Installation Instructions: General
Installation Instructions: General
2
7/16-20 FLARE (45 DEGREE)
CONNECTION USED FOR:
a) OIL FILL (SMP) CONNECTION
b) LOW PRESSURE CONNECTION DISCHARGE SERVICE VALVE LOCATION
c) HOLDING CHARGE RELIEF PORT ELECTRICAL BOX WITH
d) PRESSURE RELIEF VALVE CONNECTION STANDARD MOTOR
CARLYLE P/N EB51XW061 OR EQUIVALENT PROTECTION
e) RECOMMENDED TORQUE IS
25 FT-LBS (33 NM)
SIGHT GLASS
7/16-20 SAE OIL DRAIN (ONE ON EACH SIDE)
CONNECTION
CRANKCASE HEATER
(ACCESSORY) LOCATION
SINGLE POINT
LIFTING BRACKET
NAMEPLATE
SUCTION SERVICE
VALVE LOCATIONS
3
ELECTRICAL (06M R-410A) secondary single phasing, and loss of refrigerant condition.
Control wiring for the motor protection module is applied at
General positions No. 11, 12, and 14 as shown in Fig. 2. Field wire the
protection module supply voltage to terminal positions "L" and
Consult the wiring diagram located inside the compressor "N". Verify supply voltage matches module label voltage;
terminal box cover and Fig. 2 diagram shown below for wir- applying an incorrect supply voltage will result in motor protec-
ing connection locations. tion module failure to function.
Compressor Circuit Protection The compressor's motor protection module is equipped with a
set of normally open (NO) and normally closed (NC) contacts.
Compressor circuit protection must be used when applying • Terminals 11 and 12 are open during compressor opera-
the 06M compressor. Size appropriate circuit breaker or fuse tion. The contacts will close during a motor over-tem-
protection based on local codes. See Carlyle Application perature situation and should be used as an alarm output
Guide 574-602, Section 5.0, ‘Compressor Electrical Data signal to the main controller.
and Motor Protection.’ • Terminals 11 and 14 are closed during compression
operation. The contacts will open during a motor over-
Compressor Wiring and Motor Protection temperature situation, turning the compressor off, pro-
Connect (3) power leads from L1, L2, and L3 to terminals 1, vided Terminals 11 and 14 are wired into the compres-
2, and 3 respectively. See Fig. 2. sor's start/stop circuitry.
The motor protection device is factory installed in the 06M
electrical box. The motor embedded PTCs (Positive Tempera- TERMINAL PLATE WIRING
ture Coefficient) sensors are factory wired to the motor protec- 1. Customer wiring to the terminal plate must be provided
tion module through terminal plate positions No. 8 and No. 9 with ring terminals to accommodate the 1/4 in. - 28 ter-
(see Fig. 2). The PTC is designed to open if the compressor’s minal studs.
motor temperature exceeds 158F (70 C). The motor is pro- 2. Tighten extended terminal nuts to 30 in.-lb (3.4 Nm)
tected against locked rotor, running overload, primary and maximum.
NOTES:
1. Do not attempt to remove, inspect or re-install any
CUSTOMER WIRING
of the internal parts without referring to service manual.
SEE NOTES 2 AND 4
2. Terminals 11 and 12 are normally closed (NC). These MOTOR PROTECTION
contacts are open during normal compressor operation FACTORY WIRING TO
and will close during a motor over temperature TERMINAL PLATE POSITION
situation. Terminals 11 and 14 are normally open (NO). NO. 8 AND 9
These contacts are closed during normal compression
operation and will open during a motor overtemperature situation. ALARM LAMP
Fig. 2 — Control Wiring for the Motor Protection Module (06M R-410A)
4
ELECTRICAL: 06M CO2 SUBCRITICAL (R-744) at positions No. 11 and 14 as shown in Fig. 3. Field wire the
protection module supply voltage to terminal positions "L" and
General "N". Verify supply voltage matches module label voltage;
applying an incorrect supply voltage will result in motor protec-
Consult the wiring diagram located inside the compressor tion module failure to function.
terminal box cover and Fig. 2 diagram shown below for wir- The compressor's motor protection module is equipped with
ing connection locations. a set of normally open (NO) contacts.
Compressor Wiring and Motor Protection • Terminals 11 and 14 are closed during compression
operation. The contacts will open during a motor over-
Connect (3) power leads from L1, L2, and L3 to terminals 1, temperature or over-current situation, turning the com-
2, and 3, respectively. See Fig. 3. pressor off, provided Terminals 11 and 14 are wired into
The motor over-current / over-temperature protection device the compressor's start/stop circuitry.
is factory installed in the 06M electrical box. The motor embed-
ded PTCs (Positive Temperature Coefficient) are factory wired TERMINAL PLATE WIRING
to the motor protection module through terminal plate positions
No. 8 and No. 9 (see Fig. 3). The PTC is designed to open if the 1. Customer wiring to the terminal plate must be provided
compressor’s motor temperature exceeds 158 F (70 C). The with ring terminals to accommodate the 1/4 in. - 28 ter-
motor is protected against locked rotor, running overload, pri- minal studs.
mary and secondary single phasing, and loss of refrigerant con- 2. Tighten extended terminal nuts to 30 in.-lb (3.4 Nm)
dition. Control wiring for the motor protection module is applied maximum.
5
MODULE
COMPRESSOR
TERMINAL PLATE CT
A. Control Power to the module (Terminals “L” and “N” on the module)
B. Module connections for the control circuit (Terminal “11” and “14” on the module)
C. Power Lead that is monitored by the CT (Current Transformer) at the terminal plate
D. PTC connections at the terminal plate (Terminals “7” and “9” on the compressor)
B
A
D
C
POWER LEAD
THROUGH CT
Fig. 3 — Control Wiring for the Motor Protection Module (R-744) (cont)
6
OIL PRESSURE SAFETY SWITCH than 120 seconds is required for start-up purposes. The
1. All Carlyle 06M compressors are provided with connec- switch must also be manually reset when it trips.
tions for an oil safety switch. The use of an oil safety 3. The following oil safety switch has been approved by
switch can help prevent compressor failures when loss Carlyle for use with the 06M compressor:
of lubrication or loss of compressor oil change occurs.
The use of an oil safety switch is requires as a condi- CARLYLE PART NO. 06DA660170
tion of warranty for those 06M compressors which are Time Delay 120 Seconds
applied on systems in which two or more 06M com- Connections Electronic
pressors are connected in parallel. On units in which Pressure Difference Cutout psig (bar) 8 to10 (1.56 to 1.70)
single 06M compressors are applied, the use of an oil Pressure Difference Reset psig (bar) 12 to 14 (1.84 to 1.97)
pressure safety switch is required.
Volts (Minimum volts to maintain the 115/230
2. Normal oil pressure for 06M compressors is 15 to 45 psi switch operation) (100/220)
(1.03 to 3.10 bar) above suction pressure. Select a switch Reset Manual
to close the control circuit (at start-up) at a maximum of 12 Remote Alarm Circuit Capacity Yes
psi (1.84 bar) differential pressure and open the control
circuit at a minimum of 8 psi (1.56 bar) differential pres-
sure. A time delay of not less than 30 seconds nor more
7
ITC Classification, U.S. ECCN: EAR99
Manufacturer reserves the right to discontinue, or change CARLYLE COMPRESSOR DIVISION • © CARRIER CORPORATION Lit. No. 574-601
at any time, specifications or designs and prices without P.O. Box 4808 • Syracuse, New York 13221 (08/12)
Phone 1-800-532-5031 • Fax 1-315-432-3274
notice and without incurring obligations. In U.S. and Puerto Rico: 1-800-GO-CARLYLE (1-800-462-2759) (Rev. 8/17)
In Canada: 1-800-258-1123
In Mexico: 001-800-GO-CARLYLE (001-800-462-2759)