Man85 VB en 36 - Rev.f

This document provides instructions for the maintenance and installation of Valbia electric actuators model VB015. It includes technical specifications, electrical connection details for 12V/24V AC/DC and 100-240V AC power supply options, and diagrams of the wiring configuration. The actuator is designed to operate ball and butterfly valves in industrial applications with a rotation time of 10 seconds from 0 to 90 degrees.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
98 views1 page

Man85 VB en 36 - Rev.f

This document provides instructions for the maintenance and installation of Valbia electric actuators model VB015. It includes technical specifications, electrical connection details for 12V/24V AC/DC and 100-240V AC power supply options, and diagrams of the wiring configuration. The actuator is designed to operate ball and butterfly valves in industrial applications with a rotation time of 10 seconds from 0 to 90 degrees.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

ELECTRIC ACTUATOR MOD. VB015 2.2 Supply data elec./consumption 4.2 Electrical connection (fig.

2)
MAINTENANCE AND INSTALLATION INSTRUCTIONS OF VALBIA ELECTRIC ACTUATORS
Electrical connection for model supplied with 12 AND 24V AC 50/60 Hz
MOD. VB015
TABLE OF CONTENTS
Nominal tension 12V ac/dc 24V ac/dc 100-240V ac • The signal cable of “closing” (clockwise rotation) must be connected to the contact “1” (terminal block “F”)
1.0 - WARNINGS Nominal torque ( Nm) 15 • The signal cable of “opening” (counter-clockwise rotation)” must be connected to the contact “2” (terminal-block “F”).
2.0 - GENERAL DATA (Lbs) 133 • The cable of “neutral” must be connected to the contact “3” (terminal-block “F”)
2.1 - TECHNICAL CHARACTERISTICS Current absorbed 1,2A 0,6A 0.3-0.19A • For supplying the heating resistor connect the contact”4” (terminal-block ”F”) as show the electric wiring
2.2 - DATA ON ELECTRICAL SUPPLY AND CONSUMPTION Absorbed power 15VA 15VA 30-46 VA
3.0 - FIELD APPLICATION Electrical connection for model supplied with 12 AND 24V DC
Frequency 50/60 Hz
4.0 - ELECTRICAL CONNECTION
4.1 - OPENING COVER OF ELECTRIC ACTUATOR Duty cycle 50% ac - 75% dc 50% ac - 75% dc 75% ac
4.2 - ELECTRICAL CONNECTION 12-24 V AC/DC Rotation time 0°-90° (sec) 10 10 10 • Connect the contact “1” to the contact “2” ( terminal block “F”)
4.3 - ELECTRICAL CONNECTION 100-240V AC • Connect the contact “1” to the contact “4” for supplying the heater.
4.4 - CONNECTION OF SIGNAL AUXILIARY WIRES TO THE LIMIT SWITCHES 3.0 Field application • To get the control of “opening ” (counter-clockwise rotation) please connect the positive pole to the contact “1” and the negative pole to the contact “3”
4.5 - WIRING DIAGRAM (terminal block “F”).
4.6 - ADJUSTMENT OF ACTUATOR STROKE VALBIA electric actuators have been designed and tested to operate ball and butterfly valves for industrial sector. Actuators are available in standard • To get the control of “closing” (clockwise rotation) please connect the negative pole to the contact “1” and the positive pole to the contact “3” (terminal block
4.7 - CLOSURE OF ELECTRIC ACTUATOR COVER “F” ).
version with rotation 0°-90°. On request we can supply actuators with rotation 0°-180°.
5.0 - EMERGENCY OPERATION
5.1 - WORKING IN EMERGENCY WITH BATTERY (OPTIONAL) For applications other than that above are needed please contact our sales department.
ATTENTION : the electric actuator VB015 has the double insulation and if supplied at 12 and 24 V AC/DC then it does not need of ground wiring system.
6.0 - MAINTENANCE
7.0 - VALVE AUTOMATION 4.0 Electrical connection
8.0 - TRANSPORT AND STOCKING
9.0 - DISPOSAL OF THE ELECTRICAL ACTUATORS AT THE END OF THEIR LIFE CYCLE The connection has be done directly into the internal part of the actuator, by passing the cable through one of the two external glands PG11 (IP68).
It is then necessary to open the upper cover in order to locate the terminal-block and the correct electronic supply. Terminal block “F”
1.0 Warnings Please pay attention to the cabling and setting phases of electromechanical limit switches in order to avoid that fluids or other substance do not get in
touch with any electronic part.
• Please read the following instructions before making any installation of the actuator Before assembling the upper cover please make sure that the o-ring is seated in the proper groove and there are no other foreign which could compromise
The damages caused from the non-observance of these instructions are not covered in the warranty. the perfect tightness of cover.
This documentation must be kept in dry place and available for use.
The installation and maintenance of electric actuator must be made only by qualified personnel. ATTENTION: Valbia electric actuators can work in any position, anyhow we do not suggest application where glandes are positioned up side-down,
• Before proceeding to the electrical connections, please make sure the ground wiring system works correctly. because this position could not guarantee a perfect tightness on glandes.
• Please always check that supply voltage is included between the ones indicated on the label on the exterior of the actuator. In case the assembling of electric actuator and the electrical connection of itself are scheduled to be made in two different moments then please take
• Before making any maintenance on the actuator, always make sure to shut off the power supply. care of the right closure of the glandes entrance.
• Valbia s.r.l. reserves the right to change the data and the characteristics of this manual at any time and with no notice in the scope of a constant updating 4 3 2 1
of technological improvement. 4.1 Opening of actuator (fig.1)
WARNING: the mechanical and electronic parts, according to which the device is designed, are not eligible for modifications.

2.0 General data Remove position indicator (B) by loosening the screw (C).
Fig.2 Plate for supply 12 and 24V AC/DC and particular of terminal block “F”
• Screw the fasteners (D) to remove the upper cover (A).
DOCUMENTATION UNIT VALUE • Raise up the cover (A) carefully to avoid to damage the internal electric
Object of device - Electric actuator parts. 4.3 Electrical connection for models with supply at 100-240V AC 50/60Hz (fig. 3 )
Protection level of cover - IP65 • Turn in the electric supply cable (diam. 5÷10 mm / 0,20÷0,40 inch) by the
Ambient temperature range °C °F -20°C ÷ 55°C -4°F ÷ +131°F properly cable gland (E)(PG11). • The signal cable of “closure (clockwise rotation)” must be connected to the input 1 of the terminal block “F”.
Rated voltage used (auxiliary contacts) V 240 Vac / 30 Vdc • Proceed to connect the cable in its proper terminal-block (F) by looking • The signal cable of “opening (counter-clockwise rotation)” must be connected to the input 2 of the terminal block “F”.
Rated current (auxiliary contacts)* A 1 A @ 240Vac - 1 A @ 30 Vdc (resistite load) at the wiring diagram (please also review the tag you find inside the cover) • The signal cable of “common” must be connected to the contact 3 of the terminal block “F ”.
according to the different voltage (see 4.2 and 4.3). • The supply cable (100-240V AC) has to be linked to the contacts 5-6.
Section of connections clamps’ conductors mm² 0,5 - 1,5
• The heating resistor is automatically powered by electronics.
Maximum torque of clamps screws’ tightening Nm Lb.In 0,5 4,43
Maximum torques of cap screws’ tightening Nm Lb.In 2,5 22,15 ATTENTION: the electric actuator VB015 has the double insulation and if supplied at 100-240V AC then it does not need of ground wiring system.
Protection class against electric shock - Class II Avoid to connect external voltages to contacts 1-2-3 of the terminal block “F”.
Blocking way of cables - Glandes PG11 (cable ∅ 0,20” ÷ 0,39”)
Action type - Type 1
Level of pollution - Level III
Category of overvoltage - III
Terminal block “F”

Product in conformity to the Community norm 2014/35/UE (LVD), 2014/30/UE (EMC).


USE 60° C/75° C COPPER (Cu) CONDUCTOR AND WIRE SIZE 14 AWG, STRANDED OR SOLID. THE TERMINAL TIGHTENING TORQUE OF (6) LB PER IN.

2.1 Technical characteristics

• The electric actuator VB015 has the heating resistor standard, always supplied.
• Both the versions of the actuators, 12-24V ac/dc and 100-240Vac, have 24V motor. If the actuator has to face a torque higher than the foreseen
maximum torque then the actuator block it self and keep a state of “stress” from the electronic circuit of power control. 1 2 3 5 6
• The options at 12V and 24V AC/DC, in case the torque go over the maximum one foreseen, are projected to block automatically the actuator by taking off
the electrical supply to the motor.
• This status keeps the electric actuator steady until a new impulse will be processed.
Fig.3 Plate of supply 100-240V AC and particular of terminal block “F”
Fig.1 External view of actuator

1 2 3

4.4 Connection of signal auxiliary wires to the limit switches (fig.4) 4.6 Adjustment of actuator stroke (fig.6) 4.7 Electric actuator case closing (fig.1)

These are 2 auxiliary contacts of limit switches (free contact SPDT) available on the terminal block “G” which is possible to connect to give signals to the The procedures to adjust the actuator stroke are as follows: • After making the proper connection, please proceed to the assembling of cover “A”, by paying close attention not to hit any electronic parts.
end user. • Re-assemble the position indicator “B” on “OPEN” blocking it by screw “C”.
• To connect to the terminal block “G” between the contacts: 1. Take care there is not electrical supply. • Make sure that the tightening of cables is secure, by screwing the gland “E”.
• “7” and “8” to get the signal of closure. 2. Remove the upper cover of the actuator (see instructions point 4). • Finish the closure of the cover “A” by screwing in the fasteners “D”.
• “11” and “12” version 12-24V ac/dc - “10 and 11” version 100-240V ac to get the signal of opening. 3. Take care that the device to be automatised (example: valve) is on “OPEN” position.
4. The electric actuator VB015 has 2 discs camsholder, the upper one “2”orders the micro limit switches to control “open” and “closed”, while the bottom 5.0 Emergency operation
one “1” orders the auxiliary limit switches used to give the signal of opening and closure. For each camsholder there is a black cam, (opening rotation)
and a white cam (closure rotation), the two cams are tighted by a screws “3”. The electric actuator VB015 has an external handwheel “B” with position indicator, by which is possible to operate manually the closing and opening
operations.
WARNING: during the installation it is reccomended to verify the alignment of the auxiliary limit switches by using a multimeter/tester. The manual operation operates by working on the external handle “H” by turning it to the position “MAN”, at this point is possible to make the manual operation
Terminal block “G”
you like by working on handhweel “B”. To return to the automatic position please turn the handle “H” to position “AUTO”.

Attention: do not operate the manual override when the actuator is working.

6.0 Maintenance

These electric actuators do not need of any format maintenance.


The internal lubrication is sufficient for the whole life of the actuator.
7 8 9 10 11 12 To get a good cleaning of the external parts, we suggest to use a light detergent with low level of chemical aggressiveness.
In case of damage or a problem in operation, we recommand that you send the actuators back to Valbia for inspection.
Valbia s.r.l. declines all responsability and warrantee on our actuators repaired from any third party

7.0 Valve automation


Fig.4 View of terminal block “G” to connect to auxiliary signals

4.5 Wiring diagram (fig.5) The mechanical assembling between the electric actuator and the item to be automated (for example: the valve) can be done by direct mounting or by a
mounting kit.
The following figure shows the wiring diagram (also it is, as tag, inside the cover) to be followed for the proper cabling to the actuators. When the limit Both the cases you can verify the right alignment and the correct dimensions of the part to transmit the power in order to avoid axial stress which can
switches POS1 and POS2 are pressed they stopped the motor and so the opening and closing operation. damage valve and actuator. All Valbia electric actuators are in conformity of norm EN ISO 5211-DIN 3337. In order to have a right automation of the valve, is
necessary to use a Valbia electric actuators whose range has a torque of at least 25% over the valve maximum torque.
WARNING: for command PIN 1-2-3 it is recommended:
• use optoisolated static impulse connection; WARNING: do not operate the manual override when the actuator is powered.
• use proper cables and precautions on the control system to minimize electromagnetic interference.
8.0 Transport and stocking

Valbia electric actuators are supplied in paperboard boxes which are of solid construction for a normal transport.
SCHEMA ELETTRICO SCHEMA ELETTRICO Please handle and keep with care the cover until the moment of the installation of the actuator.
ELECTRIC WIRING ELECTRIC WIRING The stocking of the material needs a dry and well ventilated place. Please take care also that it must be protected from temperature changes.
VB015 100-240Vac 50/60Hz VB015 12-24Vac 50/60 Hz
WARNING: do not lift or move the actuator by the manual hand-wheel.
12-24Vdc

9.0 Disposal of the electrical actuators at the end of their life cycle
ATTUATORE - ACTUATOR ATTUATORE - ACTUATOR
ATTUATORE - ACTUATOR OPEN CLOSED

M
According to the provisions of the European directives 2011/65/UE and 2012/19/UE, concerning the restriction of the use of hazardous substances in
M M electrical and electronic equipment as well as waste management, all the VALBIA electric actuators are designed in order to be completely disassembled
MICRO AUX MICRO AUX L L
when they arrive at the end of their life cycle, separating the different materials for the proper disposal and/or recovery.
COMANDO STATICO OPTOISOLATO OPEN CLOSED
STATIC IMPULSE DRIVE OPTOISOLATED
OPEN CLOSED

ELETTRONICA
The crossed-out rubbish bin symbol indicates that the product, at the end of its life cycle, becomes WEEE (Waste Electrical and Electronic
OPTOISOLATORE

DI CONTROLLO 3 2 1
OPTOISOLATOR

MICRO AUX MICRO AUX I= 6 mA 12 11 10 9 8 7 4 3 2 1 4 3 2 1 Fig. 6 . Cams of the limit switch Equipment) and must be collected separately from the other waste.
OPEN CLOSED
APRE CHIUDE
ELECTRONIC OPENING CLOSING
APRE
CONTROL OPENING
L=LIMITATORE DI COPPIA CHIUDE
L=LIMITER TORQUE CLOSING

The device must not be disposed as a mixed urban waste, it must be recycled through the proper collection system for disposal and for its subsequent
10 11 12 9 7 8 6 5 4 3 2 1 STATO DEI MICRO AUSILIARI AC
N
DC
correct recycling.
IN CONDIZIONI DI VALVOLA -(N) +(L)
L

The collection system of the equipment at the end of its life is guaranteed on the national territory through the national consortia for the eco-sustainable
APRE CHIUDE
STATO DEI MICRO AUSILIARI OPENING CLOSING
APERTA.
IN CONDIZIONI DI VALVOLA
APERTA. MICRO AUX WITH VALVE management of WEEE. For all the information contact VALBIA s.r.l.
IN OPEN POSITION
MICRO AUX WITH VALVE
IN OPEN POSITION
At the end of the life cycle of the device, for its removal, a series of precaution must be followed:
N
L • the structure and the various components, if not usable, must be demolished and divided up according to the type of product. All this helps collection,
disposal and recycling centers and minimizes the environmental impact that this operation requires;
• appropriate separate waste collection for subsequent sending of the disused equipment for recycling, treatment and compatible environmental disposal
contributes to preventing possible negative effects on the environment and favors recycling of the materials of which the equipment is composed;
• the illegal disposal of the product by the user involves the application of the penalties provided by the current regulations regarding such subject.

The product at the end of its life, if properly disposed, is not potentially dangerous for human health and the environment, on the contrary, if unproperly
Fig. 5 Electric wiring diagram to cable the actuators abandoned, it could have a negative impact on the ecosystem.
4 5 6

VALBIA S.r.l. - Via Industriale, 30 - 25065 Lumezzane S.S. (Brescia) Italy - Tel. +39 030 8969411 - Fax +39 030 8610014 - www.valbia.it - E-mail valbia@bonomi.it Instruction 90004000036 rev. F