Before installation, operation, maintenance or inspection of this product, thoroughly read through and
understand this manual and all of the associated manuals. Also, take care to handle the module properly and
safely.
This manual classifies the safety precautions into two categories:                     and                  .
Depending on the circumstances, procedures indicated by                   may also cause severe injury.
It is important to follow all precautions for personal safety.
Store this manual in a safe place so that it can be taken out and read whenever necessary. Always forward it
to the end user.
1. DESIGN PRECAUTIONS
• Make sure to have the following safety circuits outside of the PLC to ensure safe system operation even during
  external power supply problems or PLC failure.
  Otherwise, malfunctions may cause serious accidents.
  1) Most importantly, have the following: an emergency stop circuit, a protection circuit, an interlock circuit for
      opposite movements (such as normal vs. reverse rotation), and an interlock circuit (to prevent damage to the
      equipment at the upper and lower positioning limits).
  2) Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all
      outputs are turned off. Also, when an error that cannot be detected by the PLC CPU occurs in an input/output
      control block, output control may be disabled.
      External circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
  3) Note that the output current of the service power supply for sensors varies depending on the model and the
      absence/presence of extension blocks. If an overload occurs, the voltage automatically drops, inputs in the
      PLC are disabled, and all outputs are turned off.
      External circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
  4) Note that when an error occurs in a relay, triac or transistor output device, the output could be held either on or
      off.
      For output signals that may lead to serious accidents, external circuits and mechanisms should be designed to
      ensure safe machinery operation in such a case.
• Do not bundle the control line together with or lay it close to the main circuit or power line.
  As a guideline, lay the control line at least 100mm(3.94") or more away from the main circuit or power line.
  Noise may cause malfunctions.
• Make sure to ground the shield wire or shield of the shielded cable connected to a special analog input adaptor or
  special analog extension block at one point on the PLC.
  However, do not use common grounding with heavy electrical systems.
  Noise may cause malfunctions.
• Make sure to ground the shield wire or shield of the shielded cable connected to a special analog output adaptor
  or special analog extension block at one point on the analog device side.
  However, do not use common grounding with heavy electrical systems.
  Noise may cause malfunctions.
• Install module so that excessive force will not be applied to the power connectors or terminal blocks.
  Failure to do so may result in wire damage/breakage or PLC failure.
                                                    (1)
                                 Safety Precautions
                                 (Read these precautions before use.)
2. WIRING PRECAUTIONS
• Make sure to cut off all phases of the power supply externally before attempting wiring work.
  Failure to do so may cause electric shock or damages to the product.
• Connect the DC power supply wiring to the dedicated terminals described in this manual.
  If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will be
  burnt out.
• Do not wire vacant terminals externally.
  Doing so may damage the product.
• Perform class D grounding (grounding resistance: 100Ω or less) to the grounding terminal on the main unit.
  Do not use common grounding with heavy electrical systems.
• When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
  Failure to do so may cause fire, equipment failures or malfunctions.
• Make sure to observe the following precautions in order to prevent malfunctions under the influence of noise:
  - Do not bundle the power line or twisted shielded cable together with or lay it close to the main circuit, high-
      voltage line, or load line.
      Otherwise, noise disturbance and/or surge induction are likely to take place. As a guideline, lay the control line
      at least 100mm (3.94") or more away from the main circuit, high-voltage line, or load line.
  - Ground the shield of the analog input/output cable at one point on the signal receiving side.
      However, do not use common grounding with heavy electrical systems.
• Make sure to properly wire to the European terminal board in accordance with the following precautions.
  Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product.
  - The disposal size of the cable end should be 9 mm (0.35").
  - Tightening torque should be between 0.22 to 0.25 N•m.
  - Twist the end of strand wire and make sure there are no loose wires.
  - Do not solder-plate the electric wire ends.
  - Do not connect more than the specified number of wires or electric wires of unspecified size.
  - Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
                                                    (2)
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
         Foreword
         This manual describes the "analog" function of the MELSEC-F FX Series programmable controllers and
         should be read and understood before attempting to install or use the unit.
         Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
         it to the end user.
           This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
           licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
           rights which may occur as a result of using the contents noted in this manual.
                                                                                                                            1
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
         Outline Precautions
         • This manual provides information for the use of the FX3U Series Programmable Controllers. The manual
           has been written to be used by trained and competent personnel. The definition of such a person or
           persons is as follows;
             1) Any engineer who is responsible for the planning, design and construction of automatic equipment
                using the product associated with this manual should be of a competent nature, trained and qualified
                to the local and national standards required to fulfill that role. These engineers should be fully aware of
                all aspects of safety with regards to automated equipment.
             2) Any commissioning or service engineer must be of a competent nature, trained and qualified to the
                local and national standards required to fulfill that job. These engineers should also be trained in the
                use and maintenance of the completed product. This includes being completely familiar with all
                associated documentation for the said product. All maintenance should be carried out in accordance
                with established safety practices.
             3) All operators of the completed equipment should be trained to use that product in a safe and
                coordinated manner in compliance to established safety practices. The operators should also be
                familiar with documentation which is connected with the actual operation of the completed equipment.
            Note:   the term 'completed equipment' refers to a third party constructed device which contains or uses
                    the product associated with this manual
         • This product has been manufactured as a general-purpose part for general industries, and has not been
           designed or manufactured to be incorporated in a device or system used in purposes related to human life.
         • Before using the product for special purposes such as nuclear power, electric power, aerospace, medicine
           or passenger movement vehicles, consult with Mitsubishi Electric.
         • This product has been manufactured under strict quality control. However when installing the product
           where major accidents or losses could occur if the product fails, install appropriate backup or failsafe
           functions in the system.
         • When combining this product with other products, please confirm the standard and the code, or regulations
           with which the user should follow. Moreover, please confirm the compatibility of this product to the system,
           machine, and apparatus with which a user is using.
         • If in doubt at any stage during the installation of the product, always consult a professional electrical
           engineer who is qualified and trained to the local and national standards. If in doubt about the operation or
           use, please consult the nearest Mitsubishi Electric distributor.
         • Since the examples indicated by this manual, technical bulletin, catalog, etc. are used as a reference,
           please use it after confirming the function and safety of the equipment and system. Mitsubishi Electric will
           accept no responsibility for actual use of the product based on these illustrative examples.
         • This manual content, specification etc. may be changed without a notice for improvement.
         • The information in this manual has been carefully checked and is believed to be accurate; however, if you
           have noticed a doubtful point, a doubtful error, etc., please contact the nearest Mitsubishi Electric
           distributor.
         Registration
         • Microsoft® and Windows® are either registered trademarks or trademarks of Microsoft Corporation in the
           United States and/or other countries.
         • The company name and the product name to be described in this manual are the registered trademarks or
           trademarks of each company.
2
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                                           Table of Contents
      Table of Contents
      SAFETY PRECAUTIONS .................................................................................................. (1)
Common Items
1. Introduction A-1
                                                                                                                                                                        3
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                                           Table of Contents
4
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                                           Table of Contents
1. Outline B-3
2. Specifications B-7
3. Wiring B-11
                                                                                                                                                                       5
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                                            Table of Contents
8. Troubleshooting B-63
6
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                                        Table of Contents
1. Outline C-3
2. Specifications C-6
3. Wiring C-10
4. Programming C-15
6. Troubleshooting C-29
                                                                                                                                                                    7
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                                       Table of Contents
1. Outline D-3
2. Specifications D-6
3. Wiring D-9
4. Programming D-13
6. Troubleshooting D-21
8
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                                     Table of Contents
1. Outline E-3
2. Specifications E-6
3. Wiring E-9
                                                                                                                                                                 9
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                                           Table of Contents
9. Troubleshooting E-64
10
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                                        Table of Contents
1. Outline F-3
2. Specifications F-6
3. Wiring F-10
4. Programming F-15
6. Troubleshooting F-26
                                                                                                                                                                    11
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                                       Table of Contents
1. Outline G-3
2. Specifications G-6
3. Wiring G-9
4. Programming G-13
6. Troubleshooting G-19
12
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                                        Table of Contents
      FX3U-4AD-PT-ADP
      (4-channel Platinum Resistance Thermometer Data Input)
1. Outline H-3
2. Specifications H-6
3. Wiring H-10
4. Programming H-15
5. Troubleshooting H-26
                                                                                                                                                                    13
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                                          Table of Contents
      FX3U-4AD-PTW-ADP
      (4-channel Platinum Resistance Thermometer Data Input)
1. Outline I-3
2. Specifications I-6
3. Wiring I-10
4. Programming I-15
5. Troubleshooting I-26
14
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                                         Table of Contents
1. Outline J-3
2. Specifications J-6
3. Wiring J-10
4. Programming J-16
5. Troubleshooting J-29
                                                                                                                                                                     15
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                                        Table of Contents
1. Outline K-3
2. Specifications K-6
3. Wiring K-10
4. Programming K-16
5. Troubleshooting K-29
16
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                                            Table of Contents
1. Outline L-3
3. Parameter L-7
4. Auto-Tuning L-18
6. Troubleshooting L-28
Warranty...................................................................................................................................... i
                                                                                                                                                                         17
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition   Table of Contents
MEMO
18
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                     1 Introduction
Common Items                                                                       1.1 Outline and Features of Analog Control
                                                                                                                                      Common Items
1.     Introduction
         This manual describes the analog products for the FX3G/FX3U/FX3UC Series PLC.                                            B
         This chapter describes the analog control methods and applications.
                                                                                                                                FX3UC-4AD
                                                                                                                                FX3U-4AD
1.1      Outline and Features of Analog Control
         For the FX Series, there are 3 types of analog control: Voltage/Current input, Voltage/Current output, and
         Temperature Sensor input.
                                                                                                                                  C
                                                                                                                                      FX3U-4AD-ADP
         It is important to select products that are optimum for the purpose of use.
                                                                                                                                      FX3G-2AD-BD
                                                                                                                                   E
                                                                                                                                      FX3U-4DA
                       Voltage/current input      Voltage/current        Temperature sensor
                        control type                output control type     input control type
                      •FX3U-4AD                    •FX3U-4DA                •FX3U-4AD-PT-ADP
                      •FX3UC-4AD                   •FX3U-4DA-ADP            •FX3U-4AD-PTW-ADP
                      •FX3U-4AD-ADP
                      •FX3G-2AD-BD
                                                   •FX3G-1DA-BD            ••FX3U-4AD-PNK-ADP
                                                                            •FX3U-4AD-TC-ADP                                        F
                                                                                                                                      FX3U-4DA-ADP
                      → Refer to Subsection       → Refer to Subsection    → Refer to Subsection
                             1.1.1.                      1.1.2.                   1.1.3.
                                                                                                                                      FX3G-1DA-BD
                            Flowmeter,                Inverter, etc.         Thermocouple,
                       pressure sensor, etc.                                 platinum resistance
                                                                             thermometer
                                                                             sensor
                                                                                                                                  H
                                                                                                                                FX3U-4AD-PT
                                                                                                                                         -ADP
In addition to the above applications, the FX3U/FX3UC/FX3G Series PLC can be used for various purposes.
                                                                                                                                          I
                                                                                                                                FX3U-4AD-PTW
                                                                                                                                         -ADP
                                                                                                                                    J
                                                                                                                                FX3U-4AD-PNK
                                                                                                                                         -ADP
                                                                                                                      A-1
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                      1 Introduction
Common Items                                                                        1.1 Outline and Features of Analog Control
                 → To determine whether or not a unit can be connected to the PLC, refer to Chapter 3 "System
                                                                Configuration Drawings of Analog Products."
A-2
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                          1 Introduction
Common Items                                                                          1.1 Outline and Features of Analog Control
                                                                                                                                       A
1.1.2    Analog output control
                                                                                                                                           Common Items
         Output the voltage/current signal from the PLC to an inverter, etc. to control the inverter frequency, etc.
                                                                                                   Inverter, etc.
            FX3U/FX3UC/FX3G Series PLC
                                                                                                                                     FX3UC-4AD
                                                                                                                                     FX3U-4AD
                                             data              special function   current
                                                                block, special
                                                                   adapter,
                                                               expansion board
                                                                                                                                           FX3U-4AD-ADP
                                                                                       the input voltage/current.
                → To determine whether or not a unit can be connected to the PLC, refer to Chapter 3 "System
                                                               Configuration Drawings of Analog Products."
                                                                                                                                           FX3G-2AD-BD
                                                                         → For detailed description, refer to Section E.
         • FX3U-4DA-ADP
                                                                         → For detailed description, refer to Section F.
                                                                                                                                           FX3U-4DA
                                                                         → For detailed description, refer to Section G.
                                                                                                                                           FX3U-4DA-ADP
                                                                      products, refer to the corresponding manuals.
FX3G-1DA-BD
                                                                                                                                       H
                                                                                                                                     FX3U-4AD-PT
                                                                                                                                              -ADP
                                                                                                                                               I
                                                                                                                                     FX3U-4AD-PTW
                                                                                                                                              -ADP
                                                                                                                                         J
                                                                                                                                     FX3U-4AD-PNK
                                                                                                                                              -ADP
                                                                                                                           A-3
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                         1 Introduction
Common Items                                                                           1.1 Outline and Features of Analog Control
           Measure the
           temperature of the                                                           Check the temperature
           equipment.                                                                   using the PLC.
                 → To determine whether or not a unit can be connected to the PLC, refer to Chapter 3 "System
                                                                Configuration Drawings of Analog Products."
A-4
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                            2 Description of Analog Products
Common Items                                                                              2.1 Types of Analog Products
                                                                                                                               Common Items
2.       Description of Analog Products
                                                                                                                           B
2.1       Types of Analog Products
                                                                                                                         FX3UC-4AD
                                                                                                                         FX3U-4AD
          Analog input/output products are required to perform analog control using the FX Series PLC.
          There are 2 types of input/output products: the expansion board, special adapter and the special function
          block.
          Subsequent subsections explain differences among analog products.                                                C
                                                                                                                               FX3U-4AD-ADP
2.1.1     Expansion board
          The analog expansion board uses PLC devices to send/receive data to/from the PLC.
                                                                                                                               FX3G-2AD-BD
          • Up to 2*1 analog expansion boards can be connected.
PLC
                     Analog
                 expansion board                                                                                            E
                                                                                                                               FX3U-4DA
                                                                                                                             F
           → For a detailed description of the system configuration, refer to the PLC User’s Manual - Hardware
                                                                                                                               FX3U-4DA-ADP
                                                                                                       Edition.
           *1.   Only 1 analog special adapter can be connected to the 14-point and 24-point type main unit.
                 When two analog expansion boards are connected to the 40-point or 60-point type main unit, analog
                 special adapters are not available in the main unit.
                                                                                                                          G
FX3G-1DA-BD
                                                                                                                           H
                                                                                                                         FX3U-4AD-PT
                                                                                                                                  -ADP
                                                                                                                                   I
                                                                                                                         FX3U-4AD-PTW
                                                                                                                                  -ADP
                                                                                                                             J
                                                                                                                         FX3U-4AD-PNK
                                                                                                                                  -ADP
                                                                                                               A-5
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                       2 Description of Analog Products
Common Items                                                                                                                         2.1 Types of Analog Products
                                                                                                          RDA
                                                                                                     RD
                                                                                                          RDB
SDA
SD SDB
SG
FX3U-***-BD
              → For a detailed description of the system configuration, refer to the PLC User’s Manual - Hardware
                                                                                                          Edition.
A-6
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                                     2 Description of Analog Products
Common Items                                                                                                                                        2.1 Types of Analog Products
                                                                                                                                                                                     A
      3. FX3UC-32MT-LT(-2) PLC
                                                                                                                                                                                         Common Items
         • Connect the special adapter(s) to the left side of the FX3UC-32MT-LT(-2) PLC.
         • An expansion board is needed to connect the special adapter(s).
         • Up to 4 analog special adapters can be connected.
                Analog special adapters                                                  Expansion board                      PLC
                                                                                                                                                                                     B
                                                                                                                                                                                   FX3UC-4AD
                                                                                                                                                                                   FX3U-4AD
                    FX3U-4AD-ADP FX 3U -4AD-ADP FX3U -4AD-ADP FX3U -4AD-ADP
                          POWER         POWER         POWER         POWER
                                                                                                    RDA
                                                                                               RD
                                                                                                    RDB
SDA
SD SDB
SG
                                                                                           FX3U-***-BD
                                                                                                                                                                                     C
                                                                                                                                                                                         FX3U-4AD-ADP
                Up to 4 Analog adapters can be connected.                                                 "***" represents "422", "232", "485", "CNV", or "USB."
→ For a detailed description of the system configuration, refer to the PLC User’s Manual - Hardware Edition.
                                                                                                                                                                                     D
      4. FX3G Series PLC
                                                                                                                                                                                         FX3G-2AD-BD
         • Connect the special adapter(s) to the left side of the FX3G Series PLC.
         • A connector conversion board is needed to connect the special adapter(s).
         • Up to 2*1 analog special adapters can be connected.
                    Analog
                special adapters
                                                                            Connector conversion adapter                     PLC                                                      E
                                                                                                                                                                                         FX3U-4DA
                                                                                                                                                                                       F
                                                                                                                                                                                         FX3U-4DA-ADP
                                                                                  FX3G-CNV-ADP
                                                                                                                                                                                         FX3G-1DA-BD
                  When two analog expansion boards are connected to the 40-point or 60-point type main unit, analog
                  special adapters are not available in the main unit.
                                                                                                                                                                                     H
                                                                                                                                                                                   FX3U-4AD-PT
                                                                                                                                                                                            -ADP
                                                                                                                                                                                             I
                                                                                                                                                                                   FX3U-4AD-PTW
                                                                                                                                                                                            -ADP
                                                                                                                                                                                       J
                                                                                                                                                                                   FX3U-4AD-PNK
                                                                                                                                                                                            -ADP
                                                                                                                                                                         A-7
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                         2 Description of Analog Products
Common Items                                                                                            2.1 Types of Analog Products
Up to 8*1 special function units/blocks can be connected (excluding the special adapters).
→ For a detailed description of the system configuration, refer to the PLC User's Manual - Hardware Edition.
A-8
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                     2 Description of Analog Products
Common Items                                                                                    2.2 List of Analog Product Models
                                                                                                                                      A
2.2      List of Analog Product Models
                                                                                                                                          Common Items
         The analog input/output products compatible with the FX3U/FX3UC/FX3G Series PLC are described below:
                                                                                                                                    FX3UC-4AD
                                                                                                                                    FX3U-4AD
                                    No. of                                                                                Refer-
                  Type                                 Range              Resolution               Function
                                   channels                                                                               ence
          Voltage/current input
          FX3G-2AD-BD                2ch
                                              Voltage: 0V to 10V DC      2.5mV(12bits) Combined use of voltage and
                                                                                                                            D
                                                                                                                                      C
                                                                                       current inputs is possible.
                                                                                                                                          FX3U-4AD-ADP
                                              Current: 4mA to 20mA DC    8µA(11bits)
          Voltage/current output
                                              Voltage: 0V to 10V DC      2.5mV(12bits)
          FX3G-1DA-BD                1ch                                                 Voltage and current output.        G
                                              Current: 4mA to 20mA DC    8µA(11bits)
                                                                                                                                      D
2.2.2    Special adapter
                                                                                                                                          FX3G-2AD-BD
                                    No. of                                                                                Refer-
                  Type                                 Range              Resolution               Function
                                   channels                                                                               ence
          Voltage/current input
          FX3U-4AD-ADP               4ch
                                              Voltage: 0V to 10V DC      2.5mV(12bits) Combined use of voltage and
                                                                                                                            C
                                                                                                                                       E
                                              Current: 4mA to 20mA DC    10µA(11bits) current inputs is possible.
                                                                                                                                          FX3U-4DA
          Voltage/current output
                                              Voltage: 0V to 10V DC      2.5mV(12bits) Combined use of voltage and
          FX3U-4DA-ADP               4ch                                                                                    F
                                              Current: 4mA to 20mA DC    4µA(12bits)   current outputs is possible.
          Temperature sensor input                                                                                                      F
                                                                                         Compatible with the platinum
                                                                                                                                          FX3U-4DA-ADP
                                                                                         resistance thermometer
                                                                                         sensor (Pt100).
          FX3U-4AD-PT-ADP            4ch      Pt100: -50°C to +250°C     0.1°C                                              H
                                                                                         The product can be switched
                                                                                         between "Centigrade" and
                                                                                         "Fahrenheit."
                                                                                        Compatible with the platinum
                                                                                                                                     G
                                                                                                                                          FX3G-1DA-BD
                                                                                        resistance thermometer
                                                                                        sensor (Pt100).
          FX3U-4AD-PTW-ADP           4ch      Pt100: -100°C to +600°C    0.2°C to 0.3°C                                      I
                                                                                        The product can be switched
                                                                                        between "Centigrade" and
                                                                                        "Fahrenheit."
                                                                                         Compatible with
                                              Type K: -100°C to +1000°C 0.4°C
          FX3U-4AD-TC-ADP            4ch
                                                                                         thermocouple types K and J.
                                                                                         The product can be switched        K
                                                                                                                                              I
                                                                                                                                    FX3U-4AD-PTW
                                                                                                                                        J
                                                                                                                                    FX3U-4AD-PNK
                                                                                                                                             -ADP
                                                                                                                          A-9
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                   2 Description of Analog Products
Common Items                                                                                 2.2 List of Analog Product Models
                            No. of                                                                                     Refer-
               Type                          Range               Resolution                    Function
                           channels                                                                                    ence
          Voltage/current input
                                      Voltage:              0.32mV                 Combined use of voltage and
                                      -10V to +10V DC       (with sign, 16 bits)   current inputs is possible. The
          FX3U-4AD*1          4ch                                                  offset/gain can be adjusted.*3        B
                                      Current:              1.25µA
                                                                                   The sampling function is
                                      -20mA to +20mA DC     (with sign, 15 bits)
                                                                                   incorporated.
                                      Voltage:              0.32mV                 Combined use of voltage and
                                      -10V to +10V DC       (with sign, 16 bits)   current inputs is possible. The
          FX3UC-4AD*2         4ch                                                  offset/gain can be adjusted.*3        B
                                      Current:              1.25µA
                                                                                   The sampling function is
                                      -20mA to +20mA DC     (with sign, 15 bits)
                                                                                   incorporated.
                                      Voltage:              0.32mV                 Combined use of voltage and
                                      -10V to +10V DC       (with sign, 16 bits)   current inputs is possible.
                                                                                   The offset/gain can be
          FX2NC-4AD*2         4ch                                                                                        *5
                                      Current:              1.25µA                 adjusted.*3
                                      -20mA to +20mA DC     (with sign, 15 bits)   The sampling function is
                                                                                   incorporated.
                                      Voltage:              0.63mV                 Combined use of voltage,
                                      -10V to +10V DC       (with sign, 15 bits)   current, and thermocouple is
                                                                                   possible. The offset/gain can be
          FX2N-8AD*1          8ch                                                                                        *5
                                      Current:              2.5µA                  adjusted.*3
                                      -20mA to +20mA DC     (with sign, 14 bits)   The sampling function is
                                                                                   incorporated.
                                      Voltage:              5mV
                                      -10V to +10V DC       (with sign, 12 bits)   Combined use of voltage and
          FX2N-4AD*1          4ch                                                  current inputs is possible.           *5
                                      Current:              10µA                   The offset/gain can be adjusted.
                                      -20mA to +20mA DC     (with sign, 11 bits)
                                      Voltage:              2.5mV                  Combined use of voltage and
                                      0V to 10V DC          (12bits)               current inputs is impossible.
          FX2N-2AD*1          2ch                                                                                        *5
                                      Current:              4µA                    The offset/gain can be adjusted.
                                      4mA to 20mA DC        (12bits)               (Common to 2 input channels)
          Voltage/current output
                                      Voltage:              0.32mV
                                                                                   Combined use of voltage and
                                      -10V to +10V DC       (with sign, 16 bits)
          FX3U-4DA*1          4ch                                                  current outputs is possible.*4        E
                                      Current:              0.63µA
                                                                                   The offset/gain can be adjusted.
                                      0mA to 20mA DC         (15bits)
                                      Voltage:              5mV
                                      -10V to +10V DC       (with sign, 12 bits)   Combined use of voltage and
          FX2NC-4DA*2         4ch                                                  current outputs is possible.          *5
                                      Current:              20µA                   The offset/gain can be adjusted.
                                      0mA to 20mA DC         (10bits)
                                      Voltage:              5 mV
                                      -10V to +10V DC       (with sign, 12 bits)   Combined use of voltage and
          FX2N-4DA*1          4ch                                                  current outputs is possible.          *5
                                      Current:              20µA                   The offset/gain can be adjusted.
                                      0mA to 20mA DC        (10bits)
                                      Voltage:              2.5 mV
                                      0V to 10V DC          (12 bits)              Combined use of voltage and
          FX2N-2DA*1          2ch                                                  current outputs is possible.          *5
                                      Current:              4µA                    The offset/gain can be adjusted.
                                      4mA to 20mA DC        (12bits)
          *1. To connect this block to the FX3UC Series PLC, either the FX2NC-CNV-IF or FX3UC-1PS-5V is required.
          *2. Connectable with the FX3UC Series PLC only.
          *3. The offset and gain of the FX3U-4AD, FX3UC-4AD, FX2NC-4AD and FX2N-8AD cannot be adjusted for
              channels using the analog value direct indication mode.
          *4. The offset and gain of the FX3U-4DA cannot be adjusted for channels using the analog value mV (or µA)
              specification mode.
          *5. Refer to the instruction manual of the respective product.
A-10
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                   2 Description of Analog Products
Common Items                                                                                  2.2 List of Analog Product Models
                                                                                                                                    A
                            No. of                                                                                      Refer-
                                                                                                                                        Common Items
               Type                              Range           Resolution                    Function
                           channels                                                                                     ence
          Voltage/current input/output mixture
                                      Voltage:              0.32mV
                           Input      -10V to +10V DC       (with sign, 16 bits)   Combined use of voltage and
                           4ch        Current:              1.25µA                 current is possible.                             B
                                      -20mA to +20mA DC     (with sign, 15 bits)   The offset/gain can be
                                                                                                                                  FX3UC-4AD
                                                                                                                                  FX3U-4AD
          FX2N-5A*1                                                                                                       *2
                                      Voltage:              5mV                    adjusted.*3
                           Output     -10V to +10V DC       (with sign, 12 bits)   The scaling function is
                           1ch        Current:              20µA                   incorporated.
                                      0mA to 20mA DC        (10bits)
                           Input
                                      Voltage:
                                      0V to 10V DC
                                                            40mV
                                                            (8bits)
                                                                                                                                    C
                                                                                                                                        FX3U-4AD-ADP
                           2ch        Current:              64µA                   The input format is common to 2
                                      4mA to 20mA DC        (8bits)                channels.
          FX0N-3A*1, *4                                                                                                   *2
                                      Voltage:              40mV                   The offset/gain can be adjusted.
                           Output     0V to 10V DC          (8bits)                (Common to 2 input channels)
                           1ch        Current:
                                      4mA to 20mA DC
                                                            64µA
                                                            (8bits)                                                                 D
                                                                                                                                        FX3G-2AD-BD
          Temperature sensor input
                                      Type K:                                      Combined use of voltage,
                                                            0.1°C
                                      -100°C to +1200°C                            current, and thermocouple is
                                      Type J:                                      possible.
                                                            0.1°C                  Compatible with thermocouple
                                      -100°C to +600°C
          FX2N-8AD*1       8ch                                                     types K, J, and T.                     *2         E
                                                                                   The unit can be switched between
                                                                                                                                        FX3U-4DA
                                      Type T:                                      "Centigrade" and "Fahrenheit."
                                                            0.1°C
                                      -100°C to +350°C                             The sampling function is
                                                                                   incorporated.
                                      Type K:                                      Compatible with thermocouple
                                                            0.4°C
                                      -100°C to +1200°C                            types K and J.
          FX2N-4AD-TC*1 4ch
                                      Type J:                                      The unit can be switched between
                                                                                                                          *2          F
                                                            0.3°C                  "Centigrade" and "Fahrenheit."
                                                                                                                                        FX3U-4DA-ADP
                                      -100°C to +600°C
                                                                                   Compatible with the platinum
                                                                                   resistance thermometer sensor
                                      Pt100:
          FX2N-4AD-PT*1 4ch                                 0.2°C to 0.3°C         (Pt100 or JPt100).                     *2
                                      -100°C to +600°C
                                                                                   The unit can be switched between
                                                                                   "Centigrade" and "Fahrenheit."                  G
                                      Example:                                   Compatible with thermocouple
                                                                                                                                        FX3G-1DA-BD
                                      Type K:                                    types K, J, R, S, E, T, B, N, PL II,
                                      -100°C to +1300°C                          WRe5-26, U, and L.
                                                                                 Compatible with the platinum
                                                                                 resistance thermometer sensor
                                                                                 (Pt100, JPt100).
                                                            0.1°C or 1°C         The unit can be switched between                   H
          FX2N-2LC*1       2ch                              (Depends on the      "Centigrade" and "Fahrenheit."           *2
                                                                                                                                  FX3U-4AD-PT
          *1. To connect this block to the FX3UC Series PLC, either the FX2NC-CNV-IF or FX3UC-1PS-5V is required.
          *2. Refer to the instruction manual of the respective product.
                                                                                                                                           -ADP
          *3. The offset and gain of the FX2N-5A cannot be adjusted for channels using the analog value direct
              indication mode or analog value mV (or µA) specification mode.                                                          J
          *4. The FX0N-3A cannot be connected to the FX3G Series PLC.
                                                                                                                                  FX3U-4AD-PNK
                                                                                                                                           -ADP
                                                                                                                        A-11
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                   3 System Configuration Drawings of Analog Products
Common Items                                                                                                                                                    3.1 FX3U Series PLC
FX3U Series
                                                                                                                                                          • Flowmeter
                                                                          RD
                                                                               RDB
                                                                          SD
                                                                               SDA
                                                                               SDB
                                                                                                                                European terminal block
                                                                                                                                                          • Pressure sensor
                                                                               SG
                                                                                            A
       Up to 4 analog special adapters can be connected.
                                                                                                                                                          Analog output
                                                                                                                                European terminal block
                                                                                                                                                          • Inverter, etc.
FX3U-4DA-ADP
                                                                                            A
                                                                                                                                                          Temperature sensor
                                                                                                                                                          input
                                                                                                                                European terminal block
                                                                                                                                                          • Thermocouple
                                                                                                                                                           (types K and J)
                                                                                           FX3U-4AD-TC-ADP
                                                                                            A
                                                                                                                                                           Temperature sensor
                                                                                                                                                            input
                                                                                                                                European terminal block   • Resistance
                                                                                                                                                            thermometer
                                                                                                                                                            sensor (Pt1000 and
                                                                                           FX3U-4AD-PNK-ADP                                                 Ni1000)
                                                                                            A
                                                                                                                                                           Temperature sensor
                                                                                                                                                            input
                                                                                                                                European terminal block   • Platinum resistance
                                                                                                                                                            thermometer
                                                                                           FX3U-4AD-PT-ADP                                                  sensor (Pt100)
                                                                                           FX3U-4AD-PTW-ADP
A-12
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                     3 System Configuration Drawings of Analog Products
Common Items                                                                                                                                                     3.1 FX3U Series PLC
                                                                                                                                                                                          A
3.1.2                                                       Connection of special function blocks
                                                                                                                                                                                              Common Items
                                                              FX3U Series                              A , B , and C represent the connecting positions.
                                                                                                        For a detailed description of installation, refer to the following manual
                                                                                                        supplied with your PLC.
                                                               A
                                                                   B                    C                     → Refer to the FX3U Series User's Manual - Hardware Edition.                B
                                                                                                                                                                                        FX3UC-4AD
                                                                                                                                                                                        FX3U-4AD
                                                                                                     To connect the special adapters A or the expansion boards B ,
                                                                                                     refer to the previous page.
                                                                                                                                                                                          C
        Up to 8 special function blocks can be connected.
                                                                                                                                                                                              FX3U-4AD-ADP
                                                                                                                                                              Analog input
                                                                                                 C                                                            • Flowmeter
                                                                                                                                                              • Pressure sensor
                                                                                                                                                              • Signal converter,
                                                                                                                                                                etc.
                                                                                                                                     Terminal block
                                                                                                                                                                                          D
                                                                                                                                                              Analog output
                                                                                                                                                                                              FX3G-2AD-BD
                                                                                                 Special function                                             • Inverter, etc.
                                                                                                 block for FX3U,
                                                                                                 FX2N and FX0N
                                                                                                                                                              Temperature sensor
                                                                                                                                                              input
                                                                                                                                                              • Thermocouple
                                                                                                                                                              • Platinum resistance        E
                                                                                                                                                                thermometer
                                                                                                                                                                                              FX3U-4DA
                                                                                                                                                                sensor (Pt100)
                                                            • For a detailed description of the connectable special function blocks and system configuration:
                                                                                                       → Refer to the FX3U Series User's Manual - Hardware Edition.                         F
                                                                                                                                                                                              FX3U-4DA-ADP
                                                            The analog special function blocks shown in the table below can be connected to the FX3U Series PLC:
                                                                         FX Series                                                       Type
                                                            Analog special function blocks for
                                                                                                 FX3U-4AD, FX3U-4DA
                                                            the FX3U
                                                                                                                                                                                         G
                                                            Analog special function blocks for   FX2N-8AD, FX2N-4AD, FX2N-2AD, FX2N-4DA, FX2N-2DA, FX2N-5A,
                                                                                                                                                                                              FX3G-1DA-BD
                                                            the FX2N                             FX2N-4AD-PT, FX2N-4AD-TC, FX2N-2LC
                                                            Analog special function blocks for
                                                                                                 FX0N-3A
                                                            the FX0N
                                                                                                                                                                                          H
                                                                                                                                                                                        FX3U-4AD-PT
                                                                                                                                                                                                 -ADP
                                                                                                                                                                                                  I
                                                                                                                                                                                        FX3U-4AD-PTW
                                                                                                                                                                                                 -ADP
                                                                                                                                                                                            J
                                                                                                                                                                                        FX3U-4AD-PNK
                                                                                                                                                                                                 -ADP
                                                                                                                                                                                 A-13
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                             3 System Configuration Drawings of Analog Products
Common Items                                                                                                                                             3.2 FX3UC Series PLC
                                                                                                                                                    Analog output
       Up to 4 analog special adapters can be connected.
FX3U-4DA-ADP
                                                                                      A
                                                                                                                                                    Temperature sensor
                                                                                                                                                    input
                                                                                                                          European terminal block
                                                                                                                                                    •Thermocouple
                                                                                                                                                      (types K and J)
                                                                                     FX3U-4AD-TC-ADP
                                                                                      A
                                                                                                                                                    Temperature sensor
                                                                                                                                                    input
                                                                                                                          European terminal block   •Resistance
                                                                                                                                                      thermometer
                                                                                                                                                      sensor (Pt1000
                                                                                                                                                      and Ni1000)
                                                                                     FX3U-4AD-PNK-ADP
                                                                                      A
                                                                                                                                                    Temperature sensor
                                                                                                                                                    input
                                                                                                                          European terminal block   •Platinum resistance
                                                                                                                                                      thermometer
                                                                                                                                                      sensor (Pt100)
                                                                                     FX3U-4AD-PT-ADP
                                                                                     FX3U-4AD-PTW-ADP
A-14
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                               3 System Configuration Drawings of Analog Products
Common Items                                                                                                                                                               3.2 FX3UC Series PLC
                                                                                                                                                                                                    A
                                2. FX3UC-32MT-LT(-2) PLC
                                                                                                                                                                                                        Common Items
                                                                                                  To connect the special function blocks C or the conversion adapters D ,
                                                         A               C1        D         C2
                                                                                                  refer to Subsection 3.2.2-2.
                                                               B
                                                                                                                                                                                                  FX3UC-4AD
                                                                                                                                                                                                  FX3U-4AD
                                                                                                   For a detailed description of installation, refer to the following manual supplied with to
                                                                                                   your PLC.
                                                                                                                        → Refer to the FX3UC Series User's Manual - Hardware Edition.
                                                                     B                                  A
                                                                                                                                                                      Analog input
                                                                                                                                                                                                    C
                                                                                       RDA
                                                                              RD
                                                                                       RDB
SD SDB
SG
•Pressure sensor
                                                                                                                                                                                                        FX3U-4AD-ADP
                                                                     FX3U-***-BD*1                     FX3U-4AD-ADP                                                   •Signal converter, etc.
                                                                                                                                                                      Analog output                 D
     Up to 4 analog special adapters can be connected.
                                                                                                                                                                                                        FX3G-2AD-BD
                                                                                                       FX3U-4DA-ADP
                                                                                                        A
                                                                                                                                                                      Temperature sensor
                                                                                                                                                                      input
                                                                                                                                                                                                     E
                                                                                                                                                                                                        FX3U-4DA
                                                                                                                                            European terminal block
                                                                                                                                                                      •Thermocouple
                                                                                                                                                                        (types K and J)
                                                                                                       FX3U-4AD-TC-ADP
                                                                                                        A
                                                                                                                                                                      Temperature sensor              F
                                                                                                                                                                      input
                                                                                                                                                                                                        FX3U-4DA-ADP
                                                                                                                                            European terminal block   •Resistance
                                                                                                                                                                        thermometer
                                                                                                                                                                        sensor (Pt1000
                                                                                                                                                                        and Ni1000)
                                                                                                       FX3U-4AD-PNK-ADP
                                                                                                        A
                                                                                                                                                                                                   G
                                                                                                                                                                                                        FX3G-1DA-BD
                                                                                                                                                                      Temperature sensor
                                                                                                                                                                      input
                                                                                                                                            European terminal block   •Platinum resistance
                                                                                                                                                                        thermometer
                                                                                                                                                                        sensor (Pt100)
                                                                                                       FX3U-4AD-PT-ADP
                                                                                                       FX3U-4AD-PTW-ADP                                                                             H
                                                                                                                                                                                                  FX3U-4AD-PT
                                                                                                                                                                                                            I
                                                                                                                                                                                                  FX3U-4AD-PTW
                                                                                                                                                                                                           -ADP
                                                                                                                                                                                                      J
                                                                                                                                                                                                  FX3U-4AD-PNK
                                                                                                                                                                                                           -ADP
                                                                                                                                                                                          A-15
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                   3 System Configuration Drawings of Analog Products
Common Items                                                                                                                                                   3.2 FX3UC Series PLC
C1
FX3UC-4AD
                                                                      C1
         Up to 8 special function blocks can be connected.
                                                                                       C1    or   C2    Special function
                                                                                                        block for FX2NC
                                                                      FX3UC-1PS-5V
                                                                                                       C2
Terminal block
                                                                                                        Special function
                                                                                                        block for FX3U,
                                                                      FX2NC-CNV-IF                      FX2N and FX0N
                                  • For a detailed description of special function block connectability and system configuration:
                                                                             → Refer to the FX3UC Series User's Manual - Hardware Edition.
                                  • Use the FX3UC-1PS-5V (extension power supply unit) if the capacity of the 5V DC power supply unit
                                    incorporated in the FX3UC Series PLC is deteriorated.
                                                                             → Refer to the FX3UC Series User's Manual - Hardware Edition.
                                  The analog special function blocks shown in the table below can be connected to the FX3UC Series PLC:
                                                                          FX Series                                                           Type
                                                Analog special function blocks for the FX3U                  FX3U-4AD, FX3U-4DA
                                                Analog special function blocks for the FX2NC                 FX2NC-4AD, FX2NC-4DA
                                                                                                             FX2N-8AD, FX2N-4AD, FX2N-2AD, FX2N-4DA, FX2N-2DA,
                                                Analog special function blocks for the FX2N
                                                                                                             FX2N-5A, FX2N-4AD-PT, FX2N-4AD-TC, FX2N-2LC
                                                Analog special function blocks for the FX0N                  FX0N-3A
A-16
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                      3 System Configuration Drawings of Analog Products
Common Items                                                                                                                                                      3.2 FX3UC Series PLC
                                                                                                                                                                                              A
      2. FX3UC-32MT-LT(-2) PLC
                                                                                                                                                                                                  Common Items
                                                                                                A , B , C , and D represent the connecting positions.
                                                                                                 For a detailed description of installation, refer to the following manual supplied with
                                                            A       C1   D    C2                 your PLC.
                                                                B
                                                                                                        → Refer to the FX3UC Series User's Manual - Hardware Edition.
                                                                                    To connect the special adapters A or the expansion boards B ,                                             B
                                                                                    refer to Subsection 3.2.1-2.
                                                                                                                                                                                            FX3UC-4AD
                                                                                                                                                                                            FX3U-4AD
                                                                         C1
                                                                                                                                                                                                  FX3U-4AD-ADP
                                                                              FX3UC-4AD
                                                                         C1
        Up to 7 special function blocks can be connected.
                                                                                                                                                                                                  FX3G-2AD-BD
                                                                             Special function                                                                     •Flowmeter
                                                                             block for FX2NC              C1                                                      •Pressure sensor
                                                                                                                                                                  •Signal converter, etc.
                                                                                                                                      European terminal block
                                                                                                                                                                  Analog output                E
                                                                                                                                                                  •Inverter, etc.
                                                                                                                                                                                                  FX3U-4DA
                                                                                                               FX3UC-4AD
                                                                                                                                                                  Temperature sensor
                                                                                                          C1                                                      input
                                                                                                                                                                  •Thermocouple
                                                                                                                                                                  •Platinum resistance
                                                                         D
                                                                                                                                      European terminal block
                                                                                                                                                                   thermometer
                                                                                                                                                                   sensor (Pt100)
                                                                                                                                                                                                F
                                                                                                                                                                                                  FX3U-4DA-ADP
                                                                                          C1    or   C2    Special function
                                                                                                           block for FX2NC
                                                                         FX3UC-1PS-5V
                                                                                                          C2
                                                                                                                                                                                             G
                                                                         D
                                                                                                                                                                                                  FX3G-1DA-BD
                                                                                                                                          Terminal block
                                                                                                           Special function
                                                                                                           block for FX3U,
                                                                         FX2NC-CNV-IF                      FX2N and FX0N
                                                                                                                                                                                              H
                                                                                                                                                                                            FX3U-4AD-PT
                                 • For a detailed description of special function block connectability and system configuration:
                                                                            → Refer to the FX3UC Series User's Manual - Hardware Edition.
                                 • Use the FX3UC-1PS-5V (extension power supply unit) if the capacity of the 5V DC power supply unit
                                                                                                                                                                                                     -ADP
                                                                             FX Series                                                           Type
                                               Analog special function blocks for the FX3U                      FX3U-4AD, FX3U-4DA
                                               Analog special function blocks for the FX2NC                     FX2NC-4AD, FX2NC-4DA
                                                                                                                                                                                                     -ADP
                                                                                                                                                                                    A-17
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                                         3 System Configuration Drawings of Analog Products
Common Items                                                                                                                                                                         3.3 FX3G Series PLC
                                                                                   FX3G Series
                                                                                                                 and     represent the connecting positions.
                                                                                                              For a detailed description of installation, refer to the following manual
                                                                                                              supplied with your PLC.
                                                                                                                 Refer to the FX3G Series User's Manual - Hardware Edition.
                                                                                                      1st
                                                                                                      board                                                                   Analog input
                                                                                                                                                                               Flowmeter
                                                                                                                                                 European terminal block
       Up to 1 analog expansion board, analog special adapters can be connected.
                                                                                                                                                                               Pressure sensor
                                                                                                                                                                               Signal converter, etc.
                                                                                             FX3G-2AD-BD
                                                                                                      1st
                                                                                                      board
FX3G-1DA-BD
                                                                                                                               1st
                                                                                                                               adapter                                        Analog input
                                                                                                                                                                               Flowmeter
                                                                                                                                                 European terminal block
                                                                                                                                                                               Pressure sensor
                                                                                                                                                                               Signal converter, etc.
                                                                                             FX3G-CNV-ADP           FX3U-4AD-ADP
                                                                                                                               1st
                                                                                                                               adapter
                                                                                                                                                                              Analog output
                                                                                                                                                 European terminal block
                                                                                                                                                                               Inverter, etc.
FX3U-4DA-ADP
A-18
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                                           3 System Configuration Drawings of Analog Products
Common Items                                                                                                                                                                           3.3 FX3G Series PLC
                                                                                                                                                                                                               A
                                                                               2. FX3G Series PLC (40-point, 60-point type)
                                                                                                                                                                                                                   Common Items
                                                                                                          A , B , and C represent the connecting positions.
                                                                                                         For a detailed description of installation, refer to the following manual supplied with to
                                                                               A
                                                                               A       B   C
                                                                                                         your PLC.
                                                                                                                             Refer to the FX3G Series User's Manual - Hardware Edition.
                                                                                                                                                                                                               B
                                                                                                                                                                                                             FX3UC-4AD
                                                                                                                                                                                                             FX3U-4AD
                                                                                                                             Only either A or C
                                                                                                                             can be used as 2nd.
                                                                                                                                                                          European
                                                                                   B           1st                                                                         terminal     Analog input
                                                                                               board
                                                                                                                                                     C           2nd
                                                                                                                                                                 board
                                                                                                                                                                             block       Flowmeter
                                                                                                                                                                                         Pressure sensor
                                                                                                                                                                                                               C
                                                                                                                                                                          European
                                                                                                                                                                                                                   FX3U-4AD-ADP
                                                                                                                                                                                         Signal converter,
                                                                                                                                                                           terminal
                                                                                                                                                                             block       etc.
                                                                                    FX3G-2AD-BD
                                                                                                                                                      FX3G-2AD-BD
                                                                                   B                                                                                      European
                                                                                               1st
                                                                                                                                                                                                               D
  Up to 2 analog expansion boards, analog special adapters can be connected.
                                                                                                                                                                           terminal
                                                                                               board                                                                         block
                                                                                                                                                     C           2nd                    Analog output
                                                                                                                                                                                                                   FX3G-2AD-BD
                                                                                                                                                                 board                   Inverter, etc.
                                                                                                                                                                          European
                                                                                                                                                                           terminal
                                                                                    FX3G-1DA-BD                                                                              block
                                                                                                                                                     FX3G-1DA-BD
                                                                                                                                                                                                                E
                                                                                                                                                                                                                   FX3U-4DA
                                                                                                                                 Any one can be
                                                                                                                                 selected.
                                                                                                                                 A        2nd
                                                                                                                                          adapter
                                                                                                        A       1st                                                       European
                                                                                   B
                                                                                                                adapter                                                    terminal     Analog input             F
                                                                                                                                                                             block       Flowmeter
                                                                                                                                                                                                                   FX3U-4DA-ADP
                                                                                                                                                                                         Pressure sensor
                                                                                                                                 FX3U-4AD-ADP                             European       Signal converter,
                                                                                                                                                                           terminal
                                                                                                        FX3U-4AD-ADP                                                                     etc.
                                                                                                                                                                             block
                                                                                                                                 A        2nd
                                                                                    FX3G-CNV-ADP
                                                                                                        A       1st
                                                                                                                                          adapter
                                                                                                                                                                          European                            G
                                                                                                                adapter
                                                                                                                                                                                                                   FX3G-1DA-BD
                                                                                                                                                                           terminal
                                                                                                                                                                             block       Analog output
                                                                                                                                 FX3U-4DA-ADP                             European        Inverter, etc.
                                                                                                                                                                           terminal
                                                                                                       FX3U-4DA-ADP
                                                                                                                                A                                            block
                                                                                                                                          2nd
                                                                                                                                          adapter
                                                                                                                                                                                         Temperature           H
                                                                                                        A       1st
                                                                                                                                                                                                             FX3U-4AD-PT
                                                                                                                               FX3U-4AD-PNK-ADP                                           Resistance
                                                                                                        FX3U-4AD-TC-ADP
                                                                                                                                FX3U-4AD-PT-ADP                                           thermometer
                                                                                                                                                                                                                       I
                                                                                                                               FX3U-4AD-PTW-ADP                           European
                                                                                                       FX3U-4AD-PNK-ADP                                                                   sensor (Pt1000
                                                                                                        FX3U-4AD-PT-ADP                                                    terminal
                                                                                                                                                                                          and Ni1000)
                                                                                                       FX3U-4AD-PTW-ADP                                                      block
                                                                                                                                                                                                             FX3U-4AD-PTW
                                                                                                                                                                                          Platinum
                                                                                                                                                                                          resistance
                                                                                                                                                                                          thermometer
                                                                                                                                                                                                                      -ADP
sensor (Pt100)
                                                                                                                                                                                                                 J
                                                                                                                                                                                                             FX3U-4AD-PNK
                                                                                                                                                                                                                      -ADP
                                                                                                                                                                                                      A-19
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                         3 System Configuration Drawings of Analog Products
Common Items                                                                                                                                                          3.3 FX3G Series PLC
                                                                                                                                                              Analog input
                                                                                                 C                                                            • Flowmeter
                                                                                                                                                              • Pressure sensor
                                                                                                                                                              • Signal converter,
                                                                                                                                                                etc.
                                                                                                                                     Terminal block
                                                                                                                                                              Analog output
                                                                                                 Special function                                             • Inverter, etc.
                                                                                                 block for FX3U
                                                                                                 and FX2N
                                                                                                                                                              Temperature sensor
                                                                                                                                                              input
                                                                                                                                                              • Thermocouple
                                                        • For a detailed description of the connectable special function blocks and system configuration:
                                                                                                   → Refer to the FX3G Series User's Manual - Hardware Edition.
The analog special function blocks shown in the table below can be connected to the FX3G Series PLC:
                                                                         FX Series                                                           Type
                                                            Analog special function blocks for
                                                                                                     FX3U-4AD, FX3U-4DA
                                                            the FX3U
                                                            Analog special function blocks for       FX2N-8AD, FX2N-4AD, FX2N-2AD, FX2N-4DA, FX2N-2DA, FX2N-5A,
                                                            the FX2N                                 FX2N-4AD-PT, FX2N-4AD-TC, FX2N-2LC
A-20
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                     4 Comparison of Performance Specifications
Common Items                                                                                                                                                 4.1 Analog Input
                                                                                                                                                                                      Common Items
4.                    Comparison of Performance Specifications
                        The analog product performance specifications are shown in the following tables. Select the optimal product                                               B
                        for your equipment.
                                                                                                                                                                                FX3UC-4AD
                                                                                                                                                                                FX3U-4AD
4.1                     Analog Input
4.1.1 FX3U-4AD-ADP C
                                                                                                                                                                                      FX3U-4AD-ADP
                                                                                                    FX3U-4AD-ADP
                     Specifications
                                                                          Voltage input                                                    Current input
   Number of input points                                                                               4ch
                                                                                                                                                                                      FX3G-2AD-BD
   Absolute maximum input                                                  -0.5V,+15V                                                      -2mA,+30mA
   Offset
                                                                     Impossible to change                                               Impossible to change
   Gain
   Digital output                                                         12 bits, binary                                                  11 bits, binary
                                                                                                                                                                                   E
   Resolution                                                        2.5mV(10V×1/4000)                                                  10µA(16mA×1/1600)
                                                                                                                                                                                      FX3U-4DA
Overall accuracy
                   Ambient temperature
                                                 ±0.5%(±50mV) for 10V full scale                                   ±0.5%(±80µA) for 16mA full scale
                   :25±5°C
                   Ambient temperature
                   :0 to 55°C
                                                ±1.0%(±100mV) for 10V full scale                                   ±1.0%(±160µA) for 16mA full scale                                F
                                                                                                                                                                                      FX3U-4DA-ADP
   Time required for A/D                 • FX3U/FX3UC Series PLC : 200µs (Data updated every scan time.)
   conversion                            • FX3G Series PLC : 250µs (Data updated every scan time.)
                                                    4080                                                                 1640
                                                    4000                                                                 1600                                                    G
                                                                                                                                                                                      FX3G-1DA-BD
                                                    Digital output
Digital output
   Input characteristics
                                                                                                                                                             20.4mA
                                                                                            10.2V
                                                                      0              10V
                                                                          Analog input
                                                                                                                                         0 4mA
                                                                                                                                            Analog input
                                                                                                                                                        20mA                      H
                                                                                                                                                                                FX3U-4AD-PT
                                         • The photocoupler is used to insulate the analog input area from the PLC.
   Insulation method                     • The DC/DC converter is used to insulate the power supply from the analog inputs.
                                                                                                                                                                                         -ADP
                                                                                                                                                                                    J
                                                                                                                                                                                FX3U-4AD-PNK
                                                                                                                                                                                         -ADP
                                                                                                                                                                      A-21
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                 4 Comparison of Performance Specifications
Common Items                                                                                                                                                         4.1 Analog Input
4.1.2 FX2N-2AD
                                                                                                                FX2N-2AD
                     Specifications
                                                                             Voltage input                                                          Current input
   Number of input points                                                                                         2ch
                                                              0V to 5V DC
                                                                                                                                       4mA to 20mA DC
   Analog input range*1                                      0V to 10V DC
                                                                                                                                   (Input resistance: 250Ω)
                                                       (Input resistance: 200 kΩ)
   Absolute maximum input                                                     -0.5V,+15V                                                            -2mA,+60mA
                                                                                                        *2,*3
   Offset                                         If the digital value is "0":0V to 1V                                  If the digital value is "0":0mA to 4mA*2,*3
                                                      If the digital value is "4000":
   Gain                                                                                                                    If the digital value is "4000":20mA*2,*3
                                                                             5V to 10V*2,*3
   Digital output                                                                                           12 bits, binary
                                                                                              *3
   Resolution                                                    2.5mV(10V×1/4000)                                                4.00µA(16mA×1/4000)*3
Overall accuracy
                   Ambient temperature:
                                                                                   -                                                                       -
                   25±5°C
                   Ambient temperature:
                                                   ±1.0%(±100mV) for 10V full scale                                           ±1.0%(±160µA) for 16mA full scale
                   0 to 55°C
                                                         4095                                                                      4095
                                                        4000                                                                       4000
                                                        Digital output
Digital input
Input characteristics
                                                                                                                                                                     20.380mA
                                                                                              10.238V
                                           • The photocoupler is used to insulate the analog input area from the PLC.
   Insulation method
                                           • Channels are not insulated from each other.
   Number of I/O points
                                           8 points (Taken from either the input or output points of the PLC.)
   occupied
                          *1.   For FX2N-2AD, combined use of the voltage and current inputs is not possible.
                          *2.   Use the adjustment volume to adjust FX2N-2AD.
                          *3.   Adjustment of the offset or gain value will change the resolution.
A-22
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                    4 Comparison of Performance Specifications
Common Items                                                                                                                                        4.1 Analog Input
                                                                                                                                                                         A
4.1.3                    FX3U-4AD
                                                                                                                                                                             Common Items
                                                                                                  FX3U-4AD
                     Specifications
                                                                       Voltage input                                            Current input
   Number of input points                                                                           4ch
                                                                                                                            -20mA to +20mA DC
                                                                                                                                                                         B
                                                            -10V to +10V DC
                                                                                                                                                                       FX3UC-4AD
                                                                                                                                                                       FX3U-4AD
   Analog input range                                                                                                         4mA to 20mA DC
                                                        (Input resistance: 200 kΩ)
                                                                                                                          (Input resistance: 250 Ω)
   Absolute maximum input                                                 ±15V                                                     ±30mA
                                                                                 *1,*2
   Offset                                                          -10V to +9V                                             -20mA to +17mA*1,*3
   Gain                                                            -9V to +10V*1,*2                                        -17mA to +30mA*1,*3                           C
                                                                                                                                                                             FX3U-4AD-ADP
   Digital output                                         With sign, 16 bits, binary                                      With sign, 15 bits, binary
                                                                0.32mV(20V×1/64000)                                       1.25µA(40mA×1/32000)
   Resolution*4                                                  2.5mV(20V×1/8000)                                         5.00µA(40mA×1/8000)
Overall accuracy
                                                                                                                                                                             FX3G-2AD-BD
                   Ambient temperature:                                                                       ±1.0%(±400µA) for 40mA full scale
                                                   ±0.5%(±100mV) for 20V full scale
                   0 to 55°C                                                                                 Same accuracy for 4mA to 20mA input
                                                                                                                                                                             FX3U-4DA
                                                                  +32640                                                   +16320
                                                                  +32000                                                   +16000
                                                                                                                                                +20.4mA
                                                                                         +10.2V
                                                                -10V      0                                          -20mA        0
                                                                                  +10V                                                    +20mA                            F
                                                                                                                -20.4mA
                                                       -10.2V
                                                                                                                                                                             FX3U-4DA-ADP
   Input characteristics*4                                                    -32000                                                  -16000
                                                                              -32640                                                  -16320
                                                                                                               zWhen the input mode is set to "3":
                                                                                                                             16400
                                                                                                                             16000
                                                                                                                                                                        G
                                                                                                                                                 20.4mA
                                                                                                                                                                             FX3G-1DA-BD
                                                                                                                                  0 4mA 20mA
                                           • The photocoupler is used to insulate the analog input area from the PLC.
   Insulation method                       • The DC/DC converter is used to insulate the power supply from the analog inputs.                                            H
                                                                                                                                                                       FX3U-4AD-PT
*1. Adjustment of the offset or gain value will not affect the resolution. In the direct indication mode, however, the
                          *2.
                                offset/gain cannot be adjusted.
                                The offset and the gain should satisfy the following condition:
                                                                                                                                                                                 I
                                                                                                                                                                       FX3U-4AD-PTW
                                1V ≤ (Gain - Offset)
                          *3.   The offset and the gain should satisfy the following condition:
                                3mA ≤ (Gain - Offset) ≤ 30mA
                                                                                                                                                                                -ADP
                          *4.   The resolution and the input/output characteristics depend on the selected mode.
                          *5.   If 1 or more channels use the digital filter(s), the time required for A/D conversion will be
                                "5 ms × number of selected channels."                                                                                                      J
                                                                                                                                                                       FX3U-4AD-PNK
                                                                                                                                                                                -ADP
                                                                                                                                                            A-23
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                            4 Comparison of Performance Specifications
Common Items                                                                                                                                           4.1 Analog Input
4.1.4 FX2N-4AD
                                                                                                         FX2N-4AD
                     Specifications
                                                                         Voltage input                                             Current input
   Number of input points                                                                                  4ch
                                                                                                                             -20mA to +20mA DC
                                                                     -10V to +10V DC
   Analog input range                                                                                                          4mA to 20mA DC
                                                                 (Input resistance: 200kΩ)
                                                                                                                           (Input resistance: 250 Ω)
   Absolute maximum input                                                      ±15V                                                   ±32mA
                                                                                      *1,*2
   Offset                                                               -5V to +5V                                            -20mA to +20mA*1,*3
   Gain                                                                 -4V to +15V*1,*2                                      -16mA to +32mA*1,*3
   Digital output                                                With sign, 12 bits, binary                                With sign, 11 bits, binary
                                                                                                *1
   Resolution                                                      5mV(20V×1/4000)                                            20µA(40mA×1/2000)*1
Overall accuracy
                   Ambient temperature:
                                                                                -                                                          -
                   25±5°C
   Time required for A/D                                              Normal conversion mode:15ms × number of selected channels
   conversion                                                        High-speed conversion mode: 6ms × number of selected channels
                                                                    +2000
                                                                                                                          +1000
                                                                                                                                               +32mA
                                                                 -10V      0
                                                                                      +10V                            -20mA    0
                                                      -10.240V
                                                                                                                                    +20mA
                                                                                                                  -32mA
                                                                               -2000
   Input characteristics                                                                                                           -1000
                                                                               -2048
                                                                                                                                   -1600
                                                                                                                 zWhen the input is set from 4 mA to 20 mA:
                                                                                                                           1750
                                                                                                                           1000
                                                                                                                                               32mA
0 4mA 20mA
                                            • The photocoupler is used to insulate the analog input area from the PLC.
   Insulation method                        • The DC/DC converter is used to insulate the power supply from the analog inputs.
                                            • Channels are not insulated from each other.
   Number of I/O points
                                            8 points (Taken from either the input or output points of the PLC.)
   occupied
                          *1.   Adjustment of the offset or gain value will not affect the resolution.
                          *2.   The offset and the gain should satisfy the following condition:
                                1V ≤ (Gain - Offset) ≤ 15V
                          *3.   The offset and the gain should satisfy the following condition:
                                4mA ≤ (Gain - Offset) ≤ 32mA
A-24
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                     4 Comparison of Performance Specifications
Common Items                                                                                                                                         4.1 Analog Input
                                                                                                                                                                          A
4.1.5                    FX3UC-4AD
                                                                                                                                                                              Common Items
                                                                                                  FX3UC-4AD
                     Specifications
                                                                       Voltage input                                             Current input
   Number of input points                                                                            4ch
                                                                                                                             -20mA to +20mA DC
                                                                                                                                                                          B
                                                            -10V to +10V DC
                                                                                                                                                                        FX3UC-4AD
                                                                                                                                                                        FX3U-4AD
   Analog input range                                                                                                          4mA to 20mA DC
                                                        (Input resistance: 200 kΩ)
                                                                                                                           (Input resistance: 250 Ω)
   Absolute maximum input                                                 ±15V                                                      ±30mA
                                                                                 *1,*2
   Offset                                                          -10V to +9V                                              -20mA to +17mA*1,*3
   Gain                                                            -9V to +10V*1,*2                                         -17mA to +30mA*1,*3                           C
                                                                                                                                                                              FX3U-4AD-ADP
   Digital output                                         With sign, 16 bits, binary                                       With sign, 15 bits, binary
                                                                0.32mV(20V×1/64000)                                        1.25µA(40mA×1/32000)
   Resolution*4                                                  2.5mV(20V×1/8000)                                          5.00µA(40mA×1/8000)
Overall accuracy
                                                                                                                                                                              FX3G-2AD-BD
                   Ambient temperature:                                                                        ±1.0%(±400µA) for 40mA full scale
                                                   ±0.5%(±100mV) for 20V full scale
                   0 to 55°C                                                                                  Same accuracy for 4mA to 20mA input
                                                                                                                                                                              FX3U-4DA
                                                                  +32640                                                    +16320
                                                                  +32000                                                    +16000
                                                                                                                                                 +20.4mA
                                                                                         +10.2V
                                                                -10V      0                                           -20mA        0
                                                                                  +10V                                                     +20mA                            F
                                                                                                                 -20.4mA
                                                       -10.2V
                                                                                                                                                                              FX3U-4DA-ADP
   Input characteristics*4                                                    -32000                                                   -16000
                                                                              -32640                                                   -16320
                                                                                                                zWhen the input mode is set to "3":
                                                                                                                              16400
                                                                                                                              16000
                                                                                                                                                                         G
                                                                                                                                                  20.4mA
                                                                                                                                                                              FX3G-1DA-BD
                                                                                                                                   0 4mA 20mA
                                           • The photocoupler is used to insulate the analog input area from the PLC.
   Insulation method                       • The DC/DC converter is used to insulate the power supply from the analog inputs.                                             H
                                                                                                                                                                        FX3U-4AD-PT
*1. Adjustment of the offset or gain value will not affect the resolution. In the direct indication mode, however, the
                          *2.
                                offset/gain cannot be adjusted.
                                The offset and the gain should satisfy the following condition:
                                                                                                                                                                                  I
                                                                                                                                                                        FX3U-4AD-PTW
                                1V ≤ (Gain - Offset)
                          *3.   The offset and the gain should satisfy the following condition:
                                3mA ≤ (Gain - Offset) ≤ 30mA
                                                                                                                                                                                 -ADP
                          *4.   The resolution and the input/output characteristics depend on the selected mode.
                          *5.   If 1 or more channels use the digital filter(s), the time required for A/D conversion will be
                                "5 ms × number of selected channels."                                                                                                       J
                                                                                                                                                                        FX3U-4AD-PNK
                                                                                                                                                                                 -ADP
                                                                                                                                                             A-25
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                 4 Comparison of Performance Specifications
Common Items                                                                                                                                    4.1 Analog Input
4.1.6 FX2NC-4AD
                                                                                              FX2NC-4AD
   Specifications
                                                                  Voltage input                                              Current input
   Number of input points                                                                        4ch
                                                                                                                         -20mA to +20mA DC
                                                                -10V to +10V DC
   Analog input range                                                                                                      4mA to 20mA DC
                                                            (Input resistance: 200kΩ)
                                                                                                                       (Input resistance: 250 Ω)
   Absolute maximum input                                             ±15V                                                      ±30mA
                                                                               *1,*2
   Offset                                                        -10V to +9V                                            -20mA to +17mA*1,*3
   Gain                                                          -9V to +10V*1,*2                                       -17mA to +30mA*1,*3
   Digital output                                           With sign, 16 bits, binary                                 With sign, 15 bits, binary
                                                             0.32mV(20V×1/64000)                                       1.25µA(40mA×1/32000)
   Resolution*4                                               2.5mV(20V×1/8000)                                        5.00µA(40mA×1/8000)
Overall accuracy
                                                  zWhen the input mode is set to "0":                      zWhen the input mode is set to "6":
                                                     +32640                                                              +16320
                                                     +32000                                                              +16000
                                                                                                                                             +20.4mA
                                                                                +10.2V
                                                          -10V   0                                                     -20mA 0
                                                                         +10V                                                          20mA
                                                                                                             -20.4mA
                                                 -10.2V
                                                                                                                                0 4mA 20mA
                                           • The photocoupler is used to insulate the analog input area from the PLC.
   Insulation method                       • The DC/DC converter is used to insulate the power supply from the analog inputs.
                                           • Channels are not insulated from each other.
   Number of I/O points
                                           8 points (Taken from either the input or output points of the PLC.)
   occupied
                          *1.   Adjustment of the offset or gain value will not affect the resolution. In the direct indication mode, however, the
                                offset/gain cannot be adjusted.
                          *2.   The offset and the gain should satisfy the following condition:
                                1V ≤ (Gain - Offset)
                          *3.   The offset and the gain should satisfy the following condition:
                                3mA ≤ (Gain - Offset) ≤ 30mA
                          *4.   The resolution and the input/output characteristics depend on the selected mode.
                          *5.   If 1 or more channels use the digital filter(s), the time required for A/D conversion will be
                                "5 ms × number of selected channels."
A-26
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                      4 Comparison of Performance Specifications
Common Items                                                                                                                                         4.1 Analog Input
                                                                                                                                                                          A
4.1.7                    FX2N-8AD
                                                                                                                                                                              Common Items
                                                                                                    FX2N-8AD
                     Specifications
                                                                      Voltage input                                                Current input
   Number of input points                                                                             8ch
                                                                                                                                                                          B
                                                                                                                               -20mA to +20mA DC
                                                                                                                                                                        FX3UC-4AD
                                                                                                                                                                        FX3U-4AD
                                                             -10V to +10V DC
   Analog input range                                                                                                            4mA to 20mA DC
                                                         (Input resistance: 200 kΩ)
                                                                                                                             (Input resistance: 250 Ω)
   Absolute maximum input                                                   ±15V                                                      ±30mA
                                                                                   *1,*2
   Offset                                                            -10V to +9V                                              -20mA to +17mA*1,*3
   Gain                                                              -9V to +10V*1,*2                                         -17mA to +30mA*1,*3
                                                                                                                                                                          C
                                                                                                                                                                              FX3U-4AD-ADP
   Digital output                                             With sign, 15 bits, binary                                     With sign, 14 bits, binary
                                                               0.63mV(20V×1/32000)                                           2.50µA(40mA×1/16000)
   Resolution*4                                                 2.5mV(20V×1/8000)                                            2.00µA(16mA×1/8000)
Overall accuracy
                                                                                                                                                                              FX3G-2AD-BD
                   Ambient temperature:                                                                         ±0.5%(±200µA) for 40mA full scale
                                                   ±0.5%(±100mV) for 20V full scale
                   0 to 55°C                                                                                   Same accuracy for 4mA to 20mA input
                                                                                                                                                                              FX3U-4DA
                                                  zWhen the input mode is set to "0":                            zWhen the input mode is set to "6":
                                                                +16320
                                                                                                                                +8160
                                                                +16000
                                                                                                                                +8000
                                                                                                                                                   +20.4mA
                                                                                           +10.2V
                                                              -10V      0                                                -20mA       0                                      F
                                                                                   +10V                                                     +20mA
                                                                                                                                                                              FX3U-4DA-ADP
                                                     -10.2V
-20.4mA
                                                                                                                                                                              FX3G-1DA-BD
                                                                                                                                 8000
                                                                                                                                                    20.4mA
0 4mA 20mA
                                          • The photocoupler is used to insulate the analog input area from the PLC.
                                                                                                                                                                          H
                                                                                                                                                                        FX3U-4AD-PT
   Insulation method                      • The DC/DC converter is used to insulate the power supply from the analog inputs.
                                          • Channels are not insulated from each other.
   Number of I/O points
                                                                                                                                                                                 -ADP
                                          8 points (Taken from either the input or output points of the PLC.)
   occupied
                          *1.   Adjustment of the offset or gain value will not affect the resolution. In the direct indication mode, however, the
                                offset/gain cannot be adjusted.
                                                                                                                                                                                  I
                                                                                                                                                                        FX3U-4AD-PTW
                          *2.   The offset and the gain should satisfy the following condition:
                                1V ≤ (Gain - Offset)
                          *3.   The offset and the gain should satisfy the following condition:
                                                                                                                                                                                 -ADP
                                                                                                                                                             A-27
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                          4 Comparison of Performance Specifications
Common Items                                                                                                                                             4.1 Analog Input
4.1.8 FX3G-2AD-BD
                                                                                                      FX3G-2AD-BD
                     Specifications
                                                                          Voltage input                                                Current input
   Number of input points                                                                                 2ch
                                                                          0V to 10V DC                                                4mA to 20mA DC
   Analog input range
                                                                  (Input resistance: 198.7 kΩ)                                    (Input resistance: 250 Ω)
   Absolute maximum input                                                 -0.5V. +15V                                                  -2mA, +30mA
   Offset
                                                                      Impossible to change                                          Impossible to change
   Gain
   Digital output                                                        12 bits, binary                                               11 bits, binary
   Resolution                                                         2.5mV(10V×1/4000)                                              8µA(16mA×1/2000)
Overall accuracy
                   Ambient temperature:
                                                    ±0.5%(±50mV) for 10V full scale                                        ±0.5%(±80µA) for 16mA full scale
                   25±5°C
                   Ambient temperature:
                                                 ±1.0%(±100mV) for 10V full scale                                      ±1.0%(±160µA) for 16mA full scale
                   0 to 55°C
                                                 4080                                                           2040
                                                 4000
                                                                                                                2000
                                                                                                                Digital output
                                                 Digital output
Input characteristics
A-28
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                4 Comparison of Performance Specifications
Common Items                                                                                                                                                        4.2 Analog Output
                                                                                                                                                                                          A
4.2                      Analog Output
                                                                                                                                                                                              Common Items
4.2.1                    FX3U-4DA-ADP
                                                                                                        FX3U-4DA-ADP
                                                                                                                                                                                          B
                                                                                                                                                                                        FX3UC-4AD
                                                                                                                                                                                        FX3U-4AD
                    Specifications
                                                                          Voltage output                                                           Current output
   Number of output points                                                                                   4ch
                                                           0V to 10V DC                                                           4mA to 20mA DC
   Analog output range
                                                     (External load: 5k to 1MΩ)                                              (External load: 500Ω or less)
   Offset                                                                                                                                                                                 C
                                                                Impossible to change                                                  Impossible to change
                                                                                                                                                                                              FX3U-4AD-ADP
   Gain
   Digital input                                                                                        12 bits, binary
   Resolution                                                        2.5mV(10V×1/4000)                                                         4µA(16mA×1/4000)
                   Ambient temperature:
                                                  ±0.5%(±50mV) for 10V full scale                                         ±0.5%(±80µA) for 16mA full scale
                   25±5°C                                                                                                                                                                 D
Overall accuracy
Ambient temperature:
                                                                                                                                                                                              FX3G-2AD-BD
                                                 ±1.0%(±100mV) for 10V full scale                                         ±1.0%(±160µA) for 16mA full scale
                   0 to 55°C
                                          If the external load resistance (Rs) is less than
                                          5kΩ, the load will be increased as shown in the
                   Reference              following formula: (Increase: 100 mV per 1%)                                                                    -
                                             47×100
                                             Rs+47
                                                    -0.9(%)                                                                                                                                E
                                                                                                                                                                                              FX3U-4DA
   Time required for D/A                  • FX3U/FX3UC Series PLC : 200µs (Data updated every scan time.)
   conversion                             • FX3G Series PLC : 250µs (Data updated every scan time.)
                                                            10V                                                               20mA                                                          F
                                                                                                                               Analog output
                                                                                                                                                                                              FX3U-4DA-ADP
                                                     Analog output
   Output characteristics
                                                                                                 4080
                                                                                                                                                                       4080
                                                                                                                               4mA
                                                                      0
                                                                          Digital input
                                                                                          4000                                                 0                4000
                                                                                                                                                    Digital input
                                                                                                                                                                                         G
                                                                                                                                                                                              FX3G-1DA-BD
                                          • The photocoupler is used to insulate the analog output area from the PLC.
   Insulation method                      • The DC/DC converter is used to insulate the power supply from the analog inputs.
                                          • Channels are not insulated from each other.
   Number of I/O points
   occupied
                                          0 point (This number is not related to the maximum I/O points of the PLC.)                                                                      H
                                                                                                                                                                                        FX3U-4AD-PT
                                                                                                                                                                                                 -ADP
                                                                                                                                                                                                  I
                                                                                                                                                                                        FX3U-4AD-PTW
                                                                                                                                                                                                 -ADP
                                                                                                                                                                                            J
                                                                                                                                                                                        FX3U-4AD-PNK
                                                                                                                                                                                                 -ADP
                                                                                                                                                                              A-29
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                    4 Comparison of Performance Specifications
Common Items                                                                                                                                         4.2 Analog Output
4.2.2 FX2N-2DA
                                                                                              FX2N-2DA
       Specifications
                                                              Voltage output                                                       Current output
Number of output points                                                                          2ch
                                                0V to 10V DC
                                                                                                                      4mA to 20mA DC
Analog output range                              0V to 5V DC
                                                                                                                 (External load: 400Ω or less)
                                          (External load: 2k to 1MΩ)
                                               If the digital value is "0":                                        If the digital value is "0":
Offset*1,*2                                             0V to 1V                                                               4mA
                                         If the digital value is "4000":                                         If the digital value is "4000":
Gain*1,*2                                          5V to 10V                                                                  20mA
Digital output                                                                              12 bits, binary
                                                                                     *2
Resolution                                          2.5mV(10V×1/4000)                                                    4µA(16mA×1/4000)*2
                                                                   ±0.1V                                                                ±0.16mA
Overall accuracy
                                    Does not include any load fluctuation.                                                                  -
Time required for D/A                                                        4ms × number of selected channels
conversion                                                             (Operation synchronized with sequence program)
10V 20mA
                                                                                                                   Analog output
                                          Analog output
Output characteristics
                                                                                     4095
                                                                                                                                                         4095
                                                                                                                   4mA
                                                          0                   4000                                                 0              4000
                                                              Digital input                                                            Digital input
                              If the input data consists of 13 bits or more, only the lower 12 bits will be valid, and the other bits will
                              be ignored.
                              • The photocoupler is used to insulate the analog output area from the PLC.
Insulation method
                              • Channels are not insulated from each other.
Number of I/O points
                              8 points (Taken from either the input or output points of the PLC.)
occupied
              *1.   Use the adjustment volume to adjust the FX2N-2DA.
              *2.   Adjustment of the offset or gain value will change the resolution.
A-30
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                              4 Comparison of Performance Specifications
Common Items                                                                                                                               4.2 Analog Output
                                                                                                                                                                 A
4.2.3                    FX3U-4DA
                                                                                                                                                                     Common Items
                                                                                            FX3U-4DA
                     Specifications
                                                                 Voltage output                                          Current output
   Number of output points                                                                     4ch                                                               B
                                                                                                                 0mA to 20mA DC
                                                                                                                                                               FX3UC-4AD
                                                                                                                                                               FX3U-4AD
                                                                -10V to +10V DC
   Analog output range                                                                                           4mA to 20mA DC
                                                            (External load: 1k to 1MΩ)
                                                                                                            (External load: 500Ω or less)
   Offset                                                        -10V to +9V*1,*2                                    0mA to 17mA*1,*3
   Gain                                                          -9V to +10V*1,*2                                    3mA to 30mA*1,*3
   Digital input                                            With sign, 16 bits, binary                                   15 bits, binary
                                                                                                                                                                 C
                                                                                                                                                                     FX3U-4AD-ADP
   Resolution                                               0.32mV(20V×1/64000)*4                            0.63µA(20mA×1/32000)*4
                   Ambient temperature:                                                                  ±0.3%(±60µA) for 20mA full scale
Overall accuracy
                                                                                                                                                                     FX3G-2AD-BD
                   Reference               Includes corrective function by load fluctuation.                                    -
                                                 zWhen the output mode is set to "0":                       zWhen the output mode is "2":
                                                                                                             (The dotted line is for mode 3.)                     E
                                                              +10.2V
                                                                                                                                                                     FX3U-4DA
                                                                                                           20.4mA
                                                               +10V
                                                                                  +32640
20mA
                                                                    0
                                                                                                            output
                                                                           +32000
                                                                                                                                                                   F
                                                   -32640
32640
                                                                                                                                                                     FX3U-4DA-ADP
                                                                                                              4mA
                                                                        -10V
                                                                        -10.2V                                       0               32000
                                                                                                                          Digital input
                                          • The photocoupler is used to insulate the analog output area from the PLC.
   Insulation method                      • The DC/DC converter is used to insulate the power supply from the analog output.
                                          • Channels are not insulated from each other.
                                                                                                                                                                G
                                                                                                                                                                     FX3G-1DA-BD
   Number of I/O points
                                          8 points (Taken from either the input or output points of the PLC.)
   occupied
                          *1.   Adjustment of the offset or gain value will not affect the resolution. In the analog value specification
                                mode, however, the offset/gain cannot be adjusted.
                          *2.   The offset and the gain should satisfy the following condition:                                                                  H
                                1V ≤ (Gain - Offset) ≤ 10V
                                                                                                                                                               FX3U-4AD-PT
                          *3.   The offset and the gain should satisfy the following condition:
                                3mA ≤ (Gain - Offset) ≤ 30mA
                                                                                                                                                                        -ADP
                          *4.   Adjustment of the offset or gain value will not affect the resolution.
                                                                                                                                                                         I
                                                                                                                                                               FX3U-4AD-PTW
                                                                                                                                                                        -ADP
                                                                                                                                                                   J
                                                                                                                                                               FX3U-4AD-PNK
                                                                                                                                                                        -ADP
                                                                                                                                                    A-31
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                    4 Comparison of Performance Specifications
Common Items                                                                                                                             4.2 Analog Output
4.2.4 FX2N-4DA
                                                                                FX2N-4DA
       Specifications
                                                    Voltage output                                                    Current output
Number of output points                                                            4ch
                                                                                                      0mA to 20mA DC
                                            -10V to +10V DC
Analog output range                                                                                   4mA to 20mA DC
                                        (External load: 2k to 1MΩ)
                                                                                                 (External load: 500Ω or less)
Offset                                             -5V to +5V*1,*2                                                -20mA to +20mA*1,*3
                                                  15 V or less, and                                               32 mA or less, and
Gain
                                                  Gain - Offset ≥ 1V                                              Gain - Offset ≥ 4mA
Digital output                            With sign, 12 bits, binary                                                  10 bits, binary
Resolution                                                            *1                                    20µA(20mA×1/1000)*1
                                                 5mV(10V×1/2000)
                                                                                              ±1.0%(±200µA) for 20mA full scale
                                    ±1.0%(±200mV) for 20V full scale
Overall accuracy                                                                            Same accuracy for 4mA to 20mA output
                                  Does not include any load fluctuation.                                                      -
Time required for D/A
                                                   2.1 ms (The number of selected channels will not affect this value.)
conversion
                                       zWhen the output mode is set to "0":                      zWhen the output mode is "2":
                                                                                                  (The dotted line is for mode 1.)
+10V 20mA
                                                                                                  Analog output
                                                                      +2047
                                                                                                                                         1023
                                                                                                  4mA
                                                             -10V                                                 0                   1000
                                                                                                                      Digital input
                           • The photocoupler is used to insulate the analog input area from the PLC.
Insulation method          • The DC/DC converter is used to insulate the power supply from the analog output.
                           • Channels are not insulated from each other.
Number of I/O points
                           8 points (Taken from either the input or output points of the PLC.)
occupied
             *1.   Adjustment of the offset or gain value will not affect the resolution.
             *2.   The offset and the gain should satisfy the following condition:1
                   1V ≤ (Gain - Offset) ≤ 15V
             *3.   The offset and the gain should satisfy the following condition:
                   4mA ≤ (Gain - Offset) ≤ 32mA
A-32
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                4 Comparison of Performance Specifications
Common Items                                                                                                                                4.2 Analog Output
                                                                                                                                                                  A
4.2.5                    FX2NC-4DA
                                                                                                                                                                      Common Items
                                                                                            FX2NC-4DA
                     Specifications
                                                                  Voltage output                                          Current output
   Number of output points                                                                      4ch                                                               B
                                                                                                                   0mA to 20mA DC
                                                                                                                                                                FX3UC-4AD
                                                                                                                                                                FX3U-4AD
                                                                 -10V to +10V DC
   Analog output range                                                                                             4mA to 20mA DC
                                                             (External load: 2k to 1MΩ)
                                                                                                              (External load: 500Ω or less)
   Offset                                                         -5V to +5V*1,*2                                     -20mA to +20mA*1,*3
   Gain                                                           -4V to +15V*1,*2                                    -16mA to +32mA*1,*3
   Digital input                                             With sign, 12 bits, binary                                   10 bits, binary
                                                                                                                                                                  C
                                                                                                                                                                      FX3U-4AD-ADP
   Resolution*1                                                 5mV(20V×1/4000)                                       20µA(20mA×1/1000)
                   Ambient temperature:                                                                    ±0.5%(±100µA) for 20mA full scale
Overall accuracy
                                                                                                                                                                      FX3G-2AD-BD
                   Reference                      Does not include any load fluctuation.                                         -
                                                   zWhen the output mode is set to "0":                      zWhen the output mode is "2":
                                                                                                              (The dotted line is for mode 1.)                     E
                                                                                                                                                                      FX3U-4DA
                                                                 +10V
                                                                                                              20mA
                                                                                    +2047
                                                                     0
                                                                                                             output
                                                                            +2000
                                                                                                                                                                    F
                                                     -2048
1023
                                                                                                                                                                      FX3U-4DA-ADP
                                                                                                               4mA
                                                                         -10V
                                                                                                                      0              1000
                                                                                                                          Digital input
                                            • The photocoupler is used to insulate the analog output area from the PLC.
   Insulation method                        • The DC/DC converter is used to insulate the power supply from the analog output.
                                            • Channels are not insulated from each other.
                                                                                                                                                                 G
                                                                                                                                                                      FX3G-1DA-BD
   Number of I/O points
                                            8 points (Taken from either the input or output points of the PLC.)
   occupied
                          *1.   Adjustment of the offset or gain value will not affect the resolution.
                          *2.   The offset and the gain should satisfy the following condition:
                                1V ≤ (Gain - Offset) ≤ 15V                                                                                                        H
                                                                                                                                                                FX3U-4AD-PT
                          *3.   The offset and the gain should satisfy the following condition:
                                4mA ≤ (Gain - Offset) ≤ 32mA
                                                                                                                                                                         -ADP
                                                                                                                                                                          I
                                                                                                                                                                FX3U-4AD-PTW
                                                                                                                                                                         -ADP
                                                                                                                                                                    J
                                                                                                                                                                FX3U-4AD-PNK
                                                                                                                                                                         -ADP
                                                                                                                                                     A-33
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                       4 Comparison of Performance Specifications
Common Items                                                                                                                                                 4.2 Analog Output
4.2.6 FX3G-1DA-BD
                                                                                                   FX3G-1DA-BD
                     Specifications
                                                                          Voltage output                                                  Current output
   Number of output points                                                                             1ch
                                                                       0V to 10V DC                                                    4mA to 20mA DC
   Analog output range
                                                                 (External load: 2k to 1MΩ)                                       (External load: 500Ω or less)
   Offset
                                                                      Impossible to change                                             Impossible to change
   Gain
   Digital input                                                          12 bits, binary                                                  11 bits, binary
   Resolution                                                         2.5mV(10V×1/4000)                                                8µA(16mA×1/2000)
                   Ambient temperature:
                                                       ±0.5%(±50mV) for 10V full scale                             ±0.5%(±80µA) for 16mA full scale
                   25±5°C
                   Ambient temperature:
Overall accuracy
                                                   ±1.0%(±100mV) for 10V full scale                              ±1.0%(±160µA) for 16mA full scale
                   0 to 55°C
                                          Shipment adjustment is carried out by external
                                          load resistance 2kΩ.
                                          If external load resistance becomes larger than
                   Reference                                                                                                                      -
                                          2kΩ, the output voltage will increase slightly.
                                          When the load is 1MΩ, the output voltage is
                                          about 2% higher than the correct value.
   Time required for D/A
                                                                                       60µs (Data updated every scan time.)
   conversion
                                                      10V                                                        20mA
                                                                                                                  Analog output
                                                 Analog output
   Output characteristics
                                                                                                                      4mA
                                          Caution:
                                          An area of dead band is located in the region of
                                          0V. Therefore the output analog value may not
                                          represent the digital value accurately.
   Insulation method                      • The analog output area is not insulated from the PLC.
   Number of I/O points
                                          0 point (This number is not related to the maximum I/O points of the PLC.)
   occupied
A-34
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                     4 Comparison of Performance Specifications
Common Items                                                                                                                         4.3 Mixed Analog Input/Output
                                                                                                                                                                              A
4.3       Mixed Analog Input/Output
                                                                                                                                                                                  Common Items
4.3.1     FX2N-5A
        1. Analog input
                                                                                                                                                                              B
                                                                                                                                                                            FX3UC-4AD
                                                                                                                                                                            FX3U-4AD
                                                                                                        FX2N-5A
                              Specifications
                                                                             Voltage input                                             Current input
             Number of output points                                                                     4ch
                                                                     -10V to +10V DC                                            -20mA to +20mA DC
             Analog input/output
             range
                                                                  -100mV to +100mV DC                                             4mA to 20mA DC                              C
                                                                 (Input resistance: 200kΩ)                                    (Input resistance: 250Ω)
                                                                                                                                                                                  FX3U-4AD-ADP
             Absolute maximum input                                             ±15V                                                       ±30mA
                                                  • -10V to +10V DC:
                                                    -32V to +5V DC
             Offset                                                                                                                  -32mA to +10mA
                                                  • -100mV to +100mV DC:
                                                    -320mV to +50mV DC
                                                  • -10V to +10V DC:
                                                                                                                                                                              D
                                                                                                                                                                                  FX3G-2AD-BD
                                                    -5V to +32V, and Gain - Offset > 1V                                            -10mA to +32mA, and
             Gain
                                                  • -100mV to +100mV DC:                                                            Gain - Offset > 1 mA
                                                    -50mV to +320mV, and Gain - Offset > 10mA
                                                  • -10V to +10V DC:
                                                    With sign, 16 bits, binary
             Digital input/output
                                                  • -100mV to +100mV DC:
                                                                                                                             With sign, 15 bits, binary
                                                                                                                                                                               E
                                                    With sign, 12 bits, binary
                                                                                                                                                                                  FX3U-4DA
                                                                      312.5µV(20V×1/64000)                                     1.25µA(40mA×1/32000)
             Resolution
                                                                       50µV(200mV×1/4000)                                       10µA(40mA×1/4000)
                                                  • -10V to +10V DC:
                             Ambient temperature:   ±0.3% (±60mV) for 20V full scale                               ±0.3%(±120µA) for 40mA full scale
          Overall accuracy
                                                                                                                                                                                  FX3U-4DA-ADP
                                                  • -10V to +10V DC:
                             Ambient temperature:   ±0.5% (±100mV) for 20V full scale                              ±0.5%(±200µA) for 40mA full scale
                             0±55°C               • -100mV to +100mV DC:                                          Same accuracy for 4mA to 20mA input
                                                    ±1.0% (±2mV) for 200mV full scale
             Time required for
                                                                                       1ms × number of selected channels
             conversion                                                                                                                                                      G
                                                                                                                                                                                  FX3G-1DA-BD
                                                         zWhen the input mode is set to "0":                        zWhen the input mode is set to "2":
                                                                        +32767                                             +32767
                                                                                                                                                         +20.480mA
                                                                                                                           +32000
                                                                                             +10.240V
+32000
                                                                      -10V      0                                                  -20mA    0
                                                                                                                                                    +20mA
                                                                                                                                                                              H
                                                                                                                       -20.480mA
                                                                                        +10V
                                                           -10.240V
FX3U-4AD-PT
                                                                                    -32000                                                      -32000
             I/O characteristics
                                                                                                                                                                                     -ADP
                                                                                    -32768                                                      -32768
                                                                                                                    zWhen the input mode is set to "1":
                                                                                                                         +32767                                                       I
                                                                                                                         +32000
                                                                                                                                                          20.383mA
FX3U-4AD-PTW
                                                                                                                                           2mA
                                                                                                                                                                                     -ADP
                                                                                                                                       0         4mA 20mA
                                                                                                                                   -4000
                                                                                                                                                                                J
                                                                                                                                                                            FX3U-4AD-PNK
                                                                                                                                                                                     -ADP
                                                                                                                                                                     A-35
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                         4 Comparison of Performance Specifications
Common Items                                                                                                                 4.3 Mixed Analog Input/Output
       2. Analog output
                                                                                                FX2N-5A
                               Specifications
                                                                      Voltage output                                         Current output
            Number of output points                                                              1ch
                                                                                                               0mA to 20mA DC
                                                                 -10V to +10V DC
            Analog input/output range                                                                          4mA to 20mA DC
                                                             (External load: 5k to 1MΩ)
                                                                                                          (External load: 500Ω or less)
            Offset                                                     -10V to +5V                                           0mA to 10mA
                                                                    -9V to +10V, and                         3 mA to 30 mA or less, and
            Gain
                                                                    Gain - Offset ≥ 1V                          Gain - Offset ≥ 3mA
            Digital input/output                                 With sign, 12 bits, binary                                  10 bits, binary
            Resolution                                              5mV(10V×1/4000)                                        20µA(20mA×1/1000)
         Overall accuracy
                                                      zWhen the output mode is set to "0":                zWhen the output mode is "4":
                                                                                                           (The dotted line is for mode 2.)
                                                                     +10V
                                                                                                          20mA
                                                                                       +32767
                                                                                                           Analog output
                                                                 -32000 0
            I/O characteristics
                                                                             +32000
                                                        -32768
                                                                                                                                           32767
                                                                            -10V                          4mA
                                                                                                            0              32000
                                                                                                             Digital input
       3. Other
                               Specifications                                                   FX2N-5A
                                                   • The photocoupler is used to insulate the analog input and output area from the
                                                     PLC.
            Insulation method                      • The DC/DC converter is used to insulate the power supply from the analog input
                                                     and output.
                                                   • Channels are not insulated from each other.
            Number of I/O points
                                                   8 points (Taken from either the input or output points of the PLC.)
            occupied
A-36
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                                          4 Comparison of Performance Specifications
Common Items                                                                                                                                                             4.3 Mixed Analog Input/Output
                                                                                                                                                                                                                        A
4.3.2        FX0N-3A
                                                                                                                                                                                                                            Common Items
                                                                                                              FX0N-3A
 Specifications
                                          Voltage input                                       Current input                                  Voltage output                                  Current output
Number of
input/output                                                          2ch                                                                                                1ch
                                                                                                                                                                                                                        B
                                                                                                                                                                                                                      FX3UC-4AD
                                                                                                                                                                                                                      FX3U-4AD
points
                         0V to 10V DC                                                                                          0V to 10V DC
Analog input/                                                               4mA to 20mA DC                                                                                             4mA to 20mA DC
                          0V to 5V DC                                                                                           0V to 5V DC
output range*1                                                          (Input resistance: 250Ω)                                                                                     (External load: 500Ω)
                   (Input resistance: 200kΩ)                                                                             (External load: 1k to 1MΩ)
Absolute
maximum
                                             -0.5V,
                                             +15V
                                                                                                -2mA,
                                                                                                +60mA
                                                                                                                                                     -                                              -                   C
input
                                                                                                                                                                                                                            FX3U-4AD-ADP
                    If the digital value is "0":                            If the digital value is "0":                        If the digital value is "0":                   If the digital value is "0":
Offset*2*3                   0V to 1V                                              0mA to 4mA                                            0V to 1V                                          4mA
                   If the digital value is "250": If the digital value is "250": If the digital value is "250": If the digital value is "250":
Gain*2*3                     5V to 10V                        20mA                         5V to 10V                        20mA
Digital input/                                              0 to 250                                                                                                 0 to 250                                           D
output
                                                                                                                                                                                                                            FX3G-2AD-BD
                                                          8 bits, binary                                                                                           8 bits, binary
Resolution*3                         40mV(10V×1/250)                                   64µA(16mA×1/250)                                  40mV(10V×1/250)                                   64µA(16mA×1/250)
Overall
                                             ±0.1V                                              ±0.16mA                                           ±0.1V                                        ±0.16mA
accuracy
Time required
for conversion
                                                      TO instruction processing time × 2 + FROM instruction processing time
                                                                 (operation synchronized with sequence program)
                                                                                                                                                                                                                         E
                                                                                                                                                                                                                            FX3U-4DA
                          255                                                       255
                          250                                                       250                                      10V                                           20mA
                                                                                                                                                                           Analog output
                                                                                                                                                                                                                          F
                                                                            Digital output
                    Digital output
                                                                                                                         Analog output
                                                                                                              20.320mA
                                                                                                                                                                                                                            FX3U-4DA-ADP
                                                            10.200V
I/O
characteristics
                                                                                                                                                                   255
                                                                                                                                                                                                                255
                                                                                                                                                                                4mA
                                      0              10V                                     0 4mA        20mA                           0                   250                  0                       250
                                          Analog input                                          Analog input                                 Digital input                                    Digital input
                                                                                                                                                                                                                       G
                                                                                                                         If the input data consists of 9 bits or more, only the
                                                                                                                                                                                                                            FX3G-1DA-BD
                                                                                                                         lower 8 bits will be valid, and the other bits will be
                                                                                                                         ignored.
Insulation         • The photocoupler is used to insulate the analog input and output area from the PLC.
method             • Channels are not insulated from each other.
Number of I/O                                                                                                                                                                                                           H
points             8 points (Taken from either the input or output points of the PLC.)
                                                                                                                                                                                                                      FX3U-4AD-PT
occupied
             *2.   Adjustment of the volume (offset or gain) value will change the resolution.
             *3.   Adjustment of the offset or gain value will change the resolution.                                                                                                                                           I
                                                                                                                                                                                                                      FX3U-4AD-PTW
                                                                                                                                                                                                                               -ADP
                                                                                                                                                                                                                          J
                                                                                                                                                                                                                      FX3U-4AD-PNK
                                                                                                                                                                                                                               -ADP
                                                                                                                                                                                                           A-37
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                               4 Comparison of Performance Specifications
Common Items                                                                                                     4.4 Temperature Sensor Input
4.4.1 FX3U-4AD-PT-ADP
                                                                            FX3U-4AD-PT-ADP
       Specifications
                                                  Centigrade(°C)                                             Fahrenheit(°F)
Number of input points                                                           4ch
                                                         3-wire platinum resistance thermometer sensor(s)
Input signal
                                                                          JIS C 1604-1997
Rated temperature range                         -50°C to +250°C                                            -58°F to +482°F
Digital output                                    -500 to +2500                                              -580 to +4820
Resolution                                             0.1°C                                                     0.18°F
                          • Ambient temperature: 25°C±5°C ±0.5% for full scale
Overall accuracy
                          • Ambient temperature: 0°C to 55°C ±1.0% for full scale
Time required for         • FX3U/FX3UC Series PLC : 200µs (Data updated every scan time.)
conversion                • FX3G Series PLC : 250µs (Data updated every scan time.)
                                       +2550                                                      +4910
                                       +2500                                                      +4820
                                                                                                 Digital
                                                                                                 output
                                      Digital
                                      output
                                                                                                                              +491°F
                                                                   +255°C
Input characteristics
                                           -50°C                                                 -58°F
                                                   0                                                         0
                                                                                              -67°F
                                   -55°C
                                                            +250°C                                                    +482°F
                                                   -500 Temperature                                          -580 Temperature
                                           -550                                                       -670
                          • The photocoupler is used to insulate the analog input area from the PLC.
Insulation method         • The DC/DC converter is used to insulate the power supply from the analog inputs.
                          • Channels are not insulated from each other.
Number of I/O points      0 points
occupied                  (This number of points is not related to the maximum number of input/output points of the PLC.)
A-38
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                               4 Comparison of Performance Specifications
Common Items                                                                                                        4.4 Temperature Sensor Input
                                                                                                                                                     A
4.4.2     FX3U-4AD-PTW-ADP
                                                                                                                                                         Common Items
                                                                            FX3U-4AD-PTW-ADP
      Specifications
                                                  Centigrade(°C)                                                Fahrenheit(°F)
Number of input points                                                            4ch                                                                B
                                                          3-wire platinum resistance thermometer sensor(s)
                                                                                                                                                   FX3UC-4AD
                                                                                                                                                   FX3U-4AD
Input signal
                                                                           JIS C 1604-1997
Rated temperature range                        -100°C to +600°C                                            -148°F to +1112°F
Digital output                                    -1000 to +6000                                             -1480 to +11120
Resolution                                        0.2°C to 0.3°C                                                0.4°F to 0.5°F
                          • Ambient temperature: 25°C±5°C ±0.5% for full scale
                                                                                                                                                     C
Overall accuracy
                                                                                                                                                         FX3U-4AD-ADP
                          • Ambient temperature: 0°C to 55°C ±1.0% for full scale
Time required for         • FX3U/FX3UC Series PLC : 200µs (Data updated every scan time.)
conversion                • FX3G Series PLC : 250µs (Data updated every scan time.)
                                         +6150
                                         +6000
                                                                                                 +11390
                                                                                                 +11120                                              D
                                                                                                                                                         FX3G-2AD-BD
                                                                                                   Digital
                                                                                                   output
                                        Digital
                                        output
                                                                                                                                 +1139°F
                                                                   +615°C
Input characteristics
                                        -100°C                                                    -148°F
                                                                                                                                                      E
                                                                                               -175°F
                                    -115°C
                                                     0        +600°C                                            0        +1112°F
                                                     -1000Temperature                                           -1480Temperature
                                                                                                                                                         FX3U-4DA
                                             -1150                                                      -1750
                          • The photocoupler is used to insulate the analog input area from the PLC.
Insulation method         • The DC/DC converter is used to insulate the power supply from the analog inputs.
                          • Channels are not insulated from each other.
Number of I/O points      0 points                                                                                                                     F
occupied                  (This number of points is not related to the maximum number of input/output points of the PLC.)
                                                                                                                                                         FX3U-4DA-ADP
                                                                                                                                                    G
FX3G-1DA-BD
                                                                                                                                                     H
                                                                                                                                                   FX3U-4AD-PT
                                                                                                                                                            -ADP
                                                                                                                                                             I
                                                                                                                                                   FX3U-4AD-PTW
                                                                                                                                                            -ADP
                                                                                                                                                       J
                                                                                                                                                   FX3U-4AD-PNK
                                                                                                                                                            -ADP
                                                                                                                                           A-39
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                   4 Comparison of Performance Specifications
Common Items                                                                                                      4.4 Temperature Sensor Input
4.4.3 FX3U-4AD-PNK-ADP
                                                                           FX3U-4AD-PNK-ADP
       Specifications
                                             Centigrade(°C)                                                Fahrenheit(°F)
Number of input points                                                             4ch
                                             Platinum resistance thermometer sensor (2-wire or 3-wire) Pt1000
                                                                     JIS C 1604-1997
Input signal
                                              Nickel resistance thermometer sensor (2-wire or 3-wire) Ni1000
                                                                     DIN 43760-1987
                          Pt1000                      -50°C to +250°C               Pt1000                        -58°F to +482°F
Rated temperature range
                          Ni1000                      -40°C to +110°C               Ni1000                        -40°F to +230°F
                          Pt1000                       -500 to +2500                Pt1000                         -580 to +4820
Digital output
                          Ni1000                       -400 to +1100                Ni1000                         -400 to +2300
                          Pt1000                                                    Pt1000
Resolution                                                  0.1°C                                                       0.2°F
                          Ni1000                                                    Ni1000
                          • Ambient temperature : 25°C±5°C ±0.5% for full scale
Overall accuracy
                          • Ambient temperature : 0°C to 55°C ±1.0% for full scale
Time required for         • FX3U/FX3UC Series PLC : 200µs (Data updated every scan time.)
conversion                • FX3G Series PLC : 250µs (Data updated every scan time.)
                                -Pt1000                                                      -Pt1000
                                         +2560                                                       +4920
                                         +2500                                                       +4820
                                                                                                                                      +492.8°F
                                                                         Approx.
                                                                         +256°C
                                                                                                                                      Approx.
                                     -50°C       0                                                 -58°F     0
                               Approx.
Approx.
                                                               +250°C                                                       +482 °F
                               -55°C
-67°F
                                                     -500                                                        -580
                                                     -550                                                        -670
Input characteristics
                                -Ni1000                                                      -Ni1000
                                         +1150                                                       +2390
                                         +1100                                                       +2300
                                                                         Approx.
                                                                                                                                      Approx.
                                                                         +115°C
+239°F
                                     -40°C       0                                                 -40°F     0
                               Approx.
Approx.
                                                                +110°C                                                      +230°F
                               -45°C
-49°F
                                                     -400                                                        -400
                                                     -450                                                        -490
                          • The photocoupler is used to insulate the analog input area from the PLC.
Insulation method         • The DC/DC converter is used to insulate the power supply line from the analog input area.
                          • Channels are not insulated from each other.
Number of I/O points      0 points
occupied                  (This number of points is not related to the maximum number of input/output points of the PLC.)
A-40
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                            4 Comparison of Performance Specifications
Common Items                                                                                                                     4.4 Temperature Sensor Input
                                                                                                                                                                   A
4.4.4       FX3U-4AD-TC-ADP
                                                                                                                                                                       Common Items
                                                                                       FX3U-4AD-TC-ADP
        Specifications
                                                      Centigrade(°C)                                                     Fahrenheit(°F)
Number of input points                                                                        4ch                                                                  B
                                                                                    Thermocouple type K or J
                                                                                                                                                                 FX3UC-4AD
                                                                                                                                                                 FX3U-4AD
Input signal
                                                                                        JIS C 1602-1995
                          • Type K: -100°C to +1000°C                                           • Type K: -148°F to +1832°F
Rated temperature range
                          • Type J: -100°C to +600°C                                            • Type J: -148°F to +1112°F
                          • Type K: -1000 to +10000                                             • Type K: -1480 to +18320
Digital output
                          • Type J: -1000 to +6000                                              • Type J: -1480 to +11120                                          C
                                                                                                                                                                       FX3U-4AD-ADP
                          • Type K: 0.4°C                                                       • Type K: 0.72°F
Resolution
                          • Type J: 0.3°C                                                       • Type J: 0.54°F
Overall accuracy                                                                ±(0.5% for full scale +1°C)
Time required for         • FX3U/FX3UC Series PLC : 200µs (Data updated every scan time.)
conversion                • FX3G Series PLC : 250µs (Data updated every scan time.)
                                                                                                • Type K
                                                                                                                                                                   D
                          • Type K
                                                                                                                                                                       FX3G-2AD-BD
                                          +10100                                                               +18500
                                          +10000                                                               +18320
                                        Digital
                                        output
                                                                                                            Digital
                                                                                                            output
                                                                                                                                                                    E
                                                                          +1010°C
+1850°F
                                                                                                                                                                       FX3U-4DA
                                         -110°C                                                                -148°F
                                                       0                                                   -166°F            0
                                     -110°C
                                                                    +1000°C                                                               +1832°F
                                                            Temperature                                                          Temperature
                                                       -1000                                                                 -1480
                                              -1100                                                                  -1660
Input characteristics
                          • Type J                                                              • Type J
                                              +6100
                                                                                                                                                                     F
                                                                                                                +11300
                                                                                                                                                                       FX3U-4DA-ADP
                                              +6000
                                                                                                                +11120
                                         Digital
                                         output
                                                                                                               Digital
                                                                                                               output
                                                                                                                                                +1130°F
                                                                            +610°C
                                          -100°C                                                                    -148°F                                        G
                                        -110°C
                                                                                                                                                                       FX3G-1DA-BD
                                                                                                                             0
                                                                                                            -166°F
                                                                     +600°C                                                               +1112°F
                                                            Temperature                                                              Temperature
                                                        -1000                                                                -1480
                                              -1100                                                                 -1660
                          • The photocoupler is used to insulate the analog input area from the PLC.
Insulation method         • The DC/DC converter is used to insulate the power supply from the analog inputs.
                          • Channels are not insulated from each other.                                                                                            H
                                                                                                                                                                 FX3U-4AD-PT
                                                                                                                                                                           I
                                                                                                                                                                 FX3U-4AD-PTW
                                                                                                                                                                          -ADP
                                                                                                                                                                     J
                                                                                                                                                                 FX3U-4AD-PNK
                                                                                                                                                                          -ADP
                                                                                                                                                          A-41
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                              4 Comparison of Performance Specifications
Common Items                                                                                                  4.4 Temperature Sensor Input
4.4.5 FX2N-4AD-PT
                                                                          FX2N-4AD-PT
        Specifications
                                                Centigrade(°C)                                          Fahrenheit(°F)
Number of input points                                                         4ch
                                                         3-wire platinum resistance thermometer sensor(s)
                                                                             DIN43760
Input signal
                                                                       Pt100 JIS C 1604-1997
                                                                       JPt100 JIS C 1604-1981
Input signal current                                              1mA(Constant current system)
Rated temperature range                        -100°C to +600°C                                   -148°F to +1112°F
Digital output                                  -1000 to +6000                                     -1480 to +11120
Resolution                                      0.2°C to 0.3°C                                     0.36°F to 0.54°F
Overall accuracy                                                       ±1.0% for full scale
Time required for
                                                                        60ms(15ms×4ch)
conversion
                                     +6000                                                    +11120
                                     Digital
                                     output
                                                                                              Digital
                                                                                              output
Input characteristics
                                     -100°C                                                   -148°F
                                                 0           +600°C                                       0           +1112°F
                                                         Temperature                                              Temperature
                                                 -1000                                                    -1480
                          • The photocoupler is used to insulate the analog input area from the PLC.
Insulation method         • The DC/DC converter is used to insulate the power supply from the analog inputs.
                          • Channels are not insulated from each other.
Number of I/O points
                          8 points (Count either the input or output points of the PLC.)
occupied
A-42
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                 4 Comparison of Performance Specifications
Common Items                                                                                                    4.4 Temperature Sensor Input
                                                                                                                                                 A
4.4.6     FX2N-4AD-TC
                                                                                                                                                     Common Items
                                                                             FX2N-4AD-TC
      Specifications
                                               Centigrade(°C)                                            Fahrenheit(°F)
Number of input points                                                          4ch                                                              B
                                                                     Thermocouple type K or J
                                                                                                                                               FX3UC-4AD
                                                                                                                                               FX3U-4AD
Input signal
                                                                         JIS C 1602-1995
                          • Type K: -100°C to +1200°C                              • Type K: -148°F to +2192°F
Rated temperature range
                          • Type J: -100°C to +600°C                               • Type J: -148°F to +1112°F
                          • Type K: -1000 to +12000                                • Type K: -1480 to +21920
Digital output
                          • Type J: -1000 to +6000                                 • Type J: -1480 to +11120                                     C
                                                                                                                                                     FX3U-4AD-ADP
                          • Type K: 0.4°C                                          • Type K: 0.72°F
Resolution
                          • Type J: 0.3°C                                          • Type J: 0.54°F
Overall accuracy                                                    ±(0.5% for full scale +1°C)
Time required for
                                                            (240ms±2%)× number of selected channels
conversion
                                                                                                                                                 D
                                                                                                                                                     FX3G-2AD-BD
                                            +12000                                                    +21920
                                           (Type K)                                                  (Type K)
                                 Digital
                                                                                           Digital
                                 output
                                                                                           output
                                             +6000                                                    +11120
                                           (Type J)                                                  (Type J)
Input characteristics                                                                                                                             E
                                            -100°C                                                    -148°F
                                                                                                                                                     FX3U-4DA
                                                      0   +600°C +1200°C                                        0 +1112°F +2192°F
                                                         (Type J) (Type K)                                        (Type J) (Type K)
                                                      -1000                                                     -1480
                                                            Temperature                                              Temperature
                          • The photocoupler is used to insulate the analog input area from the PLC.                                               F
Insulation method         • The DC/DC converter is used to insulate the power supply from the analog inputs.
                                                                                                                                                     FX3U-4DA-ADP
                          • Channels are not insulated from each other.
Number of I/O points
                          8 points (Taken from either the input or output points of the PLC.)
occupied
FX3G-1DA-BD
                                                                                                                                                 H
                                                                                                                                               FX3U-4AD-PT
                                                                                                                                                        -ADP
                                                                                                                                                         I
                                                                                                                                               FX3U-4AD-PTW
                                                                                                                                                        -ADP
                                                                                                                                                   J
                                                                                                                                               FX3U-4AD-PNK
                                                                                                                                                        -ADP
                                                                                                                                      A-43
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                            4 Comparison of Performance Specifications
Common Items                                                                                                                 4.4 Temperature Sensor Input
4.4.7 FX2N-8AD
                                                                                           FX2N-8AD
                    Specifications
                                                              Centigrade(°C)                                         Fahrenheit(°F)
   Number of input points                                                                     8ch
                                                                                 Thermocouple type K, J, and T
   Input signal
                                                                                      JIS C 1602-1995
                           • Type K                                                             • Type K
                             -100°C to +1200°C                                                    -148°F to +2192°F
                           • Type J                                                             • Type J
   Rated temperature range
                             -100°C to +600°C                                                     -148°F to +1112°F
                           • Type T                                                             • Type T
                             -100°C to +350°C                                                     -148°F to +662°F
                                         • Type K                                               • Type K
                                           -1000 to +12000                                        -1480 to +21920
                                         • Type J                                               • Type J
   Digital output
                                           -1000 to +6000                                         -1480 to +11120
                                         • Type T                                               • Type T
                                           -1000 to +3500                                         -1480 to +6620
   Resolution                                                         0.1°C                                                  0.1°F
                                        • Type K:                                               • Type K:
Overall accuracy
                                                            +12000                                                 +21920
                                                           (Type K)                                               (Type K)
                                                 Digital
                                                                                                        Digital
                                                 output
output
                                                             +6000                                                 +11120
                                                           (Type J)                                               (Type J)
                                                             +3500                                                  +6620
   Input characteristics                                   (Type T)                                               (Type T)
                                                                            +600°C                                                      +1112°F
                                                           -100°C          (Type J)                               -148°F                (Type J)
                                                               0   +350°C     +1200°C                                 0       +662°F       +2192°F
                                                                  (Type T)    (Type K)                                       (Type T)      (Type K)
                                                                      -1000                                                  -1480
                                                                           Temperature                                            Temperature
                                         • The photocoupler is used to insulate the analog input area from the PLC.
   Insulation method                     • The DC/DC converter is used to insulate the power supply from the analog inputs.
                                         • Channels are not insulated from each other.
   Number of I/O points
                                         8 points (Taken from either the input or output points of the PLC.)
   occupied
A-44
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                  4 Comparison of Performance Specifications
Common Items                                                                                                                  4.4 Temperature Sensor Input
                                                                                                                                                               A
4.4.8                    FX2N-2LC
                                                                                                                                                                   Common Items
                                                                                             FX2N-2LC*1*2
                     Specifications
                                                                Centigrade(°C)                                            Fahrenheit(°F)
   Number of input points                                                                         2ch
                                                               Thermocouple type K, J, R, S, E, T, B, N, PL II, WRe5-26, U, and L
                                                                                                                                                               B
                                                                                                                                                             FX3UC-4AD
                                                                                                                                                             FX3U-4AD
                                                                                       JIS C 1602-1995
   Input signal
                                                                      3-wire platinum resistance thermometer sensor(s)
                                                                      Pt100 JIS C 1604-1997, JPt100 JIS C 1604-1981
                                           Examples:                                                Examples:
                                           • Type K                                                 • Type K
   Rated temperature range                   -100°C to +1300°C                                        -100°F to +2400°F                                        C
                                           • Type J                                                 • Type J
                                                                                                                                                                   FX3U-4AD-ADP
                                             -100.0°C to +800.0°C                                     -100°F to +2100°F
                                           Examples:                                                Examples:
                                           • Type K                                                 • Type K
   Digital output                            -100 to +1300                                            -100 to +2400
                                           • Type J                                                 • Type J                                                   D
                                             -1000 to +8000                                           -100 to +2100
                                                                                                                                                                   FX3G-2AD-BD
   Resolution                                                    1°C or 0.1°C                                             1°F or 0.1°F
Overall accuracy
                   Ambient temperature:
                                                                                     ±0.3°C(±1digit) for full scale
                   23±5°C
                                                                                                                                                                E
                   Ambient temperature:
                                                                                  ±0.7°C (±1digit) for full scale
                                                                                                                                                                   FX3U-4DA
                   0 to 55°C
                                                                                               ±1.0°C
   Cold junction temperature
                                                                 ±2.0°C if the input value is in the range from -150°C to -100°C
   compensation error
                                                                 ±3.0°C if the input value is in the range from -200°C to -150°C
   Time required for
                                                                                      500ms(Sampling period)
                                                                                                                                                                 F
   conversion
                                                                                                                                                                   FX3U-4DA-ADP
                                                     zWhen type K (input mode 2)                                zWhen type K (input mode 4)
                                                      is set:                                                    is set:
                                                      +1300                                                     +2400
                                                                                                                                                              G
                                                     Digital
                                                     output
                                                                                                                Digital
                                                                                                                output
                                                                                                                                                                   FX3G-1DA-BD
   Input characteristics
                                                     -100°C                                                     -100°F
                                                                 0         +1300°C                                        0          +2400°F
                                                                   Temperature                                               Temperature
                                                                 -100                                                     -100                                 H
                                                                                                                                                             FX3U-4AD-PT
                                           • The photocoupler is used to insulate the analog input area from the PLC.
   Insulation method                       • The DC/DC converter is used to insulate the power supply from the analog inputs.
                                           • Channels are insulated from each other.
                                                                                                                                                                      -ADP
                                and mode.
                          *2.   Accuracy is not guaranteed for the temperature range of 0°C to 399°C(0°F to 799°F) of the thermocouple -B input
                                                                                                                                                                      -ADP
and for the temperature range of 0°F to 32°F of the PL II and WRe5-26 inputs.
                                                                                                                                                                 J
                                                                                                                                                             FX3U-4AD-PNK
                                                                                                                                                                      -ADP
                                                                                                                                                  A-45
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                     5 Manual Introduction (Types, Contents, and Obtainment)
Common Items                                                                                                   5.1 How to Use the Manuals
PLC
                                Analog products
                 Depending on the product type, the "Installation Manual" or the "User's Manual" is supplied with the
                 product.
                 For a detailed description, refer to the separate manual "User's Manual - Analog Control Edition" as
                 described below:
                     For installation and parts identification:
                       •Installation Manual Supplied
                        (For a detailed description of the programming method, refer to the
                        separate manual.)
Analog control
Voltage input Current input Voltage output Current output Temperature input
                       For each analog product, use this manual for details on wiring/setup details, example
                       programs, and troubleshooting methods.
A-46
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition       5 Manual Introduction (Types, Contents, and Obtainment)
Common Items                                                                             5.2 Description of Related Manuals
                                                                                                                                A
5.2      Description of Related Manuals
                                                                                                                                    Common Items
         The main manuals necessary for the use of analog products are described below.
         These manuals are classified into two groups: manuals necessary for the PLC main unit, and manuals
         necessary for analog products.
         The manuals specified as "supplied separately" are not supplied with the products. Other manuals are                   B
         supplied with the corresponding products.
                                                                                                                              FX3UC-4AD
                                                                                                                              FX3U-4AD
5.2.1    Analog control manuals
         The following manuals are common manuals that can be used for any of the FX3U/FX3UC/FX3G Series analog
         products.                                                                                                              C
                                                                                                                                    FX3U-4AD-ADP
                                                Supplied with
                               Document          product or
        Manual type                                                                    Description
                                number            supplied
                                                 separately
FX3G/FX3U/FX3UC Series PLC
FX3G/FX3U/FX3UC Series                       Supplied
                                                                This manual describes the details of the FX3G/ FX3U/
                                                                                                                                D
User’s Manual                JY997D16701     separately
                                                                                                                                    FX3G-2AD-BD
                                                                FX3UC Series PLC analog products.
- Analog Control Edition                     (This manual)
                                                                                                                                    FX3U-4DA
         Manual - Hardware Edition.
                                                Supplied with
                               Document          product or
        Manual type                                                                    Description
                                number            supplied
                                                 separately                                                                       F
FX3G Series PLC
                                                                                                                                    FX3U-4DA-ADP
                                                                This manual describes various items necessary for the
FX3G Series                                  Supplied with
                             JY997D33401                        hardware of the FX3G Series PLC main unit, such as
HARDWARE MANUAL                              product
                                                                specifications, wiring, and installation.
                                                                This manual describes various items necessary for the
FX3G Series User’s Manual
                             JY997D31301
                                             Supplied           FX3G Series PLC main unit and various items for the            G
- Hardware Edition                           separately         hardware, such as extension specifications, wiring, and
                                                                                                                                    FX3G-1DA-BD
                                                                installation.
FX3U Series PLC
                                                                This manual describes various items necessary for the
FX3U Series                                  Supplied with
                             JY997D18801                        hardware of the FX3U Series PLC main unit, such as
HARDWARE MANUAL                              product
                                                                specifications, wiring, and installation.                       H
                                                                This manual describes various items necessary for the
                                                                                                                              FX3U-4AD-PT
FX3U Series User’s Manual                    Supplied           FX3U Series PLC main unit and various items for the
                             JY997D16501
- Hardware Edition                           separately         hardware, such as extension specifications, wiring, and
                                                                installation.
                                                                                                                                       -ADP
FX3UC (D, DSS) Series                        Supplied with      excerpted from the FX3UC Series User's Manual (for
                             JY997D28601
HARDWARE MANUAL                              product            Hardware).
                                                                For details, refer to the FX3UC Series User's Manual (for
                                                                                                                                       -ADP
Hardware).
FX3UC-32MT-LT-2
                             JY997D31601
                                             Supplied with
                                                                This manual describes various items necessary for the
                                                                hardware of the FX3UC-32MT-LT-2 PLC main unit, such
                                                                                                                                  J
HARDWARE MANUAL                              product
                                                                                                                              FX3U-4AD-PNK
                                                                                                                   A-47
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition      5 Manual Introduction (Types, Contents, and Obtainment)
Common Items                                                                           5.2 Description of Related Manuals
                                               Supplied with
                                 Document       product or
        Manual type                                                                  Description
                                  number         supplied
                                                separately
                                                               Provides detailed information on the hardware, such as
FX3UC Series User’s Manual                   Supplied
                               JY997D28701                     the input/output specifications and detailed wiring,
- Hardware Edition                           separately
                                                               installation, and maintenance methods for the FX3UC PLC.
FX3G, FX3U, FX3UC Series PLC
FX3G/FX3U/FX3UC Series                                         This manual describes the basic and application
                                             Supplied
Programming Manual - Basic JY997D16601                         commands necessary for the FX3G/FX3U/FX3UC Series
                                             separately
& Applied Instruction Edition                                  PLC.
A-48
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition         5 Manual Introduction (Types, Contents, and Obtainment)
Common Items                                                                              5.2 Description of Related Manuals
                                                                                                                                 A
5.2.3     Manuals of analog units
                                                                                                                                     Common Items
          The manuals of various analog units are described below:
                                                 Supplied with
                                   Document       product or
          Manual type
                                    number         supplied
                                                                                        Description                              B
                                                  separately
                                                                                                                               FX3UC-4AD
                                                                                                                               FX3U-4AD
Analog input unit
                                                                 This manual describes the FX3G-2AD-BD analog input
FX3G-2AD-BD                                      Supplied with
                                JY997D33501                      expansion board hardware, such as specifications and
INSTALLATION MANUAL                              product
                                                                 installation.
                                                                                                                                     FX3U-4AD-ADP
INSTALLATION MANUAL                              product
                                                                 and installation, and also describes various programs.
                                                                 This manual describes the FX3U-4AD-ADP analog input
FX3U-4AD-ADP                                     Supplied with
                                JY997D13901                      special adapter hardware, such as specifications and
USER’S MANUAL                                    product
                                                                 installation.
                                                                                                                                     FX3G-2AD-BD
USER’S MANUAL                                    product
                                                                 and installation, and also describes various programs.
                                                                 This manual describes the FX2N-8AD analog input
FX2N-8AD                                         Supplied with
                                JY992D86001                      special function block hardware, such as specifications
USER’S MANUAL                                    product
                                                                 and installation, and also describes various programs.
                                                                                                                                     FX3U-4DA
                                                                 and installation, and also describes various programs.
                                                                 This manual describes the FX2N-2AD analog input
FX2N-2AD                                         Supplied with
                                JY992D74701                      special function block hardware, such as specifications
USER’S GUIDE                                     product
                                                                 and installation, and also describes various programs.
Analog output unit                                                                                                                 F
                                                                 This manual describes the FX3G-1DA-BD analog output
                                                                                                                                     FX3U-4DA-ADP
FX3G-1DA-BD                                      Supplied with
                                JY997D33601                      expansion board hardware, such as specifications and
INSTALLATION MANUAL                              product
                                                                 installation.
                                                                 This manual describes the FX3U-4DA analog output
FX3U-4DA                                         Supplied with
                                JY997D20801                      special function block hardware, such as specifications
INSTALLATION MANUAL                              product
                                                                 and installation.
                                                                                                                                G
                                                                 This manual describes the FX3U-4DA-ADP analog output
FX3U-4DA-ADP                                     Supplied with
                                                                                                                                     FX3G-1DA-BD
                                JY997D14001                      special adapter hardware, such as specifications and
USER’S MANUAL                                    product
                                                                 installation.
                                                                 This manual describes the FX2NC-4DA analog output
FX2NC-4DA                                        Supplied with
                                JY997D07601                      special function block hardware, such as specifications
USER’S MANUAL                                    product
                                                                 and installation, and also describes various programs.
                                                                 This manual describes the FX2N-4DA analog output
                                                                                                                                 H
FX2N-4DA                                         Supplied with
                                                                                                                               FX3U-4AD-PT
                                                                                                                    A-49
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition        5 Manual Introduction (Types, Contents, and Obtainment)
Common Items                                                                              5.2 Description of Related Manuals
                                                Supplied with
                                  Document       product or
          Manual type                                                                  Description
                                   number         supplied
                                                 separately
Temperature sensor unit
                                                                This manual describes the FX3U-4AD-PT-ADP platinum
FX3U-4AD-PT-ADP                                 Supplied with
                               JY997D14701                      resistance thermometer input special adapter hardware,
USER’S MANUAL                                   product
                                                                such as specifications and installation.
                                                                This manual describes the FX3U-4AD-PTW-ADP
FX3U-4AD-PTW-ADP                                Supplied with
                               JY997D29101                      platinum resistance thermometer input special adapter
USER’S MANUAL                                   product
                                                                hardware, such as specifications and installation.
                                                                This manual describes the FX3U-4AD-PNK-ADP
FX3U-4AD-PNK-ADP                                Supplied with
                               JY997D29201                      resistance thermometer input special adapter hardware,
USER’S MANUAL                                   product
                                                                such as specifications and installation.
                                                                This manual describes the FX3U-4AD-TC-ADP
FX3U-4AD-TC-ADP                                 Supplied with
                               JY997D14801                      thermocouple input special adapter hardware, such as
USER’S MANUAL                                   product
                                                                specifications and installation.
                                                                This manual describes the FX2N-4AD-PT platinum
FX2N-4AD-PT                                     Supplied with   resistance thermometer input special function block
                               JY992D65601
USER’S GUIDE                                    product         hardware, such as specifications and installation, and
                                                                also describes various programs.
                                                                This manual describes the FX2N-4AD-TC thermocouple
FX2N-4AD-TC                                     Supplied with   input special function block hardware, such as
                               JY992D65501
USER’S GUIDE                                    product         specifications and installation, and also describes various
                                                                programs.
                                                                This manual describes the FX2N-2LC temperature
FX2N-2LC                                        Supplied with
                               JY992D85601                      adjustment special function block hardware, such as
USER’S GUIDE                                    product
                                                                specifications and installation.
                                                                This manual describes the FX2N-2LC temperature
FX2N-2LC                                        Supplied        adjustment special function block hardware, such as
                               JY992D85801
USER’S MANUAL                                   separately      specifications and installation, and also describes various
                                                                programs.
A-50
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                6 Generic Names and Abbreviations in This Manual
Common Items                                                                                5.2 Description of Related Manuals
                                                                                                                                       Common Items
6.     Generic Names and Abbreviations in This Manual
      1. Main unit                                                                                                                 B
                                                                                                                                 FX3UC-4AD
                                                                                                                                 FX3U-4AD
              Abbreviation, generic name                                      Description
          PLC
                                             Generic name for the FX0, FX0S, FX1S, FX0N, FX1N, FX1, FX2(FX), FX2N, FX3G,
          FX Series PLC
                                             FX3U, FX1NC, FX2NC, and FX3UC Series PLC
          FX3G Series                        Generic name for the FX3G Series PLC
                                                                                                                                   C
                FX3G Series PLC or main unit Generic name for the FX3G Series PLC main unit
                                                                                                                                       FX3U-4AD-ADP
          FX3U Series                        Generic name for the FX3U Series PLC
                FX3U Series PLC or main unit Generic name for the FX3U Series PLC main unit
          FX3UC Series                       Generic name for the FX3UC Series PLC
                FX3UC Series PLC or
                main unit
                                             Generic name for the FX3UC Series PLC main unit
                                                                                                                                   D
                                                                                                                                       FX3G-2AD-BD
      2. Expansion board and special adapter
              Abbreviation, generic name                                      Description
          Expansion board                                                                                                           E
                                                                                                                                       FX3U-4DA
                                             Generic name for analog expansion board, communication expansion board,
          Expansion board                    special adapter connection expansion board and variable analog
                                             potentiometer expansion board.
          Analog expansion board             Generic name for 2AD-BD, 1DA-BD
                2AD-BD
                1DA-BD
                                             FX3G-2AD-BD
                                             FX3G-1DA-BD
                                                                                                                                     F
                                                                                                                                       FX3U-4DA-ADP
          Communication expansion board      Generic name for 232BD, 422BD, 485BD, and USBBD.
                232BD                        FX3U-232-BD, FX3G-232-BD, FX2N-232-BD, FX1N-232-BD
                422BD                        FX3U-422-BD, FX3G-422-BD, FX2N-422-BD, FX1N-422-BD
                485BD                        FX3U-485-BD, FX3G-485-BD, FX2N-485-BD, FX1N-485-BD
                USBBD                        FX3U-USB-BD                                                                          G
                                                                                                                                       FX3G-1DA-BD
          Variable analog potentiometer
                                             Generic name for 8AV-BD
          expansion board
                8AV-BD                       FX3G-8AV-BD
          Special adapter connection board
                                             Generic name for CNVBD.
          or connector conversion board
                CNVBD                        FX3U-CNV-BD, FX2N-CNV-BD, FX1N-CNV-BD
                                                                                                                                   H
                                                                                                                                 FX3U-4AD-PT
          Special adapter
                                             Generic name for High-speed input/output special adapter,
          Special adapter
                                             communication special adapter, and Analog special adapter.
                                                                                                                                          -ADP
                4HSX-ADP                     FX3U-4HSX-ADP
          Communication special adapter      Generic name for communication special adapter.
                                                                                                                                          -ADP
                                                                                                                      A-51
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                  6 Generic Names and Abbreviations in This Manual
Common Items                                                                                 5.2 Description of Related Manuals
       3. Extension unit
              Abbreviation, generic name                                       Description
          Voltage/current input
                                             Generic name for the FX2N Series extension unit, FX2NC Series extension unit,
                                             and FX0N Series extension unit.
          Extension unit                     The number of connectable units, however, depends on the type of the main
                                             unit. To check the number of connectable units, refer to the User’s Manual -
                                             Hardware Edition of the main unit to be used for your system.
                                             Generic name for FX2N Series input/output powered extension unit, FX2N Series
               FX2N Series extension unit    input/output extension block, FX2N Series special function unit, and FX2N Series
                                             special function block.
                                             Generic name for FX2NC Series input/output extension block and FX2NC Series
               FX2NC Series extension unit
                                             special function block.
                                             Generic name for FX0N Series input/output extension block and FX0N Series
               FX0N Series extension unit
                                             special function block.
                                             Generic name for FX3U Series special function block, FX3UC Series special
                                             function block, FX2N Series special function unit, FX2N Series special function
          Special function unit/block
                                             block, FX2NC Series special function block, and FX0N Series special function
                                             block.
               FX3U Series special
                                             FX3U-4AD, FX3U-4DA, FX3U-20SSC-H, FX3U-64CCL
               function block
               FX3UC Series special
                                             FX3UC-4AD
               function block
               FX2N Series special
                                             FX2N-10GM, FX2N-20GM, FX2N-1RM-E-SET, FX2N-1RM-SET
               function unit
                                             FX2N-232IF, FX2N-16CCL-M, FX2N-32CCL, FX2N-32ASI-M, FX2N-2AD,
                                             FX2N-4AD, FX2N-8AD, FX2N-4AD-PT, FX2N-4AD-TC, FX2N-2LC, FX2N-2DA,
               FX2N Series special           FX2N-4DA, FX2N-5A, FX2N-1HC, FX2N-1PG-E, FX2N-1PG, FX2N-10PG
               function block                The number of connectable units, however, depends on the type of main unit.
                                             To check the number of connectable units, refer to the User’s Manual - Hard-
                                             ware Edition of the main unit to be used for your system.
               FX2NC Series special
                                             FX2NC-4AD, FX2NC-4DA, FX2NC-1HC
               function block
               FX0N Series special
                                             FX0N-3A
               function block
A-52
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition             6 Generic Names and Abbreviations in This Manual
Common Items                                                                              5.2 Description of Related Manuals
                                                                                                                                 A
      4. Peripheral unit
                                                                                                                                     Common Items
              Abbreviation, generic name                                   Description
          Peripheral unit
                                           Generic name for programming software, handy programming panel,
          Peripheral unit
                                           and display units.
          Programming tool
                                                                                                                                 B
                                                                                                                               FX3UC-4AD
                                                                                                                               FX3U-4AD
          Programming tool                 Generic name for programming software, and handy programming panel.
          Programming software             Generic name for Programming software.
                                           Generic name for SW D5C-GPPW-J and SW D5C-GPPW-E programming
               GX Developer
                                           software packages.
      5. Manual
                                                                                                                                 C
                                                                                                                                     FX3U-4AD-ADP
              Abbreviation, generic name                                   Description
          FX3G hardware manual             FX3G Series User's Manual - Hardware Edition
          FX3U hardware manual             FX3U Series User's Manual - Hardware Edition
          FX3UC hardware manual            FX3UC Series User's Manual - Hardware Edition
                                           FX3G/FX3U/FX3UC Series Programming Manual - Basic and Applied Instruction             D
          Programming manual
                                           Edition
                                                                                                                                     FX3G-2AD-BD
                                                                                                                                  E
                                                                                                                                     FX3U-4DA
                                                                                                                                   F
                                                                                                                                     FX3U-4DA-ADP
                                                                                                                                G
FX3G-1DA-BD
                                                                                                                                 H
                                                                                                                               FX3U-4AD-PT
                                                                                                                                        -ADP
                                                                                                                                         I
                                                                                                                               FX3U-4AD-PTW
                                                                                                                                        -ADP
                                                                                                                                   J
                                                                                                                               FX3U-4AD-PNK
                                                                                                                                        -ADP
                                                                                                                    A-53
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition   6 Generic Names and Abbreviations in This Manual
Common Items                                                                 5.2 Description of Related Manuals
MEMO
A-54
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)
                                                                                                                                       Common Items
                                                                                                                                   B
                                                                                                                                 FX3UC-4AD
                                                                                                                                 FX3U-4AD
         FX3G/FX3U/FX3UC Series Programmable
         Controllers                                                                                                               C
                                                                                                                                       FX3U-4AD-ADP
         User's Manual [Analog Control Edition]
         FX3U-4AD (4-channel Analog Input)
                                                                                                                                   D
         FX3UC-4AD (4-channel Analog Input)
                                                                                                                                       FX3G-2AD-BD
                                                                                                                                    E
                                                                                                                                       FX3U-4DA
                                                                                                                                     F
                                                                                                                                       FX3U-4DA-ADP
                                                                                                                                  G
FX3G-1DA-BD
                                                                                                                                   H
                                                                                                                                 FX3U-4AD-PT
         Foreword
                                                                                                                                          -ADP
         This manual describes the specifications, wiring, and operation methods for the FX3U-4AD/FX3UC-4AD
         special extension block (4-channel analog input) and should be read and understood before attempting to
         install or use the unit.                                                                                                          I
                                                                                                                                 FX3U-4AD-PTW
         Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
         it to the end user.
                                                                                                                                          -ADP
           This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
           licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
           rights which may occur as a result of using the contents noted in this manual.                                            J
                                                                                                                                 FX3U-4AD-PNK
                                                                                                                         B-1
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)
B-2
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                  1 Outline
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                                     1.1 Outline of Functions
                                                                                                                                                 Common Items
1.     Outline
         This chapter outlines the FX3U-4AD/FX3UC-4AD.                                                                                       B
         For common descriptions of the FX3U-4AD and FX3UC-4AD, these model names are referred to as the 4AD.
                                                                                                                                           FX3UC-4AD
                                                                                                                                           FX3U-4AD
1.1      Outline of Functions
         The FX3U-4AD is an analog special function block which is connectable with the FX3G, FX3U and FX3UC
         Series PLC used to capture 4-ch voltage/current data. The FX3UC-4AD cannot be connected to the FX3G/
                                                                                                                                             C
                                                                                                                                                 FX3U-4AD-ADP
         FX3U Series PLC.
         1) Up to 8*1 units can be connected to the FX3G/FX3U/FX3UC Series PLC.
            (including the other special function blocks).
         2) Either "voltage input" or "current input" can be specified for each channel.
         3) The A/D conversion values will be stored in the 4AD buffer memory (BFM).                                                         D
                                                                                                                                                 FX3G-2AD-BD
         4) Set the digital filter to read out stable A/D conversion values.
         5) For each channel, up to 1,700 A/D conversion values can be stored as history data.
                                                                                                                                                 FX3U-4DA
                                Up to 8 units*1 connect to the FX3G/FX3U/FX3UC Series PLC
                                      (including other types of special function blocks)
                                                                                            ••••••   Number of connectable units
                                                                                                                                                 FX3U-4DA-ADP
                                                   •••••••••
                                                                                                                                                 FX3G-1DA-BD
                                                                                                     For a detailed description of
                                                                                            ••••••   analog data reading programs,
                                                                                                     refer to Chapter 4, 6, and 7.
                                                                                            ••••••
                                                                                                     For a detailed description of
                                                                                                     the buffer memory, refer to
                                                                                                                                             H
                 Program                                           Buffer memory
                                                                                                                                           FX3U-4AD-PT
                                                                                            ••••••
                                                                                                     or to directly specify the BFM,
          • BFM direct
                                                                                                                                                    -ADP
        Refer to the system configuration shown in the FX3G/FX3U/FX3UC User's Manual - Hardware Edition to check the                                 I
        number of connectable units and to configure the entire system.
                                                                                                                                           FX3U-4AD-PTW
*2. This function is just available for FX3U and FX3UC PLCs.
                                                                                                                                               J
                                                                                                                                           FX3U-4AD-PNK
                                                                                                                                                    -ADP
                                                                                                                                B-3
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                        1 Outline
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                      1.2 Setup Procedure Before Starting Operation
FX3U-4AD/FX3UC-4AD
Refer to Chapter 1.
                               Wiring                                     Wiring:
                                                                          • Power supply line
                                                                          • Analog input line
                                         Refer to Chapter 4.
Refer to Chapter 7.
B-4
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                     1 Outline
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                        1.3 Connectable PLC and Version Numbers
                                                                                                                                               A
1.3      Connectable PLC and Version Numbers
                                                                                                                                                   Common Items
         FX3U-4AD is compatible with the following PLC.
                                                                                                                                             FX3UC-4AD
                                                                                                                                             FX3U-4AD
          FX3UC Series PLC                        Ver. 1.30 or later                  August 2004 and later
          FX3G Series PLC                         Ver. 1.00 or later                  from first product
                                                                                                                                                   FX3U-4AD-ADP
          FX3UC Series PLC                        Ver. 1.30 or later                  August 2004 and later
      1. Version check
         Special data register D8001 contains information for determining the PLC version number.                                              D
                                                                                                                                                   FX3G-2AD-BD
                             D8001            2       4       1     0       0
                        PLC type and
                       version number                                     Version data (Example: Ver. 1.00)
                                                                    (
                                                       PLC type Example: 24 = FX3U and FX3UC series
                                                                         26 = FX3G series                      )                                E
                                                                                                                                                   FX3U-4DA
      2. How to look at the manufacturer's serial number
         The year and month of product production can be seen from the manufacturer's serial number "SERIAL"
         indicated on the label adhered to the right side of the product.
                                                                                                                                                 F
                                                                                                                                                   FX3U-4DA-ADP
                                              Example:
                                              FX3U-48MR/ES(production number : 570001)
                                                   MODEL           FX3U-48MR/ES
                                                             100-240VAC 50/60Hz 40W
                                                       OUT:30VDC/240VAC 2A(COSφ=1)                                                            G
                                                                                                                                                   FX3G-1DA-BD
                                                   SERIAL                    570001
                                                               5     7      0     0     0     1                                                H
                                                                                                                                             FX3U-4AD-PT
                                                                                     Control number
                                                                        Month (Example: 7 = July), 1 to 9 = January to September,
                                                                        X = October, Y = November, Z = December
                                                                                                                                                      -ADP
                                                                                                                                                       I
                                                                                                                                             FX3U-4AD-PTW
                                                                                                                                                      -ADP
                                                                                                                                                 J
                                                                                                                                             FX3U-4AD-PNK
                                                                                                                                                      -ADP
                                                                                                                                   B-5
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                      1 Outline
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                              1.4 Version Number of Compatible Programming Tools
         FX3U-4AD
                 Software           Compatible version number                       Remarks
          GX Developer                   Ver. SW8 P or later
                                            (Ver. 8.13P)          When selecting the model, select FX3U(C)*1.
          • SW D5C-GPPW-J
          • SW D5C-GPPW-E               (Ver. 8.72A or later)     When selecting the model, select FX3G.
         FX3UC-4AD
                 Software           Compatible version number                       Remarks
          GX Developer
                                         Ver. SW8 P or later
          • SW D5C-GPPW-J
                                            (Ver. 8.13P)          When selecting the model, select FX3U(C)*1.
          • SW D5C-GPPW-E
         If a programming tool with the wrong version number is used, some instructions and devices cannot be used.
          *1.   For Ver. 8.13P to 8.24A of GX Developer, select FX3UC for the PLC type.
B-6
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                          2 Specifications
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                                    2.1 Generic Specifications
                                                                                                                                                  Common Items
2.     Specifications
         This chapter describes the general, power supply, and performance specifications for the 4AD.                                        B
                                                                                                                                            FX3UC-4AD
                                                                                                                                            FX3U-4AD
2.1      Generic Specifications
Item Specifications C
                                                                                                                                                  FX3U-4AD-ADP
          Ambient            0 to 55°C (32 to 131°F) when operating
          temperature        -25 to 75°C (-13 to 167°F) when stored
          Relative
                             5 to 95%RH (no condensation) when operating
          humidity
                                                       Frequency        Acceleration       Half amplitude                                     D
                                                          (Hz)             (m/s2)               (mm)
                                                                                                                                                  FX3G-2AD-BD
                                                                                                            10 times of testing in
          Vibration                                      10 - 57             -                 0.035        each direction (X-, Y-,
                             DIN Rail Mounting
          resistance                                     57 - 150           4.9                    -        and Z-axis directions)
                                                                                                            (Total: 80 min, each)
                                                         10 - 57             -                 0.075
                             Direct Mounting*1
          Shock
                                                         57 - 150           9.8                    -
                                                                                                                                               E
                             147   m/s2   Acceleration, Action time: 11ms, 3 times by half-sine pulse in each direction X, Y, and Z
                                                                                                                                                  FX3U-4DA
          resistance
          Noise              Using noise simulator of:
          resistance         Noise voltage: 1,000Vp-p / Noise width: 1µs / Rise: 1ns / Cycle: 30 to 100Hz
          Dielectric
          withstand
          voltage
                             500 V AC, for 1 min
                                                                     Between all terminals and ground terminal
                                                                                                                                                F
                                                                                                                                                  FX3U-4DA-ADP
          Insulation         5MΩ or more using 500V DC
          resistance         insulation resistance meter
                             Class D grounding (grounding resistance: 100 Ω or less)
          Grounding
                             <Common grounding with a heavy electrical system is not allowed.>*2
          Working
                             Free from corrosive or flammable gas and excessive conductive dust                                              G
          atmosphere
                                                                                                                                                  FX3G-1DA-BD
          Working
                             < 2000m*3
          altitude
                                                                                                                                                J
                                                                                                                                            FX3U-4AD-PNK
                                                                                                                                                     -ADP
                                                                                                                                 B-7
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                       2 Specifications
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                            2.2 Power Supply Specifications
FX3U-4AD
                   Item                                                  Specifications
          A/D conversion      24V DC ±10%, 90mA
          circuit drive power (It is necessary to supply 24V DC from the terminal block.)
                                5V DC, 110mA
          CPU drive power       (Since the internal power is supplied from the main unit, it is not necessary to supply power
                                externally.)
FX3UC-4AD
                   Item                                                  Specifications
          A/D conversion      24V DC ±10%, 80mA
          circuit drive power (It is necessary to supply 24V DC from the power connector.)
                                5V DC, 100mA
          CPU drive power
                                (Since the internal power is supplied from the main unit, it is not necessary to supply the power.)
                                                                         Specifications
                   Item
                                                 Voltage input                                     Current input
                                               -10V to +10V DC                       -20mA to +20mA DC, 4mA to 20mA DC
          Analog input range
                                           (Input resistance: 200kΩ)                        (Input resistance: 250Ω)
          Offset*1                               -10V to +9V*2                                  -20mA to +17mA*3
          Gain*1                                 -9V to +10V*2                                  -17mA to +30mA*3
          Absolute maximum
                                                     ±15V                                              ±30mA
          input
          Digital output                    With sign, 16bits, binary                        With sign, 15bits, binary
                                            0.32mV (20V / 64,000)                            1.25µA (40mA / 32,000)
          Resolution*4                      2.5mV (20V × 1/8000)                             5.00µA (40mA × 1/8000)
                                                                                 • Ambient temperature: 25°C±5°C
                                 • Ambient temperature: 25°C±5°C                   ±0.5% (±200µA) for 40mA full scale
                                   ±0.3% (±60mV) for 20V full scale                Same accuracy (±200µA) for 4mA to 20mA input
          Overall accuracy
                                 • Ambient temperature: 0°C to 55°C              • Ambient temperature: 0°C to 55°C
                                   ±0.5% (±100mV) for 20V full scale               ±1% (±400µA) for 40mV full scale
                                                                                   Same accuracy (±400µA) for 4mA to 20mA input
          Time required for                                  500µs × number of selected channels
          A/D conversion               (If 1 or more channels use the digital filter(s): 5ms × number of selected channels)
                                 • The photocoupler is used to insulate the analog input area from the PLC.
          Insulation method      • The DC/DC converter is used to insulate the analog input area from the power supply unit.
                                 • Channels are not insulated from each other.
          Number of I/O
                                 8 points (Taken from either the input or output points of the PLC.)
          points occupied
          *1.      Adjustment of the offset or gain value will not affect the resolution. In the direct indication mode,
                   however, the offset/gain cannot be adjusted.
          *2.      The offset and the gain should satisfy the following condition:
                   1V ≤ (Gain - Offset)
          *3.      The offset and the gain should satisfy the following condition:
                   3 mA ≤ (Gain - Offset) ≤ 30 mA
          *4.      If 1 or more channels use the digital filter(s), the time required for A/D conversion will be
                   "5 ms × number of selected channels."
B-8
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                               2 Specifications
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                                      2.4 Input Mode (Characteristics) BFM #0
                                                                                                                                                                    A
2.4      Input Mode (Characteristics) BFM #0
                                                                                                                                                                        Common Items
         For the 4AD, there are two types of input characteristics: voltage (-10 to +10V) and current (4 to 20mA, -20 to
         +20mA) input characteristics. The input characteristics depend on the set input mode as described below. For
         each input range, there are 3 input modes.
                                                                                                                                                                    B
      1. Voltage input characteristics [-10 to +10V] (Input mode: 0 to 2)
                                                                                                                                                                  FX3UC-4AD
                                                                                                                                                                  FX3U-4AD
                                                                                                              Set input mode: 2
          Set input mode: 0                                 Set input mode: 1
                                                                                                              Input type: Voltage input
          Input type: Voltage input                         Input type: Voltage input
                                                                                                                         (analog value direct indication)
          Analog input range: -10 to +10V                   Analog input range: -10 to +10V
                                                                                                              Analog input range: -10 to +10V
          Digital output range: -32000 to +32000            Digital output range: -4000 to +4000
                                                                                                              Digital output range: -10000 to +10000
          Offset/gain adjustment: Possible                  Offset/gain adjustment: Possible
                                                                                                              Offset/gain adjustment: Impossible                    C
                                                                                                                                                                        FX3U-4AD-ADP
                             Digital value                                   Digital value                                          Digital value
                          +32640                                             +4080                                                +10200
                          +32000                                             +4000                                                +10000
                                                   +10.2V
                                                                                                                                                         +10.2V
                                                                                                     +10.2V
           Input                                            Input                                               Input
           voltage -10V          0                          voltage -10V            0                           voltage -10V            0                           D
                                          +10V                                               +10V                                               +10V
                                                                                                                                                                        FX3G-2AD-BD
                                                                                                                         -10.2V
                 -10.2V
-10.2V
                                                                                                                                                                        FX3U-4DA
                                                                                                              Set input mode: 5
          Set input mode: 3                                 Set input mode: 4
                                                                                                              Input type: Current input
          Input type: Current input                         Input type: Current input
                                                                                                                         (analog value direct indication)
          Analog input range: 4 to 20mA                     Analog input range: 4 to 20 mA
                                                                                                              Analog input range: 4 to 20 mA
          Digital output range: 0 to 16000                  Digital output range: 0 to 4000
                                                                                                              Digital output range: 4000 to 20000
          Offset/gain adjustment: Possible                  Offset/gain adjustment: Possible
                                                                                                              Offset/gain adjustment: Impossible
                                                                                                                                                                      F
                                                                                                                                                                        FX3U-4DA-ADP
           Digital value                                     Digital value                                      Digital value
           16400                                             4100                                               20400
                                                                                                                                                                   G
                                               20.4 mA
20.4 mA
20.4 mA
                                                                                                                                                                        FX3G-1DA-BD
                                                                                                                 4000
                                                                                                                                                                    H
                                                                                                                                                                  FX3U-4AD-PT
                                                                                                                                                                           -ADP
                                                                                                                                                                            I
                                                                                                                                                                  FX3U-4AD-PTW
                                                                                                                                                                           -ADP
                                                                                                                                                                      J
                                                                                                                                                                  FX3U-4AD-PNK
                                                                                                                                                                           -ADP
                                                                                                                                                         B-9
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                     2 Specifications
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                             2.4 Input Mode (Characteristics) BFM #0
+20.4mA
                                                                                                                                            +20.4mA
           Current                             +20.4mA    Current                                      Current
           Input -20mA            0                       Input -20mA          0                       Input -20mA             0
                                       +20mA                                         +20mA                                           +20mA
-20.4mA
                                                                                                              -20.4mA
                 -20.4mA
B-10
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                 3 Wiring
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                    2.4 Input Mode (Characteristics) BFM #0
                                                                                                                                               Common Items
3.     Wiring
         This chapter describes the 4AD wiring.                                                                                            B
         Observe the following cautions when wiring the 4AD.
                                                                                                                                         FX3UC-4AD
                                                                                                                                         FX3U-4AD
          WIRING PRECAUTIONS
          • Make sure to cut off all phases of the power supply externally before attempting wiring work.
            Failure to do so may cause electric shock or damages to the product.                                                           C
                                                                                                                                               FX3U-4AD-ADP
          WIRING PRECAUTIONS
          • Connect the DC power supply wiring to the dedicated terminals described in this manual.
            If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will be
            burnt out.
                                                                                                                                           D
                                                                                                                                               FX3G-2AD-BD
          • Do not wire vacant terminals externally.
            Doing so may damage the product.
          • Perform class D grounding (grounding resistance: 100Ω or less) to the grounding terminal on the main unit.
            Do not use common grounding with heavy electrical systems.
          • When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
            Failure to do so may cause fire, equipment failures or malfunctions.                                                            E
          • Make sure to observe the following precautions in order to prevent malfunctions under the influence of noise:
                                                                                                                                               FX3U-4DA
            - Do not bundle the power line or twisted shielded cable together with or lay it close to the main circuit, high-
                voltage line, or load line.
                Otherwise, noise disturbance and/or surge induction are likely to take place. As a guideline, lay the control line
                at least 100mm (3.94") or more away from the main circuit, high-voltage line, or load line.
            - Ground the shield of the analog input/output cable at one point on the signal receiving side.
                However, do not use common grounding with heavy electrical systems.                                                          F
          • Make sure to properly wire to the European terminal board in accordance with the following precautions.
                                                                                                                                               FX3U-4DA-ADP
            Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product.
            - The disposal size of the cable end should be 9 mm (0.35").
            - Tightening torque should be between 0.22 to 0.25 N•m.
            - Twist the end of strand wire and make sure there are no loose wires.
            - Do not solder-plate the electric wire ends.
            - Do not connect more than the specified number of wires or electric wires of unspecified size.                               G
            - Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
                                                                                                                                               FX3G-1DA-BD
          • Make sure to properly wire the terminal block in accordance with the following precautions.
            Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product.
            - The disposal size of the cable end should follow the dimensions described in this manual.
            - Tightening torque should be between 0.5 and 0.8 N•m.
                                                                                                                                           H
                                                                                                                                         FX3U-4AD-PT
                                                                                                                                                  -ADP
                                                                                                                                                   I
                                                                                                                                         FX3U-4AD-PTW
                                                                                                                                                  -ADP
                                                                                                                                             J
                                                                                                                                         FX3U-4AD-PNK
                                                                                                                                                  -ADP
                                                                                                                             B-11
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                 3 Wiring
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                        3.1 Terminal Layout
                                                             Signal             Application
                                                              24+
                                                                          24V DC power supply
                                                              24-
                                                                          Ground terminal
                                                              V+
                                                              VI-         Channel-1 analog input
                                                              I+
                                                              FG
                                                              V+          Channel-2 analog input
                                                              VI-
                                                              I+
                                                              FG
                                                              V+          Channel-3 analog input
                                                              VI-
                                                              I+
                                                              FG
                                                              V+          Channel-4 analog input
                                                              VI-
                                                              I+
FX3UC-4AD
PW
                                                        I1+
                                            I1+
                                                        SLD
                                             SLD
A/D
                                                        V2+
                                            V2+
                                                        I2+
                                            I2+
                                                       COM2
                                                        SLD
                                                         •
                                            •
                                                        V3+
                                            V3+
                                                        I3+
                                            I3+
                                                        SLD
                                             SLD
                                                        V4+
                                            V4+
                                                        I4+
                                            I4+
                                                        SLD
                                            SLD
Ground terminal
B-12
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                    3 Wiring
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                      3.2 Cable and Terminal Tightening Torque
                                                                                                                                              A
3.2      Cable and Terminal Tightening Torque
                                                                                                                                                  Common Items
3.2.1    Power cable (FX3UC-4AD)
         The power crossover cable (type "C" shown in the following table) is supplied with the FX3UC-4AD.                                    B
         To connect the power cable, refer to the User's Manual - Hardware Edition of the PLC main unit.
                                                                                                                                            FX3UC-4AD
                                                                                                                                            FX3U-4AD
         There are 3 types of power cables as shown in the following table. Types "A" and "B" are supplied with the
         main unit, and type "C" is supplied with the input extension blocks or the special function blocks for FX3UC
         Series.
           Type                Application                      Model             Length              Cable supplied with
                                                                                                                                                  FX3U-4AD-ADP
                                                                                             FX3UC Series PLC main unit
                    Input power cable for input                                      1m
            B                                              FX2NC-100BPCB
                    extension block                                                (3’ 3")
                                                                                             • Input extension block for FX2NC
                    Input power crossover cable for                                 0.1m       Series
            C                                              FX2NC-10BPCB1
                    input extension block                                          (0’ 3")   • Special function block for FX3UC/
                                                                                               FX2NC Series
                                                                                                                                              D
                                                                                                                                                  FX3G-2AD-BD
         The crossover cable (type "C") can skip up to 4 16-point output blocks to connect units.
         If more blocks should be skipped to supply power to an input block, use cable type "B".
                                                                                                                                                  FX3U-4DA
                                                                             Specifications/model
          Wire size                                       AWG24 (0.2mm2)
          Crimp-style terminal                            50083-8014 (manufactured by Molex Japan Co., Ltd.)
                          For main unit                   51030-0330 (manufactured by Molex Japan Co., Ltd.)
          Housing
                          For input extension block       51030-0230 (manufactured by Molex Japan Co., Ltd.)                                    F
                                                                                                                                                  FX3U-4DA-ADP
         Supply the 24V DC power to FX3UC-4AD via the power supply connector.
                                                                                                                                                  FX3G-1DA-BD
         Tighten the terminal to a torque of 0.5 N•m to 0.8 N•m.
         • When one wire is connected to one terminal
                                     φ3.2 (0.13")                    Terminal Crimp
                                                                     screw
            6.2 mm (0.24")
                or less
                                                                              terminal
                                                                                                                                              H
                                                                                                                                            FX3U-4AD-PT
                                     φ3.2 (0.13")
            6.2 mm (0.24")                                        Terminal
                                                                     ’[Žq
                or less
                                                                                                                                                     -ADP
                                      φ3.2 (0.13")
            6.2 mm (0.24")                                           Terminal Crimp
                or less                                              screw    terminal
                                          6.3 mm(0.25")
                                                                                                                                                     -ADP
                                          or more
                                      φ3.2 (0.13")                                                                                              J
            6.2 mm (0.24")                                        Terminal
                                                                                                                                            FX3U-4AD-PNK
                or less
                                          6.3 mm(0.25")
                                          or more
                                                                                                                                                     -ADP
                                                                                                                                B-13
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                3 Wiring
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                 3.2 Cable and Terminal Tightening Torque
        1. Cable
          Applicable cable and tightening torque
                          Wire size (stranded/     Tightening
                                                                                         Termination
                              single-wire)           torque
                         0.3mm2 to 0.5mm2                        • To connect a stranded cable, peel the cover off the cable
           Single wire                                             and then twist the core before connection.
                         (AWG22 to 20)
                                                                 • To connect a single-wire cable, peel the cover off the
           Double wire   0.3mm2(AWG22)                             cable before connection.
                        0.3mm2 to 0.5mm2           0.22N•m to    • Rod terminal with insulation sleeve
           Rod terminal (AWG22 to 20)               0.25N•m        (recommended terminal)
           with         (Refer to the external                     AI 0.5-8WH : Manufactured by Phoenix Contact
           insulation   view of rod terminal                     • Caulking tool
           sleeve       shown in the following                     CRIMPFOX ZA 3 : Manufactured by Phoenix Contact
                        figure.)                                   (or CRIMPFOX UD 6 : Manufactured by Phoenix Contact)
        3. Tool
          • To tighten terminals, use a purchased small-sized screwdriver whose head is straight and is not widened
            as shown in the right figure.
             Note:
             If the diameter of screwdriver grip is too small, tightening torque will not
                                                                                                                       The head
             be able to be achieved. Use the following recommended screwdriver or                                      should be
             an appropriate replacement (grip diameter: approximately 25mm).                                           straight.
                         Manufacturer                           Model
             Phoenix Contact                                SZS 0.4×2.5                       0.4mm                   2.5mm
                                                                                              (0.01")                 (0.09")
B-14
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                 3 Wiring
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                       3.3 Examples of Power Supply Circuit
                                                                                                                                           A
3.3      Examples of Power Supply Circuit
                                                                                                                                               Common Items
3.3.1    FX3U-4AD
         Below are shown examples of circuits for using the 24V DC service power supply of the FX3G/FX3U Series                            B
         PLC.
                                                                                                                                         FX3UC-4AD
                                                                                                                                         FX3U-4AD
         1) Sink input [- common] wiring
                                     AC power
                                    100 to 240 V
                                                                                                                                           C
                                                                                                                                               FX3U-4AD-ADP
                         Class-D
                        grounding
                                    L          N       S/S    0V    24V          24+   24-
                                                                                                                                           D
                                                                                                                                               FX3G-2AD-BD
                                                                                             +15V
                                                                                                                                               FX3U-4DA
         2) Source input [+ common] wiring
                                     AC power
                                                                                                                                             F
                                                                                                                                               FX3U-4DA-ADP
                                    100 to 240 V
                         Class-D
                        grounding                                                                                                         G
                                                                                                                                               FX3G-1DA-BD
                                    L         N        S/S    0V   24V           24+   24-
+15V
FX3U-4AD
                             Connect the "S/S" terminal of the main unit to the "0V" terminal.
                                                                                                                                                  -ADP
                                                                                                                                                   I
                                                                                                                                         FX3U-4AD-PTW
                                                                                                                                                  -ADP
                                                                                                                                             J
                                                                                                                                         FX3U-4AD-PNK
                                                                                                                                                  -ADP
                                                                                                                             B-15
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                           3 Wiring
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                                3.3 Examples of Power Supply Circuit
3.3.2 FX3UC-4AD
+15V +15V
                                                                    -15V                                                             -15V
                                                                                             Power
                                                                  Power           Power    crossover                               Power
                                                                  crossover                                                      crossover
                                                                  connector      connector connector                             connector
                    Power connector
                     24- 24+                    24- 24+      24- 24+              24- 24+     24- 24+              24- 24+       24- 24+
                                         Power                                                         Power
                 Black Red     Green     connector        Black         Red   Black      Red           connector
                                             Black      Red                               Black       Red Black            Red
        24V DC
                                  FX2NC-100BPCB
                                    Power cable*1
          *1.     The FX3UC-          MT/D and FX3UC-32MT-LT(-2) are supplied together with power cable.
          *2.     The FX2NC-       EX-DS and FX2NC-16EX-T-DS do not have a power connector, and receive power
                  from the input connector.
         • Ground the "      " terminal and "    " terminal to the Class - D grounding line (100 Ω or less) together
           with the ground terminal of the main unit.
         • To perform crossover wiring to connect the power line from FX3UC-4AD to a succeeding extension block,
           remove the resin cover from the power crossover connector using nippers.
         • For the timing of power-on/off when using an external power supply, see the following manual of the
           connected PLC.
                                                   → Refer to the FX3G Series User’s Manual - Hardware Edition.
                                                   → Refer to the FX3U Series User’s Manual - Hardware Edition.
                                                  → Refer to the FX3UC Series User’s Manual - Hardware Edition.
B-16
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                3 Wiring
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                                     3.4 Analog Input Line
                                                                                                                                          A
3.4      Analog Input Line
                                                                                                                                              Common Items
         The analog input type, "voltage input "or "current input", can be selected for each channel.
3.4.1    FX3U-4AD
                                                                                                                                          B
                                                                                                                                        FX3UC-4AD
                                                                                                                                        FX3U-4AD
          External power supply                                          FX3U-4AD
                  wiring
                                                      24+                                 +15V
                         24V DC
                               *1                     24-                                  -15V
                                                                                                                                          C
                      Class-D grounding
                                                 *2
                                                                                                                                              FX3U-4AD-ADP
                If current input is
                     selected
                                                ch                          6.8kΩ
                                      *3                                                   ch
                                                      V+
                                           *4                     250Ω
                                                      I+                                                                                  D
                                                      VI-
                                                                                                                                              FX3G-2AD-BD
                                                                            200kΩ
                                                      FG
                If voltage input is         *2
                     selected
                                                ch
                                      *3                                    6.8kΩ          ch
                                                      V+
                                           *5
                                                      I+
                                                                  250Ω                                                                     E
                                                                                                                                              FX3U-4DA
                                                      VI-
                                                                            200kΩ
                                                      FG
                                            *2
                                                                                                                                              FX3U-4DA-ADP
          *1.        For FX3G/FX3U Series PLC (AC power type), the 24V DC service power supply is also available.
          *2.        The [FG] terminal and the [            ] terminal are connected internally.
                     There is no “FG” terminal for ch1. When using ch1, connect directly to the [        ] terminal.
          *3.        Use a 2-core twisted shield wire for analog input line, and separate it from other power lines or
                     inductive lines.
                                                                                                                                         G
                                                                                                                                              FX3G-1DA-BD
          *4.        For the current input, short-circuit the [V+] terminal and the [I+] terminal.
          *5.        If there is voltage ripple in the input voltage or there is noise in the external wiring, connect a capacitor
                     of approximately 0.1 to 0.47µF 25 V.
                                                                                                                                          H
                                                                                                                                        FX3U-4AD-PT
                                                                                                                                                 -ADP
                                                                                                                                                  I
                                                                                                                                        FX3U-4AD-PTW
                                                                                                                                                 -ADP
                                                                                                                                            J
                                                                                                                                        FX3U-4AD-PNK
                                                                                                                                                 -ADP
                                                                                                                            B-17
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                            3 Wiring
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                                     3.5 Grounding
3.4.2 FX3UC-4AD
*4 •
                                  Class-D
                                 grounding
          *1.     Use the 2-core shielded twisted pair cable for the analog input lines, and separate the analog input
                  lines from the other motive power lines or inductive lines.
          *2.     To use the current input, be sure to short circuit the line between the V    + terminal and the I
                  + terminal ( : channel number).
          *3.     The SLD and "            " terminals are connected to each other inside.
          *4.     Do not connect any lines to the "•" terminal.
3.5      Grounding
         Grounding should be performed as stated below.
         • The grounding resistance should be 100Ω or less.
         • Independent grounding should be performed for best results.
           When independent grounding is not performed, perform "shared grounding" as shown in the following
           figure.
                                  → For details, refer to the User’s Manual - Hardware Edition of each Series.
• The PLC grounding point should be close, and all grounding wires should be as short as possible.
B-18
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                          4 Analog Input
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                                 4.1 Analog Input Procedures
                                                                                                                                                Common Items
4.     Analog Input
         This chapter describes the minimum programming necessary to readout the 4AD analog data.                                           B
         Follow the procedure below to confirm that the analog data can be properly read out.
                                                                                                                                          FX3UC-4AD
                                                                                                                                          FX3U-4AD
4.1      Analog Input Procedures
                                                                                                                                                FX3U-4AD-ADP
         Unit numbers from 0 to 7 will be assigned to the special function units/blocks starting from the left.
         When units/blocks are connected to the FX3UC-32MT-LT(-2) PLC, unit numbers from 1 to 7 are
         assigned. Check the unit number assigned to the 4AD.
                                                      Unit
                                                    number: 0
                                                                     Unit
                                                                   number: 1
                                                                                                    Unit
                                                                                                  number: 2                                 D
                                                                                                                                                FX3G-2AD-BD
                      Main unit    Input/output      Special        Special       Input/output     Special
                    (FX3U Series    extension     function block function block    extension     function unit
                       PLC)           block                                          block
                                                                                                                                                FX3U-4DA
   2     Input mode (BFM #0) setting
         Depending on the analog signal generator to be connected, set the input mode (BFM #0) for each
         channel.                                                                                                                             F
                                                                                                                                                FX3U-4DA-ADP
         Use hexadecimal numbers for input mode setting. Set the corresponding channel digit to the input
         mode setting value specified in the following table:
                                                   H
                                                  ch4                      ch1                                                             G
                                                  ch3                      ch2
                                                                                                                                                FX3G-1DA-BD
          Setting                                                Analog input
                                   Input mode                                       Digital output range
           value                                                    range
             0      Voltage input mode                            -10V to +10V        -32000 to +32000
             1      Voltage input mode                            -10V to +10V          -4000 to +4000                                      H
                    Voltage input
                                                                                                                                          FX3U-4AD-PT
             5
                    Current input mode
                    Analog value direct indication mode
                                                                 4mA to 20mA            4000 to 20000                                               I
                                                                                                                                          FX3U-4AD-PTW
                           → For a detailed description of the standard input characteristics, refer to Section 2.4.
                              → For a detailed description of the input mode (BFM #0), refer to Subsection 5.4.1.
                                                                                                                                                   -ADP
                                                                                                                              B-19
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                      4 Analog Input
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                             4.1 Analog Input Procedures
B-20
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                               5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                  5.1 Assignment of Unit Numbers and Outline of Buffer Memory
                                                                                                                                                 Common Items
5.     Buffer Memory (BFM)
         This chapter describes the buffer memory incorporated in 4AD.                                                                       B
                                                                                                                                           FX3UC-4AD
                                                                                                                                           FX3U-4AD
5.1      Assignment of Unit Numbers and Outline of Buffer Memory
                                                                                                                                                 FX3U-4AD-ADP
         When connected to the FX3G/FX3U/FX3UC (D, DSS) Series PLC
                                                    Unit           Unit                              Unit
                                                  number: 0      number: 1                         number: 2
                                                                                                                                             D
                                                                                                                                                 FX3G-2AD-BD
                                   Input/output    Special        Special     Input/output         Special
                    Main unit       extension                                  extension
                                      block     function block function block    block           function unit
                                                                                                                                              E
         When connected to the FX3UC-32MT-LT(-2) PLC
                                                                                                                                                 FX3U-4DA
                  Unit number: 0
                  (Incorporated                      Unit          Unit                              Unit
                   CC-Link/LT)                     number: 1     number: 2                         number: 3
                                                                                                                                                 FX3U-4DA-ADP
                  (FX3UC-32MT       extension                                  extension
                      -LT(-2))        block     function block function block    block           function unit
FX3G-1DA-BD
                                                                                                                                             H
                                                                                                                                           FX3U-4AD-PT
                                                                                                                                                    -ADP
                                                                                                                                                     I
                                                                                                                                           FX3U-4AD-PTW
                                                                                                                                                    -ADP
                                                                                                                                               J
                                                                                                                                           FX3U-4AD-PNK
                                                                                                                                                    -ADP
                                                                                                                               B-21
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                  5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                     5.1 Assignment of Unit Numbers and Outline of Buffer Memory
          *1. Since buffer memory direct specification (U\G) can directly specify the buffer memory in the source or
              destination area of an applied instruction, programs can be created efficiently. (This function is supported
              only in FX3U/FX3UC PLCs.)
                                → For a detailed description of buffer memory reading/writing, refer to Section 5.2.
                                           → For a detailed description of the buffer memory, refer to Section 5.4.
B-22
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                               5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                   5.2 Buffer Memory Reading/Writing Method
                                                                                                                                           A
5.2       Buffer Memory Reading/Writing Method
                                                                                                                                               Common Items
          To read or write to the 4AD buffer memory, use the FROM/TO instructions or buffer memory direct
          specifications*1.
          However, to use buffer memory direct specification*1, software compatible with FX3U/FX3UC Series PLCs is
          required.                                                                                                                        B
                                                                                                                                         FX3UC-4AD
                                                                                                                                         FX3U-4AD
           *1.   This function is supported only in FX3U/FX3UC PLCs.
                             → For a detailed description of software compatible with the FX3U/FX3UC Series PLC,
                                                                                              refer to Section 1.4.
                                                                                                                                               FX3U-4AD-ADP
          the applied instruction as follows:
                                                                                                                                               FX3G-2AD-BD
          If the following program is created, data in buffer memory (BFM #10) of unit 1 will be multiplied by the data
          (K10), and then the multiplication result will be output to data registers (D10, D11).
            READ command
                                          FNC 22    U1\G10    K10       D10
                                           MUL
                                                                                                                                            E
                                                                                 Multiplication result
                                                                                                                                               FX3U-4DA
                      Unit number
            Buffer memory number                                                 Multiplier
        2. Example 2
          If the following program is created, the value in data register (D20) is added to K10 and written to buffer
          memory (BFM #6) of unit 1.                                                                                                         F
           WRITE command
                                                                                                                                               FX3U-4DA-ADP
                                         FNC 20      D20      K10      U1\G6
                                          ADD
                                                                                         (
                                                                                Addition Unit number
                                                                                result   Buffer memory number          )
                          Augend                                                Addend
                                                                                                                                          G
5.2.2     FROM/TO instruction (FX3G, FX3U, FX3UC PLC)
                                                                                                                                               FX3G-1DA-BD
        1. FROM instruction (Reading out BFM data to PLC)
          Use the FROM instruction to read the data from the buffer memory.
          In a sequence program, use this instruction as follows:
           READ command
                               FNC 78
                                                                                                                                           H
                                               K1    K10      D10        K1
                                                                                                                                         FX3U-4AD-PT
                               FROM
                                                                                Number of transfer
                      Unit number                                               data points
                                                                                                                                                  -ADP
           WRITE command
                                FNC 79
                                  TO
                                               K1    K0      H3300       K1
                                                                                                                                             J
                                                                                Number of transfer
                                                                                                                                         FX3U-4AD-PNK
If the above program is created, 1 point of data (H3300) will be written to buffer memory BFM #0 of unit No.1.
                                                                                                                             B-23
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                     5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                                       5.3 Buffer Memory List (BFM)
       BFM number                         Description                         Setting range    Initial value      Data type     Reference
                                                                                                                  Hexadeci-      Subsection
            #0*1       Input mode setting for channels 1 to 4                      *2         H0000 at delivery
                                                                                                                    mal            5.4.1
            #1         Not used                                                     -                 -                -              -
            #2         Averaging time units for channel 1                       1 to 4095            K1            Decimal
            #3         Averaging time units for channel 2                       1 to 4095            K1            Decimal       Subsection
            #4         Averaging time units for channel 3                       1 to 4095            K1            Decimal         5.4.2
           *1.     If power failure occurs, the EEPROM will retain its data.
           *2.     To specify the input mode of each channel, set each digit using hexadecimal numbers 0 to 8 and F.
           *3.     Use b0 to b3.
B-24
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                            5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                                             5.3 Buffer Memory List (BFM)
                                                                                                                                                             Common Items
       BFM number                           Description                          Setting range       Initial value      Data type     Reference
                          Convenient function setting:
                          Convenient functions:Automatic send
                                                                                                                        Hexadeci-      Subsection
           #22*1          function, data addition, upper/lower limit
                          detection, abrupt change detection, peak
                                                                                        *2          H0000 at delivery
                                                                                                                          mal            5.4.8           B
                                                                                                                                                       FX3UC-4AD
                                                                                                                                                       FX3U-4AD
                          value holding
         #23 to #25       Not used                                                       -                  -                -              -
                          Upper/lower limit value error status (Valid if b1                                             Hexadeci-      Subsection
            #26                                                                          -               H0000
                          of BFM #22 is set to ON)                                                                        mal            5.4.9
            #27
                          Abrupt change detection status (Valid if b2 of
                          BFM #22 is set to ON)
                                                                                         -               H0000
                                                                                                                        Hexadeci-
                                                                                                                          mal
                                                                                                                                       Subsection
                                                                                                                                         5.4.10          C
                                                                                                                                                             FX3U-4AD-ADP
                                                                                                                        Hexadeci-      Subsection
            #28           Over-scale status                                              -               H0000
                                                                                                                          mal            5.4.11
                                                                                                                        Hexadeci-      Subsection
            #29           Error status                                                   -               H0000
                                                                                                                          mal            5.4.12
                                                                                                                                       Subsection
            #30           Model code K2080                                               -               K2080           Decimal
                                                                                                                                         5.4.13          D
                                                                                                                                                             FX3G-2AD-BD
         #31 to #40       Not used                                                       -                  -                -              -
           #41*1          Channel-1 offset data (Unit: mV or µA)                • Voltage input:     K0 at delivery      Decimal
                                                                   BFM #21        -10000 to
           #42   *1       Channel-2 offset data (Unit: mV or µA)   will be                           K0 at delivery      Decimal
                                                                                  +9000*3                                              Subsection
                                                                   used for
           #43*1          Channel-3 offset data (Unit: mV or µA)                • Current input:     K0 at delivery      Decimal         5.4.14
                                                                   writing
           #44*1          Channel-4 offset data (Unit: mV or µA)
                                                                   data.
                                                                                  -20000 to
                                                                                 +17000*4            K0 at delivery      Decimal
                                                                                                                                                          E
                                                                                                                                                             FX3U-4DA
         #45 to #50       Not used                                                       -                  -                -              -
           #51   *1       Channel-1 gain data (Unit: mV or µA)                  • Voltage input:    K5000 at delivery    Decimal
                                                                   BFM #21        -9000 to
           #52*1          Channel-2 gain data (Unit: mV or µA)     will be                          K5000 at delivery    Decimal
                                                                                  +10000*3                                             Subsection
                                                                   used for
           #53*1          Channel-3 gain data (Unit: mV or µA)     writing
                                                                   data.
                                                                                • Current input:
                                                                                  -17000 to
                                                                                                    K5000 at delivery    Decimal        5.4.14
                                                                                                                                                           F
           #54*1          Channel-4 gain data (Unit: mV or µA)                    +30000*4          K5000 at delivery    Decimal
                                                                                                                                                             FX3U-4DA-ADP
         #55 to #60       Not used                                                       -                  -                -              -
                          Channel-1 addition data (Valid if b0 of BFM #22
            #61                                                                 -16000 to +16000           K0            Decimal
                          is set to ON)
                          Channel-2 addition data (Valid if b0 of BFM #22
            #62
                          is set to ON)
                                                                                -16000 to +16000           K0            Decimal
                                                                                                                                       Subsection       G
                                                                                                                                                             FX3G-1DA-BD
                          Channel-3 addition data (Valid if b0 of BFM #22                                                                5.4.15
            #63                                                                 -16000 to +16000           K0            Decimal
                          is set to ON)
                          Channel-4 addition data (Valid if b0 of BFM #22
            #64                                                                 -16000 to +16000           K0            Decimal
                          is set to ON)
         #65 to #70       Not used                                                       -                  -                -              -
            #73
                          Channel-3 lower limit value error setting (Valid if upper limit value
                                                                                                    Minimum digital
                                                                                                     value in input      Decimal
                                                                                                                                         5.4.16
                                                                                                                                                                 I
                          b1 of BFM #22 is set to ON)                         error setting value
                                                                                                                                                       FX3U-4AD-PTW
                                                                                                         range
                                                                                                    Minimum digital
                          Channel-4 lower limit value error setting (Valid if
            #74                                                                                      value in input      Decimal
                          b1 of BFM #22 is set to ON)
                                                                                                                                                                -ADP
                                                                                                         range
         #75 to #80       Not used                                                       -                  -                -              -
           *1.        If power failure occurs, the EEPROM will retain its data.
                                                                                                                                                           J
                                                                                                                                                       FX3U-4AD-PNK
                                                                                                                                           B-25
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                             5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                                              5.3 Buffer Memory List (BFM)
       BFM number                        Description                           Setting range         Initial value       Data type     Reference
                       Channel-1 upper limit value error setting                                   Maximum digital
              #81                                                                                                         Decimal
                       (Valid if b1 of BFM #22 is set to ON)                                      value in input range
                       Channel-2 upper limit value error setting              From lower limit     Maximum digital
              #82                                                             value error setting value in input range    Decimal
                       (Valid if b1 of BFM #22 is set to ON)                                                                            Subsection
                                                                              value to maximum
                       Channel-3 upper limit value error setting                                   Maximum digital                        5.4.16
              #83                                                             digital value in                            Decimal
                       (Valid if b1 of BFM #22 is set to ON)                  input range         value in input range
                       Channel-4 upper limit value error setting                                   Maximum digital
              #84                                                                                                         Decimal
                       (Valid if b1 of BFM #22 is set to ON)                                      value in input range
         #85 to #90    Not used                                                        -                   -                  -              -
                       Channel-1 abrupt change detection value                 From 1 to 50% of
              #91                                                                                   5% of full scale      Decimal
                       (Valid if b2 of BFM #22 is set to ON)                      full scale
                       Channel-2 abrupt change detection value                 From 1 to 50% of
              #92                                                                                   5% of full scale      Decimal
                       (Valid if b2 of BFM #22 is set to ON)                      full scale                                            Subsection
                       Channel-3 abrupt change detection value                 From 1 to 50% of                                           5.4.17
              #93                                                                                   5% of full scale      Decimal
                       (Valid if b2 of BFM #22 is set to ON)                      full scale
                       Channel-4 abrupt change detection value                 From 1 to 50% of
              #94                                                                                   5% of full scale      Decimal
                       (Valid if b2 of BFM #22 is set to ON)                      full scale
         #95 to #98    Not used                                                        -                   -                  -              -
                       Clear of upper/lower limit error data or abrupt                                                                  Subsection
              #99                                                                     *1                H0000                 -
                       change error data                                                                                                  5.4.18
              #100     Not used                                                        -                   -                  -              -
                       Channel-1 minimum peak value (Valid if b3 of
              #101                                                                     -                   -              Decimal
                       BFM #22 is set to ON)
                       Channel-2 minimum peak value (Valid if b3 of
              #102                                                                     -                   -              Decimal
                       BFM #22 is set to ON)                                                                                            Subsection
                       Channel-3 minimum peak value (Valid if b3 of                                                                       5.4.19
              #103                                                                     -                   -              Decimal
                       BFM #22 is set to ON)
                       Channel-4 minimum peak value (Valid if b3 of
              #104                                                                     -                   -              Decimal
                       BFM #22 is set to ON)
        #105 to #108   Not used                                                        -                   -                  -              -
                                                                                                                         Hexadeci-      Subsection
              #109     Minimum peak value resetting                                   *3                H0000
                                                                                                                           mal            5.4.20
              #110     Not used                                                        -                   -                  -              -
                       Channel-1 maximum peak value (Valid if b3
              #111                                                                     -                   -              Decimal
                       of BFM #22 is set to ON)
                       Channel-2 maximum peak value (Valid if b3
              #112                                                                     -                   -              Decimal
                       of BFM #22 is set to ON)                                                                                         Subsection
                       Channel-3 maximum peak value (Valid if b3                                                                          5.4.19
              #113                                                                     -                   -              Decimal
                       of BFM #22 is set to ON)
                       Channel-4 maximum peak value (Valid if b3
              #114                                                                     -                   -              Decimal
                       of BFM #22 is set to ON)
        #115 to #118   Not used                                                        -                   -                  -              -
                                                                                                                         Hexadeci-      Subsection
              #119     Maximum peak value resetting                                   *3                H0000
                                                                                                                           mal            5.4.20
        #120 to #124   Not used                                                        -                   -                  -              -
                       Peak values (Minimum: BFM #101 to #104 /
                       Maximum: #111 to #114) automatic transfer-
                                                                                                                                        Subsection
          #125*2       to first data register specification (Valid if b4 of        0 to 7992        K200 at delivery      Decimal
                                                                                                                                          5.4.21
                       BFM #22 is set to ON / Occupies of 8
                       consecutive points)
        *1.     Use b0 to b2.
        *2.     If power failure occurs, the EEPROM will retain its data.
        *3.     Use b0 to b3.
B-26
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                       5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                                       5.3 Buffer Memory List (BFM)
                                                                                                                                                   A
       BFM number                        Description                          Setting range    Initial value      Data type     Reference
                                                                                                                                                       Common Items
                       Upper/lower limit error status data (BFM #26)
                                                                                                                                 Subsection
             #126*1    automatic transfer-to data register specification        0 to 7999     K208 at delivery     Decimal
                                                                                                                                   5.4.22
                       (Valid if b5 of BFM #22 is set to ON)
                       Abrupt change detection status data (BFM #27)
                                                                                                                                 Subsection
             #127*1    automatic transfer-to data register specification
                       (Valid if b6 of BFM #22 is set to ON)
                                                                                0 to 7999     K209 at delivery     Decimal
                                                                                                                                   5.4.23          B
                                                                                                                                                 FX3UC-4AD
                                                                                                                                                 FX3U-4AD
                       Over-scale status data (BFM #28) automatic
                                                                                                                                 Subsection
             #128*1    transfer-to data register specification (Valid if b7     0 to 7999     K210 at delivery     Decimal
                                                                                                                                   5.4.24
                       of BFM #22 is set to ON)
                       Error status data (BFM #29) automatic transfer-
                                                                                                                                 Subsection
             #129*1    to data register specification (Valid if b8 of BFM       0 to 7999     K211 at delivery     Decimal
                       #22 is set to ON)
                                                                                                                                   5.4.25
                                                                                                                                                   C
                                                                                                                                                       FX3U-4AD-ADP
        #130 to #196   Not used                                                     -                -                 -              -
                       Selection of cyclic data update function (function                                          Hexadeci-     Subsection
             #197                                                                   *2            H0000
                       for data history)                                                                             mal           5.4.26
                                                                                                                                 Subsection
             #198*1    Data history sampling time setting (Unit: ms)            0 to 30000        K15000           Decimal
                                                                                                                                   5.4.27
                                                                                                                                                       FX3G-2AD-BD
             #200      Channel-1 data history (initial value)                       -               K0             Decimal
                                                                                                                   Decimal
               ~
                                                                                                     ~
             #1899     Channel-1 data history (1,700th value)                       -               K0             Decimal
             #1900     Channel-2 data history (initial value)                       -               K0             Decimal
                                                                                                                   Decimal
                                                                                                                                                    E
               ~
                                                                                                                                                       FX3U-4DA
             #3599     Channel-2 data history (1,700th value)                       -               K0             Decimal       Subsection
             #3600     Channel-3 data history (initial value)                       -               K0             Decimal         5.4.29
                                                                                                                   Decimal
               ~
                                                                                                                                                       FX3U-4DA-ADP
                                                                                                                   Decimal
               ~
       *1.    If power failure occurs, the EEPROM will retain its data.
       *2.    Use b0 to b3.                                                                                                                       G
       *3.    Use b0 to b3 and b8 to b11.
FX3G-1DA-BD
                                                                                                                                                   H
                                                                                                                                                 FX3U-4AD-PT
                                                                                                                                                          -ADP
                                                                                                                                                           I
                                                                                                                                                 FX3U-4AD-PTW
                                                                                                                                                          -ADP
                                                                                                                                                     J
                                                                                                                                                 FX3U-4AD-PNK
                                                                                                                                                          -ADP
                                                                                                                                     B-27
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                     5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                          5.4 Buffer Memory Details
             H
           ch4                       ch1
           ch3                       ch2
          The different types of input modes are shown in the following table:
                                         → For a detailed description of input characteristics, refer to Section 2.4.
B-28
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                         5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                             5.4 Buffer Memory Details
                                                                                                                                      A
5.4.2     BFM #2 to #5: Averaging time
                                                                                                                                          Common Items
                                                                                               Setting range: 1 to 4095
                                                                                                        Initial value: K1
                                                                                         Numeric data type: Decimal (K)
To change the channel data type from the immediate data (channels 1 to 4: BFM #10 to #13) to the average B
                                                                                                                                    FX3UC-4AD
                                                                                                                                    FX3U-4AD
          data, set the desired averaging time (channels 1 to 4 : BFM #2 to 5).
          The relation between the set averaging time and the corresponding operation is shown in the following table.
                             → For a detailed description of channel data update timing, refer to Subsection 5.4.4.
            Averaging
            time (BFM
             #2 to #5)
                                    Channel data (BFM #10 to #13) type                          Error descriptions                    C
                                                                                                                                          FX3U-4AD-ADP
                         Immediate data                                               K0 will be set, and the averaging time
           0 or less     (Each time the A/D conversion is performed, the channel      setting error (b10 of BFM #29) will
                         data will be updated.)                                       occur.
                         Immediate data
           1 (initial
           value)
                         (Each time the A/D conversion is performed, the channel
                         data will be updated.)
                                                                                                         -
                                                                                                                                      D
                                                                                                                                          FX3G-2AD-BD
                         Average data
                         (Each time the A/D conversion is performed, the average
           2 to 400                                                                                      -
                         value will be calculated and the channel data will be
                         updated.)
                         Average data
                         (Each time the A/D conversion data reaches the averaging                                                      E
           401 to 4095                                                                                   -
                         time, the average data will be calculated and the channel
                                                                                                                                          FX3U-4DA
                         data will be updated.)
                        Average data                                                  4096 will be set, and the averaging
           4096 or more (Each time the A/D conversion is performed, the channel       time setting error (b10 of BFM #29) will
                        data will be updated.)                                        occur.
                                                                                                                                        F
                                                                                                                                          FX3U-4DA-ADP
        1. Application
          If the measurement signal contains comparatively reduced ripple noise, such as supply voltage frequency,
          averaging will result in obtaining of stable data.
                                                                                                                                          FX3G-1DA-BD
            filter setting: BFM #6 to #9 for channels 1 to 4)
            To use the digital filter function, be sure to set the averaging time of the corresponding channel to "1".
            (Averaging time: BFM #2 to #5 for channels 1 to 4)
            If the averaging time is set to a value other than "1" and the digital filter (BFM #6 to #9 for channels 1 to 4)
            is set to a value other than "0", the digital filter setting error (b11 of BFM #29) will occur.
                                                                                                                                      H
          • If one of the channels uses the digital filter, the A/D conversion time will be set to 5 ms for all the channels.
                                                                                                                                    FX3U-4AD-PT
          • If the averaging time is out of the setting range, the averaging time setting error (b10 of BFM #29) will
            occur.
                                                                                                                                             -ADP
• If the averaging time is set, the data history function cannot be used.
                                                                                                                                              I
                                                                                                                                    FX3U-4AD-PTW
                                                                                                                                             -ADP
                                                                                                                                        J
                                                                                                                                    FX3U-4AD-PNK
                                                                                                                                             -ADP
                                                                                                                        B-29
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                               5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                                                  5.4 Buffer Memory Details
           To use the digital filter for channel data (BFM #10 to #13 for channels 1 to 4), set the digital filter value in the
           corresponding buffer memory (BFM #6 to #9 for channels 1 to 4).
                                  → For a detailed description of channel data update timing, refer to Subsection 5.4.4.
           If the digital filter function is used, the relation between the analog input value and the set digital filter value or
           the digital output value (channel data) will be as follows:
           • Digital filter value (BFM #6 to #9 for channels 1 to 4) > Fluctuation of analog signal (fluctuation
             width: less than 10 times of sampling)
             If the fluctuation of the analog signal (input value) is less than the set digital filter value, the analog input
             value will be converted into a stabilized digital output value and stored in the corresponding buffer memory
             (BFM #10 to #13 for channels 1 to 4).
           • Digital filter value (BFM #6 to #9 for channels 1 to 4) < Fluctuation of analog signal
             If the fluctuation of the analog signal (input value) is more than the set digital filter value, the digital output
             value will follow the analog input value, and the digital output value equal to the analog input value will be
             stored in the corresponding buffer memory (BFM #10 to #13 for channels 1 to 4).
        1. Application
           If the measurement signal contains steep spike noise, use the digital filter instead of the averaging function.
           The digital filter produces more stabilized data results.
B-30
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                  5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                                      5.4 Buffer Memory Details
                                                                                                                                               A
5.4.4    BFM #10 to #13: Channel data
                                                                                                                                                   Common Items
                                                                                                   Numeric data type: Decimal (K)
         Use these buffer memories to store the A/D converted digital values.
         The channel data (BFM #10 to #13 for channels 1 to 4) and the data update timing will depend on the set
         averaging time (BFM #2 to #5 for channels 1 to 4) or the digital filter setting condition (BFM #6 to #9 for                           B
                                                                                                                                             FX3UC-4AD
                                                                                                                                             FX3U-4AD
         channels 1 to 4) as shown in the following table.
                                       → For a detailed description of the averaging time, refer to Subsection 5.4.2.
                                     → For a detailed description of digital filter functions, refer to Subsection 5.4.3.
              Averaging       Digital filter                        Channel data (BFM #10 to #13) update timing
                time            function                                                                                                       C
          (BFM #2 to #5)     (BFM #6 to #9)             Channel data type                              Update timing
                                                                                                                                                   FX3U-4AD-ADP
                                                   Immediate data                     Each time the A/D conversion is performed, the
                           0 (The digital filter   "0" will be set, and the           data will be updated.
          0 or less
                           will not be used.)      averaging time setting error       The update timing will be as follows:
                                                   (b10 of BFM #29) will occur.
                           0 (The digital filter
                                                   Immediate data
                                                                                         Update time = 500µs*1 × Number of
                                                                                         selected channels
                                                                                                                                               D
                           will not be used.)
                                                                                                                                                   FX3G-2AD-BD
                                                                                      Each time the A/D conversion is performed, the
          1                1 to 1600               Immediate data                     data will be updated.
                           (The digital filter     The digital filter function will   The update timing will be as follows:
                           will be used.)          be used.                              Update time = 5ms × Number of selected
                                                                                         channels                                               E
                                                                                                                                                   FX3U-4DA
                                                                                      Each time the A/D conversion is performed, the
                                                                                      data will be updated.
          2 to 400                                 Average data                       The update timing will be as follows:
                                                                                                                                                   FX3U-4DA-ADP
                                                                                      the set averaging time, the data will be updated.
                                                   Average data
                                                                                      The update timing will be as follows:
                                                   "4096" will be set, and the
          4096 or more
                                                   averaging time setting error          Update time = 500µs*1 × Number of
                                                   (b10 of BFM #29) will occur.          selected channels × Averaging time
                                                                                                                                                   FX3G-1DA-BD
                 all the channels.
                                                                                                                                               H
                                                                                                                                             FX3U-4AD-PT
                                                                                                                                                      -ADP
                                                                                                                                                       I
                                                                                                                                             FX3U-4AD-PTW
                                                                                                                                                      -ADP
                                                                                                                                                 J
                                                                                                                                             FX3U-4AD-PNK
                                                                                                                                                      -ADP
                                                                                                                                 B-31
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                             5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                                 5.4 Buffer Memory Details
                                                                                                     Setting range: K0 or K1
                                                                                                              Initial value: K0
                                                                                               Numeric data type: Decimal (K)
          Use this function to initialize all data in BFM #0 to #6999, to the factory default status.
                Set value                  Description
           K0                                 Normal
           K1                            Initializes all data
          Set "K1" to initialize all data. When initialization is complete, "K0" will be set automatically.
          Channel numbers are assigned to the 4 lower bits of BFM #21. If any of these bits are turned on, the offset
          data (BFM #41 to #44) and gain data (BFM #51 to #54) of the corresponding channel will be written to the
          internal memory (EEPROM). When written to the internal memory, the data will become valid.
B-32
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                             5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                                 5.4 Buffer Memory Details
                                                                                                                                          A
5.4.8     BFM #22: Convenient function setting
                                                                                                                                              Common Items
                                                                                                       Initial value: H0000
                                                                                       Numeric data type: Hexadecimal (H)
          Turn on each bit (b0 to b8) of BFM #22 to enable the function assigned to each bit (refer to the following
          table). Turn off each bit to disable the function of each bit.
                                                                                                                                          B
                                                                                                                                        FX3UC-4AD
                                                                                                                                        FX3U-4AD
        1. Function assigned to each bit of BFM #22
             Bit No.         Function                                     Description                                 Reference
                                              The channel data (BFM #10 to #13), peak data (BFM #101 to
                                              #104, #111 to #114), and data history (BFM #200 to #6999) will
                                              be subject to change (the addition data (BFM #61 to #64) will be                            C
                                                                                                                      Subsection
           b0          Data addition function added to the measurement data).
                                                                                                                                              FX3U-4AD-ADP
                                                                                                                        5.4.15
                                              When setting the lower limit error data (BFM #71 to #74) or the
                                              upper limit error data (BFM #81 to #84), add the addition data
                                              (BFM #61 to #64) to the error data to be set.
                                               If the A/D conversion data of a channel is outside the range set
           b1
                       Upper/lower limit
                       detection function
                                               by the lower limit error data (BFM #71 to #74) and the upper limit
                                               error data (BFM #81 to #84), the result will be written to BFM
                                                                                                                      Subsection
                                                                                                                        5.4.16
                                                                                                                                          D
                                                                                                                                              FX3G-2AD-BD
                                               #26 as the upper/lower limit error status data.
                                               When channel data (BFM #10 to #13) is updated, if the
                                               difference between the previous value and the new value is
                       Abrupt change                                                                                  Subsection
           b2                                  larger than the set abrupt change detection value (value set in
                       detection function                                                                               5.4.17
                                               BFM #91 to #94), the result will be written to BFM #27 as the
                                               abrupt change detection status data.                                                        E
                                                                                                                                              FX3U-4DA
                                               The minimum value of channel data written to BFM #10 to #13
                                               will be written to BFM #101 to #104 as the minimum peak value,
                       Peak value holding                                                                             Subsection
           b3                                  and the maximum value of channel data written to BFM #10 to
                       function                                                                                         5.4.19
                                               #13 will be written to BFM #111 to #114 as the maximum peak
                                               value.
                                               If the automatic transfer-to first data register is specified in BFM
                                                                                                                      Subsection
                                                                                                                                            F
                                               #125, the minimum peak value (BFM #101 to #104) and the
                                                                                                                                              FX3U-4DA-ADP
                       Peak value automatic                                                                             5.4.19
           b4                                  maximum peak value (BFM #111 to #114) will be automatically
                       transfer function                                                                              Subsection
                                               written to the specified data registers (8 points (registers)
                                                                                                                        5.4.21
                                               starting from the first data register specified).
                                               If the upper/lower limit error status data automatic transfer-to       Subsection
                       Upper/lower limit error
           b5          status data automatic
                                               data register is specified in BFM #126, the upper/lower limit error
                                               status data (BFM #26) will be automatically written to the
                                                                                                                        5.4.16
                                                                                                                      Subsection
                                                                                                                                         G
                       transfer function
                                                                                                                                              FX3G-1DA-BD
                                               specified data register.                                                 5.4.22
                       Abrupt change           If the abrupt change detection status data automatic transfer-to       Subsection
                       detection status data   data register is specified in BFM #127, the abrupt change                5.4.17
           b6
                       automatic transfer      detection status data (BFM #27) will be automatically written to       Subsection
                       function                the specified data register.                                             5.4.23
                       Over-scale status       If the over-scale status data automatic transfer-to data register is                       H
                                                                                                                      Subsection
           b7          data automatic          specified in BFM #128, the over-scale status data (BFM #28) will
                                                                                                                                        FX3U-4AD-PT
                                                                                                                        5.4.24
                       transfer function       be automatically written to the specified data register.
                       Error status data       If the error status data automatic transfer to data register is
                                                                                                                      Subsection
                                                                                                                                                 -ADP
           b8          automatic transfer      specified in BFM #129, the error status data (BFM #29) will be
                                                                                                                        5.4.25
                       function                automatically written to the specified data register.
           b9 to b15              -            Not used.                                                                    -                     I
                                                                                                                                        FX3U-4AD-PTW
                                                                                                                                                 -ADP
                                                                                                                                            J
                                                                                                                                        FX3U-4AD-PNK
                                                                                                                                                 -ADP
                                                                                                                            B-33
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                    5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                       5.4 Buffer Memory Details
B-34
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                          5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                              5.4 Buffer Memory Details
                                                                                                                                       A
5.4.9     BFM #26: Upper/lower limit error status
                                                                                                                                           Common Items
                                                                                                      Initial value: H0000
                                                                                      Numeric data type: Hexadecimal (H)
          If channel data (BFM #10 to #13) is out of the range set by the lower limit error data (BFM #71 to #74) and the
          upper limit error data (BFM #81 to #84), the following operation will be performed:                                          B
          • If "channel data < lower limit error set value":
                                                                                                                                     FX3UC-4AD
                                                                                                                                     FX3U-4AD
            The lower limit error bit will turn on.
          • If "channel data > upper limit error set value":
            The upper limit error bit will turn on.
                                       → For a detailed description of upper/lower limit error status data resetting,
                                                                                         refer to Subsection 5.4.18.                   C
                                                                                                                                           FX3U-4AD-ADP
        1. BFM #26 bit assignment
          The upper and lower limit error values of each channel are assigned as shown in the following table:
                                                                                                                                           FX3G-2AD-BD
           b2                                             Lower limit error value
                                  ch2
           b3                                             Upper limit error value
           b4                                             Lower limit error value
                                  ch3
           b5                                             Upper limit error value                                                       E
           b6                                             Lower limit error value
                                                                                                                                           FX3U-4DA
                                  ch4
           b7                                             Upper limit error value
           b8 to b15   Not used.
                                                                                                                                           FX3U-4DA-ADP
            of BFM #22).
          • Perform one of the following operations to turn off the previously turned on bit:
            - Turn the power off and on.
            - Turn on b0 or b1 of BFM #99 to reset the upper/lower limit error status.
            - Write "H0000" in BFM #26 as the upper/lower limit error status data.                                                    G
                                                                                                                                           FX3G-1DA-BD
          • Even if an error is detected, channel data (BFM #10 to #13) will be continuously updated.
        3. Upper/lower limit error status data automatic transfer function (b5 of BFM #22)
          If the upper/lower limit error status data automatic transfer-to data register is specified in BFM #126, the data
          in BFM #26 can be transferred to the specified data register.
          When the upper/lower error is detected, data will be automatically transferred from the 4AD to the PLC. For                  H
          this reason, the PLC does not need the program for reading data, and the scanning time of the PLC can be
                                                                                                                                     FX3U-4AD-PT
          shortened.
                                                                                                : Represents a numeric value.
            Convenient function
                                                                                                                                              -ADP
                                                                                                                                         J
                                                                                                                                     FX3U-4AD-PNK
                                                                                                                                              -ADP
                                                                                                                         B-35
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                       5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                           5.4 Buffer Memory Details
B-36
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                           5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                                5.4 Buffer Memory Details
                                                                                                                                         A
5.4.11 BFM #28: Over-scale status
                                                                                                                                             Common Items
                                                                                                       Initial value: H0000
                                                                                       Numeric data type: Hexadecimal (H)
         If the input analog value is out of the A/D conversion range, the following operation will be performed:
         • If "(analog input value) < (lower limit value in A/D conversion range)":                                                      B
                                                                                                                                       FX3UC-4AD
                                                                                                                                       FX3U-4AD
           The over-scale lower limit bit will turn on.
         • If "(analog input value) < (upper limit value in A/D conversion range)":
           The over-scale upper limit bit will turn on.
                                                                                                                                             FX3U-4AD-ADP
          Voltage input          -10.2V to +10.2V
          Current input         -20.4mA to +20.4mA
                                                                                                                                             FX3G-2AD-BD
               Bit No.    Channel number                          Description
          b0                                               Over-scale (lower limit)
                                   ch1
          b1                                              Over-scale (upper limit)
          b2                                               Over-scale (lower limit)
                                   ch2
          b3                                              Over-scale (upper limit)                                                        E
          b4                                               Over-scale (lower limit)
                                                                                                                                             FX3U-4DA
                                   ch3
          b5                                              Over-scale (upper limit)
          b6                                               Over-scale (lower limit)
                                   ch4
          b7                                              Over-scale (upper limit)
          b8 to b15                                   Not used.                                                                            F
                                                                                                                                             FX3U-4DA-ADP
      3. Caution regarding use of over-scale status data
         • Perform one of the following operations to turn off the previously turned on bit:
           - Turn the power off and on.
           - Write "H0000" in BFM #28 as the over-scale status data.
         • Even if over scale is detected, channel data (BFM #10 to #13) will continuously be updated.
                                                                                                                                        G
                                                                                                                                             FX3G-1DA-BD
      4. Over-scale status data automatic transfer function (b7 of BFM #22)
         If the over-scale status data automatic transfer-to data register is specified in BFM #128, the data in BFM #28
         can be transferred to the specified data register.
         When over-scale is detected, data will be automatically transferred from the 4AD to the PLC. For this reason,
         the PLC does not need any program for reading the data, and the scan time of the PLC can be shortened.                          H
                                                                                            : Represents a numeric value.
                                                                                                                                       FX3U-4AD-PT
           Convenient function
                                                                  Automatic data transfer function
                setting
                                                                                                                                                -ADP
                                                                                                                                           J
                                                                                                                                       FX3U-4AD-PNK
                                                                                                                                                -ADP
                                                                                                                           B-37
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                                     5.4 Buffer Memory Details
B-38
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                      5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                            5.4 Buffer Memory Details
                                                                                                                                     A
5.4.13 BFM #30: Model code
                                                                                                                                         Common Items
                                                                                                   Initial value: K2080
                                                                                        Numeric data type: Decimal (K)
                                                                                                                                   FX3UC-4AD
                                                                                                                                   FX3U-4AD
5.4.14 BFM #41 to #44: Offset data / BFM #51 to #54: Gain data
                                                                                                                                         FX3U-4AD-ADP
         automatically stored. The initial offset data and gain data are set for each mode as shown in the following
         table:
         • Offset data:      Analog input value when the digital value is "0" (reference offset value)
         • Gain data:        Analog input value when the digital value is equal to the reference gain value (The
                             reference gain value depends on the set input mode.)                                                    D
                                                                                                                                         FX3G-2AD-BD
      1. Reference offset/gain value and initial value set at delivery
                                                                       Offset                          Gain
                        Input mode (BFM #0)                 (Channels 1 to 4: BFM #41 to    (Channels 1 to 4: BFM #51 to
                                                                        #44)                            #54)
            Set
                                Description
                                                             Reference
                                                                            Initial value
                                                                                             Reference
                                                                                                               Initial value
                                                                                                                                      E
           value                                               value                           value
                                                                                                                                         FX3U-4DA
                   Voltage input
             0                                                   0              0mV            16000              5000mV
                   (-10V to +10V:-32000 to +32000)
                   Voltage input
             1                                                   0              0mV             2000              5000mV
                   (-10V to +10V:-4000 to +4000)
                   Voltage input                                  0            0mV              5000              5000mV
                                                                                                                                       F
                                                                                                                                         FX3U-4DA-ADP
             2     Analog value direct indication mode      (Data change   (Data change     (Data change       (Data change
                   (-10V to +10V:-10000 to +10000)           impossible)    impossible)      impossible)        impossible)
             3     Current input (4mA to 20mA:0 to 16000)        0            4000µA           16000             20000µA
             4     Current input (4mA to 20mA:0 to 4000)         0            4000µA            4000             20000µA
             5
                   Current input
                   Analog value direct indication mode
                                                                4000
                                                            (Data change
                                                                              4000µA
                                                                           (Data change
                                                                                               20000
                                                                                            (Data change
                                                                                                                 20000µA
                                                                                                               (Data change
                                                                                                                                    G
                                                                                                                                         FX3G-1DA-BD
                   (4mA to 20mA:4000 to 20000)               impossible)    impossible)      impossible)        impossible)
                   Current input
             6                                                   0              0µA            16000             20000µA
                   (-20mA to +20mA:-16000 to +16000)
                   Current input
             7                                                   0              0µA             4000             20000µA
                   (-20mA to +20mA:-4000 to +4000)
                   Current input                                  0            0µA             20000             20000µA
                                                                                                                                     H
                                                                                                                                   FX3U-4AD-PT
             8     Analog value direct indication mode      (Data change   (Data change     (Data change       (Data change
                   (-20mA to +20mA:-20000 to +20000)         impossible)    impossible)      impossible)        impossible)
                                                                                                                                            -ADP
                                                                                                                                             I
                                                                                                                                   FX3U-4AD-PTW
                                                                                                                                            -ADP
                                                                                                                                       J
                                                                                                                                   FX3U-4AD-PNK
                                                                                                                                            -ADP
                                                                                                                       B-39
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                      5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                          5.4 Buffer Memory Details
          *1.   The offset and gain values should meet the following condition:
                Gain value - Offset value ≥ 1000
          *2.   The offset and gain values should meet the following condition:
                30000 ≥ Gain value - Offset value ≥ 3000
         If the addition data (BFM #61 to #64) is set, the set data will be added before storing the channel data (BFM
         #10 to #13), peak data (BFM #101 to #104, BFM #111 to #114), or data history (BFM #200 to #6999).
B-40
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                      5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                            5.4 Buffer Memory Details
                                                                                                                                     A
5.4.16 BFM #71 to #74: Lower limit error setting / BFM #81 to #84: Upper limit error setting
                                                                                                                                         Common Items
                                                                                           Setting range: See below.
                                                                                             Initial value: See below.
                                                                                       Numeric data type: Decimal (K)
         Set the upper/lower limit error data so that the upper/lower limit error status (BFM #26) can be detected.
                                                                                                                                     B
                                                                                                                                   FX3UC-4AD
                                                                                                                                   FX3U-4AD
         The data setting range depends on the input mode set in BFM #0.
         The following table shows the data setting range for each input mode:
                                                                                                                                         FX3U-4AD-ADP
                    Voltage input
             0                                                -32768 to +32767         -32768                   32767
                    (-10V to +10V: -32000 to +32000)
                    Voltage input
             1                                                 -4095 to +4095           -4095                    4095
                    (-10V to +10V: -4000 to +4000)
                    Voltage input                                                                                                    D
             2      Analog value direct indication mode       -10200 to +10200         -10200                   10200
                                                                                                                                         FX3G-2AD-BD
                    (-10V to +10V:-10000 to +10000)
                    Current input
             3                                                  -1 to +16383              -1                    16383
                    (4mA to 20mA:0 to 16000)
             4      Current input (4mA to 20mA:0 to 4000)        -1 to +4095              -1                     4095
                    Current input                                                                                                     E
             5      Analog value direct indication mode         3999 to 20400           3999                    20400
                                                                                                                                         FX3U-4DA
                    (4mA to 20mA:4000 to 20000)
                    Current input
             6                                                -16384 to +16383         -16384                   16383
                    (-20mA to +20mA:-16000 to +16000)
                    Current input
             7
                    (-20mA to +20mA:-4000 to +4000)
                                                               -4096 to +4095           -4096                    4095
                                                                                                                                       F
                                                                                                                                         FX3U-4DA-ADP
                    Current input
             8      Analog value direct indication mode       -20400 to +20400         -20400                   20400
                    (-20mA to +20mA:-20000 to +20000)
                                                                                                                                         FX3G-1DA-BD
         • To use the data addition function (b0 of BFM #22) together with this function, be sure to add the addition
           data (channels 1 to 4: BFM #61 to #64) to the upper/lower limit values to be set. In addition, observe the
           data setting range.
                                                                                                                                     H
                                                                                                                                   FX3U-4AD-PT
                                                                                                                                            -ADP
                                                                                                                                             I
                                                                                                                                   FX3U-4AD-PTW
                                                                                                                                            -ADP
                                                                                                                                       J
                                                                                                                                   FX3U-4AD-PNK
                                                                                                                                            -ADP
                                                                                                                        B-41
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                      5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                           5.4 Buffer Memory Details
         When channel data (BFM #10 to #13) is updated, if the difference between the previous value and the new
         value is larger than the set abrupt change detection value (value set in BFM #91 to #94), the system will judge
         that the channel data is changed abruptly.
         The result of abrupt change detection will be written to BFM #27 as the abrupt change detection status data.
         The abrupt change detection value setting range depends on the set input mode (BFM #0) as shown in the
         following table:
                         Input mode (BFM #0)
            Set                                                  Setting range        Initial value
                                   Description
           value
                    Voltage input
             0                                                    1 to 32767             3200
                    (-10V to +10V:-32000 to +32000)
                    Voltage input
             1                                                     1 to 4095              400
                    (-10V to +10V:-4000 to +4000)
                    Voltage input
             2      Analog value direct indication mode           1 to 10000             1000
                    (-10V to +10V:-10000 to +10000)
             3      Current input (4mA to 20mA:0 to 16000)         1 to 8191              800
             4      Current input (4mA to 20mA:0 to 4000)          1 to 2047              200
                    Current input
             5      Analog value direct indication mode            1 to 8191              800
                    (4mA to 20mA:4000 to 20000)
                    Current input
             6                                                    1 to 16383             1600
                    (-20mA to +20mA:-16000 to +16000)
                    Current input
             7                                                     1 to 4095              400
                    (-20mA to +20mA:-4000 to +4000)
                    Current input
             8      Analog value direct indication mode           1 to 20000             2000
                    (-20mA to +20mA:-20000 to +20000)
B-42
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                        5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                          5.4 Buffer Memory Details
                                                                                                                                   A
5.4.18 BFM #99: Clearance of upper/lower limit error data and abrupt change detection data
                                                                                                                                       Common Items
                                                                                                   Initial value: H0000
                                                                                   Numeric data type: Hexadecimal (H)
         Three error data clearance commands (lower limit error data clearance command, upper limit error data
         clearance command, and abrupt change detection data clearance command) are respectively assigned to the                   B
         3 lower bits of BFM #99.
                                                                                                                                 FX3UC-4AD
                                                                                                                                 FX3U-4AD
         Turning on each bit (batch turning on for all channels) will reset the corresponding error status flag (#26 or
         #27 of BFM).
                                                                                                                                       FX3U-4AD-ADP
                                                                                                  BFM #26
          b1                  Upper limit error data clearance command
          b2                  Abrupt change detection data clearance command                      BFM #27
          b3 to b15           Not used.                                                              -
         Two or more data clearance commands can be turned on at the same time.                                                    D
                                                                                                                                       FX3G-2AD-BD
      2. Operation after resetting BFM #26, #27
         Each bit will turn off automatically.
5.4.19 BFM #101 to #104: Minimum peak value / BFM #111 to #114: Maximum peak value E
                                                                                                                                       FX3U-4DA
                                                                                        Numeric data type: Decimal (K)
         The minimum channel data (channels 1 to 4) value written to BFM #10 to #13 will be written to BFM #101 to
         #104 as the minimum peak value, and the maximum channel data value will be written to BFM #111 to #114
         as the maximum peak value.
                                                                                                                                     F
      1. Caution regarding peak value
                                                                                                                                       FX3U-4DA-ADP
         To use the minimum peak value and the maximum peak value, be sure to turn on the peak value holding
         function (b3 of BFM #22).
         Note:
         • If the data addition function (b0 of BFM #22) is used together with this function, the addition data will be
           added to the measurement data.
                                                                                                                                  G
                                                                                                                                       FX3G-1DA-BD
         • If the value holding function is not used, the peak value will be "K0".
         When the peak value is updated, data will be automatically transferred from the 4AD to the PLC. For this
         reason, the PLC does not need any program for reading the data, and the scan time of the PLC can be
         shortened.
                                                                                        : Represents a numeric value.
                                                                                                                                          -ADP
           Convenient function
                setting
                                                               Automatic data transfer function
                                                                                                                                           I
                                                                                Transfer-to data register specification
                                                                                                                                 FX3U-4AD-PTW
                                                                                           (BFM #125: K )
                 ON = Valid         Transfer-from buffer memory
                                                                                (8 points (registers) starting from the
                                                                                       specified data register)
                                                                                                                                          -ADP
                                                                                                                     B-43
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                      5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                         5.4 Buffer Memory Details
5.4.20 BFM #109: Minimum peak value resetting / BFM #119: Maximum peak value
       resetting
                                                                 Description
           Bit No.
                                         BFM #109                                          BFM #119
          b0          Channel-1 minimum peak value (BFM #101) resetting Channel-1 maximum peak value (BFM #111) resetting
          b1          Channel-2 minimum peak value (BFM #102) resetting Channel-2 maximum peak value (BFM #112) resetting
          b2          Channel-3 minimum peak value (BFM #103) resetting Channel-3 maximum peak value (BFM #113) resetting
          b3          Channel-4 minimum peak value (BFM #104) resetting Channel-4 maximum peak value (BFM #114) resetting
          b4 to b15 Not used.
         Two or more bits can be turned on at a time.
5.4.21 BFM #125: Peak value automatic transfer to first data register specification
         If the automatic transfer to first data register is specified in BFM #125, the minimum peak value (BFM #101 to
         #104) and the maximum peak value (BFM #111 to #114) will be automatically transferred to the specified
         data registers (8 points (registers) starting from the first data register specified).
         When the peak value is updated, data will be automatically transferred from the 4AD to the PLC. For this
         reason, the PLC does not need any program for reading the data, and the scan time of the PLC can be
         shortened.
            → For a detailed description of the minimum peak value (BFM #101 to #104) and the maximum peak
                                                                   value (BFM #111 to #114), refer to Subsection 5.4.19.
       2. Caution regarding peak value automatic transfer-to first data register specification
         • If data registers are already specified for the other automatic transfer functions, do not specify the same
           data registers.
         • Be sure to turn on the peak value automatic transfer function (b4 of BFM #22) and the peak value holding
           function (b3 of BFM #22).
         • The data written to BFM #125 will be retained in the EEPROM.
B-44
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                      5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                          5.4 Buffer Memory Details
                                                                                                                                   A
      3. Caution regarding EEPROM writing
                                                                                                                                       Common Items
         If data is written to BFM #0, #19, #21, #22, #125 to #129, or #198, the data will also be written to the 4AD
         EEPROM.
                    → For a detailed description of caution regarding EEPROM writing, refer to Subsection 5.4.1.
5.4.22 BFM #126: Upper/lower error status data automatic transfer-to data register                                                 B
       specification
                                                                                                                                 FX3UC-4AD
                                                                                                                                 FX3U-4AD
                                                                                                 Setting range: 0 to 7999
                                                                                        Initial value (at delivery) : K208
                                                                                        Numeric data type: Decimal (K)
         Use this function to automatically transfer the upper/lower limit error status data (BFM #26) to the data
                                                                                                                                   C
                                                                                                                                       FX3U-4AD-ADP
         register specified in BFM #126.
         When the upper/lower limit error is detected, data will be automatically transferred from the 4AD to the PLC.
         For this reason, the PLC does not need any program for reading the data, and the scanning time of the PLC
         can be shortened.
                                 → For a detailed description of the upper/lower limit error status data (BFM #26),
                                                                                             refer to Subsection 5.4.9.            D
                                                                                                                                       FX3G-2AD-BD
      1. If "BFM #126 = K208 (initial value)"
            Specified data register                     Description
                     D208              Upper/lower limit error status data in BFM #26
      2. Cautions regarding upper/lower limit error status data automatic transfer-to data register                                 E
         specification
                                                                                                                                       FX3U-4DA
         • If a data register is already specified for the other automatic transfer functions, do not specify the same
           data register.
         • Be sure to turn on the upper/lower limit error status data automatic transfer function (b5 of BFM #22) and
           the upper/lower limit detection function (b1 of BFM #22).
                                                                                                                                     F
         • The data written to BFM #126 will be retained in the EEPROM.
                                                                                                                                       FX3U-4DA-ADP
      3. Caution regarding EEPROM writing
         If data is written to BFM #0, #19, #21, #22, #125 to #129, or #198, the data will also be written to the 4AD
         EEPROM.
                    → For a detailed description of caution regarding EEPROM writing, refer to Subsection 5.4.1.
                                                                                                                                  G
FX3G-1DA-BD
                                                                                                                                   H
                                                                                                                                 FX3U-4AD-PT
                                                                                                                                          -ADP
                                                                                                                                           I
                                                                                                                                 FX3U-4AD-PTW
                                                                                                                                          -ADP
                                                                                                                                     J
                                                                                                                                 FX3U-4AD-PNK
                                                                                                                                          -ADP
                                                                                                                     B-45
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                     5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                         5.4 Buffer Memory Details
5.4.23 BFM #127: Abrupt change detection status data automatic transfer-to data register
       specification
         Use this function to automatically transfer the abrupt change detection status data (BFM #27) to the data
         register specified in BFM #127.
         When abrupt change is detected, data will be automatically transferred from the 4AD to the PLC. For this
         reason, the PLC does not need any program for reading the data, and the scan time of the PLC can be
         shortened.
                               → For a detailed description of the abrupt change detection status data (BFM #27),
                                                                                        refer to Subsection 5.4.10.
       2. Caution regarding abrupt change detection status data automatic transfer to data register
          specification
         • If a data register is already specified for the other automatic transfer functions, do not specify the same
           data register.
         • Be sure to turn on the abrupt change detection status data automatic transfer function (b6 of BFM #22) and
           the abrupt change detection function (b2 of BFM #22).
         • The data written to BFM #127 will be retained in the EEPROM.
B-46
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                     5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                         5.4 Buffer Memory Details
                                                                                                                                  A
5.4.24 BFM #128: Over-scale status data automatic transfer-to data register specification
                                                                                                                                      Common Items
                                                                                               Setting range: 0 to 7999
                                                                                      Initial value (at delivery) : K210
                                                                                      Numeric data type: Decimal (K)
         Use this function to automatically transfer the over-scale status data (BFM #28) to the data register specified
                                                                                                                                  B
                                                                                                                                FX3UC-4AD
                                                                                                                                FX3U-4AD
         in BFM #128.
         When over-scale is detected, data will be automatically transferred from the 4AD to the PLC. For this reason,
         the PLC does not need any program for reading the data, and the scan time of the PLC can be shortened.
               → For a detailed description of the over-scale status data (BFM #28), refer to Subsection 5.4.11.
                                                                                                                                      FX3U-4AD-ADP
          Specified data register                    Description
                   D210             Over-scale status data in BFM #28
      2. Cautions regarding over-scale status data automatic transfer-to data register specification
         • If a data register is already specified for the other automatic transfer functions, do not specify the same
           data register.
                                                                                                                                  D
                                                                                                                                      FX3G-2AD-BD
         • Be sure to turn on the over-scale status data automatic transfer function (b7 of BFM #22).
         • The data written to BFM #128 will be retained in the EEPROM.
                                                                                                                                      FX3U-4DA
                    → For a detailed description of caution regarding EEPROM writing, refer to Subsection 5.4.1.
5.4.25 BFM #129: Error status data automatic transfer-to data register specification
                                                                                                                                      FX3U-4DA-ADP
                                                                                      Numeric data type: Decimal (K)
         Use this function to automatically transfer the error status data (BFM #29) to the data register specified in
         BFM #129.
         When an error is detected, data will be automatically transferred from the 4AD to the PLC. For this reason,
         the PLC does not need any program for reading the data, and the scan time of the PLC can be shortened.                  G
                     → For a detailed description of the error status data (BFM #29), refer to Subsection 5.4.12.
                                                                                                                                      FX3G-1DA-BD
      1. If "BFM #129 = K211 (initial value)"
          Specified data register                    Description
                   D211             Error status data in BFM #29
                                                                                                                                  H
      2. Cautions regarding error status data automatic transfer-to data register specification
                                                                                                                                FX3U-4AD-PT
         • If a data register is already specified for the other automatic transfer functions, do not specify the same
           data register.
                                                                                                                                         -ADP
         • Be sure to turn on the error status data automatic transfer function (b8 of BFM #22).
         • The data written to BFM #129 will be retained in the EEPROM.
                                                                                                                                          I
      3. Caution regarding EEPROM writing
                                                                                                                                FX3U-4AD-PTW
         If data is written to BFM #0, #19, #21, #22, #125 to #129, or #198, the data will also be written to the 4AD
         EEPROM.
                                                                                                                                         -ADP
→ For a detailed description of caution regarding EEPROM writing, refer to Subsection 5.4.1.
                                                                                                                                    J
                                                                                                                                FX3U-4AD-PNK
                                                                                                                                         -ADP
                                                                                                                    B-47
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                            5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                               5.4 Buffer Memory Details
5.4.26 BFM #197: Selection of cyclic data update function (function for data history)
       1. Sampling cycle
         As shown in the following table, the sampling cycle depends on whether the digital filter function is used.
                                                         Value set in
           Whether digital filter function is used                                            Sampling cycle
                                                          BFM #198
                                                                        0.5 ms × number of selected channels (number of
                                                        0
                                                                        channels using the digital filter function)
          None of the channels use the digital filter
          function.                                                     Set value (ms) in BFM #198 × number of selected
                                                        1 or more       channels (number of channels using the digital filter
                                                                        function)
                                                                        5 ms × number of selected channels (number of
                                                        9 or less
                                                                        channels using the digital filter function)
          One or more channels use the digital filter
          function.                                                     Set value (ms)*1 in BFM #198 × number of selected
                                                        10 or more      channels (number of channels using the digital filter
                                                                        function)
B-48
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                      5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                         5.4 Buffer Memory Details
                                                                                                                                  A
5.4.28 BFM #199: Data history resetting/stoppage
                                                                                                                                      Common Items
                                                                                                    Initial value: H0000
                                                                                    Numeric data type: Hexadecimal (H)
         The data history resetting function and the data history stoppage function are assigned to the bits of BFM #199.
                                                                                                                                  B
      1. Data history resetting function (b0 to b3)
                                                                                                                                FX3UC-4AD
                                                                                                                                FX3U-4AD
         The sampled history data can be reset for each channel.
         Turn on a bit to reset all the history data (1st to 1,700th) of the corresponding channel. (Note that two or more
         bits can be turned on at a time.)
         When the data reset is complete, the corresponding bit will turn off automatically.
                                                                                                                                      FX3U-4AD-ADP
         Data sampling can be temporarily stopped for each channel.
         Turn on a bit to temporarily stop sampling history data for the corresponding channel. (Note that two or more
         bits can be turned on at a time.)
         Turn off the bit to restart sampling of history data.
                                                                                                                                      FX3G-2AD-BD
          b0                  ch1
          b1                  ch2
                                                  Data history resetting function
          b2                  ch3
          b3                  ch4
                                                                                                                                   E
          b4 to b7            Not used.
                                                                                                                                      FX3U-4DA
          b8                  ch1
          b9                  ch2
                                                  Data history stoppage function
          b10                 ch3
          b11                 ch4
          b12 to b15          Not used.                                                                                             F
                                                                                                                                      FX3U-4DA-ADP
      4. Caution regarding data history resetting
         • When a bit is turned on, the corresponding data history will be reset.
FX3G-1DA-BD
                                                                                                                                  H
                                                                                                                                FX3U-4AD-PT
                                                                                                                                         -ADP
                                                                                                                                          I
                                                                                                                                FX3U-4AD-PTW
                                                                                                                                         -ADP
                                                                                                                                    J
                                                                                                                                FX3U-4AD-PNK
                                                                                                                                         -ADP
                                                                                                                    B-49
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                    5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                        5.4 Buffer Memory Details
                                                                                     …
          1,700th                 #1899            #3599           #5299            #6999
B-50
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                               6 Changing Input Characteristics
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                          6.1 Procedure for Changing Input Characteristics
                                                                                                                                              Common Items
6.     Changing Input Characteristics
         For the 4AD, the standard input characteristics are provided for each input mode (BFM #0) at the time of                         B
         factory shipment.
                                                                                                                                        FX3UC-4AD
                                                                                                                                        FX3U-4AD
         Changing the offset data (BFM #41 to #44) or gain data (BFM #51 to #54), however, can change the input
         characteristics of each channel. This chapter describes how to change the input characteristics.
                                                                                                                                              FX3U-4AD-ADP
   1     Determine the input mode (BFM #0)
         Determine the optimum input mode (BFM #0) for the selected channels and the voltage/current
         specifications.
                                                                                                                                          D
            Set value
                                                                                                                                              FX3G-2AD-BD
                                        Input mode                     Analog input range          Digital output range
             (HEX)
               0        Voltage input mode                                 -10V to +10V              -32000 to +32000
               1        Voltage input mode                                 -10V to +10V                -4000 to +4000
               2
                        Voltage input analog value direct indication
                        mode
                                                                        The offset and the gain cannot be adjusted.                        E
                                                                                                                                              FX3U-4DA
               3        Current input mode                                4mA to 20mA                     0 to 16000
               4        Current input mode                                4mA to 20mA                     0 to 4000
                        Current input analog value direct indication
               5                                                        The offset and the gain cannot be adjusted.
                        mode
               6        Current input mode                               -20mA to +20mA              -16000 to +16000                       F
                                                                                                                                              FX3U-4DA-ADP
               7        Current input mode                               -20mA to +20mA                -4000 to +4000
                        Current input analog value direct indication
               8                                                        The offset and the gain cannot be adjusted.
                        mode
             9 to E     Not used.                                                -                              -
               F        Channel not used                                         -                              -                        G
         Example: Enter "HFF00" in BFM #0 to set input mode 0 for channels 1 and 2 and prevent use channels 3 and
                                                                                                                                              FX3G-1DA-BD
         4.
                                                                                                                                                  I
                                                                                                                                        FX3U-4AD-PTW
                                                                                                                                                 -ADP
                                                                                                                                            J
                                                                                                                                        FX3U-4AD-PNK
                                                                                                                                                 -ADP
                                                                                                                            B-51
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                            6 Changing Input Characteristics
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                     6.1 Procedure for Changing Input Characteristics
          Input mode 0 Input characteristics provided at the time                            Input characteristics newly provided
          of factory shipment
                          Digital value                                                                 Digital value
                                  +32640                                                                   +32000
                                  +32000
                                           -32000
                                           -32640
             Numeric
                                      Input mode                    Analog input range    Gain standard value              Initial value
              value
                 0             Voltage input mode                      -10V to +10V               16000                      5000mV
                 1             Voltage input mode                      -10V to +10V                2000                      5000mV
                 3             Current input mode                      4mA to 20mA                16000                      20000µA
                 4             Current input mode                      4mA to 20mA                 4000                      20000µA
                 6             Current input mode                    -20mA to +20mA               16000                      20000µA
                 7             Current input mode                    -20mA to +20mA                4000                      20000µA
         Set the analog input value in mV for the voltage input mode, and set the analog input value in µA
         for the current input mode.
         Example: To set the gain value of 3 V, set 3000 mV.
                                                     → For a detailed description of gain data, refer to Subsection 5.4.14.
B-52
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                   6 Changing Input Characteristics
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                              6.1 Procedure for Changing Input Characteristics
                                                                                                                                              A
   5
                                                                                                                                                  Common Items
         Create a sequence program.
         To change the input characteristics, write the offset data (BFM #41 to #44) and the gain data (BFM
         #51 to #54) in the sequence program, and then turn on the corresponding bit of BFM #21 for the
         corresponding channel. The following example shows a program for the unit number 0.
                                                                                                                                              B
         Example: Program for changing the input characteristics of channels 1 and 2 (For FX3U, FX3UC Series
                                                                                                                                            FX3UC-4AD
                                                                                                                                            FX3U-4AD
         PLCs):
                                                                                                                                                  FX3U-4AD-ADP
                   M0
                                                             SET         M0
T0 K50 *1
                   T0
                                    FNC 16      K1000    U0\G41          K2
                                                                                  Offset value of                                             D
                                    FMOV P                                        channels 1 and 2
                                                                                                                                                  FX3G-2AD-BD
                                    FNC 16                                        Gain value of
                                                K3000    U0\G51          K2       channels 1 and 2
                                    FMOV P
                                                                                                                                                  FX3U-4DA
                                                             RST         M0
          *1.   It takes approximately 5 seconds to change the input mode (BFM #0). This is because all the set
                values should be changed.
                After changing the input mode, be sure to wait for 5 seconds or more before setting other data.                                 F
                                                                                                                                                  FX3U-4DA-ADP
         The input characteristics of each channel can be written in BFM #21. It is also possible to perform
         batch writing of input characteristics for two or more channels.
                                                                                                                                                  FX3G-1DA-BD
         Start the PLC, and turn on the command (X000) to write the input characteristics. In approx. 5 sec-
         onds, the offset data and the gain data will be written.
         Since the offset data and the gain data are stored in the 4AD EEPROM, it is possible to delete the
         sequence program.                                                                                                                    H
   7
                                                                                                                                            FX3U-4AD-PT
                RUN monitor
                M8000                                                          The digital values set for                                             I
                                  FNC 16                                       channels 1 to 4 will be read
                                                                                                                                            FX3U-4AD-PTW
                                                                                                                                                J
                                                                                                                                            FX3U-4AD-PNK
                                                                                                                                                     -ADP
                                                                                                                                B-53
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                   7 Examples of Practical Programs
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                        7.1 Program That Uses Averaging Time
       1. Conditions
         The sequence program described in this section is created under the following conditions.
         1) System configuration
            The FX3U-4AD (unit No.0) should be connected to the FX3U Series PLC.
         2) Input mode
            Channels 1 and 2 should be set to mode 0 (voltage input, -10V to +10V → -32000 to +32000).
            Channels 3 and 4 should be set to mode 3 (current input, 4mA to 20mA → 0 to 16000).
         3) Averaging time
            For channels 1 to 4, the averaging time should be set to "10".
         4) Digital filter function
            For channels 1 to 4, the digital filter function should be disabled (default).
         5) Device assignment
                     Device                             Description
                        D0        A/D converted digital value for channel 1
                        D1        A/D converted digital value for channel 2
                        D2        A/D converted digital value for channel 3
                        D3        A/D converted digital value for channel 4
                   T0
                                  FNC 16                                      For channels 1 and 2, the averaging time
                                               K10     U0\G2       K4         will be set to "10".
                                  FMOV P
             *1.   After setting the input mode, set the data writing time (waiting time) to 5 seconds or more for each
                   setting.
                   The specified input mode will be retained even if power failure occurs. After specifying the input mode,
                   if the same input mode is used, it is not necessary to set the input mode and waiting time (T0 K50).
             *2.   To use the default value set for the digital filter function, it is not necessary to set the digital filter
                   function in the sequence program.
B-54
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                               7 Examples of Practical Programs
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                     7.1 Program That Uses Averaging Time
                                                                                                                                         A
         • For FX3G, FX3U, FX3UC Series PLCs
                                                                                                                                             Common Items
                Initial pulse
                  M8002
                                FNC 79                                          Input modes of channels 1
                                            K0        K0        H3300     K1    to 4 will be specified.*1
                RUN monitor     TO P
                 M8000
                                                           T0    K50 *1
                                                                                                                                         B
                                                                                                                                       FX3UC-4AD
                                                                                                                                       FX3U-4AD
                    T0
                                FNC 79                                          For channels 1 and 2, the averaging time
                                            K0        K2        K10       K4    will be set to "10".
                                TO P
                                FNC 78      K0       K10         D0       K4
                                                                                The digital values set for channels                      C
                                                                                1 to 4 will be read out to D0 to D3.
                                                                                                                                             FX3U-4AD-ADP
                                FROM
          *1.      After setting the input mode, set the data writing time (waiting time) to 5 seconds or more for each
                   setting.
                   The specified input mode will be retained even if power failure occurs. After specifying the input mode,
                   if the same input mode is used, it is not necessary to set the input mode and waiting time (T0 K50).                  D
          *2.      To use the default value set for the digital filter function, it is not necessary to set the digital filter
                                                                                                                                             FX3G-2AD-BD
                   function in the sequence program.
                                                                                                                                             FX3U-4DA
                                                                                                                                           F
                                                                                                                                             FX3U-4DA-ADP
                                                                                                                                        G
FX3G-1DA-BD
                                                                                                                                         H
                                                                                                                                       FX3U-4AD-PT
                                                                                                                                                -ADP
                                                                                                                                                 I
                                                                                                                                       FX3U-4AD-PTW
                                                                                                                                                -ADP
                                                                                                                                           J
                                                                                                                                       FX3U-4AD-PNK
                                                                                                                                                -ADP
                                                                                                                            B-55
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                               7 Examples of Practical Programs
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                              7.2 Program That Uses Convenient Functions
       1. Conditions
         The sequence program described in this section is created under the following conditions.
         1) System configuration
            The FX3U-4AD (unit No.0) should be connected to the FX3U Series PLC.
         2) Input mode
            Channels 1 and 2 should be set to mode 0 (voltage input, -10V to +10V → -32000 to +32000).
            Channels 3 and 4 should be set to mode 3 (current input, 4mA to 20mA → 0 to 16000).
         3) Averaging time
            For all the channels, the averaging time should be set to "1" (default).
            (To use the default value, it is not necessary to set the averaging time in the sequence program.)
         4) Digital filter function
            For all channels, the digital filter function should be disabled (default).
            (To use the default value, it is not necessary to set the digital filter function in the sequence program.)
         5) Convenient functions
            The upper/lower limit detection function, upper/lower limit error status data automatic transfer function,
            over-scale status data automatic transfer function, and error status data automatic transfer function
            should be used.
         6) Device assignment
                           Device                                                   Description
                                     X000        Clearance of upper/lower limit error data
                   Input
                                     X001        Clearance of over-scale data
                                     Y000        Output of channel-1 lower limit error data
                                     Y001        Output of channel-1 upper limit error data
                                     Y002        Output of channel-2 lower limit error data
                                     Y003        Output of channel-2 upper limit error data
                                     Y004        Output of channel-3 lower limit error data
                                     Y005        Output of channel-3 upper limit error data
                                     Y006        Output of channel-4 lower limit error data
                                     Y007        Output of channel-4 upper limit error data
                                     Y010        Output of channel-1 over-scale (lower limit) data
                                     Y011        Output of channel-1 over-scale (upper limit) data
                                     Y012        Output of channel-2 over-scale (lower limit) data
                                     Y013        Output of channel-2 over-scale (upper limit) data
                  Output             Y014        Output of channel-3 over-scale (lower limit) data
                                     Y015        Output of channel-3 over-scale (upper limit) data
                                     Y016        Output of channel-4 over-scale (lower limit) data
                                     Y017        Output of channel-4 over-scale (upper limit) data
                                     Y20         Output of error detection signal
                                     Y21         Output of setting error detection signal
                                      D0         A/D converted digital value of channel 1
                                      D1         A/D converted digital value of channel 2
                                      D2         A/D converted digital value of channel 3
                                      D3         A/D converted digital value of channel 4
                                     D100        Upper/lower limit error status data automatic transfer-to data register
                                     D101        Over-scale status data automatic transfer-to data register
                                     D102        Error status data automatic transfer-to data register
B-56
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                           7 Examples of Practical Programs
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                           7.2 Program That Uses Convenient Functions
                                                                                                                                     A
      2. Example of sequence program
                                                                                                                                         Common Items
         • For FX3U, FX3UC Series PLCs
         Initial pulse
            M8002
                                      FNC 12                       Input modes of channels 1 to 4 will be
         RUN monitor                   MOV P
                                                H3300     U0\G0    specified. *2                                                     B
           M8000
                                                                                                                                   FX3UC-4AD
                                                                                                                                   FX3U-4AD
                                                 T0     K50 *1
            T0
                                      FNC 12    H01A2    U0\G22    The convenient functions will be set. *2
                                       MOV P
                                                                                                                                         FX3U-4AD-ADP
                                      FNC 12                       The over-scale status data automatic transfer-to data
                                                K101     U0\G128   register will be set to D101. *2
                                       MOV P
                                                                                                                                         FX3G-2AD-BD
                                       U0\G10    D0         K4
                              BMOV                                 to #13 into D0 to D3.
          Clearance of upper/lower
          limit error data
            X000
                                      FNC 12    H0003    U0\G99    Clearance of upper/lower limit error data
                                       MOV P
          Clearance of over-scale
          data
                                                                                                                                      E
                                                                                                                                         FX3U-4DA
           X001
                                      FNC 12     K0      U0\G28    Clearance of over-scale data
                                       MOV P
          RUN monitor
          M8000
                                      FNC 12
                                       MOV
                                                D100     K2Y000
                                                                   The upper/lower limit error status data of each channel
                                                                   will be output to Y000 to Y007.                                     F
                                                                                                                                         FX3U-4DA-ADP
                                      FNC 12                       The over-scale status data of each channel will be output
                                                D101     K2Y010    to Y010 to Y017.
                                       MOV
         Error detection
         D102.0
                                                Y020               The error detection signal will be output to Y020.
                                                                                                                                    G
         Setting error detection
                                                                                                                                         FX3G-1DA-BD
         D102.8
                                                Y021               The setting error detection signal will be output to Y021.
          *1.    After setting the input mode, set the data writing time (waiting time) to 5 seconds or more for each
                 setting.
                                                                                                                                     H
                                                                                                                                   FX3U-4AD-PT
                 After this, if the same input mode is used, it is not necessary to set the input mode and waiting time
                 (T0 K50) again.
          *2.    The set input mode, convenient functions, upper/lower limit error status data automatic transfer-to
                                                                                                                                            -ADP
                 data register number, over-scale status data automatic transfer-to data register number, and error
                 status data automatic transfer-to data register number are retained in the 4AD EEPROM. For this
                 reason, even if the sequence program is deleted, the previously set functions will still be valid.
                                                                                                                                             I
                                                                                                                                   FX3U-4AD-PTW
                                                                                                                                            -ADP
                                                                                                                                       J
                                                                                                                                   FX3U-4AD-PNK
                                                                                                                                            -ADP
                                                                                                                        B-57
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                              7 Examples of Practical Programs
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                             7.2 Program That Uses Convenient Functions
    Initial pulse
       M8002
                         FNC 79                                       Input modes of channels 1 to 4 will be
                                    K0       K0     H3300      K1     specified. *2
    RUN monitor          TO P
      M8000
                                               T0   K50 *1
         T0
                         FNC 79     K0       K22    H01A2      K1     The convenient functions will be set. *2
                         TO P
       RUN monitor
       M8000
                                         FNC 12                       The upper/lower limit error status data of each channel
                                                     D100    K2Y000   will be output to Y000 to Y007.
                                          MOV
              *1.   After setting the input mode, set the data writing time (waiting time) to 5 seconds or more for each
                    setting.
                    After this, if the same input mode is used, it is not necessary to set the input mode and waiting time
                    (T0 K50) again.
              *2.   The set input mode, convenient functions, upper/lower limit error status data automatic transfer-to
                    data register number, over-scale status data automatic transfer-to data register number, and error
                    status data automatic transfer-to data register number are retained in the 4AD EEPROM. For this
                    reason, even if the sequence program is deleted, the previously set functions will still be valid.
B-58
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                              7 Examples of Practical Programs
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                             7.3 Program That Uses Data History Function
                                                                                                                                        A
7.3      Program That Uses Data History Function
                                                                                                                                            Common Items
         This section describes a program that uses the data history function of the 4AD.
      1. Conditions
         The sequence program described in this section is created under the following functions.                                       B
         1) System configuration
                                                                                                                                      FX3UC-4AD
                                                                                                                                      FX3U-4AD
            The FX3U-4AD (unit No.0) should be connected to the FX3U Series PLC.
         2) Input mode
            Channels 1 and 2 should be set to mode 0 (voltage input, -10V to +10V → -32000 to +32000).
            Channels 3 and 4 should be set to mode 3 (current input, 4mA to 20mA → 0 to 16000).
         3) Averaging time                                                                                                              C
                                                                                                                                            FX3U-4AD-ADP
            For all the channels, the averaging time should be set to "1" (default).
            (To use the default value, it is not necessary to set the averaging time in the sequence program.)
         4) Digital filter function
            For all channels, the digital filter function should be disabled (default).
            (To use the default value, it is not necessary to set the digital filter function in the sequence program.)
         5) Data history function
                                                                                                                                        D
                                                                                                                                            FX3G-2AD-BD
            For all channels, the data sampling time should be set to 100 ms.
            The sampling cycle should be 100 ms × 4 (number of selected channels) = 400 ms.
            For all channels, data will be sampled 100 times, and the sampled data will be stored as data history in
            the data registers.
         6) Device assignment
                           Device                                      Description
                                                                                                                                         E
                                                                                                                                            FX3U-4DA
                                     X000        Clearance of data history
                   Input
                                     X001        Temporarily stoppage of data history
                                      D0         A/D converted digital value of channel 1
                                      D1         A/D converted digital value of channel 2
                                      D2         A/D converted digital value of channel 3                                                 F
                                                                                                                                            FX3U-4DA-ADP
                                      D3         A/D converted digital value of channel 4
               Data register
                                D100 to D199     Channel-1 data history(100 data samples)
                                D200 to D299     Channel-2 data history(100 data samples)
                                D300 to D399     Channel-3 data history(100 data samples)
                                D400 to D499     Channel-4 data history(100 data samples)                                              G
FX3G-1DA-BD
                                                                                                                                        H
                                                                                                                                      FX3U-4AD-PT
                                                                                                                                               -ADP
                                                                                                                                                I
                                                                                                                                      FX3U-4AD-PTW
                                                                                                                                               -ADP
                                                                                                                                          J
                                                                                                                                      FX3U-4AD-PNK
                                                                                                                                               -ADP
                                                                                                                          B-59
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                            7 Examples of Practical Programs
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                            7.3 Program That Uses Data History Function
            Initial pulse
               M8002
                                        FNC 12                        Input modes of channels 1 to 4 will be
                                                   H3300     U0\G0    specified. *2
            RUN monitor                  MOV P
             M8000
                                                    T0     K50 *1
                T0
                                        FNC 12     K100     U0\G198   The sampling time will be set to 100 ms.
                                                                                                                 *2
                                         MOV P
                T0
                               FNC 15                                 Channel-1 history data (100 data samples)
                                        U0\G200    D100       K100    will be read out to D100 to D199.
                                BMOV
          *1.    After setting the input mode, set the data writing time (waiting time) to 5 seconds or more for each
                 setting.
                 After this, if the same input mode is used, it is not necessary to set the input mode and waiting time
                 (T0 K50) again.
          *2.    The set input mode and the sampling time are retained in the 4AD EEPROM. Therefore, even if the
                 sequence program is deleted, the previously set functions will still be valid.
          *3.    If a large amount of history data is read out, the scan time of the PLC will be become longer. If the
                 scan time exceeds 200 ms, the CPU error indicator lamp will illuminate, and the PLC will stop.
                 Insert WDT instruction (watchdog timer refresh) between BMOV instructions.
B-60
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                           7 Examples of Practical Programs
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                          7.3 Program That Uses Data History Function
                                                                                                                                     A
         • For FX3G, FX3U, FX3UC Series PLCs
                                                                                                                                         Common Items
             Initial pulse
                M8002
                                   FNC 79    K0       K0     H3300     K1       Input modes of channels 1 to 4 will be
                                   TO P                                         specified. *2
             RUN monitor
              M8000
                                                      T0    K50 *1                                                                   B
                                                                                                                                   FX3UC-4AD
                                                                                                                                   FX3U-4AD
                  T0
                                   FNC 79    K0     K198      K100     K1       The sampling time will be set to 100 ms.
                                                                                                                           *2
                                   TO P
                                                                                                                                         FX3U-4AD-ADP
                                   FNC 79    K0     K199     H000F     K1       Data history of all the channels will be
                                   TO P                                         erased.
                Temporarily stop
                data history
                 X001
                                   FNC 79    K0     K199     H0F00     K1       Data history of all the channels will be
                                                                                temporarily stopped.
                                                                                                                                     D
                                   TO P
                Temporarily stop
                data history
                                                                                                                                         FX3G-2AD-BD
                 X001
                                   FNC 79           K199     H0000     K1       Temporary stoppage of data history will be
                                             K0                                 canceled for all the channels.
                                   TO P
                  T0
                                   FNC 79
                                   TO
                                             K0     K200      D100    K100      Channel-1 history data (100 data samples)
                                                                                will be read out to D100 to D199.                     E
                                                                                                                                         FX3U-4DA
                                                    FNC 07                      The watchdog timer will be refreshed. *3
                                                     WDT
                                                                                                                                         FX3U-4DA-ADP
                                                     WDT
                                                                                                                                         FX3G-1DA-BD
                                   FNC 79    K0     K4300     D400    K100      Channel-4 history data (100 data samples)
                                   TO                                           will be read out to D400 to D499.
                  setting.
                  After this, if the same input mode is used, it is not necessary to set the input mode and waiting time
                  (T0 K50) again.
                                                                                                                                            -ADP
          *2.     The set input mode and the sampling time are retained in the 4AD EEPROM. Therefore, even if the
                  sequence program is deleted, the previously set functions will still be valid.                                             I
          *3.     If a large amount of history data is read out, the scan time of the PLC will be become longer. If the
                                                                                                                                   FX3U-4AD-PTW
                  scan time exceeds 200 ms, the CPU error indicator lamp will illuminate, and the PLC will stop.
                  Insert WDT instruction (watchdog timer refresh) between BMOV instructions.
                                                                                                                                            -ADP
                                                                                                                                       J
                                                                                                                                   FX3U-4AD-PNK
                                                                                                                                            -ADP
                                                                                                                        B-61
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                7 Examples of Practical Programs
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                           7.4 Initialization Program for 4AD (Factory Default)
       1. Conditions
         The sequence program described in this section runs under the following conditions.
         1) System configuration
            The FX3U-4AD (unit No.0) should be connected to the FX3U Series PLC.
         2) Device assignment
                  Device                Description
                   X000         4AD initialization command
       3. Cautions
         • It takes approximately 5 seconds to complete initialization.
           Do not write any data to the buffer memory in this time.
         • When initialization is complete, the value of BFM #20 will be reset to "K0".
         • Priority is given to the data change disable (BFM #19). To initialize, write K2080 to BFM #19.
B-62
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                8 Troubleshooting
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                        8.1 PLC Version Number Check
                                                                                                                                        Common Items
8.     Troubleshooting
         This chapter describes troubleshooting methods and error codes.                                                            B
         If the A/D conversion data is not input, or if the proper digital value is not input, check the following items:
                                                                                                                                  FX3UC-4AD
                                                                                                                                  FX3U-4AD
         • PLC version number
         • Wiring
         • Program
         • Error status                                                                                                             C
                                                                                                                                        FX3U-4AD-ADP
8.1      PLC Version Number Check
         Verify that the PLC being used is of the following version or later.
FX3U-4AD D
                                                                                                                                        FX3G-2AD-BD
           Compatible PLC           Version number
           FX3U Series PLC           Ver. 2.20 or later
           FX3UC Series PLC          Ver. 1.30 or later
           FX3G Series PLC           Ver. 1.00 or later
                                                                                                                                     E
         FX3UC-4AD
                                                                                                                                        FX3U-4DA
           Compatible PLC           Version number
           FX3UC Series PLC          Ver. 1.30 or later
                              → For a detailed description of version number check method, refer to Section 1.3.
                                                                                                                                      F
                                                                                                                                        FX3U-4DA-ADP
8.2      Wiring Check
         Check the wiring as follows:
      1. Power
         The 4AD needs driving power. Verify that the power supply line is properly connected. Also check that the 24              G
                                                                                                                                        FX3G-1DA-BD
         V indicator lamp of the 4AD is on.
         To use the current input mode for a channel, be sure to short-circuit the line between the V+ terminal and the
         I+ terminal of the channel.
         Without short circuiting the terminals, it is impossible to obtain the correctly converted digital values.
                                                                                                                                           -ADP
                                                                                                                                            I
8.3      Program Check
                                                                                                                                  FX3U-4AD-PTW
      1. Storage devices
         Check whether the device holding digital values contains any values written by other programs.
                                                                                                                                      J
      2. Setting of averaging time and digital filter function
                                                                                                                                  FX3U-4AD-PNK
         Check if the averaging time or the digital filter function is set for the same channel. It is not possible to set both
         functions for the same channel.
                                                                                                                                           -ADP
                                                                                                                       B-63
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                   8 Troubleshooting
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                                                  8.4 Error Status Check
B-64
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                            8 Troubleshooting
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                                             8.5 4AD Initialization and Test Program
                                                                                                                                    A
      8. Digital filter setting error (b11)
                                                                                                                                        Common Items
         1) Description of error
            The digital filter value (BFM #6 to #9) is not set correctly.
         2) Remedy
            Set the digital filter value again in the range from 0 to 1600.
            Also check that the averaging is not set for the selected channel.                                                      B
                                                                                                                                  FX3UC-4AD
                                                                                                                                  FX3U-4AD
      9. Abrupt change detection value setting error (b12)
         1) Description of error
            The abrupt change detection value (BFM #91 to #94) is not set correctly.
         2) Remedy
            Check that the abrupt change detection value is in the range specified for the selected input mode. If the              C
            value is out of the range, correct it.
                                                                                                                                        FX3U-4AD-ADP
      10. Upper/lower limit detection setting error (b13)
         1) Description of error
            The lower limit error detection value (BFM #71 to #74) or the upper limit error detection value (BFM #81 to
            #84) is not set correctly.                                                                                              D
         2) Remedy
                                                                                                                                        FX3G-2AD-BD
            Check that the upper/lower limit error detection value is in the range specified for the selected input
            mode. If the value is out of the range, correct it.
                                                                                                                                        FX3U-4DA
         2) Remedy
            Set the addition data again in the range from -16000 to +16000.
                                                                                                                                        FX3U-4DA-ADP
         If the remedies above cannot solve the problem, initialize and then check the conditions of the 4AD using the
         test program.
                             → For a detailed description of 4AD initialization program, refer to Subsection 7.4.
                                             → For a detailed description of the test program, refer to Chapter 4.
FX3G-1DA-BD
                                                                                                                                    H
                                                                                                                                  FX3U-4AD-PT
                                                                                                                                           -ADP
                                                                                                                                            I
                                                                                                                                  FX3U-4AD-PTW
                                                                                                                                           -ADP
                                                                                                                                      J
                                                                                                                                  FX3U-4AD-PNK
                                                                                                                                           -ADP
                                                                                                                      B-65
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                 8 Troubleshooting
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)                  8.5 4AD Initialization and Test Program
MEMO
B-66
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4AD-ADP (4-channel analog Input)
                                                                                                                                       Common Items
                                                                                                                                   B
                                                                                                                                 FX3UC-4AD
                                                                                                                                 FX3U-4AD
         FX3G/FX3U/FX3UC Series Programmable
         Controllers                                                                                                               C
                                                                                                                                       FX3U-4AD-ADP
         User's Manual [Analog Control Edition]
         FX3U-4AD-ADP (4-channel analog Input)
                                                                                                                                   D
                                                                                                                                       FX3G-2AD-BD
                                                                                                                                    E
                                                                                                                                       FX3U-4DA
                                                                                                                                     F
                                                                                                                                       FX3U-4DA-ADP
                                                                                                                                  G
FX3G-1DA-BD
                                                                                                                                   H
                                                                                                                                 FX3U-4AD-PT
         Foreword
                                                                                                                                          -ADP
         This manual describes the specifications, wiring, and operation methods for the FX3U-4AD-ADP special
         adapter (4-channel analog input) and should be read and understood before attempting to install or use the
         unit.                                                                                                                             I
         Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
                                                                                                                                 FX3U-4AD-PTW
           This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
           licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
           rights which may occur as a result of using the contents noted in this manual.                                            J
                                                                                                                                 FX3U-4AD-PNK
                                                                                                                         C-1
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4AD-ADP (4-channel analog Input)
C-2
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                   1 Outline
FX3U-4AD-ADP (4-channel analog Input)                                                                         1.1 Outline of Functions
                                                                                                                                               Common Items
1.      Outline
          This chapter outlines the FX3U-4AD-ADP (referred to as the 4AD-ADP).                                                             B
                                                                                                                                         FX3UC-4AD
                                                                                                                                         FX3U-4AD
1.1       Outline of Functions
          The FX3U-4AD-ADP is an analog special adapter. Connect the FX3U-4AD-ADP to the FX3U/FX3UC/FX3G
          Series PLC to read 4 channels of voltage/current data.
                                                                                                                                           C
                                                                                                                                               FX3U-4AD-ADP
          1) Up to 4 4AD-ADP units can be connected to the FX3U/FX3UC Series PLC.
             Up to 2*1 4AD-ADP units can be connected to the FX3G Series PLC.
             (including the other analog special adapters).
          2) Either "voltage input" or "current input" can be specified for each channel.
          3) A/D conversion data of each channel will be automatically written to the special data register of the FX3U/                   D
             FX3UC/FX3G Series PLC.
                                                                                                                                               FX3G-2AD-BD
                                                System                                                     Point and section to be
                                                                                                                 referred to
                                                                                                                                               FX3U-4DA
                                                                                                          units
                                                                    FX3U/FX3UC/FX3G Series PLC
                                                                                                                                               FX3U-4DA-ADP
                                                             *2
         4th       3rd       2nd       1st     Expansion board
       adapter   adapter   adapter   adapter
  Refer to the system configuration shown in the User's Manual - Hardware Edition to check the number of connectable units                         I
  and to configure the entire system.
                                                                                                                                         FX3U-4AD-PTW
  *1.Only 1 analog special adapter can be connected to the 14-point and 24-point type main unit.
                                                                                                                                                  -ADP
  *2.The expansion board is not required when connecting with the FX3UC (D, DSS) PLC.
     For the FX3G Series PLC a connector conversion adapter is used.
                                                                                                                                             J
                                                                                                                                         FX3U-4AD-PNK
                                                                                                                                                  -ADP
                                                                                                                                  C-3
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                         1 Outline
FX3U-4AD-ADP (4-channel analog Input)                                        1.2 Setup Procedure Before Starting Operation
FX3U-4AD-ADP
Refer to Chapter 1.
                               Wiring                                    Wiring:
                                                                         • Selection of sensor cable
                                                                         • Power supply line
                                         Refer to Chapter 4.             • Analog input line
                           Programming                                   Programming:
                                                                         • Details of special devices
                                                                         • Examples of basic programs
                                         Refer to Chapter 5.
C-4
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                           1 Outline
FX3U-4AD-ADP (4-channel analog Input)                                                                  1.3 Connectable PLCs and Version Number
                                                                                                                                                   A
1.3      Connectable PLCs and Version Number
                                                                                                                                                       Common Items
         The 4AD-ADP is compatible with the following PLCs.
                                                                                                                                                 FX3UC-4AD
                                                                                                                                                 FX3U-4AD
          FX3UC Series PLC                                   Ver.1.20 or later                After April 2004
          FX3G Series PLC                                    Ver.1.00 or later                After June 2008 (initial production)
1. Version check C
                                                                                                                                                       FX3U-4AD-ADP
         Special data register D8001 contains information for determining the PLC version number.
                            D8001                2     4        1       0        0
                       PLC type and
                      version number                                            Version data (Example: Ver. 1.00)
                                                                                                                                                   D
                                                                        (
                                                        PLC type Example: 24 = FX3U and FX3UC series
                                                                                                                      (
                                                                                                                                                       FX3G-2AD-BD
                                                                          26 = FX3G series
                                                                                                                                                       FX3U-4DA
                                                     FX3U-48MR/ES(production number : 570001)
                                                       MODEL            FX3U-48MR/ES
                                                                 100-240VAC 50/60Hz 40W
                                                           OUT:30VDC/240VAC 2A(COSφ=1)                                                               F
                                                                                                                                                       FX3U-4DA-ADP
                                                       SERIAL                        570001
5 7 0 0 0 1 G
                                                                                                                                                       FX3G-1DA-BD
                                                                                          Control number
                                                                             Month (Example: 7 = July), 1 to 9 = January to September,
                                                                             X = October, Y = November, Z = December
                                                                        Year (Example: 5 = 2005), last digit of dominical year
                                                                                                                                                   H
1.4      Compatible Programming Tool Version Number
                                                                                                                                                 FX3U-4AD-PT
         Use the programming tool with following version numbers to create programs for the 4AD-ADP:
                                                                                                                                                          -ADP
         If a programming tool with the wrong version number is used, programming will not be possible.
          *1.   For Ver. 8.13P to 8.24A of GX Developer, select FX3UC for the PLC type.
                                                                                                                                                     J
                                                                                                                                                 FX3U-4AD-PNK
                                                                                                                                                          -ADP
                                                                                                                                        C-5
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                         2 Specifications
FX3U-4AD-ADP (4-channel analog Input)                                                                       2.1 Generic Specifications
2.     Specifications
         This chapter describes the general, power supply, and performance specifications for the 4AD-ADP.
                Item                                                       Specifications
          Ambient            0 to 55°C (32 to 131°F) when operating
          temperature        -25 to 75°C (-13 to 167°F) when stored
          Relative
                             5 to 95%RH (no condensation) when operating
          humidity
                                                    Frequency            Acceleration      Half amplitude
                                                       (Hz)                 (m/s2)              (mm)
                                                                                                            Tests 10 times in each
          Vibration                                      10 - 57              -                0.035        direction (X-, Y-, and Z-
                             DIN Rail Mounting
          resistance                                 57 - 150                4.9                    -       axis directions) (Total:
                                                                                                            80 min, each)
                                                     10 to 57                 −                0.075
                             Direct Mounting*1
                                                     57 to 150               9.8                    −
          Shock
                             147 m/s2 Acceleration, Action time: 11ms, 3 times by half-sine pulse in each direction X, Y, and Z
          resistance
          Noise              Using noise simulator of:
          resistance         Noise voltage: 1,000Vp-p / Noise width: 1µs / Rise: 1ns / Cycle: 30 to 100Hz
          Dielectric
          withstand          500 V AC, for 1 min
          voltage                                                   Between all terminals and ground terminal
          Insulation         5MΩ or more using 500V DC
          resistance         insulation resistance meter
                             Class D grounding (grounding resistance: 100 Ω or less)
          Grounding
                             <Common grounding with a heavy electrical system is not allowed.>*2
          Working
                             Free from corrosive or flammable gas and excessive conductive dusts
          environment
          Working
                             < 2000m*3
          altitude
*1. If 4AD-ADP is connected to the FX3UC Series PLC, direct installation is not possible.
          *2.
                       PLC        Other            PLC         Other          PLC         Other
                                equipment                    equipment                  equipment
C-6
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                               2 Specifications
FX3U-4AD-ADP (4-channel analog Input)                                                                                        2.2 Power Supply Specifications
                                                                                                                                                                 A
2.2      Power Supply Specifications
                                                                                                                                                                     Common Items
                        Item                                                              Specifications
          A/D conversion circuit                         24V DC +20%-15%, 40mA                                                                                   B
          driving power                                  (It is necessary to connect a 24V DC power supply to the terminal block.)
                                                                                                                                                               FX3UC-4AD
                                                                                                                                                               FX3U-4AD
                                                         5V DC, 15mA
          Interface driving power                        (Since the internal power is supplied from the FX Series main unit, it is not
                                                         necessary to supply the power.)
                                                                                                                                                                     FX3U-4AD-ADP
                                                                                        Specifications
                 Item
                                                              Voltage input                                                Current input
                                                                                                                                                                 D
          Analog input                                          0V to 10V DC                                              4mA to 20mA DC
                                                                                                                                                                     FX3G-2AD-BD
          range                                          (Input resistance: 194 kΩ)                                   (Input resistance: 250 Ω)
          Absolute input
                                                                -0.5V, +15V                                                -2mA, +30mA
          maximum
          Digital output                                       12 bits, binary                                             11 bits, binary
          Resolution                                        2.5mV (10V/4000)                                             10µA (16mA/1600)                         E
                               • ±0.5% (±50mV) for 10V full scale          • ±0.5% (±80µA) for 16mA full scale
                                                                                                                                                                     FX3U-4DA
                                 (when ambient temperature is 25°C ± 5°C)    (when ambient temperature is 25°C ± 5°C)
          Total accuracy
                               • ±1.0% (±100mV) for 10V full scale         • ±1.0% (±160µA) for 16mA full scale
                                 (when ambient temperature is 0°C to 55°C)   (when ambient temperature is 0°C to 55°C)
                               • FX3U/ FX3UC Series PLC : 200 µs (The data will be updated at every scan time.)
          A/D conversion
          time
                               • FX3G Series PLC : 250 µs (The data will be updated at every scan time.)                                                           F
                                                                     → For a detailed description of data update, refer to Section 2.4.
                                                                                                                                                                     FX3U-4DA-ADP
                                     4080                                                            1640
                                     4000                                                            1600
                                                                                                                                                                G
                                                                                                                                                                     FX3G-1DA-BD
          Input
                                                                                                    Digital output
                                    Digital output
characteristics
                            • The photocoupler is used to insulate the analog input area from the PLC.
          Insulation method • The DC/DC converter is used to insulate the power supply line from the analog input area.
                                                                                                                                                                        -ADP
                                                                                                                                                                   J
                                                                                                                                                               FX3U-4AD-PNK
                                                                                                                                                                        -ADP
                                                                                                                                                     C-7
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                     2 Specifications
FX3U-4AD-ADP (4-channel analog Input)                                                                     2.4 A/D Conversion Time
                                                                                          Sequence
                                                                                           program
                                                            A/D conversion start
                                                 A/D             command
                                              conversion
                                                            Digital value writing
                                              200µs/4ch
                                                            A/D conversion start        END instruction
                        A/D                                      command
                     conversion
                                                            Digital value writing
                     200µs/4ch
C-8
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                               2 Specifications
FX3U-4AD-ADP (4-channel analog Input)                                                               2.4 A/D Conversion Time
                                                                                                                                A
2.4.2     When connected to a FX3G PLC
                                                                                                                                    Common Items
        1. A/D conversion and special data register update timing
          A/D conversion is performed at every scan time of the PLC.
          During execution of END instruction, the PLC performs A/D conversion, reads out the A/D converted data,
          and then writes the data in the special data registers.                                                               B
                                                                                                                              FX3UC-4AD
                                                                                                                              FX3U-4AD
                  FX3U-4AD-ADP            FX3U-4AD-ADP
                       2nd                     1st                                FX3G Series PLC
                                                                                                                                C
                                                                                     Sequence
                                                                                      program
                                                          A/D conversion start
                                                                                                                                    FX3U-4AD-ADP
                                                A/D            command
                                             conversion
                                                          Digital value writing
                                             250µs/4ch
                                                          A/D conversion start    END instruction
                       A/D
                    conversion
                                                               command
                                                                                                                                D
                                                                                                                                    FX3G-2AD-BD
                                                          Digital value writing
                    250µs/4ch
                                                                                                                                    FX3U-4DA
        3. If two analog special adapters are connected
          During execution of the END instruction, data will be read out from all the connected adapters (in the order of
          1st adapter → 2nd adapter).
                                                                                                                                    FX3U-4DA-ADP
          the data read out will be written to the special data registers.
          END instruction execution time will be "250µs × number of connected analog adapters."
FX3G-1DA-BD
                                                                                                                                H
                                                                                                                              FX3U-4AD-PT
                                                                                                                                       -ADP
                                                                                                                                        I
                                                                                                                              FX3U-4AD-PTW
                                                                                                                                       -ADP
                                                                                                                                  J
                                                                                                                              FX3U-4AD-PNK
                                                                                                                                       -ADP
                                                                                                                     C-9
FX3U/FX3UC Series PLC User's Manual - Analog Control Edition                                                            3 Wiring
FX3U-4AD-ADP (4-channel analog Input)
3.     Wiring
         This chapter describes the 4AD-ADP wiring.
         Observe the following caution to wire the 4AD-ADP.
WIRING PRECAUTIONS
          • Make sure to cut off all phases of the power supply externally before attempting wiring work.
            Failure to do so may cause electric shock or damages to the product.
WIRING PRECAUTIONS
          • Connect the DC power supply wiring to the dedicated terminals described in this manual.
            If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will be
            burnt out.
          • Do not wire vacant terminals externally.
            Doing so may damage the product.
          • Perform class D grounding (grounding resistance: 100Ω or less) to the grounding terminal on the main unit.
            Do not use common grounding with heavy electrical systems.
          • When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
            Failure to do so may cause fire, equipment failures or malfunctions.
          • Make sure to observe the following precautions in order to prevent malfunctions under the influence of noise:
            - Do not bundle the power line or twisted shielded cable together with or lay it close to the main circuit, high-
                voltage line, or load line.
                Otherwise, noise disturbance and/or surge induction are likely to take place. As a guideline, lay the control line
                at least 100mm (3.94") or more away from the main circuit, high-voltage line, or load line.
            - Ground the shield of the analog input/output cable at one point on the signal receiving side.
                However, do not use common grounding with heavy electrical systems.
          • Make sure to properly wire to the European terminal board in accordance with the following precautions.
            Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product.
            - The disposal size of the cable end should be 9 mm (0.35").
            - Tightening torque should be between 0.22 to 0.25 N•m.
            - Twist the end of strand wire and make sure there are no loose wires.
            - Do not solder-plate the electric wire ends.
            - Do not connect more than the specified number of wires or electric wires of unspecified size.
            - Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
C-10
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                         3 Wiring
FX3U-4AD-ADP (4-channel analog Input)                                                     3.1 Terminal Layout
                                                                                                                  A
3.1      Terminal Layout
                                                                                                                      Common Items
         The terminals of the 4AD-ADP are arranged as follows:
                                                                                                                  B
                           FX3U-4AD-ADP
                                                                                                                FX3UC-4AD
                                                                                                                FX3U-4AD
                                 POWER
                                                      Signal           Application
                                                       24+
                                                                                                                  C
                          24+
                                                                 External power
                                                       24-
                          24-
Grounding terminal
                                                                                                                      FX3U-4AD-ADP
                                                       V1+
                          VI+
                          I1+
                                                      COM1
                          V2+
                                                       V2+
                                                                 Channel 2 analog input                           D
                          I2+
                                                       I2+
                          COM2
COM2
                                                                                                                      FX3G-2AD-BD
                          V3+
                                                       V3+
                                                       I3+       Channel 3 analog input
                          I3+
                          COM3
                                                      COM3
                          V4+
                                                       V4+
                                                                 Channel 4 analog input
                          I4+
                                                       I4+
                                                                                                                   E
                          COM4
COM4
                                                                                                                      FX3U-4DA
                                                                                                                    F
                                                                                                                      FX3U-4DA-ADP
                                                                                                                 G
FX3G-1DA-BD
                                                                                                                  H
                                                                                                                FX3U-4AD-PT
                                                                                                                         -ADP
                                                                                                                          I
                                                                                                                FX3U-4AD-PTW
                                                                                                                         -ADP
                                                                                                                    J
                                                                                                                FX3U-4AD-PNK
                                                                                                                         -ADP
                                                                                                     C-11
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                3 Wiring
FX3U-4AD-ADP (4-channel analog Input)                                        3.2 Applicable Cables and Terminal Tightening Torque
       1. Cables
         Applicable cable and tightening torque
                           Wire size (stranded/       Tightening
                                                                                           Termination
                               single-wire)             torque
                         0.3mm2 to 0.5mm2                          • To connect a stranded cable, peel the cover off the cable
          Single-wire                                                and then twist the core before connection.
                         (AWG22 to 20)
                                                                   • To connect a single-wire cable, just strip the cover off the
          2-wire         0.3mm2(AWG22)                               cable before connection.
                                                      0.22N•m to • Rod terminal with insulation sleeve
          Rod terminal   0.3mm2 to 0.5mm2              0.25N•m     (recommended terminal)
          with           (AWG22 to 20)                             AI 0.5-8WH : Manufactured by Phoenix Contact
          insulation     (Refer to the rod terminal
                                                                 • Caulking tool
          sleeve         external view shown in the
                                                                   CRIMPFOX ZA 3 : Manufactured by Phoenix Contact
                         following figure.)
                                                                   (or CRIMPFOX UD 6 : Manufactured by Phoenix Contact)
       3. Tool
         • To tighten terminals, use a small-sized screwdriver whose head is straight and is not widened as shown in
           the figure to the right.
            Note:
            If the diameter of screwdriver grip is too small, tightening torque will not
                                                                                                                       The head
            be able to be achieved. Use the following recommended screwdriver or                                       should be
            an appropriate replacement (grip diameter: approximately 25mm).                                            straight.
                         Manufacturer                          Model
            Phoenix Contact                                 SZS 0.4×2.5                        0.4mm                  2.5mm
                                                                                               (0.01")                (0.09")
C-12
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                   3 Wiring
FX3U-4AD-ADP (4-channel analog Input)                                                                            3.3 Power Supply Line
                                                                                                                                           A
3.3      Power Supply Line
                                                                                                                                               Common Items
         Connect the 24V DC power supply line of the 4AD-ADP to the 24+ and 24- terminals of the terminal block.
                                                                                                                                         FX3UC-4AD
                                                                                                                                         FX3U-4AD
         1. To use an External power supply                          2. To use the 24V DC power of the PLC
                                                                                                                                               FX3U-4AD-ADP
                24- 24+                                                        24- 24+              0V 24V                                 D
                                                                                                                                               FX3G-2AD-BD
          Terminal
          block                                                       Terminal
                                                                      block
                                           Class-D                                                    Class-D
                      24V DC              grounding                                                  grounding
                                                                                                                                            E
                                                                                                                                               FX3U-4DA
         Caution regarding connection of the power supply line:
         • Ground the "    " terminal to a class-D grounded power supply line (100Ω or less) together with the
           grounding terminal of the PLC main unit.
         • For the timing of power-on/off when using an external power supply, see the following manual of the PLC
           to be connected.                                                                                                                  F
                                                   → Refer to the FX3G Series User's Manual - Hardware Edition.
                                                                                                                                               FX3U-4DA-ADP
                                                   → Refer to the FX3U Series User's Manual - Hardware Edition.
                                                                                                                                               FX3G-1DA-BD
                                           15V                                         block)
                                                                                            Power
                                                                                                                                           H
                                                                                                                                         FX3U-4AD-PT
                                                                            Class-D
                                                                           grounding
                                                                                                                                                  -ADP
24V DC
         • Ground the "    " terminal to a class-D grounded power supply line (100Ω or less) together with the
           grounding terminal of the PLC main unit.
                                                                                                                                                  -ADP
                                                                                                                              C-13
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                          3 Wiring
FX3U-4AD-ADP (4-channel analog Input)                                                                    3.4 Analog Input Line
                                                 *1                                  147kΩ          ch
                                                                   V +
                                                                           250Ω
                                                                   I +
                                                                                     47kΩ
                                                                  COM
                                                       Class-D
                                                      grounding
          *1.   Use the 2-core shielded twisted pair cable for the analog input lines, and separate the analog input
                lines from other power lines or inductive lines.
          *2.   If "current input" is selected, be sure to short the line between the V + terminal and the I + terminal.
                ( : Channel number).
3.5      Grounding
         Grounding should be performed as stated below.
         • The grounding resistance should be 100Ω or less.
         • Independent grounding should be performed for best results.
           When independent grounding is not performed, perform "shared grounding" as shown in the following
           figure.
                               → For details, refer to the User’s Manual - Hardware Edition of the PLC Series.
C-14
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                 4 Programming
FX3U-4AD-ADP (4-channel analog Input)                                                      4.1 Loading of A/D Conversion Data
                                                                                                                                      Common Items
4.     Programming
         This chapter describes how to create programs that can read analog data using the 4AD-ADP.                               B
                                                                                                                                FX3UC-4AD
                                                                                                                                FX3U-4AD
4.1      Loading of A/D Conversion Data
         1) The input analog data will be converted into digital data and then stored in the special devices of the
            FX3U/FX3UC/FX3G Series PLC.
                                                                                                                                  C
         2) If the data is stored in the special devices, the averaging time can be set, and the input mode can be
                                                                                                                                      FX3U-4AD-ADP
            specified.
         3) Special auxiliary relays (10 points) and special data registers (10 points) are assigned automatically
            starting from the adapter nearest to the main unit.
                                 → For a detailed description of special device assignment, refer to Section 4.2.
         • FX3U, FX3UC Series PLC                                                                                                 D
                                                                                                                                      FX3G-2AD-BD
                                   Communic          High-speed
      FX3U-4AD FX3U-4AD FX3U-4AD     -ation FX3U-4AD input/output
        -ADP     -ADP     -ADP      special   -ADP     special
                                    adapter            adapter                     FX3U/FX3UC Series PLC
                                                                                                                                      FX3U-4DA
                                                A/D                     Special data registers:
                                                                           D8260 to D8269
                                                                                                                                      FX3U-4DA-ADP
                                                                        Special auxiliary relays:
                                                                          M8280 to M8289
                   A/D                                                  Special data registers:
                                                                          D8280 to D8289.
                                                                                                                                      FX3G-1DA-BD
            The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the
            next adapter as the 2nd analog special adapter, and so on. However, in this case, do not include the high-
            speed input/output special adapter and the communication special adapter.                                             H
                                                                                                                                FX3U-4AD-PT
                                                                                                                                         -ADP
                                                                                                                                          I
                                                                                                                                FX3U-4AD-PTW
                                                                                                                                         -ADP
                                                                                                                                    J
                                                                                                                                FX3U-4AD-PNK
                                                                                                                                         -ADP
                                                                                                                     C-15
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                4 Programming
FX3U-4AD-ADP (4-channel analog Input)                                                     4.1 Loading of A/D Conversion Data
            The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the
            next adapter as the 2nd analog special adapter. However, in this case, do not include the connector
            conversion adapter and the communication special adapter.
          *1.   The second special adapter is not available in the 14-point and 24-point type main unit.
C-16
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                               4 Programming
FX3U-4AD-ADP (4-channel analog Input)                                                           4.2 List of Special Devices
                                                                                                                                A
4.2      List of Special Devices
                                                                                                                                    Common Items
         If the 4AD-ADP is connected, special devices will be assigned automatically as shown in the following table:
         • FX3U, FX3UC Series PLC
                                                                                                       R: Read / W: Write
            Special               Device number                                                                   Refer-
                                                                                                                                B
                                                                             Description              Attribute
                                                                                                                              FX3UC-4AD
                                                                                                                              FX3U-4AD
            device      1st       2nd       3rd        4th                                                        ence
                       M8260     M8270     M8280     M8290    Switches the input mode of channel 1      R/W
                       M8261     M8271     M8281     M8291    Switches the input mode of channel 2      R/W       Section
          Special                                                                                                   4.3
                       M8262     M8272     M8282     M8292    Switches the input mode of channel 3      R/W
          auxiliary
          relay        M8263     M8273     M8283     M8293    Switches the input mode of channel 4      R/W                     C
                                                                                                                                    FX3U-4AD-ADP
                      M8264 to M8274 to M8284 to M8294 to
                                                          Unused (Do not use.)                            -          -
                       M8269    M8279    M8289    M8299
                       D8260     D8270     D8280     D8290    Channel-1 input data                       R
                       D8261     D8271     D8281     D8291    Channel-2 input data                       R        Section
                                                                                                                    4.4
                       D8262
                       D8263
                                 D8272
                                 D8273
                                           D8282
                                           D8283
                                                     D8292
                                                     D8293
                                                              Channel-3 input data
                                                              Channel-4 input data
                                                                                                         R
                                                                                                         R
                                                                                                                                D
                                                                                                                                    FX3G-2AD-BD
                                                              Averaging time for channel-1 (Setting
                       D8264     D8274     D8284     D8294                                              R/W
                                                              range: 1 to 4095)
                                                                                                                                    FX3U-4DA
                                                              Averaging time for channel-4 (Setting
                       D8267     D8277     D8287     D8297                                              R/W
                                                              range: 1 to 4095)
                                                                                                                  Section
                       D8268     D8278     D8288     D8298    Error status                              R/W
                                                                                                                    4.6
                                                                                                                                    FX3U-4DA-ADP
                                                                                                                               G
FX3G-1DA-BD
                                                                                                                                H
                                                                                                                              FX3U-4AD-PT
                                                                                                                                       -ADP
                                                                                                                                        I
                                                                                                                              FX3U-4AD-PTW
                                                                                                                                       -ADP
                                                                                                                                  J
                                                                                                                              FX3U-4AD-PNK
                                                                                                                                       -ADP
                                                                                                                  C-17
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                            4 Programming
FX3U-4AD-ADP (4-channel analog Input)                                                                     4.3 Switching of Input Mode
C-18
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                 4 Programming
FX3U-4AD-ADP (4-channel analog Input)                                                                        4.4 Input Data
                                                                                                                                A
4.4      Input Data
                                                                                                                                    Common Items
                                                                                       Numeric data type: Decimal (K)
         The data converted by the 4AD-ADP will be stored in the special data registers.
         The special data registers that store the input data are shown in the following table:
                                                                                                                                B
         • FX3U, FX3UC Series PLC
                                                                                                                              FX3UC-4AD
                                                                                                                              FX3U-4AD
                            Special data register
                                                                                             Description
               1st          2nd               3rd          4th
             D8260         D8270          D8280           D8290          Stores the channel-1 input data
             D8261         D8271          D8281           D8291          Stores the channel-2 input data                        C
                                                                                                                                    FX3U-4AD-ADP
             D8262         D8272          D8282           D8292          Stores the channel-3 input data
             D8263         D8273          D8283           D8293          Stores the channel-4 input data
                                                                                                                                    FX3G-2AD-BD
                                                           Description
               1st          2nd
             D8280         D8290       Stores the channel-1 input data
             D8281         D8291       Stores the channel-2 input data
             D8282         D8292       Stores the channel-3 input data
                                                                                                                                 E
             D8283         D8293       Stores the channel-4 input data
                                                                                                                                    FX3U-4DA
         The converted A/D immediate data or averaged data (data average conforming to the specified averaging
         time) will be stored in the above data registers as the input data.
                                           → For a detailed description of the averaging time, refer to Section 4.5.
                                                                                                                                    FX3U-4DA-ADP
         Input data is for reading only.
         Do not change (rewrite) the input data using sequence program, indicator, or device monitor of the
         programming tool.
                                                                                                                                    FX3G-1DA-BD
           M8000                                                    Stores the channel-1 input data
                                     FNC 12     D8260    D100
                                      MOV                           of the 1st analog special
          Normally                                                  adapter in the D100.
          ON
         Even if the input data is not stored in D100 or D101, data registers D8260 or D8261 can be directly used in
         the timer/counter set value or in a PID instruction.
                                                                                                                                       -ADP
                                                                                                                                        I
                                                                                                                              FX3U-4AD-PTW
                                                                                                                                       -ADP
                                                                                                                                  J
                                                                                                                              FX3U-4AD-PNK
                                                                                                                                       -ADP
                                                                                                                   C-19
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                 4 Programming
FX3U-4AD-ADP (4-channel analog Input)                                                                     4.5 Averaging Time
C-20
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                4 Programming
FX3U-4AD-ADP (4-channel analog Input)                                                                                          4.6 Error Status
                                                                                                                                                    A
4.6      Error Status
                                                                                                                                                        Common Items
         If an error is detected in the 4AD-ADP, the error status data will be stored in the corresponding special data
         register.
         The following table shows the special data registers that store the error status data:
         • FX3U, FX3UC Series PLC                                                                                                                   B
                                                                                                                                                  FX3UC-4AD
                                                                                                                                                  FX3U-4AD
                                  Special data register
                                                                                                      Description
                1st                2nd           3rd               4th
             D8268               D8278          D8288             D8298       Stores the error status data.
                                                                                                                                                    C
         • FX3G Series PLC
                                                                                                                                                        FX3U-4AD-ADP
             Special data register
                                                                   Description
                1st                2nd
             D8288               D8298      Stores the error status data.
                                                                                                                                                    D
                                                                                                                                                        FX3G-2AD-BD
         Check the ON/OFF status of each bit of the error status data register to check the description of the error.
         Errors are assigned to the bits as shown in the following table. Create a program to detect errors.
                                              → For a detailed description of the error status, refer to Section 6.5.
                                                                                                                                                        FX3U-4DA
                 b1             Channel-2 over-scale detection                   b6        4AD-ADP hardware error
                 b2             Channel-3 over-scale detection                   b7        4AD-ADP communication data error
                 b3             Channel-4 over-scale detection                b8 to b15    Unused
                 b4             EEPROM error                                      -                                 -
                                                                                                                                                      F
      1. Caution regarding use of error status data
                                                                                                                                                        FX3U-4DA-ADP
         If a 4AD-ADP hardware error (b6) or 4AD-ADP communication data error (b7) is detected, it is necessary to
         clear the error status with a program at the next power-on of the PLC.
         For this reason, be sure to create the following program:
         • For FX3G, FX3U, FX3UC Series PLC
                  M8000
                                                                                                                                                   G
                                                                                                                                                        FX3G-1DA-BD
                                              MOV         D8288      K4M0
                Normally ON
                  M8002                                                                              *1
                                                                                  Error status of 3rd analog special adapter
                                                          RST            M6       b6 = OFF (hardware error)
                Initial pulse
                                                          RST            M7
                                                                                                     *1
                                                                                  Error status of 3rd analog status register                        H
                                                                                  b7 = OFF (communication data error)
                                                                                                                                                  FX3U-4AD-PT
                  M8002
                                                                                  Error status of 1st analog special adapter
                                                          RST       D8268.6       b6 = OFF (hardware error)
                                                                                                                                                           -ADP
                Initial pulse
                                                                                  Error status of 1st analog status register
                                                          RST       D8268.7
                                                                                  b7 = OFF (communication data error)                                 J
                                                                                                                                                  FX3U-4AD-PNK
                                                                                                                                                           -ADP
                                                                                                                                      C-21
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                               4 Programming
FX3U-4AD-ADP (4-channel analog Input)                                                                     4.6 Error Status
                      M8000
                                      MOV      D8288     K4M0
                       M0
                                                             Y000   Detects over-scale in channel 1 of
                                                                    the 3rd *1 adapter.
                       M1
                                                             Y001   Detects over-scale in channel 2 of
                                                                    the 3rd *1 adapter.
                       M2
                                                             Y002   Detects over-scale in channel 3 of
                                                                    the 3rd *1 adapter.
                       M3
                                                             Y003   Detects over-scale in channel 4 of
                                                                    the 3rd *1 adapter.
                       M4
                                                             Y004   EEPROM error in 3rd *1 adapter
                       M5
                                                             Y005   Averaging time setting error in
                                                                    3rd *1 adapter
                       M6
                                                             Y006   Hardware error in 3rd *1 4AD-ADP
                       M7
                                                             Y007   Communication data error in 3rd *1
                                                                    4AD-ADP
                     D8268.2
                                                             Y002   Detects over-scale in channel 3 of
                                                                    the 1st adapter.
                     D8268.3
                                                             Y003   Detects over-scale in channel 4 of
                                                                    the 1st adapter.
                     D8268.4
                                                             Y004   EEPROM error in 1st adapter
                     D8268.5
                                                             Y005   Averaging time setting error in
                                                                    1st adapter
                     D8268.6
                                                             Y006   Hardware error in 1st 4AD-ADP
                     D8268.7
                                                             Y007   Communication data error in 1st
                                                                    4AD-ADP
C-22
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                               4 Programming
FX3U-4AD-ADP (4-channel analog Input)                                                                     4.7 Model Code
                                                                                                                             A
4.7      Model Code
                                                                                                                                 Common Items
                                                                                                    Initial value: K1
                                                                                     Numeric data type: Decimal (K)
         When the 4AD-ADP is connected, model code "1" is stored in the corresponding special data register.
         The following table shows the special data registers that store the model code:                                     B
                                                                                                                           FX3UC-4AD
                                                                                                                           FX3U-4AD
         • FX3U, FX3UC Series PLC
                              Special data register
                                                                                       Description
               1st            2nd               3rd      4th
             D8269           D8279             D8289   D8299        Model code
                                                                                                                             C
                                                                                                                                 FX3U-4AD-ADP
         • FX3G Series PLC
           Special data register
                                                        Description
             1st            2nd
            D8289       D8299         Model code                                                                             D
         Use the special data registers above to check whether a 4AD-ADP is connected or not.
                                                                                                                                 FX3G-2AD-BD
      1. Program Example (For FX3U, FX3UC Series PLC)
                   FNC224
                    LD =
                              D8269       K1                 Y007     Checks the model code of the 1st
                                                                      analog special adapter
                                                                                                                              E
                                                                                                                                 FX3U-4DA
                                                                                                                               F
                                                                                                                                 FX3U-4DA-ADP
                                                                                                                            G
FX3G-1DA-BD
                                                                                                                             H
                                                                                                                           FX3U-4AD-PT
                                                                                                                                    -ADP
                                                                                                                                     I
                                                                                                                           FX3U-4AD-PTW
                                                                                                                                    -ADP
                                                                                                                               J
                                                                                                                           FX3U-4AD-PNK
                                                                                                                                    -ADP
                                                                                                                C-23
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                  4 Programming
FX3U-4AD-ADP (4-channel analog Input)                                                               4.8 Basic Program Example
                      M8002
                                              RST        M6        Error status: b6 = OFF
                      Initial
                      pulse
                                              RST        M7        Error status: b7 = OFF
                      M8000
                                    FNC 12                         Sets the averaging time to "5"
                                                K5     D8284       for channel-1 data.
                                     MOV
         Even if the input data is not stored into D100 or D101, the data registers D8280 or D8281 can be directly used
         in the timer/counter setting value or in a PID instruction.
          *1.   "1st" for the FX3G PLC.
C-24
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                               4 Programming
FX3U-4AD-ADP (4-channel analog Input)                                                            4.8 Basic Program Example
                                                                                                                               A
         • For FX3U, FX3UC Series PLC
                                                                                                                                   Common Items
         The following program will set channel 1 of the 1st adapter to voltage input mode and channel 2 to current
         input mode, and will store the converted A/D value of channel-1 data into D100 and that of channel-2 data
         into D101.
                      M8001                                        Sets the input mode of channel
                                                        M8260      1 to the voltage input mode
                                                                   (0 V to 10 V).
                                                                                                                               B
                                                                                                                             FX3UC-4AD
                                                                                                                             FX3U-4AD
                      M8000                                        Sets the input mode of channel
                                                        M8261      2 to the current input mode
                                                                   (4 mA to 20 mA).
                      M8002
                                               RST     D8268.6     Error status: b6 = OFF
                                                                                                                               C
                                               RST     D8268.7     Error status: b7 = OFF
                                                                                                                                   FX3U-4AD-ADP
                      M8000
                                    FNC 12                         Sets the averaging time to "5"
                                                K5     D8264       for channel-1 data.
                                     MOV
                                                                                                                                   FX3G-2AD-BD
                                    FNC 12     D8260    D100       Stores the A/D converted
                                     MOV                           channel-1 digital data into D100.
         Even if the input data is not stored into D100 or D101, the data registers D8260 or D8261 can be directly used         E
         in the timer/counter setting value or in a PID instruction.
                                                                                                                                   FX3U-4DA
                                                                                                                                 F
                                                                                                                                   FX3U-4DA-ADP
                                                                                                                              G
FX3G-1DA-BD
                                                                                                                               H
                                                                                                                             FX3U-4AD-PT
                                                                                                                                      -ADP
                                                                                                                                       I
                                                                                                                             FX3U-4AD-PTW
                                                                                                                                      -ADP
                                                                                                                                 J
                                                                                                                             FX3U-4AD-PNK
                                                                                                                                      -ADP
                                                                                                                  C-25
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                5 Changing of Input Characteristics
FX3U-4AD-ADP (4-channel analog Input)                                                 5.1 Example: Changing of Voltage Input Characteristics
       1. Input characteristics
                                               Voltage input characteristics    Digital output value to be changed
                                               (product specifications)                Y-axis
                       Digital output
4000 10000
                                                                               Digital output to
                                                                               be calculated
                                                                               (D110)
                                        2000
400
                                           0                                                                         X-axis
                                                1V        5V             10V                       0 400(1V) 2000(5V)
                                                            Analog input
                                                                                                   Digital value actually obtained
                                                                                                   by A/D conversion
C-26
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                          5 Changing of Input Characteristics
FX3U-4AD-ADP (4-channel analog Input)                                  5.1 Example: Changing of Voltage Input Characteristics
                                                                                                                                  A
      2. Example of program 1 (For FX3U, FX3UC Series PLC)
                                                                                                                                      Common Items
         • For example, create the following program to change the digital input data of the 1st analog special
           adapter:
              M8001
                                                M8260     Sets the input mode of channel 1 to the voltage input mode
              M8002
                                                          (0 V to 10 V)
                                                                                                                                  B
                                                                                                                                FX3UC-4AD
                                                                                                                                FX3U-4AD
                                      RST      D8268.6    Error status: b6 = OFF
              M8000
                            FNC 12      K1     D8264      Sets the averaging time to "1" for the channel-1 data                   C
                             MOV
                                                                                                                                      FX3U-4AD-ADP
              M8002         FNC 12      K2      D50       Program for setting scaling instruction data table
                             MOV
                                                                Item                    Description          Value Device
                            FNC 12     K400     D51       Number of points   Sets the number of points         2    D50
                             MOV                                    X-
                                                          Start coordinate
                                                                             A/D converted digital value
                                                                             start point data
                                                                                                              400   D51           D
                            FNC 12      K0      D52       point
                                                                                                                                      FX3G-2AD-BD
                                                                    Y-       Digital output value of changed
                             MOV                                coordinate   X-axis value start point          0    D52
                                                                                                                                      FX3U-4DA
              M8000 FNC 259
                            D8260       D50     D100      The scaling instruction operation results will be stored in D100.
                     SCL
                                                                                                                                      FX3U-4DA-ADP
                                                                                                                                 G
FX3G-1DA-BD
                                                                                                                                  H
                                                                                                                                FX3U-4AD-PT
                                                                                                                                         -ADP
                                                                                                                                          I
                                                                                                                                FX3U-4AD-PTW
                                                                                                                                         -ADP
                                                                                                                                    J
                                                                                                                                FX3U-4AD-PNK
                                                                                                                                         -ADP
                                                                                                                      C-27
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                         5 Changing of Input Characteristics
FX3U-4AD-ADP (4-channel analog Input)                                   5.1 Example: Changing of Voltage Input Characteristics
C-28
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                              6 Troubleshooting
FX3U-4AD-ADP (4-channel analog Input)                                                          6.1 PLC Version Number Check
                                                                                                                                    Common Items
6.     Troubleshooting
         This chapter describes troubleshooting methods and error statuses.                                                     B
         If the A/D conversion data is not input, or if the proper digital value is not input, check the following items:
                                                                                                                              FX3UC-4AD
                                                                                                                              FX3U-4AD
         • PLC version number
         • Wiring
         • Special devices
         • Programs                                                                                                             C
         • Error status
                                                                                                                                    FX3U-4AD-ADP
6.1      PLC Version Number Check
         • Any versions (from Ver.2.20 (initial version) to the latest version) of the FX3U Series are compatible.              D
         • Check the version number of the FX3UC Series PLC. The version number should be 1.20 or later.
                                                                                                                                    FX3G-2AD-BD
         • Any versions (from Ver.1.00 (initial version) to the latest version) of the FX3G Series are compatible.
                        → For a detailed description of the version number check method, refer to Section 1.3.
                                                                                                                                    FX3U-4DA
         Check the following items for wiring:
      1. Power
         The 4AD-ADP needs driving power. Verify that the power supply line is properly connected. Also check that
         the POWER indicator lamp of the 4AD-ADP is on.
                                                                                                                                  F
      2. Analog input line
                                                                                                                                    FX3U-4DA-ADP
         Use 2-core twisted shielded pair cable for the analog input line. In addition, be sure to separate the analog
         input line from other power lines or inductive lines.
                                                                                                                                    FX3G-1DA-BD
         into correct digital data.
                                                         → For a detailed description of wiring, refer to Chapter 3.
                                                                                                                                H
                                                                                                                              FX3U-4AD-PT
                                                                                                                                       -ADP
                                                                                                                                        I
                                                                                                                              FX3U-4AD-PTW
                                                                                                                                       -ADP
                                                                                                                                  J
                                                                                                                              FX3U-4AD-PNK
                                                                                                                                       -ADP
                                                                                                                     C-29
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                          6 Troubleshooting
FX3U-4AD-ADP (4-channel analog Input)                                                            6.3 Special Device Check
       2. Input data
         Verify that the special device of the selected channel is correctly selected. This special device should be
         selected depending on the connecting position and the channel.
       3. Averaging time
         Check that the set averaging time is within the specified range. The averaging time should be set in the range
         from 1 to 4095. If the set averaging time is outside the specified range, an error occurs.
       4. Error status
         Check that no error is detected in the 4AD-ADP.
         If an error is detected, check the details of the error, and then check the wiring and programs.
                                                 → For a detailed description of special devices, refer to Chapter 4.
C-30
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                            6 Troubleshooting
FX3U-4AD-ADP (4-channel analog Input)                                                                6.5 Error Status Check
                                                                                                                                A
6.5      Error Status Check
                                                                                                                                    Common Items
         If an error occurs in the 4AD-ADP, the corresponding bit will turn on.
                                                                                                                              FX3UC-4AD
                                                                                                                              FX3U-4AD
             b1     Channel-2 over-scale detection        b6      4AD-ADP hardware error
             b2     Channel-3 over-scale detection        b7      4AD-ADP communication data error
             b3     Channel-4 over-scale detection     b8 to b15 Unused
             b4     EEPROM error                           -                           -
         To solve the problem, refer to the troubleshooting method described below:                                             C
                                                                                                                                    FX3U-4AD-ADP
      1. Over-scale detection (b0 to b3)
         1) Description of error
            The input analog value (voltage or current value) is outside the specified range.
            The digital value is out of the range specified for the voltage input mode (0 to 4080) or outside the range
            specified for the current input mode (0 to 1640).                                                                   D
         2) Remedy
                                                                                                                                    FX3G-2AD-BD
            Check that the input analog value is within the specified range. Also check the wiring.
                                                                                                                                    FX3U-4DA
         2) Remedy
            Please contact the nearest Mitsubishi Electric distributor office.
                                                                                                                                    FX3U-4DA-ADP
         2) Remedy
            Check that the averaging time is set correctly for each channel.
                                                                                                                                    FX3G-1DA-BD
         2) Remedy
            Check that the 24V DC power is properly supplied to the 4AD-ADP. Also check that the 4AD-ADP is
            correctly connected to the PLC.
            If the problem cannot be solved even after the above check, please contact the nearest Mitsubishi
            Electric distributor office.                                                                                        H
                                                                                                                              FX3U-4AD-PT
         2) Remedy
            Check that the 4AD-ADP is correctly connected to the PLC.                                                                   I
            If the problem cannot be solved even after the above check, please contact the nearest Mitsubishi
                                                                                                                              FX3U-4AD-PTW
                                                                                                                                  J
                                                                                                                              FX3U-4AD-PNK
                                                                                                                                       -ADP
                                                                                                                   C-31
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition    6 Troubleshooting
FX3U-4AD-ADP (4-channel analog Input)                        6.5 Error Status Check
MEMO
C-32
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3G-2AD-BD (2-channel analog Input)
                                                                                                                                       Common Items
                                                                                                                                   B
                                                                                                                                 FX3UC-4AD
                                                                                                                                 FX3U-4AD
         FX3G/FX3U/FX3UC Series Programmable
         Controllers                                                                                                               C
                                                                                                                                       FX3U-4AD-ADP
         User's Manual [Analog Control Edition]
         FX3G-2AD-BD (2-channel analog Input)
                                                                                                                                   D
                                                                                                                                       FX3G-2AD-BD
                                                                                                                                    E
                                                                                                                                       FX3U-4DA
                                                                                                                                     F
                                                                                                                                       FX3U-4DA-ADP
                                                                                                                                  G
FX3G-1DA-BD
                                                                                                                                   H
                                                                                                                                 FX3U-4AD-PT
         Foreword
                                                                                                                                          -ADP
         This manual describes the specifications, wiring, and operation methods for the FX3G-2AD-BD analog input
         expansion board (2-channel analog input) and should be read and understood before attempting to install or
         use the unit.                                                                                                                     I
                                                                                                                                 FX3U-4AD-PTW
         Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
         it to the end user.
                                                                                                                                          -ADP
           This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
           licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
           rights which may occur as a result of using the contents noted in this manual.                                            J
                                                                                                                                 FX3U-4AD-PNK
                                                                                                                         D-1
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3G-2AD-BD (2-channel analog Input)
D-2
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                   1 Outline
FX3G-2AD-BD (2-channel analog Input)                                                                          1.1 Outline of Functions
                                                                                                                                               Common Items
1.        Outline
            This chapter outlines the FX3G-2AD-BD (referred to as the 2AD-BD).                                                             B
                                                                                                                                         FX3UC-4AD
                                                                                                                                         FX3U-4AD
1.1         Outline of Functions
            The FX3G-2AD-BD is an analog expansion board. Connect the FX3G-2AD-BD to the FX3G Series PLC to read
            2 channels of voltage/current data.
                                                                                                                                           C
                                                                                                                                               FX3U-4AD-ADP
            1) Up to 2*1 2AD-BD units can be connected to the FX3G Series PLC.
               (including the other analog expansion board, analog special adapters).
            2) Either "voltage input" or "current input" can be specified for each channel.
            3) A/D conversion data of each channel will be automatically written to the special data register of the FX3G
               Series PLC.                                                                                                                 D
                                                                                                                                               FX3G-2AD-BD
                                                 System                                                    Point and section to be
                                                                                                                 referred to
2*1 maximum
                                                                                                                                               FX3U-4DA
              board         board
                                                                                                          To check the connectable
                                                                                                     …… PLC model number, refer
                                                                                                          to Section 1.3.
                                                                                                                                               FX3U-4DA-ADP
                                             Connected to the option connector 2
                       Analog data
                                                                                                     …… For a detailed
                                                                                                        description of wiring,
                                                                                                          refer to Chapter 3.
                                                                                                                                          G
          Flowmeter, pressure sensor, etc.
  •Switching of input mode                                      2nd board     M/D8270 to M/D8279          For a detailed description
  •Setting of averaging                                                                                   of a basic program, refer to
   time                                                                                                   Section 4.8.
                                                                                                                                                  -ADP
  Refer to the system configuration shown in the User's Manual - Hardware Edition to check the number of connectable units
  and to configure the entire system.
                                                                                                                                                   I
                                                                                                                                         FX3U-4AD-PTW
  *1.Only 1 analog board can be connected to the 14-point and 24-point type main unit.
                                                                                                                                                  -ADP
                                                                                                                                             J
                                                                                                                                         FX3U-4AD-PNK
                                                                                                                                                  -ADP
                                                                                                                                  D-3
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                      1 Outline
FX3G-2AD-BD (2-channel analog Input)                                         1.2 Setup Procedure Before Starting Operation
FX3G-2AD-BD
Refer to Chapter 1.
                            Wiring                                   Wiring:
                                                                     • Selection of sensor cable
                                                                     • Power supply line
                                      Refer to Chapter 4.            • Analog input line
                        Programming                                  Programming:
                                                                     • Details of special devices
                                                                     • Examples of basic programs
                                      Refer to Chapter 5.
D-4
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                                 1 Outline
FX3G-2AD-BD (2-channel analog Input)                                                                     1.3 Connectable PLCs and Version Number
                                                                                                                                                         A
1.3      Connectable PLCs and Version Number
                                                                                                                                                             Common Items
         The 2AD-BD is compatible with the following PLC.
                                                                                                                                                       FX3UC-4AD
                                                                                                                                                       FX3U-4AD
      1. Version check
         Special data register D8001 contains information for determining the PLC version number.
                                                                                                                                                         C
                                                                                                                                                             FX3U-4AD-ADP
                            D8001                  2        6       1       1        0
                        PLC type and
                       version number                                               Version data (Example: Ver. 1.10)
                                                            PLC type (Example: 26 = FX3G series)
                                                                                                                                                         D
      2. How to look at the manufacturer's serial number
                                                                                                                                                             FX3G-2AD-BD
         The year and month of production of the product can be seen from the manufacturer's serial number
         "SERIAL" indicated on the label adhered to the right side of the product.
                                                                            PROGRAMMABLE
                                                                                                                                                          E
                                           MITSUBISHI
                                                                                                                                                             FX3U-4DA
                                                                              CONTROLLER
                            Right side
                                           MODEL            FX3G-40MT/ES
                                                           100-240VAC 50/60Hz 37W
                                                                OUT:5~30VDC 0.5A
                                           SERIAL                       8X0001
                                                                                                                                                           F
                                                                                                                                                             FX3U-4DA-ADP
                                             MITSUBISHI ELECTRIC CORPORATION
                                           MADE IN JAPAN
8 X 0 0 0 1
                                                                             Control number
                                                                Month (Example: Oct.):(1 to 9 = January to September,                                   G
                                                                X = October, Y = November, Z = December)
                                                                                                                                                             FX3G-1DA-BD
                                                           Year (Example: 2008): Last digit of year
         If a programming tool with the wrong version number is used, programming will not be possible.
                                                                                                                                                                -ADP
                                                                                                                                                           J
                                                                                                                                                       FX3U-4AD-PNK
                                                                                                                                                                -ADP
                                                                                                                                              D-5
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                       2 Specifications
FX3G-2AD-BD (2-channel analog Input)                                                                      2.1 Generic Specifications
2.     Specifications
         This chapter describes the general and performance specifications for the 2AD-BD.
                Item                                                     Specifications
          Ambient            0 to 55°C (32 to 131°F) when operating
          temperature        -25 to 75°C (-13 to 167°F) when stored
          Relative
                             5 to 95%RH (no condensation) when operating
          humidity
                                                    Frequency          Acceleration      Half amplitude
                                                       (Hz)               (m/s2)              (mm)
                                                                                                          Tests 10 times in each
          Vibration                                    10 - 57              -                0.035        direction (X-, Y-, and Z-
                             DIN Rail Mounting
          resistance                                 57 - 150              4.9                    -       axis directions) (Total:
                                                                                                          80 min, each)
                                                       10 to 57             −                0.075
                             Direct Mounting
                                                    57 to 150              9.8                    −
          Shock
                             147 m/s2 Acceleration, Action time: 11ms, 3 times by half-sine pulse in each direction X, Y, and Z
          resistance
          Noise              Using noise simulator of:
          resistance         Noise voltage: 1,000Vp-p / Noise width: 1µs / Rise: 1ns / Cycle: 30 to 100Hz
                             Class D grounding (grounding resistance: 100 Ω or less)
          Grounding
                             <Common grounding with a heavy electrical system is not allowed.>*1
          Working
                             Free from corrosive or flammable gas and excessive conductive dusts
          environment
          Working
                             < 2000m*2
          altitude
          *1.
                       PLC        Other          PLC         Other         PLC          Other
                                equipment                  equipment                  equipment
D-6
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                               2 Specifications
FX3G-2AD-BD (2-channel analog Input)                                                                                          2.2 Performance Specifications
                                                                                                                                                                 A
2.2      Performance Specifications
                                                                                                                                                                     Common Items
                                                                                        Specifications
                 Item
                                                            Voltage input                                                  Current input                         B
                                                                                                                                                               FX3UC-4AD
                                                                                                                                                               FX3U-4AD
          Analog input                                       0V to 10V DC                                                 4mA to 20mA DC
          range                                      (Input resistance: 198.7 kΩ)                                     (Input resistance: 250 Ω)
          Absolute input
                                                              -0.5V, +15V                                                  -2mA, +30mA
          maximum
          Digital output                                    12 bits, binary                                                11 bits, binary
          Resolution                                      2.5mV (10V/4000)                                               8µA (16mA/2000)
                                                                                                                                                                 C
                                                                                                                                                                     FX3U-4AD-ADP
                              • ±0.5% (±50mV) for 10V full scale          • ±0.5% (±80µA) for 16mA full scale
                                (when ambient temperature is 25°C ± 5°C)    (when ambient temperature is 25°C ± 5°C)
          Total accuracy
                              • ±1.0% (±100mV) for 10V full scale         • ±1.0% (±160µA) for 16mA full scale
                                (when ambient temperature is 0°C to 55°C)   (when ambient temperature is 0°C to 55°C)
          A/D conversion
          time
                                                      180 µs (The data will be updated at every scan time.)
                                                                  → For a detailed description of data update, refer to Section 2.4.
                                                                                                                                                                 D
                                                                                                                                                                     FX3G-2AD-BD
                                    4080                                                           2040
                                    4000                                                           2000
                                                                                                                                                                  E
          Input                                                                                     Digital output
                                                                                                                                                                     FX3U-4DA
                                    Digital output
characteristics
                                                     0
                                                         Analog input
                                                                            10V 10.2V                                0 4mA
                                                                                                                         Analog input
                                                                                                                                      20mA 20.32mA
                                                                                                                                                                   F
                                                                                                                                                                     FX3U-4DA-ADP
                              • The analog input area is not insulated from the PLC.
          Insulation method
                              • Channels are not insulated from each other.
          Number of I/O
                               0 point (This number is not related to the maximum number of input/output points of the PLC.)
          points occupied
                                                                                                                                                                G
FX3G-1DA-BD
                                                                                                                                                                 H
                                                                                                                                                               FX3U-4AD-PT
                                                                                                                                                                        -ADP
                                                                                                                                                                         I
                                                                                                                                                               FX3U-4AD-PTW
                                                                                                                                                                        -ADP
                                                                                                                                                                   J
                                                                                                                                                               FX3U-4AD-PNK
                                                                                                                                                                        -ADP
                                                                                                                                                     D-7
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                        2 Specifications
FX3G-2AD-BD (2-channel analog Input)                                                                         2.3 A/D Conversion Time
Sequence Program
END instruction
                                          A/D                                      A/D
                                       conversion                               conversion
                                            180µs                                    180µs
                                             /2ch                                     /2ch
                                      FX3G-2AD-BD                             FX3G-2AD-BD
                                          1st                                     2nd
D-8
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                              3 Wiring
FX3G-2AD-BD (2-channel analog Input)
                                                                                                                                           Common Items
3.     Wiring
         This chapter describes the 2AD-BD wiring.                                                                                     B
         Observe the following caution to wire the 2AD-BD.
                                                                                                                                     FX3UC-4AD
                                                                                                                                     FX3U-4AD
          WIRING PRECAUTIONS
          • Make sure to cut off all phases of the power supply externally before attempting wiring work.
            Failure to do so may cause electric shock or damages to the product.                                                       C
                                                                                                                                           FX3U-4AD-ADP
          WIRING PRECAUTIONS
          • Connect the DC power supply wiring to the dedicated terminals described in this manual.
            If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will be
            burnt out.
                                                                                                                                       D
                                                                                                                                           FX3G-2AD-BD
          • Do not wire vacant terminals externally.
            Doing so may damage the product.
          • Perform class D grounding (grounding resistance: 100Ω or less) to the grounding terminal on the main unit.
            Do not use common grounding with heavy electrical systems.
          • When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
            Failure to do so may cause fire, equipment failures or malfunctions.                                                        E
          • Make sure to observe the following precautions in order to prevent malfunctions under the influence of noise:
                                                                                                                                           FX3U-4DA
            - Do not bundle the power line or twisted shielded cable together with or lay it close to the main circuit, high-
                voltage line, or load line.
                Otherwise, noise disturbance and/or surge induction are likely to take place. As a guideline, lay the control line
                at least 100mm (3.94") or more away from the main circuit, high-voltage line, or load line.
            - Ground the shield of the analog input/output cable at one point on the signal receiving side.
                However, do not use common grounding with heavy electrical systems.                                                      F
          • Make sure to properly wire to the European terminal board in accordance with the following precautions.
                                                                                                                                           FX3U-4DA-ADP
            Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product.
            - The disposal size of the cable end should be 9 mm (0.35").
            - Tightening torque should be between 0.22 to 0.25 N•m.
            - Twist the end of strand wire and make sure there are no loose wires.
            - Do not solder-plate the electric wire ends.
            - Do not connect more than the specified number of wires or electric wires of unspecified size.                           G
            - Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
FX3G-1DA-BD
                                                                                                                                       H
                                                                                                                                     FX3U-4AD-PT
                                                                                                                                              -ADP
                                                                                                                                               I
                                                                                                                                     FX3U-4AD-PTW
                                                                                                                                              -ADP
                                                                                                                                         J
                                                                                                                                     FX3U-4AD-PNK
                                                                                                                                              -ADP
                                                                                                                           D-9
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                3 Wiring
FX3G-2AD-BD (2-channel analog Input)                                             3.1 Terminal Layout
D-10
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                3 Wiring
FX3G-2AD-BD (2-channel analog Input)                                         3.2 Applicable Cables and Terminal Tightening Torque
                                                                                                                                       A
3.2      Applicable Cables and Terminal Tightening Torque
                                                                                                                                           Common Items
         Use the following cables to connect with the counterpart equipment. Terminate the cable ends as shown
         below.
1. Cables B
                                                                                                                                     FX3UC-4AD
                                                                                                                                     FX3U-4AD
         Applicable cable and tightening torque
                           Wire size (stranded/       Tightening
                                                                                           Termination
                               single-wire)             torque
                         0.3mm2 to 0.5mm2                          • To connect a stranded cable, peel the cover off the cable
          Single-wire
                         (AWG22 to 20)                               and then twist the core before connection.
                                                                   • To connect a single-wire cable, just strip the cover off the
                                                                                                                                       C
          2-wire               2
                         0.3mm (AWG22)
                                                                                                                                           FX3U-4AD-ADP
                                                                     cable before connection.
                                                      0.22N•m to • Rod terminal with insulation sleeve
          Rod terminal   0.3mm2 to 0.5mm2              0.25N•m     (recommended terminal)
          with           (AWG22 to 20)                             AI 0.5-8WH : Manufactured by Phoenix Contact
          insulation     (Refer to the rod terminal
                                                                 • Caulking tool
          sleeve         external view shown in the
                         following figure.)
                                                                   CRIMPFOX ZA 3 : Manufactured by Phoenix Contact                     D
                                                                   (or CRIMPFOX UD 6 : Manufactured by Phoenix Contact)
                                                                                                                                           FX3G-2AD-BD
      2. Termination of cable end
         To terminate the cable, treat the stranded/single-wire directly or use a rod terminal with insulation sleeve.
         • To directly terminate the end of a stranded/single-wire cable:
           - Twist the end of the stranded cable so that the "barbed wires"
                                                                                            Termination of cable end
                                                                                                                                        E
             cannot protrude.
                                                                                                                                           FX3U-4DA
           - Do not solder-plate the end of the cable.
                                                                                                            9mm
                                                                                                           (0.35")
         • To terminate cable end using a rod terminal with insulation sleeve:                Insulation sleeve Contact area
           If the cable cover is too thick, it may be difficult to insert the cable into
           the insulation sleeve. For this reason, select an appropriate cable while
                                                                                                                (Crimp area)             F
                                                                                                                                           FX3U-4DA-ADP
           referring to the external view.                                                                        8mm      (0.31")
                   Manufacturer               Model                 Caulking tool            2.6mm           14mm
                                                                                              (0.1")
                                                                CRIMPFOX ZA 3                                (0.55")
            Phoenix Contact                 AI 0.5-8WH
                                                              (or CRIMPFOX UD 6)
      3. Tool
                                                                                                                                      G
                                                                                                                                           FX3G-1DA-BD
         • To tighten terminals, use a small-sized screwdriver whose head is straight and is not widened as shown in
           the figure to the right.
            Note:
            If the diameter of screwdriver grip is too small, tightening torque will not
            be able to be achieved. Use the following recommended screwdriver or
                                                                                                                     The head
                                                                                                                     should be
                                                                                                                                       H
            an appropriate replacement (grip diameter: approximately 25mm).
                                                                                                                                     FX3U-4AD-PT
straight.
                         Manufacturer                          Model
            Phoenix Contact                                 SZS 0.4×2.5
                                                                                                                                              -ADP
                                                                                              0.4mm                  2.5mm
                                                                                              (0.01")                (0.09")
                                                                                                                                               I
                                                                                                                                     FX3U-4AD-PTW
                                                                                                                                              -ADP
                                                                                                                                         J
                                                                                                                                     FX3U-4AD-PNK
                                                                                                                                              -ADP
                                                                                                                           D-11
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                            3 Wiring
FX3G-2AD-BD (2-channel analog Input)                                                                       3.3 Analog Input Line
                                                   *1                                        110kΩ    ch
                                                                  V       +
                                                                                     250Ω
                                                                  I       +                  88.7kΩ
                                       Class-D
                                       grounding
                                                                    VI-
                                                               *3
          *1.   Use the 2-core shielded twisted pair cable for the analog input lines, and separate the analog input
                lines from other power lines or inductive lines.
          *2.   If "current input" is selected, be sure to short the line between the V + terminal and the I + terminal.
                ( : Channel number).
          *3.   Make sure to short-circuit the "V +" and "VI-" terminals when ch is not used.
3.4      Grounding
         Grounding should be performed as stated below.
         • The grounding resistance should be 100Ω or less.
         • Independent grounding should be performed for best results.
           When independent grounding is not performed, perform "shared grounding" as shown in the following
           figure.
                               → For details, refer to the User’s Manual - Hardware Edition of the PLC Series.
D-12
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                 4 Programming
FX3G-2AD-BD (2-channel analog Input)                                                       4.1 Loading of A/D Conversion Data
                                                                                                                                      Common Items
4.     Programming
         This chapter describes how to create programs that can read analog data using the 2AD-BD.                                B
                                                                                                                                FX3UC-4AD
                                                                                                                                FX3U-4AD
4.1      Loading of A/D Conversion Data
         1) The input analog data will be converted into digital data and then stored in the special devices of the FX3G
            Series PLC.
                                                                                                                                  C
         2) If the data is stored in the special devices, the averaging time can be set, and the input mode can be
                                                                                                                                      FX3U-4AD-ADP
            specified.
         3) Special auxiliary relays (10 points) and special data registers (10 points) are assigned respectively to the
            analog expansion board connected to the option connector 1 and the analog expansion board connected
            to the option connector 2 in this order.
                                  → For a detailed description of special device assignment, refer to Section 4.2.                D
         • FX3G Series PLC
                                                                                                                                      FX3G-2AD-BD
                                           FX3G Series PLC
Sequence Program
                                                                                                                                      FX3U-4DA
                       Special auxiliary relays:       Special auxiliary relays:
                         M8260 to M8269                  M8270 to M8279
                        Special data register:          Special data register:
                         D8260 to D8269                  D8270 to D8279
                                  A/D                            A/D
                                                                                                                                    F
                                                                                                                                      FX3U-4DA-ADP
                               FX3G-2AD-BD                   FX3G-2AD-BD
                                   1st                          2nd*1
            The analog expansion board connected to the option connector 1 is regarded as the 1st unit, and the
            analog expansion board connected to the option connector 2 is regarded as the 2nd unit.
          *1.   The second analog expansion board is not available in the 14-point and 24-point type main unit.                  G
FX3G-1DA-BD
                                                                                                                                  H
                                                                                                                                FX3U-4AD-PT
                                                                                                                                         -ADP
                                                                                                                                          I
                                                                                                                                FX3U-4AD-PTW
                                                                                                                                         -ADP
                                                                                                                                    J
                                                                                                                                FX3U-4AD-PNK
                                                                                                                                         -ADP
                                                                                                                     D-13
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                            4 Programming
FX3G-2AD-BD (2-channel analog Input)                                                                        4.2 List of Special Devices
       1. Program Example
         To switch the channel input mode, create a sequence program as follows:
         1) To switch the input mode of channel                2) To switch the input mode of channel 2
            1 of the 1st analog board to the voltage              of the 1st analog board to the current
            input mode:                                           input mode:
             M8001                                                 M8000
                                              M8260                                                M8261
             Normally OFF                                           Normally ON
D-14
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                 4 Programming
FX3G-2AD-BD (2-channel analog Input)                                                                         4.4 Input Data
                                                                                                                                A
4.4      Input Data
                                                                                                                                    Common Items
                                                                                       Numeric data type: Decimal (K)
         The data converted by the 2AD-BD will be stored in the special data registers.
         The special data registers that store the input data are shown in the following table:
                                                                                                                                B
                                                                                                                              FX3UC-4AD
                                                                                                                              FX3U-4AD
             Special data register
                                                           Description
           1st board     2nd board
             D8260         D8270       Stores the channel-1 input data
             D8261         D8271       Stores the channel-2 input data
                                                                                                                                C
         The converted A/D immediate data or averaged data (data average conforming to the specified averaging
                                                                                                                                    FX3U-4AD-ADP
         time) will be stored in the above data registers as the input data.
                                           → For a detailed description of the averaging time, refer to Section 4.5.
                                                                                                                                    FX3G-2AD-BD
         programming tool.
      2. Program Example
           M8000
                                     FNC 12    D8260     D100       Stores the channel-1 input data
                                                                    of the 1st analog board in the D100.
                                                                                                                                 E
                                      MOV
                                                                                                                                    FX3U-4DA
          Normally
          ON
         Even if the input data is not stored in D100 or D101, data registers D8260 or D8261 can be directly used in
         the timer/counter set value or in a PID instruction.                                                                     F
                                                                                                                                    FX3U-4DA-ADP
                                                                                                                               G
FX3G-1DA-BD
                                                                                                                                H
                                                                                                                              FX3U-4AD-PT
                                                                                                                                       -ADP
                                                                                                                                        I
                                                                                                                              FX3U-4AD-PTW
                                                                                                                                       -ADP
                                                                                                                                  J
                                                                                                                              FX3U-4AD-PNK
                                                                                                                                       -ADP
                                                                                                                   D-15
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                               4 Programming
FX3G-2AD-BD (2-channel analog Input)                                                                    4.5 Averaging Time
       2. Program Example
           M8000                                                   Sets the averaging time for
                                     FNC 12     K1     D8264       channel-1 of the 1st analog
                                      MOV                          board to 1.
          Normally
          ON
                                                                   Sets the averaging time for
                                     FNC 12     K5     D8265       channel-2 of the 1st analog
                                      MOV                          board to 5.
D-16
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                         4 Programming
FX3G-2AD-BD (2-channel analog Input)                                                                                 4.6 Error Status
                                                                                                                                          A
4.6      Error Status
                                                                                                                                              Common Items
         If an error is detected in the 2AD-BD, the error status data will be stored in the corresponding special data
         register.
         The following table shows the special data registers that store the error status data:
                                                                                                                                          B
             Special data register
                                                                                                                                        FX3UC-4AD
                                                                                                                                        FX3U-4AD
                                                              Description
           1st board         2nd board
             D8268            D8278      Stores the error status data.
         Check the ON/OFF status of each bit of the error status data register to check the description of the error.
         Errors are assigned to the bits as shown in the following table. Create a program to detect errors.                              C
                                              → For a detailed description of the error status, refer to Section 6.5.
                                                                                                                                              FX3U-4AD-ADP
               Bit                       Description                        Bit                        Description
               b0            Channel-1 over-scale detection                 b5        Averaging time setting error
               b1            Channel-2 over-scale detection                 b6        2AD-BD hardware error
               b2            Unused                                         b7        2AD-BD communication data error
                                                                                                                                          D
                                                                                                                                              FX3G-2AD-BD
               b3            Unused                                      b8 to b15    Unused
               b4            EEPROM error                                    -                                 -
                                                                                                                                              FX3U-4DA
         For this reason, be sure to create the following program:
               M8000
                                         FNC 12     D8268      K4M0
                                          MOV
             Normally ON
               M8002
                                                                                                                                            F
                                                                            Error status of 1st analog board
                                                                                                                                              FX3U-4DA-ADP
                                                     RST         M6         b6 = OFF (hardware error)
             Initial pulse
                                         FNC 12
                                          MOV
                                                    K4M0       D8268                                                                     G
FX3G-1DA-BD
                                                                                                                                          H
                                                                                                                                        FX3U-4AD-PT
                                                                                                                                                 -ADP
                                                                                                                                                  I
                                                                                                                                        FX3U-4AD-PTW
                                                                                                                                                 -ADP
                                                                                                                                            J
                                                                                                                                        FX3U-4AD-PNK
                                                                                                                                                 -ADP
                                                                                                                            D-17
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                          4 Programming
FX3G-2AD-BD (2-channel analog Input)                                                                 4.6 Error Status
2. Program Example
                   M8000
                                   MOV       D8268     K4M0
                   Normally
                   ON
                     M0
                                                        Y000   Detects over-scale in channel 1 of
                                                               the 1st board.
                     M1
                                                        Y001   Detects over-scale in channel 2 of
                                                               the 1st board.
                     M4
                                                        Y004   EEPROM error in 1st board
                     M5
                                                        Y005   Averaging time setting error in
                                                               1st board
                     M6
                                                        Y006   Hardware error in 1st 2AD-BD
                     M7
                                                        Y007   Communication data error in 1st
                                                               2AD-BD
D-18
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                 4 Programming
FX3G-2AD-BD (2-channel analog Input)                                                                        4.7 Model Code
                                                                                                                               A
4.7      Model Code
                                                                                                                                   Common Items
                                                                                                    Initial value: K3
                                                                                     Numeric data type: Decimal (K)
         When the 2AD-BD is connected, model code "3" is stored in the corresponding special data register.
         The following table shows the special data registers that store the model code:                                       B
                                                                                                                             FX3UC-4AD
                                                                                                                             FX3U-4AD
             Special data register
                                                          Description
           1st board      2nd board
             D8269           D8279     Model code
         Use the special data registers above to check whether a 2AD-BD is connected or not.
                                                                                                                               C
                                                                                                                                   FX3U-4AD-ADP
      1. Program Example
                                                                                                                                   FX3G-2AD-BD
4.8      Basic Program Example
         Create the following basic program example to read out analog conversion (A/D conversion) data.
         The following program will set the 1st board to voltage input mode and channel 2 to current input mode, and
         will store the converted A/D value of channel-1 data into D100 and that of channel-2 data into D101.
                                                                                                                                E
                                                                                                                                   FX3U-4DA
                       M8001                                       Sets the input mode of the 1st board
                                                         M8260     to the voltage input mode
                       Normally                                    (0 V to 10 V).
                       OFF
                       M8000                                       Sets the input mode of the 2nd board
                                                                                                                                 F
                                                                                                                                   FX3U-4DA-ADP
                                                         M8261     to the current input mode
                       Normally                                    (4 mA to 20 mA).
                       ON
                       M8000
                                     FNC 12    D8268     K4M0
                       M8002
                                      MOV
                                                                                                                              G
                                                                                                                                   FX3G-1DA-BD
                                               RST        M6       Error status: b6 = OFF
                       Initial
                       pulse
                                               RST        M7       Error status: b7 = OFF
                                     FNC 12
                                      MOV
                                               K4M0      D8268                                                                 H
                                                                                                                             FX3U-4AD-PT
                       M8000
                                      FNC 12                       Sets the averaging time to "5"
                                                    K5   D8264     for channel-1 data.
                                       MOV
                                                                                                                                      -ADP
         Even if the input data is not stored into D100 or D101, the data registers D8260 or D8261 can be directly used
         in the timer/counter setting value or in a PID instruction.
                                                                                                                                 J
                                                                                                                             FX3U-4AD-PNK
                                                                                                                                      -ADP
                                                                                                                  D-19
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                              5 Changing of Input Characteristics
FX3G-2AD-BD (2-channel analog Input)                                                              5.1 Example: Changing of Voltage Input Characteristics
       1. Input characteristics
                                                     Voltage input characteristics            Digital output value to be changed
                                                     (product specifications)                        Y-axis
                             Digital output
4000 10000
                                                                                             Digital output to
                                                                                             be calculated
                                                                                             (D110)
                                              2000
400
                                                 0                                                                                 X-axis
                                                      1V        5V             10V                               0 400(1V) 2000(5V)
                                                                  Analog input
                                                                                                                 Digital value actually obtained
                                                                                                                 by A/D conversion
       2. Example of program
         For example, create the following program to change the digital input data of the 1st analog board:
              M8001
                                                                                             M8260                    Sets the input mode of channel 1 to the
             Normally OFF                                                                                             voltage input mode (0V to 10V).
              M8000                                                     FNC 12       D8268   K4M0
             Normally ON                                                 MOV
              M8002
                                                                                     RST        M6                     Error status : b6=OFF
             Initial pulse
               FNC 230                                         FNC 237 D110 K2000                                     Check to make sure the digital
                                         D110        K400                                        M10
                LD>=                                            AND<=                                                 value (D110) is in range.
               M10                                                FNC 21
                                                                         D110         K400   D111
                                                                   SUB
D-20
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                              6 Troubleshooting
FX3G-2AD-BD (2-channel analog Input)                                                           6.1 PLC Version Number Check
                                                                                                                                    Common Items
6.     Troubleshooting
         This chapter describes troubleshooting methods and error statuses.                                                     B
         If the A/D conversion data is not input, or if the proper digital value is not input, check the following items:
                                                                                                                              FX3UC-4AD
                                                                                                                              FX3U-4AD
         • PLC version number
         • Installation
         • Wiring
         • Special devices                                                                                                      C
         • Programs
                                                                                                                                    FX3U-4AD-ADP
         • Error status
                                                                                                                                    FX3G-2AD-BD
                       → For a detailed description of the version number check method, refer to Section 1.3.
                                                                                                                                    FX3U-4DA
           of the 2AD-BD is lit correctly.
              → For a detailed description of installing, refer to FX3G Series User’s Manual - Hardware Edition.
                                                                                                                                    FX3U-4DA-ADP
      1. Analog input line
         Use 2-core twisted shielded pair cable for the analog input line. In addition, be sure to separate the analog
         input line from other power lines or inductive lines.
                                                                                                                                    FX3G-1DA-BD
         To use the current input mode for a channel, be sure to shortcircuit the line between the V + terminal and the
         I +terminal ( : channel number) of the channel. If the line is not shortcircuited, data will not be converted
         into correct digital data.
                                                         → For a detailed description of wiring, refer to Chapter 3.
         Check whether the special devices for the 2AD-BD are being used correctly:
                                                                                                                                       -ADP
      2. Input data
         Verify that the special device of the selected channel is correctly selected. This special device should be
                                                                                                                                       -ADP
      3. Averaging time                                                                                                           J
                                                                                                                              FX3U-4AD-PNK
         Check that the set averaging time is within the specified range. The averaging time should be set in the range
         from 1 to 4095. If the set averaging time is outside the specified range, an error occurs.
                                                                                                                                       -ADP
                                                                                                                     D-21
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                            6 Troubleshooting
FX3G-2AD-BD (2-channel analog Input)                                                                   6.5 Program Check
       4. Error status
         Check that no error is detected in the 2AD-BD.
         If an error is detected, check the details of the error, and then check the wiring and programs.
                                                 → For a detailed description of special devices, refer to Chapter 4.
D-22
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                 6 Troubleshooting
FX3G-2AD-BD (2-channel analog Input)                                                      6.6 Error Status Check
                                                                                                                     A
      5. 2AD-BD communication data error (b7)
                                                                                                                         Common Items
         1) Description of error
            A communication error is detected between the 2AD-BD and the PLC.
         2) Remedy
            Check that the 2AD-BD is correctly connected to the PLC.
            If the problem cannot be solved even after the above check, please contact the nearest Mitsubishi        B
            Electric distributor office.
                                                                                                                   FX3UC-4AD
                                                                                                                   FX3U-4AD
                                                                                                                     C
                                                                                                                         FX3U-4AD-ADP
                                                                                                                     D
                                                                                                                         FX3G-2AD-BD
                                                                                                                      E
                                                                                                                         FX3U-4DA
                                                                                                                       F
                                                                                                                         FX3U-4DA-ADP
                                                                                                                    G
FX3G-1DA-BD
                                                                                                                     H
                                                                                                                   FX3U-4AD-PT
                                                                                                                            -ADP
                                                                                                                             I
                                                                                                                   FX3U-4AD-PTW
                                                                                                                            -ADP
                                                                                                                       J
                                                                                                                   FX3U-4AD-PNK
                                                                                                                            -ADP
                                                                                                        D-23
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition    6 Troubleshooting
FX3G-2AD-BD (2-channel analog Input)                         6.6 Error Status Check
MEMO
D-24
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4DA (4-channel Analog Output)
                                                                                                                                       Common Items
                                                                                                                                   B
                                                                                                                                 FX3UC-4AD
                                                                                                                                 FX3U-4AD
         FX3G/FX3U/FX3UC Series Programmable
         Controllers                                                                                                               C
                                                                                                                                       FX3U-4AD-ADP
         User's Manual [Analog Control Edition]
         FX3U-4DA (4-channel Analog Output)
                                                                                                                                   D
                                                                                                                                       FX3G-2AD-BD
                                                                                                                                    E
                                                                                                                                       FX3U-4DA
                                                                                                                                     F
                                                                                                                                       FX3U-4DA-ADP
                                                                                                                                  G
FX3G-1DA-BD
                                                                                                                                   H
                                                                                                                                 FX3U-4AD-PT
         Foreword
                                                                                                                                          -ADP
         This manual describes the specifications, wiring, and operation methods for the FX3U-4DA special extension
         block (4-channel analog output) and should be read and understood before attempting to install or use the
         unit.
                                                                                                                                           I
                                                                                                                                 FX3U-4AD-PTW
         Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
         it to the end user.
                                                                                                                                          -ADP
           This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
           licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
           rights which may occur as a result of using the contents noted in this manual.                                            J
                                                                                                                                 FX3U-4AD-PNK
                                                                                                                         E-1
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4DA (4-channel Analog Output)
E-2
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                               1 Outline
FX3U-4DA (4-channel Analog Output)                                                                                             1.1 Outline of Functions
                                                                                                                                                                Common Items
1.     Outline
         This chapter outlines the FX3U-4DA.                                                                                                                B
                                                                                                                                                          FX3UC-4AD
                                                                                                                                                          FX3U-4AD
1.1      Outline of Functions
         FX3U-4DA is an analog special function block which is connectable to the FX3G, FX3U or FX3UC Series PLC to
         convert 4-channel digital signal from the PLC to analog signal (voltage/current).
                                                                                                                                                            C
         1) Up to 8*1 units can be connected to the FX3G/FX3U/FX3UC Series PLC.
                                                                                                                                                                FX3U-4AD-ADP
            (including the other special function blocks).
         2) Each channel has either Voltage Output or Current Output specification.
         3) The block converts the digital values stored in the FX3U-4DA buffer memory (BFM) in FX3U-4DA to
            analog signals (voltage/current).
         4) A predetermined output pattern is set as data table, and analog signal can be output according to the
                                                                                                                                                            D
                                                                                                                                                                FX3G-2AD-BD
            data table.
                                                                                                                                                                FX3U-4DA
                                     (including other types of special function blocks)      ••••••               Number of connectable units
                                                              •••••••••
                                                                                                                  Section 1.3.
                                                                                                                                                              F
                                                                                                                                                                FX3U-4DA-ADP
                                           FX3U -4DA                                   FX3U -4DA
                                                        24V                                        24V
                                                        D/A                                        D/A
                                                                                                                                                                FX3G-1DA-BD
                                                                                                                  For a detailed description of
                                                                                                         ••••••   analog data output programs,
                                                                                                                  refer to Chapter 4, 7, and 8.
                                                                                                                  For a detailed description of
                                                                                                                                                            H
                                                                                                         ••••••   the buffer memory, refer to
                 Program                                                        Buffer memory
                                       Transmission direction                                                     Section 5.3, and Section 5.4.
          • FROM(FNC 78)                                                           BFM#0
          • TO(FNC 79)
                                                                                                                                                          FX3U-4AD-PT
                                                                                                         ••••••
                                                                                                                  or to directly specify the BFM,
          • BFM direct                                                           BFM#3098                         refer to Section 5.2.
            specification(U\G)*2
                                                                                                                                                                   -ADP
        Refer to the system configuration shown in the FX3G/FX3U/FX3UC User's Manual - Hardware Edition to check the
        number of connectable units and to configure the entire system.
                                                                                                                                                                    I
                                                                                                                                                          FX3U-4AD-PTW
                                                                                                                                                              J
                                                                                                                                                          FX3U-4AD-PNK
                                                                                                                                                                   -ADP
                                                                                                                                               E-3
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                           1 Outline
FX3U-4DA (4-channel Analog Output)                                                   1.2 Setup Procedure Before Starting Operation
FX3U-4DA
Refer to Chapter 1.
                           Wiring                                     Wiring:
                                                                      • Power supply line
                                                                      • Analog output line
                                     Refer to Chapter 4.
Refer to Chapter 8.
E-4
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                          1 Outline
FX3U-4DA (4-channel Analog Output)                                                                      1.3 Connectable PLCs and Version Numbers
                                                                                                                                                     A
1.3      Connectable PLCs and Version Numbers
                                                                                                                                                         Common Items
         FX3U-4DA is compatible with the following PLC.
                                                                                                                                                   FX3UC-4AD
                                                                                                                                                   FX3U-4AD
          FX3UC Series PLC                          Ver. 1.30 or later                  August 2004 and later
          FX3G Series PLC                           Ver. 1.00 or later                  from the first product
      1. Version check
         Special data register D8001 contains information for determining the PLC version.
                                                                                                                                                     C
                                                                                                                                                         FX3U-4AD-ADP
                             D8001              2       4       1     0       0
                        PLC type and
                       version number                                       Version data (Example: Ver. 1.00)
                                                                                                                                                     D
                                                                      (
                                                         PLC type Example: 24 = FX3U and FX3UC series
                                                                                                                 )
                                                                                                                                                         FX3G-2AD-BD
                                                                           26 = FX3G series
                                                                                                                                                         FX3U-4DA
                                                 Example:
                                                 FX3U-48MR/ES(production number : 570001)
                                                     MODEL           FX3U-48MR/ES
                                                               100-240VAC 50/60Hz 40W                                                                  F
                                                         OUT:30VDC/240VAC 2A(COSφ=1)
                                                                                                                                                         FX3U-4DA-ADP
                                                     SERIAL                    570001
                                                                 5     7      0     0     0     1
                                                                                                                                                    G
                                                                                                                                                         FX3G-1DA-BD
                                                                                       Control number
                                                                          Month (Example: 7 = July), 1 to 9 = January to September,
                                                                          X = October, Y = November, Z = December
                                                                     Year (Example: 5 = 2005), last digit of dominical year
                                                                                                                                                     H
                                                                                                                                                   FX3U-4AD-PT
         Use a programming tool with the following version number to create FX3U-4DA programs for the FX3G/FX3U/
         FX3UC Series PLC.
                                                                                                                                                             I
                                                                                                                                                   FX3U-4AD-PTW
          • SW D5C-GPPW-E                   (Ver. 8.72A or later)                  When selecting the model, select FX3G.
                                                                                                                                                       J
         If a programming tool with the wrong version number is used, some instructions and devices cannot be used.
                                                                                                                                                   FX3U-4AD-PNK
          *1.   For Ver. 8.13P to 8.24A of GX Developer, select FX3UC for the PLC type.
                                                                                                                                                            -ADP
                                                                                                                                         E-5
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                        2 Specifications
FX3U-4DA (4-channel Analog Output)                                                                              2.1 Generic Specifications
2.     Specifications
         This chapter describes the general, power supply, and performance specifications for the FX3U-4DA.
                Item                                                     Specifications
          Ambient            0 to 55°C (32 to 131°F) when operating
          temperature        -25 to 75°C (-13 to 167°F) when stored
          Relative
                             5 to 95%RH (no condensation) when operating
          humidity
                                                       Frequency      Acceleration       Half amplitude
                                                          (Hz)           (m/s2)               (mm)
                                                                                                          Tests 10 times in each
          Vibration                                     10 - 57            -                 0.035        direction (X-, Y-, and Z-
                             DIN Rail Mounting
          resistance                                   57 - 150           4.9                    -        axis directions) (Total:
                                                                                                          80 min, each)
                                                        10 - 57            -                 0.075
                             Direct Mounting*1
                                                       57 - 150           9.8                    -
          Shock
                             147 m/s2 Acceleration, Action time: 11ms, 3 times by half-sine pulse in each direction X, Y, and Z
          resistance
          Noise              Using noise simulator of:
          resistance         Noise voltage: 1,000Vp-p / Noise width: 1µs / Rise: 1ns / Cycle: 30 to 100Hz
          Dielectric
          withstand          500 V AC, for 1 min
          voltage                                                   Between batch of all terminals and ground terminal
          Insulation         5MΩ or more using 500V DC
          resistance         insulation resistance meter
                             Class D grounding (grounding resistance: 100 Ω or less)
          Grounding
                             <Common grounding with a heavy electrical system is not allowed.>*2
          Working
                             Free from corrosive or flammable gas and excessive conductive dusts
          environment
          Working
                             < 2000m*3
          altitude
          *1.    When this block is connected to the FX3UC Series PLC, the direct mounting method cannot be used.
          *2.
                       PLC       Other           PLC        Other        PLC           Other
                               equipment                  equipment                  equipment
E-6
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                        2 Specifications
FX3U-4DA (4-channel Analog Output)                                                                        2.2 Power Supply Specifications
                                                                                                                                              A
2.2      Power Supply Specifications
                                                                                                                                                  Common Items
                   Item                                                  Specifications
          D/A conversion      24V DC ±10%, 160mA                                                                                              B
          circuit drive power (It is necessary to supply 24V DC from the terminal block.)
                                                                                                                                            FX3UC-4AD
                                                                                                                                            FX3U-4AD
                                5V DC, 120mA
          CPU drive power       (Since the internal power is supplied from the main unit, it is not necessary to supply power
                                externally.)
                                                                                                                                                  FX3U-4AD-ADP
2.3      Performance Specifications
                   Item
                                                                         Specifications
                                                                                                                                              D
                                                Voltage output                                   Current output
                                                                                                                                                  FX3G-2AD-BD
          Analog output                        -10V to +10V DC                         0mA to 20mA DC, 4mA to 20mA DC
          range                           (External load: 1kΩ to 1MΩ)                    (External load: 500Ω or less)
          Offset*1                               -10V to +9V*2                                    0mA to 17mA*3
          Gain*1                                 -9V to +10V*2                                    3mA to 30mA*3
                                                                                                                                               E
          Digital input                     With sign, 16bits, binary                              15bits, binary
                                                                                                                                                  FX3U-4DA
          Resolution                        0.32mV (20V / 64,000)                            0.63µA (20mA / 32,000)
                                 • Ambient temperature: 25°C±5°C                 • Ambient temperature: 25°C±5°C
                                   ±0.3% (±60mV) for 20V full scale                ±0.3% (±60µA) for 20mA full scale
          Overall accuracy
                                 • Ambient temperature: 0°C to 55°C              • Ambient temperature: 0°C to 55°C
                                   ±0.5% (±100mV) for 20V full scale               ±0.5% (±100µA) for 20mA full scale                           F
          Time required for
                                                                                                                                                  FX3U-4DA-ADP
                                                1ms (The number of selected channels will not affect this value.)
          D/A conversion
                                 • The photocoupler is used to insulate the analog output area from the PLC.
          Insulation method      • The DC/DC converter is used to insulate the analog output area from the power supply unit.
                                 • Channels are not insulated from each other.
          Number of I/O
                                 8 points (Taken from either the input or output points of the PLC.)
                                                                                                                                             G
          points occupied
                                                                                                                                                  FX3G-1DA-BD
          *1.      Adjustment of the offset or gain value will not affect the resolution. In output mode 1 or 4, however, the
                   offset/gain cannot be adjusted.
          *2.      The offset and the gain should satisfy the following condition:
                   1V ≤ (Gain - Offset) ≤ 10 V
                                                                                                                                              H
          *3.      The offset and the gain should satisfy the following condition:
                                                                                                                                            FX3U-4AD-PT
                   3 mA ≤ (Gain - Offset) ≤ 30 mA
                                                                                                                                                     -ADP
                                                                                                                                                      I
                                                                                                                                            FX3U-4AD-PTW
                                                                                                                                                     -ADP
                                                                                                                                                J
                                                                                                                                            FX3U-4AD-PNK
                                                                                                                                                     -ADP
                                                                                                                                 E-7
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                              2 Specifications
FX3U-4DA (4-channel Analog Output)                                                                     2.4 Output Mode (Characteristics) BFM #0
                                                                                               10200
             value                                         value
               -32000           0                            -10000           0
            -32640
-10200
32000 10000
                                     -10                                           -10
                                     -10.2                                         -10.2
                 Current                                      Current
                 output (mA)                                  output (mA)
               20.4                                          20.4
20 20
            Current
            output (mA)
            20.32
                     20
                      4
                          0           32000 32640
                                       Digital value
E-8
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                              3 Wiring
FX3U-4DA (4-channel Analog Output)
                                                                                                                                           Common Items
3.     Wiring
         This chapter describes wiring of the FX3U-4DA.                                                                                B
         Observe the following cautions wiring the FX3U-4DA.
                                                                                                                                     FX3UC-4AD
                                                                                                                                     FX3U-4AD
          WIRING PRECAUTIONS
          • Make sure to cut off all phases of the power supply externally before attempting wiring work.
            Failure to do so may cause electric shock or damages to the product.                                                       C
                                                                                                                                           FX3U-4AD-ADP
          WIRING PRECAUTIONS
          • Connect the DC power supply wiring to the dedicated terminals described in this manual.
            If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will be
            burnt out.
                                                                                                                                       D
                                                                                                                                           FX3G-2AD-BD
          • Do not wire vacant terminals externally.
            Doing so may damage the product.
          • Perform class D grounding (grounding resistance: 100Ω or less) to the grounding terminal on the main unit.
            Do not use common grounding with heavy electrical systems.
          • When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
            Failure to do so may cause fire, equipment failures or malfunctions.                                                        E
          • Make sure to observe the following precautions in order to prevent malfunctions under the influence of noise:
                                                                                                                                           FX3U-4DA
            - Do not bundle the power line or twisted shielded cable together with or lay it close to the main circuit, high-
                voltage line, or load line.
                Otherwise, noise disturbance and/or surge induction are likely to take place. As a guideline, lay the control line
                at least 100mm (3.94") or more away from the main circuit, high-voltage line, or load line.
            - Ground the shield of the analog input/output cable at one point on the signal receiving side.
                However, do not use common grounding with heavy electrical systems.                                                      F
          • Make sure to properly wire the terminal block in accordance with the following precautions.
                                                                                                                                           FX3U-4DA-ADP
            Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product.
            - The disposal size of the cable end should follow the dimensions described in this manual.
            - Tightening torque should be between 0.5 and 0.8 N•m.
FX3G-1DA-BD
                                                                                                                                       H
                                                                                                                                     FX3U-4AD-PT
                                                                                                                                              -ADP
                                                                                                                                               I
                                                                                                                                     FX3U-4AD-PTW
                                                                                                                                              -ADP
                                                                                                                                         J
                                                                                                                                     FX3U-4AD-PNK
                                                                                                                                              -ADP
                                                                                                                            E-9
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                         3 Wiring
FX3U-4DA (4-channel Analog Output)                                                          3.1 Terminal Layout
                                                   Signal              Application
                                                    24+
                                                                24V DC power supply
                                                    24-
                                                                Ground terminal
                                                    V+
                                                    VI-         Channel-1 analog output
                                                    I+
                                                     •          Do not connect any lines.
                                                    V+
                                                    VI-         Channel-2 analog output
                                                    I+
                                                     •          Do not connect any lines.
                                                    V+
                                                    VI-         Channel-3 analog output
                                                    I+
                                                     •          Do not connect any lines.
                                                    V+
                                                    VI-         Channel-4 analog output
                                                    I+
                                φ3.2 (0.13")
            6.2 mm (0.24")                                  Terminal
                                                               ’[Žq
                or less
                                 φ3.2 (0.13")
            6.2 mm (0.24")                                     Terminal Crimp
                or less                                        screw    terminal
                                   6.3 mm(0.25")
                                   or more
                                 φ3.2 (0.13")
            6.2 mm (0.24")                                  Terminal
                or less
                                   6.3 mm(0.25")
                                   or more
E-10
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                  3 Wiring
FX3U-4DA (4-channel Analog Output)                                                                  3.3 Wiring to Power Supply Terminals
                                                                                                                                             A
3.3      Wiring to Power Supply Terminals
                                                                                                                                                 Common Items
3.3.1    Examples of Power Supply Circuit
         Below are examples of circuits for using the 24V DC service power supply of the FX3G/FX3U Series PLC.                               B
         1) Sink input [- common] wiring
                                                                                                                                           FX3UC-4AD
                                                                                                                                           FX3U-4AD
                                     AC power
                                    100 to 240 V
                                                                                                                                                 FX3U-4AD-ADP
                         Class-D
                        grounding
                                    L          N       S/S    0V   24V          24+    24-
                                                                                                                                             D
                                                                                             +15V
                                                                                                                                                 FX3G-2AD-BD
                                        FX3G/FX3U Series PLC
                                             (main unit)                                  -15V
                                                                                   FX3U-4DA
Connect the "S/S" terminal of the main unit to the "24V" terminal. E
                                                                                                                                                 FX3U-4DA
         2) Source input [+ common] wiring
                                     AC power
                                    100 to 240 V                                                                                               F
                                                                                                                                                 FX3U-4DA-ADP
                         Class-D
                        grounding
                                    L         N        S/S   0V    24V          24+    24-
                                                                                                                                            G
                                                                                                                                                 FX3G-1DA-BD
                                                                                             +15V
                             Connect the "S/S" terminal of the main unit to the "0V" terminal.
                                                                                                                                                    -ADP
         • Ground the "      " terminal and "    " terminal to the Class - D grounding line (100 Ω or less) together
           with the ground terminal of the main unit.
                                                                                                                                                    -ADP
         • For the timing of power-on/off when using an external power supply, see the following manual of the
           connected PLC.
                                                   → Refer to the FX3G Series User's Manual - Hardware Edition.                                J
                                                   → Refer to the FX3U Series User's Manual - Hardware Edition.
                                                                                                                                           FX3U-4AD-PNK
                                                                                                                                                    -ADP
                                                                                                                              E-11
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                            3 Wiring
FX3U-4DA (4-channel Analog Output)                                                                        3.4 Analog Output Wiring
                                Class-D grounding
                                                                          *2
                           If voltage output is
                                 selected
                                                             ch
                                               Shield *3
                                                                   V+
                                                                   I+                         ch
                                                                   VI-
                             *4         *5
                           If current output is
                                 selected                    ch
                                               Shield *3           V+
                                                                   I+                         ch
VI-
                                        *5
                      ch    :     represents the channel number.
          *1.   For FX3G/FX3U Series PLC (AC power type), the 24V DC service power supply is also available.
          *2.   Do not connect any wires to the " • " terminal.
          *3.   Use a 2-core twisted shield wire for analog output wire, and separate it from other power lines or
                inductive lines.
          *4.   If there is ripple or noise in the output voltage, connect a capacitor of approximately 0.1 to 0.47µF 25V
                in the vicinity of the signal receiving side.
          *5.   Ground the shielded wire at one point on the signal receiving side.
3.5      Grounding
         Grounding should be performed as stated below.
         • The grounding resistance should be 100Ω or less.
         • Independent grounding should be performed for best results.
           When independent grounding is not performed, perform "shared grounding" as shown in the following
           figure.
                                  → For details, refer to the User’s Manual - Hardware Edition of each Series.
E-12
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                       4 Analog Output
FX3U-4DA (4-channel Analog Output)                                                                          4.1 Analog Output Procedures
                                                                                                                                                 Common Items
4.     Analog Output
         This chapter describes the minimum programming necessary for analog output by the FX3U-4DA.                                         B
         Follow the procedure below to confirm that correct analog values can be output.
                                                                                                                                           FX3UC-4AD
                                                                                                                                           FX3U-4AD
4.1      Analog Output Procedures
                                                                                                                                                 FX3U-4AD-ADP
         Unit numbers from 0 to 7 will be assigned to the special function units/blocks starting from the left.
         When the units/blocks are connected to the FX3UC-32MT-LT(-2) PLC, the unit numbers from 1 to 7
         are assigned. Check the unit number assigned to the FX3U-4DA.
                                                                                                                                                 FX3G-2AD-BD
                      Main unit     Input/output    Special        Special     Input/output       Special
                    (FX3U Series     extension                                  extension
                       PLC)            block     function block function block    block         function unit
                                                                                                                                                 FX3U-4DA
   2     Output mode (BFM #0) setting
         Depending on the analog signal generator to be connected, set the output mode (BFM #0) for each
         channel.
                                                                                                                                               F
                                                                                                                                                 FX3U-4DA-ADP
         Use hexadecimal numbers for output mode setting. Set the corresponding channel digit to the
         output mode setting value specified in the following table:
                                                  H                                                                                         G
                                               ch4                       ch1
                                                                                                                                                 FX3G-1DA-BD
                                               ch3                       ch2
          Setting
                                   Output mode                 Analog output range        Digital input range
           value
             0      Voltage output mode                            -10V to +10V               -32000 to +32000                               H
                                                                                                                                           FX3U-4AD-PT
                    Voltage output
             1                                                     -10V to +10V               -10000 to +10000
                    analog value mV specification mode
             2      Current output mode                            0mA to 20mA                   0 to 32000
                                                                                                                                                    -ADP
             4
                    Current output
                                                                   0mA to 20mA                   0 to 20000
                                                                                                                                                     I
                    analog value µA specification mode
                                                                                                                                           FX3U-4AD-PTW
→ For a detailed description of the output mode (BFM #0), refer to Subsection 5.4.1.
                                                                                                                                               J
                                                                                                                                           FX3U-4AD-PNK
                                                                                                                                                    -ADP
                                                                                                                              E-13
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                             4 Analog Output
FX3U-4DA (4-channel Analog Output)                                                                                4.1 Analog Output Procedures
                T0
                              FNC 15                                            Data (BMF #1 to 4) to be output to channels 1
                                           D0         U \G1           K4        to 4 are transferred from D0 to D3.
                               BMOV
E-14
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                               5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output)                                              5.1 Assignment of Unit Numbers and Outline of Buffer Memory
                                                                                                                                                    Common Items
5.     Buffer Memory (BFM)
         This chapter describes the buffer memory incorporated in FX3U-4DA.                                                                     B
                                                                                                                                              FX3UC-4AD
                                                                                                                                              FX3U-4AD
5.1      Assignment of Unit Numbers and Outline of Buffer Memory
                                                                                                                                                    FX3U-4AD-ADP
         When connected to the FX3G/FX3U/FX3UC (D, DSS) Series PLC
                                                                                                                                                    FX3G-2AD-BD
                                   Input/output    Special        Special     Input/output        Special
                    Main unit       extension                                  extension
                                      block     function block function block    block          function unit
                                                                                                                                                    FX3U-4DA
         When connected to the FX3UC-32MT-LT(-2) PLC
                  Unit number: 0
                  (Incorporated                     Unit           Unit                            Unit
                   CC-Link/LT)                    number: 1      number: 2                       number: 3
                                                                                                                                                  F
                                                                                                                                                    FX3U-4DA-ADP
                    Main unit      Input/output                               Input/output
                  (FX3UC-32MT       extension      Special        Special      extension          Special
                    -LT(-2))          block     function block function block    block          function unit
FX3G-1DA-BD
                                                                                                                                                H
                                                                                                                                              FX3U-4AD-PT
                                                                                                                                                       -ADP
                                                                                                                                                        I
                                                                                                                                              FX3U-4AD-PTW
                                                                                                                                                       -ADP
                                                                                                                                                  J
                                                                                                                                              FX3U-4AD-PNK
                                                                                                                                                       -ADP
                                                                                                                                 E-15
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                    5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output)                                                                      5.2 Buffer Memory Reading/Writing Method
          *1. Since buffer memory direct specification (U\G) can directly specify the buffer memory in the source
              or destination area of an applied instruction, programs can be created efficiently. (This function is supported
              only in FX3U/FX3UC PLCs.)
                                → For a detailed description of buffer memory reading/writing, refer to Section 5.2.
                                           → For a detailed description of the buffer memory, refer to Section 5.4.
E-16
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                              5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output)                                                              5.2 Buffer Memory Reading/Writing Method
                                                                                                                                             A
5.2.1     Buffer memory direct specification (FX3U, FX3UC PLC only)
                                                                                                                                                 Common Items
          When directly specifying the buffer memory, specify the following device in the source or destination area of
          the applied instruction as follows:
                                                                                                                                           FX3UC-4AD
                                                                                                                                           FX3U-4AD
                        Unit number (0 to 7)                 Buffer memory number (0 - 3098)
        1. Example 1
          If the following program is created, data in buffer memory (BFM #10) of unit 1 will be multiplied by the data
          (K10), and then the multiplication result will be output to the data registers (D10, D11).                                         C
                                                                                                                                                 FX3U-4AD-ADP
            READ command
                                         FNC 22     U1\G10    K10      D10
                                          MUL
                                                                                Multiplication result
                      Unit number
            Buffer memory number                                                Multiplier                                                   D
                                                                                                                                                 FX3G-2AD-BD
        2. Example 2
          If the following program is created, the value in the data register (D20) is added to K10 and written to buffer
          memory (BFM #6) of unit 1.
           WRITE command
                                                                                                                                              E
                                        FNC 20
                                                                                                                                                 FX3U-4DA
                                                     D20     K10      U1\G6
                                         ADD
                                                                               Addition
                                                                               result     ( Unit
                                                                                            Buffer memory number )
                                                                                                 number
                         Augend                                                Addend
                                                                                                                                               F
                                                                                                                                                 FX3U-4DA-ADP
5.2.2     FROM/TO instruction (FX3G, FX3U, FX3UC PLC)
                                                                                                                                                 FX3G-1DA-BD
           READ command
                               FNC 78          K1    K10     D10        K1
                               FROM
                                                                               Number of transfer
                     Unit number                                               data points
            Buffer memory number                                               Transfer-to register                                          H
                                                                                                                                           FX3U-4AD-PT
          If the above program is created, 1 point of data will be read out from the buffer memory BFM #10 of unit No.1
          to the data register (D10).
                                                                                                                                                    -ADP
           WRITE command
                               FNC 79          K1    K0      H3300      K1
                                 TO
                                                                                                                                                    -ADP
                                                                               Number of transfer
                      Unit number                                              data points
            Buffer memory number                                               Transfer source
                                                                                                                                               J
                                                                                                                                           FX3U-4AD-PNK
          If the above program is created, 1 point of data (H3300) will be written to buffer memory (BFM #0) of unit
          No.1.
                                                                                                                                                    -ADP
                                                                                                                              E-17
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                           5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output)                                                                                        5.3 Buffer Memory List (BFM)
       BFM number                            Description                         Setting range       Initial value      Data type      Reference
                                                                                                                        Hexadeci-      Subsection
            #0*1          Output mode setting for channels 1 to 4                       *2          H0000 at delivery
                                                                                                                          mal            5.4.1
            #1            Channel 1 output data                                                            K0            Decimal
            #2            Channel 2 output data                                  Depending on the          K0            Decimal       Subsection
            #3            Channel 3 output data                                    mode used               K0            Decimal         5.4.2
           #11   *1       Channel-2 offset data (Unit: mV or µA)                 Depending on the     Depending on       Decimal       Subsection
                          Channel-3 offset data (Unit: mV or µA)                   mode used         the mode used                       5.4.6
           #12*1                                                                                                         Decimal
           #15   *1       Channel-2 gain data (Unit: mV or µA)                   Depending on the     Depending on       Decimal       Subsection
                 *1       Channel-3 gain data (Unit: mV or µA)                     mode used         the mode used       Decimal         5.4.6
           #16
           *1.        If power failure occurs, the EEPROM will retain the data.
           *2.        Specify the output mode of each channel setting one of hex code 0 to 4 and F in each digit.
           *3.        Specify the data to be output from each channel upon PLC stop setting one of hex code 0 to 2 in each
                      digit.
           *4.        Use b0 to b3.
E-18
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                         5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output)                                                                                    5.3 Buffer Memory List (BFM)
                                                                                                                                                           Common Items
       BFM number                            Description                        Setting range      Initial value    Data type      Reference
                          Data to be output from channel 1 upon PLC stop Depending on the
           #32*1          (Valid only if BFM #5 = H      2)                mode used
                                                                                                        K0           Decimal
           #33*1
                          Data to be output from channel 2 upon PLC stop Depending on the
                                                                                                        K0           Decimal                           B
                          (Valid only if BFM #5 = H   2 )                  mode used                                               Subsection
                                                                                                                                                     FX3UC-4AD
                                                                                                                                                     FX3U-4AD
                          Data to be output from channel 3 upon PLC stop Depending on the                                            5.4.12
           #34*1                                                                                        K0           Decimal
                          (Valid only if BFM #5 = H 2      )               mode used
                          Data to be output from channel 4 upon PLC stop Depending on the
           #35*1                                                                                        K0           Decimal
                          (Valid only if BFM #5 = H2       )               mode used
         #36, #37         Not used                                                     -                 -               -               -
                                                                                                                                                       C
                                                                                                                     Hexadeci-     Subsection
                                                                                                                                                           FX3U-4AD-ADP
            #38           Upper/lower limit function setting                           *2             H0000
                                                                                                                       mal           5.4.13
                                                                                                                     Hexadeci-     Subsection
            #39           Upper/lower limit function status                            -              H0000
                                                                                                                       mal           5.4.14
                                                                                                                     Hexadeci-     Subsection
            #40           Clear of upper/lower limit function status                   *3             H0000
                                                                                                                                                           FX3G-2AD-BD
            #42           Channel-2 lower limit of upper/lower limit function   Depending on the     K-32640         Decimal       Subsection
            #43           Channel-3 lower limit of upper/lower limit function     mode used          K-32640         Decimal         5.4.16
                                                                                                                                                           FX3U-4DA
            #47           Channel-3 upper limit of upper/lower limit function     mode used          K32640          Decimal         5.4.16
                                                                                                                                                           FX3U-4DA-ADP
           #52*1          Load resistance value for channel 2 (Unit: Ω)         K1000 to K30000      K30000          Decimal        Subsection
                 *1       Load resistance value for channel 3 (Unit: Ω)         K1000 to K30000      K30000          Decimal         5.4.17
           #53
           #54*1          Load resistance value for channel 4 (Unit: Ω)         K1000 to K30000      K30000          Decimal
         #55 to #59       Not used                                                     -                 -               -               -            G
                                                                                                                                   Subsection
                                                                                                                                                           FX3G-1DA-BD
           #60*1          Status automatic transfer function setting                   *5               K0           Decimal
                                                                                                                                     5.4.18
                          Error status data (BFM #29) automatic transfer-
                                                                                                                                   Subsection
           #61*1          to data register specification (Valid if b0 of BFM                          K200           Decimal
                                                                                                                                     5.4.19
                          #60 is set to ON)
                                                                             K0 to 7999 (BFM
           #62*1
                          Upper/lower limit function status data (BFM #39)
                          automatic transfer-to data register specification
                                                                            #61, #62 and #63
                                                                                                      K201           Decimal
                                                                                                                                   Subsection          H
                                                                            must have different                                      5.4.20
                                                                                                                                                     FX3U-4AD-PT
           *1.        If power failure occurs, the EEPROM will retain the data.
                                                                                                                                                               I
                                                                                                                                                     FX3U-4AD-PTW
           *2.        Specify the use of the upper/lower limit function for each channel setting one of hex code 0 to 2 in
                      each digit.
           *3.        Use b0 to b1.
                                                                                                                                                              -ADP
           *4.        Specify the use of the corrective function by load resistance for each channel setting a hex code 0 or
                      1 in each digit.                                                                                                                   J
                                                                                                                                                     FX3U-4AD-PNK
                                                                                                                                        E-19
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output)                                                                           5.3 Buffer Memory List (BFM)
       BFM number                       Description                       Setting range   Initial value    Data type      Reference
                                                                                                            Hexadeci-
            #80         Start/stop of table output function                    *1            H0000
                                                                                                              mal
            #81         Channel-1 output pattern                            K1 to K10          K1           Decimal
            #82         Channel-2 output pattern                            K1 to K10          K1           Decimal
            #83         Channel-3 output pattern                            K1 to K10          K1           Decimal
            #84         Channel-4 output pattern                            K1 to K10          K1           Decimal
                        Number of times of output execution of table
            #85                                                           K0 to K32767         K0           Decimal
                        from channel 1
                        Number of times of output execution of table                                                       Chapter 6
            #86                                                           K0 to K32767         K0           Decimal
                        from channel 2
                        Number of times of output execution of table
            #87                                                           K0 to K32767         K0           Decimal
                        from channel 3
                        Number of times of output execution of table
            #88                                                           K0 to K32767         K0           Decimal
                        from channel 4
                                                                                                            Hexadeci-
            #89         Output completion flag of table output function         -            H0000
                                                                                                              mal
            #90         Table output error code                                 -              K0           Decimal
            #91         Table output error occurrence number                    -              K0           Decimal
         #92 to #97     Not used                                                -               -               -               -
            #98         Head device number in data table                  K0 to K32767       K1000          Decimal
                                                                                                            Hexadeci-
            #99         Data table transfer command                            *2            H0000                         Chapter 6
                                                                                                              mal
        #100 to #398 Data table in pattern 1                                    -              K0           Decimal
           #399         Not used                                                -               -               -               -
        #400 to #698 Data table in pattern 2                                    -              K0           Decimal        Chapter 6
           #699         Not used                                                -               -               -               -
        #700 to #998 Data table in pattern 3                                    -              K0           Decimal        Chapter 6
           #999         Not used                                                -               -               -               -
          #1000 to
                        Data table in pattern 4                                 -              K0           Decimal        Chapter 6
           #1298
           #1299        Not used                                                -               -               -               -
          #1300 to
                        Data table in pattern 5                                 -              K0           Decimal        Chapter 6
           #1598
           #1599        Not used                                                -               -               -               -
          #1600 to
                        Data table in pattern 6                                 -              K0           Decimal        Chapter 6
           #1898
           #1899        Not used                                                -               -               -               -
          #1900 to
                        Data table in pattern 7                                 -              K0           Decimal        Chapter 6
           #2198
           #2199        Not used                                                -               -               -               -
          #2200 to
                        Data table in pattern 8                                 -              K0           Decimal        Chapter 6
           #2498
           #2499        Not used                                                -               -               -               -
          #2500 to
                        Data table in pattern 9                                 -              K0           Decimal        Chapter 6
           #2798
           #2799        Not used                                                -               -               -               -
          #2800 to
                        Data table in pattern 10                                -              K0           Decimal        Chapter 6
           #3098
            *1.       Specify whether to start or stop the table output function for each channel setting a hex code 0 or 1
                      in each digit.
            *2.       Specify the data table transfer command and the register type setting 0 or 1 in the last two digits of
                      the hex code.
E-20
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                    5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output)                                                                   5.4 Buffer Memory Details
                                                                                                                                   A
5.4       Buffer Memory Details
                                                                                                                                       Common Items
5.4.1     BFM #0: Output mode specification
                                                                                                                                 FX3UC-4AD
                                                                                                                                 FX3U-4AD
          Specify the output modes of channel 1 to 4.
          4 hexadecimal digits are assigned to specify the output modes of the 4 channels.
          Change the value of each digit to change the output mode of each channel. 0 to 4 and F can be set for each
          digit.
                                                                                                                                   C
             H
                                                                                                                                       FX3U-4AD-ADP
           ch4                      ch1
           ch3                      ch2
          The different types of output modes are shown in the following table:
                                        → For a detailed description of output characteristics, refer to Section 2.4.              D
                                                                                                                                       FX3G-2AD-BD
            Set value
                                     Output mode               Analog output range     Digital input range
             [HEX]
                   0      Voltage output mode                     -10V to +10V          -32000 to +32000
                          Voltage output
                  1*1     analog value mV specification mode
                                                                  -10V to +10V          -10000 to +10000
                                                                                                                                    E
                   2      Current output mode                     0mA to 20mA               0 to 32000
                                                                                                                                       FX3U-4DA
                   3      Current output mode                     4mA to 20mA               0 to 32000
                          Current output
                  4*1     analog value µA specification mode
                                                                  0mA to 20mA               0 to 20000
                                                                                                                                       FX3U-4DA-ADP
           *1.     The offset/gain values cannot be changed.
        1. Cautions regarding output mode setting
          • While the output mode is being changed, the output is stopped, and H0000 is automatically written in the
            output status (BFM #6).
            At the completion of change of the output mode, the output status (BFM #6) will automatically change to
                                                                                                                                  G
                                                                                                                                       FX3G-1DA-BD
            H1111, and the output is restarted.
          • It takes approximately 5 seconds to determine the output mode.
            For this reason, after changing the output mode, be sure to wait for 5 seconds or more, and then write the
            other data.
          • When the output mode is changed, the settings in the following buffer memory are initialized according to
            the new output mode.                                                                                                   H
                                                                                                                                 FX3U-4AD-PT
                *3 These settings are initialized only when the output mode is changed from current output mode
                   (mode 2, 3 or 4) to voltage output mode (mode 0 or 1).
                                                                                                                                          -ADP
                                                                                                                    E-21
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                       5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output)                                                                      5.4 Buffer Memory Details
                                                                                                       Initial value: K0
                                                                                        Numeric data type: Decimal (K)
Input the digital values corresponding to the analog signals to be output in BFM #1 to #4.
It is possible to set the output conditions from channel 1 to 4 when the PLC is in the stopped state.
             H
           ch4                       ch1
           ch3                       ch2
E-22
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                       5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output)                                                                      5.4 Buffer Memory Details
                                                                                                                                      A
5.4.4     BFM #6: Output status
                                                                                                                                          Common Items
                                                                                                   Initial value: H0000
                                                                                   Numeric data type: Hexadecimal (H)
                                                                                                                                    FX3UC-4AD
                                                                                                                                    FX3U-4AD
             H
           ch4                       ch1
           ch3                       ch2
                                                                                                                                      C
                                                                                                                                          FX3U-4AD-ADP
            Value status (HEX)                             Description
                      0            Output updating is stopped.*
                      1            Under output updating
          * The output conditions conform to the output setting upon PLC stop (BFM #5).
                                                                                                                                      D
        1. Cautions regarding use of output status
                                                                                                                                          FX3G-2AD-BD
          • The output status setting is valid only if the PLC is running.
            When the PLC is stopped, H0000 is automatically written.
          • When the setting in any of the following buffer memory areas is changed, output updating is stopped.
            H0000 is automatically written in BFM #6.
                                                                                                                                       E
                 •   BFM #0 (Output mode setting)
                                                                                                                                          FX3U-4DA
                 •   BFM #5 (Output setting upon PLC stop)
                 •   BFM #9 (Offset/gain setting value write command)
                 •   BFM #19 (Setting change prohibition)
                 •   BFM #20 (Initialization function)                                                                                  F
                 •   BFM #32 to #35 (Data to be output from each channel upon PLC stop)
                                                                                                                                          FX3U-4DA-ADP
                 •   BFM #50 (Corrective function setting by load resistance)
                 •   BFM #51 to #54 (Load resistance for each channel)
                 •   BFM #60 (Status automatic transfer function Setting)
                 •   BFM #61 (Error status data automatic transfer-to data register specification)                                   G
                                                                                                                                          FX3G-1DA-BD
                 •   BFM #62 (Upper/lower limit function status with automatic transfer to specified data register)
                 •   BFM #63 (Disconnection detection status with automatic transfer to data register specification)
                 •   BFM #99 (Data table transfer command)
                                                                                                                                      H
                                                                                                                                    FX3U-4AD-PT
                                                                                                                                             -ADP
                                                                                                                                              I
                                                                                                                                    FX3U-4AD-PTW
                                                                                                                                             -ADP
                                                                                                                                        J
                                                                                                                                    FX3U-4AD-PNK
                                                                                                                                             -ADP
                                                                                                                       E-23
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                     5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output)                                                                   5.4 Buffer Memory Details
          The WRITE command can be given to two or more channels at the same time. (Set "H000F" to write the data
          of all the channels in the EEPROM.)
          On completion of writing, "H0000" (b0 to b3: OFF) will be set automatically.
E-24
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output)                                                                                 5.4 Buffer Memory Details
                                                                                                                                                 A
5.4.6     BFM #10 to #13: Offset data/BFM #14 to #17: Gain data
                                                                                                                                                     Common Items
                                                                                                       Setting range: See below
                                                                                                          Initial value: See below
                                                                                                   Numeric data type: Decimal (K)
          If the output mode is specified in BFM #0, the initial value of the offset data and gain data of each channel will
                                                                                                                                                 B
                                                                                                                                               FX3UC-4AD
                                                                                                                                               FX3U-4AD
          be automatically stored.
          The initial offset data and the gain data are set for each mode as shown in the following table:
          • Offset data: Analog output value when the output data in BFM #1 to #4 are 0 (reference offset value)
          • Gain data: Analog output value when the output data in BFM #1 to #4 are the reference gain values (The
            reference gain value depends on the set output mode.)                                                                                C
                                                                                                                                                     FX3U-4AD-ADP
        1. Reference offset/gain value and initial value set
                                                                  Offset (channels 1 to 4:               Gain (channels 1 to 4:
                           Output mode (BFM #0)
                                                                     BFM #10 to #13)                       BFM #14 to #17)
                                                                 Reference                             Reference
           Set value                  Description                                  Initial value                          Initial value
                                                                   value                                 value                                   D
                          Voltage output
                                                                                                                                                     FX3G-2AD-BD
                  0                                                  0                  0mV              16000              5000mV
                          (-10 V to +10 V: -32000 to +32000)
                          Voltage output Analog value mV              0              0mV                  5000             5000mV
                  1       specification mode                    (Data change     (Data change         (Data change      (Data change
                          (-10 V to +10 V: -10000 to +10000)     impossible)      impossible)          impossible)       impossible)
                  2
                          Current output
                                                                     0                  0µA              16000             10000µA                E
                          (0 mA to 20 mA: 0 to 32000)
                                                                                                                                                     FX3U-4DA
                          Current output
                  3                                                  0               4000µA              16000             12000µA
                          (4 mA to 20 mA: 0 to 32000)
                          Current output Analog value µA              0              0µA                 10000            10000µA
                  4       specification mode                    (Data change     (Data change         (Data change      (Data change
                          (0 mA to 20 mA: 0 to 20000)            impossible)      impossible)          impossible)       impossible)               F
                                                                                                                                                     FX3U-4DA-ADP
        2. Offset/gain data change
          Set offset data and gain data to change the output characteristics.
          The offset and gain data can be set for each channel. If the voltage output mode is set, write the offset and
          gain data in mV. If the current output mode is set, write the offset and gain data in µA.
          To change the offset or gain data, execute the offset/gain setting value write command (BFM #9).
                                                                                                                                                G
                                                                                                                                                     FX3G-1DA-BD
          The setting range is shown in the following table.
            *1.       The offset and gain values should meet the following conditions:
                      1000 ≤ Gain value - Offset value ≤ 10000
            *2.       The offset and gain values should meet the following conditions:
                                                                                                                                                        -ADP
                                                                                                                                                   J
                                                                                                                                               FX3U-4AD-PNK
                                                                                                                                                        -ADP
                                                                                                                                  E-25
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                     5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output)                                                                    5.4 Buffer Memory Details
          • The offset and gain data should be set before the value write command BFM #9 is executed.
          • The resolution cannot be increased by changing the output characteristics.
          • When the value specified as the output mode (BFM #0) is changed, the initial value of offset and gain data
            in each output mode will be automatically written.
          • Even if the output characteristics are changed, the actual valid output range will not be changed:
            -10 V to +10 V for the voltage output mode, and 0 mA to 20 mA in the current output mode.
                                → For a detailed description of output characteristics change, refer to Chapter 7.
Specify the following value as the setting change prohibition mode (BFM #19).
E-26
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                      5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output)                                                                       5.4 Buffer Memory Details
                                                                                                                                       A
5.4.8     BFM #20: Initialization function (resetting to factory default status)
                                                                                                                                           Common Items
                                                                                             Setting range: K0 or K1
                                                                                                      Initial value: K0
                                                                                       Numeric data type: Decimal (K)
          When K1 is set in BFM #20, all functions and all buffer memory (BFM #0 to #3098) will be initialized to the                  B
          default status.
                                                                                                                                     FX3UC-4AD
                                                                                                                                     FX3U-4AD
          When BFM #20 is not K0 or K1, this function is invalid. (The settings will not be changed, and the functions
          will not be initialized.)
                                                                                                                                           FX3U-4AD-ADP
            output will be restarted.
          • It takes approximately 5 seconds to initialize all the data. Do not set (write) data in the buffer memory
            during this period.
          • Priority is given to the setting of the value change prohibition mode (BFM #19).
          • At the completion of initialization, the value of BFM #20 will automatically change to K0.
                                                                                                                                       D
                                                                                                                                           FX3G-2AD-BD
5.4.9     BFM #28: Disconnection detection status (only in current output mode)
                                                                                                  Initial value: H0000
                                                                                  Numeric data type: Hexadecimal (H)                    E
                                                                                                                                           FX3U-4DA
          When a wire-break is detected, the bit corresponding to the relevant channel will turn on.
                                                                                                                                           FX3U-4DA-ADP
                   b1            Wire-break in channel 2
                   b2            Wire-break in channel 3
                   b3            Wire-break in channel 4
               b4 to b15                Not used
                                                                                                                                      G
                                                                                                                                           FX3G-1DA-BD
        2. Cautions regarding use of disconnection detection status
          • When any of b0 to b3 is turned on, b11 of the error status (BFM #29) is turned on.
          • The disconnection detection status is valid only if the output mode (BFM #0) is the current output mode
            (mode 2 to 4). In other output modes, each corresponding bit of BFM #28 stays off.
          If the disconnection detection status with automatic transfer-to data register is specified in BFM #63, the data
          in BFM #28 can be transferred to the specified data register.
          Only when wire-break is detected, data will be automatically transferred from FX3U-4DA to the PLC. For this
                                                                                                                                              -ADP
          reason, the PLC does not need the program for reading data, and the scan time of the PLC can be shortened.
                → For a detailed description of the status automatic transfer function, refer to Subsection 5.4.18.
                                                                                                                                               I
                                                                                                                                     FX3U-4AD-PTW
                                                                                                                                              -ADP
                                                                                                                                         J
                                                                                                                                     FX3U-4AD-PNK
                                                                                                                                              -ADP
                                                                                                                        E-27
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                              5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output)                                                                             5.4 Buffer Memory Details
E-28
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                    5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output)                                                                   5.4 Buffer Memory Details
                                                                                                                                   A
5.4.11 BFM #30: Model code
                                                                                                                                       Common Items
                                                                                     Initial value (at delivery): K3030
                                                                                     Numeric data type: Decimal (K)
         K3030 (fixed value) is stored as the model code.
                                                                                                                                   B
                                                                                                                                 FX3UC-4AD
                                                                                                                                 FX3U-4AD
5.4.12 BFM #32 to #35: Data to be output upon PLC stop
                                                                                                    Initial value: K0
                                                                                     Numeric data type: Decimal (K)
         To enable the output data set when the PLC stops, Set "2" for any digit in the output data (H0000) at PLC's               C
         stop. Set the BFM values as follows.
                                                                                                                                       FX3U-4AD-ADP
             BFM number              Description
                 #32               Data in channel 1
                 #33               Data in channel 2
                 #34               Data in channel 3                                                                               D
                 #35               Data in channel 4
                                                                                                                                       FX3G-2AD-BD
         The setting range depends on the output mode.
                                                                                                                                       FX3U-4DA
                    2, 3                     0 to 32640
                       4                     0 to 20400
                                                                                                                                     F
      1. Cautions regarding data output setting when PLC is in stop
                                                                                                                                       FX3U-4DA-ADP
         • While changing the settings, the output is stopped, and H0000 is automatically written in the output status
           (BFM #6).
           After the completion of writing, the output status (BFM #6) will automatically change to H1111, and output
           will be restarted.
         • The analog values to be output depend on the output mode.                                                              G
                                                                                                                                       FX3G-1DA-BD
         • When a value out of any of the above ranges is set, b5 of the error status (BFM #29) is turned on.
                                                                                                                                           I
                                                                                                                                 FX3U-4AD-PTW
                                                                                                                                          -ADP
                                                                                                                                     J
                                                                                                                                 FX3U-4AD-PNK
                                                                                                                                          -ADP
                                                                                                                    E-29
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                             5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output)                                                                          5.4 Buffer Memory Details
            H
          ch4                         ch1
          ch3                         ch2
          *1.    When any value becomes less than the lower limit (BMF #41 to #44) or more than the upper limit
                 (BFM #45 to #48), the relevant bit of the upper/lower limit function status is turned on.
Upper limit
                  Lower limit
                                                         The value is output even if it is
                                                         below the lower limit.
          *2.    When any value becomes less than the lower limit (BMF #41 to #44) or more than the upper limit
                 (BFM #45 to #48), the relevant bit of the upper/lower limit function status is turned on.
                 In this setting, analog values more than the upper limit and less than the lower limit are not output.
                       Analog value         Values more than the upper limit are not
                                            output.
                  Upper limit
                  Lower limit
                                                         Values less than the lower limit are
                                                         not output.
E-30
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                     5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output)                                                                   5.4 Buffer Memory Details
                                                                                                                                   A
5.4.14 BFM #39: Upper/lower limit function status
                                                                                                                                       Common Items
                                                                                                  Initial value: H0000
                                                                                  Numeric data type: Hexadecimal (H)
         When any of the output data (BFM #1 to #4) is out of range between the lower limit and the upper limit (BFM
         #41 to #48), the relevant bit is turned on.                                                                               B
                                                                                                                                 FX3UC-4AD
                                                                                                                                 FX3U-4AD
      1. Assignment to each bit of BFM #39
               Bit                                 Description
          b0            Data output from channel 1 < Lower limit (BFM #41)
          b1            Data output from channel 1 > Upper limit (BFM #45)                                                         C
          b2            Data output from channel 2 < Lower limit (BFM #42)
                                                                                                                                       FX3U-4AD-ADP
          b3            Data output from channel 2 > Upper limit (BFM #46)
          b4            Data output from channel 3 < Lower limit (BFM #43)
          b5            Data output from channel 3 > Upper limit (BFM #47)
          b6            Data output from channel 4 < Lower limit (BFM #44)                                                         D
          b7            Data output from channel 4 > Upper limit (BFM #48)
                                                                                                                                       FX3G-2AD-BD
          b8 to b15     Not used
                                                                                                                                       FX3U-4DA
         • The upper/lower limit function status can be reset by the following methods.
           - Use the upper/lower limit function status reset function (BFM #40).
           - Turn the power supply off then on.
                                                                                                                                       FX3U-4DA-ADP
         transferred to a specified data register.
         Only when an error is detected, data will be automatically transferred from the FX3U-4DA to the PLC. For this
         reason, the PLC does not need the program for reading data, and the scan time of the PLC can be shortened.
               → For a detailed description of the status automatic transfer function, refer to Subsection 5.4.18.
                                                                                                                                  G
5.4.15 BFM #40: Clearance of upper/lower limit function status
                                                                                                                                       FX3G-1DA-BD
                                                                                                  Initial value: H0000
                                                                                  Numeric data type: Hexadecimal (H)
         The flags can be reset by turning on the following bits of BFM #40.
                                                                                                                                   H
      1. Assignment to each bit of BFM #40
                                                                                                                                 FX3U-4AD-PT
               Bit                  Description
               b0          Clearance of lower limit status
                                                                                                                                          -ADP
                                                                                                                                     J
                                                                                                                                 FX3U-4AD-PNK
                                                                                                                                          -ADP
                                                                                                                    E-31
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                          5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output)                                                                        5.4 Buffer Memory Details
5.4.16 BFM #41 to #44: Lower limit values of upper/lower limit function
       BFM #45 to #48: Upper limit values of upper/lower limit function
E-32
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                  5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output)                                                                                  5.4 Buffer Memory Details
                                                                                                                                                  A
5.4.17 BFM #50: Setting of output corrective function by load resistance
                                                                                                                                                      Common Items
       (only in voltage output mode)/BFM #51 to #54: Load resistance values
         The output characteristics of FX3U-4DA have been adjusted at 30 kΩ load resistance as a factory default.
                                                                                                                                                  B
                                                                                                                                                FX3UC-4AD
                                                                                                                                                FX3U-4AD
         When the load resistance is 1kΩ, the output deviation is approx. -4.3% to 20V in full scale, whereas the
         output deviation is approx. 0.15% to 20V in full scale when the load resistance is 1MΩ. When the load
         resistance is 30 kΩ or less (1 kΩ to 30 kΩ), the deviation of the output characteristics can be corrected by
         specifying the output corrective function (BFM #50) and the load resistance values (BFM #51 to #54).
Analog value C
                                                                                                                                                      FX3U-4AD-ADP
                                                     The deviation of output characteristics is
                                                     corrected by the corrective function by load
                           +10V                      resistance.
                -32000                                                                                                                            D
                                         32000 Digital value
                                                                                                                                                      FX3G-2AD-BD
                                                    : Output characteristics after correction
                                                                                                                                                      FX3U-4DA
      1. Setting of output corrective function (BFM #50)
         The corrective function by load resistance is valid or invalid by writing a 4-digit hexadecimal number,
         H        , in the output corrective function setting (BFM #50).
                                                                                                                                                    F
            H
                                                                                                                                                      FX3U-4DA-ADP
          ch4                            ch1
          ch3                            ch2
                                                                                                                                                      FX3G-1DA-BD
                      0             Corrective function by load resistance is invalid.
                      1             Corrective function by load resistance is valid.
           Other than above
                                    Invalid (setting values unchanged)
                values
      2. Setting range and initial value of load resistance (BFM #51 to #54)                                                                      H
                                                                                                                                                FX3U-4AD-PT
Set the load resistance value for each channel allocated to the following BFM.
             BFM
                                            Description                     Setting range (Ω)       Initial value (Ω)
                                                                                                                                                         -ADP
            number
                #51            Load resistance value for channel 1
                #52            Load resistance value for channel 2                                                                                        I
                                                                               1000 to 30000             30000
                                                                                                                                                FX3U-4AD-PTW
                                                                                                                                                    J
                                                                                                                                                FX3U-4AD-PNK
                                                                                                                                                         -ADP
                                                                                                                                   E-33
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                        5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output)                                                                     5.4 Buffer Memory Details
         When the bits, b0 to b2, of BFM #60 are turned on, the assigned functions (see the table below) are valid.
         When the bits are turned off, the functions are invalid.
E-34
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                     5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output)                                                                   5.4 Buffer Memory Details
                                                                                                                                   A
5.4.19 BFM #61: Error status data automatic transfer-to data register specification
                                                                                                                                       Common Items
                                                                                            Setting range: 0 to 7999
                                                                                                  Initial value: K200
                                                                                      Numeric data type: Decimal (K)
         Use this function to automatically transfer the error status data (BFM #29) to the data register specified in
                                                                                                                                   B
                                                                                                                                 FX3UC-4AD
                                                                                                                                 FX3U-4AD
         BFM #61.
         When an error is detected, data will be automatically transferred from FX3U-4DA to the PLC. For this reason,
         the PLC does not need a program for reading data, and the scan time of the PLC can be shortened.
                           → For a detailed description of the error status (BFM #29), refer to Subsection 5.4.12.
                                                                                                                                       FX3U-4AD-ADP
            Specified data
                                         Description
              register
                 D200         Value of error status (BFM #29)
                                                                                                                                       FX3G-2AD-BD
           register.
         • This function is valid by turning on b0 of the status automatic transfer function setting (BFM #60).
         • When a value out of the above setting range is set, b9 of the error status BFM #29 is turned on.
         • The data set in BFM #61 will be retained in the EEPROM.
                                                                                                                                    E
      3. Cautions regarding EEPROM writing
                                                                                                                                       FX3U-4DA
         If data is set in BFM #0, #5, #10 to #17, #32 to #35, #50 to #54 or #60 to #63, the data will be written in the
         EEPROM of FX3U-4DA.
         Do not turn off the power immediately after writing values in these buffer memories.
         The maximum number of EEPROM rewritable times is 10,000. Therefore, when creating a program, do not
         frequently write data in the above buffer memories (BFM).                                                                   F
                                                                                                                                       FX3U-4DA-ADP
                                                                                                                                  G
FX3G-1DA-BD
                                                                                                                                   H
                                                                                                                                 FX3U-4AD-PT
                                                                                                                                          -ADP
                                                                                                                                           I
                                                                                                                                 FX3U-4AD-PTW
                                                                                                                                          -ADP
                                                                                                                                     J
                                                                                                                                 FX3U-4AD-PNK
                                                                                                                                          -ADP
                                                                                                                    E-35
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                     5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output)                                                                   5.4 Buffer Memory Details
5.4.20 BFM #62: Upper/lower limit function status data automatic transfer-to data register
       specification
         Use this function to automatically transfer the upper/lower limit function status data (BFM #39) to the data
         register specified in BFM #62.
         Only when the value becomes more than the upper limit or less than the lower limit, data will be automatically
         transferred from FX3U-4DA to the PLC. For this reason, the PLC does not need the program to read data, and
         the scan time of the PLC can be shortened.
                                  → For a detailed description of the upper/lower limit function status (BFM #39),
                                                                                           refer to Subsection 5.4.14.
            Specified data
                                                    Description
              register
                 D201         Value of upper/lower limit function status (BFM #39)
       2. Cautions regarding upper/lower limit function status automatic transfer function setting
         • If a data is already specified for the other automatic transfer functions, do not specify the same data
           register.
         • This function is valid by turning on b1 of the status automatic transfer function setting (BFM #60).
         • When a value out of the above setting range is set, b9 of the error status BFM #29 is turned on.
         • The data set in BFM #62 will be retained in the EEPROM.
E-36
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                     5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output)                                                                   5.4 Buffer Memory Details
                                                                                                                                   A
5.4.21 BFM #63: Specification of data register for automatic transfer at disconnection
                                                                                                                                       Common Items
       detection
                                                                                                                                 FX3UC-4AD
                                                                                                                                 FX3U-4AD
         Use this function to automatically transfer the disconnection detection status data (BFM #28) to the data
         register specified in BFM #63.
         Only when wire-break is detected, data will be automatically transferred from FX3U-4DA to the PLC. For this
         reason, the PLC does not need the program for reading data, and the scan time of the PLC can be shortened.
                                   → For a detailed description of the disconnection detection status (BFM #28),
                                                                                          refer to Subsection 5.4.9.               C
                                                                                                                                       FX3U-4AD-ADP
      1. If "BFM #63 = K202 (initial value)"
            Specified data
                                                    Description
              register
                 D202         Value of disconnection detection status (BFM #28)
                                                                                                                                   D
                                                                                                                                       FX3G-2AD-BD
      2. Cautions regarding disconnection detection status automatic transfer function setting
         • If a data is already specified for the other automatic transfer functions, do not specify the same data
           register.
         • This function is valid by turning on b2 of the status automatic transfer function setting (BFM #60).
         • When a value out of the above setting range is set, b9 of the error status BFM #29 is turned on.                         E
                                                                                                                                       FX3U-4DA
         • The data set in BFM #63 will be retained in the EEPROM.
                                                                                                                                       FX3U-4DA-ADP
         frequently write data in the above buffer memories (BFM).
                                                                                                                                       FX3G-1DA-BD
         BFM #80 (start/stop command of table output function)
         BFM #81 to #84 (output pattern setting of channels)
         BFM #85 to #88 (output execution cycle number of channels)
         BFM #89 (completion flag of table output function)
         BFM #90 (table output error code)
         BFM #91 (table output error source number)                                                                                H
         BFM #98 (data table head device number)
                                                                                                                                 FX3U-4AD-PT
         Table output function: Sets predetermined output patterns as data table, and outputs analog signals
                                according to the data table.
                                     → For a detailed description of the table output function, refer to Chapter 6.
                                                                                                                                           I
                                                                                                                                 FX3U-4AD-PTW
                                                                                                                                          -ADP
                                                                                                                                     J
                                                                                                                                 FX3U-4AD-PNK
                                                                                                                                          -ADP
                                                                                                                    E-37
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                       6 Table Output Function
FX3U-4DA (4-channel Analog Output)                                                               6.1 Outline of Table Output Function
                  Transfer of data table*                             The data table is transferred from the PLC main
                                                                      unit to the relevant buffer memory of FX3U-4DA.
                                 Refer to Section 6.4
* It is possible to write the data table directly in FX3U-4DA using a program (TO instruction, etc.).
E-38
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                         6 Table Output Function
FX3U-4DA (4-channel Analog Output)                                                                                      6.2 Preparation of data table
                                                                                                                                                          A
6.2      Preparation of data table
                                                                                                                                                              Common Items
      1. Outline of data table
         The data table to be prepared in the PLC consists of the following items.
         (1) Number of patterns (1 to 10 patterns)
         (2) Each pattern
                                                                                                                                                          B
                                                                                                                                                        FX3UC-4AD
                                                                                                                                                        FX3U-4AD
           (3) Number of points in each pattern (1 to 99 points)
           (4) Condition after output at final point in each pattern
           (5) Points in each pattern
               (6) Data to be output at each point
               (7) Output update time at each point
               (8) Unit of output update time at each point, and point-to-point interpolation method                                                      C
                                                                                                                                                              FX3U-4AD-ADP
      2. Preparation of data table
         Prepare the data table consisting of the following items in the data registers (D1000 to D7999) in the PLC
         main unit or the expansion registers (R0 to R32767).
         It is convenient to prepare the data table on spreadsheet software and copy and paste the data to the device
         memory of GX Developer.
                                                                                                                                                          D
                                                                                                                                                              FX3G-2AD-BD
                                                Setting item                                Device number in PLC assignment
          (1) Number of patterns (x)                                                     Device number specified in BFM #98
                          (3) Number of points in pattern 1 (n)                          Device number+1 specified in BFM #98
          (2) Pattern 1
                          (4) Condition after output at final point in pattern           Device number+2 specified in BFM #98
                                         (6) Output data                                 Device number+3 specified in BFM #98                              E
                                         (7) Output update time                          Device number+4 specified in BFM #98
                                                                                                                                                              FX3U-4DA
                          (5) Point 1
                                         (8) Unit of output update time at each point,
                                                                                         Device number+5 specified in BFM #98
                                         and point-to-point interpolation method
                                .                               .                                              .
                                .                               .                                              .
                                .                               .                                              .                                            F
                                         (6) Output data
                                                                                                                                                              FX3U-4DA-ADP
                                         (7) Output update time
                          (5) Point n
                                         (8) Unit of output update time at each point,
                                         and point-to-point interpolation method
            .                                            .
            .                                            .                                                                                               G
            .                                            .
                                                                                                                                                              FX3G-1DA-BD
                          (3) Number of points in pattern X (m)
          (2) Pattern X
                                .                               .
                                                                                                               .
                                         (6) Output data
                                         (7) Output update time
                                                                                                               .
                                                                                                               .
                                                                                                                                                                  I
                          (5) Point m
                                                                                                                                                        FX3U-4AD-PTW
                                         (8) Unit of output update time at each point,   Device specified in BFM #98 + total number
                                         and point-to-point interpolation method         of data tables -1*1
                                                                                                                                                                 -ADP
         Note) The device number marked by *1 should not exceed D7999 or R32767.
         For a detailed description of the data table items (1) to (8), refer to the following pages.
                                                                                                                                                            J
                                                                                                                                                        FX3U-4AD-PNK
                                                                                                                                                                 -ADP
                                                                                                                                          E-39
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                        6 Table Output Function
FX3U-4DA (4-channel Analog Output)                                                                      6.2 Preparation of data table
          (4) Condition after output at final point in pattern (number of data items: 1)
              The condition after output at the final point in a pattern can be set to continue to output the output signal at
              the final point or output the offset signal.
              The setting is shown in the following table.
          * When a value out of the setting range is set, the error code is stored in the table output error code BFM #90,
            the device number or the buffer memory that has developed the table output error is stored in BFM #91,
            and b8 of the error status BFM #29 is turned on.
E-40
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                    6 Table Output Function
FX3U-4DA (4-channel Analog Output)                                                                  6.2 Preparation of data table
                                                                                                                                      A
         (8) Output update time unit and point-to-point interpolation method (number of data items: 1)
                                                                                                                                          Common Items
             Set the unit of the output update time and the point-to-point interpolation method for each point.
             The output update time unit and the point-to-point interpolation method for the n-th point are applied
             between the n-th point and the (n+1)-th point.
             When the pattern is repeated, the output update time unit and the point-to-point interpolation method are
             applied between the final point and the first point.
             When the pattern is not repeated, the output update time unit and the point-to-point interpolation method
                                                                                                                                      B
                                                                                                                                    FX3UC-4AD
                                                                                                                                    FX3U-4AD
             for the final point are ignored.
             A 4-digit hexadecimal number, H            , is allocated as shown below.
                          H
                 Invalid*                         Output updating time unit                                                           C
                 Invalid*                         Point-to-point interpolation method
                                                                                                                                          FX3U-4AD-ADP
         • Setting of output update time unit
                                                                                                                                          FX3G-2AD-BD
                     1            100 ms
                     2            1s
                     3            1 min
           Other than above
                values
                                  Invalid*                                                                                             E
                                                                                                                                          FX3U-4DA
         • Interpolation method
         Data output between points are interpolated every 1 ms and automatically updated.
                                                                                                                                          FX3U-4DA-ADP
                     1
                                  interpolated in the shape of a straight line.)
                                  S-shaped interpolation (Data output between points are
                     2            interpolated in the shape of an S-shaped as shown
                                  below.)
           Other than above
                                  Invalid*
                                                                                                                                     G
                values
                                                                                                                                          FX3G-1DA-BD
         • S-shaped interpolation
                           Output data
                         D/8
                                                                     Point n+1                                                        H
                                                                                                                                    FX3U-4AD-PT
           D
                                                                                                                                             -ADP
               D/2       D/8
                                  Point n
                                                                                                                                              I
                                                                                                                                    FX3U-4AD-PTW
Time
                                                       T
                                                                                                                                        J
         * When a value out of the setting range is set, the error code is stored in the table output error code BFM #90,
                                                                                                                                    FX3U-4AD-PNK
           the device number or the buffer memory that has developed the table output error is stored in BFM #91,
           and b8 of the error status BFM #29 is turned on.
                                                                                                                                             -ADP
                                                                                                                      E-41
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                     6 Table Output Function
FX3U-4DA (4-channel Analog Output)                                                                                  6.2 Preparation of data table
              Data
                       Set value                                                         Description
            register
            D5000         K2       Number of patterns                                                             2 patterns
            D5001         K3                   Number of points in pattern 1                                      3 points
                                   Pattern 1
                                                                                                                  Holding      of    value
            D5002         K0                   Setting of condition after output at final point in pattern 1
                                                                                                                  output at final point
            D5003        K3000                           Data to be output at point 1 in pattern 1                3V
            D5004         K18                  Point 1   Output update time at point 1 in pattern 1               1800 ms
                                                         Output update time unit at point 1 in pattern 1          100 ms
            D5005       H0021
                                                         Point-to-point interpolation method                      S-shaped interpolation
            D5006        K8000                           Data to be output at point 2 in pattern 1                8V
                                               Point 2
            D5013         K1                   Setting of condition after output at final point in pattern 2      Output of offset value
            D5014        K2000                           Data to be output at point 1 in pattern 2                2V
                                               Point 1
E-42
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                     6 Table Output Function
FX3U-4DA (4-channel Analog Output)                                                                    6.2 Preparation of data table
                                                                                                                                        A
      5. Example of pattern output
                                                                                                                                            Common Items
         Data can be output in a predetermined pattern as shown below. (Example of pattern 1 in output mode 1
         shown on the previous page)
                                                                                                                                      FX3UC-4AD
                                                                                                                                      FX3U-4AD
                                                                                              are set to 0 or 2 or
          Output                                                                              higher.)
           value
                                     Point 2
              8V
                                                   Linear
                        S-shaped
                                                   interpolation                                                                        C
                     interpolation
                                                                                                                                            FX3U-4AD-ADP
              5V
                                                                  Point 3
                     Point 1
              3V
                                                                                                                                        D
                                                                                                                                            FX3G-2AD-BD
                                                                                                        Time
                          Output update         Output update               Output update
                          time at point 1
                            (1800 ms)
                                                time at point 2
                                                  (2600 ms)
                                                                            time at point 3
                                                                               (500 ms)
                                                                                                                                         E
                                                                                                                                            FX3U-4DA
      6. Caution when preparing the data table
         • Prepare the data table in continuous data registers in the PLC main unit or continuous expansion registers.
           (Prepare data without spaces between patterns or points.)
           If data has spaces, the data cannot be transferred normally to the buffer memory in FX3U-4DA.                                  F
                                            → For a detailed description of data table errors, refer to Section 6.5.
                                                                                                                                            FX3U-4DA-ADP
                                                                                                                                       G
FX3G-1DA-BD
                                                                                                                                        H
                                                                                                                                      FX3U-4AD-PT
                                                                                                                                               -ADP
                                                                                                                                                I
                                                                                                                                      FX3U-4AD-PTW
                                                                                                                                               -ADP
                                                                                                                                          J
                                                                                                                                      FX3U-4AD-PNK
                                                                                                                                               -ADP
                                                                                                                        E-43
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                               6 Table Output Function
FX3U-4DA (4-channel Analog Output)                                                 6.3 Procedures for transferring data table to buffer memory
       1. Specify the head device number of the data table to be transferred. (BFM #98, initial value:
          K1000)
          Specify the head device number of the data table in BFM #98.
          The setting range is K1000 to K7994 for the data registers (D1000 to D7999) (because at least six points are
          occupied) or K0 to K32762 for the expansion registers (R0 to R32767) (because at least six points are
          occupied).
            Example) When the data table is set starting from D1000, set K1000 in BFM #98.
          When a value out of the setting range is set, the error code K21 is stored in the table output error code BFM
          #90, the number of the buffer memory, K98, that has developed the table output error is stored in BFM #91,
          and b8 of the error status BFM #29 is turned on.
       2. Start transferring the data table. (BFM #99, initial value: H0000)
          Transfer the data table from the PLC to the FX3U-4DA using the data table transfer command (BFM #99).
                    H
              Invalid*                      Data table transfer command
              Invalid*                      Register type
• Register type
          * When a value out of the setting range is set, the error code is stored in the table output error code BFM #90,
            the number of the buffer memory, K99, that has developed the table output error is stored in BFM #91, and
            b8 of the error status BFM #29 is turned on.
          Example)       When K1000 is written in the head device number of data table (BFM #98) and H0001 is written
                         in the data table transfer command (BFM #99), the data table will be transferred from the data
                         register D1000.
E-44
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                     6 Table Output Function
FX3U-4DA (4-channel Analog Output)                                                       6.3 Procedures for transferring data table to buffer memory
                                                                                                                                                         A
      3. Buffer memory contents in FX3U-4DA after transfer
                                                                                                                                                             Common Items
         The transferred data table is stored in the following buffer memory areas.
             BFM
                                                                Description
            number
             #100
                      Pattern 1
                                   Number of points                                                                                                      B
             #101                  Condition after output at final point in pattern
                                                                                                                                                       FX3UC-4AD
                                                                                                                                                       FX3U-4AD
             #102                                Output data
             #103                                Output update time
                                     Point 1
                                                 Unit of output update time at each point, and point-to-
             #104
                                                 point interpolation method
               .                         .                                      .                                                                        C
               .                         .                                      .
                                                                                                                                                             FX3U-4AD-ADP
               .                         .                                      .
             #396                                Output data
             #397                                Output update time
                                     Point 99
                                                 Unit of output update time at each point, and point-to-
             #398
                                                 point interpolation method                                                                              D
                                                                                                                                                             FX3G-2AD-BD
             #399     Not used
               .        .                                               .
               .        .                                               .
               .        .                                               .
            #2800                  Number of points
            #2801                  Condition after output at final point in pattern
                                                                                                                                                          E
                                                                                                                                                             FX3U-4DA
            #2802                                Output data
            #2803                                Output update time
                                     Point 1
                                                 Unit of output update time at each point, and point-to-
            #2804
                      Pattern 10
                                                                                                                                                             FX3U-4DA-ADP
               .                         .                                      .
            #3096                                Output data
            #3097                                Output update time
                                     Point 99
                                                 Unit of output update time at each point, and point-to-
            #3098
                                                 point interpolation method                                                                             G
FX3G-1DA-BD
                                                                                                                                                         H
                                                                                                                                                       FX3U-4AD-PT
                                                                                                                                                                -ADP
                                                                                                                                                                 I
                                                                                                                                                       FX3U-4AD-PTW
                                                                                                                                                                -ADP
                                                                                                                                                           J
                                                                                                                                                       FX3U-4AD-PNK
                                                                                                                                                                -ADP
                                                                                                                                          E-45
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                      6 Table Output Function
FX3U-4DA (4-channel Analog Output)                                        6.3 Procedures for transferring data table to buffer memory
E-46
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                             6 Table Output Function
FX3U-4DA (4-channel Analog Output)                                               6.3 Procedures for transferring data table to buffer memory
                                                                                                                                                 A
      5. Cautions regarding data table transfer
                                                                                                                                                     Common Items
         • While the table output function is executed, it is impossible to start transferring the data table.
         • The number of patterns is not transferred to the buffer memory in FX3U-4DA.
         • The transferred data table is stored in the buffer memory in FX3U-4DA. The data table stored in FX3U-4DA
           will be erased when power is turned off. Therefore, it is necessary to transfer the data table after rebooting
           the power.
                                                                                                                                                 B
                                                                                                                                               FX3UC-4AD
                                                                                                                                               FX3U-4AD
         • At completion of transfer, BFM #99 will automatically change to H0000. Also when transfer is stopped due
           to an error, BFM #99 will automatically change to H0000. When BFM #99 changes to H0000, check the
           error flag.
                          → For a detailed description of errors related to table output, refer to Subsection 6.5.
         • If an error occurs during transfer of the data table, the data up to the error is transferred. Subsequent data                        C
           is not transferred.
                                                                                                                                                     FX3U-4AD-ADP
         • It is possible to write the data table directly in the buffer memory without using the data table transfer
           command (BFM #99).
           In this case, the correctness of the data table is not evaluated until the table is output by the table output
           start/stop function (BFM #80).
           If a data table with incorrect data is output, the data up to the point where incorrect data occurs is output.
           At the point where incorrect data occurs, an error is registered and only the data output just before the
                                                                                                                                                 D
                                                                                                                                                     FX3G-2AD-BD
           occurrence of the error is held.
         • Execute the data table transfer command (BFM #99) as a pulse execution type instruction.
         •   During transfer of the data table, the scan time increases by up to about 10 ms.
         • The standard data table transfer time is obtained by the following formula.
                                                                                                                                                  E
                                                Number of         *
                                                                                                                                                     FX3U-4DA
                                              data table items
         Transfer time = (Scan time) ×                            × (number of FX3U-4DA units connected to main unit)
                                                    64
             * Fractions omitted
             Example)                                                                                                                              F
                • Scan time: 50 ms (including increase in scan time caused by data table transfer)
                                                                                                                                                     FX3U-4DA-ADP
                • Number of data table items to be transferred: 2991 items (when the number of patterns is 10
                  and the number of points in each pattern is 99)
                • Number of units connected to FX3U-4DA: 8 units
                                                 2991
                                                                                                                                                G
                  Transfer time = (50 ms) ×              × (8 units)
                                                                                                                                                     FX3G-1DA-BD
                                                  64
                                   = 18800 ms
                                                                                                                                                 H
                                                                                                                                               FX3U-4AD-PT
                                                                                                                                                        -ADP
                                                                                                                                                         I
                                                                                                                                               FX3U-4AD-PTW
                                                                                                                                                        -ADP
                                                                                                                                                   J
                                                                                                                                               FX3U-4AD-PNK
                                                                                                                                                        -ADP
                                                                                                                                  E-47
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                               6 Table Output Function
FX3U-4DA (4-channel Analog Output)                                                           6.4 Procedures for executing table output function
         After setting the output patterns for the channels (BFM #81 to #84) and the number outputs for the
         channels (BFM #85 to #88), turn on the table output function start/stop command (BFM #80) to
         execute the table output function.
       1. Set the output patterns for the channels. (BFM #81 to #84, initial value: K1)
         Set the output patterns for the channels in BFM #81 to #84.
         The output pattern can be changed in the middle of outputting the table.
         Setting range for BFM #81 to #84: 1 to 10
         When a value out of the setting range is set, the error code K31 is stored in the table output error code BFM
         #90, the number of the buffer memory (K81 to K84) that has developed the table output error is stored in BFM
         #91, and b8 of the error status BFM #29 is turned on.
       2. Set the number of table outputs for the channels. (BFM #85 to #88, initial value: K0)
         Set the number of table outputs for the channels in BFM #85 to #88.
         The number of outputs can be changed even during outputting the table.
         Setting range for BFM #85 to #88: 0 to 32767
         When 0 is set, output of the table will be repeated until the table output is stopped by BFM #80.
         When a value out of the setting range is set, the error code K32 is stored in the table output error code BFM
         #90, the number of the buffer memory (K85 to K88) that has developed the table output error is stored in BFM
         #91, and b8 of the error status BFM #29 is turned on.
            H
          ch4                     ch1
          ch3                     ch2
         * When a value out of the setting range is set, the error code K33 is stored in the table output error code BFM
           #90, the number of the buffer memory (K80) that has developed the table output error is stored in BFM #91,
           and b8 of the error status BFM #29 is turned on.
E-48
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                            6 Table Output Function
FX3U-4DA (4-channel Analog Output)                                                        6.4 Procedures for executing table output function
                                                                                                                                                 A
      4. Cautions regarding table output
                                                                                                                                                     Common Items
         • When BFM #99 (data table transfer command) is not H0000, the table output function cannot be started.
         • When an error occurs during transfer of data table, start the table output after setting the correct data table.
         • While the table output completion flag BFM #89 is ON, output of a new table cannot be started.
         • The table output function is valid only while the PLC is in RUN mode.                                                                 B
         •   While even a single channel is outputting data table (BFM #80 is not H0000), it is prohibited to change
                                                                                                                                               FX3UC-4AD
                                                                                                                                               FX3U-4AD
             BFM #0, #5, #9 to #17, #19, #20, #32 to #35, #38, #41 to 48, #50 to #54 and #60 to #63.
         • The pattern can be changed during output as shown below. (The change is invalid while the table output
           completion flag BFM #89 is ON.)
             Output                                                                                                                              C
              value                                  Pattern 5
                                                                                                                                                     FX3U-4AD-ADP
                               Pattern 1
                                                                                                                                                     FX3G-2AD-BD
                                                                                                            Time
                 Table output start           Change from output pattern
                                              1 to output pattern 5
                                                                                                                                                  E
                                                                                                                                                     FX3U-4DA
      5. Check the table output completion flag. (BFM #89, initial value: H0000)
         The value in BFM #89 indicates whether the table output from each channel has been completed.
         After data is output at the final point in the last cycle of a pattern, the table output completion flag is turned on.
         When the table output (BFM#80) is set to be stopped, the table output completion flag is turned off.                                      F
                                                                                                                                                     FX3U-4DA-ADP
             H
          ch4                         ch1
          ch3                         ch2
                                                                                                                                                G
                                                                                                                                                     FX3G-1DA-BD
             Value for each
                                            Table output completion flag
                channel
                      0         Table output uncompleted
                      1         Table output completed
                                                                                                                                                 H
                                                                                                                                               FX3U-4AD-PT
                                                                                                                                                        -ADP
                                                                                                                                                         I
                                                                                                                                               FX3U-4AD-PTW
                                                                                                                                                        -ADP
                                                                                                                                                   J
                                                                                                                                               FX3U-4AD-PNK
                                                                                                                                                        -ADP
                                                                                                                                  E-49
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                          6 Table Output Function
FX3U-4DA (4-channel Analog Output)                                                                      6.5 Details of table output error
E-50
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                        6 Table Output Function
FX3U-4DA (4-channel Analog Output)                                                                    6.5 Details of table output error
                                                                                                                                            A
      2. Cautions regarding table output errors
                                                                                                                                                Common Items
         • Errors in data table
           When the data table in the PLC contains an error, the error can be detected during transfer of the data to
           the buffer memory in FX3U-4DA. In this case, the error code (BFM #90) is K1 1, and the device number is
           written as the error source (BFM #91).
           If an error is caused in the data table by directly rewriting the data in BFM after the data table is transferred,               B
           the error can be detected when the table is output using incorrect data. In this case, the error code (BFM
                                                                                                                                          FX3UC-4AD
                                                                                                                                          FX3U-4AD
           #90) is K1 2, and the BFM number is written as the error source (BFM #91).
         • Error during transfer of the data table
           While transferring of the data table, an error (error codes K31 to K33) does not occur even when the BFM
           #80 (table output function start/stop) is set to a value out of the setting range. An error occurs after the
           completion of the transfer of the data table.                                                                                    C
         • Error during output of the table
                                                                                                                                                FX3U-4AD-ADP
           Even if the output value is scaled over during output of the table, the output of the table will not be stopped.
           However, while the output value is scaled over, b10 (scale over) of the error status BFM #29 stays on.
           When an error (error codes K122 to K172, K31 to K33) occurs during output of the table, the output of the
           table is cancelled and the analog output value just before the occurrence of the error is retained.
         • Table output errors (BFM #90) and table output error source numbers (BFM #91) are not retained. They                             D
           will be cleared when the next data table transfer command is given or the table output start function is
                                                                                                                                                FX3G-2AD-BD
           executed.
                                                                                                                                                FX3U-4DA
                                                                                                                                              F
                                                                                                                                                FX3U-4DA-ADP
                                                                                                                                           G
FX3G-1DA-BD
                                                                                                                                            H
                                                                                                                                          FX3U-4AD-PT
                                                                                                                                                   -ADP
                                                                                                                                                    I
                                                                                                                                          FX3U-4AD-PTW
                                                                                                                                                   -ADP
                                                                                                                                              J
                                                                                                                                          FX3U-4AD-PNK
                                                                                                                                                   -ADP
                                                                                                                            E-51
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                 6 Table Output Function
FX3U-4DA (4-channel Analog Output)                                                                    6.6 Examples uses of table output function
         Output
         frequency
         (Hz)
                60
30
                    0
                                    5           10V
                                          Analog signal
         To control the frequency as shown below, where control the analog signal is proportional to the frequency use
         the table output function.
         Output
         frequency
         (Hz)
60
30
                0
                                                                                               Time
         Output
         voltage (V)
                                          Point 2                Point 3
           10
                                               No interpolation
                    S-shaped                                                S-shaped
                    interpolation                                           interpolation
            5
                                                                                    Point 4
            0            Point 1
                                                                                              Time
                        Output update          Output update           Output update
                        time at point 1        time at point 2         time at point 3
E-52
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                          7 Changing Output Characteristic
FX3U-4DA (4-channel Analog Output)                                                     7.1 Procedure for Changing Output Characteristics
                                                                                                                                                 Common Items
7.     Changing Output Characteristic
         For FX3U-4DA, the standard output characteristics are provided for each output mode (BFM #0)at the time of                          B
         factory shipment.
                                                                                                                                           FX3UC-4AD
                                                                                                                                           FX3U-4AD
         Changing the offset data (BFM #10 to #13) and gain data (BFM #14 to #17) can change the output
         characteristics of each channel. This chapter describes how to change the output characteristics.
                                                                                                                                                 FX3U-4AD-ADP
   1     Cancel the setting change prohibition mode.
         If setting change is prohibited, write K3030 in BFM #19. The setting change prohibition mode will
         be canceled.
                                                                                                                                             D
   2
                                                                                                                                                 FX3G-2AD-BD
         Determine the output mode (BFM #0).
         Determine the output mode (BFM #0) optimum for the selected channels and the voltage/current
         specifications.
Set value (HEX) Output mode Analog output range Digital input range E
                                                                                                                                                 FX3U-4DA
                  0           Voltage output mode                       -10V to +10V                    -32000 to +32000
                              Voltage output analog value mV
                  1                                                       The characteristic cannot be changed.
                              specification mode
                  2           Current output mode                       0mA to 20mA                          0 to 32000
                  3           Current output mode
                              Current output analog value µA
                                                                        4mA to 20mA                          0 to 32000
                                                                                                                                               F
                  4                                                       The characteristic cannot be changed.
                                                                                                                                                 FX3U-4DA-ADP
                              specification mode
                5 to E        Setting not allowed                             -                                     -
                  F           Channel not used                                -                                     -
         Example: Enter "HFF00" in BFM to set output mode 0 for channels 1 and 2 and prevent use chan-                                      G
         nels 3 and 4
                                                                                                                                                 FX3G-1DA-BD
         Cautions regarding data setting
         • If a value "1" or "4" is set for a channel, the output characteristics of the channel cannot be changed.
         • Set the optimum output mode for the analog signal to be output.
                                                                                                                                             H
                                                                                                                                           FX3U-4AD-PT
                                                                                                                                                    -ADP
                                                                                                                                                     I
                                                                                                                                           FX3U-4AD-PTW
                                                                                                                                                    -ADP
                                                                                                                                               J
                                                                                                                                           FX3U-4AD-PNK
                                                                                                                                                    -ADP
                                                                                                                              E-53
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                 7 Changing Output Characteristic
FX3U-4DA (4-channel Analog Output)                                                         7.1 Procedure for Changing Output Characteristics
         Output mode: 0
         Output characteristics provided at the time                        Output characteristics newly provided
         of factory shipment
                      +10.2V
                        +10V                                                                 5V
                                                   Digital                                   1V                        Digital
             -32000         0                      value                                                               value
                                         +32000                                                   0            32000
                                -10V
                                -10.2V
E-54
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                         7 Changing Output Characteristic
FX3U-4DA (4-channel Analog Output)                                                 7.1 Procedure for Changing Output Characteristics
                                                                                                                                         A
   6
                                                                                                                                             Common Items
         Create a sequence program.
         To change the output characteristics, write the offset data (BFM #10 to #13) and the gain data
         (BFM #14 to #17) in the sequence program, and then turn on the corresponding bit of BFM #9 for
         the corresponding channel.
                                                                                                                                         B
         Example: Program for changing the output characteristics of channels 1 and 2 (For FX3U, FX3UC
                                                                                                                                       FX3UC-4AD
                                                                                                                                       FX3U-4AD
         Series PLCs):
           X000
                                    FNC 12                       Cancellation of setting change
                                             K3030     U0\G19    prohibition mode
                                    MOV P
                                                                                                                                             FX3U-4AD-ADP
                                    MOV P                        channels 1 to 4
SET M0
            M0
                                                      K50
                                              T0
                                                                                                                                         D
             T0
                                                                                                                                             FX3G-2AD-BD
                           FNC 16    K1000   U0\G10         K2   Setting of offset data (channels 1 and 2)
                           FMOV P
                                                                                                                                             FX3U-4DA
                                    FNC 12     K0      U0\G19    Setting change prohibition
                                    MOV P
                                                                                                                                           F
   7     Transfer the sequence program to change the output characteristics.
                                                                                                                                             FX3U-4DA-ADP
         Transfer the sequence program, and start the PLC.
         After the PLC is started and the output characteristic write command (X000) is turned on, the offset
         data and gain data will be written.
         Since the offset data and gain data are stored in the EEPROM incorporated in FX3U-4DA, it is pos-
                                                                                                                                        G
                                                                                                                                             FX3G-1DA-BD
         sible to delete the pre-written sequence program.
                                                                                                                                                 I
                                                                                                                                       FX3U-4AD-PTW
                                                                                                                                                -ADP
                                                                                                                                           J
                                                                                                                                       FX3U-4AD-PNK
                                                                                                                                                -ADP
                                                                                                                          E-55
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                       8 Examples of Practical Programs
FX3U-4DA (4-channel Analog Output)                                           8.1 Example of Program for Analog Output Operation (Regular Operation)
       1. Conditions
         The sequence program described in this section is under the following conditions.
         1) System configuration
            FX3U-4DA (unit No.0) should be connected to the FX3U Series PLC.
         2) Output mode
            Channels 1 and 2 should be set to mode 0 (voltage output, -10 V to +10 V).
            Channel 3 should be set to mode 3 (current output, 4 mA to 20 mA).
            Channel 4 should be set to mode 2 (current output, 0 mA to 20 mA).
           - For FX3U, FX3UC Series PLCs
              Initial pulse
                                                                                 Transfer H2300 to BFM #0 (output modes of
               M8002                                                             channels 1 to 4).
                                              FNC 12       H2300     U0\G0       ch1 and ch2: Voltage output (-10 to +10 V),
                                              MOV P                                           output mode 0
              RUN monitor                                                        ch3: Current output (4 mA to 20 mA), output
               M8000                                                                  mode 3
                                                                   K50 *         ch4: Current output (0 mA to 20 mA), output
                                                           T0                         mode 2
                       Data to be output to channel 1 is written in D0.          Store the data to be output to channels 1 to 4
                       Data to be output to channel 2 is written in D1.          in D0 to D3 in the following ranges.
                       Data to be output to channel 3 is written in D2.          D0 and D1: -32000 to +32000
                       Data to be output to channel 4 is written in D3.          D2 and D3: 0 to 32000
              Initial pulse
                                                                                    Transfer H2300 to BFM #0 (output modes of
               M8002                                                                channels 1 to 4).
                              FNC 79       K0         K0      H2300         K1      ch1 and ch2: Voltage output (-10 to +10 V),
                              TO P                                                               output mode 0
              RUN monitor                                                           ch3: Current output (4 mA to 20 mA), output
               M8000                                                                     mode 3
                                                                   K50 *            ch4: Current output (0 mA to 20 mA), output
                                                           T0                            mode 2
                       Data to be output to channel 1 is written in D0.             Store the data to be output to channels 1 to 4
                       Data to be output to channel 2 is written in D1.             in D0 to D3 in the following ranges.
                       Data to be output to channel 3 is written in D2.             D0 and D1: -32000 to +32000
                       Data to be output to channel 4 is written in D3.             D2 and D3: 0 to 32000
E-56
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                             8 Examples of Practical Programs
FX3U-4DA (4-channel Analog Output)                                                        8.2 Example of Program using Useful Functions
                                                                                                                                            A
8.2      Example of Program using Useful Functions
                                                                                                                                                Common Items
         This section describes a practical program that uses the disconnection detection function (BFM #28), upper/
         lower limit function (BFM #38 to #48), corrective function by load resistance (BFM #50 to #54) and status
         automatic transfer function (BFM #60 to #63) of FX3U-4DA.
      1. Conditions
                                                                                                                                            B
                                                                                                                                          FX3UC-4AD
                                                                                                                                          FX3U-4AD
         The sequence program described in this section is created under the following conditions.
         1) System configuration
            FX3U-4DA (unit No.0) should be connected to the FX3U Series PLC.
         2) Output mode
            Channels 1 and 2 should be set to mode 0 (voltage output, -10 V to +10 V).                                                      C
            Channels 3 and 4 should be set to mode 2 (current output, 0 mA to 20 mA).
                                                                                                                                                FX3U-4AD-ADP
         3) Convenient functions
            The disconnection detection function, upper/lower limit function, corrective function by load resistance
            and status automatic transfer function are used.
         4) Device assignment
                           Device                                                 Description
                                                                                                                                            D
                                                                                                                                                FX3G-2AD-BD
                                    X000       Clearance of upper/lower limit function status data
                                    X001       Clearance of error status data
                                    X002       Clearance of disconnection detection status data
                   Input            D10        Data to be output from channel 1
                                    D11        Data to be output from channel 2                                                              E
                                                                                                                                                FX3U-4DA
                                    D12        Data to be output from channel 3
                                    D13        Data to be output from channel 4
                                    Y000       Output of channel-1 lower limit error data
                                    Y001       Output of channel-1 upper limit error data
                                    Y002       Output of channel-2 lower limit error data                                                     F
                                    Y003       Output of channel-2 upper limit error data
                                                                                                                                                FX3U-4DA-ADP
                                    Y004       Output of channel-3 lower limit error data
                                    Y005       Output of channel-3 upper limit error data
                                    Y006       Output of channel-4 lower limit error data
                  Output            Y007       Output of channel-4 upper limit error data
                                    Y010       Output of disconnection detection signal
                                                                                                                                           G
                                                                                                                                                FX3G-1DA-BD
                                    Y011       Output of error detection signal
                                    D200       Data register at destination of automatic transfer of error status
                                               Data register at destination of automatic transfer of upper/lower limit
                                    D201
                                               function error status
                                    D202
                                               Data register at destination of automatic transfer of disconnection detection                H
                                               error status
                                                                                                                                          FX3U-4AD-PT
                                                                                                                                                   -ADP
                                                                                                                                                    I
                                                                                                                                          FX3U-4AD-PTW
                                                                                                                                                   -ADP
                                                                                                                                              J
                                                                                                                                          FX3U-4AD-PNK
                                                                                                                                                   -ADP
                                                                                                                             E-57
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                  8 Examples of Practical Programs
FX3U-4DA (4-channel Analog Output)                                                              8.2 Example of Program using Useful Functions
       Initial pulse
        M8002
                                       FNC 12     H2200      U0\G0   Output modes of channels 1 to 4 will be specified *1
       RUN monitor                     MOV P
        M8000
                                                   T0      K50 *2
          T0
                                       FNC 12     H1122     U0\G38   Upper/lower limit function setting
                                       MOV P
                              FNC 16     K-3200   U0\G41       K2    Setting of lower limit values for channels 1 and 2
                              FMOV P
                              FNC 16     K6400    U0\G43       K2    Setting of lower limit values for channels 3 and 4
                              FMOV P
                              FNC 16    K28800 U0\G45          K2    Setting of upper limit values for channels 1 and 2
                              FMOV P
                              FNC 16    K25600 U0\G47          K2    Setting of upper limit values for channels 3 and 4
                              FMOV P
                              FNC 16     K5000    U0\G51       K2    Setting of load resistance values for channels 1 and 2 *1
                              FMOV P
        D202.2
                                                                     Disconnection detected in channels 3 and 4
                                                  Y010               Output to Y010
        D202.3
       D200.0
                                                  Y011               Error detected Output to Y011
             *1.       The output mode setting, setting of corrective function by load characteristics and status automatic
                       transfer function setting are retained in the EEPROM of FX 3U-4DA. For this reason, even if the
                       sequence program is deleted, the previously set functions will still be valid.
             *2.       After setting the output mode, set the data writing time (waiting time) to 5 seconds or more for each
                       setting. After the output mode is specified, and the same output mode is used, it is not necessary to
                       set the output mode and the waiting time (T0 K50).
E-58
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                 8 Examples of Practical Programs
FX3U-4DA (4-channel Analog Output)                                                            8.2 Example of Program using Useful Functions
                                                                                                                                                A
           • For FX3G, FX3U, FX3UC Series PLCs
                                                                                                                                                    Common Items
   Initial pulse
    M8002
                    FNC 79       K0      K0        H2200      K1      Output modes of channels 1 to 4 will be specified *1
   RUN monitor      TO P
    M8000
                                                    K50 *2
                                                                                                                                                B
                                              T0
                                                                                                                                              FX3UC-4AD
                                                                                                                                              FX3U-4AD
      T0
                    FNC 79       K0      K38       H1122      K1      Upper/lower limit function setting
                    TO P
                    FNC 79
                    TO P
                                 K0      K41       K-3200     K2      Setting of lower limit values for channels 1 and 2
                                                                                                                                                C
                                                                                                                                                    FX3U-4AD-ADP
                    FNC 79       K0      K43       K6400      K2      Setting of lower limit values for channels 3 and 4
                    TO P
                    FNC 79       K0      K45       K28800     K2      Setting of upper limit values for channels 1 and 2
                    TO P
                    FNC 79       K0      K47       K25600     K2      Setting of upper limit values for channels 3 and 4                        D
                    TO P
                                                                                                                                                    FX3G-2AD-BD
                    FNC 79       K0      K50       H0011      K1      Corrective function setting by load resistance *1
                    TO P
                    FNC 79       K0      K51       K5000      K2      Setting of load resistance values for channels 1 and 2 *1
                    TO P
                                                                      Status automatic transfer function setting *1
                                                                                                                                                 E
                    FNC 79
                                                                                                                                                    FX3U-4DA
                                 K0      K60       H0007      K1      (The initial setting of destination data registers is used,
                    TO P                                              and the sequence program for this function is omitted.)
     X000
                    FNC 79       K0      K40       H0003      K1      Clearance of upper/lower limit function status data
                    TO P
     X001
                                                                                                                                                  F
                    FNC 79       K0      K29        K0        K1      Clearance of error status data
                    TO P
                                                                                                                                                    FX3U-4DA-ADP
     X002
                    FNC 79       K0      K28        K0        K1      Clearance of disconnection detection status data
                    TO P
    RUN monitor
    M8000
                    FNC 79       K0      K1         D10       K4      Transfer of data that will be output from channels 1 to 4
                    TO
                                                                                                                                                    FX3G-1DA-BD
                                      FNC 12       D200      K4M0
                                       MOV
     M22
                                       MOV
                                                                                                                                                H
                                                                                                                                              FX3U-4AD-PT
      M0
                                           Y011                       Error detected Output to Y011
                                                                                                                                                        I
                                                                                                                                              FX3U-4AD-PTW
            *1.    The output mode setting, setting of corrective function by load characteristics and status automatic
                   transfer function setting are retained in the EEPROM of FX 3U-4DA. For this reason, even if the
                   sequence program is deleted, the previously set functions will still be valid.
                                                                                                                                                       -ADP
            *2.    After setting the output mode, set the data writing time (waiting time) to 5 seconds or more for each
                   setting. After the output mode is specified, and the same output mode is used, it is not necessary to                          J
                   set the output mode and the waiting time (T0 K50).
                                                                                                                                              FX3U-4AD-PNK
                                                                                                                                                       -ADP
                                                                                                                                 E-59
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                    8 Examples of Practical Programs
FX3U-4DA (4-channel Analog Output)                                   8.3 Example of Program for Table Output Operation (Pattern Output Operation)
       1. Conditions
          The sequence program described in this section is under the following conditions.
          1) System configuration
             FX3U-4DA (unit No.0) should be connected to the FX3U Series PLC.
          2) Output mode
             Channel 1 should be set to mode 0 (voltage output, -10 V to +10 V).
             Channel 3 should be set to mode 2 (current output, 0 mA to 20 mA).
             Channels 2 and 4 are out of use.
          3) Convenient function
             The table output function is used.
          4) Device assignment
                               Device                                      Description
                                        X000      Start of table output function for channels 1 and 3
                                        X001      Stop of table output function
                                        X002      Restart of table output function for channel 3
                                        D10       Data to be output from channel 1
                       Input
                                        D11       Data to be output from channel 2
                                        D12       Data to be output from channel 3
                                        D13       Data to be output from channel 4
                                   D5000 or more Data table *
                                        Y000      Completion of output of table from channel 1
                                        Y001      Table output error
                                        M0        Data table transfer complete
                      Output
                                        M1        During output of table from channel 3
                                        D100      Data table transfer command
                                        D101      Table output completion flag
           Initial pulse
            M8002
                                        FNC 12    HF2F0    U0\G0       Specification of output modes of channels 1 to 4 *1
                                        MOV P
           RUN monitor
            M8000
                                                   T0     K50   *2
Continued
            *1.    The output mode setting is retained in the EEPROM of the FX3U-4DA. For this reason, even if the
                   sequence program is deleted, the previously set functions will still be valid.
            *2.    After setting the output mode, set the data writing time (waiting time) to 5 seconds or more for each
                   setting. After the output mode is specified, and the same output mode is used, it is not necessary to
                   set the output mode and the waiting time (T0 K50).
E-60
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                     8 Examples of Practical Programs
FX3U-4DA (4-channel Analog Output)                                    8.3 Example of Program for Table Output Operation (Pattern Output Operation)
                                                                                                                                                           Common Items
             T0
                                       FNC 12         K1     U0\G81       Channel-1 output pattern
                                       MOV P
                                                                                                                                                     FX3UC-4AD
                                                                                                                                                     FX3U-4AD
                                       FNC 12                             Number of repetitions of output of table
                                                      K5     U0\G85       from channel 1
                                       MOV P
                                                                                                                                                           FX3U-4AD-ADP
                                                  K5000      U0\G98       Number of head device in data table
                                       MOV P
                           FNC 79
                            FROM
                                       K0       K99    D100    K1         Readout of data table transfer command                                       D
                                                                                                                                                           FX3G-2AD-BD
                     D100.0
                                                                          Turning-on of M0 At the completion of transfer
                                                       SET     M0         of data table
            X000
                                       FNC 12     H0100      U0\G80       Start table output function (channel 3)
                                       MOV P
                                                                          Turning-on of M1 when table is output from                                    E
                                                       SET     M1         channel 3
                                                                                                                                                           FX3U-4DA
            X000      M1
                                       FNC 12     H0101      U0\G80       Start table output function (channel 1)
                                       MOV P
            X001      M1
                                       FNC 12     H0000      U0\G80       Stop table output function
                                       MOV P                                                                                                             F
                                                                                                                                                           FX3U-4DA-ADP
                                                                          Turning-off of M1 when output of table from
                                                       RST     M1         channel 3 is stopped
            X002      M1
                                       FNC 12     H0100      U0\G80       Restart of table output function (channel 3)
                                       MOV P
                                                                                                                                                           FX3G-1DA-BD
            M1
                           FNC 79      K0       K89    D101    K2         Readout table output completion flag and table
                           FROM                                           output error
           D101.0
                                                  Y000                    Completion of table output from channel 1
                                                                          Output to Y000
              FNC 228
                                                                                                                                                       H
                           K0   D102              Y001                    Output to Y001 when table output error occurs
                                                                                                                                                     FX3U-4AD-PT
               LD< >
                                                                                                                                                              -ADP
* Execute the data table transfer command as a pulse execution type instruction.
                                                                                                                                                               I
                                                                                                                                                     FX3U-4AD-PTW
                                                                                                                                                              -ADP
                                                                                                                                                         J
                                                                                                                                                     FX3U-4AD-PNK
                                                                                                                                                              -ADP
                                                                                                                                        E-61
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                         8 Examples of Practical Programs
FX3U-4DA (4-channel Analog Output)                                        8.3 Example of Program for Table Output Operation (Pattern Output Operation)
       Initial pulse
        M8002
                              FNC 79       K0       K0      HF2F0        K1         Specification of output modes of channels 1 to 4 *1
                              TO P
       RUN monitor
        M8000
                                                  T0     K50 *2
          T0
                              FNC 79       K0      K81        K1         K1         Channel-1 output pattern
                              TO P
               *1.     The output mode setting is retained in the EEPROM of the FX3U-4DA. For this reason, even if the
                       sequence program is deleted, the previously set functions will still be valid.
               *2.     After setting the output mode, set the data writing time (waiting time) to 5 seconds or more for each
                       setting. After the output mode is specified, and the same output mode is used, it is not necessary to
                       set the output mode and the waiting time (T0 K50).
               *3.     Execute the data table transfer command as a pulse execution type instruction.
E-62
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                    8 Examples of Practical Programs
FX3U-4DA (4-channel Analog Output)                                                            8.4 Program to Initialize FX3U-4DA (Factory Default)
                                                                                                                                                           Common Items
        M1
                         FNC 78        K0       K89         D101         K2       Readout table output completion flag and table
                         FROM                                                     output error
                                             FNC 12
                                              MOV
                                                            D101    K4M30                                                                              B
        M30
                                                                                                                                                     FX3UC-4AD
                                                                                                                                                     FX3U-4AD
                                              Y000                                Completion of table output from channel 1
                                                                                  Output to Y000
          FNC 228     K0    D102              Y001                                Output to Y001 when table output error occurs
           LD< >
                                                                                                                                                       C
                                                                                                                                                           FX3U-4AD-ADP
8.4      Program to Initialize FX3U-4DA (Factory Default)
         To initialize FX3U-4DA, execute the following program.
         This will return the output mode (BFM #0), the offset data (BFM #10 to #13) and the gain data (BFM #14 to
         #17) will be to the factory default status state.                                                                                             D
                                                                                                                                                           FX3G-2AD-BD
      1. Conditions
         The sequence program described in this section is under the following conditions.
         1) System configuration
            FX3U-4DA (unit No.0) should be connected to the FX3U Series PLC.
         2) Device assignment                                                                                                                           E
                   Device                 Description
                                                                                                                                                           FX3U-4DA
                    X000        4AD initialization command
                                                                                                                                                           FX3U-4DA-ADP
          4DA initialization command
           X000
                                       FNC 12         K1        U0\G20        The 4DA will be initialized.
                                       MOV P                                  (BFM #0 to #3098 will be cleared.)
                                                                                                                                                           FX3G-1DA-BD
          4DA initialization command
           X000
                        FNC 79       K0       K20          K1       K1          The 4DA will be initialized.
                        TO P                                                    (BFM #0 to #3098 will be cleared.)
                                                                                                                                                       H
      3. Cautions regarding initializing
                                                                                                                                                     FX3U-4AD-PT
         • During initialization, output is stopped, and H0000 is automatically written in the output status (BFM #6).
           At the completion of initialization, the output status (BFM #6) will automatically change to H1111, and the
           output will be restarted.
                                                                                                                                                              -ADP
         • It takes approximately 5 seconds to complete initialization. Do not set (write) data in the buffer memory
           during the period.                                                                                                                                  I
         • Priority is given to the setting of the change prohibition mode (BFM #19).
                                                                                                                                                     FX3U-4AD-PTW
         • Once initialization is completed, the value in BFM #20 will automatically change to "K0".
                                                                                                                                                              -ADP
                                                                                                                                                         J
                                                                                                                                                     FX3U-4AD-PNK
                                                                                                                                                              -ADP
                                                                                                                                        E-63
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                              9 Troubleshooting
FX3U-4DA (4-channel Analog Output)                                                                  9.1 PLC Version Number Check
9.      Troubleshooting
         This chapter describes the troubleshooting methods and error codes.
         If the D/A conversion data is not output, or if the proper digital value is not output, check the following items:
         • Wiring
         • Program
         • Error status
       1. Power
         FX3U-4DA needs driving power. Verify that the power supply line is properly connected. Also check that the
         24 V indicator lamp of FX3U-4DA is on.
E-64
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                           9 Troubleshooting
FX3U-4DA (4-channel Analog Output)                                                                      9.4 Error Status Check
                                                                                                                                   A
9.4      Error Status Check
                                                                                                                                       Common Items
         When an error occurs in FX3U-4DA, the bit appropriate to the error is turned on in the error status (BFM #29).
         Take measures, referring to the following table.
                                                                                                                                 FX3UC-4AD
                                                                                                                                 FX3U-4AD
          b1           O/G error
          b2           Power supply error
          b3           Hardware error
          b4                                                 -                                                                     C
          b5           Error in setting of function for setting output upon PLC stop
                                                                                                                                       FX3U-4AD-ADP
          b6           Upper/lower limit function setting error
                       Error in corrective function setting by load resistance
          b7
                       (Valid only in voltage output mode)
          b8           Table output function setting error
          b9           Status automatic transfer setting error
                                                                                                                                   D
                                                                                                                                       FX3G-2AD-BD
          b10          Over-scale
          b11          Disconnection detection (Valid only in current output mode)
          b12          Setting data change prohibited
          b13 to b15                                         -
                                                                                                                                    E
      1. Error detection (b0)
                                                                                                                                       FX3U-4DA
         1) Description of error
            If any of b1 is turned on, this bit (b11) will turn on.
                                                                                                                                       FX3U-4DA-ADP
         2) Remedy
            Check the output mode (BFM #0) and the offset and gain data (BFM #10 to #17).
                                                                                                                                       FX3G-1DA-BD
            24 V power is not correctly supplied.
         2) Remedy
            Check the wiring condition or the supply voltage.
      5. Error when setting the function for output upon PLC stop (b5)
         1) Description of error                                                                                                           I
                                                                                                                                 FX3U-4AD-PTW
            The bit will turn on when the functions setting value for setting output upon PLC stop is not correctly set.
         2) Remedy
            Check the output mode (BFM #0) and the setting value of output data upon PLC stop (BFM #32 to #35).
                                                                                                                                          -ADP
                                                                                                                                     J
                                                                                                                                 FX3U-4AD-PNK
                                                                                                                                          -ADP
                                                                                                                    E-65
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                 9 Troubleshooting
FX3U-4DA (4-channel Analog Output)                                                        9.5 FX3U-4DA Initialization and Test Program
E-66
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4DA-ADP (4-channel analog Output)
                                                                                                                                       Common Items
                                                                                                                                   B
                                                                                                                                 FX3UC-4AD
                                                                                                                                 FX3U-4AD
         FX3G/FX3U/FX3UC Series Programmable
         Controllers                                                                                                               C
                                                                                                                                       FX3U-4AD-ADP
         User's Manual [Analog Control Edition]
         FX3U-4DA-ADP (4-channel analog Output)
                                                                                                                                   D
                                                                                                                                       FX3G-2AD-BD
                                                                                                                                    E
                                                                                                                                       FX3U-4DA
                                                                                                                                     F
                                                                                                                                       FX3U-4DA-ADP
                                                                                                                                  G
FX3G-1DA-BD
                                                                                                                                   H
                                                                                                                                 FX3U-4AD-PT
         Foreword
                                                                                                                                          -ADP
         This manual describes the specifications, wiring, and operation method for the FX3U-4DA-ADP special
         adapter (4-channel analog output) and should be read and understood before attempting to install or use the
         unit.                                                                                                                             I
         Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
                                                                                                                                 FX3U-4AD-PTW
           This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
                                                                                                                                          -ADP
           licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
           rights which may occur as a result of using the contents noted in this manual.
                                                                                                                                     J
                                                                                                                                 FX3U-4AD-PNK
                                                                                                                          F-1
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4DA-ADP (4-channel analog Output)
F-2
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                     1 Outline
FX3U-4DA-ADP (4-channel analog Output)                                                                         1.1 Outline of Functions
                                                                                                                                                 Common Items
1.       Outline
            This chapter outlines the FX3U-4DA-ADP (referred to as 4DA-ADP).                                                                 B
                                                                                                                                           FX3UC-4AD
                                                                                                                                           FX3U-4AD
1.1         Outline of Functions
            The FX3U-4DA-ADP is an analog special adapter. Which is connectable with the FX3U, FX3UC and FX3G
            Series PLC to output the voltage/current data for up to 4 channels.
                                                                                                                                             C
            1) Up to 4 units of 4DA-ADP can be connected to the FX3U/FX3UC Series PLC.
                                                                                                                                                 FX3U-4AD-ADP
               Up to 2*1 units of 4DA-ADP can be connected to the FX3G Series PLC.
               (Including other analog special adapters).
            2) Either "voltage output" or "current output" can be specified for each channel.
            3) The D/A conversion results will be automatically output as the values to the special data register of the
               FX3U/FX3UC/FX3G Series PLC.                                                                                                   D
                                                                                                                                                 FX3G-2AD-BD
                                                     System                                                  Point and section to be
                                                                                                                   referred to
                                                                                                                                                 FX3U-4DA
                                                                                                            To check the connectable
                                                                                                       …… PLC model number, refer
+ + to Section 1.3.
                                                                                                                                                 FX3U-4DA-ADP
                                                       Expansion
              4th       3rd        2nd       1st
            adapter   adapter    adapter   adapter      board*2
                                                                                                             For a detailed
                                                                                                       …… description of wiring,
                         Analog data                                                                         refer to Chapter 3.
Inverter, etc. G
                                                                                                                                                 FX3G-1DA-BD
                                                                             For FX3U, FX3UC
                                                                             Series PLC                     For a detailed description
           Contents                                                                                    …… of special devices, refer to
                                                                                                                                             H
                                                                               Special devices              Chapter 4.
        Output mode                        Transfer direction      1st adapter M/D8260 to M/D8269
                                                                                                            For a detailed description
                                                                                                                                           FX3U-4AD-PT
     Refer to the system configuration shown in the User's Manual - Hardware Edition to check the number of connectable units
     and to configure the entire system.                                                                                                             I
                                                                                                                                           FX3U-4AD-PTW
     *1. Only 1 analog special adapter can be connected to the 14-point and 24-point type main unit.
     *2. The expansion board is not required when connecting with the FX3UC (D, DSS) PLC.
         For the FX3G Series PLC a connector conversion adapter is used.
                                                                                                                                                    -ADP
                                                                                                                                               J
                                                                                                                                           FX3U-4AD-PNK
                                                                                                                                                    -ADP
                                                                                                                                   F-3
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                       1 Outline
FX3U-4DA-ADP (4-channel analog Output)                                      1.2 Setup Procedure Before Starting Operation
FX3U-4DA-ADP
Refer to Chapter 1.
                            Wiring                                    Wiring:
                                                                      • Power supply line
                                                                      • Analog output line
                                       Refer to Chapter 4.
                                                                      Programming:
                         Programming
                                                                      • Details of special devices
                                                                      • Examples of basic programs
                                        Refer to Chapter 5.
F-4
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                               1 Outline
FX3U-4DA-ADP (4-channel analog Output)                                                              1.3 Connectable PLCs and Version Numbers
                                                                                                                                                       A
1.3      Connectable PLCs and Version Numbers
                                                                                                                                                           Common Items
         The 4DA-ADP is compatible with the following PLCs.
                                                                                                                                                     FX3UC-4AD
                                                                                                                                                     FX3U-4AD
          FX3UC Series PLC                            Ver.1.20 or later                                     After April 2004
          FX3G Series PLC                             Ver.1.00 or later                            After June 2008 (initial production)
1. Version check C
                                                                                                                                                           FX3U-4AD-ADP
         Special data register D8001 contains information for determining the PLC version number.
                            D8001                2     4        1       0        0
                        PLC type and
                       version number                                           Version data (Example: Ver. 1.00)
                                                                                                                                                       D
                                                        PLC type Example: 24 = FX3U and FX3UC series
                                                                        (                                            )
                                                                                                                                                           FX3G-2AD-BD
                                                                          26 = FX3G series
                                                                                                                                                           FX3U-4DA
                                                     Example:
                                                     FX3U-48MR/ES(production number : 570001)
                                                       MODEL            FX3U-48MR/ES
                                                                 100-240VAC 50/60Hz 40W
                                                           OUT:30VDC/240VAC 2A(COSφ=1)
                                                                                                                                                         F
                                                                                                                                                           FX3U-4DA-ADP
                                                       SERIAL                        570001
                                                                    5       7        0    0    0     1
                                                                                                                                                      G
                                                                                                                                                           FX3G-1DA-BD
                                                                                          Control number
                                                                             Month (Example: 7 = July), 1 to 9 = January to September,
                                                                             X = October, Y = November, Z = December
                                                                        Year (Example: 5 = 2005), last digit of dominical year
                                                                                                                                                       H
                                                                                                                                                     FX3U-4AD-PT
         If a programming tool with the wrong version number is used, programming will not be possible.
                                                                                                                                                         J
          *1.   For Ver. 8.13P to 8.24A of GX Developer, select FX3UC for the PLC type.
                                                                                                                                                     FX3U-4AD-PNK
                                                                                                                                                              -ADP
                                                                                                                                           F-5
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                            2 Specifications
FX3U-4DA-ADP (4-channel analog Output)                                                                      2.1 Generic Specifications
2.     Specifications
         This chapter describes the general, power supply, and performance specifications for 4DA-ADP.
                Item                                                       Specifications
          Ambient            0 to 55°C (32 to 131°F) when operating
          temperature        -25 to 75°C (-13 to 167°F) when stored
          Relative
                             5 to 95%RH (no condensation) when operating
          humidity
                                                    Frequency            Acceleration      Half amplitude
                                                       (Hz)                 (m/s2)              (mm)
                                                                                                            10 times of testing in
          Vibration                                      10 - 57              -                0.035        each direction (X-, Y-,
                             DIN Rail Mounting
          resistance                                 57 - 150                4.9                    -       and Z-axis directions)
                                                                                                            (Total: 80 min, each)
                                                     10 to 57                 −                0.075
                             Direct Mounting*1
                                                     57 to 150               9.8                    −
          Shock
                             147 m/s2 Acceleration, Action time: 11ms, 3 times by half-sine pulse in each direction X, Y, and Z
          resistance
          Noise              Using noise simulator of:
          resistance         Noise voltage: 1,000Vp-p / Noise width: 1µs / Rise: 1ns / Cycle: 30 to 100Hz
          Dielectric
          withstand          500 V AC, for 1 min
          voltage                                                   Between all terminals and ground terminal
          Insulation         5MΩ or more using 500V DC
          resistance         insulation resistance meter
                             Class D grounding (grounding resistance: 100 Ω or less)
          Grounding
                             <Common grounding with a heavy electrical system is not allowed.>*2
          Working
                             Free from corrosive or flammable gas and excessive conductive dusts
          environment
          Working
                             < 2000m*3
          altitude
*1. If 4DA-ADP is connected to the FX3UC Series PLC, direct installation is not possible.
          *2.
                       PLC        Other            PLC         Other          PLC         Other
                                equipment                    equipment                  equipment
F-6
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                                      2 Specifications
FX3U-4DA-ADP (4-channel analog Output)                                                                                           2.2 Power Supply Specifications
                                                                                                                                                                     A
2.2      Power Supply Specifications
                                                                                                                                                                         Common Items
                          Item                                                               Specifications
          D/A conversion circuit                     24V DC +20%-15%, 150mA                                                                                          B
          driving power                              (It is necessary to connect a 24V DC power line to the terminal block.)
                                                                                                                                                                   FX3UC-4AD
                                                                                                                                                                   FX3U-4AD
                                                     5V DC, 15mA
          Interface driving power                    (Since the internal power is supplied from the main unit of the FX Series, it is not
                                                     necessary to supply the power.)
                                                                                                                                                                         FX3U-4AD-ADP
                                                                                         Specifications
                  Item
                                                              Voltage output                                                   Current output
                                                                                                                                                                     D
          Analog output                                     0V to 10 V DC                                                   4mA to 20mA DC
                                                                                                                                                                         FX3G-2AD-BD
          range                                      (External load: 5kΩ to 1MΩ)                                       (External load: 500Ω or less)
          Digital input                                                                  12 bits, binary
          Resolution                                         2.5mV(10V/4000)                                                  4µA(16mA/4000)
                                 • ±0.5% (±50mV) for 10V full scale
                                   (when ambient temperature is 25°C±5 °C)                                                                                            E
                                 • ±1.0% (±100mV) for 10V full scale
                                                                                                                                                                         FX3U-4DA
                                   (when ambient temperature is 0°C to 55°C)
                                                                                   • ±0.5% (±80µA) for 16mA full scale
                                 If the external load resistance (Rs) is less than   (when ambient temperature is 25°C±5°C)
          Total accuracy
                                 5kΩ, the value calculated from the following • ±1.0% (±160µA) for 16mA full scale
                                 formula will be added:                              (when ambient temperature is 0°C to 55 °C)
                                 (Addition will be 100mV per 1%.)                                                                                                      F
                                                                                                                                                                         FX3U-4DA-ADP
                                                            47×100
                                                                         -0.9(%)
                                                            Rs+47
                                 • FX3U/FX3UC Series PLC : 200µs (The data will be updated at every scan time.)
          D/A conversion
                                 • FX3G Series PLC : 250µs (The data will be updated at every scan time.)
          time
                                                                     → For a detailed description of data update, refer to Section 2.4.                             G
                                                                                                                                                                         FX3G-1DA-BD
                                           10V                                                         20mA
                                                                                                       Analog output
                                                                                                                                                                     H
                                     Analog output
          Output
          characteristics
                                                                                                                                                                   FX3U-4AD-PT
                                                                                                             4mA
                                                                                                                                                                            -ADP
                                 • The photocoupler is used to insulate the analog output area from the PLC.
          Insulation method      • The DC/DC converter is used to insulate the power supply line from the analog output area.
                                 • Channels are not insulated from each other.
                                                                                                                                                                            -ADP
          Numbers of I/O
                                 0 point (This number is not related to the maximum number of input/output points of the PLC.)
          points occupied
                                                                                                                                                                       J
                                                                                                                                                                   FX3U-4AD-PNK
                                                                                                                                                                            -ADP
                                                                                                                                                          F-7
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                        2 Specifications
FX3U-4DA-ADP (4-channel analog Output)                                                                     2.4 D/A Conversion Time
                FX3U-4DA-ADP               FX3U-4DA-ADP
                     n'th                       1st                                FX3U/FX3UC Series PLC
                                                                                         Sequence
                                                                                          program
                                                              Digital value
                                                 D/A             writing
                                              conversion
                                                             D/A conversion
                                                200µs        start command
                                                 /4ch
                                                                                       END instruction
                     D/A                                   Digital value writing
                  conversion
                                                             D/A conversion
                  200µs/4ch                                  start command
F-8
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                    2 Specifications
FX3U-4DA-ADP (4-channel analog Output)                                                                 2.4 D/A Conversion Time
                                                                                                                                   A
2.4.2     When connected to a FX3G PLC
                                                                                                                                       Common Items
        1. D/A conversion and special data register update timing
          D/A conversion is performed at every scan time of the PLC.
          During execution of the END instruction, the PLC writes the output setting data of the special data registers,
          performs D/A conversion of the data, and updates the analog output data.                                                 B
                                                                                                                                 FX3UC-4AD
                                                                                                                                 FX3U-4AD
                  FX3U-4DA-ADP               FX3U-4DA-ADP
                       2nd                        1st                                FX3G Series PLC
                                                                                        Sequence
                                                                                         program
                                                                                                                                   C
                                                                                                                                       FX3U-4AD-ADP
                                                                Digital value
                                                   D/A             writing
                                                conversion
                                                               D/A conversion
                                                  250µs        start command
                                                   /4ch
                                                                                     END instruction
                       D/A                                   Digital value writing                                                 D
                    conversion
                                                                                                                                       FX3G-2AD-BD
                                                               D/A conversion
                    250µs/4ch                                  start command
                                                                                                                                       FX3U-4DA
          output.
          If the output holding function cancellation setting is enabled, the output at switching from RUN to STOP will be
          latched.
          Just after power-on, however, the offset value will be output until operation begins.
                                                                                                                                       FX3U-4DA-ADP
          During execution of the END instruction, data in all the connected adapters will be subject to D/A conversion
          and then output (in the order of 1st adapter → 2nd adapter).
FX3G-1DA-BD
                                                                                                                                   H
                                                                                                                                 FX3U-4AD-PT
                                                                                                                                          -ADP
                                                                                                                                           I
                                                                                                                                 FX3U-4AD-PTW
                                                                                                                                          -ADP
                                                                                                                                     J
                                                                                                                                 FX3U-4AD-PNK
                                                                                                                                          -ADP
                                                                                                                        F-9
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                3 Wiring
FX3U-4DA-ADP (4-channel analog Output)
3.     Wiring
         This chapter describes the 4DA-ADP wiring.
         Observe the following caution to wire the 4DA-ADP.
WIRING PRECAUTIONS
          • Make sure to cut off all phases of the power supply externally before attempting wiring work.
            Failure to do so may cause electric shock or damages to the product.
WIRING PRECAUTIONS
          • Connect the DC power supply wiring to the dedicated terminals described in this manual.
            If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will be
            burnt out.
          • Do not wire vacant terminals externally.
            Doing so may damage the product.
          • Perform class D grounding (grounding resistance: 100Ω or less) to the grounding terminal on the main unit.
            Do not use common grounding with heavy electrical systems.
          • When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
            Failure to do so may cause fire, equipment failures or malfunctions.
          • Make sure to observe the following precautions in order to prevent malfunctions under the influence of noise:
            - Do not bundle the power line or twisted shielded cable together with or lay it close to the main circuit, high-
                voltage line, or load line.
                Otherwise, noise disturbance and/or surge induction are likely to take place. As a guideline, lay the control line
                at least 100mm (3.94") or more away from the main circuit, high-voltage line, or load line.
            - Ground the shield of the analog input/output cable at one point on the signal receiving side.
                However, do not use common grounding with heavy electrical systems.
          • Make sure to properly wire to the European terminal board in accordance with the following precautions.
            Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product.
            - The disposal size of the cable end should be 9 mm (0.35").
            - Tightening torque should be between 0.22 to 0.25 N•m.
            - Twist the end of strand wire and make sure there are no loose wires.
            - Do not solder-plate the electric wire ends.
            - Do not connect more than the specified number of wires or electric wires of unspecified size.
            - Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
F-10
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                            3 Wiring
FX3U-4DA-ADP (4-channel analog Output)                                                     3.1 Terminal Layout
                                                                                                                   A
3.1      Terminal Layout
                                                                                                                       Common Items
         The terminals of the 4DA-ADP are arranged as follows:
                                                                                                                 FX3UC-4AD
                                                                                                                 FX3U-4AD
                             FX3U-4DA-ADP
POWER
                                                       Signal          Application
                                                        24+
                                                                                                                   C
                                                                 External power
                         24+
                                                                                                                       FX3U-4AD-ADP
                                                        24-
                         24-
                                                                 Grounding terminal
                                                        V1+
                         VI+
                                                       COM1
                                                        V2+                                                        D
                                                        I2+      Channel 2 analog output
                         V3+ COM2 I2+
                                                                                                                       FX3G-2AD-BD
                                                       COM2
                                                        V3+
                                                        I3+      Channel 3 analog output
                         V4+ COM3 I3+
                                                       COM3
                                                        V4+
                                                        I4+      Channel 4 analog output                            E
                         I4+
                         COM4
                                                                                                                       FX3U-4DA
                                                       COM4
                                                                                                                       FX3U-4DA-ADP
                                                                                                                  G
FX3G-1DA-BD
                                                                                                                   H
                                                                                                                 FX3U-4AD-PT
                                                                                                                          -ADP
                                                                                                                           I
                                                                                                                 FX3U-4AD-PTW
                                                                                                                          -ADP
                                                                                                                     J
                                                                                                                 FX3U-4AD-PNK
                                                                                                                          -ADP
                                                                                                      F-11
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                   3 Wiring
FX3U-4DA-ADP (4-channel analog Output)                                         3.2 Applicable Cables and Terminal Tightening Torque
       1. Cable
         Applicable cable and tightening torque
                            Wire size (stranded/       Tightening
                                                                                            Termination
                                single-wire)             torque
                          0.3mm2 to 0.5mm2                          • To connect a stranded cable, peel the cover off the cable
          Single-wire                                                 and then twist the core before connection.
                          (AWG22 to 20)
                                                                    • To connect a single-wire cable, just peel the cover off the
          2-wire          0.3mm2(AWG22)                               cable before connection.
                                                       0.22N•m to • Rod terminal with insulation sleeve
          Rod terminal    0.3mm2 to 0.5mm2              0.25N•m     (recommended terminal)
          with            (AWG22 to 20)                             AI 0.5-8WH : Manufactured by Phoenix Contact
          insulation      (Refer to the rod terminal
                                                                  • Caulking tool
          sleeve          external view shown in
                                                                    CRIMPFOX ZA 3 : Manufactured by Phoenix Contact
                          the following figure.)
                                                                    (or CRIMPFOX UD 6 : Manufactured by Phoenix Contact)
       3. Tool
         • To tighten terminals, use a small-sized screwdriver whose head is straight and is not widened as shown in
           the figure to the right.
            Note:
            If the diameter of screwdriver grip is too small, tightening torque will not
                                                                                                                         The head
            be able to be achieved. Use the following recommended screwdriver or                                         should be
            an appropriate replacement (grip diameter: approximately 25mm).                                              straight.
                         Manufacturer                            Model
            Phoenix Contact                                   SZS 0.4×2.5                       0.4mm                   2.5mm
                                                                                                (0.01")                 (0.09")
F-12
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                     3 Wiring
FX3U-4DA-ADP (4-channel analog Output)                                                                            3.3 Power Supply Line
                                                                                                                                            A
3.3      Power Supply Line
                                                                                                                                                Common Items
         Connect the 24V DC power supply line of the 4DA-ADP to the 24+ and 24- terminals of the terminal block.
                                                                                                                                          FX3UC-4AD
                                                                                                                                          FX3U-4AD
         1. To use an External power supply                             2. To use the 24V DC power of the PLC
                                                                                                                                                FX3U-4AD-ADP
                24- 24+                                                           24- 24+                0V 24V                             D
                                                                                                                                                FX3G-2AD-BD
         Terminal                                                           Terminal
         block                                                              block
                                           Class-D                                                        Class-D
                      24V DC              grounding                                                      grounding
                                                                                                                                             E
         Caution regarding connection of the power supply line:
                                                                                                                                                FX3U-4DA
         • Ground the "    " terminal to class-D grounded power supply line (100Ω or less) together with the
           grounding terminal of the PLC main unit.
         • For the timing of power-on/off when using an external power supply, see the following manual of the PLC
           to be connected.
                                                   → Refer to the FX3G Series User's Manual - Hardware Edition.                               F
                                                   → Refer to the FX3U Series User's Manual - Hardware Edition.
                                                                                                                                                FX3U-4DA-ADP
3.3.2    To Connect To the FX3UC Series PLC
FX3G-1DA-BD
                                                                                            Power                                           H
                                                                 Power             Power crossover
                                                                                                                                          FX3U-4AD-PT
                                                                             Class-D
                                                      24V DC                grounding
                                                                                                                                                   -ADP
         • Ground the "    " terminal to a class-D grounded power supply line (100Ω or less) together with the
           grounding terminal of the PLC main unit.
                                                                                                                                                   -ADP
                                                                                                                               F-13
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                           3 Wiring
FX3U-4DA-ADP (4-channel analog Output)                                                                 3.4 Analog Output Line
                                                         Class-D
                                                        grounding
          *1.   Use 2-core shielded twisted pair cable for the analog output lines, and separate the analog output
                lines from other power lines or inductive lines.
          *2.   24V DC service power supply of the FX3G/FX3U Series PLC can also be used.
          *3.   Ground the shielded wire at one point on the signal receiving side.
3.5      Grounding
         Grounding should be performed as stated below.
         • The grounding resistance should be 100Ω or less.
         • Independent grounding should be performed for best results.
           When independent grounding is not performed, perform "shared grounding" as shown in the following
           figure.
                                   → For details, refer to User’s Manual - Hardware Edition of the PLC Series.
F-14
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                   4 Programming
FX3U-4DA-ADP (4-channel analog Output)                                                     4.1 Writing of D/A Conversion Data
                                                                                                                                      Common Items
4.     Programming
         This chapter describes how to create programs that can output the analog data using the 4DA-ADP.                         B
                                                                                                                                FX3UC-4AD
                                                                                                                                FX3U-4AD
4.1      Writing of D/A Conversion Data
         1) The input digital data will be converted into analog data and then output to the terminals.
         2) If data is stored in the special devices, the averaging time can be set, and the output mode can be                   C
            specified.
                                                                                                                                      FX3U-4AD-ADP
         3) Special auxiliary relays (10 points) and special data registers (10 points) are assigned automatically
            starting from the adapter nearest the main unit.
                                 → For a detailed description of special device assignment, refer to Section 4.2.
         • FX3U, FX3UC Series PLC
                                      Communi-          High-speed
                                                                                                                                  D
                                        cation
                                                                                                                                      FX3G-2AD-BD
                                                        input/output
            FX3U-4DA FX3U-4DA FX3U-4DA special FX3U-4DA    special
              -ADP     -ADP     -ADP   adapter   -ADP     adapter                       FX3U/FX3UC Series PLC
                                                      D/A
                                                                             Special auxiliary relays:
                                                                               M8260 to M8269                                      E
                                                                             Special data registers:
                                                                                                                                      FX3U-4DA
                                                                                D8260 to D8269
                                                                                                                                      FX3U-4DA-ADP
                                                                               M8280 to M8289
                         D/A                                                 Special data registers:
                                                                                D8280 to D8289
                                                                                                                                      FX3G-1DA-BD
            The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the
            next adapter as the 2nd analog special adapter, and so on. In this case, however, do not include the high-
            speed input/output special adapter and the communication special adapter.
                                                                                                                                  H
                                                                                                                                FX3U-4AD-PT
                                                                                                                                         -ADP
                                                                                                                                          I
                                                                                                                                FX3U-4AD-PTW
                                                                                                                                         -ADP
                                                                                                                                    J
                                                                                                                                FX3U-4AD-PNK
                                                                                                                                         -ADP
                                                                                                                     F-15
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                     4 Programming
FX3U-4DA-ADP (4-channel analog Output)                                                       4.1 Writing of D/A Conversion Data
                2nd*1               1st
                                                              Special devices
                                                           Special auxiliary relays:
                                                             M8280 to M8289
                                    D/A                    Special data registers:
                                                             D8280 to D8289                  Sequence
                                                                                             Program
                                                           Special auxiliary relays:
                                                             M8290 to M8299
                D/A                                        Special data registers:
                                                             D8290 to D8299
            The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the
            next adapter as the 2nd analog special adapter. In this case, however, do not include the connector
            conversion adapter and the communication special adapter.
          *1.    The second special adapter is not available in the 14-point and 24-point type main unit.
F-16
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                   4 Programming
FX3U-4DA-ADP (4-channel analog Output)                                                          4.2 List of Special Devices
                                                                                                                                A
4.2      List of Special Devices
                                                                                                                                    Common Items
         If 4DA-ADP is connected, special devices will be assigned automatically as shown in the following table:
         • FX3U, FX3UC Series PLC
                                                                                                        R: Read / W: Write
          Special                Device number
                                                                                                                                B
                                                                          Description                Attribute Reference
                                                                                                                              FX3UC-4AD
                                                                                                                              FX3U-4AD
          device        1st      2nd       3rd      4th
                       M8260    M8270    M8280     M8290   Switches the output mode of channel 1.      R/W
                       M8261    M8271    M8281     M8291   Switches the output mode of channel 2.      R/W       Section
                       M8262    M8272    M8282     M8292   Switches the output mode of channel 3.      R/W         4.3
                       M8263    M8273    M8283     M8293   Switches the output mode of channel 4.      R/W                      C
                                                                                                                                    FX3U-4AD-ADP
                                                           Sets the cancel of the channel-1 output
                       M8264    M8274    M8284     M8294                                               R/W
                                                           holding function.
          Special
          auxiliary                                        Sets the cancel of the channel-2 output
                       M8265    M8275    M8285     M8295                                               R/W
           relay                                           holding function.                                     Section
                                                           Sets the cancel of the channel-3 output                 4.4
                       M8266    M8276    M8286     M8296
                                                           holding function.
                                                                                                       R/W                      D
                                                                                                                                    FX3G-2AD-BD
                                                           Sets the cancel of the channel-4 output
                       M8267    M8277    M8287     M8297                                               R/W
                                                           holding function.
                      M8268 to M8278 to M8288 to M8298 to
                                                          Unused (Do not use.)                          -           -
                       M8269    M8279    M8289    M8299
                       D8260    D8270    D8280     D8290   Channel-1 output setting data               R/W
                       D8261    D8271    D8281     D8291   Channel-2 output setting data               R/W       Section
                                                                                                                                 E
                                                                                                                                    FX3U-4DA
                       D8262    D8272    D8282     D8292   Channel-3 output setting data               R/W         4.5
                       D8263    D8273    D8283     D8293   Channel-4 output setting data               R/W
          Special
            data   D8264 to D8274 to D8284 to D8294 to
                                                       Unused (Do not use.)                             -           -
          register  D8267    D8277    D8287    D8297
                                                                                                                                    FX3U-4DA-ADP
                                                                                                                 Section
                       D8269    D8279    D8289     D8299   Model code = 2                               R
                                                                                                                   4.7
FX3G-1DA-BD
                                                                                                                                H
                                                                                                                              FX3U-4AD-PT
                                                                                                                                       -ADP
                                                                                                                                        I
                                                                                                                              FX3U-4AD-PTW
                                                                                                                                       -ADP
                                                                                                                                  J
                                                                                                                              FX3U-4AD-PNK
                                                                                                                                       -ADP
                                                                                                                   F-17
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                         4 Programming
FX3U-4DA-ADP (4-channel analog Output)                                                                 4.3 Switching of Output Mode
F-18
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                       4 Programming
FX3U-4DA-ADP (4-channel analog Output)                                           4.4 Output Holding Function Cancellation Setting
                                                                                                                                      A
      1. Program Example (For FX3U, FX3UC Series PLC)
                                                                                                                                          Common Items
         To switch the output mode of a channel, create a sequence program as follows:
          1) To switch the channel output mode of          2) To switch the output mode of channel 2
             channel 1 of the 1st analog special              of the 1st analog special adapter to the
             adapter to the voltage output mode:              current output mode:
             M8001                                             M8000                                                                  B
                                              M8260                                              M8261
                                                                                                                                    FX3UC-4AD
                                                                                                                                    FX3U-4AD
             Normally OFF                                       Normally ON
                                                                                                                                          FX3U-4AD-ADP
         This setting can hold the analog data output or to output the offset data (0V for voltage output mode, 4mA for
         current output mode) when the PLC stops.
         To cancel or set the output holding function, use the following special auxiliary relays:
         • FX3U, FX3UC Series PLC
                    Special auxiliary relay
                                                                                                                                      D
                                                                                   Description
                                                                                                                                          FX3G-2AD-BD
             1st        2nd          3rd       4th
                                                      Cancel output holding      function
           M8264      M8274         M8284     M8294
                                                      setting for channel 1
                                                      Cancel output holding      function OFF: Holds the analog data output
           M8265      M8275         M8285     M8295
                                                      setting for channel 2                    just before stop of the PLC.            E
                                                      Cancel output holding      function ON : Outputs the offset data at
                                                                                                                                          FX3U-4DA
           M8266      M8276         M8286     M8296                                            stop of the PLC.
                                                      setting for channel 3
                                                      Cancel output holding      function
           M8267      M8277         M8287     M8297
                                                      setting for channel 4
                                                                                                                                        F
         • FX3G Series PLC
                                                                                                                                          FX3U-4DA-ADP
           Special auxiliary relay
                                                                  Description
              1st             2nd
                                       Cancel output holding    function
            M8284          M8294
                                       setting for channel 1
                                       Cancel output holding    function OFF: Holds the analog data output
                                                                                                                                     G
            M8285          M8295
                                                                                                                                          FX3G-1DA-BD
                                       setting for channel 2                  just before stop of the PLC.
                                       Cancel output holding    function ON : Outputs the offset data at
            M8286          M8296                                              stop of the PLC.
                                       setting for channel 3
                                       Cancel output holding    function
            M8287          M8297
                                       setting for channel 4
                                                                                                                                      H
                                                                                                                                    FX3U-4AD-PT
         1) To set the output holding function for         2) To cancel the output holding function for
            channel 1 of the 1st analog special adapter:      channel 2 of the 1st analog special adapter:
                                                               M8000
                                                                                                                                              I
             M8001
                                                                                                                                    FX3U-4AD-PTW
                                              M8264                                           M8265
             Normally OFF                                      Normally ON
                                                                                                                                             -ADP
                                                                                                                                        J
                                                                                                                                    FX3U-4AD-PNK
                                                                                                                                             -ADP
                                                                                                                         F-19
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                      4 Programming
FX3U-4DA-ADP (4-channel analog Output)                                                                   4.5 Output Setting Data
         Using the indicator or the sequence program, input the digital data to be subject to D/A conversion (to be
         output as analog data) in D100 and D101.
F-20
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                              4 Programming
FX3U-4DA-ADP (4-channel analog Output)                                                                                  4.6 Error Status
                                                                                                                                             A
4.6      Error Status
                                                                                                                                                 Common Items
      1. Description of setting
         If an error is detected on 4DA-ADP, the error status data will be stored in the corresponding special data
         register.
         The following table shows the special data registers that store the error status data:
                                                                                                                                             B
                                                                                                                                           FX3UC-4AD
                                                                                                                                           FX3U-4AD
         • FX3U, FX3UC Series PLC
                                                                                                                                                 FX3U-4AD-ADP
         • FX3G Series PLC
                                                                                                                                                 FX3G-2AD-BD
         Check the ON/OFF status of each bit of the error status data register to check the description of the error.
         Errors are assigned to the bits as shown in the following table. Create a program to detect errors.
                            Bit                                                   Description
                            b0                 Channel-1 output data setting error                                                            E
                                                                                                                                                 FX3U-4DA
                            b1                 Channel-2 output data setting error
                            b2                 Channel-3 output data setting error
                            b3                 Channel-4 output data setting error
                            b4                 EEPROM error
                       b5 to b15               Unused                                                                                          F
                                                                                                                                                 FX3U-4DA-ADP
      2. Program Example 1 (For FX3G, FX3U, FX3UC Series PLC)
                M8000
                Normally
                                          MOV           D8288     K4M0
                                                                                                                                            G
                                                                                                                                                 FX3G-1DA-BD
                ON
                  M0
                                                                   Y000        Channel-1 output data setting error in
                                                                               3rd *1 adapter.
                  M1
                                                                   Y001        Channel-2 output data setting error in
                                                                               3rd *1 adapter.
                                                                                                                                             H
                                                                                                                                           FX3U-4AD-PT
                  M2
                                                                   Y002        Channel-3 output data setting error in
                                                                               3rd *1 adapter.
                                                                                                                                                    -ADP
                  M3
                                                                   Y003        Channel-4 output data setting error in
                                                                               3rd *1 adapter.
                                                                                                                                                     I
                                                                                                                                           FX3U-4AD-PTW
                  M4
                                                                   Y004        EEPROM error in the 3rd *1adapter
                                                                                                                                                    -ADP
                                                                                                                                F-21
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                              4 Programming
FX3U-4DA-ADP (4-channel analog Output)                                                                  4.6 Error Status
             D8268.0
                                                        Y000   Channel-1 output data setting error in
                                                               1st adapter
             D8268.1
                                                        Y001   Channel-2 output data setting error in
                                                               1st adapter
             D8268.2
                                                        Y002   Channel-3 output data setting error in
                                                               1st adapter
             D8268.3
                                                        Y003   Channel-4 output data setting error in
                                                               1st adapter
             D8268.4
                                                        Y004   EEPROM error in 1st adapter
F-22
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                 4 Programming
FX3U-4DA-ADP (4-channel analog Output)                                                                                     4.7 Model Code
                                                                                                                                              A
4.7      Model Code
                                                                                                                                                  Common Items
                                                                                                                 Initial value: K2
                                                                                                  Numeric data type: Decimal (K)
      1. Description of setting                                                                                                               B
         When the 4DA-ADP is connected, model code "2" is stored in the corresponding special data register.
                                                                                                                                            FX3UC-4AD
                                                                                                                                            FX3U-4AD
         The following table shows the special data registers that store the model code:
         • FX3U, FX3UC Series PLC
                1st         2nd        3rd              4th                                 Description
            D8269         D8279       D8289            D8299     Model code                                                                   C
                                                                                                                                                  FX3U-4AD-ADP
         • FX3G Series PLC
                1st         2nd                                   Description
            D8289         D8299       Model code
         Use the special data registers above to check whether 4DA-ADP is connected or not.                                                   D
                                                                                                                                                  FX3G-2AD-BD
      2. Program Example (For FX3U, FX3UC Series PLC)
                                                                                Checks the model code
                  FNC 224     D8269        K2                       Y007        of the 1st analog special
                   LD =                                                         adapter.
                                                                                                                                               E
                                                                                                                                                  FX3U-4DA
4.8      Basic Program Example
         Create the following basic program example to output D/A converted analog data.
         • For FX3G, FX3U, FX3UC Series PLC
         The following program will set channel 1 of the 3rd*1 adapter to the voltage output mode and channel 2 to
                                                                                                                                                F
                                                                                                                                                  FX3U-4DA-ADP
         current output mode, and will set digital data in D100 and D101 for D/A conversion.
                  M8001
                                                         M8280      Sets the output mode of channel 1 to the voltage
                                                                    output mode (0 V to 10 V).
                                                                                                                                                  FX3G-1DA-BD
                  M8000
                                                         M8281      Sets the output mode of channel 2 to the current
                                                                    output mode (4 mA to 20 mA).
                  M8000
                                  FNC 12                            Performs D/A conversion with the digital data stored
                                                                                                                                              H
                                                D100     D8280
                                                                                                                                            FX3U-4AD-PT
                                  FNC 12        D101     D8281      Performs D/A conversion with the digital data stored
                                   MOV                              in D101 for channel 2.
                                                                                                                                                     -ADP
         Using the indicator or the sequence program, input the digital data to be subject to D/A conversion (to be
         output as analog data) in D100 and D101.                                                                                                     I
                                                                                                                                            FX3U-4AD-PTW
                                                                                                                                                J
                                                                                                                                            FX3U-4AD-PNK
                                                                                                                                                     -ADP
                                                                                                                                  F-23
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                     5 Changing of Output Characteristics
FX3U-4DA-ADP (4-channel analog Output)                                                                      5.1 Example: Changing of Voltage Output Characteristics
       1. Output characteristics
                                                                              subject to D/A conversion
                                    Voltage output characteristics                                                Digital value characteristics
                                    (product specifications)
                                                                              Specified digital output
                                                                                                                  to be changed
                                                                              value to be actually
                       10V
               Analog output
Y-axis
                               5V                                                                         2000
                                                                                                          (5V)
                               1V                                                                          400
                                                                                                           (1V)
                                0 400       2000              4000                                                                                    X-axis
                                                                                                              0                           10000
                                              Digital value input
                                                                                                                  Desired digital value (D100)
               M8002
                                          FNC 12                              Program for setting scaling instruction data table
                                                         K2          D50
                                           MOV
                                                                                    Item                                        Description             Value Device
                                          FNC 12                             Number of points                          Sets the number of points.         2    D50
                                                         K0          D51
                                           MOV                                           X-                            Digital value of specified         0    D51
                                                                              Start coordinate                         start point on X-axis
                                          FNC 12                              point      Y-                            Digital value of desired D/A
                                                        K400         D52                                                                                 400   D52
                                           MOV                                       coordinate                        conversion start point
                                                                                          X-     Digital value of specified end 10000                          D53
                                          FNC 12      K10000         D53        End coordinate point on X-axis
                                           MOV                                  point     Y-     Digital value of desired D/A 2000
                                                                                      coordinate conversion end point                                          D54
                                          FNC 12       K2000         D54
                                           MOV
               M8000                                                           The result of operation by scaling instruction will be stored
                                    FNC 259    D100       D50       D8260
                                      SCL                                      in the D8260.
F-24
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                              5 Changing of Output Characteristics
FX3U-4DA-ADP (4-channel analog Output)                                  5.1 Example: Changing of Voltage Output Characteristics
                                                                                                                                    A
      3. Example of program 2 (For FX3G Series PLC)
                                                                                                                                        Common Items
         • For example, create the following program to change the digital output data (D100) of the 1st analog
           special adapter.
             M8001
                                                                                   Sets the output mode of channel 1 to the
                                                                        M8280
                                                                                   voltage output mode.                             B
                                                                                                                                  FX3UC-4AD
                                                                                                                                  FX3U-4AD
                                                                                   Sets the output holding function for
                                                                        M8284
                                                                                   channel 1.
               FNC 230    D100    K0       FNC 237    D100 K10000        M10       Check to make sure the digital
                LD>=                        AND<=                                  value (D100) is in range.
              M10                                                                                                                   C
                                             FNC 22
                                                                                                                                        FX3U-4AD-ADP
                                                       D100    K1600    D101
                                              MUL
                                                                                                                                    D
                                             FNC 20    D103     K400    D107          Stores the operation result in D8280.
                                              ADD
                                                                                                                                        FX3G-2AD-BD
                                                   FNC 12      D107     D8280
                                                    MOV
                                                                                                                                        FX3U-4DA
         • If the input digital value for the D/A conversion is out of the data table range specified by scaling instruction
           (SCL/FNC259), the FX Series PLC will detect an operation error (error code: K6706).
                                                                                                                                        FX3U-4DA-ADP
                                                                                                                                   G
FX3G-1DA-BD
                                                                                                                                    H
                                                                                                                                  FX3U-4AD-PT
                                                                                                                                           -ADP
                                                                                                                                            I
                                                                                                                                  FX3U-4AD-PTW
                                                                                                                                           -ADP
                                                                                                                                      J
                                                                                                                                  FX3U-4AD-PNK
                                                                                                                                           -ADP
                                                                                                                          F-25
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                               6 Troubleshooting
FX3U-4DA-ADP (4-channel analog Output)                                                        6.1 PLC Version Number Check
6.       Troubleshooting
         This chapter describes the troubleshooting methods and error status.
         If analog data is not output, or if the proper analog value is not output, check the following items:
         • Version number of PLC
         • Wiring
         • Special devices
         • Programs
         • Error status
       1. Power
         The 4DA-ADP needs driving power. Verify that the power supply line is properly connected. Also check that
         the POWER indicator lamp of the 4DA-ADP is on.
       3. Error status
         Check that no error is detected in the 4DA-ADP.
         If an error is detected, check the details of the error, and then check the wiring and programs.
                                                 → For a detailed description of special devices, refer to Chapter 4.
F-26
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                      6 Troubleshooting
FX3U-4DA-ADP (4-channel analog Output)                                                          6.4 Program Check
                                                                                                                      A
6.4      Program Check
                                                                                                                          Common Items
         Check the following items for the program:
                                                                                                                    FX3UC-4AD
                                                                                                                    FX3U-4AD
6.5      Error Status Check
         If an error occurs in the 4DA-ADP, the corresponding bit will turn on.
Bit Description C
                                                                                                                          FX3U-4AD-ADP
                       b0                Channel-1 output data setting error
                       b1                Channel-2 output data setting error
                       b2                Channel-3 output data setting error
                       b3                Channel-4 output data setting error
                       b4                EEPROM error                                                                 D
                                                                                                                          FX3G-2AD-BD
                    b5 to b15            Unused
         To solve the problem, refer to the troubleshooting method described below:
                                                                                                                          FX3U-4DA
            Analog data will not be correctly output.
         2) Remedy
            Check that the specified digital value is within the specified range.
                                                                                                                          FX3U-4DA-ADP
            The adjustment data set in the EEPROM before delivery from our factory cannot be read out properly or
            is destroyed.
         2) Remedy
            Please contact the nearest Mitsubishi Electric distributor office.
FX3G-1DA-BD
                                                                                                                      H
                                                                                                                    FX3U-4AD-PT
                                                                                                                             -ADP
                                                                                                                              I
                                                                                                                    FX3U-4AD-PTW
                                                                                                                             -ADP
                                                                                                                        J
                                                                                                                    FX3U-4AD-PNK
                                                                                                                             -ADP
                                                                                                          F-27
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition      6 Troubleshooting
FX3U-4DA-ADP (4-channel analog Output)                       6.5 Error Status Check
MEMO
F-28
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3G-1DA-BD (1-channel analog Output)
                                                                                                                                       Common Items
                                                                                                                                   B
                                                                                                                                 FX3UC-4AD
                                                                                                                                 FX3U-4AD
         FX3G/FX3U/FX3UC Series Programmable
         Controllers                                                                                                               C
                                                                                                                                       FX3U-4AD-ADP
         User's Manual [Analog Control Edition]
         FX3G-1DA-BD (1-channel analog Output)
                                                                                                                                   D
                                                                                                                                       FX3G-2AD-BD
                                                                                                                                    E
                                                                                                                                       FX3U-4DA
                                                                                                                                     F
                                                                                                                                       FX3U-4DA-ADP
                                                                                                                                  G
FX3G-1DA-BD
                                                                                                                                   H
                                                                                                                                 FX3U-4AD-PT
         Foreword
                                                                                                                                          -ADP
         This manual describes the specifications, wiring, and operation method for the FX3G-1DA-BD analog output
         expansion board (1-channel analog output) and should be read and understood before attempting to install or
         use the unit.                                                                                                                     I
         Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
                                                                                                                                 FX3U-4AD-PTW
           This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
           licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
           rights which may occur as a result of using the contents noted in this manual.                                            J
                                                                                                                                 FX3U-4AD-PNK
                                                                                                                         G-1
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3G-1DA-BD (1-channel analog Output)
G-2
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                      1 Outline
FX3G-1DA-BD (1-channel analog Output)                                                                           1.1 Outline of Functions
                                                                                                                                                  Common Items
1.       Outline
           This chapter outlines the FX3G-1DA-BD (referred to as 1DA-BD).                                                                     B
                                                                                                                                            FX3UC-4AD
                                                                                                                                            FX3U-4AD
1.1        Outline of Functions
           The FX3G-1DA-BD is an analog expansion board. Which is connectable with the FX3G Series PLC to output
           the voltage/current data for up to 1 channel.
                                                                                                                                              C
           1) Up to 2*1 units of 1DA-BD can be connected to the FX3G Series PLC.
                                                                                                                                                  FX3U-4AD-ADP
              (Including other analog expansion boards, analog special adapters).
           2) Either "voltage output" or "current output" can be specified.
           3) The D/A conversion results will be automatically output as the values to the special data register of the
              FX3G Series PLC.
                                                                                                                                              D
                                                                                                                                                  FX3G-2AD-BD
                                                     System                                                   Point and section to be
                                                                                                                    referred to
                        2*1 maximum
           (                                       (
                                                                                                             Number of connectable
               including other analog expansion                                                         ……
                                                                                                             units
               boards, analog special adapters.                             FX3G Series PLC
                                                                                                                                               E
                                                                                                                                                  FX3U-4DA
                      2nd             1st                                                                    To check the connectable
                                                                                                        …… PLC model number, refer
                                                                                                             to Section 1.3.
                                                                                                                                                  FX3U-4DA-ADP
                         Analog data                   Connected to the option connector 2
                                                                                                              For a detailed
                                                                                                        …… description of wiring,
                                                                                                              refer to Chapter 3.
                         Inverter, etc.
                                                                                                                                             G
                                                                                                                                                  FX3G-1DA-BD
                                                                                                             For a detailed description
           Contents                                                               For FX3G Series PLC   …… of special devices, refer to
                                                                                                             Chapter 4.
        Output mode
          switching
                                            Transfer direction
                                                                      1st board
                                                                                     Special devices
                                                                                  M/D8260 to M/D8269
                                                                                                             For a detailed description
                                                                                                             of a basic program, refer to
                                                                                                                                              H
      Output setting data
                                                                                                                                            FX3U-4AD-PT
                                                                                                             Section 4.8.
                                                                     2nd board    M/D8270 to M/D8279
          Error status
                                                                                                                                                     -ADP
     Refer to the system configuration shown in the User's Manual - Hardware Edition to check the number of connectable units
     and to configure the entire system.
     *1. Only 1 analog board can be connected to the 14-point and 24-point type main unit.
                                                                                                                                                      I
                                                                                                                                            FX3U-4AD-PTW
                                                                                                                                                     -ADP
                                                                                                                                                J
                                                                                                                                            FX3U-4AD-PNK
                                                                                                                                                     -ADP
                                                                                                                                    G-3
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                       1 Outline
FX3G-1DA-BD (1-channel analog Output)                                        1.2 Setup Procedure Before Starting Operation
FX3G-1DA-BD
Refer to Chapter 1.
                           Wiring                                    Wiring:
                                                                     • Power supply line
                                                                     • Analog output line
                                      Refer to Chapter 4.
                                                                     Programming:
                        Programming
                                                                     • Details of special devices
                                                                     • Examples of basic programs
                                       Refer to Chapter 5.
G-4
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                          1 Outline
FX3G-1DA-BD (1-channel analog Output)                                                              1.3 Connectable PLCs and Version Numbers
                                                                                                                                                  A
1.3      Connectable PLCs and Version Numbers
                                                                                                                                                      Common Items
         The 1DA-BD is compatible with the following PLC.
                                                                                                                                                FX3UC-4AD
                                                                                                                                                FX3U-4AD
      1. Version check
         Special data register D8001 contains information for determining the PLC version number.
                                                                                                                                                  C
                                                                                                                                                      FX3U-4AD-ADP
                            D8001            2       6         1        1       0
                       PLC type and
                      version number                                        Version data (Example: Ver. 1.10)
                                                      PLC type (Example: 26 = FX3G series)
                                                                                                                                                  D
                                                                                                                                                      FX3G-2AD-BD
      2. How to look at the manufacturer's serial number
         The year and month of production of the product can be seen from the manufacturer's serial number
         "SERIAL" indicated on the label adhered to the right side of the product.
                                                                                                                                                      FX3U-4DA
                                                                                    PROGRAMMABLE
                                               MITSUBISHI                             CONTROLLER
SERIAL 8X0001 F
                                                                                                                                                      FX3U-4DA-ADP
                                                 MITSUBISHI ELECTRIC CORPORATION
                                               MADE IN JAPAN
8 X 0 0 0 1
                                                                                 Control number                                                  G
                                                                    Month (Example: Oct.):(1 to 9 = January to September,
                                                                                                                                                      FX3G-1DA-BD
                                                                    X = October, Y = November, Z = December)
                                                               Year (Example: 2008): Last digit of year
         Use the programming tool with the following version number to create programs for the 1DA-BD of the FX3G
         Series PLC:
                    Software                     Version number                                         Remarks
                                                                                                                                                         -ADP
          GX Developer
          • SW D5C-GPPW-J                     (Ver.8.72A or later)                      When selecting a model, select FX3G.                              I
          • SW D5C-GPPW-E
                                                                                                                                                FX3U-4AD-PTW
         If a programming tool with the wrong version number is used, programming will not be possible.
                                                                                                                                                         -ADP
                                                                                                                                                    J
                                                                                                                                                FX3U-4AD-PNK
                                                                                                                                                         -ADP
                                                                                                                                         G-5
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                         2 Specifications
FX3G-1DA-BD (1-channel analog Output)                                                                    2.1 Generic Specifications
2.     Specifications
         This chapter describes the general and performance specifications for 1DA-BD.
                Item                                                    Specifications
          Ambient            0 to 55°C (32 to 131°F) when operating
          temperature        -25 to 75°C (-13 to 167°F) when stored
          Relative
                             5 to 95%RH (no condensation) when operating
          humidity
                                                    Frequency         Acceleration      Half amplitude
                                                       (Hz)              (m/s2)              (mm)
                                                                                                         10 times of testing in
          Vibration                                    10 - 57             -                0.035        each direction (X-, Y-,
                             DIN Rail Mounting
          resistance                                 57 - 150             4.9                    -       and Z-axis directions)
                                                                                                         (Total: 80 min, each)
                                                     10 to 57              −                0.075
                             Direct Mounting
                                                    57 to 150             9.8                    −
          Shock
                             147 m/s2 Acceleration, Action time: 11ms, 3 times by half-sine pulse in each direction X, Y, and Z
          resistance
          Noise              Using noise simulator of:
          resistance         Noise voltage: 1,000Vp-p / Noise width: 1µs / Rise: 1ns / Cycle: 30 to 100Hz
                             Class D grounding (grounding resistance: 100 Ω or less)
          Grounding
                             <Common grounding with a heavy electrical system is not allowed.>*1
          Working
                             Free from corrosive or flammable gas and excessive conductive dusts
          environment
          Working
                             < 2000m*2
          altitude
          *1.
                       PLC        Other          PLC        Other         PLC          Other
                                equipment                 equipment                  equipment
G-6
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                                 2 Specifications
FX3G-1DA-BD (1-channel analog Output)                                                                                      2.2 Performance Specifications
                                                                                                                                                                A
2.2      Performance Specifications
                                                                                                                                                                    Common Items
                                                                                  Specifications
                  Item
                                                           Voltage output                                               Current output                          B
                                                                                                                                                              FX3UC-4AD
                                                                                                                                                              FX3U-4AD
          Analog output                                    0V to 10 V DC                                             4mA to 20mA DC
          range                                     (External load: 2kΩ to 1MΩ)                                 (External load: 500Ω or less)
          Digital input                                     12 bits, binary                                              11 bits, binary
          Resolution                                      2.5mV(10V/4000)                                              8µA(16mA/2000)
                              • ±0.5% (±50mV) for 10V full scale
                                (when ambient temperature is 25°C±5 °C)
                                                                                                                                                                C
                                                                                                                                                                    FX3U-4AD-ADP
                              • ±1.0% (±100mV) for 10V full scale
                                (when ambient temperature is 0°C to 55°C)
                                                                             • ±0.5% (±80µA) for 16mA full scale
                              Shipment adjustment is carried out by external
                                                                               (when ambient temperature is 25°C±5°C)
          Total accuracy      load resistance 2kΩ.
                                                                             • ±1.0% (±160µA) for 16mA full scale
                              If external load resistance becomes larger
                                                                               (when ambient temperature is 0°C to 55 °C)                                       D
                              than 2kΩ, the output voltage will increase
                                                                                                                                                                    FX3G-2AD-BD
                              slightly.
                              When the load is 1MΩ, the output voltage
                              becomes about 2% higher than the correct
                              value.
          D/A conversion                             60µs (The data will be updated at every scan time.)
          time                                                   → For a detailed description of data update, refer to Section 2.4.                              E
                                                                                                                                                                    FX3U-4DA
                                         10V                                                   20mA
                                                                                                                                                                  F
                                                                                                Analog output
                                    Analog output
                                                                                                                                                                    FX3U-4DA-ADP
          Output
          characteristics
                                                                                                    4mA
                                                                                                                                                                    FX3G-1DA-BD
                              Caution:
                              An area of dead band is located in the region
                              of 0V. Therefore the output analog value may
                              not represent the digital value accurately.
          Insulation method   • The analog output area is not insulated from the PLC.
          Numbers of I/O
                                                                                                                                                                H
                              0 point (This number is not related to the maximum number of input/output points of the PLC.)
                                                                                                                                                              FX3U-4AD-PT
          points occupied
                                                                                                                                                                       -ADP
                                                                                                                                                                        I
                                                                                                                                                              FX3U-4AD-PTW
                                                                                                                                                                       -ADP
                                                                                                                                                                  J
                                                                                                                                                              FX3U-4AD-PNK
                                                                                                                                                                       -ADP
                                                                                                                                                    G-7
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                           2 Specifications
FX3G-1DA-BD (1-channel analog Output)                                                                         2.3 D/A Conversion Time
Sequence Program
END instruction
                                            D/A                                         D/A
                                         conversion                                  conversion
                                             60µs                                      60µs
                                             /1ch                                      /1ch
                                       FX3G-1DA-BD                             FX3G-1DA-BD
                                           1st                                      2nd
G-8
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                3 Wiring
FX3G-1DA-BD (1-channel analog Output)
                                                                                                                                           Common Items
3.     Wiring
         This chapter describes the 1DA-BD wiring.                                                                                     B
         Observe the following caution to wire the 1DA-BD.
                                                                                                                                     FX3UC-4AD
                                                                                                                                     FX3U-4AD
          WIRING PRECAUTIONS
          • Make sure to cut off all phases of the power supply externally before attempting wiring work.
            Failure to do so may cause electric shock or damages to the product.                                                       C
                                                                                                                                           FX3U-4AD-ADP
          WIRING PRECAUTIONS
          • Connect the DC power supply wiring to the dedicated terminals described in this manual.
            If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will be
            burnt out.
                                                                                                                                       D
                                                                                                                                           FX3G-2AD-BD
          • Do not wire vacant terminals externally.
            Doing so may damage the product.
          • Perform class D grounding (grounding resistance: 100Ω or less) to the grounding terminal on the main unit.
            Do not use common grounding with heavy electrical systems.
          • When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
            Failure to do so may cause fire, equipment failures or malfunctions.                                                        E
          • Make sure to observe the following precautions in order to prevent malfunctions under the influence of noise:
                                                                                                                                           FX3U-4DA
            - Do not bundle the power line or twisted shielded cable together with or lay it close to the main circuit, high-
                voltage line, or load line.
                Otherwise, noise disturbance and/or surge induction are likely to take place. As a guideline, lay the control line
                at least 100mm (3.94") or more away from the main circuit, high-voltage line, or load line.
            - Ground the shield of the analog input/output cable at one point on the signal receiving side.
                However, do not use common grounding with heavy electrical systems.                                                      F
          • Make sure to properly wire to the European terminal board in accordance with the following precautions.
                                                                                                                                           FX3U-4DA-ADP
            Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product.
            - The disposal size of the cable end should be 9 mm (0.35").
            - Tightening torque should be between 0.22 to 0.25 N•m.
            - Twist the end of strand wire and make sure there are no loose wires.
            - Do not solder-plate the electric wire ends.
            - Do not connect more than the specified number of wires or electric wires of unspecified size.                           G
            - Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
FX3G-1DA-BD
                                                                                                                                       H
                                                                                                                                     FX3U-4AD-PT
                                                                                                                                              -ADP
                                                                                                                                               I
                                                                                                                                     FX3U-4AD-PTW
                                                                                                                                              -ADP
                                                                                                                                         J
                                                                                                                                     FX3U-4AD-PNK
                                                                                                                                              -ADP
                                                                                                                           G-9
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                    3 Wiring
FX3G-1DA-BD (1-channel analog Output)                                              3.1 Terminal Layout
                            Signal      •              •   V+      I+     VI-
                                            Unused           Output       COM
                         Application
                                            terminal        terminal    terminal
G-10
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                   3 Wiring
FX3G-1DA-BD (1-channel analog Output)                                          3.2 Applicable Cables and Terminal Tightening Torque
                                                                                                                                          A
3.2      Applicable Cables and Terminal Tightening Torque
                                                                                                                                              Common Items
         Use the following cables to connect with the counterpart equipment. Terminate the cable end as shown below.
      1. Cable
         Applicable cable and tightening torque
                                                                                                                                          B
                                                                                                                                        FX3UC-4AD
                                                                                                                                        FX3U-4AD
                            Wire size (stranded/       Tightening
                                                                                            Termination
                                single-wire)             torque
                          0.3mm2 to 0.5mm2                          • To connect a stranded cable, peel the cover off the cable
          Single-wire                                                 and then twist the core before connection.
                          (AWG22 to 20)
          2-wire          0.3mm2(AWG22)
                                                                    • To connect a single-wire cable, just peel the cover off the
                                                                      cable before connection.
                                                                                                                                          C
                                                                                                                                              FX3U-4AD-ADP
                                                       0.22N•m to • Rod terminal with insulation sleeve
          Rod terminal    0.3mm2 to 0.5mm2              0.25N•m     (recommended terminal)
          with            (AWG22 to 20)                             AI 0.5-8WH : Manufactured by Phoenix Contact
          insulation      (Refer to the rod terminal
                                                                  • Caulking tool
          sleeve          external view shown in
                                                                    CRIMPFOX ZA 3 : Manufactured by Phoenix Contact
                          the following figure.)
                                                                    (or CRIMPFOX UD 6 : Manufactured by Phoenix Contact)                  D
                                                                                                                                              FX3G-2AD-BD
      2. Termination of cable end
         To terminate the cable, treat the stranded/single wire directly or use a rod terminal with insulation sleeve.
         • To directly terminate the end of a stranded/single-wire cable:                    Termination of cable end
           - Twist the end of the stranded cable so that the "barbed wires"
             cannot protrude.                                                                                                              E
           - Do not solder-plate the end of the cable.
                                                                                                                                              FX3U-4DA
                                                                                                             9mm
                                                                                                            (0.35")
         • To terminate cable end using a rod terminal with insulation sleeve:                 Insulation sleeve Contact area
           If the cable cover is too thick, it may be difficult to insert the cable into                         (Crimp area)
           the insulation sleeve. For this reason, select an appropriate cable while
           referring to the external view.                                                                            8mm    (0.31")
                                                                                                                                            F
                                                                                                                                              FX3U-4DA-ADP
                   Manufacturer                 Model                Caulking tool             2.6mm          14mm
                                                                                                (0.1")
                                                                  CRIMPFOX ZA 3                               (0.55")
            Phoenix Contact                  AI 0.5-8WH
                                                                (or CRIMPFOX UD 6)
      3. Tool
                                                                                                                                         G
         • To tighten terminals, use a small-sized screwdriver whose head is straight and is not widened as shown in
                                                                                                                                              FX3G-1DA-BD
           the figure to the right.
            Note:
            If the diameter of screwdriver grip is too small, tightening torque will not
                                                                                                                        The head
            be able to be achieved. Use the following recommended screwdriver or
            an appropriate replacement (grip diameter: approximately 25mm).
                                                                                                                        should be
                                                                                                                        straight.         H
                                                                                                                                        FX3U-4AD-PT
                         Manufacturer                            Model
            Phoenix Contact                                   SZS 0.4×2.5                       0.4mm                   2.5mm
                                                                                                (0.01")                 (0.09")
                                                                                                                                                 -ADP
                                                                                                                                                  I
                                                                                                                                        FX3U-4AD-PTW
                                                                                                                                                 -ADP
                                                                                                                                            J
                                                                                                                                        FX3U-4AD-PNK
                                                                                                                                                 -ADP
                                                                                                                             G-11
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                    3 Wiring
FX3G-1DA-BD (1-channel analog Output)                                                           3.3 Analog Output Line
          *1.   Use 2-core shielded twisted pair cable for the analog output lines, and separate the analog output
                lines from other power lines or inductive lines.
          *2.   Ground the shielded wire at one point on the signal receiving side.
3.4      Grounding
         Grounding should be performed as stated below.
         • The grounding resistance should be 100Ω or less.
         • Independent grounding should be performed for best results.
           When independent grounding is not performed, perform "shared grounding" as shown in the following
           figure.
                                   → For details, refer to User’s Manual - Hardware Edition of the PLC Series.
G-12
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                       4 Programming
FX3G-1DA-BD (1-channel analog Output)                                                          4.1 Writing of D/A Conversion Data
                                                                                                                                          Common Items
4.     Programming
         This chapter describes how to create programs that can output the analog data using the 1DA-BD.                              B
                                                                                                                                    FX3UC-4AD
                                                                                                                                    FX3U-4AD
4.1      Writing of D/A Conversion Data
         1) The input digital data will be converted into analog data and then output to the terminals.
         2) If data is stored in the special devices, the averaging time can be set, and the output mode can be                       C
            specified.
                                                                                                                                          FX3U-4AD-ADP
         3) Special auxiliary relays (10 points) and special data registers (10 points) are assigned respectively to the
            analog expansion board connected to the option connector 1 and the analog expansion board connected
            to the option connector 2 in this order.
                                  → For a detailed description of special device assignment, refer to Section 4.2.
         • FX3G Series PLC                                                                                                            D
                                                                                                                                          FX3G-2AD-BD
                                          FX3G Series PLC
Sequence Program
                                                                                                                                       E
                      Special auxiliary relays:       Special auxiliary relays:
                                                                                                                                          FX3U-4DA
                        M8260 to M8269                  M8270 to M8279
                       Special data register:          Special data register:
                        D8260 to D8269                  D8270 to D8279
                                                                                                                                          FX3U-4DA-ADP
                                  1st                          2nd*1
            The analog expansion board connected to the option connector 1 is regarded as the 1st unit, and the
            analog expansion board connected to the option connector 2 is regarded as the 2nd unit.
          *1.   The second analog expansion board is not available in the 14-point and 24-point type main unit.                      G
FX3G-1DA-BD
                                                                                                                                      H
                                                                                                                                    FX3U-4AD-PT
                                                                                                                                             -ADP
                                                                                                                                              I
                                                                                                                                    FX3U-4AD-PTW
                                                                                                                                             -ADP
                                                                                                                                        J
                                                                                                                                    FX3U-4AD-PNK
                                                                                                                                             -ADP
                                                                                                                         G-13
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                       4 Programming
FX3G-1DA-BD (1-channel analog Output)                                                                  4.2 List of Special Devices
       1. Program Example
         To switch the output mode, create a sequence program as follows:
G-14
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                            4 Programming
FX3G-1DA-BD (1-channel analog Output)                                                 4.4 Output Holding Function Cancellation Setting
                                                                                                                                           A
4.4      Output Holding Function Cancellation Setting
                                                                                                                                               Common Items
         This setting can hold the analog data output or to output the offset data (0V for voltage output mode, 4mA for
         current output mode) when the PLC stops.
         To cancel or set the output holding function, use the following special auxiliary relays:
           Special auxiliary relay
                                                                                                                                           B
                                                                     Description
                                                                                                                                         FX3UC-4AD
                                                                                                                                         FX3U-4AD
           1st board      2nd board
                                                                               OFF: Holds the analog data output
                                        Cancel output holding function              just before stop of the PLC.
            M8264          M8274
                                        setting.                               ON : Outputs the offset data at
                                                                                    stop of the PLC.
                                                                                                                                           C
                                                                                                                                               FX3U-4AD-ADP
      1. Program Example
         To set or cancel the output holding function, create a sequence program as follows:
                                                                                                                                               FX3G-2AD-BD
           M8001
                                            M8264
           Normally OFF
                                                                                                                                               FX3U-4DA
                                                                                      Numeric data type: Decimal (K)
         The 1DA-BD performs D/A conversion on the output setting data (digital data) into analog data, and outputs
         the analog data.
         Use the special data registers shown in the following table for the output setting data:
           Special data register                                                                                                             F
                                                                Description
                                                                                                                                               FX3U-4DA-ADP
          1st board 2nd board
            D8260         D8270       Output setting data
      1. Program Example
                                                                                                                                          G
                                                                                                                                               FX3G-1DA-BD
           M8000                                                         Performs D/A conversion using the digital
                                       FNC 12     D100      D8260        data stored in the D100 for the 1st analog
          Normally ON
                                        MOV                              board.
         Using the indicator or the sequence program, input the digital data to be subject to D/A conversion (to be
         output as analog data) in D100 and D101.
                                                                                                                                                  -ADP
                                                                                                                                                   I
                                                                                                                                         FX3U-4AD-PTW
                                                                                                                                                  -ADP
                                                                                                                                             J
                                                                                                                                         FX3U-4AD-PNK
                                                                                                                                                  -ADP
                                                                                                                             G-15
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                        4 Programming
FX3G-1DA-BD (1-channel analog Output)                                                                             4.6 Error Status
       1. Description of setting
         If an error is detected on 1DA-BD, the error status data will be stored in the corresponding special data
         register.
         The following table shows the special data registers that store the error status data:
         Check the ON/OFF status of each bit of the error status data register to check the description of the error.
         Errors are assigned to the bits as shown in the following table. Create a program to detect errors.
                         Bit                                                     Description
                         b0                    Output data setting error
                     b1 to b3                  Unused
                         b4                    EEPROM error
                     b5 to b15                 Unused
2. Program Example
              M8000                        FNC 12
                                                        D8268     K4M0
                                            MOV
              Normally
              ON
                M0
                                                                   Y000        Output data setting error on
                                                                               1st board.
                M4
                                                                   Y004         EEPROM error on the 1st board.
                                                                                                               Initial value: K4
                                                                                                Numeric data type: Decimal (K)
       1. Description of setting
         When the 1DA-BD is connected, model code "4" is stored in the corresponding special data register.
         The following table shows the special data registers that store the model code:
          1st board 2nd board                                    Description
            D8269        D8279         Model code
Use the special data registers above to check whether 1DA-BD is connected or not.
       2. Program Example
                                                                               Checks the model code
                FNC 224        D8269      K4                       Y007        of the 1st analog board.
                 LD =
G-16
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                       4 Programming
FX3G-1DA-BD (1-channel analog Output)                                                              4.8 Basic Program Example
                                                                                                                                   A
4.8      Basic Program Example
                                                                                                                                       Common Items
         Create the following basic program example to output D/A converted analog data.
         The following program will set the 1st board to the voltage output mode and 2nd board to current output
         mode, and will set digital data in D100 and D101 for D/A conversion.
               M8001
                                                                                                                                   B
                                                          Sets the output mode of the 1st board to the voltage
                                                                                                                                 FX3UC-4AD
                                                                                                                                 FX3U-4AD
                                                M8260
                                                          output mode (0 V to 10 V).
              Normally
              OFF
                                                M8264     Sets the output holding function for the 1st board.
M8000
              Normally
                                                M8270     Sets the output mode of the 2nd board to the current
                                                          output mode (4 mA to 20 mA).                                             C
                                                                                                                                       FX3U-4AD-ADP
              ON
                                                M8274     Cancels the output holding function for the 2nd board.
               M8000
                             FNC 12    D100    D8260      Performs D/A conversion with the digital data stored
                              MOV                         in D100 for the 1st board.
                             FNC 12    D101    D8270     Performs D/A conversion with the digital data stored
                                                                                                                                   D
                                                         in D101 for the 2nd board.
                                                                                                                                       FX3G-2AD-BD
                              MOV
         Using the indicator or the sequence program, input the digital data to be subject to D/A conversion (to be
         output as analog data) in D100 and D101.
                                                                                                                                       FX3U-4DA
                                                                                                                                     F
                                                                                                                                       FX3U-4DA-ADP
                                                                                                                                  G
FX3G-1DA-BD
                                                                                                                                   H
                                                                                                                                 FX3U-4AD-PT
                                                                                                                                          -ADP
                                                                                                                                           I
                                                                                                                                 FX3U-4AD-PTW
                                                                                                                                          -ADP
                                                                                                                                     J
                                                                                                                                 FX3U-4AD-PNK
                                                                                                                                          -ADP
                                                                                                                       G-17
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                        5 Changing of Output Characteristics
FX3G-1DA-BD (1-channel analog Output)                                                                          5.1 Example: Changing of Voltage Output Characteristics
1. Output characteristics
                                                                                 value to be actually
                         10V
                 Analog output
Y-axis
                                 5V                                                                          2000
                                                                                                             (5V)
                                 1V                                                                           400
                                                                                                              (1V)
                                  0 400       2000             4000                                                                                  X-axis
                                                                                                                 0                           10000
                                                Digital value input
                                                                                                                     Desired digital value (D100)
       2. Example of program
         For example, create the following program to change the digital output data (D100) of the 1st analog board.
            M8001
                                                                                                             M8260         Sets the output mode of 1st board
           Normally                                                                                                        to the voltage output mode (0V to 10V).
           OFF
                                                            FNC 23
                                                                         D101   K10000                        D103
                                                             DDIV                                                             Calculation for changing output
                                                                                                                              characteristics.
                                                            FNC 20                                                            Stores the operation result in D8260.
                                                                         D103   K400                          D107
                                                             ADD
G-18
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                               6 Troubleshooting
FX3G-1DA-BD (1-channel analog Output)                                                         6.1 PLC Version Number Check
                                                                                                                                   Common Items
6.      Troubleshooting
         This chapter describes the troubleshooting methods and error status.                                                  B
         If analog data is not output, or if the proper analog value is not output, check the following items:
                                                                                                                             FX3UC-4AD
                                                                                                                             FX3U-4AD
         • Version number of PLC
         • Installation
         • Wiring
         • Special devices                                                                                                     C
         • Programs
                                                                                                                                   FX3U-4AD-ADP
         • Error status
                                                                                                                                   FX3G-2AD-BD
                       → For a detailed description of the version number check method, refer to Section 1.3.
                                                                                                                                   FX3U-4DA
           of the 1DA-BD is lit correctly.
                      → For a detailed description of installing, refer to FX3G User’s Manual-Hardware Edition.
                                                                                                                                   FX3U-4DA-ADP
      1. Analog output line
         Use the 2-core twisted shielded pair cable for the analog output line. In addition, be sure to separate the
         analog output line from other power lines or inductive lines.
                                                         → For a detailed description of wiring, refer to Chapter 3.
                                                                                                                              G
                                                                                                                                   FX3G-1DA-BD
6.4      Special Device Check
         Check whether the special devices for the 1DA-BD are being used correctly:
         Turn off the device to set the output mode to the voltage output mode. Turn on the device to set the output
         mode to the current output mode.
                                                                                                                                      -ADP
      3. Error status
         Check that no error is detected in the 1DA-BD.
         If an error is detected, check the details of the error, and then check the wiring and programs.
                                                                                                                                      -ADP
                                                                                                                  G-19
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                      6 Troubleshooting
FX3G-1DA-BD (1-channel analog Output)                                                           6.5 Program Check
                       Bit                                                Description
                       b0                Output data setting error
                    b1 to b3             Unused
                       b4                EEPROM error
                    b5 to b15            Unused
         To solve the problem, refer to the troubleshooting method described below:
G-20
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input)
                                                                                                                                         Common Items
                                                                                                                                     B
                                                                                                                                   FX3UC-4AD
                                                                                                                                   FX3U-4AD
          FX3G/FX3U/FX3UC Series Programmable
          Controllers                                                                                                                C
                                                                                                                                         FX3U-4AD-ADP
          User's Manual [Analog Control Edition]
          FX3U-4AD-PT-ADP
                                                                                                                                     D
          (4-channel Platinum Resistance Thermometer Data Input)
                                                                                                                                         FX3G-2AD-BD
                                                                                                                                      E
                                                                                                                                         FX3U-4DA
                                                                                                                                       F
                                                                                                                                         FX3U-4DA-ADP
                                                                                                                                    G
FX3G-1DA-BD
                                                                                                                                     H
                                                                                                                                   FX3U-4AD-PT
          Foreword
                                                                                                                                            -ADP
          This manual describes the specifications, wiring, and operation methods for the FX3U-4AD-PT-ADP special
          adapter (4-channel platinum resistance thermometer input) and should be read and understood before                                 I
          attempting to install or use the unit.
                                                                                                                                   FX3U-4AD-PTW
          Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
          it to the end user.
                                                                                                                                            -ADP
             This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
             licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
             rights which may occur as a result of using the contents noted in this manual.
                                                                                                                                       J
                                                                                                                                   FX3U-4AD-PNK
                                                                                                                           H-1
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input)
H-2
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                    1 Outline
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input)                                            1.1 Outline of Functions
                                                                                                                                                   Common Items
1.        Outline
            This chapter describes the outline of FX3U-4AD-PT-ADP (referred to as PT-ADP).                                                     B
                                                                                                                                             FX3UC-4AD
                                                                                                                                             FX3U-4AD
1.1         Outline of Functions
            The FX3U-4AD-PT-ADP is an analog special adapter. Connect the FX3U-4AD-PT-ADP to the FX3U/FX3UC/
            FX3G Series PLC to read the temperature data from the 4-channel platinum resistance thermometers.
                                                                                                                                               C
            1) Up to 4 PT-ADP units can be connected to the FX3U/FX3UC Series PLC.
                                                                                                                                                   FX3U-4AD-ADP
               Up to 2*1 PT-ADP units can be connected to the FX3G Series PLC.
               (including other analog special adapters)
            2) After connection of the platinum resistance thermometer (Pt100), measurement of temperature will be
               possible.
            3) The temperature measurement data will be automatically written to the special data registers of the FX3U/                       D
               FX3UC/FX3G Series PLC.
                                                                                                                                                   FX3G-2AD-BD
                                                     System                                                  Point and section to be
                                                                                                                   referred to
                                                                                                                                                   FX3U-4DA
                                                                                                            To check the connectable
                                                                                                       …… PLC model number, refer
+ + to Section 1.3.
                                                                                                                                                   FX3U-4DA-ADP
                                                       Expansion
              4th       3rd        2nd       1st
            adapter   adapter    adapter   adapter      board*2
                                                                                                             For a detailed
                                                                                                       …… description of wiring,
                         Analog data                                                                         refer to Chapter 3.
                                                                                                                                                   FX3G-1DA-BD
                                                                              For FX3U, FX3UC
                                                                              Series PLC                    For a detailed description
           Description
          Measurement
                                                                                Special devices
                                                                   1st adapter M/D8260 to M/D8269
                                                                                                       …… of special devices, refer to
                                                                                                            Chapter 4.                         H
          temperature                      Transfer direction
                                                                                                                                             FX3U-4AD-PT
     Refer to the system configuration shown in the User's Manual - Hardware Edition to check the number of connectable units
     and to configure the entire system.                                                                                                               I
                                                                                                                                             FX3U-4AD-PTW
     *1. Only 1 analog special adapter can be connected to the 14-point and 24-point type main unit.
     *2. The expansion board is not required when connecting with the FX3UC (D, DSS) PLC.
                                                                                                                                                      -ADP
                                                                                                                                                 J
                                                                                                                                             FX3U-4AD-PNK
                                                                                                                                                      -ADP
                                                                                                                                   H-3
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                     1 Outline
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input)       1.2 Setup Procedure Before Starting Operation
FX3U-4AD-PT-ADP
Refer to Chapter 1.
H-4
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                                  1 Outline
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input)                                      1.3 Connectable PLC and Its Version Number
                                                                                                                                                           A
1.3       Connectable PLC and Its Version Number
                                                                                                                                                               Common Items
          PT-ADP is compatible with the following PLC.
                                                                                                                                                         FX3UC-4AD
                                                                                                                                                         FX3U-4AD
           FX3UC Series PLC                                 Ver. 1.30 or later                               After August 2004
           FX3G Series PLC                                  Ver. 1.00 or later                       After June 2008 (initial production)
       1. Version check
          Special data register D8001 contains information for determining the PLC version.
                                                                                                                                                           C
                                                                                                                                                               FX3U-4AD-ADP
                            D8001               2     4       1        0         0
                         PLC type and
                        version number                                       Version data (Example: Ver. 1.00)
                                                       PLC type Example: 24 = FX3U and FX3UC series
                                                                       (                                                 )                                 D
                                                                         26 = FX3G series
                                                                                                                                                               FX3G-2AD-BD
       2. How to look at the manufacturer's serial number
          The year and month of production of the product can be seen from the manufacturer's serial number
          "SERIAL" indicated on the label adhered to the right side of the product.
                                                     Example:
                                                                                                                                                            E
                                                                                                                                                               FX3U-4DA
                                                     FX3U-48MR/ES(production number : 570001)
                                                       MODEL               FX3U-48MR/ES
                                                                 100-240VAC 50/60Hz 40W
                                                           OUT:30VDC/240VAC 2A(COSφ=1)                                                                       F
                                                       SERIAL                        570001
                                                                                                                                                               FX3U-4DA-ADP
                                                                             80M1 IND. CONT. EQ.
                                                          MITSUBISHI ELECTRIC CORPORATION
                                                       MADE IN JAPAN
                                                                   5         7       0      0    0      1
                                                                                                                                                          G
                                                                                                                                                               FX3G-1DA-BD
                                                                                             Control number
                                                                                Month (Example: 7 = July), 1 to 9 = January to September,
                                                                                X = October, Y = November, Z = December
                                                                           Year (Example: 5 = 2005), last digit of dominical year
          Use the programming tool with the following version number to create programs for PT-ADP of the FX3U/
          FX3UC/FX3G Series PLC:
                                                                                                                                                                  -ADP
          If a programming tool with the wrong version number is used, programming will not be possible.
            *1.   For Ver. 8.13P to 8.24A of GX Developer, select FX3UC for the PLC type.
                                                                                                                                                             J
                                                                                                                                                         FX3U-4AD-PNK
                                                                                                                                                                  -ADP
                                                                                                                                               H-5
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                           2 Specifications
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input)                                        2.1 Generic Specifications
2.      Specifications
          This chapter describes the general, power supply, and performance specifications for the PT-ADP.
                  Item                                                       Specifications
           Ambient             0 to 55°C (32 to 131°F) when operating
           temperature         -25 to 75°C (-13 to 167°F) when stored
           Relative
                               5 to 95%RH (no condensation) when operating
           humidity
                                                      Frequency            Acceleration      Half amplitude
                                                         (Hz)                 (m/s2)              (mm)
                                                                                                              Tested 10 times in each
           Vibration                                       10 - 57              -                0.035        direction (X-, Y-, and Z-
                               DIN Rail Mounting
           resistance                                  57 - 150                4.9                    -       axis directions) (Total:
                                                                                                              80 min, each)
                                                       10 to 57                 −                0.075
                               Direct Mounting*1
                                                       57 to 150               9.8                    −
           Shock
                               147 m/s2 Acceleration, Action time: 11ms, 3 times by half-sine pulse in each direction X, Y, and Z
           resistance
           Noise               Using noise simulator of:
           resistance          Noise voltage: 1,000Vp-p / Noise width: 1µs / Rise: 1ns / Cycle: 30 to 100Hz
           Dielectric
           withstand           500 V AC, for 1 min
           voltage                                                    Between all terminals and ground terminal
           Insulation          5MΩ or more using 500V DC
           resistance          insulation resistance meter
                               Class D grounding (grounding resistance: 100 Ω or less)
           Grounding
                               <Common grounding with a heavy electrical system is not allowed.>*2
           Working
                               Free from corrosive or flammable gas and excessive conductive dusts
           environment
           Working
                               < 2000m*3
           altitude
*1. If PT-ADP is connected to the FX3UC Series PLC, direct installation is not possible.
            *2.
                         PLC        Other            PLC         Other          PLC         Other
                                  equipment                    equipment                  equipment
H-6
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                     2 Specifications
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input)                                               2.2 Power Supply Specifications
                                                                                                                                                         A
2.2       Power Supply Specifications
                                                                                                                                                             Common Items
                        Items                                                           Specification
           A/D conversion circuit          24V DC +20% -15%, 50mA                                                                                        B
           driving power                   (It is necessary to connect a 24V DC power supply to the terminal block.)
                                                                                                                                                       FX3UC-4AD
                                                                                                                                                       FX3U-4AD
                                           5V DC, 15mA
           Interface driving power         (Since the internal power is supplied from the FX Series main unit, it is not
                                           necessary to supply the power.)
                                                                                                                                                             FX3U-4AD-ADP
                                                                               Specifications
                  Items
                                                     Centigrade (°C)                                         Fahrenheit (°F)
           Input signal
                                                                3-wire platinum resistance thermometer sensor
                                                                             Pt100 JIS C 1604-1997
                                                                                                                                                         D
                                                                                                                                                             FX3G-2AD-BD
           Rated temperature
                                                     -50°C to +250°C                                         -58°F to +482°F
           range
           Digital output                                -500 to +2500                                        -580 to +4820
           Resolution                                          0.1°C                                                0.18°F
           Total accuracy
                                           • ±0.5% for full scale (when ambient temperature is 25°C±5°C)                                                  E
                                           • ±1.0% for full scale (when ambient temperature is in the range from 0 to 55°C)
                                                                                                                                                             FX3U-4DA
                                • FX3U/FX3UC Series PLC : 200µs (The data will be updated at every scan time.)
           A/D conversion
                                • FX3G Series PLC : 250µs (The data will be updated at every scan time.)
           time
                                                     →For a detailed description of data update, refer to Section 2.4.
                                                   +2550                                                   +4910
                                                                                                                                                           F
                                                                                                                                                             FX3U-4DA-ADP
                                                   +2500                                                   +4820
                                                                               +255°C
                                                                                                                                        +491°F
           Input
           characteristics
                                                 -50°C     0                                              -58°F 0
                                                                         +250°C                                                 +482°F                  G
                                         -55°C
-67°F
                                                                                                                                                             FX3G-1DA-BD
                                                               -500                                                 -580
                                                               -550                                                 -670
                                • The photocoupler is used to insulate the analog input area from the PLC.
                                • The DC/DC converter is used to insulate the power supply line from the analog input
           Insulation method
                                  area.                                                                                                                  H
                                • Channels are not insulated from each other.
                                                                                                                                                       FX3U-4AD-PT
                                                                                                                                                                 I
                                                                                                                                                       FX3U-4AD-PTW
                                                                                                                                                                -ADP
                                                                                                                                                           J
                                                                                                                                                       FX3U-4AD-PNK
                                                                                                                                                                -ADP
                                                                                                                                                 H-7
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                        2 Specifications
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input)                                       2.4 A/D Conversion Time
                                                                                              Sequence
                                                                                               program
                                                               A/D conversion start
                                                     A/D            command
                                                  conversion
                                                                Digital value writing
                                                  200µs/4ch
                                                               A/D conversion start        END instruction
                          A/D                                       command
                       conversion
                                                                Digital value writing
                        200µs/4ch
H-8
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                   2 Specifications
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input)                               2.5 Temperature Measurement
                                                                                                                                     A
2.4.2     When connected to a FX3G PLC
                                                                                                                                         Common Items
        1. A/D conversion and special data register update timing
          A/D conversion is performed at every scan time of the PLC.
          During execution of END instruction, the PLC performs A/D conversion, reads out the A/D converted data,
          and then writes the data in the special data registers.                                                                    B
                                                                                                                                   FX3UC-4AD
                                                                                                                                   FX3U-4AD
                   FX3U-4AD-PT-ADP           FX3U-4AD-PT-ADP
                          2nd                       1st                                FX3G Series PLC
Sequence
                                                                                                                                         FX3U-4AD-ADP
                                                    A/D             command
                                                 conversion
                                                               Digital value writing
                                                  250µs/4ch
                                                               A/D conversion start    END instruction
                          A/D
                       conversion
                                                                    command
                                                                                                                                     D
                                                                                                                                         FX3G-2AD-BD
                                                               Digital value writing
                       250µs/4ch
                                                                                                                                         FX3U-4DA
        3. If two analog special adapters are connected
          During execution of the END instruction, data will be read out from all the connected adapters (in the order of
          1st adapter → 2nd adapter).
                                                                                                                                         FX3U-4DA-ADP
          and the data read out will be written to the special data registers.
          END instruction execution time will be "250µs × number of connected adapters."
FX3G-1DA-BD
                                                                                                                                     H
                                                                                                                                   FX3U-4AD-PT
                                                                                                                                            -ADP
                                                                                                                                             I
                                                                                                                                   FX3U-4AD-PTW
                                                                                                                                            -ADP
                                                                                                                                       J
                                                                                                                                   FX3U-4AD-PNK
                                                                                                                                            -ADP
                                                                                                                         H-9
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                               3 Wiring
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input)
3.      Wiring
          This chapter describes the PT-ADP wiring.
          Observe the following caution to wire the PT-ADP.
WIRING PRECAUTIONS
           • Make sure to cut off all phases of the power supply externally before attempting wiring work.
             Failure to do so may cause electric shock or damages to the product.
WIRING PRECAUTIONS
           • Connect the DC power supply wiring to the dedicated terminals described in this manual.
             If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will be
             burnt out.
           • Do not wire vacant terminals externally.
             Doing so may damage the product.
           • Perform class D grounding (grounding resistance: 100Ω or less) to the grounding terminal on the main unit.
             Do not use common grounding with heavy electrical systems.
           • When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
             Failure to do so may cause fire, equipment failures or malfunctions.
           • Make sure to observe the following precautions in order to prevent malfunctions under the influence of noise:
             - Do not bundle the power line or twisted shielded cable together with or lay it close to the main circuit, high-
                 voltage line, or load line.
                 Otherwise, noise disturbance and/or surge induction are likely to take place. As a guideline, lay the control line
                 at least 100mm (3.94") or more away from the main circuit, high-voltage line, or load line.
             - Ground the shield of the analog input/output cable at one point on the signal receiving side.
                 However, do not use common grounding with heavy electrical systems.
           • Make sure to properly wire to the European terminal board in accordance with the following precautions.
             Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product.
             - The disposal size of the cable end should be 9 mm (0.35").
             - Tightening torque should be between 0.22 to 0.25 N•m.
             - Twist the end of strand wire and make sure there are no loose wires.
             - Do not solder-plate the electric wire ends.
             - Do not connect more than the specified number of wires or electric wires of unspecified size.
             - Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
H-10
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                3 Wiring
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input)                            3.1 Terminal Layout
                                                                                                                          A
3.1       Terminal Layout
                                                                                                                              Common Items
          The terminals of the PT-ADP are arranged as follows:
                                                                                                                        FX3UC-4AD
                                                                                                                        FX3U-4AD
                                   FX3U-4AD-PT
                                          -ADP
                                        POWER
                                                              Signal           Application                                C
                                                               24+
                             24+
                                                                                                                              FX3U-4AD-ADP
                                                                         External power
                                                               24-
                             24-
                                                                         Ground terminal
                                                               L1+
                             L1+
                                                                         Channel-1 platinum
                                                                         resistance thermometer
                             L1-
                                                               L1-
                                                                         sensor input
                             I1-
                                                               I1-
                                                                                                                          D
                             L2+
resistance thermometer
                                                                                                                              FX3G-2AD-BD
                                                               L2-
                                                                         sensor input
                             I2-
                                                               I2-
                             L3+
                                                                                                                              FX3U-4DA
                                                                         sensor input
                                                               I4-
                             I4-
                                                                                                                              FX3U-4DA-ADP
                                                                                                                         G
FX3G-1DA-BD
                                                                                                                          H
                                                                                                                        FX3U-4AD-PT
                                                                                                                                 -ADP
                                                                                                                                  I
                                                                                                                        FX3U-4AD-PTW
                                                                                                                                 -ADP
                                                                                                                            J
                                                                                                                        FX3U-4AD-PNK
                                                                                                                                 -ADP
                                                                                                            H-11
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                  3 Wiring
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input)         3.2 Applicable Cable and Terminal Tightening Torque
       1. Cables
          Applicable cable and tightening torque
                                Wire size             Tightening
                                                                                             Termination
                          (stranded/single-wire)        torque
                         0.3mm2 to 0.5mm2                          • To connect a stranded cable, peel the cover off the cable
           Single-wire                                               and then twist the core before connection.
                         (AWG22 to 20)
                                                                   • To connect a single-wire cable, just strip the cover off the
           2-wire        0.3mm2 (AWG22)                              cable before connection.
                                                      0.22 N•m to • Rod terminal with insulation sleeve
           Rod           0.3mm2 to 0.5mm2              0.25 N•m     (recommended terminal)
           terminal      (AWG22 to 20)                              AI 0.5-8WH : Manufactured by Phoenix Contact
           with          (Refer to the rod terminal
                                                                  • Caulking tool
           insulation    external view shown in
                                                                    CRIMPFOX ZA 3 : Manufactured by Phoenix Contact
           sleeve        the following figure.)
                                                                    (or CRIMPFOX UD 6 : Manufactured by Phoenix Contact)
       3. Tool
          • To tighten terminals, use a small-sized screwdriver whose head is straight and is not widened as shown in
            the figure to the right.
             Note:
             If the diameter of screwdriver grip is too small, tightening torque will not
                                                                                                                         The head
             be able to be achieved. Use the following recommended screwdriver or                                        should be
             an appropriate replacement (grip diameter: approximately 25mm).                                             straight.
                         Manufacturer                              Type
              Phoenix Contact                                SZS 0.4 × 2.5                      0.4mm                  2.5mm
                                                                                                (0.01")                (0.09")
H-12
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                  3 Wiring
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input)                                           3.3 Power Supply Line
                                                                                                                                           A
3.3       Power Supply Line
                                                                                                                                               Common Items
          Connect the 24V DC power supply line of the PT-ADP to the 24+ and 24- terminals of the terminal block.
                                                                                                                                         FX3UC-4AD
                                                                                                                                         FX3U-4AD
          1. To use an external power                                         2. To use the 24V DC power of the PLC
                                                                                                                                               FX3U-4AD-ADP
                 24- 24+                                                             24- 24+            0V 24V                             D
                                                                                                                                               FX3G-2AD-BD
          Terminal                                                             Terminal
          block                                                                block
                                             Class-D                                                     Class-D
                        24V DC              grounding                                                   grounding
                                                                                                                                            E
          Caution regarding connection of the power supply line:
                                                                                                                                               FX3U-4DA
          •    Ground the "    " terminal to a class-D grounding power supply line (100Ω or less) together with the
              ground terminal of the PLC main unit.
          • For the timing of power-on/off when using an external power supply, see the following manual of the PLC
            to be connected.
                                                    → Refer to the FX3G Series User's Manual - Hardware Edition.                             F
                                                    → Refer to the FX3U Series User's Manual - Hardware Edition.
                                                                                                                                               FX3U-4DA-ADP
3.3.2     To Connect To The FX3UC Series PLC
                                                                                                                                               FX3G-1DA-BD
                                             +5V                                    (Input extension
                                                                                         block)
                                                                                             Power
                                                                                                                                           H
                                                                                    Power crossover
                                                                                                                                         FX3U-4AD-PT
                                                                  Power
                                                                 connector        connector connector
                                                                              Class-D
                                                        24V DC               grounding
                                                                                                                                                  -ADP
          • Ground the "    " terminal to a class-D grounding power supply line (100Ω or less) together with the
            grounding terminal of the PLC main unit.
                                                                                                                                                  -ADP
                                                                                                                             H-13
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                  3 Wiring
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input)     3.4 Selection of the Platinum Resistance Thermometer Sensor
                                                                               PT-ADP
                                                                             +5V
Shield +5V
+5V
                                                              24+
                                   24V DC
                                                              24-
                                               Class-D grounding
                         L +, L -, I -, ch :      represents the channel number.
            *1.   Separate the cable of the platinum resistance thermometer sensor from the other power cables or
                  areas easily affected by inductive noise (of the commercial power, etc.).
3.6       Grounding
          Grounding should be performed as stated below.
          • The grounding resistance should be 100Ω or less.
          • Independent grounding should be performed for best results.
            When independent grounding is not performed, perform "shared grounding" as shown in the following
            figure.
                                → For details, refer to the User’s Manual - Hardware Edition of the PLC Series.
H-14
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                   4 Programming
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input)                         4.1 Loading of A/D Conversion Data
                                                                                                                                          Common Items
4.      Programming
          This chapter describes how to create programs that can read analog data using the PT-ADP.                                   B
                                                                                                                                    FX3UC-4AD
                                                                                                                                    FX3U-4AD
4.1       Loading of A/D Conversion Data
          1) The input analog data will be converted into digital data and then stored in the special devices of the
             FX3U/FX3UC/FX3G Series PLC.
                                                                                                                                      C
          2) If data is stored in the special devices, the averaging time can be set, and the input mode can be
                                                                                                                                          FX3U-4AD-ADP
             specified.
          3) Special auxiliary relays (10 points) and special data registers (10 points) are assigned automatically
             starting from the adapter nearest to the main unit.
                                  → For a detailed description of special device assignment, refer to Section 4.2.
          • FX3U, FX3UC Series PLC                                                                                                    D
                                                                                                                                          FX3G-2AD-BD
                                     Communi-         High-speed
                                      cation          input/output
           FX3U-4AD FX3U-4AD FX3U-4AD special FX3U-4AD special
           -PT-ADP -PT-ADP -PT-ADP adapter -PT-ADP adapter                             FX3U/FX3UC Series PLC
                                                                                                                                          FX3U-4DA
                                                         A/D                 M8260 to M8269
                                                                           Special data registers:
                                                                              D8260 to D8269
                                                                                                                                          FX3U-4DA-ADP
                                                                           Special auxiliary relays:
                         A/D                                                 M8280 to M8289
                                                                           Special data registers:
                                                                              D8280 to D8289
               A/D
                                                                           Special auxiliary relays:
                                                                             M8290 to M8299                                          G
                                                                           Special data registers:
                                                                                                                                          FX3G-1DA-BD
                                                                              D8290 to D8299
             The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the
             next adapter as the 2nd analog special adapter, and so on. However, in this case, do not include the high-
             speed input/output special adapter and the communication special adapter.
                                                                                                                                      H
                                                                                                                                    FX3U-4AD-PT
                                                                                                                                             -ADP
                                                                                                                                              I
                                                                                                                                    FX3U-4AD-PTW
                                                                                                                                             -ADP
                                                                                                                                        J
                                                                                                                                    FX3U-4AD-PNK
                                                                                                                                             -ADP
                                                                                                                        H-15
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                       4 Programming
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input)                           4.1 Loading of A/D Conversion Data
                  2nd*1                1st
                                                                  Special devices
                                                               Special auxiliary relays:
                                                                 M8280 to M8289
                                       A/D                     Special data registers:
                                                                 D8280 to D8289                  Sequence
                                                                                                 Program
                                                               Special auxiliary relays:
                                                                 M8290 to M8299
                  A/D                                          Special data registers:
                                                                 D8290 to D8299
             The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the
             next adapter as the 2nd analog special adapter. However, in this case, do not include the connector
             conversion adapter and the communication special adapter.
            *1.    The second special adapter is not available in the 14-point and 24-point type main unit.
H-16
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                 4 Programming
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input)                               4.2 List of Special Devices
                                                                                                                                     A
4.2       List of Special Devices
                                                                                                                                         Common Items
          If the PT-ADP is connected, special devices will be assigned automatically as shown in the following table:
          • FX3U, FX3UC Series PLC
                                                                                                         R: Read / W: Write
             Special                  Device number
                                                                                                                                     B
                                                                                Description           Attribute    Reference
                                                                                                                                   FX3UC-4AD
                                                                                                                                   FX3U-4AD
             device         1st       2nd         3rd        4th
                                                                                                                     Section
             Special      M8260      M8270      M8280      M8290     Selects the temperature unit.       R/W
                                                                                                                       4.3
             auxiliary
              relay      M8261 to M8271 to M8281 to M8291 to
                                                             Unused (Do not use.)                          -             -
                          M8269    M8279    M8289    M8299
                                                                                                                                     C
                                                                     Channel-1 temperature
                                                                                                                                         FX3U-4AD-ADP
                          D8260      D8270      D8280      D8290                                          R
                                                                     measurement data
                                                                     Channel-2 temperature
                          D8261      D8271      D8281      D8291                                          R
                                                                     measurement data                                Section
                                                                     Channel-3 temperature                             4.4
                          D8262      D8272      D8282      D8292                                          R
                                                                     measurement data
                                                                                                                                     D
                                                                     Channel-4 temperature
                          D8263      D8273      D8283      D8293                                          R
                                                                                                                                         FX3G-2AD-BD
                                                                     measurement data
                                                                     Averaging time for channel 1
             Special      D8264      D8274      D8284      D8294                                         R/W
                                                                     (Setting range: 1 to 4095)
               data
             register                                                Averaging time for channel 2
                          D8265      D8275      D8285      D8295                                         R/W
                                                                     (Setting range: 1 to 4095)                      Section
                                                                                                                       4.5
                                                                                                                                      E
                                                                     Averaging time for channel 3
                          D8266      D8276      D8286      D8296                                         R/W
                                                                                                                                         FX3U-4DA
                                                                     (Setting range: 1 to 4095)
                                                                     Averaging time for channel 4
                          D8267      D8277      D8287      D8297                                         R/W
                                                                     (Setting range: 1 to 4095)
                                                                                                                     Section
                          D8268      D8278      D8288      D8298     Error status                        R/W
                                                                                                                       4.6
                                                                                                                     Section
                                                                                                                                       F
                          D8269      D8279      D8289      D8299     Model code = 20                      R
                                                                                                                                         FX3U-4DA-ADP
                                                                                                                       4.7
FX3G-1DA-BD
                                                                                                                                     H
                                                                                                                                   FX3U-4AD-PT
                                                                                                                                            -ADP
                                                                                                                                             I
                                                                                                                                   FX3U-4AD-PTW
                                                                                                                                            -ADP
                                                                                                                                       J
                                                                                                                                   FX3U-4AD-PNK
                                                                                                                                            -ADP
                                                                                                                      H-17
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                4 Programming
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input)                                    4.3 Selection of Temperature Unit
H-18
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                        4 Programming
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input)                                   4.4 Temperature Measurement
                                                                                                                                         A
4.4       Temperature Measurement
                                                                                                                                             Common Items
          The temperature data input in the PT-ADP will be stored in the special data registers.
          The special data registers that store the temperature data are shown in the following table:
          • FX3U, FX3UC Series PLC
                                                                                                                                         B
                        Special data register
                                                                                                                                       FX3UC-4AD
                                                                                                                                       FX3U-4AD
                                                                                        Description
               1st         2nd         3rd          4th
             D8260       D8270       D8280        D8290      Stores the channel-1 temperature measurement data.
             D8261       D8271       D8281        D8291      Stores the channel-2 temperature measurement data.
             D8262       D8272       D8282        D8292      Stores the channel-3 temperature measurement data.                          C
             D8263       D8273       D8283        D8293      Stores the channel-4 temperature measurement data.
                                                                                                                                             FX3U-4AD-ADP
          • FX3G Series PLC
                                                                                                                                             FX3G-2AD-BD
             D8280        D8290      Stores the channel-1 temperature measurement data.
             D8281        D8291      Stores the channel-2 temperature measurement data.
             D8282        D8292      Stores the channel-3 temperature measurement data.
             D8283        D8293      Stores the channel-4 temperature measurement data.
                                                                                                                                          E
                                                                                                                                             FX3U-4DA
          The immediate data or the average data (data averaged in accordance with the specified averaging time) will
          be stored in the above data registers as the temperature measurement data.
                                           → For a detailed description of the averaging time, refer to Section 4.6.
                                                                                                                                             FX3U-4DA-ADP
          Do not change (rewrite) the current data using the sequence program, indicator, or device monitor of the
          programming tool.
                                                                                                                                             FX3G-1DA-BD
            ON
          Even if the temperature measurement data is not stored in the D100 or the D101, the D8260 or the D8261
          can be directly used in the arithmetic operation instruction or a PID instruction.
                                                                                                                                         H
                                                                                                                                       FX3U-4AD-PT
                                                                                                                                                -ADP
                                                                                                                                                 I
                                                                                                                                       FX3U-4AD-PTW
                                                                                                                                                -ADP
                                                                                                                                           J
                                                                                                                                       FX3U-4AD-PNK
                                                                                                                                                -ADP
                                                                                                                            H-19
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                          4 Programming
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input)                                             4.5 Averaging Time
H-20
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                 4 Programming
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input)                                                            4.6 Error Status
                                                                                                                                                       A
4.6       Error Status
                                                                                                                                                           Common Items
          If an error is detected in the PT-ADP, the error status data will be stored in the corresponding special data
          register.
          The following table shows the special data registers that store the error status data:
          • FX3U, FX3UC Series PLC                                                                                                                     B
                                                                                                                                                     FX3UC-4AD
                                                                                                                                                     FX3U-4AD
                                     Special data register
                                                                                                        Description
                   1st                2nd             3rd                 4th
                  D8268              D8278           D8288           D8298         Stores the error status data.
                                                                                                                                                       C
          • FX3G Series PLC
                                                                                                                                                           FX3U-4AD-ADP
                  Special data register
                                                                     Description
                   1st                 2nd
                  D8288               D8298       Stores the error status data.
                                                                                                                                                       D
                                                                                                                                                           FX3G-2AD-BD
          Check the ON/OFF status of each bit of the error status data register to determine the error. Errors are
          assigned to the bits as shown in the following table. Create a program to detect errors.
                    b0
                                  The temperature measurement data
                                  of channel 1 is outside the specified              b5         Averaging time setting error
                                                                                                                                                        E
                                                                                                                                                           FX3U-4DA
                                  range, or disconnection is detected.
                                  The temperature measurement data
                    b1            of channel 2 is outside the specified              b6         PT-ADP hardware error
                                  range, or disconnection is detected.
                                  The temperature measurement data
                    b2            of channel 3 is outside the specified              b7         PT-ADP communication data error                          F
                                  range, or disconnection is detected.
                                                                                                                                                           FX3U-4DA-ADP
                                  The temperature measurement data
                    b3            of channel 4 is outside the specified           b8 to b15     Unused
                                  range, or disconnection is detected.
                    b4            EEPROM error                                        -                              -
                                                                                                                                                      G
       1. Caution regarding use of error status data
                                                                                                                                                           FX3G-1DA-BD
          If a PT-ADP hardware error (b6) or PT-ADP communication data error (b7) is detected, it is necessary to clear
          the error status with a program at the next power-on of the PLC.
          For this reason, be sure to create the following program:
          • For FX3G, FX3U, FX3UC Series PLC
                  M8000
                                                                                                                                                       H
                                                                                                                                                     FX3U-4AD-PT
                  M8002
                                                             RST          M6       Error status of 3rd*1 analog special adapter
                                                                                   b6 = OFF (hardware error)
                  Initial pulse
                                                                                                                                                               I
                                                                                                                                                     FX3U-4AD-PTW
                                                                                                                                        H-21
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                       4 Programming
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input)                                                4.6 Error Status
                  M8002
                                                     RST     D8268.6     Error status of 1st analog special adapter
                                                                         b6 = OFF (hardware error)
                  Initial pulse
                  M8000
                                        MOV        D8288      K4M0
                   M0
                                                               Y000      The temperature measurement data
                                                                         of channel 1 is outside the specified
                                                                         range, or disconnection is detected.
                   M1
                                                               Y001      The temperature measurement data
                                                                         of channel 2 is outside the specified
                                                                         range, or disconnection is detected.
                   M2
                                                               Y002      The temperature measurement data
                                                                         of channel 3 is outside the specified
                                                                         range, or disconnection is detected.
                   M3
                                                               Y003      The temperature measurement data
                                                                         of channel 4 is outside the specified
                                                                         range, or disconnection is detected.
                   M4
                                                               Y004      EEPROM error in 3rd*1 adapter
                   M5
                                                               Y005      Averaging time setting error in 3rd*1
                                                                         adapter
                   M6
                                                               Y006      PT-ADP hardware error in 3rd*1
                                                                         adapter
                   M7
                                                               Y007      PT-ADP communication data error in
                                                                         3rd*1 adapter
H-22
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                       4 Programming
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input)                                             4.6 Error Status
                                                                                                                                        A
       3. Program Example 2 (For FX3U, FX3UC Series PLC)
                                                                                                                                            Common Items
               D8268.0
                                                               Y000      The temperature measurement data
                                                                         of channel 1 is outside the specified
               D8268.1
                                                                         range, or disconnection is detected.                           B
                                                               Y001      The temperature measurement data
                                                                                                                                      FX3UC-4AD
                                                                                                                                      FX3U-4AD
                                                                         of channel 2 is outside the specified
                                                                         range, or disconnection is detected.
               D8268.2
                                                               Y002      The temperature measurement data
                                                                         of channel 3 is outside the specified
               D8268.3
                                                                         range, or disconnection is detected.                           C
                                                               Y003      The temperature measurement data
                                                                                                                                            FX3U-4AD-ADP
                                                                         of channel 4 is outside the specified
                                                                         range, or disconnection is detected.
               D8268.4
                                                               Y004      EEPROM error in 1st adapter
               D8268.5
                                                                                                                                        D
                                                                         Averaging time setting error in 1st
                                                                                                                                            FX3G-2AD-BD
                                                               Y005
                                                                         adapter
               D8268.6
                                                               Y006      PT-ADP hardware error in 1st
                                                                         adapter
               D8268.7
                                                                                                                                         E
                                                                         PT-ADP communication data error in
                                                                                                                                            FX3U-4DA
                                                               Y007
                                                                         1st adapter
                                                                                                                                            FX3U-4DA-ADP
                                                                                                                                       G
FX3G-1DA-BD
                                                                                                                                        H
                                                                                                                                      FX3U-4AD-PT
                                                                                                                                               -ADP
                                                                                                                                                I
                                                                                                                                      FX3U-4AD-PTW
                                                                                                                                               -ADP
                                                                                                                                          J
                                                                                                                                      FX3U-4AD-PNK
                                                                                                                                               -ADP
                                                                                                                         H-23
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                       4 Programming
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input)                                            4.7 Model Code
Use the special data registers above to check whether PT-ADP is connected or not.
                    FNC224     D8269      K20                      Y010       Checks the model code of the 1st
                     LD =                                                     analog special adapter.
H-24
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                         4 Programming
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input)                                       4.8 Basic Program Example
                                                                                                                                           A
4.8       Basic Program Example
                                                                                                                                               Common Items
          Create the following basic program example to read out the temperature measurement data.
          • For FX3G, FX3U, FX3UC Series PLC
          The following program will store the temperature measurement data (°C) from channels 1 and 2 of the 3rd*1
          adapter to D100 and D101, respectively. The averaging time is set to "1" (immediate data) for channel 1, and
                                                                                                                                           B
                                                                                                                                         FX3UC-4AD
                                                                                                                                         FX3U-4AD
          "5" for channel 2.
                   M8000
                                 MOV        D8288      K4M0
                   M8002
                                             RST        M6
                                                                   Error status of 3rd*1 analog special
                                                                   adapter                                                                 C
                   Initial                                         b6 = OFF (hardware error)
                                                                                                                                               FX3U-4AD-ADP
                   pulse                                           Error status of 3rd*1 analog special
                                             RST        M7
                                                                   adapter
                                                                   b7 = OFF (communication data error)
                                 MOV         K4M0      D8288
                   M8001
                                                                   Sets the temperature unit to centigrade
                                                                                                                                           D
                                                       M8280
                                                                                                                                               FX3G-2AD-BD
                                                                   (°C).
                   M8002
                                  FNC 12                           Sets the averaging time to "1" for
                                               K1      D8284       channel-1 data.
                                   MOV
                                                                                                                                               FX3U-4DA
                                  FNC 12     D8280     D100        Stores the current value of the channel-1
                                   MOV                             temperature measurement data in the D100.
          Even if the temperature measurement data is not stored in D100 or D101, data register D8280 or D8281 can                           F
          be directly used in the arithmetic operation instruction or a PID instruction.
                                                                                                                                               FX3U-4DA-ADP
            *1.   "1st" for the FX3G PLC.
          • For FX3U, FX3UC Series PLC
          The following program will store the temperature measurement data (°C) from channels 1 and 2 of the 1st
          adapter to D100 and D101, respectively. The averaging time is set to "1" (immediate data) for channel 1, and
          "5" for channel 2.                                                                                                              G
                                                                                                                                               FX3G-1DA-BD
                   M8002                                           Error status of 1st analog special
                                             RST      D8268.6      adapter
                                                                   b6 = OFF (hardware error)
                                                       M8260       (°C).
                   M8002
                                  FNC 12                           Sets the averaging time to "1" for
                                               K1      D8264
                                                                                                                                                  -ADP
                                  FNC 12
                                   MOV
                                               K5      D8265       Sets the averaging time to "5" for
                                                                   channel-2 data.                                                                 I
                                                                                                                                         FX3U-4AD-PTW
                   M8000
                                  FNC 12     D8260     D100        Stores the current value of the channel-1
                                   MOV                             temperature measurement data in the D100.
                                                                                                                                                  -ADP
          Even if the temperature measurement data is not stored in D100 or D101, data register D8260 or D8261 can
                                                                                                                                             J
                                                                                                                                         FX3U-4AD-PNK
                                                                                                                              H-25
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                              5 Troubleshooting
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input)                        5.1 PLC Version Number Check
5.      Troubleshooting
          This chapter describes the troubleshooting methods and error status.
          If the temperature measurement data is not input, or if the proper digital value is not input, check the following
          items:
          • Version number of the PLC
          • Wiring
          • Special devices
          • Programs
          • Error status
       1. Power
          The PT-ADP needs driving power. Verify that the power supply line is properly connected. Also check that the
          POWER indicator lamp of the PT-ADP is on.
       1. Temperature measurement
          Verify that the special device for the selected channel is correctly selected. This special device should be
          selected depending on the connecting position and the channel.
       2. Averaging time
          Check that the set averaging time is within the specified range. The averaging time should be set in the range
          from 1 to 4095. If the set averaging time is outside the specified range, an error occurs.
       3. Error status
          Check that no error is detected in the PT-ADP.
          If an error is detected, check the details of the error, and then check the wiring and programs.
                                                  → For a detailed description of special devices, refer to Chapter 4.
H-26
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                 5 Troubleshooting
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input)                                        5.4 Program Check
                                                                                                                                    A
5.4       Program Check
                                                                                                                                        Common Items
          Check the following items for the program:
                                                                                                                                  FX3UC-4AD
                                                                                                                                  FX3U-4AD
       2. Check of storage devices
          Verify that different values are not being stored in the same device by the other parts of the programs.
                                                                                                                                        FX3U-4AD-ADP
          If an error occurs in the PT-ADP, the corresponding bit will turn on.
                                                                                                                                        FX3G-2AD-BD
                            The temperature measurement data of
                 b1         channel 2 is outside the specified             b6       PT-ADP hardware error
                            range, or disconnection is detected.
                            The temperature measurement data of
                 b2         channel 3 is outside the specified
                            range, or disconnection is detected.
                                                                           b7       PT-ADP communication data error
                                                                                                                                     E
                                                                                                                                        FX3U-4DA
                            The temperature measurement data of
                 b3         channel 4 is outside the specified           b8 to 15   Unused
                            range, or disconnection is detected.
                 b4         EEPROM error                                    -                          -
          To solve a problem, refer to the troubleshooting method described below:                                                    F
                                                                                                                                        FX3U-4DA-ADP
       1. Temperature measurement out of specified range or disconnection of line (b0 to b3)
          1) Description of error
             The input temperature measurement value is outside the specified range.
             The temperature measurement value is not in the range between -55°C to 255°C.
             Or the line between PT-ADP and the platinum resistance thermometer sensor is disconnected.                            G
          2) Remedy
                                                                                                                                        FX3G-1DA-BD
             Check that the input temperature measurement value is within the specified range. Also check the wiring
             condition.
             is destroyed.
          2) Remedy
             Please contact the nearest Mitsubishi Electric distributor office.
                                                                                                                                           -ADP
             The averaging time set for one of the channels (channels 1 to 4) is outside the specified
             range: 1 to 4095.
          2) Remedy
                                                                                                                                           -ADP
             Check that the averaging time is correctly set for each channel.
                                                                                                                                      J
                                                                                                                                  FX3U-4AD-PNK
                                                                                                                                           -ADP
                                                                                                                       H-27
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                        5 Troubleshooting
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input)                           5.5 Error Status Check
H-28
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input)
                                                                                                                                         Common Items
                                                                                                                                     B
                                                                                                                                   FX3UC-4AD
                                                                                                                                   FX3U-4AD
          FX3G/FX3U/FX3UC Series Programmable
          Controllers                                                                                                                C
                                                                                                                                         FX3U-4AD-ADP
          User's Manual [Analog Control Edition]
          FX3U-4AD-PTW-ADP
                                                                                                                                     D
          (4-channel Platinum Resistance Thermometer Data Input)
                                                                                                                                         FX3G-2AD-BD
                                                                                                                                      E
                                                                                                                                         FX3U-4DA
                                                                                                                                       F
                                                                                                                                         FX3U-4DA-ADP
                                                                                                                                    G
FX3G-1DA-BD
                                                                                                                                     H
                                                                                                                                   FX3U-4AD-PT
          Foreword
                                                                                                                                            -ADP
          This manual describes the specifications, wiring, and operation methods for the FX3U-4AD-PTW-ADP special
          adapter (4-channel platinum resistance thermometer input) and should be read and understood before                                 I
          attempting to install or use the unit.
                                                                                                                                   FX3U-4AD-PTW
          Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
          it to the end user.
                                                                                                                                            -ADP
             This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
             licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
             rights which may occur as a result of using the contents noted in this manual.
                                                                                                                                       J
                                                                                                                                   FX3U-4AD-PNK
                                                                                                                            I-1
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input)
I-2
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                    1 Outline
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input)                                          1.1 Outline of Functions
                                                                                                                                                  Common Items
1.        Outline
            This chapter describes the outline of FX3U-4AD-PTW-ADP (referred to as PTW-ADP).                                                  B
                                                                                                                                            FX3UC-4AD
                                                                                                                                            FX3U-4AD
1.1         Outline of Functions
            The FX3U-4AD-PTW-ADP is an analog special adapter. Connect the FX3U-4AD-PTW-ADP to the FX3U/
            FX3UC/FX3G Series PLC to read the temperature data from the 4-channel platinum resistance thermometers.
                                                                                                                                              C
            1) Up to 4 PTW-ADP units can be connected to the FX3U/FX3UC Series PLC.
                                                                                                                                                  FX3U-4AD-ADP
               Up to 2*1 PTW-ADP units can be connected to the FX3G Series PLC.
               (including other analog special adapters)
            2) After connection of the platinum resistance thermometer (Pt100), measurement of temperature will be
               possible.
            3) The temperature measurement data will be automatically written to the special data registers of the FX3U/                      D
               FX3UC/FX3G Series PLC.
                                                                                                                                                  FX3G-2AD-BD
                                                     System                                                  Point and section to be
                                                                                                                   referred to
                                                                                                                                                  FX3U-4DA
                                                                                                            To check the connectable
                                                                                                       …… PLC model number, refer
+ + to Section 1.3.
                                                                                                                                                  FX3U-4DA-ADP
                                                       Expansion
               4th       3rd       2nd       1st
             adapter   adapter   adapter   adapter      board*2
                                                                                                             For a detailed
                                                                                                       …… description of wiring,
                         Analog data                                                                         refer to Chapter 3.
                                                                                                                                                  FX3G-1DA-BD
                                                                              For FX3U, FX3UC
                                                                              Series PLC                    For a detailed description
                                                                                                       …… of special devices, refer to
                                                                                                                                              H
           Description                                                          Special devices             Chapter 4.
          Measurement                                              1st adapter M/D8260 to M/D8269
          temperature                      Transfer direction
                                                                                                            For a detailed description
                                                                                                                                            FX3U-4AD-PT
     Refer to the system configuration shown in the User's Manual - Hardware Edition to check the number of connectable units
     and to configure the entire system.                                                                                                              I
                                                                                                                                            FX3U-4AD-PTW
     *1. Only 1 analog special adapter can be connected to the 14-point and 24-point type main unit.
     *2. The expansion board is not required when connecting with the FX3UC (D, DSS) PLC.
         For the FX3G Series PLC a connector conversion adapter is used.
                                                                                                                                                     -ADP
                                                                                                                                                J
                                                                                                                                            FX3U-4AD-PNK
                                                                                                                                                     -ADP
                                                                                                                                   I-3
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                     1 Outline
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input)      1.2 Setup Procedure Before Starting Operation
FX3U-4AD-PTW-ADP
Refer to Chapter 1.
I-4
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                              1 Outline
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input)                                  1.3 Connectable PLC and Its Version Number
                                                                                                                                                        A
1.3       Connectable PLC and Its Version Number
                                                                                                                                                            Common Items
          PTW-ADP is compatible with the following PLC.
                                                                                                                                                      FX3UC-4AD
                                                                                                                                                      FX3U-4AD
           FX3UC Series PLC                                   Ver. 1.30 or later                          After August 2004
           FX3G Series PLC                                    Ver. 1.00 or later               After June 2008 (initial production)
       1. Version check
          Special data register D8001 contains information for determining the PLC version.
                                                                                                                                                        C
                                                                                                                                                            FX3U-4AD-ADP
                             D8001                2       4       1      0       0
                           PLC type and
                          version number                                        Version data (Example: Ver. 1.00)
                                                                        (
                                                           PLC type Example: 24 = FX3U and FX3UC series
                                                                                                                       )                                D
                                                                             26 = FX3G series
                                                                                                                                                            FX3G-2AD-BD
       2. How to look at the manufacturer's serial number
          The year and month of production of the product can be seen from the manufacturer's serial number
          "SERIAL" indicated on the label adhered to the right side of the product.
                                                      Example:
                                                                                                                                                         E
                                                                                                                                                            FX3U-4DA
                                                      FX3U-48MR/ES(production number : 570001)
                                                        MODEL           FX3U-48MR/ES
                                                                  100-240VAC 50/60Hz 40W
                                                            OUT:30VDC/240VAC 2A(COSφ=1)                                                                   F
                                                        SERIAL                     570001
                                                                                                                                                            FX3U-4DA-ADP
                                                                             80M1 IND. CONT. EQ.
                                                          MITSUBISHI ELECTRIC CORPORATION
                                                        MADE IN JAPAN
                                                                    5       7     0      0    0      1
                                                                                                                                                       G
                                                                                                                                                            FX3G-1DA-BD
                                                                                          Control number
                                                                             Month (Example: 7 = July), 1 to 9 = January to September,
                                                                             X = October, Y = November, Z = December
                                                                        Year (Example: 5 = 2005), last digit of dominical year
          Use the programming tool with the following version number to create programs for PTW-ADP of the FX3U/
          FX3UC/FX3G Series PLC:
                                                                                                                                                               -ADP
          If a programming tool with the wrong version number is used, programming will not be possible.
            *1.   For Ver. 8.13P to 8.24A of GX Developer, select FX3UC for the PLC type.
                                                                                                                                                          J
                                                                                                                                                      FX3U-4AD-PNK
                                                                                                                                                               -ADP
                                                                                                                                             I-5
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                           2 Specifications
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input)                                       2.1 Generic Specifications
2.      Specifications
          This chapter describes the general, power supply, and performance specifications for the PTW-ADP.
                  Item                                                       Specifications
           Ambient             0 to 55°C (32 to 131°F) when operating
           temperature         -25 to 75°C (-13 to 167°F) when stored
           Relative
                               5 to 95%RH (no condensation) when operating
           humidity
                                                      Frequency            Acceleration      Half amplitude
                                                         (Hz)                 (m/s2)              (mm)
                                                                                                              Tested 10 times in each
           Vibration                                       10 - 57              -                0.035        direction (X-, Y-, and Z-
                               DIN Rail Mounting
           resistance                                  57 - 150                4.9                    -       axis directions) (Total:
                                                                                                              80 min, each)
                                                       10 to 57                 −                0.075
                               Direct Mounting*1
                                                       57 to 150               9.8                    −
           Shock
                               147 m/s2 Acceleration, Action time: 11ms, 3 times by half-sine pulse in each direction X, Y, and Z
           resistance
           Noise               Using noise simulator of:
           resistance          Noise voltage: 1,000Vp-p / Noise width: 1µs / Rise: 1ns / Cycle: 30 to 100Hz
           Dielectric
           withstand           500 V AC, for 1 min
           voltage                                                    Between all terminals and ground terminal
           Insulation          5MΩ or more using 500V DC
           resistance          insulation resistance meter
                               Class D grounding (grounding resistance: 100 Ω or less)
           Grounding
                               <Common grounding with a heavy electrical system is not allowed.>*2
           Working
                               Free from corrosive or flammable gas and excessive conductive dusts
           environment
           Working
                               < 2000m*3
           altitude
*1. If PTW-ADP is connected to the FX3UC Series PLC, direct installation is not possible.
            *2.
                         PLC        Other            PLC         Other          PLC         Other
                                  equipment                    equipment                  equipment
I-6
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                  2 Specifications
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input)                                           2.2 Power Supply Specifications
                                                                                                                                                       A
2.2       Power Supply Specifications
                                                                                                                                                           Common Items
                        Items                                                      Specification
           A/D conversion circuit            24V DC +20% -15%, 50mA                                                                                    B
           driving power                     (It is necessary to connect a 24V DC power supply to the terminal block.)
                                                                                                                                                     FX3UC-4AD
                                                                                                                                                     FX3U-4AD
                                             5V DC, 15mA
           Interface driving power           (Since the internal power is supplied from the FX Series main unit, it is not
                                             necessary to supply the power.)
                                                                                                                                                           FX3U-4AD-ADP
                                                                           Specifications
                  Items
                                                    Centigrade (°C)                                       Fahrenheit (°F)
           Input signal
                                                           3-wire platinum resistance thermometer sensor
                                                                        Pt100 JIS C 1604-1997
                                                                                                                                                       D
                                                                                                                                                           FX3G-2AD-BD
           Rated temperature
                                                   -100°C to +600°C                                      -148°F to +1112°F
           range
           Digital output                           -1000 to +6000                                        -1480 to +11120
           Resolution                               0.2°C to 0.3°C                                         0.4°F to 0.5°F
           Total accuracy
                                             • ±0.5% for full scale (when ambient temperature is 25°C±5°C)                                              E
                                             • ±1.0% for full scale (when ambient temperature is in the range from 0 to 55°C)
                                                                                                                                                           FX3U-4DA
                                • FX3U/FX3UC Series PLC : 200µs (The data will be updated at every scan time.)
           A/D conversion
                                • FX3G Series PLC : 250µs (The data will be updated at every scan time.)
           time
                                                     →For a detailed description of data update, refer to Section 2.4.
                                                  +6150                                               +11390
                                                                                                                                                         F
                                                                                                                                                           FX3U-4DA-ADP
                                                  +6000                                               +11120
                                                                                                                                     +1139°F
                                                                          +615°C
           Input
           characteristics               -100°C       0                                               -148°F 0
                                                                                                                                                      G
                                         -115°C
                                                                     +600°C                                                  +1112°F
                                                                                             -175°F
                                                                                                                                                           FX3G-1DA-BD
                                                          -1000                                                  -1480
                                                          -1150                                                  -1750
                                • The photocoupler is used to insulate the analog input area from the PLC.
                                • The DC/DC converter is used to insulate the power supply line from the analog input
           Insulation method
                                  area.                                                                                                                H
                                • Channels are not insulated from each other.
                                                                                                                                                     FX3U-4AD-PT
                                                                                                                                                               I
                                                                                                                                                     FX3U-4AD-PTW
                                                                                                                                                              -ADP
                                                                                                                                                         J
                                                                                                                                                     FX3U-4AD-PNK
                                                                                                                                                              -ADP
                                                                                                                                               I-7
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                       2 Specifications
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input)                                     2.4 A/D Conversion Time
                                                                                             Sequence
                                                                                              program
                                                               A/D conversion start
                                                     A/D            command
                                                  conversion
                                                               Digital value writing
                                                  200µs/4ch
                                                               A/D conversion start       END instruction
                          A/D                                       command
                       conversion
                                                               Digital value writing
                       200µs/4ch
I-8
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                  2 Specifications
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input)                             2.5 Temperature Measurement
                                                                                                                                    A
2.4.2     When connected to a FX3G PLCs
                                                                                                                                        Common Items
        1. A/D conversion and special data register update timing
          A/D conversion is performed at every scan time of the PLC.
          During execution of END instruction, the PLC performs A/D conversion, reads out the A/D converted data,
          and then writes the data in the special data registers.                                                                   B
                                                                                                                                  FX3UC-4AD
                                                                                                                                  FX3U-4AD
                  FX3U-4AD-PTW-ADP          FX3U-4AD-PTW-ADP
                         2nd                       1st                                 FX3G Series PLC
Sequence
                                                                                                                                        FX3U-4AD-ADP
                                                    A/D            command
                                                 conversion
                                                               Digital value writing
                                                 250µs/4ch
                                                              A/D conversion start     END instruction
                          A/D
                       conversion
                                                                   command
                                                                                                                                    D
                                                                                                                                        FX3G-2AD-BD
                                                               Digital value writing
                       250µs/4ch
                                                                                                                                        FX3U-4DA
        3. If two analog special adapters are connected
          During execution of the END instruction, data will be read out from all the connected adapters (in the order of
          1st adapter → 2nd adapter).
                                                                                                                                        FX3U-4DA-ADP
          and the data read out will be written to the special data registers.
          END instruction execution time will be "250µs × number of connected adapters."
FX3G-1DA-BD
                                                                                                                                    H
                                                                                                                                  FX3U-4AD-PT
                                                                                                                                           -ADP
                                                                                                                                            I
                                                                                                                                  FX3U-4AD-PTW
                                                                                                                                           -ADP
                                                                                                                                      J
                                                                                                                                  FX3U-4AD-PNK
                                                                                                                                           -ADP
                                                                                                                          I-9
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                               3 Wiring
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input)
3.      Wiring
          This chapter describes the PTW-ADP wiring.
          Observe the following caution to wire the PTW-ADP.
WIRING PRECAUTIONS
           • Make sure to cut off all phases of the power supply externally before attempting wiring work.
             Failure to do so may cause electric shock or damages to the product.
WIRING PRECAUTIONS
           • Connect the DC power supply wiring to the dedicated terminals described in this manual.
             If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will be
             burnt out.
           • Do not wire vacant terminals externally.
             Doing so may damage the product.
           • Perform class D grounding (grounding resistance: 100Ω or less) to the grounding terminal on the main unit.
             Do not use common grounding with heavy electrical systems.
           • When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
             Failure to do so may cause fire, equipment failures or malfunctions.
           • Make sure to observe the following precautions in order to prevent malfunctions under the influence of noise:
             - Do not bundle the power line or twisted shielded cable together with or lay it close to the main circuit, high-
                 voltage line, or load line.
                 Otherwise, noise disturbance and/or surge induction are likely to take place. As a guideline, lay the control line
                 at least 100mm (3.94") or more away from the main circuit, high-voltage line, or load line.
             - Ground the shield of the analog input/output cable at one point on the signal receiving side.
                 However, do not use common grounding with heavy electrical systems.
           • Make sure to properly wire to the European terminal board in accordance with the following precautions.
             Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product.
             - The disposal size of the cable end should be 9 mm (0.35").
             - Tightening torque should be between 0.22 to 0.25 N•m.
             - Twist the end of strand wire and make sure there are no loose wires.
             - Do not solder-plate the electric wire ends.
             - Do not connect more than the specified number of wires or electric wires of unspecified size.
             - Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
I-10
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                 3 Wiring
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input)                            3.1 Terminal Layout
                                                                                                                           A
3.1       Terminal Layout
                                                                                                                               Common Items
          The terminals of the PTW-ADP are arranged as follows:
                                                                                                                         FX3UC-4AD
                                                                                                                         FX3U-4AD
                                  FX3U-4AD-PTW
                                          -ADP
                                       POWER
                                                             Signal             Application                                C
                                                              24+
                            24+
                                                                                                                               FX3U-4AD-ADP
                                                                          External power
                                                              24-
                            24-
                                                                          Ground terminal
                                                              L1+
                            L1+
                                                                          Channel-1 platinum
                                                                          resistance thermometer
                            L1-
                                                              L1-
                                                                          sensor input
                            I1-
                                                              I1-
                                                                                                                           D
                            L2+
resistance thermometer
                                                                                                                               FX3G-2AD-BD
                                                              L2-
                                                                          sensor input
                            I2-
                                                              I2-
                            L3+
                                                                                                                               FX3U-4DA
                                                                          sensor input
                                                              I4-
                            I4-
                                                                                                                               FX3U-4DA-ADP
                                                                                                                          G
FX3G-1DA-BD
                                                                                                                           H
                                                                                                                         FX3U-4AD-PT
                                                                                                                                  -ADP
                                                                                                                                   I
                                                                                                                         FX3U-4AD-PTW
                                                                                                                                  -ADP
                                                                                                                             J
                                                                                                                         FX3U-4AD-PNK
                                                                                                                                  -ADP
                                                                                                              I-11
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                  3 Wiring
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input)        3.2 Applicable Cable and Terminal Tightening Torque
       1. Cables
          Applicable cable and tightening torque
                                Wire size             Tightening
                                                                                             Termination
                          (stranded/single-wire)        torque
                         0.3mm2 to 0.5mm2                          • To connect a stranded cable, peel the cover off the cable
           Single-wire                                               and then twist the core before connection.
                         (AWG22 to 20)
                                                                   • To connect a single-wire cable, just strip the cover off the
           2-wire        0.3mm2 (AWG22)                              cable before connection.
                                                      0.22 N•m to • Rod terminal with insulation sleeve
           Rod           0.3mm2 to 0.5mm2              0.25 N•m     (recommended terminal)
           terminal      (AWG22 to 20)                              AI 0.5-8WH : Manufactured by Phoenix Contact
           with          (Refer to the rod terminal
                                                                  • Caulking tool
           insulation    external view shown in
                                                                    CRIMPFOX ZA 3 : Manufactured by Phoenix Contact
           sleeve        the following figure.)
                                                                    (or CRIMPFOX UD 6 : Manufactured by Phoenix Contact)
       3. Tool
          • To tighten terminals, use a small-sized screwdriver whose head is straight and is not widened as shown in
            the figure to the right.
             Note:
             If the diameter of screwdriver grip is too small, tightening torque will not
                                                                                                                         The head
             be able to be achieved. Use the following recommended screwdriver or                                        should be
             an appropriate replacement (grip diameter: approximately 25mm).                                             straight.
                         Manufacturer                              Type
              Phoenix Contact                                SZS 0.4 × 2.5                      0.4mm                  2.5mm
                                                                                                (0.01")                (0.09")
I-12
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                  3 Wiring
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input)                                          3.3 Power Supply Line
                                                                                                                                           A
3.3       Power Supply Line
                                                                                                                                               Common Items
          Connect the 24V DC power supply line of the PTW-ADP to the 24+ and 24- terminals of the terminal block.
                                                                                                                                         FX3UC-4AD
                                                                                                                                         FX3U-4AD
          1. To use an external power                                          2. To use the 24V DC power of the PLC
                                                                                                                                               FX3U-4AD-ADP
                 24- 24+                                                                 24- 24+        0V 24V                             D
                                                                                                                                               FX3G-2AD-BD
          Terminal                                                              Terminal
          block                                                                 block
                                             Class-D                                                      Class-D
                                                                                                         grounding
                       24V DC               grounding
                                                                                                                                            E
          Caution regarding connection of the power supply line:
                                                                                                                                               FX3U-4DA
          •    Ground the "    " terminal to a class-D grounding power supply line (100Ω or less) together with the
              ground terminal of the PLC main unit.
          • For the timing of power-on/off when using an external power supply, see the following manual of the PLC
            to be connected.
                                                    → Refer to the FX3G Series User's Manual - Hardware Edition.                             F
                                                    → Refer to the FX3U Series User's Manual - Hardware Edition.
                                                                                                                                               FX3U-4DA-ADP
3.3.2     To Connect To The FX3UC Series PLC
                                                                                                                                               FX3G-1DA-BD
                                             +5V                                     (Input extension
                                                                                          block)
                                                                                             Power
                                                                                                                                           H
                                                                                    Power crossover
                                                                                                                                         FX3U-4AD-PT
                                                                  Power
                                                                 connector        connector connector
                                                                              Class-D
                                                        24V DC               grounding
                                                                                                                                                  -ADP
          • Ground the "    " terminal to a class-D grounding power supply line (100Ω or less) together with the
            grounding terminal of the PLC main unit.
                                                                                                                                                  -ADP
                                                                                                                               I-13
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                             3 Wiring
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input)
                                                                     3.4 Selection of the Platinum Resistance Thermometer Sensor
                                                                           PTW-ADP
                                                                           +5V
Shield +5V
+5V
                                                             24+
                                   24V DC
                                                             24-
                                              Class-D grounding
                         L +, L -, I -, ch :      represents the channel number.
            *1.   Separate the cable of the platinum resistance thermometer sensor from the other power cables or
                  areas easily affected by inductive noise (of the commercial power, etc.).
3.6       Grounding
          Grounding should be performed as stated below.
          • The grounding resistance should be 100Ω or less.
          • Independent grounding should be performed for best results.
            When independent grounding is not performed, perform "shared grounding" as shown in the following
            figure.
                                → For details, refer to the User’s Manual - Hardware Edition of the PLC Series.
I-14
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                   4 Programming
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input)                        4.1 Loading of A/D Conversion Data
                                                                                                                                          Common Items
4.      Programming
          This chapter describes how to create programs that can read analog data using the PTW-ADP.                                  B
                                                                                                                                    FX3UC-4AD
                                                                                                                                    FX3U-4AD
4.1       Loading of A/D Conversion Data
          1) The input analog data will be converted into digital data and then stored in the special devices of the
             FX3U/FX3UC/FX3G Series PLC.
                                                                                                                                      C
          2) If data is stored in the special devices, the averaging time can be set, and the input mode can be
                                                                                                                                          FX3U-4AD-ADP
             specified.
          3) Special auxiliary relays (10 points) and special data registers (10 points) are assigned automatically
             starting from the adapter nearest to the main unit.
                                  → For a detailed description of special device assignment, refer to Section 4.2.
          • FX3U, FX3UC Series PLC                                                                                                    D
                                                                                                                                          FX3G-2AD-BD
                                      Communi          High-speed
                                       -cation         input/output
            FX3U-4AD FX3U-4AD FX3U-4AD special FX3U-4AD special
           -PTW-ADP -PTW-ADP -PTW-ADP adapter -PTW-ADP adapter                          FX3U/FX3UC Series PLC
                                                                                                                                          FX3U-4DA
                                                         A/D                  M8260 to M8269
                                                                            Special data registers:
                                                                               D8260 to D8269
                                                                                                                                          FX3U-4DA-ADP
                                                                            Special auxiliary relays:
                         A/D                                                  M8280 to M8289
                                                                            Special data registers:
                                                                               D8280 to D8289
              A/D
                                                                            Special auxiliary relays:
                                                                              M8290 to M8299                                         G
                                                                            Special data registers:
                                                                                                                                          FX3G-1DA-BD
                                                                               D8290 to D8299
             The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the
             next adapter as the 2nd analog special adapter, and so on. However, in this case, do not include the high-
             speed input/output special adapter and the communication special adapter.                                                H
                                                                                                                                    FX3U-4AD-PT
                                                                                                                                             -ADP
                                                                                                                                              I
                                                                                                                                    FX3U-4AD-PTW
                                                                                                                                             -ADP
                                                                                                                                        J
                                                                                                                                    FX3U-4AD-PNK
                                                                                                                                             -ADP
                                                                                                                         I-15
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                      4 Programming
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input)                         4.1 Loading of A/D Conversion Data
                  2nd*1               1st
                                                                 Special devices
                                                              Special auxiliary relays:
                                                                M8280 to M8289
                                      A/D                     Special data registers:
                                                                D8280 to D8289                  Sequence
                                                                                                Program
                                                              Special auxiliary relays:
                                                                M8290 to M8299
                  A/D                                         Special data registers:
                                                                D8290 to D8299
             The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the
             next adapter as the 2nd analog special adapter. However, in this case, do not include the connector
             conversion adapter and the communication special adapter.
            *1.    The second special adapter is not available in the 14-point and 24-point main unit.
I-16
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                4 Programming
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input)                             4.2 List of Special Devices
                                                                                                                                    A
4.2       List of Special Devices
                                                                                                                                        Common Items
          If the PTW-ADP is connected, special devices will be assigned automatically as shown in the following table:
          • FX3U, FX3UC Series PLC
                                                                                                        R: Read / W: Write
             Special                 Device number
                                                                                                                                    B
                                                                               Description           Attribute    Reference
                                                                                                                                  FX3UC-4AD
                                                                                                                                  FX3U-4AD
             device        1st        2nd        3rd        4th
                                                                                                                    Section
             Special      M8260     M8270      M8280      M8290     Selects the temperature unit.       R/W
                                                                                                                      4.3
             auxiliary
              relay      M8261 to M8271 to M8281 to M8291 to
                                                             Unused (Do not use.)                         -             -
                          M8269    M8279    M8289    M8299
                                                                                                                                    C
                                                                    Channel-1 temperature
                                                                                                                                        FX3U-4AD-ADP
                          D8260     D8270      D8280      D8290                                          R
                                                                    measurement data
                                                                    Channel-2 temperature
                          D8261     D8271      D8281      D8291                                          R
                                                                    measurement data                                Section
                                                                    Channel-3 temperature                             4.4
                          D8262     D8272      D8282      D8292                                          R
                                                                    measurement data
                                                                                                                                    D
                                                                    Channel-4 temperature
                          D8263     D8273      D8283      D8293                                          R
                                                                                                                                        FX3G-2AD-BD
                                                                    measurement data
                                                                    Averaging time for channel 1
             Special      D8264     D8274      D8284      D8294                                         R/W
                                                                    (Setting range: 1 to 4095)
               data
             register                                               Averaging time for channel 2
                          D8265     D8275      D8285      D8295                                         R/W
                                                                    (Setting range: 1 to 4095)                      Section
                                                                                                                      4.5
                                                                                                                                     E
                                                                    Averaging time for channel 3
                          D8266     D8276      D8286      D8296                                         R/W
                                                                                                                                        FX3U-4DA
                                                                    (Setting range: 1 to 4095)
                                                                    Averaging time for channel 4
                          D8267     D8277      D8287      D8297                                         R/W
                                                                    (Setting range: 1 to 4095)
                                                                                                                    Section
                          D8268      D8278     D8288      D8298     Error status                        R/W
                                                                                                                      4.6
                                                                                                                    Section
                                                                                                                                      F
                          D8269      D8279     D8289      D8299     Model code = 21                      R
                                                                                                                                        FX3U-4DA-ADP
                                                                                                                      4.7
FX3G-1DA-BD
                                                                                                                                    H
                                                                                                                                  FX3U-4AD-PT
                                                                                                                                           -ADP
                                                                                                                                            I
                                                                                                                                  FX3U-4AD-PTW
                                                                                                                                           -ADP
                                                                                                                                      J
                                                                                                                                  FX3U-4AD-PNK
                                                                                                                                           -ADP
                                                                                                                       I-17
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                  4 Programming
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input)                                   4.3 Selection of Temperature Unit
I-18
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                     4 Programming
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input)                               4.4 Temperature Measurement
                                                                                                                                      A
4.4       Temperature Measurement
                                                                                                                                          Common Items
          The temperature data input in the PTW-ADP will be stored in the special data registers.
          The special data registers that store the temperature data are shown in the following table:
          • FX3U, FX3UC Series PLC
                                                                                                                                      B
                        Special data register
                                                                                                                                    FX3UC-4AD
                                                                                                                                    FX3U-4AD
                                                                                     Description
               1st        2nd         3rd          4th
             D8260       D8270       D8280       D8290      Stores the channel-1 temperature measurement data.
             D8261       D8271       D8281       D8291      Stores the channel-2 temperature measurement data.
             D8262       D8272       D8282       D8292      Stores the channel-3 temperature measurement data.                        C
             D8263       D8273       D8283       D8293      Stores the channel-4 temperature measurement data.
                                                                                                                                          FX3U-4AD-ADP
          • FX3G Series PLC
                                                                                                                                          FX3G-2AD-BD
             D8281        D8291      Stores the channel-2 temperature measurement data.
             D8282        D8292      Stores the channel-3 temperature measurement data.
             D8283        D8293      Stores the channel-4 temperature measurement data.
          The immediate data or the average data (data averaged in accordance with the specified averaging time) will
                                                                                                                                       E
                                                                                                                                          FX3U-4DA
          be stored in the above data registers as the temperature measurement data.
                                           → For a detailed description of the averaging time, refer to Section 4.6.
                                                                                                                                          FX3U-4DA-ADP
       2. Program Example (For FX3U, FX3UC Series PLC)
             M8000
                                      FNC 12     D8260     D100       Stores the channel-1 temperature measurement
                                       MOV                            data of the 1st analog special adapter in D100.
            Normally
            ON
                                                                                                                                     G
                                                                                                                                          FX3G-1DA-BD
                                      FNC 12     D8261     D101       Stores the channel-2 temperature measurement
                                       MOV                            data of the 1st analog special adapter in D101.
          Even if the temperature measurement data is not stored in the D100 or the D101, the D8260 or the D8261
          can be directly used in the arithmetic operation instruction or a PID instruction.
                                                                                                                                      H
                                                                                                                                    FX3U-4AD-PT
                                                                                                                                             -ADP
                                                                                                                                              I
                                                                                                                                    FX3U-4AD-PTW
                                                                                                                                             -ADP
                                                                                                                                        J
                                                                                                                                    FX3U-4AD-PNK
                                                                                                                                             -ADP
                                                                                                                          I-19
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                       4 Programming
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input)                                         4.5 Averaging Time
I-20
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                 4 Programming
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input)                                                           4.6 Error Status
                                                                                                                                                       A
4.6       Error Status
                                                                                                                                                           Common Items
          If an error is detected in the PTW-ADP, the error status data will be stored in the corresponding special data
          register.
          The following table shows the special data registers that store the error status data:
          • FX3U, FX3UC Series PLC                                                                                                                     B
                                                                                                                                                     FX3UC-4AD
                                                                                                                                                     FX3U-4AD
                                     Special data register
                                                                                                       Description
                   1st                2nd             3rd                 4th
                  D8268              D8278           D8288           D8298         Stores the error status data.
                                                                                                                                                           FX3U-4AD-ADP
                  Special data register
                                                                     Description
                   1st                 2nd
                  D8288               D8298       Stores the error status data.
          Check the ON/OFF status of each bit of the error status data register to determine the error. Errors are
                                                                                                                                                       D
                                                                                                                                                           FX3G-2AD-BD
          assigned to the bits as shown in the following table. Create a program to detect errors.
                                                                                                                                                           FX3U-4DA
                                  The temperature measurement data
                    b1            of channel 2 is outside the specified              b6         PTW-ADP hardware error
                                  range, or disconnection is detected.
                                  The temperature measurement data
                    b2            of channel 3 is outside the specified              b7         PTW-ADP communication data error
                                  range, or disconnection is detected.                                                                                   F
                                  The temperature measurement data
                                                                                                                                                           FX3U-4DA-ADP
                    b3            of channel 4 is outside the specified           b8 to b15     Unused
                                  range, or disconnection is detected.
                    b4            EEPROM error                                        -                              -
                                                                                                                                                           FX3G-1DA-BD
          clear the error status with a program at the next power-on of the PLC.
          For this reason, be sure to create the following program:
          • For FX3G, FX3U, FX3UC Series PLC
               M8000
                                               MOV          D8288    K4M0                                                                              H
                                                                                                                                                     FX3U-4AD-PT
                  Normally
                  ON
                  M8002
                                                            RST           M6      Error status of 3rd*1 analog special adapter
                                                                                                                                                              -ADP
                                                                                                                                                         J
            *1.      "1st " for the FX3G PLC.
                                                                                                                                                     FX3U-4AD-PNK
                                                                                                                                                              -ADP
                                                                                                                                          I-21
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                       4 Programming
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input)                                                4.6 Error Status
                  M8002
                                                    RST      D8268.6      Error status of 1st analog special adapter
                                                                          b6 = OFF (hardware error)
                  Initial pulse
                   M8000
                                           MOV       D8288     K4M0
                      M0
                                                                Y000       The temperature measurement data
                                                                           of channel 1 is outside the specified
                                                                           range, or disconnection is detected.
                      M1
                                                                Y001        The temperature measurement data
                                                                            of channel 2 is outside the specified
                                                                            range, or disconnection is detected.
                      M2
                                                                Y002       The temperature measurement data
                                                                           of channel 3 is outside the specified
                                                                           range, or disconnection is detected.
                      M3
                                                                Y003       The temperature measurement data
                                                                           of channel 4 is outside the specified
                                                                           range, or disconnection is detected.
                      M4
                                                                Y004       EEPROM error in 3rd*1 adapter
                      M5
                                                                Y005       Averaging time setting error in 3rd*1
                                                                           adapter
                      M6
                                                                Y006       PTW-ADP hardware error in 3rd*1
                                                                           adapter
                      M7
                                                                Y007       PTW-ADP communication data error
                                                                           in 3rd*1 adapter
I-22
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                        4 Programming
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input)                                             4.6 Error Status
                                                                                                                                         A
       3. Program Example 2 (For FX3U, FX3UC Series PLC)
                                                                                                                                             Common Items
                D8268.0
                                                                Y000      The temperature measurement data
                                                                          of channel 1 is outside the specified
                D8268.1
                                                                          range, or disconnection is detected.                           B
                                                                                                                                       FX3UC-4AD
                                                                                                                                       FX3U-4AD
                                                                Y001      The temperature measurement data
                                                                          of channel 2 is outside the specified
                                                                          range, or disconnection is detected.
                D8268.2
                                                                Y002      The temperature measurement data
                                                                          of channel 3 is outside the specified
                D8268.3
                                                                          range, or disconnection is detected.                           C
                                                                Y003      The temperature measurement data
                                                                                                                                             FX3U-4AD-ADP
                                                                          of channel 4 is outside the specified
                                                                          range, or disconnection is detected.
                D8268.4
                                                                Y004      EEPROM error in 1st adapter
                                                                                                                                         D
                D8268.5
                                                                                                                                             FX3G-2AD-BD
                                                                Y005      Averaging time setting error in 1st
                                                                          adapter
                D8268.6
                                                                Y006      PTW-ADP hardware error in 1st
                                                                          adapter
                D8268.7
                                                                                                                                          E
                                                                                                                                             FX3U-4DA
                                                                Y007      PTW-ADP communication data error
                                                                          in 1st adapter
                                                                                                                                             FX3U-4DA-ADP
                                                                                                                                        G
FX3G-1DA-BD
                                                                                                                                         H
                                                                                                                                       FX3U-4AD-PT
                                                                                                                                                -ADP
                                                                                                                                                 I
                                                                                                                                       FX3U-4AD-PTW
                                                                                                                                                -ADP
                                                                                                                                           J
                                                                                                                                       FX3U-4AD-PNK
                                                                                                                                                -ADP
                                                                                                                            I-23
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                      4 Programming
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input)                                          4.7 Model Code
Use the special data registers above to check whether PTW-ADP is connected or not.
                    FNC224     D8269      K21                     Y010       Checks the model code of the 1st
                     LD =                                                    analog special adapter.
I-24
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                         4 Programming
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input)                                      4.8 Basic Program Example
                                                                                                                                           A
4.8       Basic Program Example
                                                                                                                                               Common Items
          Create the following basic program example to read out the temperature measurement data.
          • For FX3G, FX3U, FX3UC Series PLC
          The following program will store the temperature measurement data (°C) from channels 1 and 2 of the 3rd*1
          adapter to D100 and D101, respectively. The averaging time is set to "1" (immediate data) for channel 1, and
                                                                                                                                           B
                                                                                                                                         FX3UC-4AD
                                                                                                                                         FX3U-4AD
          "5" for channel 2.
                    M8000
                                  MOV        D8288      K4M0
                   Normally
                   ON
                    M8002                                          Error status of 3rd*1 analog special
                                                                                                                                           C
                                                                                                                                               FX3U-4AD-ADP
                                              RST        M6        adapter
                     Initial                                       b6 = OFF (hardware error)
                     pulse                                         Error status of 3rd*1 analog special
                                              RST        M7        adapter
                                                                   b7 = OFF (communication data error)
                                                                                                                                               FX3G-2AD-BD
                    M8001
                                                                   Sets the temperature unit to centigrade
                                                        M8280      (°C).
                    M8002
                                   FNC 12                          Sets the averaging time to "1" for
                                                K1     D8284       channel-1 data.
                                    MOV
                                                                                                                                               FX3U-4DA
                                    MOV
                    M8000
                                   FNC 12     D8280     D100       Stores the current value of the channel-1
                                    MOV                            temperature measurement data in the D100.
                                                                                                                                               FX3U-4DA-ADP
          Even if the temperature measurement data is not stored in D100 or D101, data register D8280 or D8281 can
          be directly used in the arithmetic operation instruction or a PID instruction.
            *1.   "1st " for the FX3G PLC.
          • For FX3U, FX3UC Series PLC
          The following program will store the temperature measurement data (°C) from channels 1 and 2 of the 1st
          adapter to D100 and D101, respectively. The averaging time is set to "1" (immediate data) for channel 1, and
                                                                                                                                          G
                                                                                                                                               FX3G-1DA-BD
          "5" for channel 2.
                    M8002                                          Error status of 1st analog special
                                              RST      D8268.6     adapter
                                                                   b6 = OFF (hardware error)
                    M8001
                                                                   Sets the temperature unit to centigrade
                                                        M8260      (°C).
                    M8002
                                                                                                                                                  -ADP
                                    MOV
                    M8000
                                   FNC 12     D8260     D100       Stores the current value of the channel-1
                                    MOV                            temperature measurement data in the D100.
                                                                                                                                                  -ADP
          Even if the temperature measurement data is not stored in D100 or D101, data register D8260 or D8261 can
          be directly used in the arithmetic operation instruction or a PID instruction.
                                                                                                                                                  -ADP
                                                                                                                               I-25
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                              5 Troubleshooting
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input)                       5.1 PLC Version Number Check
5.      Troubleshooting
          This chapter describes the troubleshooting methods and error status.
          If the temperature measurement data is not input, or if the proper digital value is not input, check the following
          items:
          • Version number of the PLC
          • Wiring
          • Special devices
          • Programs
          • Error status
       1. Power
          The PTW-ADP needs driving power. Verify that the power supply line is properly connected. Also check that
          the POWER indicator lamp of the PTW-ADP is on.
       1. Temperature measurement
          Verify that the special device for the selected channel is correctly selected. This special device should be
          selected depending on the connecting position and the channel.
       2. Averaging time
          Check that the set averaging time is within the specified range. The averaging time should be set in the range
          from 1 to 4095. If the set averaging time is outside the specified range, an error occurs.
       3. Error status
          Check that no error is detected in the PTW-ADP.
          If an error is detected, check the details of the error, and then check the wiring and programs.
                                                  → For a detailed description of special devices, refer to Chapter 4.
I-26
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                  5 Troubleshooting
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input)                                        5.4 Program Check
                                                                                                                                     A
5.4       Program Check
                                                                                                                                         Common Items
          Check the following items for the program:
                                                                                                                                   FX3UC-4AD
                                                                                                                                   FX3U-4AD
       2. Check of storage devices
          Verify that different values are not being stored in the same device by the other parts of the programs.
                                                                                                                                         FX3U-4AD-ADP
          If an error occurs in the PTW-ADP, the corresponding bit will turn on.
                                                                                                                                         FX3G-2AD-BD
                           The temperature measurement data of
                 b1        channel 2 is outside the specified               b6       PTW-ADP hardware error
                           range, or disconnection is detected.
                           The temperature measurement data of
                 b2        channel 3 is outside the specified
                           range, or disconnection is detected.
                                                                            b7       PTW-ADP communication data error
                                                                                                                                      E
                                                                                                                                         FX3U-4DA
                           The temperature measurement data of
                 b3        channel 4 is outside the specified             b8 to 15   Unused
                           range, or disconnection is detected.
                 b4        EEPROM error                                      -                          -
          To solve a problem, refer to the troubleshooting method described below:                                                     F
                                                                                                                                         FX3U-4DA-ADP
       1. Temperature measurement out of specified range or disconnection of line (b0 to b3)
          1) Description of error
             The input temperature measurement value is outside the specified range.
             The temperature measurement value is not in the range between -115°C to 615°C.
             Or the line between PTW-ADP and the platinum resistance thermometer sensor is disconnected.                            G
          2) Remedy
                                                                                                                                         FX3G-1DA-BD
             Check that the input temperature measurement value is within the specified range. Also check the wiring
             condition.
             is destroyed.
          2) Remedy
             Please contact the nearest Mitsubishi Electric distributor office.
                                                                                                                                            -ADP
             The averaging time set for one of the channels (channels 1 to 4) is outside the specified
             range: 1 to 4095.
          2) Remedy
                                                                                                                                            -ADP
             Check that the averaging time is correctly set for each channel.
                                                                                                                                       J
                                                                                                                                   FX3U-4AD-PNK
                                                                                                                                            -ADP
                                                                                                                         I-27
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                        5 Troubleshooting
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input)                          5.5 Error Status Check
I-28
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input)
                                                                                                                                       Common Items
                                                                                                                                   B
                                                                                                                                 FX3UC-4AD
                                                                                                                                 FX3U-4AD
         FX3G/FX3U/FX3UC Series Programmable
         Controllers                                                                                                               C
                                                                                                                                       FX3U-4AD-ADP
         User's Manual [Analog Control Edition]
         FX3U-4AD-PNK-ADP (4-channel Resistance
                                                                                                                                   D
         Thermometer Data Input)
                                                                                                                                       FX3G-2AD-BD
                                                                                                                                    E
                                                                                                                                       FX3U-4DA
                                                                                                                                     F
                                                                                                                                       FX3U-4DA-ADP
                                                                                                                                  G
FX3G-1DA-BD
                                                                                                                                   H
                                                                                                                                 FX3U-4AD-PT
         Foreword
                                                                                                                                          -ADP
         This manual describes the specifications, wiring, and operation methods for the FX3U-4AD-PNK-ADP special
         adapter (4-channel resistance thermometer data input) and should be read and understood before attempting                         I
         to install or use the unit.
                                                                                                                                 FX3U-4AD-PTW
         Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
         it to the end user.
                                                                                                                                          -ADP
           This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
           licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
           rights which may occur as a result of using the contents noted in this manual.
                                                                                                                                     J
                                                                                                                                 FX3U-4AD-PNK
                                                                                                                          J-1
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4AD-TC-ADP (4-channel Resistance Thermocouple Data Input)
J-2
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                   1 Outline
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input)                                                  1.1 Outline of Functions
                                                                                                                                                 Common Items
1.        Outline
            This chapter describes the outline of FX3U-4AD-PNK-ADP (referred to as PNK-ADP).                                                 B
                                                                                                                                           FX3UC-4AD
                                                                                                                                           FX3U-4AD
1.1         Outline of Functions
            The FX3U-4AD-PNK-ADP is an analog special adapter. Connect the FX3U-4AD-PNK-ADP to the FX3G/FX3U/
            FX3UC Series PLC to read the data from the 4-channel resistance thermometer.
                                                                                                                                             C
            1) Up to 4 PNK-ADP units can be connected to the FX3U/FX3UC Series PLC.
                                                                                                                                                 FX3U-4AD-ADP
               Up to 2*1 PNK-ADP units can be connected to the FX3G Series PLC.
               (Including other analog special adapters)
            2) Thermometer types Pt1000 and Ni1000 can be connected. (However, it's impossible to use both types
               Pt1000 and Ni1000 with 1 adapter.)
            3) The temperature data will be automatically written to the special data register of the FX3G/FX3U/FX3UC                        D
               Series PLC.
                                                                                                                                                 FX3G-2AD-BD
                                                System                                           Point and section to be referred to
                                                                                                                                                 FX3U-4DA
                                                                                                       To check the connectable
                                                                                                 …… PLC model number, refer
+ + to Section 1.3.
                                                                                                                                                 FX3U-4DA-ADP
                                                  Expansion
          4th       3rd       2nd       1st
        adapter   adapter   adapter   adapter      board*2
                                                                                                       For a detailed
                                                                                                 …… description of wiring,
                   Analog data                                                                         refer to Chapter 3.
                                                                                                                                                 FX3G-1DA-BD
        Pt1000 and Ni1000
     Refer to the system configuration shown in the User's Manual - Hardware Edition to check the number of connectable units
     and to configure the entire system.                                                                                                             I
                                                                                                                                           FX3U-4AD-PTW
     *1. Only 1 analog special adapter can be connected to the 14-point and 24-point type main unit.
     *2. The expansion board is not required when connecting with the FX3UC (D, DSS) PLC.
                                                                                                                                                    -ADP
                                                                                                                                               J
                                                                                                                                           FX3U-4AD-PNK
                                                                                                                                                    -ADP
                                                                                                                                    J-3
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                        1 Outline
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input)                  1.2 Setup Procedure Before Starting Operation
FX3U-4AD-PNK-ADP
Refer to Chapter 1.
                              Wiring                                  Wiring:
                                                                      •Selection of sensor cable
                                                                      •Power supply line
                                        Refer to Chapter 4.           •Analog input line
                          Programming                                 Programming:
                                                                      •Details of special devices
                                                                      •Examples of basic programs
J-4
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                           1 Outline
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input)                                        1.3 Connectable PLC and Its Version Number
                                                                                                                                                     A
1.3      Connectable PLC and Its Version Number
                                                                                                                                                         Common Items
         PNK-ADP is compatible with the following PLC.
                                                                                                                                                   FX3UC-4AD
                                                                                                                                                   FX3U-4AD
          FX3UC Series PLC                   Ver. 1.30 or later                             After August 2004
          FX3G Series PLC                    Ver. 1.00 or later                     After June 2008 (initial production)
      1. Version check
         Special data register D8001 contains information for determining the PLC version number.
                                                                                                                                                     C
                                                                                                                                                         FX3U-4AD-ADP
                            D8001                2     4       1      0        0
                        PLC type and
                       version number                                         Version data (Example: Ver. 1.00)
                                                                      (
                                                        PLC type Example: 24 = FX3U and FX3UC series
                                                                                                                     )                               D
                                                                          26 = FX3G series
                                                                                                                                                         FX3G-2AD-BD
      2. How to look at the manufacturer's serial number
         The year and month of production of the product can be seen from the manufacturer's serial number
         "SERIAL" indicated on the label adhered to the right side of the product.
                                                  Example:
                                                                                                                                                      E
                                                                                                                                                         FX3U-4DA
                                                  FX3U-48MR/ES(production number : 570001)
                                                                                      PROGRAMMABLE
                                    Right side       MITSUBISHI                         CONTROLLER
                                                     MODEL           FX3U-48MR/ES
                                                               100-240VAC 50/60Hz 40W
                                                         OUT:30VDC/240VAC 2A(COSφ=1)
                                                                                                                                                       F
                                                     SERIAL                     570001
                                                                                                                                                         FX3U-4DA-ADP
                                                                          80M1 IND. CONT. EQ.
                                                       MITSUBISHI ELECTRIC CORPORATION
                                                     MADE IN JAPAN
                                                                 5        7     0      0     0    1
                                                                                                                                                    G
                                                                                                                                                         FX3G-1DA-BD
                                                                                       Control number
                                                                          Month (Example: 7 = July), 1 to 9 = January to September,
                                                                          X = October, Y = November, Z = December
                                                                     Year (Example: 5 = 2005), last digit of dominical year
                                                                                                                                                     H
1.4      Compatible Programming Tool Version Number
                                                                                                                                                   FX3U-4AD-PT
         Use the programming tool having the following version number to create programs for PNK-ADP:
                                                                                                                                                            -ADP
          • SW D5C-GPPW-J
          • SW D5C-GPPW-E                        (Ver. 8.72A or later)                When selecting a model, select FX3G.
                                                                                                                                                            -ADP
         If a programming tool with the wrong version number is used, programming will not be possible.
          *1.   For Ver. 8.13P to 8.24A of GX Developer, select FX3UC for the PLC type.                                                                J
                                                                                                                                                   FX3U-4AD-PNK
                                                                                                                                                            -ADP
                                                                                                                                          J-5
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                       2 Specifications
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input)                                             2.1 Generic Specifications
2.     Specifications
         This chapter describes the general, power supply, and performance specifications for the PNK-ADP.
                  Item                                                   Specifications
                                   0 to 55°C (32 to 131°F) when operating
          Ambient temperature
                                   -25 to 75°C (-13 to 167°F) when stored
          Relative humidity        5 to 95%RH (no condensation) when operating
                                                         Frequency       Acceleration     Half amplitude
                                                            (Hz)             (m/s2)            (mm)
                                                                                                           Tested 10 times in
                                                           10 - 57             -                0.035      each direction (X-, Y-,
          Vibration resistance     DIN Rail Mounting
                                                          57 - 150            4.9                 -        and Z-axis directions)
                                                                                                           (Total: 80 min, each)
                                                          10 to 57             −                0.075
                                   Direct Mounting*1
                                                          57 to 150           9.8                −
                                   147 m/s2 Acceleration, Action time: 11ms, 3 times by half-sine pulse in each direction X, Y,
          Shock resistance
                                   and Z
                                   Using noise simulator of:
          Noise resistance
                                   Noise voltage: 1,000Vp-p / Noise width: 1µs / Rise: 1ns / Cycle: 30 to 100Hz
          Dielectric withstand
                                   500 V AC, for 1 min
          voltage
                                                                       Between batch of all terminals and ground terminal
                                   5MΩ or more using 500V DC
          Insulation resistance
                                   insulation resistance meter
                                   Class D grounding (grounding resistance: 100 Ω or less)
          Grounding
                                   <Common grounding with a heavy electrical system is not allowed.>*2
          Working
                                   Free from corrosive or flammable gas and excessive conductive dusts
          environment
          Working altitude         < 2000m*3
          *1.   If PNK-ADP is connected to the FX3UC Series PLC, direct installation is not possible.
          *2.                      Other                   Other                      Other
                      PLC        equipment      PLC      equipment      PLC         equipment
                      Item                                                  Specifications
          A/D conversion circuit          24V DC +20% -15%, 45mA
          driving power                   (It is necessary to connect a 24V DC power supply to the terminal block.)
                                          5V DC, 15mA
          Interface driving power         (Since the internal power is supplied from the FX Series main unit, it is not
                                          necessary to supply the power.)
J-6
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                          2 Specifications
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input)                                                           2.3 Performance Specifications
                                                                                                                                                              A
2.3      Performance Specifications
                                                                                                                                                                  Common Items
                                                                                Specifications
                 Item
                                                    Centigrade (°C)                                            Fahrenheit (°F)                                B
                                                                                                                                                            FX3UC-4AD
                                                                                                                                                            FX3U-4AD
                                                 Platinum resistance thermometer sensor (2-wire or 3-wire) Pt1000
                                                                         JIS C 1604-1997
          Input signal
                                                  Nickel resistance thermometer sensor (2-wire or 3-wire) Ni1000
                                                                         DIN 43760-1987
                                                                                                                                                                  FX3U-4AD-ADP
                              Pt1000                           -500 to +2500                Pt1000                              -580 to +4820
          Digital output
                              Ni1000                           -400 to +1100                Ni1000                              -400 to +2300
                              Pt1000                                                        Pt1000
          Resolution                                                0.1°C                                                          0.2°F
                              Ni1000                                                        Ni1000
                                               ±0.5% for full scale (when ambient temperature is 25°C±5°C)
                                                                                                                                                              D
          Total accuracy
                                                                                                                                                                  FX3G-2AD-BD
                                         ±1.0% for full scale (when ambient temperature is in the range of 0 to 55°C)
                              • FX3U/FX3UC Series PLC : 200µs (The data will be updated at every scan time.)
          A/D conversion
                              • FX3G PLC : 250µs (The data will be updated at every scan time.)
          time
                                                    →For a detailed description of data update, refer to Section2.4.
                                                                                                                                                                  FX3U-4DA
                                       -Pt1000                                                   -Pt1000
                                                 +2560                                                       +4920
                                                 +2500                                                       +4820
                                                                                                                                                 +492.8°F
                                                                                 Approx.
                                                                                 +256°C
                                                                                                                                                 Approx.
                                            -50°C                                                          -58°F     0
                                                                                                                                                                F
                                                         0
                                                                                                                                                                  FX3U-4DA-ADP
                                    Approx.
Approx.
                                                                       +250°C                                                          +482 °F
                                    -55°C
-67°F
                                                             -500                                                        -580
          Input                                              -550                                                        -670
          characteristics
                                       -Ni1000
                                                  +1150
                                                                                                 -Ni1000
                                                                                                             +2390                                           G
                                                  +1100                                                      +2300
                                                                                                                                                                  FX3G-1DA-BD
                                                                                                                                                 Approx.
                                                                                  Approx.
                                                                                  +115°C
+239°F
-40°C 0 -40°F 0
                                                                                                                                                              H
                                       Approx.
Approx.
                                                                        +110°C                                                         +230°F
                                       -45°C
-49°F
                                                             -400                                                        -400
                                                                                                                                                            FX3U-4AD-PT
                                                             -450                                                        -490
                                                                                                                                                                     -ADP
                              • The photocoupler is used to insulate the analog input area from the PLC.
          Insulation method   • The DC/DC converter is used to insulate the power supply line from the analog input area.
                              • Channels are not insulated from each other.                                                                                           I
          Number of I/O                                                 0 points
                                                                                                                                                            FX3U-4AD-PTW
          points occupied        (This number is not related to the maximum number of input/output points of the PLC.)
                                                                                                                                                                     -ADP
                                                                                                                                                                J
                                                                                                                                                            FX3U-4AD-PNK
                                                                                                                                                                     -ADP
                                                                                                                                                      J-7
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                    2 Specifications
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input)                                            2.4 A/D Conversion Time
                 FX3U-4AD-PNK-ADP          FX3U-4AD-PNK-ADP
                        n'th                      1st                                FX3U/FX3UC Series PLC
                                                                                           Sequence
                                                                                            program
                                                             A/D conversion start
                                                   A/D            command
                                                conversion
                                                             Digital value writing
                                                200 µs/4ch
                                                             A/D conversion start       END instruction
                        A/D                                       command
                     conversion
                                                             Digital value writing
                     200 µs/4ch
J-8
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                               2 Specifications
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input)                                  2.5 Temperature Measurement
                                                                                                                                A
2.4.2     When connected to a FX3G PLC
                                                                                                                                    Common Items
        1. A/D conversion and special data register update timing
          A/D conversion is performed at every scan time of the PLC.
          During execution of END instruction, the PLC performs A/D conversion, reads out the A/D converted data,
          and then writes the data in the special data registers.                                                               B
                                                                                                                              FX3UC-4AD
                                                                                                                              FX3U-4AD
                 FX3U-4AD-PNK-ADP          FX3U-4AD-PNK-ADP
                        2nd                       1st                                FX3G Series PLC
                                                                                        Sequence
                                                                                         program
                                                                                                                                C
                                                                                                                                    FX3U-4AD-ADP
                                                             A/D conversion start
                                                   A/D            command
                                                conversion
                                                             Digital value writing
                                                250 µs/4ch
                                                                                     END instruction
                                                                                                                                D
                                                             A/D conversion start
                         A/D                                      command
                      conversion
                                                                                                                                    FX3G-2AD-BD
                                                             Digital value writing
                      250 µs/4ch
                                                                                                                                    FX3U-4DA
        3. If two analog special adapters are connected
          During execution of the END instruction, data will be read out from all the connected adapters (in the order of
          1st adapter → 2nd adapter).
                                                                                                                                    FX3U-4DA-ADP
          During execution of the END instruction, the A/D converted data of all 4 channels will be read out in 250µs,
          and the data read out will be written to the special data registers.
          END instruction execution time will be "250µs × number of connected adapters."
                                                                                                                                    FX3G-1DA-BD
          To stabilize the temperature measurement, warm-up the system for 30 minutes or more after power-on.
                                                                                                                                H
                                                                                                                              FX3U-4AD-PT
                                                                                                                                       -ADP
                                                                                                                                        I
                                                                                                                              FX3U-4AD-PTW
                                                                                                                                       -ADP
                                                                                                                                  J
                                                                                                                              FX3U-4AD-PNK
                                                                                                                                       -ADP
                                                                                                                     J-9
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                              3 Wiring
FX3U-4AD-PNK-ADP (4-channel Thermometer Data Input)
3.     Wiring
         This chapter describes the PNK-ADP wiring.
         Observe the following caution to wire the PNK-ADP.
WIRING PRECAUTIONS
          • Make sure to cut off all phases of the power supply externally before attempting wiring work.
            Failure to do so may cause electric shock or damages to the product.
WIRING PRECAUTIONS
          • Connect the DC power supply wiring to the dedicated terminals described in this manual.
            If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will be
            burnt out.
          • Do not wire vacant terminals externally.
            Doing so may damage the product.
          • Perform class D grounding (grounding resistance: 100Ω or less) to the grounding terminal on the main unit.
            Do not use common grounding with heavy electrical systems.
          • When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
            Failure to do so may cause fire, equipment failures or malfunctions.
          • Make sure to observe the following precautions in order to prevent malfunctions under the influence of noise:
            - Do not bundle the power line or twisted shielded cable together with or lay it close to the main circuit, high-
                voltage line, or load line.
                Otherwise, noise disturbance and/or surge induction are likely to take place. As a guideline, lay the control line
                at least 100mm (3.94") or more away from the main circuit, high-voltage line, or load line.
            - Ground the shield of the analog input/output cable at one point on the signal receiving side.
                However, do not use common grounding with heavy electrical systems.
          • Make sure to properly wire to the European terminal board in accordance with the following precautions.
            Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product.
            - The disposal size of the cable end should be 9 mm (0.35").
            - Tightening torque should be between 0.22 to 0.25 N•m.
            - Twist the end of strand wire and make sure there are no loose wires.
            - Do not solder-plate the electric wire ends.
            - Do not connect more than the specified number of wires or electric wires of unspecified size.
            - Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
J-10
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                          3 Wiring
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input)                             3.1 Terminal Layout
                                                                                                                   A
3.1      Terminal Layout
                                                                                                                       Common Items
         The terminals of the PNK-ADP are arranged as follows:
                                                                                                                 FX3UC-4AD
                                                                                                                 FX3U-4AD
                            FX3U-4AD-PNK
                                    -ADP
                                 POWER
Signal Application C
                                                                                                                       FX3U-4AD-ADP
                                                       24+
                          24+
                                                                 External power
                                                       24-
                          24-
                                                                 Ground terminal
                                                       L1+
                          L1+
                                                                 Channel-1 Pt1000/Ni1000
                                                       L1-
                          L1-
                                                                                                                   D
                                                                 sensor input
                                                        l1-
                          I1-
                          L2+
L2+
                                                                                                                       FX3G-2AD-BD
                                                                 Channel-2 Pt1000/Ni1000
                          L2-
                                                        l2-
                          L3+
                                                       L3+
                                                                 Channel-3 Pt1000/Ni1000
                                                       L3-
                          L3-
                                                                 sensor input
                                                        l3-
                                                                                                                    E
                          I3-
                                                       L4+
                          L4+
Channel-4 Pt1000/Ni1000
                                                                                                                       FX3U-4DA
                                                       L4-
                          L4-
                                                                 sensor input
                                                        l4-
                          I4-
                                                                                                                       FX3U-4DA-ADP
                                                                                                                  G
FX3G-1DA-BD
                                                                                                                   H
                                                                                                                 FX3U-4AD-PT
                                                                                                                          -ADP
                                                                                                                           I
                                                                                                                 FX3U-4AD-PTW
                                                                                                                          -ADP
                                                                                                                     J
                                                                                                                 FX3U-4AD-PNK
                                                                                                                          -ADP
                                                                                                      J-11
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                  3 Wiring
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data                  Input) 3.2 Applicable Cables and Terminal Tightening Torque
       1. Cables
         Applicable cable and tightening torque
                                 Wire size            Tightening
                                                                                            Termination
                           (stranded/single-wire)       torque
                         0.3 mm2 to 0.5 mm2                        • To connect a stranded cable, peel the cover off the cable
          Single-wire                                                and then twist the core before connection.
                         (AWG22 to 20)
                                                                   • To connect a single-wire cable, just strip the cover off the
          2-wire         0.3mm2(AWG22)                               cable before connection.
                                                      0.22 N•m to • Rod terminal with insulation sleeve
          Rod terminal   0.3 mm2 to 0.5 mm2            0.25 N•m     (recommended terminal)
          with           (AWG22-20)                                 AI 0.5-8WH : Manufactured by Phoenix Contact
          insulation     (Refer to the rod terminal
                                                                  • Caulking tool
          sleeve         external view shown in the
                                                                    CRIMPFOX ZA 3 : Manufactured by Phoenix Contact
                         following figure.)
                                                                    (or CRIMPFOX UD 6 : Manufactured by Phoenix Contact)
       3. Tool
         • To tighten terminals, use a small-sized screwdriver whose head is straight and is not widened as shown in
           the figure to the right.
            Note:
            If the diameter of screwdriver grip is too small, tightening torque will not
                                                                                                                       The head
            be able to be achieved. Use the following recommended screwdriver or                                       should be
            an appropriate replacement (grip diameter: approximately 25mm).                                            straight.
                         Manufacturer                          Model
            Phoenix Contact                                  SZS 0.4×2.5                      0.4mm                    2.5mm
                                                                                              (0.01")                  (0.09")
J-12
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                              3 Wiring
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input)                                               3.3 Power Supply Line
                                                                                                                                       A
3.3      Power Supply Line
                                                                                                                                           Common Items
         Connect the 24V DC power supply line of the PNK-ADP to the 24+ and 24- terminals of the terminal block.
                                                                                                                                     FX3UC-4AD
                                                                                                                                     FX3U-4AD
         1. To use an external power                                       2. To use the 24V DC power of the PLC
                PNK-ADP                                                             PNK-ADP
                                       FX3G/FX3U                                                     FX3G/FX3U
                     +5V               Series PLC                                        +5V         Series PLC
                                       (Main unit)                                                   (Main unit)
                                                                                                                                       C
                                                                                                                                           FX3U-4AD-ADP
                24- 24+                                                             24- 24+         0V 24V                             D
                                                                                                                                           FX3G-2AD-BD
          Terminal                                                          Terminal
          block                                                             block
                                             Class-D                                                 Class-D
                                                                                                    grounding
                                                                                                                                        E
                      24V DC                grounding
                                                                                                                                           FX3U-4DA
         • Ground the "    " terminal to a class-D grounding power supply line (100Ω or less) together with the
           grounding terminal of the PLC main unit.
         • For the timing of power-on/off when using an external power supply, see the following manual of the PLC
           to be connected.
                                                   → Refer to the FX3G Series User's Manual - Hardware Edition.                          F
                                                   → Refer to the FX3U Series User's Manual - Hardware Edition.
                                                                                                                                           FX3U-4DA-ADP
3.3.2    To connect to the FX3UC Series PLC
                                       PNK-ADP
                                                        FX3UC Series PLC
                                                                                     FX2NC
                                                                                   Series PLC
                                                                                                                                      G
                                                                                                                                           FX3G-1DA-BD
                                           +5V             (Main unit)          (Input extension
                                                                                     block)
                                                                                        Power                                          H
                                                                               Power crossover
                                                                                                                                     FX3U-4AD-PT
                                                             Power
                                                            connector        connector connector
                                                                         Class-D
                                                     24V DC             grounding
                                                                                                                                              -ADP
         • Ground the "    " terminal to a class-D grounding power supply line (100Ω or less) together with the
           ground terminal of the PLC main unit.
                                                                                                                                              -ADP
                                                                                                                          J-13
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                      3 Wiring
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input)                          3.4 Selection of the Resistance Thermometer Sensor
                                                                           +5V
                          2-wire
                          sensors                                   47kΩ    47kΩ
                          type
                                                                             1MΩ       ch
                                                             L+
                                                              L-
                                                        *2                   1MΩ
                                                              I-
                                                              24+
                                    24V DC*1
                                                              24-
                                               Class-D grounding
                          L+, L-, I-, ch:  represents the channel number.
          *1.   24V DC service power supply of the FX3G/FX3U Series PLC can also be used.
          *2.   When using a 2-wire temperature sensor type, short-circuit the [L -] terminal and the [I -] terminal.
                For the lead wire use a 10Ω resistance or less per line.
          *3.   Separate the cable of the platinum resistance themometer sensor from the other power cables or
                areas easily affected by inductive noise (of the commercial power, etc.).
J-14
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                    3 Wiring
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input)                              3.6 Caution Regarding Wiring
                                                                                                                             A
3.6      Caution Regarding Wiring
                                                                                                                                 Common Items
         • It is not possible to connect different types of resistance thermometer to 4 channels of PNK-ADP. Be sure
           to use the same type of resistance thermometer for all the channels.
3.7      Grounding
                                                                                                                             B
                                                                                                                           FX3UC-4AD
                                                                                                                           FX3U-4AD
         Grounding should be performed as stated below.
         • The grounding resistance should be 100Ω or less.
         • Independent grounding should be performed for best results.
           When independent grounding is not performed, perform "shared grounding" as shown in the following                 C
           figure.
                                                                                                                                 FX3U-4AD-ADP
                               → For details, refer to the User’s Manual - Hardware Edition of the PLC Series.
                                                                                                                                 FX3G-2AD-BD
         • The grounding wire size should be AWG22 to 20 (0.3 to 0.5 mm2).
         • The grounding point should be close to the PLC, and all grounding wires should be as short as possible.
                                                                                                                                 FX3U-4DA
                                                                                                                               F
                                                                                                                                 FX3U-4DA-ADP
                                                                                                                            G
FX3G-1DA-BD
                                                                                                                             H
                                                                                                                           FX3U-4AD-PT
                                                                                                                                    -ADP
                                                                                                                                     I
                                                                                                                           FX3U-4AD-PTW
                                                                                                                                    -ADP
                                                                                                                               J
                                                                                                                           FX3U-4AD-PNK
                                                                                                                                    -ADP
                                                                                                                J-15
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                       4 Programming
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input)                                    4.1 Loading of A/D Conversion Data
4.      Programming
          This chapter describes how to create programs that can read out the analog data using the PNK-ADP.
                The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the
                next adapter as the 2nd analog special adapter, and so on. However, in this case, do not include the high-
                speed input/output special adapter and the communication special adapter.
J-16
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                  4 Programming
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input)                               4.1 Loading of A/D Conversion Data
                                                                                                                                    A
         • FX3G Series PLC
                                                                                                                                        Common Items
                     Communi-
                       cation          Connector
            FX3U-4AD          FX3U-4AD
                      special          conversion
            -PNK-ADP          -PNK-ADP
                      adapter           adapter                            FX3G Series PLC
                2nd*1                1st
                                                              Special devices                                                       B
                                                                                                                                  FX3UC-4AD
                                                                                                                                  FX3U-4AD
                                                           Special auxiliary relays:
                                                             M8280 to M8289
                                    A/D                    Special data registers:
                                                             D8280 to D8289                  Sequence
                                                                                             Program
                                                           Special auxiliary relays:
                A/D
                                                             M8290 to M8299
                                                           Special data registers:
                                                                                                                                    C
                                                                                                                                        FX3U-4AD-ADP
                                                             D8290 to D8299
            The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the
            next adapter as the 2nd analog special adapter, and so on. However, in this case, do not include the
            connect conversion adapter and the communication special adapter.
          *1.    The second special adapter is not available in the 14-point and 24-point type main unit.
                                                                                                                                    D
                                                                                                                                        FX3G-2AD-BD
                                                                                                                                     E
                                                                                                                                        FX3U-4DA
                                                                                                                                      F
                                                                                                                                        FX3U-4DA-ADP
                                                                                                                                   G
FX3G-1DA-BD
                                                                                                                                    H
                                                                                                                                  FX3U-4AD-PT
                                                                                                                                           -ADP
                                                                                                                                            I
                                                                                                                                  FX3U-4AD-PTW
                                                                                                                                           -ADP
                                                                                                                                      J
                                                                                                                                  FX3U-4AD-PNK
                                                                                                                                           -ADP
                                                                                                                       J-17
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                            4 Programming
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input)                                 4.2 List of Special Devices
J-18
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                              4 Programming
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input)                                           4.3 Selection of Temperature Unit
                                                                                                                                               A
         • FX3G Series PLC
                                                                                                                                                   Common Items
                                                                                                                      R: Read / W: Write
                                        Device number
             Special device                                                  Description                    Attribute        Refer to
                                         1st         2nd
                                        M8280       M8290     Selects the temperature unit                    R/W          Section 4.3
                                        M8281       M8291     Input sensor selection                          R/W          Section 4.4
                                                                                                                                               B
          Special auxiliary relay
                                                                                                                                             FX3UC-4AD
                                                                                                                                             FX3U-4AD
                                    M8282 to M8292 to
                                                      Unused (Do not use.)                                        -             -
                                     M8289    M8299
                                                              Channel-1 temperature measurement
                                        D8280       D8290                                                         R
                                                              data
                                        D8281       D8291
                                                              Channel-2 temperature measurement
                                                              data
                                                                                                                  R                            C
                                                                                                                           Section 4.5
                                                                                                                                                   FX3U-4AD-ADP
                                                              Channel-3 temperature measurement
                                        D8282       D8292                                                         R
                                                              data
                                                              Channel-4 temperature measurement
                                        D8283       D8293                                                         R
                                                              data
                                                                                                                                                   FX3G-2AD-BD
                                                              Averaging time for channel 2
                                        D8285       D8295                                                     R/W
                                                              (Setting range: 1 to 4095)
                                                                                                                           Section 4.6
                                                              Averaging time for channel 3
                                        D8286       D8296                                                     R/W
                                                              (Setting range: 1 to 4095)
                                        D8287       D8297
                                                              Averaging time for channel 4
                                                              (Setting range: 1 to 4095)
                                                                                                              R/W                               E
                                                                                                                                                   FX3U-4DA
                                        D8288       D8298     Error status                                    R/W          Section 4.7
                                        D8289       D8299     Model code = 11                                     R        Section 4.8
                                                                                                                                                   FX3U-4DA-ADP
         The state of special auxiliary relays decides the PNK-ADP's temperature unit as shown in the table below.
         To switch the temperature unit, use the following special auxiliary relays:
         • FX3U, FX3UC Series PLC
                                                                                                                                                   FX3G-1DA-BD
                                                                                 Selection of temperature unit:
             M8260           M8270               M8280            M8290          OFF: Centigrade (°C)
                                                                                 ON: Fahrenheit (°F)
                                                                   Description
               1st                2nd
                                                Selection of temperature unit:
                                                                                                                                                      -ADP
           centigrade (°C) for the 1st adapter:                        Fahrenheit (°F) for the 2nd adapter:
             M8001                                                       M8000
                                                  M8260                                                  M8270                                   J
             Normally OFF                                                Normally ON
                                                                                                                                             FX3U-4AD-PNK
                                                                                                                                                      -ADP
                                                                                                                                    J-19
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                     4 Programming
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input)                                           4.4 Input sensor selection
         1) To select Pt1000 for the 1st adapter:                 2)To select Ni1000 for the 2nd adapter :
             M8001                                                   M8000
                                           M8261                                                    M8271
            Normally OFF                                              Normally ON
J-20
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                 4 Programming
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input)                                   4.5 Temperature Measurement
                                                                                                                                 A
4.5      Temperature Measurement
                                                                                                                                     Common Items
         The temperature data input in the PNK-ADP will be stored in the special data registers.
         The special data registers that store the temperature data are shown in the following table:
         • FX3U, FX3UC Series PLC
                                                                                                                                 B
                        Special data register
                                                                                                                               FX3UC-4AD
                                                                                                                               FX3U-4AD
                                                                                   Description
             1st          2nd         3rd         4th
            D8260        D8270      D8280        D8290     Stores the channel-1 temperature measurement data.
            D8261        D8271      D8281        D8291     Stores the channel-2 temperature measurement data.
            D8262        D8272      D8282        D8292     Stores the channel-3 temperature measurement data.                    C
            D8263        D8273      D8283        D8293     Stores the channel-4 temperature measurement data.
                                                                                                                                     FX3U-4AD-ADP
         • FX3G Series PLC
                                                                                                                                     FX3G-2AD-BD
            D8281        D8291     Stores the channel-2 temperature measurement data.
            D8282        D8292     Stores the channel-3 temperature measurement data.
            D8283        D8293     Stores the channel-4 temperature measurement data.
         The immediate data or the average data (data averaged in accordance with the specified averaging time) will
                                                                                                                                  E
                                                                                                                                     FX3U-4DA
         be stored in the above data registers as the temperature measurement data.
                                          → For a detailed description of the averaging time, refer to Section 4.6.
                                                                                                                                     FX3U-4DA-ADP
      2. Program Example (For FX3U, FX3UC Series PLC)
              M8000
                                        FNC 12
                                         MOV
                                                   D8260    D100       Stores the channel-1 temperature measurement data
                                                                       of the 1st analog special adapter in the D100.
                                                                                                                                G
             Normally
                                                                                                                                     FX3G-1DA-BD
             ON
         Even if the temperature measurement data is not stored in D100 or D101, data registers D8260 or D8261 can
         be directly used in the arithmetic operation instruction or a PID instruction.                                          H
                                                                                                                               FX3U-4AD-PT
                                                                                                                                        -ADP
                                                                                                                                         I
                                                                                                                               FX3U-4AD-PTW
                                                                                                                                        -ADP
                                                                                                                                   J
                                                                                                                               FX3U-4AD-PNK
                                                                                                                                        -ADP
                                                                                                                     J-21
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                       4 Programming
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input)                                                   4.6 Averaging Time
                                          FNC 12     K128         D8265       Sets the averaging time to "128" for the channel-2
                                           MOV                                data of the 1st analog special adapter.
J-22
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                            4 Programming
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input)                                                            4.7 Error Status
                                                                                                                                               A
4.7      Error Status
                                                                                                                                                   Common Items
         If an error is detected on PNK-ADP, the error status data will be stored in the corresponding special data
         register.
         The following table shows the special data registers that store the error status data:
         • FX3U, FX3UC Series PLC                                                                                                              B
                                                                                                                                             FX3UC-4AD
                                                                                                                                             FX3U-4AD
                              Special data register
                                                                                                  Description
                 1st           2nd             3rd             4th
             D8268           D8278            D8288           D8298         Stores the error status data.
                                                                                                                                                   FX3U-4AD-ADP
                Special data register
                                                                Description
                 1st            2nd
             D8288            D8298         Stores the error status data.
         Check the ON/OFF status of each bit of the error status data register to determine the error. Errors are
                                                                                                                                               D
                                                                                                                                                   FX3G-2AD-BD
         assigned to the bits as shown in the following table. Create a program to detect errors.
                                                                                                                                                   FX3U-4DA
                           The temperature measurement data
                 b1        of channel 2 is outside the specified                b6         PNK-ADP hardware error
                           range, or disconnection is detected.
                           The temperature measurement data
                 b2        of channel 3 is outside the specified                b7         PNK-ADP communication data error
                           range, or disconnection is detected.                                                                                  F
                           The temperature measurement data
                                                                                                                                                   FX3U-4DA-ADP
                 b3        of channel 4 is outside the specified            b8 to b15      Unused
                           range, or disconnection is detected.
                 b4        EEPROM error                                          -                              -
                                                                                                                                                   FX3G-1DA-BD
         necessary to clear the error status with a program at next power-on of the PLC.
         For this reason, be sure to create the following program:
         • For FX3G, FX3U, FX3UC Series PLC
            M8000
                                        MOV          D8288    K4M0
                                                                                                                                               H
                                                                                                                                             FX3U-4AD-PT
           Normally
           ON
            M8002                                                           Error status in the 3rd*1 analog special adapter
                                                                                                                                                      -ADP
                                                     RST       M7
                                                                            b7 = OFF (communication data error)
                                                                                                                                                      -ADP
                                                                                                                                                 J
                                                                                                                                             FX3U-4AD-PNK
                                                                                                                                                      -ADP
                                                                                                                                 J-23
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                              4 Programming
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input)                                             4.7 Error Status
                M8000
                                      MOV     D8288     K4M0
                 M0
                                                         Y000     The temperature measurement data
                                                                  of channel 1 is outside the specified
                                                                  range, or disconnection is detected.
                 M1
                                                         Y001     The temperature measurement data
                                                                  of channel 2 is outside the specified
                                                                  range, or disconnection is detected.
                 M2
                                                         Y002     The temperature measurement data
                                                                  of channel 3 is outside the specified
                                                                  range, or disconnection is detected.
                 M3
                                                         Y003     The temperature measurement data
                                                                  of channel 4 is outside the specified
                                                                  range, or disconnection is detected.
                 M4
                                                         Y004     EEPROM error in 3rd*1 adapter
                 M5
                                                         Y005     Averaging time setting error in 3rd*1
                                                                  adapter
                 M6
                                                         Y006     PNK-ADP hardware error in 3rd*1
                                                                  adapter
                 M7
                                                         Y007     PNK-ADP communication data error
                                                                  in the 3rd*1 adapter
J-24
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                            4 Programming
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input)                                          4.7 Error Status
                                                                                                                             A
      3. Program Example 2 (For FX3U, FX3UC Series PLC)
                                                                                                                                 Common Items
              D8268.0
                                                         Y000   The temperature measurement data
                                                                of channel 1 is outside the specified
              D8268.1
                                                                range, or disconnection is detected.                         B
                                                                                                                           FX3UC-4AD
                                                                                                                           FX3U-4AD
                                                         Y001   The temperature measurement data
                                                                of channel 2 is outside the specified
                                                                range, or disconnection is detected.
              D8268.2
                                                         Y002   The temperature measurement data
                                                                of channel 3 is outside the specified
              D8268.3
                                                                range, or disconnection is detected.                         C
                                                                                                                                 FX3U-4AD-ADP
                                                         Y003   The temperature measurement data
                                                                of channel 4 is outside the specified
                                                                range, or disconnection is detected.
              D8268.4
                                                         Y004   EEPROM error in 1st adapter
              D8268.5
                                                                                                                             D
                                                                                                                                 FX3G-2AD-BD
                                                         Y005   Averaging time setting error in 1st
                                                                adapter
              D8268.6
                                                         Y006   PNK-ADP hardware error in 1st
                                                                adapter
              D8268.7
                                                                                                                              E
                                                                                                                                 FX3U-4DA
                                                         Y007   PNK-ADP communication data error
                                                                in the 1st adapter
                                                                                                                                 FX3U-4DA-ADP
                                                                                                                            G
FX3G-1DA-BD
                                                                                                                             H
                                                                                                                           FX3U-4AD-PT
                                                                                                                                    -ADP
                                                                                                                                     I
                                                                                                                           FX3U-4AD-PTW
                                                                                                                                    -ADP
                                                                                                                               J
                                                                                                                           FX3U-4AD-PNK
                                                                                                                                    -ADP
                                                                                                               J-25
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                               4 Programming
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input)                                             4.8 Model Code
Use the above special data registers to check whether PNK-ADP is connected or not.
J-26
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                    4 Programming
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input)                                         4.9 Basic Program Example
                                                                                                                                     A
4.9      Basic Program Example
                                                                                                                                         Common Items
         Create the following basic program to read out the temperature measurement data.
         • For FX3G, FX3U, FX3UC Series PLC
         The following program will select Pt1000 and will store the temperature measurement data (°C) of channels 1
         and 2 of the 3rd*1 adapter in the D100 and the D101, respectively. The averaging time will be set to "32" for
                                                                                                                                     B
                                                                                                                                   FX3UC-4AD
                                                                                                                                   FX3U-4AD
         channel 1, and "128" for channel 2.
                    M8000
                                  MOV        D8288     K4M0
                    Normally
                    ON
                    M8002                                        Error status of 3rd*1 analog special
                                                                                                                                     C
                                                                                                                                         FX3U-4AD-ADP
                                             RST        M6       adapter
                                                                 b6 = OFF (hardware error)
                     Initial
                     pulse                                       Error status of 3rd*1 analog special
                                             RST        M7       adapter
                                                                 b7 = OFF (communication data error)
                                                                                                                                         FX3G-2AD-BD
                     M8001
                                                       M8280     Sets the temperature unit to
                                                                 centigrade (°C)
                     M8002
                                   FNC 12      K32    D8284      Sets the averaging time to "32" for
                                                                                                                                      E
                                                                                                                                         FX3U-4DA
                                    MOV                          channel-1 data
                                                                                                                                         FX3U-4DA-ADP
                                   FNC 12    D8281     D101      channel-2 measurement
                                    MOV                          temperature data to D101.
         Even if the temperature measurement data is not stored to D100 or D101, data registers D8280 or D8281 can
         be directly used in the arithmetic operation instruction or a PID instruction.
          *1.   "1st" for the FX3G PLC.                                                                                             G
FX3G-1DA-BD
                                                                                                                                     H
                                                                                                                                   FX3U-4AD-PT
                                                                                                                                            -ADP
                                                                                                                                             I
                                                                                                                                   FX3U-4AD-PTW
                                                                                                                                            -ADP
                                                                                                                                       J
                                                                                                                                   FX3U-4AD-PNK
                                                                                                                                            -ADP
                                                                                                                        J-27
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                   4 Programming
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input)                                        4.9 Basic Program Example
                    M8002
                                  FNC 12      K32    D8264      Sets the averaging time to "32" for
                                   MOV                          channel-1 data
         Even if the temperature measurement data is not stored to D100 or D101, data registers D8260 or D8261 can
         be directly used in the arithmetic operation instruction or a PID instruction.
J-28
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                             5 Troubleshooting
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input)                                 5.1 PLC Version Number Check
                                                                                                                                    Common Items
5.     Troubleshooting
         This chapter describes the troubleshooting methods and error status.                                                   B
         If the temperature measurement data is not input, or if the proper digital value is not input, check the following
                                                                                                                              FX3UC-4AD
                                                                                                                              FX3U-4AD
         items:
         • Version number of the PLC
         • Wiring
         • Special devices
                                                                                                                                C
         • Programs
                                                                                                                                    FX3U-4AD-ADP
         • Error status
                                                                                                                                    FX3G-2AD-BD
         • Check the version number of FX3UC Series. The version number should be 1.30 or later.
         • Any versions (from Ver.1.00 (initial version) to the latest version) of the FX3G Series are compatible.
                        → For a detailed description of the version number check method, refer to Section 1.3.
                                                                                                                                    FX3U-4DA
         Check the following items for wiring:
      1. Power
         The PNK-ADP needs driving power. Verify that the power supply line is properly connected. Also check that
         the POWER indicator lamp of the PNK-ADP is on.                                                                           F
                                                                                                                                    FX3U-4DA-ADP
      2. Resistance thermometer sensor cable
         When using a 2-wire temperature sensor type, short-circuit the [L-] terminal and the [I-] terminal.
         Separate the cable of the resistance thermometer sensor from the other power cables or areas easily affected
         by inductive noise (of the commercial power, etc.).
                                                        → For a detailed description of wiring, refer to Chapter 3.
                                                                                                                               G
5.3      Special Device Check
                                                                                                                                    FX3G-1DA-BD
         Check whether the special devices for the PNK-ADP are correctly used:
      2. Temperature measurement
         Check if the special device of the selected channel is correctly set.
                                                                                                                                       -ADP
This special device should be selected depending on the connecting position and the channel.
      3. Averaging time                                                                                                                 I
         Verify if the set averaging time is within the specified range. The averaging time should be set in the range
                                                                                                                              FX3U-4AD-PTW
from 1 to 4095. If the set averaging time is outside the specified range, an error occurs.
      4. Error status
                                                                                                                                       -ADP
                                                                                                                    J-29
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                               5 Troubleshooting
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input)                                             5.4 Program Check
J-30
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                       5 Troubleshooting
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input)                                   5.5 Error Status Check
                                                                                                                            A
      4. PNK-ADP hardware error (b6)
                                                                                                                                Common Items
         1) Description of error
            The PNK-ADP does not operate properly.
         2) Remedy
            Check that the 24V DC power is properly supplied to the PNK-ADP.
            Also check that the PNK-ADP is correctly connected to the PLC.                                                  B
            If the problem cannot be solved even after the above check, please contact the nearest Mitsubishi
                                                                                                                          FX3UC-4AD
                                                                                                                          FX3U-4AD
            Electric distributor office.
                                                                                                                                FX3U-4AD-ADP
            Check that the PNK-ADP is correctly connected to the PLC.
            If the problem cannot be solved even after the above check, please contact the nearest Mitsubishi
            Electric distributor office.
                                                                                                                                FX3G-2AD-BD
                                                                                                                             E
                                                                                                                                FX3U-4DA
                                                                                                                              F
                                                                                                                                FX3U-4DA-ADP
                                                                                                                           G
FX3G-1DA-BD
                                                                                                                            H
                                                                                                                          FX3U-4AD-PT
                                                                                                                                   -ADP
                                                                                                                                    I
                                                                                                                          FX3U-4AD-PTW
                                                                                                                                   -ADP
                                                                                                                              J
                                                                                                                          FX3U-4AD-PNK
                                                                                                                                   -ADP
                                                                                                               J-31
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition       5 Troubleshooting
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input)   5.5 Error Status Check
MEMO
J-32
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input)
                                                                                                                                 FX3U-4AD-TC
                                                                                                                                          -ADP
                                                                                                                                     L
                                                                                                                                 PID Instruction
                                                                                                                                        (FNC 88)
         FX3G/FX3U/FX3UC Series Programmable
         Controllers
         User's Manual [Analog Control Edition]
         FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input)
         Foreword
         This manual describes the specifications, wiring, and operation methods for the FX3U-4AD-TC-ADP special
         adapter (4-channel thermocouple input) and should be read and understood before attempting to install or
         use the unit.
         Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
         it to the end user.
           This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
           licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
           rights which may occur as a result of using the contents noted in this manual.
                                                                                                                         K-1
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input)
K-2
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                1 Outline
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input)                                                          1.1 Outline of Functions
                                                                                                                                        FX3U-4AD-TC
1.      Outline
                                                                                                                                                 -ADP
           This chapter describes the outline of FX3U-4AD-TC-ADP (referred to as TC-ADP).                                                   L
                                                                                                                                        PID Instruction
1.1        Outline of Functions
                                                                                                                                               (FNC 88)
           The FX3U-4AD-TC-ADP is an analog special adapter. Connect the FX3U-4AD-TC-ADP to the FX3U/FX3UC/
           FX3G Series PLC to read the data from the 4-channel thermocouple.
           1) Up to 4 TC-ADP units can be connected to the FX3U/FX3UC Series PLC.
              Up to 2*1 TC-ADP units can be connected to the FX3G Series PLC.
              (Including other analog special adapters)
           2) Thermocouple types K and J can be connected. (However, it's impossible to use both types K and J with
              1 adapter.)
           3) A/D conversion data will be automatically written to the special data register of the FX3U/FX3UC/FX3G
              Series PLC.
+ + to Section 1.3.
                                                 Expansion
        4th       3rd       2nd       1st
      adapter   adapter   adapter   adapter       board*2
                                                                                                    For a detailed
                                                                                              …… description of wiring,
                 Analog data                                                                        refer to Chapter 3.
   Refer to the system configuration shown in the User's Manual - Hardware Edition to check the number of connectable units
   and to configure the entire system.
  *1. Only 1 analog special adapter can be connected to the 14-point and 24-point type main unit.
  *2. The expansion board is not required when connecting with the FX3UC (D, DSS) PLC.
      For the FX3G Series PLC a connector conversion adapter is used.
                                                                                                                                 K-3
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                       1 Outline
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input)                            1.2 Setup Procedure Before Starting Operation
FX3U-4AD-TC-ADP
Refer to Chapter 1.
                                Wiring                                  Wiring:
                                                                        •Selection of sensor cable
                                                                        •Power supply line
                                          Refer to Chapter 4.           •Analog input line
                            Programming                                 Programming:
                                                                        •Details of special devices
                                                                        •Examples of basic programs
K-4
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                         1 Outline
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input)                                                 1.3 Connectable PLC and Its Version Number
                                                                                                                                                   K
1.3      Connectable PLC and Its Version Number
                                                                                                                                                 FX3U-4AD-TC
         TC-ADP is compatible with the following PLC.
                                                                                                                                                          -ADP
                Compatible PLC               Version number                              Date of production
          FX3U Series PLC                    Ver. 2.20 or later                   After May 2005 (initial production)                                L
                                                                                                                                                 PID Instruction
          FX3UC Series PLC                   Ver. 1.30 or later                           After August 2004
          FX3G Series PLC                    Ver. 1.00 or later                   After June 2008 (initial production)
                                                                                                                                                        (FNC 88)
      1. Version check
         Special data register D8001 contains information for determining the PLC version number.
                            D8001                2     4        1     0       0
                        PLC type and
                       version number                                       Version data (Example: Ver. 1.00)
                                                                      (
                                                        PLC type Example: 24 = FX3U and FX3UC series
                                                                          26 = FX3G series                          )
      2. How to look at the manufacturer's serial number
         The year and month of production of the product can be seen from the manufacturer's serial number
         "SERIAL" indicated on the label adhered to the right side of the product.
                                                  Example:
                                                  FX3U-48MR/ES(production number : 570001)
                                                     MODEL           FX3U-48MR/ES
                                                               100-240VAC 50/60Hz 40W
                                                         OUT:30VDC/240VAC 2A(COSφ=1)
SERIAL 570001
5 7 0 0 0 1
                                                                                       Control number
                                                                          Month (Example: 7 = July), 1 to 9 = January to September,
                                                                          X = October, Y = November, Z = December
                                                                     Year (Example: 5 = 2005), last digit of dominical year
         If a programming tool with the wrong version number is used, programming will not be possible.
          *1.   For Ver. 8.13P to 8.24A of GX Developer, select FX3UC for the PLC type.
                                                                                                                                       K-5
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                       2 Specifications
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input)                                                        2.1 Generic Specifications
2.     Specifications
         This chapter describes the general, power supply, and performance specifications for the TC-ADP.
                  Item                                                   Specifications
                                   0 to 55°C (32 to 131°F) when operating
          Ambient temperature
                                   -25 to 75°C (-13 to 167°F) when stored
          Relative humidity        5 to 95%RH (no condensation) when operating
                                                         Frequency       Acceleration     Half amplitude
                                                            (Hz)             (m/s2)            (mm)
                                                                                                           Tested 10 times in
                                                           10 - 57             -                0.035      each direction (X-, Y-,
          Vibration resistance     DIN Rail Mounting
                                                          57 - 150            4.9                 -        and Z-axis directions)
                                                                                                           (Total: 80 min, each)
                                                          10 to 57             −                0.075
                                   Direct Mounting*1
                                                          57 to 150           9.8                −
                                   147 m/s2 Acceleration, Action time: 11ms, 3 times by half-sine pulse in each direction X, Y,
          Shock resistance
                                   and Z
                                   Using noise simulator of:
          Noise resistance
                                   Noise voltage: 1,000Vp-p / Noise width: 1µs / Rise: 1ns / Cycle: 30 to 100Hz
          Dielectric withstand
                                   500 V AC, for 1 min
          voltage
                                                                       Between batch of all terminals and ground terminal
                                   5MΩ or more using 500V DC
          Insulation resistance
                                   insulation resistance meter
                                   Class D grounding (grounding resistance: 100 Ω or less)
          Grounding
                                   <Common grounding with a heavy electrical system is not allowed.>*2
          Working
                                   Free from corrosive or flammable gas and excessive conductive dusts
          environment
          Working altitude         < 2000m*3
          *1.   If TC-ADP is connected to the FX3UC Series PLC, direct installation is not possible.
          *2.
                      PLC          Other        PLC        Other        PLC           Other
                                 equipment               equipment                  equipment
                      Item                                                  Specifications
          A/D conversion circuit          24V DC +20% -15%, 45mA
          driving power                   (It is necessary to connect a 24V DC power supply to the terminal block.)
                                          5V DC, 15mA
          Interface driving power         (Since the internal power is supplied from the FX Series main unit, it is not
                                          necessary to supply the power.)
K-6
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                              2 Specifications
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input)                                                                           2.3 Performance Specifications
                                                                                                                                                                   K
2.3      Performance Specifications
                                                                                                                                                                 FX3U-4AD-TC
                                                                                                                                                                          -ADP
                                                                                    Specifications
                 Item
                                                      Centigrade (°C)                                                   Fahrenheit (°F)                              L
                                                                                                                                                                 PID Instruction
                                                                            Thermocouple type K or J
          Input signal
                                                                                JIS C 1602-1995
                                                                                                                                                                        (FNC 88)
          Rated temperature   Type K                            -100°C to +1000°C                Type K                         -148°F to +1832°F
          range               Type J                             -100°C to +600°C                Type J                         -148°F to +1112°F
                              Type K                             -1000 to +10000                 Type K                          -1480 to +18320
          Digital output
                              Type J                              -1000 to +6000                 Type J                          -1480 to +11120
                              Type K                                    0.4°C                    Type K                                0.72°F
          Resolution
                              Type J                                    0.3°C                    Type J                                0.54°F
          Total accuracy                                                        ±(0.5% full scale +1°C)
                              • FX3U/FX3UC Series PLC : 200µs (The data will be updated at every scan time.)
          A/D conversion
                              • FX3G Series PLC : 250µs (The data will be updated at every scan time.)
          time
                                                    →For a detailed description of data update, refer to Section2.4.
                                       • Type K                                                     •Type K
                                                    +10100                                                      +18500
                                                    +10000                                                      +18320
                                                                                       +1010°C
                                                                                                                                                +1850° F
                                                 -100°C     0                                                 -148° F    0
                                                                           +1000°C                                                       +1832°F
                                        -110°C
-166° F
                                                                -1000                                                        -1480
          Input                                                 -1100                                                        -1660
          characteristics
                                       •Type J                                                      •Type J
                                                    +6100                                                       +11300
                                                    +6000                                                       +11120
                                                                                                                                                +1130°F
                                                                                    +610°C
                                                -100°C    0                                                   -148°F     0
                                                                           +600°C                                                        +1112°F
                                                                                                    -166°F
                                       -110°C
                                                                -1000                                                        -1480
                                                                -1100                                                        -1660
                              • The photocoupler is used to insulate the analog input area from the PLC.
          Insulation method   • The DC/DC converter is used to insulate the power supply line from the analog input area.
                              • Channels are not insulated from each other.
          Number of I/O                                                 0 points
          points occupied        (This number is not related to the maximum number of input/output points of the PLC.)
                                                                                                                                                           K-7
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                   2 Specifications
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input)                                                      2.4 A/D Conversion Time
                 FX3U-4AD-TC-ADP           FX3U-4AD-TC-ADP
                        n'th                      1st                               FX3U/FX3UC Series PLC
                                                                                          Sequence
                                                                                           program
                                                            A/D conversion start
                                                  A/D            command
                                               conversion
                                                            Digital value writing
                                               200 µs/4ch
                                                            A/D conversion start       END instruction
                        A/D                                      command
                     conversion
                                                            Digital value writing
                     200 µs/4ch
K-8
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                               2 Specifications
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input)                                             2.5 Temperature Measurement
                                                                                                                                K
2.4.2     When connected to a FX3G PLC
                                                                                                                              FX3U-4AD-TC
        1. A/D conversion and special data register update timing
                                                                                                                                       -ADP
          A/D conversion is performed at every scan time of the PLC.
          During execution of END instruction, the PLC performs A/D conversion, reads out the A/D converted data,
          and then writes the data in the special data registers.                                                                 L
                                                                                                                              PID Instruction
                 FX3U-4AD-TC-ADP           FX3U-4AD-TC-ADP
                                                                                    FX3G Series PLC
                                                                                                                                     (FNC 88)
                        2nd                       1st
                                                                                       Sequence
                                                                                        program
                                                            A/D conversion start
                                                  A/D            command
                                               conversion
                                                            Digital value writing
                                               250 µs/4ch
                                                            A/D conversion start    END instruction
                        A/D                                      command
                     conversion
                                                            Digital value writing
                     250 µs/4ch
                                                                                                                     K-9
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                              3 Wiring
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input)
3.     Wiring
         This chapter describes the TC-ADP wiring.
         Observe the following caution to wire the TC-ADP.
WIRING PRECAUTIONS
          • Make sure to cut off all phases of the power supply externally before attempting wiring work.
            Failure to do so may cause electric shock or damages to the product.
WIRING PRECAUTIONS
          • Connect the DC power supply wiring to the dedicated terminals described in this manual.
            If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will be
            burnt out.
          • Do not wire vacant terminals externally.
            Doing so may damage the product.
          • Perform class D grounding (grounding resistance: 100Ω or less) to the grounding terminal on the main unit.
            Do not use common grounding with heavy electrical systems.
          • When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
            Failure to do so may cause fire, equipment failures or malfunctions.
          • Make sure to observe the following precautions in order to prevent malfunctions under the influence of noise:
            - Do not bundle the power line or twisted shielded cable together with or lay it close to the main circuit, high-
                voltage line, or load line.
                Otherwise, noise disturbance and/or surge induction are likely to take place. As a guideline, lay the control line
                at least 100mm (3.94") or more away from the main circuit, high-voltage line, or load line.
            - Ground the shield of the analog input/output cable at one point on the signal receiving side.
                However, do not use common grounding with heavy electrical systems.
          • Make sure to properly wire to the European terminal board in accordance with the following precautions.
            Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product.
            - The disposal size of the cable end should be 9 mm (0.35").
            - Tightening torque should be between 0.22 to 0.25 N•m.
            - Twist the end of strand wire and make sure there are no loose wires.
            - Do not solder-plate the electric wire ends.
            - Do not connect more than the specified number of wires or electric wires of unspecified size.
            - Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
K-10
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                              3 Wiring
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input)                                            3.1 Terminal Layout
                                                                                                                       K
3.1      Terminal Layout
                                                                                                                     FX3U-4AD-TC
         The terminals of the TC-ADP are arranged as follows:
                                                                                                                              -ADP
                                                                                                                         L
                                                                                                                     PID Instruction
                                                                                                                            (FNC 88)
                                          FX3U-4AD-TC
                                                 -ADP
                                              POWER
                                                        Signal         Application
                                                         24+
                          24+
                                                                 External power
                                                         24-
                          24-
                                                                 Ground terminal
                                                           •     Unused
                         • •
                                                         L1-
                          L2+
                                                                                                         K-11
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                  3 Wiring
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input)                             3.2 Applicable Cables and Terminal Tightening Torque
       1. Cables
         Applicable cable and tightening torque
                                 Wire size            Tightening
                                                                                           Termination
                           (stranded/single-wire)       torque
                         0.3 mm2 to 0.5 mm2                        • To connect a stranded cable, peel the cover off the cable
          Single-wire                                                and then twist the core before connection.
                         (AWG22 to 20)
                                                                   • To connect a single-wire cable, just strip the cover off the
          2-wire         0.3mm2(AWG22)                               cable before connection.
                                                      0.22 N•m to • Rod terminal with insulation sleeve
          Rod terminal   0.3 mm2 to 0.5 mm2            0.25 N•m     (recommended terminal)
          with           (AWG22-20)                                 AI 0.5-8WH : Manufactured by Phoenix Contact
          insulation     (Refer to the rod terminal
                                                                  • Caulking tool
          sleeve         external view shown in the
                                                                    CRIMPFOX ZA 3 : Manufactured by Phoenix Contact
                         following figure.)
                                                                    (or CRIMPFOX UD 6 : Manufactured by Phoenix Contact)
       3. Tool
         • To tighten terminals, use a small-sized screwdriver whose head is straight and is not widened as shown in
           the figure to the right.
            Note:
            If the diameter of screwdriver grip is too small, tightening torque will not
                                                                                                                        The head
            be able to be achieved. Use the following recommended screwdriver or                                        should be
            an appropriate replacement (grip diameter: approximately 25mm).                                             straight.
                         Manufacturer                          Model
            Phoenix Contact                                  SZS 0.4×2.5                       0.4mm                    2.5mm
                                                                                               (0.01")                  (0.09")
K-12
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                              3 Wiring
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input)                                                          3.3 Power Supply Line
                                                                                                                                       K
3.3      Power Supply Line
                                                                                                                                     FX3U-4AD-TC
         Connect the 24V DC power supply line of the TC-ADP to the 24+ and 24- terminals of the terminal block.
                                                                                                                                              -ADP
3.3.1    To connect to FX3G, FX3U Series PLC
                                                                                                                                         L
                                                                                                                                     PID Instruction
         1. To use an external power                                       2. To use the 24V DC power of the PLC
                                                                                                                                            (FNC 88)
                 TC-ADP                FX3G/FX3U                                     TC-ADP           FX3G/FX3U
                                       Series PLC                                                     Series PLC
                     +5V               (Main unit)                                       +5V
                                                                                                      (Main unit)
          Terminal                                                          Terminal
          block                                                             block
                                             Class-D                                                 Class-D
                      24V DC                grounding                                               grounding
                                        TC-ADP                                       FX2NC
                                                        FX3UC Series PLC           Series PLC
                                            +5V            (Main unit)          (Input extension
                                                                                     block)
                                                                                         Power
                                                             Power             Power crossover
                                                            connector        connector connector
                                                                         Class-D
                                                     24V DC             grounding
                                                                                                                          K-13
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                               3 Wiring
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input)                                               3.4 Selection of the Thermocouple
         • There are 2 types of thermocouples: K type and J type. When selecting the thermocouple type, make sure
           that the same type of thermocouple is connection to all the channels.
         • Be sure to use a non-grounded thermocouple type.
         • The compensating lead wire indicates a temperature value of approximately 0.12°C higher than that of the
           wire resistor (10Ω). Use the appropriate compensating lead wire when considering this difference.
         • If the compensating lead wire is very long, the wire may be easily affected by noise, etc. It is, therefore,
           recommended for the length of the compensating lead wire to be 100 m or less.
                                                Shield
                                                                        Temperature
                                                                     compensating circuit
                                                                        3kΩ         ch
                                                               L +
                                                               L -
                                                                                            +5V
                                                               24+
                                     24V DC
                                                               24-
                                              Class-D
                                             grounding
          *1.   It is not necessary to connect lines to the J-type terminals. Leave these terminals disconnected.
          *2.   Keep the thermocouple away from inductive noise (commercial power, etc.).
K-14
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                             3 Wiring
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input)                                                  3.6 Caution Regarding Wiring
                                                                                                                                      K
3.5.2    Wiring of the thermocouple type J
                                                                                                                                    FX3U-4AD-TC
                                                 Terminal block
                                                                                                                                             -ADP
                                                                            TC-ADP
                                                             type J
                                                      *1
                            Thermocouple    Compensating
                                                             type J        Temperature
                                                                        compensating circuit                                            L
                            type J*2        lead wire
                                                                                                                                    PID Instruction
                                                                          3kΩ         ch
                                                             L +
                                                             L -
                                                                                                                                           (FNC 88)
                                                 Shield
                                                                           Temperature
                                                                        compensating circuit
                                                                          3kΩ
                                                             L +                       ch
                                                             L -
                                                                                               +5V
                                                              24+
                                        24V DC
                                                              24-
                                               Class-D
                                              grounding
          *1.   To use a J thermocouple type, be sure to connect the thermocouple to these terminals. In addition,
                select J type by turning on the type K/J selection special auxiliary relay.
          *2.   Keep the thermocouple away from inductive noise (commercial power, etc.).
3.7      Grounding
         Grounding should be performed as stated below.
         • The grounding resistance should be 100Ω or less.
         • Independent grounding should be performed for best results.
           When independent grounding is not performed, perform "shared grounding" as shown in the following
           figure.
                               → For details, refer to the User’s Manual - Hardware Edition of the PLC Series.
                                                                                                                        K-15
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                      4 Programming
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input)                                              4.1 Loading of A/D Conversion Data
4.      Programming
          This chapter describes how to create programs that can read out the analog data using the TC-ADP.
               The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the
               next adapter as the 2nd analog special adapter, and so on. However, in this case, do not include the high-
               speed input/output special adapter and the communication special adapter.
K-16
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                     4 Programming
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input)                                             4.1 Loading of A/D Conversion Data
                                                                                                                                       K
         • FX3G Series PLC
                                                                                                                                     FX3U-4AD-TC
                         Communi-
                           cation          Connector
                FX3U-4AD          FX3U-4AD
                                                                                                                                              -ADP
                          special          conversion
                -TC-ADP           -TC-ADP
                          adapter           adapter                           FX3G Series PLC
                  2nd*1                1st
                                                                 Special devices
                                                                                                                                         L
                                                                                                                                     PID Instruction
                                                              Special auxiliary relays:
                                                                M8280 to M8289
                                                                                                                                            (FNC 88)
                                       A/D                    Special data registers:
                                                                D8280 to D8289                    Sequence
                                                                                                  Program
                                                              Special auxiliary relays:
                                                                M8290 to M8299
                   A/D                                        Special data registers:
                                                                D8290 to D8299
            The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the
            next adapter as the 2nd analog special adapter. However, in this case, do not include the connector
            conversion adapter and the communication special adapter.
          *1.    The second special adapter is not available in the 14-point and 24-point type main unit.
                                                                                                                          K-17
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                             4 Programming
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input)                                             4.2 List of Special Devices
K-18
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                              4 Programming
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input)                                                      4.3 Selection of Temperature Unit
                                                                                                                                               K
         • FX3G Series PLC
                                                                                                                                             FX3U-4AD-TC
                                                                                                                      R: Read / W: Write
                                        Device number
             Special device                                                  Description                    Attribute        Refer to
                                                                                                                                                      -ADP
                                         1st         2nd
                                        M8280       M8290     Selects the temperature unit                    R/W          Section 4.3
                                                              Switches the thermocouple type
                                                                                                                                                 L
                                        M8281       M8291                                                     R/W          Section 4.4
                                                                                                                                             PID Instruction
          Special auxiliary relay                             between type K and type J
                                    M8282 to M8292 to
                                                                                                                                                    (FNC 88)
                                                      Unused (Do not use.)                                        -             -
                                     M8289    M8299
                                                              Channel-1 temperature measurement
                                        D8280       D8290                                                         R
                                                              data
                                                              Channel-2 temperature measurement
                                        D8281       D8291                                                         R
                                                              data
                                                                                                                           Section 4.5
                                                              Channel-3 temperature measurement
                                        D8282       D8292                                                         R
                                                              data
                                                              Channel-4 temperature measurement
                                        D8283       D8293                                                         R
                                                              data
                                                              Averaging time for channel 1
          Special data register         D8284       D8294                                                     R/W
                                                              (Setting range: 1 to 4095)
                                                              Averaging time for channel 2
                                        D8285       D8295                                                     R/W
                                                              (Setting range: 1 to 4095)
                                                                                                                           Section 4.6
                                                              Averaging time for channel 3
                                        D8286       D8296                                                     R/W
                                                              (Setting range: 1 to 4095)
                                                              Averaging time for channel 4
                                        D8287       D8297                                                     R/W
                                                              (Setting range: 1 to 4095)
                                        D8288       D8298     Error status                                    R/W          Section 4.7
                                        D8289       D8299     Model code = 10                                     R        Section 4.8
                                                                                                                                    K-19
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                     4 Programming
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input)                                                    4.4 Selection of Type K or J
K-20
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                 4 Programming
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input)                                             4.5 Temperature Measurement
                                                                                                                                K
4.5      Temperature Measurement
                                                                                                                              FX3U-4AD-TC
         The temperature data input in the TC-ADP will be stored in the special data registers.
                                                                                                                                       -ADP
         The special data registers that store the temperature data are shown in the following table:
         • FX3U, FX3UC Series PLC
                                                                                                                                  L
                        Special data register
                                                                                                                              PID Instruction
                                                                                  Description
             1st          2nd         3rd         4th
                                                                                                                                     (FNC 88)
            D8260        D8270      D8280        D8290     Stores the channel-1 temperature measurement data.
            D8261        D8271      D8281        D8291     Stores the channel-2 temperature measurement data.
            D8262        D8272      D8282        D8292     Stores the channel-3 temperature measurement data.
            D8263        D8273      D8283        D8293     Stores the channel-4 temperature measurement data.
         The immediate data or the average data (data averaged in accordance with the specified averaging time) will
         be stored in the above data registers as the temperature measurement data.
                                          → For a detailed description of the averaging time, refer to Section 4.6.
         Even if the temperature measurement data is not stored in D100 or D101, data registers D8260 or D8261 can
         be directly used in the arithmetic operation instruction or a PID instruction.
                                                                                                                    K-21
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                        4 Programming
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input)                                                               4.6 Averaging Time
                                          FNC 12      K128        D8265        Sets the averaging time to "128" for the channel-2
                                           MOV                                 data of the 1st analog special adapter.
K-22
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                            4 Programming
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input)                                                                       4.7 Error Status
                                                                                                                                               K
4.7      Error Status
                                                                                                                                             FX3U-4AD-TC
         If an error is detected on TC-ADP, the error status data will be stored in the corresponding special data
                                                                                                                                                      -ADP
         register.
         The following table shows the special data registers that store the error status data:
         • FX3U, FX3UC Series PLC                                                                                                                L
                                                                                                                                             PID Instruction
                              Special data register
                                                                                                  Description
                                                                                                                                                    (FNC 88)
                 1st           2nd             3rd             4th
             D8268           D8278            D8288           D8298         Stores the error status data.
         Check the ON/OFF status of each bit of the error status data register to determine the error. Errors are
         assigned to the bits as shown in the following table. Create a program to detect errors.
            M8000
                                        MOV          D8288    K4M0
           Normally
           ON
            M8002                                                           Error status in the 3rd*1 analog special adapter
                                                     RST       M6           b6 = OFF (hardware error)
           Initial pulse
                                                                                                                                 K-23
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                              4 Programming
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input)                                                        4.7 Error Status
                 M8000
                                        MOV   D8288     K4M0
                   M0
                                                         Y000     The temperature measurement data
                                                                  of channel 1 is outside the specified
                                                                  range, or disconnection is detected.
                   M1
                                                         Y001     The temperature measurement data
                                                                  of channel 2 is outside the specified
                                                                  range, or disconnection is detected.
                   M2
                                                         Y002     The temperature measurement data
                                                                  of channel 3 is outside the specified
                                                                  range, or disconnection is detected.
                   M3
                                                         Y003     The temperature measurement data
                                                                  of channel 4 is outside the specified
                                                                  range, or disconnection is detected.
                   M4
                                                         Y004     EEPROM error in 3rd*1 adapter
                   M5
                                                         Y005     Averaging time setting error in 3rd*1
                                                                  adapter
                   M6
                                                         Y006     TC-ADP hardware error in 3rd*1
                                                                  adapter
                   M7
                                                         Y007     TC-ADP communication data error
                                                                  in the 3rd*1 adapter
K-24
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                           4 Programming
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input)                                                    4.7 Error Status
                                                                                                                            K
      3. Program Example 2 (For FX3U, FX3UC Series PLC)
                                                                                                                          FX3U-4AD-TC
             D8268.0
                                                                                                                                   -ADP
                                                        Y000   The temperature measurement data
                                                               of channel 1 is outside the specified
             D8268.1
                                                               range, or disconnection is detected.                           L
                                                                                                                          PID Instruction
                                                        Y001   The temperature measurement data
                                                               of channel 2 is outside the specified
                                                                                                                                 (FNC 88)
                                                               range, or disconnection is detected.
             D8268.2
                                                        Y002   The temperature measurement data
                                                               of channel 3 is outside the specified
                                                               range, or disconnection is detected.
             D8268.3
                                                        Y003   The temperature measurement data
                                                               of channel 4 is outside the specified
                                                               range, or disconnection is detected.
             D8268.4
                                                        Y004   EEPROM error in 1st adapter
             D8268.5
                                                        Y005   Averaging time setting error in 1st
                                                               adapter
             D8268.6
                                                        Y006   TC-ADP hardware error in 1st
                                                               adapter
             D8268.7
                                                        Y007   TC-ADP communication data error
                                                               in the 1st adapter
                                                                                                              K-25
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                               4 Programming
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input)                                                        4.8 Model Code
Use the above special data registers to check whether TC-ADP is connected or not.
                  FNC224    D8269     K10                    Y010     Checks the model code of the 1st
                   LD =                                               analog special adapter.
K-26
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                   4 Programming
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input)                                                   4.9 Basic Program Example
                                                                                                                                    K
4.9      Basic Program Example
                                                                                                                                  FX3U-4AD-TC
         Create the following basic program to read out the temperature measurement data.
                                                                                                                                           -ADP
         • For FX3G, FX3U, FX3UC Series PLCs
         The following program will select thermocouple type K and will store the temperature measurement data (°C)
         of channels 1 and 2 of the 3rd*1 adapter in the D100 and the D101, respectively. The averaging time will be
                                                                                                                                      L
                                                                                                                                  PID Instruction
         set to "32" for channel 1, and "128" for channel 2.
                                                                                                                                         (FNC 88)
                    M8000
                                  MOV       D8288     K4M0
                    Normally
                    ON
                    M8002                                       Error status of 3rd*1 analog special
                                             RST       M6       adapter
                                                                b6 = OFF (hardware error)
                     Initial
                     pulse                                      Error status of 3rd*1 analog special
                                             RST       M7       adapter
                                                                b7 = OFF (communication data error)
                     M8001
                                                      M8280     Sets the temperature unit to
                                                                centigrade (°C)
                     M8002
                                   FNC 12     K32    D8284      Sets the averaging time to "32" for
                                    MOV                         channel-1 data
         Even if the temperature measurement data is not stored to D100 or D101, data registers D8280 or D8281 can
         be directly used in the arithmetic operation instruction or a PID instruction.
          *1.   "1st" for the FX3G PLC.
                                                                                                                       K-27
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                    4 Programming
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input)                                                    4.9 Basic Program Example
                    M8002
                                   FNC 12     K32     D8264      Sets the averaging time to "32" for
                                    MOV                          channel-1 data
         Even if the temperature measurement data is not stored to D100 or D101, data registers D8260 or D8261 can
         be directly used in the arithmetic operation instruction or a PID instruction.
K-28
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                             5 Troubleshooting
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input)                                            5.1 PLC Version Number Check
                                                                                                                              FX3U-4AD-TC
5.     Troubleshooting
                                                                                                                                       -ADP
         This chapter describes the troubleshooting methods and error status.                                                     L
         If the temperature measurement data is not input, or if the proper digital value is not input, check the following
                                                                                                                              PID Instruction
         items:
                                                                                                                                     (FNC 88)
         • Version number of the PLC
         • Wiring
         • Special devices
         • Programs
         • Error status
      1. Power
         The TC-ADP needs driving power. Verify that the power supply line is properly connected. Also check that the
         POWER indicator lamp of the TC-ADP is on.
      2. Thermocouple cable
         Use a non-grounded type thermocouple and connect the thermocouple using the compensating lead wire.
         In addition, separate the cable of the thermocouple from the other power cables or inductive cables.
      1. Selection of type K or J
         Check if the special device for type K/J selection is correctly set.
         Turn off the device to select thermocouple type K. Turn on the device to select thermocouple type J.
      2. Temperature measurement
         Check if the special device of the selected channel is correctly set.
         This special device should be selected depending on the connecting position and the channel.
      3. Averaging time
         Verify if the set averaging time is within the specified range. The averaging time should be set in the range
         from 1 to 4095. If the set averaging time is outside the specified range, an error occurs.
      4. Error status
         Check that no error is detected in the TC-ADP.
         If an error is detected, check the details of the error, and then check the wiring and programs.
                                                 → For a detailed description of special devices, refer to Chapter 4.
                                                                                                                   K-29
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                              5 Troubleshooting
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input)                                                       5.4 Program Check
K-30
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                       5 Troubleshooting
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input)                                              5.5 Error Status Check
                                                                                                                            K
      4. TC-ADP hardware error (b6)
                                                                                                                          FX3U-4AD-TC
         1) Description of error
            The TC-ADP does not operate properly.
                                                                                                                                   -ADP
         2) Remedy
            Check that the 24V DC power is properly supplied to the TC-ADP.
            Also check that the TC-ADP is correctly connected to the PLC.                                                     L
            If the problem cannot be solved even after the above check, please contact the nearest Mitsubishi
                                                                                                                          PID Instruction
            Electric distributor office.
                                                                                                                                 (FNC 88)
      5. TC-ADP communication data error (b7)
         1) Description of error
            A communication error is detected between the TC-ADP and the PLC.
         2) Remedy
            Check that the TC-ADP is correctly connected to the PLC.
            If the problem cannot be solved even after the above check, please contact the nearest Mitsubishi
            Electric distributor office.
                                                                                                              K-31
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition   5 Troubleshooting
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input)          5.5 Error Status Check
MEMO
K-32
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
PID Instruction (FNC 88)
                                                                                                                                 FX3U-4AD-TC
                                                                                                                                          -ADP
                                                                                                                                     L
                                                                                                                                 PID Instruction
                                                                                                                                        (FNC 88)
         FX3G/FX3U/FX3UC Series Programmable
         Controllers
         User's Manual [Analog Control Edition]
         PID Instruction (FNC 88)
         Foreword
         This manual describes the control methods for using the PID instruction in combination with analog products
         and should be read and understood before attempting to install or use the unit.
         Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
         it to the end user.
           This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
           licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
           rights which may occur as a result of using the contents noted in this manual.
                                                                                                                          L-1
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
PID Instruction (FNC 88)
L-2
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                           1 Outline
PID Instruction (FNC 88)                                                                                1.1 Outline of function
                                                                                                                                  FX3U-4AD-TC
1.      Outline
                                                                                                                                           -ADP
          This chapter describes the outline of PID instruction (FNC88) for the FX3U/FX3UC/FX3G Series PLC.                           L
                                                                                                                                  PID Instruction
1.1       Outline of function
                                                                                                                                         (FNC 88)
          The PID instruction requires the system to calculate the output (MV) value from the measured (PV) value.
          Through combining the P (proportional) action, I (integral) action, and D (derivative) action the target (SV)
          value can be obtained. See diagram below.
          1) Alarm output function
             The alarm function can be set for input variation (measured value) or output variation (value).
          2) Setting limit values
             The upper limit and lower limit can be set for the output value.
          3) Auto-tuning function
             The proportional gain (KP), integral time (TI) and differential time (TD) can be set automatically for both
             the limit cycle method and step response method.
          4) Operation method of the PID instruction
             Both PID speed type operation and measured value differential type operation are executed.
                    Target value
                       (SV)
                                                                                          Controlled
                                     PID Instruction                                       object
                                                                                                                       L-3
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                      1 Outline
PID Instruction (FNC 88)                                                    1.2 Basic Operation Expressions in PID Instruction (Reference)
                                                                       TS
                                          ∆MV = KP{(EVn − EVn-1) +           EVn + Dn}
                                                                       TI
          Forward operation               EVn = PVnf-SV
          (OFF)                                     TD                                    KD TD
                                          Dn  =            (−2PVnf−1 + PVnf + PVnf−2) +                            Dn-1
                                                TS + KD TD                              TS + KD TD
                                          MVn = Σ∆MV
                                                                        TS
                                           ∆MV = KP{(EVn − EVn−1) +           EVn + Dn}
                                                                        TI
          Backward                         EVn = SV − PVnf
          operation (ON)                             TD                                   KD TD
                                           Dn =             (2PVnf−1 − PVnf − PVnf−2) +            Dn-1
                                                 TS + KD TD                             TS + KD TD
                                           MVn = Σ∆MV
          1) Symbols
             EVn       : Deviation in sampling at this time                           Dn       : Differential term at this time
             EVn-1     : Deviation in previous cycle                                  Dn-1     : Differential term in previous cycle
             SV        : Target value                                                 KP       : Proportional gain
             PVnf      : Measured value in sampling at this time (after filter)       TS       : Sampling cycle
             PVnf-1    : Measured value in previous cycle (after filter)              TI       : Integral constant
             PVnf-2    : Measured value in two cycles before (after filter)           TD       : Differential constant
             ∆MV       : Output variation                                             KD       : Differential gain
             MVn       : Operation quantity at this time
          2) Expression for calculating the measured value (after the filter) in sampling at this time (PVnf)
             The value "PVnf" is obtained from the following expression based on the read measured value.
L-4
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                         2 How to Use PID Instruction
PID Instruction (FNC 88)                                                                               2.1 Explanation of function and operation
                                                                                                                                                   FX3U-4AD-TC
2.       How to Use PID Instruction
                                                                                                                                                            -ADP
      1. Instruction format                                                                                                                            L
                                                                                                                                                   PID Instruction
                                     16-bit   Mnemonic Operation Condition                      32-bit   Mnemonic Operation Condition
              FNC 88              lnstruction                                                lnstruction
               PID                                          Continuous
                                                                                                                                                          (FNC 88)
                                      9 steps PID                                                           ⎯
                  PID
                                                            Operation
      2. Set data
            Operand type                                               Description                                             Data type
      3. Target devices
                           Bit devices                                     Word devices                                       Others
                                                                                                                            Real Char-
                                                                                             Special                  Con-              Poin-
          Operand          System User           Digit Specification       System User                     Index            Num- acter
                                                                                              Unit                    stant
           type                                                                                                              ber String ter
                                                                                                               Mod-
                      X Y M T C S D .b KnX KnY KnM KnS T                      C      D   R   U \G      V   Z        K H       E    " "       P
                                                                                                                ify
S1 S
S2 S
S3
D S
                                                                                                                                         L-5
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                2 How to Use PID Instruction
PID Instruction (FNC 88)                                                     2.2 Relationship Between Parameter Setting and Auto-Tuning
L-6
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                          3 Parameter
PID Instruction (FNC 88)                                                                                    3.1 Parameter List: (S3) to (S3) + 28
                                                                                                                                                    FX3U-4AD-TC
3.      Parameter
                                                                                                                                                             -ADP
           This chapter describes various parameters of PID instruction.                                                                                L
                                                                                                                                                    PID Instruction
3.1        Parameter List: (S3) to (S3) + 28
                                                                                                                                                           (FNC 88)
                 Set item                                         Setting                              Remarks                     Reference
                                                                                          It cannot be shorter than operation Subsection
  S3         Sampling time (TS)                   1 to 32767 (ms)
                                                                                          cycle of the PLC.                     3.2.1
                                                  0: Forward operation
                                  bit0                                                    Operation direction
                                                  1: Backward operation
                                                  0: Input variation alarm is invalid.
                                  bit1
                                                  1: Input variation alarm is valid.
                                                  0: Output variation alarm is invalid.   Do not set to ON bit 2 and bit 5 at
                                  bit2
                                                  1: Output variation alarm is valid.     same time.
                                  bit3            Not available
             Operation                            0: Auto-tuning is not executed.                                                  Subsection
  S3 +1                           bit4
             setting (ACT)                        1: Auto-tuning is executed.                                                        3.2.2
                                                  0: Upper and lower limits of output
                                                     value are not valid.             Do not set to ON bit 2 and bit 5 at
                                  bit5
                                                  1: Upper and lower limits of output same time.
                                                     value are valid.
                                                  0: Step response method
                                  bit6                                                    Select auto-tuning mode.
                                                  1: Limit cycle method
                                  bit7 to bit15   Not available
                                                                                          When "0" is set, input filter is not Subsection
  S3 +2      Input filter constant (α)            0 to 99 (%)
                                                                                          provided.                              3.2.3
                                                                                                                                   Subsection
  S3 +3      Proportional gain (KP)               1 to 32767 (%)
                                                                                                                                     3.2.4
                                                                                          When "0" is set, it is handled as "∞" Subsection
  S3 +4      Integral time (TI)                   0 to 32767 (× 100 ms)
                                                                                          (no integration).                       3.2.5
                                                                                          When "0" is set, differential gain is Subsection
  S3 +5      Differential gain (KD)               0 to 100 (%)
                                                                                          not provided.                           3.2.6
                                                                                          When "0" is set, differential is not Subsection
  S3 +6      Differential time (TD)               0 to 32767 (× 10 ms)
                                                                                          executed.                              3.2.7
  S3 +7
  :          These devices are occupied for internal processing of PID operation. Do not change data.                                   ⎯
  S3 +19
                                                                                                                                         L-7
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                       3 Parameter
PID Instruction (FNC 88)                                                                                  3.1 Parameter List: (S3) to (S3) + 28
             *1.     S3 +20 to +24 become occupied only if bits 1, 2, or 5 are set to "1" to determine the action (ACT) of
                     S3 +1.
L-8
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                            3 Parameter
PID Instruction (FNC 88)                                                                                  3.2 Details of Parameters
                                                                                                                                      FX3U-4AD-TC
3.2.1     Sampling time (TS): (S3)
                                                                                                                                               -ADP
                                                                                       Setting range: 1 to 32767 [ms]
          Set the cycle time (ms) for the PID operation.
                                                                                                                                          L
                                                                                                                                      PID Instruction
          • In the PID control
            Set the sampling time longer than the operation cycle of the PLC.
                                                                                                                                             (FNC 88)
          • In the auto-tuning
            Set the sampling time to 1,000 ms (= 1 second) or more.
        1. Maximum error
          The maximum error of the sampling time (TS) is from "-(one operation cycle + 1 ms)" to "+(one operation
          cycle)."
          1) When the sampling time (TS) is a small value
             Fluctuation of the maximum error described above may cause a problem.
             In such a case, execute the PID instruction in the constant scan mode, or program it in a timer interrupt
             routine.
          2) When the sampling time (TS) is shorter than one operation cycle of the PLC
             A PID operation error (K6740) occurs, however when PID operation is executed, the sampling time (TS) is
             equal to the operation cycle of the PLC.
             In such a case, use the PID instruction in a timer interrupt (I6 to I8  ), and clear S3 +7 just before
             executing the PID instruction.
          → For a detailed description, refer to FX3U/FX3UC/FX3G Series Programming Manual - Basic & Applied
                                                                                                 Instruction Edition
                                                               S3 +7 is reset.
                     X000                                    (When the interrupt routine is executed for the
                                 FNC 12      K 0     D107
              I610                                           first time,the register for internal processing is
                                 MOVP
                                                             cleared by the pulse generation command.)
                                                                                                                           L-9
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                        3 Parameter
PID Instruction (FNC 88)                                                                              3.2 Details of Parameters
Time
Time
          Relationship between the forward/backward operation and the output (MV), measured value (PV) and
          target value (SV)
          The relationship is as follows.
                                                     Target value (SV)
                         Output (MV)
                                        Backward                    Forward
                                        operation                   operation
L-10
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                     3 Parameter
PID Instruction (FNC 88)                                                                                           3.2 Details of Parameters
      2. Alarm setting (for input variation and output variation):                        S3   +1, bit 1 and bit 2
                                                                                                                                                 K
                                                                                                                                               FX3U-4AD-TC
                                                                                                   Setting range: OFF, ON
          The input variation and output variation can be checked arbitrarily.
          These parameters can be set in S3 +24.
                                                                                                                                                        -ADP
                            → For the operation of upper/lower limit alarm output for the input and output values,
                                                                                         refer to Subsection 3.2.8.
                                                                                                                                                   L
                                                                                                                                               PID Instruction
          Input variation: S3 +1, bit 1
          When using the input variation alarm, it is necessary to set to ON the following bits and set the values to be
                                                                                                                                                      (FNC 88)
          checked.
                                                     Set item                                                   Setting (setting range)
          Operation setting                                                                                  ON: Used
                                 S3 +1     bit1      Input variation alarm
          (ACT)                                                                                              OFF: Not used
          Input variation        S3 +20              Input variation (incremental) alarm set value           0 to 32767
          alarm set value                            Input variation (decremental) alarm set value           0 to 32767
                                 S3 +21
          Output variation       S3 +22              Output variation (incremental) alarm set value          0 to 32767
          alarm set value                            Output variation (decremental) alarm set value          0 to 32767
                                 S3 +23
                      Output value
                                                     When the upper limit and lower                          These values
                                                     limit of output value are not set                       are not output.
                S3 +22
            Output value
             upper limit
                S3 +23
            Output value
              lower limit                                                                                    These values
                                                                                                             are not output.
                              When the upper limit and lower
                              limit of output value are set
                                                                                                         Time
                                                                                                                                   L-11
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                             3 Parameter
PID Instruction (FNC 88)                                                                                   3.2 Details of Parameters
          Because the input filter (α) is effective to the target value (SV), all of the proportional operation, integral
          operation and differential operation are affected.
                                                                                  Input amplitude
            Measured                                                                             Input amplitude
            value (PV)                                                                   processed by input filter
            processed by
            input filter
L-12
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                              3 Parameter
PID Instruction (FNC 88)                                                                                    3.2 Details of Parameters
                                                                                                                                        FX3U-4AD-TC
                                                                                            Setting range: 1 to 32767[%]
                                                                                      PID control: Proportional operation
                                                                                                                                                 -ADP
          During the proportional operation, the output (MV) increases in proportion to the deviation (difference
          between the target value (SV) and the measured value (PV)).
          This deviation is called proportional gain (Kp), and expressed in the following relational expression:                            L
                                                                                                                                        PID Instruction
               Output (MV) = Proportional gain (KP) x Deviation (EV)
                                                                                                                                               (FNC 88)
          The reciprocal of the proportional gain (KP) is called proportional band.
          As the proportional gain (KP) is larger (as shown in the example below), the motion to let the measured value
          (PV) be nearer to the target value (SV) becomes stronger.
                                                                                 Time
                    Output (MV)
                                                                  Proportional gain
                                                                  KP3 > KP2 > KP1
                                    KP3         KP2         KP1
Time
                                                                  Proportional gain
                                                                  KP3 > KP2 > KP1
                                  KP3         KP2     KP1
                                                                                Measured value (PV)
                                                                  Proportional gain
                                                                  KP3 > KP2 > KP1
                                   KP3         KP2      KP1
Time
                                    Setting range: 0 to 32767 [ × 100 ms] "0" is handled as "∞" (no integration).
                                                                                PID operation: Integral operation
          During the integral operation, the time after deviation is generated until the integral operation output becomes
          the proportional operation output. This is called integral time and is expressed as "TI".
          As TI becomes smaller, the integral operation becomes stronger.
                                                                                                                            L-13
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                                          3 Parameter
PID Instruction (FNC 88)                                                                                                               3.2 Details of Parameters
Time
Time
                             TI3          TI2
                          Target                        TI1
                                                                                                  Measured value in proportional operation
                          value(SV)
                                                                                                  Measured value in PI operation
Time
Time
          Important point
          The integral operation changes the output so that the continuously generated deviation is eliminated.
          As a result, the remaining deviation generated in the proportional operation can be eliminated.
           Deviation
Deviation(EV)
Time
                                                                                Output of
                                                                                "proportional operation + integral operation"
Time
L-14
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                             3 Parameter
PID Instruction (FNC 88)                                                                                   3.2 Details of Parameters
                                                                                                                                       FX3U-4AD-TC
                                                                                                Setting range: 0 to 100[%]
                                                                                         PID control: Differential operation
                                                                                                                                                -ADP
          The filter is applied to the output at the differential operation.
          Only the differential operation is affected by the differential gain (KD).
          • When the differential gain (KD) is small, the output is immediately given with regard to changes in the
                                                                                                                                           L
                                                                                                                                       PID Instruction
            measured value (PV) caused by disturbance, etc.
          • When the differential gain (KD) is large, the output is given after a long time with respect to changes in the
                                                                                                                                              (FNC 88)
            measured value (PV) caused by disturbance, etc.
          Important points
          Set the differential gain (KD) to "0", and then adjust the operation using the input filter (α).
          If the output response is too close to the disturbance, increase the differential gain (KD).
                            Disturbance
                                               TD1 (PID operation)      Deviation (EV)
                                          TD2 (PID operation)
                                                                                            Time
              Output (MV)
Time
                                                                                                                           L-15
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                      3 Parameter
PID Instruction (FNC 88)                                                                            3.2 Details of Parameters
                                                                                   Time
               Output (MV)
Time
Time
Time
L-16
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                 3 Parameter
PID Instruction (FNC 88)                                                                                       3.2 Details of Parameters
                                                                                                                                           FX3U-4AD-TC
          When the input variation [ S3 +1, bit 1] is set to 1
                                                                                                                                                    -ADP
                                                                                        Variation
                                                                                                                                               L
                               Measured value (PV)
                                                                                                                                           PID Instruction
                                                                                                                                                  (FNC 88)
                                                                                                              Time
                                                     Sampling time (TS)
                  Alarm flag
                                                                                   ON
                  S3   +24
                         bit0
                                                                                                         ON
                  S3   +24
                         bit1
                                                                  Variation
                               Output (MV)
Variation
                                                                                                              Time
                                                     Sampling time (TS)
                  Alarm flag
                                                                              ON
                  S3   +24
                         bit2
                                                                                               ON
                  S3   +24
                         bit3
                                                                                                                               L-17
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                  4 Auto-Tuning
PID Instruction (FNC 88)                                                                             4.1 Limit Cycle Method
4.      Auto-Tuning
          This chapter describes the auto-tuning function of PID instruction.
          The auto-tuning function will automatically set the important constants, such as the proportional gain and the
          integral time, to ensure optimum PID control.
          There are two auto-tuning methods: limit cycle method and step response method.
L-18
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                               4 Auto-Tuning
PID Instruction (FNC 88)                                                                       4.1 Limit Cycle Method
                                                                                                                         FX3U-4AD-TC
   1      Set the forward or backward operation
                                                                                                                                  -ADP
          Set the operation direction flag (bit 0) in the operation setting parameter (ACT)   S3   +1.
                                                                                                                             L
   2      Select the auto-tuning method (limit cycle method)
                                                                                                                         PID Instruction
          Set the auto-tuning method to ON (bit 6) in the operation setting parameter (ACT)              +1.
                                                                                                                                (FNC 88)
                                                                                                   S3
          (When bit 6 is set to OFF, the step response method is selected.)
                                                                                                               L-19
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                         4 Auto-Tuning
PID Instruction (FNC 88)                                                                                                  4.1 Limit Cycle Method
4.1.3       Reference: How to obtain three constants in PID control (limit cycle method)
            For acquiring satisfactory control results in PID control, it is necessary to obtain the optimal value of each
            constant (parameter) suitable to the control target.
            This paragraph explains the limit cycle method to obtain the amplitude (a) and vibration cycle (τ, τon) of the
            input value, and then calculate the proportional gain (KP), integral time (TI) and differential time (TD) based on
            the expressions shown in the table below.
Output value
            ULV
        (Output upper
         limit value)
           LLV                                                          τon
                                                      50 × τ on 1 -
        (Output lower                                                    τ
         limit value)
                                                                                                                                Time
Input value
       SV+SHPV
       SV(target value)                                                                                                                a
       SV-SHPV
                                                                              τ
                                                                                       τ on               τw
                                                                   τ0             τ1                 τ2                   Time(s)
L-20
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                       4 Auto-Tuning
PID Instruction (FNC 88)                                                                                             4.2 Step Response Method
                                                                                                                                                 FX3U-4AD-TC
4.2.1     Parameters to be set by auto-tuning (step response method)
                                                                                                                                                          -ADP
                    Parameter
           Operation setting (ACT)
                                                 Setting position                              Parameter
                                                                                       Integral time (TI)
                                                                                                                         Setting position
                                                                                                                                                     L
                                        S3 +1, bit 0 (operation direction)                                            S3 +4
                                                                                                                                                 PID Instruction
           Proportional gain (KP)       S3 +3                                          Differential time (TD)         S3 +6
                                                                                                                                                        (FNC 88)
4.2.2     Auto-tuning procedure
          Set the output value for auto-tuning to the maximum available output value multiplied by 0.5 to 1 for
          the output equipment.
   2      Setting the parameter S3 , target value (SV), etc. that cannot be set in auto-
          tuning according to the system
          Note that auto-tuning may not be executed normally if the cautions described below are not fol-
          lowed
        1. Set items
                    Set item and parameter                                                   Remarks
                                                      The difference from the measured value (PV) should be 150 or more.
           Target value (SV)              S1
                                                      (For the details, refer to "2. Cautions on setting" below.)
           Sampling time (TS)             S3          1,000 ms or more (For the details, refer to "2. Cautions on setting" below.)
           Input filter (α)              S3 +2
           Differential gain (KD)        S3 +5        When setting the input filter, set the differential gain to "0" usually.
           Others                                     Set other items, as necessary.
        2. Cautions on setting
          1) Difference between the target value (SV) and the measured value (PV)
             If the difference between the target value (SV) and the measured value (PV) is less than 150 when auto-
             tuning is started, auto-tuning is not executed normally.
             Accordingly, if the difference is less than 150, set the target value for auto-tuning.
             Set the target value again when auto-tuning is completed.
                      Set item       Setting in PID instruction
                                                                      Make sure that the difference from the measured value is 150 or
                Target value (SV)                S1
                                                                      more when auto-tuning is started.
        1. Important point
          Start auto-tuning while the system is stable.
          If the system is unstable when auto-tuning is started, auto-tuning may not be executed normally.
                                                                                                                                     L-21
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                              4 Auto-Tuning
PID Instruction (FNC 88)                                                                         4.3 Cautions on Auto-Tuning Execution
4.2.3     Reference: How to obtain three constants in PID control (step response method)
          For acquiring satisfactory control results during PID control, it is necessary to obtain the optimal value of each
          constant (parameter) suitable for the control target.
          This paragraph explains the step response method to obtain three constants in the PID control (proportional
          gain (KP), integral time (TI) and differential time (TD)).
Operation characteristics
                     100%
            Output value                                    Output value (MV)
                          0%
                                                                     Time
            Input value
            variation                                          Maximum ramp (R)
                                                                    Time (s)
                                    Dead time (L)   1 (s)
                                              [s]
        1. Countermeasures with in the program when the input value (PV) does not change
          When the input value (PV) does not change normally due to factors such as wire breakage in an analog input
          line, auto-tuning is not finished.
          Detect and avoid such occurrences by introducing a sequence to monitor the input value or the elapsed time
          from the start of auto-tuning.
L-22
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                               5 Example of Practical Programs (for Step Response Method)
PID Instruction (FNC 88)                                                                                            5.1 Example: System and operation
                                                                                                                                                        FX3U-4AD-TC
5.      Example of Practical Programs (for Step Response Method)
                                                                                                                                                                 -ADP
          The following is an example of a program for the operation application system shown below.                                                        L
                                                                                                                                                        PID Instruction
5.1       Example: System and operation
                                                                                                                                                               (FNC 88)
          System configuration
                       Temperature sensor       Shielded compensating
                       (Thermocouple)           conductor
                                                                                     X10 X11
                                                                                                                      ch2
                                                                                 FX3U-32MR/ FX2N-16EYT-
                                                                                                                     FX2N-4AD-
                                                                                     ES      ESS/UL*1
                                                                                                                        TC
                                                                                                      COM Y20 Y21
                       Temperature
                                                                                                               Error indication
                         chamber
          Setting contents
                                                                                                                      During auto-     During PID
                                                                 Item
                                                                                                                        tuning          control
          Target value                                                                       S1                        500 (+50°C)     500 (+50°C)
                                                                                                                           2000
                       Output value upper limit                                              S3 +22                                       2000
                                                                                                                       (2 seconds)
                       Output value lower limit                                              S3 +23                         0               0
OFF ON ON ON ON ON
1.8 sec (1800 ms) 1.8 sec (1800 ms) 1.8 sec (1800 ms)
                                                                                                                                            L-23
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition               5 Example of Practical Programs (for Step Response Method)
PID Instruction (FNC 88)                                     5.2 Program example of auto-tuning (step response method) and PID control
5.2 Program example of auto-tuning (step response method) and PID control
         Initial pulse
          M8002
                                                   FNC 12   K500         D500       The target value is set (to 50°C).
                                                    MOV
         Initial pulse
          M8002                                                                     The mode of FX2N-4AD-TC is set.
                                  FNC 79     K0       K0    H3303        K1         Ch 1: Unused Ch 3: Unused
                                    TO                                              Ch 2: K type  Ch 4: Unused
         RUN monitor
         M8000
                                  FNC 78     K0      K 10   D501         K1         Data is read from the channel 2 in
                                  FROM                                              FX2N-4AD-TC.
         Initial pulse
          M8002
                                                            RST          D502       The PID operation is initialized.
         PID control is
         started after    PID control is started
         auto-tuning      (without auto-tuning)
          X010                X011
L-24
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition               5 Example of Practical Programs (for Step Response Method)
PID Instruction (FNC 88)                                      5.2 Program example of auto-tuning (step response method) and PID control
                                                                                                                                          FX3U-4AD-TC
           Auto-tuning ON flag
             M1
                                                                                                                                                   -ADP
                                                     FNC 12                             Auto-tuning operation is
                                                                D511     K2M10          confirmed.
                                                      MOV
                           Auto-tuning ON flag                                                                                                L
                            M14
                                                                                                                                          PID Instruction
                                                               PLF          M2          Auto-tuning is finished.
                                                                                                                                                 (FNC 88)
                           Auto-tuning is finished
                            M2
                                                               RST          M1          The normal operation is started.
           Error flag
           M8067
                                                                     Y020               Error occurs.
END
                                                                                                                              L-25
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition            5 Example of Practical Programs (for Step Response Method)
PID Instruction (FNC 88)                                                    5.3 Program example of auto-tuning (step response method)
          Auto-tuning is started.
           X010
                                                     FNC 12   K500    D500           The target value is set (to 50°C).
                                                     MOVP
          Auto-tuning is started.
            M0
                                                              SET      M1            PID instruction operation
          Initial pulse
           M8002                                                                     The mode of FX2N-4AD-TC is set.
                                FNC 79        K0       K0     H3303    K1            Ch 1: Unused Ch 3: Unused
                                  TO                                                 Ch 2: K type  Ch 4: Unused
          RUN monitor
          M8000
                                FNC 78        K0       K 10   D501     K1            Data is read from the channel 2
                                FROM                                                 in FX2N-4AD-TC.
          Auto-tuning is started.
           X010
                                                              RST     D502           The PID output is initialized.
           PID
         operation
           M1
           PID
         operation
            M1
                                FNC 88       D500     D501    D510    D502           PID instruction
                                 PID
                          Auto-tuning is finished.
                            M2
                                                              RST      M1            Auto-tuning is completed.
L-26
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition           5 Example of Practical Programs (for Step Response Method)
PID Instruction (FNC 88)                                                   5.3 Program example of auto-tuning (step response method)
                                                                                                                                       FX3U-4AD-TC
            PID operation
              M1
                                                                                                                                                -ADP
                                                                                      Heater operation cycle timer
                                                                    T246              (2 sec)
                                                                            K2000
                                                                                                                                           L
             T246
                                                                                                                                       PID Instruction
                                                                                      The heater operation cycle timer
                                                              RST      T246           is preset.
             PID
                                                                                                                                              (FNC 88)
           operation
             M1
                                              PID operation
                                                   M1
                FNC226      T246    D502                            Y021              Heater output
                 LD <
            Error flag
            M8067
                                                                    Y020              Error occurs.
END
                                                                                                                           L-27
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                               6 Troubleshooting
PID Instruction (FNC 88)                                                                                                    6.1 Error Codes
6. Troubleshooting
     Error
                                    Error description                                                 Action
     code
     6730       Incorrect sampling time (TS) (TS ≤ 0)
                Incorrect input filter constant (α)
     6732
                (α < 0 or 100 ≤ α)
                                                                         <PID operation is stopped.>
     6733       Incorrect proportional gain (KP) (KP < 0)                A data error has occurred in the set value in a control parameter
     6734       Incorrect integral time (TI) (TI < 0)                    or in the middle of PID operation.
                                                                         Check the parameters.
                Incorrect derivative gain (KD)
     6735
                (KD < 0 or 201 ≤ KD)
     6736       Incorrect derivative time (TD) (TD < 0)
                                                                         <Auto-tuning is continued.>
     6740       Sampling time (TS) ≤ Operation cycle                     The operation is continued in the condition "sampling time (TS)
                                                                         = cyclic time (operation cycle)."
                Variation of measured value exceeds limit.
     6742
                (UPV < −32768 or +32767 < UPV)
                Deviation exceeds limit.
     6743
                (EV < −32768 or +32767 < EV)
                Integral result exceeds limit.
     6744                                                             <PID operation is continued.>
                (Out of range from −32768 to +32767)
                                                                      The operation is continued with each parameter set to the
                Derivative value exceeds limit due to derivative gain maximum or minimum value.
     6745
                (KD).
                Derivative result exceeds limit.
     6746
                (Out of range from −32768 to +32767)
                PID operation result exceeds limit.
     6747
                (Out of range from −32768 to +32767)
                                                                          <Output upper limit value and output lower limit value are
                PID output upper limit set value < PID output lower limit
     6748                                                                 exchanged for each other. → PID operation is continued.>
                set value
                                                                          Check whether the target settings are correct.
                Abnormal PID input variation alarm set value or output <Alarm output is not given. → PID operation is continued.>
     6749
                variation alarm set value (Set value < 0)              Check whether the target settings are correct.
                                                                         <Auto-tuning is finished. → PID operation is started.>
                                                                         • The deviation at start of auto-tuning is 150 or less.
                <Step response method>                                   • The deviation at end of auto-tuning is 1/3 or more of the
     6750
                Improper auto-tuning result                                 deviation at start of auto-tuning.
                                                                         Confirm the measured value and target value, and then execute
                                                                         auto-tuning again.
                                                                         <Auto-tuning is forced to finish. → PID operation does not
                                                                         started.>
                                                                         The operation direction estimated from the measured value at
                <Step response method>                                   the start of auto-tuning was different from the actual operation
     6751
                Auto-tuning operation direction mismatch                 direction of the output during auto-tuning.
                                                                         Correct the relationship among the target value, output value
                                                                         for auto-tuning and measured value, and then execute auto-
                                                                         tuning again.
L-28
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                    6 Troubleshooting
PID Instruction (FNC 88)                                                                                                         6.1 Error Codes
    Error
                                                                                                                                                     K
                                  Error description                                                       Action
                                                                                                                                                   FX3U-4AD-TC
    code
                                                                           <Auto-tuning is finished. → PID operation is not started.>
                                                                           Because the set value fluctuated during auto-tuning, auto-
                                                                                                                                                            -ADP
               <Step response method>                                      tuning was not executed correctly.
    6752
               Improper auto-tuning operation                              Set the sampling time to a value larger than the output change
                                                                           cycle, or set a larger value to the input filter constant.                  L
                                                                           After changing the setting, execute auto-tuning again.
                                                                                                                                                   PID Instruction
               <Limit cycle method>
    6753       Abnormal output set value for auto-tuning
                                                                                                                                                          (FNC 88)
               [ULV (upper limit) ≤ LLV (lower limit)]                     <Auto-tuning is forcibly finished. → PID operation is not
                                                                           started.>
               <Limit cycle method>                                        Check whether the target settings are correct.
    6754       Abnormal PV threshold (hysteresis) set value for auto-
               tuning (SHPV < 0)
               <Limit cycle method>                                        <Auto-tuning is forcibly finished. → PID operation is not
               Abnormal auto-tuning transfer status                        started.>
    6755
               (Data of device controlling transfer status is abnormally   Verify that devices occupied by PID instruction are not
               overwritten.)                                               overwritten in the program.
                                                                           <Auto-tuning is forcibly finished. → PID operation is not
                                                                           started.>
                                                                           The auto-tuning time is too long.
               <Limit cycle method>
                                                                           Increase the difference (ULV - LLV) between the upper limit and
    6756       Abnormal result due to excessive auto-tuning
                                                                           the lower limit of the output value for auto-tuning, set a smaller
               measurement time (τon > τ, τon < 0, τ < 0)
                                                                           value to the input filter constant (α), or set a smaller value to the
                                                                           PV threshold (SHPV) for auto-tuning, and then check whether
                                                                           the result is improved.
                                                                       <Auto-tuning is finished (KP = 32767). → PID operation is
                                                                       started.>
               <Limit cycle method>
                                                                       The variation of the measured value (PV) is small compared
    6757       Auto-tuning result exceeds proportional gain. (KP = Out
                                                                       with the output value. Multiply the measured value (PV) by "10"
               of range from 0 to 32767)
                                                                       so that the variation of the measured value will increase during
                                                                       auto-tuning.
               <Limit cycle method>                                        <Auto-tuning is finished (KP = 32767). → PID operation is
    6758       Auto-tuning result exceeds integral time.                   started.>
               (TI = Out of range from 0 to 32767)                         The auto-tuning time is too long.
                                                                           Increase the difference (ULV - LLV) between the upper limit and
               <Limit cycle method>                                        the lower limit of the output value for auto-tuning, set a smaller
    6759       Auto-tuning result exceeds derivative time.                 value to the input filter constant (α), or set a smaller value to the
               (TD = Out of range from 0 to 32767)                         PV threshold (SHPV) for auto-tuning, and then check whether
                                                                           the result is improved.
            Caution
            With regard to the measured value (PV) in PID, normal measurement data should be read before PID
            operation begins.
            Especially when the PID operation is executed to the input value in an analog input block, pay attention to the
            conversion time.
                                                                                                                                        L-29
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition   6 Troubleshooting
PID Instruction (FNC 88)                                       6.1 Error Codes
MEMO
L-30
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                                                      Warranty
Warranty
         Please confirm the following product warranty details before using this product.
      1. Gratis Warranty Term and Gratis Warranty Range                   2. Onerous repair term after discontinuation of
         If any faults or defects (hereinafter "Failure") found to be        production
         the responsibility of Mitsubishi occurs during use of the            1)   Mitsubishi shall accept onerous product repairs for
         product within the gratis warranty term, the product shall be             seven (7) years after production of the product is
         repaired at no cost via the sales representative or                       discontinued.
         Mitsubishi Service Company. However, if repairs are                       Discontinuation of production shall be notified with
         required onsite at domestic or overseas location, expenses                Mitsubishi Technical Bulletins, etc.
         to send an engineer will be solely at the customer's
         discretion. Mitsubishi shall not be held responsible for any         2)   Product supply (including repair parts) is not available
         re-commissioning, maintenance, or testing on-site that                    after production is discontinued.
         involves replacement of the failed module.                       3. Overseas service
                                                                              Overseas, repairs shall be accepted by Mitsubishi's local
         [Gratis Warranty Term]
                                                                              overseas FA Center. Note that the repair conditions at
         The gratis warranty term of the product shall be for one
                                                                              each FA Center may differ.
         year after the date of purchase or delivery to a designated
         place. Note that after manufacture and shipment from             4. Exclusion of loss in opportunity and secondary
         Mitsubishi, the maximum distribution period shall be six (6)        loss from warranty liability
         months, and the longest gratis warranty term after                   Regardless of the gratis warranty term, Mitsubishi shall not
         manufacturing shall be eighteen (18) months. The gratis              be liable for compensation of damages caused by any
         warranty term of repair parts shall not exceed the gratis            cause found not to be the responsibility of Mitsubishi, loss
         warranty term before repairs.                                        in opportunity, lost profits incurred to the user or third
                                                                              person by Failures of Mitsubishi products, special
         [Gratis Warranty Range]
                                                                              damages and secondary damages whether foreseeable or
         1)   The range shall be limited to normal use within the             not , compensation for accidents, and compensation for
              usage state, usage methods and usage environment,               damages to products other than Mitsubishi products,
              etc., which follow the conditions and precautions, etc.,        replacement by the user, maintenance of on-site
              given in the instruction manual, user's manual and              equipment, start-up test run and other tasks.
              caution labels on the product.
                                                                          5. Changes in product specifications
         2)   Even within the gratis warranty term, repairs shall be
                                                                              The specifications given in the catalogs, manuals or
              charged for in the following cases.
                                                                              technical documents are subject to change without prior
              a) Failure occurring from inappropriate storage or
                                                                              notice.
                   handling, carelessness or negligence by the user.
                   Failure caused by the user's hardware or software      6. Product application
                   design.                                                    1)   In using the Mitsubishi MELSEC programmable logic
              b) Failure caused by unapproved modifications, etc.,                 controller, the usage conditions shall be that the
                   to the product by the user.                                     application will not lead to a major accident even if any
              c) When the Mitsubishi product is assembled into a                   problem or fault should occur in the programmable
                   user's device, Failure that could have been                     logic controller device, and that backup and fail-safe
                   avoided if functions or structures, judged as                   functions are systematically provided outside of the
                   necessary in the legal safety measures the user's               device for any problem or fault.
                   device is subject to or as necessary by industry
                                                                              2)   The Mitsubishi programmable logic controller has
                   standards, had been provided.
                                                                                   been designed and manufactured for applications in
              d) Failure that could have been avoided if
                                                                                   general industries, etc. Thus, applications in which the
                   consumable parts (battery, backlight, fuse, etc.)
                                                                                   public could be affected such as in nuclear power
                   designated in the instruction manual had been
                                                                                   plants and other power plants operated by respective
                   correctly serviced or replaced.
                                                                                   power companies, and applications in which a special
              e) Relay failure or output contact failure caused by
                                                                                   quality assurance system is required, such as for
                   usage beyond the specified Life of contact
                                                                                   Railway companies or Public service purposes shall
                   (cycles).
                                                                                   be excluded from the programmable logic controller
              f) Failure caused by external irresistible forces such
                                                                                   applications.
                   as fires or abnormal voltages, and failure caused
                                                                                   In addition, applications in which human life or
                   by force majeure such as earthquakes, lightning,
                                                                                   property that could be greatly affected, such as in
                   wind and water damage.
                                                                                   aircraft, medical applications, incineration and fuel
              g) Failure caused by reasons unpredictable by
                                                                                   devices, manned transportation, equipment for
                   sc ientific tec hnol ogy s tanda rds a t tim e of
                                                                                   recreation and amusement, and safety devices, shall
                   shipment from Mitsubishi.
                                                                                   also be excluded from the programmable logic
              h) Any other failure found not to be the responsibility
                                                                                   controller range of applications.
                   of Mitsubishi or that admitted not to be so by the
                                                                                   However, in certain cases, some applications may be
                   user.
                                                                                   possible, providing the user consults their local
                                                                                   Mitsubishi representative outlining the special
                                                                                   requirements of the project, and providing that all
                                                                                   parties concerned agree to the special circumstances,
                                                                                   solely at the users discretion.
                                                                                                                                        i
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition                                               Revised History
Revised History
               Date       Revision                                         Description
              7/2005         A       First Edition
              2/2006         B       • FX3U-4AD is added to B.
                                     • FX3U-4DA is inserted to D.
                                     • Adding and revising the other descriptions.
              3/2006         C       • B-8 page, 2.2 The Power Supply Specification for the FX3U-4AD, regarding the
                                       A/D conversion circuit drive power:
                                         Revised from [24V DC ±10%, 80mA] to [24VDC ±10%, 90mA]
              3/2007         D       • JIS (Japanese Industrial Standards) for temperature sensors are added
                                     • Clerical Error Correction
             12/2007         E       • FX3UC (D, DSS) Series PLC added
                                     • FX3U-4AD-PTW-ADP is inserted to G
                                     • Clerical Error Correction
             11/2008         F       •   FX3G Series PLC added
                                     •   FX3G-2AD-BD is added to D.
                                     •   FX3G-1DA-BD is added to G.
                                     •   FX3U-4AD-PNK-ADP is added to H.
                                     •   Adding and revising the other descriptions.
ii
USER'S MANUAL - Analog Control Edition
               HEAD OFFICE: TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
               HIMEJI WORKS: 840, CHIYODA CHO, HIMEJI, JAPAN
    MODEL            FX3U-U-ANALOG-E
MODEL CODE                    09R619