0% found this document useful (0 votes)
67 views5 pages

I-Converter Com

The document contains operating data from a York International Latitude screw chiller. System 1's compressor is running while systems 2 and 3 are not running. The chiller is cooling water to a leaving liquid temperature of 7.2°C and is in local control mode. System 1 has been running for 1 hour, 15 minutes and 58 seconds.

Uploaded by

widya
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
67 views5 pages

I-Converter Com

The document contains operating data from a York International Latitude screw chiller. System 1's compressor is running while systems 2 and 3 are not running. The chiller is cooling water to a leaving liquid temperature of 7.2°C and is in local control mode. System 1 has been running for 1 hour, 15 minutes and 58 seconds.

Uploaded by

widya
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

##################################

# YORK INTERNATIONAL CORPORATION


# LATITUDE SCREW CHILLER

# OPERATING DATA
# 5:52:02 PM 15 NOV 2023

#SYS 1
#COMPRESSOR RUNNING
#SYS 2
#NOT RUNNING
#SYS 3
#NOT RUNNING

# OPTIONS
#CHILLED LIQUID WATER
#LOCAL/REMOTE MODE LOCAL
#LEAD/LAG CONTROL AUTOMATIC
#LOW AMBIENT CUTOUT ENABLED

# PROGRAM VALUES
#SUCT PRESS CUTOUT 1.65 BARG
#LOW AMBIENT CUTOUT -3.9 DEGC
#LEAVING LIQUID CUTOUT 2.2 DEGC
#MOTOR CURRENT LIMIT 95 %FLA
#PULLDOWN CURRENT LIMIT 95 %FLA
#PULLDOWN LIMIT TIME 0 MIN
#SUCTION SUPERHEAT SETP 4.5 DEGC
#UNIT ID NUMBER 0

# UNIT DATA
#LEAVING LIQUID TEMP 7.2 DEGC
#RETURN LIQUID TEMP 8.7 DEGC
#COOLING RANGE 7.0 +/- 1.1 DEGC
#REMOTE SETPOINT XX.X DEGC
#AMBIENT AIR TEMP 30.1 DEGC
#LEAD SYSTEM SYS 1
#FLOW SWITCH ON
#EVAPORATOR PUMP RUN ON
#EVAPORATOR HEATER OFF
#ACTIVE REMOTE CONTROL NONE
#OPERATING HOURS 1=33657, 2=36783
# 3=27930
#START COUNTER 1= 5468, 2= 4660
# 3= 5171
#SOFTWARE VERSION C.A22.14.03
#UNIT SERIAL NUMBER 2GYM 016894

# VSD DATA
#ACTUAL FREQUENCY 199.8 HZ
#COMMAND FREQUENCY 199.8 HZ
#DC BUS VOLTAGE 496 VDC
#INTERNAL AMBIENT TEMP 39.1 DEGC
#COOLING SYSTEM STATUS ON
#BASEPLATE TEMP 54.4, 39.4 DEGC
#PRECHARGE SIGNAL ON
#MOTOR OVERLOADS 1/2 339 338 AMPS
#MOTOR OVERLOADS 3/4 339 AMPS
#VSD SOFTWARE VERSION C.VSD.89.01

# SYSTEM 1 DATA
#COMPRESSOR STATUS ON
#RUN TIME 1-15-57-13 D-H-M-S
#MOTOR CURRENT 276 AMPS 85 %FLA
#SUCTION PRESSURE 2.26 BARG
#DISCHARGE PRESSURE 12.6 BARG
#OIL PRESSURE 11.9 BARG
#SUCTION TEMPERATURE 7.3 DEGC
#DISCHARGE TEMPERATURE 69.9 DEGC
#OIL TEMPERATURE 49.6 DEGC
#SAT SUCTION TEMP 3.1 DEGC
#SUCTION SUPERHEAT 4.2 DEGC
#SAT DISCHARGE TEMP 51.4 DEGC
#DISCHARGE SUPERHEAT 18.5 DEGC
#MOTOR TMP 57.7 52.2 35.4 DEGC
#COMPRESSOR LOAD 99.9 %
#ECONOMIZER ON
#FLASH TANK LEVEL 0.0 %
#FEED VALVE % OPEN 100.0 %
#DRAIN VALVE % OPEN 57.4 %
#CONDENSER FANS ON 6
#COMPRESSOR HEATER OFF
#RUN PERMISSIVE ON
#VSD RUN RELAY ON
#VSD SOFTWARE RUN SIGNAL ON

# SYSTEM 2 DATA
#COMPRESSOR STATUS OFF
#RUN TIME 0- 0- 0- 0 D-H-M-S
#MOTOR CURRENT 1 AMPS 0 %FLA
#SUCTION PRESSURE 3.14 BARG
#DISCHARGE PRESSURE 3.0 BARG
#OIL PRESSURE 3.1 BARG
#SUCTION TEMPERATURE 26.4 DEGC
#DISCHARGE TEMPERATURE 32.2 DEGC
#OIL TEMPERATURE 30.6 DEGC
#SAT SUCTION TEMP 10.1 DEGC
#SUCTION SUPERHEAT 16.3 DEGC
#SAT DISCHARGE TEMP 9.5 DEGC
#DISCHARGE SUPERHEAT 22.7 DEGC
#MOTOR TMP 43.3 45.3 40.3 DEGC
#COMPRESSOR LOAD 0.0 %
#ECONOMIZER OFF
#FLASH TANK LEVEL 7.4 %
#FEED VALVE % OPEN 0.0 %
#DRAIN VALVE % OPEN 0.0 %
#CONDENSER FANS ON 0
#COMPRESSOR HEATER ON
#RUN PERMISSIVE ON
#VSD RUN RELAY OFF
#VSD SOFTWARE RUN SIGNAL OFF

# SYSTEM 3 DATA
#COMPRESSOR STATUS OFF
#RUN TIME 0- 0- 0- 0 D-H-M-S
#MOTOR CURRENT 0 AMPS 0 %FLA
#SUCTION PRESSURE 2.79 BARG
#DISCHARGE PRESSURE 2.8 BARG
#OIL PRESSURE 2.7 BARG
#SUCTION TEMPERATURE 32.4 DEGC
#DISCHARGE TEMPERATURE 35.1 DEGC
#OIL TEMPERATURE 31.1 DEGC
#SAT SUCTION TEMP 7.4 DEGC
#SUCTION SUPERHEAT 25.0 DEGC
#SAT DISCHARGE TEMP 7.5 DEGC
#DISCHARGE SUPERHEAT 27.5 DEGC
#MOTOR TMP 49.3 50.8 45.6 DEGC
#COMPRESSOR LOAD 0.0 %
#ECONOMIZER OFF
#FLASH TANK LEVEL 0.3 %
#FEED VALVE % OPEN 0.0 %
#DRAIN VALVE % OPEN 0.0 %
#CONDENSER FANS ON 0
#COMPRESSOR HEATER ON
#RUN PERMISSIVE ON
#VSD RUN RELAY ON
#VSD SOFTWARE RUN SIGNAL OFF

# UNIT OPERATING SCHEDULE


#S M T W T F S *=HOLIDAY
#SUN START=00:00AM STOP=00:00AM
#MON START=00:00AM STOP=00:00AM
#TUE START=00:00AM STOP=00:00AM
#WED START=00:00AM STOP=00:00AM
#THU START=00:00AM STOP=00:00AM
#FRI START=00:00AM STOP=00:00AM
#SAT START=00:00AM STOP=00:00AM
#HOL START=00:00AM STOP=00:00AM

##################################

# YORK INTERNATIONAL CORPORATION


# LATITUDE SCREW CHILLER

# OPERATING DATA
# 5:53:02 PM 15 NOV 2023

#SYS 1
#COMPRESSOR RUNNING
#SYS 2
#NOT RUNNING
#SYS 3
#NOT RUNNING

# OPTIONS
#CHILLED LIQUID WATER
#LOCAL/REMOTE MODE LOCAL
#LEAD/LAG CONTROL AUTOMATIC
#LOW AMBIENT CUTOUT ENABLED

# PROGRAM VALUES
#SUCT PRESS CUTOUT 1.65 BARG
#LOW AMBIENT CUTOUT -3.9 DEGC
#LEAVING LIQUID CUTOUT 2.2 DEGC
#MOTOR CURRENT LIMIT 95 %FLA
#PULLDOWN CURRENT LIMIT 95 %FLA
#PULLDOWN LIMIT TIME 0 MIN
#SUCTION SUPERHEAT SETP 4.5 DEGC
#UNIT ID NUMBER 0

# UNIT DATA
#LEAVING LIQUID TEMP 7.2 DEGC
#RETURN LIQUID TEMP 8.7 DEGC
#COOLING RANGE 7.0 +/- 1.1 DEGC
#REMOTE SETPOINT XX.X DEGC
#AMBIENT AIR TEMP 30.2 DEGC
#LEAD SYSTEM SYS 1
#FLOW SWITCH ON
#EVAPORATOR PUMP RUN ON
#EVAPORATOR HEATER OFF
#ACTIVE REMOTE CONTROL NONE
#OPERATING HOURS 1=33657, 2=36783
# 3=27930
#START COUNTER 1= 5468, 2= 4660
# 3= 5171
#SOFTWARE VERSION C.A22.14.03
#UNIT SERIAL NUMBER 2GYM 016894

# VSD DATA
#ACTUAL FREQUENCY 199.9 HZ
#COMMAND FREQUENCY 199.9 HZ
#DC BUS VOLTAGE 497 VDC
#INTERNAL AMBIENT TEMP 39.1 DEGC
#COOLING SYSTEM STATUS ON
#BASEPLATE TEMP 54.4, 39.4 DEGC
#PRECHARGE SIGNAL ON
#MOTOR OVERLOADS 1/2 339 338 AMPS
#MOTOR OVERLOADS 3/4 339 AMPS
#VSD SOFTWARE VERSION C.VSD.89.01

# SYSTEM 1 DATA
#COMPRESSOR STATUS ON
#RUN TIME 1-15-58-14 D-H-M-S
#MOTOR CURRENT 274 AMPS 84 %FLA
#SUCTION PRESSURE 2.25 BARG
#DISCHARGE PRESSURE 12.5 BARG
#OIL PRESSURE 11.8 BARG
#SUCTION TEMPERATURE 7.7 DEGC
#DISCHARGE TEMPERATURE 69.9 DEGC
#OIL TEMPERATURE 49.4 DEGC
#SAT SUCTION TEMP 3.1 DEGC
#SUCTION SUPERHEAT 4.7 DEGC
#SAT DISCHARGE TEMP 51.2 DEGC
#DISCHARGE SUPERHEAT 18.8 DEGC
#MOTOR TMP 57.4 51.9 35.3 DEGC
#COMPRESSOR LOAD 99.9 %
#ECONOMIZER ON
#FLASH TANK LEVEL 0.0 %
#FEED VALVE % OPEN 100.0 %
#DRAIN VALVE % OPEN 57.7 %
#CONDENSER FANS ON 6
#COMPRESSOR HEATER OFF
#RUN PERMISSIVE ON
#VSD RUN RELAY ON
#VSD SOFTWARE RUN SIGNAL ON

# SYSTEM 2 DATA
#COMPRESSOR STATUS OFF
#RUN TIME 0- 0- 0- 0 D-H-M-S
#MOTOR CURRENT 1 AMPS 0 %FLA
#SUCTION PRESSURE 3.14 BARG
#DISCHARGE PRESSURE 3.0 BARG
#OIL PRESSURE 3.1 BARG
#SUCTION TEMPERATURE 26.4 DEGC
#DISCHARGE TEMPERATURE 32.2 DEGC
#OIL TEMPERATURE 30.6 DEGC
#SAT SUCTION TEMP 10.1 DEGC
#SUCTION SUPERHEAT 16.3 DEGC
#SAT DISCHARGE TEMP 9.5 DEGC
#DISCHARGE SUPERHEAT 22.7 DEGC
#MOTOR TMP 43.3 45.2 40.3 DEGC
#COMPRESSOR LOAD 0.0 %
#ECONOMIZER OFF
#FLASH TANK LEVEL 7.4 %
#FEED VALVE % OPEN 0.0 %
#DRAIN VALVE % OPEN 0.0 %
#CONDENSER FANS ON 0
#COMPRESSOR HEATER ON
#RUN PERMISSIVE ON
#VSD RUN RELAY OFF
#VSD SOFTWARE RUN SIGNAL OFF

# SYSTEM 3 DATA
#COMPRESSOR STATUS OFF
#RUN TIME 0- 0- 0- 0 D-H-M-S
#MOTOR CURRENT 0 AMPS 0 %FLA
#SUCTION PRESSURE 2.79 BARG
#DISCHARGE PRESSURE 2.7 BARG
#OIL PRESSURE 2.7 BARG
#SUCTION TEMPERATURE 32.4 DEGC
#DISCHARGE TEMPERATURE 35.0 DEGC
#OIL TEMPERATURE 31.1 DEGC
#SAT SUCTION TEMP 7.4 DEGC
#SUCTION SUPERHEAT 25.0 DEGC
#SAT DISCHARGE TEMP 7.4 DEGC
#DISCHARGE SUPERHEAT 27.5 DEGC
#MOTOR TMP 49.3 50.7 45.6 DEGC
#COMPRESSOR LOAD 0.0 %
#ECONOMIZER OFF
#FLASH TANK LEVEL 0.3 %
#FEED VALVE % OPEN 0.0 %
#DRAIN VALVE % OPEN 0.0 %
#CONDENSER FANS ON 0
#COMPRESSOR HEATER ON
#RUN PERMISSIVE ON
#VSD RUN RELAY ON
#VSD SOFTWARE RUN SIGNAL OFF

# UNIT OPERATING SCHEDULE


#S M T W T F S *=HOLIDAY
#SUN START=00:00AM STOP=00:00AM
#MON START=00:00AM STOP=00:00AM
#TUE START=00:00AM STOP=00:00AM
#WED START=00:00AM STOP=00:00AM
#THU START=00:00AM STOP=00:00AM
#FRI START=00:00AM STOP=00:00AM
#SAT START=00:00AM STOP=00:00AM
#HOL START=00:00AM STOP=00:00AM

##