Final Report T60 UNIT 2B

This document summarizes the results of a test report on a GE Multilin UR T60 relay unit 2B. The test was conducted on September 12, 2020 and tested the current metering ratios for various circuits and the phase time overcurrent protection settings for different injected fault currents. The test results showed the relay measurements were within acceptable accuracy ranges.

Uploaded by

Mr Ilcham
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
93 views10 pages

Final Report T60 UNIT 2B

This document summarizes the results of a test report on a GE Multilin UR T60 relay unit 2B. The test was conducted on September 12, 2020 and tested the current metering ratios for various circuits and the phase time overcurrent protection settings for different injected fault currents. The test results showed the relay measurements were within acceptable accuracy ranges.

Uploaded by

Mr Ilcham
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 10

TEST REPORT

RELAY T60 UNIT 2B

PROJECT : RETROFIT GENERATOR & PROTEKSI MAIN TRAFO UNIT 1 & 2

Contarct No. : 070/BDSN-GAE/VII/2020

Date : 12 SEPT 2020

Relay : GE MULTILIN UR T60

Type : TRANSFORMER MANAGEMENT RELAY

Order Code : T60-W00-HEH-F8L-H6W-M8N-P6X-U7H-WRH

Serial Number : ABHC20000835

PT GUNA ELEKTRO PT. PJBS ASAHAN 1


Customer : PT BDSN

PANEL : 12 SEPT 2020


MANUFACTURER : GE MULTILIN UR T60
TYPE OF RELAY : TRANSFORMER MANAGEMENT RELAY
SERIAL NUMBER : ABHC20000835

TEST EQUIPMENT : Megger SMRT46

I. CURRENT METERING
Ratio CT Phase = 750 : 1 A Source : SIDE 275kV
Secondary Measured
Expected
Metering test Injected Accuracy (%) Remarks
Current (Amp)
Current(A) Current(A) Phase A Phase B Phase C
0.25 187.5 186,97 185,23 186.79 0.62% Ok
0.5 375 375 374 375 0.09% Ok
Phase Current
0.75 562.5 562 561 562 0.15% Ok
1 750 749 750 751 0.00% Ok

Ratio CT Phase = 5000 : 1 A (SUM M1+M5) Source : SIDE 13.8kV


Secondary Measured
Expected
Metering test Injected Accuracy (%) Remarks
Current (Amp)
Current(A) Current(A) Phase A Phase B Phase C
0.25 1250 1249 1250 1249 0.05% Ok
0.5 2500 2500 2498 2489 0.17% Ok
Phase Current
0.75 3750 3750 3749 3751 0.00% Ok
1 5000 4982 4982 4987 0.33% Ok

Ratio CT Phase = 5000 : 1 A Source : SIDE GEN


Secondary Measured
Expected
Metering test Injected Accuracy (%) Remarks
Current (Amp)
Current(A) Current(A) Phase A Phase B Phase C
0.25 1250 1250 1249 1251 0.00% Ok
0.5 2500 2500 2492 2498 0.13% Ok
Phase Current
0.75 3750 3750 3749 3751 0.00% Ok
1 5000 5001 4999 4981 0.13% Ok

Ratio CT Phase = 5000 : 1 A Source : AUX TRAFO


Secondary Measured
Expected
Injected
Metering test Current (Amp) Accuracy (%) Remarks

Current(A) Current(A) Phase A Phase B Phase C


0.25 1250 1250 1249 1251 0.00% Ok
0.5 2500 2501 2505 2498 0.05% Ok
Phase Current
0.75 3750 3749 3750 3751 0.00% Ok
1 5000 4998 4998 4998 0.04% Ok

711556084.xlsx/Current Metering Page 2 of 10


Jalan Arjuna Utara No.50 Jakarta Barat 11510
Jakarta Indonesia
Telp.(021) 5655010-5655020
Fax. (021) 5654630-5655030
Website : GAE.co.id

#REF!

PANEL : 12 SEPT 2020


MANUFACTURER : GE MULTILIN UR T60
TYPE OF RELAY : TRANSFORMER MANAGEMENT RELAY
SERIAL NUMBER : ABHC20000835

TEST EQUIPMENT : FREJA 306

I. Phase TOC Unit (51 P)

51 P Pickup setting : 0.75 pu CT Pri : 4000 A


51 P Curva type : IEEE EXT INV CT Sec ; 5A
Time Dial setting : 2.65

Minimum pickup : 3.775 A

Inject Current Fault Expected Phase


(A) (%) Trip Time (ms) Trip Time (ms)
4.5 120% 0.6359
5.625 150% 0.3895
7.5 200% 25.2330 25.174
12 500% 3.4360 3.453
11.25 300% 0.1833
13.125 350% 0.1693
30 800% 0.1352

#REF!

Tested By #REF! Approved By


Guna Elektro #REF! #REF!

#REF! #REF! #REF!

711556084.xlsx/PTOC Page 3 of 10
Jalan Arjuna Utara No.50 Jakarta Barat 11510
Jakarta Indonesia
Telp.(021) 5655010-5655020
Fax. (021) 5654630-5655030
Website : GAE.co.id

#REF!

PANEL : 12 SEPT 2020


MANUFACTURER : GE MULTILIN UR T60
TYPE OF RELAY : TRANSFORMER MANAGEMENT RELAY
SERIAL NUMBER : ABHC20000835

TEST EQUIPMENT : FREJA 300

I. Phase TOC Voltage Restrained Unit (51 P)

51 P Pickup setting : 0.9 pu CT Pri : #REF! A


51 P Curva type : IAC Short Inverse CT Sec ; 5A
Time Dial setting : 16
V inj : 83%

Inject Current Fault Expected Phase


(A) (%) Trip Time (ms) Trip Time (ms)
5.4 120% 3.8397 2.478
6.75 150% 2.3516 1.681
9 200% 1.5451 1.293
11.25 250% 1.2514 1.106
13.5 300% 1.1068 1.007
15.75 350% 1.0223 0.947
18 400% 0.9673 0.905
22.5 500% 0.9001 0.859
27 600% 0.8607 0.821
31.5 700% 0.8348 0.814
36 800% 0.8164 0.778

#REF!

Tested By #REF! Approved By


Guna Elektro #REF! #REF!

#REF! #REF! #REF!

711556084.xlsx/PTOC VREST Page 4 of 10


Ground Time Overcurrent Functions (ANSI Devices 51G)

Phase Trip Time (ms)

10
Trip time (second)

0.1
100% 1000%
I fault

711556084.xlsx/PTOC VREST Page 5 of 10


Customer : PT BDSN

PANEL : 12 SEPT 2020


MANUFACTURER : GE MULTILIN UR T60
TYPE OF RELAY : TRANSFORMER MANAGEMENT RELAY
SERIAL NUMBER : ABHC20000835

TEST EQUIPMENT : Megger SMRT46

1. OVERALL DIFERENSIAL
SRC 1 SRC 2
Set Pickup : 0.34 pu 275kV 13,8 kV
Slope 1 : 30 % CT Pri : 750 5000 A
Break 1 : 1 pu CT Sec : 1 1A
Slope 2 : 90 % ramp side 275kV
Break 1 : 8 pu Source 1 side 275kV
Source 2 side 13,8 kV

1.40

1.27
1.20

1.00

0.80

0.60
0.56

0.40
0.29
0.20
0.11
0.00
0.11 0.45 0.75 1.49

Column E

CURRENT INJECTION Id Ir
Slope
I HV (275kV) I LV (13,8kV)
A pu A pu pu pu %
0.11 0.11 0.00 0.00 0.11 0.11 pkp
0.16 0.16 0.15 0.45 0.29 0.45 64.31%
0.19 0.19 0.25 0.75 0.56 0.75 74.57%
0.22 0.22 0.50 1.49 1.27 1.49 85.28%

Pickup Value 275kV 0.11 A


Pickup Value 13,8 kV 0.32 A
Trip Time
Injected Current (A) Target (ms) Error (%)
(ms)
0,2 (LV) 50 36 0.28
0,4 (LV) 50 37 0.26

TRIP TARGET
CB01_1 275kV CB01_2 275kV INTERTRIPINTERTRIP BI CB02_1 CB02_1 STOP GEN START CF
√ √ √ √ √ √
Customer : PT BDSN

PANEL : 12 SEPT 2020


MANUFACTURER : GE MULTILIN UR T60
TYPE OF RELAY : TRANSFORMER MANAGEMENT RELAY
SERIAL NUMBER : ABHC20000835

TEST EQUIPMENT : Megger SMRT46

2. PHASE OVERCURRENT (51P)_SIDE 275kV

51 Pickup setting 0.4 pu CT Pri 750 A


51 Time Delay 0.5 s CT Sec 1A

Pickup Value 0.401 A


Dropout 0.389 A

Inject Current
Target (s) Actual (s) Error (%)
(A)
2 0.5 0.516 0.032
3 0.5 0.52 0.04

TEST FUNCTION : Injection Sekunder ABC signal Source Side 275kV


TRIP TARGET
CB01_1 275kV CB01_2 275kV INTERTRIP INTERTRIP BI CB02_1 CB02_1 STOP GEN START CF
√ √ √ √ √ √

3. PHASE OVERCURRENT (51P)_SIDE 275kV_MT OVERLOAD

51 Pickup setting 0.31 pu CT Pri 750 A


51 Time Delay 9s CT Sec 1A

Pickup Value 0.311 A


Dropout 0.302 A

Inject Current
Target (s) Actual (s) Error (%)
(A)
2 9 9.01 0.0011
3 9 9.02 0.0022

TEST FUNCTION : Injection Sekunder ABC signal Source Side 275kV


TRIP TARGET
CB01_1 275kV CB01_2 275kV INTERTRIP INTERTRIP BI CB02_1 CB02_1 STOP GEN START CF
√ √ √ √ √ √

711556084.xlsx/51P Page 7 of 10
Customer : PT BDSN

PANEL : 12 SEPT 2020


MANUFACTURER : GE MULTILIN UR T60
TYPE OF RELAY : TRANSFORMER MANAGEMENT RELAY
SERIAL NUMBER : ABHC20000835

TEST EQUIPMENT : Megger SMRT46

4. PHASE OVERCURRENT (51P)_SIDE GEN

51 Pickup setting : 1.1 pu CT Pri 5000 A


51 Time Delay : 1s CT Sec 1A

Pickup Value 1.101 A


Dropout 1.068 A

Inject Current
Target (s) Actual (s) Error (%)
(A)
2 1 1.009 0.0090
3 1 1.03 0.0300

TEST FUNCTION : Injection Sekunder ABC signal Source Side Gen


TRIP TARGET
CB01_1 275kV CB01_2 275kV INTERTRIP INTERTRIP BI CB02_1 CB02_1 STOP GEN START CF
√ √ √ √ √ √

5.. GROUND OVERCURRENT (51G)_SIDE 275kV

51 Pickup setting : 1.5 pu CT Pri 150 A


51 Time Delay : 0.75 s CT Sec 1A

Pickup Value 1.504 A


Dropout 1.462 A

Inject Current
Target (s) Actual (s) Error (%)
(A)
2 0.75 0.788 0.051
3 0.75 0.79 0.053

TEST FUNCTION :
TRIP TARGET
CB01_1 275kV CB01_2 275kV INTERTRIP INTERTRIP BI CB02_1 CB02_1 STOP GEN START CF
√ √ √ √ √ √

711556084.xlsx/51P (2) Page 8 of 10


Customer : PT BDSN

PANEL : 12 SEPT 2020


MANUFACTURER : GE MULTILIN UR T60
TYPE OF RELAY : TRANSFORMER MANAGEMENT RELAY
SERIAL NUMBER : ABHC20000835

TEST EQUIPMENTMegger
: SMRT46

6. GROUND OVERCURRENT (51G)_SIDE 275kV

51 Pickup setting 1 pu CT Pri 150 A


51 Time Delay 2s CT Sec 1A

Pickup Value 1.003 A


Dropout 0.984 A

Inject Current
Target (s) Actual (s) Error (%)
(A)
2 2 2.044 0.022
3 2 2.036 0.018

TEST FUNCTION: Injection Sekunder AN signal Source Side 275kV


TRIP TARGET
CB01_1 275kV CB01_2 275kV INTERTRIP INTERTRIP BI CB02_1 CB02_1 STOP GEN START CF
√ √ √ √ √ √

7. OVER FLUXING (24)_STAGE_1

24 Pickup setting 1.21 pu VT Pri 275 kV


24 Time Delay 5s VT Sec 110 V

Pickup Value 133.1 Vp-p

Inject Voltage
Target (s) Actual (s) Error (%)
(Vp-p)
135 5 5.148 0.03
140 5 5.028 0.01

TEST FUNCTION: Injection Sekunder AN signal Source Side Neutral


TRIP TARGET : no Action to Matrik trip

711556084.xlsx/51G Page 9 of 10
Customer : PT BDSN

PANEL : 12 SEPT 2020


MANUFACTURER : GE MULTILIN UR T60
TYPE OF RELAY : TRANSFORMER MANAGEMENT RELAY
SERIAL NUMBER : ABHC20000835

TEST EQUIPMENT :Megger SMRT46

8. OVER FLUXING (24)_STAGE_2

24 Pickup setting 1.32 pu VT Pri 275 kV


24 Time Delay 3s VT Sec 110 V

Pickup Value 145.10 Vpp

Inject Voltage
Target (s) Actual (s) Error (%)
(Vp-p)
147 3 3.107 0.04
150 3 3.076 0.03

TEST FUNCTION :
TRIP TARGET
CB01_1 275kV CB01_2 275kV INTERTRIP INTERTRIP BI CB02_1 CB02_1 STOP GEN START CF
√ √ √ √ √ √

9. PHASE UV

27X Pickup setting 0.8 pu VT Pri 13.8 kV


27X Time Delay 1s VT Sec 110 V
SOURCE : 13,8 kV
Pickup Value 50.89 Vp-N

Inject Voltage
Target (s) Actual (s) Error (%)
(Vp-N)
50 1 1.023 0.023
40 1 1.023 0.023

TEST FUNCTION : Injection volt ABC source 13,8kV


TRIP TARGET : Alarm, Block UV_OCR

711556084.xlsx/24 Page 10 of 10