VRV Electrical Requirement

The document provides specifications for various indoor unit models that are compatible with Daikin VRV-X systems, including cassette, duct, wall-mounted, and floor units. It lists the model, voltage, power consumption, fan power, and recommended circuit breaker and cable sizes for proper installation of each unit. Recommended power supply for the indoor units is 1-phase + neutral, 240VAC, 50Hz electrical system with earthing and an independent distribution board.

Uploaded by

ShrenikShah
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (2 votes)
3K views6 pages

VRV Electrical Requirement

The document provides specifications for various indoor unit models that are compatible with Daikin VRV-X systems, including cassette, duct, wall-mounted, and floor units. It lists the model, voltage, power consumption, fan power, and recommended circuit breaker and cable sizes for proper installation of each unit. Recommended power supply for the indoor units is 1-phase + neutral, 240VAC, 50Hz electrical system with earthing and an independent distribution board.

Uploaded by

ShrenikShah
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

DAIKIN VRV-X INDOOR UNITS

RECOMMONDED POWER SUPPLY IS 1PH + N , 240 VAC , 50Hz. WITH EARTHING.


PROVIDE INDEPENDENT DB PANEL FOR VRV INDOOR UNITS.
EARTH LEAKAGE CKT. BRAKER 300mA PER PHASE IS MANDATORY.

FXCQ -AVM CEILING MOUNTED DOUBLE FLOW CASSETTE UNIT

SR NO MODEL VOLTAGE M C A IFM(kw) F L A Watts MCB Cable size


1 FXCQ20AVM 0.3 0.056 0.2 31 6 Amps 3C X 1.5 sq.mm.
2 FXCQ25AVM 0.3 0.056 0.2 39 6 Amps 3C X 1.5 sq.mm.
3 FXCQ32AVM 0.3 0.056 0.2 39 6 Amps 3C X 1.5 sq.mm.
4 FXCQ40AVM 0.3 0.056 0.2 41 6 Amps 3C X 1.5 sq.mm.
5 FXCQ50AVM 220 ~ 240 0.4 0.056 0.3 59 6 Amps 3C X 1.5 sq.mm.
6 FXCQ63AVM 0.5 0.106 0.4 63 6 Amps 3C X 1.5 sq.mm.
0.056
7 FXCQ80AVM 0.6 0.5 90 6 Amps 3C X 1.5 sq.mm.
+0.056
0.106
8 FXCQ125AVM 1.1 0.9 149 6 Amps 3C X 1.5 sq.mm.
+0.106

FXFSQ- ARV16 CEILING MOUNTED MULTIFLOW CASSETTE UNIT

SR NO MODEL VOLTAGE M C A IFM(kw) F L A Watts MCB Cable size


1 FXFSQ25ARV16 0.3 0.053 0.2 28 6 amps 3C X 1.5 sq.mm.
2 FXFSQ32ARV16 0.3 0.053 0.2 28 6 amps 3C X 1.5 sq.mm.
3 FXFSQ40ARV16 0.4 0.053 0.3 35 6 amps 3C X 1.5 sq.mm.
4 FXFSQ50ARV16 0.6 0.053 0.3 56 6 amps 3C X 1.5 sq.mm.
5 FXFSQ63ARV16 220~240 0.6 0.053 0.5 61 6 amps 3C X 1.5 sq.mm.
6 FXFSQ80ARV16 1.0 0.053 0.8 92 6 amps 3C X 1.5 sq.mm.
7 FXFSQ100ARV16 1.4 0.106 1.1 164 6 amps 3C X 1.5 sq.mm.
8 FXFSQ125ARV16 1.6 0.106 1.3 170 6 amps 3C X 1.5 sq.mm.
9 FXFSQ140ARV16 1.8 0.106 1.4 194 6 amps 3C X 1.5 sq.mm.

FXZQ-MVE9 CEILING MOUNTED COMPACT CASSETTE UNIT

SR NO MODEL VOLTAGE M C A IFM(kw) F L A Watts MCB Cable size


1 FXZQ20AVM 0.3 0.2 0.6 43 6 Amps 3C X 1.5 sq.mm.
2 FXZQ25AVM 0.3 0.2 0.6 43 6 Amps 3C X 1.5 sq.mm.
3 FXZQ32AVM 220~240 0.4 0.3 0.6 45 6 Amps 3C X 1.5 sq.mm.
4 FXZQ40AVM 0.4 0.3 0.6 59 6 Amps 3C X 1.5 sq.mm.
5 FXZQ50AVM 0.6 0.5 0.7 92 6 Amps 3C X 1.5 sq.mm.

FXEQ-AV36 CEILING MOUNTED CASSETTE CORNER UNIT

SR NO MODEL VOLTAGE M C A IFM(kw) F L A Watts MCB Cable size


1 FXEQ20AV36 0.3 0.087 0.2 26 6 amps 3C X 1.5 sq.mm.
2 FXEQ25AV36 0.4 0.087 0.3 27 6 amps 3C X 1.5 sq.mm.
3 FXEQ32AV36 0.4 0.087 0.3 34 6 amps 3C X 1.5 sq.mm.
220~240
4 FXEQ40AV36 0.5 0.087 0.4 46 6 amps 3C X 1.5 sq.mm.
5 FXEQ50AV36 0.5 0.117 0.4 48 6 amps 3C X 1.5 sq.mm.
6 FXEQ63AV36 0.7 0.117 0.5 67 6 amps 3C X 1.5 sq.mm.

FXDQ-PDV,FXDQ-NDV SLIM CEILING MOUNTED DUCT TYPE


SR NO MODEL VOLTAGE M C A IFM(kw) F L A Watts MCB Cable size
1 FXDQ20PDV36 0.8 0.055 0.6 86 6 amps 3C X 1.5 sq.mm.
2 FXDQ25PDV36 0.8 0.055 0.6 86 6 amps 3C X 1.5 sq.mm.
3 FXDQ32PDV36 0.8 0.055 0.6 89 6 amps 3C X 1.5 sq.mm.
220~240
4 FXDQ40NDV36 1 0.055 0.8 160 6 amps 3C X 1.5 sq.mm.
5 FXDQ50NDV36 1 0.085 0.8 165 6 amps 3C X 1.5 sq.mm.
6 FXDQ63NDV36 1.1 0.085 0.9 181 6 amps 3C X 1.5 sq.mm.

FXUQ –AVEB FOUR WAY FLOW CEILING SUSPENDED TYPE

SR NO MODEL VOLTAGE M C A IFM(kw) F L A Watts MCB Cable size


1 FXUQ71AVEB 0.6 0.046 0.5 90 6 amps 3C X 1.5 sq.mm.
220~240
2 FXUQ100AVEB 1.4 0.106 1.1 200 6 amps 3C X 1.5 sq.mm.

FXHQ –MAVE CEILING SUSPENDED TYPE

SR NO MODEL VOLTAGE M C A IFM(kw) F L A Watts MCB Cable size


1 FXHQ32MAVE 0.8 0.062 0.6 111 6 amps 3C X 1.5 sq.mm.
2 FXHQ63MAVE 0.8 0.062 0.6 115 6 amps 3C X 1.5 sq.mm.
3 FXHQ100MAVE 220~240 0.9 0.132 0.7 135 6 amps 3C X 1.5 sq.mm.
4 FXHQ125AVM 1.4 0.15 1 168 6 amps 3C X 1.5 sq.mm.
5 FXHQ140AVM 1.4 0.15 1 181 6 amps 3C X 1.5 sq.mm.

FXMQ-PVE, FXMQ-PBV36 CEILING MOUNTED DUCT TYPE UNIT

SR NO MODEL VOLTAGE M C A IFM(kw) F L A Watts MCB Cable size


1 FXMQ20PVE 0.6 0.09 0.5 81 6 amps 3C X 1.5 sq.mm.
2 FXMQ25PVE 0.6 0.09 0.5 81 6 amps 3C X 1.5 sq.mm.
3 FXMQ32PVE 0.6 0.09 0.5 85 6 amps 3C X 1.5 sq.mm.
4 FXMQ40PBV36 1.4 0.14 1.1 194 6 amps 3C X 1.5 sq.mm.
5 FXMQ50PBV36 1.6 0.35 1.3 215 6 amps 3C X 1.5 sq.mm.
220~240
6 FXMQ63PBV36 1.8 0.35 1.4 230 6 amps 3C X 1.5 sq.mm.
7 FXMQ80PBV36 2.3 0.35 1.8 298 6 amps 3C X 1.5 sq.mm.
8 FXMQ100PBV36 2.9 0.35 2.3 376 6 amps 3C X 1.5 sq.mm.
9 FXMQ125PBV36 3.4 0.35 2.7 461 6 amps 3C X 1.5 sq.mm.
10 FXMQ140PBV36 3.4 0.35 2.7 461 6 amps 3C X 1.5 sq.mm.

FXMQ-ARV16 CEILING MOUNTED DUCT TYPE UNIT

SR NO MODEL VOLTAGE M C A IFM(kw) F L A Watts MCB Cable size


1 FXMQ40ARV16 0.8 0.055 0.65 160 6 amps 3C X 1.5 sq.mm.
2 FXMQ50ARV16 1.0 0.08 0.83 185 6 amps 3C X 1.5 sq.mm.
3 FXMQ63ARV16 220~240 1.2 0.1 0.92 210 6 amps 3C X 1.5 sq.mm.
4 FXMQ80ARV16 1.6 0.13 1.3 300 6 amps 3C X 1.5 sq.mm.
5 FXMQ100ARV16 1.6 0.18 1.3 345 6 amps 3C X 1.5 sq.mm.

FXMQ-NVE6 CEILING MOUNTED DUCT TYPE UNIT

SR NO MODEL VOLTAGE M C A IFM(kw) F L A Watts MCB Cable size


1 FXMQ170NVE6 4.9 0.375X1 3.0 900 15 amps 3C X 1.5 sq.mm.
2 FXMQ200NVE6 220~240 8.2 0.75X1 6.3 1100 15 amps 3C X 1.5 sq.mm.
3 FXMQ250NVE6 10.9 0.45X2 9.0 1650 15 amps 3C X 2.5 sq.mm.
FXAQ – ARVE6 WALL MOUNTED TYPE UNIT

SR NO MODEL VOLTAGE M C A IFM(kw) F L A Watts MCB Cable size


1 FXAQ20ARVE6 0.3 0.04 0.2 17 6 amps 3C X 1.5 sq.mm.
2 FXAQ25ARVE6 0.4 0.04 0.3 19 6 amps 3C X 1.5 sq.mm.
3 FXAQ32ARVE6 0.4 0.04 0.3 21 6 amps 3C X 1.5 sq.mm.
220~240
4 FXAQ40ARVE6 0.4 0.04 0.3 22 6 amps 3C X 1.5 sq.mm.
5 FXAQ50ARVE6 0.5 0.04 0.4 27 6 amps 3C X 1.5 sq.mm.
6 FXAQ63ARVE6 0.7 0.048 0.5 56 6 amps 3C X 1.5 sq.mm.

FXLQ-MAVE8 / FXNQ–MAVE8 FLOOR & CONCELLED TYPE UNIT

SR NO MODEL VOLTAGE M C A IFM(kw) F L A Watts MCB Cable size


1 FXLQ/FXNQ20MAVE 0.3 0.015 0.2 49 6 amps 3C X 1.5 sq.mm.
2 FXLQ/FXNQ25MAVE 0.3 0.015 0.2 49 6 amps 3C X 1.5 sq.mm.
3 FXLQ/FXNQ32MAVE 0.6 0.025 0.5 90 6 amps 3C X 1.5 sq.mm.
220~240
4 FXLQ/FXNQ40MAVE 0.6 0.025 0.5 90 6 amps 3C X 1.5 sq.mm.
5 FXLQ/FXNQ50MAVE 0.6 0.035 0.5 110 6 amps 3C X 1.5 sq.mm.
6 FXLQ/FXNQ63MAVE 0.6 0.035 0.5 110 6 amps 3C X 1.5 sq.mm.

FXB(P)Q –P OUTDOOR AIR PROCESSING UNIT

SR NO MODEL VOLTAGE M C A IFM(kw) F L A Watts MCB Cable size


1 FXBQ40PVE 1.8 0.16 1.4 310 06 Amps 3C X 1.5 sq.mm.
2 FXBQ50PVE 1.8 0.16 1.4 310 06 Amps 3C X 1.5 sq.mm.
220~240
3 FXBQ63PVE 2.4 0.22 1.9 450 06 Amps 3C X 1.5 sq.mm.
4 FXBPQ63PVE 2.4 0.22 1.9 450 06 Amps 3C X 1.5 sq.mm.

RECOMMONDED POWER SUPPLY IS 3PH + N , 380V to 415V , 50Hz. WITH EARTHING.


PROVIDE INDEPENDENT DB PANEL FOR VRV INDOOR UNITS.
EARTH LEAKAGE CKT. BRAKER 300mA PER PHASE IS MANDATORY.

FXVQ-NY1 FLOOR STANDING DUCT TYPE UNIT

SR NO MODEL VOLTAGE M C A IFM(kw) F L A Watts MCB Cable size


1 FXVQ125NY1 2.5 0.75 2 530 16 amps 4C X 2.5 Sq.mm.
2 FXVQ200NY1 4.4 1.5 3.5 1330 16 amps 4C X 2.5 Sq.mm.
3 FXVQ250NY1 380~415 4.4 1.5 3.5 1610 16 amps 4C X 2.5 Sq.mm.
4 FXVQ400NY1 9 3.7 7.9 3970 25 amps 4C X 4 Sq.mm.
5 FXVQ500NY16 13.6 5.5 10.9 5250 32 amps 4C X 4 Sq.mm.

MCA : MINIMUM CIRCUIT AMPS. FLA : FULL LOAD AMPS.


MFA : MAX FUSE AMPS.
IFM : FAN MOTOR RATED OUTPUT KW.

PLEASE NOTE THE ABOVE DATA IS IN DESIGN CONDITIONS


NOTE:-1. Max. allowable voltage unbalance between phases is 2%
2. MCA= 1.25 X FLA
MFA ≤ 4 X FLA
3. Select wire size based on the MCA
4. Instead of fuse, use circuit breaker based on MFA
ELECTRICAL POWER REQUIREMENT FOR DAIKIN VRV S OUTDOOR UNITS

EARTH LEAKAGE CKT. BRAKER 300mA FOR EACH ODU IS MANDATORY.


Nominal size of
ELCB
MCA @ MCB Cu conductor,
CONECTED (Amp)
Design (Amp) XLPE insulated Power supply
SR. NO. MODEL LOAD (300mA,-
Condition Pole armoured
Pole)
cables
KW Amps. Amps. Amps. SQ. MM. Volts
1 RXYRQ4ARV16 4.5 16.5 25 25 4 RECOMMONDED POWER
2 RXYRQ5ARV16 5.5 16.5 25 25 4 SUPPLY IS 1PH + N, 240 VAC,
3 RXYRQ6ARV16 6.6 27 32 32 6 50Hz. WITH EARTHING.

NOTE:-
1. Max. allowable voltage variation between phase is 2%
SYMBOLS:-
MCA:- Min. circuit amps.
Safety Measures
1) Time delay of atleast 20 seconds is required in between power switchovers. In case
2) Auto phase change over switch should be installed in main panel to automatically change the phase sequence and
to avoid tripping of outdoor units in case of power switchovers
ELECTRICAL POWER REQUIREMENT FOR DAIKIN VRV S OUTDOOR UNITS

EARTH LEAKAGE CKT. BRAKER 300mA FOR EACH ODU IS MANDATORY.


Nominal size of
ELCB
MCA @ MCB Cu conductor,
CONECTED (Amp)
Design (Amp) XLPE insulated Power supply
SR. NO. MODEL LOAD (300mA,-
Condition Pole armoured
Pole)
cables
KW Amps. Amps. Amps. SQ. MM. Volts
1 RXYQ4ARV16 4.5 16.5 25 25 4 RECOMMONDED POWER
2 RXYQ5ARV16 5.5 27 32 32 4 SUPPLY IS 1PH + N, 240 VAC,
3 RXYMQ6ARV16 6.6 27 32 32 6 50Hz. WITH EARTHING.
4 RXYMQ8ARY16 8.8 18.9 25 25 4 RECOMMONDED POWER
5 RXYMQ10ARY16 11 22 25 25 6 SUPPLY IS 3PH + N, 415 VAC,
6 RXYMQ12ARY16 13.2 24 32 32 6 50Hz. WITH EARTHING.

NOTE:-
1. Max. aloowable voltage variation between phase is 2%
SYMBOLS:-
MCA:- Min. circuit amps.
Safety Measures
1) Time delay of atleast 20 seconds is required in between power switchovers. In case
2) Auto phase change over switch should be installed in main panel to automatically change the phase sequence and
to avoid tripping of outdoor units in case of power switchovers
ELECTRICAL POWER REQUIREMENT FOR DAIKIN VRV X OUTDOOR UNITS

RECOMMONDED POWER SUPPLY IS 3PH + N, 380 – 415 VAC, 50Hz. WITH EARTHING.
EARTH LEAKAGE CKT. BRAKER 300mA FOR EACH ODU IS MANDATORY.
Nominal size of
Cu conductor,
MCA @ Design MCB (Amp) ELCB (Amp)
CONECTED LOAD 4core XLPE
SR. NO. MODEL Condition 4 Pole (300mA,4-Pole)
insulated
armoured cables
KW Amps. Amps. Amps. SQ. MM.
1 RXYQ6ARY6 6.6 16.1 20 25 4
2 RXYQ8ARY6 8.8 16.1 20 25 4
3 RXYQ10ARY6 11 21.2 25 25 6
4 RXYQ12ARY6 13.2 22.5 25 25 6
5 RXYQ14ARY6 15.4 26.9 32 32 6
6 RXYQ16ARY6 17.6 30.2 40 40 10
7 RXYQ18ARY6 19.8 30.2 40 40 10
8 RXYQ20ARY6 22 38.9 63 63 10

NOTE:-
1. Max. aloowable voltage variation between phase is 2%
SYMBOLS:-
MCA:- Min. circuit amps.
Safety Measures
1) Time delay of atleast 20 seconds is required in between power switchovers. In case time delay is not possible reverse
2) Auto phase change over switch should be installed in main panel to automatically change the phase sequence and
to avoid tripping of outdoor units in case of power switchovers