MV distribution
metalclad switchgear withdrawable circuit-breaker 1 to 17.5 kV
Operation guide
AAG0D112F1-A0
AAG0D112F1-A0
General contents
General description Incomer and feeder IF11 & IF12 Riser R11 & R12 Coupler C11 & C12 Metering MT11 Incomer / feeder without VT Incomer / feeder with withdrawable VT Coupler / Riser cubicles General cubicle identification Earthing switch operation & CB plug-in interlock Interlocks of the withdrawable voltage transformer Symbols of earthing switch List of accessories supplied with the switchboard Access to interior of the cubicle Access possibilities to the cubicle Access to the MV cable connection compartment Access to the busbar chamber Disengaging the circuit breaker (removable part) Engaging the circuit breaker (removable part) Disengaging the withdrawable voltage transformer Engaging the withdrawable voltage transformer How to close the earthing switch How to open the earthing switch Locking by padlocks Interlocking by locks Installation & operation recommendation Test arrangements Preventive maintenance
4 4 4 5 5 6 7 8 9 9 10 10 11 12 12 13 14 15 16 18 19 20 21 22 23 24 25 26
AAG0D112F1-A0
General description
Typical cubicles
Incomer & feeder IF11 & IF12
Front
Riser R11 & R12
Front
Switchgear type
Ratings Dimensions and weight
height (H) width (W) depth (D) weight mm mm mm kg
IF11
630 A - 1250 A
2120 750 2044 750
IF12
2500 A
2120 950 2170 900
R11
1250 A
2120 750 2044 600
R12
2500 A
2120 950 2044 720
N.B.: the type of the current transformer could change according to the customers requirement, however the overall dimensions are the same.
AAG0D112F1-A0
General description
Typical cubicles
Coupler C11 & C12
Front
Metering MT11
Front
Switchgear type
Ratings Dimensions and weight
height (H) width (W) depth (D) weight mm mm mm kg
C11
1250 A
2120 750 2044 650
C12
2500 A
2120 950 2044 800
MT11
630 A - 1250 A - 2500 A
2120 750 2044 550
N.B.: the type of the current transformer could change according to the customers requirement, however the overall dimensions are the same.
AAG0D112F1-A0
General description
Incomer / feeder without VT
Front panel
A: LV compartment access door B: removable part compartment door C: voltage indicators D: earthing switch operating and interlocking plate E: Sepam protection control and monitoring
C D A E
Left-hand view
1: low voltage compartment 2: busbar compartment 3: removable part compartment 4: medium voltage cable compartment F: removable part (Evolis / LF circuit breakers) G: medium voltage cable connection point H: earthing switch I: earthing switch operating mechanism K: block CT L: low voltage cable routing duct
Front
L 2
H G
K 4
AAG0D112F1-A0
General description
Incomer / feeder with withdrawable VT
Front panel
A: LV compartment access door B: removable part compartment door C: voltage indicators D: earthing switch operating and interlocking plate E: Sepam protection control and monitoring
C D A E
Left-hand view
1: low voltage compartment 2: busbar compartment 3: removable part compartment 4: withdrawable VT compartment 5: medium voltage cable compartment F: removable part (Evolis / LF circuit breakers) G: medium voltage cable connection point H: earthing switch I: earthing switch operating mechanism K: block CT L: low voltage cable routing duct M: VT
Front
L 2 4 1 M
H G
K 5
AAG0D112F1-A0
General description
Coupler / Riser cubicles
Front panel
A: LV compartment access door B: removable part compartment door C: Sepam protection control and monitoring
A C A
Coupler
Left-hand view
1: low voltage compartment 2: busbar compartment 3: removable part compartment D: removable part (Evolis / LF circuit breaker) E: low voltage cable routing duct
Front
E 2 1
Riser
Left-hand view
1: low voltage compartment 2: busbar compartment L: low voltage cable routing duct M: LPCT (low power current transducer)
Front
E 1 2
AAG0D112F1-A0
General description
General cubicle identification
A: cubicle name B: manufacturers plate C: rating plate
Earthing switch operation and CB plug-in interlock
4: earthing switch position selector 5: hole for operating handle E: voltage indicator H: plug-in interlock L: mechanical indication earthswitch position M: provision for plug-in prevention interlock N: provision for earthing switch locks
o
4
L1 L2 L3
E 4
I
5
M 5 H
AAG0D112F1-A0
General description
Interlocks of the withdrawable voltage transformer
1: VT's locked in draw-out position: door in open position, shutters locked in close position. 2: VT's locked in draw-out position: door in close position, shutters in free position. 3: VT's transfer free: shutters locked in open position, door locked in close position. 4: VT's locked in draw-in position: shutters locked in open position, door locked in close position.
Symbols of earthing switch
Operating position
Earthing switch open position
Earthing switch open position mechanical indicator
Earthing switch closed position
Earthing switch closed position mechanical indicator
Position lockable with padlock
10
AAG0D112F1-A0
General description
List of accessories supplied with the switchboard
s 1 operating handle, s Busbar reinforcement insulator (right end of the switchboard), s 1 busbar earthing carriage (optional).
Handle
Insulator (refer to the installation guide for the assembly of the insulator
Glosssary of abbreviations
LV: low voltage MV: meduim voltage Evolis: range of vacuum circuit breakers LF: range of SF6 circuit breakers VT: voltage transformer CT: current transformer
AAG0D112F1-A0
11
Access to interior of the cubicle
Access possibilities to the cubicle
1: access to the cable terminations 2: access to the busbar chamber 3: access to the removable part 4: access to the low voltage compartment
Front
1 3
12
AAG0D112F1-A0
Access to interior of the cubicle
Access to the MV cable connection compartment
To carry out certain tests, access to the cable compartment is required. The following procedures describe this access: 1: close the earthing switch (see section named How to close the earthing switch), 2: remove the rear panel 13 screws.
N.B.: no intelocking between the two operations.
Caution: make sure that the earthing switch is closed before removing the rear panel.
Fr
on
AAG0D112F1-A0
The rear panel 13 screws
13
Access to interior of the cubicle
Access to the busbar chamber
1: make sure that the circuit breaker is disconnected, 2: it is recommended to earth the main busbar using the earthing truck.
A
To access the busbar from the top (A)
A1: remove the top cover
Front
To access the busbar from the front (B)
B1: open removable part door, B2: remove circuit breaker, B3: enter the cubicle, B4: remove the front partitioning of the busbar chamber.
In case of no potential transformers, access from the back of the cubicle is also available (C)
C1: remove the back panel
Front
Caution: make sure that the busbar is earthed before accessing the busbar chamber.
14
AAG0D112F1-A0
Operating instructions
Disengaging the circuit breaker (removable part)
1: open the cubicle door by pulling out the door handle and turn it 90 anti-clockwise. 4: disengage the circuit breaker by pulling it towards you up to the stop. The circuit breaker, now, is in the disconnected position.
Pull to test position
2: open the circuit breaker by pressing the mechanical OFF button O .
5: to remove the circuit breaker out of the cubicle: 5-A: move the arm to position 3 ,
3: move the arm to position 2 .
5-B: unplug the LV auxiliaries lead & park the plug on the circuit breaker front,
5-C: extract the circuit breaker outside the cubicle. To proceed with no load operation test: 5-C-1: steps 1 + 2 + 3 + 4, 5-C-2: move the arm to position 1 .
Pull to withdrawn position
AAG0D112F1-A0
15
Operating instructions
Engaging the circuit breaker (removable part)
1: check that the earthing switch is in the opened position from the mechanical indicator. An interlocking device prevents the circuit breaker from being inserted if the earthing switch is closed. 3: push the circuit breaker into the panel until it comes up against the stop.
L1
L2
L3
I o
Push to test position
2: move the arm to position 3 .
4: plug the LV auxiliaries, otherwise the circuit breaker will not be inserted.
5: move the arm to position 2 .
16
AAG0D112F1-A0
Operating instructions
6: engage the circuit breaker by pushing it inwards.
Push to engaged position
7: move the arm to position 1 to block it in the engaged position. The circuit breaker can then be closed by pressing the mechanical button I (provided the operating mechanism is loaded).
9: close the circuit breaker by pressing the mechcanical ON button I .
8: change the operating mechanism.
10: close the MV door with the door handle.
AAG0D112F1-A0
17
Operating instructions
Cubicle with withdrawable voltage transformer
Door
Control plate arm
Carriage handle
Shutter handle
Disengaging the voltage transformer
1: move the control plate arm to the right to liberate the shaft which pull the carriage.
ag ed En ga ge d Fr ee to m ov e
3: rotate the carriage handle in counter clockwise direction to close the shutter and enable the door opening.
Di se ng
2: while holding the control plate arm in the right direction, draw out the carriage handle till the stop. The control plate arm will move automatically to the disengaged position.
4: open the door.
Dis en
En ga
Fre e
ge
ga
en
ge
Dis
En
Dis en En ga
18
Fr ee
AAG0D112F1-A0
Fre
e to
ga
mo
ve
Operating instructions
Engaging the voltage transformer
1: close the door.
2: rotate the carriage handle clockwise direction to open the shutter and lock the door.
4: while holding the control plate arm in the right direction, push the voltage transformer inward till the stop. The control plate arm will move automatically to the engaged position.
Dis en
En ga
ag ed En ga ge d Fr ee to m ov e
3: move the control plate arm to the right to liberate the shaft which pushes the carriage.
Di se ng
Dis en
En ga
AAG0D112F1-A0
Fre e
Fr
ee
en ga ge En d ga ge d Fre e to mo ve
Dis
19
Operating instructions
On an incomer / feeder cubicle
How to close the earthing switch (yellow background front plate) Initial state:
Before proceeding, ensure the following:
s The removable part in the isolated position or removed from the cubicle.Check that the voltage indication lamps are off. s The locks, if any, should be set to enable operation.
Set the selector 4 to turning it to the right.
by pulling it out and
L1 L2 L3
I o
4 4
Insert the crank handle into the operation shaft 5 and turn the handle clockwise until the position indicator L changes state. Closure is accompanied by a distinctive sound.
L1
L2
L3
I o
4
Set the selector 4 to
by pulling it out and
L1 L2 L3
then turning it. The earthing switch is now in the earthed position. The MV cable connections are now short-circuit and earthed.
I o
4
The earthing switch is now in the earthed position. The MV cable connections are now short-circuit and earthed.
L1
L2
L3
I
4
20
AAG0D112F1-A0
Operating instructions
On an incomer / feeder cubicle
How to open the earthing switch (yellow background front plate) Initial state:
Before proceeding, ensure the following:
s The earthing is closed. s The locks, if any, should be set to enable operation.
Set the selector 4 to turning it.
by pulling it out and
L1 L2 L3
I
44
Insert the crank handle into the operation shaft 5 and turn the handle clockwise until the position indicator L changes state. Closure is accompanied by a distinctive sound.
L1
L2
L3
I o
4
Set the selector 4 to o then turning it.
by pulling it out and
L1 L2 L3
I o
4 4
AAG0D112F1-A0
21
Operating instructions
Locking by padlocks
To prevent plugging-in of the removable part
Pull out the lever H and lift the padlock in the oblong hole.
L1
L2
L3
I o
4
Locking the earthing switch in the open or closed position
L1
L2
L3
L1
L2
L3
I o
4
I
4
Earthing switch open: fit 1 to 3 locks to the selector 4 to prevent closing.
Earthing switch closed: fit 1 to 3 locks to prevent opening. This also prevents racking in of the closing of the withdrawable part.
N.B.: all locks are 6 - 8 mm diameter padlocks
To prevent opening of the bushing shutters lock
On the bushing shutter mechanism when shutters are closed. The bushing shutter mechanism is inside the cubicle on the right hand side.
22
AAG0D112F1-A0
Operating instructions
Interlocking by locks (option)
s (2 O), (2 C) or (1 O & 1 C): on the earthing switch s 1 lock in plugged-in position (on earthing switch)
Interlocking the earthing switch
The key is released only if the earthing switch is locked.
L1
L2
L3
I
4
Locking the removable part in the drawn-out position
s earthing switch closed, s pull-out the level H and turn the key lock at B and remove the key.
L1
L2
L3
I
4
B H
AAG0D112F1-A0
23
Installation & operation recommendation
Long term switchgear performance
Long term switchgear performance in a MV substation depends on 3 main factors:
s The need of proper installation of the MV cables:
the new cold slip-onand retractable technologies offer ease of installation. Their design enables operation in polluted environments with harsh atmospheres.
s The influence of the relative humidity factor:
the installation of heating resistors is essential in climates with high humidity and large temperature differences.
s Ventilation control:
cubicle ventilation must not be impeded. This is to ensure air circulation within the switchboard cubicles.
Regular operation
We strongly recommend that you carry out at regular intervals (at least every two years) a few operating cycles on the switching devices. Outside normal operating (between -5 C and +40 C, absence of dust, corrosive atmosphere, etc.) we recommend that you contact our Schneider Elecrtic Service Centre in order to examine the measures to be taken to ensure proper installation and operation.
Schneider Electric services centres
Our service centre is at your disposal at all times:
s to conduct an installation diagnosis, s to suggest the appropriate maintenance operations, s to offer you maintenance contacts, s to suggest adaptations.
24
AAG0D112F1-A0
Test arrangements
Voltage presence on MV cables
As soon as the cables are live, the lamps of the voltage indicator should light.
L1 L2 MM L3
Checking phase concordance
s phases are in sequence: lamp does not light
UF A
L1 L2 L3 L1
UF B
L2 L3
(no volt),
s phases are not in sequence: lamp lights (volt).
MV cable tests
Injecting voltage into MV cable heads Outgoing cables (without VT)
L1 L2 MM L3
L1
L2
L3
I
5
Test conditions:
s earthing switch open s cables connected to injector tools.
Verify the absence of voltage. The voltage indicator lamps are off. Close the earthing switch (see chapter how to close the earthing switch). We recommend you lock it in this position (see chapter locking with padlocks).
The rear panel 13 screws
s remove the panel (13 screws). s connect the voltage injector circuit
to the cable lugs.
L1
L2
L3
I
5
At the end of the tests
s close the earthing switch, s remove the accessories.
Open the earthing switch (see chapter how to open the earthing switch) then carry out the tests.
AAG0D112F1-A0
25
Preventive maintenance
Trouble shooting table for drawout circuit breaker
Symptoms
The circuit breaker on its trolley was just inserted into the cubicle. The lever is in the circuit breaker extraxction authorization and removal position (position no. 3) The selector cannot be turned to the rack-in authorised position (position no. 2). The circuit breaker is connected (position no. 1). The circuit breaker is closed: the lever cannot be turned to the rack-out authorized position no.2
Faulty mechanisms
The low voltage plug.
Probable causes and solutions
Check that the low voltage plug is connected.
The notching pins of the circuit breaker truck.
Make sure of using the right CB trolley.
Mismatch
The automatic opening function of the circuit breaker via the selector.
Make sure of pushing and holding the CB mechanical off button while moving the level from 1 to 2.
26
AAG0D112F1-A0
Notes
AAG0D112F1-A0
27
68, Tayaran st., Nasr City, Cairo, Egypt. P.O. Box 2658 El Horreya. Tel : +202 40 10 119 Fax: +202 26 18 908 http://www.schneider.com.eg SEE 67065 / E
Design & production: Communication - SEE Printing: Trust Advertising co.
28
AAG0D112F1-A0
AAG0D112F1-A0
Schneider Electric
NE Africa & Egypt Head Office
Customer Support Center (CSC) Tel: (202) 40 10 899 Fax: (202) 26 20 473 customer.support@eg.schneider-electric.com
As standard specifications and designs change from time to time, please ask for confirmation of the information given in this publication.