Herz Valves

The document provides specifications for a gate valve and commissioning valve (double regulating valve) from Herz Armaturen. The gate valve comes in sizes from 15 to 50 mm with bronze or steel components. The commissioning valve comes in sizes from 15 to 50 mm with integrated fixed orifice plates for flow measurement and has adjustable regulating and locking functions. Both valves are suitable for non-aggressive fluids in domestic, commercial, and industrial applications at pressures up to 20 bar and temperatures up to 130°C.

Uploaded by

at7984582
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
488 views11 pages

Herz Valves

The document provides specifications for a gate valve and commissioning valve (double regulating valve) from Herz Armaturen. The gate valve comes in sizes from 15 to 50 mm with bronze or steel components. The commissioning valve comes in sizes from 15 to 50 mm with integrated fixed orifice plates for flow measurement and has adjustable regulating and locking functions. Both valves are suitable for non-aggressive fluids in domestic, commercial, and industrial applications at pressures up to 20 bar and temperatures up to 130°C.

Uploaded by

at7984582
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 11

Gate Valve

wedge and double disc version. Data sheet for 3 4113 0x, Issue 1220

Material
Body :Bronze CC491k Technical data
Upper Part :Bronze CC491k Max. opera ng pressure : 20 bar
HandWheel :Sheet Steel,Coated Max. opera ng temperature : 120°C
Seat :EPDM Connec on thread : ISO 7-1 Rp

The use of ethylene or propylene glycol in a mixing ra o 25 -50% is allowed.


4113 1x according to EN12288 ,BS5154

Order
DN Rp D H L SW1 SW2 SW3
number
3 4113 01 15 1/2 50 71.6 49.4 27 21 15
3 4113 02 20 3/4 50 73.8 52.4 32 21 15
3 4113 03 25 1 60 84.3 61 39 26 15
3 4113 04 32 5/4 60 94 69.6 49 37 15
3 4113 05 40 6/4 80 115 74 55 41 21
3 4113 06 50 2 105 142.5 89 68 41 25

Field of applica on
For all nonaggressive fluids for domes c, commercial and industrial applica ons. Suitable for
hot and cold water.

Sealing surfaces
Sealing takes place by means of pressing the valve discs without sliding onto the seat. The fine
worked seal precision surface of the valve discs guarantees denseness for the carried flow quan ty,
also when dirt par cles have been deposited on the surfaces of the gate

All specifica ons and informa on within this document are reflecting the informa on available at the me of going to print and meant for informa onal purpose only. Herz Armaturen
reserves the right to modify and change products as well as its technical specifica ons and/or it func on according to technological progress and requirements. All diagrams are
indica ve in nature and do not to be complete. It is understood that all images of Herz products are symbolic representa ons and therefore may visually differ from the actual product.
Colours may differ due to prin ng technology used. In case of any further ques ons don’t hesitate to contact your closest HERZ Branch-Office. 31

HERZ Armaturen Ges.m.b.H


Richard-Strauss-Strasse 22,1230 Vienna, Austria.
STRÖMAX 4017
Commissioning valve (double regula�ng valve) with integral fixed orifice plate.
Data sheet for 4017, Issue 0916
Dimensions in mm
H1
H2

L1
L2
M

˜D

Order number DN L1 L2 H1 H2 M D Kvs Value Kv orifice


1 4017 01 15 83 129 96 109 25 70 2 1.95
1 4017 02 20 91 135 99 115 25 70 3.6 3.95
1 4017 03 25 110 146 109 130 25 70 6.5 7.9
1 4017 04 32 122 159 117 142 25 70 13.3 15.75
1 4017 05 40 135 178 136 163 25 70 18.5 21.5
1 4017 06 50 164 197 140 175 25 70 33 46.7

All specifica ons and informa on within this document are reflecting the informa on available at the me of going to print and meant for informa onal purpose only. Herz Armaturen
reserves the right to modify and change products as well as its technical specifica ons and/or it func on according to technological progress and requirements. All diagrams are
indica ve in nature and do not to be complete. It is understood that all images of Herz products are symbolic representa ons and therefore may visually differ from the actual product.
Colours may differ due to prin ng technology used. In case of any further ques ons don’t hesitate to contact your closest HERZ Branch-Office. 31

HERZ Armaturen Gws.m.b.H 1


Richard-Strauss-Strasse 22,1230 Vienna, Austria.
Versions
The HERZ 4017 DZR combined regula ng and measuring valve has an integral orifice incorporated into the valve
cas ng. Available in sizes from DN15 to DN50, 1/2" to 2", with BSP female threaded ends to BS21 and manufactured
to BS 7350. The valve is also available in Low Flow and Medium Flow DN15 versions.
The commissioning valve has hidden regula ng and locking func ons with high accuracy and good repeatability. The
valve is fi ed with two standard pressure test points; extended test points are available when required. A ‘Microset’
two number posi on indicator is fi ed to the adjustment handle for recording the valve posi on.

4017 M STRÖMAX 4017 M, commissioning valve in Y pa ern


1 4017 0x with an orifice plate for differen al pressure
measurement, with test points
DZR copper alloy, female threaded ends, non-rising stem
sealed with Double-O-Ring, pre-se ng through stroke
limi ng, hand wheel with pre-se ng digital display

Applica on
Can be used as isola ng and commissioning valve.

Technical data
Valve is clockwise closed.
Max. opera ng temperature : 130 °C
Max. opera ng pressure : 20 bar
Max. differen al pressure at closed valve : 10 bar
Water purity in accordance with the OeNORM H5195 and VDI 2035 standards.
HERZ compression adapters for copper and steel pipes, allowable temperature and pressure
ra ngs according to EN 1254-2 1998 Table 5.
HERZ plas c pipe connec ons max. opera ng temperature 95 ° C and max. opera ng pressure 10
bar, if approved by the pipe manufacturer.
Ammonia contained in hemp can damage brass valve bodies, EPDM gaskets can be affected by
Mineral oils lubricants and thus lead to failure of the EPDM seals. Please refer to manufacturers
documenta on when using ethylene glycol products for frost and corrosion protec on.
Characteris cs
Flow direc on
The flow is observed according to the arrow on the body. There are no special tools required.
Installa on
In any orienta on.
Se ng
The hand wheel posi on is indicated in the digital display readout on the top of the hand wheel, the
valve set posi on can be locked easily by means of a concealed memory stop. The valve can be isolated and
returned to the pre-set posi on at any me. The pre-se ng is obscured by the hand wheel and protected
against

All specifica ons and informa on within this document are reflecting the informa on available at the me of going to print and meant for informa onal purpose only. Herz Armaturen
reserves the right to modify and change products as well as its technical specifica ons and/or it func on according to technological progress and requirements. All diagrams are
indica ve in nature and do not to be complete. It is understood that all images of Herz products are symbolic representa ons and therefore may visually differ from the actual product.
Colours may differ due to prin ng technology used. In case of any further ques ons don’t hesitate to contact your closest HERZ Branch-Office. 31

HERZ Armaturen Gws.m.b.H 2


Richard-Strauss-Strasse 22,1230 Vienna, Austria.
Strainer
Data sheet for 3 2662 0x, Issue 1220
L
L1 L1

D
D
H
Art. Nr. PN
PN DN D L L1 HH
(bar) (mm) (mm) (mm)
(mm) (mm) (mm)
3 2662 01 20 15 ½” 52 9 40
3 2662 02 20 20 ¾” 67 11 52
3 2662 03 20 25 1” 81 12 59
3 2662 04 20 32 1 ¼” 90.5 15 70
3 2662 05 20 40 1 ½” 100 19.5 74.5
3 2662 06 20 50 2” 121.5 23 92
Material
Body Bronze CC491k
Mesh Stainless steel Type 304
Mesh size 0.5mm
Sealings EPDM

Technical data
max. opera ng pressure 20 bar
max. opera ng temperature 110°C
The use of ethylene or propylene glycol in a mixing ra o 25- 50% is allowed.
Applica on
Strainers are installed in pipes to protect the finely machined valve seats from par cles. Field of applica on are
building services, such as in hea ng or chilled water units for air condi oning in buildings. EPDM Sealings can be
destroyed by organic hydro carbons, which are occurring in natural gas, mineral oil or lubricants.
Installa on and maintenance
A horizontal or ver cal installa on is possible, taking into account the flow direc on. The screening mesh chamber
should face down. HERZ recommends using standard thread sealants for the connec on between strainer and pipe.
The strainer can be removed and cleaned by opening the locking screw. Drain the system before opening the
locking screw. Reassemble in reverse order. Damage to the sealing have to be avoided. For service it is
recommended to install isolators before and a er the strainer.
Spare Parts
1 6386 11 DN15 Mesh 0,50mm
1 6386 12 DN20 Mesh 0,50mm
1 6386 13 DN25 Mesh 0,50mm
1 6386 14 DN32 Mesh 0,50mm
1 6386 15 DN40 Mesh 0,50mm
1 6386 16 DN50 Mesh 0,50mm
All specifica ons and informa on within this document are reflecting the informa on available at the me of going to print and meant for informa onal purpose only. Herz Armaturen
reserves the right to modify and change products as well as its technical specifica ons and/or it func on according to technological progress and requirements. All diagrams are
indica ve in nature and do not to be complete. It is understood that all images of Herz products are symbolic representa ons and therefore may visually differ from the actual product.
Colours may differ due to prin ng technology used. In case of any further ques ons don’t hesitate to contact your closest HERZ Branch-Office. 31

HERZ Armaturen Ges.m.b.H


Richard-Strauss-Strasse 22,1230 Vienna, Austria,
HERZ TS-90
Thermostatic Valve
Data sheets for TS-90, Issue 0916

011
EN 215
tested and registered
certificated products:
1 7724 90
1 7724 91
1 7724 92 7723
1 7724 95
1 7724 96 7724
1 7724 97
1 7723 90
1 7723 91
1 7723 92
1 7723 95
1 7723 96
1 7723 97

7728

7723 + 6249

7758 7759

Special models R = R 1/2, G = G 3/4

1 7723 61 1 7737 91 1 7733 81

HERZ Armaturen Gws.m.b.H


1.
Richard-Strauss-Strasse 22,1230 Vienna, Austria.
Important for Installation
Under no circumstances should the HERZ thermostatic head be exposed to direct sunlight or to the Important for Instal-
lation effects of equipment emitting relevant quantities of heat, e. g. TV sets. If the radiator is covered by curtains this will
lead to the formation of a heat accumulation zone in which the thermostat cannot sense the room temperature properly
and consequently cannot control it. In such cases, use the HERZ thermostat with remote sensor or the HERZ thermostat
with remote adjustment.
For detailed information on the HERZ thermostats consult the individual standard sheets.

Summer Setting
After the end of the heating period open thermostats or handwheels completely by turning anti- Summer Setting clock-
wise, this prevents dirt particles accumulating at the valve seat.

HERZ-TS Handwheel
In case the lower part of a HERZ thermostatic valve is not equipped with a HERZ thermostatic head the
HERZ-TS handwheel will replace the screw cap.
During assembly follow the enclosed instructions.

Accessories, Handwheel
1 6680 00 HERZ assembly key for connections
1 6807 90 HERZ-TS-90 assembly key
1 7780 00 HERZ changing tool for thermostat upper parts
1 9102 80 HERZ-TS-90 handwheel, Series 9000 “Design”

Spare Parts
1 6390 Thermostatic upper parts, order numbers available in HERZ product range catalogue.
1 6890 00 HERZ-TS-90 O-ring set

Proportional band

kv-value
p-difference [K] 0,5 1 1,5 2 2,5 3 3,5 4

TS 90 DN10 0,13 0,27 0,39 0,51 0,59 0,63 0,66 0,68

TS 90 DN15 0,15 0,31 0,46 0,60 0,75 0,81 0,82 0,83

TS 90 DN20 0,20 0,39 0,56 0,70 0,83 0,95 1,05 1,12

TS 90 DN25 0,23 0,45 0,68 0,90 1,11 1,32 1,51 1,72

HERZ Armaturen Gws.m.b.H


5.
Richard-Strauss-Strasse 22,1230 Vienna, Austria.
HERZ Standard Diagram HERZ-TS-90
Art. No. 7723 – 7759 Dim. DN 20 R = 3/4
Valve dimensioning [Δ p] shall be performed in accordance with the “VDMA-Instruction Sheet for Planning and Hydraulic
Balancing of Heating System with Thermostatic Radiator Valves”. VDMA = Association of German Constructors.

kv-value

Values according to EN 215

a = 0,85
qmN = 220 kg/h
Pressure drop ∆p

Standard flow rate qm

HERZ Armaturen Gws.m.b.H 9.


Richard-Strauss-Strasse 22,1230 Vienna, Austria.
HERZ Standard Diagram for dimensioning HERZ-TS-90
Art. No. 7723 – 7724 Dim. DN 25

kv-value
0,001 0,005 0,01 0,05 0,1 0,5 1 5 10
100 1000

50 500

1K
10 100
2K

5 3K 50

open

1 10

0,5 5

0,1 1

0,05 0,5
Pressure drop ∆p

[kPa]

[mbar]

0,01 0,1
5 50 500 5.000 10.000
1 [kg/h] 10 100 1.000

Standard flow rate qm

HERZ Armaturen Gws.m.b.H 10.


Richard-Strauss-Strasse 22,1230 Vienna, Austria.
HERZ Actuator 7990
Data sheet for 7990 Issue 0916

Dimensions Installa�on height

1 7990 31 HERZ Actuator modula�ng 0..10 V, M28 x 1.5, 24 V, 50 Hz


normally closed, closing force 100 N, opera�ng voltage 24 V ~,
threaded connec�on M28 x 1.5, blue adapter
1 7708 85 is included, max. stroke 5 mm
1 7990 32 HERZ Actuator modula�ng 0..10 V, M28 x 1.5, 24 V, 50 Hz
normally closed, closing force 125 N, opera�ng voltage 24 V ~,
threaded connec�on M28 x 1.5, blue adapter
1 7708 85 is included, with valve path recogni�on, max. stroke 6,5 mm

Applica�on 1 7990 31, 1 7990 32


The HERZ-Actuator propor�onal 5/6,5 mm is a thermoelectric actuator for the control of hea�ng and cooling
systems in direct propor�on to the applied control voltage. The control of the actuators is performed by a 0-10 V
DC signal via a central DDC system or by a room thermostat. Principal area of applica�on is the building
management system range.
Furthermore, the variant 1 7990 32 with valve path recogni�on automa�cally register the valve path for an
op�mum use of the ac�ve control voltage range. This guarantees an even more precise control of all valves.
Opera�on
The actua�ng drive is switched on via an electrical contact, e.g. from a room thermostat, and starts opening or
closing the thermosta�c valve. The actua�ng movement is accomplished by an electrically-heated expansion
element. When the hea�ng current is switched off, the valve closes or opens respec�vely. The HERZ actua�ng drive
is maintenance-free and offers silent opera�on.
Emergency func�on
With factory se�ng “normally closed” the valve can be opened by removing the drive in case of a power failure.
Installa�on 1 7990 31, 1 7990 32
The valve adapter assortment guarantees a perfect match of the actuator to almost all valve bo�oms and hea�ng
circuit distributors available on the market. The HERZ Actuator Propor�onal is simply plugged on to the valve
adapter previously installed manually.

All specifica ons and informa on within this document are reflecting the informa on available at the me of going to print and meant for informa onal purpose only. Herz Armaturen
reserves the right to modify and change products as well as its technical specifica ons and/or it func on according to technological progress and requirements. All diagrams are
indica ve in nature and do not to be complete. It is understood that all images of Herz products are symbolic representa ons and therefore may visually differ from the actual product.
Colours may differ due to prin ng technology used. In case of any further ques ons don’t hesitate to contact your closest HERZ Branch-Office. 31

HERZ Armaturen Ges.m.b.H 1


Richard-Strauss-Strasse 22,1230 Vienna, Austria.
Screw the adapter manually Connect the line to the Posi�on the HERZ Actuator Latch the HERZ Actuator
onto the valve. actuator. manually in ver�cal posi�on to the valve adapter by
to the valve adapter. manually applied ver�cal
pressure; this can be done
noiselessly and without
any problems.
Installa�on posi�on
The HERZ-Actuator must be installed preferably in ver�cal or horizontal installa�on posi�on. For “upside down”
installa�on special circumstances (e. g. drain water) can reduce the life�me of the actuator.

Ver�cal Horizontal Upside down


Technical data 1 7990 31, 1 7990 32
Voltage 24 V AC, -20 %... +20 %
Control voltage range 0 V… 10 V DC
Max. inrush current < 300 mA for max. 2 Min.
Opera�ng power 1. W1) (1 7990 31) / 1.2 W1) (1 7990 32)
Resistance of control voltage input 100 kΩ
Stroke 5 mm (1 7990 31) / 6.5 mm (1 7990 32)
Actua�ng force 100 N ±5% (1 7990 31) / 125 N ±5% (1 7990 32)
Fluid temperature 0 to +100°C 2)
Storage temperature -25°C to +65°C
Ambient temperature 0 to +60°C
Degree / class of protec�on IP 543) / III
CE conformity according to EN 60730
Casing material / colour Polyamid / white
Connec�on line / colour 3 x 0.22 mm² PVC / white
1) measured with precision reference instrument LMG95 - 2) in dependence of the adapter even higher - 3) in all installa�on posi�ons

All specifica ons and informa on within this document are reflecting the informa on available at the me of going to print and meant for informa onal purpose only. Herz Armaturen
reserves the right to modify and change products as well as its technical specifica ons and/or it func on according to technological progress and requirements. All diagrams are
indica ve in nature and do not to be complete. It is understood that all images of Herz products are symbolic representa ons and therefore may visually differ from the actual product.
Colours may differ due to prin ng technology used. In case of any further ques ons don’t hesitate to contact your closest HERZ Branch-Office. 31

HERZ Armaturen Ges.m.b.H 2


Richard-Strauss-Strasse 22,1230 Vienna, Austria.
Room thermostat
Standard room thermostats equipped with a thermal feedback loop can be used for pilo�ng the HERZ actua�ng
drive. If required, several drives can be connected in parallel taking the maximum admissible electrical load of the
switch contact into account.
Design and planning notes
When selec�ng the switch contacts and mains fuses, the inrush current of the hea�ng element must be taken into
account. The voltage loss in the electric lines must not exceed 10 %, ensuring that the indicated run�me is
guaranteed.
Max. cable length for an actua�ng drive with given cable cross-sec�ons (informa�on with voltage drop approx. 5 %;
at 230 V voltage drop is 10 V, at 24 V voltage drop is 1 V).
When using several actua�ng drives, the indicated cable length must be divided by the number of actua�ng drives
connected.
Cable cross-sec�on (mm2) 230 V, max. length (m) 24 V, max. length (m)

2 x 0.75 1500 168


2 x 1.0 2000 224
2 x 1.5 3000 340
2 x 2.5 5000 560

Resistance values
Please refer to the HERZ standard diagrams contained in the relevant standard sheets with regard to resistance
values when opera�ng HERZ valves with HERZ actua�ng drives. The curves "Valve fully open" or "max." apply.

Electric connec�ons 1 7990 31, 1 7990 32

Calcula�on of maximum cable length (copper cable) for 24 V rated voltage


L=CxA/n
L Cable length in m; K Constant (269 m/mm²); A Conductor cross sec�on
in mm²; n Number of Alpha-Actuators

We recommend the following cables for installing a 24 V system:


Telephone line J-Y(ST)Y 0.8 mm2
Light plas�c-sheathed cable: NYM 1.5 mm²
Flat webbed building wire: NYIF 1.5 mm²

Transformer: A safety isola�ng transformer according to EN 61558-


2-6 must always be used. Transformer dimensioning results from
the making capacity of the HERZ-Actuators.
Rule-of-thumb formula: Ptransformer = 7.2 W x n
n = Number of OEM Actuators

All specifica ons and informa on within this document are reflecting the informa on available at the me of going to print and meant for informa onal purpose only. Herz Armaturen
reserves the right to modify and change products as well as its technical specifica ons and/or it func on according to technological progress and requirements. All diagrams are
indica ve in nature and do not to be complete. It is understood that all images of Herz products are symbolic representa ons and therefore may visually differ from the actual product.
Colours may differ due to prin ng technology used. In case of any further ques ons don’t hesitate to contact your closest HERZ Branch-Office. 31

HERZ Armaturen Ges.m.b.H 3


Richard-Strauss-Strasse 22,1230 Vienna, Austria.

You might also like