit 41H
5 … 100 s 12 ... 240 12 ... 240 No 3RP2513-@AW30 1 1 unit 41H
0.05 s ... 100 h 12 ... 240 12 ... 240 No 3RP2525-@AW30 1 1 unit 41H
0 0 0 2 No 0.05 s ... 100 h 24 24 No 3RP2525-@BB30 1 1 unit 41H
12 ... 240 12 ... 240 No 3RP2525-@BW30 1 1 unit 41H
0 1 0 0 Yes 0.05 s ... 240 s 12 ... 240 12 ... 240 No 3RP2527-@EW30 1 1 unit 41H
10
■ Accessories
More information
You can find information on configuring and dimensioning the accessories
in the Equipment Manual, see
https://support.industry.siemens.com/cs/ww/en/view/103532830
3ZY1122-1BA00
Spring-loaded
terminals (push-in)
• 2-pole, up to 1 x 4 mm² or 2 x 1.5 mm² 3ZY1122-2BA00 1 6 units 41L
(in shared end sleeve)
3ZY1122-2BA00
Accessories for enclosures
Sealing covers
• 17.5 mm 3ZY1321-1AA00 1 5 units 41L
• 22.5 mm 3ZY1321-2AA00 1 5 units 41L
3ZY1321-2AA00
Push-in lugs 3ZY1311-0AA00 1 10 units 41L
For wall mounting
3ZY1311-0AA00
10
Coding pins 3ZY1440-1AA00 1 12 units 41L
For removable terminals of SIRIUS devices
in the industrial DIN-rail enclosure;
enable the mechanical coding of terminals
3ZY1440-1AA00
Hinged cover
Replacement cover, without terminal labeling, titanium gray
• 17.5 mm wide 3ZY1450-1AA00 1 5 units 41L
• 22.5 mm wide 3ZY1450-1AB00 1 5 units 41L
3ZY1450-1AB00
Blank labels
Unit labeling plates1)
For SIRIUS devices
• 10 mm x 7 mm, titanium gray 3RT2900-1SB10 100 816 units 41B
• 20 mm x 7 mm, titanium gray 3RT2900-1SB20 100 340 units 41B
IC01_00181
3RT2900-1SB20
Tools for opening spring-loaded terminals
Screwdrivers Spring-loaded
For all SIRIUS devices with spring-loaded terminals terminals (push-in)
■ Overview
Multifunction
The functions of the 3RP2005 multifunctional timing relays can
be set by means of the function selector switch. Insert labels can
be used to adjust different functions of the timing relay clearly
LED for indicating
"Timing relay energized" and unmistakably. The corresponding labels can be ordered as
an accessory. The same potential must be applied to terminals
IC01_00376
(left)
LED for indicating A. and B.
"Relay switched" Function selector
(right) For functions, see 3RP2901 label set, page 10/41.
switch
Time setting
Note:
Time setting
range selector range adjuster,
switch The activation of loads parallel to the start input is not
analog
permissible when using AC control voltage.
Unit labeling
plate
L1 L1
S1 K1 S1
■ Benefits
• Suitable for 3RT miniature contactors • Labels are used on the multifunctional timing relay to
• Uniform design document the function that has been set
• Ideal for small distance between DIN rails and/or for low
mounting depth, e.g. in control boxes
■ Application
Timing relays are used in control, starting, and protective circuits
for all switching operations involving time delays. They
guarantee a high level of functionality and a high repeat
accuracy of timer settings.
■ Technical specifications
More information
Technical specifications, see Internal circuit diagrams, see CAx Download Manager
https://support.industry.siemens.com/cs/ww/en/ps/16356/td https://support.industry.siemens.com/my/ww/en/CAxOnline#CAxOnline
Operating Instructions, see FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/16356/faq
https://support.industry.siemens.com/cs/ww/en/view/11647144
Type 3RP2005,
3RP2025
Dimensions (W x H x D) mm 45 x 57 x 73
H
10
Connection type Screw terminals
A1/A2 A1/A2
>t
NSB0_00861a
>35 ms
NSB0_00862
NSB0_00858
A1/A2 A1/A2
NSB0_00859
B1/A2 B1/A2
15/18 15/18
15/16 15/18 15/18 15/16
t 15/16 15/16 t t
t t t
A B1) C D
3RP2005-.A, 3RP2025 3RP2005-.A 3RP2005-.A 3RP2005-.A
ON-delay OFF-delay with control signal ON-delay and OFF-delay Flashing, starting with interval
with control signal (t = ton = toff) (pulse/interval 1:1)
NSB0_00867
NSB0_00868
NSB0_00865
B1/A2 B1/A2 B1/A2
15/18
15/16 15/18 15/18 15/18
t 15/16 15/16 15/16
t t t
E F1) G H
3RP2005-.A 3RP2005-.A 3RP2005-.A 3RP2005-.A
Passing make contact Passing break contact with Pulse-forming with control signal Additive ON-delay with control signal
control signal (pulse generation at the output does
not depend on duration of energizing)
Legend
A ... H Identification letters for 3RP2005
Timing relay energized
Contact closed
Contact open
1) A new control signal at terminal B, after the operating time has started,
resets the operating time to zero (retriggerable).
10
A1/A2 A1/A2
A1/A2 A1/A2 > 35 ms > 35ms
15/18 B1/A2 B1/A2
15/18
NSB0_00871d
15/16 15/16 15/18
NSB0_00873a
15/18
NSB0_00872
t 15/16
NSB0_00874
25/28 15/16
25/26 21/24 25/28 t
t 21/22 25/26 21/24
t 21/22
A A! B1) B!1)
3RP2005-.B 3RP2005-.B 3RP2005-.B 3RP2005-.B
ON-delay ON-delay and instantaneous contact OFF-delay with control signal OFF-delay with control signal
and instantaneous contact
A1/A2 A1/A2
>t >t A1/A2 A1/A2
B1/A2 B1/A2 15/18 15/18
NSB0_00878
15/18 15/16
NSB0_00879
15/18 15/16
IC01_00739
15/16 NSB0_00877a
15/16 25/28 t t
25/28 t t 25/26 21/24
25/26 21/24 t t 21/22
t t 21/22
C C! D D!
3RP2005-.B 3RP2005-.B 3RP2005-.B 3RP2005-.B
ON-delay and OFF-delay ON-delay and OFF-delay Flashing, starting with interval Flashing, starting with interval
with control signal (t = ton = toff) with control signal and instantaneous (pulse/interval 1:1) (pulse/interval 1:1) and instantaneous
contact (t = ton = toff) contact
A1/A2 A1/A2
A1/A2 > 35ms >35ms
A1/A2
B1/A2 B1/A2
15/18 15/18
NSB0_00880
15/16 15/18
NSB0_00881
15/16 15/18
NSB0_00882
t 15/16
NSB0_00883
25/28 15/16
25/26 21/24 25/28 t
t 21/22 25/26 21/24
21/22
t
E E! F1) F!1)
3RP2005-.B 3RP2005-.B 3RP2005-.B 3RP2005-.B
Passing make contact Passing make contact and Passing break contact with control Passing break contact with control
10
instantaneous contact signal signal and instantaneous contact
15/18 17/18
15/18 15/18
NSB0_00884
15/16
NSB0_01381a
NSB0_00885
G G! H! *
3RP2005-.B 3RP2005-.B 3RP2005-.B 3RP2005-.B
Pulse-forming with control signal Pulse-forming with control signal Additive ON-delay with control signal Star-delta (wye-delta) function
(pulse generation at the output does and instantaneous contact (pulse and instantaneous contact
not depend on duration of energizing) generation at the output does not
depend on duration of energizing)
Legend
A ... H Identification letters for 3RP2005
! instantaneous contact
With LED and 0.05 ... 1 s 24/100 ... 127 24 3RP2025-1AQ30 3RP2025-2AQ30
1 CO contact1) 0.15 ... 3 s 24/200 ... 240 24 3RP2025-1AP30 3RP2025-2AP30
0.5 ... 10 s
1.5 ... 30 s
0.05 ... 1 min
5 ... 100 s
0.15 ... 3 min
0.5 ... 10 min
1.5 ... 30 min
0.05 ... 1 h
5 ... 100 min
0.15 ... 3 h
0.5 ... 10 h
1.5 ... 30 h
5 ... 100 h
2)
■ Accessories
Version Function Identifi Use Article No. Price PU PS* PG
cation per PU (UNIT,
letter SET, M)
10
• Passing break contact with F•
control signal and instantaneous
contact
• Pulse-forming with control signal G•
and instantaneous contact
• Additive ON-delay with control H•
signal and instantaneous
contact
• Star-delta (wye-delta) function *
Blank labels
Unit labeling plates1) For 3RP20
For SIRIUS devices
• 20 mm x 7 mm, titanium gray 3RT2900-1SB20 100 340 units 41B
IC01_00181
3RT2900-1SB20
1) PC labeling system for individual inscription
of unit labeling plates available from:
murrplastik Systemtechnik GmbH,
see page 16/18.
■ Overview
Multifunction
The functions of the 7PV1508-1A multifunctional timing relay can
be set by means of rotary switches. The identification letters A to
G are printed on the front alongside the rotary selector switch of
the unit. The related function can be found in the form of a bar
graph on the side of the device.
Enclosure version
All timing relays are suitable for snap-on mounting on TH 35
DIN rails according to IEC 60715. The enclosure complies with
DIN 43880, 1 MW.
17,5 67
90,5
67,5
45
Electronic timing relays for general use in control systems,
mechanical engineering and infrastructure with:
• 1 or 2 CO contacts
• Multifunction or monofunction NSB0_02042a
Diagrams
■ Benefits
• Wide voltage range 12 to 240 V AC/DC • High level of functionality and a high repeat accuracy of
• High switching capacity, e.g. AC-15 at 230 V, 3 A timer settings
• Combination voltage, e.g. 24 V AC/DC and 200 to 240 V AC • Integrated surge suppressor
• Changes to the time setting range during operation • Function charts printed on the side of the device for reliable
device adjustment
• Changes to the function in the de-energized state
■ Application
Timing relays are used in control, starting and protective circuits
for all switching operations involving time delays, e.g. in
functional buildings, airports, building industry, etc.
■ Technical specifications
More information
10
Technical specifications, see Operating Instructions and internal circuit diagrams, see
https://support.industry.siemens.com/cs/ww/en/ps/16358/td https://support.industry.siemens.com/cs/ww/en/view/35210295
TIA Selection Tool Cloud (TST Cloud), see
www.siemens.com/tstcloud/?node=SIRIUSRelais
Type 7PV15
Rated insulation voltage V AC 300
Pollution degree 2, overvoltage category III
Permissible ambient temperature
• During operation °C -25 ... +55
• During storage °C -40 ... +70
Operating range of excitation1) 0.85 ... 1.1 x Us
Rated operational current Ie
• AC-15 at 24 ... 240 V, 50 Hz A 3
• DC-13 at
- 24 V A 1
- 125 V A 0.2
Uninterrupted thermal current Ith A 5
Mechanical endurance Operating 1 x 107
cycles
Electrical endurance at Ie Operating 1 x 105
cycles
Connection type Screw terminals
A1/A2 250 ms
>35 ms
NSB0_00862
NSB0_00858
A1/A2 A1/A2
NSB0_00859
IC01_00551
B1/A2 A1/A2
15/18 15/18
15/16 15/18 15/18 15/16
t 15/16 15/16 t t
t t
A B1) -- C
7PV1508-1A, 7PV1511, 7PV1512, 7PV1508-1A, 7PV1538 7PV1540 7PV1508-1A
7PV1513, 7PV1518
ON-delay OFF-delay with control signal OFF-delay without control signal Flashing, starting with interval
(pulse/interval 1:1)
NSB0_00864
A1/A2 A1/A2
NSB0_00863
NSB0_00867
NSB0_00865
15/18 B1/A2 B1/A2
15/18
15/16 15/16 15/18 15/18
t 15/16 15/16
Dead time Pulse time t t
-- D E1) F
7PV1558 7PV1508-1A 7PV1508-1A 7PV1508-1A
Clock-pulse, starting with interval Passing make contact Passing break contact with control Pulse-forming with control signal
(dead time, pulse time, and time signal (pulse generation at the output does
setting ranges each separately not depend on duration of energizing)
adjustable)
A1/A2
t1 t2 t3
NSB0_00868
B1/A2
15/18
15/16
t
10
G
7PV1508-1A
Additive ON-delay with control signal
Legend
A ... G Identification letters for 7PV1508
Timing relay energized
Contact closed
Contact open
1) A new control signal at terminal B, after the operating time has started,
resets the operating time to zero (retriggerable).
Note:
With the 7PV1508-1A multifunctional timing relay the
identification letters A to G are printed on the front alongside the
rotary selector switch of the unit. The related function can be
found in the form of a bar graph on the side of the device.
A1/A2
A1/A2 > 35 ms A1/A2 A1/A2
15/18 B1/A2 15/18 15/18
NSB0_00871d
NSB0_00880
NSB0_00878
15/16 15/16 15/16
15/18
NSB0_00873a
15/16 25/28 25/28
25/28
25/26 25/28 25/26 25/26
t 25/26 t t t
t
A B1) C D
7PV1508-1B 7PV1508-1B 7PV1508-1B 7PV1508-1B
ON-delay OFF-delay with control signal Flashing, starting with interval Passing make contact
(pulse/interval 1:1)
A1/A2 A1/A2
> 35ms >t A1/A2
B1/A2 B1/A2
15/18
IC01_00552
15/18 15/18 15/16
NSB0_00884
IC01_00739
15/16 15/16
25/28
25/28 25/28 25/26
25/26 25/26 t 0,5 s
t t t
F H I
7PV1508-1B 7PV1508-1B 7PV1508-1B
Pulse-forming with control signal ON-delay and OFF-delay with Fixed pulse after ON-delay
(pulse generation at the output control signal
does not depend on duration
of energizing)
2 NO contacts
NSB_02044
A1/A2
15/18
25/28
t 0,05...1s
--
7PV1578
10
Star-delta (wye-delta) function2)
Legend
A ... D, F, H, I Identification letters for 7PV1508
Timing relay energized
Contact closed
Contact open
1) A new control signal at terminal B, after the operating time has started,
resets the operating time to zero (retriggerable).
2) With 7PV1578 the contacts 16 and 26 are not needed for the star-delta
(wye-delta) function.
Note:
With the 7PV1508-1B multifunctional timing relay the
identification letters A to D, F, H, I are printed on the front
alongside the rotary selector switch of the unit. The related
function can be found in the form of a bar graph on the side of
the device.
Version Time setting range t Rated control supply voltage Screw terminals PU PS* PG
adjustable by rotary Us (UNIT,
switch to SET, M)
50/60 Hz AC DC Article No. Price
V V per PU
7PV1508 timing relays, multifunction, 7 time setting ranges
The functions can be adjusted by means of rotary switches. The same potential must be applied to terminals A. and B.
With LED and 0.05 ... 1 s 12 ... 240 12 ... 240 7PV1508-1AW30 1 1 unit 41H
1 CO contact, 0.5 ... 10 s
7 functions 5 ... 100 s
With LED and 30 s ... 10 min 12 ... 240 12 ... 240 7PV1508-1BW30 1 1 unit 41H
2 CO contacts, 3 min ... 1 h
7 functions 30 min ... 10 h
5 ... 100 h
7PV151. timing relays, ON-delay, 1 time setting range
With LED and 0.05 ... 1 s 24/200 ... 240 24 7PV1511-1AP30 1 1 unit 41H
1 CO contact 0.5 ... 10 s 24/100 ... 127 24 7PV1512-1AQ30 1 1 unit 41H
24/200 ... 240 24 7PV1512-1AP30 1 1 unit 41H
5 … 100 s 24/100 ... 127 24 7PV1513-1AQ30 1 1 unit 41H
24/200 ... 240 24 7PV1513-1AP30 1 1 unit 41H
7PV1518 timing relays, ON-delay, 7 time setting ranges
With LED and 0.05 ... 1 s 12 ... 240 12 ... 240 7PV1518-1AW30 1 1 unit 41H
1 CO contact 0.5 ... 10 s
5 ... 100 s
30 s ... 10 min
3 min ... 1 h
30 min ... 10 h
5 ... 100 h
7PV1538 timing relays, OFF-delay, with control signal, 7 time setting ranges
With LED and 0.05 ... 1 s 12 ... 240 12 ... 240 7PV1538-1AW30 1 1 unit 41H
1 CO contact 0.5 ... 10 s
10
5 ... 100 s
30 s ... 10 min
3 min ... 1 h
30 min ... 10 h
5 ... 100 h
7PV1540 timing relays, OFF-delay, without control signal, 7 time setting ranges
With LED and 0.05 ... 1 s 12 ... 240 12 ... 240 7PV1540-1AW30 1 1 unit 41H
1 CO contact1) 0.15 ... 3 s
0.3 ... 6 s
0.5 ... 10 s
1.5 ... 30 s
3 ... 60 s
5 ... 100 s
7PV1558 timing relays, clock-pulse relay, 7 time setting ranges
With LED and 0.05 ... 1 s 12 ... 240 12 ... 240 7PV1558-1AW30 1 1 unit 41H
1 CO contact 0.5 ... 10 s
5 ... 100 s
30 s ... 10 min
3 min ... 1 h
30 min ... 10 h
5 ... 100 h
7PV1578 timing relays, star-delta (wye-delta) function, 7 time setting ranges
With LED and 0.05 ... 1 s 12 ... 240 12 ... 240 7PV1578-1BW30 1 1 unit 41H
2 NO contacts, 0.5 ... 10 s
dead interval 5 ... 100 s
0.05 ... 1 s adjustable 30 s ... 10 min
3 min ... 1 h
30 min ... 10 h
5 ... 100 h
1) Setting of output contacts in as-supplied state not defined (bistable relay).
Application of the control supply voltage once results in contact
changeover to the correct setting.
■ Overview
The 3RR2 current monitoring relays can be integrated directly in
the feeder by mounting on the 3RT2 contactor; separate wiring
of the main circuit is therefore superfluous. No separate
transformers are required.
For a line-oriented configuration or simultaneous use of an
overload relay, terminal supports for stand-alone installation are
available for separate DIN-rail mounting.
Versions
Basic versions
The basic versions with 2-phase apparent current monitoring,
a CO contact output and analog adjustability provide a high
level of monitoring reliability especially in the rated and overload
range.
SIRIUS 3RR2242, 3RR2142, 3RR2243 current monitoring relays
Standard versions
More information
The standard versions monitor the current in 3 phases with
Homepage, see www.siemens.com/sirius-monitoring-relays selectable active current monitoring. They have additional
Industry Mall, see www.siemens.com/product?3RR21 diagnostics options such as residual-current monitoring and
phase sequence monitoring, and they are also suitable for
monitoring motors below the rated torque. These devices have
an additional independent semiconductor output, an actual
value indicator, and are digitally adjustable.
Both versions are available optionally with screw or spring-
loaded terminals, in each case for sizes S00 and S0.
Video: SIRIUS 3RR2 current monitoring relays With variants of size S2 the main conducting paths always have
screw terminals; the control current side can have screw or
The SIRIUS 3RR2 current monitoring relays are suitable for load spring-loaded terminals.
monitoring of motors or other loads. In 2 or 3 phases they monitor
the rms value of AC currents for overshooting or undershooting Note:
of set threshold values. In addition to the features of the standard versions, the
Whereas apparent current monitoring is used above all in 3RR24 monitoring relays for mounting on 3RT2 contactors for
connection with the rated torque or in case of overload, the IO-Link also offer the possibility of transmitting the measured
active current monitoring option can be used to observe and values and diagnostics data to a controller via an IO-Link.
evaluate the load factor over a motor's entire torque range. Furthermore, the devices can be parameterized on the devices
themselves or via IO-Link.
For more information, see page 10/55 onwards.
10
3RR21 and 3RR22 overview table
• Screw terminals S00: 45 x 79 x 80, S00: 45 x 79 x 80, • Permit the mounting of slim-line and compact load
S0: 45 x 87 x 91, S0: 45 x 87 x 91, feeders in widths of 45 mm (S00 and S0) and 55 mm
D
W
S2: 55 x 99 x 112 S2: 55 x 99 x 112 (S2)
• Simplify configuration
• Spring-loaded S00: 45 x 90 x 80, S00: 45 x 90 x 80,
terminals S0: 45 x 109 x 92, S0: 45 x 109 x 92,
S2: 55 x 99 x 112 S2: 55 x 99 x 112
Current range S00: 1.6 ... 16 A S00: 1.6 ... 16 A • Is adapted to the other devices in the SIRIUS modular
S0: 4 ... 40 A S0: 4 ... 40 A system
S2: 8 ... 80 A S2: 8 ... 80 A • Just a single version per size with a wide setting range
enables easy configuration
Permissible ambient temperature
During operation -25 ... +60 °C -25 ... +60 °C • Suitable for applications in the control cabinet,
worldwide