Janitza BHB Umg96rme en
Janitza BHB Umg96rme en
UMG 96 RM-E
www.janitza.com Residual current monitoring (RCM)
Power Analyser
Doc. no. 1.040.129.0.r
Content
General 4
Inspection on receipt 8 Connecting the supply voltage 52
Available accessories 9 Current and voltage transformers 52
Product description 10 Programming the current transformer for I1 to I3 54
Proper use 10 Programming the voltage transformer 55
Performance characteristics – UMG 96RM-E 12 Programming parameters 56
Measuring process 13 TCP/IP configuration 57
Operating concept 13 RS485 device address (Addr. 000) 60
GridVis network analysis software 13 RS485 baud rate (Addr. 001) 60
Connection variants 14 MODBUS gateway (Addr. 002) 61
Mounting 15 User password (Addr. 050) 61
Installation 17 Parameter 62
Power supply 17 Mean value 62
Measuring voltage 18 Averaging method 62
Current measurement via I1 to I4 24 Min. and max. values 62
Residual current measurement (RCM) 33 Mains frequency (Addr. 034) 63
Temperature measurement input 37 Energy meter 64
RS485 interface 38 Reset energy meter (Addr. 507) 64
Ethernet interface 41 Harmonics 65
Digital in-/outputs 42 Measured value rotation 66
LED status bar 47 Measured value indocations 66
Operation 48 Phase sequence 68
Display mode 48 LCD contrast (Addr. 035) 68
Programming mode 48 Backlight 68
Parameters and measured values 50 Time recording 69
Configuration 52 Operating hours meter 70
Serial number (Addr. 754) 70
2
UMG 96RM-E
3
UMG 96RM-E
Trademarks
Disclaimer
4
UMG 96RM-E
c Dangerous voltage!
Danger to life or risk of serious injury.
Disconnect system and device from power
supply before beginning work.
m Caution!
Please follow the documentation.
This symbol warns of possible dangers
that can arise during installation,
commissioning and use.
C Note!
5
UMG 96RM-E
Please read the operating manual at hand as well as all Specialized personnel are persons, that based on their
other publications that must be drawn from for working respective training and experience, are qualified
with this product (in particular for the installation, to recognize risks and prevent potential dangers
operation or maintenance). that can be caused by the operation or maintenance
of the device.
Follow all safety regulations and warning information.
If you do not follow the information, it can result in bodily Additional legal and safety regulations required for
injury and/or damage to the product. the respective application are to be following during the
use of the device.
Any unauthorized changes or use of this device, which
transcend the mechanical, electrical or otherwise stated
operating limitations, can result in bodily injury or/and
damage to the product.
6
UMG 96RM-E
m
or components for critical switching,
Conductors made from single wires must control or protection applications where
be fitted with wire-end ferrules. the safety of persons and property
depends on this function.
• Do not carry out switching operations
7
UMG 96RM-E
These operating instructions are a part of the product. The prerequisites of faultless, safe operation of this
• Read the operating instructions before using device are proper transport and proper storage, set-
the device. up and assembly, as well as careful operation and
• Keep the operating instructions throughout the entire maintenance. If it can be assumed that risk-free operation
service life of the product and have them readily is no longer possible, the unit must be immediately put
available for reference. out of operation and secured against being put back into
• Pass the operating instructions on to each subsequent operation again.
owner or user of the product. The packing and unpacking must be carried out with
the customary care without the use of force and only
using suitable tools. The devices should be visually
checked for flawless mechanical condition.
It can be assumed that risk-free operation is no longer
possible if the device, for example,
8
UMG 96RM-E
Available accessories
Number Part no. Description
2 52.22.251 Mounting clips
1 10.01.855 Screw-type terminal, pluggable, 2-pole (auxiliary power)
1 10.01.849 Screw-type terminal, pluggable, 4-pole (voltage measurement)
1 10.01.871 Screw-type terminal, pluggable, 6-pole (current measurement I1-I3)
1 10.01.875 Screw-type terminal, pluggable, 2-pole (current measurement I4)
1 10.01.865 Screw-type terminal, pluggable, 10-pole (digital/analogue inputs/outputs)
1 10.01.857 Screw-type terminal, pluggable, 2-pole (RS 485)
1 10.01.859 Screw-type terminal, pluggable, 3-pole (Digital/impulse output)
1 08.01.505 Patch cable 2m, coiled, grey (connection UMG 96RM-PC/Switch)
1 52.00.008 RS485, external terminating resistor, 120 ohm
1 21.01.058 Lithium battery CR2032, 3V (approval i.a.w. UL 1642)
1 29.01.065 Silicone seal, 96 x 96
1 15.06.015 Interface converter RS485 <-> RS232
1 15.06.025 Interface converter RS485 <-> USB
9
UMG 96RM-E
Product description
Proper use
The UMG 96RM-E is intended for the measurement By continuously monitoring the residual currents
and calculation of electrical parameters such as voltage, (RCM) of an electrical system via the inputs I5 and I6,
current, power, energy, harmonics etc. in building warning pulses can be triggered if a response threshold
installations, on distribution units, circuit breakers is exceeded. Using these, the system operator can
and busbar trunking systems. be alarmed before a protective equipment reacts.
The UMG 96RM-E is suitable for integration into fixed The UMG 96RM-E does not provide protection against
and weatherproof switch panels. Conductive switch and electric shock!
panels must be earthed.
The residual current measuring is done via the current
Measured voltage and measured current must derive measurement inputs I5 and I6 via an external residual
from the same network. current transformer with a rated current of 30 mA.
The measurement results can be displayed and can
be read out and further processed via the RS485 Measurements in medium and high-voltage networks
interface. is always done via current and voltage transformers.
10
UMG 96RM-E
For Janitza measurement devices and components, The UMG 96RM-E can be used in industrial and domestic
use only current transformers intended for measuring settings.
purposes (“transformers”)!
Device characteristics
“Transformers”, unlike “protection transformers”, • Supply voltage:
go into saturation at high current peaks. “Protection Option 230V: 90V - 277V (50/60Hz) or
transformers” do not have this saturation behavior and DC 90V - 250V; 300V CATIII
can therefore significantly exceed the rated values in Option 24V: 24 - 90V AC / DC; 150V CATIII
the secondary circuit. This can overload the current • Frequency range: 45 - 65Hz
measurement inputs of the measurement devices!
Device functions
Furthermore, please note that Janitza measurement • 3 voltage measurements, 300V
devices and components are not to be used for critical • 4 current measurements
switching, control or protection applications (protective (via current transformers ../5A or ../1A)
relays)! Observe the safety and warning information in • 2 residual current measurements
the “Installation” and “Product safety” chapters! (via residual current transformers ../30mA) or
optionally 2 temperature measurements
• RS485 interface, Ethernet
• 2 digital outputs and additional 3 digital
inputs/outputs
• Clock and memory function
11
UMG 96RM-E
12
UMG 96RM-E
The UMG 96RM-E measures continuously The UMG 96RM-E can be programmed and read out
and calculates all effective values over a 10/12 period using the GridVis network analysis software (Download:
interval. The UMG 96RM-E measures the real effective www.janitza.com). For this a PC must be connected to
value (TRMS) of the voltage and current connected the UMG 96RM-E via a serial interface (RS485) or via
to the measurement inputs. Ethernet.
You can program and call up the measured values via • Programming the UMG 96RM-E
many routes using the UMG 96RM-E. • Graphical representation of measured values
13
UMG 96RM-E
Connection variants
Connection of a UMG 96RM-E to a PC via a interface Direct connection of a UMG 96RM-E to a PC via
converter: Ethernet.
UMG 96RM-E
(gedrehtes Patchkabel)
Connection of a UMG 96RM via a UMG 96RM-E Connecting a UMG 96RM-E to a PC via Ethernet.
as a gateway.
UMG 96RM
Switch
(gedrehtes Patchkabel)
(gedrehtes Patchkabel)
14
UMG 96RM-E
Mounting
Position of installation
Mounting position
Cut-out size:
92+0.8 x 92+0.8 mm.
Mounting
The UMG 96RM-E is fixed using the mounting clips The fastening is then done when the device is pushed
found on the side of the switch panel. Before inserting in an the clamps lock in place when the screws are
the device, they should be moved out of the way tightened.
in a horizontal lever using a screwdriver, for example.
• Please tight the fixing screws until they contact the
mounting plate easily.
• Tighten with two further turns, the clamping screws
Fig. side view (are the screws tightened too much, the mounting
UMG 96RM-E with bracket will be destroyed)
mounting clips.
Loosening the clips
is done using
a screwdriver Mounting plate
and a horizontal lever
effect.
Fixing screw
Mounting Screwdriver
clips
Contacting of the
fixing screws to the
mounting plate:
Tighten with maximum
two further turns for
the installation
16
UMG 96RM-E
Installation
Power supply
L
The 96RM-E needs a supply voltage to operate. N
The supply voltage is connected on the rear of the device
via terminal blocks. Fuse
17
UMG 96RM-E
Measuring voltage
You can use the UMG 96RM-E to measure voltage In systems without N, the measurements which require
in TN-, TT-, and IT systems. an N are to a calculated N.
The voltage measurement in the UMG 96RM-E
is designed for the overvoltage category 300V CAT III
(rated impulse voltage 4 kV).
L1 277V/480V 50/60Hz L1 L1
L2 L2 480V 50/60Hz
240V
L3 50/60Hz L3
N N
PE
Impedance
V1 V2 V3 VN V1 V2 V3 VN
AC/DC AC/DC
4M
4M
4M
4M
4M
4M
4M
4M
DC System DC
earthing
Measuring voltage Measuring voltage
UMG 96RM Auxiliary energy UMG 96RM Auxiliary power
Fig. schematic diagram - measurements in three-phase Fig. schematic diagram - measurements in three-phase
4-wire systems. 3-wire systems.
18
UMG 96RM-E
Three-phase, 4-wire systems with earthed neutral Three-phase, 3-wire systems, unearthed.
conductor.
Frequency Fuse
For the measurement and calculation of measured
values, the UMG 96RM-E needs the network frequency. Circuit breaker
The UMG 96RM-E is suitable for measurements
on systems in a frequency range from 45 to 65Hz.
20
UMG 96RM-E
c
When connecting the voltage to be measured,
the following must be observed: Caution!
Voltages which exceed the per-
Isolation device mitted networkrated voltage
• A suitable circuit breaker must be fitted to disconnect must be connected via a voltage
and de-energise the UMG 96RM-E. transformer.
• The circuit breaker must be placed in the vicinity of
c
the UMG 96RM-E, be marked for the user and easily
accessible. Caution!
• The circuit breaker must be UL/IEC certified. The UMG 96RM-E is not suitable for
measuring DC voltages.
Overcurrent protection device
• An overcurrent protection device must be used for
c
line protection.
Caution!
• For line protection, we recommend an overcurrent
The voltage measurement inputs
protection device as per the technical specifications.
on the UMG 96RM-E are dangerous
• The overcurrent protection device must be suitable
if touched!
for the line cross section used.
• The overcurrent protection device must be UL/IEC
certified.
• A circuit breaker can be used as an isolating and line
protection device. The circuit breaker must be UL/IEC
certified.
• Measured voltages and measured currents must
derive from the same network.
21
UMG 96RM-E
L1 L1
L2 L2
L3 L3
N N
V1 V2 V3 VN V1 V2 V3 VN
Fig. System with three line conductors Fig. System with three line conductors
and neutral conductor. and neutral conductor. Measurement using
a voltage transformer.
L1 L1
L2 L2
L3 L3
V1 V2 V3 VN V1 V2 V3 VN
Fig. System with three line conductors without Fig. System with three line conductors without
neutral conductor. Measurements which require neutral conductor. Measurement using a voltage
a N are based on a calculated N. transformer. Measurements which require a N
are based on a calculated N.
22
UMG 96RM-E
L1 L1
L2
L3
N N
V1 V2 V3 VN V1 V2 V3 VN
Fig. The values obtained from the voltage Fig. System with uniform phase loading.
measurement inputs V2 and V3 are taken The measured values for the voltage
to be null and not calculated. measurement input V2 are calculated.
23
UMG 96RM-E
L3
c
N
Caution!
The test leads must be designed for an Fig. Current measurement (I1-I3) via current
operating temperature of at least 80°C. transformers (connection example)
c Caution!
The current measurement inputs are
dangerous to touch.
m The attached screw terminal has to be
fixed sufficiently with two screws on the
device!
24
UMG 96RM-E
L1
L2
L3
N
Earthing of current transformers!
If a connection is provided for the earthing
of secondary windings then this must
be connected to the earth.
m Caution!
The UMG 96RM-E is not suitable for
measuring DC voltages.
Load
Fig. Current measurement (I4) via current
transformer (connection example)
25
UMG 96RM-E
Current direction
c
The current direction can be individually corrected via
Caution!
the existing serial interface or on the device for each
A residual current measurement is done
phase.
using the terminals I5 and I6 (see page 30).
If incorrectly connected, a subsequent re-connection of
There is no directional sensitivity of the
the current transformer is not required.
residual currents on the network or load
sides (not directionally sensitive).
When residual current measurements (RCM) are being
carried out, there is no direction sensitive difference in
the residual currents on the network or load side (not
directionally sensitive).
c Earthing of current transformers!
If a connection is provided for the earthing
of secondary windings then this must be
connected to the earth.
26
UMG 96RM-E
c Caution!
The UMG96RM is only approved for
a current measurement using the
c Disregard of the connection conditions of
the transformers to Janitza measurement
devices or their components can lead
current transformer. to injuries or even death or to material
damage!
• Do not use Janitza measurement devices
or components for critical switching,
control or protection applications
(protective relays)! It is not permitted to
use measured values or measurement
device outputs for critical applications!
• For Janitza measurement devices and their
components use only “Transformers
for measurement purposes” which are
suitable for the energy monitoring of your
system. Do not use “Transformers for
protection purposes”!
• Observe the information, regulations
and limit values in the usage information
on “Transformers for measuring
purposes”, specifically during testing
and commissioning of the Janitza
measurement device, the Janitza
component and your system.
27
UMG 96RM-E
L1 L1
L2 L2
L3 L3
N N
I1 I2 I3 I1 I2 I3
Fig. Measurement in a three-phase network with Fig. System with uniform phase loading. The
non-uniform load. measured values for the current measurement
input I2 are measured.
L1 L1
L2 L2
L3 L3
I1 I2 I3 I1 I2 I3
Fig. The measured values for the current Fig. Measurement in a three-phase network with
measurementinput I2 are calculated. non-uniform load.
28
UMG 96RM-E
L1 L1
L2 L2
L3 L3
N N
I1 I2 I3 I1 I2 I3
Fig. System with uniform phase loading. The Fig. System with uniform phase loading. The
measured values for the current measurement measured values for the current measurement
inputs I2 and I3 are calculated. input I2 are calculated.
L1 L1
L2
N
I1 I2 I3 I1 I2 I3
Fig. The null is taken from the current Fig. The null is taken from the current
measurement input I3's measured value and not measurement inputs I2 and I3 measured values
calculated. and not calculated.
29
UMG 96RM-E
• 3p 1w (Addr. 510 = 8) If you wish to measure the current not just using
the UMG 96RM, rather also with a ammeter, the ammeter
L1 must be connected to the UMG 96RM-E in series.
L2
L3
L1
L2
L3
UMG
L1 I
L2 S1 S2
L3
A
I1 I2 I3
30
UMG 96RM-E
If the current measurement is done via two current Example: The current is measured via two current
transformers, the overall transformation ratio transformers. Both current transformers have
of the current transformers must be programmed into a transformation ratio of 1000/5A. The total measurement
the UMG 96RM-E. is done using a total current transformer 5+5/5A.
Einspeisung 1 Einspeisung 2
Supply 1 Supply 2
P1 P2
Verbraucher A Verbraucher B
Consumer A Consumer B
31
UMG 96RM-E
c
Analog inputs
Attention!
The UMG 96RM-E has 2 analog inputs which can Operating equipment connected to the
be used for one residual current measurement or one analogue inputs must exhibit reinforced
temperature measurement. The measurement is done or double insulation from mains supply
using terminals 32-34 (input 1) or 35-37 (input 2). circuits!
32
UMG 96RM-E
of type A and
type B. *1 S1
S2
*1 S1
The connection from suitable external residual current
transformers with a rated current of 30 mA is done via S2
the residucal current transformer inputs I5 (terminals
33/34) and I6 (terminals 36/37).
Load
C Residual current transformer ratio
The GridVis software can be used to
individually program the residual current PE N L1 L2 L3
transformer inputs' transformer ratios.
Fig. Connection example residual current
measurement via current transformers
*1 Please note: Jumpers between connectors 32-33 respectively 35-36 are
only required from hardware-release 104!
33
UMG 96RM-E
230 V
AC
24 V
DC
for Example: Residual current
transformer from the series
4-20 mA DC CT-AC/DC type B+ RCM
*1
0-30 mA AC for Example: Residual current
transformer from the series
CT-AC-RCM
Example connection for measuring residual currents of type B and A. *1 Please note: Jumper between connector 35-36 are only
(Mains adapter with U = 24V DC, residual ripple < 5%, power: 24W) required from hardware-release 104!
34
UMG 96RM-E
230 V
AC
24 V
DC z.B. Differenzstromwandler
CT-AC/DC Typ B+
4-20 mA DC
230 V
AC
24 V
DC
z.B. Differenzstromwandler
CT-AC/DC Typ B+
4-20 mA DC
m
Example connection for measuring residual currents of type B. Every resi-
dual current transformer from the series CT-AC/DC type B+ RCM requires The residual current measurement inputs
its own mains adapter (with U = 24V DC, residual ripple < 5%, power: 24W). must be galvanically separated from each
The secondary sides of the mains adapters (24V DC) must be galvani- other!
cally separated from each other!
35
UMG 96RM-E
Residual current
L1 transformer
L2
L3
PEN
N
PE Residual
current
transformer
Fig. Example L1 L2 L3 N I1 I2 I3 I4 I5 I6
UMG96RM-E with M
residual current UMG 96RM-E (RCM) 3~
monitoring via
measuring inputs i5/I6.
C I t i s n o t n e c e s s a r y t o c o n f i g u re
a connection schematic for residual
current inputs I5 and I6.
36
UMG 96RM-E
PT100
PT100
37
UMG 96RM-E
In UMG 96RM-E, the RS485 interface is designed as a 2 The cable is terminated with resistors (120Ohm, 1/4W)
pin plug contact, which communicates via the Modbus at the beginning and at the end of a segment.
RTU protocol (also see Parameter programming).
The UMG 96RM-E does not contain any termination
resistors.
Correct
RS485 interface,
2-pole plug contact
A Incorrect
RS485 bus
B
Twisted screened cable should be used for connections The cable used must be suitable for an environmental
via the RS485 interface. temperature of at least 80°C.
• Earth the screens of all cables that lead to the cabinet, Recommended cable type:
upon entering the cabinet. Unitronic Li2YCY(TP) 2x2x0.22 (from Lapp Kabel)
• Connect the screens over a generous area
and in a manner that will conduct well, to a low-noise
earth.
• Gather the cables mechanically above the earthing
clamp in order to avoid damage due to cable Maximum cable length
movements.
• Use suitable cable glands to feed the cables into 1200m at a baud rate of 38.4k.
the cabinet - for example armoured conduit couplings.
Cable
Strain relief
Low-noise earth
Bus structure
• All devices are connected in a bus structure (line) and • It is recommended to set the master at the end
each device has its own address within the bus (also of a segment.
see programming parameters). • The bus is inoperative if the master is replaced with
• Up to 32 stations can be interconnected in one an activated bus termination.
segment. • The bus can become unstable if the slave is replaced
• The cable is terminated with resistors (bus termination, with an activated bus termination or is dead.
120 ohm 1/4 W) at the beginning and end of a segment. • Devices that are not involved in the bus termination
• If there are more than 32 stations, repeaters (line can be exchanged without making the bus unstable.
amplifiers) must be used in order to connect • The shield has to be installed continuously and needs
the individual segments. to be broadly and well conducting connected to an
• Devices with activated bus termination must external low voltage (or potential) ground at the end.
be supplied with power.
T
T
T
T
40
UMG 96RM-E
Ethernet
Connection
PC / Switch
m Attention!
Property damage due to security
vulnerabilities in programs, IT networks and
protocols.
Security vulnerabilities can result in data misuse,
faults and even cause your IT infrastructure to
shut down.
To protect your IT system, network, data
communications and measurement devices:
C
• Notify your network administrator and/or
Note!
IT manager.
The Ethernet interface is connected to
• Always keep the measurement device
GND (Ground) via a 0.1 MΩ resistor.
firmware up to date and protect the
communication to the measurement
device with an external firewall. Close any
m Caution!
The UMG 96RM-E is factory-programmed
for the dynamic allocation of the IP settings
unused ports.
• Take protective measures against viruses
and cyber attacks from the Internet,
(DHCP mode). e.g. through firewall solutions, security
Settings can be changed as described updates and antivirus programs.
in TCP/IP Configuration or, for example, • Eliminate security vulnerabilities and
via an appropriate Ethernet connection update or renew existing protection for
by means of GridVis software. your IT infrastructure.
41
UMG 96RM-E
Digital in-/outputs
The UMG 96RM-E has 2 digital outputs and 3 optional Digital outputs, Group 2
digital inputs or outputs, which are divided into two • The status of the inputs and outputs in Group 2 is
groups (see figure). This means that only entire group 2 indicated by the associated LED (cf. chapter LED
(connection 28 to 31) operate either as input or output; status bar).
a different allocation within the group is not possible!
K1/K2 display
C
status indicator
The digital outputs of group 2 are not AC
compatible.
Source Inverter
e.g.
Comparator group
Digital
output 1
42
UMG 96RM-E
Digital outputs
Group 2
These outputs are galvanically separated from
~
the analysis electronics using optocouplers. The digital
outputs have a joint reference.
Fig. Connection
~ digital / pulse outputs
Group 1
43
UMG 96RM-E
m
DC connection example
Caution!
Digital outputs are not short-circuit proof.
External
UMG 96RM-E Auxiliary voltage
13 24V DC
Group 1:
software (Download: www.janitza.com).
A connection between the UMG 96RM-E
and the PC via an interface is required for
Digital Ouput 2
the use of the GridVis software. 15
C
28
When using the digital outputs as pulse
LED
outputs the auxiliary voltage (DC) must DC
Digital Ouput 3
have a max. residual ripple of 5%. 29
K1
Group 2:
LED
DC
C
Digital Ouput 4
To prevent the measurement device from 30
K2
displaying a residual voltage, connect
terminal „13“ of the digital outputs of your
LED
measurement device as the functional earth
Digital Ouput 5
(FE) to the PE conductor of your system. Use 31
the color „pink“ (DIN EN 60445/VDE 0197)
for the functional earth lead. Fig. Example for two relays connected to
the digital outputs
44
UMG 96RM-E
Digital inputs
- + 2k21
30
Digital S2
Input 2
Group 2 2k21
2k21
31
Digital S3
Input 3
2k21
2k21
Fig. Connection
example for digital Fig. Example for the connection of external switch
inputs. contacts S1 and S2 to digital inputs 1 and 2.
45
UMG 96RM-E
S0 pulse input
1.5k
2k21
29
S0 pulse
Digital transducer
Input 1
2k21
2k21
30
Digital
Input 2
2k21
2k21
31
Digital
Input 3
2k21
2k21
Digital outputs
The LED assigned to a respective output lights up red
when the output is set as enabled - regardless of whether
there is a continuing connection to this interface.
Fig. LED status bar for inputs
and outputs
47
UMG 96RM-E
The UMG 96RM-E is operated via buttons 1 and 2 with You can view and change the necessary settings
the following functions: of the UMG 96RM-E in programming mode. Press
• briefly pressing button 1 and 2: button 1 and 2 simultaneously for about 1 second
next step (+1) to switch to programming mode after entering
• pressing and holding button 1 and 2: the password. If no password is programmed, you get
previous step (-1) directly to the programming mode menu. Programming
Measured values and programming data are displayed mode is marked by the text „PRG“ on the display.
on an LCD display.
Press button 2 to switch between the following menus:
There are display and programming modes. You can
avoid an unintentional change of programming data - Current transformer,
by entering a password. - Voltage transformer,
- Parameter list,
Display mode - TCP/IP device address,
- Subnet mask,
In display mode, you can scroll through the programmed - Gateway address,
measured values by pressing buttons 1 and 2. When - Dynamic TCP/IP addressing (in/out).
the device is delivered, all measured value indications
of profile 1 can be retrieved. For each measured value, If no button was pressed for about 60 seconds when you
up to three measured values are indicated. The measured are in programming mode, or button 1 and 2 are pressed
value rotation can display selected measured value simultaneously for about 1 second, the UMG 96RM-E
indications one after the other with a selectable changing will switch back to display mode.
time.
48
UMG 96RM-E
Mean value
Programming
mode
Total measurement
External conductor
External conductor
Password
CT: current
transformer
VT: voltage
transformer
K1: output 1
K2: output 2
Button 2
Supply Button 1
49
UMG 96RM-E
All necessary parameters for the use of UMG 96RM-E, In this example, the contents
such as current transformer data and frequently required of address "000" is indicated
measured values are provided in the table. by the value "001" on
Use the UMG 96RM‑E buttons to retrieve the contents display of the UMG 96RM‑E.
of most of the addresses via serial interface. This parameter specifies
the device address (in this
You can only enter the first 3 significant digits of a value case "001") according to
on the device. Values with more digits can be entered the list of the UMG 96 RM-E
using GridVis. within a bus.
The first 3 significant digits of a value are displayed
on the device. Measured value indication
example
Selected measured values are summarized in measured
value profiles and can be indicated in display mode In this example, the
by pressing button 1 and 2. voltage L-N is indicated
by 230V on the display of
The current measured value profile, the display change the UMG 96RM‑E. The
profile, plus date and time can be read and changed via transistor outputs K1 and K2
the RS485 interface only. are active, which ensures the
current flow.
50
UMG 96RM-E
Button functions
simultaneously
simultaneously
Scroll
Scroll Programming
short menu +1
short: Value x 10
(Decimal point to the
right) long: Value/10
(flashing) (Decimal point to the left)
51
UMG 96RM-E
Configuration
c
Connecting the supply voltage
Caution!
The supply voltage must be connected for If the supply voltage does not correspond
the configuration of the UMG 96RM-E . to the voltage indicated on the rating
plate, this may lead to malfunctions severe
The level of the supply voltage for the UMG 96RM‑E damage to the device.
is specified on the rating plate.
52
UMG 96RM-E
53
UMG 96RM-E
Switch to the programming mode Input of the current transformer secondary current
• Press button 1 and 2 simultaneously to switch • Only 1A or 5A can be set as secondary current.
to the programming mode. If a user password was • Press button 1 to select the secondary current.
programmed, the password menu appears in display • Press button 2 to change the flashing digit.
with the indication „000“. The first digit of the user
password is flashing and can be changed by pressing Exit programming mode
button 2. Press button 2 to select the next digit while • Press both buttons simultaneously to exit
it is flashing. You can get to the programming mode the programming mode.
after entering the correct code, or if no user password
was programmed.
• The symbols for the programming mode PRG
and the current transformer mode CT appear
on the display.
• Press button 1 to confirm the selection.
• The first digit of the input field for the primary current
is flashing.
54
UMG 96RM-E
Programming mode
Display of units
Voltage transformer,
secondary
Voltage transformer symbol
55
UMG 96RM-E
56
UMG 96RM-E
TCP/IP configuration
Description
Within an Ethernet, each device has a unique TCP / IP
address that can be assigned manually or from Byte identification
(e.g. byte 0) of the address
a DHCP server. The 4-byte device address (0 to 3 byte)
can be extended in the TCP / IP configuration using Address value, byte 0
the subnet mask and gateway data.
Fig. TCP/IP address, byte 1
Setting the TCP / IP device address (addr) manually A TCP / IP address consists
• Select in the programming mode as described. of 4 bytes with the following
The symbols for the programming mode PRG structure:
and the current transformer mode CT appear Byte 0 Byte 1 Byte 2 Byte 3
58
UMG 96RM-E
m Caution!
Connection of the UMG96RM-E to the
Ethernet may only be carried out after
discussion with the network administrator!
Fig. Subnet mask (Sub),
byte 0, value 255
m Caution!
The UMG 96RM-E is factory-programmed
for the dynamic allocation of the IP settings
(DHCP mode).
Settings can be changed as described
Fig. Gateway (GAt), in TCP/IP Configuration or, for example,
byte 0, value 192 via an appropriate Ethernet connection
by means of GridVis software.
Fig. Disabled
dynamic allocation (dYn IP)
of the TCP / IP address
59
UMG 96RM-E
RS485 device address (Addr. 000) RS485 baud rate (Addr. 001)
If multiple devices are connected to each other via A common baud rate can be adjusted for the RS485
the RS485 interface, a master device can only identify interfaces. The baud rate must be uniform for all
the devices by their device address. Within a network, devices on the network. Address 003 can be used to set
each device must have its own device address. the number of stop bits (0=1bit, 1= 2bits). Data bits (8)
Addresses can be set in the range of 1 to 247. are fixed default values.
60
UMG 96RM-E
Set address 002 as described in the table below to use A user password can be programmed to prevent
the UMG 96RM-E Modbus Gateway function: accidental change of the programming data. Changes
in the programming menu below can only be made after
entering the correct user password.
User password is not factory-programmed. In this case,
the password menu is skipped and you get directly
Setting Baud rate to the current transformer menu.
Modbus Gateway disabled (OFF)
0 If a user password was programmed, the password
(Factory setting)
menu appears on the display with the indication „000“.
1 Modbus Gateway enabled (ON) The first digit of the user password is flashing and can be
changed by pressing button 2. Press button 1 to select
the next digit while it is flashing.
You can only get to the current transformer programming
menu after entering the correct code.
Forgot my password
61
UMG 96RM-E
63
UMG 96RM-E
The UMG 96RM-E has power meters for active energy, The real, apparent and reactive energy meters can only
reactive energy and apparent energy. be reset simultaneously.
64
UMG 96RM-E
Harmonics are integer multiples of a fundamental THD is the ratio of the rms value of the harmonics
oscillation. to the rms value of the fundamental oscillation.
The fundamental oscillation of the voltage for
UMG 96RM-E must range between 45 and 65Hz. Total harmonic distortion of the current THDI:
The calculated harmonic voltages and currents relate
to this fundamental oscillation.
Harmonics up to 40 times the fundamental frequency are
detected.
Total harmonic distortion of the voltage THDU:
The harmonics of the currents and of the voltages are
displayed in amperes and volts, respectively.
Phase L3
Current harmonics
Value Phase L3
All 10/12 periods the measured values are calculated Setting range : 0 .. 60 seconds
and the readings are displayed on a per second basis. If 0 seconds are set, the measured value indications
There are two ways to retrieve the measurement selected will not be rotated.
readings: The rotation time set applies to all display rotation
profiles.
• The automatically changing indication of the selected
measurement readings is referred to herein Display rotation profile (Addr. 038)
as measured value rotation.
• Press button 1 and 2 to select measured value Setting range: 0 .. 3
indication from a pre-selected display profile. 0 - Display rotation profile 1, pre-programmed.
1 - Display rotation profile 2, pre-programmed.
Both methods are available simultaneously. 2 - Display rotation profile 3, pre-programmed.
The measured value rotation is enabled when at least 3 - Display rotation profile, customizable.
one measured value indication change time is over
0 seconds.
Press a button to scroll the measured value indications Measured value indocations
of selected display profile. If no button is pressed for
about 60 seconds, the device will switch to the measured Following a power resumption, the UMG 96RM-E
value rotation to display the programmed measured displays the first measurement value table in the current
value indications from the selected rotation profile display profile. To keep the selection to a manageable
in succession. size, only a fraction of the available measurement values
was preprogrammed in the factory for retrieval in the
measured value display. Select another display profile
to view other measured values on the UMG 96RM-E
display.
66
UMG 96RM-E
Setting range: 0 .. 3
0 - Display profile 1, default value.
1 - Display profile 2, default value.
2 - Display profile 3, default value.
3 - Display profile, customizable.
C Profile setting
Both profiles (display rotation profile
and display profile) are illustrated
in the GridVis software. The profiles can be
adjusted using the Device Configuration
function of the software; customizable display
profiles are programmed individually.
A connection between the UMG 96RM-E
and the PC via an interface is required for
the use of the GridVis software
Fig. Profile setting in the GridVis software.
67
UMG 96RM-E
The voltage phase sequence and the phase L1 frequency The preferred view for the LCD display is from "below".
are displayed on the screen. The LCD display contrast can be adapted by the user.
The contrast can be set stepwise in the range from
The phase sequence shows the three-phase system 0 to 9.
sequence. The rotary field usually rotates to the "right".
The voltage measurement input phase sequence 0 = very bright
is checked and displayed in the UMG 96RM-E. 9 = very dark
If the string moves in a clockwise direction, this means
that the rotary field rotates to the "right"; if the string Factory default setting: 5
moves in a counter-clockwise direction, this means that
the rotary field rotates to the "left".
The field rotation can only be determined when Backlight
the measurement and operating voltage inputs are fully
connected. If a phase is missing or two equal phases are The LCD backlight allows the display to be read easily
connected, then the phase sequence is not determined even in poor light. The brightness can be controlled by
and the string is not moving. the user in stages from 0 to 9.
746 Period of time after 60 .. 9999 900 In the measured value display, a maximum of 99999.9 h
which the backlight will Sek. Sek. (= 11.4 years) can be displayed.
switch to standby
747 Brightness for 0 .. 9 0
standby backlight
The operating hours meter measures the UMG 96RM-E The serial number displayed by the UMG 96RM-E
recording and displaying time. consists of 6 digits and is a part of the serial number
The operating period is measured and displayed in hours given on the rating plate.
with a resolution of 0.1 h. The operating hours meter The serial number cannot be changed.
cannot be reset.
Serial number
70
UMG 96RM-E
“Drag indicator”
Max. value of the mean value over n minutes
71
UMG 96RM-E
Recordings
Connecting the supply voltage The UMG 96RM-E is designed for the connection
of .. /1A and .. /5A current transformers.
• The power supply voltage level for the UMG 96RM-E Only AC currents can be measured via the current
is given on the rating plate. measurement inputs - DC currents cannot.
• After applying the power supply voltage the device Short circuit all current transformer outputs except for
switches on to display the first measured value. one. Compare the currents displayed by the UMG 96RM
• If no display appears, check whether the power supply with the applied current.
voltage is within the rated voltage range. Bearing in mind the current transformer conversion
ratio, the current displayed by the UMG 96RM-E must
Applying the measuring-circuit voltage correspond with the input current.
The UMG 96RM-E must display approx. zero amperes
• Measurement of voltages in the mains with over in the short-circuited current measurement inputs.
300VAC to earth must be connected via voltage The current transformer ratio is factory set to 5/5A
transformers. and must be adapted to the current transformer used
• After connecting the measurement-current voltages, if necessary.
the measured values displayed by the UMG 96RM-E
for the L-N and L-L voltages must correspond to those
at the voltage measurement input.
m Caution!
If the supply voltage does not correspond
to the voltage indicated on the rating
plate, this may lead to malfunctions severe
m
damage to the device.
Caution!
Voltages and currents that are outside
the permissible measuring range can lead
to personal injury and damage the device. m Caution!
The UMG 96RM is not suitable for
measuring DC voltages.
73
UMG 96RM-E
Check the direction of the voltage rotating field Connect residual current transformer only to the I5
in the measured value display of the UMG 96RM‑E. and I6 inputs with a rated current of 30mA! Both residual
A “right” rotating field usually exists. current inputs can measure AC currents, pulsing direct
currents and DC currents.
Check phase assignment
Bearing in mind the current transformer conversion ratio,
The assignment of the outer conductors to the current the residual current displayed by the UMG96RM-E must
transformer is correct, if a current transformer is short correspond with the input current.
circuited on the secondary, and the current indicated
by the UMG 96RM-E drops to 0A in the corresponding The current transformer ratio is factory set to 5/5A
phase. and must be adapted to the residual current transformer
used if necessary.
Checking the energy measurement
C
of the power output is negative, It is not necessary to configure a
• S1(k) and S2(l) could be inverted at the current connection schematic for residual current
transformer inputs I5 and I6.
• or they supply active energy back into the network.
74
UMG 96RM-E
m
The UMG96RM-E enables continuous monitoring of the
connection to the residual current transformer on inputs The failure monitoring is only available from
I5 and I6. firmware-ver. 202 and hardware-release
104!
Activation of failure monitoring is performed by setting
m
address 21264 for the residual-current measurement
Monitoring of the connection to the residual
input I5 and 21265 for I6.
current transformer is only available in AC
mode!
If there is an interruption in the connection to the current
transformer, this state is recorded in certain registers or
indicated in the GridVis software:
75
UMG 96RM-E
00110000 00000000
Unused
Failure monitoring
Alarm
Overcurrent
Warning
76
UMG 96RM-E
If all voltage and current inputs are correctly connected, If all voltages, currents and outputs for the respective
the individual and cumulative outputs are computed outer conductors are correctly displayed, the total
and displayed correctly. power outputs measured by the UMG 96RM must also
be correct. To confirm this, the total outputs measured
Checking the individual outputs by the UMG 96RM should be compared with the work
of the active and reactive power meters located
In case that a current transformer is assigned in the incoming supply.
to the wrong outer conductor, the corresponding power
output will be measured and indicated incorrectly.
The assignment of the outer conductor
and the UMG 96RM-E current transformer is correct,
if no voltage is measured between the outer conductor
and the corresponding current transformer (primary).
In order to ensure that an outer conductor at the voltage
measurement input is assigned to the correct current
transformer, the respective current transformer can
be short-circuited on the secondary side. The apparent
power displayed by the UMG 96RM-E must then
be approx. zero in this phase.
77
UMG 96RM-E
RS485 interface
The MODBUS RTU protocol with CRC check Number format: short 16 bit (-215 .. 215 -1.
on the RS485 interface can be used to access the data float 32 bit (IEEE 754)
from the parameter and the measured value lists.
Address range: 1 .. 247
Factory default setting: 1
C
The device is factory set to address 1 and the baud rate Broadcast (address 0) is not supported
of 115,2 kbps. by the device.
Transmission parameters:
Data bits: 8
Parity: no
Stop bits (UMG 96RM): 2
External stop bits: 1 or 2
78
UMG 96RM-E
The Query Message appears as follows: The Response of the UMG96 RM-E can appear
as follows:
79
UMG 96RM-E
Digital outputs
=
- S1 S2 S3
- -
24V = =
DC + +
K1 K2 K3 K4 K5 Fig.: Software GridVis, configuration menu
13 14 15 28 29 30 31
Group 11
Gruppe Group 2 2
Gruppe
Digital inputs/outputs
Digital-Eingänge/Ausgänge
C
The status of the switching outputs of group 1 is
indicated by circular symbols in the display of the Since the indication is updated once
UMG 96RM-E. per second, faster status changes
of the outputs can not be displayed.
Group 1
Status digital output 1
Status digital output 2
81
UMG 96RM-E
Impulse output
• Digital output,
• Selection of source,
• Selection of measured value,
• Pulse length,
• Pulse value.
82
UMG 96RM-E
Pulse length
The pulse length applies to both pulse outputs and is set The values in the table are based on the minimum pulse
by the software GridVis. length and the minimum pulse interval for the maximum
number of pulses per hour.
The typical pulse length of S0 pulse is 30ms.
C Pulse interval
The pulse interval is proportional to
the power output within the selected
C Measured value selection
When programming with GridVis you
have a selection of work values which are
settings. derived from the power output values.
83
UMG 96RM-E
Pulse value
86
UMG 96RM-E
Comparator
running time
87
UMG 96RM-E
Device homepage
Your measurement device features an integrated web Please compare with TCP/IP Konfiguration (page 55)
server with its own homepage. You can use this device You can execute the following functions via
home page to access your measurement device from the homepage without prior software installation:
any end device via a standard web browser. You can • Retrieve measured values
access the homepage for your device by entering • Control your device remotely
the measuring device’s PI address in a web browser on • Access installed apps
your end device.
Note:
Please observe that a measurement duration of at least
two hours are required to display energy values.
88
UMG 96RM-E
Measured values
Short overview
Display the most important measured values for each phase, e.g.
the current voltage values, power values and current strength.
89
UMG 96RM-E
Apps Information
You have the option of extending the functions on your Device information
device retrospectively by installing the “measured value Information about
monitor” app. • device name and description
Use “measured values monitor“ to display historical and • HP/Lib version
real-time measurements via easily readable, web-based • Firmware status
graphics. External servers and additional software are • Serial number
not required for this. • Current and voltage converter conditions
Additional information about the “measured values • IP address and subnet mask
monitor” are provided on our homepage.
90
UMG 96RM-E
Downloads
Help
Error correction
Additional information about possible error causes
and the associated help methods.
91
UMG 96RM-E
The device is subjected to several different safety tests Should questions arise, which are not described
before leaving the factory and is labelled with a seal. in this manual, please contact the manufacturer directly.
If a device is opened then the safety checks must
be repeated. Warranty claims will only be accepted We will need the following information from you
if the device is unopened. to answer any questions:
92
UMG 96RM-E
If the device is connected to a computer via Ethernet, The internal clock is fed from the supply voltage.
then the device firmware can be updated via the GridVis If the supply voltage fails then the clock is powered
software. by the battery. The clock provides date and time
information, for the records, min. and max. values
Select a suitable update file (menu Extras / Update and results, for example.
device) and the device and the new firmware will
be transferred. The life expectancy of the battery is at least 5 years
with a storage temperature of +45°C. The typical life
expectancy of the battery is 8 to 10 years.
93
UMG 96RM-E
94
UMG 96RM-E
Procedure
1. Disconnect system and device from power supply
before beginning work.
2. Discharge any electrostatic charge in your body,
e. g. by touching an earthed cabinet or metal part
(radiator) connected to the earth of the building.
3. Remove the battery from the battery compartment, Fig. Battery insertion on the rear
—e.g. using long-nose pliers—. The device does
not need to be opened to do this as the battery
compartment can be accessed from the outside
(see figure on the right).
4. Make sure that the polarity is as shown
m Grease or dirt on the contact surfaces
form a transfer resistance that will
shorten the life of the battery. Only touch
on the insertion opening of the battery compartment the battery at the edges.
and slide the replacement battery into the battery
c
compartment. For this, use a battery compliant with
the description in the technical data. The battery must Dangerous voltage!
fulfil the safety requirements of UL1642. Otherwise, Danger to life or risk of serious injury.
there is a risk of combustion or explosion. Disconnect system and device from power
5. Dispose of the old battery according to the legal supply before beginning work.
regulations.
6. Start up the system and the device again and check
the functionality of the UMG 96-RM. Set the date
and time.
m Make sure that the correct type of battery
is used and observe correct polarity when
changing it.
95
UMG 96RM-E
The UMG 96RM-E can display four different error Warnings are minor errors
messages: that can be acknowledged
by buttons 1 or 2.
• warnings, The measured values
• clock/battery errors, continue to be retrieved
• fatal errors and and displayed. This error
• overranges. is displayed after each
voltage return.
In the case of warnings and fatal errors, the error Fig. Warning message
message is followed by the "EEE" symbol and an error with number 500
number. (mains frequency)
96
UMG 96RM-E
Clock/battery errors
Major errors
When a major error occurs, the device must be sent Example, error message 911:
to the manufacturer's service center for inspection
and adjustment. The error number consists of major e
rror 910 and internal
error cause 0x01.
Errors Error description
EEE Error while reading the calibration. In this example an error
910 occurred while reading
the calibration data from
Internal causes: EEPROM. The device
The UMG 96RM-E sometimes determines the cause has to be returned
of a major internal error with the following error code. to the manufacturer
for inspection and
Errors Error description adjustment.
0x01 EEPROM does not respond.
0x02 Address overrange.
0x04 Checksum error.
0x08 Error in the internal I2C bus.
97
UMG 96RM-E
Overranges
V = voltage path
A = current path
V = voltage path
Fig.: Indication
of the overrange in voltage
Indication of the phase (L1/ path L3.
L2/L3) with overrange.
The current phase l4
overranges occur as shown
in the figure below.
Overrange limits:
Fig.: Indication
I = 7 Aeff
of the overrange in current
UL-N = 300 Vrms
path l4
98
UMG 96RM-E
Parameter overrange
0x F F F F F F F F
Phase 1: 1 1
Phase 2: 2 2
Phase 3: 4 4
Phase 4 (I4): 8 8
Current:
U L-N
0xF2FFFFFF
0xFFF4FFFF
99
UMG 96RM-E
100
UMG 96RM-E
Device still does not work Device defective. Send the device to the manufacturer for
despite the above measures. inspection and testing along with an accurate
fault description.
101
UMG 96RM-E
Technical data
General information
Net weight (with attached connectors) approx. 370g
Packaging weight (including accessories) approx. 950g
Battery Lithium battery CR2032, 3V (approval i.a.w. UL 1642)
Service life of background lighting 40000h (after this period of time the background lighting
efficiency will reduce by approx. 50 %)
102
UMG 96RM-E
103
UMG 96RM-E
Digital outputs
2 and 3 optional digital outputs, semiconductor relays, not short-circuit proof.
Switching voltage max. 33V AC, 60V DC
Switching current max. 50mAeff AC/DC
Response time 10/12 periods + 10ms *
Pulse output (energy pulse) max. 50Hz
Digital inputs
3 optional digital inputs, semiconductor relays, not short-circuit proof.
Maximum counter frequency 20Hz
Input signal present 18V .. 28V DC (typical 4mA)
Input signal not present 0 .. 5V DC, current less than 0.5mA
104
UMG 96RM-E
105
UMG 96RM-E
Serial interface
RS485 - Modbus RTU/Slave 9.6kbps, 19.2kbps, 38.4kbps, 57.6 kbps, 115.2kbps
Stripping length 7mm
Measuring voltage
Three-phase 4-conductor systems with nominal voltages up to 277V/480V (+-10%)
Three-phase 3-conductor systems, unearthed, IT 480V (+-10%)
with nominal voltages up to
Overvoltage category 300V CAT III
Measurement surge voltage 4kV
Measurement range L-N 01) .. 300Vrms
(max. surge voltage 520Vrms )
Measurement range L-L 01) .. 520Vrms
(max. surge voltage 900Vrms )
Resolution 0.01V
Crest factor 2,45 (related to the measurement range)
Impedance 3MΩ/phase
Power consumption apporx. 0,1VA
Sampling frequency 21.33kHz (50Hz); 25.6 kHz (60Hz) per measurement channel
Frequency range of the basic oscillation 45Hz .. 65Hz
- Resolution 0.01Hz
1)
The UMG 96RM-E can only detect measurements when a voltage L1-N greater than 20V eff (4-wire measurement) at voltage input V1 or a voltage L1-L2 greater
than 34V eff (3-wire measurement) is applied.
106
UMG 96RM-E
Current measurement I1 - I4
Rated current 5A
Measurement range 0 .. 6Arms
Crest factor 1.98
Resolution 0.1mA (Display 0.01A)
Overvoltage category 300V CAT II
Measurement surge voltage 2kV
Power consumption approx. 0.2 VA (Ri=5mOhm)
Overload for 1 sec. 120A (sinusoidal)
Sampling frequency 20kHz
107
UMG 96RM-E
Ethernet connection
Connection RJ45
Functions Modbus gateway, embedded web server (HTTP)
Protocols TCP/IP, DHCP-Client (BootP), Modbus/TCP (Port 502),
ICMP (Ping), NTP, Modbus RTU over Ethernet (Port 8000),
FTP, SNMP
108
UMG 96RM-E
Terminal connection capacity (residual current or temperature measurement inputs and digital inputs / outputs)
Rigid/flexible 0.14 - 1.5mm2, AWG 28-16
Flexible with core end sheath without plastic sleeve 0.20 - 1.5mm2
Flexible with core end sheath with plastic sleeve 0.20 - 1.5mm2
Tightening torque 0.20 - 0.25Nm
Stripping length 7mm
109
UMG 96RM-E
Function parameters
Function Symbol Precision class Measurement range Display range
Total effective power P 0.55) (IEC61557-12) 0 .. 5.4 kW 0 W .. 999 GW *
Total reactive power QA, Qv 1 (IEC61557-12) 0 .. 5.4 kvar 0 varh .. 999 Gvar *
Total apparent power SA, Sv 0.55) (IEC61557-12) 0 .. 5.4 kVA 0 VA .. 999 GVA *
Total active energy Ea 0.55) (IEC61557-12) 0 .. 5.4 kWh 0 Wh .. 999 GWh *
0.5S5) (IEC62053-22)
Total reactive power ErA, ErV 1 (IEC61557-12) 0 .. 5.4 kvarh 0 varh .. 999 Gvarh *
Total apparent energy EapA, EapV 0.55) (IEC61557-12) 0 .. 5.4 kVAh 0 VAh .. 999 GVAh *
Frequency f 0.05 (IEC61557-12) 45 .. 65Hz 45.00Hz .. 65.00Hz
Phase current I1 - I3 I 0.2 (IEC61557-12) 0 .. 6 Arms 0 A .. 999 kA
Measured neutral conductor current l4 IN 1 (IEC61557-12) 0 .. 6 Arms 0 A .. 999 kA
Residual currents I5, I6 IRes 1 (IEC61557-12) 0 .. 40 mArms 0 A .. 999 kA
Computed neutral conductor current INc 1.0 (IEC61557-12) 0.03 .. 25 A 0.03 A .. 999 kA
Voltage U L-N 0.2 (IEC61557-12) 10 .. 300 Vrms 0 V .. 999 kV
Voltage U L-L 0.2 (IEC61557-12) 18 .. 520 Vrms 0 V .. 999 kV
Power factor PFA, PFV 0.5 (IEC61557-12) 0.00 .. 1.00 0.00 .. 1.00
Short-term flicker, long-term flicker Pst, Plt - - -
Voltage drops (L-N) Udip - - -
Voltage increases (L-N) Uswl - - -
Transient overvoltages Utr - - -
Voltage drops Unit - - -
Voltage unbalance (L-N) 1) Unba - - -
Voltage unbalance (L-N) 2) Unb - - -
Voltage harmonics Uh Kl. 1 (IEC61000-4-7) up to 2.5 kHz 0 V .. 999 kV
THD of the voltage 3) THDu 1.0 (IEC61557-12) up to 2.5 kHz 0 % .. 999 %
THD of the voltage 4) THD-Ru - - -
Function Symbol Precision class Measurement range Display range
110
UMG 96RM-E
111
UMG 96RM-E
C
The following excerpt of the parameter list provides A complete overview of the parameters and
the settings that are necessary for the proper operation measured values as well as explanations
of the UMG 96RM-E, such as current transformer regarding the selected measured values
and device addresses. The valuesin the parameter list is filed in the document “Modbus Address
can be set and read. List” on the CD or Internet.
The THD and FFT voltages can be displayed as L-N or L-L values. 0=LN, 1=LL
C Only the first 3 digits (###) of a value are displayed on the screen. Values greater than
1000 are marked with "k". Example: 003k = 3000
115
UMG 96RM-E
Modbus address
Address via Display Format RD/WR Unit Note
19000 808 float RD V Voltage L1-N
19002 810 float RD V Voltage L2-N
19004 812 float RD V Voltage L3-N
19006 814 float RD V Voltage L1-L2
19008 816 float RD V Voltage L2-L3
19010 818 float RD V Voltage L3-L1
19012 860 float RD A Current, L1
19014 862 float RD A Current, L2
19016 864 float RD A Current, L3
19018 866 float RD A Vector sum; IN=I1+I2+I3
19020 868 float RD W Real power L1
19022 870 float RD W Real power L2
19024 872 float RD W Real power L3
19026 874 float RD W Sum; Psum3=P1+P2+P3
19028 884 float RD VA Apparent power S L1
19030 886 float RD VA Apparent power S L2
116
UMG 96RM-E
Modbus Address
address via Display Format RD/WR Unit Note
19032 888 float RD VA Apparent power S L3
19034 890 float RD VA Sum; Ssum3=S1+S2+S3
19036 876 float RD var Fund. reactive power (mains frequ.) Q L1
19038 878 float RD var Fund. reactive power (mains frequ.) Q L2
19040 880 float RD var Fund. reactive power (mains frequ.) Q L3
19042 882 float RD var Sum; Qsum3=Q1+Q2+Q3
19044 820 float RD - Fund.power factor, CosPhi; U L1-N IL1
19046 822 float RD - Fund.power factor, CosPhi; U L2-N IL2
19048 824 float RD - Fund.power factor, CosPhi; U L3-N IL3
19050 800 float RD Hz Measured frequency
19052 - float RD - Rotation field; 1=right, 0=none, -1=left
19054 - float RD Wh Real energy L1
19056 - float RD Wh Real energy L2
19058 - float RD Wh Real energy L3
19060 - float RD Wh Real energy L1..L3
19062 - float RD Wh Real energy L1, consumed
19064 - float RD Wh Real energy L2, consumed
19066 - float RD Wh Real energy L3, consumed
19068 - float RD Wh Real energy L1..L3, consumed, rate 1
19070 - float RD Wh Real energy L1, delivered
19072 - float RD Wh Real energy L2, delivered
19074 - float RD Wh Real energy L3, delivered
19076 - float RD Wh Real energy L1..L3, delivered
19078 - float RD VAh Apparent energy L1
19080 - float RD VAh Apparent energy L2
19082 - float RD VAh Apparent energy L3
19084 - float RD VAh Apparent energy L1..L3
19086 - float RD varh Reactive energy L1
19088 - float RD varh Reactive energy L2
19090 - float RD varh Reactive energy L3
19092 - float RD varh Reactive energy L1..L3
117
UMG 96RM-E
Modbus Address
address via Display Format RD/WR Unit Note
19094 - float RD varh Reactive energy, inductive, L1
19096 - float RD varh Reactive energy, inductive, L2
19098 - float RD varh Reactive energy, inductive, L3
19100 - float RD varh Reactive energy L1..L3, ind.
19102 - float RD varh Reactive energy, capacitive, L1
19104 - float RD varh Reactive energy, capacitive, L2
19106 - float RD varh Reactive energy, capacitive, L3
19108 - float RD varh Reactive energy L1..L3, cap.
19110 836 float RD % Harmonic, THD, U L1-N
19112 838 float RD % Harmonic, THD, U L2-N
19114 840 float RD % Harmonic, THD, U L3-N
19116 908 float RD % Harmonic, THD, I L1
19118 910 float RD % Harmonic, THD, I L2
19120 912 float RD % Harmonic, THD, I L3
Modbus Address
address via display Format RD/WR Unit Note Adjustment range Default
20006 - float RD/WR A TDD I4, full-load current 0...1000000 150
20008 - float RD/WR A current transformer I4, primary 0...1000000 5
20010 - float RD/WR A current transformer I4, secondary 1..5 5
20012 - float RD/WR A current transformer I5, primary 0..1000000 5
20014 - float RD/WR A current transformer I5, secondary 0,001...5 5
20016 - float RD/WR A current transformer I6, primary 0...1000000 5
20018 - float RD/WR A current transformer I6, secondary 0,001...5 5
118
UMG 96RM-E
Number formats
NOTE
Type Size Minimum Maximum
Note on saving measured values and configuration
short 16 bit -215 215 -1
data:
ushort 16 bit 0 216 -1 Since the following measured values are saved in a
int 32 bit -231 231 -1 non-volatile memory every 5 minutes, the recording
may be interrupted for a maximum of 5 minutes in
uint 32 bit 0 232 -1
case the operating voltage fails:
float 32 bit IEEE 754 IEEE 754 · Comparator timer
· S0 counter statuses
· Min. / Max. / mean values
(without the date and time)
· Energy values
Configuration data is saved immediately.
A detailed Modbus address and parameter list can be
found at www.janitza.com
119
UMG 96RM-E
Dimension diagrams
□ 91,5
110,5
120
UMG 96RM-E
ca. 90
92+0,8
72 (depth without connector)
96
91,5
104
92+0,8
6 57
78
121
UMG 96RM-E
122
UMG 96RM-E
123
UMG 96RM-E
A15
Measured value
L1 cos(phi)
L2 cos(phi)
L3 cos(phi)
A16 B16
A17
Measured value
Frequency L1
Rotation field display
Measured value Measured value Measured value Measured value Measured value Measured value Measured value
Total active energy Total active energy Total active energy Sum Active energy L1 Active energy L2 Active energy L3
(without a backstop) (import) (export) Apparent energy Import (tariff 1) Import (tariff 1) Import (tariff 1)
Marked menus are not displayed in the factory presetting. * Only the first 6 comparators are shown.
124
UMG 96RM-E
125
UMG 96RM-E
Max. values
Measured values Mean values Maximum values
(mean value)
L4 current L4 current L4 current
L4 current
Max. values
Measured values Mean values Maximum values
(mean value)
L5 current L5 current L5 current
L5 current
Even and odd harmonics
A35 B35 C35 D35 up to the 40th order can
Max. values be called up via the GridVis
Measured values Mean values Maximum values
L6 current L6 current L6 current
(mean value) software and can be viewed
L6 current
in the software.
Marked menus are not displayed in the factory presetting.
126
UMG 96RM-E
This equipment has been tested and found to comply with the
limits for a Class B digital device, pursuant to part 15 of the FCC
Rules. These limits are designed to provide reasonable protection
against harmful interference in a residential installation. This equip-
ment generates, uses and can radiate radio frequency energy and,
if not installed and used in accordance with the instructions, may
cause harmful interference to radio communications. However,
there is no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to
radio or television reception, which can be determined by turning
the equipment off and on, the user is encouraged to try to correct
the interference by one or more of the following measures:
127
UMG 96RM-E
Connection example 1
(with residual current measurement IPE / IRES)
=
- S1 S2 S3
IDIFF IPE
- - B
24V = =
DC + + A
K1 K2 K3 K4 K5 0-30 mA 0-30 mA
4) 4)
13 14 15 28 29 30 31 32 33 34 35 36 37 16 17
Group 11
Gruppe Group 2
Gruppe 2 I5 I6 B A
RS485
Digital inputs/outputs
Digital-Eingänge/Ausgänge Analog inputs
Analog-Eingänge
10/100Base-T
Ethernet
UMG 96RM-E (RCM) PC
RJ45
Power supply
Versorgungs- Measuring voltage Current measurement
Spannungsmessung Strommessung
voltage
spannung
N/- L/+ V1 V2 V3 VN I4
S2 S1 S2 S1 S2 S1 S2 S1
1 2 3 4 5 6 19 18
1) 2) 2) 2) 3) 3) 3) 3) 1)
UL / IEC approved overcurrent
protection system (6A Char. B)
2)
UL / IEC approved overcurrent
S2 S1
protection system
L1 (10A Class CC / Char. C)
Verbraucher
Consumer
S2 S1
L2 3)
Jumpers (external)
S2 S1
L3
4)
Jumpers between connectors
S2 S1 32-33 and 35-36 are only required
N
230V/400V 50Hz from hardware-release 104!
128
UMG 96RM-E
Connection example 2
(with temperature and residual current measurement)
=
- S1 S2 S3
IDIFF
- - PT100 B
24V = =
DC + + A
K1 K2 K3 K4 K5 0-30 mA
4)
13 14 15 28 29 30 31 32 33 34 35 36 37 16 17
Group 11
Gruppe Group 22
Gruppe I5 I6 B A
10/100Base-T
Ethernet
UMG 96RM-E (RCM) PC
RJ45
Power supply
Versorgungs- Measuring voltage Current measurement
voltage
Spannungsmessung Strommessung
spannung
N/- L/+ V1 V2 V3 VN I4
S2 S1 S2 S1 S2 S1 S2 S1
1 2 3 4 5 6 19 18
1) 2) 2) 2) 3) 3) 3) 3) 1)
UL / IEC approved overcurrent
protection system (6A Char. B)
2)
UL / IEC approved overcurrent
S2 S1
protection system
L1 (10A Class CC / Char. C)
Verbraucher
Consumer
S2 S1
L2 3)
Jumpers (external)
S2 S1
L3
4)
Jumpers between connectors
S2 S1 35-36 are only required from
N
230V/400V 50Hz hardware-release 104!
129
UMG 96RM-E
130
UMG 96RM-E
132