A B C A B C
3 3
S1
S2 S1 3 2
S2
2 S3 2
S1
1
1 1
LIGHTING LAYOUT PLAN POWER LAYOUT PLAN
SCALE: 1:100 MTS SCALE: 1:100 MTS
SCHEDULE OF LOADS
CKT NO. LOAD DESCRIPTION NO. OF OUTLETS WATTS VOLTS AMPS CKT. PROTECTION SIZE OF WIRE AND CONDUITS
2-3.5mm sq. THHN/THWN
1 LIGHTING OUTLET 15 270 230 1.17 15AT, 50AF, 2P
STRANDED Cu. WIRE IN 20mmPVC
2-3.5mm sq. THHN/THWN
2 POWER OUTLET 9 1350 230 5.87 20AT, 50AF, 2P
STRANDED Cu. WIRE IN 20mmPVC
2-5.5mm sq. THHN/THWN
3 ACU 1 1840 230 8.00 30AT, 50AF, 2P
STRANDED Cu. WIRE IN 20mmPVC
2-5.5mm sq. THHN/THWN
4 ACU 1 1840 230 8.00 30AT, 50AF, 2P
STRANDED Cu. WIRE IN 20mmPVC
5 SPARE ---- ---- ---- ---- ---- ----
6 SPARE ---- ---- ---- ---- ---- ----
TOTAL CKT NO. 26 5300 230 23.04 60AT, 100AF, 2P CKT NO.
COMPUTATION: SIZE OF WIRE: USE 2-14mm sq. THHN/THWN Cu. WIRE IN 25mm RSC
MAIN-OVER-CURRENT PROTECTION: USE 60AT, 100AF, 2P, 230V, 60Hz
= 1620(80%) + 3680 + (25% x 8)
230 230
= 23.63 AMPS
PROJECT TITLE: PREPARED BY: CHECKED BY: CONCURRED BY: APPROVED BY: SHEET CONTENT: SHEET NO.
Republci of the Philippines · LIGHTING LAYOUT PLAN
Province of Biliran
Municipality of Maripipi
CONSTRUCTION OF BRGY.
HEALTH STATION
JOENYL FERNAND C. CAINGCOY ENGR. LOU STANLEY I. PULVERA MARY GRACE R. LLEVER, MD. HON. JOSEPH C. CAINGCOY, RPsy. Ph.D.
·
·
POWER LAYOUT PLAN
SCHEDULE OF LOADS
E
OFFICE OF THE MUNICIPAL ENGINEER
LOCATION: BRGY. VIGA MARIPIPI, BILIRAN DRAFTSMAN DESIGNATE MUNICIPAL ENGINEER MHO MUNICIPAL MAYOR 1