80% found this document useful (5 votes)
2K views2 pages

Earthing System Design Guide

This document provides calculations for an underground earthing system for a 415V system. It calculates: 1) The size of earth conductors using fault current levels and temperature rise equations, selecting 75x10mm galvanized steel flat. 2) The grid resistance using conductor layout and soil resistivity, calculating 0.798 ohms. 3) The number of earth electrodes needed to achieve a combined resistance below 1 ohm, selecting 28 pipe electrodes. 4) The resistance of each electrode and their combined earth resistance of 0.438 ohms, below the target of 1 ohm.

Uploaded by

aswinikannan0998
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
80% found this document useful (5 votes)
2K views2 pages

Earthing System Design Guide

This document provides calculations for an underground earthing system for a 415V system. It calculates: 1) The size of earth conductors using fault current levels and temperature rise equations, selecting 75x10mm galvanized steel flat. 2) The grid resistance using conductor layout and soil resistivity, calculating 0.798 ohms. 3) The number of earth electrodes needed to achieve a combined resistance below 1 ohm, selecting 28 pipe electrodes. 4) The resistance of each electrode and their combined earth resistance of 0.438 ohms, below the target of 1 ohm.

Uploaded by

aswinikannan0998
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

PLANT BELOW GROUND EARTHING CALCULATION

1.0 INTRODUCTION:
Earthing system is installed in such a manner that it will limit the effect of ground potential gradients
to such a voltage & current level that it will not endanger the safety of people or equipment under normal &
fault conditions as well as assure the continuity of service.

2.0 DESIGN BASIS:

CODES & STANDARDS

IS: 3043 : Code of Practice for earthing


IS: 2309 : Code of Practice for the Protection of building & Allied Structures against Lightning.
IEEE: 665 : IEEE guide for safety in Generating Station grounding.
IEEE: 80 : IEEE guide for safety in AC substation grounding.
CBIP manual on substation

System Earthing adopted at various voltage levels is as follows:-

11KV System : Non-effectively grounded


415V System : Effectively grounded
230V AC System : Effectively grounded
110V DC System : Ungrounded

As solidly /effectively grounded system produce higher fault current thus 415V system are considered for
earthing design.

System fault levels shall be considered as

11KV System : 40KA for 3Sec


415V System : 50KA for 1Sec
230V AC System : 25KA for 1Sec
110V DC System : 25KA for 1Sec

3.0 CALCUALTION:

3.1 Size of Earth Conductor


The following factors are considered in earthing design:
(i) Duration of fault current for earth-mat sizing (t): 1 sec
(ii) Conductor type for buried earth mat & risers: Zinc Coated Steel flat

Earthing conductor size is calculated using following equation as per IS:3043


Ix√t
Minimum size, A =
K
Where,
A : Area Cross Section area in mm
I : Value (ac, rms) of fault current for a fault of negligible impedance which can flow
through the prospective device, in Amp – 50KA
t : Operation time of the disconnecting device in sec. – 1 sec.
K : factor dependent on the material of the protective conductor, theinsulation and other
parts and the intial & final temperature.Value of K for protective, steel Conductor.
Qc : Voltmetric heat capacity of Conductor material (j/°C mm3 ) – 3.8x10-3 for steel Table
5 of IS : 3043
B : reciprocal of temperature coefficient of resistivity at 0°C forconductor (°C) 202°C for
Steel Table 5 of IS:3043
δ20 : Electricity resistivity of conductor Material at 20C (Ω mm)–138 x 10-6 (Ω mm) for
steel Table 5 of IS: 3043
θ1 : initial temperature of conductor (°C) - 50°C
θt : Final temperature of conductor (°C) - 620°C (for Welded joint)

I = 50000
Ki = Sq.Root ((QC (B+20) / S20) = 78
Qc = 0.0038
B = 202
δ20 = 0.00014
78.19

K = Ki * ln (1 + (θt-θ1)
(B+θ1)

Where, K = 78 ln (1 + (620-50)
(202+50)
θt = 620

θ1 = 50
K = 85.0148
A = (Ix√t) / K
= 588.133 mm2

1
= 588 mm2
As per CBIP manual no corrosion allowance is required for steel having corrosion resistance coating.
Required conductor Size = 588 mm2
= 75 x 10 mm
Hence, 75 X 10 mm Galvanized Steel flat is selected for buried earthmat.

3.2 Resistance of Earth Grid


The value of the grid resistance to remote earth (Rg) can be calculated using the following equation:

Rg = p * ( (1/L)+ (1/20A)1/2 x ((1+1/(1+ h X (20/A)1/2)))


Where,
p , Soil resistivity in Ωm = 100
L, Length of buried conductor (M) = 694.713
2
A, Area occupied by conductor in m = 4492.058
H, Depth of buried conductor (M) = 0.6

Rg = 100 * ( (1/552.748)+ (1/20x4130.229)^(1/2) x ((1+1/(1+ 0.6 X (20/4130.229A)^(1/2))))


= 0.79836 Ω

3.3 Number of Earth Electrodes

3.3.1 Resistance of each pipe Electrode


The value of the resistance of each Pipe Electrode (Rp) can be calculated using the following equation
as per IS: 3043
100ρ x ln 4L
Rp =
2πL d
Where,
p , Soil resistivity in Ωm = 100
L, Length of electrode in cm = 275
d, Diameter of electrode in cm = 10
100x100 x ln 4x275
Rp =
2πx275 10
= 27.22 ohms

3.3.2 Resistance of each strip Electrode

Rs
= 100 x ρ ln 2 x Ls2
2 x 3.14 x Ls wt

Where,
p , Soil resistivity in Ωm = 100
L, Length of strip in cm = 69471.3
t, Width of the strip in cm = 7.5
W, Depth of burial in cm = 60
100x100 x ln 2x55274.82
Rs =
2πx55274.8 60x7.5
= 0.39 ohms
3.3.3 Total number of Pipe Electrode required for Grid resistance

N = (Rp X Rs)-(Rg X Rp)

Rs - Rg
Net Earth resistance R in ohms = 27.218

= 28 Nos
3.4 Resistance of Earth Electrode (Re)

= 1 (100 x E x ln (4L/d)
Re
n 2πL
Where,
n, No of earth pits = 28
L, Length of strip in cm = 275
d, Dia of electrode in cm = 10
E , Soil resistivity in Ωm 100
= 1 (100 x 100 x ln (4x275/10)
Re
28 2πx275

= 0.97 ohms
3.5 Combined Resistance

Re X Rg
Net Earth resistance R in ohms =
Re + Rg

0.86 x 0.97
Net Earth resistance R in ohms =
0.86+0.97
= 0.438 ohms

This is less than the CEIG stipulated value of 1 Ohm

Remarks:
1 Material constant used here is as per IS 3043- 1987 only (considering Non hazardous area)
In this revision only resistance vaules of the electrodes will slightly vary from Rev:01. because of using log formula
2 instead of ln formula.
3 For fault level calculation here we are attaching short circuit analysis and reference.

You might also like