0 ratings0% found this document useful (0 votes) 303 views24 pagesLecture 10
Electrical Related documents
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content,
claim it here.
Available Formats
Download as PDF or read online on Scribd
Protection and Switchgear 5-23 Generator Protection
5.13 Negative Sequence Relays
The negative relays are also called phase unbalance relays because these relays
provide protection against negative sequence component of unbalanced currents
existing due to unbalanced loads or phase-phase faults, The unbalanced currents are
dangerous from generators and motors paint of view as these currents can cause
overheating. Negative sequence relays are gene
gene
ly used to give protection to
tors and motors against unbalanced currents.
A negative sequence relay has a filter circuit which is operative only for negative
sequence components. Low order of over current also can cause dangerous situations
hence a negative sequence relay has low current settings. The earth relay provides
protection for phase to earth fault but mot for phase to phase fault. A negative
sequence relay provides protection against phase to phase faults which are responsible
to produce negative sequence components.
The Fig, 5.16 shows the schematic arrangement of negative phase sequence relay
Fig. 5.16 Negative phase sequence relayProtection and Switchgear 5-24 Generator Protection
Basically it consists of a resistance bridge network. The magnitudes of the
impedances of all the branches of the network are equal. The impedances Z, and Zs
and reactance. The currents in the branches Z; and Z, lag by 60° from the currents in
the branches Z; and Z;. The vertical branch B-D consists of inverse time characteristics.
relay, The relay has negligible impedance.
The current I, gets divided
into two equal parts [, and Is. And
I, lags I, by 60° The phasor
diagram is shown in the Fig. 5.17
Tat; = ip
Let
The perpendicular is drawn
from point A on the diagonal
meeting it at point B, as shown in
the Fig. 5.17. This bisects the
Fig. 5.17 diagonal,
OB =
Now in triangle OAB,
OB
cos 8 = OK
BL
2 I
b= Beheh
Now I, leads Ip by 30° while I; lags Ip by 30°
Similarly the current Ip gets divided into two equal parts 1, and 1, The current ly
lags 1, by 60°. From equation (1) we can write,
1
ma hele @
3
The current 1, leads Iz by 30° while current I; lags Ip by 30°
The current entering the relay at the junction point B in the Fig. 5.16 is the vector
sum of Ij, 1) and TyProtection and Switchgear 5-25 Generator Protection
I 1
= Ty + -& (leads I, by 309) + —E (lags I, by
ly a" 304 yg (aes Ie 304
The vector sum is shown in the Fig. 5.18 when the load is balanced and no
negative sequence currents exist,
hes
) C. T. secondary currents
Fig. 5.18
It can be seen from the Fig. 5.18 that,
ith
itty hy
=0
Thus the current entering the relay at point B is vero. Similarly the resultant
current at junction D is also zero. Thus the relay is inoperative for a balanced system.
Now consider that there is unbalanced load on generator or motor due to which
negative sequence currents exist, The phase sequence of C.T. secondary currents is as
shown in the Fig. 5.19 (a). The vector diagram of I, [, and ly is shown in the
Fig. 5.19 (b) under this condition.
The components I, and 1; are equal and opposite to each other at the junction
point B. Hence |, and 1; cancel each other. Now the relay coil carries the current ly
and when this current is more than a predetermined value, the relay trips closing the
contacts of trip circuit which opens the circuit breaker.Protection and Switchgear 5-26 Generator Protection
(a) €.7. secondary currents (b) Vector sum
Fig. 5.19 Negative sequence currents
Zero Sequence Currents : The zero sequence components of secondary currents
are shown in the Fig. 5.20 (a). We know that,
Fa by be le ly
/
{
ty ly fa ty
fa) f(b) fe) (@)
Fig. 5.20 Zero sequence currents
ip = Rely
iy = Hel
These sums are shown in the Fig. 5.20 (b) and (c), It can be seen from the
Fig. 5.20 (d) that,
Ty in phase with ly
The total current through relay is +1; +17. Thus under zero sequence currents
the total current of twice the zero sequence current flows through the relay, Hence the
rates to open the circuit breakerProtection and Switchgear $-27 Generator Protection
To make the relay sensitive to only
negative sequence currents by making it
inoperative under the influence of zero
sequence currents is possible by
connecting the current transformers in
delta as shown in the F 5.21, Under
del nsf
no zero sequence current can flow in the
connection of curre
network,
Fig. 5.21 Delta connection of C.T.s
5.13.1 Induction Type Negative Sequence Relay
Another commonly used negative sequence relay is induction type. Its construction
is similar to that of induction type over current relay. The schematic diagram of this
type of relay is shown in the Fig. 5.22
Fig. 5.22 Induction type negative sequence relay
The central limb of upper magnet carries the primary which has a centre tap. Due
to this, the primary winding has three terminal 1, 2, and 3. The section 1
energized from the secondary of an auxiliary transformer to R-phase. The section 2
is directly energized from the Y-phase current
The auxiliary transformer is a special device having an air gap in its magnetic
circuit: With the help of this, the phase angle between its primary and secondary canProtection and Switchgear 5-28 Generator Protection
be easily adjusted. In practice it is adjusted such that output current lags by 120°
rather than usual 180° feom the input.
So, Ix = Input current of auxiliary transformer
Ij = Output current of auxiliary transformer
and
lags In by 120°
Hene
the relay primary carries the current which is phase difference of Ip; and 1,
Positive Sequence Currents
‘The CT. secondary currents are shown in the
Fig, 5.23 (a). The Fig. 5.23 (b) shows the position of vector fy; lagging Ix by 120° The
Fig. 5.23 (c) shows the vector sum of Ip, and = ly.
The phase difference of Ty, and ly is the vector sum of Igy and - ly. It can seen
from the Fig, 5.23 (c) that the resultant is zero. Thus the relay primary current is zero
and relay is inoperative for positive sequence currents.
Is
(a) 6.1. secondary currents (b} Current Ip,
(0) Relay current
Fig, 5.23 Positive sequence currents.Protection and Switchgear 5-29 Generator Protection
@ shown in the
egative sequence currents : The CT. secondary currents
Fig. 5.24 {a). The Fig. 524 (b) shows the position of
Fig. 5.24 (c) shows the vector difference of Igy and ly whi
lagging I, by 120° The
h is the relay current
Under negative sequence currents, the vector difference of Igy and ly results into a
current | as shown in the Fig. 5.24 (c). This current I flows through the primary coil
of the relay
(a) C.T. secondary currents (b) Current lay
(¢) Relay current
Fig, 5.24 Negative sequence currents
Under the influence of current L the relay operates. The dise ro
trip contacts and it opens the circuit breaker.
tes to close the
This relay is inoperative for zero phase sequence currents, But the relay can be
made operative for the flow of zero sequence currents also by providing an additional
winding on the central limb of the upper magnet of the relay. This winding is
connected in the residual circuit of the three line C-T.s. This relay is called induction
type negative and zero sequence felay.Protection and Switchgear 5-30 Generator Protection
The schematic arrangement of induction type negative and zero sequence relay is
shawn in the Fig, 5.25.
Fig. 5.25 Induction type negative and zero sequence reli
5.14 Protection Against Unbalanced Loading
When the load on the generator becomes unbalanced, negative phase sequence
currents flow, The negative sequence components produce a rotating magnetic field
which rotates at synchronous speed in a direction opposite to the direction of rotor
ficld. Hence effectively the relative speed between the two is double the synchronous
speed. Thus double frequency currents are induced. in the rotor, These currents cause
severe heating of the rotor and can cause damage to the roter. The unbalanced stator
currents also cause severe vibrations and heating of stator. Hence it is necessary to
provide the negative sequence protection to the generators against the unbalanced
load conditions
The negative phase sequence filter alongwith the overcurrent relay provides the
necessary protection against the unbalanced loads
The relative asymmetry of a three phase generator is given by the ratio of negative
sequence current to the rated current. Mathematically it can be expressed as,
%S = «100
where % S = percentage asymmetry
J, = Negative sequence current
1 = Rated currentProtection and Switchgear $-31 Generator Protection
The negative sequence protection scheme is shown in the Fig. 5.26.
Generwtor
stator winding
Roiny
Fig. 5.26 Negative sequence protection
A negative phase sequence filter is connected to the secondaries of the current
transformers. A negative phase sequence filter consists of resistors and inductors.
‘These are so artanged that under normal operating conditions, the relay is inoperative.
The filter cireuit is stable for the symmetrical overloads up to about three times the
rated full load,
When unbalanced load occurs, the negative phase sequence filter circuit produces
an output proportional to the negative phase sequence components. This is directed
through the relay coil. Hence the relay operates to open the circuit breaker to isolate
the generator.
Examples with Solutions
imp Example 5.3: The neutral point of a 11 kV alternator is earthed through a resistance
of 12 $2, the relay ts set to operate when there is out of balance current of 0.8 A. The
CTs have a ratio of 2005. What percentage of the winding is pratected against carth
faults. What must be the minimum value of eartiung resistance required to give 90% of
protection to encis piuase ?Protection and Switchgear 5-32 Generator Protection
Solution ; The given values are,
Vo= kV OR
2 — CT. ratio = 2000/5
i, = relay current = 03 A
L, = minimum operating line current (CT. primary)
2000. . 0.8» 2000
tg x20 9.80200
= 220A
V = line to neutral volta; = My
ar)
= = 6350.8529 V
. Ri, _ 12320
Winding unprotected *100 = Bea epg
= 046%
% Winding protected = 100 ~ 6046 = 39.53 %
Thus with R= 12.Q only 39,53 % winding is protected.
It is necessary to give 90% protection.
% Winding unprotected = 100 - 90 = 10%
Rely
10° 100
Rx 320
10 = 50.6530 "1?
R = 1.98460
This is the minimum value of resistance to give 90% protection to the la
B Pf
machine,
am Example $4: A 50 MVA, 3 phase, 33 LV synchronous generator is protected by the
Merz-Price protection using 1000/5 ratio CTs. It is provided with restricted earth fault
protection with the earthing resistance of 7.5. . Caleulate the percentage of winding
unprotected in eack phase against earth faults if the minimum operating current of the
relay is 0.5 A
Solution : The given values are,
Vi = RV C.T. ratio = 1000/5 R=750Protection and Switehgear 5-33 Genorator Protection
i, = O5 A = relay current
minimum operating current (primary)
Vi, _ 33*10°
3 3
= 1905255 V
RI
% Winding unprotected = —[# x 100
Example 5.5: A 13.2 kV, 3 phase, 100 MW at 0.8 pf lag, alternator has reactance of
0.2 pus. If it is equipped with a circilating current differential protection set to operate
at least at 500 A fault current, determine the magnitude of the neutral grounding
resistance that leaves the 10% of the winding unprotected.
Solution : The given values are,
Vi = 12KV cos#=08 P=100MW X=02 pu
Now P= V3V I, cos}
100«10* = ¥3x 13.2% 10" xf, « 08
I, = 5467.33 A = [= full load current
The p.u, reactance is given by,
go Xe I here X w cemckance per phat
og = _SH67.33% where V « St
(13.280 ) v3
v3
X = 0.2787 0 per phase
% of unprotected winding = 10%
Reactance of unprotected winding = {10 «0.2787Protection and Switchgear 5-34 Generator Protection
= 002787:
Voltage induced in 10% of unprotected winding,
10 _ 10, 13.2108
= Too" - 00" Bi = 762.1023 V
Let this voltage be v = 762.1023 V
ze J
where Z = Impedance offered to the fault
r = Resistance in neutral
x = Reactance of 10% of winding
Now z-t
where v= Voltage induced in 10% winding
= 762.1023 V
i = Fault current = 500 A
peavey _ 762.1023
300
= 1.5242
P+ (0.02787F = 2.3232
2.9224
a
rs 15240
This is the required resistance in neutral earthing.
‘wb Example 5.6 : Ar alternator stator winding protected by a percentage differential relay
is shown in the Fig, 5.27. The relay has 15% slope of characteristics (1, — Iy) against (1,
+ 1y2). The high resistance ground fault has occursed newr the grounded neutral end of
the generator winding while the generator is carrying load. The currents flowing at each
end of the generator winding are also shown. Assuming C.T. ratio to be 50/5 A, wit
the relay operate to trip the circuit breaker ?Protection and Switchgear 5-35 Generator Protection
300+j0A 340+ )0A
(ay ©)
Fig. 5.27
Solution : From the given current at two ends, let us calculate C.T. secondary
s at two ends,
i, (300 +] 0) xg =3.4
344
(340 +40) x2
and iy 07
The directions of currents are shown in the Fig. 5.28.
Fig. 5.28
The current flowing through the relay coil is iy ~ iz.
= 3-34=-04A
While = 3S toa2a
From the characteristics of 15 % slope, corresponding, to +! = the out of balance
current required is,Protection and Switchgear 5-36 Generator Protection
‘This is shown in the
15 Siope
~ ig. 5.29.
‘Thus iy ~ ip must be
ly-ip more than 0.48 A ie.
O48 above the line to
operate the relay but
actual point is located
below the line in
negative torque region.
Hence the relay will
not operate.
Example 5.7: A 6.6 KV, star connected alternator has a transient reactance of 2.0
per phase and negligible winding resistance. It is protected by circulating current
Merz-Price protection, The alternator neutral is earthed through the resistance of 7.5 Q.
The relays are set fa operate when there is out of balance current of 1 A in secondary of
SO0/S A current transformers. How much % of winding is protected against earth fault?
Solution : The given values,
Vi, = 66kV¥ X=20/phase r=752 CT. = 500/5
Let the x % of winding is unprotected.
Reactance of unprotected windi iw0* 25002x2
Vy _ 6.6%10°
vy = b= = 3810511 V .. full voltay
3 ee
¥ = Voltage across unprotected winding
x
= jgg* 3810-511 = 38.2051 x V
r= 750
Z = Impedance offered to the fault
= r+j 02%)
= 75 +j @02x) Oo
[Z| = y7.5)° +(0.02x)*
fault current
= out of balance secondary current « C.T. ratioProtection and Switchgear 5-37 Generator Protection
500
= Ix
= 100A
¥
IZ] 7
I> oe? apa? 38.10511x
(75? +O.02x)? = =
(757 + (0.02 x)? = 0.1452 <7
56.25 + 4x10? = 0.14527
0.1448 P= 56.25
x? = 388.4668
x = 19.7%
This is % of winding unprotected.
4% of winding protected = 100 - 19.7
= 80.29 %
‘mm Example 5.8: A synchronous generator rated at 20 KV protected by circulating
current system having neutral grounded through a resistance of 15 0. The differential
protection relay is set to opertte then there is an out of balance current of 3 A. The
CTs have ratio of 1000/5 A, Determine,
i} The % of winding remains unprotected
ti) Value of earth resistance to achieve 75% protection of winding
Solution : The given values are,
Vi = 20kV, 3A, R= 159, CT. ratio = 1000/5
i I, = minimum line operating current (C.T. primary)
= j, «1000 , 3*1000
= bang
= 600A
y = Ye. 20410"
v3
= s7¥
% X = % of winding unprotectedProtection and Switchgear 5-38 Generator Protection
= 794%
ii) We want 75% protection.
% X = 100~75 = 25%
Remaining conditions are same except R.
RI
2 = 100
V
R600
28 = yey «100
25% 11547
RS Spx 100
= 4811
Tl
jamb Example 5.9: The Fig. 530 shows the percentage differential relay used for the
protection of an alternator winding, The relay has minimum pickup current of 0.25 A
and has a % slope of 10%. A high resistance ground fault occurs wear the grounded
neutral end of the generator winding with the current distribution as shown in the
Fig, 5.30. Assinte a C.T. ratio of 400 : 5, determine if relay will operate.
s is the required earth resistance.
3609 )0 A e840 +j0 A
RF
Foun
Fig. 5.30
Solution : For the given current at the two ends, the CT. secondary currents can be
obtained using C.7. ratio as,
(380 + j 0) x5 = 475A
5
(340 + j 0) qo PA
4.75 -4.25=05A4
_ 4.7544.25
2
= 454
So i: — iy current flows through operating coil while 45 A flows through the
restraining coilitchgear 5-39 Generator Protection
With the minimum pickup current of 0.25 A, and slope 10°
as shown in the Fig. 5.31.
the operating
characteristics
ve torque
Minimum
pickup current
‘The equation of the characteristics
mxte
At origin, x = 0 but y = 0.25
y= c= 025
Hence characte:
ic equation is,
where m = slope = 0.1
For 4.5 we get,
(O.1x4.5)+0.25
= O74
Thus to operate the relay, i, - i, must be greater than 0.7 A when 2742 is 4.5 A.
But actually i, - iz = 0.5 A as shown. It is located below the line in negative torque
region hence relay will not operate,
iim Example 8.10: An alternator rated 10 KV protected ly balanced circulating current
system has its neutral grounded Hiraugh a resistance of 10 ohms. The protective relay is
set fo operate when there is an out of balance current of 1.8 amperes in the pilot wires
which are connected fo the secondary of current transformers with ratio 1000/5.Protection and Switchgear 5-40 Generator Protection
Determine :
i) The percentage winding which remains unprotected.
ii) The minimum value of the earthing resistance required to protect 80% of the winding,
(V.T.U August-2002)
Solution : V, = 10 kV, R = 10.0, C-T. ratio = 1000/5, j, = 1.8 A
1, = minimum operating line current (C.-T. primary)
1000 1000
= ign Eo = BK = 360A
fs Vi _ 10x10°
V = line to neutral voltage = —L = = 57735026 V
eee
‘ is e199 = 10360.
i) % Winding unprotected = “72100 = FEES x 100
= 62.3538 %
ii) It is necessary to give 80 % protection.
= % Winding unprotected = 100 - 80 = 20 %
Rx 360
20 = 5795-5026 "100
R = 320750 _ Minimum earthing resistance required
‘me Example 5.11: An allernator stator winding protected by a percentage differential
relay is shown in Fig. 5.324). The relay has 0.15 amp minimuent pick up and a 12%
i, +i,
2
near the grounded neutral end of the generator winding while generator is carrying
load. The currents flowing at each end of the generator winding are shown in Fig, 5.32,
Assuming that the CT's have 400/5 amps ratio and no inaccuracies will the relay trip
the generator CB under this fault condition.
slope of characteristics liz = is) V, ( } A high resistance ground fault has occured
Fig. 5.32(a)Protection and Switchge:
5-41
Generator Protection
Positive torque
“a— Slope 12%
iy
=
Fig. 5.32(b)
(AU-April-2004)
Solution : From the given current at
two ends, let us calculate C:T. secondary
curents at two ends,
= (300+ j0}x
B75 A
400
iy = (300+ j0)x 45A
‘The relay coil current = i, - iy = 0.75 A
p+
ni
2
= 41254
:
From the characteristics of 12 % slope, corresponding to | a) » the out of
Uz
balance current required is,
i) - i, = slope +f 4 = )=0.12 «4.125 = 0.495 A
if }
Thus iy — i, must be more thatn 0.495 A for relay to operate. And actually it is
075 A. Hence the relay will operate :
Aijnig) 4 18-18 95
12 % slope
O.75A
0.495AProtection and Switchgear
Generator Protection
Actual point is located in positive torque region. Slope of line through actual point is
= fick).
(izia)
2
18.18 %
As this slope is more than 12% of the characteristics given, relay will operate.
wap Example §.12 : A 3 phase, 10 MVA, 6.6 kV alternator supplies a load of 8 MVA at
O8 pf. and is being protected through Merz-price circulating current system and its
relays are so set that they do not operate until the out of balance current ocurs at 20%
of full lood current. Calculate the value of earth resistance to be provided in order to
ensure that only 10% of alternator winding remains unprotected. Assume alternator
reactance of 10% Neglect resistance of the alternator. (AU-Dec.-2004)
Solution : V, = 66 kV, Rating = 10 MVA, V = V_/J3 = 38105117 V
Rating = ¥3 Vid,
2
1, = lx - ami a load current
V3 x 6.6% 105
% Reactance = 7 x 100 X = Reactance per phase
_ S74.7731X
10 = ssrosii7 “1
X = 043560
Reactance of unprotected winding = x 0.s356 = 0.09356 2
v = Voltage induced in unprotected winding
10
= jqp* ¥ = 38105117 V
i = Fault current = 20% of I, = 174.954 A
impedance offered to fault = 2.1780
But Zz
A+ j 0.08356.
|Z] = JR? +(0.04356)?
(2.178)? = R? + (0.04356)?
R= 21770 Earth resistance requiredProtection and Switchgear 5-43 Generator Protection
‘tm Example 5.13: Current transformers of current ratio of 1000/5 A are used for
protection of a star connected 3 phase, 10 MVA, 6.6 RV alternator. if the relay is set to
operates for @ minimum current of 0.5 A, Calestlate the percentage of each phase stator
winding which is uprotected agains earth fault when the machine operates at normal
woltage. Asstume that star point of alternator is earthed tirougit a resistance of 7.5.Q.
{AU-Apri
Solution : V, = 6.6 10° V, R= 752, CI. ratio = 1000/5, i, = 0.5
I, = ig x CIT. ratio = 0.5 xe = 100A
Vv
yee 100 = sere = 100
= 19.682%
% winding unprotected =
ti Example 5.14: A 500 kVA, 6.6 kV star connected alternator has a syncironous
reaclance of 1.02. per phase and negligible resistance. The differential relay operates if
the out of balance current through it exceeds 30% ofthe normal full load current of the
alternator. The star point of the alternator is earthed through a resistance of 5 © . What
percent of the stator twinding is left unprotected ? Show that the effect of the alternator
reactance cm be neglected. {AU-Dec,-2005)
Solution : The full load current,
Va 500 «10°
Le ate
V3V, V3x66x10°
Out of balance curent = 30% I, = 0.3 x 43.738 = 13.1214 A
Let winding unprotected = x %
43.738 A
Impedance of x% winding = Fog OH)
Value of earthing resistance = 5
Total impedance at fault of the fault circuit.
= [5 +j001 x)
Voltage induced in x % of winding
6.6103
Voltage induced
Out of balance current =
ImpedanceProtection and Switchgear 5-44 ‘Generator Protection
13.1214 = (1)
This is to be solved by trial and error method. Hence effect of alternator reactance
can be neglected.
66x
13.1214 = —=
V3
x = 17217 % ...Winding unprotetced
The equation (1) can be solved as,
8
=
+» Considering magnitude,
25+(0.01x)? = 8.4334 x?
x
L7217%
This shows that the reactance can be neglected without any error.
w Questions
1. Which are the narions types of frufts ahich can accur in a generator ? Explain: in brief
2. Why the pro
3, Wich are the various abnormal rinning conditions, wluich may exist in a generator ? What are
their effects and how these effects cin Be minimized ?
4. Explain the basic differential protection scheme. What are its disadvantages ?
tes
Explain the basic percentage differential protection scheme. Draw its operating charac
showing positive and negative torque regions.
6. Draw and explain the Merz-Price protection of alternatar stator windings. State its advontages.
7. What i the role of auxiliary relay, én Mera-Price protection: ?
8. Explain the resteictod carth fault protection: of generators.
9. Derive the expression for the percentage of winding unprotected in the restricted earth fault
protection.
10. Explain the operation of unrestricted earth fault protection scheme.
11. Draw anit explain balanced earth fanit protection scheme,
12. Is it possible that 100 % winding of generatar is protected against earth faults ? How ?
13. Suggest the scheme for interturn fut protection for Stator of alternator.Protection and Switchgear 5-45 Generator Protection
14,
15,
16.
i”,
18,
20.
1.
Explain the negative phase sequence protection for the generators.
What are the methods to provide rotor earth fault protection ?
How the protection against loss of excitation is provided in generators ? Why it is important ”
A. generator is provided with restricted carth-fault protection. The ratings are 11 kV, 5000 RVA
The percentage of winding protected against phase to ground fault # 80%, The relay setting such
that i trips for 25% ont of balance. Calewlate the resistance to We added ir neucteat to ground
connection tAns, 1.94.0)
The neutral point of a 19,000 V alternator is earthed through a resistance of 10 olkms, the relay is
set to operate when there is an out of balance current of 1A. The CT's have a ratio of 1000/5.
What percentage of the winding i protected against fault to earth and what must be mininun
ulus of earthing resistance to give 90% protection to each phase winding ?
(Ans, : 625%, 2.88.0)
A 3 pase, 2 pole, 11 RV, 10,000 AVA olternater hes neutral exrthed through a resistance of 7
kis. The machine has current balance protection which operates upon out of balance current
ed 20% of full toad. Determine % of winding protected against earth fauit. (Ans. :88.4%)
5.34{a) shows percentage differentiat relay applied to the protection of an alternator
winding, The relay es 10% slope of characteristics I~ 1) 05 (Ty + Ip.
A height resistance ground fault occurred near the grounded neutral ead of the generator winding
wile generator is anrrying load. As a consequence, the currents in amperes flowing at cach cra of
the winding are shorn in Fig. 5.34(b). Assuming C.T. ratio of 400/5 amperes, will the relay
operate to trip the breaker. (Ans. : Relay will not operate)
320+ 10
Fig. 5.34(b)Protection and Switchge:
5-46 Generator Protection
a.
23
ATL RV, 3 phase alternator has full load rated current of 200 A. Renctance of armature winding is
5 percent, The differential protection system is set to opennte on earth finult currents of more than
200 A. Find the neutral earthing resistance, which gives earth fult protection to 90% of stator
winding (Ans, : 3.145 0)
A starsconnected S-phase 10 MVA, 66 kV alternator has a per phase reactance of 10%, It is
protected by Merz-Price circalating-current principle which is set to operate for fault currents not
less than 175 A, Calculate the caine of earthing resistance to be procided in onder to ensure that
nly 10% of the alternator winding remains unprotected. (Ans, : 2.1710)
A star connected, 3 phase, 10 MVA, 6,6 KV alternator és protected by Merz-Price circulating
current principle using 1000/5 anaperes: current transformers. The star point of the alternator is
varthed through a resistance of 7.5.0 . If the minimum operating current for the relay is 0.5 A,
caleylate the percentage of each phase of the stator winding which is unprotected against earth
{faults token the mactine is operating at normal voltage. (Ans. : 19.69%)
A 6600 volt J-phase turbonalterniator has a niarininn continuous ating of 2.000 KW at 0.8 py
and its, reactance is 12.5%. 1 is equipped with Mers-Price circuliting current protection which is
set fo operate at fault currents not tess that 200 amperes. Find rohat value of the newtrel earthing
resistance leaves 10% of the windings unprotected ? (Ans. = 1.89.9)
ASO MVA, S-phase, 33 RV alternator is being protected by the use of circulating current balance
scheme tsing 2000/5 ampere current transformer, The neutral of the generator is carted through 3
NGR of 7.5 ohms, If the pick wp current for the relay is just above 0.5 ampere, determine what
percentage of the winding of each phase unprotected against earth then the machine eperties at
nominal voltage. (Ans, : 7.88%)
goa