Openair™: Technical Instructions
Openair™: Technical Instructions
OpenAir™
GEB Series Non-spring Return, 24
Vac, 132 lb-in Rotary Electronic
Damper Actuators
Application         Used in constant or variable air volume installations for the control of HVAC dampers
                    requiring up to 132 lb-in (15 Nm) torque.
Warning/Caution Notations
Product Numbers
                                                         Table 1.
Modulating (0 to 10 Vdc)
24 Vac ±20%
                                                                                                         Standard
                                                                                     Floating
                                                                                                Plenum
                        GEB131.1P          ●                –                        ●          ●        –           –                   –                         –                       –
                        GEB131.1U          ●                –                        ●          –        ●           –                   –                         –                       –
                        GEB132.1U          ●                –                        ●          –        ●           ●                   –                         –                       –
                        GEB136.1U          ●               –                         ●          –        ●           –                   ●                        –                        –
                        GEB161.1P          ●               ●                         –          ●        –           ●                   –                        –                        ●
                        GEB161.1U          ●               ●                         –          –        ●           ●                   –                        –                        ●
                        GEB164.1U          ●               ●                         –          –        ●           ●                   ●                        ●                        –
                                  DC rating                                      12 to 30 Vdc
                                                                                 DC 2A
                                  Switch Range
                                      Switch A                                   0 to 90° with 5° intervals
                                      Recommended range usage                    0 to 45°
                                      Factory setting                            5°
                                      Switch B                                   0 to 90° with 5° intervals
                                      Recommended range usage                    45 to 90°
                                      Factory setting                            85°
                                Switching hysteresis                             2°
                             Feedback potentiometer (GEB 132.1U)                 0 to 1000 ohm <10 mA
                                Voltage                                          UL-Class 2 (SELV/PELV for CE)
Auxiliary features,
Continued                                 WARNING:
                                          Apply only AC line voltage or only UL-Class 2 voltage (SELV for CE conformance) to
                                          the switching outputs of both auxiliary switches A and B. Mixed operation is not
                                          permissible. See Wiring for details.
                                          NOTE:     With plenum cables, only UL-Class 2 (SELV for CE) is permitted).
Miscellaneous            Pre-cabled connection                                 18 AWG
                         Cable length                                          3 feet (0.9m) length
Actuator                                                                                              Legend
Components
                                                                                        1. Actuator housing
                                                                                        2. Positioning scale for angle of
                                                                                           rotation
                                                                                        3. DIP switches and cover
                                                                                        4. Span adjustment
                                                                                        5. Offset (start point) adjustment
                                                                                        6. Mounting bracket
                                                                                        7. Connection cable for power
                                                                                           and control signals
                                                                                        8. Connection cable for auxiliary
                                                                                           switches or feedback
                                                                                           potentiometer
                                                                                        9. Manual override
                                                                                        10. Auxiliary switches A & B
                                                                                        11. Position indicator
Accessories                 NOTE:     The auxiliary switches, control signal adjustment, and feedback potentiometer
                                      cannot be added in the field. Order the product number that includes the option(s).
                                                                                        4614Z19
                                                                                                  Kit contains:
                                                                                                       • Crank arm to change the angular
                                  Figure 2. Floor /Frame Mount Kit.                                       rotation into a linear stroke.
                                                                                                       • Support bearing ring to minimize side
                                                                                                          loading on the actuator’s output
                                                                                                          bearing.
                                                                                                       • Mounting bracket.
                                                                                                       • Required mounting fasteners.
Service Parts
                                                   985-092
                                      Anti-rotation (mounting) bracket.
Operation              GEB16x
                       Apply a 0 to 10 Vdc control signal between wire 8 (Y) and wire 2 (G0) to operate the damper
                       actuator. The angle of rotation is proportional to the control signal. A 0 to 10 Vdc position
                       feedback output signal is available between wire 9 (U) and wire 2 (G0) to monitor the position
                       of the damper motor.
                       In the event of a power failure, the actuator holds its position. In the event that only the control
                       signal is lost, the actuator returns to the "0" position.
                       GEB13x
                       A floating control signal controls the damper actuator. The actuator’s angle of rotation is
                       proportional to the length of time the signal is applied. A 24 Vac control signal to wire 6 (Y1)
                       causes the actuator coupling to rotate clockwise. A 24 Vac control signal to wire 7 (Y2)
                       causes the actuator coupling to rotate counterclockwise.
                       To reverse the direction of rotation, wires 6 (Y1) and 7 (Y2) can be interchanged.
                       With no control voltage, the damper actuator holds its position.
Overload protection In the event of a blockage in the damper, the actuator is overload protected over the full range
                    to prevent damage to the actuator.
Life expectancy        An improperly tuned loop will cause excessive repositioning that will shorten the life of the
                       actuator.
Sizing
                         The type of actuator required depends on several factors:
                                                                       2         2
                             1. Obtain damper torque ratings (ft-lb/ft or Nm/m ) from the damper manufacturer.
                             2. Determine the area of the damper.
                             3. Calculate the total torque required to move the damper:
                                                         Table 2.
               Total Torque                                                    Actuator
<44lb-in                 (5Nm)                                                   GDE
>44lb-in <88lb-in        (>5Nm <10Nm)                                             GLB
>88lb-in <132lb-in       (>10Nm <15Nm)                                            GEB
>132lb-in <177lb-in      (>15Nm <20 Nm)                                           GBB
>177lb-in <310lb-in      (>20Nm <35Nm)                                            GIB
>310lb-in <620lb-in      (>35Nm <70Nm)        Use tandem-mounting bracket ASK73.2U with any combination of
                                              GIB161 AND GIB166 actuators or use Master/Slave Actuators.
                                              See OpenAir™ Electronic Damper ActuatorsTechnical Instructions (155-
                                              542P25).
Mounting and                  •    Place the actuator on the damper shaft so that the front of the actuator is accessible.
Installation                       (The label and the manual override button are on the front side.)
                              •    The minimum damper drive shaft is 3/4-inches (20mm). The shaft length determines
                                   whether the shaft adapter will be mounted on the front or back of the actuator.
                              •    Refer to Specifications for minimum and maximum damper shaft dimensions.
                              •    Set auxiliary switches, DIP switches, and Offset/Span as required by your
                                   application. (See following sections for details.)
                              •    The position indicator can be mounted to show either the clockwise or
                                   counterclockwise 0 to 90 scale.
                              •    A mounting bracket is included with the actuator.
                              •    The shaft adapter and mounting parts are shipped in a separate container with the
                                   actuator.
                              •    The actuator is shipped from the factory with a 5° pre-load to ensure tight damper
                                   close off.
                              •    Detailed mounting instructions are included with each actuator.
                             4. Determine the angle of rotation for the damper blade shaft. Subtract that amount
                                from 90°.
                             5. Remove the shaft adapter and insert it with the position indicator pointing to the mark
                                on the scale calculated in the previous step. See Figure 12.
                             6. Attach the clip.
                             7.    Rotate the damper blade shaft to its “0” position.
                             8.    Return the actuator to the damper shaft and tighten the shaft adapter to the damper
                                   shaft.
Control signal             The offset (start point) and span of the control signal can be adjusted. The offset, Uo, can
adjustment                 be adjusted between 0 to 5 Vdc. The span, ∆U, can be adjusted between 2 to 30 Vdc.
GEB164.1U
(Offset and Span)
                                                                                                      Factory setting:
                           Ys        Mechanical positioning range (100% = angle of rotation 90°)        30V span
                           Yu        Control signal                                                      0 offset
                           Uo        Offset (start point)
                           ∆U        Span
                           NOTE:       When the mechanical limitation of the angle of rotation and
                                       self-adaptive function are ON, 100% does not equal 90°.
                                  1. Uo = 0V, ∆U = 2V:  The minimum working range for
                                                        Ys = 100%
                                  2. Uo = 5V, ∆U = 30V: The maximum working range for
                                                        Ys = 100%
                                  3. Uo = 0V, ∆U = 30V: Factory setting
                           Example:
                           Open the actuator from 0 to 50% (45°) using a control signal of:
                                                              Umin= 2V to Umax= 10V.
DIP Switch
Functionality           Description                Label             Description            Function
GEB161
                  Counterclockwise                                 Clockwise         Rotary angle direction
GEB164
                                                                                     Self-adaptation to
                  Active                                    0      Off
                                                                                     mechanical range
                                                                                     GEB161: Positioning
                  2-10 Vdc                 2-10             0-10   0…10 Vdc          control signal
                                                                                     2-10 or 0-10
                                                                                     GEB164: Positioning
                  Offset 0-5V
                                                                                     signal. Turn on or off
                  Span 2-30V               ADJ              0-10   0...10 Vdc
                                                                                     capability to adjust
                                                                                     offset/span.
                                                          Figure 16. DIP Switches.
DIP Switch
Functionality,
Continued           Rotary direction
                                                • The arrow direction must match the rotational direction of
                                                  the actuator.
                                                • Factory setting:
                    Self-adapting
                                                 • Alternative switch-on/off for self-adaptation.
                                       0
                                                      : ON
                                                   0: OFF
                                                 • Factory setting: 0
Wiring        All wiring must conform to NEC and local codes and regulations.
              Use earth ground isolating step-down Class 2 transformers. Do not use autotransformers.
              The maximum rating for a Class 2 step-down transformer is 100 VA. Determine the supply transformer
              rating by summing the VA ratings of all actuators and all other components used. It is recommended
              that one transformer power no more than 10 actuators (or 80% of its VA).
                           WARNING:
                           Mixed switch operation is not permitted to the switching outputs of both auxiliary switches
                           (A and B).
                           Either all six outputs of the dual auxiliary switches must be connected to the AC line
                           voltage, or all six outputs must be connected to UL-Class 2 voltage (SELV for CE
                           conformance).
                           NOTE:       With Plenum cables only UL-Class 2 voltage (SELV for CE conformance) is
                                       permitted.
                         WARNINGS:
                         Installations requiring        Conformance:
                           •       Except for the auxiliary switches (See Warning above) all wiring for actuators must
                                   be safety extra-low voltage (SELV) or protective extra-low voltage (PELV) per
                                   HD384.
                           •       Use safety transformers per EN61558 with double isolation, designed for 100%
                                   duty-cycle for supplying SELV or PELV circuits.
                           •       Over-current protection for supply lines is maximum 10A.
                         CAUTION:
                         Do not parallel GEB13x actuators with any other type of actuator.
Wire Designations Each wire has the standard symbol printed on it. See Table 3.
Service                                    WARNING:
                                           Do not open the actuator.
                                           If the actuator is inoperative, replace the unit.
Troubleshooting                            WARNING:
                                           To avoid injury or loss of life, pay attention to any hazardous voltage
                                           (Example: 120 Vac) when performing checks.
Dimensions
Dimensions
Figure 20. Dimensions of the GEB Actuator and Mounting Bracket in inches (mm).
Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as
design improvements are introduced. OpenAir is a trademark of Siemens Schweiz AG. Other product or company names mentioned herein may be
the trademarks of their respective owners. © 2014 Siemens Industry, Inc.
 Siemens Industry, Inc.                             Your feedback is important to us. If you have                    Document No. 155-318P25
 Building Technologies Division                     comments about this document, please send                              Printed in the USA
 1000 Deerfield Parkway                             them to technical.editor@sbt.siemens.com                                           Page 16
 Buffalo Grove, IL 60089-4513
 USA
 +1 847-215-1000