Aci-Punching

This document contains calculations for punching shear at a slab-column connection according to ACI 318-02. Input data includes material properties, concrete dimensions, column case classification, and punching loads. Precalculations determine properties of the critical section. Calculations compare applied shear stresses to allowable values, finding the section is safe without shear reinforcement. The document also provides calculations for required shear reinforcement if needed.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
44 views5 pages

Aci-Punching

This document contains calculations for punching shear at a slab-column connection according to ACI 318-02. Input data includes material properties, concrete dimensions, column case classification, and punching loads. Precalculations determine properties of the critical section. Calculations compare applied shear stresses to allowable values, finding the section is safe without shear reinforcement. The document also provides calculations for required shear reinforcement if needed.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 5

Design calculation sheet

(ACI-PUNCHING-02_V-0.0)

Project no.: Date: Sheet no.: of Computed by:

Subject:
Checked by:

Approved by:

Punching Shear at Slab-Column Connections (ACI318-02)


INPUT DATA :
1-Materials :
fc = 28 MPa (Concrete Cylinderical Compressive Strength)
wc = 2400 kg/m3 (Concrete unit weight = 2400 kg/m3 for normal weight concrete)
Ec = 24870 MPa (Concrete Young's Modulus)
fyv = 420 MPa (Yield Strength of Stirrups Reinforcement)
Es = 200000 MPa (Steel Reinforcement Young's Modulus)
2-Concrete Dimensions :
b= 250 mm (Column Short Side)
t= 600 mm (Column Long Side)
St = 250 mm (Slab Thickness)
C= 40 mm (Cover To C.G of Slab Reinf.)
d= 210 mm (Slab Depth)

Mu1
Mu2 Mu2
Mu2
Mu1 Mu1 Mu2

Mu1

3-Column Case :
Column Case : B2
boUSER= N.A mm (User Defined Punching Perimeter; Only for columns not matching any of the above cases otherwise type"N.A")
Ee 0 mm -
- - -
4-Punching Loads :
Col ID.: C1 Col No.: 12
Pu= 355 kN (Ultimate Column Punching Load)
Mu1= -60 kN.m (Unbalanced Moment Between a Slab and a Column about the Column's Weak Inertia)
Mu2= 60 kN.m (Unbalanced Moment Between a Slab and a Column about the Column's Strong Inertia)
(For Floors Ultimate Uniform Load Over The Slab)
Wsu= 19 kN/m2
(For Foundation Ultimate Uniform Stress Beneath Foundation without Direct Loads (Net Contact Stress))
Design calculation sheet
(ACI-PUNCHING-02_V-0.0)

Project no.: 0 Date: 0 Sheet no.: 1 of 0 Computed by: 0

Subject:
Checked by: 0
0
Approved by: 0

PRECALCULATIONS:
1-Properties of the Critical Section for Punching Shear :
bo = 1520 mm (Perimeter of Critical Section For Punching)
Ac = 319200 mm2 (Area Of Critical Section)
βc = 2.4 (Ratio of Long Side to Short Side of The Column)
αc = 30 (Factor For Columnn Location)
a- Properties for Section Resisting Mu1 :
b1 = 355 mm (Length Of Critical Section Side Parallel To Mu1)
b2 = 810 mm (Length Of Critical Section Side Parallel To Mu2)
J/c = 55687538.7 mm3 (Modulus Of Critical Section Resisting Mu1)
b- Properties for Section Resisting Mu2 :
b1 = 810 mm (Length Of Critical Section Side Parallel To Mu2)
b2 = 355 mm (Length Of Critical Section Side Parallel To Mu1)
J/c = 84892500 mm3 (Modulus Of Critical Section Resisting Mu2)
2-Unbalanced Moment Transfer Factors :
a- Transfer Factors for Mu1 : b- Transfer Factors for Mu2 :
γF = 0.694 (Flexure Transfer Factor) γF = 0.498 (Flexure Transfer Factor)
γV = 0.306 (Shear Transfer Factor) γV = 0.502 (Shear Transfer Factor)

CALCULATIONS:
1-Applied Stresses (VU):
VPU = 1.095 MPa
VMU1 = -0.330 MPa VU = VPU + VMU1 + VMU2 = 1.120 MPa
VMU2 = 0.355 MPa
2-Allowable Stresses (Vn):
VC1 = 1.61685 MPa
VC2 = 2.70957 MPa VCmin= 1.6168 MPa
VC3 = 1.76383 MPa
Vn1 = Φ Vcmin =……..= 1.213 MPa (Max. Allowable Shear Strength without Shear Reinf.)
Vn2 = Φ (0.50 X √fc) = 1.984 MPa (Max. Allowable Shear Strength with Shear Reinf.)
Vn1 = Φ (0.60 X √fc) = 2.381 MPa (Max. Allowable Shear Strength with Shear Heads)

Section Is Safe and No Need for Shear Reinf.


Design calculation sheet
(ACI-PUNCHING-02_V-0.0)

Project no.: 0 Date: 0 Sheet no.: 2 of 0 Computed by: 0

Subject:
Checked by: 0
0
Approved by: 0

CALCULATIONS (Cont.):
3-Design for Shear Reinf.:
a- Required Shear Reinf. (Diameter & Spacing) :
S= 100 mm (Stirrups Spacing) -
n= 7 (No. of Stirrup Legs)
AVmin = 120.635 mm2 (Min. Shear Reinf. on The All Sides of The Column)
VC = 0.88192 MPa (Shear Stress Carried By Concrete)
VS = VU/Φ - VC = 0.611 MPa (Shear Stress Carried By Reinf.)
AVrep = 221.152 mm2 (Required Shear Reinf. on The All Sides of The Column)
N= 3 (No. of Column Sheared Sides)

b- Safe Perimeter Out Side Shear Reinf. :

Column Case Is : B2
K1 = 100 mm -
K2V = 310 mm
K2h = 205 mm
Φ VC = 0.66144 MPa (Shear Stress Carried By Concrete)
bO\ = 2436.88 mm (Punching Primeter Outside Shear Reinf.)
Ahi = mm
A i = 858.442 mm
Avi = mm

c- Length Required To Be Covered By Shear Reinf.:

Lsh = ### mm
Required Coverage Length For Shear Reinf.
Measured From d/2 From Column Face In
Lsv = ### mm Both Directions

Lsh + d/2= ### mm


Required Coverage Length For Shear Reinf.
Measured From Column Face In Both
Lsv + d/2= ### mm Directions