0 ratings0% found this document useful (0 votes) 333 views30 pagesNEC 2017 - Summary
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content,
claim it here.
Available Formats
Download as PDF or read online on Scribd
GLOSSARY
Accessible: Not permanently concealed or enclosed by building con:
of equipment can be considered accessible even if tools must be u!
equipment must be removed to gain access to it.
Accessible, readily: Capable of being reached quickly for operation or inspection
Without the use of tools or portable ladders or the need to remove obstacles.
Approved: Acceptable to the Authority Having Jurisdiction (AHJ). The AHJ wil usually
‘approve materials that are listed and labeled.
‘Arc fault; An electric current propagated through ait
Arc-Fault Circuit interrupter (AFCI): A device intended to provide fire protection by
recognizing arc characteristics and de-energizing the circuit when arcing occurs.
Authority Having Jurisdiction (AHS): The building official or persons authorized to
act on his or her behalf
Bonded, bonding: Connected to establish continuity and conductivity.
Branch circuit: The circuit conductors located between the last OCPD (breaker or
fuse) and the outlet or outlets protected by the OCPD.
* Branch circuit, general purpose: Branch circuit that supplies 2 or more
receptacles or outlets for lighting and appliances.
+ Branch circuit, individual: Branch circuit that supplies only 1 piece of equipment.
= Branch circuit, multiwire, residential: Branch circuit consisting of 2 hot
conductors having 208V or 240V potential between them and a grounded neutral
having 120V potential to each hot conductor F 19.
* Branch circuit, small appliance: Branch circuit that supplies portable house-
hold appliances in kitchens and related rooms.
Device: A piece of equipment that carries or controls electrical energy as its primary
function, such as a switch, receptacle, or circuit breaker.
Equipment grounding conductor (EGC): A wire or conductive path that limits volt-
‘age on metal surfaces and provides a path for fault currents F1/
Feeders: Conductors that supply panelboards other than service panels.
Flexibility after installation: Anticipated movement after initial installation, such a
that caused by motor vibration or equipment repositioning,
Ground, grounded: The earth, connected to earth,
Ground fault: An unintentional connection of a current-carrying conductor to equip
; ‘earth, or conductors that are not normally intended to carry current.
d or other
t=) AUP Leda
struction. A pioce
wy ©
Ground-Fault Circuit Interrupter (GFCI: A device to protect against shock hazards
by interrupting current when an imbalance of 6 millamps or more is detected.
Grounded conductor: A current-carrying conductor the
earth (a neutral).
Grounding electrode conductor (GEC): A
neutral or the equipment to a grounding «
electrode system Fs
Interrupting rating: The highest current an O
without sustaining damage.
Luminaire (formerly lighting ficture): A complate lighting unit inclucin
8 intentionally connected to
tor used to connect the se
of to a point on the grounding
ar of fuse) can interrupt
connect it to the power supply and possibly parts to protect or distribute the light
source. A lampholder, such as a porcelain socket, is nat itself a luminaire
Neutral conductor: The conductor connected to the neutral point of a system and
that is intended to carry current under normal operating conditions
Outlet: The point on a wiring system at which current is taken to supply equipment. A
box for a receptacle, luminaire (fisture), or smoke alarm is an outlet; most baxes for
switches are not outlets.
Overcurrent: Any current in excess of the rating of equipment, device, or conductor
ampacity. Overcurrents are produced by overaads, ground faults, or short circuits.
Overfusing: A fuse or breaker that has an overload rating greater than allowed for the
conductor or equipment itis protecting
Overload: Equipment drawing current in excess of the equi ment or conductor rating
and in such a manner that damage or dangerous conditions would occur if it contin-
ued for a sufficient time, Short circuits and ground faults are not overloads.
Service: The conductors and equipment providing a connection to the utility
Service drop: The overhead conductors supplied by the utility
Service equipment: The equipment at which the power conductors entering the
building can be switched off to disconnect the premises’ wiring from the utility power
source. A meter can be a part of or separate from the service equipment.
Underground conductors from the utility to the service point Fs.
direct connection of current-carrying conductors without the inter-
position of a load, resulting in high levels of current
Short Circuit Current Rating (SCCR): The amount of current that panelboards and
switchboards must be able to carry during a short circuit condition without
sustaining damage. See Interrupting rating.
S @ TABLE OF CONTENTS ¢@ GLOSSARYService drop conductors are protected by isolation; they typically have no protec-
tive outer jacket and no overload protection at their source. Utility rules may over-
fide the specifications in the code, so check with the AHJ to determine variations
from the clearances below. These clearances also apply to overhead feeders.
Vertical above Roof Fi 17 NEC
(0 <4:in-12 slope: min 8 ft. EM EXC 230.240
+3 ft. OK if roof area guarded or isolated 230,24AX5
(2 4:in-12 slope: min 3 ft. EB EXC ___230.24AX2
= Over eaves 18 in. OK for $4 ft. horizontal 6 ft. ‘of conductor [a] 230.24AX3
(0 Maintain req'd distance for 3 ft. past roof edge EXC. 230.244
+ Edge clearance above roof is not req'd where overhead
conductors attach to side of building _____________— 230.24AX4
CE Metal support structures for conductors passing over ,
roofs req bonding to neutral of service drop
reg'd = required
Vertical above Grade F1 17 NEC
1 10 ft. above final grade to lowest point of drip loop _ 230.2481
1 Area accessible only to pedestrians: 10 ft. 230.2481
CO General above grade & driveways: 12 #. Fa 230.2482
1 Above roads or parking areas subject
230.2484
to truck traffic: 18 ft.
1 Any direction < 10 ft. horizontal from swimming pool water: 22/2 ft._680.6A
Clearance from Openings & Communication Wires Ft 17 NEC
Vertical above decks & balconies: 10 ft. 230.98
__.230.9A
From side of area above decks & balconies: 3 ft.
1 Below or to sides of openable window: 3 ft. a __ 230.94
(0 Communications wire min 12 in. to paraliel power wires 800.4444
1 Communications wires above roofs same as power conductors_ 800.448
Window & door clearances apply to open conductors-not lo conductors con
ble with an overall outer jacket. Clea
ically per the local utility_ SERVICE ENTRANCE CONDUCTORS
The splice at the weatherhead from the service dro to the
building wiring is typically the “service point"-the handoff ten he cay tease
tomer. On overhead ‘systems, the conductors from the service point to the discon:
necting means are service entrance conductors. Though the utility does not have
exclusive Control of these conductors, they may still have jurisdiction over them.
Dwelling unit service conductors & feeders that carry the entire load of the service
are allowed to be sized in accordance with T14. The service must be large enough
to meet the calculated load (see p.6-7) and for a SFD must be at least 100 amps.
Service Riser 17 NEC
( Raceway size, material & bracing per utility, 90.20
CT Wiring method listed for electrical (no plumbing pipe) 110.3B & 230.43
C Listed for wet location & arranged to drain where exposed to weather 230.53
(1 Overhead raceway req's service head listed for wet locations 230.544
1 Riser req'd to have adequate strength & bracing 230.28A
(1 No couplings between structural support & weatherhead 230.28B?
TD Attachment of service drop below service head EXC 230.54C
+ OK up to 24 in. above when necessary (sidewall) 230.54CX
Only power conductors on service risers—no communication cables _230.28
1 Conductor fill in raceway 40% T21 Ch 9-T18T4
Service Entrance Conductors. 17 NEC
i Conductors & cables exposed to sunlight listed sunlight-resistant
or covered with material listed as sunlightresistant 310.10D
Identify both ends of neutral w/ white marking or tape 200.6B
1 No branch circuits or feeders in same raceway w/ service conductors 230.7
( Conductors through separately bushed openings at
service head, length per utility specifications 230.54E & 90.20
Gl Form drip loop in conductors 230.54F
Service Entrance (SE) Cables 17 NEC
Tl Where subject to damage, protect SE cables with RMC, IMC,
PVC-80, EMT, or other approved means F56~-58. = ane
8 ble mit 80 in. O.C. & 12 in. from terminations ____
a oe ie head listed for wet locations EXC , Botts
© «SE cable OK w/ gooseneck & taped connections "ee
oy
‘Use waterproof gland or equivalent to prevent
ee OO NS
Service Entrance Conductor Size
CO Conductor ampacity must meet load of 2,3 (p.6,7) 230.42
O Conductor ampacity per T11 (p.23) EXC 310. 15A
* 63% of T11 allowed for SFD & individual units of ae
2family & multifamily dwellings T14 (p.23) 310.1587?
O Sum of ratings of mains allowed to exceed T11 if
Conductors adequate for calculated load per T2,3
SERVICE PANELS
The switches, circuit breakers, or fuses that disconnect power from the utility at
the customer's end of the service conductors are Part of the service equipment. A
meter socket is not considered service equipment (230.66), though it may be with-
inthe service equipment. Working space must be maintained at service equipment.
17 NEC
230.90AX3
General 17 NEC
C0 Enclosure L&L as suitable for service equipment 230.68
NEMA enclosure type must be marked on equipment. 110.28
C1 No NEMA Type 1 (indoor use) equipment outdoors 110.26E2, 110.28
O Protect outdoor installations from vehicle traffic (bollards) 110.262
1 Max 6 disconnects to shut off power at service = 230.71
230.72
( Disconnects must be grouped in one location
CO Each service disconnect durably marked to indicate load served__ 230.724
1 Max height AFF of breaker or switch 6 ft. 7 in. 240.244 & 404.8A
O Provide working space from face of enclosure EXC F2. __110.26A
+ Meter may extend into working space__110.26A3X2
(C Barriers req'd over supply terminals & buses in services EXC F16___408.3A2*
+ Buses & terminals of panels w/ 2 ~ 6 mains. 408.3A2X*
2-Family & Multifamily Dwellings
(1 Only 1 service per building 230.2
C Adjoining units considered separate buildings if firewall separation. 100
1 Each occupant of multifamily to have access to their disconnect EXC _230.72C
where under continuous building management supervision _280.72CX
0 2-tamily & multifamily dwellings req house meter for common areas 210.25B
CO Senvice conductors may not pass through another building 230.3
swelling services can use a multimeter panel, or the service
ay land 1 a “hot gutter” with splices ahead of separate in-
ects, See p.10 for bonding requirements on such gutters.
nly & mutttemWORKING SPACE
SEPARATE BUILDINGS
Working space is essential for wor
std all election! equipment that fle wanes eee
maintenance while energized. Working space should not be used for storage”
General F2 17 NEC
C Front working clearance min 36 in.deep 110.26A1
0 Distance measured from exposed live parts or face of enclosure__ 110.26A1
O Min headroom 61/2 ft. AFF or equipment height EXC. 110.2643
* Existing service equipment up to 200A OK < 81/2. 110.26A3X1
C Work space extends from floor to req'd height EXC 110.2643
* Related equipment may extend 6 in, beyond panel front _ 110.2643
O Clear width min 30 in. wide or width of equipment 110.2602
1 Equipment doors or hinged panels must be openable at least 90" 110,26A2
(CO Working space not to be used for storage ____ 110.268
1 Illumination req'd for working space at all indoor panels 110.260
Working Space around Equipment
aco “ae 3 ft. min. depth
measured from front
30in. min. ‘edge of panel
width or
width of
equipment if
> 30 in. Panel need not
be centered in
working space.
Door must be
copenable to at
least 90°.
Working space height
6 ft.6 in. AFF, or
height of equipment,
whichever Is greater
Req'd working space
must extend to floor
or grade.
UNDERGROUND
i ONG CONGUGIOT
TEMPORARY WIRING
To avoid objectiorable currents on conductive paths betwaen buildings, an EGC.
must be installed in addition to the insulated neutral feeder conductor. Existing
installations with bonded noutrals can remain if there are no parallel current paths.
Outside Feeders 17 NEC
C0 Trees may not support overhead conductors 225,96
Ci Overhead feeder mast~same rules as services FY 225.17-19
7 Height above roofs < 4:12 slope 8 ft. 6 in. F1__ 225.1988
CO Provide proper cover for buried cable or conduit Fa, Tt 300.5
1 Each building or structure req’s GES F3, F6 EXC. 250.324
* Building or structure w/ only 1 branch circuit & w/ EGC 250,92AX
C Raceways entering building from outside must be sealed. 225.27°
Cl Max 1 feeder or branch circuit to or back from each building EXC__225.30
+ EV chargers L&L for more than single branch circuit or feeder__225.30A7"
1 Disconnect req'd at each building F3 225.31
C1 Disconnect must consist of max 6 switches or breakers 225.33
C1 4-conductor feeder to panel in separate building~
do not bond neutral to EGC or GEC EXC 250.328
+ Existing installations to separate buildings with no continuous metal
paths, e.g, metal water pipe, ete., between the 2 structures _950.396X1
1 Disconnect rated as service equipment when using above exception 295.36
Separate Buildings
Each building or structure
containing more than 1 branch
circuit req's its own GES.
: Cover depth per T1
=" 4 Feeders to separate buildings reqan
insulated neutral in addition to an EGC.
Panels in separate buildings are subpanels F17.“UNDERGROUND WIRING = Fic. | Mighiua Da ee
‘Where underground conduits end on significantly different elevations, a drainage a
box may be needed near the lower elevation to prevent water from rising up from
the conduit. See p.24 for additional requirements for cable protection
Generel Cover depth
17 NEC (measure from
UO Cover from top of cable or conduit to finish grade per T1, Fa 300.54 top of conduit) ~
Service laterals concrete-encased or warning ribbon 12 in. above F4 300.53
|
— SAUTION CauTioN |
Warnit , |
Jarning ribbon
12in. above service
lateral
1 Backfill w/ smooth granular matorial-no rocks F4 soo. | conduit front rocks Sm
1 Provide running boards or sleeves if subject to damage from backtilFé 300.5 | (where necessary) se al
1 OK to splice o* tap direct-buried conductors w/out boxes
where splicing means listed for the purpose (e.g, resin kits) 300.5E
O Seal underground raceway entries at either or both ends __ 300.5G
Spare or unused raceways also to be sealed aoosa General 17 NEC
© All conductors of circuit in same trench o- raceway EXC 300.61 0 Allowed only during period of construction —_____590.3A
* Parallel raceways OX if each raceway contains conductors Sewvices same height, grounding, clearance, etc.,. as permanent F1,5 590.4
ofall phases, neutrals, and EGC of circuit 300.51X1 (NM & SE allowed in any height building & SE OK underground _ 590.4B&C*
ee asest Genet oun 1 No receptacles on branch circuits supplying temporary lighting 690.4D1
*S" loops, flexible connections &/or expansion fitings. 300.6) Cl Lampholdere req quarde_____________s90.4F
i Cables & raceways for directional boring approved for O Splices in NM cable or MC cable OK without splice box if EGC 7 s
rR seins typical reach MecnK continuity maintained (including listed metal cable fittings) 290.46
1 Interior of underground raceways considered a wet location goons © ©. Baste coras. 8 cables Rcey en—inuae aeege, —_—__—_—
Cords & cables not OK on floor or ground exc extension cords 580.4)"*
1D Conductors installed underground must be L&L for wet locations _ 310.10C
i GFCI req'd on all 125V 15, 20 & 30A temporary receptacles _590.6A1"
1 Listed GFCI cordsets OK only to supplement GFCI on temporary
ea ime ustse sus ele cu ered receptacles or as first device on permanently wired receptacle _590.6A1&2""
GFCI = 208 C1 Other receptacles GFC\, special-purpose GFCI, or assured grounding 590.68"
Circuit
12in.
Gin, 6in.
raceway* | raceway”
ts
Temporary Power Pole
Typical 6x6 post with
block above weatherhead
Temporary power services
follow the same NEC rules as
permanent services as well as
standards set by the utility
GFCI receptaci
UNDERGROUND pis te PN STi lel
Pt Ta tet
ORKING SPACELOAD CALCULATIONS
_ SERVICE & FEEDER LOAD CALCULATIONS es LOAD CALCULA
The calculation methods in the codes take into account th
at not all of the | General Lighting &
possible electrical loads will be used at the same time. Each of the calculation STDs & esvep ee bees
methods allows the use of “demand factors” The “long form? shown below and 1 _ | 84.8 «SYA
in 72, is the most common calculation method. For information on multifamily load | Small Applian
calculations, refer to the examples in Annex D of the NEG. PRA 6 Re Eee
: 2 [2 smal-appliance circuits 3,000
Load Calculation Steps (Long Form) T2 17 NEC —_e
1, Determine the sq. ft, area of the residence & multiply 3 _| Additional small appliance Ts
by BVA (exclude garage & covered patios) 290.12 [4 _| Laundry circuit 1,500
2. Min 2 small-appliance circuits at 1,500VA each 220.52 5 | Subtotal general ight,
3. Each additional small-appliance circuit at 1,500VA 220.524 ‘mall appliance & laundry
4. Min 1 laundry circuit at 1,500VA 720828 [6 | pracnovA@ tome aa
5. Enter total of appliance circuits & general lighting 220.42
6. First 3,000VA counted at 100% (carries to right column) ya00.4o «| 2 Banos 628
7. Subtract 3,000 from amount in line 5 & enter difference in ‘Special Appliance Loads
mile column Mutiplythemidle courn amount by 96%6& | aaron SSS
enter in right column - __1220,
5 3,000 [or nameplate if>)
8. Range loads are calculated at nameplate rating. If a single range is Sa said cts
> B,000VA & < 12,000VA, it still counts as 8,000VA (8kW). 10 | Heating or AC @ 100%
if> 12,000VA, add 5% of each additional 1,000VA of Abpliandes Fastoned in Place
nameplate load. Nameplates of a counter mounted range & 7) |W her
up to 2 wall ovens can be added together & computed as if they :
were 1 range. Enter in right column. 220.55 12 | Miecnere:
9. Enter dryer circuit at 5,000VA (or nameplate rating greater) __ 220.54 [19 | Dishwasher
40. Enter larger of fixed-space heating or AC load _____ 220.60 14 | Compactor
44-18. Enter nameplate ratings of appliances that are fixed in place. = lees
For appliances rated in amps, multiply amps times voltage to determine
° fimatesinT4___——-22083-—«([ 16 | Atiofan
watts. If nameplate ratings unknown, use estimates —
49. Enter total load of fixed appliances. a 220,68. 17_| Spa~per MFR.
20. If there are <4 fixed appliances, enter number from |ine 19 moss [12 [Oke
in right column = 19 | Subtotal
Jiances, multiply line 19 by 75%
Picton sre = 8 Wind erpiion 22053 oo '<4 fied appliances, enter sublotal @100% or
& enter in right column a assaaunoian
22, Add 25% of the largest moto load. Skip this stop Ha name 2 | 24 fod appliances, enter subtotal x 76%
fated AC is largest load since that numbor has areacy ee as aa
factored into nameplate min conductor ampacity 700,10) Total load
493. Add numbers in right column —_______ nen ee
Sa era by 240 t0 find req'd min amperage — = [| ___Tetalload + 240V = SERVICE AMPS‘Size Requirements-General 47 NEC
OOM sizeforSFD 100A 980,706
G Service conductors adequate forload tobe sewed 990.42
1 Service conductors allowed tobe 88% of T1183 10.15837
D Feeders adequate for load to be served 215.2M
1D Branch circuits adequate for max load to be served 210.1941
1D Optional method allowed 220.824
Optional Method (Short Form) 17 NEC
1. Multiply sq. ft. area by 3VA (exclude garage & covered patios)__ 220.8281
2. Min 2 smalFappliance circuits at 1,500VA each; each
additional small-appiance circuit at 1,500VA
3. Min 1 laundry circuitat 1,500VA__
4, Nameplate ratings of fixed appliances (see 4 if ratings not known);
these include full nameplate rating of ranges & ovens without
220.8282
220.8282
ieee retort be ainpter€ cant applying reductions allowed in the “long form” method 220.8283
for expansion. These methods anply t & fe &: Entocetun of fis 324 Soonee
6. 100% of first 10,000VA 220.828
eet) Mrdogs cu ey 7. Subtract line 6 from line 5, multiply by 40% __ 220.828
1. Sq.ft. x 3VA 8. Determine largest of the Leow or cooling load. When using nameplate
z ‘ rating of heat pumps or AC, multiply “minimum circuit ampacity” times
a au eee ee SASH Nereh oe, the voltage (240). If only size (tonnage) is known, refer to T4 220.89C
Baer Re 1 PO 1800. 9. Add numbers in right column & enter total 220.828
4._ Nameplate VA of fied appliances: 10. Divide line 9 by 240 = amperage
Diyer @ 5,000VA Adding Loads to an Existing Dwelling
‘Ovenis) 1 If no new heating or AC equipment to be installed, acd the following
and count the first 8. 000W @ 100% & the remainder @40%:__220.83
eee * SW per ft. (exclude garage & covered patios)
seared + 1500W for each smali-appliance circuit and laundry circuit
Dishwasher + Nameplate rating of all installed appliances or those for specific circuits
Gapoor If new heating or AC equipment to be installed, add 100% of the larger
of the heating or air conditioning to the above calculation 220.888,
eee eS
[8 First 10,000VA @ 100% Y X
Use actual nameplate ratings when known, This table is for estimating
Balance @ 40% (eubtract ine 6 from line 8) x4o|= purposes when appliances are not yet specified.
8 Largest of heating or cooling oad ‘Appliance Typical Appliance Typical
Ba, Nameplate rating(s) of air-conditioning & cooling equipment OR Load (vA) Load (VA)
‘Bb, Hoat pump nameplate rating no supplemental electric host OR [Central AC 1,800/ton | Electric clothes dryer | 6,000
“Be. Continuous electric thermal storage @ nameplate rating OR Dishwasher 1,200 ‘Water heater 4,500
6
184. 100% of heal pump nameplate rating plus 66% of supplemental Disposer ‘300 Bectric cooktop 3.600
electric heat oF central elastic heat a Trash compactor 1,200 Single wall oven 4,800
‘Be. Space heators @ 65% of nameplate rating if <4 units OR |__ Microwave 1,500 Double wall oven 8,000
“Bf. Space heaters @ 40% of nameplate rating t® 4 units P Gentral furnace 1,000 Pool pump 2,000
mg) Central vacuum 1,500 | Well pump 2,000GROUNDING ELECTRODES GROUNDING ELECTRODE CONDUCTORS
Ga
OK to use building steo! to
imerconnect GECs
Grounding
Electrode
Conductors
panel
Ufer
Grounding provides a path for lightning and reduces electrical “noise” on commu
nications equipment. Common grounding electrodes in residential construction are
metal underground water piping, ground rods, and concrete-encased electrodes.
Other types include ground rings, motel plates, metal well casings, listed grounding
electrode eystems, underground tanks, and the steel frame of a building connected
to earth as described below. Gas piping is not an acceptatle grounding electrode.
Grounding Electrode System (GES) F6 17 NEC
1D Use all electrodes that are available on premises
during the course of construction. 250.60
Bond al electrodes to form a GES 250.50
Dl Gas pipe not OK as grounding electrode 250.5281
Water Pipe
1 Use metal water pipe if 2 10 ft. in contact with soil F6 250.521
1 Bond around water meters, filters, etc, —_ 280.5301
Cl Water pipe cannot be the sole electrode-it must be
‘supplemented by another type of electrode _ 260.5802
1D Pipe, rod, or plate that supplements water pipe must comply with =,
25 ohm rule or be supplemented by another electrode
1D Metal well casing OK as electrode (e.g. plastic water service) __ 250.5248
Ground Ring
J Min #2 copper encircling building in direct contact w/ earth F6 __ 250.52A4
Gi Min 20 in, below surface of earth __260.59F
Metal In-Ground Building Structure i :
Metal i jpport structures w/10 ft in drect contact
ee aces 250.5242
‘wi earth or encased in concrete in earth (ples)
T
Service| OK fo use water pipe within 5 ft. of entry
to building to interconnect
aR soeen
OK to use Uler extension to
interconnect GECs in location
Single rod with
resistance > 25 ohms
must be supplemented
by another electrode
other than water pipe
Water pipe
w/10 ft. in
GECs
Ground Rods 17 NEC
C1 Unlisted pipe electrodes min % in. diameter & galvanized 250.52A5a
( Copper-clad rods min Sis in. diameter unless listed for less _ 250.52A5b
1 Rods min 8 ft in contact with soil FS. __ 250.536
1 Drive rods vertical & fully below grade EXC = 250.536
+ If bedrock encountered, rod may be buried horizontally
21/eft. deep or driven at 45° angle 250.536
+ Clamp above grade OK if protected F8-10 250.536
C Must be supplemented by another electrode
that is not a water pipe EXC. 250.5302
+ Not req'd if rod resistance < 25 ohms. 250.53A2X
Supplemental roda/plates spaced min 6 ft. apart (16 ft. preferred) _ 250.5A3
Concrete-Encased Electrode (Ufer)
C1 Ufer = 20 ft. #4 or larger rebar near bottom of footing or 20 ft. of
min #4 Cu wire near bottom of footing, min 2 in, encasement 280.523,
Ci Ufer must be used if present during construction. 250.50
Ci Uter not req'd in existing building if concrete would
have to be disturbed to gain access 250.50X
1 OK to bond sections of rebar with ordinary steel
tie wires to obtain 20 ft. continuous length. 250.52A3,
Cl Can be 20 it. of vertical stee! in pier in direct earth contact 250.5243
( Where multiple Uters present, only 1 req’d to be bonded to GES_ 250.5243
Pipes & Plates
CI Pipe clectrodes min 9/ in. diameter & galvanized. 250.5246
D1 Ferrous plates min "4 in, thick & min 2 sq.ft. in contact with sol_ 250.5247
C1 Aluminum not permitted as grounding electrode 2505262RS (GECs)
The GEC that connects the system of metal grounding electrodes in earth to the Service Entrance Conductor (AWG) GEC (AWG)
electrical eystem must have adequate size and protection. Individual GECs can ———— zi
be run te each electrode of the GES, or a single GEC can be tun to one of them, wo fT a
provided all the other GECs are connected by bonding conductors. Pr 1/0 a 6
— a 17 NEC orto “Boor s t_uiS=aE=
rn
ee ent 210 oF 3/0 4/0 of 250kemil
& service neutral to the grounding electrodes__ 250.240 = =
1 Gonnect GEC to service neutral at any accessible point om ake iiae eet
load end of service drop to neutral bus in service disconnect. 250.2401 > 360-600kemil > 500-900kemil
Q Be AGE tot OKin stony oath 250.644 >800-1100kem’ | > 900-1750kemi1
ere outside, no Al ter ited within 18 in. of earth. 250.644
> 11 00kcmi > 1760kcmil 3/0 i
T Connect GEC to metal water pipe that is continuous from ~ =
underground $5. from point of pipe entrance to building F6__25068C1 Protection F7-10 17 NEC
1 Metal structural building frame OK to interconnect GECs 250.6802 —_—_[1 2 #6 req's protection if subject to physical damage EXC 2506482
1 Hold-down bolts of metal structural building frame OK as * If following building contour & not subject to damage F7. 250.6481
connection to Ufer w/ tie wires, welding, or other means 250.68C2"? D0 #8 always req's protection by raceway or armor F8 250.6483
1 Additional Ufer bar may extend through foundation to accessible 1 Bond each end of ferrous raceways enclosing GECs
point for connection where not subject to corrosion F& 250.68C3"* to the enclosure or electrade or to the GEC F8. 250.6451
Mathode of Connection C Bond protective conduit using same methods as for
1 No splices between service & GES EXC 250.646 supply-side bonding (see p.10) Tae
* Listed ireversible compression connectors or exothermic welding 260.640 __ If connection to red ie above grade and located where subject
250.596
Note: The GEC does net need to be continous ram one portion of the GES to another;
individual conductors can connect to components of the GES
Gi GEC can connect to any electrode of GES or GECs can
to damage, protect with wood or metal enclosure
Armor-clad GEC
connect individually to electrodes comprising GES. = 250.64F
Buried clamps L&l for direct burial (marked “DB") F6 250.70
1D Cuwater tubing clamps Lal for Cu tubing 250.70
DD Ufer clamps L&L for rebar & encasement FE 250.70
C Strap-type clamps suitable only for indoor #8 must be protected.
telecommuricetions 250.70 > #6 following the aN asad
1D Max 1 conductor per clamp unless listed for more. _ 250.70 building contour does not bond motel
Cl Connections must be accessible EXC 250.68A need protection. sheath to GEC,
+ Buried or encased connections 0 250.68AX1
Size .
1D Size bonding conductors that connect GES per GEC rules. 260.530 be! ici GEC in pve
Gi Size GEC based on largest size req'd among . y
all electrodes in the GES = —260.64F | Ferrous metal protective
i Size GEC per sevice conductor size TS EXC_ 250.86 Sickive coal hae
#46 Cu largest size needed if ending at rod or plate electrocie 56 ean nt bells erica iia
. Pending stUler___—— PVC a simpler solution,
#4 Cu largest size needed if ending ie
+ #2 Cu largest size needed if ending at ground ring
GROUNDING ELECTRODE CONDUCTORS
fe cm eteBONDING EQUIPMENT GROUNDING CONDUCTORS
Bonding ensures electrical continuity to limit voltage potential between conductive
‘components. On the supply side (ahead of the main disconnect F16), it provi
path back to the utility transformer for faults on service conductors and mits
voltage potential to other systems, such as telephones or cable TV, On the load
side (alter the main overcurrent protection F'18), bonding and equipment ground-
ing provide a path to clear faults and protect against shocks.
Bonding & Equipment Grounding Methods 17 NEC
Use listed connectors, terminal bars, exothermic welding,
machine screws engaging 2 threads or secured w/ nut, or
thread-forming machine screws engaging 2 threads F11 250.84
1 No sheet metal or drywall screws F11 250.8A
1 Connections may not depend solely on solder 250.88
1 Clean nonconductive coatings from contact surfaces 250.12
MERGE 0 Grounding Methods
Listed connec:
tors OK (barre!
crimps, wire
»
*
Connect ail
equipment
grounding
conneciors
nuts, pushin
connectors)
screws NOT Tt
i maintained if device
Supply-Side Bonding F12,13,16 17 ne
Cl Bond all service equipment, raceways & cable armor _ 250,02
El Threaded fittings OK for bonding service conduit 250.0282
Dl Meyers hub OK for bonding service ‘conduit F12, 250.9282
Do ‘Standard locknuts not OK on supply side of service FI2 250.9282
CD Bonding Jocknuts OK if no remaining ‘concentric knockouts F12 __ 9509284
y'd around impaired connections (concentric
pars dma oop aos 8 __ 250008
1D Senice neutral can bond suoply-side easement a a 30 42a
i eecterte pall
Stern seo maimed bw,
e service neutral & equipment grounde F16________ 250,241
me to the GES ___—_—— 260.106
1 Bond lighining protection
PU ae)
cam Fittings with No Remaining Concentric Knockouts
e
Bonding
Jocknut
e @2
Bonding at Impaired Connections
_— Bonding jumpers
Bonding
bushing
Intersystem Bonding F14 17 NEC
1D Separaie decodes for phone/CATV req #6 bond to power GES _800.100D
1 Accessible Intersystem Bonding Termination (IBT)
devce req'd external to service equipment
1 [BT req'd at disconnecting means af separate buildings.
18 rea's min 3 terminals listed for grounding & bonding
1 IBT device not to interfere w/ enclosure cover: 250.9443
Cl Min #6 Cu to bond IBT to service or GEC. 200.94A485
LD GEC or nonfexible raceway OK &s bond point in existing buildings 250.94%
BIBT not req'd if communications systems not likely to be used__ 250.94%'"
250.94A"
250.948
250.9442Load-Side Bonding 17 NEC
(2 Bond any metal piping system capable of becoming
energized, including hot & cold water &gasF14,15 980,104
CO Size water pipe bonding per TS a 250.104A1
O Size gas pipe bonding per T6. 250.1048
1 Gas bond may be from EGC of circuit Ikely to energize piping 260.1048,
Bond metal well casings to EGC of pump motor __960.119M
_ EQUIPMENT GROUNDING CONDUCTORS (EGCs)
GCs limit voltage on enclosures and provide a path for fault current. Without
GCs, the frame of an appliance could remain energized if there is a fault.
‘Equipment grounding provides a low-impedance path so the overcurrent device
will open the circuit. The purpose an of equipment grounding system is completely
‘different than that of earth grounding; earth plays no part in helping clear faults.
General 17 NEC
(1 EGC must provide effective ground fault current path 250445
DD Earth is not an effective ground-fault current path 250.4A5,
0 Size EGCs per T6 260.1224
Gl Remove pant ‘rom contact surfaces of pipes for
250.12
field-installed equipment such as ground clamps.
[ EGCs must run with other conductors of circuit EXC __ 250.118 & 300.28
* Replacement of nongrounding receptacles (see p.28) 250.1306
i Neutral not to be used for grounding equipment EXC. 250.1428
* Existing renges & dryers 250.142BX1
‘Types & Identification of EGCs
D1 Wrre £GCe can be bare, covered, or insulated 950118
1 Conductors < #6 must be bare or factory insulated
w/ green (or green with yolow stripes) 950.119
Cl Conductors 2 #4 OK bare for entire exposed length
‘or use green tape or labels encircling the conductor 260.1194,
Fl Green not OK for neutral or ungrounded conductors, 250.119
[OLRMG, IMC, EMT, AC cable armor, electrically continuous
250.118
raceways & surface metal raceways OK as EGC.
FMC& LFMC not OK as EGC exc for non-motor circuits in combined
lengths to 6 ft. with grounding fittings F 950.118
Pete he sik s ened
Bresker or Fuss
Bonding Interior us:
Piping
ng syste
be b
ing energized
them at a gas water h
provides an easy way
What we commonly call an “electrical pane!” is referred to as a panelboard (NEC
408) inside a cabinet (NEC 312) F16. See p.# for working-space requirements,
Clearances & Location 17NEC
(1 OCPDs readily accessible & max height AFF 6 f. 7 in 240.248
No panels or OCPDs in clothes closet or bathroom 240.24D8E
1 No panels or OCPDs over steps of a stairway 240.24F
Enclosures (Cabinets)
1 Enclosures weatherproof ( NEMA 3) in wet or damp locations 312.2
1 Surface-mounted wet or damp location metal enclosures
min Vain. air gap between enclosure & wall 3122
1 Equipment rated for dry or damp locations must be protected
against damage from weather during construction. 110.11
1 Open knockouts & twistouts durabiy filed EXC 110.128
+ MFR holes such as these for mounting OK 110.124
1 Protect bus bars & other internal parts from contamination
(paint or plaster) during construction 110.128
1 Max setback in noncombustible wall (steel studs) "in 3123
1 Flush (no setback allowed) in combustible (wood-frame) wall 3123
Cl Max plaster gap at side of flush-mount panel "/ain. 3124
D1 Dead:front cover req’ 408.38,
1D Circuit directories to distinguish each circuit trom all others: 4084
1 Directory labeling not based on transient conditions. 408.4
1D Unused (spare) breakers labeled 408.4
Equipment Grounding Conductors in Panels
1D Grounding terminal bar req'd if wire EGCs present F17 408.49
1D EGC not on neutral bar in subpansle, 250.2445
11 > 1 EGC (not neutrals) can be connected in
4 terminal if alowed by L&L of panel 110.144 & 408.40
1 EGCs & neutrals may not share same temninal, even in service
408.41
‘equipment where they are allowed on same terminal bar
Pe eo iSe WIRE BENDING SPACE JULTIWIRE CIRCUITS
Barriers over
Neutral Conductors 17 NEC Service
1 Bond neutral, EGCs & enclosure in service panels F16 250.246 Panel ee
1D Isolate neutrals in subpaneis F17 980.2408 ee
1 Gey mds nto depend n erlonree— 20028 Bonding
fach neutral conductor req's individual terminel 401 ushing F13
El Wei iervid taro poe tarore cron o WGA pooan | read fr | SUPPLY SIDE
no —aoer | Sites Loan SIDE
* When grouping is obvious, such as a cable system 200.48X1" entering
+ When passing through a box with no loop or splice 200.48x2" through euitral conciactor
1D Neutrals factory-applied white or grey EXC. 200.6A concentric Wdoesitied (wets
Simba et wince gees eit w_____rooo | noche Sicandees)
(White not OK on ungrounded conductors EXC __ 200.7A ~“,
* White conductors of a cable assembly OK as ungrounded 7 GEC ae
conductors with tape (not white or green) encircling ends __ 200.7C ences
OCcPDs
Gl Bus req’s overcurrent protection on supply side EXC F16,17 408.36 Be erp
* Service equisment bus w/>1 main disconnect. 408.38x1-3 Breaker oes
1 Breakers mus: be isted or classified AMI for panel _ 11038 protects
Protect ungrounded conductors w/ OCPDs 111,15 240.4 panel & cama
1 2-pole breaker or 2 single-pole breakers w/ approved handle a aecasien
ties req'd for multiwire circuits or for 240V circuits F17 _ 240.15B1&2 feeder
1 2-pole breaker or 2 single-pole breakers w/ approved handle
ties req'd for receptacles on shared yoke. ___210.7 fam
1 Backfed breakers secured in place EXC__ 408.360
+ Output circuits from listed utlty interactive PV inverter__705.12B5 Subpanel
Panel Wiring
1 Torque all breakers & terminals AMI ___ «11038 & 110.14D"
TD Antioxidant on Al conductors AM) 1102.14 —
Dl Secure each cable entering pane! AMIF16,1749____ 312.80 hana Gener
Wire Space single-handle
1D Avoid crowding of conductors = ___ 3127 2-pole breaker.
1 Spices taps in panole OK to 40% fi, 75% max cross-section. $12.8A182
Power-monitoring devices OK if fsted & meeting above fil eq's ___ 912.86 if more than one
circuit in raceway
1 Feed-through conductors OK to pass through pane if warning on ens
label that identifies power source is applied to enclosure 312.8A3 2 Sipe Sim
Min bending space for conductors not entering or leaving See
‘wall opposite terminals (*L' bend) per T7A, F18 312.681 russ ao
2] Min bending space for conductors entering or leaving siuabece on aa
‘wall opposite terminals ("S" bend) per T7B, F18 EXC 312.682 Rac wire, Also applies
cl to raceways with
© TTA distance from terminal to wall OK if conductor enters . No wire tie Cow
‘or leaves in gutter & meets distance per T7A, F16. 312.6B2X1 teales be ore te
1 Conductors entering from back wall req T7A distance muttiwire circuit.
408,580" circuit in cable.
to cover and T7B distance from terminals F18__—
eenWire Bending Space
(For clarity, neutrals & EGCs
shown)
Dimension T78 from panel wall to lug
dotermines max conductor size.
The conductors from this breaker
are allowed T7A size because
‘they exit the side wiring space to
en adjacent gutter that hes T7B—
space. The adjacent gutter space
is measured from the boundary
posts above the main lugs.
Conductors exiting wall opposite
terminals limited to T7B size
Conductors not exiting wall
‘opposite terminals limited to 7A:
size
Back-wall entry conductors.
limited to T7A measured to front —
panel edge 417B measuredto =f
breaker terminal
Pik nn Se eeaste cn a
Pea a eta nse)
L Bends—Wire not through wall
TABLE7
'S Bends—Wire through wall
opposite terminal
CuWire Cuwie | AlWie' | Distance?
aio | 128 wa
8 6 We
6 4 2
4 2 3
3 4 3
2 1/0
1 2/0
3/0
a0 6
250 on |
so | 7
1. Compact wranded aluminum conductors using AA 6000 satis aon.
Gree Tues ston angle, tw tance can ba moore wong henge Ww a th dwn
‘Tas tance i enaed in w raigh ro fom the gn ac
on papendicl oho pal wak
ae eta tS
NELS Lit
Multiwire Circuits 17 NEC
Cl Ungrounded conductors must originate from opposite poles 400
1 All conductors must originate from same panel
210.48
1 Neutrals may not feed through devices whose removal would
interrupt continuity (use pigtails from neutral to devices in box) 300,198
(All muttiwire circuits req handle ties or single handle breaker 210.48
1 All conductors of muttiwire circuit must be identified or grouped
(wice ties or other means) inside enclosures EXCF17 _ 200.46 8 210,40"
* Cable systems where grouping is obvious F17__ 200.481
* Where passing through box w/out splice or loop_ 200,48x2"
Most utity raneformers for 1- and 2-famdy dweling services have two ungrounded
“hot” conductors and neutral derived from the canter of the transformer, as
depicted in F19. The neutral is connected to earth and isa "grounded" conductor.
Te neutral mits the voltage on ether cf the hot conductors to 120V to ground.
The service is a “3-wre” shared-neutal circuit. 120V branch circuits wih shared
neutrals ae known as mutwire cicuts (iso called “Edison” circuit). tthe neutral
ip broken of loose, voltages become erratic, az in F19 [ol TV seta, motors, end
Computers don't do well wih fluctuating voltages: Signe of uetable valtage, eich
as incandescent bulbs growing brighter or dimmer as ther loads change, could
incicate a loose neutral either at abranch circuit rat the uty
Multiwire Circuits
Utility Transformer Secondary
~ yeaneu wedo
EY PROPER CIRCUIT 2 unequal loads are fed by a S-wite circuit. The
‘neutral cartes the imbalance between the 2 loads
El OVERLOADED NEUTRAL Without voltage potential between the
hat conductors, the neutral caries the sum af the loads, In a 3-conduc
tor NM cable, the black & red wires must originate from cifferent poles.
[Fl OPEN NEUTRAL Tuo unequal loads in saries across 240V from the
| anstormer, The load with lowest resistance sees the lower voltage.
Voltage at each load depends on other loads and is unstable.
1. On 120/208 systems, the neutral aways caries currant, even in
progeny balanced circuits, The principles here ail apply,
ret TALE_ ARG-FAULT CIRCUIT INTERRUPTERS (AFCIs)
AFCls provide fire protection by tripping when an arcing fault is detected. AFC!
breakers and GFO! breakers look similar F21,24, and you must read the label to
determine if oreeker is an AFCI or a GFCI. Dual-function breakers that provide
both AFC! & GFCI protection are also avallable F21, Outlat branch circuit typo
(OBC) AFCIe aro aloo available, including ones that are also GFCls, and the codes.
have changed substantially to recognize these new methods
The number of areas requiring AFCI protection expands in each code oycle. The
time to plan for the AFCis is during the rough wiring, so that separate cables are
provided for the crouits requiring AFC! protection. Not all brands and models of
‘AFCI are compatible with multiwire circuits,
Beginning January 1, 2008, all AFCIs were req'd to meet the UL standard for “com-
bination’ types rather than the older “branch/feeder” type. Combination AFCls pro
vide @ broader range of protection then branchifeeder types. OBG AFCIs provide
tho same range of protection as combination types, and when inotallod at the first
outlet box on @ circuit protected by an older *branch/feeder” AFCI, that circuit then
‘complies with the 2014 and 2017 NEC.
Areas Requiring AFCI Protection 17 NEC
Cl Regla forall 120V 18A & 20A branch circuits supplying outlets
or devieos in family rooms, dining rooms, ning rooms, parlors,
lioraries, dans, bedrooms, sunrooms, recreation rooms, closets,
allways, kitchens, lsundry areas & similar rooms EXC 210.1288
‘May be omitted on individual circuit to a fre-alarm cirouit in RMC, MC,
EMT, or steel-armored AC or MC cable w/ metal junction boxes that is,
part of centralstation system in accordance w/ NEC Article 760 _ 210.12AX
Ci Regis forall 120V 15A & 20A branch circuits supplying
cutlets & devices in dormitory unit bedrooms, living rooms,
hallways, closets, bathrooms & similar rooms 210.126
New Box &
Receptacle
on Extended
Circuit
—
Existing Receptacle
Replace with stocted
OBC AFC! a!
Unprotected
being exter
Replace with dual:
function GFCI
OFC AFC! wit
foul 20 0.28). Replacement
of Existing
Ungrounded
Receptacle
New Box &
AFCIs
Labeled
“AFCI"
on face
Two-Pole AFC!
Outlet Branch Circuit Dual-function Breaker for
(OBC) AFCI AFCI/GFC! Multiwire Circuits
AFCI Protection Methods 47 NEC
Cl Combination-type AFCI at origin of branch circuit ___ 210.1281
0 Branch/feedertype AFC! at origin of branch circuit &
OBG type at frst outlet box on branch circuit,
W/ outlet box marked as first on circuit 210.1242"
1 Ordinary circuit breaker at crigin of circuit & RMC,
IMC, EMT, Type MC, or steeharmored AC cable to
fist outlet, with OBC AFCI at frst outlet. 210.1285
C1 Ordinary cicuit breaker at origin of circuit & metalic or
onmetalic conduit or tubing encased in min. 2 in. concrete
to first cutlet & OBC AFCI at first outlet __ 210.1248
In-addivon to the 4 aiso inckides “supple
protection breskers” & *syatem combination” OC!
e used in cd
Create 2 system that i listed. As of this writing, nest
exiais, These two additional methc
Extensions, Modifications & Replacements
H ttwiring extended, modified, or replaced n areas where
protection currently req’d, provide protection by
‘combination AFC! at origin of branch circuit or OBC
‘AFC! at frst outlet of existing branch circuit F20 EXC. 210120
“Not req'd when extension of conductors $6 ft &
ddoos rot inchide ackied outlets or dovicos 210.1205
7 Ropiacoment receptacles in areas whare AFC!
protection currently req'd must be OBC AFC! or be
protected by combination AFC! or OBC AFCI EXC F20 406.404
+ Replacomonts w/ GFCI receptacle in older 2wire systems
where pane! does not accept AFCis & no practical means
available to install EGC & no added wiring to receptacle &
dual function AFCV/GFCI receptacles not available__ 406, 4004 1-4"‘GROUND-FAULT CIRCUIT INTERRUPTERS (GFCI.
A properly functioning 120V circuit is balanced-the current that travels to the
cutllet on the ungrounded conductor is balanced by the current retuming on the
‘neutral conductor. When a ground fault occurs, current travels on @ path that is not
designed to carry current, such as the metal body of an appliance, or the human
tbody touching that applianoo. This fault current creates a detectable imbalance in
the appliance's circuit. GFCIs respond to these very low levels of current mba
ance in @ circuit, and limit the duration of the fault to safe levels. ronically, even
though the earth is not a good enough conductor to trip a breaker, it is a good
enough conductor to carry the low levels of current that can cause electrocution.
GFCis have substantially reduced the number ot electiocutions since they were
first implemented. AFCle reduce fire hazards; GFCIs reduce electrocution hazards.
in F22, 09) ats aro flowing to & trom the
ated by the luc!
posite polarity &
the GFCI & the GFCI accounts for the ek
he curre the GFO! @
other, The circu through a
tions on each conductor. As lon,
Resistor
Circuit
Balanced
| load
between
hot &
neutral
utility
| tanstormer
During 2 fault F23 more current Hows to the foad than from the joad. This
diterantal erestes a meget Fld tat induces vote coll. The
resulting cu Coil signals the relay mechani irc
n. whieh opens the
Ground Fault
Fault to enclosure
Circuit opens
when GFCI
wnstream should
dé. Labels
‘mt req'd for propery
Locations Requiring GFCI NEC
‘See p.80 fot GFC} req’s for pool eg
1D GFOis req'd to be in reacly accessble locations _ 210.8
1 Distance measurements = shortest path wlout piercing
Foor, wal, cxiling, xed berrier, doorway, or window 210.8
Grolpre
Bathrooms
Dl Garages & accessory buldings (po ception
1 Outdoors EXC
“GFE cicit dadcaied to ron-eadiy accessible eceptacies
for snow-eling or doing equpment
1 Crawl spaces at or below grace level
1D Unfinhed portons of basements or basement areas
rat intended as habitable rooms EXC.
‘Permanent istaled cena station alarm ays
2 Whore eorvingltchen countertop surfaces F25
1 Within @ to a inks
Within 6 af ub or showor tall FA
1 Laundry areas
1 Outlets supphing dishwashers 21080"
1 Hycromassage (whipoo tbs 80.71
odein GPCI have groaerresiaanee fo corrosion & surges, Thay a more fl
Sra dcp oot evs tre peobler of Sikearen Dee Te
© that sce onated for GFCis have boon removed rom the
Te inlaaton nations foe OFC ate now sandacized le coneistaney
oa iy nequre checking GPCI operation afer Malan fo ensure Pa
: A ad ees on opera
jon is req f & 204
210.901
210.8A2
210.843
210843X
210.8A4
210.8a5
2108AX
210.848
‘210 BAT
210.840"
2108A10"PE eet MG Cantey
(BRANGHeIRcUTSeouTieTs EN
Branch cirouts are the permanent wiring between the final OCPDs (fuses oF
broakers) and tho outlets that provide power to electical equipment. Separate
Circuits are required forthe kitchen small applance circuits, bathroom receptacles,
laundky, garage, central heating equipment, and large appliances. h some cas
fas described below, these are “individual” ‘crcuts, with only one pleca ‘of equip
tment on the sirout, With few excoptions, roquirad raceptace outlets must be eted
tamperresistant types.
Circuit Sizes, Number & Load Limitations
1D Rule of thumb: min 1 general-purpose circuit per 800 50, ft 22012
1D Load not to excoed rating af ranch ctcut. 22018
i Min size = 125% of contiruovs load + 100% of noncortincus load 210.198
1 Continuous toad = max current for $ hours er mor 100
1 Min size forbranch cireult wirng #14 Cu 210,10A4
1D Individual crcut = supplying only one piece of equipment 100
1 Branch circuit ratings for other than individual circuits
must be 18A, 20, 30A, 40A, or BOA,
G1 Single piece of coid-&-plug-connected equipment not permanently
fastened in place max 80% of 15A or 20A branch crout
Cl Max single cord-&:plug-ocnnected load on multireceptacle
circuit rot to exceed 80%6 of receptacle rating
1 Lighte & receptacles OK on same 16A or 20A except small
17 NEC
21018
210.2801
210.2182
appliance circuits, bath-recoptacke circuit, laundy crout__ 210.93
Receptacies-General
D1 Receptacles for specific spplances laundry, garage door opener)
within 6 fof anplanes location __
D Flenble coms not OK as fixed or concealed wiring
[Fl Receptacles must be mounted with 6-32 machine screws —
Receptacle Types and Ratings
210.506
400.12
1065"
TD Alrocoptasios on 154 £204 circuite grounding type 4084A
1D Receptacies for direct Al conrecton marked ‘CO/ALR_ 40630
17 Receptacles req'd by 21052 fisted TRtype EXC 408.12
+ Receptades lcated’> 51/2. above for. 406121
1 Replacement receptacles listed TR type EXC — 400.405
‘Replacement nongrounding type reseptaces eee p28) 408.405
184 20A nonlockng receptacles in damp or wet
ean ated weather! om 4080481
1 Sl eceptacios aed nat shan bench erat 212181
‘An eraple wourd bea single (rot dupe
foe'a microwave oven range hood wit) a cord & plug c
Tl Mutiple receptacles on branch crcut per TB__ 20218
errr of hese ulna duplex epic 2 eagles ot "ge reap
peer une ui
Bee Perret meee
‘Circuit Rating, ‘Circuit Rating | Receptacle Rati
75h 0A) 40 0% 50A
208, OA ‘0A,
308
Foyer
Wail 32
Receptacle Spacing
TV outlet> Bt
AFF dovs nat count
‘a rey'd receptacle.
Max 12
between wall
‘ceptacios
mansired at
Aooe/wall ne
When wal placement
possible dur fo glass to floor
install oar receptacle within
78 in of wal
Bar-ype counters are
considered wall space and a
receplace ts 129° 09 —~
the wall wihin
Git of the ond.
This receptacte serves 7
peninasle countertop.
Ttcanrot court as @
wal space outlet.
Hallway 240"
chen
\
Retigerator can be
‘00 indvidual creat
an
S
Fh man
Tat max
amar ai morReceptacle Outlet Locations F25,26 17 NEC
TT Walle > 2. wide r0q receptacle in habitable rooms _ 210822
1 Patitions& barype counters count as walls 108942
1 Dcorwaye, fireplaces & cabinets w/out counters rot wall 210.82A2"
1H Receptacles req go no wall space > 6 ft rom receptacle
measured herizontaly along floor line of wall 21052A1
1D Receptacle req'd for hallways 2 10 fin length 210.59H
5 Receptacles that ae part of eloctri baseboard heaters
(OK 8s req'd outiets-may rot be on heater orcuit _ 210.82
1 Receptacles> 5%, above foor do not count as reqld oulleta 210.62
{1 Floor receptacles > 1@ in, from wall do rot count as req'd outlets 2105243
1D Switched receptacles installed a req'd ghiing do not count
as part of req'd receptacle outlets unless “half hot 210.82
210.521
10.52/"
1 Req} each wall2 3 tin foyers > 60 9q, ft. EXC__
* Sidelite windows to floor de not count as wall space
6 ft./12 ft. Rule and 2 ft./4-ft. Rule
Wall receptacies serve the spaces 6 ft 10 each side of the
receptacle. Therelore, the max distance of wal ne betwee
receptacles is12 It Kitchen countertop receptacles serve tho area
ior 2 ft. to each side, and max distance between receptacles is 4
6 wall
|
| QF 28 countertop
12 ft. max. wall,4 ft. max kitchen countertop
een eT eee
| FiG.27 | jand Countertops
{sland countertops that
are flat across the top
require only ove
receptacle for
ountertop space.
The receptacle can be on
the side of the cabinet no
move than 12 in, from the
countertop surface if the
overhang of the counter
{op does not exceed 6
6 ft wall
2h countertop
=n Island Range or Sink
WX<12 in, the
countertops ere
‘considerod
separate space
‘and each
roquites
a roceptacte
{At east two 20A srallappliance branch circuits are req’d in kitchens and dining
areas. These circuit are in addition to thove for lighting or permanently installed
appliances. Additional circuite can be installed for spacifc appliances, such a5
roltgerators. Receptacles are req for countertop spaces? ft. or more in widlh
See p.14 for tules on AFCis & p.18 for rules on GPCI
Branch Circuits
Dl Min 2.208 smaltappliance circuits req'd
1 Smaltappliance cicults must serve al countertop & exposed wall
receptacies in kitchen, dining room, pantry & similar arees EXC__ 210.5281
+ Switched receptacles (dining room ight) _ 2105281X1
+ 18A.cor 204 individual branch circuits fer spectic appliances 210.5981 x2"
1D No other outlets (including lights) on smallappliance circuits EXC 210.5282
17 NEC
210.1161
+ Receptacles for clock or gas range ignition OK _ 210.8282X
CD Dishwasher & disposer req separate circuits if combined rating
exceeds branch circuit rating 210.1941
1 40A 240V circuits OK for range receptacle outlets 2102184
(140A or SDA 240V circuits OK for builtin cooking applances __ 210.28
Receptacles for Countertops & Work Surfaces
D Reoeptacios reid forall wall counter spaces 212. wide 210.5261
C1 No point along wal ine > 26 in. horizontally from receptacle F25_ 210.5201
1D Countertop spaces separated by angetops, raigerators,
Corcinks considered separate countertop spaces F25______-210.5204
1D Area behind sink or range considered countertop space
2 12in.to wallor2 18 in, tocomer F29 _210.5201X
(Max 20 in. above countertop 2105205
Dl Mult-outlst assemby in bottom of upper cabinet OK as
req'd receptacles ifS 20 in. above countertop __2108208
1D Peninsulas req receptacte # long dimension
2241, & short dimension2 12m 2t0.52c3)
1 Peninaulee moagured from comectad perpendicular wall F25 __210.5209%
1D Each island countertop space w/ 2 24 in. long cimension
& 12 in, short dimension req’s receptacle F27.28
1D Sink or range with < 12 in, behind divides sand or peninsula
‘countertops into separate countertop spaces _-210.5204
1D Receptacles OK § 12 in, below top of flat islands & peninsulas
Where overhanging counter 5 6 in, past support base F27__210.5205
Ne face-up countertop receptacles 408.56
1D Listes pop-up receptacte assembles OK F27 210.5205 4 408.5E
1D Counter recentacies do not count as wall space recepiacles F25 210.52A4
2105262
x 50 Ib. rq independent support ‘314.2702
1D Palle tans req LAL paddle fan Dox ‘31827
1D Coitng-mountod bone w/ epare soparaiay switched
ungrounded conductors eq listing for pad fan 14a
L Sticke & CO slams OK to suppor on cevice ome 314270%
Devien Secu nee
ctor Support
urate
ie © 2 eunina holes
ox
cesMax. plaster
gap Yan.
Conductor Length wNec [i
1 Min 6 fn, conductor brought into box Fas == 300.14
(OO Min in. tree conductor past face of box FA5, 300.14
Box Fill
1 Size must bo sulficient to provide free space for conductor
ion
____ state
Standard metal bores per 19 314.1841 wecee
{Include volume of marked rrud ings & extensions 314.164 scien
5 Spacon within boxes with bares counted separate 4.508 Overing et
1 Barrier volume as markod oF Yscu, in. metal boxes, tin. plaatia 914.1 0A" too large
Improper Box
Install:
(I Plastic bores are marked w! their volume — 314.1942 Bor
1 4in (6 cuin) parcale OK only end of 14/2 run FA 314.168 Max. setback Vin. if ssarcer
11 1Bou.in,boxtoo smal for 3122 Romex 10, F31 314.168 noncombustible surface, (oot ing)
| 2210 combustible
Box Fill Factors 79,10 arNEC
| Size (AWG) and
Box Trade Cuin 1 Count each conductor exting box EXC. 314.1681
Sia | SHOOTS | sclime een ee + EGCs from luminaires o° up to 4 conductors < #14
6s | 10] 2] «| {ror luminaires with domed canopies 314,1881x
4x1 | Roundoctagona | 125 | 2 [5 | 5] 8/6 1 Untroken conductors passing through box count
4x 1% | Round/octagonal | 185 | 9 | 5 | 6 as only | conductor EXC ____________3144684
= ete $ * Looped urbroken conductors > 121m. eaunt 82 314.1681
4x2% | Roundioctagonal | 215 | 4 [7 | & | @ | 10] — D1 Donor count pgtaled conductors to devices 314.1681
1 Intemal clamps count only 1, based on largest conductor h bor _ 314.1082
41% saa 380i) 8 |S a)e7 |e ane Cl Support fitngs (tude or hickaye) count as 1 conductor for
auth Square ao [4«[7]e|e| 1 ‘ach fiting type based on largest conductorin bor ___ 94.168
1 Count devices as 2 conductors based on connected wire size 314.1684
4x2ik Square aos | 6 [10] 12] 13 | 15 | Al EGCs count ony as 1 based on largest
4Mh0x 1% Square a6 [5 |e [iol | Scr
atthe 14 ‘Square ws [s | oli fsal a] [tem
wenn ‘Square 420 | 6 [14 | ie | ve | a | [Wiscontuctor oitng box
#12 conductors exting bax
Device! ze: [Saleen eanie
es _ #0 conductors eating box
Bx9x9 Device! ROU MCM IERIE) | 40 conductors extn box
ae Device! ws t2lala|a«ls Wicninew eligi 7
Poe Deve Tae | Saleulneal eae Largest grounding conducior-count only one 1
Devices: 2x connected conductor ze
9x2%2% Device seo) | 4 |S) |e: | (ena clampe-one based on largest wire present 1
Bx2xo% Daves! [480 [9 | 6 | 2] ©) © | | Finuettnge-one tor each Ope Based on krgoal GE
4x2texi%s | Device! ws [2isialalo TOTAL re
“Gx2inxiih| —_Devico! wolfe l*ls|s]¢| mio — >=
axainxain| Device! 5 [2]4[s5 || 7
unde ah | Masonry boveerg | 140 | 2 | 4 | 5 | 6 | 7 Pancake
axa | Masonrydovoany | 210 | 4 | 7 | 2 | 9 | 10 re
[FS | Sriplecoverigang | 196 | 2 | 4 | 6 | 6 | © 7 sivdaniaen
FD | Sngecovergag | 160 | s |e | 7 | 0 | 0 ten, yore feu'in voume
ae aCe 6 bar can be used at tha anc fu Of 14/2 NMC abe
nein the bow, Ciheruien, paneahe Boker eat be ;
4|alo hauing a red canopy wth te whame a
ihclnt and 2 marke yh muna aLIGHTING SWITCHES APPLIANCES
PLC tC)
Lighting outlets and luminaires mast be installed with no exposed lve parts that
pose a shock hazard. Lights rated *type IC” are suitable for insulated cotings,
General qWNEC
1 Alltuminaires, lampholdors & retrofit kits sted 4108
1 Exposed metal parts grounciod EXC 41042
+ Incidental metal parts such as mounting screws 410.42
1 Wet location luminaires LAL for wet lacation —_ — 410.104
1B Damp locaton luminaires L&L for damp or wet lation —_ 410.108
i Screw shels for lanpholders only-no adapters 410.90
Recessed Lights
1D Nor-Type 1C min Via in rem combustibles 410.118A1
D1 Non-Type IC min Sin, from insulation —_ 410.1168
1B ype IC OK in contact with combustsie material 410.1182,
1D ype ICO in contact with inaultion 410.1108
1B Luiminaires that req > 60°C wire must be marked 410.74
Connect proper temprated wir to luminaire FS 410.1178
1D Tap conductors per NEC 210.19A4X1 (#14 on 20A ret)
OKit complying with note at bottom of F35. _ 410.1176
Recessed Lighting with Old Wiring
New high-
temp wire
Ord low.
wy
SOV must be sted __ ey
422.108
1D Branch crcut rating rating of appiance.
1B Branch circu rating 1259 of rating of applance Wf cordinuousload 422.104
Contral Heating Systom
1D Ovta heing eure ial cout EXC 12219
“Fated eqn soved Gas par, hin os) AR Xt
‘Pamaren) comeced AC eminent aan 1902
Cl mgctconnet ea Mocha Caen 8422 310-6
Pua ter hevundese ur posdBR vphiancral GGPO reteoana Pl
TS Ushio oto cdo apace wt po ony i onnce 212.7048
£7 1207 rsplace ode 20 ovale 21063
RM sso"
MEG su" switcn aor
fused switch An exam
| 208 creut
lL
Water Heater (WH)
[D Coneideres cominuous load fr sting circus (size at 12596) _42213
Cl tn-tight disconnect or lockable breaker or ewiteh reqiF39, 4218
1 Bond tot, cold & cas pines FS. 250.104
D Instantaneous WH w/> 1 crcll must have disconnects
42230
(grouped & identitied as the WH dacornecting means
Air-Conditioning
1D All outdoor conduits in wet locations must eartain
wet-rated conductore~no NM able
[1 Wring & OCPD per nemeplate of LAL equpmant
3009 & 810,106
(OCPD ussal larger than number shown in T18) “4048
1D Discornect on or within sight of cendencer Fa 44014
1D Discornact not OK on compressor access panel 4044
5 Working space rec'd infront of disconect F2 710.268
Bi Room AC reqs EGC _ 44081
440.620
D Room AC max ating G09 of dll branch circuit ating —
Room AC core & pag OK as ony diacannectitcontrole $6. of foor_ 44069,
[Di Mex cord lngh 120V= 10 R, 240V=6 1 44084
EAPC or leakage current detecion interrupter LCDI in
44085
Air-Conditioning
Condenser .
|
Conductors in, outdoor
raceways must be sult
ibe for wet locations
“ho NM cable Switch not to
ie installed
recy behind
AUACS quire 9“ condenser
rah
Central Vacuum 17 NEC
Ti Max 80% nalvidual branch circuit rating, 50% of
‘mutate branch ciruit rating. 422154 8210238
1D Cord eepacity > branch direut eonducter ampacty 409158
5 Bond nomcurent-canying metal parts to EGC 42218C
Electric Furnaces & Space Heaters
D Considered centinuoua load for siting circuit (sive at 12546) _ 424.98
1D Disconnect in sight orlockable breaker or switch F39 424.19
1D Unit switch that opens all ungrounded conductors OK a
494.106
dzcormoct for apace heater with ro moter> Ye ho
Hydromassage Tub (Whirlpool Bathtub)
(D Individual branch rout reed em
D Ready accoasbla GFCI protection ef 880.71
D Allroceptacten within 6 ft. eq GFCI protedion F#9 680.71
D Electrical equipment (pump motor) must be accessibe 980.73
1D Cer & plug connection receptacle mas 12in. tom
hatch eporing & receptacle face in view Fa__80.74
Bend metal piping. surfaces, rcaways, cables, motors & electical devices
Within 5 fof tub & metal pats that contact circulating water P43 _680.74A
Banding condictor min said #8 Ou FAB. 600.4
1D Gennect bonding conductor to mato ug EXC FA 680.748
+ Doubie-reulated motor (natal bond wire for future) a0 744x2
680.45
1 Bonding conductor need rot connect i panelboards.
#8 conductor bonded
to moto: lg Intended
for bonding =
Cord and plug receptacle for motor
placed in rect view through eecess:
Bond to meta piping
‘systems & any grounded
metal paris in contact
‘pening & <12 in. tom opening smn creating waar
Built-in Kitchen Appliances: 17NEC
7 Pala corde (not NM cable) OK for applies
‘conte lst} for fenble cord connection 402,184
422.1681
C) Garbage disposer cords OK min 18 in, mat 96,
[5 Compactor corde 94 Ri, teamited fn back of ape 42} ae)
17) Compactorreceptacis in aoplance space or adacent spice 422 18B9(8)
[51 DW cords 3-85 measured from back a appliance 422 8B)
[L1DW recaptacie upace adjacent tocishwasher 422. 1563(6)"
3 Range hoode cord peg OK i UB for cont prteciod Fam
physica damage & on vidual beach sreut 422.1684
I Range hood coe in 18 mx 48 72 ea
1 Groundog ype pga fo: appharces above ER aaa
222188
+ Lted double-nauated appliances
C1 Cord pig overs & cooking unta OKWLSL 490.4883
Cn An ADD DDD LEER‘WIRE AMPACITY
To determine the comec! wir wee for a given OCPO (kise or broaker), factors such
ax the temperature rating of insulation, ambient temperature, proximity to other
conductors, and function ofthe circuit must all be considored
se the appropn
must be sppled to the empscitylatic in 7
fe coluran THY forthe ype of wie beng used 722.
ee aren
Lay
General 17NEC ribtaet Torres > SONG (i
1 Prec conductor at her ampaiy EXC 1404 | ambient | kecasaets Sorts he Res ee oe
+ Bia ecodioors protected per ote A a TH aoa | tompee Temp
* AC protected AML motors per article 420 240.46 soe 78°C bec
{2 When anpacy boven 2 stared re OCPD OK owe as | ont oor ace | ares
rentanger OOPD nat branch eeu w/t ecb 24048
C. Protect per lowest rated device, terminal, oF wire in citouit. 110.140 3-40 082 088 ost 96-104
Use 6% colin oreandicores #1 rs 100 amps THY 11040) | ayaag } a ae ae
GbeckG ates ec dccrssiosicoeeat Nee,
D. Use 90°C column only for derating conductors rated 90°C T1113 110.140 46-80, 088 0% oe2 Teta
1 Serioe conductor alowed tobe 89% of 11 ampaciy 714. 9101889 | gage] oar a RS
Derating
Apply temperature correction factor T12. _ 910.1582 58-60 = O38 OF 432-140
Ada 30°C w 112 fr cond or cables “Toi abow woe _—aiotsBa" | gicag TS ca? oss | 141-140
bes osunetter ie eines None oe
grouped without spacing > 24 in. in length T13, 910.1538 68-70 ez bd = Se
1 Neural cont x curer-camin cndaton for TIS EX 1018898 [tte empress TO po
+ Neutral of mutwire crcuit or feeder rom 120/240V system 31015836
© Donte>2 NM eae cnet Grbced fl aed perenn
watt spacing coin wh hr on 13 23180
1 Une 80% for dering NM caio;bave OCPD en 6S anpacy—ean.e0 | Number of Cron Canna Wes
“8
c : 5 Zz
we [rc | we [aoe | we | we oe
oe hie 6 wal omen a nays tng ees
a SecP | ieee Uienr:|cager | a9 | cunt camyrg conductors aed stl be within the some the ames aie T2S.
Taw | THN , | Sees
co | mw | Taw rw | xan | uses,
cain) UF | raw | THM2 | TE | ME / tat jaa! [ating | uWire
Use | Tan? Chimps | size(AWeo | size ae | Amps)
rr a
wis |] = |. - | | ws [2 | 10
= |= | = ps [=] = fae woop fe oko | Booked
sw | | = | « 20] a5 | 1 | [A Suede toctarmscayn rps
Late le i |B 2014 NEG metnctedto LIOCMOV wyateme, also atoms 1 BOrRO8N.S*
s a 0 #. # cs & s C Tha table i allowed lex service conductors + main pow feediar that camry the weing
‘[e[«| [of |= |e Hibuetanch oan rang eyes ae RE
ees
woo | 1 | we | :
+1 rts iD re Wire Size AWG) | ruse of | Wire Size (awa),
ae rect
10 130 14 05 100 116 + Brooker cu at reaine: AL
¥ 32
2
“o
0
300
380.
“00ron
DLE aa oat Cd
ETL t Ly
UF Cable
==
UF unable for cry lamp,
cor wet locations; NAT is ony
‘rtable fr dy cations.
(Cable systems ar the most common residential wring methoda. Cables contain ee
al conductors of the circuit nside a protect cuter swath of retl or plastic,
Cable Protection indoors (NM, UF, AC, MC, SE) 17 NEC
1 Bored holes for cable min 114 in. setback from lace
framing mombors or protect w/ steel plate Fad
1 Protect cables in notches wi 1 in. tee pate
©) Cables parate to framing members req min. 1% in, eolback
from eurtace FAS:
00.441
—— 900.449
30040
Cable Stacker
Cables cannot he
placed side by si
Ere ee
‘raming,
Underfloor Cable in Basement or Crawl Space
Nail-Piate Protection
S-conductortg
Deondhctortg
cables
<1 In
A lited onbie tucker
Solves the problem
bunds of cat
bbe within 12 in of
Steel plate
min. rein
‘thick
Clam suitable
for NM or MC
Nt cable connector MC cable clams, |
(no locknut style)
of conductors
Into box,
rin. 3 in. past
‘ace of Box
NM-Nonmetalic Sheathed Cable F47 Nec
rag rami endcocio af ot OOPD
Tok ny can
5 free ea tom sca dager aces
ee ragae pote ta hes woh rt an
i oe mon w/nMrated cy 48 og
5 Seow beige an) pate box OK wl cao eal
only-net allowed in caro wet locations __ 994.1204
00.401
som 14,170)
reesei in of torr Ua sahig ino box —_—__ 8141708
Cl tats atoning ne bos past ee of inp. 2 condictor T21 EXC “224 Gupr 6TH
+ Stmight cond $24. OK to have 6D9G 8 Ghaoer@T1 note 4
[2 Dente conactr in aoordance with 12,1, 21015028
{ Corduciore2 #8 must be standed EXC ‘810.1066
“GEC bonding conductors (9.8 &p.10) woldOK 25062 RIGIEEN FMC-Fiexible Metal Conduit
1 tor of a uncegaund races a wet bcaton 30088
ier a a atv rac rcownye we lsatione iva vt neater _ 800.9 Coes
{ Wetrated conductors cables tin wet baton acenays 310.106 |
Factory coer of ungounded conductors cacnot bo white or reer 310.1 10C
[ Facory col of uta conducts wit, Ce ger EXC 310,110R48
+ Conductor 2 #4 reidetfed et tominstions 81010888
*EGCecanbe baat 1108
2 Beret o have ove rain nis
Mer 360" bende between pull pots Fs Lemc-tiquiatight _LFNC-Liawietight Flexible
{Racoway mast bo reamed smoah ater ating Flexible Metal Condue —-‘Nonmetalic Condult
1 Cordis in racowaye re acy runded
insatng busing wereentngendoeves PuCiacket —Comecor
1 Bow & conduit bd covers must remain accesaita ae
i Racawaya not OK te suppot other eables EXC.
+ Ausocatod costal wing (2g, themostat to AG)
i Metal racewaye & cabo sheathing net OK pass bores \
[Splicing in concut hocks any Hauler vlime permaking —a14 1802 | Cutends of meta itbon mist be trimmed
Too Many Bends
‘taka? connacton
FMC-Flenible Metal Conduit 3) aTNEC
{Not OKin wet locations or subject toconosion or damage 34812
1 Suppor spacing max 4/2. tenal & 12m, rm bores EXS__—_948,.904
Inset pall point such
se acondul body
Total bends + Wheto needed: 38 n. O 6H woatedevny3_—___—__ gm
{Bore amoeth-conot rece inn —REb20A C1 Secug win 12 nd etoapt uplo SOK hese 9580.
{Be ct nd o removed rough 08908 9S) cone ang connect
ExPomited s EGC EXC wom DEGCredt
“+ EMT on root serving AC equipn ay gy \ \ YVR VV VO17NEC — PVC-Rigid Polyvinyl Chloride Conduit F58 7NEC
1 Cover above buted conduits par 1 300.54
tring mod hat allows
RMC-Rigid Metal Conduit F57
{Galvanized RMC OK for drwct burial or embbedment w/
approved eorroaion potection 944.1081 Ol Support por T17 with
D1 Where exposed to meisture,feld cut Fe threads req LAL compound 900.64 ovement from themal expansien & contraction 982.00
1D Provieo bushing er fiting at box connction F87 344.48 (7 Horizontal run supported by holes in faming OX if securaly
loss connectors not OK on threaded condut ends 944.49 faatened within 3. of box, condi tody, or cabinat 352908
— 98248
Othe
Z Seoure in place within 3 f. of termi
7 Bushings or adaptors req'd to provent wre abrasion,
nEXC. 34401
1 Smoothly rounded insulating bushings req'd or conductors 2 #4 3004G,
= LOK where suc members proven ‘siening win 844.9082
1 Horizontal ure aupportod by hale in raning OK ecarly Expansion toga rog if alc 7 mevamen T20 — 0240
fastened within Sf ob, cond body oF cabinet 344308 Not OK fr wppat fines or bax 382198
{Horna suppor sping w/ headed ceuplngs 17 344.9082 Not parted in envionment > 50% (12277) 362120
: i 8 DISTANCE AT WHICH PVC CONDUIT REG
Moved) etna dablecd
EUMMMCUTCECNEEM Pucttene) cance | ects) Datace | uerters] 0
IMC/RMCSize | Max Spacing | PYCSze | MaxSpacing | | Chanae'F|_t-m) | Ghorge’™*| facia) | Change] _(e-h)
awn [08 inet 3h 4o_| 15-5 [oo [7-9 [00 [eee
tin 12 5h e-10 | 190 | 4-9
(wetweae mn wo [tase
I 2v 168 7h | a. 5
| a aoe
Peo
rani Conduit Fill Examples
ses ane rare)
[i [sar 163 mee condo tobe 40% of az [sox [ews [ores [ins ae
2 or =] thoconait ren yi as
10 oma] = Acieuithas 9 #2 conductors [_%_[asaajoate]axzr]aras [osas atar| ass
[ss ‘casse | eus | 1 #8 EGC, all with THEN inoula: ‘% [ears [oase|eara] cave [oars [aaa] oaa0| area [aoa]
0807 toe Re, Rat ae 720 Shania 298 + [o34e|03x3[0:227] 034s |a3e2/0.84] 038s] 0.278 [asa]
cor | ee yee TeHneo11504q n, |_iltlfosseltsei ast enim antes onro) oes)one)
= Fostis gettin cossoreain, [1 [0sta|a7s4]a7es) o7e2 [ase [asso] 079) anes axed
ssa svorsecoaer con, | 8) tawal eel soe ane eer tase) aon reo ie
ci —| 1 x0.0s07 00807 aan | 24 [2sea] — [rges] waa] — [asd tesa) x57 ar
he Total min wea = 0.9981 99, 3 [ssse[ - [2ez7)200/ - [3160/3000] 2577] 2007]
yania | Fon 72%, thenot lager sce tx PvCA0 | ata [ate] — [aa4a/aana| — |4a04)4ane| ans a
[nari] 20581 25.0, terre tein const (fsa) arm | faa ta aac neal
23421] or G0 np copys eee nT 18 sale — | — [oss 422504
ae Teac iat dat a
Pee cd
| Sit | es | ccitina| fer | ckvawwa | GRO _| pene ie a
Fete pete a
a
I =
er
é vows | Somer