Digital Energy
Introduction:
   Advanced protection, control and communications
                         Protection, Control, Metering, Monitoring,
                         Analysis and Energy Management System
                         • Supports open communications
                           protocols such as ModBus/DNP for
                           integration with other IEDs
                         • Applicable for electrical utilities as
                           well as industrial electrical systems
                         • Best value for price
                         • Building block for systems
                         • Large graphical built-in interface
                         • Meets well established IEC 61131-3
                           standard for easy logic configuration
                         • Graphical editor for programming
                           logic
                         • Pre-assigned interlocking
                                                                           2/
                                                                          GE /
                                                              August 18, 2023
Applications
Advanced Protection for Industrial and Distribution Utilities
                              The F650 can be used for:
                              •   Comprehensive feeder protection and
                                  control functionality at any voltage
                                  level
                              •   Backup protection for transformers,
                                  busbars, generators and large motors
                              •   Control functions include
                                  synchronism-check, recloser and
                                  breaker failure
                              •   Monitoring functions:
                                     Oscillography
                                     Event Recorder
                                     Fault Recorder
                                     Data Logger
                                                                               3/
                                                                              GE /
                                                                  August 18, 2023
Features & Benefits
   Supporting design flexibility with multiple I/O options
                              The F650 features advantage
                              such as:
                              • Modular hardware architecture:
                                   Main CPU board with two plug and play
                                     comm boards
                                   Universal magnetic (CTs & VTs) module
                                   Programmable I/O module
                                   Single or redundant power supply
                                   Front board: HMI ( Graphical or
                                     alphanumerical display, LEDs, RS232)
                              • Modern and open communication protocols
                                for easy integration
                                                                               4/
                                                                              GE /
                                                                  August 18, 2023
Block Diagram
 Complete Feeder Protection and Control of Multiple Devices
                                                                     5/
                                                                    GE /
                                                        August 18, 2023
Protection
 Complete Feeder Protection and Control of Multiple Devices
• Phase, neutral and ground TOCs   • Under and overvoltage elements
  and IOCs
                                   • Under and overfrequency elements
• Standard curves and
  programmable user curves:        • RMS / DFT choice independent from
                                     mains frequency (50 / 60 Hz)
     IEEE
                                   • Use of established protection
     IEC                            algorithms
     ANSI                         • Designed to withstand surges,
     IAC                            overcurrents and DC-biased faults
     I2t                          • True universal current range 1/5 A
     Definite time                • DSP to unload main CPU (64
                                     samples/cycle)
     Rectifier
                                   • Bidirectional protection
     User curves
                                   • Sensitive earth fault
                                                                                  6/
                                                                                 GE /
                                                                     August 18, 2023
Control
Control of Multiple Devices including Main Breaker and Motorized
                             Switches
      PC design mode example
                                  F650 Control functions include:
                                  •   Synchrocheck
                                  •   4 Shot autorecloser is fully programmable
                                  •   Breaker failure
                                  •   Fuse failure
                                  •   One line diagram in graphic LCD display
                                      with capability to display switchgear
     F650 Actual screen example       elements
                                  •   Full control of switches and breakers
                                  •   Built in pre-configured interlockings for
                                      secure control.
                                  •   Annunciator panel viewing
                                  •   Three setting groups available
                                                                                   7/
                                                                                  GE /
                                                                      August 18, 2023
Monitoring & Metering
 Reduce Troubleshooting time and maintenance Cost – Event
  Reports, Waveform Capture, IRIG-B Time Synchronization
                              The F650 provides:
                              • Data logger (16 Channels)
                              • Event recording of up to 479 time-
                                tagged events
                              • Programmable oscillography feature (up
                                to 20 records)
                              • Monitoring of current, voltage, power,
                                power factor, energy, demand and
                                frequency
                              • Fault recording and location with 10
                                fault reports
                              • IRIG-B DC for accurate 1 ms time
                                tagging
                              • Breaker monitoring
                              • Three phase energy metering
                                                                          8/
                                                                         GE /
                                                             August 18, 2023
Typical Wiring
  Multiple configurations suitable for various applications
                                                                      9/
                                                                     GE /
                                                         August 18, 2023
Mechanical
 Various I/O Options, Dual Power Supply Capable, High Speed
                       Communications
                   Mechanical advantages of the F650:
                   • Modular concept
                   • 6 unit height allows optimising space for terminals
                   • Built in guide-rails facilitate board insertion/extraction
                   • Grounding screw built into case
                   • Printed labels on the rear plate facilitates wiring
                   • Power supply is clearly marked with positive and
                     negative terminals far from each other to prevent
                     accidents
                   • TX and RX LEDs for Ethernet port communications
                     visible from rear side helps troubleshooting
                                                                                    10 /
                                                                                    GE /
                                                                        August 18, 2023
Hardware
  Advanced design – Dual Power Supply, DSP to improve CPU
                       Performance
  Redundant Power Supply          CPU+DSP
• Wide input range (HI & LO)              • High-speed 32-Bit RISC CPU > 50 MIPS
    LO 24 - 48 VDC                         with more than 32 Megabytes memory
    HI 110 - 250 VDC 120 - 230 VAC       • Firmware upgrades through the use of
                                            flash memory
• Switching Mode Power Supply with High
  Efficiency > 80%                        • Modular communications for flexibility
                                            and cost effective solutions
• Redundant model available through the
  use of 2 modules assembled in the       • High-speed communications:
  mother board                              10/100Mbps Ethernet LAN,
                                            single/redundant Fiber Optic 100Mbps.
                                                                                       11 /
                                                                                       GE /
                                                                           August 18, 2023
Hardware
 Accurate Metering and Expandable I/Os via Internal and External
                         I/O Modules
  Magnetic Module                                Digital I/O
• 9 analog inputs total:                    • CAN bus for increased number of I/Os
      4 VT                                 • Status inputs
      4 universal CT                             20 - 300 VDC
      1 sensitive earth CT                       Programmable threshold levels
                                            • Control outputs
• Modular universal range CT (Valid for 1         Heavy duty relays valid for heavy
  or 5 A to only one terminal)                     inductive loads
                                                  Fast activation speeds (< 8ms)
• On-board DSP provides high-speed          • Supervision
  digital sampling for detailed                   2 voltage monitors and 1 current
  oscillograms and accurate                        monitor available per trip circuit
  measurements
      >16 Bit A/D
                                                   supervision unit
                                                  2 independent trip circuit supervision
      64 samples / power cycle                    units                                 12 /
                                                                                               GE /
                                                                                   August 18, 2023
Hardware
  Easy to use Human Machine interface with Communication
                         Access
                             DISPLAY & LEDS
                              Graphic 16x40 or text 4x20 LCD display
                              Fluorescent backlight to improve visibility
                              Multicolor programmable LEDs with label panel
                             KEYPAD & SHUTTLE
                              Local / Remote / Off pushbutton with LEDs
                              Key control for easy navigation
                              ESC key, built-in ENTER function and audio
                               feedback
                              Ergonomic programmable keys
                             FRONT PORT
                              Electrically isolated front USB communication
                               port
                                                                               13 /
                                                                               GE /
                                                                   August 18, 2023
Hardware
            Complete Expandability based on modular design
                                         Standard I/O
                                         Module          Magnetic Module for AC
                          Optional I/O                   Current and Voltage Inputs
                          Module
  Standard Power
  Supply                                                                    Async F/O Com1
                                                                            Async F/O Com2
                                                                                             Rear-View diagram
  Distributed I/O                                                                            displays I/O,
  Fiber Optic CAN
                                                                                             Magnetic Module (CTs
 Redundant Power                                                            10/100BaseT      & VTs), and other
 Supply (Optional)                                                                           connector locations
                                                                            100BaseFx
                                                                            Redundant
                                                                            100BaseFx
                     IRIG-B Input                   Ground
                                                                                                                     14 /
                                                    Terminal                                                         GE /
                                                                                                         August 18, 2023
EnerVista F650 Setup Software
              Powerful Configuration Tools for the F650
The EnerVista F650 Setup Software provides the following functions:
            Settings                                   Metering
                                                     Configuration
                                                                                  15 /
                                                                                  GE /
                                                                      August 18, 2023
Configuration
 Reduce Overall System Costs and Improve System reliability by
          Reducing the number of Auxiliary Devices
                                The F650 is easy to configure:
                                • The F650 visual environment (based on
                                  IEC 61131-3 standard PLC language)
                                  permits easy configurable logic
                                • Simply make connections on the screen
                                  and load them into the flash memory
                                • Configurable HMI interface
                                                                            16 /
                                                                            GE /
                                                                August 18, 2023
Communications
      High speed communication capabilities
                                 Block Diagram:
                                 • Internal serial buses to
                                   optimize security and
                                   immunity to EMC.
                                 • High speed buses to avoid
                                   bottlenecks.
                                 • 100 Mbps Ethernet fibre
                                   optic for maximum
                                   performance.
                                 • CAN bus for distributed IO up
                                   to 1 km.
                                                                    17 /
                                                                    GE /
                                                        August 18, 2023
Communications
Access to Information – Wide Area Network Integration, Multiple
              Communication Media and Protocols
                                      Physical layer:
                                      • RS485 asynchronous port up to
                                        115200 bauds.
                                      • Fibre optics asynchronous port up
                                        to 115200 bauds.
                                      • Synchronous Ethernet port up to
                                        100 Mbits/s.
                                      • CAN port for distributed I/O.
                                      • Option for redundant ports (both
                                        synchronous and asynchronous).
                                                                           18 /
                                                                           GE /
                                                               August 18, 2023
Communications
 Powerful Communications reducing Wiring Costs with Peer-to-
                  peer Communication
  Protocols:
  • Modbus RTU and Modbus TCP/IP
  • DNP 3.0 Level 2 over TCP/IP, UDP/IP and serial
  • IEC 61850, IEC 60870-5-104
                                                                           PROTECTION RELAYS
       HV Line x 2     Breaker x 2             Transformer x 2            MV Feeder x 20
          D60             F650       F650         DTP             DTR        F650
                                                       MULTINET
                                            MULTILINK SWITCH
                                                                                Fiber Optic
          DIRECT I/O
                                                            BUS CAN
                                                           Fiber Optic
        C30        CIO       CIO                                         CIO                   HMI
    REMOTE DI/DO/AO EXTENSION
                                                                                                           19 /
                                                                                                           GE /
                                                                                               August 18, 2023
Reliability
 Reliable Design Features based on Extensive Industry Experience
  Hardware:
  • Redundant power supply
  • Distributed supply concept
  • “Cool” temperature design through low power consumption
  • Replacing hardware by firmware reduces parts count
  Firmware:
  • Double Flash memory concept avoids program
    crashes during field upgrades. This allows secure
    remote reprogramming
  • CMM model approach for quality
  • OOP in high level C language
                                                                          20 /
                                                                          GE /
                                                              August 18, 2023
F650 Ordering Code
                                 21 /
                                 GE /
                     August 18, 2023
Dimensions
                         22 /
                         GE /
             August 18, 2023
CAN Bus Remote I/O Module
                          Remote CAN Bus Input/Output Module
                          for the 650 Family
                                                                                    Connection of F650’s with CIO’s linked by an Ethernet LAN
Target Applications/Industries:                              Key Values:
 • Target any applications involving a F650, W650 or          • Additional I/O for 650 family of relays
   G650 systems to replace RTU units                          • Remote mounting from relay location (up to 1km)
 • Use CIO remote I/O modules for higher reliability,         • Operates connected to one F650, W650, and G650
   lower cost, and more functions, instead of settling for      family of relays
   an RTU.
                                                              • Each module includes up to 32 inputs and 16 outputs
 • Sense up to 32 digital inputs, 8 outputs, 2 with trip
                                                              • One 650 type relay can handle up to 1 CIO (future
   coil supervision, 8 dcmA transducers inputs for
                                                                releases will allow increased number of CIO units per
   pressures, temperatures, fluid levels, or other process
                                                                relays)
   values. Report these values to SCADA or DCS
   systems, and use them in local automatic control           • Simplified wiring (2 fiber optic cables) for lower cost and
   equations.                                                   increased reliability
                                                              • Scaleable solution (1 or 2 boards, different modules to fit
                                                                the application)
                                                              • 1 ms time tagging
                                                                                                                                        23 /
                                                                                                                                        GE /
                                                                                                                            August 18, 2023
CIO Typical Wiring
                                 24 /
                                 GE /
                     August 18, 2023
CIO Ordering Code
                                25 /
                                GE /
                    August 18, 2023
F-650
Feeder Manager and Bay Controller
Advanced Protection for Industrial and Distribution Utilities
                                 • Integrate protection and
                                   control
                                    > Remote control
                                    > Local control
                                 • Monitor trip/close circuits,
                                   rack in/out switches
                                 • Applicable for radial and
                                   looped feeders
                                                                        26 /
                                                                        GE /
                                                            August 18, 2023
F-650 Bay Controller
Standardization & Minimization
 • Control Points Eliminate the Need For:
    > Trip/Close Switches & Indicators
    > Miscellaneous Function Switches
       – Metering Display
       – Maintenance Lockout
       – Transfer, Autotransfer, Block Transfer
 • PLC Logic Eliminates the Need For:
    > Auxiliary Relays
    > Timers
 • Dynamic Mimic Eliminates the Need For:
    > On-Panel Hard Mimic and Indicators
                                                              27 /
                                                              GE /
                                                  August 18, 2023
    Appendix
      F650
Product Positioning
                                  28 /
                                  GE /
                      August 18, 2023
 Feeder Protection – F650
                                                                           Functionality
                                                                                                        F60
                                                                                                                     SR 750/760
                                                                                              F650       F35
                                                                                   MIFII
                             F650
                                                                                   FMII    SR 735/737                            Price
          “Designed and Built for the Industrial Environment”
Target Applications/Industries:                                    Key Values:
 • Primary distribution protection at any voltage level with re-    • Cost effective – Complete feeder protection and control of multiple
   closer                                                             devices including main breaker and motorized switches
 • Backup/auxiliary protection for transmission lines,              • Access to information - Wide area network integration, multiple
   transformers, generators and motors                                communication mediums and protocols
 • Feeder applications requiring Ethernet communications            • Reduced wiring costs – peer-to-peer communication
 • Low cost replacement for RTUs and I/O intensive applications     • Complete asset monitoring – full metering, data logger
 • Bay control                                                      • Reduce troubleshooting time and maintenance cost – event
                                                                      reports, waveform capture, IRIG-B time synchronization
                                                                    • Reduced number of devices – control functions, built in HMI,
Sales Strategy:
                                                                      programmable LEDs
 • Target rec-munis and industrial distribution                     • Design flexibility - Many I/O options, programming logic
     Many High End Features in a Economically Priced Package                                                                            29 /
                                                                                                                                        GE /