                               Operating Instructions
                               Deltabar S FMD77, FMD78,
                               PMD75
                               Differential pressure measurement
                                        Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
Serial number
A0023555
           Make sure the document is stored in a safe place such that it is always available when
           working on or with the device.
           To avoid danger to individuals or the facility, read the "Basic safety instructions" section
           carefully, as well as all other safety instructions in the document that are specific to
           working procedures.
           The manufacturer reserves the right to modify technical data without prior notice. Your
           Endress+Hauser Sales Center will supply you with current information and updates to these
           Instructions.
2                                                                                     Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
Table of contents
1     Document information . . . . . . . . . . . . . . 4                               7.9 Scaling the OUT parameter . . . . . . . . . . . . . . . . . . 74
                                                                                       7.10 Configuring event behavior in accordance with
1.1   Document function . . . . . . . . . . . . . . . . . . . . . . . . . . 4               FOUNDATION Fieldbus Specification FF912 Field
1.2   Symbols used . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4          Diagnostic Profile . . . . . . . . . . . . . . . . . . . . . . . . . . 75
6     Operation. . . . . . . . . . . . . . . . . . . . . . . . . 29
6.1   Onsite display (optional) . . . . . . . . . . . . . . . . . . .             29
6.2   Operating elements . . . . . . . . . . . . . . . . . . . . . . .            31
6.3   FOUNDATION Fieldbus interface . . . . . . . . . . . .                       33
6.4   Local operation – onsite display connected . . . .                          46
6.5   HistoROM®/M-DAT (optional) . . . . . . . . . . . . . .                      49
6.6   FieldCare . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   52
6.7   Locking/unlocking operation . . . . . . . . . . . . . . .                   52
6.8   Simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .    54
6.9   Factory setting (reset) . . . . . . . . . . . . . . . . . . . . .           54
7     Commissioning . . . . . . . . . . . . . . . . . . . . 57
7.1   Configuring messages . . . . . . . . . . . . . . . . . . . . . 57
7.2   Function check . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
7.3   Commissioning via an FF configuration program . .
      57
7.4   Selecting the language and measuring mode . . 59
7.5   Position adjustment . . . . . . . . . . . . . . . . . . . . . . . 60
7.6   Flow measurement . . . . . . . . . . . . . . . . . . . . . . . . 62
7.7   Level measurement . . . . . . . . . . . . . . . . . . . . . . . . 65
7.8   Differential pressure measurement . . . . . . . . . . 72
Endress+Hauser                                                                                                                                                            3
Document information                                          Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
1 Document information
Symbol Meaning
                                                  DANGER!
                           DANGER                 This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in
                                    A0011189-DE   seriousor fatal injury.
                                                  WARNING!
                           WARNING                This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in
                                    A0011190-DE   seriousor fatal injury.
                                                  CAUTION!
                           CAUTION                This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in
                                    A0011191-DE
                                                  minoror medium injury.
                                                  NOTICE!
                           NOTICE                 This symbol contains information on procedures and other facts which do not result in
                                    A0011192-DE   personalinjury.
Symbol Meaning
Allen key
A0011221
Hexagon wrench
A0011222
4                                                                                                                           Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                                                 Document information
Symbol Meaning
                                                       Permitted
                                                       Indicates procedures, processes or actions that are permitted.
                                            A0011182
                                                       Forbidden
                                                       Indicates procedures, processes or actions that are forbidden.
                                            A0011184
                                                       Tip
                                                       Indicates additional information.
                                            A0011193
Reference to documentation
A0015482
Reference to page
A0015484
Reference to graphic
A0015487
Visual inspection
A0015502
Symbol Meaning
A, B, C, D, ... Views
Symbol Meaning
                                                       Safety instructions
                                                       Observe the safety instructions contained in the associated Operating Instructions.
                                            A0019159
Endress+Hauser                                                                                                                               5
Basic safety instructions                              Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
6                                                                                                         Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                          Basic safety instructions
Endress+Hauser                                                                                                           7
Identification                                           Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
3 Identification
                 3.2.1              Nameplates
                 • The MWP (maximum working pressure) is specified on the nameplate. This value refers
                   to a reference temperature of 20°C (68°F) or 100°F (38 °C) for ASME flanges.
                 • The pressure values permitted at higher temperatures can be found in the following
                   standards:
                   – EN 1092-1: 2001 Tab. 18 1)
                   – ASME B 16.5a – 1998 Tab. 2-2.2 F316
                   – ASME B 16.5a – 1998 Tab. 2.3.8 N10276
                   – JIS B 2220
                 • For PMD75, the MWP applies for the temperature ranges specified in Technical
                   Information TI00382P in the "Ambient temperature range" and "Process temperature
                   limits" sections.
                 • The test pressure corresponds to the overpressure limit (OPL) of the device = MWP x 1.5.
                 • The Pressure Equipment Directive (EC Directive 97/23/EC) uses the abbreviation "PS". The
                   abbreviation "PS" corresponds to the MWP (maximum working pressure) of the measuring
                   device.
                 1)    With regard to their stability-temperature property, the materials 1.4435 and 1.4404 are grouped together
                       under 13EO in EN 1092-1 Tab. 18. The chemical composition of the two materials can be identical.
                                                  1
                                                  2         Order code:        Ser. no.:             5
                                                  3         Ext. order code:
4 6
A0016056
                 Fig. 1:        Nameplate
                 1         Device name
                 2         Order code (for re-orders)
                 3         Extended order code (complete)
                 4         Technical data
                 5         Serial number (for identification)
                 6         Address of manufacturer
8                                                                                                            Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                                                           Identification
Devices for use in hazardous areas are fitted with an additional nameplate.
A0021222
                          Devices suitable for oxygen applications or with PVDF process connection are fitted with an
                          additional nameplate.
A0022683
                                      1
                                      2
                                      3         Order code:
                                      4         Ext. ord. cd.:
                                      5         Ser. no.:
                                                                                                                                       7
                                      6
A0021552
                          Fig. 4:         Nameplate
                          1         Device name
                          2         Address of manufacturer
                          3         Order code (for re-orders)
                          4         Extended order code (complete)
                          5         Serial number (for identification)
                          6         Technical data
                          7         Approval-specific information and document number for safety instructions or drawing number
Endress+Hauser                                                                                                                                  9
Identification                             Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
10                                                                                            Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                                   Installation
                          4          Installation
                          NOTICE
                          Incorrect handling!
                          Damage of the device!
                          ‣ Disassembly of the screws with item number (1) is not permissible under any
                             circumstances and will result in loss of warranty.
                                                               1
                                                                                                                 A0025336
                          4.1.2      Transport
                           !   WARNING
                          Incorrect transport
                          Housing and diaphragm may be damaged and and there is a risk of injury!
                          ‣ Transport the measuring device to the measuring point in its original packaging or at the
                             process connection.
                          ‣ Follow the safety instructions and transport conditions for devices of more than 18 kg
                             (39.69 lbs).
                          4.1.3      Storage
                          The device must be stored in a dry, clean area and protected against impact (EN 837-2).
                          Storage temperature range:
                          • –40 to +90°C (–40 to +194 °F)
                          • Onsite display: –40 to +85°C (–40 to +185°F)
                          • Separate housing: –40 to +60°C (–40 to +140°F)
                          4.2.1      Dimensions
                          For dimensions, please refer to the Technical Information for Deltabar S TI00382P,
                          "Mechanical construction" section.
Endress+Hauser                                                                                                      11
Installation                                           Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
                                                                                       ➁
                                                                     ➂
                                                                         +       – ➃
P01-PMD75xxx-11-xx-xx-xx-000
               • Mount the Deltabar S above the measuring point so that the condensate can run off into
                 the process piping.
12                                                                                              Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                                         Installation
                                                                                     ➁
                                                                        ➂                        ➂
                                                                                         ➃
                                                                         +                      –
                                                                        ➄                         ➄
                                                                        ➅                         ➅
                                                                                                  ➆
                                                                                                            P01-PMD75xxx-11-xx-xx-xx-001
                                                                            ➁                      ➁
                                                                             +              ➂      –
                                                                            ➃                       ➃
                                                                            ➄                       ➄
                                                                                                    ➅
                                                                                                            P01-PMD75xxx-11-xx-xx-xx-002
                          • Mount the Deltabar S below the measuring point so that the pressure piping is always
                            filled with liquid and gas bubbles can run back into the process piping.
                          • When measuring in media with solid parts, such as dirty liquids, installing separators and
                            drain valves is useful for capturing and removing sediment.
Endress+Hauser                                                                                                                    13
Installation                                          Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
patm
min. + patm ➀
                                                                               ➃               ➁
                                                                               ➄
                                                                                       ➂
                                                                                                             P01-PMD75xxx-11-xx-xx-xx-003
               Fig. 8:       Measuring arrangement for level measurement in an open container with PMD75
               1         The negative side is open to atmospheric pressure
               2         Deltabar S, here PMD75
               3         Shutoff valve
               4         Separator
               5         Drain valve
               • Mount the Deltabar S below the lower measuring connection so that the pressure piping
                 is always filled with liquid.
               • The negative side is open to atmospheric pressure.
               • When measuring in media with solid parts, such as dirty liquids, installing separators and
                 drain valves is useful for capturing and removing sediment.
                                                                     patm
                                                         max.
                                                                               2
                                                                                       patm
                                                         min.                      –
                                                                                                   1
                                                                               +
                                                                                                                               A0024164
               Fig. 9:       Measuring arrangement for level measurement in an open container with FMD77
               1         Deltabar S, here FMD77
               2         The negative side is open to atmospheric pressure
               • Mount the Deltabar S directly on the container.  ä 20, Section 4.3.5 "Seal for flange
                 mounting".
               • The negative side is open to atmospheric pressure.
14                                                                                                         Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                                                         Installation
                                                                                      –➀
                                                                       max.
                                                                       min.               ➀
                                                                                      +
                                                                                                     ➁
                                                                                    ➂                         ➂
                                                                                    ➃                         ➃
                                                                                                              ➄
                                                                                                                            P01-PMD75xxx-11-xx-xx-xx-004
                          Fig. 10:       Measuring arrangement for level measurement in a closed container with PMD75
                          1          Shutoff valves
                          2          Deltabar S, PMD75
                          3          Separator
                          4          Drain valves
                          5          Three-way valve manifold
                          • Mount the Deltabar S below the lower measuring connection so that the pressure piping
                            is always filled with liquid.
                          • Always connect the impulse piping of negative side above the maximum level.
                          • When measuring in media with solid parts, such as dirty liquids, installing separators and
                            drain valves is useful for capturing and removing sediment.
                                                                                  –
                                                                max.
                                                                                                                        2
                                                                min.
                                                                                                                        3
                                                                                                 4
                                                                                  +
                                                                                                                                              A0024163
                          Fig. 11:       Measuring arrangement for level measurement in a closed container with FMD77
                          1          Shutoff valve
                          2          Separator
                          3          Drain valve
                          4          Deltabar S, here FMD77
                          • Mount the Deltabar S directly on the container.  ä 20, Section 4.3.5 "Seal for flange
                            mounting".
                          • Always connect the impulse piping of negative side above the maximum level.
                          • When measuring in media with solid parts, such as dirty liquids, installing separators and
                            drain valves is useful for capturing and removing sediment.
Endress+Hauser                                                                                                                                    15
Installation                                         Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
                                                                               –
                                                             max.
                                                                                               ➀
                                                                               +
                                                             min.
P01-FMD78xxx-11-xx-xx-xx-000
               Fig. 12:       Measuring arrangement for level measurement in a closed container with FMD78
               1          Deltabar S, here FMD78
               • Mount the Deltabar S below the lower diaphragm seal.  ä 19, Section 4.3.4 "Installation
                 instructions for devices with diaphragm seals (FMD78)".
               • The ambient temperature should be the same for both capillaries.
               Level measurement is only ensured between the upper edge of the lower diaphragm seal and
               the lower edge of the upper diaphragm seal.
                                                                          –                        ➀
                                                         max.
                                                                                                   ➁
                                                         min.                 ➁
                                                                          +
                                                                                        ➂
                                                                        ➃                          ➃
                                                                        ➄                          ➄
                                                                                                   ➅
                                                                                                                         P01-PMD75xxx-11-xx-xx-xx-005
               Fig. 13:       Measuring arrangement for level measurement in a container with superimposed steam with PMD75
               1          Condensate trap
               2          Shutoff valves
               3          Deltabar S, here PMD75
               4          Separator
               5          Drain valves
               6          Three-way valve manifold
               • Mount the Deltabar S below the lower measuring connection so that the pressure piping
                 is always filled with liquid.
               • Always connect the impulse piping of negative side above the maximum level.
               • A condensate trap ensures constant pressure on the negative side.
               • When measuring in media with solid parts, such as dirty liquids, installing separators and
                 drain valves is useful for capturing and removing sediment.
16                                                                                                                   Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                                                                  Installation
                                                                                                                      1
                                                                                  –
                                                                max.
                                                                                                                      2
                                                                                                                      3
                                                                min.
                                                                                                                      4
                                                                                                5
                                                                                  +
                                                                                                                                                       A0024162
                          Fig. 14:       Measuring arrangement for level measurement in a container with superimposed steam with FMD77
                          1          Condensate trap
                          2          Shutoff valve
                          3          Separator
                          4          Drain valve
                          5          Deltabar S, here FMD77
                          • Mount the Deltabar S directly on the container.  ä 20, Section 4.3.5 "Seal for flange
                            mounting".
                          • Always connect the impulse piping of negative side above the maximum level.
                          • A condensate trap ensures constant pressure on the negative side.
                          • When measuring in media with solid parts, such as dirty liquids, installing separators and
                            drain valves is useful for capturing and removing sediment.
                                                                                                  ➁
                                                                                 +
                                                                           ➂                           ➂
                                                                                         ➃
P01-PMD75xxx-11-xx-xx-xx-006
                          Fig. 15:       Measuring arrangement for differential pressure measurement in gases and steam with PMD75
                          1          Deltabar S, here PMD75
                          2          Three-way valve manifold
                          3          Shutoff valves
                          4          e.g. filter
                          • Mount the Deltabar S above the measuring point so that the condensate can run off into
                            the process piping.
Endress+Hauser                                                                                                                                             17
Installation                                         Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
                                                                               ➀
                                                                ➁                             ➁
                                                                    +                     –
                                                                                    ➂
                                                                  ➃                        ➃
                                                                  ➄                        ➄
                                                                                           ➅
                                                                                                                            P01-PMD75xxx-11-xx-xx-xx-007
               Fig. 16:       Measuring arrangement for differential pressure measurement in liquids with PMD75
               1          e.g. filter
               2          Shutoff valves
               3          Deltabar S, here PMD75
               4          Separator
               5          Drain valves
               6          Three-way valve manifold
               • Mount the Deltabar S below the measuring point so that the pressure piping is always
                 filled with liquid and gas bubbles can run back into the process piping.
               • When measuring in media with solid parts, such as dirty liquids, installing separators and
                 drain valves is useful for capturing and removing sediment.
                                                                          ➀
                                                         ➁                                 ➁
                                                         +                                 –
                                                                          ➂
                                                                                                    ➃
P01-FMD78xxx-11-xx-xx-xx-000
               Fig. 17:       Measuring arrangement for differential pressure measurement in gases, steam and liquids with FMD78
               1          Diaphragm seal
               2          Capillary
               3          e.g. filter
               4          Deltabar S, here FMD78
               • Mount the diaphragm seal with capillaries at the top or on the side on the piping.
               • For vacuum applications: mount the Deltabar S below the measuring point.  ä 19,
                 Section 4.3.4, "Vacuum application (FMD78)".
               • The ambient temperature should be the same for both capillaries.
18                                                                                                                      Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                                                               Installation
                                                                           –
                                                                                    ≥ 100 mm
+ –
P01-FMD78xxx-11-xx-xx-xx-005
                          Fig. 18:   Mounting Deltabar S, FMD78 with diaphragm seals and capillaries, recommended mounting for vacuum applications:
                                     mount pressure transmitter below the lowest diaphragm seal!
Endress+Hauser                                                                                                                                          19
Installation                                             Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
                                                                                                             12.0
                                                                                                                                                              Low temperature oil
                                                                                                             10.0
                                                                                                             8.0
                                –                                                                                                            Silicone oil
                                                                                                             6.0
                                                                                                                                                              High temperature
                                        –    + –
                                                     +                                                                                                        oil
                                                                                                             4.0
                                                                 H1                                                                                                Inert oil
                                +                                                                            2.0
                                                                                                             0.0
                                                                                                                   50 100 200       300   400   500    600      700     800       900 1000
                                                                                                                                    Pressure, diaphragm seal positive side [mbarabs]
P01-FMD7xxxx-11-xx-xx-xx-001 P01-FMD78xxx-05-xx-xx-en-017
                Fig. 19:    Installation above the lower diaphragm                Fig. 20:                              Diagram of maximum installation height above the lower
                            seal                                                                                        diaphragm seal for vacuum applications depending on the
                                                                                                                        pressure at the diaphragm seal on the positive side
1 2
A0017743
               Fig. 21:
               1        Process isolating diaphragm
               2        Seal
20                                                                                                                                                                 Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                                                                     Installation
TP Ta TP Ta
100 (3.94) A B
77 (3.03)
1 1
53 (2.09) C D
30 (1.18)
                                   1                                                                             1
       [°F] Tp [°C]
                                                                                           A
    +752   +400
                                                                                                   B                           Tp
     572    300
                                                                                  D                        C
     392    200
                                                                                                                                                   Ta
185 85
     +32        0
     −40    −40
           A, B         C, D
     −94    −70                                                                                                                            [°C]
               −40 −35 −30                            0                            45      50       55     60                 +85             Ta
                                                                                                                                           [°F]
                 −40 −31 −22                        +32                            113 122 131 140                            +185
                                                                                                                                                        A0025889
Endress+Hauser                                                                                                                                             21
Installation                                                              Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
           TP                                              TU                                 TP                                    TU
                                                   1
                                         100 (3.94)                                                                             F
                                                                     E
                                                                                                                + –
                                         +–
30 (1.18)
A0023984
E U-bracket, Transmitter horizontally  70 °C (158 °F) max. 350 °C (662 °F) , depending on 2)
(for devices which require a CRN approval) the diaphragm seal filling oil used
22                                                                                                                            Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                                                                           Installation
                                                                                                          3)
                                                                                                     ( 2.1 )
                                                                                                 54 1.63
                                                                                                        (
                                                                                                    .3
                                                                                                 41
                                                                                                           37.5 (1.48)
                                                  135 (5.31)
                                                                                                                                   12
                                                               41.3 (1.63)                                                              (0.
                                                                                                                                           47
                                                               54 (2.13)
                                                                              74                                                 1)
                                                                       12           (2.
                                                                                         91                                 ( 2.9 7)
                                                                             4(              )                           74       4.1
                                                                                  4.8
                                                                                        8)                                   0 6(
                                                                                                                           1
A0023932
1 2
                                              1
                                                                                                                                                         A0025335
Endress+Hauser                                                                                                                                              23
Installation                                            Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
                                                                                           5
                                                                                                                      7
                                                                                   4
1 r ³ 120 mm
P01-xMD7xxxx-11-xx-xx-xx-011
24                                                                                                                               Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                                     Installation
                                              2                                                               3
                                                                                                                          A0019996
+–
P01-PMD75xxx-17-xx-xx-xx-000
                          The covers for the terminal and electronics compartment are hooked into the housing and
                          closed with a screw. These screws should be tightened handtight (2 Nm (1.48 lbf ft)) to the
                          stop to ensure that the covers sit tightly.
Endress+Hauser                                                                                                                25
Wiring                                           Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
5 Wiring
                 ➀
                                                                                                                     ➃
FF FF
                 ➁                                                                                                                        ➄
                                                                                                        FF      FF
                                                                ➂
                                                                                                                         P01-xMx7xxxx-04-xx-xx-xx-009
26                                                                                                                   Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                                      Wiring
PIN Meaning
                                                                                 1     Signal –
                                               1      3
                                                                                 2     Signal +
                                                                                 3     Shield
                                               2      4
                                                                                 4     Not assigned
A0011176
Endress+Hauser                                                                                                   27
Wiring                             Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
28                                                                                    Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                                             Operation
                          6            Operation
                          Feature 20 "Output; operation" in the order code provides you with information on the
                          operating options available to you.
                          P     FOUNDATION Fieldbus; external operation, LCD   Via onsite display and 1 key on the exterior of
                                                                               the device
                          Q     FOUNDATION Fieldbus; internal operation, LCD   Via onsite display and 1 key on the inside of the
                                                                               device
                          R     FOUNDATION Fieldbus; internal operation        Without onsite display, 1 key on the inside of
                                                                               the device
Endress+Hauser                                                                                                                  29
Operation                                Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
                                                      Header line
                                                      Main line
                                                                                                                        Unit
                                                      Information
                                                      line
                      –    +   E                                    Symbol
                                                                                        Bargraph
                                                                  Editing modes
                     Operating keys
                                                      Selection
                                                      options
                                                      Value that
                                                      can be edited
            The following table illustrates the symbols that can appear on the onsite display. Four
            symbols can occur at one time.
            Symbol                    Meaning
                                      Alarm symbol
                                      – Symbol flashing: warning, device continues measuring.
                                      – Symbol permanently lit: error, device does not continue measuring.
                                      Note: The alarm symbol may overlie the tendency symbol.
                                      Lock symbol
                                      The operation of the device is locked. Unlock device,  ä 52, Section 6.7 "Locking/
                                      unlocking operation".
                                      Communication symbol
                                      Data transfer via communication
                                      Simulation symbol
                                      Simulation mode is activated. DIP switch 2 for simulation is set to "On".
                                      See also Section 6.2.1 "Position of the operating elements" and  ä 54,
                                      Section 6.8 "Simulation".
30                                                                                                    Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                                                                                                                         Operation
➄➅
                                                                                                                                        Sim.
                                                                                                                              on
                                ➀                                                                                                                  ➀                           ➁
                                                                                                                                    1   2
                                                                                                                                                                                                ➂
                                                                                                                              off
                                                                                                                                                                                                             ➃
                                                                                                                                                                         0%
                                                                                                                                                                               Zero
                                                                                                                                                                      Sensor          Display
                                                                                                                                                   Simulation
                                                                        0%
                                                                             Zero
                                                                                                                                                                                       HW
                                                                                                                                                                on
1 2 off
                                                                                                                                                                                                  PC
                                                                                                                                                                                                 Histo ROM
                                                                                    P01-xMD7xxxx-19-xx-xx-xx-074                                                                          P01-xxxxxxxx-19-xx-xx-xx-106
                          Fig. 28:        Operating key external, under the protective flap                        Fig. 29:         Operating keys, internal
                          1          Operating key for position adjustment (zero point                             1          Green LED to indicate value is accepted
                                     correction) and total reset                                                   2          Operating key for position adjustment (zero point
                                                                                                                              correction) and total reset
                                                                                                                   3          Slot for optional display
                                                                                                                   4          Slot for optional HistoROM®/M-DAT
                                                                                                                   5          DIP switch for locking/unlocking parameters relevant to
                                                                                                                              the measured value
                                                                                                                   6          DIP switch for simulation mode
Key(s) Meaning
                                                                        – Position adjustment (zero point correction): press key for at least 3 seconds. The
                                     0%                                   LED on the electronic insert lights up briefly if the pressure applied has been
                                                                          accepted for position adjustment.
                                                    Zero                  See also the following section "Performing position adjustment on site".
                                         P02-xxxxxxxx-19-xx-xx-xx-107
                                                                        – Total reset: press key for at least 12 seconds. The LED on the electronic insert
                                                                          lights up briefly if a reset is being carried out.
                                                     on
                                                                          Factory setting: off (unlocked)
                                                                           ä 52, Section 6.7 "Locking/unlocking operation".
                                                                        – DIP switch 2: for simulation mode
                                         1    2      off                  Factory setting: off (simulation mode off)
                                         P01-xxxxxxxx-19-xx-xx-xx-134
                                                                           ä 54, Section 6.8 "Simulation"
Endress+Hauser                                                                                                                                                                                                   31
Operation                                               Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
            • The pressure applied must be within the nominal pressure limits of the sensor. See
              information on the nameplate.
            Perform position adjustment:
            1.   Pressure is present at device.
            2.   Press key for at least 3 seconds.
            3.   If the LED on the electronic insert lights up briefly, the pressure applied has been
                 accepted for position adjustment.
                 If the LED does not light up, the pressure applied was not accepted. Observe the input
                 limits. For error messages,  ä 88, Section 9.2 "Diagnostic information on local
                 display".
Key(s) Meaning
                         F                          – Confirm entry
                                                    – Go to next item
                                on
                                                      Factory setting: off (unlocked)
                                                    – DIP switch 2: for the simulation mode Factory setting: off (simulation mode off)
                     1    2     off
                     P01-xxxxxxxx-19-xx-xx-xx-134
32                                                                                                                    Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                                                                         Operation
Industrial Network
                                      FF-HSE
                                                                          BT
                                                                                           FF-H1             SB
                                            LD
                                                                          PS                                                                          BT
BT
PS
                                                                                           FF-H1
                                                                                                                                                      BT
P01-xxxxxxxx-02-xx-xx-xx-001
Endress+Hauser                                                                                                                                                  33
Operation                              Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
              Up to HW version 1.10:
              – Up to 7 Deltabar S devices for Ex ia, CSA and FM IS applications
              – Up to 25 Deltabar S devices in all other applications, e.g. in non-hazardous areas, Ex nA
                etc.
              As of HW version 02.00:
              – Up to 6 Deltabar S devices for Ex ia, CSA and FM IS applications
              – Up to 24 Deltabar S devices in all other applications, e.g. in non-hazardous areas, Ex nA
                etc.
              The maximum number of measuring devices at one bus segment is defined by their current
              consumption, the performance of the bus coupler, and the required bus length.
As of hardware version 1.10, you will find a label in the device on the electronic insert.
            6.3.3       Operation
            You can obtain special configuration and operating programs from various manufacturers
            for the configuration, such as the FieldCare operating program from Endress+Hauser
             ä 52, Section 6.6 "FieldCare". These configuration programs make it possible to configure
            FF functions and all the device-specific parameters. The predefined function blocks allow
            uniform access to all the network and device data.
34                                                                                         Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                                                                           Operation
                                                         ➀                    ➁
                                     –        EH_DeltabarS-XXXXXXXXXXXXXXXX
                                                 RS_XXXXXXXXXXX (RB2)
                                                 TRD1_XXXXXXXXXXX (PCD)
                                                 SERVICE_XXXXXXXXXXX (SERVICE)
                                                 DP_FLOW_XXXXXXXXXXX (DPFLOW)
                                                 DIAGNOSTIC_XXXXXXXXXXX (DIAGNOSTIC)
                                                 DISPLAY_XXXXXXXXXXX (DISP)
                                                 AI1_XXXXXXXXXXX (AI)
                                                 AI2_XXXXXXXXXXX (AI)
                                                 AI3_XXXXXXXXXXX (AI)
                                                 DI_XXXXXXXXXXX (DI)
                                                 DO_XXXXXXXXXXX (DO)
                                                 PID_XXXXXXXXXXX (PID)
                                                 ARTH_XXXXXXXXXXX (ARB)
                                                 CHAR_XXXXXXXXXXX (SCB)
                                                 ISEL_XXXXXXXXXXX (ISB)
                                                 INTG_XXXXXXXXXXX (ITB)
                                                 AALM_XXXXXXXXXXX (AALB)
P01-xMx7xxxx-05-xx-xx-xx-005
                          Fig. 31:       Typical Deltabar S display in a configuration program after the connection has been established
                          1          Device name
                          2          Serial number
Endress+Hauser                                                                                                                                                   35
Operation                              Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
            • 5 Transducer Blocks
              – Pressure Transducer Block (TRD)
                This Block supplies the output variables PRIMARY_VALUE and SECONDARY_VALUE. It
                contains all the parameters to configure the measuring device for the measuring task
                such as measuring mode selection, linearization function and unit selection.
              – Service Transducer Block
                This Block supplies the output variables COUNTER P_PMAX, PRESSURE_1_ MAX_
                RESETABLE and PRESSURE_1_AFTER_DAMPING. It also includes all the counters for
                measuring range overshoot/undershoot for pressure and temperature, minimum and
                maximum measured values for pressure and temperature and the HistoROM function.
              – DP Flow Block
                This Block supplies the output variable TOTALIZER_1_VALUE/TOTALIZER 1. It
                contains all the parameters that are needed to configure this totalizer.
              – Display Transducer Block
                This Block does not return any output variables. It contains all the parameters for
                configuring the onsite display such as DISPLAY_CONTRAST.
              – Diagnostic Transducer Block
                This Block does not return any output variables. It contains
                – the simulation function for the Pressure Transducer Block
                – parameters to configure the alarm response
                – parameters to set the user limits for pressure and temperature.
            • 9 function blocks
              – 3 Analog Input Blocks (AI)
              – Discrete Output Block (DO)
              – Discrete Input Block (DI)
              – PID Block (PID)
              – Arithmetic Block (ARB)
              – Signal Characterizer Block (SCB)
              – Input Selector Block (ISB)
              – Analog Alarm Block (AALB)
              – Integrator Block (IT)
            In addition to the pre-instantiated blocks already mentioned, the following blocks can also
            be instantiated:
            • 3 Analog Input Blocks (AI)
            • 1 Discrete Output Block (DO)
            • 1 PID Block (PID)
            • 1 Arithmetic Block (ARB)
            • 1 Signal Characterizer Block (SCB)
            • 1 Input Selector Block (ISB)
            • 1 Analog Alarm Block (AALB)
            • Integrator Block (IT)
            A total of 20 blocks can be instantiated in Deltabar S altogether, including the blocks already
            instantiated. For instantiating blocks, see the appropriate Operating Instructions of the
            configuration program used.
            Endress+Hauser Guideline BA00062S.
            The guideline provides an overview of the standard function blocks that are described in
            FOUNDATION Fieldbus Specifications FF 890 - 894.
            It is designed to help operators use the blocks implemented in the Endress+Hauser field
            devices.
36                                                                                        Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                                                            Operation
Measured variable
                                     Display
                                     Transducer Block              Arithmetic Block   PID Block          Input Selector   Discrete Input
                                                                                                         Block            Block
                                     Diagnostic
                                     Transducer Block              Discrete Output    Signal             Analog Alarm     Integrator
                                                                   Block              Characterizer      Block            Block
                                                                                      Block
P01-xMD7xxxx-02-xx-xx-en-004
                          The Pressure Transducer Block supplies the Primary Value and the sensor temperature
                          (secondary value). In the DP Flow Transducer Block, the flow is totalized in the "Flow"
                          measuring mode and output by means of the TOTALIZER_1_VALUE/TOTALIZER 1
                          parameter. The Primary Value, Secondary Value and TOTALIZER_1_VALUE are each
                          transferred to one Analog Input Block by means of the CHANNEL parameter (see also the
                          following section).
                          The Discrete Output, PID, Arithmetic, Signal Characterizer, Input Selector and Analog Alarm
                          Block are not connected in the as-delivered state.
                          Please note that the links between the blocks are deleted and the FF parameters are reset to
                          the default values following a reset by means of the RESTART parameter in the Resource
                          Block, "Default" option.
Endress+Hauser                                                                                                                                    37
Operation                                 Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
1) Factory setting
38                                                                                           Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                                        Operation
Configuration error 2
Sensor overpressure 3
Sensor underpressure 4
Sensor overtemperature 5
Sensor undertemperature 6
Endress+Hauser                                                                                                         39
Operation                                                     Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
Resource Block
Parameter name,                         Parameter name,      Index Data type        Size    Storage Read Writ   MODE_BLK Reset
option "Symbolic name"                  option "Label"                              (Byte   Class        e               codes
                                                                                    )
ENP_VERSION                             ENP version          44    Visible String   16      S      x
DEVICE_TAG                              Device tag           45    Visible String   32      S      x     x1)    AUTO, OOS
SERIAL_NUMBER                           Serial number        46    Visible String   16      S      x     x)    AUTO, OOS
ORDER_CODE                              Order code           47    Visible String   32      S      x     x)    AUTO, OOS
FIRMWARE_VERSION                        Firmware version     48    Visible String   16      S      x
SW_LOCK                                 Insert PIN no.       49    Unsigned16       2       S      x     x      AUTO, OOS   7864, 333
STATUS_LOCKING                          Status locking       50    Unsigned16       2       D      x
HARDWARE_REVISION                       Hardware rev.        74    Visible String   16      S      x
FF_COMM_VERSION                         FF comm. version     75    Visible String   16      S      x
BLOCK_ERR_DESC_1                        Block Error desc.    76    Bit enumerated   4       D      x
DEVICE_DIALOG                           Device dialog        77    Unsigned8        1       D      x
ELECTRONIC_SERIAL_NUMBER                Electr. serial no.   78    Visible String   16      S      x
PROCESS_CONNECTION_TYPE                 Proc. conn. type     79    Unsigned16       2       S      x     x      AUTO, OOS   7864, 333
MAT_PROC_CONN_POS                       Mat. proc. conn. +   80    Unsigned16       2       S      x     x      AUTO, OOS   7864, 333
MAT_PROC_CONN_NEG                       Mat. proc. conn. -   81    Unsigned16       2       S      x     x      AUTO, OOS   7864, 333
SEAL_TYPE                               Seal type            82    Unsigned16       2       S      x     x      AUTO, OOS   7864, 333
SCI_OCTET_STRING                        SCI_OCTET_STR        83    Visible String   40      S      x     x      AUTO, OOS
MS_RESOURCE_DIRECTORY                   RESOURCE DIRECTORY   84    Unsigned16       20x2    S      x
40                                                                                                                   Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                                                          Operation
Parameter name,                 Parameter name,           Index   Data type        Size     Storage Read   Writ   MODE_BLK     Reset codes
option "Symbolic name"          option "Label"                                     (Byte)   Class          e
MEASURED_TEMPERATURE            Temperature               32      DS-65            5        D      x
MEASURED_TEMPERATURE_UNIT       Temp. eng. unit           33      Unsigned16       2        S      x       x      OOS
DEVICE_DIALOG                   Device dialog             34      Unsigned8        1        D      x
SW_LOCK                         Insert PIN no.            35      Unsigned16       2        S      x       x      AUTO, OOS,   7864, 333
                                                                                                                  MAN
STATUS_LOCKING                  Status locking            36      Unsigned16       2        D      x
LINEARIZATION                   Linearization             37      Unsigned8        2        S      x       x      OOS          7864, 333
SCALE_IN                        Scale In                  38      DS-68            11       S      x       x      OOS          7864, 333
SCALE_OUT                       Scale Out                 39      DS-68            11       S      x       x      OOS          7864, 333
DAMPING_VALUE                   Damping value             40      Float            4        S      x       x      OOS          7864, 333
ZERO_POSITION_ADJUST            Pos. zero adjust          41      Unsigned8        1        D      x       x      OOS
POSITION_INPUT_VALUE            Pos. input value          42      Float            4        S      x       x      OOS          7864, 333,
                                                                                                                               2509
CALIBRATION_OFFSET              Calib. offset             43      Float            4        S      x       x      OOS          7864, 333,
                                                                                                                               2509
CUSTOMER_UNIT_PRESSURE          Customer unit P           44      Visible String 8          S      x       x      AUTO, OOS,   7864
                                                                                                                  MAN
CUSTOMER_FACTOR_UNIT_PRESS      Cust. unit. fact. P       45      Float            4        S      x       x      OOS          7864
LOW_TRIM_MEASURED               Lo trim measured          46      Float            4        S      x                           2509
HIGH_TRIM_MEASURED              Hi trim measured          47      Float            4        S      x                           2509
LEVEL_MODE                      Level mode                48      Unsigned8        1        S      x       x      OOS          7864, 333
LINEAR_MEASURAND                Lin. measurand            49      Unsigned8        1        S      x       x      OOS          7864, 333
LINEARIZED_MEASURAND            Lin. measurand            50      Unsigned8        1        S      x       x      OOS          7864, 333
COMBINED_MEASURAND              Comb. measurand           51      Unsigned8        1        S      x       x      OOS          7864, 333
DENSITY_UNIT                    Density unit              52      Unsigned16       2        S      x       x      OOS          7864, 333
HEIGHT_UNIT                     Height unit               53      Unsigned16       2        S      x       x      OOS          7864, 333
CUSTOMER_HEIGHT_UNIT            Customer unit H           54      Visible String   8        S      x       x      AUTO, OOS,   7864
                                                                                                                  MAN
CUSTOMER_UNIT_FACTOR_HEIGHT     Cust. unit. fact. H       55      Float          4          S      x       x      OOS          7864
VOLUME_UNIT                     Unit volume               56      Unsigned16 2              S      x       x      OOS          7864, 333
CUSTOMER_UNIT_VOLUME            Customer unit V           57      Visible String 8          S      x       x      AUTO, OOS,   7864
                                                                                                                  MAN
CUSTOMER_UNIT_FACTOR_VOLUME     Cust. unit. fact. V       58      Float          4          S      x       x      OOS          7864
MASS_UNIT                       Unit mass                 59      Unsigned16 2              S      x       x      OOS          7864, 333
CUSTOMER_UNIT_MASS              Customer unit M           60      Visible String 8          S      x       x      AUTO, OOS,   7864
                                                                                                                  MAN
CUSTOMER_UNIT_FACTOR_MASS       Cust. unit. fact. M       61      Float            8        S      x       x      OOS          7864
CALIBRATION_MODE                Calibration mode          62      Unsigned8        1        S      x       x      OOS          7864, 333
ADJUST_DENSITY                  Adjust density            63      Float            4        S      x       x      OOS          7864, 333
ZERO_POSITION                   Zero position             64      Float            4        S      x       x      OOS          7864, 333
EMPTY_CALIBRATION               Empty calib. level easy   65      Float            4        S      x       x      OOS          7864, 333
FULL_CALIBRATION                Full calib. level easy    66      Float            4        S      x       x      OOS          7864, 333
TANK_VOLUME                     Tank volume               67      Float            4        S      x       x      OOS          7864, 333
TANK_HEIGHT                     Tank height               68      Float            4        S      x       x      OOS          7864, 333
HUNDRED_PERCENT_VALUE           100% point                69      Float            4        S      x       x      OOS          7864, 333
LEVEL_MIN                       Level Min.                70      Float            4        S      x       x      OOS          7864, 333
LEVEL_MAX                       Level Max.                71      Float            4        S      x       x      OOS          7864, 333
PROCESS_DENSITY                 Process density           72      Float            4        S      x       x      OOS          7864, 333
LINEARIZATION_TABLE_SELECTION   Table selection           73      Unsigned8        1        S      x       x      AUTO, OOS,   7864, 333
                                                                                                                  MAN
LINEARIZATION_EDIT_MODE         Edit table                74      Unsigned8        1        S      x       x      AUTO, OOS,   7864
                                                                                                                  MAN
LINEARIZATION_TABLE_PRE_EDIT    Editor table              75      Unsigned8        1        D      x       x      AUTO, OOS,
                                                                                                                  MAN
LINEARIZATION_TABLE_INDEX       Line numb:                76      Unsigned8        1        D      x       x      AUTO, OOS,
                                                                                                                  MAN
LINEARIZATION_TABLE_X_VALUE     X-value:                  77      Float            4        S      x       x      AUTO, OOS,   7864
                                                                                                                  MAN
LINEARIZATION_TABLE_Y_VALUE     Y-value:                  78      Float            4        S      x       x      AUTO, OOS,   7864
                                                                                                                  MAN
LINEARIZATION_TABLE_POST_EDIT   Table editor              79      Unsigned8        1        D      x       x      OOS
LINEARIZATION_TABLE_POST_VIEW   Measuring table           80      Unsigned8        1        D      x       x      AUTO, OOS,
                                                                                                                  MAN
LEVEL_TANK_DESCRIPTION          Tank description          81      Visible String 32         S      x       x      AUTO, OOS,   7864
                                                                                                                  MAN
SENSOR_PRESSURE                 Sensor pressure           82      Float            4        D      x
PRESSURE                        Pressure                  83      Float            4        D      x
LEVEL_BEFORE_LINEARISATION      Level before lin          84      Float            4        D      x
Endress+Hauser                                                                                                                              41
Operation                                                            Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
Parameter name,                 Parameter name,              Index   Data type    Size     Storage Read   Writ   MODE_BLK        Reset codes
option "Symbolic name"          option "Label"                                    (Byte)   Class          e
SENSOR_MEAS_TYPE                Sensor meas. type            85      Unsigned16   2        D      x
LEVEL_SELECTION                 Level mode                   86      Unsigned8    1        S      x       x      OOS             7864, 333
HEIGHT_UNIT_EASY                Height unit                  87      Unsigned16   2        S      x       x      OOS
OUTPUT_UNIT_EASY                Output unit                  88      Unsigned16   2        S      x       x      OOS
CALIBRATION_MODE_EASY           Calibration mode level       89      Unsigned8    1        S      x       x      OOS             7864, 333
                                easy
DENSITY_UNIT_EASY               Density unit level easy      90      Unsigned16   2        S      x       x      OOS
ADJUST_DENSITY_EASY             Adjust density level easy    91      Float        4        S      x       x      OOS             7864, 333
EMPTY_HEIGHT_EASY               Full calib. level easy       92      Float        4        S      x       x      OOS             7864, 333
FULL_HEIGHT_EASY                Full calib. level easy       93      Float        4        S      x       x      OOS             7864, 333
PROCESS_DENSITY_EASY            Process density level easy   94      Float        4        D      x       x      OOS             7864, 333
MEASURED_LEVEL_EASY             Meas. level easy             95      Float        4        D      x
FULL_CALIBRATION_EASY           Full calib. level easy       96      Float        4        S      x       x      OOS             7864, 333
EMPTY_CALIBRATION_EASY          Full calib. level easy       97      Float        4        S      x       x      OOS             7864, 333
FULL_PRESSURE_EASY              Full pressure                98      Float        4        S      x       x      OOS             7864, 333
EMPTY_PRESSURE_EASY             Empty pressure               99      Float        4        S      x       x      OOS             7864, 333
Parameter name,                 Parameter name,              Index   Data type    Size     Storage Read   Writ   MODE_BLK        Reset codes
option "Symbolic name"          option "Label"                                    (Byte)   Class          e
DEVICE_DIALOG                   Device dialog                11      Unsigned8    1        D      x
SW_LOCK                         Insert PIN no.               12      Unsigned16   2        S      x       x      AUTO, OOS,      7864, 333
                                                                                                                 MAN
STATUS_LOCKING                  Status locking               13      Unsigned16   2        D      x
CONFIGURATION_COUNTER           Config recorder              14      Unsigned16   2        S      x
ELECTRONICS_TEMPERATURE         Pcb temperature              15      Float        4        D      x
ELECTRONICS_TEMP_LOW_LIMIT      Allowed min. temp            16      Float        4        S      x
ELECTRONICS_TEMP_HIGH_LIMIT     Allowed max temp             17      Float        4        S      x
PMAX_PROC_CONN                  Pmax proc. conn.             18      Float        4        S      x       x      AUTO, OOS,
                                                                                                                 MAN
SENSOR_MEAS_TYPE                Sensor meas. type            19      Unsigned16   2        S      x
SENSOR_MIN_ABSOLUTE_LIMIT       Pmin sensor. damage          20      Float        4        S      x
SENSOR_MAX_ABSOLUTE_LIMIT       Pmax sensor. damage          21      Float        4        S      x
SENSOR_TEMP_LOW_LIMIT           Tmin sensor                  22      Float        4        S      x
SENSOR_TEMP_HIGH_LIMIT          Tmax sensor                  23      Float        4        S      x
SENSOR_HARDWARE_REV             Sens. H/ware rev.            24      Unsigned8    1        S      x
COUNTER P_MAX                   Counter: P> Pmax             25      DS-65        5        D      x
MAX_MEASURED_PRESSURE           Max. meas. press.            26      DS-65        5        D      x
COUNTER_PMIN                    Counter: P < Pmin            27      Unsigned16   2        D      x
MIN_MEASURED_PRESSURE           Min. meas. press.            28      Float        4        D      x
COUNTER_TMAX                    Counter: T > Tmax            29      Unsigned16   2        D      x
MAX_MEASURED_TEMP               Max. meas. temp.             30      Float        4        D      x
COUNTER_TMIN                    Counter: T < Tmin            31      Unsigned16   2        D      x
MIN_MEASURED_TEMP               Min. meas. temp.             32      Float        4        D      x
ELECTRONIC_OVER_TEMP_COUNTER    Pcb count: T > Tmax          33      Unsigned16   2        D      x
ELECTRONIC_OVER_TEMPERATURE     Pcb max. temp                34      Float        4        D      x
ELECTRONIC_UNDER_TEMP_COUNTER   Pcb count: T < Tmin          35      Unsigned16   2        D      x
ELECTRONIC_UNDER_TEMPERATURE    PCB min. temp.               36      Float        4        D      x
RESET_PEAK_HOLD                 Reset peakhold               37      Unsigned8    1        D      x       x      AUTO, OOS,
                                                                                                                 MAN
PRESSURE                        Pressure                     38      DS-65        5        D      x
CORRECTED_PRESSURE              Corrected press.             39      Float        4        D      x
MEASURED_VALUE_TREND            Meas. val. trend             40      Unsigned8    1        D      x
MAX_TURNDOWN                    Max. turndown                41      Float        4        S      x       x1)
SENSOR_CHANGES                  Sensor changes               42      Unsigned16   2        S      x       x)
PRESSURE_PEAK_HOLD_STEP         P. peakhold step             43      Float        4        S      x       x)
TEMP_PEAK_HOLD_STEP             T. peakhold step             44      Float        4        S      x       x)
ACCELERATION_OF_GRAVITY         Acc. of gravity              45      Float        4        S      x       x)    OOS
CREEP_FLOW_HYST                 Creep flow hyst.             46      Float        4        S      x       x)    OOS
HISTOROM_SAVING_CYCLE_TIME      Hist. saving cycl            47      Unsigned8    1        S      x       x)
HISTOROM_AVAIBLE                Historom avail.              48      Unsigned8    1        S      x
DOWNLOAD_SELECTION              Download select.             49      Unsigned8    1        D      x       x      AUTO, OOS,
                                                                                                                 MAN
HISTOROM_CONTROL                Historom control             50      Unsigned8    1        D      x       x
PRESSURE_UNIT                   Cal. unit                    51      Unsigned16   2        S      x
TEMPERATURE_UNIT                Temp. eng. unit              52      Unsigned16   2        S      x
42                                                                                                                            Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                                                            Operation
Parameter name,                         Parameter name,        Index   Data type     Size     Storage Read   Writ   MODE_BLK     Reset codes
option "Symbolic name"                  option "Label"                               (Byte)   Class          e
INPUT_PRESSURE_INVERSION                Inp.press invers       53      Unsigned8     1        S       x      x)    OOS
Parameter name,                         Parameter name,        Index   Data type     Size     Storage Read   Writ   BLK_MODE     Reset codes
option "Symbolic name"                  option "Label"                               (Byte)   Class          e
DEVICE_DIALOG                           Device dialog          10      Unsigned8     1        D      x
DISPLAY_MAINLINE_CONTENT                Main line cont.        11      Unsigned8     1        S      x       x      AUTO, OOS,   7864
                                                                                                                    MAN
DISPLAY_MAINLINE_FORMAT                 Main data format       12      Unsigned8     1        S      x       x      AUTO, OOS,   7864
                                                                                                                    MAN
DISPLAY_ALTERNATING_VALUES              Alternate data         13      Unsigned8     1        S      x       x      AUTO, OOS,   7864
                                                                                                                    MAN
DISPLAY_CONTRAST                        Display contrast       14      Unsigned8     1        S      x       x      AUTO, OOS,   7864
                                                                                                                    MAN
DISPLAY_LANGUAGE                        Language               15      Unsigned8     1        S      x       x      AUTO, OOS,   7864
                                                                                                                    MAN
SIL_DIGITS_TEST_STRING                  Digits set             16      Visible String 16      D      x
Parameter name,                         Parameter name,        Index   Data type     Size     Storage Read   Writ   BLK_MODE     Reset codes
option "Symbolic name"                  option "Label"                               (Byte)   Class          e
DEVICE_DIALOG                           Device dialog          10      Unsigned8     1        D      x
SW_LOCK                                 Insert PIN no.         11      Unsigned16    2        S      x       x      AUTO, OOS,   7864, 333
                                                                                                                    MAN
STATUS_LOCKING                          Status locking         12      Unsigned16    2        D      x
SIMULATION_MODE                         Simulation mode        13      Unsigned8     1        D      x       x      OOS
SCALE_OUT_UNITS_INDEX                   Units index            14      Unsigned16    2        S      x
SIMULATED_VALUE                         Simulated value        15      Float         4        D      x       x      AUTO, OOS,
                                                                                                                    MAN
SIMULATION_ERROR_NUMBER                 Sim. error no.         16      Unsigned16    2        D      x       x      AUTO, OOS,
                                                                                                                    MAN
ALARM_STATUS                            -                      17      Unsigned16    2        D      x
ALARM_STATUS_WITH_CATEGORY              Alarm status info      18      Unsigned16    2        D      x
LAST_DIAGNOSTIC_CODE                    -                      19      Unsigned16    2        D      x
LAST_DIAGNOSTIC_CODE_WITH_CATE          Last diag. code info   20      Unsigned16    2        D      x
GORY
ACKNOWLEDGE_ALARM_MODE                  Ack. alarm mode        21      Unsigned8     1        S      x       x      AUTO, OOS,   7864
                                                                                                                    MAN
ACKNOWLEDGE_ALARM                       Ack. alarm             22      Unsigned8     1        D      x       x      AUTO, OOS,
                                                                                                                    MAN
RESET_ALL_ALARMS                        Reset all alarms       23      Unsigned8     1        D      x       x      AUTO, OOS,
                                                                                                                    MAN
ERROR_NUMBER                            Error no.              24      Unsigned16    2        D      x       x      AUTO, OOS,
                                                                                                                    MAN
SELECT_ALARM_TYPE                       Select alarm type      25      Unsigned8     1        D      x       x      AUTO, OOS,
                                                                                                                    MAN
ALARM_DELAY                             Alarm delay            26      Float         4        S      x       x      AUTO, OOS,   7864
                                                                                                                    MAN
ALARM_DISPLAY_TIME                      Alarm displ. time      27      Float         4        S      x       x      AUTO, OOS,   7864
                                                                                                                    MAN
PRESSURE_UNIT                           Cal. unit              28      Unsigned16    2        S      x                           7864, 333
PMIN_ALARM_WINDOW                       Pmin alarm window      29      Float         4        S      x       x      AUTO, OOS,   7864
                                                                                                                    MAN
PMAX_ALARM_WINDOW                       Pmax alarm window      30      Float         4        S      x       x      AUTO, OOS,   7864
                                                                                                                    MAN
TEMPERATURE_UNIT                        Temp. eng. unit        31      Unsigned16    2        S      x                           7864, 333
TMIN_ALARM_WINDOW                       Tmin. alarm window     32      Float         4        S      x       x      AUTO, OOS,   7864
                                                                                                                    MAN
TMAX_ALARM_WINDOW                       Tmax. alarm window     33      Float         4        S      x       x      AUTO, OOS,   7864
                                                                                                                    MAN
ENTER_RESET_CODE                        Enter reset code       34      Unsigned16    2        D      x       x      AUTO, OOS,
                                                                                                                    MAN
OPERATING_HOURS                         Operating hours        35      Unsigned32 4           D      x
STATUS_HISTORY                          Alarm history          36      Visible String 18      D      x
HIGHEST_CATEGORY                        -                      37      Unsigned8      1       D      x
Endress+Hauser                                                                                                                               43
Operation                                                     Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
Parameter name,             Parameter name,           Index   Data type        Size     Storage Read   Writ    BLK_MODE          Reset codes
option "Symbolic name"      option "Label"                                     (Byte)   Class          e
FF912_CONFIG_AREA           FF912ConfigArea           38      DS271            30       S       x      x       AUTO, OOS,        7864
                                                                                                               MAN
FF912_STATUS_SELECT1        Status Select Event 115   39      Enumerated       1        S       x      x       AUTO, OOS,        7864
                                                                                                               MAN
FF912_STATUS_SELECT2        Status Select Event 120   40      Enumerated       1        S       x      x       AUTO, OOS,        7864
                                                                                                               MAN
FF912_STATUS_SELECT3        Status Select Event 715   41      Enumerated       1        S       x      x       AUTO, OOS,        7864
                                                                                                               MAN
FF912_STATUS_SELECT4        Status Select Event 717   42      Enumerated       1        S       x      x       AUTO, OOS,        7864
                                                                                                               MAN
FF912_STATUS_SELECT5        Status Select Event 718   43      Enumerated       1        S       x      x       AUTO, OOS,        7864
                                                                                                               MAN
FF912_STATUS_SELECT6        Status Select Event 720   44      Enumerated       1        S       x      x       AUTO, OOS,        7864
                                                                                                               MAN
FF912_STATUS_SELECT7        Status Select Event 726   45      Enumerated       1        S       x      x       AUTO, OOS,        7864
                                                                                                               MAN
FF912_STATUS_SELECT8        Status Select Event 727   46      Enumerated       1        S       x      x       AUTO, OOS,        7864
                                                                                                               MAN
FF912_STATUS_SELECT9        Status Select Event 730   47      Enumerated       1        S       x      x       AUTO, OOS,        7864
                                                                                                               MAN
FF912_STATUS_SELECT10       Status Select Event 731   48      Enumerated       1        S       x      x       AUTO, OOS,        7864
                                                                                                               MAN
FF912_STATUS_SELECT11       Status Select Event 732   49      Enumerated       1        S       x      x       AUTO, OOS,        7864
                                                                                                               MAN
FF912_STATUS_SELECT12       Status Select Event 733   50      Enumerated       1        S       x      x       AUTO, OOS,        7864
                                                                                                               MAN
FF912_STATUS_SELECT13       Status Select Event 740   51      Enumerated       1        S       x      x       AUTO, OOS,        7864
                                                                                                               MAN
Parameter name,             Parameter name,           Index   Data type        Size     Storage Read   Write BLK_MODE            Reset codes
option "Symbolic name"      option "Label"                                     (Byte)   Class
FSAFE_TYPE                  Fsafe_Type                37      Unsigned8        1        S      x       x       OOS, MAN
FSAFE_VALUE                 Fsafe_Value               38      Float            4        S      x       x       AUTO, OOS,
                                                                                                               MAN
HIHI_ALM_OUT_D              High high alarm output    39      DS66             2        D      x       x       AUTO, OOS,
                            discrete                                                                           MAN
HI_ALM_OUT_D                High alarm output         40      DS66             2        D      x       x       AUTO, OOS,
                            discrete                                                                           MAN
LO_ALM_OUT_D                Low alarm output          41      DS66             2        D      x       x       AUTO, OOS,
                            discrete                                                                           MAN
LOLO_ALM_OUT_D              Low low alarm output      42      DS66             2        D      x       x       AUTO, OOS,
                            discrete                                                                           MAN
ALARM_MODE                  Select alarm mode         43      Unsigned8        1        S      x       x       AUTO, OOS,
                                                                                                               MAN
ALARM_OUT_D                 Alarm output discrete     44      DS66             2        D      x       x       AUTO, OOS,
                                                                                                               MAN
BLOCK_ERR_DESC_1            Block error description   45      Unsigned32       4        D      x               AUTO, OOS,
                                                                                                               MAN
DP Flow Block
Parameter name,             Parameter name,           Index   Data type        Size     Storage Read   Write    BLK_MODE          Reset codes
option "Symbolic name"      option "Label"                                     (Byte)   Class
DEVICE_DIALOG               Device dialog             11      Unsigned8        1        D       x
SW_LOCK                     Insert PIN no.            12      Unsigned16       2        S       x      x        AUTO, OOS, MAN 7864, 333
STATUS_LOCKING              Status locking            13      Unsigned16       2        D       x
FLOW_MEAS_TYPE              Flow. meas. type          14      Unsigned8        1        S       x      x        OOS               7864
SUPPRESSED_FLOW             Suppressed flow           15      Float            4        D       x
STD_FLOW_UNIT               Unit flow                 16      Unsigned16       2        S       x      x        OOS               7864
CUSTOMER_UNIT_FLOW          Customer unit F           17      Visible String   8        S       x      x        AUTO, OOS, MAN    7864
CUSTOMER_UNIT_FACTOR_FLOW   Cust. unit fact. F        18      Float            4        S       x      x        OOS               7864
LOW_FLOW_CUT_OFF            Low flow cut-off          19      Unsigned8        1        S       x      x        OOS               7864, 333
SET_LOW_FLOW_CUT_OFF        Set. l. fl. cut-off       20      Float            4        S       x      x        OOS               7864, 333
FLOW_MAX                    Max. flow                 21      Float            4        S       x      x        OOS               7864, 333
PRESSURE                    Pressure                  22      Float            4        D       x
MAX_PRESS_FLOW              Max. press. flow          23      Float            4        S       x      x        OOS               7864, 333
PRESSURE_UNIT               Cal. unit                 24      Unsigned16       2        S       x      x        OOS               7864, 333
TOTALIZER_1_VALUE           Totalizer 1               25      DS-65            5        D       x
44                                                                                                                          Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                                                       Operation
Parameter name,              Parameter name,        Index   Data type        Size     Storage Read   Write   BLK_MODE         Reset codes
option "Symbolic name"       option "Label"                                  (Byte)   Class
TOTALIZER_1_UNIT             Total. 1 eng. unit     26      Unsigned16       2        S      x       x       OOS              7864
TOTALIZER_1_MODE             Neg. flow tot. 1       27      Unsigned8        1        S      x       x       OOS              7864, 333
TOTALIZER_1_FAIL_SAFE_MODE   Fail safe mode         28      Unsigned8        1        S      x       x
TOTALIZER_1_RESET            Reset totalizer 1      29      Unsigned8        1        D      x       x       OOS
CUSTOMER_UNIT_TOT_1          Tot. 1 user unit       30      Visible String   8        S      x       x       AUTO, OOS, MAN 7864
CUSTOMER_UNIT_FACTOR_TOT_1   Fact. u. u. total. 1   31      Float            4        S      x       x       OOS            7864
TOTALIZER_2_VALUE            Totalizer 2            32      Float            4        D      x
TOTALIZER_2_UNIT             Total. 2 eng. unit     33      Unsigned16       2        S      x       x       OOS              7864
TOTALIZER_2_MODE             Neg. flow tot. 2       34      Unsigned8        1        S      x       x       OOS              7864, 333
CUSTOMER_UNIT_TOT_2          Tot. 2 user text       35      Visible String   8        S      x       x       AUTO, OOS, MAN   7864
CUSTOMER_UNIT_FACTOR_TOT_2   Fact. u. u. total. 2   36      Float            4        S      x       x       OOS              7864
                             6.3.9            Methods
                             The FOUNDATION Fieldbus Specification includes the use of methods to make device
                             operation easier. A method is a sequence of interactive steps to be carried out in the specified
                             order so as to configure certain device functions.
                             The following methods are available for Deltabar S:
                             • Restart (Resource Block)
                             • Troubleshooting information, Config. Error No, Alarm Table (Diagnostic Block)
                             • Peakhold indicator, HistoROM (Service Block)
                             • Sensor Trim (TRD Block)
                             For further information on accessing methods, see the description of the FF configuration
                             program used.
Endress+Hauser                                                                                                                            45
Operation                                                                       Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
Measured value
GROUP SELECTION
                                                                                                         ➁
                                  ➀                                       SETTINGS                                        DISPLAY
                                                                                               ➂
                                                        ➃              POS. INPUT VALUE
CALIB. OFFSET
P01-xxxxxxxx-19-xx-xx-en-097
                                    The MEASURING MODE parameter is only displayed via the onsite display on the 1st
                                    selection level. In FieldCare, the LANGUAGE parameter is displayed in the DISPLAY group
                                    and the parameters for configuring the measuring mode are displayed in the Measuring
                                    Mode menu.
46                                                                                                                        Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                                                              Operation
MEASURINGMODE_Flow
MEASURINGMODE_Press
MEASURINGMODE_Press-1
P01-xxxxxxxx-19-xx-xx-en-023
P01-xxxxxxxx-19-xx-xx-en-027
P01-xxxxxxxx-19-xx-xx-en-028
P01-xxxxxxxx-19-xx-xx-en-029
Endress+Hauser                                                                                                                                 47
Operation                           Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
P01-xxxxxxxx-19-xx-xx-en-030
                                                                         Press "E" to save the new value and exit the editing
                                                                         mode.  See next graphic.
P01-xxxxxxxx-19-xx-xx-en-031
P01-xxxxxxxx-19-xx-xx-en-032
P01-xxxxxxxx-19-xx-xx-en-158
P01-xxxxxxxx-19-xx-xx-en-159
                                                                         Using the "E" key, assign the value (3.9 mbar) to the
                                                                         POS. ZERO ADJUST parameter. The device confirms the
                                                                         adjustment and goes back to the parameter, here POS.
                                                                         ZERO ADJUST (see next graphic).
P01-xxxxxxxx-19-xx-xx-en-037
P01-xxxxxxxx-19-xx-xx-en-160
48                                                                                                                Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                                                                                                              Operation
                                                                          ➁
                                                                              Sim.
on
                                                                    off   1   2
                                                                                                               0%
                                                                                                                                                                           ➀
                                                                                                                         Zero
                                                                                                            Sensor                     Display
                                                                                         Simulation
                                                                                                                                        HW
                                                                                                      on
                                                                                     1   2            off
                                                                                                                                                                PC
                                                                                                                                                               Histo ROM
                                                                                                                             TM
                                                                                                                                                 250002273-–
                                                                                                                     FOUNDATION
                                                                                                                     HW-Version:   1
                                                                                                                     SW-Version:   2
P01-xxxxxxxx-19-xx-xx-xx-123
                          1      Optional HistoROM®/M-DAT
                          2      To copy configuration data from the HistoROM/®M-DAT to a device or from a device to a HistoROM®/M-DAT module,
                                 operation must be unlocked (DIP switch 1, position "Off", parameter INSERT PIN No = 100). Please refer also  ä 52,
                                 Section 6.7 "Locking/unlocking operation".
Endress+Hauser                                                                                                                                                                                       49
Operation                             Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
50                                                                                   Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                                Operation
Endress+Hauser                                                                                                51
Operation                                 Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
            6.6           FieldCare
            FieldCare is Endress+Hauser's plant asset management tool based on FDT technology.
             You can use FieldCare to configure all Endress+Hauser devices as well as third-party devices
            which support the FDT standard. Hardware and software requirements you can find on the
            internet: www.endress.com  select your country  Search: FieldCare FieldCare
            Technical Data.
            FieldCare supports the following functions:
            • Configuration of transmitters in offline and online mode
            • Loading and saving device data (upload/download)
            • HistoROM®/M-DAT analysis
            • Documentation of the measuring point
            Connection options:
            • Service interface with Commubox FXA291 and ToF adapter FXA291 (USB).
            • In the "Level Standard" measuring mode, the configuration data that were loaded with FDT
              upload cannot be written again (FDT download). These data are only used to document the
              measuring point.
            • For further information, see  www.endress.com
            • If operation is locked by means of the DIP switch, you can only unlock operation again by
              means of the DIP switch. If operation is locked by means of remote operation e.g.
              FieldCare, you can only unlock operation again by means of remote operation.
            1)    Parameters which refer to how the display appears, e.g. LANGUAGE and DISPLAY CONTRAST, can still be
                  altered.
52                                                                                                 Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                                                                                                                                                       Operation
Simulation
                                                                                                                    Simulation
                                                                              ➁                             ➂
                                                                                                                                                                 0%
                                                                                                                                                                           Zero
                                                                                                                                                              Sensor                     Display
                                                                                                                                           Simulation
                                                                                                      on                         on
                                                                                                                                                                                          HW
                                                                                                                                                        on
1 2 off
                                                                                                                                                                                                                   PC
                                                                                     1      2                   1    2
                                                                                                      off                        off
                                                                                                                                                                                                                  Histo ROM
                                                                                                                                                                               TM
                                                                                                                                                                                                   250002273-–
                                                                                                                                                                       FOUNDATION
                                                                                                                                                                       HW-Version:   1
                                                                                                                                                                       SW-Version:   2
– + E
P01-xxxxxxxx-19-xx-xx-xx-177
                          Fig. 34:        "Hardware locking" DIP switch position on the electronic insert
                          1          If necessary, remove onsite display (optional)
                          2          DIP switch is set to "On": operation is locked.
                          3          DIP switch is set to "Off": operation is unlocked (operation possible)
Description
                           Locking operation                   1. Operation via FF configuration program: select SWLOCK parameter in the
                                                                  Resource Block.
                                                                  Operation via FieldCare: select INSERT PIN No. parameter.
                                                                  Menu path: OPERATING MENU OPERATION INSERT PIN No.
                                                               2. To lock operation, enter "0" for the parameter.
                           Unlocking operation                 1. Operation via FF configuration program: select SWLOCK parameter in the
                                                                  Resource Block.
                                                                  Operation via FieldCare: select INSERT PIN No.parameter.
                                                               2. To unlock operation, enter "100" for the parameter.
Endress+Hauser                                                                                                                                                                                                                         53
Operation                               Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
            6.8          Simulation
            The function of the Analog Input Block, such as input and output scaling, can be simulated
            as follows:
            1.    Set the "Simulation" DIP switch on the electronic insert to "On".
            2.    In the Analog Input Block, select the "Active" option by means of the SIMULATION
                  parameter, ENABLE_DISABLE element.
            3.    Set the Analog Input Block to the AUTO block mode.
            4.    Enter the value and status for the SIMULATION_VALUE and SIMULATION_STATUS
                  elements. During the simulation, the output value and status of the Pressure
                  Transducer Block are replaced by the simulated value and status. The OUT parameter
                  shows the result.
            5.    End simulation (SIMULATION parameter, ENABLE_DISABLE element, "Disabled"
                  option).
            You can check your adjustment for the transmitter by means of the SIMULATION_MODE
            and SIMULATION_VALUE parameters in the Diagnostic Transducer Block. See Operating
            Instructions BA303 "Description of Device Functions Cerabar S/Deltabar S/Deltapilot S",
            SIMULATION_MODE and SIMULATION_VALUE parameter descriptions.
            • Any customer-specific configuration carried out by the factory is not affected by a reset
              (customer-specific configuration remains). If, after a reset, you wish the parameters to be
              reset to the factory settings, please contact Endress+Hauser Service.
            • The OUT Value parameter may have to be rescaled after resetting with code 7864. See also
               ä 74, Section 7.9 "Scaling the OUT parameter".
54                                                                                       Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                                                Operation
Endress+Hauser                                                                                                                     55
Operation                                Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
            1)   The table uses the group and parameter names as they appear in FieldCare. See  ä 40, Section 6.3.8
                 "Index tables of Endress+Hauser parameters" for the assignment of the FieldCare parameter names and the
                 FF configuration program.
56                                                                                                    Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                                 Commissioning
                          7           Commissioning
                           !   WARNING
                          Exceeding the maximum allowable working pressure!
                          Risk of injury due to bursting of parts! Warning messages are generated if pressure is too
                          high.
                          ‣ If a pressure greater than the maximum permitted pressure is present at the device, the
                             messages "E115 Sensor overpressure" and "E727 Sensor pressure error - overrange" are
                             output in succession! Use the device only within the sensor range limits
                          NOTICE
                          Shortfall of the allowable working pressure!
                          Output of messages if pressure is too low.
                          ‣ If a pressure smaller than the minimum permitted pressure is present at the device, the
                             messages "E120 Sensor low pressure" and "E727 Sensor pressure error - overrange" are
                             output in succession! Use the device only within the sensor range limits
Endress+Hauser                                                                                                       57
Commissioning                              Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
58                                                                                             Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                                 Commissioning
                          7.     Specify the alarm priorities by means of the HI_HI_PRI, HI_PRI, LO_LO_PRI and LO_PRI
                                 parameters. Reporting to the field host system only takes place with alarms with a
                                 priority greater than 2.
                          8.     Set the block mode to Auto using the MODE_BLK parameter, TARGET element. For this
                                 purpose, the Resource Block must also be set to the "Auto" block mode.
                          Additional configuration
                          1.     Depending on the control or automation task, configure additional function blocks and
                                 output blocks. See also Operating Instructions BA00303P "Description of Device
                                 Functions Cerabar S/Deltabar S/Deltapilot S".
                          2.     Link the function blocks and output blocks.
                          3.     After specifying the active LAS, download all the data and parameters to the field
                                 device.
Betriebsart-de
Endress+Hauser                                                                                                           59
Commissioning                                 Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
Pressure None -
60                                                                                                         Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                                       Commissioning
                          POS. INPUT VALUE    Position adjustment – the pressure difference between zero (set point) and the
                          Input               measured pressure need not be known. To correct the pressure difference, you
                                              need a reference measurement value (e. g. from a reference device).
                                              Example:
                                              – MEASURED VALUE = 0.5 mbar (0.0073 psi)
                                              – For the POS. INPUT VALUE parameter, specify the desired set point for the
                                                MEASURED VALUE, e.g. 2.0 mbar (0.029 psi).
                                                (The following applies: MEASURED VALUEnew = POS. INPUT VALUE)
                                              – MEASURED VALUE (after entry for POS. INPUT VALUE) = 2.0 mbar (0.029 psi)
                                              – The CALIB. OFFSET parameter displays the resulting pressure difference (offset)
                                                by which the MEASURED VALUE was corrected.
                                                The following applies: CALIB. OFFSET = MEASURED VALUEold – POS. INPUT
                                                VALUE,
                                                here: CALIB. OFFSET= 0.5 mbar (0.0073 psi) – 2.0 mbar (0.029 psi) = – 1.5
                                                mbar (0.022 psi)
                                              Factory setting:
                                              0.0
                          CALIB. OFFSET       Position adjustment – the pressure difference between zero (set point) and the
                          Entry               measured pressure is known. (A reference pressure is not present at the device.)
                                              Example:
                                              – MEASURED VALUE = 2.2 mbar (0.032 psi)
                                              – Via the CALIB. OFFSET parameter, enter the value by which the MEASURED
                                                VALUE should be corrected. To correct the MEASURED VALUE to 0.0 mbar, you
                                                must enter the value 2.2 here.
                                                (The following applies: MEASURED VALUE new = MEASURED VALUEold –
                                                CALIB. OFFSET)
                                              – MEASURED VALUE (after entry for calib. offset) = 0.0 mbar
                                              Factory setting:
                                              0.0
Endress+Hauser                                                                                                                   61
Commissioning                                     Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
1 Close 3.
62                                                                                                                            Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                                    Commissioning
Endress+Hauser                                                                                                           63
Commissioning                                        Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
7.6.3 Quick Setup menu for the Flow measuring mode (FieldCare)
MEASURED VALUE
                                                                                                      1)
                                                                                   GROUP SELECTION
                                    1)                 1)                     2)                                                                      2)
                      LANGUAGE            MEASURING MODE       MEASURING MODE        QUICK SETUP           OPERATING MENU       PROFILE VIEW
MAX FLOW
DAMPING VALUE
P01-xxxxxxxx-19-xx-xx-en-166
Fig. 37: Quick Setup menu for the "Flow" measuring mode
                 MEASURING MODE
                 Select "Flow" option.
                For onsite operation, see also  ä 32, Section 6.2.3 "Function of the operating elements –
                onsite display connected" and  ä 46, Section 6.4 "Local operation – onsite display
                connected".
64                                                                                                                          Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                                                          Commissioning
                          Open container
                          • The Deltabar S PMD75, and FMD77 are usually suitable for level measurement in an open
                            container.
                          • FMD77: the device is ready for calibration immediately after opening a shutoff valve (may
                            or may not be present).
                          • PMD75: before calibrating the device, the pressure piping must be cleaned and filled with
                            fluid. See the following table.
                          3   Vent device.                                                                           +
                              Open 6 briefly, then close it Fill device completely with                                              6
                              again.                        fluid and remove air.                               II                                     I
Endress+Hauser                                                                                                                                              65
Commissioning                                    Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
                Closed container
                • All Deltabar S versions are suitable for level measurement in closed containers.
                • FMD77: the device is ready for calibration immediately after opening the shutoff valves
                  (may or may not be present).
                • FMD78: the device is ready for calibration immediately.
                • PMD75: before calibrating the device, the pressure piping must be cleaned and filled with
                  fluid. See the following table.
                    Now                                                                                            2               4
                    – 3, 6 and 7 are closed.
                                                                                                          1                                5
                    – 2, 4, A and B are open.
66                                                                                                                         Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                                                                Commissioning
                                                                                                                                                            B
                              Fill the negative pressure piping to the level of the
                              condensate trap.                                                         +      A
                          3   Vent device.
Endress+Hauser                                                                                                                                                  67
Commissioning                              Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
68                                                                                             Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                                                                Commissioning
Measuring task                  LEVEL             Measured variable      Description                       Comment                Measured value display
                                SELECTION/        options
                                LEVEL MODE
The measured variable is in     LEVEL             Via OUTPUT UNIT        – Calibration with reference      – Incorrect entries    The measured value
direct proportion to the        SELECTION:        parameter: %, level,     pressure - wet calibration,       are possible         display and the
measured pressure.              Level Easy        volume or mass           see Operating Instructions      – Customized units     LEVEL BEFORE LIN.
Calibration is performed by     Pressure          units.                   BA00303P.                         are not possible     parameter show the
entering two pressure-level                                              – Calibration without                                    measured value.
value pairs.                                                               reference pressure - dry
                                                                           calibration, see Operating
                                                                           Instructions BA00303P.
The measured variable is in     LEVEL             Via OUTPUT UNIT        – Calibration with reference      – Incorrect entries    The measured value
direct proportion to the        SELECTION:        parameter: %, level,     pressure - wet calibration,       are possible         display and the
measured pressure.              Level Easy        volume or mass           see Operating Instructions      – Customized units     LEVEL BEFORE LIN.
Calibration is performed by     Height            units.                   BA00303P.                         are not possible     parameter show the
entering the density and                                                 – Calibration without                                    measured value.
two height-level value                                                     reference pressure - dry
pairs.                                                                     calibration, see Operating
                                                                           Instructions BA00303P.
The measured variable is in LEVEL                 Via LIN.               – Calibration with reference      – Incorrect entries    The measured value
direct proportion to the    SELECTION:            MEASURAND                pressure - wet calibration,       are rejected by      display and the
measured pressure.          Level standard/       parameter:               see Operating Instructions        the device           LEVEL BEFORE LIN.
                            LEVEL MODE :          – % (Level)              BA00303P.                       – Customized level,    parameter show the
                            Linear                – Level                – Calibration without               volume and mass      measured value.
                                                  – Volume                 reference pressure - dry          units are possible
                                                  – Mass                   calibration, see Operating
                                                                           Instructions BA00303P.
The measured variable is        LEVEL             Via LIN.               – Calibration with reference      – Incorrect entries    The measured value
not in direct proportion to     SELECTION:        MEASURAND:               pressure: semiautomatic           are rejected by      display and the TANK
the measured pressure as,       Level standard/   – Pressure + %           entry of linearization table,     the device           CONTENT parameter
for example, with               LEVEL MODE:       – Pressure +             see Operating Instructions      – Customized level,    show the measured
containers with a conical       Pressure            Volume                 BA00303P.                         volume and mass      value.
outlet. A linearization table   Linearized        – Pressure + Mass      – Calibration without               units are possible
must be entered for the                                                    reference pressure: manual
calibration.                                                               entry of linearization table,
                                                                           see Operating Instructions
                                                                           BA00303P.
– Two measured variables        LEVEL             Via COMB.              – Calibration with reference      – Incorrect entries    The measured value
  are required or               SELECTION:        MEASURAND                pressure: wet calibration         are rejected by      display and the TANK
– The container shape is        Level standard/   parameter:               and semiautomatic entry of        the device           CONTENT parameter
  given by value pairs, such    LEVEL MODE:       – Height + Volume        linearization table, see        – Customized level,    show the 2nd
  as height and volume.         Height            – Height + Mass          Operating Instructions            volume and mass      measurand value
                                Linearized        – Height + %             BA00303P.                         units are possible   (volume, mass or %).
The 1st measured variable
%-height or height must be                        – %-Height +           – Calibration without
                                                    Volume                 reference pressure: dry                                The LEVEL BEFORE LIN
in direct proportion to the
                                                  – %-Height + Mass        calibration and manual                                 parameter displays the
measured pressure. The
2nd measured variable                             – %-Height + %           entry of linearization table,                          1st measured value
                                                                           see Operating Instructions                             (%-height or height).
volume, mass or % must
                                                                           BA00303P.
not be in direct proportion
to the measured pressure.
A linearization table must
be entered for the 2nd
measured variable. The 2nd
measured variable is
assigned to the 1st
measured variable by
means of this table.
Endress+Hauser                                                                                                                                           69
Commissioning                                          Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
MEASURED VALUE
                                                                                                            1)
                                                                                         GROUP SELECTION
                                    1)                        1)                    2)                                                                      2)
                      LANGUAGE              MEASURING MODE         MEASURING MODE          QUICK SETUP           OPERATING MENU        PROFILE VIEW
                                                              1)
                                            LEVEL SELECTION                 Pressure               Level                Flow
                                                                                                           3)
                                                                                           EMPTY CALIB.
                                                                                                           3)
                                                                                            FULL CALIB.
                                                                                          DAMPING VALUE
                  1) On-site display only
                  2) FieldCare only
                  3) – LEVEL SELECTION "Level Easy Pressure"
                       and CALIBRATION MODE "Wet"
                     – LEVEL SELECTION = "Level Standard",
                       LEVEL MODE = "Linear" and
                       CALIBRATION MODE = "Wet"
P01-xMD7xxxx-19-xx-xx-en-079
                 GROUP SELECTION
                 Select QUICK SETUP menu.
70                                                                                                                                Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                                               Commissioning
                          For onsite operation, see also  ä 32, Section 6.2.3 "Function of the operating elements –
                          onsite display connected" and  ä 46, Section 6.4 "Local operation – onsite display
                          connected".
Endress+Hauser                                                                                                                        71
Commissioning                                     Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
1 Close 3.
                4    Vent device.
                     Open 2 and 4.                 Introduce fluid.
                     Now
                     – 1, 3, 5, 6 and 7 are closed.                                                                             P01-xMD7xxxx-11-xx-xx-xx-002
                     – 2 and 4 are open.                                          Fig. 42:         Above: preferred installation for gases
                     – A and B are open (if present).                                              Below: preferred installation for liquids
                                                                                  I            Deltabar S PMD75
                6    Carry out calibration if necessary.  ä 72, Section 7.8.2. II             Three-way valve manifold
                                                                                  III          Separator
                                                                                  1, 5         Drain valves
                                                                                  2, 4         Inlet valves
                                                                                  3            Equalizing valve
                                                                                  6, 7         Vent valves on Deltabar S
                                                                                  A, B         Shutoff valve
72                                                                                                                            Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                                                                   Commissioning
MEASURED VALUE
                                                                                                                    1)
                                                                                                 GROUP SELECTION
                                               1)                     1)                    2)                                                                     2)
                                LANGUAGE             MEASURING MODE        MEASURING MODE          QUICK SETUP           OPERATING MENU       PROFILE VIEW
DAMPING VALUE
P01-xMD7xxxx-19-xx-xx-en-080
                           GROUP SELECTION
                           Select QUICK SETUP menu.
                          For onsite operation, see also  ä 32, Section 6.2.3 "Function of the operating elements –
                          onsite display connected" and  ä 46, Section 6.4 "Local operation – onsite display
                          connected".
Endress+Hauser                                                                                                                                                   73
Commissioning                                   Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
                                   EU_0                                        0
                                   0                                                                      UNITS_
                                            0             0.7      1            EU_0               EU_100 INDEX:
                                                                                                          %
                                                                                     0          70  100
                                                                                           OUT Value = 70
                                                                                                      P01-xMx7xxxx-05-xx-xx-en-008
                • If you have selected the "Direct" mode for the L_TYPE parameter, you cannot change the
                  values and units for XD_SCALE and OUT_SCALE.
                • The L_TYPE, XD_SCALE and OUT_SCALE parameters can only be changed in the OOS
                  block mode.
                • Make sure that the output scaling of the Pressure Transducer Block SCALE_OUT matches
                  the input scaling of the Analog Input Block XD_SCALE.
74                                                                                                Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                                               Commissioning
Event severity     Default event category      Event source    Bit   Events in this group
Highest severity   Failure (F)                 Sensor          31    • 122: F>Sensor not connected
                                                                     • 716: F>Process isolating diaphragm broken
Endress+Hauser                                                                                                                    75
Commissioning                                             Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
Event severity Default event category Event source Bit Events in this group
High severity    Check (C)                Sensor          27    • 101: C>Sensor electronic EEPROM error
                                                                • 725: C>Sensor connection error, cycle disturbance
                                                                • 747: C>Sensor software not compatible to electronics
Event severity Default event category Event source Bit Events in this group
76                                                                                                                      Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                                                Commissioning
Endress+Hauser                                                                                                                   77
Commissioning                                                                 Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
Event severity Highest severity High severity Low severity Lowest severity
Event source1) S E C P S E C P S E C P S E C P
Bit 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15...1
FD_FAIL_MAP 1 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0
FD_CHECK_MAP 0 0 0 0 1 1 1 1 0 0 0 0 0 0 0 0 0
FD_OFFSPEC_MAP 0 0 0 0 0 0 0 0 1 1 1 1 0 0 0 0 0
FD_MAINT_MAP 0 0 0 0 0 0 0 0 0 0 0 0 1 1 1 1 0
                                        Example
                                        The Highest Severity / Electronics group contains the events 131: Checksum error in
                                        EEPROM: min/max segment, among others. These should no longer be categorized as
                                        Failure (F), and should be categorized as Check (C) instead.
                                        1.       In the FieldCare navigation window navigate to Expert Field Device Diagnostic 
                                                 Configuration
78                                                                                                                                    Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                                   Commissioning
                          2.   In the Failure column search for the Highest Severity Electronic group and disable the
                               associated check box (A). Enable the appropriate check box in the Function column (B).
                               Please note that the "Accept" button must be pressed to confirm each entry.
(A) (B)
                          It must be ensured that the appropriate bit is set in at least one of the assignment
                          parameters for each event group. Otherwise a category is not transmitted with the event via
                          the bus. The control system will therefore generally ignore the presence of the event.
                          The detection of diagnostic events and the transmission of the messages on the bus is
                          configured on the FieldCare page Expert Field Device Diagnostic Configuration. The
                          "Mask" column is used for the transmission of the message on the bus. It must be noted that
                          device messages can still be transmitted by polling the active bits in Status 1 and 2. The mask
                          check box acts as a negative check box, i.e. if a field is selected the associated events are not
                          transmitted on the bus. The Resource Block must be set to the Auto mode to transmit status
                          information on the bus.
Endress+Hauser                                                                                                          79
Commissioning                              Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
                Example
                Error 115 "Sensor overpressure" should no longer be categorized as Out of Specification
                (S), and should be categorized as Function (C) instead.
                1.   In the FieldCare navigation window navigate to Expert Field Device Diagnostic 
                     Configuration.
80                                                                                            Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                                   Commissioning
                          2.   Select the "Configurable area" tab. In the factory setting, all the bits in the Configurable
                               Area Bits column have the value not assigned (A).
                          3.   Select one of these bits (here Configurable Area Bit 15, for instance) and select the
                               Sensor overpressure (B) option from the associated picklist. Confirm your choice by
                               pressing "Accept".
                          4.   Enable the check box for the bit concerned (here: Configurable Area Bit 15) (C).
                               Confirm your choice by pressing "Accept".
                          Additional information:
                          The "Status 1" and "Status 2" tabs indicate whether an event is active.
                          Changing the error category for Sensor overpressure does not affect an error that already
                          exists. The new category is only assigned if this error occurs again after the change has been
                          made. The "Status 1" and "Status 2" tabs indicate whether an event is active.
Endress+Hauser                                                                                                          81
Commissioning                             Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
82                                                                                 Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                                    Commissioning
                          Event priority
                          Event messages are only transmitted on the bus if their priority is between 2 and 15. Priority
                          1 events are displayed but are not transmitted on the bus. Events whose priority is 0 are
                          ignored. All events are assigned the priority 0 in the factory setting. It is possible to change
                          the priority individually for the four assignment parameters.
                          Example
                          The priority of the "Failure" category is to be set to "2" .
                          1.   In the FieldCare navigation window navigate to Expert Field Device Diagnostics 
                               Configuration
2. Select the "Standard area" tab and set the priority to "2" in the "Failure" column (D).
(D)
Endress+Hauser                                                                                                           83
Commissioning                             Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
84                                                                                          Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                                   Commissioning
                          Example
                          The status of error 115 "Sensor overpressure" should no longer be indicated as "Uncertain"
                          and should instead be indicated as "Bad".
                          1.   In the FieldCare navigation window navigate to Expert Field Device Diagnostics 
                               PV Status Config
2. All the bits of the Status Select Events have the status "Uncertain" in the factory setting.
                          3.   Select the "Bad" option for the "Status Select Event 115" row. Press Enter to confirm your
                               entry.
Endress+Hauser                                                                                                          85
Maintenance                              Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
              8           Maintenance
              Deltabar S requires no maintenance.
86                                                                                           Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                            Diagnostics and troubleshooting
9.1 Troubleshooting
                          Device is not        The supply voltage does not match the           Apply correct voltage.
                          responding.          specifications on the nameplate.
                          No display           Onsite display is set too bright or too dark.   • Set the local display brighter by
                                                                                                 simultaneously pressing O and F.
                                                                                               • Set the local display darker by
                                                                                                 simultaneously pressing S and F.
                                               Connector for local display is not plugged in Ensure connector is plugged in correctly.
                                               correctly.
Endress+Hauser                                                                                                                           87
Diagnostics and troubleshooting                           Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
Error categories
"Failure"
"Check"
C The device is in the service mode (e.g. during a simulation) or is performing a self-check.
"Out of specification"
"Maintenance required"
Diagnostic event
3-digit number
                             • If the device detects a defect in the onsite display during initialization, special error
                               messages are generated. For the error messages, see  ä 88, Section 9.2.2 "Onsite
                               display error messages".
                             • For support and further information, please contact Endress+Hauser Service.
                             • See also Section 9.8, Section 9.9 and Section 9.10.
                             • If the category of a diagnostic event is being changed, an empty field might be displayed
                               instead of "F, C, S, M".
88                                                                                                                       Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                   Diagnostics and troubleshooting
Message Measure
P01-xMx7xxxx-05-xx-xx-en-008
Endress+Hauser                                                                                                                     89
Diagnostics and troubleshooting                                                                                           Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
PRIMARY_VALUE_TYPE
                                                                                                                                                                             (Impacted CHANNEL
                                                                                                                                                                             TRANSDUCER Status
                               XD_ERROR Value Bit
BLOCK_ERROR Text
                                                                                                                                                     (Operating Mode)
                                                                                                                       PRIMARY_VALUE
                                                                                                                       Operating Mode)
                                                    XD_ERROR Text
             Diagnostic Code
                                                                                                                                                                             Propagation
Error type
                                                                                                                                                                             selection)
Alarm        747               17                   General Error           0                       Other              BAD_SENSOR_FAILURE            Pressure, Level, Flow   All
122 20 Electronics Failure 7 Sensor Failure BAD_SENSOR_FAILURE Pressure, Level, Flow All
704 20 Electronics Failure 7 Sensor Failure BAD_DEVICE_FAILURE Pressure, Level, Flow All
743 20 Electronics Failure 7 Sensor Failure BAD_DEVICE_FAILURE Pressure, Level, Flow All
748 20 Electronics Failure 7 Sensor Failure BAD_DEVICE_FAILURE Pressure, Level, Flow All
90                                                                                                                                                                                  Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                                                                                                 Diagnostics and troubleshooting
PRIMARY_VALUE_TYPE
                                                                                                                                                                                   (Impacted CHANNEL
                                                                                                                                                                                   TRANSDUCER Status
                               XD_ERROR Value Bit
BLOCK_ERROR Text
                                                                                                                                                   (Operating Mode)
                                                                                                                     PRIMARY_VALUE
                                                                                                                     Operating Mode)
                                                    XD_ERROR Text
             Diagnostic Code
                                                                                                                                                                                   Propagation
Error type
                                                                                                                                                                                   selection)
Alarm        113               20                   Electronics Failure   0                       Other              BAD_DEVICE_FAILURE            Pressure, Level, Flow           All
Endress+Hauser                                                                                                                                                                                         91
Diagnostics and troubleshooting                                                                                         Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
PRIMARY_VALUE_TYPE
                                                                                                                                                                           (Impacted CHANNEL
                                                                                                                                                                           TRANSDUCER Status
                               XD_ERROR Value Bit
BLOCK_ERROR Text
                                                                                                                                                   (Operating Mode)
                                                                                                                     PRIMARY_VALUE
                                                                                                                     Operating Mode)
                                                    XD_ERROR Text
             Diagnostic Code
                                                                                                                                                                           Propagation
Error type
                                                                                                                                                                           selection)
Alarm/       115               17                   General Error         0                       Other              – BAD_NON_SPECIFIC            Pressure, Level, Flow   Primary Value(1)
Warning                                                                                                              – STATUS_UNCERTAIN                                    Pressure(3)
                                                                                                                     – GOOD                                                Maximum Pressure(4)
                                                                                                                                                                           Counter P > Pmax(5)
                                                                                                                                                                           Totalizer 1 (6)
             120               17                   General Error         0                       Other              – BAD_NON_SPECIFIC            Pressure, Level, Flow   Primary Value(1)
                                                                                                                     – STATUS_UNCERTAIN                                    Pressure(3)
                                                                                                                     – GOOD                                                Maximum Pressure(4)
                                                                                                                                                                           Counter P > Pmax(5)
                                                                                                                                                                           Totalizer 1 (6)
             720               17                   General Error         0                       Other              – BAD_NON_SPECIFIC            Pressure, Level, Flow   Sensor Temperature(2)
                                                                                                                     – STATUS_UNCERTAIN
                                                                                                                     – GOOD
             715               17                   General Error         7                       Sensor Failure – BAD_NON_SPECIFIC                Pressure, Level, Flow   Sensor Temperature(2)
                                                                                                                 – STATUS_UNCERTAIN
                                                                                                                 – GOOD
             726               20                   Electronics Failure   7                       Sensor Failure – BAD_NON_SPECIFIC                Pressure, Level, Flow   All
                                                                                                                 – STATUS_UNCERTAIN
                                                                                                                 – GOOD
             740               20                   Electronics Failure   7                       Sensor Failure – BAD_NON_SPECIFIC                Pressure, Level, Flow   All
                                                                                                                 – STATUS_UNCERTAIN
                                                                                                                 – GOOD
             727               20                   Electronics Failure   7                       Sensor Failure – BAD_NON_SPECIFIC                Pressure, Level, Flow   All
                                                                                                                 – STATUS_UNCERTAIN
                                                                                                                 – GOOD
92                                                                                                                                                                                Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                                                                                                 Diagnostics and troubleshooting
PRIMARY_VALUE_TYPE
                                                                                                                                                                                   (Impacted CHANNEL
                                                                                                                                                                                   TRANSDUCER Status
                               XD_ERROR Value Bit
BLOCK_ERROR Text
                                                                                                                                                   (Operating Mode)
                                                                                                                     PRIMARY_VALUE
                                                                                                                     Operating Mode)
                                                    XD_ERROR Text
             Diagnostic Code
                                                                                                                                                                                   Propagation
Error type
                                                                                                                                                                                   selection)
Warning      106               17                   General Error         0                       Other              STATUS_UNCERTAIN              Pressure, Level, Flow           All
             613               17                   General Error         0                       Other              UNCERTAIN_SIM                 Pressure, Level, Flow           Primary Value(1)
                                                                                                                                                                                   Maximum Pressure(4)
                                                                                                                                                                                   Counter P > Pmax(5)
                                                                                                                                                                                   Totalizer 1 (6)
             702               17                   General Error         0                       Other              GOOD                          Pressure, Level, Flow           None
             102               23                   Data Integrity        0                       Other              GOOD                          Pressure, Level, Flow           Maximum Pressure(4)
                                                    Error                                                                                                                          Counter P > Pmax(5)
Endress+Hauser                                                                                                                                                                                         93
Diagnostics and troubleshooting                              Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
101        Alarm      F>Sensor electronic      20      11       – Electromagnetic effects are      – Wait a few minutes.               19
                      EEPROM error                                greater than specifications in   – Restart the device. Perform
                                                                  the technical data.                reset (Code 62).
                                                                  (See Section 10.) This         – Block off electromagnetic
                                                                  message normally only              effects or eliminate source of
                                                                  appears briefly.                   disturbance.
110        Alarm      F>Checksum error in      23      11       – The supply voltage is            – Reestablish supply voltage.       6
                      EEPROM:                                     disconnected when writing.         Perform reset if necessary
                      configuration segment                                                          (code 7864) and recalibrate
                                                                                                     the device.
                                                                – Electromagnetic effects are      – Block off electromagnetic
                                                                  greater than specifications in     effects or eliminate sources of
                                                                  the technical data.                disturbance.
                                                                  (See Section 10.)
                                                                – Main electronics defect.         – Replace main electronics.
113        Alarm      F>ROM failure in         20      9        – Main electronics defect.         – Replace main electronics.         1
                      transmitter electronic
121        Alarm      F>Checksum error in      23      9        – Main electronics defect.         – Replace main electronics.         5
                      factory segment of
                      EEPROM
122        Alarm      F>Sensor not             20      0        – Cable connection sensor –        – Check cable connection and        14
                      connected                                   main electronics                   repair if necessary.
                                                                  disconnected.
                                                                – Electromagnetic effects are      – Block off electromagnetic
                                                                  greater than specifications in     effects or eliminate source of
                                                                  the technical data.                disturbance.
                                                                  (See Section 10.)
130 Alarm F>EEPROM is defect. 23 11 – Main electronics defect. – Replace main electronics. 11
131        Alarm      F>Checksum error in      23      11       – Main electronics defect.         – Replace main electronics.         9
                      EEPROM: min/max
                      segment
132        Alarm      F>Checksum error in      23      11       – Main electronics defect.         – Replace main electronics.         7
                      totalizer EEPROM
133        Alarm      F>Checksum error in      23      11       – An error occurred when           – Perform reset (code 7864)         8
                      History EEPROM                              writing.                           and recalibrate the device.
135        Alarm      F>Checksum error in      23      11       – Main electronics defect.         – Replace main electronics.         10
                      EEPROM FF segment
703        Alarm      F>Measurement error      20      11       – Fault in the main electronics.   – Briefly disconnect device from 24
                                                                                                     the power supply.
94                                                                                                                      Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                             Diagnostics and troubleshooting
725        Alarm      F>Sensor connection      20      11       – Electromagnetic effects are      – Block off electromagnetic        27
                      error, cycle disturbance                    greater than specifications in     effects or eliminate source of
                                                                  the technical data.                disturbance.
                                                                  ( See Section 10.)
                                                                – Setscrew loose.                  – Retighten setscrew with 1 Nm
                                                                                                     (0.74 lbf ft) (see
                                                                                                     Section 4.3.9).
728        Alarm      F>RAM error              20      9        – Fault in the main electronics.   – Briefly disconnect device from 2
                                                                                                     the power supply.
729        Alarm      F>RAM error              20      9        – Fault in the main electronics.   – Briefly disconnect device from 3
                                                                                                     the power supply.
736        Alarm      F>RAM error              20      9        – Fault in the main electronics.   – Briefly disconnect device from 4
                                                                                                     the power supply.
737        Alarm      F>Measurement error      20      11       – Fault in the main electronics.   – Briefly disconnect device from 22
                                                                                                     the power supply.
738        Alarm      F>Measurement error      20      11       – Fault in the main electronics.   – Briefly disconnect device from 21
                                                                                                     the power supply.
739        Alarm      F>Measurement error      20      11       – Fault in the main electronics.   – Briefly disconnect device from 25
                                                                                                     the power supply.
742        Alarm      F>Sensor connection      20      11       – Electromagnetic effects are      – Wait a few minutes.              20
                      error (upload)                              greater than specifications in   – Perform reset (code 7864)
                                                                  the technical data.                and recalibrate the device.
                                                                  (See Section 10.) This
                                                                  message normally only
                                                                  appears briefly.
743        Alarm      F>Electronic PCB error   20      0        – Electromagnetic effects are      – Wait a few minutes.              15 /
                      during initialization                       greater than specifications in   – Restart the device. Perform      16
                                                                  the technical data.                reset (Code 62).
                                                                  ( See Section 10.) This
                                                                  message normally only
                                                                  appears briefly.
                                                                – Main electronics defect.         – Replace main electronics.
744        Alarm      F>Main electronic PCB 20         11       – Electromagnetic effects are      – Restart the device. Perform      12
                      error                                       greater than specifications in     reset (Code 62).
                                                                  the technical data.              – Block off electromagnetic
                                                                  (See Section 10.)                effects or eliminate source of
                                                                                                     disturbance.
Endress+Hauser                                                                                                                             95
Diagnostics and troubleshooting                              Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
747        Alarm      F>Sensor software not     17      0        – Sensor does not suit the         – Replace sensor with a suitable 18
                      compatible to                                device (electronic sensor          sensor.
                      electronics                                  nameplate).
748        Alarm      F>Memory failure in       20      0        – Electromagnetic effects are      – Block off electromagnetic        17
                      signal processor                             greater than specifications in     effects or eliminate source of
                                                                   the technical data.                disturbance.
                                                                   ( See Section 10.)
602        Warning    C>Linearization curve     19      0        – The linearization table is not   – Add to or correct linearization 67
                      not monoton                                  monotonic increasing.              table. Then accept
                                                                                                      linearization table again.
604        Warning    C>Linearization table     19      0        Note! There is no min. span for the y-points as of software version
                      invalid. Min. 2 points.                       "03.00.00".
                                                                 – The linearization table has      1. Add to linearization table.     68
                                                                   fewer than 2 points.             Perform the linearization again
                                                                                                    if necessary.
                                                                                                    2. Correct the linearization table
                                                                                                    and accept it again.
613        Warning    C>Simulation active       17      3        – Simulation is switched on, i.e. – Switch off simulation.            70
                                                                   the device is not measuring at
                                                                   present.
701        Warning    C>Adjustment outside      17      0        – The adjustment carried out       – Carry out calibration again.     63
                      sensor nominal range                         would cause a breach of the
                                                                   nominal sensor range.
704        Alarm      C>Measurement error       20      0        – Fault in the main electronics.   – Briefly disconnect device from 13
                                                                                                      the power supply.
96                                                                                                                       Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                           Diagnostics and troubleshooting
710        Warning    B>Set span too small.    18      0        – Values for calibration (e.g.   – Adjust calibration to suit       60
                      Not allowed.                                lower range value and upper      sensor (see Operating
                                                                  range value) are too close       Instructions BA00303P,
                                                                  together.                        parameter description),
                                                                                                   CAL_MIN_SPAN/MINIMUM
                                                                                                   SPAN parameter).
                                                                – The sensor was replaced and    – Reset the LRV and/or URV to
                                                                  the customer-specific            suit the sensor. Pay attention
                                                                  configuration does not suit      to position adjustment.
                                                                  the sensor.                    – Replace sensor with a suitable
                                                                                                   sensor.
713        Alarm      C>100% POINT             18      0        – The sensor was replaced.       – Carry out calibration again.     46
                      (LEVEL_100_PERCEN
                      T_VALUE) level out of
                      edit limits
719        Alarm      C>Y-VAL                  19      0        – At least one Y-VALUE           – Carry out calibration again.  47
                      (TAB_XY_VALUE) of                           (TAB_XY_VALUE) in the            (See Operating Instructions
                      lin. table out of edit                      linearization table is below     BA00303P, parameter
                      limits                                      the SCALE_OUT, EU_0/             description), Section 5).
                                                                  TANK CONTENT MIN. or
                                                                  above the SCALE_OUT,
                                                                  EU_100/TANK CONTENT
                                                                  MAX.
721        Alarm      C>ZERO POSITION          18      0        – LEVEL MIN                      – Perform reset (code 2710)        48
                      (LEVEL OFFSET) level                        (LINEAR_LEVEL_ MIN) or           and recalibrate the device.
                      out of edit limits                          LEVEL MAX
                                                                  (LINEAR_LEVEL_MAX) has
                                                                  been changed.
722        Alarm      C>EMPTY CALIB.           18      0        – LINEAR_ LEVEL_MIN/LEVEL – Perform reset (code 2710)               49/50
                      (SCALE_OUT, EU_0)                           MIN or                    and recalibrate the device.
                      or FULL CALIB.                              LINEAR_LEVEL_MAX/
                      (SCALE_OUT,                                 LEVEL MAX has been
                      EU_100) out of edit                         changed.
                      limits
Endress+Hauser                                                                                                                           97
Diagnostics and troubleshooting                           Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
746        Warning    C>Sensor connection    20      11       – Electromagnetic effects are      – Wait a few minutes.              28
                      error - initializing                      greater than specifications in   – Restart the device. Perform
                                                                the technical data.                reset (Code 7864).
                                                                ( See Section 10.) This         – Block off electromagnetic
                                                                message normally only              effects or eliminate source of
                                                                appears briefly.                   disturbance.
98                                                                                                                    Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                          Diagnostics and troubleshooting
102        Warning    M>Checksum error in    23      11       – Main electronics defect.       – Replace main electronics.          62
                      EEPROM: peakhold                          Correct measurement can
                      segment                                   continue as long as you do not
                                                                need the peak hold indicator
                                                                function.
116        Warning    M>Download error,      17      0        – The file is defect.             – Use another file.                 38
                      repeat download
                                                              – During the download, the        – Check cable connection PC –
                                                                data are not correctly            transmitter.
                                                                transmitted to the processor,   – Block off electromagnetic
                                                                e.g. because of open cable        effects or eliminate sources of
                                                                connections, spikes (ripple)      disturbance.
                                                                on the supply voltage or        – Perform reset (code 7864)
                                                                electromagnetic effects.          and recalibrate the device.
                                                                                                – Repeat download.
134        Warning    M>EEPROM lifetime      17      0        – Writing too often to            – Reduce write accessing to         65
                      WARNING                                   EEPROM.                           EEPROM.
700        Warning    M>Last configuration   23      11       – An error occurred when          – Perform reset (code 7864)         63
                      not stored                                writing or reading                and recalibrate the device.
                                                                configuration data or the
                                                                power supply was
                                                                disconnected.
702        Warning    M>HistoROM data not    17      11       – Data were not written           – Repeat upload.                    64
                      consistent                                correctly to the HistoROM,      – Perform reset (code 7864)
                                                                e.g. if the HistoROM was          and recalibrate the device.
                                                                detached during the writing
                                                                process.
706        Warning    M>Configuration in     23      11       – Configuration (parameters) in – Copy data from the device to 69
                      HistoROM and device                       the HistoROM and in the         the HistoROM. ( ä 49,
                      not identical                             device not identical.           Section 6.5.1 "Copying
                                                                                                configuration data".)
                                                                                              – Copy data from the HistoROM
                                                                                                to the device. ( ä 49,
                                                                                                Section 6.5.1 "Copying
                                                                                                configuration data".) The
                                                                                                message remains if the
                                                                                                HistoROM and the device
                                                                                                have different software
                                                                                                versions. The message
                                                                                                disappears if you copy the
                                                                                                data from the device to the
                                                                                                HistoROM.
                                                                                              – Device reset codes such as 1
                                                                                                or 40864 do not have any
                                                                                                effect on the HistoROM. That
                                                                                                means that if you perform a
                                                                                                reset, the configurations in
                                                                                                the HistoROM and in the
                                                                                                device can be different.
Endress+Hauser                                                                                                                           99
Diagnostics and troubleshooting                          Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
740        Alarm/     M>Calculation         20      7        – Level measuring mode: the      – Check configuration and         29
           warning    overflow, bad                            measured pressure has            recalibrate if necessary.
                      configuration                            undershot the value for        – Select a device with a suitable
                                                               SCALE_IN, EU_0/HYDR.             measuring range.
                                                               PRESS. MIN. or overshot the
                                                               value for SCALE_IN,
                                                               EU_100/HYDR. PRESS MAX.
100                                                                                                                Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                         Diagnostics and troubleshooting
120        Alarm/     S>Sensor low pressure   17      0        – Pressure too low.             – Increase pressure until          32
           warning                                                                               message disappears.
715        Alarm/     S>Sensor over           17      7        – The temperature measured in – Reduce process temperature/        34
           warning    temperature                                the sensor is greater than the ambient temperature.
                                                                 upper nominal temperature
                                                                 of the sensor. (See also
                                                                 Operating Instructions
                                                                 BA00303P, parameter
                                                                 description for
                                                                 TEMPERATURE_1
                                                                 _SENSOR_LIMIT_HIGH/
                                                                 Tmax SENSOR or these
                                                                 Operating Instructions)
Endress+Hauser                                                                                                                      101
Diagnostics and troubleshooting                           Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
726        Alarm/     S>Sensor temperature   20      7        – Electromagnetic effects are      – Block off electromagnetic        33
           warning    error - overrange                         greater than specifications in     effects or eliminate source of
                                                                the technical data.                disturbance.
                                                                (See Section 10.)
727        Alarm/     S>Sensor pressure      20      7        – Electromagnetic effects are      – Block off electromagnetic        30
           warning    error - overrange                         greater than specifications in     effects or eliminate source of
                                                                the technical data.                disturbance.
                                                                (See Section 10.)
730        Alarm/     S>Pmin ALARM           19      0        – Pressure measured value has      – Check system/pressure            55
           Warning    WINDOW                                    undershot the value specified      measured value.
                      (PRESSURE_1_USER_                         for the PRESSURE_1_USER_         – Change value for
                      LOW_LIMIT)                                LOW_LIMIT/Pmin ALARM               PRESSURE_1_
                      undershot                                 WINDOW parameter.                  USER_LOW_LIMIT/Pmin
                                                                                                   ALARM WINDOW if
                                                                                                   necessary.
                                                                                                   (See also Operating
                                                                                                   Instructions BA00303P,
                                                                                                   parameter description or
                                                                                                   these Operating Instructions)
                                                              – Loose connection at sensor       – Wait a short period of time
                                                                cable.                             and tighten the connection, or
                                                                                                   avoid loose connection.
731        Alarm/     S>Pmax ALARM         19        0        – Pressure measured value has      – Check system/pressure            54
           Warning    WINDOW                                    overshot the value specified       measured value.
                      (PRESSURE_1_UER_                          for the PRESSURE_1_USER_         – Change value for
                      HIGH_LIMIT) overshot                      HIGH_LIMIT/Pmax ALARM              PRESSURE_1_USER_ HIGH_
                                                                WINDOW parameter.                  LIMIT/Pmax ALARM
                                                                                                   WINDOW if necessary.
                                                                                                   (See also Operating
                                                                                                   Instructions BA00303P,
                                                                                                   parameter description or
                                                                                                   these Operating Instructions)
102                                                                                                                    Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                                                     Diagnostics and troubleshooting
FOUNDATION             The process variable in question is       Device continues measuring. The process For this error, you can enter whether the
Fieldbus               transmitted with the status BAD.          variable in question is transmitted with device should react as in the event of an
                                                                 the status UNCERTAIN.                    alarm or as in the event of a warning.
                                                                                                          See appropriate column for "Alarm" or
                                                                                                          "Warning"
                                                                                                          (see Operating Instructions
                                                                                                          BA00303P, parameter description),
                                                                                                          REACTION_ON_ ALARM_NR/SELECT
                                                                                                          ALARM TYPE parameter).
                                                                                                          The GOOD status can also be assigned to
                                                                                                          the individual error via the parameters
                                                                                                          FF912_STATUS_SELECT_1 to
                                                                                                          FF912_STATUS_SELECT _131.
Onsite display         – The measured value and message are – The measured value and message are           – The measured value and message are
                         displayed alternately                 displayed alternately                         displayed alternately
                       – Measured value display:  -symbol is – Measured value display: -symbol             – Measured value display: see
                         permanently displayed.                flashes.                                      corresponding "Alarm" or "Warning"
                                                                                                             column
                       Message display                       Message display:                              Message display:
                       – A + 3-digit number such as A122 and – W + 3-digit number such as W613             – E + 3-digit number such as E731 and
                       – Description                           and                                         – Description
                                                             – Description
Remote operation (FF   In the event of an alarm, the ALARM       In the case of a warning, the ALARM       In the case of an error, the ALARM
configuration          STATUS/ALARM_STATUS 1) parameter          STATUS/ALARM_STATUS parameter            STATUS/ALARM_STATUS parameter
program/FieldCare)     displays a 3-digit number such as 122     displays a 3-digit number such as 613     displays a 3-digit number such as 731
                       for "Sensor connection error, incorrect   for "Simulation is active".               for "Pmax ALARM WINDOW undershot".
                       data".
1) FF configuration program: Diagnostic Transducer Block. Menu path FieldCare: OPERATING MENU  MESSAGES
Endress+Hauser                                                                                                                                 103
Diagnostics and troubleshooting                            Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
                               The value specified by means of the FSAFE_VALUE1 parameter is used for further
                               processing with the status UNCERTAIN.
                             • Wrong Value
                               The current value is used for further processing with the status BAD.
                             Factory setting:
                             • FSAFE_TYPE: FsafeValue
                             • FSAFE_VALUE: 0
                             The failsafe mode is also activated if the "Out of service" option was selected by means of the
                             MODE_BLK parameter, "Target" element.
1 These parameters are not available by means of the FieldCare operating program.
Settings 1) Measures
                              – ALARM_HOLD_ON_TIME/      – Rectify the cause of the message (see also Section 9.5).
                                ALARM DISPLAY TIME = 0 s
                              – ACKNOWLEDGE_ALARM_MODE
                                /ACK. ALARM MODE = off
                              – ALARM_HOLD_ON_TIME/     – Rectify the cause of the message (see also Section 9.5).
                                ALARM DISPL. TIME > n s – Wait for the alarm display time to elapse.
                              – ACKNOWLEDGE_ALARM_MODE
                                /ACK. ALARM MODE = off
                              – ALARM_HOLD_ON_TIME/     – Rectify the cause of the message (see also Section 9.5).
                                ALARM DISPL. TIME = 0 s – Confirm message using ACKNOWLEDGE_ALARM/ACK. ALARM
                              – ACKNOWLEDGE_ALARM_MODE    parameter.
                                /ACK. ALARM MODE = on
                              – ALARM_HOLD_ON_TIME/     – Rectify the cause of the message (see also Section 9.5).
                                ALARM DISPL. TIME > n s – Confirm message using ACKNOWLEDGE_ALARM/ACK. ALARM
                              – ACKNOWLEDGE_ALARM_MODE    parameter.
                                /ACK. ALARM MODE = on   – Wait for the alarm display time to elapse. If a message appears and the
                                                          alarm display time elapses before the message has been acknowledged,
                                                          the message is cleared once it has been acknowledged.
                             9.8            Repair
                             The Endress+Hauser repair concept provides for measuring devices to have a modular design
                             and also that the customer may carry out repairs  ä 105 "Spare Parts" on ).
                             • For certified devices, please consult the "Repair of Ex-certified devices" section.
                             • For more information on service and spare parts contact the Endress+Hauser Service.
                               ( See www.endress.com/worldwide.)
104                                                                                                              Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus                               Diagnostics and troubleshooting
                          9.11       Return
                          The measuring device must be returned if repairs or a factory calibration are required, or if
                          the wrong measuring device has been ordered or delivered. According to legal regulations,
                          Endress+Hauser, as a ISO-certified company, is required to follow certain procedures when
                          handling returned products that are in contact with process fluids.
                          To ensure swift, safe and professional device returns, please read the return procedures and
                          conditions on the Endress+Hauser website at www.services.endress.com/return-material.
                          9.12       Disposal
                          When disposing, separate and recycle the device components based on the materials.
Endress+Hauser                                                                                                     105
Technical data                                                   Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
                                                                                   BA301P/00/EN/10.07        BA303P/00/EN/04.05
                                                                                   71043305                  52027502
                                                                                   BA301P/00/EN/12.07        BA303P/00/EN/04.05
                                                                                   71043305                  52027502
                                                                                   BA301P/00/EN/05.08        BA303P/00/EN/04.05
                                                                                   71071735                  52027502
                                                                                   BA301P/00/EN/06.09        BA303P/00/EN/06.09
                                                                                   71095421                  71095456
                                                                                   BA301P/00/EN/05.10        BA303P/00/EN/05.10
                                                                                   71111781                  71111814
                                                                                   BA301P/00/EN/13.11        BA303P/00/EN/13.11
                                                                                   71139766                  71139808
                                                                                   BA00301P/00/EN/14.12      BA303P/00/EN/13.11
                                                                                   71161885                  71139808
01.2013   04.00.zz         FF912 Field Diagnostic Profile Integration              BA00301P/00/EN/15.13      BA00303P/00/EN/14.13
                                                                                   71207382                  71207399
                                                                                   BA00301P/00/EN/16.14      BA00303P/00/EN/15.14
                                                                                   71254467                  71254484
                                                                                   BA00301P/00/EN/17.14      BA00303P/00/EN/16.14
                                                                                   71270387                  71254484
                                                                                   BA00301P/00/EN/18.15      BA00303P/00/EN/16.14
                                                                                   71281256                  71254484
                                 10             Technical data
                                 For technical data, please refer to Technical Information TI00382P for Deltabar S.
106                                                                                                                   Endress+Hauser
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
Index
Symbols                                                                                         Level measurement, installation . . . . . . . . . . . . . . . . . . . . 14
"Level" Quick Setup menu . . . . . . . . . . . . . . . . . . . . . . . . . 70                   Level measurement, preparatory steps . . . . . . . . . . . . . . 65
"Pressure" Quick Setup menu . . . . . . . . . . . . . . . . . . . . . . 73                      Level measurement, Quick Setup menu . . . . . . . . . . . . . . 70
                                                                                                Locking operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
A
Arbeitssicherheit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6         M
Assignment of Transducer Blocks (CHANNEL) . . . . . . . 38                                      Measuring arrangement for differential pressure measure-
                                                                                                ment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
B                                                                                               Measuring arrangement for flow measurement. . . . . . . 12
Bestimmungsgemäße Verwendung . . . . . . . . . . . . . . . . . . 6                              Measuring arrangement for level measurement . . . . . . 14
Betriebssicherheit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6          Menu structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Block configuration, delivery status . . . . . . . . . . . . . . . . 37                         Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Block model, Deltabar S . . . . . . . . . . . . . . . . . . . . . . . . . . 35
                                                                                                N
C                                                                                               Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Cable specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27            Network configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
CHANNEL-Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38                    Number of devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Current consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
                                                                                                O
D                                                                                               Onsite display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Device addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .            35   Operating elements, function . . . . . . . . . . . . . . . . . . 31–32
Device identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . .            35   Operating elements, position. . . . . . . . . . . . . . . . . . . . . . . 31
Diaphragm seals, installation instructions . . . . . . . . . . .                           19   Overvoltage protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Diaphragm seals, vacuum application. . . . . . . . . . . . . . .                           19
Differential pressure measurement. . . . . . . . . . . . . . . . .                         72   P
Differential pressure measurement, installation. . . . . .                                 17   Pipe mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Differential pressure measurement, preparatory steps                                       72   Position adjustment, FF configuration program . . . . . . . 60
Differential pressure measurement, Quick Setup menu                                        73   Position adjustment, FieldCare . . . . . . . . . . . . . . . . . . . . . 60
Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   29   Position adjustment, onsite . . . . . . . . . . . . . . . . . . . . . . . . 31
                                                                                                Produktsicherheit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
E
Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26              Q
Error messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88            Quick Setup menu flow (FieldCare) . . . . . . . . . . . . . . . . . 64
F                                                                                               R
Factory setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .        54   Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Flow measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .               63   Repair of Ex-certified devices. . . . . . . . . . . . . . . . . . . . . 105
Flow measurement, installation . . . . . . . . . . . . . . . . . . .                       12   Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Flow measurement, preparatory steps . . . . . . . . . . . . . .                            62   Returning devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Flow measurement, Quick Setup menu . . . . . . . . . . . . .                               64   Rotating the housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
FOUNDATION Fieldbus system architecture . . . . . . . . .                                  33
                                                                                                S
G                                                                                               Scaling OUT parameter. . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Grounding. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28         Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
                                                                                                Selecting the language . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
H                                                                                               Selecting the measuring mode . . . . . . . . . . . . . . . . . . . . . 59
HistoROM/M-DAT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49                   Separate housing, assemble and mount. . . . . . . . . . . . . . 24
                                                                                                Shielding. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
I                                                                                               Sicherheitshinweise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Incoming acceptance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11                Simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Index tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40         Software history . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
                                                                                                Spare Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
K                                                                                               Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Keys, onsite, function . . . . . . . . . . . . . . . . . . . . . . . . . 31–32                  Supply voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Keys, position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
                                                                                                T
L                                                                                               Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Level measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Endress+Hauser                                                                                                                                                                         107
 Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
U
Unlocking operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
W
Wall mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88