Niagara

The document proposes renovations to Cosmetique Asia Corporation's manufacturing plant, including replacing and upgrading various exhaust and supply fans. It lists 41 different fan models from Niagara/NYB ranging from ceiling cassette fans to large propeller fans. Technical specifications are provided for each fan such as capacity, ESP, motor rating, and model details. Recommendations are made for direct-on-line or wye-delta motor controllers depending on horsepower. Dimensioned drawings are included for some fan models.

Uploaded by

Mike Bongolan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
5K views45 pages

Niagara

The document proposes renovations to Cosmetique Asia Corporation's manufacturing plant, including replacing and upgrading various exhaust and supply fans. It lists 41 different fan models from Niagara/NYB ranging from ceiling cassette fans to large propeller fans. Technical specifications are provided for each fan such as capacity, ESP, motor rating, and model details. Recommendations are made for direct-on-line or wye-delta motor controllers depending on horsepower. Dimensioned drawings are included for some fan models.

Uploaded by

Mike Bongolan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 45

Date: 02 May 2023

Project: PROPOSED MANUFACTURING PLANT RENOVATION


COSMETIQUE ASIA CORPORATION

CAPACITY ESP SIZE/ MOTOR RATING


ITEM QTY NIAGARA FAN DESCRIPTION
CMH IN MODEL HP V PH HZ
PSEF-1500 2,550 0.5 1 NIAGARA EXHAUST FAN W/ SHUTTER & REAR GUARD NBX 35 120W 230 1 60
PMEF-1000 1,700 0.5 1 NIAGARA EXHAUST FAN W/ SHUTTER & REAR GUARD NBX 30 60W 230 1 60
GSEF-1500 2,550 0.5 1 NIAGARA EXHAUST FAN W/ SHUTTER & REAR GUARD NBX 35 120W 230 1 60
MSEF-1500 2,550 0.5 1 NIAGARA EXHAUST FAN W/ SHUTTER & REAR GUARD NBX 35 120W 230 1 60
WAEF-750 1,275 0.5 1 NIAGARA EXHAUST FAN W/ SHUTTER & REAR GUARD NBX 30 60W 230 1 60
SREF-1000 1,700 0.5 1 NIAGARA EXHAUST FAN W/ SHUTTER & REAR GUARD NBX 30 60W 230 1 60
CADC-8630 14,662 12 1 NIAGARA / NYB SERIES 20 GI FAN - DH WHEEL (ARR.1) 36" 30 230 3 60
➢ CAFB-4500 7,645 1.5 1 NIAGARA / NYB GPA FAN (BI-SISW) 20" 3 230 3 60
➢ FREB-1720 2,920 2 2 NIAGARA / NYB GPA FAN (BI-SISW) 15" 1-1/2 230 1 60
PMEF-1500 2,550 0.5 1 NIAGARA EXHAUST FAN W/ SHUTTER & REAR GUARD NBX 35 120W 230 1 60
FGEF-1000 1,700 0.5 2 NIAGARA EXHAUST FAN W/ SHUTTER & REAR GUARD NBX 30 60W 230 1 60
RMEF-1000 1,700 0.5 1 NIAGARA EXHAUST FAN W/ SHUTTER & REAR GUARD NBX 30 60W 230 1 60
➢ IEF-1 1,020 1 1 NIAGARA / NYB FC-DIDW FAN W/ CAB. (DIRECT) 9" 250W 230 1 60
TEF-1-1, TEF-1-2 127 0.65 2 NIAGARA CEILING CASSETTE FAN NIA 150 26W 230 1 60
TEF-2, TEF-3 850 0.25 2 KDK WALL MTD. EXHAUST FAN W/ SHUTTER 25ALH 40W 230 1 60
➢ FRPEF-500 850 0.8 1 NIAGARA EXHAUST FAN W/ SHUTTER & REAR GUARD NBX 30 60W 230 1 60
RMEF2-1500 2,550 0.5 2 NIAGARA EXHAUST FAN W/ SHUTTER & REAR GUARD NBX 35 120W 230 1 60
RMEF3-1500 2,550 0.5 2 NIAGARA EXHAUST FAN W/ SHUTTER & REAR GUARD NBX 35 120W 230 1 60
➢ PSRFB-1500 2,550 1.2 1 NIAGARA / NYB GPA FAN (BI-SISW) 15" 1 230 1 60
➢ SPPS-2400 4,077 1.2 1 NIAGARA / NYB GPA FAN (BI-SISW) 18" 1 230 1 60
TEF-1-3 127 0.65 1 NIAGARA CEILING CASSETTE FAN NIA 150 26W 230 1 60
TEF-1-4, TEF-1-5 127 0.65 2 NIAGARA CEILING CASSETTE FAN NIA 150 26W 230 1 60
TEF-1-6 127 0.65 1 NIAGARA CEILING CASSETTE FAN NIA 150 26W 230 1 60
CEF-3 510 0.8 1 NIAGARA CEILING CASSETTE FAN NIA 200 148W 230 1 60
CNEF-1500 2,550 0.5 1 NIAGARA EXHAUST FAN W/ SHUTTER & REAR GUARD NBX 35 120W 230 1 60

Page 1 of 2
CAPACITY ESP SIZE/ MOTOR RATING
ITEM QTY NIAGARA FAN DESCRIPTION
CMH IN MODEL HP V PH HZ
RREF-500 850 0.25 1 KDK WALL MTD. EXHAUST FAN W/ SHUTTER 25ALH 40W 230 1 60

NOTES:
* FOR 230/3/60: USING "WEG OR TECO" BRAND MOTOR (DEPENDING ON AVAILABILITY)
LEGEND:
➢ COMPLETE WITH VIBRATION ISOLATORS
 USING FRP COATED AIRSTREAM PARTS ONLY
RECOMMENDED MOTOR CONTROLLER
CAPACITY ESP SIZE/ MOTOR RATING
ITEM QTY NIAGARA DESCRIPTION
CMH IN MODEL HP V PH HZ
 PSEF-1500 2,550 0.5 1 DIRECT-ON-LINE MOTOR CONTROLLER NBX 35 120W 230 1 60
 PMEF-1000 1,700 0.5 1 DIRECT-ON-LINE MOTOR CONTROLLER NBX 30 60W 230 1 60
 GSEF-1500 2,550 0.5 1 DIRECT-ON-LINE MOTOR CONTROLLER NBX 35 120W 230 1 60
 MSEF-1500 2,550 0.5 1 DIRECT-ON-LINE MOTOR CONTROLLER NBX 35 120W 230 1 60
 WAEF-750 1,275 0.5 1 DIRECT-ON-LINE MOTOR CONTROLLER NBX 30 60W 230 1 60
 SREF-1000 1,700 0.5 1 DIRECT-ON-LINE MOTOR CONTROLLER NBX 30 60W 230 1 60
SERIES 20
v CADC-8630 14,662 12 1 WYE - DELTA MOTOR CONTROLLER 30 230 3 60
36"
 CAFB-4500 7,645 1.5 1 DIRECT-ON-LINE MOTOR CONTROLLER GPA 20" 3 230 3 60
 FREB-1720 2,920 2 2 DIRECT-ON-LINE MOTOR CONTROLLER GPA 15" 1-1/2 230 1 60
 PMEF-1500 2,550 0.5 1 DIRECT-ON-LINE MOTOR CONTROLLER NBX 35 120W 230 1 60
 FGEF-1000 1,700 0.5 2 DIRECT-ON-LINE MOTOR CONTROLLER NBX 30 60W 230 1 60
 RMEF-1000 1,700 0.5 1 DIRECT-ON-LINE MOTOR CONTROLLER NBX 30 60W 230 1 60
 IEF-1 1,020 1 1 DIRECT-ON-LINE MOTOR CONTROLLER FC 9" 250W 230 1 60
 FRPEF-500 850 0.8 1 DIRECT-ON-LINE MOTOR CONTROLLER NBX 30 60W 230 1 60
 RMEF2-1500 2,550 0.5 2 DIRECT-ON-LINE MOTOR CONTROLLER NBX 35 120W 230 1 60
 RMEF3-1500 2,550 0.5 2 DIRECT-ON-LINE MOTOR CONTROLLER NBX 35 120W 230 1 60
 PSRFB-1500 2,550 1.2 1 DIRECT-ON-LINE MOTOR CONTROLLER GPA 15" 1 230 1 60
 SPPS-2400 4,077 1.2 1 DIRECT-ON-LINE MOTOR CONTROLLER GPA 18" 1 230 1 60
 CNEF-1500 2,550 0.5 1 DIRECT-ON-LINE MOTOR CONTROLLER NBX 35 120W 230 1 60

NOTES:
* CEILING CASSETTE FAN & LOW WATTS WALL MOUNTED FAN ARE NOT RECOMMENDED FOR MOTOR CONTROLLER
LEGENDS:
 FOR 1/2HP TO 5HP USING MAGNETIC STARTER FOR DIRECT-ON-LINE CONNECTION, WITH ON-OFF PUSH BUTTON, OVERLOAD RELAY, ILLUMINATED PILOT LIGHT,
ELECTRIC CIRCUIT BREAKER (ECB), BMS PROVISION, BMS RUN/STOP STATUS, TRIP STATUS, NEMA 4 ENCLOSURE.
v FOR 7.5HP & ABOVE USING MAGNETIC STARTER FOR WYE-DELTA CONNECTION, WITH ON-OFF PUSH BUTTON, OVERLOAD RELAY, ILLUMINATED PILOT LIGHT,
ELECTRIC CIRCUIT BREAKER (ECB), BMS PROVISION, BMS RUN/STOP STATUS, TRIP STATUS, NEMA 4 ENCLOSURE.

Page 2 of 2
PSEF-1500
(NBX 35)
2,550 CMH @ 0.5 IN
PROPELLER FAN DIRECT DRIVE
MODEL: NBX-35
REFERENCE: PAGE 1 OF 1

CUSTOMER: COSMETIQUE ASIA CORPORATION

PROJECT: PROPOSED MANUFACTURING PLANT RENOVATION


ATTENTION: MR. CHRISTIAN REYES
REFERENCE: CAC 23-001-A
SUBMITTED BY: DATE: 05/02/2023

A
450
350
REAR GUARD
SHUTTER

AIR FLOW

BLADE
450

AIR FLOW
WIRING BOX

CL

SIDE VIEW VIEW FROM "A"

NOTE: DIMENSION'S ARE IN MM.

AIR FLOW SP FAN RPM ELECTRICAL


FAN TAG QTY ( CMH ) ( IN ) HP ACCESSORIES
CHARACTERISTICS

PSEF-1500 1 2,550 0.5 1200 120W 230 / 1 / 60 REAR GUARD

SHUTTER

MOTOR CONTROLLER
PMEF-1000
(NBX 30)
1,700 CMH @ 0.5 IN
PROPELLER FAN DIRECT DRIVE
MODEL: NBX-30
REFERENCE: PAGE 1 OF 1

CUSTOMER: COSMETIQUE ASIA CORPORATION


PROJECT: PROPOSED MANUFACTURING PLANT RENOVATION
ATTENTION: MR. CHRISTIAN REYES
REFERENCE: CAC 23-001-A
SUBMITTED BY: DATE: 05/02/2023

A
373

SHUTTER REAR GUARD 300

AIR FLOW
MOTOR BLADE
373

AIR FLOW WIRING BOX

CL

SIDE VIEW VIEW FROM "A"

NOTE: DIMENSION'S ARE IN MM.

AIR FLOW SP FAN RPM


( CMH ) ( IN ) ELECTRICAL
FAN TAG QTY HP ACCESSORIES
CHARACTERISTICS

PMEF-1000 1 1,700 0.5 1100 60W 230 / 1 / 60 SHUTTER

REAR GUARD

MOTOR CONTROLLER
GSEF-1500 & MSEF-1500
(NBX 35)
2,550 CMH @ 0.5 IN
PROPELLER FAN DIRECT DRIVE
MODEL: NBX-35
REFERENCE: PAGE 1 OF 1

CUSTOMER: COSMETIQUE ASIA CORPORATION

PROJECT: PROPOSED MANUFACTURING PLANT RENOVATION


ATTENTION: MR. CHRISTIAN REYES
REFERENCE: CAC 23-001-A
SUBMITTED BY: DATE: 05/02/2023

A
450
350
REAR GUARD
SHUTTER

AIR FLOW

BLADE
450

AIR FLOW
WIRING BOX

CL

SIDE VIEW VIEW FROM "A"

NOTE: DIMENSION'S ARE IN MM.

AIR FLOW SP FAN RPM ELECTRICAL


FAN TAG QTY ( CMH ) ( IN ) HP ACCESSORIES
CHARACTERISTICS

GSEF-1500 & 2 2,550 0.5 1200 120W 230 / 1 / 60 REAR GUARD

MSEF-1500 SHUTTER

MOTOR CONTROLLER
WAEF-750
(NBX 30)
1,275 CMH @ 0.5 IN
PROPELLER FAN DIRECT DRIVE
MODEL: NBX-30
REFERENCE: PAGE 1 OF 1

CUSTOMER: COSMETIQUE ASIA CORPORATION


PROJECT: PROPOSED MANUFACTURING PLANT RENOVATION
ATTENTION: MR. CHRISTIAN REYES
REFERENCE: CAC 23-001-A
SUBMITTED BY: DATE: 05/02/2023

A
373

SHUTTER REAR GUARD 300

AIR FLOW
MOTOR BLADE
373

AIR FLOW WIRING BOX

CL

SIDE VIEW VIEW FROM "A"

NOTE: DIMENSION'S ARE IN MM.

AIR FLOW SP FAN RPM


( CMH ) ( IN ) ELECTRICAL
FAN TAG QTY HP ACCESSORIES
CHARACTERISTICS

WAEF-750 1 1,275 0.5 1100 60W 230 / 1 / 60 SHUTTER

REAR GUARD

MOTOR CONTROLLER
SREF-1000
(NBX 30)
1,700 CMH @ 0.5 IN
PROPELLER FAN DIRECT DRIVE
MODEL: NBX-30
REFERENCE: PAGE 1 OF 1

CUSTOMER: COSMETIQUE ASIA CORPORATION


PROJECT: PROPOSED MANUFACTURING PLANT RENOVATION
ATTENTION: MR. CHRISTIAN REYES
REFERENCE: CAC 23-001-A
SUBMITTED BY: DATE: 05/02/2023

A
373

SHUTTER REAR GUARD 300

AIR FLOW
MOTOR BLADE
373

AIR FLOW WIRING BOX

CL

SIDE VIEW VIEW FROM "A"

NOTE: DIMENSION'S ARE IN MM.

AIR FLOW SP FAN RPM


( CMH ) ( IN ) ELECTRICAL
FAN TAG QTY HP ACCESSORIES
CHARACTERISTICS

SREF-1000 1 1,700 0.5 1100 60W 230 / 1 / 60 SHUTTER

REAR GUARD

MOTOR CONTROLLER
The New York Blower Company Project: PROPOSED MFG.
Fan-to-Size Location: PLANT RENOVATION
Fan Selection Data Contact: COSMETIQUE ASIA CORP.
Fan Tagging: CADC-8630

Fan Design
Product: Series 20 General Industrial Arrangement: 10
Size/Model: 364 Drive type: Belt
Wheel Type: DH
Wheel Material: Mild Steel
Wheel Width: 100.0 % Wheel Diameter: 100.0 %

Operating Conditions
Volume Flow Rate: 14,662 m3/hr Fan Speed: 1331 rpm
Fan Static Pressure: 12.0 in wg Fan Input Power: 24.1 bhp
Outlet Velocity: 3580 ft/min VP/SP ratio: 0.0667
Operating Inlet Airstream Density: 0.0750 lb/ft3
Static Efficiency: 71.89% Mechanical Efficiency: 77.40%
Maximum Operating Temperature: 200 Deg F Maximum Safe Operating Speed: 1620 rpm

Sound Power Level Ratings Levels expressed in dB (power levels reference 10^(-12) watts)
Center Frequency (Hz): 63 125 250 500 1000 2000 4000 8000
Octave Bands: 1 2 3 4 5 6 7 8
Total Fan Power Levels*: 119.6 118.5 109.8 100.8 93.6 89.6 83.6 79.6
Inlet Power Levels**: 116.6 115.5 106.8 97.8 90.6 86.6 80.6 76.6
Outlet Power Levels**: 116.6 115.5 106.8 97.8 90.6 86.6 80.6 76.6
Std Fan Housing Attenuation: -5. -8. -12. -14. -12. -12. -13. -14.
Housing Radiated Power
114.6 110.5 97.8 86.8 81.6 77.6 70.6 65.6
Levels:
*As corrected for point of operation (location on fan curve)
**Unsilenced Inlet and Outlet power ratings are 3 dB lower than total fan power levels under the assumption that "half" of the sound power
can be attributed to each opening. Silenced power ratings include this 3 dB reduction as well as the silencer attenuation.

Estimated Sound Pressure Levels Expressed in dB (pressure levels reference 2x10 -7 microbar)

Directivity/Reflection Factor (Q) is 2, hemispherical radiation; Distance is 10 ft.; A-weighting is in use.

This fan is connected to both inlet and outlet ducting which routes most sound away from the designated sound
measurement location. The Housing Radiated Sound Power levels are the basis for sound pressure level
calculations.

The estimated sound pressure level outside the fan due to Housing Radiated Noise is 79.7 dBA at 10.0 feet.

Your Representative: The New York Blower Company certifies that the
Niagara Industrial Equipment Corp. Series 20 General Industrial fan is licensed to bear
the AMCA Air Performance Seal. The ratings shown
56 12th Avenue Extension are based on tests and procedures performed in
Kalookan City 1400 accordance with AMCA Publication 211 and comply
Philippines with the requirements of the AMCA Certified Ratings
Phone: (632) 366-5562 program.
Fax: (632) 362-4257
AMCA Licensed for Air Performance without
E-Mail: sales@niagarafans.com Appurtenances. Power (bhp) excludes drives.

Performance shown is for installation type: D -


Ducted inlet, Ducted outlet.

Version: 1.71.1000 (Feb, 2002) Printed: 05/02/2023 PDF


The New York Blower Company
Fan-to-Size
Series 20 General Industrial Volume Flow Rate: 14,662 m3/hr
364 DH Fan Static Press.: 12.0 in wg
Arr.: 10 Speed: 1331 rpm Density: 0.0750 lb/ft3
Power: 24.1 bhp Outlet Velocity: 3580 ft/min
Tag: CADC-8630

50
12.5

40

Fan Input Power (bhp)


Fan Static Pressure (in wg)

10.0

30
7.5

5.0 20

2.5 10

0.0 0
0 5000 10000 15000 20000 25000 30000 35000 40000
Volume Flow Rate (m3/hr)
AMCA Licensed for Air Performance without Appurtenances. Power (bhp) excludes drives.
Performance shown is for installation type: D - Ducted inlet, Ducted outlet.
Your Sales Representative:
[v1.71.1000 -- Feb, 2002] Date Printed: 05/02/23 Niagara Industrial Equipment Corp.
Copyright ©1999 The New York Blower Company. Phone: (632) 366-5562
Version: 1.71.1000 (Feb, 2002) Printed: 05/02/2023 PDF
SERIES 20 GI FAN
MODEL: Size 364 CWTH-Arr.1
# 56 12th Avenue Ext. Calookan City 1400 Phils - Tels. : 366-55-60 to 62 Fax : (632)362-4257
REFERENCE: NYB BULLETIN NO. 251 PAGE 1 OF 1

CUSTOMER: COSMETIQUE ASIA CORPORATION


PROJECT: PROPOSED MANUFACTURING PLANT RENOVATION
ATTENTION: MR. CHRISTIAN REYES
REFERENCE: CAC 23-001-A
SUBMITTED BY: DATE: 05/02/2023

AIR FLOW SP ELECTRICAL


FAN TAG QTY FAN RPM HP ACCESSORIES
( CMH ) ( IN ) CHARACTERISTICS
CADC-8630 1 14,662 12 1331 30 230 / 3 / 60 MOTOR CONTROLLER

NOTE: DIMENSION'S ARE IN INCHES


The New York Blower Company Project: PROPOSED MFG.
Fan-to-Size Location: PLANT RENOVATION
Fan Selection Data Contact: COSMETIQUE ASIA CORP.
Fan Tagging: CAFB-4500

Fan Design
Product: GPA - PLR Arrangement: 10
Size/Model: 20 Drive type: Belt
Wheel Type: SISW Backward Inclined
Wheel Material: Mild Steel
Wheel Width: 100.0 % Wheel Diameter: 100.0 %

Operating Conditions
Volume Flow Rate: 7,645 m3/hr Fan Speed: 1253 rpm
Fan Static Pressure: 1.5 in wg Fan Input Power/Motor HP: 1.9 bhp/3HP
Outlet Velocity: 1923 ft/min VP/SP ratio: 0.1539
Operating Inlet Airstream Density: 0.0750 lb/ft3
Static Efficiency: 76.04% Mechanical Efficiency: 77.23%
Maximum Operating Temperature: 300 Deg F Maximum Safe Operating Speed: 1872 rpm

Sound Power Level Ratings Levels expressed in dB (power levels reference 10^(-12) watts)
Center Frequency (Hz): 63 125 250 500 1000 2000 4000 8000
Octave Bands: 1 2 3 4 5 6 7 8
Total Fan Power Levels*: 88.1 87.3 88.1 87.8 82.6 76.6 70.6 62.6
Inlet Power Levels**: 85.1 84.3 85.1 84.8 79.6 73.6 67.6 59.6
Outlet Power Levels**: 85.1 84.3 85.1 84.8 79.6 73.6 67.6 59.6
Std Fan Housing Attenuation: -5. -9. -12. -15. -12. -11. -13. -14.
Housing Radiated Power
83.1 78.3 76.1 72.8 70.6 65.6 57.6 48.6
Levels:
*As corrected for point of operation (location on fan curve)
**Unsilenced Inlet and Outlet power ratings are 3 dB lower than total fan power levels under the assumption that "half" of the sound power
can be attributed to each opening. Silenced power ratings include this 3 dB reduction as well as the silencer attenuation.

Estimated Sound Pressure Levels Expressed in dB (pressure levels reference 2x10 -7 microbar)

Directivity/Reflection Factor (Q) is 2, hemispherical radiation; Distance is 10 ft.; A-weighting is in use.

This fan is connected to both inlet and outlet ducting which routes most sound away from the designated sound
measurement location. The Housing Radiated Sound Power levels are the basis for sound pressure level
calculations.

The estimated sound pressure level outside the fan due to Housing Radiated Noise is 57.9 dBA at 10.0 feet.

Your Representative: The New York Blower Company certifies that the
Niagara Industrial Equipment Corp. GPA fan is licensed to bear the AMCA Air
Performance Seal. The ratings shown are based on
56 12th Avenue Extension tests and procedures performed in accordance with
Kalookan City 1400 AMCA Publication 211 and comply with the
Philippines requirements of the AMCA Certified Ratings program.
Phone: (632) 366-5562
Fax: (632) 362-4257 AMCA Licensed for Air Performance without
Appurtenances. Power (bhp) excludes drives.
E-Mail: sales@niagarafans.com
Performance shown is for installation type: B - Free
inlet, Ducted outlet.

Version: 1.71.1000 (Feb, 2002) Printed: 05/02/2023 PDF


The New York Blower Company
Fan-to-Size
GPA - PLR Volume Flow Rate: 7,645 m3/hr
20 SISW Backward Inclined Fan Static Press.: 1.5 in wg
Arr.: 10 Speed: 1253 rpm Density: 0.0750 lb/ft3
Power: 1.85 bhp/3HP Outlet Velocity: 1923 ft/min
2.5 2.00

1.75
2.0

Fan Input Power (bhp)


1.50
Fan Static Pressure (in wg)

1.5 1.25

1.00
1.0
0.75

0.50
0.5
0.25

0.0 0.00
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000
Volume Flow Rate (m3/hr)
AMCA Licensed for Air Performance without Appurtenances. Power (bhp) excludes drives.
Performance shown is for installation type: B - Free inlet, Ducted outlet.
Your Sales Representative:
[v1.71.1000 -- Feb, 2002] Date Printed: 05/02/23 Niagara Industrial Equipment Corp.
Copyright ©1999 The New York Blower Company. Phone: (632) 366-5562
Version: 1.71.1000 (Feb, 2002) Printed: 05/02/2023 PDF
GPA-20

SUBMITTAL SHEET
NYB BI-SISW CENTRIFUGAL FAN (GPA)
MODEL: Size 20" Arr.10
REFERENCE : NYB Bulletin No. 051 PAGE 1 OF 1

CUSTOMER: COSMETIQUE ASIA CORPORATION

PROJECT: PROPOSED MANUFACTURING PLANT RENOVATION

ATTENTION: MR. CHRISTIAN REYES

REFERENCE: CAC 23-001-A


SUBMITTED BY: DATE: 05/02/2023

NOTE: DIMENSIONS ARE IN INCHES

AIR FLOW SP ELECTRICAL


FAN TAG QTY FAN RPM HP ACCESSORIES
(CMH) ( IN ) CHARACTERISTICS
CAFB-4500 1 7,645 1.5 1253 3 230 / 3 / 60 VIBRATION ISOLATOR

MOTOR CONTROLLER
The New York Blower Company Project: PROPOSED MFG.
Fan-to-Size Location: PLANT RENOVATION
Fan Selection Data Contact: COSMETIQUE ASIA CORP.
Fan Tagging: FREB-1720

Fan Design
Product: GPA - PLR Arrangement: 10
Size/Model: 15 Drive type: Belt
Wheel Type: SISW Backward Inclined
Wheel Material: Mild Steel
Wheel Width: 100.0 % Wheel Diameter: 100.0 %

Operating Conditions
Volume Flow Rate: 2,920 m3/hr Fan Speed: 1631 rpm
Fan Static Pressure: 2.0 in wg Fan Input Power/Motor HP: 1.0 bhp/1.5HP
Outlet Velocity: 1332 ft/min VP/SP ratio: 0.0554
Operating Inlet Airstream Density: 0.0750 lb/ft3
Static Efficiency: 73.25% Mechanical Efficiency: 76.20%
Maximum Operating Temperature: 300 Deg F Maximum Safe Operating Speed: 2425 rpm

Sound Power Level Ratings Levels expressed in dB (power levels reference 10^(-12) watts)
Center Frequency (Hz): 63 125 250 500 1000 2000 4000 8000
Octave Bands: 1 2 3 4 5 6 7 8
Total Fan Power Levels*: 84. 84. 85. 79.6 79. 75. 70.6 63.6
Inlet Power Levels**: 81. 81. 82. 76.6 76. 72. 67.6 60.6
Outlet Power Levels**: 81. 81. 82. 76.6 76. 72. 67.6 60.6
Std Fan Housing Attenuation: -5. -8. -11. -12. -10. -9. -12. -13.
Housing Radiated Power
79. 76. 74. 67.6 69. 66. 58.6 50.6
Levels:
*As corrected for point of operation (location on fan curve)
**Unsilenced Inlet and Outlet power ratings are 3 dB lower than total fan power levels under the assumption that "half" of the sound power
can be attributed to each opening. Silenced power ratings include this 3 dB reduction as well as the silencer attenuation.

Estimated Sound Pressure Levels Expressed in dB (pressure levels reference 2x10 -7 microbar)

Directivity/Reflection Factor (Q) is 2, hemispherical radiation; Distance is 10 ft.; A-weighting is in use.

This fan is connected to both inlet and outlet ducting which routes most sound away from the designated sound
measurement location. The Housing Radiated Sound Power levels are the basis for sound pressure level
calculations.

The estimated sound pressure level outside the fan due to Housing Radiated Noise is 55.9 dBA at 10.0 feet.

Your Representative: The New York Blower Company certifies that the
Niagara Industrial Equipment Corp. GPA fan is licensed to bear the AMCA Air
Performance Seal. The ratings shown are based on
56 12th Avenue Extension tests and procedures performed in accordance with
Kalookan City 1400 AMCA Publication 211 and comply with the
Philippines requirements of the AMCA Certified Ratings program.
Phone: (632) 366-5562
Fax: (632) 362-4257 AMCA Licensed for Air Performance without
Appurtenances. Power (bhp) excludes drives.
E-Mail: sales@niagarafans.com
Performance shown is for installation type: B - Free
inlet, Ducted outlet.

Version: 1.71.1000 (Feb, 2002) Printed: 05/02/2023 PDF


The New York Blower Company
Fan-to-Size
GPA - PLR Volume Flow Rate: 2,920 m3/hr
15 SISW Backward Inclined Fan Static Press.: 2.0 in wg
Arr.: 10 Speed: 1631 rpm Density: 0.0750 lb/ft3
Power: 1.01 bhp/1.5HP Outlet Velocity: 1332 ft/min
Tag: FREB-1720

1.00
2.0

Fan Input Power (bhp)


Fan Static Pressure (in wg)

0.75
1.5

0.50
1.0

0.5 0.25

0.0 0.00
0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000
Volume Flow Rate (m3/hr)
AMCA Licensed for Air Performance without Appurtenances. Power (bhp) excludes drives.
Performance shown is for installation type: B - Free inlet, Ducted outlet.
Your Sales Representative:
[v1.71.1000 -- Feb, 2002] Date Printed: 05/02/23 Niagara Industrial Equipment Corp.
Copyright ©1999 The New York Blower Company. Phone: (632) 366-5562
Version: 1.71.1000 (Feb, 2002) Printed: 05/02/2023 PDF
NYB BI-SISW CENTRIFUGAL FAN (GPA)
MODEL: Size 15" Arr.10
REFERENCE : NYB Bulletin No. 051

CUSTOMER: COSMETIQUE ASIA CORPORATION

PROJECT: PROPOSED MANUFACTURING PLANT RENOVATION

ATTENTION: MR. CHRISTIAN REYES

REFERENCE: CAC 23-001-A

SUBMITTED BY: DATE: 05/02/2023

AIR FLOW SP FAN ELECTRICAL


FAN TAG QTY ( CMH ) ( IN ) HP ACCESSORIES
RPM CHARACTERISTICS
FREB-1720 2 2,920 2 1631 1-1/2 230 / 1 / 60 VIBRATION ISOLATOR

FRP COATED AIRSTREAM PARTS ONLY

MOTOR CONTROLLER
PMEF-1500
(NBX 35)
2,550 CMH @ 0.5 IN
PROPELLER FAN DIRECT DRIVE
MODEL: NBX-35
REFERENCE: PAGE 1 OF 1

CUSTOMER: COSMETIQUE ASIA CORPORATION

PROJECT: PROPOSED MANUFACTURING PLANT RENOVATION


ATTENTION: MR. CHRISTIAN REYES
REFERENCE: CAC 23-001-A
SUBMITTED BY: DATE: 05/02/2023

A
450
350
REAR GUARD
SHUTTER

AIR FLOW

BLADE
450

AIR FLOW
WIRING BOX

CL

SIDE VIEW VIEW FROM "A"

NOTE: DIMENSION'S ARE IN MM.

AIR FLOW SP FAN RPM ELECTRICAL


FAN TAG QTY ( CMH ) ( IN ) HP ACCESSORIES
CHARACTERISTICS

PMEF-1500 1 2,550 0.5 1200 120W 230 / 1 / 60 REAR GUARD

SHUTTER

MOTOR CONTROLLER
FGEF-1000 & RMEF-1000
(NBX 30)
1,700 CMH @ 0.5 IN
PROPELLER FAN DIRECT DRIVE
MODEL: NBX-30
REFERENCE: PAGE 1 OF 1

CUSTOMER: COSMETIQUE ASIA CORPORATION


PROJECT: PROPOSED MANUFACTURING PLANT RENOVATION
ATTENTION: MR. CHRISTIAN REYES
REFERENCE: CAC 23-001-A
SUBMITTED BY: DATE: 05/02/2023

A
373

SHUTTER REAR GUARD 300

AIR FLOW
MOTOR BLADE
373

AIR FLOW WIRING BOX

CL

SIDE VIEW VIEW FROM "A"

NOTE: DIMENSION'S ARE IN MM.

AIR FLOW SP FAN RPM


( CMH ) ( IN ) ELECTRICAL
FAN TAG QTY HP ACCESSORIES
CHARACTERISTICS

FGEF-1000 & 3 1,700 0.5 1100 60W 230 / 1 / 60 SHUTTER

RMEF-1000 REAR GUARD

MOTOR CONTROLLER
The New York Blower Company Project: PROPOSED MFG.
Fan-to-Size Location: PLANT RENOVATION
Fan Selection Data Contact: COSMETIQUE ASIA CORP.
Fan Tagging: IEF-1

Fan Design
Product: Forward Curve DWDI Drive type: Direct
Size/Model: 9 Wheel Diameter: 100.0 %
Wheel Type: FC
Wheel Material: Mild Steel
Wheel Width: 100.0 %

Operating Conditions
Volume Flow Rate: 1,020 m3/hr Fan Speed: 638 rpm
Fan Static Pressure: 1.0 in wg Fan Input Power: 0.225 bhp
Outlet Velocity: 666 ft/min VP/SP ratio: 0.0277
Operating Inlet Airstream Density: 0.0750 lb/ft3
Static Efficiency: 71.87% Mechanical Efficiency: 73.03%
Maximum Operating Temperature: 100 Deg F Maximum Safe Operating Speed: 1700 rpm

Sound Power Level Ratings Levels expressed in dB (power levels reference 10^(-12) watts)
Center Frequency (Hz): 63 125 250 500 1000 2000 4000 8000
Octave Bands: 1 2 3 4 5 6 7 8
Total Fan Power Levels*: 63.6 77.7 77.6 69.8 68.5 65.5 61.2 53.9
Inlet Power Levels**: 60.6 74.7 74.6 66.8 65.5 62.5 58.2 50.9
Outlet Power Levels**: 60.6 74.7 74.6 66.8 65.5 62.5 58.2 50.9
Std Fan Housing Attenuation: 0. 0. 0. 0. 0. 0. 0. 0.
Housing Radiated Power
63.6 77.7 77.6 69.8 68.5 65.5 61.2 53.9
Levels:
*As corrected for point of operation (location on fan curve)
**Unsilenced Inlet and Outlet power ratings are 3 dB lower than total fan power levels under the assumption that "half" of the sound power
can be attributed to each opening. Silenced power ratings include this 3 dB reduction as well as the silencer attenuation.

Estimated Sound Pressure Levels Expressed in dB (pressure levels reference 2x10 -7 microbar)

Directivity/Reflection Factor (Q) is 2, hemispherical radiation; Distance is 10 ft.; A-weighting is in use.

This fan is connected to both inlet and outlet ducting which routes most sound away from the designated sound
measurement location. The Housing Radiated Sound Power levels are the basis for sound pressure level
calculations.

The estimated sound pressure level outside the fan due to Housing Radiated Noise is 57.0 dBA at 10.0 feet.

Your Representative:
Niagara Industrial Equipment Corp.
56 12th Avenue Extension
Kalookan City 1400
Philippines
Phone: (632) 366-5562
Fax: (632) 362-4257
E-Mail: sales@niagarafans.com

Version: 1.71.1000 (Feb, 2002) Printed: 05/02/2023 PDF


The New York Blower Company
Fan-to-Size
Forward Curve DWDI Volume Flow Rate: 1,020 m3/hr
9 FC Fan Static Press.: 1.0 in wg
Speed: 638 rpm Density: 0.0750 lb/ft3
Power: 0.225 bhp Outlet Velocity: 666 ft/min
Tag: IEF-1

1.00
1.00

Fan Input Power (bhp)


Fan Static Pressure (in wg)

0.75
0.75

0.50 0.50

0.25 0.25

0.00 0.00
0 500 1000 1500 2000 2500 3000 3500 4000
Volume Flow Rate (m3/hr)
Your Sales Representative:
[v1.71.1000 -- Feb, 2002] Date Printed: 05/02/23 Niagara Industrial Equipment Corp.
Copyright ©1999 The New York Blower Company. Phone: (632) 366-5562
Version: 1.71.1000 (Feb, 2002) Printed: 05/02/2023 PDF
NIAGAR FORWARD CURVE FAN
MODEL : DIDW-FC 9 TH (DIRECT DRIVE)

REFERENCE PAGE 1 OF 1

CUSTOMER: COSMETIQUE ASIA CORPORATION

PROJECT: PROPOSED MANUFACTURING PLANT RENOVATION


ATTENTION: MR. CHRISTIAN REYES
REFERENCE: CAC 23-001-A DATE: 05/02/2023

560
460 AIR FLOW 313

279
AIR FLOW
545

545
SIDE SECTION DISCHARGE / OUTLET VIEW

560
406
396
545

SUCTION /
INLET

SUCTION / INLET VIEW


NOTE: DIMENSION'S ARE IN MILLIMETRES

AIR FLOW SP FAN ELECTRICAL


FAN TAG QTY HP ACCESSORIES
( CMH ) ( IN ) RPM CHARACTERISTICS
IEF-1 1 1,020 1 250W 638 230 / 1 / 60 VIBRATION ISOLATOR

MOTOR CONTROLLER
TEF-1-1, TEF-1-2
127 CMH @ 0.65 IN

200

150

100

50

0
25 50 75 100 125 150 175 200
TEF-2, TEF-3 (25ALH) 850 CMH @ 0.25 IN
FRPEF-500
(NBX 30)
850 CMH @ 0.8 IN
PROPELLER FAN DIRECT DRIVE
MODEL: NBX-30
REFERENCE: PAGE 1 OF 1

CUSTOMER: COSMETIQUE ASIA CORPORATION


PROJECT: PROPOSED MANUFACTURING PLANT RENOVATION
ATTENTION: MR. CHRISTIAN REYES
REFERENCE: CAC 23-001-A
SUBMITTED BY: DATE: 05/02/2023

A
373

SHUTTER REAR GUARD 300

AIR FLOW
MOTOR BLADE
373

AIR FLOW WIRING BOX

CL

SIDE VIEW VIEW FROM "A"

NOTE: DIMENSION'S ARE IN MM.

AIR FLOW SP FAN RPM


( CMH ) ( IN ) ELECTRICAL
FAN TAG QTY HP ACCESSORIES
CHARACTERISTICS

FRPEF-500 1 850 0.8 1100 60W 230 / 1 / 60 SHUTTER

REAR GUARD

MOTOR CONTROLLER
RMEF2-1500 & RMEF3-1500
(NBX 35)
2,550 CMH @ 0.5 IN
PROPELLER FAN DIRECT DRIVE
MODEL: NBX-35
REFERENCE: PAGE 1 OF 1

CUSTOMER: COSMETIQUE ASIA CORPORATION

PROJECT: PROPOSED MANUFACTURING PLANT RENOVATION


ATTENTION: MR. CHRISTIAN REYES
REFERENCE: CAC 23-001-A
SUBMITTED BY: DATE: 05/02/2023

A
450
350
REAR GUARD
SHUTTER

AIR FLOW

BLADE
450

AIR FLOW
WIRING BOX

CL

SIDE VIEW VIEW FROM "A"

NOTE: DIMENSION'S ARE IN MM.

AIR FLOW SP FAN RPM ELECTRICAL


FAN TAG QTY ( CMH ) ( IN ) HP ACCESSORIES
CHARACTERISTICS

RMEF2-1500 & 2 2,550 0.5 1200 120W 230 / 1 / 60 REAR GUARD

RMEF3-1500 SHUTTER

MOTOR CONTROLLER
The New York Blower Company Project: PROPOSED MFG.
Fan-to-Size Location: PLANT RENOVATION
Fan Selection Data Contact: COSMETIQUE ASIA CORP.
Fan Tagging: PSRFB-1500

Fan Design
Product: GPA - PLR Arrangement: 10
Size/Model: 15 Drive type: Belt
Wheel Type: SISW Backward Inclined
Wheel Material: Mild Steel
Wheel Width: 100.0 % Wheel Diameter: 100.0 %

Operating Conditions
Volume Flow Rate: 2,550 m3/hr Fan Speed: 1310 rpm
Fan Static Pressure: 1.2 in wg Fan Input Power/Motor HP: 0.7 bhp/1HP
Outlet Velocity: 1163 ft/min VP/SP ratio: 0.0704
Operating Inlet Airstream Density: 0.0750 lb/ft3
Static Efficiency: 71.80% Mechanical Efficiency: 74.75%
Maximum Operating Temperature: 300 Deg F Maximum Safe Operating Speed: 2425 rpm

Sound Power Level Ratings Levels expressed in dB (power levels reference 10^(-12) watts)
Center Frequency (Hz): 63 125 250 500 1000 2000 4000 8000
Octave Bands: 1 2 3 4 5 6 7 8
Total Fan Power Levels*: 80.1 79.2 79.2 75.1 73.2 69.2 63.3 57.2
Inlet Power Levels**: 77.1 76.2 76.2 72.1 70.2 66.2 60.3 54.2
Outlet Power Levels**: 77.1 76.2 76.2 72.1 70.2 66.2 60.3 54.2
Std Fan Housing Attenuation: -5. -8. -11. -12. -10. -9. -12. -13.
Housing Radiated Power
75.1 71.2 68.2 63.1 63.2 60.2 51.3 44.2
Levels:
*As corrected for point of operation (location on fan curve)
**Unsilenced Inlet and Outlet power ratings are 3 dB lower than total fan power levels under the assumption that "half" of the sound power
can be attributed to each opening. Silenced power ratings include this 3 dB reduction as well as the silencer attenuation.

Estimated Sound Pressure Levels Expressed in dB (pressure levels reference 2x10 -7 microbar)

Directivity/Reflection Factor (Q) is 2, hemispherical radiation; Distance is 10 ft.; A-weighting is in use.

This fan is connected to both inlet and outlet ducting which routes most sound away from the designated sound
measurement location. The Housing Radiated Sound Power levels are the basis for sound pressure level
calculations.

The estimated sound pressure level outside the fan due to Housing Radiated Noise is 50.3 dBA at 10.0 feet.

Your Representative: The New York Blower Company certifies that the
Niagara Industrial Equipment Corp. GPA fan is licensed to bear the AMCA Air
Performance Seal. The ratings shown are based on
56 12th Avenue Extension tests and procedures performed in accordance with
Kalookan City 1400 AMCA Publication 211 and comply with the
Philippines requirements of the AMCA Certified Ratings program.
Phone: (632) 366-5562
Fax: (632) 362-4257 AMCA Licensed for Air Performance without
Appurtenances. Power (bhp) excludes drives.
E-Mail: sales@niagarafans.com
Performance shown is for installation type: B - Free
inlet, Ducted outlet.

Version: 1.71.1000 (Feb, 2002) Printed: 05/02/2023 PDF


The New York Blower Company
Fan-to-Size
GPA - PLR Volume Flow Rate: 2,550 m3/hr
15 SISW Backward Inclined Fan Static Press.: 1.2 in wg
Arr.: 10 Speed: 1310 rpm Density: 0.0750 lb/ft3
Power: 0.677 bhp/1HP Outlet Velocity: 1163 ft/min
Tag: PSRFB-1500

1.50 0.7

0.6
1.25

Fan Input Power (bhp)


Fan Static Pressure (in wg)

0.5
1.00
0.4
0.75
0.3
0.50
0.2

0.25 0.1

0.00 0.0
0 500 1000 1500 2000 2500 3000 3500 4000
Volume Flow Rate (m3/hr)
AMCA Licensed for Air Performance without Appurtenances. Power (bhp) excludes drives.
Performance shown is for installation type: B - Free inlet, Ducted outlet.
Your Sales Representative:
[v1.71.1000 -- Feb, 2002] Date Printed: 05/02/23 Niagara Industrial Equipment Corp.
Copyright ©1999 The New York Blower Company. Phone: (632) 366-5562
Version: 1.71.1000 (Feb, 2002) Printed: 05/02/2023 PDF
NYB BI-SISW CENTRIFUGAL FAN (GPA)
MODEL: Size 15" Arr.10
REFERENCE : NYB Bulletin No. 051

CUSTOMER: COSMETIQUE ASIA CORPORATION

PROJECT: PROPOSED MANUFACTURING PLANT RENOVATION

ATTENTION: MR. CHRISTIAN REYES

REFERENCE: CAC 23-001-A

SUBMITTED BY: DATE: 05/02/2023

AIR FLOW SP FAN ELECTRICAL


FAN TAG QTY ( CMH ) ( IN ) HP ACCESSORIES
RPM CHARACTERISTICS
PSRFB-1500 1 2,550 1.2 1310 1 230 / 1 / 60 VIBRATION ISOLATOR

MOTOR CONTROLLER
The New York Blower Company Project: PROPOSED MFG.
Fan-to-Size Location: PLANT RENOVATION
Fan Selection Data Contact: COSMETIQUE ASIA CORP.
Fan Tagging: SPPS-2400

Fan Design
Product: GPA - PLR Arrangement: 10
Size/Model: 18 Drive type: Belt
Wheel Type: SISW Backward Inclined
Wheel Material: Mild Steel
Wheel Width: 100.0 % Wheel Diameter: 100.0 %

Operating Conditions
Volume Flow Rate: 4,077 m3/hr Fan Speed: 1055 rpm
Fan Static Pressure: 1.2 in wg Fan Input Power/Motor HP: 0.8 bhp/1HP
Outlet Velocity: 1250 ft/min VP/SP ratio: 0.0813
Operating Inlet Airstream Density: 0.0750 lb/ft3
Static Efficiency: 74.13% Mechanical Efficiency: 78.53%
Maximum Operating Temperature: 300 Deg F Maximum Safe Operating Speed: 1969 rpm

Sound Power Level Ratings Levels expressed in dB (power levels reference 10^(-12) watts)
Center Frequency (Hz): 63 125 250 500 1000 2000 4000 8000
Octave Bands: 1 2 3 4 5 6 7 8
Total Fan Power Levels*: 79.9 78.9 78.9 77.9 74.9 68.7 62.9 54.9
Inlet Power Levels**: 76.9 75.9 75.9 74.9 71.9 65.7 59.9 51.9
Outlet Power Levels**: 76.9 75.9 75.9 74.9 71.9 65.7 59.9 51.9
Std Fan Housing Attenuation: -5. -9. -12. -15. -12. -11. -13. -14.
Housing Radiated Power
74.9 69.9 66.9 62.9 62.9 57.7 49.9 40.9
Levels:
*As corrected for point of operation (location on fan curve)
**Unsilenced Inlet and Outlet power ratings are 3 dB lower than total fan power levels under the assumption that "half" of the sound power
can be attributed to each opening. Silenced power ratings include this 3 dB reduction as well as the silencer attenuation.

Estimated Sound Pressure Levels Expressed in dB (pressure levels reference 2x10 -7 microbar)

Directivity/Reflection Factor (Q) is 2, hemispherical radiation; Distance is 10 ft.; A-weighting is in use.

This fan is connected to both inlet and outlet ducting which routes most sound away from the designated sound
measurement location. The Housing Radiated Sound Power levels are the basis for sound pressure level
calculations.

The estimated sound pressure level outside the fan due to Housing Radiated Noise is 49.4 dBA at 10.0 feet.

Your Representative: The New York Blower Company certifies that the
Niagara Industrial Equipment Corp. GPA fan is licensed to bear the AMCA Air
Performance Seal. The ratings shown are based on
56 12th Avenue Extension tests and procedures performed in accordance with
Kalookan City 1400 AMCA Publication 211 and comply with the
Philippines requirements of the AMCA Certified Ratings program.
Phone: (632) 366-5562
Fax: (632) 362-4257 AMCA Licensed for Air Performance without
Appurtenances. Power (bhp) excludes drives.
E-Mail: sales@niagarafans.com
Performance shown is for installation type: B - Free
inlet, Ducted outlet.

Version: 1.71.1000 (Feb, 2002) Printed: 05/02/2023 PDF


The New York Blower Company
Fan-to-Size
GPA - PLR Volume Flow Rate: 4,077 m3/hr
18 SISW Backward Inclined Fan Static Press.: 1.2 in wg
Arr.: 10 Speed: 1055 rpm Density: 0.0750 lb/ft3
Power: 0.836 bhp/1HP Outlet Velocity: 1250 ft/min
Tag: SPPS-2400

1.25 0.8

0.7

Fan Input Power (bhp)


Fan Static Pressure (in wg)

1.00
0.6

0.5
0.75
0.4
0.50 0.3

0.2
0.25
0.1

0.00 0.0
0 1000 2000 3000 4000 5000 6000
Volume Flow Rate (m3/hr)
AMCA Licensed for Air Performance without Appurtenances. Power (bhp) excludes drives.
Performance shown is for installation type: B - Free inlet, Ducted outlet.
Your Sales Representative:
[v1.71.1000 -- Feb, 2002] Date Printed: 05/02/23 Niagara Industrial Equipment Corp.
Copyright ©1999 The New York Blower Company. Phone: (632) 366-5562
Version: 1.71.1000 (Feb, 2002) Printed: 05/02/2023 PDF
NYB BI-SISW CENTRIFUGAL FAN (GPA)
MODEL: Size 18" Arr.10
REFERENCE : NYB Bulletin No. 051

CUSTOMER: COSMETIQUE ASIA CORPORATION


PROJECT: PROPOSED MANUFACTURING PLANT RENOVATION

ATTENTION: MR. CHRISTIAN REYES


REFERENCE: CAC 23-001-A
SUBMITTED BY: DATE: 05/02/2023

AIR FLOW SP ELECTRICAL


FAN TAG QTY ( IN ) FAN RPM HP ACCESSORIES
( CMH ) CHARACTERISTICS
SPPS-2400 1 4,077 1.2 1055 1 230 / 1 / 60 VIBRATION ISOLATOR

MOTOR CONTROLLER
TEF-1-3 TO TEF-1-6
127 CMH @ 0.65 IN

200

150

100

50

0
25 50 75 100 125 150 175 200
CEF-3
510 CMH @ 0.8 IN

400

350

300

250

200

150

100

50

0
100 200 300 400 500 600 700 800
CNEF-1500
(NBX 35)
2,550 CMH @ 0.5 IN
PROPELLER FAN DIRECT DRIVE
MODEL: NBX-35
REFERENCE: PAGE 1 OF 1

CUSTOMER: COSMETIQUE ASIA CORPORATION

PROJECT: PROPOSED MANUFACTURING PLANT RENOVATION


ATTENTION: MR. CHRISTIAN REYES
REFERENCE: CAC 23-001-A
SUBMITTED BY: DATE: 05/02/2023

A
450
350
REAR GUARD
SHUTTER

AIR FLOW

BLADE
450

AIR FLOW
WIRING BOX

CL

SIDE VIEW VIEW FROM "A"

NOTE: DIMENSION'S ARE IN MM.

AIR FLOW SP FAN RPM ELECTRICAL


FAN TAG QTY ( CMH ) ( IN ) HP ACCESSORIES
CHARACTERISTICS

CCNEF-1500 1 2,550 0.5 1200 120W 230 / 1 / 60 REAR GUARD

SHUTTER

MOTOR CONTROLLER
RREF-500 (25ALH) 850 CMH @ 0.25 IN