Proportional Relief Valves Rzmo-Aes and Hzmo-A
Proportional Relief Valves Rzmo-Aes and Hzmo-A
(1) Serial communication interface always present, also for -BC, -BP and -EH options
                                                                                                                                                           F065
 3    HYDRAULIC CHARACTERISTICS (based on mineral oil ISO VG 46 at 50 °C)
Hydraulic symbols
4 MAIN CHARACTERISTICS
                                                                                                                                                                         2
1 = RZMO-A; RZMO-AE; RZMO-AES; HZMO-A
                                                                                                                                              Pressure at port P [bar]
Note:
The presence of counter pressure at port T                                                                         1
can affect the effective pressure regulation.
                                                                                                    Flow [l/min]
5.4   Dynamic response
      The response times in section  have to be considered as average values.
      The pressure variation in consequence of a modification of the reference input signal to the valve is affected by the stiffness of the hydraulic circuit:
      greater is the stiffness of the circuit, faster is the dynamic response.
 6        GENERAL NOTES
RZMO and HZMO proportional valves are CE marked according to the applicable Directives (e.g. Immunity/Emission EMC Directive and Low Voltage Directive).
Installation, wirings and start-up procedures must be performed according to the general prescriptions shown in table F003 and in the installation notes
supplied with relevant components.
The electrical signals of the valve (e.g. monitor signals) must not be directly used to activate safety functions, like to switch-ON/OFF the machine’s safety
components, as prescribed by the European standards (Safety requirements of fluid technology systems and components-hydraulics, EN-982).
                           MAIN CONNECTOR
                            7 PIN - STANDARD
                                                                                  SCALE                BIAS
       (driver view)
RAMPS
                               100                                                                                                              RD                    쩨
      ON                       130                                                                                                              RU                    쩨
          ON                   160
                                                                                                                                                B1                    쩨
                ON      200 (Standard)
      ON        ON             230                                                                                                              S1                    쩨
          ON ON                270
      ON ON ON                 300                              B1:   positive bias adjust
      ON ON          ON        380                              S1:   positive scale adjust
      ON        ON ON          430
                                                                RU:   ramp for increasing reference signal
          ON ON ON             470
                                                                RD:   ramp for decreasing reference signal
      ON ON ON ON              500
                                                               SW:    dither frequency selector (see table beside)
      The dither frequency is factory pre-
      set at 200 Hz and its regulation may
      be adjusted after contact with Atos
      technical department
                       A         V+                Power supply 24 VDC for solenoid power stage and driver logic                                          Input - power supply
                       B         V0                Power supply 0 VDC for solenoid power stage and driver logic                                           Gnd - power supply
                                 AGND              Ground - signal zero for MONITOR signal                                                                Gnd - analog signal
              C (1)
                                 ENABLE            Enable (24 VDC) or disable (0 VDC) the driver                              (for /Q option)             Input - on/off signal
                       D         INPUT+            Reference analog input: 0÷+10 VDC maximum range                            (4÷20 mA for /I option)
                                                                                                                                                      Input - analog signal
                       E         INPUT -           Normal working range 0÷+10 VDC                                             (4÷20 mA for /I option)
                       F         MONITOR           Monitor analog output: 0÷+5 VDC maximum range; 1 V = 1 A                                               Output - analog signal
                       G         EARTH             Internally connected to the driver housing
Note:                  (1) with /Q option ENABLE signal replaces AGND on pin C; MONITOR signal is reffered to pin B.
                       A minimum time of 60ms to 160ms have be considered between the driver energizing with the 24 VDC power supply and when the valve is ready
                       to operate. During this time the current to the valve coils is switched to zero
                                                                                                                                                                                  F065
11               DIGITAL INTEGRAL DRIVERS -AES - OPTIONS
Following options are available to adapt standard execution to special application requirements:
11.1 Option /Q
 To enable the driver, supply 24Vdc on pin C referred to pin B: when the enable signal is set to zero the valve status is software selectable, by factory
 default the valve functioning is disabled (zero current to the solenoid) but the driver current output stage is still active. For the complete list of selectable
 status, see tab. G115.
11.2 Option /Z
 It provides, on the 12 pin main connector, the following additional features:
     Logic power supply
     Separated power supply for the solenoid (pin 1, 2) and for the digital electronic circuits (pin 9, 10).
     Cutting solenoid power supply allows to interrupt the valve functioning but keeping energized the digital electronics thus avoiding fault conditions of the
     machine fieldbus controller. This condition allows to realize safety systems in compliance with European Norms EN13849-1 (ex EN954-1).
     Enable Input Signal
     To enable the driver, supply 24Vdc on pin 3 referred to pin 2: when the enable signal is set to zero the valve status is software selectable, by factory
     default the valve functioning is disabled (zero current to the solenoid) but the driver current output stage is still active. For the complete list of selectable
     status, see tab. G115.
     Fault Output Signal
     Fault output signal indicates fault conditions of the driver (solenoid short circuits/not connected, reference signal cable broken for 4÷20mA input, etc.).
     Fault presence corresponds to 0 VDC, normal working corresponds to 24VDC (pin 11 referred to pin 2): Fault status is not affected by the Enable input signal.
                                                                                                                                   COMMUNICATION CONNECTOR
                 MAIN CONNECTOR                                                                                                      5 PIN                                5 PIN
                     7 PIN - STANDARD                                                                                          PROFIBUS DP (-BP)                       CANopen (-BC)
                                                                                                                                                                                           (driver view)
                                                                               SCALE              BIAS
 (driver view)
LINEARIZATION RAMPS
                     12 PIN - OPTION /Z
                                                                                                                                     5 PIN
                                                                                                                                   Serial (-PS)
 (driver view)
(driver view)
                                                                                                                                                COMMUNICATION CONNECTOR
                     MAIN CONNECTOR                                                                                                        4 PIN (input)
                      7 PIN - STANDARD                                                                                                    EtherCAT (-EH)
                                                                                                                                                              (driver side)
 (driver side)
SCALE BIAS
                                                                                                                                                                               4 PIN (output)
                                                                                                                                                                              EtherCAT (-EH)
                                                                                                                                                                                                (driver side)
                                                                             LINEARIZATION                RAMPS
                      12 PIN - OPTION /Z
                                                                                                                                              5 PIN
                                                                                                                                            Serial (-PS)
 (driver side)
                                                                                                                                                              (driver side)
Note: for the electronic connections of 7 or 12 pin main connector, see section 12.1
14 MODEL CODES OF POWER SUPPLY AND COMMUNICATION CONNECTORS (to be ordered separately)
15 SOFTWARE TOOLS
The driver configuration and parameters can be easily set with the Atos E-SW programming software, available in four different versions according to the
driver’s communication execution: E-SW-PS (Serial), E-SW-BC (CANopen), E-SW-BP (PROFIBUS DP), E-SW-EH (EtherCAT). Programming software
E-SW-BC, E-SW-BP, E-SW-EH for BC, BP and -EH drivers, can be also used to modify the valve’s parameterization through the serial communication inter-
face, without disconnecting the valve from the machine’s bus line.
For a more detailed description of software interface, PC requirements, adapters, cables and terminators, please refer to technical table G500.
Programming software, must be ordered separately:
 E-SW-*     (mandatory - first supply) = Dvd including E-SW-* software installer and operator manuals; it allows the registration to Atos digital service
 E-SW-*-N (optional - next supplies) = as above but not allowing the registration to Atos digital service
On first supply of the E-SW-* software, it is required to apply for the registration in the Atos download area: www.download.atos.com.
Once the registration is completed, the password will be sent by email.
The software remains active for 10 days from the installation date and then it stops until the user inputs his password.
With the password you can also download, in your personal area, the latest releases of the Atos software, manuals, drivers and configuration files.
                                                                                                                                                                                                F065
16      INSTALLATION DIMENSIONS [mm]
ZH-7P or ZM-7P
                                                                                           
                                                                                                 
                             RZMO-AE
                             RZMO-AES-* (dotted line)
                                                                                                                      
Mass: 4 Kg
ZH-7P or ZM-7P
                                                                                                 
                             RZMO-AES-EH*
                                                               
Mass: 4,1 Kg
                                                                                                                         
                                                                                                                                       666
     ISO 4401: 2000
     Mounting surface: 4401-03-02-0-05
     (see table P005)                                      HZMO-A
     Fastening bolts:
     4 socket head screws M5 bolts class 12.9
     Tightening torque = 8 Nm                                                                                                        Mass: 2,8 Kg
     Seals: 4 OR 108