Mitsubishi MELSEC FX PLC Catalogue

The document discusses Mitsubishi Electric programmable logic controllers, specifically models FX0S, FX0N, and FX2N. It shows diagrams of the controllers with their input and output terminals labeled. The controllers have options for 16, 32, or 48 input/output channels.

Uploaded by

rajabur688
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
57 views76 pages

Mitsubishi MELSEC FX PLC Catalogue

The document discusses Mitsubishi Electric programmable logic controllers, specifically models FX0S, FX0N, and FX2N. It shows diagrams of the controllers with their input and output terminals labeled. The controllers have options for 16, 32, or 48 input/output channels.

Uploaded by

rajabur688
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 76

MITSUBISHI ELECTRIC

Programmable
Logic
Controllers

40 X 90

IN 0
1
2
3
4
5
6
7 COM X0 X2 X4 X6 X10 X12 X14 X16
L N 24+ X1 X3 X5 X7 X11 X13 X15 X17

POWER 0 1 2 3 4 5 6 7
IN

MELSEC
10 11 12 13 14 15 16 17
POWER

RUN

BATT.V

PROG-E

FX0S,
0 1 2 3 4 5 6 7
OUT
FX 2N-16EX FX 2N-32MR 10 11 12 13 14 15 16 17 CPU-E

Y0 Y2 Y4 Y6 Y10 Y12 Y14 Y16


IN 0 COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y11 Y13 COM4 Y15 Y17
1

FX0N,
2
3
4
5
6
7

FX2N
87 X

MITSUBISHI
35

90

X26
X16 X20 X22 X24
X6 X10 X12 X14 X21 X23 X25 X27
S/S 0V X0 X2 X4 X7 X11 X13 X15 X17
L N 24V X1 X3 X5
26 27
20 21 22 23 24 25
0 1 2 3 4 5 6 7
MELSEC FX0N-24MR-ES
MITSUBISHI IN
10 11 12 13 14 15
16 17 POWER

RUN

BATT.V
PROG-E
26 27
3 4 5 6 7 20 21 22 23 24 25 CPU-E
0 1 2
OUT
FX2N -48MR 10 11 12 13 14 15
16 17

Y24 Y26 COM5


Y10 Y12 Y14 Y16 Y20 Y22 Y25 Y27
Y2 Y4 Y6 Y15 Y17 Y21 Y23
Y0 COM3 Y11 Y13 COM4
COM1 Y1 Y3 COM2 Y5 Y7

T X

X21 X23 X25 X27


X11 X13 X15 X17 X26
X1 X3 X5 X7 X16 X20 X22 X24
COM COM X6 X10 X12 X14
• X0 X2 X4
L N

7
IN 0 1 2 3 4 5 6

MITSUBISHI 0 1 2 3 4 5 6 7

S/S X1 X3 1 2 3 X74 5 6X117


0 X5 X13
POWER X0 X2 X4 X6 X10 X12
6 7
OUT 0 1 2 3 4 5
IN 0 1 2 3 4 5 6 7 10 1112 13
0 1 2 3 4 5 6 7

FX 0N -40ER
35
90

Y3 COM5 Y5 Y7
Y5 Y7 COM4 Y1
Y3 COM3
24V+ • COM0 COM1 COM2

OUT 0 1 2 3 4 5 6 7

0V Y0 Y1 Y2 Y3 Y4 Y6
24V COM0 COM1 COM2 COM3 COM4 Y5 Y7
X3 X5 X7
S/S X1
X2 X4 X6
L N X0
100-240VAC 7
IN 0 1 2 3 4 5 6

MITSUBISHI
POWER
RUN
PROG-E
CPU-E

FX0S-14MR-ES
OUT 0 1 2 3 4 5

Y2 Y4 •
0V Y0 Y1
COM2 Y3 Y5
24V COM0 COM1

Technical Catalogue

1998/99
MELSEC FX

New Items in this Catalogue

MELSEC FX0N
Integration of the new FX2N extension modules
and special function modules for the FX0N series

du cts
New Pro
MELSEC FX2N
The consistent advancement of the proven

1998 FX to the FX2N

Accessories
Simulation strip for the simulation of digital inputs,
Profibus plug

Programming
MX-Scada: process supervision software
ProfiMap: Profibus configuration software

Further Publications within the PLC Range

ME
LS
EC
AnA, AnN, AnU, QnA Series Technical Catalogue
N
An
A A
An Qn
An
U
Product catalogue for programmable logic controllers and
accessories for the MELSEC A and Q series (art no. 61747)
l
Technica QnAS, AnS Series Technical Catalogue
es
Catalogu
EC
LS
ME

S
An S
Qn
A
Product catalogue for programmable logic controllers and
accessories for the MELSEC AnS and QnAS series (art. no. 59085)

LS
EC
HMI Technical Catalogue
ME
C
MA
DU
GO
T Product catalogue for operator terminals, supervision software
and accessories (art. no. 68542)

DIN ISO 9001 /


EN 29001
Zertifikat: 09 100 4371

About this product catalogue


Texts, figures and diagrams shown in this product catalogue are intended exclusively for explanation and assistance in planning and ordering
the programmable logic controllers of the MELSEC FX0S, FX0N and FX2N series and the associated accessories. Only the manuals supplied
with the modules are relevant for installation, commissioning and handling of the controllers and the accessories. The information given in this
documentation must be read before installation and commissioning of the modules.
Should questions arise with regard to the planning of modules described in this product catalogue, do not hesitate to contact the german
branch of the MITSUBISHI ELECTRIC EUROPE B.V. in Ratingen or one of its distributors (see cover page).
No parts of this product catalogue may be duplicated, stored in an information system or transmitted without prior express written permission
from MITSUBISHI ELECTRIC EUROPE B.V..
© MITSUBISHI ELECTRIC EUROPE B.V. 12/1998 (2nd issue)

2 MITSUBISHI ELECTRIC
MELSEC FX
CONTENTS

FX FAMILY
SYSTEM DESCRIPTION FX
웇 Introduction of the FX family . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 BASICS
웇 Networks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

MELSEC FX0S
BASE UNITS
웇 Description of system and unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
웇 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

ACCESSORIES
웇 Simulation strip, simulation box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
웇 Program loader. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

TERMINALS AND DIMENSIONS


웇 Terminal assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
웇 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

MELSEC FX0N/FX2N
SYSTEM DESCRIPTION
웇 Base units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
웇 Extension and special function modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
웇 System specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

BASE UNITS
웇 Specifications FX0N. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
웇 Specifications FX2N. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

EXTENSION UNITS
웇 Compact extension units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
웇 Modular extension units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

SPECIAL FUNCTION UNITS


웇 Analog modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
웇 Counter and positioning module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
웇 Interface module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
웇 Communications modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

ACCESSORIES
웇 Memory cassettes and interface converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
웇 PROM adapter, simulation box and simulation strip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
웇 Batteries and connection cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

TERMINALS AND DIMENSIONS


웇 Terminal assignments of the base units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
웇 Terminal assignments of the extension units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
웇 Terminal assignments of the special function units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
웇 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66

PROGRAMMING
PROGRAMMING UNITS AND SOFTWARE
웇 Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
웇 Hand-held programming units, cables and EPROM writer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72

APPENDIX
웇 Order form . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
웇 Index. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75

MITSUBISHI ELECTRIC 3
MELSEC FX
SYSTEM DESCRIPTION The FX Family

The MELSEC FX Family

FX Description Special features:


The MELSEC FX family includes a very 앬 Expandable from 10 – 256 I/Os 앬 Worldwide standards
BASICS
comprehensive range of base and expan- 앬 Compact, robust design 앬 Quality products manufactured in
sion modules, enabling you to configure 앬 Extensive communications support facilities with ISO 9001 certified quality
a customised system tailored to your 앬 Simple installation management systems and subject to
precise requirements. special manufacturers’ standards
앬 Custom configuration for the needs of
Depending on your application and con- existing systems
trol needs you can choose from the small, 앬 Innovative, “future-proof” technology
attractively-priced, “stand-alone” MELSEC protects your investment
FX0S series, the expandable FX0N series or
the more powerful FX2N series.
The FX0N and FX2N series are both a good
choice for plant installations because MELSEC A / Q
their expansion options enable them to
grow with the needs of your application. MELSEC FX2N
Network integration is also supported,
making it possible for your FX controllers
to communicate with other PLCs, control-
lers and MMIs. The PLC systems can be
configured as local stations in MITSUBISHI
networks (MELSECNET/MINI), and as slave
stations in open networks (PROFIBUS/DP).
In addition to this, the controllers of the
MELSEC FX0N/FX2N series also support
integration in multidrop and peer-to-peer
network configurations.
All FX systems are members of the great
MELSEC family of PLCs, in which all sys- MELSEC MELSEC FX0N
tems are compatible with one another. FX0S
MELSEC AnS/QnAS

Expandability and power There are three series in the MELSEC FX cycle time of just 0,08 µs per logical in-
family, each of which is designed for a struction.
The MELSEC FX family is highly flexible,
different application profile: Thus the FX2N series gives you the most
enabling fast and efficient configuration
and programming for the application at powefull CPU for your apllication and com-
hand. 앬 The FX0S series bines all benefits of a compact PLC system
The MELSEC FX0S series is the inexpensive with the performance of a modular PLC
It is the ideal choice, no matter whether
entry to the MELSEC FX family. With its system.
you need to install a simple control appli-
small dimensions it is also an excellent
cation requiring up to 30 I/Os (FX0S) or a
alternative to relay/contactor control
demanding, complex system with up to
configurations.
256 I/O points (FX2N).
16.000

The capacity of the CPUs of the FX0N/FX2N 앬 The FX0N series


series can be expanded with memory
The CPUs of the FX0N series offer more
cassettes. Non-volatile memory cassettes
power than the FX0S series, plus modular
with a capacity of up to 16K program
expansion capabilities. You can choose
steps are available for reliable, long-term
from I/O expansion modules and special
256

storage of your PLC projects. In addition


function modules for a wide variety of
to the other advantages this enables you
1,6 – 3,5

applications.
2.000

to switch programs at very short notice,


0,08
1,6
128

simply by replacing a cassette.


앬 The FX2N series
800
30

The new FX2N series complements the FX0N FX2N


existing FX family and replaces the suc- FX0S

cessful FX series. It gives you the freedom No. of inputs/outputs Cycle time (µs)
of modular expandability, with a wide Program steps
selection of expansion modules and spe-
cial function modules. The FX2N is also one
of the fastest PLC systems available, with a

4 MITSUBISHI ELECTRIC
MELSEC FX
The FX Family SYSTEM DESCRIPTION

Features
The modular design of the FX0N/FX2N
series makes it extremely flexible, ena-
All modules are electrically isolated from
their environment with optocouplers for
FX
bling it to be used for a very broad range maximum reliability. BASICS
of applications.
You can configure tailor-made systems
by combining modules from a variety of Digital I/O modules
different categories (see figure). For a variety of signal levels
with relay or transistor
switches.
DIGITAL
INPUTS/OUTPUTS

COMMUNI- ANALOG
CATIONS
MODULES CPU INPUTS/
OUTPUTS

Communications modules
Interface modules with POSITIONING
RS-232/RS-422/RS-485 interfaces MODULES Analog I/O modules
for the connection of peripherals For processing current/voltage
and PLC–PLC links. Network signals and temperature
modules for Profibus, GSM and for
registration with a direct
the configuration of proprietary
connection option for Pt100
Mitsubishi networks resistance thermometers and
Positioning modules thermocouples.
High-speed counter modules with support
for the connection of incremental rotary
transducers and positioning modules for
servo and stepping motor drives.

Digital and special function modu- CPU type System restrictions


les – configuration FX0S Stand-alone PLC with 10 / 14 / 20 or 30 I/Os;
no special function modules
The options for using digital and special
function modules are dictated by CPU FX0N PLC with max.128 I/Os;
max.2 special function modules supported
used in the system.
FX2N PLC with max.256 I/Os;
When calculating the number of special max.8 special function modules
function modules you can use in a system
you must take both the number of digital
modules and the maximum number of
special function modules that can be used
into account.
The table on the right provides a simpli-
fied guide to the number of modules you
can use in each system type. More de-
tailed information and the basic principles
of system configuration can be found on
page 21 ff.

MITSUBISHI ELECTRIC 5
MELSEC FX
SYSTEM DESCRIPTION The FX Family

Handling

FX Installation
BASICS
Handling and installation of the modules
are very simple.
All modules are fitted with an integrated
DIN adapter for snap-on installation on
DIN rail systems.
If you wish, the modules can also be
installed normally on flat surfaces with
screw fastenings.
In the FX0N and FX2N series all connec-
tions between the CPU’s system bus and
the expansion and special function
modules are made with the standard flat
ribbon cable. No other internal system
wiring is required for connecting the CPU
and modules.

Wiring
All external wiring is connected to the
standard cable terminals to the screw
terminals on the modules. The entire
terminal block has a cover which provides
protection against short circuits and
inadvertent contact.

Programming
All CPUs have a standardised program-
ming interface for connection of a pro-
gramming unit or a personal computer.
Simple control tasks can be programmed
directly using hand-held programming
units or the control units of the FX-DU
series. In addition to this the CPUs can
also be programmed with the MELSEC
MEDOC plus software package, which
runs on a normal PC. This powerful pro-
gramming environment can be used to
create large application programs con- Multi-functional
forming to the IEC 1131.3 standard. interfaces

POWER

Graphic operator terminal Hand-held programming unit PC with programming and


process supervision software

6 MITSUBISHI ELECTRIC
MELSEC FX
The FX Family SYSTEM DESCRIPTION

Process visualisation FX
For more effective supervision of ma- BASICS
chines and processes you can configure a
process visualisation system as a hard-
ware or software solution with partial or
full graphical support. Process visualisa-
tion products available from Mitsubishi in-
clude a variety of different operator termi-
nals and the powerful MX-SCADA process
visualisation software package.

Peripherals
Separate interface modules enable the POWER

connection of output devices such as


printers and also a variety of input devices
such as barcode readers. Optional plug-in
interfaces support the connection of
additional programming or operator ter-
minals, as well as the realization of various
serial links.
A range of special communications mod-
ules are also available for integration of
your PLC systems in a variety of networks.

Base unit FX0N


FX0N-485ADP

MELSECNET
Profibus

FX2N- FX0N- FX0N-


FX2N- 16NT
232IF 32DP
Base unit FX2N 232IF

FX 2N -232IF
FX 2N -232IF
POWER
POWER
SD
SD
RD
RD

Barcode reader Printer


Personal computer

MITSUBISHI ELECTRIC 7
MELSEC FX
SYSTEM DESCRIPTION Networks

MELSEC Networks
FX TCP/IP ETHERNET MELSECNET/B facturers is also possible. Any twisted-pair
BASICS cabling can be used as the communica-
Ready for immediate operation with the A cost-effective alternative within the pro-
tions media.
worldwide standard TCP/IP protocol. A PC duction level. Enables implementation of
connected to the Ethernet has full access easily-manageable configurations for MELSEC I/O LINK as a tree structure.
to all PLCs in the MELSECNET, all the way complex applications by means of distrib-
down to the I/Os on the production level. uted intelligence.
MELSEC FX Peer-to-Peer
The PPN construction enables a network
MELSECNET/10 und -NET(II) MELSECNET/MINI-S3 for up to 8 FX2N and FX0N controllers
Low-cost cabling, brilliantly simple set-up MELSEC I/O-LINK as clients.
and maximum availability thanks to re- Enables decentralised configurations by The max. coverage is up to 500 m.
dundancy and Floating Master. The max. linking remote modules to the machine. A standard twisted-pair cable can be
coverage is up to 30 km. Integration of devices from other manu- used as the communications media.

COMMAND LEVEL
TCP/IP ETHERNET

TCP/IP ETHERNET

CONTROL LEVEL
MELSECNET/10 AnU/
AnS/QnAS AnA
MELSECNET(II)
MELSECNET/B
MELSECNET/10 MELSECNET/10
MELSECNET/B MELSECNET(II)
AnS/
AnS/ AnU/ QnAS
QnAS AnA

AnS/
AnU/ QnAS
AnA

PRODUCTION LEVEL
MELSECNET/MINI-S3 MELSEC I/O-LINK
MELSEC I/O-LINK
MELSEC FX PPN

MELSECNET/MINI-S3
M
~

MELSEC
FX-PPN M M

8 MITSUBISHI ELECTRIC
MELSEC FX
Networks SYSTEM DESCRIPTION

Open Networks
MAP 3.0 ETHERNET Profibus FMS Profibus DP FX
Interdepartmental data exchange be- BASICS
Communication between equipment Enables quick and simple connection of
tween the command and production from different manufacturers within a sin- sensors and actuators from different
levels using a non-proprietary protocol gle plant. Automatic data exchange with manufacturers to MELSEC PLCs, with data
with short throughput times. MELSEC networks. transfer rates of up to 12 Mbaud.

COMMAND LEVEL
MAP 3.0 ETHERNET

MAP 3.0 ETHERNET

CONTROL LEVEL
Profibus FMS
P R O F I
PROCESS FIELD BUS

AnU B U S

FX0N/FX2N AnS/QnAS

PRODUCTION LEVEL
Profibus DP
PROFIBUS DP

MITSUBISHI ELECTRIC

MAC 90

FX0N/FX2N

MITSUBISHI ELECTRIC 9
MELSEC FX0S
BASE UNITS Description of System

The MELSEC FX0S Series

FX Description System structure Equipment features


BASICS
앬 Small 앬 Base unit with full PLC functionality Base units are available in a number of
앬 Fast 앬 Integrated power supply unit versions with different power supply and
앬 Versatile 앬 CPU output type configurations.
앬 Maintenance-free EEPROM memory You can choose between units with 230 V
The MELSEC FX0S is the cost-effective en- 앬 Integrated digital inputs and outputs AC or 24 V DC power supplies and relay or
try to the MELSEC family. It combines all 앬 User-friendly programming systems, in- transistor outputs.
the advantages of a PLC system in a very cluding hand-held programming units, All the base unit versions have the same
compact package, providing a space- and IEC 1131.3-compatible programming basic CPU and performance specifications.
cost-saving alternative to relay/contactor software and MMIs
control systems. 앬 Accessories

High-speed inputs for fast counting


tasks with counting frequencies of
up to 7 kHz and interrupt process-
All units feature an analog ing capabilities.
potentiometer for setpoint The internal service power
value entry and an integrated supply unit for 24 V DC has a
RUN/STOP switch. capacity of 200 mA.

Square pulse output


Integrated pulse outputs for
frequencies from 10 to 2000 Hz for
controlling stepping motors and
outputting pulse-width
modulated signals.

Integrated serial
interface for direct
communication with
computers.

Your PLC programs are stored in a


maintenance-free EEPROM user
memory with a capacity of 800 pro-
Flexible installation with the gram steps and a backup battery to
integrated DIN rail adapter and protect against power failures.
screw fastening hose for mounting
on flat surfaces. Password access
protection facility for
effective protection of
your intellectual property.

10 MITSUBISHI ELECTRIC
MELSEC FX0S
Description of System BASE UNITS

Description of the Unit

FX
BASICS
Protective cover

Terminal cover

Fixing hole
Connection of the
power supply Terminals for
digital inputs
RUN/STOP switch LEDs for indicating
the input statuses
Analog potentiometer LEDs for indicating the
operating status
Connection for
programming units LEDs for indicating
the output statuses
Protective cover
Terminals for
digital outputs
Service voltage source

Reference Table for Model Designation Code

FX왏왏 – 14 M R E S UL

1 2 3 4 5a 5b 6

The code in detail:


FX왏왏 = PLC series 5a Power supply: 6 UL = UL certification
1 Designation of the PLC series E = 100/240 V AC
D = 24 V DC
2 Number of inputs/outputs e.g. 14 I/Os
5b Model variants:
3 Description of the unit type:
M = base unit S = Inputs selectable as sink
E = extension unit or source type
EX = modular input extension Relay outputs
EY = modular output extension SS = Inputs selectable as sink
4 Description of the output type: or source type
R = relay Transistor outputs
T = transistor source type

MITSUBISHI ELECTRIC 11
MELSEC FX0S
BASE UNITS Specifications

General Specifications

FX General Specifications Data


Ambient temperature 0 – 55 °C
BASICS
Operating temperature 0 – 55 °C
Storage temperature -20 – +70 °C
Primary power supply 24 V DC,200 mA; ripple ratio at maximum load:≤ ±5 %
Protection IP 20
Noise durability 1000 Vpp with noise generator;1 µs at 30 – 100 Hz
Dielectric withstand voltage 1500 V AC,1 min.(500 V AC for direct voltage modules)
Ambient relative humidity 35 – 85 % (non-condensing)
Shock resistance 10 G (3 times each in 3 directions)
Vibration resistance 2 G:resistance to vibrations from 10 – 55 Hz for 2 hours along all 3 axes;0.5 G for DIN rail mounting
Insulation resistance 500 V DC,5 MΩ
Ground Class 3
Fuse 3A
Environment Avoid environments containing corrosive gases,install in a dust-free location.
Certifications UL / CSA / CE / DNV / RINA

Specifications of Base Units


FX0S-10 FX0S-10 FX0S-10 FX0S-14 FX0S-14 FX0S-14
Specifications
MR-DS MR-ES/UL MT-DSS MR-DS MR-ES/UL MT-DSS
Elektrical data
Max. number inputs/outputs 10 10 10 14 14 14
AC range (+10%, -15%) — 100–240 V AC — — 100–240 V AC —
Power
supply Frequency at AC Hz — 50/60 (±10%) — — 50/60 (±10%) —
DC range (+10%, -15%) 24 V DC — 24 V DC 24 V DC — 24 V DC
Max. input apparent power 4W 30VA 4W 5W 30 VA 5W
Inrush 100 V AC — 15 A / 2 ms — — 15 A / 2 ms —
current 200 V AC — 25 A / 2 ms — — 25 A / 2 ms —
at ON
24 V DC 60 A / 1.5 ms — 60 A / 1.5 ms 60 A / 1.5 ms — 60 A / 1.5 ms
Allowable momentary power failure time ms 5 10 5 5 10 5
External current supply (24 V DC) mA — 200 — — 200 —
Inputs
Integrated inputs 6 6 6 8 8 8
Min. current for logical 1 mA 4.5 4.5 4.5 4.5 4.5 4.5
Max. current for logical 0 mA 1.5 1.5 1.5 1.5 1.5 1.5
Response time ms For all units of the MELSEC FX0S series values:10 ms (at time of shipping),adjustable from 0 to 15 ms in steps of 1 ms.
Outputs
Integrated outputs 4 4 4 6 6 6
Output Art Relay Relay Transistor Relay Relay Transistor
Switching voltage (max.) V Generally for relay version:< 264 V AC,< 30 V DC;for transistor version:5 – 30 V DC
Max. output - per output A 2.5 2.5 0.5 2.5 2.5 0.5
current - per group* A — — 0.8 8 8 0.8
Max.switching - inductive load 80 VA 80VA 12W 80VA 80 VA 12 W
current - lamp load W 100 100 1.5 100 100 1.5
Response time ms 10 10 0.2 10 10 0.2
Life of contacts (switching times) For all base units of the MELSEC FX0S series values:3000000 at 20 VA;1000000 at 35 VA;200000 at 80 VA
Mechanical data
Weight kg 0.3 0.45 0.3 0.3 0.45 0.3
Dimensions (W x H x D) mm 60 x 90 x 47 60 x 90 x 75 60 x 90 x 47 60 x 90 x 47 60 x 90 x 75 60 x 90 x 47

Order information Art. no. 55774 55773 55775 55777 55776 55778

* The limitation applies only per reference terminal for each group,4 and 8 outputs for relays and 2 and 4 outputs for transistors.Please observe the terminal assignments for the group identification.

12 MITSUBISHI ELECTRIC
MELSEC FX0S
Specifications BASE UNITS

Programming Specifications
System data
Program data
FX
BASICS
Program memory 800 steps EEPROM (internal)
Program language Stepladder instructions,instruction list
Program execution Periodical execution of the stored program
Program protection Password protection with 3 protection levels
Number of instructions 20 sequence instructions,2 step ladder instructions,35 applied instructions
Cycle period 1.6 – 3.5 µs/log.instruction
Operands
Internal relays 512,16 buffered
Special relays 56
Step relays 64
Timers 56 (100 ms),with 24 to be switched to 10 ms
External setpoint entry via potentiometer 1
Counter 16 inputs,16 Bit
High speed counter inputs 4 counter inputs,32 Bit
Data register 32,16 Bit
Filer register —
Index register 2,16 Bit
Special register 27,16 Bit
Pointer 64
Nesting operands 8
Interrupt inputs 4
Constants 16 / 32 Bit

Specifications of Base Units


FX0S-20 FX0S-20 FX0S-20 FX0S-30 FX0S-30 FX0S-30
MR-DS MR-ES/UL MT-DSS MR-DS MR-ES/UL MT-DSS

20 20 20 30 30 30
— 100–240 V AC — — 100–240 V AC —
— 50/60 (±10%) — — 50/60 (±10%) —
24 V DC — 24 V DC 24 V DC — 24 V DC
6W 33VA 6W 8W 35VA 8W
— 15 A / 2 ms — — 15 A / 2 ms —
— 25 A / 2 ms — — 25 A / 2 ms —
60 A / 1.5 ms — 60 A / 1.5 ms 60 A / 1.5 ms — 60 A / 1.5 ms
5 10 5 5 10 5
— 200 — — 200 —

12 12 12 16 16 16
4.5 4.5 4.5 4.5 4.5 4.5
1.5 1.5 1.5 1.5 1.5 1.5
For all units of the MELSEC FX0S series values:10 ms (at time of shipping),adjustable from 0 to 15 ms in steps of 1 ms.

8 8 8 14 14 14
Relay Relay Transistor Relay Relay Transistor
Generally for relay version:< 264 V AC,< 30 V DC;for transistor version:5 – 30 V DC
2.5 2.5 0.5 2.5 2.5 0.5
8 8 0.8 8 8 0.8
80 VA 80VA 12W 80VA 80VA 12W
100 100 1.5 100 100 1.5
10 10 0.2 10 10 0.2
For all base units of the MELSEC FX0S series values:3000000 at 20 VA;1000000 at 35 VA;200000 at 80 VA

0.45 0.5 0.45 0.45 0.5 0.4


75 x 90 x 47 75 x 90 x 75 75 x 90 x 47 105 x 90 x 47 105 x 90 x 75 105 x 90 x 47

55787 55779 55789 55791 55790 55792

MITSUBISHI ELECTRIC 13
MELSEC FX0S
ACCESSORIES Simulation Strip and Simulation Box

왎 Simulation Strip: Input-SIM: FX0S/FX0N

The simulation strip has 8 switches for The simulation strip can be expanded
FX simulating digital inputs. with another strip for further inputs.
BASICS
The strip is directly mounted to the termi-
nals of the unit and fixed with screws to
the terminal block.
24V 0V
24V 0V
Input-SIM: FXOS/FXON
A cable is provided for connecting the
1 3 5 7
strip to the power supply.

0 2 4 6
- X07
X00 Specifications Input-SIM: FX0S/FX0N
Switches 8
Dimensions(WxHxD) mm 30 x 50 x 15

Order information Art. no. 65081

왎 Simulation Box

The simulation box has 12 switches for


simulating digital inputs.
It can be used on all controllers of the
MELSEC FX familiy.

Specifications Switch Box


Switches 12
Dimensions(WxHxD) mm 50 x 100 x 25

Order information Art. no. 3386

14 MITSUBISHI ELECTRIC
MELSEC FX0S
Program Loader ACCESSORIES

왎 Program Loader FX0-10LDR for FX0S in Combination with FX Memory Cassettes

The FX0-10LDR program loader is con-


nected directly to the PLC. It is used for
Otherwise, the program is written into the
EEPROM of the loader.
FX
BASICS
transferring programs between the inte- Moreover, the program can be transferred
grated EEPROM of FX0S units and the from the memory of the controller to
memory cassette which is used in the a memory cartridge inserted in the
FX0-10LDR. FX0-10LDR.
The FX0-10LDR can be used both with the
memory cassette and the EEPROM mem-
ory of the controller.
The program is transferred to the memory
set when a memory cassette is inserted.

Specifications FX0-10LDR
Environmental specifications Conforms to FX0 base units
Power supply 5 V DC ±5 % (from base unit)
Current consumption mA 180
Weight kg 0.08
Dimensions (W x H x D) mm 80 x 85 x 28

Order information Art. no. 36644

MITSUBISHI ELECTRIC 15
MELSEC FX0S
TERMINALS + DIMENSIONS Terminal Assignment

Terminal Assignment of Base Units

FX
BASICS
FX0S-10MT-DSS S/S X1 X3 X5 FX0S-14MT-DSS S/S X1 X3 X5 X7
+ - X0 X2 X4 + - X0 X2 X4 X6

FX0S-10MR-DS S/S X1 X3 X5 FX0S-14MR-DS S/S X1 X3 X5 X7


+ - X0 X2 X4 + - X0 X2 X4 X6

FX0S-10MR-ES/UL S/S X1 X3 X5 FX0S-14MR-ES/UL S/S X1 X3 X5 X7


L N X0 X2 X4 L N X0 X2 X4 X6

S/S X1 X3 X5
+ - X0 X2 X4 + -
24V DC 24V DC

FX0S-10MT-DSS FX0S-14MR-DS

0V Y0 Y1 Y2 Y3
24V +V0 +V1 +V2 +V3

FX0S-10MR-ES/UL
0V Y0 Y1 Y2 Y3 FX0S-14MR-ES/UL 0V Y0 Y1 Y2 Y4
24V COM0 COM1 COM2 COM3 24V COM0 COM1 COM2 Y3 Y5

FX0S-10MR-DS
Y0 Y1 Y2 Y3 FX0S-14MR-DS Y0 Y1 Y2 Y4
COM0 COM1 COM2 COM3 COM0 COM1 COM2 Y3 Y5

FX0S-10MT-DSS
Y0 Y1 Y2 Y3 FX0S-14MT-DSS Y0 Y1 Y2 Y4
+V0 +V1 +V2 +V3 +V0 +V1 +V2 Y3 Y5

FX0S-20MT-DSS S/S X1 X3 X5 X7 X11 X13 FX0S-30MT-DSS S/S S/S X1 X3 X5 X7 X11 X13 X15 X17
+ - X0 X2 X4 X6 X10 X12 + - X0 X2 X4 X6 X10 X12 X14 X16

FX0S-20MR-DS S/S X1 X3 X5 X7 X11 X13 FX0S-30MR-DS S/S S/S X1 X3 X5 X7 X11 X13 X15 X17
+ - X0 X2 X4 X6 X10 X12 + - X0 X2 X4 X6 X10 X12 X14 X16

FX0S-20MR-ES/UL S/S X1 X3 X5 X7 X11 X13 FX0S-30MR-ES/UL S/S S/S X1 X3 X5 X7 X11 X13 X15 X17
L N X0 X2 X4 X6 X10 X12 L N X0 X2 X4 X6 X10 X12 X14 X16

S/S X1 X3 X5 X7 X11 X13


+ - X0 X2 X4 X6 X10 X12 S/S S/S X1 X3 X5 X7 X11 X13 X15 X17
24V DC L N X0 X2 X4 X6 X10 X12 X14 X16
IN 0 1 2 3 4 5 6 7 10 11 12 13
IN 0 1 2 3 4 5 6 7 10 11 1213 14 15 16 17

FX -20MR-DS
0S
FX0S-30MR-ES
OUT 0 1 2 3 4 5 6 7
OUT 0 1 2 3 4 5 6 7 10 11 1213 14 15
0V Y0 Y1 Y2 Y3 Y4 Y6
24V COM0 COM1 COM2 COM3 COM4 Y5 Y7 0V Y0 Y2 Y4 Y6 Y10 Y12 Y14
24V COM0 Y1 COM1 Y3 Y5 COM2 Y7 Y11 COM3 Y13 Y15

FX0S-20MR-ES/UL
0V Y0 Y1 Y2 Y3 Y4 Y6 0V Y0 Y2 Y4 Y6 Y10 Y12 Y14
FX0S-30MR-ES/UL
24V COM0 COM1 COM2 COM3 COM4 Y5 Y7 24V COM0 Y1 COM1 Y3 Y5 COM2 Y7 Y11 COM3 Y13 Y15

FX0S-20MR-DS
Y0 Y1 Y2 Y3 Y4 Y6 Y0 Y2 Y4 Y6 Y10 Y12 Y14
FX0S-30MR-DS
COM0 COM1 COM2 COM3 COM4 Y5 Y7 COM0 Y1 COM1 Y3 Y5 COM2 Y7 Y11 COM3 Y13 Y15

FX0S-20MT-DSS
Y0 Y1 Y2 Y3 Y4 Y6 Y0 Y2 Y4 Y6 Y10 Y12 Y14
FX0S-30MT-DSS
+V0 +V1 +V2 +V3 +V4 Y5 Y7 +V0 Y1 +V1 Y3 Y5 +V2 Y7 Y11 +V3 Y13 Y15

16 MITSUBISHI ELECTRIC
MELSEC FX0S
Dimensions TERMINALS + DIMENSIONS

Dimensions of Base Units

FX
BASICS

ø4,5 X T
Type X (in mm) T (in mm)
FX0S-10MR-ES/UL 60 75
FX0S-10MR-DS 60 47
S/S X1 X3 X5 X7 X11 X13
FX0S-10MT-DSS 60 47
X0 X2 X4 X6 X10 X12

IN 0 1 2 3 4 5 6 7 10 1112 13 FX0S-14MR-ES/UL 60 75
FX0S-14MR-DS 60 47
105
35
98
90

FX0S-14MT-DSS 60 47
OUT 0 1 2 3 4 5 6 7

0V Y0 Y1 Y2 Y3 Y4 Y6
FX0S-20MR-ES/UL 75 75
24V COM0 COM1 COM2 COM3 COM4 Y5 Y7

FX0S-20MR-DS 75 47
FX0S-20MT-DSS 75 47
FX0S-30MR-ES/UL 105 75
FX0S-30MR-DS 105 47
FX0S-30MT-DSS 105 47

MITSUBISHI ELECTRIC 17
MELSEC FX0N/FX2N
SYSTEM DESCRIPTION FX0N Series

The MELSEC FX0N Series


Description System structure Equipment features
Small-scale PLC offering excellent value for 앬 Base unit with full PLC functionality Base units are available in a number of
money. 앬 Integrated power supply unit versions with different power supply
앬 Small 앬 CPU and output type configurations.
앬 Fast 앬 Maintenance-free EEPROM memory You can choose between units with
앬 Universal 앬 Integrated digital inputs and outputs 230 V AC or 24 V DC power supplies
앬 Modular expansion capability 앬 Expansion units for adapting the control- and relay or transistor outputs.
ler system to the required I/O ranges and All the base unit versions have the
The ability to combine the compact base functionality same basic CPU and performance
units with small, modular expansion units 앬 Configurable as a slave station in peer-to- specifications.
and compact I/O expansion units makes peer and 1:n networks (version 2.00 and
the FX0N enormously flexible, giving you a above)
highly economical combination of the cost 앬 User-friendly programming systems,
benefits of compact systems with the including hand-held programming units,
versatile expansion capabilities of modular IEC 1131.3-compatible programming
systems. software and MMIs
앬 Accessories

High-speed inputs for fast


counting tasks with counting
frequencies of up to 5 kHz and
interrupt processing Integrated RUN/STOP switch and two
capabilities. analog potentiometers for setpoint
value entry.

The base units can be expanded


for up to 128 I/Os with both
6 3
5 2

7
1

modular and compact


13
0

15 12
IN

14 11
10

The base units have integrated, expansion units.


15
X
13
X

maintenance-free EEPROM
11
X
7
X

3
5
X

user memory for up to 2000


2

7
1

6
3
X

5
T
U

4
O

11
SU X1

10
SH

PLC program steps with a


IT /S

S
M S

11
0
BI

7 1
-E

Y
Y Y
R

M 6
4M
N R

O Y
U E
R W

4
-2
O

4 5

backup battery to protect


U E

Y Y
P

CP OG

C
N
PR

M 3
FX

O Y
3
M 2
O Y

memory contents against power


2
M 1
O Y

C
1
M Y0
C
0
O

failures. You can also configure


C
V V
24 O

password protection to prevent


unauthorised access to your
programs.

Integrated pulse outputs


for frequencies from 10 to
2000Hz for controlling
stepping motors and
outputting pulse-width
modulated signals.
External EPROM or EEPROM
memory cassettes for PLC program
storage. These memory cassettes
are also available in versions with
a real-time clock.

18 MITSUBISHI ELECTRIC
MELSEC FX0N/FX2N
FX2N Series SYSTEM DESCRIPTION

The MELSEC FX2N Series


Description System structure Equipment features
The MELSEC FX2N series has the most 앬 Base unit with full PLC functionality A basic MELSEC FX2N PLC system consists
powerful CPUs in the MELSEC FX family. 앬 Integrated power supply unit of a stand-alone base unit. Just like the
It combines the advantages of a compact 앬 CPU modules in the other FX series these base
PLC with the performance boost of 앬 Integrated digital inputs and outputs units contain all the PLC components,
modular PLC systems: including the CPU, memory and the I/O
앬 Supplementary add-in function boards
앬 One of the fastest PLC systems avail- control circuitry.
for adapting the controller system to
able, with a program cycle period of the required I/O ranges and functio- All the base unit versions in the series
just 0.08 µs per logical instruction nality have the same basic CPU and perform-
앬 Powerful basic instruction set with an 앬 Integration as a master or slave station ance specifications.
additional 125 dedicated instructions in peer-to-peer networks and as a A total of 20 different base units are avail-
for fast, efficient programming of slave station in 1:n networks able, with between 16 and 128 I/Os in
complex tasks their standard configuration. Versions are
앬 Efficient, powerful user-friendly pro-
앬 Simple handling gramming with hand-held program- available with 230 V AC power supplies
앬 Integrated real-time clock ming units, MMIs and IEC 1131.3- (24 V DC available from Summer 1998)
앬 Integrated PID controller with auto- compatible programming software and relay or transistor outputs. The digital
tuning facility 앬 Accessories inputs are powered by the integrated
앬 Floating-point math, square root power supply unit. Removable terminal
function blocks make reconfiguration for new tasks
very quick and easy.
앬 Big memory capacity for up to 16000
PLC program steps A range of powerful expansion and spe-
cial function modules enable you to con-
figure your setup flexibly to provide the
precise functionality and I/O specifica-
tions required by your application.
You can add I/Os to the base units by in-
stalling modular expansion units with 8 or
16 additional I/Os each. You can also add
a range of compact expansion units and
special function modules – for example for
processing analog signals, for positioning
tasks and to provide additional interfaces.
Integrated high-speed counter inputs for
processing fast input signals. For example,
you can configure two 60 kHz counters RAM/EEPROM memory for up to
or four 10 kHz counters. 16000 PLC program steps gives
Interrupt processing is also handled you plenty of reserve, even for big,
via the inputs. complex applications.

The base units can be expanded


to provide configurations with
Add-in function boards can be in- up to 256 inputs and outputs
stalled in the PLC to provide a second with modular and compact
ER
W
PO

expansion units.
N
U

6
PR T.V
R

X1
T

U E
BA
16 7

RS-485 / RS-422 / RS-232 communi-


CP G

4
17
15 6

X1
14 5

2
13 4

X1
12 3
11 2

0
X1
10 1

cations interface for programming or


0

16 7

X6
17
15 6

IN
14 5

X4
13 4
12 3
11 2

X2
I

network configurations.
7
SH

6
10 1

Y1 Y1
0

X0
BI

T 4 5
OU Y1 Y1
SU

M
CO M4
CO
IT
M

3
R

2
Y1 Y1

An add-in function board with 8 analog


2M

0 1
Y1 Y1
-3
N

M3
2
FX

CO

potentiometers is also available. Y4


CO
M2
Y
Y5
6 Y7

Y2 Y3
YO Y1

CO
M1
Integrated real-time
clock with year, month
and time

Integrated serial interface for


direct communication with
computers

Integrated pulse outputs for frequencies


from 10 to 20000 Hz with deceleration
and acceleration ramps for controlling
An integrated RUN/STOP switch stepping motors and outputting
is available pulse-width modulated signals.

MITSUBISHI ELECTRIC 19
MELSEC FX0N/FX2N
SYSTEM DESCRIPTION Operator Controls

Description of Units

왎 FX0N series
Protective cover
LEDs for indicating
Connection of the the input statuses
power supply
Terminals for
Fixing hole digital inputs
Slot for memory Extension bus
cassettes
Analog potentiometer
Communications bus
RUN/STOP switch
LEDs for indicating the
operating status Connection for
programming units
Terminals for
service voltage source Protective cover
Terminals for LEDs for indicating
digital outputs the output statuses
Finger protection

Housing cover

Protective cover

왎 FX2N series

Connection of the Slot for memory


power supply cassettes
Detachable terminal strip
Fixing hole for digital inputs
LEDs for indicating
the input statuses
Extension connector
for adapter units LEDs for indicating the
operating status

Backup battery Connection for extensions

Connection for Protective cover for the


programming units extension bus

RUN/STOP switch LEDs for indicating


the output statuses
Detachable terminal strip
for digital outputs Protective cover

Housing cover

20 MITSUBISHI ELECTRIC
MELSEC FX0N/FX2N
Combination Options SYSTEM DESCRIPTION

Combining Units from Different Series


The I/O expansion modules and special A special conversion adapter is available The tables and figures below show the re-
function modules from the two series can (designation: FX2N-CNV-IF) for connecting strictions and other special requirements
be combined at will, subject to the restric- modules from the old FX series to the base that apply for combined use of modules
tions imposed by the differences between units of the FX2N series. from different systems.
the systems.
For example, you can use all the modules
for the FX0N series in combination with a
base unit from the FX2N series. Combined Series FX0N FX2N
use of modules from both series is also All special functions modules are applicable with
possible. Restrictions CPU version 2.00 or higher —

Special Modules FX0N-485ADP and FX0N-232ADP connect to the


requirements — left of the CPU and require function board FX2N-CNV-BD
for connection to the FX2N.

Modular Compact Special function Special function


Base units expansions expansions modules modules

FX0N FX0N FX0N FX0N FX2N


-24MR -8EX -40ER -32NT -4AD

FX2N FX2N FX2N FX0N FX0N


-32MR -16EX -32ET -3A -32NT

❊ ❊
FX2N FX2N
-1HC -1PG

❊ Can also be used with MELSEC FX0N and CPU version


2.00 or higher

CPU version 2.0


All base units of the FX0N series are now Version 1.30 Version 2.00 Remark
shipped with the 2.0 version of the CPU.
Up to no.78쏔쏔쏔쏔 From no.78쏔쏔쏔쏔 For all FX0N base units except
If you already have an FX0N base unit you FX0N-60MR-DS
can check the CPU version by comparing Up to no.79쏔쏔쏔쏔 From no.7Xllll For FX0N-60MR-DS only
the serial number to the entries in the
table on the right.

MITSUBISHI ELECTRIC 21
MELSEC FX0N/FX2N
SYSTEM DESCRIPTION Extension and Special Function Modules

Special Function Modules MELSEC FX0N/FX2N þ FX0N þ FX2N

FX0N -32NT-DP

POWER DC RUN

RDA RDB SDA SDB SG


BF DIA

Left-side Right-side Right-side Installation in


installation installation installation base unit

In general FX0N series configuration notes FX2N series configuration notes


Additional special function modules are The configuration specifications for the The configuration specifications for
available that make it possible to extend FX0N series permit connection of the follow- the FX2N series permit connection of
the capacity of the basic and extension ing combinations of expansion units to the the following combinations of units:
units of your PLC system. base units: 앬 A maximum of 8 special function
There are three basic categories of special 앬 a maximum of 2 special function modules or
function modules: modules 앬 Digital expansion modules with up
앬 Modules that occupy digital I/Os (con- or to 256 I/Os
nected on the right hand side of the 앬 digital expansion modules with up to Please note that it is important to cal-
controller unit). These are the digital 32 inputs and outputs (4 x 8 I/Os or culate the connected load to ensure
compact and modular extension units 2 x 16 I/Os) or that the internal 5 V bus has adequate
as well as the special function modules. 앬 one special function module and one capacity for the installed modules.
앬 Modules of the FX0N series that do not digital expansion module with up to When using special function modules
occupy any digital I/Os (connected on 16 inputs and outputs (2 x 8 I/Os or you must also check the 24 V power
the left hand side of the controller unit). 1 x 16 I/Os) supply load – the necessary 24 V
These are the FX0N-232ADP and the The same configuration specifications apply power can be drawn from the internal
FX0N-485ADP. for the connection of compact expansion service power supply, but it may be
앬 Internal adapter boards for the FX2N modules. necessary to complement this with an
series. These expansion units are in- Provided you observe these rules the sys- external power supply in some con-
stalled directly in the controller and do tem’s power supply will also be adequate to figurations.
not occupy any digital I/Os. provide the 24 V DC input required by the You can calculate the precise power
FX0N-232ADP communications module. load with the values provided in the
Similarly, the power supply for MMIs such table on the next page.
as the FX-DU control panels and MAC
operator terminals is provided via the
system’s 5 V bus.

22 MITSUBISHI ELECTRIC
MELSEC FX0N/FX2N
Power Consumption SYSTEM DESCRIPTION

Calculation of the Power Consumption ¨ FX0N þ FX2N

The power consumption figures on the Max. residual current values (in mA) for FX2N-16M첸-E첸첸 through FX2N-32M첸-E첸첸,
5 V DC bus for the special function FX2N-32E첸-E첸첸 for the permissible configuration
modules are shown in the specifications
24 25
tables on the following pages.
Number of 16 100 50 0
The maximum permissible currents on additional
the 5 V DC bus are shown in the table outputs 8 175 125 75 25
below. 0 250 200 150 100 50
0 8 16 24 32
Module Max. current on 5 V bus Number of additional inputs
FX2N-첸첸M첸-ES(ESS) 290 mA
FX2N-첸첸E첸-ES(ESS) 690 mA Max. residual current values (in mA) for FX2N-48M첸-E첸첸 through FX2N-128M첸-E첸첸,
FX2N-48E첸-E첸첸 for the permissible configuration
48 10
The residual currents for the 24 V DC serv-
ice voltage at different input/output con- 40 85 35
figurations are shown in the tables Number of 32 160 110 60 10
on the right. additional
outputs 24 235 185 135 85 35
Special function modules have to be sup-
16 310 260 210 160 110 60 10
plied external, if the residual current for
the service voltage is not satisfying. 8 385 335 285 235 185 135 85 35
A maximum of 256 I/Os are possible. 0 460 410 360 310 260 210 160 110 60
0 8 16 24 32 40 48 56 64
Number of additional inputs

Sample calculations ¨ FX0N þ FX2N


The table below and on the right show 24 V DC calculation 5 V DC calculation
different examples for sample power Module No.
Current / module Calculation Current / module Total current
calculation for a PLC system.
FX2N-80MR-ES 1 460 mA +460 mA +290 mA +290 mA
The current values for the special function
modules can be found in the specifica-
FX2N-4AD 3 50 mA -150 mA 30 mA -90 mA
tions on the following pages.
Comparison with the current value tables FX2N-4DA 2 200 mA -400 mA 30 mA -60 mA
show that the calculated figures for the FX2N-232IF 1 80 mA -80 mA 40 mA -40 mA
5 V bus lie within the allowable ranges.
-170 mA !!! 290 - 190 mA
In the example below all units can be
supplied sufficiently with the internal Result: 100 mA (OK !)

24 V power supply. An external 24 V power supply has to


be added In the example above.

Number of I/Os 24 V DC calculation 5 V DC calculation


Module No.
햲 햳
X Y X/Y Total Total current Current / module Total current
FX2N-48MR-ES/UL 1 24 24 — 290 mA +290 mA
FX2N-16EYR-ES/UL X=8
1 — 16 — — 0 mA
Y = 24 +185 mA
FX2N-8EX-ES/UL 1 8 — — ➞ — 0 mA
FX2N-8EYR-ES/UL 1 — 8 — — 0 mA
FX0N-3A 1 — — 8 -90 mA 30 mA -30 mA
+95 mA (OK!) +260 mA (OK!)
FX2N-32ER-ES/UL 1 16 16 — 690 mA +690 mA
X = 16 +150 mA
FX2N-16EX-ES/UL 1 16 — — — 0 mA
Y=0
FX2N-4AD 1 — — 8 ➞ 30 mA 50 mA -30 mA
FX2N-1HC 1 — — 8 0 mA 40 mA -90 mA
Result: 64 + 64 + 24 = 152 ! (< 256) OK! +120 mA (OK!) +570 mA (OK!)
햲 햳
Total no. of I/Os which are connected to a base unit to caculate the max. residual current values (see tables) see tables above (max. residual current values)

MITSUBISHI ELECTRIC 23
MELSEC FX0N/FX2N
SYSTEM DESCRIPTION Possible Configurations

Configuration Example FX0N

IN

The adressing of the special function Configuration


FX0N FX0N FX0N FX0N FX0N
Total
modules is independent of the address- -24MR-ES -8EX -8EYR -40ER-ES -3A
ing of the digital inputs/outputs. Inputs X 14 8 — 24 — 46
An example of adressing is shown in the Number OutputsY 10 — 8 16 — 34
table on the right. Special function modules — — — — 8 8
Inputs X 0 – 15 20 – 27 — 30 – 57 —
Adresses OutputsY 0 – 11 — 20 – 27 30 – 47 —
Special function modules No.0
Σ 88

Configuration Example FX2N

OUT

FX 0N -32NT-DP

POWER DC RUN

BF DIA

FX 2N-4DA
I+

OUT
D/A

The adressing of the special function Configuration


FX2N FX2N FX0N FX2N FX0N
Total
modules is independent of the address- -32MR-ES -16EYR -32NT/DP -32ER-ES -4DA
ing of the digital inputs/outputs. Inputs X 16 — — 16 — 32
An example of adressing is shown in the Number OutputsY 16 16 — 16 — 48
table on the right. Special function modules — — 8 — 8 16
Inputs X 0 – 17 — — 20 – 37 —
Adresses OutputsY 0 – 17 20 – 37 — 40 – 57 —
Special function modules No.0 No.1
Σ 96

24 MITSUBISHI ELECTRIC
MELSEC FX0N/FX2N
Specifications SYSTEM DESCRIPTION

Environmental Specifications þ FX0N þ FX2N


General specifications Data
Ambient temperature 0 – 55 °C
Operating temperature 0 – 55 °C
Storage temperature -20 – +70 °C
Servcie power supply 24 V DC,200 mA (FX0N);250/460 mA (FX2N) ripple ratio at maximum load:≤ ±5 %
Protection IP 20
Noise durability 1000 Vpp with noise generator;1 ms at 30 – 100 Hz
Dielectric withstand voltage 1500 V AC,1 min.
Ambient relative humidity 35 – 85 % (non-condensing)
Shock resistance 10 G (3 times in 3 directions)
Vibration resistance 2 G:resistance to vibrations from 10 – 55 Hz for 2 hours along all 3 axes;0.5 G for DIN rail mounting
Isulation resistance 500 V DC,5 MΩ
Ground Class 3
Fuse FX0N:3 A (all units),FX2N:3,15 A (up to FX2N-32왏왏); 5 A (from FX2N-48왏왏)
Environment Avoid environments containing corrosive gases,install in a dust-free location.
Certifications FX0N:UL/CSA/CE/DNV/RINA,FX2N:UL/CSA/CE/DNV/LL

General Specifications þ FX0N þ FX2N

System specifications FX0N FX2N


Program data
I/O points (adresses) 128 256
Address range Max.84 inputs X0–X123,max.64 outputs Y0–Y77 Max.256 inputs X0–X377,max.256 outputs Y0–Y377
8000 steps RAM (internal),
Program memory 2000 steps EEPROM (internal), 4000 steps EPROM/EEPROM cassettes (optional),
EEPROM/ EPROM cassettes (optional) 16000 steps RAM cassettes (optional),
16000 steps EEPROM cassettes (optional) for further details refer to p.52
Cycle period Min.1.6 µs / logical instruction 0.08 µs / logical instruction
Number of instructions 20 sequence instructions,2 stepladder instructions, 27 sequence instructions,2 stepladder instructions,18 verify instructions,
42 applied instructions 107 applied instructions
Programming language Stepladder,instruction list Stepladder,instruction list,SFC
Program execution Cyclical execution,refresh mode processing Cyclical execution,refresh mode processing
Program protection Password protection with 3 protection levels Password protection with 3 protection levels
Operands
Internal relays 512 (128 buffered) 3072
Special relays 57 256
Step ladder 128 1000
Timer 64 256
Ext. preset value via potentiometer 2 —
Counter 32 (16 buffered) 256
High-speed counter Max.4 6 single phase inputs (4 double phase inputs)
Real-time clock — Year,month,day,hour,minut,second,weekday
Data register 256 (128 buffered) 8000
File register Max.1500 Max .7000 (parameter editable)
Index register 2 16
Special register 28 256
Pointer 64 128
Nestings 8 8
Interrupt inputs Max.4 6
16 bits:K:-32768 to +32767,hex:0–FFFF 16 bits:K:-32768 to +32767,hex:0–FFFF
Constants 32 bits:K:2147483648 to +2147483647,hex:0–FFFF FFFF 32 bits:K:2147483648 to +2147483647,hex:0–FFFF FFFF
32 bits floating point:0, ±1.175 x 10-38 to ±3.403 x 10-38

MITSUBISHI ELECTRIC 25
MELSEC FX0N/FX2N
BASE UNITS Specifications

Specifications of Base Units þ FX0N ¨ FX2N

FX
BASICS Base Units FX0N
The FX0N series base units are available with
24, 40 or 60 input/output points.
It is possible to choose between relay and
transistor output type.

Special features:
앬 Integrated serial interface for communica-
tion between PC and HMI
앬 Standard programming unit interface
앬 LEDs for indicating the input and output
status
앬 Detachable terminal blocks at units with
40 and 60 I/Os
앬 Slot for memory cassettes and
real-time clock

FX0N-24 FX0N-24 FX0N-24 FX0N-40 FX0N-40 FX0N-40


Specifications
MR-DS MR-ES/UL MT-DSS MR-DS MR-ES/UL MT-DSS
Electrical data
Integrated inputs/outputs 24 24 24 40 40 40
AC range (+10%, -15%) — 100–240 V AC — — 100–240 V AC —
Power
supply Frequency at AC Hz — 50/60 (±10 %) — — 50/60 (±10 %) —
DC range (+20%, -15%) 24 V DC — 24 V DC 24 V DC — 24 V DC
Max. input apparent power 18W 50VA 18 W 20 W 50VA 20W
100 V AC — 30 A / 5 ms — — 30 A / 5 ms —
Inrush
current at ON 200 V AC — 50 A / 5 ms — — 50 A / 5 ms —
24 V DC 60 A / 50 µs — 60 A / 50 µs 60 A / 50 µs — 60 A / 50 µs
Allowable momentary power failure time 10 10 10 10 10 10
External service power supply (24 V DC) — 200 — — 200 —
Inputs
Integrated inputs 14 14 14 24 24 24
Min. current for logical 1 mA 3.5 3.5 3.5 3.5 3.5 3.5
Max. current for logical 0 mA 1.5 1.5 1.5 1.5 1.5 1.5
Response time For all base units of the MELSEC FX0N series values:10 ms (at time of shipment),partly adjustable between 0 and 15 ms
Outputs
Integrated outputs 10 10 10 16 16 16
Output type Relay Relay Transistor Relay Relay Transistor
Max. switching voltage V Generally for relay version:< 264 V AC,< 30 V DC;for transistor version:5 – 30 V DC
Max. output - per output A 2 2 0,5 2 2 0,5
current - per group* A — — 0,8 — — 0,8
Max. switching - inductive load VA 80 80 12 80 80 12
power - lamp load W 100 100 1,5 100 100 1,5
Response time ms 10 10 < 0,2 10 10 < 0,2
Life of contacts (switching times) For all base units of the MELSEC FX0N series values:3000000 at 20 VA;1000000 at 35 VA;200000 at 80 VA
Mechanical data
Weight kg 0.6 0.6 0.6 0.75 0.75 0.75
Dimensions (W x H x D) mm 130 x 90 x 87 130 x 90 x 87 130 x 90 x 87 150 x 90 x 87 150 x 90 x 87 150 x 90 x 87

Order information Art. no. 66657 66656 66658 66660 66659 66661
* Thislimitation applies only per reference terminalfor eachgroup,4 and8 outputs for relaysand 2 and 4 outputsfor transistors.Please observe the terminal assignments for thegroup identification.

26 MITSUBISHI ELECTRIC
MELSEC FX0N/FX2N
Specifications BASE UNITS

Specifications of Base Units þ FX0N ¨ FX2N

FX
BASICS

FX0N-60 FX0N-60 FX0N-60


Specifications
MR-DS MR-ES/UL MT-DSS
Electrical data
Integrated inputs/outputs 60 60 60
AC range (+10%, -15%) — 100–240 V AC —
Power
supply Frequency at AC Hz — 50/60 (±10 %) —
DC range (+20%, -15%) 24 V DC — 24 V DC
Max. input apparent power 24W 60 VA 24W
100 V AC — 30 A / 5 ms —
Inrush
current at ON 200 V AC — 50 A / 5 ms —
24 V DC 60 A / 50 µs — 60 A / 50 µs
Allowable momentary power failure time 10 10 10
Externalservicepowersupply(24VDC) mA — 200 —
Inputs
Integrated inputs 36 36 36
Min. current for logical 1 mA 3.5 3.5 3.5
Max. current for logical 0 mA 1.5 1.5 1.5
Response time For all base units of the MELSEC FX0N series values:10 ms (at time of shipment),partly adjustable between 0 and 15 ms
Outputs
Integrated outputs 24 24 24
Output type Relay Relay Transistor
Max. switching voltage V Generally for relay version:< 264 V AC,< 30 V DC;for transistor version:5 – 30 V DC
Max. output - per output A 2 2 0.5
current - per group* A — — 0.8
Max. switching - inductive load VA 80 80 12
power - lamp load W 100 100 1.5
Response time ms 10 10 < 0.2
Life of contacts (switching times) For all base units of the MELSEC FX0N series values:3000000 at 20 VA;1000000 at 35 VA;200000 at 80VA
Mechanical data
Weight kg 0.9 0.9 0.9
Dimensions (W x H x D) mm 185 x 90 x 87 185 x 90 x 87 185 x 90 x 87

Order information Art. no. 66663 66662 66664

* Thislimitation appliesonly per reference terminal for each group, 4 and 8 outputs for relaysand 2 and 4 outputsfor transistors. Please observe the terminal assignments for thegroupidentification.

MITSUBISHI ELECTRIC 27
MELSEC FX0N/FX2N
BASE UNITS Specifications

Specifications for Base Units ¨ FX0N þ FX2N

FX
BASICS
Base Units FX2N
The FX2N series base units are available with
16, 32, 48, 64, 80 or 128 input/output points.
It is possible to choose between relay and
transistor output type.

Special features:
앬 Exchangable interface modules for direct
mounting into a base unit
앬 Standard programming unit interface
앬 LEDs for indicating the input and output
status
앬 Detachable terminal blocks
앬 Slot for memory cassettes for up to 16 k
steps PLC program
앬 Integrated real-time clock

FX2N-16 FX2N-16 FX2N-32 FX2N-32 FX2N-32 FX2N-32


Specifications
MR-ES/UL MT-ESS/UL MR-DS 햳 MR-ES/UL MT-DSS 햳
MT-ESS/UL
Electrical data
Integrated inputs/outputs 16 16 32 32 32 32
AC range (+10%,-15%) 100–240 V AC 100–240 V AC — 100–240 V AC — 100–240 V AC
Power
supply Frequency at AC Hz 50/60 (±10 %) 50/60 (±10 %) — 50/60 (±10 %) — 50/60 (±10 %)
DC range (+20 %, -30 %) — — 24 V DC — 24 V DC —
Max. input apparent power 30VA 30VA 25W 40 VA 25 W 40VA
Inrush AC 100 V 40 A < 5 ms 40 A < 5 ms — 40 A < 5 ms — 40 A < 5 ms
current at ON AC 200 V 60 A < 5 ms 60 A < 5 ms — 60 A < 5 ms — 60 A < 5 ms
Allowable momentary ms 10 10 5 10 5 10
power failure time
External service power supply (24 V DC) mA 250 250 — 250 — 250
Power supply int. bus (5 V DC) mA 290 290 290 290 290 290
Inputs
Integrated inputs 8 8 16 16 16 16
Input current X0→X7 / X10→∞ mA 7 / 5 7/5 7/5 7/5 7/5 7/5
Min. current for logical 1 mA 4.5 /3.5 4.5 / 3.5 4.5 / 3.5 4.5 / 3.5 4.5 / 3.5 4.5 / 3.5
X0→X7 / X10→∞
Max. current for logical 0 mA 1.5 1.5 1.5 1.5 1.5 1.5
Isolation Photocoupler isolation between input terminals and PC power for all base units.
Response time For all base units of the MELSEC FX2N series values:10 ms (at time of shipment),partly adjustable between 0 and 15 ms (REFF,FNC51 = 0 – 60 ms)
Outputs
Integrated outputs 8 8 16 16 16 16
Output type Relay Transistor Relay Relay Transistor Transistor
ON voltage (max.) Generally for relay version:< 250 V AC,< 30 V DC;for transistor version:5 – 30 V DC
Max. output - per output A 2 0.5 2 2 0.5 0.5
current - per group 햲 A — 0.8 — — 0.8 0.8
Max. switching - inductive load W 80 12 80 80 12 12
power - lamp load W 100 1.5 100 100 1.5 1.5
Response time ms 10 < 0.2 10 < 0.2 < 0.2 < 0.2
Life of contacts (switching times) For all base units of the FX2N series values:3000000 at 20 VA;1000000 at 35 VA;200000 at 80 VA
Mechanical data
Weight kg 0.6 0.6 0.65 0.65 0.65 0.65
Dimensions (W x H x D) mm 130 x 90 x 87 130 x 90 x 87 150 x 90 x 87 150 x 90 x 87 150 x 90 x 87 150 x 90 x 87

Order information Art. no. 65550 65551 66620 65553 66621 65554
햲 This limitationappliesonly per referenceterminal for each group,4 and8 outputs for relaysand 2 and 4 outputsfor transistors. Please observe the terminal assignmentsfor the group identification.
햳 Available until 07/1998

28 MITSUBISHI ELECTRIC
MELSEC FX0N/FX2N
Specifications BASE UNITS

Specifications of Base Units ¨ FX0N þ FX2N

FX
BASICS

FX2N-48 FX2N-48 FX2N-48 FX2N-48 FX2N-64 FX2N-64 FX2N-64 FX2N-64


MR-DS 햳 MR-ES/UL MT-ESS/UL MT-DSS b MR-DS b MR-ES/UL MT-DSS b MT-ESS/UL

48 48 48 48 64 64 64 64
— 100–240 V AC 100–240 V AC — — 100–240 V AC — 100–240 V AC
— 50/60 (±10 %) 50/60 (±10 %) — — 50/60 (±10 %) — 50/60 (±10 %)
24 V DC — — 24 V DC 24 V DC — 24 V DC —
30 W 50 VA 50VA 30W 35W 60VA 35 W 60 VA
— 40 A < 5 ms 40 A < 5 ms — — 40 A < 5 ms — 40 A < 5 ms
— 60 A < 5 ms 60 A < 5 ms — — 60 A < 5 ms — 60 A < 5 ms
5 10 10 5 5 10 5 10
— 460 460 — — 460 — 460
290 290 290 290 290 290 290 290

24 24 24 24 32 32 32 32
7/5 7/5 7/5 7/5 7/5 7/5 7/5 7/5
4.5 / 3.5 4.5 / 3.5 4.5 / 3.5 4.5 / 3.5 4.5 / 3.5 4.5 / 3.5 4.5 / 3.5 4.5 / 3.5
1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5
Photocoupler isolation between input terminals and PC power for all base units.
For all base units of the MELSEC FX2N series values:10 ms (at time of shipment),partly adjustable between 0 and 15 ms (REFF,FNC51 = 0 – 60 ms)

24 24 24 24 32 32 32 32
Relay Relay Transistor Transistor Relay Relay Transistor Transistor
Generally for relay version:< 250 V AV,< 30 V DC;for transistor version:5 – 30 V DC
2 2 0.5 0.5 2 2 0.5 0.5
8 8 0.8 0.8 8 8 0.8 0.8
80 80 12 12 80 80 12 12
100 100 1.5 1,5 100 1.5 1.5 1.5
10 10 < 0.2 <0.2 10 10 < 0.2 < 0.2
For all base units of the FX2N series values:3000000 at 20 VA;1000000 at 35 VA;200000 at 80 VA

0.85 0.85 0.85 0,85 1.0 1.0 1.0 1.0


182 x 90 x 87 182 x 90 x 87 182 x 90 x 87 182 x 90 x 87 220 x 90 x 87 220 x 90 x 87 220 x 90 x 87 220 x 90 x 87

66622 65560 65561 66623 66624 65562 66626 65563


햲 This limitation applies only per reference terminal for each group, 4 and 8 outputs for relays and 2 and 4 outputs for transistors. Please observe the terminal assignments for the group identification.
햳 Available until 07/1998

MITSUBISHI ELECTRIC 29
MELSEC FX0N/FX2N
BASE UNITS Specifications

Specifications of Base Units ¨ FX0N þ FX2N

FX
BASICS

FX2N-80 FX2N-80 FX2N-80 FX2N-80 FX2N-128 FX2N-128


Specifications
MR-DS 햳 MR-ES/UL MT-ESS/UL MT-DSS b MR-ES/UL MT-ESS/UL
Electrical data
Integrated inputs/outputs 80 80 80 80 128 128
AC range (+10%,-15%) — 100–240 V AC 100–240 V AC — 100–240 V AC 100–240 V AC
Power
supply Frequency at AC Hz — 50/60 (±10 %) 50/60 (±10 %) — 50/60 (±10 %) 50/60 (±10 %)
DC range (± 8 V) 24 V DC — — 24 V DC — —
Max. input apparent power 40W 70 VA 70VA 40 W 100 VA 100VA
Inrush 100 V AC — 40 A < 5 ms 40 A < 5 ms — 50 A < 7 ms 50 A < 7 ms
current at ON 200 V AC — 60 A < 5 ms 60 A < 5 ms — 70 A < 7 ms 70 A < 7 ms
Allowable momentary ms 5 10 10 5 10 10
power failure time
Externalservice power supply (24 V DC) mA — 460 460 — 460 460
Power supply int. bus (5 V DC) mA 290 290 290 290 290 290
Inputs
Integrated inputs 40 40 40 40 64 64
Input current X0→X7 / X10→∞ mA 7/5 7/5 7/5 7/5 7/5 7/5
Min. current for logical 1 mA 4.5 / 3.5 4.5 / 3.5 4.5 / 3.5 4.5 / 3.5 4.5 / 3.5 4.5 / 3.5
X0→X7 / X10→∞
Max. current for logical 0 mA 1.5 1.5 1.5 1.5 1.5 1.5
Isolation Photocoupler isolation between input terminals and PC power for all base units
Response time For all base units of the MELSEC FX2N series values:10 ms (at time of shipment),partly adjustable between 0 and 15 ms (REFF,FNC51 = 0 – 60 ms)
Outputs
Integrated outputs 40 40 40 40 64 64
Output type Relay Relay Transistor Transistor Relay Transistor
ON voltage (max.) Generally for relay version:< 250 V AC,< 30 V DC;for transistor version:5 – 30 V DC
Max. output - per output A 2 2 0.5 0.5 2 0.5
current - per group* A 8 8 0.8 0.8 8 0.8
Max. switching - inductive load W 80 80 12 12 80 12
power - lamp load W 100 100 1.5 1.5 100 1.5
Response time ms 10 10 < 0.2 < 0.2 10 < 0.2
Life of contacts (switching times) For all base units of the FX2N series values:3000000 at 20 VA;1000000 at 35 VA;200000 at 80 VA
Mechanical data
Weight kg 1.2 1.2 1.2 1.2 1.8 1.8
Dimensions (W x H x D) mm 285 x 90 x 87 285 x 90 x 87 285 x 90 x 87 285 x 90 x 87 350 x 90 x 87 350 x 90 x 87

Order information Art. no. 66627 65564 65565 66628 65566 65567
햲 Thislimitation applies only per reference terminalfor each group,4 and 8 outputsfor relays and2 and4 outputs for transistors.Pleaseobservetheterminal assignmentsfor the group identification.
햳 Available until 07/1998

30 MITSUBISHI ELECTRIC
MELSEC FX0N/FX2N
The Extension Concept SYSTEM DESCRIPTION

Digital Inputs/Outputs
Various modular and compact extension
units are available for extending the
The large number of possible combina-
tions of base and extension units of the
A base unit can be extended by a maxi-
mum of 128 (FX0N series) or 256 (FX2N se-
FX
BASICS
MELSEC MELSEC FX0N/FX2N base units. MELSEC FX0N/FX2N ensure that the best ries) external inputs/outputs by means of
The modular extension units contain only possible economical solution is found for these extension units.
digital inputs/outputs and no separate every application. FX0N and FX2N series extension units can
power supply, while compact extension Owing to the capacity of the internal po- be combined without any problems.
units contain a larger number of in- wer supply unit of the respective base unit
puts/outputs and an integrated power or of the compact extension unit, modular
supply unit for supplying the system bus expandability of the controller is possible
and the digital inputs. with the help of a protected flat cable.

IN

Compact extension units þ FX0N þ FX2N

Module type Inputs Outputs Output type Module type Inputs Outputs Output type
FX0N-40ER-ES/UL 24 16 Relay FX2N-32ER-ES/UL 16 16 Relay
FX0N-40ER-DS 24 16 Relay FX2N-32ET-ESS/UL 16 16 Transistor
FX0N-40ET-DSS 24 16 Transistor FX2N-48ER-ES/UL 24 24 Relay
FX2N-48ET-ESS/UL 24 24 Transistor
FX2N-48ER-DS 24 24 Relay
FX2N-48ET-DSS 24 24 Transistor

Modular extension units þ FX0N þ FX2N

Module type Inputs Outputs Output type Module type Inputs Outputs Output type
FX0N-8EX-ES/UL 8 — — FX2N-16EX-ES/UL 16 — —
FX0N-16EX-ES/UL 16 — — FX2N-16EYR-ES/UL — 16 Relay
FX0N-8EYR-ES/UL — 8 Relay FX2N-16EYT-ESS/UL — 16 Transistor
FX0N-8EYT-ESS/UL — 8 Transistor
FX0N-16EYR-ES/UL — 16 Relay
FX0N-16EYT-ESS/UL — 16 Transistor
FX0N-8ER-ES/UL 4 4 Relay

MITSUBISHI ELECTRIC 31
MELSEC FX0N/FX2N
EXTENSION UNITS Specifications

Compact Extension Units þ FX0N þ FX2N

FX Extension Units FX0N


BASICS The FX0N series extension units are available
with 40 input/output points.
It is possible to choose between relay and
transistor output type.

Special features:
앬 LEDs for indicating the input and output
status
앬 MELSEC FX2N series compatible
앬 Integrated service power supply
with up to 200 mA capacity

FX0N-40 FX0N-40 FX0N-40


Specifications
ER-ES/UL ER-DS ET-DSS
Electrical data
Integrated inputs/outputs 40 40 40
AC range (+10%, -15%) AC 100 – 240 V — —
Power
supply Frequency at AC Hz 50/60 (±10%) — —
DC range (+20%, -15%) — DC 24 V DC 24
Max. input apparent power 40VA 20W 20 W
100 V AC 30 A / 5 ms — —
Inrush
current at ON 200 V AC 50 A / 5 ms — —
24 V DC — 60 A / 50 µs 60 A / 50 µs
Allowable momentary ms 10 10 10
power failure time
Externalservice power supply (24 V DC) mA 200 — —
Inputs
Integrated inputs 24 24 24
Min. current for logical 1 mA 3.5 3.5 3.5
Max. current for logical 0 mA 1.5 1.5 1.5
Response time For all base units of the MELSEC FX0N series values:10 ms (at time of shipment)
Outputs
Integrated outputs 16 16 16
Output type Relay Relay Transistor
Max. switching voltage Generally for relay version:< 264 V AC,< 30 V DC;for transistor version:5 – 30 V DC
Max. output - per output A 2 2 0.5
current - per group* A — — 0.8
Max. switching - inductive load VA 80 80 12
power - lamp load W 100 100 1,5
Response time ms 10 10 < 0.2
Life of contacts (switching times) For all extension units of the MELSEC FX0N series values:3000000 at 20 VA;1000000 at 35 VA;200000 at 80 VA
Mechanical data
Weight kg 0.6 0.6 0.6
Dimensions (W x H x D) mm 150 x 90 x 87 150 x 90 x 87 150 x 90 x 87

Order information Art. no. 60012 55955 55954

* Thislimitation applies only per reference terminal for eachgroup,4 and 8 outputsfor relaysand 2 and 4 outputsfor transistors.Please observetheterminal assignmentsfor the group identification.

32 MITSUBISHI ELECTRIC
MELSEC FX0N/FX2N
Specifications EXTENSION UNITS

Compact Extension Units þ FX0N þ FX2N

FX
Extension Units FX2N BASICS

The FX2N series extension units are available


with 32 or 48 input/output points.
It is possible to choose between relay and
transistor output type.

Special features:
앬 LEDs for indicating the input and output
status
앬 MELSEC FX0N series compatible
앬 Detachable terminal blocks
앬 Integrated service power supply
with up to 200 mA or 460 mA

FX2N-32 FX2N-32 FX2N-48 FX2N-48 FX2N-48 FX2N-48


Specifications
ER-ES/UL ET-ESS/UL ER-DS ER-ES/UL ET-DSS ET-ESS/UL
Electrical data
Integrated inputs/outputs 32 32 48 48 48 48
AC range (+10 %, -15 %) 100 – 240 V AC 100 – 240 V AC — 100 – 240 V AC — 100 – 240 V AC
Power
supply Frequency at AC Hz 50/60 (±10 %) 50/60 (±10 %) — 50/60 (±10 %) — 50/60 (±10 %)
DC range (+20 %, -30 %) — — 24 V DC — 24 V DC —
Max. input apparent power 35VA 35VA 30W 45 VA 30 W 45VA
Inrush 100 V AC 50 A < 5 ms — 50 A < 5 ms 50 A < 5 ms 50 A < 5 ms 50 A < 5 ms
current at ON 200 V AC 60 A < 5 ms — 60 A < 5 ms 60 A < 5 ms 60 A < 5 ms 60 A < 5 ms
Allowable momentary ms 10 10 10 10 10 10
power failure time
External service power supply (24 V DC) mA 250 250 — 250 — 460
Power supply int. bus (5 V DC) mA 690 690 690 690 690 690
Inputs
Integrated inputs 16 16 24 24 24 24
Min. current for logical 1 mA 3.5 3.5 3.5 3.5 3.5 3.5
Max. current for logical 0 mA 1.5 1.5 1.5 1.5 1.5 1.5
Response time For all extension units of the MELSEC FX2N series values:10 ms (at time of shipment)
Outputs
Integrated outputs 16 16 24 24 24 24
Output type Art Relay Transistor Relay Relay Transistor Transistor
ON voltage (max.) Generally for relay version:< 264 V AC,< 30 V DC;for transistor version:5 – 30 V DC
Max. output - per output A 2 0.5 2 2 0.5 0.5
current - per group* A 8 0.8 8 8 0.8 0.8
Max. switching - inductive load W 80 12 80 80 12 12
power - lamp load W 100 1.5 100 100 1.5 1.5
Response time ms 10 < 0.2 10 10 < 0.2 < 0.2
Life of contacts (switching times) For all extension units of the MELSEC FX2N series values:3000000 at 35 VA;1000000 at 80 VA;200000 at 120 VA
Mechanical data
Weight kg 0.65 0.65 0.85 0.85 0.85 0.85
Dimensions (W x H x D) mm 150 x 90 x 87 150 x 90 x 87 182 x 90 x 87 182 x 90 x 87 182 x 90 x 87 182 x 90 x 87

Order information Art. no. 65568 65569 66633 65571 66634 65572

MITSUBISHI ELECTRIC 33
MELSEC FX0N/FX2N
EXTENSION UNITS Specifications

Modular Extension Units þ FX0N þ FX2N

FX
BASICS Extension Units FX0N
The FX0N series modular extension units are
available with 8 or 16 input/output points.
It is possible to choose between relay and
transistor output type.

Special features:
앬 LEDs for indicating the input and output
IN status
앬 MELSEC FX2N series compatible
앬 Vertically mounted (at 8 I/Os) or horizon-
tally mounted (at 16 I/Os) terminal blocks
with a cable guide to the upper or lower
side

FX0N-8 FX0N-8 FX0N-8 FX0N-8 FX0N-16 FX0N-16 FX0N-16


Specifications
ER-ES/UL EX-ES/UL EYR-ES/UL EYT-ESS/UL EX-ES/UL EYR-ES/UL EYT-ESS/UL
Electrical data
Integrated inputs/outputs 8 8 8 8 16 16 16
Power supply All modulare extension units are supplied by the base unit.
Inputs
Integrated inputs 4 8 — — 16 — —
Min. current for logical 1 mA 3.5 3.5 — — 3.5 — —
Max. current for logical 0 mA 1.5 1.5 — — 1.5 — —
Response time For all extension units of the MELSEC FX0N series values:10 ms
Outputs
Integrated outputs 4 — 8 8 — 16 16
Output type Relay — Relay Transistor — Relay Transistor
Max. switching voltage Generally for relay version:< 264 V AC,< 30 V DC;for transistor version:5 – 30 V DC
Max. output - per output A 2 — 2 0.5 — 2 0.5
current - per group* A — — — 0.8 — — 0.8
Max. switching - inductive load VA 80 — 80 12 — 80 12
power - lamp load W 100 — 100 1.5 — 100 1.5
Response time ms 10 10 10 < 0.2 10 10 < 0.2
Life of contacts (switching times) For all extension units of the MELSEC FX0N series values:3000000 at 20 VA;1000000 at 35 VA;200000 at 80 VA
Mechanical data
Weight kg 0.2 0.2 0.2 0.2 0.3 0.3 0.3
Dimensions (W x H x D) mm 43 x 90 x 87 43 x 90 x 87 43 x 90 x 87 43 x 90 x 87 70 x 90 x 87 70 x 90 x 87 70 x 90 x 87

Order information Art. no. 60023 60013 60014 60016 55952 55951 55950

* Thislimitation applies only per reference terminalfor eachgroup,4 and8 outputs for relaysand 2 and 4 outputsfor transistors.Please observe the terminal assignments for thegroup identification.

34 MITSUBISHI ELECTRIC
MELSEC FX0N/FX2N
Specifications EXTENSION UNITS

Modular Extension Units þ FX0N þ FX2N

FX
Extension Units FX2N BASICS

The FX2N series modular extension units are


available with 16 input/output points.
OUT It is possible to choose between relay and
transistor output type.

Special features:
앬 LEDs for indicating the input and output
status
OUT
앬 MELSEC FX0N series compatible
앬 Especially compact design
앬 Vertical mounted terminal blocks with
a cable guide to the upper or lower side

FX2N-16 FX2N-16 FX2N-16


Specifications
EX-ES/UL EYR-ES/UL EYT-ES/UL
Electrical data
Integrated inputs/Outputs 16 16 16
Power supply All modulare extension units are supplied by the base unit.
Inputs
Integrated inputs 16 — —
Min. current for logical 1 mA 3,5 — —
Max. current for logical 0 mA 1,5 — —
Response time For all base units of the MELSEC FX2N series values:10 ms (at time of shipment)
Outputs
Integrated outputs — 16 16
Output type — Relay Transistor
ON voltage (max.) V Generally for relay version:< 264 V AC,< 30 V DC;for transistor version:5 – 30 V DC
Max. output - per output A — 2 0,5
current - per group* A — — 0,8
Max. switching - inductive load VA — 80 12
power - lamp load W — 100 1,5
Response time ms — 10 < 0,2
Life of contacts (switching times) — Same as base unit —
Mechanical data
Weight kg 0,3 0,3 0,3
Dimensions (W x H x D) mm 40x90x87 40 x 90 x 87 40 x 90 x 87

Order information Art. no. 65776 65580 65581

* Thislimitation applies only per reference terminalfor each group,4 and 8 outputsfor relays and2 and4 outputs for transistors.Pleaseobservetheterminal assignmentsfor the group identification.

MITSUBISHI ELECTRIC 35
MELSEC FX0N/FX2N
SPECIAL FUNCTION MODULES Analog Modules

왎 Analog Setpoint Adapter FX2N-8AV-BD ¨ FX0N þ FX2N

The FX2N-8AV-BD enables the user to set PLC program using the dedicated in-
FX 8 analog setpoint values. The analog values structions VRRD/VRSC (FNC85/86). The
BASICS of the potentiometers are read into the FX2N-8AV-BD adapter board is installed
controller and used as default setpoint in the expansion slot of the FX2N CPU.
values for timers, counters and data regis- No additional power supply is required
ters by the user’s PLC programs. Setpoint for operation.
value polling and the definition of the
potentiometer scales are performed in the

Specifications FX2N-8AV-BD
General specifications Conforms to base units
Power supply From base unit
JY331B88801B

Adjusting range 8 bit


Related I/O points 0
Potentiometer evaluation Via application instruction from the PLC CPU (FNC 85/86)
Weight kg 0.08
Dimensions (W x H) mm 52 x 35

Order information Art. no. 65594

왎 Analog Module FX0N-3A þ FX0N þ FX2N

The analog module FX0N-3A provides the The analog module is connected to the
user with 2 analog inputs and 1 analog out- base unit via a protected flat cable. The
put. They serve for conversion of analog connection is to the extension bus on
process signals into digital values, and vice the right side of the controller.
versa.

Specifications FX0N-3A
General specifications Conforms to base units
Dielectric withstand voltage 500 V AC for 1 minute
Power supply 24 V DC / 90 mA (from base unit),5 V DC / 30 mA
Number of inputs 2
analog points outputs 1
voltage V DC 0 – 10 / 0 – 5
Analog data
current mA DC 4 – 20
I/O resolution 20 mV/ 64 µA (8 bit)
Total accuracy ±1 %
Conversion time A→D/D→A ms 0.1/point
Related I/O points 8
Weight kg 0.2
Dimensions (W x H x D) mm 43 x 90 x 87

Order information Art. no. 41790

36 MITSUBISHI ELECTRIC
MELSEC FX0N/FX2N
Analog Modules SPECIAL FUNCTION MODULES

왎 Analog Output Module FX2N-4DA þ FX0N þ FX2N


CPU vers. 2.00

These analog output modules provide the


user with 4 analog outputs. The modules
The modules can output both current and
voltage signals.
FX
BASICS
convert digital values from the FX0N/FX2N-
controller to the analog signals required
by the process.
24+
24-

Specifications FX2N-4DA
V+
VI-
I+

General specifications Conforms to base units


Power supply 5 V DC/ 30mA(frombaseunit),24V DC/200mA
V+
VI-
I+

inputs —
V+

Analog channels
outputs 4
VI-
I+

FX2N-4DA

Analog output range -10 V DC – +10 V DC / 0 mA – +20 mA


V+
VI-
I+

voltage output 2 kΩ – 1 MΩ
24+
24-

External load
current output < 500 Ω
V+
VI-
I+

voltage V ±10
Analogdata
V+
VI-

current mA 0 – 20
I+
V+

FX 2N-4DA
Resolution 5 mV / 20 µA (11 bit + sign)
VI-
I+

Overall accuracy ±1 %
FX2N-4DA
V+
VI-

analog → digital ms —
I+

D/A
Conversion speed
digital → analog ms 2.1 for 4 channels
Related I/O points 8
Weight kg 0.3
Dimensions (W x H x D) mm 55 x 90 x 87

Order information Art. no. 65586

왎 Analog Input Module FX2N-4AD þ FX0N þ FX2N


CPU vers. 2.00

The analog input module FX2N-4AD The actual values or mean values over
provides the user with 4 analog inputs. several measurements may be output.
The module converts analog process
signals into digital values which are
further processed by the MELSEC
FX0N/FX2N controller.
24+
24-
V+
VI-

Specifications FX2N-4AD
I+
FG

General specifications Conforms to FX2N base units


V+
VI-
I+

Power supply 5 V DC / 30 mA (from base unit),24 V DC / 50 mA


FG
V+

inputs 4
VI-

Analog points
I+

outputs —
FG
V+
VI-
I+

Analog input range -10 V DC – +10 V DC / -20 mA – +20 mA / 4 – 20 mA


24+
24-

voltage input kΩ 200


V+

Input resistance
VI-


I+

current input 250


FG
V+

voltage V ±10
VI-

Analog data
I+
FG

current mA ±20
V+

5 mV / 20 µA (11 bit + sign)


VI-

Resolution
I+
FG
V+

Overall accuracy ±1 %
VI-
I+

analog → digital 15perchannel/60per4channels (high-speed)


Conversion speed
digital → analog ms —
Related I/O points 8
Weight kg 0.3
Dimensions (W x H x D) mm 55 x 90 x 87

Order information Art. no. 65585

MITSUBISHI ELECTRIC 37
MELSEC FX0N/FX2N
SPECIAL FUNCTION MODULES Analog Modules

왎 Analog Input Module for Thermo Elements FX2N-4AD-TC þ FX0N þ FX2N


CPU vers. 2.00

This special function module FX2N-4AD-TC a mean value from a predetermined


FX is used for processing temperatures. It has number of measurements in order to
BASICS 4 independent inputs for detecting sig- obtain stable digital results.
nals from thermocouples of types J and K. The number of measurements must be
The type of thermocouple can be chosen transferred by the PLC program to a
independently for each point. buffer memory of the special function
The electrical magnitude at an input is module. The value determined is avail-
24+
24- SLD

converted into a digital numerical value able in another memory address.


L+
L-

with a sign. The converted value is stored by


the PLC in a memory address, so-called
SLD
L+
L-

buffer memory, in the module and then


SLD

converted. It is also possible to calculate


L+

FX2N-4AD-TC
L-
SLD
L+
L-

24+
24- SLD

Specifications FX2N-4AD-TC
L+

General specifications Conforms to FX2N base units


L-

Power supply 5 V DC / 30 mA (from base unit),24 V DC / 50 mA


SLD
L+
L-

Analog inputs 4 (K or J type)


SLD

FX 2N-4AD-TC Compensated temperature range °C -100 – +600 (J type) / -100 – +1200 (K type)
L+

FX2N-4AD-TC
L-

Digital output -1000 – +6000 (J type) / -1000 – +12000 (K type)


SLD
L+
L-

Resolution °C 0.3 (J type) / 0.4 (K type)


Overall accuracy ±0.5 %
Conversion speed ms 240 per channel (±2 %)
Related I/O points 8
Weight kg 0.3
Dimensions (W x H x D) mm 55 x 90 x 87

Order information Art. no. 65588

왎 Analog Input Module for Pt100 Inputs FX2N-4AD-PT þ FX0N þ FX2N


CPU vers. 2.00

The analog input module FX2N-4AD-PT per- The respective temperatures can be
mits the connection of four Pt100 sensors read out either in °C or °F.
to the FX controller.
24+
24-
I-
L+
L-

Specifications FX2N-4AD-PT
FG

General specifications Conforms to FX2N base units


I-
L+
L-
FG

Power supply 5 V DC / 30 mA (from base unit),24 V DC / 50 mA


I-

Analog inputs 4 (Pt100 sensors)


L+

FX2N-4AD-PT
L-
FG

Compensated temperature range °C -100 – +600


I-
L+
L-

24+

Digital output -1000 – 6000 (12 bit conversion)


24- SLD

Resolution °C 0.2
L+
L-

Overall accuracy ±1 % over full linear range


SLD
L+
L-

Conversion speed ms 15 for 4 channels


SLD

FX 2N-4AD-PT Related I/O points 8


L+

FX2N-4AD-TC
L-
SLD

Weight kg 0.3
L+
L-

Dimensions (W x H x D) mm 55 x 90 x 87

Order information Art. no. 65587

38 MITSUBISHI ELECTRIC
MELSEC FX0N/FX2N
High-Speed Counter and Positioning Module SPECIAL FUNCTION MODULES

왎 High-Speed Counter FX2N-1HC þ FX0N þ FX2N


CPU vers. 2.00

In addition to the internal high-speed


MELSEC FX counters, the high-speed
The two integrated transistor outputs can
be switched independently of one another
FX
BASICS
counter module FX2N-1HC provides the by means of internal comparison func-
user with an external hardware counter. tions. Hence, simple positioning tasks can
It counts 1- or 2-phase pulses up to a also be realized economically. In addition,
frequency of 50 kHz. The counting range the FX2N-1HC can be used as a ring
covers either 16 or 32 bit. counter.

Specifications FX2N-1HC
General specifications Conforms to FX2N base units
Signal level 5,12,24 V DC / 7 mA
Power supply 5 V DC / 90 mA from base unit
Counter inputs 2 (1 phase) oder 1 (2 phase)
Max. counting frequency kHz 50
Input format Bit 16,32
Typ of counter Up/down counter,ring counter
16 Bit -2147483648 – +2147483647
Conting range
32 Bit 0 – 65535
Output type 2 x transistor (5 – 24 V DC;0.5 A)
Related I/O points 8
Weight kg 0.3
Dimensions (W x H x D) mm 55 x 90 x 87

Order information Art. no. 65584

왎 Single Axes Positioning Module FX2N-1PG-E þ FX0N þ FX2N


CPU vers. 2.00

The positioning module FX2N-1PG-E is an Further special features are:


extremely efficient single-axis positioning 앬 Possibility of absolute or relative posi-
module for controlling either step drives tioning
or servo drives (by external regulator) 앬 7 different operation functions, such as
with a pulse chain. It is very suitable for jog mode, zeroing, variable speeds, etc.
achieving accurate positioning in combi- 앬 Separate programming units and
nation with the MELSEC FX series. The
RP PG0+

operator panels are not required.


configuration and allocation of the posi-
1PG
앬 The speed increase or decrease can be
POWER tion data are carried out directly via the
PLC program. A very wide range of set either automatically or manually.
manual and automatic functions are
available to the user.
COM1 S/S S/S
CLR STOP DOG

Specifications FX2N-1PG-E
FX 2N -1PG
POWER
General specifications Conforms to FX2N base units
S
T D P
O O G
P G O
Signal level for digital inputs 24 V DC / 7–40 mA
F R C E
P P L R
R R
Power supply 5 – 24 V DC / 60 mA
Accessible axes 1
Output frequency pulse/s 10 – 100 000
Related I/O points 8
Weight kg 0.3
Dimensions (W x H x D) mm 43 x 90 x 87

Order information Art. no. 65583

MITSUBISHI ELECTRIC 39
MELSEC FX0N/FX2N
SPECIAL FUNCTION MODULES Interface Modules

왎 Active Data Interface FX0N-232ADP þ FX0N þ FX2N


CPU vers. 2.00

The additional RS232C interface FX0N- The module is suitable for the connection
FX 232ADP permits active communication of printers, bar code readers, PCs and
BASICS between the PLC and surrounding other PLC systems. The communication is
RS232C peripherals. All operands can handled by the PLC program using the RS
be sent or received via this interface. instruction.
Devices can be transmitted via this inter- The connection is to the communications
face. A program transfer or the connec- bus on the left side of the controller.
tion of an MAC terminal is not possible. The internal serial RS422 interface is also
fully available.

Specifications FX0N-232ADP
General specifications Conforms to FX0N/FX2N base units
Interface RS232with25poleD-SUBcompactplug(photocouplerisolated)
Power supply 5 V DC / 200 mA (from base unit)
Communication speed Bit/s 300,600,1200,2400,4800,9600,19200
Communication distance m Max.15
Communication cable Shielded cable
Communication mode Half duplex
Protocols Non-protocolmode/freeprogrammableviaPLC
Format 7 or 8 bits,parity 1 or 0,1 or 2 stop bit
Related I/O points —
Weight kg 0.2
Dimensions (W x H x D) mm 43 x 90 x 68

Order information Art. no. 42211

왎 Interface Module FX2N-232IF þ FX0N þ FX2N


CPU-Vers. 2.00

The FX2N-232IF module provides an The send and receive data are stored in
RS-232C interface for serial data communi- the FX2N-232IF’s own buffer memory.
cations with the MELSEC FX2N/FX0N. Changes at the user program are not
Communication with PCs, printers, possible via this interface.
modems, barcode readers etc. is handled
by the PLC program using FROM/TO in-
structions.

Specifications FX2N-232IF
General specifications Conforms to FX2N base units
Interface RS232 with 9 pole D-SUBconnector (photocouppler isolation)
Power supply 5 V DC / 40 mA (from base unit),24 V DC / 80 mA
Communication speed bit/s 300,600,1200,2400,4800,9600,19200
Communication distance m Max.15
Communication cable Shielded cable
Communication mode Full duplex
Protocols Nonprotocolmode/startstopsynchronisation
Format 7 or 8 data bits,parity 1 or 0,1 or 2 stop bit
Send and receive buffer 512 byte each
Related I/O points 8
Weight kg 0.3
Dimensions (W x H x D) mm 55 x 90 x 85

Order information Art. no. 66640

40 MITSUBISHI ELECTRIC
MELSEC FX0N/FX2N
Interface Modules SPECIAL FUNCTION MODULES

왎 Interface Adapter FX2N-232BD ¨ FX0N þ FX2N

The FX2N-232BD interface adapter board


provides an RS-232C interface for serial data
instruction. Connected programming
systems are identified automatically.
FX
BASICS
communications with the MELSEC FX2N. The adapter board is installed in the
Data and programmes can be transferred expansion slot provided for it in the
with the standard RS-232 protocol. The FX2N base unit.
unit’s integrated automatic parameter If the adapter is used no other adapters
setting facility also makes it possible to con- can be used.
figure a modem – for example for remote
If additional RS232C interfaces are
programming and maintenance tasks.
required, the FX2N-232IF can be used
Data can be transferred directly to other for extension.
serial peripherals using the RS dedicated

Specifications FX2N-232BD
General specifications Conforms to FX2N base units
JY331B89001C
FX2N-232-BD

Interface RS232 with 9 pole D-SUB connector


Power supply 5 V DC / 60 mA (from base unit)
Communication speed bit/s 300,600,1200,2400,4800,9600,19200
Communication distance m Max.15
Communication mode Half duplex

Protocols Free programmable via PLC/ non-protocol mode /


protocol 1 or 4
Related I/O points —
Weight kg 0,08
Dimensions (W x H x D) mm 35 x 54 x 22

Order information Art. no. 65596

왎 Interface Adapter FX2N-422BD ¨ FX0N þ FX2N

The FX2N-422BD interface adapter board is not possible to connect a second one
provides a second RS-422 interface for to the FX2N-422BD interface adapter.
connection of an additional device to the It is possible to connect two control
controller (programming unit or operator units, however.
terminal). The adapter is installed in the expansion
In addition to programming the PLC the slot provided for it in the FX2N base unit.
main applications for this interface include No additional adapter boards can be
production data logging, process visualisa- used when this unit is installed.
tion and man-machine communication.
If one programming unit is already con-
FX2N-422-BD nected to the integrated RS-422 interface it
JY331B89101B

Specifications FX2N-422BD
General specifications Conforms to FX2N base units
Interface RS422 8 pole mini DIN connector
Power supply 5 V DC / 60 mA (from base unit)
Communication distance m Max.50
Communication mode Half duplex
Protocols FreeprogrammableviaPLC
Related I/O points —
Weight kg 0.08
Dimensions (W x H x D) mm 35 x 54 x 22

Order information Art. no. 65595

MITSUBISHI ELECTRIC 41
MELSEC FX0N/FX2N
SPECIAL FUNCTION MODULES Communications Modules

The MELSECNET/MINI Network

FX Data communications
BASICS MELSECNET/MINI enables fast data ex-
change with a variety of devices. Equip-
ment you can integrate in this network
type includes:
앬 Remote digital I/Os
AnS/QnAS
앬 Analog I/Os
앬 High-speed counters
Remote I/O
앬 Remote intelligence modules
(e.g FX0N/FX2N)
앬 Frequency inverters (FR-A 540)
앬 Third-party equipment, e.g.
FESTO/SMC MELSECNET/MINI
Structure
The network’s ring topology enables a
very large maximum coverage:
앬 Max. 1700 m with shielded twisted- FX2N/FX0N
pair cabling with PPN network
FX2N
앬 Max. 10000 m with shielded twisted- Frequency inverter
pair cabling combined with fibre-
optics cables

Cable types Specifications Electrical Optical


The network supports a variety of differ- Cable type Shielded Acrylic Glass fibre Glass fibre
ent cable types as communications media: twisted-pair fibre optic SI type GI type
앬 Shielded twisted-pair rate MBit/s 1.5 1.5 1.5 1.5
앬 Acrylic fibre-optics cable (max. 50 m/ Communi- distance between
cations 2 stations m 100 50 1000 2000
segment)
total coverage m ≤ 1700 ≤ 850 ≤ 6000 ≤ 10000
앬 Glass fibre-optics cable SI200/250 µm
(max. 1000 m/segment) internal resistance Ω ≤ 88 / km — — —
(at 20 °C)
앬 Glass fibre-optics cable GI50/125 µm electrostatic
(max. 2000 m/segment) capacity nF ≤ 60 / km — — —
Media
impedance(100kHz) Ω 110 (±10) — — —
Data exchange transmissionlosses — ≤ 260 dB / km ≤ 12 dB / km ≤ 3 dB / km
inner/outer µm — 980 / 1000 200 / 250 50 / 125
This network can transport a variety of dif- diameter
ferent data without any problems, includ- Connectors
ing both digital and analog data.
Connection system RG59 CA9104AP CA9003 CA9003S
An FX0N/FX2N controller configured as a
slave can exchange (transmit and receive)
Order information Art. no. 17530 9546 29603
up to 28 data words with the master PLC
(AnS, QnAS). Recommended shielded twisted-pair cabling (2 pairs): Lappkabel Unitronic Li2YCY (TP) paired (up to 100 m) or
Unitronic Li2YCY (TP) finely-stranded (up to 50 m)

Administration
The programming software packages
MELSEC MEDOC plus and MELSEC MINI-P
make installation and set-up simple and
trouble-free.

42 MITSUBISHI ELECTRIC
MELSEC FX0N/FX2N
Communications Modules SPECIAL FUNCTION MODULES

왎 Communications Module FX0N-16NT þ FX0N þ FX2N

The communications module FX0N-16NT


enables the user to connect to the
Thus the network is expandable via the
digital inputs/outputs of the FX mod-
FX
BASICS
MELSECNET/MINI with a superior A system ules to a maximum of 512 I/Os.
as master CPU. This gives him access to The connection is to the extension bus
the network of all MELSEC PLC systems and on the right side of the controller.
frequency inverters and to additional
products from other suppliers.

Specifications FX0N-16NT
General specifications Conforms to FX0N base units
Dielectric withstand voltage 500 V AC for one minute
Power supply 24 V DC / 60 mA (from external power module)
Communication speed Mbit/s 1.5
Communication distance m 50 at 0.2 – 0.5 mm2
100 at > 0.5 mm2
Communication cable Shielded twisted pair 0.5 mm2
Communication mode Bit transformation
Related I/O points 16
Weight kg 0.2
Dimensions (W x H x D) mm 43 x 90 x 87

Order information Art. no. 41819

MITSUBISHI ELECTRIC 43
MELSEC FX0N/FX2N
SPECIAL FUNCTION MODULES Communications Modules

왎 Communications Modules for MELSECNET/MINI FX-16NP and FX-16NT þ FX0N þ FX2N


CPU-Vers. 2.00

These communications modules permit For the connection of these modules to


FX the linking of programmable logic control- the FX0N or FX2N series the adapter
BASICS lers of the MELSEC FX0N/FX2N series as a FX2N-CNV-IF is needed.
local station in the MELSECNET/MINI with
a superior A system as master CPU.

Specifications FX-16NP FX-16NT


General specifications Conforms to FX base units
Power supply 5 V DC / 80 mA (from base unit),24 V DC / 120 mA
Master module AJ71PT32-S3 A(1S)J71PT32-S3 or A2CCPU
Communications modules within network Max.32 Max.32
Data words — —
Transformed bits 8 sent / 8 received 8 sent / 8 received
Related I/O points 24 24
I/O refresh time ms 3–4 3–4
Communication speed MBit/s 1.5 1.5
Communication cable Plastic fibre Twisted pair

Communication distance m 50 50 (at 0.2–0.5mm2)


100 (at 0.5 mm2)
Weight kg 0.3 0.3
Dimensions (W x H x D) mm 45 x 140 x 95 45 x 140 x 95

Order information Art. no. 25196 25197

왎 Communications Modules for MELSECNET/MINI FX-16NP-S3 and FX-16NT-S3 þ FX0N þ FX2N


CPU-Vers. 2.00

These communications modules permitthe processing of analog values in the net-


linking of programmable logic controllers work with the FX0N-/FX2N series is possi-
of the MELSEC FX0N-/FX2N series as a local ble. Max. 16 of these communications
station in the MELSECNET/MINI-S3 with a modules can be integrated in a MELSEC-
superior A system as master CPU. NET/MINI-S3.
In a S3 network, in addition to data ex- For the connection of these module to
change via digital inputs and outputs, it the FX0N or FX2N series the adapter
is also possible to transfer data words FX2N-CNV-IF is needed.
(max. 56), with the result that, for example,

Specifications FX-16NP-S3 FX-16NT-S3


General specifications Conforms to FX base units
Power supply 5 V DC / 80 mA (from base unit),24 V DC / 100 mA
Master station AJ71PT32-S3 A(1S)J71PT32-S3 or A2CCPU
Communications modules within network Max.16 Max.16
Data words FX → A:28 / A → FX:28 FX → A:28 / A → FX:28
Transformed bits 8 sent / 8 received 8 sent / 8 received
Related I/O points 24 24
I/O refresh time ms 3–4 3–4
Communication speed MBit/s 1.5 1.5
Communication cable Plastic fibre Twisted pair

Communicatin distance m 50 50 (at 0.2–0,5mm2)


100 (at 0.5 mm2)
Weight kg 0.4 0.4
Dimensions (W x H x D) mm 73 x 140 x 95 73 x 140 x 95

Order information Art. no. 33714 33715

44 MITSUBISHI ELECTRIC
MELSEC FX0N/FX2N
Communications Modules SPECIAL FUNCTION MODULES

왎 MELSEC Peer-to-Peer Network, 1:n Network, Parallel Link

The networks in details: FX


BASICS

앬 Peer-to-Peer
You can integrate up to 8 programmable Master station
logic controllers in a peer-to-peer network.
All stations in the network can monitor all
the devices in the entire data range. How- 485BD/
ever, data writing and setting and resetting 485ADP FX2N
of individual devices is always only per-
formed in the specific station in question.
Each network station can transfer packets of Slave Slave Slave
up to 64 bits and 8 data words via the net-
work.
The maximum distance between the first 485BD/ 485BD/ 485BD/
485ADP FX0N/FX2N 485ADP FX0N/FX2N 485ADP FX0N/FX2N
and last connected stations depends on the
type of adapters used:
FX0N-485ADP: max. 500 m (CPU vers. 2.0)
FX2N-485BD: max. 50 m

앬 1 : n Multidrop-Netzwerk
This network is used for displaying and Personal computer
monitoring data from the individual sta- with FX-485PC-IF
tions on a connected computer.
You can connect up to 16 stations in one of
these networks. The maximum distance be-
tween the first and last connected station
depends on the type of adapters used:
RS485 nezwork

FX0N-485ADP: max. 500 m


FX2N-485BD: max. 50 m
AnA / AnU / QnA

Interface
unit

FX0N / FX2N FX0N / FX2N FX0N / FX2N

앬 Parallel Link
As the name indicates, parallel link mode
connects two programmable logic control-
lers with a parallel link. Data communica-
tion between the two states is performed Master station
automatically via a predefined range of
relays and data registers.
The maximum distance between two sta-
tions connected by parallel link is 50 m.
If the FX0N-485 ADP is used, the maximum
distance will be 500 m. FX2N FX2N

MITSUBISHI ELECTRIC 45
MELSEC FX0N/FX2N
SPECIAL FUNCTION MODULES Communications Modules

왎 Interface Adapter FX2N-485BD ¨ FX0N þ FX2N

The FX2N-485BD interface adapter board In peer-to-peer network configurations


FX provides the FX2N unit with an additional the adapter enables active communica-
BASICS RS-485 interface. The adapter, which is sim- tion between the individual FX0N/FX2N
ply inserted into the base unit’s expansion controllers via the RS-485 interfaces.
slot, enables the configuration of RS-485 In 1:n multidrop networks the adapter
1:n multidrop, parallel link or peer-to-peer can be use to provide communication
networks with FX0N/FX2N systems. with a host master station of the A series.
You can also transfer data directly to other
RDA RDB SDA SDB SG

RS-485 peripherals using the RS dedicated


instruction.

Specifications FX2N-485BD
JY331B88901C
FX2N-485-BD

General specifications Conforms to FX2N base units


Power supply 5 V DC / 60 mA from base unit
Interface RS485 / RS422
Communication speed bit/s 300 – 19200
Communication cable Twisted pair
Communication distance m max.50

Protocols Protocol 1 or 4 of AJ71UC24 /noprotocol/parallellink/


peer-to-peernetwork
Related I/O points Station 0
Weight kg 0.08
Dimensions (W x H x D) mm 35 x 54 x 22

Order information Art. no. 65597

왎 Communications Module FX0N-485ADP þ FX0N þ FX2N

The FX0N-485ADP communications mod- In FX0N systems the module is con-


ule enables the configuration of 1:n mul- nected directly to the communications
tidrop, parallel link and peer-to-peer data bus on the left-hand side of the FX0N
networks using the RS-485 interface. base unit. The FX2N-CNV-BD communi-
Configuration of peer-to-peer data net- cations adapter is required for connec-
works requires version 2.00 of the FX0N- tion to FX2N base unit.
485ADP (see p. 21 for details).

Specifications FX0N-485ADP
General specifications Conforms to FX0N base units
Power supply 5 V DC / max.30 mA (from base unit),24 V DC / 50 mA
Interface RS485
Communication speed bit/s 300 – 19200
Communication distance m Max.500
Communication cable Shielded cable
Communication mode Half duplex
Protocols Protocol1and4ofAJ71UC24
Related I/O points —
Weight kg 0.3
Dimensions (W x H x D) mm 43 x 90 x 87

Order information Art. no. 66665

46 MITSUBISHI ELECTRIC
MELSEC FX0N/FX2N
Communications Modules SPECIAL FUNCTION MODULES

왎 Interface Unit for RS485 1:n Multidrop Network FX-485PC-IF þ FX0N þ FX2N

The interface unit FX-485PC-IF is used for


converting interface signals.
FX
BASICS
The module has an RS232C interface for con-
nection to a PC and RS485 ports for connec-
tion to the network.

Specifications FX-485PC-IF
General specifications Conforms to FX2N base units
Current consumption mA 260
Power supply 5 V DC ±5 %
Interface RS232 / RS485
Communication speed bit/s 300,600,1200,2400,4800,9600,19200
Communication cable Shielded cable
15 (RS232)
Communication distance m
500 (RS485)
Communication mode Half duplex
Protocols Protocol 1 and 4 of AJ71UC24
Weight kg 0.3
Dimensions (W x H x D) mm 100 x 80 x 30

Order information Art. no. 53416

The power supply is used for the interface


unit FX-485PC-IF.

Specifications SC06 N-PG


General specifications Conforms to FX2N base units
Power supply 5 V DC / 800 mA
Weight kg
Dimensions (W x H x D) mm

Order information Art. no. 32630

MITSUBISHI ELECTRIC 47
MELSEC FX0N/FX2N
SPECIAL FUNCTION MODULES Communications Modules

The PROFIBUS/DP Network

FX Data Communications
Master PLC
BASICS The open PROFIBUS/DP network enables
extremely fast data exchange with a very
wide variety of slave devices, including:
앬 Remote digital I/Os
앬 Remote intelligence PLC AnS / QnAS AnA / AnU / QnA
(FX0N, FX2N)
앬 Frequency inverters (FR-A 024/044,
FR-A 240 and MELTRAC 140) Slave units
앬 Operator terminals (MAC)
앬 A range of other devices from third- max. 1.200 m at 93.75 kBit/s without repeater
party manufacturers
FX0N / FX2N

Structure E300/E700

The maximum coverage of a bus segment P R O F I


PROCESS FIELD BUS
is 1200 m (at a maximum of 93.75 kbit/s).
Up to 3 repeaters are allowed. Thus the B U S
maximum distance between 2 stations is
calculated with 4800 m.
FR-A 024/044
FR-A 240/540
Cable types MELTRAC 16 outputs

To help reduce costs PROFIBUS/DP uses


RS-485 technology with simple twisted-
pair cabling.
Suitable cables include the UNITRONIC
BUSLD from Lappkabel and the DUE 4451 Specifications Master AJ71PB92 Master A1SJ71PB92D
from Alcatel. Communications protocol EN 50170 / DIN 19245-T3
Cabling Shielded twisted-pair with 24 AWG = 0,22 mm2,impedance:100 – 130 Ω;
Shielded twisted-pair with 22 AWG = 0,34 mm2,impedance:135 – 165 Ω;
Data exchange Interface RS485
The PROFIBUS AJ71PB92 and distance
A1SJ71PB92D master modules support 1 200 m kbit/s 9.6 / 19.2 / 93.75
slave device data exchange with up to Data
transfer 1 000 m kbit/s 187.5
32 send bytes and 32 receive bytes. This rate
means you can exchange a total of up to 400 m kbit/s 500
64 bytes with a slave unit per network 200 m kbit/s 1 500 12000 / 6000 / 3000 (100 m)
1500 (200 m)
cycle.
Max total distance m 4800 (3 repeaters)
Slave units per master 60
Administration Stations per segment 32
In combination with the MELSEC Profi- Repeaters per network 3
Map configuration software the ProfiCon:PROFIBUS 9-pin D-SUB plug connector for up to 12 Mbaud,
A1SJ71PB92D PROFIBUS/DP master unit art.no.64127 or art. 87035 (see page 73) ;
Accessories ProfiMap:configurations software for MELSEC master modules and third party devices,
gives you user-friendly plug-and-play
art.no.102996 (see page 71)
technology. The configuration software is
self-explanatory, using a graphical model
for setting up the network. You simply se-
lect the slave unit (e.g. FX2N), assign the
station numbers and specify where the
information is stored in the Master CPU.
Of course, PROFIBUS/DP slaves from
MITSUBISHI ELECTRIC can also be con-
nected to master devices from other
manufacturers.

48 MITSUBISHI ELECTRIC
MELSEC FX0N/FX2N
Communications Modules SPECIAL FUNCTION MODULES

왎 Profibus DP Slave Module FX0N-32NT-DP þ FX0N þ FX2N

The FX0N-32NT-DP Profibus module en-


ables you to integrate a MELSEC FX 0N/FX2N
It links the system to the master PLC in
the Profibus DP network for efficient
FX
BASICS
system in an existing Profibus DP network. and trouble-free data exchange.
This interface module provides your FX0N
or FX2N CPU with an intelligent Profibus DP
link for the implementation of decentral-
ised control tasks.
24+ FG
24G

FXON -32NT
-DT
Specifications FX0N-32NT-DP
General specifications Conforms to FX0N base units
Power supply 5 V DC / max.170 mA (from base unit),24 V DC / 60 mA
FX 0N -32NT-DP
Interface Profibus DP
POWER DC RUN

distance
BF DIA
1200 m kbit/s 9.6 / 19.2 / 93.75
Communication
speed 1000 m kbit/s 187.5
200 m kbit/s 1500
100 m kbit/s 3000 / 6000 / 12000
Communication distance m Max.1200 (dependson communicationspeed)
Communication cable PROFIBUS cable with 9-pin D-SUB plug
Related I/O points 8
Weight kg 0.3
Dimensions (W x H x D) mm 43 x 90 x 87

Order information Art. no. 62125

MITSUBISHI ELECTRIC 49
MELSEC FX0N/FX2N
SPECIAL FUNCTION MODULES Communications Modules

왎 Communications Adapter FX2N-CNV-IF þ FX0N þ FX2N

The FX2N-CNV-IF communications adapter tal FX modules and special function


FX (IF = interface) enables you to connect your modules.
BASICS FX series special function modules to
FX0N/FX2N systems.
MITSUBISHI
The adapter provides compatibility
between the FX0N/FX2N CPU and the digi-

Specifications FX2N-CNV-IF
General specifications Conforms to FX2N base units
Power supply Not necessary
Related I/O points 0
Weight kg 0.15
Dimensions (W x H x D) mm 23 x 140 x 45
FX2N-CNV-IF

Order information Art. no. 65599

왎 Communications Adapter FX2N-CNV-BD ¨ FX0N þ FX2N

The FX2N-CNV-BD communications adapt- 485ADP special function modules to the


er (BD = function board) enables connec- left-hand side of the FX2N base units.
tion of the FX0N-232ADP and FX0N-

Specifications FX2N-CNV-BD
General specifications Conforms to FX2N base units
FX2N-CNV-BD
JY331B89201B Power supply Not necessary
Related I/O points 0
Weight kg 0.08
Dimensions (W x H) mm 54 x 35

Order information Art. no. 65598

50 MITSUBISHI ELECTRIC
MELSEC FX0N/FX2N
SPECIAL FUNCTION MODULES

FX
BASICS

MITSUBISHI ELECTRIC 51
MELSEC FX0N/FX2N
ACCESSORIES Memory Cassettes – Interface Converter

왎 Memory/Real-Time Clock Cassettes þ FX0N þ FX2N

All FX0N/FX2N base units are equipped program specified in the respective mem-
FX with a slot for the optional, robust FX ory cassette is run. The program con-
BASICS memory cassettes. By connection of these tained in the internal memory is retained
cassettes, the internal memory of the due to battery buffering.
controller is switched off and only the

Data FX-RAM-8 FX-EPROM-8 FX-EEPROM-4


Memory type RAM EPROM EEPROM
Size 16000 steps (FX2N) 8000 steps 4000 steps
Accessory — — —

Order information Art. no. 23823 23824 23825

Data FX-EEPROM-4C FX-EEPROM-8 FX-EEPROM-16 FX-RTC


Memory type EEPROM EEPROM EEPROM Real-time clock
Size 4000 steps 8000 steps 16000 steps —
Accessory Real-time clock — — Battery (optional)

Order information Art. no. 23833 23826 65600 23831

왎 Interface Converter CR01-R2/R4 SET and CR01-R4/R4 þ FX0N þ FX2N

This module is a signal amplifier with computer, especially when a potential


photocoupler isolation for RS422 signals. isolation is required and when the wir-
It is used to connect a PLC with external ing length takes more than 15 meters.
devices like operation panels or a personal

Specifications CR01-R4/R4 CR01-R2/R4 SET


Interface convertation RS422 ↔ RS422 RS422 ↔ RS232 (with SC09)

Order information Art. no. 56173 56172

52 MITSUBISHI ELECTRIC
MELSEC FX0N/FX2N
PROM Adapter – Simulation Strip – Switch Box ACCESSORIES

왎 PROM Adapter FX-ROM SOC1

The PROM adapter is used for adapting


memory cassettes to a Textool base.
commercial EPROM loader in order, for
example, to load a MEDOC program.
FX
BASICS
This socket is required if the memory
cassette EPROM-8 is to be written with a

Data FX-ROM SOC1

Order information Art. no. 27163

왎 Simulation Strip: Input-SIM

The simulation strip has 8 switches for Two different simulation strips are avail-
simulating digital inputs. able due to the differences within the
The strip is directly mounted to the termi- terminal block between the MELSEC FX0N
nals of the unit and fixed with screws to and FX2N series PLC.
the terminal block. The simulation strip can be expanded
24V 0V 24V 0V
A cable is provided for connecting the with another strip for further inputs.
Input-SIM: FXOS/FXON
strip to the power supply.
1 3 5 7

6
0 2 4
Data Input-SIM: FX0S/FX0N Input-SIM: FX2N
X00 - X07
Switches 8 8
Application FX0S and FX0N series FX2N series
Dimensions(WxHxD) mm 30 x 50 x 15 30 x 50 x 15

Order information Art. no. 65081 66513

왎 Switch Box

The simulation box has 12 switches for


simulating digital inputs.
It can be used on all controllers of the
MELSEC FX familiy.

Data Switch-Box
Switches 12

Order information Art. no. 3386

MITSUBISHI ELECTRIC 53
MELSEC FX0N/FX2N
ACCESSORIES Batteries

왎 Battery F2-40BL2N ¨ FX0N þ FX2N

The battery F2-40BL can be used for all units


FX of the MELSEC FX2N series. The battery buffers
BASICS the internal RAM of the MELSEC FX2N PLC in
the event of a voltage failure.

Data F2-40BL

Order information Art. no. 5142

왎 Battery FX0N-40B þ FX0N ¨ FX2N


The battery FX0N-40B can be used for all The battery buffers the internal real-time
units of the MELSEC FX0N series if these clock.
units are provided with a real-time clock
cassette.

Data FX0N-40B

Order information Art. no. 44331

54 MITSUBISHI ELECTRIC
MELSEC FX0N/FX2N
Connection Cable ACCESSORIES

왎 Connection Cable for Base and Compact Extension Units

The cable is used for connection between


a base unit or and a compact extension unit.
The cable must be connected to the left
side of the compact extension unit.
FX
BASICS
This permits a multi-row arrangement of a
MELSEC FX0N-/FX2N-System.

Data FX0N-65EC
Type Flat cable
Length m 0.65

Order information Art. no. 45348

MITSUBISHI ELECTRIC 55
MELSEC FX0N/FX2N
TERMINALS + DIMENSIONS Terminal Assignment

왎 Base Units MELSEC FX0N

FX
BASICS
FX0N-24MT-DSS
S/S X1 X3 X5 X7 X11 X13 X15 FX0N-40MT-DSS
S/S S/S X1 X3 X5 X7 X11 X13 X15 X17 X21 X23 X25 X27
+ X0 X2 X4 X6 X10 X12 X14 + X0 X2 X4 X6 X10 X12 X14 X16 X20 X22 X24 X26

FX0N-24MR-DS
S/S X1 X3 X5 X7 X11 X13 X15 FX0N-40MR-DS
S/S S/S X1 X3 X5 X7 X11 X13 X15 X17 X21 X23 X25 X27
+ X0 X2 X4 X6 X10 X12 X14 + X0 X2 X4 X6 X10 X12 X14 X16 X20 X22 X24 X26

FX0N-24MR-ES/UL S/S X1 X3 X5 X7 X11 X13 X15 FX0N-40MR-ES/UL S/S S/S X1 X3 X5 X7 X11 X13 X15 X17 X21 X23 X25 X27
L N X0 X2 X4 X6 X10 X12 X14 L N X0 X2 X4 X6 X10 X12 X14 X16 X20 X22 X24 X26

FX0N-24MR-ES/UL 0V Y0 Y1 Y2 Y3 Y5 Y6 Y10 FX0N-40MR-ES/UL 0V Y0 Y1 Y2 Y4 Y6 Y10 Y12 Y14 Y16


24V COM0 COM1 COM2 COM3 Y4 COM4 Y7 Y11 24V COM0 COM1 COM2 Y3 COM3 Y5 Y7 COM4 Y11 Y13 COM5 Y15 Y17

FX0N-24MR-DS
0V Y0 Y1 Y2 Y3 Y5 Y6 Y10 FX0N-40MR-DS
0V Y0 Y1 Y2 Y4 Y6 Y10 Y12 Y14 Y16
24V COM0 COM1 COM2 COM3 Y4 COM4 Y7 Y11 24V COM0 COM1 COM2 Y3 COM3 Y5 Y7 COM4 Y11 Y13 COM5 Y15 Y17

FX0N-24MT-DSS
0V Y0 Y1 Y2 Y3 Y5 Y6 Y10 FX0N-40MT-DSS
0V Y0 Y1 Y2 Y4 Y6 Y10 Y12 Y14 Y16
24V +V0 +V1 +V2 +V3 Y4 +V4 Y7 Y11 24V +V0 +V1 +V2 Y3 +V3 Y5 Y7 +V4 Y11 Y13 +V5 Y15 Y17

FX0N-60MT-DSS
S/S S/S X1 X3 X5 X7 X11 X13 X15 X17 X21 X23 X25 X27 X31 X33 X35 X37 X41 X43
+ X0 X2 X4 X6 X10 X12 X14 X16 X20 X22 X24 X26 X30 X32 X34 X36 X40 X42

FX0N-60MR-DS
S/S S/S X1 X3 X5 X7 X11 X13 X15 X17 X21 X23 X25 X27 X31 X33 X35 X37 X41 X43
+ X0 X2 X4 X6 X10 X12 X14 X16 X20 X22 X24 X26 X30 X32 X34 X36 X40 X42

FX0N-60MR-ES/UL
S/S S/S X1 X3 X5 X7 X11 X13 X15 X17 X21 X23 X25 X27 X31 X33 X35 X37 X41 X43
L N X0 X2 X4 X6 X10 X12 X14 X16 X20 X22 X24 X26 X30 X32 X34 X36 X40 X42

FX0N-60MR-ES/UL 0V Y0 Y1 Y2 Y4 Y6 Y10 Y12 Y14 Y16 Y20 Y22 Y24 Y26


24V COM0 COM1 COM2 Y3 COM3 Y5 Y7 COM4 Y11 Y13 COM5 Y15 Y17 COM6 Y21 Y23 COM7 Y25 Y27

FX0N-60MR-DS
0V Y0 Y1 Y2 Y4 Y6 Y10 Y12 Y14 Y16 Y20 Y22 Y24 Y26
24V COM0 COM1 COM2 Y3 COM3 Y5 Y7 COM4 Y11 Y13 COM5 Y15 Y17 COM6 Y21 Y23 COM7 Y25 Y27

0V Y0 Y1 Y2 Y4 Y6 Y10 Y12 Y14 Y16 Y20 Y22 Y24 Y26


FX0N-60MT-DSS
24V +V0 +V1 +V2 Y3 +V3 Y5 Y7 +V4 Y11 Y13 +V5 Y15 Y17 +V6 Y21 Y23 +V7 Y25 Y27

56
MELSEC FX0N/FX2N
Terminal Assignment TERMINALS + DIMENSIONS

왎 Base Units MELSEC FX2N

FX2N-32MT-DSS
S/S 0V X0
24V X1
X2
X3
X4
X5
X6 X10 X12 X14 X16
X7 X11 X13 X15 X17
FX
BASICS
FX2N-32MT-ESS/UL
S/S 0V X0 X2 X4 X6 X10 X12 X14 X16
L N 24V X1 X3 X5 X7 X11 X13 X15 X17

FX2N-16MT-ESS/UL
S/S 0V X0 X2 X4 X6 FX2N-32MR-DS
S/S 0V X0 X2 X4 X6 X10 X12 X14 X16
L N 24V X1 X3 X5 X7 24V X1 X3 X5 X7 X11 X13 X15 X17

FX2N-16MR-ES/UL S/S 0V X0 X2 X4 X6 FX2N-32MR-ES/UL S/S 0V X0 X2 X4 X6 X10 X12 X14 X16


L N 24V X1 X3 X5 X7 L N 24V X1 X3 X5 X7 X11 X13 X15 X17

S/S 0V X0 X2 X4 X6 COM X0 X2 X4 X6 X10 X12 X14 X16


L N 24+ X1 X3 X5 X7 L N 24+ X1 X3 X5 X7 X11 X13 X15 X17

0 1 2 3 4 5 6 7
IN IN
0 1 2 3 4 5 6 7 POWER 10 11 12 13 14 15 16 17
POWER

RUN RUN

BATT.V BATT.V

0 1 2 3 4 5 6 7 PROG-E 0 1 2 3 4 5 6 7 PROG-E
OUT OUT
FX 2N -16MR CPU-E
FX 2N-32MR 10 11 12 13 14 15 16 17 CPU-E

Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 Y0 Y2 Y4 Y6 Y10 Y12 Y14 Y16


Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y11 Y13 COM4 Y15 Y17

FX2N-16MR-ES/UL Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 FX2N-32MR-ES/UL Y0 Y2 Y4 Y6 Y10 Y12 Y14 Y16


Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y11 Y13 COM4 Y15 Y17

FX2N-16MT-ESS/UL
Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 FX2N-32MR-DS
Y0 Y2 Y4 Y6 Y10 Y12 Y14 Y16
+V0 +V1 +V2 +V3 +V4 +V5 +V6 +V7 COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y11 Y13 COM4 Y15 Y17

FX2N-32MT-ESS/UL
Y0 Y2 Y4 Y6 Y10 Y12 Y14 Y16
+V0 Y1 Y3 +V1 Y5 Y7 +V2 Y11 Y13 +V3 Y15 Y17

FX2N-32MT-DSS
Y0 Y2 Y4 Y6 Y10 Y12 Y14 Y16
+V0 Y1 Y3 +V1 Y5 Y7 +V2 Y11 Y13 +V3 Y15 Y17

FX2N-48MT-DSS
S/S 0V X0 X2 X4 X6 X10 X12 X14 X16 X20 X22 X24 X26
24V X1 X3 X5 X7 X11 X13 X15 X17 X21 X23 X25 X27

FX2N-48MT-ESS/UL
S/S 0V X0 X2 X4 X6 X10 X12 X14 X16 X20 X22 X24 X26
L N 24V X1 X3 X5 X7 X11 X13 X15 X17 X21 X23 X25 X27

FX2N-48MR-DS
S/S 0V X0 X2 X4 X6 X10 X12 X14 X16 X20 X22 X24 X26
24V X1 X3 X5 X7 X11 X13 X15 X17 X21 X23 X25 X27

FX2N-48MR-ES/UL S/S 0V X0 X2 X4 X6 X10 X12 X14 X16 X20 X22 X24 X26
L N 24V X1 X3 X5 X7 X11 X13 X15 X17 X21 X23 X25 X27

FX2N-48MR-ES/UL Y0 Y2 Y4 Y6 Y10 Y12 Y14 Y16 Y20 Y22 Y24 Y26 COM5
COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y11 Y13 COM4 Y15 Y17 Y21 Y23 Y25 Y27

FX2N-48MR-DS
Y0 Y2 Y4 Y6 Y10 Y12 Y14 Y16 Y20 Y22 Y24 Y26 COM5
COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y11 Y13 COM4 Y15 Y17 Y21 Y23 Y25 Y27

FX2N-48MT-ESS/UL
Y0 Y2 Y4 Y6 Y10 Y12 Y14 Y16 Y20 Y22 Y24 Y26 +V4
+V0 Y1 Y3 +V1 Y5 Y7 +V2 Y11 Y13 +V3 Y15 Y17 Y21 Y23 Y25 Y27

FX2N-48MT-DSS
Y0 Y2 Y4 Y6 Y10 Y12 Y14 Y16 Y20 Y22 Y24 Y26 +V4
+V0 Y1 Y3 +V1 Y5 Y7 +V2 Y11 Y13 +V3 Y15 Y17 Y21 Y23 Y25 Y27

57
MELSEC FX0N/FX2N
TERMINALS + DIMENSIONS Terminal Assignment

FX FX2N-64MT-DSS
+
S/S 0V 0V X0
24V 24V X1
X2
X3
X4
X5
X6 X10 X12 X14 X16 X20 X22 X24 X26 X30 X32 X34 X36
X7 X11 X13 X15 X17 X21 X23 X25 X27 X31 X33 X35 X37
BASICS
FX2N-64MT-ESS/UL
S/S 0V 0V X0 X2 X4 X6 X10 X12 X14 X16 X20 X22 X24 X26 X30 X32 X34 X36
L N 24V 24V X1 X3 X5 X7 X11 X13 X15 X17 X21 X23 X25 X27 X31 X33 X35 X37

FX2N-64MR-DS
S/S 0V 0V X0 X2 X4 X6 X10 X12 X14 X16 X20 X22 X24 X26 X30 X32 X34 X36
+ 24V 24V X1 X3 X5 X7 X11 X13 X15 X17 X21 X23 X25 X27 X31 X33 X35 X37

FX2N-64MR-ES/UL S/S 0V 0V X0 X2 X4 X6 X10 X12 X14 X16 X20 X22 X24 X26 X30 X32 X34 X36
L N 24V 24V X1 X3 X5 X7 X11 X13 X15 X17 X21 X23 X25 X27 X31 X33 X35 X37

S/S 0V 0V X0 X2 X4 X6 X10 X12 X14 X16 X20 X22 X24 X26 X30 X32 X34 X36
L N 24V 24V X1 X3 X5 X7 X11 X13 X15 X17 X21 X23 X25 X27 X31 X33 X35 X37

0 1 2 3 4 5 6 7 20 21 22 23 24 25 26 27

10 11 12 13 14 15 16 17 30 31 32 33 34 35 36 37

0 1 2 3 4 5 6 7 20 21 22 23 24 25 26 27
FX2N-64MR 10 11 12 13 14 15 16 17 30 31 32 33 34 35 36 37

Y0 Y2 Y4 Y6 Y10 Y12 Y14 Y16 Y20 Y22 Y24 Y26 Y30 Y32 Y34 Y36 COM6
COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y11 Y13 COM4 Y15 Y17 COM5 Y21 Y23 Y25 Y27 Y31 Y33 Y35 Y37

FX2N-64MR-ES/UL Y0 Y2 Y4 Y6 Y10 Y12 Y14 Y16 Y20 Y22 Y24 Y26 Y30 Y32 Y34 Y36 COM6
COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y11 Y13 COM4 Y15 Y17 COM5 Y21 Y23 Y25 Y27 Y31 Y33 Y35 Y37

FX2N-64MR-DS Y0 Y2 Y4 Y6 Y10 Y12 Y14 Y16 Y20 Y22 Y24 Y26 Y30 Y32 Y34 Y36 COM6
COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y11 Y13 COM4 Y15 Y17 COM5 Y21 Y23 Y25 Y27 Y31 Y33 Y35 Y37

FX2N-64MT-ESS/UL
Y0 Y2 Y4 Y6 Y10 Y12 Y14 Y16 Y20 Y22 Y24 Y26 Y30 Y32 Y34 Y36 +V5
+V0 Y1 Y3 +V1 Y5 Y7 +V2 Y11 Y13 +V3 Y15 Y17 +V4 Y21 Y23 Y25 Y27 Y31 Y33 Y35 Y37

FX2N-64MT-DSS
Y0 Y2 Y4 Y6 Y10 Y12 Y14 Y16 Y20 Y22 Y24 Y26 Y30 Y32 Y34 Y36 +V5
+V0 Y1 Y3 +V1 Y5 Y7 +V2 Y11 Y13 +V3 Y15 Y17 +V4 Y21 Y23 Y25 Y27 Y31 Y33 Y35 Y37

FX2N-80MT-DSS
S/S 0V 0V X0 X2 X4 X6 X10 X12 X14 X16 X20 X22 X24 X26 X30 X32 X34 X36 X40 X42 X44 X46
24V 24V X1 X3 X5 X7 X11 X13 X15 X17 X21 X23 X25 X27 X31 X33 X35 X37 X41 X43 X45 X47

FX2N-80MT-ESS/UL
S/S 0V 0V X0 X2 X4 X6 X10 X12 X14 X16 X20 X22 X24 X26 X30 X32 X34 X36 X40 X42 X44 X46
L N 24V 24V X1 X3 X5 X7 X11 X13 X15 X17 X21 X23 X25 X27 X31 X33 X35 X37 X41 X43 X45 X47

FX2N-80MR-DS
S/S 0V 0V X0 X2 X4 X6 X10 X12 X14 X16 X20 X22 X24 X26 X30 X32 X34 X36 X40 X42 X44 X46
24V 24V X1 X3 X5 X7 X11 X13 X15 X17 X21 X23 X25 X27 X31 X33 X35 X37 X41 X43 X45 X47

FX2N-80MR-ES/UL S/S 0V 0V X0 X2 X4 X6 X10 X12 X14 X16 X20 X22 X24 X26 X30 X32 X34 X36 X40 X42 X44 X46
L N 24V 24V X1 X3 X5 X7 X11 X13 X15 X17 X21 X23 X25 X27 X31 X33 X35 X37 X41 X43 X45 X47

FX2N-80MR-ES/UL Y0 Y2 Y4 Y6 Y10 Y12 Y14 Y16 Y20 Y22 Y24 Y26 Y30 Y32 Y34 Y36 Y40 Y42 Y44 Y46
COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y11 Y13 COM4 Y15 Y17 COM5 Y21 Y23 Y25 Y27 COM6 Y31 Y33 Y35 Y37 COM7 Y41 Y43 Y45 Y47

FX2N-80MR-DS Y0 Y2 Y4 Y6 Y10 Y12 Y14 Y16 Y20 Y22 Y24 Y26 Y30 Y32 Y34 Y36 Y40 Y42 Y44 Y46
COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y11 Y13 COM4 Y15 Y17 COM5 Y21 Y23 Y25 Y27 COM6 Y31 Y33 Y35 Y37 COM7 Y41 Y43 Y45 Y47

FX2N-80MT-ESS/UL
Y0 Y2 Y4 Y6 Y10 Y12 Y14 Y16 Y20 Y22 Y24 Y26 Y30 Y32 Y34 Y36 Y40 Y42 Y44 Y46
+V0 Y1 Y3 +V1 Y5 Y7 +V2 Y11 Y13 +V3 Y15 Y17 +V4 Y21 Y23 Y25 Y27 +V5 Y31 Y33 Y35 Y37 +V6 Y41 Y43 Y45 Y47

FX2N-80MT-DSS
Y0 Y2 Y4 Y6 Y10 Y12 Y14 Y16 Y20 Y22 Y24 Y26 Y30 Y32 Y34 Y36 Y40 Y42 Y44 Y46
+V0 Y1 Y3 +V1 Y5 Y7 +V2 Y11 Y13 +V3 Y15 Y17 +V4 Y21 Y23 Y25 Y27 +V5 Y31 Y33 Y35 Y37 +V6 Y41 Y43 Y45 Y47

58
Terminal Assignment

FX2N-128MT-ESS/UL
S/S 0V 0V X0 X2 X4 X6 X10 X12 X14 X16 X20 X22 X24 X26 X30 X32 X34 X36 X40 X42 X44 X46 X50 X52 X54 X56 X60 X62 X64 X66 X70 X72 X74 X76
L N 24V 24V X1 X3 X5 X7 X11 X13 X15 X17 X21 X23 X25 X27 X31 X33 X35 X37 X41 X43 X45 X47 X51 X53 X55 X57 X61 X63 X65 X67 X71 X73 X75 X77

FX2N-128MR-ES/UL S/S 0V 0V X0 X2 X4 X6 X10 X12 X14 X16 X20 X22 X24 X26 X30 X32 X34 X36 X40 X42 X44 X46 X50 X52 X54 X56 X60 X62 X64 X66 X70 X72 X74 X76
L N 24V 24V X1 X3 X5 X7 X11 X13 X15 X17 X21 X23 X25 X27 X31 X33 X35 X37 X41 X43 X45 X47 X51 X53 X55 X57 X61 X63 X65 X67 X71 X73 X75 X77

S/S 0V 0V X0 X2 X4 X6 X10 X12 X14 X16 X20 X22 X24 X26 X30 X32 X34 X36 X40 X42 X44 X46 X50 X52 X54 X56 X60 X62 X64 X66 X70 X72 X74 X76
L N 24V 24V X1 X3 X5 X7 X11 X13 X15 X17 X21 X23 X25 X27 X31 X33 X35 X37 X41 X43 X45 X47 X51 X53 X55 X57 X61 X63 X65 X67 X71 X73 X75 X77

0 1 2 3 4 5 6 7 20 21 22 23 24 25 26 27 40 41 42 43 44 45 46 47 60 61 62 63 64 65 66 67

10 11 12 13 14 15 16 17 30 31 32 33 34 35 36 37 50 51 52 53 54 55 56 57 70 71 72 73 74 75 76 77

0 1 2 3 4 5 6 7 20 21 22 23 24 25 26 27 40 41 42 43 44 45 46 47 60 61 62 63 64 65 66 67
FX2N-128MR 10 11 12 13 14 15 16 17 30 31 32 33 34 35 36 37 50 51 52 53 54 55 56 57 70 71 72 73 74 75 76 77

FX2N-128MR-ES/UL Y0 Y2 COM2 Y5 Y7 Y10 Y12 COM4 Y15 Y17 Y20 Y22 Y24 Y26 COM6 Y31 Y33 Y35 Y37 Y40 Y42 Y44 Y46 COM8 Y51 Y53 Y55 Y57 Y60 Y62 Y64 Y66 COM10 Y71 Y73 Y75 Y77
COM1 Y1 Y3 Y4 Y6 COM3 Y11 Y13 Y14 Y16 COM5 Y21 Y23 Y25 Y27 Y30 Y32 Y34 Y36 COM7 Y41 Y43 Y45 Y47 Y50 Y52 Y54 Y56 COM9 Y61 Y63 Y65 Y67 Y70 Y72 Y74 Y76

FX2N-128MT-ESS/UL
Y0 Y2 +V1 Y5 Y7 Y10 Y12 +V3 Y15 Y17 Y20 Y22 Y24 Y26 +V5 Y31 Y33 Y35 Y37 Y40 Y42 Y44 Y46 +V7 Y51 Y53 Y55 Y57 Y60 Y62 Y64 Y66 +V9 Y71 Y73 Y75 Y77
+V0 Y1 Y3 Y4 Y6 +V2 Y11 Y13 Y14 Y16 +V4 Y21 Y23 Y25 Y27 Y30 Y32 Y34 Y36 +V6 Y41 Y43 Y45 Y47 Y50 Y52 Y54 Y56 +V8 Y61 Y63 Y65 Y67 Y70 Y72 Y74 Y76
TERMINALS + DIMENSIONS

FX

59
BASICS
MELSEC FX0N/FX2N
MELSEC FX0N/FX2N
TERMINALS + DIMENSIONS Terminal Assignment

왎 Compact Extension Units MELSEC FX0N

FX
BASICS X3
FX0N-40ET-DSS
S/S S/S X1 X5 X7 X1 X3 X5 X7 X1 X3 X5 X7
+ X0 X2 X4 X6 X0 X2 X4 X6 X0 X2 X4 X6

FX0N-40ER-DS
COM COM X1 X3 X5 X7 X1 X3 X5 X7 X1 X3 X5 X7
+ X0 X2 X4 X6 X0 X2 X4 X6 X0 X2 X4 X6

FX0N-40ER-ES/UL
COM COM X1 X3 X5 X7 X1 X3 X5 X7 X1 X3 X5 X7
L N X0 X2 X4 X6 X0 X2 X4 X6 X0 X2 X4 X6

X1 X3 X5 X7 X1 X3 X5 X7

FX0N-40ER-ES/UL COM Y0 Y1 Y2 Y4 Y6 Y0 Y2 Y4 Y6
24V COM0 COM1 COM2 Y3 COM3 Y5 Y7 COM4 Y1 Y3 COM5 Y5 Y7

FX0N-40ER-DS COM Y0 Y1 Y2 Y4 Y6 Y0 Y2 Y4 Y6
24V COM0 COM1 COM2 Y3 COM3 Y5 Y7 COM4 Y1 Y3 COM5 Y5 Y7

FX0N-40ET-DSS COM Y0 Y1 Y2 Y4 Y6 Y0 Y2 Y4 Y6
24V +V0 +V1 +V2 Y3 +V3 Y5 Y7 +V4 Y1 Y3 +V5 Y5 Y7

왎 Modular Extension Units MELSEC FX0N

FX0N-8EYT-ESS/UL +V0 Y1 Y3 +V1 Y5 Y7


Y0 Y2 Y4 Y6
FX0N-16EYT-ES/UL +V0 Y1 Y3 +V1 Y5 Y7
Y0 Y2 Y4 Y6 FX0N-8EYR-ES/UL COM1 Y1 Y3 COM2 Y5 Y7
Y0 Y2 Y4 Y6
COM1 Y1 Y3 COM2 Y5 Y7
FX0N-16EYR-ES/UL
Y0 Y2 Y4 Y6 S/S X1 X3 X5 X7
FX0N-8EX-ES/UL
X0 X2 X4 X6
FX0N-16EX-ES/UL
S/S X1 X3 X5 X7
X0 X2 X4 X6 S/S X1 X3 COM Y1 Y3
FX0N-8ER-ES/UL
X0 X2 Y0 Y2

S/S X1 X3 X5 X7
X0 X2 X4 X6

POWER

IN 0 1 2 3 4 5 6 7

0 1 2 3 4 5 6 7

X0 X2 X4 X6
X1 X3 X5 X7

FX0N-16EX-ES/UL
X0 X2 X4 X6
X1 X3 X5 X7

FX0N-16EYR-ES/UL
Y0 Y2 Y4 Y6
COM3 Y1 Y3 COM4 Y5 Y7

FX0N-16EYT-ES/UL Y0 Y2 Y4 Y6
+V2 Y1 Y3 +V3 Y5 Y7

60
MELSEC FX0N/FX2N
Terminal Assignment TERMINALS + DIMENSIONS

왎 Compact Extension Units MELSEC FX2N

FX
BASICS

FX2N-32ET-ESS/UL
S/S 0V X0 X2 X4 X6 X0 X2 X4 X6
L N 24V X1 X3 X5 X7 X1 X3 X5 X7

FX2N-32ER-ES/UL S/S 0V X0 X2 X4 X6 X0 X2 X4 X6
L N 24V X1 X3 X5 X7 X1 X3 X5 X7

S/S 0V X0 X2 X4 X6 X0 X2 X4 X6
L N 24+ X1 X3 X5 X7 X1 X3 X5 X7

0 1 2 3 4 5 6 7
IN
10 11 12 13 14 15 16 17
POWER

RUN

BATT.V

0 1 2 3 4 5 6 7 PROG-E
OUT
FX 2N-32ER 10 11 12 13 14 15 16 17 CPU-E

Y0 Y2 Y4 Y6 Y10 Y12 Y14 Y16


COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y11 Y13 COM4 Y15 Y17

FX2N-32ER-ES/UL Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6
COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y1 Y3 COM4 Y5 Y7

FX2N-32ET-ESS/UL
Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6
+V0 Y1 Y3 +V1 Y5 Y7 +V2 Y1 Y3 +V3 Y5 Y7

FX2N-48ET-DS
S/S 0V X0 X2 X4 X6 X0 X2 X4 X6 X0 X2 X4 X6
24V X1 X3 X5 X7 X1 X3 X5 X7 X1 X3 X5 X7

FX2N-48ET-ES/UL
S/S 0V X0 X2 X4 X6 X0 X2 X4 X6 X0 X2 X4 X6
L N 24V X1 X3 X5 X7 X1 X3 X5 X7 X1 X3 X5 X7

FX2N-48ER-DS
S/S 0V X0 X2 X4 X6 X0 X2 X4 X6 X0 X2 X4 X6
24V X1 X3 X5 X7 X1 X3 X5 X7 X1 X3 X5 X7

FX2N-48ER-ES/UL S/S 0V X0 X2 X4 X6 X0 X2 X4 X6 X0 X2 X4 X6
L N 24V X1 X3 X5 X7 X1 X3 X5 X7 X1 X3 X5 X7

FX2N-48ER

FX2N-48ER-ES/UL Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6 COM5
COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y1 Y3 COM4 Y5 Y7 Y1 Y3 Y5 Y7

FX2N-48ER-DS
Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6 COM5
COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y1 Y3 COM4 Y5 Y7 Y1 Y3 Y5 Y7

FX2N-48ET-ES/UL
Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6 +V4
+V0 Y1 Y3 +V1 Y5 Y7 +V2 Y1 Y3 +V3 Y5 Y7 Y1 Y3 Y5 Y7

FX2N-48ET-DS
Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6 Y0 Y2 Y4 Y6 +V4
+V0 Y1 Y3 +V1 Y5 Y7 +V2 Y1 Y3 +V3 Y5 Y7 Y1 Y3 Y5 Y7

61
MELSEC FX0N/FX2N
TERMINALS + DIMENSIONS Terminal Assignment

왎 Modular Extension Units MELSEC FX2N


FX
BASICS

FX2N-16EX-ES/UL FX2N-16EYT-ESS/UL

IN 0 OUT 0
S/S

S/S
1

+V0
2
1 +V0
X0

X0
2
Y0

Y0
3
X1

X1
3
Y1

Y1
4
4

X2
5 X2

Y2
5 Y2
6
X3
X3 6

Y3
7 Y3
X4
7
X4

Y4
Y4
X5
X5

Y5
POWER Y5
POWER
X6

X6

Y6
Y6
X7

Y7
X7 Y7
X0

Y0
X0 Y0
X1

FX 2N -16EX

Y1
X1 FX 2N -16EYT Y1
X2

Y2
X2
X3

Y2

Y3
IN 0 X3 Y3
X4

OUT 0

Y4
1
X4
X5

1
Y4

Y5
2
2
3 X5 Y5
X6

Y6
4
X7

X6 4

Y7
5 Y6
6 X7 5
Y7

+V1
ES

6
7
7
+V1

FX2N-16EYR-ES/UL

OUT 0
COM1 Y1

1 COM1
2
Y0
Y0 Y2

3
4 Y1
5 Y2
6
Y3

7
Y3
Y4

Y4
Y5

Y5
POWER
Y6

Y6
Y7

Y7
Y0

Y0
Y1

FX 2N -16EYR Y1
Y2

Y2
Y3

OUT 0 Y3
Y4

1
Y4
Y5

2
3 Y5
Y6 COM2

4
Y7

5
Y6
6 Y7
7
COM2

62
MELSEC FX0N/FX2N
Terminal Assignment TERMINALS + DIMENSIONS

왎 Special Function Modules MELSEC FX0N / FX2N


FX
BASICS

FX0N-16NT 24 + 24G FG SDA SDB SG FX0N-3A


V IN 2 I IN 2 COM V OUT
24 + 24G ECM RDA RDB SG V IN 1 I IN 1 COM I OUT COM

FX0N-485ADP 24 + 24G FG SDA SDB SG FX0N-32NT-DP


24G
24 + 24G FG RDA RDB SG 24+ FG

24+ FG
24G
POWER DC RUN

BF DIA

FX2N-232IF
24+ 24-

FX0N-232ADP
24+ 24-

FX 2N -232IF
POWER
SD
RD

FX 2N -232IF

63
MELSEC FX0N/FX2N
TERMINALS + DIMENSIONS Terminal Assignment

왎 Special Function Modules MELSEC FX2N


FX
BASICS

24+ 24+
24- 24-
24+

24+
24-

24-
V+ V+
CH1

CH1
VI- VI-
V+

V+
VI-

VI-
I+ I+
I+

I+
POWER POWER
FG
FG

V+ V+
CH2

CH2
V+

V+
VI- VI-
VI-

VI-
I+ I+
I+

I+
FG
FG
CH3

CH3
V+ V+
V+

V+
FX 2N -4AD FX 2N -4DA
VI-

VI-
VI- VI-
FX2N-4AD

FX2N-4DA
I+

I+
I+ I+
FG

FG
CH4

CH4
V+

V+
VI-

VI-
24 V V+ 24 V V+
VI- VI-
I+

I+
A/D D/A
I+ I+

24+ 24+
24- 24-
24+

24+
24-

24-
SLD I-
CH1

CH1
L+ L+
SLD

I-
L- L-

L+
L+
L-

L-
POWER POWER
FG

FG
SLD I-
CH2

CH2
SLD

I-
L+ L+ L+
L+

L- L-
L-

FG L-
FG
CH3
CH3

SLD

SLD I-
I-

FX 2N-4AD-TC FX 2N-4AD-PT
L+
L+

L+ L+
FX2N-4AD-TC

FX2N-4AD-PT
L-
L-

L- L-
FG

FG
CH4
CH4

SLD

I-

SLD I-
L+

L+

24 V 24 V
L+ L+
L-

L-

A/D A/D
L- L-

UP A12+ VIN
VIN FP PG0-
COM0 RP PG0+

A24+ COM0
A12+ A- B12+

DOWN
A- FP
A24+ A5+ B24+

A A5+ RP
B B12+ PG0-
B24+ PG0+
POWER
FX 2N -1PG 1PG
B-
B-

POWER
B5+
B5+ XD24 XP24

POWER
XD5
XD5 COMD

S
T D P
XD24 O O G
P G O
COMD
XP24
FX 2N -1HC F R C E
P P L R
COMP YH- YS-

R R
COM1 S/S S/S

COMP COM1
FX2N-1HC
XP5 YH+ YS+

CLR STOP DOG

DIS
XP5 CLR
PRE YH- S/S
YH YH+ STOP
YS- S/S
YS
YS+ DOG

64
MELSEC FX0N/FX2N
Terminal Assignment TERMINALS + DIMENSIONS

왎 Special Function Modules MELSEC FX


FX
BASICS

24G 24G
FX-16NT FX-16NP
+24 FG 24+ FG

FX-16NT
RDB SDB
RDA SDA SG

+24 24G FG +24 24G FG


FX-16NT-S3 FX-16NP-S3
+24 24G FG +24 24G FG

FX-16NT-S3
SDA SDB
RDA RDB SG

65
MELSEC FX0N/FX2N
TERMINALS + DIMENSIONS Dimensions

Dimensions of Base Units and Compact Extension Units MELSEC FX0N


FX
BASICS
X 87
X -10 Type X (in mm)
FX0N-24MR-DS 130
FX0N-24MR-ES/UL 130
FX0N-24MT-DSS 130
MITSUBISHI
FX0N-40MR-DS 150
FX0N-40MR-ES/UL 150

80
35
90

FX0N-40MT-DSS 150
MELSEC FX0N-24MR-ES
FX0N-60MR-DS 185
FX0N-60MR-ES/UL 185
FX0N-60MT-DSS 185
FX0N-40ER-DS 150
ø4,5
FX0N-40ER-ES/UL 150

Dimensions of Modular Extension Units and Special Function Modules MELSEC FX0N

X 87
ø4,5 Type X (in mm)
FX0N- 8ER-ES/UL 43
FX0N-8EX-ES/UL 43
FX0N-8EYR-ES/UL 43
_
FXON 16NT FX0N-8EYT-ESS/UL 43
POWER
90
80

35

POWER - DC - RUN - ERR.


FX0N-16EX-ES/UL 70
FX0N-16EYR-ES/UL 70
FX0N-16EYT-ES/UL 70
FX0N-232ADP 43
FX0N-3A 43
4 FX0N-16NT 43
FX0N-32NT-DP 43
FX0N-485ADP 43

66
MELSEC FX0N/FX2N
Dimensions TERMINALS + DIMENSIONS

Dimensions of Base Units MELSEC FX2N


FX
BASICS

X 87 Base Units
X -10
Type X (in mm)
FX2N-16M 130
FX2N-32M 150
S/S 0V X0 X2 X4 X6 X0 X2 X4 X6
L N 24+ X1 X3 X5 X7 X1 X3 X5 X7 FX2N-48M 182
0 1 2 3 4 5 6 7
IN
10 11 12 13 14 15 16 17
POWER
FX2N-64M 220

80

35
RUN
90

BATT.V
FX2N-80M 285
0 1 2 3 4 5 6 7 PROG-E

FX 2N-32ER
OUT
10 11 12 13 14 15 16 17 CPU-E
FX2N-128M 350
Y0 Y2 Y4 Y6 Y10 Y12 Y14 Y16
COM1 Y1 Y3 COM2 Y5 Y7 COM3 Y11 Y13 COM4 Y15 Y17

ø4,5

Dimensions of Compact and Modular Extension Units MELSEC FX2N

X 87 Compact Extension Units


ø4,5 Type X (in mm)
IN 0
FX2N-32ER-ES/UL 150
1
2
3
4
FX2N-32ET-ESS/UL 150
5
6
7 FX2N-48ER-DS 182
POWER
FX2N-48ER-ES/UL 182
90
80

35

FX2N-48ET-DSS 182
FX 2N-16EX

IN 0
1
Modular Extension Units
2
3
4
5
Type X (in mm)
6
7
FX2N-16EX-ES/UL 40
4 FX2N-16EYR-ES/UL 40
FX2N-16EYT-ESS/UL 40

67
MELSEC FX0N/FX2N
TERMINALS + DIMENSIONS Dimensions

Dimensions of Special Function Modules MELSEC FX2N


FX
BASICS
X 87 Special Function Modules FX2N
ø4,5 Type X (in mm)
FX2N- 4DA 55
FX2N-4AD 55
FX2N-4AD-TC 55
POWER
FX2N-4AD-PT 55
90
80

35 FX2N-1HC 55
FX 2N-4AD FX2N-1PG-E 43
FX2N-232-IF 55
24 V
A/D

Dimensions of Special Function Modules MELSEC FX

A C Special Function Modules FX


Type A x B x C (in mm)
FX-16NP, FX-16NT 45 x 140 x 95
FX-16NP-S3, FX-16NT-S3 73 x 140 x 95
35
B

68
MELSEC FX0N/FX2N
Dimensions TERMINALS + DIMENSIONS

FX
BASICS

69
MELSEC FX
PROGRAMMING Software

Programming and Documentation Software for Standard Personal Computers

With MELSEC MEDOC, MELSEC MEDOC efficient programming and documenta- To take account of the importance of pro-
FX FX/WIN and MELSEC MEDOC plus, tion system for all controllers of the gramming, all program packages permit
BASICS MITSUBISHI ELECTRIC offers a program- MELSEC FX series. efficient and time-saving programming.
ming and documentation system which
makes your personal computer into an

왎 MELSEC MEDOC
In MELSEC MEDOC, convenient editing By connecting a standard printer, it is pos-
functions are accessible through a clearly sible to produce input/output lists and
laid out menu. cross reference lists for documen-
The fast, convenient creation and pro- tation.
cessing of PLC programs are performed The software is supplied complete with
by means of either a contact plan or a list an SC-09N serial interface cable for
of instructions. connecting the PLC to one of the PC’s
In addition to versatile monitor and test serial ports.
functions, MELSEC MEDOC has an
extensive Help menu.

Software F-Set E 3,5" F-Set G 3,5" FX0-Set E FX0-Set G


Series FX,FX0, FX,FX0, FX0,FX0S FX0,FX0S
FX0S,FX0N FX0S,FX0N
Language English German English German
Format 3,5" 3,5" 3,5" / 5,25" 3,5" / 5,25"

Order information Art. no. 56123 56124 32712 32787

왎 MELSEC MEDOC FX/WIN


MELSEC MEDOC FX/WIN is the standard The software is supplied complete with
programming software for the MELSEC FX an SC-09N serial interface cable, which is
familiy and combines all functions of used for the connection between the PLC
MELSEC MEDOC with the user guidance and a serial interface of a personal computer.
of Microsoft Windows®. MELSEC MEDOC plus can be run under
MELSEC MEDOC FX/WINprovides the user Windows 3.11 and Windows 95.
with facilities for structured program-
ming, function modules and many
Software MM FX/WIN
different diagnostic functions.
Series Whole FX family
This software posseses all Windows®-spe-
Language Englisch
cific benefits and is especially geared to
Format 3,5" diskettes
the new FX2N series.
Order information Art. no. 70536

왎 MELSEC MEDOC plus


MELSEC MEDOC plus provides all func- MELSEC MEDOC plus can be run under
tions of the pre-mentioned programs and Windows 3.11 and Windows 95.
meets the programming standard for the The software is supplied complete with
future: IEC 1131.3. This makes MELSEC an SC-09N serial interface cable.
MEDOC plus ready for the programming
standard of the future and offers in addi-
tion the basis for the on-leading program-
ming of the MELSEC A and Q series.

Software F-Set E F-Set G


Series Whole FX family Whole FX family
Language English German
Format 3,5" diskettes 3,5" diskettes

Order information Art. no. 56118 56117

70 MITSUBISHI ELECTRIC
MELSEC FX
Software PROGRAMMING

Parameter Software for Profibus Networks and Process Supervision System for all Mitsubishi PLCs

FX
BASICS

왎 MELSEC ProfiMap

MELSEC ProfiMap V2.0 is a user friendly Due to the supported extended user
configurations software for open net- parameters of a GSD file, easy parameter
works like MAP 3.0/ETHERNET and setting of PROFIBUS/DP slave devices is
PROFIBUS/DP or PROFIBUS/FMS. possible even for third party devices.
The software package is a 32 bit applica-
tion for Windows 95 and Windows NT4.0.
Configuration of all PROFIBUS modules
for the MELSEC series is possible.

Software Full version V2.0 Update V1.0 to V2.0


Supported master modules for the Mitsubishi Profibus/DP: A1SJ71PB92D,AJ71PB92D
Profibus/FMS:A1SJ71PB96F,AJ71PB96F
Profibus/DP: A1SJ71PB92D,AJ71PB92D
Profibus/FMS: A1SJ71PB96F,AJ71PB96F
MELSEC AnS/QnAS and A/Q series MAP3.0/Ethernet: AJ71M56EF2 MAP3.0/Ethernet: AJ71M56EF2
Language English English
Configuration cable ProfiCab is included ProfiCab is not included
Disk type 3,5" disks 3,5" disks
Order information Art. no. 102996 102997

왎 MELSEC MX SCADA

MELSEC MX SCADA is a process visualisa- jects. A variety of interfaces are sup-


tion system that can handle everything ported, including ETHERNET. The software
from simple installations to complex pro- runs under Windows 95 and Windows NT
duction control systems. The software and is available in a variety of different
package can administer up to 100000 ob-

Software Development version Run-time version DEMO version


Series All MELSEC PLC All MELSEC PLC All MELSEC PLC
Language Englisch Englisch Englisch
Disk type CD ROM CD ROM CD ROM

Order information Art. no. on request on request 65135

MITSUBISHI ELECTRIC 71
MELSEC FX
PROGRAMMING Hand-Held Programming Units – Cables – EPROM Writer

왎 Hand-Held Programming Unit FX-10 P-E and FX-20 P-E

These small hand-held programming units This ensures storage of the PLC program
FX designed for industry have a user-friendly and its duplication, for example for se-
BASICS keyboard and a clearly laid out, back-lit LC ries machines.
display. On both programming units, the
MELSEC FX family is programmed in the list
of instructions. The FX-20P has an inte-
grated CMOS-RAM with capacitor buffering.

Specifications FX-10 P-E FX-20 P-E


General specifications Conforms to base units FX2N,FX0N,FX0S
Ambient temperature 0 – 40 °C 0 – 40 °C
Ambient relative humidity 35 – 85 % 35 – 85 %
(non-condensing)
Power supply V DC 5 ±5 % by PLC DC 5 ±5 % by PLC
Current consumption mA 120 150
Display LCD LCD (backlight)
Character display 16 x 2 16 x 4
Connectable PLC FX0,FX0S,FX,FX0N,FX2N* FX0,FX0S,FX,FX0N,FX2N*
Key board keys 35 35
Memory — 8000 steps PLC-program
Data security — Data is safed up to 3 days by capacitor.
Cable, is adjoint — FX-20P-CAB
Weight kg 0.25 0.4
Dimensions(WxHxD) mm 85x160x27 90 x 170 x 30

Order information Art. no. 32538 23802


*Version 3.0 or higher

왎 Connection Cable and Adapter Cable

With the adapter cable FX-20P-CADP, the


peripheral units of the FX series are con-
nected to units of the FX0, FX0S and FX0N
series.

Data FX-20P-CAB FX-20P-CAB0 FX-20P-CABP


Cable type Connection cable Connection cable Adapter cable
Length cm 150 300 20
For connecting to controller FX FX0S,FX2N,FX0N FX0S,FX2N,FX0N

Order information Art. no. 30815 55917 31870

왎 EPROM Writer FX-20 P-RWM

The EPROM writer FX-20 P-RWM is plugged from the FX-EPROM-8 memory cassette
PO
W ER
directly into the hand-held programming into the CMOS-RAM of the controller
WR
ITE

unit FX-20 P-E. It is used for transferring the and program comparisons carried out.
WM
PLC programs of the MELSEC FX controller
0P-R
FX-2 to the EPROM memory cassette FX-EPROM-8.
Conversely, existing programs can be read

Data FX-20 P-RWM

Order information Art. no. 23818

72 MITSUBISHI ELECTRIC
MELSEC FX
PROFIBUS Connector PROGRAMMING

왎 ProfiCon Profibus Connector


The ProfiCon bus connector plug is de-
signed for connecting DIN 19245 standard
FX
Profibus components with data transfer BASICS

rates of up to 12 Mbaud.
on

The connector is available with or without a


ProfiC

selectable termination resistor.

Specifications ProfiCon ProfiConT


Data rate 12 Mbit/s supported supported
Terminator No Yes (selectable)

Order information Art. no. 64127 87035

MITSUBISHI ELECTRIC 73
MELSEC FX

ORDER FORM

MITSUBISHI ELECTRIC EUROPE B.V. Company: . . . . . . . . . . . . . . . . . . . . . .


Factory-Automation / German Branch Department: . . . . . . . . . . . . . . . . . . . . . .
Gothaer Str. 8 Street: . . . . . . . . . . . . . . . . . . . . . .
D-40880 Ratingen Address: . . . . . . . . . . . . . . . . . . . . . .
Phone: . . . . . . . . . . . . . . . . . . . . . .
Fax: +49 2102 486-717 Fax: . . . . . . . . . . . . . . . . . . . . . .

Order declaration
Pos. Number Item (type) Article number Description Remarks

Notes when ordering:


When ordering, please use only the type designations and order numbers shown in this catalogue.

74 MITSUBISHI ELECTRIC
MELSEC FX
INDEX

Adapter cable . . . . . . . . . . . . . . . . . . . . . . . . . 72 FX0N-40B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 General specifications


FX0N-40ER-DS . . . . . . . . . . . . . . . . . . . . . . . . 32 FX0S series . . . . . . . . . . . . . . . . . . . . . . . . . 12
Base units FX0N-40ER-ES/UL . . . . . . . . . . . . . . . . . . . . . 32 FX0N/FX2N series . . . . . . . . . . . . . . . . . . 25
FX0S series . . . . . . . . . . . . . . . . . . . . . . . . 12 FX0N-40ET-DSS . . . . . . . . . . . . . . . . . . . . . . . 32
FX0N series . . . . . . . . . . . . . . . . . . . . . . . . 26 FX0N-40MR-DS. . . . . . . . . . . . . . . . . . . . . . . . 26 Input-SIM: FX0S/FX0N . . . . . . . . . . . . . . . . . . 14
FX2N series . . . . . . . . . . . . . . . . . . . . . . . . 28 FX0N-40MR-ES/UL. . . . . . . . . . . . . . . . . . . . . 26 Input-SIM: FX2N. . . . . . . . . . . . . . . . . . . . . . . . 53
Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 FX0N-40MT-DSS. . . . . . . . . . . . . . . . . . . . . . . 26 Interface converter . . . . . . . . . . . . . . . . . . . . . 52
FX0N-60MR-DS. . . . . . . . . . . . . . . . . . . . . . . . 27
Combination possibilities . . . . . . . . . . . . . . 21 FX0N-60MR-ES/UL. . . . . . . . . . . . . . . . . . . . . 27 MELSEC MEDOC. . . . . . . . . . . . . . . . . . . . . . . . 70
Compact extension units. . . . . . . . . . . . . . . 32 FX0N-60MT-DSS. . . . . . . . . . . . . . . . . . . . . . . 27 MELSEC MEDOC plus . . . . . . . . . . . . . . . . . . . 70
Connection cable. . . . . . . . . . . . . . . . . . . 55, 72 FX0N-232ADP . . . . . . . . . . . . . . . . . . . . . . . . . 40 MELSEC MEDOC plus tutorial . . . . . . . . . . . 70
Configuration FX0N/FX2N series . . . . . . . 24 FX0S-10MR-DS . . . . . . . . . . . . . . . . . . . . . . . . 12 MELSECNET/MINI . . . . . . . . . . . . . . . . . . . . . . 42
CR01-R2/R4 SET . . . . . . . . . . . . . . . . . . . . . . . 52 FX0S-10MR-ES/UL . . . . . . . . . . . . . . . . . . . . . 12 Memory cassettes . . . . . . . . . . . . . . . . . . . . . . 52
CR01-R4/R4 . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 FX0S-10MT-DSS . . . . . . . . . . . . . . . . . . . . . . . 12 Model designation code. . . . . . . . . . . . . . . . 11
FX0S-14MR-DS . . . . . . . . . . . . . . . . . . . . . . . . 12 Modular extension units . . . . . . . . . . . . . . . . 34
Description of units FX0S-14MR-ES/UL . . . . . . . . . . . . . . . . . . . . . 12 MX SCADA software . . . . . . . . . . . . . . . . . . . . 71
FX0S series . . . . . . . . . . . . . . . . . . . . . . . . 11 FX0S-14MT-DSS . . . . . . . . . . . . . . . . . . . . . . . 12
FX0N/FX2N series . . . . . . . . . . . . . . . . . . 20 FX0S-20MR-DS . . . . . . . . . . . . . . . . . . . . . . . . 13 Networks (overview) . . . . . . . . . . . . . . . . . . . . 8
Dimensions FX0S-20MR-ES/UL . . . . . . . . . . . . . . . . . . . . . 13 1:n multidrop . . . . . . . . . . . . . . . . . . . . . . 45
FX0S series . . . . . . . . . . . . . . . . . . . . . . . . 17 FX0S-20MT-DSS . . . . . . . . . . . . . . . . . . . . . . . 13 MELSECNET/MINI. . . . . . . . . . . . . . . . . . . 42
FX0N series . . . . . . . . . . . . . . . . . . . . . . . . 66 FX0S-30MR-DS . . . . . . . . . . . . . . . . . . . . . . . . 13 Parallel link. . . . . . . . . . . . . . . . . . . . . . . . . 45
FX2N series . . . . . . . . . . . . . . . . . . . . . . . . 67 FX0S-30MR-ES/UL . . . . . . . . . . . . . . . . . . . . . 13 Peer-to-peer . . . . . . . . . . . . . . . . . . . . . . . 45
Digital I/Os . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 FX0S-30MT-DSS . . . . . . . . . . . . . . . . . . . . . . . 13 PROFIBUS/DP . . . . . . . . . . . . . . . . . . . . . . 48
FX2N-1HC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
EPROM writer. . . . . . . . . . . . . . . . . . . . . . . . . . 72 FX2N-1PG-E . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Power consumption. . . . . . . . . . . . . . . . . . . . 23
EPROM/EEPROM cassettes . . . . . . . . . . . . . 52 FX2N-4AD. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 Profibus plug . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Extension units FX2N-4AD-PT . . . . . . . . . . . . . . . . . . . . . . . . . 38 ProfiMap software. . . . . . . . . . . . . . . . . . . . . . 71
compact. . . . . . . . . . . . . . . . . . . . . . . . . . . 32 FX2N-4AD-TC . . . . . . . . . . . . . . . . . . . . . . . . . 38 Programming units. . . . . . . . . . . . . . . . . . . . . 72
modular . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 FX2N-4DA. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 Programm loader . . . . . . . . . . . . . . . . . . . . . . 15
FX2N-8AV-BD . . . . . . . . . . . . . . . . . . . . . . . . . 36 PROM adapter . . . . . . . . . . . . . . . . . . . . . . . . . 53
F2-40BL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 FX2N-16EX-ES/UL . . . . . . . . . . . . . . . . . . . . . 35
FX-10 P-E. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72 FX2N-16EYR-ES/UL . . . . . . . . . . . . . . . . . . . . 35 Real-time clock cassette . . . . . . . . . . . . . . . . 52
FX-16NP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 FX2N-16EYT-ES/UL . . . . . . . . . . . . . . . . . . . . 35
FX-16NP-S3 . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 FX2N-16MR-ES/UL. . . . . . . . . . . . . . . . . . . . . 28 Simulation box. . . . . . . . . . . . . . . . . . . . . 14, 53
FX-16NT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 FX2N-16MT-ESS/UL. . . . . . . . . . . . . . . . . . . . 28 Simulation strip . . . . . . . . . . . . . . . . . . . . 14, 53
FX-16NT-S3. . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 FX2N-32ER-ES/UL . . . . . . . . . . . . . . . . . . . . . 33 Special function modules
FX-20 P-CAB . . . . . . . . . . . . . . . . . . . . . . . . . . . 72 FX2N-32ET-ESS/UL . . . . . . . . . . . . . . . . . . . . 33 analog modules . . . . . . . . . . . . . . . . . . . . 36
FX-20 P-CAB0. . . . . . . . . . . . . . . . . . . . . . . . . . 72 FX2N-32MR-DS. . . . . . . . . . . . . . . . . . . . . . . . 28 common description . . . . . . . . . . . . . . . 22
FX-20 P-CABP. . . . . . . . . . . . . . . . . . . . . . . . . . 72 FX2N-32MR-ES/UL. . . . . . . . . . . . . . . . . . . . . 28 communications modules . . . 43, 46, 50
FX-20 P-E. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72 FX2N-32MT-DSS. . . . . . . . . . . . . . . . . . . . . . . 28 PROFIBUS modules . . . . . . . . . . . . . . . . . 49
FX-20 P-RWM. . . . . . . . . . . . . . . . . . . . . . . . . . 72 FX2N-32MT-ESS/UL. . . . . . . . . . . . . . . . . . . . 28 interface modules . . . . . . . . . . . . . . 40, 46
FX-65EC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 FX2N-48ER-DS . . . . . . . . . . . . . . . . . . . . . . . . 33 counter/positioning modules . . . . . . . 39
FX-485PC-IF . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 FX2N-48ER-ES/UL . . . . . . . . . . . . . . . . . . . . . 33 System description
FX-EPROM-8. . . . . . . . . . . . . . . . . . . . . . . . . . . 52 FX2N-48ET-DSS . . . . . . . . . . . . . . . . . . . . . . . 33 general . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
FX-EEPROM-4 . . . . . . . . . . . . . . . . . . . . . . . . . 52 FX2N-48ET-ESS/UL . . . . . . . . . . . . . . . . . . . . 33 FX0S series . . . . . . . . . . . . . . . . . . . . . . . . . 10
FX-EEPROM-4C . . . . . . . . . . . . . . . . . . . . . . . . 52 FX2N-48MR-DS. . . . . . . . . . . . . . . . . . . . . . . . 29 FX0N series . . . . . . . . . . . . . . . . . . . . . . . . 18
FX-EEPROM-8 . . . . . . . . . . . . . . . . . . . . . . . . . 52 FX2N-48MR-ES/UL. . . . . . . . . . . . . . . . . . . . . 29 FX2N series . . . . . . . . . . . . . . . . . . . . . . . . 19
FX-RAM-8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 FX2N-48MT-ESS/UL. . . . . . . . . . . . . . . . . . . . 29 System specifications
FX-RAM-8C . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 FX2N-48MT-DSS. . . . . . . . . . . . . . . . . . . . . . . 29 FX0S series . . . . . . . . . . . . . . . . . . . . . . . . . 13
FX-ROM SOC1 . . . . . . . . . . . . . . . . . . . . . . . . . 53 FX2N-64MR-DS. . . . . . . . . . . . . . . . . . . . . . . . 29 FX0N/FX2N series . . . . . . . . . . . . . . . . . . 25
FX-RTC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 FX2N-64MR-ES/UL. . . . . . . . . . . . . . . . . . . . . 29
FX0-10LDR . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 FX2N-64MT-DSS. . . . . . . . . . . . . . . . . . . . . . . 29 Terminal assignment
FX0N-3A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 FX2N-64MT-ESS/UL. . . . . . . . . . . . . . . . . . . . 29 FX0S series . . . . . . . . . . . . . . . . . . . . . . . . . 16
FX0N-8ER-ES/UL . . . . . . . . . . . . . . . . . . . . . . . 34 FX2N-80MR-DS. . . . . . . . . . . . . . . . . . . . . . . . 30 FX0N extension units . . . . . . . . . . . . . . . 60
FX0N-8EX-ES/UL . . . . . . . . . . . . . . . . . . . . . . . 34 FX2N-80MR-ES/UL. . . . . . . . . . . . . . . . . . . . . 30 FX2N extension units . . . . . . . . . . . . . . . 61
FX0N-8EYR-ES/UL. . . . . . . . . . . . . . . . . . . . . . 34 FX2N-80MT-ESS/UL. . . . . . . . . . . . . . . . . . . . 30 FX0N base units . . . . . . . . . . . . . . . . . . . . 56
FX0N-8EYT-ESS/UL. . . . . . . . . . . . . . . . . . . . . 34 FX2N-80MT-DSS. . . . . . . . . . . . . . . . . . . . . . . 30 FX2N base units . . . . . . . . . . . . . . . . . . . . 57
FX0N-16EX-ES/UL. . . . . . . . . . . . . . . . . . . . . . 34 FX2N-128MR-ES/UL . . . . . . . . . . . . . . . . . . . 30 Special function modules . . . . . . . . . . . 63
FX0N-16EYR-ES/UL . . . . . . . . . . . . . . . . . . . . 34 FX2N-128MT-ESS/UL . . . . . . . . . . . . . . . . . . 30
FX0N-16EYT-ESS/UL . . . . . . . . . . . . . . . . . . . 34 FX2N-232BD . . . . . . . . . . . . . . . . . . . . . . . . . . 41
FX0N-16NT . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 FX2N-232IF . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
FX0N-24MR-DS . . . . . . . . . . . . . . . . . . . . . . . . 26 FX2N-422BD . . . . . . . . . . . . . . . . . . . . . . . . . . 41
FX0N-24MR-ES/UL . . . . . . . . . . . . . . . . . . . . . 26 FX2N-485ADP . . . . . . . . . . . . . . . . . . . . . . . . . 46
FX0N-24MT-DSS . . . . . . . . . . . . . . . . . . . . . . . 26 FX2N-485BD . . . . . . . . . . . . . . . . . . . . . . . . . . 46
FX0N-32NT-DP . . . . . . . . . . . . . . . . . . . . . . . . 49 FX2N-CNV-BD . . . . . . . . . . . . . . . . . . . . . . . . . 50
FX2N-CNV-IF . . . . . . . . . . . . . . . . . . . . . . . . . . 50
FX2N-EEPROM-16 . . . . . . . . . . . . . . . . . . . . . 52

MITSUBISHI ELECTRIC 75
FA CENTER EUROPEAN REPRESENTATIVES EUROPEAN REPRESENTATIVES EUROPEAN REPRESENTATIVES
MITSUBISHI ELECTRIC JAPAN GEVA GmbH AUSTRIA MITSUBISHI ELECTRIC IRELAND GTS TURKEY
CORPORATION Wiener Straße 89 EUROPE B.V. – Irish Branch Fahri Gizden Sokak,
Mitsubishi Denki Bldg. A-2500 Baden Westgate Business Park Hacaloglu Apt. No. 22/6
Marunouchi Phone: (0 22 52) 8 55 52-0 IRL-Dublin 22 TR-80280 Gayrettepe/Istanbul
Tokyo 100 Fax: (0 22 52) 4 88 60 Phone: (1) 450 50 07 Phone: (2 12) 267 40 11
JAPAN Fax: (1) 456 13 37 Fax: (2 12) 266 14 50
Phone: (03) 3218-3176 GETRONICS NV/SA BELGIUM
Fax: (03) 3218-2422 Pontbeeklaan 43 CARPANETO & C. S.p.A. ITALY
B-1731 Zellik Via Ferrero 10
MITSUBISHI ELECTRIC EUROPE Phone: (02) 4 67 17 51 I-10090 Cascine Vica-Rivoli (TO)
EUROPE B.V. Fax: (02) 4 67 17 45 Phone: (0 11) 95 90 111 MIDDLEEASTREPRESENTATIVE
Factory Automation Fax: (0 11) 95 90 250
Gothaer Straße 8 INEA CR d.o.o. CROATIA TEXEL Electronics Ltd. ISRAEL
D-40880 Ratingen Drvinje bb Geveke Electronics bv NETHERLANDS P.O. Box 6272
Germany HR-10000 Zagreb Donauweg 10 IL-Netanya 42160
Phone: (0 21 02) 486-0 Phone: (01) 36 71 40 NL-1043 AJ-Amsterdam Phone: (09) 863 08 91
Fax: (0 21 02) 4 86-1 12 Fax: (01) 36 71 40 Phone: (0 20) 5 86 15 92 Fax: (09) 885 24 30
Fax: (0 20) 5 86 19 27
MITSUBISHI ELECTRIC EUROPE UK AUTOCONT s.r.o. CZECHIA
EUROPE B.V. Nemocnicni 12 Beijer Electronics A/S NORWAY
Industrial Division CZ-70100 Ostrava 1 Teglverksveien 1
Travellers Lane Phone: (0 69) 6 15 21 11 N-3002 Drammen
GB-Hatfield Herts. AL10 8 XB Fax: (0 69) 6 11 35 62 Phone: (32) 24 30 00
Fax: (32) 84 85 77
Great Britain ELPEFA A/S DENMARK
Phone: (0 17 07) 27 61 00 Geminivej 32 MPL Technology SP. Z.o.o POLAND
Fax: (0 17 07) 27 86 95 DK-2670 Greve ul. Wroclawska 53
MITSUBISHI ELECTRONICS USA Phone: (0 43) 95 95 95 PL-30011 Kraków
AMERICA, INC. Fax: (0 43) 95 95 90 Phone: (0 12) 632 28 85
Fax: (0 12) 632 47 82
Industrial Automation Division MITSUBISHI ELECTRIC ENGLAND
800 Biermann Court EUROPE B.V. – UK Branch F. Fonseca Lda PORTUGAL
Mt. Prospect, IL 60056 Travellers Lane Estrada de Taboeira 87/89, Esgueira
United States of America GB-Hatfield Herts. AL10 8 XB P-3800 Aveiro
Phone: (708) 298-9223 Phone: (0 17 07) 27 61 00 Phone: (0 34) 31 58 00
Fax: (708) 298-1834 Fax: (0 17 07) 27 86 95 Fax: (0 34) 31 58 04
Ryoden (Holdings) Ltd. HONG KONG UTU ELEKTROTEHNIKA ESTONIA TUINGDOR ROMANIA
10th Fl., Manulife T., Laki 12 E 20, Fierarilor Street
169 Electric Rd., N. Point EE-0006 Tallinn RO-72126 Bucaresti
Hong Kong Phone: (06) 563 194 Phone: (01) 211 98 01
Phone: 2887-8870 Fax: (06) 563 836 Fax: (01) 210 71 81
Fax: 2578-2461
Beijer Electronics OY FINLAND INEA d.o.o. SLOVENIA
P.T. SAHABAT INDONESIA INDONESIA Elannontie 5 Ljubljanska 80
Blok A/Utara No. 1 Kav, No. 11 FIN-01510 Vantaa SI-61230 Domzale
Jakarta 11050 Phone: (09) 615 20 11 Phone: (0 61) 71 80 00
Indonesia Fax: (09) 615 20 500 Fax: (0 61) 72 16 72
Phone: 6610651
Fax: 6603700 IP Systèmes FRANCE Medición y Control, S.A. SPAIN
8, Rue Colonel Chambonnet Gr. Via d. l. Corts Catalanes 133, 4
SETSUYO ENTERPRISE Co.,Ltd. TAIWAN F-69672 Lyon Bron E-08014 Barcelona
TAIWAN Phone: (04) 72 14 18 00 Phone: (03) 4 22 77 00
3rd Fl., No.122, Wu Kung 2nd Road Fax: (04) 72 14 18 01 Fax: (03) 4 32 28 47
Wu-Ku Hsiang Taipei Hsien
Taiwan MITSUBISHI ELECTRIC GERMANY Beijer Electronics AB SWEDEN
Phone: (02) 298 - 17 95 EUROPE B.V. – German Branch Box 325
Fax: (02) 298 - 18 25 Gothaer Straße 8 S-20123 Malmö
D-40880 Ratingen Phone: (0 40) 35 86 00
MITSUBISHI ELECTRIC SALE SINGAPORE Phone: (0 21 02) 486-0 Fax: (0 40) 93 23 01
SINGAPORE Pte. Ltd. Fax: (0 21 02) 4 86-1 12
Industrial Engineering Center ECONOTEC AG SWITZERLAND
No. 6, Commonwealth Lane #01 - 01 GEVA Kft HUNGARY Postfach 282
149547 Singapore Tamási Áron u. 34 CH-8309 Nürensdorf
Phone: 476 - 72 35 H-1124 Budapest Phone: (01) 838 48 11
Fax: 476 - 74 39 Phone: (01) 3 75 38 98 Fax: (01) 838 48 12
Fax: (01) 3 75 06 88

Specifications subject to change.


Art.no.68544-B,Printed in Germany 12.98 MITSUBISHI ELECTRIC EUROPE B.V. F AC TO R Y AU T O M A T I O N
GOTHAER STR. 8, D-40880 RATINGEN, TEL. (0 21 02) 4 86-0, FAX (0 21 02) 4 86-1 12
www.mitsubishi-automation.com