0% found this document useful (0 votes)
43 views13 pages

Calculation

The document contains details of lighting design for rooms on the 1st and 2nd floors of a building. It includes the room location, size, lighting requirements, fixture type and other technical specifications. A lighting intensity calculation chart is also provided to calculate the required number and type of light fixtures needed to achieve the desired lighting levels in each room.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
43 views13 pages

Calculation

The document contains details of lighting design for rooms on the 1st and 2nd floors of a building. It includes the room location, size, lighting requirements, fixture type and other technical specifications. A lighting intensity calculation chart is also provided to calculate the required number and type of light fixtures needed to achieve the desired lighting levels in each room.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 13

ROOM SIZE Lighting Fire Alarm Lamp

No. LOCATION WIDTH DEPTH AREA HIGHT LUX S/H/F Code


x(m) y(m) A(m2) z(m)

1 1st Floor

1 Office 1FL 2.40 2.90 6.96 2.8 300 h 4.60


2 President room 5.00 5.00 25.00 2.8 300 h 4.60
3 Meeting room 2.40 2.90 6.96 2.8 300 4.60
4 Guest room 6.50 42.00 273.00 3 200 3.60
5 Lobby 7.00 5.00 35.00 6 250 4.60

2 2nd Floor

1 Office 2FL 16.00 36.00 576.00 4 200 3.60


2 Meeting room 11.00 8.00 88.00 2.8 300 4.60
3 Accounting room 5.00 5.00 25.00 2.8 300 4.60
ROOM COEFICIENT UTILIZATION
LIGHTING FIXTURE TYPE
INDEX BATTEN V-SHAPE REFLECTOR OPEN METAL MIROR PRISMA PARABOLIC
0.3 0.30 0.33 0.35 0.38 0.36 0.37 0.22 0.35
0.4 0.30 0.33 0.35 0.38 0.36 0.37 0.22 0.35
0.5 0.30 0.33 0.35 0.38 0.36 0.37 0.22 0.35
0.6 0.30 0.33 0.35 0.38 0.36 0.37 0.22 0.35
0.7 0.34 0.37 0.40 0.42 0.41 0.41 0.25 0.38
0.8 0.38 0.41 0.44 0.46 0.45 0.45 0.27 0.41
0.9 0.41 0.44 0.48 0.49 0.48 0.48 0.29 0.43
1.0 0.43 0.47 0.51 0.52 0.50 0.50 0.30 0.45
1.3 0.49 0.53 0.57 0.58 0.55 0.54 0.34 0.48
1.4 0.51 0.56 0.59 0.60 0.57 0.56 0.35 0.49
1.5 0.53 0.58 0.61 0.62 0.59 0.57 0.36 0.50
1.75 0.56 0.61 0.65 0.65 0.61 0.59 0.38 0.52
2.0 0.59 0.64 0.68 0.67 0.63 0.61 0.40 0.53
1.25 0.61 0.66 0.70 0.69 0.62 0.62 0.41 0.54
2.5 0.63 0.68 0.72 0.70 0.66 0.63 0.42 0.55
2.75 0.65 0.70 0.74 0.71 0.67 0.63 0.42 0.55
3.0 0.66 0.72 0.75 0.72 0.68 0.64 0.43 0.56
3.5 0.68 0.74 0.77 0.74 0.70 0.65 0.44 0.56
4.0 0.69 0.76 0.79 0.75 0.71 0.66 0.45 0.57
4.5 0.71 0.78 0.75 0.76 0.71 0.67 0.46 0.57
5.0 0.72 0.79 0.81 0.77 0.72 0.68 0.47 0.58
6.0 0.74 0.81 0.83 0.78 0.73 0.68 0.47 0.58
7.0 0.75 0.82 0.84 0.79 0.74 0.69 0.48 0.59
8.0 0.76 0.83 0.85 0.79 0.75 0.69 0.48 0.59
10.0 0.78 0.85 0.86 0.80 0.76 0.70 0.49 0.60
NO CU FIXTURE TYPE LUMENS MF
1.1 2 Batten Type FL 10W x 1 420
1.2 2 Batten Type FL 20W x 1 1,070
1.3 2 Batten Type FL 40W x 1 3,000
1.4 2 Batten Type FL 10W x 2 840
1.5 2 Batten Type FL 20W x 2 2,140
1.6 2 Batten Type FL 40W x 2 5,400

2.1 3 V-Shape Batten Type FL 10W x 1 420


2.2 3 V-Shape Batten Type FL 20W x 1 1,070
2.3 3 V-Shape Batten Type FL 40W x 1 3,000
2.4 3 V-Shape Batten Type FL 10W x 2 840
2.5 3 V-Shape Batten Type FL 20W x 2 2,140
2.6 3 V-Shape Batten Type FL 40W x 2 5,400

3.1 4 Reflector Type FL 10W x 1 420


3.2 4 Reflector Type FL 20W x 1 1,070
3.3 4 Reflector Type FL 40W x 1 3,000
3.4 4 Reflector Type FL 10W x 2 840
3.5 4 Reflector Type FL 20W x 2 2,140
3.6 4 Reflector Type FL 40W x 2 5,400

4.1 5 Recessed Open Type FL 20W x 1 1,070


4.2 5 Recessed Open Type FL 20W x 2 2,140
4.3 5 Recessed Open Type FL 20W x 3 3,210
4.4 5 Recessed Open Type FL 20W x 4 4,280
4.5 5 Recessed Open Type FL 40W x 1 3,000
4.6 5 Recessed Open Type FL 40W x 2 5,400
4.7 5 Recessed Open Type FL 40W x 3 8,100

5.1 6 Recessed Metal Louver Type FL 20W x 1 1,070


5.2 6 Recessed Metal Louver Type FL 20W x 2 2,140
5.3 6 Recessed Metal Louver Type FL 20W x 3 3,210
5.4 6 Recessed Metal Louver Type FL 20W x 4 4,280
5.5 6 Recessed Metal Louver Type FL 40W x 1 3,000
5.6 6 Recessed Metal Louver Type FL 40W x 2 5,400
5.7 6 Recessed Metal Louver Type FL 40W x 3 8,100

6.1 7 Recessed Miror Louver Type FL 20W x 1 1,070


6.2 7 Recessed Miror Louver Type FL 20W x 2 2,140
6.3 7 Recessed Miror Louver Type FL 20W x 3 3,210
6.4 7 Recessed Miror Louver Type FL 20W x 4 4,280
6.5 7 Recessed Miror Louver Type FL 40W x 1 3,000
6.6 7 Recessed Miror Louver Type FL 40W x 2 5,400
6.7 7 Recessed Miror Louver Type FL 40W x 3 8,100

7.1 8 Recessed Prismatic Panel Type FL 20W x 1 1,070


7.2 8 Recessed Prismatic Panel Type FL 20W x 2 2,140
7.3 8 Recessed Prismatic Panel Type FL 20W x 3 3,210
7.4 8 Recessed Prismatic Panel Type FL 20W x 4 4,280
7.5 8 Recessed Prismatic Panel Type FL 40W x 1 3,000
7.6 8 Recessed Prismatic Panel Type FL 40W x 2 5,400
7.7 8 Recessed Prismatic Panel Type FL 40W x 3 8,100

8.1 9 Recessed Parabolic ML Type FL 20W x 1 1,070


8.2 9 Recessed Parabolic ML Type FL 20W x 2 2,140
8.3 9 Recessed Parabolic ML Type FL 20W x 3 3,210
8.4 9 Recessed Parabolic ML Type FL 20W x 4 4,280
8.5 9 Recessed Parabolic ML Type FL 40W x 1 3,000
8.6 9 Recessed Parabolic ML Type FL 40W x 2 5,400
8.7 9 Recessed Parabolic ML Type FL 40W x 3 8,100

8.8 FL 20W x 5 5,350


8.9 FL 40W x 4 10,800
8.10 FCL 30W x 1 1,450
8.11 FCL 32W x 1 1,780
8.12 FCL 40W x 1 2,440
8.13 FDL 9W x 1 520
8.14 FDL 13W x 1 800
8.15 FDL 18W x 1 1,070
8.16 FDL 27W x 1 1,550
8.17 HF 100W x 1 4,200
8.18 HF 200W x 1 9,900
8.19 HF 250W x 1 12,700
8.20 HF 300W x 1 15,800
8.21 HF 400W x 1 22,000
8.22 HF 700W x 1 41,000
8.23 HF1000W x 1 59,500
8.24 IL 40W x 1 485
8.25 IL 60W x 1 810
8.26 IL 100W x 1 1,520
LIGHTING INTENSITY CALCULATION CHART CU : COEFICIENT UTILIZATION
PROJECT : PT. KYOSHA INDONESIA MF : MAINTENANCE FACTOR
N : NUMBER OF LUMINAIRES
ROOM SIZE Work Light Lamp ROOM REFLECTANCE PLAN
No. LOCATION LIGHTING FIXTURE TYPE LUMENS LUX WIDTH DEPTH AREA HIGHT h1 h2 H(m) INDEX c w f CU MF N N
x(m) y(m) A(m2) z(m) Kr (%) (%) (%) ( ea ) ( ea ) LUX
1 1st Floor
0 0
1 Office 1FL Recessed Open Type FL 40W x 2 5,400 300 2.40 2.90 6.96 2.80 0.00 2.80 2.80 0.50 70 50 10 0.38 0.90 1.1 34 300 9,022
2 President room Recessed Open Type FL 40W x 2 5,400 300 5.00 5.00 25.00 2.80 0.00 2.80 2.80 0.90 70 50 10 0.49 0.90 3.1 3 300 286
3 Meeting room Recessed Open Type FL 40W x 2 5,400 300 2.40 2.90 6.96 2.80 0.00 2.80 2.80 0.50 70 50 10 0.38 0.90 1.1 2 300 531
4 Guest room Reflector Type FL 40W x 2 5,400 200 6.50 42.00 273.00 3.00 0.00 3.00 3.00 1.90 70 50 10 0.65 0.90 17.3 16 200 185
5 Lobby Recessed Open Type FL 40W x 2 5,400 250 7.00 5.00 35.00 6.00 0.00 6.00 6.00 0.50 70 50 10 0.38 0.90 4.7 5 250 264

0.00 0.00 0.00 0.00 0.00 0.00 0.00


0.00 0.00 0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00 0.00 0.00
1 Office 2FL Reflector Type FL 40W x 2 5,400 200 16.00 36.00 576.00 4.00 0.00 4.00 4.00 2.80 70 50 10 0.74 0.90 32.0 32 200 200
2 Meeting room Recessed Open Type FL 40W x 2 5,400 300 11.00 8.00 88.00 2.80 0.00 2.80 2.80 1.70 70 50 10 0.62 0.90 8.8 9 300 308
3 Accounting room Recessed Open Type FL 40W x 2 5,400 300 5.00 5.00 25.00 2.80 0.00 2.80 2.80 0.90 70 50 10 0.49 0.90 3.1 3 300 286
4 File Room Reflector Type FL 40W x 2 5,400 200 6.00 6.00 36.00 4.00 0.00 4.00 4.00 0.80 70 50 10 0.44 0.90 3.4 4 200 238
5 Storage Reflector Type FL 40W x 2 5,400 200 12.00 10.00 120.00 3.00 0.00 3.00 3.00 1.80 70 50 10 0.65 0.90 7.6 8 200 211
6 Praying Room 150 2.50 5.00 12.50 2.80 0.00 2.80 2.80
FIRE ALARM CALCULATION SHEET for : CERES 94

No. Location Ceiling Area Covered Area Class Remarks


Height(m) X(m) Y(m) A(m2) m2 S
Smoke m2 Heat/Fixed
0 0 0.00 0.00 0.00
1 1st Floor S 0.00 0.00 0.00
0 0
1 Office 1FL 0.0m~3.0M 2.40 2.90 6.96 92.0 0.08 46.0 0.15 class-1
2 President room 0.0m~3.0M 5.00 5.00 25.00 92.0 0.27 46.0 0.54 class-1
3 Meeting room 0.0m~3.0M 2.40 2.90 6.96 92.0 0.08 46.0 0.15 class-1
4 Guest room 0.0m~3.0M 6.50 42.00 273.00 92.0 2.97 46.0 5.93 class-1
5 Lobby 6.0m~6.6m 7.00 5.00 35.00 53.4 0.66 26.7 1.31 class-1
0 0 0.00 0.00
0 0 0.00 0.00
0 0 0.00 0.00
2 2nd Floor 0.00 0.00
0 0
1 Office 2FL 0.0m~3.0M 16.00 36.00 576.00 92.0 6.26 46.0 12.52 class-1
2 Meeting room 0.0m~3.0M 11.00 8.00 88.00 92.0 0.96 46.0 1.91 class-1
3 Accounting room 0.0m~3.0M 5.00 5.00 25.00 92.0 0.27 46.0 0.54 class-1
4 File Room 0.0m~3.0M 6.00 6.00 36.00 92.0 0.39 46.0 0.78 class-1
5 Storage 0.0m~3.0M 12.00 10.00 120.00 92.0 1.30 46.0 2.61 class-1
6 Praying Room 0.0m~3.0M 2.50 5.00 12.50 92.0 0.14 46.0 0.27 class-1
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
FIRE ALARM CALCULATION SHEET for : CERES 94

No. Location Ceiling Area Covered Area Class Remarks


Height(m) X(m) Y(m) A(m2) m2 S
Smoke m2 Heat/Fixed
SOUND CALCULATION SHEET for :

input No. Location Ceiling Area


Height(m) X(m) Y(m) A(m2)

1 1 1st Floor 0 0 0 0
1 0 0 0 0 0 0
1 1 Office 1FL 2.8 2.40 2.90 6.96
1 2 President room 2.8 5.00 5.00 25.00
1 3 Meeting room 2.8 2.40 2.90 6.96
1 4 Guest room 3 6.50 42.00 273.00
1 5 Lobby 6 7.00 5.00 35.00
1 0 0 0 - 0.00 0.00
1 0 0 0 - 0.00 0.00
1 0 0 0 - 0.00 0.00
1 2 2nd Floor 0 - 0.00 0.00
1 0 0 0 - 0.00 0.00
1 1 Office 2FL 4 16.00 36.00 576.00
1 2 Meeting room 2.8 11.00 8.00 88.00
1 3 Accounting room 2.8 5.00 5.00 25.00
1 4 File Room 4 6.00 6.00 36.00
1 5 Storage 3 12.00 10.00 120.00
1 6 Praying Room 2.8 2.50 5.00 12.50
1
1
Type speaker Remarks
m2 Ceilig SP m2 Horn SP Code

1
2
46.0 0.15 6.96 3
46.0 0.54 25.00 4
46.0 0.15 6.96 5
46.0 5.93 273.00 6
46.0 0.76 35.00
0.00
0.00
0.00
0.00
0.00
46.0 12.52 576.00
46.0 1.91 88.00
46.0 0.54 25.00
46.0 0.78 36.00
46.0 2.61 120.00
46.0 0.27 12.50
27
28
Ceiling Ceiling Horn
Height Speaker 3W Speaker
0.0m~3.0M 46.00
3.0m~3.6m 41.86
3.6m~4.2m 38.64
4.2m~4.8m 34.04
4.8m~5.4m 32.66
5.4m~6.0m 29.44
26.68
23.92
21.16
18.4
15.64
VOLTAGE DROP CALCULATION for KAYABA INDONESIA PROJECT

FEEDER PANEL LOAD BREAKER LOAD LOAD CURRENT CURRENT LENGTH DROP CABLE SELECT DECIDED DROP %
NUMBER FROM TO TYPE POLE AF AT KW KVA A1 A2 m % mm2 mm2 NYY CABLE V REMARK

1 LVMDB -2 DB - OT MCCB 4 1000 1000 400 500 760 950 335 2 1,289.2 1200 NYY 4c - 300 mm2 x 4 8.2 2.15%

2 LVMDB -2 DB - OT MCCB 4 1000 1000 400 500 760 950 335 2 1,289.2 480 NYY 1c - 240 mm2 x 2 x 20.4 5.37%

3 LVMDB -2 DB - OT MCCB 4 1000 1000 400 500 760 950 335 2 1,289.2 1200 NYY 1c - 240 mm2 x 5 x 8.2 2.15%

TOTAL