A-101 FIRE SUPPRESSION SYSTEM
MODELS 10, 20, 30 AND MODELS 50, 125, 250
                                                                                                  Data/Specifications
                                                                        004702                                                                           004689
  FEATURES                                                                         DESCRIPTION
 FM Approved                                                                    The ANSUL A-101 Fire Suppression System is a pre-engineered,
                                                                                 cartridge-operated dry chemical system with a fixed nozzle distribution
 Manual and/or Automatic Detection and Actuation                                network. It is approved by Factory Mutual (FM).
 Extreme Temperature Option
                                                                                 The system is capable of automatic detection and actuation and/or
 Low Profile Tank Option                                                        remote manual actuation. When a fire is detected, the A-101 system is
 Rugged Construction                                                            actuated either manually or automatically, operating the pneumatic actu-
                                                                                 ator. The pneumatic actuator ruptures a seal disc in the expellant gas
 Approved For Use in Under Ground Mines For Either Manual or                    cartridge. This, in turn, pressurizes and fluidizes the dry chemical extin-
  Automatic Agent Release (Automatic Detection System Incorporating              guishing agent in the tank, ruptures the burst disc when the required
  MSHA Approved ANSUL® CHECKFIRE® MP-N Detection System)                         pressure is reached, and propels the dry chemical through the network
                                                                                 of distribution hose. The dry chemical is discharged through fixed
                                                                                 nozzles and into the protected areas, suppressing the fire.
                                                                                 The automatic detection portion of the fire suppression system incorpo-
  APPLICATIONS
                                                                                 rates electric detection, either linear detection wire or spot detection.
The ANSUL A-101 Fire Suppression System is an automatic or manual                In addition, Triple IR flame detectors added to the linear or thermal
fire suppression system using FORAY® (monoammonium phosphate                     detection circuit can be utilized for quick fire detection response.
base) dry chemical agent for Class A, B, and C fires. The fire suppres-
sion system is designed for use on large, off-road type construction and         The fire suppression system is capable of providing local application
mining equipment (such as large excavators/shovels, draglines, haul              hazard protection for mobile equipment and industrial hazards. In certain
trucks, wheeled loaders), underground mining equipment, and specialty            industrial hazards, total flooding can be used.
vehicles (such as slag, pot and/or slab carriers, tunnel boring machines,
                                                                                 The basic system consists of: Dry Chemical Agent Storage Tank(s),
solid waste handling equipment, and forestry vehicles). These types of
                                                                                 Expellant Gas Cartridge, Distribution Hose and Nozzles,
equipment have large volumes of oils and hydraulic fluids under pres-
                                                                                 Manual/Automatic Actuator, Automatic Detection System, and
sure.
                                                                                 Accessories.
The fire system described is a suppression system only and is not
                                                                                 Agent Storage Tank – The agent storage tank(s) consists of a welded
designed or intended to extinguish all fires. It is extremely important that
                                                                                 steel tank, gas tube, brass or aluminum fill cap, agent outlet sealed
alternative firefighting equipment be available in case the system does
                                                                                 bursting disc assembly, and instruction nameplate. Tanks for tempera-
not totally extinguish a fire.
                                                                                 ture ranges of +32 °F to +120 °F (0 °C to +49 °C) and the LT-A-101-10,
If an automatic fire detection and actuation system has not been                 have a cartridge receiver and an expellant gas cartridge located on the
supplied or has been disconnected, system actuation and discharge will           side of the tank. Low profile and extreme temperature model tanks,
not occur unless the fire suppression system is manually actuated.               (–65 °F to +210 °F (–54 °C to +99 °C)), have a separate cartridge/pneu-
                                                                                 matic actuator assembly which is connected to the tank by a high pres-
                                                                                 sure 1/4 in. hose. The tank is painted with a red enamel paint. Agent
                                                                                 storage tanks are available in six sizes (10 lb., 20 lb., 30 lb., 50 lb.,
                                                                                 125 lb. and 250 lb.).
                                                                                 Mounting Bracket (10, 20, 30, 50) – Tank mounting bracket consists of
                                                                                 a rugged, welded steel back plate and clamp arm assembly. The bracket
                                                                                 is designed to retain and protect the agent storage tank in the normal
                                                                                 hostile environment that these systems are installed in. The bracket is
                                                                                 painted red enamel and can be mounted by bolting or welding.
 SPECIFICATION CHART
                                                Part                                  Shipping
Model                                           No.      Capacity                     Weight
A-101-10                                        16559    8 1/2 lbs. (3.9 kg) FORAY    31 lbs. (14 kg)
Basic unit consists of:                                  multi-purpose dry chemical   (with bracket)
• Agent tank with CO2 cartridge
• Tank mounting bracket
• Installation manual
A-101-20                                        16430    17 lbs. (7.7 kg) FORAY       43 lbs. (19.5 kg)
Basic unit consists of:                                  multi-purpose dry chemical   (with bracket)
• Agent tank with CO2 cartridge
• Tank mounting bracket
• Installation manual
LP-A-101-20-B                                   31344    17 lbs. (7.7 kg) FORAY       54 lbs. (24.4 kg)
Basic unit consists of:                                  multi-purpose dry chemical   (with bracket)
• Agent tank            • CO2 cartridge
• Tank mounting bracket
• Cartridge bracket     • Installation manual
• Pneumatic actuator
A-101-30                                        16131    25 lbs. (11.3 kg) FORAY      61 lbs. (27.6 kg)
Basic unit consists of:                                  multi-purpose dry chemical   (with bracket)
• Agent tank with CO2 cartridge
• Tank mounting bracket
• Installation manual
LT-A-101-10                                     31581    8 1/2 lbs. (3.9 kg) FORAY    31 lbs. (14 kg)
Basic unit consists of:                                  multi-purpose dry chemical   (with bracket)
• Agent tank with CO2 cartridge
• Tank mounting bracket
• Installation manual
LT-LP-A-101-20-B                                24307    17 lbs. (7.7 kg) FORAY       54 lbs. (24.4 kg)
Basic unit consists of:                                  multi-purpose dry chemical   (with bracket)
• Agent tank            • N2 cartridge
• Tank mounting bracket
• Cartridge bracket     • Pneumatic actuator
• Installation manual
LT-A-101-20                                     24306    17 lbs. (7.7 kg) FORAY       43 lbs. (19.5 kg
Basic unit consists of:                                  multi-purpose dry chemical   (with bracket)
• Agent tank            • N2 cartridge
• Tank mounting bracket
• Cartridge bracket     • Pneumatic actuator
• Installation manual
LT-A-101-30                                     53003    25 lbs. (11.3 kg) FORAY      66 lbs. (29.9 kg)
Basic unit consists of:                                  multi-purpose dry chemical   (with bracket)
• Agent tank            • N2 cartridge
• Tank mounting bracket
• Installation manual
• Cartridge bracket     • Pneumatic actuator
LT-A-101-50                                     433788   45 lbs. (20.4 kg) FORAY      105 lbs. (47.6 kg)
Basic unit consists of:                                  multi-purpose dry chemical
• Agent tank            • N2 cartridge
• Tank mounting bracket
• Cartridge bracket     • Pneumatic actuator
• Installation manual
LT-A-101-125                                    427745   112 lbs. (50.8 kg) FORAY     247 lbs. (112 kg)
Basic unit consists of:                                  multi-purpose dry chemical
• Agent tank            • N2 cartridge
• Cartridge bracket     • Pneumatic actuator
• Installation manual
LT-A-101-250                                    427746   225 lbs. (102.1 kg) FORAY    525 lbs. (238 kg)
Basic unit consists of:                                  multi-purpose dry chemical
• Agent tank            • N2 cartridge
• Cartridge bracket     • Pneumatic actuator
• Installation manual
Dimensions                                   Actuation            Nozzles                Cartridges                              Temperature
H: 16 3/4 in. (425.5 mm) (with bracket)      Electric detection   F-1/2, C-1/2 or        Dry chemical propellant (CO2)           +32 °F to +120 °F
   16 1/2 in. (419.1 mm) (without bracket)   with pneumatic       V-1/2, 2 per tank      840 psi (57.2 bar) at 70 °F (21 °C)     (0 °C to +49 °C)
W: 8 1/4 in. (209.5 mm) (with bracket)       actuation; manual    maximum                Remote actuators (N2)
D: 5 1/4 in. (133.4 mm) (with bracket)       remote pneumatic,                           1800 psi (122.5 bar) at
                                             push button                                 70 °F (21 °C)
H: 19 7/8 in. (504.8 mm) (with bracket)      Electric detection   F-1/2, C-1/2 or        Dry chemical propellant (CO2)           +32 °F to +120 °F
   19 7/8 in. (504.8 mm) (without bracket)   with pneumatic       V-1/2, 6 per tank      840 psi (57.2 bar) at 70 °F (21 °C)     (0 °C to +49 °C)
W: 11 1/2 in. (292.1 mm) (with bracket)      actuation; manual    maximum                Remote actuators (N2)
D: 8 in. (203.2 mm) (with bracket)           remote pneumatic,                           1800 psi (122.5 bar) at
                                             push button                                 70 °F (21 °C)
H: 15 1/4 in. (387.3 mm) (with bracket)      Electric detection   F-1/2, C-1/2 or        Dry chemical propellant (CO2)           +32 °F to +120 °F
   14 7/8 in. (377.8 mm) (without bracket)   with pneumatic       V-1/2, 6 per tank      840 psi (57.2 bar) at 70 °F (21 °C)     (0 °C to +49 °C)
W: 9 3/4 in. (247.6 mm) (with bracket)       actuation; manual    maximum                Remote actuators (N2)
D: 8 1/2 in. (215.9 mm) (with bracket)       remote pneumatic,                           1800 psi (122.5 bar) at
                                             push button                                 70 °F (21 °C)
H: 23 in. (584.2 mm) (with bracket)          Electric detection   F-1/2, C-1/2 or        Dry chemical propellant (CO2)           +32 °F to +120 °F
   22 in. (558.8 mm) (without bracket)       with pneumatic       V-1/2, 6 per tank      840 psi (57.2 bar) at 70 °F (21 °C)     (0 °C to +49 °C)
W: 12 in. (304.8 mm) (with bracket)          actuation; manual    maximum                Remote actuators (N2)
D: 9 1/2 in. (241.3 mm) (with bracket)       remote pneumatic,                           1800 psi (122.5 bar) at
                                             push button                                 70 °F (21 °C)
H: 16 3/4 in. (425.4 mm) (with bracket)      Electric detection   F-1/2, C-1/2 or        Dry chemical propellant (N2)            –65 °F to +210 °F
   16 1/2 in. (419.1 mm) (without bracket)   with pneumatic       V-1/2, 2 per tank      1800 psi (122.5 bar) at 70 °F (21 °C)   (–54 °C to +99 °C)
W: 8 1/4 in. (209.5 mm) (with bracket)       actuation; manual    maximum                Remote actuators (N2)
D: 5 1/4 in. (133.3 mm) (with bracket)       remote pneumatic,                           1800 psi (122.5 bar) at
                                             push button                                 70 °F (21 °C)
H: 15 1/4 in. (387.3 mm) (with bracket)      Electric detection   F-1/2, C-1/2 or        Dry chemical propellant (N2)            –65 °F to +210 °F
   14 7/8 in. (377.8 mm) (without bracket)   with pneumatic       V-1/2, 6 per tank      1800 psi (122.5 bar) at 70 °F (21 °C)   (–54 °C to +99 °C)
W: 9 3/4 in. (247.6 mm) (with bracket)       actuation; manual    maximum                Remote actuators (N2)
D: 8 1/2 in. (215.9 mm) (with bracket)       remote pneumatic,                           1800 psi (122.5 bar) at
                                             push button                                 70 °F (21 °C)
H: 22 3/8 in. (568.3 mm) (with bracket)      Electric detection   F-1/2, C-1/2 or        Dry chemical propellant (N2)            –65 °F to +210 °F)
   21 3/8 in. (542.9 mm) (without bracket)   with pneumatic       V-1/2, 6 per tank      1800 psi (122.5 bar) at 70 °F (21 °C)   (–54 °C to +99 °C)
W: 12 (304.8 mm) (with bracket)              actuation; manual    maximum                Remote actuators (N2)
D: 9 1/2 in. (241.3 mm) (with bracket)       remote pneumatic,                           1800 psi (122.5 bar) at
                                             push button                                 70 °F (21 °C)
H: 22 5/8 in. (574.6 mm) (with bracket)      Electric detection   F-1/2, C-1/2 or        Dry chemical propellant (N2)            –65 °F to +210 °F
   22 3/8 in. (568.3 mm) (without bracket)   with pneumatic       V-1/2, 6 per tank      1800 psi (122.5 bar) at 70 °F (21 °C)   (–54 °C to +99 °C)
W: 9 7/8 (258.8 mm) (with bracket)           actuation; manual    maximum                Remote actuators (N2)
D: 7 3/4 in. (196.8 mm) (with bracket)       remote pneumatic                            1800 psi (122.5 bar) at
                                             push button                                 70 °F (21 °C)
H: 21 1/2 in. (550 mm)                       Electric detection   F-1/2, C-1/2 or        Dry chemical propellant (N2)            –65 °F to +130 °F
                                             with pneumatic       V-1/2, 4, 6, or 8      1800 psi (122.5 bar) at 70 °F (21 °C)   (–54 °C to +54 °C)
W: 11 3/8 (290 mm)                           actuation; manual    per tank               Remote actuators (N2)
                                             remote pneumatic,    maximum                1800 psi (122.5 bar) at
D: 12 1/2 in. (320 mm)                       push button                                 70 °F (21 °C)
H: 31 in. (787 mm)                           Electric detection   F-1/2, C-1/2 or        Dry chemical propellant (N2)            –65 °F to +130 °F
                                             with pneumatic       with V-1/2, 12 or 16   1800 psi (122.5 bar) at 70 °F (21 °C)   (–54 °C to +54 °C
W: 18 (457 mm)                               actuation; manual    per tank               Remote actuators (N2)
                                             remote pneumatic,    maximum                1800 psi (122.5 bar) at
D: 22 in. (559 mm)                           push button                                 70 °F (21 °C)
H: 44 in. (1118 mm)                          Electric detection   F-1/2, C-1/2 or        Dry chemical propellant (N2)            –65 °F to +130 °F
                                             with pneumatic       V-1/2, 12, 16, or 24   1800 psi (122.5 bar) at 70 °F (21 °C)   (–54 °C to +54 °C)
W: 22 (559 mm)                               actuation; manual    per tank               Remote actuators (N2)
                                             remote pneumatic,    maximum                1800 psi (122.5 bar) at
D: 28 in. (711 mm)                           push button                                 70 °F (21 °C)
 DESCRIPTION
Mounting Ring (125, 250) – The mounting ring for the 125, 250 tanks is                     CHECKFIRE systems utilize either an electrical, mechanical, or pneu-
fabricated of 1/2 in. steel. The ring conforms to the outline of the tank                  matic principle. Four types of detector options can be used: A tempera-
assembly bottom. The ring can be welded to the mounting surface and                        ture-sensitive linear wire, a spot-type heat detector, or a gas filled
the tank can then be bolted to the ring, using the pre-threaded holes in                   stainless steel tubing, or a combined linear/spot type with Triple IR (IR3)
the ring.                                                                                  flame detectors.
Expellant Gas Cartridge – The expellant gas cartridge is a spun high                       • Temperature-sensitive linear wire – When fire breaks out, the wire’s
pressure cartridge containing either carbon dioxide for temperature                          insulation melts, completing an electrical circuit and causes the detec-
ranges of +32 °F to +120 °F (0 °C to +49 °C), or nitrogen for extreme                        tion system to actuate the fire suppression system.
temperature ranges of –65 °F to +210 °F (–54 °C to +99 °C).                                • Spot-type heat detectors – Internal contacts will close when the
Distribution Hose and Nozzles – The distribution piping (hose)                               temperature of the surrounding air reaches the set point temperature
network is designed to properly distribute the dry chemical to the                           of the detector. This action completes an electrical circuit and causes
nozzles. To survive the vibration found on mobile equipment, hose is                         the detection system to actuate the fire suppression system.
used to distribute the dry chemical. In the A-101 pre-engineered                           • Gas filled stainless steel tubing – When the gas in the tubing heats
system; hose sizes, maximum and minimum hose lengths, and number                             up, the increase in pressure operates a responder, thus completing
of nozzles are predetermined. There are three types of nozzles avail-                        an electrical circuit and causes the detection system to actuate the
able for the A-101 system. Each type of nozzle has been designed and                         fire suppression system.
tested for various applications and area of coverage. Nozzle blow-off
caps are available to keep the nozzles free of dirt and grease.                            • The Triple IR (IR3) Flame Detector is a high performance and high
                                                                                             reliability self-contained triple spectrum flame detector. This detector,
Manual/Automatic Actuator(s) – The manual actuator consists of an                            packaged in a small, convenient sized housing for easy installation in
actuator body, a nitrogen cartridge, and a mounting bracket. Two types                       tight areas, is specially designed as a general-purpose flame detector
of manual actuators are available: Remote type and Dashboard type.                           for off-road (mining) and industrial applications with the highest immu-
The Remote type uses either the “S” style bracket or the cartridge                           nity to false alarms. The patented Triple IR design offers two to three
guard style enclosure. The Dashboard type uses the “L” or “S” style                          times the detection distance of any conventional IR or UV/IR detector,
mounting bracket. When the manual actuator is operated by hand, gas                          scanning for oscillating IR radiation (1 to 10 Hz) in three special
supplied from the nitrogen cartridge is released into 1/4 in. actuation                      bands. Each sensor band pass has been selected to ensure the
hose. This nitrogen pressure then operates the pneumatic actuator that                       greatest degree of spectral matching to the radiant energy emissions
punctures a larger expellant gas cartridge (either carbon dioxide or                         of fire, and the lowest degree of matching to non-fire stimuli.
nitrogen) and this fluidizes and propels the dry chemical from the agent
storage tank.
Automatic actuators (a component of the automatic detection system)
operate the same way, except they can be operated automatically by                             SPECIFICATIONS
the detection system.
                                                                                           The fire suppression system shall be the dry chemical pre-engineered
                                                                                           fixed nozzle cartridge-operated type, incorporating automatic detection
                                                                                           with engine shutdown capabilities. It shall be approved by Factory
                                                                                           Mutual (FM) for the hazards to be protected based on actual fire tests by
                                                                                           the manufacturer and confirmed by the nationally recognized testing
                                                                                           laboratory. The design of the system (specific hose sizes, maximum and
                                                                                           minimum lengths, hose specifications, number of fittings, number and
                                                                                           type of nozzles, and quantity of dry chemical) shall provide protection for
                                                                                           the hazard as prescribed by the national testing laboratory. Installation
                                                                                           shall be in accordance with the approved Design, Installation,
                                                                                           Maintenance Manual and conform to NFPA Standard 17, “Dry Chemical
                                                                                           Extinguishing System,” and NFPA Standard 121, “Mobile Surface Mining
                                                                                           Equipment.”
                                                                                               APPROVAL
                                                                                           The ANSUL A-101 System has been approved by Factory Mutual (FM).
                                                                    004690
                                                                                               TWIN AGENT CONCEPT
Automatic Detection System – Three automatic detection systems are
available for use with the ANSUL A-101 fire suppression systems:                           The LVS Liquid Agent Fire Suppression System is designed to be
CHECKFIRE Series I, CHECKFIRE SC-N, or the CHECKFIRE MP-N.                                 installed with an ANSUL A-101 Dry Chemical system to create a twin
                                                                                           agent system concept that is capable of quick fire knock-down, coupled
Mounting location temperatures for the control modules for the detec-                      with the cooling application of the LVS liquid agent. The system consists
tion systems are as follows:                                                               of both dry chemical and wet chemical. The dry chemical side of the
CHECKFIRE Series I               –40 °F to +140 °F (–40 °C to +60 °C)                      system is the ANSUL LT-A-101 type system and the liquid agent side of
                                                                                           the system consists of wet chemical tank(s) containing a premixed solu-
CHECKFIRE SC-N                   –40 °F to +140 °F (–40 °C to +60 °C)
                                                                                           tion of LVS agent.
CHECKFIRE MP-N                   +32 °F to +120 °F (0 °C to +49 °C)
                                                                                               ORDERING INFORMATION
                                                                                           Order all system components through Ansul Customer Service
                                                                                           Department, One Stanton Street, Marinette, WI 54143-2542
ANSUL, CHECKFIRE, and FORAY are trademarks of Ansul Incorporated or its affiliates.
                                                                                           (715) 735-7411.
                                                                    Tyco Safety Products         715-735-7411
                                                                                                                                                  ©2005 Ansul Incorporated
                                                                    Marinette, WI 54143-2542     www.ansul.com                                        Form No. F-95143-3