Full Load
Watts per Strating Running
Load Details No Load DF PF SCM PF PF
Load 1 CFL 4 80 0.8 0.8 1 0.8 0.8
Load 2 AC 2 3000 1 0.8 1.6 0.8 0.8
Load 3 Halogen bulb 2 500 0.8 0.7 1.6 0.8 0.8
Load 4 Motor with Y-Δ starter 1 10000 0.8 0.7 4 0.7 0.8
Load 5 Motor with Soft starter 1 120000 0.8 0.7 2 0.7 0.8
Total
Size of Generator in KVA = Starting KVA * Future Expansion*
333.92 1.1
293.8496
Types of Loads SCM
Linear Load 1
Non Linear Load (UPS, Inverter, 1.6
Computer, Ballast)
DOL Starter 6
Y-Δ Starter 4
Auto Tr Starter 3
Soft Starter 2
VFD Starter 1.5
Full Load Condition Starting Condition
Starting
KW
Full Load Full Load KW(total
KW(total current in no*Full Starting
no*Full Full Load A= (Full load KVA= Starting
load KVA= Full load watts per Starting Current =
watts per Load KW/ KVA/ load* KW/ Full Load
load*DF/ Running Viltage)* DF*SCM/ Starting Current *
1000 PF 1000 1000 PF SCM
0.256 0.32 1.391304 0.256 0.32 1.391304
6 7.5 32.6087 9.6 12 52.17391
0.8 1 4.347826 1.28 1.6 6.956522
8 10 43.47826 32 45.71429 173.913
96 120 161.312 192 274.2857 322.624
Total 138.82 243.1381 333.92 557.0588
Future Expansion* Average Use
1.1 0.8
Standered Generator Ratings
1 2 4 6 8
10 25 3 50 63
75 100 132 160 200
225 320 400 500 630
750 1000 1250 1450 1500
1600 1800 2000 2500 3000
3500 4000 4500 5000